NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Inspection Type Last EditedTime InInspectionId
DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452School:
1377 2019-01-11 07:02AM 2019-06-27 04:06PMARCHITECTURAL - SENIOR
1464 2019-01-11 09:09AM 2019-06-06 03:08PMARCHITECTURAL - ASSOCIATE
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? Yes
Principal(s) Information
Principal Name Jacqueline Radoslovich
Principal Organization P.S. 555 - Bronx (Mont Eden Children’s Academy )
Meeting with Principal? Yes
Principal Feedback The Principal provided the following comment; The Heat / AC is
not working properly, and needs repairs.
Principal Name Christopher Reda
Principal Organization X010 SPED
Meeting with Principal? Yes
Principal Feedback The Principal provided the following comment; The Heat / AC is
not working properly, and needs repairs.
Principal Name Alixandre Ricci
Principal Organization I.S. 327 - Bronx
Meeting with Principal? Yes
Principal Feedback The Principal provided the following comment; The Heat / AC is
not working properly, and needs repairs.
Custodian Was not present
Fireman Kevin Alejo
Building Square Footage 170,100
Comments on the Area (Square Feet) N / A
Comments on the Stories (Floors) plus Basements 4+B+PH
Comments on the Year Built 2012
Comments on the Student Population 1221
Comments on the Staff Population 198
Comments on the Number of Classrooms 48
Weather Fair
Facade Photo
Jerome Avenue - Southwest view
Page 1 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural InspectionMain Entrance Photo
Facade A - Jerome Avenue
Roof Photo
Roof 1 - North View
No System UpgradedHave any Systems/Major Building Components been upgraded?
Have there been any New Building Additions? No New Construction
Tandem No Tandem
Leased Space? No
Priority ConditionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Accessibility
Accessibility Status Question Response
Physical Breakdown Structure Exists Complies Required Deficiency
FUNCTIONAL ACCESSIBILITY
Exterior Routes
YesExterior Entrances & Exits
NoNoExterior H/C Lifts
NoYesExterior Ramps and Railings
Interior Routes
Page 2 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Physical Breakdown Structure Exists Complies Required Deficiency
NoNoCorridor and Lobby H/C Lifts
NoYesInterior Corridor Doors And Hardware
YesInterior Corridors & Lobbies
YesYesInterior Elevators
YesInterior Lobby Doors And Hardware
YesYesInterior Ramps
Rooms & Spaces
Art Rooms
Yes YesRoom 248, 250
Auditorium
Yes Yes2nd Floor
Cafeteria
Yes YesBasement
Classrooms
Yes YesBasement - 4th Floor
Computer Rooms
Yes YesRoom B23, 260
Gymnasium
Yes YesBasement
Library
Yes YesRoom 203
Main Office
Yes YesRoom 119 (Mont Eden Children
Academy), 220 (X010 SPED), 413 ( I.S.
327)
Multi-purpose Room
Yes YesBasement and 2nd Floor
Nurse's Office
Yes YesRoom 221, 306
Pool
Yes YesBasement
Science Lab
Yes YesRoom 147, 403, 406, 419
Toilet Rooms (boys)
Yes YesBasement-4th Floor
Toilet Rooms (girls)
Yes YesBasement- 4th Floor
Toilet Rooms (staff)
Yes YesBasement-4th Floor
Page 3 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
EXTERIOR Inspected
Does not existAREAWAY
Does not existAWNINGS AND CANOPIES
Does not existCHIMNEY
InspectedCOPING
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCORNICE
InspectedDOORS
InspectedDOOR HARDWARE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTRANSOM/SIDE LIGHT
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedEXTERIOR SOFFITS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedEXTERIOR WALLS
Masonry, SteelMaterial Type(s)
34,540Replacement Quantity
Replacement Uom S.F.
Instance on All Facades Inspected
2- Between Good and FairInstance Condition
Instance Quantity 34,540
Page 4 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Instance Quantity Uom S.F.
No deficiencies recordedDeficiency
Does not existLOADING DOCK
InspectedLOUVER
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedPARAPETS
ConcreteMaterial Type(s)
4,935Replacement Quantity
Replacement Uom C.F.
Instance on All Facades Inspected
2- Between Good and FairInstance Condition
Instance Quantity 4,935
Instance Quantity Uom CF
No deficiencies recordedDeficiency
InspectedPLAZA DECK
Instance on Pavers:Roof 5 Inspected
2- Between Good and FairInstance Condition
Instance Quantity 4,000
Instance Quantity Uom S.F.
Installation Year 2012
Source of Installation Year Documented
No deficiencies recordedDeficiency
InspectedROOF
InspectedROOFING
Replacement Quantity 50,300
Replacement Uom S.F.
InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existROOF BARRIER
Does not existROOF CAGE
Does not existROOF FENCE
InspectedROOF HATCH/SMOKE HATCH
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOFING
Instance on IRMA:Roof 1 - 4 and 6 Inspected
3- FairInstance Condition
Instance Quantity 50,300
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2012
Source of Installation Year Documented
IRMA:ROOFING:MINOR LEAKAGEDeficiency
Deficiency Location/Instance
Page 5 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
500Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
4th Floor Corridor
Deficiency Photo 2
Staircase G
Violations No violations recorded
InspectedROOFING DRAINS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedSPECIALTIES
InspectedBULKHEAD/PENTHOUSE
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existCUPOLA/ SPIRES/ TOWERS
Does not existDORMER
Does not existDUNNAGE STEEL
Does not existROOF/GRAVITY TANK
InspectedSKYLIGHT/ROOF VENT
Material Type(s) Glass
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedBUILDING CHEEK/FLANK WALLS
Condition 3- Fair
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MINORDeficiency
Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Page 6 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade D
Deficiency Photo 2
Facade D
Violations No violations recorded
InspectedRAILINGS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedSTAIRS/RAMPS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWINDOWS
5,100Replacement Quantity
Replacement Uom S.F.
InspectedEXTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWINDOWS
Material Type(s) Aluminum
Instance on Aluminum - Other:All Facades Inspected
2- Between Good and FairInstance Condition
Instance Quantity 5,100
Instance Quantity Uom S.F.
Installation Year 2012
Source of Installation Year Documented
No deficiencies recordedDeficiency
INTERIOR Inspected
AUDITORIUM
Instance on 2nd Floor (412 Seats ) Inspected
Ceiling
Instance on 2nd Floor (412 Seats ) Inspected
2- Between Good and FairInstance Condition
Page 7 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
AUDITORIUM
Ceiling
GYPSUM BOARD:DAMAGED/DETERIORATEDDeficiency
Left Aisle Near EntranceDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Left Aisle Near Entrance
Violations No violations recorded
Door(s)
Instance on 2nd Floor (412 Seats ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed H/C Lift
Instance on 2nd Floor (412 Seats ) Does not exist
Fixed Seating
Instance on 2nd Floor (412 Seats ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 2nd Floor (412 Seats ) Inspected
2- Between Good and FairInstance Condition
CONCRETE:CRACKSDeficiency
Near Seats A/101, 104, 105, 108, B/102Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Seat A/101
Violations No violations recorded
Sliding-folding Partition
Instance on 2nd Floor (412 Seats ) Does not exist
Stage
Instance on 2nd Floor (412 Seats ) Inspected
Stage
Page 8 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
AUDITORIUM
Stage
Stage
Instance on 2nd Floor (412 Seats ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtain Rigging
Instance on 2nd Floor (412 Seats ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtains
Instance on 2nd Floor (412 Seats ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on 2nd Floor (412 Seats ) Inspected
2- Between Good and FairInstance Condition
WOOD PANELING:DETERIORATEDDeficiency
Near Entrance, Right Side of AuditoriumDeficiency Location/Instance
140Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Entrance
Violations No violations recorded
Window Curtains/Shades/Blinds
Instance on 2nd Floor (412 Seats ) Does not exist
CAFETERIA
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on Basement Does not exist
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Page 9 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
CAFETERIA
Sliding-folding Partition
Instance on Basement Does not exist
Stage
Instance on Basement Does not exist
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on Basement Does not exist
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 2- Between Good and Fair
ACOUSTIC TILES:DAMAGED/MISSINGDeficiency
Room 262Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 262
Violations No violations recorded
TECTUM:DAMAGED/MISSING - ACTIVE LEAKDeficiency
Corridor Near Rooms 411, 419, 423Deficiency Location/Instance
85Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor Near Room 411
Violations No violations recorded
GYPSUM BOARD:DAMAGED/DETERIORATEDDeficiency
Near Rooms B18, 121, 125, 203, 415 and other LocationsDeficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
Page 10 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Room 415
Violations No violations recorded
GYPSUM BOARD:DAMAGED/DETERIORATED - ACTIVE
LEAK
Deficiency
Corridor Near Room 417Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor Near Room 417
Violations No violations recorded
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
TERRAZZO:CRACKSDeficiency
Near Room 144Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Room 144
Violations No violations recorded
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
Page 11 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Near Room 268Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Room 268
Violations No violations recorded
InspectedSpecialties
InspectedClassroom Locker(s)
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existFixed Seating
InspectedWalls
Condition 2- Between Good and Fair
CERAMIC TILE:BROKEN/ MISSINGDeficiency
Corridor Near Room 147Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor Near Room 147
Violations No violations recorded
GYPSUM BOARD:DETERIORATEDDeficiency
Corridor Near Rooms 220, 259, 329A, 427Deficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 12 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Deficiency Photo 1
Corridor Near Room 427
Violations No violations recorded
GYMNASIUM
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
CERAMIC TILE:BROKEN/MISSING TILESDeficiency
Near Drinking FountainDeficiency Location/Instance
15Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Drinking Fountain
Violations No violations recorded
Seating
Instance on Basement Inspected
2- Between Good and FairInstance Condition
DAMAGED BLEACHERSDeficiency
Near WindowsDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
Page 13 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
GYMNASIUM
Seating
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Windows
Violations No violations recorded
Sliding-folding Partition
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage
Instance on Basement Does not exist
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
WALL PADDING:DETERIORATEDDeficiency
Near Room B06C, WindowsDeficiency Location/Instance
120Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Room B06C
Violations No violations recorded
Window Curtains/Shades/Blinds
Instance on Basement Does not exist
InspectedINTERIOR DOOR HARDWARE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedINTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
KITCHEN
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
Page 14 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
KITCHEN
Ceiling
No deficiencies recordedDeficiency
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
LIBRARY
Instance on Room 203 Inspected
Built-in Furnishing
Instance on Room 203 Does not exist
Ceiling
Instance on Room 203 Inspected
2- Between Good and FairInstance Condition
GYPSUM BOARD:DAMAGED/DETERIORATEDDeficiency
Center of RoomDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Center of Room
Violations No violations recorded
Door(s)
Instance on Room 203 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Room 203 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Room 203 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
LOCKER ROOM
Instance on Room B60 - Boys (150 Lockers) Inspected
Page 15 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
LOCKER ROOM
NoAlternative Use
Instance on Room B46 - Girls (160 Lockers ) Inspected
NoAlternative Use
Instance on Room B45 - Visitors (141 Lockers ) Inspected
NoAlternative Use
Instance on Room B67 (88 Lockers ) Inspected
NoAlternative Use
Instance on Room B71 (50 Lockers ) Inspected
NoAlternative Use
Instance on Room B73 (57 Lockers ) Inspected
NoAlternative Use
Ceiling
Instance on Room B60 - Boys (150 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B46 - Girls (160 Lockers ) Inspected
2- Between Good and FairInstance Condition
GYPSUM BOARD:DAMAGED/DETERIORATEDDeficiency
Near ShowerDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Shower
Violations No violations recorded
Instance on Room B45 - Visitors (141 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B67 (88 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B71 (50 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B73 (57 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Room B60 - Boys (150 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B46 - Girls (160 Lockers ) Inspected
2- Between Good and FairInstance Condition
Page 16 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
LOCKER ROOM
Door(s)
No deficiencies recordedDeficiency
Instance on Room B45 - Visitors (141 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B67 (88 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B71 (50 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B73 (57 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Room B60 - Boys (150 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B46 - Girls (160 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B45 - Visitors (141 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B67 (88 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B71 (50 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B73 (57 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Locker Room Lockers
Instance on Room B60 - Boys (150 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B46 - Girls (160 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B45 - Visitors (141 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B67 (88 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B71 (50 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B73 (57 Lockers ) Inspected
2- Between Good and FairInstance Condition
Page 17 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
LOCKER ROOM
Locker Room Lockers
No deficiencies recordedDeficiency
Walls
Instance on Room B60 - Boys (150 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B46 - Girls (160 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B45 - Visitors (141 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B67 (88 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B71 (50 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room B73 (57 Lockers ) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
MULTI-PURPOSE ROOM
Instance on 2nd Floor Inspected
Instance on Basement Inspected
Ceiling
Instance on 2nd Floor Inspected
2- Between Good and FairInstance Condition
ACOUSTIC TILES:DAMAGED/MISSINGDeficiency
Near Room 263Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Room 263
Violations No violations recorded
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 2nd Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Basement Inspected
Page 18 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Door(s)
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on 2nd Floor Does not exist
Instance on Basement Does not exist
Floor Finish
Instance on 2nd Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on 2nd Floor Inspected
5- PoorInstance Condition
MOTOR:INOPERABLEDeficiency
Center of the RoomDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Violations No violations recorded
Instance on Basement Does not exist
Stage
Instance on 2nd Floor Does not exist
Instance on Basement Does not exist
Walls
Instance on 2nd Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 2nd Floor Does not exist
Instance on Basement Does not exist
InspectedPOOLS
BasementInstance
CEILING
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
DECK/FLOOR
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
DIVING BOARD
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Page 19 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
POOLS
POOL LINING
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
ROOF STRUCTURE
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
SEATING
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
WALLS
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existSCIENCE DEMO ROOM
SCIENCE LAB
Instance on Rooms 147, 403, 419 Inspected
NoAlternative Use
Instance on Room 406 Inspected
NoAlternative Use
Fixed Equipment
Instance on Rooms 147, 403, 419 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room 406 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
SCIENCE PREP ROOM
Instance on Rooms 145, 401 Inspected
NoAlternative Use
Fixed Equipment
Instance on Rooms 145, 401 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
SHOWER ROOM
Instance on Inside Room B60 - Boys Inspected
YesAlternative Use
Instance on Inside Room B46 - Girls Inspected
YesAlternative Use
Instance on Inside Room B45 - Visitors Inspected
YesAlternative Use
Instance on Inside Room B67 Inspected
NoAlternative Use
Instance on Inside Room B71 Inspected
NoAlternative Use
Instance on Inside Room B73 Inspected
NoAlternative Use
Ceiling
Instance on Inside Room B60 - Boys Inspected
Page 20 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
SHOWER ROOM
Ceiling
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B46 - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B45 - Visitors Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B67 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B71 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B73 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Inside Room B60 - Boys Does not exist
Instance on Inside Room B46 - Girls Does not exist
Instance on Inside Room B45 - Visitors Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B67 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B71 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B73 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Inside Room B60 - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B46 - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B45 - Visitors Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B67 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B71 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B73 Inspected
2- Between Good and FairInstance Condition
Page 21 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
SHOWER ROOM
Floor Finish
No deficiencies recordedDeficiency
Walls
Instance on Inside Room B60 - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B46 - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B45 - Visitors Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B67 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B71 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Inside Room B73 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
InspectedSTAIRS/RAMPS: INTERIOR
Do Letter Stair Signs Exist? 1
InspectedCeiling
Condition 2- Between Good and Fair
GYPSUM BOARD:DAMAGED/DETERIORATED - ACTIVE
LEAK
Deficiency
Stair G/2Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair G/2
Violations No violations recorded
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existPartition
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStairs and Landings
Condition 2- Between Good and Fair
Page 22 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
MASONRY:CRACKS/SPALLINGDeficiency
Stair C/1Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair C/1
Violations No violations recorded
InspectedSTRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFLOOR STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFOUNDATION WALLS
Material Type(s) Concrete
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedROOF STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existVAULTS-BUNKERS
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existStalls
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTOILET ROOMS - STUDENTS
InspectedCeiling
Page 23 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Ceiling
Condition 2- Between Good and Fair
GYPSUM BOARD:DAMAGED/DETERIORATEDDeficiency
Room 314Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 314
Violations No violations recorded
GYPSUM BOARD:DAMAGED/DETERIORATEDDeficiency
Room 268Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 268
Violations No violations recorded
InspectedDoor(s)
Condition 5- Poor
METAL:MISSING DOORDeficiency
Rooms B14, 142, 242Deficiency Location/Instance
3Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 242
Page 24 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Door(s)
Violations No violations recorded
WOOD:DETERIORATED DOORDeficiency
Room 231Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 231
Violations No violations recorded
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
GYPSUM BOARD:DETERIORATED - ACTIVE LEAKDeficiency
Room 268Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 268
Violations No violations recorded
LIFE SAFETY Inspected
Does not existF.D. HOLDING AREA
Does not existSTEEL STAIRS
SITE Inspected
Does not existCONTAINERIZATION
InspectedDRAINAGE SYSTEM FOR ASPHALT
InspectedCatch Basins/Manhole - Surrounded by Asphalt
Condition 2- Between Good and Fair
Page 25 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
SITE
DRAINAGE SYSTEM FOR ASPHALT
Catch Basins/Manhole - Surrounded by Asphalt
No deficiencies recordedDeficiency
Does not existCulverts - Asphalt Covering
Does not existDRAINAGE SYSTEM FOR CONCRETE
Does not existDRAINAGE SYSTEM FOR SOIL
Does not existDRINKING FOUNTAINS
InspectedFENCES
Condition 2- Between Good and Fair
CONCRETE CURB:DAMAGED/DETERIORATEDDeficiency
Along West 172nd StreetDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along West 172nd Street
Violations No violations recorded
Does not existIRRIGATION SYSTEM
InspectedPAVING
InspectedDOT Sidewalk
Does not existAsphalt
InspectedConcrete
3- FairCondition
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
Along West 172nd Street, Along Jerome AvenueDeficiency Location/Instance
475Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along West 172nd Street
Violations No violations recorded
Does not existPavers
InspectedSite Sidewalks & Walkways
InspectedAsphalt
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Page 26 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
SITE
PAVING
Site Sidewalks & Walkways
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedPavers
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedStudent Non-Use
Gravel Exists? No
InspectedAsphalt
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existPavers
InspectedStudent Use
Gravel Exists? No
InspectedAsphalt
3- FairCondition
CRACKS - MAJORDeficiency
SchoolyardDeficiency Location/Instance
180Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Schoolyard
Violations No violations recorded
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existPavers
InspectedPLAYGROUNDS
North of SchoolyardInstance
South of SchoolyardInstance
Benches
Instance on North of Schoolyard Does not exist
Instance on South of Schoolyard Does not exist
Fence
Instance on North of Schoolyard Does not exist
Instance on South of Schoolyard Does not exist
Pavement
Instance on North of Schoolyard Does not exist
Page 27 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
SITE
PLAYGROUNDS
Pavement
Instance on South of Schoolyard Does not exist
Play Equipment
Instance on North of Schoolyard Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on South of Schoolyard Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Safety Surfacing
Instance on North of Schoolyard Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on South of Schoolyard Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Unpaved Area
Instance on North of Schoolyard Does not exist
Instance on South of Schoolyard Does not exist
Does not existPLAYING SURFACE
InspectedRETAINING WALLS
Condition 3- Fair
Are there any Retaining Walls 6' OR higher facing public street/sidewalk? No
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MINORDeficiency
SchoolyardDeficiency Location/Instance
65Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Schoolyard
Violations No violations recorded
InspectedSEATING
InspectedBenches
Does not existConcrete
InspectedMetal/Wood/Plastic
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedBleachers
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existMetal/Wood/Plastic
InspectedSITE WALLS (NOT RETAINING WALLS)
Page 28 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X240Architectural Inspection
Question Response
SITE
SITE WALLS (NOT RETAINING WALLS)
Condition 3- Fair
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MINORDeficiency
Schoolyard AmphitheaterDeficiency Location/Instance
25Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Schoolyard Amphitheater
Violations No violations recorded
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedSite Cheek/flank Walls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStairs/ramps
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Page 29 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)