+ All Categories
Home > Documents > Drye nst cti - 2 Million+ Parts | PartSelect · * Never terminate the exhaust into a common duct...

Drye nst cti - 2 Million+ Parts | PartSelect · * Never terminate the exhaust into a common duct...

Date post: 30-Jul-2020
Category:
Upload: others
View: 2 times
Download: 0 times
Share this document with a friend
8
nstallati nst cti lectric Drye Questions on Installation? Call" 1-800-GECARES (US) or Visit our Web site at: www.GEAppliances.com (US) BEFOREYOU BEGIN Read these instructions completely and carefully. IMFORTANT- S.,,e these e instructions fbr local inspector's use. "IMPORTANT- Obse,,,e all governingcodes and ordinances° * Note to Installer- Be sure to leave these instructions with the custotner. * Note to Customer - Keep these instruc> ions with your Use and Care Book for furore reference. * Before the old dryer is removed flom service or discarded, remove the d_Ter door. * Service infbrmation and the wiring dia- gram are located in the control console. * Do not allow children on or in the appli- ance. Close supe_wision of children is necessa_ T when the appliance is used near children. * Install the (bTer where the temperature is above 50°F for satisfilctory operation of the d_Ter control system. kWARN ING RIsKOF * To reduce the risk of severe i_i m T or death, fbllow all installation instruc- tions. * Clothes d_Ter insmlla6on must be performed by a qualified installer. * Install the clothes d_Ter according to these instructions and in accordance with local codes. * This d_Ter must be exhausted to the outdoors. * Use only 4" rigid metal duc6ng for exbaus6ng the clothes d_Ter to the outdoors. * DO NOT install a clothes d,Ter with flexible plastic ducdng materials. If flexible metal (semi-rigid or fbil-type) duct is installed, it must be UL listed and installed in accordance with the instructions found in "Connecting The D,Ter To House Vent" on page 5 of this manual. Flexible venting materials are known to collapse, be easily crushed, and trap lint. These conditions will obstruct dryer airflow and increase the risk of fire. * Do not install or store this appliance in any location where it coukt be exposed to water and or weather. * Save these instructions. (Installers: Be sure to leave these instructions with the customer). NOTE: installation and service of this dryer requires basic mechanical and electrical skills, it is your responsibility to contact a qualified installer to make the electrical connections. TOOLS YOU WiLL NEED SLIPJOINTPLIERS FLATBLADESCREWDRIVER PHILLIPSCREWDRIVER % MATERIALS YOU ) 4" DIA.METALDUCT (RECOMMENDED) 4"DIA,FLEXIBLE METALSEMI-RIGID) ULLSTEDTRANSTONDUCT (IFNEEDED) KITWXO8X10077 (INCLUDES 2 ELBOWS) 4"DUCT CLAMPS (2) OR 4"SPRING CLAMPS (2) % 4"DIA.METAL ELBOW 4"DIA.FLEXIBLE METALFOILTYPE) ULLSTEDTRANSTONDUCT (IFNEEDED.) DUCTTAPE WiLL NEED EXHAUST SAFETY HOOD GLASSES 3/4"STRAIN GLOVES RELIEF ULRECOGNIZED DRYERPOWER CORDKIT (NOTPROVIDED WITHDRYER) ULRATED 120/240V,30A WITH3OR4 PRONGS. IDENTIFY THEPLUG TYPEASPERTHE HOUSERECEPTACLE BEFORE PURCHASING LINECORD. Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Prepare the Area and Exhaust for Installation of New Dryer (see section 1). Check and Ensure the Existing External Exhaust is Clean (see sec6on 1) and Meets Attached Installa6on Specifications (see sec6on 3). Remove the Foam Shipping Pads (see sec6on 1). Move the DtTer to the Desired Location. Connect the Power Supply (see secdon 2). Connect the External Exhaust (see secdon 4). Level Your D_Ter (see sec6on 5). Step 8 Step 9 Check the Operation of the Power Supply an d Ve n tin g. Place the Owners Manual and the Installation Instructions in a Locadon Where They Will Be Noticed By the Owner. For Alcove or Closet Installation, see section 6. For Bathroom or Bedroom Installation, see section 7. For Mobile or Manufi_cmred Home see, section S. For side or bottom exhaust, see section 9.
Transcript
Page 1: Drye nst cti - 2 Million+ Parts | PartSelect · * Never terminate the exhaust into a common duct with a kitchen exhaust system. A combination of grease and lint creates a potential

nstallatinst cti

lectricDrye

Questions on Installation? Call" 1-800-GECARES (US)or Visit our Web site at: www.GEAppliances.com (US)

BEFOREYOU BEGINRead these instructions completely and

carefully.

IMFORTANT- S.,,ethesee

instructions fbr local inspector's use.

"IMPORTANT- Obse,,,eall governingcodes and ordinances°

* Note to Installer- Be sure to leave theseinstructions with the custotner.

* Note to Customer - Keep these instruc>

ions with your Use and Care Book forfurore reference.

* Before the old dryer is removed flomservice or discarded, remove the d_Terdoor.

* Service infbrmation and the wiring dia-gram are located in the control console.

* Do not allow children on or in the appli-ance. Close supe_wision of children isnecessa_ T when the appliance is usednear children.

* Install the (bTer where the temperatureis above 50°F for satisfilctory operation ofthe d_Ter control system.

kWARN I N G RIsKOF* To reduce the risk of severe i_i m T or death, fbllow all installation instruc-

tions.

* Clothes d_Ter insmlla6on must be performed by a qualified installer.

* Install the clothes d_Ter according to these instructions and in accordancewith local codes.

* This d_Ter must be exhausted to the outdoors.

* Use only 4" rigid metal duc6ng for exbaus6ng the clothes d_Ter to theoutdoors.

* DO NOT install a clothes d,Ter with flexible plastic ducdng materials. Ifflexible metal (semi-rigid or fbil-type) duct is installed, it must be UL listedand installed in accordance with the instructions found in "Connecting TheD,Ter To House Vent" on page 5 of this manual. Flexible venting materialsare known to collapse, be easily crushed, and trap lint. These conditions willobstruct dryer airflow and increase the risk of fire.

* Do not install or store this appliance in any location where it coukt beexposed to water and or weather.

* Save these instructions. (Installers: Be sure to leave these instructions withthe customer).

NOTE: installation and service of this dryer requires basicmechanical and electrical skills, it is your responsibility tocontact a qualified installer to make the electrical connections.

TOOLS YOUWiLL NEED

SLIPJOINTPLIERS

FLATBLADESCREWDRIVER

PHILLIPSSCREWDRIVER

%

MATERIALS YOU)

4" DIA.METALDUCT(RECOMMENDED)

4"DIA,FLEXIBLEMETALSEMI-RIGID)ULLSTEDTRANSTONDUCT

(IFNEEDED)KITWXO8X10077(INCLUDES2 ELBOWS)

4"DUCT

CLAMPS(2)OR

4"SPRING

CLAMPS(2)

%4"DIA.METAL

ELBOW

4"DIA.FLEXIBLEMETALFOILTYPE)ULLSTEDTRANSTONDUCT

(IFNEEDED.)

DUCTTAPE

WiLL NEED

EXHAUST SAFETYHOOD GLASSES

3/4"STRAIN

GLOVES RELIEFULRECOGNIZED

DRYERPOWERCORDKIT

(NOTPROVIDEDWITHDRYER)

ULRATED120/240V,30AWITH3OR4 PRONGS.IDENTIFYTHEPLUGTYPEASPERTHEHOUSERECEPTACLEBEFOREPURCHASINGLINECORD.

Step 1

Step 2

Step 3Step 4Step 5Step 6Step 7

Prepare the Area and Exhaust for Installation ofNew Dryer (see section 1).Check and Ensure the Existing External Exhaust isClean (see sec6on 1) and Meets Attached Installa6onSpecifications (see sec6on 3).Remove the Foam Shipping Pads (see sec6on 1).Move the DtTer to the Desired Location.Connect the Power Supply (see secdon 2).Connect the External Exhaust (see secdon 4).Level Your D_Ter (see sec6on 5).

Step 8

Step 9

Check the Operation of the Power Supplyan d Ve n tin g.Place the Owners Manual and the Installation

Instructions in a Locadon Where They Will Be

Noticed By the Owner.

For Alcove or Closet Installation, see section 6.For Bathroom or Bedroom Installation, see section 7.

For Mobile or Manufi_cmred Home see, section S.For side or bottom exhaust, see section 9.

Page 2: Drye nst cti - 2 Million+ Parts | PartSelect · * Never terminate the exhaust into a common duct with a kitchen exhaust system. A combination of grease and lint creates a potential

Installation instructionsMinimum Clearance Other Than Alcove or Closet Installation

Minimum clearance m combustible surfhces and for air opening are: 0 in. clearance bod_ sides and 1 in. rear. Considerationmust be given m provide adequate clearance ff)r installation and service.

I-f] PREPARING FOR iNSTALLATiONOF NEW DRYER

TIP: Install your dryer before installing your washer,

This will allow better access when installing dryer exhaust.

REMOVING LiNT FROM WALLEXHAUST OPENING

* Remove and discard existing plastic or metal foiltransition duct and replace with UL listed transitionduct°

WALL

/INTERNALDUCT CHECKTHATEXHAUSTOPENING DAMPEROPENS

ANDCLOSESFREELY.

TILTTHEDRYERSIDEWAYSANDREMOVETHEFOAMSHIPPINGPADSBYPULLINGATTHESIDESANDBREAKINGTHEMAWAYFROMTHEDRYERLEGS.BESURETOREMOVEALLOFTHEFOAMPIECESAROUNDTHELEGS.

2

[_ ELECTRICAL CONNECTIONiNFORMATiON

AWARNING- TO REDUCE THE RISK OF

FIRE, ELECTRICAL SHOCKAND PERSONAL

INJURY:e DO NOT USE AN EXTENSION CORD OR AN

ADAt_ER PLUG WITH THIS APPLIANCE.

Dwer must be electrically grounded in accordance withlocal codes and ordinances, or in the absence of localcodes, in accordance with the NATIONAL ELECTRI-CAL CODE, ANSI/NFPA NO. 70.

ELECTRICAL REQUIREMENTSThis dryer must be connected to an individual branch circuit,protected by the required time-delay fllses or circuit breakers. AIbm or three-wire, single phase, 120/240V or 120/208V, 60Hz,

30 amp circuit is required.

If the electric supply does not meet the aboxe specifications, thencall a licensed electrician.

GROUNDING INSTRUCTIONSThis dryer must be connected to a grounded metal, permanent

wiring system, or an equipmen/-grounding conductor must be run

with the circuit conductors and connected to the equipment-

grounding terminal on the appliance.

CONNECTING DRYER USING 4-WIRECONNECTION (MUST BE USED FORMOBILE HOME INSTALLATION)NOTES: Since January 1,1996, the National Electric code requiresthat the new constructions utilize a 4-wire connection toan electric dryer

t_WARNING:only a 4-conductor cord shah be used when the

appliance is installed in a location where grounding through the

neutral conductor is prohibited. Grounding through the neutral is

prohibited for the new branch-circuit installations, mobile homes,

recreational vehicles, and areas where local codes prohibit

grounding through the neutral conduction.

REMOVEGROUNDSTRAP -ANDDISCARD,KEEPGREEN HOT-"'_GROUNDSCREW WIRE RELOCATEGREEN

GROUNDSCREWHERE

GREENOR

Page 3: Drye nst cti - 2 Million+ Parts | PartSelect · * Never terminate the exhaust into a common duct with a kitchen exhaust system. A combination of grease and lint creates a potential

Installationi. Turn off the circuit breaker (s) (30 amp) or remox e tlle ch):er's

circuit fuse at the electrical box.

2. Be sure the ch):er cord is unplugged from tile wall receptacle.3. Remox e tile power cord coxer located at the lower back.

4. Remox e and discard ground strap. Keep tlle greenground screw for step 7.

5. Install 3/4 in. LL recognized strain relief to power

cord entl_ hole. Bring power cord through strain relief.

6. Comlect power cord as follows:A. Comlect the 2 hot lines to tile outer screws of

tlle terminal block (marked L1 and L2).

B. Com_ect tlle neutral (white) line to tile center of

tile terminal block (marked N).

7. Attach ground wire of power cord with tile green ground

screw (hole aboxe strain relief bracket). Tighten allterminal block screws (3) completely.

8. Properly secure power cord to strain relief.9. Reinstall tile co_ er.

_ILWARNING: NEVER LEAVE THECOVER OFF OF THE TERMINAL BLOCK,

CONNECTING DRYER USING 3-WIRECONNECTION

IFREQUIRED,BYLOCALCODE,INSTALLEXTERNALGROUND(NOTPROVIDED)TOGROUNDEDMETAL,COLDWATERPIPE,OROTHERESTABLISHEDGROUNDDETERMINEDBYA QUALIFIEDELECTRICIAN.

GREEN GROUNDGROUND STRAP

SCREW HOTWIRE STRAINRELIEF

BRACKET

_ 3/4",ULRECOGNIZED

RELIEF

NEUTRALHOT

(White) WIRE

3 #10AWGMINIMUMCOPPERCOVER CONDUCTORSOR120/240V30APOWER

SUPPLYCORDKITMARKEDFORUSEWITHDRYERS& PROVIDEDWITHCLOSEDLOOPORSPADETERMINALSWITHUPTURNEDENDS(NOTSUPPLIED).

i. Tm'n off tile circuit breaker(s) (30 amp) or remo_ e tile ch_er'scircuit fuse at the electrical box.

2. Be sure the ch_er cord is unplugged Kom the wall.

3. Remoxe the power cord coxer located at tile lower back.

4. Install 3/4 in. LL recognized strain relief to power cord

entl?_ bole. Bring power cord through strain relief.

5. Connect power cord as follows:A. Com_ect the 2 hot lines to the outer screws of tile

terminal block (marked L1 and L2).

B. Com_ect the neutral {white) line to tile center of

the terminal block {marked N).

6. Be sure grotmd strap is com_ected to neutral (center)

terminal of block and to green ground screw on cabinet

rear. Tighten all terminal block screws (3) completely.7. Properly secure power cord to strain relief.S. Reinstall tile co_ er.

A

,AHb_WARNING: NEVER LEAVE THECOVER OFF OF THE TERMINAL BLOCK.

Instructions

3

EXHAUST INFORMATION_WARNING - IN CANADA AND IN THE UNITED

STATES, THE REQUIRED EXHAUST DUCT DIAMETERIS 4 IN (102ram). DO NOT USE DUCT LONGERTHAN SPECIFIED IN THE EXHAUST LENGTH TABLE.Lsing exhaust longer than specified length wilh

" Increase the drying times and tile energy cost.

, Reduce the ch)_er life.

, Accumulate lint, creating a potential fire hazard.The correct exhaust installation is YOUR RESPONSIBILITY.

Problems due to incorrect installation are not covered

by the warranty.

Remove and discard existing plastic or metal foil transition

duct and replace with LL listed transition duct.

Tlle MAXIML M ALLOWABLE duct length and number of

bends of the exhaust system depends upon the type of duct,

number of turns, the type of exhaust hood (wall cap), and all

conditions noted below. The maximum duct length for rigidmetal duct is shown in the table below.

EXHAUST LENGTHRECOMMENDED MAXIMUM LENGTH

Exhaust Hood Types

Recommended Use only for shortrun installations

4" DIA.

_ 2-1/2"

No. of 90 -0 Rigid RigidElbows Metal Metal

0 90 Feet 60 Feet1 60 Feet 45 Feet2 45 Feet 35 Feet3 35 Feet 25 Feet4 25 Feet 15 Feet

EXHAUST SYSTEM CHECK LISTHOOD OR WALL (AP

• Terminate in a manner to prevent back drafts o1 entry of birds orother wildlife.

• Termination should present minimal resistance to the exhaust air flow

and should require little or no maintenance to prevent clogging.

• Never install a screen in or over the exhaust duct.This could cause lint build up.

• Wall caps must be installed at least 12 in. above ground level or any other

obstruction with the opening pointed down.

SEPARATION OF TURNS

For best performance, separate all turns by at least 4 ft. of straight duct,

including distance between last ttHn and exhaust hood.

TURNS OTHER THAN 90 °

* Oile tt_in of 45 ° or less may be ignored.* TWO45 ° ttH'i1S should be treated as one 90 ° ttH'i1.

, Each ttH'n over 45 ° should be treated as one 90 ° ttwn.

SEALING OF JOINTS

• _Mljoints should be tight to avoid leaks. The male end of each section of

duct must point away flom the dryer.Do not assemble the d uctwork with fasteners that extend into the d t_ct.

They will serve as a collection point for lint.

Duct joints can be made air and moisture-tight by wrapping the

overlapped joints with d t_ct rope.

Horizontal runs should slope down toward the outdoors _½inch per foot

INSULATION

Duct work that runs through an unheated area or is near air conditioning

should be insulated to reduce condensation and lint build-up.

Page 4: Drye nst cti - 2 Million+ Parts | PartSelect · * Never terminate the exhaust into a common duct with a kitchen exhaust system. A combination of grease and lint creates a potential

Installation

[-4-]EXHAUST CONNECTION

_ WARNING - TO REDUCE THE RISK

OF FIRE OR PERSONAL INJURY:* This clothes dIyer must be exhausted to the outdoors.* Use only 4" rigid metal ducting for the home exhaustduct.

. Use only 4" rigid metal or UI,-listed flexible metal(semi-rigid or foil-type) duct to connect the d_Ter to thehome exhaust duct. It must be installed in accordance

with the instructions found in "Connecting The DryerTo House Vent" on page 5 of this manual.

* Do not terminate exhaust in a chimney, a wall, aceiling, gas vent, crawl space, attic, under an enclosedfloor, or in any other concealed space of a building°The accumulated lint could create a fire hazard.

* Never terminate the exhaust into a common duct with

a kitchen exhaust system. A combination of grease andlint creates a potential fire hazard.

* Do not use duct longer than specified in the exhaustlength table. Longer ducts can accumulate lint,creating a potential fire hazard.

* Never install a screen in or over the exhaust duct. This

will cause lint to accumulate, creating a potential firehazard.

* Do not assemble ducta, vork with any fasteners thatextend into the duct. These fasteners can accumulate

lint, creating a potential fire hazard.* Do not obstruct incoming or exhausted air.* Provide an access for inspection and cleaning of theexhaust system, especially at turns and joints. Exhaustsystem shall be inspected and cleaned at least once a year.

THiS DRYER COMES READY FOR REAREXHAUSTING. iF SPACE iS LiMiTED, USETHE iNSTRUCTiONS iN SECTION 9 TOEXHAUST DIRECTLY FROM THE SIDES ORBOTTOM OF THE CABINET.

STANDARD REAR EXHAUST{Vented at floor level)

FORSTRAIGHTLINEINSTALLATION,CONNECTTHEDRYEREXHAUSTTOTHEEXTERNALEXHAUSTHOODUSINGDUCTTAPEORCLAMP.

EXTERNALDUCTOPENING

DUCTTAPEORDUCTCLAMP

4"METALDUCT

(CUTTOPROPERLENGTH) DUCTTAPEOR

DUCTCLAMP

NOTE:WESTRONGLYRECOMMENDSOLIDMETALEXHAUSTDUCTING.HOWEVER,IFFLEXIBLEDUCTINGISUSEDITMUSTBEUL-LISTEDMETALNOTPLASTIC.

instructions

STANDARD REAR EXHAUST{Vented above floor level)

ELBOWHIGHLYRECOMMENDED--

=

ELBOWHIGHLY

_ RECOMMENDED

RECOMMENDEDCONFIGURATIONTOMINIMIZEEXHAUSTBLOCKAGE.

NOTE: ELBOWS WiLL PREVENT DUCT

KiNKiNG AND COLLAPSING.

[_ LEVELING AND STABiLiZiNGYOUR DRYERSTANDTHEDRYERUPRIGHTNEARTHEFINALLOCATIONANDADJUSTTHE4LEVELINGLEGS,ATTHECORNERS,TOENSURETHATTHEDRYERISLEVELFROMSIDETOSIDEANDFRONTTOREAR.

LEVELFRONT-TO-BACK. LEVEL

SIDE-TO-SIDE.

4 LEVELINGLEGS

4

Page 5: Drye nst cti - 2 Million+ Parts | PartSelect · * Never terminate the exhaust into a common duct with a kitchen exhaust system. A combination of grease and lint creates a potential

Installation instructions, indoor ExhaustingCONNECTING THE DRYER

TO HOUSE VENTRIGID METAL TRANSITION DUCT

* For best dxying perfk_rmance, a rigid metal transitionduct is recommended.

* Rigid metal transitions ducts reduce the risk of crush-ing and kinking.

UL-LISTED FLEXIBLE METAL (SEMI-RIGID) TRANSITION DUCT

* If rigid metal duct cannot be used, then Ul,-listedflexible metal (semi-rigid) ducting can be used (KitWX08X10077).

* Never install flexible metal duct in walls, ceilings, floorsor other enclosed spaces.

* Total length of flexible metal duct should not exceed 8feet (2.4m).

* For many applications, installing elbows at both thediyer and the wall is highly recommended (see illustra-tions below). Elbows allow the d_yer to sit close to thewall without kinking and or crushing the transitionduct, maximizing d,ying perf_rmance.

* Avoid resting the duct on sharp objects.

UL-LISTEDFLEXIBLEMETAL(FOIL-TYPE) TRANSITION DUCT

* In special installations, it may be necessai T to connectthe d_Ter to the hot_se vent using a flexible metal (fkfil-type) dt_ct. A UL-listed flexible metal (fkfil-type)dt_ctmay be t]sed ONIX in installations where rigid metal orflexible metal (semi-rigid) ducfing cannot be used ANDwhere a 4" diameter can be maintained throughout theentire length of the transition dt_ct.

* In Canada and the United States, only the flexiblemetal (f_il-type) ducts that comply with the "Outline f_rClothes D_yer Transition Duct Subject 2158A" shall beused.

* Never install flexible metal duct in walls, ceilings, floorsor other enclosed spaces.

* Total length of flexible metal duct should not exceed 8feet (2.4m).

* Avoid resting the duct on sharp objects.* For best drying perf_rmance:

]. Slide one end of the duct over the clothes dryer

outlet pipe.

2. Secure the duct with a clamp.

3. With the d_yer in its permanent position, extend the

duct to its fifll length. Allow 9" of duct to overlap the

exhaust pipe. Cut offand remove excess duct. Kee I)

the duct as straight as possible t_r maximum airflow.

4. Secure the duct to the exhaust pipe with the otherclamp.

ELBOWHIGHLYRECOMMENDED

__ SHIGHLY I

MENDED

ALCOVE OR CLOSET iNSTALLATiON* If yore" dlTer is approved for installation in an alcove or

closet, it will be stated on a label on the dryer back.° The dryer MUST be vented to the outdoors. See the

EXHAUST INFORMATION sections 3 & 4.

* Minimmn clearance between duer cabinet and adjacentwalls or other surfaces is:

0 in. either side3 in. Kont and rear

* Minimmn vertical space from floor to overhead cabinets,ceiling, etc. is 52 in.

* Closet doors must be iouvered or othetwvise ventilated and

must contain a minimum of 60 sq. in. of open area equallydistributed. If the closet contains both a washer and aduet, doors must contain a minimum of 120 sq. in. of openarea equally distributed.

BATHROOM OR BEDROOMINSTALLATION

* The dryerMU ST be vented to the outdoors. SeeEXHAUST INFORN_TION section 3 & 4.

* The installation must conform with local codes or, in theabsence of local codes, with the NATIONAL ELECTRI-CAL CODE, ANSI/NFPA NO. 70.

5

FSqMOBILE OR MANUFACTUREDHOME INSTALLATION

° Installation must conform to the MANUFACTUREDHOME CONSTRUCTION & SAFETY STANDARD,TITLE 24, PART 32-80 or, when such standard is notapplicable, with %MERICAN NATIONAL STANDARDFOR MOBILE HOME, ANSI/NFPA NO. 501B.

° The dryer MU ST be vented to the outdoors with thetermination securely fastened to the mobile homestructure. (See EXHAUST INFORMATIONsection 3 & 4.)

* The vent MUST NOT be terminated beneath a mobile ormam_factured home.

* The vent duct material MU ST BE METAL.

* Do not use sheet metal screws or other fastening deviceswhich extend into the interior of the exhaust vent.

* See section 2 for electrical connection information.

Page 6: Drye nst cti - 2 Million+ Parts | PartSelect · * Never terminate the exhaust into a common duct with a kitchen exhaust system. A combination of grease and lint creates a potential

Installation InstructionsI-9-]DRYER EXHAUST TO RIGHT, LEFTOR BOTTOM CABINET

AWARNING- BEFORE PERFORMING

THIS EXHAUST INSTALLATION, BE SURETO DISCONNECT THE DRYER FROM ITSELECTRICAL SUPPLY. PROTECT YOURHANDS AND ARMS FROM SHARP EDGESWHEN WORKING INSIDE THE CABINET.BE SURE TO WEAR GLOVES

REMOVESCREWANDSAVE.

REMOVEDESIREDKNOCKOUT(ONEONLY).

Detach and remove the bottom, right or left side knockoutas desired. Remove the screw inside the dryer exhaust ductand save. Pull the duct out of the dryer.

FIXINGHOLE\

B A

9"

Cut the duct as shown and keep portion A.

TAB LOCATION

BENDTABUP45o

Through the rear opening, locate the tab in the middle ofthe appliance base. Lift the tab to about 45° using a fiatblade screwdriver.

6

ADDING NEW DUCTFIXINGHOLE

PORTION"A"

RIGHTORLEFTSIDEEXHAUST

Reconnect the cut portion (A) of the duct to the blowerhousing. Make sure that the shortened duct is aligned withthe tab in the base. Use the screw saved previously to securethe duct in place through the tab on the appliance base.

ADDING ELBOW AND DUCT FOREXHAUST TO LEFT OR RIGHTSIDE OF CABINETPreassemble 4" elbow with 4" duct. Wrap duct tapearound joint.Insert duct assembly, elbow first, through the side openingand connect the elbow to the dryer internal duct.

CAUTION: Be sure not to pull or damage theelectrical wires inside the dryerwhen inserting the duct.

J_

EXHAUSTCAN

BEADDEDTOLEFTORRIGHTSIDE

DUCT. TAPE

...... J-

Apply duct tape as shown on the joint between the dryer

internal duct and the elbow.

DUCT

CAUTION:Internal duct joints must be

__ secured with tape, otherwisethey may separate and causea safety hazard.

Page 7: Drye nst cti - 2 Million+ Parts | PartSelect · * Never terminate the exhaust into a common duct with a kitchen exhaust system. A combination of grease and lint creates a potential

Installation

ADDING ELBOW FOR EXHAUSTTHROUGH BOTTOM OF CABINET

* Insert tile elbow through the rear opening and connect itto the dryer internal duct.

* Apply duct tape oil thejoim between tile dryer internalduct and elbow, as shown oil page 6.

CAUTION:Internal duct joints must be secured with tape,otherwise they may separate and cause asafety hazard.

ADDING COVER PLATE TO REAROF CABINET (SIDES AND BOTTOMEXHAUST)

PLATE

÷

(KITWE1M454)

Connect standard metal elbows and ducts to complete theexhaust system. Cover back opening with a plate (FdtWEIM454) available from your local service provider.Place dryer in final location.

_ WARNING-NEVER LEAVE THE BACK ]OPENING WITHOUT THE PLATE. (KitWglM454)

InstructionsCHANGING DIRECTION OF

DOOR OPENING1. Open the door and remove the filler plugs opposite the

hinges. With the door completely open, remove thebottom screws from each hinge on the dryer face. Insertthese screws about half way into the TOP holes, for eachhinge on the opposite side (where you removed the fillerplugs). Apply firm pressure to get the screw started.

2. Loosen the top screws from each hinge on the dryer facehalf way. With one hand hoMing the top of the door andthe other hand holding the bottom, remove the doorfrom the dD'er by lifting itUP and OUT.

3. Rotate the door 180 °. Insert the door on the opposite sideof the opening by moving the doorlN and DOWNmltil the top hinge and the bottom hinge are resting onthe top screws inserted in step 1.

4. Remove the remaining screws from the side of theopening from which the door was removed. With thesescrews secure each hinge at the bottom. Tighten the twotop screws on each hinge. Reinsert the plastic plugs onthe side from which the door was removed.

REMOVETHEBOTTOMSCREWFROMEACHHINGEONTHEDRYER

_.__FAC_

LOOSENTHETOPSCREWSFROMEACHHINGEONTHEDRYERFACEHALFWAY.

MOVETHEDOORINANDDOWNUNTILTHETOPHINGEANDTHEBOTTOMHINGEARERESTINGONTHETOPSCREWSINSERTEDINSTEP1.

SECUREEACHHINGEATTHEBOTTOMANDTIGHTENTHETWOTOPSCREWSOFEACHHINGE.

TO REGISTER YOUR DRYER

CALL TOLL-FREE

1-888-269-1192

Prompt registration confirms your right to protection under the

terms of your warranty.

www.GEAppliances.com (US)

For Questions on Installation, Call: 1-800-GECARES (US)5(t(t,\4 _tiPO05 Re'J) Pub # 31 16224 7

SERVICING

WARNING- LABEL ALL WIRESPRIOR TO DISCONNECTING WHENSERVICING CONTROLS. WIRINGERRORS CAN CAUSE IMPROPER ANDDANGEROUS OPERATION AFTERSERVICING/INST ALIATION.

For servicing t)hone numbers for replacement parts, andother information, refer to Owner's Manual or visit ourWeb sire.

Page 8: Drye nst cti - 2 Million+ Parts | PartSelect · * Never terminate the exhaust into a common duct with a kitchen exhaust system. A combination of grease and lint creates a potential

Notes


Recommended