technical data Condensing unit ERAP110-170MBY EEDEN09-410 Applied Systems
Transcript
Page 1: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

technical data

Condensing unit

ERAP110-170MBY

EEDEN09-410

Applied System

s

Page 2: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

technical data

Condensing unit

ERAP110-170MBY

EEDEN09-410

Applied System

s

Page 3: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Chillers • R-407C • ERAP-MBY

• Applied Systems • Chillers4

Chille Applie ERAP-MB R-407C

Cooling only

Heating only

Heat pump

Page 4: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Applied Systems • Chillers 5

• Chillers • R-407C • ERAP-MBY

TABLE OF CONTENTSERAP-MBY

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2 Specification text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

4 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

5 Control systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

6 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Cooling capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Capacity correction factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

7 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 15Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

8 Piping diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

9 Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

10 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Sound power spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

11 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Fixation and foundation of units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Water charge, flow and quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

12 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Page 5: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Chillers • R-407C • ERAP-MBY

• Applied Systems • Chillers6

1 Features

11

Chillers Applied Sys ERAP-MBY R-407C • All models are PED pressure vessel approved

• Daikin semi-hermetic single screw stepless compressor

• Optimised for use with R-407C

• Advanced pCO² DDC controller

• Standard operation range down to -15°C ambient

• High quality, anti-corrosion treated components as standard

• Reverse phase protection as standard

• Moisture indicator as standard

• Low operating sound level - extra low noise option available

• DICN (Daikin Integrated Chiller Network) operation as standard within same series

• Evaporating temperature down to -15°C

• Hi-esp fans (up to 150Pa) available as option

• Inverter fans available as option

• Nitrogen holding charge

• Stepless or infinitely variable capacity control from 30 to 100%

Page 6: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Applied Systems • Chillers 7

• Chillers • R-407C • ERAP-MBY

2 Specification text

3

12

Unit construction

Compact, modular and weatherproof design air-cooled chiller for outdoor installation IP24 – manufactured according to the ISO 9001 quality standard. The range has been designed for both air conditioning and process cooling applications and meets PED conformity. The use of state-of-the-art technologies and high quality materials ensures efficiency, reliability and an extended service life. Each DAIKIN chiller is factory run tested prior to shipping.

Casing / Colour

Powder coated, galvanised steel plate. Fully factory assembled on a base frame. Colour ivory white (Munsell code 5Y7.5/1) or RAL equivalent silky grey (+-RAL7044) Number of refrigerant circuits

Size 110-170 single circuit.

Compressor

New, semi-hermetically sealed DAIKIN stepless single screw compressor developed and optimised for refrigerant R407c.

The single screw principle of a main screw meshing with 2 satellite rotors eliminates radial and axial bearing loads due to balanced pressures under all operating conditions. Bearings are designed for over 100,000 operating hours or equivalent to the full service life of the compressor.

The main screw is directly driven by a suction cooled 2 pole, 3 Phase induction motor and is cooled by refrigerant injection. Satellite rotors are made from a hard wearing polymer material eliminating metal to metal contact allowing closer tolerances and increasing running life. At 2880rpm and 12 compressions per rotation the 34,560 compressions per minute prevents pulsating compression gas and resembles a smooth discharge flow, thereby reducing vibration and noise emission. In addition the twin wall structure of the compressor casing together with the integrated oil separator offers additional attenuation.

Stepless control of the sliding vane determines the volumetric ratio of the compressor in function of the chilled water temperature. Control is infinitely variable from 30 to 100%.

Additional features include: integrated oil separator incorporating muffler effect, oil lubrication by pressure difference (no oil pump required), oil sump heating, oil inspection glass, non-return valve, hot gas shut-off valve, service valves, suction gas filter, Klixon embedded in the motor winding, star or delta start up.

The high efficiency design is optimised for the refrigerant and system and ensures the highest EER values and operational reliability. System and service costs are minimised.

Condenser

High-performance design Cu/Alu heat exchanger – arranged in a V- shape. Consisting of internally drawn helical Cu pipe (Hi -X) guaranteeing excellent heat transmission and optimal oil return. An integrated subcooler further improves performance. By increasing the heat transmission surface using continuous laminated honeycomb slotted flaps, a very low sound level is attained still with compact dimensions. The aluminium fins are precoated with Polyacryl to offer additional protection against corrosion thereby extending the range of applications of this device.

Fans

Directly driven, low-noise axial fans with outlet protective grating. Statically and dynamically balanced drive motor design with maintenance-free bearings for outdoor installation. Motor safety class IP 54.

Refrigerant Piping

Consisting of Cu pipe with all the necessary cooling fittings such as:

Service valves, filter-drier, inspection glass with moisture indicator, solenoid valve and TEV with external pressure equalisation. The refrigerant circuit is subject to factory pressure and leak testing, is cleaned, dried, evacuated and supplied with refrigerant R-407C and filled with oil ready for operation.

Safety and control devices

Permanent temperature and pressure monitoring of the refrigerant circuits by the PCO2 digital controller using high- and low-pressure sensors. Each refrigerant circuit is fitted with the following safeties: Pressure limitation control / safety pressure limitation control, drain valve, low-pressure switch, hot gas temperature monitoring, overheat cut-out for compressor and fan motors and overload relay.

Each refrigerant circuit is fitted with the following control devices: Electronic temperature monitoring, phase-sequence relay, high- and low-pressure PCO2

digital controller display, timing safety device and switch frequency limiter.

Page 7: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Chillers • R-407C • ERAP-MBY

• Applied Systems • Chillers8

2 Specification text

12

Switching and control device

In addition to the fully automated PCO2 digital controller, the control cabinet manufactured by SIEMENS in accordance with the valid EN directives (CE) fulfils safety class IP 54 and contains all the required switching and control components such as: load, auxiliary and control cut-outs, transformers, control fuses, relay and auxiliary relay, sensors, control PCBs and PCO2 digital controller.

The electronics have an automatic restart after power failure and provide the following digital inputs and outputs hard-wired to terminals for incorporating the GLT:

Digital inputs: Digital outputs:

*Remote On Off / dual set point / power limitation 1-2-3-4

PCO2 digital controller

The ERAP-MB units are fitted with a PCO2 digital controller, which allows the user to configure, operate and service the unit in a user-friendly manner. The controller consists of an alphanumerical display (LCD 4x20), 6 control keys and 6 LEDs.

The following functions are supported by the electronics, amongst other things:

- Allocation of the set point and the desired switching hysteresis

- Air temperature control using field installed sensor

- Adaptive control functions

- Various timer – date functions (Schedule –Timer)

-User display of current operating parameters such as temps, pressures, ect…

- Recording operating hours

- Automatic restart after power failure

- Service history of the last 20 alarms

- 5 languages can be freely selected (German, English, French, Italian, Spanish)

- Password protection

As an option this condenser can be fitted with an interface for integrating it into a Building Management System (BMS), which either supports the MODbus / J-bus or BACnet protocol.

Page 8: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Applied Systems • Chillers 9

• Chillers • R-407C • ERAP-MBY

3 Specifications

3

13

3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY

Capacity (Eurovent)

Cooling Nominal kW 114.00 150.00 171.00

Capacity Steps % 30-100Nominal input (Eurovent)

Cooling kW 42.10 52.40 65.20

EER 2.71 2.86 2.62Casing Colour Ivory white/Munsell code 5Y7.5/1

Material Polyester coated galvanised steelDimensions Unit Height mm 2250 2250 2250

Width mm 2346 2346 2346Depth mm 2238 2238 2238

Weight Unit kg 1326 1440 1516Air heat exchanger

Type Cross fin coil/Hi-X tubes and PE coated waffle louvre finsRows 2 3 3Stages 48+2Fin Pitch mm 2.00 2.00 2.00Face Area m² 8.40 8.40 8.40

Fan Drive Direct driveNominal air flow m³/min 960 960 960Model Quantity 4 4 4

Speed rpm 730 900 900Motor Output

W 550 1020 1020

Discharge direction VerticalCompressor Type Semi-hermetic single screw compressor

Refrigerant oil type Daphne FVC68DRefrigerant oil charge l 5.5 5.5 7.5Model Quantity 1 1 1

Model ZHC3LTGUYE ZHC3WLGUYE ZHC5LMGUYESpeed rpm 2880 2880 2880Crankcase Heater

W 150 150 150

Sound level Sound Power Cooling dBA 89 94 94Refrigerant circuit

Refrigerant type R-407CRefrigerant charge kg 5.5 5.5 7.5No of circuits 1 1 1

Piping connections

Suction line connection 2’’ 1/8Liquid line connection 7/8’’

Safety Devices Double PED approved high pressure switchesLow pressure protection

Pressure relief valveCompressor motor thermal protectorCompressor motor overcurrent relay

Discharge temperature protectorRecycling and guard timerReverse phase protector

Notes Cooling capacity / Power input conditions: Ambient 35°C; Suction dewpoint = 5°C; Superheat = 10°C

Page 9: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Chillers • R-407C • ERAP-MBY

• Applied Systems • Chillers10

3 Specifications

13

3-2 ELECTRICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY

Power Supply Name Y1Phase 3~Frequency Hz 50 50 50Voltage V 400 400 400Voltage Tolerance

Minimum % -10%Maximum % +10%

Unit Starting Current A 158 193 248Nominal Running Current Cooling

A 70.00 84.00 104.00

Maximum Running Current A 95.00 120.00 135.00Recommended fuses according to IEC standard 269-2

3x125gL 3x160gL 3x160gL

Fan Quantity 4 4 4Nominal Running Current Cooling

A 1.90 3.10 3.10

Maximum Running Current A 1.90 3.10 3.10Compressor Phase 3~

Voltage V 400 400 400Voltage Tolerance

Minimum % -10%Maximum % +10%

Starting current A 158.0 193.0 248.0Nominal running current (RLA)

A 62.00 70.00 90.00

Maximum Running Current A 87.00 106.00 121.00Starting Method Star-delta

Control Circuit Phase 1~Voltage V 230V/24V AC (supplied by factory installed performers)Recommended fuses Factory installedLiquid line solenoid valves (Y15..16S/Y25..26S)

2x(16.1VA-70mA) inrush current=130mA

Capacity solenoid valves (Y11..14S/Y21..Y24S)

1x(16.1VA-70mA) inrush current=130mA

Page 10: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Applied Systems • Chillers 11

• Chillers • R-407C • ERAP-MBY

4 Options

3

14

Num

ber

Desc

riptio

nUn

itsiz

eAv

aila

bilit

y

110

150

170

Stand

ardun

itV

VV

OPHF

Optio

nhigh

fans

VV

V

Com

plet

ely

com

bina

ble

optio

ns

OP03

Dual

pressu

rerel

iefval

veon

theco

nden

serV

(s)V

(s)V

(s)Fac

torym

ounte

d

OP12

Suctio

nstop

valve

stdstd

stdFac

torym

ounte

d

OP52

Main

isolat

orsw

itchV

VV

Factor

ymou

nted

OP57

A-me

ter,V

-mete

rV

VV

Factor

ymou

nted

OPLN

Low

noise

opera

tion

VV

VFac

torym

ounte

d

OPCG

Cond

enser

protec

tiong

rilles

VV

VFac

torym

ounte

d

Avai

labl

eki

ts

EKAC

200A

BMSc

ardV

VV

Kit

EKBM

SMBA

BMSg

atewa

ymod

bus/

j-bus

protoc

olV

VV

Kit

EKBM

SBNA

BMSg

atewa

ybacn

etpro

tocol

VV

VKit

EKRU

PCRe

mote

userin

terfac

eV

VV

Kit

3TW

5647

9-3A

Not

esV

Ava

ilabl

e

std

stan

dard

onun

it

(s)

optio

nre

quire

dfo

rSw

edish

natio

nall

awSN

FS19

92:1

6

1To

inst

allE

KBM

SBN

A,E

KBM

SMBA

→EK

AC2

00A

need

sto

bein

stal

led

onth

eun

it.

Page 11: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Chillers • R-407C • ERAP-MBY

• Applied Systems • Chillers12

5 Control systems

15

Digital controller

The digital controller consists of an alphanumeric display, labelledkeys which you can press and a number of LEDs.

Digital built-in controller

Figure - Digital built-in controller

f Key, to enter the main menu

J Key, to start up or to shut down the unit.

p Key, to enter the safeties menu or to reset analarm.

g Keys, to scroll up or down through the screensof a menu (only in case v, B or Aappears) or to raise, respectively lower a setting.h

K Key, to confirm a selection or a setting.

K Key, to confirm a selection or a setting.

s Key, has no effect on ERAP units

a Key, to enter the readout menu.

z Key, to enter the user settings menu.

e Key, to enter the timers menu.

r Key, to enter the history menu.

t Key, to enter the info menu.

y Key, to enter the input/output status menu.

a Key, to enter the user password menu.

d Key, has no effect on ERAP units

i Key, has no effect on ERAP units

Note:

– Temperature readout tolerance: ±1°C.– Legibility of the alphanumeric display may decrease in direct

sunlight.

Connection of a remote digital controller to the unit

For a remote digital controller a cable length of up to 600 metresbetween the remote digital controller and the unit is allowed.This gives the opportunity to control the unit from a considerable distance. Refer to''Cable for remote digital controller'' in the installation manual for cable specifications.

Digital remote controller (to be ordered separately)

Figure - Digital remote controller

J Key, to start up or to shut down the unit.

p Key, to enter the safeties menu or to resetan alarm.

kKey, to scroll through the screens of a menu(only in case v , A or B appears) or toraise, respectively lower a setting.

Page 12: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Applied Systems • Chillers 13

• Chillers • R-407C • ERAP-MBY

6 Capacity tables6 - 1 Cooling capacity tables

3

16

AMBIENTTEMPERATURE (°C)

15 20 25 30 35 40 43

SDP (°C) MODEL CC PI CC PI CC PI CC PI CC PI CC PI CC PI

3TW56472-1

SYMBOLSCC : Cooling capacity (kW)

PI : Total power input = compressor + fans + control circuit (kW)

SDP : Suction dew point

NOTESConditions according EN13215Superheat = 10°CSubcool = 5°C

Out of operating range

Page 13: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Chillers • R-407C • ERAP-MBY

• Applied Systems • Chillers14

6 Capacity tables6 - 2 Capacity correction factor

16

4TW50689-8

CORRECTION FACTOR FOR GLYCOL

Ethylene glycolPropylene glycol

Legend

Correction on cooling capacityCorrection on power inputCorrection on flow rateCorrection on pressure drop

Glycol

Required glycol concentration

Type Concentration (wt%) 0 10 20 30 40

Ethylene glycolFreezing point °C 0 -4 -9 -16 -23Minimum LWE °C 4 2 0 -5 -11

Propylene glycolFreezing point °C 0 -3 -7 -13 -22Minimum LWE °C 4 3 -2 -4 -10

Page 14: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Applied Systems • Chillers 15

• Chillers • R-407C • ERAP-MBY

7 Dimensional drawing & centre of gravity7 - 1 Dimensional drawing

3

17

3TW54374-1A

ERAP110-170MBY

Air Air

Required space around theunit for service and airintake

4 x Hole for fixation J20

Center of gravity

Air Air Air Air

1 Condensor

2 Compressor

3 Discharge stop valve

4 Liquid stop valve

5 Suction stop valve (optional)

6 Suction line

7 Liquid line

8 Drier + charge valve

9 Power supply intake

10 Emergency stop

11 Switchbox

12 Digital display controller

13 Transport beam

14 Ambient temperature sensor

15 Field wiring intake

16 Main isolator switch (optional)

Page 15: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Chillers • R-407C • ERAP-MBY

• Applied Systems • Chillers16

8 Piping diagram

18

3TW56475-1

ERAP110-170MBY

M11-14F Fan motorM1C Compressor motor 1S1HP High pressure switchS14HP High pressure switchS3T Discharge temperature controllerR5T Ambient temperature sensorB1P Low pressure transmitterB2P High pressure transmitterY11S Unloader solenoid valveY15S Liquid injection solenoid valveY16S Liquid line solenoid valve

O Check valve

L Flare connection

M Screw connection

N Flange connection

Z Pinched pipe

P Spinned pipe

Service port

Condenser

Strainer

Drier + chargevalve

Suction stop valve

Gauge port Gauge port

Service port

2. Dual pressure relief valve(OP03)

Liquid stop valve

Safety valves

Safety valve

1. STD

1or2

Page 16: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling
Page 17: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Chillers • R-407C • ERAP-MBY

• Applied Systems • Chillers18

9 Wiring diagram9 - 1 Wiring diagram

19

0TW56476-1A

J2 (B1-VDC): High pressure C1J2 (B2-VDC): Low pressure C1J2 (B3-VDC): Changeable Al 1J3 (B4-BC4): - -J3 (B5-BC5): Thermostat sensorJ6 (B6-GND): AmbientJ6 (B7-VDC): Capacity feedback ofC1J6 (B8-VDC): - -

Digital input

J5 (ID1-IDC1): High pressure switchC1J5 (ID2-IDC1): Reverse phase protector C1J5 (ID3-IDC1): Overcurrent relay C1J5 (ID4-IDC1): Discharge thermal protector C1J5 (ID5-IDC1): Compressor thermal protector C1J5 (ID6-IDC1): Emergency stopJ5 (ID7-IDC1): Interlock air / water flowJ5 (ID8-IDC1): Changeable DI 1J7 (ID9-IDC9): Changeable DI 2J7 (ID10-IDC9): Changeable DI 3J7 (ID11-IDC9): Changeable DI 4J7 (ID12-IDC9): - -J8 (ID13-IDC13): - -J8 (ID14-IDC13): - -

J12 (C1-NO1): Compressor star C1J12 (C1-NO2): Compressor delta C1J12 (C1-NO3): Compressor ON C1J13 (C4-NO4): 12% C1J13 (C4-NO5): - -J13 (C4-NO6): - -J14 (C7-NO7): AlarmJ15 (C8-NO8): Air / water flowcontactJ16 (C9-NO9): Fanstep 1 of C1J16 (C9-NO10): Fanstep 2 of C1J16 (C9-NO11): Fanstep 3 of C1J17 (C12-NO12): Ch. DO1: Evaporator heatertapeJ18 (C13-NO13): Changeable DO2

J5 (ID8-IDC1):J7 (ID9-IDC9):J7 (ID10-IDC9):J7 (ID11-IDC9):Dual setpoint / Remote On/Offenable/disable capacity limitatiOverview of changeable digitaJ18 (C13-NO13):2nd evaporator pump / GenerOverview of changeable analoJ2 (B3-GND):Setp signal 0-1V/0-10V/0-20m

Digital outputs (relays)Analogue input

NOTES TO GO THROUGH BEFORE STARTING THE UNIT

(1) d L1,L2,L3: Main terminalsd 1-70: Terminals on main raild 71-88: Terminal on field raild U-Z: Main terminals in compressor switchboxd A-N: Other terminals in compressor switchbox

(2) = Earth wiring

(3)15z = Wire number 15

(4)15

= Terminal number 15

(5)B= Field supply

(6) = Option

(7) = Not mounted in switchbox

(8) = PCB board

(9) = Connection continues on field ’F1’

(10) j1 = Several wiring possibilities

Alar

m

Ope

ratio

nC1

Change

ablein

put1

Remote

start/s

top

Change

ablein

put2

Duals

etpoin

t

Standard fanFuses + overcurrent ERAP 110 ERAP 150 ERAP 170F1U,F2U,F3U 3x125gL 3x160gL 3x160gLF4U,F5U 2A 2A 2AF6B 4A 4A 4AF7B 2A aM 2A aM 2A aMF8U 2A 2A 2AF9B 1A T 1A T 1A TF12B 10A 16A 16AK17S 51 62 70

Power supply

Power supply3∼50Hz 400V

Power supply1∼50Hz 230V

(11) Input terminals for fieldwring

OBLIGATORY

Pumpcontact

Example: Configurable switchesfor remote function

(12) Output terminals for field wiringMaximum output current: Resistive: 2A, Inductive:2A/Cos Phi 0,4EXAMPLE

Contactor coil ev.Waterpump

- Recommended fuses gL/gG (aM also admitted) according to IECstandard 269-2(F1U, F2U, F3U = gL/gG, F4U, F5U = gL/gG) (14) OPTIONAL

N OP52 = Main isolator switchN OP57 = A-meter, V-meter

Top view of unit

Side view of unit

ERAP110∼170MBY

(13)

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

G

H

Change

ablein

put3

Enable

/disabl

ecap.

lim.1

Pump

conta

ct(=

gene

ralop

eratio

n,wi

thout

OPDIC

N)

Power supply

J1-G: 24 VacJ1-G0: Reference (GND)

RS485 connection

J11 - TX -:J11 - TX +:J11 - GND:

Overview of changeable dig

Change

ablein

put4

Enable

/disabl

ecap.

lim.2

Chan

geab

leD

O2

2nd

evap

orat

orpu

mp

Analogue output

(Converted to digital outputs = DO)J4 (VG0-Y1): Ctrl motor loadup C1J4 (VG0-Y2): Ctrl motor loaddownC1

Chan

geab

leA

I1Se

tpsig

nal0

-1V

Flowswitch

Switc

hbox

Page 18: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Applied Systems • Chillers 19

• Chillers • R-407C • ERAP-MBY

9 Wiring diagram9 - 1 Wiring diagram

3

19

Field supplyNot poss. as option Poss. as option

Obligatory # ##Not obligatory ∗ ∗∗

Y16S Liquid line solenoide valve circuit 1Y15S Liquid injection valve of the compressor circuit 1Y11S 12% capacity step for compressor circuit 1V1** V-meter for circuit 1TR2 Transfo supply controller + digital inputsTR1 Transfo control circuitTC01..TC02 Optocoupler (Analog to digital signal)S14PH High pressure switch circuit 1S13S ## Main isolator switchS9L # Contact that closes if the pump is workingS8L ∗ Flow switchS6S,S10S ∗S11S,S12S

Changeable switch for remote function (rem. start-stop, dual setpoint, enable/disable cap. lim.1/2/3/4)/ low noise

S5E Emergency stop push buttonS3T Discharge thermal protector circuit 1S1PH High pressure switch circuit 1R5T Sensor for ambient temperatureR4T Sensor for thermostatR1P Reverse phase protector circuit 1R1F Feedback resistance for circuit 1R1 Auxiliary resistance for feedbackQ1M Thermal protector compressor motor circuit 1Q11F-Q14F Thermal protectors fan motors circuit 1PE Main earth terminalM1S Stepless capacity ctrl for compressor circuit 1M1C Compressor motor circuit 1M11F-M14F Fan motors circuit 1K7A Auxiliary relay for safety High pressure circuit 1K3A Auxiliary relay for discharge thermal protector circuit 1K2A Auxiliary relay compressor thermal protector circuit 1K1A Auxiliary relay for safeties circuit 1K17S Overcurrent relay for circuit 1K9F Fan contactor for circuit 1K8F Fan contactor for circuit 1K7F Fan contactor for circuit 1K3M Star contactor for circuit 1K2M Delta contactor for circuit 1K1M Linecontactor for circuit 1J4 Analogue outputJ12,J13,J14,J15,J16,J17,J18 Digital output

J5,J7,J8 Digital inputJ2,J3,J6 Analogue inputJ11 RS485 connectionJ1 Power supplyH5P∗ Changeable outputH3P ∗ Indication lamp operation compressor 1H2P ∗ Indication lamp alarmH1P ∗ Indication lamp general operationF12B Fuse for fanmotors circuit 1F9B Fuse for secondary of TR2F8U Surge proof fuse for A1PF7B Fuse for secondary of TR1F6B Fuse for primary of TR1F4U,F5U # Fuses for evaporator heater circuit 1F1U,F2U,F3U # Main fusesE3H ∗ evaporator, condenser heater circuit 1E1HC Crankcase heater compressor circuit 1C1..C3 CapacitorB2P High pressure transmitter for circuit 1B1P Low pressure transmitter for circuit 1A1P PCB-controllerA1 ∗∗ Current transfo, A-meter for circuit 1

Offation 1/2/3/4ital outputs DO2:

eral operation / 100% Capacityalog input AI 1

0mA/4-20mA

Connections inside thecompressor switchbox 1

Component

Terminal incompressor-switchbox 1

Wirenumber in cable betweencompressor switchbox 1 and main

switchbox

Changeable input1 Changeableinput2

10 11 12 13 14 15 16

Changeableinput4

Changeableinput3

igital inputsDI 1-2-3-4:

(16) Connection between PCB and remote userterminal position of jumpers and dipswitches.In a DICN system only valid for the master unit.For the slave units see the installation manual.

Remote userterminal

ADDRESS = 2

DipswitchONOFF

ADDRESS = 1

DipswitchONOFF

(15)

Page 19: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Chillers • R-407C • ERAP-MBY

• Applied Systems • Chillers20

10 Sound data10 - 1 Sound power spectrum

110

STD - UnitsSound power Lw per Octave band (dB) Total (dBA)

63 125 250 500 1000 2000 4000 8000 LwAERAP110MBY 87 84 88 86 84 82 70 66 89ERAP150MBY 94 91 96 90 89 86 75 70 94ERAP170MBY 90 90 93 89 89 88 76 68 94

Low noise unitsSound power Lw per Octave band (dB) Total (dBA)

63 125 250 500 1000 2000 4000 8000 LwAERAP110MBY 84 82 86 83 82 79 66 62 86ERAP150MBY 88 87 92 85 83 81 70 68 89ERAP170MBY 88 86 88 83 82 83 69 64 88

4TW56117-1A

NOTES- Data valid at nominal operation condition- According Eurovent 8-1 (Based on ISO3744)

Page 20: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Applied Systems • Chillers 21

• Chillers • R-407C • ERAP-MBY

11 Installation11 - 1 Fixation and foundation of units

3

111

4TW56119-2

Foundation is built on theground

Notes:

1 The measurement tabulated is based on the factthe base is made in the ground or on a concretefloor. In case the base is made on a rigidconcrete floor, it is possible to include thicknessof concrete floor in that of the base.

2 In case a base is made on concrete floor, be sureto provide a ditch as shown. It is important toextract drainage regardless of wether a base ismade in the ground or on the concrete floor(Ditch → Sewerage).

3 Ingredient ratio of the concrete is cement: 1,sand: 2, gravel: 3, which is standard and insertiron bars of J10 at every interval of 300 mm.The edge of the concrete base should beplaned.

Fix anchor bolts into the concrete foundation.The concrete foundation should be higher thanthe floor level by approximately 100 mm forease of plumbing work and better drain.Further, strength of the floor should be sufficientto support the weight of concrete foundationand unit.Be certain that the foundation surface is evenand flat.

ModelAnchor bolt

Size Qty.ERAP 110-170 kW M16 x 200 4

Foundation is built onconcrete floor

Section X-X

Switc

hbox

side

Unit = mm

Anchor bolts

Washer

Field supplied rubber plates, raw corkor rubber sheet for better vibrationprotection.

Ditch

Page 21: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Chillers • R-407C • ERAP-MBY

• Applied Systems • Chillers22

11 Installation11 - 2 Water charge, flow and quality

111

ITEM

S(1

)(5)

Cool

ing

wat

er(3

)Co

oled

wat

erHe

ated

wat

er(2

)Te

nden

cyif

outo

fcr

iteria

Circ

ulat

ing

syst

emOn

ceflo

wLo

wte

mpe

ratu

reHi

ghte

mpe

ratu

re

Circul

ating

water

Supp

lywa

ter(4)

Flowin

gwate

rCir

culati

ngwa

ter

[20°

C]

Supp

lywa

ter(4)

Circul

ating

water

[20°C

∼60

°C]

Supp

lywa

ter(4)

Circul

ating

water

[60°C

∼80

°C]

Supp

lywa

ter(4)

pHat

25°C

6.5∼8

.26.0

∼8.0

6.8∼8

.06.8

∼8.0

6.8∼8

.07.0

∼8.0

7.0∼8

.07.0

∼8.0

7.0∼8

.0Co

rrosio

n+sca

le

Electr

icalc

ondu

ctivity

[mS/m

]at2

5°C

below

0be

low30

below

40be

low40

below

30be

low30

below

30be

low30

below

30Co

rrosio

n+sca

le

(μS/c

m)at

25°C

(1)(be

low80

0)(be

low30

0)(be

low40

0)(be

low40

0)(be

low30

0)(be

low30

0)(be

low30

0)(be

low30

0)(be

low30

0)Co

rrosio

n+sca

le

Chlor

ideion

[mgC

I- /l]be

low20

0be

low50

below

50be

low50

below

50be

low50

below

50be

low30

below

30Co

rrosio

n

Sulfa

teion

[mgS

O2-4/l]

below

200

below

50be

low50

below

50be

low50

below

50be

low50

below

30be

low30

Corro

sion

M-al

kalini

ty(pH

4.8)

[mgC

aCO 3

/l]be

low10

0be

low50

below

50be

low50

below

50be

low50

below

50be

low50

below

50Sca

le

Total

hardn

ess[m

gCaC

O 3/l]

below

200

below

70be

low70

below

70be

low70

below

70be

low70

below

70be

low70

Scale

Calciu

mha

rdness

[mgC

aCO 3

/l]be

low15

0be

low50

below

50be

low50

below

50be

low50

below

50be

low50

below

50Sca

le

Silica

ion[m

gSiO 2

/l]be

low50

below

30be

low30

below

30be

low30

below

30be

low30

below

30be

low30

Scale

Iron

[mgF

e/l]

below

1.0be

low0.3

below

1.0be

low1.0

below

0.3be

low1.0

below

0.3be

low1.0

below

0.3Co

rrosio

n+sca

le

Copp

er[m

gCu/l

]be

low0.3

below

0.1be

low1.0

below

1.0be

low1.0

below

1.0be

low0.1

below

1.0be

low0.1

Corro

sion

Sulfit

eion

[mgS

2-/l]

Notd

etecta

bleNo

tdete

ctable

Notd

etecta

bleNo

tdete

ctable

Notd

etecta

bleNo

tdete

ctable

Notd

etecta

bleNo

tdete

ctable

Notd

etecta

bleCo

rrosio

n

ammo

nium

ion[m

gNH+ 4/l]

below

1.0be

low1.0

below

1.0be

low1.0

below

0.1be

low0.3

below

0.1be

low0.1

below

0.1Co

rrosio

n

Rema

iningc

hlorid

e[m

gCL/l]

below

0.3be

low0.3

below

0.3be

low0.3

below

0.3be

low0.2

5be

low0.3

below

0.1be

low0.3

Corro

sion

Freec

arbide

[mgC

O 2/l]

below

4.0be

low4.0

below

4.0be

low4.0

below

4.0be

low0.4

below

4.0be

low0.4

below

4.0Co

rrosio

n

Stabili

tyind

ex6.0

∼7.0

------

------

------

------

Corro

sion+

scale 3T

W50

179-

1

1N

ames

,def

initi

ons

and

units

are

acco

rdin

gto

JISK

0101

.Uni

tsan

dfig

ures

betw

een

brac

kets

are

old

units

publ

ished

asre

fere

nce

only

.

2In

case

ofus

ing

heat

edw

ater

(mor

eth

an40

°C),

corro

sion

isge

nera

llyno

ticea

ble.

Espe

cial

lyw

hen

the

iron

mat

eria

lis

indi

rect

cont

actw

ithw

ater

with

outa

nypr

otec

tion

shie

lds,

itis

desir

eabl

eto

give

the

valid

mea

sure

sfo

rcor

rosio

n.e.

g.ch

emoc

alm

easu

re.

3In

the

cool

ing

wat

erus

ing

herm

etic

cool

ing

tow

er,c

lose

dci

rcui

twat

eris

acco

rdin

gto

heat

edw

ater

stan

dard

,and

scat

tere

dw

ater

isac

cord

ing

toco

olin

gw

ater

stan

dard

.

4Su

pply

wat

eris

cons

ider

eddr

ink

wat

er,i

ndus

trial

wat

eran

dgr

ound

wat

erex

cept

forg

enui

new

ater

,neu

tralw

ater

and

soft

wat

er.

5Th

eab

ove

men

tione

dite

ms

are

repr

esen

tabl

eite

ms

inco

rrosio

nan

dsc

ale

case

s.

Page 22: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

• Applied Systems • Chillers 23

• Chillers • R-407C • ERAP-MBY

12 Operation range

3

112

4TW53503-1A

Ambient temperature

Evaporating temperature(°C) (Suction dew point)

ERAP110-170MBY

CONTINUOUS OPERATION AREA PULL-DOWN AREA

degr. C

Page 23: EEDEN09-410igclima.com/dvd-daikin/3_Applied_Systems/2_Condensing... · 2010. 5. 4. · 1 3 3-1 TECHNICAL SPECIFICATIONS ERAP110MBY ERAP150MBY ERAP170MBY Capacity (Eurovent) Cooling

Condensing unit

ERAP110-170MBY

EED

EN09

-410

- 12

/200

8Pr

inte

d in

Bel

gium

by

Goe

kint

Gra

phic

sCo

pyrig

ht ©

Dai

kin

EEDEN0 9 - 4 1 0

Naamloze Vennootschap

Zandvoordestraat 300

B-8400 Ostend, Belgium

www.daikin.eu

BTW: BE 0412 120 336

RPR Oostende

ISO14001 assures an effective environmental management system in order to help protect human health and the environment from potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.

Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

Daikin units comply with the European regulations that guarantee the safety of the product.

Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil units (FC); the certified data of certified models are listed in the Eurovent Directory.

Daikin’s unique position as a man-ufacturer of air conditioning equip-ment, compressors and refrige-rants has led to its close involve-ment in environmental issues. Forseveral years Daikin has had the in-tention to become a leader in theprovision of products that havelimited impact on the environ-ment. This challenge demands theeco design and development of awide range of products and an en-ergy management system, result-ing in energy conservation and areduction of waste.

“The present publication is drawn up by way of information only anddoes not constitute an offer binding upon Daikin Europe N.V.. DaikinEurope N.V. has compiled the content of this publication to the bestof its knowledge. No express or implied warranty is given for thecompleteness, accuracy, reliability or fitness for particular purpose ofits content and the products and services presented therein. Specifi-cations are subject to change without prior notice. Daikin Europe N.V.explicitly rejects any liability for any direct or indirect damage, In thebroadest sense, arising from or related to the use and/or interpreta-tion of this publication. All content is copyrighted by Daikin EuropeN.V..”


Recommended