3
TAYLOR ED DESIGN AND CONSTRUCTION ADMINISTRATION PROVIDED BY: UK PLANNING DESIGN AND CONSTRUCTION GROUP 211 PETERSON SERVICE BUILDING LEXINGTON, KY 40506 TAYLOR EDUCATION BUILDING UNIVERSITY OF KENTUCKY LEXINGTON, KENTUCKY VICINITY MAP ROOMS 151 AND 151F RENOVATION PROJECT THIS PROJECT IS A RENOVATION OF SUITE 151 AND WILL CREATE SEVEN NEW OFFICES, A STORAGE ROOM AND A WAITING ROOM WITHIN THE EXISTING SPACE. IMPROVEMENTS INCLUDE NEW CEILING WITH LED LIGHTS, NEW HVAC EQUIPMENT, AND ADDITIONAL POWER AND DATA FOR NEW OFFICES. NEW FINISHES WILL MATCH EXISTING LAYOUT. PROJECT DESCRIPTION T-100 TITLE SHEET AND DRAWING INDEX SHEET A-001 ARCHITECTURAL GENERAL NOTES, ABBREVIATIONS, AND LEGEND A-002 ARCHITECTURAL FINISH AND DOOR SCHEDULES AND DETAILS AD-110 ARCHITECTURAL DEMOLITION PLAN AD-111 ARCHITECTURAL REFLECTED CEILING DEMOLITION PLAN A-110 ARCHITECTURAL FLOOR PLAN A-111 ARCHITECTURAL REFLECTED CEILING PLAN M-001 MECHANICAL GENERAL NOTES AND LEGEND MD-110 MECHANICAL DEMOLITION PLANS M-110 MECHANICAL PLANS M-400 MECHANICAL SCHEDULES AND DETAILS E-001 ELECTRICAL GENERAL NOTES AND LEGEND ED-110 ELECTRICAL DEMOLITION PLANS ED-111 ELECTRICAL DEMOLITION PLANS E-100 ELECTRICAL PLAN - BASEMENT ROOM 11 E-110 ELECTRICAL PLANS - ROOM 151 E-111 ELECTRICAL PLANS - ROOM 151F E-400 ELECTRICAL SCHEDULES E-500 ELECTRICAL LIGHTING DIAGRAM DRAWING INDEX DRAWING NUMBER: APPROVED BY: PROJECT N0.: DATE: DRAWN BY: CHECKED BY: DESIGNED BY: DATE REVISIONS # BUILDING NUMBER: UNIVERSITY OF KENTUCKY Physical Plant Division 04/2020 807002758360 0001 ROOMS 151 AND 151F RENOVATION PROJECT TAYLOR EDUCATION BUILDING TITLE SHEET AND DRAWING INDEX T-100 CS STAFF ST-W BL 06/04/2020 2 2 2
Transcript
Page 1: DRAWING INDEX TAYLOR EDUCATION BUILDING · uk planning design and construction group 211 peterson service building lexington, ky 40506 taylor education building university of kentucky

TAYLOR ED

DESIGN AND CONSTRUCTION ADMINISTRATION PROVIDED BY:

UK PLANNING DESIGN AND CONSTRUCTION GROUP

211 PETERSON SERVICE BUILDING

LEXINGTON, KY 40506

TAYLOR EDUCATION BUILDING

UNIVERSITY OF KENTUCKY

LEXINGTON, KENTUCKY

VICINITY MAP

ROOMS 151 AND 151F RENOVATION PROJECT

THIS PROJECT IS A RENOVATION OF SUITE 151 AND WILL CREATE

SEVEN NEW OFFICES, A STORAGE ROOM AND A WAITING ROOM

WITHIN THE EXISTING SPACE. IMPROVEMENTS INCLUDE NEW CEILING

WITH LED LIGHTS, NEW HVAC EQUIPMENT, AND ADDITIONAL POWER

AND DATA FOR NEW OFFICES. NEW FINISHES WILL MATCH EXISTING

LAYOUT.

PROJECT DESCRIPTION

T-100 TITLE SHEET AND DRAWING INDEX SHEET

A-001 ARCHITECTURAL GENERAL NOTES, ABBREVIATIONS,

AND LEGEND

A-002 ARCHITECTURAL FINISH AND DOOR SCHEDULES AND DETAILS

AD-110 ARCHITECTURAL DEMOLITION PLAN

AD-111 ARCHITECTURAL REFLECTED CEILING DEMOLITION PLAN

A-110 ARCHITECTURAL FLOOR PLAN

A-111 ARCHITECTURAL REFLECTED CEILING PLAN

M-001 MECHANICAL GENERAL NOTES AND LEGEND

MD-110 MECHANICAL DEMOLITION PLANS

M-110 MECHANICAL PLANS

M-400 MECHANICAL SCHEDULES AND DETAILS

E-001 ELECTRICAL GENERAL NOTES AND LEGEND

ED-110 ELECTRICAL DEMOLITION PLANS

ED-111 ELECTRICAL DEMOLITION PLANS

E-100 ELECTRICAL PLAN - BASEMENT ROOM 11

E-110 ELECTRICAL PLANS - ROOM 151

E-111 ELECTRICAL PLANS - ROOM 151F

E-400 ELECTRICAL SCHEDULES

E-500 ELECTRICAL LIGHTING DIAGRAM

DRAWING INDEX

DRAWING NUMBER:

APPROVED BY:

PROJECT N0.:

DATE:

DRAWN BY:

CHECKED BY:

DESIGNED BY:

DATE

REVISIONS

#

BU

ILD

IN

G N

UM

BE

R:

UN

IV

ER

SIT

Y O

F K

EN

TU

CK

Y

Ph

ysic

al P

la

nt D

ivisio

n

04/2020

807002758360

0001

RO

OM

S 1

51

A

ND

1

51

F R

EN

OV

AT

IO

N P

RO

JE

CT

TA

YL

OR

E

DU

CA

TIO

N B

UIL

DIN

G

TIT

LE

S

HE

ET

A

ND

D

RA

WIN

G IN

DE

X

T-100

CS

STAFF

ST-W

BL

06/04/2020

2

2

2

Page 2: DRAWING INDEX TAYLOR EDUCATION BUILDING · uk planning design and construction group 211 peterson service building lexington, ky 40506 taylor education building university of kentucky

DRAWING NUMBER:

APPROVED BY:

PROJECT N0.:

DATE:

DRAWN BY:

CHECKED BY:

DESIGNED BY:

DATE

REVISIONS

#

BU

ILD

IN

G N

UM

BE

R:

UN

IV

ER

SIT

Y O

F K

EN

TU

CK

Y

Ph

ysic

al P

la

nt D

ivisio

n

04/2020

807002758360

0001

RO

OM

S 1

51

A

ND

1

51

F R

EN

OV

AT

IO

N P

RO

JE

CT

TA

YL

OR

E

DU

CA

TIO

N B

UIL

DIN

G

AR

CH

IT

EC

TU

RA

L F

IN

IS

H A

ND

D

OO

R S

CH

ED

UL

ES

A-002

CS

STAFF

ST-W

BL

HW#1 - DOORS #151G, 151G2, 151H, 151J, 151K, 151L, 151M, 151N

3EA HINGES A5112X654XNRP

1EA LOCKSET LEVER 1000-1 F04 X 630

1EA WALL STOP L02101

3EA SILENCERS L03011

2EA KICK PLATE J102 10”X2”LDWX630

1EA CLOSER C02021 X 689

DOOR AND FRAME SCHEDULE

DOOR

NO.

151G

SIZE

TYPE MATL.GLAZING

DOOR

TYPE

FRAME

MATL. HEAD JAMB SILL

DETAILS

FIRE

RATING

NO

TE

S:

WD.1

HDW.

#

DOOR TYPES

1

DOOR AND FRAME TYPES

HARDWARE SETS

REMARKS

1

1.) EGRESS DOORS SHALL MEET A.D.A. ACCESSIBLE REQUIREMENTS.

- ALL NEW FIRE RATED DOORS WILL ALSO REQUIRE RATED DOOR FRAMES WITH SAME RATING AS DOOR AND, IF APPLICABLE, MUST

HAVE WIRE MESH FIRE RATED GLAZING.

- ALL EXISTING DOORS, TO REMAIN IN PLACE OR RELOCATED (IN THIS SPACE) WILL BE PATCHED, SANDED PREPARED AND

REFINISHED TO MATCH THE EXISTING BUILDING

151J

ROOM FINISH SCHEDULE

EX

IS

TIN

G

MA

TC

H E

XIS

TIN

G

UN

LE

SS

N

OT

ED

OT

HE

RW

IS

E

ROOM NAME BASE FLOOR WALLS CEILING HGT. CLG. REMARKS

RO

OM

NU

MB

ER

6" V

IN

YL

CO

VE

/T

ILE

EX

IS

TIN

G

PA

IN

T G

YP

SU

M

PA

IN

T E

XIS

TIN

G

2'x2' A

.C

.T

. A

ND

G

RID

EX

IS

TIN

G

PA

IN

T

EX

IS

TIN

G

2'X

2' C

AR

PE

T T

ILE

LV

T P

LA

NK

NO

NE

REFERS TO NOTEX

OFFICE

NO

TE

S:

FIN

IS

HE

S:

CEILING TILE:

ARMSTRONG, USG, OR EQUAL

CEILING TILE

STYLE - ARMSTRONG: 5/8" X 24" X 24" FINE FISSURED,

BEVELED TEGULAR

USG: 5/8" X 24" X 24" RADAR, BEVELED

TEGULAR

COLOR - WHITE

CEILING GRID

STYLE - ARMSTRONG: SUPRAFINE XL, 15/16"

EXPOSED TEE

USG: DONN DX15/16 TEE

COLOR - WHITE

NOTE:

FIELD VERIFY PIPE AND DUCT LOCATIONS TO

DETERMINE CONFLICTS WITH THE DESIGNED

CEILING HEIGHTS.

FLOORING:

EXISTING CARPET

WALL BASE:

ROPPE

STYLE - #100

COLOR - BLACK

TRIM PAINT:

MATCH EXISTING

WALL PAINT:

MATCH EXISTING COLOR

WA

LL T

ILE

1.) REPAIR ALL FLOOR, WALL, AND CEILING, DAMAGED DUE TO HAZARDOUS MATERIAL MITIGATION AND AS REQUIRED FOR

INSTALLATION OF NEW FINISH APPLICATION.

2.) LEVEL EXISTING SUB-FLOOR AND CLEAN SURFACE PRIOR TO INSTALLING NEW FLOORING.

3.) PREPARE ALL WALLS PRIOR TO APPLYING PAINT.

4.) NEW CEILING TO BE INSTALLED WITH AN ELECTRONIC LEVEL AT THE HEIGHT INDICATED ABOVE, IF EQUIPMENT DOES NOT ALLOW

FOR THE CEILING TO BE INSTALLED AT THIS HEIGHT, NOTIFY THE UNIVERSITY OF KENTUCKY CONSTRUCTION MANAGER.

- PATCH ALL HOLES ASSOCIATED WITH THE REMOVAL OF ANY PIPES, FIXTURES, PARTITIONS, ETC. AND SAND SMOOTH FOR NEW

FINISHES.

- REFER TO FINISHES BELOW FOR COLORS AND MATERIALS.

- SAND, SCRAPE, PREPARE AND PAINT ALL PREVIOUSLY PAINTED PIPES, RADIATORS, STEEL COVES, BRACKETS, ETC. TO MATCH

NEW FINISH COLORS.

- NO CEILING TILES TO BE DROPPED UNTIL FINAL OVERHEAD ELECTRICAL INSPECTION IS COMPLETED.

10'-8" A.F.F.

FRAME TYPES

A

NEW SOLID CORE

DOOR PANEL WITH

GLASS

DOOR DETAILS

8 7/8" WRAP

AROUND METAL

DOOR FRAME WITH

WELDED CORNERS

SOLID CORE

WOOD DOOR

NEW METAL STUD &

GYPSUM BOARD WALL

8 7/8" WRAP

AROUND METAL

DOOR FRAME WITH

WELDED CORNERS

SOLID CORE

WOOD DOOR

LINE OF

EXISTING FLOOR

2

JAMB DETAIL

SCALE: 1" =1'-0"

A-002

3

SILL DETAIL

SCALE: 1" =1'-0"

A-002

HARDWARE NOTES:

ALL HARDWARE ABOVE ARE ANSI GRADE 1 AND ALL EXIT DEVICES WILL BE BASED ON VON DUPRIN OR EQUAL, AND ALL CLOSERS WILL BE BASED

ON LCN OR EQUAL.

THE CORES FOR THIS PROJECT ARE REMOVABLE CORES THAT WILL BE PROVIDED AND INSTALLED BY THE UNIVERSITY OF KENTUCKY KEY

SHOP. IT IS THE CONTRACTORS RESPONSIBILITY TO PROVIDE LOCK SETS WITH THE CORRECT CYLINDERS TO RECEIVE UNIVERSITY SPECIFIED

REMOVABLE CORES. UNIVERSITY CORES VARY FROM BUILDING TO BUILDING AND IT IS THE CONTRACTORS RESPONSIBILITY TO COORDINATE

WITH THE UNIVERSITY KEY SHOP PRIOR TO ORDERING LOCK SETS. SHOP DRAWINGS WILL BE REJECTED IMMEDIATELY IF COORDINATION WITH

THE UK KEY SHOP IS NOT ON THE SUBMITTAL. FORMAT AND KEYING WILL ALSO BE DETERMINED BY THE UNIVERSITY OF KENTUCKY KEY SHOP

PRIOR TO ORDERING THE HARD WARE FOR THIS PROJECT.

THIS DESIGN IS BASE ON MORTISED LATCHES WITH LEVERS HANDLES AND INDEPENDENT LOCK SETS, TYPICALLY OR UNLESS NOTED

OTHERWISE. ALL HARDWARE SHOULD MATCH THIS OR BE AN APPROVED EQUAL.

SEE GENERAL NOTES ON SHEET A-001 FOR UK STANDARDS AND ADDITIONAL KEYING INFORMATION.

YES1/A-002 2/A-002 3/A-002

NEW HOLLOW METAL

DOOR FRAME

1

HEAD DETAIL

SCALE: 1" =1'-0"

A-002

151K

151L

151M

151N

151G

151J

151K

151L

151M

151N

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

H.M.WD.3'-0" x 7'-0" x 1 3/4"

YES A1

1/A-002 2/A-002 3/A-002

3'-0" x 7'-0" x 1 3/4"

3'-0" x 7'-0" x 1 3/4"

3'-0" x 7'-0" x 1 3/4"

3'-0" x 7'-0" x 1 3/4"

H.M.

H.M.

H.M.

H.M.

1/A-002 2/A-002 3/A-002

1/A-002 2/A-002 3/A-002

1/A-002 2/A-002 3/A-002

WD.YES A

1

WD.YES A1

WD.YES A1

A

NEW METAL STUD &

GYPSUM BOARD WALL

151 EXISTING

1

1

1

1

151P3'-0" x 7'-0" x 1 3/4" H.M.

1/A-002 2/A-002 3/A-002WD.

YES A2

HW#2 - DOORS #151P

3EA HINGES A5112X654XNRP

1EA LOCKSET LEVER 1000-1 F07 X 630

1EA WALL STOP L02101

3EA SILENCERS L03011

1EA KICK PLATE J102 10”X2”LDWX630

1

1

151G2 WD.YES 1/A-002 2/A-002 3/A-00223'-0" x 7'-0" x 1 3/4"

H.M.A

DOOR TYPES

2

WAITING ROOM 10'-8" A.F.F.151

OFFICE 10'-8" A.F.F.151F

151P STORAGE ROOM

10'-8" A.F.F.

10'-8" A.F.F.

10'-8" A.F.F.

10'-8" A.F.F.

10'-8" A.F.F.

10'-8" A.F.F.

3, 4

3, 4

3, 4

3, 4

3, 4

3, 4

3, 4

3, 4

3, 4

2

EXISTING

151FEXISTING

06/04/20202

2

Page 3: DRAWING INDEX TAYLOR EDUCATION BUILDING · uk planning design and construction group 211 peterson service building lexington, ky 40506 taylor education building university of kentucky

DRAWING NUMBER:

APPROVED BY:

PROJECT N0.:

DATE:

DRAWN BY:

CHECKED BY:

DESIGNED BY:

DATE

REVISIONS

#

BU

ILD

IN

G N

UM

BE

R:

UN

IV

ER

SIT

Y O

F K

EN

TU

CK

Y

Ph

ysic

al P

la

nt D

ivisio

n

04/2020

807002758360

0001

RO

OM

S 151 A

ND

151F

R

EN

OV

AT

IO

N P

RO

JE

CT

TA

YLO

R E

DU

CA

TIO

N B

UILD

IN

G

GE

NE

RA

L E

LE

CT

RIC

AL N

OT

ES

A

ND

LE

GE

ND

E-001

STAFF

STAFF

ST-W

BL

FA

SWITCH

QUAD RECEPTACLE

DUPLEX RECEPTACLE

QUADPLEX DATA OUTLET WITH ONLY 2 DATA JACKS

ACTIVE AT THIS TIME. THE CONTRACTOR SHALL

FURNISH AND PROVIDE BOX AND 1-1/4" CONDUIT

FROM DATA OUTLET TO ABOVE CEILING PER

UNIVERSITY OF KENTUCKY COMMUNICATIONS

REQUIREMENTS. CAT 6 CABLES, FACE PLATE,

TESTING AND FINAL WIRING HOOK UP WILL BE

SUPPLIED BY OTHERS.

EMERGENCY LIGHT

EXIT SIGN

FIRE ALARM SIGNAL -STROBE & HORN

PANELBOARD

LF-1

LIGHT FIXTURE

DOWN LIGHT FIXTURE

WIRELESS ROUTER

DIMMER SWITCH

D

W

SMOKE DETECTOR

GENERAL NOTES LEGEND

S

A. CONTRACTOR SHALL INVESTIGATE PROJECT CONDITIONS THOROUGHLY PRIOR TO BID,

QUOTE, OR CONSTRUCTION AND NOTIFY PROJECT MANAGER OF ANY DISCREPANCIES

BETWEEN THE PROJECT DOCUMENTS AND EXISTING CONDITIONS.

B. BEFORE START OF WORK, THE CONTRACTOR SHALL CHECK ALL EXISTING DEVICES, LIGHT

FIXTURES AND EQUIPMENT THAT IS NOTED OR REQUIRED TO BE REUSED TO SATISFY

THEMSELF THAT THEY ARE OPERATING PROPERLY. SHOULD ANY OF THE ITEMS NOT BE

OPERATING, THE CONTRACTOR SHALL REPORT SAME TO THE ARCHITECT AND AWAIT

DIRECTIONS. CONTRACTORS NOT COMPLYING WITH THE ABOVE WILL BE RESPONSIBLE FOR

PROVIDING OPERATIONAL ITEMS AT HIS EXPENSE.

C. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ELECTRICAL INSPECTIONS. INSPECTION

REPORTS AND CERTIFICATES SHALL BE PROVIDED TO U.K. CONSTRUCTION MANAGER.

D. FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR AND SHALL PROVIDE A COPY OF ROC/FIRE

ALARM CERTIFICATE TO U.K. PROJECT MANAGER UPON COMPLETION OF PROJECT.

E. ELECTRICAL CONTRACTOR SHALL INSTALL ALL ELECTRICAL EQUIPMENT IN ACCORDANCE

WITH THE NATIONAL ELECTRICAL CODE.

F. ALL ITEMS SHOWN AS DASHED TO BE DEMOLISHED, INCLUDING ALL CONDUIT, WIRE,

JUNCTION BOXES, ETC. REMOVE WIRING COMPLETE BACK TO PANEL. EXISTING BREAKER IN

PANEL TO REMAIN UNLESS OTHERWISE NOTED. EXISTING BOXES IN EXISTING BLOCK WALLS

SHALL BE PROVIDED WITH A BLANK COVER PLATE. EXISTING CONDUIT IN BLOCK WALLS TO

REMAIN AND CAPPED. CONDUIT ABOVE CEILING SHALL BE REMOVED COMPLETE BACK TO

PANEL.

G. IN EXISTING AREAS WHERE NEW WORK IS SHOWN, REMOVE ALL EXISTING EXPOSED

CONDUITS, WIREMOLD, SURFACE AND FLUSH OUTLET BOXES, WIRING DEVICES, FIXTURES,

PANELS, ETC., NOT REQUIRED FOR NEW ARRANGEMENT.

H. GENERAL CONTRACTOR SHALL COORDINATE ALL WORK WITH ELECTRICAL CONTRACTOR.

I. FIRESTOP ALL RATED WALL AND FLOOR PENETRATIONS WITH FIRE CAULK ON BOTH SIDES.

SUBMIT CUT SHEET FOR FIRE RESISTANT ASSEMBLY USED TO U.K. CONSTRUCTION MANAGER.

J. PROVIDE ALL NECESSARY STRUCTURAL SUPPORT, BRACING, ETC. FOR NEW CONDUIT, BOXES,

LIGHT FIXTURES, ETC. AS REQUIRED BY ALL APPLICABLE CODES.

K. PATCH, PAINT, OR OTHERWISE RESTORE ANY FINISHES AFFECTED BY DEMOLITION OR

RELOCATION OF ELECTRICAL DEVICES, FIXTURES, ETC.

L. DURING DEMOLITION, REMOVE ABANDONED CONDUIT, WALL BOXES, AND WIRE BACK TO

PANELBOARDS OR TO NEAREST JUNCTION BOX THAT IS NOT BEING REMOVED AND NEEDS TO

REMAIN IN SERVICE. WIRE SHALL BE REMOVED BACK TO POINT OF ORIGIN.

M. TURN OFF CIRCUIT BREAKERS OR SWITCHES SERVING ABANDONED CIRCUITS AT THE

COMMENCEMENT OF WORK AND TAG BREAKER OR SWITCH AND LABEL PANEL SCHEDULE AS

"SPARE".

N. PROVIDE SUPPORTS FOR ALL VERTICAL CONDUIT RUNS IN ACCORDANCE WITH THE NATIONAL

ELECTRICAL CODE.

O. FLEXIBLE CONDUIT SHALL BE USED FOR FIXTURE WHIPS TO TO LIGHT FIXTURES. FLEXIBLE

CONDUITS TO LIGHT FIXTURES SHALL NOT EXCEED 6'-0" AND SHALL BE A MINIMUM OF

1

2

".

P. CONTRACTOR SHALL CHECK ALL DOOR SWINGS AND SHALL BE RESPONSIBLE FOR

INSTALLING ALL ROOM LIGHT SWITCHES/CONTROL STATIONS ASSOCIATED WITH DOORS ON

THE STRIKE SIDE OF THE DOORS REGARDLESS OF THE INDICATION ON THE ELECTRICAL

DRAWINGS. SWITCHES NOT COMPLYING SHALL BE RELOCATED AT THE CONTRACTOR'S

EXPENSE.

Q. ALL CONDUIT SHALL BE HOMERUN TO PANELBOARD AS INDICATED ON THE DRAWINGS.

COMBINING OF CIRCUITS IN HOMERUNS WILL NOT BE ACCEPTABLE. ANY DEVIATIONS IN SUCH

WORK WILL NOT BE APPROVED EXCEPT AS REQUIRED TO MEET THE NATIONAL ELECTRICAL

CODE OR BY PERMISSION OF THE ENGINEER.

R. ALL CONDUIT SHALL BE CONCEALED IN EXISTING AND NEW WALLS AND CEILINGS EXCEPT

MECHANICAL ROOMS. REFER TO SPECIFICATIONS.

S. ELECTRICAL CONTRACTOR SHALL LOCATE ALL ELECTRICAL EQUIPMENT AS REQUIRED TO

INSURE MINIMUM CLEARANCES ARE PROVIDED IN ACCORDANCE WITH THE NATIONAL

ELECTRICAL CODE.

T. ALL SCHEMATICS ARE FOR BID PURPOSES ONLY. SYSTEMS SHALL BE INSTALLED IN

ACCORDANCE WITH WIRING DIAGRAMS OBTAINED FROM THE MANUFACTURER.

U. ALL DEVICES SHALL BE LOCATED ON CLEAR WALL SPACES, CLEAR OF ALL SHELVING,

CHALKBOARDS, TACKBOARDS, CASEWORK, ETC. OUTLETS NOT COMPLYING WITH THE ABOVE

SHALL BE RELOCATED AT THE CONTRACTOR'S EXPENSE.

V. ROUGH-IN FOR EQUIPMENT SHALL BE DONE IN ACCORDANCE WITH APPROVED SHOP

DRAWINGS.

W. ELECTRICAL CONTRACTOR SHALL COORDINATE HEIGHT OF ALL DEVICES AT ALL CASEWORK

LOCATIONS TO AVOID CONFLICTS. ALL OUTLETS SHALL BE ROUGHED-IN IN ACCORDANCE

WITH ARCHITECTURAL CASEWORK ELEVATIONS. EXACT LOCATION OF ALL OUTLETS SHALL BE

AS DIRECTED BY THE OWNER.

X. COORDINATE EXACT LOCATION OF ALL DEVICES IN THE CEILING WITH THE ARCHITECTURAL,

HVAC, LIGHTING, AND FIRE PROTECTION REFLECTED CEILING PLANS.

Y. THE CONTRACTOR SHALL PROVIDE EQUIPMENT GROUNDING CONDUCTORS IN ALL FEEDERS

TO GROUND BUS IN PANELBOARDS AND IN ALL CIRCUITS TO EQUIPMENT AND RECEPTACLES.

Z. ALL ELECTRICAL OUTLETS WITHIN 6'-0" OF A WATER SOURCE SHALL BE OF THE GFI TYPE.

AA. LABEL CABLES BOTH AT THE RACK AND AT THE INDIVIDUAL OUTLET.

AB. NO MORE THAN AN EQUIVALENT OF 270 DEGREES OF BEND, INCLUDING OFFSETS, IS

ALLOWED IN A CONDUIT RUN BETWEEN JUNCTION BOXES OR PULL BOXES.

AC. PROVIDE A COPY OF ALL UPDATED PANEL SCHEDULES IN THE O & M MANUAL. PANEL

INDEXES TO BE TYPED AND SHALL INDICATE EQUIPMENT SERVED AND LOCATION OF

EQUIPMENT.

AD. DEVICE OUTLET BOXES SHALL BE 4-11/16"x4-11/16" X 2-1/8" DEEP MINIMUM WITH APPROPRIATE

DEPTH PLASTER RING.

AE. THE MOUNTING HEIGHT OF ALL WIRING DEVICES SHALL MATCH HEIGHT OF EXISTING DEVICES

UNLESS OTHERWISE NOTED.

AF. RECEPTACLES SHALL BE INSTALLED WITH GROUND JACK LOCATED IN THE ORIENTATION AS

EXISTING DEVICES. INSTALL GROUND JACK ON BOTTOM ON ALL NEW PROJECTS.

AG. IN AREAS REQUIRING CUTTING AND/OR REMOVAL OF EXISTING CEILING FOR THE

INSTALLATION OF NEW WORK, THE ELECTRICAL CONTRACTOR SHALL REMOVE EXISTING

ELECTRICAL EQUIPMENT (LIGHTING FIXTURES, ECT) AS REQUIRED AND REINSTALL WHEN NEW

CEILING IS IN PLACE.

AH. MOUNT ALL ELECTRICAL DEVICES ABOVE COUNTERTOPS AT UNIFORM HEIGHT.

AI. THE MINIMUM CONDUCTOR SIZE USED FOR LIGHTING AND POWER CIRCUITS SHALL BE #12

AWG. INCREASE THE SIZE OF THE CONDUCTORS AS NEEDED TO PREVENT EXCESSIVE

VOLTAGE DROP OVER LENGTHY FEEDER AND BRANCH CIRCUITS.MAXIMUN ACCEPTABLE

VOLTAGE DROPS SHALL BE AS FOLLOWS:

1.) VOLTAGE DROP OVER FEEDER: 3% MAX

2.) VOLTAGE DROP OVER FEEDER AND BRANCH CIRCUIT: 5% MAX

AJ. PLASTER, DRYWALL, OR OTHER WALL SURFACES THAT ARE BROKEN OR INCOMPLETE

AROUND BOX EMPLOYING A FLUSH TYPE COVER OR FACEPLATE SHALL BE REPAIRED SO

THERE ARE NO GAPS OR OPEN SPACES GREATER THAN 1/8" AROUND ALL EDGES OF BOX. THE

USED OF OVERSIZED FACEPLATES IS PROHIBITED. REFER TO N.E.C. ARTICLE 314.21.

AK. WALLPLATES SHALL BE INSTALLED PLUMB USING A TORPEDO TYPE LEVELING DEVICE.

AL. REFER TO ARCHITECTURAL PLANS FOR WALL THICKNESS AND TYPES, COORDINATE ALL WALL

MOUNTED WIRING DEVICES, JUNCTION BOXES, ETC, WITH THE WALL CONSTRUCTION. VERIFY

DEVICE LOCATIONS IN THE FIELD PRIOR TO ROUGH-IN.

AM. MAINTAIN 3'-0" WORKING CLEARANCE ON ALL INSTALLED EQUIPMENT, DISCONNECT

SWITCHES, COMBINATION MOTOR STARTERS, AND PANELBOARDS.

AN. ALL POWER AND DATA OUTLETS TO BE MOUNTED AT 18" A.F.F. UNLESS OTHERWISE NOTED.

AO. USE "J" HOOKS WITH CLIPS FOR ETHERNET CABLES ABOVE CEILING, INSTALLED PER NEC.

MAXIMUM SPACING BETWEEN HOOKS SHALL BE 4'-0".

LF-1

EMERGENCY LIGHT FIXTURE

06/04/20202

2

AutoCAD SHX Text
S
AutoCAD SHX Text
S