+ All Categories
Home > Documents > DS_8608.2

DS_8608.2

Date post: 15-Sep-2015
Category:
Upload: juan-vargas
View: 217 times
Download: 3 times
Share this document with a friend
Popular Tags:
2
DS-8608.2 1213B2 Series Service Regulators A Compact, Lightweight regulator designed for residential natural gas applications and for fast, easy installation with interchangeable orifices and springs that provide a wide range of outlet pressures and flow rates. Valve body configurations in 90˚ and 180˚ are available with 1/2", 3/4" and 1" NPT or BSP-TR connection sizes. The 1213B2 regulator features a full capacity internal relief valve with large passages to assure the fast release of gas. The standard relief spring setting is 8.0" W.C. above the normal 7" W.C. outlet pressure setpoint. All models conform to ANSI Code B109.4-1998 and CGA Service-type Regulator Specification CAN/CGA-6.18-M95. 2 4 1 3 3 1 2 4 3 4 2 1 1 2 3 4 VENT VENT VENT VENT Standard Vent Position Standard Vent Position 1213B2 Assembly Positions For 90˚ Models Standard Vent Position Standard Vent Position Valve Body Position “B” Valve Body Position “A” Valve Body Position “C” Valve Body Position “D” Data Sheet
Transcript
  • DS-8608.2

    1213B2 Series Service Regulators

    A Compact, Lightweight regulator designedfor residential natural gas applications andfor fast, easy installation withinterchangeable orices and springs thatprovide a wide range of outlet pressuresand ow rates.Valve body congurations in 90 and 180are available with 1/2", 3/4" and 1" NPT orBSP-TR connection sizes.The 1213B2 regulator features a fullcapacity internal relief valve with largepassages to assure the fast release of gas.The standard relief spring setting is 8.0"W.C. above the normal 7" W.C. outletpressure setpoint.All models conform to ANSI Code B109.4-1998 and CGAService-type Regulator SpecicationCAN/CGA-6.18-M95.

    2

    4

    1 3 3 1

    2

    4

    3

    4

    2

    11

    2

    3

    4

    VEN

    TVENT

    VENTVENT

    Standard Vent PositionStandard Vent Position

    1213B2 Assembly Positions For 90 Models

    Standard Vent PositionStandard Vent Position

    Valve Body Position BValve Body Position A

    Valve Body Position C Valve Body Position D

    Data Sheet

  • Outlet Pressure Color Code Part Number1213B2

    3.5" to 7" W.C. Light Blue 70017P083

    5" to 9" W.C. Lavender 70017P084

    6" to 15" W.C. Light Gray 70017P088

    18" to 2 PSIG Light Green 70017P085

    2 to 4 PSIG Pink 70017P086

    4 to 5 PSIG Turquoise 70017P087

    PCG/1000/12-02 FP 06-99

    300 Welsh Road, Building OneHorsham, PA 19044-2234Phone: 215/830-1800 Fax 215/830-1890www.americanmeter.com

    YesterdayTodayTomorrow275 Industrial RoadCambridge, OntarioCanada N3H 4R7Phone: 519/650-1900 Fax 519/650-1717www.americanmeter.com

    American Meter Company has a program of continuous product development and improvement and, therefore,the information in this bulletin is subject to change or modification without notice.

    1213B Series Service Regulators

    Dutch Councilfor Accreditation

    AMC Quality SystemQMI is Accredited by:

    ISO 9001 CertifiedCertificate #006697

    ANSI RAB

    AC

    C RE D I T

    ED

    RE

    GI S T R

    AR

    2

    Series 1213B Regulator Capacity Performance

    Capacity 1" Outlet 1213B2 RegulatorSet Point 7.0" W.C. @ 50 SCFH

    SCFH 0.60 specic gravity gas @ 60 F & 14.7 PSIA. Pressure spring70017P084. Outlet pressure variance not to exceed +2" -1" W.C. fromset point, horizontal position.

    Capacity 3/4" Outlet 1213B2 RegulatorSet Point 7.0" W.C. @ 50 SCFH

    SCFH 0.60 specic gravity gas @ 60 F & 14.7 PSIA. Pressure spring70017P084. Outlet pressure variance not to exceed +2" -1" W.C. fromset point, horizontal position.

    1213B2-90 Dimensions Pressure Springs

    * 2 PSIG Max.

    Order Information:Model Number:______________________________________Kind and specic gravity of gas: ________________________Inlet pressure, PSI: __________________________________Outlet pressure, inches W.C. (or PSIG): __________________Flow, scfh: _________________________________________Orice Size: ________________________________________Size of inlet and outlet: _______________________________Contact American Meter with any questions or orders atthe address and phone number below.

    Shipping Weight 28 lbs/carton of eight regulatorsReference MaterialsSales Bulletin. . . . . . . . . . . . . . . . . . SB-8506Operating Instructions Manual . . . . . IM-8705Repair Parts . . . . . . . . . . . . . . . . . . RPL-8801

    1213B2-180 Dimensions

    Inlet Orifice Size

    (PSIG) 1/8 3/16 1/4 5/16

    5 200 350 650 70010 300 600 950 110015 325 800 1100 140025 475 1100 1400 180035 600 1400 2200 250050 700 1800 220060 700 2100 2200

    Inlet Orifice Size

    (PSIG) 1/8 3/16 1/4 5/16

    5 200 350 650 75010 300 600 1000 120015 350 800 1400 160025 475 1100 2000 250035 600 1400 2500 250050 700 1800 2500 250060 800 2100 2500 2500

    For optimum performance, maximum inlet pressure should not exceed maximum capacity rating for any given orice size.The outlet pressure may vary as much as 0.5 W.C. if the diaphragm is in the vertical position.

    For optimum performance, maximum inlet pressure should not exceed maximum capacity rating for any given orice size.The outlet pressure may vary as much as 0.5 W.C. if the diaphragm is in the vertical position.

    5"

    2-25/32"

    4-9/16"

    2-3/16"

    1-1/4" 5-7/8"

    5"

    2-25/32"

    4-9/16"

    2-5/32"

    1-25/32" 5-5/16"