+ All Categories
Home > Documents > EC-TVPE EXAMINATION CERTIFICATE

EC-TVPE EXAMINATION CERTIFICATE

Date post: 16-Oct-2021
Category:
Upload: others
View: 5 times
Download: 0 times
Share this document with a friend
3
1 EC-TVPE EXAMINATION CERTIFICATE ~ 2 Equipment or Protective systems intended for use in Potentially Explosive Atmospheres - Directive 94/9/EC EC-Type Examination Certificate No: FM07ATEXOO28 Equipment or protective system: HPT Heat Trace Cable Systems (Type Reference and Name) 3 4 5 Name of Applicant: Thermon Europe B.V. 6 Address of Applicant: Boezemweg 25 2461 KG Pijnacker The Netherlands 7 This equipment or protective system and any acceptable variation thereto is specified in the schedule to this certificate and documents therein referred to. 8 FM Approvals Ltd, notified body number 1725 in accordance with Article 9 of Directive 94/9/EC of 23 March 1994, certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of equipment intended for use in potentially explosive atmospheres given in Annex 11 to the Directive. The examination and test results are recorded in confidential report number 3029771EC dated th J 4 anuary 2008. 9 Compliance with the Essential Health and Safety Requirements, with the exception of those identified in item 15 of the schedule to this certificate, has been assessed by compliance with the following documents: EN 60079-0: 2006, EN 60079-7: 2003, EN 61241-0: 2006, EN 61241-1: 2004, EN62086-1: 2005 and EN 60259: 1991 + A 1: 2000. 10 If the sign 'X' is placed after the certificate number, it indicates that the equipment is subject to special conditions for safe use specified in the schedule to this certificate. 11 This EC-Type Examination certificate relates only to the design, examination and tests of the specified equipment or protective system in accordance to the directive94/9/EC. Furtherrequirementsof the Directive apply to the manufacturing process and supply of this equipment or protective system. These are not covered by this certificate. 12 The marking of the equipment or protective system shall include: (Q 112 G Ex e 11T2 to T6 Ta=-60°C to +55°C IP66/67 112 D Ex to A21 T300°C to T85°C Ta=-60°C to +55°C IP66/67 ~~ ~pprovalS' Andrew Was General Manager, FM Approvals Ltd. Issue date: 4th January 2008 AI m,ltfT oj 11" PM GIc;j,aJ Cm"p THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE FMApprovalsLtd.1WindsorDials,Windsor,Berkshire, UK.SL41RS T: +44(0) 1753750000 F:+44(0) 1753868700 E-mail:[email protected] www.fmalobal.com FM F ATEX 020 (Feb/07) Page 1 of 3
Transcript
Page 1: EC-TVPE EXAMINATION CERTIFICATE

1

EC-TVPE EXAMINATION CERTIFICATE ~2 Equipment or Protective systems intended for use in Potentially

Explosive Atmospheres - Directive 94/9/EC

EC-Type Examination Certificate No: FM07ATEXOO28

Equipment or protective system: HPT Heat Trace Cable Systems(Type Reference and Name)

3

4

5 Name of Applicant: Thermon Europe B.V.

6 Address of Applicant: Boezemweg 252461 KG PijnackerThe Netherlands

7 This equipment or protective system and any acceptable variation thereto is specified in the schedule to thiscertificate and documents therein referred to.

8 FM Approvals Ltd, notified body number 1725 in accordance with Article 9 of Directive 94/9/EC of 23 March1994, certifies that this equipment has been found to comply with the Essential Health and SafetyRequirements relating to the design and construction of equipment intended for use in potentially explosiveatmospheres given in Annex 11to the Directive.The examination and test results are recorded in confidential report number 3029771EC dated

th J4 anuary 2008.

9 Compliance with the Essential Health and Safety Requirements, with the exception of those identified initem 15of the schedule to this certificate, has been assessed by compliance with the following documents:EN 60079-0: 2006, EN 60079-7: 2003, EN 61241-0: 2006, EN 61241-1: 2004, EN62086-1: 2005 andEN 60259: 1991 + A 1: 2000.

10 If the sign 'X' is placed after the certificate number, it indicates that the equipment is subject to specialconditions for safe use specified in the schedule to this certificate.

11 This EC-Type Examination certificate relates only to the design, examination and tests of the specifiedequipment or protective system in accordanceto the directive94/9/EC. Furtherrequirementsof the Directiveapply to the manufacturing process and supply of this equipment or protective system. These are notcovered by this certificate.

12 The marking of the equipment or protective system shall include:

(Q 112 G Ex e 11T2 to T6 Ta=-60°C to +55°C IP66/67112 D Ex to A21 T300°C to T85°C Ta=-60°C to +55°C IP66/67

~~~pprovalS'

Andrew Was

General Manager, FM Approvals Ltd.

Issue date: 4th January 2008AI m,ltfT oj 11" PM GIc;j,aJ Cm"p

THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE

FMApprovalsLtd.1WindsorDials,Windsor,Berkshire,UK.SL41RST: +44(0) 1753750000 F:+44(0) 1753868700 E-mail:[email protected]

FM F ATEX 020 (Feb/07) Page 1 of 3

Page 2: EC-TVPE EXAMINATION CERTIFICATE

SCHEDULE ~PProvals'M'm"n of,h,'nf CI"n,,1Gmup

to EC-Type Examination Certificate No. FM07 ATEXOO28

13 Description of Equipment or Protective System:

The HPT Heat Trace Cable Systems are power-limiting heating cables specifically designed for processtemperature maintenance or freeze protection where high maintain temperatures or high temperatureexposure is required. A coiled resistor alloy heating element provides the power-limiting feature of thecable. This PTC (Positive Temperature Coefficient) characteristic decreases the cable's power output asthe heat traced product temperature increases and allows the cable to be overlapped during installation.The composite construction of the heating element and fiber substrate, plus an additional fiber cushionlayer, provides for durability of the heating cable.

Product Listing: The specific models described by this report willbe shown in the ElectricalEquipmentportionof the FMApprovalGuide, a publicationof FMApprovals, as follows:

HPT a-b-c-d-e. Parallel Constant Watt Electrical Heat Trace Cable Systems.

a = Nominal Output, W/ft @ 50°F (W/m @10°C): 5 (16),10 (33),15 (49), 20 (66), or custom (up to 20 W/ft(66 W/m)).b = Voltage: 1 (120 Vac), 2 (240 Vac), 4 (480 Vac), or custom (up to 600 Vac).c = Outerjacket material option: OJ (standard) or BN.d = Additional conductor option: PC (Power Conductor).e = Large conductor option: XR (10 AWG).Maximum maintain temperature: 149°C (higher maintenance temperatures may be possible based onThermon CompuTrace software or Thermon Engineering according to calculations based on suitableparameters).Maximum exposure temperature: 260°C for HPT trace heating cable (power off), 240°C for PETK-3(D),SCTK-3, ET-8C kits.Minimum bend radius: 32 mm @ -60°C, 9.5 mm @ -15°C.

14 Special Conditions for Safe Use:

None

15 Essential Health and Safety Requirements:

The relevant EHSRs that have not been addressed by the standards listed in this certificate have beenidentified and assessed in the confidential report identified in item 8.

16 Test and Assessment Procedure and Conditions:

This EC-Type Examination Certificate is the result of testing of a sample of the product submitted, inaccordance with the provisions of the relevant specific standard(s), and assessment of supportingdocumentation. It does not imply an assessment of the whole production.

Whilst this certificate may be used in support of a manufacturer's claim for CE Marking, FM ApprovalsLtd accepts no responsibility for the compliance of the equipment against all applicable Directives in allapplications.

This Certificate has been issued in accordance with FM Approvals Ltd's ATEX Certification Scheme.

THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE

FM Approvals Ltd. 1 Windsor Dials, Windsor, Berkshire, UK. SL4 1RST: +44 (0) 1753 750 000 F: +44 (0) 1753 868 700 E-mail: [email protected] www.fmqlobal.comFM F A TEX 020 (Feb/O?) Page 2 of 3

Page 3: EC-TVPE EXAMINATION CERTIFICATE

SCHEDULE ~pprovalS"Munh" of ,h,' FM Clohed Cn"'p

to EC-Type Examination Certificate No. FM07ATEXOO28

17 Approved Drawings

THIS C~RTIFICAT~ MAY ONLY B~ R~PRODUC~D IN ITS ENTIRETY AND WITHOUT CHANGE

FM Approvals Ltd. 1 Windsor Dials, Windsor, Berkshire, UK. SL4 1RST: +44 (0) 1753 750 000 F: +44 (0) 1753 868 700 E-mail: [email protected] www.fmolobal.com

FM F ATEX 020 (Feb/07) Page 3 of 3

Drawing Rev DescriptionNumber

A0115002 5 HPT Power Limiting Heatina Cable Desian SpecificationsHPT-XR (10 AWG) Power Limiting Heating Cable Design

A0115010 4 SpecificationsB0208011 6 ET-8 End Cap DrawinaB0209002 7 TBX-4L Termination Boot DrawinaOP 5.61.3 06/15/2007 HPT Cable Marking ProcedurePN 50072 1106 ET-8C End Cap Installation InstructionsPN 50132 0406 PETK Power and End Termination Kit Installation InstructionsPN 50135 0107 SCTK Splice Connection Termination Kit Installation InstructionsPN 50207U 1107 Electrical Heat Tracina Installation InstructionsTEP0011 U 1106 HPT Product Specifications27048 10/07 Reel Wrapper Label