+ All Categories
Home > Documents > Electrical Skills Lab Manual

Electrical Skills Lab Manual

Date post: 07-Jul-2018
Category:
Upload: murali-krishna
View: 230 times
Download: 1 times
Share this document with a friend

of 112

Transcript
  • 8/18/2019 Electrical Skills Lab Manual

    1/112

     Shinas ollege of Technology

    Engineering Department  

       E   E   l   l   e   e   c   c   t   t   r   r   i   i   c   c   a   a   l   l   s   s   k   k   i   i   l   l

       l   l   s   s

       L   A   B   O   R   A   T   O   R   Y   M   A   N   U   A   L

    Course Code: EEPW2241   AY 2015-2016  Semester: 2 ID No.: Name of the Student:

    Section No. Level: Specialization:

  • 8/18/2019 Electrical Skills Lab Manual

    2/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

  • 8/18/2019 Electrical Skills Lab Manual

    3/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    CONTENTS

    Experiment

    No.Name of the Experiment

    Page

    No.

    Table of contents

    Course objectives, outcomes

    Course assessment scheme

    Laboratory rules

    General safety precautions and guidelines

    in the ELECTRICAL SKILLS lab

    Introduction

    1 Electrical Supply

    2 Measurement of the Earth Resistance

    3 Preparation of Galvanized Steel Conduit

    4 Wiring Lighting Circuit

    5 Testing Wiring Circuits

    6 Connection of Fluorescent Tube Light

    7 Sodium Vapor Lamps

    8Connection and Trouble Shooting of Fan

    Circuit

    9 Metal Halide Lamps

  • 8/18/2019 Electrical Skills Lab Manual

    4/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    COURSE OUTCOMES:

    EEPW2241: ELECTRICAL SKILLS

    Prerequisites: Engineering Workshop (EEPW 1240)

    Goal: To provide the students with the concepts, techniques and applications of

    electrical workshop

    Objectives Outcomes

    This course should enable the

    student to:

    1.  Know the safety practices in

    the workshop and production

    areas.2.  Understand the aspects of

    electrical installation

    techniques.

    3.  Understand how to assemble

    steel conduit.

    4.  Understand how to wire

    lighting and circuits.

    5.  Understand the concepts ofconstruction of DC and single-

    phase AC motors.

    6.  Know different methods of

    protections.

    7.  Understand how to control

    circuits of single phase AC

    motors.

    Upon completion of the course, the student will be

    able to:

    1.  Familiarize and apply the electricity safety

    rules in Oman and in IEE regulation.

    2.  Describe the power distribution systems,Earthing arrangement, electrical bonding,

    PME supplies and current protective

    conductors.

    3.  Prepare for assembling steel conduit.

    4.  Wire lighting and power circuits.

    5.  Assemble and connect fluorescent and sodium

    vapour lamps.

    6.  Test the wiring circuits like visual inspectiontest, continuity test and insulation resistance

    test.

    7.  Define the fault diagnosis techniques in

    electrical insulations.

    8.  Describe the construction of DC and single

    phase AC motor.

    9.  Construct bell indictor circuits.

    10. Apply different methods of circuit’sprotection.

    11. Control the circuits of single-phase AC motors.

  • 8/18/2019 Electrical Skills Lab Manual

    5/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Sources:

    I. Text Books

    1. “Electrical Installation work, Brain McAdam, Elsevier 4Th Edition. 

    2. Electrical skills, Ministry Manual.

    II. Reference Books

    3. “Electrical Engineering, “Allen R Pearson Prentice Hall. 

    4. “Basic Electrical Installation Work’’, Trevor Linsley, Newness(ACT)

    5. “Electrical Installation”, Thompson FG, Longman (NCT), 4Th Edition. 6. “Electrical Technology”, BL Theraja & AK Theraja S Chand Publications. 

    7. “Residential Construction Academy”, Stephen Herman, Thompson Publisher. 

    8. “Electrical Instant Answer” Garg Tuck, MC Graw Hill Publications. 

    III. Web sites

    http://www.ehcoman.com

    http://www.majanco.co.om

  • 8/18/2019 Electrical Skills Lab Manual

    6/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    COURSE ASSESSMENT METHODS

     Assessment Scheme (Total Practical Courses)

    Course Grading Scheme

    Course Passing Grade : 67-69 (C grade)*

    * Depends on the course

    Marks Grade GPA

    90-100 A 4.0

    85-89 A- 3.7

    80-84 B+ 3.3

    76-79 B 3.073-75 B- 2.7

    70-72 C+ 2.3

    67-69 C 2.0

    60-66 C- 1.7

    55-59 D 1.0

    Below 55 F 0.0

    Graduation Grading Scheme

    Below grade is displayed in the graduation certificate and it is based on the Overall CGPA ofall levels.

    Descriptive GradeGradeOverall CGPA

    Excellent A 4

     A- 3.7-3.99

    Very Good B+ 3.3-3.3.69

    B 2.-23  

    Good B- .-.2  

    C+ .2-.2  

    Satisfactory C .2.-.23  

    Fail 

    C- 

    92-92  

    D 92-923  

    F 0.0-.99

  • 8/18/2019 Electrical Skills Lab Manual

    7/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

     Assessment Methods

    (Total Practical Courses)

    Theory (T) Practical (P)

    Not Applicable

    Lab report 45 marks

    Viva-Voce 15 marks

    Written Questionnaire 40

    marks

    100 % Practical part marks= Total marks out of 100

     Assessment scheme for the Lab work

    Part I: Lab report with data collection and analysis–

     45 Marks

    Part II: One Viva-voce – 15 marks 

    Part III- Written questionnaire – 40 Marks

    In this part the student is subject to frequent written questionnaire about the performed

    experiments. It may include experimental data collection. A minimum of three written

    assessments are to be conducted (i.e. n > 3, where n= no. of practical assessments

    conducted). Best of (n-1) performances to be considered for final marks.  All written

    assessments are announced. 

  • 8/18/2019 Electrical Skills Lab Manual

    8/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

     Attendance:

    Issuing of Warning Letter Percentage Number of Hours

    First 10%

    Second 20%

    Third 30%

      If the absence reaches 30%, the student will be debarred from the final exam and will

    get ZERO in the final exam.

      A student will be considered as LATE when s/he arrives after 10minutes of the class

    start time. Being LATE for THREE times in a class will be considered as ONE class

    absence.

      The full course delivery plan must be covered. If students are absent without a valid

    reason, it will be considered as if the topic/s is already covered and will be included

    in exams.

      If a student is absent for two continuous weeks within the semester in all courses,

    s/he will be DISMISSED from the College.

     Absence Excuse:

      If a student failed to attend any class, s/he has to submit the original excuse

    document within one week from the date of absence to registration department

    only.

      If a student failed to attend midterm or final exam, s/he has to fill in aSupplementary Exam Form attached with the original excuse stamped from

    concern authorities and submit it to the registration department within one week

    from the exam date. Hospital/Clinic Attendance Certificate is not accepted as a

    valid excuse.

      The coverage of topics in the midterm supplementary exam will include topics

    covered up to the midterm exam + topics covered one week after the midterm

    exam.

      The final complementary exam will be conducted within four weeks from thestart of next semester. 

  • 8/18/2019 Electrical Skills Lab Manual

    9/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Course Withdrawal

    A student is allowed to withdraw one course during the semester. The withdrawal

    period will end a week after the midterm exam resultannouncement.

    Submission of Assignment

    20% of assignment scored mark will be reduced for each day of late submission.

    Cheating

    In case of an accusation of cheating during an examination is proven, the following will

    be imposed:

    Disciplinary Action for Cheating Case/s:

      First Offense (Zero Mark)

      Second Offense (Study Suspension for one semester)

      Third Offense (Dismissal from the College)

  • 8/18/2019 Electrical Skills Lab Manual

    10/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Theory (T) Practical (P)

    Not Applicable

    Lab report 45 Marks 

    Viva-Voce 15 Marks 

    Written Questionnaire 40 Marks100 % Practical part marks= Total marks out of 100

    Part I- Lab report with data collection and analysis – 45 marks

    No. Factors Marks

    1 Ability to follow procedure, data collection 10

    2Data analysis, interpretation of results & conclusions related to

    the objectives and course outcomes10

    3

    Completeness, accuracy and

    correctness of data and results (Figures, graphs, tables, units,

    software)

    20

    4 Submission on time 05

    Total 45 marks

    Part II: One Viva-voce – 15 marks

    Part II- Written questionnaire – 40 marks

    In this part the student is subject to frequent written questionnaire about the performed

    experiments. It may include experimental data collection. A minimum of three written

    assessments are to be conducted (i.e. n > 3, where n= no. of practical assessments

    conducted). Best of (n-1) performances to be considered for final marks.  All writtenassessments are announced.

    Total weightage for all the above procedures (Part I + Part II+ Part III) is 100%

  • 8/18/2019 Electrical Skills Lab Manual

    11/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    WRITING LAB REPORT

    1.  Each Student has to write a Lab report on each Experiment / Exercise performed &

    submit the report within one week.

    2.  But if the student fails to submit the report within one week, he/she will loose 1

    mark each day till the report is submitted.

    3. 

    After the completion of each experiment student must take the signature of course

    Lecturer on the cover page.

    4. 

    Attach the cover page to each Lab report before submission.

    5. 

    The report must be written on plane A4 sheets & preferably on both sides of the

    paper

    6. 

    Neat report with all the required data, graph, units and conclusion will get better

    marks.

  • 8/18/2019 Electrical Skills Lab Manual

    12/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Dos and Don’ts: 

    Dos:

    1.  Before starting Laboratory work follow all written and verbal instructions

    carefully. If you do not understand a direction or part of a procedure, ASK YOURCONCERN TEACHER BEFORE PROCEEDING WITH THE ACTIVITY

    2.  Do your wiring, setup, and a careful circuit checkout before applying power.

    3.  Conduct yourself in a responsible manner at all times in the laboratory. Don’t talk

    aloud or crack jokes in lab.

    4.  Appropriate Personal Protective Equipment should be worn during laboratory

    experiments.

    5.  Do not eat food, drink beverages or chew gum in the laboratory and do not use

    laboratory glassware as containers for food or beverages. Smoking is strictlyprohibited in lab area

    Don’ts 

    1.  Avoid contact with energized electrical circuits. 

    2.  Do not make circuit changes or perform any wiring when power is on. 

    3.  Do not wear loose-fitting clothing or jewelry in the lab. Rings and necklaces areusual excellent conductors in contact with your skin. 

    4.  Do not touch anything if your hands are wet. The "one-hand" approach is safest. 

    5.  Do not wander around the room, distract other students, startle other students or

    interfere with the laboratory experiments of others

  • 8/18/2019 Electrical Skills Lab Manual

    13/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Electrical Accidents/ Hazards are attributed to: 

      Shock/ Electrocution

      Arcing

      Fire

      Explosion

    Which result in:

      Loss of Life

      Loss of Property 

    Safety First  SAFETY CLOTHING MUST BE WORN SAFETY SHOES MUST BE

    WORN

    Boys Girls

  • 8/18/2019 Electrical Skills Lab Manual

    14/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Introduction

    Electricity and related water sector in Sultanate of Oman

    The Law for The Regulation and Privatization of the Electricity andRelated Water Sector (the Sector Law) was promulgated by Royal Decree

    # 78/2004 and came into effect on 1 August 2004.

    Reference : http://www.ehcoman.com 

    http://www.ehcoman.com/http://www.ehcoman.com/http://www.ehcoman.com/http://www.ehcoman.com/

  • 8/18/2019 Electrical Skills Lab Manual

    15/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Electricity Distribution in Oman: Geographical Coverage 

    Reference : http://www.ehcoman.com 

    Majan Electricity Company: Profile

    Majan through its systems, processes and people offers sustainable

    management of electricity with the purpose of serving the people of Omanby delivering safe, reliable and economical electricity. * 

    Reference : http://www.majanco.co.om 

    http://www.ehcoman.com/http://www.ehcoman.com/http://www.ehcoman.com/http://www.majanco.co.om/http://www.majanco.co.om/http://www.majanco.co.om/http://www.majanco.co.om/http://www.ehcoman.com/

  • 8/18/2019 Electrical Skills Lab Manual

    16/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Regulation Describe about

    OES 1 33KV & 11KV Overhead Lines

    OES 2 Underground Cables

    OES 3 LT Overhead Lines  

    OES 4 Electrical Installations in Buildings

    General Derogation OES 4 clause 6.5 Use of PVC Conduits

    OES 5, 5A & 6 Transformers

    OES 7, 21, 22, 23, 28 & 31 LT Equipment

    OES 8,9,10,16,17,18,20,25, 26, 29 &

    33Overhead Line Material & Equipment

    OES 11General Specifications Electrical Equipment &

    Materials

    OES 21A, 12B, 13, 14, 15, 19, 34 & 35 Switchgear & Associated Equipment

    OES 24 3311KV Indoor Substations

    OES 27 Volume 1 132 33KV Substations

    OES 27 Volume 2 132 33KV Substations

    OES 30 33 11KV Outdoor Substation

    OES 32 132KV OHL

    http://www.aer-oman.org/pdf/o2.pdfhttp://www.aer-oman.org/pdf/o3.pdfhttp://www.aer-oman.org/pdf/o4.pdfhttp://www.aer-oman.org/pdf/o4.pdfhttp://www.aer-oman.org/pdf/o5.pdfhttp://www.aer-oman.org/pdf/o5.pdfhttp://www.aer-oman.org/pdf/o4.pdfhttp://www.aer-oman.org/pdf/o3.pdfhttp://www.aer-oman.org/pdf/o2.pdf

  • 8/18/2019 Electrical Skills Lab Manual

    17/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    STANDARD OES 4

    Ministry of Electricity and Water (now MHEW), Sultanate of Oman has

    issued REGULATIONS FOR ELECTRICAL INSTALLATIONS known as

    STANDARD OES 4 which is available at

    http://www.aer-oman.org 

    BS 7671:2008

    •  This British Standard specifies the “Requirements for Electrical

    Installations” 

    •  It is also known as IEE Wiring Regulations

    •  The regulations apply to the design, erection, and verification of

    electrical installations.

    •  These regulations are updated and applicable in the region.

  • 8/18/2019 Electrical Skills Lab Manual

    18/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    STANDARD OES 4

    Scope and Coverage

    (Where to use the standard?)

    The regulations apply to electrical installations such as those of,

     –  Residential Premises

     –  Commercial Premises

     –  Public Premises

     –  Industrial Premises

     –  Agricultural and Horticultural Premises

     –  Prefabricated Buildings

     –  Construction Sites, Exhibitions, Fairs and other temporary installations.

    The regulations cover,

     –  Circuits supplied at normal voltages up to and including 415/240 V AC 50

    Hz.

     –  Any wiring not specifically covered by the specifications of appliances.

     –  Fixed wiring for telecommunications, signaling, control (excluding external

    wiring of apparatus).

    Reference:  STANDARD OES 4, SECOND EDITION, MAY 1989

  • 8/18/2019 Electrical Skills Lab Manual

    19/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    ELECTRICAL STANDARD

    Compliance with Regulations

    (Why to use/meet the standard?)

    Compliance with electrical regulations is essential to ensure safety of life,

    plant, equipment and buildings especially from the hazards of fire, electrical

    shocks and mishaps in the utilization of electricity in and around buildings.

    PROTECTION AGAINST ELECTRIC SHOCK  

    In electrical installations, one of the major risks is electric shock. Persons and

    livestock (animals) shall be protected against dangers that may arise,

    a.  from contact with live parts of the installation by:

     –  appropriate measures to prevent contact; ISOLATION  

     –  Limiting the value and duration of current which can pass through a body to

    a value lower than shock current. INSULATION  

    b.  From contact with exposed metal parts by one of the following methods.

     –  Preventing a fault current from passing through the body of any person or

    any livestock. EARTHING  

     –  Limiting the value and duration of current which can pass through a body to

    a value lower than shock current. INSULATION  

     –  Automatic disconnection of the supply on the occurrence of a fault likely tocause a current to flow through a body in contact with the exposed metal

    parts, where the value of the current is equal to or greater than the shock

    current . ISOLATION  

    PROTECTION AGAINST THERMAL EFFECTS 

    Another major risk with the electrical installations is excessive temperature

    likely to cause burns, fires and other injurious effects.

    Protection shall be provided against

     –  The harmful effects of heat or thermal radiation developed by electricalequipment.

     –  Ignition, combustion or degradation or material.

    Reference: BS7671-2008

     –  flame and smoke where a fire hazard could be propagated from an electrical

    installation to other nearby fire compartments and

  • 8/18/2019 Electrical Skills Lab Manual

    20/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

     –  Safety services being cutoff by the failure of electrical equipment.

    PROTECTION AGAINST OVERCURRENT 

    Persons or livestock shall be protected against injury and property shall be

    protected against damage due to excessive temperatures or electro-mechanical

    stresses caused by over currents likely to arise in live conductors by,

     –  Automatic disconnection on the occurrence of over-current before the over-

    current attains a dangerous value taking into account its duration.

     –  Limiting the maximum over-current to a safe value and duration.

    Conductors other than live conductors and any other parts intended to carry a

    fault-current shall be capable of carrying that current without assuming excessive

    temperature.

    PROTECTION AGAINST VOLTAGE DISTURBANCES AND ELECTROMAGNETIC

    DISTURBANCES 

    Shall cover,

     –  Protection of low voltage installations against temporary over-voltages due

    to earth fault in high voltage systems and due to faults in the low voltage

    systems.

     –  Protection against over-voltages of atmospheric origin or due to switching.

     –  Measures against electromagnetic influences.

     –  Protection against under voltages

    Reference: BS7671-2008 

  • 8/18/2019 Electrical Skills Lab Manual

    21/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Compliance with OES4 is achieved through following steps:

    (How to meet the Standard?)

    1.  Submission of Drawings: Schematic and wiring diagrams, layout drawings and

    schedule of points with site layout should be submitted to the Ministry beforecommencement of any electrical work whatsoever large or small, new or

    additions, and work shall start only after due approval of the Ministry. All work

    should be carried out in accordance with the approved drawings.

    2.  Inspection: All installation work will be subject to inspection and testing by the

    ministry and will be connected to the power supply only after the work is

    checked and approved by the ministry.

    3.  Electrical Supervision: All electrical installation works shall be carried out by or

    under the direct supervision of a qualified electrical engineer or a supervisor

    holding a competency license issued by the Ministry. Such competency licensewill be issued after necessary tests and interview by the Ministry.

    4.  Standards, Materials and Workmanship: The works shall be carried out in a

    neat and workmanlike manner to meet the requirements of these regulations. All

    materials used shall be the best of their respective kinds and shall comply with

    the latest relevant recommendations of the International Electro-technical

    Commission (IEC) if available and if no IEC recommendation is available with the

    latest relevant British Standard Specification (BSS)  

    Reference:  STANDARD OES 4, SECOND EDITION, MAY 1989

  • 8/18/2019 Electrical Skills Lab Manual

    22/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

  • 8/18/2019 Electrical Skills Lab Manual

    23/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Exercise 1: Electrical Supply

     Aim:  To understand different types of supply systems and trace the electrical supply

    system in Shinas College of Technology

    (After discussion of the topic in class the students will be taken around the campus

    of the institute to trace the electrical supply system)Electrical Power System in Oman:

  • 8/18/2019 Electrical Skills Lab Manual

    24/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Electrical supply at the consumers (domestic/ commercial/ industrial) is drawn from

    distribution substations. Depending on the applications and KVA the supply voltage is

    11kV or 400 V. The distribution substations are equipped with necessary means for

    isolation and protection.

    Bulk consumers of electricity such as Shinas College of Technology receive electrical

    supply at 11kV from distribution substation.

    In the consumer premises, the consumer has another substation to step down this

    voltage to 400V to meet lighting and low voltage applications.

  • 8/18/2019 Electrical Skills Lab Manual

    25/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

  • 8/18/2019 Electrical Skills Lab Manual

    26/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

       S   c    h   e   m   a   t   i   c    d   i   a   g   r   a   m    o

        f   s   u   c    h   a

       s   y   s   t   e   m    i

       s    d   i   s   p    l   a   y   e    d   i   n   t

        h   e    f   o    l    l   o   w   i   n   g    d   i   a   g   r   a   m  :

     

  • 8/18/2019 Electrical Skills Lab Manual

    27/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Exercise 1: Electrical Supply Systems:

    Reference:

    Chapter 7, Advanced Electrical Installation Work, Fifth Edition,

    Publication: Newens

    Author: Trevour Linsley

    As per the Electricity Regulations applicable in the region to ensure safety, electrical

    installations must be equipped with

    1.  Basic protection and2.  Fault protection

    This protection is provided using principle of “Protective equi-potential bonding

    coupled with automatic disconnection of supply”. In this method all exposed metal

    work is electrically connected together to an effective earth connection.

    This expose metalwork includes,

      Electrical conduits

      Trunking

      Metal switches

      Metalwork of electrical appliances

      Water service pipes

      Gas and other service pipes and ducting

      Central heating and air conditioning systems

      Exposed metallic structural parts of the building

      Lightening protective systems

  • 8/18/2019 Electrical Skills Lab Manual

    28/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    There are three commonly used arrangements of the earthing connection as described

    in IEE Electricity Regulations which are discussed here.

      TN-S System

      TN-C-S System  TT System

    These have been designated in the IEE Regulations using the letters: T, N, C

    and S. These letters stand for:

    T - terre (French for earth) and meaning a direct connection to earth.

    N - neutral

    C - combined

    S - separate.

    When these letters are grouped, they form the classification of a type of system.The first letter denotes how the supply source is earthed.

    The second denotes how the metalwork of an installation is earthed. 

    The third and fourth indicate the functions of neutral and protective conductors. 

  • 8/18/2019 Electrical Skills Lab Manual

    29/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    TN-S System (Cable Sheath Earth Supply)

        Used where the electricity company’s  supply is provided by undergroundcables.

        Neutral and protective conductors CP (also called as protective earth PE) are

    separate throughout the system.

        The protective earth conductor (PE) is the metal sheath and armour of theunderground cable and this is connected to the consumer’s main earthing

    terminal.

        All exposed metalwork is connected to the protective conductor via the main

    earthing terminal of the installation.

  • 8/18/2019 Electrical Skills Lab Manual

    30/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

  • 8/18/2019 Electrical Skills Lab Manual

    31/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

        This system has the neutral of power supply with connection of earth only atone point to the source. The consumer’s earthing terminal is usually connected

    to the metallic Armour of the distributor’s cable into the HV / LV transformer.

        It is commonly used for underground power supply to the premise or factory

    from the distributor substation to customer substation. This earth terminal is

    connected by the supply protective conductor (PE) back to the star point

    (neutral) of the secondary winding of the supply transformer, which is also

    connected at that point to an earth electrode.

    http://www.electricneutron.com/tag/cable/http://www.electricneutron.com/tag/cable/http://www.electricneutron.com/tag/cable/

  • 8/18/2019 Electrical Skills Lab Manual

    32/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    TN-C-S System (Protective Multiple Earthing Supply)

  • 8/18/2019 Electrical Skills Lab Manual

    33/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

  • 8/18/2019 Electrical Skills Lab Manual

    34/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

        The supply cable uses a combined protective earth & neutral (PEN) conductor.

        At the supply intake point a consumer’s main earthing terminal is formed byconnecting the earthing terminal to the neutral conductor.

        All exposed conductive parts of the installation are then connected to the mainearthing terminals. Thus phase to earth faults are effectively converted into

    phase to neutral faults

  • 8/18/2019 Electrical Skills Lab Manual

    35/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    TT System (No Earth Provided Supply)

        installations protective conductor must be connected to earth via an earth electrode

    provided by the consumer. The TT method is used mostly in country areas with

    overhead transmission lines.

        In contrast to the TN-S system there is no metallic path from the consumer's terminals

    back to the sub-station transformer secondary windings. Because the earth path may beof high resistance, a residual current circuit-breaker (R.C.C.B.) is often fitted so that if a

    fault current flows in the earth path then a trip disconnects the phase supply.

    For protection against indirect contact in domestic premises, every socket outlet

    requires an RCCB with a maximum rated current of 30mA.

  • 8/18/2019 Electrical Skills Lab Manual

    36/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

  • 8/18/2019 Electrical Skills Lab Manual

    37/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

  • 8/18/2019 Electrical Skills Lab Manual

    38/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Residual Current Protection

    RCDs are designed to disconnect the circuit if there is a leakage current. By detecting

    small leakage currents (typically 5–30 mA) and disconnecting quickly enough (

  • 8/18/2019 Electrical Skills Lab Manual

    39/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

     Advantages

    1. They are less sensitive to fault conditions.2. While voltage and current on the earth line is usually fault current from a live wire,

    this is not always the case, thus there are situations in which an ELCB can nuisance

    trip.

    3. When an installation has two connections to earth, a nearby high current lightningstrike will cause a voltage gradient in the soil, presenting the ELCB sense coil with

    enough voltage to cause it to trip.

    4. If the installation’s earth rod is placed close to the earth rod of a neighboringbuilding, a high earth leakage current in the other building can raise the local

    ground potential and cause a voltage difference across the two earths, again

    tripping the ELCB.

    5. If there is an accumulated or burden of currents caused by items with loweredinsulation resistance due to older equipment, or with heating elements, or rain

    conditions can cause the insulation resistance to lower due to moisture tracking. If

    there is a some mA who is equal to ELCB rating than ELCB may give nuisance

    Tripping.

    6. If either of the earth wires become disconnected from the ELCB, it will no longer tripor the installation will often no longer be properly earthed.

    7. Some ELCBs do not respond to rectified fault current. This issue is common forELCBs and RCDs, but ELCBs are on average much older than RCB so an old ELCB is

    more likely to have some uncommon fault current waveform that it will not

    respond to.8. Voltage-operated ELCB are the requirement for a second connection, and thepossibility that any additional connection to earth on the protected system can

    disable the detector.

    9. Nuisance tripping especially during thunderstorms.

  • 8/18/2019 Electrical Skills Lab Manual

    40/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Disadvantages

    1.  They do not detect faults that don’t pass current through the CPC to the earth rod. 2.  They do not allow a single building system to be easily split into multiple sections

    with independent fault protection, because earthing systems are usually use

    common earth Rod.3.  They may be tripped by external voltages from something connected to the

    earthing system such as metal pipes, a TN-S earth or a TN-C-S combined neutral

    and earth.

    4.  As electrically leaky appliances such as some water heaters, washing machinesand cookers may cause the ELCB to trip.

    5.  ELCBs introduce additional resistance and an additional point of failure into theearthing system.

    Answer following questions:

    1)  Why and where protection is required in the Electrical Installations?

    2)  Where we can use the earthing systems?

    a) TN – S System

    b) TN – C – S System

    c) TT System

    3)  What is RCD? How does it work?

    4)  What is the supply voltage obtained from the electricity board to Shinas college of

    Technology?

    5)  What is the kVA rating of the distribution substation in the college premises?

    6)  What is the type of transformer in the substation?

    7)  How much voltage is required at the consumer’s premises for Lighting and low

    voltage applications?

  • 8/18/2019 Electrical Skills Lab Manual

    41/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Exercise 2: Measurement of the Earth Resistance

    STANDARD, OES4

     Section 4.2.9

    CONSUMER EARTING SYSTEM

     An independent, separate earthing system shall be installed and maintained by

    the consumer. This shall comprise the following,

        Earth electrode of 15mm diameter copper earth rod set with driving pin

    and head driven to a minimum depth of 3 meters. This shall be installed as

    near to the consumer’s main board as possible inside earth pit with

    inspection cover as per figure 2.1. The earth electrode shall include a

    corrosion resistant terminal clamp.    PVC insulated stranded copper earth conductor (35 mm 2 copper for single

    consumer installation and 70 mm 2  copper multiple consumer

    installation) with cramped terminal lugs, shall be connected between the

    earth electrode and the consumer’s main earthing terminal or bar. 

        PVC insulated earth continuity conductor of every outgoing circuit from

    the consumer’s main board shall be connected to the main earthing

    terminal.

        The resistance of the consumer’s earthing system to the general

    mass of earth shall not exceed 50 Ω.  To achieve this value in theareas of high soil resistivity, additional earth electrodes with a

    minimum spacing of 3 meters shall be installed.

        Consumer’s earth electrode resistance shall be measured in accordance

    with the method described in Appendix VI of the OES4.

         All metal work, exposed conductive parts and enclosures, in the

    consumer’s installation (other than live conductors and current carrying

     parts) shall be connected with PVC insulated earth continuity conductor

    to the main earthing terminal.

        The consumer’s earthing system shall be connected to the MEW(electricity Distribution Company) earthing system.

        The neutral conductor shall remain insulated throughout the installation

    and shall not at any point be connected to the earthing system.

  • 8/18/2019 Electrical Skills Lab Manual

    42/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    (Note: all dimensions are in mm)

    Figure 2.1: Earth Pit

  • 8/18/2019 Electrical Skills Lab Manual

    43/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

     Aim:  To measure the value of earth resistance and earth voltage by using Earth

    Resistance Tester (Kyoritsu 4102A).

     Apparatus Required:

    1) Earth resistance tester - 1 No.

    2) Connecting leads - 3 Nos.

    3) Earth Electrodes - 2 Nos.

    4) Hammer - 1 No.

    Theory:

    The importance of earthing lies in the fact that it deals with safety. The word

    ‘earthing’ comes from the fact that the technique itself involves making a low-

    resistance connection to the earth or to the ground. The earth is considered to be a

    large conductor which is at zero potential.

    Reason for Earthing:

    The basic reason for earthing is to prevent or minimize the risk of shock to human

    beings and livestock by providing a low resistance discharge path for earth leakage

    currents which would otherwise provide injuries or even death to a person or animal

    touching the metal part.

    The following diagram describes the degree of danger of the leakage current; if, it

    flows in the human body.

  • 8/18/2019 Electrical Skills Lab Manual

    44/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    The following example through the figures describes how the earthing system works:

    In the following diagram the metallic part is not earthed and the human being is

    touching it.

    Let,

    The supply voltage is 240V, AC circuit. The apparatus is having 40Ω and the defectiveinsulation is making the metallic body live and it is not earthed. Let the body

    resistance is 1000Ω: 

    As shown above the leakage current may cause death to the person that is in contact

    with the metallic part. The fuse in the path will not be able to identify the small rise in

    current.

    In the following diagram the metallic part is earthed and the human being is touching

    it.

    With the same supply system let, the sum of the resistance of cable and the metallic

    part be 10Ω

    Now the current is 4.8 times the fuse rating current. So, the fuse will operate andprotect the human by:

    i.  Blowing out and separating the supply from the body in touch with the

    equipment

    ii.  By making the potential across the body ‘Zero’ (i.e. a shorted electric part

    through the earth wires).

  • 8/18/2019 Electrical Skills Lab Manual

    45/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Types of earth electrodes:

    Rod and pipe electrodes:

    The following drawing describes how such electrodes are used in a distribution

    wiring system:

    Plate electrodes:

  • 8/18/2019 Electrical Skills Lab Manual

    46/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    The following drawing describes how such electrodes are used in a distribution

    wiring system:

  • 8/18/2019 Electrical Skills Lab Manual

    47/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

  • 8/18/2019 Electrical Skills Lab Manual

    48/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Preparation for Measurement:

     A) 

    Mechanical Zero Adjustment

    To obtain a measurement value with high accuracy, rotate the meter zero adjuster

    with a screwdriver with the range selector switch OFF, and surely match the

    indicator to “0” graduation value at the left of the scale board. 

    B) 

    Connecting Test ProbeInsert the plug of the probe securely into the terminals of the instrument. Loose

    connection may result in inaccurate measurements.

    C) 

    Battery Voltage Check

    Set the range selector switch to BATT.CHECK position and press the test button.

    Then the indicator swings, make sure that the indicator is at the right of BATT.GOOD

    graduation borderline on the scale board. Otherwise, the batteries are exhausted.

    Connection Diagram:

  • 8/18/2019 Electrical Skills Lab Manual

    49/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Procedure:

    1) Strike the auxiliary earth spikes P and C into the ground deeply. They should be

    aligned at and interval of 5 -10 meters from the earthed equipment under test.

    2) Connect the Green  Wire to the earthed equipment under test, Yellow  to the

    auxiliary earth spike P and the Red to the auxiliary earth spike C from terminals E,

    P and C of the instrument respectively.

    3) Set the range switch to EARTH VOLTAGE position to check earth voltage. Record

    the reading in table below.

    4) Set the range switch to × 100 positions, and press the test button. The LED

    remains illuminated during testing. Turn the range switch to × 10   and × 1  

    when the earth resistance is low. This indicated value is the EARTH RESISTANCE of

    the earthed equipment under test.

    5) Change the spike ‘P’ position to 2m, 4m, 6m, 8m, 10m from the earth pin ‘E’ and

    note down the earth resistance and tabulate the readings.

    Observations:

    Distance From the Earth

    Pin ‘E’ to the Spike P

    Earth Resistance Observed

    Value (Unit)

    2 m

    4 m

    6 m

    8 m

    10 m

  • 8/18/2019 Electrical Skills Lab Manual

    50/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Graph

    The variation of earth resistance with distance

    Conclusions:

    Answer Following Questions,

      Why is it necessary to provide earthing?

      From the observations above, comment if the earth resistance measured is

    acceptable as per the OES 4.

      If the value of resistance is unacceptable, what are the measures required to bring itto the acceptable range?

  • 8/18/2019 Electrical Skills Lab Manual

    51/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Exercise 3: Preparation of Galvanized Steel Conduit  

    STANDARD, OES 4

     Section 3.13

    Steel Conduits and fittings for use in building electrical installations shall

    comply with BS 4568, Parts 1 and 2 of heavy gauge hot dip galvanized inside

    and outside, screwed type.

     Section 6.1

    Installation of Conduits

    The conduits for each circuit shall be completely installed before any cable is

    drawn in.

    Conduits shall be securely fixed and where they are liable to mechanical

    damage they shall be adequately protected.

    Provision for the safe and easy drawing in of cables shall be made by use of

    inspection fittings, draw boxes. Provisions shall be such that cables can be

    drawn in or replaced without the cables being damaged or conduit

    dismantled.

     All runs of the conduit shall be truly vertical or horizontal.

     Section 6.2

    Conduit Saddles

    Where conduits are installed on the surface of building fabric they shall be

    supported by purpose made conduit saddles or spacer bar saddles.

    Supports shall be provided at a maximum spacing of 1500 mm for

     galvanized steel conduits and 1200 mm for high impact PVC conduit.

     Section 6.3

     Smooth Finish of Conduits

    The boxes of all the conduits shall be smooth and free from projection which

    may injure cables or obstruct their drawing in. ends of conduits shall be so

    reamed and when they terminate at boxes, trunking and accessories not fitted with spout entries, shall be so bushed as to obviate abrasion of cables.

  • 8/18/2019 Electrical Skills Lab Manual

    52/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

     Section 6.4

    Radius of Bend

    The radius of every conduit bend shall not be less than 2.5 times the outside

    diameter of the conduit.

     Section 6.5

    Galvanized Steel Conduits

    Galvanized Steel conduit system shall be earthed and connected to the earth-

    continuity conductor. All joints shall be made mechanically and electrically

    continuous by screwing. The conduit shall not however be used as an earth

    continuity conductor and a separate earth continuity cable shall be drawn

    into the conduit for every final sub-circuit.

    Only Galvanized Steel conduits shall be used in the space between a roof and

    suspended false ceiling, in situations subject to fire risk and in surface

    mounted industrial installation. PVC conduits shall not be used for such

    applications. (Derogation issued in2009 to use PVC conduits)

    Galvanized Steel conduits shall not be used under floor tiles of buildings or in

    concealed wiring systems embedded in walls or floors. PVC conduits shall be

    used for all such applications.

     Section 6.6

    PVC Conduits and Fittings

    PVC conduits and fittings shall be of the unthreaded type. All joints shall be

    made with vinyl cement and entries of all conduit fittings shall be designed

    such that reliable water tight joints can be obtained.

    Surface mounted PVC conduit systems shall be so supported as to allow for

    longitudinal expansion and contraction. A cement that shall remain in

    adhesive plasticized state shall be used for expansion couplers.

     Section 6.7

    Flexible Conduits

    Flexible conduits shall only be used for the final connection of motors and

    other equipment subject to vibration or adjustment of position.

    PVC flexible conduits and fittings shall comply with BS 4607 part 3. Metallic

     flexible conduits and fittings shall comply with BS 731 Part 1 and shall

     preferable be provided with an outer sheath of PVC.

    Flexible metal conduit shall not be used as the sole means of providing earth

    continuity and a separate earth continuity cable shall be provided.

  • 8/18/2019 Electrical Skills Lab Manual

    53/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Where necessary, flexible conduit shall be adequately supported and / or

     protected.

    In damp or wet situations flexible conduits shall be watertight and remain

    impervious to ingress of water or moisture.

    The ends of flexible conduit shall be securely anchored to fixed conduit and /or equipment entries by purpose made flexible conduit adaptors.

     Section 6.8

    Conduit Sizes

    Conduits shall be limited to the following sizes

    16 mm, 20 mm, 25 mm, 32 mm and 50 mm

  • 8/18/2019 Electrical Skills Lab Manual

    54/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

     Aim: To make the Galvanized Steel conduit to do the wiring for the following

    measurement.

    1)  Making 900 bend from a fixed point.

    2)  Making two 900 set.

    3)  Making thread for 1.5 cm at one end.

    Tools Required:

    1) Steel Pipe Bending Vice - 1 No.

    2) Steel Pipe - 1 No.

    3) Threading Die - 1 No.

    4) Hand File - 1 No.

    5) Wire Brush - 1 No.

    6) Measuring Tape - 1 No.

    7) Marker Pen - 1 No.

    Cutting:

    Conduit pipes can be cut by using a hacksaw or a pipe cutter as shown in the following

    figures:

    Procedure:

    1.  Fix the conduit in the vice so that the vice grips the conduit 50 or 75mm from the

    point where the cut has to be made

    2.  The blade is to be installed so that the cut is made on the forward stroke.

    Precautions:a.  After cutting by any method the inside edge

    of the conduit must be smoothed with half

    round file as shown in the figure.

    b.  Be sure that the ridge is cleared beforeinstalling the pipe for wiring.

    c. 

  • 8/18/2019 Electrical Skills Lab Manual

    55/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Threading:

    When short lengths of conduits are to be used for switch or lamp drops, the end of

    the pipe needs to be threaded to enable fixing of the conduit to the accessories. The

    threads on the conduit in all cases shall be between 11mm to 27mm long.

    This threading of conduit is done by using dies and a die-stock.

    Note:

    1.  Apply cutting oil to the end before starting to cut threads.

    2.  Cutting threads longer than necessary will leave exposed threads that are not

    protected from corrosion.

    Precaution:

    a.  Use only a brush to remove the metal burrs from the die. Do not use your hand.

    Metal conduit boxes and the symbols used in metal conduit wiring:

    The following figure shows different popular outlet boxes used in metal conduitwiring:

  • 8/18/2019 Electrical Skills Lab Manual

    56/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Following figure shows the various symbols used for different boxes in a single line

    diagram for such a wiring:

    The following figure shows the wall and ceiling boxes for conduit wiring, a switching

    box is also displayed:

  • 8/18/2019 Electrical Skills Lab Manual

    57/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Preparing the boxes for the conduit wiring:

    The boxes can be used after removing the knock-outs in the boxes. The knock-outs

    can be removed from the boxes by using any of the method shown in the following

    figures:

    After removing the knockouts the boxes are prepared as shown in the following

    figure:

  • 8/18/2019 Electrical Skills Lab Manual

    58/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Conduit pipe bending: 

    It is often necessary to set or bend the conduit to enable it to pass over an

    obstruction as shown in the following figure:

    The bending can be made by using:

    a.  Simple bending block:

    b.  Simple bending hickey:

  • 8/18/2019 Electrical Skills Lab Manual

    59/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    c.  Using a bending machine:

    60 mm80 mm

    mm63

    8

    160

    8

    d

    d = outer diameter of

    the bending pulley

    Actual radius of bend =

    inner radius of the pulley

    Pulley

  • 8/18/2019 Electrical Skills Lab Manual

    60/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Procedure:

    1.  Measure diameter of the Galvanized Steel Pipe given for the exercise.

    2.  Select suitable pulley for bending the pipe.

    3.  Making 900 bend from a fixed point.

    1) Take a steel pipe of length 900 mm and mark 300 mm from the edge or a fixed

    point consider that mark as an initial mark.

    2) Add th8

    1 of the outer circumference of the bending pulley from the initial mark

    Example: 300mm + (  8

    160

     ) =363 mm and consider this as a new mark.

    3) Place the tube in the former with the fixed point at the rear and place the pipe

    exactly at the new mark which should be aligned with the perpendicular scale.

    4) This will give a 900 bend at the required distance from the fixed point to the back

    of the bend.

    4.  Making two 900 set:

    1) From initial mark of 300 mm, measure another 300 mm and mark.

    900

    300

    300 63 mm

    300

    mm

  • 8/18/2019 Electrical Skills Lab Manual

    61/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    2) Take this new mark as reference, subtract th8

    1 of the outer circumference of the

    bending pulley. Consider this as reference mark for the second bend.

    3) Now measure the gap between two bends. If you get 300mm from center to

    center of the bends means your work is carried out successfully.

    5.  Making thread at one end:1)  Mark the threading length in the steel pipe from the fixed end. Take the die and

    fix it with the tool used for making the thread.

    2)  Place the threading tool at the edge of the pipe and rotate it in forward direction

    for one full circle and rotate in opposite direction for one full circle.

    300

    mm

    300 mm

    63 mm

    300mm

    300 mm

    300

    mm

  • 8/18/2019 Electrical Skills Lab Manual

    62/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    3)  Repeat the same thing until the full thread is made at one end as per the

    measurement.

    Results:

    1.  Mention the various types of conduits.

    2.  What are the available sizes of conduits used in industry?

    3.  Mention the applications of various types of conduits.

    4.  Mention the precautions taken while performing the exercise?

    S.No Quantity Measurement

    1 Length of pipe used

    2 Size of Pipe used

    3 The angle made at one end

    4 The angle made at other end

    5 Radius of the bend

    6 Distance between the bends

    7 Distance from one end to center of the bend

  • 8/18/2019 Electrical Skills Lab Manual

    63/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Exercise 4: Wiring Lighting Circuit

    STANDARD OES 4

     Section 4.2.10

    Connection of Switch and Control Gear

    Switches, circuit breakers, fuses, thermostats and similar control devices shall

    be connected in live (phase) conductor only, a bolted or screwed link being

    connected in the neutral conductor. If the switch or circuit breaker includes an

    isolating neutral link, it shall be arranged to make before and open after the

    live (phase) poles.

     Section 4.2.17

    Load on lighting circuits

    Load on lighting circuits in domestic installations shall not exceed 1500 W per

     final sub circuit.

     Section 4.2.20

    Lighting Switches

    Local switches for lighting points and for appliances not connected to socket

    outlets shall have a minimum current rating of 5A. For outdoor and industrial

    use, switches shall be metal clad and water tight.

    Switches for control of discharge lighting shall have a current rating of not less

    than twice the steady state continuous current of the circuit.

     All local switches shall be mounted in readily accessible positions with the

    dollies at the minimum height of 1250 mm from finished floor level.

    In kitchens and in situations other than bathrooms, where water is regularly

    used no switch shall be mounted within 2 meters of any tap, basin, sink, if this is

    not possible, ceiling mounted insulating cord operated switches shall be used.

    In bathroom and toilets, switches shall be of the ceiling mounted insulating

    cord operated type. If wall mounted switches are used for control of lighting

    and exhaust fans, same shall be located in an accessible position outside the

    bathroom or toilet and immediately adjacent to the door. Special wall mounted

    switch for control of supply to water heater shall be similarly mounted.

    Switches for lighting and fans inside a room shall be mounted inside the room

    on the side of the door nearest to the door catch, handle knob or lock

    approximately 150mm from the door frame.

  • 8/18/2019 Electrical Skills Lab Manual

    64/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

     Section 5.2

    Current Ratings

    Current Ratings for single core and multicore cables to be adopted for use in

    consumer’s installation are set out in tables 2, 3, 4 and 5 (Appendix IV) of OES4.

    The current carried by the cables at any time shall not exceed the specified

    ratings.

     Section 5.4

    Protection against damage

     All conductors and cables shall be adequately protected against any risk of

    mechanical damage to which they may be liable in normal condition of service.

    Where cables pass through hole in metal works, rubbers or plastic grummets or

    bushes shall be provided of the edge lined with soft material to prevent

    abrasion of the cables.

     Section 5.18

    Flexible cord and cables

    Current ratings for flexible cords and cables are set out in Table 1 (Appendix IV)

    of OES4.

    Where the apparatus requires to be earthed, flexible with earth core shall be

    used.

    Where the flexible cables and cords are exposed to the risk of mechanical

    damage, they shall as a minimum be sheathed with PVC or rubber and where

    necessary shall be armored, the armour not being used as sole means of

     providing earth continuity.

    Flexible cords and cables shall be connected to plugs, ceiling roses and movable

    apparatus with the BROWN core to phase, BLUE core to neutral and

    GREEN/YELLOW core to earth terminal of accessory or frame of the apparatus.

    In situations where high temperatures are encountered, flexible cables and

    cords shall be insulated with silicon rubber type E12 of BS6899/IEC540

    Where a flexible cord supports or partially supports a luminaire, the maximum

    mass supported by the cord shall not exceed the values given in Table 1

    (Appendix IV)

  • 8/18/2019 Electrical Skills Lab Manual

    65/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

     Section 5.19

    Colour identification of cable cores

    a. 

    Colour identification of insulated cable cores for fixed installation and of

    sleeve, band or disc for bare conductors shall be as follows:

    - earthing conductor green and yellow

    - phase of a.c. single phase circuit red

    - neutral of a.c.single phase or three phase circuit black

    - phase R of three phase a.c. circuit red

    - phase Y of three phase a.c. circuit yellow

    - phase B of three phase a.c. circuit blue

    - positive of d.c. 2 wire red

    - negative of d.c. 2 wire black

    b.  Colour identification of flexible cables and flexible cords shall be as follows:

    - live brown

    - neutral blue

    - earthing green and yellow

    Mounting Heights of Accessories

    Item Height from finished floor level

    Lighting Switch 1250 mm

    Ceiling Fan Regulator 1250 mm

     20Amp, D.P switch for water heater or A/C units 1250 mm

    Shaver socket outlets 1250 mm

    13Amp switched socket outlet for general purpose 450 mm

    13Amp switched socket outlet in kitchen 250 mm

    Cooker control unit 1000 mm

  • 8/18/2019 Electrical Skills Lab Manual

    66/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Symbols of Electrical Accessories – (Appendix 3 of OES 4) 

  • 8/18/2019 Electrical Skills Lab Manual

    67/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

  • 8/18/2019 Electrical Skills Lab Manual

    68/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

  • 8/18/2019 Electrical Skills Lab Manual

    69/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

     Aim : To connect two lamps in parallel

    Objectives:

    1) Knowing the OES 4 and its sections pertaining to wiring at different installations

    2) Category of load as per OES 4

    3) Standards pertaining to wiring of a building for a normal household consumer

    4) Standard pertaining to voltage drop, current rating, parallel operation and

    protection against damage.

    5) Practice of wiring for a normal parallel connected load for domestic application.

    Tools Required:

    6) Electrical / Manual Driller

    7) Screw Drivers

    8) Hacksaw frame with Blade

    9) Wire Stripper

    10)  Pliers

     Accessories Required:

    1) PVC Conduit

    2) Conduit Saddles and Screws

    3) Elbow or Bend

    4) Junction box5) Lamp Holders with Lamps

    6) Single pole switch

    7) Miniature Circuit Breaker (MCB)

    8) Earth Leakage Circuit Breaker (ELCB)

    9) 15 Amps , 1 Way Terminal Box

    Measuring Instruments:

    Multi Meter for measurement of current and voltage

  • 8/18/2019 Electrical Skills Lab Manual

    70/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Circuit Diagram:

    Line Diagram:

    Single Phase240 V, 50 Hz

    L

     N

    S

    L1 L2

    E

    Distribution

    Board ELCB MCB Switch

    Lamp 1

    Lamp 2

  • 8/18/2019 Electrical Skills Lab Manual

    71/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Layout Diagram:

  • 8/18/2019 Electrical Skills Lab Manual

    72/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    List of Material:

    Sr. No. Item SpecificationQuantity

    Required

    1 Conduit

    2 Saddles

    3

    Cable Red

    Cable Black

    Cable Yellow and Green

    4 Switch

    5 Junction box

    6 Elbows or Bends

    7 Lamp holder

    8 MCB

    9 ELCB

    10 Lamp1

    11 Lamp2

    12 Clamp meter

  • 8/18/2019 Electrical Skills Lab Manual

    73/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Procedure:

    1)  Connect the items collected per the layout diagram on the work board.

    2)  Check the tightness of the connections.

    3)  Never forget to verify the tracing of the wires as per the layout diagram.

    4)  CHARGE THE CIRCUIT UNDER THE SUPERVISION OF TECHNICIAN.

    5)  Verify the live terminal at input of the ELCB using line tester.

    6)  Switch ON the ELCB and using line tester observe that the circuit is live and the

    wiring is perfect.

    7)  Switch on the MCB and observe that the wiring is working perfect.

    8)  Similarly check that the live terminal at the Lamp Holders turns Live, only on

    making the switch ON.

    9)  Note the Operation of the circuit by visual inspection and record the data in

    your report.

    10) Note down the reading of Voltage and current in the observation table and

    calculate the power.

  • 8/18/2019 Electrical Skills Lab Manual

    74/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Measurements and Calculations:

    Sr. No. Condition Voltage (V) Current (I)

    1

    Only Lamp1

    (______W,______V)

    2Only Lamp2

    (______W,______V)

    3 Lamp 1 and 2

    Calculations:

    SlNo 

    Specification  Voltage V 

    CurrentI 

    Power

    Consumed (P) 

    1  Lamp 1 (alone): ______W

    2  Lamp 2 (alone): ______W

    Result: Write how the activity performed meets the requirements of various

    sections of OES referred at the beginning of this experiment.

    Answer the following questions.

    1.  What is the use of MCB in the circuit?

    2.  What is the use of ELCB in the circuit?

    3.  By observing the Currents drawn by the circuit and bulbs, How the bulbs

    are connected?4.  What is the use of earth terminal in the circuit?

  • 8/18/2019 Electrical Skills Lab Manual

    75/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    5. Exercise 5: Testing Wiring Circuits

    GUIDELINES FOR TESTING WIRING CIRCUITS AND CERTIFICATION OF TESTING

    The Oman Electricity Standard, OES 4 in Section 11 guides on the testing and inspection of

    the electrical installation.

    STANDARD, OES4

     Section 11.1 General

    Every installation and major alteration to an existing installation shall on

    completion and before being energized, be inspected and tested to verify

    compliance with MEW regulations.

     Section 11.2 Visual Inspection

     A visual inspection shall be carried out to verify if the installation is in

    accordance with approved drawings and the execution of the work andworkmanship and the installation methods adopted meet the requirements of

    the MEW regulations.

     Section 11.3 Colour Identification

    It shall be verified that the correct colour identification has been adopted for all

    wiring and the fuses and switches are connected in the live conductors only and

    links or linked switches are connected in the neutral conductor.

     Section 11.4 Earth Continuity Test

    Earth continuity test shall be carried out between the consumer’s earthing

    terminal and the remote end earth continuity conductors.

    The resistance value obtained shall not exceed 0.5 ohm.

     Section 11.5 Insulation Resistance Test

    Insulation resistance test shall be carried out on the installation. For purpose of

    these tests large installations must be divided into groups each containing 50

    outlets. A 500V DC test voltage shall be applied.

    The insulation resistance to the earth shall not be less than 1 mega ohm, when

    measured with all poles and phases of wiring connected together and switchesand fuses all in place. The insulation resistance when measured between all the

    conductors connected to any one pole or phase of supply and in turn all

    conductors connected to each other pole or phase shall not be less than 1 mega

    ohm.

  • 8/18/2019 Electrical Skills Lab Manual

    76/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

     Section 11.6 Continuity Test

    Test shall be made to verify the continuity of all conductors including the earth

    continuity conductor of every ring circuit.

     Section 11.7 Earth Electrode Resistance Measurement

    Earth Electrode Resistance Measurement shall be carried out in accordance

    with method described in Appendix VI. The resistance shall not exceed 50 Ohms.

     Additional electrodes shall be provided where necessary to obtain this value.

     Section 11.8 Protection Test

    Tests shall be carried out to verify effective and correct operation of all earth

    leakage circuit breakers, close excess current protection of circuit breakers and

     fuse links and other protective devices.

     Section 11.9 Completion CertificateFollowing the inspection and testing, a completion certificate in the attached

     format shall be submitted by the electrical contractor to MEW signed by

    contractor’s competent engineer. The installation will then be further inspected

    and tested by MEW inspector and if found satisfactory, the installation will be

     permitted to be connected to supply.

  • 8/18/2019 Electrical Skills Lab Manual

    77/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    COMPLETION CERTIFICATE

    (Completion certificate to be given by the Electrical Contractor and signed by

    Contractor’s Competent Engineer/ Supervisor): 

    I hereby certify that the electrical installations at:

    has been completed, inspected and tested in accordance with the regulations

     for electrical installations issued by the Ministry of Electricity and Water,

    Sultanate of Oman and is now ready for connection to mains supply.

    The results are given in the attached forms.

    Signed: ___________________________________ Date:__________________

    For and on behalf of : _____________________________________________

     _______________________________________________

     _______________________________________________

     Address: ______________________________________________

     ________________________________________________

     _______________________________________________

    MEW Registration No. and Date: _____________________________________

  • 8/18/2019 Electrical Skills Lab Manual

    78/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    FORM A

    Particulars of the installation covered by this Certificate:

    New Installation. Alteration / Extension to existing installation.

    Installation Drawing:

    It is anticipated that the installation would comprise the following:

    S. No. Description No.kW

    Unit Total

    1 Light Points

     2 Air conditioners

    3 Fans

    4 Single Phase Motors

    5 Three Phase Motors

    6 Water Heaters

    7 Refrigerators

    8 Freezers

    9 Cookers

    10 13 A Socket Outlets

    11 Other Loads

    12 ………………………………… 

    13 ………………………………… 

    Comment (if any) on existing installation (where the certificate relates to an

    alteration or addition)

    Signed:____________________________________ Date:_________________

  • 8/18/2019 Electrical Skills Lab Manual

    79/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    FORM B

    INSPECTION AND TEST REPORT

    1.  Compliance with drawings: 

     2. 

    Standard of Installation: 

    Material: 

    Workmanship: 

    3. 

    Colour identification of wiring: 

    4. 

    Polarity Checks: 

    Switches:

    Breakers:

    Links:

    Linked Switches:

    5.  Resistance of Earth Continuity

    Conductor from remote end to

    main earthing point: 

    6. 

    Insulation Resistance: 

    -  With all poles and phases

    connected together and

    switches, fuses and breakers

    all in place 

    -  With all conductor on one

     phase connected together

    and in turn all conductors

    connected to each other. 

     – Red: 

     – Yellow: 

     – Blue: 

     – Neutral: 

  • 8/18/2019 Electrical Skills Lab Manual

    80/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    7.  Continuity of all Conductors 

    -  Red: 

    -  Yellow: 

    -  Blue: 

    -  Neutral: 

    -  Earth: 

    8. 

    Continuity of earth continuity conductor in ring circuit for socket outlet. 

    9.  Earth Electrode Resistance: 

    10. 

    Earth Leakage Circuit Breakers(Residual Current Operated Type) 

    Continuous Rating Operating Current

    (A) 

    (mA)

    Main Subsidiary 1)

     2)

    11. Load Balance

    Red Yellow Blue

    - Lights

    -  Refrigerators

    -   Air conditioners

    -  Freezers

    -  Cooker

    -  Motors

    -  Water Heaters

    -  13A Socket Outlet

    -  Other Loads

    Signed:_____________________________________ Date:_________________

  • 8/18/2019 Electrical Skills Lab Manual

    81/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Objectives: At the end of the exercise the student should be able to understand the

    following:

    1) Understanding the need for Testing and Inspection of wiring in electricalinstallations

    2) Understanding the different types of Testing and Inspection procedures as perOES 4

    3) Preparing ‘Completion Certificate’ pertaining to Testing and Inspection ofelectrical wiring as per OES 4

    4) Inspection & Testing procedure required to follow as per OES 4, for a givenelectrical circuit.

     Aim : To Connect a 3 Pin Plug connection and perform following tests 

    1) Visual inspection

    2) Color Identification

    3) Earth Continuity Test

    4) Continuity Test and

    5) Protection Test

    Tools Required:

    1) Electrical / Manual Driller

    2) Screw Drivers

    3) Hacksaw frame with Blade

    4) Wire Stripper

    5) Pliers

    6) Line Tester

     Accessories Required:

    1) Conduits

    2) Conduit Saddles and Screws

    3) Elbow or Bend

    4) Red, Black and Yellow/ Green Cable

    5) Junction box6) 3 Pin Plugs with Switches

    7) Miniature Circuit Breaker (MCB)

    8) Earth Leakage Circuit Breaker (ELCB)

    9) 15 Amps , 1 Way Terminal Block

  • 8/18/2019 Electrical Skills Lab Manual

    82/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Measuring Instruments:

    Multi Meter (KYORITSU KEW SNAP 2017)

  • 8/18/2019 Electrical Skills Lab Manual

    83/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Circuit Diagram:

    Line Diagram:

    Single Phase

    240 V, 50 Hz

    AC Supply

    DistributionBoard

    ELCB

    MCB 1

    Switch Socket

    Outlet 1

    MCB 2

    Switch Socket

    Outlet 2

  • 8/18/2019 Electrical Skills Lab Manual

    84/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Layout Diagram:

  • 8/18/2019 Electrical Skills Lab Manual

    85/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    List of Material:

    Sr. No. Item SpecificationQuantity

    Required

    1 Conduit

    2 Saddles

    3 Elbows or Bends

    4

    Cable Red

    Cable Black

    Cable Yellow and Green

    5 Switch Socket Unit

    6 Junction box

    7 Terminal Box

    8 MCB

    9 ELCB

    10 Clamp meter

  • 8/18/2019 Electrical Skills Lab Manual

    86/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Procedure:

    Visual Inspection Test:

    Observe the following points in this test and write observations.

    1.  The installation is as per the layout diagram.

    2.  The installation comprises of the protection devices as shown in the line

    diagram.

    3.  Accessories used are of standard quality and note down the standards printed

    (if any)

    4.  Connections and joints of the cable are firm/ tight and appropriately insulated.

    5.  Cables are protected against mechanical damage.

    6.  Switches are mounted at a minimum height of 1250 mm from finished ground

    surface.

    Colour Identification:

    Observe that appropriate colour code is used in the electrical installation. Write the

    observations below,

    1.  Colour of the cable used for Live/ phase wire:__________________

    2.  Colour of the cable used for Neutral wire: _____________________

    3.  Colour of the cable used for Earth wire: _______________________

    Earth Continuity Test:

    Write observation in the table below.

    Sr.

    No.Connection of the multimeter

    ObservationComment

    Sound Resistance

    1

    Earth terminal of Socket Outlet

    1 and Earth terminal of the

    Distribution board

    2

    Earth terminal of Socket Outlet

    2 and Earth terminal of the

    Distribution board

  • 8/18/2019 Electrical Skills Lab Manual

    87/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Continuity Test:

    Sr.

    No.Connection of meter

    ObservationComment

    Sound Resistance

    1 Line terminal of outlet 1 and Lineterminal of outlet 2

    2Neutral terminal of outlet 1 and

    Neutral terminal of outlet 2

    3Line terminal of outlet 1 and Line

    terminal of Distribution Box

    4

    Neutral terminal of outlet 1 and

    Neutral terminal of Distribution

    Box

    5Line terminal of outlet 1 andEarth terminal of Distribution Box

    6Neutral terminal of outlet 1 and

    Earth terminal of Distribution Box

    Protection Test:

    Press the test button of the ELCB and note your observation:

  • 8/18/2019 Electrical Skills Lab Manual

    88/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

     Answer the following questions

    1.  What is Visual Electrical Inspection?

    2.  Explain color identification procedure for electrical installation

    3.  What is Earth continuity test?

    4.  What should be the Insulation resistance as per OES-4?

    5.  What is continuity test?

    6.  How much should be the earth resistance as per OES -4?

  • 8/18/2019 Electrical Skills Lab Manual

    89/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Exercise 6: Connection of Fluorescent Tube Light

    Objectives: At the end of the session the student should be able to,

    1)  Draw the circuit diagram of a single tube fluorescent lamp

    2)  State the function of each component in the circuit3)  State probable causes for different problems in the circuit malfunctioning

     Aim: To study the working principle, assemble, connect and check the fluorescent tube

    light.

    Tools Required:

    1)  Line Tester

     Accessories Required:

    1)  Fluorescent Tube Light 20 W

    2)  Tube light fitting

    3)  Ballast

    4)  Starter

    5)  Connecting wires

    Types of lamps: 

  • 8/18/2019 Electrical Skills Lab Manual

    90/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Construction:

    The fluorescent tube light consists, a sealed glass tube. The tube contains very

    small amount of Mercury mixed with an inert gas, typically Argon, kept under very

    low pressure.

    The tube also contains a Phosphor powder, coated along the inside of the glass.

  • 8/18/2019 Electrical Skills Lab Manual

    91/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    The tube has two electrodes, one at each end, which are connected to the electrical

    supply through bi-pin plugs at both ends of the tube. 

    Ballast/ Choke: Starter:

    Circuit diagram:

    Starter

    CapacitorCathode

    Ballast/

    Choke

    Switch

    240V, AC

    Supply

    Bi-PinPlug

    Cathode

    Bi-PinPlug

  • 8/18/2019 Electrical Skills Lab Manual

    92/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    Features of Fluorescent Tube Light:

      require a ballast

      have a range of color temperatures and color rendering capabilities  have low surface brightness compared to point sources

      have a cooler operation  are more efficacious compared to incandescent  ambient temperatures and convection currents can affect light output and life  all fixtures installed indoors must use a Class P ballast that disconnects the ballast in

    the event it begins to overheat; high ballast operating temperatures can shorten

    ballast life

      have options for starting methods and lamp current loadings  require compatibility with ballast  low temperatures can affect starting unless a "cold weather" ballast is specified

    Working of the Fluorescent Tube Light Circuit: 

    The electrical circuit is connected to an alternating current (AC) supply of 240V, 50 Hz. 

    When the switch is turned ON, the path of least resistance is through the bypass

    circuit, and across the starter switch. In this circuit, the current passes through the

    electrodes on both ends of the tube. These electrodes are simple filaments, like you

    would find in an incandescent light bulb. When the current runs through the bypass

    circuit, electricity heats up the filaments. This boils off electrons from the metal

    surface, sending them into the gas tube, ionizing the gas.

  • 8/18/2019 Electrical Skills Lab Manual

    93/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    At the same time, the electrical current sets off an interesting sequence of events in

    the starter switch. The conventional starter switch is a small discharge bulb,

    containing neon or some other gas. The bulb has two electrodes positioned right

    next to each other. When electricity is initially passed through the bypass circuit, an

    electrical arc  (essentially, a flow of charged particles) jumps between these

    electrodes to make a connection. This arc lights the bulb in the same way a larger

    arc lights a fluorescent bulb

    One of the electrodes is a bimetallic strip that bends when it is heated. The small

    amount of heat from the lit bulb bends the bimetallic strip so it makes contact with

    the other electrode. With the two electrodes touching each other, the current

    doesn't need to jump as an arc anymore. Consequently, there are no charged

    particles flowing through the gas, and the light goes out. Without the heat from the

    light, the bimetallic strip cools, bending away from the other electrode. This opens

    the circuit.

    By the time this happens, the filaments have already ionized the gas in the

    fluorescent tube, creating an electrically conductive medium. The tube just needs avoltage kick across the electrodes to establish an electrical arc. This kick is provided

    by the lamp's ballast , a special sort of transformer wired into the circuit.

  • 8/18/2019 Electrical Skills Lab Manual

    94/112

    EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology

    Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale

    When the current flows through the bypass circuit, it establishes a mag


Recommended