D a t a s h e e t
ECLYPSEโข Connected System Controller
Overview The ECLYPSE Connected System Controller is a modular and scalable platform that is used to control a wide range of HVAC applications. It supports BACnet/IP communication and is a listed BACnet Building Controller (B-BC).
The ECLYPSE Connected System Controller consists of an automation and connectivity serv-er, power supply, and I/O extension modules.
This programmable Connected System Control-ler provides advanced functionality such as cus-tomizable control logic, Web-based design and visualization interface (ENVYSION embedded), logging, alarming, and scheduling.
ApplicationsThe ECLYPSE Connected System Controller is typically used as:
A controller for medium/large sized Air Han-dling Units (AHU), central plant, and other ap-plications.
Small building server and equipment con-troller with embedded ENVYSION. For ex-ample, it can be used to control and serve a boiler room.
Features & Benefits
IP Communication Communicate over IP for increased speed.
Experience faster response and save time when programming, configuring, creat-ing and viewing graphics, and upgrading your system.
Control technicians can connect the ECLYPSE Wi-Fi Adapter to the Connected System Controller enabling a Wi-Fi Hotspot network. The control technician can then connect wirelessly to the system using a mo-bile device or laptop, for faster, easier system configuration, programming, commissioning and servicing.
ECLYPSE Connected System Controller2/12
ENVYSION Embedded web-based graphic design and
visualization interface. Host system-based graphics such as Air Handling Units, Boiler Room, or Central Plant directly from the con-troller.
Design and create user interface directly from a standard web browser. Responsive in-terface design support allows a single graph-ic design to be automatically adapted to suit the displayโs screen size.
Provides visualization for schedules, alarms, and trend logs.
Programmability
Supports Distech Controlsโ EC-gfxProgram, which makes Building Automation System (BAS) programming effortless by allowing you to visu-ally assemble building blocks together to create a custom control sequence for any HVAC / build-ing automation application.
Scalable and Modular
The Connected System Controller can be ex-panded to support up to 20 input/output (I/O) modules (280 inputs/outputs with any combina-tion of modules). With this flexibility, meet the re-quirements of any HVAC application from small to medium to large systems while being able to adapt to new requirements as the need arises.
Repeatable power supply concept can be used when more power is required to power a series of I/O modules.
Cable connection is used to connect successive rows of modules within a controlsโ cabinet to pro-vide power and communication.
BACnet/IP Device
The Connected System Controller is a listed BACnet Buidling Controller (B-BC). It supports BACnet/IP communications for faster commu-nication in comparison to the traditional twisted pair communication bus.
Alarms, Trend Log, Schedule Support
Embedded alarms, trend log and schedule sup-port allows for fully distributed data and logic providing a more robust system. Embedded trend logs simplify system troubleshooting when compared to a centralized system.
Mobility
The ECY-S1000 can be remotely accessed to program, configure, or maintain the installation thus reducing costs associated with on-site vis-its. Through a mobile device or PC, the different tasks can be performed using the following free-to-use tools and interfaces:
ENVYSION web-based graphic design and visualization interface
EC-gfxProgram graphical programming in-terface
myDC Controls mobile application
3/12ECLYPSE Connected System Controller
Robust Protection
The I/O modules are protected against mis-wir-ing and faults to prevent damage caused by in-correct wiring or other mishaps.
The power supply module contains over-voltage and over-current output protection to protect the electronics in unstable power supply conditions and against mis-wiring.
I/O Status LEDs
The status LEDs on the I/O modules allow the user to confirm the status of the inputs/outputs and facilitate commissioning and troubleshoot-ing.
Ease of Installation
The Connected System Controller modules are plug & play devices. They are equipped with HD-15 connectors that transmits power and commu-nications to the next module for fast and easy as-sembly.
Auto-Addressing
The auto-addressing feature eliminates the need to manually assign an address to each I/O mod-ule therefore reducing installation and configura-tion time.
Hot-Swappable Tool-Less Design and Unique Latching Mechanism
The I/O modules are hot-swappable for replace-ment without interrupting power and communi-cations to other modules.
The front assembly of I/O modules separate from the wiring base by pushing the two latches up to unlock a moduleโs front assembly and then opening and pulling the hinged gull-wing covers. The latch design locks the front assembly to the wiring base.
The hinged gull-wing design protects and cov-er the stacked dual row detachable I/O termi-nal strips.
Color-Coded I/O
Terminal blocks are uniquely identified and color-coded for clarity and to prevent wiring mistakes.
Hand/Off/Auto Switches and Potentiometers
The front assembly of Hand/Off/Auto (HOA) equipped I/O models allow users to override the control outputs for commissioning and mainte-nance purposes.
Potentiometers provide manual analog signal and output control to override voltage or cur-rent signal.
High-Efficiency Design
The power supply uses the latest high-efficiency switch-mode circuitry to make more power avail-able to operate additional modules and for cool-er operation.
ECLYPSE Connected System Controller4/12
Model SelectionThe ECLYPSE Connected System Controller consists of a power supply, an automation and connec-tivity server, and I/O extension modules. The different models for each are shown in the tables below.
I/O ModulesUniversal Inputs Universal Outputs
Bas
ic P
ower
Con
sum
ptio
n2 , W
Qua
ntity
Con
tact
Cou
nter
0 to
10V
DC
0 to
5V
DC
0 to
20m
A
Res
ista
nce
Ther
mis
tor
18V
DC
Pow
er S
uppl
y
Qua
ntity
0 or
12V
DC
PW
M
Floa
ting
0 to
10V
DC
1
0 to
20m
A1
HO
A
ECY-8UI/6UO 8 6 UO1 UO2 UO3
0.94
ECY-8UI/6UO.HOA 8 6 UO1 UO2 UO3
0.94
1. 0 to 10VDC is available on UO1 to UO6. 0 to 20 mA is available on UO1, UO2, and UO3; this option is individually selected through an on-board DIP switch setting.
2. External loads excluded. See the ECLYPSE Selection Tool to calculate the number of Input/Output Extension Modules that can operate with a power supply.
Automation and Connectivity ServersECY-S1000 Connected System Controller for medium/large sized AHU and plant
applications and small building server/controller applications.Supports up to 20 ECY I/O extension modules.
ECY-S1000 with ENVYSION
Connected System Controller for medium/large sized AHU and plant applications and small building server/controller applications. Embed-ded ENVYSION Studio & Viewer. Supports up to 20 ECY I/O extension modules.
Accessories
ECLYPSE HD15 Cable 6ft (1.8m) cable for Connected System Controller multiple-row panel installations. An HD15 cable must always be followed by an ECY-PS24 power supply module. For more information, refer to the Hardware Installation Guide.
Power SupplyECY-PS24 24VAC/VDC power supply module for the ECY-S1000. A power supply
module must be added after each HD15 cable (see Accessories below).
5/12ECLYPSE Connected System Controller
Product SpecificationsPower Supply (ECY-PS24)Power Supply InputVoltage Rangeโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 24VAC/DC; ยฑ15%; Class 2Power Consumption โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 60VA typical plus all external loads1
โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ100VA maximumFrequency Range โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 50 to 60HzOver Voltage Input Protection โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Field replaceable fuseFuse Type โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 4A, fast-acting, 5 ร 20mm (GMA-4A)
Power Supply OutputDC Voltage โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 18VDC regulatedRated Current Range โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ0 to 1.6ARated Power โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 30W1
1. The total power consumption of all modules connected to the right of this power supply, and up to the next connected power supply, including any connected loads, must be less than this value. A separate transformer rated at 60VA minimum must be used for each ECY-PS24 power supply for it to operate at full capacity.
HardwarePower Distribution Direction โโโโโโโโโโโโโโโโโโโ Powered modules are connected to the rightBackplane Bus โโโโโโโโโโโโโโโโโโโโโโ Pass-through connection for data and control signalsStatus Indicator โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโGreen LED: power status
MechanicalDimensions โโโโโโโโโโโโโโโโโโโโโโโ 2.85 W ร 4.74 H ร 2.31โ D (72.38 ร 120.31 ร 58.56mm)
4.74" 120.31 3.18" 80.82
18.390.72
21.130.83
2.31" 58.5672.38
Inches Millimeters
0.01" 0.40Inter-Connection Gap:
2.61" 66.190.06" 1.44
0.17" 4.24 2.85"
4.96" 125.99
Front BackProfile
Shipping weight โโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 0.75lbs (0.34kg)
ECLYPSE Connected System Controller6/12
Power Supply (contโd)Mounting โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโDIN rail or screw mountingEnclosure Material1 โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ FR/ABSEnclosure Rating โโโโโโโโโโโโโโโโโโโโโโโโโโโ Plastic housing, UL94-V0 flammability rating
Plenum rating per UL19951. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)
directive.
EnvironmentalOperating Temperature โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 32ยบF to 122ยบF (0ยบC to 50ยบC)Storage Temperature โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ -22ยบF to 158ยบF (-30ยบC to 70ยบC)Relative Humidity โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 0 to 90% Non-condensingIngress Protection Rating โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ IP20Nema Rating โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 1
Standards and Regulations CE:
Emission โโโโโโโโโโโโโโโโ EN61000-6-3: 2007; A1:2011; Generic standards for residential, commercial and light-industrial environments
Immunity โโโโโโโโโโโโโโโโโโโโโโโ EN61000-6-1: 2007; Generic standards for residential, commercial and light-industrial environments
FCC โโโโโโโโโโโโโโโโโโโโโโ This device complies with FCC rules part 15, subpart B, class B UL Listed (CDN & US) โโโโโโโโโโโโโโโโโโโโโโโโโโโ UL916 Energy management equipment
Automation and Connectivity Server (ECY-S1000)Power Supply InputVoltage โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 18VDCPower Consumption โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 8.9W; external loads excluded
CommunicationsEthernet Connection Speed โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ10/100 MbpsBACnet Profile โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ BACnet Building Controller (B-BC)BACnet Interconnectivity โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ BBMD forwarding capabilitiesBACnet Transport Layer โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโIPBACnet Listingโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ BTLWeb Server Protocol โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ HTML5Web Server Application Interface โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโREST APIOptional Supported Wireless Connectivity:
Wi-Fi Communication Protocol โโโโโโโโโโโโโโโโโโโโโโโโ IEEE 802.11a/b/g/n and 802.11s Wi-Fi Network Types โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโClient, Access Point, Hotspot
7/12ECLYPSE Connected System Controller
Automation and Connectivity Server (contโd)HardwareProcessor โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Sitara ARM processorCPU Speed โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 1GHzMemory โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 4GB Non-volatile Flash (applications & storage)โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 512MB RAMReal Time Clock (RTC) โโโโโโโโโโโโโโโโโโโโโโโโReal Time Clock with rechargeable battery โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Supports SNTP network time synchronizationRTC Battery โโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 20 hours charge time, 20 days discharge timeโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโUp to 500 charge / discharge cyclesCommunications Ports:
Ethernet โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 2 switched RJ-45 Ethernet ports USB Connections โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 2 ร USB 2.0 Ports
โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 1 ร Micro-USB 2.0 Ports RS-485 Serial Communications โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Screw terminals Subnet โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโRJ-45
Status Indicators โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Green LEDs: power status & LAN Txโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Orange LEDs: controller status & LAN Rx
MechanicalDimensions โโโโโโโโโโโโโโโโโโโโโโโโ3.57 W ร 4.74 H ร 2.31โ D (90.67 ร 120.31 ร 58.56mm)
3.18" 80.82
18.540.73
21.080.83
3.33" 84.47
0.4" 1.092.31" 58.563.57" 90.67
Inches Millimeters
Inter-Connection Gap: 0.01" 0.40
5.13" 130.29
0.06" 1.44
4.74" 120.31
0.39" 9.98 Front BackProfile
Shipping weight โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 0.85lbs (0.39kg)Mounting โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโDIN rail or screw mountingEnclosure Material โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ FR/ABSEnclosure Rating1 โโโโโโโโโโโโโโโโโโโโโโโโโโ Plastic housing, UL94-V0 flammability ratingโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Plenum rating per UL19951. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)
directive.
ECLYPSE Connected System Controller8/12
I/O ModulesPower Supply InputVoltage โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 18VDCPower Consumption โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Calculate power supply requirements
with the ECLYPSE Selection Tool
HardwareStatus Indicator โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Green LEDs: inputs and outputs Enclosure Material โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ FR/ABS
MechanicalDimensions โโโโโโโโโโโโโโโโโโโโโโโโ 3.20 W ร 4.74 H ร 2.31โ D (81.17 ร 120.31 ร 58.56mm)
2.95" 74.99
4.74" 120.31
3.20" 81.17 2.31" 58.56
3.18" 80.82
18.540.73
21.080.83
Inches Millimeters
Inter-Connection Gap: 0.01" 0.40
Front BackProfile
Automation and Connectivity Server (contโd)EnvironmentalOperating Temperature โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 32ยบF to 122ยบF (0ยบC to 50ยบC)Storage Temperature โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ -22ยบF to 158ยบF (-30ยบC to 70ยบC)Relative Humidity โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 0 to 90% Non-condensingIngress Protection Rating โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ IP20Nema Rating โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 1
Standards and Regulations CE:
Emission โโโโโโโโโโโโโโโโ EN61000-6-3: 2007; A1:2011; Generic standards for residential, commercial and light-industrial environments
Immunity โโโโโโโโโโโโโโโโโโโโโโโ EN61000-6-1: 2007; Generic standards for residential, commercial and light-industrial environments
FCC โโโโโโโโโโโโโโโโโโโโโโ This device complies with FCC rules part 15, subpart B, class B UL Listed (CDN & US) โโโโโโโโโโโโโโโโโโโโโโโโโโโ UL916 Energy management equipment
9/12ECLYPSE Connected System Controller
I/O Modules (contโd)Shipping weight โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 0.85lbs (0.39kg)Mounting โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโDIN rail or screw mountingEnclosure Material โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ FR/ABSEnclosure Rating1 โโโโโโโโโโโโโโโโโโโโโโโโโโ Plastic housing, UL94-V0 flammability ratingโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Plenum rating per UL19951. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)
directive
EnvironmentalOperating Temperature โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 32ยบF to 122ยบF (0ยบC to 50ยบC)Storage Temperature โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ -22ยบF to 158ยบF (-30ยบC to 70ยบC)Relative Humidity โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 0 to 90% Non-condensingIngress Protection Rating โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ IP20Nema Rating โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 1
Standards and RegulationsCE:
Emission โโโโโโโโโโโโโโโโ EN61000-6-3: 2007; A1:2011; Generic standards for residential, commercial and light-industrial environments
Immunity โโโโโโโโโโโโโโโโโโโโโโโ EN61000-6-1: 2007; Generic standards for residential, commercial and light-industrial environments
FCC โโโโโโโโโโโโโโโโโโโโโโ This device complies with FCC rules part 15, subpart B, class B UL Listed (CDN & US) โโโโโโโโโโโโโโโโโโโโโโโโโโโ UL916 Energy management equipment
ECLYPSE Connected System Controller10/12
I/O Modules - Universal Inputs (UI)GeneralInput Type โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Universal; software configurableCurrent Input Option Selection โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ DIP switchInput Resolution โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 16-bit analog to digital converterPower Supply Output โโโโโโโโโโโโโโโโโโโโโโโ 18VDC; 20mA maximum per 0 to 20 mA input
ContactType โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโDry contact
CounterType โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโDry contactMaximum Frequency โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 1Hz maximum,Minimum Duty Cycle โโโโโโโโโโโโโโโโโโโโโโโโโโ 500milliseconds On / 500milliseconds Off
0 to 10VDCRange โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 0 to 10VDC (40kฮฉ input impedance)
0 to 5VDCRange โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 0 to 5VDC (high input impedance)
0 to 20mARange โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ0 to 20mAโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 249ฮฉ DIP-switch configurable internal resistor
Resistance/ThermistorRange โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 0 to 350 Kฮฉ.Supported Thermistor Types โโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Any that operate in this rangePre-configured Temperature Sensor Types:
Thermistor โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 10Kฮฉ Type 2, 3 (10Kฮฉ @ 77ยบF; 25ยบC) Platinum โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Pt1000 (1Kฮฉ @ 32ยบF; 0ยบC) Nickel โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ RTD Ni1000 (1Kฮฉ @ 32ยบF; 0ยบC)
โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ RTD Ni1000 (1Kฮฉ @ 69.8ยบF; 21ยบC)
11/12ECLYPSE Connected System Controller
I/O Modules - Universal Outputs (UO)GeneralOutput Type โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Universal; software configurableOutput Resolution โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 10-bit digital to analog ConverterOutput Protection โโโโโโโโโโโโโโโโ Built-in snubbing diode to protect against back-EMF, when
used with a 12VDC relayLoad Resistance โโโโโโโโโโโโโโโโโโโ Minimum 200ฮฉ for 0 to 10VDC and 0 to 12VDC outputsโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Maximum 500ฮฉ for 0 to 20mA outputAuto-reset Fuse โโโโโโโโโโโโโโโโโโโโโ 20mA maximum per 0 to 60 mA output @ 140ยบF; 60ยบCโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 33mA maximum per 0 to 100 mA output @ 68ยบF; 20ยบC
0 or 12VDC (On/Off)Range โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ0 or 12VDC
PWMRange โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโAdjustable period from 2 to 65seconds
FloatingMinimum Pulse On/Off Time โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 500milliseconds,Drive Time Period โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Adjustable
0 to 10VDCRange โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ 0 to 10VDC linear
0 to 20mARange โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ0 to 20mACurrent Source โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ20mA maximum per 0 to 20 mA output Ports UO1, UO2, and UO3 only โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ DIP switch
HOAHand-Off-Auto switch โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ When equippedโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Supervision allows control logic to read the current
HOA switch and potentiometer settings Threshold โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ Configurable Potentiometer voltage range โโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโโ0 to 12VDC
05DI-DSIPCTR-12
Specifications subject to change without notice. ECLYPSE, Distech Controls, and the Distech Controls logo are trademarks of Distech Controls Inc. BACnet is a registered trademark of ASHRAE; BTL is a
registered trademark of the BACnet Manufacturers Association. All other trademarks are property of their respective owner. ยฉ, Distech Controls Inc., 2014. All rights reserved.
12/12