LOAD
AREA
FACTOR
EXITS
ROOM NAME
PANIC
*.02
#OCC
Width
n
1
A101
SIM
1
A101
SIM
AA
0
A0.00
A1
A2A4
A3
A0.00
A1
1
A101
SIM
NameElevation
NORTH ARROW
OVERLAY ARROW INDICATES TRUE NORTH
SHADED AREA INDICATES PLAN NORTH
SECTION CALLOUT
INDICATES A SIMILAR CONDITION
LOCATION ON SHEET
DETAIL CALLOUT
ELEVATION CALLOUT
INTERIOR ELEVATION CALLOUT
INTERIOR ELEVATION ORENTATION
ILOCATION ON SHEET
SHEET WHERE ELEVATION IS DRAWN
DETAIL CALLOUT
CONTROL OR DATUM POINT
NAME OF ELEVATION (IF APPLICABLE)
ELEVATION ABOVE FINISHED FLOOR
GRID BUBBLE
GRID NUMBER
DEMOLITION KEYNOTE
KEYNOTE NUMBER (SEE LEGEND ON SHEET)
NEW CONSTRUCTION KEYNOTE
KEYNOTE NUMBER (SEE LEGEND ON SHEET)
DOOR CALLOUT
DOOR NUMBER
WINDOW CALLOUT
WINDOW NUMBER
(SEE WINDOW SCHEDULE A9.12 - A9.13)
ROOM EXITING INFORMATION
AREA (SQ FT)
OCCUPANT LOAD FACTOR (REFER TO TABLE 1004.1.1)
OCCUPANT LOAD (AREA DIVIDED BY LOAD FACTOR)
SHEET WHERE SECTION IS DRAWN
INDICATES A SIMILAR CONDITION
LOCATION ON SHEET
SHEET WHERE SECTION IS DRAWN
LOCATION ON SHEET
SHEET WHERE ELEVATION IS DRAWN
INDICATES A SIMILAR CONDITION
LOCATION ON SHEET
SHEET WHERE SECTION IS DRAWN
NUMBER OF EXITS REQUIRED (REFER TO TABLE 1015.1)
DOOR EXITING INFORMATION
NUMBER OF OCCUPANTS EXITING THRU DOOR OPENING
REQUIRED EXIT WIDTH (OCCUPANT LOAD X 0.2)
PROVIDED EXIT WIDTH (IN INCHES)
PANIC EXIT HARDEWARE (WHERE OCCURS)
?
?
?
22
22
5
CIVIC CENTER DRIVE W
W 1ST STREET
W 17TH STREET
FLO
WE
R S
T
MA
IN S
T
BR
IST
OL S
T
FA
IRV
IEW
ST
HA
RB
OR
BLV
D
PROJECT SITE:
1530 W 17TH STREETSANTA ANA, CA 92706
n
Project Title
Agency ApprovalConsultant Seal
Drawing Title
Designed:
Drawn:
Checked:
Reviewed:
Date:
Project No.
Scale:
Drawing No.
Architect's Seal
IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT
OFFICE OF REGULATION SERVICES
APPL.
AC
DATE
FLS SS
04-
TELEPHONE:FAX:Architecture . Planning . Interior DesignWWW.HMCARCHITECTS.COM
ARCHITECTS3546 CONCOURS STREETONTARIO, CALIFORNIA 91764
909.483.1400909.989.9979
www.sac.edu
MDJ
JD,DR
JD
JD
HMC ARCHITECTSSM
FILE NO. 30-C2
010203040506070809
J
H
G
F
E
D
C
B
A
J
H
G
F
E
D
C
B
A
010203040506070809
KEV
INM. WILKESON
NO. C-20601
REN. 03- 31- 13ST
ATEOF CAL I FORN
IA
LIC
ENSED ARCHITECT
(714) 564-6000
1530 W 17th StreetSanta Ana, CA 92706
Rancho Santiago Community College DistrictSanta Ana College
Dunlap Hall4th Floor Restroom Alteration
C:\
Revit L
ocal F
iles\5
002011000_A
14_R
estr
oom
s_kdoan.r
vt
6/6/2016 9:46:56 AM
As indicated
4TH FLOOR RESTROOM ALTERATION BID
G0.1
COVER SHEET
5002011-00
SANTA ANA COLLEGE - DUNLAP HALL
8/07/2012
DUNLAP HALL - 4th FLOOR RESTROOM ALTERATION
RANCHO SANTIAGO COMMUNITY COLLEGE DISTRICT
1530 WEST 17TH STREET
BKF ENGINEERS
CIVIL
600 SOUTH MAIN STREET, SUITE 920ORANGE, CA 92868
(714) 415-0500
CDTLA
LANDSCAPE
1903 ST SIMONS PLACEFULLERTON, CA 92831
(714) 928-5107
HMC ARCHITECTS
ARCHITECT
2601 MAIN STREET, STUDIO 100IRVINE, CA 92614
(949) 567-1833
RODRIGUEZ ENG
STRUCTURAL
1411 BATAVIA STREET, SUITE 121ORANGE, CA 92867
(714) 998-2300
IDS GROUP
MECHANICAL
1 PETERS CYN ROAD, SUITE 130IRVINE, CA 92606
(949) 387-8500
IDS GROUP
PLUMBING
1 PETERS CYN ROAD, SUITE 130IRVINE, CA 92606
(949) 387-8500
P2S ENGINEERING
ELECTRICAL
5000 EAST SPRING STREET, 8TH FLRLONG BEACH, CA 90815-5218
(562) 497-2999
RANCHO SANTIAGO CCD
OWNER
2323 NORTH BROADWAYSANTA ANA, CA 92706
(714) 480-7517
SANTA ANA COMMUNITY COLLEGE
SANTA ANA, CA 92706
ABBREVIATIONSØ DIAMETER OR ROUND+/- PLUS/MINUS# POUND OR NUMBER% PERCENT@ AT° DEGREE℄ CENTER LINE∠ ANGLE⅊ PROPERTY LINEAB ANCHOR BOLTABS ABSOLUTEAC ASPHALTIC CONCRETEACC ACCESSIBLE WORK STATIONACOUS ACOUSTICALADJ ADJACENTAFF ABOVE FINISH FLOORALUM ALUMINIUMANSI AMERICAN NATIONAL
STANDARDS INSTITUTEARCH ARCHITECTURALBD BOARDBLDG BUILDINGBLK BLOCKBLKG BLOCKINGBTWN BETWEENC CHANNELCER CERAMICCF CUBIC FEETCFCI CONTRACTOR FURNISHED,
CONTRACTOR INSTALLEDCFOI CONTRACTOR FURNISHED,
OWNER INSTALLEDCJ CONTROL JOINTCLG CEILING
CLR CLEARCMU CONCRETE MASONRY UNITCONC CONCRETECONT CONTINUOUSCORR CORRIDORCR CLASSROOMCTSK COUNTER SUNKCTC CENTER TO CENTERd PENNYDBL DOUBLEDEL DELETEDET DETAILDF DRINKING FOUNTAINDIA DIAMETERDIM DIMENSIONDL DOOR LOUVERDN DOWNDP DISABLED PERSON ACCESSIBLEDS DOWNSPOUTDWG DRAWINGEA EACHEJ EXPANSION JOINTELEV ELEVATIONELEC ELECTRICALEMT ELECTRICAL METAL TUBINGENCL ENCLOSUREENGR ENGINEEREOS EDGE OF SLABEQ EQUALEQPT EQUIPMENTEW EACH WAY(E) EXISTINGEXP ECPANSIONEXT EXTERIOR
FA FIRE ALARMFD FLOOR DRAINFDC FIRE DEPARTMENT CONNECTIONFDN FOUNDATIONFE FIRE EXTINGUISHERFEC FIRE EXTINGUISHER W/CABINETFF FINISH FLOORFG FINISH GRADEFH FIRE HYDRANTFHC FIRE HOSE W/ CABINETFHWS FLAT HEAD WOOD SCREWFL FLOORFO FACE OFFOC FACE OF CONCRETEFOF FACE OF FINISHFOM FACE OF MASONRYFOS FACE OF STUDFS FINISH SURFACEFT FOOT OF FEETFTG FOOTINGGA GAUGEGALV GALVANIZEDGB GYPSUM BOARDGFRC GLASS FIBER REINFORCED CONCRETEGYP GYPSUMHB HOSE BIBHDWE HARDWAREHM HOLLOW METALHOR HORIZONTALHR HOURHVAC HEATING VENTILATION AIRID INSIDE DIAMETERIN INCH OR INCHESINT INTERIOR
INV INVERTJBOX JUNCTION BOXJAN JANITOR CLOSETLAV LAVATORYLB(S) POUND(S)MAX MAXIMUMMB MACHINE BOLTMDF MEDIUM DENSITY FIBERBOARDMFR MANUFACTURERMH MANHOLEMIN MINIMUMMISC MISCELLANEOUSMO MASONRY OPENINGMTL METAL(N) NEWNIC NOT IN CONTRACTNO NUMBERNR NON RATEDNTS NOT TO SCALENTS NOT TO SCALEO/ OVEROA OVERALLOC ON CENTEROD OUTSIDE DIAMETEROFCI OWNER-FURNISHED
CONTRACTOR-INSTALLEDOFOI OWNER-FURNISHED
OWNER-INSTALLEDOH OVERHANGOTO OUT TO OUTPA PUBLIC ADDRESSPE PAD ELEVATIONPERP PERPENDICULARPH PANIC HARDWARE
PIV POST INDICATOR VALVEPL PLATEPLAM PLASTIC LAMINATEPLUMB PLUMBINGPLYWD PLYWOODPM PARTITION MOUNTEDPOC POINT OF CONNECTIONPR PAIRPREP PREPAREPSF POUNDS PER SQUARE FOOTPSI POUNDS PER SQUARE INCHPVC POLYVINYL CHLORIDER RISER, RADIUSRD ROOF DRAINREC RECESSEDREF REFERENCEREQ REQUIREDRM ROOMRWL RAIN WATER LEADERRO ROUGH OPENINGSCHED SCHEDULESECT SECTIONSF SQUARE FEETSHT SHEETSIM SIMILARSM SURFACE MOUNTEDSMS SHEET METAL SCREWSOV SHUT OFF VALVESPEC SPECIFICATIONSST STAINLESS STEELSTD STANDARDSTL STEELSTRUCT STRUCTURALT&B TOP AND BOTTOM
TEMP TEMPORARYTO TOP OFTOC TOP OF CURBTOD TOP OF DRAINTOP TOP OF PARAPETTOPL TOP OF PLATETOR TOP OF RIDGETOS TOP OF SLABTOW TOP OF WALLTST TOP OF STEELTV TELEVISIONTYP TYPICALUC UNERCUTUNO UNLESS NOTED OTHERWISEVCT VINYL COMPOSITION TILEVERT BERTICALW WIDE FLANGEW/ WITHW/O WITHOUTWD WOODWH WATER HEATERWI WOODWORK INSTITUTEWIN WINDOWWP WATERPROOFWS WOOD SCREWWT WEIGHTWWF WELDED WIRE FABRICx BYYD YARD
NOTE:OTHER ABBREVIATIONS USED ON THESE DRAWINGS ARECONSIDERED STANDARDS IN THE BUILDING INDUSTRY.CONTACT ARCHITECT FOR NECESSARY CLARIFICATION.
APPLICABLE CODES2010 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R.
2010 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R.(2009 INTERNATIONAL BUILDING CODE OF THE INTERNATIONAL CODE COUNCIL,WITH CALIFORNIA AMENDMENTS)
2010 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R.(2008 NATIONAL ELECTRICAL CODE OF THE NATIONAL FIRE PROTECTIONASSOCIATION, NFPA)
2010 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R.(2009 UNIFORM MECHANICAL CODE OF THE INTERNATIONAL ASSOCIATIONS OFPLUMBING AND MECHANICAL OFFICIALS, IAPMO)
2010 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R.(2009 UNIFORM PLUMBING CODE OF THE INTERNATIONAL ASSOCIATION OFPLUMBING AND MECHANICAL OFFICIALS, IAPMO)
2010 CALIFORNIA ENERGY CODE, PART 6, TITLE 24 C.C.R.
2010 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R.(2009 INTERNATIONAL FIRE CODE OF THE INTERNATIONAL CODE COUNCIL)
2010 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN CODE), PART 11,TITLE 24 C.C.R.
2010 CALIFORNIA REFERENCED STANDARDS CODE, PART 12, TITLE 24 C.C.R.
2010 TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.
AMERICANS WITH DISABILITIES ACT
PARTIAL LIST OF APPLICABLE STANDARDS
NFPA 13 AUTOMATIC SPRINKLER SYSTEMS, 2010 EDITION
NFPA 14 STANDPIPE SYSTEMS (CALIFORNIA AMENDED), 2007 EDITION
NFPA 17AWET CHEMICAL SYSTEMS, 2002 EDITION
NFPA 20 STATIONARY PUMPS, 2007 EDITION
NFPA 24 PRIVATE FIRE MAINS (CALIFORNIA AMENDED), 2010 EDITION
NFPA 72 NATIONAL FIRE ALARM CODE (CALIFORNIA AMENDED) , 2010EDITION
NFPA 80 FIRE DOOR AND OTHER OPENING PROTECTIVES, 2007 EDITION
NFPA 2001 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS, 2008 EDITION
REFERENCE CODE SECTION FOR NFPA STANDARDS - 2010 CALIFORNIA BUILDING CODE(SFM) CHAPTER 35.
SEE CHAPTER 35 FOR STATE OF CALIFORNIA AMENDMENTS TO NFPA STANDARDS.
SYMBOL LEGEND
VICINITY MAP
1. VERIFY ALL DIMENSIONS, LOCATIONS OF EXISTING UTILITIES, ANDCONDITIONS ON THE JOB SITE PRIOR TO THE START OF WORK ORPORTIONS OF THE WORK. NOTIFY THE ARCHITECT IMMEDIATELY OFANY DISCREPANCIES BETWEEN THE ACTUAL FIELD CONDITIONS ANDTHE CONSTRUCTION DOCUMENTS. EXISTING CONDITIONS AREINDICATED AS A RESULT OF FIELD OBSERVATIONS, INFORMATIONSHOWN ON AVAILABLE DOCUMENTS AND FIELD CONDITIONS AT THETIME OF PREPARATION.
2. ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH ALLGOVERNING CODES, ORDINANCES, REGULATIONS AND LAWS.
3. THE DESIGN ADEQUACY AND SAFETY OF ERECTION BRACING,SHORING, TEMPORARY SUPPORTS AND SCAFFOLDING IS THE SOLERESPONSIBILITY OF THE CONTRACTOR.
4. WHERE ANY CONFLICT OCCURS BETWEEN THE REQUIREMENTS OFLAWS, CODES, ORDINANCES, RULES AND REGULATIONS, THE MOSTSTRINGENT SHALL GOVERN.
5. IN NO CASE SHALL WORKING DIMENSIONS BE SCALED FROM PLANS,SECTIONS OR DETAILS ON THE DRAWINGS.
6. DETAILS MARKED 'TYPICAL' SHALL APPLY IN ALL CASES UNLESSSPECIFICALLY NOTED OTHERWISE.
7. WHERE NO SPECIFIC DETAIL IS SHOWN, THE FRAMING ORCONSTRUCTION SHALL BE IDENTICAL OR SIMILAR TO THAT INDICATEDFOR LIKE CASES OF CONSTRUCTION.
8. ENACT ALL MEASURES TO PROTECT AND SAFEGUARD ALL EXISTINGELEMENTS TO REMAIN FROM BEING DAMAGED. REPLACE OR REPAIREXISTING ELEMENTS DAMAGED BY THE EXECUTION OF THISCONTRACT TO EQUAL OR BETTER CONDITION.
9. WHERE NEW CONSTRUCTION ABUTS EXISTING FINISHEDSURFACES, CONTRACTOR SHALL ALIGN NEW CONSTRUCTION SOTHAT NEW FINISHES ARE FLUSH WITH EXISTING. MATCH EXISTINGTEXTURES AND COLORS.
10. PRIOR TO THE START OF WORK THE CONTRACTOR SHALLCOORDINATE BETWEEN THE REQUIREMENTS OF ALL DISCIPLINESHEREIN AND BETWEEN THE REQUIREMENTS OF ALL DRAWINGS ANDSPECIFICATIONS IN ORDER THAT ALL ITEMS SATISFACTORILY RELATETO ONE ANOTHER. NOTIFY ARCHITECT IMMEDIATELY REGARDING ANYITEMS THAT CANNOT BE COORDINATED.
11. CONTRACTOR SHALL EXCERCISE EXTREME CAUTION INEXCAVATING AND TRENCHING ON THIS SITE TO AVOIDEXISTING DUCTS, PIPING, CONDUIT, ETC. AND TO PREVENT HAZARDTO PERSONNEL AND/OR TO EXISTING UNDERGROUND UTILITIES ORSTRUCTURES. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THEARCHITECT SHOULD SUCH UNIDENTIFIED CONDITIONS BEDISCOVERED. THESE DRAWINGS AND SPECIFICATIONS DO NOTINCLUDE THE NECESSARY COMPONENTS FOR CONSTRUCTIONSAFETY.
12. CHANGES TO THE APPROVED DRAWINGS AND/OR SPECIFICATIONSSHALL BE MADE BY ADDENDA OR A CHANGE ORDER APPROVED BYTHE DIVISION OF THE STATE ARCHITECT, AS REQUIRED BY SECTION 4-338, PART 1, TITLE 24, C.C.R..
13. A CLASS 1 CERTIFIED PROJECT INSPECTOR, EMPLOYED BY THEDISTRICT (OWNER) AND APPROVED BY THE DIVISION OF THE STATEARCHITECT, SHALL PROVIDE CONTINUOUS INSPECTION OF THE WORK.THE DUTIES OF THE INSPECTOR ARE DEFINED IN SECTION 4-342, PART1, TITLE 24, C.C.R..
14. ALL DIMENSIONS ARE TO GRID LINES, FACE OF CONCRETE, FACEOF CONCRETE MASONRY UNITS OR FACE OF STUDS, UNLESS NOTEDOTHERWISE.
15. CONTRACTOR'S SAFETY BARRICADE (TEMPORARY FENCING)SHALL BE PROVIDED BY CONTRACTOR TO PROTECT STUDENTS,FACULTY, STAFF AND PUBLIC FROM CONSTRUCTION ACTIVITIES.CONTRACTOR'S SAFETY BARRICADE SHALL PROTECT AND SECURECONSTRUCTION AREA. TEMPORARY FENCING SHALL ALSO BEPROVIDED BY CONTRACTOR TO PROTECT AND SECURE STORAGEYARDS. EXACT LOCATION OF CONTRACTOR'S SAFETY BARRICADE ANDOTHER TEMPORARY FENCING SHALL BE APPROVED BY THECONSTRUCTION MANAGER PRIOR TO INSTALLATION.
16. CUTTING, BORING, SAWCUTTING OR DRILLING THROUGH THEEXISTING OR NEW STRUCTURAL ELEMENTS IS NOT TO BE STARTEDUNTIL THE DETAILS HAVE BEEN REVIEWED AND APPROVED BY THEARCHITECT, STRUCTURAL ENGINEER AND THE D.S.A. FIELD ENGINEERIF DETAILS ARE NOT SHOWN OR DO NOT CONFORM TO THEAPPROVED DRAWINGS.
17. COMPLY W/ CFC CHAPTER 14 FOR FIRE SAFETY DURINGDEMOLITION AND CONSTRUCTION
18. FIREPROOFING OF STRUCTURAL MEMBERS MAY NOT BEGRAPHICALLY INDICATED IN SECTIONS OR DETAILS. REFERENCESHEET G0.2 FOR PROJECT FIREPROOFING REQUIREMENTS.
GENERAL NOTES PROJECT TEAM
LERCH BATES, INC
VERTICAL TRANSPORTATION
14649 VINTAGE DRIVESAN DIEGO, CA 92129
(949) 567-1833
SHEET INDEX (3 SHEETS)
GENERAL (2 SHEETS)
ARCHITECT (9 SHEETS)
SCOPE OF WORK STATEMENT
ALTERATIONS TO 4th FLOOR MEN RESTROOM.1. REMOVE EXISTING URINALS AND RELOCATE AS SHOWN2. REMOVE AND RELOCATE EXISTING LAVORATORIES AND MIRRORS AND RELOCATEAS SHOWN3. RELOCATE EXISTING URINAL PARTITION AND RELOCATE AS SHOWN4. REMOVE WALL TILES AND DRYWALL AS NECESSARY TO MODIFY PLUMBING FORNEW INSTALLATION5. PATCH AND REPAIR WALLS, AND REPLACE TILES TO MATCH EXISTING FINISH
A8.2 INTERIOR ELEVATIONS
A10.6 INTERIOR DETAILS
G0.1 COVER SHEET
No. Description Date
ATTACHMENT B
A8.24D
4A
4B
4C
A8.23D
3A
3B
3C
A8.22
MEN'S RRD439
WOMEN'S RRD437
FD
FD
.
.
SHAFT
SHAFT
CUSTODIALD436
ELECD449
STAIR 4D438
(NIC)
32" CLR
FO
S
5' -
1"
MIN
CLR5'
- 0"
5' - 0"
30x48 30x48
8' -
0"
CLR
5' -
0"
30x4830x48
MIN
CLR5'
- 0"
1'-6"
CLR
CLR
.
3' -
8"
1' - 2"
10.08
22.02
TYPOF 3
TYPOF 2
18" CLR.
24' - 3 1/2"
4' -
0"
1' -
0"
56"
MIN
.
60"
MIN
.
CLR
.
2' -
10"
MIN
.
1' - 6"
0' - 4"
1' - 6"
12". 24".
30x48
22.04
26.01
10.2010.20
1' - 6"
G
2' - 0"
C
C
FO
W
FO
S
DG
1' -
0"
1' -
8"
1' -
2"
FOW
FOS
22.02
REMOVE (E) LAVATORY & MIRROR(TYP OF 2)RELOCATE AS SHOWN(TYP OF 2)
REMOVE (E) URINAL (TYP OF 2)
RELOCATE AS SHOWN
MIN
CLR5'
- 0"
(E) HAND DRYER - TOREMAIN
5' -
6"
(E)
2' -
2"
3' -
4"
26.01 (E)10.22
10.07
09.03
09.02
09.01
7' -
0"
09.03 09.03
09.01
13 F
ULL T
ILE
S
6' -
6"
0' -
6"
26.01
(E) FINISH HAND DRYER TOREMAIN
(E)
09.03
09.02
7' -
0"
TYPOF 2
09.01
09.0209.03
09.01
7' -
0"
09.07
TYP. OF 2
10.09
PATCH AND REPAIR WALL WHERETOILET FIXTURE AND TILE IS REMOVED.MATCH (E) CONSTRUCTION & FINISH
09.03
09.02
09.01
7' -
0"
26.01 TYP.OF 2
09.0309.02
09.0110.02
OPEN
09.0309.02
09.03
09.02
7' -
0"
09.01
26.01 TYP.OF 2
10.09TYP
OF 3
09.03 09.0209.03
09.02
7' -
0"
09.07
(E) PAINTED CONC
(E) CMU (E) PLASTER
(E) PAINTEDCONC
(E) CMU09.04 09.05
1. DIMENSIONS @ RESTROOMS ARE FROM FINISHED FACE OF WALL, TYP U.N.O.
2. SEE SHEET A10.6 FOR TYP. ACCESSORY & FIXTURE MTG. LOCATION REQUIREMENTS
6" MTL STUD WALL ..................................1/A10.2
6" MTL STUD WALLW/ CMU VENEER ..................................1/A10.2
1-HR FIRE RATED 8"MTL STUD WALL ..................................1/A10.2
WALL LEGEND
3-5/8" MTL STUD WALL ..................................1/A10.2
CONCRETE WALL ..................................1/A10.2
3-5/8" MTL STUDINTERIOR WALL ..................................1/A10.2
A
B
C
D
E
F
1-HR CONCRETE WALL ..................................1/A10.2
2-HR CONCRETE WALL ..................................1/A10.2
2-1/2" MTL STUD WALL ..................................1/A10.2G
NOTES
KEYNOTES
Project Title
Agency ApprovalConsultant Seal
Drawing Title
Designed:
Drawn:
Checked:
Reviewed:
Date:
Project No.
Scale:
Drawing No.
Architect's Seal
IDENTIFICATION STAMP. OF THE STATE ARCHITECT
OFFICE OF REGULATION SERVICES
APPL.
AC
DATE
FLS SS
04-112285
TELEPHONE:FAX:Architecture . Planning . Interior DesignWWW.HMCARCHITECTS.COM
ARCHITECTS3546 CONCOURS STREETONTARIO, CALIFORNIA 91764
909.483.1400909.989.9979
www.sac.edu
MDJ
JD,DR
JD
JD
HMC ARCHITECTSSM
FILE NO. 30-C2
010203040506070809
J
H
G
F
E
D
C
B
A
J
H
G
F
E
D
C
B
A
010203040506070809
KEV
INM. WILKESON
NO. C-20601
REN. 03- 31- 15ST
ATEOF CAL I FORN
IA
LIC
ENSED ARCHITECT
(714) 564-6000
1530 W 17th StreetSanta Ana, CA 92706
Rancho Santiago Community College DistrictSanta Ana College
Dunlap Hall Addition & Alterations
C:\
Revit L
ocal F
iles\5
002011000_A
14_R
estr
oom
s_kdoan.r
vt
6/6/2016 9:46:53 AM
As indicated
4TH FLOOR RESTROOM ALTERATION BID
A8.2
INTERIOR ELEVATIONS
5002011-00
SANTA ANA COLLEGE - DUNLAP HALL
8/07/2012 1/4" = 1'-0"
14TH FLR RESTROOM PLAN
DA B C
DA B C
4D439 MENS RESTROOM INTERIOR ELEVATIONS
1/4" = 1'-0"
3D437 WOMENS RESTROOM INTERIOR ELEVATIONS
1/4" = 1'-0"
1/4" = 1'-0"
24TH FLR BREEZEWAY ELEVATION
NO. DESCRIPTION
09.01 PAINTED GYP BD
09.02 CERAMIC WALL TILE TO BE CT1 STANDARD GRID PATTERN - SEE SPECIFICATION SECTION 09 06 00
09.03 TILE BASE
09.04 EXT PLASTER
09.05 PATCH & REPAIR (E) PLASTER
09.07 CERAMIC WALL TILE TO BE CT2 STANDARD GRID PATTERN - SEE SPECIFICATION SECTION 09 06 00
10.02 GRAB BAR (4/A10.6)
10.07 URINAL SCREEN (6/A10.6)
10.08 TOILET PARTITION (5 & 6/A10.6)
10.09 MIRROR (1/A10.6)
10.20 TOILET TISSUE DISPENSER
10.22 (N) 18" WIDE X 72" HIGH FLOOR MOUNTED PRIMARY PARTITION
22.02 LAVATORY (1/A10.6) (PLUMBING)
22.03 URINAL (1/A10.6) (PLUMBING)
22.04 DRINKING FOUNTAIN (9/A10.6) (PLUMBING)
26.01 ELECTRIC HAND DRYER (1/A10.6)
No. Description Date
CCD 7/1/14
1
1
1
1
11
11
REVISION 1 4/14/16
1
1
1
SECTION
FINISH
HANDRAIL/GRAB BAR
NOTE:ALL SCREWS MUST BEINTO 18 GA PLATE10 GA STL PL
T&B OFTRACKEA END 1/8
1
600T200- 16 GA
1/81/2 - 5
MIN 16 GAMTL STUDS
6" X 18 GA
(3) 1/4"∅ SMSFROM MOUNTINGKIT
11 _ 2"
MIN
A
A
ALTERNATIVE DIMENSIONS IN INCHES
Toilet centering from wall
A E K FED
(Inches) Children
A = ADULT DIMENSIONS (AGE 12 AND OVER)E = ELEMENTARY SCHOOL DIMENSIONSK = KINDERGARTEN AND PRE- SCHOOL DIMENSIONSFED = ADAAG DIMENSIONS FOR CHILDREN AGE 12 AND YOUNGER, SHOWN FOR REFERENCE ONLY
(Inches) (Inches)a
b
c
d
e
f
g
h
i
j
k
l
m
n
o
18 15 12 12-18
Toilet seat height/ dimensions to top of seat 17-19 14-16 11-12 11-17
Grab bar height (centerline) 33 27 20-22 18-27
Toilet paper above floor (centerline) 19 min. - - 14-19
Toilet paper in front of toilet 12 max 6 max 6 max -
Napkin disposal in front of toilet 12 max 12 max N/A -
Dispenser height 40 max 36 max 32 max -
Mirror height (to bottom of glass) 40 max 34 max 32 max 34 max
Lavatory/ sink top height 34 max 31 max 24 max 31 max
Lavatory apron clearance 29 min - - 24 min*
Lavatory/ sink knee clearance 27 min 24 min 19 min 24 min*
Urinal lip height 17 max 15 max 13 min -
Urinal, toilet flush handle height 44 max 36 max 32 max 36 max
Drinking fountain bubbler height 36 max 32 max 30 max 30 max
Drinking fountain knee clearance 27 min 24 min 22 min -
NOTE:NO ADAAG REQUIREMENT IF ELEMENT IS USED PRIMARILY BY CHILDREN AGES 5 AND
YOUNGER AND IF CLEAR FLOOR AND PARALLEL APPROACH IS PROVIDED.
F.F.
1 1
/2".
NOTES:REFER TO TILE COUNCIL OF AMERICA HANDBOOK:F121-03 FOR ADDITIONAL DESIGN INFORMATIONPROVIDE CONTROL JOINTS 12'-0" O.C. MAX. U.N.O.
FLOOR TILE
MORTAR BED, SLOPE TODRAIN
SEALANT & BACKER RODw/ COMPRESSABLEBACK-UP
WATERPROOF MEMBRANE
CONTROL JOINTDEPRESSED CONCRETE SLAB
REINFORCING
FLOOR DRAIN
FLOOR DRAIN PIPE
DEPRESSEDCONCRETE SLAB
MORTAR BED
1/2" MAX.
2'-0". 2'-0".
FLOOR TILE
SLOPE2% MAX.
SLOPE2% MAX.
STILE
SHOE
3/8" DRILLED ANCHORw/ WASHER & NUTSREF TO STRUCT DWGS
LEVELING PLATE
CONCRETE SLAB
EXPANSION ANCHOR, TYPPER MFR'S RECOMMENDATION
METAL STUDWALL ASSEMBLY
CERMAIC TILEWHERE OCCURS
PARTITION PANELOR WALL POST
BACKINGREF
MOUNTING BRACKET
SHT MTL SCREW &SPACER
NOTE:VERIFY w/ PARTITION MFRFOR BACKING LOCATIONS
MINIMUM OF 1-1/4"OF STUD MUST EXTENDOUT OF FINISHED WALL
HIGH-LOW DRINKINGFOUNTAIN
FINISH WALL OVERMOUNTINGPLATE AND BEHIND BACKPANEL
600XXC16 CONT.NOTCHED STUDANCHOR BACKINGTO STUDS MIN.
LOCATE MTL STUD@ MOUNTINGLOCATIONS
MOUNTING PLATE(BEHIND WALL FINISH)
USE (3) #10 S.M.S TYP.
BACKING TOP & BOTT.
48" MIN SEE PLAN
SE
E P
LA
N
18"
MIN
NO
TE
#2
ACCCESSIBLE DF
18"- 19" MIN.
NO
TE
#1 (
T0 B
UB
BLE
R)
NO
TE
#2
CLR.
17" MIN
MIN.
8"
MAX.
6"
MIN
.
9"
EQ EQ
*
NO
TE
#1 (
TO
BU
BB
LE
R)
FOR WALL ATTACHMENT- REF
*16" MIN. IFALCOVE DEPTH IS< 24"
*19" MIN. IFALCOVE DEPTH IS> 24"
ACCESSIBLE D.F.
PLAN
ELEVATION
SECTION
- UNDERSIDE OF DF.SHALL BE FREE OFSHARP OR ABRASIVEEDGES OR SURFACES
AREA OUTSIDE HATCHSHALL BE CLEAR
ACCESSIBLE MOUNTING HEIGHTS:
NOTE #1: 36" MAXNOTE #2: 27" MIN CLR
ACCESSIBLE D.F.
A10.6
10
6" MAX.
SANITARYNAPKINVENDOR
HAND DRYER
CENTER OFCOIN SLOTS
SANITARYNAPKIN
DISPOSAL
SANITARYNAPKINDISPOSALTISSUEDISPENSER
SEAT COVERDISPENSER
TOILETTISSUEDISPENSERB-388
SANITARYNAPKIN
DISPOSALB-353
SENSOR/SWITCH
36"
MAX
"g"
12"MAX
18"
MAX
12"MAX.
20"
"b"
20"
MIRRORSOAP DISPENSERLAVATORY FRONT
BOTTOMOFGLASS
URINAL SCREENWHERE OCCURS
NOTES:
1. WATER CLOSET FLUSH VALVE TO BE LOCATED TO THE WIDE SIDE OF COMPARTMENT2. LAVATORY DRAIN & HOT WATER PIPING SHALL BE INSULATED WITH NO SHARP OR ABRASIVE ELEMENTS UNDER LAVATORY
3. REF FOR DIMENSIONS
4. REF FOR ACCESSORY MOUNTING/BACKING
STANDARDURINAL
ACCESSIBLEURINAL
EQ EQ
30" MIN
CLR
2'-0"
"I"
"m"
1'-2" MIN.1'-5" MAX.
18"
29"
MIN
.
F.O
.F.
"g"
MIRRORWHERE OCCURS
1'-5"MIN
9"
MIN
"k" "j" "i"
6"MAX 8" MIN
"h"
LAVATORY SIDE
UTILITY SHELF
.36"
MAX.
.1 1
/2"
CLR
.
"c"
CL
2' - 0" 1' - 0"
1' - 6"
FLUSHVALVE
5' -
0"
A
B
B-1
C
D
E
PANELTYPE
PANELLENGTH
5' - 10"
5' - 5 1/2"
5' - 5 1/2" (F.V)
6' - 0"
5' - 0"
3' - 4"
AA
BB
CC
DD
EE
FF
GG
PANEL TYPE @ CORNER CONDITION
5' - 10" (F.V)
3' - 4" (F.V)
3' - 0" (F.V)
4' - 10" (F.V)
3' - 3" (F.V)
5' - 0" (F.V)
3' - 5 1/2" (F.V)
PANELTYPE
PANELLENGTH
DETAIL
4/A10.1
4/A10.1
4/A10.1
4/A10.1
4/A10.1
4/A10.1
5/A10.1
5/A10.1
6/A10.1
5/A10.1
6/A10.1
5/A10.1
6/A10.1
DETAIL
PANEL TYPE AT (E) BUILDING
S-1
S-2
PANEL TYPE @ STAIRS
3' - 2" (F.V)
4' - 8" (F.V)
PANELTYPE
PANELLENGTH
4/A5.2
5/A5.2
DETAIL
SS BALUSTER
PERFORATED AL PANEL
(E) CONC SLAB
1' -
10 3
/4"
(E) CONC SLAB WHERE OCCURS @EAST & WEST BALCONIES
1' -
7 1
/2"
(E)
1' -
6 3
/4"
(E)
0' -
3 1
/4"
0' -
0 3
/4"
SS RAILING
PANEL ATTACHMENT-REFREF STRUCT FOR
INFILL OF (E)GUARDRAIL EMBEDHOLES & SLAB REPAIR
3' -
6"
0' -
0 3
/4"
(E) 3/4" CHAMFER
A10.1
14
5
A10.1
1
2
3
4
5
PANELTYPE
PANELLENGTH
5' - 10"
5' - 0"
3' - 10" (F.V)
6' - 2 1/2" (F.V)
5' - 10" (F.V)
DETAIL
PANEL TYPE AT (N) ADDITION
11/A10.1
11/A10.1
11/A10.1
11/A10.1
18/A10.6
1A
2A
PANELTYPE
PANELLENGTH
2' - 6" (F.V)
5' - 0" (F.V)
DETAIL
PANEL TYPE @ CORNER CONDITION
12/A10.1
12/A10.1
SS BALUSTER
PERFORATED ALUMPANEL
SS RAILING
PANEL ATTACHMENT-REF
LIGHT-WEIGHT CONC
MTL DECK
STL BEAM
COMPOSITE MTL PANEL
3 5/8" MTL STUDS @ 16"OC
COLUMN GRID
PAINTED STL BRAKE
1' - 0"
PAINTED STL ANGLE
3' -
6"
STL ANGLE
BACKER ROD &SEALANT ATJOINT
ATTACHMENT
14
A10.1
SS BALUSTER
PERFORATED AL PANEL
PANEL ATTACHMENT
ATTACHMENT BRACKETBELOW
6".
8" - 12" SEISMIC EXPANSION JOINT
CONC. FLR SLAB
.040 BENT TO 'S' SHAPE ALUMSEISMIC JOINT WITH HEM TOP& BOTTOM
CONT. STEEL ANGLE
FLOOR SEISMIC JOINT
SS TOP RAIL
.040 BENT TO S-SHAPEALUM SEISMIC JOINT WITHHEM TOP & BOT.
3 1/2" X 8" ANGLE WELDEDTO SS BALUSTER
SS BALUSTER
FINISHED FLR
SOLID AL PANEL
10
A10.1
3 7/
8" M
AX
.
3 7/8" MAX.
8" - 12"
2" X 2"x1/4" ANGLEANCHOR TO WALL
NOTES
KEYNOTES
Project Title
Agency ApprovalConsultant Seal
Drawing Title
Designed:
Drawn:
Checked:
Reviewed:
Date:
Project No.
Scale:
Drawing No.
Architect's Seal
IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT
OFFICE OF REGULATION SERVICES
APPL.
AC
DATE
FLS SS
04-112285
TELEPHONE:FAX:Architecture . Planning . Interior DesignWWW.HMCARCHITECTS.COM
ARCHITECTS3546 CONCOURS STREETONTARIO, CALIFORNIA 91764
909.483.1400909.989.9979
www.sac.edu
MDJ
JD,DR
JD
JD
HMC ARCHITECTSSM
FILE NO. 30-C2
010203040506070809
J
H
G
F
E
D
C
B
A
J
H
G
F
E
D
C
B
A
010203040506070809
KEV
INM. WILKESON
NO. C-20601
REN. 03- 31- 15ST
ATEOF CAL I FORN
IA
LIC
ENSED ARCHITECT
(714) 564-6000
1530 W 17th StreetSanta Ana, CA 92706
Rancho Santiago Community College DistrictSanta Ana College
Dunlap Hall Addition & Alterations
C:\
Revit L
ocal F
iles\5
002011000_A
14_R
estr
oom
s_kdoan.r
vt
6/6/2016 9:46:55 AM
As indicated
4TH FLOOR RESTROOM ALTERATION BID
A10.6
INTERIOR DETAILS
5002011-00
SANTA ANA COLLEGE - DUNLAP HALL
8/07/2012
1 1/2" = 1'-0"
3METAL STUD BACKING
6" = 1'-0"
4MTL STUD BACKING @ GRAB BAR/HANDRAIL
12" = 1'-0"
2ALTERNATE DIMENSIONS IN INCHES
3" = 1'-0"
7CERAMIC TILE FLOOR DETAIL
1 1/2" = 1'-0"
8FLOOR DRAIN AT TILE
6" = 1'-0"
5TOILET PARTITION TO FLOOR
6" = 1'-0"
6TOILET PARTITION WALL ANCHORAGE
1 1/2" = 1'-0"
10HI-LOW DRINKING FOUNTAIN ATTACHMENT
3/4" = 1'-0"
9HI-LOW DRINKING FOUNTAIN
1/4" = 1'-0"
PLUMBING FIXTURES AND ACCESSORIES
3/4" = 1'-0"
13GUARDRAIL SECTION @ END CONDITION
GUARDRAIL PANEL SCHEDULE 14
3/4" = 1'-0"
11GUARDRAIL @ END CONDITION (N)
3" = 1'-0"
18GUARDRAIL @ SEISMIC JOINT
3/4" = 1'-0"
16GUARDRAIL @ SEISMIC JOINT
GUARDRAIL PANEL SCHEDULE 19
2
2
No. Description Date
2 ADDENDUM #2 1/10/14
METAL STUD WALL 12
N.T.S