GE India Industrial Pvt Ltd, Pune Electrical works - BOQ as 030113 C.R.Narayana Rao LLP,Architects & Engineers 1 GE INDIA INDUSTRIAL PVT LTD, PUNE ELECTRICALS WORKS SUMMARY DESCRIPTION Addendum BoQ Synefra estimate Supply Install Total 1 A. SECTION A-HT. SECTION 6,703,901 715,190 7,419,091 2 B SECTION -B-HT/LT SUB-STATION EQUIPMENT 108,828,560 3,753,140 112,581,700 3 C L.T. CABLES AND CABLE TERMINATIONS 17,446,317 2,551,870 19,998,187 4 D CABLE TRAYS & ASSOCIATED WORKS 7,110,500 849,150 7,959,650 5 E SECTION -E-EARTHING 7,829,260 992,450 8,821,710 6 F DIESEL GENERATOR SET 26,700,250 499,600 27,199,850 7 G LIGHTING LUMINARIES 6,049,943 440,650 6,490,593 8 H POINT WIRINGS & ACCESSORIES 93,235 21,500 114,735 9 I LIGHTING PANEL/FINAL DISTRIBUTION BOARDS 4,079,076 127,765 4,206,841 10 J EXTERNAL LIGHTING 3,972,390 761,000 4,733,390 11 K MISC. 567,917 56,860 624,777 12 L CIVIL WORKS 1,060,500 1,684,025 2,744,525 TOTAL : RS. 190,441,848 12,453,200 202,895,048 TOTAL SUPPLY & INSTALLATION 202,895,048 S.No. & Section
Transcript
Page 1: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Pvt Ltd, Pune Electrical works - BOQ as 030113

C.R.Narayana Rao LLP,Architects & Engineers 1

GE INDIA INDUSTRIAL PVT LTD, PUNE

ELECTRICALS WORKS

SUMMARY

DESCRIPTION Addendum BoQ Synefra estimate

Supply Install Total

1 A. SECTION A-HT. SECTION 6,703,901 715,190 7,419,091

2 B SECTION -B-HT/LT SUB-STATION EQUIPMENT 108,828,560 3,753,140 112,581,700

3 C L.T. CABLES AND CABLE TERMINATIONS 17,446,317 2,551,870 19,998,187

4 D CABLE TRAYS & ASSOCIATED WORKS 7,110,500 849,150 7,959,650

5 E SECTION -E-EARTHING 7,829,260 992,450 8,821,710

6 F DIESEL GENERATOR SET 26,700,250 499,600 27,199,850

7 G LIGHTING LUMINARIES 6,049,943 440,650 6,490,593

8 H POINT WIRINGS & ACCESSORIES 93,235 21,500 114,735

9 I LIGHTING PANEL/FINAL DISTRIBUTION BOARDS 4,079,076 127,765 4,206,841

10 J EXTERNAL LIGHTING 3,972,390 761,000 4,733,390

11 K MISC. 567,917 56,860 624,777

12 L CIVIL WORKS 1,060,500 1,684,025 2,744,525

TOTAL : RS. 190,441,848 12,453,200 202,895,048

TOTAL SUPPLY & INSTALLATION 202,895,048

S.No. & Section

Page 2: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 2

GE INDIA INDUSTRIAL PVT LTD, PUNE

BILL OF QUANTITIES AS ON 030113

ELECTRICALS WORKS

Synefra revised estimate after addendum

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply A. SECTION A-HT. SECTION(CABLES & TERMINATION)

HT Cables

1

1.1 3Cx300 Sq.mm 33kV XLPE-UE- Cable 100 Mtr. 1,896 120 189,618 1.2 3Cx300 Sq.mm 11kV XLPE -UE-Cable UR Mtr. 1,304 120 1.3 3Cx240 Sq.mm 11kV XLPE -UE-Cable 4972 Mtr. 1,131 120 5,622,469

Note: No straight through joints will be allowded for any single length of cables. - 2 -

-

- 2.1 Indoor type -

2.1.1 3Cx300Sq.mm 33kV XLPE-UE- Cable 4 No. 18,854 2,100 75,416 2.1.2 3Cx300 Sq.mm 11kV XLPE -UE-Cable UR No. 8,822 2,100 2.1.3 3Cx240 Sq.mm 11kV XLPE -UE-Cable 38 No. 7,744 2,100 294,272

- 2.2 Outdoor type -

2.2.1 3Cx240 Sq.mm 33kV XLPE-UE- Cable 1 No. 27,500 2,100 27,500 -

2.3 Straight Through Joint - 2.3.1 3Cx300 Sq.mm 11kV XLPE -UE-Cable UR No2.3.2 3Cx240 Sq.mm 11kV XLPE -UE-Cable UR No

-

3 1 Set 83,160 3,500 83,160

- - -

4 1 No 343,741 7,500 343,741

- - -

5 1 No 44,100 2,100 44,100

- - -

6 15 Mtr 1,575 210 23,625

-

7 UR Mtr

- TOTAL OF SECTION A- HT SECTION 6,703,901

B SECTION -B-HT/LT SUB-STATION EQUIPMENT

1

1.1 HT Panel Designation:33k.V.Main HT Panel at point of supply:

Supply, taking delivery ,unloading at site,Installation,testing & commissioning of HT XLPE insulated, UE grade, cables, as per IS 7098 , burried in ground such as excavation up to 1 meter depth , backfilling, sand and brick protection and cable tray / tray supports are measured separately and Miscellaneous items such as saddles, 3 mm thick aluminum clamps, cleats, cable tags/ cable markers etc. are included in the scope.(The testing shall including HI-POT test at site before commissioning of the system & Test voltage shall be as per IS 7098)

CABLE TERMINATIONS :

Supply,installation,testing & commisioning of Heat shrikable type cable termination kit with long head Crimping type Lugs, for following XLPE insulated, (UE) grade cable including necessary Right angle /straight insulating boots. The scope also includes thermography test of all terminations at loads by using Themo graphic meter.

Supply, Installation, Testing and commissioning 33kV Distribution Class Lightening Arrestors with cross arm (1 Set of 3 Nos)

Supply installation testing and commissioning of 33kV CT& PT Metering kiosk including approval ,testing from MSEDCL .Detailes of CT & PT shall be as per MSEDCL load sanctionapproval.(Without T.O.D. meter)

Supply & installation H.T. Static Three Vector T. O. D. Meter as per MSEDCL.The scope also including calibration & testing of meter from MSEDCL

G. I. Pipe-CL -B- 150mm dia.for supporting of HT Cables connected to Overhead Lines ,road crossing etc for MSEDCL incoming cable.

HD PVC Pipe 150mm dia.for supporting of HT Cables connected to Overhead Lines ,road crossing etc for MSEDCL incoming cable.

Supply, assembly, factory test, loading,Taking delivery at site storing at site & supervision at site of HT panel board indoor type free standing,in various shipping section, Form 4b in construction, IP4X , fabricated out of 3 mm CRCA Sheet etc & as per specifications. Each panel shall comprising as per followings & Enlcosed ELECTRICAL SLD along with Tender Technical Specifciations.The panel shall be suitable for top cable entries for Incoming and outgoing cables except 33 k.V. HT Panels which shall be from bottom.

Page 3: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 3

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply

a 1 Set 10,395,000 35,000 10,395,000

a.1 -

-

a.2 -

- a.3 30k.V. ,10k.A.Class-III Zno Surger Arrestor -

-

a.4 -

-

a.4.1 Core 1: 15VA burden for Differential Protection(86) protection ( Class PS) -

- a.4.2 Core 2:15VA burden of metering ( accuracy class 1.0) -

- a.4.3 Core 3: 30VA burden for OC/EF protection ( Class 5P-20) -

- -

a.5 -

- a.6 Protectives Relays as under -

a.6.1 -

- a.6.1 Stand by Earth Fault relay (51G) -

- a.6.1 Restricated Fault relay (64R) -

- a.6.1 Transformer Auxiliary Protection Relays (63Tx) -

- a.6.1 Trip circuit supervision relay (95). -

- a.6.1 Antipumping relay -

- a.6.1 Lockout relay (86) -

- a.6.1 Under /Over Frequency Relay(81) -

- a.6.1 Under /OverVoltgae Relay(27/59) -

- a.6.1 Reverse Power relay (32) -

- a.6.1 Breaker Failure Relay (52BF) -

- a.7 Control & wiring terminals -

-

a.7.1 -

-

a.7.2 -

- a.8 Meterings as under -

-

a.8.1 -

-

a.8.2 -

-

a.8.3 -

33-KV-Indoor free Vacuum circuit breaker panels with 1250 Amp Aluminum busbar ,26.2 k.A.-1 Second ,EDO Type for Transformer Feeder with over currents & Auxiliary Protection of Oil Cooled transformer and as per enclosed electrical SLD Ref GE-P-FAC-Ele00-01-011-155000-R5- Sh No 1 of 03 & as per followings requirements.

One (1) No. 33 KV,1250 A VCB/26.2 KA rupturing capacity at 33 kV rated metal clad, floor mounting, horizontal isolation horizontal drawout type complete with the followings.

Manually & motor operated (230V AC), spring charged trip free type, VCB incorporating mechanical as well as electrical ON/OFF indication, spring charge/discharge mechanical indication"OFF" push button test/service position limit switches with 4NO/4NC breaker auxilary contacts in service position.

Cast Resin CT with double wound,100- 225/1+1+1 with metering and protection core.

Voltage transformer with each , 3 limbs connected in star, dual class , 33kV/√3/110V/√3 with drawable type with automatic shutters 100 VA burden with HRC fuses for primary & secondary .( Confirming related IS specs.)

Over current 50,50N Insutantaneaus short circuit 51,51N & one earth fault element with numerical IDMT relay with shunt trip on 110volts DC, consisting 3 element over current relay with setting from 50 to 200% (step of 25%) and earth fault with setting from 20 to 80% (step of 10%) .

All control wiring necessary for the above including interconnections. The size of the conductor should not be less than 1.5sqmm, PVC insulated, copper wire where required.

Test terminal block fuses, circuit lables , phase indication lamps etc. as per Electrical SLD

Voltmeter range 0-33KV with necessary voltmeter selector switch & suitable for 110V AC 96x96sqmm dial with shrouded terminal & protection fuses.

Ammeter range (0-100-225A) with necessary ammeter selector switch dual graduated scale, 96x96 sqmm dial with shrouded terminal .

Multifunction Digital meter with RS 485 Serial Communication Port for following parameters.

Page 4: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 4

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply -

Line & Phase Voltage - Line Current - Frequency - M.D. KVA Meter - KW,KVA - KWH - KVAH - RKVAH - p.f. - TDH -

- a.9 Other Accessories as under & as per technical specifications -

- a.9.1 -

-

a.9.2 -

- a.9.3 Danger plate (As per specification) -

-

a.9.4 -

- a.9.5 Three pin socket + switch. -

- a.9.6 Anticondensation space heater / thermostat -

- a.9.7 16 Window Announciator for Transforemr Faults -

- a.9.8 Hooter with Accept & Reset Push Button -

-

a.10 -

- a.10.1 Potenial free (DI)contact of VCB -ON -Status - a.10.2 Potenial free (DI)contact of VCB -OFF -Status - a.10.3 Potenial free (DI) contact of VCB -Trip On Fault- Status - a.10.4 VCB in TEST position (DI) Status - a.10.5 VCB in Serive position (DI) Status - a.10.6 ON Command to VCB(DO) - a.10.7 OFF Command to VCB(DO) - a.10.8 RS 485 (AI) of Mutifunction meters - a.10.9 RS 485 (AI) of Numerical Relays -

-

-

- 1.2 HT Panel Designation: 11k.V.Main HT Panel at MRS -

-

1 Set 9,544,500 49,000 9,544,500

a EACH INCOMERS - - -

a.1 - - -

- - -

a.2 - - -

- - - a.3 9k.V. ,10k.A.Class-III Zno Surger Arrestor - - -

- - -

a.4 - - -

- - - a.4.1 Core 1: 15VA burden for Differential (87) protection ( Class PS) - - -

- - - a.4.2 Core 2:15VA burden of metering ( accuracy class 1.0) - - -

- - - a.4.3 Core 3: 30VA burden for OC/EF protection ( Class 5P-20) - - -

- - -

Necessary DC supply healthy LED type indication lamp & switch.

Control : T-N-C ( Trip , Neutral & Close) breaker control switch with indicating arrangement.

Set of Indication circuit breaker ON/OFF/Trip on Fault / Spring charged/Trip circuit healthy/Test/Service positions etc.

Followings wirings duly brought out to terminal block for BMS/SCADA interface by using twisted pair shielded wires in side the HT. Panels

NOTE: Above VCB Panel shall be suitable for expandable type for future suit to One incomers & two outgoings feeders.

11-KV-Indoor Vacuum circuit breaker panels with 1250 Amp, Aluminum busbar 26.2 k.A.-1 Second , EDO Type with over currents ,earth fault Protections. The complete panel shall be as per enclosed electrical SLD Ref GE-P-FAC-Ele00-01-011-155000-R5- Sh No 1 of 03 with Tender Technical specifications & as per followings requirements.

2 Sets of 11 KV,1250 A VCB/26.2 KA rupturing capacity at 11 kV rated metal clad, floor mounting, horizontal isolation horizontal drawout type complete with the followings.

Manually & motor operated (230V AC), spring charged trip free type, VCB incorporating mechanical as well as electrical ON/OFF indication, spring charge/discharge mechanical indication"OFF" push button test/service position limit switches with 4NO/4NC breaker auxilary contacts in service position.

Cast Resin CT with double wound, 350-800Amp/1+1+1 with metering and protection core.

Page 5: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 5

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply - - -

a.5 - - -

- - - a.6 Protectives Relays as under - - -

a.6.1 - - -

- - - a.6.2 Stand by Earth Fault relay (51G) - - -

- - - a.6.3 Restricated Fault relay (64R) - - -

- - - a.6.4 Differential Protection relay (87R) - - -

- - - a.6.5 Trip circuit supervision relay (95). - - -

- - - a.6.6 Antipumping relay - - -

- - - a.6.7 Lockout relay (86) - - -

- - - a.6.8 Under /OverVoltgae Relay(27/59) - - -

- - - a.6.9 Reverse Power relay (32) - - -

- - - a.6.10 Breaker Failure Relay (52BF) - - -

- - - a.6.11 Master lock out relay (86) - - -

- - - a.7 Control Wiring & Terminal - - -

a.7.1 - - -

- - -

a.7.2 - - -

- - - a.8 Meterings - - -

- - -

a.8.1 - - -

- - -

a.8.2 - - -

- - -

a.8.3 - - -

- - - Line & Phase Voltage - - - Line Current - - - Frequency - - - M.D. KVA Meter - - - KW,KVA - - - KWH - - - KVAH - - - RKVAH - - - p.f. - - - TDH - - -

- - - a.9 Other Accessories as under & as per technical specifications - - -

- - - a.9.1 - - -

- - -

a.9.2 - - -

- - - a.9.3 Danger plate (As per specification) - - -

- - -

a.9.4 - - -

- - - a.9.5 Three pin socket + switch. - - -

- - - a.9.6 Anticondensation space heater / thermostat - - -

- - -

Voltage transformer with each , 3 limbs connected in star, dual class , 11kV/√3/110V/√3 with drawable type with automatic shutters 100 VA burden with HRC fuses for primary & secondary .( Confirming related IS specs.)

Over current 50,50N Insutantaneaus short circuit 51,51N & one earth fault element with numerical IDMT relay with shunt trip on 110volts DC, consisting 3 element over current relay with setting from 50 to 200% (step of 25%) and earth fault with setting from 20 to 80% (step of 10%) .

All control wiring necessary for the above including interconnections. The size of the conductor should not be less than 1.5sqmm, PVC insulated, copper wire where required.

Test terminal block fuses, circuit lables , phase indication lamps etc. as per Electrical SLD

Voltmeter range 0-12KV with necessary voltmeter selector switch & suitable for 110V AC 96x96sqmm dial with shrouded terminal & protection fuses.

Ammeter range (0-350-800A) with necessary ammeter selector switch dual graduated scale, 96x96 sqmm dial with shrouded terminal .

Mutifunction Digital meter with RS485 Serial Communication Port for following parameters

Necessary DC supply healthy LED type indication lamp & switch.

Control : T-N-C ( Trip , Neutral & Close) breaker control switch with indicating arrangement.

Set of Indication for circuit breaker ON/OFF/Trip on Fault / Spring charged/Trip circuit healthy/Test/Service positions etc.

Page 6: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 6

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply a.9.7 8 Window Announciator for Faults - - -

- - - a.9.8 Hooter with Accept & Reset Push Button - - -

- - -

a.10 - - -

- - - a.10.1 Potenial free (DI)contact of VCB -ON -Status - - - a.10.2 Potenial free (DI)contact of VCB -OFF -Status - - - a.10.3 Potenial free (DI) contact of VCB -Trip On Fault- Status - - - a.10.4 VCB in TEST position (DI) Status - - - a.10.5 VCB in Serive position (DI) Status - - - a.10.6 ON Command to VCB(DO) - - - a.10.7 OFF Command to VCB(DO) - - - a.10.8 RS 485 (AI) of Mutifunction meters - - - a.10.9 RS 485 (AI) of Numerical Relays - - -

- - - b Outgoings VCBs - - -

b.1 - - -

- - -

b.2 - - -

- - -

b.3 - - -

- - - 15VA burden for protection ( Class 5P-20) - - -

- - - 15VA burden of metering ( accuracy class 1.0) - - -

- - - b.4 Protection to each outgoings - - -

- - -

- - -

- - - - - -

Trip circuit supervision relay (95). - - - - - -

Lockout relay (86) - - - - - -

Antipumping relay - - - - - - - - -

b.5 Other Accessories as under & as per technical specifications - - - - - - - - - - - -

- - -

- - - Danger plate (As per specification) - - -

- - -

- - -

- - - Three pin socket + switch. - - -

- - - Anticondensation space heater / thermostat - - -

- - - 50x6mm, copper earth bus shall be provided for the full length of panel. - - -

- - -

- - -

- - -

- - -

- - -

- - -

Followings wirings duly brought out to terminal block for BMS/SCADA interface by using twisted pair shielded wires in side the HT. Panels

Five (5) Nos. 11 KV, 1250 A VCB/ 26.2 KA rupturing capacity at 11kV rated metal clad, floor mounting, horizontal isolation horizontal drawout type complete with the following:

Manually & motor operated (230V AC), spring charged trip free type, VCB incorporating mechanical as well as electrical ON/OFF indication, spring charge/discharge mechanical indication"OFF" push button test/service position limit switches with 4NO/4NC breaker auxilary contacts in service position.

Cast Resin CT with double wound, with metering and protection core. CT.Ratio as indciated on Electrical SLD for each outgoing VCB in MRS room panel

Over current 50,50N Insutantaneaus short circuit 51,51N & one earth fault element with numerical IDMT relay with shunt trip on 110volts DC, consisting 3 element over current relay with setting from 50 to 200% (step of 25%) and earth fault with setting from 20 to 80% (step of 10%) .

Necessary DC supply healthy LED type indication lamp & switch.

Control : T-N-C ( Trip , Neutral & Close) breaker control switch with indicating arrangement.

Set of Indication for circuit breaker ON/OFF/Trip on Fault / Spring charged/Trip circuit healthy/Test/Service positions etc.

Terminal boxes with single gland trifucating cable box suitable for 11KV aluminium XLPE cable of size 3C x 300sqmm for incoming & outgoing &Suitable for TOP CABLE ENTRY

All control wiring necessary for the above including interconnections. The size of the conductor should not be less than 1.5sqmm, PVC insulated, copper wire where required.

Test terminal block fuses, circuit lables , phase indication lamps etc. as per standard practice.

Page 7: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 7

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply - - -

b.6 - - -

- - - Potenial free (DI)contact of VCB -ON -Status - - - Potenial free (DI)contact of VCB -OFF -Status - - - Potenial free (DI) contact of VCB -Trip On Fault- Status - - - VCB in TEST position (DI) Status - - - VCB in Serive position (DI) Status - - - ON Command to VCB(DO) - - - OFF Command to VCB(DO) - - - RS 485 (AI) of Numerical Relays - - -

- - - c BUS COUPLERS: 2Nos Bus couplers VCB Panel comprising as under - - -

c.1 As per above Outgoing VCB Breaker panels except No CT for metering - - - & no meters. - - -

- - - d - - -

- - -

- - -

NOTE: 1: Above Panel shall be suitable for Expandable type from both Side - - -

- - -

- - -

- - - - - -

1.3 HT Panel Designation :11kV HT Panel Office Load Centre-1 as 1 Set 2,693,250 49,000 2,693,250 - - -

- - -

a 2 NOS INCOMER FEEDER :EACH INCOMERS COMPRISING AS UNDER. - - -

a.1 - - -

- - -

a.2 - - -

- - - a.3 9k.V. ,10k.A.Class-III Zno Surger Arrestor - - -

- - -

a.4 - - -

- - - a.4.1 Core 1:15VA burden of metering ( accuracy class 1.0) - - -

- - - a.4.2 Core 2: 30VA burden for OC/EF protection ( Class 5P-20) - - -

- - - - - -

a.5 - - -

- - - a.6 Protectives Relays as under to each Incomers - - -

a.6.1 - - -

- - - a.6.1 Trip circuit supervision relay (95). - - -

- - - a.6.2 Antipumping relay - - -

- - - a.6.3 Lockout relay (86) - - -

- - - a.6.4 Under /OverVoltgae Relay(27/59) - - -

- - - a.6.5 Reverse Power relay (32) - - -

- - -

Followings wirings duly brought out to terminal block for BMS/SCADA interface by using twisted pair shielded wires in side the HT. Panels

3 Nos Bus PT Section: 3Nos Withdrawable type BUS PT section as shown in Tender Electrical SLD Ref GE-P-FAC-Ele00-01-011-155000-R5- Sh No 1 of 03

NOTE: 2: Control Voltgae Bus for D.C. & AC votlage shall be as per Electrica SLD ref.GE-P-FAC-Ele00-01-011-155000-R5- Sh No 1 of 03

NOTE: 3: Interlocks and control logics shall be suitable for 4 Incomers & 3Bus-Couplers as shown in above mentioned SLD

11-KV-Indoor Vacuum circuit breaker panels with 1250 Amp,26.2 k.A.-1 Second , EDO Type with over currents ,earth fault Protections. The complete panel shall be as per enclosed electrical SLD Ref GE-P-FAC-Ele00-01-011-155000-R5- Sh No 1 of 03 with Tender Technical specifications & as per followings requirements.

11 KV,1250 A,Aluminum Busbar VCB/26.2 KA rupturing capacity at 11 kV rated metal clad, floor mounting, horizontal isolation horizontal drawout type complete with the followings.

Manually & motor operated (230V AC), spring charged trip free type, VCB incorporating mechanical as well as electrical ON/OFF indication, spring charge/discharge mechanical indication"OFF" push button test/service position limit switches with 4NO/4NC breaker auxilary contacts in service position.

Cast Resin CT with double wound, 250-Amp/1+1 with metering and protection core.

Voltage transformer with each , 3 limbs connected in star, dual class , 11kV/√3/110V/√3 with drawable type with automatic shutters 100 VA burden with HRC fuses for primary & secondary .( Confirming related IS specs.)

Over current 50,50N Insutantaneaus short circuit 51,51N & one earth fault element with numerical IDMT relay with shunt trip on 110volts DC, consisting 3 element over current relay with setting from 50 to 200% (step of 25%) and earth fault with setting from 20 to 80% (step of 10%) .

Page 8: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 8

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply a.6.6 Breaker Failure Relay (52BF) - - -

- - - a.6.7 Master lock out relay (86) - - -

- - - a.7 Control Wiring & Terminal - - -

a.7.1 - - -

- - -

a.7.2 - - -

- - - a.8 Meterings to each Incomers - - -

- - -

a.8.1 - - -

- - -

a.8.2 - - -

- - - Line & Phase Voltage - - - Line Current - - - Frequency - - - M.D. KVA Meter - - - KW,k.V.A - - - KWH - - - KVAH - - - RKVAH - - - p.f. - - - TDH - - -

- - - a.9 Other Accessories as under & as per technical specifications - - -

- - - a.9.1 - - -

- - -

a.9.2 - - -

- - - a.9.3 Danger plate (As per specification) - - -

- - -

a.9.4 - - -

- - - a.9.5 Three pin socket + switch. - - -

- - - a.9.6 Anticondensation space heater / thermostat - - -

- - - a.9.7 8 Window Announciator for Faults - - -

- - - a.9.8 Hooter with Accept & Reset Push Button - - -

- - -

a.10 - - -

- - - a.10.1 Potenial free (DI)contact of VCB -ON -Status - - - a.10.2 Potenial free (DI)contact of VCB -OFF -Status - - - a.10.3 Potenial free (DI) contact of VCB -Trip On Fault- Status - - - a.10.4 VCB in TEST position (DI) Status - - - a.10.5 VCB in Serive position (DI) Status - - - a.10.6 ON Command to VCB(DO) - - - a.10.7 OFF Command to VCB(DO) - - - a.10.8 RS 485 (AI) of Mutifunction meters - - - a.10.9 RS 485 (AI) of Numerical Relays - - -

- - -

b Outgoings VCBs - - -

b.1 - - -

- - -

b.2 - - -

- - -

All control wiring necessary for the above including interconnections. The size of the conductor should not be less than 1.5sqmm, PVC insulated, copper wire where required.

Test terminal block fuses, circuit lables , phase indication lamps etc. as per Electrical SLD GE-P-FAC-Ele00-01-011-155000-R5- Sh No 1 of 03

Voltmeter range 0-12KV with necessary voltmeter selector switch & suitable for 110V AC 96x96sqmm dial with shrouded terminal & protection fuses.

Mutifunction Digital meter with RS485 Serial Communication Port for following parameters

Necessary DC supply healthy LED type indication lamp & switch.

Control : T-N-C ( Trip , Neutral & Close) breaker control switch with indicating arrangement.

Set of Indication for circuit breaker ON/OFF/Trip on Fault / Spring charged/Trip circuit healthy/Test/Service positions etc.

Followings wirings duly brought out to terminal block for BMS/SCADA interface by using twisted pair shielded wires in side the HT. Panels

Note: E& M Interlocaks shall be provided as indicted on Tender Electrical SLD for both Incomers

One (1) Nos. 11 KV, 1250 A VCB/ 26.2 KA rupturing capacity at 11kV rated metal clad, floor mounting, horizontal isolation horizontal drawout type complete with the following:

Manually & motor operated (230V AC), spring charged trip free type, VCB incorporating mechanical as well as electrical ON/OFF indication, spring charge/discharge mechanical indication"OFF" push button test/service position limit switches with 4NO/4NC breaker auxilary contacts in service position.

Page 9: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 9

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply

b.3 - - -

- - - 15VA burden for protection ( Class 5P-20) - - -

- - - 15VA burden of metering ( accuracy class 1.0) - - -

- - - b.4 Protection to each outgoings - - -

- - -

- - -

- - - - - -

Trip circuit supervision relay (95). - - - - - -

Lockout relay (86) - - - - - -

Antipumping relay - - - - - -

b.5 Metering : - - - - - -

- - -

- - - Line & Phase Voltage - - - Line Current - - - Frequency - - - M.D. KVA Meter - - - KWH - - - KWH - - - KVAH - - - RKVAH - - - p.f. - - - TDH - - -

- - - b.6 Other Accessories as under & as per technical specifications - - -

- - - - - - - - -

- - -

- - - Danger plate (As per specification) - - -

- - -

- - -

- - - Three pin socket + switch. - - -

- - - Anticondensation space heater / thermostat - - -

- - - 50x6mm, copper earth bus shall be provided for the full length of panel. - - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

b.7 - - -

- - - Potenial free (DI)contact of VCB -ON -Status - - - Potenial free (DI)contact of VCB -OFF -Status - - - Potenial free (DI) contact of VCB -Trip On Fault- Status - - - VCB in TEST position (DI) Status - - - VCB in Serive position (DI) Status - - - ON Command to VCB(DO) - - - OFF Command to VCB(DO) - - - RS 485 (AI) of Mutifunction meters - - - RS 485 (AI) of Numerical Relays - - -

Cast Resin CT with double wound, with metering and protection core. CT.Ratio as indciated on Electrical SLD for each outgoing VCB in MRS room panel

Over current 50,50N Insutantaneaus short circuit 51,51N & one earth fault element with numerical IDMT relay with shunt trip on 110volts DC, consisting 3 element over current relay with setting from 50 to 200% (step of 25%) and earth fault with setting from 20 to 80% (step of 10%) .

Mutifunction Digital meter with RS485 Serial Communication Port for following parameters

Necessary DC supply healthy LED type indication lamp & switch.

Control : T-N-C ( Trip , Neutral & Close) breaker control switch with indicating arrangement.

Set of Indication for circuit breaker ON/OFF/Trip on Fault / Spring charged/Trip circuit healthy/Test/Service positions etc.

Terminal boxes with single gland trifucating cable box suitable for 11KV aluminium XLPE (E) cable of size 3C x 300sqmm for incoming & outgoing &Suitable for TOP CABLE ENTRY

All control wiring necessary for the above including interconnections. The size of the conductor should not be less than 1.5sqmm, FRLS insulated, copper wire where required.

Test terminal block fuses, circuit lables , phase indication lamps etc. as per standard practice.

Followings wirings duly brought out to terminal block for BMS/SCADA interface by using twisted pair shielded wires in side the HT. Panels

Page 10: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 10

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply - - -

NOTE: 11K.V. HT Panel shall be Expandable from both side - - - - - -

1.4 1 Set 2,693,250 49,000 2,693,250

- - -

a - - -

- - -

b - - -

NOTE: 11K.V. HT Panel shall be Expandable from both side - - - - - - - - -

1.5 1 Set 4,037,250 63,000 4,037,250

- - -

a - - -

- - -

b - - -

NOTE: 11K.V. HT Panel shall be Expandable from both side - - - - - -

- - -

2 Battery Charger - - -

2.1 1 Set 351,645 10,500 351,645

- - -

2.2 3 Set 219,240 7,000 657,720

- - - 3 TRANSFORMERS - - -

- - -

3.1 1 No 2,845,500 77,000 2,845,500

- - -

3.2 3 No 2,514,750 35,000 7,544,250

- - - KVA Rating :2000KVA, %Z 6.25% - - - Primary Volts : 11kV 50 HZ - - - Secondary Volts : 433 Volts 50 HZ - - - Type of cooling : Air Natural - - - Type of tap & Range: LINK : +5%,-7.5 % in the steps of 2.5 % - - - IP Degree : 31 - - -

- - -

HT Panel Designation :11kV HT Panel at HEB Load Centre-2 as per tender Electrical SLD ref GE-P-FAC-Ele00-01-06-155000-R5: Sh1 of 3

Incomers: Complete Incomers section shall be as per above panel of Load cetner-1 & suitable for 2 Incomers

Outgings : Each outgoing feeders shall be as per above panel of Load cetner-1 & suitable for 1 Outgoing

HT Panel Designation :11kV HT Panel at LEB Load Centre-3 as per tender Electrical SLD ref GE-P-FAC-Ele00-01-06-155000-R5: Sh1 of 3

Incomers: Complete Incomers section shall be as per above panel of Load cetner-1 & suitable for 3 Incomers VCB panel

Outgings : Each outgoing feeders shall be as per above panel of Load cetner-1 & suitable for 1 Outgoings VCB feeders panel.

NOTE FOR ALL 11 KV HT PANEL: ALL 11k.V. HT PANELS SHALL BE SUITABLE TO TOP CABLE ENTRIES FOR INCOMING AND OUTGOINGS CABLES TERMINATIONS.

BATTERY CHARGER AT MRS: Supply, Installation ,Testing & commissioning of 110 Volts-350-AH-Battery with battery charger with full wave rectifire ,independent 3 Phase charger for Float & Boost at Main Reciving Station ( Input voltage 3 Phase 415 Volts) with wall mounted DCDB, Suitable for bottom cable entries for incoming and all outgoing cables The Configuration of DCDB shall be as under - Incomer : 1No 250 Amp ,DP MCCB ,35kA , Outgoing : 32Amp , DP MCB 10kA - 12Nos

BATTERY CHARGER AT EACH LOAD CENTERS :Supply, Installation ,Testing & commissioning of 110 Volts-100-AH-Battery with battery charger with full wave rectifire ,independent 3 Phase charger for Float & Boost ( Input voltage 3 Phase 415 Volts) with DCDB as under Incomer : 125 Amp ,DP MCB ,10kA -1 No Outgoing : 32Amp , DP MCB 10kA - 6Nos

Supply,Taking deliver at site storing at site, shifting from the place of storage to the place of installation, installation,with all fittings and accessories, testing and commissioning. Drying out and oil filteration till adequate values of insulation resistance of windings and break down value of oil are achieved is included in the scope. 5000 kVA, 33/11 kV with vector group of Dyn-11 with OLTC & RTCC.The transformer shall be as per latest IS 2026. The transformer shall be suitable for Outdoor installation as per tender specification /drawinhs & with HT & LT Cable box for indoor cable terminations & as per tender Data sheet. Refer Drawing no GE-P-SITE-ELE01-01-05-155008 for Location of Transformer installation. ( Note: Civil foundation will be provided by other)

Supply,Installation ,testing & commissioning of Open ventilated Dry type Transformer with Off circuit tap changing link to Primary Side,with Cable box for Incoming and Busduct for outgoing etc & as per latest I.S.11171: 1985 specification. Rating & details of Transformer is as under.The transformer shall be suitable for Indoor installation as per tender drawing reference GE-P-SITE-Ele00-01-08-155012 & tender data sheet.

Page 11: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 11

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply

3.3 - - -

- - - KVA Rating :250KVA, %Z 5% 3 No 375,000 15,000 1,125,000 Primary Volts : 415 Volts 50 HZ - - - Secondary Volts : 415Volts 50 HZ - - - Type of cooling : Air Natural - - - Type of tap & Range: LINK : +5%,.5 % in the steps of 2.5 % - - - IP Degree : 31 - - -

- - -

3.3 1 No 12,034 4,900 12,034

- - -

3.4 9 Mtr 40,348 8,400 363,132

- - - 4 BUSDUCT - - -

- - -

- - - 4.1 - - -

- - - 4.1.1 Straight Run 3200 Amp TPN, 50kA, AL Busduct Indoor 25 Mtr 40,085 3,500 1,002,120

- - - 4.1.2 Right Angle Bend 3200 Amp, 50kA 6 No 23,618 4,900 141,706

- - - 4.1.3 Bimetallic Flexible Transformer end connections (3-ph & Neutral) 3 Set 26,020 4,900 78,060

- - - 4.1.4 Wall frame assembly with fire barrier UR No - 3,500

- - - - - -

4.3 - - -

- - -

4.3.1 - - -

a 500 Mtr 40,085 1,000 20,042,295

b Joint suitable for above busway 10 Nos 19,879 2,100 198,786

c 4 Nos 24,781 3,500 99,123

d 6 Nos 22,493 2,100 134,959

e 8 Nos 23,147 2,100 185,173

f 8 Nos 34,720 2,100 277,763

g Provision of Edgewise cross with joint 8 Nos 35,476 2,100 283,811 h Adaptor Box suitable for above busways 3 Nos 54,463 2,100 163,390 i Reducers of following ratings - - - j 3200A/800A 4 Nos 46,725 2,100 186,900 k 3200A/630A 4 Nos 45,675 2,100 182,700

LIGHTING TRANSFORMERS: Supply,Installation ,testing & commissioning of Dry type Transformer with Off circuit tap changing link to Primary Side,with Cable box for Incoming and Busduct for outgoing etc & as per latest I.S.11171: 1985 specification. The transformer shall be suitable for Indoor installation as per tender drawing reference GE-P-SITE-Ele00-01-08-155012 & tender data sheet.The rating of Transformer is as under

Supply & installation of Transformer yard gate made out of 40mm dia GI pipe 11/2" 8 SWG GI wire mesh and two leaves gate with clear width of 3000 mm.

Supply & installation 8 SWG GI wire 1 1/2" mesh chain link fencing of 1.8 Mtr. height with 50 x 50x 6 MS angle at every 2 M interval and 50 x 50 x6 Angle at top. The fencing should be painted with 2 coat of red oxide primer with Aluminium paint

Supply ,Taking delivery at site, shifting from the place of storage to the place of installation between Transformer secondary to Main PCC ,unpacking, site assembly of loose accessories, installation testing and commissioning of the following LT.Busdcuts & its accessories including required support ,etc of following ratings.The required M.S. support for installation of busduct shall be measured under boq item no------------- of M.S .Steel items . The route/ location of busducts shall be as per tender drgawing no GE-P-SITE-Ele00-01-08-155012&GE-P-SITE-Ele00-01-08-155013.

3200A -TPN Busduct (Air Insulated type)

SECTION- M- OVER HEAD BUSTRUNKING SYSTEM (SANDWITCH TYPE)

3200Amp TPN -AL BUSWAY SYSTEM: 3Pole and 100% neutral (TPN) busduct, totally enclosed in extruded Aluminium enclosure, dust proof with IP54 ingress protection,compact sandwitch type low inductance busduct with Tin Plated Aluminium throug out the length of busbars rated as under to withstand the stresses of suitable symmetrical fault levle at 415 Volts with bends ,expansion joints. The bustrunking shall be as per IEC 60439-1&2 and designed for the temperature rise of 55 degree rise over ambient of 35 degree.Thermal stickers shall be provided at each joints for detection of temperature rise of 60/70/80 degree celcious. The testing scope also includes testing of all buseays joint by theremographic meter . The busways shall be installed as per Tender Drawing referenceGE-P-FAC-Ele01-01-18-154988. The required M.S. support for installation of busduct shall be measured under boq item of M.S .Steel items

3200 amp TPN Aluminium Feeder busway with 65KA short circuit with stand for 1 sec.

Provision of Flanged End with joint ( meterage will be counted in running meters)

Provision of 90deg. Bends with joint (Vertical) ( meterage will be counted in running meters)

Provision of 90deg. Bends with joint (Horizontal) ( meterage will be counted in running meters)

Provision of 'T' with joint (Horizontal) ( meterage will be counted in running meters)

Page 12: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 12

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply

4.3.2 - - -

a 440 Meter 12,777 2,100 5,621,847

b Joint suitable for above busway 20 Nos 6,039 1,680 120,790

c 10 Nos 7,537 3,500 75,374

d 4 Nos 6,838 1,680 27,354

e 4 Nos 7,038 1,680 28,153

f Adaptor Box 10 Nos 9,726 1,680 97,262 g Spring hangers 150 Nos 4,224 350 633,623 h End Cover 4 Nos 1,315 350 5,261

- - -

4.3.3 - - -

a 440 Meter 11,239 2,100 4,945,248

b Joint suitable for above busway 20 Nos 5,373 1,680 107,457

c 10 Nos 6,673 3,500 66,728

d 4 Nos 6,066 1,680 24,263

e 4 Nos 6,240 1,680 24,961

f Adaptor Box 10 Nos 9,726 1,680 97,262 g Spring hangers 150 Nos 4,076 350 611,415 h End Cover 4 Nos 1,260 350 5,040

- - -

4.3.4 - - -

a 800Amp 50 k.A. 4 No 378,277 700 1,513,109 b 630Amp 50 k.A. 4 No 199,976 560 799,903

4.3.5 - - -

a UR No 32,190 350

b 1 No 12,162 280 12,162

c 10 No 12,162 280 121,622

d 8 No 12,162 210 97,297

e 4 No 12,162 210 48,648

f 5 No 9,674 210 48,368

g 40 No 9,674 140 386,946

- - -

800 Amp TPN -AL-RISING MAINS : 3Pole and 100% neutral (TPN) busduct, totally enclosed in extruded Aluminium enclosure, dust proof with IP54 ingress protection,compact sandwitch type low inductance busduct with Tin Plated Aluminium throug out the length of busbars rated as under to withstand the stresses of suitable symmetrical fault levle at 415 Volts with bends ,expansion joints. The bustrunking shall be as per IEC 60439-1&2 and designed for the temperature rise of 55 degree rise over ambient of 35 degree.Thermal stickers shall be provided at each joints for detection of temperature rise of 60/70/80 degree celcious.The rising mail shall be provided plug at 2 points in each length of 3 meter of busways( i.e. only 2 tapings)

800 amp TPN Aluminium Plug in busway with 30KA short circuit with stand for 1 sec.(2 plugs)

Provision of Flanged End with joint ( meterage will be counted in running meters)

Provision of 90deg. Bends with joint (Vertical) ( meterage will be counted in running meters)

Provision of 90deg. Bends with joint (Horizontal) ( meterage will be counted in running meters)

630 Amp TPN -AL-RISING MAINS : 3Pole and 100% neutral (TPN) busduct, totally enclosed in extruded Aluminium enclosure, dust proof with IP54 ingress protection,compact sandwitch type low inductance busduct with Tin Plated Aluminium throug out the length of busbars rated as under to withstand the stresses of suitable symmetrical fault levle at 415 Volts with bends ,expansion joints. The bustrunking shall be as per IEC 60439-1&2 and designed for the temperature rise of 55 degree rise over ambient of 35 degree.Thermal stickers shall be provided at each joints for detection of temperature rise of 60/70/80 degree celcious.The rising mail shall be provided plug at 4 points in each length of busways( i.e.2 Nos to each side of Busways)

630 amp TPN Aluminium Plug in busway with 30KA short circuit with stand for 1 sec.(2 plugs)

Provision of Flanged End with joint ( meterage will be counted in running meters)

Provision of 90deg. Bends with joint (Vertical) ( meterage will be counted in running meters)

Provision of 90deg. Bends with joint (Horizontal) ( meterage will be counted in running meters)

Tap off boxes box: Supplying ,installing of 4Poles MCCB With LSG release , 3 CT Operated Dual KWH meter with RS 485 Serial communication Ports, rotary handle etc.of following ratings

Plug in box : Supplying, installing,testing and commissioning of TPN plug in box of of following capacity on above horizontal bus system complete with TPN MCCB 30KA, electrical interconnections, earthing etc as required.

Plug in type type box with rating 315Amp TPN MCCB-30KA Microprocessor LSG type with rotary handle on top of front of plug in box

Plug in type type box with rating 250Amp TPN MCCB-30KA Microprocessor LSG type with rotary handle on top of front of plug in box

Plug in type type box with rating 200Amp TPN MCCB-30KA Microprocessor LSG type with rotary handle on top of front of plug in box

Plug in type type box with rating 125Amp TPN MCCB-30KA Microprocessor LSG type with rotary handle on top of front of plug in box

Plug in type type box with rating 100 Amp TPN MCCB-30KA Microprocessor LSG type with rotary handle on top of front of plug in box

Plug in type type box with rating 63 Amp TPN MCCB-30KA Microprocessor LSG type with rotary handle on top of front of plug in box

Plug in type type box with rating 32 Amp TPN MCCB-30KA Microprocessor LSG type with rotary handle on top of front of plug in box

Page 13: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 13

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply 5 LT Switchgear - - -

- - -

- - - - - -

5.1 Panel Designation: PCC FOR LOAD CENTER-1 - - -

- - -

Approx.Overall dimension ( in mm ):8000 (L) x1500 (W) x 2375 (H) - - - Location : Load Center-1 1 No. 2,479,311 15,000 2,479,311

- - - - - -

5.2 Panel Designation: MLDB OFFICE & CAFETARIA BLDB - - -

- - -

Approx.Overall dimension ( in mm ):3000 (L) x450 (W) x 2025 (H) - - - Location : Load Center-1 1 No. 838,332 6,500 838,332

- - - - - -

5.3 Panel Designation: 675kVAR APFC PANEL 1- ( Load Centre) - - -

- - -

Approx.Overall dimension ( in mm ): 4000 (L) x800 (W) x 2375 (H) - - - Location : HT/LT Substation Room at Factory Load Centre-2 1 No. 972,414 3,500 972,414

- - -

- - - 5.4 Panel Designation:PDB FOR CAFETARIA - - -

- - -

Approx.Overall dimension ( in mm ):2700 (L) x800 (W) x 2375 (H) 1 No. 564,544 2,000 564,544 Location : - - -

- - - 5.5 Panel Designation:PDB OFFICE -2A 1 No. 419,382 1,500 419,382

- - -

Approx.Overall dimension ( in mm ):2700 (L) x800 (W) x 2375 (H) - - - Location : - - -

- - - 5.6 Panel Designation:PDB OFFICE -2B 1 No. 419,382 1,500 419,382

- - -

Approx.Overall dimension ( in mm ):2700 (L) x800 (W) x 2375 (H) - - - Location : - - -

- - - - - -

5.7 Panel Designation:PDB KITCHEN & BASEMENT VENTILATION PDB - - -

- - -

Approx.Overall dimension ( in mm ):3500 (L) x800 (W) x 2375 (H) 1 No. 434,082 2,000 434,082 Location : - - -

- - - 5.8 Panel Designation:LIFT PDB(-Office and cafetaria ) - - -

- - -

Approx.Overall dimension ( in mm ):3500 (L) x800 (W) x 2375 (H) 1 No. 336,694 1,000 336,694 Location : - - -

- - - 5.9 Panel Designation:UTILITY PUMP MCC 1 No. 650,907 2,500 650,907

- - -

Location : Chiller Room - - - - - -

5.10 Panel Designation :PCC For Load Centre-2(HEB) - - -

- - -

Approx.Overall dimension ( in mm ): 6500 (L) x1500 (W) x 2375 (H) - - - Location : Load Centre-2 1 No. 3,679,305 35,000 3,679,305

- - - 5.11 Panel Designation: PCC For Load Centre-3(LEB) - - -

- - -

Supply, assembly, factory test, loading,Taking delivery at site storing at site & supervision at site of LT panel board as per IS 8623/1993, indoor type free standing,in various shipping section, Form 4b in construction, ALUMINIUM BUS BAR , IP54 , fabricated out of 3 mm CRCA Sheet etc & as per specifications. Each panel shall comprising as per followings & Enlcosed ELECTRICAL SLD along with Tender Technical Specifciations.(All panels shall be with TOP and exit of cables.)

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Note: The APFC Relay shall be intelligent microprocessor type with RS 485 serial communication port suitable for minimum 12 stages & 2 Sets of relays shall be considered in each APFC Panel

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Page 14: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 14

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply Approx.Overall dimension ( in mm ): 6500 (L) x1500 (W) x 2375 (H) - - -

Location : Load Centre-2 1 No. 3,350,672 25,000 3,350,672 - - -

5.12 Panel Designation:675kVAR-RT- APFC Panel at Factory Load Centre 2&3 - - -

- - -

Approx.Overall dimension ( in mm ): 4000 (L) x800 (W) x 2375 (H) - - - Location : Load Centre-2&3 2 No. 2,078,560 3,500 4,157,120

- - -

5.13 Panel Designation: MLDB-1 - for Factory Building (LEB) - - -

- - -

Approx.Overall dimension ( in mm ):1800 (L) x450 (W) x 2025 (H) - - - Location : Load Centre-3 1 No. 494,719 4,500 494,719

- - - 5.14 Panel Designation: MLDB-2 - for Factory Building (HEB) - - -

- - -

Approx.Overall dimension ( in mm ):1800 (L) x450 (W) x 2025 (H) - - - Location : Load Centre-2 1 No. 560,869 4,000 560,869

- - - 5.15 Panel Designation:HVAC &OTHER UTILITIES PDB -1 - - -

- - -

Approx.Overall dimension ( in mm ):4500 (L) x800 (W) x 2375 (H) - - - Location : Load Centre-2 1 No. 1,137,817 4,500 1,137,817

- - - 5.16 Panel Designation:HVAC &OTHER UTILITIES PDB -2 - - -

- - -

Approx.Overall dimension ( in mm ):4500 (L) x800 (W) x 2375 (H) - - - Location : Load Centre-3 1 No. 815,931 3,500 815,931

- - - - - -

5.17 Panel Designation: PDB -LOAD CENTER-2 - - -

- - -

Approx.Overall dimension ( in mm ):2700 (L) x800 (W) x 2375 (H) - - - Location : Load Centre-3 1 No. 377,119 1,500 377,119

- - - 5.18 Panel Designation: PDB -LOAD CENTER -3 - - -

- - -

Approx.Overall dimension ( in mm ):2700 (L) x800 (W) x 2375 (H) - - - Location : Load Centre3 1 No. 266,869 1,500 266,869

- - - - - -

5.19 Panel Designation : -3 -Phase 32 Amp -SOCKET OUTLET PDB - - -

- - -

Approx.Overall dimension ( in mm ):2400 (L) x800 (W) x 2375 (H) - - - Location : HEB & LEB FACTORY SHED 2 No. 226,444 2,000 452,888

- - - 5.20 Panel Designation : -1- Phase 20 Amp -SOCKET OUTLET PDB - - -

- - -

Approx.Overall dimension ( in mm ):2400 (L) x800 (W) x 2375 (H) - - - Location : HEB & LEB FACTORY SHED 4 No. 213,582 2,000 854,326

- - -

5.21 - - -

- - -

Approx.Overall dimension ( in mm ):2500 (L) x800 (W) x 2375 (H) - - - Location : Load Center-3 1 No. 169,491 3,000 169,491

- - -

5.22 - - -

- - -

Approx.Overall dimension ( in mm ):2500 (L) x800 (W) x 2375 (H) - - - Location : Load Center-3 1 No. 437,757 1,800 437,757

- - - 5.23 1 No 432,244 750 432,244

- - -

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Note: The APFC Relay shall be intelligent microprocessor type with RS 485 serial communication port suitable for minimum 12 stages & 2 Sets of relays shall be considered in each APFC Panel

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155012 - R0 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155012 - R0 & Panel annexure-1

Panel Designation :UPS Input D.B. 2X60 k.V.A-FACTORY EMERGENCY LIGHTING

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155008 - R0 & Panel annexure-1

Panel Designation :UPS Output D.B. 2X60 k.V.A-FACTORY EMERGENCY LIGHTING

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155008 - R0 & Panel annexure-1

Panel Designation :A.C. D.B- -Utility Building(35k.A.)

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Page 15: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 15

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply Approx.Overall dimension ( in mm ):2500 (L) x800 (W) x 2375 (H) - - - Location : MRS Building - - -

- - - 6 UPS SYSTEM : - - -

- - -

- - -

- - -

6.1 UR Set 1,309,875 21,000

- - -

6.2 2 Set 1,239,000 17,500 2,478,000

- - - 6.3 10k.V.A. UPS for Server application (Independent application) 0 Set 603,750 8,400 -

- - -

- - -

- - -

6.4 2 Set 173,250 7,000 346,500

- 7 TPN -ISOLATORS -

-

UR Nos 64,260 4,900 7.1 400Amps -TPN UR Nos 61,047 2,100 7.2 315Amps -TPN UR Nos 36,540 1,400 7.3 250Amps -TPN UR Nos 36,540 1,400 7.4 200mps -TPN UR Nos 23,940 1,120 7.5 125Amps -TPN UR Nos 13,860 980 7.6 100Amps -TPN 6 Nos 13,860 840 83,160 7.7 63Amps -TPN 36 Nos 13,860 840 498,960 7.8 UP TO 32Amps -TPN 26 Nos 13,860 840 360,360

TOTAL OF SECTION B-SUBSTATION EQUIPMENTS 108,828,560

C SECTION -C -CABLES AND CABLE TERMINATIONS

1 LT CABLES

1.1

1.1.1 3.5.C x 400 Sq.mm. A2XFY(XLPE- AL-Armoured) 400 MTR 1,265 120 506,000 1.1.2 3.5.C x 300 Sq.mm. A2XFY(XLPE- AL-Armoured) 8000 MTR 882 100 7,057,600 1.1.3 3.5.C x 240 Sq.mm. A2XFY(XLPE- AL-Armoured) 1100 MTR 725 100 797,390 1.1.4 3.5.C x 185 Sq.mm. A2XFY(XLPE- AL-Armoured) 1400 MTR 572 80 800,800 1.1.5 3.5.C x 150 Sq.mm. A2XFY(XLPE- AL-Armoured) 1800 MTR 471 80 847,440 1.1.6 3.5.C x 120 Sq.mm. A2XFY(XLPE- AL-Armoured) 300 MTR 396 70 118,800 1.1.7 3.5.C x 95 Sq.mm. A2XFY(XLPE- AL-Armoured) 1000 MTR 314 70 313,500 1.1.8 3.5.C x 70 Sq.mm. A2XFY(XLPE- AL-Armoured) 1300 MTR 255 60 331,760 1.1.9 3.5.C x 50 Sq.mm. A2XFY(XLPE- AL-Armoured) 1350 MTR 183 60 246,510

Supply, Transprtation, storing at site, shifting at work place installation, testing and commissioning of following rating UPS with ,15 Min battery backup , with static & manual bypass Input Voltage: 3 Ph 415 Volts, ±10% Output : 3 -Phase-415Volts 4w 50 Hz ±2% , The scope also includes supply, Installation, Testing and Commissioning with flooded lead-acid batteries complete with intercell connectors & copper cables, battery stand made out of Powder Coated MS Angles with adequate supports to carry the load of the batteries & also TVSS at the input of each UPS to protect against transients, surges & Noise as per the tender specifications

80k.V.A. UPS(Factory Office W.S.) Application & suitable for Parallel operation with communication facilities.

60k.V.A. UPS Lighting Application & suitable for Parallel operation with communication facilities.

Note :Above UPS system shall be suitable for Parallel operation on Separate Power Distribution Boards.

Supply, Transprtation, storing at site, shifting at work place installation, testing and commissioning of 10 KVATrue- On Line sine wave invertor with ,30 Min battery backup , Input Voltage: 3 Ph 415 Volts, ±10% Output : 3 -Phase-415Volts 4w 50 Hz ±2% , The scope also includes supply, Installation, Testing and Commissioning with flooded lead-acid batteries complete with intercell connectors & copper cables, battery stand made out of Powder Coated MS Angles with adequate supports to carry the load of the batteries. (1No Dedicated invertor for MRS Internal Emergemcy Lighting & 1 No Dedicated for Emergency lighting of Basement of Load center-1 )

Supply, Transprtation, storing at site, shifting at work place installation, testing and commissioning of TPN 415 Volts Heavy duty Isolators of following rating, The complete assembly shall be with 2 mm thick CRCA metalic enclosure, Finished paints, IP 65 Degree of protection , Padlock arrangements & Suitable incoming & outgoings cables termination arrangements.

Supply,taking delivery at site, unloading at site,Installation,testing & commisioning of XLPE Insulated, PVC sheathed, armoured, 650/ 1100 V grade power and control cables to be laid in trenches, on cable trays, burried in ground. Civil work for cables to be laid burried in ground such as excavation, backfilling, sand and brick protection and cable tray /tray supports are measured separately and Miscellaneous items such as saddles, clamps, cleats, cable tags/ cable markers etc. are included in the scope

Page 16: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 16

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply 1.1.10 3.5C x 35 Sq.mm. A2XFY(XLPE- AL-Armoured) 1250 MTR 141 50 176,000 1.1.11 2C x 25 Sq.mm. A2XFY(XLPE- AL-Armoured) 300 MTR 116 - 34,650 1.1.12 3.5C x 25 Sq.mm. A2XFY(XLPE- AL-Armoured) 900 MTR 116 50 103,950 1.1.13 4C x 25 Sq.mm.A2XFY(XLPE- AL-Armoured) 3700 MTR 136 - 504,680 1.1.14 3C x 50 Sq.mm. A2XFY(XLPE- AL-Armoured) UR MTR 161 - 1.1.15 3C x 35 Sq.mm. A2XFY(XLPE- AL-Armoured) UR MTR 121 - 1.1.16 3C x 25 Sq.mm. A2XFY(XLPE- AL-Armoured) UR MTR 99 - 1.1.17 3CX10Sq.mm. XFY(XLPE -CU-Armoured) UR MTR 267 - 1.1.18 3CX4Sq.mm. XFY(XLPE -CU-Armoured) UR MTR - - 1.1.19 3CX2.5 Sq.mm. XFY(XLPE -CU-Armoured) 25000 MTR 86 - 2,145,000 1.1.20 4CX16Sq.mm. A2XFY(XLPE- AL-Armoured) 1000 MTR 95 35 94,600 1.1.21 4CX10Sq.mm. A2XFY(XLPE- AL-Armoured) 15500 MTR 88 30 1,364,000 1.1.22 4CX10Sq.mm. XFY(XLPE -CU-Armoured) 450 MTR 348 30 156,420 1.1.23 4CX6 Sq.mm.XFY(XLPE -CU-Armoured) 600 MTR 222 30 133,320 1.1.24 4CX4Sq.mm. XFY(XLPE -CU-Armoured) 1800 MTR 161 25 289,080 1.1.25 4CX2.5Sq.mm. XFY(XLPE -CU-Armoured) 3000 MTR 105 25 313,500 1.1.26 4CX1.5Sq.mm. YWY(PVC -CU-Armoured) 200 MTR 77 25 15,400 1.1.27 2CX10Sq.mm. XFY(XLPE -CU-Armoured) UR MTR - - 1.1.28 2CX4Sq.mm. XFY(XLPE -CU-Armoured) UR MTR - - 1.1.29 19CX1.5Sq.mm. YWY(PVC -Cu-Armoured) 125 MTR 396 70 49,500 1.1.30 24CX1.5Sq.mm. YWY(PVC -Cu-Armoured) 125 MTR 399 80 49,913 1.1.31 5CX2.5 Sq.mm. WY(PVC -CU-Un-Armoured Flexible ) UR MTR - 25

- 2 LT cable Terminations : -

- 2.1 LT cable Termination : -

-

- 2.1.1 3.5.C x 400 Sq.mm. A2XFY(XLPE- AL-Armoured) 36 No 2,977 350 107,172 2.1.2 3.5.C x 300 Sq.mm. A2XFY(XLPE- AL-Armoured) 32 No 2,643 300 84,576 2.1.3 3.5.C x 240 Sq.mm. A2XFY(XLPE- AL-Armoured) 14 No 2,570 300 35,980 2.1.4 3.5.C x 185 Sq.mm. A2XFY(XLPE- AL-Armoured) 20 No 1,658 250 33,160 2.1.5 3.5.C x 150 Sq.mm. A2XFY(XLPE- AL-Armoured) 6 No 1,649 250 9,894 2.1.6 3.5.C x 120 Sq.mm. A2XFY(XLPE- AL-Armoured) 2 No 1,114 200 2,228 2.1.7 3.5.C x 95 Sq.mm. A2XFY(XLPE- AL-Armoured) 8 No 940 200 7,520 2.1.8 3.5.C x 70 Sq.mm. A2XFY(XLPE- AL-Armoured) 22 No 835 180 18,370 2.1.9 3.5.C x 50 Sq.mm. A2XFY(XLPE- AL-Armoured) 16 No 679 180 10,864 2.1.10 3.5C x 35 Sq.mm. A2XFY(XLPE- AL-Armoured) 14 No 600 120 8,400 2.1.11 2C x 25 Sq.mm.A2XFY(XLPE- AL-Armoured) 4 No 395 120 1,580 2.1.12 3.5C x 25 Sq.mm. A2XFY(XLPE- AL-Armoured) 14 No 395 150 5,530 2.1.13 4C x 25 Sq.mm. A2XFY(XLPE- AL-Armoured) 46 No 401 120 18,446 2.1.14 3C x 50 Sq.mm. A2XFY(XLPE- AL-Armoured) UR No - 120 2.1.15 3C x 35 Sq.mm. A2XFY(XLPE- AL-Armoured) UR No - 100 2.1.16 3C x 25 Sq.mm. A2XFY(XLPE- AL-Armoured) UR No - 60 2.1.17 3CX10Sq.mm. XFY(XLPE -CU-Armoured) UR No - 80 2.1.18 3CX4Sq.mm. XFY(XLPE -CU-Armoured) UR No - 100 2.1.19 3CX2.5 Sq.mm. XFY(XLPE -CU-Armoured) 2000 No 180 100 360,000 2.1.20 4CX16Sq.mm. XFY(XLPE -CU-Armoured) 40 No 422 60 16,880 2.1.21 4CX10Sq.mm. XFY(XLPE -CU-Armoured)) 550 No 345 60 189,750 2.1.22 4CX10Sq.mm. XFY(XLPE -CU-Armoured) 30 No 345 60 10,350 2.1.23 4CX6 Sq.mm. XFY(XLPE -CU-Armoured) 40 No 257 60 10,280 2.1.24 4CX4Sq.mm. XFY(XLPE -CU-Armoured) 70 No 257 60 17,990 2.1.25 4CX2.5Sq.mm. XFY(XLPE -CU-Armoured) 60 No 212 40 12,720 2.1.26 4CX1.5Sq.mm. YWY(PVC -CU-Armoured) 20 No 184 40 3,680 2.1.27 2CX10Sq.mm. XFY(XLPE -CU-Armoured) UR No - - 2.1.28 2CX4Sq.mm. XFY(XLPE -CU-Armoured) UR No - - 2.1.29 19CX1.5Sq.mm. YWY(PVC -Cu-Armoured) 30 No 461 100 13,830 2.1.30 24CX1.5Sq.mm. YWY(PVC -Cu-Armoured) 24 No 721 150 17,304 2.1.31 5CX2.5 Sq.mm. WY(PVC -CU-Un-Armoured Flexible ) UR No - 35

- - -

-

TOTAL OF SECTION C- CABLES 17,446,317 D SECTION -D-CABLE TRAYS & ASSOCIATED WORKS

1

1.1 750 mm wide 50 Mtr. 671 200 33,550

Supply & installation of Termination of XLPE insulated, PVC sheathed, 650/1100 V grade, armoured cable including stripping of cable insulation, supplying and fixing of Aluminum / tinned plated copper lugs and crimping the same to the conductor, supply and fixing of double compression cable glands including all 'labour supply and consumable material required for jointing / termination.

Note: Aluminum Lugs shall be used for AlLUMINUM Conductor Cables & Copper Lugs for COPPER Cables

Supply and fixing of followings sizes pre galvanized factory fabricated GI Ladder type cable tays, including straight runs, bends, reducers, Tees, cross members ,couplings, earth continuity flexible conductor for each joints,anchor fastners, supports,drilling,cuttings,nuts, bolts, required civil works etc to complet the work. The required MS support shall be measured under M.S. steel BOQ item no--------------------------

Page 17: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 17

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply Runners 20 x 75 x 20 x 2.5 mm - - - Rungs 20 x 30 x 20 x 2.5 mm 250 mm C/C - - -

- - - 1.2 600 mm wide 2000 Mtr. 611 140 1,221,000

Runners 20 x 75 x 20 x 2.5 mm - - - Rungs 20 x 30 x 20 x 2.5 mm 250 mm C/C - - -

- - - 1.3 450 mm wide 100 Mtr. 545 120 54,450

Runners 20 x 75 x 20 x 2.5 mm - - - Rungs 20 x 30 x 20 x 2.5 mm 250 mm C/C - - -

- - - 1.4 300 mm wide 50 Mtr. 479 84 23,925 1.5 Runners 20 x 75 x 20 x 2.5 mm - - -

Rungs 20 x 30 x 20 x 2.5 mm 250 mm C/C - - - - - -

1.6 100 mm wide UR Mtr. 396 70 Runners 20 x 75 x 20 x 2.5 mm

Rungs 20 x 30 x 20 x 2.5 mm 250 mm C/C - -

2 -

2.1 750 mm x 75 x 75 x 2 mm thick UR Mtr. 1,095 200 2.2 600 mm x 75 x 75 x 2 mm thick 1200 Mtr. 913 140 1,095,600 2.3 450 mm x 75x 75 x 2 mm thick 300 Mtr. 732 140 219,450 2.4 300 mm x 75x 75 x 2 mm thick 800 Mtr. 550 105 440,000 2.5 150 mm x 50 x 50 x 2 mm thick 600 Mtr. 308 105 184,800

- - -

3 - - -

- - - 3.1 750 mm x 75 x 75 x 2 mm thick UR Mtr. 809 140 3.2 600 mm x 75 x 75 x 2 mm thick 50 Mtr. 655 105 32,725 3.3 450 mm x 40 x 40 x 2 mm thick UR Mtr. 501 105 3.4 300 mm x 40 x 40 x 2 mm thick UR Mtr. 341 70 3.5 150 mm x 25 x 25 x 2 mm thick UR Mtr. 187 63

- - -

4 4000 Mtr 400 45 1,600,000

- - -

5 35 MT 63,000 20 2,205,000

TOTAL OF SECTION D- CABLE TRAYS 7,110,500 E SECTION -E-EARTHING

1

1.1 75 mm x 10 mm UR Mtr. 591 85 1.2 50 mm x 10 mm 9000 Mtr. 397 49 35730001.4 25 mm x 6 mm UR Mtr. 132 14 1.5 25 mm x 3 mm (For street light & power socket earthing) 7500 Mtr. 62 21 465000

1.6 300 Mtr. 1,147 21 344100

1.7 50 mm x6 mm (Cu) with Brazing joint 50 Mtr. 2,211 21 1105501.8 8 SWG GI wire 500 Mtr. 13 7 65001.9 14 SWG GI wire UR Mtr. 15 11

1.10 12 SWG GI wire 200 Mtr. 15 8 3000

1.11 200 Nos. 819 100 163800

1.12 80 Nos. 1,200 100 96000

1.12 Lightning air terminal 25 mm dia copper rod 1500 mm Long UR No. 1,071 100

1.13 1200 Mtr. 764 35 916800

- - 0

Supply and fixing of perforated type GI cable trays of the following sizes as per specification.

Supply and fixing of GI cable trays covers of 2 mm thick including all necessary fixing arrangement,hardware, consumable etc . Suit to following GI perforated and ladder type cable trays .

Supply, Installation,testing & Commissioning,  of  MS Powder Coated with RAL 7032 Race Ways ,for fixing high bay light fitting at10 to 12 M. from finished floor leve,.  fabricated out of  14 gauge MS CRC sheet to form C type channel raceway with cover on side(Screw Fixed Type) of size 100x50x50  to be suspended with rods / sleek guyrope / clutch wire from true ceiling /roof  for mounting of tube light fitiings. All supporting membere shall be equvillant to GRIPPLE OR PROFAB Make supporitng members/ structures..  

Supply, fabrication and installation of cable tray cable tray supports, supports for cable trench covers, supporting frame for mounting of control panels, supports for mounting of local control station,Main Electrical Panel,lighting panel, lighting fixture etc. with 2 coats of enemel primer and 2 coats of epoxy paint Note - The rates shall be inclusive of grouting of supports , Anchor fastner,welding rods, nut,bolts,clamps,and any other consumable which required to complete the works.

Supplying and laying of G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by welding overlapping )

25 mm x6 mm (Cu) with Brazing joint (For metering Kiosk & Transformer neutral)

G.I.earthing bus, 750mm Long x 50x10mm with supporting insulators & all Hardwares

Tin plated CU.earthing bus, 750mm Long x 50x6mm with supporting insulators & all Hardwares

1core x70 Sq.mm cu cable ,green colour with yellow strip FRLS PVC insulation (For UPS, L.E.B m/c, CNC m/c & Welding m/c earthing)

Page 18: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 18

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply

2 18 No 9,500 2,100 171000

- - 0

3 22 No 9,500 2,100 209000

- - 0

4

84 No

9,500 2,000 798000

Length - 3000mm - - 0Outer Pipe Dia - 76mm - - 0Inner Pipe Dia. - 38mm - - 0

- - 0

Make : Ashlok,Fast Track, JEF - - 0 - - 0

5 LIGHTNING PROTECTION SYSTEM - - 0 - - 0

5.1 7 Set 123,530 7,500 864710

- - 0 - - 0 - - 0 - - 0

- - 0

- - 0

- - 0 - - 0

- - 0

- - 0

- - 0

- - 0

- - 0

- - 0Each lightning protection set shall be comprising with followings devices - - 0

- - 0

a - - 0

- - 0

b - - 0

Providing earthing stations at locations as called for including providing and laying 3 Mtr Long x 65mmDia G.I. electrode with 50 x 6 mm thick G.I. strip, To form earth electrode with inspection chamber,Watering funnel with 20 gauge G I wire ,600 x600 mm heavy duty Chamber with CI Manhole cover etc.(Scope including excavation by manual/Machines /Boaring, Charcoal, salt, or Bentonie slurry etc) For MSDCL Metering Kiosk.

Supply,Installation,Testing and commissioning of earth pit of size 600 x 600 x 3 mm copper plate with GI water pipe 2.7 mtr long x19mm dia , buried in earth pit with charcoal and salt each in alternative layers including excavation re-filling etc. all as per enclosed drawing, with C.I.legend identification marker.The complete earth pit shall be as per IS 3043. The scope also includes with inspection chamber,Watering funnel with 20 gauge G I wire ,,600 x600 mm heavy duty Chamber with CI Manhole cover etc.(Scope including excavation by manual/Machines , Charcoal, salt, or Bentonie slurry etc) (For UPS,Transformer & DG Neutral earthing)

Supply, testing and commissioning earthing stations as per IS 3043, maintenance free earthing pit of mild steel hot dep galvanised. The pipe shall be insterted one inside the another. The pipe shall be filled & packed with highly conductive and anti corrosive mixture with following diamension. The scope also includes with inspection chamber,Watering funnel with 20 gauge G I wire ,600 x600 mm heavy duty Chamber with CI Manhole cover etc.(Scope including excavation by manual/Machines /Boaring, .

300 X 150mm chamber shall be provided for inspection and connection. 50mmx6 mm thick copper strip shall be nut bolted to connect the earthing strips/Leads The electrode shall be provided with two chemical compound bags (20Kg each)

Supply & Installation of ESE Lightning Rod , with Stainless Steel Body, working on the Principle of (ESE) Early Streamer Emission technology, which will offer LEVEL 1 protection for 79 Mtrs radius when mounted at a height of 5 mtrs from the plane to be protected, complying to NFC 17 102.

Type- Early Streamer EmissionMake & Model - CIRPROTEC (NIMBUS)

Matrerial Used - Corrosion resistant stainless steel body

Construction Details => The electronic circuit of the ESE rod shall be encapsulated in an epoxy mould toavoid derating or degradation due to atmospheric conditions. This also makes the Lightning rod weather proof and suitable for installation in highly corrosive atmosphere.The rods shall be made of Corrosion Resistant Stainless body conforming AISI 316 grade.

The Lightning rod shall be self powered type and shall not require any form of external power supply/batteries for its operation. .

Conformity to standards - As per NF C17-102 and UNE 21186-96Radius of Protection(M) - 79M level 1

Construction Details - Lightning Rods shall be manufactured according to UNE 21.186-96 and NF C17-102 standards .

Sensors-Type - Electronic equipped with triggering device

Test Reports -Should have been tested at an internationally accredited Laboratory and CPRI , Bangalore and the necessary test reports to be attached.

Shall be designed to check the integerity of the electronics periodically with a tester

4 DIGIT ELECTROMECHANICAL Lightning Transient Event counter ,in a IN WEATHER PROOF ENCLOSURE shall be mounted in 1.5 Mtrs from the ground level

Main Lightning Air terminal suitable for protection of Radious of 80 meter from its base of 5 Meter height for Level III Protection.

GI Elevation pole with a reducer to fix the LA unit, Base Plate, Clamps and all required fixing accessories ( Ready to Install).

Page 19: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 19

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply - - 0

c - - 0

- - 0

d - - 0

- - 0

5.2 7 Nos. 15,400 1,000 107800

- - TOTAL OF SECTION- E- EARTHING (GROUNDING) - - 7,829,260

- - F SECTION – F D.G.SETS - - 1 DIESEL GENERATOR SET - -

1.1 2 Nos 9,000,000 30,000 18,000,000

- - -

1.2 2 Nos 1,000,000 10,000 2,000,000

- - -

1.3 - - -

- - - a 500 mm dia. NB 55 Mtrs 8,800 2,500 484,000 b 350 mm dia. NB 35 Mtrs 6,550 2,000 229,250

- - -

1.4 5000 K.G. 85 25 425,000

- - - - - -

1.5 ELECTRICAL - - - - - -

a - - -

b 24C x 1.5 Sq.mm PVC screened cable 300 Mtr 1,445 56 433,500 c 8C x 1.5 Sq.mm PVC screened cable 300 Mtr 535 42 160,500 d 4C x 1.5 Sq.mm PVC screened cable ( For Electronic Governer ) 300 Mtr 314 35 94,200

e 12 C x 0.5 Sq.mm PVC screened Triad cable ( for temperature scanner ) 300 Mtr 562 42 168,600

f Profi bus 2 wire Communication cable 300 Mtr 184 42 55,200 - - - - - -

1.6 1 Set 4,200,000 12,000 4,200,000

- - -

Test Clamp to connect the down conductor to the earth termination and disconnect the down conductor from the earth termination for regular checks of the earth termination resistance value.

1 Set of Remote Control unit required only for testing the Prevectron air terminal.

Lightning Flash Counter. Electronically controlled, register every strike between 1000 A to 100 KA for a 8/20 microsecond peak current. Tested in High Voltage Laboratory (CPRI).

Supply Transporation, Unloading at Place of installations,, installation, testing and commissioning of radiator cooled 1000 KVA prime (actual) rating diesel generating set (11000 Volts Alternator with PCCM or equivalent) along with day oil fuel tank, CT Adaptor Box, AVM Pads including cable termination box with all associated equipment / work as per specifications. Alternator shall have class H insulation 11000 Volts and rated for 800 KW output. Engine shall not be derated upto 50 deg.C ambient and suitable for bearing the starting current after changeover. The scope also includes providing foundation details drawings to Engineer In Charge (Foundation will be provided by Civil scope of works), Liasioning work from Govt Authorities Like Electrcial Inspector, MIDC, Pollution control Boards etc. The scope also includes filling first oil ,fuel for commissioning.

Supply, installation, testing and commissioning of powder coated acoustic enclosure suitable for 1000 KVA DG set for indoor application as per specification complete with all accessories as required including ventilation system. No deration in DG set capacity shall be accepted on this account. The scope also includes providing foundation details drawings to Engineer In Charge (Foundation will be provided by Civil scope of works), Liasioning work from Govt Authorities Like Electrcial Inspector, MIDC, Pollution control Boards etc.

Supply, erection, testing and commissioning of exhaust piping Min. 6mm Thick of following sizes with welding joint including bends, MS pipe supports, clamps, dash fastener, nuts, bolts etc.,with first layer of insulation 25mm thick ceramic fiber wool (96Kg/Cub. Mtr.) & second layer minimum 50mm thick rockwooll (150Kg/Cub Mtr.) covered with 26 SWG aluminium sheet claddings etc. complete as required and as per specifications.

Exhaust pipe supporting system with M.S channel, M.S angle, M.S flat, dash fastners, nut, bolt etc. complete including 1 coat of redoxide & 2 coat of enamel paint and other Accessories as required at the site of work.

PLC / SCADA Application Interface cables Supply & Installation( PVC Screened Copper cables)

Supply, installation, testing and commissioning of D.G Set Automatic Synchronizing panel suitable for,11k.V.26.2k.A. ,2 x 1000k.V.A. D.G. Set as per Technical specification & enclosed Single line diagram ( Drg. No GE-P-FAC-Ele00-01-08-155003 ) The Specification for D.G. Autosynchronizing Panel shall be as per HT Panel items reference sr 1 of section B

Page 20: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 20

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply

1.7 - - -

NGR Element : Resistance: 121Ohms & 52.48 Amps at 11/√ 3 k.V. 2 Nos 225,000 5,000 450,000 1 No 400Amp-12k.V. Single Pole Vacumm contactor with Auxiliary contacts - - - 3 Nos 75/1Amp CL -PS CT with internal wiring & terminals - - - IP Degree of complete NGRVPanel : IP65 - - -

- - - TOTAL OF SECTION- F- GENERATOR SET - - 26,700,250

G SECTION -G-LIGHTING FIXTURES/EXHAUST FANS - - - -

1 - -

- -

1.1 50 Nos 1,260 280 63,000

- - -

1.2 875 Nos 4,883 350 4,272,188

- - -

- - - - - -

1.4 176 Nos 3,308 420 582,120

- - -

1.5 8 Nos 7,560 490 60,480

- - -

1.6 0 Nos 2,310 280 -

- - -

1.7 10 Nos 1,418 210 14,175

- - -

1.8 0 Nos 1,208 210 -

- - -

1.9 0 Nos 3,833 140 -

- - -

1.10 8 Nos 5,460 245 43,680

- - -

Supply, installation, testing and commissioning of NEUTRAL GROUNDING RESISTOR (NGR) panel suitable for Each D.G. Set of 1000k.V.A. as per Technical specification & enclosed Single line diagram ( Drg. No GE-P-FAC-Ele00-01-08-155003 ) The Complete NGR Panels shall be comprising followings parameters.

Supply, installation, testing and commissioning of luminaires complete with, lamps, ballast, starter, HPF condenser, standard down rod, connecting cord, The rate shall include all necessary fixing accessories like MS hooks, MS supports, fasteners, with all necessary hardware, accessories as required for complete installation. Quoted rate shall exclude the cost of earthing . Note: Catalogue numbers indicated are only to describe type of light fixture required. Lamp Colour shall be - 84 or as approved by Architect / Consultant.

Supply Installation, testing & commissioning of 2x28 W T5 with electronic ballast equivallent to GE cat no GET CI 2X28 C/S HF.The scope also includes all accessories and tube etc., including supplying and fixing ball and socket arrangement, 2 no. down rods of 20 mm dia X1.6 mm thick G.I. steel conduit upto 30 cm length, painting and wiring the down rods and connection with 1.5 sq. mm FR PVC insulated, copper conductor, single core wires and earthing , fastening accessores etc as required to complete the work

4X54W T5 Highdbay Luminaire Equivallent to GE Cat Ref ELC454 with Lamps of 4 X54W FTL T5 with dimmable choke suit for dimming control, on M.S. raceway mouted on 12-14 Meter elevation including arrangement of all cherry pickers, loopings of 3 core 1.5 Sq.mm Flexible FRLS insulated cables from looping junction boxe to each fitting

NOTE.:- Race will supply 7 instaalation will be measured separetly. (No welding will allowed)

95 W LED IP 66 Street light fixture to fixed on 7.5 to 9 Meter hight poles including supply and pulling of 3 Core x 1.5 Sq..mm Cu Flexible ,-FRLS cables from Pole mouted looping junction box to each fitting terminals

150W HPMV Integral Post top light fixture equivallent to GE cat no DUNAADCMH150W TU including supply and pulling of 3 Core x 1.5 Sq..mm Cu Flexible ,-FRLS cables from concealed looping junction box to each fitting terminals, including providing concealed 25 mm PVC pipes for incoming cables to Looping junction box & up to each light fittings,

42 W LED Recess mounted decorative luminaries equivallent to GE cat no GCRO42.56 MO with all accessories and tube etc., including supplying and fixing ball and socket arrangement 2 nos /Flexible SS Chains/ or 2 no. down rods of 20 mm dia X1.6 mm thick steel conduit upto 30 cm length, painting and wiring the down rods and connection with 3 Corex 1.5 sq. mm FRLS insulated, copper conductor, cable and earthing etc as required.

2X28W FTL T5 Surface Mounted with clear Acrylic cover Luminaire with electronic ballast equivallent to Wipro cat no WCF 50228 SGW including required clamps , fastners ,connection to fittings etc to fixed in staircase etc.

2 x18 W Decorative Recess mounted Down lighter equivallent to GE cat no GECFLC2X36DNLR(H) HF with required hanging support from ceiling

1 x18 W Decorative Recess mounted Down lighter equivallent to GE cat no GECFLC2X18DNLR(H) HF with required hanging support from ceiling

150 W MH Integral Flood light Luminaire Equivallent to GE cat no GEMF1X150CAI with required support to fixed on top plate of 7.5 Mtr high street light pole

Page 21: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 21

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply

1.11 UR Nos - -

- - - Note for above light fittings items - - -

i - - -

ii - - -

iii - - -

- - - 2 Supply,& Installation of Exhaust fans of following ratings - - -

- - -

2.1 30 No 6,930 350 207,900

- - -

2.2 0 Nos 1,890 175 -

- - -

2.3 80 Nos 10,080 350 806,400

- - -

2.4 0 Nos. 7,560 280 -

- - TOTAL OF SECTION G- LIGHTING LUMINARIES - - 6,049,943

- -

H - -

- - 1 POINT WIRING -IN M.S. CONDUITS - -

1.1 - -

a Primary light point up to 5 meter length 10 Point 806 175 8,060 b Primary light point up to 8 meter length 20 Point 1,151 200 23,020 c Primary light point up to 10meter length 20 Point 1,424 225 28,480

- - -

1.2 - - -

a Secondary light point up to 2 meter length 25 Point 355 150 8,875 b Secondary light point up to 4 meter length 20 Point 547 175 10,940 c Secondary light point up to 5meter length 20 Point 693 200 13,860

- - -

1.3 UR Point 1,424 -

- - -

1.4 - - -

400 W MH Integral Flood light Luminaire Equivallent to GE cat no ZF400 KRC .The fitting shall be installed on top mounting plate of 16 Mtr high lighting mask.

All light fittings quantities shall be procured as per Final approved Drawings by architect & approval from client /Architects for sample of each light fittings.

Connection of lighting fixtures from ceiling rose / junction box by flexible copper wires in flexible conduit/M.S. ball and socket arraqngment is included in the conduit down rod, scope

The structural supports for suspension of lighting fixtures are measured seperately

Supply, of Exhaust fan Heavy duty 230 V AC 50 Hz 305 mm 1400 RPM with condenser complete erected in position with n/c materials Fan motor with moisture treatment and class E insulation & With bird protective screen

Supplying of capacitor type1200 mm sweep ceiling fan complete with down rod, blades, shakle etc. with high breeze, high speed for operation on 230V, 50 Cy. Single phase A.C. supply confirming to IS 374-1979 and with double ball bearing system The fan shall be green rated as per BEE norms.

Supply of 750 mm sweep-1 Ph 240 Volts 50 Hz Wall/Column Mounted Air cirulated fans including Inbuilt speed regulator Including all necessary fixing hardware,Anchor fastner etc. Almonard make

Supply & Fixing of Ceiling mounted (surface/flush) high performance, Movement Detector with the coverage of 6Mtrs dia complete with necessary Sensor control wiring.vWIPRO Cat ref COP 11010 OR Hager make EE805 or Schneider make CSS54E-WE or Bajaj Make - Bajaj-Leviton OSC 10-MOW

SECTION :H: SUPPLY & PROVIDING OF POINT WIRING AND ACCESSORIES.

Primary light Wiring for followings light point/ fan point/ exhaust fan point/ call bell point with 2 Nos 2.5 sq.mm FRLS insulated copper conductor single core cable in surface / recessed 25 mm dia, 16 SWG black stove enemelled steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS insulated copper conductor single core cable etc as required. (Wiring from Lighting Switch boards to first light points in the group of lighting circuit )

Secondary light Wiring for followings light point/ fan point/ exhaust fan point/ call bell point with 3 Nos 1.5 sq.mm FRLS insulated copper conductor single core cable in surface / recessed 25 mm dia, 16 SWG Black stove enemelled steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS insulated copper conductor single core cable etc as required. (Wiring from Lighting Switch boards to first light points in the group of lighting circuit )

Secondary point Wiring for twin control light point with 1.5 sq.mm FR LS insulated copper conductor single core cable in surface / recessed 25 mm dia, 16 SWG Black stove enemelled steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR LS insulated copper conductor single core cable etc as required.

Wiring for circuit/ submain wiring along with earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface / recessed 25 mm dia, 16 SWG Black stove enemelled steel conduit as required

Page 22: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 22

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply a 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire 0 Mtr 311 25 - b 2 X 4 sq. mm + 1 X 4 sq. mm earth wire 0 Mtr 349 35 - c 2 X 6 sq. mm + 1 X 6 sq. mm earth wire 0 Mtr 405 40 -

- - -

1.5 0 Mtr 475 35 -

1.6 0 Mtr 437 25 -

1.7 0 Mtr 516 45 -

- - - 2 POINT WIRING -IN PVC CONDUITS - - -

2.1 - - -

a Primary light point up to 5 meter length 0 Point 806 150 - b Primary light point up to 8 meter length 0 Point 1,151 175 - c Primary light point up to 10meter length 0 Point 1,424 200 -

- - -

2.2 - - -

a Secondary light point up to 3 meter length 0 Point 280 125 - b Secondary light point up to 5 meter length 0 Point 542 160 - c Secondary light point up to 8meter length 0 Point 867 175 -

- - -

2.3 UR Poit 1,273 -

- - -

2.4 - - -

a 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire 0 Mtr 248 15 - b 2 X 4 sq. mm + 1 X 4 sq. mm earth wire 0 Mtr 286 20 - c 2 X 6 sq. mm + 1 X 6 sq. mm earth wire 0 Mtr 342 25 -

- - -

2.5 0 Mtr 273 20 -

2.6 0 Mtr 248 15 -

Power plug wiring in M.S. Black stove condiut (2 x 4 sq.mm) - Wiring for power plug with 2X4 sq. mm., FR LS insulated, copper conductor, single core cable in surface/recessed 16SWG ,25 mm dia M.S. Black stove conduit along with 1 no. 4sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.

Power plug wiring in M.S. Black stove condiut (2 x 2.5 sq.mm) - Wiring for power plug with 2X2.5 sq. mm., FR LS insulated, copper conductor, single core cable in surface/recessed 16SWG ,25mm dia,M.S. Black stove conduit along with 1 no. 2.5sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.

Power plug wiring in M.S. condiut (4 x 4 sq.mm )- Wiring for powersocket outlet with 4X4 sq. mm. FRLS insulated, copper conductor, single core cable in surface/recessed 16SWG ,25 mm. dia M.S. black stoved enemelled conduit along with 2 nos. 4sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.

Primary light Wiring for followings light point/ fan point/ exhaust fan point/ call bell point with 2 Nos 2.5 sq.mm FRLS insulated copper conductor single core cable in surface / recessed Heavy duty 2 mm in thick & 25 mm diameter PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS insulated copper conductor single core cable etc as required. (Wiring from Lighting Switch boards to first light points in the group of lighting circuit )

Secondary light Wiring for followings light point/ fan point/ exhaust fan point/ call bell point with 3 Nos 1.5 sq.mm FRLS insulated copper conductor single core cable in surface / recessed Heavy duty 2 mm in thick & 25 mm diameter PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS insulated copper conductor single core cable etc as required. (Wiring from Lighting Switch boards to first light points in the group of lighting circuit )

Secondary point Wiring for twin control light point with 1.5 sq.mm FR LS insulated copper conductor single core cable in surface / recessed Heavy duty 2 mm in thick & 25 mm diameter PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR LS insulated copper conductor single core cable etc as required.

Wiring for circuit/ submain wiring along with earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed Heavy duty 2 mm in thick & 25 mm diameter PVC conduit as required

Power plug wiring in PVC condiut (2 x 4 sq.mm) - Wiring for power plug with 2X4 sq. mm., FR LS insulated, copper conductor, single core cable in surface/recessed Heavy duty 2 mm in thick & 25 mm diameter PVC conduit along with 1 no. 4sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.

Power plug wiring in PVC condiut (2 x 2.5 sq.mm) - Wiring for power plug with 2X2.5 sq. mm., FR LS insulated, copper conductor, single core cable in surface/recessed Heavy duty 2 mm in thick & 25 mm diameter PVC conduit along with 1 no. 2.5sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.

Page 23: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 23

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply

2.7 UR Mtr 1,084 -

- - - 3 Wiring Accessores for Raw power & UPS Power socket outlets - - -

- - -

3.1 - -

a 1 or 2 Module(75mmx75mm) UR No 132 25 b 3 Module (100mmX75mm) UR No 138 25 c 4 Module (125mmX75mm) UR No 159 30 d 6 Module (200mmX75mm) UR No 274 35 e 8 Module (125mmX125mm) UR No 307 35 f 12 Module (200mmX150mm) UR No 460 50

- -

3.2 - -

a 1 or 2 Module UR No 130 25 b 3 Module UR No 145 25 c 4 Module UR No 162 30 d 6 Module UR No 253 35 e 8 Module UR No 271 35 f 12 Module UR No 284 50

- -

3.3 - -

a 5/6 amps switch UR No 110 25 b 15/16 amp switch UR No 169 25 c 3 pin 5/6 amp socket outlet UR No 177 35 d 6 pin 15/16 amp socket outlet UR No 208 40

- - - - - -

3.4 UR Mtr 122 10

- -

3.5 UR Mtr 110 8

- -

4 - -

- - a 50 x 38 x 2 mm UR Mtr 266 40 b 100 x 38 x 2 mm UR Mtr 411 60 c 150 x 38 x 2 mm UR Mtr 696 95 d 200 x 38 x 2 mm UR Mtr 785 125 e 300 x 38 x 2 mm UR Mtr 1,081 130

5 - -

- - a 250x250x60- 75 mm three compartment. UR Nos 1,512 - b 265x265x53- 80 mm three compartment. UR Nos 1,512 -

UR Nos - -

6 - -

a 250x250x60- 75 mm three compartment. UR Nos 3,150 - b 300x300x60- 80 mm three compartment. UR Nos 3,150 -

Power plug wiring in PVC condiutt (4 x 4 sq.mm )- Wiring for powersocket outlet with 4X4 sq. mm. FRLS insulated, copper conductor, single core cable in surface/recessed Heavy duty 2 mm in thick & 25 mm diameter PVC conduit along with 2 nos. 4sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.

S/F GI Box along with modular plate: Supplying and fixing following size /modules, GI box along with modular base & cover plate for modular switches in recess etc as required. The scope also includes cutting of wall, block works, & POP of walls with mesh after plate fixing & other related civil works to make surface good .

Supply & fixing following modular base and cover plate for modular switches in recess etc as required.

Supplying and fixing following modular switch/ socket on theexisting modular plate & switch box including connections butexcluding modular plate etc. as required.(Raw Power /UPS Power socket outlets)

Supply and providing of Power plug wiring in Raceway in office (2 x 4 sq.mm) - Wiring for light/power plug with 2X4 sq. mm., FR LS insulated, copper conductor, single core cable in existing surface/recessed raceway along with 1 no. 4sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.(UPS & Raw Power Power)

Supply and providing of Power plug wiring in Raceway in office (2 x 2.5 sq.mm) - Wiring for light/power plug with 2X4 sq. mm., FR LS insulated, copper conductor, single core cable in existing surface/recessed raceway along with 1 no. 2.5sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.(UPS & Raw Power Power)

Supply, fixing, laying and embedding in UNDER FLOOR ALUMINUM of following sizes complete with all accessories including junction box with 2 mm thick Stainless steel cover plate,neoprene gasket in joints ,cutting the floor and jamming the raceway with all necessary hardware (including civil works) as required.

Supply, fixing, commissioning of following sizes access outlet with all accessories, cutting the floor and jamming the access outlet with all ncessary hardware (including civil works) as required.

Supply , fixing, commissioning of following sizes cross over/ junction box with 3 mm thick cover plate with all accessories cutting the floor and jamming the junction box with all necessary hardware including civil works as required.

Page 24: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 24

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply - - - - -

TOTAL OF SECTION H- POINT WIRING & ACCESSORIES - - 93,235 - - - -

I - -

- -

1 - -

- -

1.1 20 No 65,000 1,500 1,300,000

Incomer : 63 A,4 pole, MCB 10k.A. C-CL - - - Outgoing :As under - - - 16 - 25A-2P-RCBO 30m.A.:15 Nos - - - (5 Nos/Phase) - - -

- - -

1.2 12 Nos 50,000 1,200 600,000

(a) - - -

(b) Outgoing :As under - - -

i - - -

ii 16 - 25A-2P-RCBO 30m.A.:36 Nos(12 Nos Per Phase) - - - - - -

1.3 6 Nos 35,000 900 210,000

(a) - - -

(b) Outgoing :As under - - -

i - - -

ii 16 - 25A-2P-RCBO 30m.A.:18 Nos(6 Nos Per Phase) - - - - - -

1.4 Typical E. L. D.B. (Ref Tender drawing no GE-P-FAC-Ele00-01-11-1550010) 15 Nos 32,000 800 480,000

(a) - - -

(b) Outgoing :As under - - -

i - - -

ii 16 - 25A-2P-RCBO 30m.A.:12 Nos(4 Nos Per Phase) - - - - - -

1.5 Area Street light Final D.B. for Street Lights as under 2 No 80,000 1,500 160,000 Incomer : 125 Amp -4 Pole MCCB + 1 No 4 Pole-110 Amp Moduler Contractor - - - Outgoing 12 Nos 32 Amp TP MCB 10K.A. CL + 32Amp - - - 4 Pole ELCB -30m.A. per Outgoings& 24 Hrs Timer + Photo Cell with - - - Manual / Auto Selctor switch, Interface provision with BMS & its control wiring etc. - - -

- - - 1.6 Flood Light Mast lighting PDB.as under 1 No 80,000 1,500 80,000

Incomer : 100 Amp -4 Pole MCCB , + 1No4 Pole-110 Amp Moduler Contractor - - - + 24 Hrs Timer + Photo Cell with - - - Manual / Auto Selctor switch, Interface provision with BMS & its control wiring etc. - - - Outgoing 10 Nos 32Amp 25k.A. TP-MCCB-LS -Release. - - -

- - - 1.7 D.B. Server system 1 No 15,000 500 15,000

Incomer : 63 A,DP,MCB type Isolator - - - Outgoing : 25 A DPMCB- 10k.A -D-CL10 Nos per Phase - - -

- - - 1.8 Security Kiosk D.B. as under 4 No 22,000 650 88,000

Incomer : 63 A,4 pole, MCB 10k.A. C-CL +4 Pole - - - 63 Amp ELCB 100m.A. - - - Outgoing : As under - - - a. 12 Nos 20 A SPMCB- 10k.A -C-CL (4 Nos /Phase) - - -

b. 4 Nos 32 A -TP MCB 10k.A. C-CL - - - - - -

SECTION -I-LIGHTING PANELS-IP42 - & INDUSTRIAL SWITCH SOCKET OUTLET/ISOLATORS

Supplying and fixing following way prewired TP&N MCB distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FR LS insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc. as required.

Typical Raw Power & UPS Power Final D.B. Application (Ref Tender drawing no GE-P-FAC-Ele00-01-11-1550013)

Typical Lighting D.B. (Ref Tender drawing no GE-P-FAC-Ele00-01-11-1550011)

Incomer : 63 A,4 pole, MCB 10k.A. C-CL+Auto /Manual Control selector switch for outgoing circuits

16-25 Amp 2 P Moduler Power contactor with Auxiliary contact for Remote ON /OFF of contactor from BMS & ON/OFF status of contactor to BMS : 36 Nos(12 Nos Per Phase)

Typical Lighting D.B. (Ref Tender drawing no GE-P-FAC-Ele00-01-11-1550011)

Incomer : 63 A,4 pole, MCB 10k.A. C-CL+Auto /Manual Control selector switch for outgoing circuits

16-25 Amp 2 P Moduler Power contactor with Auxiliary contact for Remote ON /OFF of contactor from BMS & ON/OFF status of contactor to BMS : 18 Nos(6 Nos Per Phase)

Incomer : 25 A,4 pole, MCB 10k.A. C-CL+Auto /Manual Control selector switch for outgoing circuits

16-25 Amp 2 P Moduler Power contactor with Auxiliary contact for Remote ON /OFF of contactor from BMS & ON/OFF status of contactor to BMS : 12 Nos(4 Nos Per Phase)

Page 25: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 25

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply

2 - - -

- - - - - -

2.1 100 Set 6,640 350 664,000

- - -

2.2 28 Set 10,630 490 297,640

- - -

2.3 4 Set 24,774 630 99,096

- - -

3 - - -

3.1 20A SP MCB - 01 No. in Metal BOX 25 No. 536 75 13,400 3.2 20A SP MCB - 02 No. in Metal BOX 30 No. 902 75 27,060 3.3 20A SP MCB - 03 No. in Metal BOX 40 No. 1,122 75 44,880

- - - - - -

TOTAL OF SECTION I- FDB /SSO/LDS - - 4,079,076 J SECTION -J-EXTERNAL LIGHTING - -

- -

1.0 - -

- - 1.1 Single bracket 183 No 12,500 2,500 2,287,500 1.2 Double bracket 3 No 15,000 700 45,000 1.3 50 mm dia G.I. bracket mouted street light poles(Max 3 Mtr Length) 2 No 10,080 700 20,160

- - - - - -

3 Flood Light Mast As under - - - - - -

2.1 5 Set 323,946 60,000 1,619,730

2.1.1 - - -

Supply, Installation, Testing & Commissioning of Following Readymade Industrial Power Sockets with neccessory cable end boxes.The each socket outlet shall be installed at fabricated M.S. Supports/ Frames suit to Sokcet outelt dimensions. The required steel shall be measured under M.S. Fabrication item of this BOQ.

3 Pin, 20 Amp, 230 Volts Industrial switch socket outlet sheet steel enclosed IP54 with 1 No. earthing terminal 'controlled by -SPN MCB 10K.A -C-CL and provided with chain and 'cover and suitable for loop in loop out of 3 x 2.5 'sq.mm XFY cable.:The complete assembly shall be suitable for IP65 with Polycarbonate body.

Combine Industrial switch Socket Out Let : 5 Pin 32A, TPN, 415 Volts Industrial switch socket controlled by 4 Pole MCB 10K.A. C-CL & 3 Pin, 20 Amp, 230 V industrial switch socket out let controlled by-SPN MCB 10K.A .-C-CL , sheet steel enclosed indoor type with 2 Nos. earthing terminals and provided with chain & cover suitable 'for loop in loop out of 3.5C x 35 sqmm A2XFY cable.:The complete assembly shall be suitable for IP65 with Polycarbonate body.

5 Pin 63A, TPN, 415 Volts Industrial switch socket controlled by 4 Pole MCB 10K.A. C-CL industrial switch socket out let sheet steel enclosed indoor type IP-54 with 2 Nos. earthing terminals and provided with chain & cover suitable 'for loop in loop out of 3.5C x 35 sqmm A2XFY cable.:The complete assembly shall be suitable for IP65 with Polycarbonate body.

METAL MCB BOXES (IP 42) : Supply & fixing of MCB Box enclosed in 1.6mm thick, CRCA sheet steel box. The box shall be concealed / Surface in the wall. The plate cover is properly aligned & flush with the wall surface all materials will be in contractor scope.

Supply & installation of hot deep galvanized (internally & externally) Octogonal cross section pole with base plate as per IS 2629 with ,supply and fixing of 2 Nos. of 63 mm dia PVC pipes for cable entry,with inside cable termination,earth connection & with weatherproof door & locking facility 3Nos. 2.5 sq.mm stranded copper flexible wires with MCB control (Minimum Overall Height 8.00 M,3mm thick, bottom dia 200mm,top dia 76 mm,bottom plate 275 mm x 275 mm x 20 mmthick. Including concrate foundation & foundation bolts.(The weather proof Loop In Loop Out junction box with all accessories shall be integral part of street light Poles)

Supply of 16M high mast shaft in two sections suitable for 39 m/sec wind speed, with raising lowering system comprising, head frame, luminaries carriage suitable to install 8 nos luminaries in symmetrical arrangement, double drum winch, 6mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle, junction box, lightening finial.The scope of works also includes installation including supply of foundation bolts manufactured from special steel along with nuts, washers, anchor plates and templates. and concreeting including excvation,cement, etc to complete the works.Each lighting mast shall be provided with followings electrical requirement & accessoris. (Note: Contractor to submit required vendor shop drawings for complete Flood light mast system with calculation from structural consultant for foundation before commence of work)

Supply of non-integral floodlight luminaries type Equvillent to GE Cat ref ZF 400KRC with one no. 400 W MH(KRC) T lamps With control gear boxes The scope also includes Supply and fixing of 3 x 2.5 Sq.mm Cu-Armoured Cables from each Control gear to each light fittings & its connection with Weather proof D.C. Gland .: 8 Nos to each lighting mast .

Page 26: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 26

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply

2.1.2 - - -

2.1.3 - - -

a. - - -

b Outgoing as under - - - b.1 8Nos SP MCB,16Amp,10k.A., B-Class for lighting circuit - - - b.2 2 No 16 Amp DP MCB,10k.A., B-Class forAviation light - - -

b.3 - - -

b.4 16 Amp 10k.A.,B-Class SP MCB controlled 5/15Amp Socket Outlet - - - - -

TOTAL OF SECTION J- EXTERNAL LIGHTING - - 3,972,390 - -

K SECTION -K -MISCELLANEOUS : - - 1 Supply,Installation,Testing & commissioning of - -

the following - of the following - - - -

1.1 Supply, Installation, testing and commissioning of start stop - - local control stations of LM6 material with momentary - - type PB for stop, start and latch and 1 No. earthing terminal - - suitable for 4 x 1.5 sq.mm - YWY cable - -

- -

Supply of single dome aviation obstruction lights of type BJAOL 1 with one nos no. 25 W Neon lamp : 2 Set to each lighting mast & individual Armoured 3x2.5 cu cable connection for the same from its control panel to neon lamp terminals .

Supply of out door, Weather proof IP65 Feeder Pillar as per following specification to each Lighting Mast

Incomer:32Amp 4 Pole MCB ,10k.A.,C-Class & 32 Amp 4 Pole ELCB 30m.A. +RYB LED Indication+Space Heater with Thermostat.

1 DOL Feeder for suitable winch motor as per vendor design & with necessary indication & control system for "LOWER& RAISE" of mast.

Page 27: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 27

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply i Outdoor, weatherproof type with IP 65 protection UR No. - -

- - ii Indoor type with IP54 protection UR No. - -

- - 1.2 Junction box fabricated from 16 SWG sheet steel with - -

screwed gasketed cover and 1 No.earth terminal duly - - painted with two coats of red oxide and two coats of - - aluminium paint and to receive 4 Nos. 3 x 2.5 sq.mm YWY - - cables complete with Elmex terminals. - - (Minimum size100mm x 100mm x 75mm) 850 No. 441 49 374,850

- - - Note : Structural supports for mounting are measured separately - - -

- - - 1.3 Floor mounted bucket stand with buckets to hand 4 nos. - - -

of 13 ltrs buckets. The stand shall be 5'(L) x 3'(H) x 2"(W) - - - made out of 30 x 300 x 4mm MS angle frame duly - - - coated with 2 coats of red oxide primer & 2 coats of 2 Set 3,000 500 6,000 red finish paint - - -

- - - 2 Supply and installation of GI pipe class B on wall / steel structure / - -

under floor including bending / treading etc - - - -

2.1 38 mm dia UR RMT - - - -

2.2 50mm dia UR RMT - - - -

2.3 75mm dia UR RMT - - - -

2.4 100 mm dia UR RMT - - - -

2.5 150 mm dia UR RMT - - - - - -

3 Supply and installation of 2c x 2.5 sq.mm copper flexible wire UR Mtr. - - - - -

4 Cable Markers as per Std. Drawing - - - 4.1 H.T. Cable marker 15 No. 315 70 4,725 4.2 L.T. Cable Marker 5 No. 315 70 1,575 4.3 Earthing Tag Marker as per Electrical Inspectorate requirement 103 No. 315 70 32,445

- - - 5 Saftey Equipmnt - - -

- - - 5.1 Antiskid black rubber mat of approved make,12 mm thick - - -

900mm wide x 1800mm Long chequered type as per IS-5424 in - - - following voltage grade(Jyothi Make) - - -

- - - 5.1.1 415 V voltage grade 60 Mtr. 930 35 55,800 5.1.2 33 kV voltage grade 5 Mtr. 2,500 35 12,500 5.1.2 11 kV voltage grade 30 Mtr. 1,800 35 54,000

- - - 6 First Aid box with all the standard contents. 3 No. 1,000 35 3,000

- - - 7 First aid chart made of cloth for electricall shock treatment - - -

printed in English ,& Hindi duly framed with front glasses. 3 No. 189 35 567 - - -

8 Pair of rubber gloves and gumboots - - - 8.1 33 kV grade 1 No. 600 - 600 8.2 11 kV grade 3 No. 600 - 1,800

- - - 9 Metallic danger boards. - - - i 33 kV 2 No. 175 35 350 i 11 kV 3 No. 175 35 525 ii 415 V 3 No. 175 35 525

- - - 10 Portable 5 kg. dry type fire extinguisher suitable for electrical - - -

fire and as recommended by the tariff advisory committee. 1 No. 6,400 210 6,400 - - -

11 - - -

- - - i Single line diagram 3 No. 750 105 2,250

- - - ii Outdoor lighting and cable layout 2 No. 750 105 1,500

- - - 12 Supply and installation of RCC hume pipe as under - - -

- - -

12.1 15 RMT 567 70 8,505

- - -

Supply and fixing of the following charts / drawings duly framed with front glass

300 mm dia Half Round Pipe( For Incoming HT cable from Overhead Line to Metering Room)

Page 28: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 28

Sr.No ITEMS DESCRIPTION Qty Unit Unit Rate: Rs Amount ( Rs )

Supply Installation Supply 12.2 150mm dia UR RMT 235 56

- - 12.3 300mm dia UR RMT 480 70

- - 13 4 way Flame proof Junction box suitable for - -

installation in hazardous area with IP 65 Protection as per - - IS 12063/1897 & Gas group IIA & IIB & 1 No.earth - - terminal inside & 2 terminal outside duly painted with two - - coats of red oxide and two coats of aluminium paint - - and to receive 4 Nos. 3 x 2.5 sq.mm YWYcables - - complete with Elmex terminals. UR No 2,520 2,100

- - 14 Flame proof Rotary Switches suitable for installation - -

in hazardous area with IP 65 Protection as per - - IS 12063/1987 & Gas group IIA & IIB & 1 No.earth - - terminal inside & 2 terminal outside & to receive 3 Nos. - - 3 x 2.5 sq.mm YWY cables UR No 3,150 2,100

- - TOTAL OF SECTION K- MISC. - - 567,917

- - L SECTION- L-CIVIL WORKS - -

- - 1 Excavation & Back filling of cable trenches in following soil conditions - -

- - 1.1 Soft soil 650 Cum - 350 - 1.2 Murum 485 Cum - 715 - 1.3 Hard Rock 485 Cum - 1,750 -

- - - 2 Supply and laying of sand for cables. 325 CU.Mtr 2,700 700 877,500

- - - 3 Supply and laying of burnt bricks for cables as per standard practice 14500 Nos 9 2 130,500

- - - 4 Supply and Spreading of gravel 40mm size, 100 mm 15 Cu Mtr 3,500 300 52,500

thick with duly levelling of Transformer pit - - - - -

TOTAL OF SECTION L- CIVIL WORKS 1,060,500

Page 29: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 29

Synefra revised estimate after addendum

Amount ( Rs ) Installation

12,000

596,640 - -

-

- - 8,400

79,800 - - 2,100 - -

-

3,500

-

7,500

-

2,100

-

3,150

-

- 715,190

Page 30: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 30

Amount ( Rs ) Installation

35,000

-

-

-

- - -

-

-

-

- - - - - -

-

- -

-

- - - - - - - - - - - - - - - - - - - - - - -

-

-

-

- - -

-

-

-

-

-

Page 31: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 31

Amount ( Rs ) Installation - - - - - - - - - - - - - - - -

-

- - -

-

- - - - - - - - -

-

- - - - - - - - - - -

-

- - -

49,000

-

-

-

-

- - -

-

- - - - - - -

Page 32: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 32

Amount ( Rs ) Installation -

-

- -

-

- - - - - - - - - - - - - - - - - - - - - -

-

-

-

- - -

-

-

-

-

-

- - - - - - - - - - - - - - - -

-

- - -

-

- - - - -

Page 33: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 33

Amount ( Rs ) Installation - - - -

-

- - - - - - - - - - - -

-

-

-

-

-

- - - - - - -

-

- - - - - - - - - - - - -

-

- - -

-

- - - - - - -

-

-

-

-

-

Page 34: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 34

Amount ( Rs ) Installation -

-

- - - - - - - - - - - - - - -

-

-

-

-

-

- - 49,000 -

-

-

-

-

-

- - -

-

- - - - - -

-

- -

-

- - - - - - - - - - -

Page 35: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 35

Amount ( Rs ) Installation - - - - -

-

-

-

- - -

-

-

-

- - - - - - - - - - - - - - - -

-

- - -

-

- - - - - - - - -

-

- - - - - - - - - -

-

-

-

-

-

-

Page 36: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 36

Amount ( Rs ) Installation

-

- - - - - - -

-

- - - - - - - - - -

-

- - - - - - - - - - - - - - - -

-

- - -

-

- - - - - - -

-

-

-

-

-

-

-

- - - - - - - - - -

Page 37: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 37

Amount ( Rs ) Installation - - -

49,000

-

-

-

-

- - -

63,000

-

-

-

-

- -

-

-

10,500

-

21,000

- - -

77,000

-

105,000

- - - - - - - -

Page 38: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 38

Amount ( Rs ) Installation

-

- 45,000 - - - - - -

4,900

-

75,600

- -

-

- - - 87,500 - 29,400 - 14,700 -

- -

-

-

-

500,000

21,000

14,000

12,600

16,800

16,800

16,800 6,300 - 8,400 8,400

Page 39: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 39

Amount ( Rs ) Installation

-

924,000

33,600

35,000

6,720

6,720

16,800 52,500 1,400 -

-

924,000

33,600

35,000

6,720

6,720

16,800 52,500 1,400 -

-

2,800 2,240

-

280

2,800

1,680

840

1,050

5,600

-

Page 40: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 40

Amount ( Rs ) Installation -

-

- - -

-

- 15,000 - - -

-

- 6,500 - - -

-

- 3,500

-

- -

-

2,000 - - 1,500

-

- - - 1,500

-

- - - - -

-

2,000 - - -

-

1,000 - - 2,500

-

- - -

-

- 35,000 - -

-

Page 41: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 41

Amount ( Rs ) Installation - 25,000 -

-

-

- 7,000

-

-

-

- 4,500 - -

-

- 4,000 - -

-

- 4,500 - -

-

- 3,500 - - -

-

- 1,500 - -

-

- 1,500 - - -

-

- 4,000 - -

-

- 8,000 -

-

-

- 3,000 -

-

-

- 1,800 - 750

-

Page 42: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 42

Amount ( Rs ) Installation - - - - -

-

-

-

35,000

- - -

-

-

14,000

- -

-

5,040 30,240 21,840

3,753,140

48,000 800,000 110,000 112,000 144,000 21,000 70,000 78,000 81,000

Page 43: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 43

Amount ( Rs ) Installation 62,500 - 45,000 -

- 35,000 465,000 13,500 18,000 45,000 75,000 5,000

8,750 10,000

- - - -

-

- 12,600 9,600 4,200 5,000 1,500 400 1,600 3,960 2,880 1,680 480 2,100 5,520

200,000 2,400 33,000 1,800 2,400 4,200 2,400 800

3,000 3,600

-

-

2,551,870

10,000

Page 44: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 44

Amount ( Rs ) Installation - - - 280,000 - - - 12,000 - - - 4,200 - - -

- -

-

168,000 42,000 84,000 63,000 -

-

-

5,250

-

180,000

-

700

849,150

441000

157500

6300

10503500

1600

20000

8000

42000

0

Page 45: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 45

Amount ( Rs ) Installation

37800

0

46200

0

168000

000

0

0000

52500

0000

0

0

00

0

0

0

0

0

000

0

0

0

Page 46: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 46

Amount ( Rs ) Installation

0

0

0

0

0

7000

992,450

60,000

-

20,000

-

-

- 137,500 70,000 -

125,000

- - - -

-

16,800 12,600 10,500

12,600

12,600 - -

12,000

-

Page 47: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 47

Amount ( Rs ) Installation

-

10,000 - - - - 499,600

14,000

-

306,250

-

- -

73,920

-

3,920

-

-

-

2,100

-

-

-

-

-

1,960

-

Page 48: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 48

Amount ( Rs ) Installation

- -

-

-

-

- - -

10,500

-

-

-

28,000

-

-

440,650

1,750 4,000 4,500 -

-

3,750 3,500 4,000 -

-

-

Page 49: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 49

Amount ( Rs ) Installation - - - -

-

-

-

- -

-

- - - -

-

- - - -

-

-

- - - -

-

-

Page 50: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 50

Amount ( Rs ) Installation

- - -

- -

Page 51: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 51

Amount ( Rs ) Installation -

21,500

30,000

- - - - -

14,400

-

-

-

- -

5,400

-

-

-

- -

12,000

-

-

-

- - 3,000 - - - - - 1,500 - - - - - 500 - - - 2,600 - - - - - -

Page 52: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 52

Amount ( Rs ) Installation

-

- -

35,000

-

13,720

-

2,520

-

-

1,875 2,250 3,000 - - 127,765

457,500 2,100 1,400 - - - -

300,000

-

Page 53: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 53

Amount ( Rs ) Installation

-

-

-

- - -

-

-

761,000

Page 54: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 54

Amount ( Rs ) Installation

41,650 - - - - - - 1,000 - -

- - 1,050 350 7,210 - - - - - - - 2,100 175 1,050 - 105 - - 105 - - - - - - 70 105 105 - - 210 -

-

- 315 - 210 - - -

1,050

-

Page 55: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE India Industrial Ltd, Pune Electrical Works BOQ as on 030113

C.R.Narayana Rao LLP,Architects & Engineers 55

Amount ( Rs ) Installation

56,860

227,500 346,775 848,750 - 227,500 - 29,000 - 4,500 -

1,684,025

Page 56: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges Remark

A. SECTION A-HT. SECTION(CABLES & TERMINATION)

HT Cables

1

1.1 3Cx300 Sq.mm 33kV XLPE-UE- Cable 100 Mtr. 1723.8 10% 172 1,896 120 Offer from Polycab attched1.2 3Cx300 Sq.mm 11kV XLPE -UE-Cable UR Mtr. 1185.41 10% 119 1,304 120

1.3 3Cx240 Sq.mm 11kV XLPE -UE-Cable 4972 Mtr. 1028.024 10% 103 1,131 120 Note: No straight through joints will be allowded for any single length of cables.

2

2.1 Indoor type2.1.1 3Cx300Sq.mm 33kV XLPE-UE- Cable 4 No. 17140 10% 1,714 18,854 2,100

Offer from Rhychem attched

2.1.2 3Cx300 Sq.mm 11kV XLPE -UE-Cable UR No. 8020 10% 802 8,822 2,100 2.1.3 3Cx240 Sq.mm 11kV XLPE -UE-Cable 38 No. 7040 10% 704 7,744 2,100

2.2 Outdoor type2.2.1 3Cx240 Sq.mm 33kV XLPE-UE- Cable 1 No. 25000 10% 2,500 27,500 2,100

2.3 Straight Through Joint 2.3.1 3Cx300 Sq.mm 11kV XLPE -UE-Cable UR No2.3.2 3Cx240 Sq.mm 11kV XLPE -UE-Cable UR No

3 1 Set 83,160 - 83,160 3,500

Offer from subcontractor attached

-

4 1 No 343,741 - 343,741 7,500

-

5 1 No 44,100 - 44,100 2,100

-

6 15 Mtr 1,575 - 1,575 210

7 UR Mtr

TOTAL OF SECTION A- HT SECTION

B SECTION -B-HT/LT SUB-STATION EQUIPMENT

1

1.1 HT Panel Designation:33k.V.Main HT Panel at point of supply:

a 1 Set 9,900,000 5% 495,000 10,395,000 35,000 CAPEX ITEM-Offer from GE attached

a.1

a.2

a.3 30k.V. ,10k.A.Class-III Zno Surger Arrestor

a.4

a.4.1 Core 1: 15VA burden for Differential Protection(86) protection ( Class PS)

a.4.2 Core 2:15VA burden of metering ( accuracy class 1.0)

a.4.3 Core 3: 30VA burden for OC/EF protection ( Class 5P-20)

a.5

Quoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

Supply, taking delivery ,unloading at site,Installation,testing & commissioning of HT XLPE insulated, UE grade, cables, as per IS 7098 , burried in ground such as excavation up to 1 meter depth , backfilling, sand and brick protection and cable tray / tray supports are measured separately and Miscellaneous items such as saddles, 3 mm thick aluminum clamps, cleats, cable tags/ cable markers etc. are included in the scope.(The testing shall including HI-POT test at site before commissioning of the system & Test voltage shall be as per IS 7098)

CABLE TERMINATIONS :

Supply,installation,testing & commisioning of Heat shrikable type cable termination kit with long head Crimping type Lugs, for following XLPE insulated, (UE) grade cable including necessary Right angle /straight insulating boots. The scope also includes thermography test of all terminations at loads by using Themo graphic meter.

Supply, Installation, Testing and commissioning 33kV Distribution Class Lightening Arrestors with cross arm (1 Set of 3 Nos)

Supply installation testing and commissioning of 33kV CT& PT Metering kiosk including approval ,testing from MSEDCL .Detailes of CT & PT shall be as per MSEDCL load sanctionapproval.(Without T.O.D. meter)

Supply & installation H.T. Static Three Vector T. O. D. Meter as per MSEDCL.The scope also including calibration & testing of meter from MSEDCL

G. I. Pipe-CL -B- 150mm dia.for supporting of HT Cables connected to Overhead Lines ,road crossing etc for MSEDCL incoming cable.

HD PVC Pipe 150mm dia.for supporting of HT Cables connected to Overhead Lines ,road crossing etc for MSEDCL incoming cable.

Supply, assembly, factory test, loading,Taking delivery at site storing at site & supervision at site of HT panel board indoor type free standing,in various shipping section, Form 4b in construction, IP4X , fabricated out of 3 mm CRCA Sheet etc & as per specifications. Each panel shall comprising as per followings & Enlcosed ELECTRICAL SLD along with Tender Technical Specifciations.The panel shall be suitable for top cable entries for Incoming and outgoing cables except 33 k.V. HT Panels which shall be from bottom.

33-KV-Indoor free Vacuum circuit breaker panels with 1250 Amp Aluminum busbar ,26.2 k.A.-1 Second ,EDO Type for Transformer Feeder with over currents & Auxiliary Protection of Oil Cooled transformer and as per enclosed electrical SLD Ref GE-P-FAC-Ele00-01-011-155000-R5- Sh No 1 of 03 & as per followings requirements.

One (1) No. 33 KV,1250 A VCB/26.2 KA rupturing capacity at 33 kV rated metal clad, floor mounting, horizontal isolation horizontal drawout type complete with the followings.

Manually & motor operated (230V AC), spring charged trip free type, VCB incorporating mechanical as well as electrical ON/OFF indication, spring charge/discharge mechanical indication"OFF" push button test/service position limit switches with 4NO/4NC breaker auxilary contacts in service position.

Cast Resin CT with double wound,100- 225/1+1+1 with metering and protection core.

Voltage transformer with each , 3 limbs connected in star, dual class , 33kV/√3/110V/√3 with drawable type with automatic shutters 100 VA burden with HRC fuses for primary & secondary .( Confirming related IS specs.)

Page 57: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

a.6 Protectives Relays as under

a.6.1

a.6.1 Stand by Earth Fault relay (51G)

a.6.1 Restricated Fault relay (64R)

a.6.1 Transformer Auxiliary Protection Relays (63Tx)

a.6.1 Trip circuit supervision relay (95).

a.6.1 Antipumping relay

a.6.1 Lockout relay (86)

a.6.1 Under /Over Frequency Relay(81)

a.6.1 Under /OverVoltgae Relay(27/59)

a.6.1 Reverse Power relay (32)

a.6.1 Breaker Failure Relay (52BF)

a.7 Control & wiring terminals

a.7.1

a.7.2

a.8 Meterings as under

a.8.1

a.8.2

a.8.3

Line & Phase VoltageLine CurrentFrequencyM.D. KVA MeterKW,KVAKWHKVAHRKVAHp.f. TDH

a.9 Other Accessories as under & as per technical specifications

a.9.1

a.9.2

a.9.3 Danger plate (As per specification)

a.9.4

a.9.5 Three pin socket + switch.

a.9.6 Anticondensation space heater / thermostat

a.9.7 16 Window Announciator for Transforemr Faults

a.9.8 Hooter with Accept & Reset Push Button

a.10

a.10.1 Potenial free (DI)contact of VCB -ON -Statusa.10.2 Potenial free (DI)contact of VCB -OFF -Statusa.10.3 Potenial free (DI) contact of VCB -Trip On Fault- Statusa.10.4 VCB in TEST position (DI) Statusa.10.5 VCB in Serive position (DI) Statusa.10.6 ON Command to VCB(DO)a.10.7 OFF Command to VCB(DO)a.10.8 RS 485 (AI) of Mutifunction meters a.10.9 RS 485 (AI) of Numerical Relays

1.2 HT Panel Designation: 11k.V.Main HT Panel at MRS

1 Set 9,090,000 5% 454,500 9,544,500 49,000 CAPEX ITEM-Offer from GE attached

a EACH INCOMERS

Over current 50,50N Insutantaneaus short circuit 51,51N & one earth fault element with numerical IDMT relay with shunt trip on 110volts DC, consisting 3 element over current relay with setting from 50 to 200% (step of 25%) and earth fault with setting from 20 to 80% (step of 10%) .

All control wiring necessary for the above including interconnections. The size of the conductor should not be less than 1.5sqmm, PVC insulated, copper wire where required.

Test terminal block fuses, circuit lables , phase indication lamps etc. as per Electrical SLD

Voltmeter range 0-33KV with necessary voltmeter selector switch & suitable for 110V AC 96x96sqmm dial with shrouded terminal & protection fuses.

Ammeter range (0-100-225A) with necessary ammeter selector switch dual graduated scale, 96x96 sqmm dial with shrouded terminal .

Multifunction Digital meter with RS 485 Serial Communication Port for following parameters.

Necessary DC supply healthy LED type indication lamp & switch.

Control : T-N-C ( Trip , Neutral & Close) breaker control switch with indicating arrangement.

Set of Indication circuit breaker ON/OFF/Trip on Fault / Spring charged/Trip circuit healthy/Test/Service positions etc.

Followings wirings duly brought out to terminal block for BMS/SCADA interface by using twisted pair shielded wires in side the HT. Panels

NOTE: Above VCB Panel shall be suitable for expandable type for future suit to One incomers & two outgoings feeders.

11-KV-Indoor Vacuum circuit breaker panels with 1250 Amp, Aluminum busbar 26.2 k.A.-1 Second , EDO Type with over currents ,earth fault Protections. The complete panel shall be as per enclosed electrical SLD Ref GE-P-FAC-Ele00-01-011-155000-R5- Sh No 1 of 03 with Tender Technical specifications & as per followings requirements.

Page 58: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

a.1

a.2

a.3 9k.V. ,10k.A.Class-III Zno Surger Arrestor

a.4

a.4.1 Core 1: 15VA burden for Differential (87) protection ( Class PS)

a.4.2 Core 2:15VA burden of metering ( accuracy class 1.0)

a.4.3 Core 3: 30VA burden for OC/EF protection ( Class 5P-20)

a.5

a.6 Protectives Relays as under

a.6.1

a.6.2 Stand by Earth Fault relay (51G)

a.6.3 Restricated Fault relay (64R)

a.6.4 Differential Protection relay (87R)

a.6.5 Trip circuit supervision relay (95).

a.6.6 Antipumping relay

a.6.7 Lockout relay (86)

a.6.8 Under /OverVoltgae Relay(27/59)

a.6.9 Reverse Power relay (32)

a.6.10 Breaker Failure Relay (52BF)

a.6.11 Master lock out relay (86)

a.7 Control Wiring & Terminal

a.7.1

a.7.2

a.8 Meterings

a.8.1

a.8.2

a.8.3

Line & Phase VoltageLine CurrentFrequencyM.D. KVA MeterKW,KVAKWHKVAHRKVAHp.f. TDH

a.9 Other Accessories as under & as per technical specifications

a.9.1

a.9.2

a.9.3 Danger plate (As per specification)

a.9.4

a.9.5 Three pin socket + switch.

a.9.6 Anticondensation space heater / thermostat

a.9.7 8 Window Announciator for Faults

a.9.8 Hooter with Accept & Reset Push Button

2 Sets of 11 KV,1250 A VCB/26.2 KA rupturing capacity at 11 kV rated metal clad, floor mounting, horizontal isolation horizontal drawout type complete with the followings.

Manually & motor operated (230V AC), spring charged trip free type, VCB incorporating mechanical as well as electrical ON/OFF indication, spring charge/discharge mechanical indication"OFF" push button test/service position limit switches with 4NO/4NC breaker auxilary contacts in service position.

Cast Resin CT with double wound, 350-800Amp/1+1+1 with metering and protection core.

Voltage transformer with each , 3 limbs connected in star, dual class , 11kV/√3/110V/√3 with drawable type with automatic shutters 100 VA burden with HRC fuses for primary & secondary .( Confirming related IS specs.)

Over current 50,50N Insutantaneaus short circuit 51,51N & one earth fault element with numerical IDMT relay with shunt trip on 110volts DC, consisting 3 element over current relay with setting from 50 to 200% (step of 25%) and earth fault with setting from 20 to 80% (step of 10%) .

All control wiring necessary for the above including interconnections. The size of the conductor should not be less than 1.5sqmm, PVC insulated, copper wire where required.

Test terminal block fuses, circuit lables , phase indication lamps etc. as per Electrical SLD

Voltmeter range 0-12KV with necessary voltmeter selector switch & suitable for 110V AC 96x96sqmm dial with shrouded terminal & protection fuses.

Ammeter range (0-350-800A) with necessary ammeter selector switch dual graduated scale, 96x96 sqmm dial with shrouded terminal .

Mutifunction Digital meter with RS485 Serial Communication Port for following parameters

Necessary DC supply healthy LED type indication lamp & switch.

Control : T-N-C ( Trip , Neutral & Close) breaker control switch with indicating arrangement.

Set of Indication for circuit breaker ON/OFF/Trip on Fault / Spring charged/Trip circuit healthy/Test/Service positions etc.

Page 59: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

a.10

a.10.1 Potenial free (DI)contact of VCB -ON -Statusa.10.2 Potenial free (DI)contact of VCB -OFF -Statusa.10.3 Potenial free (DI) contact of VCB -Trip On Fault- Statusa.10.4 VCB in TEST position (DI) Statusa.10.5 VCB in Serive position (DI) Statusa.10.6 ON Command to VCB(DO)a.10.7 OFF Command to VCB(DO)a.10.8 RS 485 (AI) of Mutifunction meters a.10.9 RS 485 (AI) of Numerical Relays

b Outgoings VCBs

b.1

b.2

b.3

15VA burden for protection ( Class 5P-20)

15VA burden of metering ( accuracy class 1.0)

b.4 Protection to each outgoings

Trip circuit supervision relay (95).

Lockout relay (86)

Antipumping relay

b.5 Other Accessories as under & as per technical specifications

Danger plate (As per specification)

Three pin socket + switch.

Anticondensation space heater / thermostat

50x6mm, copper earth bus shall be provided for the full length of panel.

b.6

Potenial free (DI)contact of VCB -ON -StatusPotenial free (DI)contact of VCB -OFF -StatusPotenial free (DI) contact of VCB -Trip On Fault- StatusVCB in TEST position (DI) StatusVCB in Serive position (DI) StatusON Command to VCB(DO)OFF Command to VCB(DO)RS 485 (AI) of Numerical Relays

c BUS COUPLERS: 2Nos Bus couplers VCB Panel comprising as underc.1 As per above Outgoing VCB Breaker panels except No CT for metering

& no meters.

d

NOTE: 1: Above Panel shall be suitable for Expandable type from both Side

Followings wirings duly brought out to terminal block for BMS/SCADA interface by using twisted pair shielded wires in side the HT. Panels

Five (5) Nos. 11 KV, 1250 A VCB/ 26.2 KA rupturing capacity at 11kV rated metal clad, floor mounting, horizontal isolation horizontal drawout type complete with the following:

Manually & motor operated (230V AC), spring charged trip free type, VCB incorporating mechanical as well as electrical ON/OFF indication, spring charge/discharge mechanical indication"OFF" push button test/service position limit switches with 4NO/4NC breaker auxilary contacts in service position.

Cast Resin CT with double wound, with metering and protection core. CT.Ratio as indciated on Electrical SLD for each outgoing VCB in MRS room panel

Over current 50,50N Insutantaneaus short circuit 51,51N & one earth fault element with numerical IDMT relay with shunt trip on 110volts DC, consisting 3 element over current relay with setting from 50 to 200% (step of 25%) and earth fault with setting from 20 to 80% (step of 10%) .

Necessary DC supply healthy LED type indication lamp & switch.

Control : T-N-C ( Trip , Neutral & Close) breaker control switch with indicating arrangement.

Set of Indication for circuit breaker ON/OFF/Trip on Fault / Spring charged/Trip circuit healthy/Test/Service positions etc.

Terminal boxes with single gland trifucating cable box suitable for 11KV aluminium XLPE cable of size 3C x 300sqmm for incoming & outgoing &Suitable for TOP CABLE ENTRY

All control wiring necessary for the above including interconnections. The size of the conductor should not be less than 1.5sqmm, PVC insulated, copper wire where required.

Test terminal block fuses, circuit lables , phase indication lamps etc. as per standard practice.

Followings wirings duly brought out to terminal block for BMS/SCADA interface by using twisted pair shielded wires in side the HT. Panels

3 Nos Bus PT Section: 3Nos Withdrawable type BUS PT section as shown in Tender Electrical SLD Ref GE-P-FAC-Ele00-01-011-155000-R5- Sh No 1 of 03

NOTE: 2: Control Voltgae Bus for D.C. & AC votlage shall be as per Electrica SLD ref.GE-P-FAC-Ele00-01-011-155000-R5- Sh No 1 of 03

NOTE: 3: Interlocks and control logics shall be suitable for 4 Incomers & 3Bus-Couplers as shown in above mentioned SLD

Page 60: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

1.3 HT Panel Designation :11kV HT Panel Office Load Centre-1 as 1 Set 2,565,000 5% 128,250 2,693,250 49,000 CAPEX ITEM-Offer from GE attached

a 2 NOS INCOMER FEEDER :EACH INCOMERS COMPRISING AS UNDER.

a.1

a.2

a.3 9k.V. ,10k.A.Class-III Zno Surger Arrestor

a.4

a.4.1 Core 1:15VA burden of metering ( accuracy class 1.0)

a.4.2 Core 2: 30VA burden for OC/EF protection ( Class 5P-20)

a.5

a.6 Protectives Relays as under to each Incomers

a.6.1

a.6.1 Trip circuit supervision relay (95).

a.6.2 Antipumping relay

a.6.3 Lockout relay (86)

a.6.4 Under /OverVoltgae Relay(27/59)

a.6.5 Reverse Power relay (32)

a.6.6 Breaker Failure Relay (52BF)

a.6.7 Master lock out relay (86)

a.7 Control Wiring & Terminal

a.7.1

a.7.2

a.8 Meterings to each Incomers

a.8.1

a.8.2

Line & Phase VoltageLine CurrentFrequencyM.D. KVA MeterKW,k.V.AKWHKVAHRKVAHp.f. TDH

a.9 Other Accessories as under & as per technical specifications

a.9.1

a.9.2

a.9.3 Danger plate (As per specification)

a.9.4

a.9.5 Three pin socket + switch.

a.9.6 Anticondensation space heater / thermostat

a.9.7 8 Window Announciator for Faults

11-KV-Indoor Vacuum circuit breaker panels with 1250 Amp,26.2 k.A.-1 Second , EDO Type with over currents ,earth fault Protections. The complete panel shall be as per enclosed electrical SLD Ref GE-P-FAC-Ele00-01-011-155000-R5- Sh No 1 of 03 with Tender Technical specifications & as per followings requirements.

11 KV,1250 A,Aluminum Busbar VCB/26.2 KA rupturing capacity at 11 kV rated metal clad, floor mounting, horizontal isolation horizontal drawout type complete with the followings.

Manually & motor operated (230V AC), spring charged trip free type, VCB incorporating mechanical as well as electrical ON/OFF indication, spring charge/discharge mechanical indication"OFF" push button test/service position limit switches with 4NO/4NC breaker auxilary contacts in service position.

Cast Resin CT with double wound, 250-Amp/1+1 with metering and protection core.

Voltage transformer with each , 3 limbs connected in star, dual class , 11kV/√3/110V/√3 with drawable type with automatic shutters 100 VA burden with HRC fuses for primary & secondary .( Confirming related IS specs.)

Over current 50,50N Insutantaneaus short circuit 51,51N & one earth fault element with numerical IDMT relay with shunt trip on 110volts DC, consisting 3 element over current relay with setting from 50 to 200% (step of 25%) and earth fault with setting from 20 to 80% (step of 10%) .

All control wiring necessary for the above including interconnections. The size of the conductor should not be less than 1.5sqmm, PVC insulated, copper wire where required.

Test terminal block fuses, circuit lables , phase indication lamps etc. as per Electrical SLD GE-P-FAC-Ele00-01-011-155000-R5- Sh No 1 of 03

Voltmeter range 0-12KV with necessary voltmeter selector switch & suitable for 110V AC 96x96sqmm dial with shrouded terminal & protection fuses.

Mutifunction Digital meter with RS485 Serial Communication Port for following parameters

Necessary DC supply healthy LED type indication lamp & switch.

Control : T-N-C ( Trip , Neutral & Close) breaker control switch with indicating arrangement.

Set of Indication for circuit breaker ON/OFF/Trip on Fault / Spring charged/Trip circuit healthy/Test/Service positions etc.

Page 61: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

a.9.8 Hooter with Accept & Reset Push Button

a.10

a.10.1 Potenial free (DI)contact of VCB -ON -Statusa.10.2 Potenial free (DI)contact of VCB -OFF -Statusa.10.3 Potenial free (DI) contact of VCB -Trip On Fault- Statusa.10.4 VCB in TEST position (DI) Statusa.10.5 VCB in Serive position (DI) Statusa.10.6 ON Command to VCB(DO)a.10.7 OFF Command to VCB(DO)a.10.8 RS 485 (AI) of Mutifunction meters a.10.9 RS 485 (AI) of Numerical Relays

b Outgoings VCBs

b.1

b.2

b.3

15VA burden for protection ( Class 5P-20)

15VA burden of metering ( accuracy class 1.0)

b.4 Protection to each outgoings

Trip circuit supervision relay (95).

Lockout relay (86)

Antipumping relay

b.5 Metering :

Line & Phase VoltageLine CurrentFrequencyM.D. KVA MeterKWHKWHKVAHRKVAHp.f. TDH

b.6 Other Accessories as under & as per technical specifications

Danger plate (As per specification)

Three pin socket + switch.

Anticondensation space heater / thermostat

50x6mm, copper earth bus shall be provided for the full length of panel.

b.7

Potenial free (DI)contact of VCB -ON -StatusPotenial free (DI)contact of VCB -OFF -StatusPotenial free (DI) contact of VCB -Trip On Fault- StatusVCB in TEST position (DI) StatusVCB in Serive position (DI) StatusON Command to VCB(DO)

Followings wirings duly brought out to terminal block for BMS/SCADA interface by using twisted pair shielded wires in side the HT. Panels

Note: E& M Interlocaks shall be provided as indicted on Tender Electrical SLD for both Incomers

One (1) Nos. 11 KV, 1250 A VCB/ 26.2 KA rupturing capacity at 11kV rated metal clad, floor mounting, horizontal isolation horizontal drawout type complete with the following:

Manually & motor operated (230V AC), spring charged trip free type, VCB incorporating mechanical as well as electrical ON/OFF indication, spring charge/discharge mechanical indication"OFF" push button test/service position limit switches with 4NO/4NC breaker auxilary contacts in service position.

Cast Resin CT with double wound, with metering and protection core. CT.Ratio as indciated on Electrical SLD for each outgoing VCB in MRS room panel

Over current 50,50N Insutantaneaus short circuit 51,51N & one earth fault element with numerical IDMT relay with shunt trip on 110volts DC, consisting 3 element over current relay with setting from 50 to 200% (step of 25%) and earth fault with setting from 20 to 80% (step of 10%) .

Mutifunction Digital meter with RS485 Serial Communication Port for following parameters

Necessary DC supply healthy LED type indication lamp & switch.

Control : T-N-C ( Trip , Neutral & Close) breaker control switch with indicating arrangement.

Set of Indication for circuit breaker ON/OFF/Trip on Fault / Spring charged/Trip circuit healthy/Test/Service positions etc.

Terminal boxes with single gland trifucating cable box suitable for 11KV aluminium XLPE (E) cable of size 3C x 300sqmm for incoming & outgoing &Suitable for TOP CABLE ENTRY

All control wiring necessary for the above including interconnections. The size of the conductor should not be less than 1.5sqmm, FRLS insulated, copper wire where required.

Test terminal block fuses, circuit lables , phase indication lamps etc. as per standard practice.

Followings wirings duly brought out to terminal block for BMS/SCADA interface by using twisted pair shielded wires in side the HT. Panels

Page 62: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

OFF Command to VCB(DO)RS 485 (AI) of Mutifunction meters RS 485 (AI) of Numerical Relays

NOTE: 11K.V. HT Panel shall be Expandable from both side

1.4 1 Set 2,565,000 5% 128,250 2,693,250 49,000 CAPEX ITEM-Offer from GE attached

a

b

NOTE: 11K.V. HT Panel shall be Expandable from both side

1.5 1 Set 3,845,000 5% 192,250 4,037,250 63,000 CAPEX ITEM-Offer from GE attached

a

b

NOTE: 11K.V. HT Panel shall be Expandable from both side

2 Battery Charger

2.1 1 Set 334,900 5% 16,745 351,645 10,500 CAPEX ITEM-Offer from GE attached

2.2 3 Set 208,800 5% 10,440 219,240 7,000 CAPEX ITEM-Offer from GE attached

3 TRANSFORMERS

3.1 1 No 2,710,000 5% 135,500 2,845,500 77,000 CAPEX ITEM-Offer from GE attached

3.2 3 No 2,395,000 5% 119,750 2,514,750 35,000 CAPEX ITEM-Offer from GE attached

KVA Rating :2000KVA, %Z 6.25%Primary Volts : 11kV 50 HZSecondary Volts : 433 Volts 50 HZType of cooling : Air NaturalType of tap & Range: LINK : +5%,-7.5 % in the steps of 2.5 %IP Degree : 31

3.3

KVA Rating :250KVA, %Z 5% 3 No 375,000 - 375,000 15,000 CAPEX ITEM-Primary Volts : 415 Volts 50 HZSecondary Volts : 415Volts 50 HZType of cooling : Air NaturalType of tap & Range: LINK : +5%,.5 % in the steps of 2.5 %IP Degree : 31

3.3 1 No 12,034 - 12,034 4,900

Offer from subcontractor attached

3.4 9 Mtr 40,348 - 40,348 8,400

HT Panel Designation :11kV HT Panel at HEB Load Centre-2 as per tender Electrical SLD ref GE-P-FAC-Ele00-01-06-155000-R5: Sh1 of 3

Incomers: Complete Incomers section shall be as per above panel of Load cetner-1 & suitable for 2 Incomers

Outgings : Each outgoing feeders shall be as per above panel of Load cetner-1 & suitable for 1 Outgoing

HT Panel Designation :11kV HT Panel at LEB Load Centre-3 as per tender Electrical SLD ref GE-P-FAC-Ele00-01-06-155000-R5: Sh1 of 3

Incomers: Complete Incomers section shall be as per above panel of Load cetner-1 & suitable for 3 Incomers VCB panel

Outgings : Each outgoing feeders shall be as per above panel of Load cetner-1 & suitable for 1 Outgoings VCB feeders panel.

NOTE FOR ALL 11 KV HT PANEL: ALL 11k.V. HT PANELS SHALL BE SUITABLE TO TOP CABLE ENTRIES FOR INCOMING AND OUTGOINGS CABLES TERMINATIONS.

BATTERY CHARGER AT MRS: Supply, Installation ,Testing & commissioning of 110 Volts-350-AH-Battery with battery charger with full wave rectifire ,independent 3 Phase charger for Float & Boost at Main Reciving Station ( Input voltage 3 Phase 415 Volts) with wall mounted DCDB, Suitable for bottom cable entries for incoming and all outgoing cables The Configuration of DCDB shall be as under - Incomer : 1No 250 Amp ,DP MCCB ,35kA , Outgoing : 32Amp , DP MCB 10kA - 12Nos

BATTERY CHARGER AT EACH LOAD CENTERS :Supply, Installation ,Testing & commissioning of 110 Volts-100-AH-Battery with battery charger with full wave rectifire ,independent 3 Phase charger for Float & Boost ( Input voltage 3 Phase 415 Volts) with DCDB as under Incomer : 125 Amp ,DP MCB ,10kA -1 No Outgoing : 32Amp , DP MCB 10kA - 6Nos

Supply,Taking deliver at site storing at site, shifting from the place of storage to the place of installation, installation,with all fittings and accessories, testing and commissioning. Drying out and oil filteration till adequate values of insulation resistance of windings and break down value of oil are achieved is included in the scope. 5000 kVA, 33/11 kV with vector group of Dyn-11 with OLTC & RTCC.The transformer shall be as per latest IS 2026. The transformer shall be suitable for Outdoor installation as per tender specification /drawinhs & with HT & LT Cable box for indoor cable terminations & as per tender Data sheet. Refer Drawing no GE-P-SITE-ELE01-01-05-155008 for Location of Transformer installation. ( Note: Civil foundation will be provided by other)

Supply,Installation ,testing & commissioning of Open ventilated Dry type Transformer with Off circuit tap changing link to Primary Side,with Cable box for Incoming and Busduct for outgoing etc & as per latest I.S.11171: 1985 specification. Rating & details of Transformer is as under.The transformer shall be suitable for Indoor installation as per tender drawing reference GE-P-SITE-Ele00-01-08-155012 & tender data sheet.

LIGHTING TRANSFORMERS: Supply,Installation ,testing & commissioning of Dry type Transformer with Off circuit tap changing link to Primary Side,with Cable box for Incoming and Busduct for outgoing etc & as per latest I.S.11171: 1985 specification. The transformer shall be suitable for Indoor installation as per tender drawing reference GE-P-SITE-Ele00-01-08-155012 & tender data sheet.The rating of Transformer is as under

Supply & installation of Transformer yard gate made out of 40mm dia GI pipe 11/2" 8 SWG GI wire mesh and two leaves gate with clear width of 3000 mm.

Supply & installation 8 SWG GI wire 1 1/2" mesh chain link fencing of 1.8 Mtr. height with 50 x 50x 6 MS angle at every 2 M interval and 50 x 50 x6 Angle at top. The fencing should be painted with 2 coat of red oxide primer with Aluminium paint

Page 63: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

4 BUSDUCT

4.1

4.1.1 Straight Run 3200 Amp TPN, 50kA, AL Busduct Indoor 25 Mtr 38,176 5% 1,909 40,085 3,500

CAPEX ITEM-Offer from GE attached

- 4.1.2 Right Angle Bend 3200 Amp, 50kA 6 No 22,493 5% 1,125 23,618 4,900

- - 4.1.3 Bimetallic Flexible Transformer end connections (3-ph & Neutral) 3 Set 24,781 5% 1,239 26,020 4,900

- 4.1.4 Wall frame assembly with fire barrier UR No - 3,500

- -

4.3 -

-

4.3.1 -

a 500 Mtr 38,176 5% 1,909 40,085 1,000

CAPEX ITEM-Offer from GE attached

b Joint suitable for above busway 10 Nos 18,932 5% 947 19,879 2,100

c 4 Nos 23,601 5% 1,180 24,781 3,500

d 6 Nos 21,422 5% 1,071 22,493 2,100

e 8 Nos 22,044 5% 1,102 23,147 2,100

f 8 Nos 33,067 5% 1,653 34,720 2,100

g Provision of Edgewise cross with joint 8 Nos 33,787 5% 1,689 35,476 2,100

h Adaptor Box suitable for above busways 3 Nos 51,870 5% 2,593 54,463 2,100 i Reducers of following ratings - - j 3200A/800A 4 Nos 44,500 5% 2,225 46,725 2,100 k 3200A/630A 4 Nos 43,500 5% 2,175 45,675 2,100

4.3.2 -

a 440 Meter 12,169 5% 608 12,777 2,100

CAPEX ITEM-Offer from GE attached

b Joint suitable for above busway 20 Nos 5,752 5% 288 6,039 1,680

c 10 Nos 7,179 5% 359 7,537 3,500

d 4 Nos 6,513 5% 326 6,838 1,680

e 4 Nos 6,703 5% 335 7,038 1,680

f Adaptor Box 10 Nos 9,263 5% 463 9,726 1,680 g Spring hangers 150 Nos 4,023 5% 201 4,224 350 h End Cover 4 Nos 1,253 5% 63 1,315 350

-

4.3.3 -

a 440 Meter 10,704 5% 535 11,239 2,100

CAPEX ITEM-Offer from GE attached

b Joint suitable for above busway 20 Nos 5,117 5% 256 5,373 1,680

c 10 Nos 6,355 5% 318 6,673 3,500

d 4 Nos 5,777 5% 289 6,066 1,680

e 4 Nos 5,943 5% 297 6,240 1,680

f Adaptor Box 10 Nos 9,263 5% 463 9,726 1,680 g Spring hangers 150 Nos 3,882 5% 194 4,076 350

Supply ,Taking delivery at site, shifting from the place of storage to the place of installation between Transformer secondary to Main PCC ,unpacking, site assembly of loose accessories, installation testing and commissioning of the following LT.Busdcuts & its accessories including required support ,etc of following ratings.The required M.S. support for installation of busduct shall be measured under boq item no------------- of M.S .Steel items . The route/ location of busducts shall be as per tender drgawing no GE-P-SITE-Ele00-01-08-155012&GE-P-SITE-Ele00-01-08-155013.

3200A -TPN Busduct (Air Insulated type)

SECTION- M- OVER HEAD BUSTRUNKING SYSTEM (SANDWITCH TYPE)

3200Amp TPN -AL BUSWAY SYSTEM: 3Pole and 100% neutral (TPN) busduct, totally enclosed in extruded Aluminium enclosure, dust proof with IP54 ingress protection,compact sandwitch type low inductance busduct with Tin Plated Aluminium throug out the length of busbars rated as under to withstand the stresses of suitable symmetrical fault levle at 415 Volts with bends ,expansion joints. The bustrunking shall be as per IEC 60439-1&2 and designed for the temperature rise of 55 degree rise over ambient of 35 degree.Thermal stickers shall be provided at each joints for detection of temperature rise of 60/70/80 degree celcious. The testing scope also includes testing of all buseays joint by theremographic meter . The busways shall be installed as per Tender Drawing referenceGE-P-FAC-Ele01-01-18-154988. The required M.S. support for installation of busduct shall be measured under boq item of M.S .Steel items

3200 amp TPN Aluminium Feeder busway with 65KA short circuit with stand for 1 sec.

Provision of Flanged End with joint ( meterage will be counted in running meters)

Provision of 90deg. Bends with joint (Vertical) ( meterage will be counted in running meters)

Provision of 90deg. Bends with joint (Horizontal) ( meterage will be counted in running meters)

Provision of 'T' with joint (Horizontal) ( meterage will be counted in running meters)

800 Amp TPN -AL-RISING MAINS : 3Pole and 100% neutral (TPN) busduct, totally enclosed in extruded Aluminium enclosure, dust proof with IP54 ingress protection,compact sandwitch type low inductance busduct with Tin Plated Aluminium throug out the length of busbars rated as under to withstand the stresses of suitable symmetrical fault levle at 415 Volts with bends ,expansion joints. The bustrunking shall be as per IEC 60439-1&2 and designed for the temperature rise of 55 degree rise over ambient of 35 degree.Thermal stickers shall be provided at each joints for detection of temperature rise of 60/70/80 degree celcious.The rising mail shall be provided plug at 2 points in each length of 3 meter of busways( i.e. only 2 tapings)

800 amp TPN Aluminium Plug in busway with 30KA short circuit with stand for 1 sec.(2 plugs)

Provision of Flanged End with joint ( meterage will be counted in running meters)

Provision of 90deg. Bends with joint (Vertical) ( meterage will be counted in running meters)

Provision of 90deg. Bends with joint (Horizontal) ( meterage will be counted in running meters)

630 Amp TPN -AL-RISING MAINS : 3Pole and 100% neutral (TPN) busduct, totally enclosed in extruded Aluminium enclosure, dust proof with IP54 ingress protection,compact sandwitch type low inductance busduct with Tin Plated Aluminium throug out the length of busbars rated as under to withstand the stresses of suitable symmetrical fault levle at 415 Volts with bends ,expansion joints. The bustrunking shall be as per IEC 60439-1&2 and designed for the temperature rise of 55 degree rise over ambient of 35 degree.Thermal stickers shall be provided at each joints for detection of temperature rise of 60/70/80 degree celcious.The rising mail shall be provided plug at 4 points in each length of busways( i.e.2 Nos to each side of Busways)

630 amp TPN Aluminium Plug in busway with 30KA short circuit with stand for 1 sec.(2 plugs)

Provision of Flanged End with joint ( meterage will be counted in running meters)

Provision of 90deg. Bends with joint (Vertical) ( meterage will be counted in running meters)

Provision of 90deg. Bends with joint (Horizontal) ( meterage will be counted in running meters)

Page 64: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

h End Cover 4 Nos 1,200 5% 60 1,260 350

CAPEX ITEM-Offer from GE attached

-

4.3.4 -

a 800Amp 50 k.A. 4 No 360264 5% 18,013 378,277 700

CAPEX ITEM-Offer from GE attached

b 630Amp 50 k.A. 4 No 190453 5% 9,523 199,976 560

4.3.5

a UR No 30,658 5% 1,533 32,190 350

b 1 No 11,583 5% 579 12,162 280

c 10 No 11,583 5% 579 12,162 280

d 8 No 11,583 5% 579 12,162 210

e 4 No 11,583 5% 579 12,162 210

f 5 No 9,213 5% 461 9,674 210

g 40 No 9,213 5% 461 9,674 140

5 LT Switchgear

5.1 Panel Designation: PCC FOR LOAD CENTER-1

Approx.Overall dimension ( in mm ):8000 (L) x1500 (W) x 2375 (H)Location : Load Center-1 1 No. 2361249 5% 118,062 2,479,311 15,000 CAPEX ITEM-Offer from GE attached

5.2 Panel Designation: MLDB OFFICE & CAFETARIA BLDB

Approx.Overall dimension ( in mm ):3000 (L) x450 (W) x 2025 (H) Location : Load Center-1 1 No. 798411 5% 39,921 838,332 6,500 CAPEX ITEM-Offer from GE attached

- - - -

5.3 Panel Designation: 675kVAR APFC PANEL 1- ( Load Centre) - -

- -

Approx.Overall dimension ( in mm ): 4000 (L) x800 (W) x 2375 (H) - - Location : HT/LT Substation Room at Factory Load Centre-2 1 No. 926109 5% 46,305 972,414 3,500 CAPEX ITEM-Offer from GE attached

- -

- - 5.4 Panel Designation:PDB FOR CAFETARIA - -

- -

Approx.Overall dimension ( in mm ):2700 (L) x800 (W) x 2375 (H) 1 No. 537661 5% 26,883 564,544 2,000 CAPEX ITEM-Offer from GE attachedLocation : - -

- - 5.5 Panel Designation:PDB OFFICE -2A 1 No. 399411 5% 19,971 419,382 1,500 CAPEX ITEM-Offer from GE attached

- -

Approx.Overall dimension ( in mm ):2700 (L) x800 (W) x 2375 (H) - - Location : - -

- - 5.6 Panel Designation:PDB OFFICE -2B 1 No. 399411 5% 19,971 419,382 1,500 CAPEX ITEM-Offer from GE attached

- -

Approx.Overall dimension ( in mm ):2700 (L) x800 (W) x 2375 (H) - - Location : - -

- - - -

5.7 Panel Designation:PDB KITCHEN & BASEMENT VENTILATION PDB - -

- -

Approx.Overall dimension ( in mm ):3500 (L) x800 (W) x 2375 (H) 1 No. 413411 5% 20,671 434,082 2,000 CAPEX ITEM-Offer from GE attachedLocation : - -

- - 5.8 Panel Designation:LIFT PDB(-Office and cafetaria ) - -

- -

Approx.Overall dimension ( in mm ):3500 (L) x800 (W) x 2375 (H) 1 No. 320661 5% 16,033 336,694 1,000 CAPEX ITEM-Offer from GE attachedLocation : - -

- - 5.9 Panel Designation:UTILITY PUMP MCC 1 No. 619911 5% 30,996 650,907 2,500 CAPEX ITEM-Offer from GE attached

- -

Location : Chiller Room - - - -

Tap off boxes box: Supplying ,installing of 4Poles MCCB With LSG release , 3 CT Operated Dual KWH meter with RS 485 Serial communication Ports, rotary handle etc.of following ratings

Plug in box : Supplying, installing,testing and commissioning of TPN plug in box of of following capacity on above horizontal bus system complete with TPN MCCB 30KA, electrical interconnections, earthing etc as required.

Plug in type type box with rating 315Amp TPN MCCB-30KA Microprocessor LSG type with rotary handle on top of front of plug in box

Plug in type type box with rating 250Amp TPN MCCB-30KA Microprocessor LSG type with rotary handle on top of front of plug in box

Plug in type type box with rating 200Amp TPN MCCB-30KA Microprocessor LSG type with rotary handle on top of front of plug in box

Plug in type type box with rating 125Amp TPN MCCB-30KA Microprocessor LSG type with rotary handle on top of front of plug in box

Plug in type type box with rating 100 Amp TPN MCCB-30KA Microprocessor LSG type with rotary handle on top of front of plug in box

Plug in type type box with rating 63 Amp TPN MCCB-30KA Microprocessor LSG type with rotary handle on top of front of plug in box

Plug in type type box with rating 32 Amp TPN MCCB-30KA Microprocessor LSG type with rotary handle on top of front of plug in box

Supply, assembly, factory test, loading,Taking delivery at site storing at site & supervision at site of LT panel board as per IS 8623/1993, indoor type free standing,in various shipping section, Form 4b in construction, ALUMINIUM BUS BAR , IP54 , fabricated out of 3 mm CRCA Sheet etc & as per specifications. Each panel shall comprising as per followings & Enlcosed ELECTRICAL SLD along with Tender Technical Specifciations.(All panels shall be with TOP and exit of cables.)

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Note: The APFC Relay shall be intelligent microprocessor type with RS 485 serial communication port suitable for minimum 12 stages & 2 Sets of relays shall be considered in each APFC Panel

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 2 of 3 - R6 & Panel annexure-1

Page 65: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

5.10 Panel Designation :PCC For Load Centre-2(HEB) - -

- -

Approx.Overall dimension ( in mm ): 6500 (L) x1500 (W) x 2375 (H) - - Location : Load Centre-2 1 No. 3504100 5% 175,205 3,679,305 35,000 CAPEX ITEM-Offer from GE attached

- - 5.11 Panel Designation: PCC For Load Centre-3(LEB) - -

- -

Approx.Overall dimension ( in mm ): 6500 (L) x1500 (W) x 2375 (H) - - Location : Load Centre-2 1 No. 3191116 5% 159,556 3,350,672 25,000 CAPEX ITEM-Offer from GE attached

- -

5.12 Panel Designation:675kVAR-RT- APFC Panel at Factory Load Centre 2&3 - -

- -

Approx.Overall dimension ( in mm ): 4000 (L) x800 (W) x 2375 (H) - - Location : Load Centre-2&3 2 No. 1979581 5% 98,979 2,078,560 3,500 CAPEX ITEM-Offer from GE attached

- -

5.13 Panel Designation: MLDB-1 - for Factory Building (LEB) - -

- -

Approx.Overall dimension ( in mm ):1800 (L) x450 (W) x 2025 (H) - - Location : Load Centre-3 1 No. 471161 5% 23,558 494,719 4,500 CAPEX ITEM-Offer from GE attached

- - 5.14 Panel Designation: MLDB-2 - for Factory Building (HEB) - -

- -

Approx.Overall dimension ( in mm ):1800 (L) x450 (W) x 2025 (H) - - Location : Load Centre-2 1 No. 534161 5% 26,708 560,869 4,000 CAPEX ITEM-Offer from GE attached

- - 5.15 Panel Designation:HVAC &OTHER UTILITIES PDB -1 - -

- -

Approx.Overall dimension ( in mm ):4500 (L) x800 (W) x 2375 (H) - - Location : Load Centre-2 1 No. 1083635 5% 54,182 1,137,817 4,500 CAPEX ITEM-Offer from GE attached

- - 5.16 Panel Designation:HVAC &OTHER UTILITIES PDB -2 - -

- -

Approx.Overall dimension ( in mm ):4500 (L) x800 (W) x 2375 (H) - - Location : Load Centre-3 1 No. 777077 5% 38,854 815,931 3,500 CAPEX ITEM-Offer from GE attached

- - - -

5.17 Panel Designation: PDB -LOAD CENTER-2 - -

- -

Approx.Overall dimension ( in mm ):2700 (L) x800 (W) x 2375 (H) - - Location : Load Centre-3 1 No. 359161 5% 17,958 377,119 1,500 CAPEX ITEM-Offer from GE attached

- - 5.18 Panel Designation: PDB -LOAD CENTER -3 - -

- -

Approx.Overall dimension ( in mm ):2700 (L) x800 (W) x 2375 (H) - - Location : Load Centre3 1 No. 254161 5% 12,708 266,869 1,500 CAPEX ITEM-Offer from GE attached

- - - -

5.19 Panel Designation : -3 -Phase 32 Amp -SOCKET OUTLET PDB - -

- -

Approx.Overall dimension ( in mm ):2400 (L) x800 (W) x 2375 (H) - - Location : HEB & LEB FACTORY SHED 2 No. 215661 5% 10,783 226,444 2,000 CAPEX ITEM-Offer from GE attached

- - 5.20 Panel Designation : -1- Phase 20 Amp -SOCKET OUTLET PDB - -

- -

Approx.Overall dimension ( in mm ):2400 (L) x800 (W) x 2375 (H) - - Location : HEB & LEB FACTORY SHED 4 No. 203411 5% 10,171 213,582 2,000 CAPEX ITEM-Offer from GE attached

- -

5.21 - -

- -

Approx.Overall dimension ( in mm ):2500 (L) x800 (W) x 2375 (H) - - Location : Load Center-3 1 No. 161420 5% 8,071 169,491 3,000 CAPEX ITEM-Offer from GE attached

- -

5.22 - -

- -

Approx.Overall dimension ( in mm ):2500 (L) x800 (W) x 2375 (H) - - Location : Load Center-3 1 No. 416911 5% 20,846 437,757 1,800 CAPEX ITEM-Offer from GE attached

- - 5.23 1 No 411661 5% 20,583 432,244 750 CAPEX ITEM-Offer from GE attached

- -

Approx.Overall dimension ( in mm ):2500 (L) x800 (W) x 2375 (H) - - Location : MRS Building - -

- - 6 UPS SYSTEM : - -

- -

- -

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Note: The APFC Relay shall be intelligent microprocessor type with RS 485 serial communication port suitable for minimum 12 stages & 2 Sets of relays shall be considered in each APFC Panel

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155012 - R0 & Panel annexure-1

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155012 - R0 & Panel annexure-1

Panel Designation :UPS Input D.B. 2X60 k.V.A-FACTORY EMERGENCY LIGHTING

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155008 - R0 & Panel annexure-1

Panel Designation :UPS Output D.B. 2X60 k.V.A-FACTORY EMERGENCY LIGHTING

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155008 - R0 & Panel annexure-1

Panel Designation :A.C. D.B- -Utility Building(35k.A.)

Electrical SLD Ref.GE-P-FAC-Ele00-01-11-155000-Sh 3 of 3 - R6 & Panel annexure-1

Supply, Transprtation, storing at site, shifting at work place installation, testing and commissioning of following rating UPS with ,15 Min battery backup , with static & manual bypass Input Voltage: 3 Ph 415 Volts, ±10% Output : 3 -Phase-415Volts 4w 50 Hz ±2% , The scope also includes supply, Installation, Testing and Commissioning with flooded lead-acid batteries complete with intercell connectors & copper cables, battery stand made out of Powder Coated MS Angles with adequate supports to carry the load of the batteries & also TVSS at the input of each UPS to protect against transients, surges & Noise as per the tender specifications

Page 66: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

- -

6.1 UR Set 1247500 5% 62,375 1,309,875 21,000 CAPEX ITEM-Offer from GE attached

- -

6.2 2 Set 1180000 5% 59,000 1,239,000 17,500 CAPEX ITEM-Offer from GE attached

- - 6.3 10k.V.A. UPS for Server application (Independent application) 0 Set 575000 5% 28,750 603,750 8,400 CAPEX ITEM-Offer from GE attached

- -

- -

- -

6.4 2 Set 165000 5% 8,250 173,250 7,000 CAPEX ITEM-Offer from GE attached

7 TPN -ISOLATORS

Offer from subcontractor is attched

UR Nos 64,260 - 64,260 4,900 7.1 400Amps -TPN UR Nos 61,047 - 61,047 2,100 7.2 315Amps -TPN UR Nos 36,540 - 36,540 1,400 7.3 250Amps -TPN UR Nos 36,540 - 36,540 1,400 7.4 200mps -TPN UR Nos 23,940 - 23,940 1,120 7.5 125Amps -TPN UR Nos 13,860 - 13,860 980 7.6 100Amps -TPN 6 Nos 13,860 - 13,860 840 7.7 63Amps -TPN 36 Nos 13,860 - 13,860 840 7.8 UP TO 32Amps -TPN 26 Nos 13,860 - 13,860 840

TOTAL OF SECTION B-SUBSTATION EQUIPMENTS

C SECTION -C -CABLES AND CABLE TERMINATIONS1 LT CABLES

1.1

1.1.1 3.5.C x 400 Sq.mm. A2XFY(XLPE- AL-Armoured) 400 MTR 1,150 10% 115 1,265 120

Offer from Poly cab is attached

1.1.2 3.5.C x 300 Sq.mm. A2XFY(XLPE- AL-Armoured) 8000 MTR 802 10% 80 882 100 1.1.3 3.5.C x 240 Sq.mm. A2XFY(XLPE- AL-Armoured) 1100 MTR 659 10% 66 725 100 1.1.4 3.5.C x 185 Sq.mm. A2XFY(XLPE- AL-Armoured) 1400 MTR 520 10% 52 572 80 1.1.5 3.5.C x 150 Sq.mm. A2XFY(XLPE- AL-Armoured) 1800 MTR 428 10% 43 471 80 1.1.6 3.5.C x 120 Sq.mm. A2XFY(XLPE- AL-Armoured) 300 MTR 360 10% 36 396 70 1.1.7 3.5.C x 95 Sq.mm. A2XFY(XLPE- AL-Armoured) 1000 MTR 285 10% 29 314 70 1.1.8 3.5.C x 70 Sq.mm. A2XFY(XLPE- AL-Armoured) 1300 MTR 232 10% 23 255 60 1.1.9 3.5.C x 50 Sq.mm. A2XFY(XLPE- AL-Armoured) 1350 MTR 166 10% 17 183 60 1.1.10 3.5C x 35 Sq.mm. A2XFY(XLPE- AL-Armoured) 1250 MTR 128 10% 13 141 50 1.1.11 2C x 25 Sq.mm. A2XFY(XLPE- AL-Armoured) 300 MTR 105 10% 11 116 1.1.12 3.5C x 25 Sq.mm. A2XFY(XLPE- AL-Armoured) 900 MTR 105 10% 11 116 50 1.1.13 4C x 25 Sq.mm.A2XFY(XLPE- AL-Armoured) 3700 MTR 124 10% 12 136 1.1.14 3C x 50 Sq.mm. A2XFY(XLPE- AL-Armoured) UR MTR 146 10% 15 161 1.1.15 3C x 35 Sq.mm. A2XFY(XLPE- AL-Armoured) UR MTR 110 10% 11 121 1.1.16 3C x 25 Sq.mm. A2XFY(XLPE- AL-Armoured) UR MTR 90 10% 9 99 1.1.17 3CX10Sq.mm. XFY(XLPE -CU-Armoured) UR MTR 243 10% 24 267 1.1.18 3CX4Sq.mm. XFY(XLPE -CU-Armoured) UR MTR 10% - - 1.1.19 3CX2.5 Sq.mm. XFY(XLPE -CU-Armoured) 25000 MTR 78 10% 8 86 1.1.20 4CX16Sq.mm. A2XFY(XLPE- AL-Armoured) 1000 MTR 86 10% 9 95 35 1.1.21 4CX10Sq.mm. A2XFY(XLPE- AL-Armoured) 15500 MTR 80 10% 8 88 30 1.1.22 4CX10Sq.mm. XFY(XLPE -CU-Armoured) 450 MTR 316 10% 32 348 30 1.1.23 4CX6 Sq.mm.XFY(XLPE -CU-Armoured) 600 MTR 202 10% 20 222 30 1.1.24 4CX4Sq.mm. XFY(XLPE -CU-Armoured) 1800 MTR 146 10% 15 161 25 1.1.25 4CX2.5Sq.mm. XFY(XLPE -CU-Armoured) 3000 MTR 95 10% 10 105 25 1.1.26 4CX1.5Sq.mm. YWY(PVC -CU-Armoured) 200 MTR 70 10% 7 77 25 1.1.27 2CX10Sq.mm. XFY(XLPE -CU-Armoured) UR MTR 10% - - 1.1.28 2CX4Sq.mm. XFY(XLPE -CU-Armoured) UR MTR 10% - - 1.1.29 19CX1.5Sq.mm. YWY(PVC -Cu-Armoured) 125 MTR 360 10% 36 396 70 1.1.30 24CX1.5Sq.mm. YWY(PVC -Cu-Armoured) 125 MTR 363 10% 36 399 80 1.1.31 5CX2.5 Sq.mm. WY(PVC -CU-Un-Armoured Flexible ) UR MTR 10% - - 25

2 LT cable Terminations :

2.1 LT cable Termination :

2.1.1 3.5.C x 400 Sq.mm. A2XFY(XLPE- AL-Armoured) 36 No 2,977 - 2,977 350

Offer from subcontractor is atatched

2.1.2 3.5.C x 300 Sq.mm. A2XFY(XLPE- AL-Armoured) 32 No 2,643 - 2,643 300 2.1.3 3.5.C x 240 Sq.mm. A2XFY(XLPE- AL-Armoured) 14 No 2,570 - 2,570 300 2.1.4 3.5.C x 185 Sq.mm. A2XFY(XLPE- AL-Armoured) 20 No 1,658 - 1,658 250 2.1.5 3.5.C x 150 Sq.mm. A2XFY(XLPE- AL-Armoured) 6 No 1,649 - 1,649 250 2.1.6 3.5.C x 120 Sq.mm. A2XFY(XLPE- AL-Armoured) 2 No 1,114 - 1,114 200

80k.V.A. UPS(Factory Office W.S.) Application & suitable for Parallel operation with communication facilities.

60k.V.A. UPS Lighting Application & suitable for Parallel operation with communication facilities.

Note :Above UPS system shall be suitable for Parallel operation on Separate Power Distribution Boards.

Supply, Transprtation, storing at site, shifting at work place installation, testing and commissioning of 10 KVATrue- On Line sine wave invertor with ,30 Min battery backup , Input Voltage: 3 Ph 415 Volts, ±10% Output : 3 -Phase-415Volts 4w 50 Hz ±2% , The scope also includes supply, Installation, Testing and Commissioning with flooded lead-acid batteries complete with intercell connectors & copper cables, battery stand made out of Powder Coated MS Angles with adequate supports to carry the load of the batteries. (1No Dedicated invertor for MRS Internal Emergemcy Lighting & 1 No Dedicated for Emergency lighting of Basement of Load center-1 )

Supply, Transprtation, storing at site, shifting at work place installation, testing and commissioning of TPN 415 Volts Heavy duty Isolators of following rating, The complete assembly shall be with 2 mm thick CRCA metalic enclosure, Finished paints, IP 65 Degree of protection , Padlock arrangements & Suitable incoming & outgoings cables termination arrangements.

Supply,taking delivery at site, unloading at site,Installation,testing & commisioning of XLPE Insulated, PVC sheathed, armoured, 650/ 1100 V grade power and control cables to be laid in trenches, on cable trays, burried in ground. Civil work for cables to be laid burried in ground such as excavation, backfilling, sand and brick protection and cable tray /tray supports are measured separately and Miscellaneous items such as saddles, clamps, cleats, cable tags/ cable markers etc. are included in the scope

Supply & installation of Termination of XLPE insulated, PVC sheathed, 650/1100 V grade, armoured cable including stripping of cable insulation, supplying and fixing of Aluminum / tinned plated copper lugs and crimping the same to the conductor, supply and fixing of double compression cable glands including all 'labour supply and consumable material required for jointing / termination.

Page 67: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

2.1.7 3.5.C x 95 Sq.mm. A2XFY(XLPE- AL-Armoured) 8 No 940 - 940 200

Offer from subcontractor is atatched

2.1.8 3.5.C x 70 Sq.mm. A2XFY(XLPE- AL-Armoured) 22 No 835 - 835 180 2.1.9 3.5.C x 50 Sq.mm. A2XFY(XLPE- AL-Armoured) 16 No 679 - 679 180 2.1.10 3.5C x 35 Sq.mm. A2XFY(XLPE- AL-Armoured) 14 No 600 - 600 120 2.1.11 2C x 25 Sq.mm.A2XFY(XLPE- AL-Armoured) 4 No 395 - 395 120 2.1.12 3.5C x 25 Sq.mm. A2XFY(XLPE- AL-Armoured) 14 No 395 - 395 150 2.1.13 4C x 25 Sq.mm. A2XFY(XLPE- AL-Armoured) 46 No 401 - 401 120 2.1.14 3C x 50 Sq.mm. A2XFY(XLPE- AL-Armoured) UR No - 120 2.1.15 3C x 35 Sq.mm. A2XFY(XLPE- AL-Armoured) UR No - 100 2.1.16 3C x 25 Sq.mm. A2XFY(XLPE- AL-Armoured) UR No - 60 2.1.17 3CX10Sq.mm. XFY(XLPE -CU-Armoured) UR No - 80 2.1.18 3CX4Sq.mm. XFY(XLPE -CU-Armoured) UR No - 100 2.1.19 3CX2.5 Sq.mm. XFY(XLPE -CU-Armoured) 2000 No 180 - 180 100 2.1.20 4CX16Sq.mm. XFY(XLPE -CU-Armoured) 40 No 422 - 422 60 2.1.21 4CX10Sq.mm. XFY(XLPE -CU-Armoured)) 550 No 345 - 345 60 2.1.22 4CX10Sq.mm. XFY(XLPE -CU-Armoured) 30 No 345 - 345 60 2.1.23 4CX6 Sq.mm. XFY(XLPE -CU-Armoured) 40 No 257 - 257 60 2.1.24 4CX4Sq.mm. XFY(XLPE -CU-Armoured) 70 No 257 - 257 60 2.1.25 4CX2.5Sq.mm. XFY(XLPE -CU-Armoured) 60 No 212 - 212 40 2.1.26 4CX1.5Sq.mm. YWY(PVC -CU-Armoured) 20 No 184 - 184 40 2.1.27 2CX10Sq.mm. XFY(XLPE -CU-Armoured) UR No - 2.1.28 2CX4Sq.mm. XFY(XLPE -CU-Armoured) UR No - 2.1.29 19CX1.5Sq.mm. YWY(PVC -Cu-Armoured) 30 No 461 - 461 100 2.1.30 24CX1.5Sq.mm. YWY(PVC -Cu-Armoured) 24 No 721 - 721 150 2.1.31 5CX2.5 Sq.mm. WY(PVC -CU-Un-Armoured Flexible ) UR No 35

TOTAL OF SECTION C- CABLESD SECTION -D-CABLE TRAYS & ASSOCIATED WORKS

1

1.1 750 mm wide 50 Mtr. 610 10% 61 671 200 Offer from profab is attachedRunners 20 x 75 x 20 x 2.5 mm - - Rungs 20 x 30 x 20 x 2.5 mm 250 mm C/C - -

- - 1.2 600 mm wide 2000 Mtr. 555 10% 56 611 140 Offer from profab is attached

Runners 20 x 75 x 20 x 2.5 mm - - Rungs 20 x 30 x 20 x 2.5 mm 250 mm C/C - -

- - 1.3 450 mm wide 100 Mtr. 495 10% 50 545 120 Offer from profab is attached

Runners 20 x 75 x 20 x 2.5 mm - - Rungs 20 x 30 x 20 x 2.5 mm 250 mm C/C - -

- - 1.4 300 mm wide 50 Mtr. 435 10% 44 479 84 Offer from profab is attached1.5 Runners 20 x 75 x 20 x 2.5 mm - -

Rungs 20 x 30 x 20 x 2.5 mm 250 mm C/C - - - -

1.6 100 mm wide UR Mtr. 360 10% 36 396 70 Offer from profab is attachedRunners 20 x 75 x 20 x 2.5 mm

Rungs 20 x 30 x 20 x 2.5 mm 250 mm C/C

2

2.1 750 mm x 75 x 75 x 2 mm thick UR Mtr. 995 10% 100 1,095 200 Offer from profab is attached2.2 600 mm x 75 x 75 x 2 mm thick 1200 Mtr. 830 10% 83 913 140 Offer from profab is attached2.3 450 mm x 75x 75 x 2 mm thick 300 Mtr. 665 10% 67 732 140 Offer from profab is attached2.4 300 mm x 75x 75 x 2 mm thick 800 Mtr. 500 10% 50 550 105 Offer from profab is attached2.5 150 mm x 50 x 50 x 2 mm thick 600 Mtr. 280 10% 28 308 105 Offer from profab is attached

3

3.1 750 mm x 75 x 75 x 2 mm thick UR Mtr. 735 10% 74 809 140 Offer from profab is attached3.2 600 mm x 75 x 75 x 2 mm thick 50 Mtr. 595 10% 60 655 105 Offer from profab is attached3.3 450 mm x 40 x 40 x 2 mm thick UR Mtr. 455 10% 46 501 105 Offer from profab is attached3.4 300 mm x 40 x 40 x 2 mm thick UR Mtr. 310 10% 31 341 70 Offer from profab is attached3.5 150 mm x 25 x 25 x 2 mm thick UR Mtr. 170 10% 17 187 63 Offer from profab is attached

- -

4 4000 Mtr 400 10% 400 45 Offer from profab is attached

5 35 MT 63,000 63,000 20 Rate is built up with previous experience

TOTAL OF SECTION D- CABLE TRAYS E SECTION -E-EARTHING

1

1.1 75 mm x 10 mm UR Mtr. 591 - 591 85 Offer from subcontractor is atatched1.2 50 mm x 10 mm 9000 Mtr. 397 - 397 49 Offer from subcontractor is atatched1.4 25 mm x 6 mm UR Mtr. 132 - 132 14 Offer from subcontractor is atatched

Note: Aluminum Lugs shall be used for AlLUMINUM Conductor Cables & Copper Lugs for COPPER Cables

Supply and fixing of followings sizes pre galvanized factory fabricated GI Ladder type cable tays, including straight runs, bends, reducers, Tees, cross members ,couplings, earth continuity flexible conductor for each joints,anchor fastners, supports,drilling,cuttings,nuts, bolts, required civil works etc to complet the work. The required MS support shall be measured under M.S. steel BOQ item no--------------------------

Supply and fixing of perforated type GI cable trays of the following sizes as per specification.

Supply and fixing of GI cable trays covers of 2 mm thick including all necessary fixing arrangement,hardware, consumable etc . Suit to following GI perforated and ladder type cable trays .

Supply, Installation,testing & Commissioning,  of  MS Powder Coated with RAL 7032 Race Ways ,for fixing high bay light fitting at10 to 12 M. from finished floor leve,.  fabricated out of  14 gauge MS CRC sheet to form C type channel raceway with cover on side(Screw Fixed Type) of size 100x50x50  to be suspended with rods / sleek guyrope / clutch wire from true ceiling /roof  for mounting of tube light fitiings. All supporting membere shall be equvillant to GRIPPLE OR PROFAB Make supporitng members/ structures..  

Supply, fabrication and installation of cable tray cable tray supports, supports for cable trench covers, supporting frame for mounting of control panels, supports for mounting of local control station,Main Electrical Panel,lighting panel, lighting fixture etc. with 2 coats of enemel primer and 2 coats of epoxy paint Note - The rates shall be inclusive of grouting of supports , Anchor fastner,welding rods, nut,bolts,clamps,and any other consumable which required to complete the works.

Supplying and laying of G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by welding overlapping )

Page 68: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

1.5 25 mm x 3 mm (For street light & power socket earthing) 7500 Mtr. 62 - 62 21 Offer from subcontractor is atatched

1.6 300 Mtr. 1,147 - 1,147 21 Offer from subcontractor is atatched

1.7 50 mm x6 mm (Cu) with Brazing joint 50 Mtr. 2,211 - 2,211 21 Offer from subcontractor is atatched1.8 8 SWG GI wire 500 Mtr. 13 - 13 7 Offer from subcontractor is atatched1.9 14 SWG GI wire UR Mtr. 15 - 15 11 Offer from subcontractor is atatched1.10 12 SWG GI wire 200 Mtr. 15 - 15 8 Offer from subcontractor is atatched

1.11 200 Nos. 819 - 819 100 Offer from subcontractor is atatched

1.12 80 Nos. 1,200 - 1,200 100 Offer from subcontractor is atatched

1.12 Lightning air terminal 25 mm dia copper rod 1500 mm Long UR No. 1,071 - 1,071 100 Offer from subcontractor is atatched

1.13 1200 Mtr. 764 - 764 35 Offer from subcontractor is atatched

2 18 No 8,500 10% 850 9,500 2,100 Considered market rate

3 22 No 11,000 10% 1,100 9,500 2,100 Considered market rate

-

4

84 No

8,150 10% 815 9,500 2,000 Offer from Jef is atached

Length - 3000mm Outer Pipe Dia - 76mmInner Pipe Dia. - 38mm

Make : Ashlok,Fast Track, JEF

5 LIGHTNING PROTECTION SYSTEM

5.1 7 Set 112,300 10% 11,230 123,530 7,500 Offer from Jef is atached

Each lightning protection set shall be comprising with followings devices

a

b

c

d

25 mm x6 mm (Cu) with Brazing joint (For metering Kiosk & Transformer neutral)

G.I.earthing bus, 750mm Long x 50x10mm with supporting insulators & all Hardwares

Tin plated CU.earthing bus, 750mm Long x 50x6mm with supporting insulators & all Hardwares

1core x70 Sq.mm cu cable ,green colour with yellow strip FRLS PVC insulation (For UPS, L.E.B m/c, CNC m/c & Welding m/c earthing)

Providing earthing stations at locations as called for including providing and laying 3 Mtr Long x 65mmDia G.I. electrode with 50 x 6 mm thick G.I. strip, To form earth electrode with inspection chamber,Watering funnel with 20 gauge G I wire ,600 x600 mm heavy duty Chamber with CI Manhole cover etc.(Scope including excavation by manual/Machines /Boaring, Charcoal, salt, or Bentonie slurry etc) For MSDCL Metering Kiosk.

Supply,Installation,Testing and commissioning of earth pit of size 600 x 600 x 3 mm copper plate with GI water pipe 2.7 mtr long x19mm dia , buried in earth pit with charcoal and salt each in alternative layers including excavation re-filling etc. all as per enclosed drawing, with C.I.legend identification marker.The complete earth pit shall be as per IS 3043. The scope also includes with inspection chamber,Watering funnel with 20 gauge G I wire ,,600 x600 mm heavy duty Chamber with CI Manhole cover etc.(Scope including excavation by manual/Machines , Charcoal, salt, or Bentonie slurry etc) (For UPS,Transformer & DG Neutral earthing)

Supply, testing and commissioning earthing stations as per IS 3043, maintenance free earthing pit of mild steel hot dep galvanised. The pipe shall be insterted one inside the another. The pipe shall be filled & packed with highly conductive and anti corrosive mixture with following diamension. The scope also includes with inspection chamber,Watering funnel with 20 gauge G I wire ,600 x600 mm heavy duty Chamber with CI Manhole cover etc.(Scope including excavation by manual/Machines /Boaring, .

300 X 150mm chamber shall be provided for inspection and connection. 50mmx6 mm thick copper strip shall be nut bolted to connect the earthing strips/Leads The electrode shall be provided with two chemical compound bags (20Kg each)

Supply & Installation of ESE Lightning Rod , with Stainless Steel Body, working on the Principle of (ESE) Early Streamer Emission technology, which will offer LEVEL 1 protection for 79 Mtrs radius when mounted at a height of 5 mtrs from the plane to be protected, complying to NFC 17 102.

Type- Early Streamer EmissionMake & Model - CIRPROTEC (NIMBUS)

Matrerial Used - Corrosion resistant stainless steel body

Construction Details => The electronic circuit of the ESE rod shall be encapsulated in an epoxy mould toavoid derating or degradation due to atmospheric conditions. This also makes the Lightning rod weather proof and suitable for installation in highly corrosive atmosphere.The rods shall be made of Corrosion Resistant Stainless body conforming AISI 316 grade.

The Lightning rod shall be self powered type and shall not require any form of external power supply/batteries for its operation. .

Conformity to standards - As per NF C17-102 and UNE 21186-96Radius of Protection(M) - 79M level 1

Construction Details - Lightning Rods shall be manufactured according to UNE 21.186-96 and NF C17-102 standards .

Sensors-Type - Electronic equipped with triggering device

Test Reports -Should have been tested at an internationally accredited Laboratory and CPRI , Bangalore and the necessary test reports to be attached.

Shall be designed to check the integerity of the electronics periodically with a tester

4 DIGIT ELECTROMECHANICAL Lightning Transient Event counter ,in a IN WEATHER PROOF ENCLOSURE shall be mounted in 1.5 Mtrs from the ground level

Main Lightning Air terminal suitable for protection of Radious of 80 meter from its base of 5 Meter height for Level III Protection.

GI Elevation pole with a reducer to fix the LA unit, Base Plate, Clamps and all required fixing accessories ( Ready to Install).

Test Clamp to connect the down conductor to the earth termination and disconnect the down conductor from the earth termination for regular checks of the earth termination resistance value.

1 Set of Remote Control unit required only for testing the Prevectron air terminal.

Page 69: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

5.2 7 Nos. 14000 10% 1,400 15,400 1,000 Offer from Jef is atached

TOTAL OF SECTION- E- EARTHING (GROUNDING)

F SECTION – F D.G.SETS1 DIESEL GENERATOR SET

1.1 2 Nos 9,000,000 9,000,000 30,000

1.2 2 Nos 1,000,000 1,000,000 10,000

1.3

a 500 mm dia. NB 55 Mtrs 8,800 8,800 2,500 b 350 mm dia. NB 35 Mtrs 6,550 6,550 2,000

1.4 5000 K.G. 85 85 25

1.5 ELECTRICAL

a

b 24C x 1.5 Sq.mm PVC screened cable 300 Mtr 1,445 1,445 56 c 8C x 1.5 Sq.mm PVC screened cable 300 Mtr 535 535 42 d 4C x 1.5 Sq.mm PVC screened cable ( For Electronic Governer ) 300 Mtr 314 314 35

e 12 C x 0.5 Sq.mm PVC screened Triad cable ( for temperature scanner ) 300 Mtr 562 562 42

f Profi bus 2 wire Communication cable 300 Mtr 184 184 42

1.6 1 Set 4,200,000 4,200,000 12,000

1.7

NGR Element : Resistance: 121Ohms & 52.48 Amps at 11/√ 3 k.V. 2 Nos 225,000 225,000 5,000 Rate from Market as panel is fabricated1 No 400Amp-12k.V. Single Pole Vacumm contactor with Auxiliary contacts3 Nos 75/1Amp CL -PS CT with internal wiring & terminalsIP Degree of complete NGRVPanel : IP65

TOTAL OF SECTION- F- GENERATOR SETG SECTION -G-LIGHTING FIXTURES/EXHAUST FANS

1

1.1 50 Nos 1200 5% 60 1,260 280 CAPEX ITEM-Offer from GE is attached

- -

Lightning Flash Counter. Electronically controlled, register every strike between 1000 A to 100 KA for a 8/20 microsecond peak current. Tested in High Voltage Laboratory (CPRI).

Supply Transporation, Unloading at Place of installations,, installation, testing and commissioning of radiator cooled 1000 KVA prime (actual) rating diesel generating set (11000 Volts Alternator with PCCM or equivalent) along with day oil fuel tank, CT Adaptor Box, AVM Pads including cable termination box with all associated equipment / work as per specifications. Alternator shall have class H insulation 11000 Volts and rated for 800 KW output. Engine shall not be derated upto 50 deg.C ambient and suitable for bearing the starting current after changeover. The scope also includes providing foundation details drawings to Engineer In Charge (Foundation will be provided by Civil scope of works), Liasioning work from Govt Authorities Like Electrcial Inspector, MIDC, Pollution control Boards etc. The scope also includes filling first oil ,fuel for commissioning.

NON GE CAPEX ITEM- OFFER FROM POWERICA IS ATTACHED

Supply, installation, testing and commissioning of powder coated acoustic enclosure suitable for 1000 KVA DG set for indoor application as per specification complete with all accessories as required including ventilation system. No deration in DG set capacity shall be accepted on this account. The scope also includes providing foundation details drawings to Engineer In Charge (Foundation will be provided by Civil scope of works), Liasioning work from Govt Authorities Like Electrcial Inspector, MIDC, Pollution control Boards etc.

Supply, erection, testing and commissioning of exhaust piping Min. 6mm Thick of following sizes with welding joint including bends, MS pipe supports, clamps, dash fastener, nuts, bolts etc.,with first layer of insulation 25mm thick ceramic fiber wool (96Kg/Cub. Mtr.) & second layer minimum 50mm thick rockwooll (150Kg/Cub Mtr.) covered with 26 SWG aluminium sheet claddings etc. complete as required and as per specifications.

Exhaust pipe supporting system with M.S channel, M.S angle, M.S flat, dash fastners, nut, bolt etc. complete including 1 coat of redoxide & 2 coat of enamel paint and other Accessories as required at the site of work.

PLC / SCADA Application Interface cables Supply & Installation( PVC Screened Copper cables)

Supply, installation, testing and commissioning of D.G Set Automatic Synchronizing panel suitable for,11k.V.26.2k.A. ,2 x 1000k.V.A. D.G. Set as per Technical specification & enclosed Single line diagram ( Drg. No GE-P-FAC-Ele00-01-08-155003 ) The Specification for D.G. Autosynchronizing Panel shall be as per HT Panel items reference sr 1 of section B

Supply, installation, testing and commissioning of NEUTRAL GROUNDING RESISTOR (NGR) panel suitable for Each D.G. Set of 1000k.V.A. as per Technical specification & enclosed Single line diagram ( Drg. No GE-P-FAC-Ele00-01-08-155003 ) The Complete NGR Panels shall be comprising followings parameters.

Supply, installation, testing and commissioning of luminaires complete with, lamps, ballast, starter, HPF condenser, standard down rod, connecting cord, The rate shall include all necessary fixing accessories like MS hooks, MS supports, fasteners, with all necessary hardware, accessories as required for complete installation. Quoted rate shall exclude the cost of earthing . Note: Catalogue numbers indicated are only to describe type of light fixture required. Lamp Colour shall be - 84 or as approved by Architect / Consultant.

Supply Installation, testing & commissioning of 2x28 W T5 with electronic ballast equivallent to GE cat no GET CI 2X28 C/S HF.The scope also includes all accessories and tube etc., including supplying and fixing ball and socket arrangement, 2 no. down rods of 20 mm dia X1.6 mm thick G.I. steel conduit upto 30 cm length, painting and wiring the down rods and connection with 1.5 sq. mm FR PVC insulated, copper conductor, single core wires and earthing , fastening accessores etc as required to complete the work

Page 70: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

1.2 875 Nos 4650 5% 233 4,883 350 CAPEX ITEM-Offer from GE is attached

- -

- - - -

1.4 176 Nos 3150 158 3,308 420 CAPEX ITEM-Offer from GE is attached

- -

1.5 8 Nos 7200 360 7,560 490 CAPEX ITEM-Offer from GE is attached

- -

1.6 0 Nos 2200 5% 110 2,310 280 CAPEX ITEM-Offer from GE is attached

- -

1.7 10 Nos 1350 5% 68 1,418 210 CAPEX ITEM-Offer from GE is attached

- -

1.8 0 Nos 1150 5% 58 1,208 210 CAPEX ITEM-Offer from GE is attached

- -

1.9 0 Nos 3650 5% 183 3,833 140 CAPEX ITEM-Offer from GE is attached

- -

1.10 8 Nos 5200 5% 260 5,460 245 CAPEX ITEM-Offer from GE is attached

- -

1.11 UR Nos - -

- - Note for above light fittings items

i

ii

iii

2 Supply,& Installation of Exhaust fans of following ratings

2.1 30 No 6,930 6,930 350 Offer from subcontractor is attached

2.2 0 Nos 1,890 1,890 175 Offer from subcontractor is attached

2.3 80 Nos 10,080 10,080 350 Offer from subcontractor is attached

2.4 0 Nos. 7,560 7,560 280 Offer from subcontractor is attached

TOTAL OF SECTION G- LIGHTING LUMINARIES

H

1 POINT WIRING -IN M.S. CONDUITS

1.1

a Primary light point up to 5 meter length 10 Point 806 806 175 Offer from subcontractor is attachedb Primary light point up to 8 meter length 20 Point 1,151 1,151 200

c Primary light point up to 10meter length 20 Point 1,424 1,424 225

4X54W T5 Highdbay Luminaire Equivallent to GE Cat Ref ELC454 with Lamps of 4 X54W FTL T5 with dimmable choke suit for dimming control, on M.S. raceway mouted on 12-14 Meter elevation including arrangement of all cherry pickers, loopings of 3 core 1.5 Sq.mm Flexible FRLS insulated cables from looping junction boxe to each fitting

NOTE.:- Race will supply 7 instaalation will be measured separetly. (No welding will allowed)

95 W LED IP 66 Street light fixture to fixed on 7.5 to 9 Meter hight poles including supply and pulling of 3 Core x 1.5 Sq..mm Cu Flexible ,-FRLS cables from Pole mouted looping junction box to each fitting terminals

150W HPMV Integral Post top light fixture equivallent to GE cat no DUNAADCMH150W TU including supply and pulling of 3 Core x 1.5 Sq..mm Cu Flexible ,-FRLS cables from concealed looping junction box to each fitting terminals, including providing concealed 25 mm PVC pipes for incoming cables to Looping junction box & up to each light fittings,

42 W LED Recess mounted decorative luminaries equivallent to GE cat no GCRO42.56 MO with all accessories and tube etc., including supplying and fixing ball and socket arrangement 2 nos /Flexible SS Chains/ or 2 no. down rods of 20 mm dia X1.6 mm thick steel conduit upto 30 cm length, painting and wiring the down rods and connection with 3 Corex 1.5 sq. mm FRLS insulated, copper conductor, cable and earthing etc as required.

2X28W FTL T5 Surface Mounted with clear Acrylic cover Luminaire with electronic ballast equivallent to Wipro cat no WCF 50228 SGW including required clamps , fastners ,connection to fittings etc to fixed in staircase etc.

2 x18 W Decorative Recess mounted Down lighter equivallent to GE cat no GECFLC2X36DNLR(H) HF with required hanging support from ceiling

1 x18 W Decorative Recess mounted Down lighter equivallent to GE cat no GECFLC2X18DNLR(H) HF with required hanging support from ceiling

150 W MH Integral Flood light Luminaire Equivallent to GE cat no GEMF1X150CAI with required support to fixed on top plate of 7.5 Mtr high street light pole

400 W MH Integral Flood light Luminaire Equivallent to GE cat no ZF400 KRC .The fitting shall be installed on top mounting plate of 16 Mtr high lighting mask.

All light fittings quantities shall be procured as per Final approved Drawings by architect & approval from client /Architects for sample of each light fittings.

Connection of lighting fixtures from ceiling rose / junction box by flexible copper wires in flexible conduit/M.S. ball and socket arraqngment is included in the conduit down rod, scope

The structural supports for suspension of lighting fixtures are measured seperately

Supply, of Exhaust fan Heavy duty 230 V AC 50 Hz 305 mm 1400 RPM with condenser complete erected in position with n/c materials Fan motor with moisture treatment and class E insulation & With bird protective screen

Supplying of capacitor type1200 mm sweep ceiling fan complete with down rod, blades, shakle etc. with high breeze, high speed for operation on 230V, 50 Cy. Single phase A.C. supply confirming to IS 374-1979 and with double ball bearing system The fan shall be green rated as per BEE norms.

Supply of 750 mm sweep-1 Ph 240 Volts 50 Hz Wall/Column Mounted Air cirulated fans including Inbuilt speed regulator Including all necessary fixing hardware,Anchor fastner etc. Almonard make

Supply & Fixing of Ceiling mounted (surface/flush) high performance, Movement Detector with the coverage of 6Mtrs dia complete with necessary Sensor control wiring.vWIPRO Cat ref COP 11010 OR Hager make EE805 or Schneider make CSS54E-WE or Bajaj Make - Bajaj-Leviton OSC 10-MOW

SECTION :H: SUPPLY & PROVIDING OF POINT WIRING AND ACCESSORIES.

Primary light Wiring for followings light point/ fan point/ exhaust fan point/ call bell point with 2 Nos 2.5 sq.mm FRLS insulated copper conductor single core cable in surface / recessed 25 mm dia, 16 SWG black stove enemelled steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS insulated copper conductor single core cable etc as required. (Wiring from Lighting Switch boards to first light points in the group of lighting circuit )

Page 71: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

1.2

a Secondary light point up to 2 meter length 25 Point 355 355 150 Offer from subcontractor is attachedb Secondary light point up to 4 meter length 20 Point 547 547 175

c Secondary light point up to 5meter length 20 Point 693 693 200

1.3 UR Point 1,424 1,424 Offer from subcontractor is attached

1.4

a 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire 0 Mtr 311 311 25 Offer from subcontractor is attachedb 2 X 4 sq. mm + 1 X 4 sq. mm earth wire 0 Mtr 349 349 35

c 2 X 6 sq. mm + 1 X 6 sq. mm earth wire 0 Mtr 405 405 40

1.5 0 Mtr 475 475 35 Offer from subcontractor is attached

1.6 0 Mtr 437 437 25 Offer from subcontractor is attached

1.7 0 Mtr 516 516 45 Offer from subcontractor is attached

2 POINT WIRING -IN PVC CONDUITS

2.1

a Primary light point up to 5 meter length 0 Point 806 806 150 Offer from subcontractor is attachedb Primary light point up to 8 meter length 0 Point 1,151 1,151 175

c Primary light point up to 10meter length 0 Point 1,424 1,424 200

2.2

a Secondary light point up to 3 meter length 0 Point 280 280 125 Offer from subcontractor is attachedb Secondary light point up to 5 meter length 0 Point 542 542 160

c Secondary light point up to 8meter length 0 Point 867 867 175

2.3 UR Poit 1,273 1,273 Offer from subcontractor is attached

2.4

a 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire 0 Mtr 248 248 15 Offer from subcontractor is attachedb 2 X 4 sq. mm + 1 X 4 sq. mm earth wire 0 Mtr 286 286 20

c 2 X 6 sq. mm + 1 X 6 sq. mm earth wire 0 Mtr 342 342 25

2.5 0 Mtr 273 273 20 Offer from subcontractor is attached

2.6 0 Mtr 248 248 15 Offer from subcontractor is attached

2.7 UR Mtr 1,084 1,084 Offer from subcontractor is attached

Secondary light Wiring for followings light point/ fan point/ exhaust fan point/ call bell point with 3 Nos 1.5 sq.mm FRLS insulated copper conductor single core cable in surface / recessed 25 mm dia, 16 SWG Black stove enemelled steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS insulated copper conductor single core cable etc as required. (Wiring from Lighting Switch boards to first light points in the group of lighting circuit )

Secondary point Wiring for twin control light point with 1.5 sq.mm FR LS insulated copper conductor single core cable in surface / recessed 25 mm dia, 16 SWG Black stove enemelled steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR LS insulated copper conductor single core cable etc as required.

Wiring for circuit/ submain wiring along with earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface / recessed 25 mm dia, 16 SWG Black stove enemelled steel conduit as required

Power plug wiring in M.S. Black stove condiut (2 x 4 sq.mm) - Wiring for power plug with 2X4 sq. mm., FR LS insulated, copper conductor, single core cable in surface/recessed 16SWG ,25 mm dia M.S. Black stove conduit along with 1 no. 4sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.

Power plug wiring in M.S. Black stove condiut (2 x 2.5 sq.mm) - Wiring for power plug with 2X2.5 sq. mm., FR LS insulated, copper conductor, single core cable in surface/recessed 16SWG ,25mm dia,M.S. Black stove conduit along with 1 no. 2.5sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.

Power plug wiring in M.S. condiut (4 x 4 sq.mm )- Wiring for powersocket outlet with 4X4 sq. mm. FRLS insulated, copper conductor, single core cable in surface/recessed 16SWG ,25 mm. dia M.S. black stoved enemelled conduit along with 2 nos. 4sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.

Primary light Wiring for followings light point/ fan point/ exhaust fan point/ call bell point with 2 Nos 2.5 sq.mm FRLS insulated copper conductor single core cable in surface / recessed Heavy duty 2 mm in thick & 25 mm diameter PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS insulated copper conductor single core cable etc as required. (Wiring from Lighting Switch boards to first light points in the group of lighting circuit )

Secondary light Wiring for followings light point/ fan point/ exhaust fan point/ call bell point with 3 Nos 1.5 sq.mm FRLS insulated copper conductor single core cable in surface / recessed Heavy duty 2 mm in thick & 25 mm diameter PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS insulated copper conductor single core cable etc as required. (Wiring from Lighting Switch boards to first light points in the group of lighting circuit )

Secondary point Wiring for twin control light point with 1.5 sq.mm FR LS insulated copper conductor single core cable in surface / recessed Heavy duty 2 mm in thick & 25 mm diameter PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR LS insulated copper conductor single core cable etc as required.

Wiring for circuit/ submain wiring along with earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed Heavy duty 2 mm in thick & 25 mm diameter PVC conduit as required

Power plug wiring in PVC condiut (2 x 4 sq.mm) - Wiring for power plug with 2X4 sq. mm., FR LS insulated, copper conductor, single core cable in surface/recessed Heavy duty 2 mm in thick & 25 mm diameter PVC conduit along with 1 no. 4sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.

Power plug wiring in PVC condiut (2 x 2.5 sq.mm) - Wiring for power plug with 2X2.5 sq. mm., FR LS insulated, copper conductor, single core cable in surface/recessed Heavy duty 2 mm in thick & 25 mm diameter PVC conduit along with 1 no. 2.5sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.

Power plug wiring in PVC condiutt (4 x 4 sq.mm )- Wiring for powersocket outlet with 4X4 sq. mm. FRLS insulated, copper conductor, single core cable in surface/recessed Heavy duty 2 mm in thick & 25 mm diameter PVC conduit along with 2 nos. 4sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.

Page 72: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

3 Wiring Accessores for Raw power & UPS Power socket outlets

3.1

a 1 or 2 Module(75mmx75mm) UR No 132 132 25

Offer from subcontractor is attached

b 3 Module (100mmX75mm) UR No 138 138 25 c 4 Module (125mmX75mm) UR No 159 159 30 d 6 Module (200mmX75mm) UR No 274 274 35 e 8 Module (125mmX125mm) UR No 307 307 35 f 12 Module (200mmX150mm) UR No 460 460 50

3.2

a 1 or 2 Module UR No 130 130 25

Offer from subcontractor is attached

b 3 Module UR No 145 145 25 c 4 Module UR No 162 162 30 d 6 Module UR No 253 253 35 e 8 Module UR No 271 271 35 f 12 Module UR No 284 284 50

3.3

a 5/6 amps switch UR No 110 110 25

Offer from subcontractor is attachedb 15/16 amp switch UR No 169 169 25 c 3 pin 5/6 amp socket outlet UR No 177 177 35 d 6 pin 15/16 amp socket outlet UR No 208 208 40

3.4 UR Mtr 122 122 10 Offer from subcontractor is attached

3.5 UR Mtr 110 110 8 Offer from subcontractor is attached

4

a 50 x 38 x 2 mm UR Mtr 266 266 40

Offer from subcontractor is attachedb 100 x 38 x 2 mm UR Mtr 411 411 60 c 150 x 38 x 2 mm UR Mtr 696 696 95 d 200 x 38 x 2 mm UR Mtr 785 785 125 e 300 x 38 x 2 mm UR Mtr 1,081 1,081 130

5

a 250x250x60- 75 mm three compartment. UR Nos 1,512 1,512 Offer from subcontractor is attached

b 265x265x53- 80 mm three compartment. UR Nos 1,512 1,512 UR Nos - -

6

a 250x250x60- 75 mm three compartment. UR Nos 3,150 3,150 Offer from subcontractor is attached

b 300x300x60- 80 mm three compartment. UR Nos 3,150 3,150

TOTAL OF SECTION H- POINT WIRING & ACCESSORIES

I

1

1.1 20 No 65,000 65,000 1,500 Rates from GE Price list are taken

Incomer : 63 A,4 pole, MCB 10k.A. C-CL Outgoing :As under16 - 25A-2P-RCBO 30m.A.:15 Nos (5 Nos/Phase)

1.2 12 Nos 50,000 50,000 1,200 Rates from GE Price list are taken

(a)

(b) Outgoing :As under

i

ii 16 - 25A-2P-RCBO 30m.A.:36 Nos(12 Nos Per Phase)

S/F GI Box along with modular plate: Supplying and fixing following size /modules, GI box along with modular base & cover plate for modular switches in recess etc as required. The scope also includes cutting of wall, block works, & POP of walls with mesh after plate fixing & other related civil works to make surface good .

Supply & fixing following modular base and cover plate for modular switches in recess etc as required.

Supplying and fixing following modular switch/ socket on theexisting modular plate & switch box including connections butexcluding modular plate etc. as required.(Raw Power /UPS Power socket outlets)

Supply and providing of Power plug wiring in Raceway in office (2 x 4 sq.mm) - Wiring for light/power plug with 2X4 sq. mm., FR LS insulated, copper conductor, single core cable in existing surface/recessed raceway along with 1 no. 4sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.(UPS & Raw Power Power)

Supply and providing of Power plug wiring in Raceway in office (2 x 2.5 sq.mm) - Wiring for light/power plug with 2X4 sq. mm., FR LS insulated, copper conductor, single core cable in existing surface/recessed raceway along with 1 no. 2.5sq.mm., FR LS insulated, copper conductor single core cable for loop earthing as required.(UPS & Raw Power Power)

Supply, fixing, laying and embedding in UNDER FLOOR ALUMINUM of following sizes complete with all accessories including junction box with 2 mm thick Stainless steel cover plate,neoprene gasket in joints ,cutting the floor and jamming the raceway with all necessary hardware (including civil works) as required.

Supply, fixing, commissioning of following sizes access outlet with all accessories, cutting the floor and jamming the access outlet with all ncessary hardware (including civil works) as required.

Supply , fixing, commissioning of following sizes cross over/ junction box with 3 mm thick cover plate with all accessories cutting the floor and jamming the junction box with all necessary hardware including civil works as required.

SECTION -I-LIGHTING PANELS-IP42 - & INDUSTRIAL SWITCH SOCKET OUTLET/ISOLATORS

Supplying and fixing following way prewired TP&N MCB distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FR LS insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc. as required.

Typical Raw Power & UPS Power Final D.B. Application (Ref Tender drawing no GE-P-FAC-Ele00-01-11-1550013)

Typical Lighting D.B. (Ref Tender drawing no GE-P-FAC-Ele00-01-11-1550011)

Incomer : 63 A,4 pole, MCB 10k.A. C-CL+Auto /Manual Control selector switch for outgoing circuits

16-25 Amp 2 P Moduler Power contactor with Auxiliary contact for Remote ON /OFF of contactor from BMS & ON/OFF status of contactor to BMS : 36 Nos(12 Nos Per Phase)

Page 73: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

1.3 6 Nos 35,000 35,000 900 Rates from GE Price list are taken

(a)

(b) Outgoing :As under

i

ii 16 - 25A-2P-RCBO 30m.A.:18 Nos(6 Nos Per Phase)

1.4 Typical E. L. D.B. (Ref Tender drawing no GE-P-FAC-Ele00-01-11-1550010) 15 Nos 32,000 32,000 800 Rates from GE Price list are taken

(a)

(b) Outgoing :As under

i

ii 16 - 25A-2P-RCBO 30m.A.:12 Nos(4 Nos Per Phase)

1.5 Area Street light Final D.B. for Street Lights as under 2 No 80,000 80,000 1,500 Rates from GE Price list are takenIncomer : 125 Amp -4 Pole MCCB + 1 No 4 Pole-110 Amp Moduler Contractor Outgoing 12 Nos 32 Amp TP MCB 10K.A. CL + 32Amp 4 Pole ELCB -30m.A. per Outgoings& 24 Hrs Timer + Photo Cell with Manual / Auto Selctor switch, Interface provision with BMS & its control wiring etc.

1.6 Flood Light Mast lighting PDB.as under 1 No 80,000 80,000 1,500 Rates from GE Price list are takenIncomer : 100 Amp -4 Pole MCCB , + 1No4 Pole-110 Amp Moduler Contractor + 24 Hrs Timer + Photo Cell with Manual / Auto Selctor switch, Interface provision with BMS & its control wiring etc.Outgoing 10 Nos 32Amp 25k.A. TP-MCCB-LS -Release.

1.7 D.B. Server system 1 No 15,000 15,000 500 Rates from GE Price list are takenIncomer : 63 A,DP,MCB type IsolatorOutgoing : 25 A DPMCB- 10k.A -D-CL10 Nos per Phase

1.8 Security Kiosk D.B. as under 4 No 22,000 22,000 650 Rates from GE Price list are takenIncomer : 63 A,4 pole, MCB 10k.A. C-CL +4 Pole 63 Amp ELCB 100m.A.Outgoing : As undera. 12 Nos 20 A SPMCB- 10k.A -C-CL (4 Nos /Phase)

b. 4 Nos 32 A -TP MCB 10k.A. C-CL

2

2.1 100 Set 6,640 6,640 350 Rates from GE Price list are taken

2.2 28 Set 10,630 10,630 490 Rates from GE Price list are taken

2.3 4 Set 24,774 24,774 630 Rates from GE Price list are taken

3

3.1 20A SP MCB - 01 No. in Metal BOX 25 No. 536 536 75 Rates from GE Price list are taken3.2 20A SP MCB - 02 No. in Metal BOX 30 No. 902 902 75 Rates from GE Price list are taken3.3 20A SP MCB - 03 No. in Metal BOX 40 No. 1,122 1,122 75 Rates from GE Price list are taken

TOTAL OF SECTION I- FDB /SSO/LDSJ SECTION -J-EXTERNAL LIGHTING

1.0

1.1 Single bracket 183 No 12,500 12,500 2,500 Market rates considered1.2 Double bracket 3 No 15,000 15,000 700 Market rates considered1.3 50 mm dia G.I. bracket mouted street light poles(Max 3 Mtr Length) 2 No 10,080 10,080 700 Market rates considered

3 Flood Light Mast As under

Typical Lighting D.B. (Ref Tender drawing no GE-P-FAC-Ele00-01-11-1550011)

Incomer : 63 A,4 pole, MCB 10k.A. C-CL+Auto /Manual Control selector switch for outgoing circuits

16-25 Amp 2 P Moduler Power contactor with Auxiliary contact for Remote ON /OFF of contactor from BMS & ON/OFF status of contactor to BMS : 18 Nos(6 Nos Per Phase)

Incomer : 25 A,4 pole, MCB 10k.A. C-CL+Auto /Manual Control selector switch for outgoing circuits

16-25 Amp 2 P Moduler Power contactor with Auxiliary contact for Remote ON /OFF of contactor from BMS & ON/OFF status of contactor to BMS : 12 Nos(4 Nos Per Phase)

Supply, Installation, Testing & Commissioning of Following Readymade Industrial Power Sockets with neccessory cable end boxes.The each socket outlet shall be installed at fabricated M.S. Supports/ Frames suit to Sokcet outelt dimensions. The required steel shall be measured under M.S. Fabrication item of this BOQ.

3 Pin, 20 Amp, 230 Volts Industrial switch socket outlet sheet steel enclosed IP54 with 1 No. earthing terminal 'controlled by -SPN MCB 10K.A -C-CL and provided with chain and 'cover and suitable for loop in loop out of 3 x 2.5 'sq.mm XFY cable.:The complete assembly shall be suitable for IP65 with Polycarbonate body.

Combine Industrial switch Socket Out Let : 5 Pin 32A, TPN, 415 Volts Industrial switch socket controlled by 4 Pole MCB 10K.A. C-CL & 3 Pin, 20 Amp, 230 V industrial switch socket out let controlled by-SPN MCB 10K.A .-C-CL , sheet steel enclosed indoor type with 2 Nos. earthing terminals and provided with chain & cover suitable 'for loop in loop out of 3.5C x 35 sqmm A2XFY cable.:The complete assembly shall be suitable for IP65 with Polycarbonate body.

5 Pin 63A, TPN, 415 Volts Industrial switch socket controlled by 4 Pole MCB 10K.A. C-CL industrial switch socket out let sheet steel enclosed indoor type IP-54 with 2 Nos. earthing terminals and provided with chain & cover suitable 'for loop in loop out of 3.5C x 35 sqmm A2XFY cable.:The complete assembly shall be suitable for IP65 with Polycarbonate body.

METAL MCB BOXES (IP 42) : Supply & fixing of MCB Box enclosed in 1.6mm thick, CRCA sheet steel box. The box shall be concealed / Surface in the wall. The plate cover is properly aligned & flush with the wall surface all materials will be in contractor scope.

Supply & installation of hot deep galvanized (internally & externally) Octogonal cross section pole with base plate as per IS 2629 with ,supply and fixing of 2 Nos. of 63 mm dia PVC pipes for cable entry,with inside cable termination,earth connection & with weatherproof door & locking facility 3Nos. 2.5 sq.mm stranded copper flexible wires with MCB control (Minimum Overall Height 8.00 M,3mm thick, bottom dia 200mm,top dia 76 mm,bottom plate 275 mm x 275 mm x 20 mmthick. Including concrate foundation & foundation bolts.(The weather proof Loop In Loop Out junction box with all accessories shall be integral part of street light Poles)

Page 74: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

2.1 5 Set 323,946 323,946 60,000 Offer from GE is attached

2.1.1

2.1.2

2.1.3

a.

b Outgoing as underb.1 8Nos SP MCB,16Amp,10k.A., B-Class for lighting circuitb.2 2 No 16 Amp DP MCB,10k.A., B-Class forAviation light

b.3

b.4 16 Amp 10k.A.,B-Class SP MCB controlled 5/15Amp Socket Outlet

TOTAL OF SECTION J- EXTERNAL LIGHTING

K SECTION -K -MISCELLANEOUS : 1 Supply,Installation,Testing & commissioning of

the following - of the following

1.1 Supply, Installation, testing and commissioning of start stop local control stations of LM6 material with momentary type PB for stop, start and latch and 1 No. earthing terminal suitable for 4 x 1.5 sq.mm - YWY cable

i Outdoor, weatherproof type with IP 65 protection UR No.

ii Indoor type with IP54 protection UR No.

1.2 Junction box fabricated from 16 SWG sheet steel with screwed gasketed cover and 1 No.earth terminal duly painted with two coats of red oxide and two coats of aluminium paint and to receive 4 Nos. 3 x 2.5 sq.mm YWY cables complete with Elmex terminals. (Minimum size100mm x 100mm x 75mm) 850 No. 441 441 49 Offer from subcontractor is attached

Note : Structural supports for mounting are measured separately

1.3 Floor mounted bucket stand with buckets to hand 4 nos. of 13 ltrs buckets. The stand shall be 5'(L) x 3'(H) x 2"(W) made out of 30 x 300 x 4mm MS angle frame duly coated with 2 coats of red oxide primer & 2 coats of 2 Set 3,000 3,000 500 Offer from subcontractor is attachedred finish paint

2 Supply and installation of GI pipe class B on wall / steel structure /under floor including bending / treading etc

2.1 38 mm dia UR RMT

2.2 50mm dia UR RMT

2.3 75mm dia UR RMT

2.4 100 mm dia UR RMT

2.5 150 mm dia UR RMT

3 Supply and installation of 2c x 2.5 sq.mm copper flexible wire UR Mtr.

4 Cable Markers as per Std. Drawing4.1 H.T. Cable marker 15 No. 315 315 70 Offer from subcontractor is attached4.2 L.T. Cable Marker 5 No. 315 315 70 Offer from subcontractor is attached4.3 Earthing Tag Marker as per Electrical Inspectorate requirement 103 No. 315 315 70 Offer from subcontractor is attached

5 Saftey Equipmnt

5.1 Antiskid black rubber mat of approved make,12 mm thick 900mm wide x 1800mm Long chequered type as per IS-5424 infollowing voltage grade(Jyothi Make)

5.1.1 415 V voltage grade 60 Mtr. 930 930 35 Offer from subcontractor is attached5.1.2 33 kV voltage grade 5 Mtr. 2,500 2,500 35 Offer from subcontractor is attached5.1.2 11 kV voltage grade 30 Mtr. 1,800 1,800 35 Offer from subcontractor is attached

6 First Aid box with all the standard contents. 3 No. 1,000 1,000 35 Offer from subcontractor is attached

7 First aid chart made of cloth for electricall shock treatment printed in English ,& Hindi duly framed with front glasses. 3 No. 189 189 35 Offer from subcontractor is attached

8 Pair of rubber gloves and gumboots8.1 33 kV grade 1 No. 600 600 Offer from subcontractor is attached8.2 11 kV grade 3 No. 600 600 Offer from subcontractor is attached

Supply of 16M high mast shaft in two sections suitable for 39 m/sec wind speed, with raising lowering system comprising, head frame, luminaries carriage suitable to install 8 nos luminaries in symmetrical arrangement, double drum winch, 6mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle, junction box, lightening finial.The scope of works also includes installation including supply of foundation bolts manufactured from special steel along with nuts, washers, anchor plates and templates. and concreeting including excvation,cement, etc to complete the works.Each lighting mast shall be provided with followings electrical requirement & accessoris. (Note: Contractor to submit required vendor shop drawings for complete Flood light mast system with calculation from structural consultant for foundation before commence of work)

Supply of non-integral floodlight luminaries type Equvillent to GE Cat ref ZF 400KRC with one no. 400 W MH(KRC) T lamps With control gear boxes The scope also includes Supply and fixing of 3 x 2.5 Sq.mm Cu-Armoured Cables from each Control gear to each light fittings & its connection with Weather proof D.C. Gland .: 8 Nos to each lighting mast .

Supply of single dome aviation obstruction lights of type BJAOL 1 with one nos no. 25 W Neon lamp : 2 Set to each lighting mast & individual Armoured 3x2.5 cu cable connection for the same from its control panel to neon lamp terminals .

Supply of out door, Weather proof IP65 Feeder Pillar as per following specification to each Lighting Mast

Incomer:32Amp 4 Pole MCB ,10k.A.,C-Class & 32 Amp 4 Pole ELCB 30m.A. +RYB LED Indication+Space Heater with Thermostat.

1 DOL Feeder for suitable winch motor as per vendor design & with necessary indication & control system for "LOWER& RAISE" of mast.

Page 75: Electrical Works - Package 2B Addendum BoQ Synefra Estimate

GE INDIA INDUSTRIAL PVT LTD, PUNE

RATE ANALYSIS

ELECTRICALS WORKS

Sr.No ITEMS DESCRIPTION Qty Unit

Unit Rate: Rs

Local Taxes , Fright charges RemarkQuoted rate from vendor

Total Supply Quoted rate from subcontractorfor Installation

9 Metallic danger boards.i 33 kV 2 No. 175 175 35 Offer from subcontractor is attachedi 11 kV 3 No. 175 175 35 Offer from subcontractor is attachedii 415 V 3 No. 175 175 35 Offer from subcontractor is attached

10 Portable 5 kg. dry type fire extinguisher suitable for electrical fire and as recommended by the tariff advisory committee. 1 No. 6,400 6,400 210 Offer from subcontractor is attached

11 Supply and fixing of the following charts / drawings duly framed with front glass

i Single line diagram 3 No. 750 750 105 Offer from subcontractor is attached

ii Outdoor lighting and cable layout 2 No. 750 750 105 Offer from subcontractor is attached

12 Supply and installation of RCC hume pipe as under

12.1 15 RMT 567 567 70 Offer from subcontractor is attached

12.2 150mm dia UR RMT 235 235 56 Offer from subcontractor is attached

12.3 300mm dia UR RMT 480 480 70 Offer from subcontractor is attached

13 4 way Flame proof Junction box suitable for installation in hazardous area with IP 65 Protection as per IS 12063/1897 & Gas group IIA & IIB & 1 No.earthterminal inside & 2 terminal outside duly painted with two coats of red oxide and two coats of aluminium paint and to receive 4 Nos. 3 x 2.5 sq.mm YWYcables complete with Elmex terminals. UR No 2,520 2,520 2,100 Offer from subcontractor is attached

14 Flame proof Rotary Switches suitable for installation in hazardous area with IP 65 Protection as per IS 12063/1987 & Gas group IIA & IIB & 1 No.earthterminal inside & 2 terminal outside & to receive 3 Nos. 3 x 2.5 sq.mm YWY cables UR No 3,150 3,150 2,100 Offer from subcontractor is attached

TOTAL OF SECTION K- MISC.

L SECTION- L-CIVIL WORKS

1 Excavation & Back filling of cable trenches in following soil conditions

1.1 Soft soil 650 Cum 350 Offer from subcontractor is attached1.2 Murum 485 Cum 715 Offer from subcontractor is attached1.3 Hard Rock 485 Cum 1,750 Offer from subcontractor is attached

2 Supply and laying of sand for cables. 325 CU.Mtr 2,700 2,700 700 Offer from subcontractor is attached

3 Supply and laying of burnt bricks for cables as per standard practice 14500 Nos 9 9 2 Offer from subcontractor is attached

4 Supply and Spreading of gravel 40mm size, 100 mm 15 Cu Mtr 3,500 3,500 300 Offer from subcontractor is attachedthick with duly levelling of Transformer pit - - -

- - TOTAL OF SECTION L- CIVIL WORKS

300 mm dia Half Round Pipe( For Incoming HT cable from Overhead Line to Metering Room)


Recommended