of 47
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
1/47
SRI LANKA INSTITUTE of ADVANCED TECHNOLOGICAL
EDUCATION
Training Unit
Electrical Control 2
Theory
No: EE 015
ELECTRICAL and ELECTRONIC
ENGINEERING
Instructor Manual
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
2/47
1
Training Unit
Electrical Control 2
Theoretical Part
No.: EE 015
Edition: 2008Al l Rights Reserved
Editor: MCE Industrietechnik Linz GmbH & CoEducation and Training Systems, DM-1Lunzerst rasse 64 P.O.Box 36, A 4031 Linz / Aus triaTel. (+ 43 / 732) 6987 - 3475Fax (+ 43 / 732) 6980 - 4271Website: www.mcelinz.com
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
3/47
2
ELECTRICAL CONTROL 2
CONTENTS Page
LEARNING OBJECTIVES...................................................................................................3
1 SCHEMATIC DIAGRAMS ............................................................................................4
1.1 Wiring diagram.....................................................................................................4
1.1.1
Hints for the design of wiring diagrams ............................................................7
1.2
Single line diagram ............................................................................................13
1.3 Complete circuit diagram ...................................................................................14
1.4 Lay-out diagram .................................................................................................15
1.5
Equipment diagram............................................................................................15
1.6
Terminal table ....................................................................................................16
2 TYPES OF CIRCUIT CONSTRUCTION ....................................................................17
3
WIRING OF CIRCUITS ..............................................................................................18
4 ENVIRONMENTAL EFFECTS ...................................................................................19
4.1.
Protection against climatic influences ................................................................19
4.2. Protection against vermin ..................................................................................19
4.3.
Protection against corrosion ..............................................................................19
5 FAULT FINDING ........................................................................................................ 20
5.1. Tips for remedying faults....................................................................................20
6
SUMMARY OF SWITCHING SYMBOLS ...................................................................24
7 IDENTIFICATION LETTERS FOR GENERAL FUNCTIONS .....................................33
8
GLOSSARY OF ELECTRICAL TERMS.....................................................................35
8.1. Definition of characteristic quantities .................................................................35
9
OPERATING EQUIPMENT........................................................................................36
9.1. Designation of operating equipment ..................................................................36
9.1.1. Designation block "type, number, function"................................................36
9.1.2. Designation block "plant" ...........................................................................37
9.1.3.
Designation block "location".......................................................................37
9.1.4.
Designation block "connection"..................................................................38
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
4/47
3
ELECTRICAL CONTROL 2
LEARNING OBJECTIVES
name and describe schematic diagrams.
draw wiring diagrams complying with standards.
recognize switching symbols and design simple contactor circuits.
state the difference between wiring diagram and complete circuit diagram.
produce a terminal table.
list the types of wiring.
recognize and find minor faults.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
5/47
4
ELECTRICAL CONTROL 2
1 SCHEMATIC DIAGRAMS
These are used to represent electrical devices by means of symbols. Operating
equipment can be shown in a simplified form.
Schematic diagrams always show the equipment de-energized, in the mechanically non-
activated condition.
1.1 Wiring diagram
This is the most frequently used representation of a circuit in electrical engineering.
The current paths should be drawn in straight lines, as far as possible, and without
crossovers.
The spatial position and mechanical interconnection of individual parts are not taken into
account.
The wiring diagram should show the method of operation and switching sequence of a
control system clearly and unambiguously.
The magnet coils (contactor coils) should be arranged in such a way that one terminal is
directly connected to the neutral line of the control circuit. The input to the coil is
connected to the other control line via various switching elements (contacts) of the
switchgear (pushbuttons, overcurrent relays etc.).
All contacts operated by one contactor have the same designation as the contactor itself.
Terminals are shown, and are given the same numbers as on the terminal table and the
circuit diagram.
For large circuits it is recommended that the wiring diagram should be divided into current
paths.
The equipment diagram of switchgear can be shown below the current path (as shown on
page 8).
The switch contact types, whether they are normally closed or open, the section in which
they are found and whether any of the contacts are free.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
6/47
5
Each piece of equipment is lettered to indicate its type. 1f here are several items of the
same type of equipment, they are given consecutive numbers. A further letter indicates its
general function, e.g., K 2 A auxiliary contactor and K 4 M main contactor (motor
contactor).
a) Main circuit wiring diagram
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
7/47
6
b) Control circuit wiring diagram
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
8/47
7
1.1.1 Hints for the design of wiring diagrams
When designing a wiring diagram, the following points should be observed.
a) The current paths are drawn vertically, in between the horizontally drawn bus bars.
b) Switching appliances, switchgear and initiating equipment must be drawn at right
angles to the current path.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
9/47
8
c) The direction of the current flow should always be from top to bottom.
d) Crossover of lines should be avoided.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
10/47
9
e) Apparatus and equipment must be represented in zero volt condition (switched off).
Exceptions have to be clearly indicated (i.e. arrow).
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
11/47
10
f) Control equipment e.g. coils, signal lamps must be connected directly to the neutral
conductor, or in case of an earthed supply system, to the potential earth neutral (PEN)
conductor.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
12/47
11
g) Current paths must be numbered consecutively, circuit elements must be placed from
left to right, depending on their sequence of operation. Circuit elements must be
provided with code letters and consecutive numbers.
For clean representation of the various circuit elements, a table can be added below
the wiring diagram.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
13/47
12
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
14/47
13
1.2 Single line diagram
This is a simplified, single-phase representation of the circuit.
F1 = motor fuses
F2 = overcurrent relay
K1 = motor contractor
M1 = 3-phase AC motor
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
15/47
14
1.3 Complete circuit diagram
This is the representation of a circuit in all its details.
As both main and control circuits appear in one diagram, this can become unwieldy and
makes fault finding more difficult.
F1 = motor fuses K1 = motor contractor
F2 = overcurrent relay M1 = 3-phase AC motor
F3 = control fuses S1 = ON-OFF-pushbutton
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
16/47
15
1.4 Lay-out diagram
This is a document for wiring up the components. All equipment is shown in the correct
position.
1.5 Equipment diagram
This gives information on electrical switchgear (contactors, controllers, and master
switches etc.), but not on its construction. The switch positions and contacts must havethe same designation on the wiring diagram.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
17/47
16
1.6 Terminal table
The terminals shown in the wiring diagram and complete circuit diagram are compiled in
the terminal table into terminal strips. The terminal table contains the cable or wire
numbers, the terminal number, the origin and the destination.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
18/47
17
2 TYPES OF CIRCUIT CONSTRUCTION
Small circuits are built up on boards and are installed in the places provided on the
machines, e.g., star-delta starter circuit.
Cubicles are fixed directly to the machine and contain all control and switching devices.
Freestanding cubicles for large machine tool controls contain e.g. measuring equipment,
switching devices and control devices.
Freestanding contactor boards are used for extensive electrical plants, e.g., rolling mills
and cranes etc.
Contactor boards are erected separately in the switchgear rooms provided.
Control desks contain all the Instruments and control devices on one board, in order to be
able to control a plant from a central position.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
19/47
18
3 WIRING OF CIRCUITS
Wiring in ducts:
This is affected by laying wired in plastic ducts. Note:
Always make the ducts large enough.
Back-panel wiring:
Wires are connected on the back of panels.
Note:
When wiring is taken through a panel, grommets should be used, otherwise the wiring
insulation will be damaged.
Flat wiring:Individual wires are laid next to and above one another in layers.
Round bundle wiring:
Bundles of wires are bunched with string or held together by tapes.
Laced wiring harness:
This is a preformed and tied bundle of wires.
Quick wiring:
The wires are laid from terminal to terminal (by the shortest path).
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
20/47
19
4 ENVIRONMENTAL EFFECTS
4.1. Protection against climatic influences
The required control devices may be affected by local conditions. This means that the
prevalent climatic conditions have to be taken into consideration in advance.
The control devices have to work satisfactorily in temperate and dry climates, as well as in
hot climates with high air humidity. If water condenses in a control cubicle due to frequent
temperature changes at high air humidity (changing climate), then control devices will not
function properly. Heaters may be employed to ensure that water is not deposited in the
equipment.
4.2. Protection against vermin
Control devices may suffer adverse effects from vermin (e.g. termites). Components made
of materials containing cellulose should be avoided in electrical operating areas, and a
high degree of cleanliness and brightness of illumination should be ensured. It is useful to
employ encapsulated equipment in areas likely to be affected by vermin.
4.3. Protection against corrosion
There is a corrosive atmosphere in many plants due to the manufacturing processes e.g.
in chemical and electroplating works and steelworks etc.
The following information may serve as a rough guide:
In atmospheres in which human beings can exist, normal encapsulation of equipment will
provide resistance to corrosion.
Metal parts used as contacts must be suitable for the constructional and switching load
requirements. They are male of precious metals or appropriate alloys.
The above considerations do not only apply for contactors and switchgear, but for all
electrical machines and electrical installations.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
21/47
20
5 FAULT FINDING
For rated voltages above 42 V up to a voltage of 250 V to earth, work on live parts is only
permitted, if, in order to prevent danger or for other important reasons, it is impossible to
make those parts of the plant dead, on which work is to be carried out. Such work may
only be carried out by an "expert". An expert is one who can judge and recognize possible
dangers based on his technical training, knowledge and experience as well as his
knowledge of the appropriate regulations applying to the work entrusted to him.
Electricians with completed electro-technical engineering training fulfil these conditions.
Note:
Under no circumstances may apprentices work on live parts of a plant.
5.1. Tips for remedying faults
This table includes the faults which occur most frequently on contactors.
CAUSE REMEDY
Contactor does not switch on:
Control fuse burnt out. Fist remove cause of short circuit, then
replace the fuse.
Thermal overload relay has operated Wait for cooling period, press reset button.
Switch on again.
Coil defective Replace coil
Coil for wrong voltage, wrong
frequency or wrongly connected.
Replace coil. Change the circuit.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
22/47
21
Low voltage (permitted lower limit
0.85 x UC) particularly for DC operated
contactors.
Replace coil, use special coil for increased
voltage security
(0.75 x UC). Provide stable mains supply.
Low voltage 214 V. Note the voltage drop. If necessary, choose
higher control voltage.
Circuit errors. Look for and remove the cause. Go
through the wiring diagram step by step.
By-pass normally closed contacts in circuit,
one by one.
Broken wire. Pull the wires to check whether they are
broken inside the insulation. Frequently the
break in the wire, caused by incorrect
removal of the insulation, is inside the
insulation.
Contactor with thermal overcurrent device
trips
Thermal overcurrent trip not operating
correctly
Set trip to motor operating current. Note
that, in the delivered condition, the trip is
always set to the lowest current value.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
23/47
22
Long starting time due to starting against
the load, too low voltage.
Install thermal overcurrent
trip with saturation transformer. During start
up the load should be switched off
(coupling) so that rotary Pumps should not
be started against a closed gate valve.
Measure voltage at motor terminals.
Check cross section of wires (possibly
voltage drop). Thermal trips are by passed
during starting period.
Too high switching frequency. Use thermistor protection. Thermal
overload trips are only suitable up to 15
operations/ hour.
Bimetal strip has turned blue or burnt out;
overload due to too high current; short
circuit with wrong (too high) fuse ratings.
Change overload trip. Install fuses suitable
for overload trip.
Loss of one-phase (motor does not start - it
hums).
Possibly a burnt-out fuse, loose or broken
main connection to motor winding.
Contactor does not switch off
Contactor contacts welded together. Break the contacts apart and replace them.
Install bigger type of contactor.
The control wires between contactor and
operating device is too long (holds itself in
due to capacitive currents).
Lower the control voltage. Install contactor
with smaller holding capacity.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
24/47
23
Stop push Button is short circuited. Remove short circuit, break the contacts
apart, if necessary, and renew them.
Faulty star-delta circuit switching. Use timing relay with changeover time .of
40 - 100 s. Set timing relay to longer time
period. The motor must nearly reach the
nominal speed in the star circuit.
Contactor flutters. Ensure that the operating signal is correct.
Remove fault on operating elements.
Check rated voltage of the contactor coil.
Contactor hums
Coil of wrong voltage or wrong frequency. Replace coil.
Magnet surfaces dirty or corroded (after
long period of shutdown).
Clean magnet surfaces. Do not file, do not
grease them.
Short circuiting ring broken. Replace contactor.
Foreign bodies in air gap. Switch on and off several times.
Remove foreign bodies.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
25/47
24
6 SUMMARY OF SWITCHING SYMBOLS
Contacts with two or three positions Description
Symbol Description
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
26/47
25
Wiring contacts with two positions
Leading and lagging contacts
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
27/47
26
Contacts showing delay in actuation and resetting
Contacts with automatic and non-automatic resetting
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
28/47
27
Switches
Symbols Description
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
29/47
28
Switches, which are actuated by pushing or pulling, normally have an inherent reset force.
It is therefore not necessary to draw the symbol for automatic reset.
In exceptional cases, where switches have latching qualities, the symbol for latching is to
be used.
Switchgear
Symbol Description
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
30/47
29
Electromechanical and electromagnetic drives
Symbol Description
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
31/47
30
Fused and fuse switches
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
32/47
31
Electrical machines and transformers
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
33/47
32
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
34/47
33
7 IDENTIFICATION LETTERS FOR GENERAL FUNCTIONS
Letter General function
A Auxiliary function
BDirection of movement (forwards, backwards, raising, lowering,
clockwise, anticlockwise)
C Counting
D Differentiation
E ---
F Protection
G Test
H Alarm
J IntegrationK Pushbutton operation
L ---
M Main function
N Measurement
P Proportional
Q Condition (start, stop, limits)
R Reset, cancel
S Storage, indication
T Time measurement, time delay
U ---
V Speed (acceleration, braking)
W Addition
X Multiplication
Y Analogue
Z Digital
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
35/47
34
For example:
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
36/47
35
8 GLOSSARY OF ELECTRICAL TERMS
8.1. Definition of characteristic quantities
Rated insulation voltage
Uiis the standardised value of voltage for which the insulation is suitable.
Rated voltage (rated operating voltage)
Ueis the reference voltage for switching.
Continuous current (thermal rated current)
Ith2is the current which the switchgear can carry for an unlimited period of time in normaloperating conditions, without the controls having to be cleaned and without the limiting
maximum temperatures being exceeded.
Rated operating current
Ieis the current reached in normal operation
Mechanical life span
The mechanical life span in expressed by the number of switching cycles possible under
no-load condition.
Life span of switching contacts
The life span of switching contacts is determined by the number of switching cycles which
can be achieved under full load conditions.
Frequency of switching
Frequency of switching is the number of switching operations (number of switching cycles)
per hour.
Rated actuating voltage UC
Control voltage is the voltage for which the coil or the tripping mechanism is suitable. It is
also called the coil rated voltage.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
37/47
36
9 OPERATING EQUIPMENT
9.1. Designation of operating equipment
The complete system of designation contains four blocks. Each block has a prefix for
designation.
Prefix Information in identification block
- Type of operating equipment Consecutive number Function
= Plant
+ Location
: Connection
The four designation blocks can be arranged in any sequence. i.e.:
: A 1 = B4 + D1 K 3 A
or
- K 3 A + D1 = B4 : A1
For small units it is sufficient to quote one or two designation blocks. Normally only the
designation block "Type of operating equipment - consecutive number - function" is used,
so that the prefix can be omitted.
i.e.: instead of - K 3 A only K 3 A
9.1.1. Designation block "type, number, function"
For the designation of "type" an identification letter from the table "identification letters for
type of equipment" must be used.
The consecutive number is obligatory, and must always be stated. In some cases the
number alone might be sufficient to designate operating equipment.
The function relative to other operating equipment is indicated by a letter from the table
"identification letters for general functions".
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
38/47
37
The designation of the function may be omitted if is not required. However it is not
permitted to use the designation "function" by itself.
9.1.2. Designation block "plant"
The designation "plant" is written down only once in a suitable place on the switching
document. The designation of the plant may be omitted if not required.
9.1.3. Designation block "location"
The designation "location" states, where the operating equipment is located. The
designation of location may be omitted if not required.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
39/47
38
9.1.4. Designation block "connection"
The designation "connection" has a colon as prefix. The designation of connection may be
omitted if not required.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
40/47
39
Examples of block combinations
Designation Block combination Explanation
= C 1 -K 5 A
= Plant
- Type, consecutive
number, function
Auxiliary contactor K 5 in plant C 1
+ L 2 : 3+ Location
: ConnectionTerminal 3 of component L 2
= B 2 + 2 D 4 = Plant
+ Location
4th component of control panel 2 on
floor D of plant B 2
- K 2 M. : 11
- Type, consecutive
number, function
: Connection
Terminal 11 of main contactor K 2
= B 3 B + D = Q
= Plant
+ Location
- Type, number, function
Circuit breaker Q of panel D, Plant B
3 B
+ A 2 - S 10 : 4
+ Location
- Type, number,
function
: Connection
Terminal 4 of push button S 10 on
control desk A 2
: A 1 = B 4+ D 1 - K 3 A
: Connection
= Plant
+ Location
- Type, number, function
Terminal A 1 of
auxiliary contactor K 3, control panel
D 1, plant B 4
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
41/47
40
EE 015
Electrical Control 2
Theoretical Test
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
42/47
41
ELECTRICAL CONTROL 2
TEST 1
1. Explain the purpose of schematic diagrams.
2. Name the six different types of schematic diagrams.
3. Draw an equipment diagram for a contactor with three main contacts and four auxiliary
contacts (two normally closed and two normally open contacts).
4. What information is provided by a terminal table?
5. State how back panel wiring is carried out.
6. What is the purpose of a control desk?
7. State what is meant by the term "laced wiring harness".
8. The contactor of a switching circuit "hums". Name possible sources of error.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
43/47
42
ELECTRICAL CONTROL 2
TEST 2
1. State four points which have to be observed when designing a wiring diagram.
2. Describe the design of a complete circuit diagram.
3. Describe the term "flat wiring".
4. Draw an equipment diagram for a contactor with three main contacts and two auxiliary
contacts (one normally closed and one normally open).
5. Explain the term "frequency of switching" of a contactor.
6. Name the two main parts of a wiring diagram.
7. Trouble shooting in control circuits must be carried out by experts only. Which persons
qualify under the stipulation of operating instructions for the term "expert"?
8. The contactor of a switching circuit "flutters". Name possible sources of error.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
44/47
43
ELECTRICAL CONTROL 2
TEST 1
(Solution)
1. Representation of electrical installations through switching symbols. Simple
representation of operational equipment.
Schematic diagrams always show the equipment in a de-energized state, i.e. in the
mechanically non-activated condition.
2. Wiring-, single-line-, complete circuit-, lay out-, equipment diagram and terminal table.
3.
4. Cable or wire number, terminal number, the origin and the destination.
5. Wires are connected on the back of panels. Always use grommets through the panel.
6. All instruments and control equipment assembled on one panel for purpose of
controlling a plant from one central place.
7. This is a preformed and tied bundle of wires.
8. Coil on wrong voltage or frequency; dirt on the mating faces of the magnetic core;
short circuiting ring broken; foreign body in the air gap.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
45/47
44
ELECTRICAL CONTROL 2
TEST 2
(Solution)
1. The current paths are drawn vertically in between the horizontally drawn bus bars.
Circuit elements must be drawn at right angles to the current path.
The direction of current flow should always be from top to bottom. Crossovers of lines
should be avoided.
Circuit elements must be represented in zero volt condition (switched off).
Control equipment such as coils, signal lamps etc. must be connected directly to the
neutral conductor.
Current paths must be numbered consecutively, circuit elements must be provided
with code letters and consecutive numbers.
2. The complete circuit diagram is the representation of a circuit in all its details.
If the main and control circuits appear in one diagram, it can become unwieldy and
makes fault finding more difficult.
3. Individual wires are laid next to end above one another in layers.
4.
5. The number of switching cycles per hour.
6. Main circuit and control wiring diagrams.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
46/47
45
7. An expert is one who can judge and recognize possible dangers, based on his
technical training, knowledge and experience as well as his knowledge of the
appropriate regulations applying to the work entrusted to him. Electricians with
completed electro-technical engineering training fulfil these conditions.
8. The operating signal is not correct. Fault on the operating elements. Contactor coil
voltage is incorrect.
7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf
47/47
KEY TO EVALUATION
PER CENT MARK
88 100 1
75 87 2
62 74 3
50 61 4
0 49 5