NYC Department of Education Building Condition Assessment Survey 2018-2019 X240 Architectural Inspection Inspection Type Last Edited Time In InspectionId DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452 School: 1377 2019-01-11 07:02AM 2019-06-27 04:06PM ARCHITECTURAL - SENIOR 1464 2019-01-11 09:09AM 2019-06-06 03:08PM ARCHITECTURAL - ASSOCIATE Asset Data Question Answer Was the Building Fully Accessible for Inspection? Yes Principal(s) Information Principal Name Jacqueline Radoslovich Principal Organization P.S. 555 - Bronx (Mont Eden Children’s Academy ) Meeting with Principal? Yes Principal Feedback The Principal provided the following comment; The Heat / AC is not working properly, and needs repairs. Principal Name Christopher Reda Principal Organization X010 SPED Meeting with Principal? Yes Principal Feedback The Principal provided the following comment; The Heat / AC is not working properly, and needs repairs. Principal Name Alixandre Ricci Principal Organization I.S. 327 - Bronx Meeting with Principal? Yes Principal Feedback The Principal provided the following comment; The Heat / AC is not working properly, and needs repairs. Custodian Was not present Fireman Kevin Alejo Building Square Footage 170,100 Comments on the Area (Square Feet) N / A Comments on the Stories (Floors) plus Basements 4+B+PH Comments on the Year Built 2012 Comments on the Student Population 1221 Comments on the Staff Population 198 Comments on the Number of Classrooms 48 Weather Fair Facade Photo Jerome Avenue - Southwest view Page 1 of 29 Print Date: 7/3/2019 Mobile Validity Version 2.0 (P)
Transcript
Page 1: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Inspection Type Last EditedTime InInspectionId

DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452School:

1377 2019-01-11 07:02AM 2019-06-27 04:06PMARCHITECTURAL - SENIOR

1464 2019-01-11 09:09AM 2019-06-06 03:08PMARCHITECTURAL - ASSOCIATE

Asset DataQuestion Answer

Was the Building Fully Accessible for Inspection? Yes

Principal(s) Information

Principal Name Jacqueline Radoslovich

Principal Organization P.S. 555 - Bronx (Mont Eden Children’s Academy )

Meeting with Principal? Yes

Principal Feedback The Principal provided the following comment; The Heat / AC is

not working properly, and needs repairs.

Principal Name Christopher Reda

Principal Organization X010 SPED

Meeting with Principal? Yes

Principal Feedback The Principal provided the following comment; The Heat / AC is

not working properly, and needs repairs.

Principal Name Alixandre Ricci

Principal Organization I.S. 327 - Bronx

Meeting with Principal? Yes

Principal Feedback The Principal provided the following comment; The Heat / AC is

not working properly, and needs repairs.

Custodian Was not present

Fireman Kevin Alejo

Building Square Footage 170,100

Comments on the Area (Square Feet) N / A

Comments on the Stories (Floors) plus Basements 4+B+PH

Comments on the Year Built 2012

Comments on the Student Population 1221

Comments on the Staff Population 198

Comments on the Number of Classrooms 48

Weather Fair

Facade Photo

Jerome Avenue - Southwest view

Page 1 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 2: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural InspectionMain Entrance Photo

Facade A - Jerome Avenue

Roof Photo

Roof 1 - North View

No System UpgradedHave any Systems/Major Building Components been upgraded?

Have there been any New Building Additions? No New Construction

Tandem No Tandem

Leased Space? No

Priority ConditionExist

Last Year?

Priority

Category

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Structural Engineer Required

Structural

Condition Type

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Accessibility

Accessibility Status Question Response

Physical Breakdown Structure Exists Complies Required Deficiency

FUNCTIONAL ACCESSIBILITY

Exterior Routes

YesExterior Entrances & Exits

NoNoExterior H/C Lifts

NoYesExterior Ramps and Railings

Interior Routes

Page 2 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 3: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Physical Breakdown Structure Exists Complies Required Deficiency

NoNoCorridor and Lobby H/C Lifts

NoYesInterior Corridor Doors And Hardware

YesInterior Corridors & Lobbies

YesYesInterior Elevators

YesInterior Lobby Doors And Hardware

YesYesInterior Ramps

Rooms & Spaces

Art Rooms

Yes YesRoom 248, 250

Auditorium

Yes Yes2nd Floor

Cafeteria

Yes YesBasement

Classrooms

Yes YesBasement - 4th Floor

Computer Rooms

Yes YesRoom B23, 260

Gymnasium

Yes YesBasement

Library

Yes YesRoom 203

Main Office

Yes YesRoom 119 (Mont Eden Children

Academy), 220 (X010 SPED), 413 ( I.S.

327)

Multi-purpose Room

Yes YesBasement and 2nd Floor

Nurse's Office

Yes YesRoom 221, 306

Pool

Yes YesBasement

Science Lab

Yes YesRoom 147, 403, 406, 419

Toilet Rooms (boys)

Yes YesBasement-4th Floor

Toilet Rooms (girls)

Yes YesBasement- 4th Floor

Toilet Rooms (staff)

Yes YesBasement-4th Floor

Page 3 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 4: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Building Template

Inspection

Question Response

Architectural

ATHLETIC FIELDS Does not exist

EXTERIOR Inspected

Does not existAREAWAY

Does not existAWNINGS AND CANOPIES

Does not existCHIMNEY

InspectedCOPING

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existCORNICE

InspectedDOORS

InspectedDOOR HARDWARE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDOORS AND FRAMES

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedLINTELS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedTRANSOM/SIDE LIGHT

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedEXTERIOR SOFFITS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedEXTERIOR WALLS

Masonry, SteelMaterial Type(s)

34,540Replacement Quantity

Replacement Uom S.F.

Instance on All Facades Inspected

2- Between Good and FairInstance Condition

Instance Quantity 34,540

Page 4 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 5: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Instance Quantity Uom S.F.

No deficiencies recordedDeficiency

Does not existLOADING DOCK

InspectedLOUVER

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedPARAPETS

ConcreteMaterial Type(s)

4,935Replacement Quantity

Replacement Uom C.F.

Instance on All Facades Inspected

2- Between Good and FairInstance Condition

Instance Quantity 4,935

Instance Quantity Uom CF

No deficiencies recordedDeficiency

InspectedPLAZA DECK

Instance on Pavers:Roof 5 Inspected

2- Between Good and FairInstance Condition

Instance Quantity 4,000

Instance Quantity Uom S.F.

Installation Year 2012

Source of Installation Year Documented

No deficiencies recordedDeficiency

InspectedROOF

InspectedROOFING

Replacement Quantity 50,300

Replacement Uom S.F.

InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existROOF BARRIER

Does not existROOF CAGE

Does not existROOF FENCE

InspectedROOF HATCH/SMOKE HATCH

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedROOFING

Instance on IRMA:Roof 1 - 4 and 6 Inspected

3- FairInstance Condition

Instance Quantity 50,300

Instance Quantity Uom S.F.

“Does the roof have major mechanical equipment sitting on Dunnage

Steel less than 18" above the Roofing?"

No

Installation Year 2012

Source of Installation Year Documented

IRMA:ROOFING:MINOR LEAKAGEDeficiency

Deficiency Location/Instance

Page 5 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 6: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

EXTERIOR

ROOF

ROOFING

ROOFING

500Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

4th Floor Corridor

Deficiency Photo 2

Staircase G

Violations No violations recorded

InspectedROOFING DRAINS

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedSPECIALTIES

InspectedBULKHEAD/PENTHOUSE

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existCUPOLA/ SPIRES/ TOWERS

Does not existDORMER

Does not existDUNNAGE STEEL

Does not existROOF/GRAVITY TANK

InspectedSKYLIGHT/ROOF VENT

Material Type(s) Glass

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedSTAIRS/RAMPS: EXTERIOR

InspectedBUILDING CHEEK/FLANK WALLS

Condition 3- Fair

CAST IN PLACE CONCRETE:CRACKS/SPALLING - MINORDeficiency

Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Page 6 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 7: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade D

Deficiency Photo 2

Facade D

Violations No violations recorded

InspectedRAILINGS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedSTAIRS/RAMPS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWINDOWS

5,100Replacement Quantity

Replacement Uom S.F.

InspectedEXTERIOR GUARDS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedLINTELS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWINDOWS

Material Type(s) Aluminum

Instance on Aluminum - Other:All Facades Inspected

2- Between Good and FairInstance Condition

Instance Quantity 5,100

Instance Quantity Uom S.F.

Installation Year 2012

Source of Installation Year Documented

No deficiencies recordedDeficiency

INTERIOR Inspected

AUDITORIUM

Instance on 2nd Floor (412 Seats ) Inspected

Ceiling

Instance on 2nd Floor (412 Seats ) Inspected

2- Between Good and FairInstance Condition

Page 7 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 8: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

AUDITORIUM

Ceiling

GYPSUM BOARD:DAMAGED/DETERIORATEDDeficiency

Left Aisle Near EntranceDeficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Left Aisle Near Entrance

Violations No violations recorded

Door(s)

Instance on 2nd Floor (412 Seats ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed H/C Lift

Instance on 2nd Floor (412 Seats ) Does not exist

Fixed Seating

Instance on 2nd Floor (412 Seats ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on 2nd Floor (412 Seats ) Inspected

2- Between Good and FairInstance Condition

CONCRETE:CRACKSDeficiency

Near Seats A/101, 104, 105, 108, B/102Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Seat A/101

Violations No violations recorded

Sliding-folding Partition

Instance on 2nd Floor (412 Seats ) Does not exist

Stage

Instance on 2nd Floor (412 Seats ) Inspected

Stage

Page 8 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 9: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

AUDITORIUM

Stage

Stage

Instance on 2nd Floor (412 Seats ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage Curtain Rigging

Instance on 2nd Floor (412 Seats ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage Curtains

Instance on 2nd Floor (412 Seats ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Walls

Instance on 2nd Floor (412 Seats ) Inspected

2- Between Good and FairInstance Condition

WOOD PANELING:DETERIORATEDDeficiency

Near Entrance, Right Side of AuditoriumDeficiency Location/Instance

140Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Entrance

Violations No violations recorded

Window Curtains/Shades/Blinds

Instance on 2nd Floor (412 Seats ) Does not exist

CAFETERIA

Instance on Basement Inspected

Ceiling

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on Basement Does not exist

Floor Finish

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Sliding-folding Partition

Page 9 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 10: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

CAFETERIA

Sliding-folding Partition

Instance on Basement Does not exist

Stage

Instance on Basement Does not exist

Walls

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on Basement Does not exist

InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES

InspectedCeiling

Condition 2- Between Good and Fair

ACOUSTIC TILES:DAMAGED/MISSINGDeficiency

Room 262Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 262

Violations No violations recorded

TECTUM:DAMAGED/MISSING - ACTIVE LEAKDeficiency

Corridor Near Rooms 411, 419, 423Deficiency Location/Instance

85Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Corridor Near Room 411

Violations No violations recorded

GYPSUM BOARD:DAMAGED/DETERIORATEDDeficiency

Near Rooms B18, 121, 125, 203, 415 and other LocationsDeficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

Page 10 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 11: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Room 415

Violations No violations recorded

GYPSUM BOARD:DAMAGED/DETERIORATED - ACTIVE

LEAK

Deficiency

Corridor Near Room 417Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Corridor Near Room 417

Violations No violations recorded

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

TERRAZZO:CRACKSDeficiency

Near Room 144Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Room 144

Violations No violations recorded

VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency

Page 11 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 12: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Near Room 268Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Room 268

Violations No violations recorded

InspectedSpecialties

InspectedClassroom Locker(s)

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existFixed Seating

InspectedWalls

Condition 2- Between Good and Fair

CERAMIC TILE:BROKEN/ MISSINGDeficiency

Corridor Near Room 147Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Corridor Near Room 147

Violations No violations recorded

GYPSUM BOARD:DETERIORATEDDeficiency

Corridor Near Rooms 220, 259, 329A, 427Deficiency Location/Instance

40Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 12 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 13: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls

Deficiency Photo 1

Corridor Near Room 427

Violations No violations recorded

GYMNASIUM

Instance on Basement Inspected

Ceiling

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Basement Inspected

2- Between Good and FairInstance Condition

CERAMIC TILE:BROKEN/MISSING TILESDeficiency

Near Drinking FountainDeficiency Location/Instance

15Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Drinking Fountain

Violations No violations recorded

Seating

Instance on Basement Inspected

2- Between Good and FairInstance Condition

DAMAGED BLEACHERSDeficiency

Near WindowsDeficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

Page 13 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 14: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

GYMNASIUM

Seating

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Windows

Violations No violations recorded

Sliding-folding Partition

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage

Instance on Basement Does not exist

Walls

Instance on Basement Inspected

2- Between Good and FairInstance Condition

WALL PADDING:DETERIORATEDDeficiency

Near Room B06C, WindowsDeficiency Location/Instance

120Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Room B06C

Violations No violations recorded

Window Curtains/Shades/Blinds

Instance on Basement Does not exist

InspectedINTERIOR DOOR HARDWARE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedINTERIOR GUARDS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

KITCHEN

Instance on Basement Inspected

Ceiling

Instance on Basement Inspected

2- Between Good and FairInstance Condition

Page 14 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 15: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

KITCHEN

Ceiling

No deficiencies recordedDeficiency

Door(s)

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Walls

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

LIBRARY

Instance on Room 203 Inspected

Built-in Furnishing

Instance on Room 203 Does not exist

Ceiling

Instance on Room 203 Inspected

2- Between Good and FairInstance Condition

GYPSUM BOARD:DAMAGED/DETERIORATEDDeficiency

Center of RoomDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Center of Room

Violations No violations recorded

Door(s)

Instance on Room 203 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Room 203 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Walls

Instance on Room 203 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

LOCKER ROOM

Instance on Room B60 - Boys (150 Lockers) Inspected

Page 15 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 16: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

LOCKER ROOM

NoAlternative Use

Instance on Room B46 - Girls (160 Lockers ) Inspected

NoAlternative Use

Instance on Room B45 - Visitors (141 Lockers ) Inspected

NoAlternative Use

Instance on Room B67 (88 Lockers ) Inspected

NoAlternative Use

Instance on Room B71 (50 Lockers ) Inspected

NoAlternative Use

Instance on Room B73 (57 Lockers ) Inspected

NoAlternative Use

Ceiling

Instance on Room B60 - Boys (150 Lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B46 - Girls (160 Lockers ) Inspected

2- Between Good and FairInstance Condition

GYPSUM BOARD:DAMAGED/DETERIORATEDDeficiency

Near ShowerDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Shower

Violations No violations recorded

Instance on Room B45 - Visitors (141 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B67 (88 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B71 (50 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B73 (57 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Room B60 - Boys (150 Lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B46 - Girls (160 Lockers ) Inspected

2- Between Good and FairInstance Condition

Page 16 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 17: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

LOCKER ROOM

Door(s)

No deficiencies recordedDeficiency

Instance on Room B45 - Visitors (141 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B67 (88 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B71 (50 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B73 (57 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Room B60 - Boys (150 Lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B46 - Girls (160 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B45 - Visitors (141 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B67 (88 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B71 (50 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B73 (57 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Locker Room Lockers

Instance on Room B60 - Boys (150 Lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B46 - Girls (160 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B45 - Visitors (141 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B67 (88 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B71 (50 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B73 (57 Lockers ) Inspected

2- Between Good and FairInstance Condition

Page 17 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 18: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

LOCKER ROOM

Locker Room Lockers

No deficiencies recordedDeficiency

Walls

Instance on Room B60 - Boys (150 Lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B46 - Girls (160 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B45 - Visitors (141 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B67 (88 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B71 (50 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room B73 (57 Lockers ) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

MULTI-PURPOSE ROOM

Instance on 2nd Floor Inspected

Instance on Basement Inspected

Ceiling

Instance on 2nd Floor Inspected

2- Between Good and FairInstance Condition

ACOUSTIC TILES:DAMAGED/MISSINGDeficiency

Near Room 263Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Room 263

Violations No violations recorded

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 2nd Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Basement Inspected

Page 18 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 19: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

MULTI-PURPOSE ROOM

Door(s)

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on 2nd Floor Does not exist

Instance on Basement Does not exist

Floor Finish

Instance on 2nd Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Sliding-folding Partition

Instance on 2nd Floor Inspected

5- PoorInstance Condition

MOTOR:INOPERABLEDeficiency

Center of the RoomDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Violations No violations recorded

Instance on Basement Does not exist

Stage

Instance on 2nd Floor Does not exist

Instance on Basement Does not exist

Walls

Instance on 2nd Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on 2nd Floor Does not exist

Instance on Basement Does not exist

InspectedPOOLS

BasementInstance

CEILING

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

DECK/FLOOR

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

DIVING BOARD

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Page 19 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 20: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

POOLS

POOL LINING

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

ROOF STRUCTURE

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

SEATING

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

WALLS

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Does not existSCIENCE DEMO ROOM

SCIENCE LAB

Instance on Rooms 147, 403, 419 Inspected

NoAlternative Use

Instance on Room 406 Inspected

NoAlternative Use

Fixed Equipment

Instance on Rooms 147, 403, 419 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room 406 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

SCIENCE PREP ROOM

Instance on Rooms 145, 401 Inspected

NoAlternative Use

Fixed Equipment

Instance on Rooms 145, 401 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

SHOWER ROOM

Instance on Inside Room B60 - Boys Inspected

YesAlternative Use

Instance on Inside Room B46 - Girls Inspected

YesAlternative Use

Instance on Inside Room B45 - Visitors Inspected

YesAlternative Use

Instance on Inside Room B67 Inspected

NoAlternative Use

Instance on Inside Room B71 Inspected

NoAlternative Use

Instance on Inside Room B73 Inspected

NoAlternative Use

Ceiling

Instance on Inside Room B60 - Boys Inspected

Page 20 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 21: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

SHOWER ROOM

Ceiling

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B46 - Girls Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B45 - Visitors Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B67 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B71 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B73 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Inside Room B60 - Boys Does not exist

Instance on Inside Room B46 - Girls Does not exist

Instance on Inside Room B45 - Visitors Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B67 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B71 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B73 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Inside Room B60 - Boys Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B46 - Girls Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B45 - Visitors Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B67 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B71 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B73 Inspected

2- Between Good and FairInstance Condition

Page 21 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 22: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

SHOWER ROOM

Floor Finish

No deficiencies recordedDeficiency

Walls

Instance on Inside Room B60 - Boys Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B46 - Girls Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B45 - Visitors Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B67 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B71 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Inside Room B73 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

InspectedSTAIRS/RAMPS: INTERIOR

Do Letter Stair Signs Exist? 1

InspectedCeiling

Condition 2- Between Good and Fair

GYPSUM BOARD:DAMAGED/DETERIORATED - ACTIVE

LEAK

Deficiency

Stair G/2Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair G/2

Violations No violations recorded

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existPartition

InspectedRailings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStairs and Landings

Condition 2- Between Good and Fair

Page 22 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 23: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Stairs and Landings

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

MASONRY:CRACKS/SPALLINGDeficiency

Stair C/1Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair C/1

Violations No violations recorded

InspectedSTRUCTURAL

InspectedCOLUMNS/BEAMS/BEARING WALLS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFLOOR STRUCTURE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFOUNDATION WALLS

Material Type(s) Concrete

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedROOF STRUCTURE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existVAULTS-BUNKERS

InspectedTOILET ROOMS - STAFF

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existStalls

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedTOILET ROOMS - STUDENTS

InspectedCeiling

Page 23 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 24: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Ceiling

Condition 2- Between Good and Fair

GYPSUM BOARD:DAMAGED/DETERIORATEDDeficiency

Room 314Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 314

Violations No violations recorded

GYPSUM BOARD:DAMAGED/DETERIORATEDDeficiency

Room 268Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 268

Violations No violations recorded

InspectedDoor(s)

Condition 5- Poor

METAL:MISSING DOORDeficiency

Rooms B14, 142, 242Deficiency Location/Instance

3Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 242

Page 24 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 25: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Door(s)

Violations No violations recorded

WOOD:DETERIORATED DOORDeficiency

Room 231Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 231

Violations No violations recorded

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

GYPSUM BOARD:DETERIORATED - ACTIVE LEAKDeficiency

Room 268Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 268

Violations No violations recorded

LIFE SAFETY Inspected

Does not existF.D. HOLDING AREA

Does not existSTEEL STAIRS

SITE Inspected

Does not existCONTAINERIZATION

InspectedDRAINAGE SYSTEM FOR ASPHALT

InspectedCatch Basins/Manhole - Surrounded by Asphalt

Condition 2- Between Good and Fair

Page 25 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 26: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

SITE

DRAINAGE SYSTEM FOR ASPHALT

Catch Basins/Manhole - Surrounded by Asphalt

No deficiencies recordedDeficiency

Does not existCulverts - Asphalt Covering

Does not existDRAINAGE SYSTEM FOR CONCRETE

Does not existDRAINAGE SYSTEM FOR SOIL

Does not existDRINKING FOUNTAINS

InspectedFENCES

Condition 2- Between Good and Fair

CONCRETE CURB:DAMAGED/DETERIORATEDDeficiency

Along West 172nd StreetDeficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along West 172nd Street

Violations No violations recorded

Does not existIRRIGATION SYSTEM

InspectedPAVING

InspectedDOT Sidewalk

Does not existAsphalt

InspectedConcrete

3- FairCondition

DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency

Along West 172nd Street, Along Jerome AvenueDeficiency Location/Instance

475Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along West 172nd Street

Violations No violations recorded

Does not existPavers

InspectedSite Sidewalks & Walkways

InspectedAsphalt

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Page 26 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 27: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

SITE

PAVING

Site Sidewalks & Walkways

InspectedConcrete

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedPavers

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedStudent Non-Use

Gravel Exists? No

InspectedAsphalt

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedConcrete

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existPavers

InspectedStudent Use

Gravel Exists? No

InspectedAsphalt

3- FairCondition

CRACKS - MAJORDeficiency

SchoolyardDeficiency Location/Instance

180Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Schoolyard

Violations No violations recorded

InspectedConcrete

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existPavers

InspectedPLAYGROUNDS

North of SchoolyardInstance

South of SchoolyardInstance

Benches

Instance on North of Schoolyard Does not exist

Instance on South of Schoolyard Does not exist

Fence

Instance on North of Schoolyard Does not exist

Instance on South of Schoolyard Does not exist

Pavement

Instance on North of Schoolyard Does not exist

Page 27 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 28: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

SITE

PLAYGROUNDS

Pavement

Instance on South of Schoolyard Does not exist

Play Equipment

Instance on North of Schoolyard Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on South of Schoolyard Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Safety Surfacing

Instance on North of Schoolyard Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on South of Schoolyard Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Unpaved Area

Instance on North of Schoolyard Does not exist

Instance on South of Schoolyard Does not exist

Does not existPLAYING SURFACE

InspectedRETAINING WALLS

Condition 3- Fair

Are there any Retaining Walls 6' OR higher facing public street/sidewalk? No

CAST IN PLACE CONCRETE:CRACKS/SPALLING - MINORDeficiency

SchoolyardDeficiency Location/Instance

65Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Schoolyard

Violations No violations recorded

InspectedSEATING

InspectedBenches

Does not existConcrete

InspectedMetal/Wood/Plastic

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedBleachers

InspectedConcrete

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existMetal/Wood/Plastic

InspectedSITE WALLS (NOT RETAINING WALLS)

Page 28 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 29: DOE NEW SETTLEMENT COMMUNITY CAMPUS - …InspectionId Inspection Type Time In Last Edited School: DOE NEW SETTLEMENT COMMUNITY CAMPUS - BRONX, 1501 JEROME AVENUE, BRONX, NY, 10452

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X240Architectural Inspection

Question Response

SITE

SITE WALLS (NOT RETAINING WALLS)

Condition 3- Fair

CAST IN PLACE CONCRETE:CRACKS/SPALLING - MINORDeficiency

Schoolyard AmphitheaterDeficiency Location/Instance

25Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Schoolyard Amphitheater

Violations No violations recorded

InspectedSTAIRS/RAMPS: EXTERIOR

InspectedRailings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedSite Cheek/flank Walls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStairs/ramps

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Page 29 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)