07INDIVIDUALCATALOG
EARTHLEAKAGECIRCUITBREAKERS
SG series Motor-operated breakers
EG series Protective relaysBRR, RRD, EL
HG series
4-poleSG and EG series
Handle-operated type LOWVOLTAGE
EQUIPMENTUp to 600 Volts
from D&C CATALOG 19th EditionRevised
LOW VOLTAGE PRODUCTS Up to 600 VoltsIndividualcatalog No.
01 Magnetic Contactors and StartersThermal Overload Relays, Solid-state Contactors
02
Industrial RelaysIndustrial Control RelaysTime Delay Relays
DUO seriesManual Motor Starters and Contactors Combination Starters
Pushbuttons, Selector Switches, Pilot Lights
AS-Interface, Limit SwitchesProximity SwitchesPhotoelectric Switches
Rotary Switches, Cam Type Selector SwitchesPanel Switches, Terminal Blocks, Testing Terminals
Molded Case Circuit Breakers
Earth Leakage Circuit BreakersEarth Leakage Protective Relays
Circuit Protectors
Measuring Instruments, Arresters, TransducersPower Factor ControllersPower Monitoring Equipment (F-MPC)
Low Voltage Current-Limiting FusesAir Circuit Breakers
03
04
05
06
07
08
09
10
HIGH VOLTAGE PRODUCTS Up to 36kV
11Disconnecting Switches, Power FusesAir Load Break SwitchesInstrument Transformers — VT, CT
D & C CATALOG DIGEST INDEX
AC Power RegulatorsNoise Suppression FiltersControl Power Transformers
Vacuum Circuit Breakers, Vacuum Magnetic Contactors12 Protective Relays
Earth Leakage Circuit BreakersEarth Leakage Protective Relays07
Page
Earth Leakage Circuit Breakers General information............................................................................................ 07/1Design features .................................................................................................. 07/4Breaking capacities ............................................................................................ 07/7Quick reference guide
Line protectionSG series .................................................................................................. 07/9EG series ................................................................................................ 07/14HG series ................................................................................................ 07/19
Motor protectionSG series ................................................................................................ 07/21EG series ................................................................................................ 07/23
UL Listed ...................................................................................................... 07/24Mounting modifications .................................................................................... 07/30Terminal connections ....................................................................................... 07/31Wire size and terminal ..................................................................................... 07/32Type number nomenclature ............................................................................. 07/34Type number
Line protectionSG series ................................................................................................ 07/36EG series ................................................................................................ 07/38HG series ................................................................................................ 07/41
Motor protectionSG series ................................................................................................ 07/42EG series ................................................................................................ 07/43
UL Listed ...................................................................................................... 07/44Dimensions....................................................................................................... 07/45Characteristic curves ....................................................................................... 07/56Accessories ...................................................................................................... 07/68
Internal accessories..................................................................................... 07/70Motor-operated breakers ............................................................................. 07/84Mechanical interlocking device ................................................................... 07/87Operating handles ....................................................................................... 07/90Steel enclosures ........................................................................................ 07/102Terminal covers ......................................................................................... 07/104Insulation barriers ...................................................................................... 07/105Mounting modification kits ......................................................................... 07/106Padlocking device...................................................................................... 07/107
Application guide ............................................................................................ 07/119CCC approved................................................................................................ 07/121
Earth Leakage Protective Relays Selection guide ............................................................................................... 07/108Specifications
BRR type ................................................................................................... 07/110RRD type ................................................................................................... 07/111EL type ....................................................................................................... 07/113
Dimensions..................................................................................................... 07/115
MINIMUM ORDERSOrders amounting to less than ¥10,000 net per order willbe charged as ¥10,000 net per order plus freight andother charges.
WEIGHTS AND DIMENSIONSWeights and dimensions appearing in this catalog are thebest information available at the time of going to press.FUJI ELECTRIC FA has a policy of continuous productimprovement, and design changes may make thisinformation out of date.Please confirm such details before planning actualconstruction.
INFORMATION IN THIS CATALOG IS SUBJECT TOCHANGE WITHOUT NOTICE.
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 07/1
07
Earth Leakage Circuit BreakersGeneral information
■ DescriptionNow, ELCB's and MCCB's rated at 30AF (ampere frame) to800AF share the same frame sizes and dimensions. FUJIhas expanded its line up of 30AF to 800AF Breakermodels.Standardized dimensions ease panel design andmanufacture. " series" Models 30AF to 225AF (EGand SG series) are 60mm deep and require a panel cutoutheight of 52mm. Models 400AF to 800AF are 103mm deepand require a panel cutout height of 92mm.With standardized modular construction, FUJI Breakers cut panel manufacturing costs.
■ Features• Highly sensitive leakage current deviceFUJI's specially designed earth leakage tripping device usesa solid-state amplifier, which are highly efficient and quicklyrespond to ground faults.Moreover, there is a wide variety of tripping sensitivities tochoose to suit different protection purposes. Standardtripping values are 15mA, 30mA, 100mA, 200mA and500mA.
• ELCB for many applicationsFUJI manufacture many types of ELCB's to satisfy amultitude of purposes. The SG series are the standard type,HG series are high breaking capacity type and the EG theeconomy type. ELCB's are available in single-phase 2-wire,single-phase 3-wire, three-phase 3-wire and three-phase 4-wire versions.
• Easy to install and maintenance freeThe unit is installed and wired in exactly the same way asany other MCCB. FUJI ELCB's are available in a widevoltage ranges (100–230 or 100–230–440 Volts). Insulationtesting between phases is easily carried out by simplyswitching the ELCB to OFF (the control power source mustbe disconnected).
• Testing proceduresAll the ELCB's are provided with test buttons. Simply pressbutton to check operation of the tripping device as instructedin operation manual.
• Ambient temperatureThe ELCB's rated current is calibrated for an ambienttemperature of 40°C. If the ambient temperature differsgreatly from 40°C, it is necessary to compensate the ratedcurrent or operating time according to the ambienttemperature calibration curve.
• Time delay typeTime delay type (...D) has been added to the EG, SG and HGseries. These are mainly used as main circuit breakers.Since they trip later than the breakers at the end of the line,protective coordination can be carried out more easily.For further information, contact FUJI.
• Conforming to international standardsThe series conforms to IEC and EN standards, andfeatures cUL and CCC.
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice07/2
Earth Leakage Circuit BreakersGeneral information
Circuit breaker
Earthleakagerelay unit
Amplifier
Sensor
Testbutton
R
T.C
■ Variety of ELCB'sChoose from a wide variety ofmodels—from economical to high-performance.Three series of Breakersensure the best choice for theapplication: the economical E series,the standard S series, and the high-performance, high-breaking capacity Hseries. The E series line-up ofcompact, economical ELCB is best forcircuits with relatively low short-circuitcurrents. The S series new andunique current-liminting mechanismprovides a surprisingly high breakingcapacity for a compact breaker. The Hseries features an excellent current-limiting mechanism and an enhancedmethod of arc-extinguishing to achievea higher breaking capacity than the Eand S series.
SG, EG and HG seriesThe SG, EG and HG series haveelectric device provided with ICs andcan be applied to a wide variety ofvoltages. The 2-pole breakers can beused within the range of rated voltageof 100–230 volts and the 3-polebreakers within the range of 100–230–440 volts. The SG and EG areavailable with ratings between 30AFand 800AF.The HG series are available withratings between 50AF and 800AF.SG series of over 30AF, HG and EGseries of over 50AF are also availablein the sensitive current changeovertype.
SG series – 3-phase 4-wireThe SG series 4-pole ELCB is astandard 3-pole ELCB to which afourth neutral pole has been added.It has been designed for 3-phase 4-wire power systems. 100A, 225A and400A frame sizes are available.SG104H and SG204H have a highbreaking capacity of 85kA at 200V AC.They are ideally suited for mainbreakers in distribution circuits. Theearth leakage tripping device is a solid-state type. The breaker is so designedthat the neutral pole makes the firstcontact on closing, and the last breakwhen opening so reducing thepossibility of incorrect or carelessoperation.
Motor protection ELCBFUJI ELCB's are designed to eliminateerroneous operations due to the rushcurrent produced at the time of startingthe motor. They will trip in the face ofsustained overcurrent when theintegrated bimetal relay has operated.
■ Wiring diagram (skelton)
■ ModificationsMounting modificationsFUJI SG, EG and HG series ELCB'sare normally supplied as frontmounting front connection type.However, they are also available eitheras X-type (front mounting rearconnection), E-type (flush mounting) orP-type (plug-in mounting).
Accessories-modificationsFUJI ELCB's can be supplied withaccessories such as alarm switch,auxiliary switch or shunt trip device,which are customer-mountable orfactory-mounted.For details see page 07/68.
CE markingLine protectionSG series
Standard
EG series
Economical
Motor protectionSG, EG series
Standard, economical
UL approvedUL489 approved line protectionSG-UL series EG-UL series
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 07/3
07
Earth Leakage Circuit BreakersGeneral information
Note: Type number with " -CE" indicates the IEC and CE marking conformed model, but type number without " -CE" indicates also the same.
Series
SG
EG
HG
SG
EG
Pole
3
3
2
3
3
3
4
4
Standard
IEC 60947-2JIS C8201-2-2
IEC 60947-2 Ed.2JIS C8201-2-2
IEC 60947-2JIS C8201-2-2
IEC 60947-2 Ed.2JIS C8201-2-2
JIS C8201-2-2 Ann.2
Ampere frame
30
SG33C -CE
EG32AC -CE
EG33AC -CEEG33C -CE
50
SG53C -CESG53RC -CE
EG52AC -CE
EG53AC -CEEG53C -CE
HG53B
60
SG63C -CESG63RC -CE
EG63C -CE
100
SG103C -CESG103RC -CE
EG102C -CE
EG103AC -CEEG103C -CE
HG103B
SGa104ASG104H
EG104A
225
SG203C -CESG203RC -CE
EG203C -CE
HG203B
SGa204ASG204H
400
SG403C -CE
SG403RC
EG403C -CE
HG403B
SGa404A
600
SG603RC
EG603C
HG603B
800
SG803RC
EG803C
HG803B
Varieties of ELCBs
Line protection
Series
SG
EG
Pole
3
3
Standard
IEC 60947-2JIS C8201-2-2
IEC 60947-2JIS C8201-2-2
Ampere frame
30
SG33CM -CE
EG33CM -CE
50
SG53CM -CE
EG53CM -CE
60
SG63CM -CE
EG63CM -CE
100
SG103CM -CESG103RCM -CE
EG103CM -CE
225
SG203CM -CESG203RCM -CE
EG203CM -CE
Motor protection
Series
SG
EG
Pole
3
2
3
Standard
UL489IEC 60947-2JIS C8201-2-2
UL489IEC 60947-2JIS C8201-2-2
Ampere frame
50
SG53RCUL
–
–
225
SG203CUL
–
–
400
SG403CUL
–
–
100
SG103CUL
EG102CUL
EG103CUL
UL489 Listed
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice07/4
Panel cutout52, 92mm
Terminalheight24mm(Up to 225AF)
Depth60, 103mm
Earth Leakage Circuit BreakersDesign features
MCCB ELCB Earth leakagedetector
Earth leakagedetector
Miniaturization, size unification
ZCT
Feed through primaryconductor
Insulation tube
10 mm
Base
Earth-leakage tripindicator
Earth-leakage tripcoil
Connector
Armature
Trip spring
Test circuit contact
■ DescriptionToday's industries have introducedadvanced information systems andautomated systems to increaseefficiency.These systems rely on a stable supplyof electrical power. The reliability,operational ease, and costeffectiveness of these power suppliesmust improved. Earth leakage circuitbreakers must also be more compactwith improved reliability. They need tobe economical to reduce the overalldistribution panel cost.The new FUJI ELCB has beendeveloped to meet these expectationsand requirements. Now, for the firsttime, FUJI ELCB and MCCB of thesame rating are the same size, a long-awaited development in themanufacture of low-voltage distributionboard.
■ Features• Standardized ELCB and MCCB
outline dimensionsFUJI breakers featurecompact and modular construction.The ELCB's and MCCB's of the samerating, from 30AF to 800AF, are thesame size.
• Standardized modular constructionHaving circuit breakers of the samebasic dimensions promote modulardesigns. New ELCB's areavailable in two standard depths: 60and 103mm, choose it from two frontpanel cutout height of 52mm or 92mm.The center of the window frame ispositioned at the center of the circuitbreaker. These design featuresenable a radical reduction in thenumber of mounting patterns.
• Ultra-small leakage detector andtrip unit
The leakage detector is equipped witha new, thin, high-performance ZCTwith uniform magnetic characteristics.The new ZCT allows a compactleakage detector with stable balancingcharacteristics to be manufactured.
• Simple and highly reliableelectronic circuit
Very stable operation across a widevoltage range has been obtained witha highly reliable dedicated IC which isoperated with minute currents and aFUJI designed power circuit.
• Small, high-efficiency trip unitA small, highly efficient trip coil whichoperates with a small tripping currentand has a strong driving force hasbeen developed with a CAD(Computer Aided Design) basedmethod of magnetic field analysis.
• One ELCB can be used with circuitvoltages of 100–230–440V AC (high-speed type)Easy selection of ELCB and greatflexibility in meeting specificationchanges.Selection of the proper ELCB is madeeasier because of the wide voltagerange of one unit, (100–230–440V AC).Changes in specifications can also bemade more easily with such a widevoltage range.
• Three-step, sensitivity to faultcurrents (100/200/500mA)A three-step change (100/200/500mA)in the rated sensitivity to fault currentshas widened the range of application.This allows full compliance withchanges in specifications.
• Easily interchangeable ELCB andMCCBThe ELCB and MCCB allow thedesigner to quickly alter distributionpanel and facility design whenspecifications are changed.The ELCB and MCCB can be easilyreplaced by each other because theirsizes and basic specifications are thesame.
ZCTSolid-stateamplifier
Powersupplycircuit
Currentlimitingcircuit
R
T
Charging capacitor
100V/ 230V/440V circuit
Magnetic hold type trip coil
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 07/5
07
Earth Leakage Circuit BreakersDesign features
The ELCB can be mechanically tripped externally.
Insulation has been strengthened by using resin to mold the main circuit conductor and ZCT into an integrated unit.
The sensitive trip mechanism operation can be checked at any time by simply pressing the test button.
A unit construction for the ELR and greater wiring efficiency has boosted connection reliability.
Accessorymounting space
Insulationmechanism
Earth leakagedetection section
Arc quencher(Larger arc-extinguishing space)
Overcurrent tripping device
Resin molded
ZCT
Conductor
When the breaker opens due to an earth leakage current the trip indication button pops out to indicate that an earth leakage has occurred.
Tripping indication button ELR unit with less wiring
Test button
Solid-state insulation ZCT
Trip button
■ Construction
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice07/6
Earth Leakage Circuit BreakersDesign features
■ Internal and external accessoriesA wider range of customer-mountable accessoriesThe range of cassette-type internalaccessories has been greatlyexpanded for ELCBs. Thisspeeds up and simplifies customerresponse to specification changes.All accessories shown here can bemounted by the customer except formotor operating mechanism and platetype padlocking device.
Wide variety of internal accessorycombinationsUp to two auxiliary switches, two alarmswitches, and one shunt trip device orundervoltage trip device quickly snapon or in.
Quick and easy mountingNo need to open breaker cover tomount accessories. Internalaccessories easily snap into a pocketat the left of the breaker window frame.
No adjustmentsAccessory mounting is quick and easy— accessories adjust automatically atthe correct position when mounted.
AF93-82 AF93-81
• Terminal block typesTerminal blocks are mounted on theside of the breaker case. Blocks areonly 12.5 or 19mm thick, minimizingpanel mounting space. Installed leadwires are parallel to the side of thecase.
Two ways to connect — lead wiresor terminal blocks• Lead wire typesLeads are marked with to indicate thecorrect terminal number of theaccessory — incorrect wiring isminimized. To make wiring easy andprevent to incorrect connection, thelead wires are provided with colorcoated tube and marking on it.
Undervoltage trip deviceShunt trip device
Auxiliary switch Terminal block
Modification kitsOperating handles
Mechanical interlockingdeviceLong type
Short type
Alarm switch
Interphase barrierEarth barrier
Steel enclosureN type V type
Handle padlocking deviceHandle locking cover
Motor operatingmechanism
Terminal covers Insulation barriers
For front mounting,rear connection
For plug-inmounting
For flush mounting,rear connection
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 07/7
07
Earth Leakage Circuit BreakersBreaking capacities
■ Breaking capacitiesEarth leakage + Overcurrent + Short-circuit protection
Series
SG
EG
Breaker ampereframe
30
50 50
60 60 100 100
225 225
400
30 30 30
50 50 50 60
100 100 100
225
400
Breakertype
SG33C -CE
SG53C -CESG53RC -CE
SG63C -CESG63RC -CE
SG103C -CESG103RC -CE
SG203C -CESG203RC -CE
SG403C -CE
EG32AC -CEEG33AC -CEEG33C -CE
EG52AC -CEEG53AC -CEEG53C -CE
EG63C -CE
EG103AC -CEEG102C -CEEG103C -CE
EG203C -CE
EG403C -CE
Pole
3
33
33
33
33
3
233
233
3
323
3
3
Rated current
(A)
3, 5, 10, 15, 20, 30
5, 10, 15, 20, 30, 40, 5010, 15, 20, 30, 40, 50
6060
15, 20, 30, 40, 50, 60, 75, 10015, 20, 30, 40, 50, 60, 75, 100
125, 150, 175, 200, 225125, 150, 175, 200, 225
250, 300, 350, 400
5, 10, 15, 20, 305, 10, 15, 20, 305, 10, 15, 20, 30
5, 10, 15, 20, 30, 40, 505, 10, 15, 20, 30, 40, 505, 10, 15, 20, 30, 40, 50
60
60, 75, 10050, 60, 75, 10050, 60, 75, 100
125, 150, 175, 200, 225
250, 300, 350, 400
Rated voltage
(V AC)
100–440
100–440100–440
100–440100–440
100–440100–440
100–440100–440
100–440
100–230100–230100–440
100–230100–230100–440
100–440
100–230100–230100–440
100–440
100–440
Sensitive current
(mA)
30, 100/200/500
30, 100/200/50030, 100/200/500
30, 100/200/50030, 100/200/500
30, 100/200/50030, 100/200/500
30, 100/200/50030, 100/200/500
30, 100/200/500
15, 30, 10015, 30, 10015, 30, 100
15, 30, 10015, 30, 10015, 30, 100/200
15, 30, 100/200
30, 100/20030, 100/20030, 100/200/500
30, 100/200/500
30, 100/200/500
Breaking capacity (kA) (Icu/Ics)
230V
5/3
10/5 25/13
10/5 25/13
50/25 100/50
50/25 100/50
50/25
2.5/2 2.5/2 2.5/2
2.5/2 2.5/2 5/3
5/3
5/3 10/5 25/13
35/18
35/18
100V
5/3
10/5 25/13
10/5 25/13
50/25 100/50
50/25 100/50
50/25
2.5/2 2.5/2 5/3
2.5/2 2.5/2 5/3
5/3
5/3 10/5 25/13
35/18
35/18
400V
2.5/2
7.5/4 10/5
7.5/4 10/5
30/8 50/13
30/8 50/13
35/18
––1.5/1
––2.5/2
2.5/2
––10/5
18/5
25/13
415V
2.5/2
7.5/4 10/5
7.5/4 10/5
25/7 50/13
25/7 50/13
35/18
––1.5/1
––2.5/2
2.5/2
––10/5
15/4
25/13
440V
2.5/2
7.5/4 10/5
7.5/4 10/5
25/7 50/13
25/7 50/13
35/18
––1.5/1
––2.5/2
2.5/2
––10/5
15/4
25/13
• IEC 60947-2, EN60947-2, JIS C8201-2-2 IEC and CE marking conformed
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice07/8
Earth Leakage Circuit BreakersBreaking capacities
Note: * 3P+1N, neutral phase cannot be made or broken.
■ Breaking capacitiesEarth leakage + Overcurrent + Short-circuit protection type
Series
SG
EG
HG
Breaker ampereframe
400 600
800
100 100
225 225
400
100
600
800
50
100
225
400
600
800
Breakertype
SG403RCSG603RC
SG803RC
SGa104ASG104H
SGa204ASG204H
SGa404A
EG104A
EG603C
EG803C
HG53B
HG103B
HG203B
HG403B
HG603B
HG803B
Pole
33
3
4 4
4 4
4
*
3
3
3
3
3
3
3
3
Rated current
(A)
250, 300, 350, 400500, 600
700, 800
40, 50, 60, 75, 10050, 60, 75, 100
125, 150, 175, 200, 225125, 150, 175, 200, 225
250, 300, 350, 400
30, 40, 50, 60, 75, 100
500, 600
700, 800
15, 20, 30, 40, 50
15, 20, 30, 40, 50, 60, 75, 100
125, 150, 175, 200, 225
250, 300, 350, 400
500, 600
700, 800
Rated voltage
(V AC)
100-440100-440
100-440
200-415 200-415
200-415 200-415
200-415
380-415
100-415
100-415
100-415
100-415
100-415
100-415
100-415
100-415
Sensitive current
(mA)
30, 100/200/500100/200/500
100/200/500
30, 100/200/50030, 100/200/500
30, 100/200/50030, 100/200/500
30, 100/200/500
30, 100, 300, 500
100/200/500
100/200/500
30, 100/200/500
30, 100/200/500
30, 100/200/500
30, 100/200/500
100/200/500
100/200/500
Breaking capacity (kA) [Icu]
230V
8585
85
50 85
42 85
42
–
50
50
100
100
100
125
125
125
400V
5050
50
25 42
25 42
25
–
35
35
65
65
65
65
65
65
415V
5050
50
25 42
25 42
25
14
35
35
65
65
65
65
65
65
100V
8585
85
––
––
–
–
50
50
100
100
100
125
125
125
440V
5050
50
––
––
–
–
35
35
65
65
65
65
65
65
• IEC 60947-2 Ed.2 , JIS C8201-2-2 Ann.2
Breaker ampereframe
50
100100100
225
400
Breakertype
SG53RCUL
EG102CULEG103CULSG103CUL
SG203CUL
SG403CUL
Pole
3
233
3
3
Rated current
(A)
3, 5, 10, 15, 20, 30, 40, 50
60, 70, 75, 80, 90, 10060, 70, 75, 80, 90, 10032, 40, 50, 60, 75, 100
125, 150, 175, 200, 225
250, 300, 350, 400
Rated voltage
(V AC)
100–440
100–440100–440100–440
100–440
100–440
Sensitive current
(mA)
30, 100/200/500
30, 100/20030, 100/200/50030, 100/200/500
30, 100/200/500
30, 100/200/500
Breaking capacity (kA)
14
141435
35
42
• UL489 Listed
240V
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 07/9
Earth Leakage Circuit BreakersQuick reference guide
Line protection
07
SG series IEC and CE marking conformed types
Instantaneous trip typeTime delay trip type
Instantaneous trip typeTime delay trip type
FramePoleType
Phase and wire
Rated voltage (V AC)[IEC 60947-2/JIS C 8201-2-2]Rated current (A)Frequency (Hz)Instantaneous trip type
Rated breaking capacity(kA)[IEC 60947-2/JIS C 8201-2-2](Icu/Ics) *1
Instantaneoustrip type[UL508]
Tripping time (s) [UL1053]Dimensions (mm) a bPage 07/45 c dMass (kg) Front mounting typeFront mounting, front connection No-markFront mounting, rear connection XFlush mounting, rear connection EFlush mounting, top & bottom connection YPlug-in mounting PIEC 35mm wide rail mounting
Rated sensitive current (mA)Tripping time (s)
Rated operating voltage (V AC)Rated sensitive current I∆n (mA) Page 07/28Pick-up current [UL1053]
440V AC415V AC400V AC230V AC100V AC
30A3SG33C -CE–3ø3W1ø3W1ø2W100–230–440–3, 5, 10, 15, 20, 3050/6030, 100/200/5000.12.5/22.5/22.5/25/35/324030, 100/200/500
0.7 x Rated sensitive current0.1 75100 60 840.6
50A3SG53C -CE–3ø3W1ø3W1ø2W100–230–440–5, 10, 15, 20, 30, 40, 5050/6030, 100/200/5000.17.5/47.5/47.5/410/510/524030, 100/200/500
0.7 x Rated sensitive current0.1 75100 60 840.6
3SG53RC -CE–3ø3W1ø3W1ø2W100–230–440–10, 15, 20, 30, 40, 5050/6030, 100/200/5000.110/510/510/525/1325/1324030, 100/200/500
0.1 75100 60 840.6
Internal accessories Alarm switch K Alarm switch with terminal block KA Auxiliary switch W Auxiliary switch with terminal block WA Undervoltage trip R Shunt trip F Test lead wire TLExternal accessories Motor operating mechanism M Handle padlocking device Cap type Q1 Plate type Q2 Mechanical interlocking device M1 M2 M3 Operating handle N-type N Operating handle V-type V Steel enclosure Direct operating C Dustproof steel enclosure Handle operating CV Rainproof steel enclosure Handle operating CW Terminal cover Short TS Terminal cover Long TB Insulation barrier Interphase *2 B Insulation barrier Earth BL Handle locking cover L Flat terminal S
ca d
b
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C503
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C503
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C503
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
Notes: *1 Icu: Rated ultimate short-circuit breaking capacity Ics: Rated service short-circuit breaking capacity *2 Interphase insulation barriers are standard provided for the front mounting type breakers of 50AF and over.
Factory-mounted accessoryAvailable – Not available
Rated voltage (V) Operationalvoltage range (V)
100–230–440 80–484
07/10Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit BreakersQuick reference guideLine protection
SG series IEC and CE marking conformed types
Instantaneous trip typeTime delay trip type
Instantaneous trip typeTime delay trip type
FramePoleType
Phase and wire
Rated voltage (V AC)[IEC 60947-2/JIS C 8201-2-2]Rated current (A)Frequency (Hz)Instantaneous trip type
Rated breaking capacity(kA)[IEC 60947-2/JIS C 8201-2-2](Icu/Ics) *1
Instantaneoustrip type[UL508]
Tripping time (s) [UL1053]Dimensions (mm) a bPage 07/45 c dMass (kg) Front mounting typeFront mounting, front connection No-markFront mounting, rear connection XFlush mounting, rear connection EFlush mounting, top & bottom connection YPlug-in mounting PIEC 35mm wide rail mounting
Rated sensitive current (mA)Tripping time (s)
Rated operating voltage (V AC)Rated sensitive current I∆n (mA) Page 07/28Pick-up current [UL1053]
440V AC415V AC400V AC230V AC100V AC
3SG63RC -CE–3ø3W1ø3W1ø2W100–230–440–6050/6030, 100/200/5000.110/510/510/525/1325/1324030, 100/200/500
0.1 75100 60 840.6
60A3SG63C -CE–3ø3W1ø3W1ø2W100–230–440–6050/6030, 100/200/5000.17.5/47.5/47.5/410/510/524030, 100/200/500
0.7 x Rated sensitive current0.1 75100 60 840.6
ca d
b
Internal accessories Alarm switch K Alarm switch with terminal block KA Auxiliary switch W Auxiliary switch with terminal block WA Undervoltage trip R Shunt trip F Test lead wire TLExternal accessories Motor operating mechanism M Handle padlocking device Cap type Q1 Plate type Q2 Mechanical interlocking device M1 M2 M3 Operating handle N-type N Operating handle V-type V Steel enclosure Direct operating C Dustproof steel enclosure Handle operating CV Rainproof steel enclosure Handle operating CW Terminal cover Short TS Terminal cover Long TB Insulation barrier Interphase *2 B Insulation barrier Earth BL Handle locking cover L Flat terminal S
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C1003
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C1003
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
Notes: *1 Icu: Rated ultimate short-circuit breaking capacity Ics: Rated service short-circuit breaking capacity *2 Interphase insulation barriers are standard provided for the front mounting type breakers of 50AF and over.
– – ––
––
3SG103RC -CE
3ø3W1ø3W1ø2W100–230–440–
50/6030, 100/200/5000.150/1350/1350/13100/50100/50––
–– 90155 60 821.3
100A3SG103C -CE
3ø3W1ø3W1ø2W100–230–440–15, 20, 30, 40, 50, 60, 75, 10050/6030, 100/200/5000.125/725/730/850/2550/25––
–– 90155 60 821.3
–––BZ-N30CBZ6V30CBZ6C30C3BZ-CV30CBZ-CW30CBZ-TS30B-3BZ-TB30B-3BZ-B30BBZ-BL35BBZ6L30CBZ-S35B-1003
BZ6K 30C
BZ6W 30C
–
–
–––BZ-N30CBZ6V30CBZ6C30C3BZ-CV30CBZ-CW30CBZ-TS30B-3BZ-TB30B-3BZ-B30BBZ-BL35BBZ6L30CBZ-S35B-1003
BZ6K 30C
BZ6W 30C
–
–
Factory-mounted accessoryAvailable – Not available
Rated voltage (V) Operationalvoltage range (V)
100–230–440 80–484
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 07/11
Earth Leakage Circuit BreakersQuick reference guide
Line protection
07
Instantaneous trip typeTime delay trip type
Instantaneous trip typeTime delay trip type
FramePoleType
Phase and wire
Rated voltage (V AC)[IEC 60947-2/JIS C 8201-2-2]Rated current (A)Frequency (Hz)Instantaneous trip type
Rated breaking capacity(kA)[IEC 60947-2/JIS C 8201-2-2](Icu/Ics) *1
Instantaneoustrip type[UL508]
Tripping time (s) [UL1053]Dimensions (mm) a bPage 07/46 c dMass (kg) Front mounting typeFront mounting, front connection No-markFront mounting, rear connection XFlush mounting, rear connection EFlush mounting, top & bottom connection YPlug-in mounting PIEC 35mm wide rail mounting
Rated sensitive current (mA)Tripping time (s)
Rated operating voltage (V AC)Rated sensitive current I∆n (mA) Pick-up current [UL1053]
440V AC415V AC400V AC230V AC100V AC
225A3SG203C -CE–3ø3W1ø3W1ø2W100–230–440–125, 150, 175, 200, 22550/6030, 100/200/5000.125/725/730/850/2550/25––
––105165 60 841.5
3SG203RC -CE–3ø3W1ø3W1ø2W100–230–440–125, 150, 175, 200, 22550/6030, 100/200/5000.150/1350/1350/13100/50100/50––
––105165 60 841.5
400A3SG403C -CE–3ø3W1ø3W1ø2W100–230–440–250, 300, 350, 40050/6030, 100/200/5000.135/1835/1835/1850/2550/25––
––1402571031465.6
Internal accessories Alarm switch K Alarm switch with terminal block KA Auxiliary switch W Auxiliary switch with terminal block WA Undervoltage trip R Shunt trip F Test lead wire TLExternal accessories Motor operating mechanism M Handle padlocking device Cap type Q1 Plate type Q2 Mechanical interlocking device M1 M2 M3 Operating handle N-type N Operating handle V-type V Steel enclosure Direct operating C Dustproof steel enclosure Handle operating CV Rainproof steel enclosure Handle operating CW Terminal cover Short TS Terminal cover Long TB Insulation barrier Interphase *2 B Insulation barrier Earth BL Handle locking cover L Flat terminal S
ca d
b
–––––BZ-N40CBZ6V40CBZ-C40BBZ-CV40CBZ-CW40CBZ-TS40BBZ-TB40BBZ-B40BBZ-BL40BBZ6L40CBZ-S50B-2253
BZ6K 40C
BZ6W 40C
–
–––––BZ-N40CBZ6V40CBZ-C40BBZ-CV40CBZ-CW40CBZ-TS40BBZ-TB40BBZ-B40BBZ-BL40BBZ6L40CBZ-S50B-2253
BZ6K 40C
BZ6W 40C
–
–
BZ-M160CBZ-M260CBZ-M360CBZ-N60CBZ6V60CBZ-C60BBZ-CV60CBZ-CW60C–BZ-TB60BB-43A–BZ-L70B–
BZ-K70BBZ-K70BABZ-W70BBZ-W70BABZ-R70B-BZ-F70B-
–
– – –
Notes: *1 Icu: Rated ultimate short-circuit breaking capacity Ics: Rated service short-circuit breaking capacity *2 Interphase insulation barriers are standard provided for the front mounting type breakers of 50AF and over.
Factory-mounted accessoryAvailable – Not available
SG series IEC and CE marking conformed types
Rated voltage (V) Operationalvoltage range (V)
100–230–440 80–484
07/12Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit BreakersQuick reference guideLine protection
SG series
Instantaneous trip typeTime delay trip type
Instantaneous trip typeTime delay trip type
FramePoleType
Phase and wire
Rated voltage (V AC)[IEC 60947-2 Ed.2/JIS C8201-2-2]Rated current (A)Frequency (Hz)Instantaneous trip type
Time delay trip type
Rated breaking capacity(kA)[IEC 60947-2 Ed.2 / JIS C8201-2-2](Icu/Ics)
Instantaneoustrip type[UL508]
Dimensions (mm) a bPage 07/46 c dMass (kg) Front mounting typeFront mounting, front connection No-markFront mounting, rear connection XFlush mounting, rear connection EFlush mounting, top & bottom connection YPlug-in mounting PIEC 35mm wide rail mounting
Rated sensitive current (mA)Tripping time (s)Rated sensitive current (mA)Tripping time (s)Inertia non-tripping time (ms) [2I∆n]
Rated operating voltage (V AC)Rated sensitive current I∆n (mA) Pick-up current [UL1053]
440V AC415V AC400V AC230V AC100V AC
400A3SG403RCSG403RCD3ø3W1ø3W1ø2W100–230–440200–440250, 300, 350, 40050/6030, 100/200/5000.1100/200/5000.3/0.8/2150/400/100050/2550/2550/2585/4385/43––
–1402571031465.6
600A3SG603RC SG603RCD3ø3W1ø3W1ø2W100–230–440200–440500, 60050/60100/200/5000.1100/200/5000.3/0.8/2150/400/100050/2550/2550/2585/4385/43––
–21027510314610
800A3SG803RC SG803RCD3ø3W1ø3W1ø2W100–230–440200–440700, 80050/60100/200/5000.1100/200/5000.3/0.8/2150/400/100050/2550/2550/2585/4385/43––
21027510314610
Internal accessories Alarm switch K Alarm switch with terminal block KA Auxiliary switch W Auxiliary switch with terminal block WA Undervoltage trip R Shunt trip F Test lead wire TL Megger test switch MGSExternal accessories Motor operating mechanism M Handle padlocking device Cap type Q1 Plate type Q2 Mechanical interlocking device M1 M2 M3 Operating handle N-type N Operating handle V-type V Steel enclosure Direct operating C Dustproof steel enclosure Handle operating CV Rainproof steel enclosure Handle operating CW Terminal cover Short TS Terminal cover Long TB Insulation barrier Interphase *1 B Insulation barrier Earth BL Handle locking cover L Flat terminal S
ca d
b
BZ-M160CBZ-M260CBZ-M360CBZ-N60CBZ6V60CBZ-C60BBZ-CV60CBZ-CW60C–BZ-TB60BB-43A–BZ-L70B–
–
BZ-M170CBZ-M270CBZ-M370CBZ-N70CBZ6V70CBZ-C70BBZ-CV70C––BZ-TB70BB-43A–BZ-L70B–
BZ-K70BBZ-K70BABZ-W70BBZ-W70BABZ-R70B-BZ-F70B-
–
BZ-M170CBZ-M270CBZ-M370CBZ-N70CBZ6V70CBZ-C70BBZ-CV70C––BZ-TB60BB-43A–BZ-L70B–
BZ-K70BBZ-K70BABZ-W70BBZ-W70BABZ-R70B-BZ-F70B-
–
– – –
BZ-K70BBZ-K70BABZ-W70BBZ-W70BABZ-R70B-BZ-F70B-
Notes: *1 Interphase insulation barriers are standard provided for the front mounting type breakers of 50AF and over.
Factory-mounted accessoryAvailable – Not availableRated voltage (V) Operational
voltage range (V)
100–230–440 80–484200–440 160–484
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 07/13
Earth Leakage Circuit BreakersQuick reference guide
Line protection
07
■ SG series/4-pole
Note: • Time delay trip types are also available on request.* For motor-operated breaker, sensitive current and tripping time are fixed. Specify the sensitive current and tripping time when ordering.
Rated voltage (V) Operationalvoltage range (V)
200–415 160–484
Frame
Pole
Type
Phase and wire
Rated current (A) Ambient temp.: 40°C
Rated voltage (V) [JIS C8201-2-2 Ann.2]
Rated sensitive current (mA)
Tripping time (sec)
Rated breaking capacity 415V AC(kA) [JIS C8201-2-2 Ann.2] 400V AC 200V AC
Earth leakage tripping device
Overcurrent tripping device
Dimensions a(mm) b cPage 07/48 d
Mass (kg) Front mounting type
Front mounting, front connection No-mark rear connection X
Flush mounting, rear connection E top & bottom connection Y
Plug-in mounting P
Alarm switch KAuxiliary switch WUndervoltage trip RShunt trip FTest lead wire TLMegger test switch MGS
Motor operating mechanism M*Padlocking device QMechanical interlocking device M1Operating handle N-type NOperating handle G-type G
Steel enclosure CSteel enclosure with G-type handle CG
Terminal cover Inside panel use A1Terminal cover Outside panel use T1Insulation barrier Interphase BInsulation barrier Earth BL
100A
4
SGa104A
3ø4W
40, 50, 60, 75, 100
200-415
30, 100/200/500
0.1
25 25 50
Solid-state
Thermal-magnetic
140230 86109
3.2
–
–
––
–N-13EAG-12A
––
A1-14–––
SG104H
50, 60, 75, 100
42 42 85
225A
4
SGa204A
3ø4W
125, 150, 175, 200, 225
200-415
30, 100/200/500
0.1
25 25 42
Solid-state
Thermal-magnetic
185350103134
8.7
–
–
––
–N-23EAG-22A
––
––B-44A–
400A
4
SGa404A
3ø4W
250, 300, 350, 400
200-415
30, 100/200/500
0.1
25 25 42
Solid-state
Thermal-magnetic
185350103134
11.3
–
–
––
–N-23EAG-22A
––
––B-44A–
SG204H
42 42 85
Factory-mounted accessoryAvailable – Not available
ca d
b
07/14Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit BreakersQuick reference guideLine protection
EG series IEC and CE marking conformed types
Internal accessories Alarm switch K Alarm switch with terminal block KA Auxiliary switch W Auxiliary switch with terminal block WA Undervoltage trip R Shunt trip F Test lead wire TL Megger test switch MGSExternal accessories Motor operating mechanism M Handle padlocking device Cap type Q1 Plate type Q2 Mechanical interlocking device M1 M2 M3 Operating handle N-type N Operating handle V-type V Steel enclosure Direct operating C Dustproof steel enclosure Handle operating CV Rainproof steel enclosure Handle operating CW Terminal cover Short TS Terminal cover Long TB Insulation barrier Interphase *2 B Insulation barrier Earth BL Handle locking cover L Flat terminal S
––
BZ6M110C2BZ6M210C2BZ6M310C2BZ6N10CBZ6V10CBZ6C10C2BZ6CV10CBZ6CW10CBZ6TS10C2BZ6TB10C2BZ6B10CBZ6BL10C2BZ6L10CBZ6S10C502
BZ6KR10CBZ6KR10CABZ6WR10CBZ6WR10CABZ6R 10CBZ6F 10C
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
–
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
–
BZ6KR10CBZ6KR10CABZ6WR10CBZ6WR10CABZ6R 10CBZ6F 10C
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
–
––
BZ6M110C2BZ6M210C2BZ6M310C2BZ6N10CBZ6V10CBZ6C10C2BZ6CV10CBZ6CW10CBZ6TS10C2BZ6TB10C2BZ6B10CBZ6BL10C2BZ6L10CBZ6S10C502
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C503
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C503
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C503
Instantaneous trip typeTime delay trip type
Instantaneous trip typeTime delay trip type
FramePoleType
Phase and wire
Rated voltage (V AC)[IEC 60947-2/JIS C 8201-2-2]Rated current (A)Rated frequency (Hz)Instantaneous trip type
Rated breaking capacity(kA)[IEC 60947-2/JIS C 8201-2-2](Icu/Ics) *1
Instantaneoustrip type[UL508]
Tripping time (s) [UL1053]Dimensions (mm) a bPage 07/49 c dMass (kg) Front mounting typeFront mounting, front connection No-markFront mounting, rear connection XFlush mounting, rear connection EFlush mounting, top & bottom connection YPlug-in mounting PIEC 35mm wide rail mounting
Rated sensitive current (mA)Tripping time (s)
Rated operating voltage (V AC) Rated sensitive current I∆n(mA) Page 07/29 Pick-up current [UL1053]
440V AC415V AC400V AC230V AC100V AC
2EG32AC -CE–1ø2W
100–230–5, 10, 15, 20, 3050/6015, 30, 1000.1–––2.5/22.5/224015, 30, 100
0.7 x Rated sensitive current0.1 50100 60 840.4
3EG33AC -CE–3ø3W1ø3W1ø2W100–230–
50/6015, 30, 1000.1 –––2.5/22.5/224015, 30, 100
0.1 75100 60 840.6
3EG33C -CE–3ø3W1ø3W1ø2W100–230–440–
50/6015, 30, 1000.11.5/11.5/11.5/12.5/25/324015, 30, 100
0.1 75100 60 840.6
2EG52AC -CE–1ø2W
100–230 –5, 10, 15, 20, 30, 40, 5050/6015, 30, 1000.1 –––2.5/22.5/224015, 30, 100
0.7 x Rated sensitive current0.1 50100 60 840.4
30A 50A3EG53AC -CE–3ø3W1ø3W1ø2W100–230–
50/6015, 30, 1000.1 –––2.5/22.5/224015, 30, 100
0.1 75100 60 840.6
ca d
b
Notes: *1 Icu: Rated ultimate short-circuit breaking capacity Ics: Rated service short-circuit breaking capacity *2 Interphase insulation barriers are standard provided for the front mounting type breakers of 50AF and over. Except for EG50AC
Factory-mounted accessoryAvailable – Not availableRated voltage (V) Operational
voltage range (V)
100–230 80–264100–230–440 80–484
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 07/15
Earth Leakage Circuit BreakersQuick reference guide
Line protection
07
EG series IEC and CE marking conformed types
Internal accessories Alarm switch K Alarm switch with terminal block KA Auxiliary switch W Auxiliary switch with terminal block WA Undervoltage trip R Shunt trip F Test lead wire TL Megger test switch MGSExternal accessories Motor operating mechanism M Handle padlocking device Cap type Q1 Plate type Q2 Mechanical interlocking device M1 M2 M3 Operating handle N-type N Operating handle V-type V Steel enclosure Direct operating C Dustproof steel enclosure Handle operating CV Rainproof steel enclosure Handle operating CW Terminal cover Short TS Terminal cover Long TB Insulation barrier Interphase *2 B Insulation barrier Earth BL Handle locking cover L Flat terminal S
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C503
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
–
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
–
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
–
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
–
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C25C3BZ6CV25CBZ6CW25CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C1002
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C1003
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C25C3BZ6CV25CBZ6CW25CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C1003
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C25C3BZ6CV25CBZ6CW25CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C1003
Instantaneous trip typeTime delay trip type
Instantaneous trip typeTime delay trip type
FramePoleType
Phase and wire
Rated voltage (V AC)[IEC 60947-2/JIS C 8201-2-2]Rated current (A)Rated frequency (Hz)Instantaneous trip type
Rated breaking capacity(kA)[IEC 60947-2/JIS C 8201-2-2](Icu/Ics) *1
Instantaneoustrip type[UL508]
Tripping time (s) [UL1053]Dimensions (mm) a bPage 07/49 c dMass (kg) Front mounting typeFront mounting, front connection No-markFront mounting, rear connection XFlush mounting, rear connection EFlush mounting, top & bottom connection YPlug-in mounting PIEC 35mm wide rail mounting
Rated sensitive current (mA)Tripping time (s)
Rated operating voltage (V AC) Rated sensitive current I∆n(mA) Page 07/29 Pick-up current [UL1053]
440V AC415V AC400V AC230V AC100V AC
3EG53C -CE–3ø3W1ø3W1ø2W100–230–440–5,10,15,20,30,40,5050/6015, 30, 100/2000.12.5/22.5/22.5/25/35/324015, 30, 100/200
0.7 x Rated sensitive current0.1 75100 60 840.6
3EG63C -CE–3ø3W1ø3W1ø2W100–230–440–6050/6015, 30, 100/2000.12.5/22.5/22.5/25/35/324015, 30, 100/200
0.1 75100 60 840.6
3EG103AC -CE–3ø3W1ø3W1ø2W100–230–60, 75, 10050/6030, 100/2000.1–––5/35/324030, 100/200
0.7 x Rated sensitive current0.1 75100 60 840.6
2EG102C -CE–1ø2W
100–230 –50, 60, 75, 10050/6030, 100/2000.1–––10/510/524030, 100/200
0.1 75100 60 840.55
50A 60A 100A3EG103C -CE–3ø3W1ø3W1ø2W100–230–440–
50/6030, 100/200/5000.110/510/510/525/1325/1324030, 100/200/500
0.1 75100 60 840.6
ca d
b
Notes: *1 Icu: Rated ultimate short-circuit breaking capacity Ics: Rated service short-circuit breaking capacity *2 Interphase insulation barriers are standard provided for the front mounting type breakers of 50AF and over. Except for EG50AC and EG100AC
Factory-mounted accessoryAvailable – Not availableRated voltage (V) Operational
voltage range (V)
100–230 80–264100–230–440 80–484
07/16Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit BreakersQuick reference guideLine protection
EG series IEC and CE marking conformed types
Instantaneous trip typeTime delay trip type
Instantaneous trip typeTime delay trip type
FramePoleType
Phase and wire
Rated voltage (V AC)[IEC 60947-2/JIS C 8201-2-2]Rated current (A)Rated frequency (Hz)Instantaneous trip type
Rated breaking capacity(kA)[IEC 60947-2/JIS C 8201-2-2](Icu/Ics) *1
Instantaneoustrip type[UL508]
Tripping time (s) [UL1053]Dimensions (mm) a bPage 07/50 c dMass (kg) Front mounting typeFront mounting, front connection No-markFront mounting, rear connection XFlush mounting, rear connection EFlush mounting, top & bottom connection YPlug-in mounting PIEC 35mm wide rail mounting
Rated sensitive current (mA)Tripping time (s)
Rated operating voltage (V AC)Rated sensitive current I∆n (mA) Pick-up current [UL1053]
440V AC415V AC400V AC230V AC100V AC
400A3EG403C -CE–3ø3W1ø3W1ø2W100–230–440–250, 300, 350, 40050/6030, 100/200/5000.125/1325/1325/1335/1835/18––
––1402571301465.6
225A3EG203C -CE–3ø3W1ø3W1ø2W100–230–440–125, 150, 175, 200, 22550/6030, 100/200/5000.115/415/418/535/1835/18––
––105165 60 841.5
ca d
b
Internal accessories Alarm switch K Alarm switch with terminal block KA Auxiliary switch W Auxiliary switch with terminal block WA Undervoltage trip R Shunt trip F Test lead wire TL Megger test switch MGSExternal accessories Motor operating mechanism M Handle padlocking device Cap type Q1 Plate type Q2 Mechanical interlocking device M1 M2 M3 Operating handle N-type N Operating handle V-type V Steel enclosure Direct operating C Dustproof steel enclosure Handle operating CV Rainproof steel enclosure Handle operating CW Terminal cover Short TS Terminal cover Long TB Insulation barrier Interphase *2 B Insulation barrier Earth BL Handle locking cover L Flat terminal S
–
–––BZ-N40CBZ6V40CBZ-C40B-3BZ-CV40CBZ-CW40CBZ-TS40BBZ-TB40BBZ-B40BBZ-BL40BBZ6L40CBZ-S50B-2253
BZ6K 40C
BZ6W 40C
–
–
BZ-M160CBZ-M260CBZ-M360CBZ-N60CBZ6V60CBZ-C60B-3BZ-CV60CBZ-CW60C–BZ-TB60BB-43A–BZ-L70B–
BZ-K70BBZ-K70BABZ-W70BBZ-W70BABZ-R70B-BZ-F70B-
–
–
– –
Notes: *1 Icu: Rated ultimate short-circuit breaking capacity Ics: Rated service short-circuit breaking capacity *2 Interphase insulation barriers are standard provided for the front mounting type breakers of 50AF and over.
Factory-mounted accessoryAvailable – Not available
Rated voltage (V) Operationalvoltage range (V)
100–230–440 80–484
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 07/17
Earth Leakage Circuit BreakersQuick reference guide
Line protection
07
EG series
Instantaneous trip typeTime delay trip type
Instantaneous trip typeTime delay trip type
FramePoleType
Phase and wire
Rated voltage (V AC)[IEC 60947-2 Ed.2/JIS C 8201-2-2]Rated current (A)Rated frequency (Hz)Instantaneous trip type
Time delay trip type
Rated breaking capacity(kA)[IEC 60947-2 Ed.2/JIS C 8201-2-2]
Instantaneoustrip type[UL508]
Tripping time (s) [UL1053]Dimensions (mm) a bPage 07/51 c dMass (kg) Front mounting typeFront mounting, front connection No-markFront mounting, rear connection XFlush mounting, rear connection EFlush mounting, top & bottom connection YPlug-in mounting PIEC 35mm wide rail mounting
Rated sensitive current (mA)Tripping time (s)Rated sensitive current (mA)Tripping time (s)Inertia non-tripping time (s) [2I∆n]
Rated operating voltage (V AC)Rated sensitive current I∆n (mA) Pick-up current [UL1053]
440V AC415V AC400V AC200V AC100V AC
800A3EG803CEG803CD3ø3W1ø3W1ø2W100–230–440200–440700, 80050/60100/200/5000.1100/200/5000.3/0.8/20.15/0.4/13535355050––
––21027510314610
600A3EG603CEG603CD3ø3W1ø3W1ø2W100–230–440200–440500, 60050/60100/200/5000.1100/200/5000.3/0.8/20.15/0.4/13535355050––
––21027510314610
ca d
b
Internal accessories Alarm switch K Alarm switch with terminal block KA Auxiliary switch W Auxiliary switch with terminal block WA Undervoltage trip R Shunt trip F Test lead wire TL Megger test switch MGSExternal accessories Motor operating mechanism M Handle padlocking device Cap type Q1 Plate type Q2 Mechanical interlocking device M1 M2 M3 Operating handle N-type N Operating handle V-type V Steel enclosure Direct operating C Dustproof steel enclosure Handle operating CV Rainproof steel enclosure Handle operating CW Terminal cover Short TS Terminal cover Long TB Insulation barrier Interphase *1 B Insulation barrier Earth BL Handle locking cover L Flat terminal S
BZ6M170CBZ-M270CBZ-M370CBZ-N70CBZ6V70CBZ-C70BBZ-CV70C––BZ-TB70BB-43A–BZ-L70B–
BZ-K70BBZ-K70BABZ-W70BBZ-W70BABZ-R70B-BZ-F70B-
–
BZ6M170CBZ-M270CBZ-M370CBZ-N70CBZ6V70CBZ-C70BBZ-CV70C––BZ-TB70BB-43A–BZ-L70B–
BZ-K70BBZ-K70BABZ-W70BBZ-W70BABZ-R70B-BZ-F70B-
–
– –
Notes: *1 Interphase insulation barriers are standard provided for the front mounting type breakers of 50AF and over.
Factory-mounted accessoryAvailable – Not available
Rated voltage (V) Operationalvoltage range (V)
100–230–440 80–484
200–440 160–484
07/18Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit BreakersQuick reference guideLine protection
Rated voltage (V) Operationalvoltage range (V)
380–415 304–484
■ EG series/3P+1N
Note: * For motor-operated breaker, sensitive current and tripping time are fixed. Specify the sensitive current and tripping time when ordering.
Frame
Pole
Type
Phase and wire
Rated current (A) Ambient temp.: 40°C
Rated voltage (V)
Rated sensitive current (mA)
Tripping time (s)
Rated breaking capacity 415V AC(kA) 380V AC
Earth leakage tripping device
Overcurrent tripping device
Dimensions a(mm) b cPage 07/51 d
Mass (kg) Front mounting type
Front mounting, front connection No-mark rear connection X
Flush mounting, rear connection E top & bottom connection Y
Plug-in mounting P
Alarm switch KAuxiliary switch WUndervoltage trip RShunt trip FTest lead wire TLMegger test switch MGS
Motor operating mechanism M*Padlocking device QMechanical interlocking device M1Operating handle N-type NOperating handle G-type G
Steel enclosure CSteel enclosure with G-type handle CG
Terminal cover Inside panel use A1Terminal cover Outside panel use T1Insulation barrier Interphase BInsulation barrier Earth BL
100A
4
EG104A
3ø4W
30, 40, 50, 60, 75, 100
380-415
30, 100, 300, 500
0.1
14 14
Solid-state
Hydraulic-magnetic
120200 60 80
1.8
–
––
–
––––––
–––N-6EAG-5A
––
––––
ca d
b
Factory-mounted accessoryAvailable – Not available
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 07/19
Earth Leakage Circuit BreakersQuick reference guide
Line protection
07
Rated voltage (V) Operationalvoltage range (V)
100–230–440 80–484
200–440 160–484
■ HG series/3-pole
Frame
Pole
Type Instantaneous trip type
Time delay trip type
Phase and wire
Rated current (A) Ambient temp.: 40°C
Rated voltage (V AC) Instantaneous trip type
[JIS C 8201-2-2 Ann.2] Time delay trip type
Instantaneous trip type Rated sensitive current (mA)
Tripping time (s)
Time delay trip type Rated sensitive current (mA)
Tripping time (s)
Inertia non-tripping time (s) [2I∆n]
Rated breaking capacity 440V AC(kA) 415V AC[JIS C 8201-2-2 Ann.2] 400V AC 200V AC 100V AC
Earth leakage tripping device
Overcurrent tripping device
Dimensions a(mm) b cPage 07/52 d
Mass (kg) Front mounting type
Front mounting, front connection No-mark rear connection X
Flush mounting, rear connection E top & bottom connection Y
Plug-in mounting P
Alarm switch KAuxiliary switch WUndervoltage trip RShunt trip FTest lead wire TLMegger test switch MGS
Motor operating mechanism M*Padlocking device QMechanical interlocking device M1Operating handle N-type NOperating handle V-type VOperating handle G-type G
Steel enclosure CSteel enclosure with G-type handle CG
Terminal cover Short TSTerminal cover Long TBInsulation barrier Interphase BInsulation barrier Earth BL
50A
3
HG53B
HG53BD
3ø3W, 1ø3W, 1ø2W
15, 20, 30, 40, 50
100–230–440
200–440
30, 100/200/500
0.1
100/200/500
0.3/0.8/2
0.15/0.4/1
65 65 65100100
Solid-state
Thermal-magnetic
90155 82104
2.3
–
––
BZ-M130C-3BZ-N35B– BZ-G35C
BZ-C35B(CG-type BZ-CG35B)
BZ-TS35BBZ-TB35BBZ-B35BBZ-BL35B
100A
3
HG103B
HG103BD
3ø3W, 1ø3W, 1ø2W
15, 20, 30, 40, 50, 60, 75, 100
100–230–440
200–440
30, 100/200/500
0.1
100/200/500
0.3/0.8/2
0.15/0.4/1
65 65 65100100
Solid-state
Thermal-magnetic
90155 82104
2.3
–
––
BZ-M130C-3BZ-N35B–BZ-G35C
BZ-C35B(CG-type BZ-CG35B)
BZ-TS35BBZ-TB35BBZ-B35BBZ-BL35B
225A
3
HG203B
HG203BD
3ø3W, 1ø3W, 1ø2W
125, 150, 175, 200, 225
100–230–440
200–440
30, 100/200/500
0.1
100/200/500
0.3/0.8/2
0.15/0.4/1
65 65 65100100
Solid-state
Thermal-magnetic
105165 99127
3.3
–
––
BZ-M140CBZ-N50CBZ-V50C–
BZ-C50B–
BZ-TS50BBZ-TB50BBZ-B50BBZ-BL50B
ca d
b
Factory-mounted accessoryAvailable – Not availableNotes: • Terminal covers (Height: 5mm) are standard provided for the X and P mounting types of 50AF to 225AF.• Time delay trip types are also available on request.* For motor-operated breaker, sensitive current and tripping time are fixed. Specify the sensitive current and tripping time when ordering.
07/20Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit BreakersQuick reference guideLine protection
■ HG series/3-pole
Frame
Pole
Type Instantaneous trip type
Time delay trip type
Phase and wire
Rated current (A)
Rated voltage (V)
[JIS C 8201-2-2 Ann.2]
Instantaneous trip type Rated sensitive current (mA)
Tripping time (sec)
Time delay trip type Rated sensitive current (mA)
Tripping time (s)
Inertia non-tripping time (s) [2I∆n]
Rated breaking capacity 440V AC(kA) 415V AC[JIS C 8201-2-2 Ann.2] 400V AC 200V AC 100V AC
Earth leakage tripping device
Overcurrent tripping device
Dimensions a(mm) b cPage 07/53 d
Mass (kg) Front mounting type
Applicable wire size (Max. mm2)
Front mounting, front connection No-mark rear connection X
Flush mounting, rear connection E top & bottom connection Y
Plug-in mounting P
Alarm switch KAuxiliary switch WUndervoltage trip RShunt trip FTest lead wire TLMegger test switch MGSEarth leakage indication contact EAL
Motor operating mechanism M*Padlocking device QMechanical interlocking device M1Operating handle N-type NOperating handle V-type V
Steel enclosure CSteel enclosure with V-type handle CV
Terminal cover Short TSTerminal cover Long TBInsulation barrier Interphase BInsulation barrier Earth BL
400A
3
HG403B
HG403BD
3ø3W, 1ø3W, 1ø2W
250, 300, 350, 400
100–230–440
200–440
30, 100/200/500
0.1
100/200/500
0.3/0.8/2
0.15/0.4/1
65 65 65125125
Solid-state
Thermal-magnetic
140257103146
5.6
325
–
BZ-K70BBZ-W70BBZ-R70B-BZ-F70B-
BZ-M160CBZ-N60CBZ-V60C
BZ-C60BBZ-CV60C
–BZ-TB60BB-43A–
600A
3
HG603B
HG603BD
3ø3W, 1ø3W, 1ø2W
500, 600
100–230–440
200–440
100/200/500
0.1
100/200/500
0.3/0.8/2
0.15/0.4/1
65 65 65125125
Solid-state
Thermal-magnetic
210275103146
10
325
–
BZ-K70BBZ-W70BBZ-R70B-BZ-F70B-
BZ-M170CBZ-N70CBZ-V70C
BZ-C70BBZ-CV70C
–BZ-TB70BB-43A–
800A
3
HG803B
HG803BD
3ø3W, 1ø3W, 1ø2W
700, 800
100–230–440
200–440
100/200/500
0.1
100/200/500
0.3/0.8/2
0.15/0.4/1
65 65 65125125
Solid-state
Thermal-magnetic
210275103146
10
325
–
BZ-K70BBZ-W70BBZ-R70B-BZ-F70B-
BZ-M170CBZ-N70CBZ-V70C
BZ-C70BBZ-CV70C
–BZ-TB70BB-43A–
Factory-mounted accessoryAvailable – Not available
ca d
b
Note: * For motor-operated breaker, sensitive current and tripping time are fixed. Specify the sensitive current and tripping time when ordering.
Rated voltage (V) Operationalvoltage range (V)
100–230–440 80–484
200–440 160–484
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 07/21
Earth Leakage Circuit BreakersQuick reference guide
Motor protection
07
SG series IEC and CE marking conformed types
Instantaneous trip typeTime delay trip type
Instantaneous trip typeTime delay trip type
FramePoleType
Phase and wire
Rated voltage (V AC)[IEC 60947-2/JIS C 8201-2-2]Rated current (A) Frequency (Hz)Instantaneous trip type
Rated breaking capacity(kA)[IEC 60947-2/JIS C 8201-2-2](Icu/Ics) *1
Dimensions (mm) a bPage 07/45 c dMass (kg) Front mounting typeFront mounting, front connection No-markFront mounting, rear connection XFlush mounting, rear connection EFlush mounting, top & bottom connection YPlug-in mounting PIEC 35mm wide rail mounting
Rated sensitive current (mA)Tripping time (s)
440V AC415V AC400V AC230V AC100V AC
30A3SG33CM -CE–3ø3W1ø3W1ø2W100–230–440–0.7, 1.4, 2, 2.6, 4, 5, 8,10, 12, 16, 24, 3250/6030, 100/200/5000.12.5/22.5/22.5/25/35/3 75100 60 840.6
50A3SG53CM -CE–3ø3W1ø3W1ø2W100–230–440–0.7, 1.4, 2, 2.6, 4, 5, 8,10, 12, 16, 24, 32, 40, 45 50/6030, 100/200/5000.17.5/47.5/47.5/410/510/5 75100 60 840.6
Internal accessories Alarm switch K Alarm switch with terminal block KA Auxiliary switch W Auxiliary switch with terminal block WA Undervoltage trip R Shunt trip F Test lead wire TLExternal accessories Motor operating mechanism M Handle padlocking device Cap type Q1 Plate type Q2 Mechanical interlocking device M1 M2 M3 Operating handle N-type N Operating handle V-type V Steel enclosure Direct operating C Dustproof steel enclosure Handle operating CV Rainproof steel enclosure Handle operating CW Terminal cover Short TS Terminal cover Long TB Insulation barrier Interphase *2 B Insulation barrier Earth BL Handle locking cover L Flat terminal S
ca d
b
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C503
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C503
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C1003
––BZ6M130C3BZ-M230C-3BZ-M330C-3BZ-N30CBZ6V30CBZ6C30C3BZ-CV30CBZ-CW30CBZ-TS30B-3BZ-TB30B-3BZ-B30BBZ-BL35BBZ6L30CBZ-S35B-1003
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
BZ6K 30CBZ6K 30CABZ6W 30CBZ6W 30CA
60A3SG63CM -CE–3ø3W1ø3W1ø2W100–230–440–60
50/6030, 100/200/5000.17.5/47.5/47.5/410/510/5 75100 60 840.6
100A3SG103CM -CE–3ø3W1ø3W1ø2W100–230–440–75, 90
50/6030, 100/200/5000.125/725/730/850/2550/25 90155 60 821.3
Notes: *1 Icu: Rated ultimate short-circuit breaking capacity Ics: Rated service short-circuit breaking capacity *2 Interphase insulation barriers are standard provided for the front mounting type breakers of 50AF and over.
–
–
Factory-mounted accessoryAvailable – Not available
Rated voltage (V) Operationalvoltage range (V)
100–230–440 80–484
07/22Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit BreakersQuick reference guideMotor protection
SG series IEC and CE marking conformed types
Instantaneous trip typeTime delay trip type
Instantaneous trip typeTime delay trip type
FramePoleType
Phase and wire
Rated voltage (V AC)[IEC 60947-2/JIS C 8201-2-2]Rated current (A)Rated frequency (Hz)Instantaneous trip type
Rated breaking capacity(kA)[IEC 60947-2/JIS C 8201-2-2](Icu/Ics) *1
Dimensions (mm) a bPage 07/46 c dMass (kg) Front mounting typeFront mounting, front connection No-markFront mounting, rear connection XFlush mounting, rear connection EFlush mounting, top & bottom connection YPlug-in mounting PIEC 35mm wide rail mounting
Rated sensitive current (mA)Tripping time (s)
440V AC415V AC400V AC230V AC100V AC
ca d
b
Internal accessories Alarm switch K Alarm switch with terminal block KA Auxiliary switch W Auxiliary switch with terminal block WA Undervoltage trip R Shunt trip F Test lead wire TLExternal accessories Motor operating mechanism M Handle padlocking device Cap type Q1 Plate type Q2 Mechanical interlocking device M1 M2 M3 Operating handle N-type N Operating handle V-type V Steel enclosure Direct operating C Dustproof steel enclosure Handle operating CV Rainproof steel enclosure Handle operating CW Terminal cover Short TS Terminal cover Long TB Insulation barrier Interphase *2 B Insulation barrier Earth BL Handle locking cover L Flat terminal S
Notes: *1 Icu: Rated ultimate short-circuit breaking capacity Ics: Rated service short-circuit breaking capacity *2 Interphase insulation barriers are standard provided for the front mounting type breakers of 50AF and over.
100A3SG103RCM -CE–3ø3W1ø3W1ø2W100–230–440–45, 60, 75, 9050/6030, 100/200/5000.150/1350/1350/13100/50100/50 90155 60 821.3
––BZ6M130C3BZ-M230C-3BZ-M330C-3BZ-N30CBZ6V30CBZ6C30C3BZ-CV30CBZ-CW30CBZ-TS30B-3BZ-TB30B-3BZ-B30BBZ-BL35BBZ6L30CBZ-S35B-1003
BZ6K 30CBZ6K 30CABZ6W 30CBZ6W 30CA
–
–
225A3SG203CM -CE–3ø3W1ø3W1ø2W100–230–440–125, 150, 175, 225 50/6030, 100/200/5000.125/725/730/850/2550/25105165 60 841.5
3SG203RCM -CE–3ø3W1ø3W1ø2W100–230–440–125, 150, 175, 225 50/6030, 100/200/5000.150/1350/1350/13100/50100/50105165 60 841.5
––BZ6M140CBZ-M240CBZ-M340CBZ-N40CBZ6V40CBZ-C40BBZ-CV40CBZ-CW40CBZ-TS40BBZ-TB40BBZ-B40BBZ-BL40BBZ6L40CBZ-S50B-2253
BZ6K 40CBZ6K 40CABZ6W 40CBZ6W 40CA
–
––BZ6M140CBZ-M240CBZ-M340CBZ-N40CBZ6V40CBZ-C40BBZ-CV40CBZ-CW40CBZ-TS40BBZ-TB40BBZ-B40BBZ-BL40BBZ6L40CBZ-S50B-2253
BZ6K 40CBZ6K 40CABZ6W 40CBZ6W 40CA
–
– –
Factory-mounted accessoryAvailable – Not available
Rated voltage (V) Operationalvoltage range (V)
100–230–440 80–484
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 07/23
Earth Leakage Circuit BreakersQuick reference guide
Motor protection
07
Instantaneous trip typeTime delay trip type
Instantaneous trip typeTime delay trip type
FramePoleType
Phase and wire
Rated voltage (V AC)[IEC 60947-2/JIS C 8201-2-2]Rated current (A)
Rated frequency (Hz)Instantaneous trip type
Rated breaking capacity(kA)[IEC 60947-2/JIS C 8201-2-2](Icu/Ics) *1
Dimensions (mm) a bPage 07/49 c dMass (kg) Front mounting typeFront mounting, front connection No-markFront mounting, rear connection XFlush mounting, rear connection EFlush mounting, top & bottom connection YPlug-in mounting PIEC 35mm wide rail mounting
Rated sensitive current (mA)Tripping time (s)
440V AC415V AC400V AC230V AC100V AC
30A3EG33CM -CE–3ø3W1ø3W1ø2W100–230–440–1.4, 2.6, 4, 5, 8, 10, 16, 24, 3250/6030, 1000.11.5/11.5/11.5/12.5/25/3 75100 60 840.6
Internal accessories Alarm switch K Alarm switch with terminal block KA Auxiliary switch W Auxiliary switch with terminal block WA Undervoltage trip R Shunt trip F Test lead wire TLExternal accessories Motor operating mechanism M Handle padlocking device Cap type Q1 Plate type Q2 Mechanical interlocking device M1 M2 M3 Operating handle N-type N Operating handle V-type V Steel enclosure Direct operating C Dustproof steel enclosure Handle operating CV Rainproof steel enclosure Handle operating CW Terminal cover Short TS Terminal cover Long TB Insulation barrier Interphase *2 B Insulation barrier Earth BL Handle locking cover L Flat terminal S
ca d
b
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C503
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C503
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
BZ6K 10CBZ6K 10CABZ6W 10CBZ6W 10CABZ6R 10CBZ6F 10C
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C10C3BZ6CV10CBZ6CW10CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C1003
–
BZ6M110C3BZ6M210C3BZ6M310C3BZ6N10CBZ6V10CBZ6C25C3BZ6CV25CBZ6CW25CBZ6TS10C3BZ6TB10C3BZ6B10CBZ6BL10C3BZ6L10CBZ6S10C1003
3EG53CM -CE–3ø3W1ø3W1ø2W100–230–440–45
50/6030, 100/2000.12.5/22.5/22.5/25/35/3 75100 60 840.6
3EG63CM -CE–3ø3W1ø3W1ø2W100–230–440–60
50/6030, 100/2000.12.5/22.5/22.5/25/35/3 75100 60 840.6
50A 60A 100A3EG103CM -CE–3ø3W1ø3W1ø2W100–230–440–60, 75, 90
50/6030, 100/200/5000.110/510/510/525/1325/13 75100 60 840.6
225A3EG203CM -CE–3ø3W1ø3W1ø2W100–230–440–125, 150, 175, 22550/6030, 100/200/5000.115/415.418/535/1835/18105165 60 841.5
–––––BZ6N40CBZ6V40CBZ-C40BBZ-CV40CBZ-CW40CBZ-TS40BBZ-TB40BBZ-B40BBZ-BL40BBZ6L40CBZ-S50B-2253
BZ6K 40C
BZ6W 40C
–
–
Factory-mounted accessoryAvailable – Not availableNotes: *1 Icu: Rated ultimate short-circuit breaking capacity Ics: Rated service short-circuit breaking capacity *2 Interphase insulation barriers are standard provided for the front mounting type breakers of 50AF and over.
EG series IEC and CE marking conformed types
Rated voltage (V) Operationalvoltage range (V)
100–230–440 80–484
07/24Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit BreakersQuick reference guideUL Listed
SG series UL489 Listed
Instantaneous trip typeTime delay trip type
Instantaneous trip typeTime delay trip type
FramePoleType
Phase and wire
Rated voltage (V AC)[IEC 60947-2/JIS C 8201-2-2]Rated current (A)Frequency (Hz)Instantaneous trip type
Rated breaking capacity (kA)
Dimensions (mm) a bPage 07/54 c dMass (kg) Front mounting typeConnecting terminal Screw Flat Block
Rated sensitive current (mA)Tripping time (s)UL489 240V ACCSA C22.2 No.5IEC 60947-2 440V ACJIS C 8201-2-2 415V AC[Icu/Ics] *1 400V AC 230V AC 100V AC
50A3SG53RCUL–3ø3W1ø3W1ø2W100–230–440–3, 5, 10, 15, 20, 30, 40, 5050/6030, 100/200/5000.114
10/510/510/525/1325/13 75120 60 840.6
–
100A3SG103CUL–3ø3W1ø3W1ø2W100–230–440–32, 40, 50, 60, 75, 10050/6030, 100/200/5000.135
25/725/730/850/1350/13 90155 60 821.3
Internal accessories Alarm switch K Alarm switch with terminal block KA Auxiliary switch W Auxiliary switch with terminal block WA Undervoltage trip with terminal block RA Shunt trip with terminal block FA Test lead wire TLExternal accessories Handle padlocking device Cap type Q1 Operating handle N-type N Operating handle V-type V Terminal cover Short TS Terminal cover Long TB Terminal cover For flat terminal TL Insulation barrier Interphase *2 B Handle locking cover L Flat terminal S Block terminal –
ca d
b
–BZ6N10CPBZ6V10CProvidedBZ6TB10C3U––BZ6L10CBZ-SU20B
BZ6K 10CUBZ6K 10CAUBZ6W 10CUBZ6W 10CAUBZ6R 10CAUBZ6F 10CAU
–BZ6N30CPBZ6V30CBZ-TS30B-3BZ-TB30B-3BZ-TL30B-3BZ6B30CUBZ6L30CBZ6SU35BBZ6TA100
BZ6K 30CU
BZ6W 30CU
225A3SG203CUL–3ø3W1ø3W1ø2W100–230–440–125, 150, 175, 200, 22550/6030, 100/200/5000.135
25/725/730/850/1350/13105165 65 841.5
–BZ6N40CPBZ6V40CBZ-TS40BBZ-TB40BBZ-TL40BBZ6B40CUBZ6L40CBZ6SU50BBZ6TA225
BZ6K 40CU
BZ6W 40CU
400A3SG403CUL–3ø3W1ø3W1ø2W100–230–440–250, 300, 350, 40050/6030, 100/200/5000.142
35/1835/1835/1850/2550/251402571031465.6–
BZ6N60CPBZ6V60C–BZ-TB60B–B-43ABZ-L70B––
Notes: *1 Icu: Rated ultimate short-circuit breaking capacity Ics: Rated service short-circuit breaking capacity *2 Interphase insulation barriers are standard provided for the front mounting type breakers of 50AF and over.
Factory-mounted accessoryAvailable – Not available
Rated voltage (V) Operationalvoltage range (V)
100–230–440 80–484
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 07/25
Earth Leakage Circuit BreakersQuick reference guide
UL Listed
EG series UL489 Listed
Internal accessories Alarm switch K Alarm switch with terminal block KA Auxiliary switch W Auxiliary switch with terminal block WA Undervoltage trip with terminal block RA Shunt trip with terminal block FA Test lead wire TL Megger test switch MGSExternal accessories Handle padlocking device Cap type Q1 Operating handle N-type N Operating handle V-type V Terminal cover Short TS Terminal cover Long TB Terminal cover For flat terminal TL Insulation barrier Interphase *2 B Handle locking cover L Flat terminal S Block teminal
–BZ6N10CPBZ6V10CProvidedBZ6TB10C3U––BZ6L10CBZ-SU20B–
BZ6K 10CUBZ6K 10CAUBZ6W 10CUBZ6W 10CAUBZ6R 10CAUBZ6F 10CAU
–
BZ6K 10CU
BZ6W 10CU
BZ6R 10CAUBZ6F 10CAU
–
–BZ6N10CPBZ6V10CProvidedBZ6TB10C3U––BZ6L10CBZ-SU20B–
Instantaneous trip typeTime delay trip type
Instantaneous trip typeTime delay trip type
FramePoleType
Phase and wire
Rated voltage (V AC)[IEC 60947-2/JIS C 8201-2-2]Rated current (A)Rated frequency (Hz)Instantaneous trip type
Rated breaking capacity (kA)
Dimensions (mm) a bPage 07/55 c dMass (kg) Front mounting typeConnecting terminal Screw Flat Block
Rated sensitive current (mA)Tripping time (s)
2EG102CUL–1ø2W
100–230-440–60, 70, 75, 80, 90, 10050/6030, 100/2000.114
–––10/510/5 75120 60 840.6
–
3EG103CUL–3ø3W1ø3W1ø2W100–230–440–60, 70, 75, 80, 90, 10050/6030, 100/200/5000.114
10/510/510/525/1325/13 75120 60 840.6
–
100A
UL489 [cUL] 240V ACCSA C22.2 No.5IEC 60947-2 440V ACJIS C 8201-2-2 415V AC[Icu/Ics] *1 400V AC 230V AC 100V AC
ca d
b
Notes: *1 Icu: Rated ultimate short-circuit breaking capacity Ics: Rated service short-circuit breaking capacity *2 Interphase insulation barriers are standard provided for the front mounting type breakers of 50AF and over. Except for EG50AC and EG100AC
Factory-mounted accessoryAvailable – Not available
Rated voltage (V) Operationalvoltage range (V)
100–230–440 80–484
07/26Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Earth Leakage Circuit BreakersQuick reference guideMotor protection
Circuit configuration and breaker application for controlpanels of industrial machinery in North America.
UL508A (Industrial control panels) requirements
1. The requirements of NFPA70 (NEC), NFPA79, andapplicable UL standards must be satisfied.
2. Positioning of protective equipment• Install branch circuit protection (BCP) for the main circuit at
the point of electrical inlet.• Use equipment that is UL508 listed as applicable to each
kind of loads, installed under appropriate load conditions,as protective equipment for load circuits used in branchcircuits downstream from the BCP.
UL508/Group Installation, which combines UL489 Listed SG/EG-UL series and UL508 Listed Manual Motor Controllers(MMCs), complies with the UL508A requirements for NorthAmerican industrial control panels.
UL489Listed
Item NEC430.53 Group Installation
SG/EG-ULseries
UL508Listed
1 Applicable to motor loads
2 Applicable to other general use loads
3 Applicable to resistance loads (heaters)
4 Applicable to discharge lamp loads
5 Applicable to incandescent lamp loads
Includes an isolating function.
1
2345
Application of UL489 Listed SG/EG-UL series andUL508 Listed MMCs (Group installation)
1. For group installations, if the UL489 Listed SG/EG-ULseries is installed at the power inlet point (upstream) andany of the following conditions is satisfied in the circuit, aUL508 Listed MMC can be used as a downstream multi-circuit protective device. (In accordance with NEC430.53.)
a. No conductor to the motor shall have an ampacity lessthan that of the branch-circuit conductors.
b. No conductor to the motor shall have an ampacity lessthan one-third than of the branch-circuit conductors, theconductors to the motor overload device being not morethan 7.5m(25ft) long and being protected from physicaldamage.
c. Conductors from the branch-circuit short-circuit andground-fault protective device to a listed manual motorcontroller shall be permitted to have an ampacity not lessthan 1/10 the rating or setting of the branch-circuit short-circuit and ground-fault protective device. The conductorsfrom the branch-circuit short-circuit and ground-faultprotective device to the controller shall (1) be suitablyprotected from physical damage and enclosed either by anenclosed controller or by a raceway and shall be not morethan 3m(10ft) long or (2) shall have an ampacity not lessthan that of the branch circuit conductors.
2. The UL508 Listed MMC also has UL508 Group Installationcertification.
3. See NEC 430.53 for detail.
4. Refer to the table on the next page for breaking capacity ofthe UL508 Listed Group Installation when making yourselection.
Fuji Electric FA Components & Systems Co., Ltd./D & C CatalogInformation subject to change without notice 07/27
Earth Leakage Circuit BreakersQuick reference guide
Motor protection
07
Group Installation
2 UL508 Listed MMCsSA30CSA50CSA50RCSA60CSA60RCEA30ACEA50ACEA50CEA60CEA100ACEA100C
1 UL489 Listed MCCBs (+ UL1053)SA53RCULSG53RCUL
5kA10kA25kA10kA25kA
5kA5kA5kA5kA5kA
25kA
SA103CULSA103RCULEA103CULEG103CUL
5kA10kA25kA10kA25kA
5kA5kA5kA5kA5kA
25kA
SA203CULSA203RCULSG103CUL
5kA10kA25kA10kA25kA
5kA5kA5kA5kA5kA
25kA
SA403CULSA403RCULSG203CUL
5kA10kA25kA10kA25kA
5kA5kA5kA5kA5kA
25kA
SA603RCUL
– – –
10kA25kA
– – –
5kA5kA
25kA
SA803RCUL
– – –
10kA25kA
– – –
5kA5kA
25kA
240V AC for UL508 Listed MMC ( 2 in figure) combined with UL489 Listed MCCB (+ UL1053) ( 1 in figure)
480V AC for UL508 Listed MMC ( 2 in figure) combined with UL489 Listed MCCB (+ UL1053) ( 1 in figure)
240V AC for UL508 Listed MMC + UL1053 ( 2 in figure) combined with UL489 Listed MCCB (+ UL1053) ( 1 in figure)
2 UL508 Listed MMCsSA30CSA50CSA50RCSA60CSA60RCEA50CEA60CEA100C
1 UL489 Listed MCCBs (+ UL1053)SA103RCUL
5kA10kA10kA10kA10kA
5kA5kA
10kA
SA203RCUL5kA
10kA10kA10kA10kA
5kA5kA
10kA
SA403RCUL5kA
10kA10kA10kA10kA
5kA5kA
10kA
SA603RCUL – – –
10kA10kA
–5kA
10kA
SA803RCUL – – –
10kA10kA
–5kA
10kA
2 UL508 Listed MMCs + UL1053SG33CSG53CSG53RCSG63CSG63RCEG32AC, EG33ACEG33CEG52AC, EG53ACEG53CEG63CEG102AC, EG103ACEG103C
1 UL489 Listed MCCBs (+ UL1053)SA53RCULSG53RCUL
5kA10kA25kA10kA25kA
5kA5kA5kA5kA5kA5kA
25kA
SA103CULSA103RCULEA103CULEG103CUL
5kA10kA25kA10kA25kA
5kA5kA5kA5kA5kA5kA
25kA
SA203CULSA203RCULSG103CUL
5kA10kA25kA10kA25kA
5kA5kA5kA5kA5kA5kA
25kA
SA403CULSA403RCULSG203CUL
5kA10kA25kA10kA25kA
5kA5kA5kA5kA5kA5kA
25kA
SA603RCUL
– – –
10kA25kA
– – – –
5kA5kA
25kA
SA803RCUL
– – –
10kA25kA
– – – –
5kA5kA
25kA
1
2
UL489 Listed MCCB or UL489