The data listed above is approximate and subject to change without notice. Single Conductor DLO • Industrial Motor Lead Cable 14 AWG - 777 KCMIL • 1000 Volts • 90°C Applications These cables were designed for use as motor and power leads where flexi- bility and portability are required. DLO cables are also suitable for use in wiring diesel-electric locomotives, railroad and transit cars, earth moving equipment, offshore drilling rigs, storage batteries, charging equipment and in sizes 1/0 AWG and larger, flexible wiring for installation in conduit or tray per the NEC. Construction Conductor: Class I stranded, tin coated annealed copper per ASTM B-33 and B-172. Separator: A suitable opaque separator tape shall be used over the con- ductor to facilitate stripping. Insulation and Jacket: Black, heavy duty, oil-resistant chlorosulfonated polyethylene (CSPE). Other colors available upon special request. Print Legends: The surface of the jacket shall be printed using white ink and with the following information: Sizes 14 AWG through 1 AWG: “(size) AWG CSPE 1000 VOLTS A.I.W. CORP.” Sizes 1/0 AWG and larger: “(size) AWG (or KCMIL) CSPE Diesel Locomotive Cable 1000 VOLTS IEEE 383---USE or RHH or RHW VW-1 600V. SUN RES FOR CT USE (UL)---A.I.W. CORP.---CSA(Size KCMIL where applicable) AWM I B 90°C 600V FT4---” Note: 262 KCMIL and larger are marked at the next lowest CSA recognized size. (Example: 262 is CSA 250, etc.) 31041 14 19 .070 .060 .200 35 32 30872 12 19 .090 .060 .220 40 42 13570 10 27 .123 .060 .240 55 58 13571 8 37 .156 .080 .325 80 85 13572 6 61 .186 .080 .355 105 126 13573 4 105 .235 .080 .405 140 190 13575 2 147 .315 .080 .490 190 257 13577 1 224 .370 .095 .585 220 386 13578 1/0 273 .405 .095 .620 260 455 13579 2/0 324 .445 .095 .660 300 532 13580 3/0 448 .535 .095 .745 350 714 13581 4/0 532 .545 .095 .800 405 850 13582 262 646 .640 .110 .880 470 1014 13583 313 775 .710 .110 .950 510 1206 13585 373 925 .760 .110 1.000 590 1405 13587 444 1110 .835 .110 1.075 655 1662 13588 535 1332 .870 .125 1.150 730 2016 - 646 1591 .955 .125 1.230 815 2365 13590 777 1924 1.020 .125 1.290 905 2821 Part Number Size AWG or KCMIL Stranding Conductor O.D. (Inches) Insulation Thickness (Inches) Nominal O.D. (Inches) Amps 1 Ship Wt. Lbs./M Ft. 1 Ampacities (amps per conductor) are based on single conductor in free air, 30°C ambient air temperature, 90°C conductor temperature per Table 310.17 of the 2008 NEC. MSHA listed OSHA accepted ES05216 AMERICAN INSULATED WIRE CORP. | 260 Forbes Blvd. | Mansfield, MA 02048 | 1-800-366-2492 Tin Coated
Transcript
Page 1: Dlo cables

The data listed above is approximate and subject to change without notice.

Single Conductor DLO • Industrial Motor Lead Cable14 AWG - 777 KCMIL • 1000 Volts • 90°C

ApplicationsThese cables were designed for use as motor and power leads where flexi-bility and portability are required. DLO cables are also suitable for use inwiring diesel-electric locomotives, railroad and transit cars, earth movingequipment, offshore drilling rigs, storage batteries, charging equipment andin sizes 1/0 AWG and larger, flexible wiring for installation in conduit or trayper the NEC.ConstructionConductor: Class I stranded, tin coated annealed copper per ASTM B-33and B-172.Separator: A suitable opaque separator tape shall be used over the con-ductor to facilitate stripping.Insulation and Jacket: Black, heavy duty, oil-resistant chlorosulfonatedpolyethylene (CSPE). Other colors available upon special request.Print Legends: The surface of the jacket shall be printed using white inkand with the following information:Sizes 14 AWG through 1 AWG: “(size) AWG CSPE 1000 VOLTS A.I.W.CORP.”Sizes 1/0 AWG and larger: “(size) AWG (or KCMIL) CSPE DieselLocomotive Cable 1000 VOLTS IEEE 383---USE or RHH or RHW VW-1600V. SUN RES FOR CT USE (UL)---A.I.W. CORP.---CSA (Size KCMILwhere applicable) AWM I B 90°C 600V FT4---”Note: 262 KCMIL and larger are marked at the next lowest CSA recognizedsize. (Example: 262 is CSA 250, etc.)

31041 14 19 .070 .060 .200 35 3230872 12 19 .090 .060 .220 40 4213570 10 27 .123 .060 .240 55 5813571 8 37 .156 .080 .325 80 8513572 6 61 .186 .080 .355 105 12613573 4 105 .235 .080 .405 140 19013575 2 147 .315 .080 .490 190 25713577 1 224 .370 .095 .585 220 38613578 1/0 273 .405 .095 .620 260 45513579 2/0 324 .445 .095 .660 300 53213580 3/0 448 .535 .095 .745 350 71413581 4/0 532 .545 .095 .800 405 85013582 262 646 .640 .110 .880 470 101413583 313 775 .710 .110 .950 510 120613585 373 925 .760 .110 1.000 590 140513587 444 1110 .835 .110 1.075 655 166213588 535 1332 .870 .125 1.150 730 2016

- 646 1591 .955 .125 1.230 815 236513590 777 1924 1.020 .125 1.290 905 2821

PartNumber

SizeAWG orKCMIL Stranding

ConductorO.D.

(Inches)

InsulationThickness(Inches)

NominalO.D.

(Inches) Amps1Ship Wt.

Lbs./M Ft.

1Ampacities (amps per conductor) are based on single conductor in free air, 30°C ambient air temperature, 90°C conductor temperature per Table310.17 of the 2008 NEC.

MSHA listedOSHA accepted

ES05216

AMERICAN INSULATED WIRE CORP. | 260 Forbes Blvd. | Mansfield, MA 02048 | 1-800-366-2492

Tin Coated

Page 2: Dlo cables

The data listed above is approximate and subject to change without notice.

ApplicationsThese cables were designed for use as motor and power leads where flexibility,reduced diameter and portability are required. DLO cables are also suitable foruse in wiring diesel-electric locomotives, railroad and transit cars, earth movingequipment, drilling rigs, storage batteries, charging equipment and flexible wiringfor installation in open air, trays (1/0 and larger) or conduit per the N.E.C.Passes cold bend and impact at -40˚C.ConstructionConductor: Tin-coated annealed copper per ASTM B-33 and B-172 or B-174.Separator (Sizes 4 AWG and larger only): A suitable opaque separator tapeshall be used over the conductor to facilitate stripping.Insulation: Ethylene propylene rubber (EPR) conforming to UL-1581 for ClassEP Table 50.42, UL-44 requirements for RHH and RHW-2, ASTM D-2270 andICEA S-95-658, Class E-1. It shall be suitable for conductor temperatures up to90˚C in wet or dry locations for continuous use, 130˚C for emergency overloads,and 250˚C for short circuits.Jacket: Heavy-duty chlorosulfonated polyethylene (CSPE) conforming to ICEAS-95-658, Par. 4.1.11 and UL-1581 Table 50.1.Print Legends: The surface of the jacket shall be printed using white ink andwith the following information:14 AWG thru 1 AWG: “Size AWG Type RHH or RHW-2 2kV -40˚C VW-1 Sun Res (UL)(E No.)---A.I.W. Corp.---CSA LL8825 RW90 EP/Jkt 1kV -40˚C Oil Res TC FT1---EPR/CSPE2kV Diesel Locomotive Cable P-7K-No.-MSHA”

1/0 AWG thru 1111 KCMIL: “Size AWG (or KCMIL) Type RHH or RHW-2 2kV-40˚C Sun Res for CT use FT4/IEEE-1202 (UL) (E No.)---A.I.W. Corp.---CSA LL8825 (size printed here on 250 & larger only)Type RW90 EP/Jkt -40˚C Oil Res TC 1kV FT4---EPR/CSPE 2kV Diesel Locomotive Cable P-7K-No.-MSHA”

Note: 262 KCMIL and larger are marked at the next lowest CSA recognized size. (Example: 262 is CSA 250, etc.)

Single Cond. DLO • Industrial Motor Lead Cable • Lead-Free14 AWG - 1111 KCMIL • 2000 Volts • 90˚C

67431 14 19 .070 .045 .015 .205 35 3067432 12 19 .090 .045 .015 .225 40 4067433 10 27 .123 .045 .015 .255 55 5767434 8 41 .156 .055 .030 .335 80 9367435 6 65 .186 .060 .030 .380 105 13367436 4 105 .235 .060 .030 .440 140 20367437 2 168 .315 .060 .030 .520 190 30267438 1 224 .370 .080 .045 .645 220 43467439 1/0 273 .405 .080 .045 .675 260 50667440 2/0 324 .445 .080 .045 .715 300 56767441 3/0 448 .540 .080 .045 .810 350 75267442 4/0 532 .545 .080 .045 .815 405 78367443 262 646 .640 .090 .065 .980 470 109367444 313 775 .710 .090 .065 1.040 510 128367445 373 925 .760 .090 .065 1.095 590 149267446 444 1110 .835 .090 .065 1.165 655 175567447 535 1332 .870 .090 .065 1.200 730 205367448 646 1591 .955 .090 .065 1.285 815 241067449 777 1924 1.020 .090 .065 1.355 905 286167478 929 2318 1.180 .090 .065 1.520 1005 357567477 1111 2745 1.310 .115 .095 1.770 1115 4214

PartNumber

SizeAWG orKCMIL Stranding

ConductorO.D.

(Inches)

InsulationThickness(Inches)

JacketThickness(Inches)

NominalO.D.

(Inches) Amps1Ship Wt.

Lbs./M Ft.

1Ampacities (amps per conductor) are based on single conductor in free air, 30˚C ambient air temperature, 90˚C conductor temperature per Table 310.17 of the 2008NEC.

MSHA listedOSHA accepted

ES16744

AMERICAN INSULATED WIRE CORP. | 260 Forbes Blvd. | Mansfield, MA 02048 | 1-800-366-2492

Page 3: Dlo cables

The data listed above is approximate and subject to change without notice.

Single Conductor DLO • Marine Shipboard Cable • Lead-Free8 AWG - 1111 KCMIL • 2000 Volts • 90˚C

ApplicationsThese cables were designed for use as motor and power leads where flexibilityand portability are required. DLO cables are also suitable for use in wiringdiesel-electric locomotives, railroad and transit cars, earth moving equipment,offshore drilling rigs, storage batteries, charging equipment and flexible wiringfor installation in open air or conduit per the CEC. Passes cold bend and impactat -40˚C.

ConstructionConductor: Class I stranded, tin-coated annealed copper per ASTM B-33 andB-172.Separator: A suitable opaque separator tape shall be used over the conductorto facilitate stripping.Insulation: Ethylene propylene rubber (EPR) conforming to UL-1309 Type E90(0-2kV) and CSA C22.2 No. 38 requirements. It shall be suitable for conductortemperatures up to 90˚C in wet or dry locations for continuous use, 130˚C foremergency overloads and 250˚C for short circuits.Jacket: Heavy-duty black CSPE conforming to ICEA S-95-658 Par. 4.1.11 and1309 Type CP requirements.Print Legends: The surface of the jacket shall be printed using white ink andwith the following information: “DLO (size) AWG (or KCMIL) 2kV E86047 (UL)Marine Shipboard Cable 90˚C (year)---A.I.W. Corp. P-7K-122015 MSHA---Type

---CSA monogram)LL8825 RW-90 EP 1kV (-40˚C) EP/JKT Oil Res.TC FT1”

Notes:For sizes 1/0 AWG and larger add “For CT Use FT4/ IEEE 1202” after “Sun Res” and substitute “FT4” for “FT1.”

For sizes 262.6 KCMIL and larger add the CSA cable size after “RW-90 EP ” and omit “VW-1.”

CSA cables sizes are rounded off to the next lowest qualifying size. Example: 262.6 KCMIL is CSA size 250 KCMIL.

39009 8 41 .156 .055 .045 .375 80 9539008 6 65 .186 .060 .045 .405 105 14539007 4 105 .235 .060 .045 .460 140 21339006 2 168 .315 .060 .060 .575 190 27739005 1 224 .370 .080 .060 .675 220 43739004 1/0 273 .405 .080 .060 .705 260 51439245 2/0 324 .445 .080 .060 .745 300 59239003 3/0 448 .540 .080 .080 .880 350 78238847 4/0 532 .545 .080 .080 .885 405 91138962 262 646 .640 .090 .080 1.010 470 114638846 313 775 .710 .090 .080 1.070 510 136238845 373 925 .760 .090 .080 1.120 590 159438963 444 1110 .835 .090 .080 1.195 655 188238826 535 1332 .870 .090 .080 1.235 730 222639002 646 1591 .955 .090 .080 1.320 815 262938827 777 1924 1.020 .090 .080 1.385 905 3119

- 929 2318 1.180 .090 .080 1.550 1005 3754- 1111 2425 1.310 .110 .110 1.780 1115 4478

PartNumber Size Stranding

ConductorO.D.

(Inches)

InsulationThickness(Inches)

JacketThickness(Inches)

NominalO.D.

(Inches) Amps1Ship Wt.

Lbs./M Ft.

1Ampacities (amps per conductor) are based on single conductor in free air, 30˚C ambient air temperature, 90˚C conductor temperature per Table 310.17 of the 2008 NEC.

MSHA listedOSHA accepted

ES16273

AMERICAN INSULATED WIRE CORP. | 260 Forbes Blvd. | Mansfield, MA 02048 | 1-800-366-2492

Tin Coated

RHH or RHW-2 2kV (-40˚C) VW-1 Sun Res (UL) E18321


Recommended