Rack PDU plugs and receptaclesThis cheat sheet provides an overview of the different styles of plugs and receptacles for Eaton rackmount PDUs.
R indicates receptacle P indicates plug L indicates locking plug or receptacle
L6-30R L6-30P L14-30R L14-30P
5-15R 5-15P 5-20R 5-20P
L5-20R L5-20P L5-30R L5-30P
6-15R 6-15P L6-20R L6-20P
16A 32A
General PDU environment specifications
• Operating temperature is 0 to 60˚C (32 to 140˚F)
• Altitude maximum 10,000 ft.
• Relative humidity is 95% max non-condensing
Learn more at Eaton.com/PDU
Eaton.com/PDU
Eaton1000 Eaton Boulevard Cleveland, OH 44122 United StatesEaton.com
©2021 EatonAll Rights ReservedPrinted in USAPDU37FXA / GGOctober 2021
Eaton is a registered trademark.
All other trademarks are property of their respective owners.
IEC309
332P6250V
30A 60A
360P6250V
30A
532P63ØY230/400V
60A 60A 60A
460P93Ø250V
560P93ØY120/208V
563P63ØY230/400V
50A, 2P3W250V
Y
G
X
Y
X
ZG
HBLCS8265C HBLCS8365C
Y
G
X
Y
X
ZG
50A, 3P4W
3Ø250V
IEC320
C13 C14
North AmericanEurope
20 amp 250 volts16 amp 250 volts
C19 C20
15 amp 250 volts10 amp 250 volts
Standard NEMA plugs
L22-30277/480V30A3 phase wyetwist lock
5-20120V20A1 phasestraight blade
L5-20120V20A1 phasetwist lock
L5-30120V30A 1 phasetwist lock
5-15 120V15A1 phasestraight blade
6-20208V20A1 phasestraight blade
L6-20208V20A1 phase twist lock
L6-30 208V30A, 1 phasetwist lock
L14-30120/240V30A2 phase (split phase)
L21-20 120/208V20A, 3 phase wyetwist lock
L21-30120/208V30A3 phase wyetwist lock
L15-20208V20A3 phase deltatwist lock
L15-30208V30A3 phase deltatwist lock
L22-20277/480V20A3 phase wyetwist lock
Eaton C39 universal outlet:The C39 outlet allows both C14 and C20 plugs to connect into a single outlet. Like its NEMA counterpart the 5-20P, the C39 outlet allows for both 15- and 20-amp inlets. This flexibility allows you to swap out equipment without having the inconvenience of re-ordering a new rack PDU to meet specific outlet count requirements on a per rack basis.