7
Electronic Temperature Controller 3699A Series Selco Products Company 8780 Technology Way, Reno, Nevada 89521-590 Tel: 775-674-5100 [email protected] www.selcoproducts.com 3699A Series Specificationsv1.5 - 1 01/08/13
Transcript
Page 1: Electronic Temperature Controller 3699A Series - … · Electronic Temperature Controller 3699A Series Selco Products Company 8780 Technology Way, Reno, Nevada 89521-590 Tel: 775-674-5100

Electronic Temperature Controller 3699A Series

Selco Products Company

8780 Technology Way, Reno, Nevada 89521-590

Tel: 775-674-5100 [email protected]

www.selcoproducts.com

3699A Series Specificationsv1.5 - 1

01/08/13

Page 2: Electronic Temperature Controller 3699A Series - … · Electronic Temperature Controller 3699A Series Selco Products Company 8780 Technology Way, Reno, Nevada 89521-590 Tel: 775-674-5100

3699A Series Specifications v1.5

U ser Interface:

Normal Operation : Controller will start to run with current parameters after power-up.

Current temperature is shown in the display. First time power-up will

use default values.

Basic operations:

Error Messages:

Sensor openProbe is not properly connected – Check installation.

Sensor shortProbe is not properly connected – Check installation.

OUt of rangeTemperature reading out of range – Check if using correct

sensor.

S LoTemperature is below reading range. Only for thermocouple

inputs.

Configuration Mode:Sets system time, temperature set-point limits, mode operations, etc.

In configuration mode, the control loop will pause until you return to

normal operation. All parameters changed in this mode are saved in

non-volatile memory . For more information refer to the parameter

table for each software mode .

Buttons functions on configuration mode:

E xample: Changing High Set Point Limit:

1. for around 3 seconds until you enter to

configuration mode.

2. Press until you reach control settings category (CTRL).

3. Press to enter to next level of parameters.

4. Press until you reach high set point limit parameter (C.USP).

5. Press to change parameter.

6. Press

7. Press to save on RAM and non-volatile memory.

8. Press to exit control settings.

9. for about 3 seconds to return to normal operation with

the changes.

Selco Products Company

8780 Technology Way, Reno, Nevada 89521-5908

Tel: 775-674-5100 [email protected]

www.selcoproducts.com

2/7

Page 3: Electronic Temperature Controller 3699A Series - … · Electronic Temperature Controller 3699A Series Selco Products Company 8780 Technology Way, Reno, Nevada 89521-590 Tel: 775-674-5100

3699A Series Specifications v1.5

ON/OFF Options

Parameter Description Unit Default Min Max

Syst - System Time Parameters

S.st Set current time H:M NA 0:00 23:59

s.hr Display Time Hour mode Option 24 12 –12 Hour

24 – 24 hour

–Ctrl Control Parameters

C.sp Current set-point.

Changing set-point

here will write in non-

volatile memory.

°C

°F

30

86

Set by

C.LSP

Set by

C.USP

C.Lsp Low set-point temperature

limit

°C

°F

-20

-4

Set by

I.Slo

Setpoint

C.USP High set-point temperature

limit

°C

°F

120

248

Setpoint Set by

I.Shi

C.dif Differential for ON/OFF

control

°C

°F

4

7

2 20

C.Sb Setback Set point °C

°F

OFF Set by

C.LSP

Set by

C.USP

C.Sbt Time for entering to

change to Setback

temperature

H:M 00:30 00:01 24:00

C.tp Mode of ON/OFF Option Heat Heat – Reverse

Cool - Direct

–Inp1 First Input Parameters

I.Cal Calibration offset to

sensing temperature.

°C

°F

0

0

-10

-18

10

18

I.Tp Curve selection for

thermistor.

Thermocouple type.

Option A

J

Curve A,B,C,D,E,F.

Type E,K,J

–Inp2 Second Input Parameters

I.Fun Functionality of external

switch.

Option OFF oFF – On

Alr- Alarm mode

SSP– Switch SP

I.Stp Switch Type Option NO NC – N. Close

No- N. Open

PB– Push Button

I.Sd Switch delay on alarm

mdoe.

M:S 00:05 00:01 5:00

–Out1 First Output Parameters

O.Otl Output minimum ON time M:S 00:00 00:00 60:00

O.Otu Output maximum ON time H:M 05:00 00:30 24:00

0.ftl Output minimum OFF time M:S 00:00 00:00 60:00

0.st Output start-up delay time. M:S 00:20 00:00 60:00

–Alr Alarm Parameters

A.Lo Low alarm temperature

threshold.

°C

°F

-20

-4

Set by

I.Slo

Setpoint

A.Hi High alarm temperature

threshold.

°C

°F

120

248

Setpoint Set by

I.Shi

A.Dt Time delay to activate

alarm event

M:S 00:05 00:00 60:00

A.Sp Alarm on SP Option OFF on – On

off- Off

A.ton Alarm tone for buzzers. Option 0 0 - 4

A.Ps Pre-setpoint alarm °C

°F

OFF 0 150

A.Ptd Pre-setpoint alarm

duration.

M:S 00:05 00:01 60:00

–Disp Display Parameters

D.dgs Degrees Unit Option °F Cels – Celsius

Fahr- Fahrenheit

D.res Sensing resolution Option 0 0 – with out decimal

1 – with one decimal

D.sd Show degree in last digit Option ON on – On

off- Off

–prog Programmed Set points

P.t1 First Programed Setpoint H:M NA OFF 23:59

P.SP1 First Programed time °C

°F

30

86

OFF Set by

C.USP

P.t2 Second Programmed

Setpoint

H:M NA OFF 23:59

P.SP2 Second Programed time °C

°F

30

86

OFF Set by

C.USP

Examples – ON/OFF Connection Diagrams:

Selco Products Company

8780 Technology Way, Reno, Nevada 89521-5908

Tel: 775-674-5100 [email protected]

www.selcoproducts.com

3/7

Page 4: Electronic Temperature Controller 3699A Series - … · Electronic Temperature Controller 3699A Series Selco Products Company 8780 Technology Way, Reno, Nevada 89521-590 Tel: 775-674-5100

3699A Series Specifications v1.5

ON/OFF DEFROST0nly for cooling applications.

Options

Parameter Description Unit Default Min Max

Syst - System Time Parameters

S.st Set current time H:M NA 0:00 23:59

s.hr Display Time Hour mode Option 24 12 –12 Hour

24 – 24 hour

–Ctrl Control Parameters

C.sp Current set-point

Changing set-point here

will write in non-volatile

memory.

°C

°F

5

41

Set by

C.LSP

Set by

C.USP

C.Lsp Low set-point temperature

limit

°C

°F

-20

-4

Set by

I.Slo

Setpoint

C.USP High set-point temperature

limit

°C

°F

120

248

Setpoint Set by

I.Shi

C.dif Differential for ON/OFF

control

°C

°F

4

7

2 20

C.Dt Defrost type – Timed to

activate defrost time in

certain interval or sensed

to use additional input.

Option Timed Tp t – Timed

tp S- Sensed using

input 2

C.dp Defrost Priority – Activate

defrost above compressor

output delays .

Option OFF on – On

off- Off

C.dSP Defrost set-point – Used

for sensed mode.

°C

°F

0

32

Set by

C.LSP

Set by

C.USP

C.ddf Defrost differential – Used

for sensed mode.

°C

°F

4

7

2 20

C.dit Defrost interval time –

Used for timed mode.

Interval time must be

equal or bigger to min

output time.

H:M 05:00 00:30 24:00

C.ddp Defrost dripping delay. M:S 1:00 00:00 60:00

C.dSt Defrost on start up – Will

turn on defrost on power

up.

Option OFF on – On

off- Off

–Inp1 First Input Parameters

I.Cal Calibration offset to

sensing temperature.

°C

°F

0

0

-10

-18

10

18

I.Tp Curve selection for

thermistor.

Option A Type A,B,C

–Inp2 Second Input Parameters (Defrost/Switch)

I.Fun Function of Input 2 Option Sensor Snsr – Sensor

Stch- Switch

I.Cal Calibration offset to

sensing temperature.

°C

°F

0

0

-10

-18

10

18

I.Tp Curve selection for

thermistor.

Option A Type A,B,C.

I.Stp External Switch Type Option NO NO – Normally Open

NC- Normally Close

I.Sd Switch Delay to activate

alarm.

M:S 0:10 0:00 60:00

Out1 – First Output Parameters (Compressor)

O.Otl Output minimum ON time M:S 00:01 00:00 60:00

O.Otu Output maximum ON time H:M 05:00 00:01 24:00

0.ftl Output minimum OFF time M:S 00:01 00:00 60:00

0.st Output start-up delay time. M:S 00:20 00:00 60:00

OUT2 – Second Output Parameters (Defrost Element/Alarm)

O.Fun Function of second output Option Defrost def – Defrost

alr- Alarm

O.Otl Output minimum ON time M:S 15:00 00:00 60:00

O.Otu Output maximum ON time H:M 05:00 00:01 24:00

0.ftl Output minimum OFF time M:S 00:01 00:00 60:00

0.st Output start-up delay time. M:S 00:20 00:00 60:00

–Alr Alarm Parameters

A.Lo Low alarm temperature

threshold.

°C

°F

-20

-4

Set by

I.Slo

Setpoint

A.Hi High alarm temperature

threshold.

°C

°F

120

248

Setpoint Set by

I.Shi

A.Dt Time delay to activate

alarm event

M:S 00:05 00:00 60:00

–Disp Display Parameters

D.dgs Degrees Unit used Option °F Cels – Celsius

Fahr- Fahrenheit

D.res Sensing resolution Option 0 0-with out decimal

1–with one decimal

D.sd Show degree in last digit Option ON on – On

off- Off

d.def Show Defrost - When

defrost activate will display

Defr

Option OFF on – On

off- Off

–prog Programmed Set Points

P.t1 Set current time H:M NA OFF 24:00

P.SP1 Set-point °C

°F

30

86

OFF Set by

C.USP

P.t2 Set current time H:M NA OFF 24:00

Selco Products Company

8780 Technology Way, Reno, Nevada 89521-5908

Tel: 775-674-5100 [email protected]

www.selcoproducts.com

4/7

Page 5: Electronic Temperature Controller 3699A Series - … · Electronic Temperature Controller 3699A Series Selco Products Company 8780 Technology Way, Reno, Nevada 89521-590 Tel: 775-674-5100

3699A Series Specifications v1.5

Options

Parameter Description Unit Default Min Max

P.SP2 Set-point °C

°F

30

86

OFF Set by

C.USP

P.t3 Set current time H:M NA OFF 24:00

P.SP3 Set-point °C

°F

30

86

OFF Set by

C.USP

Examples - Connection Diagrams:

Selco Products Company

8780 Technology Way, Reno, Nevada 89521-5908

Tel: 775-674-5100 [email protected]

www.selcoproducts.com

5/7

Page 6: Electronic Temperature Controller 3699A Series - … · Electronic Temperature Controller 3699A Series Selco Products Company 8780 Technology Way, Reno, Nevada 89521-590 Tel: 775-674-5100

3699A Series Specifications v1.5

TIMEROptions

Parameter Description Unit Default Min Max

Syst - System Time Parameters

S.st Set current time H:M NA 0:00 24:00

s.hr Display Time Hour mode Option 24 12 –12 Hour

24 – 24 hour

–Ctrl Control Parameters

C.dt Default timer time. H:M 0:10 0:00 24:00

C.Lt Timer upper limit. H:M 0:30 0:01 24:00

C.Ut Timer lower limit. H:M 0:05 0:01 24:00

C.iSP Idle set-point. Waiting for

timer to start.

°C

°F

30

86

OFF Set by

C.USP

C.RSP Run set-point. When timer

is running.

°C

°F

30

86

Set by

C.LSP

Set by

C.USP

C.RSP Differential for ON/OFF

control

°C

°F

4

7

2 20

C.ht Hold timer until reach

temperature.

Option Heat Heat – Reverse

Cool - Direct

C.iDt Delay after time out to

return to idle set-point.

H:M 0:05 0:01 24:00

–Inp1 First Input Parameters

I.sLo Low sensing temperature

input limit.

°C

°F

NA NA NA

I.Shi High sensing temperature

input limit.

°C

°F

NA NA NA

I.Cal Calibration offset to

sensing temperature.

°C

°F

0

0

-10

-18

10

18

I.Tp Curve selection for

thermistor.

Thermocouple type.

Option A

J

Curve A,B,C,D,E,F.

Type E,K,J

–Out1 First Output Parameters

O.Otl Output minimum ON time M:S 00:00 00:00 60:00

O.Otu Output maximum ON time H:M 05:00 00:30 24:00

0.ftl Output minimum OFF time M:S 00:00 00:00 60:00

0.st Output start-up delay time. M:S 00:20 00:00 60:00

–Alr Alarm Parameters

A.Lo Low alarm temperature

threshold.

°C

°F

-20

-4

Set by

I.Slo

Setpoint

A.Hi High alarm temperature

threshold.

°C

°F

120

248

Setpoint Set by

I.Shi

A.Dt Time delay to activate

alarm event

M:S 00:05 00:00 60:00

–Disp Display Parameters

D.dgs Degrees Unit used Option °F Cels – Celsius

Fahr- Fahrenheit

D.res Sensing resolution Option 0 0 – with out decimal

1 – with one decimal

D.sd Show degree in last digit Option ON on – On

off- Off

D.tr Timer resolution Option Sec Seconds – Display

M:S

Minutes – Display

H:M

D.tr Countdown mode Option Desc. Descending

Ascending

Examples – Connection Diagrams:

Selco Products Company

8780 Technology Way, Reno, Nevada 89521-5908

Tel: 775-674-5100 [email protected]

www.selcoproducts.com

6/7

Page 7: Electronic Temperature Controller 3699A Series - … · Electronic Temperature Controller 3699A Series Selco Products Company 8780 Technology Way, Reno, Nevada 89521-590 Tel: 775-674-5100

3699A Series Specifications v1.5

PIDNote: PID version only works for heating applications with resistive

actuator and using SSR output. (PWM)

Options

Parameter Description Unit Default Min Max

–Ctrl Control Parameters

C.sp Current set-point.

Changing set-point here

will write in non-volatile

memory.

°C

°F

5

41

Set by

C.LSP

Set by

C.USP

C.Lsp Low set-point temperature

limit

°C

°F

-20

-4

Set by

I.Slo

Setpoint

C.USP High set-point temperature

limit

°C

°F

120

248

Setpoint Set by

I.Shi

C.At Auto-tunning.

Changing to ON will start

Autotunning when

returning to normal

operation.

Option OFF OFF– 1ON - 2

C.Po Fix output

When turn on will fix the

output of the PWM and

disable PID algorithm.

Option 20 OFF 100

C.Ptp Process type.

Non-Stable (Process never

stabilize on Certain PWM).

Stable the process stabilize

on certain PWM

Option Stable Stable – ST

Non Stable - NST

C.db Actuator Dead Band Option 0.0 0.0, 0.83 ,1.66, 2.5,

3.33, 4.16, 5.0

C.sp Control response speed. Option 1.0 0.2, 0.25, 0.33, 0.5,

1.0, 2.0, 3.0, 4.0, 5.0

C.tn Control tuning type

(Robustness)

Option Normal

1

Fast -0

Normal -1

Medium – 2

Robust - 3

–Inp1 First Input Parameters

I.Cal Calibration offset to

sensing temperature.

°C

°F

0

0

-10

-18

10

18

I.Tp Curve selection for

thermistor.

Thermocouple type.

Option A

J

Curve A,B,C,D,E,F.

Type E,K,J

–Alr Alarm Parameters

A.Lo Low alarm temperature

threshold.

°C

°F

-20

-4

Set by

I.Slo

Setpoint

A.Hi High alarm temperature

threshold.

°C

°F

120

248

Setpoint Set by

I.Shi

A.Dt Time delay to activate

alarm event

M:S 00:05 00:00 60:00

–Disp Display Parameters

D.dgs Degrees Unit used Option °F Cels

Fahr

D.res Sensing resolution Option 0 0 – with

out decimal

1 – with

one

decimal

D.sd Show degree in last digit Option ON on – On

off- Off

Examples- Connection Diagrams:

Selco Products Company

8780 Technology Way, Reno, Nevada 89521-5908

Tel: 775-674-5100 [email protected]

www.selcoproducts.com

7/7