XC21 DAVE LENNOX SIGNATUREt COLLECTION R-410A - Two-Stage Compressor - SilentComfortt Technology A I R C O N D I T I O N E R S E N G I N E E R I N G D A T A Bulletin No. 210414 April 2005 Supersedes March 2005 SEER - up to 20.50 2 to 5 Tons Cooling Capacity - 23,600 to 60,500 Btuh MODEL NUMBER IDENTIFICATION C 21 036 Unit Type C = Air Conditioner Series Nominal Cooling Capacity 024 = 2 tons (7.0 kW) 036 = 3 tons (10.5 kW) 048 = 4 tons (14.0 kW) 060 = 5 tons (17.5 kW) Minor Revision Number 230 Voltage 230 = 208/230V−1ph−60hz Refrigerant Type X = R−410A X 2
Transcript
Page 1: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21DAVE LENNOX SIGNATURE� COLLECTION

R−410A − Two−Stage Compressor − SilentComfort� Technology

A I R C O N D I T I O N E R S

E N G I N E E R I N G D A T A Bulletin No. 210414

April 2005

Supersedes March 2005

SEER − up to 20.502 to 5 Tons

Cooling Capacity − 23,600 to 60,500 Btuh

MODEL NUMBER IDENTIFICATION

C 21 036− −

Unit TypeC = Air Conditioner

Series

Nominal Cooling Capacity024 = 2 tons (7.0 kW)036 = 3 tons (10.5 kW)048 = 4 tons (14.0 kW)060 = 5 tons (17.5 kW)

Minor Revision Number

230

Voltage230 = 208/230V−1ph−60hz

Refrigerant TypeX = R−410A

X 2−

Page 2: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 2

FEATURES

CONTENTS

ARI Ratings Pages 8−18. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions Page 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical Data Page 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Features Pages 1−4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Expanded Rating Tables Pages 19−127. . . . . . . . . . . . . . .

Field Wiring Page 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Installation Clearances Page 7. . . . . . . . . . . . . . . . . . . . . . .

Model Number Identification Page 1. . . . . . . . . . . . . . . . . .

Optional Accessories Page 5. . . . . . . . . . . . . . . . . . . . . . . .

Sound Data Page 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Specifications Page 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Equipment Warranty

Compressor − limited warranty for ten years inresidential installations and five years in non-residentialinstallations.All other covered components − five years inresidential installations and one year in non-residentialinstallations.Refer to Lennox Equipment Limited Warranty certificateincluded with unit for specific details.

Application

SEER up to 20.50.2 through 5 ton (7.0 through 17.6 kW).Single phase power supply.Sound levels as low as 69 dB.Vertical air discharge allows concealment behind shrubsat grade level or out of sight on a roof.Matching add−on furnace indoor coils or air handlersprovide a wide range of cooling capacities andapplications. See ARI Ratings tables.See Indoor Coils and Air Handlers tab sections for data.Units shipped completely factory assembled, piped, andwired. Each unit is test operated at the factory insuringproper operation.Installer must set air conditioner, connect refrigerant lines,and make electrical connections to complete job.

Approvals

Certified in accordance with USE certification programwhich is based on ARI Standard 210/240−94.Sound rated in Lennox reverberant sound test room inaccordance with test conditions included in ARI Standard270−95.Tested in the Lennox Research Laboratory environmentaltest room.Rated according to U.S. Department of Energy (DOE) testprocedures.Air conditioners and components within bonded forgrounding to meet safety standards for servicing requiredby UL and CEC.Units are UL and ULC listed.ISO 9001 Registered Manufacturing Quality System.ENERGY STAR® certified units are designed to use lessenergy, help save money on utility bills, and help protectthe environment.

REFRIGERATION SYSTEM

RefrigerantNon−chlorine, ozone friendly, R−410A.Unit pre−charged with refrigerant.See Specification table.

B

D

E

C

G

FH

IM

K

J

L

Condenser Fan with SilentComfort� TechnologySpecially−designed, SilentComfort fan guard usesPassive Vortex Suppression to reduce air noise.Constructed of corrosion−resistant PVC (polyvinylchloride) coated steel wire.Specially designed fan blades reduce operating soundlevels. Direct drive fan moves large air volumes uniformlythrough entire condenser coil for high refrigerant coolingcapacity.Vertical air discharge minimizes operating sounds andeliminates damage to lawn and shrubs.Fan motor is inherently protected.All models have a variable−speed outdoor fan motor forquiet operation.Motor totally enclosed for maximum protection fromweather, dust and corrosion.Fan service access accomplished by removal of fanguard.

Copper Tube/Enhanced Fin CoilLennox designed and fabricated coil.Ripple−edged aluminum fins.Copper tube construction.Lanced fins provide maximum exposure of fin surface toair stream resulting in excellent heat transfer.Fin collars grip tubing for maximum contact area.Flared shoulder tubing connections/silver solderingconstruction.Coil is factory tested under high pressure to insureleakproof construction.Entire coil is accessible for cleaning.

B

C

D

E

Page 3: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

Internalsolenoid

SliderRing

Fixed scrollInternal solenoid

Slider Ring

XC21 − 2 to 5 Ton Air Conditioner / Page 3

FEATURES

REFRIGERATION SYSTEM (CONTINUED)

High Pressure SwitchShuts off unit if abnormal operating conditions cause thedischarge pressure to rise above setting.Protects compressor from excessive condensingpressure.Manual reset.

Low Pressure SwitchShuts off unit if suction pressure falls below setting.Provides loss of charge and freeze-up protection.Automatic reset.

Hi-Capacity Liquid Line DrierFactory installed in the liquid line, the drier traps moistureor dirt that could contaminate the refrigerant system.100% molecular−sieve bead type drier.

OPTIONS

Expansion Valve KitsMust be ordered extra and field installed on certain indoorunits. See ARI Ratings tables.Chatleff style fitting.

FreezestatInstalls on or near the discharge line of the indoor coil or onthe suction line.Senses suction line temperature and cycles thecompressor off when suction line temperature falls belowit’s setpoint.Opens at 29°F (−2°C) and closes at 58°F (14°C).

Refrigerant Line KitsRefrigerant lines (suction & liquid) are shippedrefrigeration clean. Lines are cleaned, dried, pressurized,and sealed at factory.Suction line fully insulated.L15 lines are stubbed at both ends.See Specifications table for selection.Not available for −060 model and must be field fabricated.

COMPRESSOR

Copeland Scroll Ultra Tech� Two−Stage CompressorCompressor features highefficiency with uniformsuction flow, constantdischarge flow and highvolumetric efficiency andquiet operation.Compressor consists oftwo involute spiral scrollsmatched together togenerate a series ofcrescent shaped gaspockets between them.During compression, onescroll remains stationarywhile the other scroll orbitsaround it.Gas is drawn into the outerpocket, the pocket is sealed as the scroll rotates.As the spiral movement continues, gas pockets arepushed to the center of the scrolls. Volume between thepockets is simultaneously reduced.

When pocket reaches the center, gas is now at highpressure and is forced out of a port located in the center

of the fixed scrolls. Duringcompression, severalpockets are compressedsimultaneously resulting ina smooth continuouscompression cycle.Continuous flank contact,maintained by centrifugalforce, minimizes gasleakage and maximizes

efficiency.Scroll compressor is tolerant to the effects of sluggingand contaminants. If this occurs, scrolls separate,allowing liquid or contaminants to to be worked towardthe center and discharged.On the fixed scroll there are two bypass ports in the firstsuction pocket. On the outside of the fixed scroll there is a�slider ring" that is controlled by an internal solenoid thatwill rotate and cover the bypass ports. When thethermostat calls for first−stage cooling, the bypass portsare open and the compressor operates at 67% capacity,creating more cost−effective and efficient compressoroperation. The bypassed refrigerant is returned to thecompressor housing through the bypass ports. Whenthe thermostat calls for second−stage cooling, theinternal solenoid is energized, the slider ring rotates andcovers the bypass ports, and the compressor operatesat full capacity.Low gas pulses during compression reducesoperational sound levels.Compressor motor is internally protected fromexcessive current and temperature.Compressor is installed in the unit on speciallyformulated, resilient rubber mounts for better sounddampening and vibration free operation.

Crankcase HeaterCrankcase heater prevents migration of liquid refrigerantinto compressor and ensures proper compressorlubrication.

OPTIONS

Compressor Hard Start KitSingle−phase units are equipped with a PSC compressormotor.This type of motor normally does not need a potentialrelay and start capacitor.In conditions such as low voltage, kit may be required toincrease the compressor starting torque.

F

G

H

I

Page 4: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 4

FEATURES

CONTROLS

Lennox® System Operations MonitorProvides detailed information for properpreventive maintenance and fast, easyservicing.Displays the most common fault conditionsthrough indicator LED’s.Monitor detects both mechanical andelectrical system problems.Monitors only and does not provide safetyprotection.When an abnormal condition is detected, communicatesthe specific condition through the ALERT and TRIP lights.POWER LED (green) − indicates voltage within the range of19−28VAC is present at the power connection.ALERT LED (yellow) − communicates an abnormalsystem condition through a unique flash code. TheALERT LED will flash a number of times consecutively,pause and then repeat the process. The number ofconsecutive flashes, defined as the Flash Code,correlates to a particular abnormal condition. The codescan indicate one of the following: long run time, systempressure trip (discharge or suction pressure out−of−limitsor compressor overloaded), short cycling, locked rotor,open circuit, open start circuit (current present only in runcircuit), open run circuit (current present only in startcircuit), welded contactor (compressor runscontinuously), or low voltage (control circuit < 17VAC).TRIP LED (red) − indicates there is a demand signal fromthe thermostat but no current to the compressor isdetected by the monitor.

OPTIONS

SignatureStat� Home Comfort ControlCombination temperatureand humidity control.2 Heat/2 CoolAuto−changeoverEasy−to−use, menu driventhermostat with a back−lit,dot−matrix LCD screen.Remote outdoor sensor(furnished) allows the thermostat to display outdoortemperature and adjust indoor dewpoint temperature forprecision humidity control.See the SignatureStat Engineering Handbook bulletin inthe Controls section for more information.See Controls section and Lennox Price Book foradditional thermostats.

Indoor Blower Speed Relay KitRelay kit provides optimum humidity control conditions byautomatically reducing indoor blower speed duringcontinuous fan or first−stage compressor operation.

Time Delay Relay KitDelays the indoor blower−off time during the cooling cycle.See ARI Rating Tables for usage.

Low Ambient KitAir conditioner will operate satisfactorily down to 45�F (7�C)outdoor air temperature without any additional controls.Kit can be added in the field enabling unit to operateproperly down to 30�F (−1�C).Freezestat should be installed on compressors equippedwith a low ambient kit.A compressor lock−out thermostat should be added toterminate compressor operation below recommendedoperation conditions (on/off operation, 30°F (−1°C) ormodulating operation, 0°F (−18°C).

CabinetHeavy−gauge steel constructionPre−painted cabinet finish.Painted base section.Compressor and control box located in a separatecompartment, insulated with thick fiberglass insulation.Compartment provides protection from the weather andkeeps sound transmission at a minimum.Control box is conveniently located with all controlsfactory wired.Large removable panel provides service access.Drainage holes are provided in base section for moistureremoval.High density polyethylene unit support feet raise the unit offof the mounting surface, away from damaging moisture.

SmartHinge� Louvered Coil ProtectionSteel louvered panelsprovides complete coilprotection.Panels are hinged toallow easy cleaningand servicing of coils.Panels may becompletely removed.Interlocking tabs andslots assure tight fit oncabinet.

Refrigerant Line Connections, Electrical Inlets andService ValvesSuction and liquid lines are located on corner of unitcabinet and are made with sweat connections. Seedimension drawing.Fully serviceable brass service valves prevent corrosionand provide access to refrigerant system. Suction valvecan be fully shut off, while liquid valve may be front seatedto manage refrigerant charge while servicing system.Suction and liquid line service valves and gauge ports arelocated inside the cabinet.Refrigerant line connections and field wiring inlets arelocated in one central area of the cabinet. See dimensiondrawing.

OPTIONS

Mounting BaseProvides permanent foundation for outdoor units.High density polyethylene structural material islightweight, sturdy, sound absorbing and will withstand therigors of the sun, heat, cold, moisture, oil and refrigerant.Will not mildew or rot.Dimensions: 32 x 34 x 3 in.Can be shipped singly or in packages of 6 to a carton.

J

K

L

M

Page 5: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 5

SPECIFICATIONS

GeneralD t

Model No. XC21−024 XC21−036 XC21−048 XC21−060Data Nominal Tonnage (kW) 2 (7.0) 3 (10.6) 4 (14.1) 5 (17.6)

Connections(sweat)

Liquid line (o.d.) − in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)(sweat)

Suction line (o.d.) − in. (mm) 7/8 (22.2) 7/8 (22.2) 7/8 (22.2) 1−1/8 (28.6)

Refrigerant 1 R−410A charge furnished 12 lbs. 0 oz. (5.4 kg) 12 lbs. 5 oz. (5.6 kg) 13 lbs. 0 oz. (5.9 kg) 13 lbs. 0 oz. (5.9 kg)

OutdoorCoil

Net face area − sq. ft. (m2) Outer coil 26.92 (2.50) 26.92 (2.50) 26.92 (2.50) 26.92 (2.50)Coil

Inner coil 26.07 (2.42) 26.07 (2.42) 26.07 (2.42) 26.07 (2.42)

Tube diameter − in. (mm) 5/16 (0.52) 5/16 (0.52) 5/16 (0.52) 5/16 (0.52)

No. of rows 2 2 2 2

Fins per inch (m) 22 (866) 22 (866) 22 (866) 22 (866)

OutdoorFan

Diameter − in. (mm) 26 (660) 26 (660) 26 (660) 26 (660)Fan

No. of blades 3 3 3 3

Motor hp (W) 1/3 (249) 1/3 (249) 1/3 (249) 1/3 (249)

Cfm (L/s) 1st stage 2800 (1320) 3200 (1510) 3800 (1795) 3800 (1795)

2nd stage 3200 (1510) 3700 (1745) 4400 (2075) 4400 (2075)

Rpm − 1st stage 700 700 700 700

2nd stage 820 820 820 820

Watts − 1st stage 70 96 150 150

2nd stage 105 140 220 220

Shipping Data − lbs. (kg) 1 pkg. 314 (142) 331 (150) 337 (153) 357 (162)

ELECTRICAL DATA

Line voltage data − 60hz 208/230V−1ph 208/230V−1ph 208/230V−1ph 208/230V−1ph

3 Maximum overcurrent protection (amps) 25 40 50 60

2 Minimum circuit ampacity 15.7 23.7 29.3 34.9

Compressor Rated load amps 10.3 16.7 21.2 25.7

Locked rotor amps 52 82 96 118

Power factor 0.98 0.98 0.98 0.98

Outdoor FanMotor

Full load amps 2.8 2.8 2.8 2.8

OPTIONAL ACCESSORIES − must be ordered extra

Compressor Hard Start Kit 10J42 � �

81J69 � �

Compressor Low Ambient Cut−Off 45F08 � � � �

Compressor Time−Off Control 47J27 � � � �

Freezestat 3/8 in. tubing 93G35 � � � �

1/2 in. tubing 39H29 � � � �

5/8 in. tubing 50A93 � � � �

Indoor Blower Relay 40K58 � � � �

Low Ambient Kit 68M04 � � � �

Mounting Base 69J07 � � � �

SignatureStat� Home Comfort Control 81M27 � � � �

RefrigerantLine Sets

L15−65−15L15−65−30

L15−65−40L15−65−50

� � �

Field Fabricate �

Time Delay Relay 58M81 � � � �

NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.1 Refrigerant charge sufficient for 15 ft. (4.6 m) length of refrigerant lines.2 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.3 HACR type breaker or fuse.

Page 6: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 6

DIMENSIONS � INCHES

39−1/2 35−1/2

47

18−1/2

8

1

4−1/2

LIQUID LINEINLET

SUCTION LINEINLET

ELECTRICALINLETS

TOP VIEW

SIDE VIEW ACCESS VIEW

DISCHARGE AIR

10−1/2

13−1/2

11 18

TOP VIEW BASE SECTION

COIL DRAIN OUTLETS(Around perimeter of base)

UNIT SUPPORT FEET

Page 7: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 7

INSTALLATION CLEARANCES

ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ

1 36

1 − One of these three sides must be 36 in.

One of the two remaining sides may be 12 in.

The remaining side may be 6 in.

− Service Clearance − 30 in.

− 48 in. clearance required on top of unit

− 24 in. required between two units

1 36 30(service)

1 36

FIELD WIRING

DISCONNECTSWITCH

(By Others)

DISCONNECTSWITCH

(By Others)

A � Two Wire Power (not furnished)

B � Two Power (not furnished) � See Electrical Data

C � Four Wire Low Voltage (not furnished) � 18 ga. minimum

D � Six Wire Low Voltage (not furnished) � 18 ga. minimum

All wiring must conform to NEC or CEC and local electrical codes.

B

LENNOXAIR

CONDITIONER

LENNOXHEATING UNIT

ORAIR HANDLER

THERMOSTAT(Optional)

C

D A

OUTDOOR SOUND DATA

1 U itOctave Band Sound Power Levels dBA, re 10−12 Watts 1Sound

R ti1 UnitModel No.

Center Frequency − HZRating

NumberModel No.63 125 250 500 1000 2000 4000 8000

Number(dB)

XC21-024 48.5 54.5 61 64 62 60 56 49 69

XC21-036 49 60 65 66.5 64.5 61.5 56.5 50 71

XC21-048 49.5 59.5 66.5 68 67 63 58 52 73

XC21-060 50 60 65.5 70 68.5 64 57 50.5 73

NOTE − the octave sound power data does not include tonal correction.1 Tested according to ARI Standard 270-95 test conditions.

Page 8: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 8

ARI RATINGS − R−410A INDOOR COILS / INDOOR COILS + FURNACES / AIR HANDLERS 2 Ton

NOTE − Match−ups are sorted by: Cooling Capacity then SEER

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No. Expansion Device

XC21−0242 Ton

Up-FlowIndoor Coils

23,600 6.9 16.05 12.25 1925 5 CX34−18/24A/B/C−6F Factory Installed TXV2 Ton(69 dB)

Indoor Coils24,000 7.0 16.55 12.65 1900 5 CX34−30A/B/C−6F Factory Installed TXV( )

24,400 7.2 16.75 12.85 1900 5 CX34−36A/B/C−6F Factory Installed TXV

24,400 7.2 16.75 12.85 1900 5 CX34−42B−6F 3 37L51 − order separately

24,600 7.2 16.75 12.75 1930 5 CX34−25A/B−6F Factory Installed TXV

25,000 7.3 16.90 12.95 1930 5 CX34−31A/B−6F Factory Installed TXV

25,200 7.4 17.25 13.25 1905 5 CX34−38B−6F Factory Installed TXV

Up-FlowIndoor Coils

24,400 7.2 19.15 14.00 1750 6 CX34−18/24B−6F + G60UHV−36B−090 Factory Installed TXVIndoor Coils+ Furnaces 24,400 7.2 19.10 13.90 1755 6 CX34−30B−6F + G60UHV−36B−090 Factory Installed TXV

24,400 7.2 19.00 13.75 1775 6 CX34−18/24A−6F + G60UHV−36A−070 Factory Installed TXV

24,400 7.2 18.90 13.70 1780 6 CX34−30A−6F + G60UHV−36A−070 Factory Installed TXV

24,400 7.2 18.75 13.70 1780 6 CX34−18/24B−6F + G61MPV−36B−045 Factory Installed TXV

24,400 7.2 18.75 13.65 1790 6 CX34−30B−6F + G61MPV−36B−045 Factory Installed TXV

25,000 7.3 19.45 14.10 1775 6 CX34−36B−6F + G61MPV−36B−070 Factory Installed TXV

25,000 7.3 19.40 14.10 1775 6 CX34−42B−6F + G60UHV−36B−090 3 37L51 − order separately

25,000 7.3 19.50 14.05 1780 6 CX34−36A−6F + G60UHV−36A−070 Factory Installed TXV

25,200 7.4 19.75 14.35 1755 6 CX34−36B−6F + G60UHV−36B−090 Factory Installed TXV

25,200 7.4 19.75 14.35 1755 6 CX34−38B−6F + G60UHV−36B−090 Factory Installed TXV

25,200 7.4 19.70 14.15 1780 6 CX34−25A−6F + G60UHV−36A−070 Factory Installed TXV

25,200 7.4 19.30 14.10 1785 6 CX34−36B−6F + G61MPV−36B−045 Factory Installed TXV

25,200 7.4 19.30 14.10 1785 6 CX34−42B−6F + G61MPV−36B−045 3 37L51 − order separately

25,400 7.4 20.00 14.45 1755 6 CX34−25B−6F + G60UHV−36B−090 Factory Installed TXV

25,400 7.4 19.55 14.20 1790 6 CX34−25B−6F + G61MPV−36B−045 Factory Installed TXV

25,400 7.4 19.65 14.30 1775 6 CX34−25B−6F + G61MPV−36B−070 Factory Installed TXV

25,600 7.5 19.90 14.40 1780 6 CX34−31A−6F + G60UHV−36A−070 Factory Installed TXV

25,600 7.5 19.80 14.40 1780 6 CX34−31B−6F + G61MPV−36B−070 Factory Installed TXV

25,600 7.5 19.75 14.25 1795 6 CX34−31B−6F + G61MPV−36B−045 Factory Installed TXV

25,800 7.6 20.00 14.70 1755 6 CX34−31B−6F + G60UHV−36B−090 Factory Installed TXV

25,800 7.6 20.00 14.50 1780 6 CX34−38B−6F + G61MPV−36B−070 Factory Installed TXV

25,800 7.6 19.75 14.30 1805 6 CX34−38A−6F + G60UHV−36A−070 Factory Installed TXV

26,000 7.6 19.90 14.55 1790 6 CX34−38B−6F + G61MPV−36B−045 Factory Installed TXV

Air Handlers 25,000 7.3 19.70 14.55 1720 6 CBX32MV−024/030 (Multi−Position) Factory Installed TXV

25,000 7.3 19.30 13.70 1825 6 CBX32MV−018/024 (Multi−Position) Factory Installed TXV

25,000 7.3 17.80 13.50 1855 5 CBX32M−030 (Multi−Position) Factory Installed TXV

25,000 7.3 17.50 13.25 1885 5 CBX32M−036 (Multi−Position) Factory Installed TXV

25,000 7.3 17.50 13.25 1885 5 CBX32M−042 (Multi−Position) 3 37L51 − order separately

26,000 7.6 20.50 14.75 1765 4, 6 CBX32MV−036 (Multi−Position) Factory Installed TXV

1 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.2 Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air with 25 ft. (7.6 m) of connecting refrigerant lines.3 Factory installed expansion valve or RFCIV device on indoor unit MUST be replaced with valve specified.4 Most popular air handler.5 Blower must be capable of time−off blower delay, high−speed cooling/heating operation during second−stage compressor operation, and low−speed cooling/heating operation

during first−stage compressor operation. Time Delay Relay Kit (58M81) and Indoor Blower Speed Relay Kit (40K58) are recommend for field installation.6 Blower control must be set for a time−off blower delay.

Page 9: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 9

ARI RATINGS − R−22 INDOOR COILS / AIR HANDLERS 2 Ton

NOTE − Match−ups are sorted by: Cooling Capacity then SEER

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No. Expansion Device

XC21−0242 Ton

Up-FlowIndoor Coils

23,600 6.9 16.05 12.25 1925 4 C33−24A/B/C 3 37L51 − order separately2 Ton(69 dB)

Indoor Coils24,000 7.0 16.55 12.65 1900 4 C33−30A/B/C 3 37L51 − order separately( )

24,400 7.2 16.75 12.85 1900 4 C33−36A/B/C 3 37L51 − order separately

24,400 7.2 16.75 12.85 1900 4 C33−42B 3 37L51 − order separately

24,600 7.2 16.75 12.75 1930 4 C33−25A/B 3 37L51 − order separately

25,000 7.3 17.15 13.10 1905 4 C33−44C 3 37L51 − order separately

25,000 7.3 16.90 12.95 1930 4 C33−31A/B 3 37L51 − order separately

25,200 7.4 17.25 13.25 1905 4 C33−38B 3 37L51 − order separately

Down-FlowIndoor Coils

24,200 7.1 16.75 12.75 1900 4 CR26−30N−F 3 37L51 − order separatelyIndoor Coils

24,800 7.3 17.00 13.00 1905 4 CR26−36N/W−F 3 37L51 − order separately

HorizontalIndoor Coils

22,000 6.4 15.10 11.45 1920 4 CH33−18A−2F 3 37L51 − order separatelyIndoor Coils

22,800 6.7 15.40 11.85 1925 4 CH23−21 3 37L51 − order separately

23,200 6.8 15.60 12.05 1925 4 CH23−31 3 37L51 − order separately

23,800 7.0 16.45 12.55 1900 4 CH33−24/30A−2F 3 37L51 − order separately

24,000 7.0 16.40 12.65 1900 4 CH23−41 3 37L51 − order separately

24,200 7.1 16.75 12.75 1900 4 CH33−36B−2F 3 37L51 − order separately

24,400 7.2 16.85 12.85 1900 4 CH33−36A−2F 3 37L51 − order separately

24,600 7.2 16.85 13.00 1900 4 CH33−36C−2F 3 37L51 − order separately

24,600 7.2 16.85 13.00 1900 4 CH23−51 3 37L51 − order separately

Air Handlers 25,000 7.3 17.80 13.50 1855 4 CB30M−31 (Multi−Position) 3 37L51 − order separately

25,000 7.3 17.80 13.50 1855 4 CB30U−31 (Up−Flow) 3 37L51 − order separately

25,000 7.3 17.50 13.25 1885 4 CB30M−41 (Multi−Position) 3 37L51 − order separately

25,000 7.3 17.50 13.25 1885 4 CB30U−41/46 (Up−Flow) 3 37L51 − order separately

25,800 7.6 17.85 13.65 1890 4 CB30M−46 (Multi−Position) 3 37L51 − order separately

26,000 7.6 20.50 14.75 1765 5 CB31MV−41 (Multi−Position) 3 37L51 − order separately

NOTE − Ratings for all C33 coils include all cased and uncased coils.1 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.2 Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air with 25 ft. (7.6 m) of connecting refrigerant lines.3 Factory installed expansion valve or RFCIV device on indoor unit MUST be replaced with valve specified.4 Blower must be capable of time−off blower delay, high−speed cooling/heating operation during second−stage compressor operation, and low−speed cooling/heating operation

during first−stage compressor operation. Time Delay Relay Kit (58M81) and Indoor Blower Speed Relay Kit (40K58) are recommend for field installation.5 Blower control must be set for a time−off blower delay.

Page 10: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 10

ARI RATINGS − R−22 INDOOR COILS + FURNACES 2 Ton

NOTE − Match−ups are sorted by: Cooling Capacity then SEER

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No. Expansion Device

XC21−0242 T

Up-FlowI d C il

24,400 7.2 19.15 14.00 1750 4 C33−24B + G60UHV−36B−090 3 37L51 − order separately2 Ton(69 dB)

pIndoor Coils+ Furnaces 24,400 7.2 19.10 13.90 1755 4 C33−30B + G60UHV−36B−090 3 37L51 − order separately(69 dB) + Furnaces

24,400 7.2 19.00 13.75 1775 4 C33−24A + G60UHV−36A−070 3 37L51 − order separately

24,400 7.2 18.90 13.70 1780 4 C33−30A + G60UHV−36A−070 3 37L51 − order separately

24,400 7.2 18.75 13.70 1780 4 C33−24B + G61MPV−36B−045 3 37L51 − order separately

24,400 7.2 18.75 13.65 1790 4 C33−30B + G61MPV−36B−045 3 37L51 − order separately

25,000 7.3 19.50 14.05 1780 4 C33−36A + G60UHV−36A−070 3 37L51 − order separately

25,000 7.3 19.45 14.10 1775 4 C33−36B + G61MPV−36B−070 3 37L51 − order separately

25,000 7.3 19.40 14.10 1775 4 C33−42B + G60UHV−36B−090 3 37L51 − order separately

25,200 7.4 19.75 14.35 1755 4 C33−36B + G60UHV−36B−090 3 37L51 − order separately

25,200 7.4 19.75 14.35 1755 4 C33−38B + G60UHV−36B−090 3 37L51 − order separately

25,200 7.4 19.70 14.15 1780 4 C33−25A + G60UHV−36A−070 3 37L51 − order separately

25,200 7.4 19.30 14.10 1785 4 C33−36B + G61MPV−36B−045 3 37L51 − order separately

25,200 7.4 19.30 14.10 1785 4 C33−42B + G61MPV−36B−045 3 37L51 − order separately

25,400 7.4 20.00 14.45 1755 4 C33−25B + G60UHV−36B−090 3 37L51 − order separately

25,400 7.4 19.65 14.30 1775 4 C33−25B + G61MPV−36B−070 3 37L51 − order separately

25,400 7.4 19.55 14.20 1790 4 C33−25B + G61MPV−36B−045 3 37L51 − order separately

25,600 7.5 19.90 14.40 1780 4 C33−31A + G60UHV−36A−070 3 37L51 − order separately

25,600 7.5 19.80 14.40 1780 4 C33−31B + G61MPV−36B−070 3 37L51 − order separately

25,600 7.5 19.75 14.25 1795 4 C33−31B + G61MPV−36B−045 3 37L51 − order separately

25,800 7.6 20.00 14.70 1755 4 C33−31B + G60UHV−36B−090 3 37L51 − order separately

25,800 7.6 20.00 14.50 1780 4 C33−38B + G61MPV−36B−070 3 37L51 − order separately

25,800 7.6 19.75 14.30 1805 4 C33−38A + G60UHV−36A−070 3 37L51 − order separately

26,000 7.6 19.90 14.55 1790 4 C33−38B + G61MPV−36B−045 3 37L51 − order separately

Down-FlowI d C il

25,400 7.4 19.25 14.10 1800 4 CR26−30N−F + G60DFV−36B−090 3 37L51 − order separatelyIndoor Coils+ Furnaces 25,800 7.6 19.65 14.35 1800 4 CR26−36N−F + G60DFV−36B−090 3 37L51 − order separately+ Furnaces

25,800 7.6 19.65 14.35 1800 4 CR26−48N−F + G60DFV−36B−090 3 37L51 − order separately

HorizontalI d C il

23,600 6.9 18.75 13.65 1730 4 CH23−21 + G60UHV−36B−090 3 37L51 − order separatelyIndoor Coils+ Furnaces 23,600 6.9 18.50 13.45 1755 4 CH23−21 + G61MPV−36B−070 3 37L51 − order separately+ Furnaces

23,600 6.9 18.30 13.35 1765 4 CH23−21 + G61MPV−36B−045 3 37L51 − order separately

25,000 7.3 19.40 14.10 1775 4 CH33−42B−2F + G60UHV−36B−090 3 37L51 − order separately

25,000 7.3 19.30 13.90 1800 4 CH33−36A−2F + G60UHV−36A−070 3 37L51 − order separately

25,000 7.3 19.05 13.95 1795 4 CH33−44/48B−2F + G60UHV−36B−090 3 37L51 − order separately

25,200 7.4 19.75 14.30 1760 4 CH33−36B−2F + G61MPV−36B−070 3 37L51 − order separately

25,200 7.4 19.70 14.35 1755 4 CH33−36B−2F + G60UHV−36B−090 3 37L51 − order separately

25,200 7.4 19.60 14.30 1765 4 CH33−36B−2F + G61MPV−36B−045 3 37L51 − order separately

25,600 7.5 19.80 14.40 1775 4 CH33−42B−2F + G61MPV−36B−070 3 37L51 − order separately

25,600 7.5 19.70 14.30 1790 4 CH33−42B−2F + G61MPV−36B−045 3 37L51 − order separately

NOTE − Ratings for all C33 coils include all cased and uncased coils.1 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.2 Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air with 25 ft. (7.6 m) of connecting refrigerant lines.3 Factory installed expansion valve or RFCIV device on indoor unit MUST be replaced with valve specified.4 Blower control must be set for a time−off blower delay.

Page 11: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 11

ARI RATINGS − R−410A INDOOR COILS / INDOOR COILS + FURNACES / AIR HANDLERS 3 Ton

NOTE − Match−ups are sorted by: Cooling Capacity then SEER

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No. Expansion Device

XC21−0363 T

Up-FlowI d C il

35,200 10.3 16.05 12.05 2925 5 CX34−36A/B/C−6F Factory Installed TXV3 Ton(71 dB)

pIndoor Coils

35,200 10.3 16.05 12.05 2925 5 CX34−42B−6F 3 37L51 − order separately(71 dB)36,200 10.6 16.40 12.35 2930 5 CX34−44/48B/C−6F 3 37L51 − order separately

36,600 10.7 16.60 12.45 2935 5 CX34−38B−6F Factory Installed TXV

36,600 10.7 16.55 12.45 2935 5 CX34−50/60C−6F 3 37L51 − order separately

36,600 10.7 16.40 12.45 2935 5 CX34−49C−6F 3 37L51 − order separately

Up-FlowI d C il

35,600 10.4 18.10 12.55 2835 6 CX34−36B−6F + G61MPV−36B−070 Factory Installed TXVpIndoor Coils+ Furnaces 35,600 10.4 18.10 12.55 2835 6 CX34−42B−6F + G61MPV−36B−070 3 37L51 − order separately+ Furnaces

35,800 10.5 18.20 12.65 2835 6 CX34−36A−6F + G60UHV−36A−070 Factory Installed TXV

36,000 10.6 18.55 13.00 2775 6 CX34−36B−6F + G60UHV−36B−090 Factory Installed TXV

36,000 10.6 18.55 13.00 2775 6 CX34−42B−6F + G60UHV−36B−090 3 37L51 − order separately

36,800 10.8 18.50 13.00 2845 6 CX34−44/48B−6F + G61MPV−36B−070 3 37L51 − order separately

37,200 10.9 19.00 13.55 2745 6 CX34−44/48B−6F + G60UHV−36B−090 3 37L51 − order separately

37,200 10.9 18.70 13.10 2845 6 CX34−38B−6F + G61MPV−36B−070 Factory Installed TXV

37,400 11.0 19.20 13.45 2780 6 CX34−44/48C−6F + G61MPV−60C−090 3 37L51 − order separately

37,400 11.0 19.15 13.60 2745 6 CX34−50/60C−6F + G61MPV−36C−090 3 37L51 − order separately

37,400 11.0 18.50 13.00 2870 6 CX34−38A−6F + G60UHV−36A−070 Factory Installed TXV

37,600 11.0 18.90 13.50 2785 6 CX34−38B−6F + G60UHV−36B−090 Factory Installed TXV

38,500 11.3 19.35 13.75 2795 6 CX34−50/60C−6F + G60UHV−60C−090 3 37L51 − order separately

38,500 11.3 19.30 13.75 2795 6 CX34−49C−6F + G60UHV−60C−090 3 37L51 − order separately

39,000 11.4 19.35 13.25 2945 6 CX34−49C−6F + G61MPV−60C−110 3 37L51 − order separately

39,000 11.4 19.20 13.20 2950 6 CX34−49C−6F + G61MPV−60C−090 3 37L51 − order separately

Air Handlers 36,200 10.6 17.30 12.75 2840 5 CBX32M−030 (Multi−Position) Factory Installed TXV

36,200 10.6 17.25 12.55 2885 5 CBX32M−036 (Multi−Position) Factory Installed TXV

36,200 10.6 17.25 12.55 2885 5 CBX32M−042 (Multi−Position) 3 37L51 − order separately

36,400 10.7 18.90 13.15 2765 6 CBX32MV−024/030 (Multi−Position) Factory Installed TXV

36,800 10.8 19.25 13.35 2755 6 CBX32MV−036 (Multi−Position) Factory Installed TXV

37,400 11.0 17.15 13.10 2855 5 CBX32M−048 (Multi−Position) 3 37L51 − order separately

38,000 11.1 20.00 14.00 2695 4, 6 CBX32MV−048 (Multi−Position) 3 37L51 − order separately1 Sound Rating Number rated in accordance + test conditions included in ARI Standard 270.2 Certified in accordance + USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air + 25 ft. (7.6 m) of connecting refrigerant lines.3 Factory installed expansion valve or RFCIV device on indoor unit MUST be replaced with valve specified.4 Most popular air handler.5 Blower must be capable of time−off blower delay, high−speed cooling/heating operation during second−stage compressor operation, and low−speed cooling/heating operation

during first−stage compressor operation. Time Delay Relay Kit (58M81) and Indoor Blower Speed Relay Kit (40K58) are recommend for field installation.6 Blower control must be set for a time−off blower delay.

Page 12: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 12

ARI RATINGS − R−22 INDOOR COILS / AIR HANDLERS 3 Ton

NOTE − Match−ups are sorted by: Cooling Capacity then SEER

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No. Expansion Device

XC21−0363 Ton

Up-FlowIndoor Coils

35,200 10.3 16.05 12.05 2925 4 C33−42B 3 37L51 − order separately3 Ton(71 dB)

Indoor Coils35,200 10.3 16.05 12.05 2925 4 C33−36A/B/C 3 37L51 − order separately( )

36,200 10.6 16.40 12.35 2930 4 C33−48B/C 3 37L51 − order separately

36,200 10.6 16.35 12.35 2930 4 C33−44C 3 37L51 − order separately

36,600 10.7 16.60 12.45 2935 4 C33−38A/B 3 37L51 − order separately

36,600 10.7 16.55 12.45 2935 4 C33−50/60C 3 37L51 − order separately

36,600 10.7 16.40 12.45 2935 4 C33−49C 3 37L51 − order separately

Down-FlowIndoor Coils

35,800 10.5 16.25 12.20 2930 4 CR26−48N/W−F 3 37L51 − order separatelyIndoor Coils

36,000 10.6 16.45 12.30 2930 4 CR26−36N/W−F 3 37L51 − order separately

HorizontalIndoor Coils

35,400 10.4 16.20 12.10 2925 4 CH33−36A/B/C−2F 3 37L51 − order separatelyIndoor Coils

35,400 10.4 16.00 12.10 2925 4 CH23−41 3 37L51 − order separately

36,200 10.6 16.40 12.35 2935 4 CH23−51 3 37L51 − order separately

36,400 10.7 16.55 12.40 2935 4 CH33−42B−2F 3 37L51 − order separately

37,000 10.8 16.75 12.60 2940 4 CH33−44/48B−2F 3 37L51 − order separately

Air Handlers 36,200 10.6 17.30 12.75 2840 4 CB30M−31 (Multi−Position) 3 37L51 − order separately

36,200 10.6 17.25 12.55 2885 4 CB30M−41 (Multi−Position) 3 37L51 − order separately

36,200 10.6 17.25 12.55 2885 4 CB30M−46 (Multi−Position) 3 37L51 − order separately

36,400 10.7 17.40 12.80 2845 4 CB30U−31 (Up−Flow) 3 37L51 − order separately

36,400 10.7 17.35 12.60 2885 4 CB30U−41/46 (Up−Flow) 3 37L51 − order separately

36,800 10.8 19.25 13.35 2755 5 CB31MV−41 (Multi−Position) 3 37L51 − order separately

37,400 11.0 17.15 13.10 2855 4 CB30M−51 (Multi−Position) 3 37L51 − order separately

37,400 11.0 17.15 13.10 2855 4 CB30U−51 (Up−Flow) 3 37L51 − order separately

38,000 11.1 20.00 14.00 2695 5 CB31MV−51 (Multi−Position) 3 37L51 − order separately

NOTE − Ratings for all C33 coils include all cased and uncased coils.1 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.2 Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air with 25 ft. (7.6 m) of connecting refrigerant lines.3 Factory installed expansion valve or RFCIV device on indoor unit MUST be replaced with valve specified.4 Blower must be capable of time−off blower delay, high−speed cooling/heating operation during second−stage compressor operation, and low−speed cooling/heating operation

during first−stage compressor operation. Time Delay Relay Kit (58M81) and Indoor Blower Speed Relay Kit (40K58) are recommend for field installation.5 Blower control must be set for a time−off blower delay.

Page 13: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 13

ARI RATINGS − R−22 INDOOR COILS + FURNACES 3 Ton

NOTE − Match−ups are sorted by: Cooling Capacity then SEER

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No. Expansion Device

XC21−0363 Ton

Up-FlowIndoor Coils

35,600 10.4 18.10 12.55 2835 4 C33−36B + G61MPV−36B−070 3 37L51 − order separately3 Ton(71 dB)

Indoor Coils+ Furnaces 35,600 10.4 18.10 12.55 2835 4 C33−42B + G61MPV−36B−070 3 37L51 − order separately( )

35,800 10.5 18.20 12.65 2835 4 C33−36A + G60UHV−36A−070 3 37L51 − order separately

36,000 10.6 18.55 13.00 2775 4 C33−36B + G60UHV−36B−090 3 37L51 − order separately

36,000 10.6 18.55 13.00 2775 4 C33−42B + G60UHV−36B−090 3 37L51 − order separately

36,800 10.8 18.50 13.00 2845 4 C33−48B + G61MPV−36B−070 3 37L51 − order separately

37,200 10.9 19.00 13.55 2745 4 C33−48B + G60UHV−36B−090 3 37L51 − order separately

37,200 10.9 18.70 13.10 2845 4 C33−38B + G61MPV−36B−070 3 37L51 − order separately

37,400 11.0 19.20 13.45 2780 4 C33−48C + G61MPV−60C−090 3 37L51 − order separately

37,400 11.0 19.15 13.60 2745 4 C33−50/60C + G61MPV−36C−090 3 37L51 − order separately

37,400 11.0 18.50 13.00 2870 4 C33−38A + G60UHV−36A−070 3 37L51 − order separately

37,600 11.0 18.90 13.50 2785 4 C33−38B + G60UHV−36B−090 3 37L51 − order separately

38,500 11.3 19.35 13.75 2795 4 C33−50/60C + G60UHV−60C−090 3 37L51 − order separately

38,500 11.3 19.30 13.75 2795 4 C33−49C + G60UHV−60C−090 3 37L51 − order separately

39,000 11.4 19.35 13.25 2945 4 C33−49C + G61MPV−60C−110 3 37L51 − order separately

39,000 11.4 19.20 13.20 2950 4 C33−49C + G61MPV−60C−090 3 37L51 − order separately

Down-FlowIndoor Coils

36,400 10.7 18.85 13.00 2805 4 CR26−36N−2F + G60DFV−36B−090 3 37L51 − order separatelyIndoor Coils+ Furnaces 36,400 10.7 18.70 13.20 2755 4 CR26−48N−2F + G60DFV−36B−090 3 37L51 − order separately

HorizontalIndoor Coils

35,400 10.4 17.80 12.35 2865 4 CH33−36A−2F + G61MPV−36A−070 3 37L51 − order separatelyIndoor Coils+ Furnaces 35,600 10.4 18.00 12.50 2845 4 CH33−36B−2F + G61MPV−36B−090 3 37L51 − order separately

35,600 10.4 18.00 12.50 2845 4 CH33−36B−2F + G61MPV−36B−070 3 37L51 − order separately

35,600 10.4 17.90 12.45 2855 4 CH33−36A−2F + G60UHV−36A−070 3 37L51 − order separately

36,000 10.6 18.50 13.00 2770 4 CH33−36B−2F + G60UHV−36B−090 3 37L51 − order separately

36,400 10.7 18.70 13.25 2750 4 CH33−36C−2F + G61MPV−36C−090 3 37L51 − order separately

36,600 10.7 18.55 12.90 2840 4 CH33−42B−2F + G61MPV−36B−070 3 37L51 − order separately

37,000 10.8 19.00 13.30 2780 4 CH33−42B−2F + G60UHV−36B−090 3 37L51 − order separately

37,400 11.0 18.75 13.30 2815 4 CH33−44/48B−2F + G61MPV−36B−070 3 37L51 − order separately

37,800 11.1 19.25 13.75 2750 4 CH33−44/48B−2F + G60UHV−36B−090 3 37L51 − order separately

NOTE − Ratings for all C33 coils include all cased and uncased coils.1 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.2 Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air with 25 ft. (7.6 m) of connecting refrigerant lines.3 Factory installed expansion valve or RFCIV device on indoor unit MUST be replaced with valve specified.4 Blower control must be set for a time−off blower delay.

Page 14: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 14

ARI RATINGS − R−410A INDOOR COILS / INDOOR COILS + FURNACES / AIR HANDLERS 4 Ton

NOTE − Match−ups are sorted by: Cooling Capacity then SEER

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No. Expansion Device

XC21−0484 Ton

Up-FlowIndoor Coils

47,500 13.9 15.30 12.00 3965 4 CX34−44/48B/C−6F Factory Installed TXV4 Ton(73 dB)

Indoor Coils48,500 14.2 15.45 12.20 3970 4 CX34−50/60C−6F Factory Installed TXV( )

48,500 14.2 15.40 12.20 3975 4 CX34−49C−6F Factory Installed TXV

49,000 14.4 15.70 12.30 3985 4 CX34−60D−6F Factory Installed TXV

49,500 14.5 15.75 12.40 3990 4 CX34−62D−6F Factory Installed TXV

Up-FlowIndoor Coils

48,000 14.1 16.75 12.45 3850 5 CX34−44/48C + G61MPV−60C−110 Factory Installed TXVIndoor Coils+ Furnaces 48,000 14.1 16.70 12.35 3880 5 CX34−44/48C + G61MPV−60C−090 Factory Installed TXV

48,500 14.2 17.00 12.60 3855 5 CX34−44/48C + G60UHV−60C−090 Factory Installed TXV

48,500 14.2 17.00 12.60 3855 5 CX34−50/60C + G61MPV−60C−110 Factory Installed TXV

48,500 14.2 16.95 12.50 3885 5 CX34−50/60C + G61MPV−60C−090 Factory Installed TXV

48,500 14.2 16.85 12.50 3885 5 CX34−49C + G61MPV−60C−090 Factory Installed TXV

49,000 14.4 17.15 12.70 3865 5 CX34−50/60C + G60UHV−60C−090 Factory Installed TXV

49,000 14.4 17.05 12.70 3860 5 CX34−49C + G60UHV−60C−090 Factory Installed TXV

49,500 14.5 17.55 13.00 3810 5 CX34−60D + G61MPV−60D−135 Factory Installed TXV

50,000 14.7 17.65 13.10 3815 5 CX34−62D + G61MPV−60D−135 Factory Installed TXV

50,500 14.8 17.75 13.20 3820 5 CX34−60D + G60UHV−60D−135 Factory Installed TXV

51,000 14.9 17.85 13.35 3825 5 CX34−62D + G60UHV−60D−135 Factory Installed TXV

Air Handlers 46,000 13.5 16.80 11.85 3880 5 CBX32MV−036 (Multi−Position) Factory Installed TXV

46,000 13.5 15.90 12.00 3830 4 CBX32M−036 (Multi−Position) Factory Installed TXV

46,000 13.5 15.90 12.00 3830 4 CBX32M−042 (Multi−Position) Factory Installed TXV

49,000 14.4 17.80 12.80 3870 3, 5 CBX32MV−048 (Multi−Position) Factory Installed TXV

49,000 14.4 16.05 12.60 3890 4 CBX32M−048 (Multi−Position) Factory Installed TXV

49,000 14.4 16.05 12.60 3895 4 CBX32M−060 (Multi−Position) Factory Installed TXV

49,500 14.5 18.10 13.10 3760 5 CBX32MV−068 (Multi−Position) Factory Installed TXV

49,500 14.5 17.70 12.75 3875 5 CBX32MV−060 (Multi−Position) Factory Installed TXV

1 Sound Rating Number rated in accordance + test conditions included in ARI Standard 270.2 Certified in accordance + USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air + 25 ft. (7.6 m) of connecting refrigerant lines.3 Most popular air handler.4 Blower must be capable of time−off blower delay, high−speed cooling/heating operation during second−stage compressor operation, and low−speed cooling/heating operation

during first−stage compressor operation. Time Delay Relay Kit (58M81) and Indoor Blower Speed Relay Kit (40K58) are recommend for field installation.5 Blower control must be set for a time−off blower delay.

Page 15: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 15

ARI RATINGS − R−22 INDOOR COILS / AIR HANDLERS 4 Ton

NOTE − Match−ups are sorted by: Cooling Capacity then SEER

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No. Expansion Device

XC21−0484 Ton

Up-FlowIndoor Coils

47,500 13.9 15.30 12.00 3965 4 C33−48B/C 3 39L72 − order separately4 Ton(73 dB)

Indoor Coils48,500 14.2 15.45 12.20 3970 4 C33−50/60C 3 39L72 − order separately( )

48,500 14.2 15.40 12.20 3975 4 C33−49C 3 39L72 − order separately

49,000 14.4 15.70 12.30 3985 4 C33−60D 3 39L72 − order separately

49,500 14.5 15.75 12.40 3990 4 C33−62D 3 39L72 − order separately

Down-FlowIndoor Coils

46,500 13.6 14.90 11.75 3955 4 CR26−48N/W−F 3 39L72 − order separatelyIndoor Coils

48,500 14.2 15.45 12.20 3975 4 CR26−60N/W−F 3 39L72 − order separately

HorizontalIndoor Coils

47,000 13.8 15.00 11.85 3970 4 CH23−51 3 39L72 − order separatelyIndoor Coils

47,500 13.9 15.20 12.00 3980 4 CH23−65 3 39L72 − order separately

48,500 14.2 15.50 12.15 3985 4 CH33−44/48B−2F 3 39L72 − order separately

49,000 14.4 15.55 12.30 3990 4 CH33−60D−2F 3 39L72 − order separately

49,000 14.4 15.60 12.30 3990 4 CH33−62D−2F 3 39L72 − order separately

49,500 14.5 15.75 12.40 3995 4 CH33−50/60C−2F 3 39L72 − order separately

50,000 14.7 15.80 12.50 4000 4 CH23−68 3 39L72 − order separately

Air Handlers 46,000 13.5 16.80 11.85 3880 5 CB31MV−41 (Multi−Position) 3 39L72 − order separately

46,000 13.5 15.90 12.00 3830 4 CB30M−41 (Multi−Position) 3 39L72 − order separately

46,000 13.5 15.90 12.00 3830 4 CB30M−46 (Multi−Position) 3 39L72 − order separately

46,500 13.6 15.60 12.15 3835 4 CB30U−41/46 (Up−Flow) 3 39L72 − order separately

48,500 14.2 15.90 12.40 3905 4 CB30U−51 (Up−Flow) 3 39L72 − order separately

49,000 14.4 16.55 12.60 3895 4 CB30U−65 (Up−Flow) 3 39L72 − order separately

49,000 14.4 16.05 12.60 3890 4 CB30M−51 (Multi−Position) 3 39L72 − order separately

49,000 14.4 16.05 12.60 3895 4 CB30M−65 (Multi−Position) 3 39L72 − order separately

49,000 14.4 17.80 12.80 3870 5 CB31MV−51 (Multi−Position) 3 39L72 − order separately

49,500 14.5 17.70 12.75 3875 5 CB31MV−65 (Multi−Position) 3 39L72 − order separately

NOTE − Ratings for all C33 coils include all cased and uncased coils.1 Sound Rating Number rated in accordance + test conditions included in ARI Standard 270.2 Certified in accordance + USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air + 25 ft. (7.6 m) of connecting refrigerant lines.3 Factory installed expansion valve or RFCIV device on indoor unit MUST be replaced with valve specified.4 Blower must be capable of time−off blower delay, high−speed cooling/heating operation during second−stage compressor operation, and low−speed cooling/heating operation

during first−stage compressor operation. Time Delay Relay Kit (58M81) and Indoor Blower Speed Relay Kit (40K58) are recommend for field installation.5 Blower control must be set for a time−off blower delay.

Page 16: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 16

ARI RATINGS − R−22 INDOOR COILS + FURNACES 4 Ton

NOTE − Match−ups are sorted by: Cooling Capacity then SEER

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No. Expansion Device

XC21−0484 Ton

Up-FlowIndoor Coils

48,000 14.1 16.75 12.45 3850 4 C33−48C + G61MPV−60C−110 3 39L72 − order separately4 Ton(73 dB)

Indoor Coils+ Furnaces 48,000 14.1 16.70 12.35 3880 4 C33−48C + G61MPV−60C−090 3 39L72 − order separately( )

48,500 14.2 17.00 12.60 3855 4 C33−48C + G60UHV−60C−090 3 39L72 − order separately

48,500 14.2 17.00 12.60 3855 4 C33−50/60C + G61MPV−60C−110 3 39L72 − order separately

48,500 14.2 16.95 12.50 3885 4 C33−50/60C + G61MPV−60C−090 3 39L72 − order separately

48,500 14.2 16.85 12.50 3885 4 C33−49C + G61MPV−60C−090 3 39L72 − order separately

49,000 14.4 17.15 12.70 3865 4 C33−50/60C + G60UHV−60C−090 3 39L72 − order separately

49,000 14.4 17.05 12.70 3860 4 C33−49C + G60UHV−60C−090 3 39L72 − order separately

49,500 14.5 17.55 13.00 3810 4 C33−60D + G61MPV−60D−135 3 39L72 − order separately

50,000 14.7 17.65 13.10 3815 4 C33−62D + G61MPV−60D−135 3 39L72 − order separately

50,500 14.8 17.75 13.20 3820 4 C33−60D + G60UHV−60D−135 3 39L72 − order separately

51,000 14.9 17.85 13.35 3825 4 C33−62D + G60UHV−60D−135 3 39L72 − order separately

Down-FlowIndoor Coils

47,000 13.8 16.40 12.25 3835 4 CR26−48N−F + G61MPV−60C−110 3 39L72 − order separatelyIndoor Coils+ Furnaces 47,500 13.9 16.60 12.35 3840 4 CR26−48N−F + G60DFV−60C−090 3 39L72 − order separately

49,000 14.4 17.35 12.90 3800 4 CR26−60W−F + G61MPV−60D−135 3 39L72 − order separately

49,500 14.5 17.50 13.00 3825 4 CR26−60W−F + G60DFV−60D−135 3 39L72 − order separately

HorizontalIndoor Coils

48,000 14.1 16.75 12.45 3850 4 CH23−51 + G60UHV−60C−090 3 39L72 − order separatelyIndoor Coils+ Furnaces 48,500 14.2 17.00 12.50 3885 4 CH33−48C−2F + G61MPV−60C−090 3 39L72 − order separately

49,000 14.4 17.20 12.70 3865 4 CH33−48C−2F + G60UHV−60C−090 3 39L72 − order separately

49,000 14.4 17.05 12.60 3890 4 CH33−50/60C−2F + G61MPV−60C−090 3 39L72 − order separately

49,500 14.5 17.50 13.00 3810 4 CH33−60D−2F + G61MPV−60D−135 3 39L72 − order separately

49,500 14.5 17.50 13.00 3810 4 CH33−62D−2F + G61MPV−60D−135 3 39L72 − order separately

49,500 14.5 17.25 12.80 3870 4 CH33−50/60C−2F + G60UHV−60C−090 3 39L72 − order separately

50,000 14.7 17.70 13.10 3815 4 CH33−60D−2F + G60UHV−60D−135 3 39L72 − order separately

50,500 14.8 17.75 13.20 3820 4 CH33−62D−2F + G60UHV−60D−135 3 39L72 − order separately

NOTE − Ratings for all C33 coils include all cased and uncased coils.1 Sound Rating Number rated in accordance + test conditions included in ARI Standard 270.2 Certified in accordance + USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air + 25 ft. (7.6 m) of connecting refrigerant lines.3 Factory installed expansion valve or RFCIV device on indoor unit MUST be replaced with valve specified.4 Blower control must be set for a time−off blower delay.

Page 17: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 17

ARI RATINGS − R−410A INDOOR COILS / INDOOR COILS + FURNACES / AIR HANDLERS 5 Ton

NOTE − Match−ups are sorted by: Cooling Capacity then SEER

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No. Expansion Device

XC21−0605 Ton

Up-FlowIndoor Coils

56,500 16.6 14.55 11.20 5050 4 CX34−44/48B/C−6F Factory Installed TXV5 Ton(73 dB)

Indoor Coils57,500 16.9 14.75 11.35 5060 4 CX34−50/60C−6F Factory Installed TXV( )

58,000 17.0 14.80 11.45 5075 4 CX34−49C−6F Factory Installed TXV

59,000 17.3 15.00 11.65 5075 4 CX34−60D−6F Factory Installed TXV

59,500 17.4 15.15 11.70 5085 4 CX34−62D−6F Factory Installed TXV

60,000 17.6 15.40 11.80 5090 4 CX34−62C−6F Factory Installed TXV

Up-FlowIndoor Coils

56,500 16.6 14.70 10.55 5355 5 CX34−44/48C−6F + G61MPV−60C−090 Factory Installed TXVIndoor Coils+ Furnaces 57,000 16.7 15.60 11.25 5060 5 CX34−44/48C−6F + G60UHV−60C−090 Factory Installed TXV

57,500 16.9 14.85 10.70 5375 5 CX34−50/60C−6F + G61MPV−60C−090 Factory Installed TXV

58,000 17.0 15.70 11.45 5060 5 CX34−50/60C−6F + G60UHV−60C−090 Factory Installed TXV

58,500 17.1 15.70 11.50 5090 5 CX34−49C−6F + G60UHV−60C−090 Factory Installed TXV

58,500 17.1 14.85 10.85 5390 5 CX34−49C−6F + G61MPV−60C−090 Factory Installed TXV

60,000 17.6 16.30 11.95 5025 5 CX34−60D−6F + G60UHV−60D−135 Factory Installed TXV

60,000 17.6 15.45 11.35 5275 5 CX34−60D−6F + G61MPV−60D−135 Factory Installed TXV

60,500 17.7 16.50 12.05 5030 5 CX34−62D−6F + G60UHV−60D−135 Factory Installed TXV

60,500 17.7 15.75 11.45 5280 5 CX34−62D−6F + G61MPV−60D−135 Factory Installed TXV

60,500 17.7 15.55 11.15 5415 5 CX34−62C−6F + G61MPV−60C Factory Installed TXV

61,000 17.9 16.35 11.95 5105 5 CX34−62C−6F + G60UHV−60C−090 Factory Installed TXV

Air Handlers 58,000 17.0 15.40 11.35 5110 4 CBX32M−048 (Multi−Position) Factory Installed TXV

58,500 17.1 16.65 11.90 4915 5 CBX32MV−048 (Multi−Position) Factory Installed TXV

58,500 17.1 15.50 11.45 5120 4 CBX32M−060 (Multi−Position) Factory Installed TXV

59,000 17.3 16.80 12.20 4860 3, 5 CBX32MV−060 (Multi−Position) Factory Installed TXV

59,500 17.4 17.00 12.50 4775 5 CBX32MV−068 (Multi−Position) Factory Installed TXV

1 Sound Rating Number rated in accordance + test conditions included in ARI Standard 270.2 Certified in accordance + USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air + 25 ft. (7.6 m) of connecting refrigerant lines.3 Most popular air handler.4 Blower must be capable of time−off blower delay, high−speed cooling/heating operation during second−stage compressor operation, and low−speed cooling/heating operation

during first−stage compressor operation. Time Delay Relay Kit (58M81) and Indoor Blower Speed Relay Kit (40K58) are recommend for field installation.5 Blower control must be set for a time−off blower delay.

Page 18: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

XC21 − 2 to 5 Ton Air Conditioner / Page 18

ARI RATINGS − R−22 INDOOR COILS / INDOOR COILS + FURNACES / AIR HANDLERS 5 Ton

NOTE − Match−ups are sorted by: Cooling Capacity then SEER

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No. Expansion Device

XC21−0605 T

Up-FlowI d C il

56,500 16.6 14.55 11.20 5050 4 C33−48B/C 3 39L72 − order separately5 Ton(73 dB)

pIndoor Coils

57,500 16.9 14.75 11.35 5060 4 C33−50/60C 3 39L72 − order separately(73 dB)58,000 17.0 14.80 11.45 5075 4 C33−49C 3 39L72 − order separately

59,000 17.3 15.00 11.65 5075 4 C33−60D 3 39L72 − order separately

59,500 17.4 15.15 11.70 5085 4 C33−62D 3 39L72 − order separately

60,000 17.6 15.40 11.80 5090 4 C33−62C 3 39L72 − order separately

Up-FlowI d C il

56,500 16.6 14.70 10.55 5355 5 C33−48C + G61MPV−60C−090 3 39L72 − order separatelypIndoor Coils+ Furnaces 57,000 16.7 15.60 11.25 5060 5 C33−48C + G60UHV−60C−090 3 39L72 − order separately+ Furnaces

57,500 16.9 14.85 10.70 5375 5 C33−50/60C + G61MPV−60C−090 3 39L72 − order separately

58,000 17.0 15.70 11.45 5060 5 C33−50/60C + G60UHV−60C−090 3 39L72 − order separately

58,500 17.1 15.70 11.50 5090 5 C33−49C + G60UHV−60C−090 3 39L72 − order separately

58,500 17.1 14.85 10.85 5390 5 C33−49C + G61MPV−60C−090 3 39L72 − order separately

60,000 17.6 16.30 11.95 5025 5 C33−60D + G60UHV−60D−135 3 39L72 − order separately

60,000 17.6 15.45 11.35 5275 5 C33−60D + G61MPV−60D−135 3 39L72 − order separately

60,500 17.7 16.50 12.05 5030 5 C33−62D + G60UHV−60D−135 3 39L72 − order separately

60,500 17.7 15.75 11.45 5280 5 C33−62D + G61MPV−60D−135 3 39L72 − order separately

60,500 17.7 15.55 11.15 5415 5 C33−62C + G61MPV−60C−110 3 39L72 − order separately

61,000 17.9 16.35 11.95 5105 5 C33−62C + G60UHV−60C−090 3 39L72 − order separately

Down-FlowI d C il

55,000 16.1 14.20 10.95 5020 4 CR26−48N/W−F 3 39L72 − order separatelyIndoor Coils

57,000 16.7 14.80 11.25 5060 4 CR26−60N/W−F 3 39L72 − order separately

Down-FlowI d C il

55,000 16.1 14.40 10.30 5330 5 CR26−48N−F + G61MPV−60C−110 3 39L72 − order separatelyIndoor Coils+ Furnaces 56,000 16.4 15.35 10.85 5150 5 CR26−48N−F + G60DFV−60C−110 3 39L72 − order separately+ Furnaces

58,000 17.0 16.15 11.65 4980 5 CR26−60W−F + G60DFV−60D−135 3 39L72 − order separately

58,000 17.0 15.20 11.10 5225 5 CR26−60W−F + G61MPV−60D−135 3 39L72 − order separately

HorizontalI d C il

56,000 16.4 14.45 11.15 5030 4 CH23−51 3 39L72 − order separatelyIndoor Coils

57,000 16.7 14.60 11.30 5055 4 CH23−65 3 39L72 − order separately

58,000 17.0 14.95 11.45 5070 4 CH33−60D−2F 3 39L72 − order separately

59,000 17.3 15.05 11.60 5080 4 CH33−50/60C−2F 3 39L72 − order separately

59,000 17.3 15.00 11.60 5080 4 CH33−62D−2F 3 39L72 − order separately

59,500 17.4 15.15 11.70 5085 4 CH23−68 3 39L72 − order separately

HorizontalI d C il

56,500 16.6 15.35 11.15 5060 5 CH23−51 + G60UHV−60C−090 3 39L72 − order separatelyIndoor Coils+ Furnaces 57,000 16.7 15.55 11.25 5075 5 CH23−65 + G60UHV−60C−090 3 39L72 − order separately+ Furnaces

58,000 17.0 14.80 10.70 5420 5 CH33−50/60C−2F + G61MPV−60C−090 3 39L72 − order separately

58,500 17.1 15.85 11.50 5085 5 CH33−50/60C−2F + G60UHV−60C−090 3 39L72 − order separately

59,000 17.3 16.25 11.75 5015 5 CH33−60D−2F + G60UHV−60D−135 3 39L72 − order separately

59,000 17.3 15.40 11.15 5295 5 CH33−60D−2F + G61MPV−60D−135 3 39L72 − order separately

60,000 17.6 16.30 11.95 5030 5 CH33−62D−2F + G60UHV−60D−135 3 39L72 − order separately

60,000 17.6 15.50 11.30 5315 5 CH33−62D−2F + G61MPV−60D−135 3 39L72 − order separately

60,500 17.7 16.20 11.55 5245 5 CH23−68 + G60UHV−60C−110 3 39L72 − order separately

Air Handlers 57,000 16.7 15.20 11.55 4940 4 CB30U−51 (Up−Flow) 3 39L72 − order separately

58,000 17.0 15.40 11.35 5110 4 CB30M−51 (Multi−Position) 3 39L72 − order separately

58,500 17.1 16.65 11.90 4915 5 CB31MV−51 (Multi−Position) 3 39L72 − order separately

58,500 17.1 15.50 11.45 5120 4 CB30M−65 (Multi−Position) 3 39L72 − order separately

59,000 17.3 16.80 12.20 4860 5 CB31MV−65 (Multi−Position) 3 39L72 − order separately

59,000 17.3 15.40 11.55 5115 4 CB30U−65 (Up−Flow) 3 39L72 − order separately

NOTE − Ratings for all C33 coils include all cased and uncased coils.1 Sound Rating Number rated in accordance + test conditions included in ARI Standard 270.2 Certified in accordance + USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air + 25 ft. (7.6 m) of connecting refrigerant lines.3 Factory installed expansion valve or RFCIV device on indoor unit MUST be replaced with valve specified.4 Blower must be capable of time−off blower delay, high−speed cooling/heating operation during second−stage compressor operation, and low−speed cooling/heating operation

during first−stage compressor operation. Time Delay Relay Kit (58M81) and Indoor Blower Speed Relay Kit (40K58) are recommend for field installation.5 Blower control must be set for a time−off blower delay.

Page 19: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 19

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−18/24A/B/C−6F] [C33−24A/B/C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT t

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTemperat

ure

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbure

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 18.1 5.3 .77 .72 .84 .95 17.4 5.1 .92 .73 .85 .97 16.5 4.8 1.10 .74 .87 .99 15.6 4.6 1.31 .76 .90 1.00

63�F(17�C)

560 265 19.1 5.6 .77 .75 .88 1.00 18.3 5.4 .93 .76 .90 1.00 17.4 5.1 1.10 .78 .93 1.00 16.4 4.8 1.30 .80 .96 1.00(17�C)

660 310 19.9 5.8 .77 .78 .92 1.00 19.0 5.6 .92 .79 .95 1.00 18.1 5.3 1.10 .81 .97 1.00 17.1 5.0 1.30 .84 1.00 1.00

67�F460 215 19.1 5.6 .77 .58 .69 .80 18.3 5.4 .92 .58 .70 .82 17.5 5.1 1.10 .59 .72 .83 16.6 4.9 1.30 .60 .73 .86

67�F(19�C)

560 265 20.2 5.9 .77 .60 .72 .85 19.4 5.7 .93 .60 .74 .86 18.5 5.4 1.10 .61 .75 .88 17.4 5.1 1.31 .62 .77 .92(19�C)

660 310 21.0 6.2 .77 .61 .75 .89 20.2 5.9 .93 .62 .77 .91 19.1 5.6 1.10 .63 .79 .93 18.1 5.3 1.30 .65 .81 .96

71�F460 215 20.0 5.9 .77 .45 .56 .67 19.2 5.6 .93 .46 .57 .68 18.4 5.4 1.10 .45 .58 .69 17.4 5.1 1.30 .46 .59 .70

71�F(22�C)

560 265 21.2 6.2 .77 .46 .58 .70 20.4 6.0 .93 .46 .59 .71 19.4 5.7 1.10 .46 .60 .72 18.4 5.4 1.30 .47 .61 .74(22�C)

660 310 22.0 6.4 .78 .47 .60 .73 21.2 6.2 .93 .47 .61 .74 20.2 5.9 1.10 .47 .62 .76 19.1 5.6 1.30 .48 .63 .78

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−18/24A/B/C−6F] [C33−24A/B/C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 23.0 6.7 1.29 .72 .84 .95 22.0 6.4 1.50 .73 .85 .97 20.8 6.1 1.74 .74 .88 .99 19.6 5.7 2.00 .76 .90 1.00

63�F(17�C)

800 380 24.4 7.2 1.29 .77 .91 1.00 23.4 6.9 1.50 .78 .93 1.00 22.2 6.5 1.74 .80 .96 1.00 20.8 6.1 2.01 .82 .98 1.00(17�C)

1000 470 25.6 7.5 1.29 .81 .97 1.00 24.4 7.2 1.51 .83 .99 1.00 23.0 6.7 1.74 .85 1.00 1.00 21.8 6.4 2.01 .89 1.00 1.00

67�F600 285 24.0 7.0 1.29 .58 .69 .80 23.0 6.7 1.50 .59 .71 .82 21.8 6.4 1.74 .59 .72 .84 20.6 6.0 2.01 .60 .74 .87

67�F(19�C)

800 380 25.8 7.6 1.29 .61 .74 .87 24.6 7.2 1.50 .62 .76 .89 23.2 6.8 1.74 .63 .78 .92 21.8 6.4 2.02 .64 .80 .95(19�C)

1000 470 26.8 7.9 1.29 .63 .79 .94 25.6 7.5 1.51 .65 .81 .96 24.2 7.1 1.75 .66 .83 .99 22.6 6.6 2.02 .68 .86 1.00

71�F600 285 25.2 7.4 1.29 .45 .56 .67 24.0 7.0 1.50 .45 .57 .68 22.8 6.7 1.74 .45 .58 .70 21.6 6.3 2.01 .46 .59 .71

71�F(22�C)

800 380 27.0 7.9 1.30 .46 .59 .72 25.8 7.6 1.51 .47 .60 .74 24.4 7.2 1.75 .47 .61 .75 23.0 6.7 2.02 .48 .63 .78(22�C)

1000 470 28.2 8.3 1.30 .48 .62 .77 26.8 7.9 1.51 .48 .63 .79 25.4 7.4 1.75 .49 .65 .81 23.8 7.0 2.03 .49 .67 .84

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−25A/B] [C33−25A/B]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 18.7 5.5 .77 .71 .84 .95 17.9 5.2 .92 .73 .85 .97 17.0 5.0 1.10 .74 .87 .99 16.0 4.7 1.31 .76 .90 1.00

63�F(17�C)

560 265 19.8 5.8 .77 .75 .88 1.00 18.9 5.5 .92 .76 .90 1.00 17.9 5.2 1.09 .78 .93 1.00 16.8 4.9 1.30 .80 .96 1.00(17�C)

660 310 20.6 6.0 .77 .78 .93 1.00 19.7 5.8 .93 .80 .96 1.00 18.6 5.5 1.10 .82 .98 1.00 17.5 5.1 1.30 .84 1.00 1.00

67�F460 215 20.0 5.9 .77 .57 .69 .80 19.2 5.6 .93 .58 .70 .81 18.2 5.3 1.10 .58 .71 .83 17.2 5.0 1.30 .60 .73 .86

67�F(19�C)

560 265 21.2 6.2 .78 .59 .72 .84 20.2 5.9 .93 .60 .74 .87 19.2 5.6 1.10 .61 .75 .89 18.1 5.3 1.30 .62 .77 .92(19�C)

660 310 22.0 6.4 .78 .61 .75 .89 21.0 6.2 .93 .62 .77 .92 19.9 5.8 1.10 .63 .79 .94 18.7 5.5 1.30 .65 .82 .97

71�F460 215 21.2 6.2 .77 .45 .56 .66 20.4 6.0 .93 .45 .56 .67 19.4 5.7 1.10 .45 .57 .68 18.3 5.4 1.30 .45 .58 .70

71�F(22�C)

560 265 22.4 6.6 .78 .45 .57 .69 21.4 6.3 .93 .45 .58 .71 20.4 6.0 1.10 .46 .60 .72 19.3 5.7 1.30 .46 .61 .75(22�C)

660 310 23.4 6.9 .78 .46 .60 .73 22.4 6.6 .93 .46 .61 .75 21.2 6.2 1.10 .47 .62 .77 20.0 5.9 1.30 .47 .63 .79

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−25A/B] [C33−25A/B]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 23.8 7.0 1.29 .72 .84 .96 22.6 6.6 1.50 .73 .86 .98 21.4 6.3 1.74 .74 .88 1.00 20.0 5.9 2.02 .76 .91 1.00

63�F(17�C)

800 380 25.4 7.4 1.29 .77 .92 1.00 24.2 7.1 1.50 .79 .94 1.00 22.8 6.7 1.74 .81 .97 1.00 21.4 6.3 2.02 .84 1.00 1.00(17�C)

1000 470 26.6 7.8 1.29 .83 .99 1.00 25.2 7.4 1.51 .85 1.00 1.00 24.0 7.0 1.75 .87 1.00 1.00 22.6 6.6 2.02 .90 1.00 1.00

67�F600 285 25.2 7.4 1.29 .58 .69 .80 24.0 7.0 1.50 .58 .70 .82 22.8 6.7 1.74 .59 .72 .84 21.4 6.3 2.02 .60 .74 .87

67�F(19�C)

800 380 26.8 7.9 1.30 .61 .75 .88 25.6 7.5 1.51 .62 .76 .91 24.2 7.1 1.75 .63 .79 .94 22.6 6.6 2.02 .64 .81 .97(19�C)

1000 470 28.0 8.2 1.30 .64 .80 .96 26.6 7.8 1.51 .65 .82 .98 25.0 7.3 1.74 .67 .85 1.00 23.4 6.9 2.02 .69 .88 1.00

71�F600 285 26.6 7.8 1.30 .45 .56 .67 25.4 7.4 1.51 .45 .57 .68 24.0 7.0 1.74 .45 .57 .69 22.6 6.6 2.02 .45 .59 .71

71�F(22�C)

800 380 28.4 8.3 1.30 .46 .59 .72 27.0 7.9 1.51 .46 .60 .74 25.6 7.5 1.75 .47 .62 .76 24.0 7.0 2.02 .47 .63 .79(22�C)

1000 470 29.6 8.7 1.31 .47 .63 .78 28.0 8.2 1.52 .48 .64 .80 26.6 7.8 1.75 .48 .65 .82 24.8 7.3 2.03 .49 .67 .85

Page 20: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 20

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−30A/B/C−6F] [C33−30A/B/C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 18.0 5.3 .77 .72 .83 .94 17.3 5.1 .92 .73 .85 .96 16.5 4.8 1.09 .74 .87 .99 15.6 4.6 1.30 .76 .89 1.00

63�F(17�C)

560 265 19.0 5.6 .77 .75 .87 .99 18.2 5.3 .93 .76 .89 1.00 17.3 5.1 1.10 .78 .92 1.00 16.4 4.8 1.30 .80 .95 1.00(17�C)

660 310 19.7 5.8 .77 .77 .92 1.00 18.9 5.5 .93 .79 .94 1.00 18.0 5.3 1.10 .81 .97 1.00 17.1 5.0 1.30 .83 .99 1.00

67�F460 215 19.0 5.6 .77 .58 .69 .80 18.3 5.4 .92 .59 .70 .81 17.5 5.1 1.10 .59 .72 .83 16.6 4.9 1.30 .60 .73 .85

67�F(19�C)

560 265 20.2 5.9 .77 .60 .72 .84 19.3 5.7 .93 .61 .73 .86 18.4 5.4 1.10 .62 .75 .88 17.5 5.1 1.30 .63 .77 .91(19�C)

660 310 21.0 6.2 .77 .62 .75 .88 20.2 5.9 .93 .63 .76 .90 19.2 5.6 1.10 .63 .78 .93 18.1 5.3 1.30 .65 .81 .96

71�F460 215 19.9 5.8 .77 .45 .57 .67 19.2 5.6 .93 .45 .57 .68 18.4 5.4 1.10 .45 .58 .69 17.5 5.1 1.30 .45 .59 .71

71�F(22�C)

560 265 21.2 6.2 .77 .45 .58 .70 20.4 6.0 .93 .46 .59 .71 19.4 5.7 1.10 .46 .60 .72 18.4 5.4 1.30 .47 .61 .74(22�C)

660 310 22.2 6.5 .78 .47 .60 .72 21.2 6.2 .93 .47 .61 .74 20.2 5.9 1.10 .48 .62 .76 19.2 5.6 1.30 .48 .64 .78

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−30A/B/C−6F] [C33−30A/B/C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 23.0 6.7 1.28 .72 .83 .95 22.0 6.4 1.50 .73 .85 .97 20.8 6.1 1.73 .75 .87 .99 19.6 5.7 2.01 .76 .90 1.00

63�F(17�C)

800 380 24.6 7.2 1.28 .76 .90 1.00 23.4 6.9 1.50 .78 .93 1.00 22.2 6.5 1.75 .80 .95 1.00 20.8 6.1 2.01 .82 .98 1.00(17�C)

1000 470 25.6 7.5 1.29 .81 .97 1.00 24.4 7.2 1.51 .83 .99 1.00 23.4 6.9 1.75 .85 1.00 1.00 22.0 6.4 2.01 .88 1.00 1.00

67�F600 285 24.2 7.1 1.28 .58 .70 .80 23.2 6.8 1.51 .59 .71 .82 22.0 6.4 1.74 .60 .72 .84 20.8 6.1 2.01 .61 .74 .86

67�F(19�C)

800 380 25.8 7.6 1.29 .61 .74 .87 24.8 7.3 1.51 .62 .76 .89 23.4 6.9 1.75 .63 .78 .92 22.0 6.4 2.02 .64 .80 .95(19�C)

1000 470 27.0 7.9 1.30 .64 .79 .94 25.8 7.6 1.51 .65 .81 .96 24.4 7.2 1.75 .66 .83 .99 22.8 6.7 2.02 .68 .86 1.00

71�F600 285 25.2 7.4 1.29 .45 .57 .67 24.2 7.1 1.50 .45 .57 .68 23.0 6.7 1.75 .45 .58 .70 21.8 6.4 2.01 .45 .59 .72

71�F(22�C)

800 380 27.2 8.0 1.29 .46 .60 .72 25.8 7.6 1.51 .47 .61 .73 24.6 7.2 1.75 .47 .62 .75 23.2 6.8 2.02 .48 .63 .78(22�C)

1000 470 28.4 8.3 1.30 .48 .63 .76 27.0 7.9 1.51 .48 .64 .78 25.6 7.5 1.75 .49 .65 .81 24.0 7.0 2.02 .49 .67 .83

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−31A/B−6F] [C33−31A/B]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 18.9 5.5 .77 .71 .83 .95 18.1 5.3 .92 .72 .85 .97 17.1 5.0 1.10 .74 .87 .99 16.2 4.7 1.31 .76 .90 1.00

63�F(17�C)

560 265 20.0 5.9 .77 .75 .88 1.00 19.1 5.6 .93 .77 .90 1.00 18.1 5.3 1.10 .78 .93 1.00 17.0 5.0 1.30 .80 .96 1.00(17�C)

660 310 20.8 6.1 .77 .78 .93 1.00 19.9 5.8 .93 .80 .96 1.00 18.8 5.5 1.10 .82 .98 1.00 17.7 5.2 1.30 .84 1.00 1.00

67�F460 215 20.2 5.9 .77 .57 .69 .79 19.3 5.7 .93 .58 .70 .81 18.4 5.4 1.10 .58 .71 .83 17.4 5.1 1.30 .60 .73 .86

67�F(19�C)

560 265 21.4 6.3 .78 .59 .72 .84 20.4 6.0 .93 .60 .74 .86 19.4 5.7 1.10 .61 .75 .89 18.2 5.3 1.30 .62 .77 .92(19�C)

660 310 22.2 6.5 .78 .61 .75 .89 21.2 6.2 .93 .62 .77 .92 20.0 5.9 1.10 .63 .79 .94 18.9 5.5 1.30 .64 .81 .97

71�F460 215 21.4 6.3 .78 .44 .55 .66 20.6 6.0 .93 .45 .56 .67 19.5 5.7 1.10 .45 .57 .68 18.5 5.4 1.30 .45 .58 .70

71�F(22�C)

560 265 22.6 6.6 .78 .45 .57 .69 21.6 6.3 .93 .46 .58 .71 20.6 6.0 1.10 .46 .59 .72 19.5 5.7 1.30 .46 .61 .74(22�C)

660 310 23.6 6.9 .78 .46 .60 .73 22.6 6.6 .93 .47 .61 .74 21.4 6.3 1.10 .47 .62 .76 20.2 5.9 1.30 .47 .63 .79

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−31A/B−6F] [C33−31A/B]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 24.0 7.0 1.28 .72 .84 .95 22.8 6.7 1.50 .73 .85 .98 21.6 6.3 1.74 .74 .88 1.00 20.4 6.0 2.02 .76 .91 1.00

63�F(17�C)

800 380 25.8 7.6 1.29 .77 .91 1.00 24.4 7.2 1.51 .79 .94 1.00 23.0 6.7 1.74 .81 .97 1.00 21.6 6.3 2.02 .83 1.00 1.00(17�C)

1000 470 27.0 7.9 1.29 .82 .98 1.00 25.6 7.5 1.51 .84 1.00 1.00 24.4 7.2 1.75 .87 1.00 1.00 23.0 6.7 2.02 .90 1.00 1.00

67�F600 285 25.6 7.5 1.29 .58 .69 .80 24.2 7.1 1.50 .58 .70 .82 23.0 6.7 1.74 .59 .71 .84 21.6 6.3 2.02 .60 .74 .87

67�F(19�C)

800 380 27.2 8.0 1.30 .61 .75 .88 26.0 7.6 1.51 .62 .76 .90 24.4 7.2 1.75 .63 .78 .93 23.0 6.7 2.02 .64 .81 .97(19�C)

1000 470 28.4 8.3 1.30 .64 .79 .95 27.0 7.9 1.51 .65 .82 .98 25.4 7.4 1.75 .66 .85 1.00 23.8 7.0 2.02 .69 .88 1.00

71�F600 285 27.0 7.9 1.29 .45 .56 .67 25.6 7.5 1.50 .45 .56 .68 24.4 7.2 1.75 .45 .57 .69 23.0 6.7 2.02 .46 .58 .71

71�F(22�C)

800 380 28.8 8.4 1.30 .46 .59 .72 27.4 8.0 1.52 .46 .60 .74 25.8 7.6 1.75 .47 .62 .76 24.4 7.2 2.03 .47 .63 .78(22�C)

1000 470 30.0 8.8 1.31 .47 .62 .77 28.4 8.3 1.52 .48 .64 .80 26.8 7.9 1.76 .48 .65 .81 25.2 7.4 2.03 .48 .68 .85

Page 21: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 21

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−36A/B/C−6F] [C33−36A/B/C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 18.6 5.5 .77 .72 .84 .96 17.8 5.2 .92 .73 .86 .98 16.9 5.0 1.10 .75 .88 1.00 15.9 4.7 1.31 .77 .91 1.00

63�F(17�C)

560 265 19.7 5.8 .77 .76 .89 1.00 18.8 5.5 .92 .77 .91 1.00 17.9 5.2 1.10 .79 .94 1.00 16.8 4.9 1.30 .81 .97 1.00(17�C)

660 310 20.6 6.0 .77 .79 .94 1.00 19.7 5.8 .93 .81 .96 1.00 18.7 5.5 1.10 .83 .99 1.00 17.7 5.2 1.30 .85 1.00 1.00

67�F460 215 19.6 5.7 .77 .58 .70 .81 18.8 5.5 .92 .59 .71 .82 17.9 5.2 1.10 .59 .72 .84 16.9 5.0 1.31 .60 .74 .87

67�F(19�C)

560 265 20.8 6.1 .77 .60 .73 .85 19.9 5.8 .93 .61 .74 .87 18.9 5.5 1.10 .62 .76 .90 17.9 5.2 1.30 .63 .78 .93(19�C)

660 310 21.6 6.3 .77 .62 .76 .90 20.8 6.1 .93 .63 .78 .92 19.7 5.8 1.10 .64 .80 .95 18.6 5.5 1.30 .66 .82 .98

71�F460 215 20.4 6.0 .78 .45 .56 .67 19.6 5.7 .93 .45 .57 .68 18.7 5.5 1.10 .45 .58 .69 17.8 5.2 1.30 .46 .59 .71

71�F(22�C)

560 265 21.8 6.4 .78 .46 .58 .70 20.8 6.1 .93 .46 .59 .72 19.9 5.8 1.10 .46 .60 .73 18.8 5.5 1.30 .47 .62 .75(22�C)

660 310 22.8 6.7 .78 .47 .61 .74 21.8 6.4 .93 .47 .62 .75 20.8 6.1 1.10 .47 .63 .77 19.6 5.7 1.30 .48 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−36A/B/C−6F] [C33−36A/B/C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 23.6 6.9 1.28 .72 .85 .96 22.4 6.6 1.50 .74 .86 .98 21.4 6.3 1.74 .75 .89 1.00 20.0 5.9 2.02 .77 .92 1.00

63�F(17�C)

800 380 25.2 7.4 1.29 .78 .92 1.00 24.0 7.0 1.50 .79 .95 1.00 22.8 6.7 1.74 .81 .97 1.00 21.4 6.3 2.01 .84 1.00 1.00(17�C)

1000 470 26.6 7.8 1.29 .83 .99 1.00 25.2 7.4 1.50 .85 1.00 1.00 24.0 7.0 1.74 .88 1.00 1.00 22.8 6.7 2.02 .91 1.00 1.00

67�F600 285 24.8 7.3 1.29 .58 .70 .81 23.6 6.9 1.50 .59 .71 .83 22.4 6.6 1.74 .60 .73 .85 21.2 6.2 2.02 .61 .75 .88

67�F(19�C)

800 380 26.6 7.8 1.30 .61 .75 .89 25.4 7.4 1.51 .62 .77 .91 24.0 7.0 1.75 .64 .79 .94 22.6 6.6 2.02 .65 .82 .97(19�C)

1000 470 27.8 8.1 1.30 .65 .81 .96 26.4 7.7 1.51 .66 .83 .98 25.0 7.3 1.75 .67 .85 1.00 23.4 6.9 2.02 .69 .88 1.00

71�F600 285 25.8 7.6 1.29 .45 .57 .68 24.6 7.2 1.50 .45 .57 .69 23.4 6.9 1.75 .46 .58 .70 22.0 6.4 2.01 .46 .59 .72

71�F(22�C)

800 380 27.8 8.1 1.30 .46 .60 .73 26.4 7.7 1.51 .47 .61 .75 25.2 7.4 1.75 .47 .62 .77 23.6 6.9 2.02 .48 .64 .79(22�C)

1000 470 29.2 8.6 1.31 .48 .63 .79 27.8 8.1 1.52 .48 .65 .81 26.2 7.7 1.76 .49 .66 .83 24.6 7.2 2.02 .50 .68 .86

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−38B−6F] [C33−38B]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 19.0 5.6 .77 .72 .84 .95 18.2 5.3 .93 .72 .85 .98 17.3 5.1 1.10 .74 .87 1.00 16.2 4.7 1.31 .76 .90 1.00

63�F(17�C)

560 265 20.0 5.9 .77 .75 .89 1.00 19.2 5.6 .93 .77 .91 1.00 18.2 5.3 1.10 .79 .93 1.00 17.1 5.0 1.30 .81 .96 1.00(17�C)

660 310 21.0 6.2 .77 .79 .94 1.00 20.0 5.9 .93 .80 .96 1.00 19.0 5.6 1.10 .82 .99 1.00 17.9 5.2 1.30 .85 1.00 1.00

67�F460 215 20.4 6.0 .77 .57 .69 .80 19.5 5.7 .92 .58 .70 .81 18.5 5.4 1.10 .59 .71 .83 17.5 5.1 1.30 .60 .73 .86

67�F(19�C)

560 265 21.6 6.3 .78 .60 .72 .85 20.6 6.0 .93 .60 .74 .87 19.5 5.7 1.10 .61 .76 .89 18.4 5.4 1.30 .62 .78 .92(19�C)

660 310 22.4 6.6 .78 .62 .76 .90 21.4 6.3 .93 .62 .78 .92 20.2 5.9 1.10 .63 .79 .95 19.0 5.6 1.30 .64 .82 .98

71�F460 215 21.6 6.3 .78 .45 .55 .66 20.6 6.0 .93 .45 .56 .67 19.7 5.8 1.10 .45 .57 .68 18.6 5.5 1.30 .45 .58 .70

71�F(22�C)

560 265 22.8 6.7 .78 .45 .58 .70 21.8 6.4 .93 .46 .59 .71 20.8 6.1 1.10 .46 .59 .73 19.6 5.7 1.30 .46 .61 .75(22�C)

660 310 23.8 7.0 .79 .46 .60 .73 22.8 6.7 .93 .47 .61 .75 21.6 6.3 1.10 .47 .62 .77 20.4 6.0 1.30 .47 .63 .79

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−38B−6F] [C33−38B]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 24.2 7.1 1.28 .72 .84 .96 23.0 6.7 1.50 .73 .86 .98 21.8 6.4 1.74 .75 .88 1.00 20.4 6.0 2.02 .77 .91 1.00

63�F(17�C)

800 380 26.0 7.6 1.29 .78 .92 1.00 24.6 7.2 1.51 .79 .95 1.00 23.2 6.8 1.75 .81 .98 1.00 21.8 6.4 2.02 .84 1.00 1.00(17�C)

1000 470 27.2 8.0 1.29 .83 .99 1.00 25.8 7.6 1.51 .85 1.00 1.00 24.6 7.2 1.75 .88 1.00 1.00 23.2 6.8 2.02 .91 1.00 1.00

67�F600 285 25.8 7.6 1.29 .58 .69 .80 24.4 7.2 1.50 .58 .70 .82 23.2 6.8 1.75 .59 .72 .85 21.8 6.4 2.02 .60 .74 .87

67�F(19�C)

800 380 27.6 8.1 1.30 .61 .75 .89 26.2 7.7 1.51 .62 .77 .91 24.6 7.2 1.75 .63 .79 .94 23.0 6.7 2.02 .64 .81 .97(19�C)

1000 470 28.6 8.4 1.30 .64 .81 .96 27.2 8.0 1.52 .65 .82 .99 25.6 7.5 1.75 .67 .86 1.00 24.0 7.0 2.02 .70 .89 1.00

71�F600 285 27.2 8.0 1.29 .45 .56 .67 25.8 7.6 1.50 .45 .56 .68 24.6 7.2 1.75 .45 .57 .69 23.0 6.7 2.02 .45 .59 .71

71�F(22�C)

800 380 29.0 8.5 1.31 .46 .60 .73 27.6 8.1 1.52 .46 .61 .74 26.0 7.6 1.75 .47 .62 .77 24.4 7.2 2.03 .47 .63 .79(22�C)

1000 470 30.2 8.9 1.31 .47 .63 .78 28.8 8.4 1.52 .48 .64 .80 27.2 8.0 1.76 .48 .66 .83 25.4 7.4 2.03 .49 .69 .86

Page 22: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 22

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−42B−6F] [C33−42B]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 18.6 5.5 .77 .72 .84 .96 17.8 5.2 .92 .73 .86 .98 16.9 5.0 1.10 .75 .88 1.00 15.9 4.7 1.31 .77 .91 1.00

63�F(17�C)

560 265 19.7 5.8 .77 .76 .89 1.00 18.8 5.5 .92 .77 .91 1.00 17.9 5.2 1.10 .79 .94 1.00 16.8 4.9 1.30 .81 .97 1.00(17�C)

660 310 20.6 6.0 .77 .79 .94 1.00 19.7 5.8 .93 .81 .96 1.00 18.7 5.5 1.10 .83 .99 1.00 17.7 5.2 1.30 .85 1.00 1.00

67�F460 215 19.6 5.7 .77 .58 .70 .81 18.8 5.5 .92 .59 .71 .82 17.9 5.2 1.10 .59 .72 .84 16.9 5.0 1.31 .60 .74 .87

67�F(19�C)

560 265 20.8 6.1 .77 .60 .73 .85 19.9 5.8 .93 .61 .74 .87 18.9 5.5 1.10 .62 .76 .90 17.9 5.2 1.30 .63 .78 .93(19�C)

660 310 21.6 6.3 .77 .62 .76 .90 20.8 6.1 .93 .63 .78 .92 19.7 5.8 1.10 .64 .80 .95 18.6 5.5 1.30 .66 .82 .98

71�F460 215 20.4 6.0 .78 .45 .56 .67 19.6 5.7 .93 .45 .57 .68 18.7 5.5 1.10 .45 .58 .69 17.8 5.2 1.30 .46 .59 .71

71�F(22�C)

560 265 21.8 6.4 .78 .46 .58 .70 20.8 6.1 .93 .46 .59 .72 19.9 5.8 1.10 .46 .60 .73 18.8 5.5 1.30 .47 .62 .75(22�C)

660 310 22.8 6.7 .78 .47 .61 .74 21.8 6.4 .93 .47 .62 .75 20.8 6.1 1.10 .47 .63 .77 19.6 5.7 1.30 .48 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−42B−6F] [C33−42B]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 23.6 6.9 1.28 .72 .85 .96 22.4 6.6 1.50 .74 .86 .98 21.4 6.3 1.74 .75 .89 1.00 20.0 5.9 2.02 .77 .92 1.00

63�F(17�C)

800 380 25.2 7.4 1.29 .78 .92 1.00 24.0 7.0 1.50 .79 .95 1.00 22.8 6.7 1.74 .81 .97 1.00 21.4 6.3 2.01 .84 1.00 1.00(17�C)

1000 470 26.6 7.8 1.29 .83 .99 1.00 25.2 7.4 1.50 .85 1.00 1.00 24.0 7.0 1.74 .88 1.00 1.00 22.8 6.7 2.02 .91 1.00 1.00

67�F600 285 24.8 7.3 1.29 .58 .70 .81 23.6 6.9 1.50 .59 .71 .83 22.4 6.6 1.74 .60 .73 .85 21.2 6.2 2.02 .61 .75 .88

67�F(19�C)

800 380 26.6 7.8 1.30 .61 .75 .89 25.4 7.4 1.51 .62 .77 .91 24.0 7.0 1.75 .64 .79 .94 22.6 6.6 2.02 .65 .82 .97(19�C)

1000 470 27.8 8.1 1.30 .65 .81 .96 26.4 7.7 1.51 .66 .83 .98 25.0 7.3 1.75 .67 .85 1.00 23.4 6.9 2.02 .69 .88 1.00

71�F600 285 25.8 7.6 1.29 .45 .57 .68 24.6 7.2 1.50 .45 .57 .69 23.4 6.9 1.75 .46 .58 .70 22.0 6.4 2.01 .46 .59 .72

71�F(22�C)

800 380 27.8 8.1 1.30 .46 .60 .73 26.4 7.7 1.51 .47 .61 .75 25.2 7.4 1.75 .47 .62 .77 23.6 6.9 2.02 .48 .64 .79(22�C)

1000 470 29.2 8.6 1.31 .48 .63 .79 27.8 8.1 1.52 .48 .65 .81 26.2 7.7 1.76 .49 .66 .83 24.6 7.2 2.02 .50 .68 .86

FIRST STAGE COOLING CAPACITY − XC21−024 with [C33−44C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 18.9 5.5 .77 .71 .83 .95 18.0 5.3 .92 .72 .85 .97 17.1 5.0 1.10 .74 .87 .99 16.1 4.7 1.31 .76 .90 1.00

63�F(17�C)

560 265 20.0 5.9 .77 .75 .88 1.00 19.0 5.6 .92 .76 .90 1.00 18.0 5.3 1.10 .78 .93 1.00 17.0 5.0 1.30 .80 .96 1.00(17�C)

660 310 20.8 6.1 .77 .78 .93 1.00 19.8 5.8 .93 .80 .95 1.00 18.8 5.5 1.10 .82 .98 1.00 17.7 5.2 1.30 .84 1.00 1.00

67�F460 215 20.2 5.9 .77 .57 .68 .80 19.3 5.7 .92 .58 .70 .81 18.4 5.4 1.10 .58 .71 .83 17.4 5.1 1.30 .60 .73 .86

67�F(19�C)

560 265 21.4 6.3 .78 .59 .72 .84 20.4 6.0 .93 .60 .73 .86 19.3 5.7 1.10 .61 .75 .89 18.2 5.3 1.30 .62 .77 .92(19�C)

660 310 22.2 6.5 .78 .61 .75 .89 21.2 6.2 .93 .62 .77 .91 20.0 5.9 1.10 .63 .79 .94 18.9 5.5 1.30 .64 .81 .97

71�F460 215 21.4 6.3 .78 .45 .55 .66 20.6 6.0 .93 .44 .56 .67 19.6 5.7 1.10 .45 .57 .68 18.5 5.4 1.30 .45 .58 .70

71�F(22�C)

560 265 22.6 6.6 .78 .45 .57 .69 21.6 6.3 .93 .45 .58 .71 20.6 6.0 1.10 .46 .60 .72 19.5 5.7 1.30 .46 .61 .74(22�C)

660 310 23.6 6.9 .78 .46 .59 .73 22.6 6.6 .93 .47 .61 .74 21.4 6.3 1.10 .47 .62 .76 20.2 5.9 1.30 .47 .63 .78

SECOND STAGE COOLING CAPACITY − XC21−024 with [C33−44C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 24.0 7.0 1.29 .72 .84 .95 22.8 6.7 1.50 .73 .85 .98 21.6 6.3 1.74 .74 .88 1.00 20.2 5.9 2.02 .76 .90 1.00

63�F(17�C)

800 380 25.6 7.5 1.29 .77 .91 1.00 24.4 7.2 1.51 .79 .94 1.00 23.0 6.7 1.74 .81 .97 1.00 21.6 6.3 2.02 .83 .99 1.00(17�C)

1000 470 26.8 7.9 1.29 .82 .98 1.00 25.6 7.5 1.51 .84 1.00 1.00 24.2 7.1 1.75 .87 1.00 1.00 23.0 6.7 2.02 .90 1.00 1.00

67�F600 285 25.4 7.4 1.29 .58 .69 .80 24.2 7.1 1.51 .58 .70 .82 23.0 6.7 1.74 .59 .72 .84 21.6 6.3 2.02 .60 .74 .87

67�F(19�C)

800 380 27.2 8.0 1.30 .61 .75 .88 26.0 7.6 1.51 .62 .76 .90 24.4 7.2 1.75 .63 .78 .93 23.0 6.7 2.02 .64 .80 .96(19�C)

1000 470 28.4 8.3 1.30 .64 .79 .95 27.0 7.9 1.51 .65 .82 .98 25.4 7.4 1.76 .66 .84 1.00 23.8 7.0 2.02 .68 .87 1.00

71�F600 285 27.0 7.9 1.29 .45 .56 .66 25.6 7.5 1.51 .45 .56 .68 24.4 7.2 1.75 .45 .57 .69 22.8 6.7 2.03 .46 .58 .71

71�F(22�C)

800 380 28.8 8.4 1.31 .46 .59 .72 27.4 8.0 1.52 .46 .60 .74 25.8 7.6 1.75 .47 .61 .76 24.4 7.2 2.03 .47 .63 .78(22�C)

1000 470 30.0 8.8 1.31 .47 .62 .77 28.4 8.3 1.52 .48 .64 .79 26.8 7.9 1.76 .48 .65 .81 25.2 7.4 2.03 .49 .67 .85

Page 23: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 23

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−18/24A−6F + G60UHV−36A−070][C33−24A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F630 295 19.7 5.8 .77 .77 .91 1.00 18.8 5.5 .93 .78 .93 1.00 17.9 5.2 1.10 .80 .96 1.00 16.9 5.0 1.30 .83 .99 1.00

63�F(17�C)

630 295 19.7 5.8 .77 .77 .91 1.00 18.8 5.5 .93 .78 .93 1.00 17.9 5.2 1.10 .80 .96 1.00 16.9 5.0 1.30 .83 .99 1.00(17�C)

745 350 20.6 6.0 .78 .80 .96 1.00 19.6 5.7 .93 .82 .98 1.00 18.7 5.5 1.10 .84 1.00 1.00 17.7 5.2 1.30 .87 1.00 1.00

67�F630 295 20.8 6.1 .77 .61 .74 .87 19.9 5.8 .92 .62 .76 .90 18.9 5.5 1.10 .63 .78 .92 17.9 5.2 1.30 .64 .80 .95

67�F(19�C)

630 295 20.8 6.1 .77 .61 .74 .87 19.9 5.8 .92 .62 .76 .90 18.9 5.5 1.10 .63 .78 .92 17.9 5.2 1.30 .64 .80 .95(19�C)

745 350 21.6 6.3 .78 .63 .78 .92 20.6 6.0 .93 .64 .79 .94 19.6 5.7 1.10 .65 .82 .97 18.5 5.4 1.30 .67 .84 .99

71�F630 295 21.8 6.4 .78 .46 .59 .72 21.0 6.2 .93 .47 .60 .73 20.0 5.9 1.10 .47 .61 .75 18.9 5.5 1.30 .47 .63 .77

71�F(22�C)

630 295 21.8 6.4 .78 .46 .59 .72 21.0 6.2 .93 .47 .60 .73 20.0 5.9 1.10 .47 .61 .75 18.9 5.5 1.30 .47 .63 .77(22�C)

745 350 22.8 6.7 .78 .47 .61 .75 21.8 6.4 .93 .48 .62 .77 20.8 6.1 1.10 .48 .64 .79 19.6 5.7 1.30 .49 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−18/24A−6F + G60UHV−36A−070][C33−24A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F830 390 24.6 7.2 1.29 .77 .92 1.00 23.6 6.9 1.50 .79 .94 1.00 22.2 6.5 1.74 .81 .97 1.00 21.0 6.2 2.02 .83 .99 1.00

63�F(17�C)

830 390 24.6 7.2 1.29 .77 .92 1.00 23.6 6.9 1.50 .79 .94 1.00 22.2 6.5 1.74 .81 .97 1.00 21.0 6.2 2.02 .83 .99 1.00(17�C)

1040 490 25.8 7.6 1.29 .82 .98 1.00 24.6 7.2 1.50 .84 1.00 1.00 23.4 6.9 1.74 .87 1.00 1.00 22.0 6.4 2.02 .90 1.00 1.00

67�F830 390 26.0 7.6 1.29 .61 .75 .88 24.8 7.3 1.50 .62 .76 .91 23.4 6.9 1.75 .63 .78 .93 22.0 6.4 2.02 .65 .81 .96

67�F(19�C)

830 390 26.0 7.6 1.29 .61 .75 .88 24.8 7.3 1.50 .62 .76 .91 23.4 6.9 1.75 .63 .78 .93 22.0 6.4 2.02 .65 .81 .96(19�C)

1040 490 27.0 7.9 1.30 .64 .80 .95 25.8 7.6 1.51 .65 .82 .97 24.2 7.1 1.75 .67 .84 .99 22.8 6.7 2.01 .68 .87 1.00

71�F830 390 27.2 8.0 1.29 .47 .60 .73 26.0 7.6 1.51 .47 .61 .74 24.6 7.2 1.75 .47 .62 .76 23.2 6.8 2.02 .48 .63 .79

71�F(22�C)

830 390 27.2 8.0 1.29 .47 .60 .73 26.0 7.6 1.51 .47 .61 .74 24.6 7.2 1.75 .47 .62 .76 23.2 6.8 2.02 .48 .63 .79(22�C)

1040 490 28.4 8.3 1.30 .48 .63 .77 27.0 7.9 1.51 .48 .64 .79 25.6 7.5 1.75 .49 .66 .82 24.0 7.0 2.03 .50 .67 .85

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−18/24B−6F + G60UHV−36B−090][C33−24B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 19.7 5.8 .77 .77 .91 1.00 18.8 5.5 .93 .78 .93 1.00 17.9 5.2 1.10 .80 .96 1.00 16.9 5.0 1.30 .82 .98 1.00

63�F(17�C)

625 295 19.7 5.8 .77 .77 .91 1.00 18.8 5.5 .93 .78 .93 1.00 17.9 5.2 1.10 .80 .96 1.00 16.9 5.0 1.30 .82 .98 1.00(17�C)

740 350 20.4 6.0 .78 .80 .95 1.00 19.6 5.7 .93 .82 .98 1.00 18.6 5.5 1.10 .84 1.00 1.00 17.6 5.2 1.30 .87 1.00 1.00

67�F625 295 20.8 6.1 .77 .61 .74 .87 19.9 5.8 .92 .61 .76 .89 18.9 5.5 1.10 .63 .77 .92 17.9 5.2 1.30 .64 .80 .95

67�F(19�C)

625 295 20.8 6.1 .77 .61 .74 .87 19.9 5.8 .92 .61 .76 .89 18.9 5.5 1.10 .63 .77 .92 17.9 5.2 1.30 .64 .80 .95(19�C)

740 350 21.6 6.3 .78 .63 .78 .92 20.6 6.0 .93 .64 .79 .94 19.6 5.7 1.10 .65 .81 .97 18.5 5.4 1.30 .67 .84 .99

71�F625 295 21.8 6.4 .78 .46 .59 .72 21.0 6.2 .93 .47 .60 .73 19.9 5.8 1.10 .47 .61 .75 18.8 5.5 1.30 .47 .63 .77

71�F(22�C)

625 295 21.8 6.4 .78 .46 .59 .72 21.0 6.2 .93 .47 .60 .73 19.9 5.8 1.10 .47 .61 .75 18.8 5.5 1.30 .47 .63 .77(22�C)

740 350 22.6 6.6 .78 .47 .61 .75 21.8 6.4 .93 .48 .62 .77 20.6 6.0 1.10 .48 .64 .79 19.5 5.7 1.30 .49 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−18/24B−6F + G60UHV−36B−090][C33−24B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F825 390 24.6 7.2 1.29 .77 .91 1.00 23.4 6.9 1.50 .79 .94 1.00 22.2 6.5 1.74 .81 .96 1.00 21.0 6.2 2.02 .83 .99 1.00

63�F(17�C)

825 390 24.6 7.2 1.29 .77 .91 1.00 23.4 6.9 1.50 .79 .94 1.00 22.2 6.5 1.74 .81 .96 1.00 21.0 6.2 2.02 .83 .99 1.00(17�C)

1035 490 25.8 7.6 1.29 .82 .97 1.00 24.6 7.2 1.50 .84 .99 1.00 23.4 6.9 1.74 .86 1.00 1.00 22.0 6.4 2.02 .89 1.00 1.00

67�F825 390 26.0 7.6 1.29 .61 .75 .88 24.8 7.3 1.50 .62 .76 .90 23.4 6.9 1.74 .63 .78 .93 22.0 6.4 2.02 .65 .81 .96

67�F(19�C)

825 390 26.0 7.6 1.29 .61 .75 .88 24.8 7.3 1.50 .62 .76 .90 23.4 6.9 1.74 .63 .78 .93 22.0 6.4 2.02 .65 .81 .96(19�C)

1035 490 27.0 7.9 1.30 .64 .80 .95 25.6 7.5 1.51 .65 .82 .97 24.2 7.1 1.75 .67 .84 .99 22.8 6.7 2.01 .68 .87 1.00

71�F825 390 27.2 8.0 1.30 .46 .60 .72 25.8 7.6 1.51 .47 .61 .74 24.6 7.2 1.75 .47 .62 .76 23.0 6.7 2.02 .48 .63 .78

71�F(22�C)

825 390 27.2 8.0 1.30 .46 .60 .72 25.8 7.6 1.51 .47 .61 .74 24.6 7.2 1.75 .47 .62 .76 23.0 6.7 2.02 .48 .63 .78(22�C)

1035 490 28.4 8.3 1.30 .48 .63 .77 27.0 7.9 1.51 .48 .64 .79 25.6 7.5 1.75 .49 .65 .82 24.0 7.0 2.03 .50 .67 .85

Page 24: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 24

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−18/24B−6F + G61MPV−36B−045][C33−24B + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F610 290 19.5 5.7 .77 .76 .90 1.00 18.7 5.5 .93 .78 .92 1.00 17.8 5.2 1.10 .80 .95 1.00 16.8 4.9 1.30 .82 .98 1.00

63�F(17�C)

610 290 19.5 5.7 .77 .76 .90 1.00 18.7 5.5 .93 .78 .92 1.00 17.8 5.2 1.10 .80 .95 1.00 16.8 4.9 1.30 .82 .98 1.00(17�C)

725 340 20.4 6.0 .77 .80 .95 1.00 19.5 5.7 .93 .81 .97 1.00 18.5 5.4 1.10 .83 .99 1.00 17.5 5.1 1.30 .86 1.00 1.00

67�F610 290 20.6 6.0 .77 .61 .74 .87 19.8 5.8 .93 .61 .75 .89 18.8 5.5 1.10 .62 .77 .91 17.8 5.2 1.30 .64 .79 .94

67�F(19�C)

610 290 20.6 6.0 .77 .61 .74 .87 19.8 5.8 .93 .61 .75 .89 18.8 5.5 1.10 .62 .77 .91 17.8 5.2 1.30 .64 .79 .94(19�C)

725 340 21.4 6.3 .78 .62 .77 .91 20.6 6.0 .93 .63 .79 .94 19.5 5.7 1.10 .65 .81 .96 18.4 5.4 1.30 .66 .83 .99

71�F610 290 21.6 6.3 .78 .46 .59 .71 20.8 6.1 .93 .46 .60 .73 19.8 5.8 1.10 .47 .61 .74 18.7 5.5 1.30 .47 .62 .76

71�F(22�C)

610 290 21.6 6.3 .78 .46 .59 .71 20.8 6.1 .93 .46 .60 .73 19.8 5.8 1.10 .47 .61 .74 18.7 5.5 1.30 .47 .62 .76(22�C)

725 340 22.6 6.6 .78 .47 .61 .75 21.6 6.3 .93 .47 .62 .76 20.6 6.0 1.10 .48 .63 .78 19.5 5.7 1.30 .48 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−18/24B−6F + G61MPV−36B−045][C33−24B + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F840 395 24.8 7.3 1.29 .78 .92 1.00 23.6 6.9 1.50 .79 .94 1.00 22.4 6.6 1.74 .81 .97 1.00 21.0 6.2 2.02 .84 .99 1.00

63�F(17�C)

840 395 24.8 7.3 1.29 .78 .92 1.00 23.6 6.9 1.50 .79 .94 1.00 22.4 6.6 1.74 .81 .97 1.00 21.0 6.2 2.02 .84 .99 1.00(17�C)

1050 495 25.8 7.6 1.29 .82 .98 1.00 24.6 7.2 1.51 .84 1.00 1.00 23.4 6.9 1.74 .87 1.00 1.00 22.0 6.4 2.02 .90 1.00 1.00

67�F840 395 26.0 7.6 1.29 .61 .75 .89 24.8 7.3 1.50 .62 .77 .91 23.4 6.9 1.75 .63 .79 .94 22.0 6.4 2.02 .65 .81 .97

67�F(19�C)

840 395 26.0 7.6 1.29 .61 .75 .89 24.8 7.3 1.50 .62 .77 .91 23.4 6.9 1.75 .63 .79 .94 22.0 6.4 2.02 .65 .81 .97(19�C)

1050 495 27.0 7.9 1.30 .64 .80 .95 25.8 7.6 1.51 .65 .82 .97 24.4 7.2 1.75 .67 .85 1.00 22.8 6.7 2.01 .69 .88 1.00

71�F840 395 27.2 8.0 1.29 .47 .60 .73 26.0 7.6 1.51 .47 .61 .74 24.6 7.2 1.75 .47 .62 .77 23.2 6.8 2.02 .48 .64 .79

71�F(22�C)

840 395 27.2 8.0 1.29 .47 .60 .73 26.0 7.6 1.51 .47 .61 .74 24.6 7.2 1.75 .47 .62 .77 23.2 6.8 2.02 .48 .64 .79(22�C)

1050 495 28.4 8.3 1.30 .48 .63 .78 27.0 7.9 1.51 .48 .64 .80 25.6 7.5 1.75 .49 .66 .82 24.0 7.0 2.03 .50 .68 .85

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−25A−6F + G60UHV−36A−070][C33−25A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F630 295 20.4 6.0 .77 .77 .92 1.00 19.4 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.3 5.1 1.30 .83 1.00 1.00

63�F(17�C)

630 295 20.4 6.0 .77 .77 .92 1.00 19.4 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.3 5.1 1.30 .83 1.00 1.00(17�C)

745 350 21.2 6.2 .77 .81 .97 1.00 20.2 5.9 .93 .83 .99 1.00 19.2 5.6 1.10 .85 1.00 1.00 18.2 5.3 1.30 .88 1.00 1.00

67�F630 295 21.8 6.4 .78 .61 .75 .88 20.8 6.1 .93 .62 .76 .90 19.7 5.8 1.10 .63 .78 .93 18.5 5.4 1.30 .64 .80 .96

67�F(19�C)

630 295 21.8 6.4 .78 .61 .75 .88 20.8 6.1 .93 .62 .76 .90 19.7 5.8 1.10 .63 .78 .93 18.5 5.4 1.30 .64 .80 .96(19�C)

745 350 22.4 6.6 .78 .63 .78 .93 21.4 6.3 .93 .64 .80 .96 20.4 6.0 1.10 .65 .82 .98 19.2 5.6 1.30 .67 .85 1.00

71�F630 295 23.0 6.7 .78 .46 .59 .72 22.0 6.4 .93 .46 .60 .74 21.0 6.2 1.10 .47 .61 .75 19.8 5.8 1.30 .47 .63 .78

71�F(22�C)

630 295 23.0 6.7 .78 .46 .59 .72 22.0 6.4 .93 .46 .60 .74 21.0 6.2 1.10 .47 .61 .75 19.8 5.8 1.30 .47 .63 .78(22�C)

745 350 24.0 7.0 .79 .47 .62 .76 22.8 6.7 .93 .47 .63 .78 21.6 6.3 1.10 .48 .64 .80 20.4 6.0 1.30 .48 .65 .82

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−25A−6F + G60UHV−36A−070][C33−25A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F830 390 25.6 7.5 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .95 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.01 .84 1.00 1.00

63�F(17�C)

830 390 25.6 7.5 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .95 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.01 .84 1.00 1.00(17�C)

1040 490 26.6 7.8 1.29 .84 1.00 1.00 25.4 7.4 1.51 .85 1.00 1.00 24.2 7.1 1.75 .88 1.00 1.00 22.8 6.7 2.03 .92 1.00 1.00

67�F830 390 27.0 7.9 1.29 .61 .76 .89 25.8 7.6 1.51 .62 .77 .92 24.4 7.2 1.75 .64 .80 .95 22.8 6.7 2.02 .65 .82 .98

67�F(19�C)

830 390 27.0 7.9 1.29 .61 .76 .89 25.8 7.6 1.51 .62 .77 .92 24.4 7.2 1.75 .64 .80 .95 22.8 6.7 2.02 .65 .82 .98(19�C)

1040 490 28.2 8.3 1.30 .65 .81 .97 26.8 7.9 1.52 .65 .83 .99 25.2 7.4 1.75 .67 .86 1.00 23.6 6.9 2.02 .70 .89 1.00

71�F830 390 28.6 8.4 1.30 .46 .60 .73 27.2 8.0 1.51 .47 .61 .75 25.8 7.6 1.75 .47 .62 .77 24.2 7.1 2.02 .48 .64 .80

71�F(22�C)

830 390 28.6 8.4 1.30 .46 .60 .73 27.2 8.0 1.51 .47 .61 .75 25.8 7.6 1.75 .47 .62 .77 24.2 7.1 2.02 .48 .64 .80(22�C)

1040 490 29.8 8.7 1.31 .48 .64 .79 28.2 8.3 1.52 .48 .65 .81 26.6 7.8 1.76 .49 .67 .84 25.0 7.3 2.03 .50 .68 .87

Page 25: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 25

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−25B−6F + G60UHV−36B−090][C33−25B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 20.4 6.0 .77 .77 .91 1.00 19.4 5.7 .92 .79 .94 1.00 18.4 5.4 1.10 .81 .96 1.00 17.3 5.1 1.31 .83 .99 1.00

63�F(17�C)

625 295 20.4 6.0 .77 .77 .91 1.00 19.4 5.7 .92 .79 .94 1.00 18.4 5.4 1.10 .81 .96 1.00 17.3 5.1 1.31 .83 .99 1.00(17�C)

740 350 21.2 6.2 .77 .81 .97 1.00 20.2 5.9 .93 .83 .99 1.00 19.2 5.6 1.10 .84 1.00 1.00 18.2 5.3 1.30 .88 1.00 1.00

67�F625 295 21.6 6.3 .78 .61 .74 .88 20.8 6.1 .93 .61 .76 .90 19.7 5.8 1.10 .63 .78 .93 18.5 5.4 1.30 .64 .80 .96

67�F(19�C)

625 295 21.6 6.3 .78 .61 .74 .88 20.8 6.1 .93 .61 .76 .90 19.7 5.8 1.10 .63 .78 .93 18.5 5.4 1.30 .64 .80 .96(19�C)

740 350 22.4 6.6 .78 .63 .78 .93 21.4 6.3 .93 .64 .80 .95 20.4 6.0 1.10 .65 .82 .98 19.1 5.6 1.30 .67 .84 1.00

71�F625 295 23.0 6.7 .78 .46 .59 .72 22.0 6.4 .93 .46 .60 .73 21.0 6.2 1.10 .47 .61 .75 19.8 5.8 1.30 .47 .62 .77

71�F(22�C)

625 295 23.0 6.7 .78 .46 .59 .72 22.0 6.4 .93 .46 .60 .73 21.0 6.2 1.10 .47 .61 .75 19.8 5.8 1.30 .47 .62 .77(22�C)

740 350 24.0 7.0 .79 .47 .62 .76 22.8 6.7 .93 .47 .63 .77 21.6 6.3 1.10 .48 .64 .80 20.4 6.0 1.30 .48 .65 .82

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−25B−6F + G60UHV−36B−090][C33−25B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F825 390 25.6 7.5 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .95 1.00 23.0 6.7 1.74 .82 .98 1.00 21.4 6.3 2.01 .84 1.00 1.00

63�F(17�C)

825 390 25.6 7.5 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .95 1.00 23.0 6.7 1.74 .82 .98 1.00 21.4 6.3 2.01 .84 1.00 1.00(17�C)

1035 490 26.6 7.8 1.29 .83 1.00 1.00 25.4 7.4 1.51 .85 1.00 1.00 24.2 7.1 1.75 .88 1.00 1.00 22.8 6.7 2.03 .92 1.00 1.00

67�F825 390 27.0 7.9 1.29 .61 .76 .89 25.8 7.6 1.51 .62 .77 .92 24.2 7.1 1.75 .63 .79 .95 22.8 6.7 2.02 .65 .82 .98

67�F(19�C)

825 390 27.0 7.9 1.29 .61 .76 .89 25.8 7.6 1.51 .62 .77 .92 24.2 7.1 1.75 .63 .79 .95 22.8 6.7 2.02 .65 .82 .98(19�C)

1035 490 28.2 8.3 1.30 .65 .81 .97 26.8 7.9 1.52 .65 .83 .99 25.2 7.4 1.75 .67 .86 1.00 23.6 6.9 2.02 .69 .89 1.00

71�F825 390 28.6 8.4 1.30 .46 .60 .73 27.2 8.0 1.51 .47 .61 .75 25.8 7.6 1.75 .47 .62 .77 24.2 7.1 2.02 .48 .64 .79

71�F(22�C)

825 390 28.6 8.4 1.30 .46 .60 .73 27.2 8.0 1.51 .47 .61 .75 25.8 7.6 1.75 .47 .62 .77 24.2 7.1 2.02 .48 .64 .79(22�C)

1035 490 29.6 8.7 1.31 .48 .63 .79 28.2 8.3 1.52 .48 .65 .81 26.6 7.8 1.76 .48 .66 .83 25.0 7.3 2.03 .49 .68 .87

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−25B−6F + G61MPV−36B−045][C33−25B + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F610 290 20.2 5.9 .77 .77 .91 1.00 19.3 5.7 .92 .78 .93 1.00 18.3 5.4 1.10 .80 .96 1.00 17.2 5.0 1.30 .82 .99 1.00

63�F(17�C)

610 290 20.2 5.9 .77 .77 .91 1.00 19.3 5.7 .92 .78 .93 1.00 18.3 5.4 1.10 .80 .96 1.00 17.2 5.0 1.30 .82 .99 1.00(17�C)

725 340 21.0 6.2 .77 .81 .96 1.00 20.0 5.9 .93 .82 .99 1.00 19.0 5.6 1.10 .85 1.00 1.00 18.1 5.3 1.30 .87 1.00 1.00

67�F610 290 21.6 6.3 .78 .61 .74 .87 20.6 6.0 .93 .61 .75 .89 19.5 5.7 1.10 .62 .77 .92 18.4 5.4 1.30 .64 .80 .95

67�F(19�C)

610 290 21.6 6.3 .78 .61 .74 .87 20.6 6.0 .93 .61 .75 .89 19.5 5.7 1.10 .62 .77 .92 18.4 5.4 1.30 .64 .80 .95(19�C)

725 340 22.4 6.6 .78 .63 .78 .92 21.4 6.3 .93 .64 .79 .95 20.2 5.9 1.10 .64 .82 .97 19.0 5.6 1.30 .66 .84 1.00

71�F610 290 22.8 6.7 .78 .46 .59 .71 22.0 6.4 .93 .46 .60 .73 20.8 6.1 1.10 .46 .61 .74 19.7 5.8 1.30 .47 .62 .77

71�F(22�C)

610 290 22.8 6.7 .78 .46 .59 .71 22.0 6.4 .93 .46 .60 .73 20.8 6.1 1.10 .46 .61 .74 19.7 5.8 1.30 .47 .62 .77(22�C)

725 340 23.8 7.0 .79 .47 .61 .75 22.8 6.7 .93 .47 .62 .77 21.6 6.3 1.10 .48 .63 .79 20.4 6.0 1.30 .48 .65 .82

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−25B−6F + G61MPV−36B−045][C33−25B + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F840 395 25.6 7.5 1.29 .78 .93 1.00 24.4 7.2 1.51 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.01 .85 1.00 1.00

63�F(17�C)

840 395 25.6 7.5 1.29 .78 .93 1.00 24.4 7.2 1.51 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.01 .85 1.00 1.00(17�C)

1050 495 26.8 7.9 1.29 .84 1.00 1.00 25.6 7.5 1.51 .86 1.00 1.00 24.2 7.1 1.75 .89 1.00 1.00 23.0 6.7 2.02 .92 1.00 1.00

67�F840 395 27.2 8.0 1.29 .62 .76 .90 25.8 7.6 1.51 .63 .78 .92 24.4 7.2 1.75 .64 .80 .95 22.8 6.7 2.03 .65 .83 .99

67�F(19�C)

840 395 27.2 8.0 1.29 .62 .76 .90 25.8 7.6 1.51 .63 .78 .92 24.4 7.2 1.75 .64 .80 .95 22.8 6.7 2.03 .65 .83 .99(19�C)

1050 495 28.2 8.3 1.30 .65 .82 .97 26.8 7.9 1.51 .66 .84 1.00 25.2 7.4 1.75 .67 .86 1.00 23.6 6.9 2.02 .70 .90 1.00

71�F840 395 28.6 8.4 1.30 .46 .60 .73 27.2 8.0 1.52 .47 .61 .75 25.8 7.6 1.75 .47 .63 .77 24.2 7.1 2.02 .48 .64 .80

71�F(22�C)

840 395 28.6 8.4 1.30 .46 .60 .73 27.2 8.0 1.52 .47 .61 .75 25.8 7.6 1.75 .47 .63 .77 24.2 7.1 2.02 .48 .64 .80(22�C)

1050 495 29.8 8.7 1.31 .48 .64 .79 28.2 8.3 1.52 .48 .65 .81 26.8 7.9 1.76 .49 .67 .84 25.0 7.3 2.03 .50 .69 .87

Page 26: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 26

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−25B−6F + G61MPV−36B−070][C33−25B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 20.4 6.0 .77 .77 .91 1.00 19.4 5.7 .92 .79 .94 1.00 18.4 5.4 1.10 .81 .96 1.00 17.3 5.1 1.31 .83 .99 1.00

63�F(17�C)

625 295 20.4 6.0 .77 .77 .91 1.00 19.4 5.7 .92 .79 .94 1.00 18.4 5.4 1.10 .81 .96 1.00 17.3 5.1 1.31 .83 .99 1.00(17�C)

725 340 21.0 6.2 .77 .81 .96 1.00 20.0 5.9 .93 .82 .99 1.00 19.1 5.6 1.10 .85 1.00 1.00 18.1 5.3 1.30 .87 1.00 1.00

67�F625 295 21.6 6.3 .78 .61 .74 .88 20.8 6.1 .93 .61 .76 .90 19.7 5.8 1.10 .63 .78 .93 18.5 5.4 1.30 .64 .80 .96

67�F(19�C)

625 295 21.6 6.3 .78 .61 .74 .88 20.8 6.1 .93 .61 .76 .90 19.7 5.8 1.10 .63 .78 .93 18.5 5.4 1.30 .64 .80 .96(19�C)

725 340 22.4 6.6 .78 .63 .78 .92 21.4 6.3 .93 .64 .80 .95 20.2 5.9 1.10 .65 .82 .97 19.0 5.6 1.30 .66 .84 1.00

71�F625 295 23.0 6.7 .78 .46 .59 .72 22.0 6.4 .93 .46 .60 .73 21.0 6.2 1.10 .47 .61 .75 19.8 5.8 1.30 .47 .62 .77

71�F(22�C)

625 295 23.0 6.7 .78 .46 .59 .72 22.0 6.4 .93 .46 .60 .73 21.0 6.2 1.10 .47 .61 .75 19.8 5.8 1.30 .47 .62 .77(22�C)

725 340 23.8 7.0 .79 .47 .61 .75 22.8 6.7 .93 .47 .62 .76 21.6 6.3 1.10 .48 .64 .79 20.4 6.0 1.30 .48 .65 .82

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−25B−6F + G61MPV−36B−070][C33−25B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F830 390 25.6 7.5 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .95 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.01 .84 1.00 1.00

63�F(17�C)

830 390 25.6 7.5 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .95 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.01 .84 1.00 1.00(17�C)

1020 480 26.6 7.8 1.29 .83 .99 1.00 25.4 7.4 1.50 .85 1.00 1.00 24.0 7.0 1.74 .87 1.00 1.00 22.8 6.7 2.03 .91 1.00 1.00

67�F830 390 27.0 7.9 1.29 .61 .76 .89 25.8 7.6 1.51 .62 .77 .92 24.4 7.2 1.75 .64 .80 .95 22.8 6.7 2.02 .65 .82 .98

67�F(19�C)

830 390 27.0 7.9 1.29 .61 .76 .89 25.8 7.6 1.51 .62 .77 .92 24.4 7.2 1.75 .64 .80 .95 22.8 6.7 2.02 .65 .82 .98(19�C)

1020 480 28.0 8.2 1.30 .64 .81 .96 26.6 7.8 1.51 .65 .83 .99 25.2 7.4 1.75 .67 .85 1.00 23.6 6.9 2.03 .69 .89 1.00

71�F830 390 28.6 8.4 1.30 .46 .60 .73 27.2 8.0 1.51 .47 .61 .75 25.8 7.6 1.75 .47 .62 .77 24.2 7.1 2.02 .48 .64 .80

71�F(22�C)

830 390 28.6 8.4 1.30 .46 .60 .73 27.2 8.0 1.51 .47 .61 .75 25.8 7.6 1.75 .47 .62 .77 24.2 7.1 2.02 .48 .64 .80(22�C)

1020 480 29.6 8.7 1.31 .48 .63 .78 28.2 8.3 1.52 .48 .64 .80 26.6 7.8 1.76 .49 .66 .83 25.0 7.3 2.02 .49 .68 .86

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−30A−6F + G60UHV−36A−070][C33−30A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F630 295 19.5 5.7 .77 .77 .90 1.00 18.7 5.5 .92 .78 .93 1.00 17.8 5.2 1.10 .80 .95 1.00 16.8 4.9 1.30 .82 .98 1.00

63�F(17�C)

630 295 19.5 5.7 .77 .77 .90 1.00 18.7 5.5 .92 .78 .93 1.00 17.8 5.2 1.10 .80 .95 1.00 16.8 4.9 1.30 .82 .98 1.00(17�C)

745 350 20.2 5.9 .77 .80 .95 1.00 19.4 5.7 .93 .82 .97 1.00 18.6 5.5 1.10 .84 .99 1.00 17.7 5.2 1.30 .87 1.00 1.00

67�F630 295 20.8 6.1 .77 .61 .74 .87 19.9 5.8 .93 .62 .76 .89 19.0 5.6 1.10 .63 .77 .91 18.0 5.3 1.30 .64 .80 .94

67�F(19�C)

630 295 20.8 6.1 .77 .61 .74 .87 19.9 5.8 .93 .62 .76 .89 19.0 5.6 1.10 .63 .77 .91 18.0 5.3 1.30 .64 .80 .94(19�C)

745 350 21.6 6.3 .78 .63 .77 .91 20.6 6.0 .93 .64 .79 .94 19.6 5.7 1.10 .65 .81 .97 18.5 5.4 1.30 .67 .84 .99

71�F630 295 21.8 6.4 .78 .47 .60 .72 21.0 6.2 .93 .47 .60 .73 20.0 5.9 1.10 .47 .62 .75 18.9 5.5 1.30 .48 .63 .77

71�F(22�C)

630 295 21.8 6.4 .78 .47 .60 .72 21.0 6.2 .93 .47 .60 .73 20.0 5.9 1.10 .47 .62 .75 18.9 5.5 1.30 .48 .63 .77(22�C)

745 350 22.8 6.7 .78 .47 .62 .75 21.8 6.4 .93 .48 .63 .76 20.8 6.1 1.10 .48 .64 .79 19.6 5.7 1.30 .49 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−30A−6F + G60UHV−36A−070][C33−30A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F830 390 24.8 7.3 1.29 .77 .91 1.00 23.6 6.9 1.50 .79 .94 1.00 22.2 6.5 1.74 .81 .97 1.00 21.0 6.2 2.01 .83 .99 1.00

63�F(17�C)

830 390 24.8 7.3 1.29 .77 .91 1.00 23.6 6.9 1.50 .79 .94 1.00 22.2 6.5 1.74 .81 .97 1.00 21.0 6.2 2.01 .83 .99 1.00(17�C)

1040 490 25.8 7.6 1.29 .82 .98 1.00 24.6 7.2 1.50 .84 .99 1.00 23.6 6.9 1.74 .86 1.00 1.00 22.2 6.5 2.02 .90 1.00 1.00

67�F830 390 26.0 7.6 1.29 .62 .75 .88 24.8 7.3 1.51 .62 .77 .90 23.6 6.9 1.75 .64 .78 .93 22.2 6.5 2.02 .65 .81 .97

67�F(19�C)

830 390 26.0 7.6 1.29 .62 .75 .88 24.8 7.3 1.51 .62 .77 .90 23.6 6.9 1.75 .64 .78 .93 22.2 6.5 2.02 .65 .81 .97(19�C)

1040 490 27.2 8.0 1.30 .64 .79 .95 25.8 7.6 1.51 .65 .81 .98 24.4 7.2 1.74 .67 .84 .99 23.0 6.7 2.01 .69 .87 1.00

71�F830 390 27.4 8.0 1.29 .46 .60 .73 26.2 7.7 1.51 .47 .61 .74 24.8 7.3 1.75 .48 .62 .76 23.4 6.9 2.03 .48 .64 .78

71�F(22�C)

830 390 27.4 8.0 1.29 .46 .60 .73 26.2 7.7 1.51 .47 .61 .74 24.8 7.3 1.75 .48 .62 .76 23.4 6.9 2.03 .48 .64 .78(22�C)

1040 490 28.6 8.4 1.30 .48 .63 .77 27.2 8.0 1.52 .49 .64 .79 25.8 7.6 1.75 .49 .66 .82 24.2 7.1 2.02 .50 .68 .85

Page 27: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 27

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−30B−6F + G60UHV−36B−090][C33−30B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 19.5 5.7 .77 .76 .90 1.00 18.7 5.5 .92 .78 .92 1.00 17.8 5.2 1.10 .80 .95 1.00 16.8 4.9 1.30 .82 .98 1.00

63�F(17�C)

625 295 19.5 5.7 .77 .76 .90 1.00 18.7 5.5 .92 .78 .92 1.00 17.8 5.2 1.10 .80 .95 1.00 16.8 4.9 1.30 .82 .98 1.00(17�C)

740 350 20.2 5.9 .77 .80 .95 1.00 19.4 5.7 .93 .81 .97 1.00 18.6 5.5 1.10 .84 .99 1.00 17.7 5.2 1.30 .86 1.00 1.00

67�F625 295 20.8 6.1 .77 .61 .74 .86 19.9 5.8 .93 .62 .75 .89 18.9 5.5 1.10 .63 .77 .91 17.9 5.2 1.30 .64 .79 .94

67�F(19�C)

625 295 20.8 6.1 .77 .61 .74 .86 19.9 5.8 .93 .62 .75 .89 18.9 5.5 1.10 .63 .77 .91 17.9 5.2 1.30 .64 .79 .94(19�C)

740 350 21.6 6.3 .78 .63 .77 .91 20.6 6.0 .93 .64 .79 .94 19.6 5.7 1.10 .65 .81 .96 18.5 5.4 1.30 .67 .83 .99

71�F625 295 21.8 6.4 .78 .46 .60 .72 21.0 6.2 .93 .46 .60 .73 20.0 5.9 1.10 .47 .61 .75 18.9 5.5 1.30 .48 .63 .77

71�F(22�C)

625 295 21.8 6.4 .78 .46 .60 .72 21.0 6.2 .93 .46 .60 .73 20.0 5.9 1.10 .47 .61 .75 18.9 5.5 1.30 .48 .63 .77(22�C)

740 350 22.8 6.7 .78 .47 .61 .75 21.8 6.4 .93 .48 .63 .76 20.8 6.1 1.10 .48 .64 .78 19.6 5.7 1.30 .49 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−30B−6F + G60UHV−36B−090][C33−30B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F825 390 24.6 7.2 1.29 .77 .91 1.00 23.6 6.9 1.50 .79 .93 1.00 22.2 6.5 1.74 .81 .96 1.00 21.0 6.2 2.01 .83 .99 1.00

63�F(17�C)

825 390 24.6 7.2 1.29 .77 .91 1.00 23.6 6.9 1.50 .79 .93 1.00 22.2 6.5 1.74 .81 .96 1.00 21.0 6.2 2.01 .83 .99 1.00(17�C)

1035 490 25.8 7.6 1.29 .82 .98 1.00 24.6 7.2 1.50 .84 .99 1.00 23.6 6.9 1.74 .86 1.00 1.00 22.2 6.5 2.02 .89 1.00 1.00

67�F825 390 26.0 7.6 1.29 .61 .75 .88 24.8 7.3 1.51 .62 .76 .90 23.6 6.9 1.75 .63 .78 .93 22.2 6.5 2.02 .65 .81 .96

67�F(19�C)

825 390 26.0 7.6 1.29 .61 .75 .88 24.8 7.3 1.51 .62 .76 .90 23.6 6.9 1.75 .63 .78 .93 22.2 6.5 2.02 .65 .81 .96(19�C)

1035 490 27.2 8.0 1.30 .64 .79 .95 25.8 7.6 1.51 .65 .81 .97 24.4 7.2 1.74 .67 .84 .99 23.0 6.7 2.02 .69 .87 1.00

71�F825 390 27.2 8.0 1.29 .47 .60 .72 26.0 7.6 1.51 .47 .61 .74 24.8 7.3 1.75 .48 .62 .76 23.2 6.8 2.02 .48 .64 .78

71�F(22�C)

825 390 27.2 8.0 1.29 .47 .60 .72 26.0 7.6 1.51 .47 .61 .74 24.8 7.3 1.75 .48 .62 .76 23.2 6.8 2.02 .48 .64 .78(22�C)

1035 490 28.6 8.4 1.30 .48 .63 .77 27.2 8.0 1.52 .49 .64 .79 25.8 7.6 1.75 .49 .66 .82 24.2 7.1 2.02 .50 .68 .85

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−30B−6F + G61MPV−36B−045][C33−30B + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F610 290 19.4 5.7 .77 .76 .89 1.00 18.6 5.5 .93 .78 .92 1.00 17.7 5.2 1.10 .79 .94 1.00 16.7 4.9 1.30 .82 .98 1.00

63�F(17�C)

610 290 19.4 5.7 .77 .76 .89 1.00 18.6 5.5 .93 .78 .92 1.00 17.7 5.2 1.10 .79 .94 1.00 16.7 4.9 1.30 .82 .98 1.00(17�C)

725 340 20.2 5.9 .77 .79 .94 1.00 19.3 5.7 .93 .81 .97 1.00 18.4 5.4 1.10 .83 .99 1.00 17.6 5.2 1.30 .86 1.00 1.00

67�F610 290 20.6 6.0 .77 .61 .74 .86 19.8 5.8 .93 .61 .75 .88 18.8 5.5 1.10 .63 .77 .90 17.8 5.2 1.30 .64 .79 .93

67�F(19�C)

610 290 20.6 6.0 .77 .61 .74 .86 19.8 5.8 .93 .61 .75 .88 18.8 5.5 1.10 .63 .77 .90 17.8 5.2 1.30 .64 .79 .93(19�C)

725 340 21.4 6.3 .78 .63 .77 .91 20.6 6.0 .93 .64 .78 .93 19.5 5.7 1.10 .65 .80 .96 18.5 5.4 1.30 .66 .83 .98

71�F610 290 21.6 6.3 .78 .46 .59 .71 20.8 6.1 .93 .47 .60 .72 19.9 5.8 1.10 .47 .61 .74 18.8 5.5 1.30 .47 .62 .76

71�F(22�C)

610 290 21.6 6.3 .78 .46 .59 .71 20.8 6.1 .93 .47 .60 .72 19.9 5.8 1.10 .47 .61 .74 18.8 5.5 1.30 .47 .62 .76(22�C)

725 340 22.6 6.6 .78 .47 .61 .74 21.6 6.3 .93 .48 .62 .76 20.6 6.0 1.10 .48 .63 .78 19.5 5.7 1.30 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−30B−6F + G61MPV−36B−045][C33−30B + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F840 395 24.8 7.3 1.29 .77 .91 1.00 23.6 6.9 1.50 .79 .94 1.00 22.4 6.6 1.74 .81 .97 1.00 21.0 6.2 2.01 .84 .99 1.00

63�F(17�C)

840 395 24.8 7.3 1.29 .77 .91 1.00 23.6 6.9 1.50 .79 .94 1.00 22.4 6.6 1.74 .81 .97 1.00 21.0 6.2 2.01 .84 .99 1.00(17�C)

1050 495 25.8 7.6 1.29 .82 .98 1.00 24.8 7.3 1.50 .84 1.00 1.00 23.6 6.9 1.74 .87 1.00 1.00 22.4 6.6 2.02 .90 1.00 1.00

67�F840 395 26.2 7.7 1.29 .62 .75 .88 25.0 7.3 1.51 .63 .77 .91 23.6 6.9 1.75 .64 .79 .93 22.2 6.5 2.02 .65 .81 .97

67�F(19�C)

840 395 26.2 7.7 1.29 .62 .75 .88 25.0 7.3 1.51 .63 .77 .91 23.6 6.9 1.75 .64 .79 .93 22.2 6.5 2.02 .65 .81 .97(19�C)

1050 495 27.2 8.0 1.30 .64 .80 .95 26.0 7.6 1.51 .65 .82 .98 24.6 7.2 1.74 .67 .85 1.00 23.0 6.7 2.01 .69 .88 1.00

71�F840 395 27.4 8.0 1.29 .46 .60 .73 26.2 7.7 1.51 .47 .61 .74 24.8 7.3 1.75 .48 .63 .76 23.4 6.9 2.03 .48 .64 .79

71�F(22�C)

840 395 27.4 8.0 1.29 .46 .60 .73 26.2 7.7 1.51 .47 .61 .74 24.8 7.3 1.75 .48 .63 .76 23.4 6.9 2.03 .48 .64 .79(22�C)

1050 495 28.6 8.4 1.30 .48 .63 .78 27.2 8.0 1.52 .49 .64 .80 25.8 7.6 1.75 .49 .66 .82 24.2 7.1 2.02 .50 .68 .85

Page 28: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 28

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−31A−6F + G60UHV−36A−070][C33−31A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F630 295 20.6 6.0 .77 .77 .92 1.00 19.6 5.7 .93 .79 .94 1.00 18.6 5.5 1.10 .81 .97 1.00 17.5 5.1 1.30 .83 .99 1.00

63�F(17�C)

630 295 20.6 6.0 .77 .77 .92 1.00 19.6 5.7 .93 .79 .94 1.00 18.6 5.5 1.10 .81 .97 1.00 17.5 5.1 1.30 .83 .99 1.00(17�C)

745 350 21.4 6.3 .77 .81 .97 1.00 20.4 6.0 .93 .83 .99 1.00 19.4 5.7 1.10 .85 1.00 1.00 18.4 5.4 1.30 .88 1.00 1.00

67�F630 295 22.0 6.4 .78 .60 .75 .88 21.0 6.2 .93 .62 .76 .90 19.9 5.8 1.10 .63 .78 .93 18.7 5.5 1.30 .64 .80 .96

67�F(19�C)

630 295 22.0 6.4 .78 .60 .75 .88 21.0 6.2 .93 .62 .76 .90 19.9 5.8 1.10 .63 .78 .93 18.7 5.5 1.30 .64 .80 .96(19�C)

745 350 22.8 6.7 .78 .63 .78 .93 21.6 6.3 .93 .64 .80 .95 20.6 6.0 1.10 .65 .82 .98 19.4 5.7 1.30 .67 .85 1.00

71�F630 295 23.4 6.9 .78 .46 .59 .72 22.4 6.6 .93 .46 .60 .73 21.2 6.2 1.10 .46 .61 .75 20.0 5.9 1.30 .47 .62 .77

71�F(22�C)

630 295 23.4 6.9 .78 .46 .59 .72 22.4 6.6 .93 .46 .60 .73 21.2 6.2 1.10 .46 .61 .75 20.0 5.9 1.30 .47 .62 .77(22�C)

745 350 24.2 7.1 .79 .47 .61 .76 23.2 6.8 .93 .47 .62 .77 22.0 6.4 1.10 .47 .64 .79 20.6 6.0 1.30 .48 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−31A−6F + G60UHV−36A−070][C33−31A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F830 390 26.0 7.6 1.29 .78 .93 1.00 24.6 7.2 1.51 .80 .95 1.00 23.2 6.8 1.75 .81 .98 1.00 21.8 6.4 2.02 .84 1.00 1.00

63�F(17�C)

830 390 26.0 7.6 1.29 .78 .93 1.00 24.6 7.2 1.51 .80 .95 1.00 23.2 6.8 1.75 .81 .98 1.00 21.8 6.4 2.02 .84 1.00 1.00(17�C)

1040 490 27.0 7.9 1.30 .83 1.00 1.00 25.8 7.6 1.51 .85 1.00 1.00 24.6 7.2 1.75 .88 1.00 1.00 23.2 6.8 2.02 .91 1.00 1.00

67�F830 390 27.4 8.0 1.30 .61 .75 .89 26.0 7.6 1.51 .62 .77 .92 24.6 7.2 1.75 .63 .79 .95 23.0 6.7 2.02 .65 .82 .98

67�F(19�C)

830 390 27.4 8.0 1.30 .61 .75 .89 26.0 7.6 1.51 .62 .77 .92 24.6 7.2 1.75 .63 .79 .95 23.0 6.7 2.02 .65 .82 .98(19�C)

1040 490 28.6 8.4 1.30 .64 .81 .97 27.2 8.0 1.51 .65 .83 .99 25.6 7.5 1.75 .67 .86 1.00 24.0 7.0 2.02 .69 .89 1.00

71�F830 390 29.0 8.5 1.30 .46 .60 .73 27.6 8.1 1.52 .46 .61 .75 26.0 7.6 1.75 .47 .62 .76 24.4 7.2 2.03 .48 .64 .79

71�F(22�C)

830 390 29.0 8.5 1.30 .46 .60 .73 27.6 8.1 1.52 .46 .61 .75 26.0 7.6 1.75 .47 .62 .76 24.4 7.2 2.03 .48 .64 .79(22�C)

1040 490 30.2 8.9 1.31 .48 .63 .79 28.6 8.4 1.52 .48 .64 .81 27.0 7.9 1.76 .48 .65 .83 25.4 7.4 2.03 .50 .68 .86

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−31B−6F + G60UHV−36B−090][C33−31B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 20.6 6.0 .77 .77 .92 1.00 19.6 5.7 .93 .79 .94 1.00 18.6 5.5 1.10 .81 .96 1.00 17.5 5.1 1.30 .83 .99 1.00

63�F(17�C)

625 295 20.6 6.0 .77 .77 .92 1.00 19.6 5.7 .93 .79 .94 1.00 18.6 5.5 1.10 .81 .96 1.00 17.5 5.1 1.30 .83 .99 1.00(17�C)

740 350 21.4 6.3 .78 .81 .97 1.00 20.4 6.0 .92 .83 .99 1.00 19.4 5.7 1.10 .85 1.00 1.00 18.4 5.4 1.30 .88 1.00 1.00

67�F625 295 22.0 6.4 .78 .60 .74 .88 21.0 6.2 .93 .62 .76 .90 19.9 5.8 1.10 .63 .78 .92 18.7 5.5 1.30 .64 .80 .95

67�F(19�C)

625 295 22.0 6.4 .78 .60 .74 .88 21.0 6.2 .93 .62 .76 .90 19.9 5.8 1.10 .63 .78 .92 18.7 5.5 1.30 .64 .80 .95(19�C)

740 350 22.8 6.7 .78 .63 .78 .93 21.6 6.3 .93 .64 .80 .95 20.6 6.0 1.10 .65 .82 .98 19.3 5.7 1.30 .67 .85 1.00

71�F625 295 23.4 6.9 .78 .46 .59 .72 22.2 6.5 .93 .46 .60 .73 21.2 6.2 1.10 .46 .61 .75 20.0 5.9 1.30 .47 .62 .76

71�F(22�C)

625 295 23.4 6.9 .78 .46 .59 .72 22.2 6.5 .93 .46 .60 .73 21.2 6.2 1.10 .46 .61 .75 20.0 5.9 1.30 .47 .62 .76(22�C)

740 350 24.2 7.1 .79 .47 .61 .75 23.0 6.7 .93 .47 .62 .77 22.0 6.4 1.10 .47 .64 .80 20.6 6.0 1.30 .48 .65 .82

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−31B−6F + G60UHV−36B−090][C33−31B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F825 390 25.8 7.6 1.29 .78 .93 1.00 24.6 7.2 1.51 .79 .95 1.00 23.2 6.8 1.75 .81 .98 1.00 21.8 6.4 2.01 .84 1.00 1.00

63�F(17�C)

825 390 25.8 7.6 1.29 .78 .93 1.00 24.6 7.2 1.51 .79 .95 1.00 23.2 6.8 1.75 .81 .98 1.00 21.8 6.4 2.01 .84 1.00 1.00(17�C)

1035 490 27.0 7.9 1.30 .83 .99 1.00 25.8 7.6 1.51 .85 1.00 1.00 24.6 7.2 1.75 .88 1.00 1.00 23.2 6.8 2.02 .91 1.00 1.00

67�F825 390 27.4 8.0 1.30 .61 .75 .89 26.0 7.6 1.51 .62 .77 .92 24.6 7.2 1.75 .63 .78 .94 23.0 6.7 2.01 .65 .82 .98

67�F(19�C)

825 390 27.4 8.0 1.30 .61 .75 .89 26.0 7.6 1.51 .62 .77 .92 24.6 7.2 1.75 .63 .78 .94 23.0 6.7 2.01 .65 .82 .98(19�C)

1035 490 28.6 8.4 1.30 .64 .81 .97 27.2 8.0 1.51 .65 .83 .99 25.6 7.5 1.75 .67 .86 1.00 24.0 7.0 2.02 .69 .89 1.00

71�F825 390 29.0 8.5 1.30 .46 .60 .73 27.6 8.1 1.52 .46 .61 .75 26.0 7.6 1.75 .47 .62 .76 24.4 7.2 2.03 .47 .63 .79

71�F(22�C)

825 390 29.0 8.5 1.30 .46 .60 .73 27.6 8.1 1.52 .46 .61 .75 26.0 7.6 1.75 .47 .62 .76 24.4 7.2 2.03 .47 .63 .79(22�C)

1035 490 30.2 8.9 1.31 .48 .63 .78 28.6 8.4 1.52 .48 .64 .80 27.0 7.9 1.76 .48 .65 .83 25.4 7.4 2.03 .50 .68 .86

Page 29: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 29

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−31B−6F + G61MPV−36B−045][C33−31B + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F610 290 20.4 6.0 .77 .76 .91 1.00 19.5 5.7 .93 .78 .93 1.00 18.5 5.4 1.10 .80 .96 1.00 17.4 5.1 1.30 .82 .99 1.00

63�F(17�C)

610 290 20.4 6.0 .77 .76 .91 1.00 19.5 5.7 .93 .78 .93 1.00 18.5 5.4 1.10 .80 .96 1.00 17.4 5.1 1.30 .82 .99 1.00(17�C)

725 340 21.2 6.2 .78 .80 .96 1.00 20.2 5.9 .92 .82 .98 1.00 19.2 5.6 1.10 .84 1.00 1.00 18.3 5.4 1.30 .87 1.00 1.00

67�F610 290 21.8 6.4 .78 .60 .74 .87 20.8 6.1 .93 .61 .75 .89 19.8 5.8 1.10 .62 .77 .92 18.6 5.5 1.30 .63 .79 .95

67�F(19�C)

610 290 21.8 6.4 .78 .60 .74 .87 20.8 6.1 .93 .61 .75 .89 19.8 5.8 1.10 .62 .77 .92 18.6 5.5 1.30 .63 .79 .95(19�C)

725 340 22.6 6.6 .78 .63 .78 .92 21.6 6.3 .93 .63 .79 .95 20.4 6.0 1.10 .64 .81 .97 19.3 5.7 1.30 .66 .84 1.00

71�F610 290 23.2 6.8 .78 .46 .59 .71 22.2 6.5 .93 .46 .59 .73 21.0 6.2 1.10 .47 .61 .74 19.9 5.8 1.30 .47 .62 .76

71�F(22�C)

610 290 23.2 6.8 .78 .46 .59 .71 22.2 6.5 .93 .46 .59 .73 21.0 6.2 1.10 .47 .61 .74 19.9 5.8 1.30 .47 .62 .76(22�C)

725 340 24.0 7.0 .79 .47 .61 .75 23.0 6.7 .94 .47 .62 .77 21.8 6.4 1.10 .47 .63 .79 20.6 6.0 1.30 .48 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−31B−6F + G61MPV−36B−045][C33−31B + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F840 395 26.0 7.6 1.29 .78 .93 1.00 24.6 7.2 1.51 .80 .96 1.00 23.4 6.9 1.75 .82 .98 1.00 21.8 6.4 2.02 .84 1.00 1.00

63�F(17�C)

840 395 26.0 7.6 1.29 .78 .93 1.00 24.6 7.2 1.51 .80 .96 1.00 23.4 6.9 1.75 .82 .98 1.00 21.8 6.4 2.02 .84 1.00 1.00(17�C)

1050 495 27.2 8.0 1.29 .83 1.00 1.00 26.0 7.6 1.51 .86 1.00 1.00 24.6 7.2 1.75 .89 1.00 1.00 23.2 6.8 2.02 .92 1.00 1.00

67�F840 395 27.6 8.1 1.30 .61 .76 .90 26.2 7.7 1.51 .62 .77 .92 24.6 7.2 1.75 .63 .79 .95 23.2 6.8 2.02 .65 .82 .98

67�F(19�C)

840 395 27.6 8.1 1.30 .61 .76 .90 26.2 7.7 1.51 .62 .77 .92 24.6 7.2 1.75 .63 .79 .95 23.2 6.8 2.02 .65 .82 .98(19�C)

1050 495 28.6 8.4 1.30 .64 .81 .97 27.2 8.0 1.52 .66 .83 .99 25.6 7.5 1.75 .68 .86 1.00 24.0 7.0 2.02 .69 .89 1.00

71�F840 395 29.0 8.5 1.30 .46 .60 .74 27.6 8.1 1.52 .47 .61 .75 26.2 7.7 1.75 .47 .62 .76 24.6 7.2 2.02 .48 .64 .80

71�F(22�C)

840 395 29.0 8.5 1.30 .46 .60 .74 27.6 8.1 1.52 .47 .61 .75 26.2 7.7 1.75 .47 .62 .76 24.6 7.2 2.02 .48 .64 .80(22�C)

1050 495 30.2 8.9 1.31 .48 .63 .79 28.8 8.4 1.52 .48 .65 .81 27.2 8.0 1.76 .48 .67 .84 25.4 7.4 2.03 .50 .69 .87

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−31B−6F + G61MPV−36B−070][C33−31B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 20.6 6.0 .77 .77 .92 1.00 19.6 5.7 .93 .79 .94 1.00 18.6 5.5 1.10 .81 .96 1.00 17.5 5.1 1.30 .83 .99 1.00

63�F(17�C)

625 295 20.6 6.0 .77 .77 .92 1.00 19.6 5.7 .93 .79 .94 1.00 18.6 5.5 1.10 .81 .96 1.00 17.5 5.1 1.30 .83 .99 1.00(17�C)

725 340 21.2 6.2 .78 .80 .96 1.00 20.2 5.9 .92 .82 .98 1.00 19.3 5.7 1.10 .84 1.00 1.00 18.3 5.4 1.30 .87 1.00 1.00

67�F625 295 22.0 6.4 .78 .60 .74 .88 21.0 6.2 .93 .62 .76 .90 19.9 5.8 1.10 .63 .78 .92 18.7 5.5 1.30 .64 .80 .95

67�F(19�C)

625 295 22.0 6.4 .78 .60 .74 .88 21.0 6.2 .93 .62 .76 .90 19.9 5.8 1.10 .63 .78 .92 18.7 5.5 1.30 .64 .80 .95(19�C)

725 340 22.6 6.6 .78 .63 .78 .92 21.6 6.3 .93 .63 .79 .95 20.4 6.0 1.10 .64 .81 .97 19.3 5.7 1.30 .66 .84 1.00

71�F625 295 23.4 6.9 .78 .46 .59 .72 22.2 6.5 .93 .46 .60 .73 21.2 6.2 1.10 .46 .61 .75 20.0 5.9 1.30 .47 .62 .76

71�F(22�C)

625 295 23.4 6.9 .78 .46 .59 .72 22.2 6.5 .93 .46 .60 .73 21.2 6.2 1.10 .46 .61 .75 20.0 5.9 1.30 .47 .62 .76(22�C)

725 340 24.0 7.0 .79 .47 .61 .75 23.0 6.7 .94 .47 .62 .77 21.8 6.4 1.10 .47 .63 .79 20.6 6.0 1.30 .48 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−31B−6F + G61MPV−36B−070][C33−31B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F830 390 26.0 7.6 1.29 .78 .93 1.00 24.6 7.2 1.51 .80 .95 1.00 23.2 6.8 1.75 .81 .98 1.00 21.8 6.4 2.02 .84 1.00 1.00

63�F(17�C)

830 390 26.0 7.6 1.29 .78 .93 1.00 24.6 7.2 1.51 .80 .95 1.00 23.2 6.8 1.75 .81 .98 1.00 21.8 6.4 2.02 .84 1.00 1.00(17�C)

1020 480 27.0 7.9 1.29 .83 .99 1.00 25.6 7.5 1.51 .85 1.00 1.00 24.4 7.2 1.75 .88 1.00 1.00 23.0 6.7 2.02 .91 1.00 1.00

67�F830 390 27.4 8.0 1.30 .61 .75 .89 26.0 7.6 1.51 .62 .77 .92 24.6 7.2 1.75 .63 .79 .95 23.0 6.7 2.02 .65 .82 .98

67�F(19�C)

830 390 27.4 8.0 1.30 .61 .75 .89 26.0 7.6 1.51 .62 .77 .92 24.6 7.2 1.75 .63 .79 .95 23.0 6.7 2.02 .65 .82 .98(19�C)

1020 480 28.4 8.3 1.30 .63 .80 .96 27.0 7.9 1.52 .65 .82 .98 25.6 7.5 1.75 .67 .85 1.00 24.0 7.0 2.02 .69 .88 1.00

71�F830 390 29.0 8.5 1.30 .46 .60 .73 27.6 8.1 1.52 .46 .61 .75 26.0 7.6 1.75 .47 .62 .76 24.4 7.2 2.03 .48 .64 .79

71�F(22�C)

830 390 29.0 8.5 1.30 .46 .60 .73 27.6 8.1 1.52 .46 .61 .75 26.0 7.6 1.75 .47 .62 .76 24.4 7.2 2.03 .48 .64 .79(22�C)

1020 480 30.0 8.8 1.31 .47 .63 .78 28.6 8.4 1.52 .48 .64 .80 27.0 7.9 1.76 .48 .65 .83 25.2 7.4 2.03 .49 .68 .86

Page 30: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 30

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−36A−6F + G60UHV−36A−070][C33−36A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F630 295 20.4 6.0 .77 .78 .92 1.00 19.4 5.7 .93 .79 .95 1.00 18.5 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .84 1.00 1.00

63�F(17�C)

630 295 20.4 6.0 .77 .78 .92 1.00 19.4 5.7 .93 .79 .95 1.00 18.5 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .84 1.00 1.00(17�C)

745 350 21.2 6.2 .78 .82 .97 1.00 20.2 5.9 .93 .83 .99 1.00 19.3 5.7 1.10 .86 1.00 1.00 18.3 5.4 1.30 .89 1.00 1.00

67�F630 295 21.4 6.3 .78 .61 .75 .89 20.6 6.0 .93 .62 .77 .91 19.5 5.7 1.10 .63 .79 .94 18.4 5.4 1.30 .65 .81 .97

67�F(19�C)

630 295 21.4 6.3 .78 .61 .75 .89 20.6 6.0 .93 .62 .77 .91 19.5 5.7 1.10 .63 .79 .94 18.4 5.4 1.30 .65 .81 .97(19�C)

745 350 22.2 6.5 .78 .64 .79 .94 21.4 6.3 .93 .65 .81 .96 20.2 5.9 1.10 .66 .83 .99 19.0 5.6 1.30 .68 .86 1.00

71�F630 295 22.4 6.6 .78 .46 .60 .73 21.6 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.4 5.7 1.30 .47 .63 .78

71�F(22�C)

630 295 22.4 6.6 .78 .46 .60 .73 21.6 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.4 5.7 1.30 .47 .63 .78(22�C)

745 350 23.4 6.9 .78 .47 .62 .77 22.4 6.6 .93 .48 .63 .78 21.4 6.3 1.10 .48 .65 .81 20.2 5.9 1.30 .49 .66 .83

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−36A−6F + G60UHV−36A−070][C33−36A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F830 390 25.6 7.5 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .85 1.00 1.00

63�F(17�C)

830 390 25.6 7.5 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .85 1.00 1.00(17�C)

1040 490 26.8 7.9 1.29 .84 1.00 1.00 25.6 7.5 1.51 .86 1.00 1.00 24.2 7.1 1.75 .89 1.00 1.00 23.0 6.7 2.02 .92 1.00 1.00

67�F830 390 26.8 7.9 1.29 .62 .76 .90 25.6 7.5 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .83 .98

67�F(19�C)

830 390 26.8 7.9 1.29 .62 .76 .90 25.6 7.5 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .83 .98(19�C)

1040 490 28.0 8.2 1.30 .65 .82 .97 26.6 7.8 1.51 .66 .84 .99 25.0 7.3 1.74 .68 .87 1.00 23.4 6.9 2.02 .70 .90 1.00

71�F830 390 28.0 8.2 1.30 .47 .61 .74 26.8 7.9 1.51 .47 .62 .76 25.4 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .65 .80

71�F(22�C)

830 390 28.0 8.2 1.30 .47 .61 .74 26.8 7.9 1.51 .47 .62 .76 25.4 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .65 .80(22�C)

1040 490 29.4 8.6 1.30 .48 .64 .80 28.0 8.2 1.52 .49 .65 .82 26.4 7.7 1.76 .49 .67 .84 24.8 7.3 2.02 .50 .69 .88

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−36B−6F + G60UHV−36B−090][C33−36B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 20.2 5.9 .77 .78 .92 1.00 19.4 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .84 1.00 1.00

63�F(17�C)

625 295 20.2 5.9 .77 .78 .92 1.00 19.4 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .84 1.00 1.00(17�C)

740 350 21.2 6.2 .78 .82 .97 1.00 20.2 5.9 .93 .83 .99 1.00 19.3 5.7 1.10 .86 1.00 1.00 18.3 5.4 1.30 .89 1.00 1.00

67�F625 295 21.4 6.3 .78 .61 .75 .89 20.4 6.0 .93 .62 .77 .91 19.5 5.7 1.10 .63 .79 .93 18.3 5.4 1.30 .65 .81 .96

67�F(19�C)

625 295 21.4 6.3 .78 .61 .75 .89 20.4 6.0 .93 .62 .77 .91 19.5 5.7 1.10 .63 .79 .93 18.3 5.4 1.30 .65 .81 .96(19�C)

740 350 22.2 6.5 .78 .64 .79 .94 21.2 6.2 .93 .65 .81 .96 20.2 5.9 1.10 .66 .83 .99 19.0 5.6 1.30 .68 .86 1.00

71�F625 295 22.4 6.6 .78 .46 .60 .73 21.6 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78

71�F(22�C)

625 295 22.4 6.6 .78 .46 .60 .73 21.6 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78(22�C)

740 350 23.4 6.9 .78 .47 .62 .76 22.4 6.6 .93 .48 .63 .78 21.2 6.2 1.10 .48 .65 .80 20.0 5.9 1.30 .49 .66 .83

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−36B−6F + G60UHV−36B−090][C33−36B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F825 390 25.4 7.4 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .85 1.00 1.00

63�F(17�C)

825 390 25.4 7.4 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .85 1.00 1.00(17�C)

1035 490 26.8 7.9 1.29 .84 1.00 1.00 25.6 7.5 1.51 .86 1.00 1.00 24.2 7.1 1.75 .89 1.00 1.00 23.0 6.7 2.02 .92 1.00 1.00

67�F825 390 26.8 7.9 1.29 .62 .76 .90 25.4 7.4 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .83 .98

67�F(19�C)

825 390 26.8 7.9 1.29 .62 .76 .90 25.4 7.4 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .83 .98(19�C)

1035 490 28.0 8.2 1.30 .65 .82 .97 26.6 7.8 1.51 .66 .84 .99 25.0 7.3 1.74 .68 .87 1.00 23.4 6.9 2.02 .70 .90 1.00

71�F825 390 28.0 8.2 1.30 .47 .61 .74 26.6 7.8 1.51 .47 .62 .75 25.2 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .64 .80

71�F(22�C)

825 390 28.0 8.2 1.30 .47 .61 .74 26.6 7.8 1.51 .47 .62 .75 25.2 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .64 .80(22�C)

1035 490 29.2 8.6 1.30 .48 .64 .79 27.8 8.1 1.52 .49 .65 .82 26.4 7.7 1.76 .49 .67 .84 24.8 7.3 2.02 .50 .69 .87

Page 31: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 31

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−36B−6F + G61MPV−36B−045][C33−36B + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F610 290 20.2 5.9 .77 .77 .92 1.00 19.3 5.7 .93 .79 .94 1.00 18.3 5.4 1.10 .81 .96 1.00 17.3 5.1 1.31 .83 .99 1.00

63�F(17�C)

610 290 20.2 5.9 .77 .77 .92 1.00 19.3 5.7 .93 .79 .94 1.00 18.3 5.4 1.10 .81 .96 1.00 17.3 5.1 1.31 .83 .99 1.00(17�C)

725 340 21.0 6.2 .78 .81 .97 1.00 20.2 5.9 .93 .83 .99 1.00 19.2 5.6 1.10 .85 1.00 1.00 18.2 5.3 1.30 .88 1.00 1.00

67�F610 290 21.2 6.2 .78 .61 .75 .88 20.4 6.0 .93 .62 .76 .90 19.3 5.7 1.10 .63 .78 .93 18.3 5.4 1.30 .64 .80 .96

67�F(19�C)

610 290 21.2 6.2 .78 .61 .75 .88 20.4 6.0 .93 .62 .76 .90 19.3 5.7 1.10 .63 .78 .93 18.3 5.4 1.30 .64 .80 .96(19�C)

725 340 22.2 6.5 .78 .63 .78 .93 21.2 6.2 .93 .64 .80 .95 20.2 5.9 1.10 .66 .82 .98 18.9 5.5 1.30 .67 .85 1.00

71�F610 290 22.2 6.5 .78 .46 .59 .72 21.4 6.3 .93 .47 .60 .73 20.4 6.0 1.10 .47 .62 .75 19.2 5.6 1.30 .47 .63 .77

71�F(22�C)

610 290 22.2 6.5 .78 .46 .59 .72 21.4 6.3 .93 .47 .60 .73 20.4 6.0 1.10 .47 .62 .75 19.2 5.6 1.30 .47 .63 .77(22�C)

725 340 23.2 6.8 .78 .47 .62 .76 22.2 6.5 .93 .48 .63 .78 21.2 6.2 1.10 .48 .64 .80 20.0 5.9 1.30 .49 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−36B−6F + G61MPV−36B−045][C33−36B + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F840 395 25.6 7.5 1.29 .79 .94 1.00 24.4 7.2 1.50 .81 .96 1.00 23.0 6.7 1.74 .83 .99 1.00 21.8 6.4 2.02 .85 1.00 1.00

63�F(17�C)

840 395 25.6 7.5 1.29 .79 .94 1.00 24.4 7.2 1.50 .81 .96 1.00 23.0 6.7 1.74 .83 .99 1.00 21.8 6.4 2.02 .85 1.00 1.00(17�C)

1050 495 26.8 7.9 1.30 .84 1.00 1.00 25.6 7.5 1.51 .87 1.00 1.00 24.4 7.2 1.75 .89 1.00 1.00 23.0 6.7 2.02 .93 1.00 1.00

67�F840 395 26.8 7.9 1.30 .62 .76 .91 25.6 7.5 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .96 22.8 6.7 2.03 .66 .83 .99

67�F(19�C)

840 395 26.8 7.9 1.30 .62 .76 .91 25.6 7.5 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .96 22.8 6.7 2.03 .66 .83 .99(19�C)

1050 495 28.0 8.2 1.30 .65 .82 .98 26.6 7.8 1.51 .67 .84 1.00 25.2 7.4 1.75 .68 .87 1.00 23.6 6.9 2.03 .70 .90 1.00

71�F840 395 28.0 8.2 1.30 .47 .61 .74 26.8 7.9 1.51 .47 .62 .76 25.4 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .65 .81

71�F(22�C)

840 395 28.0 8.2 1.30 .47 .61 .74 26.8 7.9 1.51 .47 .62 .76 25.4 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .65 .81(22�C)

1050 495 29.4 8.6 1.30 .48 .64 .80 28.0 8.2 1.52 .49 .66 .82 26.4 7.7 1.75 .49 .67 .85 24.8 7.3 2.02 .50 .69 .88

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−36B−6F + G61MPV−36B−070][C33−36B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 20.2 5.9 .77 .78 .92 1.00 19.4 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .84 1.00 1.00

63�F(17�C)

625 295 20.2 5.9 .77 .78 .92 1.00 19.4 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .84 1.00 1.00(17�C)

725 340 21.0 6.2 .78 .81 .97 1.00 20.2 5.9 .92 .83 .99 1.00 19.2 5.6 1.10 .85 1.00 1.00 18.2 5.3 1.30 .88 1.00 1.00

67�F625 295 21.4 6.3 .78 .61 .75 .89 20.4 6.0 .93 .62 .77 .91 19.5 5.7 1.10 .63 .79 .93 18.3 5.4 1.30 .65 .81 .96

67�F(19�C)

625 295 21.4 6.3 .78 .61 .75 .89 20.4 6.0 .93 .62 .77 .91 19.5 5.7 1.10 .63 .79 .93 18.3 5.4 1.30 .65 .81 .96(19�C)

725 340 22.2 6.5 .78 .63 .78 .93 21.2 6.2 .93 .64 .80 .96 20.2 5.9 1.10 .66 .82 .98 19.0 5.6 1.30 .67 .85 1.00

71�F625 295 22.4 6.6 .78 .46 .60 .73 21.6 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78

71�F(22�C)

625 295 22.4 6.6 .78 .46 .60 .73 21.6 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78(22�C)

725 340 23.4 6.9 .78 .47 .62 .76 22.4 6.6 .93 .48 .63 .78 21.2 6.2 1.10 .48 .64 .80 20.0 5.9 1.30 .49 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−36B−6F + G61MPV−36B−070][C33−36B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F830 390 25.6 7.5 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .85 1.00 1.00

63�F(17�C)

830 390 25.6 7.5 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .85 1.00 1.00(17�C)

1020 480 26.6 7.8 1.29 .83 .99 1.00 25.4 7.4 1.51 .86 1.00 1.00 24.2 7.1 1.75 .88 1.00 1.00 22.8 6.7 2.02 .92 1.00 1.00

67�F830 390 26.8 7.9 1.29 .62 .76 .90 25.6 7.5 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .83 .98

67�F(19�C)

830 390 26.8 7.9 1.29 .62 .76 .90 25.6 7.5 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .83 .98(19�C)

1020 480 27.8 8.1 1.30 .65 .81 .97 26.4 7.7 1.51 .66 .83 .99 25.0 7.3 1.74 .68 .86 1.00 23.4 6.9 2.03 .70 .89 1.00

71�F830 390 28.0 8.2 1.30 .47 .61 .74 26.8 7.9 1.51 .47 .62 .76 25.4 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .65 .80

71�F(22�C)

830 390 28.0 8.2 1.30 .47 .61 .74 26.8 7.9 1.51 .47 .62 .76 25.4 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .65 .80(22�C)

1020 480 29.2 8.6 1.31 .48 .64 .79 27.8 8.1 1.52 .49 .65 .81 26.2 7.7 1.76 .49 .67 .84 24.6 7.2 2.02 .50 .69 .87

Page 32: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 32

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−38A−6F + G60UHV−36A−070][C33−38A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F630 295 20.8 6.1 .77 .78 .92 1.00 19.8 5.8 .93 .79 .95 1.00 18.8 5.5 1.10 .81 .97 1.00 17.7 5.2 1.30 .83 1.00 1.00

63�F(17�C)

630 295 20.8 6.1 .77 .78 .92 1.00 19.8 5.8 .93 .79 .95 1.00 18.8 5.5 1.10 .81 .97 1.00 17.7 5.2 1.30 .83 1.00 1.00(17�C)

745 350 21.6 6.3 .77 .81 .98 1.00 20.6 6.0 .93 .83 1.00 1.00 19.7 5.8 1.10 .86 1.00 1.00 18.6 5.5 1.30 .89 1.00 1.00

67�F630 295 22.2 6.5 .78 .61 .75 .88 21.2 6.2 .93 .62 .76 .91 20.0 5.9 1.10 .63 .78 .93 18.8 5.5 1.30 .64 .81 .96

67�F(19�C)

630 295 22.2 6.5 .78 .61 .75 .88 21.2 6.2 .93 .62 .76 .91 20.0 5.9 1.10 .63 .78 .93 18.8 5.5 1.30 .64 .81 .96(19�C)

745 350 23.0 6.7 .78 .63 .79 .94 21.8 6.4 .93 .64 .81 .96 20.8 6.1 1.10 .66 .83 .99 19.5 5.7 1.30 .67 .86 1.00

71�F630 295 23.6 6.9 .78 .46 .59 .72 22.4 6.6 .93 .46 .60 .74 21.4 6.3 1.10 .47 .61 .76 20.2 5.9 1.30 .47 .62 .77

71�F(22�C)

630 295 23.6 6.9 .78 .46 .59 .72 22.4 6.6 .93 .46 .60 .74 21.4 6.3 1.10 .47 .61 .76 20.2 5.9 1.30 .47 .62 .77(22�C)

745 350 24.4 7.2 .79 .47 .62 .76 23.4 6.9 .94 .47 .63 .78 22.2 6.5 1.10 .48 .64 .80 20.8 6.1 1.30 .48 .66 .83

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−38A−6F + G60UHV−36A−070][C33−38A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F830 390 26.2 7.7 1.29 .78 .93 1.00 24.8 7.3 1.51 .80 .96 1.00 23.4 6.9 1.74 .82 .99 1.00 22.0 6.4 2.02 .85 1.00 1.00

63�F(17�C)

830 390 26.2 7.7 1.29 .78 .93 1.00 24.8 7.3 1.51 .80 .96 1.00 23.4 6.9 1.74 .82 .99 1.00 22.0 6.4 2.02 .85 1.00 1.00(17�C)

1040 490 27.4 8.0 1.30 .84 1.00 1.00 26.2 7.7 1.51 .87 1.00 1.00 24.8 7.3 1.75 .89 1.00 1.00 23.4 6.9 2.02 .93 1.00 1.00

67�F830 390 27.6 8.1 1.30 .62 .76 .90 26.4 7.7 1.51 .63 .78 .93 24.8 7.3 1.75 .64 .80 .95 23.2 6.8 2.02 .65 .83 .99

67�F(19�C)

830 390 27.6 8.1 1.30 .62 .76 .90 26.4 7.7 1.51 .63 .78 .93 24.8 7.3 1.75 .64 .80 .95 23.2 6.8 2.02 .65 .83 .99(19�C)

1040 490 28.8 8.4 1.30 .65 .82 .98 27.4 8.0 1.52 .65 .84 1.00 25.8 7.6 1.76 .68 .87 1.00 24.2 7.1 2.02 .70 .90 1.00

71�F830 390 29.2 8.6 1.31 .46 .60 .74 27.8 8.1 1.52 .47 .61 .75 26.2 7.7 1.76 .47 .62 .77 24.6 7.2 2.02 .47 .64 .80

71�F(22�C)

830 390 29.2 8.6 1.31 .46 .60 .74 27.8 8.1 1.52 .47 .61 .75 26.2 7.7 1.76 .47 .62 .77 24.6 7.2 2.02 .47 .64 .80(22�C)

1040 490 30.4 8.9 1.31 .48 .64 .79 28.8 8.4 1.52 .48 .65 .82 27.2 8.0 1.76 .48 .67 .84 25.6 7.5 2.03 .50 .69 .88

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−38B−6F + G60UHV−36B−090][C33−38B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 20.2 5.9 .77 .78 .92 1.00 19.4 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .84 1.00 1.00

63�F(17�C)

625 295 20.2 5.9 .77 .78 .92 1.00 19.4 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .84 1.00 1.00(17�C)

740 350 21.2 6.2 .78 .82 .97 1.00 20.2 5.9 .93 .83 .99 1.00 19.3 5.7 1.10 .86 1.00 1.00 18.3 5.4 1.30 .89 1.00 1.00

67�F625 295 21.4 6.3 .78 .61 .75 .89 20.4 6.0 .93 .62 .77 .91 19.5 5.7 1.10 .63 .79 .93 18.3 5.4 1.30 .65 .81 .96

67�F(19�C)

625 295 21.4 6.3 .78 .61 .75 .89 20.4 6.0 .93 .62 .77 .91 19.5 5.7 1.10 .63 .79 .93 18.3 5.4 1.30 .65 .81 .96(19�C)

740 350 22.2 6.5 .78 .64 .79 .94 21.2 6.2 .93 .65 .81 .96 20.2 5.9 1.10 .66 .83 .99 19.0 5.6 1.30 .68 .86 1.00

71�F625 295 22.4 6.6 .78 .46 .60 .73 21.6 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78

71�F(22�C)

625 295 22.4 6.6 .78 .46 .60 .73 21.6 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78(22�C)

740 350 23.4 6.9 .78 .47 .62 .76 22.4 6.6 .93 .48 .63 .78 21.2 6.2 1.10 .48 .65 .80 20.0 5.9 1.30 .49 .66 .83

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−38B−6F + G60UHV−36B−090][C33−38B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F825 390 25.4 7.4 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .85 1.00 1.00

63�F(17�C)

825 390 25.4 7.4 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .85 1.00 1.00(17�C)

1035 490 26.8 7.9 1.29 .84 1.00 1.00 25.6 7.5 1.51 .86 1.00 1.00 24.2 7.1 1.75 .89 1.00 1.00 23.0 6.7 2.02 .92 1.00 1.00

67�F825 390 26.8 7.9 1.29 .62 .76 .90 25.4 7.4 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .83 .98

67�F(19�C)

825 390 26.8 7.9 1.29 .62 .76 .90 25.4 7.4 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .83 .98(19�C)

1035 490 28.0 8.2 1.30 .65 .82 .97 26.6 7.8 1.51 .66 .84 .99 25.0 7.3 1.74 .68 .87 1.00 23.4 6.9 2.02 .70 .90 1.00

71�F825 390 28.0 8.2 1.30 .47 .61 .74 26.6 7.8 1.51 .47 .62 .75 25.2 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .64 .80

71�F(22�C)

825 390 28.0 8.2 1.30 .47 .61 .74 26.6 7.8 1.51 .47 .62 .75 25.2 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .64 .80(22�C)

1035 490 29.2 8.6 1.30 .48 .64 .79 27.8 8.1 1.52 .49 .65 .82 26.4 7.7 1.76 .49 .67 .84 24.8 7.3 2.02 .50 .69 .87

Page 33: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 33

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−38B−6F + G61MPV−36B−045][C33−38B + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F610 290 20.6 6.0 .77 .77 .91 1.00 19.6 5.7 .93 .79 .94 1.00 18.6 5.5 1.10 .81 .96 1.00 17.5 5.1 1.30 .83 .99 1.00

63�F(17�C)

610 290 20.6 6.0 .77 .77 .91 1.00 19.6 5.7 .93 .79 .94 1.00 18.6 5.5 1.10 .81 .96 1.00 17.5 5.1 1.30 .83 .99 1.00(17�C)

725 340 21.4 6.3 .78 .81 .97 1.00 20.4 6.0 .93 .83 .99 1.00 19.5 5.7 1.10 .85 1.00 1.00 18.5 5.4 1.30 .88 1.00 1.00

67�F610 290 22.0 6.4 .78 .60 .74 .87 21.0 6.2 .93 .61 .76 .90 19.9 5.8 1.10 .62 .78 .92 18.7 5.5 1.30 .64 .80 .95

67�F(19�C)

610 290 22.0 6.4 .78 .60 .74 .87 21.0 6.2 .93 .61 .76 .90 19.9 5.8 1.10 .62 .78 .92 18.7 5.5 1.30 .64 .80 .95(19�C)

725 340 22.8 6.7 .78 .63 .78 .93 21.8 6.4 .93 .64 .80 .95 20.6 6.0 1.10 .64 .82 .98 19.4 5.7 1.30 .67 .85 1.00

71�F610 290 23.4 6.9 .78 .46 .59 .71 22.4 6.6 .93 .46 .60 .73 21.2 6.2 1.10 .47 .61 .75 20.0 5.9 1.30 .47 .62 .77

71�F(22�C)

610 290 23.4 6.9 .78 .46 .59 .71 22.4 6.6 .93 .46 .60 .73 21.2 6.2 1.10 .47 .61 .75 20.0 5.9 1.30 .47 .62 .77(22�C)

725 340 24.2 7.1 .79 .47 .61 .75 23.2 6.8 .94 .47 .62 .77 22.0 6.4 1.10 .47 .63 .79 20.8 6.1 1.30 .48 .65 .82

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−38B−6F + G61MPV−36B−045][C33−38B + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F840 395 26.2 7.7 1.29 .79 .94 1.00 25.0 7.3 1.51 .80 .96 1.00 23.6 6.9 1.74 .83 .99 1.00 22.2 6.5 2.02 .85 1.00 1.00

63�F(17�C)

840 395 26.2 7.7 1.29 .79 .94 1.00 25.0 7.3 1.51 .80 .96 1.00 23.6 6.9 1.74 .83 .99 1.00 22.2 6.5 2.02 .85 1.00 1.00(17�C)

1050 495 27.4 8.0 1.30 .84 1.00 1.00 26.2 7.7 1.51 .87 1.00 1.00 25.0 7.3 1.75 .89 1.00 1.00 23.6 6.9 2.02 .93 1.00 1.00

67�F840 395 27.8 8.1 1.30 .62 .76 .90 26.4 7.7 1.51 .63 .78 .93 24.8 7.3 1.75 .64 .80 .96 23.2 6.8 2.02 .65 .83 .99

67�F(19�C)

840 395 27.8 8.1 1.30 .62 .76 .90 26.4 7.7 1.51 .63 .78 .93 24.8 7.3 1.75 .64 .80 .96 23.2 6.8 2.02 .65 .83 .99(19�C)

1050 495 29.0 8.5 1.30 .65 .82 .98 27.4 8.0 1.52 .67 .85 1.00 25.8 7.6 1.75 .68 .87 1.00 24.2 7.1 2.02 .70 .91 1.00

71�F840 395 29.2 8.6 1.31 .46 .60 .74 27.8 8.1 1.52 .47 .61 .76 26.4 7.7 1.76 .47 .63 .77 24.6 7.2 2.02 .48 .64 .80

71�F(22�C)

840 395 29.2 8.6 1.31 .46 .60 .74 27.8 8.1 1.52 .47 .61 .76 26.4 7.7 1.76 .47 .63 .77 24.6 7.2 2.02 .48 .64 .80(22�C)

1050 495 30.4 8.9 1.31 .48 .64 .80 29.0 8.5 1.52 .48 .65 .82 27.4 8.0 1.76 .49 .67 .85 25.6 7.5 2.03 .50 .69 .88

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−38B−6F + G61MPV−36B−070][C33−38B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 20.8 6.1 .77 .78 .92 1.00 19.8 5.8 .93 .79 .94 1.00 18.7 5.5 1.10 .81 .97 1.00 17.6 5.2 1.30 .83 1.00 1.00

63�F(17�C)

625 295 20.8 6.1 .77 .78 .92 1.00 19.8 5.8 .93 .79 .94 1.00 18.7 5.5 1.10 .81 .97 1.00 17.6 5.2 1.30 .83 1.00 1.00(17�C)

725 340 21.4 6.3 .78 .81 .97 1.00 20.4 6.0 .93 .83 .99 1.00 19.5 5.7 1.10 .85 1.00 1.00 18.5 5.4 1.30 .88 1.00 1.00

67�F625 295 22.0 6.4 .78 .61 .75 .88 21.0 6.2 .93 .62 .76 .90 20.0 5.9 1.10 .63 .78 .93 18.8 5.5 1.30 .64 .80 .96

67�F(19�C)

625 295 22.0 6.4 .78 .61 .75 .88 21.0 6.2 .93 .62 .76 .90 20.0 5.9 1.10 .63 .78 .93 18.8 5.5 1.30 .64 .80 .96(19�C)

725 340 22.8 6.7 .78 .63 .78 .93 21.8 6.4 .93 .64 .80 .95 20.6 6.0 1.10 .65 .82 .98 19.4 5.7 1.30 .67 .85 1.00

71�F625 295 23.4 6.9 .78 .46 .59 .72 22.4 6.6 .93 .46 .60 .73 21.4 6.3 1.10 .47 .61 .75 20.2 5.9 1.30 .47 .62 .77

71�F(22�C)

625 295 23.4 6.9 .78 .46 .59 .72 22.4 6.6 .93 .46 .60 .73 21.4 6.3 1.10 .47 .61 .75 20.2 5.9 1.30 .47 .62 .77(22�C)

725 340 24.2 7.1 .79 .47 .61 .75 23.2 6.8 .94 .47 .62 .77 22.0 6.4 1.10 .47 .63 .79 20.8 6.1 1.30 .48 .65 .82

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−38B−6F + G61MPV−36B−070][C33−38B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F830 390 26.2 7.7 1.29 .78 .93 1.00 24.8 7.3 1.51 .80 .96 1.00 23.4 6.9 1.74 .82 .99 1.00 22.0 6.4 2.02 .85 1.00 1.00

63�F(17�C)

830 390 26.2 7.7 1.29 .78 .93 1.00 24.8 7.3 1.51 .80 .96 1.00 23.4 6.9 1.74 .82 .99 1.00 22.0 6.4 2.02 .85 1.00 1.00(17�C)

1020 480 27.2 8.0 1.30 .83 1.00 1.00 26.0 7.6 1.51 .86 1.00 1.00 24.8 7.3 1.75 .88 1.00 1.00 23.4 6.9 2.02 .92 1.00 1.00

67�F830 390 27.6 8.1 1.30 .62 .76 .90 26.4 7.7 1.51 .63 .78 .93 24.8 7.3 1.75 .64 .80 .95 23.2 6.8 2.02 .65 .83 .99

67�F(19�C)

830 390 27.6 8.1 1.30 .62 .76 .90 26.4 7.7 1.51 .63 .78 .93 24.8 7.3 1.75 .64 .80 .95 23.2 6.8 2.02 .65 .83 .99(19�C)

1020 480 28.6 8.4 1.30 .65 .81 .97 27.4 8.0 1.52 .65 .83 .99 25.8 7.6 1.75 .68 .86 1.00 24.0 7.0 2.02 .69 .89 1.00

71�F830 390 29.2 8.6 1.31 .46 .60 .74 27.8 8.1 1.52 .47 .61 .75 26.2 7.7 1.76 .47 .62 .77 24.6 7.2 2.02 .47 .64 .80

71�F(22�C)

830 390 29.2 8.6 1.31 .46 .60 .74 27.8 8.1 1.52 .47 .61 .75 26.2 7.7 1.76 .47 .62 .77 24.6 7.2 2.02 .47 .64 .80(22�C)

1020 480 30.4 8.9 1.31 .47 .63 .79 28.8 8.4 1.52 .48 .64 .81 27.2 8.0 1.76 .48 .67 .84 25.4 7.4 2.03 .49 .68 .87

Page 34: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 2 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 34

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−42B−6F + G60UHV−36B−090][C33−42B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 20.2 5.9 .77 .78 .92 1.00 19.4 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .84 1.00 1.00

63�F(17�C)

625 295 20.2 5.9 .77 .78 .92 1.00 19.4 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .84 1.00 1.00(17�C)

740 350 21.2 6.2 .78 .82 .97 1.00 20.2 5.9 .93 .83 .99 1.00 19.3 5.7 1.10 .86 1.00 1.00 18.3 5.4 1.30 .89 1.00 1.00

67�F625 295 21.4 6.3 .78 .61 .75 .89 20.4 6.0 .93 .62 .77 .91 19.5 5.7 1.10 .63 .79 .93 18.3 5.4 1.30 .65 .81 .96

67�F(19�C)

625 295 21.4 6.3 .78 .61 .75 .89 20.4 6.0 .93 .62 .77 .91 19.5 5.7 1.10 .63 .79 .93 18.3 5.4 1.30 .65 .81 .96(19�C)

740 350 22.2 6.5 .78 .64 .79 .94 21.2 6.2 .93 .65 .81 .96 20.2 5.9 1.10 .66 .83 .99 19.0 5.6 1.30 .68 .86 1.00

71�F625 295 22.4 6.6 .78 .46 .60 .73 21.6 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78

71�F(22�C)

625 295 22.4 6.6 .78 .46 .60 .73 21.6 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78(22�C)

740 350 23.4 6.9 .78 .47 .62 .76 22.4 6.6 .93 .48 .63 .78 21.2 6.2 1.10 .48 .65 .80 20.0 5.9 1.30 .49 .66 .83

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−42B−6F + G60UHV−36B−090][C33−42B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F825 390 25.4 7.4 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .85 1.00 1.00

63�F(17�C)

825 390 25.4 7.4 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .85 1.00 1.00(17�C)

1035 490 26.8 7.9 1.29 .84 1.00 1.00 25.6 7.5 1.51 .86 1.00 1.00 24.2 7.1 1.75 .89 1.00 1.00 23.0 6.7 2.02 .92 1.00 1.00

67�F825 390 26.8 7.9 1.29 .62 .76 .90 25.4 7.4 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .83 .98

67�F(19�C)

825 390 26.8 7.9 1.29 .62 .76 .90 25.4 7.4 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .83 .98(19�C)

1035 490 28.0 8.2 1.30 .65 .82 .97 26.6 7.8 1.51 .66 .84 .99 25.0 7.3 1.74 .68 .87 1.00 23.4 6.9 2.02 .70 .90 1.00

71�F825 390 28.0 8.2 1.30 .47 .61 .74 26.6 7.8 1.51 .47 .62 .75 25.2 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .64 .80

71�F(22�C)

825 390 28.0 8.2 1.30 .47 .61 .74 26.6 7.8 1.51 .47 .62 .75 25.2 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .64 .80(22�C)

1035 490 29.2 8.6 1.30 .48 .64 .79 27.8 8.1 1.52 .49 .65 .82 26.4 7.7 1.76 .49 .67 .84 24.8 7.3 2.02 .50 .69 .87

FIRST STAGE COOLING CAPACITY − XC21−024 with [CX34−42B−6F + G61MPV−36B−045][C33−42B + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F610 290 20.2 5.9 .77 .77 .92 1.00 19.3 5.7 .93 .79 .94 1.00 18.3 5.4 1.10 .81 .96 1.00 17.3 5.1 1.31 .83 .99 1.00

63�F(17�C)

610 290 20.2 5.9 .77 .77 .92 1.00 19.3 5.7 .93 .79 .94 1.00 18.3 5.4 1.10 .81 .96 1.00 17.3 5.1 1.31 .83 .99 1.00(17�C)

725 340 21.0 6.2 .78 .81 .97 1.00 20.2 5.9 .93 .83 .99 1.00 19.2 5.6 1.10 .85 1.00 1.00 18.2 5.3 1.30 .88 1.00 1.00

67�F610 290 21.2 6.2 .78 .61 .75 .88 20.4 6.0 .93 .62 .76 .90 19.3 5.7 1.10 .63 .78 .93 18.3 5.4 1.30 .64 .80 .96

67�F(19�C)

610 290 21.2 6.2 .78 .61 .75 .88 20.4 6.0 .93 .62 .76 .90 19.3 5.7 1.10 .63 .78 .93 18.3 5.4 1.30 .64 .80 .96(19�C)

725 340 22.2 6.5 .78 .63 .78 .93 21.2 6.2 .93 .64 .80 .95 20.2 5.9 1.10 .66 .82 .98 18.9 5.5 1.30 .67 .85 1.00

71�F610 290 22.2 6.5 .78 .46 .59 .72 21.4 6.3 .93 .47 .60 .73 20.4 6.0 1.10 .47 .62 .75 19.2 5.6 1.30 .47 .63 .77

71�F(22�C)

610 290 22.2 6.5 .78 .46 .59 .72 21.4 6.3 .93 .47 .60 .73 20.4 6.0 1.10 .47 .62 .75 19.2 5.6 1.30 .47 .63 .77(22�C)

725 340 23.2 6.8 .78 .47 .62 .76 22.2 6.5 .93 .48 .63 .78 21.2 6.2 1.10 .48 .64 .80 20.0 5.9 1.30 .49 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−024 with [CX34−42B−6F + G61MPV−36B−045][C33−42B + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F840 395 25.6 7.5 1.29 .79 .94 1.00 24.4 7.2 1.50 .81 .96 1.00 23.0 6.7 1.74 .83 .99 1.00 21.8 6.4 2.02 .85 1.00 1.00

63�F(17�C)

840 395 25.6 7.5 1.29 .79 .94 1.00 24.4 7.2 1.50 .81 .96 1.00 23.0 6.7 1.74 .83 .99 1.00 21.8 6.4 2.02 .85 1.00 1.00(17�C)

1050 495 26.8 7.9 1.30 .84 1.00 1.00 25.6 7.5 1.51 .87 1.00 1.00 24.4 7.2 1.75 .89 1.00 1.00 23.0 6.7 2.02 .93 1.00 1.00

67�F840 395 26.8 7.9 1.30 .62 .76 .91 25.6 7.5 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .96 22.8 6.7 2.03 .66 .83 .99

67�F(19�C)

840 395 26.8 7.9 1.30 .62 .76 .91 25.6 7.5 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .96 22.8 6.7 2.03 .66 .83 .99(19�C)

1050 495 28.0 8.2 1.30 .65 .82 .98 26.6 7.8 1.51 .67 .84 1.00 25.2 7.4 1.75 .68 .87 1.00 23.6 6.9 2.03 .70 .90 1.00

71�F840 395 28.0 8.2 1.30 .47 .61 .74 26.8 7.9 1.51 .47 .62 .76 25.4 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .65 .81

71�F(22�C)

840 395 28.0 8.2 1.30 .47 .61 .74 26.8 7.9 1.51 .47 .62 .76 25.4 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .65 .81(22�C)

1050 495 29.4 8.6 1.30 .48 .64 .80 28.0 8.2 1.52 .49 .66 .82 26.4 7.7 1.75 .49 .67 .85 24.8 7.3 2.02 .50 .69 .88

Page 35: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 2 TON

DOWN−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 35

FIRST STAGE COOLING CAPACITY − XC21−024 with [CR26−30N−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 18.5 5.4 .77 .72 .84 .95 17.8 5.2 .92 .73 .85 .97 16.9 5.0 1.10 .74 .87 .99 15.9 4.7 1.30 .76 .90 1.00

63�F(17�C)

560 265 19.5 5.7 .77 .75 .88 1.00 18.7 5.5 .92 .76 .90 1.00 17.8 5.2 1.10 .78 .93 1.00 16.8 4.9 1.31 .80 .96 1.00(17�C)

660 310 20.4 6.0 .77 .78 .93 1.00 19.5 5.7 .93 .80 .95 1.00 18.5 5.4 1.10 .82 .98 1.00 17.4 5.1 1.30 .85 1.00 1.00

67�F460 215 19.8 5.8 .77 .57 .69 .80 19.0 5.6 .93 .58 .70 .81 18.1 5.3 1.10 .59 .71 .83 17.1 5.0 1.30 .60 .73 .86

67�F(19�C)

560 265 20.8 6.1 .78 .59 .72 .85 20.0 5.9 .93 .60 .74 .87 19.0 5.6 1.10 .61 .75 .89 17.9 5.2 1.30 .62 .77 .92(19�C)

660 310 21.6 6.3 .78 .61 .75 .89 20.6 6.0 .93 .62 .77 .91 19.7 5.8 1.10 .63 .79 .94 18.5 5.4 1.30 .65 .82 .97

71�F460 215 21.0 6.2 .77 .45 .56 .66 20.2 5.9 .93 .45 .56 .67 19.2 5.6 1.10 .45 .57 .68 18.1 5.3 1.30 .45 .58 .70

71�F(22�C)

560 265 22.0 6.4 .78 .45 .58 .69 21.2 6.2 .93 .45 .58 .71 20.2 5.9 1.10 .46 .59 .72 19.0 5.6 1.30 .47 .61 .74(22�C)

660 310 23.0 6.7 .78 .47 .60 .73 22.0 6.4 .93 .47 .61 .74 20.8 6.1 1.10 .47 .62 .76 19.7 5.8 1.30 .48 .63 .79

SECOND STAGE COOLING CAPACITY − XC21−024 with [CR26−30N−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 23.4 6.9 1.28 .72 .84 .95 22.4 6.6 1.50 .73 .86 .98 21.2 6.2 1.75 .74 .88 .99 19.9 5.8 2.01 .76 .91 1.00

63�F(17�C)

800 380 25.0 7.3 1.29 .77 .91 1.00 23.8 7.0 1.51 .79 .94 1.00 22.6 6.6 1.75 .81 .96 1.00 21.2 6.2 2.02 .83 .99 1.00(17�C)

1000 470 26.2 7.7 1.29 .82 .98 1.00 24.8 7.3 1.51 .84 .99 1.00 23.6 6.9 1.75 .87 1.00 1.00 22.4 6.6 2.02 .90 1.00 1.00

67�F600 285 24.8 7.3 1.29 .58 .69 .81 23.8 7.0 1.50 .58 .70 .82 22.4 6.6 1.74 .59 .72 .84 21.2 6.2 2.01 .60 .74 .87

67�F(19�C)

800 380 26.4 7.7 1.29 .61 .74 .88 25.2 7.4 1.51 .62 .76 .90 23.8 7.0 1.75 .63 .78 .93 22.4 6.6 2.02 .64 .81 .96(19�C)

1000 470 27.4 8.0 1.30 .64 .80 .95 26.2 7.7 1.51 .65 .82 .97 24.6 7.2 1.74 .67 .85 .99 23.2 6.8 2.01 .68 .87 1.00

71�F600 285 26.2 7.7 1.29 .45 .56 .67 25.0 7.3 1.51 .45 .57 .68 23.8 7.0 1.74 .45 .58 .69 22.4 6.6 2.02 .46 .59 .71

71�F(22�C)

800 380 27.8 8.1 1.30 .46 .59 .72 26.6 7.8 1.51 .45 .60 .74 25.2 7.4 1.75 .47 .62 .76 23.6 6.9 2.02 .48 .63 .78(22�C)

1000 470 29.0 8.5 1.30 .47 .63 .78 27.6 8.1 1.52 .48 .64 .79 26.0 7.6 1.76 .49 .66 .82 24.4 7.2 2.02 .49 .68 .85

FIRST STAGE COOLING CAPACITY − XC21−024 with [CR26−36N/W−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 18.9 5.5 .77 .71 .83 .95 18.1 5.3 .93 .73 .85 .97 17.2 5.0 1.10 .74 .87 1.00 16.1 4.7 1.30 .76 .90 1.00

63�F(17�C)

560 265 19.9 5.8 .77 .75 .88 1.00 19.1 5.6 .92 .76 .91 1.00 18.1 5.3 1.10 .78 .93 1.00 17.0 5.0 1.30 .80 .96 1.00(17�C)

660 310 20.8 6.1 .78 .79 .94 1.00 19.9 5.8 .93 .80 .96 1.00 18.8 5.5 1.09 .82 .99 1.00 17.8 5.2 1.30 .85 1.00 1.00

67�F460 215 20.2 5.9 .77 .57 .69 .80 19.3 5.7 .93 .58 .70 .82 18.4 5.4 1.10 .59 .71 .84 17.3 5.1 1.30 .59 .73 .86

67�F(19�C)

560 265 21.2 6.2 .78 .59 .72 .85 20.4 6.0 .93 .60 .74 .87 19.4 5.7 1.10 .61 .75 .89 18.2 5.3 1.30 .62 .78 .92(19�C)

660 310 22.2 6.5 .78 .62 .76 .90 21.2 6.2 .93 .63 .78 .92 20.0 5.9 1.10 .64 .80 .95 18.8 5.5 1.30 .65 .82 .98

71�F460 215 21.4 6.3 .78 .44 .55 .66 20.6 6.0 .93 .44 .56 .67 19.5 5.7 1.10 .44 .56 .68 18.5 5.4 1.30 .45 .58 .70

71�F(22�C)

560 265 22.6 6.6 .78 .45 .58 .70 21.6 6.3 .93 .46 .58 .71 20.6 6.0 1.10 .46 .59 .72 19.4 5.7 1.30 .46 .61 .75(22�C)

660 310 23.6 6.9 .78 .46 .60 .73 22.4 6.6 .93 .47 .61 .75 21.4 6.3 1.10 .47 .62 .77 20.0 5.9 1.30 .48 .63 .79

SECOND STAGE COOLING CAPACITY − XC21−024 with [CR26−36N/W−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 24.0 7.0 1.29 .72 .84 .96 22.8 6.7 1.50 .73 .86 .98 21.6 6.3 1.74 .75 .89 1.00 20.2 5.9 2.00 .76 .91 1.00

63�F(17�C)

800 380 25.6 7.5 1.29 .77 .92 1.00 24.4 7.2 1.51 .79 .95 1.00 23.0 6.7 1.74 .81 .98 1.00 21.6 6.3 2.01 .84 1.00 1.00(17�C)

1000 470 26.8 7.9 1.29 .83 .99 1.00 25.4 7.4 1.51 .85 1.00 1.00 24.2 7.1 1.75 .88 1.00 1.00 23.0 6.7 2.02 .91 1.00 1.00

67�F600 285 25.4 7.4 1.29 .58 .69 .81 24.2 7.1 1.50 .58 .70 .82 23.0 6.7 1.75 .59 .72 .85 21.6 6.3 2.01 .60 .74 .88

67�F(19�C)

800 380 27.0 7.9 1.29 .61 .75 .89 25.8 7.6 1.51 .62 .77 .91 24.4 7.2 1.75 .63 .79 .94 22.8 6.7 2.02 .65 .82 .97(19�C)

1000 470 28.2 8.3 1.30 .64 .81 .96 26.8 7.9 1.51 .66 .83 .99 25.2 7.4 1.75 .67 .86 1.00 23.6 6.9 2.02 .69 .89 1.00

71�F600 285 26.8 7.9 1.29 .44 .56 .67 25.6 7.5 1.51 .45 .56 .68 24.2 7.1 1.75 .45 .57 .70 22.8 6.7 2.02 .45 .59 .71

71�F(22�C)

800 380 28.6 8.4 1.30 .46 .60 .73 27.2 8.0 1.52 .46 .61 .74 25.6 7.5 1.76 .47 .62 .77 24.2 7.1 2.02 .48 .63 .79(22�C)

1000 470 29.8 8.7 1.31 .47 .63 .79 28.2 8.3 1.52 .48 .65 .81 26.6 7.8 1.75 .48 .66 .83 25.0 7.3 2.03 .49 .68 .86

Page 36: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 2 TON

DOWN−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 36

FIRST STAGE COOLING CAPACITY − XC21−024 with [CR26−30N−2F + G60DFV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F695 330 20.6 6.0 .77 .79 .94 1.00 19.7 5.8 .93 .81 .96 1.00 18.7 5.5 1.10 .83 .99 1.00 17.7 5.2 1.31 .86 1.00 1.00

63�F(17�C)

695 330 20.6 6.0 .77 .79 .94 1.00 19.7 5.8 .93 .81 .96 1.00 18.7 5.5 1.10 .83 .99 1.00 17.7 5.2 1.31 .86 1.00 1.00(17�C)

800 380 21.2 6.2 .78 .83 .98 1.00 20.4 6.0 .93 .85 1.00 1.00 19.4 5.7 1.10 .87 1.00 1.00 18.4 5.4 1.30 .90 1.00 1.00

67�F695 330 21.8 6.4 .78 .62 .77 .91 21.0 6.2 .93 .63 .78 .93 19.8 5.8 1.10 .64 .80 .95 18.7 5.5 1.30 .66 .83 .98

67�F(19�C)

695 330 21.8 6.4 .78 .62 .77 .91 21.0 6.2 .93 .63 .78 .93 19.8 5.8 1.10 .64 .80 .95 18.7 5.5 1.30 .66 .83 .98(19�C)

800 380 22.4 6.6 .78 .64 .80 .95 21.4 6.3 .93 .65 .82 .97 20.4 6.0 1.10 .67 .84 .99 19.1 5.6 1.30 .68 .87 1.00

71�F695 330 23.2 6.8 .78 .46 .61 .74 22.2 6.5 .93 .47 .62 .75 21.0 6.2 1.10 .47 .63 .78 19.9 5.8 1.30 .48 .64 .80

71�F(22�C)

695 330 23.2 6.8 .78 .46 .61 .74 22.2 6.5 .93 .47 .62 .75 21.0 6.2 1.10 .47 .63 .78 19.9 5.8 1.30 .48 .64 .80(22�C)

800 380 23.8 7.0 .79 .46 .63 .78 22.8 6.7 .93 .47 .64 .79 21.6 6.3 1.10 .49 .65 .82 20.4 6.0 1.30 .49 .67 .84

SECOND STAGE COOLING CAPACITY − XC21−024 with [CR26−30N−2F + G60DFV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F920 435 25.8 7.6 1.29 .80 .95 1.00 24.6 7.2 1.50 .82 .98 1.00 23.2 6.8 1.74 .84 1.00 1.00 21.8 6.4 2.02 .87 1.00 1.00

63�F(17�C)

920 435 25.8 7.6 1.29 .80 .95 1.00 24.6 7.2 1.50 .82 .98 1.00 23.2 6.8 1.74 .84 1.00 1.00 21.8 6.4 2.02 .87 1.00 1.00(17�C)

1135 535 26.8 7.9 1.29 .86 1.00 1.00 25.6 7.5 1.51 .88 1.00 1.00 24.4 7.2 1.74 .90 1.00 1.00 23.0 6.7 2.02 .94 1.00 1.00

67�F920 435 27.2 8.0 1.30 .63 .78 .92 25.8 7.6 1.51 .64 .80 .94 24.4 7.2 1.75 .65 .82 .97 22.8 6.7 2.01 .67 .85 1.00

67�F(19�C)

920 435 27.2 8.0 1.30 .63 .78 .92 25.8 7.6 1.51 .64 .80 .94 24.4 7.2 1.75 .65 .82 .97 22.8 6.7 2.01 .67 .85 1.00(19�C)

1135 535 28.0 8.2 1.30 .66 .83 .98 26.6 7.8 1.51 .67 .86 1.00 25.2 7.4 1.75 .69 .88 1.00 23.6 6.9 2.03 .71 .91 1.00

71�F920 435 28.6 8.4 1.30 .47 .61 .75 27.2 8.0 1.51 .48 .62 .78 25.8 7.6 1.75 .48 .64 .79 24.2 7.1 2.03 .48 .66 .82

71�F(22�C)

920 435 28.6 8.4 1.30 .47 .61 .75 27.2 8.0 1.51 .48 .62 .78 25.8 7.6 1.75 .48 .64 .79 24.2 7.1 2.03 .48 .66 .82(22�C)

1135 535 29.6 8.7 1.30 .48 .65 .81 28.0 8.2 1.52 .49 .66 .84 26.6 7.8 1.75 .50 .68 .86 24.8 7.3 2.03 .51 .70 .89

FIRST STAGE COOLING CAPACITY − XC21−024 with [CR26−36N−2F + G60DFV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F695 330 21.2 6.2 .77 .80 .95 1.00 20.2 5.9 .93 .82 .98 1.00 19.1 5.6 1.10 .83 1.00 1.00 18.1 5.3 1.30 .87 1.00 1.00

63�F(17�C)

695 330 21.2 6.2 .77 .80 .95 1.00 20.2 5.9 .93 .82 .98 1.00 19.1 5.6 1.10 .83 1.00 1.00 18.1 5.3 1.30 .87 1.00 1.00(17�C)

800 380 21.8 6.4 .78 .84 .99 1.00 20.8 6.1 .93 .86 1.00 1.00 19.9 5.8 1.10 .88 1.00 1.00 18.9 5.5 1.30 .91 1.00 1.00

67�F695 330 22.4 6.6 .78 .62 .77 .92 21.4 6.3 .93 .63 .79 .94 20.2 5.9 1.10 .64 .81 .97 19.0 5.6 1.30 .66 .84 .99

67�F(19�C)

695 330 22.4 6.6 .78 .62 .77 .92 21.4 6.3 .93 .63 .79 .94 20.2 5.9 1.10 .64 .81 .97 19.0 5.6 1.30 .66 .84 .99(19�C)

800 380 23.0 6.7 .78 .64 .81 .96 22.0 6.4 .93 .65 .83 .99 20.8 6.1 1.10 .67 .85 1.00 19.6 5.7 1.30 .69 .88 1.00

71�F695 330 23.8 7.0 .79 .46 .61 .75 22.8 6.7 .93 .47 .62 .76 21.6 6.3 1.10 .47 .63 .78 20.4 6.0 1.30 .48 .64 .81

71�F(22�C)

695 330 23.8 7.0 .79 .46 .61 .75 22.8 6.7 .93 .47 .62 .76 21.6 6.3 1.10 .47 .63 .78 20.4 6.0 1.30 .48 .64 .81(22�C)

800 380 24.4 7.2 .79 .47 .63 .78 23.4 6.9 .94 .48 .64 .80 22.2 6.5 1.11 .48 .66 .83 20.8 6.1 1.30 .49 .68 .85

SECOND STAGE COOLING CAPACITY − XC21−024 with [CR26−36N−2F + G60DFV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F920 435 26.4 7.7 1.29 .81 .97 1.00 25.0 7.3 1.51 .83 .99 1.00 23.6 6.9 1.75 .85 1.00 1.00 22.4 6.6 2.02 .88 1.00 1.00

63�F(17�C)

920 435 26.4 7.7 1.29 .81 .97 1.00 25.0 7.3 1.51 .83 .99 1.00 23.6 6.9 1.75 .85 1.00 1.00 22.4 6.6 2.02 .88 1.00 1.00(17�C)

1135 535 27.6 8.1 1.30 .87 1.00 1.00 26.2 7.7 1.51 .89 1.00 1.00 25.0 7.3 1.75 .92 1.00 1.00 23.6 6.9 2.03 .95 1.00 1.00

67�F920 435 27.8 8.1 1.30 .63 .79 .93 26.4 7.7 1.51 .64 .81 .96 25.0 7.3 1.74 .66 .83 .99 23.4 6.9 2.03 .67 .86 1.00

67�F(19�C)

920 435 27.8 8.1 1.30 .63 .79 .93 26.4 7.7 1.51 .64 .81 .96 25.0 7.3 1.74 .66 .83 .99 23.4 6.9 2.03 .67 .86 1.00(19�C)

1135 535 28.6 8.4 1.30 .67 .85 1.00 27.2 8.0 1.51 .68 .87 1.00 25.8 7.6 1.75 .70 .90 1.00 24.2 7.1 2.03 .72 .93 1.00

71�F920 435 29.4 8.6 1.31 .47 .62 .76 27.8 8.1 1.52 .47 .63 .78 26.4 7.7 1.76 .48 .65 .81 24.6 7.2 2.02 .49 .66 .84

71�F(22�C)

920 435 29.4 8.6 1.31 .47 .62 .76 27.8 8.1 1.52 .47 .63 .78 26.4 7.7 1.76 .48 .65 .81 24.6 7.2 2.02 .49 .66 .84(22�C)

1135 535 30.4 8.9 1.31 .49 .66 .82 28.8 8.4 1.52 .49 .67 .85 27.2 8.0 1.76 .50 .69 .88 25.4 7.4 2.03 .51 .71 .91

Page 37: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 2 TON

DOWN−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 37

FIRST STAGE COOLING CAPACITY − XC21−024 with [CR26−48N−2F + G60DFV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F695 330 21.2 6.2 .77 .80 .95 1.00 20.2 5.9 .93 .82 .98 1.00 19.1 5.6 1.10 .83 1.00 1.00 18.1 5.3 1.30 .87 1.00 1.00

63�F(17�C)

695 330 21.2 6.2 .77 .80 .95 1.00 20.2 5.9 .93 .82 .98 1.00 19.1 5.6 1.10 .83 1.00 1.00 18.1 5.3 1.30 .87 1.00 1.00(17�C)

800 380 21.8 6.4 .78 .84 .99 1.00 20.8 6.1 .93 .86 1.00 1.00 19.9 5.8 1.10 .88 1.00 1.00 18.9 5.5 1.30 .91 1.00 1.00

67�F695 330 22.4 6.6 .78 .62 .77 .92 21.4 6.3 .93 .63 .79 .94 20.2 5.9 1.10 .64 .81 .97 19.0 5.6 1.30 .66 .84 .99

67�F(19�C)

695 330 22.4 6.6 .78 .62 .77 .92 21.4 6.3 .93 .63 .79 .94 20.2 5.9 1.10 .64 .81 .97 19.0 5.6 1.30 .66 .84 .99(19�C)

800 380 23.0 6.7 .78 .64 .81 .96 22.0 6.4 .93 .65 .83 .99 20.8 6.1 1.10 .67 .85 1.00 19.6 5.7 1.30 .69 .88 1.00

71�F695 330 23.8 7.0 .79 .46 .61 .75 22.8 6.7 .93 .47 .62 .76 21.6 6.3 1.10 .47 .63 .78 20.4 6.0 1.30 .48 .64 .81

71�F(22�C)

695 330 23.8 7.0 .79 .46 .61 .75 22.8 6.7 .93 .47 .62 .76 21.6 6.3 1.10 .47 .63 .78 20.4 6.0 1.30 .48 .64 .81(22�C)

800 380 24.4 7.2 .79 .47 .63 .78 23.4 6.9 .94 .48 .64 .80 22.2 6.5 1.11 .48 .66 .83 20.8 6.1 1.30 .49 .68 .85

SECOND STAGE COOLING CAPACITY − XC21−024 with [CR26−48N−2F + G60DFV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F920 435 26.4 7.7 1.29 .81 .97 1.00 25.0 7.3 1.51 .83 .99 1.00 23.6 6.9 1.75 .85 1.00 1.00 22.4 6.6 2.02 .88 1.00 1.00

63�F(17�C)

920 435 26.4 7.7 1.29 .81 .97 1.00 25.0 7.3 1.51 .83 .99 1.00 23.6 6.9 1.75 .85 1.00 1.00 22.4 6.6 2.02 .88 1.00 1.00(17�C)

1135 535 27.6 8.1 1.30 .87 1.00 1.00 26.2 7.7 1.51 .89 1.00 1.00 25.0 7.3 1.75 .92 1.00 1.00 23.6 6.9 2.03 .95 1.00 1.00

67�F920 435 27.8 8.1 1.30 .63 .79 .93 26.4 7.7 1.51 .64 .81 .96 25.0 7.3 1.74 .66 .83 .99 23.4 6.9 2.03 .67 .86 1.00

67�F(19�C)

920 435 27.8 8.1 1.30 .63 .79 .93 26.4 7.7 1.51 .64 .81 .96 25.0 7.3 1.74 .66 .83 .99 23.4 6.9 2.03 .67 .86 1.00(19�C)

1135 535 28.6 8.4 1.30 .67 .85 1.00 27.2 8.0 1.51 .68 .87 1.00 25.8 7.6 1.75 .70 .90 1.00 24.2 7.1 2.03 .72 .93 1.00

71�F920 435 29.4 8.6 1.31 .47 .62 .76 27.8 8.1 1.52 .47 .63 .78 26.4 7.7 1.76 .48 .65 .81 24.6 7.2 2.02 .49 .66 .84

71�F(22�C)

920 435 29.4 8.6 1.31 .47 .62 .76 27.8 8.1 1.52 .47 .63 .78 26.4 7.7 1.76 .48 .65 .81 24.6 7.2 2.02 .49 .66 .84(22�C)

1135 535 30.4 8.9 1.31 .49 .66 .82 28.8 8.4 1.52 .49 .67 .85 27.2 8.0 1.76 .50 .69 .88 25.4 7.4 2.03 .51 .71 .91

Page 38: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 2 TON

HORIZONTAL INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 38

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH23−21]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 17.1 5.0 .77 .72 .83 .94 16.5 4.8 .93 .73 .85 .96 15.7 4.6 1.10 .74 .86 .98 14.9 4.4 1.30 .76 .89 1.00

63�F(17�C)

560 265 18.1 5.3 .77 .74 .87 .98 17.4 5.1 .92 .76 .89 .99 16.5 4.8 1.10 .77 .91 1.00 15.7 4.6 1.31 .79 .94 1.00(17�C)

660 310 18.9 5.5 .77 .77 .91 1.00 18.1 5.3 .93 .79 .93 1.00 17.2 5.0 1.10 .81 .96 1.00 16.4 4.8 1.30 .83 .98 1.00

67�F460 215 18.2 5.3 .77 .58 .69 .80 17.6 5.2 .93 .59 .70 .81 16.8 4.9 1.10 .60 .71 .83 15.9 4.7 1.30 .60 .73 .85

67�F(19�C)

560 265 19.4 5.7 .77 .59 .72 .83 18.6 5.5 .93 .61 .73 .85 17.7 5.2 1.10 .61 .75 .87 16.8 4.9 1.31 .63 .77 .90(19�C)

660 310 20.2 5.9 .77 .61 .75 .87 19.4 5.7 .93 .62 .76 .90 18.4 5.4 1.10 .63 .78 .92 17.4 5.1 1.31 .65 .80 .95

71�F460 215 19.3 5.7 .77 .45 .56 .67 18.6 5.5 .93 .45 .57 .68 17.7 5.2 1.10 .45 .58 .69 16.9 5.0 1.30 .45 .59 .70

71�F(22�C)

560 265 20.4 6.0 .78 .46 .58 .69 19.7 5.8 .93 .46 .59 .71 18.8 5.5 1.10 .46 .60 .72 17.8 5.2 1.30 .47 .61 .74(22�C)

660 310 21.4 6.3 .78 .47 .59 .72 20.6 6.0 .93 .47 .61 .74 19.6 5.7 1.10 .47 .62 .75 18.5 5.4 1.30 .48 .63 .78

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH23−21]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 22.0 6.4 1.28 .72 .83 .94 21.0 6.2 1.50 .73 .85 .96 20.0 5.9 1.74 .74 .87 .98 18.8 5.5 2.01 .76 .89 1.00

63�F(17�C)

800 380 23.4 6.9 1.28 .76 .89 1.00 22.4 6.6 1.50 .78 .92 1.00 21.2 6.2 1.74 .79 .95 1.00 20.0 5.9 2.01 .82 .98 1.00(17�C)

1000 470 24.6 7.2 1.29 .80 .96 1.00 23.4 6.9 1.51 .82 .98 1.00 22.4 6.6 1.75 .85 1.00 1.00 21.2 6.2 2.01 .87 1.00 1.00

67�F600 285 23.2 6.8 1.28 .58 .69 .80 22.2 6.5 1.50 .59 .71 .82 21.2 6.2 1.74 .60 .72 .83 20.0 5.9 2.01 .61 .74 .86

67�F(19�C)

800 380 25.0 7.3 1.28 .61 .74 .86 23.8 7.0 1.50 .62 .75 .89 22.6 6.6 1.74 .63 .77 .91 21.2 6.2 2.02 .64 .79 .94(19�C)

1000 470 26.0 7.6 1.29 .63 .78 .93 24.8 7.3 1.50 .65 .80 .95 23.6 6.9 1.74 .66 .82 .98 22.2 6.5 2.02 .67 .85 1.00

71�F600 285 24.4 7.2 1.29 .45 .57 .67 23.4 6.9 1.51 .45 .57 .68 22.2 6.5 1.74 .44 .58 .70 21.0 6.2 2.02 .46 .59 .71

71�F(22�C)

800 380 26.2 7.7 1.29 .46 .60 .72 25.0 7.3 1.50 .47 .61 .73 23.8 7.0 1.75 .47 .62 .75 22.4 6.6 2.02 .47 .63 .77(22�C)

1000 470 27.6 8.1 1.30 .48 .62 .76 26.2 7.7 1.51 .48 .63 .78 24.8 7.3 1.75 .49 .65 .80 23.4 6.9 2.02 .49 .67 .83

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH23−31]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 17.3 5.1 .77 .72 .83 .94 16.6 4.9 .92 .73 .85 .96 15.9 4.7 1.10 .74 .87 .98 15.0 4.4 1.31 .76 .89 1.00

63�F(17�C)

560 265 18.3 5.4 .77 .75 .87 .99 17.5 5.1 .92 .76 .89 1.00 16.7 4.9 1.10 .78 .92 1.00 15.8 4.6 1.31 .80 .94 1.00(17�C)

660 310 19.1 5.6 .77 .77 .91 1.00 18.3 5.4 .93 .79 .94 1.00 17.5 5.1 1.10 .81 .96 1.00 16.6 4.9 1.31 .83 .99 1.00

67�F460 215 18.4 5.4 .77 .58 .69 .80 17.7 5.2 .92 .59 .70 .81 17.0 5.0 1.10 .60 .72 .83 16.1 4.7 1.30 .61 .73 .85

67�F(19�C)

560 265 19.6 5.7 .77 .59 .72 .84 18.8 5.5 .93 .60 .73 .86 17.9 5.2 1.10 .62 .75 .88 17.0 5.0 1.30 .63 .77 .91(19�C)

660 310 20.4 6.0 .77 .61 .75 .88 19.6 5.7 .93 .62 .76 .90 18.6 5.5 1.10 .64 .78 .93 17.6 5.2 1.30 .65 .81 .96

71�F460 215 19.4 5.7 .77 .45 .56 .67 18.7 5.5 .93 .45 .57 .68 17.9 5.2 1.10 .45 .58 .69 17.0 5.0 1.30 .45 .59 .70

71�F(22�C)

560 265 20.6 6.0 .77 .46 .58 .70 19.9 5.8 .92 .46 .58 .71 19.0 5.6 1.10 .46 .60 .72 18.0 5.3 1.30 .47 .61 .74(22�C)

660 310 21.6 6.3 .77 .47 .60 .72 20.8 6.1 .93 .47 .60 .74 19.8 5.8 1.10 .47 .62 .76 18.8 5.5 1.30 .48 .64 .78

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH23−31]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 22.2 6.5 1.28 .72 .83 .94 21.2 6.2 1.50 .73 .85 .96 20.2 5.9 1.74 .75 .87 .99 19.0 5.6 2.01 .76 .90 1.00

63�F(17�C)

800 380 23.8 7.0 1.28 .76 .90 1.00 22.6 6.6 1.50 .78 .92 1.00 21.6 6.3 1.74 .80 .95 1.00 20.2 5.9 2.02 .82 .98 1.00(17�C)

1000 470 24.8 7.3 1.29 .81 .97 1.00 23.8 7.0 1.50 .83 .98 1.00 22.8 6.7 1.75 .85 1.00 1.00 21.6 6.3 2.02 .88 1.00 1.00

67�F600 285 23.4 6.9 1.29 .58 .69 .80 22.4 6.6 1.50 .59 .70 .82 21.4 6.3 1.74 .60 .72 .84 20.2 5.9 2.01 .61 .74 .86

67�F(19�C)

800 380 25.2 7.4 1.29 .61 .74 .87 24.0 7.0 1.50 .62 .76 .89 22.8 6.7 1.75 .63 .78 .92 21.6 6.3 2.02 .65 .80 .95(19�C)

1000 470 26.4 7.7 1.29 .64 .79 .93 25.2 7.4 1.51 .65 .81 .96 23.8 7.0 1.74 .66 .83 .98 22.4 6.6 2.02 .68 .86 1.00

71�F600 285 24.6 7.2 1.29 .45 .57 .67 23.6 6.9 1.50 .44 .58 .69 22.4 6.6 1.74 .44 .58 .70 21.2 6.2 2.01 .45 .59 .72

71�F(22�C)

800 380 26.6 7.8 1.30 .46 .60 .72 25.4 7.4 1.51 .47 .61 .73 24.0 7.0 1.75 .47 .62 .75 22.6 6.6 2.02 .47 .63 .78(22�C)

1000 470 27.8 8.1 1.30 .48 .63 .77 26.6 7.8 1.51 .48 .64 .78 25.2 7.4 1.75 .49 .65 .81 23.6 6.9 2.02 .49 .67 .83

Page 39: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 2 TON

HORIZONTAL INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 39

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH23−41]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 17.8 5.2 .77 .71 .83 .94 17.1 5.0 .93 .72 .84 .96 16.3 4.8 1.10 .74 .87 .98 15.4 4.5 1.31 .75 .89 1.00

63�F(17�C)

560 265 18.9 5.5 .77 .74 .87 .99 18.0 5.3 .92 .75 .89 1.00 17.2 5.0 1.10 .77 .92 1.00 16.2 4.7 1.30 .79 .95 1.00(17�C)

660 310 19.7 5.8 .77 .77 .92 1.00 18.8 5.5 .93 .79 .94 1.00 17.9 5.2 1.10 .81 .96 1.00 17.0 5.0 1.30 .84 .99 1.00

67�F460 215 19.2 5.6 .77 .57 .68 .79 18.4 5.4 .92 .58 .69 .81 17.6 5.2 1.10 .59 .71 .83 16.6 4.9 1.31 .60 .72 .85

67�F(19�C)

560 265 20.4 6.0 .77 .59 .71 .84 19.5 5.7 .93 .60 .73 .86 18.5 5.4 1.10 .61 .74 .88 17.4 5.1 1.30 .62 .76 .91(19�C)

660 310 21.2 6.2 .78 .61 .75 .88 20.2 5.9 .93 .62 .76 .90 19.2 5.6 1.10 .63 .78 .93 18.1 5.3 1.30 .64 .81 .96

71�F460 215 20.6 6.0 .78 .44 .55 .66 19.8 5.8 .92 .44 .56 .67 18.9 5.5 1.10 .44 .57 .68 17.8 5.2 1.30 .44 .58 .70

71�F(22�C)

560 265 21.8 6.4 .78 .45 .57 .69 21.0 6.2 .93 .45 .58 .70 19.9 5.8 1.10 .45 .59 .72 18.8 5.5 1.30 .46 .60 .74(22�C)

660 310 22.8 6.7 .78 .46 .59 .72 21.8 6.4 .93 .46 .60 .73 20.8 6.1 1.10 .47 .61 .75 19.6 5.7 1.30 .47 .63 .78

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH23−41]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 22.8 6.7 1.29 .71 .83 .94 21.8 6.4 1.50 .73 .85 .97 20.8 6.1 1.74 .74 .87 .99 19.5 5.7 2.01 .76 .90 1.00

63�F(17�C)

800 380 24.6 7.2 1.29 .76 .91 1.00 23.4 6.9 1.51 .78 .93 1.00 22.2 6.5 1.75 .80 .96 1.00 20.8 6.1 2.02 .83 .98 1.00(17�C)

1000 470 25.8 7.6 1.29 .81 .97 1.00 24.6 7.2 1.51 .83 .99 1.00 23.6 6.9 1.75 .86 1.00 1.00 22.2 6.5 2.02 .89 1.00 1.00

67�F600 285 24.6 7.2 1.28 .57 .69 .80 23.4 6.9 1.50 .58 .70 .82 22.2 6.5 1.74 .59 .72 .84 20.8 6.1 2.01 .60 .73 .86

67�F(19�C)

800 380 26.2 7.7 1.29 .61 .74 .87 25.0 7.3 1.51 .62 .76 .89 23.6 6.9 1.74 .63 .78 .92 22.2 6.5 2.02 .64 .80 .95(19�C)

1000 470 27.4 8.0 1.30 .64 .79 .94 26.0 7.6 1.51 .65 .81 .97 24.6 7.2 1.75 .66 .84 .99 23.0 6.7 2.02 .68 .87 1.00

71�F600 285 26.0 7.6 1.29 .43 .56 .66 25.0 7.3 1.51 .44 .57 .68 23.6 6.9 1.75 .45 .58 .69 22.2 6.5 2.02 .45 .59 .71

71�F(22�C)

800 380 28.0 8.2 1.30 .45 .59 .72 26.6 7.8 1.51 .46 .60 .73 25.2 7.4 1.75 .46 .62 .75 23.6 6.9 2.02 .46 .63 .78(22�C)

1000 470 29.0 8.5 1.30 .47 .62 .77 27.8 8.1 1.52 .48 .64 .79 26.2 7.7 1.76 .48 .65 .81 24.6 7.2 2.03 .49 .67 .85

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH23−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 18.5 5.4 .77 .71 .83 .95 17.7 5.2 .93 .72 .85 .96 16.8 4.9 1.10 .74 .87 .99 15.8 4.6 1.30 .75 .90 1.00

63�F(17�C)

560 265 19.5 5.7 .77 .75 .88 .99 18.7 5.5 .93 .76 .90 1.00 17.7 5.2 1.10 .78 .92 1.00 16.7 4.9 1.30 .80 .95 1.00(17�C)

660 310 20.4 6.0 .77 .78 .93 1.00 19.5 5.7 .93 .80 .95 1.00 18.5 5.4 1.10 .82 .97 1.00 17.5 5.1 1.30 .84 1.00 1.00

67�F460 215 19.8 5.8 .77 .57 .69 .79 19.0 5.6 .93 .58 .70 .81 18.0 5.3 1.10 .58 .71 .83 17.0 5.0 1.31 .59 .73 .85

67�F(19�C)

560 265 21.0 6.2 .78 .59 .72 .84 20.0 5.9 .93 .60 .73 .86 19.0 5.6 1.10 .61 .75 .89 17.9 5.2 1.30 .62 .77 .91(19�C)

660 310 21.8 6.4 .78 .61 .75 .89 20.8 6.1 .93 .62 .77 .91 19.8 5.8 1.10 .63 .79 .94 18.6 5.5 1.30 .65 .81 .97

71�F460 215 21.0 6.2 .77 .44 .56 .66 20.2 5.9 .93 .44 .56 .67 19.3 5.7 1.10 .44 .56 .68 18.2 5.3 1.30 .45 .58 .70

71�F(22�C)

560 265 22.2 6.5 .78 .44 .57 .69 21.4 6.3 .93 .45 .58 .71 20.4 6.0 1.10 .45 .59 .72 19.2 5.6 1.30 .45 .60 .74(22�C)

660 310 23.2 6.8 .78 .46 .59 .73 22.2 6.5 .93 .46 .60 .74 21.2 6.2 1.10 .46 .62 .76 19.9 5.8 1.30 .47 .63 .78

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH23−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 23.6 6.9 1.28 .72 .84 .95 22.6 6.6 1.50 .73 .85 .97 21.4 6.3 1.74 .74 .88 .99 20.0 5.9 2.02 .76 .90 1.00

63�F(17�C)

800 380 25.4 7.4 1.29 .77 .92 1.00 24.0 7.0 1.50 .79 .94 1.00 22.8 6.7 1.75 .81 .96 1.00 21.4 6.3 2.01 .83 .99 1.00(17�C)

1000 470 26.6 7.8 1.29 .82 .98 1.00 25.4 7.4 1.51 .84 1.00 1.00 24.2 7.1 1.74 .87 1.00 1.00 22.8 6.7 2.02 .90 1.00 1.00

67�F600 285 25.2 7.4 1.29 .57 .69 .80 24.0 7.0 1.50 .58 .70 .82 22.8 6.7 1.75 .59 .72 .84 21.4 6.3 2.01 .60 .74 .87

67�F(19�C)

800 380 27.0 7.9 1.30 .61 .74 .88 25.6 7.5 1.51 .61 .76 .91 24.2 7.1 1.75 .63 .78 .93 22.8 6.7 2.01 .64 .81 .96(19�C)

1000 470 28.0 8.2 1.29 .64 .80 .95 26.6 7.8 1.51 .65 .82 .98 25.2 7.4 1.75 .66 .85 1.00 23.6 6.9 2.02 .68 .88 1.00

71�F600 285 26.6 7.8 1.30 .44 .56 .66 25.4 7.4 1.51 .44 .56 .68 24.0 7.0 1.75 .45 .57 .69 22.6 6.6 2.02 .45 .59 .71

71�F(22�C)

800 380 28.4 8.3 1.30 .45 .59 .72 27.0 7.9 1.52 .45 .60 .74 25.6 7.5 1.75 .46 .61 .76 24.0 7.0 2.03 .47 .63 .78(22�C)

1000 470 29.6 8.7 1.30 .47 .63 .78 28.2 8.3 1.52 .47 .64 .80 26.6 7.8 1.75 .48 .65 .82 25.0 7.3 2.02 .49 .67 .85

Page 40: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 2 TON

HORIZONTAL INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 40

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH33−18A−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 17.1 5.0 .78 .71 .83 .94 16.4 4.8 .94 .72 .85 .96 15.6 4.6 1.12 .74 .87 .98 14.8 4.3 1.33 .75 .89 1.00

63�F(17�C)

560 265 17.9 5.2 .78 .74 .87 .99 17.2 5.0 .94 .75 .89 1.00 16.4 4.8 1.12 .77 .91 1.00 15.5 4.5 1.32 .79 .94 1.00(17�C)

660 310 18.6 5.5 .79 .77 .91 1.00 17.8 5.2 .94 .78 .93 1.00 17.0 5.0 1.12 .80 .96 1.00 16.0 4.7 1.33 .82 .99 1.00

67�F460 215 18.0 5.3 .79 .58 .69 .79 17.3 5.1 .94 .58 .70 .81 16.6 4.9 1.12 .59 .71 .83 15.7 4.6 1.33 .60 .73 .85

67�F(19�C)

560 265 19.0 5.6 .78 .59 .72 .83 18.2 5.3 .94 .60 .73 .85 17.4 5.1 1.12 .61 .74 .87 16.5 4.8 1.32 .62 .76 .90(19�C)

660 310 19.7 5.8 .79 .61 .74 .87 18.9 5.5 .94 .62 .76 .89 18.0 5.3 1.11 .63 .78 .92 17.0 5.0 1.32 .64 .80 .95

71�F460 215 18.9 5.5 .78 .45 .56 .66 18.2 5.3 .94 .44 .56 .67 17.4 5.1 1.12 .45 .57 .68 16.5 4.8 1.32 .46 .58 .70

71�F(22�C)

560 265 20.0 5.9 .78 .46 .58 .69 19.2 5.6 .94 .46 .58 .70 18.3 5.4 1.12 .46 .59 .72 17.4 5.1 1.33 .46 .60 .73(22�C)

660 310 20.8 6.1 .79 .47 .60 .72 20.0 5.9 .94 .47 .60 .73 19.0 5.6 1.11 .47 .61 .75 18.0 5.3 1.32 .47 .63 .77

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH33−18A−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 21.4 6.3 1.28 .71 .83 .94 20.6 6.0 1.50 .72 .84 .96 19.5 5.7 1.74 .74 .86 .99 18.4 5.4 2.02 .75 .89 1.00

63�F(17�C)

800 380 22.8 6.7 1.28 .76 .89 1.00 21.8 6.4 1.50 .77 .91 1.00 20.6 6.0 1.74 .79 .94 1.00 19.4 5.7 2.01 .81 .97 1.00(17�C)

1000 470 23.8 7.0 1.29 .80 .95 1.00 22.6 6.6 1.50 .81 .97 1.00 21.4 6.3 1.74 .84 .99 1.00 20.2 5.9 2.02 .86 1.00 1.00

67�F600 285 22.6 6.6 1.29 .57 .69 .80 21.6 6.3 1.50 .58 .70 .81 20.6 6.0 1.74 .59 .71 .83 19.4 5.7 2.01 .60 .73 .86

67�F(19�C)

800 380 24.0 7.0 1.28 .60 .73 .86 23.0 6.7 1.50 .61 .75 .88 21.8 6.4 1.74 .62 .76 .90 20.6 6.0 2.01 .63 .79 .94(19�C)

1000 470 25.0 7.3 1.28 .63 .77 .92 23.8 7.0 1.50 .64 .79 .94 22.6 6.6 1.74 .65 .81 .97 21.2 6.2 2.01 .67 .84 .99

71�F600 285 23.6 6.9 1.28 .45 .56 .66 22.6 6.6 1.50 .44 .56 .67 21.6 6.3 1.74 .45 .57 .69 20.4 6.0 2.01 .46 .58 .70

71�F(22�C)

800 380 25.2 7.4 1.29 .46 .59 .71 24.0 7.0 1.50 .46 .60 .72 22.8 6.7 1.74 .47 .61 .74 21.6 6.3 2.01 .47 .62 .76(22�C)

1000 470 26.2 7.7 1.29 .47 .61 .75 25.0 7.3 1.50 .48 .63 .77 23.8 7.0 1.74 .48 .64 .79 22.4 6.6 2.02 .49 .65 .82

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH33−24/30A−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 18.3 5.4 .77 .72 .84 .95 17.5 5.1 .92 .73 .85 .97 16.7 4.9 1.10 .74 .87 .99 15.7 4.6 1.31 .76 .90 1.00

63�F(17�C)

560 265 19.3 5.7 .77 .75 .88 1.00 18.5 5.4 .92 .76 .90 1.00 17.6 5.2 1.10 .78 .93 1.00 16.6 4.9 1.30 .80 .96 1.00(17�C)

660 310 20.2 5.9 .77 .78 .93 1.00 19.2 5.6 .93 .80 .95 1.00 18.3 5.4 1.10 .82 .97 1.00 17.3 5.1 1.30 .84 1.00 1.00

67�F460 215 19.2 5.6 .77 .58 .69 .80 18.5 5.4 .92 .58 .70 .82 17.6 5.2 1.09 .59 .71 .84 16.7 4.9 1.30 .60 .73 .86

67�F(19�C)

560 265 20.4 6.0 .78 .60 .72 .85 19.5 5.7 .93 .60 .74 .86 18.6 5.5 1.10 .61 .75 .89 17.6 5.2 1.30 .62 .77 .92(19�C)

660 310 21.2 6.2 .78 .62 .75 .89 20.4 6.0 .93 .62 .77 .91 19.3 5.7 1.10 .64 .79 .94 18.2 5.3 1.30 .65 .81 .97

71�F460 215 20.2 5.9 .77 .45 .56 .67 19.3 5.7 .92 .46 .57 .68 18.5 5.4 1.10 .45 .57 .69 17.5 5.1 1.30 .45 .58 .70

71�F(22�C)

560 265 21.4 6.3 .77 .46 .58 .70 20.6 6.0 .93 .46 .59 .71 19.6 5.7 1.10 .46 .60 .73 18.5 5.4 1.30 .47 .61 .74(22�C)

660 310 22.4 6.6 .78 .47 .60 .73 21.4 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH33−24/30A−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 23.2 6.8 1.29 .72 .84 .95 22.2 6.5 1.50 .73 .86 .98 21.0 6.2 1.74 .74 .88 1.00 19.7 5.8 2.01 .76 .90 1.00

63�F(17�C)

800 380 24.8 7.3 1.29 .77 .91 1.00 23.6 6.9 1.50 .78 .94 1.00 22.4 6.6 1.74 .80 .96 1.00 21.0 6.2 2.02 .83 .99 1.00(17�C)

1000 470 26.0 7.6 1.29 .82 .97 1.00 24.6 7.2 1.50 .83 .99 1.00 23.4 6.9 1.74 .86 1.00 1.00 22.2 6.5 2.02 .89 1.00 1.00

67�F600 285 24.4 7.2 1.29 .58 .69 .80 23.2 6.8 1.50 .58 .71 .82 22.0 6.4 1.74 .59 .72 .84 20.8 6.1 2.01 .60 .74 .87

67�F(19�C)

800 380 26.0 7.6 1.29 .61 .74 .88 24.8 7.3 1.50 .62 .76 .90 23.4 6.9 1.75 .63 .78 .93 22.0 6.4 2.02 .64 .80 .96(19�C)

1000 470 27.2 8.0 1.30 .64 .79 .94 25.8 7.6 1.51 .65 .81 .97 24.4 7.2 1.75 .66 .84 .99 23.0 6.7 2.01 .68 .87 1.00

71�F600 285 25.4 7.4 1.29 .45 .56 .67 24.2 7.1 1.50 .45 .57 .68 23.0 6.7 1.75 .45 .58 .70 21.8 6.4 2.01 .46 .59 .71

71�F(22�C)

800 380 27.2 8.0 1.29 .46 .60 .72 26.0 7.6 1.51 .47 .61 .74 24.6 7.2 1.75 .47 .62 .76 23.2 6.8 2.02 .48 .63 .78(22�C)

1000 470 28.4 8.3 1.30 .48 .63 .77 27.2 8.0 1.52 .48 .64 .79 25.6 7.5 1.76 .49 .65 .81 24.2 7.1 2.03 .49 .67 .84

Page 41: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 2 TON

HORIZONTAL INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 41

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH33−36A−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 18.5 5.4 .77 .71 .83 .95 17.8 5.2 .92 .72 .84 .97 16.9 5.0 1.10 .73 .86 .99 15.9 4.7 1.31 .75 .89 1.00

63�F(17�C)

560 265 19.6 5.7 .77 .74 .88 1.00 18.7 5.5 .92 .76 .90 1.00 17.7 5.2 1.10 .78 .92 1.00 16.7 4.9 1.30 .79 .95 1.00(17�C)

660 310 20.4 6.0 .77 .78 .92 1.00 19.5 5.7 .93 .79 .95 1.00 18.5 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .84 1.00 1.00

67�F460 215 19.8 5.8 .77 .57 .68 .79 19.0 5.6 .92 .58 .69 .81 18.1 5.3 1.10 .58 .71 .83 17.1 5.0 1.31 .59 .72 .85

67�F(19�C)

560 265 21.0 6.2 .78 .59 .71 .84 20.0 5.9 .93 .60 .73 .86 19.0 5.6 1.10 .61 .75 .88 17.9 5.2 1.30 .62 .76 .91(19�C)

660 310 21.8 6.4 .78 .61 .75 .88 20.8 6.1 .93 .62 .76 .91 19.7 5.8 1.10 .63 .78 .93 18.6 5.5 1.30 .64 .81 .96

71�F460 215 21.0 6.2 .77 .44 .55 .66 20.2 5.9 .92 .45 .56 .67 19.3 5.7 1.10 .45 .57 .68 18.2 5.3 1.30 .45 .57 .69

71�F(22�C)

560 265 22.2 6.5 .78 .45 .57 .69 21.4 6.3 .93 .46 .58 .70 20.2 5.9 1.10 .46 .59 .72 19.1 5.6 1.30 .46 .60 .74(22�C)

660 310 23.2 6.8 .78 .46 .59 .72 22.2 6.5 .93 .46 .60 .74 21.0 6.2 1.10 .47 .61 .76 19.8 5.8 1.30 .47 .63 .78

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH33−36A−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 23.6 6.9 1.28 .71 .83 .95 22.4 6.6 1.50 .72 .85 .97 21.2 6.2 1.74 .74 .87 .99 19.9 5.8 2.01 .76 .90 1.00

63�F(17�C)

800 380 25.0 7.3 1.29 .76 .91 1.00 23.8 7.0 1.50 .78 .93 1.00 22.6 6.6 1.74 .80 .96 1.00 21.2 6.2 2.02 .82 .99 1.00(17�C)

1000 470 26.2 7.7 1.29 .81 .97 1.00 25.0 7.3 1.50 .83 1.00 1.00 23.6 6.9 1.75 .86 1.00 1.00 22.4 6.6 2.02 .89 1.00 1.00

67�F600 285 25.0 7.3 1.29 .57 .69 .80 23.8 7.0 1.50 .58 .70 .81 22.6 6.6 1.75 .59 .71 .84 21.2 6.2 2.01 .60 .73 .86

67�F(19�C)

800 380 26.6 7.8 1.29 .60 .73 .87 25.4 7.4 1.51 .61 .76 .90 24.0 7.0 1.75 .62 .78 .92 22.4 6.6 2.02 .64 .80 .95(19�C)

1000 470 27.8 8.1 1.30 .63 .79 .94 26.4 7.7 1.51 .64 .80 .97 24.8 7.3 1.75 .66 .83 .99 23.2 6.8 2.02 .67 .86 1.00

71�F600 285 26.4 7.7 1.29 .45 .56 .66 25.2 7.4 1.51 .45 .56 .67 23.8 7.0 1.74 .45 .57 .69 22.4 6.6 2.02 .45 .58 .70

71�F(22�C)

800 380 28.2 8.3 1.30 .46 .59 .71 26.8 7.9 1.51 .46 .59 .73 25.4 7.4 1.75 .47 .61 .75 23.8 7.0 2.02 .47 .63 .77(22�C)

1000 470 29.4 8.6 1.31 .47 .62 .77 27.8 8.1 1.52 .48 .63 .78 26.4 7.7 1.76 .48 .64 .81 24.8 7.3 2.02 .49 .66 .84

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH33−36B−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 18.6 5.5 .77 .72 .84 .96 17.8 5.2 .92 .73 .86 .98 16.9 5.0 1.10 .74 .88 1.00 16.0 4.7 1.31 .76 .90 1.00

63�F(17�C)

560 265 19.7 5.8 .77 .75 .89 1.00 18.8 5.5 .92 .77 .91 1.00 17.8 5.2 1.10 .78 .93 1.00 16.8 4.9 1.31 .81 .97 1.00(17�C)

660 310 20.6 6.0 .78 .79 .94 1.00 19.6 5.7 .93 .80 .96 1.00 18.7 5.5 1.10 .82 .98 1.00 17.6 5.2 1.30 .85 1.00 1.00

67�F460 215 19.5 5.7 .77 .58 .69 .80 18.8 5.5 .92 .58 .70 .82 17.9 5.2 1.10 .59 .72 .84 16.9 5.0 1.30 .60 .73 .86

67�F(19�C)

560 265 20.8 6.1 .77 .60 .73 .85 19.9 5.8 .93 .61 .74 .87 18.9 5.5 1.10 .62 .76 .90 17.9 5.2 1.30 .63 .78 .92(19�C)

660 310 21.6 6.3 .77 .62 .76 .90 20.8 6.1 .93 .63 .78 .92 19.7 5.8 1.10 .64 .80 .95 18.6 5.5 1.30 .65 .82 .98

71�F460 215 20.4 6.0 .77 .45 .56 .67 19.6 5.7 .93 .45 .57 .68 18.7 5.5 1.10 .45 .58 .69 17.7 5.2 1.30 .45 .59 .71

71�F(22�C)

560 265 21.8 6.4 .78 .46 .58 .70 20.8 6.1 .93 .46 .59 .72 19.9 5.8 1.10 .46 .60 .73 18.8 5.5 1.30 .47 .61 .75(22�C)

660 310 22.8 6.7 .78 .47 .60 .74 21.8 6.4 .93 .47 .61 .75 20.8 6.1 1.10 .47 .63 .77 19.6 5.7 1.30 .48 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH33−36B−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 23.6 6.9 1.28 .72 .85 .96 22.4 6.6 1.50 .73 .86 .98 21.4 6.3 1.74 .75 .88 1.00 20.0 5.9 2.02 .77 .91 1.00

63�F(17�C)

800 380 25.2 7.4 1.29 .77 .92 1.00 24.0 7.0 1.50 .79 .95 1.00 22.8 6.7 1.74 .81 .97 1.00 21.4 6.3 2.01 .84 1.00 1.00(17�C)

1000 470 26.4 7.7 1.29 .83 .99 1.00 25.2 7.4 1.50 .85 1.00 1.00 24.0 7.0 1.75 .87 1.00 1.00 22.6 6.6 2.02 .91 1.00 1.00

67�F600 285 24.8 7.3 1.29 .58 .70 .81 23.6 6.9 1.50 .59 .71 .83 22.4 6.6 1.74 .60 .72 .85 21.0 6.2 2.01 .61 .74 .88

67�F(19�C)

800 380 26.6 7.8 1.30 .61 .75 .89 25.2 7.4 1.50 .62 .77 .91 24.0 7.0 1.75 .63 .79 .94 22.4 6.6 2.02 .65 .81 .97(19�C)

1000 470 27.8 8.1 1.30 .64 .81 .96 26.4 7.7 1.51 .66 .82 .98 25.0 7.3 1.75 .67 .85 1.00 23.4 6.9 2.02 .69 .88 1.00

71�F600 285 25.8 7.6 1.29 .45 .57 .67 24.6 7.2 1.50 .45 .57 .69 23.4 6.9 1.75 .45 .58 .70 22.0 6.4 2.01 .46 .59 .72

71�F(22�C)

800 380 27.8 8.1 1.30 .46 .60 .73 26.4 7.7 1.51 .47 .61 .75 25.0 7.3 1.75 .47 .62 .77 23.6 6.9 2.02 .48 .64 .79(22�C)

1000 470 29.0 8.5 1.31 .48 .63 .78 27.6 8.1 1.52 .48 .65 .80 26.2 7.7 1.76 .49 .66 .83 24.6 7.2 2.02 .50 .68 .86

Page 42: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 2 TON

HORIZONTAL INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 42

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH33−36C−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 18.7 5.5 .77 .72 .84 .96 17.9 5.2 .92 .73 .86 .98 17.0 5.0 1.10 .75 .88 1.00 16.1 4.7 1.31 .77 .91 1.00

63�F(17�C)

560 265 19.9 5.8 .77 .76 .89 1.00 19.0 5.6 .92 .77 .91 1.00 18.0 5.3 1.09 .79 .94 1.00 17.0 5.0 1.30 .81 .97 1.00(17�C)

660 310 20.8 6.1 .77 .79 .94 1.00 19.8 5.8 .93 .81 .97 1.00 18.9 5.5 1.10 .83 .99 1.00 17.8 5.2 1.30 .85 1.00 1.00

67�F460 215 19.7 5.8 .77 .58 .70 .81 18.9 5.5 .92 .59 .71 .82 18.0 5.3 1.10 .59 .72 .84 17.0 5.0 1.31 .61 .74 .87

67�F(19�C)

560 265 21.0 6.2 .78 .60 .73 .86 20.0 5.9 .93 .61 .75 .88 19.1 5.6 1.10 .62 .76 .90 18.0 5.3 1.31 .63 .78 .93(19�C)

660 310 21.8 6.4 .78 .62 .77 .91 21.0 6.2 .93 .63 .78 .93 19.9 5.8 1.10 .64 .80 .96 18.7 5.5 1.30 .66 .83 .98

71�F460 215 20.6 6.0 .77 .45 .56 .67 19.7 5.8 .92 .45 .57 .68 18.8 5.5 1.10 .45 .58 .70 17.8 5.2 1.30 .46 .59 .71

71�F(22�C)

560 265 22.0 6.4 .78 .46 .59 .71 21.0 6.2 .93 .46 .59 .72 20.0 5.9 1.10 .46 .60 .74 18.9 5.5 1.30 .47 .62 .76(22�C)

660 310 23.0 6.7 .78 .47 .61 .74 22.0 6.4 .93 .47 .62 .76 21.0 6.2 1.10 .47 .63 .78 19.8 5.8 1.30 .48 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH33−36C−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 23.8 7.0 1.28 .73 .85 .97 22.6 6.6 1.50 .74 .87 .99 21.6 6.3 1.73 .75 .89 1.00 20.2 5.9 2.02 .77 .92 1.00

63�F(17�C)

800 380 25.6 7.5 1.29 .78 .93 1.00 24.4 7.2 1.50 .80 .95 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .85 1.00 1.00(17�C)

1000 470 26.8 7.9 1.29 .83 1.00 1.00 25.6 7.5 1.51 .86 1.00 1.00 24.4 7.2 1.75 .88 1.00 1.00 23.0 6.7 2.02 .92 1.00 1.00

67�F600 285 25.0 7.3 1.28 .58 .70 .82 23.8 7.0 1.50 .59 .71 .83 22.6 6.6 1.74 .60 .73 .85 21.2 6.2 2.02 .61 .75 .88

67�F(19�C)

800 380 26.8 7.9 1.30 .62 .76 .89 25.6 7.5 1.51 .63 .77 .92 24.2 7.1 1.75 .64 .79 .95 22.8 6.7 2.02 .65 .82 .98(19�C)

1000 470 28.0 8.2 1.30 .65 .81 .97 26.6 7.8 1.51 .66 .83 .99 25.2 7.4 1.75 .68 .86 1.00 23.6 6.9 2.03 .70 .89 1.00

71�F600 285 26.0 7.6 1.29 .45 .57 .68 24.8 7.3 1.50 .45 .58 .69 23.6 6.9 1.75 .45 .58 .71 22.2 6.5 2.01 .46 .60 .72

71�F(22�C)

800 380 28.0 8.2 1.30 .46 .60 .73 26.8 7.9 1.51 .47 .61 .75 25.4 7.4 1.75 .47 .63 .77 23.8 7.0 2.02 .48 .64 .80(22�C)

1000 470 29.4 8.6 1.30 .48 .64 .79 28.0 8.2 1.52 .49 .65 .81 26.4 7.7 1.75 .49 .67 .84 24.8 7.3 2.02 .50 .69 .87

Page 43: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 2 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 43

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH23−21 + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 18.6 5.5 .77 .76 .90 1.00 17.8 5.2 .93 .78 .92 1.00 17.0 5.0 1.10 .79 .94 1.00 16.1 4.7 1.31 .82 .97 1.00

63�F(17�C)

625 295 18.6 5.5 .77 .76 .90 1.00 17.8 5.2 .93 .78 .92 1.00 17.0 5.0 1.10 .79 .94 1.00 16.1 4.7 1.31 .82 .97 1.00(17�C)

740 350 19.4 5.7 .77 .79 .94 1.00 18.6 5.5 .92 .81 .97 1.00 17.8 5.2 1.10 .83 .98 1.00 17.0 5.0 1.30 .86 1.00 1.00

67�F625 295 19.9 5.8 .77 .60 .74 .86 19.1 5.6 .93 .61 .75 .88 18.2 5.3 1.10 .63 .77 .90 17.2 5.0 1.30 .64 .79 .93

67�F(19�C)

625 295 19.9 5.8 .77 .60 .74 .86 19.1 5.6 .93 .61 .75 .88 18.2 5.3 1.10 .63 .77 .90 17.2 5.0 1.30 .64 .79 .93(19�C)

740 350 20.8 6.1 .78 .62 .77 .90 19.9 5.8 .93 .63 .78 .93 18.9 5.5 1.10 .65 .81 .96 17.9 5.2 1.30 .66 .83 .98

71�F625 295 21.0 6.2 .77 .46 .59 .71 20.2 5.9 .93 .47 .60 .72 19.3 5.7 1.10 .47 .61 .74 18.3 5.4 1.30 .47 .63 .76

71�F(22�C)

625 295 21.0 6.2 .77 .46 .59 .71 20.2 5.9 .93 .47 .60 .72 19.3 5.7 1.10 .47 .61 .74 18.3 5.4 1.30 .47 .63 .76(22�C)

740 350 22.0 6.4 .78 .47 .61 .74 21.2 6.2 .93 .48 .62 .76 20.2 5.9 1.10 .48 .63 .78 19.0 5.6 1.30 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH23−21 + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F825 390 23.6 6.9 1.28 .77 .90 1.00 22.6 6.6 1.50 .78 .93 1.00 21.4 6.3 1.74 .80 .95 1.00 20.2 5.9 2.02 .83 .98 1.00

63�F(17�C)

825 390 23.6 6.9 1.28 .77 .90 1.00 22.6 6.6 1.50 .78 .93 1.00 21.4 6.3 1.74 .80 .95 1.00 20.2 5.9 2.02 .83 .98 1.00(17�C)

1035 490 24.8 7.3 1.29 .81 .97 1.00 23.6 6.9 1.50 .83 .99 1.00 22.6 6.6 1.75 .85 1.00 1.00 21.4 6.3 2.02 .88 1.00 1.00

67�F825 390 25.2 7.4 1.28 .61 .74 .87 24.0 7.0 1.50 .62 .76 .89 22.8 6.7 1.75 .63 .78 .92 21.4 6.3 2.02 .65 .80 .95

67�F(19�C)

825 390 25.2 7.4 1.28 .61 .74 .87 24.0 7.0 1.50 .62 .76 .89 22.8 6.7 1.75 .63 .78 .92 21.4 6.3 2.02 .65 .80 .95(19�C)

1035 490 26.2 7.7 1.29 .64 .79 .94 25.0 7.3 1.51 .65 .81 .97 23.8 7.0 1.74 .66 .83 .98 22.2 6.5 2.02 .68 .86 1.00

71�F825 390 26.4 7.7 1.29 .47 .60 .72 25.2 7.4 1.51 .47 .61 .74 24.0 7.0 1.75 .47 .62 .76 22.6 6.6 2.02 .47 .64 .78

71�F(22�C)

825 390 26.4 7.7 1.29 .47 .60 .72 25.2 7.4 1.51 .47 .61 .74 24.0 7.0 1.75 .47 .62 .76 22.6 6.6 2.02 .47 .64 .78(22�C)

1035 490 27.6 8.1 1.30 .47 .63 .77 26.4 7.7 1.51 .48 .64 .79 25.0 7.3 1.75 .49 .65 .81 23.6 6.9 2.02 .49 .67 .84

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH23−21 + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F610 290 18.5 5.4 .77 .76 .89 .99 17.7 5.2 .93 .77 .91 1.00 16.9 5.0 1.10 .79 .94 1.00 16.0 4.7 1.31 .81 .97 1.00

63�F(17�C)

610 290 18.5 5.4 .77 .76 .89 .99 17.7 5.2 .93 .77 .91 1.00 16.9 5.0 1.10 .79 .94 1.00 16.0 4.7 1.31 .81 .97 1.00(17�C)

720 340 19.3 5.7 .77 .79 .93 1.00 18.5 5.4 .93 .80 .96 1.00 17.7 5.2 1.10 .82 .98 1.00 16.8 4.9 1.31 .85 1.00 1.00

67�F610 290 19.8 5.8 .77 .60 .73 .85 19.0 5.6 .93 .61 .75 .87 18.1 5.3 1.10 .62 .76 .90 17.1 5.0 1.30 .64 .78 .93

67�F(19�C)

610 290 19.8 5.8 .77 .60 .73 .85 19.0 5.6 .93 .61 .75 .87 18.1 5.3 1.10 .62 .76 .90 17.1 5.0 1.30 .64 .78 .93(19�C)

720 340 20.6 6.0 .78 .62 .76 .90 19.7 5.8 .93 .63 .78 .92 18.8 5.5 1.10 .64 .80 .95 17.8 5.2 1.30 .66 .82 .98

71�F610 290 21.0 6.2 .77 .46 .58 .71 20.2 5.9 .93 .47 .60 .72 19.2 5.6 1.10 .47 .61 .74 18.2 5.3 1.30 .47 .62 .76

71�F(22�C)

610 290 21.0 6.2 .77 .46 .58 .71 20.2 5.9 .93 .47 .60 .72 19.2 5.6 1.10 .47 .61 .74 18.2 5.3 1.30 .47 .62 .76(22�C)

720 340 21.8 6.4 .77 .47 .61 .74 21.0 6.2 .93 .47 .62 .75 20.0 5.9 1.10 .48 .63 .77 18.9 5.5 1.30 .48 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH23−21 + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F840 395 23.8 7.0 1.28 .77 .91 1.00 22.6 6.6 1.50 .79 .93 1.00 21.4 6.3 1.74 .80 .96 1.00 20.2 5.9 2.02 .83 .98 1.00

63�F(17�C)

840 395 23.8 7.0 1.28 .77 .91 1.00 22.6 6.6 1.50 .79 .93 1.00 21.4 6.3 1.74 .80 .96 1.00 20.2 5.9 2.02 .83 .98 1.00(17�C)

1050 495 24.8 7.3 1.29 .81 .97 1.00 23.8 7.0 1.50 .83 .99 1.00 22.8 6.7 1.75 .86 1.00 1.00 21.6 6.3 2.02 .89 1.00 1.00

67�F840 395 25.2 7.4 1.29 .61 .75 .88 24.0 7.0 1.50 .62 .76 .90 22.8 6.7 1.75 .64 .78 .93 21.4 6.3 2.02 .65 .81 .96

67�F(19�C)

840 395 25.2 7.4 1.29 .61 .75 .88 24.0 7.0 1.50 .62 .76 .90 22.8 6.7 1.75 .64 .78 .93 21.4 6.3 2.02 .65 .81 .96(19�C)

1050 495 26.4 7.7 1.29 .64 .79 .94 25.2 7.4 1.51 .65 .81 .97 23.8 7.0 1.74 .67 .84 .99 22.2 6.5 2.02 .68 .87 1.00

71�F840 395 26.6 7.8 1.30 .47 .60 .72 25.4 7.4 1.51 .47 .61 .74 24.0 7.0 1.75 .47 .62 .76 22.6 6.6 2.02 .48 .64 .78

71�F(22�C)

840 395 26.6 7.8 1.30 .47 .60 .72 25.4 7.4 1.51 .47 .61 .74 24.0 7.0 1.75 .47 .62 .76 22.6 6.6 2.02 .48 .64 .78(22�C)

1050 495 27.8 8.1 1.30 .47 .63 .77 26.4 7.7 1.51 .49 .64 .79 25.2 7.4 1.75 .49 .66 .81 23.6 6.9 2.02 .50 .68 .84

Page 44: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 2 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 44

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH23−21 + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 18.6 5.5 .77 .76 .90 1.00 17.8 5.2 .93 .78 .92 1.00 17.0 5.0 1.10 .79 .94 1.00 16.1 4.7 1.31 .82 .97 1.00

63�F(17�C)

625 295 18.6 5.5 .77 .76 .90 1.00 17.8 5.2 .93 .78 .92 1.00 17.0 5.0 1.10 .79 .94 1.00 16.1 4.7 1.31 .82 .97 1.00(17�C)

725 340 19.3 5.7 .77 .79 .94 1.00 18.5 5.4 .93 .81 .96 1.00 17.7 5.2 1.10 .83 .98 1.00 16.9 5.0 1.30 .85 1.00 1.00

67�F625 295 19.9 5.8 .77 .60 .74 .86 19.1 5.6 .93 .61 .75 .88 18.2 5.3 1.10 .63 .77 .90 17.2 5.0 1.30 .64 .79 .93

67�F(19�C)

625 295 19.9 5.8 .77 .60 .74 .86 19.1 5.6 .93 .61 .75 .88 18.2 5.3 1.10 .63 .77 .90 17.2 5.0 1.30 .64 .79 .93(19�C)

725 340 20.6 6.0 .78 .62 .76 .90 19.8 5.8 .93 .63 .78 .92 18.8 5.5 1.10 .65 .80 .95 17.8 5.2 1.30 .66 .83 .98

71�F625 295 21.0 6.2 .77 .46 .59 .71 20.2 5.9 .93 .47 .60 .72 19.3 5.7 1.10 .47 .61 .74 18.3 5.4 1.30 .47 .63 .76

71�F(22�C)

625 295 21.0 6.2 .77 .46 .59 .71 20.2 5.9 .93 .47 .60 .72 19.3 5.7 1.10 .47 .61 .74 18.3 5.4 1.30 .47 .63 .76(22�C)

725 340 22.0 6.4 .78 .47 .61 .74 21.0 6.2 .93 .48 .62 .75 20.0 5.9 1.10 .48 .63 .78 19.0 5.6 1.30 .48 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH23−21 + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F830 390 23.6 6.9 1.28 .77 .90 1.00 22.6 6.6 1.50 .78 .93 1.00 21.4 6.3 1.74 .80 .96 1.00 20.2 5.9 2.02 .83 .98 1.00

63�F(17�C)

830 390 23.6 6.9 1.28 .77 .90 1.00 22.6 6.6 1.50 .78 .93 1.00 21.4 6.3 1.74 .80 .96 1.00 20.2 5.9 2.02 .83 .98 1.00(17�C)

1020 480 24.6 7.2 1.29 .81 .97 1.00 23.6 6.9 1.51 .83 .98 1.00 22.6 6.6 1.75 .85 1.00 1.00 21.4 6.3 2.02 .88 1.00 1.00

67�F830 390 25.2 7.4 1.29 .61 .74 .87 24.0 7.0 1.50 .62 .76 .90 22.8 6.7 1.75 .63 .78 .92 21.4 6.3 2.02 .65 .80 .96

67�F(19�C)

830 390 25.2 7.4 1.29 .61 .74 .87 24.0 7.0 1.50 .62 .76 .90 22.8 6.7 1.75 .63 .78 .92 21.4 6.3 2.02 .65 .80 .96(19�C)

1020 480 26.2 7.7 1.29 .64 .79 .93 25.0 7.3 1.51 .65 .81 .96 23.6 6.9 1.74 .66 .83 .98 22.2 6.5 2.02 .68 .86 1.00

71�F830 390 26.4 7.7 1.29 .47 .60 .72 25.2 7.4 1.51 .47 .61 .74 24.0 7.0 1.75 .47 .62 .76 22.6 6.6 2.02 .47 .64 .78

71�F(22�C)

830 390 26.4 7.7 1.29 .47 .60 .72 25.2 7.4 1.51 .47 .61 .74 24.0 7.0 1.75 .47 .62 .76 22.6 6.6 2.02 .47 .64 .78(22�C)

1020 480 27.6 8.1 1.29 .48 .63 .76 26.4 7.7 1.51 .48 .64 .78 25.0 7.3 1.75 .49 .65 .81 23.4 6.9 2.02 .49 .67 .83

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH33−36A−2F + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F630 295 20.2 5.9 .77 .77 .91 1.00 19.3 5.7 .93 .78 .93 1.00 18.3 5.4 1.10 .80 .96 1.00 17.2 5.0 1.31 .82 .99 1.00

63�F(17�C)

630 295 20.2 5.9 .77 .77 .91 1.00 19.3 5.7 .93 .78 .93 1.00 18.3 5.4 1.10 .80 .96 1.00 17.2 5.0 1.31 .82 .99 1.00(17�C)

745 350 21.0 6.2 .78 .80 .96 1.00 20.0 5.9 .93 .82 .98 1.00 18.9 5.5 1.10 .84 1.00 1.00 18.0 5.3 1.30 .87 1.00 1.00

67�F630 295 21.6 6.3 .78 .60 .74 .87 20.6 6.0 .93 .61 .76 .89 19.5 5.7 1.10 .62 .77 .92 18.4 5.4 1.30 .64 .80 .95

67�F(19�C)

630 295 21.6 6.3 .78 .60 .74 .87 20.6 6.0 .93 .61 .76 .89 19.5 5.7 1.10 .62 .77 .92 18.4 5.4 1.30 .64 .80 .95(19�C)

745 350 22.4 6.6 .78 .63 .78 .92 21.4 6.3 .93 .63 .79 .95 20.2 5.9 1.10 .65 .81 .97 19.0 5.6 1.30 .66 .84 1.00

71�F630 295 22.8 6.7 .78 .45 .58 .71 22.0 6.4 .93 .46 .60 .73 20.8 6.1 1.10 .47 .61 .75 19.7 5.8 1.30 .47 .62 .77

71�F(22�C)

630 295 22.8 6.7 .78 .45 .58 .71 22.0 6.4 .93 .46 .60 .73 20.8 6.1 1.10 .47 .61 .75 19.7 5.8 1.30 .47 .62 .77(22�C)

745 350 23.8 7.0 .79 .47 .61 .75 22.6 6.6 .93 .47 .62 .77 21.6 6.3 1.10 .48 .63 .79 20.2 5.9 1.30 .48 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH33−36A−2F + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F830 390 25.2 7.4 1.29 .77 .92 1.00 24.0 7.0 1.50 .79 .94 1.00 22.8 6.7 1.74 .81 .97 1.00 21.2 6.2 2.02 .84 1.00 1.00

63�F(17�C)

830 390 25.2 7.4 1.29 .77 .92 1.00 24.0 7.0 1.50 .79 .94 1.00 22.8 6.7 1.74 .81 .97 1.00 21.2 6.2 2.02 .84 1.00 1.00(17�C)

1040 490 26.4 7.7 1.29 .82 .99 1.00 25.0 7.3 1.51 .84 1.00 1.00 23.8 7.0 1.75 .87 1.00 1.00 22.6 6.6 2.03 .90 1.00 1.00

67�F830 390 26.8 7.9 1.29 .60 .75 .88 25.6 7.5 1.51 .62 .77 .91 24.2 7.1 1.75 .63 .78 .93 22.6 6.6 2.02 .64 .81 .97

67�F(19�C)

830 390 26.8 7.9 1.29 .60 .75 .88 25.6 7.5 1.51 .62 .77 .91 24.2 7.1 1.75 .63 .78 .93 22.6 6.6 2.02 .64 .81 .97(19�C)

1040 490 27.8 8.1 1.30 .64 .80 .95 26.4 7.7 1.51 .65 .81 .98 25.0 7.3 1.74 .67 .85 1.00 23.4 6.9 2.02 .68 .88 1.00

71�F830 390 28.4 8.3 1.30 .46 .59 .72 27.0 7.9 1.51 .46 .60 .74 25.6 7.5 1.75 .47 .62 .76 24.0 7.0 2.02 .47 .63 .78

71�F(22�C)

830 390 28.4 8.3 1.30 .46 .59 .72 27.0 7.9 1.51 .46 .60 .74 25.6 7.5 1.75 .47 .62 .76 24.0 7.0 2.02 .47 .63 .78(22�C)

1040 490 29.4 8.6 1.30 .47 .63 .78 28.0 8.2 1.52 .48 .64 .79 26.4 7.7 1.75 .48 .65 .82 24.8 7.3 2.02 .49 .67 .85

Page 45: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 2 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 45

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH33−36B−2F + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 20.2 5.9 .77 .78 .92 1.00 19.3 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .83 1.00 1.00

63�F(17�C)

625 295 20.2 5.9 .77 .78 .92 1.00 19.3 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .83 1.00 1.00(17�C)

740 350 21.2 6.2 .78 .81 .97 1.00 20.2 5.9 .93 .83 .99 1.00 19.2 5.6 1.10 .85 1.00 1.00 18.3 5.4 1.30 .88 1.00 1.00

67�F625 295 21.4 6.3 .78 .61 .75 .88 20.4 6.0 .93 .62 .76 .91 19.4 5.7 1.10 .63 .78 .93 18.3 5.4 1.30 .64 .81 .96

67�F(19�C)

625 295 21.4 6.3 .78 .61 .75 .88 20.4 6.0 .93 .62 .76 .91 19.4 5.7 1.10 .63 .78 .93 18.3 5.4 1.30 .64 .81 .96(19�C)

740 350 22.2 6.5 .78 .63 .79 .93 21.2 6.2 .93 .65 .80 .96 20.2 5.9 1.10 .66 .83 .98 19.0 5.6 1.30 .67 .85 1.00

71�F625 295 22.4 6.6 .78 .46 .60 .72 21.4 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78

71�F(22�C)

625 295 22.4 6.6 .78 .46 .60 .72 21.4 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78(22�C)

740 350 23.4 6.9 .78 .47 .62 .76 22.4 6.6 .93 .47 .63 .78 21.2 6.2 1.10 .48 .65 .80 20.0 5.9 1.30 .49 .66 .83

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH33−36B−2F + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F825 390 25.4 7.4 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.01 .85 1.00 1.00

63�F(17�C)

825 390 25.4 7.4 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.01 .85 1.00 1.00(17�C)

1035 490 26.6 7.8 1.30 .84 1.00 1.00 25.4 7.4 1.51 .86 1.00 1.00 24.2 7.1 1.75 .88 1.00 1.00 22.8 6.7 2.02 .92 1.00 1.00

67�F825 390 26.8 7.9 1.29 .62 .76 .90 25.4 7.4 1.51 .63 .78 .92 24.0 7.0 1.75 .64 .80 .95 22.6 6.6 2.02 .65 .82 .98

67�F(19�C)

825 390 26.8 7.9 1.29 .62 .76 .90 25.4 7.4 1.51 .63 .78 .92 24.0 7.0 1.75 .64 .80 .95 22.6 6.6 2.02 .65 .82 .98(19�C)

1035 490 28.0 8.2 1.30 .65 .81 .97 26.6 7.8 1.51 .66 .83 .99 25.0 7.3 1.75 .68 .86 1.00 23.4 6.9 2.03 .70 .89 1.00

71�F825 390 28.0 8.2 1.30 .47 .60 .74 26.6 7.8 1.51 .47 .62 .75 25.2 7.4 1.75 .48 .63 .77 23.8 7.0 2.02 .48 .64 .80

71�F(22�C)

825 390 28.0 8.2 1.30 .47 .60 .74 26.6 7.8 1.51 .47 .62 .75 25.2 7.4 1.75 .48 .63 .77 23.8 7.0 2.02 .48 .64 .80(22�C)

1035 490 29.2 8.6 1.31 .48 .64 .79 27.8 8.1 1.52 .48 .65 .81 26.4 7.7 1.76 .49 .67 .84 24.8 7.3 2.02 .50 .69 .87

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH33−36B−2F + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F610 290 20.0 5.9 .77 .77 .91 1.00 19.2 5.6 .93 .79 .93 1.00 18.3 5.4 1.10 .80 .96 1.00 17.2 5.0 1.30 .83 .99 1.00

63�F(17�C)

610 290 20.0 5.9 .77 .77 .91 1.00 19.2 5.6 .93 .79 .93 1.00 18.3 5.4 1.10 .80 .96 1.00 17.2 5.0 1.30 .83 .99 1.00(17�C)

720 340 21.0 6.2 .78 .81 .96 1.00 20.0 5.9 .93 .82 .98 1.00 19.1 5.6 1.10 .85 1.00 1.00 18.1 5.3 1.30 .87 1.00 1.00

67�F610 290 21.2 6.2 .78 .61 .74 .88 20.4 6.0 .93 .62 .76 .90 19.3 5.7 1.10 .63 .78 .92 18.2 5.3 1.30 .64 .80 .95

67�F(19�C)

610 290 21.2 6.2 .78 .61 .74 .88 20.4 6.0 .93 .62 .76 .90 19.3 5.7 1.10 .63 .78 .92 18.2 5.3 1.30 .64 .80 .95(19�C)

720 340 22.2 6.5 .78 .63 .78 .93 21.2 6.2 .93 .64 .80 .95 20.0 5.9 1.10 .65 .82 .97 18.9 5.5 1.30 .67 .85 1.00

71�F610 290 22.2 6.5 .78 .46 .59 .72 21.4 6.3 .93 .47 .60 .73 20.4 6.0 1.10 .47 .61 .75 19.2 5.6 1.30 .47 .63 .77

71�F(22�C)

610 290 22.2 6.5 .78 .46 .59 .72 21.4 6.3 .93 .47 .60 .73 20.4 6.0 1.10 .47 .61 .75 19.2 5.6 1.30 .47 .63 .77(22�C)

720 340 23.2 6.8 .78 .47 .62 .76 22.2 6.5 .93 .48 .63 .77 21.2 6.2 1.10 .48 .64 .79 19.9 5.8 1.30 .49 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH33−36B−2F + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F840 395 25.6 7.5 1.29 .79 .94 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.75 .82 .99 1.00 21.6 6.3 2.02 .85 1.00 1.00

63�F(17�C)

840 395 25.6 7.5 1.29 .79 .94 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.75 .82 .99 1.00 21.6 6.3 2.02 .85 1.00 1.00(17�C)

1050 495 26.8 7.9 1.30 .84 1.00 1.00 25.6 7.5 1.51 .86 1.00 1.00 24.2 7.1 1.75 .89 1.00 1.00 23.0 6.7 2.02 .92 1.00 1.00

67�F840 395 26.8 7.9 1.29 .62 .76 .90 25.6 7.5 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .96 22.6 6.6 2.02 .66 .83 .99

67�F(19�C)

840 395 26.8 7.9 1.29 .62 .76 .90 25.6 7.5 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .96 22.6 6.6 2.02 .66 .83 .99(19�C)

1050 495 28.0 8.2 1.30 .65 .82 .97 26.6 7.8 1.51 .66 .84 .99 25.2 7.4 1.75 .68 .87 1.00 23.6 6.9 2.02 .70 .90 1.00

71�F840 395 28.0 8.2 1.30 .47 .61 .74 26.8 7.9 1.52 .47 .62 .76 25.4 7.4 1.75 .48 .63 .78 23.8 7.0 2.02 .48 .65 .80

71�F(22�C)

840 395 28.0 8.2 1.30 .47 .61 .74 26.8 7.9 1.52 .47 .62 .76 25.4 7.4 1.75 .48 .63 .78 23.8 7.0 2.02 .48 .65 .80(22�C)

1050 495 29.4 8.6 1.30 .48 .64 .80 28.0 8.2 1.52 .49 .66 .82 26.4 7.7 1.76 .49 .67 .84 24.8 7.3 2.02 .50 .69 .88

Page 46: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 2 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 46

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH33−36B−2F + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 20.2 5.9 .77 .78 .92 1.00 19.3 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .83 1.00 1.00

63�F(17�C)

625 295 20.2 5.9 .77 .78 .92 1.00 19.3 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .83 1.00 1.00(17�C)

725 340 21.0 6.2 .78 .81 .97 1.00 20.2 5.9 .93 .83 .99 1.00 19.1 5.6 1.10 .85 1.00 1.00 18.1 5.3 1.30 .88 1.00 1.00

67�F625 295 21.4 6.3 .78 .61 .75 .88 20.4 6.0 .93 .62 .76 .91 19.4 5.7 1.10 .63 .78 .93 18.3 5.4 1.30 .64 .81 .96

67�F(19�C)

625 295 21.4 6.3 .78 .61 .75 .88 20.4 6.0 .93 .62 .76 .91 19.4 5.7 1.10 .63 .78 .93 18.3 5.4 1.30 .64 .81 .96(19�C)

725 340 22.2 6.5 .78 .63 .78 .93 21.2 6.2 .93 .64 .80 .95 20.0 5.9 1.10 .66 .82 .98 18.9 5.5 1.30 .67 .85 1.00

71�F625 295 22.4 6.6 .78 .46 .60 .72 21.4 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78

71�F(22�C)

625 295 22.4 6.6 .78 .46 .60 .72 21.4 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78(22�C)

725 340 23.2 6.8 .78 .47 .62 .76 22.2 6.5 .93 .48 .63 .78 21.2 6.2 1.10 .48 .64 .80 20.0 5.9 1.30 .49 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH33−36B−2F + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F830 390 25.4 7.4 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.01 .85 1.00 1.00

63�F(17�C)

830 390 25.4 7.4 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.01 .85 1.00 1.00(17�C)

1020 480 26.6 7.8 1.29 .83 .99 1.00 25.4 7.4 1.51 .85 1.00 1.00 24.0 7.0 1.75 .88 1.00 1.00 22.8 6.7 2.02 .91 1.00 1.00

67�F830 390 26.8 7.9 1.29 .62 .76 .90 25.4 7.4 1.51 .63 .78 .92 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .82 .98

67�F(19�C)

830 390 26.8 7.9 1.29 .62 .76 .90 25.4 7.4 1.51 .63 .78 .92 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .82 .98(19�C)

1020 480 27.8 8.1 1.30 .65 .81 .96 26.4 7.7 1.51 .66 .83 .99 25.0 7.3 1.74 .67 .86 1.00 23.4 6.9 2.02 .69 .89 1.00

71�F830 390 28.0 8.2 1.30 .47 .61 .74 26.6 7.8 1.51 .47 .62 .75 25.2 7.4 1.75 .48 .63 .78 23.8 7.0 2.02 .48 .64 .80

71�F(22�C)

830 390 28.0 8.2 1.30 .47 .61 .74 26.6 7.8 1.51 .47 .62 .75 25.2 7.4 1.75 .48 .63 .78 23.8 7.0 2.02 .48 .64 .80(22�C)

1020 480 29.2 8.6 1.31 .48 .64 .79 27.8 8.1 1.52 .48 .65 .81 26.2 7.7 1.76 .49 .67 .83 24.6 7.2 2.02 .50 .68 .86

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH33−42B−2F + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 20.2 5.9 .77 .78 .92 1.00 19.4 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .84 1.00 1.00

63�F(17�C)

625 295 20.2 5.9 .77 .78 .92 1.00 19.4 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .84 1.00 1.00(17�C)

740 350 21.2 6.2 .78 .82 .97 1.00 20.2 5.9 .93 .83 .99 1.00 19.3 5.7 1.10 .86 1.00 1.00 18.3 5.4 1.30 .89 1.00 1.00

67�F625 295 21.4 6.3 .78 .61 .75 .89 20.4 6.0 .93 .62 .77 .91 19.5 5.7 1.10 .63 .79 .93 18.3 5.4 1.30 .65 .81 .96

67�F(19�C)

625 295 21.4 6.3 .78 .61 .75 .89 20.4 6.0 .93 .62 .77 .91 19.5 5.7 1.10 .63 .79 .93 18.3 5.4 1.30 .65 .81 .96(19�C)

740 350 22.2 6.5 .78 .64 .79 .94 21.2 6.2 .93 .65 .81 .96 20.2 5.9 1.10 .66 .83 .99 19.0 5.6 1.30 .68 .86 1.00

71�F625 295 22.4 6.6 .78 .46 .60 .73 21.6 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78

71�F(22�C)

625 295 22.4 6.6 .78 .46 .60 .73 21.6 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78(22�C)

740 350 23.4 6.9 .78 .47 .62 .76 22.4 6.6 .93 .48 .63 .78 21.2 6.2 1.10 .48 .65 .80 20.0 5.9 1.30 .49 .66 .83

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH33−42B−2F + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F825 390 25.4 7.4 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .85 1.00 1.00

63�F(17�C)

825 390 25.4 7.4 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .85 1.00 1.00(17�C)

1035 490 26.8 7.9 1.29 .84 1.00 1.00 25.6 7.5 1.51 .86 1.00 1.00 24.2 7.1 1.75 .89 1.00 1.00 23.0 6.7 2.02 .92 1.00 1.00

67�F825 390 26.8 7.9 1.29 .62 .76 .90 25.4 7.4 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .83 .98

67�F(19�C)

825 390 26.8 7.9 1.29 .62 .76 .90 25.4 7.4 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .83 .98(19�C)

1035 490 28.0 8.2 1.30 .65 .82 .97 26.6 7.8 1.51 .66 .84 .99 25.0 7.3 1.74 .68 .87 1.00 23.4 6.9 2.02 .70 .90 1.00

71�F825 390 28.0 8.2 1.30 .47 .61 .74 26.6 7.8 1.51 .47 .62 .75 25.2 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .64 .80

71�F(22�C)

825 390 28.0 8.2 1.30 .47 .61 .74 26.6 7.8 1.51 .47 .62 .75 25.2 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .64 .80(22�C)

1035 490 29.2 8.6 1.30 .48 .64 .79 27.8 8.1 1.52 .49 .65 .82 26.4 7.7 1.76 .49 .67 .84 24.8 7.3 2.02 .50 .69 .87

Page 47: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 2 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 47

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH33−42B−2F + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F610 290 20.4 6.0 .77 .76 .90 1.00 19.4 5.7 .92 .78 .93 1.00 18.4 5.4 1.10 .80 .95 1.00 17.3 5.1 1.30 .82 .98 1.00

63�F(17�C)

610 290 20.4 6.0 .77 .76 .90 1.00 19.4 5.7 .92 .78 .93 1.00 18.4 5.4 1.10 .80 .95 1.00 17.3 5.1 1.30 .82 .98 1.00(17�C)

725 340 21.2 6.2 .78 .80 .96 1.00 20.2 5.9 .93 .82 .98 1.00 19.2 5.6 1.10 .84 1.00 1.00 18.2 5.3 1.30 .87 1.00 1.00

67�F610 290 21.8 6.4 .78 .60 .73 .86 20.8 6.1 .93 .61 .75 .88 19.7 5.8 1.10 .62 .77 .91 18.6 5.5 1.30 .63 .79 .94

67�F(19�C)

610 290 21.8 6.4 .78 .60 .73 .86 20.8 6.1 .93 .61 .75 .88 19.7 5.8 1.10 .62 .77 .91 18.6 5.5 1.30 .63 .79 .94(19�C)

725 340 22.6 6.6 .78 .62 .78 .92 21.6 6.3 .93 .63 .79 .94 20.4 6.0 1.10 .64 .81 .97 19.2 5.6 1.30 .66 .84 1.00

71�F610 290 23.2 6.8 .78 .46 .58 .71 22.2 6.5 .93 .46 .59 .72 21.0 6.2 1.10 .46 .60 .74 19.8 5.8 1.30 .47 .62 .76

71�F(22�C)

610 290 23.2 6.8 .78 .46 .58 .71 22.2 6.5 .93 .46 .59 .72 21.0 6.2 1.10 .46 .60 .74 19.8 5.8 1.30 .47 .62 .76(22�C)

725 340 24.0 7.0 .79 .47 .61 .74 23.0 6.7 .93 .47 .62 .76 21.8 6.4 1.10 .47 .63 .78 20.6 6.0 1.30 .48 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH33−42B−2F + G61MPV−36B−045]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F840 395 25.8 7.6 1.29 .78 .93 1.00 24.6 7.2 1.51 .79 .95 1.00 23.2 6.8 1.75 .81 .98 1.00 21.8 6.4 2.02 .84 1.00 1.00

63�F(17�C)

840 395 25.8 7.6 1.29 .78 .93 1.00 24.6 7.2 1.51 .79 .95 1.00 23.2 6.8 1.75 .81 .98 1.00 21.8 6.4 2.02 .84 1.00 1.00(17�C)

1050 495 27.0 7.9 1.29 .83 .99 1.00 25.8 7.6 1.51 .84 1.00 1.00 24.6 7.2 1.75 .88 1.00 1.00 23.2 6.8 2.02 .91 1.00 1.00

67�F840 395 27.4 8.0 1.30 .61 .75 .89 26.0 7.6 1.51 .62 .77 .92 24.6 7.2 1.75 .63 .79 .94 23.0 6.7 2.02 .65 .82 .98

67�F(19�C)

840 395 27.4 8.0 1.30 .61 .75 .89 26.0 7.6 1.51 .62 .77 .92 24.6 7.2 1.75 .63 .79 .94 23.0 6.7 2.02 .65 .82 .98(19�C)

1050 495 28.6 8.4 1.30 .64 .81 .96 27.0 7.9 1.51 .65 .83 .99 25.6 7.5 1.75 .67 .86 1.00 24.0 7.0 2.02 .70 .89 1.00

71�F840 395 29.0 8.5 1.30 .46 .60 .73 27.6 8.1 1.52 .47 .61 .75 26.0 7.6 1.75 .47 .62 .77 24.4 7.2 2.03 .48 .63 .79

71�F(22�C)

840 395 29.0 8.5 1.30 .46 .60 .73 27.6 8.1 1.52 .47 .61 .75 26.0 7.6 1.75 .47 .62 .77 24.4 7.2 2.03 .48 .63 .79(22�C)

1050 495 30.2 8.9 1.31 .48 .63 .79 28.6 8.4 1.52 .48 .64 .81 27.0 7.9 1.76 .48 .65 .83 25.4 7.4 2.03 .50 .68 .86

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH33−42B−2F + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 20.4 6.0 .77 .76 .91 1.00 19.5 5.7 .93 .78 .93 1.00 18.5 5.4 1.10 .80 .96 1.00 17.4 5.1 1.30 .83 .99 1.00

63�F(17�C)

625 295 20.4 6.0 .77 .76 .91 1.00 19.5 5.7 .93 .78 .93 1.00 18.5 5.4 1.10 .80 .96 1.00 17.4 5.1 1.30 .83 .99 1.00(17�C)

725 340 21.2 6.2 .77 .80 .96 1.00 20.2 5.9 .93 .82 .98 1.00 19.2 5.6 1.10 .84 1.00 1.00 18.2 5.3 1.30 .87 1.00 1.00

67�F625 295 21.8 6.4 .78 .60 .74 .87 20.8 6.1 .93 .61 .75 .89 19.8 5.8 1.10 .62 .77 .92 18.7 5.5 1.30 .63 .79 .95

67�F(19�C)

625 295 21.8 6.4 .78 .60 .74 .87 20.8 6.1 .93 .61 .75 .89 19.8 5.8 1.10 .62 .77 .92 18.7 5.5 1.30 .63 .79 .95(19�C)

725 340 22.6 6.6 .78 .62 .78 .92 21.6 6.3 .93 .63 .79 .94 20.4 6.0 1.10 .64 .81 .97 19.2 5.6 1.30 .66 .84 1.00

71�F625 295 23.2 6.8 .78 .46 .59 .71 22.2 6.5 .93 .46 .60 .73 21.2 6.2 1.10 .47 .61 .74 19.9 5.8 1.30 .47 .62 .77

71�F(22�C)

625 295 23.2 6.8 .78 .46 .59 .71 22.2 6.5 .93 .46 .60 .73 21.2 6.2 1.10 .47 .61 .74 19.9 5.8 1.30 .47 .62 .77(22�C)

725 340 24.0 7.0 .79 .47 .61 .75 23.0 6.7 .93 .47 .62 .76 21.8 6.4 1.10 .47 .63 .78 20.6 6.0 1.30 .48 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH33−42B−2F + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F830 390 25.8 7.6 1.29 .77 .92 1.00 24.6 7.2 1.51 .79 .95 1.00 23.2 6.8 1.74 .81 .98 1.00 21.8 6.4 2.01 .84 1.00 1.00

63�F(17�C)

830 390 25.8 7.6 1.29 .77 .92 1.00 24.6 7.2 1.51 .79 .95 1.00 23.2 6.8 1.74 .81 .98 1.00 21.8 6.4 2.01 .84 1.00 1.00(17�C)

1020 480 27.0 7.9 1.30 .82 .99 1.00 25.6 7.5 1.51 .84 1.00 1.00 24.4 7.2 1.75 .87 1.00 1.00 23.0 6.7 2.02 .90 1.00 1.00

67�F830 390 27.4 8.0 1.30 .61 .75 .89 26.0 7.6 1.51 .62 .76 .91 24.6 7.2 1.75 .63 .78 .94 23.0 6.7 2.01 .65 .81 .97

67�F(19�C)

830 390 27.4 8.0 1.30 .61 .75 .89 26.0 7.6 1.51 .62 .76 .91 24.6 7.2 1.75 .63 .78 .94 23.0 6.7 2.01 .65 .81 .97(19�C)

1020 480 28.4 8.3 1.30 .64 .80 .95 27.0 7.9 1.51 .65 .82 .98 25.4 7.4 1.75 .66 .85 1.00 23.8 7.0 2.02 .69 .88 1.00

71�F830 390 29.0 8.5 1.30 .46 .60 .73 27.6 8.1 1.52 .47 .61 .74 26.0 7.6 1.76 .47 .62 .76 24.4 7.2 2.03 .48 .63 .78

71�F(22�C)

830 390 29.0 8.5 1.30 .46 .60 .73 27.6 8.1 1.52 .47 .61 .74 26.0 7.6 1.76 .47 .62 .76 24.4 7.2 2.03 .48 .63 .78(22�C)

1020 480 30.0 8.8 1.31 .47 .63 .77 28.6 8.4 1.52 .48 .64 .80 27.0 7.9 1.76 .48 .65 .81 25.2 7.4 2.03 .49 .68 .85

Page 48: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 2 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 48

FIRST STAGE COOLING CAPACITY − XC21−024 with [CH33−44/48B−2F + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 20.2 5.9 .77 .78 .92 1.00 19.4 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .84 1.00 1.00

63�F(17�C)

625 295 20.2 5.9 .77 .78 .92 1.00 19.4 5.7 .93 .79 .94 1.00 18.4 5.4 1.10 .81 .97 1.00 17.4 5.1 1.30 .84 1.00 1.00(17�C)

740 350 21.2 6.2 .78 .82 .97 1.00 20.2 5.9 .93 .83 .99 1.00 19.3 5.7 1.10 .86 1.00 1.00 18.3 5.4 1.30 .89 1.00 1.00

67�F625 295 21.4 6.3 .78 .61 .75 .89 20.4 6.0 .93 .62 .77 .91 19.5 5.7 1.10 .63 .79 .93 18.3 5.4 1.30 .65 .81 .96

67�F(19�C)

625 295 21.4 6.3 .78 .61 .75 .89 20.4 6.0 .93 .62 .77 .91 19.5 5.7 1.10 .63 .79 .93 18.3 5.4 1.30 .65 .81 .96(19�C)

740 350 22.2 6.5 .78 .64 .79 .94 21.2 6.2 .93 .65 .81 .96 20.2 5.9 1.10 .66 .83 .99 19.0 5.6 1.30 .68 .86 1.00

71�F625 295 22.4 6.6 .78 .46 .60 .73 21.6 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78

71�F(22�C)

625 295 22.4 6.6 .78 .46 .60 .73 21.6 6.3 .93 .47 .61 .74 20.4 6.0 1.10 .47 .62 .76 19.3 5.7 1.30 .48 .63 .78(22�C)

740 350 23.4 6.9 .78 .47 .62 .76 22.4 6.6 .93 .48 .63 .78 21.2 6.2 1.10 .48 .65 .80 20.0 5.9 1.30 .49 .66 .83

SECOND STAGE COOLING CAPACITY − XC21−024 with [CH33−44/48B−2F + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F825 390 25.4 7.4 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .85 1.00 1.00

63�F(17�C)

825 390 25.4 7.4 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .96 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .85 1.00 1.00(17�C)

1035 490 26.8 7.9 1.29 .84 1.00 1.00 25.6 7.5 1.51 .86 1.00 1.00 24.2 7.1 1.75 .89 1.00 1.00 23.0 6.7 2.02 .92 1.00 1.00

67�F825 390 26.8 7.9 1.29 .62 .76 .90 25.4 7.4 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .83 .98

67�F(19�C)

825 390 26.8 7.9 1.29 .62 .76 .90 25.4 7.4 1.51 .63 .78 .93 24.2 7.1 1.75 .64 .80 .95 22.6 6.6 2.02 .66 .83 .98(19�C)

1035 490 28.0 8.2 1.30 .65 .82 .97 26.6 7.8 1.51 .66 .84 .99 25.0 7.3 1.74 .68 .87 1.00 23.4 6.9 2.02 .70 .90 1.00

71�F825 390 28.0 8.2 1.30 .47 .61 .74 26.6 7.8 1.51 .47 .62 .75 25.2 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .64 .80

71�F(22�C)

825 390 28.0 8.2 1.30 .47 .61 .74 26.6 7.8 1.51 .47 .62 .75 25.2 7.4 1.75 .48 .63 .78 23.8 7.0 2.03 .48 .64 .80(22�C)

1035 490 29.2 8.6 1.30 .48 .64 .79 27.8 8.1 1.52 .49 .65 .82 26.4 7.7 1.76 .49 .67 .84 24.8 7.3 2.02 .50 .69 .87

Page 49: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 2 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 49

FIRST STAGE COOLING CAPACITY − XC21−024 with [CBX32M−030][CB30M−31] [CB30U−31]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 19.0 5.6 .77 .72 .84 .96 18.1 5.3 .93 .72 .85 .98 17.2 5.0 1.10 .74 .88 1.00 16.2 4.7 1.31 .76 .90 1.00

63�F(17�C)

560 265 20.0 5.9 .77 .75 .89 1.00 19.1 5.6 .92 .77 .91 1.00 18.1 5.3 1.10 .79 .94 1.00 17.1 5.0 1.30 .81 .97 1.00(17�C)

660 310 20.8 6.1 .77 .79 .94 1.00 19.9 5.8 .93 .81 .97 1.00 18.9 5.5 1.10 .83 .99 1.00 17.8 5.2 1.30 .85 1.00 1.00

67�F460 215 20.2 5.9 .77 .57 .69 .80 19.4 5.7 .92 .58 .70 .82 18.4 5.4 1.10 .58 .71 .83 17.4 5.1 1.30 .59 .73 .86

67�F(19�C)

560 265 21.4 6.3 .77 .60 .73 .85 20.4 6.0 .93 .60 .74 .87 19.4 5.7 1.10 .61 .75 .90 18.2 5.3 1.30 .63 .78 .93(19�C)

660 310 22.2 6.5 .78 .62 .76 .90 21.2 6.2 .93 .63 .78 .93 20.2 5.9 1.10 .64 .80 .95 18.9 5.5 1.30 .65 .82 .98

71�F460 215 21.4 6.3 .77 .44 .55 .66 20.6 6.0 .93 .45 .56 .67 19.6 5.7 1.10 .45 .57 .68 18.5 5.4 1.30 .45 .58 .70

71�F(22�C)

560 265 22.6 6.6 .78 .45 .57 .69 21.6 6.3 .93 .45 .59 .71 20.6 6.0 1.10 .46 .59 .73 19.5 5.7 1.30 .46 .61 .75(22�C)

660 310 23.6 6.9 .78 .46 .60 .74 22.6 6.6 .93 .47 .61 .75 21.4 6.3 1.10 .47 .62 .77 20.2 5.9 1.30 .48 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−024 with [CBX32M−030][CB30M−31] [CB30U−31]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 24.0 7.0 1.29 .72 .84 .96 22.8 6.7 1.50 .73 .86 .98 21.6 6.3 1.74 .75 .88 1.00 20.2 5.9 2.01 .77 .91 1.00

63�F(17�C)

800 380 25.6 7.5 1.29 .78 .93 1.00 24.4 7.2 1.50 .80 .95 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.02 .84 1.00 1.00(17�C)

1000 470 26.8 7.9 1.29 .84 .99 1.00 25.6 7.5 1.51 .86 1.00 1.00 24.4 7.2 1.75 .88 1.00 1.00 23.0 6.7 2.02 .92 1.00 1.00

67�F600 285 25.4 7.4 1.28 .58 .69 .81 24.2 7.1 1.50 .58 .71 .83 23.0 6.7 1.74 .59 .72 .85 21.6 6.3 2.02 .60 .74 .88

67�F(19�C)

800 380 27.2 8.0 1.30 .61 .75 .89 25.8 7.6 1.51 .62 .77 .92 24.4 7.2 1.75 .63 .79 .95 22.8 6.7 2.02 .65 .82 .98(19�C)

1000 470 28.2 8.3 1.30 .65 .81 .97 26.8 7.9 1.51 .66 .83 .99 25.4 7.4 1.75 .67 .86 1.00 23.6 6.9 2.02 .70 .89 1.00

71�F600 285 26.8 7.9 1.29 .45 .56 .67 25.6 7.5 1.51 .45 .57 .68 24.2 7.1 1.74 .45 .58 .70 22.8 6.7 2.02 .45 .59 .72

71�F(22�C)

800 380 28.6 8.4 1.30 .46 .60 .73 27.2 8.0 1.51 .46 .61 .75 25.8 7.6 1.75 .47 .62 .77 24.2 7.1 2.02 .48 .64 .80(22�C)

1000 470 29.8 8.7 1.31 .48 .64 .79 28.4 8.3 1.52 .48 .65 .81 26.8 7.9 1.76 .49 .66 .84 25.2 7.4 2.03 .50 .69 .86

FIRST STAGE COOLING CAPACITY − XC21−024 with [CBX32M−036][CB30M−41] [CB30U−41/46]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 19.1 5.6 .77 .72 .84 .96 18.2 5.3 .93 .73 .85 .98 17.2 5.0 1.10 .74 .88 1.00 16.2 4.7 1.31 .76 .90 1.00

63�F(17�C)

560 265 20.2 5.9 .77 .75 .89 1.00 19.2 5.6 .92 .76 .91 1.00 18.2 5.3 1.10 .79 .94 1.00 17.1 5.0 1.30 .81 .97 1.00(17�C)

660 310 21.0 6.2 .77 .79 .94 1.00 20.0 5.9 .93 .81 .97 1.00 18.9 5.5 1.10 .83 .99 1.00 17.9 5.2 1.30 .85 1.00 1.00

67�F460 215 20.4 6.0 .77 .57 .69 .80 19.4 5.7 .92 .58 .70 .82 18.5 5.4 1.10 .59 .71 .83 17.4 5.1 1.30 .59 .73 .86

67�F(19�C)

560 265 21.4 6.3 .78 .59 .73 .85 20.6 6.0 .93 .60 .74 .87 19.5 5.7 1.10 .61 .76 .90 18.3 5.4 1.30 .62 .78 .93(19�C)

660 310 22.4 6.6 .78 .62 .76 .91 21.4 6.3 .93 .63 .78 .93 20.2 5.9 1.10 .64 .80 .96 19.0 5.6 1.30 .65 .82 .98

71�F460 215 21.6 6.3 .77 .44 .55 .66 20.6 6.0 .93 .45 .56 .67 19.6 5.7 1.10 .45 .57 .68 18.6 5.5 1.30 .45 .58 .70

71�F(22�C)

560 265 22.8 6.7 .78 .45 .58 .70 21.8 6.4 .93 .45 .59 .71 20.6 6.0 1.10 .46 .60 .73 19.5 5.7 1.30 .46 .61 .75(22�C)

660 310 23.8 7.0 .78 .46 .60 .73 22.6 6.6 .93 .47 .61 .75 21.6 6.3 1.10 .47 .62 .77 20.2 5.9 1.30 .48 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−024 with [CBX32M−036][CB30M−41] [CB30U−41/46]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 24.2 7.1 1.29 .72 .85 .97 23.0 6.7 1.50 .73 .86 .99 21.6 6.3 1.74 .75 .89 1.00 20.4 6.0 2.01 .77 .92 1.00

63�F(17�C)

800 380 25.8 7.6 1.29 .78 .93 1.00 24.6 7.2 1.50 .80 .96 1.00 23.2 6.8 1.75 .82 .98 1.00 21.8 6.4 2.01 .85 1.00 1.00(17�C)

1000 470 27.0 7.9 1.30 .84 1.00 1.00 25.8 7.6 1.51 .86 1.00 1.00 24.4 7.2 1.75 .89 1.00 1.00 23.2 6.8 2.02 .92 1.00 1.00

67�F600 285 25.6 7.5 1.29 .58 .69 .81 24.4 7.2 1.50 .58 .71 .83 23.0 6.7 1.74 .59 .72 .85 21.6 6.3 2.02 .60 .74 .88

67�F(19�C)

800 380 27.4 8.0 1.30 .61 .76 .90 26.0 7.6 1.51 .62 .77 .92 24.4 7.2 1.75 .64 .80 .95 23.0 6.7 2.01 .65 .82 .98(19�C)

1000 470 28.4 8.3 1.30 .65 .81 .97 27.0 7.9 1.51 .66 .84 .99 25.4 7.4 1.75 .68 .86 1.00 23.8 7.0 2.02 .70 .90 1.00

71�F600 285 27.0 7.9 1.29 .45 .56 .67 25.6 7.5 1.51 .45 .57 .68 24.4 7.2 1.74 .45 .57 .70 23.0 6.7 2.02 .45 .59 .72

71�F(22�C)

800 380 28.8 8.4 1.30 .46 .60 .73 27.4 8.0 1.51 .46 .61 .75 26.0 7.6 1.76 .47 .62 .77 24.4 7.2 2.02 .48 .64 .80(22�C)

1000 470 30.0 8.8 1.31 .48 .64 .79 28.6 8.4 1.52 .48 .65 .81 27.0 7.9 1.76 .48 .66 .84 25.2 7.4 2.03 .50 .69 .87

Page 50: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 2 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 50

XC21−024 with − CBX32M−042 − FIRST STAGE COOLINGCAPACITY −

[CBX32M−042][CB30M−46]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F460 215 19.1 5.6 .77 .72 .84 .96 18.2 5.3 .93 .73 .85 .98 17.2 5.0 1.10 .74 .88 1.00 16.2 4.7 1.31 .76 .90 1.00

63�F(17�C)

560 265 20.2 5.9 .77 .75 .89 1.00 19.2 5.6 .92 .76 .91 1.00 18.2 5.3 1.10 .79 .94 1.00 17.1 5.0 1.30 .81 .97 1.00(17�C)

660 310 21.0 6.2 .77 .79 .94 1.00 20.0 5.9 .93 .81 .97 1.00 18.9 5.5 1.10 .83 .99 1.00 17.9 5.2 1.30 .85 1.00 1.00

67�F460 215 20.4 6.0 .77 .57 .69 .80 19.4 5.7 .92 .58 .70 .82 18.5 5.4 1.10 .59 .71 .83 17.4 5.1 1.30 .59 .73 .86

67�F(19�C)

560 265 21.4 6.3 .78 .59 .73 .85 20.6 6.0 .93 .60 .74 .87 19.5 5.7 1.10 .61 .76 .90 18.3 5.4 1.30 .62 .78 .93(19�C)

660 310 22.4 6.6 .78 .62 .76 .91 21.4 6.3 .93 .63 .78 .93 20.2 5.9 1.10 .64 .80 .96 19.0 5.6 1.30 .65 .82 .98

71�F460 215 21.6 6.3 .77 .44 .55 .66 20.6 6.0 .93 .45 .56 .67 19.6 5.7 1.10 .45 .57 .68 18.6 5.5 1.30 .45 .58 .70

71�F(22�C)

560 265 22.8 6.7 .78 .45 .58 .70 21.8 6.4 .93 .45 .59 .71 20.6 6.0 1.10 .46 .60 .73 19.5 5.7 1.30 .46 .61 .75(22�C)

660 310 23.8 7.0 .78 .46 .60 .73 22.6 6.6 .93 .47 .61 .75 21.6 6.3 1.10 .47 .62 .77 20.2 5.9 1.30 .48 .64 .80

XC21−024 with − CBX32M−042 − SECOND STAGE COOLINGCAPACITY −

[CBX32M−042][CB30M−46]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 24.2 7.1 1.29 .72 .85 .97 23.0 6.7 1.50 .73 .86 .99 21.6 6.3 1.74 .75 .89 1.00 20.4 6.0 2.01 .77 .92 1.00

63�F(17�C)

800 380 25.8 7.6 1.29 .78 .93 1.00 24.6 7.2 1.50 .80 .96 1.00 23.2 6.8 1.75 .82 .98 1.00 21.8 6.4 2.01 .85 1.00 1.00(17�C)

1000 470 27.0 7.9 1.30 .84 1.00 1.00 25.8 7.6 1.51 .86 1.00 1.00 24.4 7.2 1.75 .89 1.00 1.00 23.2 6.8 2.02 .92 1.00 1.00

67�F600 285 25.6 7.5 1.29 .58 .69 .81 24.4 7.2 1.50 .58 .71 .83 23.0 6.7 1.74 .59 .72 .85 21.6 6.3 2.02 .60 .74 .88

67�F(19�C)

800 380 27.4 8.0 1.30 .61 .76 .90 26.0 7.6 1.51 .62 .77 .92 24.4 7.2 1.75 .64 .80 .95 23.0 6.7 2.01 .65 .82 .98(19�C)

1000 470 28.4 8.3 1.30 .65 .81 .97 27.0 7.9 1.51 .66 .84 .99 25.4 7.4 1.75 .68 .86 1.00 23.8 7.0 2.02 .70 .90 1.00

71�F600 285 27.0 7.9 1.29 .45 .56 .67 25.6 7.5 1.51 .45 .57 .68 24.4 7.2 1.74 .45 .57 .70 23.0 6.7 2.02 .45 .59 .72

71�F(22�C)

800 380 28.8 8.4 1.30 .46 .60 .73 27.4 8.0 1.51 .46 .61 .75 26.0 7.6 1.76 .47 .62 .77 24.4 7.2 2.02 .48 .64 .80(22�C)

1000 470 30.0 8.8 1.31 .48 .64 .79 28.6 8.4 1.52 .48 .65 .81 27.0 7.9 1.76 .48 .66 .84 25.2 7.4 2.03 .50 .69 .87

FIRST STAGE COOLING CAPACITY − XC21−024 with [CBX32MV−018/024]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F495 235 19.1 5.6 .77 .72 .85 .97 18.3 5.4 .92 .74 .87 .99 17.4 5.1 1.10 .75 .89 1.00 16.3 4.8 1.31 .77 .92 1.00

63�F(17�C)

595 280 20.0 5.9 .77 .76 .90 1.00 19.2 5.6 .93 .78 .92 1.00 18.2 5.3 1.10 .80 .95 1.00 17.1 5.0 1.30 .82 .98 1.00(17�C)

695 330 20.8 6.1 .77 .80 .95 1.00 19.9 5.8 .93 .81 .97 1.00 18.9 5.5 1.10 .83 .99 1.00 17.9 5.2 1.30 .86 1.00 1.00

67�F495 235 20.4 6.0 .77 .58 .70 .81 19.5 5.7 .93 .58 .71 .83 18.6 5.5 1.10 .59 .72 .85 17.5 5.1 1.30 .60 .74 .88

67�F(19�C)

595 280 21.4 6.3 .78 .60 .74 .87 20.4 6.0 .93 .61 .75 .89 19.4 5.7 1.10 .62 .77 .91 18.3 5.4 1.30 .63 .79 .94(19�C)

695 330 22.2 6.5 .78 .62 .77 .91 21.2 6.2 .93 .63 .79 .94 20.0 5.9 1.10 .64 .81 .96 18.9 5.5 1.30 .65 .83 .99

71�F495 235 21.6 6.3 .78 .45 .56 .67 20.8 6.1 .93 .45 .56 .68 19.8 5.8 1.10 .45 .57 .69 18.7 5.5 1.30 .45 .59 .72

71�F(22�C)

595 280 22.8 6.7 .78 .45 .58 .71 21.8 6.4 .93 .46 .59 .72 20.6 6.0 1.10 .46 .60 .74 19.5 5.7 1.30 .47 .62 .76(22�C)

695 330 23.6 6.9 .78 .46 .61 .75 22.6 6.6 .93 .47 .62 .76 21.4 6.3 1.10 .47 .63 .78 20.2 5.9 1.30 .48 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−024 with [CBX32MV−018/024]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F625 295 24.0 7.0 1.29 .72 .85 .97 22.8 6.7 1.50 .74 .87 .99 21.6 6.3 1.74 .75 .89 1.00 20.2 5.9 2.02 .77 .92 1.00

63�F(17�C)

825 390 25.4 7.4 1.29 .78 .93 1.00 24.2 7.1 1.50 .80 .95 1.00 23.0 6.7 1.74 .82 .98 1.00 21.6 6.3 2.01 .85 1.00 1.00(17�C)

1025 485 26.6 7.8 1.30 .84 .99 1.00 25.4 7.4 1.51 .85 1.00 1.00 24.0 7.0 1.75 .88 1.00 1.00 22.8 6.7 2.03 .92 1.00 1.00

67�F625 295 25.4 7.4 1.29 .58 .70 .81 24.2 7.1 1.50 .58 .71 .84 23.0 6.7 1.74 .59 .72 .86 21.6 6.3 2.01 .61 .75 .89

67�F(19�C)

825 390 27.0 7.9 1.30 .61 .76 .90 25.6 7.5 1.51 .62 .77 .92 24.2 7.1 1.75 .63 .79 .95 22.8 6.7 2.02 .65 .82 .98(19�C)

1025 485 28.0 8.2 1.30 .65 .81 .97 26.6 7.8 1.51 .66 .83 .99 25.0 7.3 1.75 .67 .86 1.00 23.4 6.9 2.03 .69 .89 1.00

71�F625 295 26.8 7.9 1.29 .44 .56 .67 25.6 7.5 1.51 .45 .57 .69 24.2 7.1 1.74 .45 .58 .70 22.8 6.7 2.02 .45 .59 .72

71�F(22�C)

825 390 28.4 8.3 1.30 .46 .60 .73 27.0 7.9 1.51 .47 .61 .75 25.6 7.5 1.75 .47 .62 .77 24.0 7.0 2.02 .48 .64 .80(22�C)

1025 485 29.6 8.7 1.31 .48 .64 .79 28.0 8.2 1.52 .48 .65 .81 26.6 7.8 1.75 .49 .66 .84 24.8 7.3 2.03 .49 .68 .87

Page 51: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 2 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 51

FIRST STAGE COOLING CAPACITY − XC21−024 with [CBX32MV−024/030]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F450 210 18.8 5.5 .77 .71 .83 .95 18.0 5.3 .92 .72 .85 .97 17.1 5.0 1.10 .74 .87 .99 16.1 4.7 1.30 .75 .90 1.00

63�F(17�C)

550 260 19.9 5.8 .77 .75 .89 1.00 19.0 5.6 .92 .76 .91 1.00 18.0 5.3 1.10 .78 .93 1.00 17.0 5.0 1.30 .80 .96 1.00(17�C)

650 305 20.8 6.1 .77 .79 .94 1.00 19.8 5.8 .92 .80 .96 1.00 18.8 5.5 1.10 .82 .98 1.00 17.7 5.2 1.30 .84 1.00 1.00

67�F450 210 20.0 5.9 .77 .57 .69 .80 19.2 5.6 .93 .58 .70 .81 18.3 5.4 1.10 .58 .71 .83 17.2 5.0 1.31 .59 .73 .85

67�F(19�C)

550 260 21.2 6.2 .78 .59 .72 .85 20.4 6.0 .93 .60 .74 .87 19.3 5.7 1.10 .61 .75 .89 18.2 5.3 1.30 .62 .77 .92(19�C)

650 305 22.2 6.5 .78 .62 .76 .90 21.2 6.2 .93 .62 .78 .92 20.0 5.9 1.10 .64 .80 .95 18.8 5.5 1.30 .65 .82 .98

71�F450 210 21.4 6.3 .77 .44 .55 .66 20.4 6.0 .93 .45 .56 .67 19.4 5.7 1.10 .45 .57 .68 18.4 5.4 1.30 .45 .58 .70

71�F(22�C)

550 260 22.6 6.6 .78 .45 .57 .69 21.6 6.3 .93 .45 .58 .71 20.6 6.0 1.10 .46 .59 .72 19.4 5.7 1.30 .46 .61 .75(22�C)

650 305 23.6 6.9 .78 .46 .60 .73 22.4 6.6 .93 .47 .61 .75 21.4 6.3 1.10 .47 .62 .77 20.0 5.9 1.30 .48 .63 .79

SECOND STAGE COOLING CAPACITY − XC21−024 with [CBX32MV−024/030]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F530 250 23.2 6.8 1.28 .70 .81 .93 22.2 6.5 1.50 .71 .83 .95 21.0 6.2 1.74 .72 .85 .97 19.7 5.8 2.01 .74 .87 1.00

63�F(17�C)

730 345 25.2 7.4 1.29 .76 .90 1.00 23.8 7.0 1.51 .77 .92 1.00 22.6 6.6 1.74 .79 .95 1.00 21.2 6.2 2.02 .82 .98 1.00(17�C)

930 440 26.4 7.7 1.29 .82 .98 1.00 25.2 7.4 1.50 .84 .99 1.00 23.8 7.0 1.75 .86 1.00 1.00 22.6 6.6 2.02 .89 1.00 1.00

67�F530 250 24.6 7.2 1.29 .57 .67 .78 23.4 6.9 1.50 .57 .68 .80 22.2 6.5 1.74 .58 .70 .82 21.0 6.2 2.01 .58 .71 .84

67�F(19�C)

730 345 26.6 7.8 1.29 .60 .73 .86 25.4 7.4 1.51 .61 .75 .89 24.0 7.0 1.75 .62 .77 .91 22.4 6.6 2.02 .63 .79 .95(19�C)

930 440 28.0 8.2 1.30 .63 .79 .95 26.6 7.8 1.51 .65 .81 .97 25.0 7.3 1.75 .66 .84 .99 23.4 6.9 2.02 .68 .87 1.00

71�F530 250 26.0 7.6 1.29 .44 .55 .65 24.8 7.3 1.50 .44 .55 .66 23.6 6.9 1.74 .44 .56 .67 22.2 6.5 2.01 .45 .57 .69

71�F(22�C)

730 345 28.0 8.2 1.30 .45 .58 .71 26.8 7.9 1.51 .46 .59 .72 25.4 7.4 1.75 .46 .60 .75 23.8 7.0 2.02 .47 .62 .77(22�C)

930 440 29.4 8.6 1.31 .47 .62 .77 28.0 8.2 1.52 .48 .63 .79 26.4 7.7 1.75 .48 .65 .81 24.8 7.3 2.03 .49 .67 .84

FIRST STAGE COOLING CAPACITY − XC21−024 with [CBX32MV−036][CB31MV−41

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F530 250 19.8 5.8 .77 .74 .88 1.00 18.9 5.5 .92 .76 .90 1.00 17.9 5.2 1.09 .77 .92 1.00 16.9 5.0 1.30 .79 .95 1.00

63�F(17�C)

630 295 20.6 6.0 .77 .78 .93 1.00 19.8 5.8 .93 .80 .95 1.00 18.8 5.5 1.10 .82 .98 1.00 17.7 5.2 1.30 .84 1.00 1.00(17�C)

730 345 21.4 6.3 .78 .82 .98 1.00 20.4 6.0 .93 .83 .99 1.00 19.5 5.7 1.10 .86 1.00 1.00 18.5 5.4 1.30 .89 1.00 1.00

67�F530 250 21.2 6.2 .78 .59 .71 .84 20.2 5.9 .93 .59 .73 .85 19.2 5.6 1.10 .60 .74 .88 18.1 5.3 1.30 .62 .76 .91

67�F(19�C)

630 295 22.0 6.4 .78 .61 .75 .89 21.2 6.2 .93 .62 .77 .91 20.0 5.9 1.10 .63 .79 .94 18.8 5.5 1.30 .64 .81 .97(19�C)

730 345 22.8 6.7 .78 .63 .79 .94 21.8 6.4 .93 .64 .81 .96 20.6 6.0 1.10 .66 .83 .99 19.4 5.7 1.30 .67 .86 1.00

71�F530 250 22.4 6.6 .78 .45 .57 .69 21.4 6.3 .93 .45 .58 .70 20.4 6.0 1.10 .45 .59 .72 19.3 5.7 1.30 .46 .60 .73

71�F(22�C)

630 295 23.4 6.9 .78 .46 .59 .72 22.4 6.6 .93 .46 .60 .74 21.2 6.2 1.10 .47 .62 .76 20.0 5.9 1.30 .47 .63 .78(22�C)

730 345 24.2 7.1 .79 .47 .62 .76 23.2 6.8 .94 .47 .63 .78 22.0 6.4 1.10 .48 .64 .80 20.6 6.0 1.30 .48 .66 .83

SECOND STAGE COOLING CAPACITY − XC21−024 with [CBX32MV−036][CB31MV−41

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F700 330 25.0 7.3 1.29 .75 .89 1.00 23.8 7.0 1.50 .76 .91 1.00 22.4 6.6 1.74 .78 .94 1.00 21.0 6.2 2.02 .81 .97 1.00

63�F(17�C)

900 425 26.4 7.7 1.29 .81 .97 1.00 25.2 7.4 1.51 .83 .99 1.00 23.8 7.0 1.75 .85 1.00 1.00 22.4 6.6 2.02 .88 1.00 1.00(17�C)

1100 520 27.6 8.1 1.29 .87 1.00 1.00 26.4 7.7 1.51 .89 1.00 1.00 25.0 7.3 1.75 .92 1.00 1.00 23.6 6.9 2.02 .96 1.00 1.00

67�F700 330 26.6 7.8 1.29 .59 .72 .85 25.2 7.4 1.51 .60 .74 .87 23.8 7.0 1.75 .61 .76 .90 22.4 6.6 2.02 .63 .78 .93

67�F(19�C)

900 425 28.0 8.2 1.30 .63 .79 .94 26.6 7.8 1.51 .64 .81 .96 25.0 7.3 1.75 .65 .83 .99 23.4 6.9 2.02 .67 .86 1.00(19�C)

1100 520 28.8 8.4 1.30 .66 .84 1.00 27.4 8.0 1.51 .68 .87 1.00 25.8 7.6 1.75 .70 .90 1.00 24.2 7.1 2.02 .72 .93 1.00

71�F700 330 28.0 8.2 1.30 .45 .58 .70 26.6 7.8 1.52 .46 .59 .72 25.2 7.4 1.75 .46 .60 .74 23.8 7.0 2.02 .46 .61 .76

71�F(22�C)

900 425 29.4 8.6 1.31 .47 .62 .76 28.0 8.2 1.52 .47 .63 .78 26.4 7.7 1.76 .48 .64 .81 24.8 7.3 2.03 .48 .66 .84(22�C)

1100 520 30.4 8.9 1.31 .48 .65 .82 29.0 8.5 1.52 .49 .66 .85 27.4 8.0 1.76 .50 .69 .88 25.6 7.5 2.03 .50 .71 .91

Page 52: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 3 TON

UP−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 52

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−36A/B/B−6F] [C33−36A/B/C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 26.6 7.8 1.10 .76 .90 1.00 25.4 7.4 1.29 .78 .92 1.00 24.2 7.1 1.50 .79 .94 1.00 22.8 6.7 1.74 .81 .97 1.00

63�F(17�C)

900 425 27.2 8.0 1.11 .79 .93 1.00 26.2 7.7 1.29 .80 .96 1.00 25.0 7.3 1.50 .82 .98 1.00 23.6 6.9 1.75 .84 1.00 1.00(17�C)

1000 470 28.0 8.2 1.11 .81 .96 1.00 26.8 7.9 1.30 .83 .98 1.00 25.6 7.5 1.51 .85 1.00 1.00 24.2 7.1 1.75 .87 1.00 1.00

67�F800 380 28.0 8.2 1.11 .60 .74 .86 26.8 7.9 1.30 .61 .75 .88 25.6 7.5 1.51 .62 .77 .91 24.2 7.1 1.75 .63 .79 .94

67�F(19�C)

900 425 28.8 8.4 1.12 .62 .76 .90 27.6 8.1 1.30 .63 .78 .92 26.2 7.7 1.51 .64 .79 .94 24.8 7.3 1.75 .65 .82 .97(19�C)

1000 470 29.4 8.6 1.12 .63 .78 .93 28.2 8.3 1.30 .64 .80 .95 26.8 7.9 1.51 .65 .82 .98 25.2 7.4 1.76 .67 .85 1.00

71�F800 380 29.4 8.6 1.12 .46 .59 .71 28.2 8.3 1.30 .46 .60 .73 26.8 7.9 1.51 .47 .61 .74 25.4 7.4 1.76 .47 .62 .76

71�F(22�C)

900 425 30.2 8.9 1.13 .47 .60 .73 29.0 8.5 1.31 .47 .61 .75 27.6 8.1 1.52 .47 .62 .77 26.2 7.7 1.76 .48 .64 .79(22�C)

1000 470 31.0 9.1 1.13 .47 .62 .76 29.6 8.7 1.31 .48 .63 .78 28.2 8.3 1.52 .48 .64 .80 26.8 7.9 1.76 .49 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−36A/B/B−6F] [C33−36A/B/C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 35.2 10.3 2.06 .74 .87 .99 33.4 9.8 2.32 .75 .89 1.00 31.6 9.3 2.61 .77 .91 1.00 29.8 8.7 2.93 .79 .94 1.00

63�F(17�C)

1200 565 36.4 10.7 2.07 .77 .92 1.00 34.8 10.2 2.33 .79 .94 1.00 33.0 9.7 2.62 .81 .97 1.00 31.0 9.1 2.94 .83 .99 1.00(17�C)

1400 660 37.6 11.0 2.08 .80 .96 1.00 35.8 10.5 2.34 .82 .98 1.00 34.0 10.0 2.62 .85 1.00 1.00 32.0 9.4 2.95 .87 1.00 1.00

67�F1000 470 37.0 10.8 2.08 .59 .71 .83 35.2 10.3 2.33 .60 .73 .85 33.4 9.8 2.62 .61 .75 .88 31.4 9.2 2.94 .62 .77 .91

67�F(19�C)

1200 565 38.5 11.3 2.09 .61 .75 .88 36.6 10.7 2.34 .62 .77 .91 34.6 10.1 2.63 .63 .78 .93 32.6 9.6 2.95 .65 .81 .96(19�C)

1400 660 39.5 11.6 2.10 .63 .78 .93 37.6 11.0 2.35 .64 .80 .95 35.6 10.4 2.64 .65 .82 .98 33.4 9.8 2.96 .67 .85 1.00

71�F1000 470 38.5 11.3 2.09 .46 .58 .69 36.8 10.8 2.35 .46 .59 .70 35.0 10.3 2.63 .46 .59 .72 32.8 9.6 2.95 .47 .61 .74

71�F(22�C)

1200 565 40.5 11.9 2.10 .46 .60 .73 38.5 11.3 2.36 .47 .61 .74 36.2 10.6 2.64 .47 .62 .76 34.2 10.0 2.97 .48 .63 .78(22�C)

1400 660 41.5 12.2 2.11 .47 .62 .76 39.5 11.6 2.37 .48 .63 .78 37.4 11.0 2.65 .48 .64 .80 35.2 10.3 2.98 .49 .66 .83

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−38B−6F] [C33−38A/B]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 27.4 8.0 1.11 .76 .90 1.00 26.2 7.7 1.29 .77 .92 1.00 24.8 7.3 1.50 .79 .94 1.00 23.4 6.9 1.75 .81 .97 1.00

63�F(17�C)

900 425 28.2 8.3 1.11 .78 .93 1.00 27.0 7.9 1.30 .80 .96 1.00 25.6 7.5 1.51 .82 .98 1.00 24.0 7.0 1.75 .84 1.00 1.00(17�C)

1000 470 28.8 8.4 1.12 .81 .97 1.00 27.6 8.1 1.30 .82 .99 1.00 26.2 7.7 1.51 .84 1.00 1.00 24.8 7.3 1.75 .87 1.00 1.00

67�F800 380 29.2 8.6 1.12 .60 .73 .86 28.0 8.2 1.30 .61 .75 .88 26.4 7.7 1.51 .62 .76 .90 25.0 7.3 1.75 .63 .78 .93

67�F(19�C)

900 425 30.0 8.8 1.12 .62 .76 .90 28.6 8.4 1.31 .62 .77 .92 27.2 8.0 1.51 .63 .79 .94 25.6 7.5 1.76 .65 .81 .97(19�C)

1000 470 30.6 9.0 1.13 .63 .78 .93 29.2 8.6 1.31 .64 .80 .95 27.6 8.1 1.52 .65 .82 .98 26.0 7.6 1.76 .67 .85 1.00

71�F800 380 30.8 9.0 1.13 .46 .58 .71 29.6 8.7 1.31 .46 .59 .72 28.2 8.3 1.52 .46 .60 .74 26.6 7.8 1.76 .47 .61 .76

71�F(22�C)

900 425 31.8 9.3 1.14 .46 .60 .73 30.4 8.9 1.32 .47 .61 .75 28.8 8.4 1.52 .47 .62 .77 27.2 8.0 1.76 .48 .63 .79(22�C)

1000 470 32.4 9.5 1.14 .47 .62 .75 31.0 9.1 1.32 .47 .63 .78 29.4 8.6 1.53 .48 .64 .79 27.8 8.1 1.76 .48 .65 .82

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−38B−6F] [C33−38A/B]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 36.4 10.7 2.07 .74 .87 .99 34.6 10.1 2.33 .75 .88 1.00 32.8 9.6 2.61 .77 .91 1.00 30.8 9.0 2.93 .79 .94 1.00

63�F(17�C)

1200 565 38.0 11.1 2.09 .77 .92 1.00 36.0 10.6 2.34 .79 .94 1.00 34.0 10.0 2.62 .81 .97 1.00 32.0 9.4 2.94 .83 1.00 1.00(17�C)

1400 660 39.0 11.4 2.09 .80 .96 1.00 37.2 10.9 2.35 .82 .99 1.00 35.0 10.3 2.63 .85 1.00 1.00 33.2 9.7 2.96 .88 1.00 1.00

67�F1000 470 38.5 11.3 2.09 .59 .71 .83 36.8 10.8 2.34 .59 .72 .85 34.8 10.2 2.63 .60 .74 .87 32.6 9.6 2.95 .61 .76 .90

67�F(19�C)

1200 565 40.0 11.7 2.10 .60 .75 .88 38.0 11.1 2.36 .62 .76 .90 36.0 10.6 2.64 .63 .78 .93 33.8 9.9 2.96 .64 .81 .97(19�C)

1400 660 41.5 12.2 2.11 .63 .78 .93 39.0 11.4 2.36 .64 .80 .96 37.0 10.8 2.65 .65 .83 .98 34.6 10.1 2.97 .67 .85 1.00

71�F1000 470 40.5 11.9 2.11 .45 .57 .69 38.5 11.3 2.36 .45 .58 .70 36.8 10.8 2.65 .46 .59 .71 34.6 10.1 2.97 .46 .60 .74

71�F(22�C)

1200 565 42.5 12.5 2.12 .46 .59 .72 40.5 11.9 2.37 .46 .60 .74 38.0 11.1 2.66 .47 .62 .76 35.8 10.5 2.98 .47 .63 .78(22�C)

1400 660 43.5 12.7 2.13 .47 .62 .76 41.5 12.2 2.38 .48 .63 .78 39.0 11.4 2.67 .48 .64 .79 36.6 10.7 2.99 .49 .66 .83

Page 53: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 3 TON

UP−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 53

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−42B−6F] [C33−42A/B]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 26.6 7.8 1.10 .76 .90 1.00 25.4 7.4 1.29 .78 .92 1.00 24.2 7.1 1.50 .79 .94 1.00 22.8 6.7 1.74 .81 .97 1.00

63�F(17�C)

900 425 27.2 8.0 1.11 .79 .93 1.00 26.2 7.7 1.29 .80 .96 1.00 25.0 7.3 1.50 .82 .98 1.00 23.6 6.9 1.75 .84 1.00 1.00(17�C)

1000 470 28.0 8.2 1.11 .81 .96 1.00 26.8 7.9 1.30 .83 .98 1.00 25.6 7.5 1.51 .85 1.00 1.00 24.2 7.1 1.75 .87 1.00 1.00

67�F800 380 28.0 8.2 1.11 .60 .74 .86 26.8 7.9 1.30 .61 .75 .88 25.6 7.5 1.51 .62 .77 .91 24.2 7.1 1.75 .63 .79 .94

67�F(19�C)

900 425 28.8 8.4 1.12 .62 .76 .90 27.6 8.1 1.30 .63 .78 .92 26.2 7.7 1.51 .64 .79 .94 24.8 7.3 1.75 .65 .82 .97(19�C)

1000 470 29.4 8.6 1.12 .63 .78 .93 28.2 8.3 1.30 .64 .80 .95 26.8 7.9 1.51 .65 .82 .98 25.2 7.4 1.76 .67 .85 1.00

71�F800 380 29.4 8.6 1.12 .46 .59 .71 28.2 8.3 1.30 .46 .60 .73 26.8 7.9 1.51 .47 .61 .74 25.4 7.4 1.76 .47 .62 .76

71�F(22�C)

900 425 30.2 8.9 1.13 .47 .60 .73 29.0 8.5 1.31 .47 .61 .75 27.6 8.1 1.52 .47 .62 .77 26.2 7.7 1.76 .48 .64 .79(22�C)

1000 470 31.0 9.1 1.13 .47 .62 .76 29.6 8.7 1.31 .48 .63 .78 28.2 8.3 1.52 .48 .64 .80 26.8 7.9 1.76 .49 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−42B−6F] [C33−42A/B]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 35.2 10.3 2.06 .74 .87 .99 33.4 9.8 2.32 .75 .89 1.00 31.6 9.3 2.61 .77 .91 1.00 29.8 8.7 2.93 .79 .94 1.00

63�F(17�C)

1200 565 36.4 10.7 2.07 .77 .92 1.00 34.8 10.2 2.33 .79 .94 1.00 33.0 9.7 2.62 .81 .97 1.00 31.0 9.1 2.94 .83 .99 1.00(17�C)

1400 660 37.6 11.0 2.08 .80 .96 1.00 35.8 10.5 2.34 .82 .98 1.00 34.0 10.0 2.62 .85 1.00 1.00 32.0 9.4 2.95 .87 1.00 1.00

67�F1000 470 37.0 10.8 2.08 .59 .71 .83 35.2 10.3 2.33 .60 .73 .85 33.4 9.8 2.62 .61 .75 .88 31.4 9.2 2.94 .62 .77 .91

67�F(19�C)

1200 565 38.5 11.3 2.09 .61 .75 .88 36.6 10.7 2.34 .62 .77 .91 34.6 10.1 2.63 .63 .78 .93 32.6 9.6 2.95 .65 .81 .96(19�C)

1400 660 39.5 11.6 2.10 .63 .78 .93 37.6 11.0 2.35 .64 .80 .95 35.6 10.4 2.64 .65 .82 .98 33.4 9.8 2.96 .67 .85 1.00

71�F1000 470 38.5 11.3 2.09 .46 .58 .69 36.8 10.8 2.35 .46 .59 .70 35.0 10.3 2.63 .46 .59 .72 32.8 9.6 2.95 .47 .61 .74

71�F(22�C)

1200 565 40.5 11.9 2.10 .46 .60 .73 38.5 11.3 2.36 .47 .61 .74 36.2 10.6 2.64 .47 .62 .76 34.2 10.0 2.97 .48 .63 .78(22�C)

1400 660 41.5 12.2 2.11 .47 .62 .76 39.5 11.6 2.37 .48 .63 .78 37.4 11.0 2.65 .48 .64 .80 35.2 10.3 2.98 .49 .66 .83

FIRST STAGE COOLING CAPACITY − XC21−036 with [C33−44C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 27.0 7.9 1.11 .75 .89 1.00 25.8 7.6 1.29 .77 .91 1.00 24.6 7.2 1.50 .78 .93 1.00 23.2 6.8 1.75 .80 .96 1.00

63�F(17�C)

900 425 27.8 8.1 1.11 .78 .92 1.00 26.6 7.8 1.30 .79 .95 1.00 25.2 7.4 1.50 .81 .97 1.00 23.8 7.0 1.75 .83 1.00 1.00(17�C)

1000 470 28.4 8.3 1.12 .80 .96 1.00 27.2 8.0 1.30 .82 .98 1.00 25.8 7.6 1.51 .84 1.00 1.00 24.4 7.2 1.75 .86 1.00 1.00

67�F800 380 28.8 8.4 1.12 .59 .73 .85 27.6 8.1 1.30 .61 .74 .87 26.2 7.7 1.51 .61 .76 .89 24.8 7.3 1.75 .63 .78 .92

67�F(19�C)

900 425 29.6 8.7 1.12 .61 .75 .88 28.4 8.3 1.30 .62 .76 .91 26.8 7.9 1.51 .63 .78 .93 25.4 7.4 1.76 .64 .80 .96(19�C)

1000 470 30.2 8.9 1.13 .62 .77 .92 28.8 8.4 1.31 .63 .79 .94 27.4 8.0 1.51 .64 .81 .97 25.8 7.6 1.76 .65 .84 .99

71�F800 380 30.6 9.0 1.13 .45 .58 .70 29.2 8.6 1.31 .45 .59 .71 27.8 8.1 1.52 .46 .60 .73 26.4 7.7 1.76 .47 .61 .75

71�F(22�C)

900 425 31.4 9.2 1.13 .46 .60 .72 30.0 8.8 1.31 .47 .60 .74 28.6 8.4 1.52 .47 .61 .76 27.0 7.9 1.76 .47 .63 .78(22�C)

1000 470 32.2 9.4 1.14 .47 .61 .74 30.6 9.0 1.32 .47 .62 .76 29.2 8.6 1.52 .47 .63 .78 27.4 8.0 1.76 .48 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−036 with [C33−44C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 36.0 10.6 2.07 .73 .86 .97 34.2 10.0 2.32 .74 .87 1.00 32.4 9.5 2.61 .76 .90 1.00 30.4 8.9 2.93 .78 .93 1.00

63�F(17�C)

1200 565 37.4 11.0 2.08 .76 .90 1.00 35.6 10.4 2.34 .78 .93 1.00 33.6 9.8 2.62 .80 .95 1.00 31.6 9.3 2.94 .82 .98 1.00(17�C)

1400 660 38.5 11.3 2.09 .80 .95 1.00 36.8 10.8 2.34 .81 .97 1.00 34.6 10.1 2.63 .84 1.00 1.00 32.6 9.6 2.95 .86 1.00 1.00

67�F1000 470 38.0 11.1 2.09 .58 .70 .82 36.4 10.7 2.34 .59 .72 .84 34.4 10.1 2.63 .60 .73 .86 32.4 9.5 2.95 .61 .75 .89

67�F(19�C)

1200 565 39.5 11.6 2.10 .60 .73 .87 37.8 11.1 2.35 .61 .75 .89 35.6 10.4 2.64 .62 .77 .92 33.4 9.8 2.96 .64 .80 .95(19�C)

1400 660 41.0 12.0 2.11 .62 .77 .92 39.0 11.4 2.36 .63 .79 .94 36.6 10.7 2.64 .65 .81 .97 34.2 10.0 2.96 .66 .84 1.00

71�F1000 470 40.5 11.9 2.10 .45 .57 .68 38.5 11.3 2.36 .45 .57 .69 36.4 10.7 2.64 .46 .58 .71 34.2 10.0 2.96 .46 .60 .73

71�F(22�C)

1200 565 42.0 12.3 2.11 .46 .59 .71 40.0 11.7 2.37 .46 .59 .73 37.8 11.1 2.65 .47 .61 .75 35.4 10.4 2.98 .47 .62 .77(22�C)

1400 660 43.0 12.6 2.13 .47 .61 .75 41.0 12.0 2.38 .47 .62 .76 39.0 11.4 2.67 .48 .63 .79 36.2 10.6 2.98 .48 .65 .81

Page 54: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 3 TON

UP−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 54

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−44/48B/C−6F] [C33−48B/C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 27.0 7.9 1.11 .75 .89 1.00 25.8 7.6 1.29 .77 .91 1.00 24.6 7.2 1.50 .78 .93 1.00 23.2 6.8 1.75 .80 .96 1.00

63�F(17�C)

900 425 27.8 8.1 1.11 .77 .92 1.00 26.6 7.8 1.30 .79 .94 1.00 25.2 7.4 1.50 .81 .97 1.00 23.8 7.0 1.75 .83 .99 1.00(17�C)

1000 470 28.4 8.3 1.12 .80 .95 1.00 27.2 8.0 1.30 .81 .97 1.00 25.8 7.6 1.51 .83 1.00 1.00 24.4 7.2 1.75 .86 1.00 1.00

67�F800 380 28.8 8.4 1.12 .59 .72 .85 27.6 8.1 1.30 .60 .74 .87 26.2 7.7 1.51 .61 .76 .89 24.6 7.2 1.75 .63 .78 .92

67�F(19�C)

900 425 29.6 8.7 1.12 .61 .75 .88 28.2 8.3 1.30 .62 .76 .90 26.8 7.9 1.51 .63 .78 .93 25.4 7.4 1.76 .64 .80 .96(19�C)

1000 470 30.2 8.9 1.13 .62 .77 .91 29.0 8.5 1.31 .63 .79 .94 27.4 8.0 1.51 .64 .81 .96 25.8 7.6 1.76 .65 .83 .99

71�F800 380 30.6 9.0 1.13 .46 .58 .69 29.2 8.6 1.31 .46 .59 .71 27.8 8.1 1.52 .46 .60 .73 26.4 7.7 1.76 .47 .61 .75

71�F(22�C)

900 425 31.4 9.2 1.13 .46 .59 .72 30.0 8.8 1.31 .47 .60 .74 28.6 8.4 1.52 .47 .61 .75 27.0 7.9 1.76 .47 .63 .78(22�C)

1000 470 32.0 9.4 1.14 .47 .61 .74 30.6 9.0 1.32 .47 .62 .76 29.2 8.6 1.52 .47 .63 .78 27.4 8.0 1.77 .48 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−44/48B/C−6F] [C33−48B/C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 36.0 10.6 2.07 .73 .85 .97 34.4 10.1 2.33 .74 .87 .99 32.4 9.5 2.61 .76 .90 1.00 30.4 8.9 2.93 .78 .92 1.00

63�F(17�C)

1200 565 37.6 11.0 2.08 .75 .90 1.00 35.8 10.5 2.34 .77 .92 1.00 33.8 9.9 2.62 .79 .95 1.00 31.6 9.3 2.94 .82 .98 1.00(17�C)

1400 660 38.5 11.3 2.09 .79 .94 1.00 36.8 10.8 2.35 .81 .97 1.00 34.8 10.2 2.63 .83 .99 1.00 32.6 9.6 2.95 .86 1.00 1.00

67�F1000 470 38.0 11.1 2.09 .58 .70 .82 36.4 10.7 2.34 .59 .72 .84 34.4 10.1 2.63 .60 .73 .86 32.4 9.5 2.95 .61 .75 .89

67�F(19�C)

1200 565 39.5 11.6 2.10 .60 .73 .86 37.8 11.1 2.35 .61 .75 .89 35.8 10.5 2.64 .62 .77 .91 33.4 9.8 2.96 .64 .79 .94(19�C)

1400 660 41.0 12.0 2.11 .62 .76 .91 39.0 11.4 2.36 .63 .79 .93 36.8 10.8 2.65 .64 .81 .96 34.4 10.1 2.96 .66 .83 .99

71�F1000 470 40.5 11.9 2.10 .45 .57 .68 38.5 11.3 2.36 .46 .57 .69 36.4 10.7 2.64 .45 .58 .70 34.2 10.0 2.97 .46 .60 .73

71�F(22�C)

1200 565 42.0 12.3 2.12 .46 .58 .71 40.0 11.7 2.37 .46 .59 .73 37.8 11.1 2.65 .47 .61 .75 35.4 10.4 2.98 .47 .62 .77(22�C)

1400 660 43.0 12.6 2.13 .46 .61 .74 41.0 12.0 2.38 .47 .62 .76 39.0 11.4 2.66 .48 .63 .78 36.4 10.7 2.99 .48 .64 .81

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−49C−6F] [C33−49C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT t

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTemperat

ure

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbure

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 27.2 8.0 1.11 .75 .89 1.00 26.0 7.6 1.30 .76 .91 1.00 24.8 7.3 1.51 .78 .93 1.00 23.4 6.9 1.76 .80 .96 1.00

63�F(17�C)

900 425 28.0 8.2 1.12 .77 .92 1.00 26.8 7.9 1.30 .79 .94 1.00 25.4 7.4 1.52 .81 .97 1.00 24.0 7.0 1.76 .83 1.00 1.00(17�C)

1000 470 28.8 8.4 1.12 .80 .95 1.00 27.6 8.1 1.31 .81 .98 1.00 26.2 7.7 1.52 .84 1.00 1.00 24.8 7.3 1.76 .86 1.00 1.00

67�F800 380 28.8 8.4 1.12 .60 .73 .85 27.6 8.1 1.31 .60 .74 .87 26.4 7.7 1.52 .61 .76 .89 24.8 7.3 1.77 .63 .78 .92

67�F(19�C)

900 425 29.8 8.7 1.13 .61 .75 .88 28.4 8.3 1.31 .62 .76 .90 27.2 8.0 1.52 .63 .78 .93 25.6 7.5 1.77 .64 .80 .96(19�C)

1000 470 30.4 8.9 1.13 .62 .77 .91 29.2 8.6 1.32 .63 .79 .94 27.6 8.1 1.52 .65 .81 .97 26.2 7.7 1.77 .66 .83 .99

71�F800 380 30.6 9.0 1.13 .46 .58 .70 29.2 8.6 1.31 .46 .59 .71 27.8 8.1 1.53 .46 .60 .73 26.4 7.7 1.77 .47 .61 .75

71�F(22�C)

900 425 31.4 9.2 1.14 .46 .59 .72 30.2 8.9 1.32 .47 .60 .74 28.6 8.4 1.53 .47 .62 .76 27.0 7.9 1.77 .48 .63 .78(22�C)

1000 470 32.2 9.4 1.14 .47 .61 .75 30.8 9.0 1.32 .47 .62 .76 29.4 8.6 1.53 .48 .63 .78 27.6 8.1 1.77 .47 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−49C−6F] [C33−49C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 36.4 10.7 2.07 .73 .85 .97 34.6 10.1 2.33 .74 .87 1.00 32.8 9.6 2.61 .76 .90 1.00 30.8 9.0 2.94 .78 .93 1.00

63�F(17�C)

1200 565 38.0 11.1 2.08 .76 .90 1.00 36.2 10.6 2.34 .78 .92 1.00 34.2 10.0 2.62 .80 .95 1.00 32.0 9.4 2.95 .82 .98 1.00(17�C)

1400 660 39.5 11.6 2.10 .79 .95 1.00 37.2 10.9 2.35 .81 .97 1.00 35.2 10.3 2.63 .83 1.00 1.00 33.2 9.7 2.96 .86 1.00 1.00

67�F1000 470 38.5 11.3 2.09 .58 .70 .82 36.6 10.7 2.34 .59 .72 .84 34.8 10.2 2.63 .60 .73 .86 32.6 9.6 2.95 .61 .75 .89

67�F(19�C)

1200 565 40.0 11.7 2.10 .60 .74 .87 38.0 11.1 2.36 .61 .75 .89 36.2 10.6 2.64 .62 .77 .92 33.8 9.9 2.97 .64 .80 .95(19�C)

1400 660 41.5 12.2 2.11 .62 .77 .91 39.5 11.6 2.37 .63 .79 .94 37.2 10.9 2.65 .65 .81 .97 34.8 10.2 2.97 .66 .84 1.00

71�F1000 470 40.5 11.9 2.10 .45 .57 .68 38.5 11.3 2.36 .45 .58 .69 36.6 10.7 2.65 .46 .58 .71 34.4 10.1 2.97 .46 .60 .73

71�F(22�C)

1200 565 42.0 12.3 2.12 .46 .59 .71 40.0 11.7 2.37 .46 .60 .73 38.0 11.1 2.66 .47 .61 .75 35.6 10.4 2.98 .47 .63 .77(22�C)

1400 660 43.5 12.7 2.13 .47 .61 .75 41.5 12.2 2.38 .47 .62 .77 39.0 11.4 2.67 .48 .64 .79 36.8 10.8 2.99 .47 .65 .81

Page 55: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 3 TON

UP−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 55

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−50/60C−6F] [C33−50/60C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 27.4 8.0 1.12 .75 .89 1.00 26.2 7.7 1.31 .77 .91 1.00 24.8 7.3 1.53 .78 .94 1.00 23.4 6.9 1.78 .81 .96 1.00

63�F(17�C)

900 425 28.2 8.3 1.13 .78 .92 1.00 27.0 7.9 1.31 .79 .95 1.00 25.6 7.5 1.53 .81 .97 1.00 24.0 7.0 1.78 .83 1.00 1.00(17�C)

1000 470 28.8 8.4 1.13 .80 .96 1.00 27.6 8.1 1.32 .82 .98 1.00 26.2 7.7 1.53 .84 1.00 1.00 24.8 7.3 1.79 .87 1.00 1.00

67�F800 380 29.2 8.6 1.13 .59 .73 .85 27.8 8.1 1.32 .61 .74 .87 26.4 7.7 1.53 .62 .76 .90 25.0 7.3 1.78 .63 .78 .93

67�F(19�C)

900 425 29.8 8.7 1.13 .61 .75 .88 28.6 8.4 1.32 .62 .76 .91 27.2 8.0 1.53 .63 .79 .93 25.6 7.5 1.78 .64 .81 .96(19�C)

1000 470 30.6 9.0 1.14 .63 .77 .92 29.2 8.6 1.32 .63 .79 .94 27.8 8.1 1.54 .64 .81 .97 26.2 7.7 1.79 .65 .84 1.00

71�F800 380 31.0 9.1 1.14 .45 .58 .70 29.6 8.7 1.32 .46 .59 .71 28.2 8.3 1.54 .46 .60 .73 26.6 7.8 1.78 .47 .61 .75

71�F(22�C)

900 425 31.8 9.3 1.14 .46 .59 .73 30.4 8.9 1.33 .46 .61 .74 29.0 8.5 1.54 .47 .62 .76 27.2 8.0 1.79 .47 .62 .78(22�C)

1000 470 32.6 9.6 1.15 .47 .61 .75 31.0 9.1 1.33 .47 .62 .76 29.6 8.7 1.54 .48 .63 .78 27.8 8.1 1.79 .48 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−50/60C−6F] [C33−50/60C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 36.4 10.7 2.07 .73 .86 .98 34.6 10.1 2.33 .74 .87 1.00 32.8 9.6 2.62 .76 .90 1.00 30.8 9.0 2.94 .78 .93 1.00

63�F(17�C)

1200 565 38.0 11.1 2.08 .76 .91 1.00 36.0 10.6 2.34 .78 .93 1.00 34.2 10.0 2.63 .80 .96 1.00 32.0 9.4 2.94 .82 .99 1.00(17�C)

1400 660 39.0 11.4 2.09 .80 .95 1.00 37.2 10.9 2.35 .82 .98 1.00 35.0 10.3 2.63 .84 1.00 1.00 33.2 9.7 2.96 .87 1.00 1.00

67�F1000 470 38.5 11.3 2.09 .58 .71 .82 36.8 10.8 2.34 .59 .72 .84 34.8 10.2 2.63 .60 .73 .87 32.6 9.6 2.95 .61 .76 .89

67�F(19�C)

1200 565 40.0 11.7 2.10 .60 .74 .87 38.0 11.1 2.35 .62 .76 .89 36.0 10.6 2.64 .63 .77 .92 33.8 9.9 2.96 .64 .80 .95(19�C)

1400 660 41.5 12.2 2.11 .62 .77 .92 39.5 11.6 2.36 .63 .79 .94 37.0 10.8 2.65 .65 .81 .97 34.6 10.1 2.97 .66 .84 1.00

71�F1000 470 41.0 12.0 2.11 .45 .57 .68 39.0 11.4 2.36 .45 .57 .70 36.8 10.8 2.65 .45 .58 .70 34.6 10.1 2.97 .46 .60 .73

71�F(22�C)

1200 565 42.5 12.5 2.12 .46 .59 .71 40.5 11.9 2.37 .46 .60 .73 38.0 11.1 2.66 .47 .61 .75 35.8 10.5 2.98 .47 .63 .77(22�C)

1400 660 43.5 12.7 2.13 .47 .61 .75 41.5 12.2 2.38 .47 .62 .77 39.0 11.4 2.67 .48 .63 .79 36.8 10.8 2.99 .48 .65 .82

Page 56: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 3 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 56

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−36A−6F + G60UHV−36A−070][C33−36A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F670 315 25.4 7.4 1.11 .74 .86 .97 24.4 7.2 1.29 .75 .88 .99 23.2 6.8 1.51 .76 .90 1.00 22.0 6.4 1.76 .78 .92 1.00

63�F(17�C)

850 400 27.2 8.0 1.11 .78 .92 1.00 26.0 7.6 1.30 .80 .94 1.00 24.8 7.3 1.51 .81 .97 1.00 23.4 6.9 1.76 .84 .99 1.00(17�C)

910 430 27.6 8.1 1.12 .80 .94 1.00 26.4 7.7 1.30 .81 .96 1.00 25.2 7.4 1.52 .83 .99 1.00 23.8 7.0 1.76 .86 1.00 1.00

67�F670 315 26.8 7.9 1.11 .59 .71 .82 25.8 7.6 1.30 .60 .72 .84 24.6 7.2 1.51 .61 .74 .86 23.2 6.8 1.76 .62 .75 .88

67�F(19�C)

850 400 28.6 8.4 1.12 .62 .75 .89 27.4 8.0 1.31 .63 .77 .91 26.0 7.6 1.52 .64 .79 .93 24.6 7.2 1.77 .65 .81 .96(19�C)

910 430 29.2 8.6 1.12 .63 .77 .91 27.8 8.1 1.31 .64 .79 .93 26.4 7.7 1.52 .65 .80 .95 25.0 7.3 1.77 .66 .83 .98

71�F670 315 28.0 8.2 1.12 .46 .57 .68 27.0 7.9 1.30 .46 .58 .70 25.8 7.6 1.52 .46 .59 .71 24.4 7.2 1.77 .47 .60 .73

71�F(22�C)

850 400 30.0 8.8 1.13 .47 .60 .73 28.8 8.4 1.31 .48 .61 .74 27.4 8.0 1.52 .48 .62 .76 26.0 7.6 1.77 .49 .64 .78(22�C)

910 430 30.6 9.0 1.13 .48 .61 .74 29.2 8.6 1.32 .48 .62 .76 27.8 8.1 1.53 .49 .63 .78 26.4 7.7 1.77 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−36A−6F + G60UHV−36A−070][C33−36A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1035 490 35.6 10.4 2.07 .75 .88 1.00 34.0 10.0 2.32 .77 .91 1.00 32.0 9.4 2.61 .79 .93 1.00 30.2 8.9 2.93 .81 .96 1.00

63�F(17�C)

1230 580 37.0 10.8 2.08 .79 .93 1.00 35.2 10.3 2.33 .81 .96 1.00 33.4 9.8 2.61 .83 .98 1.00 31.4 9.2 2.94 .85 1.00 1.00(17�C)

1375 650 37.8 11.1 2.08 .82 .97 1.00 36.0 10.6 2.34 .84 .99 1.00 34.2 10.0 2.62 .86 1.00 1.00 32.2 9.4 2.95 .89 1.00 1.00

67�F1035 490 37.4 11.0 2.08 .61 .73 .85 35.6 10.4 2.33 .61 .75 .87 33.8 9.9 2.62 .63 .76 .90 31.8 9.3 2.95 .64 .78 .93

67�F(19�C)

1230 580 39.0 11.4 2.09 .63 .77 .90 37.0 10.8 2.35 .64 .78 .93 35.0 10.3 2.63 .65 .80 .95 32.8 9.6 2.96 .67 .83 .98(19�C)

1375 650 40.0 11.7 2.10 .65 .79 .94 37.8 11.1 2.35 .66 .81 .96 35.8 10.5 2.64 .67 .84 .99 33.6 9.8 2.96 .69 .86 1.00

71�F1035 490 39.0 11.4 2.09 .47 .59 .71 37.4 11.0 2.35 .47 .60 .72 35.4 10.4 2.63 .48 .61 .74 33.2 9.7 2.95 .48 .63 .76

71�F(22�C)

1230 580 40.5 11.9 2.11 .48 .61 .74 39.0 11.4 2.36 .49 .63 .76 36.8 10.8 2.65 .49 .64 .78 34.6 10.1 2.97 .50 .66 .81(22�C)

1375 650 41.5 12.2 2.11 .49 .63 .77 39.5 11.6 2.37 .50 .65 .79 37.6 11.0 2.66 .50 .66 .81 35.4 10.4 2.98 .51 .68 .84

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−36B−6F + G60UHV−36B−090][C33−36B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F740 350 26.2 7.7 1.11 .75 .88 1.00 25.0 7.3 1.30 .76 .90 1.00 23.8 7.0 1.51 .78 .93 1.00 22.6 6.6 1.76 .80 .95 1.00

63�F(17�C)

840 395 27.0 7.9 1.11 .78 .92 1.00 25.8 7.6 1.30 .79 .94 1.00 24.6 7.2 1.51 .81 .96 1.00 23.2 6.8 1.76 .83 .99 1.00(17�C)

920 435 27.6 8.1 1.11 .80 .95 1.00 26.4 7.7 1.30 .81 .97 1.00 25.2 7.4 1.52 .83 .99 1.00 23.8 7.0 1.76 .86 1.00 1.00

67�F740 350 27.6 8.1 1.11 .60 .73 .85 26.4 7.7 1.30 .61 .74 .87 25.2 7.4 1.51 .62 .76 .89 23.8 7.0 1.76 .63 .78 .92

67�F(19�C)

840 395 28.6 8.4 1.12 .61 .75 .88 27.4 8.0 1.31 .62 .77 .90 26.0 7.6 1.52 .63 .78 .93 24.6 7.2 1.77 .65 .81 .96(19�C)

920 435 29.2 8.6 1.12 .63 .77 .91 27.8 8.1 1.31 .64 .79 .93 26.6 7.8 1.52 .65 .81 .96 25.0 7.3 1.77 .66 .83 .98

71�F740 350 29.0 8.5 1.12 .46 .59 .70 27.8 8.1 1.31 .47 .59 .71 26.4 7.7 1.52 .47 .60 .73 25.0 7.3 1.77 .47 .61 .75

71�F(22�C)

840 395 30.0 8.8 1.13 .47 .60 .73 28.6 8.4 1.31 .47 .61 .74 27.4 8.0 1.52 .48 .62 .76 25.8 7.6 1.77 .48 .63 .78(22�C)

920 435 30.6 9.0 1.13 .48 .61 .75 29.4 8.6 1.32 .48 .62 .76 28.0 8.2 1.53 .48 .63 .78 26.4 7.7 1.77 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−36B−6F + G60UHV−36B−090][C33−36B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1035 490 35.6 10.4 2.07 .75 .88 1.00 33.8 9.9 2.32 .77 .90 1.00 32.0 9.4 2.61 .79 .93 1.00 30.0 8.8 2.93 .81 .96 1.00

63�F(17�C)

1225 580 36.8 10.8 2.07 .79 .93 1.00 35.2 10.3 2.33 .80 .96 1.00 33.2 9.7 2.62 .82 .98 1.00 31.4 9.2 2.94 .85 1.00 1.00(17�C)

1385 655 37.8 11.1 2.08 .81 .97 1.00 36.0 10.6 2.34 .83 .99 1.00 34.2 10.0 2.62 .86 1.00 1.00 32.2 9.4 2.95 .89 1.00 1.00

67�F1035 490 37.4 11.0 2.08 .60 .73 .85 35.6 10.4 2.33 .61 .74 .87 33.8 9.9 2.62 .62 .76 .90 31.8 9.3 2.95 .64 .78 .93

67�F(19�C)

1225 580 39.0 11.4 2.09 .62 .76 .90 37.0 10.8 2.35 .64 .78 .92 35.0 10.3 2.63 .65 .80 .95 32.8 9.6 2.96 .66 .83 .98(19�C)

1385 655 40.0 11.7 2.10 .64 .79 .94 37.8 11.1 2.35 .65 .81 .96 35.8 10.5 2.64 .67 .83 .98 33.6 9.8 2.96 .69 .86 1.00

71�F1035 490 39.0 11.4 2.09 .47 .59 .71 37.4 11.0 2.35 .47 .60 .72 35.4 10.4 2.63 .48 .61 .74 33.2 9.7 2.95 .48 .62 .76

71�F(22�C)

1225 580 40.5 11.9 2.11 .48 .61 .74 38.5 11.3 2.36 .48 .62 .76 36.8 10.8 2.65 .49 .63 .78 34.4 10.1 2.97 .50 .65 .80(22�C)

1385 655 41.5 12.2 2.11 .49 .63 .77 39.5 11.6 2.37 .49 .64 .79 37.6 11.0 2.66 .50 .66 .81 35.2 10.3 2.98 .51 .68 .84

Page 57: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 3 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 57

XC21−036 with − C33−36B � G61MPV−36B−070 − FIRSTSTAGE COOLING CAPACITY −

[CX34−36B−6F + G61MPV−36B−070][C33−36B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F695 330 25.8 7.6 1.11 .74 .87 .98 24.6 7.2 1.29 .75 .89 1.00 23.4 6.9 1.51 .77 .91 1.00 22.2 6.5 1.76 .79 .94 1.00

63�F(17�C)

815 385 26.8 7.9 1.11 .77 .91 1.00 25.6 7.5 1.30 .79 .93 1.00 24.4 7.2 1.51 .80 .96 1.00 23.2 6.8 1.76 .83 .98 1.00(17�C)

935 440 27.8 8.1 1.12 .80 .95 1.00 26.6 7.8 1.30 .82 .97 1.00 25.4 7.4 1.52 .84 .99 1.00 24.0 7.0 1.76 .86 1.00 1.00

67�F695 330 27.2 8.0 1.11 .60 .72 .83 26.0 7.6 1.30 .60 .73 .85 24.8 7.3 1.52 .61 .74 .87 23.4 6.9 1.76 .62 .76 .90

67�F(19�C)

815 385 28.4 8.3 1.12 .61 .75 .88 27.2 8.0 1.30 .62 .76 .89 25.8 7.6 1.52 .63 .78 .92 24.4 7.2 1.77 .65 .80 .95(19�C)

935 440 29.2 8.6 1.12 .63 .78 .92 28.0 8.2 1.31 .64 .79 .94 26.6 7.8 1.52 .65 .81 .96 25.2 7.4 1.77 .67 .84 .99

71�F695 330 28.4 8.3 1.12 .46 .58 .69 27.2 8.0 1.31 .47 .59 .70 26.0 7.6 1.52 .47 .60 .72 24.6 7.2 1.77 .47 .61 .74

71�F(22�C)

815 385 29.8 8.7 1.12 .47 .60 .72 28.6 8.4 1.31 .47 .61 .74 27.2 8.0 1.52 .48 .62 .75 25.8 7.6 1.77 .48 .63 .77(22�C)

935 440 30.8 9.0 1.13 .48 .62 .75 29.4 8.6 1.32 .48 .63 .77 28.0 8.2 1.53 .49 .64 .79 26.6 7.8 1.77 .49 .66 .81

XC21−036 with − C33−36B � G61MPV−36B−070 − SECONDSTAGE COOLING CAPACITY −

[CX34−36B−6F + G61MPV−36B−070][C33−36B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F950 450 34.8 10.2 2.06 .74 .86 .98 33.2 9.7 2.32 .75 .88 1.00 31.4 9.2 2.60 .77 .91 1.00 29.6 8.7 2.93 .79 .93 1.00

63�F(17�C)

1190 560 36.6 10.7 2.07 .78 .93 1.00 35.0 10.3 2.33 .80 .95 1.00 33.0 9.7 2.61 .82 .97 1.00 31.2 9.1 2.94 .85 1.00 1.00(17�C)

1395 660 38.0 11.1 2.09 .82 .97 1.00 36.2 10.6 2.34 .84 .99 1.00 34.4 10.1 2.62 .86 1.00 1.00 32.4 9.5 2.95 .89 1.00 1.00

67�F950 450 36.6 10.7 2.08 .60 .72 .83 35.0 10.3 2.33 .60 .73 .85 33.2 9.7 2.61 .61 .74 .87 31.2 9.1 2.94 .63 .76 .90

67�F(19�C)

1190 560 38.5 11.3 2.09 .62 .76 .89 36.8 10.8 2.34 .63 .78 .92 34.8 10.2 2.63 .65 .80 .94 32.6 9.6 2.95 .66 .82 .97(19�C)

1395 660 40.0 11.7 2.10 .65 .80 .94 38.0 11.1 2.36 .66 .82 .97 35.8 10.5 2.64 .68 .84 .99 33.6 9.8 2.96 .69 .87 1.00

71�F950 450 38.5 11.3 2.09 .46 .58 .69 36.6 10.7 2.34 .47 .59 .70 34.6 10.1 2.63 .47 .60 .72 32.6 9.6 2.95 .48 .61 .74

71�F(22�C)

1190 560 40.5 11.9 2.11 .48 .61 .74 38.5 11.3 2.36 .48 .62 .75 36.6 10.7 2.64 .49 .63 .77 34.4 10.1 2.97 .50 .65 .80(22�C)

1395 660 42.0 12.3 2.12 .49 .64 .78 40.0 11.7 2.37 .50 .65 .80 37.8 11.1 2.66 .51 .66 .82 35.4 10.4 2.98 .51 .68 .85

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−38A−6F + G60UHV−36A−070][C33−38A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F745 350 27.0 7.9 1.11 .75 .88 1.00 25.8 7.6 1.30 .76 .90 1.00 24.6 7.2 1.51 .78 .93 1.00 23.2 6.8 1.76 .80 .95 1.00

63�F(17�C)

850 400 28.0 8.2 1.12 .78 .92 1.00 26.8 7.9 1.31 .79 .94 1.00 25.4 7.4 1.52 .81 .97 1.00 24.0 7.0 1.76 .84 .99 1.00(17�C)

910 430 28.4 8.3 1.12 .79 .94 1.00 27.2 8.0 1.30 .81 .97 1.00 25.8 7.6 1.52 .83 .99 1.00 24.4 7.2 1.77 .85 1.00 1.00

67�F745 350 28.8 8.4 1.12 .59 .72 .84 27.6 8.1 1.31 .61 .74 .86 26.2 7.7 1.52 .61 .75 .89 24.8 7.3 1.77 .63 .77 .92

67�F(19�C)

850 400 29.8 8.7 1.12 .62 .75 .88 28.4 8.3 1.31 .62 .77 .91 27.0 7.9 1.52 .64 .78 .93 25.4 7.4 1.77 .65 .81 .96(19�C)

910 430 30.2 8.9 1.13 .63 .77 .91 28.8 8.4 1.31 .64 .78 .93 27.4 8.0 1.52 .64 .80 .96 25.8 7.6 1.77 .66 .83 .98

71�F745 350 30.4 8.9 1.13 .46 .58 .69 29.2 8.6 1.31 .46 .58 .71 27.8 8.1 1.52 .47 .60 .73 26.4 7.7 1.77 .47 .61 .75

71�F(22�C)

850 400 31.6 9.3 1.14 .47 .60 .73 30.2 8.9 1.32 .47 .61 .74 28.6 8.4 1.53 .48 .62 .76 27.0 7.9 1.78 .48 .63 .78(22�C)

910 430 32.0 9.4 1.14 .47 .61 .74 30.6 9.0 1.32 .48 .62 .76 29.2 8.6 1.53 .48 .63 .78 27.4 8.0 1.77 .49 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−38A−6F + G60UHV−36A−070][C33−38A + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1035 490 37.0 10.8 2.08 .75 .88 1.00 35.2 10.3 2.33 .77 .90 1.00 33.2 9.7 2.62 .79 .93 1.00 31.2 9.1 2.94 .81 .96 1.00

63�F(17�C)

1230 580 38.5 11.3 2.09 .79 .94 1.00 36.6 10.7 2.34 .81 .96 1.00 34.6 10.1 2.63 .83 .99 1.00 32.4 9.5 2.95 .86 1.00 1.00(17�C)

1375 650 39.5 11.6 2.09 .82 .97 1.00 37.4 11.0 2.35 .84 .99 1.00 35.4 10.4 2.63 .86 1.00 1.00 33.4 9.8 2.96 .89 1.00 1.00

67�F1035 490 39.0 11.4 2.09 .60 .73 .85 37.2 10.9 2.35 .61 .74 .87 35.2 10.3 2.63 .62 .76 .90 33.0 9.7 2.96 .63 .78 .93

67�F(19�C)

1230 580 40.5 11.9 2.11 .63 .77 .90 38.5 11.3 2.36 .64 .78 .93 36.4 10.7 2.64 .65 .80 .95 34.0 10.0 2.97 .66 .83 .99(19�C)

1375 650 41.5 12.2 2.11 .64 .80 .94 39.5 11.6 2.37 .66 .81 .97 37.2 10.9 2.65 .67 .84 .99 34.8 10.2 2.97 .69 .87 1.00

71�F1035 490 41.0 12.0 2.11 .47 .58 .70 39.5 11.6 2.36 .47 .59 .72 37.2 10.9 2.65 .47 .60 .74 35.0 10.3 2.98 .48 .62 .76

71�F(22�C)

1230 580 43.0 12.6 2.12 .47 .61 .74 40.5 11.9 2.38 .48 .62 .76 38.5 11.3 2.66 .49 .64 .78 36.2 10.6 2.98 .50 .65 .81(22�C)

1375 650 44.0 12.9 2.13 .49 .63 .77 41.5 12.2 2.38 .49 .64 .80 39.5 11.6 2.67 .50 .66 .81 36.8 10.8 2.99 .50 .68 .84

Page 58: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 3 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 58

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−38B−6F + G60UHV−36B−090][C33−38B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F740 350 27.0 7.9 1.11 .75 .88 1.00 25.8 7.6 1.30 .76 .90 1.00 24.6 7.2 1.51 .78 .92 1.00 23.0 6.7 1.76 .80 .95 1.00

63�F(17�C)

840 395 27.8 8.1 1.12 .77 .92 1.00 26.6 7.8 1.30 .79 .94 1.00 25.2 7.4 1.52 .81 .96 1.00 23.8 7.0 1.76 .83 .99 1.00(17�C)

920 435 28.4 8.3 1.12 .79 .95 1.00 27.2 8.0 1.31 .81 .97 1.00 25.8 7.6 1.52 .83 .99 1.00 24.4 7.2 1.77 .85 1.00 1.00

67�F740 350 28.8 8.4 1.12 .59 .72 .84 27.6 8.1 1.31 .60 .73 .86 26.2 7.7 1.52 .61 .75 .88 24.6 7.2 1.77 .63 .77 .91

67�F(19�C)

840 395 29.6 8.7 1.13 .61 .75 .88 28.4 8.3 1.31 .62 .76 .90 27.0 7.9 1.52 .63 .78 .93 25.4 7.4 1.77 .64 .80 .96(19�C)

920 435 30.2 8.9 1.13 .63 .77 .91 28.8 8.4 1.31 .64 .79 .93 27.4 8.0 1.52 .64 .80 .96 25.8 7.6 1.77 .66 .83 .99

71�F740 350 30.4 8.9 1.13 .46 .58 .69 29.2 8.6 1.31 .46 .58 .71 27.8 8.1 1.52 .46 .60 .72 26.2 7.7 1.77 .47 .61 .74

71�F(22�C)

840 395 31.4 9.2 1.14 .47 .60 .72 30.0 8.8 1.32 .47 .61 .74 28.6 8.4 1.53 .47 .62 .76 27.0 7.9 1.77 .48 .63 .78(22�C)

920 435 32.0 9.4 1.14 .47 .61 .75 30.6 9.0 1.32 .48 .62 .76 29.2 8.6 1.53 .48 .63 .78 27.4 8.0 1.77 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−38B−6F + G60UHV−36B−090][C33−38B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1035 490 36.8 10.8 2.08 .75 .88 1.00 35.0 10.3 2.33 .76 .90 1.00 33.2 9.7 2.62 .78 .93 1.00 31.2 9.1 2.94 .81 .96 1.00

63�F(17�C)

1225 580 38.5 11.3 2.09 .79 .93 1.00 36.4 10.7 2.34 .80 .96 1.00 34.4 10.1 2.63 .82 .98 1.00 32.2 9.4 2.95 .85 1.00 1.00(17�C)

1385 655 39.5 11.6 2.09 .82 .97 1.00 37.4 11.0 2.35 .84 .99 1.00 35.2 10.3 2.63 .86 1.00 1.00 33.4 9.8 2.96 .89 1.00 1.00

67�F1035 490 39.0 11.4 2.09 .60 .73 .85 37.2 10.9 2.35 .60 .74 .87 35.2 10.3 2.63 .62 .76 .89 33.0 9.7 2.96 .63 .78 .92

67�F(19�C)

1225 580 40.5 11.9 2.10 .62 .76 .90 38.5 11.3 2.36 .63 .78 .92 36.4 10.7 2.64 .65 .80 .95 34.0 10.0 2.96 .66 .83 .98(19�C)

1385 655 41.5 12.2 2.11 .64 .79 .94 39.5 11.6 2.36 .65 .81 .96 37.2 10.9 2.65 .67 .84 .99 34.8 10.2 2.97 .68 .86 1.00

71�F1035 490 41.0 12.0 2.11 .46 .58 .70 39.0 11.4 2.36 .46 .59 .72 37.2 10.9 2.65 .47 .60 .73 35.0 10.3 2.98 .48 .62 .76

71�F(22�C)

1225 580 42.5 12.5 2.12 .47 .60 .74 40.5 11.9 2.37 .48 .62 .76 38.5 11.3 2.66 .48 .63 .77 36.0 10.6 2.98 .49 .65 .80(22�C)

1385 655 43.5 12.7 2.13 .48 .63 .76 41.5 12.2 2.39 .49 .64 .79 39.5 11.6 2.67 .50 .66 .80 36.8 10.8 2.99 .50 .67 .84

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−38B−6F + G61MPV−36B−070][C33−38B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F695 330 26.4 7.7 1.11 .73 .86 .98 25.4 7.4 1.30 .75 .88 1.00 24.0 7.0 1.51 .77 .91 1.00 22.8 6.7 1.76 .79 .93 1.00

63�F(17�C)

815 385 27.6 8.1 1.12 .77 .91 1.00 26.4 7.7 1.30 .78 .93 1.00 25.2 7.4 1.52 .80 .96 1.00 23.6 6.9 1.76 .82 .98 1.00(17�C)

935 440 28.6 8.4 1.12 .80 .95 1.00 27.4 8.0 1.30 .82 .97 1.00 26.0 7.6 1.52 .84 1.00 1.00 24.6 7.2 1.76 .86 1.00 1.00

67�F695 330 28.2 8.3 1.12 .59 .71 .83 27.0 7.9 1.31 .59 .72 .84 25.8 7.6 1.52 .61 .74 .87 24.4 7.2 1.76 .61 .76 .89

67�F(19�C)

815 385 29.4 8.6 1.12 .61 .74 .87 28.2 8.3 1.31 .62 .76 .89 26.8 7.9 1.52 .63 .78 .92 25.2 7.4 1.77 .64 .80 .95(19�C)

935 440 30.4 8.9 1.13 .63 .77 .92 29.0 8.5 1.31 .64 .79 .94 27.4 8.0 1.52 .65 .81 .96 25.8 7.6 1.77 .66 .83 .99

71�F695 330 30.0 8.8 1.13 .46 .57 .68 28.6 8.4 1.31 .46 .58 .69 27.4 8.0 1.52 .46 .59 .71 25.8 7.6 1.77 .47 .60 .73

71�F(22�C)

815 385 31.2 9.1 1.13 .46 .59 .72 30.0 8.8 1.32 .47 .60 .73 28.4 8.3 1.53 .47 .61 .75 26.8 7.9 1.77 .48 .63 .77(22�C)

935 440 32.2 9.4 1.14 .47 .61 .74 30.8 9.0 1.32 .48 .62 .77 29.2 8.6 1.53 .48 .64 .79 27.6 8.1 1.78 .49 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−38B−6F + G61MPV−36B−070][C33−38B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F950 450 36.0 10.6 2.07 .74 .86 .98 34.4 10.1 2.33 .75 .88 1.00 32.6 9.6 2.61 .76 .90 1.00 30.6 9.0 2.94 .79 .93 1.00

63�F(17�C)

1190 560 38.0 11.1 2.09 .78 .93 1.00 36.2 10.6 2.34 .80 .95 1.00 34.2 10.0 2.63 .82 .98 1.00 32.2 9.4 2.94 .85 1.00 1.00(17�C)

1395 660 39.5 11.6 2.10 .82 .98 1.00 37.6 11.0 2.35 .84 1.00 1.00 35.4 10.4 2.64 .87 1.00 1.00 33.6 9.8 2.96 .90 1.00 1.00

67�F950 450 38.5 11.3 2.09 .59 .71 .82 36.6 10.7 2.34 .60 .73 .85 34.6 10.1 2.63 .60 .74 .87 32.4 9.5 2.95 .62 .76 .90

67�F(19�C)

1190 560 40.5 11.9 2.10 .61 .76 .89 38.5 11.3 2.36 .63 .78 .91 36.2 10.6 2.64 .64 .80 .94 34.0 10.0 2.96 .66 .82 .98(19�C)

1395 660 41.5 12.2 2.11 .65 .80 .95 39.5 11.6 2.37 .66 .82 .97 37.2 10.9 2.65 .67 .84 1.00 35.0 10.3 2.97 .69 .87 1.00

71�F950 450 40.5 11.9 2.10 .46 .57 .68 38.5 11.3 2.36 .46 .58 .70 36.4 10.7 2.64 .47 .59 .71 34.4 10.1 2.97 .47 .60 .73

71�F(22�C)

1190 560 42.5 12.5 2.12 .47 .60 .73 40.5 11.9 2.37 .48 .62 .75 38.5 11.3 2.66 .49 .63 .77 36.0 10.6 2.99 .49 .65 .80(22�C)

1395 660 44.0 12.9 2.13 .49 .63 .77 41.5 12.2 2.38 .50 .65 .80 39.5 11.6 2.67 .50 .66 .82 36.8 10.8 2.99 .51 .68 .85

Page 59: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 3 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 59

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−42B−6F + G60UHV−36B−090][C33−42B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F740 350 26.2 7.7 1.11 .75 .88 1.00 25.0 7.3 1.30 .76 .90 1.00 23.8 7.0 1.51 .78 .93 1.00 22.6 6.6 1.76 .80 .95 1.00

63�F(17�C)

840 395 27.0 7.9 1.11 .78 .92 1.00 25.8 7.6 1.30 .79 .94 1.00 24.6 7.2 1.51 .81 .96 1.00 23.2 6.8 1.76 .83 .99 1.00(17�C)

920 435 27.6 8.1 1.11 .80 .95 1.00 26.4 7.7 1.30 .81 .97 1.00 25.2 7.4 1.52 .83 .99 1.00 23.8 7.0 1.76 .86 1.00 1.00

67�F740 350 27.6 8.1 1.11 .60 .73 .85 26.4 7.7 1.30 .61 .74 .87 25.2 7.4 1.51 .62 .76 .89 23.8 7.0 1.76 .63 .78 .92

67�F(19�C)

840 395 28.6 8.4 1.12 .61 .75 .88 27.4 8.0 1.31 .62 .77 .90 26.0 7.6 1.52 .63 .78 .93 24.6 7.2 1.77 .65 .81 .96(19�C)

920 435 29.2 8.6 1.12 .63 .77 .91 27.8 8.1 1.31 .64 .79 .93 26.6 7.8 1.52 .65 .81 .96 25.0 7.3 1.77 .66 .83 .98

71�F740 350 29.0 8.5 1.12 .46 .59 .70 27.8 8.1 1.31 .47 .59 .71 26.4 7.7 1.52 .47 .60 .73 25.0 7.3 1.77 .47 .61 .75

71�F(22�C)

840 395 30.0 8.8 1.13 .47 .60 .73 28.6 8.4 1.31 .47 .61 .74 27.4 8.0 1.52 .48 .62 .76 25.8 7.6 1.77 .48 .63 .78(22�C)

920 435 30.6 9.0 1.13 .48 .61 .75 29.4 8.6 1.32 .48 .62 .76 28.0 8.2 1.53 .48 .63 .78 26.4 7.7 1.77 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−42B−6F + G60UHV−36B−090][C33−42B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1035 490 35.6 10.4 2.07 .75 .88 1.00 33.8 9.9 2.32 .77 .90 1.00 32.0 9.4 2.61 .79 .93 1.00 30.0 8.8 2.93 .81 .96 1.00

63�F(17�C)

1225 580 36.8 10.8 2.07 .79 .93 1.00 35.2 10.3 2.33 .80 .96 1.00 33.2 9.7 2.62 .82 .98 1.00 31.4 9.2 2.94 .85 1.00 1.00(17�C)

1385 655 37.8 11.1 2.08 .81 .97 1.00 36.0 10.6 2.34 .83 .99 1.00 34.2 10.0 2.62 .86 1.00 1.00 32.2 9.4 2.95 .89 1.00 1.00

67�F1035 490 37.4 11.0 2.08 .60 .73 .85 35.6 10.4 2.33 .61 .74 .87 33.8 9.9 2.62 .62 .76 .90 31.8 9.3 2.95 .64 .78 .93

67�F(19�C)

1225 580 39.0 11.4 2.09 .62 .76 .90 37.0 10.8 2.35 .64 .78 .92 35.0 10.3 2.63 .65 .80 .95 32.8 9.6 2.96 .66 .83 .98(19�C)

1385 655 40.0 11.7 2.10 .64 .79 .94 37.8 11.1 2.35 .65 .81 .96 35.8 10.5 2.64 .67 .83 .98 33.6 9.8 2.96 .69 .86 1.00

71�F1035 490 39.0 11.4 2.09 .47 .59 .71 37.4 11.0 2.35 .47 .60 .72 35.4 10.4 2.63 .48 .61 .74 33.2 9.7 2.95 .48 .62 .76

71�F(22�C)

1225 580 40.5 11.9 2.11 .48 .61 .74 38.5 11.3 2.36 .48 .62 .76 36.8 10.8 2.65 .49 .63 .78 34.4 10.1 2.97 .50 .65 .80(22�C)

1385 655 41.5 12.2 2.11 .49 .63 .77 39.5 11.6 2.37 .49 .64 .79 37.6 11.0 2.66 .50 .66 .81 35.2 10.3 2.98 .51 .68 .84

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−42B−6F + G61MPV−36B−070][C33−42B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F695 330 25.8 7.6 1.11 .74 .87 .98 24.6 7.2 1.29 .75 .89 1.00 23.4 6.9 1.51 .77 .91 1.00 22.2 6.5 1.76 .79 .94 1.00

63�F(17�C)

815 385 26.8 7.9 1.11 .77 .91 1.00 25.6 7.5 1.30 .79 .93 1.00 24.4 7.2 1.51 .80 .96 1.00 23.2 6.8 1.76 .83 .98 1.00(17�C)

935 440 27.8 8.1 1.12 .80 .95 1.00 26.6 7.8 1.30 .82 .97 1.00 25.4 7.4 1.52 .84 .99 1.00 24.0 7.0 1.76 .86 1.00 1.00

67�F695 330 27.2 8.0 1.11 .60 .72 .83 26.0 7.6 1.30 .60 .73 .85 24.8 7.3 1.52 .61 .74 .87 23.4 6.9 1.76 .62 .76 .90

67�F(19�C)

815 385 28.4 8.3 1.12 .61 .75 .88 27.2 8.0 1.30 .62 .76 .89 25.8 7.6 1.52 .63 .78 .92 24.4 7.2 1.77 .65 .80 .95(19�C)

935 440 29.2 8.6 1.12 .63 .78 .92 28.0 8.2 1.31 .64 .79 .94 26.6 7.8 1.52 .65 .81 .96 25.2 7.4 1.77 .67 .84 .99

71�F695 330 28.4 8.3 1.12 .46 .58 .69 27.2 8.0 1.31 .47 .59 .70 26.0 7.6 1.52 .47 .60 .72 24.6 7.2 1.77 .47 .61 .74

71�F(22�C)

815 385 29.8 8.7 1.12 .47 .60 .72 28.6 8.4 1.31 .47 .61 .74 27.2 8.0 1.52 .48 .62 .75 25.8 7.6 1.77 .48 .63 .77(22�C)

935 440 30.8 9.0 1.13 .48 .62 .75 29.4 8.6 1.32 .48 .63 .77 28.0 8.2 1.53 .49 .64 .79 26.6 7.8 1.77 .49 .66 .81

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−42B−6F + G61MPV−36B−070][C33−42B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F950 450 34.8 10.2 2.06 .74 .86 .98 33.2 9.7 2.32 .75 .88 1.00 31.4 9.2 2.60 .77 .91 1.00 29.6 8.7 2.93 .79 .93 1.00

63�F(17�C)

1190 560 36.6 10.7 2.07 .78 .93 1.00 35.0 10.3 2.33 .80 .95 1.00 33.0 9.7 2.61 .82 .97 1.00 31.2 9.1 2.94 .85 1.00 1.00(17�C)

1395 660 38.0 11.1 2.09 .82 .97 1.00 36.2 10.6 2.34 .84 .99 1.00 34.4 10.1 2.62 .86 1.00 1.00 32.4 9.5 2.95 .89 1.00 1.00

67�F950 450 36.6 10.7 2.08 .60 .72 .83 35.0 10.3 2.33 .60 .73 .85 33.2 9.7 2.61 .61 .74 .87 31.2 9.1 2.94 .63 .76 .90

67�F(19�C)

1190 560 38.5 11.3 2.09 .62 .76 .89 36.8 10.8 2.34 .63 .78 .92 34.8 10.2 2.63 .65 .80 .94 32.6 9.6 2.95 .66 .82 .97(19�C)

1395 660 40.0 11.7 2.10 .65 .80 .94 38.0 11.1 2.36 .66 .82 .97 35.8 10.5 2.64 .68 .84 .99 33.6 9.8 2.96 .69 .87 1.00

71�F950 450 38.5 11.3 2.09 .46 .58 .69 36.6 10.7 2.34 .47 .59 .70 34.6 10.1 2.63 .47 .60 .72 32.6 9.6 2.95 .48 .61 .74

71�F(22�C)

1190 560 40.5 11.9 2.11 .48 .61 .74 38.5 11.3 2.36 .48 .62 .75 36.6 10.7 2.64 .49 .63 .77 34.4 10.1 2.97 .50 .65 .80(22�C)

1395 660 42.0 12.3 2.12 .49 .64 .78 40.0 11.7 2.37 .50 .65 .80 37.8 11.1 2.66 .51 .66 .82 35.4 10.4 2.98 .51 .68 .85

Page 60: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 3 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 60

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−44/48B−6F + G60UHV−36B−090][C33−48B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F740 350 26.6 7.8 1.11 .74 .87 .99 25.4 7.4 1.30 .75 .89 1.00 24.2 7.1 1.51 .77 .91 1.00 22.8 6.7 1.76 .79 .94 1.00

63�F(17�C)

840 395 27.4 8.0 1.11 .77 .90 1.00 26.2 7.7 1.30 .78 .93 1.00 25.0 7.3 1.52 .80 .95 1.00 23.6 6.9 1.76 .82 .98 1.00(17�C)

920 435 28.2 8.3 1.12 .79 .93 1.00 26.8 7.9 1.30 .80 .95 1.00 25.4 7.4 1.52 .82 .98 1.00 24.0 7.0 1.76 .84 1.00 1.00

67�F740 350 28.4 8.3 1.12 .59 .71 .83 27.2 8.0 1.31 .60 .73 .85 25.8 7.6 1.52 .61 .74 .87 24.4 7.2 1.77 .62 .76 .90

67�F(19�C)

840 395 29.2 8.6 1.12 .61 .74 .87 28.0 8.2 1.31 .62 .75 .89 26.6 7.8 1.52 .63 .77 .91 25.0 7.3 1.77 .64 .79 .94(19�C)

920 435 29.8 8.7 1.13 .62 .76 .89 28.6 8.4 1.31 .63 .77 .92 27.0 7.9 1.52 .64 .79 .94 25.6 7.5 1.77 .65 .82 .97

71�F740 350 30.2 8.9 1.13 .46 .57 .69 28.8 8.4 1.31 .46 .58 .70 27.4 8.0 1.52 .46 .59 .71 26.0 7.6 1.77 .47 .60 .74

71�F(22�C)

840 395 31.0 9.1 1.13 .46 .58 .71 29.8 8.7 1.32 .47 .60 .73 28.4 8.3 1.53 .47 .61 .74 26.8 7.9 1.77 .48 .62 .76(22�C)

920 435 31.8 9.3 1.14 .47 .60 .73 30.4 8.9 1.32 .47 .61 .75 28.8 8.4 1.53 .48 .62 .77 27.2 8.0 1.77 .48 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−44/48B−6F + G60UHV−36B−090][C33−48B + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1035 490 36.4 10.7 2.07 .74 .87 .99 34.8 10.2 2.33 .75 .89 1.00 32.8 9.6 2.61 .77 .91 1.00 30.8 9.0 2.94 .79 .94 1.00

63�F(17�C)

1225 580 37.8 11.1 2.08 .77 .91 1.00 36.0 10.6 2.34 .79 .94 1.00 34.0 10.0 2.62 .81 .96 1.00 32.0 9.4 2.95 .84 .99 1.00(17�C)

1385 655 39.0 11.4 2.09 .80 .95 1.00 37.0 10.8 2.35 .82 .97 1.00 35.0 10.3 2.63 .84 1.00 1.00 32.8 9.6 2.95 .87 1.00 1.00

67�F1035 490 38.5 11.3 2.09 .59 .72 .83 36.8 10.8 2.34 .60 .73 .85 34.8 10.2 2.63 .61 .75 .88 32.8 9.6 2.95 .62 .77 .91

67�F(19�C)

1225 580 40.0 11.7 2.10 .61 .75 .88 38.0 11.1 2.35 .62 .77 .90 36.0 10.6 2.64 .64 .79 .93 33.8 9.9 2.96 .65 .81 .96(19�C)

1385 655 41.0 12.0 2.11 .63 .77 .92 39.0 11.4 2.36 .64 .79 .94 36.8 10.8 2.65 .65 .82 .97 34.4 10.1 2.96 .67 .84 1.00

71�F1035 490 41.0 12.0 2.11 .46 .58 .69 39.0 11.4 2.36 .46 .59 .70 36.8 10.8 2.65 .46 .59 .72 34.6 10.1 2.97 .47 .61 .74

71�F(22�C)

1225 580 42.5 12.5 2.12 .47 .59 .72 40.5 11.9 2.37 .47 .61 .74 38.0 11.1 2.66 .48 .62 .76 35.8 10.5 2.98 .49 .64 .78(22�C)

1385 655 43.0 12.6 2.13 .48 .62 .75 41.0 12.0 2.38 .48 .63 .77 39.0 11.4 2.67 .49 .64 .79 36.4 10.7 2.99 .49 .66 .82

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−44/48B−6F + G61MPV−36B−070][C33−48B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F695 330 26.2 7.7 1.11 .73 .85 .97 25.0 7.3 1.30 .74 .87 .99 23.8 7.0 1.51 .76 .89 1.00 22.4 6.6 1.76 .78 .92 1.00

63�F(17�C)

815 385 27.4 8.0 1.11 .76 .90 1.00 26.2 7.7 1.30 .77 .92 1.00 24.8 7.3 1.51 .79 .94 1.00 23.4 6.9 1.76 .82 .97 1.00(17�C)

935 440 28.2 8.3 1.12 .79 .94 1.00 27.0 7.9 1.31 .81 .96 1.00 25.6 7.5 1.52 .83 .99 1.00 24.2 7.1 1.76 .85 1.00 1.00

67�F695 330 28.0 8.2 1.12 .58 .70 .82 26.8 7.9 1.31 .59 .71 .84 25.4 7.4 1.52 .60 .73 .86 24.0 7.0 1.76 .61 .75 .88

67�F(19�C)

815 385 29.0 8.5 1.12 .60 .73 .86 27.8 8.1 1.31 .61 .75 .88 26.4 7.7 1.52 .62 .77 .90 25.0 7.3 1.77 .64 .79 .93(19�C)

935 440 30.0 8.8 1.13 .62 .76 .90 28.6 8.4 1.31 .63 .78 .92 27.2 8.0 1.52 .64 .80 .95 25.6 7.5 1.77 .65 .82 .98

71�F695 330 29.6 8.7 1.13 .46 .57 .68 28.4 8.3 1.31 .46 .57 .69 27.0 7.9 1.52 .46 .58 .70 25.6 7.5 1.77 .47 .60 .72

71�F(22�C)

815 385 30.8 9.0 1.13 .46 .59 .70 29.6 8.7 1.32 .47 .60 .72 28.2 8.3 1.53 .47 .61 .74 26.6 7.8 1.77 .48 .62 .76(22�C)

935 440 31.8 9.3 1.14 .47 .61 .74 30.4 8.9 1.32 .48 .62 .75 29.0 8.5 1.53 .48 .63 .77 27.4 8.0 1.77 .49 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−44/48B−6F + G61MPV−36B−070][C33−48B + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F950 450 35.6 10.4 2.07 .73 .85 .96 34.0 10.0 2.33 .74 .87 .98 32.2 9.4 2.61 .76 .89 1.00 30.2 8.9 2.93 .78 .92 1.00

63�F(17�C)

1190 560 37.8 11.1 2.08 .77 .91 1.00 35.8 10.5 2.34 .79 .93 1.00 34.0 10.0 2.62 .81 .96 1.00 31.8 9.3 2.95 .83 .99 1.00(17�C)

1395 660 39.0 11.4 2.09 .81 .96 1.00 37.2 10.9 2.35 .83 .98 1.00 35.0 10.3 2.63 .85 1.00 1.00 33.0 9.7 2.95 .88 1.00 1.00

67�F950 450 38.0 11.1 2.08 .59 .70 .81 36.2 10.6 2.34 .59 .72 .83 34.2 10.0 2.62 .60 .73 .85 32.2 9.4 2.95 .61 .75 .88

67�F(19�C)

1190 560 40.0 11.7 2.10 .62 .74 .87 38.0 11.1 2.36 .62 .76 .90 36.0 10.6 2.64 .64 .78 .92 33.6 9.8 2.96 .65 .81 .96(19�C)

1395 660 41.0 12.0 2.11 .64 .78 .92 39.0 11.4 2.36 .65 .80 .95 37.0 10.8 2.65 .66 .82 .98 34.6 10.1 2.97 .68 .85 1.00

71�F950 450 40.0 11.7 2.10 .46 .57 .68 38.0 11.1 2.35 .46 .58 .69 36.2 10.6 2.64 .46 .59 .71 34.0 10.0 2.97 .47 .60 .72

71�F(22�C)

1190 560 42.0 12.3 2.12 .47 .59 .72 40.0 11.7 2.37 .47 .61 .74 38.0 11.1 2.66 .48 .62 .76 35.6 10.4 2.98 .49 .64 .78(22�C)

1395 660 43.5 12.7 2.13 .48 .62 .76 41.5 12.2 2.38 .49 .64 .78 39.0 11.4 2.67 .50 .65 .80 36.6 10.7 2.99 .50 .67 .83

Page 61: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 3 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 61

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−44/48C−6F + G61MPV−60C−090][C33−48C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F890 420 28.0 8.2 1.12 .78 .92 1.00 26.6 7.8 1.30 .79 .94 1.00 25.4 7.4 1.52 .81 .97 1.00 23.8 7.0 1.76 .83 .99 1.00

63�F(17�C)

890 420 28.0 8.2 1.12 .78 .92 1.00 26.6 7.8 1.30 .79 .94 1.00 25.4 7.4 1.52 .81 .97 1.00 23.8 7.0 1.76 .83 .99 1.00(17�C)

995 470 28.6 8.4 1.12 .80 .96 1.00 27.4 8.0 1.31 .82 .98 1.00 26.0 7.6 1.52 .84 1.00 1.00 24.6 7.2 1.77 .87 1.00 1.00

67�F890 420 29.6 8.7 1.13 .61 .75 .88 28.4 8.3 1.31 .62 .76 .90 27.0 7.9 1.52 .63 .78 .93 25.4 7.4 1.77 .65 .81 .96

67�F(19�C)

890 420 29.6 8.7 1.13 .61 .75 .88 28.4 8.3 1.31 .62 .76 .90 27.0 7.9 1.52 .63 .78 .93 25.4 7.4 1.77 .65 .81 .96(19�C)

995 470 30.4 8.9 1.13 .63 .78 .92 29.0 8.5 1.31 .64 .79 .94 27.6 8.1 1.52 .65 .81 .97 26.0 7.6 1.77 .66 .84 .99

71�F890 420 31.4 9.2 1.14 .46 .60 .72 30.2 8.9 1.32 .47 .61 .74 28.6 8.4 1.53 .48 .62 .75 27.0 7.9 1.77 .48 .63 .78

71�F(22�C)

890 420 31.4 9.2 1.14 .46 .60 .72 30.2 8.9 1.32 .47 .61 .74 28.6 8.4 1.53 .48 .62 .75 27.0 7.9 1.77 .48 .63 .78(22�C)

995 470 32.2 9.4 1.14 .47 .61 .75 30.8 9.0 1.32 .48 .62 .77 29.2 8.6 1.53 .48 .64 .79 27.6 8.1 1.78 .49 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−44/48C−6F + G61MPV−60C−090][C33−48C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1275 600 38.0 11.1 2.09 .78 .92 1.00 36.4 10.7 2.34 .80 .95 1.00 34.4 10.1 2.63 .82 .98 1.00 32.2 9.4 2.95 .84 1.00 1.00

63�F(17�C)

1275 600 38.0 11.1 2.09 .78 .92 1.00 36.4 10.7 2.34 .80 .95 1.00 34.4 10.1 2.63 .82 .98 1.00 32.2 9.4 2.95 .84 1.00 1.00(17�C)

1440 680 39.0 11.4 2.10 .81 .96 1.00 37.2 10.9 2.35 .83 .99 1.00 35.2 10.3 2.63 .85 1.00 1.00 33.2 9.7 2.96 .88 1.00 1.00

67�F1275 600 40.5 11.9 2.10 .62 .76 .89 38.5 11.3 2.36 .63 .77 .92 36.2 10.6 2.64 .64 .80 .94 34.0 10.0 2.97 .66 .82 .97

67�F(19�C)

1275 600 40.5 11.9 2.10 .62 .76 .89 38.5 11.3 2.36 .63 .77 .92 36.2 10.6 2.64 .64 .80 .94 34.0 10.0 2.97 .66 .82 .97(19�C)

1440 680 41.5 12.2 2.11 .64 .79 .93 39.5 11.6 2.36 .65 .80 .95 37.2 10.9 2.65 .66 .83 .98 34.8 10.2 2.97 .68 .85 1.00

71�F1275 600 42.5 12.5 2.12 .47 .60 .73 40.5 11.9 2.38 .47 .62 .75 38.5 11.3 2.66 .48 .63 .77 36.0 10.6 2.99 .49 .64 .80

71�F(22�C)

1275 600 42.5 12.5 2.12 .47 .60 .73 40.5 11.9 2.38 .47 .62 .75 38.5 11.3 2.66 .48 .63 .77 36.0 10.6 2.99 .49 .64 .80(22�C)

1440 680 43.5 12.7 2.13 .48 .63 .76 41.5 12.2 2.38 .49 .64 .78 39.0 11.4 2.67 .49 .65 .80 36.6 10.7 2.99 .50 .67 .83

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−49C−6F + G60UHV−60C−090][C33−49C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F930 440 28.4 8.3 1.12 .79 .93 1.00 27.2 8.0 1.31 .80 .96 1.00 25.8 7.6 1.52 .82 .98 1.00 24.4 7.2 1.76 .85 1.00 1.00

63�F(17�C)

930 440 28.4 8.3 1.12 .79 .93 1.00 27.2 8.0 1.31 .80 .96 1.00 25.8 7.6 1.52 .82 .98 1.00 24.4 7.2 1.76 .85 1.00 1.00(17�C)

1055 500 29.2 8.6 1.12 .82 .98 1.00 28.0 8.2 1.31 .83 1.00 1.00 26.6 7.8 1.52 .86 1.00 1.00 25.4 7.4 1.77 .89 1.00 1.00

67�F930 440 30.2 8.9 1.13 .62 .76 .90 28.8 8.4 1.31 .63 .78 .92 27.4 8.0 1.52 .64 .80 .95 25.8 7.6 1.77 .66 .82 .98

67�F(19�C)

930 440 30.2 8.9 1.13 .62 .76 .90 28.8 8.4 1.31 .63 .78 .92 27.4 8.0 1.52 .64 .80 .95 25.8 7.6 1.77 .66 .82 .98(19�C)

1055 500 31.0 9.1 1.13 .64 .79 .94 29.6 8.7 1.32 .65 .81 .96 28.2 8.3 1.53 .66 .83 .99 26.4 7.7 1.77 .68 .86 1.00

71�F930 440 31.8 9.3 1.14 .47 .61 .74 30.4 8.9 1.32 .47 .62 .75 29.0 8.5 1.53 .48 .63 .77 27.4 8.0 1.77 .49 .64 .79

71�F(22�C)

930 440 31.8 9.3 1.14 .47 .61 .74 30.4 8.9 1.32 .47 .62 .75 29.0 8.5 1.53 .48 .63 .77 27.4 8.0 1.77 .49 .64 .79(22�C)

1055 500 32.8 9.6 1.14 .48 .62 .77 31.4 9.2 1.33 .48 .64 .78 29.8 8.7 1.53 .49 .65 .80 28.0 8.2 1.78 .49 .67 .83

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−49C−6F + G60UHV−60C−090][C33−49C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1355 640 39.0 11.4 2.10 .80 .95 1.00 37.4 11.0 2.35 .81 .97 1.00 35.2 10.3 2.63 .84 1.00 1.00 33.2 9.7 2.96 .87 1.00 1.00

63�F(17�C)

1355 640 39.0 11.4 2.10 .80 .95 1.00 37.4 11.0 2.35 .81 .97 1.00 35.2 10.3 2.63 .84 1.00 1.00 33.2 9.7 2.96 .87 1.00 1.00(17�C)

1520 715 40.0 11.7 2.10 .82 .98 1.00 38.0 11.1 2.35 .84 1.00 1.00 36.2 10.6 2.64 .87 1.00 1.00 34.4 10.1 2.97 .90 1.00 1.00

67�F1355 640 41.5 12.2 2.11 .63 .77 .91 39.5 11.6 2.36 .64 .79 .94 37.2 10.9 2.65 .66 .81 .97 34.8 10.2 2.97 .67 .84 1.00

67�F(19�C)

1355 640 41.5 12.2 2.11 .63 .77 .91 39.5 11.6 2.36 .64 .79 .94 37.2 10.9 2.65 .66 .81 .97 34.8 10.2 2.97 .67 .84 1.00(19�C)

1520 715 42.5 12.5 2.12 .65 .80 .95 40.0 11.7 2.37 .66 .82 .98 38.0 11.1 2.66 .68 .85 1.00 35.6 10.4 2.98 .69 .88 1.00

71�F1355 640 43.5 12.7 2.13 .48 .62 .75 41.5 12.2 2.38 .48 .63 .77 39.0 11.4 2.67 .49 .64 .79 36.8 10.8 2.99 .49 .66 .81

71�F(22�C)

1355 640 43.5 12.7 2.13 .48 .62 .75 41.5 12.2 2.38 .48 .63 .77 39.0 11.4 2.67 .49 .64 .79 36.8 10.8 2.99 .49 .66 .81(22�C)

1520 715 44.5 13.0 2.14 .49 .64 .78 42.0 12.3 2.39 .49 .65 .80 40.0 11.7 2.68 .50 .66 .82 37.4 11.0 3.00 .51 .68 .85

Page 62: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 3 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 62

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−49C−6F + G61MPV−60C−090][C33−49C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F960 455 28.6 8.4 1.12 .79 .95 1.00 27.4 8.0 1.31 .81 .97 1.00 26.0 7.6 1.52 .83 .99 1.00 24.6 7.2 1.76 .86 1.00 1.00

63�F(17�C)

1090 515 29.4 8.6 1.12 .82 .98 1.00 28.2 8.3 1.31 .84 1.00 1.00 27.0 7.9 1.52 .87 1.00 1.00 25.6 7.5 1.77 .90 1.00 1.00(17�C)

1205 570 30.2 8.9 1.13 .85 1.00 1.00 29.0 8.5 1.31 .87 1.00 1.00 27.8 8.1 1.53 .90 1.00 1.00 26.4 7.7 1.77 .93 1.00 1.00

67�F960 455 30.4 8.9 1.13 .63 .77 .91 29.0 8.5 1.31 .63 .79 .93 27.6 8.1 1.53 .65 .81 .96 26.0 7.6 1.77 .66 .83 .99

67�F(19�C)

1090 515 31.2 9.1 1.13 .64 .80 .95 29.8 8.7 1.32 .65 .82 .97 28.2 8.3 1.53 .67 .84 1.00 26.6 7.8 1.77 .68 .87 1.00(19�C)

1205 570 31.8 9.3 1.14 .66 .83 .98 30.4 8.9 1.32 .67 .85 1.00 28.8 8.4 1.53 .69 .87 1.00 27.2 8.0 1.77 .71 .90 1.00

71�F960 455 32.0 9.4 1.14 .47 .61 .74 30.6 9.0 1.32 .48 .62 .76 29.2 8.6 1.53 .48 .63 .78 27.6 8.1 1.78 .49 .65 .80

71�F(22�C)

1090 515 33.0 9.7 1.14 .48 .63 .77 31.6 9.3 1.33 .49 .64 .79 30.0 8.8 1.54 .48 .66 .81 28.2 8.3 1.78 .50 .67 .84(22�C)

1205 570 33.6 9.8 1.15 .49 .65 .80 32.2 9.4 1.33 .49 .66 .82 30.6 9.0 1.54 .49 .68 .84 28.8 8.4 1.78 .51 .70 .87

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−49C−6F + G61MPV−60C−090][C33−49C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1380 650 39.5 11.6 2.09 .80 .95 1.00 37.4 11.0 2.35 .82 .98 1.00 35.4 10.4 2.63 .84 1.00 1.00 33.4 9.8 2.96 .87 1.00 1.00

63�F(17�C)

1590 750 40.5 11.9 2.10 .84 1.00 1.00 38.5 11.3 2.36 .86 1.00 1.00 36.8 10.8 2.65 .88 1.00 1.00 34.8 10.2 2.97 .92 1.00 1.00(17�C)

1750 825 41.5 12.2 2.11 .86 1.00 1.00 39.5 11.6 2.37 .89 1.00 1.00 37.8 11.1 2.65 .92 1.00 1.00 35.6 10.4 2.98 .95 1.00 1.00

67�F1380 650 41.5 12.2 2.11 .63 .78 .92 39.5 11.6 2.37 .65 .80 .94 37.4 11.0 2.65 .66 .82 .98 35.0 10.3 2.97 .68 .85 1.00

67�F(19�C)

1590 750 42.5 12.5 2.12 .66 .81 .97 40.5 11.9 2.38 .67 .83 .99 38.5 11.3 2.66 .69 .86 1.00 35.8 10.5 2.98 .70 .90 1.00(19�C)

1750 825 43.5 12.7 2.13 .67 .84 1.00 41.0 12.0 2.38 .69 .87 1.00 39.0 11.4 2.67 .70 .89 1.00 36.4 10.7 2.99 .73 .93 1.00

71�F1380 650 43.5 12.7 2.13 .48 .62 .75 41.5 12.2 2.38 .49 .63 .77 39.0 11.4 2.67 .49 .65 .80 36.8 10.8 2.99 .49 .66 .82

71�F(22�C)

1590 750 45.0 13.2 2.14 .49 .64 .79 42.5 12.5 2.39 .50 .66 .81 40.5 11.9 2.68 .51 .68 .84 37.8 11.1 3.00 .51 .69 .87(22�C)

1750 825 45.5 13.3 2.15 .50 .66 .82 43.5 12.7 2.40 .51 .68 .84 41.0 12.0 2.68 .51 .70 .87 38.5 11.3 3.01 .53 .72 .91

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−49C−6F + G61MPV−60C−110][C33−49C + G61MPV−60C−110]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F805 380 27.4 8.0 1.11 .76 .89 1.00 26.2 7.7 1.30 .77 .91 1.00 24.8 7.3 1.51 .79 .94 1.00 23.4 6.9 1.76 .81 .97 1.00

63�F(17�C)

925 435 28.4 8.3 1.12 .79 .93 1.00 27.0 7.9 1.30 .80 .96 1.00 25.8 7.6 1.52 .82 .98 1.00 24.2 7.1 1.76 .85 1.00 1.00(17�C)

1050 495 29.2 8.6 1.12 .81 .97 1.00 27.8 8.1 1.31 .83 .99 1.00 26.6 7.8 1.52 .85 1.00 1.00 25.2 7.4 1.77 .88 1.00 1.00

67�F805 380 29.0 8.5 1.12 .60 .73 .85 27.8 8.1 1.31 .61 .74 .87 26.4 7.7 1.52 .62 .76 .90 25.0 7.3 1.77 .63 .78 .93

67�F(19�C)

925 435 30.0 8.8 1.13 .62 .76 .90 28.8 8.4 1.31 .63 .78 .92 27.4 8.0 1.52 .64 .80 .94 25.8 7.6 1.77 .65 .82 .98(19�C)

1050 495 31.0 9.1 1.13 .64 .79 .94 29.6 8.7 1.32 .65 .81 .96 28.0 8.2 1.53 .66 .83 .99 26.4 7.7 1.77 .68 .85 1.00

71�F805 380 30.6 9.0 1.13 .46 .59 .71 29.4 8.6 1.32 .46 .60 .72 28.0 8.2 1.52 .47 .61 .73 26.4 7.7 1.77 .47 .62 .76

71�F(22�C)

925 435 31.8 9.3 1.14 .47 .60 .73 30.4 8.9 1.32 .47 .62 .75 28.8 8.4 1.53 .48 .63 .77 27.4 8.0 1.78 .48 .64 .79(22�C)

1050 495 32.6 9.6 1.14 .48 .62 .76 31.2 9.1 1.33 .48 .63 .78 29.8 8.7 1.53 .49 .65 .80 28.0 8.2 1.78 .49 .66 .83

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−49C−6F + G61MPV−60C−110][C33−49C + G61MPV−60C−110]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1405 665 39.5 11.6 2.10 .81 .96 1.00 37.6 11.0 2.35 .82 .98 1.00 35.6 10.4 2.64 .85 1.00 1.00 33.6 9.8 2.96 .88 1.00 1.00

63�F(17�C)

1610 760 40.5 11.9 2.11 .84 1.00 1.00 38.5 11.3 2.36 .86 1.00 1.00 36.8 10.8 2.65 .89 1.00 1.00 34.8 10.2 2.97 .92 1.00 1.00(17�C)

1795 845 41.5 12.2 2.11 .87 1.00 1.00 40.0 11.7 2.37 .89 1.00 1.00 38.0 11.1 2.66 .93 1.00 1.00 35.8 10.5 2.98 .96 1.00 1.00

67�F1405 665 41.5 12.2 2.11 .64 .78 .92 39.5 11.6 2.37 .65 .80 .95 37.4 11.0 2.65 .66 .82 .98 35.0 10.3 2.98 .68 .85 1.00

67�F(19�C)

1610 760 43.0 12.6 2.12 .66 .82 .97 40.5 11.9 2.38 .67 .84 .99 38.5 11.3 2.66 .69 .86 1.00 35.8 10.5 2.98 .71 .90 1.00(19�C)

1795 845 43.5 12.7 2.13 .68 .85 1.00 41.5 12.2 2.38 .69 .87 1.00 39.0 11.4 2.66 .71 .90 1.00 36.6 10.7 2.99 .73 .94 1.00

71�F1405 665 43.5 12.7 2.13 .48 .62 .76 41.5 12.2 2.38 .49 .63 .78 39.5 11.6 2.67 .49 .65 .80 37.0 10.8 2.99 .49 .67 .83

71�F(22�C)

1610 760 45.0 13.2 2.14 .49 .65 .79 42.5 12.5 2.40 .49 .66 .81 40.5 11.9 2.68 .50 .68 .84 37.8 11.1 3.00 .52 .70 .87(22�C)

1795 845 46.0 13.5 2.15 .50 .67 .82 43.5 12.7 2.40 .51 .68 .85 41.0 12.0 2.68 .52 .70 .88 38.5 11.3 3.01 .53 .73 .92

Page 63: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 3 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 63

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−50/60C−6F + G60UHV−36C−090][C33−50/60C + G60UHV−36C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F705 335 26.6 7.8 1.11 .73 .86 .98 25.4 7.4 1.30 .75 .88 1.00 24.0 7.0 1.51 .76 .90 1.00 22.8 6.7 1.76 .78 .93 1.00

63�F(17�C)

790 375 27.4 8.0 1.11 .76 .89 1.00 26.2 7.7 1.30 .77 .91 1.00 24.8 7.3 1.51 .79 .94 1.00 23.4 6.9 1.76 .81 .97 1.00(17�C)

915 430 28.4 8.3 1.12 .79 .94 1.00 27.2 8.0 1.30 .80 .96 1.00 25.8 7.6 1.52 .82 .98 1.00 24.2 7.1 1.76 .84 1.00 1.00

67�F705 335 28.2 8.3 1.12 .59 .71 .82 27.0 7.9 1.31 .59 .71 .84 25.8 7.6 1.52 .61 .74 .86 24.4 7.2 1.76 .62 .76 .89

67�F(19�C)

790 375 29.0 8.5 1.12 .60 .73 .85 27.8 8.1 1.31 .61 .74 .88 26.4 7.7 1.52 .62 .76 .90 25.0 7.3 1.77 .63 .78 .93(19�C)

915 430 30.0 8.8 1.13 .62 .76 .90 28.8 8.4 1.31 .63 .78 .92 27.4 8.0 1.53 .64 .80 .95 25.8 7.6 1.77 .65 .82 .98

71�F705 335 30.0 8.8 1.13 .46 .57 .68 28.8 8.4 1.31 .46 .57 .69 27.4 8.0 1.52 .46 .58 .71 26.0 7.6 1.77 .46 .60 .73

71�F(22�C)

790 375 30.8 9.0 1.13 .46 .58 .70 29.6 8.7 1.32 .46 .59 .72 28.2 8.3 1.53 .47 .60 .73 26.6 7.8 1.77 .47 .62 .75(22�C)

915 430 32.0 9.4 1.14 .47 .60 .73 30.6 9.0 1.32 .47 .62 .75 29.2 8.6 1.53 .48 .63 .77 27.4 8.0 1.77 .48 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−50/60C−6F + G60UHV−36C−090][C33−50/60C + G60UHV−36C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1015 480 36.6 10.7 2.07 .74 .86 .99 34.8 10.2 2.33 .75 .88 1.00 33.0 9.7 2.62 .77 .91 1.00 31.0 9.1 2.94 .79 .94 1.00

63�F(17�C)

1185 560 38.0 11.1 2.09 .77 .91 1.00 36.2 10.6 2.34 .79 .93 1.00 34.2 10.0 2.63 .81 .96 1.00 32.0 9.4 2.95 .83 .99 1.00(17�C)

1395 660 39.5 11.6 2.10 .81 .96 1.00 37.4 11.0 2.35 .83 .99 1.00 35.4 10.4 2.63 .85 1.00 1.00 33.4 9.8 2.96 .88 1.00 1.00

67�F1015 480 39.0 11.4 2.09 .59 .72 .83 37.0 10.8 2.35 .60 .73 .85 35.0 10.3 2.63 .60 .75 .88 32.8 9.6 2.95 .62 .77 .91

67�F(19�C)

1185 560 40.0 11.7 2.10 .61 .75 .88 38.0 11.1 2.36 .62 .76 .90 36.2 10.6 2.64 .63 .78 .93 33.8 9.9 2.96 .65 .80 .96(19�C)

1395 660 41.5 12.2 2.11 .64 .79 .93 39.5 11.6 2.37 .64 .80 .95 37.4 11.0 2.65 .66 .83 .98 35.0 10.3 2.97 .68 .86 1.00

71�F1015 480 41.0 12.0 2.11 .46 .58 .69 39.0 11.4 2.36 .46 .58 .71 37.0 10.8 2.65 .46 .59 .72 34.8 10.2 2.97 .47 .61 .74

71�F(22�C)

1185 560 42.5 12.5 2.12 .47 .60 .72 40.5 11.9 2.37 .47 .61 .74 38.5 11.3 2.66 .48 .62 .76 35.8 10.5 2.98 .49 .63 .78(22�C)

1395 660 44.0 12.9 2.13 .48 .62 .76 41.5 12.2 2.39 .49 .64 .78 39.5 11.6 2.67 .49 .65 .80 37.0 10.8 2.99 .50 .67 .83

FIRST STAGE COOLING CAPACITY − XC21−036 with [CX34−50/60C−6F + G60UHV−60C−090][C33−50/60C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F930 440 28.4 8.3 1.12 .79 .94 1.00 27.2 8.0 1.31 .81 .96 1.00 25.8 7.6 1.52 .83 .99 1.00 24.4 7.2 1.76 .85 1.00 1.00

63�F(17�C)

930 440 28.4 8.3 1.12 .79 .94 1.00 27.2 8.0 1.31 .81 .96 1.00 25.8 7.6 1.52 .83 .99 1.00 24.4 7.2 1.76 .85 1.00 1.00(17�C)

1055 500 29.2 8.6 1.12 .82 .98 1.00 28.0 8.2 1.31 .84 1.00 1.00 26.6 7.8 1.52 .86 1.00 1.00 25.4 7.4 1.77 .89 1.00 1.00

67�F930 440 30.2 8.9 1.13 .62 .76 .90 28.8 8.4 1.31 .63 .78 .92 27.4 8.0 1.53 .64 .80 .95 25.8 7.6 1.77 .65 .82 .98

67�F(19�C)

930 440 30.2 8.9 1.13 .62 .76 .90 28.8 8.4 1.31 .63 .78 .92 27.4 8.0 1.53 .64 .80 .95 25.8 7.6 1.77 .65 .82 .98(19�C)

1055 500 31.0 9.1 1.13 .64 .79 .94 29.6 8.7 1.32 .65 .81 .97 28.2 8.3 1.53 .66 .83 .99 26.4 7.7 1.77 .68 .86 1.00

71�F930 440 32.0 9.4 1.14 .47 .61 .74 30.6 9.0 1.32 .47 .62 .75 29.2 8.6 1.53 .48 .63 .77 27.6 8.1 1.77 .48 .64 .80

71�F(22�C)

930 440 32.0 9.4 1.14 .47 .61 .74 30.6 9.0 1.32 .47 .62 .75 29.2 8.6 1.53 .48 .63 .77 27.6 8.1 1.77 .48 .64 .80(22�C)

1055 500 33.0 9.7 1.15 .48 .62 .77 31.4 9.2 1.33 .48 .63 .79 29.8 8.7 1.53 .48 .65 .81 28.2 8.3 1.78 .49 .67 .84

SECOND STAGE COOLING CAPACITY − XC21−036 with [CX34−50/60C−6F + G60UHV−60C−090][C33−50/60C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1355 640 39.0 11.4 2.09 .80 .95 1.00 37.2 10.9 2.35 .82 .98 1.00 35.2 10.3 2.63 .84 1.00 1.00 33.2 9.7 2.96 .87 1.00 1.00

63�F(17�C)

1355 640 39.0 11.4 2.09 .80 .95 1.00 37.2 10.9 2.35 .82 .98 1.00 35.2 10.3 2.63 .84 1.00 1.00 33.2 9.7 2.96 .87 1.00 1.00(17�C)

1520 715 40.0 11.7 2.10 .83 .99 1.00 38.0 11.1 2.35 .85 1.00 1.00 36.2 10.6 2.64 .87 1.00 1.00 34.2 10.0 2.97 .91 1.00 1.00

67�F1355 640 41.0 12.0 2.11 .63 .77 .92 39.0 11.4 2.36 .64 .79 .94 37.0 10.8 2.65 .65 .82 .97 34.8 10.2 2.97 .67 .84 1.00

67�F(19�C)

1355 640 41.0 12.0 2.11 .63 .77 .92 39.0 11.4 2.36 .64 .79 .94 37.0 10.8 2.65 .65 .82 .97 34.8 10.2 2.97 .67 .84 1.00(19�C)

1520 715 42.0 12.3 2.12 .64 .81 .96 40.0 11.7 2.37 .66 .83 .98 37.8 11.1 2.66 .68 .85 1.00 35.4 10.4 2.98 .70 .88 1.00

71�F1355 640 43.5 12.7 2.13 .48 .62 .75 41.5 12.2 2.38 .48 .63 .77 39.0 11.4 2.67 .49 .64 .79 36.8 10.8 2.99 .49 .66 .82

71�F(22�C)

1355 640 43.5 12.7 2.13 .48 .62 .75 41.5 12.2 2.38 .48 .63 .77 39.0 11.4 2.67 .49 .64 .79 36.8 10.8 2.99 .49 .66 .82(22�C)

1520 715 44.5 13.0 2.14 .49 .64 .78 42.0 12.3 2.39 .49 .64 .80 40.0 11.7 2.67 .50 .66 .83 37.4 11.0 3.00 .50 .68 .86

Page 64: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 2 TON

DOWN−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 64

FIRST STAGE COOLING CAPACITY − XC21−036 with [CR26−36N/W−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 27.2 8.0 1.11 .77 .91 1.00 26.0 7.6 1.29 .79 .93 1.00 24.8 7.3 1.50 .81 .96 1.00 23.4 6.9 1.75 .83 .98 1.00

63�F(17�C)

900 425 28.0 8.2 1.11 .80 .95 1.00 26.8 7.9 1.30 .82 .97 1.00 25.4 7.4 1.51 .84 .99 1.00 24.0 7.0 1.75 .87 1.00 1.00(17�C)

1000 470 28.6 8.4 1.12 .83 .98 1.00 27.4 8.0 1.30 .85 1.00 1.00 26.2 7.7 1.51 .87 1.00 1.00 24.8 7.3 1.75 .90 1.00 1.00

67�F800 380 28.8 8.4 1.12 .62 .75 .88 27.6 8.1 1.30 .63 .76 .90 26.2 7.7 1.51 .64 .78 .92 24.8 7.3 1.75 .65 .80 .95

67�F(19�C)

900 425 29.6 8.7 1.12 .63 .78 .91 28.4 8.3 1.30 .64 .79 .93 27.0 7.9 1.51 .66 .81 .96 25.4 7.4 1.75 .67 .84 .99(19�C)

1000 470 30.2 8.9 1.13 .65 .80 .95 29.0 8.5 1.31 .66 .82 .97 27.4 8.0 1.52 .68 .84 .99 25.8 7.6 1.76 .69 .87 1.00

71�F800 380 30.6 9.0 1.13 .47 .60 .72 29.4 8.6 1.31 .48 .61 .74 27.8 8.1 1.52 .48 .62 .75 26.4 7.7 1.76 .49 .63 .78

71�F(22�C)

900 425 31.4 9.2 1.13 .48 .62 .75 30.0 8.8 1.31 .49 .63 .77 28.6 8.4 1.52 .49 .64 .79 27.0 7.9 1.76 .50 .66 .81(22�C)

1000 470 32.0 9.4 1.14 .49 .64 .78 30.6 9.0 1.32 .50 .65 .80 29.2 8.6 1.52 .50 .66 .82 27.4 8.0 1.76 .51 .68 .84

SECOND STAGE COOLING CAPACITY − XC21−036 with [CR26−36N/W−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 35.8 10.5 2.07 .75 .88 .99 34.2 10.0 2.33 .77 .90 1.00 32.2 9.4 2.61 .78 .93 1.00 30.4 8.9 2.93 .81 .95 1.00

63�F(17�C)

1200 565 37.2 10.9 2.08 .79 .93 1.00 35.6 10.4 2.34 .81 .95 1.00 33.6 9.8 2.62 .83 .98 1.00 31.6 9.3 2.94 .86 1.00 1.00(17�C)

1400 660 38.5 11.3 2.09 .83 .98 1.00 36.6 10.7 2.34 .85 .99 1.00 34.6 10.1 2.63 .87 1.00 1.00 32.8 9.6 2.95 .90 1.00 1.00

67�F1000 470 38.0 11.1 2.08 .60 .73 .85 36.2 10.6 2.34 .61 .74 .87 34.2 10.0 2.63 .62 .76 .89 32.2 9.4 2.95 .64 .78 .92

67�F(19�C)

1200 565 39.5 11.6 2.10 .63 .77 .90 37.4 11.0 2.35 .64 .78 .92 35.4 10.4 2.63 .65 .81 .95 33.2 9.7 2.96 .67 .83 .98(19�C)

1400 660 40.5 11.9 2.10 .65 .80 .95 38.5 11.3 2.36 .66 .83 .97 36.2 10.6 2.64 .68 .85 .99 34.0 10.0 2.96 .70 .88 1.00

71�F1000 470 40.0 11.7 2.10 .47 .59 .70 38.0 11.1 2.36 .47 .60 .72 36.0 10.6 2.64 .48 .61 .73 34.0 10.0 2.97 .48 .62 .76

71�F(22�C)

1200 565 41.5 12.2 2.11 .48 .61 .74 39.5 11.6 2.37 .48 .62 .76 37.4 11.0 2.65 .49 .64 .78 35.2 10.3 2.98 .50 .66 .81(22�C)

1400 660 42.5 12.5 2.12 .49 .64 .78 40.5 11.9 2.38 .50 .65 .80 38.5 11.3 2.66 .50 .67 .83 36.0 10.6 2.98 .51 .69 .86

FIRST STAGE COOLING CAPACITY − XC21−036 with [CR26−48N/W−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 26.4 7.7 1.10 .76 .90 1.00 25.4 7.4 1.29 .78 .92 1.00 24.2 7.1 1.50 .80 .94 1.00 22.8 6.7 1.75 .82 .97 1.00

63�F(17�C)

900 425 27.2 8.0 1.11 .79 .93 1.00 26.0 7.6 1.29 .80 .95 1.00 24.8 7.3 1.50 .82 .98 1.00 23.6 6.9 1.75 .84 1.00 1.00(17�C)

1000 470 27.8 8.1 1.11 .81 .96 1.00 26.6 7.8 1.30 .83 .98 1.00 25.6 7.5 1.51 .85 1.00 1.00 24.2 7.1 1.75 .88 1.00 1.00

67�F800 380 28.2 8.3 1.11 .61 .74 .86 27.2 8.0 1.30 .62 .75 .88 25.8 7.6 1.51 .63 .77 .90 24.4 7.2 1.75 .64 .79 .93

67�F(19�C)

900 425 29.0 8.5 1.12 .63 .76 .89 27.8 8.1 1.30 .64 .78 .91 26.4 7.7 1.51 .65 .79 .94 25.0 7.3 1.76 .66 .82 .97(19�C)

1000 470 29.6 8.7 1.12 .64 .78 .92 28.4 8.3 1.30 .65 .80 .95 27.0 7.9 1.51 .66 .82 .97 25.4 7.4 1.76 .68 .85 1.00

71�F800 380 30.0 8.8 1.12 .47 .60 .71 28.8 8.4 1.31 .47 .60 .73 27.4 8.0 1.51 .48 .62 .74 26.0 7.6 1.76 .49 .63 .76

71�F(22�C)

900 425 30.8 9.0 1.13 .48 .61 .74 29.6 8.7 1.31 .48 .62 .75 28.2 8.3 1.52 .49 .63 .77 26.6 7.8 1.76 .50 .65 .79(22�C)

1000 470 31.4 9.2 1.13 .49 .63 .76 30.2 8.9 1.31 .49 .63 .77 28.6 8.4 1.52 .50 .65 .80 27.2 8.0 1.76 .51 .67 .82

SECOND STAGE COOLING CAPACITY − XC21−036 with [CR26−48N/W−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 35.4 10.4 2.07 .74 .87 .98 33.8 9.9 2.32 .76 .89 1.00 32.0 9.4 2.61 .77 .91 1.00 30.0 8.8 2.93 .79 .94 1.00

63�F(17�C)

1200 565 36.8 10.8 2.08 .77 .91 1.00 35.0 10.3 2.33 .79 .94 1.00 33.2 9.7 2.62 .81 .96 1.00 31.2 9.1 2.94 .83 .99 1.00(17�C)

1400 660 38.0 11.1 2.08 .81 .96 1.00 36.0 10.6 2.34 .82 .98 1.00 34.2 10.0 2.63 .85 1.00 1.00 32.4 9.5 2.95 .88 1.00 1.00

67�F1000 470 37.6 11.0 2.08 .60 .72 .83 35.8 10.5 2.33 .61 .73 .85 34.0 10.0 2.63 .62 .75 .87 32.0 9.4 2.95 .63 .77 .90

67�F(19�C)

1200 565 39.0 11.4 2.09 .62 .75 .88 37.2 10.9 2.35 .63 .77 .90 35.2 10.3 2.63 .64 .79 .93 33.0 9.7 2.95 .66 .81 .96(19�C)

1400 660 40.0 11.7 2.10 .64 .78 .92 38.0 11.1 2.36 .65 .80 .95 36.2 10.6 2.64 .67 .82 .98 33.8 9.9 2.97 .68 .85 1.00

71�F1000 470 40.0 11.7 2.10 .46 .58 .69 38.0 11.1 2.35 .47 .59 .71 36.0 10.6 2.64 .47 .61 .72 33.8 9.9 2.96 .48 .62 .74

71�F(22�C)

1200 565 41.5 12.2 2.11 .48 .61 .73 39.5 11.6 2.36 .48 .62 .74 37.2 10.9 2.65 .49 .63 .76 35.0 10.3 2.97 .50 .65 .79(22�C)

1400 660 42.5 12.5 2.12 .49 .63 .76 40.5 11.9 2.37 .50 .64 .78 38.0 11.1 2.66 .50 .65 .80 35.8 10.5 2.98 .51 .67 .83

Page 65: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 3 TON

DOWN−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 65

FIRST STAGE COOLING CAPACITY − XC21−036 with [CR26−36N−F + G60DFV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F745 350 26.6 7.8 1.11 .75 .88 1.00 25.4 7.4 1.30 .76 .90 1.00 24.2 7.1 1.51 .78 .93 1.00 22.8 6.7 1.76 .80 .95 1.00

63�F(17�C)

860 405 27.6 8.1 1.12 .78 .92 1.00 26.4 7.7 1.30 .80 .94 1.00 25.0 7.3 1.52 .81 .97 1.00 23.6 6.9 1.76 .84 .99 1.00(17�C)

970 460 28.4 8.3 1.12 .81 .96 1.00 27.0 7.9 1.30 .82 .98 1.00 25.6 7.5 1.52 .85 1.00 1.00 24.4 7.2 1.76 .87 1.00 1.00

67�F745 350 28.2 8.3 1.12 .59 .72 .85 27.0 7.9 1.31 .60 .74 .86 25.8 7.6 1.52 .61 .75 .89 24.4 7.2 1.76 .62 .77 .91

67�F(19�C)

860 405 29.2 8.6 1.12 .61 .75 .89 28.0 8.2 1.31 .62 .77 .91 26.6 7.8 1.52 .64 .79 .93 25.0 7.3 1.77 .65 .81 .96(19�C)

970 460 30.0 8.8 1.13 .63 .78 .92 28.6 8.4 1.31 .64 .80 .95 27.2 8.0 1.52 .66 .82 .97 25.6 7.5 1.77 .67 .85 1.00

71�F745 350 30.0 8.8 1.13 .46 .58 .69 28.6 8.4 1.31 .46 .59 .71 27.4 8.0 1.52 .46 .60 .72 25.8 7.6 1.77 .47 .61 .74

71�F(22�C)

860 405 31.0 9.1 1.13 .46 .60 .73 29.6 8.7 1.32 .47 .61 .74 28.2 8.3 1.53 .47 .62 .76 26.6 7.8 1.77 .48 .63 .78(22�C)

970 460 31.8 9.3 1.14 .47 .62 .76 30.4 8.9 1.32 .48 .63 .77 28.8 8.4 1.53 .48 .64 .79 27.2 8.0 1.77 .49 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−036 with [CR26−36N−F + G60DFV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1040 490 36.0 10.6 2.07 .75 .89 1.00 34.4 10.1 2.33 .77 .91 1.00 32.4 9.5 2.61 .79 .93 1.00 30.6 9.0 2.94 .81 .96 1.00

63�F(17�C)

1235 585 37.4 11.0 2.08 .79 .94 1.00 35.6 10.4 2.34 .81 .96 1.00 33.8 9.9 2.62 .83 .98 1.00 31.6 9.3 2.94 .86 1.00 1.00(17�C)

1425 675 38.5 11.3 2.09 .83 .98 1.00 36.8 10.8 2.34 .85 .99 1.00 34.8 10.2 2.63 .87 1.00 1.00 32.8 9.6 2.96 .90 1.00 1.00

67�F1040 490 38.0 11.1 2.09 .60 .73 .85 36.4 10.7 2.34 .61 .74 .87 34.4 10.1 2.63 .62 .76 .90 32.2 9.4 2.95 .63 .78 .93

67�F(19�C)

1235 585 39.5 11.6 2.10 .63 .77 .90 37.6 11.0 2.35 .64 .79 .93 35.6 10.4 2.64 .65 .81 .95 33.2 9.7 2.96 .67 .83 .98(19�C)

1425 675 40.5 11.9 2.10 .65 .81 .95 38.5 11.3 2.36 .66 .83 .97 36.4 10.7 2.64 .68 .85 .99 34.0 10.0 2.97 .70 .88 1.00

71�F1040 490 40.0 11.7 2.10 .46 .59 .70 38.5 11.3 2.35 .47 .60 .72 36.2 10.6 2.64 .47 .61 .74 34.2 10.0 2.97 .48 .62 .76

71�F(22�C)

1235 585 41.5 12.2 2.11 .47 .61 .74 39.5 11.6 2.37 .48 .62 .76 37.4 11.0 2.65 .49 .64 .78 35.2 10.3 2.98 .49 .65 .81(22�C)

1425 675 42.5 12.5 2.12 .49 .64 .78 40.5 11.9 2.38 .49 .65 .80 38.5 11.3 2.66 .50 .67 .83 36.0 10.6 2.98 .51 .69 .86

FIRST STAGE COOLING CAPACITY − XC21−036 with [CR26−48N−F + G60DFV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F745 350 26.0 7.6 1.11 .74 .87 .99 24.8 7.3 1.30 .75 .89 1.00 23.6 6.9 1.51 .77 .91 1.00 22.4 6.6 1.76 .79 .94 1.00

63�F(17�C)

860 405 26.8 7.9 1.11 .77 .90 1.00 25.6 7.5 1.30 .78 .93 1.00 24.4 7.2 1.51 .80 .95 1.00 23.0 6.7 1.76 .82 .98 1.00(17�C)

970 460 27.6 8.1 1.12 .79 .94 1.00 26.4 7.7 1.30 .81 .96 1.00 25.0 7.3 1.51 .83 .99 1.00 24.0 7.0 1.76 .85 1.00 1.00

67�F745 350 27.8 8.1 1.12 .60 .71 .83 26.6 7.8 1.30 .60 .73 .85 25.4 7.4 1.52 .61 .74 .87 24.0 7.0 1.76 .62 .76 .90

67�F(19�C)

860 405 28.6 8.4 1.12 .61 .74 .87 27.4 8.0 1.31 .62 .76 .89 26.0 7.6 1.52 .63 .77 .91 24.6 7.2 1.77 .64 .79 .94(19�C)

970 460 29.4 8.6 1.12 .62 .77 .90 28.0 8.2 1.31 .63 .78 .93 26.8 7.9 1.52 .65 .80 .95 25.2 7.4 1.77 .66 .82 .98

71�F745 350 29.4 8.6 1.12 .45 .58 .69 28.2 8.3 1.31 .45 .59 .70 27.0 7.9 1.52 .46 .60 .71 25.4 7.4 1.77 .46 .61 .73

71�F(22�C)

860 405 30.4 8.9 1.13 .46 .59 .72 29.2 8.6 1.31 .47 .60 .73 27.8 8.1 1.53 .47 .61 .75 26.2 7.7 1.77 .48 .63 .77(22�C)

970 460 31.2 9.1 1.13 .47 .61 .74 29.8 8.7 1.32 .47 .62 .76 28.4 8.3 1.53 .47 .63 .77 26.8 7.9 1.77 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−036 with [CR26−48N−F + G60DFV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1040 490 35.6 10.4 2.07 .74 .87 .99 34.0 10.0 2.32 .76 .89 1.00 32.2 9.4 2.61 .77 .91 1.00 30.2 8.9 2.93 .79 .94 1.00

63�F(17�C)

1235 585 37.0 10.8 2.08 .77 .92 1.00 35.2 10.3 2.33 .79 .94 1.00 33.2 9.7 2.62 .81 .96 1.00 31.2 9.1 2.94 .83 .99 1.00(17�C)

1425 675 38.0 11.1 2.08 .80 .96 1.00 36.0 10.6 2.34 .82 .98 1.00 34.2 10.0 2.63 .85 1.00 1.00 32.4 9.5 2.95 .88 1.00 1.00

67�F1040 490 37.8 11.1 2.08 .60 .72 .83 36.0 10.6 2.34 .61 .73 .85 34.2 10.0 2.63 .62 .75 .88 32.0 9.4 2.95 .63 .77 .91

67�F(19�C)

1235 585 39.0 11.4 2.09 .62 .75 .88 37.2 10.9 2.35 .63 .77 .90 35.2 10.3 2.63 .64 .79 .93 33.0 9.7 2.95 .65 .81 .96(19�C)

1425 675 40.0 11.7 2.10 .64 .78 .92 38.5 11.3 2.36 .65 .80 .95 36.2 10.6 2.64 .66 .82 .98 34.0 10.0 2.97 .68 .85 1.00

71�F1040 490 40.0 11.7 2.10 .45 .58 .69 38.0 11.1 2.36 .45 .59 .71 36.0 10.6 2.64 .46 .60 .72 34.0 10.0 2.96 .47 .62 .74

71�F(22�C)

1235 585 41.5 12.2 2.11 .47 .61 .73 39.5 11.6 2.36 .47 .61 .74 37.4 11.0 2.65 .48 .63 .76 35.0 10.3 2.97 .49 .64 .79(22�C)

1425 675 42.5 12.5 2.12 .48 .63 .76 40.5 11.9 2.37 .49 .64 .78 38.0 11.1 2.66 .50 .65 .80 36.0 10.6 2.98 .51 .67 .83

Page 66: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 3 TON

HORIZONTAL INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 66

FIRST STAGE COOLING CAPACITY − XC21−036 with [CH23−41]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 26.0 7.6 1.10 .76 .90 1.00 24.8 7.3 1.29 .78 .92 1.00 23.6 6.9 1.50 .80 .94 1.00 22.4 6.6 1.74 .82 .97 1.00

63�F(17�C)

900 425 26.6 7.8 1.11 .79 .93 1.00 25.6 7.5 1.29 .80 .95 1.00 24.4 7.2 1.50 .82 .97 1.00 23.2 6.8 1.75 .85 .99 1.00(17�C)

1000 470 27.4 8.0 1.11 .81 .96 1.00 26.4 7.7 1.29 .83 .98 1.00 25.2 7.4 1.50 .85 1.00 1.00 24.0 7.0 1.75 .88 1.00 1.00

67�F800 380 27.8 8.1 1.11 .61 .74 .86 26.8 7.9 1.30 .62 .75 .88 25.4 7.4 1.51 .63 .77 .91 24.0 7.0 1.75 .65 .79 .94

67�F(19�C)

900 425 28.6 8.4 1.12 .63 .76 .90 27.4 8.0 1.30 .64 .78 .92 26.2 7.7 1.51 .65 .80 .94 24.6 7.2 1.75 .66 .82 .97(19�C)

1000 470 29.2 8.6 1.12 .64 .79 .93 28.0 8.2 1.30 .65 .80 .95 26.6 7.8 1.51 .67 .83 .97 25.0 7.3 1.76 .68 .85 .99

71�F800 380 29.8 8.7 1.12 .47 .60 .71 28.6 8.4 1.31 .48 .61 .73 27.2 8.0 1.51 .48 .62 .74 25.8 7.6 1.76 .49 .63 .76

71�F(22�C)

900 425 30.6 9.0 1.13 .48 .61 .74 29.4 8.6 1.31 .48 .62 .75 28.0 8.2 1.52 .49 .63 .77 26.4 7.7 1.76 .50 .65 .80(22�C)

1000 470 31.2 9.1 1.13 .49 .62 .76 30.0 8.8 1.31 .49 .64 .78 28.6 8.4 1.52 .50 .65 .80 27.0 7.9 1.76 .51 .67 .83

SECOND STAGE COOLING CAPACITY − XC21−036 with [CH23−41]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 34.8 10.2 2.06 .74 .87 .98 33.2 9.7 2.31 .76 .89 .99 31.4 9.2 2.60 .78 .91 1.00 29.6 8.7 2.93 .80 .94 1.00

63�F(17�C)

1200 565 36.2 10.6 2.07 .78 .92 1.00 34.6 10.1 2.33 .80 .94 1.00 32.8 9.6 2.61 .82 .97 1.00 30.8 9.0 2.94 .84 .99 1.00(17�C)

1400 660 37.4 11.0 2.08 .81 .96 1.00 35.8 10.5 2.34 .83 .98 1.00 34.0 10.0 2.62 .86 1.00 1.00 32.2 9.4 2.95 .89 1.00 1.00

67�F1000 470 37.2 10.9 2.08 .60 .72 .84 35.4 10.4 2.34 .61 .73 .86 33.6 9.8 2.62 .62 .75 .88 31.6 9.3 2.95 .63 .77 .91

67�F(19�C)

1200 565 38.5 11.3 2.09 .62 .76 .89 36.8 10.8 2.34 .63 .77 .91 34.8 10.2 2.63 .65 .79 .94 32.8 9.6 2.95 .66 .82 .97(19�C)

1400 660 40.0 11.7 2.10 .64 .79 .93 38.0 11.1 2.35 .66 .81 .96 35.8 10.5 2.64 .67 .83 .98 33.6 9.8 2.96 .69 .86 1.00

71�F1000 470 39.5 11.6 2.10 .47 .59 .70 37.6 11.0 2.35 .47 .60 .71 35.8 10.5 2.64 .48 .61 .73 33.6 9.8 2.96 .48 .62 .75

71�F(22�C)

1200 565 41.0 12.0 2.11 .48 .61 .73 39.0 11.4 2.36 .48 .62 .75 37.0 10.8 2.65 .49 .63 .77 34.8 10.2 2.97 .50 .65 .80(22�C)

1400 660 42.0 12.3 2.12 .49 .63 .77 40.0 11.7 2.37 .49 .64 .79 38.0 11.1 2.66 .50 .66 .81 35.8 10.5 2.98 .51 .68 .84

FIRST STAGE COOLING CAPACITY − XC21−036 with [CH23−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 26.8 7.9 1.11 .77 .91 1.00 25.6 7.5 1.29 .78 .93 1.00 24.4 7.2 1.50 .80 .95 1.00 23.0 6.7 1.75 .82 .98 1.00

63�F(17�C)

900 425 27.6 8.1 1.11 .79 .94 1.00 26.4 7.7 1.29 .81 .96 1.00 25.2 7.4 1.50 .83 .98 1.00 23.8 7.0 1.75 .86 1.00 1.00(17�C)

1000 470 28.4 8.3 1.11 .82 .97 1.00 27.2 8.0 1.30 .84 .99 1.00 26.0 7.6 1.51 .86 1.00 1.00 24.8 7.3 1.75 .89 1.00 1.00

67�F800 380 28.6 8.4 1.12 .61 .74 .87 27.6 8.1 1.30 .62 .76 .89 26.2 7.7 1.51 .63 .77 .92 24.6 7.2 1.75 .65 .80 .94

67�F(19�C)

900 425 29.4 8.6 1.12 .63 .77 .91 28.2 8.3 1.30 .64 .78 .93 26.8 7.9 1.51 .65 .80 .95 25.4 7.4 1.76 .67 .83 .98(19�C)

1000 470 30.2 8.9 1.13 .64 .79 .94 28.8 8.4 1.31 .66 .81 .96 27.4 8.0 1.51 .67 .83 .98 25.8 7.6 1.76 .68 .86 1.00

71�F800 380 30.4 8.9 1.13 .47 .60 .72 29.2 8.6 1.31 .47 .61 .73 27.8 8.1 1.52 .47 .62 .75 26.2 7.7 1.76 .48 .63 .77

71�F(22�C)

900 425 31.2 9.1 1.13 .48 .61 .74 30.0 8.8 1.31 .48 .62 .76 28.6 8.4 1.52 .48 .64 .78 27.0 7.9 1.76 .49 .65 .80(22�C)

1000 470 32.0 9.4 1.14 .49 .63 .77 30.6 9.0 1.32 .49 .64 .79 29.0 8.5 1.52 .50 .66 .81 27.4 8.0 1.76 .50 .67 .83

SECOND STAGE COOLING CAPACITY − XC21−036 with [CH23−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 36.0 10.6 2.07 .75 .87 .99 34.2 10.0 2.32 .76 .89 1.00 32.4 9.5 2.61 .78 .92 1.00 30.4 8.9 2.93 .80 .95 1.00

63�F(17�C)

1200 565 37.4 11.0 2.08 .78 .93 1.00 35.6 10.4 2.34 .80 .95 1.00 33.6 9.8 2.62 .82 .97 1.00 31.6 9.3 2.94 .85 .99 1.00(17�C)

1400 660 38.5 11.3 2.09 .82 .97 1.00 36.8 10.8 2.35 .84 .99 1.00 35.0 10.3 2.63 .86 1.00 1.00 33.0 9.7 2.96 .90 1.00 1.00

67�F1000 470 38.0 11.1 2.09 .60 .72 .84 36.4 10.7 2.34 .61 .73 .86 34.4 10.1 2.63 .62 .75 .88 32.2 9.4 2.95 .63 .78 .92

67�F(19�C)

1200 565 39.5 11.6 2.10 .62 .76 .89 37.8 11.1 2.35 .63 .77 .92 35.6 10.4 2.64 .65 .80 .94 33.4 9.8 2.96 .66 .82 .97(19�C)

1400 660 41.0 12.0 2.11 .64 .79 .94 39.0 11.4 2.36 .66 .81 .96 36.6 10.7 2.65 .67 .84 .99 34.2 10.0 2.96 .69 .87 1.00

71�F1000 470 40.0 11.7 2.10 .46 .59 .70 38.5 11.3 2.36 .47 .59 .71 36.4 10.7 2.64 .47 .61 .73 34.2 10.0 2.97 .48 .62 .75

71�F(22�C)

1200 565 42.0 12.3 2.12 .47 .61 .73 40.0 11.7 2.37 .48 .62 .75 37.8 11.1 2.66 .49 .63 .77 35.4 10.4 2.98 .49 .65 .80(22�C)

1400 660 43.0 12.6 2.13 .49 .63 .77 41.0 12.0 2.38 .50 .64 .79 38.5 11.3 2.66 .50 .66 .82 36.4 10.7 2.99 .51 .68 .85

Page 67: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 3 TON

HORIZONTAL INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 67

FIRST STAGE COOLING CAPACITY − XC21−036 with [CH33−36A/B/C−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 26.6 7.8 1.10 .76 .90 1.00 25.4 7.4 1.29 .78 .92 1.00 24.2 7.1 1.50 .80 .94 1.00 22.8 6.7 1.74 .82 .97 1.00

63�F(17�C)

900 425 27.4 8.0 1.11 .79 .93 1.00 26.2 7.7 1.29 .81 .95 1.00 24.8 7.3 1.51 .82 .98 1.00 23.4 6.9 1.75 .85 1.00 1.00(17�C)

1000 470 28.0 8.2 1.11 .81 .96 1.00 26.8 7.9 1.30 .83 .98 1.00 25.4 7.4 1.51 .84 1.00 1.00 24.0 7.0 1.75 .88 1.00 1.00

67�F800 380 28.4 8.3 1.11 .61 .74 .86 27.0 7.9 1.30 .61 .75 .88 25.8 7.6 1.51 .63 .77 .91 24.4 7.2 1.75 .64 .79 .93

67�F(19�C)

900 425 29.0 8.5 1.12 .62 .76 .90 27.8 8.1 1.30 .63 .78 .92 26.4 7.7 1.51 .65 .80 .94 25.0 7.3 1.76 .66 .82 .97(19�C)

1000 470 29.8 8.7 1.12 .64 .78 .93 28.4 8.3 1.30 .65 .80 .95 27.0 7.9 1.51 .66 .82 .97 25.4 7.4 1.76 .68 .85 1.00

71�F800 380 30.0 8.8 1.13 .47 .59 .71 28.8 8.4 1.31 .47 .60 .72 27.4 8.0 1.51 .48 .61 .74 26.0 7.6 1.76 .49 .62 .76

71�F(22�C)

900 425 31.0 9.1 1.13 .48 .61 .73 29.6 8.7 1.31 .48 .62 .75 28.2 8.3 1.52 .49 .63 .77 26.6 7.8 1.76 .49 .65 .79(22�C)

1000 470 31.6 9.3 1.13 .49 .62 .76 30.2 8.9 1.31 .49 .64 .78 28.8 8.4 1.52 .50 .65 .80 27.0 7.9 1.76 .50 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−036 with [CH33−36A/B/C−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 35.0 10.3 2.06 .74 .86 .98 33.4 9.8 2.32 .75 .88 1.00 31.6 9.3 2.60 .77 .91 1.00 29.8 8.7 2.93 .79 .94 1.00

63�F(17�C)

1200 565 36.4 10.7 2.07 .78 .91 1.00 34.6 10.1 2.33 .79 .94 1.00 32.8 9.6 2.61 .81 .96 1.00 30.8 9.0 2.93 .84 .99 1.00(17�C)

1400 660 37.6 11.0 2.08 .81 .96 1.00 35.8 10.5 2.34 .82 .98 1.00 33.8 9.9 2.62 .85 1.00 1.00 31.8 9.3 2.94 .88 1.00 1.00

67�F1000 470 37.2 10.9 2.08 .60 .72 .83 35.4 10.4 2.33 .61 .73 .85 33.6 9.8 2.62 .61 .75 .87 31.6 9.3 2.94 .63 .77 .90

67�F(19�C)

1200 565 38.5 11.3 2.09 .62 .75 .88 36.8 10.8 2.34 .63 .76 .90 34.8 10.2 2.63 .64 .78 .93 32.8 9.6 2.95 .65 .81 .96(19�C)

1400 660 40.0 11.7 2.10 .64 .78 .93 37.8 11.1 2.35 .65 .80 .95 35.8 10.5 2.64 .66 .83 .98 33.4 9.8 2.96 .68 .85 1.00

71�F1000 470 39.5 11.6 2.09 .47 .58 .69 37.6 11.0 2.35 .47 .59 .70 35.6 10.4 2.63 .48 .60 .72 33.4 9.8 2.96 .48 .61 .74

71�F(22�C)

1200 565 41.0 12.0 2.11 .48 .60 .73 39.0 11.4 2.36 .48 .61 .74 36.8 10.8 2.65 .49 .62 .76 34.6 10.1 2.97 .49 .64 .78(22�C)

1400 660 42.0 12.3 2.12 .49 .62 .76 40.0 11.7 2.37 .49 .63 .78 37.8 11.1 2.65 .50 .65 .80 35.6 10.4 2.98 .51 .67 .83

FIRST STAGE COOLING CAPACITY − XC21−036 with [CH33−42B−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 27.2 8.0 1.11 .76 .90 1.00 26.0 7.6 1.29 .78 .92 1.00 24.8 7.3 1.50 .80 .95 1.00 23.4 6.9 1.75 .82 .98 1.00

63�F(17�C)

900 425 28.0 8.2 1.11 .79 .94 1.00 26.8 7.9 1.30 .81 .96 1.00 25.4 7.4 1.51 .83 .98 1.00 24.0 7.0 1.75 .85 1.00 1.00(17�C)

1000 470 28.8 8.4 1.12 .81 .97 1.00 27.4 8.0 1.30 .83 .99 1.00 26.0 7.6 1.51 .85 1.00 1.00 24.8 7.3 1.75 .88 1.00 1.00

67�F800 380 29.0 8.5 1.12 .61 .74 .86 27.8 8.1 1.30 .62 .75 .88 26.4 7.7 1.51 .63 .77 .91 24.8 7.3 1.75 .64 .79 .94

67�F(19�C)

900 425 29.8 8.7 1.12 .63 .76 .90 28.4 8.3 1.30 .64 .78 .92 27.0 7.9 1.51 .65 .80 .95 25.6 7.5 1.76 .66 .83 .98(19�C)

1000 470 30.4 8.9 1.13 .64 .79 .93 29.0 8.5 1.31 .65 .81 .95 27.6 8.1 1.52 .66 .83 .98 26.0 7.6 1.76 .67 .85 1.00

71�F800 380 30.8 9.0 1.13 .47 .59 .71 29.4 8.6 1.31 .48 .60 .72 28.0 8.2 1.52 .48 .61 .74 26.6 7.8 1.76 .49 .63 .76

71�F(22�C)

900 425 31.6 9.3 1.13 .48 .61 .74 30.2 8.9 1.32 .49 .62 .75 28.8 8.4 1.52 .49 .63 .77 27.2 8.0 1.76 .50 .65 .79(22�C)

1000 470 32.4 9.5 1.14 .49 .63 .76 30.8 9.0 1.32 .49 .64 .78 29.4 8.6 1.52 .50 .65 .80 27.8 8.1 1.77 .50 .67 .82

SECOND STAGE COOLING CAPACITY − XC21−036 with [CH33−42B−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 36.2 10.6 2.07 .74 .86 .98 34.4 10.1 2.33 .75 .88 1.00 32.6 9.6 2.61 .77 .91 1.00 30.6 9.0 2.93 .79 .94 1.00

63�F(17�C)

1200 565 37.6 11.0 2.08 .77 .92 1.00 35.8 10.5 2.34 .79 .94 1.00 33.8 9.9 2.62 .81 .97 1.00 31.8 9.3 2.95 .84 1.00 1.00(17�C)

1400 660 39.0 11.4 2.09 .81 .96 1.00 37.0 10.8 2.35 .83 .99 1.00 34.8 10.2 2.63 .85 1.00 1.00 33.0 9.7 2.96 .88 1.00 1.00

67�F1000 470 38.5 11.3 2.09 .59 .72 .83 36.6 10.7 2.34 .60 .73 .85 34.6 10.1 2.63 .61 .74 .87 32.6 9.6 2.95 .63 .77 .90

67�F(19�C)

1200 565 40.0 11.7 2.10 .62 .75 .88 38.0 11.1 2.35 .63 .77 .90 35.8 10.5 2.64 .64 .79 .93 33.6 9.8 2.96 .66 .81 .96(19�C)

1400 660 41.0 12.0 2.11 .64 .79 .93 39.0 11.4 2.36 .65 .81 .95 36.8 10.8 2.65 .67 .83 .98 34.4 10.1 2.97 .69 .86 1.00

71�F1000 470 40.5 11.9 2.11 .47 .58 .69 38.5 11.3 2.36 .47 .59 .70 36.6 10.7 2.65 .47 .60 .72 34.4 10.1 2.97 .48 .61 .74

71�F(22�C)

1200 565 42.0 12.3 2.12 .48 .60 .73 40.0 11.7 2.37 .48 .61 .74 38.0 11.1 2.66 .49 .63 .76 35.6 10.4 2.98 .49 .64 .79(22�C)

1400 660 43.5 12.7 2.13 .49 .63 .76 41.5 12.2 2.38 .49 .64 .78 39.0 11.4 2.66 .50 .65 .80 36.6 10.7 2.99 .51 .67 .83

Page 68: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 3 TON

HORIZONTAL INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 68

FIRST STAGE COOLING CAPACITY − XC21−036 with [CH33−44/48B−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 27.6 8.1 1.11 .77 .91 1.00 26.4 7.7 1.29 .79 .93 1.00 25.0 7.3 1.50 .80 .95 1.00 23.6 6.9 1.75 .83 .98 1.00

63�F(17�C)

900 425 28.4 8.3 1.12 .80 .94 1.00 27.2 8.0 1.30 .81 .96 1.00 25.8 7.6 1.51 .83 .99 1.00 24.4 7.2 1.75 .86 1.00 1.00(17�C)

1000 470 29.0 8.5 1.12 .82 .97 1.00 27.8 8.1 1.30 .84 .99 1.00 26.4 7.7 1.51 .86 1.00 1.00 25.2 7.4 1.76 .89 1.00 1.00

67�F800 380 29.4 8.6 1.12 .62 .74 .87 28.2 8.3 1.30 .62 .76 .89 26.8 7.9 1.51 .63 .78 .91 25.2 7.4 1.76 .65 .80 .94

67�F(19�C)

900 425 30.2 8.9 1.13 .63 .76 .90 28.8 8.4 1.31 .64 .78 .93 27.4 8.0 1.52 .65 .80 .95 25.8 7.6 1.76 .66 .83 .98(19�C)

1000 470 31.0 9.1 1.13 .65 .79 .94 29.6 8.7 1.31 .65 .81 .96 28.0 8.2 1.52 .66 .82 .99 26.4 7.7 1.76 .69 .86 1.00

71�F800 380 31.2 9.1 1.13 .47 .60 .71 29.8 8.7 1.31 .48 .61 .73 28.4 8.3 1.52 .48 .62 .75 26.8 7.9 1.76 .49 .63 .77

71�F(22�C)

900 425 32.0 9.4 1.14 .48 .61 .74 30.6 9.0 1.32 .49 .62 .76 29.2 8.6 1.52 .49 .63 .77 27.4 8.0 1.76 .50 .65 .80(22�C)

1000 470 32.8 9.6 1.14 .49 .63 .77 31.2 9.1 1.32 .49 .63 .79 29.8 8.7 1.53 .50 .65 .80 28.0 8.2 1.77 .50 .67 .83

SECOND STAGE COOLING CAPACITY − XC21−036 with [CH33−44/48B−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 36.8 10.8 2.07 .74 .87 .99 35.0 10.3 2.33 .76 .89 1.00 33.2 9.7 2.61 .78 .92 1.00 31.0 9.1 2.94 .80 .95 1.00

63�F(17�C)

1200 565 38.5 11.3 2.09 .78 .92 1.00 36.4 10.7 2.34 .80 .95 1.00 34.4 10.1 2.63 .82 .97 1.00 32.2 9.4 2.95 .84 1.00 1.00(17�C)

1400 660 39.5 11.6 2.10 .82 .97 1.00 37.6 11.0 2.35 .83 .99 1.00 35.6 10.4 2.64 .86 1.00 1.00 33.6 9.8 2.96 .89 1.00 1.00

67�F1000 470 39.0 11.4 2.09 .60 .72 .84 37.2 10.9 2.35 .60 .73 .85 35.2 10.3 2.63 .62 .75 .88 33.0 9.7 2.95 .63 .77 .91

67�F(19�C)

1200 565 40.5 11.9 2.10 .62 .76 .89 38.5 11.3 2.36 .63 .77 .91 36.4 10.7 2.64 .64 .79 .94 34.2 10.0 2.96 .66 .82 .97(19�C)

1400 660 41.5 12.2 2.11 .64 .79 .94 39.5 11.6 2.37 .65 .81 .96 37.6 11.0 2.65 .67 .83 .99 35.2 10.3 2.98 .69 .86 1.00

71�F1000 470 41.0 12.0 2.11 .47 .58 .70 39.0 11.4 2.36 .47 .59 .71 37.2 10.9 2.65 .47 .60 .73 35.0 10.3 2.98 .48 .62 .75

71�F(22�C)

1200 565 43.0 12.6 2.12 .47 .60 .73 41.0 12.0 2.38 .48 .62 .75 38.5 11.3 2.66 .49 .63 .76 36.2 10.6 2.98 .50 .65 .79(22�C)

1400 660 44.0 12.9 2.13 .49 .63 .77 42.0 12.3 2.39 .49 .64 .79 39.5 11.6 2.67 .50 .65 .81 37.0 10.8 2.99 .51 .67 .84

Page 69: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 3 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 69

FIRST STAGE COOLING CAPACITY − XC21−036 with [CH33−36A−2F + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F745 350 26.0 7.6 1.11 .74 .87 .99 24.8 7.3 1.30 .75 .89 1.00 23.6 6.9 1.51 .77 .91 1.00 22.4 6.6 1.76 .79 .94 1.00

63�F(17�C)

850 400 26.8 7.9 1.11 .77 .91 1.00 25.6 7.5 1.30 .78 .93 1.00 24.4 7.2 1.51 .80 .95 1.00 23.0 6.7 1.76 .82 .98 1.00(17�C)

910 430 27.4 8.0 1.11 .78 .93 1.00 26.0 7.6 1.30 .80 .95 1.00 24.8 7.3 1.51 .82 .97 1.00 23.4 6.9 1.76 .84 1.00 1.00

67�F745 350 27.8 8.1 1.12 .59 .72 .83 26.6 7.8 1.30 .60 .73 .85 25.4 7.4 1.52 .61 .74 .87 24.0 7.0 1.76 .62 .76 .90

67�F(19�C)

850 400 28.6 8.4 1.12 .61 .74 .87 27.4 8.0 1.31 .61 .76 .89 26.0 7.6 1.52 .63 .77 .91 24.6 7.2 1.77 .64 .79 .94(19�C)

910 430 29.2 8.6 1.12 .61 .75 .89 27.8 8.1 1.31 .63 .77 .91 26.4 7.7 1.52 .64 .79 .94 25.0 7.3 1.77 .65 .81 .97

71�F745 350 29.6 8.7 1.13 .46 .58 .69 28.2 8.3 1.31 .46 .58 .70 27.0 7.9 1.52 .46 .59 .71 25.4 7.4 1.77 .47 .60 .73

71�F(22�C)

850 400 30.4 8.9 1.13 .47 .59 .71 29.2 8.6 1.31 .46 .60 .72 27.8 8.1 1.53 .47 .61 .75 26.2 7.7 1.77 .48 .63 .77(22�C)

910 430 31.0 9.1 1.13 .47 .60 .73 29.6 8.7 1.32 .47 .60 .74 28.2 8.3 1.53 .48 .62 .76 26.6 7.8 1.77 .48 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−036 with [CH33−36A−2F + G60UHV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1035 490 35.2 10.3 2.06 .74 .87 .99 33.6 9.8 2.32 .76 .89 1.00 31.8 9.3 2.61 .77 .91 1.00 29.8 8.7 2.93 .79 .94 1.00

63�F(17�C)

1230 580 36.6 10.7 2.07 .78 .92 1.00 34.8 10.2 2.33 .79 .94 1.00 33.0 9.7 2.62 .81 .97 1.00 31.0 9.1 2.93 .84 1.00 1.00(17�C)

1375 650 37.4 11.0 2.08 .80 .95 1.00 35.6 10.4 2.34 .82 .97 1.00 33.8 9.9 2.62 .84 1.00 1.00 31.6 9.3 2.94 .87 1.00 1.00

67�F1035 490 37.4 11.0 2.08 .60 .72 .84 35.6 10.4 2.34 .61 .73 .85 33.8 9.9 2.62 .61 .75 .88 31.8 9.3 2.95 .63 .77 .91

67�F(19�C)

1230 580 39.0 11.4 2.09 .62 .75 .88 37.0 10.8 2.34 .63 .77 .91 35.0 10.3 2.63 .64 .79 .93 32.8 9.6 2.95 .65 .81 .97(19�C)

1375 650 39.5 11.6 2.10 .63 .78 .92 37.8 11.1 2.35 .65 .80 .94 35.6 10.4 2.64 .66 .82 .97 33.4 9.8 2.96 .68 .85 1.00

71�F1035 490 39.5 11.6 2.10 .47 .58 .69 37.8 11.1 2.35 .47 .59 .71 35.8 10.5 2.64 .47 .60 .72 33.6 9.8 2.96 .48 .61 .74

71�F(22�C)

1230 580 41.0 12.0 2.11 .47 .60 .73 39.0 11.4 2.36 .48 .61 .74 37.0 10.8 2.65 .48 .63 .76 34.8 10.2 2.97 .49 .64 .79(22�C)

1375 650 42.0 12.3 2.11 .48 .62 .75 40.0 11.7 2.37 .49 .63 .77 37.6 11.0 2.65 .49 .65 .79 35.4 10.4 2.98 .50 .66 .82

FIRST STAGE COOLING CAPACITY − XC21−036 with [CH33−36A−2F + G61MPV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F710 335 25.8 7.6 1.11 .73 .86 .98 24.6 7.2 1.29 .75 .88 1.00 23.4 6.9 1.51 .76 .90 1.00 22.0 6.4 1.76 .78 .93 1.00

63�F(17�C)

815 385 26.6 7.8 1.11 .76 .89 1.00 25.4 7.4 1.30 .77 .92 1.00 24.2 7.1 1.51 .79 .94 1.00 22.8 6.7 1.76 .81 .97 1.00(17�C)

875 415 27.0 7.9 1.11 .77 .92 1.00 25.8 7.6 1.30 .79 .94 1.00 24.6 7.2 1.51 .81 .96 1.00 23.2 6.8 1.76 .83 .99 1.00

67�F710 335 27.4 8.0 1.12 .59 .71 .82 26.4 7.7 1.30 .59 .72 .84 25.0 7.3 1.52 .60 .73 .86 23.6 6.9 1.76 .61 .75 .89

67�F(19�C)

815 385 28.4 8.3 1.12 .60 .73 .86 27.2 8.0 1.31 .61 .74 .88 25.8 7.6 1.52 .62 .76 .90 24.4 7.2 1.76 .63 .79 .93(19�C)

875 415 28.8 8.4 1.12 .61 .75 .88 27.6 8.1 1.31 .62 .76 .90 26.2 7.7 1.52 .63 .78 .92 24.8 7.3 1.77 .65 .80 .95

71�F710 335 29.2 8.6 1.12 .46 .57 .68 28.0 8.2 1.31 .46 .58 .69 26.6 7.8 1.52 .46 .59 .71 25.2 7.4 1.77 .47 .60 .72

71�F(22�C)

815 385 30.2 8.9 1.13 .46 .59 .71 28.8 8.4 1.31 .46 .59 .72 27.6 8.1 1.53 .47 .61 .74 26.0 7.6 1.77 .48 .62 .76(22�C)

875 415 30.6 9.0 1.13 .47 .60 .72 29.4 8.6 1.32 .47 .60 .74 28.0 8.2 1.53 .48 .62 .75 26.4 7.7 1.77 .48 .63 .78

SECOND STAGE COOLING CAPACITY − XC21−036 with [CH33−36A−2F + G61MPV−36A−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F995 470 35.0 10.3 2.06 .74 .86 .98 33.2 9.7 2.32 .75 .88 1.00 31.6 9.3 2.60 .77 .90 1.00 29.6 8.7 2.93 .79 .93 1.00

63�F(17�C)

1190 560 36.4 10.7 2.07 .77 .91 1.00 34.6 10.1 2.33 .78 .93 1.00 32.8 9.6 2.61 .81 .96 1.00 30.6 9.0 2.94 .83 .99 1.00(17�C)

1335 630 37.2 10.9 2.08 .79 .94 1.00 35.4 10.4 2.33 .81 .97 1.00 33.4 9.8 2.62 .84 .99 1.00 31.4 9.2 2.94 .86 1.00 1.00

67�F995 470 37.2 10.9 2.08 .59 .71 .83 35.4 10.4 2.33 .60 .72 .84 33.6 9.8 2.62 .61 .74 .87 31.6 9.3 2.94 .62 .76 .90

67�F(19�C)

1190 560 38.5 11.3 2.09 .61 .75 .87 36.8 10.8 2.34 .62 .76 .90 34.8 10.2 2.63 .63 .78 .92 32.6 9.6 2.95 .65 .80 .96(19�C)

1335 630 39.5 11.6 2.10 .63 .77 .91 37.6 11.0 2.35 .64 .79 .93 35.6 10.4 2.64 .66 .81 .96 33.2 9.7 2.96 .67 .84 .99

71�F995 470 39.0 11.4 2.09 .46 .58 .69 37.4 11.0 2.35 .47 .59 .70 35.4 10.4 2.63 .47 .59 .72 33.4 9.8 2.96 .48 .61 .74

71�F(22�C)

1190 560 40.5 11.9 2.11 .47 .60 .72 39.0 11.4 2.36 .48 .61 .74 36.8 10.8 2.65 .48 .62 .76 34.6 10.1 2.97 .49 .64 .78(22�C)

1335 630 41.5 12.2 2.11 .48 .62 .75 39.5 11.6 2.36 .49 .63 .76 37.6 11.0 2.65 .49 .64 .79 35.2 10.3 2.98 .50 .66 .81

Page 70: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 3 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 70

FIRST STAGE COOLING CAPACITY − XC21−036 with [CH33−36B−2F + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F740 350 26.0 7.6 1.11 .74 .87 .99 24.8 7.3 1.30 .75 .89 1.00 23.6 6.9 1.51 .77 .91 1.00 22.2 6.5 1.76 .79 .94 1.00

63�F(17�C)

840 395 26.8 7.9 1.11 .76 .90 1.00 25.6 7.5 1.30 .78 .92 1.00 24.4 7.2 1.51 .80 .95 1.00 23.0 6.7 1.76 .82 .98 1.00(17�C)

920 435 27.4 8.0 1.11 .78 .93 1.00 26.2 7.7 1.30 .80 .95 1.00 24.8 7.3 1.51 .82 .97 1.00 23.4 6.9 1.76 .84 1.00 1.00

67�F740 350 27.8 8.1 1.12 .59 .71 .83 26.6 7.8 1.30 .60 .72 .85 25.2 7.4 1.52 .61 .74 .87 23.8 7.0 1.76 .62 .76 .90

67�F(19�C)

840 395 28.6 8.4 1.12 .60 .73 .86 27.4 8.0 1.31 .61 .75 .88 26.0 7.6 1.52 .62 .77 .91 24.6 7.2 1.77 .64 .79 .94(19�C)

920 435 29.2 8.6 1.12 .61 .75 .89 27.8 8.1 1.31 .62 .77 .91 26.4 7.7 1.52 .64 .79 .94 25.0 7.3 1.77 .65 .81 .97

71�F740 350 29.4 8.6 1.12 .46 .57 .69 28.2 8.3 1.31 .46 .58 .70 26.8 7.9 1.52 .46 .59 .71 25.4 7.4 1.77 .47 .60 .73

71�F(22�C)

840 395 30.4 8.9 1.13 .46 .59 .71 29.0 8.5 1.31 .46 .59 .72 27.6 8.1 1.53 .47 .61 .74 26.2 7.7 1.77 .47 .62 .76(22�C)

920 435 31.0 9.1 1.13 .46 .60 .73 29.6 8.7 1.32 .47 .61 .74 28.2 8.3 1.53 .47 .63 .76 26.6 7.8 1.77 .48 .64 .78

SECOND STAGE COOLING CAPACITY − XC21−036 with [CH33−36B−2F + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1035 490 35.2 10.3 2.06 .74 .87 .99 33.6 9.8 2.32 .75 .89 1.00 31.8 9.3 2.61 .77 .91 1.00 29.8 8.7 2.93 .79 .94 1.00

63�F(17�C)

1225 580 36.4 10.7 2.07 .77 .91 1.00 34.6 10.1 2.33 .79 .94 1.00 32.8 9.6 2.62 .81 .96 1.00 30.8 9.0 2.93 .83 .99 1.00(17�C)

1385 655 37.4 11.0 2.08 .80 .95 1.00 35.6 10.4 2.33 .82 .97 1.00 33.6 9.8 2.62 .84 1.00 1.00 31.6 9.3 2.94 .87 1.00 1.00

67�F1035 490 37.4 11.0 2.08 .59 .72 .83 35.6 10.4 2.34 .60 .73 .85 33.8 9.9 2.62 .61 .75 .88 31.8 9.3 2.95 .62 .77 .91

67�F(19�C)

1225 580 38.5 11.3 2.09 .61 .75 .88 36.8 10.8 2.34 .62 .76 .90 34.8 10.2 2.63 .64 .78 .93 32.8 9.6 2.95 .65 .81 .96(19�C)

1385 655 39.5 11.6 2.10 .63 .77 .92 37.6 11.0 2.35 .64 .79 .94 35.6 10.4 2.63 .65 .82 .97 33.4 9.8 2.96 .67 .84 1.00

71�F1035 490 39.5 11.6 2.10 .46 .58 .69 37.6 11.0 2.35 .47 .59 .71 35.6 10.4 2.64 .47 .60 .72 33.6 9.8 2.96 .47 .61 .74

71�F(22�C)

1225 580 41.0 12.0 2.11 .47 .60 .72 39.0 11.4 2.36 .48 .61 .74 36.8 10.8 2.65 .48 .62 .76 34.6 10.1 2.97 .49 .64 .78(22�C)

1385 655 42.0 12.3 2.11 .48 .62 .75 40.0 11.7 2.37 .48 .63 .77 37.6 11.0 2.65 .49 .64 .79 35.4 10.4 2.98 .50 .66 .82

FIRST STAGE COOLING CAPACITY − XC21−036 with [CH33−36B−2F + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F695 330 25.8 7.6 1.11 .74 .87 .98 24.6 7.2 1.29 .75 .88 1.00 23.4 6.9 1.51 .77 .90 1.00 22.2 6.5 1.76 .79 .93 1.00

63�F(17�C)

815 385 26.8 7.9 1.11 .77 .91 1.00 25.6 7.5 1.30 .78 .93 1.00 24.4 7.2 1.51 .80 .96 1.00 23.0 6.7 1.76 .82 .98 1.00(17�C)

935 440 27.6 8.1 1.11 .80 .95 1.00 26.6 7.8 1.30 .82 .97 1.00 25.2 7.4 1.52 .84 .99 1.00 24.0 7.0 1.76 .86 1.00 1.00

67�F695 330 27.2 8.0 1.11 .60 .71 .83 26.0 7.6 1.30 .60 .73 .85 24.8 7.3 1.51 .61 .74 .87 23.4 6.9 1.76 .62 .76 .89

67�F(19�C)

815 385 28.4 8.3 1.12 .61 .74 .87 27.2 8.0 1.30 .62 .76 .89 25.8 7.6 1.52 .63 .78 .92 24.4 7.2 1.76 .64 .80 .95(19�C)

935 440 29.2 8.6 1.12 .63 .77 .91 28.0 8.2 1.31 .64 .79 .94 26.6 7.8 1.52 .65 .81 .96 25.0 7.3 1.77 .67 .84 .99

71�F695 330 28.4 8.3 1.12 .46 .58 .69 27.2 8.0 1.31 .46 .59 .70 26.0 7.6 1.52 .47 .59 .72 24.6 7.2 1.77 .47 .61 .73

71�F(22�C)

815 385 29.6 8.7 1.12 .47 .60 .72 28.4 8.3 1.31 .47 .61 .73 27.2 8.0 1.52 .48 .62 .75 25.6 7.5 1.77 .48 .63 .77(22�C)

935 440 30.8 9.0 1.13 .48 .62 .75 29.4 8.6 1.32 .48 .63 .77 28.0 8.2 1.53 .49 .64 .78 26.6 7.8 1.77 .49 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−036 with [CH33−36B−2F + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F950 450 34.8 10.2 2.07 .74 .86 .98 33.2 9.7 2.32 .75 .88 1.00 31.4 9.2 2.60 .77 .90 1.00 29.6 8.7 2.93 .79 .93 1.00

63�F(17�C)

1190 560 36.6 10.7 2.07 .78 .92 1.00 34.8 10.2 2.33 .80 .95 1.00 33.0 9.7 2.62 .82 .97 1.00 31.0 9.1 2.94 .84 1.00 1.00(17�C)

1395 660 37.8 11.1 2.08 .82 .97 1.00 36.2 10.6 2.34 .84 .99 1.00 34.2 10.0 2.63 .86 1.00 1.00 32.4 9.5 2.95 .89 1.00 1.00

67�F950 450 36.6 10.7 2.08 .60 .71 .83 35.0 10.3 2.33 .60 .73 .85 33.0 9.7 2.61 .61 .74 .87 31.2 9.1 2.94 .63 .76 .90

67�F(19�C)

1190 560 38.5 11.3 2.09 .62 .76 .89 36.8 10.8 2.34 .63 .77 .91 34.8 10.2 2.63 .65 .79 .94 32.6 9.6 2.95 .66 .82 .97(19�C)

1395 660 40.0 11.7 2.10 .65 .79 .94 38.0 11.1 2.35 .66 .81 .96 35.8 10.5 2.64 .67 .84 .99 33.6 9.8 2.96 .69 .87 1.00

71�F950 450 38.0 11.1 2.09 .46 .58 .69 36.4 10.7 2.34 .47 .59 .70 34.6 10.1 2.63 .47 .60 .72 32.6 9.6 2.95 .48 .61 .74

71�F(22�C)

1190 560 40.5 11.9 2.10 .48 .61 .74 38.5 11.3 2.36 .49 .62 .75 36.4 10.7 2.64 .49 .63 .77 34.4 10.1 2.97 .50 .65 .79(22�C)

1395 660 42.0 12.3 2.12 .49 .64 .77 40.0 11.7 2.37 .50 .65 .79 37.6 11.0 2.66 .50 .66 .81 35.4 10.4 2.98 .51 .68 .84

Page 71: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 3 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 71

FIRST STAGE COOLING CAPACITY − XC21−036 with [CH33−36B−2F + G61MPV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F695 330 25.6 7.5 1.10 .73 .85 .97 24.4 7.2 1.29 .74 .87 .99 23.2 6.8 1.51 .75 .89 1.00 22.0 6.4 1.76 .78 .92 1.00

63�F(17�C)

815 385 26.6 7.8 1.11 .76 .89 1.00 25.4 7.4 1.30 .77 .92 1.00 24.2 7.1 1.51 .79 .94 1.00 22.8 6.7 1.76 .81 .97 1.00(17�C)

935 440 27.4 8.0 1.12 .79 .93 1.00 26.2 7.7 1.30 .80 .96 1.00 25.0 7.3 1.52 .82 .98 1.00 23.4 6.9 1.77 .85 1.00 1.00

67�F695 330 27.4 8.0 1.11 .59 .70 .82 26.2 7.7 1.30 .59 .71 .83 24.8 7.3 1.52 .60 .73 .85 23.6 6.9 1.76 .61 .75 .88

67�F(19�C)

815 385 28.4 8.3 1.12 .60 .73 .86 27.2 8.0 1.31 .61 .74 .88 25.8 7.6 1.52 .62 .76 .90 24.4 7.2 1.76 .63 .78 .93(19�C)

935 440 29.2 8.6 1.12 .61 .76 .90 28.0 8.2 1.31 .63 .78 .92 26.6 7.8 1.52 .64 .80 .94 25.0 7.3 1.77 .66 .82 .98

71�F695 330 29.0 8.5 1.12 .46 .57 .67 27.8 8.1 1.31 .46 .58 .69 26.4 7.7 1.52 .46 .58 .70 25.0 7.3 1.77 .46 .59 .72

71�F(22�C)

815 385 30.2 8.9 1.13 .46 .58 .71 28.8 8.4 1.31 .46 .59 .72 27.4 8.0 1.53 .47 .60 .74 26.0 7.6 1.77 .47 .62 .76(22�C)

935 440 31.0 9.1 1.13 .47 .60 .73 29.8 8.7 1.32 .48 .61 .75 28.4 8.3 1.53 .48 .63 .77 26.8 7.9 1.77 .49 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−036 with [CH33−36B−2F + G61MPV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F950 450 34.6 10.1 2.06 .73 .85 .96 33.0 9.7 2.31 .74 .87 .99 31.2 9.1 2.60 .76 .89 1.00 29.2 8.6 2.93 .77 .92 1.00

63�F(17�C)

1190 560 36.4 10.7 2.07 .77 .91 1.00 34.6 10.1 2.33 .78 .93 1.00 32.6 9.6 2.61 .80 .96 1.00 30.6 9.0 2.94 .83 .99 1.00(17�C)

1395 660 37.6 11.0 2.08 .80 .96 1.00 35.8 10.5 2.34 .82 .98 1.00 33.8 9.9 2.62 .85 1.00 1.00 31.8 9.3 2.94 .87 1.00 1.00

67�F950 450 36.6 10.7 2.08 .59 .70 .81 35.0 10.3 2.33 .59 .71 .83 33.2 9.7 2.62 .60 .73 .85 31.2 9.1 2.93 .61 .75 .88

67�F(19�C)

1190 560 38.5 11.3 2.09 .61 .75 .87 36.6 10.7 2.34 .62 .76 .90 34.8 10.2 2.63 .63 .78 .92 32.6 9.6 2.95 .65 .80 .96(19�C)

1395 660 40.0 11.7 2.10 .63 .78 .92 37.8 11.1 2.35 .65 .80 .95 35.8 10.5 2.64 .66 .82 .97 33.4 9.8 2.96 .68 .85 1.00

71�F950 450 38.5 11.3 2.09 .46 .57 .67 37.0 10.8 2.35 .46 .58 .69 35.0 10.3 2.63 .47 .59 .70 33.0 9.7 2.95 .47 .60 .72

71�F(22�C)

1190 560 40.5 11.9 2.11 .47 .60 .72 39.0 11.4 2.36 .48 .61 .74 36.8 10.8 2.65 .48 .62 .75 34.6 10.1 2.97 .49 .64 .78(22�C)

1395 660 42.0 12.3 2.12 .48 .62 .75 40.0 11.7 2.37 .49 .63 .77 37.8 11.1 2.66 .50 .65 .80 35.4 10.4 2.98 .50 .67 .83

FIRST STAGE COOLING CAPACITY − XC21−036 with [CH33−36C−2F + G61MPV−36C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F705 335 26.0 7.6 1.11 .75 .87 .99 25.0 7.3 1.30 .76 .89 1.00 23.8 7.0 1.51 .77 .91 1.00 22.4 6.6 1.76 .79 .94 1.00

63�F(17�C)

790 375 27.0 7.9 1.11 .77 .90 1.00 25.8 7.6 1.30 .78 .93 1.00 24.4 7.2 1.51 .80 .95 1.00 23.2 6.8 1.76 .82 .98 1.00(17�C)

915 430 28.0 8.2 1.12 .80 .95 1.00 26.8 7.9 1.30 .82 .97 1.00 25.4 7.4 1.52 .84 .99 1.00 24.2 7.1 1.77 .86 1.00 1.00

67�F705 335 27.6 8.1 1.11 .60 .72 .84 26.4 7.7 1.30 .60 .73 .86 25.2 7.4 1.51 .61 .75 .88 23.8 7.0 1.76 .62 .77 .90

67�F(19�C)

790 375 28.4 8.3 1.12 .61 .74 .87 27.2 8.0 1.31 .62 .76 .89 25.8 7.6 1.52 .63 .77 .91 24.4 7.2 1.77 .64 .79 .94(19�C)

915 430 29.6 8.7 1.13 .63 .77 .91 28.2 8.3 1.31 .64 .79 .94 26.8 7.9 1.52 .65 .81 .96 25.2 7.4 1.77 .67 .83 .99

71�F705 335 28.8 8.4 1.12 .46 .58 .69 27.6 8.1 1.31 .46 .59 .71 26.4 7.7 1.52 .47 .60 .72 25.0 7.3 1.77 .47 .61 .74

71�F(22�C)

790 375 29.8 8.7 1.13 .47 .59 .72 28.6 8.4 1.31 .47 .60 .73 27.2 8.0 1.52 .47 .61 .75 25.8 7.6 1.77 .48 .63 .77(22�C)

915 430 31.0 9.1 1.13 .48 .62 .75 29.6 8.7 1.32 .48 .63 .77 28.2 8.3 1.53 .49 .64 .78 26.6 7.8 1.77 .49 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−036 with [CH33−36C−2F + G61MPV−36C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1015 480 35.8 10.5 2.07 .75 .88 1.00 34.2 10.0 2.33 .77 .90 1.00 32.2 9.4 2.61 .78 .93 1.00 30.2 8.9 2.93 .81 .96 1.00

63�F(17�C)

1185 560 37.0 10.8 2.08 .78 .93 1.00 35.2 10.3 2.33 .80 .95 1.00 33.4 9.8 2.62 .82 .98 1.00 31.4 9.2 2.94 .85 1.00 1.00(17�C)

1395 660 38.5 11.3 2.09 .82 .98 1.00 36.6 10.7 2.34 .84 1.00 1.00 34.8 10.2 2.63 .87 1.00 1.00 32.8 9.6 2.95 .90 1.00 1.00

67�F1015 480 37.6 11.0 2.08 .60 .73 .85 35.8 10.5 2.34 .61 .74 .87 34.0 10.0 2.62 .62 .76 .89 32.0 9.4 2.95 .63 .78 .92

67�F(19�C)

1185 560 39.0 11.4 2.09 .62 .76 .89 37.2 10.9 2.35 .63 .78 .92 35.2 10.3 2.63 .65 .80 .95 33.0 9.7 2.96 .66 .82 .98(19�C)

1395 660 40.5 11.9 2.10 .65 .80 .95 38.5 11.3 2.36 .66 .82 .97 36.2 10.6 2.64 .68 .84 1.00 34.0 10.0 2.96 .69 .87 1.00

71�F1015 480 39.5 11.6 2.09 .46 .59 .70 37.6 11.0 2.35 .47 .60 .72 35.6 10.4 2.63 .47 .61 .74 33.4 9.8 2.96 .48 .62 .76

71�F(22�C)

1185 560 41.0 12.0 2.11 .48 .61 .74 39.0 11.4 2.36 .48 .62 .75 36.8 10.8 2.65 .49 .63 .77 34.6 10.1 2.97 .49 .65 .80(22�C)

1395 660 42.5 12.5 2.12 .49 .64 .78 40.5 11.9 2.37 .50 .65 .80 38.0 11.1 2.66 .50 .66 .82 35.8 10.5 2.98 .51 .68 .85

Page 72: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 3 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 72

FIRST STAGE COOLING CAPACITY − XC21−036 with [CH33−42B−2F + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F740 350 26.6 7.8 1.11 .74 .87 .99 25.4 7.4 1.30 .75 .89 1.00 24.2 7.1 1.51 .77 .91 1.00 22.8 6.7 1.76 .79 .94 1.00

63�F(17�C)

840 395 27.4 8.0 1.12 .76 .90 1.00 26.2 7.7 1.30 .78 .93 1.00 25.0 7.3 1.51 .80 .95 1.00 23.4 6.9 1.76 .82 .98 1.00(17�C)

920 435 28.0 8.2 1.12 .78 .93 1.00 26.8 7.9 1.30 .80 .95 1.00 25.4 7.4 1.52 .82 .98 1.00 24.0 7.0 1.76 .84 1.00 1.00

67�F740 350 28.4 8.3 1.12 .59 .71 .83 27.2 8.0 1.31 .59 .72 .85 25.8 7.6 1.52 .60 .74 .87 24.4 7.2 1.76 .62 .76 .90

67�F(19�C)

840 395 29.2 8.6 1.12 .61 .74 .87 28.0 8.2 1.31 .61 .75 .89 26.6 7.8 1.52 .62 .77 .91 25.0 7.3 1.77 .64 .79 .94(19�C)

920 435 29.8 8.7 1.13 .62 .76 .89 28.6 8.4 1.31 .63 .77 .92 27.0 7.9 1.52 .64 .79 .94 25.6 7.5 1.77 .65 .81 .97

71�F740 350 30.0 8.8 1.13 .46 .57 .69 28.8 8.4 1.31 .46 .58 .70 27.4 8.0 1.52 .46 .59 .71 26.0 7.6 1.77 .47 .60 .73

71�F(22�C)

840 395 31.0 9.1 1.13 .46 .59 .71 29.8 8.7 1.32 .47 .60 .73 28.2 8.3 1.53 .47 .61 .74 26.6 7.8 1.77 .48 .62 .76(22�C)

920 435 31.8 9.3 1.14 .47 .60 .73 30.4 8.9 1.32 .47 .61 .75 28.8 8.4 1.53 .48 .62 .77 27.2 8.0 1.77 .48 .63 .78

SECOND STAGE COOLING CAPACITY − XC21−036 with [CH33−42B−2F + G60UHV−36B−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1035 490 36.4 10.7 2.07 .74 .87 .99 34.6 10.1 2.33 .75 .89 1.00 32.6 9.6 2.61 .77 .92 1.00 30.6 9.0 2.94 .79 .94 1.00

63�F(17�C)

1225 580 37.6 11.0 2.08 .77 .92 1.00 35.8 10.5 2.34 .79 .94 1.00 34.0 10.0 2.62 .81 .97 1.00 31.8 9.3 2.95 .84 1.00 1.00(17�C)

1385 655 38.5 11.3 2.09 .80 .95 1.00 36.8 10.8 2.35 .82 .98 1.00 34.8 10.2 2.63 .84 1.00 1.00 32.6 9.6 2.95 .87 1.00 1.00

67�F1035 490 38.5 11.3 2.09 .59 .72 .83 36.6 10.7 2.34 .60 .73 .85 34.8 10.2 2.63 .61 .75 .88 32.6 9.6 2.95 .62 .77 .91

67�F(19�C)

1225 580 40.0 11.7 2.10 .61 .75 .88 38.0 11.1 2.35 .63 .77 .91 35.8 10.5 2.64 .64 .79 .93 33.6 9.8 2.96 .65 .81 .96(19�C)

1385 655 41.0 12.0 2.11 .63 .78 .92 39.0 11.4 2.36 .64 .80 .95 36.6 10.7 2.65 .66 .82 .97 34.4 10.1 2.96 .67 .85 1.00

71�F1035 490 40.5 11.9 2.11 .46 .58 .69 38.5 11.3 2.36 .46 .58 .71 36.8 10.8 2.65 .47 .59 .72 34.6 10.1 2.97 .48 .61 .74

71�F(22�C)

1225 580 42.0 12.3 2.12 .47 .60 .72 40.0 11.7 2.37 .48 .61 .74 38.0 11.1 2.66 .48 .62 .76 35.6 10.4 2.98 .49 .64 .79(22�C)

1385 655 43.0 12.6 2.13 .48 .62 .76 41.0 12.0 2.38 .49 .63 .77 39.0 11.4 2.67 .49 .65 .80 36.4 10.7 2.99 .50 .66 .82

FIRST STAGE COOLING CAPACITY − XC21−036 with [CH33−42B−2F + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F695 330 26.2 7.7 1.11 .73 .85 .97 25.0 7.3 1.30 .74 .87 .99 23.8 7.0 1.51 .76 .89 1.00 22.4 6.6 1.76 .78 .92 1.00

63�F(17�C)

815 385 27.2 8.0 1.12 .76 .90 1.00 26.0 7.6 1.30 .78 .92 1.00 24.8 7.3 1.51 .79 .94 1.00 23.4 6.9 1.76 .81 .97 1.00(17�C)

935 440 28.2 8.3 1.12 .79 .94 1.00 27.0 7.9 1.30 .81 .96 1.00 25.6 7.5 1.52 .82 .99 1.00 24.2 7.1 1.76 .85 1.00 1.00

67�F695 330 28.0 8.2 1.12 .58 .70 .82 26.8 7.9 1.30 .59 .71 .83 25.4 7.4 1.52 .60 .73 .85 24.0 7.0 1.77 .61 .75 .88

67�F(19�C)

815 385 29.0 8.5 1.12 .60 .73 .85 27.8 8.1 1.31 .61 .75 .88 26.4 7.7 1.52 .62 .76 .90 25.0 7.3 1.77 .63 .79 .93(19�C)

935 440 30.0 8.8 1.13 .62 .76 .90 28.6 8.4 1.31 .63 .78 .92 27.2 8.0 1.52 .64 .80 .95 25.6 7.5 1.77 .66 .82 .98

71�F695 330 29.6 8.7 1.13 .46 .57 .67 28.4 8.3 1.31 .46 .57 .69 27.0 7.9 1.52 .45 .58 .70 25.6 7.5 1.77 .46 .59 .72

71�F(22�C)

815 385 30.8 9.0 1.13 .46 .58 .70 29.6 8.7 1.32 .46 .60 .72 28.2 8.3 1.52 .47 .60 .74 26.6 7.8 1.77 .48 .62 .76(22�C)

935 440 31.8 9.3 1.14 .47 .61 .74 30.4 8.9 1.32 .48 .62 .75 29.0 8.5 1.53 .48 .63 .77 27.2 8.0 1.77 .49 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−036 with [CH33−42B−2F + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F950 450 35.6 10.4 2.07 .73 .85 .97 34.0 10.0 2.32 .74 .87 .99 32.0 9.4 2.61 .75 .89 1.00 30.2 8.9 2.93 .78 .92 1.00

63�F(17�C)

1190 560 37.6 11.0 2.08 .77 .91 1.00 35.6 10.4 2.34 .79 .93 1.00 33.8 9.9 2.62 .81 .96 1.00 31.6 9.3 2.94 .83 .99 1.00(17�C)

1395 660 39.0 11.4 2.09 .81 .96 1.00 37.0 10.8 2.35 .83 .98 1.00 34.8 10.2 2.63 .85 1.00 1.00 32.8 9.6 2.95 .88 1.00 1.00

67�F950 450 37.8 11.1 2.08 .58 .70 .81 36.0 10.6 2.34 .59 .71 .83 34.2 10.0 2.63 .60 .73 .85 32.0 9.4 2.95 .61 .75 .88

67�F(19�C)

1190 560 39.5 11.6 2.10 .61 .74 .88 37.8 11.1 2.35 .62 .76 .90 35.8 10.5 2.64 .64 .78 .93 33.6 9.8 2.96 .65 .81 .96(19�C)

1395 660 41.0 12.0 2.11 .64 .79 .93 39.0 11.4 2.36 .65 .80 .95 36.8 10.8 2.65 .66 .83 .98 34.4 10.1 2.97 .68 .86 1.00

71�F950 450 40.0 11.7 2.10 .45 .57 .68 38.0 11.1 2.35 .46 .58 .69 36.0 10.6 2.64 .46 .58 .71 34.0 10.0 2.97 .47 .60 .72

71�F(22�C)

1190 560 42.0 12.3 2.12 .47 .60 .72 40.0 11.7 2.37 .48 .61 .74 37.8 11.1 2.66 .48 .62 .76 35.6 10.4 2.98 .49 .64 .78(22�C)

1395 660 43.5 12.7 2.13 .49 .63 .76 41.0 12.0 2.38 .49 .64 .78 39.0 11.4 2.66 .50 .65 .80 36.4 10.7 2.99 .51 .67 .83

Page 73: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 3 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 73

FIRST STAGE COOLING CAPACITY − XC21−036 with [CH33−44/48B−2F + G60UHV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F740 350 26.8 7.9 1.11 .74 .87 .99 25.8 7.6 1.30 .76 .89 1.00 24.4 7.2 1.51 .77 .92 1.00 23.0 6.7 1.76 .80 .95 1.00

63�F(17�C)

840 395 27.8 8.1 1.12 .77 .91 1.00 26.6 7.8 1.31 .78 .93 1.00 25.2 7.4 1.52 .80 .96 1.00 23.8 7.0 1.76 .82 .98 1.00(17�C)

920 435 28.4 8.3 1.12 .79 .94 1.00 27.2 8.0 1.30 .80 .96 1.00 25.8 7.6 1.52 .82 .98 1.00 24.4 7.2 1.76 .85 1.00 1.00

67�F740 350 28.6 8.4 1.12 .59 .71 .83 27.4 8.0 1.30 .60 .73 .86 26.2 7.7 1.52 .61 .75 .88 24.6 7.2 1.77 .62 .77 .91

67�F(19�C)

840 395 29.6 8.7 1.13 .61 .74 .87 28.4 8.3 1.31 .62 .76 .89 26.8 7.9 1.52 .63 .77 .92 25.4 7.4 1.77 .64 .80 .95(19�C)

920 435 30.2 8.9 1.13 .62 .76 .90 28.8 8.4 1.31 .63 .77 .92 27.4 8.0 1.53 .64 .80 .95 25.8 7.6 1.77 .65 .82 .98

71�F740 350 30.4 8.9 1.13 .46 .57 .69 29.2 8.6 1.32 .45 .58 .70 27.8 8.1 1.52 .46 .59 .72 26.2 7.7 1.77 .47 .61 .74

71�F(22�C)

840 395 31.4 9.2 1.14 .46 .59 .72 30.0 8.8 1.32 .47 .60 .73 28.6 8.4 1.53 .47 .61 .75 27.0 7.9 1.77 .48 .63 .77(22�C)

920 435 32.0 9.4 1.14 .47 .61 .71 30.8 9.0 1.32 .47 .62 .76 29.2 8.6 1.53 .48 .63 .77 27.6 8.1 1.77 .48 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−036 with [CH33−44/48B−2F + G60UHV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1035 490 37.0 10.8 2.08 .74 .87 .99 35.2 10.3 2.33 .76 .89 1.00 33.2 9.7 2.62 .78 .92 1.00 31.2 9.1 2.94 .80 .95 1.00

63�F(17�C)

1225 580 38.5 11.3 2.09 .78 .92 1.00 36.4 10.7 2.34 .79 .94 1.00 34.4 10.1 2.63 .81 .97 1.00 32.2 9.4 2.95 .84 1.00 1.00(17�C)

1385 655 39.5 11.6 2.10 .81 .96 1.00 37.4 11.0 2.35 .82 .98 1.00 35.4 10.4 2.63 .85 1.00 1.00 33.4 9.8 2.96 .88 1.00 1.00

67�F1035 490 39.0 11.4 2.09 .59 .72 .84 37.2 10.9 2.35 .60 .73 .86 35.4 10.4 2.63 .61 .75 .88 33.2 9.7 2.95 .63 .77 .91

67�F(19�C)

1225 580 40.5 11.9 2.11 .62 .75 .89 38.5 11.3 2.36 .63 .77 .91 36.4 10.7 2.64 .64 .79 .94 34.2 10.0 2.96 .65 .82 .97(19�C)

1385 655 41.5 12.2 2.11 .64 .78 .93 39.5 11.6 2.37 .65 .80 .95 37.4 11.0 2.65 .66 .82 .98 35.0 10.3 2.97 .67 .85 1.00

71�F1035 490 41.5 12.2 2.11 .46 .58 .69 39.5 11.6 2.36 .46 .59 .71 37.2 10.9 2.65 .47 .60 .72 35.0 10.3 2.98 .47 .61 .75

71�F(22�C)

1225 580 43.0 12.6 2.12 .47 .60 .73 41.0 12.0 2.38 .47 .61 .75 38.5 11.3 2.66 .48 .63 .77 36.2 10.6 2.98 .49 .64 .79(22�C)

1385 655 44.0 12.9 2.13 .48 .62 .76 41.5 12.2 2.38 .49 .63 .78 39.5 11.6 2.67 .49 .64 .80 36.8 10.8 2.99 .50 .66 .83

FIRST STAGE COOLING CAPACITY − XC21−036 with [CH33−44/48B−2F + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F695 330 26.4 7.7 1.11 .73 .86 .98 25.4 7.4 1.30 .75 .88 1.00 24.0 7.0 1.51 .76 .90 1.00 22.8 6.7 1.76 .78 .92 1.00

63�F(17�C)

815 385 27.6 8.1 1.11 .77 .90 1.00 26.4 7.7 1.30 .78 .92 1.00 25.0 7.3 1.52 .80 .95 1.00 23.6 6.9 1.76 .82 .98 1.00(17�C)

935 440 28.6 8.4 1.12 .80 .95 1.00 27.2 8.0 1.31 .81 .97 1.00 25.8 7.6 1.52 .83 .99 1.00 24.4 7.2 1.76 .86 1.00 1.00

67�F695 330 28.2 8.3 1.12 .59 .71 .82 27.0 7.9 1.31 .59 .72 .84 25.8 7.6 1.52 .60 .73 .86 24.4 7.2 1.76 .61 .75 .88

67�F(19�C)

815 385 29.4 8.6 1.12 .61 .74 .87 28.2 8.3 1.31 .61 .75 .88 26.8 7.9 1.52 .63 .77 .91 25.2 7.4 1.77 .64 .79 .94(19�C)

935 440 30.4 8.9 1.13 .63 .77 .91 29.0 8.5 1.31 .64 .78 .93 27.6 8.1 1.52 .64 .80 .95 26.0 7.6 1.77 .66 .82 .99

71�F695 330 30.0 8.8 1.13 .46 .57 .68 28.6 8.4 1.31 .46 .57 .69 27.4 8.0 1.52 .46 .58 .71 25.8 7.6 1.77 .46 .60 .72

71�F(22�C)

815 385 31.2 9.1 1.13 .46 .59 .71 29.8 8.7 1.32 .47 .60 .73 28.4 8.3 1.53 .47 .61 .74 26.8 7.9 1.77 .48 .62 .76(22�C)

935 440 32.2 9.4 1.14 .47 .61 .74 30.8 9.0 1.32 .48 .62 .76 29.4 8.6 1.53 .48 .63 .78 27.6 8.1 1.78 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−036 with [CH33−44/48B−2F + G61MPV−36B−070]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F950 450 36.2 10.6 2.07 .73 .85 .97 34.4 10.1 2.33 .74 .87 .99 32.6 9.6 2.61 .76 .89 1.00 30.6 9.0 2.93 .78 .92 1.00

63�F(17�C)

1190 560 38.0 11.1 2.09 .77 .92 1.00 36.2 10.6 2.34 .79 .94 1.00 34.4 10.1 2.63 .81 .96 1.00 32.2 9.4 2.95 .84 .99 1.00(17�C)

1395 660 39.5 11.6 2.10 .81 .96 1.00 37.6 11.0 2.35 .83 .99 1.00 35.4 10.4 2.63 .85 1.00 1.00 33.6 9.8 2.96 .89 1.00 1.00

67�F950 450 38.5 11.3 2.09 .59 .70 .82 36.6 10.7 2.34 .59 .72 .84 34.6 10.1 2.63 .60 .73 .86 32.6 9.6 2.95 .62 .75 .89

67�F(19�C)

1190 560 40.5 11.9 2.10 .62 .75 .88 38.5 11.3 2.36 .63 .77 .90 36.4 10.7 2.64 .64 .79 .93 34.0 10.0 2.96 .65 .80 .96(19�C)

1395 660 41.5 12.2 2.11 .64 .79 .93 39.5 11.6 2.37 .65 .81 .96 37.4 11.0 2.65 .66 .83 .99 35.0 10.3 2.97 .68 .86 1.00

71�F950 450 40.5 11.9 2.11 .46 .57 .68 38.5 11.3 2.36 .46 .58 .69 36.6 10.7 2.65 .46 .59 .71 34.4 10.1 2.97 .47 .60 .73

71�F(22�C)

1190 560 42.5 12.5 2.12 .47 .60 .72 40.5 11.9 2.38 .48 .61 .74 38.5 11.3 2.66 .48 .62 .76 36.0 10.6 2.99 .49 .64 .78(22�C)

1395 660 44.0 12.9 2.13 .49 .63 .77 42.0 12.3 2.39 .49 .64 .78 39.5 11.6 2.67 .50 .65 .80 37.0 10.8 2.99 .51 .67 .83

Page 74: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together where applicable:[CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 3 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 74

FIRST STAGE COOLING CAPACITY − XC21−036 with [CBX32M−030][CB30M−31] [CB30U−31]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 27.0 7.9 1.11 .76 .90 1.00 25.8 7.6 1.29 .78 .92 1.00 24.6 7.2 1.50 .80 .95 1.00 23.0 6.7 1.75 .82 .98 1.00

63�F(17�C)

900 425 27.8 8.1 1.11 .79 .94 1.00 26.4 7.7 1.30 .81 .96 1.00 25.2 7.4 1.50 .82 .98 1.00 23.8 7.0 1.75 .85 1.00 1.00(17�C)

1000 470 28.4 8.3 1.12 .81 .97 1.00 27.2 8.0 1.30 .83 .99 1.00 25.8 7.6 1.51 .86 1.00 1.00 24.6 7.2 1.75 .88 1.00 1.00

67�F800 380 28.8 8.4 1.12 .60 .73 .86 27.4 8.0 1.30 .61 .75 .89 26.2 7.7 1.51 .62 .77 .91 24.6 7.2 1.75 .63 .79 .94

67�F(19�C)

900 425 29.4 8.6 1.12 .62 .76 .90 28.2 8.3 1.30 .63 .78 .92 26.8 7.9 1.51 .64 .80 .95 25.2 7.4 1.75 .65 .82 .98(19�C)

1000 470 30.2 8.9 1.13 .63 .79 .94 28.8 8.4 1.31 .64 .81 .96 27.2 8.0 1.51 .66 .83 .98 25.6 7.5 1.76 .67 .85 1.00

71�F800 380 30.4 8.9 1.13 .45 .58 .71 29.2 8.6 1.31 .46 .59 .72 27.8 8.1 1.52 .46 .60 .74 26.2 7.7 1.76 .47 .62 .76

71�F(22�C)

900 425 31.2 9.1 1.13 .46 .60 .74 29.8 8.7 1.31 .46 .61 .75 28.4 8.3 1.52 .47 .62 .77 26.8 7.9 1.76 .48 .64 .79(22�C)

1000 470 32.0 9.4 1.14 .47 .62 .76 30.6 9.0 1.32 .47 .63 .78 29.0 8.5 1.52 .48 .64 .80 27.4 8.0 1.76 .49 .66 .83

SECOND STAGE COOLING CAPACITY − XC21−036 with [CBX32M−030][CB30M−31] [CB30U−31]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 35.6 10.4 2.07 .74 .87 .99 33.8 9.9 2.32 .75 .89 1.00 32.0 9.4 2.61 .77 .92 1.00 30.0 8.8 2.93 .79 .95 1.00

63�F(17�C)

1200 565 37.0 10.8 2.08 .77 .92 1.00 35.2 10.3 2.33 .79 .95 1.00 33.2 9.7 2.62 .82 .97 1.00 31.2 9.1 2.94 .84 .99 1.00(17�C)

1400 660 38.0 11.1 2.08 .81 .97 1.00 36.4 10.7 2.34 .84 .99 1.00 34.4 10.1 2.62 .86 1.00 1.00 32.4 9.5 2.95 .89 1.00 1.00

67�F1000 470 37.8 11.1 2.08 .59 .72 .84 36.0 10.6 2.34 .60 .73 .86 34.0 10.0 2.62 .61 .75 .88 32.0 9.4 2.95 .62 .77 .91

67�F(19�C)

1200 565 39.0 11.4 2.09 .61 .75 .89 37.4 11.0 2.35 .62 .77 .91 35.2 10.3 2.63 .63 .79 .94 33.0 9.7 2.96 .65 .82 .97(19�C)

1400 660 40.5 11.9 2.10 .63 .79 .94 38.5 11.3 2.36 .64 .81 .96 36.2 10.6 2.64 .66 .83 .98 33.8 9.9 2.97 .68 .86 1.00

71�F1000 470 40.0 11.7 2.10 .45 .57 .69 38.0 11.1 2.35 .46 .58 .70 35.8 10.5 2.64 .46 .59 .72 33.8 9.9 2.96 .46 .60 .74

71�F(22�C)

1200 565 41.5 12.2 2.11 .46 .60 .73 39.5 11.6 2.36 .46 .61 .74 37.2 10.9 2.65 .47 .62 .77 34.8 10.2 2.97 .48 .64 .79(22�C)

1400 660 42.5 12.5 2.12 .47 .62 .77 40.5 11.9 2.37 .48 .63 .79 38.0 11.1 2.66 .48 .65 .81 35.8 10.5 2.98 .49 .67 .84

FIRST STAGE COOLING CAPACITY − XC21−036 with [CBX32M−036] [CBX32M−042][CB30M−41] [CB30M−46]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 27.2 8.0 1.11 .76 .91 1.00 26.0 7.6 1.29 .78 .93 1.00 24.6 7.2 1.50 .80 .95 1.00 23.2 6.8 1.75 .82 .98 1.00

63�F(17�C)

900 425 28.0 8.2 1.11 .79 .94 1.00 26.6 7.8 1.30 .81 .97 1.00 25.4 7.4 1.51 .83 .99 1.00 24.0 7.0 1.75 .85 1.00 1.00(17�C)

1000 470 28.6 8.4 1.12 .82 .98 1.00 27.4 8.0 1.30 .83 .99 1.00 26.0 7.6 1.51 .85 1.00 1.00 24.6 7.2 1.75 .88 1.00 1.00

67�F800 380 29.0 8.5 1.12 .60 .74 .87 27.6 8.1 1.30 .61 .75 .89 26.2 7.7 1.51 .62 .77 .91 24.8 7.3 1.76 .63 .79 .94

67�F(19�C)

900 425 29.6 8.7 1.12 .62 .76 .90 28.4 8.3 1.30 .63 .78 .93 27.0 7.9 1.51 .64 .80 .95 25.4 7.4 1.76 .65 .82 .98(19�C)

1000 470 30.4 8.9 1.13 .63 .79 .94 29.0 8.5 1.31 .64 .81 .96 27.4 8.0 1.51 .66 .83 .98 25.8 7.6 1.76 .67 .86 1.00

71�F800 380 30.6 9.0 1.13 .45 .58 .71 29.4 8.6 1.31 .46 .59 .73 27.8 8.1 1.52 .46 .60 .74 26.4 7.7 1.76 .47 .62 .76

71�F(22�C)

900 425 31.4 9.2 1.13 .46 .60 .74 30.0 8.8 1.31 .47 .61 .75 28.6 8.4 1.52 .47 .62 .77 27.0 7.9 1.76 .48 .64 .80(22�C)

1000 470 32.2 9.4 1.14 .47 .62 .77 30.8 9.0 1.32 .47 .63 .78 29.2 8.6 1.52 .48 .64 .80 27.4 8.0 1.76 .49 .66 .83

SECOND STAGE COOLING CAPACITY − XC21−036 with [CBX32M−036] [CBX32M−042][CB30M−41] [CB30M−46]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 35.8 10.5 2.07 .74 .87 .99 34.2 10.0 2.32 .75 .90 1.00 32.2 9.4 2.61 .77 .92 1.00 30.2 8.9 2.93 .80 .95 1.00

63�F(17�C)

1200 565 37.2 10.9 2.08 .78 .93 1.00 35.4 10.4 2.33 .80 .95 1.00 33.4 9.8 2.62 .82 .98 1.00 31.4 9.2 2.94 .84 1.00 1.00(17�C)

1400 660 38.5 11.3 2.09 .82 .97 1.00 36.6 10.7 2.34 .84 .99 1.00 34.6 10.1 2.63 .86 1.00 1.00 32.6 9.6 2.95 .89 1.00 1.00

67�F1000 470 38.0 11.1 2.08 .59 .72 .84 36.2 10.6 2.34 .60 .73 .86 34.2 10.0 2.63 .61 .75 .88 32.2 9.4 2.95 .62 .77 .92

67�F(19�C)

1200 565 39.5 11.6 2.10 .61 .75 .89 37.6 11.0 2.35 .62 .77 .92 35.4 10.4 2.63 .63 .79 .95 33.2 9.7 2.96 .65 .82 .98(19�C)

1400 660 40.5 11.9 2.10 .63 .79 .95 38.5 11.3 2.36 .65 .82 .97 36.4 10.7 2.65 .66 .84 .99 34.0 10.0 2.97 .68 .87 1.00

71�F1000 470 40.0 11.7 2.10 .45 .57 .69 38.0 11.1 2.36 .45 .58 .71 36.2 10.6 2.64 .46 .59 .72 34.0 10.0 2.97 .46 .61 .75

71�F(22�C)

1200 565 41.5 12.2 2.11 .46 .60 .73 39.5 11.6 2.37 .46 .61 .75 37.4 11.0 2.65 .47 .62 .77 35.2 10.3 2.98 .48 .64 .80(22�C)

1400 660 43.0 12.6 2.12 .47 .62 .77 40.5 11.9 2.38 .47 .63 .79 38.5 11.3 2.66 .48 .65 .81 36.0 10.6 2.98 .49 .67 .84

Page 75: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together where applicable:[CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 3 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 75

FIRST STAGE COOLING CAPACITY − XC21−036 with [CBX32M−048][CB30M−51] [CB30U−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 27.6 8.1 1.11 .76 .91 1.00 26.4 7.7 1.30 .78 .93 1.00 25.0 7.3 1.51 .80 .95 1.00 23.6 6.9 1.75 .82 .98 1.00

63�F(17�C)

900 425 28.4 8.3 1.12 .79 .95 1.00 27.2 8.0 1.30 .81 .97 1.00 25.8 7.6 1.51 .83 .99 1.00 24.4 7.2 1.75 .85 1.00 1.00(17�C)

1000 470 29.2 8.6 1.12 .81 .98 1.00 27.8 8.1 1.30 .84 1.00 1.00 26.6 7.8 1.51 .86 1.00 1.00 25.4 7.4 1.76 .89 1.00 1.00

67�F800 380 29.4 8.6 1.12 .60 .74 .87 28.2 8.3 1.30 .61 .75 .89 26.8 7.9 1.51 .62 .77 .91 25.2 7.4 1.76 .63 .79 .94

67�F(19�C)

900 425 30.2 8.9 1.13 .62 .76 .91 29.0 8.5 1.31 .63 .78 .93 27.4 8.0 1.52 .64 .80 .96 25.8 7.6 1.76 .65 .82 .98(19�C)

1000 470 31.0 9.1 1.13 .63 .79 .94 29.6 8.7 1.31 .64 .81 .97 28.0 8.2 1.52 .65 .83 .99 26.4 7.7 1.76 .67 .86 1.00

71�F800 380 31.2 9.1 1.13 .45 .58 .71 30.0 8.8 1.31 .45 .59 .72 28.4 8.3 1.52 .46 .60 .74 26.8 7.9 1.76 .46 .62 .76

71�F(22�C)

900 425 32.2 9.4 1.14 .46 .60 .74 30.8 9.0 1.32 .46 .61 .75 29.2 8.6 1.52 .47 .62 .77 27.6 8.1 1.76 .47 .64 .80(22�C)

1000 470 32.8 9.6 1.14 .47 .62 .77 31.4 9.2 1.32 .47 .63 .78 29.8 8.7 1.53 .47 .64 .80 28.0 8.2 1.77 .48 .66 .83

SECOND STAGE COOLING CAPACITY − XC21−036 with [CBX32M−048][CB30M−51] [CB30U−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 36.8 10.8 2.08 .74 .87 .99 35.2 10.3 2.33 .75 .89 1.00 33.2 9.7 2.61 .77 .92 1.00 31.0 9.1 2.94 .79 .95 1.00

63�F(17�C)

1200 565 38.5 11.3 2.09 .78 .93 1.00 36.4 10.7 2.34 .80 .95 1.00 34.4 10.1 2.63 .82 .98 1.00 32.4 9.5 2.94 .84 1.00 1.00(17�C)

1400 660 39.5 11.6 2.10 .82 .98 1.00 37.8 11.1 2.35 .84 1.00 1.00 35.8 10.5 2.64 .86 1.00 1.00 33.8 9.9 2.96 .89 1.00 1.00

67�F1000 470 39.0 11.4 2.09 .59 .71 .84 37.2 10.9 2.35 .60 .73 .86 35.2 10.3 2.63 .61 .75 .89 33.0 9.7 2.96 .62 .77 .92

67�F(19�C)

1200 565 40.5 11.9 2.11 .61 .75 .90 38.5 11.3 2.36 .62 .77 .92 36.6 10.7 2.65 .63 .79 .95 34.2 10.0 2.97 .65 .82 .98(19�C)

1400 660 42.0 12.3 2.12 .63 .79 .95 40.0 11.7 2.37 .65 .81 .97 37.4 11.0 2.65 .66 .84 1.00 35.0 10.3 2.98 .68 .87 1.00

71�F1000 470 41.0 12.0 2.11 .45 .57 .69 39.5 11.6 2.36 .45 .58 .70 37.2 10.9 2.65 .45 .59 .72 35.0 10.3 2.97 .46 .60 .74

71�F(22�C)

1200 565 43.0 12.6 2.12 .46 .60 .73 41.0 12.0 2.38 .46 .61 .75 38.5 11.3 2.66 .47 .62 .77 36.2 10.6 2.99 .47 .64 .80(22�C)

1400 660 44.0 12.9 2.13 .47 .62 .77 42.0 12.3 2.39 .47 .63 .79 39.5 11.6 2.67 .48 .65 .82 37.2 10.9 3.00 .49 .67 .85

FIRST STAGE COOLING CAPACITY − XC21−036 with [CBX32MV−024/030]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 27.0 7.9 1.11 .76 .90 1.00 25.8 7.6 1.29 .78 .92 1.00 24.6 7.2 1.50 .80 .95 1.00 23.0 6.7 1.75 .82 .98 1.00

63�F(17�C)

900 425 27.8 8.1 1.11 .79 .94 1.00 26.4 7.7 1.30 .81 .96 1.00 25.2 7.4 1.50 .82 .98 1.00 23.8 7.0 1.75 .85 1.00 1.00(17�C)

1000 470 28.4 8.3 1.12 .81 .97 1.00 27.2 8.0 1.30 .83 .99 1.00 25.8 7.6 1.51 .86 1.00 1.00 24.6 7.2 1.75 .88 1.00 1.00

67�F800 380 28.8 8.4 1.12 .60 .73 .86 27.4 8.0 1.30 .61 .75 .89 26.2 7.7 1.51 .62 .77 .91 24.6 7.2 1.75 .63 .79 .94

67�F(19�C)

900 425 29.4 8.6 1.12 .62 .76 .90 28.2 8.3 1.30 .63 .78 .92 26.8 7.9 1.51 .64 .80 .95 25.2 7.4 1.75 .65 .82 .98(19�C)

1000 470 30.2 8.9 1.13 .63 .79 .94 28.8 8.4 1.31 .64 .81 .96 27.2 8.0 1.51 .66 .83 .98 25.6 7.5 1.76 .67 .85 1.00

71�F800 380 30.4 8.9 1.13 .45 .58 .71 29.2 8.6 1.31 .46 .59 .72 27.8 8.1 1.52 .46 .60 .74 26.2 7.7 1.76 .47 .62 .76

71�F(22�C)

900 425 31.2 9.1 1.13 .46 .60 .74 29.8 8.7 1.31 .46 .61 .75 28.4 8.3 1.52 .47 .62 .77 26.8 7.9 1.76 .48 .64 .79(22�C)

1000 470 32.0 9.4 1.14 .47 .62 .76 30.6 9.0 1.32 .47 .63 .78 29.0 8.5 1.52 .48 .64 .80 27.4 8.0 1.76 .49 .66 .83

SECOND STAGE COOLING CAPACITY − XC21−036 with [CBX32MV−024/030]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 36.4 10.7 2.07 .76 .90 1.00 34.6 10.1 2.33 .77 .92 1.00 32.6 9.6 2.61 .79 .95 1.00 30.6 9.0 2.94 .82 .98 1.00

63�F(17�C)

1200 565 37.0 10.8 2.08 .77 .92 1.00 35.2 10.3 2.33 .79 .95 1.00 33.2 9.7 2.62 .82 .97 1.00 31.2 9.1 2.94 .84 .99 1.00(17�C)

1320 625 37.6 11.0 2.08 .80 .95 1.00 35.8 10.5 2.34 .82 .97 1.00 34.0 10.0 2.62 .84 .99 1.00 31.8 9.3 2.94 .87 1.00 1.00

67�F1100 520 38.5 11.3 2.09 .60 .73 .86 36.6 10.7 2.34 .61 .75 .89 34.8 10.2 2.63 .62 .77 .91 32.6 9.6 2.95 .63 .79 .94

67�F(19�C)

1200 565 39.0 11.4 2.09 .61 .75 .89 37.4 11.0 2.35 .62 .77 .91 35.2 10.3 2.63 .63 .79 .94 33.0 9.7 2.96 .65 .82 .97(19�C)

1320 625 40.0 11.7 2.10 .62 .77 .92 38.0 11.1 2.36 .63 .79 .95 35.8 10.5 2.64 .65 .82 .97 33.6 9.8 2.96 .67 .84 .99

71�F1100 520 40.5 11.9 2.10 .45 .58 .71 38.5 11.3 2.36 .46 .59 .73 36.6 10.7 2.65 .46 .61 .74 34.4 10.1 2.97 .47 .62 .77

71�F(22�C)

1200 565 41.5 12.2 2.11 .46 .60 .73 39.5 11.6 2.36 .46 .61 .74 37.2 10.9 2.65 .47 .62 .77 34.8 10.2 2.97 .48 .64 .79(22�C)

1320 625 42.0 12.3 2.12 .47 .61 .75 40.0 11.7 2.37 .47 .62 .77 37.8 11.1 2.65 .48 .64 .79 35.6 10.4 2.98 .48 .65 .82

Page 76: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together where applicable:[CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 3 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 76

FIRST STAGE COOLING CAPACITY − XC21−036 with [CBX32MV−036][CB31MV−41]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F795 375 27.0 7.9 1.11 .76 .90 1.00 25.8 7.6 1.29 .78 .93 1.00 24.6 7.2 1.50 .79 .95 1.00 23.2 6.8 1.75 .82 .98 1.00

63�F(17�C)

855 405 27.6 8.1 1.11 .78 .93 1.00 26.4 7.7 1.29 .79 .95 1.00 25.0 7.3 1.50 .81 .97 1.00 23.6 6.9 1.75 .84 1.00 1.00(17�C)

900 425 28.0 8.2 1.11 .79 .94 1.00 26.6 7.8 1.30 .81 .97 1.00 25.4 7.4 1.51 .83 .99 1.00 24.0 7.0 1.75 .85 1.00 1.00

67�F795 375 28.8 8.4 1.12 .60 .74 .87 27.6 8.1 1.30 .61 .75 .89 26.2 7.7 1.51 .62 .77 .91 24.8 7.3 1.75 .63 .79 .94

67�F(19�C)

855 405 29.4 8.6 1.12 .61 .75 .89 28.0 8.2 1.30 .62 .77 .91 26.6 7.8 1.51 .63 .79 .94 25.2 7.4 1.76 .64 .81 .97(19�C)

900 425 29.6 8.7 1.12 .62 .76 .90 28.4 8.3 1.30 .63 .78 .93 27.0 7.9 1.51 .64 .80 .95 25.4 7.4 1.76 .65 .82 .98

71�F795 375 30.6 9.0 1.13 .45 .58 .71 29.2 8.6 1.31 .46 .59 .72 27.8 8.1 1.52 .46 .60 .74 26.2 7.7 1.76 .47 .62 .76

71�F(22�C)

855 405 31.2 9.1 1.13 .46 .59 .73 29.8 8.7 1.31 .46 .60 .74 28.4 8.3 1.52 .47 .62 .76 26.8 7.9 1.76 .47 .63 .78(22�C)

900 425 31.4 9.2 1.13 .46 .60 .74 30.0 8.8 1.31 .47 .61 .75 28.6 8.4 1.52 .47 .62 .77 27.0 7.9 1.76 .48 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−036 with [CBX32MV−036][CB31MV−41]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1135 535 36.8 10.8 2.07 .77 .91 1.00 35.0 10.3 2.33 .78 .94 1.00 33.2 9.7 2.62 .80 .96 1.00 31.0 9.1 2.94 .83 .99 1.00

63�F(17�C)

1225 580 37.4 11.0 2.08 .78 .94 1.00 35.6 10.4 2.33 .80 .96 1.00 33.6 9.8 2.62 .82 .98 1.00 31.6 9.3 2.94 .85 1.00 1.00(17�C)

1275 600 37.6 11.0 2.08 .79 .95 1.00 35.8 10.5 2.34 .81 .97 1.00 33.8 9.9 2.62 .83 .99 1.00 31.8 9.3 2.94 .86 1.00 1.00

67�F1135 535 39.0 11.4 2.09 .60 .74 .88 37.2 10.9 2.35 .61 .76 .90 35.2 10.3 2.63 .63 .78 .93 32.8 9.6 2.95 .64 .80 .96

67�F(19�C)

1225 580 39.5 11.6 2.10 .61 .76 .90 37.8 11.1 2.35 .62 .78 .93 35.6 10.4 2.64 .64 .80 .95 33.4 9.8 2.96 .65 .83 .98(19�C)

1275 600 40.0 11.7 2.10 .62 .77 .91 38.0 11.1 2.35 .63 .79 .94 35.8 10.5 2.64 .64 .81 .97 33.6 9.8 2.96 .66 .84 .99

71�F1135 535 41.0 12.0 2.11 .45 .59 .72 39.0 11.4 2.36 .46 .60 .73 37.0 10.8 2.65 .47 .61 .76 34.8 10.2 2.97 .47 .63 .78

71�F(22�C)

1225 580 42.0 12.3 2.11 .46 .60 .74 40.0 11.7 2.37 .46 .61 .75 37.6 11.0 2.65 .47 .62 .78 35.4 10.4 2.98 .48 .64 .80(22�C)

1275 600 42.0 12.3 2.12 .46 .61 .74 40.0 11.7 2.37 .47 .62 .76 37.8 11.1 2.65 .47 .63 .79 35.6 10.4 2.98 .48 .65 .81

FIRST STAGE COOLING CAPACITY − XC21−036 with [CBX32MV−048][CB31MV−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F835 395 28.0 8.2 1.11 .77 .92 1.00 26.8 7.9 1.30 .79 .94 1.00 25.4 7.4 1.51 .81 .97 1.00 24.0 7.0 1.75 .83 .99 1.00

63�F(17�C)

840 395 28.0 8.2 1.11 .77 .93 1.00 26.8 7.9 1.30 .79 .94 1.00 25.4 7.4 1.51 .81 .97 1.00 24.0 7.0 1.75 .83 .99 1.00(17�C)

960 455 28.8 8.4 1.12 .81 .97 1.00 27.6 8.1 1.30 .82 .98 1.00 26.4 7.7 1.51 .85 1.00 1.00 25.0 7.3 1.75 .87 1.00 1.00

67�F835 395 29.8 8.7 1.12 .60 .74 .88 28.4 8.3 1.31 .62 .76 .90 27.0 7.9 1.51 .63 .78 .93 25.4 7.4 1.76 .64 .80 .96

67�F(19�C)

840 395 29.8 8.7 1.12 .60 .75 .88 28.6 8.4 1.31 .62 .76 .91 27.0 7.9 1.51 .63 .78 .93 25.6 7.5 1.76 .64 .80 .96(19�C)

960 455 30.8 9.0 1.13 .63 .78 .93 29.4 8.6 1.31 .64 .80 .95 27.8 8.1 1.52 .65 .82 .98 26.2 7.7 1.76 .67 .85 1.00

71�F835 395 31.6 9.3 1.13 .45 .59 .72 30.2 8.9 1.31 .46 .60 .73 28.8 8.4 1.52 .46 .61 .75 27.2 8.0 1.76 .47 .62 .77

71�F(22�C)

840 395 31.6 9.3 1.13 .45 .59 .72 30.2 8.9 1.31 .46 .60 .74 28.8 8.4 1.52 .46 .61 .75 27.2 8.0 1.76 .47 .62 .78(22�C)

960 455 32.6 9.6 1.14 .46 .61 .76 31.2 9.1 1.32 .47 .62 .77 29.6 8.7 1.53 .47 .64 .79 27.8 8.1 1.77 .48 .65 .82

SECOND STAGE COOLING CAPACITY − XC21−036 with [CBX32MV−048][CB31MV−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1200 565 38.5 11.3 2.09 .78 .93 1.00 36.4 10.7 2.34 .80 .95 1.00 34.4 10.1 2.63 .82 .98 1.00 32.4 9.5 2.94 .84 1.00 1.00

63�F(17�C)

1205 570 38.5 11.3 2.09 .78 .93 1.00 36.6 10.7 2.34 .80 .96 1.00 34.6 10.1 2.63 .82 .98 1.00 32.4 9.5 2.94 .85 1.00 1.00(17�C)

1380 650 39.5 11.6 2.10 .81 .97 1.00 37.6 11.0 2.35 .83 .99 1.00 35.6 10.4 2.64 .86 1.00 1.00 33.6 9.8 2.96 .89 1.00 1.00

67�F1200 565 40.5 11.9 2.11 .61 .75 .90 38.5 11.3 2.36 .62 .77 .92 36.6 10.7 2.65 .63 .79 .95 34.2 10.0 2.97 .65 .82 .98

67�F(19�C)

1205 570 41.0 12.0 2.11 .61 .76 .90 38.5 11.3 2.36 .62 .77 .92 36.6 10.7 2.65 .63 .79 .95 34.2 10.0 2.97 .65 .82 .98(19�C)

1380 650 42.0 12.3 2.11 .63 .79 .94 39.5 11.6 2.37 .64 .81 .97 37.4 11.0 2.65 .66 .84 .99 35.0 10.3 2.97 .68 .87 1.00

71�F1200 565 43.0 12.6 2.12 .46 .60 .73 41.0 12.0 2.38 .46 .61 .75 38.5 11.3 2.66 .47 .62 .77 36.2 10.6 2.99 .47 .64 .80

71�F(22�C)

1205 570 43.0 12.6 2.12 .46 .60 .73 41.0 12.0 2.38 .46 .61 .75 38.5 11.3 2.66 .47 .62 .77 36.2 10.6 2.99 .47 .64 .80(22�C)

1380 650 44.0 12.9 2.13 .47 .62 .77 42.0 12.3 2.39 .47 .63 .79 39.5 11.6 2.67 .48 .65 .81 37.0 10.8 2.99 .48 .67 .84

Page 77: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together where applicable:[CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 3 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 77

FIRST STAGE COOLING CAPACITY − XC21−036 with [CB30U−41/46]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F800 380 27.4 8.0 1.12 .78 .92 1.00 26.2 7.7 1.31 .79 .94 1.00 25.0 7.3 1.53 .81 .96 1.00 23.6 6.9 1.78 .84 .99 1.00

63�F(17�C)

900 425 28.2 8.3 1.13 .80 .95 1.00 27.0 7.9 1.31 .82 .97 1.00 25.6 7.5 1.53 .84 .99 1.00 24.2 7.1 1.78 .86 1.00 1.00(17�C)

1000 470 29.0 8.5 1.13 .83 .98 1.00 27.6 8.1 1.32 .85 1.00 1.00 26.4 7.7 1.53 .87 1.00 1.00 25.2 7.4 1.78 .90 1.00 1.00

67�F800 380 29.2 8.6 1.13 .62 .75 .88 28.0 8.2 1.32 .63 .77 .90 26.6 7.8 1.53 .64 .78 .93 25.0 7.3 1.78 .65 .81 .96

67�F(19�C)

900 425 30.0 8.8 1.13 .63 .77 .92 28.6 8.4 1.32 .64 .79 .94 27.2 8.0 1.53 .65 .81 .96 25.6 7.5 1.78 .67 .84 .99(19�C)

1000 470 30.8 9.0 1.14 .65 .81 .95 29.4 8.6 1.33 .66 .82 .97 27.8 8.1 1.54 .68 .85 .99 26.2 7.7 1.79 .70 .88 1.00

71�F800 380 31.0 9.1 1.14 .47 .60 .72 29.6 8.7 1.33 .48 .61 .74 28.2 8.3 1.54 .48 .62 .76 26.6 7.8 1.79 .49 .64 .78

71�F(22�C)

900 425 31.8 9.3 1.14 .48 .61 .75 30.4 8.9 1.33 .48 .62 .77 29.0 8.5 1.54 .49 .64 .79 27.2 8.0 1.79 .49 .66 .81(22�C)

1000 470 32.6 9.6 1.15 .49 .64 .78 31.0 9.1 1.33 .50 .65 .80 29.6 8.7 1.54 .50 .66 .82 27.8 8.1 1.79 .51 .68 .85

SECOND STAGE COOLING CAPACITY − XC21−036 with [CB30U−41/46]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 36.2 10.6 2.07 .76 .89 1.00 34.4 10.1 2.33 .77 .91 1.00 32.4 9.5 2.61 .79 .94 1.00 30.4 8.9 2.93 .81 .97 1.00

63�F(17�C)

1200 565 37.4 11.0 2.08 .79 .94 1.00 35.6 10.4 2.34 .81 .97 1.00 33.8 9.9 2.62 .84 .99 1.00 31.8 9.3 2.94 .86 1.00 1.00(17�C)

1400 660 38.5 11.3 2.09 .84 .98 1.00 37.0 10.8 2.35 .86 1.00 1.00 35.0 10.3 2.63 .88 1.00 1.00 33.0 9.7 2.96 .91 1.00 1.00

67�F1000 470 38.5 11.3 2.09 .61 .73 .85 36.4 10.7 2.34 .61 .75 .87 34.4 10.1 2.63 .63 .76 .90 32.4 9.5 2.95 .64 .79 .93

67�F(19�C)

1200 565 39.5 11.6 2.10 .63 .77 .91 37.8 11.1 2.35 .64 .79 .93 35.8 10.5 2.64 .65 .81 .96 33.4 9.8 2.96 .67 .84 .98(19�C)

1400 660 41.0 12.0 2.11 .66 .81 .96 39.0 11.4 2.36 .67 .83 .98 36.6 10.7 2.65 .68 .86 1.00 34.2 10.0 2.97 .70 .89 1.00

71�F1000 470 40.5 11.9 2.10 .47 .59 .70 38.5 11.3 2.36 .47 .60 .72 36.4 10.7 2.64 .48 .61 .74 34.2 10.0 2.97 .48 .63 .76

71�F(22�C)

1200 565 42.0 12.3 2.11 .48 .61 .74 40.0 11.7 2.37 .48 .63 .76 37.6 11.0 2.65 .49 .64 .79 35.4 10.4 2.98 .50 .66 .81(22�C)

1400 660 43.0 12.6 2.13 .49 .64 .79 41.0 12.0 2.38 .50 .66 .81 38.5 11.3 2.66 .51 .67 .83 36.2 10.6 2.98 .52 .69 .87

Page 78: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 4 TON

UP−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 78

FIRST STAGE COOLING CAPACITY XC21−048 with [CX34−44/48B/C−6F] [C33−48B/C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 36.0 10.6 1.63 .77 .90 1.00 34.4 10.1 1.88 .78 .92 1.00 32.8 9.6 2.17 .80 .94 1.00 31.2 9.1 2.50 .82 .97 1.00

63�F(17�C)

1200 565 36.8 10.8 1.63 .79 .93 1.00 35.2 10.3 1.88 .80 .95 1.00 33.6 9.8 2.17 .82 .97 1.00 31.8 9.3 2.50 .84 .99 1.00(17�C)

1300 615 37.4 11.0 1.62 .80 .95 1.00 35.8 10.5 1.88 .82 .97 1.00 34.2 10.0 2.16 .84 .99 1.00 32.4 9.5 2.49 .86 1.00 1.00

67�F1100 520 38.5 11.3 1.62 .61 .74 .87 36.8 10.8 1.87 .62 .76 .89 35.0 10.3 2.16 .63 .77 .90 33.2 9.7 2.48 .64 .79 .93

67�F(19�C)

1200 565 39.0 11.4 1.62 .62 .76 .89 37.4 11.0 1.87 .63 .77 .91 35.6 10.4 2.15 .64 .79 .93 33.8 9.9 2.48 .65 .81 .96(19�C)

1300 615 39.5 11.6 1.62 .64 .78 .91 38.0 11.1 1.87 .64 .79 .93 36.2 10.6 2.15 .65 .81 .96 34.4 10.1 2.47 .67 .83 .98

71�F1100 520 40.5 11.9 1.62 .47 .59 .71 39.0 11.4 1.86 .48 .60 .73 37.4 11.0 2.14 .48 .62 .74 35.4 10.4 2.46 .49 .63 .76

71�F(22�C)

1200 565 41.5 12.2 1.62 .48 .61 .73 40.0 11.7 1.86 .48 .62 .75 38.0 11.1 2.14 .49 .63 .76 36.0 10.6 2.46 .49 .64 .78(22�C)

1300 615 42.0 12.3 1.62 .48 .62 .75 40.5 11.9 1.86 .49 .63 .77 38.5 11.3 2.14 .49 .64 .78 36.6 10.7 2.46 .50 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−44/48B/C−6F] [C33−48B/C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 47.5 13.9 2.84 .75 .88 .99 45.5 13.3 3.19 .76 .90 1.00 43.5 12.7 3.58 .78 .92 1.00 41.0 12.0 4.01 .80 .95 1.00

63�F(17�C)

1600 755 49.0 14.4 2.86 .77 .91 1.00 47.0 13.8 3.21 .79 .94 1.00 44.5 13.0 3.59 .81 .96 1.00 42.0 12.3 4.02 .83 .99 1.00(17�C)

1800 850 50.0 14.7 2.87 .80 .95 1.00 48.0 14.1 3.22 .82 .97 1.00 45.5 13.3 3.61 .84 .99 1.00 43.0 12.6 4.03 .86 1.00 1.00

67�F1400 660 50.5 14.8 2.88 .60 .73 .84 48.5 14.2 3.23 .61 .74 .86 46.0 13.5 3.61 .62 .75 .88 43.5 12.7 4.04 .63 .77 .91

67�F(19�C)

1600 755 52.0 15.2 2.89 .62 .75 .88 49.5 14.5 3.24 .63 .77 .90 47.5 13.9 3.63 .64 .78 .92 44.5 13.0 4.05 .65 .81 .95(19�C)

1800 850 53.0 15.5 2.91 .63 .78 .91 51.0 14.9 3.25 .64 .79 .94 48.0 14.1 3.64 .66 .82 .96 45.5 13.3 4.07 .67 .84 .99

71�F1400 660 53.5 15.7 2.91 .47 .59 .70 51.0 14.9 3.26 .47 .59 .72 48.5 14.2 3.64 .48 .60 .73 46.0 13.5 4.08 .48 .62 .75

71�F(22�C)

1600 755 55.0 16.1 2.93 .48 .60 .73 52.5 15.4 3.27 .48 .61 .74 50.0 14.7 3.66 .49 .62 .76 47.5 13.9 4.09 .49 .64 .78(22�C)

1800 850 56.0 16.4 2.94 .48 .62 .75 54.0 15.8 3.29 .49 .63 .77 51.0 14.9 3.67 .50 .64 .79 48.5 14.2 4.11 .50 .66 .81

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−49C−6F] [C33−49C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 36.4 10.7 1.65 .77 .90 1.00 35.0 10.3 1.91 .78 .92 1.00 33.4 9.8 2.20 .80 .94 1.00 31.8 9.3 2.54 .82 .97 1.00

63�F(17�C)

1200 565 37.2 10.9 1.64 .78 .92 1.00 35.6 10.4 1.90 .80 .95 1.00 34.2 10.0 2.20 .82 .97 1.00 32.4 9.5 2.53 .84 .99 1.00(17�C)

1300 615 37.8 11.1 1.64 .80 .95 1.00 36.4 10.7 1.90 .82 .97 1.00 34.8 10.2 2.19 .83 .99 1.00 33.0 9.7 2.52 .86 1.00 1.00

67�F1100 520 38.5 11.3 1.64 .61 .74 .86 37.2 10.9 1.89 .62 .75 .88 35.6 10.4 2.18 .63 .77 .90 33.8 9.9 2.52 .64 .79 .93

67�F(19�C)

1200 565 39.5 11.6 1.64 .62 .76 .89 38.0 11.1 1.89 .63 .77 .91 36.2 10.6 2.18 .64 .79 .93 34.4 10.1 2.51 .66 .81 .96(19�C)

1300 615 40.0 11.7 1.63 .63 .78 .91 38.5 11.3 1.89 .65 .79 .93 37.0 10.8 2.18 .66 .81 .96 35.0 10.3 2.50 .67 .83 .98

71�F1100 520 41.0 12.0 1.63 .47 .60 .71 39.0 11.4 1.89 .48 .61 .73 37.6 11.0 2.17 .48 .62 .74 35.8 10.5 2.50 .49 .63 .76

71�F(22�C)

1200 565 41.5 12.2 1.63 .48 .61 .73 40.0 11.7 1.88 .48 .62 .75 38.5 11.3 2.16 .49 .63 .76 36.4 10.7 2.49 .50 .64 .78(22�C)

1300 615 42.5 12.5 1.63 .49 .62 .75 41.0 12.0 1.88 .49 .63 .76 39.0 11.4 2.16 .50 .64 .78 37.2 10.9 2.48 .50 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−49C−6F] [C33−49C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 48.5 14.2 2.87 .75 .88 .99 46.5 13.6 3.23 .76 .90 1.00 44.5 13.0 3.61 .78 .92 1.00 42.0 12.3 4.05 .80 .95 1.00

63�F(17�C)

1600 755 50.0 14.7 2.89 .77 .91 1.00 48.0 14.1 3.24 .79 .93 1.00 45.5 13.3 3.63 .81 .96 1.00 43.5 12.7 4.07 .83 .98 1.00(17�C)

1800 850 51.5 15.1 2.90 .80 .95 1.00 49.0 14.4 3.25 .82 .97 1.00 47.0 13.8 3.64 .84 .99 1.00 44.5 13.0 4.08 .86 1.00 1.00

67�F1400 660 51.5 15.1 2.89 .61 .73 .84 49.0 14.4 3.25 .61 .74 .86 47.0 13.8 3.64 .62 .75 .88 44.5 13.0 4.08 .63 .77 .91

67�F(19�C)

1600 755 53.0 15.5 2.92 .62 .75 .88 50.5 14.8 3.27 .63 .76 .90 48.5 14.2 3.66 .64 .78 .92 46.0 13.5 4.10 .65 .80 .95(19�C)

1800 850 54.5 16.0 2.93 .64 .78 .91 52.0 15.2 3.28 .65 .79 .93 49.5 14.5 3.68 .66 .81 .96 47.0 13.8 4.11 .67 .83 .99

71�F1400 660 54.0 15.8 2.93 .47 .59 .70 52.0 15.2 3.28 .47 .60 .71 49.5 14.5 3.67 .48 .61 .73 47.0 13.8 4.12 .48 .62 .75

71�F(22�C)

1600 755 56.0 16.4 2.94 .48 .61 .73 53.5 15.7 3.30 .48 .62 .74 51.0 14.9 3.69 .49 .63 .76 48.5 14.2 4.13 .49 .64 .78(22�C)

1800 850 57.0 16.7 2.96 .49 .62 .75 54.5 16.0 3.31 .49 .63 .77 52.0 15.2 3.71 .50 .64 .79 49.5 14.5 4.15 .50 .66 .81

Page 79: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 4 TON

UP−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 79

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−50/60C−6F] [C33−50/60C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 36.4 10.7 1.63 .77 .91 1.00 34.8 10.2 1.88 .79 .93 1.00 33.2 9.7 2.17 .80 .95 1.00 31.6 9.3 2.50 .82 .98 1.00

63�F(17�C)

1200 565 37.2 10.9 1.62 .79 .93 1.00 35.6 10.4 1.88 .80 .95 1.00 34.0 10.0 2.16 .82 .98 1.00 32.2 9.4 2.49 .84 1.00 1.00(17�C)

1300 615 37.8 11.1 1.62 .81 .96 1.00 36.2 10.6 1.87 .82 .98 1.00 34.6 10.1 2.16 .84 1.00 1.00 32.8 9.6 2.49 .87 1.00 1.00

67�F1100 520 39.0 11.4 1.62 .61 .75 .87 37.2 10.9 1.87 .63 .76 .89 35.4 10.4 2.16 .63 .77 .91 33.6 9.8 2.48 .65 .80 .94

67�F(19�C)

1200 565 39.5 11.6 1.62 .63 .76 .90 37.8 11.1 1.87 .64 .78 .92 36.0 10.6 2.15 .65 .79 .94 34.2 10.0 2.48 .66 .81 .97(19�C)

1300 615 40.0 11.7 1.62 .64 .78 .92 38.5 11.3 1.87 .65 .80 .94 36.6 10.7 2.15 .65 .81 .96 34.8 10.2 2.47 .67 .84 .99

71�F1100 520 41.0 12.0 1.62 .47 .60 .71 39.5 11.6 1.86 .48 .61 .73 37.8 11.1 2.14 .48 .62 .75 35.8 10.5 2.46 .49 .63 .76

71�F(22�C)

1200 565 42.0 12.3 1.62 .48 .61 .74 40.5 11.9 1.86 .48 .62 .75 38.5 11.3 2.14 .49 .63 .77 36.4 10.7 2.46 .49 .64 .78(22�C)

1300 615 42.5 12.5 1.61 .49 .62 .76 41.0 12.0 1.86 .49 .63 .77 39.0 11.4 2.14 .49 .64 .79 37.0 10.8 2.45 .50 .66 .81

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−50/60C−6F] [C33−50/60C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 48.0 14.1 2.85 .75 .88 1.00 46.0 13.5 3.20 .77 .91 1.00 44.0 12.9 3.59 .79 .93 1.00 41.5 12.2 4.01 .81 .96 1.00

63�F(17�C)

1600 755 49.5 14.5 2.87 .78 .92 1.00 47.5 13.9 3.21 .80 .94 1.00 45.0 13.2 3.60 .81 .97 1.00 42.5 12.5 4.03 .84 .99 1.00(17�C)

1800 850 51.0 14.9 2.88 .81 .96 1.00 48.5 14.2 3.23 .82 .98 1.00 46.0 13.5 3.61 .84 1.00 1.00 43.5 12.7 4.04 .87 1.00 1.00

67�F1400 660 51.0 14.9 2.89 .61 .73 .85 49.0 14.4 3.23 .61 .74 .87 46.5 13.6 3.62 .62 .76 .89 44.0 12.9 4.05 .64 .78 .92

67�F(19�C)

1600 755 52.5 15.4 2.90 .62 .76 .89 50.5 14.8 3.25 .63 .77 .91 48.0 14.1 3.63 .64 .79 .93 45.0 13.2 4.07 .66 .81 .96(19�C)

1800 850 54.0 15.8 2.91 .64 .78 .92 51.5 15.1 3.26 .65 .79 .95 49.0 14.4 3.65 .66 .82 .97 46.0 13.5 4.07 .67 .84 1.00

71�F1400 660 54.0 15.8 2.92 .47 .59 .70 52.0 15.2 3.27 .47 .60 .72 49.5 14.5 3.65 .48 .61 .73 46.5 13.6 4.09 .48 .62 .75

71�F(22�C)

1600 755 55.5 16.3 2.94 .48 .61 .73 53.5 15.7 3.28 .48 .61 .75 51.0 14.9 3.67 .49 .63 .77 48.0 14.1 4.10 .49 .64 .79(22�C)

1800 850 57.0 16.7 2.95 .49 .62 .76 54.5 16.0 3.30 .49 .64 .76 52.0 15.2 3.68 .50 .65 .79 49.0 14.4 4.11 .50 .66 .82

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−60D−6F] [C33−60D]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 36.8 10.8 1.63 .78 .92 1.00 35.4 10.4 1.88 .79 .94 1.00 33.8 9.9 2.17 .81 .96 1.00 32.0 9.4 2.49 .83 .99 1.00

63�F(17�C)

1200 565 37.6 11.0 1.62 .80 .94 1.00 36.0 10.6 1.88 .81 .97 1.00 34.4 10.1 2.16 .83 .99 1.00 32.6 9.6 2.49 .85 1.00 1.00(17�C)

1300 615 38.5 11.3 1.62 .82 .97 1.00 36.8 10.8 1.87 .83 .99 1.00 35.2 10.3 2.16 .85 1.00 1.00 33.6 9.8 2.48 .88 1.00 1.00

67�F1100 520 39.0 11.4 1.62 .62 .75 .88 37.6 11.0 1.87 .63 .77 .90 35.8 10.5 2.15 .64 .78 .92 34.0 10.0 2.47 .65 .80 .95

67�F(19�C)

1200 565 40.0 11.7 1.62 .63 .77 .91 38.5 11.3 1.87 .64 .79 .93 36.6 10.7 2.15 .65 .81 .95 34.6 10.1 2.47 .66 .83 .98(19�C)

1300 615 40.5 11.9 1.62 .64 .79 .93 39.0 11.4 1.86 .65 .81 .95 37.2 10.9 2.14 .67 .83 .98 35.2 10.3 2.47 .68 .85 1.00

71�F1100 520 41.5 12.2 1.62 .48 .60 .73 40.0 11.7 1.86 .48 .61 .74 38.5 11.3 2.14 .48 .62 .76 36.4 10.7 2.46 .49 .64 .78

71�F(22�C)

1200 565 42.5 12.5 1.62 .48 .62 .75 41.0 12.0 1.86 .49 .63 .76 39.0 11.4 2.14 .49 .64 .78 37.0 10.8 2.46 .50 .65 .80(22�C)

1300 615 43.0 12.6 1.61 .49 .63 .77 41.5 12.2 1.86 .49 .64 .78 39.5 11.6 2.13 .50 .65 .80 37.4 11.0 2.45 .50 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−60D−6F] [C33−60D]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 49.0 14.4 2.86 .76 .90 1.00 47.0 13.8 3.20 .78 .92 1.00 44.5 13.0 3.59 .80 .94 1.00 42.0 12.3 4.02 .82 .97 1.00

63�F(17�C)

1600 755 50.5 14.8 2.88 .79 .94 1.00 48.5 14.2 3.23 .81 .96 1.00 46.0 13.5 3.61 .83 .98 1.00 43.5 12.7 4.04 .85 1.00 1.00(17�C)

1800 850 51.5 15.1 2.89 .82 .97 1.00 49.5 14.5 3.24 .84 .99 1.00 47.0 13.8 3.62 .86 1.00 1.00 45.0 13.2 4.06 .89 1.00 1.00

67�F1400 660 52.0 15.2 2.89 .61 .74 .86 49.5 14.5 3.24 .62 .75 .88 47.0 13.8 3.63 .63 .77 .91 44.5 13.0 4.06 .64 .79 .93

67�F(19�C)

1600 755 53.5 15.7 2.91 .63 .77 .90 51.0 14.9 3.26 .64 .78 .92 48.5 14.2 3.64 .65 .80 .95 46.0 13.5 4.07 .67 .83 .98(19�C)

1800 850 54.5 16.0 2.93 .65 .80 .94 52.0 15.2 3.27 .66 .82 .96 49.5 14.5 3.66 .67 .84 .99 47.0 13.8 4.09 .69 .86 1.00

71�F1400 660 55.0 16.1 2.93 .47 .60 .71 52.5 15.4 3.27 .48 .60 .73 50.5 14.8 3.67 .48 .61 .74 47.5 13.9 4.10 .49 .63 .77

71�F(22�C)

1600 755 56.5 16.6 2.95 .48 .61 .74 54.5 16.0 3.29 .49 .63 .76 51.5 15.1 3.68 .49 .64 .78 48.5 14.2 4.11 .50 .65 .80(22�C)

1800 850 58.0 17.0 2.96 .49 .63 .77 55.5 16.3 3.31 .49 .65 .79 52.5 15.4 3.70 .50 .66 .81 49.5 14.5 4.13 .50 .67 .84

Page 80: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 4 TON

UP−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 80

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−62D−6F] [C33−62D]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 37.0 10.8 1.63 .78 .91 1.00 35.6 10.4 1.88 .79 .94 1.00 33.8 9.9 2.17 .81 .96 1.00 32.0 9.4 2.49 .83 .99 1.00

63�F(17�C)

1200 565 37.8 11.1 1.62 .80 .94 1.00 36.2 10.6 1.88 .81 .96 1.00 34.6 10.1 2.16 .83 .99 1.00 32.8 9.6 2.48 .85 1.00 1.00(17�C)

1300 615 38.5 11.3 1.62 .82 .97 1.00 36.8 10.8 1.87 .83 .99 1.00 35.2 10.3 2.15 .85 1.00 1.00 33.6 9.8 2.48 .88 1.00 1.00

67�F1100 520 39.5 11.6 1.62 .61 .75 .88 37.8 11.1 1.87 .63 .77 .90 36.0 10.6 2.15 .64 .78 .92 34.2 10.0 2.47 .65 .80 .95

67�F(19�C)

1200 565 40.0 11.7 1.62 .63 .77 .91 38.5 11.3 1.87 .64 .79 .93 36.8 10.8 2.15 .65 .80 .95 34.8 10.2 2.47 .66 .82 .98(19�C)

1300 615 41.0 12.0 1.62 .64 .79 .93 39.5 11.6 1.86 .65 .81 .95 37.4 11.0 2.14 .66 .82 .98 35.4 10.4 2.46 .68 .85 1.00

71�F1100 520 41.5 12.2 1.62 .48 .60 .73 40.0 11.7 1.86 .48 .60 .74 38.0 11.1 2.14 .48 .61 .76 36.2 10.6 2.46 .49 .63 .78

71�F(22�C)

1200 565 42.5 12.5 1.62 .48 .61 .75 41.0 12.0 1.86 .48 .62 .76 39.0 11.4 2.14 .49 .64 .78 37.0 10.8 2.45 .50 .65 .80(22�C)

1300 615 43.0 12.6 1.61 .49 .63 .76 41.5 12.2 1.86 .49 .64 .78 39.5 11.6 2.13 .50 .65 .80 37.6 11.0 2.45 .50 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−62D−6F] [C33−62D]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 49.5 14.5 2.87 .76 .89 1.00 47.5 13.9 3.21 .78 .92 1.00 45.0 13.2 3.60 .79 .94 1.00 42.5 12.5 4.03 .82 .97 1.00

63�F(17�C)

1600 755 51.0 14.9 2.88 .79 .94 1.00 49.0 14.4 3.23 .81 .96 1.00 46.5 13.6 3.62 .83 .98 1.00 44.0 12.9 4.04 .85 1.00 1.00(17�C)

1800 850 52.5 15.4 2.90 .82 .97 1.00 50.0 14.7 3.24 .84 .99 1.00 47.5 13.9 3.63 .86 1.00 1.00 45.5 13.3 4.06 .88 1.00 1.00

67�F1400 660 52.0 15.2 2.90 .61 .74 .86 50.0 14.7 3.24 .62 .75 .88 47.5 13.9 3.63 .63 .77 .90 45.0 13.2 4.06 .64 .79 .93

67�F(19�C)

1600 755 54.0 15.8 2.92 .63 .77 .90 51.5 15.1 3.26 .64 .78 .92 49.0 14.4 3.65 .65 .80 .95 46.5 13.6 4.08 .66 .82 .98(19�C)

1800 850 55.0 16.1 2.93 .64 .80 .94 53.0 15.5 3.28 .66 .81 .96 50.0 14.7 3.66 .67 .83 .99 47.5 13.9 4.09 .69 .86 1.00

71�F1400 660 55.5 16.3 2.93 .47 .59 .71 53.0 15.5 3.28 .47 .60 .73 50.5 14.8 3.67 .48 .62 .74 47.5 13.9 4.10 .49 .63 .76

71�F(22�C)

1600 755 57.0 16.7 2.95 .48 .60 .74 54.5 16.0 3.30 .49 .63 .76 52.0 15.2 3.68 .49 .64 .78 49.0 14.4 4.12 .50 .65 .80(22�C)

1800 850 58.5 17.1 2.97 .49 .63 .76 55.5 16.3 3.31 .49 .65 .79 53.0 15.5 3.70 .50 .66 .81 50.0 14.7 4.13 .51 .67 .83

Page 81: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 4 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 81

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−44/48C−6F + G60UHV−60C−090][C33−48C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1015 480 35.2 10.3 1.64 .74 .87 .99 33.6 9.8 1.90 .76 .89 1.00 32.2 9.4 2.19 .77 .91 1.00 30.4 8.9 2.53 .79 .94 1.00

63�F(17�C)

1140 540 36.2 10.6 1.64 .77 .90 1.00 34.6 10.1 1.90 .78 .92 1.00 33.0 9.7 2.19 .80 .95 1.00 31.4 9.2 2.52 .82 .97 1.00(17�C)

1285 605 37.2 10.9 1.63 .79 .94 1.00 35.6 10.4 1.89 .81 .96 1.00 34.0 10.0 2.18 .83 .98 1.00 32.2 9.4 2.51 .84 1.00 1.00

67�F1015 480 37.4 11.0 1.63 .59 .72 .84 36.0 10.6 1.89 .60 .73 .85 34.4 10.1 2.18 .61 .74 .87 32.6 9.6 2.51 .62 .76 .90

67�F(19�C)

1140 540 38.5 11.3 1.63 .61 .74 .87 37.0 10.8 1.88 .62 .75 .88 35.2 10.3 2.17 .63 .77 .91 33.4 9.8 2.50 .64 .79 .93(19�C)

1285 605 39.5 11.6 1.62 .62 .77 .90 37.8 11.1 1.88 .63 .78 .92 36.0 10.6 2.16 .64 .80 .94 34.2 10.0 2.49 .65 .82 .97

71�F1015 480 40.0 11.7 1.63 .46 .58 .69 38.0 11.1 1.87 .46 .58 .70 36.6 10.7 2.16 .47 .59 .72 34.8 10.2 2.49 .47 .61 .73

71�F(22�C)

1140 540 41.0 12.0 1.62 .46 .59 .71 39.5 11.6 1.88 .47 .60 .73 37.6 11.0 2.16 .47 .61 .74 35.6 10.4 2.48 .48 .62 .76(22�C)

1285 605 42.0 12.3 1.62 .47 .61 .74 40.5 11.9 1.87 .48 .62 .75 38.5 11.3 2.15 .48 .63 .77 36.4 10.7 2.47 .49 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−44/48C−6F + G60UHV−60C−090][C33−48C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1460 690 48.0 14.1 2.86 .75 .88 1.00 46.0 13.5 3.21 .76 .90 1.00 44.0 12.9 3.60 .78 .93 1.00 41.5 12.2 4.03 .80 .95 1.00

63�F(17�C)

1635 770 49.5 14.5 2.87 .77 .92 1.00 47.0 13.8 3.22 .79 .94 1.00 45.0 13.2 3.61 .81 .96 1.00 42.5 12.5 4.04 .83 .99 1.00(17�C)

1855 875 50.5 14.8 2.89 .81 .95 1.00 48.5 14.2 3.24 .82 .97 1.00 46.0 13.5 3.62 .84 .99 1.00 43.5 12.7 4.06 .86 1.00 1.00

67�F1460 690 51.0 14.9 2.89 .60 .73 .85 49.0 14.4 3.24 .61 .74 .87 46.5 13.6 3.63 .62 .76 .89 44.0 12.9 4.06 .63 .78 .92

67�F(19�C)

1635 770 52.5 15.4 2.90 .62 .75 .88 50.0 14.7 3.25 .63 .77 .90 47.5 13.9 3.64 .64 .78 .93 45.0 13.2 4.07 .65 .80 .95(19�C)

1855 875 53.5 15.7 2.91 .64 .78 .92 51.0 14.9 3.27 .65 .80 .94 48.5 14.2 3.66 .66 .82 .97 46.0 13.5 4.09 .67 .84 .99

71�F1460 690 54.0 15.8 2.92 .47 .59 .70 51.5 15.1 3.27 .47 .59 .72 49.0 14.4 3.66 .47 .60 .73 46.5 13.6 4.10 .48 .62 .75

71�F(22�C)

1635 770 55.5 16.3 2.93 .47 .60 .73 53.0 15.5 3.29 .48 .61 .74 50.5 14.8 3.68 .48 .62 .76 47.5 13.9 4.11 .49 .64 .78(22�C)

1855 875 56.5 16.6 2.95 .48 .62 .76 54.5 16.0 3.30 .49 .63 .77 51.5 15.1 3.69 .49 .64 .79 48.5 14.2 4.13 .50 .66 .81

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−44/48C−6F + G61MPV−60C−090][C33−48C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F960 455 34.6 10.1 1.63 .73 .86 .98 33.2 9.7 1.89 .75 .88 1.00 31.6 9.3 2.18 .76 .90 1.00 30.0 8.8 2.51 .78 .92 1.00

63�F(17�C)

1090 515 35.8 10.5 1.63 .76 .89 1.00 34.2 10.0 1.88 .77 .91 1.00 32.6 9.6 2.17 .79 .94 1.00 31.0 9.1 2.50 .81 .96 1.00(17�C)

1215 575 36.6 10.7 1.63 .78 .92 1.00 35.2 10.3 1.88 .80 .94 1.00 33.4 9.8 2.17 .81 .97 1.00 31.8 9.3 2.50 .83 .99 1.00

67�F960 455 36.8 10.8 1.62 .59 .71 .83 35.4 10.4 1.88 .59 .72 .84 33.8 9.9 2.17 .60 .73 .86 32.2 9.4 2.49 .62 .75 .88

67�F(19�C)

1090 515 38.0 11.1 1.62 .60 .73 .86 36.4 10.7 1.87 .61 .75 .88 34.8 10.2 2.16 .62 .76 .89 33.0 9.7 2.48 .63 .78 .92(19�C)

1215 575 39.0 11.4 1.62 .62 .75 .89 37.4 11.0 1.87 .63 .77 .91 35.6 10.4 2.15 .64 .78 .93 33.8 9.9 2.48 .65 .81 .96

71�F960 455 39.0 11.4 1.62 .46 .57 .68 37.6 11.0 1.87 .46 .58 .69 36.0 10.6 2.15 .46 .58 .71 34.2 10.0 2.48 .47 .60 .72

71�F(22�C)

1090 515 40.5 11.9 1.62 .46 .58 .71 39.0 11.4 1.87 .47 .59 .72 37.0 10.8 2.14 .47 .60 .73 35.2 10.3 2.47 .48 .62 .75(22�C)

1215 575 41.5 12.2 1.62 .47 .60 .73 40.0 11.7 1.86 .47 .61 .74 38.0 11.1 2.14 .48 .62 .76 36.0 10.6 2.46 .48 .63 .78

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−44/48C−6F + G61MPV−60C−090][C33−48C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1380 650 47.5 13.9 2.84 .75 .87 .99 45.5 13.3 3.19 .76 .89 1.00 43.0 12.6 3.58 .77 .91 1.00 40.5 11.9 4.00 .79 .94 1.00

63�F(17�C)

1590 750 49.0 14.4 2.86 .77 .91 1.00 47.0 13.8 3.21 .79 .93 1.00 44.5 13.0 3.59 .81 .95 1.00 42.0 12.3 4.02 .83 .98 1.00(17�C)

1750 825 50.0 14.7 2.87 .80 .94 1.00 48.0 14.1 3.22 .81 .96 1.00 45.5 13.3 3.60 .83 .98 1.00 43.0 12.6 4.03 .85 1.00 1.00

67�F1380 650 50.0 14.7 2.88 .60 .72 .84 48.0 14.1 3.22 .60 .73 .86 46.0 13.5 3.61 .61 .75 .88 43.5 12.7 4.04 .63 .77 .90

67�F(19�C)

1590 750 52.0 15.2 2.89 .61 .75 .88 49.5 14.5 3.24 .62 .76 .90 47.0 13.8 3.63 .64 .78 .92 44.5 13.0 4.05 .65 .80 .95(19�C)

1750 825 53.0 15.5 2.90 .63 .77 .91 50.5 14.8 3.25 .64 .79 .93 48.0 14.1 3.64 .65 .81 .95 45.5 13.3 4.06 .67 .83 .98

71�F1380 650 53.0 15.5 2.91 .46 .58 .70 51.0 14.9 3.25 .47 .59 .71 48.5 14.2 3.64 .47 .60 .72 46.0 13.5 4.07 .48 .61 .74

71�F(22�C)

1590 750 55.0 16.1 2.92 .47 .60 .72 52.5 15.4 3.27 .48 .61 .74 50.0 14.7 3.66 .48 .62 .76 47.0 13.8 4.09 .49 .63 .77(22�C)

1750 825 56.0 16.4 2.94 .48 .61 .75 53.5 15.7 3.29 .49 .63 .76 51.0 14.9 3.67 .49 .64 .78 48.0 14.1 4.10 .50 .65 .80

Page 82: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 4 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 82

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−44/48C−6F + G61MPV−60C−110][C33−48C + G61MPV−60C−110]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F805 380 32.8 9.6 1.64 .71 .82 .93 31.6 9.3 1.90 .72 .84 .95 30.2 8.9 2.19 .73 .85 .97 28.6 8.4 2.53 .74 .87 .99

63�F(17�C)

925 435 34.2 10.0 1.63 .73 .85 .97 32.8 9.6 1.89 .74 .86 .99 31.4 9.2 2.18 .75 .89 1.00 29.8 8.7 2.51 .77 .91 1.00(17�C)

1050 495 35.4 10.4 1.63 .75 .88 1.00 33.8 9.9 1.89 .76 .90 1.00 32.4 9.5 2.17 .78 .92 1.00 30.6 9.0 2.51 .80 .95 1.00

67�F805 380 35.0 10.3 1.63 .57 .68 .79 33.8 9.9 1.89 .58 .69 .80 32.2 9.4 2.18 .58 .70 .81 30.6 9.0 2.50 .59 .71 .83

67�F(19�C)

925 435 36.4 10.7 1.63 .58 .70 .81 35.0 10.3 1.88 .59 .71 .83 33.6 9.8 2.17 .60 .72 .85 31.8 9.3 2.50 .61 .74 .87(19�C)

1050 495 37.6 11.0 1.62 .59 .72 .85 36.2 10.6 1.88 .60 .73 .86 34.6 10.1 2.16 .62 .75 .88 32.8 9.6 2.49 .62 .77 .91

71�F805 380 37.2 10.9 1.62 .45 .55 .65 35.8 10.5 1.88 .45 .56 .66 34.4 10.1 2.16 .46 .57 .67 32.6 9.6 2.48 .46 .57 .69

71�F(22�C)

925 435 38.5 11.3 1.62 .45 .57 .67 37.2 10.9 1.87 .46 .57 .69 35.6 10.4 2.15 .46 .58 .70 33.8 9.9 2.48 .46 .59 .71(22�C)

1050 495 40.0 11.7 1.62 .46 .58 .70 38.5 11.3 1.86 .46 .59 .71 36.8 10.8 2.15 .47 .60 .72 34.8 10.2 2.47 .47 .61 .74

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−44/48C−6F + G61MPV−60C−110][C33−48C + G61MPV−60C−110]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1405 665 47.5 13.9 2.84 .75 .88 .99 45.5 13.3 3.19 .76 .89 1.00 43.0 12.6 3.58 .78 .92 1.00 41.0 12.0 4.01 .80 .94 1.00

63�F(17�C)

1610 760 49.0 14.4 2.86 .77 .91 1.00 47.0 13.8 3.21 .79 .93 1.00 44.5 13.0 3.59 .80 .96 1.00 42.0 12.3 4.02 .83 .98 1.00(17�C)

1795 845 50.0 14.7 2.87 .80 .94 1.00 48.0 14.1 3.22 .81 .97 1.00 45.5 13.3 3.60 .83 .99 1.00 43.0 12.6 4.03 .86 1.00 1.00

67�F1405 665 50.5 14.8 2.88 .60 .72 .84 48.5 14.2 3.23 .61 .74 .86 46.0 13.5 3.61 .61 .75 .88 43.5 12.7 4.04 .63 .77 .91

67�F(19�C)

1610 760 52.0 15.2 2.89 .62 .75 .88 49.5 14.5 3.24 .62 .76 .90 47.0 13.8 3.63 .64 .78 .92 44.5 13.0 4.05 .65 .80 .95(19�C)

1795 845 53.0 15.5 2.91 .63 .77 .91 50.5 14.8 3.25 .64 .79 .93 48.0 14.1 3.64 .65 .81 .96 45.5 13.3 4.07 .67 .83 .98

71�F1405 665 53.5 15.7 2.91 .47 .58 .70 51.0 14.9 3.26 .47 .59 .71 48.5 14.2 3.64 .47 .60 .72 46.0 13.5 4.08 .48 .61 .74

71�F(22�C)

1610 760 55.0 16.1 2.93 .47 .60 .72 52.5 15.4 3.27 .48 .61 .74 50.0 14.7 3.66 .48 .62 .76 47.5 13.9 4.09 .49 .63 .78(22�C)

1795 845 56.0 16.4 2.94 .48 .62 .75 54.0 15.8 3.29 .49 .63 .77 51.0 14.9 3.67 .49 .64 .78 48.5 14.2 4.11 .50 .65 .81

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−49C−6F + G60UHV−60C−090][C33−49C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1015 480 35.4 10.4 1.64 .75 .87 .99 34.0 10.0 1.90 .76 .89 1.00 32.4 9.5 2.19 .77 .91 1.00 30.8 9.0 2.53 .79 .94 1.00

63�F(17�C)

1140 540 36.4 10.7 1.63 .77 .90 1.00 35.0 10.3 1.89 .78 .93 1.00 33.4 9.8 2.18 .80 .95 1.00 31.8 9.3 2.51 .82 .98 1.00(17�C)

1285 605 37.6 11.0 1.63 .79 .94 1.00 36.0 10.6 1.89 .81 .96 1.00 34.4 10.1 2.17 .83 .98 1.00 32.6 9.6 2.50 .85 1.00 1.00

67�F1015 480 37.6 11.0 1.63 .60 .72 .84 36.2 10.6 1.89 .60 .73 .85 34.4 10.1 2.17 .61 .75 .87 32.8 9.6 2.51 .62 .76 .90

67�F(19�C)

1140 540 38.5 11.3 1.63 .61 .74 .87 37.2 10.9 1.88 .62 .75 .89 35.6 10.4 2.17 .63 .77 .91 33.8 9.9 2.50 .64 .79 .94(19�C)

1285 605 40.0 11.7 1.63 .63 .77 .90 38.0 11.1 1.88 .63 .78 .92 36.6 10.7 2.16 .65 .80 .95 34.6 10.1 2.49 .66 .82 .97

71�F1015 480 39.5 11.6 1.63 .46 .58 .69 38.0 11.1 1.88 .46 .59 .71 36.4 10.7 2.16 .47 .60 .72 34.8 10.2 2.49 .47 .61 .74

71�F(22�C)

1140 540 41.0 12.0 1.62 .47 .59 .71 39.5 11.6 1.87 .47 .60 .73 37.6 11.0 2.15 .47 .61 .74 35.8 10.5 2.48 .48 .62 .76(22�C)

1285 605 42.0 12.3 1.62 .47 .61 .74 40.5 11.9 1.87 .48 .62 .75 38.5 11.3 2.15 .48 .63 .77 36.8 10.8 2.47 .49 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−49C−6F + G60UHV−60C−090][C33−49C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1460 690 49.0 14.4 2.86 .75 .89 1.00 47.0 13.8 3.22 .77 .91 1.00 44.5 13.0 3.61 .79 .93 1.00 42.0 12.3 4.04 .80 .96 1.00

63�F(17�C)

1635 770 50.0 14.7 2.88 .78 .92 1.00 48.0 14.1 3.23 .79 .94 1.00 45.5 13.3 3.62 .81 .97 1.00 43.0 12.6 4.05 .83 .99 1.00(17�C)

1855 875 51.5 15.1 2.89 .81 .96 1.00 49.5 14.5 3.25 .82 .98 1.00 47.0 13.8 3.63 .84 1.00 1.00 44.5 13.0 4.07 .87 1.00 1.00

67�F1460 690 51.5 15.1 2.90 .61 .73 .85 49.5 14.5 3.25 .61 .74 .87 47.0 13.8 3.64 .62 .76 .89 44.5 13.0 4.07 .64 .78 .92

67�F(19�C)

1635 770 53.0 15.5 2.91 .62 .75 .88 50.5 14.8 3.26 .63 .77 .90 48.5 14.2 3.65 .64 .79 .93 45.5 13.3 4.09 .65 .81 .96(19�C)

1855 875 54.5 16.0 2.92 .64 .78 .92 52.0 15.2 3.28 .65 .80 .95 49.5 14.5 3.67 .66 .82 .97 46.5 13.6 4.09 .68 .84 1.00

71�F1460 690 54.5 16.0 2.92 .47 .59 .71 52.0 15.2 3.28 .47 .60 .72 49.5 14.5 3.67 .48 .61 .73 47.0 13.8 4.10 .48 .62 .75

71�F(22�C)

1635 770 55.5 16.3 2.94 .47 .61 .73 53.5 15.7 3.29 .48 .62 .74 51.0 14.9 3.68 .49 .63 .76 48.0 14.1 4.12 .49 .64 .78(22�C)

1855 875 57.0 16.7 2.96 .49 .63 .76 55.0 16.1 3.31 .49 .64 .78 52.0 15.2 3.70 .50 .65 .79 49.5 14.5 4.14 .50 .66 .82

Page 83: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 4 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 83

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−49C−6F + G61MPV−60C−090][C33−49C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F960 455 34.8 10.2 1.63 .74 .86 .98 33.6 9.8 1.89 .75 .88 1.00 32.0 9.4 2.18 .76 .90 1.00 30.4 8.9 2.51 .78 .92 1.00

63�F(17�C)

1090 515 36.0 10.6 1.63 .76 .89 1.00 34.6 10.1 1.88 .77 .91 1.00 33.0 9.7 2.17 .79 .94 1.00 31.4 9.2 2.50 .81 .96 1.00(17�C)

1215 575 37.0 10.8 1.62 .78 .92 1.00 35.6 10.4 1.88 .80 .95 1.00 33.8 9.9 2.16 .81 .97 1.00 32.2 9.4 2.49 .83 .99 1.00

67�F960 455 37.0 10.8 1.62 .59 .71 .83 35.6 10.4 1.88 .60 .72 .84 34.0 10.0 2.16 .61 .74 .86 32.4 9.5 2.49 .62 .75 .88

67�F(19�C)

1090 515 38.0 11.1 1.62 .61 .73 .86 36.8 10.8 1.87 .61 .75 .88 35.0 10.3 2.16 .62 .76 .90 33.4 9.8 2.48 .64 .78 .92(19�C)

1215 575 39.5 11.6 1.62 .62 .75 .89 37.6 11.0 1.87 .63 .77 .91 36.0 10.6 2.15 .64 .79 .93 34.2 10.0 2.48 .65 .81 .96

71�F960 455 39.0 11.4 1.62 .46 .58 .69 37.6 11.0 1.87 .46 .58 .70 36.0 10.6 2.15 .46 .59 .71 34.2 10.0 2.47 .47 .60 .73

71�F(22�C)

1090 515 40.5 11.9 1.62 .46 .59 .71 39.0 11.4 1.86 .47 .60 .72 37.0 10.8 2.14 .47 .61 .74 35.2 10.3 2.47 .48 .62 .75(22�C)

1215 575 41.5 12.2 1.62 .47 .60 .73 40.0 11.7 1.86 .48 .61 .74 38.0 11.1 2.14 .48 .63 .76 36.2 10.6 2.46 .49 .64 .78

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−49C−6F + G61MPV−60C−090][C33−49C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1380 650 48.0 14.1 2.85 .75 .87 .99 46.0 13.5 3.20 .76 .89 1.00 44.0 12.9 3.58 .78 .91 1.00 41.5 12.2 4.01 .80 .94 1.00

63�F(17�C)

1590 750 49.5 14.5 2.87 .77 .91 1.00 47.5 13.9 3.22 .79 .93 1.00 45.5 13.3 3.60 .81 .96 1.00 43.0 12.6 4.03 .83 .99 1.00(17�C)

1750 825 51.0 14.9 2.88 .80 .94 1.00 48.5 14.2 3.23 .81 .97 1.00 46.0 13.5 3.61 .83 .99 1.00 43.5 12.7 4.04 .86 1.00 1.00

67�F1380 650 51.0 14.9 2.88 .60 .72 .84 48.5 14.2 3.23 .61 .74 .86 46.5 13.6 3.62 .62 .75 .88 44.0 12.9 4.05 .63 .77 .91

67�F(19�C)

1590 750 52.5 15.4 2.90 .62 .75 .88 50.5 14.8 3.25 .63 .77 .90 48.0 14.1 3.64 .64 .78 .92 45.5 13.3 4.07 .65 .80 .95(19�C)

1750 825 53.5 15.7 2.91 .63 .77 .91 51.5 15.1 3.26 .64 .79 .93 49.0 14.4 3.65 .66 .81 .96 46.0 13.5 4.08 .67 .83 .99

71�F1380 650 53.5 15.7 2.91 .47 .59 .70 51.5 15.1 3.26 .47 .59 .71 49.0 14.4 3.64 .47 .60 .73 46.5 13.6 4.08 .48 .61 .74

71�F(22�C)

1590 750 55.0 16.1 2.93 .48 .60 .73 53.0 15.5 3.28 .48 .61 .74 50.5 14.8 3.66 .48 .62 .76 48.0 14.1 4.10 .49 .64 .78(22�C)

1750 825 56.5 16.6 2.94 .48 .62 .75 54.0 15.8 3.29 .49 .63 .76 51.5 15.1 3.68 .49 .64 .78 48.5 14.2 4.11 .50 .66 .81

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−50/60C−6F + G60UHV−60C−090][C33−50/60C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1015 480 35.6 10.4 1.64 .74 .88 1.00 34.0 10.0 1.90 .76 .90 1.00 32.4 9.5 2.19 .78 .92 1.00 30.8 9.0 2.53 .79 .94 1.00

63�F(17�C)

1140 540 36.6 10.7 1.63 .77 .91 1.00 35.0 10.3 1.89 .78 .93 1.00 33.4 9.8 2.18 .80 .95 1.00 31.6 9.3 2.51 .82 .98 1.00(17�C)

1285 605 37.6 11.0 1.63 .79 .95 1.00 36.0 10.6 1.89 .81 .97 1.00 34.4 10.1 2.17 .83 .99 1.00 32.6 9.6 2.50 .85 1.00 1.00

67�F1015 480 37.8 11.1 1.63 .59 .72 .84 36.4 10.7 1.89 .60 .73 .85 34.8 10.2 2.17 .61 .75 .88 33.0 9.7 2.50 .62 .76 .90

67�F(19�C)

1140 540 39.0 11.4 1.63 .61 .74 .87 37.4 11.0 1.88 .62 .76 .89 35.6 10.4 2.17 .63 .77 .91 33.8 9.9 2.50 .64 .79 .94(19�C)

1285 605 40.0 11.7 1.62 .63 .77 .91 38.0 11.1 1.88 .64 .78 .93 36.4 10.7 2.16 .64 .80 .95 34.6 10.1 2.49 .66 .82 .98

71�F1015 480 40.5 11.9 1.62 .46 .58 .70 38.5 11.3 1.88 .46 .58 .70 37.0 10.8 2.16 .47 .59 .72 35.2 10.3 2.49 .47 .61 .74

71�F(22�C)

1140 540 41.5 12.2 1.62 .47 .59 .72 40.0 11.7 1.87 .47 .60 .73 38.0 11.1 2.15 .47 .61 .74 36.0 10.6 2.48 .48 .62 .76(22�C)

1285 605 42.5 12.5 1.62 .47 .61 .74 41.0 12.0 1.87 .48 .62 .74 39.0 11.4 2.15 .48 .63 .77 36.8 10.8 2.47 .49 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−50/60C−6F + G60UHV−60C−090][C33−50/60C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1460 690 48.5 14.2 2.86 .76 .89 1.00 46.5 13.6 3.22 .77 .91 1.00 44.5 13.0 3.60 .79 .93 1.00 42.0 12.3 4.04 .81 .96 1.00

63�F(17�C)

1635 770 50.0 14.7 2.88 .78 .93 1.00 47.5 13.9 3.23 .80 .95 1.00 45.5 13.3 3.62 .81 .97 1.00 43.0 12.6 4.05 .84 .99 1.00(17�C)

1855 875 51.5 15.1 2.89 .81 .96 1.00 49.0 14.4 3.24 .83 .98 1.00 46.5 13.6 3.63 .85 1.00 1.00 44.0 12.9 4.07 .87 1.00 1.00

67�F1460 690 51.5 15.1 2.90 .60 .74 .86 49.5 14.5 3.25 .61 .74 .87 47.0 13.8 3.64 .62 .76 .90 44.5 13.0 4.07 .64 .78 .93

67�F(19�C)

1635 770 53.0 15.5 2.91 .62 .76 .89 50.5 14.8 3.26 .63 .77 .91 48.0 14.1 3.65 .64 .79 .94 45.5 13.3 4.08 .65 .81 .96(19�C)

1855 875 54.0 15.8 2.92 .64 .79 .93 52.0 15.2 3.27 .65 .81 .95 49.0 14.4 3.66 .66 .82 .98 46.5 13.6 4.10 .68 .85 1.00

71�F1460 690 54.5 16.0 2.93 .47 .59 .71 52.5 15.4 3.28 .47 .60 .72 50.0 14.7 3.67 .48 .61 .74 47.0 13.8 4.11 .48 .62 .76

71�F(22�C)

1635 770 56.0 16.4 2.94 .47 .60 .73 53.5 15.7 3.29 .48 .61 .75 51.0 14.9 3.69 .48 .63 .76 48.0 14.1 4.12 .49 .64 .79(22�C)

1855 875 57.5 16.9 2.96 .48 .63 .76 55.0 16.1 3.31 .49 .64 .78 52.0 15.2 3.70 .50 .65 .79 49.0 14.4 4.13 .50 .66 .82

Page 84: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 4 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 84

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−50/60C−6F + G61MPV−60C−090][C33−50/60C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F960 455 35.0 10.3 1.63 .74 .87 .98 33.6 9.8 1.89 .75 .88 1.00 32.0 9.4 2.18 .77 .90 1.00 30.4 8.9 2.51 .78 .93 1.00

63�F(17�C)

1090 515 36.2 10.6 1.63 .76 .90 1.00 34.6 10.1 1.88 .78 .92 1.00 33.0 9.7 2.17 .79 .94 1.00 31.2 9.1 2.50 .81 .97 1.00(17�C)

1215 575 37.0 10.8 1.62 .78 .93 1.00 35.6 10.4 1.88 .80 .95 1.00 33.8 9.9 2.16 .82 .97 1.00 32.0 9.4 2.49 .84 1.00 1.00

67�F960 455 37.4 11.0 1.62 .59 .71 .83 35.8 10.5 1.88 .60 .72 .85 34.2 10.0 2.16 .61 .74 .86 32.4 9.5 2.49 .62 .76 .89

67�F(19�C)

1090 515 38.5 11.3 1.62 .60 .74 .86 37.0 10.8 1.87 .62 .75 .88 35.2 10.3 2.16 .62 .76 .90 33.4 9.8 2.48 .63 .78 .93(19�C)

1215 575 39.5 11.6 1.62 .62 .76 .89 37.8 11.1 1.87 .63 .77 .91 36.0 10.6 2.15 .64 .79 .94 34.0 10.0 2.48 .65 .81 .96

71�F960 455 39.5 11.6 1.62 .46 .57 .68 38.0 11.1 1.87 .46 .58 .70 36.4 10.7 2.15 .46 .59 .70 34.6 10.1 2.47 .47 .60 .73

71�F(22�C)

1090 515 41.0 12.0 1.62 .46 .59 .71 39.0 11.4 1.86 .46 .59 .72 37.6 11.0 2.14 .47 .61 .74 35.6 10.4 2.46 .48 .62 .75(22�C)

1215 575 42.0 12.3 1.62 .47 .60 .73 40.0 11.7 1.86 .48 .61 .74 38.5 11.3 2.14 .48 .62 .76 36.4 10.7 2.46 .49 .63 .78

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−50/60C−6F + G61MPV−60C−090][C33−50/60C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1380 650 48.0 14.1 2.85 .75 .88 1.00 46.0 13.5 3.20 .76 .90 1.00 43.5 12.7 3.58 .78 .92 1.00 41.0 12.0 4.02 .80 .95 1.00

63�F(17�C)

1590 750 49.5 14.5 2.87 .78 .92 1.00 47.5 13.9 3.21 .79 .94 1.00 45.0 13.2 3.60 .81 .96 1.00 42.5 12.5 4.03 .83 .99 1.00(17�C)

1750 825 50.5 14.8 2.88 .80 .95 1.00 48.5 14.2 3.23 .82 .97 1.00 46.0 13.5 3.61 .84 .99 1.00 43.5 12.7 4.04 .86 1.00 1.00

67�F1380 650 51.0 14.9 2.88 .60 .72 .84 49.0 14.4 3.23 .61 .74 .86 46.5 13.6 3.62 .62 .75 .88 44.0 12.9 4.05 .63 .77 .91

67�F(19�C)

1590 750 52.5 15.4 2.90 .62 .75 .88 50.0 14.7 3.24 .63 .77 .91 47.5 13.9 3.63 .64 .79 .93 45.0 13.2 4.06 .65 .81 .96(19�C)

1750 825 53.5 15.7 2.91 .63 .78 .91 51.0 14.9 3.26 .64 .79 .94 48.5 14.2 3.64 .66 .81 .96 46.0 13.5 4.07 .67 .83 .99

71�F1380 650 54.0 15.8 2.92 .47 .59 .70 51.5 15.1 3.26 .47 .59 .71 49.0 14.4 3.65 .47 .60 .72 46.5 13.6 4.08 .48 .61 .75

71�F(22�C)

1590 750 55.5 16.3 2.93 .47 .60 .73 53.0 15.5 3.28 .48 .61 .74 50.5 14.8 3.67 .48 .62 .76 48.0 14.1 4.10 .49 .64 .78(22�C)

1750 825 56.5 16.6 2.95 .48 .62 .75 54.5 16.0 3.30 .49 .63 .77 51.5 15.1 3.68 .49 .64 .79 48.5 14.2 4.11 .50 .66 .81

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−50/60C−6F + G61MPV−60C−110][C33−50/60C + G61MPV−60C−110]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT t

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTemperat

ure

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbure

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F805 380 33.2 9.7 1.64 .71 .82 .94 31.8 9.3 1.90 .72 .84 .95 30.4 8.9 2.19 .73 .86 .97 28.8 8.4 2.53 .74 .88 1.00

63�F(17�C)

925 435 34.6 10.1 1.63 .73 .86 .97 33.2 9.7 1.89 .74 .87 .99 31.6 9.3 2.18 .76 .89 1.00 30.0 8.8 2.51 .77 .91 1.00(17�C)

1050 495 35.8 10.5 1.63 .75 .89 1.00 34.2 10.0 1.88 .77 .91 1.00 32.6 9.6 2.17 .78 .93 1.00 31.0 9.1 2.50 .80 .95 1.00

67�F805 380 35.6 10.4 1.63 .57 .68 .79 34.2 10.0 1.88 .58 .69 .80 32.6 9.6 2.17 .58 .70 .82 31.0 9.1 2.50 .59 .72 .83

67�F(19�C)

925 435 37.0 10.8 1.62 .58 .71 .82 35.4 10.4 1.88 .59 .72 .83 33.8 9.9 2.17 .60 .73 .85 32.2 9.4 2.49 .61 .75 .88(19�C)

1050 495 38.0 11.1 1.62 .60 .72 .85 36.6 10.7 1.87 .61 .74 .87 34.8 10.2 2.16 .62 .76 .89 33.0 9.7 2.48 .63 .77 .91

71�F805 380 37.6 11.0 1.62 .45 .55 .65 36.2 10.6 1.88 .45 .56 .67 34.6 10.1 2.16 .45 .57 .68 33.0 9.7 2.48 .46 .57 .69

71�F(22�C)

925 435 39.0 11.4 1.62 .45 .57 .68 37.6 11.0 1.87 .46 .57 .69 36.0 10.6 2.15 .46 .58 .70 34.2 10.0 2.48 .46 .59 .72(22�C)

1050 495 40.5 11.9 1.62 .46 .58 .70 39.0 11.4 1.87 .46 .59 .71 37.2 10.9 2.14 .47 .60 .73 35.2 10.3 2.47 .47 .61 .74

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−50/60C−6F + G61MPV−60C−110][C33−50/60C + G61MPV−60C−110]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1405 665 48.0 14.1 2.85 .75 .88 1.00 46.0 13.5 3.20 .76 .90 1.00 44.0 12.9 3.59 .78 .93 1.00 41.5 12.2 4.01 .80 .95 1.00

63�F(17�C)

1610 760 49.5 14.5 2.87 .78 .92 1.00 47.5 13.9 3.21 .80 .94 1.00 45.0 13.2 3.60 .81 .97 1.00 42.5 12.5 4.03 .84 .99 1.00(17�C)

1795 845 51.0 14.9 2.88 .81 .95 1.00 48.5 14.2 3.23 .82 .98 1.00 46.0 13.5 3.61 .84 1.00 1.00 43.5 12.7 4.04 .87 1.00 1.00

67�F1405 665 51.0 14.9 2.88 .60 .72 .85 49.0 14.4 3.23 .61 .74 .87 46.5 13.6 3.62 .62 .76 .89 44.0 12.9 4.05 .63 .78 .92

67�F(19�C)

1610 760 52.5 15.4 2.90 .62 .75 .89 50.5 14.8 3.25 .63 .77 .91 48.0 14.1 3.63 .64 .79 .93 45.0 13.2 4.07 .65 .81 .96(19�C)

1795 845 54.0 15.8 2.92 .64 .78 .92 51.5 15.1 3.26 .65 .80 .94 49.0 14.4 3.64 .66 .82 .97 46.0 13.5 4.07 .67 .84 .99

71�F1405 665 54.0 15.8 2.92 .47 .58 .70 52.0 15.2 3.27 .47 .59 .72 49.0 14.4 3.65 .47 .60 .73 46.5 13.6 4.09 .48 .62 .75

71�F(22�C)

1610 760 55.5 16.3 2.93 .47 .60 .73 53.5 15.7 3.28 .48 .61 .75 50.5 14.8 3.67 .48 .63 .76 48.0 14.1 4.10 .49 .64 .78(22�C)

1795 845 57.0 16.7 2.95 .48 .62 .76 54.5 16.0 3.30 .49 .63 .76 52.0 15.2 3.68 .49 .64 .79 49.0 14.4 4.11 .50 .66 .81

Page 85: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 4 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 85

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−60D−6F + G60UHV−60D−135][C33−60D + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1075 505 36.4 10.7 1.64 .76 .89 1.00 35.0 10.3 1.89 .78 .92 1.00 33.4 9.8 2.18 .79 .94 1.00 31.6 9.3 2.52 .81 .97 1.00

63�F(17�C)

1180 555 37.2 10.9 1.63 .78 .93 1.00 35.8 10.5 1.89 .80 .95 1.00 34.2 10.0 2.18 .82 .97 1.00 32.4 9.5 2.50 .83 1.00 1.00(17�C)

1325 625 38.5 11.3 1.63 .81 .97 1.00 36.8 10.8 1.88 .83 .99 1.00 35.0 10.3 2.17 .84 1.00 1.00 33.6 9.8 2.50 .87 1.00 1.00

67�F1075 505 39.0 11.4 1.63 .60 .74 .86 37.0 10.8 1.88 .61 .74 .88 35.4 10.4 2.17 .62 .77 .90 33.8 9.9 2.49 .63 .79 .93

67�F(19�C)

1180 555 39.5 11.6 1.63 .62 .76 .89 38.0 11.1 1.88 .63 .77 .91 36.2 10.6 2.16 .64 .79 .94 34.4 10.1 2.49 .65 .81 .96(19�C)

1325 625 41.0 12.0 1.63 .64 .78 .93 39.0 11.4 1.87 .65 .80 .95 37.2 10.9 2.15 .66 .82 .98 35.4 10.4 2.48 .67 .84 1.00

71�F1075 505 41.5 12.2 1.62 .46 .59 .71 39.5 11.6 1.87 .46 .60 .72 38.0 11.1 2.15 .47 .61 .74 36.0 10.6 2.47 .47 .62 .76

71�F(22�C)

1180 555 42.5 12.5 1.62 .47 .60 .73 40.5 11.9 1.87 .47 .61 .73 38.5 11.3 2.15 .48 .62 .76 36.8 10.8 2.47 .48 .64 .78(22�C)

1325 625 43.5 12.7 1.62 .48 .62 .76 41.5 12.2 1.87 .48 .63 .77 39.5 11.6 2.15 .48 .64 .79 37.6 11.0 2.47 .49 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−60D−6F + G60UHV−60D−135][C33−60D + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1540 725 50.0 14.7 2.88 .78 .92 1.00 48.0 14.1 3.23 .79 .94 1.00 45.5 13.3 3.62 .81 .96 1.00 43.0 12.6 4.05 .83 .99 1.00

63�F(17�C)

1695 800 51.0 14.9 2.89 .80 .95 1.00 49.0 14.4 3.24 .82 .97 1.00 46.5 13.6 3.63 .84 .99 1.00 44.0 12.9 4.06 .86 1.00 1.00(17�C)

1905 900 52.5 15.4 2.90 .83 .99 1.00 50.0 14.7 3.25 .85 1.00 1.00 48.0 14.1 3.64 .87 1.00 1.00 45.5 13.3 4.09 .90 1.00 1.00

67�F1540 725 53.0 15.5 2.91 .62 .75 .88 50.5 14.8 3.26 .63 .77 .90 48.5 14.2 3.65 .64 .79 .93 45.5 13.3 4.09 .65 .81 .96

67�F(19�C)

1695 800 54.0 15.8 2.92 .63 .77 .91 52.0 15.2 3.27 .64 .79 .94 49.0 14.4 3.66 .65 .81 .96 46.5 13.6 4.10 .66 .83 .99(19�C)

1905 900 55.5 16.3 2.94 .65 .80 .95 53.0 15.5 3.29 .66 .82 .98 50.0 14.7 3.67 .67 .85 1.00 47.5 13.9 4.11 .69 .87 1.00

71�F1540 725 56.0 16.4 2.94 .47 .60 .73 54.0 15.8 3.30 .47 .61 .74 51.5 15.1 3.69 .48 .62 .76 48.5 14.2 4.12 .49 .64 .78

71�F(22�C)

1695 800 57.5 16.9 2.96 .48 .62 .75 55.0 16.1 3.31 .48 .63 .77 52.0 15.2 3.70 .49 .64 .79 49.5 14.5 4.14 .49 .65 .81(22�C)

1905 900 58.5 17.1 2.97 .49 .64 .78 56.0 16.4 3.32 .49 .65 .80 53.0 15.5 3.71 .50 .66 .82 50.5 14.8 4.15 .51 .68 .85

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−60D−6F + G61MPV−60D−135][C33−60D + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F985 465 35.8 10.5 1.65 .75 .87 .99 34.2 10.0 1.91 .89 1.00 32.6 9.6 2.21 .77 .91 1.00 31.0 9.1 2.54 .79 .94 1.00

63�F(17�C)

1115 525 37.0 10.8 1.64 .77 .91 1.00 35.4 10.4 1.90 .78 .93 1.00 33.8 9.9 2.20 .80 .95 1.00 32.0 9.4 2.53 .82 .98 1.00(17�C)

1235 585 37.8 11.1 1.64 .79 .94 1.00 36.2 10.6 1.90 .81 .96 1.00 34.6 10.1 2.19 .82 .98 1.00 32.8 9.6 2.52 .85 1.00 1.00

67�F985 465 37.8 11.1 1.64 .59 .72 .84 36.4 10.7 1.90 .60 .73 .85 34.6 10.1 2.19 .61 .73 .87 33.2 9.7 2.52 .62 .76 .90

67�F(19�C)

1115 525 39.0 11.4 1.64 .61 .74 .87 37.6 11.0 1.89 .62 .76 .89 36.0 10.6 2.18 .63 .77 .91 34.2 10.0 2.51 .64 .79 .94(19�C)

1235 585 40.0 11.7 1.63 .63 .77 .90 38.5 11.3 1.89 .63 .78 .92 36.8 10.8 2.17 .65 .80 .95 34.8 10.2 2.50 .66 .82 .97

71�F985 465 40.5 11.9 1.63 .46 .58 .69 39.0 11.4 1.88 .45 .58 .70 37.2 10.9 2.17 .46 .59 .72 35.4 10.4 2.50 .47 .61 .73

71�F(22�C)

1115 525 41.5 12.2 1.63 .46 .59 .72 40.0 11.7 1.88 .47 .60 .73 38.5 11.3 2.17 .47 .61 .75 36.4 10.7 2.49 .48 .63 .77(22�C)

1235 585 42.5 12.5 1.63 .47 .61 .74 41.0 12.0 1.88 .48 .62 .76 39.0 11.4 2.16 .48 .63 .77 37.0 10.8 2.49 .49 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−60D−6F + G61MPV−60D−135][C33−60D + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 49.0 14.4 2.88 .75 .89 1.00 47.0 13.8 3.23 .77 .91 1.00 45.0 13.2 3.62 .79 .93 1.00 42.5 12.5 4.06 .81 .96 1.00

63�F(17�C)

1600 755 50.5 14.8 2.89 .78 .93 1.00 48.5 14.2 3.25 .80 .95 1.00 46.0 13.5 3.64 .82 .97 1.00 43.5 12.7 4.08 .84 1.00 1.00(17�C)

1780 840 52.0 15.2 2.91 .81 .96 1.00 49.5 14.5 3.26 .83 .98 1.00 47.0 13.8 3.65 .85 1.00 1.00 45.0 13.2 4.09 .87 1.00 1.00

67�F1400 660 52.0 15.2 2.90 .61 .73 .85 49.5 14.5 3.26 .61 .74 .87 47.5 13.9 3.65 .62 .76 .90 45.0 13.2 4.09 .63 .78 .92

67�F(19�C)

1600 755 53.5 15.7 2.92 .62 .76 .89 51.5 15.1 3.27 .63 .78 .91 49.0 14.4 3.67 .64 .79 .94 46.0 13.5 4.11 .66 .82 .97(19�C)

1780 840 55.0 16.1 2.93 .64 .79 .93 52.5 15.4 3.29 .65 .80 .95 50.0 14.7 3.68 .66 .82 .98 47.0 13.8 4.12 .67 .85 1.00

71�F1400 660 55.0 16.1 2.94 .46 .59 .71 53.0 15.5 3.29 .47 .59 .72 50.5 14.8 3.69 .47 .61 .73 47.5 13.9 4.13 .48 .62 .75

71�F(22�C)

1600 755 56.5 16.6 2.95 .47 .60 .74 54.5 16.0 3.31 .48 .62 .75 51.5 15.1 3.70 .48 .63 .77 49.0 14.4 4.14 .49 .64 .79(22�C)

1780 840 58.0 17.0 2.97 .48 .63 .76 55.5 16.3 3.32 .49 .64 .78 52.5 15.4 3.71 .49 .65 .80 49.5 14.5 4.15 .50 .66 .82

Page 86: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 4 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 86

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−62D−6F + G60UHV−60D−135][C33−62D + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1075 505 36.6 10.7 1.64 .76 .90 1.00 35.0 10.3 1.89 .78 .92 1.00 33.6 9.8 2.18 .79 .94 1.00 31.8 9.3 2.51 .81 .97 1.00

63�F(17�C)

1180 555 37.6 11.0 1.63 .78 .93 1.00 36.0 10.6 1.89 .80 .95 1.00 34.2 10.0 2.17 .82 .97 1.00 32.4 9.5 2.51 .83 1.00 1.00(17�C)

1325 625 38.5 11.3 1.63 .81 .97 1.00 37.0 10.8 1.88 .82 .99 1.00 35.2 10.3 2.17 .84 1.00 1.00 33.6 9.8 2.49 .87 1.00 1.00

67�F1075 505 39.0 11.4 1.63 .60 .73 .86 37.4 11.0 1.88 .60 .75 .88 35.6 10.4 2.17 .62 .77 .90 33.8 9.9 2.49 .63 .78 .93

67�F(19�C)

1180 555 40.0 11.7 1.63 .62 .76 .89 38.0 11.1 1.88 .63 .77 .91 36.6 10.7 2.16 .64 .79 .93 34.6 10.1 2.48 .65 .81 .96(19�C)

1325 625 41.0 12.0 1.62 .64 .78 .93 39.5 11.6 1.88 .65 .80 .95 37.4 11.0 2.16 .65 .82 .97 35.4 10.4 2.48 .67 .84 1.00

71�F1075 505 41.5 12.2 1.62 .46 .59 .71 39.5 11.6 1.87 .46 .58 .72 37.8 11.1 2.16 .47 .61 .74 36.0 10.6 2.48 .47 .62 .76

71�F(22�C)

1180 555 42.0 12.3 1.62 .47 .59 .73 40.5 11.9 1.87 .47 .61 .74 38.5 11.3 2.15 .48 .62 .76 36.6 10.7 2.47 .48 .63 .78(22�C)

1325 625 43.5 12.7 1.62 .48 .62 .76 41.5 12.2 1.87 .48 .63 .77 39.5 11.6 2.15 .49 .64 .79 37.6 11.0 2.47 .49 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−62D−6F + G60UHV−60D−135][C33−62D + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1540 725 50.5 14.8 2.88 .78 .92 1.00 48.5 14.2 3.23 .79 .94 1.00 46.0 13.5 3.62 .81 .96 1.00 43.5 12.7 4.05 .83 .99 1.00

63�F(17�C)

1695 800 51.5 15.1 2.89 .80 .95 1.00 49.5 14.5 3.24 .82 .97 1.00 47.0 13.8 3.63 .83 .99 1.00 44.5 13.0 4.07 .86 1.00 1.00(17�C)

1905 900 53.0 15.5 2.91 .83 .98 1.00 50.5 14.8 3.26 .84 1.00 1.00 48.5 14.2 3.65 .87 1.00 1.00 46.0 13.5 4.09 .89 1.00 1.00

67�F1540 725 53.5 15.7 2.92 .61 .75 .88 51.0 14.9 3.27 .63 .77 .90 48.5 14.2 3.65 .64 .79 .93 46.0 13.5 4.09 .65 .81 .96

67�F(19�C)

1695 800 54.5 16.0 2.93 .63 .77 .91 52.0 15.2 3.28 .64 .79 .94 49.5 14.5 3.67 .65 .81 .96 47.0 13.8 4.10 .67 .83 .99(19�C)

1905 900 56.0 16.4 2.94 .65 .80 .95 53.5 15.7 3.29 .66 .82 .98 50.5 14.8 3.68 .67 .84 1.00 48.0 14.1 4.12 .69 .87 1.00

71�F1540 725 56.5 16.6 2.95 .47 .60 .73 54.0 15.8 3.30 .47 .61 .74 51.5 15.1 3.69 .48 .62 .76 48.5 14.2 4.13 .49 .64 .78

71�F(22�C)

1695 800 57.5 16.9 2.96 .48 .62 .75 55.0 16.1 3.31 .48 .63 .77 52.5 15.4 3.70 .49 .64 .79 49.5 14.5 4.13 .49 .65 .81(22�C)

1905 900 59.0 17.3 2.98 .49 .64 .78 56.5 16.6 3.33 .49 .65 .80 53.5 15.7 3.72 .50 .66 .82 50.5 14.8 4.16 .50 .68 .84

FIRST STAGE COOLING CAPACITY − XC21−048 with [CX34−62D−6F + G61MPV−60D−135][C33−62D + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F985 465 35.8 10.5 1.65 .74 .87 .99 34.4 10.1 1.91 .75 .89 1.00 32.8 9.6 2.20 .77 .91 1.00 31.2 9.1 2.54 .79 .94 1.00

63�F(17�C)

1115 525 37.0 10.8 1.64 .77 .91 1.00 35.6 10.4 1.90 .78 .93 1.00 34.0 10.0 2.20 .80 .95 1.00 32.2 9.4 2.53 .82 .98 1.00(17�C)

1235 585 38.0 11.1 1.64 .79 .94 1.00 36.4 10.7 1.90 .81 .96 1.00 34.8 10.2 2.19 .82 .98 1.00 33.0 9.7 2.52 .85 1.00 1.00

67�F985 465 38.0 11.1 1.64 .59 .72 .84 36.6 10.7 1.90 .60 .73 .85 35.0 10.3 2.19 .61 .74 .87 33.2 9.7 2.52 .62 .76 .90

67�F(19�C)

1115 525 39.5 11.6 1.64 .60 .74 .87 37.8 11.1 1.89 .62 .76 .89 36.2 10.6 2.18 .63 .77 .91 34.2 10.0 2.51 .64 .79 .94(19�C)

1235 585 40.5 11.9 1.63 .62 .77 .90 39.0 11.4 1.89 .63 .78 .92 37.0 10.8 2.17 .64 .80 .95 35.0 10.3 2.50 .65 .82 .97

71�F985 465 40.5 11.9 1.63 .45 .58 .69 39.0 11.4 1.89 .46 .58 .70 37.0 10.8 2.18 .46 .58 .72 35.4 10.4 2.50 .47 .60 .73

71�F(22�C)

1115 525 41.5 12.2 1.63 .46 .59 .72 40.0 11.7 1.88 .47 .59 .73 38.0 11.1 2.17 .47 .61 .75 36.4 10.7 2.50 .48 .62 .76(22�C)

1235 585 42.5 12.5 1.63 .47 .61 .74 41.0 12.0 1.88 .48 .62 .75 39.0 11.4 2.16 .48 .63 .77 37.2 10.9 2.49 .48 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−048 with [CX34−62D−6F + G61MPV−60D−135][C33−62D + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 49.5 14.5 2.88 .75 .88 1.00 47.5 13.9 3.23 .77 .91 1.00 45.0 13.2 3.62 .78 .93 1.00 42.5 12.5 4.06 .80 .96 1.00

63�F(17�C)

1600 755 51.0 14.9 2.89 .78 .93 1.00 49.0 14.4 3.25 .80 .95 1.00 46.5 13.6 3.64 .82 .97 1.00 44.0 12.9 4.08 .84 1.00 1.00(17�C)

1780 840 52.5 15.4 2.91 .81 .96 1.00 50.0 14.7 3.26 .83 .98 1.00 47.5 13.9 3.65 .84 1.00 1.00 45.0 13.2 4.09 .87 1.00 1.00

67�F1400 660 52.5 15.4 2.91 .60 .73 .85 50.0 14.7 3.26 .61 .74 .87 48.0 14.1 3.66 .62 .76 .89 45.5 13.3 4.10 .63 .78 .92

67�F(19�C)

1600 755 54.0 15.8 2.93 .62 .76 .89 52.0 15.2 3.28 .63 .78 .91 49.5 14.5 3.67 .64 .79 .94 46.5 13.6 4.11 .66 .81 .97(19�C)

1780 840 55.5 16.3 2.94 .64 .79 .93 53.0 15.5 3.29 .65 .80 .95 50.5 14.8 3.68 .66 .82 .97 47.5 13.9 4.12 .67 .84 1.00

71�F1400 660 55.5 16.3 2.94 .46 .59 .70 53.0 15.5 3.29 .46 .59 .72 50.5 14.8 3.69 .47 .61 .73 48.0 14.1 4.13 .48 .62 .75

71�F(22�C)

1600 755 57.0 16.7 2.96 .47 .60 .73 55.0 16.1 3.31 .48 .62 .75 52.0 15.2 3.71 .48 .63 .77 49.0 14.4 4.15 .49 .64 .79(22�C)

1780 840 58.5 17.1 2.97 .48 .63 .76 56.0 16.4 3.33 .49 .64 .78 53.0 15.5 3.72 .49 .65 .80 50.5 14.8 4.16 .50 .66 .82

Page 87: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 4 TON

DOWN−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 87

FIRST STAGE COOLING CAPACITY − XC21−048 with [CR26−48N/W−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 35.0 10.3 1.63 .77 .90 1.00 33.6 9.8 1.89 .78 .92 1.00 32.0 9.4 2.18 .80 .94 1.00 30.4 8.9 2.51 .82 .97 1.00

63�F(17�C)

1200 565 35.6 10.4 1.63 .78 .93 1.00 34.2 10.0 1.89 .80 .95 1.00 32.6 9.6 2.17 .82 .97 1.00 31.0 9.1 2.51 .84 .99 1.00(17�C)

1300 615 36.2 10.6 1.63 .80 .95 1.00 34.8 10.2 1.88 .82 .97 1.00 33.2 9.7 2.17 .84 .99 1.00 31.6 9.3 2.50 .86 1.00 1.00

67�F1100 520 37.4 11.0 1.62 .61 .74 .87 35.8 10.5 1.88 .63 .76 .88 34.2 10.0 2.16 .63 .77 .91 32.6 9.6 2.49 .64 .79 .93

67�F(19�C)

1200 565 38.0 11.1 1.62 .63 .76 .89 36.6 10.7 1.87 .63 .77 .91 34.8 10.2 2.16 .64 .79 .93 33.0 9.7 2.49 .66 .81 .96(19�C)

1300 615 39.0 11.4 1.62 .64 .78 .91 37.2 10.9 1.87 .65 .79 .93 35.4 10.4 2.16 .66 .81 .96 33.6 9.8 2.48 .67 .83 .98

71�F1100 520 40.0 11.7 1.62 .47 .60 .72 38.0 11.1 1.87 .47 .61 .73 36.4 10.7 2.15 .48 .62 .74 34.6 10.1 2.47 .49 .63 .76

71�F(22�C)

1200 565 40.5 11.9 1.62 .47 .61 .73 39.0 11.4 1.87 .48 .62 .75 37.2 10.9 2.15 .48 .63 .76 35.2 10.3 2.46 .49 .64 .78(22�C)

1300 615 41.0 12.0 1.62 .48 .62 .75 39.5 11.6 1.86 .49 .63 .76 37.8 11.1 2.14 .49 .64 .78 35.8 10.5 2.46 .50 .66 .80

SECOND STAGE COOLING CAPACITY − XC21−048 with [CR26−48N/W−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 46.5 13.6 2.84 .76 .88 1.00 44.5 13.0 3.18 .77 .90 1.00 42.0 12.3 3.57 .78 .92 1.00 40.0 11.7 3.99 .80 .95 1.00

63�F(17�C)

1600 755 47.5 13.9 2.85 .78 .92 1.00 45.5 13.3 3.20 .79 .94 1.00 43.5 12.7 3.58 .81 .96 1.00 41.0 12.0 4.01 .83 .99 1.00(17�C)

1800 850 49.0 14.4 2.86 .80 .95 1.00 46.5 13.6 3.21 .82 .97 1.00 44.5 13.0 3.59 .84 .99 1.00 42.0 12.3 4.02 .86 1.00 1.00

67�F1400 660 49.5 14.5 2.87 .61 .73 .85 47.5 13.9 3.21 .62 .74 .87 45.0 13.2 3.60 .63 .76 .89 42.5 12.5 4.03 .64 .78 .91

67�F(19�C)

1600 755 50.5 14.8 2.88 .63 .76 .89 48.5 14.2 3.23 .63 .77 .90 46.0 13.5 3.61 .64 .79 .93 43.5 12.7 4.04 .66 .81 .96(19�C)

1800 850 52.0 15.2 2.89 .64 .78 .92 49.5 14.5 3.24 .65 .80 .94 47.0 13.8 3.62 .66 .81 .96 44.5 13.0 4.05 .68 .84 .99

71�F1400 660 52.5 15.4 2.90 .47 .59 .71 50.0 14.7 3.24 .47 .60 .72 47.5 13.9 3.63 .48 .61 .73 45.0 13.2 4.06 .48 .62 .75

71�F(22�C)

1600 755 53.5 15.7 2.91 .48 .61 .73 51.5 15.1 3.26 .48 .62 .75 49.0 14.4 3.65 .49 .63 .76 46.0 13.5 4.08 .49 .64 .78(22�C)

1800 850 55.0 16.1 2.93 .49 .63 .76 52.5 15.4 3.27 .49 .64 .77 50.0 14.7 3.66 .49 .65 .79 47.0 13.8 4.09 .50 .66 .81

FIRST STAGE COOLING CAPACITY − XC21−048 with [CR26−60N/W−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 36.2 10.6 1.63 .78 .92 1.00 34.8 10.2 1.88 .79 .94 1.00 33.0 9.7 2.17 .81 .96 1.00 31.4 9.2 2.50 .83 .99 1.00

63�F(17�C)

1200 565 37.0 10.8 1.63 .80 .95 1.00 35.4 10.4 1.88 .81 .97 1.00 33.8 9.9 2.16 .83 .99 1.00 32.2 9.4 2.49 .86 1.00 1.00(17�C)

1300 615 37.6 11.0 1.62 .82 .97 1.00 36.0 10.6 1.88 .83 .99 1.00 34.6 10.1 2.16 .85 1.00 1.00 33.0 9.7 2.48 .88 1.00 1.00

67�F1100 520 38.5 11.3 1.62 .62 .75 .88 37.2 10.9 1.87 .63 .77 .90 35.4 10.4 2.15 .64 .78 .93 33.6 9.8 2.48 .65 .80 .95

67�F(19�C)

1200 565 39.5 11.6 1.62 .63 .77 .91 37.8 11.1 1.87 .64 .79 .93 36.0 10.6 2.15 .65 .81 .95 34.2 10.0 2.47 .67 .83 .98(19�C)

1300 615 40.0 11.7 1.62 .65 .79 .94 38.5 11.3 1.87 .65 .81 .96 36.6 10.7 2.15 .67 .83 .98 34.6 10.1 2.47 .68 .85 1.00

71�F1100 520 41.0 12.0 1.62 .47 .61 .73 39.5 11.6 1.86 .48 .61 .74 37.6 11.0 2.14 .48 .62 .76 35.8 10.5 2.47 .49 .64 .78

71�F(22�C)

1200 565 42.0 12.3 1.62 .48 .62 .75 40.0 11.7 1.86 .48 .63 .76 38.5 11.3 2.14 .49 .64 .78 36.4 10.7 2.46 .50 .65 .80(22�C)

1300 615 42.5 12.5 1.61 .48 .63 .77 41.0 12.0 1.86 .49 .64 .78 39.0 11.4 2.14 .50 .65 .80 37.0 10.8 2.46 .51 .67 .82

SECOND STAGE COOLING CAPACITY − XC21−048 with [CR26−60N/W−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 48.0 14.1 2.85 .77 .90 1.00 46.0 13.5 3.20 .78 .92 1.00 43.5 12.7 3.58 .80 .95 1.00 41.0 12.0 4.01 .82 .97 1.00

63�F(17�C)

1600 755 49.5 14.5 2.87 .80 .94 1.00 47.5 13.9 3.21 .81 .96 1.00 45.0 13.2 3.60 .83 .98 1.00 42.5 12.5 4.03 .85 1.00 1.00(17�C)

1800 850 50.5 14.8 2.88 .82 .98 1.00 48.5 14.2 3.23 .84 .99 1.00 46.5 13.6 3.61 .86 1.00 1.00 44.0 12.9 4.05 .89 1.00 1.00

67�F1400 660 51.0 14.9 2.89 .62 .74 .87 49.0 14.4 3.23 .62 .76 .89 46.5 13.6 3.62 .63 .77 .91 44.0 12.9 4.04 .65 .79 .94

67�F(19�C)

1600 755 52.5 15.4 2.90 .63 .77 .91 50.5 14.8 3.25 .64 .79 .93 47.5 13.9 3.63 .65 .81 .95 45.0 13.2 4.06 .67 .83 .98(19�C)

1800 850 53.5 15.7 2.91 .65 .80 .95 51.5 15.1 3.26 .66 .82 .97 48.5 14.2 3.64 .67 .84 .99 46.0 13.5 4.08 .69 .86 1.00

71�F1400 660 54.0 15.8 2.92 .47 .60 .72 52.0 15.2 3.26 .47 .61 .73 49.5 14.5 3.65 .47 .62 .75 46.5 13.6 4.08 .48 .63 .77

71�F(22�C)

1600 755 55.5 16.3 2.94 .48 .62 .76 53.0 15.5 3.28 .48 .63 .76 50.5 14.8 3.67 .49 .64 .78 47.5 13.9 4.10 .50 .66 .81(22�C)

1800 850 57.0 16.7 2.95 .49 .64 .78 54.5 16.0 3.30 .49 .65 .80 51.5 15.1 3.68 .50 .66 .82 48.5 14.2 4.11 .51 .68 .84

Page 88: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 4 TON

DOWN−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 88

FIRST STAGE COOLING CAPACITY − XC21−048 with [CR26−48N−F + G60DFV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1050 495 34.6 10.1 1.64 .75 .88 1.00 33.2 9.7 1.91 .76 .90 1.00 31.6 9.3 2.20 .78 .92 1.00 29.8 8.7 2.54 .79 .94 1.00

63�F(17�C)

1165 550 35.4 10.4 1.64 .77 .91 1.00 33.8 9.9 1.90 .78 .93 1.00 32.4 9.5 2.19 .80 .95 1.00 30.6 9.0 2.53 .82 .98 1.00(17�C)

1280 605 36.0 10.6 1.64 .79 .94 1.00 34.6 10.1 1.90 .80 .96 1.00 32.8 9.6 2.19 .82 .98 1.00 31.4 9.2 2.51 .84 1.00 1.00

67�F1050 495 37.0 10.8 1.63 .60 .72 .85 35.4 10.4 1.89 .61 .74 .86 33.8 9.9 2.18 .62 .75 .88 32.0 9.4 2.51 .63 .77 .91

67�F(19�C)

1165 550 37.8 11.1 1.63 .61 .74 .87 36.2 10.6 1.89 .62 .76 .89 34.6 10.1 2.17 .63 .77 .91 32.8 9.6 2.50 .64 .79 .94(19�C)

1280 605 38.5 11.3 1.63 .62 .76 .90 37.0 10.8 1.88 .63 .78 .92 35.2 10.3 2.17 .64 .79 .94 33.4 9.8 2.50 .66 .82 .97

71�F1050 495 39.5 11.6 1.63 .45 .58 .70 37.6 11.0 1.88 .46 .59 .71 36.0 10.6 2.16 .46 .60 .72 34.2 10.0 2.49 .46 .61 .74

71�F(22�C)

1165 550 40.0 11.7 1.62 .46 .60 .72 38.5 11.3 1.88 .46 .61 .73 36.8 10.8 2.16 .47 .61 .75 35.0 10.3 2.49 .48 .63 .77(22�C)

1280 605 41.0 12.0 1.62 .47 .61 .74 39.5 11.6 1.88 .47 .62 .75 37.6 11.0 2.16 .48 .63 .77 35.6 10.4 2.48 .49 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−048 with [CR26−48N−F + G60DFV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1510 715 47.0 13.8 2.85 .76 .90 1.00 45.0 13.2 3.20 .78 .92 1.00 43.0 12.6 3.59 .79 .94 1.00 40.5 11.9 4.02 .81 .97 1.00

63�F(17�C)

1685 795 48.5 14.2 2.86 .78 .93 1.00 46.0 13.5 3.21 .80 .95 1.00 44.0 12.9 3.60 .82 .97 1.00 41.5 12.2 4.03 .84 .99 1.00(17�C)

1860 880 49.0 14.4 2.87 .81 .96 1.00 47.0 13.8 3.22 .82 .98 1.00 44.5 13.0 3.61 .84 .99 1.00 42.5 12.5 4.04 .87 1.00 1.00

67�F1510 715 50.0 14.7 2.88 .61 .74 .86 48.0 14.1 3.23 .62 .75 .88 45.5 13.3 3.62 .63 .77 .90 43.0 12.6 4.05 .64 .79 .93

67�F(19�C)

1685 795 51.5 15.1 2.89 .63 .76 .89 49.0 14.4 3.24 .64 .78 .91 46.5 13.6 3.63 .65 .79 .94 44.0 12.9 4.07 .66 .81 .97(19�C)

1860 880 52.5 15.4 2.90 .64 .78 .93 50.0 14.7 3.25 .65 .80 .95 47.5 13.9 3.64 .66 .82 .97 44.5 13.0 4.08 .68 .84 .99

71�F1510 715 53.0 15.5 2.91 .47 .60 .71 51.0 14.9 3.27 .47 .61 .73 48.5 14.2 3.65 .47 .62 .74 46.0 13.5 4.09 .48 .63 .76

71�F(22�C)

1685 795 54.5 16.0 2.92 .47 .61 .74 52.0 15.2 3.27 .48 .62 .75 49.5 14.5 3.66 .49 .63 .77 46.5 13.6 4.10 .49 .65 .79(22�C)

1860 880 55.5 16.3 2.94 .48 .63 .76 53.0 15.5 3.29 .49 .64 .78 50.5 14.8 3.67 .49 .65 .79 47.5 13.9 4.11 .50 .66 .82

FIRST STAGE COOLING CAPACITY − XC21−048 with [CR26−48N−F + G61MPV−60C−110]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F805 380 32.2 9.4 1.64 .71 .82 .93 31.0 9.1 1.91 .72 .84 .95 29.6 8.7 2.20 .73 .85 .97 28.0 8.2 2.54 .74 .87 .99

63�F(17�C)

925 435 33.4 9.8 1.64 .73 .85 .97 32.0 9.4 1.90 .74 .87 .99 30.6 9.0 2.19 .75 .89 1.00 29.0 8.5 2.52 .77 .91 1.00(17�C)

1050 495 34.4 10.1 1.63 .75 .88 1.00 33.0 9.7 1.89 .76 .90 1.00 31.4 9.2 2.18 .78 .92 1.00 29.8 8.7 2.52 .79 .95 1.00

67�F805 380 34.4 10.1 1.63 .57 .68 .79 33.0 9.7 1.89 .58 .69 .80 31.6 9.3 2.18 .59 .70 .82 30.0 8.8 2.51 .60 .72 .84

67�F(19�C)

925 435 35.8 10.5 1.63 .59 .70 .82 34.4 10.1 1.89 .59 .72 .83 32.8 9.6 2.17 .60 .73 .85 31.0 9.1 2.50 .61 .74 .87(19�C)

1050 495 36.8 10.8 1.62 .60 .73 .85 35.4 10.4 1.88 .61 .74 .86 33.8 9.9 2.17 .62 .75 .88 32.0 9.4 2.50 .63 .77 .91

71�F805 380 36.4 10.7 1.62 .44 .55 .66 35.0 10.3 1.88 .44 .56 .67 33.6 9.8 2.17 .45 .57 .68 32.0 9.4 2.49 .45 .58 .69

71�F(22�C)

925 435 38.0 11.1 1.62 .45 .57 .68 36.4 10.7 1.87 .45 .58 .69 35.0 10.3 2.16 .45 .59 .70 33.2 9.7 2.48 .46 .60 .72(22�C)

1050 495 39.0 11.4 1.62 .46 .59 .70 37.6 11.0 1.87 .46 .59 .71 36.0 10.6 2.15 .46 .60 .73 34.0 10.0 2.47 .46 .61 .74

SECOND STAGE COOLING CAPACITY − XC21−048 with [CR26−48N−F + G61MPV−60C−110]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1405 665 46.5 13.6 2.83 .75 .88 .99 44.5 13.0 3.18 .76 .90 1.00 42.0 12.3 3.57 .78 .92 1.00 39.5 11.6 3.99 .80 .95 1.00

63�F(17�C)

1610 760 47.5 13.9 2.85 .78 .92 1.00 45.5 13.3 3.19 .79 .94 1.00 43.5 12.7 3.58 .81 .96 1.00 41.0 12.0 4.01 .83 .98 1.00(17�C)

1795 845 48.5 14.2 2.86 .80 .95 1.00 46.5 13.6 3.21 .82 .97 1.00 44.0 12.9 3.59 .83 .99 1.00 42.0 12.3 4.02 .86 1.00 1.00

67�F1405 665 49.5 14.5 2.87 .61 .73 .85 47.0 13.8 3.21 .61 .74 .86 45.0 13.2 3.60 .62 .75 .88 42.5 12.5 4.03 .63 .77 .91

67�F(19�C)

1610 760 50.5 14.8 2.88 .62 .75 .88 48.5 14.2 3.23 .63 .77 .90 46.0 13.5 3.61 .64 .78 .93 43.5 12.7 4.04 .65 .81 .96(19�C)

1795 845 52.0 15.2 2.89 .64 .78 .92 49.5 14.5 3.24 .65 .79 .94 47.0 13.8 3.62 .66 .81 .96 44.5 13.0 4.05 .67 .83 .99

71�F1405 665 52.0 15.2 2.90 .46 .59 .70 50.0 14.7 3.24 .46 .60 .72 47.5 13.9 3.63 .47 .61 .73 45.0 13.2 4.06 .48 .62 .75

71�F(22�C)

1610 760 53.5 15.7 2.91 .47 .61 .73 51.5 15.1 3.26 .48 .62 .74 49.0 14.4 3.65 .48 .63 .76 46.0 13.5 4.08 .48 .64 .78(22�C)

1795 845 55.0 16.1 2.93 .48 .62 .75 52.5 15.4 3.27 .49 .63 .77 50.0 14.7 3.66 .49 .65 .79 47.0 13.8 4.09 .50 .66 .81

Page 89: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 4 TON

DOWN−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 89

FIRST STAGE COOLING CAPACITY − XC21−048 with [CR26−60W−F + G60DFV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1045 495 35.6 10.4 1.64 .76 .89 1.00 34.2 10.0 1.90 .77 .91 1.00 32.6 9.6 2.19 .79 .94 1.00 30.8 9.0 2.53 .81 .96 1.00

63�F(17�C)

1160 550 36.6 10.7 1.63 .78 .93 1.00 35.0 10.3 1.89 .79 .95 1.00 33.2 9.7 2.18 .81 .97 1.00 31.6 9.3 2.51 .83 .99 1.00(17�C)

1270 600 37.2 10.9 1.63 .80 .96 1.00 35.6 10.4 1.89 .82 .98 1.00 34.2 10.0 2.18 .84 .99 1.00 32.6 9.6 2.50 .86 1.00 1.00

67�F1045 495 38.0 11.1 1.63 .60 .73 .86 36.6 10.7 1.88 .61 .74 .88 34.8 10.2 2.17 .62 .76 .90 33.0 9.7 2.50 .63 .78 .92

67�F(19�C)

1160 550 39.0 11.4 1.63 .62 .75 .89 37.4 11.0 1.88 .63 .77 .91 35.8 10.5 2.17 .64 .79 .93 33.8 9.9 2.50 .65 .81 .96(19�C)

1270 600 40.0 11.7 1.63 .63 .78 .92 38.0 11.1 1.88 .64 .79 .94 36.4 10.7 2.17 .65 .81 .96 34.4 10.1 2.49 .66 .83 .99

71�F1045 495 40.5 11.9 1.62 .45 .59 .71 39.0 11.4 1.88 .46 .60 .72 37.0 10.8 2.16 .46 .60 .73 35.2 10.3 2.48 .47 .62 .75

71�F(22�C)

1160 550 41.5 12.2 1.62 .46 .60 .73 40.0 11.7 1.87 .47 .61 .74 38.0 11.1 2.15 .47 .62 .76 36.0 10.6 2.48 .48 .63 .78(22�C)

1270 600 42.5 12.5 1.62 .47 .62 .75 40.5 11.9 1.87 .47 .63 .77 38.5 11.3 2.15 .48 .64 .78 36.6 10.7 2.47 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−048 with [CR26−60W−F + G60DFV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1500 710 49.0 14.4 2.87 .77 .92 1.00 46.5 13.6 3.21 .79 .94 1.00 44.5 13.0 3.60 .81 .96 1.00 42.0 12.3 4.04 .83 .98 1.00

63�F(17�C)

1680 795 50.0 14.7 2.88 .80 .95 1.00 48.0 14.1 3.23 .82 .97 1.00 45.5 13.3 3.62 .84 .99 1.00 43.0 12.6 4.05 .86 1.00 1.00(17�C)

1865 880 51.0 14.9 2.89 .83 .98 1.00 49.0 14.4 3.24 .85 .99 1.00 46.5 13.6 3.63 .87 1.00 1.00 44.5 13.0 4.07 .90 1.00 1.00

67�F1500 710 52.0 15.2 2.90 .62 .75 .88 49.5 14.5 3.25 .63 .76 .90 47.0 13.8 3.64 .64 .78 .93 44.5 13.0 4.07 .65 .80 .95

67�F(19�C)

1680 795 53.0 15.5 2.91 .63 .78 .92 51.0 14.9 3.26 .64 .79 .94 48.0 14.1 3.65 .66 .81 .96 45.5 13.3 4.08 .67 .84 .99(19�C)

1865 880 54.0 15.8 2.92 .65 .80 .95 51.5 15.1 3.27 .66 .82 .97 49.0 14.4 3.66 .68 .84 .99 46.0 13.5 4.09 .69 .87 1.00

71�F1500 710 55.0 16.1 2.93 .46 .60 .73 52.5 15.4 3.28 .47 .61 .74 50.0 14.7 3.67 .47 .62 .76 47.0 13.8 4.11 .48 .64 .78

71�F(22�C)

1680 795 56.0 16.4 2.95 .47 .62 .75 54.0 15.8 3.30 .48 .63 .77 51.0 14.9 3.69 .49 .64 .79 48.5 14.2 4.12 .49 .66 .81(22�C)

1865 880 57.5 16.9 2.96 .49 .64 .78 55.0 16.1 3.31 .49 .65 .80 52.0 15.2 3.70 .50 .66 .82 49.0 14.4 4.13 .51 .68 .85

FIRST STAGE COOLING CAPACITY − XC21−048 with [CR26−60W−F + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F985 465 35.2 10.3 1.63 .75 .88 .99 33.6 9.8 1.89 .76 .90 1.00 32.0 9.4 2.18 .77 .92 1.00 30.4 8.9 2.51 .79 .94 1.00

63�F(17�C)

1115 525 36.2 10.6 1.63 .77 .92 1.00 34.6 10.1 1.88 .79 .94 1.00 33.0 9.7 2.17 .80 .96 1.00 31.2 9.1 2.50 .82 .98 1.00(17�C)

1235 585 37.0 10.8 1.63 .80 .95 1.00 35.4 10.4 1.88 .81 .97 1.00 33.8 9.9 2.16 .83 .99 1.00 32.2 9.4 2.49 .85 1.00 1.00

67�F985 465 37.4 11.0 1.62 .60 .72 .84 36.0 10.6 1.88 .60 .73 .86 34.4 10.1 2.16 .61 .75 .88 32.6 9.6 2.49 .62 .76 .90

67�F(19�C)

1115 525 38.5 11.3 1.62 .61 .75 .88 37.0 10.8 1.87 .62 .76 .90 35.4 10.4 2.15 .63 .78 .92 33.4 9.8 2.48 .64 .80 .95(19�C)

1235 585 39.5 11.6 1.62 .63 .77 .91 37.8 11.1 1.87 .64 .79 .93 36.0 10.6 2.15 .65 .80 .96 34.2 10.0 2.48 .66 .83 .98

71�F985 465 39.5 11.6 1.62 .45 .58 .70 38.0 11.1 1.87 .45 .59 .71 36.4 10.7 2.15 .46 .60 .72 34.6 10.1 2.47 .46 .61 .74

71�F(22�C)

1115 525 41.0 12.0 1.62 .46 .60 .72 39.5 11.6 1.86 .46 .61 .73 37.6 11.0 2.15 .47 .62 .75 35.6 10.4 2.47 .48 .63 .77(22�C)

1235 585 42.0 12.3 1.62 .47 .61 .74 40.5 11.9 1.86 .47 .62 .76 38.5 11.3 2.14 .48 .63 .78 36.4 10.7 2.46 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−048 with [CR26−60W−F + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 48.0 14.1 2.85 .76 .90 1.00 46.0 13.5 3.19 .77 .92 1.00 43.5 12.7 3.58 .79 .94 1.00 41.0 12.0 4.01 .81 .97 1.00

63�F(17�C)

1600 755 49.5 14.5 2.86 .79 .94 1.00 47.0 13.8 3.21 .81 .96 1.00 44.5 13.0 3.59 .83 .98 1.00 42.5 12.5 4.02 .85 1.00 1.00(17�C)

1780 840 50.5 14.8 2.88 .82 .97 1.00 48.0 14.1 3.22 .83 .99 1.00 46.0 13.5 3.61 .85 1.00 1.00 43.5 12.7 4.04 .88 1.00 1.00

67�F1400 660 51.0 14.9 2.88 .61 .74 .86 49.0 14.4 3.23 .62 .75 .88 46.5 13.6 3.62 .63 .77 .90 43.5 12.7 4.04 .64 .79 .93

67�F(19�C)

1600 755 52.5 15.4 2.90 .63 .77 .90 50.0 14.7 3.24 .64 .78 .93 47.5 13.9 3.63 .65 .80 .95 45.0 13.2 4.06 .66 .82 .98(19�C)

1780 840 53.5 15.7 2.91 .65 .79 .94 51.0 14.9 3.26 .66 .81 .96 48.5 14.2 3.64 .67 .83 .98 45.5 13.3 4.07 .68 .86 1.00

71�F1400 660 54.0 15.8 2.92 .46 .59 .71 51.5 15.1 3.26 .46 .60 .73 49.0 14.4 3.65 .47 .61 .74 46.5 13.6 4.08 .47 .63 .76

71�F(22�C)

1600 755 55.5 16.3 2.93 .47 .61 .74 53.0 15.5 3.28 .48 .62 .76 50.5 14.8 3.67 .48 .64 .78 47.5 13.9 4.10 .49 .65 .80(22�C)

1780 840 56.5 16.6 2.95 .48 .63 .77 54.0 15.8 3.29 .49 .64 .79 51.5 15.1 3.68 .50 .66 .81 48.5 14.2 4.11 .50 .67 .83

Page 90: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 4 TON

HORIZONTAL INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 90

FIRST STAGE COOLING CAPACITY − XC21−048 with [CH23−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 35.2 10.3 1.64 .76 .90 1.00 33.8 9.9 1.90 .77 .92 1.00 32.2 9.4 2.19 .79 .94 1.00 30.4 8.9 2.53 .81 .96 1.00

63�F(17�C)

1200 565 36.0 10.6 1.64 .78 .92 1.00 34.4 10.1 1.90 .79 .94 1.00 32.8 9.6 2.19 .81 .96 1.00 31.2 9.1 2.52 .83 .99 1.00(17�C)

1300 615 36.6 10.7 1.64 .80 .95 1.00 35.0 10.3 1.89 .81 .96 1.00 33.4 9.8 2.18 .83 .99 1.00 32.0 9.4 2.51 .85 1.00 1.00

67�F1100 520 37.8 11.1 1.63 .61 .73 .86 36.2 10.6 1.89 .62 .75 .88 34.6 10.1 2.18 .63 .76 .90 32.8 9.6 2.51 .64 .78 .93

67�F(19�C)

1200 565 38.5 11.3 1.63 .62 .75 .88 37.0 10.8 1.89 .63 .77 .90 35.2 10.3 2.17 .64 .78 .93 33.4 9.8 2.50 .65 .80 .95(19�C)

1300 615 39.0 11.4 1.63 .63 .77 .91 37.6 11.0 1.88 .64 .78 .93 35.8 10.5 2.17 .65 .80 .95 33.8 9.9 2.49 .66 .82 .98

71�F1100 520 40.0 11.7 1.62 .47 .59 .71 38.5 11.3 1.88 .47 .60 .72 37.0 10.8 2.16 .48 .61 .74 35.0 10.3 2.49 .48 .62 .76

71�F(22�C)

1200 565 41.0 12.0 1.62 .48 .60 .73 39.5 11.6 1.87 .47 .61 .74 37.6 11.0 2.16 .48 .62 .76 35.6 10.4 2.48 .49 .63 .78(22�C)

1300 615 41.5 12.2 1.62 .48 .61 .74 40.0 11.7 1.87 .48 .62 .76 38.0 11.1 2.15 .49 .64 .77 36.2 10.6 2.48 .50 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−048 with [CH23−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 47.0 13.8 2.84 .75 .88 .99 45.0 13.2 3.19 .76 .89 1.00 42.5 12.5 3.58 .78 .92 1.00 40.0 11.7 4.01 .80 .94 1.00

63�F(17�C)

1600 755 48.0 14.1 2.86 .77 .91 1.00 46.0 13.5 3.21 .79 .93 1.00 43.5 12.7 3.59 .80 .95 1.00 41.0 12.0 4.03 .83 .98 1.00(17�C)

1800 850 49.0 14.4 2.87 .80 .95 1.00 47.0 13.8 3.22 .81 .96 1.00 44.5 13.0 3.61 .83 .99 1.00 42.5 12.5 4.04 .86 1.00 1.00

67�F1400 660 50.0 14.7 2.88 .60 .72 .84 48.0 14.1 3.23 .61 .73 .86 45.5 13.3 3.62 .62 .75 .88 43.0 12.6 4.05 .63 .77 .91

67�F(19�C)

1600 755 51.5 15.1 2.89 .62 .75 .88 49.0 14.4 3.24 .62 .76 .90 46.5 13.6 3.63 .64 .78 .92 44.0 12.9 4.07 .65 .80 .95(19�C)

1800 850 52.5 15.4 2.91 .63 .77 .91 50.0 14.7 3.26 .64 .79 .94 47.5 13.9 3.64 .65 .81 .96 45.0 13.2 4.08 .67 .83 .98

71�F1400 660 53.0 15.5 2.91 .46 .59 .70 50.5 14.8 3.26 .47 .59 .71 48.0 14.1 3.65 .47 .60 .72 45.5 13.3 4.09 .48 .61 .74

71�F(22�C)

1600 755 54.5 16.0 2.93 .47 .60 .72 52.0 15.2 3.28 .47 .61 .74 49.5 14.5 3.67 .48 .62 .76 47.0 13.8 4.10 .49 .64 .78(22�C)

1800 850 55.5 16.3 2.94 .48 .62 .75 53.0 15.5 3.29 .48 .63 .76 50.5 14.8 3.68 .49 .64 .78 48.0 14.1 4.11 .50 .65 .81

FIRST STAGE COOLING CAPACITY − XC21−048 with [CH23−65]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 35.8 10.5 1.64 .77 .90 1.00 34.2 10.0 1.90 .78 .92 1.00 32.6 9.6 2.19 .80 .95 1.00 30.8 9.0 2.52 .81 .97 1.00

63�F(17�C)

1200 565 36.4 10.7 1.64 .78 .93 1.00 34.8 10.2 1.90 .80 .95 1.00 33.2 9.7 2.18 .81 .97 1.00 31.6 9.3 2.52 .84 .99 1.00(17�C)

1300 615 37.0 10.8 1.63 .80 .95 1.00 35.6 10.4 1.89 .82 .97 1.00 33.8 9.9 2.18 .83 .99 1.00 32.4 9.5 2.51 .86 1.00 1.00

67�F1100 520 38.5 11.3 1.63 .61 .74 .87 36.8 10.8 1.89 .62 .75 .88 35.0 10.3 2.17 .63 .77 .91 33.2 9.7 2.50 .64 .79 .93

67�F(19�C)

1200 565 39.0 11.4 1.63 .62 .76 .89 37.4 11.0 1.88 .63 .77 .91 35.6 10.4 2.17 .64 .79 .94 33.8 9.9 2.49 .65 .81 .96(19�C)

1300 615 39.5 11.6 1.63 .63 .77 .91 38.0 11.1 1.88 .64 .79 .94 36.2 10.6 2.16 .65 .81 .96 34.2 10.0 2.49 .67 .83 .98

71�F1100 520 40.5 11.9 1.62 .47 .60 .71 39.0 11.4 1.88 .47 .60 .72 37.4 11.0 2.16 .48 .61 .74 35.4 10.4 2.48 .48 .63 .76

71�F(22�C)

1200 565 41.5 12.2 1.62 .47 .61 .73 40.0 11.7 1.87 .48 .62 .74 38.0 11.1 2.16 .48 .63 .76 36.2 10.6 2.48 .49 .64 .78(22�C)

1300 615 42.5 12.5 1.62 .48 .62 .75 40.5 11.9 1.87 .48 .63 .76 38.5 11.3 2.15 .49 .64 .78 36.6 10.7 2.47 .50 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−048 with [CH23−65]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 47.5 13.9 2.85 .75 .88 .99 45.5 13.3 3.20 .76 .90 1.00 43.0 12.6 3.59 .78 .92 1.00 40.5 11.9 4.02 .80 .95 1.00

63�F(17�C)

1600 755 49.0 14.4 2.87 .78 .92 1.00 46.5 13.6 3.22 .79 .94 1.00 44.0 12.9 3.60 .81 .96 1.00 42.0 12.3 4.03 .83 .99 1.00(17�C)

1800 850 50.0 14.7 2.88 .80 .95 1.00 47.5 13.9 3.23 .82 .97 1.00 45.5 13.3 3.61 .84 .99 1.00 43.0 12.6 4.06 .87 1.00 1.00

67�F1400 660 50.5 14.8 2.88 .60 .73 .85 48.5 14.2 3.24 .61 .74 .87 46.0 13.5 3.62 .62 .76 .89 43.5 12.7 4.06 .63 .78 .92

67�F(19�C)

1600 755 52.0 15.2 2.90 .62 .75 .88 49.5 14.5 3.25 .63 .77 .90 47.0 13.8 3.64 .64 .79 .93 44.5 13.0 4.07 .65 .81 .96(19�C)

1800 850 53.0 15.5 2.91 .63 .78 .92 51.0 14.9 3.26 .64 .80 .94 48.5 14.2 3.65 .66 .82 .97 45.5 13.3 4.08 .67 .84 .99

71�F1400 660 53.5 15.7 2.92 .46 .59 .70 51.5 15.1 3.26 .46 .59 .71 49.0 14.4 3.66 .47 .61 .73 46.0 13.5 4.10 .48 .62 .75

71�F(22�C)

1600 755 55.0 16.1 2.93 .47 .60 .73 53.0 15.5 3.28 .47 .61 .74 50.0 14.7 3.67 .48 .62 .76 47.5 13.9 4.11 .49 .64 .78(22�C)

1800 850 56.5 16.6 2.95 .48 .62 .75 54.0 15.8 3.30 .49 .63 .77 51.5 15.1 3.69 .49 .64 .79 48.5 14.2 4.12 .50 .66 .81

Page 91: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 4 TON

HORIZONTAL INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 91

FIRST STAGE COOLING CAPACITY − XC21−048 with [CH23−68]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 37.0 10.8 1.63 .78 .91 1.00 35.4 10.4 1.89 .79 .93 1.00 33.8 9.9 2.18 .81 .96 1.00 32.0 9.4 2.51 .83 .98 1.00

63�F(17�C)

1200 565 37.8 11.1 1.63 .80 .94 1.00 36.2 10.6 1.89 .81 .96 1.00 34.6 10.1 2.17 .83 .98 1.00 32.8 9.6 2.51 .85 1.00 1.00(17�C)

1300 615 38.5 11.3 1.63 .82 .97 1.00 37.0 10.8 1.88 .83 .99 1.00 35.4 10.4 2.17 .85 1.00 1.00 33.8 9.9 2.49 .88 1.00 1.00

67�F1100 520 39.5 11.6 1.62 .62 .75 .88 38.0 11.1 1.88 .62 .76 .90 36.2 10.6 2.16 .63 .78 .92 34.2 10.0 2.49 .65 .80 .95

67�F(19�C)

1200 565 40.5 11.9 1.62 .63 .77 .91 38.5 11.3 1.88 .64 .78 .93 36.8 10.8 2.16 .65 .80 .95 34.8 10.2 2.49 .66 .82 .97(19�C)

1300 615 41.0 12.0 1.62 .64 .79 .93 39.5 11.6 1.87 .65 .81 .95 37.4 11.0 2.16 .66 .83 .98 35.4 10.4 2.48 .68 .85 1.00

71�F1100 520 42.5 12.5 1.62 .47 .60 .72 40.5 11.9 1.87 .47 .61 .74 39.0 11.4 2.15 .48 .62 .75 36.8 10.8 2.47 .49 .63 .77

71�F(22�C)

1200 565 43.5 12.7 1.62 .48 .61 .74 41.5 12.2 1.87 .48 .62 .76 39.5 11.6 2.14 .49 .63 .78 37.4 11.0 2.47 .49 .65 .80(22�C)

1300 615 44.0 12.9 1.62 .48 .62 .76 42.0 12.3 1.87 .49 .64 .78 40.0 11.7 2.14 .49 .65 .80 38.0 11.1 2.46 .50 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−048 with [CH23−68]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 49.5 14.5 2.87 .76 .90 1.00 47.0 13.8 3.22 .78 .92 1.00 45.0 13.2 3.61 .79 .94 1.00 42.5 12.5 4.05 .82 .96 1.00

63�F(17�C)

1600 755 51.0 14.9 2.89 .79 .94 1.00 48.5 14.2 3.24 .81 .96 1.00 46.5 13.6 3.63 .83 .98 1.00 44.0 12.9 4.06 .85 1.00 1.00(17�C)

1800 850 52.0 15.2 2.90 .82 .97 1.00 50.0 14.7 3.25 .84 .99 1.00 47.5 13.9 3.64 .86 1.00 1.00 45.5 13.3 4.09 .89 1.00 1.00

67�F1400 660 52.5 15.4 2.91 .61 .74 .86 50.5 14.8 3.26 .62 .75 .88 48.0 14.1 3.65 .63 .77 .90 45.0 13.2 4.08 .64 .79 .93

67�F(19�C)

1600 755 54.0 15.8 2.92 .63 .77 .90 52.0 15.2 3.27 .64 .78 .93 49.0 14.4 3.66 .65 .80 .95 46.5 13.6 4.09 .66 .83 .97(19�C)

1800 850 55.5 16.3 2.94 .65 .80 .94 53.0 15.5 3.29 .66 .82 .96 50.5 14.8 3.67 .67 .84 .99 47.5 13.9 4.11 .69 .86 1.00

71�F1400 660 56.0 16.4 2.94 .47 .59 .71 53.5 15.7 3.29 .47 .60 .73 51.0 14.9 3.69 .48 .61 .74 48.0 14.1 4.12 .48 .63 .76

71�F(22�C)

1600 755 57.5 16.9 2.96 .48 .61 .74 55.0 16.1 3.31 .48 .62 .76 52.5 15.4 3.70 .49 .64 .78 49.5 14.5 4.14 .50 .65 .80(22�C)

1800 850 59.0 17.3 2.98 .48 .63 .77 56.5 16.6 3.33 .49 .64 .79 53.5 15.7 3.72 .50 .66 .81 50.5 14.8 4.15 .51 .67 .84

FIRST STAGE COOLING CAPACITY − XC21−048 with [CH33−44/48B−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 36.6 10.7 1.63 .77 .91 1.00 35.0 10.3 1.89 .79 .93 1.00 33.4 9.8 2.18 .80 .95 1.00 31.6 9.3 2.52 .82 .98 1.00

63�F(17�C)

1200 565 37.2 10.9 1.63 .79 .93 1.00 35.8 10.5 1.89 .80 .95 1.00 34.0 10.0 2.18 .82 .98 1.00 32.2 9.4 2.51 .84 1.00 1.00(17�C)

1300 615 38.0 11.1 1.63 .80 .96 1.00 36.4 10.7 1.89 .82 .98 1.00 34.6 10.1 2.17 .84 1.00 1.00 33.0 9.7 2.50 .87 1.00 1.00

67�F1100 520 39.0 11.4 1.63 .61 .74 .87 37.4 11.0 1.88 .63 .76 .89 35.6 10.4 2.17 .63 .77 .91 33.8 9.9 2.49 .64 .79 .94

67�F(19�C)

1200 565 39.5 11.6 1.63 .63 .76 .90 38.0 11.1 1.88 .64 .78 .92 36.2 10.6 2.16 .65 .79 .94 34.4 10.1 2.48 .65 .81 .96(19�C)

1300 615 40.5 11.9 1.62 .64 .78 .92 38.5 11.3 1.88 .65 .80 .94 36.8 10.8 2.16 .65 .81 .96 34.8 10.2 2.49 .67 .83 .99

71�F1100 520 41.5 12.2 1.62 .47 .59 .72 39.5 11.6 1.87 .48 .61 .73 38.0 11.1 2.15 .48 .62 .75 36.0 10.6 2.48 .49 .63 .76

71�F(22�C)

1200 565 42.0 12.3 1.62 .48 .61 .74 40.5 11.9 1.87 .48 .62 .75 38.5 11.3 2.15 .49 .63 .77 36.6 10.7 2.47 .49 .64 .79(22�C)

1300 615 43.0 12.6 1.62 .48 .62 .75 41.0 12.0 1.87 .49 .63 .76 39.5 11.6 2.15 .49 .64 .79 37.2 10.9 2.47 .50 .66 .81

SECOND STAGE COOLING CAPACITY − XC21−048 with [CH33−44/48B−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 48.5 14.2 2.86 .75 .88 1.00 46.5 13.6 3.21 .77 .90 1.00 44.0 12.9 3.60 .79 .93 1.00 41.5 12.2 4.03 .80 .95 1.00

63�F(17�C)

1600 755 50.0 14.7 2.88 .78 .92 1.00 47.5 13.9 3.23 .80 .94 1.00 45.5 13.3 3.62 .81 .97 1.00 43.0 12.6 4.05 .84 .99 1.00(17�C)

1800 850 51.0 14.9 2.89 .81 .96 1.00 49.0 14.4 3.24 .82 .98 1.00 46.5 13.6 3.63 .84 1.00 1.00 44.0 12.9 4.06 .87 1.00 1.00

67�F1400 660 51.5 15.1 2.89 .60 .73 .85 49.0 14.4 3.24 .61 .74 .87 47.0 13.8 3.63 .62 .76 .89 44.0 12.9 4.07 .64 .78 .92

67�F(19�C)

1600 755 53.0 15.5 2.91 .62 .76 .88 50.5 14.8 3.26 .63 .77 .91 48.0 14.1 3.65 .64 .79 .93 45.5 13.3 4.09 .66 .81 .96(19�C)

1800 850 54.0 15.8 2.92 .64 .78 .92 51.5 15.1 3.27 .65 .80 .94 49.0 14.4 3.66 .66 .82 .97 46.5 13.6 4.09 .67 .84 .99

71�F1400 660 54.5 16.0 2.92 .47 .59 .71 52.0 15.2 3.27 .47 .60 .72 49.5 14.5 3.67 .48 .61 .73 47.0 13.8 4.10 .48 .62 .75

71�F(22�C)

1600 755 56.0 16.4 2.94 .48 .60 .73 53.5 15.7 3.29 .48 .61 .75 51.0 14.9 3.69 .49 .63 .76 48.5 14.2 4.12 .49 .64 .79(22�C)

1800 850 57.5 16.9 2.96 .49 .62 .76 55.0 16.1 3.31 .49 .63 .77 52.0 15.2 3.70 .50 .65 .80 49.0 14.4 4.13 .50 .66 .81

Page 92: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 4 TON

HORIZONTAL INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 92

FIRST STAGE COOLING CAPACITY − XC21−048 with [CH33−50/60C−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 37.0 10.8 1.63 .77 .91 1.00 35.4 10.4 1.89 .79 .93 1.00 33.8 9.9 2.18 .81 .96 1.00 32.0 9.4 2.51 .83 .98 1.00

63�F(17�C)

1200 565 37.8 11.1 1.63 .79 .94 1.00 36.2 10.6 1.89 .81 .96 1.00 34.4 10.1 2.17 .83 .98 1.00 32.6 9.6 2.50 .85 1.00 1.00(17�C)

1300 615 38.5 11.3 1.63 .81 .97 1.00 36.8 10.8 1.88 .83 .99 1.00 35.0 10.3 2.17 .85 1.00 1.00 33.6 9.8 2.50 .87 1.00 1.00

67�F1100 520 39.5 11.6 1.63 .62 .75 .88 37.8 11.1 1.88 .63 .76 .90 36.0 10.6 2.16 .64 .78 .92 34.2 10.0 2.49 .65 .80 .95

67�F(19�C)

1200 565 40.5 11.9 1.63 .63 .77 .90 38.5 11.3 1.88 .64 .78 .92 36.8 10.8 2.16 .65 .80 .95 34.8 10.2 2.48 .66 .82 .97(19�C)

1300 615 41.0 12.0 1.62 .64 .79 .93 39.0 11.4 1.87 .65 .80 .95 37.4 11.0 2.16 .66 .82 .97 35.4 10.4 2.48 .68 .85 1.00

71�F1100 520 42.0 12.3 1.62 .47 .60 .72 40.0 11.7 1.87 .48 .61 .74 38.5 11.3 2.15 .48 .62 .75 36.4 10.7 2.48 .49 .63 .77

71�F(22�C)

1200 565 43.0 12.6 1.62 .48 .61 .74 41.0 12.0 1.87 .48 .62 .75 39.0 11.4 2.15 .49 .63 .77 37.2 10.9 2.47 .49 .64 .79(22�C)

1300 615 43.5 12.7 1.62 .49 .63 .76 41.5 12.2 1.87 .49 .63 .78 40.0 11.7 2.14 .49 .65 .79 37.8 11.1 2.47 .50 .66 .81

SECOND STAGE COOLING CAPACITY − XC21−048 with [CH33−50/60C−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 49.0 14.4 2.87 .76 .89 1.00 47.0 13.8 3.22 .77 .91 1.00 44.5 13.0 3.61 .79 .93 1.00 42.0 12.3 4.04 .81 .96 1.00

63�F(17�C)

1600 755 50.5 14.8 2.88 .79 .93 1.00 48.5 14.2 3.24 .80 .95 1.00 46.0 13.5 3.62 .82 .98 1.00 43.5 12.7 4.05 .84 1.00 1.00(17�C)

1800 850 52.0 15.2 2.90 .81 .97 1.00 49.5 14.5 3.25 .83 .99 1.00 47.0 13.8 3.63 .85 1.00 1.00 44.5 13.0 4.07 .88 1.00 1.00

67�F1400 660 52.0 15.2 2.90 .61 .73 .85 50.0 14.7 3.25 .62 .75 .87 47.5 13.9 3.64 .63 .76 .90 45.0 13.2 4.07 .64 .78 .93

67�F(19�C)

1600 755 54.0 15.8 2.92 .62 .76 .90 51.5 15.1 3.27 .63 .78 .92 49.0 14.4 3.66 .65 .80 .94 46.0 13.5 4.09 .66 .82 .97(19�C)

1800 850 55.0 16.1 2.93 .64 .79 .93 52.5 15.4 3.28 .65 .81 .96 50.0 14.7 3.67 .66 .83 .98 47.0 13.8 4.10 .68 .85 1.00

71�F1400 660 55.5 16.3 2.94 .47 .59 .71 53.0 15.5 3.29 .47 .60 .72 50.5 14.8 3.68 .48 .61 .74 47.5 13.9 4.11 .48 .62 .76

71�F(22�C)

1600 755 57.0 16.7 2.95 .48 .61 .74 54.5 16.0 3.30 .48 .62 .75 52.0 15.2 3.70 .49 .63 .77 49.0 14.4 4.13 .49 .65 .79(22�C)

1800 850 58.0 17.0 2.97 .49 .63 .76 55.5 16.3 3.32 .49 .64 .78 53.0 15.5 3.71 .50 .65 .80 50.0 14.7 4.14 .50 .67 .83

FIRST STAGE COOLING CAPACITY − XC21−048 with [CH33−60D−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 36.6 10.7 1.63 .77 .91 1.00 35.2 10.3 1.89 .79 .93 1.00 33.6 9.8 2.18 .80 .95 1.00 31.8 9.3 2.52 .82 .98 1.00

63�F(17�C)

1200 565 37.4 11.0 1.63 .79 .94 1.00 35.8 10.5 1.89 .81 .96 1.00 34.2 10.0 2.18 .82 .98 1.00 32.4 9.5 2.50 .85 1.00 1.00(17�C)

1300 615 38.0 11.1 1.63 .81 .96 1.00 36.6 10.7 1.89 .83 .98 1.00 34.8 10.2 2.17 .84 1.00 1.00 33.2 9.7 2.50 .87 1.00 1.00

67�F1100 520 39.0 11.4 1.63 .62 .74 .87 37.4 11.0 1.88 .62 .76 .89 35.8 10.5 2.17 .63 .78 .91 33.8 9.9 2.49 .65 .79 .94

67�F(19�C)

1200 565 40.0 11.7 1.62 .63 .77 .90 38.0 11.1 1.88 .64 .78 .92 36.4 10.7 2.16 .65 .80 .94 34.4 10.1 2.48 .66 .82 .97(19�C)

1300 615 40.5 11.9 1.62 .64 .78 .92 39.0 11.4 1.88 .65 .80 .94 37.0 10.8 2.16 .66 .82 .97 35.0 10.3 2.48 .67 .83 .99

71�F1100 520 41.5 12.2 1.62 .47 .60 .72 40.0 11.7 1.87 .48 .61 .73 38.0 11.1 2.15 .48 .62 .75 36.2 10.6 2.47 .49 .63 .77

71�F(22�C)

1200 565 42.5 12.5 1.62 .48 .61 .74 40.5 11.9 1.87 .48 .62 .75 39.0 11.4 2.15 .49 .63 .77 36.8 10.8 2.47 .50 .64 .79(22�C)

1300 615 43.0 12.6 1.62 .49 .62 .76 41.5 12.2 1.87 .49 .63 .77 39.5 11.6 2.15 .49 .64 .79 37.4 11.0 2.47 .50 .66 .81

SECOND STAGE COOLING CAPACITY − XC21−048 with [CH33−60D−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 48.5 14.2 2.86 .75 .89 1.00 46.5 13.6 3.22 .77 .91 1.00 44.5 13.0 3.60 .79 .93 1.00 42.0 12.3 4.04 .81 .96 1.00

63�F(17�C)

1600 755 50.0 14.7 2.88 .78 .92 1.00 48.0 14.1 3.23 .80 .95 1.00 45.5 13.3 3.62 .82 .97 1.00 43.0 12.6 4.05 .84 .99 1.00(17�C)

1800 850 51.5 15.1 2.89 .81 .96 1.00 49.0 14.4 3.25 .83 .98 1.00 46.5 13.6 3.63 .85 1.00 1.00 44.5 13.0 4.07 .87 1.00 1.00

67�F1400 660 52.0 15.2 2.90 .61 .73 .85 49.5 14.5 3.25 .61 .74 .87 47.0 13.8 3.64 .62 .76 .89 44.5 13.0 4.07 .64 .78 .92

67�F(19�C)

1600 755 53.5 15.7 2.91 .62 .76 .89 51.0 14.9 3.27 .64 .77 .91 48.5 14.2 3.65 .64 .79 .94 45.5 13.3 4.09 .66 .82 .96(19�C)

1800 850 54.5 16.0 2.93 .64 .79 .93 52.0 15.2 3.28 .65 .80 .95 49.5 14.5 3.66 .66 .82 .97 46.5 13.6 4.10 .68 .85 1.00

71�F1400 660 55.0 16.1 2.93 .47 .59 .71 52.5 15.4 3.28 .47 .60 .72 50.0 14.7 3.67 .48 .61 .73 47.5 13.9 4.11 .48 .62 .76

71�F(22�C)

1600 755 56.5 16.6 2.95 .48 .61 .73 54.0 15.8 3.30 .48 .62 .75 51.5 15.1 3.69 .49 .63 .77 48.5 14.2 4.12 .49 .64 .79(22�C)

1800 850 58.0 17.0 2.96 .49 .63 .76 55.0 16.1 3.31 .49 .64 .78 52.5 15.4 3.70 .50 .65 .80 49.5 14.5 4.14 .50 .66 .82

Page 93: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 4 TON

HORIZONTAL INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 93

FIRST STAGE COOLING CAPACITY − XC21−048 with [CH33−62D−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 36.8 10.8 1.63 .77 .91 1.00 35.2 10.3 1.89 .79 .93 1.00 33.6 9.8 2.18 .80 .95 1.00 31.8 9.3 2.51 .82 .98 1.00

63�F(17�C)

1200 565 37.6 11.0 1.63 .79 .93 1.00 36.0 10.6 1.89 .81 .95 1.00 34.4 10.1 2.17 .82 .98 1.00 32.4 9.5 2.50 .84 1.00 1.00(17�C)

1300 615 38.5 11.3 1.63 .81 .96 1.00 36.6 10.7 1.89 .82 .98 1.00 35.0 10.3 2.17 .84 1.00 1.00 33.4 9.8 2.50 .87 1.00 1.00

67�F1100 520 39.0 11.4 1.63 .62 .75 .87 37.6 11.0 1.88 .62 .76 .89 35.8 10.5 2.16 .64 .78 .91 34.0 10.0 2.49 .65 .79 .94

67�F(19�C)

1200 565 40.0 11.7 1.63 .63 .76 .89 38.5 11.3 1.88 .64 .78 .92 36.6 10.7 2.16 .65 .80 .94 34.6 10.1 2.48 .66 .82 .97(19�C)

1300 615 40.5 11.9 1.62 .64 .78 .92 39.0 11.4 1.87 .65 .80 .94 37.2 10.9 2.16 .66 .82 .97 35.2 10.3 2.48 .67 .84 .99

71�F1100 520 41.5 12.2 1.62 .47 .60 .72 39.5 11.6 1.87 .48 .61 .73 38.0 11.1 2.16 .48 .62 .75 36.0 10.6 2.48 .49 .63 .77

71�F(22�C)

1200 565 42.5 12.5 1.62 .48 .61 .74 40.5 11.9 1.87 .48 .62 .75 39.0 11.4 2.15 .49 .63 .77 36.8 10.8 2.47 .49 .65 .79(22�C)

1300 615 43.0 12.6 1.62 .48 .62 .75 41.5 12.2 1.87 .49 .63 .77 39.5 11.6 2.14 .49 .65 .79 37.6 11.0 2.47 .50 .66 .81

SECOND STAGE COOLING CAPACITY − XC21−048 with [CH33−62D−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 49.0 14.4 2.86 .76 .88 1.00 47.0 13.8 3.22 .77 .90 1.00 44.5 13.0 3.61 .79 .93 1.00 42.0 12.3 4.04 .81 .96 1.00

63�F(17�C)

1600 755 50.5 14.8 2.88 .78 .92 1.00 48.5 14.2 3.23 .80 .94 1.00 46.0 13.5 3.62 .82 .97 1.00 43.5 12.7 4.05 .84 .99 1.00(17�C)

1800 850 52.0 15.2 2.89 .81 .96 1.00 49.5 14.5 3.25 .82 .98 1.00 47.0 13.8 3.64 .85 1.00 1.00 44.5 13.0 4.07 .87 1.00 1.00

67�F1400 660 52.0 15.2 2.90 .61 .73 .85 50.0 14.7 3.25 .62 .74 .87 47.5 13.9 3.64 .63 .76 .89 45.0 13.2 4.07 .64 .78 .92

67�F(19�C)

1600 755 53.5 15.7 2.92 .62 .76 .89 51.0 14.9 3.27 .63 .77 .91 49.0 14.4 3.66 .65 .79 .93 46.0 13.5 4.10 .66 .81 .96(19�C)

1800 850 55.0 16.1 2.93 .64 .78 .92 52.5 15.4 3.28 .65 .80 .95 50.0 14.7 3.67 .66 .82 .97 47.0 13.8 4.11 .68 .85 1.00

71�F1400 660 55.0 16.1 2.93 .47 .59 .71 52.5 15.4 3.28 .47 .60 .72 50.0 14.7 3.68 .48 .61 .74 47.5 13.9 4.11 .49 .62 .76

71�F(22�C)

1600 755 56.5 16.6 2.95 .48 .61 .73 54.0 15.8 3.30 .48 .62 .75 51.5 15.1 3.69 .49 .63 .77 48.5 14.2 4.13 .49 .64 .79(22�C)

1800 850 58.0 17.0 2.96 .49 .63 .76 55.5 16.3 3.32 .49 .64 .78 52.5 15.4 3.71 .50 .65 .80 50.0 14.7 4.15 .50 .67 .82

Page 94: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 4 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 94

FIRST STAGE COOLING CAPACITY − − XC21−048 with [CH23−51 + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1015 480 34.6 10.1 1.64 .75 .88 .99 33.2 9.7 1.90 .76 .90 1.00 31.8 9.3 2.20 .78 .92 1.00 30.0 8.8 2.53 .79 .95 1.00

63�F(17�C)

1140 540 35.8 10.5 1.64 .77 .92 1.00 34.2 10.0 1.90 .79 .94 1.00 32.6 9.6 2.19 .80 .96 1.00 31.0 9.1 2.52 .82 .98 1.00(17�C)

1285 605 36.6 10.7 1.64 .80 .95 1.00 35.2 10.3 1.89 .81 .97 1.00 33.6 9.8 2.18 .83 .99 1.00 32.0 9.4 2.52 .86 1.00 1.00

67�F1015 480 37.0 10.8 1.64 .59 .72 .85 35.6 10.4 1.89 .60 .74 .86 34.0 10.0 2.18 .61 .75 .88 32.2 9.4 2.51 .62 .77 .91

67�F(19�C)

1140 540 38.0 11.1 1.63 .61 .75 .88 36.6 10.7 1.89 .62 .76 .90 34.8 10.2 2.17 .63 .78 .92 33.0 9.7 2.50 .64 .80 .95(19�C)

1285 605 39.0 11.4 1.63 .63 .77 .92 37.6 11.0 1.88 .64 .79 .93 35.8 10.5 2.17 .65 .81 .96 33.8 9.9 2.50 .66 .83 .98

71�F1015 480 39.5 11.6 1.62 .46 .58 .70 37.8 11.1 1.88 .46 .59 .71 36.2 10.6 2.17 .46 .60 .72 34.4 10.1 2.49 .47 .61 .74

71�F(22�C)

1140 540 40.5 11.9 1.63 .46 .60 .72 39.0 11.4 1.88 .46 .61 .73 37.2 10.9 2.16 .47 .61 .75 35.2 10.3 2.49 .47 .63 .77(22�C)

1285 605 41.5 12.2 1.62 .47 .61 .75 40.0 11.7 1.87 .48 .62 .76 38.0 11.1 2.15 .48 .63 .78 36.0 10.6 2.48 .49 .65 .80

SECOND STAGE COOLING CAPACITY − − XC21−048 with [CH23−51 + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1460 690 47.5 13.9 2.85 .76 .90 1.00 45.5 13.3 3.20 .78 .92 1.00 43.0 12.6 3.59 .79 .94 1.00 40.5 11.9 4.02 .81 .97 1.00

63�F(17�C)

1635 770 48.5 14.2 2.87 .79 .93 1.00 46.5 13.6 3.22 .80 .95 1.00 44.0 12.9 3.60 .82 .98 1.00 42.0 12.3 4.04 .85 .99 1.00(17�C)

1855 875 50.0 14.7 2.88 .82 .97 1.00 47.5 13.9 3.23 .84 .99 1.00 45.5 13.3 3.62 .86 1.00 1.00 43.5 12.7 4.05 .88 1.00 1.00

67�F1460 690 50.5 14.8 2.88 .61 .74 .87 48.5 14.2 3.23 .62 .75 .89 46.0 13.5 3.62 .63 .77 .91 43.5 12.7 4.06 .64 .79 .93

67�F(19�C)

1635 770 52.0 15.2 2.89 .62 .76 .90 49.5 14.5 3.25 .63 .78 .92 47.0 13.8 3.64 .65 .80 .94 44.5 13.0 4.07 .66 .82 .97(19�C)

1855 875 53.0 15.5 2.91 .64 .80 .94 50.5 14.8 3.26 .65 .81 .96 48.0 14.1 3.65 .67 .83 .98 45.5 13.3 4.08 .68 .86 1.00

71�F1460 690 53.5 15.7 2.91 .46 .59 .71 51.0 14.9 3.26 .47 .60 .73 48.5 14.2 3.66 .47 .61 .74 46.0 13.5 4.09 .48 .62 .76

71�F(22�C)

1635 770 54.5 16.0 2.93 .47 .61 .74 52.5 15.4 3.28 .47 .62 .75 50.0 14.7 3.67 .48 .63 .77 47.0 13.8 4.10 .49 .65 .80(22�C)

1855 875 56.0 16.4 2.94 .48 .63 .77 53.5 15.7 3.29 .49 .64 .79 51.0 14.9 3.68 .50 .66 .81 48.0 14.1 4.12 .51 .67 .84

FIRST STAGE COOLING CAPACITY − XC21−048 with [CH33−48C−2F + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1015 480 35.6 10.4 1.64 .75 .88 1.00 34.2 10.0 1.90 .76 .90 1.00 32.6 9.6 2.19 .78 .92 1.00 30.8 9.0 2.53 .79 .94 1.00

63�F(17�C)

1140 540 36.6 10.7 1.63 .77 .91 1.00 35.2 10.3 1.89 .78 .93 1.00 33.4 9.8 2.18 .80 .95 1.00 31.8 9.3 2.51 .82 .98 1.00(17�C)

1285 605 37.6 11.0 1.63 .79 .95 1.00 36.2 10.6 1.89 .81 .97 1.00 34.4 10.1 2.17 .83 .99 1.00 32.6 9.6 2.51 .84 1.00 1.00

67�F1015 480 38.0 11.1 1.63 .59 .72 .84 36.4 10.7 1.89 .60 .73 .86 34.8 10.2 2.17 .61 .75 .88 33.0 9.7 2.50 .62 .76 .90

67�F(19�C)

1140 540 39.0 11.4 1.63 .61 .74 .87 37.4 11.0 1.88 .62 .76 .89 35.8 10.5 2.17 .63 .77 .91 33.8 9.9 2.50 .64 .79 .94(19�C)

1285 605 40.0 11.7 1.62 .63 .77 .91 38.5 11.3 1.88 .64 .79 .93 36.6 10.7 2.16 .64 .81 .95 34.6 10.1 2.49 .66 .82 .98

71�F1015 480 40.5 11.9 1.62 .46 .58 .69 38.5 11.3 1.88 .46 .58 .70 37.0 10.8 2.16 .46 .60 .72 35.2 10.3 2.48 .47 .61 .74

71�F(22�C)

1140 540 41.5 12.2 1.62 .47 .59 .72 40.0 11.7 1.87 .47 .60 .73 38.0 11.1 2.16 .47 .61 .75 36.2 10.6 2.47 .48 .62 .76(22�C)

1285 605 42.5 12.5 1.62 .47 .61 .74 41.0 12.0 1.87 .48 .62 .75 39.0 11.4 2.15 .48 .63 .77 37.0 10.8 2.47 .49 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−048 with [CH33−48C−2F + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1460 690 48.5 14.2 2.87 .76 .89 1.00 46.5 13.6 3.22 .77 .91 1.00 44.5 13.0 3.61 .79 .93 1.00 42.0 12.3 4.04 .81 .96 1.00

63�F(17�C)

1635 770 50.0 14.7 2.88 .78 .93 1.00 48.0 14.1 3.23 .80 .95 1.00 45.5 13.3 3.62 .82 .97 1.00 43.0 12.6 4.05 .84 .99 1.00(17�C)

1855 875 51.5 15.1 2.89 .81 .96 1.00 49.0 14.4 3.24 .83 .98 1.00 46.5 13.6 3.63 .85 1.00 1.00 44.0 12.9 4.07 .87 1.00 1.00

67�F1460 690 52.0 15.2 2.90 .60 .73 .86 49.5 14.5 3.25 .61 .74 .88 47.0 13.8 3.64 .62 .76 .90 44.5 13.0 4.07 .64 .78 .93

67�F(19�C)

1635 770 53.0 15.5 2.91 .62 .76 .89 51.0 14.9 3.26 .63 .77 .91 48.0 14.1 3.65 .64 .79 .94 45.5 13.3 4.09 .65 .81 .96(19�C)

1855 875 54.5 16.0 2.92 .64 .79 .93 52.0 15.2 3.28 .65 .80 .95 49.5 14.5 3.66 .66 .82 .98 46.5 13.6 4.10 .68 .85 1.00

71�F1460 690 55.0 16.1 2.93 .47 .59 .71 52.5 15.4 3.28 .47 .60 .72 50.0 14.7 3.67 .48 .61 .74 47.5 13.9 4.11 .48 .62 .75

71�F(22�C)

1635 770 56.0 16.4 2.94 .47 .60 .73 54.0 15.8 3.30 .48 .61 .74 51.0 14.9 3.69 .48 .63 .77 48.5 14.2 4.12 .49 .64 .79(22�C)

1855 875 57.5 16.9 2.96 .49 .63 .76 55.0 16.1 3.31 .49 .64 .78 52.5 15.4 3.70 .50 .65 .79 49.5 14.5 4.13 .50 .66 .82

Page 95: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 4 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 95

FIRST STAGE COOLING CAPACITY − XC21−048 with [CH33−48C−2F + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F960 455 35.2 10.3 1.67 .74 .86 .98 33.8 9.9 1.93 .74 .88 1.00 32.2 9.4 2.23 .76 .90 1.00 30.6 9.0 2.58 .78 .92 1.00

63�F(17�C)

1090 515 36.4 10.7 1.66 .76 .90 1.00 34.8 10.2 1.92 .77 .91 1.00 33.2 9.7 2.22 .79 .94 1.00 31.6 9.3 2.56 .81 .96 1.00(17�C)

1215 575 37.4 11.0 1.66 .78 .93 1.00 35.8 10.5 1.91 .80 .95 1.00 34.2 10.0 2.21 .81 .97 1.00 32.4 9.5 2.56 .83 .99 1.00

67�F960 455 37.6 11.0 1.65 .59 .71 .83 36.0 10.6 1.91 .59 .72 .84 34.4 10.1 2.21 .61 .74 .86 32.6 9.6 2.56 .62 .75 .88

67�F(19�C)

1090 515 38.5 11.3 1.65 .60 .73 .86 37.2 10.9 1.91 .61 .75 .88 35.4 10.4 2.20 .62 .76 .90 33.6 9.8 2.54 .63 .78 .92(19�C)

1215 575 39.5 11.6 1.65 .62 .76 .89 38.0 11.1 1.90 .63 .77 .91 36.2 10.6 2.20 .64 .79 .93 34.4 10.1 2.53 .65 .81 .96

71�F960 455 40.0 11.7 1.64 .46 .57 .68 38.5 11.3 1.90 .46 .58 .69 36.6 10.7 2.19 .46 .58 .70 34.8 10.2 2.53 .47 .60 .72

71�F(22�C)

1090 515 41.0 12.0 1.64 .46 .59 .70 39.5 11.6 1.90 .46 .60 .72 37.8 11.1 2.18 .47 .61 .74 35.8 10.5 2.52 .48 .62 .75(22�C)

1215 575 42.0 12.3 1.64 .47 .60 .73 40.5 11.9 1.89 .47 .61 .74 38.5 11.3 2.18 .48 .62 .76 36.6 10.7 2.51 .49 .63 .78

SECOND STAGE COOLING CAPACITY − XC21−048 with [CH33−48C−2F + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1380 650 48.5 14.2 2.88 .75 .87 .99 46.5 13.6 3.24 .76 .89 1.00 44.0 12.9 3.63 .77 .91 1.00 41.5 12.2 4.07 .79 .94 1.00

63�F(17�C)

1590 750 50.0 14.7 2.90 .77 .91 1.00 48.0 14.1 3.25 .79 .93 1.00 45.5 13.3 3.65 .81 .96 1.00 43.0 12.6 4.09 .83 .98 1.00(17�C)

1750 825 51.0 14.9 2.90 .80 .94 1.00 49.0 14.4 3.26 .81 .96 1.00 46.5 13.6 3.65 .83 .99 1.00 44.0 12.9 4.09 .85 1.00 1.00

67�F1380 650 51.5 15.1 2.91 .60 .72 .84 49.0 14.4 3.26 .61 .74 .86 47.0 13.8 3.66 .61 .75 .88 44.0 12.9 4.10 .63 .77 .90

67�F(19�C)

1590 750 53.0 15.5 2.92 .62 .75 .88 50.5 14.8 3.28 .63 .76 .90 48.0 14.1 3.67 .64 .78 .92 45.5 13.3 4.12 .65 .80 .95(19�C)

1750 825 54.0 15.8 2.94 .63 .77 .91 51.5 15.1 3.29 .64 .79 .93 49.0 14.4 3.69 .65 .81 .95 46.5 13.6 4.13 .67 .83 .98

71�F1380 650 54.5 16.0 2.94 .46 .58 .70 52.0 15.2 3.30 .47 .59 .71 49.5 14.5 3.69 .47 .60 .72 47.0 13.8 4.14 .48 .61 .74

71�F(22�C)

1590 750 56.0 16.4 2.96 .47 .60 .72 53.5 15.7 3.31 .48 .61 .74 51.0 14.9 3.71 .48 .62 .76 48.5 14.2 4.15 .49 .63 .78(22�C)

1750 825 57.0 16.7 2.97 .48 .61 .75 54.5 16.0 3.32 .49 .63 .76 52.0 15.2 3.72 .49 .64 .78 49.0 14.4 4.16 .50 .65 .80

FIRST STAGE COOLING CAPACITY − XC21−048 with [CH33−50/60C−2F + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1015 480 35.8 10.5 1.64 .75 .88 1.00 34.2 10.0 1.90 .76 .90 1.00 32.6 9.6 2.19 .78 .92 1.00 31.0 9.1 2.52 .80 .95 1.00

63�F(17�C)

1140 540 36.8 10.8 1.63 .77 .91 1.00 35.2 10.3 1.89 .79 .93 1.00 33.6 9.8 2.18 .80 .96 1.00 31.8 9.3 2.51 .82 .98 1.00(17�C)

1285 605 37.8 11.1 1.63 .80 .95 1.00 36.2 10.6 1.89 .81 .97 1.00 34.6 10.1 2.17 .83 .99 1.00 32.8 9.6 2.50 .85 1.00 1.00

67�F1015 480 38.0 11.1 1.63 .59 .72 .84 36.6 10.7 1.89 .60 .73 .86 35.0 10.3 2.17 .61 .75 .88 33.2 9.7 2.50 .62 .77 .90

67�F(19�C)

1140 540 39.5 11.6 1.63 .61 .75 .87 37.6 11.0 1.88 .62 .76 .89 35.8 10.5 2.17 .63 .78 .92 34.0 10.0 2.50 .64 .80 .94(19�C)

1285 605 40.5 11.9 1.62 .63 .77 .91 38.5 11.3 1.88 .64 .79 .93 36.8 10.8 2.16 .65 .80 .96 34.8 10.2 2.49 .66 .83 .98

71�F1015 480 40.5 11.9 1.62 .46 .58 .69 39.0 11.4 1.88 .46 .59 .70 37.2 10.9 2.16 .46 .60 .72 35.4 10.4 2.48 .47 .61 .74

71�F(22�C)

1140 540 42.0 12.3 1.62 .47 .59 .72 40.0 11.7 1.87 .47 .60 .73 38.5 11.3 2.15 .47 .61 .75 36.4 10.7 2.48 .48 .63 .77(22�C)

1285 605 43.0 12.6 1.62 .47 .61 .74 41.0 12.0 1.87 .48 .62 .76 39.0 11.4 2.15 .48 .63 .78 37.2 10.9 2.47 .49 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−048 with [CH33−50/60C−2F + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1460 690 49.0 14.4 2.87 .76 .89 1.00 47.0 13.8 3.22 .77 .92 1.00 44.5 13.0 3.61 .79 .94 1.00 42.0 12.3 4.04 .81 .97 1.00

63�F(17�C)

1635 770 50.5 14.8 2.88 .79 .93 1.00 48.0 14.1 3.23 .80 .95 1.00 45.5 13.3 3.62 .82 .97 1.00 43.0 12.6 4.05 .84 1.00 1.00(17�C)

1855 875 51.5 15.1 2.90 .82 .97 1.00 49.5 14.5 3.25 .83 .99 1.00 47.0 13.8 3.63 .85 1.00 1.00 44.5 13.0 4.07 .88 1.00 1.00

67�F1460 690 52.0 15.2 2.90 .60 .73 .86 50.0 14.7 3.25 .61 .75 .88 47.5 13.9 3.64 .63 .77 .90 45.0 13.2 4.07 .64 .79 .93

67�F(19�C)

1635 770 53.5 15.7 2.91 .62 .76 .89 51.0 14.9 3.27 .63 .77 .91 48.5 14.2 3.65 .64 .79 .94 45.5 13.3 4.09 .66 .82 .97(19�C)

1855 875 54.5 16.0 2.93 .64 .79 .93 52.5 15.4 3.28 .65 .81 .96 49.5 14.5 3.67 .67 .83 .98 46.5 13.6 4.10 .68 .85 1.00

71�F1460 690 55.0 16.1 2.93 .47 .59 .71 53.0 15.5 3.28 .47 .60 .72 50.5 14.8 3.68 .48 .61 .74 47.5 13.9 4.11 .48 .62 .76

71�F(22�C)

1635 770 56.5 16.6 2.95 .48 .60 .73 54.0 15.8 3.30 .48 .62 .75 51.5 15.1 3.69 .48 .63 .77 48.5 14.2 4.12 .49 .64 .79(22�C)

1855 875 58.0 17.0 2.97 .49 .63 .76 55.5 16.3 3.31 .49 .64 .79 52.5 15.4 3.71 .50 .65 .81 49.5 14.5 4.14 .50 .67 .82

Page 96: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 4 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 96

FIRST STAGE COOLING CAPACITY − XC21−048 with [CH33−50/60C−2F + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F960 455 35.2 10.3 1.63 .74 .87 .99 33.8 9.9 1.89 .75 .88 1.00 32.2 9.4 2.17 .77 .90 1.00 30.6 9.0 2.51 .78 .93 1.00

63�F(17�C)

1090 515 36.4 10.7 1.63 .76 .90 1.00 34.8 10.2 1.88 .78 .92 1.00 33.2 9.7 2.17 .79 .94 1.00 31.4 9.2 2.50 .81 .97 1.00(17�C)

1215 575 37.4 11.0 1.62 .79 .93 1.00 35.8 10.5 1.88 .80 .95 1.00 34.2 10.0 2.17 .82 .98 1.00 32.2 9.4 2.49 .84 1.00 1.00

67�F960 455 37.6 11.0 1.62 .59 .71 .83 36.0 10.6 1.88 .60 .72 .85 34.4 10.1 2.16 .61 .74 .86 32.6 9.6 2.49 .62 .76 .89

67�F(19�C)

1090 515 39.0 11.4 1.62 .61 .74 .86 37.2 10.9 1.87 .61 .75 .88 35.4 10.4 2.15 .62 .77 .90 33.6 9.8 2.48 .64 .78 .93(19�C)

1215 575 39.5 11.6 1.62 .62 .76 .89 38.0 11.1 1.87 .63 .78 .92 36.2 10.6 2.15 .64 .79 .94 34.4 10.1 2.47 .65 .81 .97

71�F960 455 40.0 11.7 1.62 .46 .57 .69 38.5 11.3 1.87 .46 .58 .70 36.6 10.7 2.15 .46 .59 .71 34.8 10.2 2.47 .47 .60 .73

71�F(22�C)

1090 515 41.0 12.0 1.62 .46 .59 .71 39.5 11.6 1.87 .47 .60 .72 37.8 11.1 2.14 .47 .61 .74 35.8 10.5 2.46 .48 .62 .76(22�C)

1215 575 42.5 12.5 1.62 .47 .61 .74 40.5 11.9 1.86 .48 .62 .75 38.5 11.3 2.14 .48 .63 .77 36.8 10.8 2.46 .49 .64 .78

SECOND STAGE COOLING CAPACITY − XC21−048 with [CH33−50/60C−2F + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1380 650 48.5 14.2 2.85 .75 .88 1.00 46.0 13.5 3.20 .76 .90 1.00 44.0 12.9 3.59 .78 .92 1.00 41.5 12.2 4.02 .80 .95 1.00

63�F(17�C)

1590 750 50.0 14.7 2.87 .78 .92 1.00 47.5 13.9 3.21 .80 .94 1.00 45.5 13.3 3.60 .81 .97 1.00 43.0 12.6 4.04 .84 .99 1.00(17�C)

1750 825 51.0 14.9 2.88 .80 .95 1.00 48.5 14.2 3.23 .82 .97 1.00 46.5 13.6 3.61 .84 1.00 1.00 43.5 12.7 4.05 .87 1.00 1.00

67�F1380 650 51.5 15.1 2.89 .60 .72 .85 49.0 14.4 3.23 .61 .74 .87 47.0 13.8 3.62 .62 .76 .89 44.0 12.9 4.05 .63 .77 .91

67�F(19�C)

1590 750 53.0 15.5 2.91 .62 .76 .89 50.5 14.8 3.25 .63 .77 .91 48.0 14.1 3.63 .64 .79 .93 45.5 13.3 4.07 .65 .81 .96(19�C)

1750 825 54.0 15.8 2.92 .64 .78 .92 51.5 15.1 3.26 .65 .80 .94 49.0 14.4 3.65 .66 .82 .97 46.0 13.5 4.08 .67 .84 .99

71�F1380 650 54.5 16.0 2.92 .47 .58 .70 52.0 15.2 3.27 .47 .59 .71 49.5 14.5 3.65 .47 .60 .73 47.0 13.8 4.09 .48 .62 .75

71�F(22�C)

1590 750 56.0 16.4 2.94 .47 .60 .73 53.5 15.7 3.29 .48 .62 .75 51.0 14.9 3.67 .48 .63 .77 48.0 14.1 4.11 .49 .64 .79(22�C)

1750 825 57.0 16.7 2.96 .48 .62 .75 55.0 16.1 3.30 .49 .63 .77 52.0 15.2 3.69 .49 .64 .79 49.0 14.4 4.12 .50 .66 .81

FIRST STAGE COOLING CAPACITY − XC21−048 with [CH33−60D−2F + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1075 505 36.2 10.6 1.64 .76 .89 1.00 34.8 10.2 1.89 .77 .91 1.00 33.2 9.7 2.18 .79 .94 1.00 31.4 9.2 2.52 .81 .96 1.00

63�F(17�C)

1180 555 37.0 10.8 1.63 .78 .92 1.00 35.6 10.4 1.89 .79 .94 1.00 33.8 9.9 2.18 .81 .97 1.00 32.0 9.4 2.51 .83 .99 1.00(17�C)

1325 625 38.0 11.1 1.63 .80 .96 1.00 36.6 10.7 1.89 .82 .98 1.00 34.8 10.2 2.17 .84 1.00 1.00 33.0 9.7 2.50 .86 1.00 1.00

67�F1075 505 38.5 11.3 1.63 .60 .73 .85 37.0 10.8 1.88 .61 .74 .87 35.4 10.4 2.17 .62 .76 .90 33.6 9.8 2.50 .63 .78 .92

67�F(19�C)

1180 555 39.5 11.6 1.63 .61 .75 .88 37.8 11.1 1.88 .62 .77 .90 36.0 10.6 2.16 .63 .78 .93 34.2 10.0 2.49 .64 .80 .95(19�C)

1325 625 40.5 11.9 1.62 .63 .78 .92 39.0 11.4 1.88 .64 .79 .94 37.0 10.8 2.16 .65 .81 .97 35.0 10.3 2.49 .66 .83 .99

71�F1075 505 41.0 12.0 1.62 .46 .58 .70 39.5 11.6 1.87 .46 .59 .72 37.6 11.0 2.15 .47 .60 .73 35.8 10.5 2.48 .47 .61 .75

71�F(22�C)

1180 555 42.0 12.3 1.62 .47 .60 .72 40.5 11.9 1.87 .47 .61 .74 38.5 11.3 2.15 .48 .62 .76 36.6 10.7 2.48 .48 .63 .78(22�C)

1325 625 43.0 12.6 1.62 .47 .62 .75 41.5 12.2 1.87 .48 .63 .77 39.5 11.6 2.15 .48 .64 .78 37.4 11.0 2.47 .49 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−048 with [CH33−60D−2F + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1540 725 49.5 14.5 2.87 .77 .91 1.00 47.5 13.9 3.22 .79 .93 1.00 45.0 13.2 3.61 .80 .95 1.00 42.5 12.5 4.05 .82 .98 1.00

63�F(17�C)

1695 800 50.5 14.8 2.88 .79 .94 1.00 48.5 14.2 3.24 .81 .96 1.00 46.0 13.5 3.62 .83 .98 1.00 43.5 12.7 4.05 .84 1.00 1.00(17�C)

1905 900 52.0 15.2 2.90 .82 .97 1.00 49.5 14.5 3.25 .84 .99 1.00 47.0 13.8 3.64 .86 1.00 1.00 45.0 13.2 4.07 .88 1.00 1.00

67�F1540 725 52.5 15.4 2.90 .61 .74 .88 50.5 14.8 3.26 .62 .76 .89 48.0 14.1 3.65 .63 .78 .92 45.0 13.2 4.08 .64 .80 .95

67�F(19�C)

1695 800 53.5 15.7 2.92 .62 .76 .90 51.5 15.1 3.27 .63 .78 .92 49.0 14.4 3.66 .65 .80 .95 46.0 13.5 4.09 .66 .82 .98(19�C)

1905 900 55.0 16.1 2.93 .64 .80 .94 52.5 15.4 3.28 .65 .81 .96 50.0 14.7 3.67 .66 .83 .99 47.0 13.8 4.10 .68 .86 1.00

71�F1540 725 56.0 16.4 2.94 .47 .59 .72 53.5 15.7 3.29 .47 .60 .73 51.0 14.9 3.68 .48 .62 .75 48.0 14.1 4.12 .48 .63 .77

71�F(22�C)

1695 800 57.0 16.7 2.95 .48 .61 .74 54.5 16.0 3.30 .48 .62 .76 52.0 15.2 3.70 .48 .63 .78 49.0 14.4 4.13 .49 .65 .80(22�C)

1905 900 58.0 17.0 2.97 .48 .63 .77 55.5 16.3 3.32 .49 .64 .79 53.0 15.5 3.71 .50 .65 .81 50.0 14.7 4.14 .50 .67 .83

Page 97: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 4 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 97

FIRST STAGE COOLING CAPACITY − XC21−048 with [CH33−60D−2F + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F985 465 35.4 10.4 1.65 .74 .87 .99 34.0 10.0 1.91 .75 .89 1.00 32.4 9.5 2.21 .77 .91 1.00 30.8 9.0 2.55 .79 .93 1.00

63�F(17�C)

1115 525 36.6 10.7 1.64 .77 .90 1.00 35.2 10.3 1.91 .78 .92 1.00 33.6 9.8 2.20 .79 .95 1.00 31.8 9.3 2.54 .81 .97 1.00(17�C)

1235 585 37.6 11.0 1.64 .79 .93 1.00 36.0 10.6 1.90 .80 .95 1.00 34.4 10.1 2.19 .82 .98 1.00 32.6 9.6 2.53 .84 1.00 1.00

67�F985 465 37.8 11.1 1.64 .59 .71 .83 36.2 10.6 1.90 .59 .72 .85 34.6 10.1 2.19 .61 .74 .87 32.8 9.6 2.52 .62 .76 .89

67�F(19�C)

1115 525 39.0 11.4 1.64 .61 .74 .87 37.4 11.0 1.89 .62 .75 .88 35.6 10.4 2.18 .63 .77 .91 33.8 9.9 2.51 .64 .79 .93(19�C)

1235 585 40.0 11.7 1.64 .62 .76 .90 38.0 11.1 1.89 .63 .77 .92 36.6 10.7 2.18 .64 .79 .94 34.6 10.1 2.50 .65 .81 .96

71�F985 465 40.0 11.7 1.63 .46 .57 .69 38.5 11.3 1.88 .46 .58 .70 36.8 10.8 2.17 .46 .59 .71 35.2 10.3 2.50 .47 .60 .73

71�F(22�C)

1115 525 41.5 12.2 1.63 .46 .59 .71 40.0 11.7 1.88 .47 .60 .73 38.0 11.1 2.17 .47 .61 .74 36.2 10.6 2.49 .48 .62 .76(22�C)

1235 585 42.5 12.5 1.63 .47 .61 .73 41.0 12.0 1.88 .47 .61 .75 39.0 11.4 2.16 .48 .62 .76 36.8 10.8 2.49 .48 .63 .78

SECOND STAGE COOLING CAPACITY − XC21−048 with [CH33−60D−2F + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 48.5 14.2 2.87 .75 .88 1.00 46.5 13.6 3.23 .76 .90 1.00 44.5 13.0 3.61 .78 .92 1.00 42.0 12.3 4.05 .80 .95 1.00

63�F(17�C)

1600 755 50.0 14.7 2.89 .78 .92 1.00 48.0 14.1 3.24 .79 .94 1.00 45.5 13.3 3.63 .81 .96 1.00 43.0 12.6 4.07 .83 .99 1.00(17�C)

1780 840 51.5 15.1 2.90 .80 .95 1.00 49.0 14.4 3.25 .82 .97 1.00 47.0 13.8 3.64 .84 .99 1.00 44.0 12.9 4.08 .86 1.00 1.00

67�F1400 660 51.5 15.1 2.90 .60 .73 .84 49.5 14.5 3.25 .60 .73 .86 47.0 13.8 3.64 .62 .75 .88 44.5 13.0 4.08 .63 .77 .91

67�F(19�C)

1600 755 53.0 15.5 2.92 .61 .75 .88 51.0 14.9 3.27 .63 .77 .90 48.5 14.2 3.66 .64 .78 .93 45.5 13.3 4.10 .65 .81 .95(19�C)

1780 840 54.5 16.0 2.93 .64 .78 .92 52.0 15.2 3.28 .64 .79 .94 49.5 14.5 3.68 .65 .81 .96 46.5 13.6 4.11 .67 .83 .99

71�F1400 660 54.5 16.0 2.93 .46 .58 .70 52.5 15.4 3.29 .47 .59 .71 50.0 14.7 3.67 .47 .60 .73 47.0 13.8 4.12 .48 .61 .74

71�F(22�C)

1600 755 56.5 16.6 2.95 .47 .60 .73 54.0 15.8 3.31 .48 .61 .74 51.5 15.1 3.70 .48 .62 .76 48.5 14.2 4.14 .49 .64 .78(22�C)

1780 840 57.5 16.9 2.96 .48 .62 .75 55.0 16.1 3.32 .49 .63 .77 52.5 15.4 3.71 .49 .64 .79 49.5 14.5 4.15 .50 .65 .81

FIRST STAGE COOLING CAPACITY − XC21−048 with [CH33−62D−2F + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1075 505 36.4 10.7 1.64 .76 .89 1.00 34.8 10.2 1.89 .77 .91 1.00 33.2 9.7 2.18 .79 .93 1.00 31.4 9.2 2.52 .81 .96 1.00

63�F(17�C)

1180 555 37.2 10.9 1.63 .78 .92 1.00 35.6 10.4 1.89 .79 .94 1.00 34.0 10.0 2.18 .81 .96 1.00 32.2 9.4 2.51 .83 .99 1.00(17�C)

1325 625 38.0 11.1 1.63 .80 .95 1.00 36.6 10.7 1.89 .82 .98 1.00 34.8 10.2 2.17 .84 1.00 1.00 33.2 9.7 2.50 .86 1.00 1.00

67�F1075 505 38.5 11.3 1.63 .60 .73 .85 37.0 10.8 1.88 .61 .74 .87 35.4 10.4 2.17 .62 .76 .89 33.6 9.8 2.49 .63 .78 .92

67�F(19�C)

1180 555 39.5 11.6 1.62 .61 .75 .88 38.0 11.1 1.88 .62 .76 .90 36.2 10.6 2.16 .64 .78 .92 34.4 10.1 2.49 .65 .80 .95(19�C)

1325 625 40.5 11.9 1.62 .63 .78 .92 39.0 11.4 1.87 .64 .79 .94 37.2 10.9 2.16 .65 .81 .96 35.2 10.3 2.49 .66 .83 .99

71�F1075 505 41.0 12.0 1.62 .46 .59 .70 39.5 11.6 1.88 .46 .59 .72 37.6 11.0 2.16 .47 .60 .73 35.6 10.4 2.48 .47 .61 .75

71�F(22�C)

1180 555 42.0 12.3 1.62 .47 .60 .72 40.0 11.7 1.87 .47 .61 .74 38.5 11.3 2.15 .47 .62 .75 36.4 10.7 2.47 .48 .63 .77(22�C)

1325 625 43.0 12.6 1.62 .47 .62 .75 41.5 12.2 1.87 .48 .63 .77 39.5 11.6 2.14 .48 .64 .78 37.4 11.0 2.47 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−048 with [CH33−62D−2F + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1540 725 50.0 14.7 2.88 .77 .90 1.00 48.0 14.1 3.23 .78 .93 1.00 45.5 13.3 3.61 .80 .95 1.00 43.0 12.6 4.05 .82 .98 1.00

63�F(17�C)

1695 800 51.0 14.9 2.89 .79 .93 1.00 49.0 14.4 3.24 .80 .96 1.00 46.5 13.6 3.63 .82 .98 1.00 43.5 12.7 4.06 .85 1.00 1.00(17�C)

1905 900 52.5 15.4 2.90 .82 .97 1.00 50.0 14.7 3.26 .83 .99 1.00 47.5 13.9 3.64 .86 1.00 1.00 45.0 13.2 4.08 .88 1.00 1.00

67�F1540 725 53.0 15.5 2.91 .61 .74 .87 50.5 14.8 3.26 .62 .76 .89 48.0 14.1 3.65 .63 .78 .92 45.5 13.3 4.08 .64 .80 .94

67�F(19�C)

1695 800 54.0 15.8 2.92 .62 .76 .90 51.5 15.1 3.27 .64 .78 .92 49.0 14.4 3.66 .65 .80 .95 46.5 13.6 4.10 .66 .82 .98(19�C)

1905 900 55.5 16.3 2.94 .64 .79 .94 53.0 15.5 3.29 .66 .81 .96 50.5 14.8 3.68 .67 .83 .99 47.5 13.9 4.11 .68 .86 1.00

71�F1540 725 56.0 16.4 2.94 .47 .60 .72 53.5 15.7 3.30 .47 .61 .73 51.0 14.9 3.69 .48 .62 .75 48.0 14.1 4.12 .48 .63 .77

71�F(22�C)

1695 800 57.0 16.7 2.96 .48 .61 .74 54.5 16.0 3.31 .48 .62 .76 52.0 15.2 3.70 .48 .63 .77 49.0 14.4 4.14 .49 .65 .80(22�C)

1905 900 58.5 17.1 2.97 .48 .63 .77 56.0 16.4 3.32 .49 .64 .79 53.0 15.5 3.71 .50 .66 .81 50.0 14.7 4.15 .50 .67 .83

Page 98: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 4 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 98

FIRST STAGE COOLING CAPACITY − XC21−048 with [CH33−62D−2F + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F985 465 35.4 10.4 1.63 .74 .87 .99 34.0 10.0 1.89 .75 .89 1.00 32.4 9.5 2.17 .77 .91 1.00 30.8 9.0 2.50 .79 .93 1.00

63�F(17�C)

1115 525 36.6 10.7 1.63 .77 .90 1.00 35.0 10.3 1.88 .78 .92 1.00 33.4 9.8 2.17 .80 .95 1.00 31.8 9.3 2.50 .82 .97 1.00(17�C)

1235 585 37.6 11.0 1.62 .79 .93 1.00 36.0 10.6 1.88 .80 .96 1.00 34.2 10.0 2.16 .82 .98 1.00 32.4 9.5 2.49 .84 1.00 1.00

67�F985 465 37.6 11.0 1.62 .59 .72 .83 36.2 10.6 1.88 .60 .73 .85 34.4 10.1 2.16 .61 .74 .87 32.8 9.6 2.48 .62 .76 .89

67�F(19�C)

1115 525 39.0 11.4 1.62 .61 .74 .87 37.4 11.0 1.87 .62 .75 .89 35.6 10.4 2.15 .63 .77 .91 33.8 9.9 2.48 .64 .79 .94(19�C)

1235 585 40.0 11.7 1.62 .62 .76 .90 38.5 11.3 1.87 .63 .78 .92 36.6 10.7 2.15 .64 .79 .94 34.6 10.1 2.47 .66 .81 .97

71�F985 465 40.0 11.7 1.62 .46 .58 .69 38.5 11.3 1.87 .46 .58 .70 36.6 10.7 2.15 .46 .59 .71 34.8 10.2 2.47 .47 .60 .73

71�F(22�C)

1115 525 41.0 12.0 1.62 .46 .59 .71 39.5 11.6 1.86 .47 .60 .73 37.8 11.1 2.14 .47 .61 .74 36.0 10.6 2.46 .48 .62 .76(22�C)

1235 585 42.0 12.3 1.62 .47 .61 .74 40.5 11.9 1.86 .47 .62 .75 38.5 11.3 2.14 .48 .63 .77 36.8 10.8 2.46 .48 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−048 with [CH33−62D−2F + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 49.0 14.4 2.86 .75 .88 1.00 46.5 13.6 3.21 .76 .90 1.00 44.5 13.0 3.59 .78 .92 1.00 42.0 12.3 4.02 .80 .95 1.00

63�F(17�C)

1600 755 50.5 14.8 2.88 .78 .92 1.00 48.0 14.1 3.22 .79 .94 1.00 45.5 13.3 3.61 .81 .97 1.00 43.0 12.6 4.04 .83 .99 1.00(17�C)

1780 840 51.5 15.1 2.89 .80 .95 1.00 49.0 14.4 3.23 .82 .97 1.00 47.0 13.8 3.62 .84 1.00 1.00 44.0 12.9 4.05 .86 1.00 1.00

67�F1400 660 51.5 15.1 2.89 .60 .73 .85 49.5 14.5 3.24 .61 .74 .86 47.0 13.8 3.62 .62 .76 .89 44.5 13.0 4.06 .63 .77 .91

67�F(19�C)

1600 755 53.5 15.7 2.91 .62 .75 .89 51.0 14.9 3.25 .63 .77 .91 48.5 14.2 3.64 .64 .79 .93 46.0 13.5 4.07 .65 .81 .96(19�C)

1780 840 54.5 16.0 2.92 .64 .78 .92 52.0 15.2 3.27 .65 .80 .94 49.5 14.5 3.66 .66 .82 .97 47.0 13.8 4.09 .67 .84 .99

71�F1400 660 54.5 16.0 2.92 .47 .59 .70 52.0 15.2 3.27 .47 .59 .72 50.0 14.7 3.66 .47 .60 .73 47.0 13.8 4.09 .48 .62 .75

71�F(22�C)

1600 755 56.0 16.4 2.94 .47 .60 .73 54.0 15.8 3.29 .48 .61 .74 51.5 15.1 3.68 .48 .63 .76 48.5 14.2 4.11 .49 .64 .78(22�C)

1780 840 57.5 16.9 2.96 .48 .62 .76 55.0 16.1 3.31 .49 .63 .77 52.5 15.4 3.69 .49 .65 .79 49.5 14.5 4.12 .50 .66 .81

Page 99: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 4 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 99

FIRST STAGE COOLING CAPACITY − XC21−048 with [CBX32M−036] {CBX32M−042}[CB30M−41] [CB30M−46]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 35.4 10.4 1.63 .77 .91 1.00 34.0 10.0 1.89 .78 .94 1.00 32.4 9.5 2.18 .80 .96 1.00 30.6 9.0 2.51 .82 .98 1.00

63�F(17�C)

1200 565 36.2 10.6 1.63 .79 .94 1.00 34.6 10.1 1.88 .80 .96 1.00 33.0 9.7 2.17 .82 .98 1.00 31.4 9.2 2.50 .85 1.00 1.00(17�C)

1250 590 36.4 10.7 1.63 .80 .95 1.00 35.0 10.3 1.88 .81 .97 1.00 33.4 9.8 2.17 .83 .99 1.00 31.6 9.3 2.50 .86 1.00 1.00

67�F1100 520 37.8 11.1 1.62 .60 .74 .88 36.2 10.6 1.88 .61 .76 .90 34.6 10.1 2.16 .62 .77 .92 32.6 9.6 2.49 .64 .79 .95

67�F(19�C)

1200 565 38.5 11.3 1.62 .62 .76 .91 37.0 10.8 1.87 .62 .78 .93 35.2 10.3 2.16 .64 .80 .95 33.4 9.8 2.48 .65 .82 .97(19�C)

1250 590 39.0 11.4 1.62 .62 .77 .92 37.2 10.9 1.87 .63 .79 .94 35.4 10.4 2.16 .64 .81 .96 33.6 9.8 2.48 .66 .83 .98

71�F1100 520 40.0 11.7 1.62 .46 .59 .72 38.5 11.3 1.87 .46 .60 .73 36.8 10.8 2.15 .47 .61 .75 34.8 10.2 2.47 .47 .62 .77

71�F(22�C)

1200 565 41.0 12.0 1.62 .46 .60 .73 39.0 11.4 1.87 .47 .61 .75 37.4 11.0 2.14 .47 .62 .77 35.4 10.4 2.47 .47 .64 .79(22�C)

1250 590 41.0 12.0 1.62 .46 .61 .75 39.5 11.6 1.86 .47 .62 .76 37.6 11.0 2.14 .47 .63 .78 35.8 10.5 2.47 .48 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−048 with [CBX32M−036] {CBX32M−042}[CB30M−41] [CB30M−46]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 46.5 13.6 2.83 .76 .90 1.00 44.5 13.0 3.18 .77 .92 1.00 42.0 12.3 3.56 .79 .94 1.00 39.5 11.6 3.99 .81 .97 1.00

63�F(17�C)

1500 710 47.0 13.8 2.84 .77 .92 1.00 45.0 13.2 3.19 .79 .94 1.00 42.5 12.5 3.57 .80 .96 1.00 40.0 11.7 3.99 .83 .98 1.00(17�C)

1550 730 47.5 13.9 2.84 .78 .93 1.00 45.0 13.2 3.19 .79 .95 1.00 43.0 12.6 3.57 .81 .97 1.00 40.5 11.9 4.00 .84 .99 1.00

67�F1400 660 49.5 14.5 2.86 .60 .73 .86 47.0 13.8 3.21 .61 .75 .88 44.5 13.0 3.59 .62 .76 .91 42.0 12.3 4.03 .63 .78 .94

67�F(19�C)

1500 710 50.0 14.7 2.87 .61 .75 .88 48.0 14.1 3.22 .62 .76 .90 45.0 13.2 3.60 .63 .78 .93 42.5 12.5 4.03 .64 .80 .96(19�C)

1550 730 50.5 14.8 2.88 .61 .75 .89 48.0 14.1 3.22 .62 .77 .92 45.5 13.3 3.61 .63 .79 .94 43.0 12.6 4.03 .65 .81 .97

71�F1400 660 52.0 15.2 2.89 .46 .58 .71 49.5 14.5 3.24 .46 .59 .72 47.5 13.9 3.63 .46 .60 .74 44.5 13.0 4.05 .47 .62 .76

71�F(22�C)

1500 710 52.5 15.4 2.90 .46 .59 .72 50.5 14.8 3.25 .46 .60 .74 48.0 14.1 3.63 .47 .61 .76 45.5 13.3 4.07 .47 .63 .78(22�C)

1550 730 53.0 15.5 2.91 .46 .60 .73 51.0 14.9 3.25 .47 .61 .75 48.0 14.1 3.63 .47 .62 .76 45.5 13.3 4.07 .47 .63 .79

FIRST STAGE COOLING CAPACITY − XC21−048 with [CBX32M−048][CB30M−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 36.6 10.7 1.63 .77 .92 1.00 35.0 10.3 1.88 .78 .94 1.00 33.4 9.8 2.17 .80 .96 1.00 31.6 9.3 2.50 .82 .98 1.00

63�F(17�C)

1200 565 37.2 10.9 1.62 .79 .94 1.00 35.8 10.5 1.88 .80 .96 1.00 34.0 10.0 2.16 .82 .98 1.00 32.4 9.5 2.49 .84 1.00 1.00(17�C)

1300 615 38.0 11.1 1.62 .81 .97 1.00 36.4 10.7 1.88 .82 .98 1.00 34.8 10.2 2.16 .84 1.00 1.00 33.2 9.7 2.49 .87 1.00 1.00

67�F1100 520 39.0 11.4 1.62 .60 .74 .88 37.4 11.0 1.87 .61 .76 .90 35.6 10.4 2.15 .62 .77 .92 33.8 9.9 2.48 .63 .79 .95

67�F(19�C)

1200 565 39.5 11.6 1.62 .61 .76 .91 38.0 11.1 1.87 .62 .78 .93 36.4 10.7 2.15 .63 .80 .95 34.4 10.1 2.47 .65 .82 .97(19�C)

1300 615 40.5 11.9 1.62 .63 .78 .93 39.0 11.4 1.87 .64 .80 .95 36.8 10.8 2.15 .65 .82 .97 34.8 10.2 2.47 .66 .84 1.00

71�F1100 520 41.5 12.2 1.62 .45 .59 .71 39.5 11.6 1.86 .46 .60 .73 38.0 11.1 2.14 .46 .61 .75 36.0 10.6 2.46 .47 .62 .76

71�F(22�C)

1200 565 42.5 12.5 1.62 .46 .60 .74 40.5 11.9 1.86 .46 .61 .75 38.5 11.3 2.14 .47 .62 .77 36.6 10.7 2.46 .47 .63 .79(22�C)

1300 615 43.0 12.6 1.61 .46 .61 .76 41.0 12.0 1.86 .47 .62 .77 39.5 11.6 2.13 .47 .63 .79 37.2 10.9 2.45 .48 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−048 with [CBX32M−048][CB30M−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 48.5 14.2 2.86 .75 .90 1.00 46.5 13.6 3.20 .77 .92 1.00 44.0 12.9 3.59 .79 .94 1.00 41.5 12.2 4.01 .81 .97 1.00

63�F(17�C)

1600 755 50.0 14.7 2.87 .78 .94 1.00 47.5 13.9 3.21 .80 .96 1.00 45.0 13.2 3.60 .82 .98 1.00 42.5 12.5 4.03 .84 1.00 1.00(17�C)

1800 850 51.0 14.9 2.88 .81 .97 1.00 49.0 14.4 3.23 .83 .99 1.00 46.5 13.6 3.61 .85 1.00 1.00 44.0 12.9 4.05 .88 1.00 1.00

67�F1400 660 51.5 15.1 2.89 .60 .73 .86 49.0 14.4 3.24 .60 .74 .88 46.5 13.6 3.62 .62 .76 .91 44.0 12.9 4.05 .63 .78 .93

67�F(19�C)

1600 755 53.0 15.5 2.91 .61 .76 .90 50.5 14.8 3.25 .62 .78 .93 48.0 14.1 3.64 .63 .80 .95 45.0 13.2 4.07 .65 .82 .98(19�C)

1800 850 54.0 15.8 2.92 .63 .79 .94 51.5 15.1 3.26 .64 .81 .96 49.0 14.4 3.65 .66 .83 .98 46.0 13.5 4.07 .67 .86 1.00

71�F1400 660 54.5 16.0 2.92 .45 .58 .70 52.0 15.2 3.27 .45 .59 .72 49.5 14.5 3.65 .46 .60 .74 47.0 13.8 4.09 .46 .61 .76

71�F(22�C)

1600 755 56.0 16.4 2.94 .46 .60 .74 53.5 15.7 3.28 .46 .61 .75 51.0 14.9 3.67 .47 .62 .77 48.0 14.1 4.10 .47 .64 .79(22�C)

1800 850 57.0 16.7 2.95 .47 .62 .77 54.5 16.0 3.30 .47 .63 .78 52.0 15.2 3.69 .48 .64 .80 49.0 14.4 4.12 .48 .66 .83

Page 100: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 4 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 100

FIRST STAGE COOLING CAPACITY − XC21−048 with [CBX32M−060][CB30M−65]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 36.8 10.8 1.64 .77 .91 1.00 35.2 10.3 1.89 .78 .93 1.00 33.6 9.8 2.18 .80 .95 1.00 31.8 9.3 2.51 .82 .98 1.00

63�F(17�C)

1200 565 37.6 11.0 1.63 .79 .94 1.00 36.0 10.6 1.89 .80 .96 1.00 34.4 10.1 2.17 .82 .98 1.00 32.6 9.6 2.51 .84 1.00 1.00(17�C)

1300 615 38.5 11.3 1.63 .80 .96 1.00 36.8 10.8 1.88 .82 .98 1.00 35.0 10.3 2.17 .84 1.00 1.00 33.4 9.8 2.50 .86 1.00 1.00

67�F1100 520 39.0 11.4 1.63 .60 .74 .87 37.4 11.0 1.88 .61 .75 .89 35.8 10.5 2.17 .62 .78 .91 34.0 10.0 2.49 .63 .79 .94

67�F(19�C)

1200 565 40.0 11.7 1.63 .61 .76 .90 38.0 11.1 1.88 .62 .77 .92 36.4 10.7 2.16 .63 .79 .94 34.6 10.1 2.48 .65 .81 .97(19�C)

1300 615 40.5 11.9 1.62 .63 .78 .92 39.0 11.4 1.88 .64 .79 .95 37.0 10.8 2.16 .65 .81 .97 35.2 10.3 2.48 .66 .84 .99

71�F1100 520 41.5 12.2 1.62 .45 .59 .71 40.0 11.7 1.87 .46 .60 .73 38.0 11.1 2.15 .46 .61 .74 36.2 10.6 2.48 .47 .62 .77

71�F(22�C)

1200 565 42.5 12.5 1.62 .46 .60 .73 40.5 11.9 1.87 .46 .61 .75 39.0 11.4 2.15 .47 .62 .77 36.8 10.8 2.47 .47 .63 .79(22�C)

1300 615 43.0 12.6 1.62 .47 .61 .75 41.5 12.2 1.87 .47 .62 .77 39.5 11.6 2.15 .48 .63 .79 37.4 11.0 2.47 .48 .65 .81

SECOND STAGE COOLING CAPACITY − XC21−048 with [CBX32M−060][CB30M−65]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 49.0 14.4 2.86 .75 .89 1.00 47.0 13.8 3.22 .77 .91 1.00 44.5 13.0 3.60 .78 .93 1.00 42.0 12.3 4.04 .80 .96 1.00

63�F(17�C)

1600 755 50.5 14.8 2.88 .78 .93 1.00 48.0 14.1 3.23 .80 .95 1.00 46.0 13.5 3.62 .81 .97 1.00 43.0 12.6 4.06 .84 .99 1.00(17�C)

1800 850 51.5 15.1 2.89 .81 .96 1.00 49.5 14.5 3.24 .83 .98 1.00 47.0 13.8 3.63 .85 1.00 1.00 44.5 13.0 4.07 .87 1.00 1.00

67�F1400 660 52.0 15.2 2.90 .60 .73 .85 49.5 14.5 3.25 .60 .74 .87 47.0 13.8 3.64 .61 .76 .90 44.5 13.0 4.07 .62 .78 .92

67�F(19�C)

1600 755 53.5 15.7 2.91 .61 .76 .89 51.0 14.9 3.26 .62 .77 .91 48.5 14.2 3.65 .63 .79 .94 45.5 13.3 4.08 .65 .81 .97(19�C)

1800 850 54.5 16.0 2.93 .63 .79 .93 52.0 15.2 3.28 .64 .80 .95 49.5 14.5 3.67 .65 .82 .98 46.5 13.6 4.10 .67 .85 1.00

71�F1400 660 54.5 16.0 2.93 .45 .58 .70 52.5 15.4 3.28 .46 .59 .71 50.0 14.7 3.67 .46 .60 .73 47.5 13.9 4.11 .46 .61 .75

71�F(22�C)

1600 755 56.5 16.6 2.95 .46 .60 .73 54.0 15.8 3.29 .46 .61 .75 51.5 15.1 3.69 .47 .62 .77 48.5 14.2 4.13 .47 .63 .79(22�C)

1800 850 57.5 16.9 2.96 .47 .62 .76 55.0 16.1 3.32 .47 .63 .78 52.5 15.4 3.71 .48 .64 .80 49.5 14.5 4.14 .48 .66 .82

FIRST STAGE COOLING CAPACITY − XC21−048 with [CBX32MV−036][CB31MV−41]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1000 470 34.8 10.2 1.63 .75 .89 1.00 33.2 9.7 1.89 .76 .90 1.00 31.6 9.3 2.18 .78 .93 1.00 30.0 8.8 2.52 .80 .95 1.00

63�F(17�C)

1080 510 35.4 10.4 1.63 .77 .91 1.00 33.8 9.9 1.88 .78 .93 1.00 32.2 9.4 2.18 .80 .95 1.00 30.6 9.0 2.51 .82 .97 1.00(17�C)

1085 510 35.4 10.4 1.63 .77 .91 1.00 33.8 9.9 1.89 .78 .93 1.00 32.2 9.4 2.18 .80 .95 1.00 30.6 9.0 2.51 .82 .98 1.00

67�F1000 470 37.0 10.8 1.63 .59 .72 .85 35.4 10.4 1.88 .60 .74 .87 33.8 9.9 2.16 .61 .75 .89 32.0 9.4 2.49 .62 .77 .91

67�F(19�C)

1080 510 37.6 11.0 1.62 .60 .74 .87 36.2 10.6 1.88 .61 .75 .89 34.4 10.1 2.16 .62 .77 .91 32.6 9.6 2.49 .63 .79 .94(19�C)

1085 510 37.6 11.0 1.62 .60 .74 .87 36.2 10.6 1.88 .61 .75 .89 34.4 10.1 2.16 .62 .77 .92 32.6 9.6 2.49 .63 .79 .94

71�F1000 470 39.0 11.4 1.62 .45 .58 .70 37.6 11.0 1.87 .45 .58 .71 36.0 10.6 2.15 .46 .59 .72 34.2 10.0 2.47 .46 .60 .74

71�F(22�C)

1080 510 40.0 11.7 1.62 .46 .59 .71 38.5 11.3 1.87 .46 .59 .72 36.6 10.7 2.15 .46 .61 .74 34.6 10.1 2.47 .47 .62 .76(22�C)

1085 510 40.0 11.7 1.62 .46 .59 .71 38.5 11.3 1.87 .46 .59 .73 36.6 10.7 2.15 .46 .61 .74 34.6 10.1 2.47 .47 .62 .76

SECOND STAGE COOLING CAPACITY − XC21−048 with [CBX32MV−036][CB31MV−41]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 46.5 13.6 2.83 .76 .90 1.00 44.5 13.0 3.18 .77 .92 1.00 42.0 12.3 3.56 .79 .94 1.00 39.5 11.6 3.99 .81 .97 1.00

63�F(17�C)

1545 730 47.5 13.9 2.84 .78 .93 1.00 45.0 13.2 3.19 .79 .95 1.00 43.0 12.6 3.58 .81 .97 1.00 40.5 11.9 4.00 .84 .99 1.00(17�C)

1550 730 47.5 13.9 2.84 .78 .93 1.00 45.0 13.2 3.19 .79 .95 1.00 43.0 12.6 3.57 .81 .97 1.00 40.5 11.9 4.00 .84 .99 1.00

67�F1400 660 49.5 14.5 2.86 .60 .73 .86 47.0 13.8 3.21 .61 .75 .88 44.5 13.0 3.59 .62 .76 .91 42.0 12.3 4.03 .63 .78 .94

67�F(19�C)

1545 730 50.5 14.8 2.88 .61 .75 .89 48.0 14.1 3.22 .62 .77 .91 45.5 13.3 3.61 .63 .79 .94 43.0 12.6 4.03 .65 .81 .97(19�C)

1550 730 50.5 14.8 2.88 .61 .75 .89 48.0 14.1 3.22 .62 .77 .92 45.5 13.3 3.61 .63 .79 .94 43.0 12.6 4.03 .65 .81 .97

71�F1400 660 52.0 15.2 2.89 .46 .58 .71 49.5 14.5 3.24 .46 .59 .72 47.5 13.9 3.63 .46 .60 .74 44.5 13.0 4.05 .47 .62 .76

71�F(22�C)

1545 730 53.0 15.5 2.91 .46 .60 .73 50.5 14.8 3.25 .46 .61 .75 48.0 14.1 3.63 .47 .62 .76 45.5 13.3 4.07 .47 .63 .79(22�C)

1550 730 53.0 15.5 2.91 .46 .60 .73 51.0 14.9 3.25 .47 .61 .75 48.0 14.1 3.63 .47 .62 .76 45.5 13.3 4.07 .47 .63 .79

Page 101: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 4 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 101

FIRST STAGE COOLING CAPACITY − XC21−048 with [CBX32MV−048][CB31MV−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1090 515 36.6 10.7 1.63 .76 .91 1.00 35.0 10.3 1.88 .78 .93 1.00 33.2 9.7 2.17 .80 .95 1.00 31.6 9.3 2.50 .82 .98 1.00

63�F(17�C)

1140 540 37.0 10.8 1.63 .78 .93 1.00 35.4 10.4 1.88 .79 .95 1.00 33.6 9.8 2.17 .81 .97 1.00 31.8 9.3 2.49 .83 .99 1.00(17�C)

1205 570 37.4 11.0 1.62 .79 .94 1.00 35.8 10.5 1.88 .80 .96 1.00 34.0 10.0 2.16 .82 .98 1.00 32.4 9.5 2.49 .84 1.00 1.00

67�F1090 515 39.0 11.4 1.62 .60 .74 .88 37.2 10.9 1.87 .61 .75 .89 35.6 10.4 2.15 .62 .77 .92 33.6 9.8 2.48 .63 .79 .94

67�F(19�C)

1140 540 39.5 11.6 1.62 .61 .75 .89 37.6 11.0 1.87 .62 .76 .91 35.8 10.5 2.15 .63 .78 .93 34.0 10.0 2.48 .64 .80 .96(19�C)

1205 570 40.0 11.7 1.62 .61 .76 .91 38.0 11.1 1.87 .62 .78 .93 36.4 10.7 2.15 .64 .80 .95 34.4 10.1 2.47 .65 .82 .98

71�F1090 515 41.5 12.2 1.62 .45 .59 .71 39.5 11.6 1.86 .46 .59 .73 37.8 11.1 2.14 .46 .60 .74 35.8 10.5 2.46 .47 .62 .76

71�F(22�C)

1140 540 42.0 12.3 1.62 .46 .59 .72 40.0 11.7 1.86 .46 .60 .74 38.0 11.1 2.14 .46 .61 .75 36.2 10.6 2.46 .47 .62 .77(22�C)

1205 570 42.5 12.5 1.62 .46 .60 .74 40.5 11.9 1.86 .46 .61 .75 38.5 11.3 2.14 .47 .62 .77 36.6 10.7 2.46 .47 .63 .79

SECOND STAGE COOLING CAPACITY − XC21−048 with [CBX32MV−048][CB31MV−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1555 735 49.5 14.5 2.87 .78 .93 1.00 47.5 13.9 3.21 .79 .95 1.00 45.0 13.2 3.60 .81 .97 1.00 42.5 12.5 4.03 .84 .99 1.00

63�F(17�C)

1625 765 50.0 14.7 2.87 .79 .94 1.00 47.5 13.9 3.21 .80 .96 1.00 45.5 13.3 3.60 .82 .98 1.00 43.0 12.6 4.03 .85 1.00 1.00(17�C)

1725 815 50.5 14.8 2.88 .80 .96 1.00 48.5 14.2 3.22 .82 .98 1.00 46.0 13.5 3.61 .84 1.00 1.00 43.5 12.7 4.04 .87 1.00 1.00

67�F1555 735 52.5 15.4 2.90 .61 .75 .89 50.0 14.7 3.25 .62 .77 .92 47.5 13.9 3.63 .63 .79 .94 45.0 13.2 4.06 .64 .81 .97

67�F(19�C)

1625 765 53.0 15.5 2.91 .62 .76 .91 50.5 14.8 3.25 .63 .78 .93 48.0 14.1 3.64 .64 .80 .96 45.5 13.3 4.06 .65 .82 .98(19�C)

1725 815 53.5 15.7 2.91 .63 .78 .93 51.0 14.9 3.26 .64 .80 .95 48.5 14.2 3.64 .65 .82 .97 46.0 13.5 4.07 .66 .84 .99

71�F1555 735 55.5 16.3 2.94 .46 .60 .73 53.0 15.5 3.28 .46 .61 .74 50.5 14.8 3.67 .47 .62 .76 48.0 14.1 4.10 .47 .63 .79

71�F(22�C)

1625 765 56.0 16.4 2.94 .46 .60 .74 53.5 15.7 3.29 .46 .61 .76 51.0 14.9 3.67 .47 .62 .78 48.0 14.1 4.11 .48 .64 .80(22�C)

1725 815 57.0 16.7 2.95 .46 .61 .75 54.5 16.0 3.30 .47 .62 .77 51.5 15.1 3.68 .47 .64 .79 48.5 14.2 4.11 .48 .65 .82

FIRST STAGE COOLING CAPACITY − XC21−048 with [CBX32MV−060][CB31MV−65]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1090 515 36.6 10.7 1.63 .76 .91 1.00 35.2 10.3 1.88 .78 .93 1.00 33.6 9.8 2.17 .80 .95 1.00 31.8 9.3 2.50 .81 .97 1.00

63�F(17�C)

1140 540 37.0 10.8 1.62 .77 .92 1.00 35.6 10.4 1.88 .79 .94 1.00 33.8 9.9 2.16 .81 .96 1.00 32.0 9.4 2.49 .83 .99 1.00(17�C)

1205 570 37.6 11.0 1.62 .79 .94 1.00 36.0 10.6 1.88 .80 .96 1.00 34.2 10.0 2.16 .82 .98 1.00 32.6 9.6 2.49 .84 1.00 1.00

67�F1090 515 39.0 11.4 1.62 .60 .74 .87 37.2 10.9 1.87 .61 .75 .89 35.6 10.4 2.16 .62 .77 .91 33.8 9.9 2.48 .63 .79 .94

67�F(19�C)

1140 540 39.5 11.6 1.62 .61 .75 .88 37.6 11.0 1.87 .62 .76 .90 36.0 10.6 2.15 .63 .78 .93 34.0 10.0 2.47 .64 .80 .95(19�C)

1205 570 40.0 11.7 1.62 .62 .76 .90 38.0 11.1 1.87 .62 .78 .92 36.4 10.7 2.15 .64 .79 .94 34.6 10.1 2.47 .65 .81 .97

71�F1090 515 41.5 12.2 1.62 .46 .59 .71 39.5 11.6 1.86 .46 .59 .73 37.8 11.1 2.14 .46 .60 .74 36.0 10.6 2.46 .47 .62 .76

71�F(22�C)

1140 540 42.0 12.3 1.62 .46 .59 .72 40.0 11.7 1.86 .46 .60 .74 38.0 11.1 2.14 .47 .61 .75 36.2 10.6 2.46 .47 .62 .77(22�C)

1205 570 42.5 12.5 1.62 .46 .60 .74 40.5 11.9 1.86 .47 .61 .75 38.5 11.3 2.14 .47 .62 .77 36.8 10.8 2.46 .48 .63 .79

SECOND STAGE COOLING CAPACITY − XC21−048 with [CBX32MV−060][CB31MV−65]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1555 735 50.0 14.7 2.87 .77 .92 1.00 48.0 14.1 3.22 .79 .94 1.00 45.5 13.3 3.60 .81 .96 1.00 43.0 12.6 4.03 .83 .99 1.00

63�F(17�C)

1625 765 50.5 14.8 2.88 .78 .93 1.00 48.0 14.1 3.22 .80 .96 1.00 46.0 13.5 3.61 .82 .98 1.00 43.5 12.7 4.04 .84 1.00 1.00(17�C)

1725 815 51.0 14.9 2.88 .79 .95 1.00 49.0 14.4 3.23 .81 .97 1.00 46.5 13.6 3.62 .84 .99 1.00 44.0 12.9 4.05 .86 1.00 1.00

67�F1555 735 53.0 15.5 2.90 .61 .75 .89 50.5 14.8 3.25 .62 .77 .91 48.0 14.1 3.64 .63 .78 .93 45.0 13.2 4.06 .64 .81 .96

67�F(19�C)

1625 765 53.5 15.7 2.91 .61 .76 .90 51.0 14.9 3.26 .62 .78 .92 48.5 14.2 3.64 .64 .80 .95 45.5 13.3 4.07 .65 .82 .97(19�C)

1725 815 54.0 15.8 2.92 .62 .77 .92 51.5 15.1 3.26 .63 .80 .94 49.0 14.4 3.65 .65 .81 .97 46.0 13.5 4.08 .66 .84 .99

71�F1555 735 56.0 16.4 2.94 .46 .60 .73 53.5 15.7 3.28 .46 .60 .74 51.0 14.9 3.67 .47 .62 .76 48.0 14.1 4.11 .47 .63 .78

71�F(22�C)

1625 765 56.5 16.6 2.94 .46 .60 .74 54.0 15.8 3.29 .47 .61 .75 51.5 15.1 3.68 .47 .62 .77 48.5 14.2 4.11 .48 .64 .79(22�C)

1725 815 57.0 16.7 2.95 .47 .61 .75 54.5 16.0 3.30 .47 .62 .77 52.0 15.2 3.69 .47 .63 .79 49.0 14.4 4.12 .48 .65 .81

Page 102: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 4 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 102

FIRST STAGE COOLING CAPACITY − XC21−048 with [CBX32MV−068]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1250 590 37.6 11.0 1.63 .78 .93 1.00 36.2 10.6 1.89 .80 .96 1.00 34.4 10.1 2.17 .82 .98 1.00 32.6 9.6 2.50 .84 1.00 1.00

63�F(17�C)

1250 590 37.6 11.0 1.63 .78 .93 1.00 36.2 10.6 1.89 .80 .96 1.00 34.4 10.1 2.17 .82 .98 1.00 32.6 9.6 2.50 .84 1.00 1.00(17�C)

1465 690 39.0 11.4 1.62 .82 .98 1.00 37.4 11.0 1.88 .83 1.00 1.00 35.8 10.5 2.17 .86 1.00 1.00 34.2 10.0 2.49 .88 1.00 1.00

67�F1250 590 40.0 11.7 1.63 .61 .76 .90 38.5 11.3 1.88 .62 .77 .92 36.6 10.7 2.16 .63 .79 .94 34.6 10.1 2.49 .65 .81 .97

67�F(19�C)

1250 590 40.0 11.7 1.63 .61 .76 .90 38.5 11.3 1.88 .62 .77 .92 36.6 10.7 2.16 .63 .79 .94 34.6 10.1 2.49 .65 .81 .97(19�C)

1465 690 41.5 12.2 1.62 .64 .79 .95 39.5 11.6 1.87 .65 .81 .97 37.8 11.1 2.16 .66 .83 .99 35.8 10.5 2.48 .67 .85 1.00

71�F1250 590 42.0 12.3 1.62 .46 .60 .73 40.5 11.9 1.87 .47 .61 .75 38.5 11.3 2.15 .47 .62 .76 36.6 10.7 2.47 .48 .62 .78

71�F(22�C)

1250 590 42.0 12.3 1.62 .46 .60 .73 40.5 11.9 1.87 .47 .61 .75 38.5 11.3 2.15 .47 .62 .76 36.6 10.7 2.47 .48 .62 .78(22�C)

1465 690 43.5 12.7 1.62 .47 .62 .77 41.5 12.2 1.87 .48 .63 .78 40.0 11.7 2.14 .48 .64 .80 37.8 11.1 2.46 .48 .66 .83

SECOND STAGE COOLING CAPACITY − XC21−048 with [CBX32MV−068]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1465 690 49.5 14.5 2.87 .75 .89 1.00 47.0 13.8 3.22 .76 .91 1.00 45.0 13.2 3.61 .78 .93 1.00 42.5 12.5 4.04 .80 .96 1.00

63�F(17�C)

1625 765 50.5 14.8 2.88 .77 .91 1.00 48.5 14.2 3.23 .79 .94 1.00 46.0 13.5 3.62 .80 .96 1.00 43.5 12.7 4.05 .82 .99 1.00(17�C)

1840 870 52.0 15.2 2.89 .80 .95 1.00 49.5 14.5 3.25 .81 .98 1.00 47.0 13.8 3.64 .83 1.00 1.00 44.5 13.0 4.07 .86 1.00 1.00

67�F1465 690 52.0 15.2 2.90 .59 .73 .85 49.5 14.5 3.25 .60 .74 .87 47.5 13.9 3.64 .61 .76 .89 45.0 13.2 4.08 .63 .78 .92

67�F(19�C)

1625 765 53.0 15.5 2.91 .60 .74 .88 51.0 14.9 3.26 .62 .76 .90 48.5 14.2 3.66 .63 .78 .93 46.0 13.5 4.09 .64 .80 .96(19�C)

1840 870 54.5 16.0 2.93 .62 .77 .92 52.0 15.2 3.28 .63 .79 .94 49.5 14.5 3.67 .64 .81 .97 47.0 13.8 4.10 .66 .83 .99

71�F1465 690 55.0 16.1 2.93 .46 .58 .70 53.0 15.5 3.28 .46 .59 .71 50.5 14.8 3.68 .46 .60 .73 47.5 13.9 4.11 .47 .61 .75

71�F(22�C)

1625 765 56.0 16.4 2.94 .46 .59 .72 54.0 15.8 3.30 .47 .60 .74 51.0 14.9 3.68 .47 .61 .75 48.5 14.2 4.12 .47 .63 .77(22�C)

1840 870 57.5 16.9 2.96 .47 .61 .75 55.0 16.1 3.31 .47 .62 .76 52.0 15.2 3.70 .48 .63 .78 49.0 14.4 4.13 .48 .64 .81

FIRST STAGE COOLING CAPACITY − XC21−048 with [CB30U−41/46]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 35.8 10.5 1.63 .78 .93 1.00 34.2 10.0 1.88 .80 .95 1.00 32.6 9.6 2.17 .81 .97 1.00 31.0 9.1 2.50 .84 .99 1.00

63�F(17�C)

1200 565 36.4 10.7 1.63 .80 .95 1.00 35.0 10.3 1.88 .82 .97 1.00 33.2 9.7 2.17 .84 .99 1.00 31.6 9.3 2.50 .86 1.00 1.00(17�C)

1250 590 36.8 10.8 1.62 .81 .97 1.00 35.2 10.3 1.88 .83 .98 1.00 33.6 9.8 2.17 .85 1.00 1.00 32.0 9.4 2.49 .87 1.00 1.00

67�F1100 520 38.0 11.1 1.62 .62 .75 .89 36.6 10.7 1.88 .63 .77 .91 34.8 10.2 2.16 .64 .79 .93 33.0 9.7 2.49 .65 .81 .96

67�F(19�C)

1200 565 39.0 11.4 1.62 .63 .78 .92 37.2 10.9 1.87 .64 .79 .94 35.4 10.4 2.15 .65 .81 .96 33.6 9.8 2.48 .67 .83 .98(19�C)

1250 590 39.0 11.4 1.62 .64 .79 .93 37.4 11.0 1.87 .65 .81 .95 35.8 10.5 2.15 .66 .82 .97 33.8 9.9 2.48 .68 .85 .99

71�F1100 520 40.5 11.9 1.62 .47 .60 .73 38.5 11.3 1.87 .48 .61 .74 37.0 10.8 2.15 .48 .62 .76 35.0 10.3 2.47 .49 .64 .78

71�F(22�C)

1200 565 41.0 12.0 1.62 .48 .62 .75 39.5 11.6 1.86 .48 .63 .77 37.6 11.0 2.14 .49 .64 .79 35.6 10.4 2.47 .50 .65 .81(22�C)

1250 590 41.5 12.2 1.62 .48 .62 .76 40.0 11.7 1.86 .49 .63 .78 37.8 11.1 2.14 .49 .65 .80 36.0 10.6 2.46 .50 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−048 with [CB30U−41/46]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 46.5 13.6 2.84 .77 .91 1.00 44.5 13.0 3.18 .79 .93 1.00 42.5 12.5 3.56 .80 .96 1.00 40.0 11.7 3.99 .83 .98 1.00

63�F(17�C)

1500 710 47.5 13.9 2.84 .79 .93 1.00 45.0 13.2 3.19 .80 .95 1.00 43.0 12.6 3.57 .82 .97 1.00 40.5 11.9 4.00 .84 .99 1.00(17�C)

1550 730 47.5 13.9 2.85 .79 .94 1.00 45.5 13.3 3.19 .81 .96 1.00 43.0 12.6 3.58 .83 .98 1.00 41.0 12.0 4.00 .86 1.00 1.00

67�F1400 660 49.5 14.5 2.87 .61 .75 .87 47.5 13.9 3.22 .62 .76 .89 45.0 13.2 3.60 .63 .78 .92 42.5 12.5 4.03 .65 .80 .95

67�F(19�C)

1500 710 50.5 14.8 2.87 .62 .76 .90 48.0 14.1 3.22 .63 .78 .92 45.5 13.3 3.60 .64 .80 .94 43.0 12.6 4.04 .66 .82 .97(19�C)

1550 730 50.5 14.8 2.88 .63 .77 .91 48.5 14.2 3.23 .64 .79 .93 46.0 13.5 3.61 .65 .80 .96 43.0 12.6 4.04 .67 .83 .98

71�F1400 660 52.0 15.2 2.90 .47 .60 .72 50.0 14.7 3.24 .48 .61 .74 47.5 13.9 3.63 .48 .62 .75 45.0 13.2 4.06 .49 .63 .77

71�F(22�C)

1500 710 53.0 15.5 2.90 .48 .61 .74 50.5 14.8 3.25 .48 .62 .75 48.0 14.1 3.63 .48 .63 .77 45.5 13.3 4.07 .49 .64 .79(22�C)

1550 730 53.5 15.7 2.91 .48 .61 .74 51.0 14.9 3.26 .48 .63 .76 48.5 14.2 3.64 .49 .64 .78 46.0 13.5 4.08 .50 .65 .80

Page 103: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 4 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 103

FIRST STAGE COOLING CAPACITY − XC21−048 with [CB30U−51]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 36.2 10.6 1.63 .78 .92 1.00 34.8 10.2 1.88 .80 .94 1.00 33.2 9.7 2.17 .81 .96 1.00 31.6 9.3 2.50 .84 .99 1.00

63�F(17�C)

1200 565 37.0 10.8 1.63 .80 .95 1.00 35.6 10.4 1.88 .82 .97 1.00 34.0 10.0 2.17 .84 .99 1.00 32.2 9.4 2.49 .86 1.00 1.00(17�C)

1300 615 37.8 11.1 1.62 .82 .97 1.00 36.4 10.7 1.88 .84 .99 1.00 34.6 10.1 2.16 .86 1.00 1.00 33.0 9.7 2.48 .88 1.00 1.00

67�F1100 520 38.5 11.3 1.62 .62 .76 .89 37.0 10.8 1.87 .63 .77 .91 35.4 10.4 2.15 .64 .79 .93 33.4 9.8 2.48 .65 .81 .95

67�F(19�C)

1200 565 39.5 11.6 1.62 .63 .77 .91 37.8 11.1 1.87 .64 .79 .93 36.0 10.6 2.15 .65 .81 .95 34.0 10.0 2.48 .67 .83 .98(19�C)

1300 615 40.0 11.7 1.62 .64 .80 .94 38.5 11.3 1.87 .66 .81 .96 36.6 10.7 2.15 .67 .83 .98 34.6 10.1 2.47 .68 .86 1.00

71�F1100 520 41.0 12.0 1.62 .47 .60 .73 39.5 11.6 1.86 .48 .61 .74 37.8 11.1 2.14 .48 .63 .76 35.8 10.5 2.46 .49 .64 .78

71�F(22�C)

1200 565 42.0 12.3 1.62 .48 .61 .75 40.5 11.9 1.86 .48 .63 .76 38.5 11.3 2.14 .49 .64 .78 36.4 10.7 2.46 .49 .65 .80(22�C)

1300 615 43.0 12.6 1.62 .49 .63 .77 41.0 12.0 1.86 .49 .64 .79 39.0 11.4 2.14 .50 .65 .81 37.0 10.8 2.45 .51 .67 .83

SECOND STAGE COOLING CAPACITY − XC21−048 with [CB30U−51]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 48.0 14.1 2.85 .77 .91 1.00 46.0 13.5 3.20 .78 .93 1.00 44.0 12.9 3.58 .80 .95 1.00 41.5 12.2 4.02 .82 .97 1.00

63�F(17�C)

1600 755 49.5 14.5 2.87 .80 .94 1.00 47.5 13.9 3.22 .81 .97 1.00 45.0 13.2 3.60 .83 .98 1.00 42.5 12.5 4.03 .86 1.00 1.00(17�C)

1800 850 51.0 14.9 2.88 .83 .98 1.00 49.0 14.4 3.23 .85 .99 1.00 46.5 13.6 3.62 .87 1.00 1.00 44.0 12.9 4.05 .90 1.00 1.00

67�F1400 660 51.0 14.9 2.89 .61 .74 .87 49.0 14.4 3.23 .62 .76 .89 46.5 13.6 3.62 .63 .78 .92 44.0 12.9 4.05 .65 .80 .94

67�F(19�C)

1600 755 52.5 15.4 2.90 .63 .77 .91 50.5 14.8 3.25 .64 .79 .93 48.0 14.1 3.63 .65 .81 .96 45.0 13.2 4.07 .67 .83 .98(19�C)

1800 850 54.0 15.8 2.91 .65 .80 .95 51.5 15.1 3.26 .66 .82 .97 49.0 14.4 3.65 .68 .85 .99 46.0 13.5 4.08 .69 .87 1.00

71�F1400 660 54.0 15.8 2.92 .47 .60 .72 52.0 15.2 3.27 .47 .61 .73 49.5 14.5 3.65 .48 .62 .75 46.5 13.6 4.08 .49 .63 .77

71�F(22�C)

1600 755 56.0 16.4 2.94 .48 .62 .75 53.5 15.7 3.28 .48 .63 .77 51.0 14.9 3.67 .49 .64 .78 48.0 14.1 4.10 .50 .65 .81(22�C)

1800 850 57.0 16.7 2.95 .49 .64 .78 54.5 16.0 3.30 .49 .65 .80 52.0 15.2 3.69 .50 .66 .82 49.0 14.4 4.12 .51 .68 .85

FIRST STAGE COOLING CAPACITY − XC21−048 with [CB30U−65]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1100 520 37.0 10.8 1.63 .78 .93 1.00 35.4 10.4 1.88 .80 .95 1.00 33.6 9.8 2.17 .82 .97 1.00 32.0 9.4 2.49 .84 .99 1.00

63�F(17�C)

1200 565 37.6 11.0 1.62 .80 .95 1.00 36.0 10.6 1.88 .82 .97 1.00 34.4 10.1 2.16 .84 .99 1.00 32.8 9.6 2.49 .86 1.00 1.00(17�C)

1300 615 38.5 11.3 1.62 .83 .98 1.00 36.8 10.8 1.87 .84 1.00 1.00 35.2 10.3 2.16 .87 1.00 1.00 33.6 9.8 2.48 .89 1.00 1.00

67�F1100 520 39.5 11.6 1.62 .62 .76 .89 37.6 11.0 1.87 .63 .77 .91 36.0 10.6 2.15 .64 .79 .94 34.0 10.0 2.48 .65 .81 .96

67�F(19�C)

1200 565 40.0 11.7 1.62 .63 .77 .92 38.5 11.3 1.87 .64 .79 .94 36.6 10.7 2.15 .65 .81 .96 34.6 10.1 2.47 .66 .83 .99(19�C)

1300 615 41.0 12.0 1.62 .65 .80 .95 39.0 11.4 1.87 .66 .82 .97 37.2 10.9 2.14 .67 .84 .99 35.2 10.3 2.47 .69 .86 1.00

71�F1100 520 42.0 12.3 1.62 .47 .60 .73 40.0 11.7 1.86 .48 .61 .74 38.5 11.3 2.14 .48 .63 .76 36.4 10.7 2.46 .49 .64 .78

71�F(22�C)

1200 565 42.5 12.5 1.61 .47 .61 .75 41.0 12.0 1.86 .48 .62 .76 39.0 11.4 2.14 .48 .64 .78 37.0 10.8 2.46 .49 .65 .80(22�C)

1300 615 43.5 12.7 1.61 .48 .63 .77 41.5 12.2 1.86 .49 .64 .79 39.5 11.6 2.14 .50 .66 .81 37.6 11.0 2.45 .50 .67 .83

SECOND STAGE COOLING CAPACITY − XC21−048 with [CB30U−65]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1400 660 49.0 14.4 2.86 .77 .91 1.00 46.5 13.6 3.21 .79 .93 1.00 44.5 13.0 3.59 .80 .96 1.00 42.0 12.3 4.02 .83 .98 1.00

63�F(17�C)

1600 755 50.0 14.7 2.87 .80 .95 1.00 48.0 14.1 3.22 .82 .97 1.00 45.5 13.3 3.61 .84 .99 1.00 43.0 12.6 4.04 .86 1.00 1.00(17�C)

1800 850 51.5 15.1 2.89 .83 .98 1.00 49.5 14.5 3.24 .85 1.00 1.00 47.0 13.8 3.62 .88 1.00 1.00 44.5 13.0 4.06 .90 1.00 1.00

67�F1400 660 52.0 15.2 2.89 .61 .75 .88 49.5 14.5 3.24 .62 .76 .90 47.0 13.8 3.62 .63 .78 .92 44.5 13.0 4.06 .65 .80 .95

67�F(19�C)

1600 755 53.5 15.7 2.91 .63 .78 .92 51.0 14.9 3.25 .64 .79 .94 48.5 14.2 3.64 .65 .81 .96 45.5 13.3 4.07 .67 .84 .99(19�C)

1800 850 54.5 16.0 2.92 .65 .81 .96 52.0 15.2 3.27 .66 .83 .98 49.5 14.5 3.65 .68 .85 1.00 46.5 13.6 4.08 .70 .88 1.00

71�F1400 660 55.0 16.1 2.93 .47 .60 .72 52.5 15.4 3.27 .47 .61 .74 50.0 14.7 3.66 .48 .62 .75 47.0 13.8 4.09 .48 .63 .78

71�F(22�C)

1600 755 56.5 16.6 2.94 .48 .62 .75 54.0 15.8 3.29 .48 .63 .77 51.5 15.1 3.68 .49 .64 .79 48.5 14.2 4.11 .49 .66 .81(22�C)

1800 850 57.5 16.9 2.96 .49 .64 .78 55.0 16.1 3.30 .49 .65 .80 52.5 15.4 3.69 .50 .67 .83 49.5 14.5 4.12 .51 .68 .85

Page 104: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 5 TON

UP−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 104

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−44/48B/C−6F] [C33−48B/C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 44.0 12.9 2.10 .76 .89 1.00 42.0 12.3 2.45 .77 .91 1.00 40.0 11.7 2.86 .79 .93 1.00 38.0 11.1 3.33 .81 .96 1.00

63�F(17�C)

1400 660 44.5 13.0 2.09 .77 .91 1.00 43.0 12.6 2.44 .79 .93 1.00 41.0 12.0 2.85 .80 .95 1.00 38.5 11.3 3.33 .82 .98 1.00(17�C)

1500 710 45.5 13.3 2.08 .79 .93 1.00 43.5 12.7 2.44 .80 .95 1.00 41.5 12.2 2.85 .82 .97 1.00 39.0 11.4 3.30 .84 .99 1.00

67�F1300 615 46.5 13.6 2.08 .61 .74 .85 45.0 13.2 2.43 .61 .75 .87 42.5 12.5 2.83 .62 .76 .89 40.5 11.9 3.30 .64 .78 .92

67�F(19�C)

1400 660 47.5 13.9 2.08 .61 .74 .87 45.5 13.3 2.43 .62 .76 .89 43.5 12.7 2.83 .64 .78 .92 41.0 12.0 3.30 .65 .80 .94(19�C)

1500 710 48.0 14.1 2.08 .62 .76 .90 46.0 13.5 2.42 .63 .78 .91 44.0 12.9 2.82 .65 .79 .94 41.5 12.2 3.28 .66 .82 .96

71�F1300 615 49.5 14.5 2.07 .47 .59 .71 47.5 13.9 2.42 .47 .60 .72 45.5 13.3 2.80 .48 .61 .74 43.0 12.6 3.27 .49 .62 .76

71�F(22�C)

1400 660 50.5 14.8 2.07 .47 .60 .72 48.0 14.1 2.42 .48 .61 .74 46.0 13.5 2.81 .48 .62 .75 43.5 12.7 3.26 .49 .63 .77(22�C)

1500 710 51.0 14.9 2.07 .48 .61 .74 49.0 14.4 2.41 .48 .62 .75 46.5 13.6 2.80 .49 .63 .77 44.0 12.9 3.26 .50 .64 .78

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−44/48B/C−6F] [C33−48B/C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1600 755 57.0 16.7 3.68 .73 .85 .97 54.5 16.0 4.12 .75 .87 .99 51.5 15.1 4.63 .76 .89 1.00 48.5 14.2 5.25 .78 .92 1.00

63�F(17�C)

1800 850 58.5 17.1 3.69 .75 .88 .99 56.0 16.4 4.15 .77 .90 1.00 53.0 15.5 4.67 .78 .92 1.00 49.5 14.5 5.25 .80 .95 1.00(17�C)

2000 945 60.0 17.6 3.69 .77 .91 1.00 57.0 16.7 4.16 .78 .93 1.00 54.0 15.8 4.68 .80 .95 1.00 50.5 14.8 5.26 .83 .98 1.00

67�F1600 755 60.5 17.7 3.71 .59 .71 .82 57.5 16.9 4.17 .60 .72 .84 54.5 16.0 4.69 .61 .74 .86 51.0 14.9 5.24 .62 .75 .88

67�F(19�C)

1800 850 62.0 18.2 3.72 .61 .73 .85 59.0 17.3 4.18 .61 .74 .87 55.5 16.3 4.69 .63 .76 .89 52.5 15.4 5.28 .64 .78 .92(19�C)

2000 945 63.0 18.5 3.74 .62 .75 .87 60.0 17.6 4.19 .63 .76 .89 57.0 16.7 4.72 .64 .78 .92 53.5 15.7 5.30 .65 .80 .95

71�F1600 755 63.5 18.6 3.74 .47 .58 .68 60.5 17.7 4.20 .47 .59 .70 57.5 16.9 4.72 .48 .60 .71 54.0 15.8 5.31 .48 .61 .73

71�F(22�C)

1800 850 65.0 19.0 3.76 .48 .59 .70 62.0 18.2 4.22 .48 .60 .72 59.0 17.3 4.75 .48 .61 .73 55.5 16.3 5.31 .49 .62 .75(22�C)

2000 945 67.0 19.6 3.77 .48 .60 .73 63.5 18.6 4.23 .48 .61 .74 60.0 17.6 4.76 .49 .62 .75 56.5 16.6 5.34 .50 .64 .78

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−49C−6F] [C33−49C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT t

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTemperat

ure

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbure

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 44.5 13.0 2.23 .76 .89 1.00 42.5 12.5 2.61 .78 .91 1.00 40.5 11.9 3.06 .79 .94 1.00 38.0 11.1 3.56 .81 .97 1.00

63�F(17�C)

1400 660 45.0 13.2 2.23 .78 .91 1.00 43.0 12.6 2.61 .79 .94 1.00 41.0 12.0 3.03 .81 .96 1.00 39.0 11.4 3.56 .83 .99 1.00(17�C)

1500 710 46.0 13.5 2.22 .79 .93 1.00 44.0 12.9 2.59 .81 .95 1.00 42.0 12.3 3.03 .83 .98 1.00 39.5 11.6 3.52 .85 1.00 1.00

67�F1300 615 47.0 13.8 2.19 .61 .74 .86 45.0 13.2 2.58 .62 .75 .88 43.0 12.6 3.02 .63 .77 .90 40.5 11.9 3.54 .64 .79 .93

67�F(19�C)

1400 660 48.0 14.1 2.20 .62 .75 .88 46.0 13.5 2.58 .63 .76 .90 43.5 12.7 3.01 .64 .78 .92 41.5 12.2 3.50 .65 .80 .95(19�C)

1500 710 48.5 14.2 2.20 .63 .76 .90 46.5 13.6 2.57 .64 .78 .92 44.5 13.0 2.98 .65 .80 .94 42.0 12.3 3.51 .66 .82 .98

71�F1300 615 49.5 14.5 2.19 .47 .60 .71 47.5 13.9 2.53 .48 .60 .72 45.5 13.3 2.98 .48 .61 .74 43.0 12.6 3.48 .49 .63 .76

71�F(22�C)

1400 660 50.5 14.8 2.16 .48 .60 .73 48.5 14.2 2.55 .48 .61 .74 46.0 13.5 2.97 .49 .63 .76 43.5 12.7 3.45 .49 .64 .78(22�C)

1500 710 51.0 14.9 2.17 .48 .61 .74 49.0 14.4 2.54 .49 .62 .76 46.5 13.6 2.96 .49 .64 .77 44.0 12.9 3.46 .50 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−49C−6F] [C33−49C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1600 755 58.0 17.0 3.83 .74 .86 .97 55.5 16.3 4.32 .75 .88 .99 52.5 15.4 4.90 .77 .90 1.00 49.0 14.4 5.53 .79 .93 1.00

63�F(17�C)

1800 850 60.0 17.6 3.84 .76 .88 1.00 57.0 16.7 4.35 .77 .91 1.00 53.5 15.7 4.92 .79 .93 1.00 50.0 14.7 5.54 .81 .97 1.00(17�C)

2000 945 61.0 17.9 3.87 .77 .91 1.00 58.0 17.0 4.37 .79 .94 1.00 55.0 16.1 4.93 .81 .96 1.00 51.5 15.1 5.54 .84 .99 1.00

67�F1600 755 61.5 18.0 3.86 .60 .71 .82 58.5 17.1 4.36 .61 .73 .84 55.5 16.3 4.89 .62 .74 .86 52.0 15.2 5.55 .63 .76 .89

67�F(19�C)

1800 850 63.0 18.5 3.87 .61 .73 .85 60.0 17.6 4.35 .62 .75 .87 57.0 16.7 4.94 .63 .76 .90 53.0 15.5 5.57 .64 .79 .93(19�C)

2000 945 64.5 18.9 3.88 .62 .75 .88 61.5 18.0 4.39 .63 .77 .90 58.0 17.0 4.96 .64 .79 .93 54.5 16.0 5.58 .66 .81 .96

71�F1600 755 64.5 18.9 3.87 .47 .58 .69 61.5 18.0 4.38 .47 .59 .70 58.5 17.1 4.95 .48 .60 .72 55.0 16.1 5.54 .48 .61 .74

71�F(22�C)

1800 850 66.0 19.3 3.90 .48 .59 .71 63.0 18.5 4.40 .48 .60 .72 60.0 17.6 4.93 .49 .61 .74 56.0 16.4 5.59 .49 .63 .76(22�C)

2000 945 68.0 19.9 3.91 .48 .61 .73 65.0 19.0 4.38 .49 .62 .74 61.5 18.0 4.97 .49 .63 .76 57.5 16.9 5.60 .50 .64 .79

Page 105: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 5 TON

UP−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 105

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−50/60C−6F] [C33−50/60C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 44.5 13.0 2.10 .76 .90 1.00 42.5 12.5 2.45 .78 .92 1.00 40.5 11.9 2.85 .79 .94 1.00 38.5 11.3 3.33 .81 .96 1.00

63�F(17�C)

1400 660 45.5 13.3 2.09 .78 .92 1.00 43.5 12.7 2.44 .79 .94 1.00 41.5 12.2 2.85 .81 .96 1.00 39.0 11.4 3.31 .82 .98 1.00(17�C)

1500 710 46.0 13.5 2.08 .79 .94 1.00 44.0 12.9 2.44 .81 .96 1.00 42.0 12.3 2.84 .83 .98 1.00 39.5 11.6 3.30 .85 1.00 1.00

67�F1300 615 47.5 13.9 2.07 .61 .74 .86 45.5 13.3 2.44 .62 .75 .88 43.0 12.6 2.83 .63 .77 .90 41.0 12.0 3.29 .64 .79 .93

67�F(19�C)

1400 660 48.0 14.1 2.08 .62 .75 .88 46.0 13.5 2.43 .63 .77 .90 44.0 12.9 2.83 .64 .78 .92 41.5 12.2 3.28 .65 .81 .95(19�C)

1500 710 48.5 14.2 2.07 .63 .77 .90 46.5 13.6 2.43 .64 .78 .92 44.5 13.0 2.82 .65 .80 .95 42.0 12.3 3.27 .66 .82 .97

71�F1300 615 50.0 14.7 2.07 .47 .59 .71 48.0 14.1 2.41 .47 .60 .72 46.0 13.5 2.81 .48 .61 .74 43.5 12.7 3.26 .49 .63 .76

71�F(22�C)

1400 660 51.0 14.9 2.07 .47 .60 .73 49.0 14.4 2.41 .48 .61 .74 46.5 13.6 2.80 .49 .62 .76 44.0 12.9 3.26 .49 .64 .78(22�C)

1500 710 51.5 15.1 2.07 .48 .61 .74 49.5 14.5 2.41 .49 .63 .76 47.0 13.8 2.80 .49 .64 .78 44.5 13.0 3.24 .50 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−50/60C−6F] [C33−50/60C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1600 755 58.0 17.0 3.68 .74 .86 .97 55.0 16.1 4.13 .75 .88 .99 52.5 15.4 4.67 .77 .90 1.00 49.0 14.4 5.25 .79 .93 1.00

63�F(17�C)

1800 850 59.5 17.4 3.70 .76 .89 1.00 56.5 16.6 4.16 .77 .91 1.00 53.5 15.7 4.68 .79 .93 1.00 50.0 14.7 5.25 .81 .96 1.00(17�C)

2000 945 61.0 17.9 3.71 .78 .91 1.00 58.0 17.0 4.17 .79 .94 1.00 55.0 16.1 4.69 .81 .96 1.00 51.5 15.1 5.28 .83 .99 1.00

67�F1600 755 61.0 17.9 3.72 .60 .71 .82 58.5 17.1 4.18 .60 .73 .84 55.0 16.1 4.68 .61 .74 .86 52.0 15.2 5.27 .63 .76 .89

67�F(19�C)

1800 850 62.5 18.3 3.73 .61 .73 .85 59.5 17.4 4.19 .62 .75 .87 56.5 16.6 4.71 .63 .76 .90 53.0 15.5 5.29 .64 .78 .93(19�C)

2000 945 64.0 18.8 3.74 .62 .75 .88 61.0 17.9 4.20 .63 .77 .90 58.0 17.0 4.73 .64 .79 .93 54.0 15.8 5.30 .66 .81 .96

71�F1600 755 64.5 18.9 3.75 .47 .58 .69 61.5 18.0 4.21 .47 .59 .70 58.5 17.1 4.74 .48 .60 .72 55.0 16.1 5.32 .48 .61 .73

71�F(22�C)

1800 850 66.0 19.3 3.77 .47 .59 .71 63.0 18.5 4.24 .48 .60 .72 60.0 17.6 4.75 .48 .61 .74 56.0 16.4 5.33 .49 .63 .76(22�C)

2000 945 68.0 19.9 3.79 .48 .61 .73 64.5 18.9 4.24 .48 .62 .74 61.0 17.9 4.77 .49 .63 .76 57.0 16.7 5.35 .50 .64 .78

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−60D−6F] [C33−60D]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 45.0 13.2 2.09 .77 .90 1.00 43.5 12.7 2.44 .78 .93 1.00 41.5 12.2 2.85 .80 .95 1.00 39.0 11.4 3.32 .82 .98 1.00

63�F(17�C)

1400 660 46.0 13.5 2.08 .78 .93 1.00 44.0 12.9 2.44 .80 .95 1.00 42.0 12.3 2.84 .82 .97 1.00 39.5 11.6 3.31 .84 1.00 1.00(17�C)

1500 710 46.5 13.6 2.09 .80 .95 1.00 44.5 13.0 2.43 .82 .97 1.00 42.5 12.5 2.83 .84 .99 1.00 40.5 11.9 3.30 .86 1.00 1.00

67�F1300 615 48.0 14.1 2.08 .62 .74 .87 46.0 13.5 2.43 .63 .76 .89 44.0 12.9 2.82 .64 .78 .92 41.5 12.2 3.29 .65 .80 .94

67�F(19�C)

1400 660 48.5 14.2 2.08 .62 .75 .89 46.5 13.6 2.42 .64 .78 .91 44.5 13.0 2.82 .65 .80 .94 42.0 12.3 3.27 .66 .82 .97(19�C)

1500 710 49.5 14.5 2.07 .64 .78 .91 47.5 13.9 2.42 .65 .79 .94 45.0 13.2 2.81 .66 .81 .96 42.5 12.5 3.26 .67 .84 .99

71�F1300 615 51.0 14.9 2.07 .47 .60 .72 49.0 14.4 2.41 .48 .61 .73 46.5 13.6 2.80 .48 .62 .75 44.0 12.9 3.25 .49 .63 .77

71�F(22�C)

1400 660 51.5 15.1 2.06 .48 .61 .74 49.5 14.5 2.41 .48 .62 .75 47.5 13.9 2.79 .49 .63 .77 44.5 13.0 3.26 .49 .65 .79(22�C)

1500 710 52.5 15.4 2.07 .48 .62 .75 50.0 14.7 2.40 .49 .63 .77 48.0 14.1 2.79 .49 .64 .79 45.5 13.3 3.24 .50 .66 .81

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−60D−6F] [C33−60D]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1600 755 59.0 17.3 3.69 .75 .87 .99 56.5 16.6 4.15 .76 .89 1.00 53.5 15.7 4.68 .77 .91 1.00 50.0 14.7 5.24 .80 .94 1.00

63�F(17�C)

1800 850 60.5 17.7 3.71 .77 .90 1.00 58.0 17.0 4.18 .78 .92 1.00 54.5 16.0 4.69 .80 .95 1.00 51.5 15.1 5.28 .82 .98 1.00(17�C)

2000 945 62.0 18.2 3.73 .79 .93 1.00 59.0 17.3 4.18 .81 .96 1.00 56.0 16.4 4.70 .83 .98 1.00 52.5 15.4 5.29 .85 1.00 1.00

67�F1600 755 62.5 18.3 3.72 .60 .72 .84 59.5 17.4 4.19 .61 .73 .86 56.0 16.4 4.70 .62 .75 .88 53.0 15.5 5.27 .63 .77 .91

67�F(19�C)

1800 850 64.0 18.8 3.74 .62 .74 .87 61.0 17.9 4.20 .62 .76 .89 58.0 17.0 4.73 .63 .78 .92 54.5 16.0 5.30 .65 .80 .95(19�C)

2000 945 65.0 19.0 3.76 .63 .76 .90 62.5 18.3 4.23 .64 .78 .92 59.0 17.3 4.74 .65 .80 .95 55.5 16.3 5.32 .66 .83 .98

71�F1600 755 66.0 19.3 3.77 .47 .58 .70 63.0 18.5 4.24 .47 .59 .71 59.5 17.4 4.75 .48 .60 .73 56.0 16.4 5.33 .48 .62 .75

71�F(22�C)

1800 850 68.0 19.9 3.79 .47 .60 .72 64.5 18.9 4.24 .48 .61 .74 61.0 17.9 4.77 .48 .62 .75 57.0 16.7 5.35 .49 .63 .77(22�C)

2000 945 69.0 20.2 3.80 .48 .62 .74 66.0 19.3 4.27 .49 .62 .76 62.0 18.2 4.78 .49 .64 .78 58.0 17.0 5.36 .50 .65 .80

Page 106: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 5 TON

UP−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 106

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−62C−6F] [C33−62C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 46.0 13.5 2.22 .78 .92 1.00 44.0 12.9 2.58 .79 .94 1.00 41.5 12.2 3.03 .81 .97 1.00 39.5 11.6 3.53 .83 .99 1.00

63�F(17�C)

1400 660 47.0 13.8 2.20 .80 .95 1.00 44.5 13.0 2.58 .81 .97 1.00 42.5 12.5 3.03 .83 .99 1.00 40.0 11.7 3.52 .86 1.00 1.00(17�C)

1500 710 47.5 13.9 2.20 .82 .97 1.00 45.5 13.3 2.58 .83 .99 1.00 43.0 12.6 3.00 .85 1.00 1.00 41.0 12.0 3.51 .88 1.00 1.00

67�F1300 615 49.0 14.4 2.19 .62 .75 .88 46.5 13.6 2.57 .63 .77 .90 44.5 13.0 2.98 .64 .79 .93 42.0 12.3 3.50 .65 .81 .96

67�F(19�C)

1400 660 49.5 14.5 2.19 .63 .77 .91 47.5 13.9 2.54 .64 .79 .93 45.0 13.2 2.99 .65 .80 .96 42.5 12.5 3.47 .66 .83 .99(19�C)

1500 710 50.5 14.8 2.17 .64 .79 .93 48.0 14.1 2.55 .65 .80 .95 45.5 13.3 2.98 .66 .83 .98 43.0 12.6 3.47 .68 .85 1.00

71�F1300 615 51.5 15.1 2.18 .47 .60 .73 49.5 14.5 2.54 .48 .61 .74 47.0 13.8 2.96 .48 .62 .76 44.5 13.0 3.45 .49 .64 .78

71�F(22�C)

1400 660 52.5 15.4 2.18 .48 .62 .75 50.5 14.8 2.54 .48 .63 .76 48.0 14.1 2.93 .49 .64 .78 45.0 13.2 3.46 .50 .66 .80(22�C)

1500 710 53.5 15.7 2.17 .49 .63 .76 51.0 14.9 2.50 .49 .64 .78 48.5 14.2 2.94 .50 .65 .80 46.0 13.5 3.42 .50 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−62C−6F] [C33−62C]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1600 755 60.5 17.7 3.85 .75 .88 1.00 57.5 16.9 4.35 .77 .90 1.00 54.0 15.8 4.91 .79 .93 1.00 50.5 14.8 5.54 .81 .96 1.00

63�F(17�C)

1800 850 62.0 18.2 3.86 .78 .92 1.00 59.0 17.3 4.37 .80 .94 1.00 55.5 16.3 4.93 .82 .97 1.00 52.0 15.2 5.55 .84 1.00 1.00(17�C)

2000 945 63.5 18.6 3.88 .80 .95 1.00 60.5 17.7 4.38 .82 .98 1.00 57.0 16.7 4.95 .84 1.00 1.00 53.5 15.7 5.55 .87 1.00 1.00

67�F1600 755 64.0 18.8 3.87 .60 .73 .85 60.5 17.7 4.37 .61 .74 .87 57.5 16.9 4.94 .63 .76 .90 53.5 15.7 5.56 .64 .79 .93

67�F(19�C)

1800 850 66.0 19.3 3.88 .62 .75 .88 62.5 18.3 4.40 .63 .77 .91 59.0 17.3 4.95 .64 .79 .93 55.0 16.1 5.58 .66 .82 .97(19�C)

2000 945 67.0 19.6 3.90 .64 .78 .92 64.0 18.8 4.41 .65 .80 .94 60.0 17.6 4.96 .66 .82 .97 56.0 16.4 5.57 .69 .85 1.00

71�F1600 755 68.0 19.9 3.91 .47 .59 .70 64.5 18.9 4.39 .47 .60 .72 61.0 17.9 4.93 .48 .61 .73 57.0 16.7 5.60 .49 .62 .76

71�F(22�C)

1800 850 69.0 20.2 3.91 .47 .60 .73 66.0 19.3 4.41 .48 .61 .74 62.5 18.3 4.98 .49 .63 .77 58.0 17.0 5.60 .49 .64 .79(22�C)

2000 945 71.0 20.8 3.93 .48 .62 .75 67.0 19.6 4.44 .49 .63 .77 63.5 18.6 4.99 .50 .65 .79 59.5 17.4 5.58 .51 .66 .82

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−62D−6F] [C33−62D]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 45.5 13.3 2.08 .77 .91 1.00 43.5 12.7 2.44 .78 .92 1.00 41.5 12.2 2.84 .80 .95 1.00 39.5 11.6 3.31 .82 .98 1.00

63�F(17�C)

1400 660 46.5 13.6 2.08 .79 .93 1.00 44.5 13.0 2.43 .80 .95 1.00 42.5 12.5 2.83 .82 .97 1.00 40.0 11.7 3.30 .84 1.00 1.00(17�C)

1500 710 47.0 13.8 2.08 .80 .95 1.00 45.0 13.2 2.43 .82 .97 1.00 43.0 12.6 2.83 .84 .99 1.00 40.5 11.9 3.29 .86 1.00 1.00

67�F1300 615 48.0 14.1 2.08 .61 .74 .87 46.0 13.5 2.42 .62 .76 .89 44.0 12.9 2.82 .63 .78 .91 42.0 12.3 3.29 .65 .80 .94

67�F(19�C)

1400 660 49.0 14.4 2.07 .62 .76 .89 47.0 13.8 2.42 .64 .78 .91 45.0 13.2 2.81 .65 .79 .94 42.5 12.5 3.28 .66 .82 .97(19�C)

1500 710 50.0 14.7 2.07 .64 .78 .91 47.5 13.9 2.41 .65 .79 .94 45.5 13.3 2.81 .66 .81 .96 43.0 12.6 3.26 .67 .83 .99

71�F1300 615 51.0 14.9 2.07 .47 .59 .72 49.0 14.4 2.40 .48 .60 .73 46.5 13.6 2.80 .48 .62 .75 44.0 12.9 3.25 .49 .63 .77

71�F(22�C)

1400 660 51.5 15.1 2.06 .48 .60 .73 49.5 14.5 2.41 .48 .62 .75 47.5 13.9 2.80 .49 .63 .77 45.0 13.2 3.25 .49 .65 .79(22�C)

1500 710 52.5 15.4 2.06 .48 .62 .75 50.5 14.8 2.40 .49 .63 .77 48.0 14.1 2.79 .49 .65 .79 45.5 13.3 3.23 .50 .66 .81

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−62D−6F] [C33−62D]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1600 755 59.5 17.4 3.69 .74 .87 .99 57.0 16.7 4.16 .76 .89 1.00 54.0 15.8 4.67 .78 .91 1.00 50.5 14.8 5.26 .80 .94 1.00

63�F(17�C)

1800 850 61.5 18.0 3.71 .77 .90 1.00 58.5 17.1 4.17 .78 .92 1.00 55.5 16.3 4.70 .80 .95 1.00 52.0 15.2 5.26 .82 .98 1.00(17�C)

2000 945 63.0 18.5 3.73 .79 .93 1.00 60.0 17.6 4.20 .81 .95 1.00 56.5 16.6 4.72 .83 .98 1.00 53.0 15.5 5.29 .85 1.00 1.00

67�F1600 755 63.0 18.5 3.74 .60 .72 .84 60.0 17.6 4.20 .61 .73 .85 57.0 16.7 4.72 .62 .75 .88 53.5 15.7 5.29 .63 .77 .91

67�F(19�C)

1800 850 65.0 19.0 3.75 .61 .74 .87 62.0 18.2 4.22 .62 .76 .89 58.5 17.1 4.73 .63 .78 .91 55.0 16.1 5.32 .65 .80 .94(19�C)

2000 945 66.0 19.3 3.77 .63 .76 .90 63.5 18.6 4.24 .64 .78 .92 60.0 17.6 4.75 .65 .80 .95 56.0 16.4 5.34 .67 .83 .98

71�F1600 755 67.0 19.6 3.78 .47 .58 .70 63.5 18.6 4.24 .47 .59 .71 60.5 17.7 4.76 .48 .60 .72 56.5 16.6 5.34 .48 .61 .74

71�F(22�C)

1800 850 68.0 19.9 3.80 .47 .60 .72 65.0 19.0 4.27 .48 .61 .73 61.5 18.0 4.78 .48 .62 .75 58.0 17.0 5.34 .49 .63 .77(22�C)

2000 945 70.0 20.5 3.81 .48 .61 .74 66.0 19.3 4.27 .49 .62 .76 63.0 18.5 4.80 .49 .64 .78 59.0 17.3 5.38 .50 .65 .80

Page 107: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 5 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 107

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−44/48C−6F + G60UHV−60C−090][C33−48C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1135 535 42.0 12.3 2.27 .73 .85 .97 40.5 11.9 2.64 .74 .87 .99 38.5 11.3 3.09 .75 .89 1.00 36.2 10.6 3.62 .77 .92 1.00

63�F(17�C)

1280 605 43.5 12.7 2.24 .75 .88 1.00 41.5 12.2 2.63 .76 .90 1.00 39.5 11.6 3.07 .78 .92 1.00 37.2 10.9 3.60 .80 .95 1.00(17�C)

1445 680 44.5 13.0 2.23 .78 .92 1.00 42.5 12.5 2.62 .79 .94 1.00 40.5 11.9 3.06 .81 .96 1.00 38.5 11.3 3.56 .83 .99 1.00

67�F1135 535 45.0 13.2 2.24 .59 .70 .82 43.0 12.6 2.62 .59 .72 .84 41.0 12.0 3.04 .60 .73 .85 38.5 11.3 3.56 .61 .75 .88

67�F(19�C)

1280 605 46.0 13.5 2.23 .60 .73 .85 44.0 12.9 2.58 .61 .73 .86 42.0 12.3 3.03 .62 .75 .89 39.5 11.6 3.55 .63 .77 .91(19�C)

1445 680 47.5 13.9 2.19 .61 .74 .88 45.5 13.3 2.58 .62 .76 .90 43.0 12.6 3.02 .63 .78 .92 40.5 11.9 3.50 .65 .80 .95

71�F1135 535 47.5 13.9 2.22 .46 .57 .68 45.5 13.3 2.58 .46 .58 .69 43.5 12.7 3.03 .46 .58 .70 41.0 12.0 3.51 .46 .59 .72

71�F(22�C)

1280 605 49.0 14.4 2.20 .46 .58 .70 47.0 13.8 2.58 .47 .59 .71 44.5 13.0 2.98 .47 .60 .72 42.5 12.5 3.50 .48 .61 .75(22�C)

1445 680 50.5 14.8 2.17 .47 .60 .72 48.0 14.1 2.53 .47 .61 .74 46.0 13.5 2.98 .48 .62 .76 43.5 12.7 3.48 .49 .63 .77

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−44/48C−6F + G60UHV−60C−090][C33−48C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1635 770 57.0 16.7 3.85 .74 .86 .97 54.0 15.8 4.34 .75 .88 .99 51.5 15.1 4.86 .77 .90 1.00 48.0 14.1 5.52 .78 .93 1.00

63�F(17�C)

1855 875 58.5 17.1 3.84 .76 .89 1.00 56.0 16.4 4.31 .77 .91 1.00 52.5 15.4 4.90 .79 .93 1.00 49.0 14.4 5.53 .81 .96 1.00(17�C)

2070 975 60.0 17.6 3.85 .78 .92 1.00 57.0 16.7 4.36 .79 .94 1.00 54.0 15.8 4.92 .81 .97 1.00 50.5 14.8 5.51 .84 .99 1.00

67�F1635 770 60.5 17.7 3.84 .59 .71 .82 57.5 16.9 4.37 .60 .72 .84 54.0 15.8 4.92 .61 .74 .86 50.5 14.8 5.53 .62 .76 .89

67�F(19�C)

1855 875 62.0 18.2 3.88 .61 .73 .85 59.0 17.3 4.37 .62 .75 .87 55.5 16.3 4.91 .63 .76 .90 52.0 15.2 5.55 .64 .79 .93(19�C)

2070 975 63.5 18.6 3.87 .63 .75 .88 60.5 17.7 4.36 .63 .77 .90 57.0 16.7 4.93 .64 .79 .93 53.5 15.7 5.56 .66 .81 .96

71�F1635 770 64.0 18.8 3.85 .47 .58 .68 60.5 17.7 4.38 .47 .59 .70 57.5 16.9 4.95 .48 .60 .72 53.5 15.7 5.58 .48 .61 .73

71�F(22�C)

1855 875 66.0 19.3 3.89 .47 .59 .71 62.5 18.3 4.40 .48 .60 .72 59.0 17.3 4.96 .48 .61 .74 55.0 16.1 5.57 .49 .63 .76(22�C)

2070 975 67.0 19.6 3.90 .48 .61 .73 64.0 18.8 4.41 .49 .62 .75 60.0 17.6 4.92 .49 .63 .77 56.0 16.4 5.58 .50 .65 .79

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−44/48C−6F + G61MPV−60C−090][C33−48C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1185 560 42.5 12.5 2.26 .74 .86 .98 41.0 12.0 2.62 .75 .88 1.00 39.0 11.4 3.08 .77 .90 1.00 36.6 10.7 3.61 .78 .93 1.00

63�F(17�C)

1355 640 44.0 12.9 2.24 .76 .90 1.00 42.0 12.3 2.62 .78 .92 1.00 40.0 11.7 3.07 .79 .94 1.00 37.8 11.1 3.59 .81 .97 1.00(17�C)

1545 730 45.5 13.3 2.23 .79 .94 1.00 43.5 12.7 2.61 .81 .96 1.00 41.5 12.2 3.03 .83 .98 1.00 39.0 11.4 3.57 .85 1.00 1.00

67�F1185 560 45.5 13.3 2.23 .59 .71 .83 43.5 12.7 2.62 .60 .73 .85 41.5 12.2 3.02 .61 .74 .87 39.0 11.4 3.56 .62 .76 .89

67�F(19�C)

1355 640 47.0 13.8 2.21 .61 .74 .86 45.0 13.2 2.59 .62 .75 .88 42.5 12.5 3.02 .63 .77 .90 40.0 11.7 3.54 .64 .79 .93(19�C)

1545 730 48.0 14.1 2.20 .63 .77 .90 46.0 13.5 2.57 .64 .78 .92 44.0 12.9 2.98 .65 .80 .95 41.0 12.0 3.51 .66 .82 .97

71�F1185 560 48.0 14.1 2.20 .46 .58 .69 46.0 13.5 2.58 .46 .58 .70 44.0 12.9 2.99 .47 .59 .71 41.5 12.2 3.50 .47 .60 .73

71�F(22�C)

1355 640 49.5 14.5 2.20 .47 .59 .71 47.5 13.9 2.55 .47 .60 .72 45.5 13.3 2.98 .48 .61 .74 43.0 12.6 3.49 .48 .62 .76(22�C)

1545 730 51.0 14.9 2.16 .48 .61 .74 49.0 14.4 2.55 .48 .62 .76 46.5 13.6 2.97 .49 .63 .77 44.0 12.9 3.46 .49 .65 .79

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−44/48C−6F + G61MPV−60C−090][C33−48C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1710 805 57.5 16.9 3.83 .75 .87 .98 54.5 16.0 4.35 .76 .89 1.00 52.0 15.2 4.89 .77 .91 1.00 48.5 14.2 5.53 .80 .94 1.00

63�F(17�C)

1925 910 59.0 17.3 3.85 .77 .90 1.00 56.5 16.6 4.35 .78 .92 1.00 53.0 15.5 4.91 .80 .95 1.00 49.5 14.5 5.54 .82 .98 1.00(17�C)

2165 1020 61.0 17.9 3.86 .79 .93 1.00 58.0 17.0 4.36 .81 .96 1.00 54.5 16.0 4.92 .83 .98 1.00 51.0 14.9 5.53 .85 1.00 1.00

67�F1710 805 61.0 17.9 3.86 .60 .72 .83 58.0 17.0 4.36 .61 .73 .86 54.5 16.0 4.90 .62 .75 .88 51.0 14.9 5.54 .63 .77 .91

67�F(19�C)

1925 910 62.5 18.3 3.86 .62 .74 .86 59.5 17.4 4.35 .63 .76 .88 56.0 16.4 4.92 .64 .78 .91 52.5 15.4 5.56 .65 .80 .94(19�C)

2165 1020 64.0 18.8 3.85 .63 .77 .90 61.0 17.9 4.38 .64 .78 .92 57.5 16.9 4.94 .65 .80 .95 54.0 15.8 5.57 .67 .83 .98

71�F1710 805 64.5 18.9 3.87 .47 .58 .69 61.5 18.0 4.40 .48 .59 .71 58.0 17.0 4.95 .48 .60 .73 54.5 16.0 5.55 .49 .62 .74

71�F(22�C)

1925 910 66.0 19.3 3.90 .48 .60 .72 63.0 18.5 4.40 .48 .61 .73 59.5 17.4 4.94 .49 .62 .75 55.5 16.3 5.58 .50 .64 .77(22�C)

2165 1020 68.0 19.9 3.91 .49 .62 .74 64.5 18.9 4.39 .49 .63 .76 61.0 17.9 4.96 .50 .64 .78 56.5 16.6 5.59 .51 .66 .80

Page 108: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 5 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 108

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−49C−6F + G60UHV−60C−090][C33−49C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1135 535 42.5 12.5 2.27 .73 .85 .97 41.0 12.0 2.63 .74 .87 .99 39.0 11.4 3.08 .76 .89 1.00 36.8 10.8 3.61 .78 .92 1.00

63�F(17�C)

1280 605 44.0 12.9 2.24 .75 .88 1.00 42.0 12.3 2.62 .77 .90 1.00 40.0 11.7 3.06 .78 .93 1.00 37.8 11.1 3.59 .80 .95 1.00(17�C)

1445 680 45.5 13.3 2.23 .78 .92 1.00 43.5 12.7 2.61 .79 .94 1.00 41.5 12.2 3.03 .81 .96 1.00 39.0 11.4 3.58 .83 .99 1.00

67�F1135 535 45.0 13.2 2.23 .59 .71 .82 43.5 12.7 2.61 .60 .72 .84 41.5 12.2 3.04 .60 .73 .86 39.0 11.4 3.55 .61 .75 .88

67�F(19�C)

1280 605 46.5 13.6 2.20 .60 .73 .85 44.5 13.0 2.58 .61 .74 .87 42.5 12.5 3.02 .62 .76 .89 40.5 11.9 3.54 .63 .78 .92(19�C)

1445 680 48.0 14.1 2.20 .62 .75 .88 46.0 13.5 2.58 .63 .77 .90 44.0 12.9 3.01 .64 .78 .93 41.5 12.2 3.50 .65 .81 .96

71�F1135 535 48.0 14.1 2.22 .46 .57 .68 46.0 13.5 2.58 .46 .58 .69 43.5 12.7 3.02 .46 .59 .71 41.5 12.2 3.51 .47 .60 .72

71�F(22�C)

1280 605 49.0 14.4 2.19 .46 .59 .70 47.0 13.8 2.54 .47 .59 .71 45.0 13.2 2.98 .47 .60 .73 42.5 12.5 3.49 .48 .62 .75(22�C)

1445 680 50.5 14.8 2.18 .47 .60 .73 48.5 14.2 2.55 .48 .61 .74 46.0 13.5 2.97 .48 .62 .76 44.0 12.9 3.45 .49 .64 .78

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−49C−6F + G60UHV−60C−090][C33−49C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1635 770 58.5 17.1 3.84 .74 .86 .98 55.5 16.3 4.31 .75 .88 1.00 52.5 15.4 4.90 .77 .90 1.00 49.0 14.4 5.53 .79 .93 1.00

63�F(17�C)

1855 875 60.0 17.6 3.85 .76 .89 1.00 57.5 16.9 4.36 .78 .91 1.00 54.0 15.8 4.92 .79 .94 1.00 50.5 14.8 5.52 .82 .97 1.00(17�C)

2070 975 62.0 18.2 3.84 .78 .92 1.00 58.5 17.1 4.37 .80 .95 1.00 55.5 16.3 4.93 .82 .97 1.00 52.0 15.2 5.55 .85 1.00 1.00

67�F1635 770 61.5 18.0 3.87 .60 .71 .83 58.5 17.1 4.37 .61 .73 .84 55.5 16.3 4.92 .61 .74 .87 52.0 15.2 5.55 .63 .76 .90

67�F(19�C)

1855 875 63.5 18.6 3.87 .61 .74 .86 60.5 17.7 4.37 .62 .75 .88 57.5 16.9 4.94 .63 .77 .90 53.5 15.7 5.57 .65 .79 .94(19�C)

2070 975 65.0 19.0 3.89 .62 .76 .89 62.0 18.2 4.40 .64 .78 .91 58.5 17.1 4.96 .65 .80 .94 55.0 16.1 5.55 .67 .82 .97

71�F1635 770 65.0 19.0 3.88 .46 .58 .69 62.0 18.2 4.39 .47 .59 .70 58.5 17.1 4.95 .47 .60 .72 55.0 16.1 5.57 .48 .61 .74

71�F(22�C)

1855 875 67.0 19.6 3.89 .48 .60 .71 63.5 18.6 4.41 .48 .61 .73 60.5 17.7 4.92 .49 .62 .74 56.5 16.6 5.59 .49 .63 .77(22�C)

2070 975 68.0 19.9 3.90 .48 .61 .73 65.0 19.0 4.38 .49 .62 .75 61.5 18.0 4.97 .49 .64 .77 58.0 17.0 5.61 .50 .65 .79

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−49C−6F + G61MPV−60C−090][C33−49C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1185 560 43.5 12.7 2.24 .74 .86 .98 41.5 12.2 2.63 .75 .88 1.00 39.5 11.6 3.07 .77 .90 1.00 37.2 10.9 3.60 .79 .93 1.00

63�F(17�C)

1355 640 44.5 13.0 2.23 .76 .90 1.00 43.0 12.6 2.61 .78 .92 1.00 40.5 11.9 3.06 .80 .95 1.00 38.5 11.3 3.56 .82 .97 1.00(17�C)

1545 730 46.0 13.5 2.20 .79 .94 1.00 44.0 12.9 2.59 .81 .96 1.00 42.0 12.3 3.03 .83 .99 1.00 39.5 11.6 3.54 .85 1.00 1.00

67�F1185 560 45.5 13.3 2.23 .60 .72 .83 44.0 12.9 2.58 .60 .73 .85 42.0 12.3 3.03 .61 .74 .87 39.5 11.6 3.55 .62 .76 .89

67�F(19�C)

1355 640 47.5 13.9 2.20 .61 .74 .86 45.5 13.3 2.58 .62 .75 .88 43.0 12.6 3.02 .63 .77 .91 41.0 12.0 3.53 .64 .79 .94(19�C)

1545 730 48.5 14.2 2.20 .63 .77 .90 46.5 13.6 2.57 .64 .78 .92 44.5 13.0 2.99 .65 .80 .95 42.0 12.3 3.51 .66 .82 .98

71�F1185 560 48.5 14.2 2.20 .46 .58 .69 46.5 13.6 2.57 .46 .59 .70 44.0 12.9 2.98 .47 .59 .72 42.0 12.3 3.50 .47 .61 .73

71�F(22�C)

1355 640 50.0 14.7 2.17 .47 .60 .71 48.0 14.1 2.55 .47 .60 .73 45.5 13.3 2.97 .48 .61 .74 43.0 12.6 3.48 .48 .63 .76(22�C)

1545 730 51.5 15.1 2.18 .48 .61 .74 49.0 14.4 2.54 .48 .62 .76 47.0 13.8 2.96 .49 .64 .78 44.5 13.0 3.46 .50 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−49C−6F + G61MPV−60C−090][C33−49C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1710 805 59.0 17.3 3.85 .75 .87 .99 56.0 16.4 4.34 .76 .89 1.00 53.0 15.5 4.91 .78 .92 1.00 49.5 14.5 5.54 .80 .95 1.00

63�F(17�C)

1925 910 61.0 17.9 3.86 .77 .90 1.00 58.0 17.0 4.36 .79 .93 1.00 54.5 16.0 4.93 .81 .95 1.00 51.0 14.9 5.53 .83 .99 1.00(17�C)

2165 1020 62.5 18.3 3.85 .80 .94 1.00 59.5 17.4 4.38 .81 .96 1.00 56.0 16.4 4.91 .84 .99 1.00 52.5 15.4 5.52 .86 1.00 1.00

67�F1710 805 62.5 18.3 3.85 .60 .72 .84 59.5 17.4 4.35 .61 .74 .86 56.0 16.4 4.93 .62 .75 .88 52.5 15.4 5.56 .64 .78 .91

67�F(19�C)

1925 910 64.0 18.8 3.85 .62 .74 .87 61.0 17.9 4.38 .63 .76 .89 58.0 17.0 4.95 .64 .78 .92 54.0 15.8 5.58 .66 .80 .95(19�C)

2165 1020 66.0 19.3 3.89 .64 .77 .90 62.5 18.3 4.41 .65 .79 .93 59.0 17.3 4.96 .66 .81 .96 55.5 16.3 5.57 .68 .84 .99

71�F1710 805 66.0 19.3 3.89 .47 .59 .70 62.5 18.3 4.39 .47 .60 .71 59.0 17.3 4.93 .48 .61 .73 55.5 16.3 5.58 .49 .62 .75

71�F(22�C)

1925 910 67.0 19.6 3.90 .48 .60 .72 64.5 18.9 4.39 .49 .61 .74 61.0 17.9 4.96 .49 .63 .75 57.0 16.7 5.60 .50 .64 .78(22�C)

2165 1020 69.0 20.2 3.90 .49 .62 .75 66.0 19.3 4.42 .49 .63 .76 62.5 18.3 4.98 .50 .65 .79 58.5 17.1 5.62 .51 .66 .81

Page 109: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 5 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 109

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−50/60C−6F + G60UHV−60C−090][C33−50/50C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1135 535 42.5 12.5 2.26 .74 .86 .98 41.0 12.0 2.62 .74 .87 .99 39.0 11.4 3.08 .76 .90 1.00 36.8 10.8 3.61 .78 .92 1.00

63�F(17�C)

1280 605 44.0 12.9 2.22 .75 .89 1.00 42.0 12.3 2.62 .77 .91 1.00 40.0 11.7 3.07 .79 .93 1.00 37.8 11.1 3.59 .81 .96 1.00(17�C)

1445 680 45.0 13.2 2.23 .78 .92 1.00 43.5 12.7 2.61 .79 .94 1.00 41.0 12.0 3.03 .81 .97 1.00 39.0 11.4 3.56 .83 .99 1.00

67�F1135 535 45.5 13.3 2.23 .59 .71 .82 43.5 12.7 2.62 .60 .72 .84 41.5 12.2 3.02 .60 .73 .86 39.0 11.4 3.56 .62 .75 .88

67�F(19�C)

1280 605 47.0 13.8 2.23 .60 .73 .85 45.0 13.2 2.59 .61 .74 .87 42.5 12.5 3.02 .62 .76 .90 40.0 11.7 3.54 .63 .78 .92(19�C)

1445 680 48.0 14.1 2.20 .62 .75 .89 46.0 13.5 2.58 .63 .77 .91 43.5 12.7 3.01 .64 .78 .93 41.0 12.0 3.50 .65 .80 .96

71�F1135 535 48.0 14.1 2.19 .46 .57 .68 46.0 13.5 2.58 .46 .58 .70 44.0 12.9 2.99 .46 .59 .71 41.5 12.2 3.49 .47 .60 .73

71�F(22�C)

1280 605 49.5 14.5 2.20 .46 .59 .71 47.5 13.9 2.55 .46 .59 .71 45.5 13.3 2.96 .47 .60 .73 43.0 12.6 3.49 .48 .62 .75(22�C)

1445 680 51.0 14.9 2.17 .47 .60 .73 49.0 14.4 2.55 .48 .61 .74 46.5 13.6 2.97 .48 .62 .76 44.0 12.9 3.45 .49 .64 .78

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−50/60C−6F + G60UHV−60C−090][C33−50/50C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1635 770 58.0 17.0 3.83 .74 .86 .98 55.0 16.1 4.35 .75 .88 1.00 52.0 15.2 4.89 .77 .91 1.00 48.5 14.2 5.53 .79 .94 1.00

63�F(17�C)

1855 875 59.5 17.4 3.85 .76 .89 1.00 56.5 16.6 4.35 .78 .92 1.00 53.5 15.7 4.91 .80 .94 1.00 50.0 14.7 5.54 .82 .97 1.00(17�C)

2070 975 61.0 17.9 3.87 .78 .93 1.00 58.0 17.0 4.37 .80 .95 1.00 54.5 16.0 4.92 .82 .98 1.00 51.0 14.9 5.53 .85 1.00 1.00

67�F1635 770 61.5 18.0 3.86 .60 .71 .83 58.5 17.1 4.36 .60 .73 .85 55.0 16.1 4.90 .62 .74 .87 51.5 15.1 5.54 .63 .76 .90

67�F(19�C)

1855 875 63.0 18.5 3.86 .61 .74 .86 60.0 17.6 4.35 .62 .75 .88 56.5 16.6 4.93 .63 .77 .91 53.0 15.5 5.56 .65 .79 .94(19�C)

2070 975 64.5 18.9 3.88 .63 .76 .89 61.5 18.0 4.39 .64 .78 .92 58.0 17.0 4.94 .65 .80 .94 54.0 15.8 5.57 .67 .82 .97

71�F1635 770 65.0 19.0 3.88 .47 .58 .69 62.0 18.2 4.38 .47 .59 .70 58.5 17.1 4.96 .48 .60 .72 54.5 16.0 5.55 .48 .61 .74

71�F(22�C)

1855 875 67.0 19.6 3.89 .48 .59 .71 63.5 18.6 4.41 .48 .61 .73 60.0 17.6 4.94 .48 .62 .75 56.0 16.4 5.58 .49 .63 .77(22�C)

2070 975 68.0 19.9 3.92 .48 .61 .74 65.0 19.0 4.39 .49 .62 .75 61.0 17.9 4.96 .49 .63 .77 57.0 16.7 5.59 .50 .65 .79

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−50/60C−6F + G61MPV−60C−090][C33−50/50C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1185 560 43.0 12.6 2.26 .74 .87 .99 41.5 12.2 2.63 .75 .88 1.00 39.5 11.6 3.07 .77 .91 1.00 37.0 10.8 3.60 .79 .94 1.00

63�F(17�C)

1355 640 44.5 13.0 2.23 .77 .91 1.00 42.5 12.5 2.62 .78 .93 1.00 40.5 11.9 3.06 .80 .95 1.00 38.5 11.3 3.56 .82 .98 1.00(17�C)

1545 730 46.0 13.5 2.22 .80 .94 1.00 44.0 12.9 2.59 .81 .96 1.00 41.5 12.2 3.03 .83 .99 1.00 39.5 11.6 3.53 .86 1.00 1.00

67�F1185 560 46.0 13.5 2.23 .59 .72 .83 44.0 12.9 2.62 .60 .73 .85 42.0 12.3 3.03 .61 .74 .87 39.5 11.6 3.55 .62 .76 .90

67�F(19�C)

1355 640 47.5 13.9 2.19 .61 .74 .87 45.5 13.3 2.58 .62 .76 .89 43.0 12.6 3.02 .63 .77 .91 40.5 11.9 3.53 .64 .79 .94(19�C)

1545 730 48.5 14.2 2.20 .63 .77 .91 46.5 13.6 2.57 .64 .79 .93 44.0 12.9 2.98 .65 .80 .95 41.5 12.2 3.50 .66 .83 .98

71�F1185 560 48.5 14.2 2.20 .46 .58 .69 46.5 13.6 2.58 .46 .58 .70 44.5 13.0 2.98 .47 .59 .71 42.0 12.3 3.50 .47 .61 .74

71�F(22�C)

1355 640 50.5 14.8 2.17 .47 .59 .72 48.0 14.1 2.54 .47 .60 .73 46.0 13.5 2.98 .48 .62 .75 43.5 12.7 3.48 .48 .63 .77(22�C)

1545 730 51.5 15.1 2.17 .47 .61 .74 49.5 14.5 2.54 .48 .62 .76 47.0 13.8 2.96 .49 .64 .78 44.5 13.0 3.46 .50 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−50/60C−6F + G61MPV−60C−090][C33−50/50C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1710 805 58.5 17.1 3.84 .75 .87 .99 55.5 16.3 4.32 .76 .90 1.00 52.5 15.4 4.90 .78 .92 1.00 49.0 14.4 5.53 .80 .95 1.00

63�F(17�C)

1925 910 60.0 17.6 3.85 .77 .91 1.00 57.0 16.7 4.36 .79 .93 1.00 54.0 15.8 4.92 .81 .96 1.00 50.5 14.8 5.51 .83 .99 1.00(17�C)

2165 1020 62.0 18.2 3.85 .80 .94 1.00 58.5 17.1 4.37 .82 .97 1.00 55.5 16.3 4.92 .84 .99 1.00 51.5 15.1 5.55 .86 1.00 1.00

67�F1710 805 62.0 18.2 3.88 .60 .72 .84 59.0 17.3 4.37 .61 .74 .86 55.5 16.3 4.92 .62 .75 .88 52.0 15.2 5.55 .63 .78 .92

67�F(19�C)

1925 910 63.5 18.6 3.87 .62 .75 .87 60.5 17.7 4.37 .63 .76 .89 57.0 16.7 4.94 .64 .78 .92 53.5 15.7 5.56 .65 .81 .95(19�C)

2165 1020 65.0 19.0 3.88 .63 .77 .91 62.0 18.2 4.39 .65 .79 .93 58.5 17.1 4.95 .66 .81 .96 55.0 16.1 5.55 .68 .84 .99

71�F1710 805 66.0 19.3 3.89 .47 .59 .70 62.5 18.3 4.40 .48 .60 .71 59.0 17.3 4.97 .48 .61 .73 55.5 16.3 5.54 .49 .62 .75

71�F(22�C)

1925 910 67.0 19.6 3.90 .48 .60 .72 64.0 18.8 4.42 .49 .61 .74 60.5 17.7 4.93 .49 .63 .76 56.5 16.6 5.59 .50 .64 .78(22�C)

2165 1020 69.0 20.2 3.91 .49 .62 .75 66.0 19.3 4.39 .50 .63 .76 61.5 18.0 4.97 .50 .65 .79 57.5 16.9 5.60 .51 .66 .81

Page 110: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 5 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 110

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−60D−6F + G60UHV−60D−135][C33−60D + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1185 560 44.0 12.9 2.23 .74 .87 .99 42.0 12.3 2.62 .76 .89 1.00 40.0 11.7 3.06 .78 .92 1.00 37.6 11.0 3.59 .80 .95 1.00

63�F(17�C)

1330 630 45.0 13.2 2.23 .76 .90 1.00 43.0 12.6 2.61 .78 .93 1.00 41.0 12.0 3.03 .80 .95 1.00 38.5 11.3 3.56 .82 .98 1.00(17�C)

1495 705 46.5 13.6 2.20 .80 .94 1.00 44.0 12.9 2.59 .81 .97 1.00 42.0 12.3 3.03 .83 .99 1.00 40.0 11.7 3.54 .85 1.00 1.00

67�F1185 560 46.5 13.6 2.23 .59 .72 .84 44.5 13.0 2.57 .60 .73 .86 42.5 12.5 3.02 .61 .75 .88 40.0 11.7 3.54 .63 .77 .91

67�F(19�C)

1330 630 47.5 13.9 2.20 .61 .74 .87 45.5 13.3 2.57 .62 .75 .89 43.5 12.7 3.01 .63 .78 .92 41.0 12.0 3.50 .64 .80 .95(19�C)

1495 705 49.0 14.4 2.19 .63 .77 .91 47.0 13.8 2.54 .64 .79 .93 44.5 13.0 2.98 .65 .81 .96 42.0 12.3 3.50 .66 .83 .99

71�F1185 560 49.5 14.5 2.19 .46 .58 .69 47.5 13.9 2.55 .46 .58 .71 45.0 13.2 2.97 .46 .60 .72 42.5 12.5 3.49 .47 .61 .74

71�F(22�C)

1330 630 51.0 14.9 2.17 .46 .59 .71 48.5 14.2 2.55 .47 .60 .73 46.5 13.6 2.97 .47 .62 .75 44.0 12.9 3.45 .48 .63 .77(22�C)

1495 705 52.0 15.2 2.18 .47 .61 .74 50.0 14.7 2.54 .48 .62 .76 47.5 13.9 2.94 .48 .63 .78 44.5 13.0 3.46 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−60D−6F + G60UHV−60D−135][C33−60D + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1690 800 59.5 17.4 3.85 .75 .88 1.00 56.5 16.6 4.34 .77 .90 1.00 53.5 15.7 4.91 .79 .93 1.00 50.0 14.7 5.54 .81 .96 1.00

63�F(17�C)

1900 895 61.0 17.9 3.87 .78 .92 1.00 58.0 17.0 4.37 .79 .94 1.00 55.0 16.1 4.92 .81 .97 1.00 51.0 14.9 5.53 .84 .99 1.00(17�C)

2135 1010 63.0 18.5 3.86 .80 .95 1.00 59.5 17.4 4.38 .82 .98 1.00 56.5 16.6 4.90 .85 1.00 1.00 53.0 15.5 5.52 .87 1.00 1.00

67�F1690 800 63.0 18.5 3.86 .61 .73 .85 60.0 17.6 4.35 .61 .74 .87 56.5 16.6 4.93 .62 .76 .89 53.0 15.5 5.56 .64 .78 .92

67�F(19�C)

1900 895 64.5 18.9 3.88 .62 .75 .88 61.5 18.0 4.38 .63 .77 .90 58.0 17.0 4.95 .64 .79 .93 54.5 16.0 5.57 .65 .81 .96(19�C)

2135 1010 66.0 19.3 3.89 .64 .78 .92 63.0 18.5 4.41 .65 .80 .94 59.5 17.4 4.96 .66 .82 .97 55.5 16.3 5.57 .68 .85 1.00

71�F1690 800 67.0 19.6 3.89 .47 .59 .70 63.5 18.6 4.40 .47 .60 .72 60.0 17.6 4.94 .48 .61 .74 56.0 16.4 5.58 .48 .62 .75

71�F(22�C)

1900 895 68.0 19.9 3.92 .48 .61 .73 65.0 19.0 4.39 .48 .61 .74 61.5 18.0 4.96 .48 .62 .76 57.0 16.7 5.59 .49 .64 .79(22�C)

2135 1010 70.0 20.5 3.90 .48 .62 .75 66.0 19.3 4.42 .49 .63 .77 62.5 18.3 4.98 .50 .65 .79 58.5 17.1 5.60 .51 .66 .82

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−60D−6F + G61MPV−60D−135][C33−60D + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1240 585 44.5 13.0 2.23 .75 .89 1.00 42.5 12.5 2.61 .76 .91 1.00 40.5 11.9 3.06 .79 .93 1.00 38.0 11.1 3.59 .81 .96 1.00

63�F(17�C)

1390 655 45.5 13.3 2.22 .78 .92 1.00 43.5 12.7 2.61 .80 .94 1.00 41.5 12.2 3.03 .81 .97 1.00 39.0 11.4 3.57 .84 1.00 1.00(17�C)

1545 730 46.5 13.6 2.21 .80 .95 1.00 44.5 13.0 2.59 .82 .98 1.00 42.5 12.5 3.03 .84 1.00 1.00 40.0 11.7 3.53 .87 1.00 1.00

67�F1240 585 47.0 13.8 2.20 .60 .73 .85 45.0 13.2 2.58 .61 .74 .87 43.0 12.6 3.02 .62 .76 .89 40.5 11.9 3.53 .63 .78 .92

67�F(19�C)

1390 655 48.0 14.1 2.20 .62 .75 .88 46.0 13.5 2.57 .63 .77 .91 44.0 12.9 2.98 .64 .79 .93 41.5 12.2 3.50 .65 .81 .96(19�C)

1545 730 49.5 14.5 2.19 .63 .78 .92 47.5 13.9 2.55 .64 .80 .94 45.0 13.2 2.99 .65 .82 .97 42.5 12.5 3.47 .67 .84 .99

71�F1240 585 50.0 14.7 2.19 .46 .58 .70 48.0 14.1 2.54 .47 .59 .72 45.5 13.3 2.98 .47 .61 .73 43.0 12.6 3.49 .47 .62 .75

71�F(22�C)

1390 655 51.5 15.1 2.16 .47 .60 .73 49.0 14.4 2.55 .47 .61 .74 47.0 13.8 2.97 .48 .62 .76 44.0 12.9 3.45 .49 .64 .78(22�C)

1545 730 52.5 15.4 2.18 .48 .62 .75 50.0 14.7 2.54 .48 .63 .77 48.0 14.1 2.94 .49 .64 .79 45.0 13.2 3.46 .49 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−60D−6F + G61MPV−60D−135][C33−60D + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1780 840 60.5 17.7 3.85 .76 .90 1.00 57.5 16.9 4.36 .78 .92 1.00 54.0 15.8 4.92 .80 .95 1.00 50.5 14.8 5.54 .82 .98 1.00

63�F(17�C)

1985 935 62.0 18.2 3.86 .79 .93 1.00 58.5 17.1 4.37 .80 .95 1.00 55.5 16.3 4.93 .82 .98 1.00 51.5 15.1 5.54 .85 1.00 1.00(17�C)

2190 1035 63.5 18.6 3.86 .81 .96 1.00 60.0 17.6 4.38 .83 .99 1.00 56.5 16.6 4.91 .85 1.00 1.00 53.5 15.7 5.55 .88 1.00 1.00

67�F1780 840 63.5 18.6 3.87 .61 .74 .86 60.5 17.7 4.37 .62 .75 .88 57.5 16.9 4.94 .63 .77 .91 53.5 15.7 5.57 .65 .80 .94

67�F(19�C)

1985 935 65.0 19.0 3.89 .62 .76 .89 62.0 18.2 4.40 .64 .78 .92 58.5 17.1 4.95 .65 .80 .95 55.0 16.1 5.58 .66 .83 .98(19�C)

2190 1035 67.0 19.6 3.90 .64 .79 .93 63.5 18.6 4.41 .65 .81 .95 60.0 17.6 4.96 .67 .83 .98 56.0 16.4 5.57 .68 .86 1.00

71�F1780 840 67.0 19.6 3.91 .47 .60 .72 64.0 18.8 4.41 .48 .60 .73 60.5 17.7 4.96 .48 .61 .75 56.5 16.6 5.59 .49 .63 .77

71�F(22�C)

1985 935 69.0 20.2 3.91 .48 .61 .74 66.0 19.3 4.41 .48 .62 .75 62.0 18.2 4.97 .49 .64 .78 57.5 16.9 5.60 .50 .65 .80(22�C)

2190 1035 70.0 20.5 3.92 .49 .63 .76 67.0 19.6 4.42 .49 .64 .78 63.0 18.5 4.98 .50 .65 .80 59.0 17.3 5.61 .51 .67 .83

Page 111: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 5 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 111

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−62C−6F + G60UHV−60C−090][C33−62C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1135 535 44.0 12.9 2.23 .74 .87 .99 42.0 12.3 2.61 .76 .89 1.00 40.0 11.7 3.06 .77 .91 1.00 38.0 11.1 3.59 .79 .94 1.00

63�F(17�C)

1280 605 45.5 13.3 2.22 .77 .91 1.00 43.5 12.7 2.61 .78 .93 1.00 41.5 12.2 3.02 .80 .95 1.00 39.0 11.4 3.57 .82 .99 1.00(17�C)

1445 680 47.0 13.8 2.22 .80 .95 1.00 45.0 13.2 2.58 .82 .97 1.00 42.5 12.5 3.00 .83 .99 1.00 40.5 11.9 3.52 .86 1.00 1.00

67�F1135 535 47.0 13.8 2.20 .59 .71 .84 45.0 13.2 2.58 .60 .73 .85 43.0 12.6 3.02 .61 .75 .88 40.5 11.9 3.54 .62 .77 .91

67�F(19�C)

1280 605 48.5 14.2 2.20 .61 .74 .87 46.5 13.6 2.57 .62 .76 .89 44.0 12.9 3.00 .63 .78 .92 41.5 12.2 3.50 .64 .80 .95(19�C)

1445 680 50.0 14.7 2.19 .63 .77 .91 47.5 13.9 2.54 .64 .79 .94 45.0 13.2 3.00 .65 .81 .96 42.5 12.5 3.48 .66 .83 .99

71�F1135 535 50.0 14.7 2.19 .46 .57 .69 48.0 14.1 2.54 .46 .58 .70 45.5 13.3 2.98 .47 .59 .72 43.0 12.6 3.49 .47 .61 .74

71�F(22�C)

1280 605 51.5 15.1 2.17 .47 .59 .72 49.0 14.4 2.55 .47 .60 .73 47.0 13.8 2.97 .47 .61 .75 44.0 12.9 3.45 .48 .63 .77(22�C)

1445 680 53.0 15.5 2.17 .47 .61 .75 50.5 14.8 2.53 .48 .62 .76 48.0 14.1 2.94 .48 .64 .78 45.5 13.3 3.46 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−62C−6F + G60UHV−60C−090][C33−62C + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1635 770 60.5 17.7 3.85 .75 .89 1.00 57.5 16.9 4.36 .77 .91 1.00 54.5 16.0 4.92 .79 .94 1.00 50.5 14.8 5.54 .82 .97 1.00

63�F(17�C)

1855 875 62.5 18.3 3.87 .79 .93 1.00 59.0 17.3 4.38 .80 .95 1.00 56.0 16.4 4.93 .82 .98 1.00 52.0 15.2 5.53 .85 1.00 1.00(17�C)

2070 975 64.0 18.8 3.86 .81 .96 1.00 60.5 17.7 4.38 .83 .99 1.00 57.5 16.9 4.94 .86 1.00 1.00 54.0 15.8 5.56 .89 1.00 1.00

67�F1635 770 64.0 18.8 3.88 .60 .73 .85 61.0 17.9 4.38 .61 .74 .87 57.5 16.9 4.94 .63 .76 .90 54.0 15.8 5.57 .64 .79 .93

67�F(19�C)

1855 875 66.0 19.3 3.89 .62 .76 .89 62.5 18.3 4.40 .63 .78 .91 59.0 17.3 4.95 .65 .80 .94 55.0 16.1 5.55 .66 .82 .98(19�C)

2070 975 68.0 19.9 3.90 .64 .79 .93 64.5 18.9 4.41 .65 .81 .95 60.5 17.7 4.97 .67 .83 .98 56.5 16.6 5.58 .69 .86 1.00

71�F1635 770 68.0 19.9 3.91 .47 .59 .71 64.5 18.9 4.39 .47 .60 .72 61.0 17.9 4.96 .48 .61 .74 57.0 16.7 5.60 .48 .62 .76

71�F(22�C)

1855 875 70.0 20.5 3.91 .47 .61 .73 66.0 19.3 4.42 .48 .62 .75 62.5 18.3 4.99 .49 .63 .77 58.5 17.1 5.61 .50 .65 .80(22�C)

2070 975 72.0 21.1 3.94 .49 .63 .76 68.0 19.9 4.44 .49 .64 .78 64.0 18.8 4.99 .50 .66 .81 60.0 17.6 5.59 .51 .67 .83

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−62C−6F + G61MPV−60C−090][C33−62C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1185 560 44.5 13.0 2.23 .75 .89 1.00 43.0 12.6 2.61 .77 .91 1.00 40.5 11.9 3.06 .78 .93 1.00 38.5 11.3 3.56 .80 .96 1.00

63�F(17�C)

1355 640 46.5 13.6 2.20 .78 .93 1.00 44.0 12.9 2.60 .80 .95 1.00 42.0 12.3 3.03 .81 .98 1.00 39.5 11.6 3.54 .84 1.00 1.00(17�C)

1545 730 47.5 13.9 2.20 .82 .98 1.00 45.5 13.3 2.59 .84 .99 1.00 43.5 12.7 3.00 .86 1.00 1.00 41.5 12.2 3.51 .88 1.00 1.00

67�F1185 560 47.5 13.9 2.19 .60 .72 .85 45.5 13.3 2.58 .61 .74 .87 43.5 12.7 3.01 .62 .76 .89 41.0 12.0 3.53 .63 .78 .92

67�F(19�C)

1355 640 49.0 14.4 2.19 .62 .76 .89 47.0 13.8 2.57 .63 .77 .92 44.5 13.0 2.98 .64 .79 .94 42.0 12.3 3.50 .66 .82 .97(19�C)

1545 730 50.5 14.8 2.17 .64 .79 .94 48.5 14.2 2.55 .65 .81 .96 46.0 13.5 2.95 .66 .83 .99 43.0 12.6 3.47 .68 .86 1.00

71�F1185 560 50.5 14.8 2.17 .46 .58 .70 48.5 14.2 2.55 .47 .59 .71 46.0 13.5 2.98 .47 .60 .73 43.5 12.7 3.48 .47 .61 .75

71�F(22�C)

1355 640 52.0 15.2 2.18 .47 .61 .73 50.0 14.7 2.54 .48 .61 .75 47.5 13.9 2.93 .48 .62 .76 45.0 13.2 3.45 .49 .63 .78(22�C)

1545 730 53.5 15.7 2.17 .48 .63 .77 51.5 15.1 2.50 .49 .64 .78 49.0 14.4 2.94 .49 .65 .81 46.0 13.5 3.41 .50 .67 .83

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−62C−6F + G61MPV−60C−090][C33−62C + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1710 805 61.0 17.9 3.87 .77 .90 1.00 58.0 17.0 4.36 .78 .93 1.00 55.0 16.1 4.92 .80 .95 1.00 51.5 15.1 5.52 .83 .98 1.00

63�F(17�C)

1925 910 63.0 18.5 3.87 .80 .94 1.00 60.0 17.6 4.38 .81 .97 1.00 56.5 16.6 4.91 .84 .99 1.00 53.0 15.5 5.55 .86 1.00 1.00(17�C)

2165 1020 65.0 19.0 3.86 .83 .98 1.00 61.5 18.0 4.38 .85 1.00 1.00 58.5 17.1 4.94 .87 1.00 1.00 55.0 16.1 5.58 .91 1.00 1.00

67�F1710 805 65.0 19.0 3.86 .61 .74 .87 61.5 18.0 4.39 .62 .76 .89 58.0 17.0 4.95 .63 .78 .92 54.5 16.0 5.57 .65 .80 .95

67�F(19�C)

1925 910 67.0 19.6 3.89 .63 .77 .91 63.0 18.5 4.41 .64 .79 .93 60.0 17.6 4.96 .66 .81 .96 56.0 16.4 5.56 .67 .84 .99(19�C)

2165 1020 68.0 19.9 3.91 .65 .80 .95 65.0 19.0 4.41 .66 .82 .97 61.5 18.0 4.94 .68 .85 1.00 57.0 16.7 5.60 .70 .88 1.00

71�F1710 805 69.0 20.2 3.90 .47 .59 .72 65.0 19.0 4.40 .48 .60 .73 61.5 18.0 4.98 .48 .62 .75 57.5 16.9 5.60 .49 .63 .78

71�F(22�C)

1925 910 70.0 20.5 3.91 .48 .61 .74 67.0 19.6 4.43 .49 .63 .76 63.0 18.5 4.98 .50 .64 .79 59.0 17.3 5.61 .50 .66 .81(22�C)

2165 1020 72.0 21.1 3.94 .50 .64 .78 69.0 20.2 4.44 .50 .65 .80 64.5 18.9 4.97 .51 .67 .82 60.5 17.7 5.60 .52 .69 .85

Page 112: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CX34/C33 coils].

RATINGS 5 TON

UP−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 112

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−62D−6F + G60UHV−60D−135][C33−62D + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1185 560 44.0 12.9 2.23 .75 .87 .99 42.0 12.3 2.62 .76 .89 1.00 40.0 11.7 3.06 .77 .92 1.00 37.8 11.1 3.58 .79 .94 1.00

63�F(17�C)

1330 630 45.5 13.3 2.22 .77 .91 1.00 43.5 12.7 2.61 .78 .93 1.00 41.5 12.2 3.03 .80 .95 1.00 39.0 11.4 3.57 .82 .98 1.00(17�C)

1495 705 46.5 13.6 2.21 .80 .94 1.00 44.5 13.0 2.58 .81 .97 1.00 42.5 12.5 3.03 .83 .99 1.00 40.0 11.7 3.52 .85 1.00 1.00

67�F1185 560 46.5 13.6 2.20 .59 .72 .84 45.0 13.2 2.58 .60 .73 .86 42.5 12.5 3.02 .61 .75 .88 40.5 11.9 3.53 .62 .77 .91

67�F(19�C)

1330 630 48.0 14.1 2.20 .60 .74 .87 46.0 13.5 2.57 .62 .75 .89 44.0 12.9 2.98 .63 .78 .92 41.5 12.2 3.50 .64 .80 .94(19�C)

1495 705 49.5 14.5 2.19 .63 .77 .91 47.5 13.9 2.55 .63 .79 .93 45.0 13.2 2.99 .65 .80 .96 42.5 12.5 3.49 .66 .83 .98

71�F1185 560 49.5 14.5 2.19 .46 .58 .69 47.5 13.9 2.54 .46 .58 .70 45.0 13.2 2.98 .47 .59 .72 43.0 12.6 3.49 .47 .61 .74

71�F(22�C)

1330 630 51.0 14.9 2.16 .47 .59 .72 49.0 14.4 2.55 .47 .60 .73 46.5 13.6 2.96 .47 .61 .75 44.0 12.9 3.45 .48 .63 .77(22�C)

1495 705 52.5 15.4 2.17 .47 .61 .74 50.0 14.7 2.53 .48 .62 .76 47.5 13.9 2.94 .48 .63 .78 45.0 13.2 3.46 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−62D−6F + G60UHV−60D−135][C33−62D + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1690 800 60.0 17.6 3.85 .75 .88 1.00 57.5 16.9 4.36 .77 .90 1.00 54.0 15.8 4.92 .79 .93 1.00 50.5 14.8 5.51 .81 .96 1.00

63�F(17�C)

1900 895 62.0 18.2 3.86 .77 .91 1.00 59.0 17.3 4.37 .79 .94 1.00 55.5 16.3 4.93 .81 .97 1.00 52.0 15.2 5.55 .84 1.00 1.00(17�C)

2135 1010 63.5 18.6 3.86 .80 .95 1.00 60.5 17.7 4.38 .82 .98 1.00 57.0 16.7 4.92 .84 1.00 1.00 53.5 15.7 5.56 .87 1.00 1.00

67�F1690 800 63.5 18.6 3.87 .61 .73 .85 60.5 17.7 4.37 .61 .74 .87 57.5 16.9 4.94 .62 .76 .89 54.0 15.8 5.57 .64 .78 .92

67�F(19�C)

1900 895 65.0 19.0 3.90 .61 .75 .88 62.5 18.3 4.40 .63 .77 .90 59.0 17.3 4.95 .64 .79 .93 55.0 16.1 5.55 .66 .81 .96(19�C)

2135 1010 67.0 19.6 3.90 .64 .78 .92 64.0 18.8 4.41 .65 .80 .94 60.5 17.7 4.97 .66 .82 .97 56.5 16.6 5.58 .68 .84 1.00

71�F1690 800 68.0 19.9 3.91 .47 .59 .70 64.0 18.8 4.42 .47 .60 .72 60.5 17.7 4.95 .48 .61 .73 56.5 16.6 5.59 .48 .62 .76

71�F(22�C)

1900 895 69.0 20.2 3.91 .47 .60 .73 66.0 19.3 4.41 .48 .61 .74 62.0 18.2 4.97 .49 .62 .76 58.0 17.0 5.61 .49 .64 .79(22�C)

2135 1010 71.0 20.8 3.92 .48 .62 .75 67.0 19.6 4.43 .49 .63 .77 63.5 18.6 4.99 .50 .65 .79 59.5 17.4 5.59 .50 .66 .82

FIRST STAGE COOLING CAPACITY − XC21−060 with [CX34−62D−6F + G61MPV−60D−135][C33−62D + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1240 585 44.5 13.0 2.23 .75 .88 1.00 42.5 12.5 2.61 .77 .91 1.00 40.5 11.9 3.05 .79 .93 1.00 38.5 11.3 3.56 .80 .96 1.00

63�F(17�C)

1390 655 46.0 13.5 2.22 .78 .92 1.00 44.0 12.9 2.59 .79 .94 1.00 42.0 12.3 3.02 .81 .97 1.00 39.5 11.6 3.53 .83 .99 1.00(17�C)

1545 730 47.0 13.8 2.21 .80 .95 1.00 45.0 13.2 2.58 .82 .98 1.00 42.5 12.5 2.99 .84 1.00 1.00 40.5 11.9 3.52 .87 1.00 1.00

67�F1240 585 47.5 13.9 2.21 .60 .73 .85 45.5 13.3 2.58 .60 .74 .87 43.0 12.6 3.01 .62 .76 .89 40.5 11.9 3.53 .63 .78 .92

67�F(19�C)

1390 655 48.5 14.2 2.19 .61 .75 .88 46.5 13.6 2.57 .63 .77 .91 44.5 13.0 2.98 .64 .79 .93 42.0 12.3 3.50 .65 .81 .96(19�C)

1545 730 50.0 14.7 2.17 .63 .78 .92 47.5 13.9 2.55 .64 .80 .94 45.5 13.3 2.99 .65 .81 .97 42.5 12.5 3.48 .67 .84 .99

71�F1240 585 50.0 14.7 2.19 .46 .58 .70 48.0 14.1 2.53 .46 .59 .72 46.0 13.5 2.97 .47 .61 .73 43.5 12.7 3.48 .47 .62 .75

71�F(22�C)

1390 655 51.5 15.1 2.17 .47 .59 .73 49.5 14.5 2.54 .47 .61 .74 47.0 13.8 2.96 .48 .62 .76 44.5 13.0 3.45 .48 .64 .78(22�C)

1545 730 52.5 15.4 2.17 .48 .62 .75 50.5 14.8 2.53 .48 .63 .77 48.0 14.1 2.94 .49 .64 .79 45.0 13.2 3.46 .49 .66 .81

SECOND STAGE COOLING CAPACITY − XC21−060 with [CX34−62D−6F + G61MPV−60D−135][C33−62D + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1780 840 61.0 17.9 3.86 .76 .89 1.00 58.0 17.0 4.36 .78 .92 1.00 55.0 16.1 4.92 .80 .95 1.00 51.0 14.9 5.53 .82 .98 1.00

63�F(17�C)

1985 935 62.5 18.3 3.85 .79 .93 1.00 59.5 17.4 4.37 .80 .95 1.00 56.5 16.6 4.90 .82 .98 1.00 52.5 15.4 5.54 .85 1.00 1.00(17�C)

2190 1035 64.0 18.8 3.86 .81 .96 1.00 61.0 17.9 4.38 .83 .98 1.00 57.5 16.9 4.91 .85 1.00 1.00 54.0 15.8 5.56 .88 1.00 1.00

67�F1780 840 64.5 18.9 3.88 .61 .74 .86 61.5 18.0 4.38 .62 .75 .88 58.0 17.0 4.95 .63 .77 .91 54.5 16.0 5.58 .65 .80 .94

67�F(19�C)

1985 935 66.0 19.3 3.89 .62 .76 .89 63.0 18.5 4.40 .64 .78 .92 59.5 17.4 4.96 .65 .80 .95 55.5 16.3 5.57 .67 .83 .98(19�C)

2190 1035 68.0 19.9 3.91 .64 .79 .93 64.5 18.9 4.42 .65 .81 .95 61.0 17.9 4.94 .67 .83 .98 57.0 16.7 5.59 .68 .86 1.00

71�F1780 840 68.0 19.9 3.92 .47 .60 .71 65.0 19.0 4.39 .47 .60 .73 61.5 18.0 4.96 .48 .61 .75 57.5 16.9 5.60 .49 .63 .77

71�F(22�C)

1985 935 70.0 20.5 3.91 .48 .61 .74 66.0 19.3 4.42 .48 .62 .75 62.5 18.3 4.98 .49 .64 .77 59.0 17.3 5.61 .50 .65 .80(22�C)

2190 1035 71.0 20.8 3.93 .49 .63 .76 68.0 19.9 4.43 .50 .64 .78 64.0 18.8 4.99 .50 .66 .80 60.0 17.6 5.60 .51 .67 .83

Page 113: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 5 TON

DOWN−FLOW INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 113

FIRST STAGE COOLING CAPACITY − XC21−060 with [CR26−48N/W−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 43.0 12.6 2.10 .76 .89 1.00 41.0 12.0 2.46 .77 .91 1.00 39.0 11.4 2.86 .79 .93 1.00 37.0 10.8 3.33 .81 .96 1.00

63�F(17�C)

1400 660 43.5 12.7 2.09 .77 .91 1.00 42.0 12.3 2.46 .79 .93 1.00 39.5 11.6 2.86 .80 .95 1.00 37.6 11.0 3.33 .82 .98 1.00(17�C)

1500 710 44.0 12.9 2.09 .79 .93 1.00 42.5 12.5 2.45 .80 .95 1.00 40.5 11.9 2.86 .82 .97 1.00 38.0 11.1 3.33 .84 .99 1.00

67�F1300 615 45.5 13.3 2.08 .61 .74 .86 44.0 12.9 2.44 .62 .75 .88 41.5 12.2 2.84 .63 .76 .90 39.5 11.6 3.31 .64 .78 .92

67�F(19�C)

1400 660 46.5 13.6 2.08 .62 .75 .88 44.5 13.0 2.44 .63 .76 .90 42.5 12.5 2.84 .64 .78 .92 40.0 11.7 3.30 .65 .80 .95(19�C)

1500 710 47.0 13.8 2.08 .63 .76 .90 45.0 13.2 2.43 .64 .78 .92 43.0 12.6 2.84 .65 .79 .94 40.5 11.9 3.30 .66 .82 .97

71�F1300 615 48.5 14.2 2.08 .47 .60 .71 46.5 13.6 2.42 .47 .61 .73 44.5 13.0 2.81 .48 .62 .74 42.0 12.3 3.27 .48 .63 .76

71�F(22�C)

1400 660 49.0 14.4 2.07 .48 .61 .73 47.0 13.8 2.41 .48 .62 .74 45.0 13.2 2.81 .48 .63 .76 42.5 12.5 3.27 .49 .64 .77(22�C)

1500 710 50.0 14.7 2.07 .48 .62 .74 47.5 13.9 2.41 .49 .63 .75 45.5 13.3 2.80 .49 .64 .77 43.0 12.6 3.27 .50 .65 .79

SECOND STAGE COOLING CAPACITY − XC21−060 with [CR26−48N/W−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1600 755 55.0 16.1 3.65 .74 .86 .97 52.5 15.4 4.10 .75 .87 .99 49.5 14.5 4.63 .77 .90 1.00 46.5 13.6 5.19 .79 .92 1.00

63�F(17�C)

1800 850 56.5 16.6 3.66 .76 .88 1.00 53.5 15.7 4.12 .77 .90 1.00 50.5 14.8 4.62 .79 .93 1.00 47.5 13.9 5.23 .81 .96 1.00(17�C)

2000 945 57.5 16.9 3.67 .78 .91 1.00 55.0 16.1 4.12 .79 .93 1.00 52.0 15.2 4.64 .81 .96 1.00 48.5 14.2 5.22 .83 .98 1.00

67�F1600 755 58.5 17.1 3.68 .60 .72 .83 55.5 16.3 4.14 .61 .73 .84 52.5 15.4 4.66 .62 .74 .86 49.5 14.5 5.23 .63 .76 .89

67�F(19�C)

1800 850 60.0 17.6 3.70 .61 .73 .85 57.0 16.7 4.15 .62 .75 .87 54.0 15.8 4.67 .63 .76 .89 50.5 14.8 5.25 .64 .78 .92(19�C)

2000 945 61.0 17.9 3.71 .63 .75 .88 58.0 17.0 4.18 .64 .77 .90 55.0 16.1 4.68 .65 .79 .92 51.5 15.1 5.27 .66 .81 .95

71�F1600 755 62.0 18.2 3.72 .46 .59 .69 59.0 17.3 4.18 .47 .59 .70 56.0 16.4 4.69 .48 .61 .72 52.5 15.4 5.28 .48 .61 .74

71�F(22�C)

1800 850 63.5 18.6 3.74 .47 .60 .71 60.5 17.7 4.20 .48 .61 .72 57.0 16.7 4.72 .48 .62 .74 53.5 15.7 5.31 .49 .63 .76(22�C)

2000 945 64.5 18.9 3.75 .48 .61 .73 61.5 18.0 4.21 .48 .62 .74 58.0 17.0 4.73 .49 .63 .76 54.5 16.0 5.30 .50 .64 .78

FIRST STAGE COOLING CAPACITY − XC21−060 with [CR26−60N/W−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 44.5 13.0 2.09 .77 .91 1.00 42.5 12.5 2.45 .79 .93 1.00 40.5 11.9 2.86 .80 .95 1.00 38.5 11.3 3.33 .82 .98 1.00

63�F(17�C)

1400 660 45.0 13.2 2.09 .79 .93 1.00 43.0 12.6 2.44 .80 .95 1.00 41.0 12.0 2.84 .82 .97 1.00 39.0 11.4 3.31 .84 .99 1.00(17�C)

1500 710 46.0 13.5 2.09 .80 .95 1.00 44.0 12.9 2.44 .82 .97 1.00 42.0 12.3 2.84 .84 .99 1.00 40.0 11.7 3.30 .86 1.00 1.00

67�F1300 615 47.5 13.9 2.08 .62 .75 .88 45.5 13.3 2.43 .63 .76 .90 43.0 12.6 2.83 .64 .78 .92 41.0 12.0 3.30 .65 .80 .95

67�F(19�C)

1400 660 48.0 14.1 2.08 .63 .76 .90 46.0 13.5 2.43 .64 .78 .92 44.0 12.9 2.83 .65 .80 .94 41.5 12.2 3.28 .66 .82 .97(19�C)

1500 710 48.5 14.2 2.07 .64 .78 .92 46.5 13.6 2.43 .65 .80 .94 44.5 13.0 2.82 .66 .82 .96 42.0 12.3 3.27 .67 .84 .99

71�F1300 615 50.0 14.7 2.07 .47 .60 .72 48.0 14.1 2.41 .47 .61 .74 45.5 13.3 2.81 .48 .62 .75 43.5 12.7 3.26 .49 .64 .77

71�F(22�C)

1400 660 51.0 14.9 2.07 .48 .61 .74 48.5 14.2 2.41 .48 .62 .76 46.5 13.6 2.80 .49 .64 .77 44.0 12.9 3.26 .49 .65 .79(22�C)

1500 710 51.5 15.1 2.07 .48 .62 .76 49.5 14.5 2.41 .49 .63 .77 47.0 13.8 2.80 .49 .65 .79 44.5 13.0 3.26 .50 .66 .81

SECOND STAGE COOLING CAPACITY − XC21−060 with [CR26−60N/W−2F]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1600 755 57.5 16.9 3.67 .75 .88 .99 54.5 16.0 4.14 .76 .90 1.00 51.5 15.1 4.64 .78 .92 1.00 48.0 14.1 5.25 .80 .95 1.00

63�F(17�C)

1800 850 59.0 17.3 3.68 .77 .91 1.00 56.0 16.4 4.14 .79 .93 1.00 53.0 15.5 4.67 .80 .95 1.00 49.5 14.5 5.23 .83 .98 1.00(17�C)

2000 945 60.0 17.6 3.69 .79 .94 1.00 57.0 16.7 4.15 .81 .96 1.00 54.0 15.8 4.67 .83 .98 1.00 51.0 14.9 5.26 .85 .99 1.00

67�F1600 755 61.0 17.9 3.72 .61 .73 .84 58.0 17.0 4.16 .62 .74 .86 55.0 16.1 4.69 .63 .76 .89 51.5 15.1 5.26 .64 .78 .91

67�F(19�C)

1800 850 62.5 18.3 3.72 .62 .75 .88 59.5 17.4 4.19 .63 .76 .90 56.0 16.4 4.70 .64 .78 .92 52.5 15.4 5.27 .66 .80 .95(19�C)

2000 945 63.5 18.6 3.74 .63 .77 .91 60.5 17.7 4.20 .64 .79 .93 57.0 16.7 4.71 .66 .81 .95 53.5 15.7 5.29 .67 .83 .98

71�F1600 755 64.0 18.8 3.75 .47 .59 .70 61.0 17.9 4.22 .47 .60 .72 58.0 17.0 4.73 .48 .61 .73 54.5 16.0 5.29 .48 .63 .75

71�F(22�C)

1800 850 66.0 19.3 3.77 .47 .61 .73 63.0 18.5 4.24 .48 .62 .74 59.5 17.4 4.75 .49 .63 .76 55.5 16.3 5.31 .50 .64 .78(22�C)

2000 945 67.0 19.6 3.78 .48 .62 .75 64.0 18.8 4.25 .49 .63 .76 60.5 17.7 4.75 .50 .65 .78 56.5 16.6 5.32 .50 .66 .81

Page 114: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 5 TON

DOWN−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 114

FIRST STAGE COOLING CAPACITY − XC21−060 with [CR26−48N−F + G60DFV−60C−110]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1265 595 42.5 12.5 2.26 .75 .88 1.00 40.5 11.9 2.64 .76 .90 1.00 38.5 11.3 3.07 .78 .92 1.00 36.2 10.6 3.60 .80 .95 1.00

63�F(17�C)

1400 660 43.0 12.6 2.24 .77 .91 1.00 41.5 12.2 2.62 .78 .93 1.00 39.0 11.4 3.06 .80 .95 1.00 37.0 10.8 3.58 .82 .98 1.00(17�C)

1585 750 44.5 13.0 2.23 .80 .95 1.00 42.5 12.5 2.60 .81 .97 1.00 40.0 11.7 3.04 .83 .99 1.00 38.0 11.1 3.59 .85 1.00 1.00

67�F1265 595 45.0 13.2 2.25 .60 .73 .85 43.0 12.6 2.60 .61 .74 .87 41.0 12.0 3.03 .62 .75 .88 38.5 11.3 3.55 .63 .77 .91

67�F(19�C)

1400 660 46.0 13.5 2.21 .61 .75 .87 44.0 12.9 2.59 .62 .76 .89 42.0 12.3 3.02 .63 .78 .92 39.5 11.6 3.53 .64 .80 .94(19�C)

1585 750 47.0 13.8 2.20 .63 .77 .91 45.0 13.2 2.57 .64 .79 .93 43.0 12.6 2.99 .65 .80 .96 40.5 11.9 3.52 .67 .83 .98

71�F1265 595 47.5 13.9 2.22 .46 .59 .70 46.0 13.5 2.57 .46 .60 .71 43.5 12.7 3.00 .47 .61 .73 41.0 12.0 3.51 .47 .62 .75

71�F(22�C)

1400 660 49.0 14.4 2.19 .47 .60 .72 47.0 13.8 2.55 .47 .61 .73 44.5 13.0 2.98 .48 .62 .75 42.0 12.3 3.49 .48 .63 .77(22�C)

1585 750 50.0 14.7 2.17 .48 .62 .75 48.0 14.1 2.54 .48 .63 .76 45.5 13.3 2.96 .48 .64 .78 43.0 12.6 3.47 .50 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CR26−48N−F + G60DFV−60C−110]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1845 870 56.5 16.6 3.84 .76 .89 1.00 53.5 15.7 4.32 .78 .91 1.00 50.5 14.8 4.87 .79 .94 1.00 47.0 13.8 5.49 .82 .97 1.00

63�F(17�C)

2035 960 57.5 16.9 3.83 .78 .92 1.00 54.5 16.0 4.33 .80 .94 1.00 51.5 15.1 4.87 .81 .96 1.00 48.0 14.1 5.50 .84 .99 1.00(17�C)

2290 1080 59.0 17.3 3.83 .81 .95 1.00 56.0 16.4 4.33 .82 .97 1.00 52.5 15.4 4.88 .84 .99 1.00 49.5 14.5 5.50 .87 1.00 1.00

67�F1845 870 60.0 17.6 3.84 .62 .74 .86 57.0 16.7 4.37 .63 .75 .88 54.0 15.8 4.90 .64 .77 .90 50.0 14.7 5.52 .65 .79 .93

67�F(19�C)

2035 960 61.0 17.9 3.86 .63 .76 .88 58.0 17.0 4.35 .64 .77 .91 54.5 16.0 4.90 .65 .79 .93 51.0 14.9 5.52 .66 .82 .96(19�C)

2290 1080 62.5 18.3 3.85 .65 .78 .92 59.5 17.4 4.36 .66 .80 .94 56.0 16.4 4.90 .67 .82 .97 52.0 15.2 5.52 .68 .85 .99

71�F1845 870 63.5 18.6 3.85 .47 .60 .71 60.5 17.7 4.37 .48 .61 .73 57.0 16.7 4.94 .48 .62 .75 53.5 15.7 5.55 .49 .63 .77

71�F(22�C)

2035 960 65.0 19.0 3.87 .48 .61 .73 61.5 18.0 4.40 .49 .63 .75 58.0 17.0 4.96 .49 .64 .77 54.5 16.0 5.55 .50 .65 .79(22�C)

2290 1080 66.0 19.3 3.90 .49 .63 .76 63.0 18.5 4.39 .50 .64 .78 59.5 17.4 4.94 .51 .66 .80 55.5 16.3 5.56 .52 .67 .82

FIRST STAGE COOLING CAPACITY − XC21−060 with [CR26−48N−F + G61MPV−60C−110]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1060 500 40.5 11.9 2.28 .72 .84 .95 38.5 11.3 2.69 .73 .85 .97 37.0 10.8 3.12 .75 .87 .99 34.8 10.2 3.64 .76 .90 1.00

63�F(17�C)

1180 555 41.5 12.2 2.29 .74 .86 .98 40.0 11.7 2.65 .75 .88 1.00 37.8 11.1 3.09 .76 .90 1.00 35.6 10.4 3.61 .78 .93 1.00(17�C)

1300 615 42.5 12.5 2.26 .76 .89 1.00 40.5 11.9 2.63 .77 .91 1.00 38.5 11.3 3.07 .78 .93 1.00 36.4 10.7 3.59 .80 .96 1.00

67�F1060 500 43.0 12.6 2.26 .58 .70 .80 41.5 12.2 2.63 .59 .71 .82 39.5 11.6 3.07 .60 .72 .84 37.2 10.9 3.59 .61 .74 .86

67�F(19�C)

1180 555 44.5 13.0 2.24 .59 .71 .83 42.5 12.5 2.61 .60 .73 .85 40.5 11.9 3.05 .61 .74 .87 38.0 11.1 3.56 .62 .76 .89(19�C)

1300 615 45.5 13.3 2.22 .61 .73 .85 43.5 12.7 2.60 .61 .74 .87 41.5 12.2 3.03 .62 .76 .89 39.0 11.4 3.55 .64 .78 .92

71�F1060 500 46.0 13.5 2.21 .45 .56 .67 44.0 12.9 2.60 .45 .57 .68 42.0 12.3 3.03 .45 .58 .69 39.5 11.6 3.55 .46 .59 .71

71�F(22�C)

1180 555 47.0 13.8 2.21 .45 .58 .69 45.0 13.2 2.58 .46 .59 .70 43.0 12.6 3.01 .46 .59 .71 40.5 11.9 3.52 .47 .61 .73(22�C)

1300 615 48.0 14.1 2.20 .46 .59 .71 46.0 13.5 2.57 .46 .60 .72 44.0 12.9 2.99 .47 .61 .73 41.5 12.2 3.50 .47 .62 .75

SECOND STAGE COOLING CAPACITY − XC21−060 with [CR26−48N−F + G61MPV−60C−110]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1785 845 56.0 16.4 3.83 .76 .88 .99 53.0 15.5 4.32 .77 .90 1.00 50.0 14.7 4.87 .79 .93 1.00 47.0 13.8 5.49 .81 .96 1.00

63�F(17�C)

1990 940 57.5 16.9 3.83 .78 .91 1.00 54.5 16.0 4.32 .79 .93 1.00 51.5 15.1 4.87 .81 .96 1.00 48.0 14.1 5.49 .84 .99 1.00(17�C)

2210 1045 58.5 17.1 3.82 .80 .94 1.00 55.5 16.3 4.33 .82 .96 1.00 52.5 15.4 4.88 .84 .99 1.00 49.0 14.4 5.50 .86 1.00 1.00

67�F1785 845 59.5 17.4 3.83 .61 .73 .85 56.5 16.6 4.36 .62 .75 .87 53.5 15.7 4.89 .63 .76 .89 50.0 14.7 5.53 .65 .79 .92

67�F(19�C)

1990 940 61.0 17.9 3.86 .63 .75 .88 58.0 17.0 4.35 .64 .77 .90 54.5 16.0 4.90 .65 .79 .93 51.0 14.9 5.52 .66 .81 .96(19�C)

2210 1045 62.0 18.2 3.85 .64 .78 .91 59.0 17.3 4.35 .65 .79 .93 55.5 16.3 4.90 .66 .81 .96 52.0 15.2 5.52 .68 .84 .98

71�F1785 845 63.0 18.5 3.86 .47 .60 .71 60.0 17.6 4.36 .48 .61 .72 56.5 16.6 4.93 .48 .62 .74 53.0 15.5 5.54 .49 .63 .76

71�F(22�C)

1990 940 64.5 18.9 3.87 .48 .61 .73 61.5 18.0 4.40 .48 .62 .75 58.0 17.0 4.96 .49 .64 .76 54.0 15.8 5.55 .50 .65 .79(22�C)

2210 1045 66.0 19.3 3.89 .49 .63 .75 62.5 18.3 4.39 .50 .64 .77 59.0 17.3 4.94 .51 .65 .79 55.0 16.1 5.56 .52 .67 .81

Page 115: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 5 TON

DOWN−FLOW INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 115

FIRST STAGE COOLING CAPACITY − XC21−060 with [CR26−60W−F + G60DFV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1165 550 43.0 12.6 2.24 .75 .87 .99 41.0 12.0 2.62 .76 .89 1.00 39.0 11.4 3.06 .77 .92 1.00 36.8 10.8 3.61 .79 .94 1.00

63�F(17�C)

1270 600 44.0 12.9 2.23 .76 .90 1.00 42.0 12.3 2.60 .78 .92 1.00 39.5 11.6 3.07 .79 .94 1.00 37.4 11.0 3.58 .81 .97 1.00(17�C)

1405 665 45.0 13.2 2.22 .78 .93 1.00 43.0 12.6 2.61 .80 .95 1.00 40.5 11.9 3.04 .82 .97 1.00 38.5 11.3 3.58 .84 .99 1.00

67�F1165 550 45.5 13.3 2.22 .60 .72 .84 44.0 12.9 2.59 .60 .73 .86 41.5 12.2 3.04 .61 .75 .88 39.0 11.4 3.56 .62 .77 .90

67�F(19�C)

1270 600 46.5 13.6 2.20 .61 .74 .86 44.5 13.0 2.59 .62 .75 .88 42.5 12.5 3.03 .63 .77 .91 40.0 11.7 3.52 .64 .79 .93(19�C)

1405 665 47.5 13.9 2.20 .62 .76 .89 45.5 13.3 2.58 .63 .77 .91 43.5 12.7 2.99 .64 .79 .94 41.0 12.0 3.52 .66 .81 .97

71�F1165 550 48.5 14.2 2.19 .45 .58 .70 46.5 13.6 2.56 .45 .59 .71 44.0 12.9 2.98 .46 .60 .72 42.0 12.3 3.48 .46 .61 .74

71�F(22�C)

1270 600 49.5 14.5 2.18 .46 .59 .71 47.5 13.9 2.54 .46 .60 .73 45.0 13.2 2.96 .47 .61 .74 42.5 12.5 3.50 .47 .62 .76(22�C)

1405 665 50.5 14.8 2.16 .47 .61 .73 48.5 14.2 2.55 .47 .62 .75 46.0 13.5 2.98 .48 .63 .77 43.5 12.7 3.46 .48 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−060 with [CR26−60W−F + G60DFV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1780 840 58.5 17.1 3.82 .77 .90 1.00 55.5 16.3 4.32 .78 .93 1.00 52.0 15.2 4.87 .80 .95 1.00 48.5 14.2 5.49 .83 .98 1.00

63�F(17�C)

1985 935 60.0 17.6 3.82 .79 .94 1.00 56.5 16.6 4.33 .81 .96 1.00 53.5 15.7 4.90 .83 .98 1.00 50.0 14.7 5.52 .86 .99 1.00(17�C)

2190 1035 61.0 17.9 3.83 .81 .97 1.00 58.0 17.0 4.35 .83 .98 1.00 55.0 16.1 4.89 .86 .99 1.00 51.5 15.1 5.56 .89 1.00 1.00

67�F1780 840 62.0 18.2 3.85 .62 .74 .87 59.0 17.3 4.35 .63 .76 .89 55.5 16.3 4.89 .64 .78 .92 52.0 15.2 5.51 .65 .80 .95

67�F(19�C)

1985 935 63.5 18.6 3.85 .63 .77 .90 60.5 17.7 4.34 .64 .78 .93 56.5 16.6 4.92 .66 .81 .95 53.0 15.5 5.56 .67 .83 .98(19�C)

2190 1035 64.5 18.9 3.88 .65 .79 .94 61.5 18.0 4.38 .66 .81 .96 58.0 17.0 4.94 .67 .83 .98 54.0 15.8 5.53 .69 .86 .99

71�F1780 840 66.0 19.3 3.89 .47 .60 .72 62.5 18.3 4.39 .48 .61 .74 59.0 17.3 4.93 .48 .62 .75 55.0 16.1 5.54 .49 .64 .78

71�F(22�C)

1985 935 67.0 19.6 3.90 .48 .62 .74 64.0 18.8 4.39 .49 .63 .76 60.0 17.6 4.93 .49 .64 .78 56.0 16.4 5.58 .50 .66 .81(22�C)

2190 1035 68.0 19.9 3.90 .49 .63 .77 65.0 19.0 4.39 .50 .65 .79 61.5 18.0 4.96 .51 .66 .81 57.0 16.7 5.60 .52 .68 .84

FIRST STAGE COOLING CAPACITY − XC21−060 with [CR26−60W−F + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1240 585 43.5 12.7 2.23 .76 .89 1.00 41.5 12.2 2.61 .77 .91 1.00 39.5 11.6 3.07 .79 .94 1.00 37.2 10.9 3.58 .81 .96 1.00

63�F(17�C)

1390 655 44.5 13.0 2.22 .78 .93 1.00 42.5 12.5 2.62 .80 .95 1.00 40.5 11.9 3.04 .82 .97 1.00 38.5 11.3 3.58 .84 .99 1.00(17�C)

1545 730 45.5 13.3 2.21 .81 .96 1.00 43.5 12.7 2.59 .82 .98 1.00 41.5 12.2 3.04 .84 1.00 1.00 39.5 11.6 3.53 .87 1.00 1.00

67�F1240 585 46.5 13.6 2.21 .60 .73 .86 44.5 13.0 2.57 .61 .74 .87 42.0 12.3 3.03 .62 .76 .90 40.0 11.7 3.55 .64 .78 .93

67�F(19�C)

1390 655 47.5 13.9 2.20 .62 .76 .89 45.5 13.3 2.58 .63 .77 .91 43.5 12.7 2.99 .64 .79 .94 40.5 11.9 3.52 .65 .81 .97(19�C)

1545 730 48.5 14.2 2.20 .64 .78 .93 46.5 13.6 2.55 .65 .80 .95 44.0 12.9 2.99 .66 .82 .97 41.5 12.2 3.52 .67 .84 .99

71�F1240 585 49.0 14.4 2.20 .46 .59 .71 47.0 13.8 2.55 .46 .60 .72 45.0 13.2 2.96 .46 .61 .74 42.5 12.5 3.50 .47 .62 .76

71�F(22�C)

1390 655 50.5 14.8 2.17 .47 .61 .73 48.5 14.2 2.55 .47 .62 .75 46.0 13.5 2.98 .48 .63 .76 43.5 12.7 3.46 .48 .64 .79(22�C)

1545 730 51.5 15.1 2.17 .48 .62 .76 49.5 14.5 2.54 .48 .63 .77 47.0 13.8 2.94 .49 .64 .79 44.0 12.9 3.46 .49 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−060 with [CR26−60W−F + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1670 790 57.5 16.9 3.82 .76 .89 .99 54.5 16.0 4.32 .77 .91 1.00 51.5 15.1 4.87 .79 .93 1.00 48.0 14.1 5.49 .81 .96 1.00

63�F(17�C)

1865 880 59.0 17.3 3.82 .78 .92 1.00 56.0 16.4 4.32 .79 .94 1.00 52.5 15.4 4.87 .81 .96 1.00 49.0 14.4 5.49 .84 .99 1.00(17�C)

2050 970 60.0 17.6 3.82 .80 .95 1.00 57.0 16.7 4.32 .82 .97 1.00 53.5 15.7 4.90 .84 .99 1.00 50.5 14.8 5.53 .86 1.00 1.00

67�F1670 790 61.0 17.9 3.86 .61 .73 .85 58.0 17.0 4.35 .62 .75 .87 55.0 16.1 4.90 .63 .76 .90 51.0 14.9 5.51 .64 .78 .93

67�F(19�C)

1865 880 62.5 18.3 3.85 .62 .75 .88 59.5 17.4 4.35 .63 .77 .90 56.0 16.4 4.92 .65 .79 .93 52.5 15.4 5.52 .66 .81 .96(19�C)

2050 970 64.0 18.8 3.85 .64 .78 .91 60.5 17.7 4.37 .65 .79 .94 57.0 16.7 4.93 .66 .81 .96 53.0 15.5 5.56 .68 .84 .99

71�F1670 790 64.5 18.9 3.87 .46 .59 .71 61.5 18.0 4.40 .47 .60 .72 58.0 17.0 4.96 .48 .62 .74 54.5 16.0 5.55 .48 .63 .76

71�F(22�C)

1865 880 66.0 19.3 3.90 .47 .61 .73 63.0 18.5 4.41 .48 .62 .75 59.5 17.4 4.93 .49 .63 .76 55.5 16.3 5.54 .49 .65 .79(22�C)

2050 970 68.0 19.9 3.90 .48 .62 .75 64.0 18.8 4.39 .49 .63 .77 60.5 17.7 4.93 .50 .65 .79 56.5 16.6 5.58 .51 .67 .82

Page 116: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 5 TON

HORIZONTAL INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 116

FIRST STAGE COOLING CAPACITY − XC21−060 with [CH23−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 43.5 12.7 2.12 .77 .90 1.00 41.5 12.2 2.49 .78 .92 1.00 39.5 11.6 2.91 .80 .94 1.00 37.4 11.0 3.42 .82 .97 1.00

63�F(17�C)

1400 660 44.5 13.0 2.13 .78 .93 1.00 42.5 12.5 2.50 .80 .94 1.00 40.0 11.7 2.92 .81 .97 1.00 38.0 11.1 3.39 .84 .99 1.00(17�C)

1500 710 45.0 13.2 2.13 .80 .94 1.00 43.0 12.6 2.48 .81 .96 1.00 41.0 12.0 2.89 .83 .99 1.00 39.0 11.4 3.40 .86 1.00 1.00

67�F1300 615 46.5 13.6 2.10 .61 .74 .87 44.5 13.0 2.47 .62 .76 .89 42.0 12.3 2.89 .63 .77 .91 40.0 11.7 3.36 .64 .79 .94

67�F(19�C)

1400 660 47.0 13.8 2.11 .62 .76 .89 45.0 13.2 2.47 .63 .77 .91 43.0 12.6 2.87 .64 .79 .93 40.5 11.9 3.35 .66 .81 .96(19�C)

1500 710 47.5 13.9 2.10 .63 .77 .91 45.5 13.3 2.46 .64 .79 .93 43.5 12.7 2.87 .65 .81 .95 41.0 12.0 3.36 .67 .83 .98

71�F1300 615 49.0 14.4 2.09 .47 .60 .72 47.0 13.8 2.44 .47 .61 .73 45.0 13.2 2.85 .48 .62 .75 42.5 12.5 3.32 .48 .63 .77

71�F(22�C)

1400 660 49.5 14.5 2.09 .47 .61 .73 47.5 13.9 2.45 .48 .62 .75 45.5 13.3 2.85 .49 .63 .76 43.0 12.6 3.32 .49 .64 .79(22�C)

1500 710 50.5 14.8 2.09 .48 .62 .75 48.5 14.2 2.44 .48 .63 .76 46.0 13.5 2.85 .49 .64 .78 43.5 12.7 3.31 .50 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CH23−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1600 755 56.0 16.4 3.69 .75 .87 .98 53.5 15.7 4.18 .76 .89 .99 50.5 14.8 4.69 .77 .91 1.00 47.0 13.8 5.29 .80 .94 1.00

63�F(17�C)

1800 850 57.5 16.9 3.71 .77 .90 1.00 55.0 16.1 4.19 .78 .92 1.00 51.5 15.1 4.70 .80 .94 1.00 48.5 14.2 5.32 .82 .97 1.00(17�C)

2000 945 58.5 17.1 3.73 .79 .93 1.00 56.0 16.4 4.19 .80 .95 1.00 52.5 15.4 4.73 .82 .97 1.00 49.5 14.5 5.34 .85 .99 1.00

67�F1600 755 59.5 17.4 3.73 .60 .72 .84 56.5 16.6 4.21 .61 .73 .86 53.5 15.7 4.75 .62 .75 .88 50.0 14.7 5.31 .63 .77 .91

67�F(19�C)

1800 850 61.0 17.9 3.74 .62 .74 .87 58.0 17.0 4.21 .62 .76 .89 55.0 16.1 4.75 .64 .78 .91 51.5 15.1 5.34 .65 .80 .94(19�C)

2000 945 62.5 18.3 3.75 .63 .76 .90 59.5 17.4 4.21 .64 .78 .92 56.0 16.4 4.74 .65 .80 .94 52.5 15.4 5.36 .67 .83 .97

71�F1600 755 62.5 18.3 3.76 .46 .59 .70 60.0 17.6 4.24 .47 .59 .71 56.5 16.6 4.78 .48 .61 .73 53.0 15.5 5.38 .49 .62 .75

71�F(22�C)

1800 850 64.5 18.9 3.77 .48 .60 .72 61.5 18.0 4.24 .48 .61 .73 58.0 17.0 4.78 .49 .62 .75 54.5 16.0 5.35 .50 .64 .78(22�C)

2000 945 66.0 19.3 3.79 .48 .62 .74 62.5 18.3 4.26 .49 .63 .76 59.0 17.3 4.78 .50 .64 .78 55.5 16.3 5.40 .50 .66 .80

FIRST STAGE COOLING CAPACITY − XC21−060 with [CH23−65]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 44.0 12.9 2.10 .77 .91 1.00 42.0 12.3 2.46 .78 .93 1.00 40.0 11.7 2.86 .80 .95 1.00 38.0 11.1 3.33 .82 .97 1.00

63�F(17�C)

1400 660 45.0 13.2 2.09 .78 .93 1.00 43.0 12.6 2.45 .80 .95 1.00 40.5 11.9 2.85 .82 .97 1.00 38.5 11.3 3.31 .84 .99 1.00(17�C)

1500 710 45.5 13.3 2.09 .80 .95 1.00 43.5 12.7 2.44 .82 .97 1.00 41.5 12.2 2.85 .84 .99 1.00 39.5 11.6 3.31 .86 1.00 1.00

67�F1300 615 47.0 13.8 2.08 .61 .74 .87 45.0 13.2 2.43 .62 .76 .89 43.0 12.6 2.84 .63 .77 .92 40.5 11.9 3.30 .65 .79 .94

67�F(19�C)

1400 660 47.5 13.9 2.08 .62 .76 .90 45.5 13.3 2.43 .63 .77 .92 43.5 12.7 2.83 .64 .79 .94 41.0 12.0 3.28 .66 .81 .96(19�C)

1500 710 48.5 14.2 2.08 .63 .78 .92 46.5 13.6 2.43 .64 .79 .94 44.0 12.9 2.82 .66 .81 .96 41.5 12.2 3.28 .67 .84 .99

71�F1300 615 49.5 14.5 2.07 .46 .60 .72 47.5 13.9 2.42 .47 .61 .73 45.5 13.3 2.81 .48 .62 .75 43.0 12.6 3.27 .48 .63 .77

71�F(22�C)

1400 660 50.5 14.8 2.07 .47 .61 .74 48.5 14.2 2.41 .48 .62 .75 46.0 13.5 2.80 .48 .63 .77 43.5 12.7 3.26 .49 .64 .79(22�C)

1500 710 51.0 14.9 2.07 .48 .62 .75 49.0 14.4 2.41 .48 .63 .77 46.5 13.6 2.80 .49 .64 .79 44.0 12.9 3.25 .50 .66 .81

SECOND STAGE COOLING CAPACITY − XC21−060 with [CH23−65]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1600 755 57.0 16.7 3.67 .75 .87 .99 54.5 16.0 4.13 .76 .89 1.00 51.5 15.1 4.64 .78 .92 1.00 48.0 14.1 5.22 .80 .94 1.00

63�F(17�C)

1800 850 58.5 17.1 3.68 .77 .90 1.00 55.5 16.3 4.14 .78 .93 1.00 52.5 15.4 4.67 .80 .95 1.00 49.0 14.4 5.25 .83 .98 1.00(17�C)

2000 945 59.5 17.4 3.69 .79 .93 1.00 57.0 16.7 4.15 .81 .95 1.00 53.5 15.7 4.68 .83 .98 1.00 50.5 14.8 5.26 .85 1.00 1.00

67�F1600 755 60.5 17.7 3.71 .60 .72 .84 57.5 16.9 4.16 .61 .74 .86 54.5 16.0 4.67 .62 .75 .88 51.0 14.9 5.26 .63 .77 .91

67�F(19�C)

1800 850 62.0 18.2 3.72 .61 .75 .87 59.0 17.3 4.19 .62 .76 .89 56.0 16.4 4.69 .64 .78 .92 52.5 15.4 5.27 .65 .80 .95(19�C)

2000 945 63.0 18.5 3.73 .63 .77 .90 60.0 17.6 4.20 .64 .78 .92 57.0 16.7 4.71 .65 .81 .95 53.0 15.5 5.29 .67 .83 .98

71�F1600 755 63.5 18.6 3.74 .46 .59 .70 61.0 17.9 4.21 .47 .59 .71 57.5 16.9 4.72 .48 .61 .73 54.0 15.8 5.29 .48 .62 .75

71�F(22�C)

1800 850 65.0 19.0 3.76 .47 .60 .72 62.5 18.3 4.22 .48 .61 .74 59.0 17.3 4.73 .49 .63 .76 55.5 16.3 5.31 .50 .64 .78(22�C)

2000 945 67.0 19.6 3.78 .48 .61 .75 63.5 18.6 4.25 .49 .63 .76 60.0 17.6 4.75 .49 .64 .78 56.5 16.6 5.32 .50 .66 .81

Page 117: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 5 TON

HORIZONTAL INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 117

FIRST STAGE COOLING CAPACITY − XC21−060 with [CH23−68]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 45.5 13.3 2.09 .77 .91 1.00 43.5 12.7 2.44 .79 .93 1.00 41.5 12.2 2.84 .81 .95 1.00 39.0 11.4 3.30 .83 .98 1.00

63�F(17�C)

1400 660 46.0 13.5 2.08 .79 .94 1.00 44.0 12.9 2.44 .81 .96 1.00 42.0 12.3 2.83 .83 .98 1.00 40.0 11.7 3.30 .85 1.00 1.00(17�C)

1500 710 47.0 13.8 2.08 .81 .96 1.00 45.0 13.2 2.43 .82 .98 1.00 43.0 12.6 2.83 .85 1.00 1.00 41.0 12.0 3.30 .87 1.00 1.00

67�F1300 615 48.5 14.2 2.08 .62 .75 .88 46.5 13.6 2.43 .62 .76 .90 44.0 12.9 2.82 .63 .78 .92 41.5 12.2 3.29 .65 .80 .95

67�F(19�C)

1400 660 49.0 14.4 2.08 .63 .77 .90 47.0 13.8 2.42 .64 .78 .92 45.0 13.2 2.81 .65 .80 .95 42.5 12.5 3.28 .66 .82 .97(19�C)

1500 710 50.0 14.7 2.07 .64 .78 .92 47.5 13.9 2.41 .65 .80 .95 45.5 13.3 2.81 .66 .82 .97 43.0 12.6 3.26 .68 .85 .99

71�F1300 615 51.5 15.1 2.07 .47 .60 .72 49.5 14.5 2.41 .47 .61 .74 47.0 13.8 2.80 .48 .62 .76 44.5 13.0 3.25 .49 .63 .78

71�F(22�C)

1400 660 52.5 15.4 2.06 .47 .61 .74 50.0 14.7 2.41 .48 .62 .76 48.0 14.1 2.79 .49 .63 .78 45.0 13.2 3.25 .49 .65 .80(22�C)

1500 710 53.0 15.5 2.06 .48 .62 .76 51.0 14.9 2.40 .49 .63 .78 48.5 14.2 2.79 .49 .65 .80 45.5 13.3 3.24 .50 .66 .82

SECOND STAGE COOLING CAPACITY − XC21−060 with [CH23−68]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1600 755 59.5 17.4 3.70 .75 .88 .99 56.5 16.6 4.16 .76 .90 1.00 53.5 15.7 4.67 .78 .92 1.00 50.0 14.7 5.24 .80 .95 1.00

63�F(17�C)

1800 850 61.0 17.9 3.72 .77 .91 1.00 58.5 17.1 4.17 .79 .93 1.00 55.0 16.1 4.68 .81 .96 1.00 51.5 15.1 5.26 .83 .98 1.00(17�C)

2000 945 62.5 18.3 3.73 .80 .95 1.00 59.5 17.4 4.19 .82 .96 1.00 56.5 16.6 4.71 .84 .99 1.00 53.0 15.5 5.29 .87 1.00 1.00

67�F1600 755 63.0 18.5 3.73 .61 .73 .85 60.5 17.7 4.20 .61 .74 .87 57.0 16.7 4.72 .62 .76 .89 53.5 15.7 5.29 .63 .78 .92

67�F(19�C)

1800 850 65.0 19.0 3.75 .62 .75 .88 61.5 18.0 4.21 .63 .77 .90 58.5 17.1 4.73 .64 .79 .93 54.5 16.0 5.31 .65 .81 .96(19�C)

2000 945 66.0 19.3 3.77 .63 .78 .91 63.0 18.5 4.23 .64 .79 .94 59.5 17.4 4.75 .65 .81 .96 55.5 16.3 5.32 .67 .84 .99

71�F1600 755 67.0 19.6 3.78 .46 .59 .70 64.0 18.8 4.24 .47 .60 .72 60.5 17.7 4.76 .47 .61 .73 57.0 16.7 5.34 .48 .62 .76

71�F(22�C)

1800 850 69.0 20.2 3.80 .47 .60 .73 66.0 19.3 4.27 .48 .61 .74 62.0 18.2 4.78 .48 .63 .76 58.0 17.0 5.35 .49 .64 .79(22�C)

2000 945 70.0 20.5 3.81 .48 .62 .75 67.0 19.6 4.28 .48 .63 .77 63.0 18.5 4.79 .49 .64 .79 59.0 17.3 5.38 .50 .66 .82

FIRST STAGE COOLING CAPACITY − XC21−060 with [CH33−50/60C−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 45.0 13.2 2.09 .77 .90 1.00 43.5 12.7 2.44 .78 .92 1.00 41.0 12.0 2.85 .80 .95 1.00 39.0 11.4 3.30 .82 .97 1.00

63�F(17�C)

1400 660 46.0 13.5 2.08 .78 .92 1.00 44.0 12.9 2.44 .80 .95 1.00 42.0 12.3 2.84 .81 .97 1.00 39.5 11.6 3.32 .84 .99 1.00(17�C)

1500 710 46.5 13.6 2.08 .80 .95 1.00 44.5 13.0 2.43 .81 .97 1.00 42.5 12.5 2.83 .83 .99 1.00 40.0 11.7 3.29 .86 1.00 1.00

67�F1300 615 48.0 14.1 2.08 .61 .74 .87 46.0 13.5 2.43 .62 .76 .89 44.0 12.9 2.83 .63 .77 .91 41.5 12.2 3.28 .64 .79 .94

67�F(19�C)

1400 660 49.0 14.4 2.07 .62 .76 .89 47.0 13.8 2.42 .63 .77 .91 44.5 13.0 2.81 .64 .79 .93 42.0 12.3 3.27 .65 .81 .96(19�C)

1500 710 49.5 14.5 2.07 .63 .78 .91 47.5 13.9 2.42 .64 .79 .93 45.0 13.2 2.81 .65 .81 .96 42.5 12.5 3.26 .67 .83 .98

71�F1300 615 51.0 14.9 2.07 .47 .60 .72 49.0 14.4 2.41 .48 .61 .73 46.5 13.6 2.80 .48 .61 .75 44.0 12.9 3.26 .48 .63 .77

71�F(22�C)

1400 660 51.5 15.1 2.07 .48 .61 .73 49.5 14.5 2.40 .48 .62 .75 47.5 13.9 2.80 .49 .63 .76 45.0 13.2 3.25 .49 .64 .78(22�C)

1500 710 52.5 15.4 2.06 .48 .62 .75 50.5 14.8 2.40 .49 .63 .76 48.0 14.1 2.79 .49 .64 .78 45.5 13.3 3.23 .50 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CH33−50/60C−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1600 755 59.0 17.3 3.69 .74 .87 .98 56.0 16.4 4.15 .75 .88 1.00 53.0 15.5 4.66 .77 .91 1.00 50.0 14.7 5.23 .79 .94 1.00

63�F(17�C)

1800 850 60.5 17.7 3.71 .76 .89 1.00 57.5 16.9 4.18 .78 .92 1.00 54.5 16.0 4.69 .80 .94 1.00 51.0 14.9 5.27 .82 .97 1.00(17�C)

2000 945 62.0 18.2 3.73 .78 .93 1.00 59.0 17.3 4.19 .80 .95 1.00 56.0 16.4 4.70 .82 .97 1.00 52.0 15.2 5.26 .85 1.00 1.00

67�F1600 755 62.5 18.3 3.72 .60 .72 .83 59.5 17.4 4.19 .60 .73 .85 56.5 16.6 4.69 .62 .75 .87 53.0 15.5 5.27 .63 .77 .90

67�F(19�C)

1800 850 64.0 18.8 3.75 .61 .74 .86 61.0 17.9 4.21 .62 .75 .88 57.5 16.9 4.72 .63 .77 .91 54.0 15.8 5.30 .65 .79 .94(19�C)

2000 945 65.0 19.0 3.76 .62 .76 .89 62.5 18.3 4.23 .64 .78 .91 59.0 17.3 4.74 .65 .80 .94 55.5 16.3 5.32 .66 .82 .97

71�F1600 755 66.0 19.3 3.77 .47 .58 .69 63.0 18.5 4.23 .47 .59 .71 59.5 17.4 4.75 .48 .60 .72 56.0 16.4 5.33 .48 .61 .74

71�F(22�C)

1800 850 68.0 19.9 3.79 .47 .59 .72 64.5 18.9 4.24 .48 .60 .73 61.0 17.9 4.77 .48 .62 .75 57.5 16.9 5.36 .49 .63 .77(22�C)

2000 945 69.0 20.2 3.80 .48 .61 .73 66.0 19.3 4.27 .48 .62 .75 62.5 18.3 4.79 .49 .63 .77 58.5 17.1 5.36 .50 .65 .80

Page 118: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 5 TON

HORIZONTAL INDOOR COILS

XC21 − 2 to 5 Ton Air Conditioner / Page 118

FIRST STAGE COOLING CAPACITY − XC21−060 with [CH33−60D−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 45.0 13.2 2.09 .76 .90 1.00 43.0 12.6 2.45 .78 .92 1.00 41.0 12.0 2.85 .80 .94 1.00 38.5 11.3 3.33 .81 .97 1.00

63�F(17�C)

1400 660 45.5 13.3 2.08 .78 .92 1.00 43.5 12.7 2.44 .80 .94 1.00 41.5 12.2 2.85 .81 .96 1.00 39.5 11.6 3.30 .83 .99 1.00(17�C)

1500 710 46.5 13.6 2.08 .80 .94 1.00 44.5 13.0 2.44 .81 .96 1.00 42.0 12.3 2.84 .83 .98 1.00 40.0 11.7 3.29 .85 1.00 1.00

67�F1300 615 47.5 13.9 2.08 .61 .73 .86 45.5 13.3 2.43 .62 .75 .88 43.5 12.7 2.82 .63 .77 .90 41.0 12.0 3.30 .64 .79 .93

67�F(19�C)

1400 660 48.5 14.2 2.07 .62 .75 .89 46.5 13.6 2.42 .63 .77 .90 44.0 12.9 2.82 .64 .79 .93 41.5 12.2 3.27 .65 .81 .96(19�C)

1500 710 49.0 14.4 2.07 .63 .77 .91 47.0 13.8 2.42 .64 .79 .93 45.0 13.2 2.82 .65 .80 .95 42.5 12.5 3.26 .66 .83 .98

71�F1300 615 50.5 14.8 2.07 .47 .59 .71 48.5 14.2 2.41 .48 .60 .73 46.0 13.5 2.80 .48 .62 .74 44.0 12.9 3.26 .49 .63 .76

71�F(22�C)

1400 660 51.5 15.1 2.07 .48 .60 .73 49.0 14.4 2.41 .48 .61 .74 47.0 13.8 2.80 .49 .63 .76 44.5 13.0 3.25 .49 .64 .78(22�C)

1500 710 52.0 15.2 2.06 .48 .62 .75 50.0 14.7 2.41 .49 .63 .76 47.5 13.9 2.79 .49 .64 .78 45.0 13.2 3.24 .50 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CH33−60D−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1600 755 58.5 17.1 3.67 .74 .86 .98 55.5 16.3 4.14 .75 .88 1.00 52.5 15.4 4.67 .77 .90 1.00 49.5 14.5 5.25 .79 .93 1.00

63�F(17�C)

1800 850 60.0 17.6 3.69 .76 .89 1.00 57.0 16.7 4.17 .77 .91 1.00 54.0 15.8 4.69 .79 .94 1.00 50.5 14.8 5.26 .81 .97 1.00(17�C)

2000 945 61.5 18.0 3.71 .78 .92 1.00 58.5 17.1 4.17 .80 .94 1.00 55.5 16.3 4.70 .81 .97 1.00 52.0 15.2 5.27 .84 1.00 1.00

67�F1600 755 62.0 18.2 3.73 .60 .72 .83 59.0 17.3 4.18 .60 .73 .85 56.0 16.4 4.69 .62 .74 .87 52.5 15.4 5.28 .63 .76 .90

67�F(19�C)

1800 850 63.5 18.6 3.74 .61 .74 .86 60.5 17.7 4.20 .62 .75 .88 57.0 16.7 4.72 .63 .77 .90 53.5 15.7 5.29 .64 .79 .93(19�C)

2000 945 64.5 18.9 3.75 .62 .76 .88 61.5 18.0 4.22 .63 .77 .91 58.5 17.1 4.73 .64 .79 .93 55.0 16.1 5.31 .66 .81 .96

71�F1600 755 65.0 19.0 3.76 .47 .58 .69 62.5 18.3 4.23 .47 .59 .70 59.0 17.3 4.75 .48 .60 .72 55.5 16.3 5.33 .48 .61 .74

71�F(22�C)

1800 850 67.0 19.6 3.78 .47 .59 .71 64.0 18.8 4.24 .48 .60 .72 60.5 17.7 4.77 .48 .61 .74 56.5 16.6 5.34 .49 .63 .76(22�C)

2000 945 68.0 19.9 3.80 .48 .61 .73 65.0 19.0 4.26 .48 .62 .75 61.5 18.0 4.78 .49 .63 .77 58.0 17.0 5.34 .50 .64 .79

FIRST STAGE COOLING CAPACITY − XC21−060 with [CH33−62D−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 45.0 13.2 2.08 .76 .90 1.00 43.5 12.7 2.45 .78 .91 1.00 41.0 12.0 2.85 .79 .94 1.00 39.0 11.4 3.32 .81 .97 1.00

63�F(17�C)

1400 660 46.0 13.5 2.09 .78 .92 1.00 44.0 12.9 2.44 .79 .94 1.00 42.0 12.3 2.84 .81 .96 1.00 39.5 11.6 3.30 .83 .99 1.00(17�C)

1500 710 46.5 13.6 2.08 .79 .94 1.00 44.5 13.0 2.43 .81 .96 1.00 42.5 12.5 2.83 .83 .98 1.00 40.0 11.7 3.30 .85 1.00 1.00

67�F1300 615 48.0 14.1 2.08 .61 .74 .86 46.0 13.5 2.43 .62 .75 .88 43.5 12.7 2.82 .63 .77 .90 41.5 12.2 3.28 .64 .79 .93

67�F(19�C)

1400 660 48.5 14.2 2.08 .62 .75 .88 46.5 13.6 2.43 .63 .77 .90 44.5 13.0 2.81 .64 .79 .93 42.0 12.3 3.28 .65 .81 .95(19�C)

1500 710 49.5 14.5 2.07 .63 .77 .90 47.5 13.9 2.42 .64 .78 .92 45.0 13.2 2.81 .65 .80 .95 42.5 12.5 3.26 .66 .83 .98

71�F1300 615 50.5 14.8 2.07 .47 .60 .71 48.5 14.2 2.41 .48 .60 .73 46.0 13.5 2.81 .48 .61 .74 44.0 12.9 3.25 .49 .63 .76

71�F(22�C)

1400 660 51.5 15.1 2.06 .48 .61 .73 49.0 14.4 2.41 .48 .62 .74 47.0 13.8 2.80 .49 .63 .76 44.5 13.0 3.26 .49 .64 .78(22�C)

1500 710 52.0 15.2 2.07 .48 .62 .74 50.0 14.7 2.40 .49 .63 .76 47.5 13.9 2.79 .49 .64 .78 45.0 13.2 3.25 .50 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CH33−62D−2F]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1600 755 59.0 17.3 3.69 .74 .86 .98 56.5 16.6 4.15 .75 .88 1.00 53.5 15.7 4.67 .77 .90 1.00 50.0 14.7 5.24 .79 .93 1.00

63�F(17�C)

1800 850 60.5 17.7 3.71 .76 .89 1.00 58.0 17.0 4.18 .77 .91 1.00 55.0 16.1 4.69 .79 .94 1.00 51.5 15.1 5.26 .81 .97 1.00(17�C)

2000 945 62.0 18.2 3.72 .78 .92 1.00 59.0 17.3 4.18 .80 .94 1.00 56.0 16.4 4.70 .82 .97 1.00 52.5 15.4 5.28 .84 1.00 1.00

67�F1600 755 62.5 18.3 3.72 .60 .72 .83 59.5 17.4 4.19 .61 .73 .84 56.5 16.6 4.71 .62 .74 .87 53.0 15.5 5.28 .63 .76 .90

67�F(19�C)

1800 850 64.0 18.8 3.74 .61 .74 .86 61.5 18.0 4.21 .62 .75 .88 58.0 17.0 4.73 .63 .77 .90 54.5 16.0 5.31 .65 .79 .93(19�C)

2000 945 66.0 19.3 3.77 .62 .76 .88 62.5 18.3 4.23 .63 .77 .91 59.5 17.4 4.75 .65 .79 .93 55.5 16.3 5.33 .66 .82 .97

71�F1600 755 66.0 19.3 3.77 .47 .58 .69 63.0 18.5 4.23 .47 .59 .70 59.5 17.4 4.74 .48 .60 .72 56.0 16.4 5.33 .48 .61 .74

71�F(22�C)

1800 850 68.0 19.9 3.78 .47 .59 .71 64.5 18.9 4.26 .48 .60 .73 61.5 18.0 4.77 .48 .62 .74 57.5 16.9 5.36 .49 .63 .76(22�C)

2000 945 69.0 20.2 3.81 .48 .61 .73 66.0 19.3 4.27 .49 .62 .75 62.5 18.3 4.79 .49 .63 .77 59.0 17.3 5.37 .50 .65 .79

Page 119: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 5 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 119

FIRST STAGE COOLING CAPACITY − XC21−060 with [CH23−51 + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1135 535 42.0 12.3 2.26 .74 .86 .98 40.0 11.7 2.64 .75 .88 .99 38.0 11.1 3.08 .76 .90 1.00 35.8 10.5 3.64 .78 .93 1.00

63�F(17�C)

1280 605 43.0 12.6 2.25 .76 .89 1.00 41.0 12.0 2.62 .77 .92 1.00 39.0 11.4 3.09 .79 .94 1.00 36.8 10.8 3.62 .81 .96 1.00(17�C)

1445 680 44.0 12.9 2.23 .78 .93 1.00 42.0 12.3 2.63 .80 .95 1.00 40.0 11.7 3.07 .82 .97 1.00 37.8 11.1 3.58 .84 .99 1.00

67�F1135 535 44.5 13.0 2.24 .59 .71 .83 42.5 12.5 2.61 .60 .72 .85 40.5 11.9 3.04 .61 .74 .87 38.5 11.3 3.58 .62 .76 .89

67�F(19�C)

1280 605 46.0 13.5 2.22 .61 .73 .86 44.0 12.9 2.59 .61 .75 .88 41.5 12.2 3.04 .62 .76 .90 39.5 11.6 3.57 .64 .78 .93(19�C)

1445 680 47.0 13.8 2.20 .62 .76 .90 45.0 13.2 2.59 .63 .77 .92 42.5 12.5 3.03 .64 .79 .94 40.5 11.9 3.52 .66 .82 .97

71�F1135 535 47.0 13.8 2.21 .45 .57 .69 45.0 13.2 2.58 .45 .58 .70 43.0 12.6 3.03 .46 .59 .71 40.5 11.9 3.51 .46 .60 .73

71�F(22�C)

1280 605 48.5 14.2 2.19 .46 .59 .71 46.5 13.6 2.56 .46 .60 .72 44.0 12.9 2.98 .47 .61 .74 42.0 12.3 3.51 .48 .62 .76(22�C)

1445 680 49.5 14.5 2.18 .47 .61 .73 47.5 13.9 2.54 .47 .61 .75 45.5 13.3 2.99 .48 .63 .77 43.0 12.6 3.50 .49 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−060 with [CH23−51 + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1635 770 56.0 16.4 3.83 .75 .88 .99 53.0 15.5 4.32 .76 .90 1.00 50.0 14.7 4.87 .78 .92 1.00 47.0 13.8 5.49 .80 .95 1.00

63�F(17�C)

1855 875 57.5 16.9 3.83 .77 .91 1.00 54.5 16.0 4.33 .79 .93 1.00 51.5 15.1 4.88 .81 .95 1.00 48.0 14.1 5.52 .83 .98 1.00(17�C)

2070 975 59.0 17.3 3.83 .80 .94 1.00 56.0 16.4 4.33 .82 .96 1.00 53.0 15.5 4.90 .84 .98 1.00 49.5 14.5 5.50 .86 1.00 1.00

67�F1635 770 59.5 17.4 3.83 .60 .72 .84 56.5 16.6 4.36 .61 .74 .86 53.5 15.7 4.89 .62 .75 .89 50.0 14.7 5.52 .64 .78 .92

67�F(19�C)

1855 875 61.0 17.9 3.86 .62 .75 .88 58.0 17.0 4.35 .63 .76 .90 55.0 16.1 4.90 .64 .78 .92 51.0 14.9 5.51 .66 .81 .95(19�C)

2070 975 62.5 18.3 3.85 .64 .77 .91 59.5 17.4 4.35 .65 .79 .93 56.0 16.4 4.90 .66 .81 .96 52.0 15.2 5.55 .68 .84 .98

71�F1635 770 63.0 18.5 3.86 .47 .59 .70 60.0 17.6 4.36 .47 .59 .71 56.5 16.6 4.93 .48 .61 .73 53.0 15.5 5.55 .49 .62 .75

71�F(22�C)

1855 875 64.5 18.9 3.87 .48 .60 .72 61.5 18.0 4.40 .48 .61 .74 58.0 17.0 4.96 .49 .63 .76 54.5 16.0 5.55 .50 .65 .78(22�C)

2070 975 66.0 19.3 3.90 .49 .62 .75 63.0 18.5 4.41 .49 .63 .77 59.5 17.4 4.93 .50 .65 .79 55.5 16.3 5.55 .51 .67 .82

FIRST STAGE COOLING CAPACITY − XC21−060 with [CH23−65 + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1135 535 42.0 12.3 2.25 .74 .87 .98 40.5 11.9 2.63 .75 .88 1.00 38.5 11.3 3.07 .77 .91 1.00 36.2 10.6 3.63 .78 .93 1.00

63�F(17�C)

1280 605 43.5 12.7 2.24 .76 .90 1.00 41.5 12.2 2.63 .78 .92 1.00 39.5 11.6 3.08 .79 .94 1.00 37.2 10.9 3.61 .81 .97 1.00(17�C)

1445 680 44.5 13.0 2.24 .79 .94 1.00 42.5 12.5 2.62 .80 .96 1.00 40.5 11.9 3.04 .82 .98 1.00 38.5 11.3 3.58 .85 1.00 1.00

67�F1135 535 45.0 13.2 2.24 .59 .71 .83 43.0 12.6 2.60 .60 .73 .85 41.0 12.0 3.03 .61 .74 .87 38.5 11.3 3.57 .62 .76 .90

67�F(19�C)

1280 605 46.5 13.6 2.21 .61 .74 .86 44.5 13.0 2.57 .61 .75 .88 42.0 12.3 3.04 .62 .77 .91 40.0 11.7 3.56 .64 .79 .93(19�C)

1445 680 47.5 13.9 2.21 .62 .76 .90 45.5 13.3 2.59 .63 .78 .92 43.0 12.6 3.02 .64 .80 .95 41.0 12.0 3.52 .66 .82 .97

71�F1135 535 47.5 13.9 2.22 .45 .58 .69 45.5 13.3 2.58 .46 .58 .70 43.5 12.7 2.99 .46 .59 .71 41.0 12.0 3.50 .46 .60 .73

71�F(22�C)

1280 605 49.0 14.4 2.20 .46 .59 .71 47.0 13.8 2.55 .46 .60 .72 45.0 13.2 2.99 .47 .61 .74 42.5 12.5 3.51 .48 .62 .76(22�C)

1445 680 50.5 14.8 2.17 .46 .61 .74 48.5 14.2 2.55 .47 .62 .75 46.0 13.5 2.98 .48 .63 .77 43.5 12.7 3.49 .49 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−060 with [CH23−65 + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1635 770 57.0 16.7 3.85 .75 .88 .99 54.0 15.8 4.32 .76 .90 1.00 51.0 14.9 4.88 .78 .92 1.00 47.5 13.9 5.51 .81 .95 1.00

63�F(17�C)

1855 875 58.5 17.1 3.83 .78 .91 1.00 55.5 16.3 4.33 .79 .94 1.00 52.5 15.4 4.90 .81 .96 1.00 49.0 14.4 5.53 .84 .99 1.00(17�C)

2070 975 60.0 17.6 3.83 .80 .95 1.00 57.0 16.7 4.35 .82 .97 1.00 53.5 15.7 4.92 .84 .99 1.00 50.5 14.8 5.53 .87 1.00 1.00

67�F1635 770 60.5 17.7 3.85 .60 .72 .84 57.5 16.9 4.35 .61 .74 .87 54.5 16.0 4.90 .62 .76 .89 50.5 14.8 5.51 .64 .78 .92

67�F(19�C)

1855 875 62.0 18.2 3.85 .62 .75 .88 59.0 17.3 4.35 .63 .77 .90 56.0 16.4 4.90 .64 .79 .93 52.0 15.2 5.55 .66 .81 .96(19�C)

2070 975 63.5 18.6 3.85 .64 .78 .91 60.5 17.7 4.35 .65 .79 .94 57.0 16.7 4.93 .66 .82 .96 53.0 15.5 5.56 .68 .85 .99

71�F1635 770 64.0 18.8 3.85 .46 .58 .70 61.0 17.9 4.38 .47 .60 .72 57.5 16.9 4.95 .48 .61 .73 54.0 15.8 5.54 .48 .62 .75

71�F(22�C)

1855 875 66.0 19.3 3.89 .48 .61 .73 62.5 18.3 4.40 .48 .61 .74 59.0 17.3 4.93 .49 .63 .76 55.5 16.3 5.54 .50 .64 .79(22�C)

2070 975 67.0 19.6 3.90 .49 .62 .76 64.0 18.8 4.39 .49 .64 .77 60.5 17.7 4.93 .50 .65 .79 56.5 16.6 5.59 .50 .67 .82

Page 120: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 5 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 120

FIRST STAGE COOLING CAPACITY − XC21−060 with [CH23−68 + G60UHV−60C−110]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1265 595 44.5 13.0 2.23 .76 .90 1.00 43.0 12.6 2.62 .78 .92 1.00 40.5 11.9 3.04 .80 .94 1.00 38.5 11.3 3.57 .82 .97 1.00

63�F(17�C)

1400 660 46.0 13.5 2.23 .79 .93 1.00 44.0 12.9 2.59 .80 .95 1.00 41.5 12.2 3.04 .82 .98 1.00 39.5 11.6 3.52 .85 1.00 1.00(17�C)

1585 750 47.0 13.8 2.21 .82 .97 1.00 45.0 13.2 2.58 .84 .99 1.00 43.0 12.6 3.01 .86 1.00 1.00 41.0 12.0 3.52 .89 1.00 1.00

67�F1265 595 47.5 13.9 2.21 .60 .74 .87 45.5 13.3 2.59 .61 .75 .89 43.5 12.7 3.02 .62 .77 .91 41.0 12.0 3.51 .64 .79 .93

67�F(19�C)

1400 660 49.0 14.4 2.20 .62 .76 .90 46.5 13.6 2.58 .63 .78 .92 44.5 13.0 2.99 .64 .80 .94 41.5 12.2 3.51 .66 .82 .97(19�C)

1585 750 50.5 14.8 2.17 .64 .79 .94 48.0 14.1 2.55 .65 .81 .96 45.5 13.3 2.97 .67 .83 .98 43.0 12.6 3.49 .68 .86 1.00

71�F1265 595 51.0 14.9 2.18 .46 .59 .71 48.5 14.2 2.55 .46 .60 .73 46.5 13.6 2.98 .47 .61 .74 44.0 12.9 3.46 .48 .62 .76

71�F(22�C)

1400 660 52.0 15.2 2.16 .47 .60 .74 50.0 14.7 2.54 .47 .61 .75 47.5 13.9 2.94 .48 .63 .77 44.5 13.0 3.46 .48 .64 .79(22�C)

1585 750 53.5 15.7 2.17 .48 .63 .77 51.5 15.1 2.51 .49 .64 .79 48.5 14.2 2.95 .49 .65 .81 46.0 13.5 3.42 .50 .67 .83

SECOND STAGE COOLING CAPACITY − XC21−060 with [CH23−68 + G60UHV−60C−110]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1845 870 61.5 18.0 3.87 .78 .92 1.00 58.0 17.0 4.37 .80 .94 1.00 55.0 16.1 4.92 .82 .97 1.00 51.5 15.1 5.55 .84 .99 1.00

63�F(17�C)

2035 960 62.5 18.3 3.86 .80 .95 1.00 59.5 17.4 4.37 .82 .97 1.00 56.5 16.6 4.92 .85 .99 1.00 53.0 15.5 5.56 .88 1.00 1.00(17�C)

2290 1080 64.5 18.9 3.89 .84 .98 1.00 61.5 18.0 4.37 .86 1.00 1.00 58.5 17.1 4.95 .89 1.00 1.00 55.0 16.1 5.58 .91 1.00 1.00

67�F1845 870 65.0 19.0 3.89 .62 .75 .89 61.5 18.0 4.39 .63 .77 .91 58.0 17.0 4.96 .64 .79 .94 54.5 16.0 5.54 .66 .82 .96

67�F(19�C)

2035 960 66.0 19.3 3.88 .64 .78 .92 63.0 18.5 4.41 .65 .80 .94 59.5 17.4 4.96 .66 .82 .97 55.5 16.3 5.57 .68 .85 .99(19�C)

2290 1080 68.0 19.9 3.91 .66 .81 .96 64.5 18.9 4.41 .67 .83 .98 60.5 17.7 4.94 .68 .86 1.00 56.5 16.6 5.56 .71 .89 1.00

71�F1845 870 69.0 20.2 3.90 .47 .61 .73 66.0 19.3 4.41 .48 .61 .75 62.0 18.2 4.98 .48 .63 .77 58.0 17.0 5.61 .49 .65 .79

71�F(22�C)

2035 960 71.0 20.8 3.91 .48 .62 .76 67.0 19.6 4.43 .48 .63 .77 63.0 18.5 4.99 .50 .65 .80 59.0 17.3 5.58 .51 .66 .82(22�C)

2290 1080 72.0 21.1 3.95 .49 .65 .79 69.0 20.2 4.44 .50 .66 .81 64.5 18.9 4.97 .51 .67 .84 60.0 17.6 5.61 .52 .70 .87

FIRST STAGE COOLING CAPACITY − XC21−060 with [CH33−50/60C−2F + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1135 535 43.0 12.6 2.26 .73 .86 .98 41.0 12.0 2.61 .74 .88 1.00 39.0 11.4 3.07 .76 .90 1.00 37.0 10.8 3.60 .78 .92 1.00

63�F(17�C)

1280 605 44.5 13.0 2.23 .76 .89 1.00 42.5 12.5 2.62 .77 .91 1.00 40.5 11.9 3.06 .79 .93 1.00 38.0 11.1 3.59 .81 .96 1.00(17�C)

1445 680 45.5 13.3 2.23 .78 .93 1.00 43.5 12.7 2.61 .80 .95 1.00 41.5 12.2 3.03 .82 .97 1.00 39.0 11.4 3.56 .84 1.00 1.00

67�F1135 535 46.0 13.5 2.23 .59 .71 .82 44.0 12.9 2.61 .59 .72 .84 42.0 12.3 3.03 .60 .74 .86 39.5 11.6 3.55 .62 .75 .89

67�F(19�C)

1280 605 47.0 13.8 2.20 .60 .73 .85 45.0 13.2 2.58 .61 .74 .87 43.0 12.6 3.02 .62 .76 .90 40.5 11.9 3.54 .63 .78 .92(19�C)

1445 680 48.5 14.2 2.20 .62 .76 .89 46.5 13.6 2.57 .63 .77 .91 44.0 12.9 2.98 .64 .79 .94 41.5 12.2 3.50 .65 .81 .96

71�F1135 535 48.5 14.2 2.20 .46 .57 .68 46.5 13.6 2.58 .46 .58 .69 44.5 13.0 2.98 .46 .59 .71 42.0 12.3 3.50 .47 .60 .73

71�F(22�C)

1280 605 50.0 14.7 2.19 .46 .58 .70 48.0 14.1 2.54 .47 .59 .71 45.5 13.3 2.98 .47 .61 .74 43.0 12.6 3.49 .48 .62 .75(22�C)

1445 680 51.5 15.1 2.16 .47 .60 .73 49.0 14.4 2.55 .48 .62 .75 47.0 13.8 2.97 .48 .63 .76 44.0 12.9 3.45 .49 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−060 with [CH33−50/60C−2F + G60UHV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1635 770 58.5 17.1 3.83 .74 .87 .98 55.5 16.3 4.32 .76 .89 1.00 52.5 15.4 4.90 .77 .91 1.00 49.0 14.4 5.53 .79 .94 1.00

63�F(17�C)

1855 875 60.0 17.6 3.85 .76 .90 1.00 57.0 16.7 4.36 .78 .92 1.00 54.0 15.8 4.92 .80 .95 1.00 50.5 14.8 5.54 .82 .98 1.00(17�C)

2070 975 61.5 18.0 3.86 .79 .93 1.00 58.5 17.1 4.37 .81 .95 1.00 55.5 16.3 4.92 .83 .98 1.00 51.5 15.1 5.54 .85 1.00 1.00

67�F1635 770 62.0 18.2 3.88 .60 .72 .83 59.0 17.3 4.37 .60 .73 .85 55.5 16.3 4.89 .62 .75 .87 52.0 15.2 5.55 .63 .77 .90

67�F(19�C)

1855 875 63.5 18.6 3.88 .61 .74 .86 60.5 17.7 4.37 .62 .76 .88 57.0 16.7 4.94 .63 .78 .91 53.5 15.7 5.56 .65 .80 .94(19�C)

2070 975 65.0 19.0 3.89 .63 .77 .90 62.0 18.2 4.40 .64 .78 .92 58.5 17.1 4.95 .65 .80 .95 54.5 16.0 5.54 .67 .83 .98

71�F1635 770 66.0 19.3 3.89 .47 .58 .69 62.5 18.3 4.40 .47 .59 .71 59.0 17.3 4.97 .47 .60 .72 55.5 16.3 5.55 .48 .61 .74

71�F(22�C)

1855 875 67.0 19.6 3.91 .47 .60 .72 64.0 18.8 4.42 .48 .61 .73 60.5 17.7 4.93 .48 .62 .75 56.5 16.6 5.59 .49 .63 .77(22�C)

2070 975 69.0 20.2 3.91 .48 .61 .74 66.0 19.3 4.39 .49 .62 .76 62.0 18.2 4.97 .49 .64 .78 58.0 17.0 5.60 .50 .65 .80

Page 121: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 5 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 121

FIRST STAGE COOLING CAPACITY − XC21−060 with [CH33−50/60C−2F + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1185 560 43.5 12.7 2.24 .74 .87 .99 41.5 12.2 2.62 .76 .89 1.00 39.5 11.6 3.07 .77 .91 1.00 37.4 11.0 3.60 .79 .94 1.00

63�F(17�C)

1355 640 45.0 13.2 2.23 .77 .91 1.00 43.0 12.6 2.61 .79 .93 1.00 41.0 12.0 3.06 .80 .95 1.00 38.5 11.3 3.56 .83 .98 1.00(17�C)

1545 730 46.5 13.6 2.20 .80 .95 1.00 44.5 13.0 2.59 .82 .97 1.00 42.0 12.3 3.04 .84 .99 1.00 40.0 11.7 3.51 .86 1.00 1.00

67�F1185 560 46.5 13.6 2.23 .59 .72 .84 44.5 13.0 2.58 .60 .73 .85 42.0 12.3 3.03 .61 .75 .88 40.0 11.7 3.55 .62 .77 .90

67�F(19�C)

1355 640 48.0 14.1 2.20 .61 .74 .87 46.0 13.5 2.58 .62 .76 .89 43.5 12.7 3.01 .63 .78 .92 41.0 12.0 3.50 .64 .80 .95(19�C)

1545 730 49.0 14.4 2.19 .63 .78 .91 47.0 13.8 2.55 .64 .79 .93 44.5 13.0 2.98 .65 .81 .96 42.0 12.3 3.50 .67 .83 .99

71�F1185 560 49.0 14.4 2.20 .46 .58 .69 47.0 13.8 2.55 .47 .58 .70 45.0 13.2 2.97 .47 .59 .71 42.5 12.5 3.50 .47 .61 .74

71�F(22�C)

1355 640 51.0 14.9 2.17 .47 .59 .71 48.5 14.2 2.55 .48 .61 .73 46.5 13.6 2.98 .48 .62 .75 43.5 12.7 3.48 .48 .63 .77(22�C)

1545 730 52.0 15.2 2.18 .48 .62 .75 50.0 14.7 2.54 .49 .63 .77 47.5 13.9 2.94 .49 .64 .78 45.0 13.2 3.46 .50 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CH33−50/60C−2F + G61MPV−60C−090]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1710 805 59.0 17.3 3.84 .75 .88 1.00 56.0 16.4 4.34 .77 .90 1.00 53.0 15.5 4.91 .78 .93 1.00 49.5 14.5 5.53 .81 .96 1.00

63�F(17�C)

1925 910 61.0 17.9 3.86 .78 .91 1.00 58.0 17.0 4.36 .79 .94 1.00 54.5 16.0 4.92 .81 .96 1.00 51.0 14.9 5.52 .84 .99 1.00(17�C)

2165 1020 62.5 18.3 3.87 .80 .95 1.00 59.5 17.4 4.38 .82 .97 1.00 56.0 16.4 4.90 .84 1.00 1.00 52.5 15.4 5.56 .87 1.00 1.00

67�F1710 805 62.5 18.3 3.86 .61 .73 .85 59.5 17.4 4.38 .61 .74 .86 56.0 16.4 4.92 .62 .76 .89 52.5 15.4 5.55 .64 .78 .92

67�F(19�C)

1925 910 64.0 18.8 3.88 .62 .75 .88 61.0 17.9 4.38 .63 .77 .90 57.5 16.9 4.94 .64 .79 .93 54.0 15.8 5.57 .66 .81 .96(19�C)

2165 1020 66.0 19.3 3.89 .64 .78 .91 62.5 18.3 4.40 .65 .80 .94 59.0 17.3 4.95 .66 .82 .96 55.5 16.3 5.56 .68 .84 1.00

71�F1710 805 66.0 19.3 3.90 .47 .59 .70 63.0 18.5 4.40 .48 .60 .72 59.5 17.4 4.95 .48 .61 .73 56.0 16.4 5.58 .49 .62 .75

71�F(22�C)

1925 910 68.0 19.9 3.92 .48 .61 .73 65.0 19.0 4.40 .48 .62 .74 61.0 17.9 4.96 .49 .63 .76 57.0 16.7 5.59 .50 .64 .79(22�C)

2165 1020 70.0 20.5 3.91 .49 .62 .75 66.0 19.3 4.41 .50 .63 .77 62.5 18.3 4.98 .50 .65 .79 58.5 17.1 5.60 .51 .67 .82

FIRST STAGE COOLING CAPACITY − XC21−060 with [CH33−60D−2F + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1185 560 43.5 12.7 2.24 .74 .87 .99 41.5 12.2 2.62 .75 .89 1.00 39.5 11.6 3.07 .77 .91 1.00 37.2 10.9 3.60 .79 .94 1.00

63�F(17�C)

1330 630 44.5 13.0 2.23 .76 .90 1.00 42.5 12.5 2.61 .78 .92 1.00 40.5 11.9 3.06 .79 .94 1.00 38.5 11.3 3.56 .82 .97 1.00(17�C)

1495 705 46.0 13.5 2.22 .79 .93 1.00 44.0 12.9 2.59 .80 .96 1.00 41.5 12.2 3.03 .82 .98 1.00 39.5 11.6 3.53 .85 1.00 1.00

67�F1185 560 46.0 13.5 2.23 .59 .71 .83 44.5 13.0 2.58 .60 .72 .85 42.0 12.3 3.03 .61 .74 .87 40.0 11.7 3.55 .62 .76 .90

67�F(19�C)

1330 630 47.5 13.9 2.19 .61 .74 .86 45.5 13.3 2.58 .61 .75 .88 43.0 12.6 3.02 .63 .77 .91 41.0 12.0 3.53 .64 .79 .94(19�C)

1495 705 49.0 14.4 2.20 .62 .76 .90 46.5 13.6 2.57 .63 .78 .92 44.5 13.0 2.98 .64 .80 .94 41.5 12.2 3.50 .65 .82 .97

71�F1185 560 49.0 14.4 2.20 .46 .57 .69 47.0 13.8 2.55 .46 .58 .70 45.0 13.2 2.97 .47 .59 .71 42.5 12.5 3.50 .47 .60 .73

71�F(22�C)

1330 630 50.5 14.8 2.17 .46 .59 .71 48.5 14.2 2.53 .47 .60 .73 46.0 13.5 2.98 .47 .61 .74 43.5 12.7 3.48 .48 .62 .76(22�C)

1495 705 52.0 15.2 2.17 .47 .61 .74 49.5 14.5 2.55 .48 .62 .75 47.0 13.8 2.96 .48 .63 .77 44.5 13.0 3.46 .49 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CH33−60D−2F + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1690 800 59.0 17.3 3.84 .75 .87 .99 56.0 16.4 4.32 .76 .89 1.00 53.0 15.5 4.90 .78 .92 1.00 49.5 14.5 5.53 .80 .95 1.00

63�F(17�C)

1900 895 60.5 17.7 3.85 .77 .90 1.00 57.5 16.9 4.36 .78 .93 1.00 54.0 15.8 4.92 .80 .95 1.00 50.5 14.8 5.52 .83 .99 1.00(17�C)

2135 1010 62.0 18.2 3.86 .79 .94 1.00 59.0 17.3 4.37 .81 .96 1.00 55.5 16.3 4.93 .83 .99 1.00 52.0 15.2 5.55 .86 1.00 1.00

67�F1690 800 62.5 18.3 3.85 .60 .72 .84 59.5 17.4 4.38 .61 .74 .86 56.0 16.4 4.92 .62 .75 .88 52.5 15.4 5.55 .63 .77 .91

67�F(19�C)

1900 895 64.0 18.8 3.88 .61 .74 .87 61.0 17.9 4.37 .62 .76 .89 57.5 16.9 4.94 .64 .78 .92 53.5 15.7 5.56 .65 .80 .95(19�C)

2135 1010 65.0 19.0 3.88 .63 .77 .90 62.5 18.3 4.40 .64 .79 .93 59.0 17.3 4.95 .65 .81 .96 55.0 16.1 5.55 .67 .83 .99

71�F1690 800 66.0 19.3 3.90 .47 .58 .70 63.0 18.5 4.40 .47 .59 .71 59.5 17.4 4.97 .47 .60 .73 55.5 16.3 5.57 .48 .61 .75

71�F(22�C)

1900 895 68.0 19.9 3.91 .47 .60 .72 64.5 18.9 4.40 .48 .61 .73 61.0 17.9 4.93 .48 .62 .75 57.0 16.7 5.59 .49 .64 .78(22�C)

2135 1010 69.0 20.2 3.91 .48 .61 .74 66.0 19.3 4.41 .49 .63 .76 62.0 18.2 4.98 .49 .64 .78 58.0 17.0 5.60 .50 .66 .81

Page 122: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 5 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 122

FIRST STAGE COOLING CAPACITY − XC21−060 with [CH33−60D−2F + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1240 585 44.0 12.9 2.22 .75 .88 1.00 42.0 12.3 2.62 .76 .90 1.00 40.0 11.7 3.07 .78 .92 1.00 37.6 11.0 3.59 .80 .95 1.00

63�F(17�C)

1390 655 45.0 13.2 2.23 .77 .91 1.00 43.0 12.6 2.61 .79 .94 1.00 41.0 12.0 3.03 .81 .96 1.00 38.5 11.3 3.57 .83 .99 1.00(17�C)

1545 730 46.0 13.5 2.20 .80 .95 1.00 44.0 12.9 2.59 .81 .97 1.00 42.0 12.3 3.03 .83 .99 1.00 39.5 11.6 3.54 .86 1.00 1.00

67�F1240 585 47.0 13.8 2.21 .60 .72 .84 45.0 13.2 2.59 .61 .74 .86 42.5 12.5 3.02 .61 .75 .89 40.0 11.7 3.54 .63 .77 .91

67�F(19�C)

1390 655 48.0 14.1 2.20 .61 .75 .88 46.0 13.5 2.58 .62 .76 .90 43.5 12.7 3.01 .63 .78 .92 41.0 12.0 3.50 .65 .80 .95(19�C)

1545 730 49.0 14.4 2.19 .63 .77 .91 47.0 13.8 2.55 .64 .79 .93 44.5 13.0 2.98 .65 .81 .96 42.0 12.3 3.50 .66 .83 .99

71�F1240 585 49.5 14.5 2.20 .46 .58 .70 47.5 13.9 2.54 .46 .59 .71 45.5 13.3 2.96 .47 .60 .73 43.0 12.6 3.49 .47 .61 .75

71�F(22�C)

1390 655 51.0 14.9 2.16 .47 .59 .72 49.0 14.4 2.55 .47 .61 .74 46.5 13.6 2.97 .48 .62 .75 44.0 12.9 3.45 .48 .63 .77(22�C)

1545 730 52.0 15.2 2.18 .48 .61 .75 50.0 14.7 2.54 .48 .62 .76 47.5 13.9 2.94 .49 .63 .78 44.5 13.0 3.46 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CH33−60D−2F + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1780 840 59.5 17.4 3.85 .76 .89 1.00 56.5 16.6 4.35 .77 .91 1.00 53.5 15.7 4.91 .79 .94 1.00 50.0 14.7 5.54 .81 .97 1.00

63�F(17�C)

1985 935 61.0 17.9 3.87 .78 .92 1.00 58.0 17.0 4.36 .80 .94 1.00 54.5 16.0 4.92 .82 .97 1.00 51.0 14.9 5.53 .84 1.00 1.00(17�C)

2190 1035 62.5 18.3 3.87 .80 .95 1.00 59.5 17.4 4.38 .82 .97 1.00 56.0 16.4 4.90 .84 1.00 1.00 52.5 15.4 5.56 .87 1.00 1.00

67�F1780 840 63.0 18.5 3.86 .61 .73 .85 60.0 17.6 4.35 .62 .75 .87 56.5 16.6 4.93 .63 .76 .90 53.0 15.5 5.56 .64 .79 .93

67�F(19�C)

1985 935 64.5 18.9 3.88 .62 .75 .88 61.5 18.0 4.38 .63 .77 .91 58.0 17.0 4.95 .64 .79 .93 54.0 15.8 5.57 .66 .82 .97(19�C)

2190 1035 66.0 19.3 3.89 .64 .78 .91 62.5 18.3 4.40 .65 .79 .94 59.0 17.3 4.95 .66 .82 .96 55.5 16.3 5.56 .68 .84 1.00

71�F1780 840 67.0 19.6 3.89 .47 .59 .71 63.5 18.6 4.41 .47 .60 .72 60.0 17.6 4.94 .48 .61 .74 56.0 16.4 5.58 .49 .63 .76

71�F(22�C)

1985 935 68.0 19.9 3.92 .48 .61 .73 65.0 19.0 4.39 .48 .61 .75 61.5 18.0 4.96 .49 .63 .77 57.5 16.9 5.59 .50 .64 .79(22�C)

2190 1035 70.0 20.5 3.91 .49 .62 .75 66.0 19.3 4.41 .49 .63 .77 62.5 18.3 4.98 .50 .65 .79 58.5 17.1 5.60 .51 .66 .82

FIRST STAGE COOLING CAPACITY − XC21−060 with [CH33−62D−2F + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1185 560 43.5 12.7 2.23 .74 .87 .99 42.0 12.3 2.62 .75 .88 1.00 40.0 11.7 3.06 .77 .91 1.00 37.4 11.0 3.59 .79 .93 1.00

63�F(17�C)

1330 630 45.0 13.2 2.22 .76 .90 1.00 43.0 12.6 2.61 .78 .92 1.00 41.0 12.0 3.05 .79 .94 1.00 38.5 11.3 3.56 .81 .97 1.00(17�C)

1495 705 46.0 13.5 2.20 .79 .93 1.00 44.0 12.9 2.59 .80 .95 1.00 42.0 12.3 3.03 .82 .98 1.00 39.5 11.6 3.53 .84 1.00 1.00

67�F1185 560 46.5 13.6 2.22 .59 .72 .83 44.5 13.0 2.59 .60 .73 .85 42.5 12.5 3.02 .61 .74 .87 40.0 11.7 3.54 .62 .76 .90

67�F(19�C)

1330 630 47.5 13.9 2.20 .61 .74 .86 45.5 13.3 2.57 .61 .75 .88 43.5 12.7 3.01 .63 .77 .90 41.0 12.0 3.53 .64 .79 .93(19�C)

1495 705 49.0 14.4 2.19 .62 .76 .90 47.0 13.8 2.57 .63 .78 .92 44.5 13.0 2.98 .64 .80 .94 42.0 12.3 3.50 .66 .82 .97

71�F1185 560 49.0 14.4 2.19 .46 .58 .69 47.0 13.8 2.55 .46 .58 .70 44.5 13.0 2.98 .47 .59 .72 42.5 12.5 3.49 .47 .61 .73

71�F(22�C)

1330 630 50.5 14.8 2.16 .46 .59 .71 48.5 14.2 2.55 .47 .60 .73 46.0 13.5 2.97 .47 .61 .74 43.5 12.7 3.48 .48 .62 .76(22�C)

1495 705 52.0 15.2 2.18 .47 .61 .74 49.5 14.5 2.54 .48 .62 .75 47.0 13.8 2.96 .48 .63 .77 44.5 13.0 3.46 .49 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−060 with [CH33−62D−2F + G60UHV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1690 800 59.5 17.4 3.82 .75 .87 .99 56.5 16.6 4.35 .76 .89 1.00 53.5 15.7 4.91 .78 .92 1.00 50.0 14.7 5.54 .80 .95 1.00

63�F(17�C)

1900 895 61.5 18.0 3.85 .77 .90 1.00 58.5 17.1 4.37 .78 .92 1.00 55.0 16.1 4.93 .80 .95 1.00 51.5 15.1 5.53 .83 .98 1.00(17�C)

2135 1010 63.0 18.5 3.85 .79 .94 1.00 60.0 17.6 4.38 .81 .96 1.00 56.5 16.6 4.90 .83 .99 1.00 52.5 15.4 5.54 .86 1.00 1.00

67�F1690 800 63.0 18.5 3.86 .60 .72 .84 60.0 17.6 4.34 .61 .73 .86 57.0 16.7 4.93 .62 .75 .88 53.5 15.7 5.57 .63 .77 .91

67�F(19�C)

1900 895 65.0 19.0 3.89 .61 .74 .87 61.5 18.0 4.39 .62 .76 .89 58.5 17.1 4.95 .64 .78 .92 54.5 16.0 5.58 .65 .80 .95(19�C)

2135 1010 67.0 19.6 3.90 .63 .77 .90 63.5 18.6 4.38 .65 .79 .93 60.0 17.6 4.97 .66 .81 .95 56.0 16.4 5.57 .67 .83 .99

71�F1690 800 67.0 19.6 3.89 .47 .58 .69 63.5 18.6 4.40 .47 .59 .71 60.0 17.6 4.93 .48 .60 .73 56.5 16.6 5.59 .48 .62 .75

71�F(22�C)

1900 895 69.0 20.2 3.90 .47 .60 .72 65.0 19.0 4.39 .48 .61 .73 61.5 18.0 4.97 .48 .62 .75 57.5 16.9 5.61 .49 .64 .78(22�C)

2135 1010 70.0 20.5 3.90 .48 .62 .74 67.0 19.6 4.43 .49 .63 .76 63.0 18.5 4.99 .49 .64 .78 59.0 17.3 5.62 .50 .66 .81

Page 123: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.

RATINGS 5 TON

HORIZONTAL INDOOR COILS + FURNACE

XC21 − 2 to 5 Ton Air Conditioner / Page 123

FIRST STAGE COOLING CAPACITY − XC21−060 with [CH33−62D−2F + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1240 585 44.0 12.9 2.23 .75 .88 1.00 42.0 12.3 2.61 .76 .90 1.00 40.0 11.7 3.06 .78 .92 1.00 37.8 11.1 3.59 .80 .95 1.00

63�F(17�C)

1390 655 45.5 13.3 2.22 .77 .91 1.00 43.5 12.7 2.61 .79 .93 1.00 41.5 12.2 3.03 .80 .96 1.00 39.0 11.4 3.57 .83 .99 1.00(17�C)

1545 730 46.5 13.6 2.21 .80 .94 1.00 44.5 13.0 2.60 .81 .96 1.00 42.0 12.3 3.03 .83 .99 1.00 40.0 11.7 3.52 .85 1.00 1.00

67�F1240 585 47.0 13.8 2.19 .60 .72 .84 45.0 13.2 2.58 .61 .74 .86 42.5 12.5 3.02 .62 .75 .88 40.5 11.9 3.54 .63 .77 .91

67�F(19�C)

1390 655 48.0 14.1 2.20 .61 .75 .87 46.0 13.5 2.57 .62 .76 .90 44.0 12.9 3.01 .63 .78 .92 41.5 12.2 3.50 .65 .80 .95(19�C)

1545 730 49.5 14.5 2.19 .63 .77 .91 47.5 13.9 2.55 .64 .79 .93 45.0 13.2 2.99 .65 .81 .95 42.5 12.5 3.49 .67 .83 .98

71�F1240 585 49.5 14.5 2.19 .46 .58 .70 47.5 13.9 2.54 .47 .59 .71 45.5 13.3 2.98 .47 .60 .73 43.0 12.6 3.49 .47 .61 .75

71�F(22�C)

1390 655 51.0 14.9 2.17 .47 .60 .72 49.0 14.4 2.54 .47 .61 .74 46.5 13.6 2.97 .48 .62 .75 44.0 12.9 3.45 .48 .63 .77(22�C)

1545 730 52.0 15.2 2.17 .48 .61 .74 50.0 14.7 2.54 .48 .62 .76 47.5 13.9 2.94 .49 .63 .78 45.0 13.2 3.46 .49 .65 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CH33−62D−2F + G61MPV−60D−135]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1780 840 60.5 17.7 3.85 .76 .89 1.00 57.5 16.9 4.36 .77 .91 1.00 54.0 15.8 4.92 .79 .93 1.00 50.5 14.8 5.54 .81 .97 1.00

63�F(17�C)

1985 935 62.0 18.2 3.86 .78 .92 1.00 59.0 17.3 4.37 .80 .94 1.00 55.5 16.3 4.93 .82 .97 1.00 52.0 15.2 5.54 .84 1.00 1.00(17�C)

2190 1035 63.5 18.6 3.86 .80 .95 1.00 60.5 17.7 4.38 .82 .97 1.00 57.0 16.7 4.91 .84 1.00 1.00 53.0 15.5 5.55 .87 1.00 1.00

67�F1780 840 64.0 18.8 3.87 .61 .73 .85 61.0 17.9 4.38 .62 .75 .87 57.5 16.9 4.94 .63 .77 .90 54.0 15.8 5.58 .65 .79 .93

67�F(19�C)

1985 935 66.0 19.3 3.88 .62 .75 .88 62.5 18.3 4.40 .63 .77 .90 59.0 17.3 4.96 .64 .79 .93 55.0 16.1 5.56 .66 .82 .96(19�C)

2190 1035 67.0 19.6 3.90 .64 .78 .91 64.0 18.8 4.39 .65 .80 .94 60.0 17.6 4.97 .66 .82 .97 56.5 16.6 5.58 .68 .84 1.00

71�F1780 840 68.0 19.9 3.91 .47 .59 .71 64.5 18.9 4.39 .47 .60 .72 61.0 17.9 4.96 .48 .61 .74 57.0 16.7 5.60 .49 .63 .76

71�F(22�C)

1985 935 69.0 20.2 3.90 .48 .61 .73 66.0 19.3 4.41 .48 .62 .75 62.0 18.2 4.98 .49 .63 .77 58.5 17.1 5.61 .50 .65 .79(22�C)

2190 1035 71.0 20.8 3.93 .48 .62 .75 67.0 19.6 4.43 .49 .64 .77 63.5 18.6 4.99 .50 .65 .79 59.5 17.4 5.59 .51 .67 .82

Page 124: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 5 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 124

FIRST STAGE COOLING CAPACITY − XC21−060 with [CBX32M−048][CB30M−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 45.0 13.2 2.09 .76 .91 1.00 43.0 12.6 2.45 .78 .93 1.00 40.5 11.9 2.85 .79 .95 1.00 38.5 11.3 3.33 .81 .97 1.00

63�F(17�C)

1400 660 45.5 13.3 2.09 .78 .93 1.00 43.5 12.7 2.44 .79 .95 1.00 41.5 12.2 2.85 .81 .97 1.00 39.0 11.4 3.31 .83 .99 1.00(17�C)

1500 710 46.0 13.5 2.08 .79 .95 1.00 44.0 12.9 2.44 .81 .97 1.00 42.0 12.3 2.84 .83 .99 1.00 40.0 11.7 3.30 .85 1.00 1.00

67�F1300 615 47.5 13.9 2.08 .60 .74 .87 45.5 13.3 2.43 .61 .75 .89 43.5 12.7 2.82 .62 .77 .91 41.0 12.0 3.29 .63 .79 .94

67�F(19�C)

1400 660 48.5 14.2 2.08 .61 .75 .89 46.0 13.5 2.42 .62 .77 .92 44.0 12.9 2.82 .63 .79 .94 41.5 12.2 3.28 .64 .81 .97(19�C)

1500 710 49.0 14.4 2.07 .62 .77 .92 47.0 13.8 2.42 .63 .79 .94 44.5 13.0 2.82 .64 .80 .96 42.0 12.3 3.28 .65 .83 .98

71�F1300 615 50.5 14.8 2.07 .45 .59 .71 48.0 14.1 2.41 .46 .59 .72 46.0 13.5 2.80 .46 .60 .74 43.5 12.7 3.26 .46 .62 .76

71�F(22�C)

1400 660 51.0 14.9 2.07 .46 .60 .73 49.0 14.4 2.41 .46 .60 .74 46.5 13.6 2.80 .47 .62 .76 44.0 12.9 3.26 .47 .63 .78(22�C)

1500 710 52.0 15.2 2.07 .46 .61 .74 49.5 14.5 2.41 .47 .62 .76 47.5 13.9 2.80 .47 .63 .78 44.5 13.0 3.25 .48 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CBX32M−048][CB30M−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1650 780 58.5 17.1 3.68 .75 .88 1.00 55.5 16.3 4.14 .76 .90 1.00 52.5 15.4 4.66 .78 .93 1.00 49.0 14.4 5.25 .80 .96 1.00

63�F(17�C)

1850 875 59.5 17.4 3.70 .77 .91 1.00 57.0 16.7 4.15 .78 .94 1.00 53.5 15.7 4.67 .80 .96 1.00 50.5 14.8 5.25 .83 .99 1.00(17�C)

2050 970 61.0 17.9 3.71 .79 .94 1.00 58.0 17.0 4.17 .81 .97 1.00 55.0 16.1 4.70 .83 .99 1.00 51.5 15.1 5.26 .86 1.00 1.00

67�F1650 780 62.0 18.2 3.72 .59 .72 .85 59.0 17.3 4.18 .60 .73 .87 56.0 16.4 4.71 .61 .75 .89 52.0 15.2 5.26 .62 .77 .92

67�F(19�C)

1850 875 63.5 18.6 3.73 .61 .74 .88 60.5 17.7 4.20 .62 .76 .90 57.0 16.7 4.71 .63 .78 .93 53.5 15.7 5.30 .64 .80 .96(19�C)

2050 970 64.5 18.9 3.75 .62 .77 .91 61.5 18.0 4.22 .63 .78 .94 58.0 17.0 4.73 .64 .81 .96 54.5 16.0 5.30 .66 .83 .99

71�F1650 780 65.0 19.0 3.76 .45 .58 .70 62.0 18.2 4.23 .45 .59 .71 59.0 17.3 4.74 .46 .60 .73 55.5 16.3 5.32 .46 .61 .75

71�F(22�C)

1850 875 67.0 19.6 3.78 .46 .59 .72 63.5 18.6 4.25 .46 .60 .74 60.5 17.7 4.76 .46 .61 .76 56.5 16.6 5.32 .47 .63 .78(22�C)

2050 970 68.0 19.9 3.79 .46 .61 .74 65.0 19.0 4.25 .47 .62 .76 61.5 18.0 4.77 .47 .63 .78 57.5 16.9 5.35 .48 .65 .81

FIRST STAGE COOLING CAPACITY − XC21−060 with [CBX32M−060][CB30M−65]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 45.0 13.2 2.09 .76 .90 1.00 43.0 12.6 2.44 .77 .92 1.00 41.0 12.0 2.85 .79 .94 1.00 39.0 11.4 3.31 .81 .97 1.00

63�F(17�C)

1400 660 46.0 13.5 2.08 .77 .92 1.00 44.0 12.9 2.44 .79 .94 1.00 42.0 12.3 2.84 .81 .97 1.00 39.5 11.6 3.30 .83 .99 1.00(17�C)

1500 710 46.5 13.6 2.08 .79 .94 1.00 44.5 13.0 2.44 .81 .96 1.00 42.5 12.5 2.83 .83 .98 1.00 40.0 11.7 3.31 .85 1.00 1.00

67�F1300 615 47.5 13.9 2.07 .60 .74 .86 45.5 13.3 2.42 .61 .75 .88 43.5 12.7 2.83 .62 .77 .91 41.0 12.0 3.28 .63 .79 .93

67�F(19�C)

1400 660 48.5 14.2 2.08 .61 .75 .89 46.5 13.6 2.42 .62 .77 .91 44.5 13.0 2.82 .63 .79 .93 42.0 12.3 3.28 .64 .80 .96(19�C)

1500 710 49.0 14.4 2.07 .62 .77 .91 47.0 13.8 2.42 .63 .78 .93 45.0 13.2 2.81 .64 .80 .95 42.5 12.5 3.27 .65 .82 .98

71�F1300 615 50.5 14.8 2.07 .45 .58 .71 48.5 14.2 2.41 .46 .59 .72 46.0 13.5 2.80 .46 .60 .74 43.5 12.7 3.26 .47 .62 .76

71�F(22�C)

1400 660 51.5 15.1 2.06 .46 .59 .73 49.0 14.4 2.40 .46 .60 .74 47.0 13.8 2.79 .47 .61 .76 44.5 13.0 3.25 .47 .63 .78(22�C)

1500 710 52.0 15.2 2.06 .46 .61 .74 50.0 14.7 2.41 .47 .61 .76 47.5 13.9 2.79 .47 .63 .78 45.0 13.2 3.25 .48 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CBX32M−060][CB30M−65]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1650 780 59.5 17.4 3.69 .74 .87 .99 56.5 16.6 4.16 .75 .89 1.00 53.5 15.7 4.68 .77 .92 1.00 50.0 14.7 5.25 .79 .95 1.00

63�F(17�C)

1850 875 61.0 17.9 3.71 .76 .90 1.00 58.0 17.0 4.18 .78 .93 1.00 55.0 16.1 4.70 .80 .95 1.00 51.5 15.1 5.26 .82 .98 1.00(17�C)

2050 970 62.0 18.2 3.72 .78 .93 1.00 59.0 17.3 4.18 .80 .96 1.00 56.0 16.4 4.70 .82 .98 1.00 52.5 15.4 5.27 .85 1.00 1.00

67�F1650 780 62.5 18.3 3.73 .59 .72 .84 59.5 17.4 4.18 .60 .73 .86 56.5 16.6 4.71 .61 .75 .88 53.0 15.5 5.28 .62 .77 .91

67�F(19�C)

1850 875 64.0 18.8 3.74 .60 .74 .87 61.0 17.9 4.21 .61 .75 .89 58.0 17.0 4.73 .62 .77 .92 54.0 15.8 5.30 .64 .80 .95(19�C)

2050 970 65.0 19.0 3.76 .62 .76 .90 62.5 18.3 4.23 .63 .78 .92 59.0 17.3 4.74 .64 .80 .95 55.5 16.3 5.32 .65 .82 .98

71�F1650 780 66.0 19.3 3.77 .46 .58 .69 63.0 18.5 4.24 .46 .58 .71 59.5 17.4 4.75 .46 .60 .72 56.0 16.4 5.33 .47 .61 .74

71�F(22�C)

1850 875 68.0 19.9 3.79 .46 .59 .72 64.5 18.9 4.24 .46 .60 .73 61.0 17.9 4.77 .47 .61 .75 57.0 16.7 5.34 .47 .63 .77(22�C)

2050 970 69.0 20.2 3.80 .46 .60 .74 66.0 19.3 4.27 .47 .61 .75 62.0 18.2 4.79 .48 .63 .77 58.5 17.1 5.35 .48 .64 .80

Page 125: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 5 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 125

FIRST STAGE COOLING CAPACITY − XC21−060 with [CBX32MV−048][CB31MV−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1175 555 44.0 12.9 2.10 .74 .87 .99 42.0 12.3 2.45 .75 .89 1.00 40.0 11.7 2.86 .77 .91 1.00 38.0 11.1 3.33 .79 .94 1.00

63�F(17�C)

1275 600 45.0 13.2 2.09 .76 .89 1.00 43.0 12.6 2.44 .77 .91 1.00 41.0 12.0 2.85 .79 .94 1.00 39.0 11.4 3.32 .81 .96 1.00(17�C)

1405 665 46.0 13.5 2.08 .78 .92 1.00 44.0 12.9 2.44 .79 .94 1.00 42.0 12.3 2.84 .81 .97 1.00 39.5 11.6 3.31 .83 .99 1.00

67�F1175 555 46.5 13.6 2.08 .59 .71 .84 44.5 13.0 2.43 .60 .73 .85 42.5 12.5 2.82 .60 .74 .87 40.5 11.9 3.30 .61 .76 .90

67�F(19�C)

1275 600 47.5 13.9 2.08 .60 .73 .86 45.5 13.3 2.43 .61 .74 .88 43.5 12.7 2.83 .61 .76 .90 41.0 12.0 3.29 .63 .78 .93(19�C)

1405 665 48.5 14.2 2.08 .61 .75 .89 46.5 13.6 2.42 .62 .77 .91 44.5 13.0 2.82 .63 .79 .93 42.0 12.3 3.28 .64 .81 .96

71�F1175 555 49.0 14.4 2.07 .45 .57 .69 47.5 13.9 2.41 .45 .58 .70 45.0 13.2 2.81 .46 .59 .72 43.0 12.6 3.26 .46 .60 .73

71�F(22�C)

1275 600 50.5 14.8 2.07 .45 .58 .71 48.0 14.1 2.41 .46 .59 .72 46.0 13.5 2.80 .46 .60 .74 43.5 12.7 3.26 .47 .61 .75(22�C)

1405 665 51.5 15.1 2.06 .46 .59 .73 49.0 14.4 2.40 .46 .60 .74 47.0 13.8 2.80 .47 .62 .76 44.5 13.0 3.25 .47 .63 .78

SECOND STAGE COOLING CAPACITY − XC21−060 with [CBX32MV−048][CB31MV−51]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1725 815 60.0 17.6 3.69 .75 .88 1.00 57.0 16.7 4.17 .76 .90 1.00 54.0 15.8 4.67 .78 .93 1.00 50.5 14.8 5.26 .80 .96 1.00

63�F(17�C)

1820 860 60.5 17.7 3.71 .76 .90 1.00 58.0 17.0 4.17 .77 .92 1.00 54.5 16.0 4.69 .79 .95 1.00 51.5 15.1 5.28 .82 .97 1.00(17�C)

2005 945 62.0 18.2 3.72 .78 .93 1.00 59.0 17.3 4.18 .80 .95 1.00 56.0 16.4 4.70 .82 .97 1.00 52.0 15.2 5.29 .84 .99 1.00

67�F1725 815 63.5 18.6 3.74 .60 .73 .85 60.5 17.7 4.20 .60 .74 .87 57.0 16.7 4.71 .61 .76 .90 53.5 15.7 5.29 .63 .78 .92

67�F(19�C)

1820 860 64.0 18.8 3.74 .60 .73 .87 61.0 17.9 4.21 .61 .75 .89 57.5 16.9 4.73 .62 .77 .91 54.0 15.8 5.30 .64 .79 .94(19�C)

2005 945 65.0 19.0 3.76 .61 .76 .89 62.0 18.2 4.22 .62 .77 .92 58.5 17.1 4.74 .64 .79 .94 55.0 16.1 5.32 .65 .82 .97

71�F1725 815 67.0 19.6 3.78 .46 .58 .70 63.5 18.6 4.23 .46 .59 .71 60.5 17.7 4.76 .46 .60 .73 56.5 16.6 5.33 .47 .61 .75

71�F(22�C)

1820 860 67.0 19.6 3.78 .46 .59 .71 64.0 18.8 4.24 .46 .60 .73 61.0 17.9 4.77 .46 .61 .74 57.0 16.7 5.34 .47 .62 .77(22�C)

2005 945 69.0 20.2 3.80 .46 .60 .73 66.0 19.3 4.26 .47 .61 .75 62.0 18.2 4.79 .47 .62 .77 58.0 17.0 5.35 .48 .64 .79

FIRST STAGE COOLING CAPACITY − XC21−060 with [CBX32MV−060][CB31MV−65]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1175 555 44.0 12.9 2.10 .74 .87 .99 42.0 12.3 2.45 .75 .89 1.00 40.0 11.7 2.86 .77 .91 1.00 38.0 11.1 3.33 .79 .94 1.00

63�F(17�C)

1275 600 45.0 13.2 2.09 .76 .89 1.00 43.0 12.6 2.44 .77 .91 1.00 41.0 12.0 2.85 .79 .94 1.00 39.0 11.4 3.32 .81 .96 1.00(17�C)

1405 665 46.0 13.5 2.08 .78 .92 1.00 44.0 12.9 2.44 .79 .94 1.00 42.0 12.3 2.84 .81 .97 1.00 39.5 11.6 3.31 .83 .99 1.00

67�F1175 555 46.5 13.6 2.08 .59 .71 .84 44.5 13.0 2.43 .60 .73 .85 42.5 12.5 2.82 .60 .74 .87 40.5 11.9 3.30 .61 .76 .90

67�F(19�C)

1275 600 47.5 13.9 2.08 .60 .73 .86 45.5 13.3 2.43 .61 .74 .88 43.5 12.7 2.83 .61 .76 .90 41.0 12.0 3.29 .63 .78 .93(19�C)

1405 665 48.5 14.2 2.08 .61 .75 .89 46.5 13.6 2.42 .62 .77 .91 44.5 13.0 2.82 .63 .79 .93 42.0 12.3 3.28 .64 .81 .96

71�F1175 555 49.0 14.4 2.07 .45 .57 .69 47.5 13.9 2.41 .45 .58 .70 45.0 13.2 2.81 .46 .59 .72 43.0 12.6 3.26 .46 .60 .73

71�F(22�C)

1275 600 50.5 14.8 2.07 .45 .58 .71 48.0 14.1 2.41 .46 .59 .72 46.0 13.5 2.80 .46 .60 .74 43.5 12.7 3.26 .47 .61 .75(22�C)

1405 665 51.5 15.1 2.06 .46 .59 .73 49.0 14.4 2.40 .46 .60 .74 47.0 13.8 2.80 .47 .62 .76 44.5 13.0 3.25 .47 .63 .78

SECOND STAGE COOLING CAPACITY − XC21−060 with [CBX32MV−060][CB31MV−65]

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1725 815 60.0 17.6 3.69 .75 .88 1.00 57.0 16.7 4.17 .76 .90 1.00 54.0 15.8 4.67 .78 .93 1.00 50.5 14.8 5.26 .80 .96 1.00

63�F(17�C)

1820 860 60.5 17.7 3.71 .76 .90 1.00 58.0 17.0 4.17 .77 .92 1.00 54.5 16.0 4.69 .79 .95 1.00 51.5 15.1 5.28 .82 .97 1.00(17�C)

2005 945 62.0 18.2 3.72 .78 .93 1.00 59.0 17.3 4.18 .80 .95 1.00 56.0 16.4 4.70 .82 .97 1.00 52.0 15.2 5.29 .84 .99 1.00

67�F1725 815 63.5 18.6 3.74 .60 .73 .85 60.5 17.7 4.20 .60 .74 .87 57.0 16.7 4.71 .61 .76 .90 53.5 15.7 5.29 .63 .78 .92

67�F(19�C)

1820 860 64.0 18.8 3.74 .60 .73 .87 61.0 17.9 4.21 .61 .75 .89 57.5 16.9 4.73 .62 .77 .91 54.0 15.8 5.30 .64 .79 .94(19�C)

2005 945 65.0 19.0 3.76 .61 .76 .89 62.0 18.2 4.22 .62 .77 .92 58.5 17.1 4.74 .64 .79 .94 55.0 16.1 5.32 .65 .82 .97

71�F1725 815 67.0 19.6 3.78 .46 .58 .70 63.5 18.6 4.23 .46 .59 .71 60.5 17.7 4.76 .46 .60 .73 56.5 16.6 5.33 .47 .61 .75

71�F(22�C)

1820 860 67.0 19.6 3.78 .46 .59 .71 64.0 18.8 4.24 .46 .60 .73 61.0 17.9 4.77 .46 .61 .74 57.0 16.7 5.34 .47 .62 .77(22�C)

2005 945 69.0 20.2 3.80 .46 .60 .73 66.0 19.3 4.26 .47 .61 .75 62.0 18.2 4.79 .47 .62 .77 58.0 17.0 5.35 .48 .64 .79

Page 126: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 5 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 126

FIRST STAGE COOLING CAPACITY − XC21−060 with [CBX32MV−068]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1250 590 44.5 13.0 2.23 .75 .88 1.00 42.5 12.5 2.62 .76 .90 1.00 40.5 11.9 3.06 .78 .93 1.00 38.0 11.1 3.56 .80 .95 1.00

63�F(17�C)

1390 655 45.5 13.3 2.23 .77 .91 1.00 43.5 12.7 2.59 .79 .93 1.00 41.5 12.2 3.03 .80 .96 1.00 39.0 11.4 3.57 .83 .99 1.00(17�C)

1465 690 46.0 13.5 2.22 .78 .93 1.00 44.0 12.9 2.59 .80 .95 1.00 42.0 12.3 3.04 .82 .98 1.00 39.5 11.6 3.54 .84 1.00 1.00

67�F1250 590 47.0 13.8 2.21 .59 .72 .84 45.0 13.2 2.58 .60 .74 .87 43.0 12.6 3.02 .62 .75 .89 40.5 11.9 3.53 .63 .77 .92

67�F(19�C)

1390 655 48.0 14.1 2.20 .60 .75 .88 46.0 13.5 2.57 .62 .76 .90 44.0 12.9 2.98 .63 .78 .92 41.5 12.2 3.51 .64 .80 .95(19�C)

1465 690 48.5 14.2 2.19 .61 .76 .89 46.5 13.6 2.54 .63 .77 .91 44.5 13.0 2.99 .64 .79 .94 42.0 12.3 3.51 .65 .81 .97

71�F1250 590 49.5 14.5 2.20 .46 .58 .70 48.0 14.1 2.54 .46 .59 .71 45.5 13.3 2.98 .47 .60 .73 43.0 12.6 3.49 .47 .61 .75

71�F(22�C)

1390 655 51.0 14.9 2.16 .46 .59 .72 48.5 14.2 2.54 .47 .60 .74 46.5 13.6 2.96 .48 .62 .75 44.0 12.9 3.45 .48 .62 .77(22�C)

1465 690 51.5 15.1 2.17 .47 .60 .73 49.0 14.4 2.54 .48 .60 .75 47.0 13.8 2.96 .48 .62 .76 44.0 12.9 3.46 .49 .64 .79

SECOND STAGE COOLING CAPACITY − XC21−060 with [CBX32MV−068]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1800 850 60.5 17.7 3.86 .76 .89 1.00 57.5 16.9 4.36 .77 .91 1.00 54.5 16.0 4.92 .79 .94 1.00 51.0 14.9 5.53 .81 .97 1.00

63�F(17�C)

2000 945 62.0 18.2 3.85 .78 .92 1.00 59.0 17.3 4.38 .80 .94 1.00 56.0 16.4 4.90 .82 .97 1.00 52.0 15.2 5.52 .84 1.00 1.00(17�C)

2150 1015 63.0 18.5 3.86 .79 .94 1.00 60.0 17.6 4.38 .81 .97 1.00 56.5 16.6 4.92 .83 .99 1.00 53.0 15.5 5.55 .86 1.00 1.00

67�F1800 850 64.0 18.8 3.85 .61 .73 .85 60.5 17.7 4.37 .61 .75 .87 57.5 16.9 4.94 .63 .77 .90 54.0 15.8 5.57 .64 .79 .93

67�F(19�C)

2000 945 65.0 19.0 3.89 .62 .75 .88 62.0 18.2 4.40 .63 .77 .91 59.0 17.3 4.96 .64 .79 .94 55.0 16.1 5.56 .66 .82 .97(19�C)

2150 1015 66.0 19.3 3.89 .63 .77 .90 63.0 18.5 4.40 .64 .79 .93 60.0 17.6 4.96 .66 .81 .96 56.0 16.4 5.58 .67 .84 .99

71�F1800 850 67.0 19.6 3.89 .47 .59 .71 64.0 18.8 4.39 .47 .60 .72 60.5 17.7 4.93 .48 .61 .74 56.5 16.6 5.59 .49 .63 .76

71�F(22�C)

2000 945 69.0 20.2 3.90 .48 .61 .73 65.0 19.0 4.38 .48 .62 .74 61.5 18.0 4.97 .49 .63 .77 58.0 17.0 5.60 .50 .65 .79(22�C)

2150 1015 69.0 20.2 3.90 .49 .62 .74 66.0 19.3 4.41 .49 .63 .76 62.5 18.3 4.98 .50 .64 .78 59.0 17.3 5.61 .51 .66 .81

FIRST STAGE COOLING CAPACITY − XC21−060 with [CB30U−51]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 44.0 12.9 2.09 .76 .90 1.00 42.0 12.3 2.45 .77 .92 1.00 40.5 11.9 2.86 .79 .94 1.00 38.0 11.1 3.33 .81 .97 1.00

63�F(17�C)

1400 660 45.0 13.2 2.09 .77 .92 1.00 43.0 12.6 2.45 .79 .94 1.00 41.0 12.0 2.86 .81 .96 1.00 39.0 11.4 3.33 .83 .99 1.00(17�C)

1500 710 45.5 13.3 2.09 .79 .94 1.00 43.5 12.7 2.44 .81 .96 1.00 41.5 12.2 2.84 .83 .98 1.00 39.5 11.6 3.31 .85 1.00 1.00

67�F1300 615 47.0 13.8 2.08 .60 .73 .86 45.0 13.2 2.43 .61 .75 .88 43.0 12.6 2.84 .62 .76 .91 40.5 11.9 3.31 .63 .78 .93

67�F(19�C)

1400 660 47.5 13.9 2.08 .61 .75 .89 45.5 13.3 2.43 .62 .76 .91 43.5 12.7 2.83 .63 .78 .93 41.0 12.0 3.30 .64 .80 .96(19�C)

1500 710 48.5 14.2 2.07 .62 .77 .91 46.5 13.6 2.43 .63 .78 .93 44.0 12.9 2.83 .64 .80 .95 41.5 12.2 3.28 .65 .82 .98

71�F1300 615 49.5 14.5 2.07 .45 .58 .71 47.5 13.9 2.42 .46 .59 .72 45.5 13.3 2.81 .46 .60 .74 43.0 12.6 3.26 .47 .62 .76

71�F(22�C)

1400 660 50.5 14.8 2.07 .46 .60 .73 48.5 14.2 2.41 .46 .60 .74 46.0 13.5 2.80 .47 .61 .76 43.5 12.7 3.26 .47 .63 .78(22�C)

1500 710 51.5 15.1 2.06 .46 .61 .74 49.0 14.4 2.40 .47 .61 .76 47.0 13.8 2.80 .47 .63 .78 44.5 13.0 3.25 .48 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CB30U−51]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1500 710 56.5 16.6 3.66 .73 .85 .97 53.5 15.7 4.11 .74 .87 .99 51.0 14.9 4.63 .75 .89 1.00 47.5 13.9 5.23 .77 .92 1.00

63�F(17�C)

1700 800 58.0 17.0 3.68 .75 .88 1.00 55.5 16.3 4.14 .76 .91 1.00 52.5 15.4 4.66 .78 .93 1.00 49.0 14.4 5.25 .80 .96 1.00(17�C)

1900 895 59.5 17.4 3.69 .77 .92 1.00 56.5 16.6 4.16 .78 .94 1.00 53.5 15.7 4.67 .81 .96 1.00 50.5 14.8 5.25 .83 .99 1.00

67�F1500 710 60.0 17.6 3.70 .58 .70 .82 57.0 16.7 4.16 .59 .71 .84 54.0 15.8 4.68 .60 .73 .86 50.5 14.8 5.27 .61 .75 .89

67�F(19�C)

1700 800 61.5 18.0 3.72 .59 .72 .85 59.0 17.3 4.18 .60 .74 .87 55.5 16.3 4.69 .61 .76 .90 52.0 15.2 5.27 .63 .78 .93(19�C)

1900 895 63.0 18.5 3.74 .61 .75 .88 60.0 17.6 4.19 .62 .76 .90 57.0 16.7 4.71 .63 .78 .93 53.0 15.5 5.29 .64 .81 .96

71�F1500 710 63.5 18.6 3.74 .45 .57 .68 60.5 17.7 4.20 .45 .57 .70 57.5 16.9 4.73 .45 .58 .71 54.0 15.8 5.30 .46 .60 .72

71�F(22�C)

1700 800 65.0 19.0 3.76 .45 .58 .70 62.0 18.2 4.22 .46 .59 .71 59.0 17.3 4.74 .46 .60 .73 55.0 16.1 5.32 .47 .61 .75(22�C)

1900 895 67.0 19.6 3.78 .46 .59 .72 63.5 18.6 4.23 .46 .61 .74 60.0 17.6 4.75 .47 .62 .76 56.5 16.6 5.34 .48 .63 .78

Page 127: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.Expanded rating tables are sorted by smallest to largest indoor unit model no.The following units have the same ratings and are listed together: [CBX32M/CB31M/CB30U] [CBX32MV/CB31MV] air handlers.

RATINGS 5 TON

AIR HANDLERS

XC21 − 2 to 5 Ton Air Conditioner / Page 127

FIRST STAGE COOLING CAPACITY − XC21−060 with [CB30U−65]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

75�F (24�C) 85�F (29�C) 95�F (35�C) 105�F (41�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1300 615 45.0 13.2 2.09 .76 .90 1.00 43.5 12.7 2.44 .78 .92 1.00 41.0 12.0 2.85 .79 .94 1.00 39.0 11.4 3.32 .81 .97 1.00

63�F(17�C)

1400 660 46.0 13.5 2.08 .78 .92 1.00 44.0 12.9 2.44 .79 .94 1.00 42.0 12.3 2.84 .81 .97 1.00 39.5 11.6 3.31 .83 .99 1.00(17�C)

1500 710 46.5 13.6 2.09 .79 .94 1.00 44.5 13.0 2.44 .81 .97 1.00 42.5 12.5 2.83 .83 .99 1.00 40.5 11.9 3.30 .85 1.00 1.00

67�F1300 615 48.0 14.1 2.08 .60 .74 .87 46.0 13.5 2.42 .61 .75 .89 44.0 12.9 2.82 .62 .77 .91 41.5 12.2 3.28 .63 .79 .93

67�F(19�C)

1400 660 49.0 14.4 2.07 .61 .75 .89 46.5 13.6 2.42 .62 .77 .91 44.5 13.0 2.82 .63 .78 .93 42.0 12.3 3.27 .64 .81 .96(19�C)

1500 710 49.5 14.5 2.07 .62 .77 .91 47.5 13.9 2.42 .63 .78 .93 45.0 13.2 2.81 .64 .80 .96 42.5 12.5 3.26 .65 .82 .98

71�F1300 615 50.5 14.8 2.07 .45 .58 .71 48.5 14.2 2.41 .46 .59 .72 46.5 13.6 2.80 .46 .60 .74 44.0 12.9 3.26 .47 .62 .76

71�F(22�C)

1400 660 51.5 15.1 2.07 .46 .60 .73 49.5 14.5 2.41 .46 .61 .74 47.0 13.8 2.80 .47 .62 .76 44.5 13.0 3.25 .47 .63 .78(22�C)

1500 710 52.5 15.4 2.06 .46 .61 .74 50.0 14.7 2.41 .47 .62 .76 47.5 13.9 2.79 .47 .63 .78 45.0 13.2 3.24 .48 .64 .80

SECOND STAGE COOLING CAPACITY − XC21−060 with [CB30U−65]Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera-

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F1700 800 59.5 17.4 3.69 .75 .88 .99 57.0 16.7 4.16 .76 .90 1.00 54.0 15.8 4.68 .78 .93 1.00 50.5 14.8 5.26 .80 .96 1.00

63�F(17�C)

1900 895 61.0 17.9 3.72 .77 .91 1.00 58.5 17.1 4.18 .78 .93 1.00 55.0 16.1 4.69 .80 .96 1.00 51.5 15.1 5.26 .83 .98 1.00(17�C)

2100 990 62.5 18.3 3.72 .79 .94 1.00 59.5 17.4 4.19 .81 .96 1.00 56.0 16.4 4.71 .83 .98 1.00 53.0 15.5 5.28 .85 1.00 1.00

67�F1700 800 63.0 18.5 3.74 .59 .72 .85 60.0 17.6 4.20 .60 .74 .87 57.0 16.7 4.71 .61 .75 .89 53.5 15.7 5.29 .63 .78 .92

67�F(19�C)

1900 895 64.5 18.9 3.75 .61 .74 .88 61.5 18.0 4.21 .61 .76 .90 58.0 17.0 4.74 .63 .78 .92 54.5 16.0 5.31 .64 .80 .95(19�C)

2100 990 66.0 19.3 3.77 .62 .77 .91 62.5 18.3 4.22 .63 .78 .93 59.5 17.4 4.75 .64 .80 .96 55.5 16.3 5.33 .66 .83 .98

71�F1700 800 67.0 19.6 3.77 .46 .58 .70 63.5 18.6 4.24 .46 .59 .71 60.0 17.6 4.75 .46 .60 .73 56.5 16.6 5.34 .47 .61 .75

71�F(22�C)

1900 895 68.0 19.9 3.79 .46 .59 .72 65.0 19.0 4.26 .46 .60 .74 61.5 18.0 4.77 .47 .61 .75 57.5 16.9 5.36 .48 .63 .78(22�C)

2100 990 69.0 20.2 3.80 .47 .60 .74 66.0 19.3 4.27 .47 .62 .76 62.5 18.3 4.80 .48 .63 .78 58.5 17.1 5.36 .48 .64 .81

Page 128: ehb xc21 0503 - Climate Solutions, Inc. provides ... · PDF fileCooling Capacity − 23,600 to 60,500 Btuh ... relay and start capacitor. ... open run circuit (current present only

Visit us at www.lennox.com

For the latest technical information, www.lennoxdavenet.com

Contact us at 1−800−4−LENNOX

NOTE − Due to Lennox’ ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.Installation and service must be performed by a qualified installer and servicing agency. ©2005 Lennox Industries Inc.