TAYLOR ED
DESIGN AND CONSTRUCTION ADMINISTRATION PROVIDED BY:
UK PLANNING DESIGN AND CONSTRUCTION GROUP
211 PETERSON SERVICE BUILDING
LEXINGTON, KY 40506
TAYLOR EDUCATION BUILDING
UNIVERSITY OF KENTUCKY
LEXINGTON, KENTUCKY
VICINITY MAP
ROOMS 151 AND 151F RENOVATION PROJECT
THIS PROJECT IS A RENOVATION OF SUITE 151 AND WILL CREATE
SEVEN NEW OFFICES, A STORAGE ROOM AND A WAITING ROOM
WITHIN THE EXISTING SPACE. IMPROVEMENTS INCLUDE NEW CEILING
WITH LED LIGHTS, NEW HVAC EQUIPMENT, AND ADDITIONAL POWER
AND DATA FOR NEW OFFICES. NEW FINISHES WILL MATCH EXISTING
LAYOUT.
PROJECT DESCRIPTION
T-100 TITLE SHEET AND DRAWING INDEX SHEET
A-001 ARCHITECTURAL GENERAL NOTES, ABBREVIATIONS,
AND LEGEND
A-002 ARCHITECTURAL FINISH AND DOOR SCHEDULES AND DETAILS
AD-110 ARCHITECTURAL DEMOLITION PLAN
AD-111 ARCHITECTURAL REFLECTED CEILING DEMOLITION PLAN
A-110 ARCHITECTURAL FLOOR PLAN
A-111 ARCHITECTURAL REFLECTED CEILING PLAN
M-001 MECHANICAL GENERAL NOTES AND LEGEND
MD-110 MECHANICAL DEMOLITION PLANS
M-110 MECHANICAL PLANS
M-400 MECHANICAL SCHEDULES AND DETAILS
E-001 ELECTRICAL GENERAL NOTES AND LEGEND
ED-110 ELECTRICAL DEMOLITION PLANS
ED-111 ELECTRICAL DEMOLITION PLANS
E-100 ELECTRICAL PLAN - BASEMENT ROOM 11
E-110 ELECTRICAL PLANS - ROOM 151
E-111 ELECTRICAL PLANS - ROOM 151F
E-400 ELECTRICAL SCHEDULES
E-500 ELECTRICAL LIGHTING DIAGRAM
DRAWING INDEX
DRAWING NUMBER:
APPROVED BY:
PROJECT N0.:
DATE:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
DATE
REVISIONS
#
BU
ILD
IN
G N
UM
BE
R:
UN
IV
ER
SIT
Y O
F K
EN
TU
CK
Y
Ph
ysic
al P
la
nt D
ivisio
n
04/2020
807002758360
0001
RO
OM
S 1
51
A
ND
1
51
F R
EN
OV
AT
IO
N P
RO
JE
CT
TA
YL
OR
E
DU
CA
TIO
N B
UIL
DIN
G
TIT
LE
S
HE
ET
A
ND
D
RA
WIN
G IN
DE
X
T-100
CS
STAFF
ST-W
BL
06/04/2020
2
2
2
DRAWING NUMBER:
APPROVED BY:
PROJECT N0.:
DATE:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
DATE
REVISIONS
#
BU
ILD
IN
G N
UM
BE
R:
UN
IV
ER
SIT
Y O
F K
EN
TU
CK
Y
Ph
ysic
al P
la
nt D
ivisio
n
04/2020
807002758360
0001
RO
OM
S 1
51
A
ND
1
51
F R
EN
OV
AT
IO
N P
RO
JE
CT
TA
YL
OR
E
DU
CA
TIO
N B
UIL
DIN
G
AR
CH
IT
EC
TU
RA
L F
IN
IS
H A
ND
D
OO
R S
CH
ED
UL
ES
A-002
CS
STAFF
ST-W
BL
HW#1 - DOORS #151G, 151G2, 151H, 151J, 151K, 151L, 151M, 151N
3EA HINGES A5112X654XNRP
1EA LOCKSET LEVER 1000-1 F04 X 630
1EA WALL STOP L02101
3EA SILENCERS L03011
2EA KICK PLATE J102 10”X2”LDWX630
1EA CLOSER C02021 X 689
DOOR AND FRAME SCHEDULE
DOOR
NO.
151G
SIZE
TYPE MATL.GLAZING
DOOR
TYPE
FRAME
MATL. HEAD JAMB SILL
DETAILS
FIRE
RATING
NO
TE
S:
WD.1
HDW.
#
DOOR TYPES
1
DOOR AND FRAME TYPES
HARDWARE SETS
REMARKS
1
1.) EGRESS DOORS SHALL MEET A.D.A. ACCESSIBLE REQUIREMENTS.
- ALL NEW FIRE RATED DOORS WILL ALSO REQUIRE RATED DOOR FRAMES WITH SAME RATING AS DOOR AND, IF APPLICABLE, MUST
HAVE WIRE MESH FIRE RATED GLAZING.
- ALL EXISTING DOORS, TO REMAIN IN PLACE OR RELOCATED (IN THIS SPACE) WILL BE PATCHED, SANDED PREPARED AND
REFINISHED TO MATCH THE EXISTING BUILDING
151J
ROOM FINISH SCHEDULE
EX
IS
TIN
G
MA
TC
H E
XIS
TIN
G
UN
LE
SS
N
OT
ED
OT
HE
RW
IS
E
ROOM NAME BASE FLOOR WALLS CEILING HGT. CLG. REMARKS
RO
OM
NU
MB
ER
6" V
IN
YL
CO
VE
/T
ILE
EX
IS
TIN
G
PA
IN
T G
YP
SU
M
PA
IN
T E
XIS
TIN
G
2'x2' A
.C
.T
. A
ND
G
RID
EX
IS
TIN
G
PA
IN
T
EX
IS
TIN
G
2'X
2' C
AR
PE
T T
ILE
LV
T P
LA
NK
NO
NE
REFERS TO NOTEX
OFFICE
NO
TE
S:
FIN
IS
HE
S:
CEILING TILE:
ARMSTRONG, USG, OR EQUAL
CEILING TILE
STYLE - ARMSTRONG: 5/8" X 24" X 24" FINE FISSURED,
BEVELED TEGULAR
USG: 5/8" X 24" X 24" RADAR, BEVELED
TEGULAR
COLOR - WHITE
CEILING GRID
STYLE - ARMSTRONG: SUPRAFINE XL, 15/16"
EXPOSED TEE
USG: DONN DX15/16 TEE
COLOR - WHITE
NOTE:
FIELD VERIFY PIPE AND DUCT LOCATIONS TO
DETERMINE CONFLICTS WITH THE DESIGNED
CEILING HEIGHTS.
FLOORING:
EXISTING CARPET
WALL BASE:
ROPPE
STYLE - #100
COLOR - BLACK
TRIM PAINT:
MATCH EXISTING
WALL PAINT:
MATCH EXISTING COLOR
WA
LL T
ILE
1.) REPAIR ALL FLOOR, WALL, AND CEILING, DAMAGED DUE TO HAZARDOUS MATERIAL MITIGATION AND AS REQUIRED FOR
INSTALLATION OF NEW FINISH APPLICATION.
2.) LEVEL EXISTING SUB-FLOOR AND CLEAN SURFACE PRIOR TO INSTALLING NEW FLOORING.
3.) PREPARE ALL WALLS PRIOR TO APPLYING PAINT.
4.) NEW CEILING TO BE INSTALLED WITH AN ELECTRONIC LEVEL AT THE HEIGHT INDICATED ABOVE, IF EQUIPMENT DOES NOT ALLOW
FOR THE CEILING TO BE INSTALLED AT THIS HEIGHT, NOTIFY THE UNIVERSITY OF KENTUCKY CONSTRUCTION MANAGER.
- PATCH ALL HOLES ASSOCIATED WITH THE REMOVAL OF ANY PIPES, FIXTURES, PARTITIONS, ETC. AND SAND SMOOTH FOR NEW
FINISHES.
- REFER TO FINISHES BELOW FOR COLORS AND MATERIALS.
- SAND, SCRAPE, PREPARE AND PAINT ALL PREVIOUSLY PAINTED PIPES, RADIATORS, STEEL COVES, BRACKETS, ETC. TO MATCH
NEW FINISH COLORS.
- NO CEILING TILES TO BE DROPPED UNTIL FINAL OVERHEAD ELECTRICAL INSPECTION IS COMPLETED.
10'-8" A.F.F.
FRAME TYPES
A
NEW SOLID CORE
DOOR PANEL WITH
GLASS
DOOR DETAILS
8 7/8" WRAP
AROUND METAL
DOOR FRAME WITH
WELDED CORNERS
SOLID CORE
WOOD DOOR
NEW METAL STUD &
GYPSUM BOARD WALL
8 7/8" WRAP
AROUND METAL
DOOR FRAME WITH
WELDED CORNERS
SOLID CORE
WOOD DOOR
LINE OF
EXISTING FLOOR
2
JAMB DETAIL
SCALE: 1" =1'-0"
A-002
3
SILL DETAIL
SCALE: 1" =1'-0"
A-002
HARDWARE NOTES:
ALL HARDWARE ABOVE ARE ANSI GRADE 1 AND ALL EXIT DEVICES WILL BE BASED ON VON DUPRIN OR EQUAL, AND ALL CLOSERS WILL BE BASED
ON LCN OR EQUAL.
THE CORES FOR THIS PROJECT ARE REMOVABLE CORES THAT WILL BE PROVIDED AND INSTALLED BY THE UNIVERSITY OF KENTUCKY KEY
SHOP. IT IS THE CONTRACTORS RESPONSIBILITY TO PROVIDE LOCK SETS WITH THE CORRECT CYLINDERS TO RECEIVE UNIVERSITY SPECIFIED
REMOVABLE CORES. UNIVERSITY CORES VARY FROM BUILDING TO BUILDING AND IT IS THE CONTRACTORS RESPONSIBILITY TO COORDINATE
WITH THE UNIVERSITY KEY SHOP PRIOR TO ORDERING LOCK SETS. SHOP DRAWINGS WILL BE REJECTED IMMEDIATELY IF COORDINATION WITH
THE UK KEY SHOP IS NOT ON THE SUBMITTAL. FORMAT AND KEYING WILL ALSO BE DETERMINED BY THE UNIVERSITY OF KENTUCKY KEY SHOP
PRIOR TO ORDERING THE HARD WARE FOR THIS PROJECT.
THIS DESIGN IS BASE ON MORTISED LATCHES WITH LEVERS HANDLES AND INDEPENDENT LOCK SETS, TYPICALLY OR UNLESS NOTED
OTHERWISE. ALL HARDWARE SHOULD MATCH THIS OR BE AN APPROVED EQUAL.
SEE GENERAL NOTES ON SHEET A-001 FOR UK STANDARDS AND ADDITIONAL KEYING INFORMATION.
YES1/A-002 2/A-002 3/A-002
NEW HOLLOW METAL
DOOR FRAME
1
HEAD DETAIL
SCALE: 1" =1'-0"
A-002
151K
151L
151M
151N
151G
151J
151K
151L
151M
151N
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
H.M.WD.3'-0" x 7'-0" x 1 3/4"
YES A1
1/A-002 2/A-002 3/A-002
3'-0" x 7'-0" x 1 3/4"
3'-0" x 7'-0" x 1 3/4"
3'-0" x 7'-0" x 1 3/4"
3'-0" x 7'-0" x 1 3/4"
H.M.
H.M.
H.M.
H.M.
1/A-002 2/A-002 3/A-002
1/A-002 2/A-002 3/A-002
1/A-002 2/A-002 3/A-002
WD.YES A
1
WD.YES A1
WD.YES A1
A
NEW METAL STUD &
GYPSUM BOARD WALL
151 EXISTING
1
1
1
1
151P3'-0" x 7'-0" x 1 3/4" H.M.
1/A-002 2/A-002 3/A-002WD.
YES A2
HW#2 - DOORS #151P
3EA HINGES A5112X654XNRP
1EA LOCKSET LEVER 1000-1 F07 X 630
1EA WALL STOP L02101
3EA SILENCERS L03011
1EA KICK PLATE J102 10”X2”LDWX630
1
1
151G2 WD.YES 1/A-002 2/A-002 3/A-00223'-0" x 7'-0" x 1 3/4"
H.M.A
DOOR TYPES
2
WAITING ROOM 10'-8" A.F.F.151
OFFICE 10'-8" A.F.F.151F
151P STORAGE ROOM
10'-8" A.F.F.
10'-8" A.F.F.
10'-8" A.F.F.
10'-8" A.F.F.
10'-8" A.F.F.
10'-8" A.F.F.
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
2
EXISTING
151FEXISTING
06/04/20202
2
DRAWING NUMBER:
APPROVED BY:
PROJECT N0.:
DATE:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
DATE
REVISIONS
#
BU
ILD
IN
G N
UM
BE
R:
UN
IV
ER
SIT
Y O
F K
EN
TU
CK
Y
Ph
ysic
al P
la
nt D
ivisio
n
04/2020
807002758360
0001
RO
OM
S 151 A
ND
151F
R
EN
OV
AT
IO
N P
RO
JE
CT
TA
YLO
R E
DU
CA
TIO
N B
UILD
IN
G
GE
NE
RA
L E
LE
CT
RIC
AL N
OT
ES
A
ND
LE
GE
ND
E-001
STAFF
STAFF
ST-W
BL
FA
SWITCH
QUAD RECEPTACLE
DUPLEX RECEPTACLE
QUADPLEX DATA OUTLET WITH ONLY 2 DATA JACKS
ACTIVE AT THIS TIME. THE CONTRACTOR SHALL
FURNISH AND PROVIDE BOX AND 1-1/4" CONDUIT
FROM DATA OUTLET TO ABOVE CEILING PER
UNIVERSITY OF KENTUCKY COMMUNICATIONS
REQUIREMENTS. CAT 6 CABLES, FACE PLATE,
TESTING AND FINAL WIRING HOOK UP WILL BE
SUPPLIED BY OTHERS.
EMERGENCY LIGHT
EXIT SIGN
FIRE ALARM SIGNAL -STROBE & HORN
PANELBOARD
LF-1
LIGHT FIXTURE
DOWN LIGHT FIXTURE
WIRELESS ROUTER
DIMMER SWITCH
D
W
SMOKE DETECTOR
GENERAL NOTES LEGEND
S
A. CONTRACTOR SHALL INVESTIGATE PROJECT CONDITIONS THOROUGHLY PRIOR TO BID,
QUOTE, OR CONSTRUCTION AND NOTIFY PROJECT MANAGER OF ANY DISCREPANCIES
BETWEEN THE PROJECT DOCUMENTS AND EXISTING CONDITIONS.
B. BEFORE START OF WORK, THE CONTRACTOR SHALL CHECK ALL EXISTING DEVICES, LIGHT
FIXTURES AND EQUIPMENT THAT IS NOTED OR REQUIRED TO BE REUSED TO SATISFY
THEMSELF THAT THEY ARE OPERATING PROPERLY. SHOULD ANY OF THE ITEMS NOT BE
OPERATING, THE CONTRACTOR SHALL REPORT SAME TO THE ARCHITECT AND AWAIT
DIRECTIONS. CONTRACTORS NOT COMPLYING WITH THE ABOVE WILL BE RESPONSIBLE FOR
PROVIDING OPERATIONAL ITEMS AT HIS EXPENSE.
C. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ELECTRICAL INSPECTIONS. INSPECTION
REPORTS AND CERTIFICATES SHALL BE PROVIDED TO U.K. CONSTRUCTION MANAGER.
D. FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR AND SHALL PROVIDE A COPY OF ROC/FIRE
ALARM CERTIFICATE TO U.K. PROJECT MANAGER UPON COMPLETION OF PROJECT.
E. ELECTRICAL CONTRACTOR SHALL INSTALL ALL ELECTRICAL EQUIPMENT IN ACCORDANCE
WITH THE NATIONAL ELECTRICAL CODE.
F. ALL ITEMS SHOWN AS DASHED TO BE DEMOLISHED, INCLUDING ALL CONDUIT, WIRE,
JUNCTION BOXES, ETC. REMOVE WIRING COMPLETE BACK TO PANEL. EXISTING BREAKER IN
PANEL TO REMAIN UNLESS OTHERWISE NOTED. EXISTING BOXES IN EXISTING BLOCK WALLS
SHALL BE PROVIDED WITH A BLANK COVER PLATE. EXISTING CONDUIT IN BLOCK WALLS TO
REMAIN AND CAPPED. CONDUIT ABOVE CEILING SHALL BE REMOVED COMPLETE BACK TO
PANEL.
G. IN EXISTING AREAS WHERE NEW WORK IS SHOWN, REMOVE ALL EXISTING EXPOSED
CONDUITS, WIREMOLD, SURFACE AND FLUSH OUTLET BOXES, WIRING DEVICES, FIXTURES,
PANELS, ETC., NOT REQUIRED FOR NEW ARRANGEMENT.
H. GENERAL CONTRACTOR SHALL COORDINATE ALL WORK WITH ELECTRICAL CONTRACTOR.
I. FIRESTOP ALL RATED WALL AND FLOOR PENETRATIONS WITH FIRE CAULK ON BOTH SIDES.
SUBMIT CUT SHEET FOR FIRE RESISTANT ASSEMBLY USED TO U.K. CONSTRUCTION MANAGER.
J. PROVIDE ALL NECESSARY STRUCTURAL SUPPORT, BRACING, ETC. FOR NEW CONDUIT, BOXES,
LIGHT FIXTURES, ETC. AS REQUIRED BY ALL APPLICABLE CODES.
K. PATCH, PAINT, OR OTHERWISE RESTORE ANY FINISHES AFFECTED BY DEMOLITION OR
RELOCATION OF ELECTRICAL DEVICES, FIXTURES, ETC.
L. DURING DEMOLITION, REMOVE ABANDONED CONDUIT, WALL BOXES, AND WIRE BACK TO
PANELBOARDS OR TO NEAREST JUNCTION BOX THAT IS NOT BEING REMOVED AND NEEDS TO
REMAIN IN SERVICE. WIRE SHALL BE REMOVED BACK TO POINT OF ORIGIN.
M. TURN OFF CIRCUIT BREAKERS OR SWITCHES SERVING ABANDONED CIRCUITS AT THE
COMMENCEMENT OF WORK AND TAG BREAKER OR SWITCH AND LABEL PANEL SCHEDULE AS
"SPARE".
N. PROVIDE SUPPORTS FOR ALL VERTICAL CONDUIT RUNS IN ACCORDANCE WITH THE NATIONAL
ELECTRICAL CODE.
O. FLEXIBLE CONDUIT SHALL BE USED FOR FIXTURE WHIPS TO TO LIGHT FIXTURES. FLEXIBLE
CONDUITS TO LIGHT FIXTURES SHALL NOT EXCEED 6'-0" AND SHALL BE A MINIMUM OF
1
2
".
P. CONTRACTOR SHALL CHECK ALL DOOR SWINGS AND SHALL BE RESPONSIBLE FOR
INSTALLING ALL ROOM LIGHT SWITCHES/CONTROL STATIONS ASSOCIATED WITH DOORS ON
THE STRIKE SIDE OF THE DOORS REGARDLESS OF THE INDICATION ON THE ELECTRICAL
DRAWINGS. SWITCHES NOT COMPLYING SHALL BE RELOCATED AT THE CONTRACTOR'S
EXPENSE.
Q. ALL CONDUIT SHALL BE HOMERUN TO PANELBOARD AS INDICATED ON THE DRAWINGS.
COMBINING OF CIRCUITS IN HOMERUNS WILL NOT BE ACCEPTABLE. ANY DEVIATIONS IN SUCH
WORK WILL NOT BE APPROVED EXCEPT AS REQUIRED TO MEET THE NATIONAL ELECTRICAL
CODE OR BY PERMISSION OF THE ENGINEER.
R. ALL CONDUIT SHALL BE CONCEALED IN EXISTING AND NEW WALLS AND CEILINGS EXCEPT
MECHANICAL ROOMS. REFER TO SPECIFICATIONS.
S. ELECTRICAL CONTRACTOR SHALL LOCATE ALL ELECTRICAL EQUIPMENT AS REQUIRED TO
INSURE MINIMUM CLEARANCES ARE PROVIDED IN ACCORDANCE WITH THE NATIONAL
ELECTRICAL CODE.
T. ALL SCHEMATICS ARE FOR BID PURPOSES ONLY. SYSTEMS SHALL BE INSTALLED IN
ACCORDANCE WITH WIRING DIAGRAMS OBTAINED FROM THE MANUFACTURER.
U. ALL DEVICES SHALL BE LOCATED ON CLEAR WALL SPACES, CLEAR OF ALL SHELVING,
CHALKBOARDS, TACKBOARDS, CASEWORK, ETC. OUTLETS NOT COMPLYING WITH THE ABOVE
SHALL BE RELOCATED AT THE CONTRACTOR'S EXPENSE.
V. ROUGH-IN FOR EQUIPMENT SHALL BE DONE IN ACCORDANCE WITH APPROVED SHOP
DRAWINGS.
W. ELECTRICAL CONTRACTOR SHALL COORDINATE HEIGHT OF ALL DEVICES AT ALL CASEWORK
LOCATIONS TO AVOID CONFLICTS. ALL OUTLETS SHALL BE ROUGHED-IN IN ACCORDANCE
WITH ARCHITECTURAL CASEWORK ELEVATIONS. EXACT LOCATION OF ALL OUTLETS SHALL BE
AS DIRECTED BY THE OWNER.
X. COORDINATE EXACT LOCATION OF ALL DEVICES IN THE CEILING WITH THE ARCHITECTURAL,
HVAC, LIGHTING, AND FIRE PROTECTION REFLECTED CEILING PLANS.
Y. THE CONTRACTOR SHALL PROVIDE EQUIPMENT GROUNDING CONDUCTORS IN ALL FEEDERS
TO GROUND BUS IN PANELBOARDS AND IN ALL CIRCUITS TO EQUIPMENT AND RECEPTACLES.
Z. ALL ELECTRICAL OUTLETS WITHIN 6'-0" OF A WATER SOURCE SHALL BE OF THE GFI TYPE.
AA. LABEL CABLES BOTH AT THE RACK AND AT THE INDIVIDUAL OUTLET.
AB. NO MORE THAN AN EQUIVALENT OF 270 DEGREES OF BEND, INCLUDING OFFSETS, IS
ALLOWED IN A CONDUIT RUN BETWEEN JUNCTION BOXES OR PULL BOXES.
AC. PROVIDE A COPY OF ALL UPDATED PANEL SCHEDULES IN THE O & M MANUAL. PANEL
INDEXES TO BE TYPED AND SHALL INDICATE EQUIPMENT SERVED AND LOCATION OF
EQUIPMENT.
AD. DEVICE OUTLET BOXES SHALL BE 4-11/16"x4-11/16" X 2-1/8" DEEP MINIMUM WITH APPROPRIATE
DEPTH PLASTER RING.
AE. THE MOUNTING HEIGHT OF ALL WIRING DEVICES SHALL MATCH HEIGHT OF EXISTING DEVICES
UNLESS OTHERWISE NOTED.
AF. RECEPTACLES SHALL BE INSTALLED WITH GROUND JACK LOCATED IN THE ORIENTATION AS
EXISTING DEVICES. INSTALL GROUND JACK ON BOTTOM ON ALL NEW PROJECTS.
AG. IN AREAS REQUIRING CUTTING AND/OR REMOVAL OF EXISTING CEILING FOR THE
INSTALLATION OF NEW WORK, THE ELECTRICAL CONTRACTOR SHALL REMOVE EXISTING
ELECTRICAL EQUIPMENT (LIGHTING FIXTURES, ECT) AS REQUIRED AND REINSTALL WHEN NEW
CEILING IS IN PLACE.
AH. MOUNT ALL ELECTRICAL DEVICES ABOVE COUNTERTOPS AT UNIFORM HEIGHT.
AI. THE MINIMUM CONDUCTOR SIZE USED FOR LIGHTING AND POWER CIRCUITS SHALL BE #12
AWG. INCREASE THE SIZE OF THE CONDUCTORS AS NEEDED TO PREVENT EXCESSIVE
VOLTAGE DROP OVER LENGTHY FEEDER AND BRANCH CIRCUITS.MAXIMUN ACCEPTABLE
VOLTAGE DROPS SHALL BE AS FOLLOWS:
1.) VOLTAGE DROP OVER FEEDER: 3% MAX
2.) VOLTAGE DROP OVER FEEDER AND BRANCH CIRCUIT: 5% MAX
AJ. PLASTER, DRYWALL, OR OTHER WALL SURFACES THAT ARE BROKEN OR INCOMPLETE
AROUND BOX EMPLOYING A FLUSH TYPE COVER OR FACEPLATE SHALL BE REPAIRED SO
THERE ARE NO GAPS OR OPEN SPACES GREATER THAN 1/8" AROUND ALL EDGES OF BOX. THE
USED OF OVERSIZED FACEPLATES IS PROHIBITED. REFER TO N.E.C. ARTICLE 314.21.
AK. WALLPLATES SHALL BE INSTALLED PLUMB USING A TORPEDO TYPE LEVELING DEVICE.
AL. REFER TO ARCHITECTURAL PLANS FOR WALL THICKNESS AND TYPES, COORDINATE ALL WALL
MOUNTED WIRING DEVICES, JUNCTION BOXES, ETC, WITH THE WALL CONSTRUCTION. VERIFY
DEVICE LOCATIONS IN THE FIELD PRIOR TO ROUGH-IN.
AM. MAINTAIN 3'-0" WORKING CLEARANCE ON ALL INSTALLED EQUIPMENT, DISCONNECT
SWITCHES, COMBINATION MOTOR STARTERS, AND PANELBOARDS.
AN. ALL POWER AND DATA OUTLETS TO BE MOUNTED AT 18" A.F.F. UNLESS OTHERWISE NOTED.
AO. USE "J" HOOKS WITH CLIPS FOR ETHERNET CABLES ABOVE CEILING, INSTALLED PER NEC.
MAXIMUM SPACING BETWEEN HOOKS SHALL BE 4'-0".
LF-1
EMERGENCY LIGHT FIXTURE
06/04/20202