+ All Categories
Home > Documents > EE015-Electrical Control 2-Th-Inst.pdf

EE015-Electrical Control 2-Th-Inst.pdf

Date post: 28-Feb-2018
Category:
Upload: sameera
View: 223 times
Download: 0 times
Share this document with a friend

of 47

Transcript
  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    1/47

    SRI LANKA INSTITUTE of ADVANCED TECHNOLOGICAL

    EDUCATION

    Training Unit

    Electrical Control 2

    Theory

    No: EE 015

    ELECTRICAL and ELECTRONIC

    ENGINEERING

    Instructor Manual

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    2/47

    1

    Training Unit

    Electrical Control 2

    Theoretical Part

    No.: EE 015

    Edition: 2008Al l Rights Reserved

    Editor: MCE Industrietechnik Linz GmbH & CoEducation and Training Systems, DM-1Lunzerst rasse 64 P.O.Box 36, A 4031 Linz / Aus triaTel. (+ 43 / 732) 6987 - 3475Fax (+ 43 / 732) 6980 - 4271Website: www.mcelinz.com

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    3/47

    2

    ELECTRICAL CONTROL 2

    CONTENTS Page

    LEARNING OBJECTIVES...................................................................................................3

    1 SCHEMATIC DIAGRAMS ............................................................................................4

    1.1 Wiring diagram.....................................................................................................4

    1.1.1

    Hints for the design of wiring diagrams ............................................................7

    1.2

    Single line diagram ............................................................................................13

    1.3 Complete circuit diagram ...................................................................................14

    1.4 Lay-out diagram .................................................................................................15

    1.5

    Equipment diagram............................................................................................15

    1.6

    Terminal table ....................................................................................................16

    2 TYPES OF CIRCUIT CONSTRUCTION ....................................................................17

    3

    WIRING OF CIRCUITS ..............................................................................................18

    4 ENVIRONMENTAL EFFECTS ...................................................................................19

    4.1.

    Protection against climatic influences ................................................................19

    4.2. Protection against vermin ..................................................................................19

    4.3.

    Protection against corrosion ..............................................................................19

    5 FAULT FINDING ........................................................................................................ 20

    5.1. Tips for remedying faults....................................................................................20

    6

    SUMMARY OF SWITCHING SYMBOLS ...................................................................24

    7 IDENTIFICATION LETTERS FOR GENERAL FUNCTIONS .....................................33

    8

    GLOSSARY OF ELECTRICAL TERMS.....................................................................35

    8.1. Definition of characteristic quantities .................................................................35

    9

    OPERATING EQUIPMENT........................................................................................36

    9.1. Designation of operating equipment ..................................................................36

    9.1.1. Designation block "type, number, function"................................................36

    9.1.2. Designation block "plant" ...........................................................................37

    9.1.3.

    Designation block "location".......................................................................37

    9.1.4.

    Designation block "connection"..................................................................38

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    4/47

    3

    ELECTRICAL CONTROL 2

    LEARNING OBJECTIVES

    name and describe schematic diagrams.

    draw wiring diagrams complying with standards.

    recognize switching symbols and design simple contactor circuits.

    state the difference between wiring diagram and complete circuit diagram.

    produce a terminal table.

    list the types of wiring.

    recognize and find minor faults.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    5/47

    4

    ELECTRICAL CONTROL 2

    1 SCHEMATIC DIAGRAMS

    These are used to represent electrical devices by means of symbols. Operating

    equipment can be shown in a simplified form.

    Schematic diagrams always show the equipment de-energized, in the mechanically non-

    activated condition.

    1.1 Wiring diagram

    This is the most frequently used representation of a circuit in electrical engineering.

    The current paths should be drawn in straight lines, as far as possible, and without

    crossovers.

    The spatial position and mechanical interconnection of individual parts are not taken into

    account.

    The wiring diagram should show the method of operation and switching sequence of a

    control system clearly and unambiguously.

    The magnet coils (contactor coils) should be arranged in such a way that one terminal is

    directly connected to the neutral line of the control circuit. The input to the coil is

    connected to the other control line via various switching elements (contacts) of the

    switchgear (pushbuttons, overcurrent relays etc.).

    All contacts operated by one contactor have the same designation as the contactor itself.

    Terminals are shown, and are given the same numbers as on the terminal table and the

    circuit diagram.

    For large circuits it is recommended that the wiring diagram should be divided into current

    paths.

    The equipment diagram of switchgear can be shown below the current path (as shown on

    page 8).

    The switch contact types, whether they are normally closed or open, the section in which

    they are found and whether any of the contacts are free.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    6/47

    5

    Each piece of equipment is lettered to indicate its type. 1f here are several items of the

    same type of equipment, they are given consecutive numbers. A further letter indicates its

    general function, e.g., K 2 A auxiliary contactor and K 4 M main contactor (motor

    contactor).

    a) Main circuit wiring diagram

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    7/47

    6

    b) Control circuit wiring diagram

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    8/47

    7

    1.1.1 Hints for the design of wiring diagrams

    When designing a wiring diagram, the following points should be observed.

    a) The current paths are drawn vertically, in between the horizontally drawn bus bars.

    b) Switching appliances, switchgear and initiating equipment must be drawn at right

    angles to the current path.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    9/47

    8

    c) The direction of the current flow should always be from top to bottom.

    d) Crossover of lines should be avoided.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    10/47

    9

    e) Apparatus and equipment must be represented in zero volt condition (switched off).

    Exceptions have to be clearly indicated (i.e. arrow).

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    11/47

    10

    f) Control equipment e.g. coils, signal lamps must be connected directly to the neutral

    conductor, or in case of an earthed supply system, to the potential earth neutral (PEN)

    conductor.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    12/47

    11

    g) Current paths must be numbered consecutively, circuit elements must be placed from

    left to right, depending on their sequence of operation. Circuit elements must be

    provided with code letters and consecutive numbers.

    For clean representation of the various circuit elements, a table can be added below

    the wiring diagram.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    13/47

    12

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    14/47

    13

    1.2 Single line diagram

    This is a simplified, single-phase representation of the circuit.

    F1 = motor fuses

    F2 = overcurrent relay

    K1 = motor contractor

    M1 = 3-phase AC motor

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    15/47

    14

    1.3 Complete circuit diagram

    This is the representation of a circuit in all its details.

    As both main and control circuits appear in one diagram, this can become unwieldy and

    makes fault finding more difficult.

    F1 = motor fuses K1 = motor contractor

    F2 = overcurrent relay M1 = 3-phase AC motor

    F3 = control fuses S1 = ON-OFF-pushbutton

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    16/47

    15

    1.4 Lay-out diagram

    This is a document for wiring up the components. All equipment is shown in the correct

    position.

    1.5 Equipment diagram

    This gives information on electrical switchgear (contactors, controllers, and master

    switches etc.), but not on its construction. The switch positions and contacts must havethe same designation on the wiring diagram.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    17/47

    16

    1.6 Terminal table

    The terminals shown in the wiring diagram and complete circuit diagram are compiled in

    the terminal table into terminal strips. The terminal table contains the cable or wire

    numbers, the terminal number, the origin and the destination.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    18/47

    17

    2 TYPES OF CIRCUIT CONSTRUCTION

    Small circuits are built up on boards and are installed in the places provided on the

    machines, e.g., star-delta starter circuit.

    Cubicles are fixed directly to the machine and contain all control and switching devices.

    Freestanding cubicles for large machine tool controls contain e.g. measuring equipment,

    switching devices and control devices.

    Freestanding contactor boards are used for extensive electrical plants, e.g., rolling mills

    and cranes etc.

    Contactor boards are erected separately in the switchgear rooms provided.

    Control desks contain all the Instruments and control devices on one board, in order to be

    able to control a plant from a central position.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    19/47

    18

    3 WIRING OF CIRCUITS

    Wiring in ducts:

    This is affected by laying wired in plastic ducts. Note:

    Always make the ducts large enough.

    Back-panel wiring:

    Wires are connected on the back of panels.

    Note:

    When wiring is taken through a panel, grommets should be used, otherwise the wiring

    insulation will be damaged.

    Flat wiring:Individual wires are laid next to and above one another in layers.

    Round bundle wiring:

    Bundles of wires are bunched with string or held together by tapes.

    Laced wiring harness:

    This is a preformed and tied bundle of wires.

    Quick wiring:

    The wires are laid from terminal to terminal (by the shortest path).

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    20/47

    19

    4 ENVIRONMENTAL EFFECTS

    4.1. Protection against climatic influences

    The required control devices may be affected by local conditions. This means that the

    prevalent climatic conditions have to be taken into consideration in advance.

    The control devices have to work satisfactorily in temperate and dry climates, as well as in

    hot climates with high air humidity. If water condenses in a control cubicle due to frequent

    temperature changes at high air humidity (changing climate), then control devices will not

    function properly. Heaters may be employed to ensure that water is not deposited in the

    equipment.

    4.2. Protection against vermin

    Control devices may suffer adverse effects from vermin (e.g. termites). Components made

    of materials containing cellulose should be avoided in electrical operating areas, and a

    high degree of cleanliness and brightness of illumination should be ensured. It is useful to

    employ encapsulated equipment in areas likely to be affected by vermin.

    4.3. Protection against corrosion

    There is a corrosive atmosphere in many plants due to the manufacturing processes e.g.

    in chemical and electroplating works and steelworks etc.

    The following information may serve as a rough guide:

    In atmospheres in which human beings can exist, normal encapsulation of equipment will

    provide resistance to corrosion.

    Metal parts used as contacts must be suitable for the constructional and switching load

    requirements. They are male of precious metals or appropriate alloys.

    The above considerations do not only apply for contactors and switchgear, but for all

    electrical machines and electrical installations.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    21/47

    20

    5 FAULT FINDING

    For rated voltages above 42 V up to a voltage of 250 V to earth, work on live parts is only

    permitted, if, in order to prevent danger or for other important reasons, it is impossible to

    make those parts of the plant dead, on which work is to be carried out. Such work may

    only be carried out by an "expert". An expert is one who can judge and recognize possible

    dangers based on his technical training, knowledge and experience as well as his

    knowledge of the appropriate regulations applying to the work entrusted to him.

    Electricians with completed electro-technical engineering training fulfil these conditions.

    Note:

    Under no circumstances may apprentices work on live parts of a plant.

    5.1. Tips for remedying faults

    This table includes the faults which occur most frequently on contactors.

    CAUSE REMEDY

    Contactor does not switch on:

    Control fuse burnt out. Fist remove cause of short circuit, then

    replace the fuse.

    Thermal overload relay has operated Wait for cooling period, press reset button.

    Switch on again.

    Coil defective Replace coil

    Coil for wrong voltage, wrong

    frequency or wrongly connected.

    Replace coil. Change the circuit.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    22/47

    21

    Low voltage (permitted lower limit

    0.85 x UC) particularly for DC operated

    contactors.

    Replace coil, use special coil for increased

    voltage security

    (0.75 x UC). Provide stable mains supply.

    Low voltage 214 V. Note the voltage drop. If necessary, choose

    higher control voltage.

    Circuit errors. Look for and remove the cause. Go

    through the wiring diagram step by step.

    By-pass normally closed contacts in circuit,

    one by one.

    Broken wire. Pull the wires to check whether they are

    broken inside the insulation. Frequently the

    break in the wire, caused by incorrect

    removal of the insulation, is inside the

    insulation.

    Contactor with thermal overcurrent device

    trips

    Thermal overcurrent trip not operating

    correctly

    Set trip to motor operating current. Note

    that, in the delivered condition, the trip is

    always set to the lowest current value.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    23/47

    22

    Long starting time due to starting against

    the load, too low voltage.

    Install thermal overcurrent

    trip with saturation transformer. During start

    up the load should be switched off

    (coupling) so that rotary Pumps should not

    be started against a closed gate valve.

    Measure voltage at motor terminals.

    Check cross section of wires (possibly

    voltage drop). Thermal trips are by passed

    during starting period.

    Too high switching frequency. Use thermistor protection. Thermal

    overload trips are only suitable up to 15

    operations/ hour.

    Bimetal strip has turned blue or burnt out;

    overload due to too high current; short

    circuit with wrong (too high) fuse ratings.

    Change overload trip. Install fuses suitable

    for overload trip.

    Loss of one-phase (motor does not start - it

    hums).

    Possibly a burnt-out fuse, loose or broken

    main connection to motor winding.

    Contactor does not switch off

    Contactor contacts welded together. Break the contacts apart and replace them.

    Install bigger type of contactor.

    The control wires between contactor and

    operating device is too long (holds itself in

    due to capacitive currents).

    Lower the control voltage. Install contactor

    with smaller holding capacity.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    24/47

    23

    Stop push Button is short circuited. Remove short circuit, break the contacts

    apart, if necessary, and renew them.

    Faulty star-delta circuit switching. Use timing relay with changeover time .of

    40 - 100 s. Set timing relay to longer time

    period. The motor must nearly reach the

    nominal speed in the star circuit.

    Contactor flutters. Ensure that the operating signal is correct.

    Remove fault on operating elements.

    Check rated voltage of the contactor coil.

    Contactor hums

    Coil of wrong voltage or wrong frequency. Replace coil.

    Magnet surfaces dirty or corroded (after

    long period of shutdown).

    Clean magnet surfaces. Do not file, do not

    grease them.

    Short circuiting ring broken. Replace contactor.

    Foreign bodies in air gap. Switch on and off several times.

    Remove foreign bodies.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    25/47

    24

    6 SUMMARY OF SWITCHING SYMBOLS

    Contacts with two or three positions Description

    Symbol Description

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    26/47

    25

    Wiring contacts with two positions

    Leading and lagging contacts

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    27/47

    26

    Contacts showing delay in actuation and resetting

    Contacts with automatic and non-automatic resetting

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    28/47

    27

    Switches

    Symbols Description

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    29/47

    28

    Switches, which are actuated by pushing or pulling, normally have an inherent reset force.

    It is therefore not necessary to draw the symbol for automatic reset.

    In exceptional cases, where switches have latching qualities, the symbol for latching is to

    be used.

    Switchgear

    Symbol Description

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    30/47

    29

    Electromechanical and electromagnetic drives

    Symbol Description

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    31/47

    30

    Fused and fuse switches

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    32/47

    31

    Electrical machines and transformers

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    33/47

    32

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    34/47

    33

    7 IDENTIFICATION LETTERS FOR GENERAL FUNCTIONS

    Letter General function

    A Auxiliary function

    BDirection of movement (forwards, backwards, raising, lowering,

    clockwise, anticlockwise)

    C Counting

    D Differentiation

    E ---

    F Protection

    G Test

    H Alarm

    J IntegrationK Pushbutton operation

    L ---

    M Main function

    N Measurement

    P Proportional

    Q Condition (start, stop, limits)

    R Reset, cancel

    S Storage, indication

    T Time measurement, time delay

    U ---

    V Speed (acceleration, braking)

    W Addition

    X Multiplication

    Y Analogue

    Z Digital

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    35/47

    34

    For example:

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    36/47

    35

    8 GLOSSARY OF ELECTRICAL TERMS

    8.1. Definition of characteristic quantities

    Rated insulation voltage

    Uiis the standardised value of voltage for which the insulation is suitable.

    Rated voltage (rated operating voltage)

    Ueis the reference voltage for switching.

    Continuous current (thermal rated current)

    Ith2is the current which the switchgear can carry for an unlimited period of time in normaloperating conditions, without the controls having to be cleaned and without the limiting

    maximum temperatures being exceeded.

    Rated operating current

    Ieis the current reached in normal operation

    Mechanical life span

    The mechanical life span in expressed by the number of switching cycles possible under

    no-load condition.

    Life span of switching contacts

    The life span of switching contacts is determined by the number of switching cycles which

    can be achieved under full load conditions.

    Frequency of switching

    Frequency of switching is the number of switching operations (number of switching cycles)

    per hour.

    Rated actuating voltage UC

    Control voltage is the voltage for which the coil or the tripping mechanism is suitable. It is

    also called the coil rated voltage.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    37/47

    36

    9 OPERATING EQUIPMENT

    9.1. Designation of operating equipment

    The complete system of designation contains four blocks. Each block has a prefix for

    designation.

    Prefix Information in identification block

    - Type of operating equipment Consecutive number Function

    = Plant

    + Location

    : Connection

    The four designation blocks can be arranged in any sequence. i.e.:

    : A 1 = B4 + D1 K 3 A

    or

    - K 3 A + D1 = B4 : A1

    For small units it is sufficient to quote one or two designation blocks. Normally only the

    designation block "Type of operating equipment - consecutive number - function" is used,

    so that the prefix can be omitted.

    i.e.: instead of - K 3 A only K 3 A

    9.1.1. Designation block "type, number, function"

    For the designation of "type" an identification letter from the table "identification letters for

    type of equipment" must be used.

    The consecutive number is obligatory, and must always be stated. In some cases the

    number alone might be sufficient to designate operating equipment.

    The function relative to other operating equipment is indicated by a letter from the table

    "identification letters for general functions".

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    38/47

    37

    The designation of the function may be omitted if is not required. However it is not

    permitted to use the designation "function" by itself.

    9.1.2. Designation block "plant"

    The designation "plant" is written down only once in a suitable place on the switching

    document. The designation of the plant may be omitted if not required.

    9.1.3. Designation block "location"

    The designation "location" states, where the operating equipment is located. The

    designation of location may be omitted if not required.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    39/47

    38

    9.1.4. Designation block "connection"

    The designation "connection" has a colon as prefix. The designation of connection may be

    omitted if not required.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    40/47

    39

    Examples of block combinations

    Designation Block combination Explanation

    = C 1 -K 5 A

    = Plant

    - Type, consecutive

    number, function

    Auxiliary contactor K 5 in plant C 1

    + L 2 : 3+ Location

    : ConnectionTerminal 3 of component L 2

    = B 2 + 2 D 4 = Plant

    + Location

    4th component of control panel 2 on

    floor D of plant B 2

    - K 2 M. : 11

    - Type, consecutive

    number, function

    : Connection

    Terminal 11 of main contactor K 2

    = B 3 B + D = Q

    = Plant

    + Location

    - Type, number, function

    Circuit breaker Q of panel D, Plant B

    3 B

    + A 2 - S 10 : 4

    + Location

    - Type, number,

    function

    : Connection

    Terminal 4 of push button S 10 on

    control desk A 2

    : A 1 = B 4+ D 1 - K 3 A

    : Connection

    = Plant

    + Location

    - Type, number, function

    Terminal A 1 of

    auxiliary contactor K 3, control panel

    D 1, plant B 4

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    41/47

    40

    EE 015

    Electrical Control 2

    Theoretical Test

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    42/47

    41

    ELECTRICAL CONTROL 2

    TEST 1

    1. Explain the purpose of schematic diagrams.

    2. Name the six different types of schematic diagrams.

    3. Draw an equipment diagram for a contactor with three main contacts and four auxiliary

    contacts (two normally closed and two normally open contacts).

    4. What information is provided by a terminal table?

    5. State how back panel wiring is carried out.

    6. What is the purpose of a control desk?

    7. State what is meant by the term "laced wiring harness".

    8. The contactor of a switching circuit "hums". Name possible sources of error.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    43/47

    42

    ELECTRICAL CONTROL 2

    TEST 2

    1. State four points which have to be observed when designing a wiring diagram.

    2. Describe the design of a complete circuit diagram.

    3. Describe the term "flat wiring".

    4. Draw an equipment diagram for a contactor with three main contacts and two auxiliary

    contacts (one normally closed and one normally open).

    5. Explain the term "frequency of switching" of a contactor.

    6. Name the two main parts of a wiring diagram.

    7. Trouble shooting in control circuits must be carried out by experts only. Which persons

    qualify under the stipulation of operating instructions for the term "expert"?

    8. The contactor of a switching circuit "flutters". Name possible sources of error.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    44/47

    43

    ELECTRICAL CONTROL 2

    TEST 1

    (Solution)

    1. Representation of electrical installations through switching symbols. Simple

    representation of operational equipment.

    Schematic diagrams always show the equipment in a de-energized state, i.e. in the

    mechanically non-activated condition.

    2. Wiring-, single-line-, complete circuit-, lay out-, equipment diagram and terminal table.

    3.

    4. Cable or wire number, terminal number, the origin and the destination.

    5. Wires are connected on the back of panels. Always use grommets through the panel.

    6. All instruments and control equipment assembled on one panel for purpose of

    controlling a plant from one central place.

    7. This is a preformed and tied bundle of wires.

    8. Coil on wrong voltage or frequency; dirt on the mating faces of the magnetic core;

    short circuiting ring broken; foreign body in the air gap.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    45/47

    44

    ELECTRICAL CONTROL 2

    TEST 2

    (Solution)

    1. The current paths are drawn vertically in between the horizontally drawn bus bars.

    Circuit elements must be drawn at right angles to the current path.

    The direction of current flow should always be from top to bottom. Crossovers of lines

    should be avoided.

    Circuit elements must be represented in zero volt condition (switched off).

    Control equipment such as coils, signal lamps etc. must be connected directly to the

    neutral conductor.

    Current paths must be numbered consecutively, circuit elements must be provided

    with code letters and consecutive numbers.

    2. The complete circuit diagram is the representation of a circuit in all its details.

    If the main and control circuits appear in one diagram, it can become unwieldy and

    makes fault finding more difficult.

    3. Individual wires are laid next to end above one another in layers.

    4.

    5. The number of switching cycles per hour.

    6. Main circuit and control wiring diagrams.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    46/47

    45

    7. An expert is one who can judge and recognize possible dangers, based on his

    technical training, knowledge and experience as well as his knowledge of the

    appropriate regulations applying to the work entrusted to him. Electricians with

    completed electro-technical engineering training fulfil these conditions.

    8. The operating signal is not correct. Fault on the operating elements. Contactor coil

    voltage is incorrect.

  • 7/25/2019 EE015-Electrical Control 2-Th-Inst.pdf

    47/47

    KEY TO EVALUATION

    PER CENT MARK

    88 100 1

    75 87 2

    62 74 3

    50 61 4

    0 49 5


Recommended