UG DB CONDUIT PLAN SYMBOLS XX-XXX SWITCHES, OUTLETS, & TELECOM SYMBOLS: GROUNDING / LIGHTNING PROTECTION SYMBOLS: INTERIOR AND EXTERIOR LIGHTING SYMBOLS: MISC. ELECTRICAL DEVICES: CATHODIC PROTECTION SYMBOLS: FIRE ALARM DEVICE SYMBOLS: CONDUIT PLAN SYMBOLS: GROUND CONDUCTOR (SIZE AS INDICATED ON DRAWING) GROUND CONNECTION TO EQUIPMENT OR STEEL BOLTED CONNECTION TO EQUIPMENT OR STEEL EXOTHERMIC CONNECTION GROUND ROD 3/4" X 10'-0" (UNLESS NOTED OTHERWISE) GROUND TEST WELL GROUND PLATE CAST IN FOUNDATION, WALL, OR FLOOR GROUND CONDUCTOR TURNING DOWN FROM KEY ELEVATION GROUND CONDUCTOR TURNING UP FROM KEY ELEVATION GROUND CONDUCTOR CONTINUING THROUGH KEY ELEVATION GROUND CONDUCTOR, 6'-0" COIL (FOR CONNECTION TO EQUIPMENT) GROUND CONDUCTOR, 6'-0" LOOP (FOR FUTURE GRID EXTENSION) AIR TERMINAL (3/8" X 24") DOWN CONDUCTOR & GROUND ROD FIRE ALARM MANUAL PULL STATION FIRE ALARM HORN FIRE ALARM BELL FIRE ALARM FLASHING LIGHT FIRE ALARM CHIME FIRE VISUAL SIGNAL WATER FLOW ALARM SWITCH FIRE ALARM SHUTTER RELEASE FIRE ALARM DOOR HOLDER SMOKE DETECTOR HEAT DETECTOR DETECTOR - IONIZATION '(7(&725 &20% ),;(' 7(03 5$7( 2) 5,6( '(7(&725 &20% ),;(' 7(03 5$7( 2) 5,6( )$ '(7(&725 ),;(' 7(03(5$785( )$ '(7(&725 ),;(' 7(03(5$785( )$ '(7(&725 ),;(' 7(03(5$785( DETECTOR - SMOKE PHOTOELECTRIC FIRE ALARM RELAY FIRE ALARM SUPERVISED VALVE FIRE ALARM CONTROL PANEL FIRE ALARM ANNUNCIATOR F F F F F L FS R R S H I P EXPOSED CONDUIT CONCEALED CONDUIT UNDERGROUND CONDUIT DIRECT BURIAL CABLE UNDERGROUND DUCT BANK SURFACE PLUG STRIP CAPPED CONDUIT CONDUIT TURNED UP CONDUIT TURNED DOWN UNION FLEX CONDUIT CONDUIT "T" FITTING CONDUIT FITTING CONDUIT SEAL FITTING (EYS) INSTRUMENT TAG NUMBER MOTOR TAG NUMBER MOTOR TAG NUMBER (VFD) CIRCUIT NUMBER CALLOUT RACEWAY NUMBER CALLOUT: EQUIPMENT TAG NUMBER ONE-LINE SYMBOLS: CATHODIC PROTECTION FIELD TEST STATION - IDENTIFICATION TAG NUMBER AS INDICATED "A" INDICATES ABOVEGROUND TYPE "F" INDICATES FLUSH MOUNTED TYPE "C" INDICATES THAT A PERMANENT REFERENCE ELECTRODE IS CONNECTED. CATHODIC PROTECTION ANODE "I" INDICATES IMPRESSED CURRENT TYPE "G" INDICATES GALVANIC TYPE CATHODIC PROTECTION EQUIPMENT - IDENTIFICATION TAG NUMBER AS INDICATED "R" INDICATES RECTIFIER "P" INDICATES POLARIZATION CELL "N" INDICATES NEGATIVE TERMINAL JUNCTION BOX "A" INDICATES ANODE JUNCTION BOX 00 XX G R01 SUBSCRIPT APPLIED TO ANY SYMBOL INDICATES THE FOLLOWING: FAR FAV FACP FAAP SINGLE RECEPTACLE: 20A, 120V, 3W, 2P (5-20R) DUPLEX RECEPTACLE - RECEPTACLE: 20A, 120V, 3W, 2P (5-20R) DUPLEX RECEPTACLE - SAFETY TYPE: 20A, 120V, 3W, 2P (5-20R) DUPLEX RECEPTACLE - BOTTOM HALF SWITCHED DUPLEX RECEPTACLE - FLOOR (F) OR CEILING (C) MOUNT TWIST LOCK RECEPTACLE DOUBLE DUPLEX RECEPTACLE: 20A, 120V, 3W, 2P (5-20R) DOUBLE DUPLEX RECEPTACLE - FLOOR (F) OR CEILING (C) MOUNT WELDING RECEPTACLE SPECIAL RECEPTACLE - NEMA 6-30R (UNLESS OTHERWISE NOTED) DRYER RECEPTACLE - NEMA 14-30R STOVE RECEPTACLE NEMA 14-50R (MTD @ 48": A.F.F) SINGLE POLE SWITCH: 2 - DOUBLE POLE SWITCH 3 - THREE WAY SWITCH 4 - FOUR WAY SWITCH TE - THERMAL ELEMENT O - OCCUPANCY SENSOR D - DIMMING AD - AUTOMATIC DOOR MC - MOMENTARY CONTACT TELEPHONE OUTLET DATA OUTLET COMBINATION TELEPHONE - DATA OUTLET FLOOR MOUNTED TELEPHONE OUTLET FLOOR MOUNTED DATA OUTLET FLOOR MOUNTED COMBINATION TELEPHONE / DATA OUTLET TELEVISION OUTLET TELEPHONE TERMINAL CABINET DATA RACK INTERCOM: LETTERS DENOTE DI - DOOR INTERCOM MI - MASTER INTERCOM IC - INTERCOM STATION PUSHBUTTON (TYPE AS NOTED) DOOR CHIME CEILING SPEAKER WALL SPEAKER VOLUME CONTROL CLOCK OUTLET DOOR SWITCH REMOTE AMPLIFIER PAGING TERMINAL CABINET NARROW ANGLE SPEAKER NARROW ANGLE SPEAKER, (C) FLUSH CEILING MOUNT NARROW ANGLE SPEAKER WITH AMPLIFIER WALL MOUNT HANDSET HAND SWITCH CEILING MOUNTED SECURITY CAMERA WALL MOUNTED SECURITY CAMERA CARD READER XX XX XX T T TTC DRC XX TV C S V RA PTC C XX XX XX XX XX XX XX XX S XX XX OS OS 48" FLUORESCENT STRIP LIGHT (LETTER DENOTES TYPE) 48" FLUORESCENT STRIP EMERGENCY LIGHT (LETTER DENOTES TYPE) 1'X3' FLUORESCENT LIGHT (LETTER DENOTES TYPE) 1'X3' FLUORESCENT EMERGENCY LIGHT (LETTER DENOTES TYPE) 16"x4' FLUORESCENT LIGHT (LETTER DENOTES TYPE) 16"x4' FLUORESCENT LIGHT - EMERGENCY EGRESS LIGHT (LETTER DENOTES TYPE) 2'x4' FLUORESCENT LIGHT (LETTER DENOTES TYPE) 2'x4' FLUORESCENT LIGHT - EMERGENCY EGRESS LIGHT (LETTER DENOTES TYPE) 2'x2' FLUORESCENT LIGHT (LETTER DENOTES TYPE) 2'X2' FLUORESCENT LIGHT (LETTER DENOTES TYPE) 1'x4' FLUORESCENT LIGHT - PENDANT OR SURFACE MOUNT (LETTER DENOTES TYPE) 1'X4' FLUORESCENT EMERGENCY LIGHT - PENDANT OR SURFACE MOUNT (LETTER DENOTES TYPE) 1'X8' FLUORESCENT LIGHT (LETTER DENOTES TYPE) 1'X8' FLUORESCENT LIGHT - EMERGENCY EGRESS LIGHT (LETTER DENOTES TYPE) WALLPACK FIXTURE (LETTER DENOTES TYPE) INCANDESCENT - METAL HALIDE, OR HIGH PRESSURE SODIUM LIGHTING FIXTURE (LETTER DENOTES TYPE) WALL MOUNT LIGHTING FIXTURE (LETTER DENOTES TYPE) TRACK HEAD OR FLOOD LIGHT (ARROW INDICATES DIRECTION) EXIT LIGHT - CEILING MOUNT (SHADING INDICATES FIXTURE FACES) (DO NOT SWITCH OR CONNECT TO LIGHTING CONTROL PANEL) EXIT LIGHT - WALL MOUNT (SHADING INDICATES FIXTURE FACES) (DO NOT SWITCH OR CONNECT TO LIGHTING CONTROL PANEL) EMERGENCY LIGHT (LETTER DENOTES TYPE) (DO NOT SWITCH OR CONNECT TO LIGHTING CONTROL PANEL) 2 BULB INCANDESCENT WALL MOUNT INCANDESCENT DIRECTIONAL PENDANT POLE MOUNTED FIXTURE - ROUND (LETTER DENOTES TYPE) POLE MOUNTED FIXTURE - SQUARE (LETTER DENOTES TYPE) OCCUPANCY SENSOR - CEILING MOUNT OCCUPANCY SENSOR - WALL MOUNT A A A XX XX J JUNCTION BOX MOTOR NON-FUSED DISCONNECT SWITCH FUSED DISCONNECT SWITCH COMBINATION MOTOR STARTER CONDULET PULLBOX DRY-TYPE TRANSFORMER VARIABLE FREQUENCY DRIVE (VFD) START - STOP PUSHBUTTON POWER PANEL (PPL) LIGHTING PANEL (LPL) MAIN DISTRIBUTION PANEL OR SWITCHBOARD (MDP) UNIT HEATER - VERTICAL (UHT) - DUCT HEATER (DHT) - CABINET HEATER (CHT) LIGHTING CONTRACTOR M C P T VFD MDP LC FUSE (TYPE, SIZE, AND FRAME SHOWN AS INDICATED) NON-FUSED DISCONNECT SWITCH (TYPE, SIZE, AND FRAME SHOWN AS INDICATED) FUSED DISCONNECT SWITCH (SIZE AS INDICATED) HV FUSED CUTOUT SWITCH (TYPE, SIZE, AND FRAME SHOWN AS INDICATED) DRAWOUT LOW VOLTAGE POWER CIRCUIT BREAKER (TYPE TRIP AND FRAME SIZE SHOWN) FIXED LOW VOLTAGE POWER CIRCUIT BREAKER (TYPE TRIP AND FRAME SIZE SHOWN) DRAWOUT HIGH VOLTAGE POWER CIRCUIT BREAKER (TYPE TRIP AND FRAME SIZE SHOWN) FIXED HIGH VOLTAGE POWER CIRCUIT BREAKER (TYPE TRIP AND FRAME SIZE SHOWN) THREE PHASE MOTOR CONTACTOR - STARTER (TYPE AND NEMA SIZE SHOWN) MOTOR OVERLOAD RELAY (TYPE AS SHOWN) VARIABLE FREQUENCY DRIVE SOFT START CONTROLLER ELECTRICAL PANELBOARD (SEE PANELBOARD SCHEDULES FOR DETAILS) LOCAL DISCONNECT SWITCH - NON FUSED LOCAL DISCONNECT SWITCH - FUSED POWER TRANSFORMER WITH VOLTAGES, TRANSFORMER SIZE, AND IMPEDANCE AS INDICATED CONTROL POWER TRANSFORMER CURRENT TRANSFORMER WITH POLARITY MARKING (RATING SHOWN) GROUND CURRENT TRANSFORMER (RATING SHOWN) POTENTIAL TRANSFORMER (NUMBER OF PT'S & RATING SHOWN) CT SHORTING BLOCK DELTA CONNECTION WYE CONNECTION CAPACITOR LIGHTNING / SURGE ARRESTER (RATING INDICATED) GROUND BATTERY MOTOR (HORSEPOWER & FLA SHOWN) GENERATOR (PHASE ROTATION SHOWN) HAND - OFF - AUTO PUSHBUTTON XXX XXX XXX XXX XXX XXX XXX XXX XXX XXX VFD XXX RVS XXX PNL XXX XXX XXX XXX SB XXX XXX XXX XXX XXX A B C S S 2 S 3 S 4 S TE S O S D S AD S MC H O A AREA CLASSIFICATION: AREA CLASSIFICATION KEY NON-HAZARDOUS - NEMA 1 NON-HAZARDOUS - NEMA 4 HAZARDOUS AREA - CLASS I, DIV. 1, GROUP D (TEMPERATURE RATING BETWEEN T2D-T6) HAZARDOUS AREA - CLASS I, DIV. 2, GROUP D (TEMPERATURE RATING BETWEEN T2D-T6) HAZARDOUS AREA - CLASS II, DIV. 1, GROUP G (TEMPERATURE RATING BETWEEN T3A-T6) HAZARDOUS AREA - CLASS II, DIV. 2, GROUP G (TEMPERATURE RATING BETWEEN T3A-T6) X XXX D U XX-XXX SYMBOL IDENTIFICATION SEQUENCE NUMBER RACEWAY TYPE: C: CONDUIT T: TRAY DB: DUCTBANK RACEWAY NUMBER DESCRIPTION: XX-XXX VOLTAGE LEVEL: P: POWER C: CONTROL COMC: COMMUNICATIONS 120V/277V, 20A CIRCUIT TO PANEL AND BREAKER INDICATED. SHORT DASH INDICATES SWITCHED OR "HOT" CONDUCTOR, LONG DASH INDICATES NEUTRAL, ARC INDICATES GROUND. (3 #12 AWG AND 3/4" RGS CONDUIT) 208V/240V, 20A CIRCUIT TO PANEL AND BREAKER INDICATED. SHORT DASHES INDICATES SWITCHED OR "HOT" CONDUCTORS, ARC INDICATES GROUND. (3 #12 AWG AND 3/4" RGS CONDUIT) 208V/480V 3PHASE 20A, CIRCUIT TO PANEL AND BREAKER INDICATED. SHORT DASHES INDICATES SWITCHED OR "HOT" CONDUCTORS, ARC INDICATES GROUND. (4 #12 AWG AND 3/4" RGS CONDUIT) XX-XXX SEQUENCE NUMBER CIRCUIT TYPE: P0: LOW VOLTAGE POWER CIRCUIT P1: 120V POWER CIRCUIT P2: 208/277V POWER CIRCUIT P4: 480V POWER CIRCUIT P5: 5KV POWER CIRCUIT CA: ANALOG CONTROL CIRCUIT GMC: COMMUNICATIONS CIRCUIT CD: DISCRETE CONTROL CIRCUIT CIRCUIT NUMBER DESCRIPTION: PPL-XX, CKT XX PPL-XX, CKT XX PPL-XX, CKT XX EP EXPLOSION PROOF: (CLASS 1, DIV 1) CR CORROSION RESISTANT P PILOT LIGHT K KEY OPERATED IG ISOLATED GROUND NL ILLUMINATED FU FUSED EMT ELECTRICAL METALLIC TUBING RGS RIGID GALVANIZED STEEL RAC RIGID ALUMINUM CONDUIT SSI SAFETY SWITCH INTERLOCK LSH HIGH LEVEL SWITCH LSL LOW LEVEL SWITCH SS SPEED SWITCH XV DISCRETE VALVE ZV MULTIPORT VALVE FV FLOW VALVE LV LEVEL VALVE CP CONTROL PANEL SB SUMMING BOX WE WEIGHT ELEMENT TT TEMPERATURE TRANSMITTER TV TEMPERATURE VALVE LT LEVEL TRANSMITTER PIT PRESSURE INDICATING TRANSMITTER PT PRESSURE TRANSMITTER LIT LEVEL INDICATING TRANSMITTER FC FLOW CONTROLLER FIC FLOW INDICATING CONTROLLER VFD VARIABLE FREQUENCY DRIVE ONE-LINE SYMBOLS CONTINUED: START - STOP PUSHBUTTON INDICATING LIGHT (COLOR AS SHOWN) DEVICE AS DEFINED BY ANSI NUMBER COMBINATION RELAY DEVICE (FUNCTIONS AS DEFINED BY ANSI NUMBER) METER (LETTER INDICATES TYPE) A - AMMETER V - VOLTMETER W - WATTMETER WH - WATT HOUR METER G 86 XXX X S S 50 51 50G DRAFTING SYMBOLS: UP DN SPAN GRATING SLOPE DETAIL CALL OUT SECTION CUT ELEVATION ELEVATION INDICATOR BUILDING COLUMN STAIR UP OR DOWN BAR GRATING SPAN SLOPE DIRECTION (DOWN) KEY NOTE TIE IN POINT UTILITY FEED REVISION CLOUD & DELTA CONTINUATION 1 TIP 1 1 1 GA_._ 1 X- 1 X-? EL. = 100'-0" DESCRIPTION 1 HP XXX XXX SUBSCRIPT APPLIED TO ANY SYMBOL INDICATES THE FOLLOWING: C CEILING MOUNTED F FLOOR MOUNTED GFCI GROUND FAULT CIRCUIT INTERRUPTER RP RAIN PROOF NEMA TYPE 3R OR EQUIVALENT WT WATER TIGHT NEMA TYPE 4 OR EQUIVALENT DT DUST/IGNITION PROOF: (CLASS 2, DIV 1) EP EXPLOSION PROOF: (CLASS 1, DIV 1) C XX C CR PI XXX M XX M XX 1 0 31-05-2013 ISSUED FOR CONSTRUCTION HEIGHTS ARE TO CENTER LINE UNLESS OTHERWISE NOTED ON THE DRAWINGS. ALL DEVICES TO BE RECESSED UNLESS OTHERWISE NOTED ON THE DRAWINGS. MOUNTING HEIGHTS SHALL CONFORM TO ADA REQUIREMENTS RECEPTACLES IN FINISHED SPACES +18" AFF WIREMOLD AND RECEPTACLES ABOVE COUNTERTOP 4" ABOVE BACKSPLASH OR +34" AFF SWITCHES +44"(ADA) AFF THERMOSTATS +60" AFF FIRE ALARM HORN, HORN STROBE, +80" AFF STROBE OR CHIME PANELBOARDS TO TOP +72" AFF CABINETS TO TOP +72" AFF DISCONNECTS, STARTERS +60" AFF TELEPHONE/DATA OUTLETS +18" AFF CLOCKS, CLOCK HANGER RECEPTACLES +62" AFF CATV, TV OUTLETS AND RECEPTACLES +78" AFF MANUAL FIRE ALARM PULL STATIONS +44' AFF (ADA) WALL MTD NURSE CALL CORRIDOR DOME LIGHT +78" AFF NURSE CALL CEILING DOME LIGHT IN CEILING WALL MTD SPEAKERS +78" AFF CEILING MTD SPEAKERS IN CEILING RECEPTACLES IN MECHANICAL ROOMS +48" AFF NURSE CALL EMERGENCY PULL STATIONS +44" AFF(ADA) STAFF DUTY STATIONS AND BEDSIDE STATIONS REMOTE INDICATING LIGHTS +78" AFF OR IN CEILING FIRE ALARM ANNUNCIATOR PANELS +62" AFF NURSE CALL ANNUNCIATOR PANELS +48" AFF GRAPHIC ZONE MAPS +62" AFF BUZZERS, KEYPADS, VOLUME +44" AFF CONTROL SWITCHES DOORBELL CHIMES ETC. +78" AFF NOTE: NOT ALL DEVICES MAY BE SHOWN ON THE DRAWINGS. THIS IS A MASTER MOUNTING HEIGHT SCHEDULE SHOWING TYPICAL DEVICES. SEE DRAWINGS FOR ACTUAL DEVICES USED. ALL MOUNTING HEIGHTS FOR OTHER DEVICES NOT SHOWN ON THIS SCHEDULE SHALL BE AS SHOWN ON THE DRAWINGS. THIS SCHEDULE IS BASED UPON CEILING HEIGHTS 8'-0" OR HIGHER; WHERE LOWER CEILING HEIGHTS OR EXISTING CONDITIONS DICTATE, ADJUST MOUNTING HEIGHTS ACCORDINGLY. MOUNTING HEIGHTS: 1. ALL ELECTRICAL EQUIPMENT AND ENCLOSURES SHALL BE SUITABLE FOR THE AREA CLASSIFICATION IN WHICH IT IS LOCATED AS FOLLOWS: 1.1. NEMA 1 - INDOOR GENERAL USE IN DRY AREAS. 1.2. NEMA 12 FOR UNCLASSIFIED AREAS, EQUIPMENT ROOMS UNLESS OTHERWISE SPECIFIED-DUSTTIGHT AND DRIPTIGHT. 1.3. NEMA 4 FOR WET AREAS SUBJECT TO HOSEDOWN-WATERTIGHT AND DUST TIGHT. 1.4. NEMA 4X (STAINLESS STEEL-CROUSE HINDS "KRYDON" OR APPROVED EQUAL) FOR CORROSIVE AREAS-WATERTIGHT, DUST TIGHT AND CORROSION RESISTANT. 1.5. NEMA TYPE 7 AND 9 FOR CLASS I, DIVISION I, GROUPS C AND D AND CLASS II, DIVISION I, GROUPS E, F, AND G HAZARDOUS LOCATIONS, RESPECTIVELY-CAST ALUMINUM ENCLOSURES. 1.6. NEMA 3R FOR AREAS LOCATED OUTDOORS AND/OR OTHERWISE SPECIFIED AS WEATHERPROOF(WP)-RAINTIGHT. ELECTRICAL ENCLOSURE RATINGS: SUBSCRIPT APPLIED TO ANY SYMBOL INDICATES THE FOLLOWING CONTINUED: AV AUTOMATED VALVE PV PRESSURE VALVE TIT TEMPERATURE INDICATING TRANSMITTER ZS LIMIT SWITCH HS HAND SHAKE YI SKID INDICATOR XA SKID ALARM M MOTOR STARTER FT FLOW TRANSMITTER FIT FLOW INDICATING TRANSMITTER MARK DESCRIPTION DATE Chicago Lumber Warehouse Facility 1234 South 14th Street Omaha, Nebraska 68102 C:/R&A/projects/0901chicagolumb/Drawings/Drawing Set I1.02 ELDON E. JENSEN II E-13155 06-06-2013 3635 South 149th Street Omaha, NE. 68144 P (402) 884-8650 F (402) 884-8651 www.eadengineering.com 3635 South 149th Street Omaha, NE. 68144 P (402) 884-8650 F (402) 884-8651 www.eadengineering.com
Transcript
Page 1: E5bidroom.net/lundross/2013-06-27/4 electrical drawings.pdfxxx xxx xxx a b c s s 2 s 3 s 4 s te s o s d s ad s mc h o a area classification: area classification key non-hazardous -

UG

DB

CONDUIT PLAN SYMBOLS

XX-XXX

SWITCHES, OUTLETS, & TELECOM SYMBOLS:

GROUNDING / LIGHTNING PROTECTION SYMBOLS:

INTERIOR AND EXTERIOR LIGHTING SYMBOLS:

MISC. ELECTRICAL DEVICES:

CATHODIC PROTECTION SYMBOLS:

FIRE ALARM DEVICE SYMBOLS:

CONDUIT PLAN SYMBOLS:

GROUND CONDUCTOR (SIZE AS INDICATED ON DRAWING)

GROUND CONNECTION TO EQUIPMENT OR STEEL

BOLTED CONNECTION TO EQUIPMENT OR STEEL

EXOTHERMIC CONNECTION

GROUND ROD 3/4" X 10'-0" (UNLESS NOTED OTHERWISE)

GROUND TEST WELL

GROUND PLATE CAST IN FOUNDATION, WALL, OR FLOOR

GROUND CONDUCTOR TURNING DOWN FROM KEYELEVATION

GROUND CONDUCTOR TURNING UP FROM KEY ELEVATION

GROUND CONDUCTOR CONTINUING THROUGH KEYELEVATION

GROUND CONDUCTOR, 6'-0" COIL (FOR CONNECTION TOEQUIPMENT)

GROUND CONDUCTOR, 6'-0" LOOP (FOR FUTURE GRIDEXTENSION)

AIR TERMINAL (3/8" X 24")

DOWN CONDUCTOR & GROUND ROD

FIRE ALARM MANUAL PULL STATION

FIRE ALARM HORN

FIRE ALARM BELL

FIRE ALARM FLASHING LIGHT

FIRE ALARM CHIME

FIRE VISUAL SIGNAL

WATER FLOW ALARM SWITCH

FIRE ALARM SHUTTER RELEASE

FIRE ALARM DOOR HOLDER

SMOKE DETECTOR

HEAT DETECTOR

DETECTOR - IONIZATION

DETECTOR - 135° COMB FIXED TEMP & RATE OF RISE

DETECTOR - 190° COMB FIXED TEMP & RATE OF RISE

F.A. DETECTOR - 135° FIXED TEMPERATURE

F.A. DETECTOR - 190° FIXED TEMPERATURE

F.A. DETECTOR - 250° FIXED TEMPERATURE

DETECTOR - SMOKE PHOTOELECTRIC

FIRE ALARM RELAY

FIRE ALARM SUPERVISED VALVE

FIRE ALARM CONTROL PANEL

FIRE ALARM ANNUNCIATOR

F

F

F

F

F

L

FS

R

R

S

H

I

P

EXPOSED CONDUIT

CONCEALED CONDUIT

UNDERGROUND CONDUIT

DIRECT BURIAL CABLE

UNDERGROUND DUCT BANK

SURFACE PLUG STRIP

CAPPED CONDUIT

CONDUIT TURNED UP

CONDUIT TURNED DOWN

UNION

FLEX CONDUIT

CONDUIT "T" FITTING

CONDUIT FITTING

CONDUIT SEAL FITTING (EYS)

INSTRUMENT TAG NUMBER

MOTOR TAG NUMBER

MOTOR TAG NUMBER (VFD)

CIRCUIT NUMBER CALLOUT

RACEWAY NUMBER CALLOUT:

EQUIPMENT TAG NUMBER

ONE-LINE SYMBOLS:

CATHODIC PROTECTION FIELD TEST STATION - IDENTIFICATIONTAG NUMBER AS INDICATED

"A" INDICATES ABOVEGROUND TYPE"F" INDICATES FLUSH MOUNTED TYPE"C" INDICATES THAT A PERMANENT REFERENCEELECTRODE IS CONNECTED.

CATHODIC PROTECTION ANODE

"I" INDICATES IMPRESSED CURRENT TYPE"G" INDICATES GALVANIC TYPE CATHODIC

PROTECTION EQUIPMENT - IDENTIFICATION TAG NUMBER ASINDICATED

"R" INDICATES RECTIFIER"P" INDICATES POLARIZATION CELL"N" INDICATES NEGATIVE TERMINAL JUNCTION BOX"A" INDICATES ANODE JUNCTION BOX

00XX

G

R01

SUBSCRIPTAPPLIED TO ANY SYMBOL INDICATES THE FOLLOWING:

FAR

FAV

FACP

FAAP

SINGLE RECEPTACLE: 20A, 120V, 3W, 2P (5-20R)

DUPLEX RECEPTACLE - RECEPTACLE: 20A, 120V, 3W, 2P (5-20R)

DUPLEX RECEPTACLE - SAFETY TYPE: 20A, 120V, 3W, 2P (5-20R)

DUPLEX RECEPTACLE - BOTTOM HALF SWITCHED

DUPLEX RECEPTACLE - FLOOR (F) OR CEILING (C) MOUNT

TWIST LOCK RECEPTACLE

DOUBLE DUPLEX RECEPTACLE: 20A, 120V, 3W, 2P (5-20R)

DOUBLE DUPLEX RECEPTACLE - FLOOR (F) OR CEILING (C)MOUNT

WELDING RECEPTACLE

SPECIAL RECEPTACLE - NEMA 6-30R (UNLESS OTHERWISENOTED)

DRYER RECEPTACLE - NEMA 14-30R

STOVE RECEPTACLE NEMA 14-50R (MTD @ 48": A.F.F)

SINGLE POLE SWITCH:

2 - DOUBLE POLE SWITCH

3 - THREE WAY SWITCH

4 - FOUR WAY SWITCH

TE - THERMAL ELEMENT

O - OCCUPANCY SENSOR

D - DIMMING

AD - AUTOMATIC DOOR

MC - MOMENTARY CONTACT

TELEPHONE OUTLET

DATA OUTLET

COMBINATION TELEPHONE - DATA OUTLET

FLOOR MOUNTED TELEPHONE OUTLET

FLOOR MOUNTED DATA OUTLET

FLOOR MOUNTED COMBINATION TELEPHONE / DATA OUTLET

TELEVISION OUTLET

TELEPHONE TERMINAL CABINET

DATA RACK

INTERCOM:LETTERS DENOTE

DI - DOOR INTERCOM

MI - MASTER INTERCOM

IC - INTERCOM STATION

PUSHBUTTON (TYPE AS NOTED)

DOOR CHIME

CEILING SPEAKER

WALL SPEAKER

VOLUME CONTROL

CLOCK OUTLET

DOOR SWITCH

REMOTE AMPLIFIER

PAGING TERMINAL CABINET

NARROW ANGLE SPEAKER

NARROW ANGLE SPEAKER, (C) FLUSH CEILING MOUNT

NARROW ANGLE SPEAKER WITH AMPLIFIER

WALL MOUNT HANDSET

HAND SWITCH

CEILING MOUNTED SECURITY CAMERA

WALL MOUNTED SECURITY CAMERA

CARD READER

XX

XX

XX

T

T

TTC

DRC

XX

TV

C

S

V

RA

PTC

C

XX

XX

XX

XX

XX

XX

XX

XX

S

XX

XX

OS

OS

48" FLUORESCENT STRIP LIGHT (LETTER DENOTESTYPE)

48" FLUORESCENT STRIP EMERGENCY LIGHT (LETTERDENOTES TYPE)

1'X3' FLUORESCENT LIGHT (LETTER DENOTES TYPE)

1'X3' FLUORESCENT EMERGENCY LIGHT (LETTERDENOTES TYPE)

16"x4' FLUORESCENT LIGHT (LETTER DENOTES TYPE)

16"x4' FLUORESCENT LIGHT - EMERGENCY EGRESSLIGHT (LETTER DENOTES TYPE)

2'x4' FLUORESCENT LIGHT (LETTER DENOTES TYPE)

2'x4' FLUORESCENT LIGHT - EMERGENCY EGRESSLIGHT (LETTER DENOTES TYPE)

2'x2' FLUORESCENT LIGHT (LETTER DENOTES TYPE)

2'X2' FLUORESCENT LIGHT (LETTER DENOTES TYPE)

1'x4' FLUORESCENT LIGHT - PENDANT OR SURFACEMOUNT (LETTER DENOTES TYPE)

1'X4' FLUORESCENT EMERGENCY LIGHT - PENDANTOR SURFACE MOUNT (LETTER DENOTES TYPE)

1'X8' FLUORESCENT LIGHT (LETTER DENOTES TYPE)

1'X8' FLUORESCENT LIGHT - EMERGENCY EGRESSLIGHT (LETTER DENOTES TYPE)

WALLPACK FIXTURE (LETTER DENOTES TYPE)

INCANDESCENT - METAL HALIDE, OR HIGH PRESSURESODIUM LIGHTING FIXTURE (LETTER DENOTES TYPE)

WALL MOUNT LIGHTING FIXTURE (LETTER DENOTESTYPE)

TRACK HEAD OR FLOOD LIGHT (ARROW INDICATESDIRECTION)

EXIT LIGHT - CEILING MOUNT (SHADING INDICATESFIXTURE FACES) (DO NOT SWITCH OR CONNECT TOLIGHTING CONTROL PANEL)

EXIT LIGHT - WALL MOUNT (SHADING INDICATESFIXTURE FACES) (DO NOT SWITCH OR CONNECT TOLIGHTING CONTROL PANEL)

EMERGENCY LIGHT (LETTER DENOTES TYPE) (DO NOTSWITCH OR CONNECT TO LIGHTING CONTROL PANEL)

2 BULB INCANDESCENT WALL MOUNT

INCANDESCENT DIRECTIONAL PENDANT

POLE MOUNTED FIXTURE - ROUND (LETTER DENOTESTYPE)

POLE MOUNTED FIXTURE - SQUARE (LETTERDENOTES TYPE)

OCCUPANCY SENSOR - CEILING MOUNT

OCCUPANCY SENSOR - WALL MOUNT

A

A

A

XX

XX

J JUNCTION BOX

MOTOR

NON-FUSED DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

COMBINATION MOTOR STARTER

CONDULET

PULLBOX

DRY-TYPE TRANSFORMER

VARIABLE FREQUENCY DRIVE (VFD)

START - STOP PUSHBUTTON

POWER PANEL (PPL)

LIGHTING PANEL (LPL)

MAIN DISTRIBUTION PANEL OR SWITCHBOARD (MDP)

UNIT HEATER - VERTICAL (UHT) - DUCT HEATER (DHT) -CABINET HEATER (CHT)

LIGHTING CONTRACTOR

M

C

P

T

VFD

MDP

LC

FUSE (TYPE, SIZE, AND FRAME SHOWN ASINDICATED)

NON-FUSED DISCONNECT SWITCH (TYPE, SIZE,AND FRAME SHOWN AS INDICATED)

FUSED DISCONNECT SWITCH (SIZE ASINDICATED)

HV FUSED CUTOUT SWITCH (TYPE, SIZE, ANDFRAME SHOWN AS INDICATED)

DRAWOUT LOW VOLTAGE POWER CIRCUITBREAKER (TYPE TRIP AND FRAME SIZE SHOWN)

FIXED LOW VOLTAGE POWER CIRCUIT BREAKER(TYPE TRIP AND FRAME SIZE SHOWN)

DRAWOUT HIGH VOLTAGE POWER CIRCUITBREAKER (TYPE TRIP AND FRAME SIZE SHOWN)

FIXED HIGH VOLTAGE POWER CIRCUIT BREAKER(TYPE TRIP AND FRAME SIZE SHOWN)

THREE PHASE MOTOR CONTACTOR - STARTER(TYPE AND NEMA SIZE SHOWN)

MOTOR OVERLOAD RELAY (TYPE AS SHOWN)

VARIABLE FREQUENCY DRIVE

SOFT START CONTROLLER

ELECTRICAL PANELBOARD (SEE PANELBOARDSCHEDULES FOR DETAILS)

LOCAL DISCONNECT SWITCH - NON FUSED

LOCAL DISCONNECT SWITCH - FUSED

POWER TRANSFORMER WITH VOLTAGES,TRANSFORMER SIZE, AND IMPEDANCE ASINDICATED

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER WITH POLARITYMARKING (RATING SHOWN)

GROUND CURRENT TRANSFORMER (RATINGSHOWN)

POTENTIAL TRANSFORMER (NUMBER OF PT'S &RATING SHOWN)

CT SHORTING BLOCK

DELTA CONNECTION

WYE CONNECTION

CAPACITOR

LIGHTNING / SURGE ARRESTER (RATINGINDICATED)

GROUND

BATTERY

MOTOR (HORSEPOWER & FLA SHOWN)

GENERATOR (PHASE ROTATION SHOWN)

HAND - OFF - AUTO PUSHBUTTON

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

VFD XXX

RVS XXX

PNL XXX

XXX

XXX

XXX

SB

XXX

XXX

XXX

XXX

XXX

A

B C

SS2

S3

S4

STE

SO

SD

SAD

SMC

HOA

AREA CLASSIFICATION:

AREA CLASSIFICATION KEY

NON-HAZARDOUS - NEMA 1

NON-HAZARDOUS - NEMA 4

HAZARDOUS AREA - CLASS I, DIV. 1, GROUP D(TEMPERATURE RATING BETWEEN T2D-T6)

HAZARDOUS AREA - CLASS I, DIV. 2, GROUP D(TEMPERATURE RATING BETWEEN T2D-T6)

HAZARDOUS AREA - CLASS II, DIV. 1, GROUP G(TEMPERATURE RATING BETWEEN T3A-T6)

HAZARDOUS AREA - CLASS II, DIV. 2, GROUP G(TEMPERATURE RATING BETWEEN T3A-T6)X

XXX

D

U

XX-XXX

SYMBOL IDENTIFICATION

SEQUENCE NUMBER

RACEWAY TYPE:C: CONDUITT: TRAYDB: DUCTBANK

RACEWAY NUMBER DESCRIPTION:

XX-XXX

VOLTAGE LEVEL:P: POWERC: CONTROLCOMC: COMMUNICATIONS

120V/277V, 20A CIRCUIT TO PANEL ANDBREAKER INDICATED. SHORT DASHINDICATES SWITCHED OR "HOT"CONDUCTOR, LONG DASH INDICATESNEUTRAL, ARC INDICATES GROUND. (3 #12AWG AND 3/4" RGS CONDUIT)

208V/240V, 20A CIRCUIT TO PANEL ANDBREAKER INDICATED. SHORT DASHESINDICATES SWITCHED OR "HOT"CONDUCTORS, ARC INDICATES GROUND. (3#12 AWG AND 3/4" RGS CONDUIT)

208V/480V 3PHASE 20A, CIRCUIT TO PANELAND BREAKER INDICATED. SHORT DASHESINDICATES SWITCHED OR "HOT"CONDUCTORS, ARC INDICATES GROUND. (4#12 AWG AND 3/4" RGS CONDUIT)

XX-XXX

SEQUENCE NUMBER

CIRCUIT TYPE:P0: LOW VOLTAGE POWER CIRCUITP1: 120V POWER CIRCUITP2: 208/277V POWER CIRCUITP4: 480V POWER CIRCUITP5: 5KV POWER CIRCUITCA: ANALOG CONTROL CIRCUITGMC: COMMUNICATIONS CIRCUITCD: DISCRETE CONTROL CIRCUIT

CIRCUIT NUMBER DESCRIPTION:

PPL-XX,CKT XX

PPL-XX,CKT XX

PPL-XX,CKT XX

EP EXPLOSION PROOF: (CLASS 1, DIV 1)

CR CORROSION RESISTANT

P PILOT LIGHT K KEY OPERATED

IG ISOLATED GROUND

NL ILLUMINATED

FU FUSED

EMT ELECTRICAL METALLIC TUBING

RGS RIGID GALVANIZED STEEL

RAC RIGID ALUMINUM CONDUIT

SSI SAFETY SWITCH INTERLOCK

LSH HIGH LEVEL SWITCH

LSL LOW LEVEL SWITCH

SS SPEED SWITCH

XV DISCRETE VALVE

ZV MULTIPORT VALVE

FV FLOW VALVE

LV LEVEL VALVE

CP CONTROL PANEL

SB SUMMING BOX

WE WEIGHT ELEMENT

TT TEMPERATURE TRANSMITTER

TV TEMPERATURE VALVE

LT LEVEL TRANSMITTER

PIT PRESSURE INDICATING TRANSMITTER

PT PRESSURE TRANSMITTER

LIT LEVEL INDICATING TRANSMITTER

FC FLOW CONTROLLER

FIC FLOW INDICATING CONTROLLER

VFD VARIABLE FREQUENCY DRIVE

ONE-LINE SYMBOLS CONTINUED:

START - STOP PUSHBUTTON

INDICATING LIGHT (COLOR AS SHOWN)

DEVICE AS DEFINED BY ANSI NUMBER

COMBINATION RELAY DEVICE (FUNCTIONS ASDEFINED BY ANSI NUMBER)

METER (LETTER INDICATES TYPE)A - AMMETERV - VOLTMETERW - WATTMETERWH - WATT HOUR METER

G

86XXX

X

SS

5051

50G

DRAFTING SYMBOLS:

UPDN

SPANGRATING

SLOPE

DETAIL CALL OUT

SECTION CUT

ELEVATION

ELEVATION INDICATOR

BUILDING COLUMN

STAIR UP OR DOWN

BAR GRATING SPAN

SLOPE DIRECTION (DOWN)

KEY NOTE

TIE IN POINT

UTILITY FEED

REVISION CLOUD & DELTA

CONTINUATION

1

TIP1

1

1GA_._

1

X-

1X-?

EL. = 100'-0"DESCRIPTION

1

HPXXX

XXX

SUBSCRIPT APPLIED TO ANYSYMBOL INDICATES THE FOLLOWING:C CEILING MOUNTED

F FLOOR MOUNTED

GFCI GROUND FAULT CIRCUIT INTERRUPTER

RP RAIN PROOF NEMA TYPE 3R OR EQUIVALENT

WT WATER TIGHT NEMA TYPE 4 OR EQUIVALENT

DT DUST/IGNITION PROOF: (CLASS 2, DIV 1)

EP EXPLOSION PROOF: (CLASS 1, DIV 1)

C XX

C

CR

PIXXX

MXX

MXX

1

0 31-05-2013 ISSUED FOR CONSTRUCTION

HEIGHTS ARE TO CENTER LINE UNLESS OTHERWISE NOTEDON THE DRAWINGS. ALL DEVICES TO BE RECESSED UNLESSOTHERWISE NOTED ON THE DRAWINGS.

MOUNTING HEIGHTS SHALL CONFORM TO ADA REQUIREMENTSRECEPTACLES IN FINISHED SPACES +18" AFFWIREMOLD AND RECEPTACLES ABOVE COUNTERTOP 4" ABOVE

BACKSPLASH OR+34" AFF

SWITCHES +44"(ADA) AFFTHERMOSTATS +60" AFFFIRE ALARM HORN, HORN STROBE, +80" AFFSTROBE OR CHIMEPANELBOARDS TO TOP +72" AFFCABINETS TO TOP +72" AFFDISCONNECTS, STARTERS +60" AFFTELEPHONE/DATA OUTLETS +18" AFFCLOCKS, CLOCK HANGER RECEPTACLES +62" AFFCATV, TV OUTLETS AND RECEPTACLES +78" AFFMANUAL FIRE ALARM PULL STATIONS +44' AFF (ADA)WALL MTD NURSE CALL CORRIDOR DOME LIGHT +78" AFFNURSE CALL CEILING DOME LIGHT IN CEILINGWALL MTD SPEAKERS +78" AFFCEILING MTD SPEAKERS IN CEILINGRECEPTACLES IN MECHANICAL ROOMS +48" AFFNURSE CALL EMERGENCY PULL STATIONS +44" AFF(ADA)STAFF DUTY STATIONS AND BEDSIDE STATIONSREMOTE INDICATING LIGHTS +78" AFF OR IN

CEILINGFIRE ALARM ANNUNCIATOR PANELS +62" AFFNURSE CALL ANNUNCIATOR PANELS +48" AFFGRAPHIC ZONE MAPS +62" AFFBUZZERS, KEYPADS, VOLUME +44" AFFCONTROL SWITCHESDOORBELL CHIMES ETC. +78" AFF

NOTE:

NOT ALL DEVICES MAY BE SHOWN ON THE DRAWINGS. THIS IS AMASTER MOUNTING HEIGHT SCHEDULE SHOWING TYPICAL DEVICES.SEE DRAWINGS FOR ACTUAL DEVICES USED. ALL MOUNTING HEIGHTSFOR OTHER DEVICES NOT SHOWN ON THIS SCHEDULE SHALL BE ASSHOWN ON THE DRAWINGS. THIS SCHEDULE IS BASED UPON CEILINGHEIGHTS 8'-0" OR HIGHER; WHERE LOWER CEILING HEIGHTS OREXISTING CONDITIONS DICTATE, ADJUST MOUNTING HEIGHTSACCORDINGLY.

MOUNTING HEIGHTS:

1. ALL ELECTRICAL EQUIPMENT AND ENCLOSURES SHALL BE SUITABLEFOR THE AREA CLASSIFICATION IN WHICH IT IS LOCATED ASFOLLOWS:

1.1. NEMA 1 - INDOOR GENERAL USE IN DRY AREAS.

1.2. NEMA 12 FOR UNCLASSIFIED AREAS, EQUIPMENT ROOMSUNLESS OTHERWISE SPECIFIED-DUSTTIGHT AND DRIPTIGHT.

1.3. NEMA 4 FOR WET AREAS SUBJECT TO HOSEDOWN-WATERTIGHTAND DUST TIGHT.

1.4. NEMA 4X (STAINLESS STEEL-CROUSE HINDS "KRYDON" ORAPPROVED EQUAL) FOR CORROSIVE AREAS-WATERTIGHT,DUST TIGHT AND CORROSION RESISTANT.

1.5. NEMA TYPE 7 AND 9 FOR CLASS I, DIVISION I, GROUPS C AND DAND CLASS II, DIVISION I, GROUPS E, F, AND G HAZARDOUSLOCATIONS, RESPECTIVELY-CAST ALUMINUM ENCLOSURES.

1.6. NEMA 3R FOR AREAS LOCATED OUTDOORS AND/OR OTHERWISESPECIFIED AS WEATHERPROOF(WP)-RAINTIGHT.

ELECTRICAL ENCLOSURE RATINGS:

SUBSCRIPT APPLIED TO ANYSYMBOL INDICATES THE FOLLOWING CONTINUED:AV AUTOMATED VALVE

PV PRESSURE VALVE

TIT TEMPERATURE INDICATING TRANSMITTER

ZS LIMIT SWITCH

HS HAND SHAKE

YI SKID INDICATOR

XA SKID ALARM

M MOTOR STARTER

FT FLOW TRANSMITTER

FIT FLOW INDICATING TRANSMITTER

MARK DESCRIPTIONDATE

Ch

icag

o L

um

ber

War

eho

use

Fac

ility

1234 S

outh

14th

Str

eet

Om

aha,

Neb

rask

a 6

8102

C:/R

&A

/p

ro

je

cts/0

90

1ch

ica

go

lu

mb

/D

ra

win

gs/D

ra

win

g S

et

I1.02

ELDON E.

JENSEN II

E-13155

06-06-2013

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

Page 2: E5bidroom.net/lundross/2013-06-27/4 electrical drawings.pdfxxx xxx xxx a b c s s 2 s 3 s 4 s te s o s d s ad s mc h o a area classification: area classification key non-hazardous -

1. CODES AND STANDARDS:

1.1. ELECTRICAL INSTALLATION SHALL ADHERE TO THE 2011 EDITION OF THE NATIONALELECTRICAL CODE (NEC) AND ALL APPLICABLE STATE AND LOCAL CODES ANDORDINANCES.

1.2. THE ELECTRICAL CONTRACTOR (EC) SHALL BE RESPONSIBLE TO OBTAIN ALLNECESSARY ELECTRICAL PERMITS FROM THE LOCAL AUTHORITY HAVINGJURISDICTION AND PAY ALL FEES ASSOCIATED THEREWITH. THE ELECTRICALCONTRACTOR SHALL BE RESPONSIBLE TO ENSURE THAT THE ELECTRICALINSTALLATION PASSES ALL REQUIRED INSPECTIONS.

1.3. THE ELECTRICAL CONTRACTOR SHALL COMPLY WITH ALL THE REQUIREMENTS OFTHE APPLICABLE UTILITY COMPANIES SERVING THIS PROJECT. THE EC SHALL MAKEALL ARRANGEMENTS WITH THE UTILITY COMPANIES FOR PROPER COORDINATIONOF WORK.

1.4. WHERE THESE PLANS AND SPECIFICATIONS EXCEED THE MINIMUM REQUIREMENTSOF THE 2011 NEC OR OTHER ESTABLISHED CODES, THE CONTRACT DOCUMENTSSHALL TAKE PRECEDENCE.

1.5. THE DESIGN, MANUFACTURE, TESTING AND METHOD OF INSTALLATION OF ALLAPPARATUS AND MATERIALS FURNISHED UNDER THE REQUIREMENTS OF THESESPECIFICATIONS SHALL CONFORM TO THE LATEST PUBLICATIONS OR STANDARDRULES OF THE FOLLOWING:

1.5.1. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS - IEEE1.5.2. NATIONAL ELECTRICAL MANUFACTURERS' ASSOCIATION - NEMA1.5.3. UNDERWRITERS' LABORATORIES, INC. - U.L.1.5.4. NATIONAL FIRE PROTECTION ASSOCIATION - NFPA1.5.5. AMERICAN SOCIETY FOR TESTING AND MATERIALS - ASTM1.5.6. NATIONAL ELECTRIC CODE - NEC1.5.7. NATIONAL ELECTRIC SAFETY CODE - NESC

2. DRAWINGS:

2.1. PLAN DRAWINGS INDICATE DIAGRAMMATICALLY THE DESIRED ARRANGEMENT ANDTHE APPROXIMATE LOCATION OF PRINCIPAL ITEMS SUCH AS LIGHTING, MOTORS,ELECTRICAL PANELS, SWITCHES, OUTLETS, ETC. THE DRAWINGS SHOULD NOT BEUSED FOR TAKE OFFS AS ACTUAL LOCATIONS OF THE DEVICES AND CONDUIT RUNSMAY VARY. THE ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONSBEFORE START OF WORK.

2.2. WITHIN 14 DAYS OF NOTICE TO PROCEED, ELECTRICAL CONTRACTOR SHALL SUBMIT(5) BOUND SETS OF SHOP DRAWINGS TO OWNER'S REPRESENTATIVE CONTAININGMANUFACTURER'S CUT SHEETS OF ALL ELECTRICAL EQUIPMENT FURNISHED UNDERTHIS CONTRACT.

2.3. WITHIN 30 DAYS AFTER WORK IS COMPLETE, THE ELECTRICAL CONTRACTOR SHALLSUBMIT TO THE OWNER'S REPRESENTATIVE A SET OF DRAWINGS SHOWING"AS-BUILT" CONDITIONS THAT SHALL INCLUDE ALL MODIFICATIONS AND ADDITIONSTO THE ORIGINAL DESIGN.

2.4. WITHIN 30 DAYS AFTER WORK IS COMPLETE, THE ELECTRICAL CONTRACTOR SHALLSUBMIT ALL INSTRUCTION MANUALS, MANUFACTURES DRAWINGS, AND ANY OTHERLITERATURE SUBMITTED WITH CONTRACTOR FURNISHED EQUIPMENT.

3. MATERIALS AND EQUIPMENT:

3.1. THE ELECTRICAL CONTRACTOR SHALL PURCHASE AND INSTALL ALL EQUIPMENTAND DEVICES AS SPECIFIED ON THE DRAWINGS AND IN THE SPECIFICATIONS. THISINCLUDES ALL BASIC MATERIALS REQUIRED TO COMPLETE THE PROJECT THAT ARENOT SPECIFICALLY CALLED OUT IN THE SPECIFICATIONS: CONDUIT FITTINGS,JUNCTION BOXES, HANGERS, ETC.

3.2. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND WHERE POSSIBLE OF USMANUFACTURE. ALL EQUIPMENT AND MATERIALS SHALL BE LISTED BY THEUNDERWRITERS LABORATORIES, INC., AND SHALL BEAR THEIR LABEL WHEREPOSSIBLE. ALL MATERIALS AND PRODUCTS SHALL BE OF THE LATEST DESIGN ANDCURRENTLY IN PRODUCTION. OBSOLETE COMPONENTS SHALL NOT BE USED.

3.3. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROPERLY PROTECTING THEEQUIPMENT AND MATERIALS AT ALL TIMES FROM THE WEATHER OR ANY OTHERADVERSE ENVIRONMENTAL CONDITIONS. THIS RESPONSIBILITY SHALL INCLUDE ANYEQUIPMENT THAT THE CONTRACTOR HAS PURCHASED OR OWNER SUPPLIEDEQUIPMENT THAT HAS BEEN TURNED OVER TO THE CONTRACTOR FORINSTALLATION.

3.4. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR RE-PAINTING,REPAIRING, OR REPLACING ANY EQUIPMENT OR DEVICE THAT IS DAMAGED PRIORTO THE FINAL ACCEPTANCE TEST DUE TO CONTRACTOR NEGLIGENCE AT NO COSTTO THE OWNER.

3.5. THE ELECTRICAL CONTRACTOR SHALL OBTAIN WRITTEN PERMISSION FROM THEOWNER'S REPRESENTATIVE PRIOR TO SUBSTITUTING ANY ELECTRICAL EQUIPMENTFROM THOSE SPECIFIED IN THE SPECIFICATIONS OR ON THE DRAWINGS.

4. EXECUTION OF WORK:

4.1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS,EQUIPMENT, TOOLS, SERVICES, SUPERVISION, PERMITS, LICENSES, INSPECTIONFEES, TRANSPORTATION, AND MISCELLANEOUS EXPENSES NECESSARY TOCOMPLETE THE CONTRACT IN ACCORDANCE WITH THE DRAWINGS ANDSPECIFICATIONS.

4.2. THE ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL INFORMATION PRESENTEDIN THESE DRAWINGS PRIOR TO STARTING THE WORK. THE ELECTRICALCONTRACTOR SHALL BE RESPONSIBLE FOR ANY REWORK RESULTING IN FAILURETO FIELD VERIFY EXISTING CONDITIONS OF THE JOB SITE AT NO ADDITIONAL COSTTO THE OWNER.

4.3. THE ELECTRICAL CONTRACTOR SHALL INSTALL ALL MATERIALS IN A NEAT ANDWORKMANLIKE MANNER AND ALIGN, LEVEL, AND ADJUST EQUIPMENT FORSATISFACTORY OPERATION.

4.4. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO REWORK THEINSTALLATION OF ELECTRICAL ITEMS THAT DO NOT ADHERE TO THIS ELECTRICALDESIGN AT NO EXPENSE TO THE OWNER.

4.5. ELECTRICAL CONTRACTOR SHALL PERFORM THE WORK IN A SAFE MANNER ANDSHALL AT ALL TIMES COMPLY WITH ALL OSHA, OWNER, STATE, AND LOCAL SAFETYPROCEDURES.

4.6. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING, PAINTING,REPAIRING, OR REPLACING OF ALL WALLS, CEILINGS, OR OTHER BUILDINGELEMENTS WHICH ARE DAMAGED OR DISTURBED AS PART OF THE INSTALLATION OFELECTRICAL WORK.

4.7. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE MOUNTING OF CONDUITON OR NEAR MECHANICAL EQUIPMENT TO MAINTAIN ACCESS TO REMOVABLESERVICE PANELS AND TO PREVENT DAMAGE TO THE EQUIPMENT.

4.8. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OTHER TRADES TOENSURE THAT THE ELECTRICAL EQUIPMENT INSTALLED UNDER THIS CONTRACTMAINTAINS CLEARANCE REQUIREMENTS OF THE NEC.

4.9. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE ELECTRICAL WORK WITHTHE OTHER TRADES SO THAT THE WORK PROCEEDS WITH A MINIMUM OFCONFLICTS AND INTERFERENCE WITH OTHER TRADES. CONFLICTS RESULTING INREWORK THAT ARISE FROM LACK OF COORDINATION SHALL BE THERESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.

4.10. THE ELECTRICAL CONTRACTOR SHALL COORDINATE ALL ELECTRICAL SERVICEOUTAGES WITH THE OWNER'S REPRESENTATIVE AT LEAST 48 HOURS IN ADVANCEAND THE OUTAGE SHALL BE APPROVED BY THE OWNER.

1. GENERAL:

1.1. ELECTRICAL CONTRACTOR SHALL PROVIDE EQUIPMENT GROUNDING CONDUCTORSIN ALL LIGHTING AND POWER BRANCH CIRCUITS.

1.2. ELECTRICAL CONTRACTOR SHALL BOND ALL RACEWAYS AND ENCLOSURES PERTHE NEC.

1.3. PROVIDE A SEPARATE GROUND WIRE, SIZED PER THE NEC IN ALLRACEWAYS INCLUDING ALL BELOW AND ABOVE GRADE RIGID NONMETALLIC (PVC)CONDUITS. THE CONDUIT SYSTEM SHALL NOT BE USED FOR ESTABLISHING AGROUNDING CONDUCTOR MEANS.

1.4. GROUND ELECTRICAL EQUIPMENT PER THE NEC.

1.5. GROUND THE DRAIN WIRE OF SHIELD WIRES AT ONE END ONLY.

1.6. FOR ALL ISOLATED GROUND CIRCUITS AND SPD CIRCUITS PROVIDE A SEPARATEISOLATED GROUND CONDUCTOR IN CIRCUIT THAT IS IN ADDITION TO THE NORMALRACEWAY GROUNDING CONDUCTOR AND ROUTE BACK TO MAIN SERVICEGROUNDING ELECTRODE OR ELECTRICAL GROUND BUSS PER NEC 250-74

1.7. PER NEC SECTION 250.94, AN EXTERNAL ACCESSIBLE INTERSYSTEM BONDINGTERMINAL FOR THE GROUNDING AND BONDING OF COMMUNICATIONS SYSTEMSMUST BE PROVIDED AT SERVICE EQUIPMENT AND DISCONNECTING MEANS FORBUILDING. COMMUNICATIONS SYSTEM SHALL BE BONDED TO THE INTERSYSTEMBONDING TERMINAL INCLUDING ANTENNAS, SATELLITE DISHES 810.15 AND 810.21.CATV 820.100. TELEPHONE CIRCUITS 800.100.

1.8. WHERE MULTIPLE CIRCUITS ARE ROUTED IN THE SAME CONDUIT EACH SHALL HAVEA DEDICATED GROUND AND NEUTRAL WIRE. THE USE OF SHARED NEUTRALS ORGROUNDS SHALL NOT BE ALLOWED.

1.9. PROVIDE A SEPARATE CODE SIZED GROUND WIRE IN ALL BELOW GRADE LINEVOLTAGE CONDUITS, 120V AND GREATER.

1.10. THE ELECTRICAL CONTRACTOR SHALL PROVIDE GROUND RESISTANCE TESTING OFTHE MAIN SERVICE ENTRANCE GROUNDING ELECTRODE CONDUCTOR AND BONDTHE MAIN SERVICE GROUND TO ADDITIONAL GROUNDING ELECTRODES PER THENEC AS REQUIRED TO ACHIEVE A MINIMUM OF 5 OHMS GROUND RESISTANCE.

1.11. WHERE MEGGER CIRCUIT CONTINUITY TESTS OF ALL CONDUCTORS INDICATEFAULTY OR DAMAGED INSULATION, THE CONTRACTOR SHALL REPAIR OR REPLACEDEFECTIVE OR DAMAGED CONDUCTORS.

1. GENERAL:

1.1. ELECTRICAL CONTRACTOR SHALL PROVIDE A 2"X4" PHENOLIC NAMEPLATE FOR ALLPANELBOARDS, MOTOR STARTERS, DISCONNECT SWITCHES, AND LIGHTINGCONTACTORS. NAMEPLATE SHALL BE WHITE WITH BLACK LETTERS. NAMEPLATESHALL INCLUDE THE PANELBOARD TAG NUMBER, NAME, AND VOLTAGE LEVEL ASDESCRIBED ON THE PANELBOARD SCHEDULE. USE “PLIOBOND” INDUSTRIALADHESIVE BY GOODYEAR, OR EQUAL, FOR MOUNTING NAMEPLATES.

1.2. THE ELECTRICAL CONTRACTOR SHALL FILL OUT THE PANELBOARD DIRECTORY PERINSTALLED CONDITIONS. THIS SHALL BE PLACED IN THE PANELBOARD AT THE ENDOF THE PROJECT.

1.3. THE ELECTRICAL CONTRACTOR SHALL LABEL ALL JUNCTION BOXES, FACEPLATES,ETC. WITH PANEL AND CIRCUIT NUMBER USING A BRADY PERMANENT STICK ONLABELS.

1. GENERAL:

1.1. ALL ELECTRICAL WIRING SHALL BE COPPER, 600V RATED, TYPE THWN/THHN. ALLWIRING SHALL BE INSTALLED IN CONTINUOUS RACEWAY. ALL CIRCUITS SHALL HAVEDEDICATED NEUTRAL AND GROUND WIRES. MINIMUM WIRE SIZE SHALL BE #12 AWGFOR POWER CIRCUITS, #14 AWG FOR CONTROL CIRCUITS, AND #18AWG FOR LOWVOLTAGE CONTROL CIRCUITS. UNLESS SPECIFICALLY CALLED OUT ELSE WHERE.

1.2. ELECTRICAL WIRING #10 AWG AND SMALLER SHALL BE PROVIDED WITH COLORCODED INSULATION. FOR WIRE SIZES LARGER THAN #10 AWG, COLOREDELECTRICAL TAPE SHALL BE PROVIDED AT EACH CONDUCTOR TERMINATION.COLOR CODES SHALL BE PER THE NEC.

1.3. ALL WIRE AND CABLE SHALL BE STANDARD PREMIUM QUALITY. NO WIRE OR CABLESHALL BE MORE THAN SIX MONTHS OLD. ALL WIRE SHALL BE COPPER, TINNED ANDANNEALED WITH CLASS B STRANDING. SOLID CONDUCTORS SHALL NOT BE USED.

1.4. INSTALL INSTRUMENTATION AND CONTROL CIRCUITS IN SEPARATE CONDUITS. DONOT COMBINE 24V DC AND 120 VAC CONDUCTORS IN COMMON CONDUIT.

1.5. COLOR CODE ALL CONDUCTORS IN LIGHTING AND POWER WIRING AS FOLLOWS:120/208: 277/480:

PHASE A BLACK BROWNPHASE B RED ORANGEPHASE C BLUE YELLOWNEUTRAL WHITE GREYGROUND GREEN GREEN W/YELLOWSTRIPE

1.6. SWITCH LEGS SHALL BE COLOR CODED TO DISTINGUISH FROM HOT OR PHASECONDUCTORS. COLOR CODING OF ENDS WILL BE ACCEPTABLE FOR FEEDER PHASECONDUCTORS ONLY. ALL BRANCH CIRCUIT WIRING SHALL BE COLOR CODED ASINDICATED FOR THE ENTIRE LENGTH OF THE WIRE.

1.7. ALL POWER AND MOTOR WIRING SHALL BE CONTINUOUS WITHOUT SPLICES. ONLIGHTING AND RECEPTACLE CIRCUITS, CONDUCTORS SHALL BE CONTINUOUS FROMOUTLET TO OUTLET OR FIXTURE TO FIXTURE AND NO SPLICES SHALL BE MADEEXCEPT IN OUTLET OR TERMINAL BOXES. NO SPLICES SHALL BE MADE IN CONDUITSOR CONDUIT BODIES.

1.8. CONTROL AND INSTRUMENTATION CONDUCTORS SHALL NOT BE SPLICED. ALLCONTROL AND INSTRUMENTATION CONNECTIONS SHALL BE MADE ON TERMINALSTRIPS. PROVIDE 600 VOLT RATED, CHANNEL MOUNTED TERMINAL BLOCKS,SQUARE D CLASS 9080 OR EQUAL.

1.9. WIRE SHALL BE INSTALLED INTO CONDUIT USING THE CABLE MANUFACTURER'SSTANDARD, POWDERED SOAPSTONE, OR ELECTRO-COMPOUND CO. “Y-ER-EAS”WHERE REQUIRED. GREASE OR OIL SHALL NOT BE USED FOR THIS PURPOSE.PULLING LUBRICANT SHALL BE UL LISTED.

1. CONDUIT:

1.1. ELECTRICAL CONTRACTOR SHALL GENERALLY USE STEEL ELECTRICAL METALLICTUBING (EMT) THROUGHOUT IN INTERIOR LOCATIONS. CONDUITS SHALL BE ROUTEDCONCEALED IN FINISHED AREAS AND EXPOSED IN UNFINISHED AREAS. ALL CONDUITSHALL BE ROUTED PARALLEL AND PERPENDICULAR WITH BUILDING LINES. MIN. SIZEFOR EMT CONDUIT SHALL BE 3/4”. ALL CONDUIT IN AREAS SUBJECT TO PHYSICALDAMAGE (MECH/ ELEC. EQUIP. ROOMS) SHALL BE HEAVY WALL GALVANIZED STEELRIGID METALLIC CONDUIT (RMC). MIN SIZE FOR RMC SHALL BE ¾”.

1.2. ELECTRICAL CONTRACTOR MAY USE ZINC COATED STEEL FLEXIBLE METALLICCONDUIT WHERE APPROPRIATE AND ALLOWED BY CODE. "SEAL-TITE" TYPE LASHALL BE USED IN WET OR EXTERIOR LOCATIONS WHERE FLEXIBLE CONDUIT ISREQUIRED.

1.3. ELECTRICAL CONTRACTOR MAY USE EMT SET SCREW FITTINGS IN INTERIOR DRYLOCATIONS. IN WET OR EXTERIOR LOCATIONS COMPRESSION RAIN TIGHT FITTINGSOR THREADED HUB TYPES SHALL BE USED. ALL FITTINGS SHALL BE STEEL AND ULLISTED FOR THE ENVIRONMENT IN WHICH THEY ARE INSTALLED. RIGID METALGALVANIZED, HEAVY WALL CONDUIT SHALL USE THREADED CONNECTORS ANDFITTINGS.

1.4. ELECTRICAL CONTRACTOR SHALL SUPPORT CONDUIT AS REQUIRED BY THE NEC.CONDUIT SHALL BE SUPPORTED BY THE BUILDING STRUCTURE OR APPROPRIATEMATERIALS. DO NOT SUPPORT CONDUIT FROM CEILING WIRES, PIPING, DUCTS,OTHER CONDUIT, ETC. CONDUIT SUPPORTS SHALL BE CORROSION RESISTANT ANDUL LISTED: I.E. ONE-HOLE AND TWO-HOLE STRAPS, "MINERALLAC" CONDUIT CLAMPS,"CADDY" CLIPS, THREADED ROD, AND "UNI-STRUT."

1.5. EXPANSION/DEFLECTION FITTINGS SHALL BE INSTALLED ON THE EXTERIOR OF THESTRUCTURE WHENEVER A CONDUIT ENTERS A STRUCTURE FROM THE OUTSIDE.FITTINGS SHALL HAVE A 2-INCH STRAIGHT LINE MOVEMENT IN EITHER DIRECTION.EXPANSION FITTINGS SHALL BE INSTALLED WHENEVER A CONDUIT SPANS ACROSSA STRUCTURAL EXPANSION JOINT. EXPANSION COUPLINGS SHALL BEWEATHERTIGHT, INSULATING BUSHING, SLEEVE-STEEL ZINC-PLATED.

1.6. RACEWAY RUNS SHOWN ARE DIAGRAMMATIC AND INTENDED TO BE USED AS AGUIDE. SITE CONDITIONS MAY AFFECT ACTUAL ROUTING. CONTRACTOR SHALLCOORDINATE ROUTING AND MEASUREMENT WITH OTHER TRADES AND WITHEQUIPMENT SUPPLIERS TO AVOID INTERFERENCE WITH EQUIPMENT, PIPING,DUCTWORK ETC.

1.7. CONDUIT SHALL BE PROPERLY SUPPORTED AS PER THE NEC. CONDUITS SHALL BEKEPT A MINIMUM OF 6" FROM HOT WATER PIPES OR OTHER SOURCES OF HEAT.SUPPORT EXPOSED CONDUITS BY USE OF HANGERS, CLAMPS OR CLIPS. SUPPORTCONDUITS ON EACH SIDE OF BENDS AND ON SPACING NOT TO EXCEED THEFOLLOWING: UP TO 1"-6'-0"; 1-1/4" AND OVER; 8'-0".

1.8. FOR CIRCUIT WIRING CONDUCTOR FILL SHALL NOT CONTAIN MORE THAN 6CURRENT CARRYING WIRES PER CONDUIT HOMERUN.

1.9. ALL CONDUITS PASSING THROUGH EXTERIOR WALLS SHALL BE PROVIDED WITH AHYDROSTATIC SEAL SUCH AS LINK SEAL OR EQUAL.

1.10. PROVIDE JUNCTION, PULL BOXES AND WIRE WAYS AS NECESSARY TO FACILITATEPULLING CONDUCTORS AND AS REQUIRED TO MEET THE MAXIMUM THREE (3) 90DEGREE BEND RULE PER THE LATEST EDITION OF THE NEC.

1.11. PROVIDE 3'-0" MAXIMUM FLEXIBLE CONDUIT CONNECTION TO MOTORS AND LIGHTFIXTURES AND ITEMS SUBJECT TO VIBRATION. USE LIQUID-TIGHT FLEXIBLECONDUIT FOR EXTERIOR LOCATIONS AND AREAS SUBJECT TO DAMP OR WETCONDITIONS.

1.12. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL SLOTS, SLEEVE HOLES, ANDOTHER OPENINGS NECESSARY THROUGH WALLS, FLOORS, OR ANY OTHER PART OFTHE STRUCTURE. SLEEVES FOR CONDUITS PASSING THROUGH LOAD BEARINGWALLS OR FOUNDATION WALLS. SLEEVES THROUGH FLOORS AND WALLS SHALL BEBLACK IRON PIPE FLUSH WITH WALLS, CEILINGS, OR FINISHED FLOORS, SIZED TOACCOMMODATE THE RACEWAY.

1.13. USE CARE IN PIERCING WATERPROOFING. AFTER THE PART PIERCING THEWATERPROOFING HAS BEEN SET IN PLACE, SEAL OPENING AND MAKE ABSOLUTELYWATERTIGHT.

1.14. PROVIDE CHROME-PLATED SPRING-CLIPPED ESCUTCHEON PLATES WHEREEXPOSED PIPE PASSES THROUGH WALLS, FLOORS, OR CEILING. COVER SLEEVESAND OPENING MADE FOR THE PIPE WITH ESCUTCHEON PLATE. PROVIDE AIR ANDWATERTIGHT CONDUIT OPENINGS THROUGH FLOOR SLABS, MASONRY WALLS, ANDCONTINUOUS PARTITIONS BY TIGHTLY CAULKING SPACES BETWEEN CONDUIT ANDBUILDING MATERIALS WITH ASBESTOS ROPE AND NON-FLAMMABLE SEALANT.

1.15. ALL CONDUITS SHALL BE SIZED PER THE NEC FOR THWN/THWN WIRE UNLESSCONDUIT SIZES ARE GIVEN ON THE DRAWING. WHERE CONDUIT SIZES ARE GIVEN,THEN THE CONTRACTOR SHALL FOLLOW THESE SIZES EVEN WHEN THE NECALLOWS A SMALLER CONDUIT SIZE.

1.16. ALL CONDUITS SHALL BE MARKED AT JUNCTION BOXES AND WITH COLORED TAPEAT 10'-0" INTERVALS PER THE FOLLOWING COLOR CODING SCHEDULE:120/208V-GREEN, TELEPHONE-WHITE, AND COMMUNICATIONS/CONTROL-YELLOW

1.17. ALL CONDUIT LOCATED BELOW GRADE AND IN FLOOR SLABS SHALL BE SCHEDULE80 PVC.

1. OUTLETS AND SWITCHES:

1.1. WIRING DEVICES SHALL BE LOCATED AS SHOWN ON THE DRAWINGS. LOCATIONSMAY BE ADJUSTED AS REQUIRED TO COMPLY WITH LOCAL CODES OR TO EASEINSTALLATION. MOUNTING HEIGHTS SHALL BE PER THE CHART ON THE ELECTRICALLEGEND SHEET UNLESS SPECIFICALLY NOTED OTHERWISE.

1.2. CENTER ALL OUTLETS WITH REGARD TO PANELING, FURRING, AND TRIM.SYMMETRICALLY ARRANGE OUTLETS IN THE ROOM. SET OUTLETS PLUMB ANDEXTEND TO THE FINISHED SURFACE OF THE WALL, CEILING, OR FLOOR WITHOUTPROJECTING BEYOND. CONTRACTOR SHALL CORRECT ANY OUTLET NOT INSTALLEDPROPERLY AT NO ADDITIONAL EXPENSE TO THE OWNER.

1.3. WIRING DEVICES SHALL BE MANUFACTURED BY HUBBELL, LEVITION, OR GENERALELECTRIC. ALL OUTLETS AND SWITCHES FOR THE PROJECT SHALL BEMANUFACTURED BY THE SAME COMPANY. ALL OUTLETS AND SWITCHES SHALL BEPROVIDED WITH A COLOR MATCHED FACEPLATE. FLOOR OUTLETS SHALL HAVE ASTAINLESS STEEL FACEPLATE. CATALOG NUMBERS SUPPLIED ARE FOR HUBBELLDEVICES WITH WHITE COLOR. ELECTRICAL CONTRACTOR SHALL COORDINATE WITHARCHITECT FOR OWNER SPECIFIC COLORS.

DUPLEX RECEPTACLES HUBBELL #BR20AL (ALMOND)TAMPER RESISTANCE RECEPTACLES HUBBELL #BR20ALTR (ALMOND)WEATHERPROOF RECEPTACLES HUBBELL #BR20ALWR (ALMOND)DUPLEX GFI RECEPTACLES HUBBELL #GF20ALL (ALMOND)SINGLE POLE SWITCHES HUBBELL #CSB120AL (ALMOND)THREE-WAY SWITCHES HUBBELL #CSB320AL (ALMOND)FOUR-WAY SWITCHES HUBBELL #CSB420AL (ALMOND)OCCUPANCY SENSOR SWITCH HUBBELL #AD1277AL1 (ALMOND)

1.4. RECEPTACLES IN WET LOCATIONS SHALL HAVE AN ENCLOSURE THAT ISWEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED.RECEPTACLE BOX SHALL BE RATED FOR WET LOCATIONS. RECEPTACLE SHALL BEWEATHERPROOF. RECEPTACLE SHALL HAVE A WEATHERPROOF COVER HUBBELLCATALOG #WP826MHP.

2. TELECOMMUNICATIONS OUTLETS:

2.1. FOR EACH DATA OR TELEPHONE OUTLET PROVIDE (1) 4X4 SQUARE STEEL BOX WITHSINGLE GANG PLASTER RING IN THE LOCATION SHOWN. ROUTE (1) 3/4" EMTCONDUIT FROM BOX TO ABOVE CEILING. WHERE 1 OR 2 PORT DATA OR TELEPHONEIS INDICATED ON DRAWINGS, PROVIDE 2 PORT FACEPLATE WITH NUMBER OF PLUGSNEEDED. ROUTE (2) CAT 6E FROM OUTLET TO DATA RACK LOCATION. WHERE 3 OR 4PORT DATA OR TELEPHONE IS INDICATED, PROVIDE 4 PORT FACEPLATE WITHNUMBER OF PLUGS NEEDED. ROUTE (4) CAT 6E FROM OUTLET TO DATA RACKLOCATION. PROVIDE "BLANKS" FOR UNUSED PORTS. LEAVE 10' COILED @ DATARACK OR TELEPHONE BOARD FOR CONNECTION. ELECTRICAL CONTRACTOR SHALLBE RESPONSIBLE FOR TERMINATING THE CAT 6E CABLES AT THE TELEPHONE ANDDATA OUTLETS. TERMINATION OF THE CAT 6E CABLES AT THE SERVER RACK SHALLBE BY OTHERS. COORDINATE THIS WORK WITH TELEPHONE AND DATACONTRACTORS. DATA / TELEPHONE OUTLETS SHALL BE SINGLE GANG, TWO PORTOR 4 PORT SHOWN ON THE DRAWINGS. AND MANUFACTURED BY HUBBELL ORLEVITON. FLOOR OUTLETS SHALL HAVE A STAINLESS STEEL FACEPLATE. CATALOGNUMBERS BELOW ARE FOR HUBBELL.

2 PORT FACEPLATE HUBBELL #IFP12EAL (ALMOND)2 PORT FACEPLATE HUBBELL #SSF12 (STAINLESS STEEL)4 PORT FACEPLATE HUBBELL #IFP14EAL (ALMOND)4 PORT FACE PLATE HUBBELL #SSF12 (STAINLESS STEAL)CAT5E PLUG HUBBELL #HXJ5EEAL (ALMOND)TELEPHONE PLUG HUBBELL #HXJUEAL (ALMOND)

1. GENERAL:

1.1. PANELBOARDS SHALL BE PROVIDED AS SHOWN ON THE DRAWINGS. PANELBOARDSSHALL BE PER THE PANELBOARD SCHEDULE. PANELBOARDS SHALL BEMANUFACTURED BY, SIEMENS, PER SPECIFICATIONS ON RISER DIAGRAM.PANELBOARDS SHALL BE PROVIDED WITH BRANCH BREAKERS AS NOTED ON THEPANELBOARD SCHEDULE.

1.2. THE ELECTRICAL CONTRACTOR SHALL PROVIDE BRANCH BREAKERS AS NOTED FOREXISTING PANELBOARDS. MATCH EXISTING MANUFACTURER.

1.3. ALL PANELBOARDS AND TRANSFORMERS SHALL BE PROVIDED BY THE SAMEMANUFACTURER.

1. GENERAL:

1.1. DRY-TYPE TRANSFORMERS SHALL BE PROVIDED WITH RATINGS AND WINDINGCONNECTIONS AS SHOWN ON THE DRAWINGS. TRANSFORMERS SHALL BEMANUFACTURED BY SIEMENS.

1.2. DRY-TYPE TRANSFORMERS SHALL BE SIEMENS, GENERAL PURPOSE TYPE,SECONDARY SELF-COOLED BY NATURAL CONVECTION, INDOOR, 2-WINDING,DRY-TYPE. PROVIDE WITH RATINGS AS SHOWN ON THE ONE LINE DIAGRAM.

1.3. GROUND ENCLOSURE AND NEUTRAL CONDUCTORS IN ACCORDANCE WITH THE NEC.USE FLEXIBLE (2 FT. MIN. LENGTH) METAL CONDUIT TO CONTAIN THE CONDUCTORFROM THE TRANSFORMER TO THE RACEWAY SYSTEM.

1.4. MEASURE PRIMARY AND SECONDARY VOLTAGES AND MAKE APPROPRIATE TAPADJUSTMENTS TO ACHIEVE THE DESIRED MINIMUM SECONDARY VOLTAGE.

1. GENERAL:

1.1. DISCONNECT SWITCHES SHALL BE HEAVY DUTY TYPE, FUSIBLE OR NON-FUSIBLE,600VAC, SQUARE D CLASS 8810 OR EQUAL (HUBBELL, GENERAL ELECTRIC, ORCUTLER HAMMER), AMPERE RATING AND NO OF POLES AS SHOWN ON THEDRAWINGS AND ON THE ELECTRICAL LEGEND PAGE. ENCLOSURE SHALL BE NEMA12 FOR INDOOR LOCATIONS NOT SUBJECT TO WET OR DAMP CONDITIONS ANDSHALL BE NEMA 3R FOR OUTDOOR LOCATIONS AND LOCATIONS SUBJECT TODAMP OR WET LOCATIONS.

1.2. FUSES SHALL BE CLASS RK5, DUAL ELEMENT TIME DELAY.

1.3. COMBINATION MOTOR STARTERS SHALL BE SQUARE D CLASS 8538, MCP MOTORCIRCUIT PROTECTOR OR FUSIBLE DISCONNECT SWITCH TYPE, NEMA SIZE 1MINIMUM. ENCLOSURE TYPE SHALL BE NEMA 12 IN INDOOR LOCATIONS NOTSUBJECT TO DAMP OR WET CONDITIONS AND SHALL BE NEMA 3R IN OUTDOORLOCATIONS OR LOCATIONS SUBJECT TO DAMP OR WET CONDITIONS. PROVIDE2-NO/NC CONTACTS, HOA SWITCH, RED-GREEN INDICATING LIGHTS, CONTROLPOWER TRANSFORMER WITH FUSED PRIMARY AND SECONDARY, AND THERMALMELTING ALLOY OVERLOAD RELAYS IN EACH LEG, FULL VOLTAGE,NON-REVERSING TYPE.

1.4. FRACTIONAL HORSEPOWER MANUAL STARTERS SHALL BE SQUARE D 2510 ORAPPROVED EQUAL WITH PILOT LIGHT AND MELTING ALLOY THERMAL OVERLOADRELAYS IN EACH LEG, RATED 2 HP MAX AT 115VOLT, 1-PHASE. ENCLOSURE TYPESHALL BE NEMA 12 IN INDOOR LOCATIONS NOT SUBJECT TO DAMP OR WETCONDITIONS AND SHALL BE NEMA 3R IN OUTDOOR LOCATIONS OR INDOORLOCATIONS SUBJECT TO DAMP OR WET CONDITIONS.

1. GENERAL:

1.1. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL INTERIOR LIGHTING PER THELUMINAIRE SCHEDULE. ANY SUBSTITUTIONS SHALL BE APPROVED BY THE OWNER'SREPRESENTATIVE PRIOR TO PURCHASE AND INSTALLATION.

1. GENERAL:

1.1.ELECTRICAL CONTRACTOR SHALL PROVIDE ALL EXTERIOR LIGHTING PER THELUMINAIRE SCHEDULE. ANY SUBSTITUTIONS SHALL BE APPROVED BY THE OWNER'SREPRESENTATIVE PRIOR TO PURCHASE AND INSTALLATION.

SECTION 16050 - BASIC ELECTRICAL MATERIALS AND METHODS:

SECTION 16060 - GROUNDING AND BONDING:

SECTION 16075 - ELECTRICAL IDENTIFICATION:

SECTION 16120 - CONDUCTORS AND CABLES:

SECTION 16130 - RACEWAYS AND BOXES:

SECTION 16442 - ELECTRICAL PANELBOARDS:

SECTION 16511 - INTERIOR LIGHTING:

SECTION 16521 - EXTERIOR LIGHTING:

SECTION 16150 MOTOR CONTROLLERS & DISCONNECT SWITCHES:

SECTION 16140 - WIRING DEVICES:

SECTION 16461 - DRY TYPE TRANSFORMERS (600V AND LESS):

SECTION 16050 - BASIC ELECTRICAL MATERIALS AND METHODS CONT.:4.11. THE E.C. SHALL OBTAIN PERMISSION FROM THE OWNER'S REPRESENTATIVE

BEFORE CUTTING OR PIERCING STRUCTURAL MEMBERS.

4.12. THE E.C. SHALL USE CRAFTSMAN SKILLED IN THEIR RESPECTIVE TRADES FORCUTTING, FITTING, REPAIRING, PATCHING OF DRYWALL OR FINISHING MATERIALSINCLUDING CARPENTRY WORK, METAL WORK, OR CONCRETE WORK REQUIRED FORTHIS WORK. DO NOT WEAKEN WALLS, PARTITIONS, OR FLOORS WHILE CUTTING.HOLES REQUIRED TO BE CUT IN FLOORS MUST BE DRILLED WITHOUT BREAKINGOUT AROUND THE HOLES.

1.10. ALL MOTOR LEAD CONDUCTOR TERMINATIONS SHALL BE MADE WITH T&B FULLCOMPRESSION LUG, FULL RING TYPE AND TAPED AS REQUIRED, TWO (2) LAYERS OF1/2 LAP, 3M SCOTCH NO 33 TAPE

1.11. ELECTRICAL TAPE: PREMIUM GRADE, HEAT, COLD, MOISTURE AND SUNLIGHTRESISTANT VINYL TAPE, #8 OR SMALLER: 7 MIL VINYL; FOR SPLICES OR TAPS OF #6OR LARGER: 10 MIL VINYL; COLD OR OUTDOOR LOCATIONS: 8.5 MIL ALL WEATHERVINYL.

1.12. CABLES SHALL BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONSAND RECOMMENDATIONS OF THE CABLE MANUFACTURER. MAXIMUM PULLINGTENSION SHALL NOT BE EXCEEDED. CABLE PULLING RIG MUST POSITIVELY LIMITTHIS TENSION OR A SUITABLE DYNAMOMETER WHICH CONTINUOUSLY MEASURESTHE PULLING TENSION SHALL BE USED. ALL CABLE ENDS SHALL BE SEALED FROMCONTAMINATION DURING ITS PULLING OPERATION & DURING STORAGE ON CABLEREELS.

1.13. PROVIDE ON EVERY CIRCUIT, AT EACH TERMINATION, A CIRCUIT IDENTIFICATIONSUCH AS BRADY WIRE MARKERS WITH ENCAPSULATED HEAT SHRINK SLEEVE FORPERMANENT IDENTIFICATION.

1.14. ALL CONDUCTORS INSTALLED IN WIREWAYS OF HID OR FLUORESCENT LIGHTFIXTURES SHALL HAVE SILICON RUBBER INSULATION, 90 DEGREES C MINIMUMRATED FIXTURE WIRE, SUITABLE FOR TEMPERATURES ENCOUNTERED.

1.15. THE INSULATION ON ALL CONDUCTORS SHALL BE PERMANENTLY MARKED WITHWIRE SIZE, INSULATION TYPE, VOLTAGE RANGE AND MANUFACTURER'S NAME.

1.16. ALL CONDUCTORS SHALL BE SIZED PER THE DRAWINGS AND SPECIFICATIONS EVENWHEN THE NEC ALLOWS SMALLER SIZE. DEVIATION SHALL NOT BE ALLOWED.

1.17. AT LEAST 6 INCHES OF EXTRA WIRE SHALL BE LEFT IN EACH JUNCTION AND DEVICEBOX.

1.18. NO WIRE SHALL BE PULLED, NOR FISHWIRED OR STRING INSERTED, BEFORECONDUIT AND FITTINGS ARE PERMANENTLY IN PLACE.

SECTION 16120 - CONDUCTORS AND CABLES CONT.:1.18. ALL SITE LIGHTING AND POWER CONDUITS SHALL BE BURIED AT A MINIMUM DEPTH

PER THE NEC TABLE 300.5. PROVIDE YELLOW “CAUTION: ELECTRIC LINES BURIEDBELOW” WARNING TAPE FOR ALL UNDERGROUND BURIED CONDUITS.

1.19. GALVANIZED CONDUIT SUPPORTS DAMAGED DURING NORMAL CUTTING, DRILLING,OR HANDLING SHALL BE RE-GALVANIZED WITH “ZINCILATE 810” OR APPROVEDEQUAL.

1.20. WIRE PHASING SHALL BE ABC OR 123, LEFT TO RIGHT, FRONT TO BACK, TOP TOBOTTOM.

2. CONDUIT FITTINGS:

2.1. PROVIDE CONDUIT FITTINGS AS DESCRIBED BELOW. CATALOG NUMBERS SHOWNARE APPLETON ELECTRIC COMPANY. STEEL CITY AND RACO ARE EQUALLYACCEPTABLE.

2.1.1. EMT COUPLINGS: 6000S SERIES2.1.2. EMT CONNECTORS: 7000S SERIES2.1.3. INSULATING BUSHINGS (1 ¼” AND LARGER): BBU SERIES2.1.4. FLEXIBLE CONDUIT STRAIGHT BOX CONNECTORS: 728 SERIES2.1.5. FLEXIBLE CONDUIT ANGLE BOX CONNECTORS: 738 SERIES2.1.6. SEALING GLAND ASSEMBLY: O-Z GEDNEY TYPE AX OR TX WITH BONDING

JUMPERS AND CLAMPS2.1.7. EXPANSION AND DEFLECTION FITTINGS: O-Z GEDNEY TYPE DX2.1.8. CAST METAL CONDUIT FITTINGS: CROUSE-HINDS “CONDULETS”2.1.9.

3. BOXES:

3.1. ELECTRICAL BOXES SHALL GENERALLY BE 4" SQUARE STEEL TYPE OF DEPTHREQUIRED. THE EC SHALL PROVIDE THE APPROPRIATE PLASTER OR TILE RINGS TOENSURE A NEAT FINISH. PROVIDE OUTLET BOXES AS DESCRIBED BELOW. CATALOGNUMBERS SHOWN ARE APPLETON ELECTRIC COMPANY. STEEL CITY AND RACO AREEQUALLY ACCEPTABLE.

3.1.1. CONCEALED LIGHTING BOXES: #4O-3/43.1.2. CONCRETE LIGHTING BOXES: OCR SERIES3.1.3. EXPOSED LIGHTING BOXES: #4S-3/4 OR #3O-3/43.1.4. FLUSH SWITCH, RECEPTACLE, TELEPHONE AND J-BOXES: #4S-3/4 OR #225

WHERE SEPARATE EXTENSION OR PLASTER RING CANNOT BE USED.3.1.5. EXPOSED SWITCH, RECEPTACLE, TELEPHONE, AND J-BOXES: FS SERIES

3.2. SIZE OUTLET BOXES IN ACCORDANCE WITH THE ALLOWABLE FILL PERMITTED BYTHE NATIONAL ELECTRIC CODE.

4. PULL BOXES:

4.1. PROVIDE CODE GAGE GALVANIZED SHEET METAL SIZED AS PER THE NEC OR ASSHOWN ON THE DRAWINGS. PROVIDE REMOVABLE COVER ON THE LARGESTACCESS SIDE OF THE BOX UNLESS OTHERWISE NOTED. WHERE CAST BOXES ARESPECIFIED, PROVIDE CONDUIT ENTRANCES WITH THREADED HUBS. PROVIDESTAINLESS STEEL SCREWS IN ALL EXTERIOR LOCATIONS AND IN WET OR DAMPLOCATIONS.

5. FIRE RATING:

5.1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE FIRE SEALS AS REQUIRED BY THELOCAL BUILDING CODE TO MAINTAIN FIRE ASSEMBLY AND BARRIER RATINGS INWALLS AND CEILINGS.

SECTION 16130 - RACEWAYS AND BOXES:

MARK DESCRIPTIONDATE

Ch

icag

o L

um

ber

War

eho

use

Fac

ility

1234 S

outh

14th

Str

eet

Om

aha,

Neb

rask

a 6

8102

C:/R

&A

/p

ro

je

cts/0

90

1ch

ica

go

lu

mb

/D

ra

win

gs/D

ra

win

g S

et

I1.04

ELDON E.

JENSEN II

E-13155

06-06-2013

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

0 31-05-2013 ISSUED FOR CONSTRUCTION

Page 3: E5bidroom.net/lundross/2013-06-27/4 electrical drawings.pdfxxx xxx xxx a b c s s 2 s 3 s 4 s te s o s d s ad s mc h o a area classification: area classification key non-hazardous -

GFCI

GFCI

PP-1

GFCI+ 48" A.F.F.

GFCI+ 48" A.F.F.

GFCI+ 48" A.F.F.

PP-1,CKT 14

GFCI+ 48" A.F.F.

GFCI+ 48" A.F.F.

GFCI+ 48" A.F.F.

PP-1CKT 18

GFCI

GFCI

GFCIGFCI

GFCIPP-1CKT 16

PP-1,CKT 50, 52, 54

8

GFCI

PP-1CKT 20

GFCI+ 48" A.F.F.

GFCI+ 48" A.F.F.

PP-1,CKT 61, 63, 65

11

GFCI

PP-1,CKT 43, 45, 47

PP-1CKT 26

15

PP-1,CKT 55, 57, 59

11

16UP TO EQUIPMENT

PLATFORM SEE E1.03

PP-1,CKT 50, 52, 54

8

PP-1,CKT 40, 42

PP-1CKT 41

22

T

GFCI+ 48" A.F.F.

LEGEND GENERAL NOTES:1. SEE SHEET I1.02 FOR SYMBOLS LEGEND.

2. SEE SHEET I1.04 FOR GENERAL NOTES AND SPECIFICATIONS.

3. ELECTRICAL INSTALLATION SHALL ADHERE TO THE LATEST EDITION OF THE NATIONALELECTRIC CODE (N.E.C.) AND ALL APPLICABLE STATE AND LOCAL CODES.

4. ELECTRICAL CONTRACTOR SHALL COORDINATE ELECTRICAL SERVICE INSTALLATIONWITH OPPD.

5. ELECTRICAL CONTRACTOR SHALL COORDINATE ANY POTENTIAL SERVICE OUTAGEWITH OWNER PRIOR OR PERFORMING WORK.

6. LOCATION OF MECHANICAL EQUIPMENT IS SHOWN FOR INFORMATION ONLY. REFER TOMECHANICAL SHEETS FOR EXACT LOCATIONS.

7. DUPLEX RECEPTACLES SHALL BE MOUNTED AT 18" A.F.F. TO CENTER OF OUTLETEXCEPT WHERE NOTED OTHERWISE.

8. ALL ROOF PENETRATIONS SHALL BE SEALED PER SPECIFICATIONS AND DETAILS.

9. ELECTRICAL DESIGN IS BASED ON ALL AREAS BEING RATED AS "S-1" OCCUPANCIES.ELECTRICAL CLASSIFICATION IS "NON-CLASSIFIED." ANY ACTIVITIES HANDLING ORSTORING FLAMMABLE MATERIALS COULD CHANGE THE ELECTRICAL CLASSIFICATION.FOLLOW ALL NEC REGULATIONS, NAMELY ARTICLES 500, 501, 502 AND 503.

EXPOSED CONDUIT

CONCEALED CONDUIT

CONDUIT TURNED UP

CONDUIT TURNED DOWN

METER SOCKET

NON-FUSED DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

DUPLEX RECEPTACLE - RECEPTACLE: 20A, 120V, 3W, 2P (5-20R)

120V/277V, 20A CIRCUIT TO PANEL AND BREAKER INDICATED.SHORT DASH INDICATES SWITCHED OR "HOT" CONDUCTOR,LONG DASH INDICATES NEUTRAL, ARC INDICATES GROUND. (3#12 AWG AND 3/4" EMT CONDUIT)

208V/480V 3PHASE 20A, CIRCUIT TO PANEL AND BREAKERINDICATED. SHORT DASHES INDICATES SWITCHED OR "HOT"CONDUCTORS, ARC INDICATES GROUND. (4 #12 AWG AND 3/4"EMT CONDUIT)

208V/240V, 20A CIRCUIT TO PANEL AND BREAKER INDICATED.SHORT DASHES INDICATES SWITCHED OR "HOT"CONDUCTORS, ARC INDICATES GROUND. (3 #12 AWG AND 3/4"RGS CONDUIT)

EXHAUST FAN TIMER PANEL (BY MECHANICAL CONTRACTOR)

KEY NOTES:

CONTRACTOR TO FURNISH AND INSTALL SERVICE MAST WITH WEATHER HEAD FOROVERHEAD OPPD SERVICE CONNECTION. SERVICE MAST SHALL MEET ALL OPPD &N.E.C. REQUIREMENTS.

CONTRACTOR SHALL FURNISH AND INSTALL (1) 320A, 3 PHASE OPPD APPROVEDMETER SOCKET IN THIS LOCATION. FOLLOW ALL OPPD REQUIREMENTS FOR SOCKETINSTALLATION.

CONTRACTOR SHALL INSTALL (1) 400A, 3 PHASE, 600V, 3 NEMA 3R RATED DISCONNECTIN THIS LOCATION. SEE E3.01 FOR WIRE, CONDUIT, AND FUSE SIZES.

CONTRACTOR SHALL ROUTE CONDUIT AND CONDUCTORS TO NEW 400A PANELBOARD,PP-1 UNDER GROUND AS SHOWN. ROUTE IN 4" PVC BELOW GRADE AND TRANSITIONTO EMT FOR ABOVE GRADE PORTIONS. ROUTE AT 36" BELOW FINISHED FLOOR.COORDINATE ROUTING WITH PLUMBING PLANS TO AVOID CONFLICTS..

CONTRACTOR SHALL FURNISH AND INSTALL (2) GFCI RATED DUPLEX OUTLETS ASSHOWN. OUTLETS SHALL BE PROVIDED WITH WEATHERPROOF COVER THATMAINTAINS ITS WEATHERPROOF RATING WHEN OUTLETS ARE IN USE WITH CORDSPLUGGED IN.

MOUNT 30A, 3 PHASE, 600V, NEMA 1, NON-FUSED DISCONNECT IN LOCATION SHOWNFOR OVERHEAD DOOR OPERATORS. COORDINATE FINAL LOCATIONS WITH OVERHEADDOOR VENDOR.

MOUNT (1) 84 CIRCUIT PANELBOARD (PP-1) AS SHOWN. COORDINATE FINAL LOCATIONWITH OWNER. PANEL SHALL BE SURFACE MOUNTED. SEE RISER DIAGRAM ON E3.01FOR SPECIFICATIONS ON PANEL.

(3) #12 AWG, (1) #12 AWG GND, (1) 3/4" EMT CONDUIT.

PROVIDE OUTLET FOR SHRINK WRAP MACHINE. COORDINATE EXACT LOCATION ANDTYPE OF PLUG WITH OWNER.

1

SCALE:

1E1.01

WAREHOUSE POWER PLAN3/32" 1'-0"

1 2 3 4 5 6 7 8 9 10 11 12

A

B

C

D

E

F

G

25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0"

18'-0

"14

'-0"

28'-0

"18

'-0"

24'-0

"18

'-0"

KEY PLAN

MARK DESCRIPTIONDATE

Ch

icag

o L

um

ber

War

eho

use

Fac

ility

1234 S

outh

14th

Str

eet

Om

aha,

Neb

rask

a 6

8102

C:/R

&A

/p

ro

je

cts/0

90

1ch

ica

go

lu

mb

/D

ra

win

gs/D

ra

win

g S

et

E1.01

5

5

1

2

3

4

2

3

4

5

6

7

8

9

M

6

7

XX

PPL-XX,CKT XX

6

EF-2(ON ROOF)

L-6 L-5

L-1 L-2 L-3 L-4

COND-1(ON ROOF)

RTU-1(ON ROOF)

EF-1(ON ROOF)

10

9

EF-3(ON ROOF)

12

17

13

14

18

10

11

KEY NOTES:

PROVIDE 120V POWER TO L1-L6 LOUVERS. ROUTE (3) #12 AWG IN 3/4" EMT CONDUIT.ROUTE L-1, L-2, L-3, L-4 POWER TO BREAKER 30 IN PP-1. ROUTE L-5 AND L-6 POWER TOBREAKER 36 IN PP-1

(3) #12 AWG, (1) #12 GND, 3/4" EMT

PROVIDE 3Ø, 3 HP, NEMA 3R, COMBINATION MOTOR STARTER FOR EF-1 AND EF-2.PROVIDE 30A DISCONNECT AND 15A FUSES. SEE SPECIFICATION SECTION 16150 ONI1.04 FOR MORE INFORMATION.

RTU-1 DISCONNECT IS SUPPLIED WITH UNIT.

COND-1 DISCONNECT IS SUPPLIED WITH UNIT.

(3) #8 AWG, (1) #10 AWG GND, EMT

(2) #12 AWG, (1) AWG GND, EMT

CONNECT VENDOR SUPPLIED GFCI OUTLET TO CIRCUIT AS SHOWN.

PROVIDE FRACTIONAL HORSE POWER MANUAL STARTER WITH MELTING ALLOY TYPETHERMAL OVERLOAD RELAYS, ONE POLE FOR EF-3. EF-3 IS 120V, 1Ø, 1/6HP. PROVIDEWITH 30A DISCONNECT AND 15A FUSES. SEE SPECIFICATIONS SECTION 16150 ON I1.04FOR DETAILS. ROUTE CONDUCTORS UP TO EF-3 ON ROOF.

ROUTE CONTROL CIRCUITS TO LOUVERS L1-L6 AS SHOWN ON DETAIL 5 ON E5.01.COORDINATE WITH MECHANICAL CONTRACTOR.

ROUTE CONTROL CIRCUITS TO EF-1 AND EF-2 AS SHOWN ON DETAIL 6 ON E5.01.COORDINATE WITH MECHANICAL CONTRACTOR. SEE MECHANICAL SEQUENCE OFOPERATIONS.

ROUTE CONTROL CIRCUIT FOR EF-3 PER DETAIL 7 ON E5.01. COORDINATE WITHMECHANICAL CONTRACTOR.

(3) #10 AWG, EMT FOR RECEPT CIRCUIT.

12

13

14

15

16

17

18PPL-XX,CKT XX

PPL-XX,CKT XX

19 10 19 10 19 10 19

10 1910 19

20 12 20

6E5.01

(TYP. OF 2)

5E5.01

(TYP. OF 2)

22

7E5.01

T

19

20

21

22

ELDON E.

JENSEN II

E-13155

06-06-2013

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

20

0 31-05-2013 ISSUED FOR CONSTRUCTION

Page 4: E5bidroom.net/lundross/2013-06-27/4 electrical drawings.pdfxxx xxx xxx a b c s s 2 s 3 s 4 s te s o s d s ad s mc h o a area classification: area classification key non-hazardous -

GFCI

GFCI

GFCI

GFCI

+ 48"

GFCI

PP-1,CKT 22

PP-1,CKT 19

PP-1,CKT 38

PP-1,CKT 34

PP-1,CKT 28

PP-1,CKT 32

J

PP-1,CKT 31

PP-1

PP-1,CKT 24

PP-1,CKT 49, 51, 53

2

PP-1,CKT 37, 39

4

LEGEND GENERAL NOTES:1. SEE SHEET I1.02 FOR SYMBOLS LEGEND.

2. SEE SHEET I1.04 FOR GENERAL NOTES AND SPECIFICATIONS.

3. ELECTRICAL INSTALLATION SHALL ADHERE TO THE LATEST EDITION OF THE NATIONALELECTRIC CODE (N.E.C.) AND ALL APPLICABLE STATE AND LOCAL CODES.

4. LOCATION OF MECHANICAL EQUIPMENT IS SHOWN FOR INFORMATION ONLY. REFER TOMECHANICAL SHEETS FOR EXACT LOCATIONS.

5. DUPLEX RECEPTACLES SHALL BE MOUNTED AT 18" A.F.F. TO CENTER OF OUTLETEXCEPT WHERE NOTED OTHERWISE.

6. COORDINATE EXACT LOCATION OF DATA / TELEPHONE OUTLETS WITH OWNER.

7. FOR EACH DATA / TELEPHONE OUTLET SHOWN ROUTE (2) CAT 6 CONDUCTORS BACKTO TELEPHONE BOARD / DATA RACK AND COIL 10' FOR CONNECTION BY OTHERS.CONTRACTOR SHALL INSTALL OUTLET AND MAKE CONNECTIONS AT OUTLET. SEESPECIFICATIONS FOR PART # OF OUTLET.

8. ELECTRICAL DESIGN IS BASED ON ALL AREAS BEING RATED AS "S-1" OCCUPANCIES.ELECTRICAL CLASSIFICATION IS "NON-CLASSIFIED." ANY ACTIVITIES HANDLING ORSTORING FLAMMABLE MATERIALS COULD CHANGE THE ELECTRICAL CLASSIFICATION.FOLLOW ALL NEC REGULATIONS, NAMELY ARTICLES 500, 501, 502 AND 503.

JUNCTION BOX

COMBINATION TELEPHONE - DATA OUTLET

DUPLEX RECEPTACLE - RECEPTACLE: 20A, 120V, 3W, 2P (5-20R)

NON-FUSED DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

120V, 20A CIRCUIT TO PANEL AND BREAKER INDICATED. SHORTDASH INDICATES SWITCHED OR "HOT" CONDUCTOR, LONGDASH INDICATES NEUTRAL, ARC INDICATES GROUND. (3 #12AWG AND 3/4" EMT CONDUIT).

208V/240V, 20A CIRCUIT TO PANEL AND BREAKER INDICATED.SHORT DASHES INDICATES SWITCHED OR "HOT" CONDUCTORS,ARC INDICATES GROUND. (3 #12 AWG AND 3/4" EMT CONDUIT)

208V/480V 3PHASE 20A, CIRCUIT TO PANEL AND BREAKERINDICATED. SHORT DASHES INDICATES SWITCHED OR "HOT"CONDUCTORS, ARC INDICATES GROUND. (4 #12 AWG AND 3/4"EMT CONDUIT)

KEY NOTES:

PPL-XX,CKT XX

SCALE:

1E1.02

OFFICE POWER PLAN1/4" 1'-0"

CONTRACTOR SHALL MOUNT A 3'X4'X3/4" PLYWOOD IN THIS LOCATION FORTELEPHONE / DATA RACK.

(3) #10 AWG, (1) #12 AWG GND, 3/4" EMT.

PROVIDE 30A, 3P, 600V, NEMA 1 DISCONNECT WITH 30A FUSES FOR HOT WATERHEATER.

(2) #12 AWG, (1) #12 AWG GND, 3/4" EMT

UH-1 DISCONNECT IS PROVIDED WITH EQUIPMENT

PROVIDE 4X4 J-BOX FOR DRINKING FOUNTAIN CONNECTION

1

10987625'-0" 25'-0" 25'-0" 25'-0"

E

24'-0

"

F

G

18'-0

"

KEY PLAN

MARK DESCRIPTIONDATE

Ch

icag

o L

um

ber

War

eho

use

Fac

ility

1234 S

outh

14th

Str

eet

Om

aha,

Neb

rask

a 6

8102

C:/R

&A

/p

ro

je

cts/0

90

1ch

ica

go

lu

mb

/D

ra

win

gs/D

ra

win

g S

et

E1.02

J

XX

1

HWH-1

UH-1

3

2

3

4

PPL-XX,CKT XX

PPL-XX,CKT XX

5

5

ELDON E.

JENSEN II

E-13155

06-06-2013

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

6

6

0 31-05-2013 ISSUED FOR CONSTRUCTION

Page 5: E5bidroom.net/lundross/2013-06-27/4 electrical drawings.pdfxxx xxx xxx a b c s s 2 s 3 s 4 s te s o s d s ad s mc h o a area classification: area classification key non-hazardous -

DOWN TO 1STFLOOR SEE E1.01

PP-1,CKT 33PP-1,

CKT 35

LEGEND GENERAL NOTES:1. SEE SHEET I1.02 FOR SYMBOLS LEGEND.

2. SEE SHEET I1.04 FOR GENERAL NOTES AND SPECIFICATIONS.

3. ELECTRICAL INSTALLATION SHALL ADHERE TO THE LATEST EDITION OF THE NATIONALELECTRIC CODE (N.E.C.) AND ALL APPLICABLE STATE AND LOCAL CODES.

4. LOCATION OF MECHANICAL EQUIPMENT IS SHOWN FOR INFORMATION ONLY. REFER TOMECHANICAL SHEETS FOR EXACT LOCATIONS.

5. ELECTRICAL DESIGN IS BASED ON ALL AREAS BEING RATED AS "S-1" OCCUPANCIES.ELECTRICAL CLASSIFICATION IS "NON-CLASSIFIED." ANY ACTIVITIES HANDLING ORSTORING FLAMMABLE MATERIALS COULD CHANGE THE ELECTRICAL CLASSIFICATION.FOLLOW ALL NEC REGULATIONS, NAMELY ARTICLES 500, 501, 502 AND 503.

DUPLEX RECEPTACLE - RECEPTACLE: 20A, 120V, 3W, 2P (5-20R)

FUSED DISCONNECT SWITCH

120V, 20A CIRCUIT TO PANEL AND BREAKER INDICATED. SHORTDASH INDICATES SWITCHED OR "HOT" CONDUCTOR, LONGDASH INDICATES NEUTRAL, ARC INDICATES GROUND. (3 #12AWG AND 3/4" EMT CONDUIT).

PPL-XX,CKT XX

SCALE:

1E1.03

EQUIPMENT PLATFORM POWER PLAN1/4" 1'-0"

10987625'-0" 25'-0" 25'-0" 25'-0"

E

24'-0

"

F

G

18'-0

"

KEY PLAN

MARK DESCRIPTIONDATE

Ch

icag

o L

um

ber

War

eho

use

Fac

ility

1234 S

outh

14th

Str

eet

Om

aha,

Neb

rask

a 6

8102

C:/R

&A

/p

ro

je

cts/0

90

1ch

ica

go

lu

mb

/D

ra

win

gs/D

ra

win

g S

et

E1.03

ERV-1F-1

XX PROVIDE FRACTIONAL HORSE POWER MANUAL STARTER WITH MELTING ALLOY TYPETHERMAL OVERLOAD RELAYS. ONE POLE FOR FURNACE. SEE SPECIFICATION SECTION16150 ON I1.04 FOR DETAILS.

DISCONNECT FOR ERV-1 IS PROVIDED WITH EQUIPMENT. COORDINATE WITHMECHANICAL CONTRACTOR.

ROUTE CONTROL WIRING FOR ERV-1 INTERLOCKS AS SHOWN ON DETAIL 8 ON E5.01BACK TO FURNACE THERMOSTAT LOCATED IN CORRIDOR. COORDINATE WITHMECHANICAL CONTRACTOR. SEE MECHANICAL SEQUENCE OF OPERATIONS.

ROUTE 120V CIRCUIT TO IH-1 AND RH-1 FOR DAMPER POWER. ROUTE TO PP-1,BREAKER 56.

1

KEY NOTES:

2 1

2

PP-1

RH-1(ON ROOF)

IH-1(ON ROOF)

3 4

3 43

3

4

ELDON E.

JENSEN II

E-13155

06-06-2013

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

0 31-05-2013 ISSUED FOR CONSTRUCTION

Page 6: E5bidroom.net/lundross/2013-06-27/4 electrical drawings.pdfxxx xxx xxx a b c s s 2 s 3 s 4 s te s o s d s ad s mc h o a area classification: area classification key non-hazardous -

A B

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

B

B

B

B

A

B

B

B

B

B

B

A

B

A

A

J+14'-8" A.F.F.

J+21' A.F.F.

J+14'-8" A.F.F.

J+14'-8" A.F.F.

J+14'-8" A.F.F.

J+21' A.F.F.

J+21' A.F.F.

J+21' A.F.F.

J+14'-8" A.F.F.

J+14'-8" A.F.F.

PP-1,CKT 17

PP-1

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

35'-0" (TYP.)

20'-0

" (TY

P.)

PP-1,CKT 1, 3

1

PP-1,CKT 5, 7

1

PP-1,CKT 9, 11

1

PP-1,CKT 13, 15

1

PP-1,CKT 2, 4

1

PP-1,CKT 6, 8

1PP-1,CKT 10, 12

1

I

I

II

2

A BB

SCALE:

1E2.01

WAREHOUSE LIGHTING PLAN3/32" 1'-0"

1 2 3 4 5 6 7 8 9 10 11 12

A

B

C

D

E

F

G

25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0"

18'-0

"14

'-0"

28'-0

"18

'-0"

24'-0

"18

'-0"

KEY PLAN

LEGEND GENERAL NOTES:1. SEE SHEET I1.02 FOR SYMBOL LEGEND.

2. SEE SHEET I1.04 FOR GENERAL NOTES / SPECIFICATIONS.

3. ELECTRICAL INSTALLATION SHALL ADHERE TO THE LATEST EDITION OF THE NATIONALELECTRIC CODE (N.E.C.) AND ALL APPLICABLE STATE AND LOCAL CODES.

4. LIGHT FIXTURE MOUNTING HEIGHT ARE FROM TOP OF FINISHED FLOOR TO BOTTOM OFFIXTURE.

5. COORDINATE FINAL PLACEMENT OF FIXTURES WITH ARCHITECTURAL PLANS & FIELDVERIFY.

6. SEE E4.01 FOR PANELBOARD SCHEDULE.

7. SEE LUMINAIRE SCHEDULE ON E4.01 FOR FIXTURE MOUNTING HEIGHTS PER FIXTURETYPE.

8. PROVIDE OCCUPANCY SENSORS AS SHOWN. SENSORS SHALL BE MOUNTED AT 18'-0"A.F.F. SENSORS SHALL BE SENSOR SWITCH MODEL CMR6 208V OR APPROVED EQUAL.SEE WIRING DETAIL ON E5.02.

9. CARRY UNSWITCHED HOT LEG THROUGH TO EACH EMERGENCY BALLAST THATBYPASSES OCCUPANCY SENSOR OR SWITCHES.

10. ELECTRICAL DESIGN IS BASED ON ALL AREAS BEING RATED AS "S-1" OCCUPANCIES.ELECTRICAL CLASSIFICATION IS "NON-CLASSIFIED." ANY ACTIVITIES HANDLING ORSTORING FLAMMABLE MATERIALS COULD CHANGE THE ELECTRICAL CLASSIFICATION.FOLLOW ALL NEC REGULATIONS, NAMELY ARTICLES 500, 501, 502 AND 503.

11. MOUNT EXIT LIGHTS SHOWN ON THIS PAGE AT 10' A.F.F. FOR COLUMN MOUNTEDLIGHTS AND 12" ABOVE DOOR TO BOTTOM OF FIXTURE FOR LIGHTS ABOVE DOORS.

2'x4' FLUORESCENT LIGHT (LETTER DENOTES TYPE)

2'x4' FLUORESCENT LIGHT - EMERGENCY EGRESS LIGHT(LETTER DENOTES TYPE)

WALL PACK FIXTURE

OCCUPANCY SENSOR - CEILING MOUNT

EXIT LIGHT - CEILING MOUNT (SHADING INDICATES FIXTUREFACES) (DO NOT SWITCH OR CONNECT TO LIGHTING CONTROLPANEL)

120V, 277V CIRCUIT TO PANEL AND BREAKER INDICATED.SHORT DASH INDICATES SWITCHED OR "HOT" CONDUCTOR,LONG DASH INDICATES NEUTRAL, ARC INDICATES GROUND. (3#12 AWG AND 3/4" EMT CONDUIT UNLESS NOTED OTHERWISE)

208V/240V, 20A CIRCUIT TO PANEL AND BREAKER INDICATED.SHORT DASHES INDICATES SWITCHED OR "HOT"CONDUCTORS, ARC INDICATES GROUND. (3 #12 AWG AND 3/4"EMT CONDUIT)

PPL-XX,CKT XX

KEY NOTES:

(2) #10 AWG & (1) #12 AWG GND IN 3/4" EMT

(3) #10 AWG IN EMT

1

MARK DESCRIPTIONDATE

Ch

icag

o L

um

ber

War

eho

use

Fac

ility

1234 S

outh

14th

Str

eet

Om

aha,

Neb

rask

a 6

8102

C:/R

&A

/p

ro

je

cts/0

90

1ch

ica

go

lu

mb

/D

ra

win

gs/D

ra

win

g S

et

E2.01

PPL-XX,CKT XX

OS

4E5.02

(TYP.)

2E5.02

(TYP.)

5E5.02

(TYP.)

1E5.02

(TYP.)

2ELDON E.

JENSEN II

E-13155

06-06-2013

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

0 31-05-2013 ISSUED FOR CONSTRUCTION

Page 7: E5bidroom.net/lundross/2013-06-27/4 electrical drawings.pdfxxx xxx xxx a b c s s 2 s 3 s 4 s te s o s d s ad s mc h o a area classification: area classification key non-hazardous -

EF

H

H

C

D

3, 0

3, 0

0

S0S0

00

3

S

C

C C

C

CCC

C

C

CCC

C

C

C C C

D

D D

C

DD

D

PP-1,CKT 21

C

PP-1,CKT 29

I

I

I

I

K+8' A.F.F.

K+8' A.F.F.

OS

OSOS

PP-1

PP-1,CKT 23

S3

PP-1,CKT 25

UP TO LIGHTS ONEQUIPMENT

PLATFORM SEE E2.03

OS

PP-1,CKT 27

D

SCALE:

1E2.02

OFFICE LIGHTING PLAN1/4" 1'-0"

10987625'-0" 25'-0" 25'-0" 25'-0"

E

24'-0

"

F

G

18'-0

"

KEY PLAN

LEGEND GENERAL NOTES:1. SEE SHEET I1.02 FOR SYMBOL LEGEND.

2. SEE SHEET I1.04 FOR GENERAL NOTES / SPECIFICATIONS.

3. ELECTRICAL INSTALLATION SHALL ADHERE TO THE LATEST EDITION OF THE NATIONALELECTRIC CODE (N.E.C.) AND ALL APPLICABLE STATE AND LOCAL CODES.

4. LIGHT FIXTURE MOUNTING HEIGHT ARE FROM TOP OF FINISHED FLOOR TO BOTTOM OFFIXTURE.

5. COORDINATE FINAL PLACEMENT OF FIXTURES WITH ARCHITECTURAL PLANS & FIELDVERIFY.

6. SEE E4.01 FOR PANELBOARD SCHEDULE.

7. SEE LUMINAIRE SCHEDULE ON E4.01 FOR FIXTURE MOUNTING HEIGHTS PER FIXTURETYPE.

8. PROVIDE OCCUPANCY SENSORS AS SHOWN. SENSORS SHALL BE MOUNTED AT 18'-0"A.F.F. SENSORS SHALL BE SENSOR SWITCH MODEL CM6 WITH PP20 POWERPACK ORAPPROVED EQUAL. SEE WIRING DETAIL ON E5.02.

9. CARRY UNSWITCHED HOT LEG THROUGH TO EACH EMERGENCY BALLAST THATBYPASSES OCCUPANCY SENSOR OR SWITCHES.

10. ELECTRICAL DESIGN IS BASED ON ALL AREAS BEING RATED AS "S-1" OCCUPANCIES.ELECTRICAL CLASSIFICATION IS "NON-CLASSIFIED." ANY ACTIVITIES HANDLING ORSTORING FLAMMABLE MATERIALS COULD CHANGE THE ELECTRICAL CLASSIFICATION.FOLLOW ALL NEC REGULATIONS, NAMELY ARTICLES 500, 501, 502 AND 503.

PPL-XX,CKT XX

KEY NOTES:

INSTALL CEILING OCCUPANCY SENSORS AS SHOWN. SENSORS SHALL BE SENSORSWITCH CMG WITH PP20 POWER PACKS OR EQUAL. MOUNT SENSORS AT 16' A.F.F. SEEE5.02 FOR WIRING DIAGRAM.

MOUNT LIGHT UNDER SOFFIT AND ABOVE MIRROR. MOUNT AS CLOSE TO MIRROR ASPOSSIBLE. COORDINATE FINAL PLACEMENT WITH ARCHITECT.

1

MARK DESCRIPTIONDATE

Ch

icag

o L

um

ber

War

eho

use

Fac

ility

1234 S

outh

14th

Str

eet

Om

aha,

Neb

rask

a 6

8102

C:/R

&A

/p

ro

je

cts/0

90

1ch

ica

go

lu

mb

/D

ra

win

gs/D

ra

win

g S

et

E2.02

48" FLUORESCENT STRIP EMERGENCY LIGHT (LETTERDENOTES TYPE)

2'x4' FLUORESCENT LIGHT (LETTER DENOTES TYPE)

2'x4' FLUORESCENT LIGHT - EMERGENCY EGRESS LIGHT(LETTER DENOTES TYPE)

EMERGENCY LIGHT (LETTER DENOTES TYPE) (DO NOT SWITCHOR CONNECT TO LIGHTING CONTROL PANEL)

OCCUPANCY SENSOR - CEILING MOUNT

SINGLE POLE SWITCH - OCCUPANCY SENSOR

3 - THREE WAY SWITCH

120V, 277V CIRCUIT TO PANEL AND BREAKER INDICATED.SHORT DASH INDICATES SWITCHED OR "HOT" CONDUCTOR,LONG DASH INDICATES NEUTRAL, ARC INDICATES GROUND. (3#12 AWG AND 3/4" RGS CONDUIT

1

1

1

S0S3

OS

4E5.02

3E5.02

2E5.02

2

2

2ELDON E.

JENSEN II

E-13155

06-06-2013

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

1

0 31-05-2013 ISSUED FOR CONSTRUCTION

Page 8: E5bidroom.net/lundross/2013-06-27/4 electrical drawings.pdfxxx xxx xxx a b c s s 2 s 3 s 4 s te s o s d s ad s mc h o a area classification: area classification key non-hazardous -

C+8' A.F.F.

D+8' A.F.F.

DOWN TO1ST FLOORSEE E2.02

SCALE:

1E2.03

EQUIPMENT PLATFORM LIGHTING PLAN1/4" 1'-0"

10987625'-0" 25'-0" 25'-0" 25'-0"

E

24'-0

"

F

G

18'-0

"

KEY PLAN

LEGEND1'x4' FLUORESCENT LIGHT - PENDANT OR SURFACE MOUNT(LETTER DENOTES TYPE)

1'X4' FLUORESCENT EMERGENCY LIGHT - PENDANT ORSURFACE MOUNT (LETTER DENOTES TYPE)

MARK DESCRIPTIONDATE

Ch

icag

o L

um

ber

War

eho

use

Fac

ility

1234 S

outh

14th

Str

eet

Om

aha,

Neb

rask

a 6

8102

C:/R

&A

/p

ro

je

cts/0

90

1ch

ica

go

lu

mb

/D

ra

win

gs/D

ra

win

g S

et

E2.03

GENERAL NOTES:1. SEE SHEET I1.02 FOR SYMBOL LEGEND.

2. SEE SHEET I1.04 FOR GENERAL NOTES / SPECIFICATIONS.

3. ELECTRICAL INSTALLATION SHALL ADHERE TO THE LATEST EDITION OF THE NATIONALELECTRIC CODE (N.E.C.) AND ALL APPLICABLE STATE AND LOCAL CODES.

4. LIGHT FIXTURE MOUNTING HEIGHT ARE FROM TOP OF FINISHED FLOOR TO BOTTOM OFFIXTURE.

5. COORDINATE FINAL PLACEMENT OF FIXTURES WITH ARCHITECTURAL PLANS & FIELDVERIFY.

6. SEE E4.01 FOR PANELBOARD SCHEDULE.

7. SEE LUMINAIRE SCHEDULE ON E4.01 FOR FIXTURE MOUNTING HEIGHTS PER FIXTURETYPE.

8. CARRY UNSWITCHED HOT LEG THROUGH TO EACH EMERGENCY BALLAST THATBYPASSES OCCUPANCY SENSOR OR SWITCHES.

9. ELECTRICAL DESIGN IS BASED ON ALL AREAS BEING RATED AS "S-1" OCCUPANCIES.ELECTRICAL CLASSIFICATION IS "NON-CLASSIFIED." ANY ACTIVITIES HANDLING ORSTORING FLAMMABLE MATERIALS COULD CHANGE THE ELECTRICAL CLASSIFICATION.FOLLOW ALL NEC REGULATIONS, NAMELY ARTICLES 500, 501, 502 AND 503.

ELDON E.

JENSEN II

E-13155

06-06-2013

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

0 31-05-2013 ISSUED FOR CONSTRUCTION

Page 9: E5bidroom.net/lundross/2013-06-27/4 electrical drawings.pdfxxx xxx xxx a b c s s 2 s 3 s 4 s te s o s d s ad s mc h o a area classification: area classification key non-hazardous -

KEY NOTES:

GENERAL NOTES:1. SEE SHEET I1.04 FOR GENERAL NOTES AND I1.02 FOR SYMBOLS LEGEND.

2. ELECTRICAL CONTRACTOR SHALL COORDINATE INSTALLATION OF NEW SERVICE WITHOPPD AND ABIDE BY ALL OPPD REGULATIONS & PROCEDURES INVOLVING NEWELECTRICAL SERVICES.

3. SEE ELECTRICAL SITE PLAN E1.01 FOR LOCATIONS OF ELECTRICAL SERVICEEQUIPMENT.

SCALE:

1E3.01

OVERALL ONE-LINE DIAGRAMNOT TO SCALE MARK DESCRIPTIONDATE

Ch

icag

o L

um

ber

War

eho

use

Fac

ility

1234 S

outh

14th

Str

eet

Om

aha,

Neb

rask

a 6

8102

C:/R

&A

/p

ro

je

cts/0

90

1ch

ica

go

lu

mb

/D

ra

win

gs/D

ra

win

g S

et

E3.01

N - BUS

G - BUS

# 1/O GND

MAIN BONDINGJUMPER4

5 6 7

1

FROM UTILITYPOLE

M.C.B.400A3P

1

ELECTRICAL PANEL BOARD PP-1

400A, 120Y/208V, 3 - PHASE, 4 - WIRE, 65 KAIC

3

8

WH

2

7

#6 GND

XX

30A

SPD

10

ELECTRICAL CONTRACTOR TO PROVIDE MAST AND WEATHER HEAD FOR OVERHEADSERVICE CONNECTION PER OPPD AND NEC REQUIREMENTS.

ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ONE 320A 3 PHASE OPPDAPPROVED METER SOCKET.

ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL NEW SERVICE ENTRANCERATED SQUARE D NQ PANELBOARD WITH 84 CKTS, 400A MAIN BUS, 400A MAINBREAKER, 3P, 4W 120/208V. PANEL BOARD SHALL BE PROVIDED WITH BRANCHBREAKERS PER THE PANELBOARD SCHEDULE THIS SHEET. PROVIDE WITH FEEDTHROUGH LUGS. PANEL WILL BE SURFACE MOUNTED.

PROVIDE MAIN BONDING JUMPER TO CONNECT THIS GROUNDED SERVICECONDUCTOR, THE EQUIPMENT GROUNDING CONDUCTOR, AND THE SERVICEEQUIPMENT ENCLOSURE PER NEC 250.24. SIZE PER NEC TABLE 250.66.

BOND TO INCOMING MAIN WATER PIPE. PROVIDE BONDING STRAP AT WATER METERUNION/INSULATING JOINT LOCATION.

BOND TO BUILDING STEEL USING EXOTHERMIC WELD CONNECTION WHERE POSSIBLE.

BOND TO 3/4"X10' COPPER CLAD GROUND ROD.

BOND TO A CONCRETE ENCASED ELECTRODE PER NEC 250.52 AND OMAHA MUNICIPALCODE.

CONTRACTOR SHALL PROVIDE AND INSTALL 400A FUSED DISCONNECT WITH 400AFUSES, NEMA 3R RATED.

ELECTRICAL CONTRACTOR SHALL PROVIDE SURGE SUPPRESSIVE DEVICE, (SPD)PANEL. SPD SHALL BE SQ'D CAT #TVS2HWA10X. SPD SHALL BE NIPPLE MOUNTED TOPANEL. CONTRACTOR SHALL MINIMIZE THE CONDUCTOR USED TO THAT SUPPLIEDWITH SPD. SUPPLY 3 POLE BREAKER SIZED TO DEVICE.

ROUTE FEEDERS FROM DISCONNECT TO PP-1 UNDERGROUND AS SHOWN ON PLANS.ROUTE IN 4" PVC BELOW GRADE AND TRANSITION TO EMT FOR ABOVE GRADEPORTIONS.

1

2

3

4

5

6

7

8

9

10

400ADISC.

400AFUSES

(4) 500MCM(1) 1/O AWG GND(1) 4" EMT

(4) 500MCM(1) 1/O AWG GND(1) 4" PVC

9

(3) #10 AWG(1) #10 AWG GNDEMT CONDUIT

ELDON E.

JENSEN II

E-13155

06-06-2013

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

0 31-05-2013 ISSUED FOR CONSTRUCTION

11

11

Page 10: E5bidroom.net/lundross/2013-06-27/4 electrical drawings.pdfxxx xxx xxx a b c s s 2 s 3 s 4 s te s o s d s ad s mc h o a area classification: area classification key non-hazardous -

SCALE:

1E4.01

ELECTRICAL PANELBOARD PP-1 SCHEDULENOT TO SCALE

SCALE:

2E4.01

LUMINAIRE SCHEDULENOT TO SCALE

MARK DESCRIPTIONDATE

Ch

icag

o L

um

ber

War

eho

use

Fac

ility

1234 S

outh

14th

Str

eet

Om

aha,

Neb

rask

a 6

8102

C:/R

&A

/p

ro

je

cts/0

90

1ch

ica

go

lu

mb

/D

ra

win

gs/D

ra

win

g S

et

E4.01

LUMINAIRE SCHEDULETYPE USE LOCATION QTY MANUFACTURER CATALOG# VOLTS/WATTS MOUNTING

LAMP DATABALLAST OPTICS FINISH/COLOR NOTES

TYPE NO WATTSA WAREHOUSE 26 LITHONIA FGB24-6-54T5HO-N1/X20-MVOLT-2/3-GEB10PS-LP835-MSI360-IBAC120M20 208V / 324W PENDANT - 18' AFF T5HO 6 54 STD - 2/3 STD STD

B WAREHOUSE 14 LITHONIA FGB24-6-54T5HO-N1/X20-MVOLT-2/3-GEB10PS-LP835-MSI360-EL14-IBAC120M20 208V / 324W PENDANT - 18' AFF T5HO 6 54 STD - 2/3 STD STD PROVIDED WITH BATTERY BALLAST FOR EMERGENCY LIGHTING

C WORKSHOP 21 LITHONIA FGB164-4-32-N1/X20-PCL125WG-MVOLT-1/4-GEB10ISH-LP835-IBAC120M20 120V / 128W PENDANT - 16' AFF T8 4 32 STD - 1/4 STD STD

D WORKSHOP 7 LITHONIA FGB164-4-32-N1/X20-PCL125WG-MVOLT-1/4-GEB10ISH-LP835-EL14-IBAC120M20 120V / 128W PENDANT - 16' AFF T8 4 32 STD - 1/4 STD STD PROVIDED WITH BATTERY BALLAST FOR EMERGENCY LIGHTING

E OFFICE 1 LITHONIA 2M-4-32WT8-A12-MVOLT-1/4--GEB10IS-LP835 120V / 128W SURFACE T8 4 32 STD - 1/4 STD STD

F OFFICE 1 LITHONIA 2M-4-32WT8-A12-MVOLT-1/4-GEB10IS-LP835-EL14 120V / 128W SURFACE T8 4 32 STD - 1/4 STD STD PROVIDED WITH BATTERY BALLAST FOR EMERGENCY LIGHTING

G CORRIDOR 1 LITHONIA CB-2-32WT8-MVOLT-GEB10IS-EL 120V / 64W SURFACE T8 2 32 STD - 1/2 STD STD PROVIDED WITH BATTERY BALLAST FOR EMERGENCY LIGHTING

H RESTROOMS 2 LITHONIA W-2-32-MVOLT-GEB10IS 120V / 64W WALL - UNDER SOFFIT T8 2 32 STD - 1/2 STD STD

I EXITS 8 LITHONIA LQM-S-W-3-R-120/277-ELN 120V / 0.71W WALL 18" ABOVEDOORS LED 1 0.71 STD STD STD PROVIDED WITH BATTERY BALLAST FOR EMERGENCY LIGHTING

J WALLPACK 10 LITHONIA THWLED-20C-T3M-PE-DBLXD 120V / 72W WALL - PER PLANS LED 10 7.2 STD STD STD PROVIDE WITH INTEGRAL PHOTOCELL

K EMERGENCY 2 LITHONIA ELM2-LED 120V / 1.44W WALL - 8'AFF LED 2 0.72 STD STD STD PROVIDED WITH BATTERY BALLAST FOR EMERGENCY LIGHTING

ELDON E.

JENSEN II

E-13155

06-06-2013

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

0 31-05-2013 ISSUED FOR CONSTRUCTION

ELECTRICAL PANELBOARD 84 CKT SCHEDULEPANEL NAME: PP-1

PANEL LOCATION: WAREHOUSE VOLTAGE L-L: 208V

BUS CAPACITY (A): 400A VOLTAGE L-N: 120V

MAIN BRKR OR MLO: 400A MAIN BREAKER PANEL TYPE: 3PHASE, 4 WIRE

PANEL LOCATION: MOUNTING/ENCLOSURE: NEMA 1, SURFACE MOUNT

SHORT CIRCUIT RATING: 65KAIC FEEDER CIRCUIT SIZE: 500MCM

CBAMPS

NO.POLES

LGHTNG(VA)

RECEPT(VA)

OTHER(VA)

LOAD(VA) DESCRIPTION CKT NO. PHASE CKT NO. DESCRIPTION

LOAD(VA)

OTHER(VA)

RECEPT(VA)

LGHTNG(VA)

NO.POLES

CBAMPS

20 2 19441124 WAREHOUSE

LIGHTS ROW 11 A 2 WAREHOUSE

LIGHTS ROW 51124

1944 1 201124 3 B 4 1124

20 2 19441124 WAREHOUSE

LIGHTS ROW 25 C 6 WAREHOUSE

LIGHTS ROW 61124

1944 1 201124 7 A 8 1124

20 2 19441124 WAREHOUSE

LIGHTS ROW 39 B 10 WAREHOUSE

LIGHTS ROW 7936

1620 1 201124 11 C 12 936

20 2 1620936

WAREHOUSELIGHTS ROW 4

13 A 14 WAREHOUSERECEPS SOUTH 1080 1080 1 20

936 15 B 16 WAREHOUSERECEPS EAST 900 900 1 20

20 1 720 720 EXTERIOR LIGHTS 17 C 18 WAREHOUSERECEPS N/W 900 900 1 20

20 1 180 180 PHONE BOARDOUTLET IN CUST 19 A 20 SHRINK

WRAPPER

1400 1400 1 20

20 1 1024 1024 104 LIGHTS 21 B 22 ROOM 104RECEPS 720 720 1 20

20 1 1024 1024 WORKSHOPLIGHTS SOUTH 23 C 24 WORKSHOP

RECEPS SOUTH 540 540 1 20

20 1 1152 1152 WORKSHOPLIGHTS NORTH 25 A 26 ROOFTOP GFCI 180 180 1 20

20 1 768 768 102/STAGINGLIGHTS 27 B 28 WORKSHOP

RECEPS NORTH 900 900 1 20

20 1 832 832 OFFICE/LAV/ CUSTLIGHTS 29 C 30 L-1, L-2, L-3, L-4

LOUVERS 1500 1500 1 20

20 1 360 360 WATER FOUNTAIN 31 A 32 102/STAGINGRECEPS 720 720 1 20

15 1400

400 FURNACE F-1 33 B 34 OFFICE RECEPS 720 720 1 20

15 1 600 600 ERV-1 35 C 36 L-5, L-6 LOUVERS 0 1 20

20 2 3300

1908UH-1

37 A 38 LAV/HALL/CUSTRECEPS 720 720 1 20

1908 39 B 40COND-1

11562000 2 15

15 1 200 200 EF-3 41 C 42 1156

50 3 10000

3333

RTU-1

43 A 44NORTH GARAGEDOOR OPENER

200

600 3 153333 45 B 46 200

3333 47 C 48 200

30 3 6000

2000

HWH-1

49 A 50SOUTH GARAGEDOOR OPENER

200

600 3 152000 51 B 52 200

2000 53 C 54 200

15 3 2250

750

EF-1

55 A 56 RH-1, IH-1

POWER

0 1 20

750 57 B 58 SPARE 0 1 20

750 59 C 60 SPARE 0 1 20

15 3 2250

750

EF-2

61 A 62 SPARE 0 1 20

750 63 B 64 SPARE 0 1 20

750 65 C 66 SPARE 0 1 20

20 1 0 SPARE 67 A 68 SPARE 0 1 20

20 1 0 SPARE 69 B 70 SPARE 0 1 20

- 1 0 BLANK 71 B 72 BLANK 0 1 -

- 1 0 BLANK 73 B 74 BLANK 0 1 -

- 1 0 BLANK 75 B 76 BLANK 0 1 -

- 1 0 BLANK 77 B 78 BLANK 0 1 -

- 1 0 BLANK 79 B 80 BLANK 0 1 -

- 1 0 BLANK 81 B 82 BLANK 0 1 -

- 1 0 BLANK 83 B 84 BLANK 0 1 -

CONNECTED D.F. DEMAND

LIGHTING LOAD 18,480 1.25 23,100

RECEPTACLE (FIRST 10KVA) 9,320 1.00 9,320

RECEPTACLE (REMAINDER) 0 0.50 0

LARGEST OTHER 10,000 1.25 12,500

REMAINING OTHERS 19,700 1.00 19,700

SUB FEED PANEL 0 1.00 0

TOTAL VA 57,500 64,620

TOTAL AMPS 159.61 179.37

Page 11: E5bidroom.net/lundross/2013-06-27/4 electrical drawings.pdfxxx xxx xxx a b c s s 2 s 3 s 4 s te s o s d s ad s mc h o a area classification: area classification key non-hazardous -

THREADED HUB (TYP.)

PIPE CLAMP SUPPORT (TYP.) ATTACH TO BUILDINGSTRUCTURE

BOLT ENCLOSURE TOTHESE MEMBERS MINIMUMOF FOUR PLACES

PANELBOARD, JUNCTIONBOX, OR OTHER LOCALELECTRICAL ENCLOSURE

S.S. STRUT OR ANGLE(TYPICAL)

S.S.POST BASE

LEVELING BOLTS

EXPANSION ANCHORS

CONCRETE FLOOR

1" OF GROUT

S.S. STRUT OR ANGLE(TYP)

RIGID CONDUIT (TYP.)

SCALE:

2E5.01

PANELBOARD INSTALLATION DETAILNOT TO SCALE

* MAXIMUM LOAD ALLOWED FOR ATR, ACTUALLOAD MAY BE DETERMINED BY STRUCTURAL

STEEL CAPACITY.

BEAM CLAMPOR BOLT

ATR ALLOWABLELOAD

SIZE LBS. (KN)

3/8"-16 610 (2.71)

1/2"-13 1130 (5.02)

5/8"-11 1810 (8.05)

3/4"-10 2710 (12.05)

7/8"-9 3770 (16.77)

HEX NUT &WASHER

L3X3X1/4

LOAD

THREADED ROD

UNISTRUT PIPE CLAMPSIZE AS REQUIRED

CONDUIT3/8" HEX NUT

3/8" X 1 3/4" ROD COUPLINGZINC PLATED (AS NEEDED)

3/8" THREADED ROD

(2) 3/8" HEX NUTSZINC PLATED

P1001 UNISTRUT

AS NEEDED

NOTES:SEE E1.1 SECTION 16130.117 FOR CONDUIT TRAPEZE SUPPORT SPACING

NEW HEAD FLASHING EXTENDOVER JAMB FLASHING W/DRIP

JAMB FLASHING AND TRIMINSTALLED TO "CLOSE" EDGEOF PANEL

CUT SQUARE HOLECONDUIT O.D. PLUS 4"

CAULK ALL AROUNDFOR WATERTIGHT SEAL

.O5O SPLIT FACE ALUM SHEETSILL CAP FLASHING EXTENDUNDER JAMB FLASHING

CLOSURE AS REQUIRED FOR "AIRTIGHT SEAL" AND CAULKED (TYP)

LOCKNUT, FLAT WASHER ANDNEOPRENE GASKET, EACH SIDE

NEW HEAD FLASHING EXTENDOVER JAMB FLASHING W/DRIP

FIRE RATED PACKING ORINSULATION AS REQUIRED BY CODE

INSIDEOUTSIDE

NOTE:FOR SMALLER CONDUIT WHERE OUTERDIAMETER OF FLAT WASHER IS LESSTHAN THE AVAILABLE FLAT AREA ONTHE METAL WALL PANEL, THE PANELMAY BE HOLE PUNCHED AND THEWASHERS AND LOCKNUTS TERMINATEDON THE WALL PANEL WITHOUT CUTTINGTHE SQUARE HOLE AND INSTALLINGFLASHING.

NOTE:ALL MATERIALS TO BE .050ALUM TO MATCH COLOR OFWALL PANEL.

SCALE:

1E5.01

TYPICAL BEAM CONNECTION DETAILNOT TO SCALE SCALE:

3E5.01

TYPICAL CONDUIT WALL PENETRATIONS - METAL WALL DETAILNOT TO SCALE SCALE:

4E5.01

CONDUIT TRAPEZE HANGER DETAILNOT TO SCALE

MARK DESCRIPTIONDATE

Ch

icag

o L

um

ber

War

eho

use

Fac

ility

1234 S

outh

14th

Str

eet

Om

aha,

Neb

rask

a 6

8102

C:/R

&A

/p

ro

je

cts/0

90

1ch

ica

go

lu

mb

/D

ra

win

gs/D

ra

win

g S

et

E5.01

NOTES:1. COORDINATE LOCATION OF MECHANICAL EQUIPMENT WITH MECHANICAL CONTRACTOR.2. COORDINATE TERMINATIONS IN THERMOSTAT WITH MECHANICAL CONTRACTOR.3. UPSIZE CONDUCTORS AS REQUIRED BY NEC FOR VOLTAGE DROP ON LONG RUNS.4. DETAIL IS TYPICAL OF 6 LOUVERS.5. ALL WIRING BY ELECTRICAL CONTRACTOR.

SCALE:

5E5.01

LOUVER L1-L6 WIRINGNOT TO SCALE

TO EXHAUST FANTIMER PANEL

SEE E1.01CR

120V N GND

LOUVERMOTOR

120VAC CIRCUITPER PLANS

120VAC CIRCUITPER PLANS

NOTES:1. COORDINATE LOCATION OF MECHANICAL EQUIPMENT WITH MECHANICAL CONTRACTOR.2. COORDINATE TERMINATIONS IN THERMOSTAT WITH MECHANICAL CONTRACTOR.3. UPSIZE CONDUCTORS AS REQUIRED BY NEC FOR VOLTAGE DROP ON LONG RUNS.4. ALL WIRING BY ELECTRICAL CONTRACTOR.

SCALE:

6E5.01

EXHAUST FAN EF-1, EF-2 WIRINGNOT TO SCALE

FU M OL

FU

FU

M

M

OL

OL

TO THERMOSTATSEE PLANS CR

(3) #12 AWG, EMT120VAC CIRCUIT

M

EFDAMPEREND SWITCH

M EXHAUSTFAN

COMBINATION MOTOR STARTER3Ø CIRCUITPER PLANS

L1

L2

L3

GND208V

120VCPT

G

N

120V

EFDAMPER

120V

N

EF-3DAMPER

+120V

N

G

EFDAMPER

END SWITCH

M EF-3MOTOR

NOTES:1. COORDINATE LOCATION OF MECHANICAL EQUIPMENT WITH MECHANICAL CONTRACTOR.2. COORDINATE TERMINATIONS IN THERMOSTAT WITH MECHANICAL CONTRACTOR.3. UPSIZE CONDUCTORS AS REQUIRED BY NEC FOR VOLTAGE DROP ON LONG RUNS.4. ALL WIRING BY ELECTRICAL CONTRACTOR.

SCALE:

7E5.01

EF-3 WIRING DIAGRAMNOT TO SCALE

120V CIRCUITPER PLANS

SINGLE PHASEFRACTIONAL HP STARTER

FURNENABLE

CR

120 N GND

RH-1DAMPER

IH-1DAMPER

THERMOSTAT

BY MECHANICALCONTRACTOR

24VDC

120V CKTPER PLANS

LOCALDISCONNECT

120V

N

G

ERVMTR

120V CKTPER PLANS

NOTES:1. COORDINATE LOCATION OF MECHANICAL EQUIPMENT WITH MECHANICAL CONTRACTOR.2. COORDINATE TERMINATIONS IN THERMOSTAT WITH MECHANICAL CONTRACTOR.3. UPSIZE CONDUCTORS AS REQUIRED BY NEC FOR VOLTAGE DROP ON LONG RUNS.4. ALL WIRING BY ELECTRICAL CONTRACTOR.

SCALE:

8E5.01

ERV-1 WIRING DIAGRAMNOT TO SCALE

CR

CRCR

IH-1 ENDSWITCH

RH-1 ENDSWITCH

ELDON E.

JENSEN II

E-13155

06-06-2013

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

0 31-05-2013 ISSUED FOR CONSTRUCTION

Page 12: E5bidroom.net/lundross/2013-06-27/4 electrical drawings.pdfxxx xxx xxx a b c s s 2 s 3 s 4 s te s o s d s ad s mc h o a area classification: area classification key non-hazardous -

REDBLK

WHT

N H

UNSWITCHED HOT LEG FOREMERGENCY BALLASTS.

LIGHT LOAD

SENSOR SWITCHCM6

OCCUPANCY SENSOR #2

SENSOR SWITCHCM6

OCCUPANCY SENSOR #1

WHTBLK / ORN

BLU

J-BOXSENSOR SWITCH

PP-20

LIGHTING CIRCUIT

WALLSWITCH

TOADDITIONALSENSORS

3/4" EMT

2X4 1 GANG CAST BOX

OCCUPANCY SENSORMOUNT @ SAMEELEVATION ASLIGHTING

WHTBLKBLU

H H

UNSWITCHED HOT LEG FOREMERGENCY BALLASTS.

LIGHT LOAD

SENSOR SWITCHCMR6

208

LIGHTING CIRCUIT

OCCUPANCY SENSOR

NEW LIGHT FIXTURE &BULBS (PER LUMINAIRESCHEDULE)

SCALE:

2E5.02

FLUORESCENT LIGHT MOUNTING DETAIL #1NOT TO SCALE SCALE:

3E5.02

OCCUPANCY SENSOR WIRING DETAILNOT TO SCALE

SCALE:

4E5.02

OCCUPANCY SENSOR MOUNTING DETAILNOT TO SCALE SCALE:

5E5.02

OCCUPANCY SENSOR WIRING DETAILNOT TO SCALE

MARK DESCRIPTIONDATE

Ch

icag

o L

um

ber

War

eho

use

Fac

ility

1234 S

outh

14th

Str

eet

Om

aha,

Neb

rask

a 6

8102

C:/R

&A

/p

ro

je

cts/0

90

1ch

ica

go

lu

mb

/D

ra

win

gs/D

ra

win

g S

et

E5.02

HORIZONTAL SECTIONTHROUGH FIXTURE AND SIDING

ELEVATIONMOUNTING PLATE

1/4" STAINLESS STEELMETAL SCREWS (TYP.)

HOLE FOR 1/2" CONDUIT

FIXTURE OUTLINE

WALL BRACKET SUPPLIEDWITH FIXTURE

3/4" STEEL LOCKNUT (USESTEEL AND NEOPRENE WASHERS)COAT CONDUIT TREADS WITH "ZINCRICH" TO PREVENT RUST RUNS

CORRUGATED FLAT OR METAL SIDING

CONDUIT FITTINGS AS REQ'D

3/4" IMC CONDUIT LENGTH AS REQ'D

LIGHT FIXTURE

MOUNTING PLATE

INSULATION

FIXTURE MOUNTINGSCREWS (TYP.)

B-LINE D314BEAM CLAMP

(TYP: 2 PLACES)

STEAL ROOFPURLINS

1/2" FLEXIBLE METALLICCONDUIT WHIP. PURCHASEWHIP PREWIRED WITH FIXTURE(SUPPORT PER NEC)

4X4 -BOX

EMT CONDUIT

GALVANIZED METALSTRUT CHANNEL

CONDUIT CLAMP

SCALE:

1E5.02

WALL PACK LIGHT FIXTURE MOUNTING DETAILNOT TO SCALE

V-BRACKET(CONTRACTORSUPPLIED WITH LIGHT) 1/8" COATED AIRCRAFT CABLE

(CONTRACTOR SUPPLIED WITH LIGHT)

BLKBLU

ELDON E.

JENSEN II

E-13155

06-06-2013

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

3635 South 149th Street Omaha, NE. 68144P (402) 884-8650 F (402) 884-8651 www.eadengineering.com

0 31-05-2013 ISSUED FOR CONSTRUCTION