SITE PLANNING DATA

SYSTEM 9395-825 ISBM, MODELS 650, 750, 825kVA, SINGLE M

ODULE

MAINTENANCE BYPASS SWITCHGEAR (OPTION)

AC OUTPUT

MIS

MBP

TO LOAD

UPS M

ODULE

ISBM

BYPASS

AC INPUT

MBB

RECTIFIER

CB1 (OPTION)

BATTERY

AC INPUT

UPM1

UPM2

UPM3

UPM1

UPM2

UPM3

Notes:

ISBM

1. Rectiÿer AC input current calculations: Continuous - 100% load without charging; Nameplate -

9. The UPS cabinet can be installed in line-up-and-m

atch or standalone conÿgurations.

100% load with m

axim

um charging.

10. Top and bottom cable entries through removable access plates are standard for all conÿgurations.

2. Inverter AC output current calculation: Nameplate - 100% rated output load.

Access plates shall be custom-m

odiÿed to suit conduit sizes.

3. Bypass AC input current calculation is based on 100% rated output.

11. All wiring is to be in accordance with National and Local Electric Codes.

4. The system m

ust be installed on a level "oor suitable for computer or electronic equipment.

12. AC input to UPS rectiÿer (0.98 m

in.pF): (3) phases, (1) ground.

5. The system m

ust be installed in a temperature and humidity controlled indoor area

AC output to load: (3) phases, (1) neutral if required, (1) ground.

free of conductive contaminants.

AC input to UPS bypass: (3) phases, (1) neutral if required, (1) ground.

6. Ambient temperature range: 0-40C (32-104F); Recommended operating range: 20-25C (68-77F);

DC input from battery to UPS: (1) positive, (1) negative, (1) ground.

Maxim

um relative humidity: 95% non-condensing.

13. The front panels m

ust be removed to m

eet the 830mm (or 32.7" depth) to ÿt through doors.

7. Minim

um overhead clearance for ventilation above the UPS cabinet is 457mm (18in.).

14. If the UPS is to be installed with the right side near a wall a m

inim

um of 6" is required betw

een the

8. Minim

um 915mm (36in.) clearance in front of the UPS cabinet is required for cooling air intake

wall and the unit. If a battery cabinet is installed to the right of the UPS the 6" are not required.

and servicing space.

15. Speciÿcations are subject to change.

Product Speciÿcations

Battery

Inverter AC

Nameplate

AC

Max. Battery Current

AC

Rectiÿer AC Input Current

Max. Heat

Approx. Weight

Output Current

UPS Rating

Input

Current

Output

Floor Loading

at End of Discharging

Dissipation at

Dim

ensions W

xDxH

Unpacked

Voltage

Voltage

(240 Cell,

(240 Cell, 1.67V/cell)

Continuous

100% Load

Nameplate

Nameplate

2.00 V/cell)

kW(BTU/hr)

mm(in)

kg(lbs)

kg/m

2(lb/ft2)

kVA

kW

VAC

VAC

AMP

AMP

AMP

AMP

AMP

3578x830x1872

37.1 (126716)

2297 (5065)

774 (158)

650

591

480

480

763

891

782

1280

1559

(140.9x32.7x73.7)

3578x830x1872

42.8 (146211)

2297 (5065)

774 (158)

750

682

480

480

880

1028

902

1502

1799

(140.9x32.7x73.7)

3578x830x1872

47.1 (160832)

2297 (5065)

774 (158)

825

750

480

480

969

1130

992

1600

1979

(140.9x32.7x73.7)

11/3/08

P/N

110100215-001 Sheet 8 of 10 Rev. 1

!"#$%%%%++

Page 10: Eaton 9395 200–1100 kVA dimension

SITE PLANNING DATA

SYSTEM 9395-825 ISBM SEPARATE RECTIFIER FEEDS, M

ODELS 650, 750, 825kV

A, SINGLE M

ODULE

MAINTENANCE BYPASS SWITCHGEAR (OPTION)

AC OUTPUT

MIS

MBP

TO LOAD

UPS M

ODULE

ISBM

BYPASS

AC IN

PUT

MBB

BATTERY

RECTIFIER

AC IN

PUTS

UPM1

UPM2

UPM3

UPM1

UPM2

UPM3

Notes:

ISBM

1. Rectiÿer AC in

put current calculations: Continuous - 100% load without ch

arging; N

ameplate -

9. The UPS cabinet can be in

stalled in

line-up-and-m

atch or standalone conÿgurations.

100% load with m

aximum charging.

10. Top and bottom cable entries through removable access plates are standard for all conÿgurations.

2. Inverter AC output current calculation: N

ameplate - 100% rated output load.

Access plates shall be custom-m

odiÿed to suit conduit sizes.

3. Byp

ass AC in

put current calculation is based on 100% rated output.

11. A

ll wiring is to be in

accordance with National and Local Electric Codes.

4. The system m

ust be in

stalled on a level !oor suitable for computer or electronic equipment.

12. A

C in

put to UPS rectiÿer (0.98 m

in.pF): (3) phases, (1) ground.

5. The system m

ust be in

stalled in

a temperature and humidity controlled in

door area

AC output to load: (3) phases, (1) neutral if required, (1) ground.

free of conductive contaminants.

AC in

put to UPS byp

ass: (3) phases, (1) neutral if required, (1) ground.

6. A

mbient temperature range: 0-40C (32-104F); Recommended operating range: 20-25C (68-77F);

DC in

put from battery to UPS: (1) positive, (1) negative, (1) ground.

Maximum relative humidity: 95% non-condensing.

13. The front panels m

ust be removed to m

eet the 830mm (or 32.7" depth) to ÿt through doors.

7. M

inim

um overhead clearance for ventilation above the UPS cabinet is 457mm (18in.).

14. If the UPS is to be in

stalled with the right side near a wall a m

inim

um of 6" is required betw

een the

8. M

inim

um 915mm (36in.) clearance in

front of the UPS cabinet is required for coolin

g air in

take

wall and the unit. If a battery cabinet is in

stalled to the right of the UPS the 6" are not required.

and servicing space.

15. Speciÿcations are subject to change.

Product Speciÿcations

Battery

Inverter AC

Rectiÿer AC In

put Current

Nameplate

AC

Max. Battery Current

AC

Max. Heat

Approx. W

eight

Output Current

Per UPM

UPS Rating

Input

Floor Loading

Current

Output

at End of Disch

arging

Dissipation at

Dim

ensions WxD

xH

Unpacked

Voltage

Voltage

(240 Cell,

(240 Cell, 1.67V/cell)

Continuous

100% Load

Nameplate

Nameplate

2.00 V/cell)

kW(BTU/hr)

mm(in)

kg(lbs)

kg/m

2(lb/ft2)

kVA

kW

VAC

VAC

AMP

AMP

AMP

AMP

AMP

3578x830x1872

37.1 (126716)

2297 (5065)

774 (158)

650

591

480

480

255

370

782

1280

1559

(140.9x32.7x73.7)

3578x830x1872

42.8 (146211)

2297 (5065)

774 (158)

750

682

480

480

294

370

902

1502

1799

(140.9x32.7x73.7)

3578x830x1872

47.1 (160832)

2297 (5065)

774 (158)

825

750

480

480

323

370

992

1600

1979

(140.9x32.7x73.7)

P/N

110100215-002 Sheet 5 of 7 Rev. 1

!"#$%%%%+.

Page 11: Eaton 9395 200–1100 kVA dimension

SITE PLANNING DATA

SYSTEM 9395-825 PLUS 1 ISBM, MODELS 650, 750, 825kVA, SINGLE M

ODULE

MAINTENANCE BYPASS SWITCHGEAR (OPTION)

AC OUTPUT

MIS

MBP

TO LOAD

UPS M

ODULE

ISBM

BYPASS

AC INPUT

MBB

RECTIFIER

CB1 (OPTION)

BATTERY

AC INPUT

UPM1

UPM2

UPM3

UPM4

UPM4

ISBM

UPM1

UPM2

UPM3

Notes:

1. Rectiÿer AC input current calculations: Continuous - 100% load without charging; Nameplate -

9. The UPS cabinet can be installed in line-up-and-m

atch or standalone conÿgurations.

100% load with m

axim

um charging.

10. Top and bottom cable entries through removable access plates are standard for all conÿgurations.

2. Inverter AC output current calculation: Nameplate - 100% rated output load.

Access plates shall be custom-m

odiÿed to suit conduit sizes.

3. Bypass AC input current calculation is based on 100% rated output.

11. All wiring is to be in accordance with National and Local Electric Codes.

4. The system m

ust be installed on a level "oor suitable for computer or electronic equipment.

12. AC input to UPS rectiÿer (0.98 m

in.pF): (3) phases, (1) ground.

5. The system m

ust be installed in a temperature and humidity controlled indoor area

AC output to load: (3) phases, (1) neutral if required, (1) ground.

free of conductive contaminants.

AC input to UPS bypass: (3) phases, (1) neutral if required, (1) ground.

6. Ambient temperature range: 0-40C (32-104F); Recommended operating range: 20-25C (68-77F);

DC input from battery to UPS: (1) positive, (1) negative, (1) ground.

Maxim

um relative humidity: 95% non-condensing.

13. The front panels m

ust be removed to m

eet the 830mm (or 32.7" depth) to ÿt through doors.

7. Minim

um overhead clearance for ventilation above the UPS cabinet is 457mm (18in.).

14. If the UPS is to be installed with the right side near a wall a m

inim

um of 6" is required betw

een the

8. Minim

um 915mm (36in.) clearance in front of the UPS cabinet is required for cooling air intake

wall and the unit. If a battery cabinet is installed to the right of the UPS the 6" are not required.

and servicing space.

15. Speciÿcations are subject to change.

Product Speciÿcations

Battery

Inverter AC

AC

AC

Max. Battery Current

Rectiÿer AC Input Current

Max. Heat

Nameplate

Output Current

Approx. Weight

UPS Rating

Input

Output

at End of Discharging

Dissipation at

Dim

ensions W

xDxH

Floor Loading

Current

Unpacked

Voltage

Voltage

(240 Cell, 1.67V/cell)

Continuous

100% Load

(240 Cell,

Nameplate

Nameplate

2.00 V/cell)

kW(BTU/hr)

mm(in)

kg(lbs)

kg/m

2(lb/ft2)

kVA

kW

VAC

VAC

AMP

AMP

AMP

AMP

AMP

4322x830x1872

37.1 (126716)

2887 (6365)

805 (165)

650

591

480

480

763

891

782

1280

1559

(170.2x32.7x73.7)

4322x830x1872

42.8 (146211)

2887 (6365)

805 (165)

750

682

480

480

880

1028

902

1502

1799

(170.2x32.7x73.7)

4322x830x1872

47.1 (160832)

2887 (6365)

805 (165)

825

750

480

480

969

1130

992

1600

1979

(170.2x32.7x73.7)

11/3/08

P/N

110100215-001 Sheet 9 of 10 Rev. 1

!"#$%%%%+'

Page 12: Eaton 9395 200–1100 kVA dimension

SITE PLANNING DATA

SYSTEM 9395-825 PLUS 1 ISBM SEPARATE RECTIFIER FEEDS, MODELS 650, 750, 825kVA, SINGLE M

ODULE

MAINTENANCE BYPASS SWITCHGEAR (OPTION)

AC OUTPUT

MIS

MBP

TO LOAD

UPS M

ODULE

ISBM

BYPASS

AC INPUT

MBB

BATTERY

RECTIFIER

AC INPUTS

UPM1

UPM2

UPM3

UPM4

UPM4

ISBM

UPM1

UPM2

UPM3

Notes:

1. Rectiÿer AC input current calculations: Continuous - 100% load without charging; Nameplate -

9. The UPS cabinet can be installed in line-up-and-m

atch or standalone conÿgurations.

100% load with m

axim

um charging.

10. Top and bottom cable entries through removable access plates are standard for all conÿgurations.

2. Inverter AC output current calculation: Nameplate - 100% rated output load.

Access plates shall be custom-m

odiÿed to suit conduit sizes.

3. Bypass AC input current calculation is based on 100% rated output.

11. All wiring is to be in accordance with National and Local Electric Codes.

4. The system m

ust be installed on a level "oor suitable for computer or electronic equipment.

12. AC input to UPS rectiÿer (0.98 m

in.pF): (3) phases, (1) ground.

5. The system m

ust be installed in a temperature and humidity controlled indoor area

AC output to load: (3) phases, (1) neutral if required, (1) ground.

free of conductive contaminants.

AC input to UPS bypass: (3) phases, (1) neutral if required, (1) ground.

6. Ambient temperature range: 0-40C (32-104F); Recommended operating range: 20-25C (68-77F);

DC input from battery to UPS: (1) positive, (1) negative, (1) ground.

Maxim

um relative humidity: 95% non-condensing.

13. The front panels m

ust be removed to m

eet the 830mm (or 32.7" depth) to ÿt through doors.

7. Minim

um overhead clearance for ventilation above the UPS cabinet is 457mm (18in.).

14. If the UPS is to be installed with the right side near a wall a m

inim

um of 6" is required betw

een the

8. Minim

um 915mm (36in.) clearance in front of the UPS cabinet is required for cooling air intake

wall and the unit. If a battery cabinet is installed to the right of the UPS the 6" are not required.

and servicing space.

15. Speciÿcations are subject to change.

Product Speciÿcations

Battery

Inverter AC

Rectiÿer AC Input Current

Max. Battery Current

AC

AC

Max. Heat

Nameplate

Output Current

Approx. Weight

Per UPM

UPS Rating

Input

Output

Dissipation at

Dim

ensions W

xDxH

Floor Loading

Current

at End of Discharging

Unpacked

Voltage

Voltage

(240 Cell, 1.67V/cell)

Continuous

100% Load

(240 Cell,

Nameplate

Nameplate

2.00 V/cell)

kW(BTU/hr)

mm(in)

kg(lbs)

kg/m

2(lb/ft2)

kVA

kW

VAC

VAC

AMP

AMP

AMP

AMP

AMP

4322x830x1872

37.1 (126716)

2887 (6365)

805 (165)

650

591

480

480

255

370

782

1280

1559

(170.2x32.7x73.7)

4322x830x1872

42.8 (146211)

2887 (6365)

805 (165)

750

682

480

480

294

370

902

1502

1799

(170.2x32.7x73.7)

4322x830x1872

47.1 (160832)

2887 (6365)

805 (165)

825

750

480

480

323

370

992

1600

1979

(170.2x32.7x73.7)

11/3/08

P/N

110100215-002 Sheet 6 of 7 Rev. 1

!"#$%%%%+(

Page 13: Eaton 9395 200–1100 kVA dimension

SITE PLANNING DATA

SYSTEM 9395-1100 ISBM, MODELS 1000, 1100kVA, SINGLE M

ODULE

MAINTENANCE BYPASS SWITCHGEAR (OPTION)

AC OUTPUT

MIS

MBP

TO LOAD

UPS M

ODULE

BYPASS

AC INPUT

ISBM

MBB

RECTIFIER

CB1 (OPTION)

BATTERY

AC INPUT

UPM1

UPM2

UPM3

UPM4

UPM4

ISBM

UPM1

UPM2

UPM3

Notes:

1. Rectiÿer AC input current calculations: Continuous - 100% load without charging; Nameplate -

9. The UPS cabinet can be installed in line-up-and-m

atch or standalone conÿgurations.

100% load with m

axim

um charging.

10. Top and bottom cable entries through removable access plates are standard for all conÿgurations.

2. Inverter AC output current calculation: Nameplate - 100% rated output load.

Access plates shall be custom-m

odiÿed to suit conduit sizes.

3. Bypass AC input current calculation is based on 100% rated output.

11. All wiring is to be in accordance with National and Local Electric Codes.

4. The system m

ust be installed on a level "oor suitable for computer or electronic equipment.

12. AC input to UPS rectiÿer (0.98 m

in.pF): (3) phases, (1) ground.

5. The system m

ust be installed in a temperature and humidity controlled indoor area

AC output to load: (3) phases, (1) neutral if required, (1) ground.

free of conductive contaminants.

AC input to UPS bypass: (3) phases, (1) neutral if required, (1) ground.

6. Ambient temperature range: 0-40C (32-104F); Recommended operating range: 20-25C (68-77F);

DC input from battery to UPS: (1) positive, (1) negative, (1) ground.

Maxim

um relative humidity: 95% non-condensing.

13. The front panels m

ust be removed to m

eet the 830mm (or 32.7" depth) to ÿt through doors.

7. Minim

um overhead clearance for ventilation above the UPS cabinet is 457mm (18in.).

14. If the UPS is to be installed with the right side near a wall a m

inim

um of 6" is required betw

een the

8. Minim

um 915mm (36in.) clearance in front of the UPS cabinet is required for cooling air intake

wall and the unit. If a battery cabinet is installed to the right of the UPS the 6" are not required.

and servicing space.

15. Speciÿcations are subject to change.

Product Speciÿcations

Battery

Inverter AC

AC

AC

Max. Battery Current

Rectiÿer AC Input Current

Max. Heat

Nameplate

Output Current

Approx. Weight

UPS Rating

Input

Output

at End of Discharging

Dissipation at

Dim

ensions W

xDxH

Floor Loading

Current

Unpacked

Voltage

Voltage

(240 Cell, 1.67V/cell)

Continuous

100% Load

(240 Cell,

Nameplate

Nameplate

2.00 V/cell)

kW(BTU/hr)

mm(in)

kg(lbs)

kg/m

2(lb/ft2)

kVA

kW

VAC

VAC

AMP

AMP

AMP

AMP

AMP

4322x830x1872

57.1 (194948)

2960 (6525)

825 (169)

1000

909

480

480

1174

1370

1203

2000

2398

(170.2x32.7x73.7)

4322x830x1872

62.8 (214443)

2960 (6525)

825 (169)

1100

1000

480

480

1291

1507

1323

2203

2638

(170.2x32.7x73.7)

11/3/08

P/N

110100215-001 Sheet 10 of 10 Rev. 1

!"#$%%%%+)

Page 14: Eaton 9395 200–1100 kVA dimension

SITE PLANNING DATA

SYSTEM 9395-1100 ISBM SEPARATE RECTIFIER FEEDS, MODELS 1000, 1100kVA, SINGLE M

ODULE

MAINTENANCE BYPASS SWITCHGEAR (OPTION)

AC OUTPUT

MIS

MBP

TO LOAD

UPS M

ODULE

ISBM

BYPASS

AC INPUT

MBB

BATTERY

RECTIFIER

AC INPUTS

UPM1

UPM2

UPM3

UPM4

UPM4

ISBM

UPM1

UPM2

UPM3

Notes:

1. Rectiÿer AC input current calculations: Continuous - 100% load without charging; Nameplate -

9. The UPS cabinet can be installed in line-up-and-m

atch or standalone conÿgurations.

100% load with m

axim

um charging.

10. Top and bottom cable entries through removable access plates are standard for all conÿgurations.

2. Inverter AC output current calculation: Nameplate - 100% rated output load.

Access plates shall be custom-m

odiÿed to suit conduit sizes.

3. Bypass AC input current calculation is based on 100% rated output.

11. All wiring is to be in accordance with National and Local Electric Codes.

4. The system m

ust be installed on a level "oor suitable for computer or electronic equipment.

12. AC input to UPS rectiÿer (0.98 m

in.pF): (3) phases, (1) ground.

5. The system m

ust be installed in a temperature and humidity controlled indoor area

AC output to load: (3) phases, (1) neutral if required, (1) ground.

free of conductive contaminants.

AC input to UPS bypass: (3) phases, (1) neutral if required, (1) ground.

6. Ambient temperature range: 0-40C (32-104F); Recommended operating range: 20-25C (68-77F);

DC input from battery to UPS: (1) positive, (1) negative, (1) ground.

Maxim

um relative humidity: 95% non-condensing.

13. The front panels m

ust be removed to m

eet the 830mm (or 32.7" depth) to ÿt through doors.

7. Minim

um overhead clearance for ventilation above the UPS cabinet is 457mm (18in.).

14. If the UPS is to be installed with the right side near a wall a m

inim

um of 6" is required betw

een the

8. Minim

um 915mm (36in.) clearance in front of the UPS cabinet is required for cooling air intake

wall and the unit. If a battery cabinet is installed to the right of the UPS the 6" are not required.

and servicing space.

15. Speciÿcations are subject to change.

Product Speciÿcations

Battery

Inverter AC

Rectiÿer AC Input Current

AC

AC

Max. Battery Current

Max. Heat

Nameplate

Output Current

Approx. Weight

Per UPM

UPS Rating

Input

Output

Dissipation at

Dim

ensions W

xDxH

Floor Loading

Current

at End of Discharging

Unpacked

Voltage

Voltage

(240 Cell, 1.67V/cell)

Continuous

100% Load

(240 Cell,

Nameplate

Nameplate

2.00 V/cell)

kW(BTU/hr)

mm(in)

kg(lbs)

kg/m

2(lb/ft2)

kVA

kW

VAC

VAC

AMP

AMP

AMP

AMP

AMP

4322x830x1872

57.1 (194948)

2960 (6525)

825 (169)

1000

909

480

480

294

370

1203

2000

2398

(170.2x32.7x73.7)

4322x830x1872

62.8 (214443)

2960 (6525)

825 (169)

1100

1000

480

480

323

370

1323

2203

2638

(170.2x32.7x73.7)

11/3/08

P/N

110100215-002 Sheet 7 of 7 Rev. 1

!"#$%%%%+*