Dynamic Exit Signage
Transcript
Page 1: Dynamic Exit Signage - CleverEVAC · RU RL RD R. 8 9 SYSTEM INTERFACE AND DYNAMIC SIGN / SOUNDER OPERATION Activation of the Volt Free (VF) outputs of the Fire Relay Interface is

Dynamic ExitSignage

Page 2: Dynamic Exit Signage - CleverEVAC · RU RL RD R. 8 9 SYSTEM INTERFACE AND DYNAMIC SIGN / SOUNDER OPERATION Activation of the Volt Free (VF) outputs of the Fire Relay Interface is

32

A New Path Forward for Exit Signage • Dynamic EXIT signage

• Increased visibility of EXIT signs

• Locatable sound technology

• Negative enforcement options

• Zoneworks® XT automatic testing

Introducing CleverEVAC

Introducing CleverEVAC

Dynamic Emergency SignageA new concept in emergency signage, which I call the ‘Active Dynamic Signage System (ADSS)’, extends the idea of smart buildings to emergency wayfinding, with a new generation of advanced emergency exit signs. Traditional emergency signs are not always noticed in an emergency and cannot adapt to the circumstances of an incident or a changing threat environment, even if they are directing people into potential danger. The ADSS is intended to save lives by addressing these shortcomings - attracting attention when signs need to be conspicuous, redirecting people during an evolving emergency, and automatically identifying, not just an exit route, but the optimal exit route.

The ADSS combines three key safety innovations. Flashing and running green LED lights within the arrow of emergency exit signs make people more likely to notice them and hence spend less time wayfinding. A large illuminated ‘red cross’ through the sign can deter use of exit routes compromised by an incident. And the system can be expanded to identify optimal evacuation routes by responding ‘intelligently’ to an evolving emergency using up-to-the-minute situational awareness and advanced faster than real-time evacuation simulations conducted during the incident itself.

These advances bring the humble emergency exit sign into the 21st century.

Prof Ed Galea BSc, Dip.Ed, PhD, CMath, FIMA, CEng, FIFireECAA Professor of Mathematical ModellingDirector Fire Safety Engineering Group University of Greenwich

Clevertronics is a global innovator in Exit and Emergency lighting, as well as being the market leader in Australia and New Zealand.

Leading the product innovation has been a constant focus, with a drive to provide products and systems that improve the way Exit and Emergency lighting are designed, installed and managed.

Some of these innovations include the introduction of LEDs to emergency lights, lithium battery technology, and CleverSparky,® a mobile, cloud-based compliance management app for smartphones. Zoneworks® XT is a valuable compliance tool for building owners and operators, taking the manual labour element out of the testing process for emergency and exit lighting installations, and centralising the site’s full database, fault reporting, and log-booking.

CleverEVAC is a system and suite of dynamic EXIT signs that provide increased visibility, audible cues, and negative enforcement options. The work conducted by the Fire Safety Engineering Group (FSEG) at the University of Greenwich led to the development of the CleverEVAC Dynamic Signage product range. The FSEG, and also the University of Leeds have provided the required research, experience and trials of dynamic EXIT signage and locatable sound technology. CleverEVAC is a tool for Fire Safety Engineers to consider for use in fire engineered / performance solutions and also in designs where an increased visibility EXIT sign is preferred.

An extensive library of research and trial data is available relating to CleverEVAC technology for both audible technology of Sound Escape™ and visual enhancements of Dynamic Signage.

Page 3: Dynamic Exit Signage - CleverEVAC · RU RL RD R. 8 9 SYSTEM INTERFACE AND DYNAMIC SIGN / SOUNDER OPERATION Activation of the Volt Free (VF) outputs of the Fire Relay Interface is

54

Original research by the FSEG found that people often didn’t notice static exit signage, whereas significantly more people noticed dynamic exit signage.

This led to the development of the CleverEVAC Dynamic GREEN exit sign to provide an increased visibility of the sign.

Dynamic GREEN is available with a variety of directional options based on your needs. The Dynamic GREEN mode is triggered either by a 24VDC or voltage free open/close signal from the fire detection or other building safety system.

STANDARD WITH SOUNDESCAPE™

DYGC-CP-RR-ZWDYGC-CP-RL-ZWDYGC-CP-RU-ZWDYGC-CP-RD-ZWDYGC-CP-R-ZW

DYGC-CP-RR-SND-ZWDYGC-CP-RL-SND-ZWDYGC-CP-RU-SND-ZWDYGC-CP-RD-SND-ZWDYGC-CP-R-SND-ZW

DYGL-CP-RR-ZWDYGL-CP-RL-ZWDYGL-CP-RU-ZWDYGL-CP-RD-ZWDYGL-CP-R-ZW

DYGL-CP-RR-SND-ZWDYGL-CP-RL-SND-ZWDYGL-CP-RU-SND-ZWDYGL-CP-RD-SND-ZWDYGL-CP-R-SND-ZW

CleverEVAC Dynamic RED X signs can be interfaced to the building’s fire detection or other safety system, as designed by a fire safety engineer.

CleverEVAC Dynamic RED X sign can display a red cross, alerting those evacuating to seek an alternative exit. Using a red cross through the sign has been demonstrated by FSEG research to be effective in conveying negative enforcement.

The Dynamic RED X mode is triggered either by a 24VDC or voltage free open/close signal from the fire detection or other building safety system.

STANDARD WITH SOUNDESCAPE™

DYRC-CP-RR-ZWDYRC-CP-RL-ZWDYRC-CP-RU-ZWDYRC-CP-RD-ZWDYRC-CP-R-ZW

DYRC-CP-RR-SND-ZWDYRC-CP-RL-SND-ZWDYRC-CP-RU-SND-ZWDYRC-CP-RD-SND-ZWDYRC-CP-R-SND-ZW

DYRL-CP-RR-ZWDYRL-CP-RL-ZWDYRL-CP-RU-ZWDYRL-CP-RD-ZWDYRL-CP-R-ZW

DYRL-CP-RR-SND-ZWDYRL-CP-RL-SND-ZWDYRL-CP-RU-SND-ZWDYRL-CP-RD-SND-ZWDYRL-CP-R-SND-ZW

CleverEVAC Dynamic RED X

CleverEVAC Dynamic GREEN

CleverEVAC Dynamic Red X RangeCleverEVAC Dynamic Green Range

Page 4: Dynamic Exit Signage - CleverEVAC · RU RL RD R. 8 9 SYSTEM INTERFACE AND DYNAMIC SIGN / SOUNDER OPERATION Activation of the Volt Free (VF) outputs of the Fire Relay Interface is

76

Combining audible locatable sounds including announcements such as ‘Exit Here’, with the increased visibility of dynamic exit signage, can improve the evacuation outcome, especially in conditions of reduced visibility. The Sound Escape™ option is available and fits perfectly into all dynamic exit sign products.

To ensure Fire Safety Engineers can select their directional preference a variety of options have been established:

G-GREENR-RED

C-LPL-L10

DIRECTIONALOPTIONS

SOUND ESCAPE

ZONEWORKS®

DYGC-CP-RR-SND-ZW

escapesound

RUNNING MAN RIGHT RUNNING MAN LEFT

RUNNING MAN UP RUNNING MAN DOWN

RUNNING MAN

Zoneworks® XT is a real-time, automatic monitoring & testing system for CleverEVAC Exit & Emergency luminaires to assist in meeting mandated testing and reporting requirements under AS2293.1.

Performance solutions can be designed using instruction from the Fire Safety Engineering report that determines what needs to occur within the evacuation system based on events, and the required action, including activating CleverEVAC Dynamic signage. Advanced building management systems can specifically activate a predetermined function within a CleverEVAC fitting or fittings making a “scene of events”. This development can include fire and evacuation modelling systems such as SMARTFIRE® and building EXODUS® evacuation simulation software, and can determine which event and subsequent action can be executed based on inputs from the building’s safety systems, and these advanced modelling systems.

NOTE: Zoneworks® does not test the interface from the fire detection or other system. Testing method of the interface needs to be documented by the fire engineer.

The future of CleverEVAC will allow for the intelligent control of fittings through advanced building management, simulation and modelling software systems.

Zoneworks XTTesting

Soundescape™

Directional Options

CleverEVAC Part Numbers

Zoneworks XT TestingCleverEVAC Options

RR

RU

RL

RD

R

Page 5: Dynamic Exit Signage - CleverEVAC · RU RL RD R. 8 9 SYSTEM INTERFACE AND DYNAMIC SIGN / SOUNDER OPERATION Activation of the Volt Free (VF) outputs of the Fire Relay Interface is

98

SYSTEM INTERFACE AND DYNAMIC SIGN / SOUNDER OPERATION Activation of the Volt Free (VF) outputs of the Fire Relay Interface is triggered by the Fire System (e.g. detector alarm).

Dynamic RED X signs will receive a direct VF input from the fire system.

Dynamic GREEN signs can be triggered either by a volt free input to the ZW system via the ZXTELC units (as shown) or receive a direct VF input from the Fire System (also shown). Consideration should be given to the critical nature of the Dynamic GREEN (with/without SoundEscape™) activation to determine if the hard-wired connection is a necessary redundancy, in addition to the ZW System activation (hence the dotted lines).

The required actions are determined by the Building’s Fire System matrix.

The methodology depicted below has the Fire Relay Interface and ZXTELC in the same fire zone. This allows for zonal activation of signs without reliance on network infrastructure spanning multiple fire zones. The Fire Relay Interface is shown either connected directly to Dynamic Signs within the same fire zone and to the ZXTEC also in the same fire zone. Further consideration should be given to a UPS backup for the ZXTELC to maintain functions in the event of a supply failure.

SYSTEM OPERATIONThe Emergency Lighting Functions,including the Dynamic RED X and Dynamic GREEN signs in activated mode, are tested by the Zoneworks® System. This is a power-fail-simulation test for the 90min or 120min duration.

The fire system input triggers and subsequent activation of the Dynamic GREEN and Dynamic RED X signs must be tested, and visually inspected for correct operation, in accordance with the maintenance schedule (this may be part of a Fire Engineered Solution). Each input trigger, from the fire system, should be operated and the resulting actions inspected to confirm correct operation in accordance with the maintenance schedule.

CleverEVAC Interface Schematic System Interface and Dynamic Sign Sounder Operation

ZONEWORKS® SERVER

ETHERNET SWITCH

ETHERNET SWITCH

ETHERNET SWITCH

Ethernet Structured Cabling between the network port and the Ethernet switch.

RJ45 Network Port

Ethernet Patch Lead (RJ-45, Cat5 min) NOTE: Any volt free (VF) input direct to the dynamic signs can be 24V DC.

NOTE: Inputs to the ZXTELC can only be volt free.

Additional Zoneworks® XT

Controllers located and servicing other AREAS/FIRE ZONES of the building connected to the Integrated Ethernet Network directly to Distribution Boards.

Zoneworks XT CleverEvac Interface Schematic

Document Issue: 1.2Document Name: Zoneworks XT CleverEvac Interface Schematic25/01/2018

3-Phase Coupling Device

L1 L2 L3

Distribution Board

SD

Med

ia C

onve

rter

LIN

KPW

RLI

NK

5VD

C. 1

A_

__ _

_ +

UP

LIN

K

RX

TX

Com3

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Ethe

rnet

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Zoneworks Server

Ethernet Switch

Ethernet switch

SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TXSD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Eth

erne

t

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Additional Zoneworks XT Controllers located and servicing other AREAS/FIRE ZONES of the building connected to the Integrated Ethernet Network directly to Distribution Boards.

Ethernet Switch

RJ45 Network Port Ethernet Patch Lead (RJ-45, Cat5 min)

Ethernet Structured Cabling between the network port and the Ethernet switch

Powerline Signal Coupling link

3-Phase MCB

FIRE ZONE/AREA

ZXTELC

Fire Panel

Red cable = fire loop

SYSTEM INTERFACE AND DYNAMIC SIGN/SOUNDER OPERATIONActivation of the Volt Free (VF) outputs of the Fire Relay Interface is triggered by the Fire System (e.g. detector alarm).

Dynamic RED X signs will receive a direct VF input from the fire system.

Dynamic Green signs can be triggered either by a volt free input to the ZW system via the ZXTELC units (as shown) or receive a direct VF input from the Fire System (also shown). Consideration should be given to the critical nature of the Dynamic Green (with/without SoundEscape) activation to determine if the hard-wired connection is a necessary redundancy, in addition to the ZW System activation (hence the dotted lines).

The required actions are determined by the Building’s Fire System matrix.

The methodology depicted below has the Fire Relay Interface and ZXTELC in the same fire zone. This allows for zonal activation of signs without reliance on network infrastructure spanning multiple fire zones. The Fire Relay Interface is shown either connected directly to Dynamic Signs within the same fire zone and to the ZXTEC also in the same fire zone. Further consideration should be given to a UPS backup for the ZXTELC to maintain functions in the event of a supply failure.

ATU = Automatic test unit with, sensing of supply, key-switch test start and automatic reset, part number, EATUKS.

CATU GOG EXIT Sign (with SoundEscape)GOG EXIT Sign ROG EXIT Sign

Fire Relay InterfaceVOLT FREE Outputs

Volt Free Fire alarm input trigger to the ZXTELC – the resulting actions are to be defined by the Building Fire Matrix. This input will be used to trigger GOG EXIT Signs only via the ZW System (if this approach is selected).

Other EM lights

SYSTEM OPERATIONThe Emergency Lighting Functions, including the Dynamic RED X and Dynamic Green signs in activated mode, are tested by the Zoneworks System. This is a power-fail-simulation test for the 90min or 120min duration.

The fire system input triggers and subsequent activation of the Dynamic Green and Dynamic RED X signs must be tested, and visually inspected for correct operation, in accordance with the maintenance schedule (this may be part of a Fire Engineered Solution). Each input trigger, from the fire system, should be operated and the resulting actions inspected to confirm correct operation in accordance with the maintenance schedule.

Consideration should be given to a UPS backup for the ZXTELC.

NOTE: Any volt free (VF) input direct to the dynamic signs can be 24V DC.

NOTE: Inputs to the ZXTELC can only be volt free.

Clevertronics Pty Ltd is a vendor of CleverEVAC products. It is not a fire engineer or designer. It does not purport to recommend its products for use in any particular application or to achieve any particular outcome. Purchasers and users of its products must take their own steps to ensure compliance with statutory requirements, safe practice and suitable application of the products.

Zoneworks XT CleverEvac Interface Schematic

Document Issue: 1.2Document Name: Zoneworks XT CleverEvac Interface Schematic25/01/2018

3-Phase Coupling Device

L1 L2 L3

Distribution Board

SD

Med

ia C

onve

rter

LIN

KPW

RLI

NK

5VD

C. 1

A_

__ _

_ +

UP

LIN

K

RX

TX

Com3

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Ethe

rnet

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Zoneworks Server

Ethernet Switch

Ethernet switch

SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TXSD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Eth

erne

t

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Additional Zoneworks XT Controllers located and servicing other AREAS/FIRE ZONES of the building connected to the Integrated Ethernet Network directly to Distribution Boards.

Ethernet Switch

RJ45 Network Port Ethernet Patch Lead (RJ-45, Cat5 min)

Ethernet Structured Cabling between the network port and the Ethernet switch

Powerline Signal Coupling link

3-Phase MCB

FIRE ZONE/AREA

ZXTELC

Fire Panel

Red cable = fire loop

SYSTEM INTERFACE AND DYNAMIC SIGN/SOUNDER OPERATIONActivation of the Volt Free (VF) outputs of the Fire Relay Interface is triggered by the Fire System (e.g. detector alarm).

Dynamic RED X signs will receive a direct VF input from the fire system.

Dynamic Green signs can be triggered either by a volt free input to the ZW system via the ZXTELC units (as shown) or receive a direct VF input from the Fire System (also shown). Consideration should be given to the critical nature of the Dynamic Green (with/without SoundEscape) activation to determine if the hard-wired connection is a necessary redundancy, in addition to the ZW System activation (hence the dotted lines).

The required actions are determined by the Building’s Fire System matrix.

The methodology depicted below has the Fire Relay Interface and ZXTELC in the same fire zone. This allows for zonal activation of signs without reliance on network infrastructure spanning multiple fire zones. The Fire Relay Interface is shown either connected directly to Dynamic Signs within the same fire zone and to the ZXTEC also in the same fire zone. Further consideration should be given to a UPS backup for the ZXTELC to maintain functions in the event of a supply failure.

ATU = Automatic test unit with, sensing of supply, key-switch test start and automatic reset, part number, EATUKS.

CATU GOG EXIT Sign (with SoundEscape)GOG EXIT Sign ROG EXIT Sign

Fire Relay InterfaceVOLT FREE Outputs

Volt Free Fire alarm input trigger to the ZXTELC – the resulting actions are to be defined by the Building Fire Matrix. This input will be used to trigger GOG EXIT Signs only via the ZW System (if this approach is selected).

Other EM lights

SYSTEM OPERATIONThe Emergency Lighting Functions, including the Dynamic RED X and Dynamic Green signs in activated mode, are tested by the Zoneworks System. This is a power-fail-simulation test for the 90min or 120min duration.

The fire system input triggers and subsequent activation of the Dynamic Green and Dynamic RED X signs must be tested, and visually inspected for correct operation, in accordance with the maintenance schedule (this may be part of a Fire Engineered Solution). Each input trigger, from the fire system, should be operated and the resulting actions inspected to confirm correct operation in accordance with the maintenance schedule.

Consideration should be given to a UPS backup for the ZXTELC.

NOTE: Any volt free (VF) input direct to the dynamic signs can be 24V DC.

NOTE: Inputs to the ZXTELC can only be volt free.

Clevertronics Pty Ltd is a vendor of CleverEVAC products. It is not a fire engineer or designer. It does not purport to recommend its products for use in any particular application or to achieve any particular outcome. Purchasers and users of its products must take their own steps to ensure compliance with statutory requirements, safe practice and suitable application of the products.

Zoneworks XT CleverEvac Interface Schematic

Document Issue: 1.2Document Name: Zoneworks XT CleverEvac Interface Schematic25/01/2018

3-Phase Coupling Device

L1 L2 L3

Distribution Board

SD

Med

ia C

onve

rter

LIN

KPW

RLI

NK

5VD

C. 1

A_

__ _

_ +

UP

LIN

K

RX

TX

Com3

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Ethe

rnet

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Zoneworks Server

Ethernet Switch

Ethernet switch

SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TXSD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Eth

erne

t

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Additional Zoneworks XT Controllers located and servicing other AREAS/FIRE ZONES of the building connected to the Integrated Ethernet Network directly to Distribution Boards.

Ethernet Switch

RJ45 Network Port Ethernet Patch Lead (RJ-45, Cat5 min)

Ethernet Structured Cabling between the network port and the Ethernet switch

Powerline Signal Coupling link

3-Phase MCB

FIRE ZONE/AREA

ZXTELC

Fire Panel

Red cable = fire loop

SYSTEM INTERFACE AND DYNAMIC SIGN/SOUNDER OPERATIONActivation of the Volt Free (VF) outputs of the Fire Relay Interface is triggered by the Fire System (e.g. detector alarm).

Dynamic RED X signs will receive a direct VF input from the fire system.

Dynamic Green signs can be triggered either by a volt free input to the ZW system via the ZXTELC units (as shown) or receive a direct VF input from the Fire System (also shown). Consideration should be given to the critical nature of the Dynamic Green (with/without SoundEscape) activation to determine if the hard-wired connection is a necessary redundancy, in addition to the ZW System activation (hence the dotted lines).

The required actions are determined by the Building’s Fire System matrix.

The methodology depicted below has the Fire Relay Interface and ZXTELC in the same fire zone. This allows for zonal activation of signs without reliance on network infrastructure spanning multiple fire zones. The Fire Relay Interface is shown either connected directly to Dynamic Signs within the same fire zone and to the ZXTEC also in the same fire zone. Further consideration should be given to a UPS backup for the ZXTELC to maintain functions in the event of a supply failure.

ATU = Automatic test unit with, sensing of supply, key-switch test start and automatic reset, part number, EATUKS.

CATU GOG EXIT Sign (with SoundEscape)GOG EXIT Sign ROG EXIT Sign

Fire Relay InterfaceVOLT FREE Outputs

Volt Free Fire alarm input trigger to the ZXTELC – the resulting actions are to be defined by the Building Fire Matrix. This input will be used to trigger GOG EXIT Signs only via the ZW System (if this approach is selected).

Other EM lights

SYSTEM OPERATIONThe Emergency Lighting Functions, including the Dynamic RED X and Dynamic Green signs in activated mode, are tested by the Zoneworks System. This is a power-fail-simulation test for the 90min or 120min duration.

The fire system input triggers and subsequent activation of the Dynamic Green and Dynamic RED X signs must be tested, and visually inspected for correct operation, in accordance with the maintenance schedule (this may be part of a Fire Engineered Solution). Each input trigger, from the fire system, should be operated and the resulting actions inspected to confirm correct operation in accordance with the maintenance schedule.

Consideration should be given to a UPS backup for the ZXTELC.

NOTE: Any volt free (VF) input direct to the dynamic signs can be 24V DC.

NOTE: Inputs to the ZXTELC can only be volt free.

Clevertronics Pty Ltd is a vendor of CleverEVAC products. It is not a fire engineer or designer. It does not purport to recommend its products for use in any particular application or to achieve any particular outcome. Purchasers and users of its products must take their own steps to ensure compliance with statutory requirements, safe practice and suitable application of the products.

240V Light Fitting

Fire System Detector

Dynamic GREEN EXIT sign

Dynamic GREEN EXIT sign (with Sound Escape™)

Dynamic RED X EXIT sign

Other EM lights

Zoneworks XT CleverEvac Interface Schematic

Document Issue: 1.2Document Name: Zoneworks XT CleverEvac Interface Schematic25/01/2018

SD

Med

ia C

onve

rter

LIN

KPW

RLI

NK

5VD

C. 1

A_

__ _

_ +

UP

LIN

K

RX

TX

Com3

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Ethe

rnet

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Zoneworks Server

Ethernet Switch

Ethernet switch

SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TXSD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Eth

erne

t

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Additional Zoneworks XT Controllers located and servicing other AREAS/FIRE ZONES of the building connected to the Integrated Ethernet Network directly to Distribution Boards.

Ethernet Switch

Ethernet Structured Cabling between the network port and the Ethernet switch

Fire Panel

SYSTEM INTERFACE AND DYNAMIC SIGN/SOUNDER OPERATIONActivation of the Volt Free (VF) outputs of the Fire Relay Interface is triggered by the Fire System (e.g. detector alarm).

Dynamic RED X signs will receive a direct VF input from the fire system.

Dynamic Green signs can be triggered either by a volt free input to the ZW system via the ZXTELC units (as shown) or receive a direct VF input from the Fire System (also shown). Consideration should be given to the critical nature of the Dynamic Green (with/without SoundEscape) activation to determine if the hard-wired connection is a necessary redundancy, in addition to the ZW System activation (hence the dotted lines).

The required actions are determined by the Building’s Fire System matrix.

The methodology depicted below has the Fire Relay Interface and ZXTELC in the same fire zone. This allows for zonal activation of signs without reliance on network infrastructure spanning multiple fire zones. The Fire Relay Interface is shown either connected directly to Dynamic Signs within the same fire zone and to the ZXTEC also in the same fire zone. Further consideration should be given to a UPS backup for the ZXTELC to maintain functions in the event of a supply failure.

SYSTEM OPERATIONThe Emergency Lighting Functions, including the Dynamic RED X and Dynamic Green signs in activated mode, are tested by the Zoneworks System. This is a power-fail-simulation test for the 90min or 120min duration.

The fire system input triggers and subsequent activation of the Dynamic Green and Dynamic RED X signs must be tested, and visually inspected for correct operation, in accordance with the maintenance schedule (this may be part of a Fire Engineered Solution). Each input trigger, from the fire system, should be operated and the resulting actions inspected to confirm correct operation in accordance with the maintenance schedule.

Clevertronics Pty Ltd is a vendor of CleverEVAC products. It is not a fire engineer or designer. It does not purport to recommend its products for use in any particular application or to achieve any particular outcome. Purchasers and users of its products must take their own steps to ensure compliance with statutory requirements, safe practice and suitable application of the products.

Zoneworks XT CleverEvac Interface Schematic

Document Issue: 1.2Document Name: Zoneworks XT CleverEvac Interface Schematic25/01/2018

SD

Med

ia C

onve

rter

LIN

KPW

RLI

NK

5VD

C. 1

A_

__ _

_ +

UP

LIN

K

RX

TX

Com3

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Ethe

rnet

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Zoneworks Server

Ethernet Switch

Ethernet switch

SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TXSD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Eth

erne

t

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Additional Zoneworks XT Controllers located and servicing other AREAS/FIRE ZONES of the building connected to the Integrated Ethernet Network directly to Distribution Boards.

Ethernet Switch

Ethernet Structured Cabling between the network port and the Ethernet switch

Fire Panel

SYSTEM INTERFACE AND DYNAMIC SIGN/SOUNDER OPERATIONActivation of the Volt Free (VF) outputs of the Fire Relay Interface is triggered by the Fire System (e.g. detector alarm).

Dynamic RED X signs will receive a direct VF input from the fire system.

Dynamic Green signs can be triggered either by a volt free input to the ZW system via the ZXTELC units (as shown) or receive a direct VF input from the Fire System (also shown). Consideration should be given to the critical nature of the Dynamic Green (with/without SoundEscape) activation to determine if the hard-wired connection is a necessary redundancy, in addition to the ZW System activation (hence the dotted lines).

The required actions are determined by the Building’s Fire System matrix.

The methodology depicted below has the Fire Relay Interface and ZXTELC in the same fire zone. This allows for zonal activation of signs without reliance on network infrastructure spanning multiple fire zones. The Fire Relay Interface is shown either connected directly to Dynamic Signs within the same fire zone and to the ZXTEC also in the same fire zone. Further consideration should be given to a UPS backup for the ZXTELC to maintain functions in the event of a supply failure.

SYSTEM OPERATIONThe Emergency Lighting Functions, including the Dynamic RED X and Dynamic Green signs in activated mode, are tested by the Zoneworks System. This is a power-fail-simulation test for the 90min or 120min duration.

The fire system input triggers and subsequent activation of the Dynamic Green and Dynamic RED X signs must be tested, and visually inspected for correct operation, in accordance with the maintenance schedule (this may be part of a Fire Engineered Solution). Each input trigger, from the fire system, should be operated and the resulting actions inspected to confirm correct operation in accordance with the maintenance schedule.

Clevertronics Pty Ltd is a vendor of CleverEVAC products. It is not a fire engineer or designer. It does not purport to recommend its products for use in any particular application or to achieve any particular outcome. Purchasers and users of its products must take their own steps to ensure compliance with statutory requirements, safe practice and suitable application of the products.

Zoneworks XT CleverEvac Interface Schematic

Document Issue: 1.2Document Name: Zoneworks XT CleverEvac Interface Schematic25/01/2018

SD

Med

ia C

onve

rter

LIN

KPW

RLI

NK

5VD

C. 1

A_

__ _

_ +

UP

LIN

K

RX

TX

Com3

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Ethe

rnet

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Zoneworks Server

Ethernet Switch

Ethernet switch

SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TXSD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Eth

erne

t

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Additional Zoneworks XT Controllers located and servicing other AREAS/FIRE ZONES of the building connected to the Integrated Ethernet Network directly to Distribution Boards.

Ethernet Switch

Ethernet Structured Cabling between the network port and the Ethernet switch

Fire Panel

SYSTEM INTERFACE AND DYNAMIC SIGN/SOUNDER OPERATIONActivation of the Volt Free (VF) outputs of the Fire Relay Interface is triggered by the Fire System (e.g. detector alarm).

Dynamic RED X signs will receive a direct VF input from the fire system.

Dynamic Green signs can be triggered either by a volt free input to the ZW system via the ZXTELC units (as shown) or receive a direct VF input from the Fire System (also shown). Consideration should be given to the critical nature of the Dynamic Green (with/without SoundEscape) activation to determine if the hard-wired connection is a necessary redundancy, in addition to the ZW System activation (hence the dotted lines).

The required actions are determined by the Building’s Fire System matrix.

The methodology depicted below has the Fire Relay Interface and ZXTELC in the same fire zone. This allows for zonal activation of signs without reliance on network infrastructure spanning multiple fire zones. The Fire Relay Interface is shown either connected directly to Dynamic Signs within the same fire zone and to the ZXTEC also in the same fire zone. Further consideration should be given to a UPS backup for the ZXTELC to maintain functions in the event of a supply failure.

SYSTEM OPERATIONThe Emergency Lighting Functions, including the Dynamic RED X and Dynamic Green signs in activated mode, are tested by the Zoneworks System. This is a power-fail-simulation test for the 90min or 120min duration.

The fire system input triggers and subsequent activation of the Dynamic Green and Dynamic RED X signs must be tested, and visually inspected for correct operation, in accordance with the maintenance schedule (this may be part of a Fire Engineered Solution). Each input trigger, from the fire system, should be operated and the resulting actions inspected to confirm correct operation in accordance with the maintenance schedule.

Clevertronics Pty Ltd is a vendor of CleverEVAC products. It is not a fire engineer or designer. It does not purport to recommend its products for use in any particular application or to achieve any particular outcome. Purchasers and users of its products must take their own steps to ensure compliance with statutory requirements, safe practice and suitable application of the products.

Zoneworks XT CleverEvac Interface Schematic

Document Issue: 1.2Document Name: Zoneworks XT CleverEvac Interface Schematic25/01/2018

SD

Med

ia C

onve

rter

LIN

KPW

RLI

NK

5VD

C. 1

A_

__ _

_ +

UP

LIN

K

RX

TX

Com3

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Ethe

rnet

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Zoneworks Server

Ethernet Switch

Ethernet switch

SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TXSD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Eth

erne

t

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Additional Zoneworks XT Controllers located and servicing other AREAS/FIRE ZONES of the building connected to the Integrated Ethernet Network directly to Distribution Boards.

Ethernet Switch

Ethernet Structured Cabling between the network port and the Ethernet switch

Fire Panel

SYSTEM INTERFACE AND DYNAMIC SIGN/SOUNDER OPERATIONActivation of the Volt Free (VF) outputs of the Fire Relay Interface is triggered by the Fire System (e.g. detector alarm).

Dynamic RED X signs will receive a direct VF input from the fire system.

Dynamic Green signs can be triggered either by a volt free input to the ZW system via the ZXTELC units (as shown) or receive a direct VF input from the Fire System (also shown). Consideration should be given to the critical nature of the Dynamic Green (with/without SoundEscape) activation to determine if the hard-wired connection is a necessary redundancy, in addition to the ZW System activation (hence the dotted lines).

The required actions are determined by the Building’s Fire System matrix.

The methodology depicted below has the Fire Relay Interface and ZXTELC in the same fire zone. This allows for zonal activation of signs without reliance on network infrastructure spanning multiple fire zones. The Fire Relay Interface is shown either connected directly to Dynamic Signs within the same fire zone and to the ZXTEC also in the same fire zone. Further consideration should be given to a UPS backup for the ZXTELC to maintain functions in the event of a supply failure.

SYSTEM OPERATIONThe Emergency Lighting Functions, including the Dynamic RED X and Dynamic Green signs in activated mode, are tested by the Zoneworks System. This is a power-fail-simulation test for the 90min or 120min duration.

The fire system input triggers and subsequent activation of the Dynamic Green and Dynamic RED X signs must be tested, and visually inspected for correct operation, in accordance with the maintenance schedule (this may be part of a Fire Engineered Solution). Each input trigger, from the fire system, should be operated and the resulting actions inspected to confirm correct operation in accordance with the maintenance schedule.

Clevertronics Pty Ltd is a vendor of CleverEVAC products. It is not a fire engineer or designer. It does not purport to recommend its products for use in any particular application or to achieve any particular outcome. Purchasers and users of its products must take their own steps to ensure compliance with statutory requirements, safe practice and suitable application of the products.

Zoneworks XT CleverEvac Interface Schematic

Document Issue: 1.2Document Name: Zoneworks XT CleverEvac Interface Schematic25/01/2018

SD

Med

ia C

onve

rter

LIN

KPW

RLI

NK

5VD

C. 1

A_

__ _

_ +

UP

LIN

K

RX

TX

Com3

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Ethe

rnet

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Zoneworks Server

Ethernet Switch

Ethernet switch

SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TXSD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX SD

Media C

onverter

LINK

PWR

LINK

5VDC

. 1A_ __ __ +

UP LIN

K

RX

TX

1 2 3 4 5 6

7 8 9101112

AB

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

Eth

erne

t

A

12x

6x

8x

2x

9x

3x

10x

4x

11x

5x

7x

1x

C

Additional Zoneworks XT Controllers located and servicing other AREAS/FIRE ZONES of the building connected to the Integrated Ethernet Network directly to Distribution Boards.

Ethernet Switch

Ethernet Structured Cabling between the network port and the Ethernet switch

Fire Panel

SYSTEM INTERFACE AND DYNAMIC SIGN/SOUNDER OPERATIONActivation of the Volt Free (VF) outputs of the Fire Relay Interface is triggered by the Fire System (e.g. detector alarm).

Dynamic RED X signs will receive a direct VF input from the fire system.

Dynamic Green signs can be triggered either by a volt free input to the ZW system via the ZXTELC units (as shown) or receive a direct VF input from the Fire System (also shown). Consideration should be given to the critical nature of the Dynamic Green (with/without SoundEscape) activation to determine if the hard-wired connection is a necessary redundancy, in addition to the ZW System activation (hence the dotted lines).

The required actions are determined by the Building’s Fire System matrix.

The methodology depicted below has the Fire Relay Interface and ZXTELC in the same fire zone. This allows for zonal activation of signs without reliance on network infrastructure spanning multiple fire zones. The Fire Relay Interface is shown either connected directly to Dynamic Signs within the same fire zone and to the ZXTEC also in the same fire zone. Further consideration should be given to a UPS backup for the ZXTELC to maintain functions in the event of a supply failure.

SYSTEM OPERATIONThe Emergency Lighting Functions, including the Dynamic RED X and Dynamic Green signs in activated mode, are tested by the Zoneworks System. This is a power-fail-simulation test for the 90min or 120min duration.

The fire system input triggers and subsequent activation of the Dynamic Green and Dynamic RED X signs must be tested, and visually inspected for correct operation, in accordance with the maintenance schedule (this may be part of a Fire Engineered Solution). Each input trigger, from the fire system, should be operated and the resulting actions inspected to confirm correct operation in accordance with the maintenance schedule.

Clevertronics Pty Ltd is a vendor of CleverEVAC products. It is not a fire engineer or designer. It does not purport to recommend its products for use in any particular application or to achieve any particular outcome. Purchasers and users of its products must take their own steps to ensure compliance with statutory requirements, safe practice and suitable application of the products.

LEGEND

FIRE PANEL

DISTRIBUTION BOARD

FIRE ZO

NE / A

RE

A

Fire Relay Interface VOLT FREE Outputs

Red Cable = Addressable Fire Detection Loop

Zoneworks®Emergency Lighting Controller (ZXTELC)

System Interface and Dynamic Sign Sounder and System OperationCleverEVAC Interface Schematic

Page 6: Dynamic Exit Signage - CleverEVAC · RU RL RD R. 8 9 SYSTEM INTERFACE AND DYNAMIC SIGN / SOUNDER OPERATION Activation of the Volt Free (VF) outputs of the Fire Relay Interface is

10

24V 24VDC on/off signal output provided by the fire detection or other building safety system

AS2293 Australian Standards for Emergency & Exit Lighting for buildings covering design, installation, maintainence and fittings

L,N,E Mains Power cables

LED Light Emitting Diode

UPS Uninterruptable Power Supply

VF Volt Free open/close signal output provided by the fire detection or other building safety system

ZONEWORKS® XT Automatic testing & monitoring system for Emergency Lighting system provided by Clevertronics

ZXTELC Zoneworks® XT Emergency Lighting Controller

Glossary of Terms

Glossary of Terms

Notes

Notes

• Australia’s No1 selling emergency lighting range• Over 50% maintenance savings vs NiCd

The LP range is the proven project performer that combines Lithium Iron Phosphate battery technology with premium electronics and LED technology

Nothing else competes with L10 Nanophosphate®, due to the structure of the Nanophosphate chemistry that enables higher power, increased abuse tolerance and longer life compared to other Lithium Iron Phosphate offerings

• Lowest total ownership cost• 50% longer battery life vs any other lithium product• 60% maintenance savings vs any other lithium product• Over 80% maintenance savings vs NiCd

Page 7: Dynamic Exit Signage - CleverEVAC · RU RL RD R. 8 9 SYSTEM INTERFACE AND DYNAMIC SIGN / SOUNDER OPERATION Activation of the Volt Free (VF) outputs of the Fire Relay Interface is

Victoria195 Chesterville Road Moorabbin VIC 3189 P +61 3 9559 2700 F +61 3 9559 2799

South Australia Unit 2 / 19 Main Terrace, Richmond SA 5033 P +61 8 8301 8800 F +61 8 8351 8286

New South Wales 9 Distribution Place Seven Hills NSW 2147 P +61 2 8805 6400 F +61 2 8805 6444

Western Australia12 Milly Court Malaga WA 6090 P +61 8 9248 3720 F +61 8 9248 3725

QueenslandUnit 2/8-12 Monte-Khoury Drive Loganholme QLD 4129 P +61 7 3442 9700 F +61 7 3442 9777

Auckland Unit 22/761 Great South RoadPenrose, Auckland 1061 P +64 800 548 448

Christchurch163B Wordsworth Street, Sydenham, Christchurch 8023P +64 092 224 635

United KingdomUnit 362 Stockley Close, West Drayton, London UB7 9BLP +44 01895 430 255 F +44 01895 430 254

Clevertronics Pty Ltd is a vendor of CleverEVAC products. It is not a fire engineer or designer. It does not purport to recommend its products for use in

any particular application or to achieve any particular outcome.Purchasers and users of its products must take their own steps to ensure compliance with statutory requirements, safe practice and suitable application of the products.

236A CleverEVAC 22082019

cleverevac.com.au


Recommended