Introduction: This manual covers the assembly, installation, start up, operation and maintenance of the 1300 and 1600 remote low side cuber systems. An illustrated parts list and wiring diagram is in the center of this manual. Keep this manual for future reference. Eclipseä 1300,1600 September 2003 Page 1 Table of Contents Introduction: · · · · · · · · · · · · · · · · · · Page 1 Configuration: · · · · · · · · · · · · · · · · · Page 2 Technical Specifications · · · · · · · · · · · · Page 3 Model Number Locations · · · · · · · · · · · Page 4 Cabinet Drawings, Ice Making System · · · · Page 5 Cabinet Drawings, Compressor Package and Condensers · · · · · · · · · · · · · · · · · · Page 6 Proper Combinations: · · · · · · · · · · · · · Page 7 CreatetheSystem· · · · · · · · · · · · · · · Page 8 SystemExamples · · · · · · · · · · · · · · · Page 9 SystemExamples · · · · · · · · · · · · · · · Page 10 Place Remote System· · · · · · · · · · · · · Page 11 SystemLocation· · · · · · · · · · · · · · · · Page 12 Route Tubing ················· Page 13 Ice Making Section ·············· Page 14 Compressor Package · · · · · · · · · · · · · Page 15 Condensing Section Assembly · · · · · · · · Page 16 Condensing Section Assembly · · · · · · · · Page 17 Icemakingsection: · · · · · · · · · · · · · · Page 18 Bin Thermostat - Routing · · · · · · · · · · · Page 19 Bin Thermostat - Bracket & Bulb ······· Page 20 WaterandDrain· · · · · · · · · · · · · · · · Page 21 WaterandDrain· · · · · · · · · · · · · · · · Page 22 Ice Making Section Set Up ·········· Page 23 Coupling Connections: ············ Page 24 Condensing Unit Connections · · · · · · · · · Page 25 FinalPlacement · · · · · · · · · · · · · · · · Page 26 Controller Operation · · · · · · · · · · · · · · Page 27 Initial Start Up - 1300 and 1600 · · · · · · · · Page 28 PurgeAdjustment · · · · · · · · · · · · · · · Page 29 SystemOperation:· · · · · · · · · · · · · · · Page 30 Refrigeration Details: · · · · · · · · · · · · · Page 31 Technicians Only: Freeze Cycle Sequence of Operation ·························Page32 Technicians Only: Harvest Cycle Sequence of Operation · · · · · · · · · · · · · · · · · · · Page 33 Power and Water Interruptions · · · · · · · · Page 34 Sanitation and Cleaning · · · · · · · · · · · · Page 35 OtherMaintenance · · · · · · · · · · · · · · Page 36 WaterDistributors · · · · · · · · · · · · · · · Page 37 IceSensors · · · · · · · · · · · · · · · · · · Page 38 Water Level Sensor Maintenance · · · · · · · Page 39 ServiceDiagnosis · · · · · · · · · · · · · · · Page 40 ServiceDiagnosis · · · · · · · · · · · · · · · Page 41 ServiceDiagnosis · · · · · · · · · · · · · · · Page 42 Controller Features & Last Error Recall · · · · Page 43 Operational Characteristics 1300 lb system · · Page 44 Operational Characteristics 1600 lb system · · Page 45 Refrigeration System Service · · · · · · · · · Page 46 Note this symbol when it appears. It indicates a potential hazard.
Transcript
Page 1: eclipselargeman - static-pt.com

Introduction:This manual covers the assembly, installation, startup, operation and maintenance of the 1300 and1600 remote low side cuber systems.

An illustrated parts list and wiring diagram is in the

center of this manual.

Keep this manual for future reference.

Eclipse� 1300,1600

September 2003Page 1

Table of Contents

Introduction: · · · · · · · · · · · · · · · · · · Page 1

Configuration: · · · · · · · · · · · · · · · · · Page 2

Technical Specifications · · · · · · · · · · · · Page 3

Model Number Locations · · · · · · · · · · · Page 4

Cabinet Drawings, Ice Making System · · · · Page 5

Cabinet Drawings, Compressor Package andCondensers · · · · · · · · · · · · · · · · · · Page 6

Proper Combinations: · · · · · · · · · · · · · Page 7

Create the System· · · · · · · · · · · · · · · Page 8

System Examples · · · · · · · · · · · · · · · Page 9

System Examples · · · · · · · · · · · · · · · Page 10

Place Remote System · · · · · · · · · · · · · Page 11

System Location · · · · · · · · · · · · · · · · Page 12

Route Tubing · · · · · · · · · · · · · · · · · Page 13

Ice Making Section · · · · · · · · · · · · · · Page 14

Compressor Package · · · · · · · · · · · · · Page 15

Condensing Section Assembly · · · · · · · · Page 16

Condensing Section Assembly · · · · · · · · Page 17

Ice making section: · · · · · · · · · · · · · · Page 18

Bin Thermostat - Routing · · · · · · · · · · · Page 19

Bin Thermostat - Bracket & Bulb · · · · · · · Page 20

Water and Drain · · · · · · · · · · · · · · · · Page 21

Water and Drain · · · · · · · · · · · · · · · · Page 22

Ice Making Section Set Up · · · · · · · · · · Page 23

Coupling Connections: · · · · · · · · · · · · Page 24

Condensing Unit Connections · · · · · · · · · Page 25

Final Placement · · · · · · · · · · · · · · · · Page 26

Controller Operation · · · · · · · · · · · · · · Page 27

Initial Start Up - 1300 and 1600 · · · · · · · · Page 28

Purge Adjustment · · · · · · · · · · · · · · · Page 29

System Operation:· · · · · · · · · · · · · · · Page 30

Refrigeration Details: · · · · · · · · · · · · · Page 31

Technicians Only: Freeze Cycle Sequence of Operation· · · · · · · · · · · · · · · · · · · · · · · · · Page 32

Technicians Only: Harvest Cycle Sequence ofOperation · · · · · · · · · · · · · · · · · · · Page 33

Power and Water Interruptions · · · · · · · · Page 34

Sanitation and Cleaning · · · · · · · · · · · · Page 35

Other Maintenance · · · · · · · · · · · · · · Page 36

Water Distributors · · · · · · · · · · · · · · · Page 37

Ice Sensors · · · · · · · · · · · · · · · · · · Page 38

Water Level Sensor Maintenance · · · · · · · Page 39

Service Diagnosis · · · · · · · · · · · · · · · Page 40

Service Diagnosis · · · · · · · · · · · · · · · Page 41

Service Diagnosis · · · · · · · · · · · · · · · Page 42

Controller Features & Last Error Recall · · · · Page 43

Operational Characteristics 1300 lb system · · Page 44

Operational Characteristics 1600 lb system · · Page 45

Refrigeration System Service · · · · · · · · · Page 46

Note this symbol when it appears. Itindicates a potential hazard.

Page 2: eclipselargeman - static-pt.com

Configuration:A remote low side cuber system includes severalsub systems: an ice making section, a remotecompressor package, and a remote air cooledcondenser. Additionally, there are two models ofeach sub-system and this manual covers all ofthem.

The ice making sections are designed for useindoors in a controlled environment. The remotecompressor packages and condensers aredesigned to operate outdoors. Each sub-systemhas limits for power, water and temperature.

Operational Limitations:

Minimum Maximum

Air Temp (IMS) 50oF 100

oF.

Air Temp (CU) -20oF. 120

oF.

Water Temp 40oF. 100

oF.

Water Pressure 20 psi 80 psi

Voltage (IMS) 104 126

Voltage (CU) 198 253

IMS = Ice Making Section, CU= Condensing Unit

Do Not operate the machine in conditions beyondthese limitations. Doing so will void the warranty.

Scotsman ice systems are designed andmanufactured with the highest regard for safetyand performance. They meet or exceed thestandards of UL and NSF.

Scotsman assumes no liability of responsibility ofany kind for products manufactured by Scotsmanthat have been altered in any way, including theuse of any part and/or other components notspecifically approved by Scotsman.

Scotsman reserves the right to make designchanges and/or improvements at any time.

Specifications and design are subject to changewithout notice.

Warranty

Refer to the warranty coverage in effect when theequipment was sold. Warranty statements areincluded with each product.

Systems:

Each sub-system is a separate entity that carriesits own model and serial number. They must becombined to create a remote cuber low sidesystem.

Eclipse� 1300, 1600

September 2003Page 2

System ModelNumber

Condensing Unit (CU) Ice Making Section (IMS)

Compressor Package Condenser

Model Electrical Model Electrical Model Electrical

Eclipse 1300-42 CP1316-32A 208-230/60/1ERC1086 -32A 208-230/60/1 CME1386RLS-1A 115/60/1

Eclipse 1300-43 CP1316-3A 208-230/60/3

Eclipse 1600-42 CP1316-32A 208-230/60/1ERC1086-32A 208-230/60/1 CME1686RLS-1A 115/60/1

Eclipse 1600-43 CP1316-3A 208-230/60/3

Notes: Voltage Codes are at the end of the model number. Codes read Voltage/Hertz/Phase. Those relatedto these products include:

-1 = 115/60/1

-3 = 208-230/60/3

-32 = 208-230/60/1

-42 = 115/60/1 and 208-230/60/1 (separate units)

-43 = 115/60/1 and 208-230/60/3 (separate units)

System Information

Pre-charged tubing kits are required tointerconnect the IMS to the CP.

Interconnecting 24 volt control wire ships with theCP unit.

Page 3: eclipselargeman - static-pt.com

Technical SpecificationsIce Making Section (IMS)

Compressor Package (CP)

Condenser

* * ERC condenser fan motor is powered from CPunit and the ERC’s ampacity is included in CP unitnumbers.

Note: The ERC1086 does NOT contain aheadmaster. The headmaster is in the CP units.

Note: 75 feet of interconnecting control wire (24volt) is included with the CP units.

Eclipse� 1300,1600

September 2003Page 3

Model Voltage Minimum CircuitAmpacity

Max Fuse Size Cabinet Size Weight (lb)

CME1386RLS-1A 115/60/1 3 15 30”w x 24”d x 28”h 144

CME1686RLS-1A 115/60/1 3 15 same 154

Model Voltage ContainsHeadmaster?

MinimumCircuit

Ampacity

MaxFuseSize

RefrigerantCharge (R-404A)*

Cabinet Size Weight(lb)

CP1316-32A 208-230/60/1 Yes 24.3 30 18 lb 29 ¾” w x 18”d x 34 ½” h 180

CP1316-3A 208-230/60/3 Yes 15.3 20 18 lb same 180

* Includes entire system charge.

Model Voltage ContainsHeadmaster?

NumberofCircuits

MinimumCircuit

Ampacity**

MaxFuseSize**

Cabinet Size, with legs Weight(lb)

ERC1086-32A 208-230/60/1 No 1 1.25 15 29 ¾”w x 28 5/8”d x 38 ½”h 95

Page 4: eclipselargeman - static-pt.com

Model Number LocationsIce Making Section

The dataplate on the back of the ice machinecontains the model number, serial number andelectrical data.

A second plate, located behind the front panel atthe lower left front, also lists the model and serialnumbers.

Compressor Package

The dataplate on the right side of thecompressor package contains the modelnumber, serial number, electrical data andsystem refrigerant charge.

A second plate, located behind the frontpanel in front of the compressor, also liststhe model number, serial number andrefrigerant charge.

Condenser

The dataplate lists the condenser’selectrical information plus the modeland serial numbers.

On the ERC1086 it is located on the sideopposite the refrigeration connections.

Eclipse� 1300, 1600

September 2003Page 4

Dataplatelocation for

CP Unit

Dataplatelocation forERC1086

Dataplatelocation forIce Making

Section

Page 5: eclipselargeman - static-pt.com

Cabinet Drawings, Ice Making System

Eclipse� 1300,1600

September 2003Page 5

�����

����

���

�����

�� ���

��� ���� ����

�� ������

����������

���� ���

����� �����

�����

����

����

�����

����

���� ���

���� ����

��� �����

�����

�� � �

��!���

����������

���� ���

����������

����

����

ThermostatRouting Hole,

13” from front,4.63” from side

Page 6: eclipselargeman - static-pt.com

Cabinet Drawings, Compressor Package and Condensers

Eclipse� 1300, 1600

September 2003Page 6

BACK VIEW

FRONT VIEW

RIGHT SIDE VIEW

1/2" COOL VAPOR LINE

0.88 ELECTRICAL INLET

3/4" SUCTION LINE

INTERFACE HARNESS

ACCESS HOLE

3/8" CONDENSER LIQUID LINE (OUT)

1/2" CONDENSER DISCHARGE LINE (IN)

CONDENSER FAN WIRE ROUTING

ERC680 or ERC1086:This Side Attaches toCP1316

27.90

28.53

35.72

2.75

Liquid LineDischargeLine

29.50

38.47

33.19

6.6822.51

29.19

9/16” Mounting Hole 9/16” Mounting Hole

23.5”

1.5” 1.5”

3/8" LIQUID LINE

15”1.5” 1.5”

Page 7: eclipselargeman - static-pt.com

Proper Combinations:The three sub systems are designed to beconnected together in certain combinations to meetthe user’s needs:

Eclipse 1300 System:

�CME1386, CP1316, ERC1086

Eclipse 1600 System:

�CME1686, CP1316, ERC1086

ERC1086 may be substituted for by an approvedcentral condenser coil & fan (coil must be withoutheadmaster - headmaster is part of CP1316).

Condenser coil internal volume target is 165 cubicinches, BHTU target is 42,000 BTUH.

Note: The ice making section cannot be stackedvertically.

Accessories such as bin adapters and tubing kitsare required to complete the installation.

Dispenser Adapter Kits:

�Scotsman ID200 or ID250: KBT44

Note: Dispensers with two rotors. If possible, theice making head should NOT be centered left toright between the two rotors. It should be shiftedslightly to one side, and the agitation should beminimized.

Bin Adapter Kits:

�BH800: KBT23

�BH801: KBT29

�BH900: KBT22

Tubing Kits:

�20 foot: 3RTE20

�35 foot: 3RTE35

�50 foot: 3RTE50

�75 foot: 3RTE75

�Suction Line Trap: KSLT075

�Interconnecting Tubing to Approved RackCondenser Coil: RTE10

�Line end kit: KTE6

Items required for installation:

�Ice making section

�Compressor Package (includes interconnectingcontrol system wire)

�Remote condenser or approved rack coilw/tubing kit

�20’, 35’, 50’ or 75’ triple line set (liquid, vaporand suction)

�Bin or dispenser adapter

Special Considerations

The ice making section’s footprint is 30” wide by24” deep. The refrigeration connections can bemade out the top panel or out the back. Theelectrical power cord and the water inlet line canalso be routed through either of those areas. Thedrain may be routed out the back or to the left side.

The bin thermostat, when deployed, will be about5” below the bottom of the cabinet, and that iswhere the ice will fill to. This ice level maximizesice storage without overfilling the bin or dispenser.

Water

Pure water does not exist. All water suppliescontain some amounts of impurities, althoughpotable water is, by definition, fit for humanconsumption. Because the contents of the water toan ice machine directly impact its performance,consideration should be given to improving thewater’s quality.

There are two ways water can contain impurities:in suspension or in solution. Suspended solids canbe filtered out of the water. In solution or dissolvedsolids must be diluted or treated. Water filters arerecommended to remove the suspended solids.Some filters or filter systems have treatmentchemicals in them for treating the suspendedsolids.

This ice machine has an adjustment for the amountof water rinsed or purged. Water use adjustmentsare customer convenience adjustments; they arenot factory defects and are not covered bywarranty.

Eclipse� 1300,1600

September 2003Page 7

Page 8: eclipselargeman - static-pt.com

Create the SystemPlan the installation. The system consists of fourparts: the ice making section, the compressorpackage, the interconnecting tubing and theremote condenser. Of these, the biggest variable isthe interconnecting tubing.

Tubing: The tubing consists of three pre-charged,insulated and sealed soft copper tubes. They eachcontain a small holding charge of R-404A. Onetube, the liquid line, is 3/8” OD. The vapor tube is½” OD and the suction tube is ¾” OD. A siteinspection will determine what length of tubing isrequired for the installation.

Excess tubing must be either shortened at the jobsite (recovering the holding charge, purging withnitrogen when brazing and evacuating to 50microns) or coiled up inside the building.

Installations with greater than 20 feet of vertical liftbetween ice machine and the compressor requirea suction line trap. The suction line requires carefulhandling and large radius bends to prevent kinking.

Roof mounting: To make installation easier thecompressor and condenser are designed to beassembled together on the roof. Someinstallations will require the use of a hoist to lift thecomponents to the roof.

Pad mounting: The compressor and condensermay be located below the ice making section, up toa limit of 15 feet.

Distance from unit: Limited to the length of theavailable pre-charged tubing.

Elevation: CP unit limited to 35 feet above the icemaking section.

Compressor package: Electrical power must besupplied to the compressor package. The remotecondenser fan motor takes its power from thecompressor package.

Ice making section location and attachment:The 115/60 Hz ice making section is cordconnected and requires an outlet within 6 feet ofthe installation.

Interconnecting wires: An interconnecting wireharness is included with the CP unit. One endplugs into the ice making section and the other intothe compressor package. The system will NOToperate without this harness.

Exposed tubing: Minimize the amount of tubingexposed outdoors.

Confirm Component Availability:

�CME1386 or CME1686

�CP1316

�ERC1086 unless connecting to an approvedcondenser coil.

Note: Only these condensers may be used. Theydo NOT contain a headmaster valve. That valve isin the Compressor Package. Do NOT use anyother Scotsman condenser. Do NOT use thesecondensers on any other Scotsman remoteproduct.

�Interconnecting tubing kit

Note: Check tubing integrity before assembly byattaching a refrigeration compound gauge onto oneof each tube’s schrader valves. If there is pressure,the tube is OK, if not it should be checked fordamage and leaks.

�Bin or dispenser adapter

Eclipse� 1300, 1600

September 2003Page 8

Page 9: eclipselargeman - static-pt.com

System ExamplesThe Eclipse system can be installed on a bin ordispenser. The CP unit can be installed on either asingle circuit condenser or onto a coil in a separaterack condenser.

Separate coils must be:

�Scotsman approved

�The correct size and capacity

�New or not have been part of a system thatused mineral oil.

Eclipse� 1300,1600

September 2003Page 9

System on Ice Storage Bin System on Ice Dispenser

Page 10: eclipselargeman - static-pt.com

System ExamplesA variation of the typical system set up is one thatuses a non-Scotsman condenser. In that case theCP unit is NOT bolted to the condenser and aRTE10 line set is used to connect the refrigerationsystem to the condenser’s coil.

Eclipse� 1300, 1600

September 2003Page 10

IMS on Bin, CP Unit Connected to Approved CentralCondenser Coil

Page 11: eclipselargeman - static-pt.com

Place Remote SystemRoof preparation

Most installations of this system will place thecompressor package and condenser on the roof ofa building. The roof must be physically stoutenough to accept the load of the equipment andthe roofing material must be prepared to preventwater leaks.

Follow local codes for the placement andattachment of the equipment.

Location

The air cooled condensing unit assembly requiresunobstructed air flow to operate efficiently. A fourfoot space between each intake side and a wall orother cabinet is recommended. Provide at least 2feet of space above the air cooled condenser forproper air flow.

Do not place where the air cooled condenser willpick up hot discharged air from an air conditioneror other refrigeration system condensing unit.

Space must also be reserved for service on thecompressor package.

Roof Piercing:

The roof (or wall) must have a passage largeenough for the three pre-charged, pre-bent tubesand the control wire to pass through. The minimumrecommended size is 4” ID. In most areas thepower supply may also pass through the samepassage. If there isn’t a passage one must becreated. In most cases this must be done by alicensed and bonded roofer in order to maintain theroof’s integrity.

Suggestions:

Hoist the compressor package and condenser tothe roof in separate loads.

Note: In most cases a mechanical lift, boom truckor crane will be required to hoist the condensingunit components.

Assemble the compressor package to thecondenser and mount both to either roof rails orpressure treated 4 x 4s.

Orient the assembled unit so that the unit’s mountsare parallel to the pitch of the roof to allow water todrain freely.

Do NOT place the unit directly onto roof rock.

Eclipse� 1300,1600

September 2003Page 11

Page 12: eclipselargeman - static-pt.com

System LocationLimitations:

Distance: Limited to the maximum length of asingle pre-charged tubing kit, 75 feet.

Condensing Unit Elevation over Ice MakingSection: 35 feet.

Note: Elevations greaterthan 20 feet requireinstallation of a suction linetrap at the 20 foot mark.

Ice Making SectionElevation over CondensingUnit: 15 feet.

Line Routing:

�Allowed: One rise after a drop.

�Allowed: One drop after a rise.

�Not Allowed: More than one rise after a drop

�Not Allowed: More than one drop after a rise.

Eclipse� 1300, 1600

September 2003Page 12

22

.87

"1

7.1

5"

40.35"

Condensing Unit Distance Schematic

Max Rise:35 Feet

Max Drop:15 Feet

Max Length -Limit of Line Set

CondensingUnit LocatedBelow IceMachine

CondensingUnit LocatedAbove IceMachine

S-Trap

Page 13: eclipselargeman - static-pt.com

Route TubingScotsman’s pre-charged tubing kits are pre-bent tofit the connection path at the ice making section.

�If the tubing is to be routed out the back, usethe double-bend ends.

�If the tubing is to be routed out the back andthen up, use the ends with the single 90degree bends.

Note: Units mounted flush against the wall requirerefrigerant connections out the top, water supply infrom the top, power supply routed through the topand drain routed to the left side.

Select the correct end to send to the roof.

The method or technique used to route the tube isleft to the installer. However, in many cases it iseasier to position the tubing inside the building first,then feed the outside portion through the tubingpassage (pitch pot). Installation of tubing will beeasier if the suction line is run first, followed by theliquid and vapor lines. Use of two persons issuggested to prevent kinking of the tubing, longruns may require three people.

�Allow enough tubing to make large radius bendsfrom the roof passage to the compressor unit.Do NOT leave excess tubing on the roof.

�If a trap must be installed, the suction linetubing must be cut apart to install it.

�Identify the ice machine end of the tubing. Eachtube has one end formed to route through thehole in the unit’s top.

�Tape the ends of the vapor and liquid line tubestogether along with the interconnecting wire.Extend the end of the interconnecting wireabout 2 feet beyond the end of the prechargedtubes and then tape it back onto the tubes.

�Route the three tubes and the wire from theroof, or other entrance, to the ice makingsection’s planned position. Avoid uncoiling andrecoiling the tubing, as that can lead to kinks.

�Support long runs of tubing with hangers.

�Repair any tears in the tubing insulation,especially those on the suction line that areinside the building.

Shortening Tubing

The precharged tubing kits are available in avariety of lengths, they should only be shortened ifabsolutely necessary.

To Shorten Tubes:

1. Recover the 3 ounce R-404A holding chargefrom each tube.

2. Cut out the required length of tubing, do not cutthe tubing right at the quick connects.

3. Attach nitrogen bottle to one quick connect anda hose with a depressor to the other end, purgenitrogen through each tube while brazing.

4. Remove nitrogen, evacuate to 200 microns.

Note: If tubes are connected to the IMS, evacuatethe vapor & suction lines to get the entire system.

Eclipse� 1300,1600

September 2003Page 13

Suction

Vapor

Liquid

Suction

Vapor

Liquid

Page 14: eclipselargeman - static-pt.com

Ice Making SectionThe CME1386 and CME1686 are similar in layout.They differ in evaporator count, controller, floatstem and vapor inlet valve.

Major Components:

TXV - one feeding a refrigerant distributor

Water Pump - same for both models

Water Level Sensor - signals reservoir water levelto the controller

Controller - operates both the ice machine sectionand the compressor unit.

Drain Valve - opens to allow pump to drain thereservoir

Water Inlet Valve - 2.77 GPM solenoid valve thatopens to fill the reservoir

Low Side Access Valve - allows connection fordiagnosis of ice machine section refrigerationoperation. Not for recovery.

Liquid, Vapor and SuctionConnections - where thepre-charged tubing kitsconnect to.

Eclipse� 1300, 1600

September 2003Page 14

WaterPump Water

LevelSensor

Drain Valve

Water InletSolenoid

Valve

FreezingCompartment

Low SideAccess Valve

VaporConnection

LiquidConnection

SuctionConnection

TXV

Controller

Front IceSensor

BinThermostat

Vapor InletValve

Page 15: eclipselargeman - static-pt.com

Compressor PackageBoth compressor packages are similar in layout,they only differ in compressor and charge.

Major Components:

CPR Valve - limits refrigeration pressuresinside the dome of the compressor.

Condenser By Pass Valve - opens duringharvest to allow discharge gas to flow to thevapor line.

Headmaster - maintains a minimumdischarge pressure during freeze

Liquid Inlet Valve - Normally Open, closesduring harvest.

Receiver - stores liquid refrigerant forfreeze and provides vapor for harvest

Suction Access Valve - provides a place toattach a refrigeration manifold for diagnosticsand recovery.

Eclipse� 1300,1600

September 2003Page 15

CP Unit Refrigeration Connection ID

PowerRouting Hole

Vapor LineConnection

24 volt comm lineRouting Hole

Liquid LineConnection

Suction LineConnection

Liquid fromCond. Discharge to

Cond.

CondenserWire RoutingHole

CP Component Location

CPR Valve

LiquidAccessValve

HeadmasterCondenser By

Pass Valve

HiPressureCut Out

Liquid InletValve

Receiver

SuctionAccess

Valve

Page 16: eclipselargeman - static-pt.com

Condensing Section Assembly(CP1316 to ERC1086):

1. Remove cartons from compressor package andcondenser.

2. Remove top from both units.

3. Remove front panel from CP unit.

4. Locate legs, secured to ERC unit.

5. Locate fasteners, inside junction box of ERCunit.

6. Assemble rear legs to ERC using fasteners fromprior step.

7. Locate wire package in CP unit. Remove shortwires and two wire nuts.

8. Use wire & wire nuts from step 7 to connect tothe wires inside the junction box of the condenser.Return junction box cover to its original position.

9. Place front of ERC on back flange of CP unit.

10. Secure CP unit to ERC.

11. Attach leg brace between ERC unit and CPunit.

12. Route wires from condenser through hole inback of CP unit to the CP unit control box.

13 Pull ERC female refrigerant connectionsforward to engage male connections on CP unit.

14. Rotate swivel nuts to tighten refrigerantconnections. Use a back up wrench to hold femaleconnection to prevent tearing of the diaphragms.

15. Connect wire to T1 and T2 of the contactor.Use the two wire nuts to connect the other end tothe two black wires in the condenser junction box.

16. Return tops to their original positions.

Eclipse� 1300, 1600

September 2003Page 16

CP Unit Contactor, Three Phase Shown

ConnectFan Motor

Leads

ConnectPower

Here

Rotate SwivelNuts to Connect

CondenserSystem to

CompressorUnit

LocateFastenerPackage

Page 17: eclipselargeman - static-pt.com

Condensing Section AssemblyAlternate Assembly:

The CP unit may be connected to an approvedcondenser coil in a central condenser rack. Inthose cases, the CP unit must be connected to thecondenser coil using special kit RTE10.

Position the CP unit in its final spot. It must bewithin 6 feet of the condenser coil connections.

Route tubing from kit RTE10 from the CP unit tothe condenser coil.

Connect tubing per the Coupling Instructions in thismanual.

No wire connection is required between the CPunit at the condenser.

Note: Approved condensers must maintain powerto their fan motor at all times.

Note: For local codes requiring a pressure reliefvalve: Recover charge and connect valve toreceiver liquid outlet tubing.

All Assemblies:

Route interconnecting control wire through properhole in side of CP unit and plug into the connectionon the bottom of the control box.

Route power conduit (liquid tight) and wires to thehole in the side of the CP unit. Secure with theproper type of connector.

Note: The power supply wires must be the correctsize and type per the National Electric Code.Locate the nameplate on the CP unit for theVoltage, Phase, Minimum Circuit Ampacity andMaximum Fuse Size. Either fuses or HACR typecircuit breakers may be used.

Follow all Local, State and National Codes.

Connect power wires to the contactor, L1 and L2 ifsingle phase, L1, L2 and L3 if three phase. Note: Ifthere is a “wild leg” in the three phase powersupply place it on L3.

Connect electrical power to the CP unit.

Return front of CP unit to its original position.

Eclipse� 1300,1600

September 2003Page 17

Control Wire Connection in CP Unit

InterconnectingControl Wire Plug

CP Unit Contactor, Three Phase Shown

ConnectPower

Here

ConnectFan Motor

Leads

ApprovedCentral

CondenserUnit

ScotsmanCondensingUnit

Page 18: eclipselargeman - static-pt.com

Ice making section:Remove from carton.

Remove all panels.

Utility Connection Route:

Electrical: The unit is supplied with a power cord.The power cord can be routed out the back, leftside or top. There is also an interconnecting controlwire that must be routed between the ice makinghead and the CP unit. That wire can be routed outthe back or top.

Water Supply: The water supply can be routedfrom the top, back or left side.

Drain: The drain can be routed out the back or theleft side.

Refrigeration Tubing: The tubing can be routed outthe top or the back.

Adapters:

In many cases an adapter kit will be required whenplacing the head unit on a bin or dispenser. Seesales information for the correct kit. Place adapterkit onto bin or dispenser top. If adapter does NOThave gasket tape install tape such as Scotsmanpart number 19-0503-04.

Attachment:

If the unit is a direct fit, place it on the bin. If theunit is in a position that it need not be moved tocomplete the installation, secure it to the bin withthe hardware provided with the head unit.

On some bins or dispensers it may be necessaryto drill small holes and use field supplied sheetmetal screws to secure the ice making head to thatbin, dispenser or adapter.

Control Wire

Plug the interconnecting control wire into theharness at the back of the head unit’s electricalbox.

Eclipse� 1300, 1600

April 2003Page 18

Ice Making Section Control Wire Connection

IMS Shown on Ice Dispenser

ControlWireConnector

Electrical Box inIce Making Head

Page 19: eclipselargeman - static-pt.com

Bin Thermostat - Routing

Install the bin thermostat after the ice makinghead has been placed on the bin or dispenser.

Note: Dispensers may require special attention tokeep ice or agitator/sweep arm from moving thethermostat from its installed position. Place thehead on the dispenser and install the thermostatbefore connecting refrigerant tubing.

Before starting, remove the left side and frontpanels and any baffle in the bin.

1. Locate bin thermostat bulb.

2. Route bulb thru routing tube (located behind thereservoir).

3. Locate bin thermostat bracket.

4. Carefully position the thermostat bulb on thebracket (see the diagram on the next page).

5. Fasten the bracket to the bottom of the icemachine with the two 3-pronged knob head screwssupplied with the unit.

6. Pull back into the ice machine any excesscapillary tubing.

7. Return the baffle to the bin and continue with theinstallation.

Note: If the machine is located at an altitude higherthan 2,000 ft., adjust the thermostat by removingthe plastic cover and rotating the adjustment screwper the table.

Eclipse� 1300,1600

September 2003Page 19

Bin Thermostat Altitude Correction Table

CW Turns of Range Screw (under plastic cover)

Feet Turns Feet Turns

2000 55o

8000 340o

4000 160o

9000 385o

6000 250o

10000 405o

BinThermostatBulb

ThermostatBulb Routing

Tube

Page 20: eclipselargeman - static-pt.com

Bin Thermostat - Bracket & Bulb

Eclipse� 1300, 1600

September 2003Page 20

Attach Thermostat Bulb to Bracket

Mount Bracket to Bottom of ice Head

Bracket

ThermostatCapillary Tube

Insert Tip intoHole

Snap TubeThrough Slot

Bulb

Page 21: eclipselargeman - static-pt.com

Water and DrainThe ice making section requires an adequatepotable water supply and a gravity drain.

Determine how the water supply and drain will beconnected to the ice making section.

�If access is available behind the unit, route thedrain and water supply in from the back.

�If the unit is to be flush mounted to the back ofthe bin or dispenser and tight against the wall,the water supply must enter the cabinet throughthe area in the lower back of the left side panelor through the top panel with the refrigerantlines.

�If the unit is to be flush mounted to the back ofthe bin or dispenser and tight against the wall,the drain must be routed through the area in thelower back of the left side panel.

In some tight situations it will be necessary toassemble the ice making section to the dispenseror bin and install the water and drain connectionsbefore placing the system in its installed position. Aloop of water supply tubing will allow movement ofthe system.

In other tight situations the unit should have itswater and drain tubing connected and stubbed outbefore placing on the dispenser or bin.

The drain fitting is adaptable to drain connectionsto the left or back.

Eclipse� 1300,1600

September 2003Page 21

DrainFitting

Water Inlet

Remove this section ofthe top panel if routingrefrigeration tubingthrough the top

Remove this plate ifrouting drain to the left

Page 22: eclipselargeman - static-pt.com

Water and DrainWater Supply: Connect a supply of cold, potablewater to the 3/8” fitting on the right side of thecabinet. A male flare fitting is on the unit.

Note: This is an NSF listed ice machine andcontains provisions for back-flow prevention in itsdesign. No external back flow preventer isrequired.

Drain: Connect rigid drain tubing to the reservoirdrain fitting. Route the drain either out the back orto the left side. Add a 18” vertical vent to the draintube.

Route the drain tubing to the building drain. Do not“Tee” into any other drain, including the bin ordispenser drain.

Follow all local codes.

Eclipse� 1300, 1600

September 2003Page 22

Back View, Drain Tubing Installed for Back Drain

PotableWater Inlet

Removable Plate

Purge Valve

ReservoirDrain

Page 23: eclipselargeman - static-pt.com

Ice Making Section Set UpRotate the ice making section as needed to accessthe left side, where the refrigeration connectionswill be made. Connect the suction line to the topfitting. Connect the vapor line to the middle fitting.Connect the liquid line to the bottom fitting.

See Coupling Connections on the next page fordetailed instructions.

After couplings are connected, add cork-tape typeinsulation to exposed fittings to reducecondensation potential.

Eclipse� 1300,1600

September 2003Page 23

Refrigerant Lines, Shown Routed Out The Top

Addinsulation

SuctionVapor

Liquid

Refrigerant Lines, Shown Routed Out the Back

Page 24: eclipselargeman - static-pt.com

Coupling Connections:The couplings on the ends of the pre-charged linesets are self-sealing when installed properly.

Follow these instructions carefully. These stepsmust be performed by an EPA Certified Type II orhigher technician.

Initial Connections

1. Remove the protector caps and plugs. Wipe theseats and threaded surfaces with a clean cloth toremove any possible foreign matter.

2. Thoroughly lubricate the threads, o-rings,diaphragms and all internal coupling surfaces withpolyolester refrigerant oil.

3. Position the fittings on the correct connectionson the condenser and ice machine.

Final Connections:

4a. Begin to tighten the couplings together byhand. Continue to turn the swivel nuts by hand untilit is certain that the threads are properly engaged.

4b. Using two wrenches, one to rotate the swivelnut and one to hold the tubing in place, tighteneach coupling.

It is CRITICAL that ONLY the NUT on thepre-charged tube be turned, or the diaphragms willbe torn by the piercing knives and become loose inthe refrigeration system causing severe operationalproblems.

Note: As the coupling is tightened, the diaphragmsin the quick connect couplings will begin to bepierced. As that happens, there will be increasedresistance to tightening the swivel nut.

4c. Continue tightening the swivel nut until itbottoms out or a very definite increase inresistance is felt (no threads should be showing).Do NOT overtighten.

5. Use a marker or pen to mark a line on thecoupling nut and unit panel. Then tighten thecoupling nut an additional one-quarter turn. Theline will show the amount that the nut turns.

6. After all connections have been made check thecouplings for leaks.

7. Add cork tape to the swivel nut of the suctionline to insulate it. Be sure all exposed tubing ofthe suction line is insulated.

Note: The system charge is contained in thereceiver tank of the ice machine. Only “holding"charges are present in the “pre-charged" tubing orthe condenser.

Eclipse� 1300, 1600

September 2003Page 24

Clean and Lubricate Couplings

Tighten Swivel Nut

Rotate Swivel Nut ¼ Turn More

Page 25: eclipselargeman - static-pt.com

Condensing Unit ConnectionsConnect the suction line, the vapor line and theliquid line to the matching fittings on the CP unit.

See Coupling Connections on the prior page fordetailed instructions.

Eclipse� 1300,1600

September 2003Page 25

Assembled Condensing Unit

Control Wire

PowerSupply

Inlet

FieldSuppliedServiceDisconnect

Liquid Line

Suction Line

Vapor Line

Page 26: eclipselargeman - static-pt.com

Final PlacementAfter the utilities and refrigeration connectionshave been made, secure the unit to the dispenseror bin top.

Secure ice making section to dispenser or binadapter.

Use strap/clips to secure unit. On some bins ordispensers it may be necessary to drill small holesand use field supplied sheet metal screws tosecure the ice making head to that bin, dispenseror adapter.

If the ice maker & bin or dispenser is not yet in itsfinal position gently move it there.

Note: The refrigerant lines above the machinemust be able to move freely while the machine isbeing moved into position.

Final Check List Before Initial Start Up

1. Confirm that the ice making section is installedindoors in a controlled environment.

2. Confirm that all packing materials have beenremoved from all products.

3. Confirm that the ice making section is level.

4. Confirm that all the refrigerant connectionshave been made and checked for leaks.

5. Confirm that the proper power supply has beenturned on to the condensing unit.

6. Confirm that cold, potable water has beensupplied to the ice making section and checkedfor leaks.

7. Confirm that the water supply is adequate.

8. Confirm that there is adequate water pressureand that any water filters have been checked toconfirm that the cartridges do not needchanging.

9. Confirm that the proper size drain tubing hasbeen installed and properly routed.

10. Confirm that the ice making section has beenconnected to the proper power supply.

11. Confirm that the interconnecting wire has beenrouted and connected between the ice makingsection and the compressor package.

12. Confirm that the bin thermostat has beenproperly installed.

Eclipse� 1300, 1600

September 2003Page 26

Page 27: eclipselargeman - static-pt.com

Controller OperationThe controller has seven indicator lights and fourpush buttons.

Indicator Lights

Bin Full: On when the bin is full, blinks on and offas ice falls during a harvest cycle.

Freeze: On when the unit is in the Freeze cycle.Blinks when a freeze cycle is pending.

Harvest: On when the unit is in the Harvest cycle.

Clean: Blinks when the unit is in the first part of aClean cycle, on steady when switched to thesecond part.

Off: On when the unit has been switched off, blinkswhen the unit is preparing to shut off.

Water Diagnostic: On when the controller hasidentified a problem with the water system. Flashesa code to specify what area may be the problem.

Refrigeration Diagnostic: On when the controllerhas identified a problem with the refrigerationsystem. Flashes a code to specify what area maybe the problem.

Push Buttons

Freeze: Push and Release to start the unit

Harvest: Push and Release to start a manualharvest of ice.

Clean: Push and Release to start the first part ofthe cleaning process. Push and release again tostart the second part of the cleaning process.

Off: Push and Release to shut the machine off atthe end of the next harvest cycle. Push and Holdfor three seconds to stop the machine. Push andHold again to go into the Purge Adjustment orError Recall mode.

Cycle Definitions:

Freeze: The refrigeration system is operating toremove heat from the evaporators. Thecompressor, fan motor, and water pump are on.

Harvest: The refrigeration system and watersystem are operating to harvest the ice and rinsethe reservoir. The compressor is on for the fullcycle, the pump is off and then on, the purge valveis open and then closed, the inlet water valve isclosed, opens and recluses. The vapor andcondenser by-pass valves are open during theentire harvest cycle.

Clean: The inlet water valve opens to fill thereservoir. The water pump starts. The Cleanindicator light is switched On. A manually initiatedrinse flushes the system.

Eclipse� 1300,1600

September 2003Page 27

1

2

3

4

5

6

7

8 9

BIN FULL

FREEZE

HARVEST

CLEAN

OFF

WATER

REFRIGERATION

PUSH BUTTONCONTROL SWITCHES

INDICATOR LIGHTS:

DIAGNOSTIC LIGHTS:

Controller Lights and Push Buttons

Page 28: eclipselargeman - static-pt.com

Initial Start Up - 1300 and 1600Pre Start

A soak-out period of four hours is optional for thissystem. If desired, powering the compressor unitfor four hours prior to start up allows the crankcaseheater to warm up the oil in the compressor.

Start Up

1. Connect power to the condensing unit and moveits toggle switch to Run or On.

2. Open the water supply valve.

3. Connect or reconnect power to the ice makingsection.

4. Observe the lights on the controller:

�All flash on as the power supply is reconnected.

�The two red lights blink for 20 seconds whilesome green lights are on. See page 43.

Note: If the light pattern does NOT match – do notstart the machine. Install a replacement controllerset to the correct program.

�The red lights and harvest lights go out.

�The Off light turns on.

�The Bin Full light will be on for a few seconds.

At this point the machine is ready for start up.

5. Push and Release the Freeze button to start themachine.

�The Freeze light will begin to blink.

�The Purge valve will open for a few secondsand then close.

�The Inlet water valve will open and fill thereservoir with water.

�The Water pump will begin to circulate waterover the evaporators.

When the reservoir is full, the Freeze light will stopblinking and the controller will close a circuit to thecompressor contactor to start the first freeze cycle.

Note: Because the condensing unit is external tothe ice making section, no visible signs ofoperation will be noticeable until the water beginsto cool and frost forms on the evaporator tubing.

6. Go to the condensing unit and confirm that thecompressor and fan motor are operating. Warm airwill be discharged from the condenser.

After a few minutes ice will begin to form on theevaporators. When enough ice has formed tonearly empty the water reservoir, the controller willrefill the reservoir. The next time the water leveldrops that far, the ice is ready for release and theController will initiate a Harvest cycle.

�The Freeze light goes out and the Harvest lightswitches on.

�The vapor inlet valve in the ice making sectionopens.

�In the CP unit, the condenser by-pass valveopens and the liquid inlet valve closes

�The water pump stops.

�The purge valve opens.

Refrigerant vapor flows into the evaporators whereit condenses, discharging its latent heat.

The evaporators warm up and melt the bondbetween the ice cube surface and the evaporatorcells.

After about 20 seconds the water pump re-starts topurge water out of the reservoir.

After a few more seconds the purge valve closesand the inlet water valve opens for a few secondsto add some water to the reservoir. The waterpump then circulates this water over theevaporators, and ice begins to fall.

As the ice falls, it passes through two infrared lightbeams. These beams, when interrupted, signal tothe Controller that ice is harvesting. Theinterruptions are shown by the blinking of the BinFull light.

The first Harvest cycle continues for about 5minutes. The controller will use the ice release timemeasured during this time to compute the nextharvest cycle.

At the end of the Harvest cycle the ice machine willswitch back into a Freeze cycle.

The inlet water valve will open to re-fill thereservoir with water, and the cycle repeats.

Note: Machines are shipped from the factory withthe purge level set to accommodate average waterconditions. To achieve optimal machineperformance, set the purge level to the minimumsetting. See the next page.

7. Attach the front panel to the ice making section.

Eclipse� 1300, 1600

September 2003Page 28

Page 29: eclipselargeman - static-pt.com

Purge Adjustment

Note: While the amount of water purge isadjustable, only those installations with a watersupply known to be excellent (very low TDS)should adjust to the minimum setting. See belowfor purge adjustment instructions.

How to Adjust the Amount of Water Purge

Adjustment is done by use of the control buttonson the AutoIQ Controller. Examine the next sectionto become familiar with the AutoIQ Controllerbefore beginning.

1. If the machine is on, push and hold the OFFbutton for more than 3 seconds, then release it.This switches the machine Off.

2. Push and hold the OFF button for more than 3seconds (just until all lights flash on) then releaseit. Do not hold it in it too long.

3. Examine the green lights. They should have allflashed once, then certain ones will have turned onto indicate which purge level the machine is set at.

There are 5 levels of purge available:

�1. Maximum Purge is when All 5 lights are ON.Use for extreme water conditions.

�2. Heavy Purge is when these 4 lights are ON:Freeze, Harvest, Clean, Off. Use for severewater conditions.

�3. Standard Purge (factory setting) is whenthese 3 lights are ON: Harvest, Clean, Off. Usefor moderate to severe water conditions.

�4. Moderate Purge is when these 2 lights areON: Clean, Off. This is for typical waterconditions.

�5. Minimum Purge is when this light is ON: Off.For excellent water conditions.

Adjust by pushing and releasing the Freeze button.Pushing and releasing the Freeze button increasesthe purge one level up to the maximum, then itgoes to the minimum.

4. The machine will automatically restart after 60seconds of no switch inputs, or restart the machineby pushing in and holding the Off button for morethan 3 seconds, then releasing it. The unit will thenbe Off. From there the machine may be placed in afreeze cycle by pushing and releasing the Freezebutton.

Adjustments

Cube Size: Cube size is fixed and cannot beadjusted.

Thermostatic Expansion Valve:

The TXV is not adjustable, do not attempt to adjustit.

If there was a problem during Initial Start Up:

If an error light came on, check the following.

1. Water error.

A water error could have been determined by theAutoIQ Controller if the inlet water valve does notfill the reservoir, or if the water pump does not startand lower the water level.

2. Refrigeration error.

A refrigeration error could have been determinedby the AutoIQ Controller if the water temperaturedid not drop during the freeze cycle. The controllerwill next check the compressor dischargetemperature, If the discharge temperature is toolow, the refrigerant error light will be switched on,and the machine will Shut Down.

Note: Reset and restart the machine bypushing and releasing the Off push buttonswitch, and then pushing and releasing thefreeze push button switch.

Eclipse� 1300,1600

September 2003Page 29

Page 30: eclipselargeman - static-pt.com

System Operation:This section is intended for the technician.Understanding it is not necessary for the normaloperation and maintenance of this ice makingsystem.

Major Components:

Ice making section sub-system:

�Controller,

�Ice Sensors,

�Water Level Sensor,

�Transformer,

�Evaporators,

�Expansion Valve,

�Vapor Inlet Valve,

�Water Pump,

�Inlet Water Valve

�Purge Valve.

Compressor Package sub-system:

�Compressor,

�Contactor,

�Condenser Bypass Valve,

�Liquid Inlet Valve,

�Receiver,

�Accumulator,

�CPR Valve,

�Headmaster.

Condenser sub-system:

�Coils

�Fan Motor

The controller receives input from the water levelsensor, ice sensor and temperature sensor. It thenactuates various loads in the ice making sectionand in the condensing unit to control ice making. Italso responds to push button input and displayscycle and diagnostic indicators.

Freeze: At the ice making sub system, thecontroller fills the water reservoir and starts thepump and compressor to make ice. The vapor inletvalve is closed. Water circulates over theevaporators until it begins to freeze to theevaporators. As ice builds up the water level in thereservoir falls until it reaches a point where thewater level sensor indicates to the controller thatthe water level is low. At that point, about half-waythrough the freeze cycle, the controller opens thewater valve to refill the reservoir. The second timethe water level drops in the freeze cycle indicatesto the controller that the freeze cycle is complete.

In the air cooled condensing unit sub-system(compressor package and condenser) thecompressor is on, the condenser by-pass valve isclosed, the fan motor is rotating the fan blade.

Harvest: At the ice making sub system, thecontroller shuts off the pump, opens the vapor inletvalve, opens the purge valve. The controller alsocontrols items in the condensing unit, where thecondenser by pass valve is opened. After a settime the water pump restarts and shortly after thatthe purge valve closes. The inlet water valve opensto add water to the reservoir.

Ice releases and falls into the bin or dispenser.

Eclipse� 1300, 1600

September 2003Page 30

Typical Ice Level When Full - Shown WithoutBaffle - A Baffle is Recommended

BinThermostat

Bulb Location

Page 31: eclipselargeman - static-pt.com

Refrigeration Details:The compressor provides the force that circulatesrefrigerant in the refrigeration system. Duringfreeze, when the vapor inlet and condenser bypass valves are closed, discharge gas flows fromthe compressor into the condenser, where its heatis discharged into the air stream. Liquid refrigerantflows out of the condenser and through thenormally open liquid line outlet valve on its way tothe receiver inlet. Under low ambient/low pressureconditions, the headmaster valve closes the liquidoutlet of the condenser and opens a bypass routeto direct refrigerant gas to the receiver inlet untildischarge pressure builds back up to theheadmaster’s set point.

From the receiver liquid outlet, liquidrefrigerant flows into the liquid lineand into the ice making section. Atthe ice making section, therefrigerant flows into the expansionvalve where a pressure changetakes place. The liquid refrigerantmoves from the expansion valveinto a low-pressure area (theevaporators) where it can rapidlyevaporate and absorb heat. Heat isabsorbed from the copperevaporator tubing, attached copper,tin, plastic and the water flowingover the evaporators. Thelow-pressure refrigerant gas thenflows into the suction line, whichcarries it back to the condensingunit, where it enters theaccumulator. In the accumulatormost of any liquid carried with thesuction gas is separated and onlyvapor flows out of the accumulatorthrough the CPR valve and to thecompressor where the cyclecontinues.

During harvest discharge gas flowsthrough the open condenser bypass valve into the vapor line.Power is also applied to the coil ofthe liquid inlet valve, closing it. Atthe same time, in the ice makingsection, the vapor inlet valve opens.Discharge gas, combined with somevapor from the receiver’s outlet,then flows through the vapor line tothe evaporator inlets. The gas-vapor

combination, when entering the relatively coldevaporators, condenses, transferring latent heat tothe evaporators, which warms them. Ice releasesand falls into the bin. The low-pressure refrigerantthen flows out of the evaporators and into thesuction line. The suction line brings the refrigerant,now consisting of a vapor-liquid combination, to theaccumulator. From the accumulator thevapor-liquid combination (now more vapor thanliquid) goes to the Crankcase Pressure Regulatorvalve which limits the amount of dome pressure inthe compressor, where the cycle continues.

Eclipse� 1300,1600

September 2003Page 31

DischargeLine

Headmaster

Liquid InletValve (N.O.)

By-Pass Valve

TXVVapor Inlet Valve

Evaporators

Receiver

LiquidLine

CPRValve

DistributionTubes

Suction LineManifold

InletManifold

Accumulator

Air CooledCondenserCoil

D L

LVS

Page 32: eclipselargeman - static-pt.com

Technicians Only: Freeze Cycle Sequence of OperationThis sequence begins with a restart after the unithas shut off with the bin full. Ice has beenconsumed, causing the ice sensors to becomeun-blocked.

1. The controller switches off the bin full light (fourminutes has to have passed since the machineshut off on bin full for the machine to restart) andswitches on the Freeze light.

2. The purge valve is opened and the pumpstarted.

3. After the purge valve closes the inlet water valveopens and fills the reservoir.

Note: If the water reservoir does not fill within thetime period expected the controller will shut off andblink the water diagnostic light. It will re-try to fillthe reservoir in 20 minutes. If successful the freezecycle will continue.

4. The compressor andfan motor start and thefreezing process begins.

5. The controllermeasures the reservoirwater temperature andcompares it to thetemperature it expects tofind at that point in thecycle. If normal, nothinghappens.

If high, the controllerchecks the dischargetemperature. If that isnormal, nothing happens.If that is low, the controllerstarts a diagnosticprocess that could lead tothe unit shutting off, asthe refrigeration systemmay not be operable.

6. Assuming that the system is working normally,the controller will shut the water pump off for a fewseconds when the reservoir’s water temperaturereaches a pre-set point.

7. As the machine makes ice the water level in thereservoir falls. When it reaches the point where thefloat stem blocks the upper infrared beam in thewater level sensor the controller opens the inletwater valve to refill the reservoir. The water valvestays on until the float stem rises to block the lowerbeam in the water level sensor.

8. The freezing process continues until the floatstem blocks the upper beam for the second time.That signals to the controller that the freezingprocess is complete.

Eclipse� 1300, 1600

September 2003Page 32

Water Schematic

Water Pump

Purge Valve

Inlet WaterValve

Page 33: eclipselargeman - static-pt.com

Technicians Only: Harvest Cycle Sequence of OperationAt the beginning of harvest, the controller:

�Shuts off the Freeze light

�Turns on the Harvest light

�Opens the vapor inlet valve

�Opens the condenser bypass valve

�Closes the normally open liquid inlet valve

�Shuts off the water pump

�Opens the purge valve

�Begins to time the harvest cycle

When the ice falls off the evaporators, it passesthrough the two infrared light beams emitted by theice sensors in the ice chute. The falling ice breaksthe beams, signaling to the controller that ice isbeing released.

During harvest the controller:

�Blinks the Bin Full light at every light beaminterruption to indicate that ice is being sensed

�Changes the time measured from the beginningof harvest to the time the last cube was sensed.

First Harvest Cycle

The first harvest cycle after a restart continues fora default period of about 5 minutes. The nextcycle’s harvest time will be determined from theactual time used to release ice in this cycle, andwill likely be much shorter.

Slow Ice Release

If ice releases slowly the controller will extend theharvest cycle until it ice quits falling within thenormal harvest time or until it reaches the pre-setmaximum time. The controller will then return theunit to the freeze cycle.

No Ice Released

If no ice is sensed harvest continues until itreaches its pre-set maximum, when the controllerswitches the unit back into freeze.

Shut Down - Maximum Harvest Time

If a maximum harvest time is reached again duringthe next harvest cycle, the controller will shut thesystem down and blink the refrigeration diagnosticlight. It will automatically attempt a restart in 50minutes. If the maximum harvest time is reachedagain in the next two consecutive cycles, thecontroller will repeat the shut down and restartprocess. If the system still requires a maximumlength harvest cycle the controller will shut the unitdown and must be manually reset.

Purge Valve

The purge valve is open for a fixed time period. Atthe beginning of that time the pump is off, but afterthe time determined by the Purge setting in thecontroller, the pump starts and forces water out ofthe reservoir. The pump stays on after the purgevalve closes. The inlet water valve opens for a fewseconds to add water (but not fill) the reservoir.

End of Cycle

At the end of the harvest cycle the controllerswitches the Harvest light off and the Freeze lighton. If the ice sensors had been blockedcontinuously for more than 5 seconds the controllersenses this as Bin Full and would then shut themachine off and turn on the Bin Full light.

At the beginning of the Freeze cycle the inlet watervalve is turned on to fill the reservoir and the cyclerepeats.

Eclipse� 1300,1600

September 2003Page 33

Page 34: eclipselargeman - static-pt.com

Power and Water InterruptionsShort (less than one second) power interruptionscause no change in operation.

Longer interruptions initiate a restart process:

�Freeze light blinks on controller

�Compressor is off

�Vapor inlet valve opens

�Liquid inlet valve closes

�Purge valve opens

�Pump starts, empties the reservoir

�Purge valve closes

�Inlet water valve fills reservoir

�The Compressor starts

�Vapor inlet valve closes

�Liquid inlet valve opens

�Freeze cycle proceeds for 30 seconds

�Harvest cycle initiated, continues for 4 minutes

�Normal freeze cycle starts

Water Interruptions

The water level sensor checks for water fillwhenever the water inlet valve is activated. If thewater level sensor does not record a full reservoirwithin the pre-set time, the controller

�shuts the unit off

�blinks the water diagnostic light two times andrepeats

After 20 minutes the inlet water valve is poweredagain and if the water level sensor is satisfied, theunit is restarted. If the controller still doesn’t sensea full reservoir it keeps the unit off for another 20minutes and then restarts the water fill process.

The process of retrying water fill will continue untila full reservoir is sensed. There is no limit to thenumber of refill attempts.

Eclipse� 1300, 1600

September 2003Page 34

Page 35: eclipselargeman - static-pt.com

Sanitation and CleaningIt is the User’s responsibility to keep the ice machine and ice storage bin in a sanitary condition.

Without human intervention, sanitation will not be maintained. Ice machines also require occasionalcleaning of their water systems with a specifically designed chemical. This chemical dissolves mineral buildup that forms during the ice making process.

Sanitize the ice storage bin as frequently as local health codes require, and every time the ice machine iscleaned and sanitized.

The ice machine’s water system should becleaned and sanitized a minimum of twice peryear.

In Place Cleaning of the Water System

1. Remove all ice from the bin.

2. Remove the front panel.

3. Push and release the Harvest button (thisreleases any ice that may be on the evaporatorsand warms them up).

4. Wait for the machine to finish the Harvest cycle(the machine will stop).

5. Remove the the insulated plastic evaporatorcover, the two inner splash panels (part number02-3680-01 and the one above it), both cubedeflectors, and the ice sensors. Place the splashpanels and the cube deflectors in a separatecontainer. Place the ice sensors in the reservoir,but be sure that the ends of the connecting wiresare not in the water.

6. Push and release the Clean button. The Cleanindicator light will be blinking, and the pump willrestart.

7. Pour 24 ounces of Scotsman Ice MachineCleaner into the reservoir water. Return theevaporator cover to its normal position.

8. Mix a solution of 8 ounces of Scotsman icemachine cleaner and 1 gallon of warm (95-115

oF.)

water. Use the solution to scrub the splash panelsand cube deflectors in the separate container.

9. After the ice machine cleaner has circulated for10 minutes, push and release the Clean button.This starts the rinsing process. The Clean indicatorlight will be ON. Note: The rinse process flushesany residual cleaner out of the ice machine’s watersystem.

10. Continue the rinsing process for 20 minutes,then push the off button to switch the machine off.

11. Go to the next step to sanitize the machine orgo to step 19 to finish the cleaning process.

12. Mix 2 gallons of Sanitizer solution. Follow localcodes for Sanitizer.

Note: A possible sanitizing solution may be madeby mixing 1 ounce of liquid household bleach with2 gallons of warm (95-115

oF.) potable water.

13. Push and release the Clean button again.

14. Pour 24 ounces of Sanitizer solution into thereservoir water.

15. After the solution has circulated for 10 minutespush and release the Clean button. This starts therinse process. Sanitize the ice storage bin whilewaiting.

16. Continue the rinsing process for 20 minutes,then push the off button to switch the machine off.

17. Remove the evaporator cover and spray orwash all interior surfaces of the freezingcompartment including the evaporator cover withsanitizer solution.

18. Thoroughly immerse the splash panels andcube deflectors in the sanitizing solution.

19. Return the ice sensors, splash panels andcube deflectors to their original positions.

20. Return the evaporator cover to its originalposition. Push and release the Freeze button.

21. Return the front panel to its normal positionand secure it to the machine with the originalscrews.

Eclipse� 1300,1600

September 2003Page 35

Scotsman Ice MachineCleaner contains acids.

Acids may cause burns. Ifconcentrated cleaner comesin contact with skin, flushwith water. If swallowed, doNOT induce vomiting. Givelarge amounts of water orMilk.

Call Physician immediately.Keep out of the reach ofchildren.

Page 36: eclipselargeman - static-pt.com

Other MaintenanceThe remote air cooled condenser coil must becleaned occasionally to keep the system operatingat high efficiency.

�Remove any large debris from the outside of thecoil.

�Vacuum accumulated dust.

�Wash out the coils with water.

Caution: Do NOT use excessive water pressure asthat will bend the fins.

�Straighten any damaged fins with a fin comb.

�If the coils have become coated with grease, acoil cleaner will have to be used to wash thecoils.

Disconnect power to the condensing unit andremove the condenser top.

�Inspect the fan blade to be sure it is not crackedand is clean.

Return the condenser top to its original positionand reconnect the power supply.

Eclipse� 1300, 1600

September 2003Page 36

Moving Parts Hazard

Rotating fan blade cancause cuts

Disconnect electricalpower before removingcondenser top or fanguard.

Page 37: eclipselargeman - static-pt.com

Water DistributorsIt may become necessary to remove the waterdistributors from the top of the evaporator andclean (de-mineralize) them outside of the icemachine.

1. Remove front panel.

2. Push and release the off button.

3. Remove the evaporator cover.

4. Remove the upper splash panel.

5. Remove the top panel.

6. Lift the center of the distributor assembly torelease them from the top of the evaporators.Repeat for each plate.

7. Examine the top of the evaporators. The waterdistribution channels must be free of mineral buildup. If build up is present, scrub the channels withScotsman Ice Machine Cleaner and a plasticbristle brush.

8. Examine the water distributors. Although theyare made of a material that is resistant to mineralbuild up, some may be present, especially in thedischarge holes. Soak or scrub the distributors in asolution of Scotsman Ice Machine Cleaner andwarm, potable water.

9. Return the water distributors to their normalposition.

10. Snap the two distributors onto the top of eachevaporator.

11. Repeat for all evaporators.

12. Reconnect the water hose.

13. Push and release the clean button to begin thecleaning process, after the reservoir refills pushand release the button again to start the rinseprocess. After 20 minutes push and release the Offbutton.

14. Push and release the Freeze button.

15. Return all covers and panels to their originalpositions.

Inlet Water Valve Screen

The inlet water valve has a screen on its inlet sideto keep debris from flowing into the valve. In somecases, this screen may become clogged orrestricted by debris build up. Check for the properwater flow.

Flow rate is 2.77 GPM

1. Remove front panel.

2. Obtain a measuring cup and a watch.

3. Push and release the Harvest button.

4. When the water valve opens, it will fill a 16ounce cup in about 3 seconds. Be prepared topush the Off button! If the water does not flow infast enough, the water inlet valve or other waterdevice is restricted.

To Check the Inlet Water Valve Screen

1. Disconnect the electrical power.

2. Shut off the water supply.

3. Remove the front panel.

4. Unplug the electrical connection from the inletwater valve.

5. Remove the screws holding the water valve tothe cabinet.

6. Remove the outlet tube from the inlet watervalve.

7. Rotate the inlet water valve from the inlet fittingand remove valve from machine.

8. Examine the inlet screen. If dirty, brush the dirtfrom the screen.

Note: Screen is not replaceable, and may only beremoved by taking off the covering bracket. Thebracket is part of the valve and must be water tight.Removal is not recommended.

9. Reverse to reassemble.

Eclipse� 1300,1600

September 2003Page 37

Page 38: eclipselargeman - static-pt.com

Ice SensorsThe ice sensors, located in holders in the base ofthe ice making section, must be clean and free ofmineral scale to provide the controller withaccurate information.

To clean them they must be removed from theirinstalled positions.

1. Remove front panel.

2. Push and release the Harvest button to releaseice. When ice quits falling, push and hold the Offbutton until the machine stops.

3. Remove evaporator cover.

4. Remove lower splash panel.

5. Locate sensors. There is one at the back andone at the front of the ice outlet port.

6. Pull the back sensor forward and out of itsmounting position.

7. Unplug the sensor from its harness.

8. Remove the bracket holding the front sensor,then pull the front sensor out of the bracket.

9. Each sensor contains a removable tray. Onetray contains the infrared emitters, the other theinfrared receiver. Each lens must be clean and freeof scale for proper operation. The trays may beremoved from their holders for better access.

10. Push the tray in with a finger or thumb until thetray flips out of its socket.

11. Wipe the lensclean with a soft clothdipped in an icemachine cleaner solution (3parts water to 1 part icemachine cleaner). Do NOTuse any abrasives on thelenses.

12. Return the tray to itsnormal position. Be sure itsnaps into place. The graywire must be secured underthe black plastic clip.

13. Return each ice sensorto its normal position. Besure no wires arepinched in themounting sockets.

14. Return the lowersplash panel to itsnormal position.

15. Return theevaporator cover to itsnormal position.

16. Push and release the Freeze button.

17. Return the front panel to its normal position.

Ice Sensor Diagnostics

Diagnostics assume that the control system isworking but may not be able to sense cubes. Itspurpose is to determine which component may beat fault - the controller or the ice sensors.

Unplug thermostat from terminal 7 of the controllerand check bin full light, if off place an objectbetween the ice sensors, after 5 seconds the BinFull light will be glowing steadily, if not checkoperation of sensors by unplugging #4. Bin Fulllight will go on after 5 seconds, If not, replacecontroller. If the light does go on, replace icesensor set.

Eclipse� 1300, 1600

September 2003Page 38

Page 39: eclipselargeman - static-pt.com

Water Level Sensor MaintenanceIn most cases the water level sensor will notrequire maintenance. However, if the area wherethe ice making section is located is dusty or thereis a high concentration of minerals in the water, theinfrared emitter and detector lenses inside thesensor may need to be wiped off.

1. Remove front panel.

2. Push and hold the Off button until the machinestops.

3. Unplug sensor wire harness from sensor.

4. Remove two screws holding dust cover tosensor.

5. Wipe the four lenses with a cotton swap soakedin potable water.

6. Return the dust cover to its original position,secure with the original screws.

7. Reconnect wire harness.

8. Push and release the Freeze button.

9. Return the front panel to its normal position.

Water Level Sensor Diagnosis

Tools Needed: Digital voltmeter that can read DC

Note: Ambient light can affect this test. Shade thesensor if needed.

1. Unplug water sensor harness from controller(connection #2).

2. Confirm that the power to the machine is ONand that there is at least one light on the board thatis glowing. If not, check the transformer.

3. Set the voltmeter to DC and use a scale lowenough to measure less than 40 Volts.

4. Measure the voltage between the top and thebottom pins on the controller at connection #2 (thebottom is ground or negative).

�Harness unplugged - .5 to 2 VDC

Eclipse� 1300,1600

September 2003Page 39

Water Level Sensor, Dust Cover Removed

CleanLenses

CleanLenses

If it is much less than that, there is somethingwrong with either the power supply to the controlleror the controller itself. If the voltage measurescorrectly proceed to the next step.

5. Reconnect the harness. Be SURE it is onproperly and has a good connection. To confirm,unplug the harness from the water sensor andredo step #4 at the end of the harness. Then plugthe harness back onto the sensor.

Harness Connected Voltage (DC)

6. At the controller, measure the voltage betweenthe top and bottom pins on connection #2. Thisshould be between the ranges in the table below. Ifit outside this range there is a problem in thesensor and it should be changed out. If it is withinthis range, proceed to the next step.

7. Place negative voltmeter probe on the bottomterminal (yellow wire). Place the other on the onejust above it (terminate freeze sender - white wire).Move the float stem/stick up and down and notethe voltage changes. There should be a significantchange between when it is blocked to when it isnot blocked. If there is NO change, the sensormay be dirty or has failed. Remove the dust coverfrom the sensor to clean it.

Note: The sensor must be properly reassembled.When looking at the terminals of the sensor, theymust be in the lower right corner. If they are in theupper left remove the sensor’s dust cover andreverse the board. Later models have an UP arrowon the right side of the circuit board.

Yellow (bottom)

White - Blocked about 5 VDC

White - Unblocked less than when blocked

8. With the voltmeter probe still on the bottomterminal (connection #2), place the other probe onthe second pin from the top (sump full sender - redwire). Move the float stick up & down, changes involtage should be the same as in step 7.

Yellow (bottom)

Red - Blocked about 5 VDC

Red - Unblocked less than when blocked

9. If all voltages check out, there is nothing wrongwith the sensor or the voltage it receives from thecontroller.

Page 40: eclipselargeman - static-pt.com

Service Diagnosis

Eclipse� 1300, 1600

September 2003Page 40

Problem or Symptom Possible Cause Probable Correction

No ice No power to ice making section Restore power

No power to condensing unit Restore power

No lights on controller Check transformer

Unit manually switched off Push and release the Freeze button, askuser why it was shut off

Power to both sections, controller reset,but condensing unit does not operate

Interconnecting control wiredisconnected, reconnect it

Low or high pressure cut outs open,check system pressures

No water to ice making section, controllerblinking water light twice and repeating

Restore water supply, check water filters,reset controller

Check inlet water valve operation

Check water level sensor operation,including harness between sensor andcontroller*

Ice making section has exceededmaximum freeze time and controller hasshut down the system

Condenser coils may need cleaning

Check condenser fan blade and motor

Check for excessive air intaketemperatures at condenser coil

Check compressor contactor

Check compressor and startingcomponents

Check water pump

Check purge valve for leak through

Check vapor inlet valve for leak though

Ice making section has exceededmaximum harvest time and shut down thesystem

Check ice making section for lime scalebuild up, clean as needed

Check condenser by pass valve

Check vapor inlet valve*

Check headmaster

Check ice sensors for cube sensing*

Check inlet water valve for leak through

Check for obstruction in ice delivery chute

Bin full light is on but bin is not full Check ice sensors*

Check thermostat*

* Additional diagnostics for this component are on the following pages

Page 41: eclipselargeman - static-pt.com

Service Diagnosis

Eclipse� 1300,1600

September 2003Page 41

Problem or Symptom Possible Cause Probable Correction

No ice No refrigeration, unit shut down andrefrigeration diagnostic light is on withoutblinking

Check compressor, refrigerant charge,and liquid inlet valve. Note that if liquidinlet valve is not open, compressor willpump down and suction pressure will bevery low.

No water to ice making section Water level sensor or harness notworking properly

Replace harness or sensor

Slow ice release during harvest Cubes are too large Check inlet water valve for leak through

Check float for sticking

Condenser by-pass valve does not open Check coil of valve

Check power to valve during harvest

No ice sensed during harvest Ice sensing system failure Check sensing system by pouring about10 ice cubes through the ice outlet port.The bin full light should blink, indicatingthat it has sensed the ice. If not, checkthe sensors.

Check the ice sensors. Place an objectbetween the ice sensors, after 5 secondsthe Bin Full light will be glowing steadily,if not check operation of sensors byunplugging #4. Bin Full light will go onafter 5 seconds, If not, replace controller.If the light does go on, replace icesensor set.

No ice released to bin Ice outlet blocked - check for obstruction

No ice released, vapor inlet valve doesnot open

Check coil for continuity, if open replacecoil

Check for 24 volts to coil during harvest,if non, check at controller

Check low side pressure, if pressuredoes not rise during harvest, and valve iselectrically OK, replace vapor inlet valve

Page 42: eclipselargeman - static-pt.com

Service Diagnosis

Eclipse� 1300, 1600

September 2003Page 42

Problem or Symptom Possible Cause Probable Correction

Low capacity Dirty condenser Clean condenser

Air temperature intake to condenservery high

Re-orient condenser to avoid hot airintake

Water temperature intake to ice makingsection very high

Check for hot water supply to icemachine due to mal-functioning ornon-existent hot water check valve atdishwashing sink

False bin full - bin full light is ON and thebin is not full

Unplug thermostat from terminal 7 andcheck controller. Bin full light must goout within 4 minutes or ice sensors needchecking.

Check ice sensors for proper position

Check ice sensors for scale build up

Storage bin or dispenser not holding iceproperly

Check drains for water flow from icemachine (separate to correct) orrestriction

High volume of drinks dispensed, coldplate melting ice

Suggest pre-cooler for water supply tocold plate

Vapor inlet valve leaks through slightlyduring the freeze cycle

Check valve body for similartemperatures on inlet and outlet, theoutlet should be colder and frostdevelops on the tubes to theevaporators

Splash shield missing/out of positionand water is cascading out of thereservoir

Install or re-secure splash shield. Checkwater distributors for proper attachment.

Exceeding maximum freeze time,compressor unit trips on high dischargetemp

Check condenser bypass valve

Poor ice formation - very cloudyand misshapen

Dirty water system Clean the water distributors and the topsof the evaporators to remove built upmineral scale

Low refrigerant charge. Add several pounds of refrigerant tocheck. If low on charge, locate leak.Recover refrigerant, repair leak, replacedrier, evacuate to 300 microns andweigh in the nameplate charge.

Whistling noise at CP unit duringharvest

By pass and liquid inlet valve coils notgetting power

Check harness

Page 43: eclipselargeman - static-pt.com

Controller Features & Last Error RecallLast Error/Diagnostic Light Recall

To recall the last error on the blue housing CM3

controller:

1. Switch the unit OFF by holding the OFF buttonfor longer than 3 seconds.

2. Hold the Off button down again until the PurgeSetting indicators (Green Lights) are on.

3. Push and release the Harvest button.

The last error code stored in the controller will bedisplayed and the purge setting will disappear.

Push the Harvest button again and thesecond-to-last error code will be displayed. The binfull light will also be on to signal that this is thesecond-to-last code.

Pushing the Harvest button again will display thelast error code again. Only two error codes areavailable for display.

If no error code exists, no code will be displayedand there will be NO LIGHTS showing.

To return from the display of the last error, donothing for 60 seconds or push and hold the Offbutton.

After returning from the display of the last error (Offlight glows), the machine may be returned to theice making process by pushing and releasing theFreeze button.

Controller Diagnostic Codes

If a DiagnosticLight

Water Light RefrigerationLight

Blinks once andrepeats

Water pump willnot start

Very long iceharvest

Blinks twice andrepeats

Lack of water fill No harvest of ice

Blinks threetimes andrepeats

not used High dischargetemperature

Is ON all the time Water valveleaking thrurapidly

Maximum freezetime

Both ON all thetime

Check for thermistor set unpluggedor failed

Program ID

The blue housing controller will display a code atpower up that indicates which ice machine model ithas been programmed for.

The code is based on the green lights that aredisplayed.

1. At power up all lights flash ON once to indicatethat the controller has passed its internalself-checks.

2. Immediately after that the program code will bedisplayed for 20 seconds or until a button ispushed.

Note: The proper program code for this machine isglowing

�CME1386: Bin Full and Freeze

�CME1686: Bin Full, Freeze and Clean

Do NOT operate this machine if the wrong code isdisplayed.

3. If no button is pushed after 20 seconds themachine will display the Off light and is ready forswitch inputs (push and release Freeze to startmaking ice).

Note: The Red Diagnostic Lights will beFLASHING while the program ID is displayed.

Eclipse� 1300,1600

September 2003Page 43

Page 44: eclipselargeman - static-pt.com

Operational Characteristics 1300 lb systemCycle Times @ Condenser Temp/Cabinet Temp/Water Temp in degrees F

System Pressures @ Condenser Temp/Cabinet Temp/Water Temp in degrees F.

Headmaster maintains a minimum dischargepressure during freeze of:

�217 PSIG + 25, -15 PSIG

CPR Valve Setting: 55 - 60 PSIG.

Note: CPR allows a maximum low side pressure atthe CP unit’s compressor. Maximum only occursduring harvest.

Refrigerant Charge

�288 oz

Compressor Amps

�Single Phase - 15

�Three Phase - 8

Batch Weight

�16 lb

Discharge Pressure Cut Out Switch

�Cuts Out at: 450 PSIG

�Resets at: 350 PSIG

Compressor: CS20K6E

Expansion Valves: 1

Eclipse� 1300, 1600

September 2003Page 44

70/70/50 90/90/70 120/110/100

Freeze 12 to 13 minutes 16 to 17 minutes 26 to 28 minutes

Harvest 3 minutes 2 minutes 1 minute

70/70/50 90/90/70 120/110/100

Suction at Ice Making Section, end of Freeze 30 to 34 PSIG 32 to 36 PSIG 40 to 44 PSIG

Suction at Ice Making Section, Harvest 70 to 80 PSIG 90 to 110 PSIG 120 to 140 PSIG

Discharge at Condensing Unit: Freeze 230 to 250 PSIG 250 to 270 PSIG 370 to 390 PSIG

Page 45: eclipselargeman - static-pt.com

Operational Characteristics 1600 lb systemCycle Times @ Condenser Temp/Cabinet Temp/Water Temp in degrees F.

System Pressures @ Condenser Temp/Cabinet Temp/Water Temp in degrees F

Headmaster maintains a minimum dischargepressure during freeze of:

�217 PSIG + 25, -15 PSIG

CPR Valve Setting: 55 - 60 PSIG.

Note: CPR allows a maximum low side pressure atthe CP unit’s compressor. Maximum only occursduring harvest.

Refrigerant Charge

�288 oz

Compressor Amps

�Single Phase - 15

�Three Phase - 8

Batch Weight: 19 - 20 lb

Discharge Pressure Cut Out Switch

�Cuts Out at: 450 PSIG

�Resets at: 350 PSIG

Compressor: CS20K6E

Expansion Valves: 1

Eclipse� 1300,1600

September 2003Page 45

70/70/50 90/90/70 120/110/100

Freeze 15 to 16 minutes 17 to 18 minutes 28 to 29 minutes

Harvest 2 ½ minutes 1 ½ minutes 1 ½ minutes

70/70/50 90/90/70 120/110/100

Suction at Ice Making Section, end of Freeze 35 to 37 PSIG 35 to 37 PSIG 40 to 44 PSIG

Suction at Ice Making Section, Harvest - Peak 70 to 80 PSIG 80 to 100 PSIG 120 to 140 PSIG

Discharge at Condensing Unit: Freeze - 5 minutes in 230 to 250 PSIG 250 to 270 PSIG 370 to 390 PSIG

Page 46: eclipselargeman - static-pt.com

Refrigeration System ServiceRecovery

Recovery must be done from the condensing unit,but requires the ice machine to be shut down.

1. At the ice making section, remove the frontpanel.

2. Push and release the Harvest button. When themachine shuts off, recover the refrigerant.

3. Remove compressor package covers.

4. Attach recovery system to low side (compressorprocess port valve)

5. If the recovery system can recover liquid, attachrecovery system to high side (receiver liquid lineout valve)

Operate recovery system to remove refrigerantfrom the system. No other points of attachment orsolenoid activation are required.

Eclipse� 1300, 1600

September 2003Page 46