90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-2ELECTRONIC SIGNALS
Duotronic®
Horns and Sirens
The 5520 and 5521 Series are low current, high performance, high
decibel signals which may be coded or used as a continuous alarm.
The 5520 Series is designed to function as either a horn or siren by
setting an internal, tamper proof switch. The signal's universal
Adaptaplate® mounts directly on walls, or on any single-gang open-
ing. Adaptaplate speeds installation by allowing the installer to con-
nect all field wiring to the plate and then finishing the installation by
snapping the horn onto the plate. It also mounts to 3 1/4" (83mm), 3
1/2" (89mm), 4" (102mm) octagon, 4" (102mm) square boxes, or
equivalent fittings. The signal may be weatherproofed using the
Edwards Cat. No. 349 back box (see page 5-10).
The 5521 operates as a horn only. It is intended for weatherproof
applications and must be mounted on the supplied Edwards Cat.
No. 349 backbox (see page 5-10) using the universal Adaptaplate®
(supplied).
The 5520 and 5521 Series are used for schools, factories, lumber
yards, and other industrial and commercial installations. The horn
signal is often used for timing, paging, and alarms. The siren signal
is particularly suitable for high noise areas and often used for alert-
ing an evacuation.
5520 & 5521 SeriesFEATURES
> 114 dB audible signal
> 5520 Series is weatherproofed byadding 349 back box
> 5521 Series is weatherproof assupplied
> Horn and siren or horn models
> Easy Adaptaplate installation
AGENCY APPROVALS
> UL 464 Listed
> FM Approved Audible NotificationAppliances Standard 3151-3152
SPECIFICATIONS
> Horn frequency - 1.1KHz
> Siren frequency - rises and fallsfrom 600 to 1300 Hz every 3seconds
> Speaker swivels 180° horizontallyand 90° vertically
High dB, Electronic Sound
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-3
*Uses separately mounted 598Y Transformer.
11"(279mm)
8 3/4"Dia.(222)
14"(356mm)
7" Dia.(178mm)
5 1/2"(140mm)
13 1/2"(343mm)
11"(279mm)
90°
Speaker can bepositioned anywherewithin 90° verticallyor 180° horizontally5520 Series may be weatherproofed using Cat. No. 349 back box (purchased separately.)
5521 is supplied with Cat. No. 349 weatherproof back box
dB atCat. No. Volts Amps VA 10 ft (3.05m)
5520-AS 12V AC 60 Hz 1.3 15.612V DC .7 8.4
5520-AQ 24V AC 60 Hz .85 20.4 11424V DC .35 8.4 (Horn)
5520-N5 120V AC 60 Hz .35 42 112
5520-P1 125V DC .1 12.5 (Siren)
5520-R5* 240V AC 60 Hz .1 24.0
5521-S1 250V DC .065 16.3 114 (Horn only)
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-4ELECTRONIC SIGNALS
Low current, high performance, high decibel signaling appliance de-
signed to function as either a horn or siren by setting an internal,
tamper proof switch. The 5520D is primarily intended for use in ap-
plications requiring electrical supervision of signaling circuit field
wiring. These signals may also be used for unsupervised signaling
applications.
The signal's universal Adaptaplate® mounts directly on walls, or on
any single-gang opening. Adaptaplate speeds installation by allow-
ing the installer to connect all field wiring to the plate and then fin-
ishing the installation by snapping the horn onto the plate. It also
mounts to 3 1/4" (83mm), 3 1/2" (89mm), 4" (102mm) octagon, 4"
(102mm) square boxes, or equivalent fittings. The signal may be
weatherproofed using the Edwards Cat. No. 349 back box (see page
5-10).
Used for schools, factories, lumber yards, and commercial installa-
tions. The horn signal is often used for timing, paging, and burglar
and fire alarms. The siren signal is particularly suitable for alarm
and evacuation in high noise areas.
Duotronic®
Horn/Siren
5520D Series
Diode Polarized, High dB
FEATURES
> Diode polarized for supervisorycircuits
> Weatherproofed by adding 349back box
> Switchable horn or sirenoperation
> Easy Adaptaplate installation
AGENCY APPROVALS
> UL 464 Listed
> FM Approved Audible NotificationAppliances Standard 3151-3152
SPECIFICATIONS
> Speaker swivels 180° horizontallyand 90° vertically
> Horn frequency - 1.1KHz
> Siren frequency - rises and fallsfrom 600 to 1300 Hz every 3seconds
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-5
11"(279mm)
8 3/4"Dia.(222)
14"(356mm)
7" Dia.(178mm)
5 1/2"(140mm)
13 1/2"(343mm)
11"(279mm)
90°
Speaker can bepositioned anywherewithin 90° vertically
and 180° horizontallyMay be weatherproofed using Cat. No. 349 back box (not supplied)
dB atCat. No. Volts Amps VA 10 ft (3.05m)
5520D-N5 120V AC .35 42.0 11450/60 Hz (Horn)
5520D-AW 20-24V DC .35 8.4 112(Siren)
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-6ELECTRONIC SIGNALS
Duotronic® ElectronicHorns and Sirens
The 5522 Series Horn and 5523 Series Siren are low current, high
performance, high decibel signals for hazardous locations.
They can be mounted on any surface using three bolts. Flying leads
allow for quick installation
For use where a high decibel sound is required for alert or evacua-
tion in hazardous locations. Typical applications include signaling for
security, evacuation, power failure, and danger. Ideal for use in fac-
tories, mines, flour mills, refineries and paint shops.
5522 & 5523 SeriesFEATURES
> Corrosion resistant electrostaticheat flowed powder epoxy grayfinish
> Fitted with factory sealed 1/2"(13mm) threaded pipe nipple forquick installation
AGENCY APPROVALS
> UL Listed for Class I, Division 1and 2, Groups B, C, and Dhazardous locations
> UL 464 and 1203 Listed
SPECIFICATIONS
> Speaker swivels 180° vertically orhorizontally depending onorientation of mounting bracket
> 30" (762mm) wire leads
> Horn frequency - 982 Hz
> Siren frequency - rises and fallsfrom 600 to 1250 Hz every 8seconds
Explosionproof
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-7
11 1/4"(286mm)
11 1/4"(286mm)
18 3/8"(467mm)
Speaker pivots 180°
Signal Off Signal On dB atCat. No. Description Volts Standby Current (Amps) Operating Current (Amps) 10 ft (3.05m)
5522-AQ Horn 24V DC 0.061 0.47024V AC 50/60 Hz 0.250 1.32
5522-Y6 Horn 120V AC 50/60 Hz 0,088 0.260 109240V AC 50/60 Hz 0.091 0.190
125V DC 0.031 0.130250V DC 0.019 0.070
5523-AQ Siren 24V DC 0.061 0.47024V AC 50/60 Hz 0.250 1.32
5523-Y6 Siren 120V AC 50/60 Hz 0,088 0.260 105240V AC 50/60 Hz 0.091 0.190
125V DC 0.031 0.130250V DC 0.019 0.070
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-8ELECTRONIC SIGNALS
The 5522D Horn and 5523D Siren are low current, high perfor-
mance, high decibel signals for hazardous locations. They are pri-
marily intended for use in hazardous location applications requiring
electrical supervision of signaling circuit field wiring. These signals
may also be used for unsupervised signaling applications.
They may be mounted on any surface using three bolts.
For use where a high decibel sound is required for alert or evacua-
tion in hazardous locations. Typical applications include signaling for
security, fire, power failure, and danger. Ideal for use in factories,
flour mills, refineries and paint shops.
Duotronic® ElectronicHorns and Sirens
5522D & 5523D
Explosionproof, DiodePolarized
FEATURES
> Diode polarized for supervisorycircuits
> Corrosion resistant electrostaticheat flowed powder epoxy grayfinish
> Fitted with factory sealed 1/2"(13mm) threaded pipe nipple forquick installation
AGENCY APPROVALS
> UL Listed for Class I, Division 1and 2, Groups B, C, and Dhazardous locations
> UL 464 and 1604 Listed
SPECIFICATIONS
> Speaker swivels 180° vertically orhorizontally depending onorientation of mounting bracket
> 30" (762mm) wire leads
> Horn frequency - 9.82 Hz
> Siren frequency - rises and fallsfrom 600 to 1250 Hz every 8seconds
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-9
11 1/4"(286mm)
11 1/4"(286mm)
18 3/8"(467mm)
Speaker pivots 180°
Signal Off Signal On dB atCat. No. Description Volts Standby Current (Amps) Operating Current (Amps) 10 ft (3.05m)
5522D-AW Horn 20-31V DC 0.061 0.400 109
5523D-AW Siren 20-31V DC 0.061 0.400 105
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-12ELECTRONIC SIGNALS
Adaptatone® MillenniumMultiple Tone Signal
The Edwards 5530M Adaptatone Millennium is a heavy-duty indus-
trial, tone-selectable, signaling device capable of producing volume-
controlled, high-decibel tones. It uses a microprocessor circuit to
create 27 distinctive tones, selected by setting a dip switch within
the unit. For a complete listing of all 27 tones, see page 4-55. The
Adaptatone Millennium can be activated from field-wired, normally
open contacts, or from a 24VDC or 120VAC external voltage source
such as an output of a PLC. PLC compatibility assures no addi-
tional loading resistors or relays are required to set up your
Adaptatone.
Selected models are designed to serially connect to RS485 net-
works. The 5530MV-485Y6 additionally has a field recordable voice
feature that allows activation of voice messages over the RS485
network. See connectivity and Activation section for more detail.
Normally open contacts can be obtained from the Cat. No. 5538-4
and/or Cat. No. 5538-4R Adaptatone Signal Actuators. See pg. 4-49.
Designed for industrial applications requiring high decibel output and
microprocessor reliability. Typical applications include emergency
warning systems, plant evacuation and security intrusion alarms,
process monitoring, shift start-and-dismissal horns, and paging sig-
nals.
½" (13mm) conduit or surface mounting. See Adaptatone Signaling
Installation, page 4-56.
Single OutputRS485 Activation5530M & 5530MV Series
FEATURES
> 27 tone capability - No additionaltone modules needed
> PLC compatible
> Output up to 110 dB
> Suitable for Division 2 Locations
> Captive components
> RS485 models
AGENCY APPROVALS
> NEMA Type 3R
> UL 464 and 1604 Listed
> UL Listed for indoor and outdoorapplications in Class I, Division2, Groups A, B, C & D; Class II,Division 2, Groups F & G; andClass III Hazardous Locations
> cUL C22.2 No. 205 (24AQ, 24N5& 24Y6 models)
> CE Marked, LV & EMC Directives,(24Y6 AC & 24AQ models)
SPECIFICATIONS
> Speaker can be rotated andlocked in any horizontal direction
> 24V DC battery backup terminalsprovided
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-13
Operating Input Card Signal Off Signal OnCat. No. Voltage Activation Voltage Standby Current (Amps) Operating Current (Amps)
5530M-24AQ 24V DC 24VDC 0.10 0.6424V AC 50/60 Hz 0.10 1.22
5530M-24N5 120V AC 50/60 Hz 24VDC 0.10 0.285530M-120N5 120VAC 0.10 0.28
5530M-24Y6 120V AC 50/60 Hz 24VDC 0.10 0.245530M-120Y6 240V AC 50/60 Hz 120VAC 0.10 0.15
125V DC 0.04 0.16250V DC 0.02 0.08
5530M-485Y6 120V AC 50/60 Hz RS485 0.10 0.245530MV-485Y6 240V AC 50/60 Hz 0.10 0.15(voice model) 125V DC 0.04 0.16
250V DC 0.02 0.08
*This device is PLC compatible and may be operated by PLCs with output characteristics that match the input load requirements of this signal.
SIGNAL INPUT LOAD CHARACTERISTICS* (PLC output to meet following product input parameters)
Operating Max. off state Continuous on Surge (inrush/duration)Cat. No. voltage leakage current (mA) current (mA) Amps/milliseconds
5530M-24AQ 24V DC only 2 740 8/4
5530M-24N5 120V 50/60 Hz 2 360 2.82/4
5530M-120N5 120V 50/60 Hz 5 380 2.82/4
24VDC Input Board 5V DC to 24V DC 2 6 —
120VAC Input Board 120VAC 50/60 Hz 5 13 —
Nut to adjustspeakerdirection
Mountingflange4 holes(2 each side)
3 1/2"(89mm)
6"(152mm)
8 47/64"(222mm)
8"(203mm)
13 3/4"(349mm)
1/2" (13mm)conduit mounting
6"(152mm)
8"(203mm)
4"(102mm)
8"(203mm)
2 1/2"(64mm)
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-14ELECTRONIC SIGNALS
Adaptatone® MillenniumMultiple Tone Signal
The Edwards 5530MD-24AW Adaptatone Millennium is a heavy-
duty industrial, tone-selectable, signaling device intended primarily
for use in fire alarm systems and other applications requiring electri-
cal supervision of signaling circuit field wiring. It uses a micropro-
cessor circuit to create 27 distinctive tones A single tone may be
selected by setting a miniature dip switch within the unit. For a
complete listing of all 27 tones, see page 4-55. The Adaptatone Mil-
lennium can be activated from field-wired, normally open contacts,
or a 24VDC external voltage source such as an output of a PLC or
Fire/Security panel. Normally open contacts can be obtained from
the Cat. No. 5538-4 and/or Cat. No. 5538-4R Adaptatone Signal Ac-
tuators. See page 4-49.
1/2" (13mm) conduit or surface mounting. See Adaptatone Signal-
ing Installation, pages 4-56.
The signal may also be used for unsupervised signaling applica-
tions. Typical applications include fire alarm emergency warning
systems, plant evacuation and security intrusion alarms, process
monitoring, shift start-and-dismissal horns, and paging signals.
FEATURES
> 27 tone capability - No additionaltone modules needed
> Output up to 110 dB
> Suitable for Division 2 Locations
> Diode polarized for supervisorycircuits
> Captive Components
AGENCY APPROVALS
> NEMA Type 3R
> IP 44
> UL 464 and UL 1604 Listed forindoor and outdoor applications
> CSFM
> CE Marked
> ULC S525
> UL Listed for use in Class I,Division 2, Groups A, B, C & D;Class II, Division 2, Groups F &G; and Class III HazardousLocation applications
> TUV Rheinland Certified
SPECIFICATIONS
> Speaker can be rotated andlocked in any horizontal direction
5530MD-24AW
Diode Polarized for Fire AlarmCommunication, Single Output
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-15
Operating Signal Off Signal OnCat. No. Voltage Standby Current (Amps) Operating Current (Amps)
5530MD-24AW 20-31V DC 0.10 0.80
Nut to adjustspeakerdirection
Mountingflange4 holes(2 each side)
3 1/2"(89mm)
6"(152mm)
8 47/64"(222mm)
8"(203mm)
13 3/4"(349mm)
1/2" (13mm)conduit mounting
6"(152mm)
8"(203mm)
4"(102mm)
8"(203mm)
2 1/2"(64mm)
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-16ELECTRONIC SIGNALS
Adaptatone® MillenniumMultiple Tone Signal
The Edwards 5530MHV Adaptatone Millennium is a heavy-duty,
high volume, 30 watt, industrial signaling device capable of produc-
ing volume-controlled, high-decibel tones. It uses a microprocessor
circuit to create 27 distinctive tones. A single tone may be selected
by setting a miniature switch within the unit. For a complete listing
of all 27 tones, see page 4-55.
The Adaptatone Millenium can be activated from field-wired, nor-
mally open contacts, or a 24VDC or 120VAC external voltage
source such as an output of a PLC. Normally open contacts can be
obtained from the 5538-4 and/or 5538-4R Adaptatone Signal Actua-
tors. See page 4-49.
The 5530MHV-485Y6 is designed to be connected to RS485 net-
works, allowing full serial signaling communication control.
Designed for industrial applications. Typical applications include
emergency warning systems, plant evacuation and security intru-
sion alarms, process monitoring, shift start-and-dismissal horns,
and paging signals.
The 5530MHV is designed for either 1/2" (13mm) conduit or surface
mounting. See Adaptatone Signaling Installation, pages 4-56.
30 Watt High Volume, SingleOutput, RS485 Activation5530MHV Series
FEATURES
> 27 tone capability - No additionaltone modules needed
> Output up to 113 dB @ 10 ft
> PLC compatible
> Suitable for Division 2 Locations
> Captive Components
> RS485 model available
AGENCY APPROVALS
> NEMA Type 3R
> IP 44
> UL 464 and 1604 Listed
> UL Listed for indoor and outdoorapplications in Class I, Division2, Groups A, B, C & D; Class II,Division 2, Groups F & G; andClass III Hazardous Locations
> cUL C22.2 No. 205 (24AQ, 24N5& 24Y6 models)
> TUV Rheinland Certified
> CE Marked, LV & EMC Directives,(24Y6 AC only & 24AQ models)
SPECIFICATIONS
> Speaker can be rotated andlocked in any horizontal direction
> 24V DC battery backup terminalsprovided
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-17
Operating Input Card Signal Off Signal OnCat. No. Voltage Activation Voltage Standby Current (Amps) Operating Current (Amps)
5530MHV-24AQ 24V DC 24VDC 0.10 1.2224V AC 50/60 Hz 0.10 2.21
5530MHV-24Y6 120V AC 50/60 Hz 24VDC 0.10 0.635530MHV-120Y6 240V AC 50/60 Hz 120VAC 0.07 0.30
125V DC 0.04 0.37250V DC 0.02 0.17
5530MHV-485Y6 120V AC 50/60 Hz RS485 0.10 0.63240V AC 50/60 Hz 0.07 0.30
125V DC 0.04 0.37250V DC 0.02 0.17
*This device is PLC compatible and may be operated by PLCs with output characteristics that match the input load requirements of this signal.
SIGNAL INPUT LOAD CHARACTERISTICS* (PLC output to meet following product input parameters)
Operating Max. off state Continuous on Surge (inrush/duration)Cat. No. voltage leakage current (mA) current (mA) Amps/milliseconds
5530MHV-24AQ 24V DC only 2 740 8/4
24VDC Input Board 5V DC to 24V DC 2 6 —
120VAC Input Board 120VAC 50/60 Hz 5 13 —
Nut to adjustspeakerdirection
Mountingflange4 holes(2 each side)
3 1/2"(89mm)
6"(152mm)
11 1/2"(292mm)
9 3/4"(248mm)
15"(381mm)
1/2" (13mm)conduit mounting
6"(152mm)
8"(203mm)
4"(102mm)
9 3/4"(248mm)
2 1/2"(64mm)
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-18ELECTRONIC SIGNALS
Adaptatone® MillenniumMultiple Tone Signal
The Edwards 5531M Series Adaptatone Millennium is a heavy-duty
industrial, tone-selectable, signaling device capable of producing
volume-controlled, high-decibel tones. four tones can be activated
from field-wired, normally open contacts, or a 24VDC or 120VAC
external voltage source such as the output of a PLC. Normally open
contacts can be obtained from the Cat. No. 5538-4 and/or Cat. No.
5538-4R Adaptatone Signal Actuators. See page 4-49.
The unit uses a microprocessor circuit to create 27 distinctive
tones, by setting miniature dip switches within the unit. The pro-
grammed tones operate on a pyramid-type priority system. For
more information on priority tone operation and a complete listing of
all 27 tones, see page 4-55.
Designed for industrial applications. Typical applications include
emergency warning systems, plant evacuation and security alarms,
process monitoring, shift notification horns, and paging signals.
The 5531M is designed for either 1/2" (13mm) conduit or surface
mounting. See Adaptatone Signaling Installation, pages 4-56.
Four Outputs
5531M SeriesFEATURES
> 27 tone capability - No additionaltone modules needed
> Output up to 110 dB @ 10 ft
> PLC compatible
> Suitable for Division 2 Locations
> Captive Components
AGENCY APPROVALS
> NEMA Type 3R
> IP 44
> UL 464 and 1604
> UL Listed for indoor and outdoorapplications in Class I, Division2, Groups A, B, C & D; Class II,Division 2, Groups F & G; andClass III Hazardous Locations
> cUL C22.2 No. 205 (24AQ, 24N5& 24Y6 models)
> CE Marked, LV & EMC Directives,(24Y6 AC only & 24AQ models)
> TUV Rheinland Certified
SPECIFICATIONS
> Built-in cascading priority system
> Speaker can be rotated andlocked in any horizontal direction
> 24V DC battery backup terminals
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-19
Operating Input Card Signal Off Signal OnCat. No. Voltage Activation Voltage Standby Current (Amps) Operating Current (Amps)
5531M-24AQ 24V DC 24VDC 0.10 0.5724V AC 50/60 Hz 0.10 0.98
5531M-24N5 120V AC 50/60 Hz 24VDC 0.10 0.235531M-120N5 120VAC 0.10 0.23
5531M-24Y6 120V AC 50/60 Hz 24VDC 0.10 0.285531M-120Y6 240V AC 50/60 Hz 120VAC 0.08 0.15
125V DC 0.10 0.15250V DC 0.02 0.08
*This device is PLC compatible and may be operated by PLCs with output characteristics that match the input load requirements of this signal.
SIGNAL INPUT LOAD CHARACTERISTICS* (PLC output to meet following product input parameters)
Operating Max. off state Continuous on Surge (inrush/duration)Cat. No. voltage leakage current (mA) current (mA) Amps/milliseconds
5531M-24AQ 24V DC only 2 740 8/4
5531M-24N5 120V 50/60 hz 2 360 2.82/4
5531M-120N5 120V 50/60 hz 5 380 2.82/4
24VDC 5V DC to 24V DC 2 6 —Input Board (each input)
120VAC 120VAC 50/60 Hz 5 13 —Input Board (each input)
Nut to adjustspeakerdirection
Mountingflange4 holes(2 each side)
3 1/2"(89mm)
6"(152mm)
8 47/64"(222mm)
8"(203mm)
13 3/4"(349mm)
1/2" (13mm)conduit mounting
6"(152mm)
8"(203mm)
4"(102mm)
8"(203mm)
2 1/2"(64mm)
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-20ELECTRONIC SIGNALS
Adaptatone® MillenniumMultiple Tone Signal
The Edwards 5531MHV Series Adaptatone Millennium is a high vol-
ume, 30 watt heavy-duty industrial signaling device capable of pro-
ducing volume-controlled, high-decibel tones. Four tones can be ac-
tivated from field-wired, normally open contacts, or a 24VDC or
120VAC external voltage source such as the output of a PLC. Nor-
mally open contacts can be obtained from the Cat. No. 5538-4 and/
or Cat. No. 5538-4R Adaptatone Signal Actuators. See page 4-49.
The unit uses a microprocessor circuit to create 27 distinctive
tones, selected by setting miniature dip switches within the unit.
The tones programmed operate on a pyramid-type priority system in
which a switch with a programmed tone takes priority over all
switches that follow it. For more information on priority tone opera-
tion and a complete listing of all 27 tones, see page 4-55.
Designed for industrial applications including emergency warning
systems, plant evacuation and security intrusion alarms, process
monitoring, shift start-and-dismissal horns, and paging signals.
The 5531M is designed for either 1/2" (13mm) conduit or surface
mounting. See Adaptatone Signaling Installation, pages 4-56.
Four Outputs
5531MHV SeriesFEATURES
> 27 tone capability - No additionaltone modules needed
> PLC compatible
> Output up to 113 dB
> Suitable for Division 2 Locations
> Captive Components
AGENCY APPROVALS
> NEMA Type 3R
> IP 44
> UL 464 and 1604 Listed
> UL Listed for indoor and outdoorapplications in Class I, Division2, Groups A, B, C & D; Class II,Division 2, Groups F & G; andClass III Hazardous Locations
> cUL C22.2 No. 205 (24AQ, 24N5& 24Y6 models)
> CE Marked, LV & EMC Directives,(24Y6 AC only & 24AQ models)
> TUV Rheinland Certified
SPECIFICATIONS
> Built-in cascading priority system
> Speaker can be rotated andlocked in any horizontal direction
> 24V DC battery backup terminals
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-21
Operating Input Card Signal Off Signal OnCat. No. Voltage Activation Voltage Standby Current (Amps) Operating Current (Amps)
5531MHV-24AQ 24V DC 24VDC 0.10 1.1424V AC 50/60 Hz 0.10 1.73
5531MHV-24Y6 120V AC 50/60 HZ 24VDC 0.10 0.475531MHV-120Y6 240V AC 50/60 Hz 120VAC 0.10 0.28
125V DC 0.10 0.31
*This device is PLC compatible and may be operated by PLCs with output characteristics that match the input load requirements of this signal.
SIGNAL INPUT LOAD CHARACTERISTICS* (PLC output to meet following product input parameters)
Operating Max. off state Continuous on Surge (inrush/duration)Cat. No. voltage leakage current (mA) current (mA) Amps/milliseconds
5531MHV-24AQ 24V DC only 2 1500 8/4
24VDC 5V DC to 24V DC 2 6 —Input Board (each input)
Nut to adjustspeakerdirection
Mountingflange4 holes(2 each side)
3 1/2"(89mm)
6"(152mm)
11 1/2"(292mm)
9 3/4"(248mm)
15"(381mm)
1/2" (13mm)conduit mounting
6"(152mm)
8"(203mm)
4"(102mm)
9 3/4"(248mm)
2 1/2"(64mm)
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-22ELECTRONIC SIGNALS
Adaptatone® MillenniumMultiple Tone Signal
The Edwards 5531MV Adaptatone Millennium Voice unit is a heavy-
duty industrial, tone-selectable, signaling device capable of produc-
ing volume-controlled, high-decibel tones and up to 20 seconds of
field recorded voice messages. The Adaptatone Millennium Voice
unit can be activated from field-wired, normally open contacts, or a
24VDC or 120VAC external voltage source such as an output of a
PLC. Normally open contacts can be obtained from the Cat. No.
5538-4 and/or Cat. No. 5538-4R Adaptatone Signal Actuators. See
page 4-49.
The unit uses a microprocessor circuit to create 27 distinctive
tones and store 20 seconds of field recorded voice messages. Mes-
sages and tones may be selected by setting miniature dip switches
within the unit. A total of four messages and tones programmed op-
erate on a pyramid-type priority system. For more information on
priority tone operation and a complete listing of all 27 tones, see
page 4-55.
The 5531MV is designed for either 1/2" (13mm) conduit or surface
mounting. See Adaptatone Signaling Installation, pages 4-56.
Designed for industrial applications including emergency warning,
plant evacuation and security alarms, process monitoring, shift noti-
fication horns, paging and process control.
PLC CompatibleVoice Capability5531MV Series
FEATURES
> Stand-alone, 27 tone capability -No additional tone modulesneeded
> Output up to 110 dB @ 10 ft
> PLC compatible
> 20 sec. of field recorded VoiceMessages
> Suitable for Division 2 Locations
> Captive Components
AGENCY APPROVALS
> NEMA Type 3R
> IP 44
> UL 464 and 1604 Listed
> UL Listed for indoor and outdoorapplications in Class I, Division2, Groups A, B, C & D; Class II,Division 2, Groups F & G; andClass III Hazardous Locations
> cUL C22.2 No. 205 (24N5 model)
SPECIFICATIONS
> Built-in cascading priority system
> Speaker can be rotated andlocked in any horizontal direction
> 24V DC battery backup terminals
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-23
Operating Input Card Signal Off Signal OnCat. No. Voltage Activation Voltage Standby Current (Amps) Operating Current (Amps)
5531MV-24N5 120V AC 50/60 Hz 24VDC 0.10 0.23
5531MV-120N5 120V AC 50/60 Hz 120VAC 0.10 0.23
*This device is PLC compatible and may be operated by PLCs with output characteristics that match the input load requirements of this signal.
SIGNAL INPUT LOAD CHARACTERISTICS* (PLC output to meet following product input parameters)
Operating Max. off state Continuous on Surge (inrush/duration)Cat. No. voltage leakage current (mA) current (mA) Amps/milliseconds
5531MV-24N5 120V 50/60 hz 2 360 2.82/4
5531MV-120N5 120V 50/60 hz 5 380 2.82/4
24VDC 5V DC to 24V DC 2 6 —Input Board (each input)
120VAC 120VAC 50/60 Hz 5 13 —Input Board (each input)
Nut to adjustspeakerdirection
Mountingflange4 holes(2 each side)
3 1/2"(89mm)
6"(152mm)
8 47/64"(222mm)
8"(203mm)
13 3/4"(349mm)
1/2" (13mm)conduit mounting
6"(152mm)
8"(203mm)
4"(102mm)
8"(203mm)
2 1/2"(64mm)
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-38ELECTRONIC SIGNALS
Adaptatone® MillenniumRemote Speaker/Amp
The Edwards 5532M Adaptatone Millennium Remote Speaker/
Amplifier has been designed for high decibel system operation
when connected to the 5540M Central Tone Generator or 5541M
System Master Panel. See Adaptatone Millennium Tone Generator,
page 4-28.
Each Speaker/Amplifier operates directly from local power sources,
making it possible in a single system to connect the remote
Speaker/Amplifiers to local power sources of different voltages. De-
signed for either 1/2" (13mm) conduit or surface mounting.
The 5532M-485Y6 is designed to be connected to RS485 networks,
allowing full signaling communication control.
The 5532MD-25AW and 5532MD-70AW are diode polarized units
designed for use in applications requiring electrical supervision of
signaling circuit field wiring. The 25AW utilizes a 25 VRMS coupler
board; the 70AW utilizes a 70 VRMS coupler board.
Adaptatone Signaling Systems are designed for industrial applica-
tions calling for high decibel output and microprocessor reliability
combined with simultaneous signal delivery over all speakers in-
cluded in the system. Typical applications include: emergency warn-
ing systems, plant evacuation alarms, security intrusion sirens, pro-
cess monitoring, shift start-and-dismissal horns, and paging sig-
nals.
RS485 units are MEDI compatible. See page 4-10.
5532M & 5532MD SeriesFEATURES
> Output up to 110 dB at 10 ft
> Corrosion resistant electrostaticheat flowed epoxy finish
> Individual volume control
> Suitable for Division 2 Locations
> Captive Components
> RS485 model available
> Diode Polarized models
AGENCY APPROVALS
> NEMA Type 3R
> IP 44
> UL 464 and 1604 Listed
> UL & cUL Listed for indoor andoutdoor application in Class I,Division 2, Groups A, B, C & D;Class II, Division 2, Groups F &G; and Class III HazardousLocations
> cUL C22.2 No. 205
> TUV Rheinland Certified
> CE Marked, LV & EMC Directives(Y6 AC only and AQ models)
SPECIFICATIONS
> 24V DC battery backup terminals
> Speaker can be rotated andlocked in any horizontal direction
System Speaker OperationRS485 Activation
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-39
Operating Signal Off Signal OnCat. No. Voltage Standby Current (Amps) Operating Current (Amps)
5532M-AQ 24V DC 0.10 0.6424V AC 50/60 Hz 0.10 1.22
5532M-N5 120V AC 50/60 Hz 0.10 0.23
5532M-Y6 120V AC 50/60 Hz 0.10 0.28240V AC 50/60 Hz 0.10 0.15
125V DC 0.10 0.15250V DC 0.02 0.08
5532M-485Y6 120V AC 50/60 Hz 0.10 0.28240V AC 50/60 Hz 0.10 0.15
125V DC 0.10 0.15250V DC 0.02 0.08
5532MD-25AW 20 - 24V DC 0.10 0.64
5532MD-70AW 20 - 24V DC 0.10 0.64
Nut to adjustspeakerdirection
Mountingflange4 holes(2 each side)
3 1/2"(89mm)
6"(152mm)
8 47/64"(222mm)
8"(203mm)
13 3/4"(349mm)
1/2" (13mm)conduit mounting
6"(152mm)
8"(203mm)
4"(102mm)
8"(203mm)
2 1/2"(64mm)
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-40ELECTRONIC SIGNALS
Adaptatone® MillenniumRemote Speaker/Amp
The Edwards 5532MHV Adaptatone Millennium Remote Speaker/
Amplifier has been designed for high decibel system operation
when connected to the 5540M Central Tone Generator or 5541M
System Master Panel. See Adaptatone Tone Generator, page 4-28.
Each Speaker/Amplifier operates directly from local power sources,
making it possible in a single system to connect the remote
Speaker/Amplifiers to local power sources of different voltages. De-
signed for either 1/2" (13mm) conduit or surface mounting.
The 5532MHV-485Y6 is designed to be connected to RS485 net-
works, allowing full signaling communication control.
Adaptatone Signaling Systems are designed for industrial applica-
tions calling for high decibel output and microprocessor reliability
combined with simultaneous signal delivery over all speakers in-
cluded in the system. Typical applications include: emergency
warning systems, plant evacuation alarms, security intrusion si-
rens, process monitoring, shift start-and-dismissal horns, and pag-
ing signals.
RS485 units are MEDI compatible. See page 4-10.
5532MHV Series
30 Watt, High Volume SystemSpeaker, RS485 Activation
FEATURES
> Output up to 113 dB at 10 ft
> Corrosion resistant electrostaticheat flowed epoxy finish
> Individual volume control
> Suitable for Division 2 Locations
> Captive Components
> RS485 models available
AGENCY APPROVALS
> NEMA Type 3R
> IP 44
> UL 464 and 1604 Listed
> cUL 22.2 No. 205
> UL & cUL Listed for indoor andoutdoor applications for use inClass I, Division 2, Groups A, B,C & D; Class II, Division 2,Groups F & G; and Class IIIHazardous Locations
> TUV Rheinland Certified
> CE Marked, LV & EMC Directives(Y6 AC only and AQ models)
SPECIFICATIONS
> 24V DC battery backup terminalsprovided
> Speaker can be rotated andlocked in any horizontal direction
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-41
Operating Signal Off Signal OnCat. No. Voltage Standby Current (Amps) Operating Current (Amps)
5532MHV-AQ 24V DC 0.10 1.2224V AC 50/60 Hz 0.10 2.21
5532MHV-Y6 120V AC 50/60 Hz 0.10 0.48240V AC 50/60 Hz 0.10 0.28
125V DC 0.10 0.32250V DC 0.10 0.15
5532MHV-485Y6 120V AC 50/60 Hz 0.10 0.48240V AC 50/60 Hz 0.10 0.28
125V DC 0.10 0.32250V DC 0.10 0.15
Nut to adjustspeakerdirection
Mountingflange4 holes(2 each side)
3 1/2"(89mm)
6"(152mm)
11 1/2"(292mm)
9 3/4"(248mm)
15"(381mm)
1/2" (13mm)conduit mounting
6"(152mm)
8"(203mm)
4"(102mm)
9 3/4"(248mm)
2 1/2"(64mm)
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-24ELECTRONIC SIGNALS
Adaptatone®
Electronic Signal
The Edwards 5533M Adaptatone Signal is an explosionproof,
heavy-duty industrial, tone-selectable, signaling device capable of
producing volume-controlled, high-decibel tones. The signal ac-
cepts up to two contact closures and delivers two audible output
signals selected from the 55 tones available. The two tones may
be selected by setting miniature switches within the unit. One of
the tones can be assigned a priority status to override the other
tone. For more information on priority tone operation and a complete
listing of all 55 tones, see page 4-55.
The electrical inputs activating the Adaptatone Signal are received
from field-wired, normally open contacts or from the Cat. No. 5538-4
Adaptatone Signal Actuator. (Not suitable for hazardous locations.)
See page 4-49.
The 5533M Adaptatone mounts on any surface using three bolts.
See Adaptatone Signaling Installation, pages 4-56.
For use where a high decibel sound is required for alert or evacua-
tion in hazardous locations. Typical applications include signaling
use in mining, granaries, flour mills, tankers, refineries, laboratories,
spray booths, and other hazardous locations.
5533M SeriesFEATURES
> 55 tone capability - No additionaltone modules needed
> Internal volume control
> Corrosion resistant heat flowedepoxy finish
> Supplied with factory sealed 1/2"(13mm) threaded fitting for quickinstallation
AGENCY APPROVALS
> UL 464 and 1203 Listed
> UL Listed for Class I, Division 1and 2, Groups B, C, and Dhazardous locations
SPECIFICATIONS
> Speaker swivels 180° vertically orhorizontally depending onorientation of mounting bracket
> 30" (762mm) numbered wireleads
> Heavy duty zinc cast construction
Explosionproof, Two Outputs
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-25
Horn pivots one way 180°
11 1/4"(286mm)
11 1/4"(286mm)
18 3/8"(467mm)
Operating Signal Off Signal OnCat. No. Voltage Standby Current (Amps) Operating Current (Amps)
5533M-AQ 24V DC 0.061 0.47036V DC 0.077 0.600
24V AC 50/60 Hz 0.250 1.320
5533M-Y6 120V AC 50/60 Hz 0.088 0.260240V AC 50/60 Hz 0.091 0.190
125V DC 0.031 0.130250V DC 0.019 0.070
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-26ELECTRONIC SIGNALS
Adaptatone®
Electronic Signal
The Edwards 5533MD Adaptatone Signal is an explosionproof,
heavy-duty industrial, tone-selectable, signaling device capable of
producing volume-controlled, high-decibel tones. The signal deliv-
ers one audible output signal selected from the 55 tones available.
The tone may be selected by setting a miniature switch within the
unit. For more information on priority tone operation and a complete
listing of all 55 tones, see page 4-55.
The 5533MD Adaptatone mounts on any surface using three bolts.
See Adaptatone Signaling Installation, pages 4-56.
The 5533MD Adaptatone is designed hazardous location applica-
tions requiring electrical supervision of signaling circuit field wiring.
The signal may also be used for unsupervised signaling applica-
tions. Typical applications include signaling use in mining, grana-
ries, flour mills, tankers, refineries, laboratories, spray booths, and
other hazardous locations.
5533MD
Explosionproof, DiodePolarized, Single Output
FEATURES
> Stand-alone. 55 tone capability -No additional tone modulesneeded
> Diode polarized for supervisedsignaling circuits
> Internal volume control
> Corrosion resistant heat flowedepoxy finish
AGENCY APPROVALS
> UL 464 and UL1203
> UL Listed for Class I, Division 1and 2, Groups B, C, and Dhazardous locations
SPECIFICATIONS
> Speaker swivels 180° vertically orhorizontally depending onorientation of mounting bracket
> 30" (762mm) numbered wireleads
> Supplied with factory sealed 1/2"(13mm) threaded fitting for quickinstallation
> Heavy duty zinc cast construction
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-27
Operating Signal Off Signal OnCat. No. Voltage Standby Current (Amps) Operating Current (Amps)
5533MD-AW 20-31 VDC 0.061 0.400
Horn pivots one way 180°
11 1/4"(286mm)
11 1/4"(286mm)
18 3/8"(467mm)
D-04
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-48
Adaptatone® RemoteAmplifier and AudioSignal Converter
The Edwards 5535 Remote Amplifier has been designed to power
remote speakers in Adaptatone system operation. The amplifier
output is 70V line with a maximum of 15 watts.
The 5510M Audio Signal Converter allows signaling flexibility
through the integration of Adaptatone signals into installed paging
systems. The 5510M-25Y6 converts a 25V RMS input into a 10
VRMS output. The 5510M-70Y6 converts a 70V RMS input into a
10V RMS output.
All units are designed for either 1/2" (13mm) conduit or surface
mounting in industrial applications calling for high decibel output
and microprocessor reliability combined with simultaneous signal
delivery over all speakers included in the system. Typical applica-
tions include: emergency warning systems, plant evacuation
alarms, security intrusion sirens, process monitoring, shift start-
and-dismissal horns, and paging signals.
5535 & 5510M SeriesFEATURES
> 15 Watts
> Weatherproof
> Corrosion resistant electrostaticheat flowed epoxy finish
AGENCY APPROVALS
> UL 464 Listed
> NEMA Type 3R
> IP 44
SPECIFICATIONS
> Heavy duty zinc cast construction
> 24V DC battery backup terminalsprovided
Cat.No.5535
Cat.No.5510
Signal Off Signal OnCat. No. Volts Standby Current (Amps) Operating Current (Amps)5535-N5 120V AC 50/60 Hz 0.110 0.3105510M-25Y6 125V DC 0.10 0.155510M-70Y6 250V DC 0.10 0.77
120V AC 50/60 Hz 0.10 0.24240V AC 50/60 Hz 0.10 0.15
3 1/2"(89mm)
6 3/8"(162mm)
(2) Mounting holesfor wall mounting
1/2" (13mm)conduitmounting
6 3/8"(162mm) 3 1/2"
(89mm)
Mounting flange4 holes (2 each side)
1/2" (13mm)conduit mounting
6"(152mm)
2 1/2"(64mm)
6"(152)
2"(51mm)
8"(203mm)
Cat. No. 5535 Remote Amplifier Cat. No. 5510 Audio Signal Converter
D-0
4
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-44ELECTRONIC SIGNALS
Adaptatone® MillenniumLocal/System Signal
The Edwards 5536M Adaptatone Millennium accepts three electri-
cal inputs from the closing of three normally open contacts, or a
24VDC external voltage source such as an output of a PLC, and
delivers three tones from the 27 tones available. One of these in-
puts is a priority signal. The 5536M can also work within an
Adaptatone System, sounding the central tone or voice signal or its
own tone signals. The Adaptatone Millennium System has priority
over the locally initiated contacts. See Adaptatone Signaling Sys-
tem Installation, page 4-56.
Programming the signal for the tones selected is accomplished
through setting internal dipswitches. On-site volume control is also
available by adjusting the internal volume control.
The programmed tones on the 5536M operate on a pyramid-type
priority system in which a switch with a programmed tone takes pri-
ority over all switches that follow it. For more information on priority
tone operation and a complete listing of all 27 tones, see page 4-55.
Designed for either 1/2" (13mm) conduit or surface mounting. See
Adaptatone Signaling System Installation, pages 4-56.
The 5536M Adaptatone is designed for industrial applications call-
ing for high decibel output and microprocessor reliability combined
with simultaneous signal delivery over all speakers included in the
system. Typical applications include: emergency warning systems,
plant evacuation alarms, security intrusion sirens, process monitor-
ing, shift start-and-dismissal horns, and paging signals.
5536M Series
Three Outputs & Priority
FEATURES
> Output up to 110 dB at 10 ft
> 27 tone capability - No additionaltone modules needed
> PLC Compatible
> Suitable for Division 2 locations
> Corrosion resistant electrostaticheat flowed epoxy finish
> Individual volume control
AGENCY APPROVALS
> NEMA Type 3R
> IP 44
> UL 464 and 1604 Listed
> UL & cUL Listed for indoor andoutdoor applications in Class I,Division 2, Groups A, B, C & D;Class II, Division 2, Groups F &G; and Class III HazardousLocation applications
> TUV Rheinland Certified
> CE Marked, LV & EMC Directives(24Y6 AC only & 24AQ models)
SPECIFICATIONS
> 24V DC battery backup terminals
> Speaker can be rotated andlocked in any horizontal direction
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-45
Operating Input Card Signal Off Signal OnCat. No. Voltage Activation Voltage Standby Current (Amps) Operating Current (Amps)
5536M-24AQ 24V DC 24VDC 0.10 0.6424V AC 50/60 Hz 0.10 1.22
5536M-24N5 120V AC 50/60 Hz 24VDC 0.10 0.28
5536M-24Y6 125V DC 24VDC 0.10 0.15250V DC 0.10 0.77
120V AC 50/60 Hz 0.10 0.24240V AC 50/60 Hz 0.10 0.15
*This device is PLC compatible and may be operated by PLCs with output characteristics that match the input load requirements of this signal.
SIGNAL INPUT LOAD CHARACTERISTICS* (PLC output to meet following product input parameters)Operating Max. off state Continuous on Surge (inrush/duration)
Cat. No. voltage leakage current (mA) current (mA) Amps/milliseconds
5536M-24AQ 24V DC only 2 740 8/4
5536M-24N5 120V 50/60 hz 2 360 2.82/4
24VDC 5V DC to 24V DC 2 6 —Input Board (each input)
Nut to adjustspeakerdirection
Mountingflange4 holes(2 each side)
3 1/2"(89mm)
6"(152mm)
8 47/64"(222mm)
8"(203mm)
13 3/4"(349mm)
1/2" (13mm)conduit mounting
6"(152mm)
8"(203mm)
4"(102mm)
8"(203mm)
2 1/2"(64mm)
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-46ELECTRONIC SIGNALS
Adaptatone® MillenniumLocal/System Signal
The Edwards 5536MHV high output Adaptatone Millenium accepts
three electrical inputs from the closing of three normally open con-
tacts, or a 24VDC or 120VAC external voltage source such as an
output of a PLC, and delivers three tones from the 27 tones avail-
able. One of these tones is a priority signal. The 5536MHV can also
work within an Adaptatone System, sounding the central tone or
voice signal or its own tone signals. The Adaptatone System has
priority over the locally initiated contacts. See Adaptatone Signaling
System Installation, page 4-56.
Programming the signal for the tone or tones selected is accom-
plished through setting internal dipswitches. On-site volume control
is also available by adjusting the internal volume control.
The programmed tones on the 5536MHV operate on a pyramid-type
priority system in which a switch with a programmed tone takes pri-
ority over all switches that follow it. For more information on priority
tone operation and a complete listing of all 27 tones, see page 4-55.
Designed for either 1/2" (13mm) conduit or surface mounting.
The 5536MHV Adaptatone is designed for industrial applications
calling for high decibel output and microprocessor reliability com-
bined with simultaneous signal delivery over all speakers included
in the system. Typical applications include: emergency warning
systems, plant evacuation alarms, security intrusion sirens, pro-
cess monitoring, shift start-and-dismissal horns, and paging sig-
nals.
5536MHV Series
30 Watt, High VolumeThree Outputs & Priority
FEATURES
> 30 Watt Output to 113 dB @ 10 ft
> 27 tone capability - No additionaltone modules needed
> PLC compatible
> Suitable for Division 2 locations
> Corrosion resistant electrostaticheat flowed epoxy finish
> Individual volume control
AGENCY APPROVALS
> NEMA Type 3R
> IP 44
> UL 464 and 1604 Listed
> UL & cUL Listed for indoor andoutdoor applications in Class I,Division 2, Groups A, B, C & D;Class II, Division 2, Groups F &G; and Class III HazardousLocation applications
> cUL C22.2 No. 205
> TUV Rheinland Certified
> CE Marked, LV & EMC Directives(Y6 AC only & AQ models)
SPECIFICATIONS
> 24V DC battery backup terminals
> Speaker can be rotated andlocked in any horizontal directionD
-04
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-47
Operating Input Card Signal Off Signal OnCat. No. Voltage Activation Voltage Standby Current (Amps) Operating Current (Amps)
5536MHV-24AQ 24V DC 24VDC 0.10 1.1424V AC 50/60 Hz 0.10 1.73
5536MHV-24Y6 125V DC 24VDC 0.03 0.34250V DC 0.02 0.17
120V AC 50/60 Hz 0.10 0.53240V AC 50/60 Hz 0.07 0.30
*This device is PLC compatible and may be operated by PLCs with output characteristics that match the input load requirements of this signal.
SIGNAL INPUT LOAD CHARACTERISTICS* (PLC output to meet following product input parameters)
Operating Max. off state Continuous on Surge (inrush/duration)Cat. No. voltage leakage current (mA) current (mA) Amps/milliseconds
5536MHV-24AQ 24V DC only 2 1500 8/4
24VDC Input 5V DC to 24V DC 2 6 —Board Circuit (each input)
Nut to adjustspeakerdirection
Mountingflange4 holes(2 each side)
3 1/2"(89mm)
6"(152mm)
11 1/2"(292mm)
9 3/4"(248mm)
15"(381mm)
1/2" (13mm)conduit mounting
6"(152mm)
8"(203mm)
4"(102mm)
9 3/4"(248mm)
2 1/2"(64mm)
D-04
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
4-49
FEATURES
5538-4
> Allows remote activation of up tofour tones
5538-4R
> Allows remote activation of up tofour tones
> Allows the Adaptatone MultipleTone System to be interfaced tolocal/system units for priorityoverride
Adaptatone® RemoteSignal Actuator
The Edwards 5538-4 & 5538-4R Adaptatone Remote Signal Actua-
tors permit an operator to initiate up to four tones from a remote lo-
cation.
Adaptatone signaling systems are designed for industrial applica-
tions calling for high decibel output and microprocessor reliability
combined with simultaneous signal delivery over all speakers in-
cluded in the system. Typical applications include: emergency
warning systems, plant evacuation alarms, security intrusion si-
rens, process monitoring, shift start-and-dismissal horns, and pag-
ing signals. see Adaptatone Signaling System Installation, pg. 4-56.
5538 Series
2 1/8"(54mm)
4 1/8"(105mm)
4 1/2"(114mm)
Provides NormallyOpen Contacts
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-28ELECTRONIC SIGNALS
Adaptatone® MillenniumCentral Tone Generator
The Edwards 5540M Millennium Central Tone Generator has been
designed for applications where simultaneous signaling of a high
decibel, heavy duty signal is required. The tone generator assures a
synchronous signaling sound from all remote speakers. The Millen-
nium Central Tone Generator produces the 27 standard Adaptatone
sounds. Four tones may be activated from field-wired, normally
open contacts, or a 24VDC or 120VAC external voltage source
such as an output of a PLC.
Normally open contacts can be obtained from the Cat. No. 5538-4 or
Cat. No. 5538-4R Adaptatone Signal Actuator. See page 4-49. The
tones are selected by setting miniature dip switches within the unit.
The programmed tones operate on a pyramid-type priority system.
For more information on priority tone operation and a complete list-
ing of all 27 tones, see page 4-55.
On-site volume control is accomplished by adjusting the conve-
niently located volume control inside the unit.
The 5540M-485Y6 is designed to be connected to RS485 networks,
allowing full serial signaling communication control.
Adaptatone Signaling Systems are designed for industrial applica-
tions calling for high decibel output and microprocessor reliability
combined with simultaneous signal delivery over all speakers in-
cluded in the system. Typical applications include: emergency
warning systems, plant evacuation alarms, security intrusion si-
rens, process monitoring, shift start-and-dismissal horns, and pag-
ing signals.
RS485 units are MEDI compatible. See page 4-10.
5540M Series
Synchronized System Signaling,Four Outputs, RS485 Activation
FEATURES
> 27 tone capability - No additionaltone modules needed
> PLC Compatible
> Captive Components
> Centralized programmable toneselection
> System-wide priority toneselection
> RS485 models available
AGENCY APPROVALS
> NEMA Type 3R
> IP 44
> UL 464 and 1604 Listed
> UL Listed for indoor and outdoorapplications in Class I, Div. 2,Groups A, B, C & D; Class II, Div.2, Groups F & G; and Class IIIhazardous locations
> cUL C22.2 No. 205 (24AQ, 24N5& 24Y6 models)
> TUV Rheinland Certified
> CE Marked - Cenelec LV & EMCDirectives (24Y6 AC only &24AQ models)
SPECIFICATIONS
> 24V DC battery backup terminals
> Short Circuit protectedD-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-29
Operating Input Card Signal Off Signal OnCat. No. Voltage Activation Voltage Standby Current (Amps) Operating Current (Amps)
5540M-24AQ 24V DC 24VDC 0.10 0.7424V AC 50/60 Hz 0.10 1.3
5540M-24N5 120V AC 50/60 Hz 24VDC 0.10 0.365540M-120N5 120V AC 50/60 Hz 120VAC 0.10 0.38
5540M-24Y6 120V AC 50/60 Hz 24V DC 0.10 0.32240V AC 50/60 Hz 0.10 0.20
125V DC 0.10 0.21250V DC 0.02 0.10
5540M-120Y6 120V AC 50/60 Hz 120VAC 0.10 0.31240V AC 50/60 Hz 0.10 0.20
125V DC 0.10 0.20250V DC 0.02 0.10
5540M-485Y6 120V AC 50/60 Hz RS485 0.10 0.31240V AC 50/60 Hz 0.10 0.20
125V DC 0.10 0.20250V DC 0.02 0.10
*This device is PLC compatible and may be operated by PLCs with output characteristics that match the input load requirements of this signal.
SIGNAL INPUT LOAD CHARACTERISTICS* (PLC output to meet following product input parameters)
Operating Max. off state Continuous on Surge (inrush/duration)Cat. No. voltage leakage current (mA) current (mA) Amps/milliseconds
5540M-24AQ 24V DC only 2 740 8/4
5540M-24N5 120V 60 Hz 2 360 2.82/4
5540M-120N5 120V 60 Hz 5 380 2.82/4
5540M-24Y6 120V 60 Hz 2 320 2.82/4
5540M-120Y6 120V 60 Hz 5 310 2.82/4
24VDC Input Board 24V DC (each input) 2 6 —
120VAC Input Board 120VAC 60 Hz (each input) 5 13 —
Mounting flange4 holes (2 each side)
2 1/2"(64mm)
6"(152mm)
4"(102mm)
1/2" (13mm)conduit mounting
6"(152mm)
8"(203mm)
3 1/2"(89mm)
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-32ELECTRONIC SIGNALS
Adaptatone® MillenniumCentral Tone Generator
The Edwards 5540MP Millennium Central Tone Generator, when
used with the 5542RPU Remote Paging Unit, is designed for appli-
cations where voice paging and other audio output are desired. The
paging/voice signal is inputed into the Remote Paging Unit via ei-
ther an audio pair or the 5542MIC series microphone.
The Millennium Central Tone Generator produces the 27 standard
Adaptatone sounds. The tone generator assures a synchronous sig-
naling sound from all remote speakers. Three tones may be pro-
grammed into the Tone Generator at any time. The tones may be
selected by setting miniature dip switches within the unit. The tones
operate on a pyramid-type priority system. The input from the Re-
mote Page Unit has priority over all three tones. The three signals
may be activated from field-wired, normally open contacts or a
24VDC external voltage source such as an output from a PLC. Nor-
mally open contacts can be obtained from the Cat. No. 5538-4 or
Cat. No. 5538-4R Adaptatone Signal Actuator. See page 4-49.
Adaptatone Signaling Systems are designed for industrial applica-
tions calling for high decibel output, voice paging, and microproces-
sor reliability combined with simultaneous signal delivery over all
speakers included in the system. Typical applications include: emer-
gency warning systems, plant evacuation alarms, security intrusion
sirens, process monitoring, shift start-and-dismissal horns, and
paging signals.
5540MP Series
Synchronized SystemPaging & Signaling
FEATURES
> Voice paging
> 27 tone capability - No additionaltone modules needed
> Suitable for Division 2 Locations
> Centralized programmable toneselection
> System-wide priority toneselection
AGENCY APPROVALS
> NEMA Type 3R
> IP 44
> UL 464 and 1604 Listed
> UL Listed for indoor and outdoorapplications in Class I, Div. 2,Groups A, B, C & D; Class II, Div.2, Groups F & G; and Class IIIhazardous locations
> cUL C22.2 No. 205
SPECIFICATIONS
> 24V DC battery backup terminalsprovided
> Short Circuit protected
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-33
Operating Input Card Signal Off Signal OnCat. No. Voltage Activation Voltage Standby Current (Amps) Operating Current (Amps)
5540MP-24Y6* 120V AC 50/60 Hz 24V DC 0.10 0.32240V AC 50/60 Hz 0.10 0.20
125V DC 0.10 0.21250V DC 0.02 0.10
* Must be connected to 5542RPU to operate
HazardousLocationSpeaker/AmplifierCat. Nos. 5545B
Speaker/AmplifierCat. No. 5532MHV
Speaker/AmplifierCat. No. 5532M Local/System Signal
Cat. No. 5536M3 Local Tones
Central ToneGenerator with pagingCat. No. 5540MP
ReentrantSpeakerCat. No. 5547
Cone SpeakerCat. No. 5551B
Remote AmplifierCat. No. 5535
Remote Signal ActuatorCat. No. 5538-4
for local inputs 2, 3, 4
4 wires5 wires
Cat. No. 5542RPU-M1V peak to peak audiosource or telephone systemaudio converted usingBogen Telephone AccessModule or equivalent
*Local Power 3 wires
Typical Adaptatone Paging System Configuration
Mounting flange4 holes (2 each side)
2 1/2"(64mm)
6"(152mm)
4"(102mm)
1/2" (13mm)conduit mounting
6"(152mm)
8"(203mm)
3 1/2"(89mm)
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-30ELECTRONIC SIGNALS
Adaptatone® MillenniumCentral Tone Generator
The Edwards 5540MV Adaptatone Millennium Central Tone Genera-
tor with Voice messaging has been designed for applications where
simultaneous signaling of a high decibel, heavy duty signal and pre-
recorded voice messaging is required. The tone generator assures
a synchronous signaling sound from all remote speakers. The Mil-
lennium Central Tone Generator produces the 27 standard
Adaptatone sounds and can store 20 seconds of field recorded
voice messages. Four signals may be activated from field-wired,
normally open contacts, or a 24VDC external voltage source such
as an output of a PLC. Normally open contacts can be obtained
from the Cat. No. 5538-4 or Cat. No. 5538-4R Adaptatone Signal Ac-
tuator. See page 4-49.
Messages and tones may be selected by setting miniature dip
switches within the unit. The programmed tones operate on a pyra-
mid-type priority system. For more information on priority tone op-
eration and a complete listing of all 27 tones, see page 4-55.
The 5540MV-485Y6 is designed to be connected to RS485 net-
works, allowing full serial signaling communication control.
Adaptatone Signaling Systems are designed for industrial applica-
tions calling for high decibel output and microprocessor reliability
combined with simultaneous signal delivery over all speakers in-
cluded in the system. Typical applications include: emergency warn-
ing systems, plant evacuation alarms, security intrusion sirens, pro-
cess monitoring, shift start-and-dismissal horns & paging signals.
RS485 units are MEDI compatible. See page 4-10.
5540MV Series
Voice Messaging & SystemSignaling, Four Outputs, RS485
FEATURES
> 27 tone capability - No additionaltone modules needed
> PLC compatible> 20 sec. of field recorded Voice> Suitable for Division 2 Locations> Centralized programmable tone
selection> System-wide priority tone
selection> RS485 model available
AGENCY APPROVALS
> NEMA Type 3R> IP 44> UL 464 and 1604 Listed> UL Listed for indoor and outdoor
applications in Class I, Div. 2,Groups A, B, C & D; Class II, Div.2, Groups F & G; and Class IIIhazardous locations
> cUL Listed C22.2 No. 205> CE Marked - Cenelec LV & EMC
Directives (24Y6 AC model only)
SPECIFICATIONS
> 24V DC battery backup terminals> Built in Presignal tone option on
first message location> Short Circuit protected
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-31
Operating Input Card Signal Off Signal OnCat. No. Voltage Activation Voltage Standby Current (Amps) Operating Current (Amps)
5540MV-24N5 120V AC 50/60 Hz 24VDC 0.10 0.36
5540MV-24Y6 120V AC 50/60 Hz 24VDC 0.10 0.32240V AC 50/60 Hz 0.10 0.20
125V DC 0.10 0.21250V DC 0.02 0.10
5540MV-485Y6 120V AC 50/60 Hz RS485 0.10 0.32240V AC 50/60 Hz 0.10 0.20
125V DC 0.10 0.21250V DC 0.02 0.10
*This device is PLC compatible and may be operated by PLCs with output characteristics that match the input load requirements of this signal.** = Input board designation 24 or 120
SIGNAL INPUT LOAD CHARACTERISTICS* (PLC output to meet following product input parameters)
Operating Max. off state Continuous on Surge (inrush/duration)Cat. No. voltage leakage current (mA) current (mA) Amps/milliseconds
5540MV-24N5 120V 60 Hz 2 360 2.82/4
5540MV-24Y6 120V 60 Hz 2 320 2.82/4
24VDC Input Board 24V DC 2 6 —
Mounting flange4 holes (2 each side)
2 1/2"(64mm)
6"(152mm)
4"(102mm)
1/2" (13mm)conduit mounting
6"(152mm)
8"(203mm)
3 1/2"(89mm)
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-34ELECTRONIC SIGNALS
Adaptatone® MillenniumSystem Master
The Edwards 5541M Millennium System Master is a fully super-
vised personnel notification control system for both emergency fa-
cility evacuation, and non-emergency process control and plant-
wide signaling communications.
The System Master may be used for ancilliary Fire Alarm evacua-
tion by tying into an existing fire alarm system.
The 5532M Series Speaker/Amplifier is used for sound output. Up
to 200 speaker/amplifiers can be connected to the system master.
The System Master is simple to program and operate using a nine-
button keypad and an easy-to-read, 40-character LCD display, with
Dynamic Zone Control (DZC™). DZC enables zone reconfiguration
through a series of simple keystrokes without the need for expen-
sive system rewiring. The System Master may be remotely pro-
grammed from a PC using available software.
Employing both voice and tone to alert, warn and communicate, the
System master features 68 built-in tones, hand-held microphone
operation, and stores up to four, five-second, field-recordable voice
messages for playing over remote speakers. PBX phone paging is
included, so no separate telephone paging system is required. The
Millennium System Master meets all OSHA self-monitoring,
prioritization and standby power requirements, plus the latest UL
standards for evacuation signaling.
MEDI compatible. See page 4-10.
5541M Series
Evacuation & Plant-wideSignaling, RS485 Activation
FEATURES
> 68 tones
> 4 zone control with zone paging
> Audio, voice & power supervision
> Microphone & external inputsupervision
> Up to 4 5-second voice messagesor one 20-second message
> Remote programming anddiagnostics
> Phone paging from PBX systems
> Up to 64 satellite units addressablethrough RS485
> Output and trouble relays designedfor fail-safe operation
> Top, side and bottom knockoutsfor easy wire entry
> LED alarm, standby power &status indications
> Activates LED text displays
> Easy to adjust audio output
AGENCY APPROVALS
> OSHA approved
> UL 2017 Listed for Emergency SelfMonitored Use
> UL 864 and UL 1711 Listed
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-35
Operating Signal Off Signal OnCat. No. Voltage Standby Current (Amps) Operating Current (Amps)
5541M-Y6 120V AC 60 Hz .14 .37240V AC 50 Hz .10 .22
18 1/4"(464mm)
4 5/8"(117mm)
14"(356mm)
Typical Adaptatone System Master Configuration
D-04
Up to 64 RS-485 devices(satellite panels or Adaptatone Millennium Units)
Up to 25 Multiple5542RPU's Input
(see manual)
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-36ELECTRONIC SIGNALS
5542RPU Remote Paging Unit
Sends audio page to, and is powered by the 5540MP-24Y6. UL and
cUL Listed. Input is received from a microphone input or audio pair
signal source such as phone PBX. Indoor, Type 2 enclosure when
flush wall mounted. Indoor, Type 12 or 2 when mounted to outdoor
listed 4" square utility box. Outdoor, Type 3R and Indoor Type 12 or
2 when mounted with 5542WPK to outdoor listed 4" square utility
box.
5542RPU-M Remote Paging Unit
Same as 5542RPU but includes 5542MIC-H Hand Held Microphone.
5542MIC-H Hand Held Microphone
Optional. May be plugged into 5542 RPU either permanently or as
needed.
5542MIC-D Desktop Microphone
Optional. May be plugged into 5542RPU either permanently or as
needed.
5542WPK Weatherproof Mounting Kit
Optional. Intended for use with 5542RPU or 5542RPU-M to provide
Type 3R outdoor protection for the 5542RPU series.
Weatherproof mounting kit for use with the 5542 Series Remote
Paging Unit. The mounting kit is UL Listed, CSA Certified and has a
Type 3R rating when mounted to the weatherproof box (included).
MR-201/C Relay
Optional. Used to enable the audio output from the 5540MP-24Y6 to
override output from other sources to the same 5532B or 5532BHV
series, 5532M or 5532MHV series, 5536M or 5536MHV series, and
5545B series products in the system.
5542RPU
Adaptatone® MillenniumRemote Paging Unit
FEATURES
> Weatherproof when mounted with5542WPK
> Optional Desk Microphone
> Removable Microphones
AGENCY APPROVALS
> UL 464 Listed
> cUL C22.2 No. 205
> Indoor Type 2 enclosure whenflush wall mounted
> Indoor Type 12 or 2 whenmounted to outdoor listed 4"(102mm) square utility box
> Outdoor Type 3R and indoor Type12 or 2 when mounted with5542WPK to outdoor listed 4"(102mm) square utility box
System Wide Paging
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-37
Cat. No. 5542RPU with 5542WPK weatherproof mounting kit
HazardousLocationSpeaker/AmplifierCat. Nos. 5545B
Speaker/AmplifierCat. No. 5532MHV
Speaker/AmplifierCat. No. 5532M
Local/System SignalCat. No. 5536M
3 Local Tones
Central ToneGenerator with pagingCat. No. 5540MP
ReentrantSpeakerCat. No. 5547
Cone SpeakerCat. No. 5551B
Remote AmplifierCat. No. 5535
Remote Signal ActuatorCat. No. 5538-4
for local inputs 2, 3, 4
4 wires
5 wires
Cat. No. 5542RPU-M1V peak to peak audiosource or telephone systemaudio converted usingBogen Telephone AccessModule or equivalent
*Local Power 3 wires
Typical Adaptatone Paging System Configuration
D-04
Cover Assembly
5542RPU RemotePage Unit Four (4) #6-32 x 3/8"
mounting screws(supplied with 5542WPK)
Cover Gasket
WeatherproofBack Box
Four (4) #6-32 x 5/8"mounting screws(supplied with 5542RPU Series)
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-42ELECTRONIC SIGNALS
Adaptatone®
Remote Speaker/Amp
The Edwards 5545M Hazardous Location Adaptatone Remote
Speaker/Amplifier has been designed for high decibel system opera-
tion when connected to the 5540M Central Tone Generator or 5541M
System Master Panel. See Adaptatone Tone Generator page 4-28.
Each Speaker/Amplifier operates directly from local power sources,
making it possible in a single system to connect the remote
Speaker/Amplifiers to local power sources of different voltages. The
unit mounts on any surface using three bolts. See Adaptatone Sig-
naling System Installation, pages 4-56.
Typical applications include signaling use in mining, granaries, flour
mills, tankers, refineries, laboratories, spray booths, and other haz-
ardous locations.
5545M SeriesFEATURES
> Corrosion resistant electrostaticheat flowed epoxy finish
> Individual volume control
AGENCY APPROVALS
> UL 464 and UL 1203 Listed
> UL Listed for Class I, Division 1and 2, Groups B, C, and Dhazardous locations
SPECIFICATIONS
> Speaker swivels 180° vertically orhorizontally depending onorientation of mounting bracket
> 30" (762mm) numbered wireleads
> Supplied with factory sealed 1/2"(13mm) threaded fitting for quickinstallation
> Heavy duty zinc cast construction
Explosionproof
D-0
4
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
TECHNICAL INFORMATION
4-43
Operating Signal Off Signal OnCat. No. Voltage Standby Current (Amps) Operating Current (Amps)
5545M-AQ 24V DC 0.061 0.47024V AC 50/60 Hz 0.250 1.320
5545M-Y6 120V AC 50/60 Hz 0.088 0.260240V AC 50/60 Hz 0.091 0.190
125V DC 0.031 0.130250V DC 0.091 0.070
Horn pivots one way 180°
11 1/4"(286mm)
11 1/4"(286mm)
18 3/8"(467mm)
D-04
ELECTRONIC SIGNALS
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-50
Multi-Power Taps2W, 4W, 8W & 15W
Reentrant Speaker
Low power consumption, multi-watt power selection, and high sound
level output speakers
For surface mounting, use Cat. No. 5549 Surface Backbox; for
weatherproof mounting use Cat. No. 5548 Weatherproof Backbox.
They are primarily intended for use with the 5535 Remote Amplifier,
page 4-48. For use in general utility signaling applications.
Sound Pressure Level*Cat. No. Input Voltage 2W 4W 8W 15W
5547-15W 70V 90 dBA 93 dBA 96 dBA 99 dBA
*At 10 feet (3.05m) in a reverberant room using 400-4000 Hz band limited pink noise perUL 1480
4 1/4"(108mm)
4 1/4"(108mm)
Total Depth of Speaker - 3 1/4" (83mm)
5547-15WFEATURES
> Multi-watt power selection
Weatherproof installationavailable
Fungus and moisture resistant
Baked epoxy finish
UL 1480 Listed
Four power taps - 2W, 4W, 8Wand 15W
70V RMS
Frequency: 400-4,000 Hz
6" (152mm) color coded leads
© Copyright 2004 Edwards
D-0
4
ELECTRONIC SIGNALS
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
4-51
Multi-power Taps2.5W, .5W, 1W & 2W
Cone Speaker
The Edwards 5551B-2W speakers are voice/tone notification appli-
ances designed for indoor ceiling or wall mounting and offer low
power consumption, multi-watt power selection, and high sound
level output.
Mounts on four inch square backbox with extension ring
They are primarily intended for use with the 5535 Remote Amplifier.
See 5535 Remote Amplifier, page 4-48. May be used for fire alarm
applications with compatible fire alarm control panels. Consult the
installation instructions supplied with the control panel.
8"(203mm)
One of two#8-32 x 1 1/2"(38mm) screws
2 1/2"(64mm)
5551B-2W
Multi-watt power selection
Wall or ceiling mount
Fire retardant and moisture proof
UL 1480 Listed for use in firealarm or emergencycommunication systems installedin accordance with NFPA 72National Fire Alarm Code
Four power taps - .25W, .5W,1.0W and 2.0W
70V RMS
Color - White
Sound Pressure Level*Cat. No. Input Voltage .25W .50W 1.0W 2.0W
5551B-2W 70V RMS 75 dBA 81 dBA 84 dBA 87 dBA
*At 10 feet (3.05m) in a reverberant room using 400-4000 Hz band limited pink noise perUL 1480
© Copyright 2004 Edwards
D-04
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com4-52ELECTRONIC SIGNALS
Millennium Mini-MiTM
Voice & Tone Generator
The Edwards 5560M Millennium Mini-Mi is a compact tone and
voice generator which is completely modular in construction. The
5560M base unit is supplied with or without a 110 candela strobe.
One of five optional modules may be installed in the base unit.
The 5560M is configured for stand-alone operation when installed
with the 556T-M Tone Module Board. One tone may be dipswitch
selected from a field of 55 tones and will be played whenever power
is applied to the unit. When installed with the 556T-M485 Tone Mod-
ule Board, any of the available 55 tones can be activated over a
RS485 Network. For a complete listing of all 55 tones, see page
4-55.
When configured with the 556V-M Voice Module Board, the unit is
capable of stand-alone voice operation. When power is applied to
the unit it will play up to 20 seconds of one pre-recorded, field pro-
grammed voice message.
The 5560M is capable of system operation when fitted with an au-
dio coupler board. The 556A-M Audio Coupler Board allows the
Mini-Mi to be operated as a system speaker amplifier over any sys-
tem that outputs 10, 25, or 70.7 VRMS. Audio input voltage is se-
lected on the audio coupler through an onboard jumper. The 5560M
Mini-Mi may also be used as a system signal on an RS485 network
using the 556A-M485 Audio Coupler Module Board.
Diode polarized fire alarm models are available with and without the
110 candela strobe. The fire alarm models operate from 16 to 33
VDC and are available in standard white or red Lexan housings.
5560M Series
Weatherproof, durable,Multi-purpose
Compact, modular design allowsunit to be configured with tone,voice, audio coupling or RS485
10, 25 or 70.7VRMS audio inputboards available
Internal volume control
Strobe and diode polarized firealarm models
Weatherproof
UL 464
UL 1971 (AW model only)
UL 464 and 1604 Listed
NEMA Type 3R
24V AC/24V DC, 120V AC, 16-33V DC
Rugged Lexan construction
ELECTRONIC SIGNALS
© Copyright 2004 Edwards
90 F ie lds tone Cour t ||||| Chesh i re , CT 06410P h : 2 0 3 . 6 9 9 . 3 3 0 0 ||||| F x : 2 0 3 . 6 9 9 . 3 1 0 8
www.edwards-s ignals.com
4-53
MOUNTING
The Mini-Mi mounts to any standard 4” (102mm)
backbox and is suitable for outdoor mounting when
mounted to the 449 backbox or any weatherproof
4" (102mm) box.
APPLICATIONS
The 5560M Mini-Mi is ideal for sounding stand-alone
or system tones and voice in factory hallway, office
and personnel areas where the use of large, horn
type devices is not desirable because of sound out-
put and appearance issues. The Mini-Mi may also be
used for fire/emergency signaling applications,
where operation and control of high decibel audio
and voice is required for plant or area-wide tone and
voice notification.
Cat. No. Color Description Voltage
5560M-AQ White Mini-Mi Base Model 24VDC or 24VAC 50/60 Hz
5560M-N5 White Mini-Mi Base Model 120VAC 50/60 Hz
5560MD-AW White Mini-Mi Base Model - Diode Polarized 16-33VDC
5560MDR-AW Red Mini-Mi Base Model - Diode Polarized 16-33VDC
5560MS-AQ White Mini-Mi Base Model with Strobe 24VDC or 24VAC 50/60 Hz
5560MS-N5 White Mini-Mi Base Model with Strobe 120VAC 50/60 Hz
5560MDS-AW White Mini-Mi Base Model with Strobe - Diode Polarized 16-33VDC
5560MDSR-AW Red Mini-Mi Base Model with Strobe - Diode Polarized 16-33VDC
556A-M N/A Audio Coupler Module Board N/A
556A-M485 N/A Audio Coupler Module Board with RS485 Connectivity N/A
556T-M N/A Tone Module Board N/A
556T-M485 N/A Tone Module Board with RS485 Connectivity N/A
556V-M N/A Voice Module Board N/A
5.06"(128.5mm)
6.56"(166.6mm)