+ All Categories
Home > Documents > Dse332dse333 Pc Software Manual 2

Dse332dse333 Pc Software Manual 2

Date post: 03-Jun-2018
Category:
Upload: boris-agurto-espinoza
View: 234 times
Download: 0 times
Share this document with a friend

of 44

Transcript
  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    1/44

    DEEP SEA ELECTRONICS

    DSE332 / DSE333 Series ATS

    Configuration SuiteDocument Number 057-106

    Author : Anthony Manton

    COMPLEX SOLUTIONSMADE SIMPLE

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    2/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM2

    Deep Sea Electronics PlcHighfield HouseHunmanbyNorth YorkshireYO14 0PHENGLAND

    Sales Tel: +44 (0) 1723 890099Sales Fax: +44 (0) 1723 893303

    E-mail : [email protected] : www.deepseaplc.com

    DSE300 Series configuration suite

    Deep Sea Electronics PlcAll rights reserved. No part of this publication may be reproduced in any material form (including photocopyingor storing in any medium by electronic means or other) without the written permission of the copyright holderexcept in accordance with the provisions of the Copyright, Designs and Patents Act 1988.Applications for the copyright holders written permission to reproduce any part of this publication should beaddressed to Deep Sea Electronics Plc at the address above.

    The DSE logo and the names DSEUltra, DSEControl, DSEPower, DSEExtra, DSEMarine and DSENet are UKregistered trademarks of Deep Sea Electronics PLC.

    Any reference to trademarked product names used within this publication is owned by their respectivecompanies.

    Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice.

    Amendments List

    Amd.No.

    Comments Moduleversion

    Configuration SuiteVersion

    1.1 Added more desciption to breaker schemes and transfer timers. N/A N/A1.2 Change of gen current to load current N/A N/A

    2 Addition of DSE333 ATS and V2 332 2.0+ 2.0.8.100+

    Typeface : The typeface used in this document is Arial. Care should be taken not to mistake the upper case

    letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    3/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 3

    TABLE OF CONTENTS1 BIBLIOGRAPHY .......................................................................................... 42 DESCRIPTION ............................................................................................. 4

    2.1 SOFTWARE INSTALLATION INSTRUCTIONS................................................................................. 53 HARDWARE INSTALLATION ...................................................................... 8

    3.1 TROUBLESHOOTING INSTALLATION............................................................................................. 84 USING THE CONFIGURATION SUITE ......................................................... 95 MENUS AND TOOLBAR ............................................................................ 10

    5.1 FILE MENU ....................................................................................................................................... 105.2 TOOLS MENU................................................................................................................................... 11

    5.2.1 OPTIONS .................................................................................................................................. 115.2.2 ACCESS PERMISSIONS .......................................................................................................... 115.2.4 UPDATE FIRMWARE ............................................................................................................... 13

    5.3 HELP MENU ..................................................................................................................................... 155.4 TOOLBAR ......................................................................................................................................... 15

    6 EDIT CONFIG............................................................................................. 166.1 SCREEN LAYOUT ............................................................................................................................ 166.2 MODULE OPTIONS .......................................................................................................................... 176.3 APPLICATION OPTIONS ................................................................................................................. 18

    6.3.1 BREAKER SCHEME A.............................................................................................................. 196.3.2 BREAKER SCHEME B.............................................................................................................. 20

    6.4 DIGITAL INPUTS .............................................................................................................................. 226.4.1 INPUT FUNCTIONS .................................................................................................................. 23

    6.5 OUTPUTS ......................................................................................................................................... 256.5.1 DIGITAL OUTPUTS .................................................................................................................. 256.5.2 OUTPUT SOURCES ................................................................................................................. 26

    6.6 TIMERS ............................................................................................................................................. 286.6.1 START TIMERS ........................................................................................................................ 286.6.2 LOAD / STOPPING TIMERS..................................................................................................... 296.6.3 MODULE TIMERS..................................................................................................................... 29

    6.7 GENERATOR.................................................................................................................................... 306.7.1 GENERATOR OPTIONS........................................................................................................... 306.7.2 GENERATOR ALARMS ............................................................................................................ 31

    6.8 LOAD CURRENT .............................................................................................................................. 326.9 MAINS ............................................................................................................................................... 336.9.1 MAINS OPTIONS ...................................................................................................................... 33

    6.9.2 MAINS ALARMS ....................................................................................................................... 346.10 PLANT BATTERY............................................................................................................................. 356.11 SCHEDULER .................................................................................................................................... 36

    8 SCADA....................................................................................................... 378.2 MIMIC ................................................................................................................................................ 388.3 LANGUAGES.................................................................................................................................... 398.4 DIGITAL INPUTS .............................................................................................................................. 408.5 DIGITAL OUTPUTS .......................................................................................................................... 408.6 MAINS ............................................................................................................................................... 418.7 GENERATOR.................................................................................................................................... 418.8 LOAD ................................................................................................................................................ 428.9 PLANT BATTERY............................................................................................................................. 428.10 ALARMS ........................................................................................................................................... 428.11 STATUS ............................................................................................................................................ 438.12 EVENT LOG ...................................................................................................................................... 438.13 DATE AND TIME .............................................................................................................................. 44

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    4/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM4

    1 BIBLIOGRAPHY

    This document refers to and is referred to by the following DSE publications which can be obtained from theDSE website www.deepseaplc.com :

    DSE PART DESCRIPTION

    057-097 DSE332 ATS operator manual057-118 DSE333 ATS operator manual

    2 DESCRIPTION

    The DSE300 Series configuration suiteallows the 300 family of ATS control modules (DSE332 / DSE333)to be connected to a PC via USB A USB B cable. Once connected the various operating parameters withinthe module can be viewed or edited as required by the engineer.

    The configuration suite should only be used by competent, qualified personnel, as changes to the operation ofthe module may have safety implications on the panel / generating set to which it is fitted. Access to criticaloperational sequences and settings for use by qualified engineers, may be barred by a security code set bythe generator provider.

    The information contained in this manual should be read in conjunction with the information contained in theappropriate module documentation. This manual only details which settings are available and how they maybe used.A separate manual deals with the operation of the individual module (See section entitled Bibliography

    elsewhere in this document).

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    5/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 5

    2.1 SOFTWARE INSTALLATION INSTRUCTIONSMinimum system requirements

    Operating System Windows Vista, Windows XP or Windows 2000 with Microsoft .Net 2.0 framework

    Monitor 17 inch recommended (1024 x 768 resolution)

    Communications USB required o configure the module.

    NOTE: - As 300 Series configuration software for Windows is a 32-Bit application requiringMicrosoft .net 2 framework, it will not operate on Windows 2.0, 3.0, 3.1,3.11, 95, 98 or Me.

    NOTE: - Exit all other programs before installing the software. It is recommended that any earlierreleases of the software be uninstalled prior to installing this version.

    NOTE: - Please register online at www.deepseaplc.com Once registered you will be able to

    download updates to the software to ensure that you always have access to the latest features.

    Insert the Software CD into the CD-ROM drive on the PC. The CD will then Auto-run if this feature is enabledon your PC.

    Alternatively:

    Double click on Computer

    Double click on CD-ROM Drive

    Double click CDSetup

    Click Nextto continue

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    6/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM6

    Select Disk Costto view remaining disk space, Click Nextto continue.

    Example showing the Disk Costwindow.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    7/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 7

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    8/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM8

    3 HARDWARE INSTALLATION

    Ensure the Configuration Suite Software is installed on the PC as described above.The installation of the PC software also installs the DSE Controller USB Driver automatically.Connect the USB cable (USB type A to Type B as commonly used on USB printers) to the module and tothe PC as shown below.

    Windows detects the module when power is applied to it.

    You are now ready to configure or monitor the module using the Configuration Suite Software.

    3.1 TROUBLESHOOTING INSTALLATION

    Occasionally USB devices are disabled by the Windows operating system, the fo llowing procedure will re-enable thedevice in these instances.

    Disconnect the Deep Sea Electronics Controllerfrom the USB port. Wait a moment, then reconnect and tryagain. If you still encounter problems then :

    Try another USB cable. If you dont have one, its the same type of cable as usually used between a PCand a USB printer. If you still encounter problems then :

    Disconnect the Deep Sea Electronics Controller. Shutdown, then restart the PC. Reconnect the interface,then try again. If you continue to experience problems then :

    Check the USB port with another device (for instance a mouse, printer or digital camera).

    DSE332 ATS USB socket

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    9/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 9

    4 USING THE CONFIGURATION SUITE

    To run the Configuration Suite Software for Windows program click the Windows start button

    or depending upon your version of Windows.

    Then select All Programs - Deep Sea Electronics PLC DSE Configuration Suite DSE Configuration

    Suite

    After a short delay to load the application, the splash screen is shown, after which the screen willdisplay:-

    This is the initial start-up screen and can be disabled by checking the box Hide this screen at start-up.

    The screen prompts the user to select between the three main uses for the software:

    Creating a new configuration. Select the module type under Create new configuration. This allowsyou to create a configuration for the latest module version. Use File | Convert to...to convert theconfiguration to suit an earlier module version or use Tools | Update firmwareto update an earliermodule to the latest firmware version.

    Editing a configuration previously saved to disk or flash memory device. Select the configuration fileeither from the Open recent configurationarea or by clicking Open a configuration fileand browsing

    to the file. Reading and changing the configuration of a connected module. Click Read configuration from a

    module.The file is read from a currently connected controller and is available for editing in the

    Configuration Suite.

    Alternatively you can ignore this screen and continue to use the program in the background. Once you make aconnection or load/create a configuration, the start-up screen will disappear.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    10/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM10

    5 MENUS AND TOOLBAR

    The menu and toolbar are located at the top of the screen:

    5.1 FILE MENU

    Create a new configuration file. You are prompted to select what kind ofmodule you want to create the configuration for.The settings of the new configuration file match the factory settings for thechosen module type.You can only select to create a configuration file for the latest version ofcontroller. If you want to create a configuration for an earlier version ofcontroller, you can use Convert to...to make your configuration suitable for theearlier controller or use Tools | Update firmwareto update the earlier module

    to the latest version.

    Open an existing file from disk or flash memory device.Close the currently open file.

    Save the currently open file to the location it was loaded from previously. If thisis a new file, you are prompted to enter a filename.Save the currently open file, under a new name. You will be prompted to entera filename.

    Send the currently open configuration settings to the controller.

    Read the settings out of the connected controller for viewing / editing.

    Read the settings from the connected controller and convert to the currentlyselected configuration type.Read the settings from a configuration file on disk or flash memory device andconvert to the currently selected configuration type.

    Convert the currently loaded configuration file to suit another module type or

    another module version.Print the currently open configuration file.

    Preview what the configuration file will look like on the page after printing.

    Select printer type and printer settings.

    Exit the software. If the currently open file has changed since it was lastsaved, you will be prompted to save it.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    11/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 11

    5.2 TOOLS MENU

    5.2.1 OPTIONS

    Opens the Settingsscreen containing customisation options for the Configuration Suite.

    5.2.2 ACCESS PERMISSIONS

    Access permissions is an advanced Administration option to allow OEMS to setup the Configuration Suitesoftware to limit access for certain users.For instance, the generator OEM can install the software on the End Users PC and then setup multipleusernames to limit the customers access to only those functions that the OEM requires for the end user.An example of this is to give only SCADA access to a user requiring monitoring, or to give access to read andwrite configuration files, but not to edit a configuration file.

    Create a new user type

    Click the exitbutton if you dont

    want to update your module.

    Select Edit,then Newto createa new user

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    12/44

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    13/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 13

    5.2.4 UPDATE FIRMWARE

    Selecting Update Firmwareinitiates the update wizard:

    Click the exitbutton if you dont

    want to update your module.

    Click nextto continue.

    Hint: Stopping the update processonce it begins could leave themodule inoperable! If this occurs,simply run the update wizard again

    and let it complete correctly.

    Ensure the modules supply isremoved, and then Click nextto

    continue.

    Connect the USB cable to themodule and into your PC, thenClick nextto continue.

    Click to select the firmware update

    file.

    Then click nexttocontinue.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    14/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM14

    If the file you attempt to send to themodule is not compatible with thecurrently connected module, theupdate cannot continue.In this example an attempt wasmade to send a 7210 firmware fileto a 7220 module!

    Power up the module. It will beautomatically detected and the

    update process will begin.

    The update is now in progress and willtake under one minute.

    During this phase:

    DO NOT DISCONNECT THE USBCONNECTION

    DO NOT TURN OFF YOUR PC

    DO NOT REMOVE POWER

    FROM THE CONTROLLER

    The update is now complete.

    The module will automatically restartwith the updated firmware (internalsoftware program).

    It is now safe to disconnect the USBlead and power down the module oryour PC.

    Click OKto continue.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    15/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 15

    5.3 HELP MENU

    Shows the version number of the configuration suite

    5.4 TOOLBAR

    The toolbar contains the most used commands from the menus and is often a quicker way of accessing these

    commands.Create a new configuration file

    Open an existing file from disk or flash memory device

    Save the currently open file to the location it was loaded from previously. If this isa new file, you are prompted to enter a filename.

    Print the currently open configuration file

    Preview what the configuration file will look like on the page after printing.

    Send the currently open configuration settings to the controller

    Read the settings out of the connected controller for viewing / editing

    Shows the version number of the configuration suite

    Voltages are shown as phase to phase voltages in the configuration editor

    Voltages are shown as phase to neutral voltages in the configuration editorSelect the communication method. The choices present are dependent upon yourPCs configuration.

    USB To connect via USBdirectly to the controller, select USB:

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    16/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM16

    6 EDIT CONFIG

    This menu allows module configuration, to change the function of Inputs, Outputs and LEDs, system timersand level settings to suit a particular application.

    6.1 SCREEN LAYOUT

    The type ofconfiguration

    file being edited

    Close thisconfiguration file

    Move to thePreviousor Next

    configuration page

    The colouredshading showsthe currentlyselected page.

    Click + or toshow or hidethe sub settingswithin each

    sections.

    Click to selectthe subsection

    to view / edit

    Click to returnto this page atany time

    Step forward orbackward throughpreviously viewedpages

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    17/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 17

    6.2 MODULE OPTIONS

    This section allows the user to change the options related to the module itself.

    MiscellaneousOptions

    Lamp test at powerup

    =Lamp test at power up is disabled.=All module lamps illuminate when power is first applied.

    Transfer by buttons =Fascia load control buttons are disabled.=Fascia load control buttons are enabled when the module is in Manual Mode.

    Allows the user toselect the functionof the modulesuser configurableLED indicators.For details ofpossibleselections, pleasesee sectionentitled Outputsources

    elsewhere in this

    document.

    Allows the user tocreate logo and text

    insert cards

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    18/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM18

    6.3 APPLICATION OPTIONS

    MiscellaneousOptionsBreaker type

    Check Sync

    See overleaf for description of the BreakerTypeand CheckSyncoptions

    Return toprogrammedtransition

    This option is only available when Check Syncis enabled.= Normal operation=During load transfer if the check syncof the supplies does not occur within two minutes,

    a break or open transition transfer will occur.

    Elevator PostTransfer

    =Normal operation=Any configurable output set to elevator control remains active for the duration of theelevator delayafter a load transfer has taken place.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    19/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 19

    6.3.1 BREAKER SCHEME A

    Breaker scheme A is suitable for contactors or ACBs.

    NOTE : Generator Closed Auxiliary and Mains Closed Auxiliary inputs do not affect the operation

    of the load switching in Breaker Scheme A

    6.3.1.1 MAINS / GENERATOR LOAD INHIBIT

    Activation of an input configured to mainsload inhibitor generatorload inhibitinputs cause the corresponding

    breaker to be opened immediately. No other change in function will occur.When the input is deactivated the breaker is closed again if appropriate.

    6.3.1.2 LOAD SHEDDING

    If an input configured to Load Shed is activated, outputs set to Open Mains and Open Gen will energise, andinputs configured to Close Mains and Close Gen will de-energise. Open Mains Pulse and Open Gen Pulseoutputs will only energise if the corresponding supply was on load before application of the Load Shed input.When the Load Shed input is deactivated, the load will be transferred back to the supply that was

    disconnected before application of the input.

    6.3.1.3 TIMING DIAGRAM

    Open Mains

    Close Gen

    Close Mains

    Open Gen

    Open Mains Pulse

    Close Gen Pulse

    Close Mains Pulse

    Open Gen Pulse

    Transfer timeTransfer Time

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    20/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM20

    6.3.2 BREAKER SCHEME B

    Breaker Scheme B is intended only for use with certain designs of transfer switch. If you are using contactors,you MUST select Breaker Scheme A.

    6.3.2.1 CHECK SYNCHRONISING IS DISABLED

    6.3.2.1.1 TRANSFERRING TO GENERATOR

    To open the mains breaker the Open Mainsoutput energises, it then de-energises when the Mains ClosedAuxiliaryindicates it has successfully opened, or after 1s whichever occurs first.When the Mains Closed Auxiliary indicates the mains breaker has opened, the transfer timerbegins.When the transfer timerexpires, the module attempts to close the generator breaker by energising the OpenMainsand Close Generatoroutputs simultaneously, it then de-energises these outputs when the GeneratorClosed Auxiliaryinput indicates it has successfully closed, or after 1s whichever occurs first.

    6.3.2.1.2 TRANSFERRING TO MAINS

    To open the generator breaker the Open Genoutput energises, it then de-energises when the GeneratorClosed Auxiliaryindicates it has successfully opened, or after 1s whichever occurs first.When the Generator Closed Auxiliary indicates the generator breaker has opened, the transfer timerbegins.When the transfer timerexpires, the module attempts to close the mains breaker by energising the Open Genand Close Mainsoutputs simultaneously, it then de-energises these outputs when the Mains Closed Auxiliaryinput indicates it has successfully closed, or after 1s whichever occurs first

    6.3.2.1.3 LOAD SHED INPUT

    When the Load Shedinput is activated while the generator is closed the Open Genoutput energises, it thende-energises when the Generator Closed Auxiliaryinput indicates that it has successfully opened, or after 1s

    whichever occurs first.

    When the Load Shedinput is activated while the mains is closed the Open Mainsoutput energises, it then de-energises when the Mains Closed Auxiliaryinput indicates that it has successfully opened, or after 1s

    whichever occurs first.

    When the Load shedinput is de-energised the load will be returned to the supply that was disconnected,

    providing that supply is healthy.

    6.3.2.1.4 TIMING DIAGRAM

    Open Mains

    Close Gen

    Close Mains

    Open Gen

    Non-Sync Transfer TimeNon-Sync Transfer Time

    Gen has closed

    Mains has closed

    Mains has opened

    Gen has opened

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    21/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 21

    6.3.2.2 CHECK SYNCHRONISING IS ENABLED

    NOTE : The module waits indefinitely for synchronisation unless the Return to programmedtransition function is active in which case after 2 minutes it performs a non-sync transfer as

    described in the previous section.

    NOTE : The transfer time is ignored during a check-sync but is used if the transfer fails and it

    performs a non-sync transfer.

    6.3.2.2.1 TRANSFER TO GENERATOR

    When the module is about to transfer from mains to generator it activates the check sync function.When the mains and generator are within the phase and frequency window the module energises the OpenMains and Close Genoutputs simultaneously. These outputs are de-energised when the Generator ClosedAuxiliaryinput indicates it has successfully closed, or after 1s whichever occurs first.

    6.3.2.2.2 TRANSFER TO MAINS

    When the module is about to transfer from generator to mains it activates the check sync function.When the mains and generator are within the phase and frequency window the module energises the OpenGenand Close Mainsoutputs simultaneously. These outputs are de-energised when the Generator ClosedAuxiliary input indicates it has successfully closed, or after 1s whichever occurs first.

    6.3.2.2.3 LOAD SHED INPUT

    When the Load Shedinput is activated while the generator is closed the Open Genoutput energises, it thende-energises when the Generator Closed Auxiliaryinput indicates that it has successfully opened, or after 1s

    whichever occurs first.

    When the Load Shedinput is activated while the mains is closed the Open Mainsoutput energises, it then de-energises when the Mains Closed Auxiliaryinput indicates that it has successfully opened, or after 1s

    whichever occurs first.

    When the Load shedinput is de-energised the load will be returned to the supply that was disconnected,

    providing that supply is healthy.

    6.3.2.2.4 TIMING DIAGRAM

    Open Mains

    Close Gen

    Close Mains

    Open Gen

    Gen has closed

    Mains has closed

    In Sync

    In Sync

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    22/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM22

    6.4 DIGITAL INPUTS

    The inputs page is subdivided into smaller sections.Select the required section with the mouse.

    Input function. See sectionentitled Input functionsfordetails of all available functions

    Closeor open to activate

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    23/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 23

    6.4.1 INPUT FUNCTIONS

    Under the scope of IEEE 37.2, function numbers can also be used to represent functions in microprocessordevices and software programs. Where the DSE input functions can be represented by IEEE 37.2, the

    function number is listed below.

    Function Description

    Not used The input is disabledAlarm Mute This input is used to silence the audible alarm from an external source,

    such as a remote mute switch.

    Alarm Reset This input is used to reset any latched alarms from a remote location. Itis also used to clear any latched warnings which may have occurred (ifconfigured) without having to stop the generator.

    Auto Restore InhibitIEEE 37.2 - 3 checking orinterlocking relay

    In the event of a remote start/mains failure, the generator will beinstructed to start and take load. On removal of the remote startsignal/mains return the module will continue to run the generator onload until the Auto Restore Inhibitinput is removed. This input allowsthe controller to be fitted as part of a system where the restoration tomains is controlled remotely or by an automated system.

    Auto start InhibitIEEE 37.2 - 3 checking or

    interlocking relay

    This input is used to provide an over-ride function to prevent thecontroller from starting the generator in the event of a remote

    start/mains out of limits condition occurring. If this input is active and aremote start signal/mains failure occurs the module will not give a startcommand to the generator. If this input signal is then removed, thecontroller will operate as if a remote start/mains failure has occurred,starting and loading the generator. This function can be used to give anANDfunction so that a generator will only be called to start if themains fails and another condition exists which requires the generator torun. If the Auto start Inhibit signal becomes active once more it will beignored until the module has returned the mains supply on load andshutdown.This input does not prevent starting of the engine in MANUAL or TESTmodes.

    Auxiliary Generator Ready Allows an external device (such as the engine control module) toinstruct the ATS controller that the system is healthy and available to

    take load. The ATS controller then monitors the voltage and frequencyto check they are within acceptable limits before performing the loadtransfer function.

    Input K is fixed to provide this function.If not required, configure input k to open to activateand leave input Kdisconnected. Alternatively, connect input K permanently to the DCpositive supply.

    Auxiliary Mains Fail The module will monitor the incoming single or three phase supply forOver voltage, Under Voltage, Over Frequency or Under frequency. Itmay be required to monitor a different mains supply or some aspect ofthe incoming mains not monitored by the controller. If the devicesproviding this additional monitoring are connected to operate this input,the controller will operate as if the incoming mains supply has fallenoutside of limits, the generator will be instructed to start and take theload. Removal of the input signal will cause the module to act if themains has returned to within limits providing that the mains sensing alsoindicates that the mains is within limits.

    Generator Closed AuxiliaryIEEE 37.2 - 3 Checking orinterlocking relay(breaker acheme B)

    This input is used to provide feedback to allow the controller to give trueindication of the contactor or circuit breaker switching status. It shouldbe connected to the generator load switching device auxiliary contact.

    In Breaker Scheme A, Incorrect application of this signal does nottrigger an alarm condition, it is used solely for indication of the breakerstatus.

    In Breaker Scheme B this feedback is used for internal interlocking ofthe breaker outputs.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    24/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM24

    Generator Load InhibitIEEE 37.2 - 52 AC circuit breaker

    This input is used to prevent the controller from loading the generator. Ifthe generator is already on load, activating this input will cause the 300series controller to unload the generator. Removing the input will allowthe generator to be loaded again.

    NOTE: -This input only operates to control the generator-switching device if the 300 load switching logic is attempting to

    load the generator. It will not control the generator-switchingdevice when the mains supply is on load.

    Inhibit scheduled run This input is used to prevent operation of the set by the internalScheduler function.

    Lamp Test This input is used to provide a test facility for the front panel indicatorsfitted to the 300 module. When the input is activated all LEDs shouldilluminate.

    Load Shedding Opens both the mains and generator load switch devices. See thesection entitled Breaker Schemefor details of how this input interactswith the load switching control.

    Mains closed AuxiliaryIEEE 37.2 - 3 Checking orinterlocking relay(breaker acheme B)

    This input is used to provide feedback to allow the 300to give trueindication of the contactor or circuit breaker switching status. It shouldbe connected to the mains load switching device auxiliary contact.

    In Breaker Scheme A, Incorrect application of this signal does nottrigger an alarm condition, it is used solely for indication of the breakerstatus.

    In Breaker Scheme B this feedback is used for internal interlocking ofthe breaker outputs.

    Mains Load InhibitIEEE 37.2 - 3 checking orinterlocking relay

    This input is used to prevent the 300from loading the mains supply. Ifthe mains supply is already on load activating this input will cause the300to unload the mains supply. Removing the input will allow the mainsto be loaded again.

    NOTE: -This input only operates to control the mainsswitching device if the 300load switching logic is attempting toload the mains. It will not control the mains switching device when

    the generator is on load.Open / Close generatorIEEE 37.2 - 52 AC circuit breaker

    Allows connection of an external signal to control open and closing ofthe generator load switch device.

    Open / Close mainsIEEE 37.2 - 52 AC circuit breaker

    Allows connection of an external signal to control open and closing ofthe mains load switch device.

    Panel Lock Locks the module into the current operating mode.

    Remote Start off load If this input is active, operation will be similar to the Remote Start onload function except that the generator will not be instructed to take theload. This function can be used where an engine only run is requirede.g. for exercise.

    Remote Start on load When in auto mode, the module will perform the start sequence andtransfer load to the generator.In Manual mode, the load will be transferred to the generator if theengine is already running, however in manual mode, this input will not

    generate start/stop requests of the engine.Simulate Mains available This function is provided to override the modules internal monitoring

    function. If this input is active, the module will not respond to the state ofthe incoming AC mains supply.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    25/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 25

    6.5 OUTPUTS

    6.5.1 DIGITAL OUTPUTS

    Select if the relay is toenergiseor de-energise

    upon activation of the

    source

    Select what theoutput is to be

    used to control

    These labelsmatch thetypical wiringdiagram

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    26/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM26

    6.5.2 OUTPUT SOURCES

    The list of output sources available for configuration of the module relay outputs also applies to the LEDconfiguration and expansion relay outputs (7300 series only).

    Under the scope of IEEE 37.2, function numbers can also be used to represent functions in microprocessordevices and software programs. Where the DSE output functions can be represented by IEEE 37.2, the

    function number is listed below.

    Output source Activates Is not active.

    Not Used The output will not change state (Unused)

    Audible AlarmIEEE 37.2 74 alarm relay

    This output indicates that the internalsounder is operating to a llow it to feed anexternal sounder. Operation of the Mutepushbutton will reset this output once

    activated.

    Inactive if the internal sounder is notoperating.

    Battery Over VoltageIEEE 37.2 59DC overvoltage relay

    This output indicates that a Battery Overvoltage alarm has occurred.

    Inactive when battery voltage is not High

    Battery Under VoltageIEEE 37.2 27DC undervoltage relay

    This output indicates that a Battery UnderVoltage alarm has occurred.

    Inactive when battery voltage is not Low

    Close Gen OutputIEEE 37.2 52 ac circuit breaker

    Used to control the load switching device.Whenever the 6100 module selects thegenerator to be o n load this control sourcewill be active.

    Inactive whenever the generator is notrequired to be on load

    Close Gen Output PulseIEEE 37.2 52 ac circuit breaker

    Used to control the load switching device. Whenever the 6100 module selects thegenerator to be o n load this control source will be active for the duration of the BreakerClose Pulse timer, a fter which it will become inactive again.

    This output is not available when Breaker Scheme B is selected, use Close GenOutput instead.

    Close Mains OutputIEEE 37.2 52 ac circuit breaker

    Used to control the load switching device.Whenever the 6100 module selects the mains tobe on load this control source will be active.

    The output is inactive wheneverthe mains is not required to be onload

    Close Mains Output PulseIEEE 37.2 52 ac circuit breaker

    Used to control the load switching device. Whenever the 6100 module selects the mainsto be on load this control source will be active for the duration of the Breaker ClosePulse timer, af ter which it will become inactive again.

    This output is not available when Breaker Scheme B is selected, use Close MainsOutput instead.

    Combined Mains Failure Active when the mains supply is out of limits OR the input for Auxiliary Mains Failure isactive

    Common Warning Active when o ne or more Warningalarms areactive

    The output is inactive when nowarning alarms are present

    Cooling Down Active during the off load cooling runDigital Input A - K Active when the digital input is active Inactive when :

    If the input is not active If the input is active but

    conditioned by activation delay,safety timeror Armingrequirements.

    Elevator control Active during the elevator delaytime before aload transfer takes place and remains activefor the duration of the elevator delayafter atransfer takes place (when elevator posttransferis enabled.

    Inactive at a ll other times

    Generator Available Becomes active when the generator isavailable to take load.

    Inactive when

    Loading voltageand loadingfrequencyhave not been reached

    After electrical tripalarm

    During the starting sequencebefore the end of the warmingtimer.

    The outputs are in alphabeticalorder with the parameterfirst. Forinstance for overspeed output, its

    listed asEngine Overspeed.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    27/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 27

    Output source Activates Is not active.

    Generator failure Latched Activates when the generator failure alarm is ac tived. Reset by digital input configured toAlarm Reset

    Generator failure Unlatched Activates when the generator failure alarm is ac tived. Reset automatically when thegenerator becomes available

    Generator available Activates when the generator becomes available, is within configured limits and theauxiliary generator readyinput is active.

    Generator load inhibited Indicates that an input configured to Generator Load Inhibitis active, preventing the set

    from taking load.Generator available Activates when the generator becomes available. Ignores alarm conditions and thegenerator transient delay

    Mains failure Latched Activates when the mains failure alarm is ac tived. Reset by digital input configured toAlarm Reset

    Mains failure Unlatched Activates when the mains failure alarm is ac tived. Reset automatically when the mainsbecomes available

    Mains in limits Activates when the generator becomes available, is within configured limits and theauxiliary generator readyinput is active.

    Mains load inhibited Indicates that an input configured to Generator Load Inhibitis active, preventing the setfrom taking load.

    Mains available Activates when the generator becomes available. Ignores alarm conditions and thegenerator transient delay

    Open Gen OutputIEEE 37.2 52 ac circuit breaker

    Used to control the load switching device.Whenever the 300 module selects thegenerator to be off load this control source

    will be active.

    Inactive whenever the generator isrequired to be on load

    Open Gen Output PulseIEEE 37.2 52 ac circuit breaker

    Used to control the load switching device. Whenever the 300 module selects thegenerator to be off load this control source will be active for the duration of the BreakerOpen Pulse timer, after which it will become inactive again.

    This output is not available when Breaker Scheme B is selected, use Open GenOutput instead.

    Open Mains OutputIEEE 37.2 52 ac circuit breaker

    Used to control the load switching device.Whenever the 300 module selects themains to be off load this control source willbe active.

    The output is inactive whenever the mainsis required to be on load

    Open Mains Output PulseIEEE 37.2 52 ac circuit breaker

    Used to control the load switching device. Whenever the 300 module selects the mainsto be off load this control source will be active for the duration of the Breaker OpenPulse timer, af ter which it will become inactive again.

    This output is not available when Breaker Scheme B is selected, use Open MainsOutput instead.

    Return delay Indicates that the set is on load, and the mains is available, during the return delaytimers.

    Scheduled Run Active when the controller is requesting the set to run under control of the inbuiltScheduler.

    Start Delay The controller is in the start delaytimer, after which the set will be called to start.

    System in Auto Mode When the controller is in AUTO mode Inactive in any other mode.

    System in Manual Mode When the controller is in MANUAL mode Inactive in any other mode.

    System in Prohibit return Mode Becomes active when the generator is on load and the mains supply is healthy but aninput configured to Manual Restore is active.This can be used to signal to an operator that action is required before the set cantransfer back to the mains supply.

    System in Test on load Mode When the controller is in MANUAL mode Inactive in any other mode.

    Waiting for generator The controller has requested the generator to start and is waiting for i t to become

    available.Waiting for Manual Restore Becomes active when the generator is on load and the mains supply is healthy but an

    input configured to Manual Restore is active.This can be used to signal to an operator that action is required before the set cantransfer back to the mains supply.

    Warming up Active when the set is running off load, during the warming timer, before taking load.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    28/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM28

    6.6 TIMERS

    Many timers are associated with alarms. Where this occurs, the timer for the alarm is located on the samepage as the alarm setting. Timers not associated with an alarm are located on the timers page.The timerspage is subdivided into smaller sections. Select the required section with the mouse.

    6.6.1 START TIMERS

    Timer Description

    Mains Transient Delay Used to give a delay between the mains supply being measured out of limits, and acceptancethat the mains has failed. This can be used to prevent the generator starting caused by shortterm events on the mains supply.

    Start delay Used to give a delay before starting in AUTO mode. This timer is activated upon a remote startsignal being applied, or upon a start due to mains failure, scheduled run or any other automaticstart.Typically this timer is applied to prevent starting upon f leeting remote start signals or short termmains failures.

    Warming up time The amount of time that the set will run BEFORE being allowed to take load. This is used towarm the engine to prevent excessive wear.

    Generator Fail Delay The 332 instructs the set to start and waits for the period of this timer for the set to becomeavailable. If it is not available when the timer expires, the generator failurealarm is triggerred.

    Elevator Delay Use to delay the elevator controloutput before and after load transfer takes place. See sectionentitled Applicationfor details of elevator control.

    Click and drag to change the setting.Timers increment in steps of 1 second up toone minute, then in steps of 30 seconds upto 30minutes, then in steps of 30 minutesthereafter (where allowed by the limits of the

    timer).

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    29/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 29

    6.6.2 LOAD / STOPPING TIMERS

    Timer Description

    Transfer Time The time between the generator load switch being opened and the mains load switch beingclosed (or vice versa). Used to give time for the load switches to move to their correctpositions and to prevent the mechanical interlock from jamming.This timer can also be used to give a dead time to ensure that any machinery stops fully afterremoval of the supply, before applying the new supply to the equipment (for instance directlydriven AC motors).

    Breaker close pulse The amount of time that Breaker Close Pulsesignals will be present when the request toclose a breaker is given.

    Breaker Trip pulse The amount of time that Breaker Open Pulsesignals will be present when the request to opena breaker is given.

    Return delay A delay, used in auto mode only, that allows for short term removal of the request to stop theset before action is taken. This is usually used to ensure the set remains on load beforeaccepting that the start request has been removed.

    Cooling time The amount of time that the set will be made to run OFF LOAD before being stopped. This isto allow the set to cool down and is particularly important for engines with turbo chargers.

    Fail to stop delay If the set is called to stop and is still running after the fail to stopdelay, a Fail to Stopalarm isgenerated.

    Generator transientdelay

    Used to delay the generator under/over volts/frequency alarms. Typically this is used toprevent spurious shutdown alarms caused by large changes in load levels.

    6.6.3 MODULE TIMERS

    Timer Description

    LCD Page timer If the module is left unattended for the duration of the LCD Page Timerit will revert to showthe Statuspage.

    LCD Scroll Timer The scroll time between parameters on a selected page

    Click and drag to change the setting.Timers increment in steps of 1second upto one minute, then in steps of30seconds up to 30minutes, then in stepsof 30minutes thereafter (where allowedby the limits of the timer).

    If you need to change the timer by asmall amount, try clicking with themouse to the side of the adjust handle to the right (increase) or left (decrease).

    Alternatively once youve selected thetimer, you can use the left (decrease) or

    right (increase) keyboard keys.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    30/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM30

    6.7 GENERATOR

    The generatorpage is subdivided into smaller sections.

    Select the required section with the mouse.

    6.7.1 GENERATOR OPTIONS

    Select your ACsystem. A schematicis shown below withconnection detailsfrom the alternator

    to the DSE300Series module.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    31/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 31

    6.7.2 GENERATOR ALARMS

    Alarm IEEE designation

    Generator Under voltage IEEE 37.2 - 27AC Undervoltage relay

    Generator loading voltage The generator will not be permitted to take load until the loading voltage and loadingfrequency have been reached.

    Generator Under Frequency IEEE 37.2 -81 Frequency relay

    Generator loading Frequency The generator will not be permitted to take load until the loading voltage and loadingfrequency have been reached.

    Click to enable ordisable the alarms.The relevant valuesbelow will appeargreyed outif the

    alarm is disabled.

    Click and drag to change the

    setting.

    Type the valueor click the upand downarrows tochange the

    settings

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    32/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM32

    6.8 LOAD CURRENT

    Timer DescriptionEnable CT SupportNot available on DSE332 V1

    = CTs are not fitted. The ATS module will not include Load Amps on theinstrumentation display.= CTs are not fitted. The ATS module will display Load Amps.

    CT Primary Primary rating of the Current Transformers

    Full Load Rating This value should be set to the full load rating of the generator.

    Click and drag to change the

    setting.

    Type the valueor click the upand downarrows tochange the

    settings

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    33/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 33

    6.9 MAINS

    The mainspage is subdivided into smaller sections.Select the required section with the mouse.

    6.9.1 MAINS OPTIONS

    Timer Description

    ImmediateMains Dropout

    = Upon mains failure, the mains load switch will be kept closed until the generator is upto speed and volts.= Upon mains failure, the mains load switch will be opened immediately, subject to thesetting of the mains transient timer.

    AC System These settings are used to detail the type of AC system to which the module is connected:3 phase 4 wire, 1 phase 2 wire, 2 phase 3 wire L1-L2, 2 phase 3 wire L1-L3, 3 phase 3wire, 3 phase 4 wire delta

    This list is not exhaustive. DSE reserve the right to add to this list as part of our policy ofcontinual development

    If three phase loads arepresent, it is usually desirableto set this parameter totoenable Immediate MainsDropout.

    This is read only forinformation purposes. The ACsystem is configured in theGenerator Options page.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    34/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM34

    6.9.2 MAINS ALARMS

    Alarm IEEE designation

    Mains Under voltage IEEE 37.2 - 27AC Undervoltage relay

    Mains Over voltage IEEE 37.2 - 59AC Overvoltage relay

    Mains Under Frequency IEEE 37.2 -81 Frequency relay

    Mains Over Frequency IEEE 37.2 -81 Frequency relay

    Click and drag to change the

    setting.

    Type the valueor click the upand downarrows tochange the

    settings

    Click to enable ordisable the alarms.The relevant valuesbelow will appeargreyed outif the

    alarm is disabled.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    35/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 35

    6.10 PLANT BATTERY

    Alarm IEEE designation

    Plant Battery Undervolts IEEE 37.2 -27 DC Undervoltage relay

    Plant Battery Overvolts IEEE 37.2 -59 DC Overvoltage relay

    Click and drag to change the

    setting.

    Type the valueor click the upand downarrows tochange the

    settings

    Click to enable ordisable the option.The relevant valuesbelow will appeargreyed outif the

    alarm is disabled.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    36/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM36

    6.11 SCHEDULER

    The Exercise Scheduler is used to give up to 16 scheduled runs. This run schedule is configurable to repeatevery 7 days (weekly) or every 28 days (monthly) . The run can be on loador off load.

    Click to enable ordisable the option.The relevant valuesbelow will appeargreyed outif thealarm is disabled. Configure the

    required start time

    and run duration.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    37/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 37

    8 SCADA

    SCADA stands for Supervisory Control And Data Acquisition and is provided both as a service tool and alsoas a means of monitoring / controlling the generator set.

    As a service tool, the SCADA pages is to check the operation of the controllers inputs and outputs as well aschecking the generators operating parameters.

    When connection is made

    The SCADApage is subdivided into smaller sections.

    Select the required section with the mouse.

    Click to connect to

    the module

    Click to close theconnection to themodule

    The connectedmodules firmware

    revision number

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    38/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM38

    8.2 MIMIC

    This screen provides a mimic of the control module and allows the operator to change the control mode of themodule.

    Click the mimic buttons to

    control the module remotely

    Hint: Buttons may not operate if this hasbeen locked out by the Access securityfeature of the Configuration SuiteSoftware.Refer to your system supplier for details.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    39/44

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    40/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM40

    8.4 DIGITAL INPUTS

    8.5 DIGITAL OUTPUTS

    State of the input(open or closed tobattery negative)

    Shows if the input channel is active

    or not.

    State of theoutput (open orclosed)

    Shows if the output channel is active or not.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    41/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 41

    8.6 MAINS

    Shows the modules measurements of the mains supply.

    8.7 GENERATOR

    Shows the modules measurements of the generator supply.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    42/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM42

    8.8 LOAD

    Shows the modules measurements of the load.

    8.9 PLANT BATTERY

    Shows the measurement of the plant battery

    8.10 ALARMSShows any present alarm conditions.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    43/44

    DSE300 Series ATS Configuration Suite

    DSE300 Series configuration suite 057-106 ISSUE 2 AM 43

    8.11 STATUSShows the modules current status.

    8.12 EVENT LOG

    Shows the contents of the modules event log.

  • 8/12/2019 Dse332dse333 Pc Software Manual 2

    44/44

    DSE300 Series ATS Configuration Suite

    8.13 DATE AND TIME


Recommended