EC Fans Energy Efficiency / Upgrade Projects Helen McHugh ebm-papst Ian Shaw CBRE Proprietary and confidential information. Any circulation of this document or parts of it in whatsoever form without explicit permission of ebm-papst is strictly forbidden.
Transcript
Page 1: EC Fans Efficiency / Upgrade Projects

EC Fans Energy Efficiency / Upgrade Projects Helen McHugh ebm-papst

Ian Shaw CBRE

Proprietary and confidential information. Any circulation of this document or parts of it in whatsoever form without explicit permission of ebm-papst is strictly forbidden.

Page 2: EC Fans Efficiency / Upgrade Projects

Topics Covered

The role of fans in building energy efficiency

Energy legislation relating to Fans & Motors

EC Fans - What are they?

How they can reduce your buildings energy consumption?

Case Studies

Upgrade projects - energy savings & payback

1. Data Centre cooling - Large Investment bank

2. FCU - Multinational professional services firm HQ

3. AHU - MERCEDES AMG PETRONAS Formula OneTM Team

4. Condenser - Marks & Spencer

Page 4: EC Fans Efficiency / Upgrade Projects

Energy efficiency

ErP Directive

IE 4

IE 3

IE 2

1 5 10 kW Shaft Power

Mo

tor

effi

cien

cy

95

90

85

(%)

ebm-papst

EC Motors

Energy savings resulting from ErP legislation

ebm-papst calculate

(using ebm-papst fan sales across Europe)

1.75 TWh saving / year Jan 13 – Dec 14

3.25 TWh saving / year Since Jan 15

Motors: minimum of IE3 - for motor sizes > 7.5kW (0.75kW from Jan 17)

Fans: minimum efficiency for individual fan types. Min efficiency level will increase from Jan 2020

Page 5: EC Fans Efficiency / Upgrade Projects

What is an EC motor ?

Traditional AC motor EC motor

AC to DC

conversion

Commutation

Electronics

Permanent magnet

Stator

Rotor

2 sets of copper windings

External speed control required

Low efficiency (copper losses & Induction)

Stator

Windings

Permanent magnet on rotor.

AC mains Input – converted to DC onboard

Integrated variable speed control (0 – 10v or PWM)

High efficiency (>IE4 as standard)

Page 6: EC Fans Efficiency / Upgrade Projects

Key Benefits of using EC Technology

Energy Efficiency Reduced Noise

Permanent magnet motors are more energy efficient Reduced noise under speed control

than standard induction motors

System Efficiency Compact Design

EC fans operate outside their preferred operating range Integrated motor & speed control

& still maintain a high efficiency

Speed Control Reduced Maintenance

Integrated speed control no additional VSD needed No belts & pulleys

Infinitely variable speed using 0 – 10v input

Can deliver constant volume, constant pressure etc Built in Power Factor Correction

Monitoring & Alarms

Remote control, monitoring, and alarms via Modbus

Page 7: EC Fans Efficiency / Upgrade Projects

Case Studies Energy efficiency & Control

Energy savings achieved by upgrading to EC fans

Savings resulting from both improved motor efficiency & optimising system design

Case Studies covered - HVAC applications

Data Centre / Computer room cooling

Fan Coils

Air Handling Units

Condenser

Page 8: EC Fans Efficiency / Upgrade Projects

Case Study – Data Centre Cooling

Investment Bank

Page 9: EC Fans Efficiency / Upgrade Projects

Case Study – Data Centre Cooling

Investment Bank

The aims of the project:

• Improve the energy efficiency of the data centre.

• Free up supply capacity.

• Improve the air flow and controllability.

Save money on Utility Bills (including TRIAD) and CRCEES.

Data Centre 130,000 sq ft (12,000m2) of IT racks

21,500 tonnes CO2 pa (£344,000 for CRC)

PUE 2.13

Costs £3.36m pa (energy)

Close to the edge

Page 10: EC Fans Efficiency / Upgrade Projects

Case Study – Data Centre Cooling

Investment Bank

Old equipment

Intensive maintenance

Access issues

24/7 critical environment

Capital (£) shortage

Changing IT requirements

Very tight and controlled time schedules to tie in with other data

centres around the world.

9 week programme 2 units per day (in different areas).

Sufficient cooling at all times.

CDM (Form10) – HSE notifiable.

The Answer

Replace fans in 77 CRAC - DFUs with EC fans.

Change control strategy from Return to Supply air.

Page 11: EC Fans Efficiency / Upgrade Projects

Case Study – Data Centre Cooling

Investment Bank

Measurements prior to and following installation;

• Air flow

• Amps

• Volts

• Noise

Continuous commissioning.

100% duty Matching Air

Flow New Controls

Average 38% 54% 68%

Maximum 62% 72% 83%

Minimum 19% 45% 54%

Page 12: EC Fans Efficiency / Upgrade Projects

Case Study – Data Centre Cooling

Investment Bank

Page 13: EC Fans Efficiency / Upgrade Projects

Case Study – Data Centre Cooling

Investment Bank

Predicted From fans Total (pumps etc)

Site Metered

% of Building Load 3.6% 4.9% 7.95%

Load Reduction 180kW 250kW -

Consumption 1,577,000kWh 2,190,000kWh 3,454,000kWh

Cash Savings £168,000 £233,000 £368,000

Tonnes CO2 870 1,210 1,910

Simple payback 33 Months 23.5 Months 12.1 Months

Capital Cost £371,547

Page 14: EC Fans Efficiency / Upgrade Projects

The aims of the upgrade were to:

• Reduce the energy consumption of the heating, ventilation and air conditioning (HVAC) equipment

• Reduce the noise

• Reduce the need for maintenance

• Increase the controllability of the HVAC system in the building

Case Study

Fan Coil Units - Company HQ building London

Upgrade Fan Coil Units

in the London HQ of Multinational Professional Services Firm as part of a major refurbishment.

Replacing AC fan motors coming to the end of their life with EC fans with a customised control platform.

1,200 FCUs in total across a ten floor building.

Page 15: EC Fans Efficiency / Upgrade Projects

Measurements

Taken on individual FCU’s before and after

the EC fans were fitted

Old Deck New Deck Saving

Large 247W 49W 80%

Small 150W 54W 64%

Old AC twin fan deck New EC double fan unit

Case Study

Fan Coil Units - Company HQ building London

Page 16: EC Fans Efficiency / Upgrade Projects

Induction Motor (AC)

motor efficiency @ Operation point 25 %

Energy consumed per FCU. 150 W

SFP = 0.75

EC Motor (permanent magnet)

motor efficiency @ Operating point 78 %

Energy consumed per FCU. 54 W

SFP = 0.25

64% energy saving

Savings (annual) Single 2 fan unit 1,200 units

Energy (kWh) 464 556,800

Value (£) £46.40 £55,800

CO2 (tonnes) 0.253 304

Case Study

Fan Coil Units - Company HQ building London

Page 17: EC Fans Efficiency / Upgrade Projects

Case Study - AHU MERCEDES AMG PETRONAS Formula OneTM Team

Trane AHU

Belt driven AC blower

motor + standby

EC plug fan

+ standby

Page 18: EC Fans Efficiency / Upgrade Projects

Cost £3,000

AC Fan power 5.9kW

EC Fan power 2.1kW

Total Saving 64%

Annual saving (kWh) 15,410 kWh

Annual saving (£) £1,325

Payback Period 2.3 years

Case Study - AHU MERCEDES AMG PETRONAS Formula OneTM Team

Page 19: EC Fans Efficiency / Upgrade Projects

Stores: 152

Condensers: 258

Fans: 1,404 (910mm Axial + AxiTop)

Energy saving 22%

3,265kWh / fan

4,584,060 kWh (total)

Financial saving £527,223 / year

ROI < 5 years

Case Study - Condenser M&S - EC fans & AxiTop

Page 20: EC Fans Efficiency / Upgrade Projects

Thank you

Helen McHugh

Head of New Product Research

ebm-papst UK Ltd