DZ47LE C45LE Residual Current Circuit Breaker with Over Current ProtectionDZ47LE C45LE Residual Current Circuit Breaker with Over Current ProtectionDZ47LE C45LE Residual Current Circuit Breaker with Over Current ProtectionDZ47LE C45LE Residual Current Circuit Breaker with Over Current ProtectionDZ47LE C45LE Residual Current Circuit Breaker with Over Current Protection
ApplicationDZ47LE C45LE RCBO is used for the protection against electrical leakage in the circuitof 50Hz or 60Hz, rated voltage 1 phase 230V and 3 phase 400V, rated current up to63A. When somebody gets an electric shock or the residual current of the circuit ex-ceeds the fixed value, the RCBO can cut off the power within the time of 0.1s automati-cally to protect the personal safety and preventing the equipment from the fault resultedby the residual current. With this function, the RCBO can protect the circuit againstoverload and short circuit or can be used for the unfrequent switchover of the circuitunder normal conditions. It conforms to IEC61009 standard.
Specifications
Operation Principle
• Circumstance temperature -5°C~+40°C, average temperature not exceeding 35°C.
• Altitude above sea level less than 2000m.
• Humidity not exceeding 50% at 40°C and not exceeding 90% at 25°C.
• Installation class II or III.
• Pollution class II.
• Installation method DIN Rail mounting type.
• The external magnetism shall not be more than 5 times of terrestrial one.
• Product shall be installed vertically at the place where there shall be no severe impact
and vibration. The product is switched on when the handle is at upper position.
Normal Operation and Mounting Requirement
1P+N, 2P, 3P, 3P+N, 4P
6, 10, 16, 20, 25, 32, 40, 50, 63
30, 100, 300, 500
� 0.5IΔn
220/380
C, D
Electronic
Number of Poles
Rated current (A)
Rated operating current (mA)
Rated non operating (IΔN)(mA)
Rated voltage (V)
Tripping curve
Type
Wiring Diagram
Single-Pole
Double Line
C45N+DZ47L
C45N+C45L
1/2
Double-Pole
Double Line
C45N+DZ47L
C45N+C45L
2/2
Triple-Pole
Triple Line
C45N+DZ47L
C45N+C45L
3/3
Triple-Pole
Four Line
C45N+DZ47L
C45N+C45L
3/4
Four-Pole
Four Line
C45N+DZ47L
C45N+C45L
4/4
DZ47LE 1P+N
DZ47LE 3P
C45LE 1P+N
C45LE 3P
www.ck-electrical.com
21Tel:0086-577-88999052 Fax:0086-577-88999161 E-mail:[email protected]
C65NLE Residual Current Circuit Breaker withC65NLE Residual Current Circuit Breaker withC65NLE Residual Current Circuit Breaker withC65NLE Residual Current Circuit Breaker withC65NLE Residual Current Circuit Breaker with
Over Current ProtectionOver Current ProtectionOver Current ProtectionOver Current ProtectionOver Current ProtectionApplicationC65NLE RCBO is used for the protection against electrical leakage in the circuit of 50Hz
or 60Hz, rated voltage single-phase 230V, 3 phase 400V, rated current up to 60A. When
somebody gets an electric shock or the residual current of the circuit exceeds the fixed
value, the ELCB can cut off the power within the time of 0.1s automatically to protect the
personal safety and preventing the equipment from the fault resulted by the residual
current. With this function, the ELCB can protect the circuit against overload and short
circuit or can be used for the unfrequent switchover of the circuit under normal conditions.
It conforms to IEC61009 standard.
Specifications1P+N, 2P, 3P, 3P+N, 4P
240/415V
6A 10A 16A 20A 25A 32A 40A 50A 63A
30mA 100mA 300mA
� 0.5IΔn
C, D
Number of Poles
Rated voltage
Rated current
Rated operating current (mA)
Rated non-operating(IΔn)
Tripping Curve
C65NLE 2P
C65NLE 4PC60NLE Earth Leakage Circuit Breaker with OverC60NLE Earth Leakage Circuit Breaker with OverC60NLE Earth Leakage Circuit Breaker with OverC60NLE Earth Leakage Circuit Breaker with OverC60NLE Earth Leakage Circuit Breaker with Over
Current ProtectionCurrent ProtectionCurrent ProtectionCurrent ProtectionCurrent Protection
72.536
O.OFF 35.5
85.5
C60NLE
Dimensions
Specifications
Number of Poles
Rated Current (A)
Rated Residual Operating Current (IΔn)(mA)
Rated Voltage (V)
Residual Current Off-time
Short Circuit Capacity (Icu) (A)
2P
10, 16, 20, 25, 32, 40
30, 100, 300
230
� 0.1S
4500
www.ck-electrical.com
Tel:0086-577-88999052 Fax:0086-577-88999161 E-mail:[email protected]
22
DZ30LE(DPNLE) Earth Leakage Circuit Breaker with Over Cur-DZ30LE(DPNLE) Earth Leakage Circuit Breaker with Over Cur-DZ30LE(DPNLE) Earth Leakage Circuit Breaker with Over Cur-DZ30LE(DPNLE) Earth Leakage Circuit Breaker with Over Cur-DZ30LE(DPNLE) Earth Leakage Circuit Breaker with Over Cur-rent Protectionrent Protectionrent Protectionrent Protectionrent ProtectionSpecifications
Dimensions
DZ30LE Overload Trip Characteristic
NC100LE Residual Current Circuit Breaker with Over Current ProtectionNC100LE Residual Current Circuit Breaker with Over Current ProtectionNC100LE Residual Current Circuit Breaker with Over Current ProtectionNC100LE Residual Current Circuit Breaker with Over Current ProtectionNC100LE Residual Current Circuit Breaker with Over Current Protection
NC100LE 1P+N
NC100LE 3P
Number of Poles
Rated Current (A)
Rated Residual Operating Current (IΔn)(mA)
Rated Residual Non-operation Current (IΔno)(mA)
Rated Voltage (V)
Residual Current Off-time
Short Circuit Capacity (Icu)
1P+N
6, 10, 16, 20, 25, 32
30
15
230
� 0.1S
4500A
Testing
Current(A)
1.13In
1.45In
2.55In
5In
10In
Rated
Voltage(V)
all
all
all
all
all
Limited
Time
t � 1h
t<1h
1s<t<60s
t � 0.1s
t<0.1s
Pre-engage
Result
non-triptrip
trip
non-trip
trip
StartSituation
cold state
heat state
cole state
cold state
cole state
Note
The current rise steadily to afixed value within 5s
Open the supplementaryswitch, connect the powerOpen the supplementary
switch, connect the powerOpen the supplementary
switch, connect the power
NC100LE RCBO is suitable for the circuit of 50Hz, rated voltage 230/400V, and rated
current up to 100A. It has the earth leakage, overload & short circuit protect function. It
can also add over voltage protect function. It is mainly used in building illumination and
electrical distribution system.
Application
Number of Poles
Rated Current (A)
Rated Residual Operating Current (IΔn)(mA)
Rated Residual Non-operation Current (IΔno)(mA)
Rated Voltage (V)
Residual Current Off-time
Short Circuit Capacity (Icu)
Endurance
Tripping Curve
Protection Degree
1P+N, 2P, 3P, 3P+N, 4P
40, 50, 63, 80, 100
30, 50, 100, 200, 300
� 0.5IΔn
AC 230/400
� 0.1S
3000A
� 4000
C, D
IP20
Specifications
www.ck-electrical.com
23Tel:0086-577-88999052 Fax:0086-577-88999161 E-mail:[email protected]
F360 Residual Current Circuit BreakerF360 Residual Current Circuit BreakerF360 Residual Current Circuit BreakerF360 Residual Current Circuit BreakerF360 Residual Current Circuit Breaker
ApplicationThe RCCB is in conformity with the standard of IEC61008. The RCCB can cut off the
fault circuit immediately on the occasion of shock hazard or earth leakage of trunk. Thus,
it is suitable to avoid the shock hazard and fire caused by earth leakage.
The RCCB is mainly suitable for use in varieties of plants and enterprises, building con-
struction 1 phase 230V and 3 phase 400V 50/60Hz. RCCB is not suitable for use on DC
pulse system.
Number of Poles
Rated Current (A)
Rated Residual Operating Current (IΔn)(mA)
Rated Residual Non-operation Current (IΔno)(mA)
Rated Voltage (V)
Residual Operating Current Scope
Residual Current Off-time
Short Circuit Capacity (Icu)
Type
Protection Degree
2P, 4P
16, 20, 25, 32, 40, 50, 63, 80
30, 100, 300
� 0.5IΔn
AC 230/240
AC 400/415
0.5IΔn~IΔn
� 0.3S
3000A
A Type ,AC Type
IP20
Specifications
1 1
2
3
4
5
6
7
8
N
N
3
2 4
Operation Principle
Overall And Mounting Dimensions (Unit: mm)
69
6844
6.3
3517.5
7.5
17.5�2
90.4
90.4
71 46
17.5�2
7017.5
7.5
17.5�2
90.4
71 46
17.517.517.5�2
F360 2P
F360 4P
F360 2P(NEW)
F360 4P(NEW)
www.ck-electrical.com
Tel:0086-577-88999052 Fax:0086-577-88999161 E-mail:[email protected]
24
NFIN Residual Current DeviceNFIN Residual Current DeviceNFIN Residual Current DeviceNFIN Residual Current DeviceNFIN Residual Current Device
ApplicationThe Residual Current Device NFIN is in conformity with the standard of IEC61008,
VDE0664,CEE27 and BS4263
It can cut off the fault circuit immediately on the occasion of shock hazard or earth leak-
age of trunk line. Thus it is suitable to avoid the shock hazard and fire caused by earth
leakage.
NFIN RCD is mainly suitable for using in varieties of plants, enterprises, buildings,
constructions, commerce, guesthouses and families. It can be used in circuits of 1 phase
230V and 3 phase 400V 50/60Hz.
Specifications
Number of Poles
Rated Current (A)
Rated Residual Operating Current (IΔn)(mA)
Rated Residual Non-operation Current (IΔno)(mA)
Rated Voltage (V)
Residual Current Off-time
Short Circuit Capacity (Icu)
Endurance
Protection Degree
2P, 4P
16, 20, 25, 32, 40, 50, 63, 80, 100
30, 100, 300, 500
� 0.5IΔn
AC 230/400
� 0.1S
3000A
� 4000
IP20
ID Residual Current Circuit BreakerID Residual Current Circuit BreakerID Residual Current Circuit BreakerID Residual Current Circuit BreakerID Residual Current Circuit Breaker
ApplicationID RCCB is in conformity with the standard of IEC61008. The RCCB can cut off the fault
circuit immediately on the occasion of shock hazard or earth leakage of trunk. Thus, it is
suitable to avoid the shock hazard and fire caused by earth leakage.
The RCCB is mainly suitable for use in varieties of plants and enterprises, building con-
struction 1 phase 230V and 3 phase 400V 50/60Hz. RCCB is not suitable for use on DC
pulse system.
Specifications
Number of Poles
Rated Current (A)
Rated Residual Operating Current (IΔn)(mA)
Rated Voltage (V)
Residual Operating Current Scope
Residual Current Off-time
Short Circuit Capacity (Icu)
Endurance
Protection Degree
1P+N, 3P+N
16, 20, 25, 40, 50, 63
30, 100, 300, 500
AC 230/240
AC 400/415
0.5IΔn~IΔn
� 0.3S
6000A
4000
IP20
ID 2P
ID 4P
NFIN-2 2P
NFIN-2 4P
NFIN-1 2P
NFIN-1 4P
www.ck-electrical.com
25Tel:0086-577-88999052 Fax:0086-577-88999161 E-mail:[email protected]
L1 N
L1 N L3L2L1 N
L3L2L1 N
L1 L2 L3 N
L1 L2 L3 N
75±0
.8
45
70±0.5
Ø7.5305.5
0.5
74±0.8
35±0
.3
Ø4.3
T
I
Operation Principle
Overall And Mounting Dimensions (Unit: mm)
FIN Residual Current DeviceFIN Residual Current DeviceFIN Residual Current DeviceFIN Residual Current DeviceFIN Residual Current Device
Residual Current Device(RCD) FIN is in conformity with the standard of IEC61008.
It can cut off the fault circuit immediately on the occasion of shock hazard or earth leak-
age of trunk line. Thus it is suitable to avoid the shock hazard and fire caused by earth
leakage.
FIN ELCB is mainly suitable for varieties of plants and enterprises, buildings, construction,
commerce, hotels and families. It can be used in circuits of 1 phase 230V and 3 phase
400V 50/60Hz.
Application
Specifications
• C i r cums tance tempera tu re -
5°C~+40°C, average temperature not
exceeding 35°C.
• Altitude above sea level less than
2000m.
• Humidity not exceeding 50% at 40°Cand not exceeding 90% at 25°C.
• Installation class II or III.
• Pollution class II.
• Installation method DIN Rail mounting
type.
• The external magnetism shall not be
more than 5 times of terrestrial one.
• Product shall be installed vertically at
the place where there shall be no se-
vere impact and vibration. The prod-
uct is switched on when the handle is
at upper position.
Normal Operation and Mount-
ing Requirement
FIN 2P
FIN 4P
Number of Poles
Rated Current (A)
Rated Residual Operating Current (IΔn)(mA)
Rated Residual Non-operation Current (IΔno)(mA)
Rated Voltage (V)
Residual Current Off-time
Short Circuit Capacity (Icu)
Endurance
Protection Degree
2P, 4P
16, 20, 25, 32, 40, 50, 63
30, 100, 300, 500
� 0.5IΔn
AC 230/400
� 0.1S
3000A
� 4000
IP20
www.ck-electrical.com
Tel:0086-577-88999052 Fax:0086-577-88999161 E-mail:[email protected]
26
RC Residual Current DeviceRC Residual Current DeviceRC Residual Current DeviceRC Residual Current DeviceRC Residual Current Device
ApplicationRC Residual Current Device is in conformity with the standard of IEC61008.
It can cut off the fault circuit immediately on the occasion of shock hazard or earth leak-
age of trunk line. Thus it is suitable to avoid the shock hazard and fire caused by earth
leakage.
The product is mainly suitable for using in varieties of plants, enterprises, buildings,
constructions, commerce, guesthouses and families. It can be used in circuits of 1 phase
230V and 3 phases 400V 50/60Hz.
Specifications
Operation Principle
Overall And Mounting Dimensions (Unit: mm)
Number of Poles
Rated Current (A)
Rated Residual Operating Current (IΔn)(mA)
Rated Residual Non-operation Current (IΔno)(mA)
Rated Voltage (V)
Residual Current Off-time
Short Circuit Capacity (Icu)
Endurance
Protection Degree
2P, 4P
16, 20, 25, 32, 40, 50, 63, 80, 100
30, 100, 300, 500
� 0.5IΔn
AC 230/400
� 0.1S
3000A
� 4000
IP20
L1 N
L1 N
L1 L2�
L1�
L3
L2� L3�
N
N
35±0
.3
86±0
.8
45
75±0.8 35.6±0.3
5
O.OFF
Test
71.2±0.5
O.OFF
Test
RC1 2P
RC1 4P
RC2 2P
RC2 4P
www.ck-electrical.com
27Tel:0086-577-88999052 Fax:0086-577-88999161 E-mail:[email protected]
F7 Residual Current DeviceF7 Residual Current DeviceF7 Residual Current DeviceF7 Residual Current DeviceF7 Residual Current Device
ApplicationThe Residual Current Device F7 is in conformity with the standard of IEC61008.
It can cut off the fault circuit immediately on the occasion of shock hazard or earth leak-
age of trunk line. Thus it is suitable to avoid the shock hazard and fire caused by earth
leakage.
F7 RCD is mainly suitable for using in varieties of plants, enterprises, buildings,
constructions, commerce, guesthouses and families. It can be used in circuits of 1 phase
230V and 3 phases 400V 50/60Hz.
Specifications
Overall And Mounting Dimensions (Unit: mm)
Operation Principle
Number of Poles
Rated Current (A)
Rated Residual Operating Current (IΔn)(mA)
Rated Residual Non-operation Current (IΔno)(mA)
Rated Voltage (V)
Residual Current Off-time
Short Circuit Capacity (Icu)
Endurance
Protection Degree
2P, 4P
30, 100, 300, 500
� 0.5IΔn
AC 230/400
� 0.1S
� 4000
IP20
16, 20, 25, 32, 40 50, 63
1500A 3000A
2� N�
1� N�
2� N�
1�
4�
3�
6�
5� N�
75±0.8 35±0.3 70±0.55.5
1 N
2
T
N
36±0
.3
80±0
.8
45
5 N
6
T
N
1 3
2 4
F7-1 2P
F7-1 4P
F7-2 2P
F7-2 4P
www.ck-electrical.com
Tel:0086-577-88999052 Fax:0086-577-88999161 E-mail:[email protected]
28
BV-D Residual Current DeviceBV-D Residual Current DeviceBV-D Residual Current DeviceBV-D Residual Current DeviceBV-D Residual Current DeviceSpecifications
KD Residual Current DeviceKD Residual Current DeviceKD Residual Current DeviceKD Residual Current DeviceKD Residual Current DeviceApplicationEarth leakage circuit breaker KD is suitable for the circuit of AC 50/60Hz,rated voltage
250V,and rated current up to 30A,It can cut off the circuit immediately on the occasion
of shock hazard and fire caused by earth leakage.And it is especially used in household
and public building,And this product conforms to GB16916.1/EC1008.1 standard.
Pole
Rated voltage Ui(V)
Rated current(A)
Rated leakage operating current
Rated leakage dead current
Leadage operating time
Mechanical and electrical endurance
Specifications
Design according to
Tripping time
Rated voltage
Rated tripping current
Sensitivity
Rated short
Circuit strength
Maximum bakc-up fuse for
Short circuit protection
Maximum back-up fuse for
Overload protection
Resistance to climatic conditions
Degree of protection
Endurance electrical comp.
mech comp.
ICE 1008 (EN 61008)
undelayed
min.10 ms delay
min.40 ms delay
with selective disconnecting function
230/400V; 50Hz
10, 30, 100, 300, 500mA
AC and pulsating DC
10KA with 63A gL back-up fuse
10KA with 80A gL (F7-80 and -863)
6KA (rated current 63A) with 63A gL
63A gL
80 A gL (F7-80 and -863)
45 A gL (F7 - 25 and -40 A)
40 A gL(F7 -80 A)
according to IEC 1008
built-in switch IP 40
≤4.000 operating cycles
≥20.000 operating cycles
2P
AC 240V
30A
15mA 30mA
7.5mA 15mA
T � 0.1s
� 4000 times
BV-D 2P
BV-D 4P
KD
www.ck-electrical.com
29Tel:0086-577-88999052 Fax:0086-577-88999161 E-mail:[email protected]
5SM Residual Current Device5SM Residual Current Device5SM Residual Current Device5SM Residual Current Device5SM Residual Current Device
ApplicationSeries 5SM earth leakage breakers apply to in AC circuit of 50Hz,rated voltage up to
415V,rated current up to 80A.It is mainly used as an indirect contact protection for human.
It also can be used to prevent against the fire danger caused by earth fault current owing
to equipment insulation damage.When the proective measures of the electric shock are
out of work,the RCCB whose rated residual operating current less than 30mA can serve
as the supplementary protection for in direct contact,but it can’t be used as the sole
direct contact protection.
Product features
Dimension And Mounting
1.Series 5SM1 Leakage breaker are the protector for pure electromagetic residual cur-
rent operation.
2.The operation function is unrelated to circuit voltage,but operation is reliable.
3.It can be reliably operated on the less of phase or neutral.
4.The capacity of resisting electromagnetic interference is strong.
Main Technical Data
Type Un(V) HzIm
I� m
Inc
I� m
InA I� n
mA
The maximum of break-time(s)
I� N 2I
� N 5I� N 0.25A 500A
0.04
0.04
0.04
0.04
0.04
0.04
0.04
0.04
0.04
0.04
0.04
0.04
0.04
0.04
0.04
-
0.04
0.04
0.04
0.04
0.04
-
0.04
0.04
-
-
-
0.04
0.04
0.04
-
-
-
0.04
0.04
0.04
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
30
50
75
100
300
500
30
50
75
100
300
500
I� no
mA
15
25
40
50
150
250
15
25
40
50
150
250
6,10,
16,25,
32,40,
50,63,
80
6,10,
16,25,
32,40,
50,63,
80
6000A
6000A
500A
(In �
50A
10In)
(In �
50A)
500A
(In �
50A
10In)
(In �
50A)
5SM1
2P
5SM1
4P
240
415
50,
60
5SM 2P
5SM 4P
www.ck-electrical.com
Tel:0086-577-88999052 Fax:0086-577-88999161 E-mail:[email protected]
30
CT Residual Current DeviceCT Residual Current DeviceCT Residual Current DeviceCT Residual Current DeviceCT Residual Current DeviceUsage
PGPGPGPGPG230 230 230 230 230 PGPGPGPGPG430 430 430 430 430 EEEEEarth arth arth arth arth LLLLLeakage eakage eakage eakage eakage CCCCCircuit ircuit ircuit ircuit ircuit BBBBBreakerreakerreakerreakerreaker
Application
CT Residual Current Circuit Breaker without over current protection conforms to the
standards of GB16916.1, IEC1008, BS4293 etc. It is used in the circuits of AC 50~60Hz,
single phase 230V(220V), three phases 400V(380V) in industrial & mining enterprises,
commercial buildings and housing for protection of personal electric shock hazard and
electric equipment and for unfrequent switchover of circuits under normal conditions.
Mounting InstructionsThis RCD is intended for installation within an enclosure in an ambient temperature
between -5°C and 40°C with an average value not exceeding 35°C over a 24 hour
period. It should not be installed at an altitude greater than 2000m above sea level, nor
in an atmosphere subject to excessive pollution by smoke, dust, chemical fumes, salt
laden spray, prolonged periods of high humidity or other abnormal conditions. See cur-
rent product catalogues for a wide range of suitable enclosure.
PG230 & PG430 earth leagkage circuit breakers, the rated curent is adjustable
form 10A up to 60A. User can select suitable current for better protection against
overload and short circuit. The products comply with NFC1450.
Specifications
Type
Poles
Rated voltage(V)
Rated current(A)
Leakage motion current(mA)
Leakage dead current(mA)
Standard
PG230
2P
PG430
4P
250V/440V
10, 15, 20, 30, 45, 50, 60A Ajustable
NFC 61450
300mA, 500mA
150mA, 250mA
300mA, 500mA
150mA, 250mA
CT
PG230
PG430
www.ck-electrical.com
31Tel:0086-577-88999052 Fax:0086-577-88999161 E-mail:[email protected]
Number of Poles
Rated Current (A)
Rated Residual Operating Current (IΔn)(mA)
Rated Residual Non-operation Current (IΔno)(mA)
Rated Voltage (V)
Residual Current Off-time
Short Circuit Capacity (Icu)
Endurance
Protection Degree
2P, 4P
25, 32, 40, 63, 80, 100, 125
100, 300, 500
� 0.5IΔn
AC 230/400
� 0.1S
3000A
� 4000
IP20
F 1 Residual Current Circuit BreakerF 1 Residual Current Circuit BreakerF 1 Residual Current Circuit BreakerF 1 Residual Current Circuit BreakerF 1 Residual Current Circuit Breaker
ApplicationF1 RCCB is in conformity with the standard of IEC61008. The RCCB can cut off the fault
circuit immediately on the occasion of shock hazard or earth leakage of trunk. Thus, it is
suitable to avoid the shock hazard and fire caused by earth leakage.
The RCCB is mainly suitable for use in varieties of plants and enterprises, building con-
struction 1 phase 230V and 3 phase 400V 50/60Hz. RCCB is not suitable for use on DC
pulse system.
Specifications
Overall And Mounting Dimensions (Unit: mm)
Operation Principle
• C i r cums tance tempera tu re -
5°C~+40°C, average temperature not
exceeding 35°C.
• Altitude above sea level less than
2000m.
• Humidity not exceeding 50% at 40°Cand not exceeding 90% at 25°C.
• Installation class II or III.
• Pollution class II.
• Installation method DIN Rail mounting
type.
• The external magnetism shall not be
more than 5 times of terrestrial one.
• Product shall be installed vertically at
the place where there shall be no se-
vere impact and vibration. The product
is switched on when the handle is at
upper position.
Normal Operation and Mount-
ing Requirement
F1 2P
M2.5
R2.290
82
116 90 35.5
98
L1 N
L1 N
L1 L3
L1 L3
L2 N
L2 N
C-F1
www.ck-electrical.com
Tel:0086-577-88999052 Fax:0086-577-88999161 E-mail:[email protected]
32