of 48
7/29/2019 Ear Thing Concepts
1/48
EARTHING CONCEPTS
7/29/2019 Ear Thing Concepts
2/48
2
Earthing in a EHV Substation
Providing adequate Earthing in asubstation is an important safety measure.
Earthing means connecting the electrical
equipment to the general mass of earth oflow resistance.
Objective is to provide under and around
the substation a surface of uniformpotential
-- At near zero or absolute earth potential
7/29/2019 Ear Thing Concepts
3/48
3
Earthing in a EHV Substation
1. Objective:
The touch and step potential shall be within
limits under all conditions including fault
condition
Grounding resistance shall be lower.
Effective earthing system shall aim at
providing protection to life and propertyagainst dangerous potentials under fault
conditions
7/29/2019 Ear Thing Concepts
4/48
4
Earthing in a EHV Substation
I.E.Rules 1956
Rule 92 Every substation /generating station exposed to
lightning shall adopt efficient means for divertingthe electrical surges due to lightning to earth
Earth lead of any lightning arrestor shall not passthrough any iron or steel pipe.
It shall be taken directly, as far as possible, to aseparate earth electrode and/or junction of the
earth mat. Bends Shall be avoided where ever practicable
Earth screen if provided for lightning protectionshall be connected to main earth grid.
7/29/2019 Ear Thing Concepts
5/48
5
Earthing in a EHV Substation
I.E.Rules 1956 Functioning of earthing in a substation
It shall be capable of passing maximum earth fault current
The passage of fault current does not result in any thermalor mechanical damage to the insulation of connected plant /equipment
Every exposed conductor part and extraneous conductivepart may be connected to the earth.
There is no danger to the personnel
Ensure equi-potential bonding within the power system
No dangerous potential gradients (step or touch or transferpotentials) shall occur under normal or abnormal operatingconditions
To minimize electromagnetic interference between powerand control/ communication system
7/29/2019 Ear Thing Concepts
6/48
6
Earthing System
Points to be earthed in a substation The neutral point of each separate system
should have an independent earth, in turninterconnected with the station grounding mat.
Equipment frame work and other non-currentparts (two connections)
All extraneous metallic frame works notassociated with equipment ( two connections)
Lightning arrestors should have independentearths, in turn connected to the stationgrounding grid.
7/29/2019 Ear Thing Concepts
7/48
7
Earthing SystemPoints to be earthed-contd
Over head lightning screen shall also be
connected to main ground mat.
Operating handles of Isolators with a auxiliary
earth mat underneath, if necessary. Peripheral fencing
Buildings inside the switch yard.
Transformer Neutrals shall be connecteddirectly to the earth electrode by twoindependent MS strips
7/29/2019 Ear Thing Concepts
8/48
8
Earthing and grounding -distinction
Grounding:- connection of current carrying parts
to ground. Ex :Generator or transformer neutral.
This is for equipment safety.
In a resistance grounded system it limits thecore damage in stator of rotating machines.
In solidly grounded system substantial ground
fault current flows enabling fault detection andfaster clearance.
7/29/2019 Ear Thing Concepts
9/48
9
Earthing and grounding -distinction
Earthing:- connection of non currentcarrying parts to ground. Ex : Metallicenclosure.
This is for human safety. Earthing system plays no role under
balanced power system conditions.
Under ground fault conditions, enablesground fault current to return back tosource without endangering human safety.
7/29/2019 Ear Thing Concepts
10/48
10
Basics of Earthing
Resistivity of earth
Resistivity of earth:-
Mother earth is a bad conductor.
Resistivity is normally around 100 ohm mt.
GI of 65x10mm section will have same resistance
as copper of 25x4mm section.
Corresponding figure for earth is 800x800mt
(158acres) Metallic conductor is a preferred alternative to
earth to bring the fault current back to source.
7/29/2019 Ear Thing Concepts
11/48
11
Electric field Earth resistance
Current flows through a series of hemi-sphericalshells of earth of continuously increasing crosssections.
Almost 95% of final resistance is contributed by soilwithin 5mts of the electrode.
If current is discharged from a grid towards anothergrid at B100 km away, only soil with in 5 to10 mts of
the electrode contributes maximum resistance.
Earth beyond, offers very minimum resistance.
This is the concept of treating the soil around
electrode of an earth pit.
7/29/2019 Ear Thing Concepts
12/48
12
Electric field Earth resistance
Earth with its huge mass offers equi-potential everywhere
A very large charge is required to changeearth potential everywhere
Disturbance due to current injection at apoint is felt, only locally.
7/29/2019 Ear Thing Concepts
13/48
13
Substation earthing
Design of Earth mat
Design depends upon the following parameters
Durational and magnitude of the fault current Resistivity of the surface layer of the soil
Resistivity of the soil Magnitude of current that the human body cansafely carry
Permissible earth potential raise that may takeplace due to the fault conditions
Shock duration Material of Earth- mat conductor. Earth- mat geometry
7/29/2019 Ear Thing Concepts
14/48
14
Substation earthing
Design of Earth mat
Parameters for the calculation of Maximumpermissible step and touch potential Fault duration :- Fault clearing time of back up
protection is adopted Modern protection systems provides for fast
acting back up protection Considerable saving can be made by optimizing
the size of the conductor of earthing grid by
considering lesser fault duration. These will change the earth potential raise due to
which Step and Touch potentials arise.
7/29/2019 Ear Thing Concepts
15/48
15
Earth mat parameters
Let go current
Maximum safe current a person cantolerate and still release grip of anenergised object, using muscles affected
by the current The magnitude of let go current adopted in
calculating maximum permissible step andtouch potentials (As per IEEE 80 1976)
for man 9 milli ampsfor woman 6milli amps
7/29/2019 Ear Thing Concepts
16/48
16
Substation Earthing
Non-fibrillation current
Developed by Dalziel and approved by AIEE80-1963Magnitude of power frequency alternating current
(mA) that a human body of average weight( 50kgsto 70 kgs) can with stand without ventricular
fibrillation,
I =0.116 for a body of 50kgs wt.
t
I =0.157 for a body of 70kgs wt.
t
Av. Value of human body resistance (dry) 8 to 9K-ohms
Adopted value for designing Earthing system1Kohms
7/29/2019 Ear Thing Concepts
17/48
17
Substation Earthing
Non fibrillation current contd Non fibrillating current adopted for earth grid design
in India.Magnitude of power frequency alternating currentthat a human body of average weight( 50kgs to 70kgs) can with stand without ventricular fibrillation,
I =0.165t
I = rms current through human body in amps t =durtation of shock in seconds
Assumption /considerations in deriving the aboveequation
--The duration of shock is from 8 milli-seconds to 3seconds
7/29/2019 Ear Thing Concepts
18/48
18
Substation Earthing
Fault duration and magnitude
During a line to earth or double line earth fault
current through earthing system causes
a) Heating of earthing conductor
b) Potential gradients in the soil
For earthing design single line to ground fault
is considered as
Most of the faults are of this type Current through earth in case of single line
to earth fault is higher that in the later case.
7/29/2019 Ear Thing Concepts
19/48
19
Substation Earthing
Fault duration and magnitude-contd.
For determining maximum permissible step and
touch potentials
Fault duration corresponding to maximum fault
clearing time of back up protection relays areconsidered
Normally in modern sub station clearance time
of primary protection is 0.2 sec, ie., 200 milli sec
and clearance time for back up protection is 0.5
sec, ie., 500 milli sec
A fault duration time of 0.5 sec (500 mill sec) is
adopted for design
7/29/2019 Ear Thing Concepts
20/48
20
Earthing conductor once placed under
earth may not be inspected normally.
Prudent to make it capable of carrying
maximum possible current for maximum
time.
If felt necessary and if it is economical,
fault duration of 1 sec can be adopted for
design.
Substation Earthing
Fault duration and magnitude-contd.
7/29/2019 Ear Thing Concepts
21/48
21
Substation Earthing
Soil resistivity
To design most economically and technicallysound earthing system accurate data of soilresistivity and its variation with in substation soilis essential.
Resistivity of soil in many substations has beenfound varying -at times between 1 and 10,000ohm meters.
Variation in soil Resistivity with depth is morepredominant as compared to variation inhorizontal distances.
7/29/2019 Ear Thing Concepts
22/48
22
Substation Earthing
Soil resistivity Large variations in stratification of earth layers will
result in large variations in earth resistivity.
Highly refined techniques for the determination of
resistivity of homogeneous soil( non
uniform soil)is available.
As resistivity of soil varies widely based on moisturecontent earth resistivity readings to be obtained in
summer or dry season.
Weiner's 4 electrode method is generally adopted fortesting.
7/29/2019 Ear Thing Concepts
23/48
23
Substation Earthing- Soil resistivity
Weiner's 4 electrode method
Earth resistivity tests shall be carried out at leastin 8 directions
If results obtained indicate wide variation, test
shall be conducted in more number directions. Four electrodes are driven into earth along a
straight line at equal intervals.
Current is passed through two outer electrodes
and earth. Voltage difference is measured between two
inner electrodes.
7/29/2019 Ear Thing Concepts
24/48
24
Substation Earthing
Soil resistivity
Current flowing through the earth
produces are electric field proportional to
current density and resistivity of soil.
Voltage measured is proportional to the
ratio of voltage to the current i.e R
= 4sR - __s__
1+ 2s___ s+e
s+4e
7/29/2019 Ear Thing Concepts
25/48
25
Substation Earthing
Soil resistivity Where
= Resistivity of soil in ohm-meters= Distance between two successive electrodesin meter
R= Ratio of voltage to current or electroderesistances in ohm
e= depth of burial of electrodes in meters
In case depth of burial of the electrodes in theground (e) is negligible compared to electrodesspacing. This formula is the adjusted =2sR(This formula is normally adopted in AP Transco Ltd.)
7/29/2019 Ear Thing Concepts
26/48
26
Substation Earthing
Measurement of Soil resistivityThere point method Two temporary electrodes spikes are driven in to the
earth at 150ft and 75ft respectively from earthelectrode under test.
Former is for current and the later is for voltage. Ohmic values of earth electrode resistances are
obtained using earth meagerR = log 10 (4L/P) where
2
R = Electrode resistance in ohmL = Length in cms of the rod driven under groundD = Dia in cms of the rod
= Earth resistivity in ohm-meter
7/29/2019 Ear Thing Concepts
27/48
27
Resistance of the earthing system
R = +
4r L
= Soil resistivity in ohm meter
L = Length of conductor buried in meters
r = radius in meters of circle having the same
area as that occupied by the earth mat.
The value of the R should be less than theimpendence to ground values stated below
7/29/2019 Ear Thing Concepts
28/48
28
Earthing System
Permissible resistance of earthing system
Primary requirements : Impendence to ground
(resistance of earthing system)
Small substations 2 Ohms
EHV substations up to 220 kV 1 Ohm
Power stations and 400 kV substations 0.5 Ohms
Distribution transformer - 5 Ohms.
In order to avoid abnormal shift of the neutral
potential, earth resistance of the station earthing
system shall be normally less than or equal to 1ohm.
7/29/2019 Ear Thing Concepts
29/48
29
Substation Earthing
Step and touch potential
Step potential - Difference in surfacepotentials experienced by a man bridging adistance of 1 mt with his feet, with outcontracting any other grounded object.
Touch potential- potential difference betweenthe earth potential raise and the surfacepotential at the point where a person isstanding touching an earthed structure.
Tolerable touch potential of human body isless than tolerable step potential.
7/29/2019 Ear Thing Concepts
30/48
30
Substation Earthing
Step and touch potential-contd
In any switch yard, chances of exposure toTouch potential is higher than that to steppotential.
Resistance offered by the feet of a personagainst Touch potential is much lesscompared to that against Step potential.
Hence Touch potential is more critical fordesign while Step potential is usuallyacademic.
7/29/2019 Ear Thing Concepts
31/48
31
Substation Earthing
Step and touch potential- contd.
Step potential is independent of the diameter ( cross-section) of the earthing conductor.
For 400% increase in diameter, reduction in Touchpotential is only 35%.
Thus cross- section has minor influence on Touchand Step potentials.
Length of earthing conductor has significant effecton Touch and Step potentials.
7/29/2019 Ear Thing Concepts
32/48
32
Substation Earthing
Step and touch potential Tolerable Step and touch potentials (CBIP Publication no.
223)
E step (LMT) = 0.116 (1000+1.5Cs(hs.K.)s) (volts)t
E touch (LMT) = 0.116 (1000+ 6Cs.(hs.K.)s) (volts)
tWhere Cs= Reduction factor for de-rating normalvalue of surface layer resisvity, a function of K.
K= -- s+ s
, sare resistivities of soil and surface layer respectively.cs =1 when crushed rock has resistivity equal to that of soil.
Otherwise it is derived from reference graphs ( Cs. vs hs.)
hs =thickness of surface layer in meter.t = Duration of shock current flow in secs.
7/29/2019 Ear Thing Concepts
33/48
33
Substation Earthing
Step and touch potential-contd.
Tolerable Step and touch potentials as adopted by certain
utilities.
E step (LMT) = IB(RG +1.5Cs.s) (volts)------(1)
E touch (LMT) = IB (RG + 6Cs.s) (volts) ------(2)RG= body resistance in Ohms= 1000
IB= Permissible body current of human beings.
Cs=Reduction factor(0 to 1)=1-(k / (2h+0.09) ------(3)
k=0.09x(1- /s)
s= surface layer resistivity ( taken as 2000 ohm- mt.) h= Thickness of gravel in cm.
= Soil resistivity ( taken as 100 ohm- mt.)
7/29/2019 Ear Thing Concepts
34/48
34
Substation Earthing
Step and touch potential-contd. Sample calculation forE step (LMT) and E touch (LMT) Data
Weight of the man =70kgs
Fault duration =0.5 sec
Resistivity Soil = =100 ohm-mt, Surface layer =s=2000ohm-mt,h= Thickness of gravel in cm.=10cm
From (3), Cs=0.705
From table in slide 24 for a 70 kgs man and for a shock duration of
0.5 sec IB= 222mAFrom (1) E step (LMT)= 691V
From (2) E touch (LMT) =2100V
E thi S t
7/29/2019 Ear Thing Concepts
35/48
35
Methodology of design as adopted in APTransco
Size of earth mat conductor (steel strip ) Shall be :
A (Steel) = 0.0013 x I t sq. mm for bolted joints
= 0.011 x I t sq. mm for welded joints
Where A = Area of Cross sectionI = Fault current in Amps. at the station
= Fault MVA x 1000
3 x system kV
and t = Time in seconds during which current is
applied
Earthing System
Size of earth mat conductor
7/29/2019 Ear Thing Concepts
36/48
36
Earthing materials
Determination of size of conductor for earth mat.- Based on thermal stability determined by an approximate
formula of IEEE - 80-1986
A = I/ ( TCAP x10 4) I n (Ko + Tm)
tc x irr (Ko + Ta)Where
In case of steel
A = I x 12.3 tc mm for welded joints= I x 15.13 tc mm for bolted joints
In case tc = Duration of current =1secA = 12.3 x I mm for welded joints
= 15.3 x I mm for bolted joints
7/29/2019 Ear Thing Concepts
37/48
37
Earthing materials
Based on Mechanical ruggedness of conductor and for easy installation.
Ratio of max width to thickness =7.5
Thickness for flat shall not be less than = 3mm (Asadopted 5to 6mm)
Minimum dia for steel rod = 5mm
Standard sizes of conductor as, As per IS 1730 1989(I)10 x 6mm (II)20x6mm
(II)30 x 6mm (IV)40 x 6mm
(IV)50 x 6mm (VI)60 x 6mm
(VI)50 x 8mm (VIII)65 x 8mm(IX)75 x 12mm (X)100 x 16mm
- For 33kV Substations 75x8mm and 50x6mm
7/29/2019 Ear Thing Concepts
38/48
38
Earthing materialsUp to 220 kV substation
Earth mat
a) Peripheral or main earth mat : 100x 16m MS flat
b) Internal earth mat : 50x8m MS flat placed at 5 m apart
c) Branch connections : cross section not less than64.5 sq.m
d) Raisers : 50x8m MS flat
For 400 kV substation
Earth mat
a) Peripheral or main earth mat :40mm dia MS rod of 3mt. length
b) Internal earth mat 50x8mm MS flat placed at 5m apartc) Raisers : 50x8m MS flat
Where necessary, 40mm rods will be driven in to earth verticallyalong the periphery of the earth mat.
7/29/2019 Ear Thing Concepts
39/48
39
Pipe earthing
a) EHT Substations :(i) Cast iron pipes 125mm in diameter2.75 m long and not less than 9.5 mm
thick.
(ii) Pipes 50.8 mm in dia and
3.05 m long
1. Joints are to be kept down to the minimumnumber
2. All joints and connections in earth grid are to bebrazed, riveted, sweated, bolted or welded.
3. For rust protection welds shall be treated withBarium chromate.
7/29/2019 Ear Thing Concepts
40/48
40
Earthing
2. Welded surfaces to be painted with red lead
and aluminium paint and then with bitumen.
3. Joints to be broken periodically shall be bolted
and joint faces tinned.4. All exposed steel earthing conductors should
be protected with bituminous paint
5. All joints in steel earthing system shall be
welded except joints to be removed for testing
shall be bolted.
7/29/2019 Ear Thing Concepts
41/48
41
Earthing system
Lowering of earth impedance
2) Lowering of earth impedanceIn places where soil resistivity is high steps to be taken to reduceearth impedance by one or combination of following:-
a. Connection of substation grid with a remote ground grid andadjacent grounding facilities.
b. Use of deep driven ground rods or longer ground rods or maximumnumber of ground rods along the perimeter of the earth grid.c. Use of foundation rods as auxiliary grids where feasibled. Formation of auxiliary grids if soil of low earth resistivity is available
close bye. Max. touch potential occurs in the corner of mesh of the grid. No
equipment are to be kept in such areas. higher values of touchpotential than the tolerable limit can be accepted if step potentialare within permissible limits
f. If equipment is to be kept at corners of the mesh. Auxiliary grids areto be created at those corner to limit touch potential.
7/29/2019 Ear Thing Concepts
42/48
42
Earthing System
Earthing of switch yard fencing
Two methods of fence earthinga) Extension of substation earth grid up to 0.5 to 1.5 m beyond the
fence, bonding the fence to the grid at regular intervals.b) Keeping the fence beyond the perimeter of the switch yard
earthing grid, providing its own earthing system not connectingto the main earthing grid.
In the former case substantial reduction in the effectivesubstation earthing resistance is possible but at additionalcost.
In the later case any inadvertent connection could give rise todangerous potential under fault condition unless special care istaken.
Electrical isolation of fence into short section with individualearthing is required where fence is closer to a single phasereactor or an electrical plant generating large electromagneticfields.
7/29/2019 Ear Thing Concepts
43/48
43
Earthing System
Earthing of switch yard fencing- con
Methods of earthing of fencing As per CBIP reportA. Design permits extension of earth mat within 1.5mt inside
perimeter fencing
Electrical isolation of fencing can be ensured Isolate fencing for earth mat Running of independent earth conductor underneath boundary
and connecting it to fencing at frequent intervals.
B. Design permits extension of earth mat up to fencing Calculated touch potential within safe limit
Extending the earth mat up to perimeter fencing and connectingthe fencing at frequent intervals to earth mat
Spreading crushed metal 1.5mt beyond fencing
7/29/2019 Ear Thing Concepts
44/48
44
Earthing System
Earthing of switch yard fencing- con
C.
Design permits extension of earth mat up tofencing
Calculated touch potential beyond the fenceabove the permissible limit for touch potential
Termination of earth mat within 1.5 mt offencing
Fence electrically isolated and independentlyearthed by running an earthed conductorunderneath the fence connecting it to the fenceat frequent intervals
f
7/29/2019 Ear Thing Concepts
45/48
45
Earthing of gas insulated
substation
In GIS multi-components like buses, switch gearassociated equipment are present in an earthedmetallic housing
They are subjected to same magnitude of faultcurrent and require low impendence earthing
Compared to a conventional substation, as GISrequires only 25% of land area design of earthmat is comparatively difficult.
Metallic enclosures of GIS have inducedcurrents, specially during internal earth faults.
E hi f i l d
7/29/2019 Ear Thing Concepts
46/48
46
Earthing of gas insulated
substation Inductive voltage drop occurring with GIS assembly shall be
taken into account for the design of earth mat
Touch voltage criteria = (FA)2+(EG)2 < ET (max)Where FA = Actually calculated touch voltage
EG= Max value of metal to metal voltage differenceon and between GIS enclosures or
between GIS enclosures and supportingstructures
ET (max) = maximum permissible touchvoltage
Metallic enclosures of GIS may be continuous or not In either case provision of earth bond frequently is essential to
minimize hazards of touch potential In addition, earthing of GIS structures and service platforms at
frequent intervals are to be done.
S b t ti E thi
7/29/2019 Ear Thing Concepts
47/48
47
Substation Earthing
Case studies
Karimnagar132kV ss
Kamalapuram 132kV ssfencing givingshock
Auxiliary Earth grid at RTPP
7/29/2019 Ear Thing Concepts
48/48
48
Thank you