    RTU560Remote Terminal Unit

    Host Communication Interfacewith Harris-5000/5500/6000

    Contents: This manual describes the RTU560 Host CommunicationInterface with Harris-5000/5500/6000 protocol

  • 7/26/2019 e560 Harris Host

    2/36

  • 7/26/2019 e560 Harris Host

    3/36

    ABB AG 1KGT 150 643 V000 1 III

    Revision

    Document identity: 1KGT 150 643 V000 1

    Revision: 0 Date: 09/2008Base version

    We reserve all rights in this document and in the information contained therein.Reproduction, use or disclosure to third parties without express authority is strictlyforbidden.

    Copyright 2009 Oleg Mamilovic.

  • 7/26/2019 e560 Harris Host

    4/36

  • 7/26/2019 e560 Harris Host

    5/36

    ABB AG 1KGT 150 643 V000 1 V

    Contents

    HOST COMMUNICATION INTERFACE WITH HARRIS-5000/5500/6000.. I

    REVISION .................................................................................................. III

    CONTENTS.................................................................................................V

    ABBREVIATIONS.....................................................................................VII

    INTRODUCTION........................................................................................IX

    1 PHYSICAL LAYER............................................................................1-1

    1.1 General .......................................................................................................... 1-1

    2 LINK LAYER .....................................................................................2-2

    2.1 General .......................................................................................................... 2-2

    2.2 Transmission ................................................................................................. 2-2

    3 APPLICATION LAYER .....................................................................3-1

    3.1 General .......................................................................................................... 3-1

    3.2 Information types ........................................................................................... 3-3

    3.3 Addressing..................................................................................................... 3-3

    4 DATA TYPES MONITORING DIRECTION ....................................... 4-1

    4.1 SPI Single Point Information....................................................................... 4-1

    4.2 DPI Double Point Information ..................................................................... 4-2

    4.3 STI Step Position Information..................................................................... 4-3

    4.4 BSI Bit String Information ........................................................................... 4-4

    4.5 ITI Integrated Totals Information ................................................................ 4-54.6 DMI Digital Measured Information .............................................................. 4-6

    4.7 AMI Analog Measured Information ............................................................. 4-7

    4.8 SEV System Event ..................................................................................... 4-8

    5 DATA TYPES CONTROLLING DIRECTION ....................................5-1

    5.1 SCO Single Command Output.................................................................... 5-1

    5.2 DCO Double Command Output.................................................................. 5-2

    5.3 RCO Regulation Command Output............................................................ 5-3

    5.4 ASO Analog Setpoint Output ...................................................................... 5-4

  • 7/26/2019 e560 Harris Host

    6/36

    Contents RTU560 Host Communication Interface Harris-5000/5500/6000

    ABB AG 1KGT 150 643 V000 1 VI

    5.5 DSO Digital Setpoint Output ....................................................................... 5-5

    5.6 BSO Bit String Output................................................................................. 5-6

    5.7 Power Fail Reset ........................................................................................... 5-7

    5.8 Accumulator freeze........................................................................................ 5-8

    6 TIME SYNCHRONIZATION ..............................................................6-1

    7 INTEROPERABILITY LIST ...............................................................7-1

    7.1 System or device ........................................................................................... 7-1

    7.2 Physical layer................................................................................................. 7-1

  • 7/26/2019 e560 Harris Host

    7/36

    ABB AG 1KGT 150 643 V000 1 VII

    Abbreviations

    ACC

    AMI

    ASO

    BSI

    BSO

    C&I

    COS

    CRC

    DCO

    DMI

    DPI

    DSO

    HCI

    IEC

    ITI

    OSI

    RCO

    R/L

    RTU

    SBO

    SCO

    SEV

    Accumulator

    Analog Measured Information

    Analog Setpoint command Output

    Bit String Information

    Bit String Output

    Control And Indication

    Change Of Input Status

    Cyclic Redundancy Check

    Double Command Output

    Digital Measured Information

    Double Point Information

    Digital Setpoint Output

    Host Communication Interface

    International Electrotechnical Commission

    Integrated Totals Input

    Open System Interconnection

    Regulation Command Output

    Raise / Lower

    Remote Terminal Unit

    Select Before Operate

    Single Command Output

    System Event

  • 7/26/2019 e560 Harris Host

    8/36

    Abbreviations RTU560 Host Communication Interface Harris-5000/5500/6000

    ABB AG 1KGT 150 643 V000 1 VIII

    SOE

    SPI

    STI

    Sequence Of Events

    Single Point Information

    Step Position Input

  • 7/26/2019 e560 Harris Host

    9/36

    ABB AG 1KGT 150 643 V000 1 IX

    Introduction

    Preface

    This document describes the functions of the host interface in RTU560 according toHarris5000/5500/6000 communication protocols.

    References

    [1] Harris corporationGeneral specification for series 6000 remote terminal unitCode ident no. 34369 : 985-1390

    [2] Harris corporation5000/5500/6000 functional interface requirements specificationCode ident no. 34369 : 985-1181

    Conventions

    In this document function codes of data types according to Harris 5000/5500/6000 are

    marked with angel brackets:

    Italic fonts with the heading Parameter are references to configuration parameter inRTUtil560. The parameter is followed by definitions in round brackets where to find thisparameter in RTUtil560.

    Example:

    Parameter: Link address(RTU560 Line parameter)

    In this document references to elements of the standard will be printed bold and inbrackets:[2, 7.4]

    The tables in the next chapters include lists of the functions, options and message typessupported according to the protocol structure given in Harris 5000/5500/6000 (EPA threelayer model) for

    the physical layer the link layer the application layer

  • 7/26/2019 e560 Harris Host

    10/36

    Introduction RTU560 Host Communication Interface Harris-5000/5500/6000

    ABB AG 1KGT 150 643 V000 1 X

    This layered model does not exactly apply to protocol Harris5000/5500/6000, but is

    adapted because of the structure of the host communication interface of RTU560.

  • 7/26/2019 e560 Harris Host

    11/36

    ABB AG 1KGT 150 643 V000 1 1-1

    1 Physical Layer

    1.1 General

    The possibility to use different transmission speeds in control and in monitor direction isnot supported by RTU560.

    Possible communication interfaces are according to Table 1-1.

    Interface

    Device

    CP 1 CP 2 CP A CP B

    560SLI02

    560CMU04

    RS232C,

    RS422

    RS232C,

    RS422

    RS232C

    RS485

    RS232C

    RS485

    560CMU02RS232C RS232C RS485 -----------------

    560ETH03 --------------------- ---------------------RS232C

    RS485

    RS232C

    RS485

    560CMU80 RS232C RS232C RS485 -----------------

    560CMU05RS485

    RS232C

    RS485

    RS232C

    RS485

    RS232C

    RS485

    RS232C

    Table 1-1: Communication interfaces - Harris 5000/5500/6000

    Parameter Range Default

    Interface type See Table 1-1

    Baud rate50, 75, 100, 110, 200, 300, 600, 1200, 1500, 2400,4800, 9600, 19200, 38400

    9600

    Modem control According to interface type Direct linkCarrier pre time Enable / Disable Disabled

    Table 1-2: Communication parameter Harris 5000/5500/6000

    Parameter Range Default

    Host number Position of single point information in the systemevent block. 1... 16

    1

    Table 1-3: Interface Parameter Harris 5000/5500/6000

  • 7/26/2019 e560 Harris Host

    12/36

    ABB AG 1KGT 150 643 V000 1 2-2

    2 Link Layer

    2.1 General

    Communication primitives like framing of messages, parity checks or retransmissions arehandled by the Harris-5000/5500/6000 protocol. These tasks are executed in the link layerthat connects RTUs and control systems or other RTUs. The selectable parameters haveto be calculated regarding the real communication technology.

    Option / Parameter Range of Values / Explanations Default

    Protocol type 5000, 5500 or 6000 5000Host offline timeout(in sec.)

    1..65535 300

    Gap supervision timein t0 steps

    -1..255 / -1 = no gap check 0

    Table 2-1: Table of Harris 5000/5500/6000 Link layer line parameters

    2.2 Transmission

    RTU mode: asynchronous

    1 start-bit, 6 data bits, 1 RTU address character identification bit, 1 parity bit and 1 stop bit.

    The basic message element in the Harris-5000/5500/6000 RTU protocol consists ofcharacter 10 bits length. Each character is composed of start bit, six data bits, a RTUaddress character identification bit, a parity bit and a stop bit.

    Characters are transmitted serially, from start bit through stop bit at baud rates determinedby the customer.

    The controlling station is primary station; controlled station (RTU) is secondary station.

  • 7/26/2019 e560 Harris Host

    13/36

    ABB AG 1KGT 150 643 V000 1 3-1

    3 Application Layer

    3.1 General

    Overview on type identifications for data elements of the application. defined in [1].

    The column RTU560 Type shows the type of data with must be configured in RTUtil560.

    Function Description Function Code RTU560 Types

    ADC and AccumulatorData Dump

    Returns data values for arequested number of points onany A/D or accumulator datapoints, and check for any statuschanges

    0

    Status Change CheckRTU can store up to 31 statuschanges for the C&I

    3

    Status Change DumpReturns the changes of statusreported by the Change Checkor Data Dump command

    4

    Status DumpReturns the current status of allpoints on requested statusports

    5

    Port Online Status ScanReturns port-online statuscharacter for each port

    12

    SOE Change DumpReturns SOE changespreviously indicated by the C&Iport status word

    18

    Table 3-1: Table of Harris 5000/5500/6000 RTU data request functions

    Function Description FunctionCode

    RTU560 Types

    Trip/Close Control PointArm

    Arm requested control point onthe Requested C&I Port forcontrol operation

    6

    Trip/Close Control PointOperate

    Execute previously armedcontrol point

    7

    AGC Raise/LowerFrom one to six points will becontrolled

    8RCO

    Set Point Control Arm Arm up to 12 bits to operate 9 ASO, DSO,BSO01/02/08/16

    Set Point Control OperateSent previously armed bits

    10ASO, DSO,BSO01/02/08/16

    Table 3-2: Table of Harris 5000/5500/6000 - RTU data control functions

  • 7/26/2019 e560 Harris Host

    14/36

    Application Layer RTU560 Host Communication Interface Harris-5000/5500/6000

    ABB AG 1KGT 150 643 V000 1 3-2

    Function Description FunctionCode

    Power FailReset

    Reset PF bit in all Port Status responses11

    BroadcastAccumulatorFreeze

    Freeze the current accumulator values atmultiple RTUs at the same time 15

    TimeSynchronization(SOE)

    Clock synchronization command17

    Time SyncAdjustment

    Adjust RTUs clock by the received offset19

    TimeSynchronization(Non SOE)

    Clock synchronization command withoutTime Sync Adjustment command 23

    Set FreezeInterval

    Establish or change the number of minutesbetween accumulator freeze times

    24

    Table 3-3: Table of Harris 5000/5500/6000 RTU control functions

  • 7/26/2019 e560 Harris Host

    15/36

    RTU560 Host Communication Interface Harris-5000/5500/6000 Application Layer

    ABB AG 1KGT 150 643 V000 1 3-3

    3.2 Information types

    The firmware supports the following Harris-5000/5500/6000 information types:

    Monitoring direction:- Single indication [1 bit]- Measured value [12 bit]- Counter value [12 bit]- Counter value [24 bit]- Counter value [32 bit]- Parallel data [16 bit]

    Control direction:- Double command- Regulating step command- Setpoint [12 bit]

    3.3 Addressing

    The sizes of the addressing fields can be configured as shown in the following table:

    Option / Parameter Range of Values / Default value

    RTU Address 1 .. 63 / 1, (0 is global address)

    PortHarris-5000: 0 .. 7 / 0Harris-6000: 0 .. 15 / 0

    PointHarris-5000: 0 .. 32 / 0Harris-6000: 0 .. 63 / 0

    Table 0-4: Table of Harris 5000/5500/6000 Address elements

  • 7/26/2019 e560 Harris Host

    16/36

  • 7/26/2019 e560 Harris Host

    17/36

    ABB AG 1KGT 150 643 V000 1 4-1

    4 Data Types Monitoring Direction

    4.1 SPI Single Point Information

    Binary system process information indicated by one bit

    Supported DataTypes

    Status Change Check Status Change Dump Status Dump SOE Change Dump

    AdditionalThe RTU will store SOE data only if it has been time synchronizedParameter: Use COS or SOE queue (1=COS, 2=COS and SOE, 3=SOE)

    Conversion of value

    RTU560 internal communication Protocol specific

    Off 0On 1

    Conversion of quality descriptors

    RTU560 internal communication Protocol specific

    BL Blocked -SB Substituted -NT Not Topical -IV Invalid Message Fail bit is set

    Conversion of cause of transmission

    RTU560 internal communication Protocol specific

    T Test -P/N Positive/negative confirmation -

    Spontaneous -Requested -Cause

    Interrogated -

  • 7/26/2019 e560 Harris Host

    18/36

    Data Types Monitoring Direction RTU560 Host Communication Interface Harris-5000/5500/6000

    ABB AG 1KGT 150 643 V000 1 4-2

    4.2 DPI Double Point Information

    Binary process information indicated by two bits.

    SupportedData Types

    Status Change Check

    Status Change Dump Status Dump SOE Change Dump

    Additional

    The value is transmitted with 2 sequenced points from the same portThe RTU will store SOE data only if it has been time synchronizedDPI Point must be on even addressParameter: Use COS or SOE queue (1=COS, 2=COS and SOE, 3=SOE)

    Conversion of value

    RTU560 internal communication Protocol specific

    First bit / pointnumber n

    Second bit / pointnumber n+1

    Intermediate 0 0Off 1 0

    On 0 1Indeterminate 1 1

    Conversion of quality descriptors

    RTU560 internal communication Protocol specific

    BL Blocked -SB Substituted -NT Not Topical -IV Invalid Message Fail bit is set

    Conversion of cause of transmission

    RTU560 internal communication Protocol specific

    T Test -P/N Positive/negative confirmation -

    Spontaneous -

    Requested -Cause

    Interrogated -

  • 7/26/2019 e560 Harris Host

    19/36

    RTU560 Host Communication Interface Harris-5000/5500/6000 Data Types Monitoring Direction

    ABB AG 1KGT 150 643 V000 1 4-3

    4.3 STI Step Position Information

    Binary process information indicated by 8 bits.

    SupportedData Types

    Data Dump

    AdditionalWithin 16 bit field15

    thbit is used as sign

    Conversion of value

    RTU560 internal communication Protocol specific

    Range min. -63 1000 0000 0011 11112... ... 0000 0000 0000 00002

    Range max. +63 0000 0000 0011 11112

    Conversion of quality descriptors

    RTU560 internal communication Protocol specific

    OV Overflow -BL Blocked -SB Substituted -NT Not Topical -

    IV Invalid Message Fail bit is setT Transient Bit -

    Conversion of cause of transmission

    RTU560 internal communication Protocol specific

    T Test -P/N Positive/negative confirmation -

    Spontaneous -Requested -Cause

    Interrogated -

  • 7/26/2019 e560 Harris Host

    20/36

    Data Types Monitoring Direction RTU560 Host Communication Interface Harris-5000/5500/6000

    ABB AG 1KGT 150 643 V000 1 4-4

    4.4 BSI Bit String Information

    Binary process information indicated by 8, 16 or 32 bit.

    Supported

    Data TypesData Dump

    Additional Used as parallel data within 16 bit field

    Conversion of value

    RTU560 internal communication Protocol specific

    Range min. 0 0... ...

    BSI8: Bit mask of 8 bit;range ... 255

    255

    BSI16: Bit mask of 16 bit;

    range ... 6553565535

    Range max. BSI32: Bit mask of 32 bit;range:

    0 6553565536... 4 294 967 295

    ...65535Not supported, 2

    17- 1 returned

    Conversion of quality descriptors

    RTU560 internal communication Protocol specific

    OV Overflow -BL Blocked -SB Substituted -

    NT Not Topical -IV Invalid Message Fail bit is set

    Conversion of cause of transmission

    RTU560 internal communication Protocol specific

    T Test -P/N Positive/negative confirmation -

    Spontaneous -

    Requested -Cause

    Interrogated -

  • 7/26/2019 e560 Harris Host

    21/36

    RTU560 Host Communication Interface Harris-5000/5500/6000 Data Types Monitoring Direction

    ABB AG 1KGT 150 643 V000 1 4-5

    4.5 ITI Integrated Totals Information

    Binary process information indicated by 12, 24 or 32 bit as a countered value.

    Supported

    Data Types

    Status Change Dump

    Status Dump

    AdditionalThe first reported Accumulator value is substituted with a timestamp instead ofthe frozen valueParameter: Can be configured as 12, 24 or 32 bit counter

    Conversion of value for 12 bit Accumulator

    RTU560 internal communication Protocol specific

    Range min. 0 0... ...

    4095 40954096 0 ( only first 12 bits are used )

    Range max. 4294967295 4095

    Conversion of value for 24 bit Accumulator

    RTU560 internal communication Protocol specific

    Range min. 0 0... ...

    16777215 1677721516777216 0 ( only first 24 bits are used )

    Range max. 4294967295 16777215

    Conversion of value for 32 bit Accumulator

    RTU560 internal communication Protocol specificRange min. 0 0... ...Range max. 4294967295 4294967295

    Conversion of quality descriptors

    RTU560 internal communication Protocol specific

    SEQ Sequence number -CY Carry -CA Adjusted -

    IV Invalid Message Fail bit is set

    Conversion of cause of transmission

    RTU560 internal communication Protocol specific

    T Test -P/N Positive/negative confirmation -

    Spontaneous -Requested -Cause

    Interrogated -

  • 7/26/2019 e560 Harris Host

    22/36

    Data Types Monitoring Direction RTU560 Host Communication Interface Harris-5000/5500/6000

    ABB AG 1KGT 150 643 V000 1 4-6

    4.6 DMI Digital Measured Information

    Binary process information indicated by 8 or 16 bit used as a measured value from digitalinputs in normalized format.

    SupportedData Types

    Data Dump

    Additional None

    Conversion of value

    RTU560 internal communication Protocol specific

    Range min. -100% 10000000000020% 0000000000002

    Range max. +100% 0111111111112

    Conversion of quality descriptors

    RTU560 internal communication Protocol specific

    OV Overflow -BL Blocked -

    SB Substituted -NT Not Topical -

    IV Invalid Message Fail bit is set

    Conversion of cause of transmission

    RTU560 internal communication Protocol specific

    T Test -P/N Positive/negative confirmation - Irrelevant -

    Spontaneous -Requested -Cause

    Interrogated -

  • 7/26/2019 e560 Harris Host

    23/36

    RTU560 Host Communication Interface Harris-5000/5500/6000 Data Types Monitoring Direction

    ABB AG 1KGT 150 643 V000 1 4-7

    4.7 AMI Analog Measured Information

    Analog process information indicated by 8 or 16 bits used as a measured value fromanalog inputs in normalized or scaled format.

    SupportedData Types

    Data Dump

    Additional None

    Conversion of value

    RTU560 internal communication Protocol specific

    Range min. -100% 10000000000020% 0000000000002

    Range max. +100% 0111111111112

    Conversion of quality descriptors

    RTU560 internal communication Protocol specific

    OV Overflow -BL Blocked -

    SB Substituted -NT Not Topical -

    IV Invalid Message Fail bit is set

  • 7/26/2019 e560 Harris Host

    24/36

    Data Types Monitoring Direction RTU560 Host Communication Interface Harris-5000/5500/6000

    ABB AG 1KGT 150 643 V000 1 4-8

    4.8 SEV System Event

    Binary system process information indicated by one bit:

    Supported DataTypes

    Status Change Check

    Status Change Dump Status Dump SOE Change Data

    AdditionalSystem events are handling as SPI data typesThe RTU will store SOE data only if it has been time synchronizedParameter: Use COS or SOE queue (1=COS, 2=COS and SOE, 3=SOE)

    Conversion of value

    RTU560 internal communication Protocol specific

    Off 0On 1

    Conversion of quality descriptors

    RTU560 internal communication Protocol specific

    BL Blocked -SB Substituted -NT Not Topical -IV Invalid Message Fail bit is set

    Conversion of cause of transmission

    RTU560 internal communication Protocol specific

    T Test -

    P/N Positive/negative confirmation -Spontaneous -

    Requested -Cause

    Interrogated -

  • 7/26/2019 e560 Harris Host

    25/36

    ABB AG 1KGT 150 643 V000 1 5-1

    5 Data Types Controlling Direction

    5.1 SCO Single Command Output

    Binary process command (one bit)

    SupportedData Types

    Control Point Arm Control Point Operate

    CommandAuthority

    None

    Additional -

    Conversion of value

    RTU560 internal communication Protocol specific

    off Tripon Close

    Conversion of quality descriptors

    RTU560 internal communication Protocol specific

    SE Select / ExecuteSelect Control Point Arm Execute Control Point Operate

    Conversion of cause of transmission

    RTU560 internal communication Protocol specific

    T Test -P/N Positive/negative confirmation Correct Status Change

    Activation < - -Activation Confirmation - > -

    Deactivation < -Control Point Operate is not the nextcommunication on the channel

    Deactivation Confirmation - > -Activation Termination - > -

    Cause

    Negative Confirmation - >Correct Status ChangeVerification must be done by Change Check or Data Dump commands

  • 7/26/2019 e560 Harris Host

    26/36

    Data Types Controlling Direction RTU560 Host Communication Interface Harris-5000/5500/6000

    ABB AG 1KGT 150 643 V000 1 5-2

    5.2 DCO Double Command Output

    Binary process command

    Supported

    Data Types

    Control Point Arm

    Control Point Operate CommandAuthority

    None

    Additional -

    Conversion of value

    RTU560 internal communication Protocol specific

    Off TripOn Close

    Conversion of quality descriptors

    RTU560 internal communication Protocol specific

    SE Select / ExecuteSelect Control Point Arm Execute Control Point Operate

    Conversion of cause of transmission

    RTU560 internal communication Protocol specific

    T Test -P/N Positive/negative confirmation Correct Status Change

    Activation < - -

    Activation Confirmation - > -Deactivation < -

    Control Operate is not the nextcommunication on the channel

    Deactivation Confirmation - > -

    Activation Termination - > -

    Cause

    Negative Confirmation - >Correct Status ChangeVerification must be done by Change Check or Data Dump commands

  • 7/26/2019 e560 Harris Host

    27/36

    RTU560 Host Communication Interface Harris-5000/5500/6000 Data Types Controlling Direction

    ABB AG 1KGT 150 643 V000 1 5-3

    5.3 RCO Regulation Command Output

    Regulation step command (two bits)

    Supported

    Data Types

    Raise/Lower

    CommandAuthority

    None

    Additional

    If the Command Handoff Count value for associated point is 0 (No-Op) then itwill be ignoredIf a command is received for a port while a previous raise/lower command isactive the RTU will generate a master station response then ignore the newcommandThe response signifies only that the operate command was communicatedwithout errorsIt is NOT recommended to use more than one command at once otherwise itspossible that other commands will not be executed if they are send to thesame I/O module

    Conversion of value

    RTU560 internal communication Protocol specific

    Off LowerOn Raise

    Conversion of quality descriptors

    RTU560 internal communication Protocol specific

    SE Select / Execute Only execute is supported

    Conversion of cause of transmission

    RTU560 internal communication Protocol specific

    T Test -

    P/N Positive/negative confirmationMust be verified with Data Dump command

    Activation < - -

    Activation Confirmation - > -Deactivation < - -

    Deactivation Confirmation - > -Activation Termination - > -

    Cause

    Negative Confirmation - >Must be verified with Data Dump command

  • 7/26/2019 e560 Harris Host

    28/36

    Data Types Controlling Direction RTU560 Host Communication Interface Harris-5000/5500/6000

    ABB AG 1KGT 150 643 V000 1 5-4

    5.4 ASO Analog Setpoint Output

    Analog process command (16 bit signed number)

    Supported

    Data Types

    Set Point Arm

    Set Point OperateCommandAuthority

    None

    AdditionalThe response signifies only that the command was communicated withouterrors

    Conversion of value

    RTU560 internal communication Protocol specific

    Range min. -100% 00% 2048

    Range max. +100% 4095

    Conversion of quality descriptors

    RTU560 internal communication Protocol specific

    SE Select / ExecuteSelect Set Point Arm Execute Set Point Operate

    Conversion of cause of transmission

    RTU560 internal communication Protocol specific

    T Test -P/N Positive/negative confirmation Not used, always immediately responded

    Activation -Activation Confirmation -Deactivation -

    Deactivation Confirmation -

    Cause

    Negative Confirmation -

  • 7/26/2019 e560 Harris Host

    29/36

    RTU560 Host Communication Interface Harris-5000/5500/6000 Data Types Controlling Direction

    ABB AG 1KGT 150 643 V000 1 5-5

    5.5 DSO Digital Setpoint Output

    Binary process command (8 or 16 bit signed number)

    SupportedData Types

    Set Point Arm Set Point Operate

    CommandAuthority

    None

    AdditionalThe response signifies only that the command was communicated withouterrors

    Conversion of value

    RTU560 internal communication Protocol specific

    Range min. -100% 0

    0% 2048Range max. +100% 4095

    Conversion of quality descriptors

    RTU560 internal communication Protocol specific

    SE Select / ExecuteSelect Set Point Arm Execute Set Point Operate

    Conversion of cause of transmission

    RTU560 internal communication Protocol specific

    T Test -P/N Positive/negative confirmation Not used, always immediately responded

    Activation -

    Activation Confirmation -Deactivation -

    Cause

    Deactivation Confirmation -

    Negative Confirmation -

  • 7/26/2019 e560 Harris Host

    30/36

    Data Types Controlling Direction RTU560 Host Communication Interface Harris-5000/5500/6000

    ABB AG 1KGT 150 643 V000 1 5-6

    5.6 BSO Bit String Output

    Binary process command (1, 2, 8, and 16 bit unsigned number)

    SupportedData Types

    Set Point Arm Set Point Operate

    CommandAuthority

    None

    AdditionalFor BSO16 only first 12 bits are usedThe response signifies only that the command was communicated withouterrors

    Conversion of value

    RTU560 internal communication Protocol specific

    Range min. 0 0... 4095 4095

    value 4096 4095

    Range max. 65535 4095

    Only first 24 bits are used.

    Conversion of quality descriptors

    RTU560 internal communication Protocol specific

    SE Select / ExecuteSelect Set Point Arm Execute Set Point Operate

    Conversion of cause of transmission

    RTU560 internal communication Protocol specific

    T Test -P/N Positive/negative confirmation Not used, always immediately responded

    Activation -

    Activation Confirmation -Cause

    Negative Confirmation -

  • 7/26/2019 e560 Harris Host

    31/36

    RTU560 Host Communication Interface Harris-5000/5500/6000 Data Types Controlling Direction

    ABB AG 1KGT 150 643 V000 1 5-7

    5.7 Power Fail Reset

    Process command to reset PF bit in all responses to the master

    SupportedData Types

    Power Fail Reset

    CommandAuthority

    None

    AdditionalIf the RTU has power fail restarted, the PF bit will remain set until a Power FailReset message is received by the RTU

    Conversion of quality descriptors

    RTU560 HCI internal Protocol specific

    SE Select / Execute Only execute supported

    Conversion of cause of transmission

    RTU560 internal communication Protocol specific

    T Test -

    P/N Positive/negative confirmation -

    Activation -Activation Confirmation -Cause

    Negative Confirmation -

  • 7/26/2019 e560 Harris Host

    32/36

    Data Types Controlling Direction RTU560 Host Communication Interface Harris-5000/5500/6000

    ABB AG 1KGT 150 643 V000 1 5-8

    5.8 Accumulator freeze

    Command to Freeze the current accumulator values

    Supported

    Data Types

    Broadcast Accumulator Freeze

    Set Freeze interval CommandAuthority

    None

    Additional

    Broadcast Accumulator Freeze does not generate a response

    The Freeze Time Interval command is used to establish or change thenumber of minutes between accumulator freeze time (1, 2, 3, 4, 5, 6, 10, 12,15, 20, 30 or 60 minutes). Freeze time 0 will perform immediate freezeoperation without affecting current freeze cycle. Freeze time 63 is used to stopfreeze processing. If an interval of 0 or 63 is used and freeze processing is notyet active, the interval is not validThe message fail bit will remain set until the first accumulator freeze operationhas occurredThe first reported Accumulator has value substituted with a time of the last

    freeze (minutes after midnight) or F0016if it was not been frozen yet

    Conversion of quality descriptors

    RTU560 HCI internal Protocol specific

    SE Select / Execute Only execute supported

    Conversion of cause of transmission

    RTU560 internal communication Protocol specific

    T Test -

    P/N Positive/negative confirmationValidity code has value 61 if time interval isnot valid

    Activation -

    Activation Confirmation -Cause

    Negative Confirmation -

  • 7/26/2019 e560 Harris Host

    33/36

    ABB AG 1KGT 150 643 V000 1 6-1

    6 Time Synchronization

    Parameter: Time administration (RTU560-Parameter)

    SupportedData Types

    Time Synchronization (SOE) Time Sync Adjustment (SOE) Time Synchronization (Non-SOE)

    Value Complete time information in milliseconds past midnightCommandAuthority

    None

    Additional

    Time Synchronization (SOE) has delay 100 ms between receiving the

    last bit of the LRC character, and starting the first bit of its response. Thiscommand must be followed by the Time Sync Adjustment

    Time Synchronization (Non-SOE) is standalone command and itsoperated without Time Sync Adjustment command

    Conversion of cause of transmission

    RTU560 host internal Protocol specific

    T Test -P/N Positive/negative confirmation Time Sync Out-of-Range value returned

    Spontaneous -

    Activation -

    Activation Confirmation -Cause Negative confirmation Time Sync Out-of-Range bit is set

  • 7/26/2019 e560 Harris Host

    34/36

  • 7/26/2019 e560 Harris Host

    35/36

    ABB AG 1KGT 150 643 V000 1 7-1

    7 Interoperability List

    The selected parameters are marked in the white boxes as follows:

    7.1 System or device

    System definition

    Controlling station definition

    Controlled station definition

    7.2 Physical layer

    (Network-specific parameter)

    Transmission speed (baud)

    Unbalanced interchangeCircuit V.24/V.28 Circuit V.24/V.28Standard Recommended if speed >1 200 bit/s

    50 200 1500 19200

    75 300 2400 38400

    100 600 4800

    110 1200 9600 (default)

    Function is used as standardized (default)

    Function is not used

  • 7/26/2019 e560 Harris Host

    36/36

    Interoperability List RTU560 Host Communication Interface Harris-5000/5500/6000

    Selection of standard functions

    !"#

    $ !%" !"#

    & !%"

    '

    ( )" )

    * )" ) ""

    + , -)"."

    / " )

    0 " ) ""

    00 " 1) -""

    02 3.)"

    0' 1""4"

    0* )" 5!)4) 67

    0+ !%"

    0/ )" 5 8" 67

    2 "%"

    20 ))

    22 2&3) )5 "%"

    2$ )" 5!)4) 69 7

    2& " 1""4" ":


Recommended