Vito ALUNNO ROSSETTI, Antonella FERRARO
Do thermal cracks of concrete columns close on cooling ?
Due to the heat of hydration generated by cement in concrete and the consequent warming and cooling of
structural elements, various types of cracks can develop1.
In wall type elements, vertical cracks form on cooling, generally in the first week after casting and not
wider than 0.8 mm, sometimes passing, not always reaching the wall top. Such cracks tend to widen in
time, due to the drying shrinkage.
Figure 1 a - Cracks on a concrete wall at two months since the casting. Water
passage and salt crystallization is visible since 2 days from the casting
Figure 1 b – A special wall: 1.7 m in heigth, 8 meters wide, 30 m in length,
same type of cracks has been observed
In column type elements, the cracks form on warming, due to the temperature distribution (warmer in the
core and colder in the cortical layers). The inner column core in the presence of the outer concrete layers,
1 Vito ALUNNO ROSSETTI “Il Calcestruzzo – Materiali e tecnologia”, Ed. McGraw & Hill, Terza Edizione, Milano 2007, pag. 226
clinicadelcalcestruzzo
clinicadelcalcestruzzo
2
ww
w.c
lin
ica
de
lca
lce
stru
zzo
.it
finds an obstacle to dilatation, both in the horizontal and in the vertical direction) so it is compressed; the
contrary happens for the cortical zone where a tensile stress develops .
Column section
Figure 2 - Thermal expansion crack on a massive concrete
column at six days
Figura 3 – At the crossing of the
green and blue lines a no-stress
zone is present
A FEM calculation for a 35 MPa concrete gives an idea of the situation at short term, generating horizontal
and vertical cracks.
Figura 4- FEM Thermal and
tensional analysis. Tension
distribution at 45 h (when the
maximum tensile stress of
the used concrete is reached).
Compression is negative.
The stresses have a vertical
direction; circular horizontal
and linear vertical cracks are
formed.
A question seems to be reasonable: when the inner core of the column loses heat and starts to cool,
producing a thermal contraction, is it possible that also the cortical outer cylinder of the column contracts
and “shrinks” and a closing (at least partial) of the cracks can be noticed?
First of all, an answer can be found by intuition. It is evident that when the core (still compressed) cools,
the outer concrete cannot contract (excluding the elastic contraction in compression) because its form is an
arc; it will lose the residual initial tensile stress and will go in a compression state. Having also lost on
hardening most of the initial creep ability, such a compression will not cause the closing of the vertical
cracks. In time, the drying shrinkage will cause a widening of the cracks.
Being this the case, some tensile stress can be imagined at the internal boundary between the outer and
the inner cylinder, due to the impossibility of the former to follow the contraction of the latter.
Compression
zone
Tensile zone
Temperature
Distribution
No-stress
line
Clinicadelcalcestruzzo
Clinicadelcalcestruzzo
3
ww
w.c
lin
ica
de
lca
lce
stru
zzo
.it
A fem analysis at 200 hours of the same column confirms the idea. Between the compressed annular
outer zones and the still compressed core zone, a circular tensile zone is evident.
Figure 5 - A inner annular
tensile zone is evident
On the basis of the preceding considerations, the interpretation of an initially rather obscure experimental
result has become possible.
Figure 6 - Sonic tomography after 5 months. Visible
cracks on the surface in correspondence of
blue spots.
The yellow internal annular zone, is
presumably due to some damage of the
concrete originated by the local existence of
tensile stresses on cooling of the column.
The yellow annular inner zone confirms a damage of the concrete, due to the presence of a tensile zone.
Clinicadelcalcestruzzo