AMOUNT In Fig. (Rs.) In Words (Rs.) 1.1 Wiring for light Point/ fan point/ exhaust fan point/ call bell point with 1.5 Sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed Steel conduit, with modular switch, modular plate, suitable size GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required. Point 7277 1.2 Wiring for twin control light Point with 1.5 Sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed Steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. Point 10 1.3 Wiring for submain wiring/ circuit wiring along with earth wire with the following sizes of PVC insulated copper conductor, single core cable in surface/ recessed Steel conduits as required. a) 2 x 2.5 Sq. mm + 1 x 2.5 Sq. mm earth wire. Mtrs. 23145 b) 2 x 4 Sq. mm + 1 x 4 Sq. mm earth wire. Mtrs. 13010 c) 2 x 6 Sq. mm + 1 x 6 Sq. mm earth wire. Mtrs. 200 d) 4 x 2.5 Sq. mm + 2 x 2.5 sq.mm earth wire Mtrs. 100 e) 4 x 4 Sq. mm + 2 x 4 sq.mm earth wire Mtrs. 4800 f) 4 x 6 Sq. mm + 2 x 6 sq.mm earth wire Mtrs. 200 g) 4 x 10 Sq. mm + 2 x 10sq.mm earth wire Mtrs. 250 h) 4 x 16 Sq. mm + 2 x 16sq.mm earth wire Mtrs. 200 1.4 Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduits as required. Metre 1360 1.5 Supplying and fixing of following sizes of Steel conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. a) 25 mm Metre 1360 b) 32 mm Metre 100 c) 40 mm Metre 200 1.6 Supplying and fixing following modular switch/ socket on existing modular plate & switch box including connections but excluding modular plate etc. as required. TV antenna socket outlet Each 34 1.7 Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. Each 632 1.8 Supplying and fixing modular blanking plate on the existing modular plate switch box including connections but excluding modular plate etc. as required. Each 200 UNIT RATE SUBHEAD-I: POINT WIRING & SUBMAIN WIRING Sl. No. DESCRIPTION OF ITEM UNIT QTY. Ru-Tech Services Inc. Page-1 Electrical BOQ.xls
Transcript
Page 1: Electrical BOQ Final

AMOUNTIn Fig. (Rs.) In Words (Rs.)

1.1 Wiring for light Point/ fan point/ exhaust fan point/ call bell point with 1.5 Sq. mm FRLSPVC insulated copper conductor single core cable in surface/ recessed Steel conduit,with modular switch, modular plate, suitable size GI box and earthing the point with 1.5sq.mm FRLS PVC insulated copper conductor single core cable etc as required.

Point 72771.2 Wiring for twin control light Point with 1.5 Sq. mm FRLS PVC insulated copper

conductor single core cable in surface/ recessed Steel conduit, 2 way modular switch,modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVCinsulated copper conductor single core cable etc as required. Point 10

1.3 Wiring for submain wiring/ circuit wiring along with earth wire with the following sizes ofPVC insulated copper conductor, single core cable in surface/ recessed Steel conduitsas required.

a) 2 x 2.5 Sq. mm + 1 x 2.5 Sq. mm earth wire. Mtrs. 23145b) 2 x 4 Sq. mm + 1 x 4 Sq. mm earth wire. Mtrs. 13010c) 2 x 6 Sq. mm + 1 x 6 Sq. mm earth wire. Mtrs. 200d) 4 x 2.5 Sq. mm + 2 x 2.5 sq.mm earth wire Mtrs. 100e) 4 x 4 Sq. mm + 2 x 4 sq.mm earth wire Mtrs. 4800f) 4 x 6 Sq. mm + 2 x 6 sq.mm earth wire Mtrs. 200g) 4 x 10 Sq. mm + 2 x 10sq.mm earth wire Mtrs. 250h) 4 x 16 Sq. mm + 2 x 16sq.mm earth wire Mtrs. 2001.4 Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor

PE insulated, shielded with fine tinned copper braid and protected with PVC sheath inthe existing surface/ recessed steel/ PVC conduits as required. Metre 1360

1.5 Supplying and fixing of following sizes of Steel conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduitas required.

a) 25 mm Metre 1360b) 32 mm Metre 100c) 40 mm Metre 2001.6 Supplying and fixing following modular switch/ socket on existing modular plate & switch

box including connections but excluding modular plate etc. as required.TV antenna socket outlet Each 34

1.7 Supplying and fixing stepped type electronic fan regulator on the existing modular plateswitch box including connections but excluding modular plate etc. as required.

Each 6321.8 Supplying and fixing modular blanking plate on the existing modular plate switch box

including connections but excluding modular plate etc. as required. Each 200

UNIT RATE

SUBHEAD-I: POINT WIRING & SUBMAIN WIRING

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls

Page 2: Electrical BOQ Final

AMOUNTIn Fig. (Rs.) In Words (Rs.)

UNIT RATE

SUBHEAD-I: POINT WIRING & SUBMAIN WIRING

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

1.9 Supplying and fixing of metal box of GI box with modular plate and cover in front onsurface or in recess, including providing and fixing of 3 pin 5/6 amps. modular socketoutlet and 5/6 amps. modular switch, connections, painting etc. as required. (For lightplugs). Each 682

2.0 Supplying and fixing of metal box of GI box with modular plate and cover in front onsurface or in recess, including providing and fixing of 6 pin 15/16 & 5/6 amps modularsocket outlet and 15/16 amps. modular switch, connections, painting etc. as required.(For power plugs). Each 768

2.1 Supplying and fixing of metal box of GI box with modular plate and cover in front onsurface or in recess , including providing and fixing of 3 Nos 3 pin 5/6 amps modularsocket outlet and 15/16 amps. modular switch, connections, painting etc. as required.(For computer plugs). Each 657

2.2 Supplying and fixing of 3 pin, 5 Amp. ceiling rose on the existing junction box/ woodenblock including connection etc. as required. (For power plugs). Each 143

2.3 Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 poleand earth, metal enclosed plug top alongwith 20 amps. 'C'-series, SP, MCB, in sheetsteel enclosure, on surface or in recess, with chained metal cover for the socket outletand complete with connections, testing and commissioning etc. as required.

Each 902.4 Supplying and fixing 30 amps, 240 volts, TPN industrial type socket outlet, with 4 pole

and earth metal enclosed plug top alongwith 30 amps. 'C'-series, TPMCB, in sheet steelenclosure, on surface or in recess, with chained metal cover for the socket outlet, andcomplete with connections, testing and commissioning etc. as required.

Each 117

TOTAL OF SUBHEAD I CARRIED OVER TO SUMMARY OF ELECTRICAL WORKS

Ru-Tech Services Inc. Page-2 Electrical BOQ.xls

Page 3: Electrical BOQ Final

AMOUNTIn Fig.(Rs.) In Words(Rs.)

Supplying, installation, testing and commissioning of the followingluminaries mounting on surface / recess required for the internal wiring ofthe building along with suitable hangers and lamps.

1 Surface mounted Industrial Box type 4 X 14W T-5 fixtures with HF ballast(Philips Cat No. TPS 814/414 D8 HF/ Equivalent ) complete in everywaywith accessories & lamps. Each 721

2 Recessed mounted in modular cielings with 4 X 14W T-5 fixtures with HFballast (Philips Cat No. TBS 869/414 D8 HF/ Equivalent ) complete ineveryway with accessories & lamps. Each 800

3 Recessed mounted low glare luminair with 3 X PL-L36W (Philips Cat No.FBS 300/336 P5 HF/ Equivalent ) complete in everyway with accessories& lamps. Each 1134

4 Recessed mounted low glare luminair with 2 X PL-L36W (Philips Cat No.FBS 570/236 FNC D6 MM HPF/ Equivalent ) complete in everyway withaccessories & lamps. Each 270

5 Recessed mounted downlighter 2 X PL-C 26W (Philips Cat No. FBH225/226 ALR/ Equivalent ) complete in everyway with accessories &lamps. Each 55

6 Surface mounted rectangular luminaire with 2 X 28W T-5 fixtures with HFballast (Philips Cat No. TPS 814/228 D8 HF/ Equivalent ) complete ineveryway with accessories & lamps. Each 100

7 Recessed mounted rectangular luminaire with 2 X 28W T-5 fixtures withHF ballast(Philips Cat No. TBS 869/228 D8 HF/ Equivalent ) complete ineveryway with accessories & lamps. Each 47

8 Industrial Batton suitable for 1 X 28W T-5 fixtures with HF ballast (PhilipsCat No. TMS 122/128 HF/ Equivalent ) complete in everyway withaccessories & lamps. Each 10

9 Indoor decorative surface mounted suitable for 1 X 28W T-5 fixtures withHF ballast (Philips Cat No. TWG 128 / 2005 HF/ Equivalent ) complete ineveryway with accessories & lamps. Each 93

10 Surface mounted suitable for 1 X PL-S 9 W fixtures with HF ballast(Philips Cat No. FCS 518/209 / Equivalent ) complete in everyway withaccessories & lamps. Each 2

QTY.

SUBHEAD-II: FANS & FITTINGS

UNIT RATESl. No.

DESCRIPTION OF ITEM UNIT

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls

Page 4: Electrical BOQ Final

AMOUNTIn Fig.(Rs.) In Words(Rs.)

QTY.

SUBHEAD-II: FANS & FITTINGS

UNIT RATESl. No.

DESCRIPTION OF ITEM UNIT

11 Wall recess step light luminaire die cast housing suitable for 2 X PL-C 18W fixtures with HF ballast (Philips Cat No. DBP701/ 2x PLC18W/ Similarspecifications of other approved makes) complete in everyway withaccessories & lamps. Each 11

12 Surface mounted suitable for 2 X PL-S 18 W fixtures with HF ballast(Philips Cat No. FCS 518/218 / Equivalent ) complete in everyway withaccessories & lamps. Each 734

13 Recessed down lighter suitable for 1 X PL-C 13W fixtures (Philips CatNo. FBH 145 /113 L / Equivalent ) complete in everyway with accessories& lamps. Each 184

14 Recessed down lighter suitable for 1 X PL-C 18W fixtures (Philips CatNo. FBH 145 /118 L / Equivalent ) complete in everyway with accessories& lamps. Each 2

15 Recessed down lighter suitable for 2 X PL-C 18W fixtures (Philips CatNo. FBH 145 /218 L/ Equivalent ) complete in everyway with accessories& lamps. Each 1000

16 Surface mounted down lighter suitable for 1 X 70W (Philips Cat No.MBS205 / 1 X 70W MHN-TD / Equivalent ) complete in everyway withaccessories & lamps. Each 80

17 Scrabble with adjustable Lamp position 1X70W CDMT 3000 Deg.K(Havells Cat No. LHOH80150399 / Equivalent ) complete in everywaywith accessories & lamps. Each 117

18 Scrabble with adjustable Lamp position 1X35W CDMT 3000 Deg.K(Havells Cat No. LHOH80150399 / Equivalent ) complete in everywaywith accessories & lamps. Each 25

19 Scrabble with adjustable Lamp position 2X70W CDMT 3000 Deg.K(Havells Cat No. LHOH80250399 / Equivalent ) complete in everywaywith accessories & lamps. Each 51

20 Decorative non-integral medium bay luminaire with prismatic diffuserssuitable for 1 X CDM-TT 150W fixtures (Philips Cat No. HPK 205 /CDM-TT 150W PR / Equivalent ) complete in everyway with accessories &lamps. Each 302

Ru-Tech Services Inc. Page-2 Electrical BOQ.xls

Page 5: Electrical BOQ Final

AMOUNTIn Fig.(Rs.) In Words(Rs.)

QTY.

SUBHEAD-II: FANS & FITTINGS

UNIT RATESl. No.

DESCRIPTION OF ITEM UNIT

21 Wall mounted mirror luminaire suitable for 1 X PL-5 11W fixtures (PhilipsCat No. FMS 200/111 / Equivalent ) complete in everyway withaccessories & lamps. Each 134

22 Bulkhead luminaire fitting suitable for 18 W CFL (Philips Cat No. FXC101/ Equivalent ) complete in everyway with accessories & lamps

Each 4523 Decorative moulded body ceiling mounted fixture suitable for 2 X 9W CFL

(Havells Cat. No. LHDC27209024 / Equivalent ) complete in everywaywith accessories & lamps. Each 10

24 Wall Bracket Lighting fixture suitable for 2 X 9W CFL (Havells Cat. No.LHDC01209017 / Equivalent ) complete in everyway with accessories &lamps. Each 97

25 Supplying of 1200mm A.C Ceiling fan sweep complete (Havells Cat. No.LHDC27209024 / Equivalent ) (But without regulator) Each 632

26 Supplying of wall mounted Turbo Force Air Circulators 450 MM Wall TFof Havells Cat. / Equivalent ) (But without regulator) Each 439

27 Supplying of Heavy Duty Exhaust Fan complete with louvers / shutter offollowing sizes

a) 300 MM x 1400 RPM Single phase Nos 30b) 380 MM x 1400 RPM Single phase Nos 113

TOTAL OF SUBHEAD II CARRIED OVER TO SUMMARY OFELECTRICAL WORKS

Ru-Tech Services Inc. Page-3 Electrical BOQ.xls

Page 6: Electrical BOQ Final

AMOUNTIn Fig. (Rs.) In Words(Rs.)

DISTRIBUTION BOARDS1.1 Supplying and fixing following way, single pole and neutral, prewired, sheet

steel, MCB distribution board, 240 volts, on surface/ recess, complete withloose wire box, terminal box, duly prewired with suitable size FRLS PVCinsulated copper conductor upto terminal blocks, tinned copper busbar,neutral links, earthbar, dinbar, detachable gland plate, interconnections,phosphatized and powder painted including earthing etc. as required (Butwithout MCB/ RCCB/ Isolator) 2+4, Double door Each 10

1.2 Supplying, installation, testing and commissioning of surface/ recessmounting, vertical type, 415 volts, prewired, TPN MCB distribution board ofsheet steel, dust protected, duly phosphatized and powder painted, inclusiveof 200 amps tinned copper busbars, common neutral link, earth bar, din barfor mounting MCB's, detachable gland/ knock out plate, and with built in loosewire box, and superior make terminal connectors for all incoming andoutgoing circuits, duly prewired with adequate size of FRLS PVC insulatedcopper conductor upto the terminal connector/ neutral link and ready forinstallation of following ways (but without MCB's and incomer) as required.

a) 4 way (4+12), Double door Each 51b) 6 way (4+18), Double door Each 83c) 8 way (4+24), Double door Each 81d) 12 way (4+36), Double door Each 311.3 Supplying and fixing 5 amps to 32 amps rating, 240 volts, 'B' series ,

miniature circuit breaker suitable for lighting and other loads of following polesin the existing MCB DB complete with connections, testing and commissioningetc. as required.

a) Single Pole, 10/16/20/32 Amps Nos 2629b) Triple Pole, 16/20/32 Amps Nos 1171.4 Supplying and fixing following rating, double pole, (single phase and neutral),

240 volts, residual current circuit breaker (RCCB), having a sensitivity currentupto 300 milliamperes in the existing MCB DB complete with connections,testing and commissioning etc. as required.40 Amps Each 10

QTY.

SUBHEAD-III: DISTRIBUTION BOARDS

UNIT RATES (Rs.)Sl. No DESCRIPTION OF ITEM UNIT

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls

Page 7: Electrical BOQ Final

AMOUNTIn Fig. (Rs.) In Words(Rs.)

QTY.

SUBHEAD-III: DISTRIBUTION BOARDS

UNIT RATES (Rs.)Sl. No DESCRIPTION OF ITEM UNIT

1.5 Supplying and fixing following rating, foure pole, (three phase and neutral),415 volts, residual current circuit breaker (RCCB), having a sensitivity currentupto 300 milliamperes in the existing MCB DB complete with connections,testing and commissioning etc. as required.

a) 25 Amps Each 142b) 40 Amps Each 20c) 63 Amps Each 52

1.6 Providing and fixing following rating and breaking capacity MCCB in existingcubicle panel board incuding drilling holes in cubicle panel, makingconnections, etc. as required. 100 Amp, 16kA Each 32

TOTAL OF SUBHEAD III CARRIED OVER TO SUMMARY OF ELECTRICALWORKS

Ru-Tech Services Inc. Page-2 Electrical BOQ.xls

Page 8: Electrical BOQ Final

AMOUNTIn Fig. (Rs.) In Words (Rs.)

1 Supplying and fixing cat 5e Information outlet for telephone sockets housed in GI boxes recessed in walls/ partitions/ panelling for telephone outlets Nos. 361

a) Single surface mount/recessed box within jacks (RJ-45) I/O (Cat-6) Nos 361

2 Fish wire of 5 SWG, fixing hardware etc., including cutting,chasing the walls/floor and filling the chased portion and making good the damages etc. complete as required

a) 25 mm dia RM 1000

3 Supplying and drawing the following sizes of anealed tinned electrolytic copper conductor PVC insulated unshielded twisted wires in eisting conduitand making connection on both the ends.

a) Cat -5 cable RM 15000

4 Supply, installation, testing, and commissioning of 24 port Jack Panel Cat 5e cable management system with all material as required.

Nos 285 Supplying and fixing the telephone tag blocks housed in MS boxes

(with hinged cover and duly painted) recessed in wall with adequate knockouts including chase cutting and making the surface good and making connections complete as required

a) 10 pair Nos 200b) 20 pair Nos 1000c) 50 pair Nos 1000

TOTAL OF SUBHEAD IV CARRIED OVER TO SUMMARY OFELECTRICAL WORKS

SUBHEAD-IV: TELEPHONE CONDUITING & WIRING

Sl. No. DESCRIPTION OF ITEM UNIT QTY. UNIT RATE

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls

Page 9: Electrical BOQ Final

AMOUNTIn Fig. (Rs.) In Words (Rs.)

1 Supply, installation, testing and commissioning of category 6 flush mounted information outlets wired according to T568B standard with a faceplate. The plastic shall be high impact, flame retardent & UL- rated thermoplastic with minimum insulation resistance of 500 M Ohm Nos. 657

2 Single surface mount/recessed box withn jacks (RJ-45) I/O (Cat-6)Nos 657

3 fish wire of 6 SWG, fixing hardware etc., including cutting,chasing the walls/floor and filling the chased portion ande making good the damages etc. complete as required

a) 25 mm dia RM 4000

4 Supplying and drawing the following sizes of anealed tinned electrolytic copper conductor PCV insulated unshielded twisted wires in eisting conduitand making connection on both the ends.

a) Cat - 6 cable RM 26280

5 Supply, installation, testing, and commissioning of 24 port Jack Panel Cat 6 cable management system with all material as required.

Nos 22

6 Supply, installation, testing, and commissioning of 24 port switch with all meterial as required Nos 22

7 Supply, installation, testing, and commissioning of 12U rack with all meterial as required Nos 2

8 Supply, installation, testing, and commissioning of 12 port 1000 MBPS core switch with all materials as required . Nos 4

9 Supply, installation, testing, and commissioning of rack server 42U with all meterial as required Nos 3

10 Supply, installation, testing, and commissioning of patch cord 2 meter with all meterial as required Nos 657

SUBHEAD V: DATA NETWORKING

Sl. No. DESCRIPTION OF ITEM UNIT QTY. UNIT RATES

Ru-Tech Services Inc. Page 1 Electrical BOQ.xls

Page 10: Electrical BOQ Final

AMOUNTIn Fig. (Rs.) In Words (Rs.)

SUBHEAD V: DATA NETWORKING

Sl. No. DESCRIPTION OF ITEM UNIT QTY. UNIT RATES

11 Supply, installation, testing, and commissioning of patch cord 5 meter (1 side R445 another side Unterminated)with all meterial as required Nos 657

12 Supply, installation, testing, and commissioning of information outlet(WI-FY)with all material as required Nos 20

13 Supply, installation, testing, and commissioning of UPS system with following features 1. High freq. PWM inverter using IGBT 2. Manual bypass switch 3. Inbuilt Static Switch 4. 80 Character Alpha Numeric LCD display with 5. SMF batteries to provide approx. 2 hours backup time on IT load alongwith battery rack.

a. 8 KVA True on-line, Nos 2b. 20 KVA True on-line, Nos 2c. 25 KVA True on-line, Nos 1d. 40 KVA True on-line, Nos 1

TOTAL OF SUBHEAD V CARRIED OVER TO SUMMARY OFELECTRICAL WORKS

Ru-Tech Services Inc. Page 2 Electrical BOQ.xls

Page 11: Electrical BOQ Final

AMOUNTIn Fig. (Rs.) In Words (Rs.)

1.1 Supply and laying in cable Tray/clamped to wall with suitable clamps saddles and fixing bolts/ in ground including the cost of digging and back filling with sand and brick protection as required and including testing and commissioning of the following sizes of 1.1KV grade multicore aluminium conductor XLPE insulated and PVC sheathed armoured cable conforming to IS : 7098 (Part-I). The costs shall include for all cables to be provided with a 1D gap and shall be properly clamped with cable clamps and ties. Identification tags shall be provided for all cables and route markers for cables in ground as per specifications and as per instructions of Engineer-in-charge.

a) 3.5 core, 185 Sq.mm. Meter 160b) 3.5 core, 150 Sq.mm. Meter 20c) 3.5 core, 120 Sq.mm. Meter 210d) 3.5 core, 70 Sq.mm. Meter 460e) 3.5 core, 50 Sq.mm. Meter 120f) 3.5 core, 35 Sq.mm. Meter 95g) 3.5 core, 25 Sq.mm. Meter 465

1.2 Supply and laying in cable Tray/clamped to wall with suitable clamps saddles and fixing bolts/ in ground including the cost of digging and back filling with sand and brick protection as required and including testing and commissioning of the following sizes of 1.1KV grade multicore aluminium conductor PVC insulated and PVC sheathed armoured cable conforming to IS : 1554 (Part-I). Identification tags shall be provided for all cables and route markers for cables in ground as per specifications and as per instructions of Engineer-in-charge.

a) 4 core, 16 Sq.mm. Meter 2505b) 4 core, 10 Sq.mm. Meter 1580c) 4 core, 6 Sq.mm. Meter 1810d) 4 core, 4 Sq.mm. Meter 4770

SUBHEAD VI: LT CABLES & TERMINATIONS, CABLE TRAYS etc.

UNIT RATESSl . No. DESCRIPTION OF ITEM UNIT QTY.

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls

Page 12: Electrical BOQ Final

AMOUNTIn Fig. (Rs.) In Words (Rs.)

SUBHEAD VI: LT CABLES & TERMINATIONS, CABLE TRAYS etc.

UNIT RATESSl . No. DESCRIPTION OF ITEM UNIT QTY.

1.3 Supply and laying in cable Tray/clamped to wall with suitable clamps saddles and fixing bolts/ in ground as required and including testing and commissioning of the following sizes of 1.1KV grade multicore copper conductor PVC insulated and PVC sheathed un-armoured cable conforming to IS : 1554 (Part-I). Identification tags shall be provided for all cables and route markers for cables in ground as per specifications and as per instructions of Engineer-in-charge.

a) 4 core, 25 Sq.mm. Meter 190b) 4 core, 16 Sq.mm. Meter 240c) 4 core, 10 Sq.mm. Meter 380d) 4 core, 6 Sq.mm. Meter 450e) 4 core, 4 Sq.mm. Meter 3540f) 4 core, 2.5 Sq.mm. Meter 1310

1.4 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/ XLPE aluminium conductor cable of 1.1 KV grade as required.

a) 3.5 core, 185 Sq.mm. Set 6b) 3.5 core, 150 Sq.mm. Set 2c) 3.5 core, 120 Sq.mm. Set 10d) 3.5 core, 70 Sq.mm. Set 19e) 3.5 core, 50 Sq.mm. Set 4f) 3.5 core, 35 Sq.mm. Set 4g) 3.5 core, 25 Sq.mm. Set 18h) 4 core, 16 Sq.mm. Set 102i) 4 core, 10 Sq.mm. Set 64j) 4 core, 6 Sq.mm. Set 72k) 4 core, 4 Sq.mm. Set 258l) 4 core, 2.5 Sq.mm. Set 46

Ru-Tech Services Inc. Page-2 Electrical BOQ.xls

Page 13: Electrical BOQ Final

AMOUNTIn Fig. (Rs.) In Words (Rs.)

SUBHEAD VI: LT CABLES & TERMINATIONS, CABLE TRAYS etc.

UNIT RATESSl . No. DESCRIPTION OF ITEM UNIT QTY.

1.5 Fabrication and installing following size of perforated M.S. cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with M.S. suspenders and including painting with powder coating etc. as required.

a) 375 mm width x 50 mm depth x 2.0 mm thickness Meter 1250b) 150 mm width x 50 mm depth x 1.6 mm thickness Meter 300c) 100 mm width x 50 mm depth x 1.6 mm thickness Meter 350

1.6 Providing & laying in position hume pipes of the following sizes in road crossings, paved areas etc., including collars, joints filled with cement mortar 1:4 (1 Cement :4 Coarse sand ) finished complete as required.

a) 100mm dia Meter 150b) 250mm dia Meter 100

TOTAL OF SUBHEAD VI CARRIED OVER TO SUMMARY OFELECTRICAL WORKS

Ru-Tech Services Inc. Page-3 Electrical BOQ.xls

Page 14: Electrical BOQ Final

AMOUNTIn Fig. (Rs.) In Words (Rs.)

1 Earthing with G.I. earth pipe 4.5 mtr long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) as required.

Set 36

2 Extra for using salt and charcoal for pipe earth electrode as required. Set 36

3 Supplying and laying 25 mm X 5 mm thick G.I. Strip at 0.5 meters below groundas strip earth electrod including soldering etc. as required.

Metre 2350

4 Providing and Fixing 25mm x 5mm GI strip in 40 mm dia G.I. Pipe from earth electrode, as required.

Metre 1800

5 Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface forconnections etc. as required.

Metre 90

TOTAL OF SUBHEAD VII CARRIED OVER TO SUMMARY OF ELECTRICALWORKS

QTY.

SUBHEAD VII: EARTHING

UNIT RATESSl. No.

DESCRIPTION OF ITEM UNIT

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls

Page 15: Electrical BOQ Final

AMOUNTIn Fig. (Rs.) In Words ( Rs.)

1 Supply, installation tested and commissioning of Early streamer Emission basedadvance Lightning Arrestor System made of 304 L stainless steel including supplyand fixing of 1 no. support Mast on top of Mumti complete as required.

Each 62 Supply and fixing GI strip 25 mm x 3 mm along outside wall / columns as vertical

conductors fixing, saddles, screws complete as required. Each 2403 Supply and laying in ground with GI strip 25 mm x 3 mm including the cost of digging

and back filling complete as required for earth pits interconnection complete asrequired. Each 120

4 Providing and making maintenance free earthpits including the cost of 3 nos 16 mmdia 1.2 m long MS earth rods molecularly bonded with 250 micron copper andtreated with 10 kGs ground enhancing back filled chemical TEREC+, all earth work,masonary enclosure with bituminized CI pit cover and frame as per IS 3043: 1987.

Metre 12

TOTAL OF SUBHEAD VIII CARRIED OVER TO SUMMARY OF ELECTRICALWORKS

SUBHEAD VIII: LIGHTENING

QTY. UNIT RATESSl. No. DESCRIPTION OF ITEM UNIT

Ru-Tech Services Inc. Page 1 Electrical BOQ.xls

Page 16: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)1.0 GUEST HOUSE MAIN LT PANEL

Supply, erection, testing and commissioning of LT panel fully compartmentalized (bolted type design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminum busbars complete with following accessories. Set 1Incoming :1 no. 200A FP MCCB Ics=35kA with TMD release.1 No. Multifunction meter with control MCBs. 2 Nos. ON/OFF indicating Lamp3 Nos. phase indication lamps with control fuses.Busbar :250A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :2 Nos. 100 A TP MCCB (Ics=25 kA) 6 Nos. 63 A TP MCCB (Ics=25 kA) All the O/G shall have with ON/OFF indication lamp

1.1 GUEST HOUSE SMB-GF,F/F,S/F,T/FSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 4Incoming1 No. 63 Amp FP MCB(10kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 100A continuous current.Outgoing1Nos. 25 Amp TP MCB2 Nos. 63 Amp TP MCB

1.2 GUEST HOUSE UPS DBSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 1

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls

Page 17: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

Incoming1 No. 63 Amp FP MCB(10kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+2N Busbar(Aluminium) shall be suitable to carry 100A continuous current.Outgoing5 Nos. 25 Amp TP MCB(10kA)

1.3 GUEST HOUSE AC DISTRIBUTION PANELSupply, erection, testing and commissioning of AC Distribution panel fully compartmentalized (bolted type design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminium busbars complete with following accessories. Set 1Incoming :1 No. 200A FP MCCB (Ics=35kA) with TMD release.1 No. Volt meter with Selector switch.1 No. Ammeter with Selector switch. 2 Nos. ON/OFF indicating Lamp.3 Nos. phase indication lamps with control fuses.Busbar :300A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :2 Nos. 100 A TP MCCB (Ics=25 kA) 1 Nos. 63 A TP MCB (Ics=10kA) All the O/G shall have with ON/OFF indication lamp.

2.0 COMMON ACTIVITY MAIN LT PANELSupply, erection, testing and commissioning of LT panel fully compartmentalized (bolted type design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminum busbars complete with following accessories. Set 1Incoming :1 no. 250A FP MCCB Ics=35kA with Electronic release.1 No. Multifunction meter with control MCBs. 2 Nos. ON/OFF indicating Lamp3 Nos. phase indication lamps with control fuses.

Ru-Tech Services Inc. Page-2 Electrical BOQ.xls

Page 18: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

Busbar :300A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :4 Nos. 100 A TP MCCB (Ics=25 kA) 5 Nos. 63 A TP MCCB (Ics=25 kA) All the O/G shall have with ON/OFF indication lamp

2.1 COMMON ACTIVITY SMB-GFSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 100 Amp FP MCCB(25kA) with TMD release1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 125A continuous current.Outgoing2 Nos. 25 Amp TP MCB(10kA)3 Nos. 63 Amp TP MCB(10kA)

2.2 COMMON ACTIVITY SMB-F/F,T/FSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 2Incoming1 No. 63 Amp FP MCB(10kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 100A continuous current.Outgoing2 Nos. 25 Amp TP MCB(10kA)3 Nos. 40 Amp TP MCB(10kA)

Ru-Tech Services Inc. Page-3 Electrical BOQ.xls

Page 19: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

2.3 COMMON ACTIVITY UPS DBSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 1Incoming1 No. 63 Amp FP MCB(10kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+2N Busbar(Aluminium) shall be suitable to carry 100A continuous current.Outgoing3 Nos. 25 Amp TP MCB(10kA)

2.4 COMMON ACTIVITY SOLAR DBSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 1Incoming1 No. 63A Automatic transfer switch1 No. 63 Amp FP MCB(10kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTPN Busbar(Aluminium) shall be suitable to carry 100A continuous current.Outgoing4 Nos. 25 Amp TP MCB(10kA)

2.5 COMMON ACTIVITY AC DISTRIBUTION PANELSupply, erection, testing and commissioning of AC Distribution panel fully compartmentalized (bolted type design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminium busbars complete with following accessories. Set 1Incoming :1No. 300A FP MCCB (Ics=35kA) with TMD release.1 No. Volt meter with Selector switch.1 No. Ammeter with Selector switch.

Ru-Tech Services Inc. Page-4 Electrical BOQ.xls

Page 20: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

2 Nos. ON/OFF indicating Lamp.3 Nos. phase indication lamps with control fuses.Busbar :350A TPN Al Busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :3 Nos. 100 A TP MCCB (Ics=25 kA) 1 Nos. 63 A TP MCB (Ics=10 kA) All the O/G shall have with ON/OFF indication lamp.

3.0 FILM &TV MAIN LT PANELSupply, erection, testing and commissioning of LT panel fully compartmentalized (bolted type design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminum busbars complete with following accessories. Set 1Incoming :1 no. 1000A FP MDO ACB with microprocessor based O/L & S/C Protection1 No. Multifunction meter with control MCBs. 2 Nos. ON/OFF indicating Lamp3 Nos. phase indication lamps with control fuses.Busbar :1250A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :3 Nos. 200 A TP MCCB (Ics=25 kA) 3 Nos. 315 A TP MCCB (Ics=25 kA) 3 Nos. 100 A TP MCCB (Ics=25 kA) All the O/G shall have with ON/OFF indication lamp

3.1 FILM & TV SMB- 2 GFSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 315 Amp FP MCCB(35kA) 1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.

Ru-Tech Services Inc. Page-5 Electrical BOQ.xls

Page 21: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

BusbarsTP+N AL Busbar shall be suitable to carry 400A continuous current.Outgoing5 Nos. 25 Amp TP MCB(10kA)1 Nos. 40 Amp TP MCB(10kA)6 Nos. 63 Amp TP MCB(10kA)

3.2 FILM & TV SMB- 1 GFSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 315 Amp FP MCCB(35kA) 1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 350A continuous current.Outgoing6 Nos. 25 Amp TP MCB(10kA)6 Nos. 63 Amp TP MCB(10kA)

3.3 FILM & TV SMB- FFSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1

Ru-Tech Services Inc. Page-6 Electrical BOQ.xls

Page 22: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

Incoming1 No. 200 Amp FP MCCB(25kA) 1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 250A continuous current.Outgoing2 Nos. 25 Amp TP MCB(10kA)3 Nos. 63 Amp TP MCB(10kA)

3.4 FILM & TV SMB- SFSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 200 Amp FP MCCB(25kA) 1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 250A continuous current.Outgoing6 Nos. 25 Amp TP MCB(10kA)5 Nos. 63 Amp TP MCB(10kA)

3.5 FILM & TV UPS DBSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 1Incoming1 No. 100Amp FP MCCB(Ics=25kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+2N Busbar(Aluminium) shall be suitable to carry 125A continuous current.Outgoing5 Nos. 40 Amp TP MCB(10kA)

Ru-Tech Services Inc. Page-7 Electrical BOQ.xls

Page 23: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

Ru-Tech Services Inc. Page-8 Electrical BOQ.xls

Page 24: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

3.6 FILM & TV UPS SUB-DB-1,Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 1Incoming1 No. 40Amp FP MCB(10kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+2N Busbar(Aluminium) shall be suitable to carry 63A continuous current.Outgoing6 Nos. 20 Amp TP MCB(10kA)

3.7 FILM & TV UPS SUB-DB-2 , 3Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 2Incoming1 No. 40Amp FP MCB(10kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+2N Busbar(Aluminium) shall be suitable to carry 63A continuous current.Outgoing3 Nos. 20 Amp TP MCB(10kA)

3.8 FILM & TV SOLAR DBSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 1Incoming1 No. 100A Automatic transfer switch1 No. 100 Amp FP MCCB(25kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.

Ru-Tech Services Inc. Page-9 Electrical BOQ.xls

Page 25: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

BusbarsTPN Busbar(Aluminium) shall be suitable to carry 125A continuous current.Outgoing5 Nos. 25 Amp TP MCB(10kA)

3.9 FILM &TV AC DISTRIBUTION PANELSupply, erection, testing and commissioning of AC Distribution panel fully compartmentalized (bolted type design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminium busbars complete with following accessories. Set 1Incoming :1 No. 800A FP MDO ACB with microprocessor based O/L & S/C Protection.1 No. Volt meter with Selector switch.1 No. Ammeter with Selector switch. 2 Nos. ON/OFF indicating Lamp.3 Nos. phase indication lamps with control fuses.Busbar :1000A TPN Al Busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :7 Nos. 100 A TP MCCB (Ics=25 kA) 6 Nos. 63 A TP MCB (Ics=10 kA) All the O/G shall have with ON/OFF indication lamp

4.0 PROFESSIONAL STUDIES MAIN LT PANELSupply, erection, testing and commissioning of LT panel fully compartmentalized (bolted type design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminum busbars complete with following accessories. Set 1Incoming :1 no. 630A FP MCCB Ics=35kA with Electronic release.1 No. Multifunction meter with control MCBs. 2 Nos. ON/OFF indicating Lamp3 Nos. phase indication lamps with control fuses.Busbar :800A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.Outgoings :2 Nos. 200 A TP MCCB (Ics=25 kA)

Ru-Tech Services Inc. Page-10 Electrical BOQ.xls

Page 26: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

2 Nos. 150 A TP MCCB (Ics=25 kA) 1 No. 125 A TP MCCB (Ics=25 kA) 2 Nos. 100 A TP MCCB (Ics=25 kA)

Ru-Tech Services Inc. Page-11 Electrical BOQ.xls

Page 27: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

1 No. 63 A TP MCCB (Ics=25 kA) All the O/G shall have with ON/OFF indication lamp

4.1 PROFESSIONAL STUDIES SMB-GFSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 200 Amp FP MCCB(25kA) with TMD release1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 250A continuous current.Outgoing5 Nos. 25 Amp TP MCB(10kA)1 No. 40 Amp TP MCB(10kA)4 Nos. 63 Amp TP MCB(10kA)

4.2 PROFESSIONAL STUDIES SMB-F/FSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 150 Amp FP MCCB(25kA) with TMD release1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 200A continuous current.Outgoing5 Nos. 25 Amp TP MCB(10kA)1 No. 40 Amp TP MCB(10kA)4 Nos. 63 Amp TP MCB(10kA)

Ru-Tech Services Inc. Page-12 Electrical BOQ.xls

Page 28: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

4.3 PROFESSIONAL STUDIES SMB-S-T/FSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 125 Amp FP MCCB(25kA) with TMD release1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 160A continuous current.Outgoing5 Nos. 25 Amp TP MCB(10kA)1 No. 40 Amp TP MCB(10kA)3 Nos. 63 Amp TP MCB(10kA)

4.4 PROFESSIONAL STUDIES UPS DBSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 1Incoming1 No. 100 Amp FP MCCB(25kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+2N Busbar(Aluminium) shall be suitable to carry 150A continuous current.Outgoing5 Nos. 63 Amp TP MCB(10kA)

4.5 PROFESSIONAL STUDIES UPS SUB-DB-1,2,3Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 3Incoming1 No. 63Amp FP MCB(10kA)1 No. Ammeter with control MCBs.

Ru-Tech Services Inc. Page-13 Electrical BOQ.xls

Page 29: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

3 Nos. phase indication lamps with control fuses.BusbarsTP+2N Busbar(Aluminium) shall be suitable to carry 100A continuous current.Outgoing4 Nos. 25 Amp TP MCB(10kA)

4.6 PROFESSIONAL STUDIES SOLAR DBSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 1Incoming1 No. 63A Automatic transfer switch1 No. 63 Amp FP MCB(10kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTPN Busbar(Aluminium) shall be suitable to carry 100A continuous current.Outgoing9 Nos. 25 Amp TP MCB(10kA)

4.7 PROFFESSIONAL STUDY AC DISTRIBUTION PANELSupply, erection, testing and commissioning of AC Distribution panel fully compartmentalized (bolted type design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminium busbars complete with following accessories. Set 1Incoming :1 No. 250A FP MCCB (Ics =35 kA ) with TMD release.1 No. Volt meter with Selector switch.1 No. Ammeter with Selector switch. 2 Nos. ON/OFF indicating Lamp.3 Nos. phase indication lamps with control fuses.Busbar :300A TPN Al Busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :3 Nos. 100 A TP MCCB (Ics=25 kA) 1 Nos. 63 A TP MCB (Ics=10 kA)

Ru-Tech Services Inc. Page-14 Electrical BOQ.xls

Page 30: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

All the O/G shall have with ON/OFF indication lamp.

5.0 FINE ARTS MAIN LT PANELSupply, erection, testing and commissioning of LT panel fully compartmentalized (bolted type design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminum busbars complete with following accessories. Set 1Incoming :1 no. 800A FP MDO ACB with microprocessor based O/L & S/C Protection1 No. Multifunction meter with control MCBs. 2 Nos. ON/OFF indicating Lamp3 Nos. phase indication lamps with control fuses.Busbar :1000A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :3 Nos. 200 A TP MCCB (Ics=25 kA) 3 Nos.160 A TP MCCB (Ics=25 kA) 4 Nos. 100 A TP MCCB (Ics=25 kA) All the O/G shall have with ON/OFF indication lamp

5.1 FINE ARTS SMB- 2 GFSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 200 Amp FP MCCB(25kA) 1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 250A continuous current.Outgoing8 Nos. 63 Amp TP MCB(10kA)

5.2 FINE ARTS SMB- 1 GF

Ru-Tech Services Inc. Page-15 Electrical BOQ.xls

Page 31: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 200 Amp FP MCCB(25kA) 1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 250A continuous current.Outgoing4 Nos. 25 Amp TP MCB(10kA)4 Nos. 63 Amp TP MCB(10kA)

5.3 FINE ARTS SMB- FF , SFSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 2Incoming1 No. 160 Amp FP MCCB(25kA) 1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 200A continuous current.Outgoing4 Nos. 25 Amp TP MCB(10kA)4 Nos. 63 Amp TP MCB(10kA)

5.4 FINE ARTS SMB- TFSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 100 Amp FP MCCB(25kA) 1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.

Ru-Tech Services Inc. Page-16 Electrical BOQ.xls

Page 32: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

BusbarsTP+N AL Busbar shall be suitable to carry 125A continuous current.Outgoing4 Nos. 25 Amp TP MCB(10kA)4 Nos. 63 Amp TP MCB(10kA)

Ru-Tech Services Inc. Page-17 Electrical BOQ.xls

Page 33: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

5.5 FINE ARTS UPS DBSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 1Incoming1 No. 100Amp FP MCCB(Ics=25kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+2N Busbar(Aluminium) shall be suitable to carry 125A continuous current.Outgoing10 Nos. 25 Amp TP MCB(10kA)

5.6 FINE ARTS SOLAR DBSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 1Incoming1 No. 100A Automatic transfer switch1 No. 100 Amp FP MCCB(25kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTPN Busbar(Aluminium) shall be suitable to carry 125A continuous current.Outgoing10 Nos. 25 Amp TP MCB(10kA)

5.7 FINE ARTS AC DISTRIBUTION PANELSupply, erection, testing and commissioning of AC Distribution panel fully compartmentalized (bolted type design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminium busbars complete with following accessories. Set 1Incoming :1 No. 500 A FP MCCB (Ics= 35 kA ) with TMD release.1 No. Volt meter with Selector switch.1 No. Ammeter with Selector switch.

Ru-Tech Services Inc. Page-18 Electrical BOQ.xls

Page 34: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

2 Nos. ON/OFF indicating Lamp.3 Nos. phase indication lamps with control fuses.Busbar :630 A TPN Al Busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :4 Nos. 100 A TP MCCB (Ics=25 kA) 5 Nos. 63 A TP MCB (Ics=10kA) All the O/G shall have with ON/OFF indication lamp

6.0 FASHION DESIGN MAIN LT PANELSupply, erection, testing and commissioning of LT panel fully compartmentalized (bolted type design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminum busbars complete with following accessories. Set 1Incoming :1 no. 1000A FP MDO ACB with microprocessor based O/L & S/C Protection1 No. Multifunction meter with control MCBs. 2 Nos. ON/OFF indicating Lamp3 Nos. phase indication lamps with control fuses.Busbar :1250A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :1 Nos. 125 A TP MCCB (Ics=25 kA) 3 Nos. 315 A TP MCCB (Ics=25 kA) 4 Nos. 200 A TP MCCB (Ics=25 kA) 2 Nos. 160 A TP MCCB (Ics=25 kA) 1 Nos. 100 A TP MCCB (Ics=25 kA) All the O/G shall have with ON/OFF indication lamp

6.1 FASHION DESIGN SMB-1 SFSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 315 Amp FP MCCB(35kA)

Ru-Tech Services Inc. Page-19 Electrical BOQ.xls

Page 35: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 400A continuous current.Outgoing7 Nos. 25 Amp TP MCB(10kA)5 Nos. 40 Amp TP MCB(10kA)3 Nos. 63 Amp TP MCB(10kA)

6.2 FASHION DESIGN SMB-1 GFSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 300 Amp FP MCCB(35kA) 1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 400A continuous current.Outgoing7 Nos. 25 Amp TP MCB(10kA)6 Nos. 40 Amp TP MCB(10kA)2 Nos. 63 Amp TP MCB(10kA)

6.3 FASHION DESIGN SMB-2 GFSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 200 Amp FP MCCB(25kA) 1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 250A continuous current.Outgoing4 Nos. 25 Amp TP MCB(10kA)

Ru-Tech Services Inc. Page-20 Electrical BOQ.xls

Page 36: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

6 Nos. 63 Amp TP MCB(10kA)

Ru-Tech Services Inc. Page-21 Electrical BOQ.xls

Page 37: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

6.4 FASHION DESIGN SMB-FFSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 200 Amp FP MCCB(25kA) 1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 250A continuous current.Outgoing5 Nos. 25 Amp TP MCB(10kA)5 Nos. 63 Amp TP MCB(10kA)

6.5 FASHION DESIGN SMB-2 SFSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 160 Amp FP MCCB(25kA) 1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 200A continuous current.Outgoing4 Nos. 25 Amp TP MCB(10kA)4 Nos. 63 Amp TP MCB(10kA)

6.6 FASHION DESIGN SMB-TFSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections andhaving following incoming and outgoing as per the SLD and specifications . Set 1Incoming1 No. 160 Amp FP MCCB(25kA) 1 No. Ammeter with control MCBs.

Ru-Tech Services Inc. Page-22 Electrical BOQ.xls

Page 38: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

3 Nos. phase indication lamps with control fuses.BusbarsTP+N AL Busbar shall be suitable to carry 200A continuous current.Outgoing4 Nos. 25 Amp TP MCB(10kA)3 Nos. 63 Amp TP MCB(10kA)1 Nos. 40 Amp TP MCB(10kA)

6.7 FASHION DESIGN UPS DBSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 1Incoming1 No. 200Amp FP MCCB(Ics=25kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+2N Busbar(Aluminium) shall be suitable to carry 250A continuous current.Outgoing5 Nos. 63 Amp TP MCB(10kA)

6.8 FASHION DESIGN UPS SUB-DB-1,2Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 2Incoming1 No. 63Amp FP MCB(10kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+2N Busbar(Aluminium) shall be suitable to carry 100A continuous current.Outgoing6 Nos. 25 Amp TP MCB(10kA)

6.9 FASHION DESIGN UPS SUB-DB-3

Ru-Tech Services Inc. Page-23 Electrical BOQ.xls

Page 39: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 1

Ru-Tech Services Inc. Page-24 Electrical BOQ.xls

Page 40: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

Incoming1 No. 63Amp FP MCB(10kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTP+2N Busbar(Aluminium) shall be suitable to carry 100A continuous current.Outgoing9 Nos. 25 Amp TP MCB(10kA)

6.10 FASHION DESIGN SOLAR DBSupply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thickCRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnectionsand having following incoming and outgoing as per the SLD and specifications. Set 1Incoming1 No. 125A Automatic transfer switch1 No. 125 Amp FP MCCB(25kA)1 No. Ammeter with control MCBs. 3 Nos. phase indication lamps with control fuses.BusbarsTPN Busbar(Aluminium) shall be suitable to carry 150A continuous current.Outgoing10 Nos. 25 Amp TP MCB(10kA)

6.11 FASHION DESIGN AC DISTRIBUTION PANELSupply, erection, testing and commissioning of AC Distribution panel fully compartmentalized (bolted type design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminium busbars complete with following accessories. Set 1Incoming :1 No. 1000A FP MDO ACB with microprocessor based O/L & S/C Protection.1 No. Volt meter with Selector switch.1 No. Ammeter with Selector switch. 2 Nos. ON/OFF indicating Lamp.

Ru-Tech Services Inc. Page-25 Electrical BOQ.xls

Page 41: Electrical BOQ Final

AMOUNT

In Fig. (Rs.)In Words

(Rs.)

UNIT RATES

SUBHEAD IX: DISTRIBUTION LT PANELS

Sl. No. DESCRIPTION OF ITEM UNIT QTY.

3 Nos. phase indication lamps with control fuses.Busbar :1000A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :7 Nos. 100 A TP MCCB (Ics=25 kA) 8 Nos. 63 A TP MCB (Ics=10 kA) All the O/G shall have with ON/OFF indication lamp

TOTAL OF SUBHEAD IX CARRIED OVER TO SUMMARY OF ELECTRICAL WORKS

Ru-Tech Services Inc. Page-26 Electrical BOQ.xls

Page 42: Electrical BOQ Final

AMOUNTIn Fig. (Rs.) In Words (Rs.)

1 Supply, Installation, Testing & Commissioning of Microprocessor based addressable Fire Alarm Control Panel with with built-in Battery Back-up for identification of the fire location and fire alarm system control( each Loop consists of 199 devices and 199 detector). The panel shall have 240 volts AC power supply, automatic battery charger, 24 volts, sealed lead acid maintenance free batteries sufficient for 24 hours normal working and then be capable of operating the system for 30 minutes during emergency condition as detailled.

Nos 6

2 Supply installation testing and commossioning of Repeater panelwith LCD display with battery & battery charger completed as perspecification as required. No 26

3 Supply, Installation, Testing & Commissioning of addressable Multi-criteria photo thermal smoke detector including the cost of base plate mounting accessories as per detailed.

Nos 204

4 Supply, Installation, Testing & Commissioning of plug-in type addressable (ROR + Fixed temp) heat detectors including the cost of base plate mounting accessories as per detailed.

Nos 773

5 Supply, Installation, Testing & Commissioning of Addressable type Duct Detector complete as per detailed.

Nos 2

6 Supply, Installation, Testing & Commissioning of Control Modules for trip off of (AHU+Fire Damper etc) and as required. The control module should have 2 independent outputs including the cost of mounting accessories complete as per detailed.

Nos 4

7 Supply, Installation, Testing & Commissioning of Addressable Manual Call Point break glass type with Alarm LED and mounting accessories complete as per detailed.

Nos 60

8 Supply, Installation, Testing & Commissioning of Monitor Module with minimum of 2 monitoring inputs for various applications complete as per detailed.

Nos. 15

SUB-HEAD X: FIRE DETECTION AND ALARM

Sl. No. DESCRIPTION OF ITEM UNIT QTY. UNIT RATES

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls

Page 43: Electrical BOQ Final

AMOUNTIn Fig. (Rs.) In Words (Rs.)

SUB-HEAD X: FIRE DETECTION AND ALARM

Sl. No. DESCRIPTION OF ITEM UNIT QTY. UNIT RATES

9 Supply, Installation, Testing & Commissioning of Hooter including the cost of mounting complete as per detailed.

Nos 63

10 Supply, Installation, Testing & Commissioning of Response indicator complete as per detailed.

Nos 210

11 Supply,Installation ,Testing & Commissioning of Fire exit sign (Illuminated) made from etched sheet with LED illumination and all electrical accessories including battery and battery charger etc. as per detailled.

Nos 88

12 Supplying and fixing of 2X 1.5 sq. mm PVC insulated Copper conductor wire.

RM 14655

13 Supplying and fixing of 4X 1.5 sq. mm PVC insulated Copper conductor wire.

RM 3690

14 Supplying and fixing of following sizes of MS conduit along with theaccessories in surface/ recess including cutting the wall and makinggood the same in case of recessed conduit as required.

a) 25 mm Metre 12842

TOTAL OF SUBHEAD XI OF ELECTRICAL WORKS

Ru-Tech Services Inc. Page-2 Electrical BOQ.xls

Page 44: Electrical BOQ Final

S.NO. Brief Description of Material Name of Approved Makes

1 11 KV VCB PANEL BOARD. SIEMENS / AREVA / ABB / CROMPTON GREAVES / KIRLOSKAR

2 XLPE 11 KV CABLE CCI / UNIVERSAL / NICCO / POLYCAB / HAVELLS

3 HT TERMINATIONS CAB SEAL / RAYCHEM / YAMUNA GAS

4 OIL TYPE TRANSFORMERS CROMPTON GREAVES / EMCO / KIRLOSKAR / ECE / AREVA

5 OLTC OLG / CTR / CROMPTON

6 DIESEL ENGINE CATERPILLAR / CUMMINS / KOHLER / MTU / PERKINS

7 ALTERNATOR STAMFORD / CATERPILLAR / LEROY SOMER & CONTROL

8 BATTERY CHARGER EXPO-FYN / AMAR RAJA / CHHABI ELECTRICALS / VOLSTAT

9 BATTERIES EXCIDE / AMARA RAJA / STANDARD FARRUKAWA / OKAYA

10 CAPACITORS L & T / GE / ABB / EPCOS

11 APFCR L & T / SYSTEM SENSOR / ABB / SIEMENS

12 PROTECTION RELAY SIEMENS / EASUN / ABB / L & T ( PNB - Gold Series)

13 DIGITAL/ MICROPROCESSOR BASED ENERGY METERS

ABB / L & T / NEPTUNE / SECURE / ENERCON / FPI

14 LT CABLES HAVELLS / TECHNOCARE / NICCO / FINOLEX / POLYCAB / ECHO / SKYTONE / LAPP CABLE

15 PVC INSULATED WIRES HAVELLS / TECHNOCARE / NICCO / FINOLEX / POLYCAB / ECHO / SKYTONE / LAPP CABLE

16 CAT - 6 CABLES AWAYA / LAPPCABLE

17 RG - 6 / RG - 11 COMSOB / SKYLINE / PLYCAB

18 TELEPHONE TAG BLOCKS MK / L K FUGA / CLIPSAL / LEGRAND / KRON

19 CABLE TRAY PILCO / UBITECH / RICO STEEL / STEELCO

LIST OF APPROVED MANUFACTURERS

Page 45: Electrical BOQ Final

S.NO. Brief Description of Material Name of Approved Makes

LIST OF APPROVED MANUFACTURERS

20 CABLE COMPRESSION GLANDS COMET / PEECO / RAYCHEM

21 CABLE LUGS DOWELS / RAYCHEM

22 MODULAR RANGE OF SWITCHES, SOCKET

HONEY WELL / CLIPSAL / LEGRAND / CRABTREE / HAVELLS

23 INDUSTRIAL SOCKET & PLUGS INDO ASIAN / SIEMENS / SCHNEIDER / CROMPTON / LEGRAND/ BCH / HAGGER

24 STEEL CONDUIT BEC / AKG / STEEL KRAFT

25 LIGHT FIXTURES PHILIPS / BAJAJ / CROMPTON / HAVELLS / THORN

26 CEILING FANS CROMPTON GREAVES / HAVELLS / USHA / KHAITAN

27 EXHAUST FAN CROMPTON GREAVES / USHA / KHAITAN / HAVELLS

28 MV PANELS TRICOLITE / MILESTONE SWITCHGEARS / MADHUELECTRICALS/ UBITECH / CONTROLS & SWITCHGEARS

29 BUSDUCTS / RISING MAIN TRICOLITE / MILESTONE SWITCHGEARS / MADHUELECTRICALS/ UBITECH / CONTROLS & SWITCHGEARS / ZETA

30 AIR CIRCUIT BREAKER L & T (U Power ) / SIEMENS / ABB / SCHNEIDER( MASTERPACK)

31 MCCB SCHNEIDER (COMPAC) / SIEMENS / HAGGER / ABB / LEGRAND

32 MCB-DB's, MCB, ELCB MCB-Isolator etc.SCHNEIDER (COMPAC) / SIEMENS / L & T / ABB / LEGRAND / INDOASIAN / HAVELLS / MK

33 FSU/SDFU/SFU L & T/ ABB / SIEMENS / HAVELLS / C & S

34 Power Contactors L & T/ ABB / SIEMENS / SCHNEIDER / C & S

35 Measuring Instruments AE / MECO / Rishline (L & T) / RAAS ControlsNOTE:1. Above makes of materials are approved subject to their meeting the tender specifications & requirements. Contractor however shall seek approval of specific make from the engineer incharge before commencement the work. The final choice of make to be used in the work will rest with RITES and the decision of the Engineer -in-charge shall be final & binding on

the contractor.2. For any item not covered in the above list, the contractor shall get the make & sample

approved from the Engineer-in-charge before procurement. The final choice of make to be used in the work will rest with RITES and the decision of the engineer -in-charge shall be

final & binding on the contractor in this respect.