www.caledonian-cables.co.uk www.addison-cables.com ADDISON Caledonian 4 PE Insulation, LSZH Outer Sheath European Installation Bus(EIB) Cables EIB 2Y(St)H 2x2x0.8  Solid Copper Conductor PE Insulation LSZH Outer Sheath Overall AL/Polyester Tape With Tinned Copper Drain Wire APPLICATION EIB installation consists of sensors and actuators. The E.I.B. concept allows intergration of Building Management Systems (B.M.S.) over one common system. Lighting, blinds, heating and ventilation can be automatically controlled through the E.I.B cable. This dramatically reduces the cabling required in a modern building. To meet European standards this cable is LSZH throughout. They can be installed over, in, or below the plaster, in pipes and pipe ducts, in dry, moist, and wet areas, as well as outside, provided they are protected against direct exposure to the sun. STANDARDS Basic design to European Standard EN 50090 FIRE PERFORMANCE Flame Retardance (Single Vertical Wire T est) EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1* ; DIN VDE 0482-265-2-1* Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) EN 60332-3-24 (cat. C); IEC 60332-3-2 4; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* No Toxic gases NES 02-713; NF C 20-454 Note: Asterisk * denotes superseded standard.
Transcript

8/13/2019 EIB-2Y(St)H

http://slidepdf.com/reader/full/eib-2ysth 1/3

www.caledonian-cables.co.uk www.addison-cables.com

ADDISON

Caledonian4

PE Insulation, LSZH Outer Sheath European Installation Bus(EIB) Cables

EIB 2Y(St)H 2x2x0.8

 Solid Copper Conductor 

PE Insulation

LSZH Outer Sheath

Overall AL/Polyester Tape With Tinned Copper Drain Wire

APPLICATION

EIB installation consists of sensors and actuators. The E.I.B. concept allows intergration of Building

Management Systems (B.M.S.) over one common system. Lighting, blinds, heating and ventilation

can be automatically controlled through the E.I.B cable. This dramatically reduces the cabling

required in a modern building. To meet European standards this cable is LSZH throughout. They can

be installed over, in, or below the plaster, in pipes and pipe ducts, in dry, moist, and wet areas, as

well as outside, provided they are protected against direct exposure to the sun.

STANDARDS

Basic design to European Standard EN 50090

FIRE PERFORMANCE

Flame Retardance (Single VerticalWire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation(Vertically-mounted bundled wires

& cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24;VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1);

CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen FreeIEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke EmissionIEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.

8/13/2019 EIB-2Y(St)H

http://slidepdf.com/reader/full/eib-2ysth 2/3

Caledonian

5ADDISON

European Installation Bus(EIB) Cables

CABLE CONSTRUCTION

Type/Cable Construction 1 Quad 2 Pair  

Inner Conductor  Plain copper conductors

0.8mm

Plain copper conductors 0.8mm

Conductor Insulation PE PE

Insulation Colour  White, yellow, red, black White/yellow, red/black

Stranding Element Cores twisted into a quad Cores twisted into pairs, pairs laid

up

Screen  Aluminium/polyester foil

screen

 Aluminium/polyester foil screen

Drain Wire Solid copper Stranded tinned copper  

Outer Sheath LSZH LSZH

COLOUR CODE

Insulation Colour:

Pair1: Red/Black; Pair2: White/Yellow

Sheath Colour: Green

ELECTRICAL PROPERTIES

Test Voltage 4000V

Working Voltage MAX.150V

Conductor resistance 37.0 Ohm/km @ 20°C

Insulation resistance   1000MΩhms*km @ 20°C

Mutual capacitance@800Hz 60nF/km max

Unbalanced capacitance 300PF/100M MAX