3
1 (3) 901210-03/02 Subject to modification. DPU 7920 I/NET ® Seven The door processor unit 7920 (DPU-7920) functions as either a stand-alone device or as part of a larger local area network (LAN) host system. It controls up to two doors with entry reader inputs, or one door with entry and exit reader inputs, eight universal inputs, and eight relay contact outputs. By processing input data with programmed information, the DPU controls access into and exit from an area. It can monitor the status of the lock and door, routing status information to selected CRT displays and printers, and generate fault messages according to its programming. The DPU-7920 supports a total of 48,000 users. Recommended enclosure: ENCL7920 (Refer to enclosures datasheet) Recommended power supply: XFMR6 (Refer to transformers datasheet) Installation guide for DPU7920: TCON117 Communication Ports: Sub-LAN port Baud Rate ................. 9,600 Protocol ..................... Proprietary Transport .................. RS 485 multi-drop asynchronous, polling (open or closed loop) Connector ................. 2-part screw terminal Network Wiring Requirements: Length ....................... 5,000 feet per segment Extended Length ....... 25,000 feet with repeaters Connector ................. 2-part screw terminal Cable Type ................ Belden 9184 or equivalent twisted pair shielded Cable Size ................. <22AWG Impedance ................ 85 to 150 Ohm Capacitance .............. >30pF/ft between conductors and >55pF/ft conductor to shield Reader Wiring Requirements: General I/DISC ........................ 2 twisted pair shielded, Belden # 9184 or 9855 Wiegand .................... 8 conductor shielded Belden # 9536 / 9537 (500 ft. max) ABA 115 & 85 ............ 8 conductor shielded Belden # 9305 / 8725 Hardware Details: Processor ................. Seimens™ 80C535 operating at a clock speed of 11.0592 Mhz. TECHNICAL DATA EPROM ..................... 64KB Static RAM ................. 128KB Battery support .......... Onboard ni-cad, rechargeable, 30 days Clock/Calendar ......... Crystal controlled, real time Physical Details: General Power ........................ 24Vac, ±10%, 50/60Hz, Requirements 1.2A max or 24Vdc, ±10%, 1.2A max Operating .................. 32°F to 122°F without Temperature battery-backup 50°F to 100°F with lead-acid battery-backup Operating Humidity ... 10-80% RH, non-condensing Battery Backup Option Type .......................... Gel cell, mmaintenance free, rechargeable Capacity .................... 4AH, 12Vdc for up to 8 hours of normal operation (excluding power for locking mechanism, which must be powered separately) Charge Current 2A max (short circuit), .8A typical Power Supply ............ 115Vac or 250Vac transformer (50/60 Hz +15%), 75VA max Power Failure ........... Standard, using internal Notification detection logic Weight ....................... 5.5 lbs Door Processing Unit
Transcript
  • 1 (3) 901210-03/02

    TAC Vista IV®

    TAC Menta® 20 Feb 2002

    Subject to modification.

    DPU 7920I/NET

    ® Seven

    The door processor unit 7920 (DPU-7920) functions aseither a stand-alone device or as part of a larger local areanetwork (LAN) host system. It controls up to two doors withentry reader inputs, or one door with entry and exit readerinputs, eight universal inputs, and eight relay contactoutputs.

    By processing input data with programmed information, theDPU controls access into and exit from an area. It canmonitor the status of the lock and door, routing statusinformation to selected CRT displays and printers, andgenerate fault messages according to its programming.The DPU-7920 supports a total of 48,000 users.

    Recommended enclosure: ENCL7920(Refer to enclosures datasheet)

    Recommended power supply: XFMR6(Refer to transformers datasheet)

    Installation guide for DPU7920: TCON117

    Communication Ports:Sub-LAN port

    Baud Rate ................. 9,600Protocol ..................... ProprietaryTransport .................. RS 485 multi-drop

    asynchronous, polling(open or closed loop)

    Connector ................. 2-part screw terminalNetwork Wiring Requirements:

    Length ....................... 5,000 feet per segmentExtended Length ....... 25,000 feet with repeatersConnector ................. 2-part screw terminalCable Type ................ Belden 9184 or equivalent

    twisted pair shieldedCable Size ................. 30pF/ft between conductors

    and >55pF/ft conductor toshield

    Reader Wiring Requirements:General

    I/DISC ........................ 2 twisted pair shielded,Belden # 9184 or 9855

    Wiegand .................... 8 conductor shielded Belden# 9536 / 9537 (500 ft. max)

    ABA 115 & 85 ............ 8 conductor shielded Belden# 9305 / 8725

    Hardware Details:Processor ................. Seimens™ 80C535 operating

    at a clock speed of11.0592 Mhz.

    TECHNICAL DATAEPROM ..................... 64KBStatic RAM ................. 128KBBattery support .......... Onboard ni-cad,

    rechargeable, 30 daysClock/Calendar ......... Crystal controlled, real time

    Physical Details:General

    Power ........................ 24Vac, ±10%, 50/60Hz,Requirements 1.2A max or 24Vdc, ±10%,

    1.2A maxOperating .................. 32°F to 122°F withoutTemperature battery-backup 50°F to 100°F

    with lead-acid battery-backupOperating Humidity ... 10-80% RH, non-condensing

    Battery Backup OptionType .......................... Gel cell, mmaintenance free,

    rechargeableCapacity .................... 4AH, 12Vdc for up to 8 hours

    of normal operation(excluding power for lockingmechanism, which must bepowered separately)

    Charge Current 2A max (short circuit),.8A typical

    Power Supply ............ 115Vac or 250Vactransformer (50/60 Hz +15%),75VA max

    Power Failure ........... Standard, using internalNotification detection logicWeight ....................... 5.5 lbs

    Door Processing Unit

  • TECHNICAL DATA

    Baseplate VersionSize ........................... 9.6"L x 10"W x 1.5"DWeight ....................... 2lbs

    Enclosure VersionSize ........................... 14.25"L x 14.25"W x 3.5"DWeight ....................... 13 lbsWeight with Battery ... 18.5 lbs

    Controller Capacities:Tenants and Card Holders

    Number of Tenants .. Up to 255Card Holders ............ 48,000 (24,000 per door)

    SchedulesPersonnel ................. Up to 31 per door eachSchedules containing a seven-day week,

    seven special days and twotemporary schedules. Eachschedule contains sevenintervals with user-definedbegin and end times.

    Door Mode ................ One per door, containing aSchedules seven-day week, plus special

    days and two temporaryschedules. Entries for accesscontrol, locked or unlocked,times

    DoorsNumber of doors ...... 2 entry only

    1 entry/exitNumber of readers ... 1 or 2

    ElevatorsNumber of Cabs ....... 2 cabs each with one entry

    per 7920 readerStored Messages Capacity

    Buffer ......................... 5,000 messages, nominalReader Details:

    Readers SupportedI/DISCABA (TRACK 2) 115 & 85, 9 to 16 digit configurableWiegand 26 to 64 bit configurableWatermark Magnetics

    Input Details:General

    Number of inputs ....... 8Universal .................... DI or AI (0-5Vdc, 0-10Vdc,

    0-20ma)

    Supervision ................ 1K OHM, ¼ WATT, ± 5%resistor

    Terminations ............. Removable screw terminalconnectors

    Reader Ports ............. 2 ports, TTL Level signal,including 13 or 5 Vdc @50MA reader power

    Door Sense Input ...... 2 dry contact closure(one per door)

    Door Request to Exit 2 dry contact closures(one per door)

    Tamper Switch ........... Dry contact closurePower Loss Alarm ..... Dry contact closure

    Digital Output Details:General

    Standard Quantity ...... 8Terminations ............. Removable screw terminal

    connectorsType ........................... Form C relays, 1 A contact

    rating @ 24Vac/dc. Relaysoperate in pairs, one pair perdoor. Door unlock timeruser-defined 0-255 seconds

    LED Details:Sub-LAN TXSub-LAN RXLAN ReconfigStandby PowerNormal PowerEach Output On/Off

    Listings:UL294 ........................ Access control system unitsUL864 UUKL ............. Smoke control and smoke

    managementCE Marking ...................... Available

    EN61000-4-2 ............. Electro static dischargeEN61000-4-3 ............. Radiated RFEN61000-4-4 ............. EFTEN61000-4-5 ............. Surge testedEN61000-4-6 ............. Conducted RFEN61000-4-8 ............. Magnetic fieldEN61000-4-11 ........... Power quality

    2 (3)901210-03/02

    S1

    S2

    D11 D10 D9

    RX TX STATUS1 2 3 4 5 6 7 8 9 10 11 12

    OFFTB1

    TB2

    A1A2A3A4B1B2B3B4

    C1C2C3C4D1D2D3D4

    A5A6A7A8B5B6B7B8

    C5C6C7C8D5D6D7D8

    TB3

    TB4

    EPROM

    Reader Input 1

    12

    34

    5678

    12

    34

    5678

    Reader Input 2

    Door Switch

    RequestTo Exit

    +13V Reader Power(Not Used) Aux

    Data/Data-1+5V Reader Power

    Clk/Data-0LED (Red)

    LED (Green)Ground

    12

    34

    5678

    1 2 3 1 2 3 4 5 6 7 8

    SH

    LD

    CO

    M-

    CO

    M+

    TM

    P–

    TM

    P+

    BA

    T–

    BA

    T+

    E G

    ND

    PW

    R–

    PW

    R+

    Previo

    us

    Co

    ntro

    ller

    Next

    Co

    ntro

    ller

    SECONDARY ALARM BYPASS

    STRIKE POWERSUPPLY+ –

    NOC

    NC

    24Vac

    48VAPower

    Transformer

    4AH 12V Battery

    Tamper

    121110987654321

    TB8

    TB9

    SH

    LD

    CO

    M-

    CO

    M+

    NOC

    NC

    +

    TB1

    TB2

    TB3

    TB4

    TB5

    TB6

    TB8

    TB9D8

    D7

    D6

    D5

    D4

    D3

    D2

    D1

    C1

    C2

    C3

    C4

    D1

    D2

    D3

    D4

    STATUS

    8.00 "

    9.31 "

    8.64 "

    8.11 "

    7.00 "

    7.00 "

    S2

    D11 D10 D9

    RX TX

    S1 OFF 1 2 3 4 5 6 7 8 9 10 1112

    9.60"

    9.00"

    10.0"

    EPROM

    C5

    C6

    C7

    C8

    D5

    D6

    D7

    D8

    A1

    A2

    A3

    A4

    B1

    B2

    B3

    B4

    A5

    A6

    A7

    A8

    B5

    B6

    B7

    B8

    12345678

    RS5

    DPU 7920 Controller Card

  • 3 (3)901210-03/02

    TAC and TAC products are trademarks and/or registered trademarks of TAC AB. All other trademarksmentioned belong to their respective owners. Copyright © 2002 TAC AB. All rights reserved.

    www.tac-global.com

    7920-U8

    PART NUMBERS

    DIBA

    SE8 8 2Door processing unit, single door entry/exit,no enclosure, no transformer, UL2947920

    RDRDO

    8 8 2Door processing unit, single door entry/exit,no enclosure, no transformer, UL294, CEmarked

    7920-C

    8 8 2Door processing unit, single door entry/exit, noenclosure, no transformer, UL294, UL864 UUKL

    8 8 2Door processing unit, single door entry/exit, notassembled, enclosure, no transformer7921

    8 8 2Door processing unit, single door entry/exit, notassembled, enclosure, transformer, tamperswitch kit, battery backup kit, power on light kit,UL294, UL864 UUKL

    7921-U8

    8 8 2Door processing unit, single door entry/exit, notassembled, enclosure, transformer79211

    8 8 2Door processing unit, single door entry/exit,assembled, enclosure, transformer, tamperswitch kit, battery backup kit, power on light kit,UL294

    79211U

    8 8 2Door processing unit, single door entry/exit,assembled, enclosure, transformer 120V7922

    8 8 2Door processing unit, single door entry/exit,assembled, enclosure, transformer 120V,tamper switch kit, battery backup kit, power onlight kit, UL294

    7922U

    8 8 2Door processing unit, single door entry/exit,assembled, enclosure, transformer 120V,tamper switch kit, battery backup kit, power onlight kit, UL294, UL864 UUKL

    7922-U8

    Noise suppressionVaristor kitKITVAR

    COMMENT

    1 x 4AH, 12VDC batteryBattery backup kitKITBAT12 x 4AH, 12VDC batteryDouble battery backup kitKITBAT2Switch, wiring, screwsCabinet tamper switch kitKITSW120/24VACPlug-in transformerPLUGINTX

    14.25"x14.25"x3.5"Purpose-made enclosureENCL7920

    120/24VAC 2.4A SecPanel mounting transformerXFMR6Download FOC7920 Installation guideTCON117

    8 8 2Door processing unit, single door entry/exit,assembled, enclosure, transformer 240V7923


Recommended