HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
UseDYNACIAT single unit chilled water producers or hot water producers with water-cooled condensers are medium-capacity machines designed for heating or air conditioning applications in collective housing blocks and business units, as well as industrial premises and processes. They operate by drawing or recovering heat from the ground (horizontal or vertical geothermal loop) or from groundwater. When producing cold water, they can also be connected to a drycooler or a water cooling tower. The LG range is also available in a version without a condenser (LGN version) which is covered in a separate manual. These units are designed to be installed in machine rooms that are protected against freezing temperatures and inclement weather. Connected to an underfloor heating or cooling system, fan
coil units or an air handling unit, the LG series heat pump provides heating and air conditioning for buildings using a set of valves located on the hydraulic system (not supplied).The ILG series features a reversing valve which enables you to switch between cooling and heating modes, independently of the hydraulic system.Each unit is delivered fully assembled, wired (control and power), charged with refrigerant and factory tested.Simply make the necessary electrical and hydraulic connections, and your unit is ready to operate.In order to enable quick and easy installation, the DYNACIAT range includes a HYDRAULIC option (on the secondary circuit) and an AQUATHERM option (on the primary circuit). These self-contained modules with an external design identical to the DYNACIAT range can be perfectly integrated into a machine room.
The DYNACIAT LG series is supplied as standard with the following components:- water-cooled condenser- chilled-water evaporator- chilled water or hot water outlet power control- control, automatic operation and startup box: . Power supply: 3~50 Hz 400 V (+10%/-10%) + earth . Control circuit 1~50 Hz 230 V (+10%/-10%)
(transformers fitted on unit as standard)- casing for indoor installation
n Complies with European EC directives- "Low voltage" directive (LVD)- 98/37 EEC machines- Electromagnetic 89/336/EEC (EMC)- PED 97/23 CEE pressure equipment . category 2 (LG-LGP-ILG)
n Complies with standards- EN 60-204 and EN 378-2
Description
DYNACIAT LG - LGP seriesCooling-only or heating-only models with water-cooled condenser.
DYNACIAT ILG seriesWater-to-water reversible heat pumps.
range
High energy efficiency
Compact and quietScroll compressors
Brazed-plate heat exchangers
Self-adjusting electronic control
Hydraulic module linked with aquatherm moduleCooling capacity: 35 to 180 kWHeating capacity: 40 to 210 kW
Cooling or heating
CoolingHeating
410A
Hydraulic module
2 HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIATMain coMponentsn Casing- Casing made from galvanised sheet metal panels- RAL 7024 and RAL 7035 lacquer coatingn Hermetic SCROLL compressors- Built-in electric motor cooled by suction gases- Motor protected by internal winding thermostat- Placed on anti-vibration mountsn Evaporator- Brazed-plate exchanger(s)- End and inside plates in AISI 316 stainless steel- High-performance, optimised plate patterns- Thermal insulationn Condensern LG - LGP - ILG series- Brazed-plate exchanger(s)- End and inside plates in AISI 316 stainless steel- High-performance, optimised plate patterns- Thermal insulationn Control functions and safety devices- Thermostatic expansion valve(s)- Refrigerant high and low pressure safety devices- Safety valves on refrigeration circuit- Temperature and pressure sensors- Evaporator water flow controller fittedn Electrics boxThe fully wired electrics box, which houses all the electrical components and the electronic CPU board, controls the entire unit, monitors its operation, adjusts water setpoints and interfaces with an external control system.It comprises:- Control and power circuits- Wire numbering- Main safety switch with handle on front- Control circuit transformer- Circuit breakers on the power and control circuits- Compressor and motor switch(es)- Main earth connection- Microprocessor-controlled electronic control unit . CONNECT2 LG - LGP . MICROCONNECT ILG- Alarm or information signals on free terminals
Options (kit for installation on site)n Main options (delivered separately)- Hydraulic module (LG - LGN 120 - 600 and ILG 120 - 300)- Aquatherm module (LG - ILG 120 - 300)- Remote control unit (except ILG)- Additional voltage-free contact boards (except ILG)- Evaporator and condenser flexible couplings- 800-micron water filter on evaporator and condenser- Two-way valve condenser for unused water (municipal water)
(LG 120 - 500)- Three-way valve condenser for start-up at low temperatures,
(LG 120 - 500)- Phase controller (rotation, missing phases, overvoltage and
undervoltage)- Soft Start gradual start-up- Master/slave control sensor for water outlet regulation
(except ILG)
DYNACIAT LG: CONNECT2 electronic control moduleCIAT electronic control module with microprocessor and CPU, with central automatic operation and access to internal operation states.Features and options:- Start, stop, reset or remote
control- cooling or heating operating
mode selector- Outputs. RS485 output for
CMS link (ModBus-JBus)• additional potential-free (dry)
contact card adapter• remote control adapter- Multilingual analogue LCD and LED displayFunctions: - Operation information displayed via: . multilingual clear-text messages . direct temperature and pressure readings- complete management of compressors with start-up
sequence, timer and runtime balancing- Master/Slave Management allows two machines to be
controlled on a single water loop, by alternating the Master and Slave according to the running time.
- Short-cycle protection- Self-adjusting and proactive functions with adjustment of
settings drift control- In series stage system on multiple compressors lowers power
based on cooling and heating demands controlled using the water temperatures
- Monitoring of internal operation parameters- Second setpoint management- Setpoint adjustable by 4-20 mA signal- Master/slave operation- Weekly programming- Direct display of water temperatures- Diagnosis of operation and fault states: . HP/LP, water flow, compressor motor(s), frost protection- Remote management and remote monitoring
DYNACIAT ILG: MICROCONNECT electronic control modulen Components - 1 control terminal with display to view and select the
different modes (on/off, heating/cooling mode, timer, weekly programming)
- an electronic control board- an outdoor temperature sensorn Functions - controls the water or air temperature in
each mode- continuous monitoring of operating
parameters - display and diagnosis of faults - setpoint adjustment based on outdoor
temperature (in heating and cooling modes)
- auxiliary management- management and automatic equalisation of compressor
operating time (multiple compressors)- dialogue with remote control terminal
3
DYN
ACIA
T
HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
stanDarD eqUipMent/available options
DYNACIAT LG LG - LGP 120 V to 600 V ILG 120 V to 300 V
Hydraulic module z z
Aquatherm module (120 - 300) z z
Safety switch l l
Control circuit transformer l l
Electrical cabinet wire numbers l l
RS485 communication interface l -
Ethernet gateway l -
Water flow controller l l
Master/slave control of two machines l -
Soft start z z
Water filter on evaporator and condenser z z
Phase controller (reversal, loss, asymmetry) z z
Anti-vibration mounts l l
Flexible hydraulic couplings on evaporator and condenser z z
Refrigent leak detection z z
2-way valve kit (except LG 540 V - 600 V) z -
3-way valve kit (except LG 540 V - 600 V) z -
Master/slave control sensor z -
Underfloor heating/cooling system thermostat kit - z
Humidity sensor for underfloor heating/cooling system - z
DUO model (floor management + terminal unit) - z
Loop heater (9 or 15 kW) - z
400 L mixer tank - z
9 kW auxiliary electric heater kit - z
Remote control unit (remote control console) z -
Relay board with dry contacts z -
MULTICONNECT multi-unit management z -
LONWORKS/BACNET gateway z -
l Supplied as standard s Factory-assembled option z Option supplied as a kit - Not available
4 HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIAT
Outputs in accordance with EUROVENT standard EN 14511 - 2013 conditions(1) Chilled water 12°C / 7°C and hot water 30°C / 35°C (2) Chilled water 10°C / 7°C and hot water 40°C / 45°C
(3) Hot water 30°C/35°C - Average climate conditions according to standard EN 14825-2013
(4) LW: Overall sound power level as per ISO3744
DYNACIAT LG - LGP 120V 150V 200V 240V 300V 350V 400V 500V 540V 600V
Net cooling capacity (1) kW 34,50 45,30 61,10 68,60 90,90 104,70 118,90 146,50 158,90 181,90
Net power input (1) kW 8,00 10,30 13,90 16,20 20,30 23,60 26,90 33,80 36,10 40,10
Net energy efficiency rating (EER) (1) kW/kW 4,29 4,40 4,40 4,23 4,48 4,43 4,42 4,33 4,40 4,53
Net ESEER kW/kW 4,63 4,69 5,23 4,99 4,97 4,98 5,02 4,80 4,99 5,06
Net heating capacity (2) kW 40,5 53,4 71,5 80,6 107 122,4 140 173 187 213,3Net power input (2) kW 10,1 12,9 17,7 20,3 25,3 29,1 33,2 41,4 45,1 50,2
Net COP (2) 4,02 4,13 4,04 3,98 4,22 4,20 4,21 4,17 4,13 4,25Net Seasonal Coefficient of Performance (SCOP) (3) kW/kW 5,23 5,17 5,36 5,27 5,23 5,16 5,12 5,26 5,05 5,2
ŋs heating % 201 199 206 203 201 198 197 202 194 200
Prated kW 41 55,02 73,19 81,11 109,27 125,87 143,79 176,6 190,71 219,31
Sound power level (4) dB(A) 67 70 69 70 73 74 75 76 75 76
No. of refrigerating circuits 1 2
Refrigerant (GWP) R410A (GWP = 2088)
Refrigerant charge, circuits 1 and 2 kg 3,3 3,8 6,8 7,1 9,9 11 13,7 16,1 7.3/9.5 9.9/9.9
CO2 equivalent tonne TCO2Eq 6,89 7,93 14,19 14,82 20,67 22,96 28,60 33,61 35,07 41,34
Type Hermetic SCROLL (2900 rpm)
Start-up mode - Direct in series
Number 1 2 4
Power control % 100-0 100-0 100-50-0 100-50-0 100-50-0 100-5743-0
100-6337-0 100-50-0 100-72-50-
22-0100-75-50-
25-0Refrigerant oil type Polyolester POE 3MAF (32cSt)
Oil capacityl (cir1) 3,25 4,14 6,50 6,50 8,28 8,84 9,76 11,24 8,28 8,28
l (cir2) - - - - - - - - 6,50 8,28
Type ph/Hz/V 3~50Hz 400V (+10%/-10%) + Earth
Max. rated current A 23,2 30,2 42,2 46,2 60,2 66,2 76,0 91,8 106,2 120,2
Starting current A 137 174 139 160 204 255 302 317,8 250 264Starting currentSoft Start option A 70 60 76 93 90 167 194 210 136 150
Breaking capacity kA 50
Unit protection IP22
Max. wire cross-section mm2 50 95
Control circuit voltage ph/Hz/V 1~50Hz 230V (+10%/-10%) - transformer fitted
Type Brazed-plate heat exchanger
Water content l 2,7 3,6 4,8 5,3 9,9 11,3 12,8 15,7 15,2 19,8
Min./max. water outlet temp °C -10°C/+18°C
Min/max water flow m3/h 3.5 / 11.2 4.8 / 14.6 6.2 / 19.8 7.0 / 22.2 9.5 / 29.2 10.9 / 34.0 12.4 / 38.4 15.2 / 47.5 16.4 / 51.1 19.1 / 58.4
Water connections Ø G 1’’1/2 G 2’’ G 2’’1/2 DN80 PN16
Max service pressure bar 10 bar, water sideType Brazed-plate heat exchangerWater content l 3 4,1 5,1 5,8 8,0 9,4 11,1 15,2 13,8 16,0Min./max. water outlet temp °C +30°C/+55°CMin/max water flow m3/h 3.1 / 8.5 4.1 / 11.1 5.4 / 15.1 6.1 / 17.0 8.2 / 22.3 9.4 / 26.0 10.7 / 29.4 13.1 / 35.0 14.3 / 39.1 16.3 / 44.6Water connections Ø G 1’’1/2 G 2’’ G 2’’1/2 DN80 PN16Max service pressure bar 10 bar, water sideMin. water volume (system) l 226 299 197 222 292 286 279 454 217 274Operating height mm 1201Length mm 798 1492 2380Depth mm 883Weight (empty) kg 230 300 385 390 590 620 665 735 930 1125Operating weight kg 240 312 400 406 617 650 703 780 990 1190Storage temperature °C -20°C/+50°C
technical anD electrical properties
Perfo
rman
ceCo
mpr
esso
rRe
frige
ratio
n ci
rcui
tPo
wer
sup
ply
Evap
orat
orCo
nden
ser
Dim
ensio
nsW
eigh
t
5
DYN
ACIA
T
HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIAT ILG 120V 150V 200V 240V 300V
Net cooling capacity (1) kW 29 37,8 50,5 58,9 76,7
Net power input (1) kW 8,4 10,8 14,6 16,3 20,9
Net energy efficiency rating (EER) (1) kW/kW 3,44 3,51 3,46 3,62 3,67
Net ESEER kW/kW 3,53 3,61 4,31 4,38 4,34
Net heating capacity (2) kW 39,2 51,2 68,3 79 101,9
Net power input (2) kW 9,9 12,7 17,3 19 24,16
Net COP (2) 3,98 4,02 3,95 4,16 4,15
Net Seasonal Coefficient of Performance (SCOP) (3) kW/kW 5,33 5,36 5,63 6,02 5,54
ŋs heating % 205 206 217 233 214
Prated kW 41,14 55,85 74,85 83,83 106,64
Sound power level (4) dB(A) 67 70 69 70 73
No. of refrigerating circuits 1
Refrigerant (GWP) R410A (GWP =2088)
Refrigerant content kg 3,25 3,6 5,5 8,1 9,2
CO2 equivalent tonne TCO2Eq 6,78 7,51 11,48 16,91 19,20
Type Hermetic SCROLL (2900 rpm)
Start-up mode - Direct in series
Number 1 2
Power control % 100-0 100-0 100-50-0 100-50-0 100-50-0
Refrigerant oil type Polyolester POE 3MAF (32cSt)
Oil capacity l 3,25 4,14 6,50 6,50 8,28
Type ph/Hz/V 3~50Hz 400V (+10%/-10%) + Earth
Max. rated current A 23,2 30,2 42,2 46,2 60,2
Starting current A 137 174 139, 160 204Starting currentSoft Start option A 70 60 76 93 90
Breaking capacity kA 50
Unit protection IP22
Max. wire cross-section mm2 50
Control circuit voltage ph/Hz/V 1~50 Hz 230 V (+10%/-10%) - transformer fitted
Type Brazed-plate heat exchanger
Water content l 2,7 3,6 4,8 5,3 9,9
Minimum/maximum water flow rate m3/h 4.1 / 14 5.3 / 18 7.2 / 25 8.4 / 28 11 / 36
Water connections Ø G 1’’1/2 G 2’’
Max service pressure bar 10 bar, water side
Type Brazed-plate heat exchanger
Water content l 2,7 3,6 4,8 5,8 9,9
Min/max water flow m3/h 4.1 / 14 5.3 / 18 7.2 / 25 8.4 / 28 11 / 36
Water connections Ø G 1’’1/2 G 2’’
Max service pressure bar 10 bar, water side
Min water volume l 226 299 197 222 292
Operating height mm 1201
Length mm 798 1492
Depth mm 883
Weight (empty) kg 226 289 379 452 595
Operating weight kg 237 301 394 468 622
Storage temperature °C -20°C/+50°C
technical anD electrical properties
Perfo
rman
ceCo
mpr
esso
rRe
frige
ratio
n cir
cuit
Pow
er s
uppl
yIn
door
circ
uit
Out
door
circ
uit
Dim
ensio
nsW
eigh
t
Outputs in accordance with EUROVENT standard EN 14511 - 2013 conditions(1) Chilled water 12°C / 7°C and hot water 30°C / 35°C (2) Chilled water 10°C / 7°C and hot water 40°C / 45°C
(3) Hot water 30°C/35°C - Average climate conditions according to standard EN 14825-2013
(4) LW: Overall sound power level as per ISO3744
6 HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIAT
Glycol compulsory
operating range
Brazed-plate evaporator
Water outlet temperature (°C)
Δ T
acc
epta
ble
wat
er in
let/
outle
t tem
pera
ture
diff
eren
ce
Δ T from performance table calculations
-4-4Chilled water outlet (°C)
ILG 120 to 300heating mode
7 -4-3
Con
dens
er w
ater
out
let (
°C)
LG - LGP 120 V - 600 V
Glycol compulsory
Chilled water outlet (°C) Chilled water outlet (°C)
Con
dens
er w
ater
out
let (
°C)
ILG 120 to 300cooling mode
Con
dens
er w
ater
out
let (
°C)
evaporator liMitsThe curves opposite show the minimum and maximum acceptable temperature differences for chilled water or glycol/water solution based on the outlet temperature.
Glycol/water mix
Example:
For a water outlet temperature of +5°C
Minimum difference: 2.6°C Water temperature: 7.6/5°C
Maximum difference: 6°C Water temperature: 11/5°CIf the temperature difference calculated is outside these two curves, contact us.
Maximum DT
Minimum DT
% concentration volume percent of ethylene
Multiplier correction factorCooling capacity Water flow rate Pressure drops
10 0.99 1.05 1.0520 0.985 1.10 1.1030 0.98 1.15 1.1540 0.97 1.20 1.23
correction factor for ethylene glycolnEvaporator
n Glycol concentration requiredVolume concentration in % 0 10 20 30 40
Ethylene glycolFreezing point °C 0 -4 -10 -18 -27Minimum water outlet °C 5 3 -1 -7 -14
Propylene glycolFreezing point °C 0 -4 -9 -16 -25Minimum water outlet °C 5 4 1 -4 -9
7
DYN
ACIA
T
HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
The Connect2 controller uses anticipation logic making it particularly flexible in adjusting operation to changes in settings, particularly on low-volume hydraulic systems.By adjusting compressor running times, it prevents short-cycle protection cycles from starting and, in most cases, eliminates the need for a buffer tank.The calculation of the minimum water volume is given for EUROVENT rated conditions, in cooling mode only.This value is applicable for most air conditioning applications (unit with fan coil units)
Note: For installations running with a low volume of water (unit with air handling unit) or for industrial processes, the buffer tank is essential.For heat pump applications, we recommend the use of a buffer tank to ensure a stable temperature is maintained during the defrosting cycles.
MiniMUM water volUMe
LG - ILG models 120V 150V 200V 240V 300V 350V 400V 500V 540V 600VMin. system capacity (litres) 226 299 197 222 292 286 279 454 217 274
soUnD levelsThe DYNACIAT LG - LGP - ILG range features a "noiseless" construction designed to reduce vibrations and noise sources:
n Scroll compressor(s) fitted on anti-vibration mounts n Refrigerating circuit mounted on a structure separate from the frame to prevent vibrations (120 to 600) n Pipework separate from the structure of the unit
n Sound power level ref 2 x 10-12 Pa ±3 dB (Lw)
n Sound pressure level ref 2 x 10-5 Pa ±3 dB (Lp)Measurement conditions: n free field n 10 metres from machine, 1.50 metres above floor level n directivity 2
SizesSOUND POWER LEVEL SPECTRUM (dB) Overall Lw
overall dB(A)63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz
120V 77 65 65 59 59 61 59 67150V 78 74 72 67 60 64 57 70200V 78 60 60 62 62 64 62 69240V 78 68 68 62 62 64 62 70300V 81 77 75 70 63 67 60 73350V 82 75 75 68 64 69 63 74400V 83 76 76 69 67 70 64 75500V 84 74 77 67 69 72 66 76540V 83 78 76 70 66 69 64 75600V 84 80 78 73 66 70 63 76
Sizes SOUND PRESSURE SPECTRUM (dB) Lp level
overall dB(A)63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz
120V 46 34 34 28 28 29 28 35150V 47 43 41 35 29 33 25 39200V 47 28 29 31 31 33 30 38240V 47 37 37 31 31 32 31 38300V 50 46 44 38 32 36 28 42350V 51 43 43 37 33 38 31 42400V 52 44 45 37 36 39 32 44500V 53 43 45 36 38 40 34 45540V 51 46 44 39 34 37 33 43600V 52 48 47 41 35 39 31 45
Note: Sound pressure levels depend on each system. As such, the levels listed above are given for information only. We remind you that only sound power levels are comparable and certified.
8 HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIAT
hyDraUlic configUrationn Hydraulic moduleThis module is available for the entire DYNACIAT range:• LG and LGN (version without a condenser) in sizes 120 to 600 • ILG (reversible model) in sizes 120 to 300.
Hydraulic module configuration
Hydraulic module specifications
MHG 40 41 42 43 46
Pump No. 40 41 42 43 46
Max. power input kW 0.95 1.37 1.83 2.62 3.54
Max. current at 50 Hz/400 V A 1.91 2.36 3.15 5.2 6
Min water flow rate m3/h 3 3 4 4 10
Max. pressure mWC 17.5 21.5 22 24.5 23
Max water flow rate m3/h 19 22.5 30 30 60
Min pressure mWC 8.5 8 10 14 11.5
Tank volume l 150
Expansion vessel volume l 24
Electrical supply V 3 ph - 50 Hz - 400 V (+10%/-10%) + earth
Protection rating IP 55
Hydraulic connections Ø 1”1/2 - 2” - 2”1/2
Dimensions Height x Length x Depth mm 1201 x 798 x 883
WeightEmpty kg 285
In operation kg 535
H
R
F
D
I
P
H
E
J
KK
S
Options: Kit for the flexible connections to the heat pump and indoor circuitPressure gauge + control valve kitScreen filterPump suction pressure safety device(option only available when the module is connected to a DYANCIAT LG or LGN)
Features and options:Expansion vesselDrain valveBuffer tankAir bleed valveSafety valveHydraulic pump
D
E
F
I
J
K
R
S
P
9
DYN
ACIA
T
HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
Operating pressure - Single pumps 40 - 41 - 42 - 43 - 46(does not take into account the pressure drop inside the hydraulic module and the heat pump)
Hydraulic module pressure drop
Man
omet
ric h
ead
of p
umps
(mW
C)
3 4 5 6 7 8 9 10 20 30 40 50 60 70 800.1
0.2
0.3
0.4
0.50.60.70.80.9
1
2
3
4
5678
10
MHG
40-
41-4
2-43
MHG
46
Wat
er p
ress
ure
drop
(mW
C)
Water flow rate m3/h
Water flow rate m3/h
3 4 5 6 7 8 9 10 20 30 40 50 60 70 805
6
7
8
9
10
20
30
water pressUre Drop
10 HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIAT
hyDraUlic configUrationn Aquatherm moduleThe Aquatherm module is provided as an option on the DYNACIAT LG and ILG (reversible model) range up to size 300.It is connected to the sensor side in geothermal applications with an intermediate exchanger.
Aquatherm module configuration
Aquatherm module specifications
MA 29 38 51 59 77
Exchanger Itex Ageo 29 Itex Ageo 38 Itex Ageo 51 Itex Ageo 59 Itex Ageo 77
Accelerator pump* IPL 50/120-1.5/2 N°140B
Max. power input kW 1,85
Max. current at 50 Hz/400 V A 3,2
Min water flow rate m3/h 5 6,5 9 10 13,5
Max. pressure mWC 11.5 10.9 11.9 11.4 12.8
Max water flow rate m3/h 14 18 25 28 36
Min. pressure mWC 8.6 5.8 10.1 9.1 8.4
Expansion vessel volume l 12
Electrical supply V 3 ph - 50 Hz - 400 V (+10%/-10%) + earth
Protection rating IPX4D
Hydraulic connections Ø 1”1/2 2”
Dimensions Height x Length x Depth mm 1201 x 798 x 883
WeightEmpty kg 246 368 383
In operation kg 258 396 423
P
G
O
JJ
F O
P
K
F
D
G
R
S
Options: Kit for the flexible connections to the heat pump and indoor circuitScreen filterPump suction pressure safety device(option only available when the module is connected to a DYNACIAT LG or LGN)
Features and options:Expansion vesselDrain valveShut-off valveITEX AGEO exchangerSafety valveAccelerator pump
D
F
J
K
R
S
* 3-speed accelerator pump (factory set at medium speed)
11
DYN
ACIA
T
HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
O
DYNACIAT ILG
Power exchanged*(kW) Module MA
Primary operation water 10°C/6°C Secondary operation MPG 20% 4/8°C
Flow rate (m3/h) Module pressure drop** (mWC) Flow rate (m3/h)
120V 30.2 29 6.3 2.6 6.7
150V 39.2 38 8.2 3.6 8.7
200V 52.4 51 10.7 0.85 11.6
240V 60 59 13 1 13.3
300V 78.7 77 17.1 1.1 17.4
DYNACIAT LGP
Power exchanged*(kW) Module MA
Primary operation water 10°C/6°C Secondary operation MPG 20% 4/8°C
Flow rate (m3/h) Module pressure drop** (mWC) Flow rate (m3/h)
120V 30.7 29 6.5 2.8 6.9
150V 40.4 38 8.4 3.7 9.1
200V 54.3 51 11.8 0.96 12.2
240V 61 59 13.2 1.1 13.7
300V 80.6 77 17.5 1.2 18
well water interMeDiate exchanger specifications
* Condenser mode 30/35°C**Necessary for sizing the well pump
* Condenser mode 30/35°C**Necessary for sizing the well pump
Echangeur intermédiaire ITEX AGEO
MPG 20% 4°C
MPG 20% 8°C
30°C35°C
Rejet
EtéHiverCondenseur Evaporateur
ITEX AGEO intermediate exchanger
SummerWinter
MPG 20% 4°C
MPG 20% 8°C
Discharge
Condenser Evaporator
12 HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIAT
Water flow rate m3/h
Operating pressure of the Aquatherm module accelerator pump (between the heat pump and the module)Does not take into account the pressure drop inside the Aquatherm module and the heat pump
Man
omet
ric h
ead
of th
e m
WC
ac
cele
rato
r pum
p
water pressUre Drop
Pressure drop for modules connected to a heat pump
3 4 5 6 7 8 9 10 15 20 25 30 40 50 600.3
0.40.50.6
0.81
2
3
456
810
20
30
MA38MA29
MA59
MA51
MA77
Water flow rate m3/h
Pressure drop for modules connected to ground water
Wat
er p
ress
ure
drop
(mW
C)
Wat
er p
ress
ure
drop
(mW
C)
3 4 5 6 7 8 9 10 15 20 25 30 40 50 600.3
0.40.50.6
0.81
2
3
456
810
20
30
Water flow rate m3/h
MA29
MA38
MA51
MA77
MA59
140
13
DYN
ACIA
T
HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
cooling anD heating capacitiesDYNACIAT LG - LGP
R4
10
A
LGLGP
CONDENSER WATER OUTLET TEMPERATURE (°C)Evaporator water outlet
temperature (°C)
30 35 40 45 50 55Cc Pi Hc Cc Pi Hc Cc Pi Hc Cc Pi Hc Cc Pi Hc Cc Pi HckW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
120V
Glycol/water mix
-10 19.0 6.7 25.4 17.9 7.5 25 16.5 8.4 24.5 15.2 9.4 24.1-4 24.0 6.7 30.5 22.6 7.5 29.9 21.1 8.4 29.1 19.4 9.4 28.3 17.8 10.6 27.82 30.1 6.7 36.6 28.6 7.5 35.8 27.0 8.3 35 25.2 9.3 34.1 23.2 10.5 33.2 21.1 11.8 32.3
Pure water
5 34.2 6.8 40.8 32.6 7.5 39.9 30.8 8.4 38.8 28.9 9.3 37.9 26.8 10.5 36.8 24.5 11.7 35.77 36.4 6.8 43.0 34.7 7.5 42.0 33.0 8.4 41.1 30.9 9.3 39.9 28.6 10.5 38.7 26.3 11.7 37.5
12 42.8 6.9 49.5 41.0 7.6 48.4 39.0 8.4 47.1 36.7 9.4 45.8 34.3 10.4 44.4 31.6 11.7 42.815 46.1 6.9 52.8 44.3 7.6 51.7 42.3 8.3 50.4 40.0 9.2 49.0 37.4 10.2 47.3 34.6 11.5 45.618 50.2 7.0 57.1 48.2 7.7 55.7 46.0 8.4 54.2 43.7 9.2 52.6 40.9 10.3 50.9 37.9 11.4 48.9
150V
Glycol/water mix
-10 25.5 8.4 33.6 24.2 9.3 33.1 22.8 10.4 32.7 21.3 11.5 32.1-4 31.6 8.5 39.8 30.2 9.5 39.3 28.6 10.5 38.7 26.9 11.7 38.1 24.8 13.1 37.22 39.3 8.6 47.6 37.7 9.5 46.9 35.9 10.6 46.1 33.8 11.8 45.2 31.5 13.2 44.2 29.0 14.8 43.0
Pure water
5 44.6 8.7 53.1 42.9 9.6 52.1 40.8 10.7 51.1 38.6 11.9 50.0 36.0 13.3 48.8 33.3 14.8 47.57 47.5 8.7 56.0 45.6 9.6 55.0 43.5 10.7 53.8 41.2 11.9 52.7 38.6 13.3 51.4 35.7 14.9 49.9
12 55.9 9.0 64.7 53.8 9.8 63.3 51.4 10.8 61.9 48.7 12.0 60.4 45.8 13.4 58.7 42.6 15.0 56.915 60.5 9.0 69.3 58.3 9.8 67.8 55.8 10.7 66.2 52.9 11.8 64.4 49.6 13.2 62.4 46.3 14.7 60.518 65.9 9.3 75.0 63.6 10.0 73.4 60.6 10.8 71.2 57.8 11.9 69.4 54.4 13.2 67.2 50.9 14.6 65.1
200V
Glycol/water mix
-10 33.5 11.4 44.5 31.4 12.9 43.7 29.1 14.6 42.9 26.6 16.5 42.1-4 42.5 11.4 53.5 40.1 12.9 52.5 37.5 14.6 51.4 34.6 16.5 50.2 31.5 18.7 49.22 53.2 11.5 64.3 50.5 12.9 62.9 47.6 14.5 61.6 44.4 16.4 60.1 41.0 18.5 58.6 37.2 21 57.1
Pure water
5 60.5 11.6 71.7 57.7 13.0 70.2 54.5 14.6 68.6 51.0 16.4 66.8 47.2 18.5 64.9 43.1 20.9 63.07 64.4 11.7 75.7 61.5 13.0 74.1 58.2 14.6 72.3 54.6 16.4 70.4 50.6 18.5 68.4 46.4 20.9 66.3
12 76.0 11.8 87.5 73.0 13.1 85.7 69.5 14.5 83.6 65.4 16.3 81.2 61.1 18.3 78.7 56.4 20.5 76.215 81.8 11.9 93.4 78.5 13.1 91.3 75.0 14.5 89.2 70.8 16.1 86.4 66.4 18.0 83.7 60.9 20.4 80.518 89.0 12.1 100.9 85.5 13.3 98.6 81.6 14.7 96.0 77.8 16.2 93.5 72.5 18.2 90.1 67.0 20.3 86.6
240V
Glycol/water mix
-10 37.8 13.4 50.6 35.6 15.0 49.8 32.8 16.8 48.8 30.1 18.9 47.8-4 47.9 13.4 60.9 45.3 15.0 59.7 42.3 16.8 58.3 39.2 18.9 57.1 35.7 21.2 55.82 59.7 13.5 72.9 56.8 15.0 71.3 53.6 16.8 69.7 50.0 18.8 68.0 46.1 21.1 66.2 41.9 23.7 64.4
Pure water
5 67.7 13.6 80.9 64.6 15.1 79.2 61.1 16.8 77.4 57.3 18.8 75.3 53.1 21.0 73.2 48.6 23.6 71.07 72.2 13.7 85.6 69.0 15.2 83.7 65.3 16.8 81.6 61.3 18.8 79.4 56.9 21.0 77.1 52.2 23.5 74.6
12 84.9 13.9 98.5 81.4 15.3 96.4 77.3 17.0 93.8 73.0 18.8 91.2 68.1 21.0 88.3 62.8 23.5 85.415 91.9 14.0 105.5 87.7 15.2 102.5 84.3 16.7 100.6 79.5 18.5 97.5 74.4 20.5 94.2 68.3 23.0 90.418 99.7 14.2 113.6 96.0 15.5 111.1 91.8 16.9 108.2 86.7 18.7 104.8 81.3 20.6 101.3 75.3 23.0 97.5
300V
Glycol/water mix
-10 50.1 16.8 66.2 47.6 18.7 65.4 44.7 20.7 64.4 41.8 22.9 63.4-4 62.8 16.9 79.1 59.9 18.9 78.0 56.8 21.0 76.9 53.3 23.4 75.6 49.3 26.0 74.02 78.1 17.1 94.7 74.9 19.0 93.3 71.2 21.2 91.7 67.2 23.7 90.0 62.7 26.5 88.0 57.6 29.5 85.7
Pure water
5 89.1 17.3 105.9 85.5 19.2 104.0 81.4 21.3 102.0 76.9 23.8 99.8 72.0 26.6 97.5 66.6 29.7 94.97 95.1 17.4 112.0 91.3 19.2 109.9 86.9 21.4 107.6 82.3 23.9 105.3 77.1 26.6 102.7 71.4 29.8 99.8
12 112. 17.9 129.5 107. 19.6 126.7 102.9 21.6 123.9 97.8 24.0 121.0 91.7 26.8 117.6 85.3 29.9 114.115 121.5 18.1 139.2 116.9 19.5 136.0 111.9 21.4 132.7 106.6 23.6 129.5 100.4 26.2 125.7 92.6 29.5 121.018 132.3 18.6 150.5 127.6 20.0 147.2 122.2 21.7 143.3 116.4 23.8 139.5 109.1 26.4 134.7 102.5 29.3 130.8
350V
Glycol/water mix
-10 57.0 19.3 75.5 53.7 21.4 74.1 50.5 23.8 73.1 47.0 26.4 71.9-4 71.9 19.5 90.7 68.1 21.6 88.9 64.3 24.0 87.3 60.4 26.8 85.9 56.0 29.9 84.32 90.0 19.8 109.3 85.7 21.9 106.6 81.5 24.3 104.9 76.5 27.1 102.5 71.4 30.3 100.3 65.6 33.9 97.8
Pure water
5 103.0 20.1 122.6 98.4 22.2 119.9 93.3 24.5 117.0 88.0 27.3 114.3 82.3 30.4 111.5 76.1 34.1 108.67 110.2 20.3 129.9 105.1 22.3 126.8 99.9 24.6 123.7 94.2 27.4 120.6 88.2 30.5 117.5 81.7 34.2 114.4
12 130.3 20.8 150.7 124.6 22.7 146.8 118.8 25.0 143.1 112.3 27.7 139.1 105.3 30.8 135.1 98.1 34.5 131.315 142.5 21.0 163.1 135.9 22.8 158.2 129.9 24.9 154.2 122.7 27.4 149.4 115.4 30.4 144.8 107.2 34.2 140.118 156.1 21.6 177.2 149.0 23.3 171.7 141.8 25.3 166.5 134.7 27.8 161.8 126.3 30.8 156.1 116.8 34.3 150.0
400V
Glycol/water mix
-10 64.2 22.0 85.3 60.9 24.5 84.3 57.2 27.3 83.0 52.9 30.2 81.5-4 81.4 22.3 102.8 77.6 24.7 101.3 73.5 27.6 99.8 68.6 30.7 97.8 63.3 34.2 95.72 101.9 22.6 123.9 97.5 25.0 121.7 92.7 27.8 119.5 87.5 31.0 117.2 81.4 34.6 114.4 74.8 38.5 111.4
Pure water
5 116.6 22.9 138.9 111.6 25.3 136.1 106.2 28.0 133.3 100.3 31.2 130.4 93.8 34.8 127.1 86.6 38.8 123.67 124.3 23.1 146.8 119.3 25.4 144.0 113.7 28.1 141.0 107.6 31.3 137.7 100.6 34.8 134.0 93.0 38.9 130.1
12 147.4 23.7 170.5 141.3 25.9 166.5 135.1 28.5 162.7 128.0 31.5 158.5 120.2 35.1 154.1 111.4 39.1 149.015 162.9 23.6 186.0 156.1 25.7 181.2 150.2 28.1 177.6 141.5 30.8 171.5 132.4 34.2 165.5 122.2 38.3 159.118 177.7 24.1 201.4 171.1 26.1 196.7 162.0 28.6 189.9 154.8 31.2 185.1 145.5 34.4 178.9 134.2 38.3 171.2
Cc: Gross cooling capacityPi: Compressors gross power input.Hc: Gross heating capacity
Standard conditions Glycol/water mix required.
Calculated fouling: 0.00005 m2 °C/W
14 HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIAT
cooling anD heating capacitiesDYNACIAT LG - LGP
R4
10
A
LGLGP
CONDENSER WATER OUTLET TEMPERATURE (°C)Evaporator water outlet
temperature (°C)
30 35 40 45 50 55Cc Pi Hc Cc Pi Hc Cc Pi Hc Cc Pi Hc Cc Pi Hc Cc Pi Hc
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
500V
Glycol/water mix
-10 78.8 27.3 105.0 74.4 30.3 103.4 69.9 33.7 101.9 64.5 37.5 99.9-4 99.6 27.6 126.2 94.8 30.7 124.3 89.6 34.1 122.3 83.7 38.0 119.9 77.0 42.3 117.1
2 125.2 28.1 152.4 119.8 31.1 149.8 113.8 34.5 147.0 107.3 38.4 144.1 99.9 42.8 140.7 91.3 47.7 136.5
Pure water
5 143.6 28.5 171.3 137.2 31.4 167.6 130.9 34.8 164.5 123.5 38.6 160.7 115.4 43.0 156.7 106.1 47.9 151.8
7 153.3 28.7 181.3 147.0 31.6 177.7 139.9 35.0 173.7 132.2 38.7 169.6 123.8 43.1 165.2 114.2 48.1 160.2
12 182.1 29.4 210.8 174.5 32.3 205.9 166.5 35.5 201.0 157.5 39.2 195.4 148.1 43.5 190.0 137.3 48.4 183.7
15 203.3 29.2 231.9 195.2 31.9 226.3 186.8 35.0 220.9 175.5 38.3 212.7 164.1 42.3 205.0 150.2 47.5 195.918 222.8 29.7 252.0 212.7 32.3 244.4 203.4 35.3 237.9 192.2 38.7 229.9 179.9 42.7 221.4 166.1 47.7 212.2
540V
Glycol/water mix
-10 87.5 30.2 116.5 82.6 33.7 114.7 77.3 37.5 112.9 71.7 41.8 111.1 -4 110.4 30.4 139.6 104.9 33.8 137.4 98.7 37.8 134.9 92.2 42.3 132.4 84.8 47.2 129.5
2 137.4 30.6 167.1 131.2 34.0 164.1 124.3 38.0 160.9 116.8 42.5 157.5 108.5 47.5 153.8 99.2 53.3 149.7
Pure water
5 156.2 30.9 186.3 149.5 34.3 182.7 142.1 38.1 179.0 133.7 42.6 174.7 124.5 47.6 170.1 114.6 53.3 165.4
7 166.6 31.1 196.8 159.6 34.4 192.9 151.6 38.2 188.6 143.0 42.6 184.1 133.4 47.7 179.2 123.1 53.3 174.1
12 196.0 31.9 227.1 188.1 35.0 222.2 179.4 38.6 216.8 170.2 42.8 211.6 159.1 47.7 205.2 147.4 53.4 198.7 15 212.4 32.1 243.8 203.5 34.8 237.5 194.9 38.2 232.0 184.2 42.2 225.1 173.5 46.8 218.7 160.1 52.2 210.318 230.5 32.9 262.7 223.4 35.6 258.2 212.6 38.7 249.9 201.6 42.5 242.9 189.5 47.2 235.2 174.4 52.8 225.4
600V
Glycol/water mix
-10 100.1 33.6 132.3 95.1 37.3 130.7 89.5 41.4 128.8 83.5 45.8 126.8 -4 125.6 33.9 158.3 119.8 37.7 156.1 113.5 42.1 153.7 106.4 46.8 151.0 98.7 52.0 148.0
2 156.3 34.2 189.4 149.8 38.0 186.6 142.5 42.5 183.4 134.5 47.4 179.9 125.4 52.9 175.9 115.4 59.0 171.5
Pure water
5 177.9 34.6 211.6 170.9 38.3 208.1 163.0 42.6 204.2 154.0 47.6 199.8 144.0 53.2 195.1 133.1 59.3 189.7
7 190.1 34.8 224.0 182.4 38.4 219.7 173.9 42.8 215.3 164.5 47.7 210.5 154.1 53.3 205.3 142.7 59.5 199.6
12 223.9 35.8 258.9 215.4 39.2 253.6 206.0 43.2 248.0 195.4 48.0 241.9 183.7 53.5 235.3 170.8 59.8 228.2 15 242.8 36.3 278.4 234.0 39.2 272.3 223.9 42.9 265.8 212.6 47.2 258.4 199.5 52.7 250.5 184.7 59.2 241.818 264.6 37.2 301.1 254.0 40.1 293.2 244.0 43.4 286.3 231.4 47.9 277.9 218.6 53.0 270.0 203.7 59.3 261.0
Cc: Gross cooling capacityPi: Compressors gross power input. Hc: Gross heating capacity
Standard conditions Glycol/water mix mandatory
Calculated fouling: 0.00005 m2 °C/W
15
DYN
ACIA
T
HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
cooling capacities - cooling MoDeDYNACIAT ILG
R4
10
A
ILG
CONDENSER WATER OUTLET TEMPERATURE (°C)
Evaporator water outlet
temperature (°C)
30 35 40 45 50 55
Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
kW kW kW kW kW kW kW kW kW kW kW kW
120V Water
5 28.9 7.1 27.3 7.9 25.6 8.8 23.8 9.9 21.8 11.1 19.8 12.3
7 31.0 7.1 29.2 8.0 27.4 8.9 25.5 9.9 23.4 11.1 21.4 12.3
12 36.5 7.2 34.5 8.0 32.5 8.9 30.5 9.9 28.2 11.1 25.9 12.3
15 40.0 7.3 38.0 8.0 36.0 8.9 33.5 9.9 31.0 11.1 28.7 12.3
18 43.5 7.3 41.5 8.1 39.5 8.9 37.0 9.9 34.5 11.1 32.0 12.3
150V Water
5 37.0 9.2 35.5 10.1 33.5 11.3 31.5 12.6 29.3 14.0 27.0 15.4
7 40.0 9.2 38.0 10.2 35.9 11.4 33.8 12.7 31.5 14.1 29.0 15.5
12 47.0 9.3 45.0 10.3 42.6 11.4 40.0 12.8 37.5 14.3 34.8 15.7
15 51.5 9.4 49.0 10.3 46.5 11.5 44.0 12.8 41.0 14.3 38.5 15.8
18 56.5 9.5 54.0 10.4 51.0 11.5 48.3 12.8 45.0 14.3 42.0 15.8
200V Water
5 50.2 12.3 47.4 13.8 44.2 15.6 41.0 17.6 37.4 19.9 33.8 22.2
7 53.6 12.4 50.8 13.9 47.4 15.6 44.0 17.6 40.4 19.9 36.8 22.2
12 63.7 12.5 60.2 13.9 56.8 15.6 52.8 17.6 48.6 19.9 44.6 22.2
15 70.0 12.5 66.0 14.0 62.5 15.6 58.4 17.6 54.0 19.9 49.6 22.2
18 76.0 12.6 72.0 14.0 68.0 15.7 64.0 17.7 59.6 19.9 55.0 22.2
240V Water
5 58.6 14.2 55.4 15.8 51.9 17.6 48.2 19.8 44.2 22.2 40.4 24.6
7 62.0 14.2 59.1 15.8 55.6 17.6 51.8 19.8 47.6 22.2 43.4 24.6
12 73.6 14.4 70.0 16.0 66.0 17.8 62.0 19.8 57.2 22.2 52.4 24.6
15 81.0 14.4 77.0 16.0 73.0 17.8 68.3 19.8 63.0 22.2 58.2 24.4
18 88.0 14.6 84.0 16.0 80.0 17.8 75.2 19.8 69.6 22.2 64.0 24.4
300V Water
5 76.0 18.2 72.0 20.2 68.0 22.4 64.0 25.0 59.4 28.0 55.0 30.6
7 80.7 18.2 77.0 20.2 73.0 22.6 68.7 25.2 64.0 28.0 59.0 30.8
12 95.0 18.6 91.0 20.4 86.0 22.8 81.0 25.4 75.6 28.4 70.7 31.2
15 104.0 18.8 100.0 20.6 95.0 22.8 89.2 25.4 83.7 28.4 78.0 31.4
18 113.5 19.0 109.0 20.8 104.0 23.0 98.0 25.6 92.0 28.6 86.0 31.4
Cc: Gross cooling capacityPi: Compressors gross power input.
Standard conditions Glycol/water mix mandatory
Calculated fouling: 0.00005 m2 °C/W
16 HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIAT
heating capacities - heating MoDeDYNACIAT ILG
R4
10
A
ILG
CONDENSER WATER OUTLET TEMPERATURE (°C)
Evaporator water outlet
temperature (°C)
30 35 40 45 50 55Hc Pi Hc Pi Hc Pi Hc Pi Hc Pi Hc Pi
kW kW kW kW kW kW kW kW kW kW kW kW
120V
Glycol/water mix
-8 26.9 6.5 26.4 7.3 25.7 8.3 24.8 9.1-4 30.2 6.5 29.5 7.2 28.8 8.2 28.0 9.1 27.1 10.3
2 35.9 6.6 35.2 7.3 34.3 8.1 33.4 9.2 32.6 10.3 31.2 11.9
Pure water
5 39.9 6.6 38.9 7.3 38.0 8.1 36.9 9.1 35.9 10.2 34.8 11.4
7 42.2 6.6 41.1 7.3 40.1 8.2 38.9 9.1 37.6 10.2 36.5 11.4
10 45.6 6.7 44.5 7.4 43.4 8.2 42.1 9.1 40.8 10.1 39.3 11.4
12 48.5 6.8 47.3 7.5 46.0 8.2 44.6 9.1 43.1 10.1 41.7 11.4
150V
Glycol/water mix
-8 34.6 8.2 34.0 9.2 33.5 10.3 32.7 11.4-4 38.7 8.3 38.0 9.2 37.4 10.4 36.6 11.5 35.9 12.9
2 46.3 8.4 45.3 9.3 44.5 10.5 43.8 11.7 42.8 13.0 41.5 14.5
Pure water
5 51.4 8.5 50.4 9.4 49.4 10.5 48.4 11.7 47.0 13.1 45.9 14.8
7 54.2 8.6 53.2 9,9 52.2 10.5 50.8 11.7 49.5 13.1 48.5 14.8
10 58.8 8.7 57.6 9.6 56.3 10.6 54.8 11.8 53.3 13.2 51.7 14.812 62.4 8.9 61.2 9.7 59.7 10.6 58.1 11.8 56.6 13.1 54.8 14.8
200V
Glycol/water mix
-8 46.4 11.1 45.0 12.7 44.1 14.4 43.3 16.3-4 52.3 11.1 50.9 12.6 50.2 14.3 49.1 16.2 47.7 18.2
2 62.3 11.3 60.9 12.7 59.6 14.3 58.0 16.1 56.1 18.0 54.7 20.6
Pure water
5 69.6 11.4 67.9 12.8 66.2 14.3 64.5 16.0 62.8 18.2 61.1 20.2
7 73.1 11.5 71.3 12.8 69.6 14.3 67.9 16.1 66.0 18.2 64.1 20.1
10 79.5 11.6 77.8 12.9 75.4 14.4 73.5 16.2 71.0 18.2 68.7 20.012 83.7 11.7 82.2 13.0 80.2 14.4 78.0 16.1 75.4 18.1 73.0 19.9
240V
Glycol/water mix
-8 53.1 13.1 52.3 14.6 51.7 16.6 50.5 18.6-4 59.8 13.0 58.6 14.6 57.8 16.5 56.5 18.6 55.4 20.9
2 71.3 13.2 69.9 14.7 68.4 16.5 66.8 18.5 65.6 20.8 63.8 23.3
Pure water
5 80.8 13.2 78.8 14.6 76.8 16.3 74.3 18.2 72.1 20.4 69.9 22.9
7 85.0 13.3 83.2 14.7 81.1 16.3 78.6 18.1 76.1 20.4 73.6 22.8
10 92.4 13.5 89.6 14.9 87.7 16.4 85.5 18.2 82.7 20.3 79.6 22.812 98.2 13.7 96.1 15.0 93.5 16.5 90.9 18.2 87.3 20.3 84.2 22.8
300V
Glycol/water mix
-8 69.1 16.5 67.7 18.3 66.4 20.6 65.1 23.0-4 77.7 16.7 76.6 18.4 75.0 20.7 73.7 23.2 72.2 25.7
2 92.6 16.9 91.1 18.6 89.5 20.8 87.8 23.4 85.5 26.0 83.1 28.9
Pure water
5 103.3 17.0 101.4 18.8 99.4 20.9 97.2 23.3 94.5 26.0 91.5 29.7
7 107.9 17.1 106.3 18.8 104.1 20.9 101.5 23.3 98.9 26.1 95.1 29.8
10 117.2 17.4 114.6 19.1 112.1 21.1 109.1 23.4 106.2 26.2 101.6 29.912 124.1 17.5 121.3 19.3 118.6 21.3 115.7 23.4 112.5 26.3 107.7 29.9
Hc: Gross heating capacityPi: Compressor gross power input.
Standard conditions Glycol/water mix required.
Calculated fouling: 0.00005 m2 °C/W
17
DYN
ACIA
T
HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
water pressUre DropLG - LGP 120 - 600In the evaporator (use prohibited beyond these limits)EVAPORATOR
kPa = bar x 100
bar = mWC x 0.0981
kg/cm2 = bar x 1.0197
Pound per square inch (psi) = bar x 14.504
Inch (in) = mm x 0.0394
Foot (ft) = mm x 0.0032808
Pound (lb) = kg x 2.205
Cubic feet per minute (cfm) = m3/h x 0.5885
US gallons = m3 x 264.2
UK gallons = m3 x 220
n Unit conversion formulae
Filter (mandatory) on the evaporator side
3 4 5 6 7 8 9 10 20 30 40 50 60 70 800.80.9
1
2
3
4
5
6
7
89
10
16
540
500
600
400
350
300
240
200
150
120
3 4 5 6 7 8 9 10 20 30 40 50 60 70 800.1
0.2
0.3
0.4
0.50.6
0.8
1
2
3
4
56
8
10
18
120 -
150
200-240
300-350
400-500
540-600
Do not extrapolate the curves. Always stay within minimum and maximum flow rate values.
Water flow rate m3/h
Water flow rate m3/h
Wat
er p
ress
ure
drop
(mW
C)
Wat
er p
ress
ure
drop
(mW
C)
18 HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIAT
CONDENSER
3 4 5 6 7 8 9 10 15 20 25 30 40 500.80.9
1
2
3
4
5
6
7
89
10
16
540
500
600
400
350
300
240
200
150
120
water pressUre DropLG - LGP 120 - 600In the condenser (use prohibited beyond these limits)
n Unit conversion formulae
3 4 5 6 7 8 9 10 15 20 25 30 40 500.1
0.2
0.3
0.4
0.50.60.70.80.9
1
2
3
4
56789
1012
120-150-2
00-240
300-350
400-500
540-600
Filter (mandatory) on the condenser side
Do not extrapolate the curves. Always stay within minimum and maximum flow rate values.
kPa = bar x 100
bar = mWC x 0.0981
kg/cm2 = bar x 1.0197
Pound per square inch (psi) = bar x 14.504
Inch (in) = mm x 0.0394
Foot (ft) = mm x 0.0032808
Pound (lb) = kg x 2.205
Cubic feet per minute (cfm) = m3/h x 0.5885
US gallons = m3 x 264.2
UK gallons = m3 x 220
Water flow rate m3/h
Water flow rate m3/h
Wat
er p
ress
ure
drop
(mW
C)
Wat
er p
ress
ure
drop
(mW
C)
19
DYN
ACIA
T
HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
water pressUre DropILG 120 - 300In the evaporator (use prohibited beyond these limits) INDOOR AND OUTDOOR CIRCUITS
n Unit conversion formulae
Filter - ILG (mandatory)
3 4 5 6 7 8 9 10 15 20 25 30 401.5
2
3
4
5
6
7
8
910
20
25
240 30
0
120 15
0200
300
200
150
120
240
Water flow rate m3/h
Water flow rate m3/h
Wat
er p
ress
ure
drop
(mW
C)
Wat
er p
ress
ure
drop
(mW
C)
3 4 5 6 7 8 9 10 15 20 25 30 400.1
0.2
0.3
0.4
0.50.60.70.80.9
1
2
3
4
56789
1012
Do not extrapolate the curves. Always stay within minimum and maximum flow rate values.
kPa = bar x 100
bar = mWC x 0.0981
kg/cm2 = bar x 1.0197
Pound per square inch (psi) = bar x 14.504
Inch (in) = mm x 0.0394
Foot (ft) = mm x 0.0032808
Pound (lb) = kg x 2.205
Cubic feet per minute (cfm) = m3/h x 0.5885
US gallons = m3 x 264.2
UK gallons = m3 x 220
20 HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIAT
20
DiMensionsDYNACIAT LG - LGP 120 - 600
LG – LGP 120 150 200 240 300 350 400 500 540 600Figure 1 2 3
Sleeves/Male PN16 flangesa - b
G 1” 1/2 G 2” G 2” 1/2 DN 80c - dA 127 126 127
Weight (kg)Empty 230 300 385 390 590 620 665 735 930 1125
In operation 240 312 400 406 617 650 703 780 990 1190
a: Condenser cold water outlet (LG)Condenser hot water outlet (LGP)
b: Condenser cold water inlet (LG)Condenser hot water inlet (LGP)
c: Chilled water outletd: Chilled water inlete: Power supply
FIG. 1 FIG. 2 FIG. 3
21
DYN
ACIA
T
HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DiMensionsDYNACIAT ILG 120 - 300
169 150 150 150169 461 140 280 280
95
321
a : Sortie eau circuit intérieur
c : Sortie eau circuit extérieur
b : Entrée eau circuit intérieur
d : Entrée eau circuit extérieur
e : Alimentation électrique
A
ILG 120 150 200 240 300Figure 1 2
Sleeves (Male)
a - bG 1” 1/2 G 2”
c - d
A 127 126
Weight (kg)Empty 226 289 379 452 595
In operation 237 301 394 468 622
FIG. 1 FIG. 2
a: Indoor circuit water outletb: Indoor circuit water inletc: Outdoor circuit water outletd: Outdoor circuit water inlete: Power supply
22 HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIATDiMensionsHydraulic module Aquatherm module
MHG 40 41 42 43 46
Hydraulic connection a - b Ø 1”1/2 - 2” - 2”1/2
WeightEmpty kg 285
In operation kg 535
MA 29 38 51 59 77Hydraulic connection
a - b - c - d Ø G 1”1/2
WeightEmpty kg 235 357 372
In operation kg 247 385 412
788
a b
798
883
551
798
1201
1347
5 5
145
118,5 118,5 904,5
178873
873
514
5
118155 192 212118873
175105
555 5
883798
904,5
a b c d
a: Outdoor circuit water inletb: Outdoor circuit water outletc: Indoor circuit water inletd: Indoor circuit water outlete: Power supply
a: Water outletb: Water inlete: Power supply
23
DYN
ACIA
T
HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
scheMatic installation DiagraM
LG - ILG MA MHG
MHG MA LG
Cooling only (LG series) or heating/cooling (ILG series)
Cooling only or heating only operation with hydraulic reversibility (LG series)
Note: the schematic diagrams herein are provided for information only. Under no circumstances do they constitute actual installation diagrams.
24 HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIAT
n Cooling installation with drycooler (LG series)
scheMatic installation DiagraM
Note: the schematic diagrams herein are provided for information only. Under no circumstances do they constitute actual installation diagrams.
chilled water circuitrecovery water circuitwater fillingexpansion vesselcontrol valvedrainshut-off valve
air bleed valvewater filter (mandatory)water hoses (mandatory)thermowellwell dischargehydraulic changeover valvecleanable heat exchangersafety valvetemperature controller
25
DYN
ACIA
T
HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
scheMatic installation DiagraM with well or groUnD water anD hyDraUlic MoDUle Heating/cooling operation (ILG series) or heating only operation (LG series)
VENTILO-CONVECTEURS
MHG MA
Note: the schematic diagrams herein are provided for information only. Under no circumstances do they constitute actual installation diagrams.
UNDERFLOOR HEATING SYSTEM (COOLING) FAN COIL UNITSand / or
Room thermostat
Floor
DUO MODULE
Outdoor sensor
Shut-off valvesThermometer pockets
Control valves
Solenoid valve
External water network (pump with booster or
municipal water)
Well or
ground water
(Place a screen filter upstream of the well pump if the latter is not suitable
for unfiltered water)
Discharge SUMMER
Hydraulic module Aquatherm module
WINTER
Strainer valve
Closed in summer
CONTROLLER
Possible space heater
26 HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIATscheMatic geotherMal installation with hyDraUlic MoDUle DiagraMHeating/cooling operation (ILG series) or heating only operation (LG series)
MHG
A A
VENTILO-CONVECTEURS
Note: the schematic diagrams herein are provided for information only. Under no circumstances do they constitute actual installation diagrams.
UNDERFLOOR HEATING/COOLING SYSTEM FAN COIL UNITSand / or
Outdoor sensor
Room thermostat
Floor
DUO MODULE
Safety valve + pressure gauge
Possible space heater Flexible sleeves
Filling
Expansion vessel
Screen filter
Supply circuit
Return circuit
Filler materialGeometric sensor
Shut-off valves
Thermometer pocketsControl valves
Buried glycol solution loop
Pump
CONTROLLER
Hydraulic module
27
DYN
ACIA
T
HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
Dynaciat lg - lgp - ilg series Installation recommendationsn Water quality criteria to be respectedWarning: It is essential that an 800-micron water filter be placed on the unit's water inlet during installation.The quality of the water used has a direct impact on the correct operation of the unit and its service life. This is particularly true if the water used clogs or corrodes components or promotes the growth of algae or micro-organisms.The water must be tested to determine whether it is suitable for the unit and whether chemical treatment will suffice to make it of acceptable quality and if a water softening/demineralising system should be installed.The results of the analysis must confirm whether the site's water is compatible with the various materials used on the CIAT unit's circuit: - 99.9% copper tubes brazed with copper and silver,- threaded bronze couplings or flat steel flanges, depending on the unit model,- plate heat exchangers and AISI 316/DIN 1.4401 stainless steel connections brazed with copper and silver.Warning: failure to follow these instructions will result in the immediate voiding of the unit warranty.
n Lifting and handling operationsThe strictest safety precautions must be taken when lifting and handling the unit.Always follow the lifting diagram on the unit and in the instruction manual. Before attempting to lift the unit, make sure the path leading to its intended location is free from obstacles.Always keep the unit vertical when moving it. Never tip it or lie it on its side.
n Choosing a location for the unitDYNACIAT units are designed for installation in a machine room.Precautions should be taken to protect them from freezing temperatures.Special attention should be paid to ensure sufficient free space (including at the top) to allow maintenance.The unit must be placed on a perfectly level, fireproof surface strong enough to support it when ready for operation.Noise pollution from auxiliary equipment such as pumps should be studied thoroughly.Depending on the room and its structure, potential noise transmission routes should be studied, with assistance from an acoustical engineer if necessary, before the unit is installed.Flexible couplings MUST be placed over pipes (available as options).
n Machine room ventilationIn accordance with the regulations in force in the place in which the machine is to be installed, the machine room must comply with certain ventilation rules for fresh air to ensure there is no risk of discomfort or hazard in the event of a refrigerant leak.
n Fitting accessories supplied separately A number of optional accessories may be delivered separately and installed on the unit on site.You must follow the instructions in the manual.
n Electrical connections You must follow the instructions in the manual and the wiring diagrams on the unit. The unit must be connected according to industry standards and the norms and regulations in force.Electrical connections to be made on site:. unit's electrical supply,. outdoor operation authorisation (optional),. information feedback (optional).It should be noted that the unit's electrical system is not protected against lightning strikes.Therefore components to protect against transient voltage surges must be installed on the system and inside the electrical supply unit.
28 HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIATn Pipe connections You must follow the instructions in the user manual.All pipes must be correctly aligned and slope toward the system's drain valve.Pipes must be installed to allow sufficient access to the panels and fitted with heat insulation.Pipe mountings and clamps must be separate to avoid vibrations and pressure on the unit. Water shut-off and control valves must be fitted when the unit is installed.- Pipe connections to be made on site:
. system water supply with pressure-reducing valve,
. evaporator, condenser and drain,- Accessories essential to any hydraulic system must also be installed, such as:
- a thermostatically-controlled valve for controlling the flow rate of cooling water placed at the condenser water inlet or outlet.. water expansion vessel,. drain nozzles at pipe low points,. exchanger shut-off valves equipped with filters,. air vents at pipe high points,- check the system's water capacity (install a buffer water tank if necessary),. flexible couplings on exchanger inlets and outlets, . thermometers on each water inlet and outlet to allow all the necessary checks during start-up and maintenance.
N.B.:- Pressure in the water circuits below 4.0 bar.- Place the expansion vessel before the pump.- Do not place any valves on the expansion vessel.- Make sure the water circulation pumps are placed directly at the exchanger inlets.- Make sure the pressure of the water drawn in by the circulation pumps is greater than or equal to the required minimum NPSH, particularly if the water circuits are "open".- Test the water quality in accordance with the relevant technical requirements.- Take the necessary precautions to protect the unit and hydraulic system from freezing temperatures (e.g. allow for the possibility of draining the unit). If glycol is added to prevent freezing, check its type and concentration beforehand.- Before making any final hydraulic connections, flush the pipes with clean water to remove any debris in the network.
n CommissioningDYNACIAT units must be commissioned by CIAT or a CIAT-approved firm.You must follow the instructions in the manual.Partial list of precommissioning checks:- Correct positioning of unit,- Power supply protections,- Phases and direction of rotation,- Wiring connections on unit,- Direction of water flow in unit,- Cleanliness of water circuit,- Adjusting water flow rate to specified value,- Pressure in the refrigeration circuit,- Direction of rotation of compressors,- Water pressure drops and flow rates,- Operating readings.
n Maintenance operationsSpecific preventive maintenance operations must be carried out regularly on the unit by CIAT-approved firms.The operating parameters are read and noted on a "CHECK LIST" form to be returned to CIAT.It is essential to comply with the Instructions, Installation, Operation, Commissioning and Maintenance Manual.You must take out a maintenance contract with a CIAT-approved refrigeration equipment specialist. Such a contract is required even during the warranty period.
29
DYN
ACIA
T
HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
Drycoolers
n CIAT OPERA series drycoolers are compatible with DYNACIAT LG water-cooled condenser units
n Available in a wide range of sizes and with 6 ventilation speeds, OPERA can be adapted to the acoustic constraints or space restrictions of each site.
30 HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
DYNACIATconnect2 control
USER-FRIENDLY INTERFACE CONSOLE- LCD display (4 lines of 24 characters each) - Pressure and temperature readings- Diagnosis of operation and fault states- Master/slave control of two machines in parallel- Fault memory management- Pump management- Remote control- Time schedules
Smart CIATControl
MULTICONNECT MULTI-UNIT MANAGEMENT (OPTION)Main functions available:- Management of up to 8 units on a single water loop- Management in cooling mode (water chiller) or heating mode
(heat pump)- Management of chilled-water or hot-water pumps- Centralised management of a backup unit- Machine load shedding- System time programming- Energy storage mode management- Unit running time balancing
Communication with Hysys system (generator, transmitter, air handling unit), controlled by an Easy CIATControl or Smart CIATControl touch tablet.
•Logging of consumption data and temperatures•Optimal Water®: optimisation of producer performance based on
building requirements•Optimal Stop and Start: optimisation of the building restart time
POTENTIAL-FREE (DRY) CONTACTS AVAILABLE AS STANDARD Inputs: - Pump and machine automatic operation control - Selection of setpoints 1 / 2 - Setpoint adjustable by 4-20 mA signal - Heating/cooling mode selection - Compressor load shedding
Outlets: - General fault reporting - Fault reporting on each circuit - Pump controlAdditional outlets available as options: - Water flow fault - Frost protection fault - Pump fault - Compressor lubrication fault - Fan fault - Low and high pressure fault - Compressor overheating fault - Discharge temperature fault - Compressor operating status
OUTLET AS STANDARD- Open ModBus-JBUS RS 485 protocol (standard)- ModBus-ETHERNET TC/IP protocol (standard)- LONWORKS protocol (option)- BACNET protocol (option)
PRODUCT FUNCTIONALITY
CIAT SYSTEM FUNCTIONALITY
Via dry contact
Via BUS communication
COMMUNICATIONCustomer CMS
Power’Control
Communication with CIAT Energy Pool controlled by Power’Control.
Integrated Power’Control:•Energyoptimisationofrefrigerationandheatingusingseveral
generators, •Managesfreecoolingcapacity•Usesheatrecoverytosupplydomestichotwater.
31
DYN
ACIA
T
HEAT PUMPS - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.538 A
Water chillersHeat pumps
This document is non-contractual. As part of its policy of continual product improvement, CIAT reserves the right to make any technical modification it feels appropriate without prior notification.
Head office Avenue Jean Falconnier - B.P. 1401350 - Culoz - FranceTel.: +33 (0)4 79 42 42 42Fax: +33 (0)4 79 42 42 [email protected] - www.ciat.com
Compagnie Industrielle d’Applications Thermiques - S.A. with a registered capital of 26 728 480 € - R.C.S. Bourg-en-Bresse B 545 620 114
CIAT ServiceTel. : 08 11 65 98 98 (0,15 € / mn)Fax : 08 26 10 13 63 (0,15 € / mn)