Click here to load reader
Click here to load reader
1 1
TRAINING WIN-S
TS-E/TRG/2000
Hydraulic Governing PrincipleGovernor
DieselEngine
POWER
ActualSpeed
Reference Speed
To Electronic
Fuel
2 2
TRAINING WIN-S
TS-E/TRG/2000
Representation OfHydraulic Governing
To Electronic
3 3
TRAINING WIN-S
TS-E/TRG/2000
Electronic Governing PrincipleTo Hydraulic
Actuator
DieselEngine
POWER
Fuel
Reference Speed
Actual Speed
GovernorDigital ControllerIn Control Panel.
4 4
TRAINING WIN-S
TS-E/TRG/2000
Representation OfElectronic Governing
Digital Controller
1 1 0 - 200 mA2 Actual Speed
2To Hydraulic
5 5
TRAINING WIN-S
TS-E/TRG/2000
M
Principle (Hydraulic)
6 6
TRAINING WIN-S
TS-E/TRG/2000
Principle (Electronic)
Magnet
Coil0-200 mA
7 7
TRAINING WIN-S
TS-E/TRG/2000
Digital Controller
Types Used
2301 / 2301 A
721 Digital ControllerDroop / Isochronous ModeDroop / kW mode
723Digital Controller
8 8
TRAINING WIN-S
TS-E/TRG/2000
721 (Droop / Isochronous Mode)
Digital InputsA - Run / StopB - Increase Speed / LoadC - Decrease Speed / LoadD - Circuit Breaker Aux.E - Auto UnloadF - Droop / IsochronousG - Idle / Rated SpeedH - Emergency Loading Rate
Digital OutputsMajor AlarmMinor AlarmBreaker Open Command
9 9
TRAINING WIN-S
TS-E/TRG/2000
Analogue InputsEngine SpeedActive PowerDigital SynchroniserLoad Sharing
721 (Droop / Isochronous Mode)
Analogue OutputsOutput to ActuatorLoad LevelEngine SpeedActuator PositionLoad Sharing Lines
10 10
TRAINING WIN-S
TS-E/TRG/2000
721 (Droop / kW Mode)
Digital InputsA - Run / StopB - Increase Speed / LoadC - Decrease Speed / LoadD - Circuit Breaker Aux.E - Auto UnloadF - kW / DroopG - Select Remote kW ReferenceH - Parallel with Grid
Digital OutputsMajor AlarmkW In ControlBreaker Open Command
11 11
TRAINING WIN-S
TS-E/TRG/2000
Analogue InputsEngine SpeedActive PowerDigital SynchroniserRemote kW Reference
721 (Droop / kW Mode)
Analogue OutputsOutput to ActuatorLoad LevelEngine SpeedLoad Limit or kW Reference
12 12
TRAINING WIN-S
TS-E/TRG/2000
723 Droop / Isochronous / kW mode
Digital InputsA - Run / StopB - Increase Speed / LoadC - Decrease Speed / LoadD - Circuit Breaker Aux.E - Unload / Idle / RatedF - kW / Isochronous / DroopG - Select MW ControlH - Parallel with Grid / Emergency Load Rate
Digital OutputsMajor AlarmMinor Alarm / Grid Bkr OpenDG Breaker Open Command
13 13
TRAINING WIN-S
TS-E/TRG/2000
723 Droop / Isochronous / kW mode
Analogue InputsEngine Speed # 1Engine Speed # 2 / T/C SpeedActual Active PowerActive Power ReferenceLoad Sharing LinesDigital SynchroniserRemote kW Reference
Analogue OutputsOutput to Actuator* Actuator Position* Load Level* kW Reference* Engine Speed # 1* Engine Speed # 2* Turbocharger Speed
* Any 3 Outputs Can Be Configured.