SMARTDRIVE VF1000 · L Series Instruction Manual Frequency Inverters 1.5 to 22kW stop return start enter Hz SMART CARD EN ANTRIEBSTECHNIK
Transcript
Page 1: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

SMARTDRIVE VF1000 · L Series

Instruction Manual

Frequency Inverters 1.5 to 22kW

stopreturn

startenter

VAL

Hz

SMARTC A R D

EN

ANTRIEBSTECHNIK

Page 2: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

Instruction Manualfor staticFrequency Inverters

1 x 230 V - VersionVF1207L - 1.5 kWVF1209L - 2,2 kW

Valid from Software Version V 1.5

Id.No.: 0786.21B.1 - 00Issue: June 1996

3 x 400/460 V - VersionVF1404L - 1.5 kWVF1406L - 2.2 kWVF1408L - 3 kWVF1410L - 4 kWVF1414L - 5.5 kWVF1418L - 7.5 kWVF1432L - 11 kWVF1432L - 15 kWVF1445L - 22 kW

Page 3: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-1

Dear Customer!

We should like to thank you for the trust that you have placed in us bypurchasing the Lust SMARTDRIVE Frequency Inverter.

Installation and commissioning should be carried out by trainedpersonnel. Please take the time to read the instructions carefully. Ifyou follow all the instructions, you will save yourself much time andmany questions at the commissioning stage.

Reading the instructions is essential for another reason too: incorrectuse of the equipment can damage both the inverter and also otherparts of the installation.

If after reading the instructions you still have questions, do pleasecontact us.

Lust Antriebstechnik GmbHGewerbestr. 5-9D-35633 LahnauGermanyTel: +49 6441 966 - 0Fax: +49 6441 966 - 137

Page 4: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-2

Wait 2 mins after disconnecting

!

stopreturn

startenter

A Information about the Instruction Manual

The information contained in this manual applies to all frequency invertersSMARTDRIVE VF 1000, Series L. Suffix L stands for "Large" (size of theenclosure).

This instruction manual contains 6 chapters listed under "Signpost toSuccess".

Chapter A provides information on design versions, safety information andCE acceptance procedure.

Chapters 1, 2 and 3 contain important information on commissioning.Chapters 4, 5 and 6 provide information on controlling the inverter with theuse of the KEYPAD, and the device parameters.

A number of different versions with special functions are available tomeet varying customer requirements for frequency inverters. Versi-on information which differs from standard is noted in the optiondescriptions.

For ease of use the following symbols are used to identify warnings andimportance advice:

⇒ Warning! Before opening the equipment, disconnect from the mainspower supply and wait approximately 2 minutes for the DC linkcapacitors to discharge.

⇒ Warning! It is essential that this instruction be followed.

⇒ Caution! Danger of death by electrocution.

⇒ Prohibited! Incorrect operation may cause damage to the equipment.

⇒ Settings can be changed with the KeyPad.

⇒ Useful tip

Page 5: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-3

Signposts to sucess

A Information about the Instruction Manual ..................... A-2A.1 Safety instructions ............................................................ A-4A.2 Using the inverter for the intended purpose ....................... A-5A.3 Design and accessories ................................................... A-6A.4 Inverter manufacturer's declaration ................................... A-8A.5 VF1000 Series L with CE tap .......................................... A-12A.6 Information on installation in accordance with

suppression regulations (EMC) ....................................... A-16

1 Technical Specifications ................................................ 1-11.1 Design and Layout ........................................................... 1-11.2 Data Table ........................................................................ 1-21.3 Dimensions ...................................................................... 1-51.4 Installation ........................................................................ 1-6

2 Electrical Connections ................................................... 2-12.1 Connections ..................................................................... 2-12.2 Radio Interference Suppression ........................................ 2-32.3 Power Connections ........................................................ 2-42.3.1 Mains Power Supply Connections ..................................... 2-42.3.2 Braking Chopper .............................................................. 2-52.3.3 Motor Connection ............................................................. 2-62.4 Control Connections ...................................................... 2-72.4.1 Specification ..................................................................... 2-72.4.2 Function of FSINA Reference Value Input ......................... 2-82.4.3 Control Functions using STR/STL ....................................2-102.4.4 Control Functions via S1IND/S2IND ................................. 2-112.4.5 Signal Outputs .................................................................2-132.4.6 LUSTBUS Connection ........................................................2-152.4.7 INTERBUS-S Connection ....................................................2-162.4.8 CAN-Bus Connection ......................................................2-18

3 Operating and Fault Diagnosis ...................................... 3-13.1 Operating Display ............................................................. 3-13.2 Error Messages ................................................................ 3-13.3 Warning Messages ........................................................... 3-23.4 Motor/inverter Overload Protection (I ∗ t Monitoring) .......... 3-3

Page 6: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-4

4 Using the K EYPAD KP100 ............................................... 4-14.1 Layout ............................................................................. 4-14.2 General ........................................................................... 4-24.2.1 Menu Options .................................................................. 4-24.2.2 Key Functions.................................................................. 4-24.2.3 LCD Display .................................................................... 4-34.3 Menu Structure ................................................................ 4-44.3.1 Overview ......................................................................... 4-44.3.2 MOP - Function ............................................................... 4-6

5 Parameter List ............................................................... 5-15.1 Operating Level 1 ............................................................ 5-15.2 Operating Level 2 ............................................................ 5-25.3 Inverter-Type-Dependent Parameters ............................. 5-4

6 Parameter Description ................................................... 6-16.1 Reference Value Input ...................................................... 6-16.2 Actual Values ................................................................... 6-56.3 Frequencies ..................................................................... 6-76.4 Ramps ............................................................................. 6-86.5 Characteristics ................................................................6-106.6 Special Functions ............................................................ 6-116.7 Signal Outputs .................................................................6-176.8 Program Functions ..........................................................6-18

A.1 Safety instructions

Running inverters may have live, unprotected, moving or rotating partsand hot surfaces, depending on their types of enclosure. Therefore,inverters are potentially hazardous to life.

To avoid serious injury or major damage to equipment, only suitablyqualified personnel familiar with electric drives may work on this equipment.The suitable personnel are those acquainted with installation, assembly,commissioning and operation of inverters and appropriately qualified intheir trade. They must read these instructions carefully before installationand commissioning and follow the safety instructions in detail.(IEC364, CENELEC HD 384 or DIN VDE 0100 specifications and EICReport 664 or VDE 0110 specification and the appropriate national accidentprevention regulations or the VBG4 regulations must be observed in thisconnection.)

Page 7: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-5

Repairs to the unit must be carried our by the manufacturer or serviceworkshops authorized by him. Injury or damage to property may result ifthe unit is interfered with or opened by an unauthorized person.

A.2 Using the inverter for the intended purpose

Inverters are designed for use in electrical systems or machinery.An inverter installed in a machine must not be commissioned (that is startedfor the first time) until compliance with the stipulations of the EC guidelinespecification 89.392/EEC (machine design guideline specification) isconfirmed; the requirements contained in EN 60204 must be observed.The low voltage guideline specification 73/23/EEC is applied to invertersin conjunction with the homologated prEN50178/DIN VDE 0160 seriesstandards in conjunction with EN 604391/DIN VDE 0660 Part 500 and EN60146/DIN CDE 0558. Technical data and information on powerconnections will be found on the data plate and in written documentationand must be strictly followed.

Inverters must be protected against excessive mechanical stresses. It isparticularly important to ensure that no components become distorted and/or that no insulation gaps are disturbed in transit. Inverters containcomponents sensitive to electrostatic conditions and can be easilydamaged by careless handling. Electrical components must not be allowedto suffer mechanical or any other damage.The current national health and safety regulations (such as VBG 4) mustbe observed when working on live inverters.

Electrical installation must be carried out in accordance with the relevantspecifications (e.g. cable cross-section, fuses, grounding lead connection).Further relevant information will be found in the documentation.

Electronic equipment is not inherently fail-safe. The user therefore acceptsresponsibility for ensuring that the drive reverts to a safe condition if theequipment fails.

If the inverter is used in a special environment (e.g. in an explosiveatmosphere), the standards and specifications applying to the specificapplication (e.g. EN50014 and EN 50018) must be strictly observed.

!

!

Page 8: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-6

Schnittstelle RS485 + PTC

ohne Bedieneinheit KP100

,KP0 ,OP3VF1410L ,

x H F 0 8xV F 1 x L

Output frequency up to 800 Hz

Series L

Effective direct current

Mains voltage

Unit family VF1000

A.3 Design and accessories

General informationThe standard version of the VF1000L carries this type designation withoutadditions. Variations from this standard version are marked by suffixesadded to the basic type code.Each suffix has a specific meaning; see inverter versions. Special inverterswhich are not listed are also marked by the appropriate version suffixeswhich are not shown here.

Ordering of type designation codeStandard A

Ordering of type designation codeStandard B

Type key for non-standard versionsOnly one terminal is specified for each version; it can only be occupiedonce. The number and sequence of the code suffix is free, the codes mustbe separated by a comma.

Example

interface RS485 + PTC

without control unit KP100

F 1 x x xV L

Series L

Effective direct current

Mains voltage

Unit family VF1000

Series LEffective direct currentMains voltageUnit family VF1000

Output frequency up to 800 HzSeries LEffective direct currentMains voltageUnit family VF1000

Page 9: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-7

Versions of inver ter VF1000L

Out of the versions shown, only one type can be ordered for each location(e.g. external options = 1, internal options = 3).Selection of versions available:

Location Description Type Code

1 Without KEYPAD KP100 KP03 Digital frequency reference value setting OP13 Thermistor evaluation (PTC) OP23 Interface RS485 + PTC OP33 OP1 + OP3 + external addressing OP43 3rd control input S3IND OP53 Analog ref. value setting with +/-10V OP63 OP5 + OP6 OP73 Frequency reference value for optical cable OP103 INTERBUS-S interface C13 CAN-Bus interface C2

Accessories for inverter VF1000LAccessories can be fitted restrospectively by the customer himself becausethe inverter does not need to be opened to fit them.

Description Orderingcode

General SMARTCARD, without data ZSCaccessories Control unit, incl. chip card reader KP100

Mains for VF1207L/09L END20chokes for VF1404L/06L DND6

for VF1408L, VF1410L DND10for VF1414L DND14for VF1418L DND18for VF1424L DND24for VF1432L DND32for VF1445L DND45

Sup- for VF1207L FN350-12-29pressors for VF1209L FN350-20-29

for VF1404L/06L/08L FN351-8-29for VF1410L/14L FN351-16-29for VF1418L FN351-25-33for VF1424L/32L FN351-36-33for VF1445L FN351-50-33

Page 10: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-8

A.4 Inverter manufacturer's declaration

Page 11: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-9

Page 12: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-10

Page 13: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-11

Page 14: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-12

A.5 VF1000 Series L with CE tap

Copie of the CE test report for the inverters VF1404L ... VF1414L

Page 15: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-13

Page 16: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-14

Copie of the CE test report for the inverters VF1418L ... VF1445L

Page 17: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-15

Page 18: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

A-16

A.6 Information on installation in accordance withsuppression regulations (EMC)

VF1000L series frequency inverters fulfil the low voltage guidelinespecifications and can be adapted to comply with stringent specificationsallowing them to be used within dwelling areas (except VF1424L up to45L). Their technical acceptance/approval tests were carried out underlaboratory conditions in the approved Schenk testing workshop and theresults cannot be guaranteed to apply to site conditions in a machine orplant.

The following illustration shows installation details providing optimumresults.

EMC will be achieved by providing the following measures:

Important:See Chapter 2.1 and 2.2 for further information

ZK

+

ZK

-

WVU L2L1 L3

M3

L1 L2 L33 x 380 V

K1

SI

X1

47484950

RS485

46

PE

212223242526

27282930

3132

3334353637

X2

... with screened control cable

... with screened control cable

... with screenedmain cable

... with mains filter (see Chapter 2.2)

... with screened motor cable

... with an earthed mounting plate

Frequency inverter VF1000L

MC

-Prin

t...by earthing the cable screen at the mounting

plate

... by earthing the cable screen at the

mounting plate

> 10 mm2

Center point (main ground)in the switchgear cabinet

!

Page 19: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

1-1

stopreturn

startenter

VAL

Hz

SMARTC A R D

+-

4

1

L1 L2 L3 PE

PE

U V W ZK

-Z

K+

21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

L1 N PE

PE

U V W ZK

-Z

K+

L1 L2 L3 PE PE U V W - +

8

7

11

910

15

18

14

13

12

16

3

4

5

6

2

1

17

1 Technical Specifications

1.1 Design and Layout

Key

1 DC fan connection

2 Connection for additionalbreking resistor (external)

3 LED (yellow) indicates“breakingchopper active

4 Terminal strip X1 for powerconnections VF1207L, VF1209L

5 Terminal strip X1 for power con-nections VF1404L ...VF1414L

6 Terminal strip X0 for power con-nections VF1406L ...VF1415L

7 KEYPAD control unit

8 SMARTCARD chip card

9 Socket for optional card

10 Socket for optional card

11 KEYPAD connector cable

12 Software version label

13 Terminal strip X42 forinterface RS485

14 Socket X41 for KEYPAD

15 LED H2 (green) operatingindicator

16 LED H1 (red) error indicator

17 Jumper strip X11, seereference value setting

18 Terminal strip X2 controlconnections

Page 20: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

1-2

Code Unit VF1207L VF1209L VF1404L VF1406L VF1408L

Output motor side

Recom. rating with 4 pole P kW 1,5 2,2 1,5 2,2 3 standard motor

Unit power S kVA 12,4 13,7 22,4 23,8 24,9

Phase current (100% IN) I A 16,2 19,6 23,5 25,6 27,2

Continous load - % 110

Overload factor (60 sec.) - % 150

Overload current IMAX

A 9,3 14,4 5,3 8,4 10,8

Voltage U V 3 x 0...230 3 x 0...400/460

Rotating field frequency f Hz 0...400

Frequency resolution f % 0,1 of FMAX (0,05 Hz min.)

Load type - - ohmic/ inductive

Short circuit proof - - at terminals

Leakage to earth - - at every power on

Input mains side

Mains voltage U V 1 x 230V +15/-20% 3 x 460 +10/-26%

Mains frequency f Hz 50/60 +/- 10%

Power factor A mm² 2,5

Recom. input fuse3 I AT 1 x 16 1 x16 3 x 16 3 x 16 3 x 16

Mains voltage inbalance ∆U % - 3 max.

General

Operation - - 4 quadrants

Peak break power PBrsp kW 1,6 max. 6 max.

Power loss PV W 130 140 100 100 120

Efficiency (PN) h % 95 95 95 95 96

Ambient conditions

Cooling air temparature T °C 0 ... 40

Power reduction / - - 2,5 %/°C in the range 40°C...50°Cambient temparature

Max. installation altitude a.s.l. - m 1000 m (with 5 % loss up to max. 2000 m)

Relative humidity - % 15 ... 85 non-condensing

Vibration (IEC 68-2-6) - - 2 g

Weight/dimensions

Dimensions (HxWxD) - mm 210 x 350 x 180

Weight (excl. packing) - kg approx. 6,9 kg

Protection - - IP20, VBG4, NEMA 1

Type of installation - - vertical wall mounting1 With 230V mains supply.2 With 400V mains supply (with 460V mains supply, reduce current by -15%).3 Note also the data of the local mains if mains fuse protection is provided.

1.2 Data Table

Page 21: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

1-3

Code Unit VF1410L VF1414L VF1418L VF1424L VF1432L VF1445L

Output motor side

Recom. rating with 4 pole P kW 4 5,5 7,5 11 15 22standard motor

Unit power S kVA 26,1 28,6 211,4 215,9 220,7 230,1

Phase current (100% IN) I A 28,9 212,5 216,5 223 230 243

Continous load - % 110

Overload factor (60 sec.) - % 150

Overload current IMAX A 13,5 18,8 25 34,5 45 52

Voltage U V 3 x 0...400/460

Rotating field frequency f Hz 0...400

Frequency resolution f % 0,1 of FMAX (0,05 Hz min.)

Load type - - ohmic/ inductive

Short circuit proof - - at terminals

Leakage to earth - - at every power on

Input mains side

Mains voltage U V 3 x 460 +10/-26%

Mains frequency f Hz 50/60 +/- 10%

Power factor A mm² 2,5 10

Recom. input fuse3 I AT 3 x 16 3 x 20 3 x 25 3 x 35 3 x 50 3 x 63

Mains voltage inbalance ∆U % 3 max.

General

Operation - - 4 quadrants

Peak break power PBrsp kW 6 max.

Power loss PV W 160 180 225 330 400 500

Efficiency (PN) h % 96 97 >97 >97 >97 >97

Ambient conditions

Cooling air temparature T °C 0 ... 40

Power reduction / - - 2,5 %/°C in the range 40°C...50°Cambient temparature

Max. installation altitude - m 1000 m (with 5 % loss up to max. 2000 m)

Relative humidity - % 15 ... 85 non-condensing

Vibration (IEC 68-2-6) - - 2 g

Weight/dimensions

Dimensions (HxWxD) - mm 210 x 350 x 180 210 x 350 x 272

Weight (excl. packing) - kg approx. .6,9 kg 10,1 kg 10,7 kg

Protection - - IP20, VBG4, NEMA 1

Type of installation - - vertical wall mounting

Page 22: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

1-4

FMAX = 800 Hz Code Unit VF1408L VF1410L VF1414L VF1418L VF1424L74PWM = 2 HF08 HF08 HF08 HF08 HF08

Output, motor end

Unit power S kVA 4,9 6,1 8,6 11,4 15,9

Phase current1) (100%) IN A 7,2 8,9 12,5 16,5 23

Phase current at 460 V 6,2 7,8 10,8 14,5 20

Overload current (60 sec.) 1,5xIN A 10,8 13,5 18,8 25 34,5

Overload current at 460 V 9,3 11,7 16,2 21,8 30

Rotating field frequency f Hz 0 ... 800

FMAX = 1600 Hz Code Unit VF1408L VF1410L VF1414L VF1418L VF1424L74PWM = 3 HF08 HF08 HF08 HF08 HF08

Output, motor end

Unit power S kVA 3,8 4,9 6,1 8,6 11,4

Phase current1) (100%) IN A 5,6 7,2 8,9 12,5 16,5

Phase current at 460 V 4,8 6,2 7,8 10,8 14,4

Overload current (60 sec.) 1,5xIN A 8,4 10 ,8 13,5 18,8 25

Overload current at 460 V 7,2 9,3 11,7 16,2 21,6

Rotating field frequency f Hz 0 ... 1600

Miscellaneous

Power loss (inverter) PV W 140 180 210 290 400

Mechanical data

Weight M kg approx. 6,9 10,1 10,7

Dimensions A mm 210x350x180 210x350x272

Standard units type HF08 can be set to an output frequency up toFMAX 1600 Hz. Note also the end stage cycle frequency (74PWM). Ifthe cycle frequency is to be set higher, it will be necessary to reducethe output power (see table).

Page 23: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

1-5

1.3 Dimensions

Equipment group VF1418L ... VF1445L

Equipment group VF1207L ... VF1414L

Dimensions

Equipment A B C D E F

VF1207L...VF1414L 175 5,8∅ 350 340 210 180

VF1418L...VF1445L 175 5,8∅ 350 340 210 272

All dimensions in mm

stopreturn

startenter

VAL

Hz

SMARTC A R D

A

C D

E F

B

stopreturn

startenter

VAL

Hz

SMARTC A R D

A

C D

E F

B

Page 24: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

1-6

A = 100 mmB = 20 mm

1.4 Installation

General:The location for installation must be free from conducting or corrosivematerials and also free from humidity. Frequency inverters are normallyhoused in cabinets with external air throughflow. They are attached to amounting board with four M5 screws.It is essential that the minimum distances above and below the unit areobserved to avoid heat buildup. The air openings on the top surface mustnot be covered or closed under any circumstances.Units may be mounted directly adjacent to each other horizontally, with nolimit on number.

Warning:Take care to ensure that no foreign bodies, such as metal swarf or screws,drop into the equipment, as it may be damaged beyond repair.

Installation clearances:The size of the control cabinet depends partly on the power loss of theinverter (see performance table). To avoid heat buildup in the cabinet it isessential that appropriate minimum clearances are observed. Correctinstallation will ensure a long and safe service life.

!

!

stopreturn

startenter

VAL

Hz

stopreturn

startenter

VAL

Hz

SMARTC A R D

BA

A

B

B

Page 25: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-1

nach Netz-Aus2 Minuten warten

2 Electrical Connections

2.1 Connections

Terminal connections

ZK

+

WVU NL1

M3

L1 L2/N PE1 x 230 V

K1

SI

BC

212223

242526

27282930

3132

3334353637

+24 V

FSIN

STRSTL

S1OUT

SOUTF

S2OUTS3OUT

S1INDS2IND

SOUTA

n.c.

+10 VUR

UV

X2

X1

VF1207L

KP100

RS

48550

49484746

BAGNDVDD

ZK

-VF1209L

X

X

X

Y

X41

X42

X2 Code Explanation21 UR 10 V ref. volt. for ref. value

potentiometer

22 FSIN frequency reference valueinput

23,28,30 Ground reference point,control connection

24 STR start clockwise input

25 STL start counterclockwise input

26 UV supply voltage 24 V DC

27 S1OUT prog. output HIGH active

X2 Code Explanation29 FOUTF digital frequency

output

31 S2OUT prog. output LOWactive

32 S3OUT prog. output LOWactive

33 S1IND prog. input digital

34 S2IND prog. input digital

35 n.c. not allocated

36 SOUTA prog. output analog

Page 26: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-2

nach Netz-Aus2 Minuten warten

* In the case of units VF1418L ... 1445L the earthing pin is located inthe r.h. panel.

Note:The KEYPAD control unit plugs into the 8-pin KP100 socket (seealso layout).The serial interface RS485 connects through the terminal strip X2/46...50.The terminal strip X1 is mounted directly on the mother board. Itis used in VF1404L...VF1414L and VF1207L/ 09L.The X0 terminal strip is a terminal block which is mounted on the heatsink. It is used in VF1418L ...VF1445L.

Warning:The following effective voltages from the mains must not be exceeded forall units described in this Instruction Manual:

VF1207L/1209L L1 -> L2/N 230VACL1 -> 270VAC

L2/N -> 270VAC

VF1404L bis L1 -> L2 -> L3 460VACVF1445L L1/L2/L3 -> 270VAC

X ZK

+

WVU L2L1

M3

L1 PE3 x 400/460 V

K1

SI

BC

X1

VF1404L bis 1445L

ZK

-

X

L3

L2 L3

Y

(*)

Page 27: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-3

2.2 Radio Interference Suppression

All Series L SMARTCARD frequency inverters fulfil the requirements in respectof resistance to electromagnetic interference in industrial areas as per ECGuideline Specifications/European Standard 89/336/EEC, prEN 50 062-1(see also CE Test Certificate in Chapter A).

The certified EMC test (resistance to EMC interference) for inverters wascarried out in laboratory conditions as per prEN 50082-2/01.93.

It is essential to observe the following instructions with regard tocompliance with the EMC law relating to inverters installed inmachinery:

⇒ Motor cable, mains cable and control cables must be screenedand routed separately.

⇒ The inverter unit must be bolted to a wellearthed mounting plate. A shakeproofwasher (Z) must be placed under the headof each of the fixing bolts to ensure reliablecontact at the mounting plate.

⇒ The mains cable screen must be laced tothe earthing bolt at the inverter end overthe shortest possible piece of wire (length <2.5 cm, see layout ofconnections).

⇒ Attach the motor and control cable screens on the surface of theconductive mounting plate (remove paint, as necessary) as closeto the inverter terminals as possible. Use a conductive cable forthis purpose,as shown in the drawing (X).

⇒ The interface connection screen, can be carried to the X42/46terminal. The connecting wire must be as short as possible hereas well (length: <2.5 cm).

⇒ The motor terminal box must be HF-radiation-proof. It musttherefore be manufactured from metal or metallized plastic.

⇒ Cable bushing for the motor cable at the terminal box must be ofthe conductive threaded union type with laced screening.

A mains filter must be installed as in the drawing (Y), to prevent line-related asymmetrical interference voltages.

Z

FN 351-25-33 for VF1418LFN 351-36-33 for VF1424/32LFN 351-50-33 for VF1445L

FN 350-12-29 for VF1207LFN 350-20-29 for VF1209LFN 351-8 -29 for VF1404/06/08LFN 351-16-29 for VF1410L/14L

Page 28: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-4

2.3 Power Connetions

2.3.1 Mains Power Supply Connections

General:Inverters must be connected to the mains power supply in accordancewith the VDE regulations such that they can be isolated from the mains atany time with appropriate means of isolation such as a master switch.

Warning:Never connect inverters to the mains, start or acknowledge an error whilea connected, permanently excited synchronous motor is still running.

Note:When mains power is first supplied to the inverter it first charges the internalintermediate circuit. That means that the inverter is only ready to operateafter a certain switch-on delay. Mains switch-on can therefore only berepeated at reasonably long intervals (60 sec.) . Pulsing the mains contactoris not permissible.

Warning:Because of the high leakage current (> 3.5 mA) in general the use of FIprotective switches alone is not permitted. A protective ground is thereforemandatory.

Mains fuses must be designed to suit the current load of the connectingcable to DIN 57100 (see recommendations in the Power Table).

VF1207L/9L connectionThe mains power connection (1 x 230 V) is via terminals X1/ L1, L2/N, .For technical specifications see Data Table.

Warning!Never connect 400/460 V to terminals X1/L1 and X1/N. The excessivevoltage would destroy the equipment.

VF1404L... VF1414L connectionThe mains power connection (3 x 400/460V) is via terminals X1/ L1, L2,L3, . For technical specifications see Data Table.

VF1418L ... VF1445L connectionThe mains power connection (3 x 400/460V) is via terminals X0/ L1, L2,L3, . For technical specifications see Data Table.

!

Page 29: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-5

2.3.2 Braking Chopper

General:If the rotor speed is higher than the corresponding stator speed, the motorreturns energy to the inverter. In this mode the motor is braked by theinverter. The internal braking chopper converts the regenerative brakingenergy into heat in a load resistor.

All SMARTDRIVE inverters in the 2.2 kW - 22 kW range are fitted with aninternal braking chopper. For technical specifications see power table.

Accessories:To ensure interference-free braking operation even in dynamic applicationsit is sometimes necessary for an additional external braking resistor to befitted, depending on the braking energy level to be dissipated.

Warning:The braking resistor must not be of a lowervalue than RBr = 90 Ω. The brakingresistor becomes very hot and allassemblies in its vicinity must be installedat a suitable distance.

For connection see diagram.

It also the possibility of connecting anexternal braking chopper For specialapplications eg. BC2300 or BC3000.The length of cable between the inverterand the braking chopper (intermediate DCcircuit) must not exceed 2 m.

L1 L2 L3 PE

PE

U V W ZK

-Z

K+

21 22 23

RBr

- +L1

L2/NRL

Wait 2 mins after disconnecting

Page 30: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-6

Wait 2 mins after disconnecting

2.3.3 Motor Connection

GeneralStandard three-phase motors in the range up to 4 kW are produced inaccordance with IEC34 for various mains supplies in Delta (3∗230 V) andin Star (3∗400 V) formats.Standard three-phase motors in the range above 4 kW are produced inaccordance with IEC34, for various mains supplies in Delta (3∗400 V) andin Star (3∗660 V) formats

Information on connecting special three-phase motors which do notcomply with the IEC34 standard must be obtained from the motormanufacturer.

To comply with electromagnetic suppression regulations, the motor terminalbox must be HF-radiation-proof. Therefore, it must be manufactured eitherfrom metal or metallized plastic.Cable bushing for the motor cable at the terminal box must be of theconductive threaded union type with laced screening.

VF1207L/9L connectionThe motor is connected at terminals X1/ , U, V, W.The motor connection must be Delta (3∗230 V).

VF1404L ... VF1410L connectionThe motor is connected at terminals X1/ , U, V, W.The motor connection must be Star (3∗400 V).

VF1414L connectionThe motor is connected at terminals X1/ , U, V, W.The motor connection must be Delta (3∗400 V).

VF1418L...1445L connectionThe motor is connected at terminals X0/ , U, V, W.The motor connection must be Delta (3∗400 V)..

W2

U1

U2

V1

V2

W1

Delta

W2

U1

U2

V1

V2

W1

Stern

W2

U1

U2

V1

V2

W1

Delta

W2

U1

U2

V1

V2

W1

Delta

Page 31: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-7

stopreturn

startenter

stopreturn

startenter

2.4 Control Connections

2.4.1 Specification

Specification

10 V ± 2%, not short circuit proofload up to 2 mA

24 V ± 10%, short circuit proofload up to 200 mA

cascading serveral inverters possible usingvoltage ref. value,resolution 10 BIT, deviation ± 1,5%, softwarefilter up to 50 ms

Schmitt trigger input, LOW < 4 V, HIGH > 5 V(max.10 V), 0...1 kHz, 0... 10 kHz, pulse widthmin. 10 µs, deviation ± 8%, ± 0,8%, softwarefilter up to 50 ms

Low < 3 V, High > 8 V (max. 30 V), currentconsumtion (at 24 V) = 10 mA max., SPScompatible, +24 V logic to ground, hardwarefilter 3,3 ms, software filter 1x polling cycle

LOW pulse, LOW level approx. 1V, pulsepause ration 1:1, 6 times output frequency,at rest HIGH = 24 V

output voltage 10 V, 50% overrange,load (up to 10 V) = 8 mAload (10...15 V) = 5 mAnot short circuit proof, resolution 10 BIT

S1OUT = driver output, functionprogrammable, short circuit proof,load max. 80 mA, HIGH active

S2OUT/S3OUT = open collector output, notshort circuit proof, load = 50 mA max., LOWactive, intern. pulled with 10 kΩ above 24 V,LOW level < 4,5V

Connection

Referenceoutput UR

Power supplyoutput UV

Frequencereference valueinput FSIN (analog)

Frequencyreference valueinput FSIN (digital)

Digital controlinputs STR, STL,S1IND, S2IND

Digital frequencyinput SOUTF

Analog inputSOUTA

Digital controloutput S1OUT,S2OUT, S3OUT

Page 32: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-8

212223

+10 VX2

4

1

A

X11

4

1

21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

X11

1. Connection of a potentiometer(4,7... 10 kΩ)

X11 matching:Position A

04-FSSEL = 0 factory setting04-FSSEL = 2 with cable break safeguard

2. External voltage reference value0(2)...10 V DC

X11 matching:Position A: 0... 10 VPosition D: 0... 2 VPosition E: 2... 10 V04-FSSEL = 0 factory setting

3. External current ref. value0(4)...20 mA

X11 matching:Position B: 0... 20 mAPosition C: 4... 20 mA

04-FSSEL = 0 factory setting

Position of jumper strip X11

2.4.2 Function of FSINA Reference Value Input

Setting analog frequency reference value FSINAThe three-phase frequency is set using terminal X2/22. The input ismatched to the specific type of drive at jumper strip X11. There are threepossibilities:

Note:For a given direction of rotation the inverter can also be started from thefrequency reference value input.

FS > 0,5 Hz → START

FS < 0,25 Hz → STOP

212223

X2

4

1

D

X114

1

A

X114

1

E

X11

+-

212223

X2

4

1

B

X114

1

C

X11

+-

Page 33: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-9

212223

X2

4

1

A

X11

212223

X2

4

1

A

X11

stopreturn

startenter

In addition to FSINA input matching using jumper strip X11 the equipmentsoftware provides matching facilities using the KEYPADs or the interface.Parameter 04-FSSEL (frequency reference value selector) determinesthe origin of the frequency reference value (see table). See also parameterdescription.

04-FSSEL Function0 analog input active, matching via X111 FSIN as pulse input direct active, ramp and

filter functions switched off*2 analog input with cable break safeguarding active3 FSIN as frequency input 0 - 1 kHz active4 FSIN as frequency input 0 - 10 kHz active5 FSIN as PWM input 20 - 100% active6 FSIN as PWM input 0 - 100% active7 FSIN not active, reference value via KP100 (CTRL-menu)8 Reference value set via interface

9 - 16 For setting the reference value, see Chapter 6, Page 6-417 - 22 correction of analog reference value via S1IND/S2IND

(motor potentiometer function) active23 inverted PWM input: 100% => FMIN, 20% => FMAX

*Hardware option required, please contact us for further details

Setting the digital frequency reference value FSINA(F)

1. Setting external freq. ref. value0...1kHzScaling: FMIN → FMAX 0 . . . 1 kHz04-FSSEL = 3Amplitude: 10 V max.Pulse width: 10 µs min.

2. Setting external freq. ref. value0 ... 10 kHzScaling: FMIN → FMAX

0 . . . 10 kHz 04-FSSEL = 4

Amplitude: 10 V max.Pulse width: 10 µs min.

stopreturn

startenter

Page 34: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-10

!

2.4.3 Control Functions using STR/STL

Mains switching with STL/STRFor safety reasons the inverter must not be switched on to the mainssupply using the preset control function STL or STR. The start functiononly recognises the inverter when it has been activated after power on orself test.The choice of direction of rotation is made by inputs STR or STL usingtwo switching contacts as shown on the connection plan. Alternatively thechoice of direction of rotation may also be made using two external volt-age signals in accordance with the control connection details.

STARTThe inverter starts when both a control signal STL or STR and a referencevalue for the three-phase frequency of at least 0.5 Hz = 0.1 V are presentat FSIN.

STOPThe inverter stops when the control signals STL or STR have beendiscontinued. The motor which is connected coasts on uncontrolled withoutany braking.

BRAKE/STOPThe inverter brakes the motor to a STOP when two control signals arepresent at STL and STR. A fresh start occurs when one of the two controlsignals is set to zero.

REVERSINGThe direction of rotation reverses when the control signal is changed fromone control input (eg. STL) to the other control input (eg. STR).The overlap interval must be at least 8 ms .

Truth table

STL STR Explanation

0 0 STOP, motor coasts1 0 START, counterclockwise with RACC/RDEC0 1 START, clockwise with RACC/RDEC1 1 STOP

0 1 Reverse direction of rotation

1 0

242526

+24 VSTRSTL

X2

Page 35: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-11

stopreturn

startenter

2.4.4 Control Functions via S1IND/S2IND

Choice of fixed frequencies FF2, FF3, FF4In addition to the FSINA input the frequency design of value can also bepreset using control inputs S1IND/S2IND as a fixed frequency. There is achoice of three fixed frequencies which are activated in accordance withthe Truth Table.The truth table relates to factory setting Parameter 31-KSEL = O (Dataset selector).

Truth Table

S1IND S2IND Explanation Range Factory Setting

0 0 FSINA-Input Active* 0 to 999 Hz FMAX = 50 Hz1 0 FF2-Fixed Freq. Active 0 to 999 Hz FF2 = 3 Hz0 1 FF3-Fixed Freq. Active 0 to 999 Hz FF3 = 15 Hz1 1 FF3-Fixed Freq. Active 0 to 999 Hz FF4 = 30 Hz

*Note setting of 04-FSSEL

Sequence Diagram

The number of fixed frequencies may be extended by FF5, FF6 and FF7.These may be selected by using the optional control input S3IND (OP5).The required option card is available to order.

FSINA

FF2FF3

FF3FF4

STL

STR

S1IND

S2IND

0

f

f

t

Page 36: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-12

Dataset SwitchingThe inverter has two data sets which can be switched using the controlinput SIIND/S2IND. Each data set has a total of eight parameters whichmay be set individually (see Parameter Description).

The Truth Table relates to Parameter 31-KSEL = 2 (Data Set Selector)

Truth Table

S1IND S2IND Explanation Data Set0 0 FSINA-input active 1 active1 0 FF2-1 fixed freq. active 1 active0 1 FSINA-input active 2 active1 1 FF2-2 fixed freq. active 2 active

Ramp SwitchingThe data set switching facility means that the inverter also has 2 ramppairs. The function of ramp switching is shown by the following sequencediagram (where 31-KSEL=2). For further information see ParameterDescription

Sequence Diagram

stopreturn

startenter

STL

STR

S2IND

0

f

t

RACC2

RACC1

RDEC2

RDEC1

Page 37: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-13

26X1

3132

S2OUTS3OUT+ 24 V

stopreturn

startenter

2.4.5 Signal Outputs

Ready Signal S1OUT (driver output HIGH active)The output becomes inactive (relays drops off) in the case of mains orcable failure or inverter breakdown. The relay pulls in again when the faultis rectified and the mains supply is reset.

2728

S1OUT X1

Frequency Limit Value S2OUT (Open Collector Output LOW active)The indicator output is active (relay pulls in) when the rotating fieldfrequency exceeds the programmed value of the fixed frequency 25-FF5(WE=3 Hz) (F>FF5).

Frequency Reference V alue reaches S3OUT(Open Collector Output LOW Active)The Output becomes active when the rotating field frequency reaches theprescribed frequency reference value FS (F=FS ± 0.5Hz).

Programming:All three outputs can be set using the KEYPAD or the interface to one of10 different functions. The function description refers to the following factorysettingsParameter 62-S1OUT = 1Parameter 63-S2OUT = 7Parameter 64-S3OUT = 7

For further information see Parameter Description.

Page 38: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-14

3637

SOUTA X1

2930

FOUTF

400 X1

0

U/V

t/s

24

stopreturn

startenter

Digital Frequency Output SOUTFThe output SOUTF supplies 24 V pulses. For each 1 Hz rotating fieldfrequency 6 low pulses are fed to the frequency output.

FSIN SOUTF< 5 Hz 30 Hz constant5 - 260 Hz 30-1560 Hz linear> 260 Hz 1560 Hz constant

ProgrammingThe SOUTA and SOUTF outputs may be programmed for additionalfunctions using the KEYPAD or the interface. Parameter 61-SOUTA canbe set using either output. In addition Parameter 69-KOUTA can be usedfor scaling the analog output SOUTA.

Factory Setting: 61-SOUTA = 969-KOUTA = 100%

For further information see Parameter Description.

Analog Output SOUTAThe output works in the basic setting as an analog frequency output. Itprovides a DC voltage which is proportional to the output of the outputfrequency of the inverter.

SOUTA Explanation0 V F = 0 Hz10 V Inverter Start, F= FMAX>10 V Inverter Start, F= MAXF

Page 39: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-15

KP100

RS

48550

49484746

BAGNDVDD

X41

X42

2.4.6 LUSTBUS Connection

GeneralStandard inverters VF1000 Series L have a floating interface connectionRS485. Inverters can be controlled through this interface in accordancewith the LUSTBUS data transmission protocol.

Terminal connections:

An external 24V DC supply (VDD) isrequired to operate the interface.

Technical Data:

Code RS485

Voltage supply, ext. VDD 24 VDC ±10%

Current consumption I Transmitting 100 mA, Receiving 20 mA

Isolation - Galvanic function separation

Driver output - 31 participators, distance < 1000 m

Transmission rate - variable 9600, 4800 or 2400 Baud

Isolation - as per VDE 0884, protection low voltage

Page 40: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-16

+-

4

1

ZK

-

ZK

+

21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

ZK

+

U V W - +

A

E

54

53

C

2.4.7 INTERBUS-S Connection (C1)

GeneralThe C1 version of the VF1000 inverter Series L has an INTERBUS-S coupling(IBS) with external 24V feed and a local bus interface. The inverter can becontrolled through this interface in accordance with the INTERBUS-S datatransmission protocol.

Layout:

An external 24V DC supply isrequired to operate the interface.Terminal 54 = +24 VDC inputTerminal 53 = ground

A = IBS output, 15-pinSub D socket strip X51

E = IBS input, 15-pinSub D pin strip X52

C = IBS option print

Screening is laced through theplug housing.

Connections:

11

12

13

14

15

5

6

7

8

-

1

2

9

10

3

4

RC

SLO

CKO

CRO

DO

SLI

CKI

CRI

DI

Uv0

Uv0

COM

COM

+5V

RBST

RC

SLO

CKO

CRO

DO

SLI

CKI

CRI

DI

Uv0

Uv0

COM

COM

11

12

13

14

15

5

6

7

8

-

1

2

9

10

-

D-SUB 15 pin, socket IBS output D-SUB 15 pin, plug IBS input

X52X51

Page 41: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-17

Technical Data

Code VF1000 L, I NTERBUS-S

Power supply, external VDD 24 VDC ±10%

Current consumption I 120 mA max.

Interface - Local bus

Module Ident. No. - 195

Data - Data words through process datachannel (control word and Data -speed reference value) as perDRIVECOM specification

- PCP Data

Page 42: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-18

+-

A

E

C

2.4.8 CAN-BUS Connection (C2)

General:

The C2 version of the inverter VF1000 Series L can have a CAN-Buscoupling (CAN). The bus interface is isolated.The bus is connected by two 9-pin Sub-D plug-in connectors as per CiADraft Standard 102.V2.0.This inverter can be operated by a CAL protocol in a network.

Layout:

An external 24V DC supply isrequired to operate the interface.Connection by means of a D-Subplug.

A = CAN output,9-pin Sub D socket strip X61

E = CAN input,9-pin Sub D pin strip X62

C = CAN-Bus option print

Screening is laced through the plughousing.

Connections:

* Address preset, alternatively through DIP switches on options board (donot wire up if not required).

1

6

2

7

3

8

4

9

5

+5v

GND CAN

CAN_L

CAN_H

GND

ADR2*

ADR0*

+24V

ADR1*

1

6

2

7

3

8

4

9

5

D-SUB 9 pin, socket CAN output D-SUB 9 pin, plug CAN input

+5v

GND CAN

CAN_L

CAN_H

GND

ADR2*

ADR0*

+24V

ADR1*X61 X62

Page 43: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-19

Allocating device addresses:

a) using a parameterb) using DIP-switches on the CAN-Bus option print (see drawing)c) using a coded plug ( Adresses 0 ... 7)

DIP5 DIP4 DIP3 DIP2 DIP1 Adress- - ADR2 ADR1 ADR0

0 0 0 0 0 0

0 0 0 0 1 1

0 0 0 1 0 2

: : : : : :

0 1 0 0 0 8

: : : : : :

1 1 1 0 1 29

Note: DIP6 ...8 are without any significance.

Nr. Function

1 CAN-output-input

2 CAN-Bus option print

3 DIP-switch fordevice addresses

CAN

12

34

56

78

ON

2

1

3

Page 44: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

2-20

Technical Data

Code VF1000 L, CAN-Busto ISO 11898

Number of participants 30, maximum

Power supply, external VDD 24 VDC ±10%

Stromaufnahme I 100 mA max.

Current consumption - up to 1 M bauds

Transmission and Time on the Time in theprocessing speeds bus inverter

Control command andsubsequent status scan

- for 1 inverter 0,3 ms 8 ms

- for 30 inverters 9 ms 8 ms

Setting parameters

- for 1 inverter 0,15 ms approx. 30ms

- for 30 inverters 4,5 ms approx. 30 ms

Page 45: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

3-1

4

1

21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

H2

H1

3 Operation and Fault Diagnostics

3.1 Operation Display

H1 H2 Meaning Location of LEDs:

Power off, no function H1 = yellow

Power is switched on, self-test after H2 = greenapprox. 0.5 s., inverter ready

inverter is started

Overload protection,I∗t-monitoring active

Switch-off on error, see H1 flashingfor cause Chapter 3.2

3.2 Error Messages

H1 Error Condition / Solution /flashes Cause Comment

1 time E-CPU Error in CPU Switch off mains power supplyand switch on again (Reset)

2 times E-OFF Power switched off flashes until U DC linkor undervoltage < 150V (VF12xxL)

< 300V (VF14xxL)

3 times E-OC Over current switch Check drive/motor cableoff, short-circuit

4 times E-OV Over voltage, motor Check power/driveregenerative mode

5 times E-OLM Motor overloaded, Check drive / motor /I∗t switch-off ventilation

6 times E-OLI Inverter overloaded Check drive/ventilationI∗t switch-off

7 times E-OTM Motor temperature Only possible if thermistortoo high protection option fitted

8 times E-OTI Inverter temperature Inverter overloaded, checktoo high installation conditions

9 times E-EEP Error in EE-PROM Switch off mains supply andswitch on again

Hold start/enter key down for at least 3 seconds to reset.

Page 46: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

3-2

3.3 Warning Messages(no reaction from the unit to errors)

VF1000 control error

ATT1 Changing parameters in online operation (with the motorrunning) is not allowed.

ATT2 Controlling the motor through the KEYPAD in online operationis not allowed.

ATT3 Access to Lust SMARTCARD in online operation is not allowed.ATT4 The system is in error status. Control through the KEYPAD

is not allowed.ATT5 Motor data for a selected function, e.g. I ∗ R compensation,

must be complete.ERROR Invalid pass word

Reset error by holding down the start/enter key.

Fehler bei S MARTCARD- Betrieb

ERR91 SMARTCARD is write-protected.ERR92 Error in the plausibility check.ERR93 SMARTCARD not readable, wrong inverter/servo regulator type.ERR94 SMARTCARD not readable, parameters not compatible.ERR96 Connection to SMARTCARD interrupted.ERR97 SMARTCARD data invalid (CS test)ERR98 Insufficient memory space on SMARTCARD (only MC6000)

Reset error by holding down the start/enter key.

Support:If you should happen to experience difficulties in installing the frequencyinverter, we shall be pleased to assist you as necessary. You can contactour specialists at the following address:

Lust Antriebstechnik GmbH Telephone: ++49 6441/966111Gewerbestraße 5-9 Fax No.: ++49 6441/966137D-35633 Lahnau / Germany

Page 47: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

3-3

Programming:The parameter 59-ITRIP is used for setting the I∗t tripping current. Thismeans that currents < IN (rated device current) can be set. Consequently,motors of lower power than the rated device current can be protectedeffectively from overload. Factory setting:

59-ITRIP = IN (rated device current)

3.4 Motor/Inverter Overload Protection (I ∗∗∗∗∗ t Monitoring)

I ∗ t monitoring provides electronic motor protection and inverter protectionagainst high thermal loads. The triggering characteristic is shown in thediagram. The details refer to an output frequency of 50 Hz.It should be noted that during continuous operation with frequencies < 40Hz the motor requires forced cooling.

General rule:Within any 10 minute period, with a continuous current of I = 1.5 ∗ IN (150%overload), an overload of 1 minute is permissible.

Exception: Maximum overload VF1445L = 120%

Diagram:Line A = VF1445L, Line B = all other inverter types

B

A

stopreturn

startenter

Page 48: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

4-1

4 Using the KP100 KEYPAD

4.1 Layout

stopreturn

startenter

VAL

Hz

SMARTC A R D

2

4

35

6

7

1

Item Code Function1 LCD-Display 140 segments, backlit green/red2 Down arrow key Scroll back within the menustructure3 Up arrow key Scroll forwards within the menu structure4 Stop/Return key Stop (menu CTRL) Exit or leave selected

menu5 Start/Enter key Start (menu CTRL) Confirm or Select menu6 SMARTCARD Chipcard data store, storage of device

settings7 Connecting cable Maximum length 0.30m

Dimensions and Weight

Code Unit KP100Dimensions WxHxT mm 62x158x21Weight g 100Protection VBG4, IP20Ambient Temperature °C 0 ... 40

Page 49: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

4-2

4.2 General

4.2.1 Menu Options

After power on the device carries out a selftest (display backlit red).

The VF1000 then goes straight to the current value of the output frequency(display backlit green).

The menu option VAL is active. By tapping the Stop/Return key twice thedisplay will change to menu and opens up the selection of other menuoptions.

stopreturn

startenter

stopreturn

startenter

stopreturn

startenter

stopreturn

startenter

4.2.2 Key Functions

The arrow keys are used for selectingmenu options and specific parametersand enable changes to be made tothem.

Tap them once and move to the nextmenu option or parameter or thesmallest increment in a parametervalue.

If a key is held down it will scrollautomatically and stop when the key isreleased. The Stop/Return key is usedfor leaving the menu options for exitfrom parameter changes (old value isretained).

The start/enter key is used for callingup menu options or parameters andstoring changes.

.

VAL = Display Actual Values

PARA = Change Parameter Setting

CTRL = Control Motor using KEYPAD

CARD = Load device settings/store with SMARTCARD

PARA CTRL CARDVAL

Page 50: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

4-3

4.2.3 LCD Display

Item Description Function

8 Counterclockwise Monitoring display for outputCounterclockwise active

9 Clockwise Monitoring Display for output rotating field,Clockwise active

10 Acceleration Monitoring Display, active duringRamp acceleration

11 Braking Ramp Monitoring Display, active during braking

12 3-digit Display 7 Segment Display for actual values,parameter numbers

13 VAL Menu Display actual values e.g. frequencyvoltage, current

14 PARA-Menu Change Parameter Setting

15 CTRL-Menu Control Motor by KEYPAD

16 CARD-Menu Load device setting/store with SMARTCARD

17 Physical Unit to Shows % V, A, VA with automaticItem 20 allocation

18 Physical Unit to Shows h, min-1 (rpm) with automaticItem 20 allocation

19 Physical Unit to Shows Hz, s, Hz/s with automaticItem 20 allocation

20 5-digit display 15-segment display for parameter namesand values

21 Barchart Shows formula characters and physicalunit to item 22

22 10 position Shows parameter values, frequency,Barchart display voltage, apparent or effective currents

PARA CTRL CARDVAL

%VAhmin-1Hz/s

1213

14

20

21

8 9 10

11

1516

17

18

19

22

Page 51: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

4-4

4.3 Menu Structure

4.3.1 Overview

Menu VAL (actual value) selected Menu PARA selected

Display actual value, Select parameter e.g. FMIN1with arrow key change to

Next actual value parameter Change Parameter settingin off-line mode (Inverter stop)

Detect new actual value Read Parameter setting inoff-line mode (Inverter start)

B

A

C

D

VAL

VAL

Hz

VAL

V

VAL

V

startenter

startenter

stopreturn

stopreturn

PARA

PARA

Hz

PARA

Hz

PARA

Hz

startenter

startenter

startenter

stopreturn

A

B

C

D

Page 52: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

4-5

Menu CTRL (Control Motor via Load/store menu device settingKEYPAD) selected using the SMARTCARD (SC)

Enter password READ = Load device setting from SCFactory Setting = 573 WRITE = Save device setting to SC

LOCK = write protect SCUNLCK = remove write protect

Enter Frequency Reference Start selected functionValue (KEYPAD ) e.g. (10 Hz ) with start/enter key

Activation of Motor Potentiometer Function completed error freefunction (see next page)

A

B

C

D

CTRL

CTRL

CTRL

Hz

startenter

startenter

startenter

stopreturn

CARD

CARD

CARD

CARD

startenter

startenter

startenter

stopreturn

stopreturn

MOP-Function(motor operatedpotentiometer)

A

B

C

D

Page 53: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

4-6

The motor potentiometer function is reacti-vated with the start/enter key

CTRL

CTRL

Hz

CTRL

Hz

startenter

CTRL

Hz

CTRL

Hz

stopreturn

From overviewCTRL-Menü

to overviewCTRL-Menü

4.3.2 MOP - Function

After password confirmation the control ter-minal is blocked. The pre-set frequency ref-erence value (KEYPAD) may be for example 10Hz. Start inverter by tapping the start/enterkey.

Actual value (small display) and direction ofrotation clockwise are also indicated.

Increase speed reference value with arrow keyto e.g 50 Hz.

Inverter follows with acceleration ramp in-crease.

Reduce speed reference value using arrowkeys.

Inverter follows with braking ramp for decel-eration. At < 0.0 Hz the inverter changes thedirection of the rotating field.

Increase speed reference value (counter-clockwise) to e.g. 10Hz.

Prefix (--) also shows counterclockwise direc-tion

Press stop/return key and release. Inverterbrakes the motor to a stop.

Page 54: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

5-1

5 Parameter List5.1 Operating Level 1

Display parameters

Code Name Unit Display range Page Factory Clientsetting setting

Actual values

10-G Scaled frequency - 0 to 65535 6-512-F Output frequency Hz 0,0 to 999,0 6-513-U Output voltage V 0 to 460 6-514-IS Apparent current A 0,0 to 52,0 6-515-IW Effective current A 0,0 to 52,0 6-516-PW Effective power W 0 to 22000 6-517-UZK DC link voltage VDC 0 to 900 6-518-TIME Switch on time after reset h 0,0 to 960,0 6-619-TOP Operating hours h 0 to 60000 6-6Device Data

91-TYPE Inverter type - 15 types possible 6-1892-REV Software version - - 6-18 See inside cover95-ERR1 Last error - 0-0,0 to 9-1,5 6-18

11-0,0 to 11 -1,5

Commissioning parameters

Code Name Unit Setting range Page Factory Clientsetting setting

1-MODE Operating mode - 0 to 3 6-1 1Frequencies

20-FF2-1 Fixed frequency 2 Hz 0,0 to 999,0 6-6 321-FMIN1 Minimum frequency Hz 0,0 to 999,0 6-6 022-FMAX1 Maximum frequency Hz 4,0 to 999,0 6-6 5023-FF3 Fixed frequency 3 Hz 0,0 to 999,0 6-6 1524-FF4 Fixed frequency 4 Hz 0,0 to 999,0 6-6 3025-FF5 Comparison frequency Hz 0,0 to 999,0 6-6 3

for S2OUTRamps

32-RACC1 Acceleration ramp 1 Hz/s 0,1 to 999,0 6-7 2033-RDEC1 Delay ramp 1 Hz/s 0,1 to 999,0 6-7 2036-RSTOP STOP delay ramp Hz/s 0,0 to 999,0 6-8 0Characteristics

41-V/FC U/F selector - 1 and 4 6-8 142-VB1 Start voltage (Boost 1) % 0,0 to 25,0 6-9 *43-FN1 Rated frequency Hz 15,0 to 960,0 6-9 5044-VN1 Rated voltage V 220,0 to 460,0 6-9 *

* depends on inverter type

Page 55: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

5-2

5.2 Operating Level 2

Code Name Unit Setting range Page Factory Clientsetting setting

Reverence value input

4-FSSEL Frequency reference - 0 to 23 6-1 0value selector

Actual values

9-BARG Bar chart - 6 actual values 6-4 13-UFrequencies

20-FF2-1 1st fixed frequency 2 Hz 0.0 to 999.0 6-6 321-FMIN1 Minimum frequency Hz 0.0 to 999.0 6-6 022-FMAX1 Maximum frequency Hz 4.0 to 999.0 6-6 5023-FF3 Fixed frequency 3 Hz 0.0 to 999.0 6-6 1524-FF4 Fixed frequency 4 Hz 0.0 to 999.0 6-6 3025-FF5 Comparison freq. S2OUT Hz 0.0 to 999.0 6-6 326-FF6 Control frequency Hz 0.0 to 999.0 6-6 027-FF2-2 2nd fixed frequency 2 Hz 0.0 to 999.0 6-6 528-FMIN2 Minimum frequency 2 Hz 0.0 to 999.0 6-6 029-FMAX2 Maximum frequency 2 Hz 4.0 to 999.0 6-6 5030-FF7 Fixed frequency FF7 Hz 0.0 to 999.0 6-6 50Ramps

31-KSEL Data set selector - 0 to 3 6-7 032-RACC1 Acceleration ramp 1 Hz/s 0.1 to 999.0 6-7 *33-RDEC1 Delay ramp 1 Hz/s 0.1 to 999.0 6-7 *34-RACC2 Acceleration ramp 2 Hz/s 0.1 to 999.0 6-8 *35-RDEC2 Delay ramp 2 Hz/s 0.1 to 999.0 6-8 *36-RSTOP STOP delay ramp Hz/s 0.0 to 999.0 6-8 *Characteristics

38-THTDC Switch-off delay s 0.0 to 120.0 6-8 039-VHTDC DC hold voltage % 1 to 25 6-8 441-V/FC U/F selector - 1 and 4 6-8 142-VB1 Start voltage (Boost 1) % 0.0 to 25.0 6-9 *43-FN1 Rated frequency 1 Hz 15 to 960 6-9 5044-VN1 Rated voltage 1 V 220.0 to 460.0 6-9 *45-VB2 Start voltage (Boost 2) % 0.0 to 25.0 6-9 *46-FN2 Rated frequency 2 Hz 15 to 960 6-9 50

* depends on inverter type

Note:To set all editable parameters to factory setting, set the 71-PROG parameter to 1 andacknowledge the parameter change by pressing the start/enter key ("wait" message).

Page 56: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

5-3

Code Name Unit Setting range Page Factory Clientsetting setting

Special functions

48-IXR I∗R compensation - 0 to 3 6-10 049-SC Slip compensation - 0 to 2 6-11 050-IN Motor rated current A 3.0 to 45.0 6-11 *51-COS Power factor x100 % 0 to 100 6-11 8252-NN Motor rated speed RPM 0 to 24000 6-11 *53-KIXR Correction factor for - 0.0 to 30.0 6-12 *

I∗R compensation54-KSC Correction factor for % 0.0 to 20.0 6-12 *

slip compensation55-ISEL Current controller selector - 0 to 5 6-12 056-ILIM Current limit A 5 to 52 6-13 *57-FILIM Minimum decrease Hz 0.0 to 999.0 6-13 15

frequency58-RILIM Delay ramp for current Hz/s 0.1 to 999.0 6-13 50

control59-TRIP I∗t monitoring A 3.5 to 43,0 6-14 *Signal outputs

61-SOUTA Frequency/analog output - 0 to 14 6-15 162-S1OUT Output 1 digital - 0 to 10 6-15 163-S2OUT Output 2 digital - 0 to 10 6-15 764-S3OUT Output 3 digital - 0 to 10 6 -15 767-FST Filter time constant - 0 to 4 6-16 269-KOUTA SOUTA scaling % 0 to 200 6-16 100Program functions

71-PROG Special programs - 0 to 2 6-16 072-START Start options - 0 to 7 6-17 074-PWM Switching frequency - 0 to 2 6-18 *86-KG Scaling factor for 10-G - 0 to 1000 6-18 087-DISP Continously stored actual - all display 6-18 12-F

value display parameters88-PSW1 Password 1 <PARA> - 0.0 to 999.0 6-18 089-PSW2 Password 2 <CTRL> - 0.0 to 999.0 6-18 57394-MAXF Absolute max. freq. Hz 0.0 to 999.0 6-19 0

* depends on inverter type

Page 57: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

5-4

5.3 Inverter-Type-Dependent Parameters

Code Code Unit Factory Page Inverter typesetting

42-VB1 % 4 6-9 VF1207L, VF1209L,VF1404L,VF1406L,VF1408L, VF1410L, VF1414L

42-VB1 % 3 6-9 VF1418L, VF1424L42-VB1 % 2 6-9 VF1432L,VF1445L45-VB2 % 4 6-9 VF1207L, VF1209L, VF1404L, VF1406L,

VF1408L, VF1410L, VF1414L45-VB2 % 3 6-9 VF1418L, VF1424L45-VB2 % 2 6-9 VF1432L, VF1445L44-VN1 V 220 6-9 VF1207L, VF1209L44-VN1 V 380 6-9 VF1404L bis VF1445L47-VN2 V 220 6-9 VF1207L, VF1209L47-VN2 V 380 6-9 VF1404L bis VF1445L50-IN 59-TRIP A 6,8 6-11 VF1207L50-IN 59-TRIP A 9,5 6-11 VF1209L50-IN 59-TRIP A 3,9 6-11 VF1404L50-IN 59-TRIP A 5,6 6-11 VF1406L50-IN 59-TRIP A 6,8 6-11 VF1408L50-IN 59-TRIP A 8,9 6-11 VF1410L50-IN 59-TRIP A 12,5 6-11 VF1414L50-IN 59-TRIP A 16,5 6-11 VF1418L50-IN 59-TRIP A 23 6-11 VF1424L50-IN 59-TRIP A 30 6-11 VF1432L50-IN 59-TRIP A 43,5 6-11 VF1445L52-NN UPM 1480 6-11 VF1207L, VF1209L,VF1445L52-NN UPM 1420 6-11 VF1404L, VF1406L, VF1408L52-NN UPM 1430 6-11 VF1410L52-NN UPM 1440 6-11 VF1414L52-NN UPM 1450 6-11 VF1418L52-NN UPM 1460 6-11 VF1424L, VF1432L

Note:To set all editable parameters to factory setting, set the 71-PROG parameterto 1 and acknowledge the parameter change by pressing the start/enterkey ("wait" message).

Page 58: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

5-5

Code Code Unit Factory Page Inverter typesetting

53-KIXR - 5 6-12 VF1207L, VF1209L, VF1404L, VF1406L,VF1408L

53-KIXR - 3,5 6-12 VF1410L53-KIXR - 2,5 6-12 VF1414L53-KIXR - 1,8 6-12 VF1418L53-KIXR - 1,1 6-12 VF1424L53-KIXR - 0,6 6-12 VF1432L53-KIXR - 0,4 6-12 VF1445L54-KSC % 5 6-12 VF1207L, VF1209L54-KSC % 6,5 6-12 VF1404L, VF1406L, VF1408L54-KSC % 5,7 6-12 VF1410L54-KSC % 4,8 6-12 VF1414L, VF1418L54-KSC % 3,2 6-12 VF1424L54-KSC % 1,6 6-12 VF1432L, VF1445L56-ILIM A 9,3 6-13 VF1207L56-ILIM A 14,25 6-13 VF1209L56-ILIM A 5,3 6-13 VF1404L56-ILIM A 8,4 6-13 VF1406L56-ILIM A 10,2 6-13 VF1408L56-ILIM A 13,5 6-13 VF1410L56-ILIM A 18,75 6-13 VF1414L56-ILIM A 24,75 6-13 VF1418L56-ILIM A 34,5 6-13 VF1424L56-ILIM A 45 6-13 VF1432L56-ILIM A 54,75 6-13 VF1445L

Page 59: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-1

6 Parameter Description

O1-MODE Operating Mode [decimal]MODE determines the control options of the inverter and the operatinglevel for the KP100 KEYPAD.

The parameters are divided into three operating levels. Level 1 containsthe most important parameters for installation. Level 2 in addition to chang-ing level 1 also contains parameters for access to other parameters andspecial functions and control functions, for example data set switching orprogramming the control outputs.Level 3 is reserved for interface parameters (SIO-Operation) and specialparameters. Please contact us for further details.

01-MODE = 1 -> Operator Level 1 Installation level01-MODE = 2 -> Operator Level 2 Special and control functions01-MODE = 3,0 -> Operator Level 3 SIO - Operation via interface

6.1 Reference Value Input04-FSSEL Frequency reference value selectorProvides the choice between various types of reference value (analog,frequency or PWM signal) and their means of input (KEYPAD, SIO...).

04-FSSEL Function

0 Analog input active, matching via X11

1 FSIN as pulse input direct active, ramp and filter functionsswitched off *

2 Analog input with cable break safeguarding active

3 FSIN as frequency input 0 to 1 kHz active

4 FSIN as frequnecy input 0 to 10 kHz active

5 FSIN as PWM input 20 to 100% active

6 FSIN as PWM input 0 to 100% active

7 FSIN not active, reference value via KP100 (CTRL-menu)

8 Reference value set via interface

9 - 16 For setting the reference value, see Chapter 6, Page 6-4

17 - 22 Correction of analog reference value via S1IND/S2IND (motorpotentiometer function) active

23 Inverted analog input: 10V => FMIN, 0V => FMAX

04-FSSEL = 0Input FSIN is active as an analog input. Adjustment to 0(2)...10V or0(4)...20 mA via jumper strip X11.

Page 60: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-2

Block Diagram Reference Value Input

0

2

3

4

5

1

6

7

17...22

23

04-FSSEL

FF2

FF3

FF4

FF5

FF6

FF7

FMAX

S1

IND

1 0 (0)

0 1 (0)

1 1 (0)

0 0 (1)

1 0 (1)

0 1 (1)

1 1 (1)

0 0 (0)

S2

IND

(I

N5

)

A

stopreturn

startenter

VAL

Hz

SMARTC A R D

M

67-FST 29-FMAX2

0 Hz

28-FMIN221-FMIN1

94-MAXF22-FMAX1

20...100%

0...100%

67-FST

D

100...20%

8...16

*only version OP5

Page 61: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-3

0

U/V

t

10

tp

T

F = (FMAX * k)+FMIN

k = Ttp

FMAX -> k = 1FMIN -> k = 0 (04-FSSEL = 6)FMIN -> k = 0,2 (04-FSSEL = 5)

04-FSSEL = 1FSIN input operates as direct frequency input. The frequency signal fed inswitches the output rotating field without delay. That means that the start-ing and braking ramps and also the frequency range (FMIN/FMAX) aredetermined externally.

Warning: This function switches off all the limits which protect the device.Feeding in an incorrect signal can overload the drive or damage it.

04-FSSEL = 2Input FSIN is active as an analog input with cable break safeguardingspecially for potentiometer use. In the case of cable break the inverterbrakes the motor to STOP.

04-FSSEL = 3Input FSIN operates as frequency input.FMIN = 0 Hz FMAX = 1kHz

04-FSSEL = 4Input FSIN operates as frequency inputFMIN = 0 Hz FMAX = 10kHz

04-FSSEL = 5Input FSIN operates as pulse input for pulse width modulated signal.FMIN = 20% PWM FMAX = 100% PWM(see diagram)

04-FSSEL = 6Input FSIN operates as pulse input for pulse width modulated signalFMIN = 0% PWM FMAX = 100% PWM(see diagram)

!

Page 62: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-4

04-FSSEL = 7Input FSIN is not active. When the motor potentiometer function is startedusing the CTRL menu of the KEYPAD, 04-FSSEL = 7 is automatically setand on leaving it again is reset to 04-FSSEL = 0.

04-FSSEL = 8Input FSIN and KEYPAD input are not active. The reference can only be setexternally via the interface.

04-FSSEL = 9The reference value is set to the value from 20-FF2-1 or 27-FF2-2 (notedata record changeover 31-KSEL). Input FSIN is not active.

04-FSSEL = 10The reference value is set to the value from 23-FF3. Input FSIN is not active.

04-FSSEL = 11The reference value is set to the value from 24-FF4. Input FSIN is not active.

04-FSSEL = 12The reference value is set to the value from 25-FF5. Input FSIN is not active.

04-FSSEL = 13The reference value is set to the value from 26-FF6. Input FSIN is not active.

04-FSSEL = 14The reference value is set to the value from 21-FMIN1 or 29-FMIN2 (notedata record changeover 31-KSEL). Input FSIN is not active.

04-FSSEL = 15The reference value is set to the value from 22-FMAX1 or 29-FMAX2 (notedata record changeover 31-KSEL). Input FSIN is not active.

04-FSSEL = 16The reference value is set to the value from 30-F7. Input FSIN is not active.

04-FSSEL = 17Input FSIN active (basis reference value). The design reference valuecan be increased continuously using S1IND and reduced continuouslyusing S2IND (reference value offset with motor potentiometer function).

04-FSSEL = 18This has the same function as 04-FSSEL = 17 but with the following ad-dition:If S1IND and S2IND are both activated simultaneously the referencevalue is reset to the basic reference value (reference value offset = 0).

04-FSSEL = 19This has the same function as 04-FSSEL = 18 with the following additions:With the reference value offset and power off this offset is stored until it ischanged or reset using S1IND or S2IND.

Page 63: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-5

04-FSSEL = 20This has the same function as 04-FSSEL = 18 and 19.

04-FSSEL = 21This has the same function as 04-FSSEL = 18 with the following addition:When the inverter stops the reference value is reset to the base referencevalue (reference value offset = 0).

04-FSSEL = 22This has the same function as 04-FSSEL = 18 and 21.

04-FSSEL = 23The input FSIN operates as an inverted analog input10V = FMIN 0V = FMAX

6.2 Actual Values

09-BARG Barchart Display [Decimal]The following parameters can be displayed in the barchart display.

09-BARG Function Code

STAT Display as bit pattern see Fig. 1

12-F Output frequency as analog bar < F >

13-V Output voltage as analog bar < V > Factory setting

14-IS Apparant current as analog bar < I >

15-IW Effective current as analog bar < I >

SIN Display as bit pattern see Fig. 2

Fig. 1 Fig. 2

VAL

Hz

ABCD

VAL

Hz

EFGH

A -> Reference value achivedB -> 12-F > 23-FF5C -> Current limit value achieved IS > 110% IN

D -> Regenerative current

E -> S1IND activeF -> S2IND activeG -> S1OUT activeH -> S2OUT active

Page 64: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-6

( ) ( ) ( )16 3 15 13− = ∗ − ∗ −PW IW V

10-G Scaled FrequencyShows the current output frequency 12-F multiplied by the factor fromparameter 86-KG. No decimal places or physical units are displayed.

(10-G) = (12-F) ∗ (86-KG)

12-F Output Frequency [Hz]Displays the current output frequency. After a switch off on error the actualvalue present immediately before switch off is stored (hold function).

13-V Output Voltage [V]Displays the current output voltage. The output voltage is held constantindependent of the DC voltage if there is a control reserve present (DCcompensation). After a switch off on error the actual value presentimmediately before switch off is stored (hold function).

14-IS Phase Current [A]Displays the current phase apparent current. After a switch off on errorthe actual value present immediately before switch off is stored (holdfunction).

15-IW Effective Current [A]Displays the current phase effective current. After a switch off on error theactual value present immediately before switch off is stored (hold function).

16-PW Effective CurrentDisplays the effective power produced by the inverter.

17-VZK Intermediate Circuit Voltage [VDC]Displays the current intermediate circuit voltage (DC). After a switch off onerror the actual value present immediately before switch off is stored (holdfunction).

18-TIME Time on since reset [0.1 H]Displays time on since the last time the mains supply was switched on.

19-TOP Operating Hours [h]Displays the total operating hours. The maximum value of the operatinghour counter is 60000. When it reaches this value it remains unchanged.

Page 65: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-7

6.3 Frequencies

20-FF2-1 Fixed Frequency FF2-1 [Hz]Parameter of first data set.Selectable as reference value using S1IND = 1 and S2IND = O

21-FMIN1 Minimum frequency for analog ref. value setting [Hz]Parameter of first data set. Setting reference value FSIN=0(2) V or 0(4)mA corresponds to an output frequency of FMIN.

22-FMAX1 Maximum frequency for setting analog ref. value [Hz]Parameter of first data set. Setting reference value FSIN=10Vor 20 mA corresponds to an output frequency of FMAX. In Version OP5 itcan be selected via S1IND = 0. S2IND = 1 and S3IND = 1 (additional inputon options card).

23-FF3 Fixed Frequency FF3 [Hz]Selectable as reference value using S1IND = 0 and S2IND = 1

24-FF4 Fixed Frequency FF4 [Hz]Selectable as reference value using S1IND = 1 and S2IND = 1

25-FF5 Fixed frequency FF5 [Hz]Frequency threshold for programmable output S1OUT and S2OUT andS3OUT (see also 62-S1OUT, 63-S2OUT, 64-S3OUT)

26-FF6 Fixed Frequency FF6 [Hz]Frequency threshold for data set switching where 31-KSEL = 1. In VersionOP5 it can be selected via S1IND = 0. S2IND = 1 and S3IND = 1 (additionalinput on options card).

27-FF2-2 Fixed Frequency FF2-2 [Hz]Parameter of second data set. Selectable as reference value usingS1IND = 1 and S2IND = 0

28-FMIN2 Minimum frequency for setting analog ref. value (Hz)Parameter of second data set (see also 21-FMIN1)

29-FMAX2 Maximum frequency for setting analog ref. value (Hz)Parameter of second data set (see also 21-FMAX1)

30-FF7 Fixed frequency FF7 [Hz]Can be selected as a reference value via 04-FSSEL = 16. In Version OP5it can be selected via S1IND = 0. S2IND = 1 and S3IND = 1 (additionalinput on options card).

Page 66: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-8

6.4 Ramps

31-KSEL Data Set SelectorThe data set selector determines the control value for data set switching.Possible control values for data set switching are:

31-KSEL Function Application example

0 Data set switchung inactive, Standard, factory setalways data set 1

1 Switching to second data set Heavy load startwhen 12-F > 26-FF6

2 Switching of data set using Alternate use of 2 motorsS1IND and S2IND on one inverter

3 Switching to second data set for Drive with load dependingcounterclockwise operation on direction of rotating(STL active)

Two data sets are available with the following parameters.

Parameter Data set 1 Data set 2

Minimum frequency 21-FMIN1 28-FMIN2

Minimum frequency 22-FMAX1 29-FMAX2

Fixed frequency 2 20-FF2-1 27-FF2-2

Acceleration ramp 32-RACC1 34-RACC2

Braking ramp 33-RDEC1 35-RDEC2

Voltage rise 42-VB1 45-VB2

Rated voltage 44-VN1 47-VN2

Rated voltage 43-FN1 46-FN2

32-RACC1 Acceleration Ramp [Hz/s]Parameter of first data set

33-RDEC1 Deceleration Ramp [Hz/s]Parameter of first data set

32-RACC2 Acceleration Ramp [Hz/s]Parameter of second data set

33-RDEC2 Deceleration Ramp [Hz/s]Parameter of second data set

Page 67: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-9

Ramp setting without data record changeover (31-KSEL=0)

Ramp setting with data record changeover (31KSEL = 1.2 or 3)

36-RSTOP Stop Ramp [Hz/s]When the stop ramp (36-RSTOP > 0) is activated the inverter executes adeceleration ramp of gradient 36-RSTOP after setting the control inputsSTR and STL to 0. A subsequent DC current hold is possible using 38-THTDC > 0. If 36-RSTOP = 0 the motor coasts on when STL and STR areset to 0.

f

RACC1

0t

Page 68: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-10

6.5 Characteristics

38-THTDC DC Current Hold Switch Off Delay [s]DC current hold is active after the value has dropped below the switch offcurrent (F < 0,5Hz). Braking can be from 33-RDEC1 or 36-RSTOP. Thehold time can be set to a value up to 120 seconds. Continuous hold is notpossible.

39-VHTDC DC Current Hold Voltage Level [%]The output voltage for DC current hold can be set using parameter 39-VHTDC as a % of the rated voltage of the device.

41-V/FC Characteristic Selector [Decimal]

41-V/FC = 1 -> linear voltage frequency characteristics4 -> quadratic voltage frequency characteristics

See also the diagrams on the right.

42-VB1 Voltage Rise [%]Parameter of first data set. Voltage at frequency at 0 Hz. Rise in torque instart up range.See also diagrams below.

43-FN1 Rated Frequency [Hz]Parameter of first data set. Frequency at which the inverter achieves therated output voltage (setting of 44VN1).See also diagrams below.

44-VN1 Rated Voltage [V]Parameter of first data set. Initial setting of voltage which the invertershould have attained when it reaches 43-FN1.See also diagrams below.

45-VB2 Voltage Rise [%]Parameter of second data set. See 42-VB1.See also diagrams below.

46-FN2 Rated Frequency [Hz]Parameter of second data set. See 43-FN1.See also diagrams below.

47-VN2 Rated Voltage [V]Parameter of second data set. See 44-VN1.See also diagrams below.

Page 69: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-11

0

U/UN

F

1

VB

FN

4

41-V/FC = 1 41-V/FC = 4

6.6 Special Functions

48-IXR I ∗ R Compensation On/Off [Decimal]

48-IXR = 0 -> I∗R Compensation inactive1 -> I∗R Compensation with first and second data set active2 -> I∗R Compensation with only first data set active3 -> I∗R Compensation with only second data set active

Condition for activation of I∗R compensation: enter motor data (on typeplate) 50-IN, 51-COS and 52-NN for the load characteristics.

The aim of I∗R compensation is to produce constant torque and reduceheating of the motor windings. This is achieved when the load character-istics as determined by the characteristic parameters are displaced by anamount ∆∆∆∆∆U which depends on the effective current. See Figure A.

IW = 15-IW (effective current)IN = 50-IN (motor rated current)COS = 51-COS (cosϕ motor)KIXR = 53-KIXR (correction factor)

0

U/UN

F

1

VB

FN

∆U IW IN COS KIXR= − ∗ ∗( )

Page 70: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-12

I∗R Compensation begins from frequency VB∗FN. It increases in a linearfashion: from 0% of frequency VB∗FN through to 100% at frequency2∗VB∗FN. Beyond that it is 100%. See Figure B.

A -> IW > rated current (rated load)B -> IW = 0 (free speed)C -> non-compensated line

2*VB*FN

0

100%

FNVB*FN10 20 30 40 50 F/Hz

50%

I*R SK

Figure B

Proportion of I ∗ R compensation (I ∗ R)Proportion of slip compensation (SK)

0

U/UN

F

1

VB

FNVB*FN

A

B

C

Figure A

Page 71: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-13

∆FKSC IW

IFN

NU=

∗∗

49-SC Slip Compensation On/Off [Decimal]

49-SC = 0 -> Slip compensation inactive1 -> Slip compensation active with first and second data set2 -> Slip compensation only active with first data set only

Condition of activation of the Slip compensation:Enter Motor data (type plate) 50-IN, 51-COS and 52-NN.Slip compensation is intended to maintain the speed constant irrespec-tive of the load. In the basic setting range 0-FN a frequency ∆∆∆∆∆F which isproportionate to the effective current (15-IW) is added to the actual fre-quency (12-F).

In the field weakening range this ∆∆∆∆∆F is further corrected by the factorF/FN. The frequency increase calculated in this way is not displayed inthe parameter 12-F.

Slip compensation starts at VB*FN. It increases in linear fashion from 0%at frequency VB ∗ FN to 100% at frequency 2 ∗ VB ∗ FN. Beyond that it is100%. See p. 50 Fig. B.

The increase in frequency is only limited by parameter 94-MAXF. Fre-quency correction is produced by the formula:

In the basic setting rangeIW = 15-IW (effective current)INU = Inverter rated currentFN = 43-FN1(rated frequency)KSC = 54-KSC (correction factor)F = 12-F (actual frequency)

In the field weakening range

50-IN Motor Rated Current [A]Motor rated current from motor type plate.Used in I ∗ R compensation and slip compensation

51-COS Rated-cos ϕϕϕϕϕ [%]Cosj from motor type plate (enter as %).Used in I ∗ R compensation and slip compensation.

52-NN Rated Speed (RPM)Rated speed from motor type plate.Used in I ∗ R compensation and slip compensation.

∆FKSC IW

I

F

FNFN

NU=

∗∗ ∗

Page 72: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-14

!

[ ]KSCn n

n

I

I COS

SYN N

SYN

UN

N

=−

⋅⋅

⋅100 %

53-KIXR I ∗ R Compensation, Correction Factor [Decimal]The KIXR correction factor corresponds to the resistance measured be-tween the two motor lines. The correction factor can either be entered, ormeasured from the inverter.

Measurement starts when 48-IXR = 1 and 53-KIXR = 0The inverter then produces a maximum 1/16th of the device rated voltagefor approximately two seconds or allows a current of maximum 50-IN (en-tered rated current of motor) to flow. The measured value is automaticallystored under 53-KIXR.

Warning:During this measurement the motor shaft may turn slowly.

54-KSC Slip Compensation, Correction Factor [%]The correction factor 54-KSC is scaled like the motor rated slip to thedevice rated current.

nSYN = Synchronous speednN = 52-NN (motor rated speed)IUN = Inverter rated currentIN = 50-IN (motor rated current)COS = 51-COS (cos ϕ)

The correction factor can either be entered or calculated from the inverter.Calculation starts when 49-SC = 1 and 54-KSC = 0.The synchronous speed for the calculation is determined from the ratedfrequency 43-FN1. The calculated value is automatically stored under54-KSC.

55-ISEL Current Regulation Selector [Decimal]The current regulation selector determines the type of current limit valueregulation. The control value is the phase apparent current 14-IS.

55-ISEL Function

0 Current limit value control inactive

1 Acceleration/braking ramp current control, retun to rampfunctian at I>125 ILIM

2 Acceleration/breaking ramp current control, ramp stop atI >125% ILIM

3 Current injection*

4 As 1 but with current injection*

5 As 2 but with current injection*

*Further details upon request.

Page 73: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-15

100%

75%

125%

FSIN

FILIM

12-F 56-ILIM

tRACC

RILIM

RACC

12-F

14-IS

Current controlled acceleration (55-ISEL = 1)After the inverter starts, the motor is accelerated with 32-RACC1. Accel-eration reduces on reaching the current limit 75% of 56-ILIM. If the phasecurrent 14-IS continues increasing and exceeds 100% of 56-ILIM, themotor is not accelerated any further. If the current limit 125% of 56-ILIM isexceeded the rotating field frequency set with FSIN is reduced to the mini-mum reduction frequency 57-FILIM using ramp 58-RILIM. As the phasecurrent reduces below 100% of 56-ILIM, the inverter accelerates the mo-tor again using ramp 32-RACC1 and the same applies in the case of brak-ing (See diagram).

Current controlled acceleration (55-ISEL = 2)Function as above but with the following difference:After exceeding the current limit 125% of 56 ILIM the ramp 32-RACC1does not accelerate any further. There is no reduction in frequency.

Current controlled acceleration (55-ISEL = 3/4/5)Further information is available on request.

Diagram to show current controlled acceleration.

56-ILIM Current limit value [A]See 55-ISEL and diagram57-FILIM Minimum reduction frequency for current control [Hz]See 55-ISEL and diagram.58-RILIM Ramp for current control [Hz/s]See 55-ISEL and diagram.

Page 74: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-16

59-ITRIP I ∗∗∗∗∗ t Monitoring (Motor) Trigger Current [A]

Parameter 59-ITRIP sets the I ∗∗∗∗∗ t trigger current. When this current isexceeded, switch off occurs after a pre-set triggering time (see diagram)with error message E_OLM.

Motor ProtectionThe setting of the I ∗∗∗∗∗ t triggering current must correspond with the ratedcurrent of the motor. This ensures that lower power motors than the ratedequipment are also adequately protected against overload.

Quite apart from parameter 59-ITRIP the inverter has an I ∗∗∗∗∗ t monitoring(device) which corresponds to setting to 59-ITRIP = device rated currentand switching off with error message E_OLI.

Factory setting:59-ITRIP = IN (device rated current)

Diagram:Line A = VF1445L, Line B = all other inverter types.

B

A

Page 75: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-17

6.7 Signal Outputs

61-SOUTA Analog/Frequency Output

61-SOUTA Function

0/2/7/ No function, output SOUTA, SOUTF = 08/10/11

1 WE SOUTA = 0...10V => FMIN...FMAX proportional outputfrequency, FOUTF = 0

3 SOUTF = 6 x the output frequency,SOUTA = 0

4 SOUTA = 0...10 V => apparent current scaled to100% device rated current, SOUTF= 0

5 SOUTA = 0...10 V => effective current scaled to100% device rated current, SOUTF= 0

6 SOUTA = 0...10 V =>effective power scaled to100% device rated power, SOUTF = 0

9 SOUTA as 61-SOUTA= 1, SOUTF as 61-SOUTA= 3

12 SOUTA as 61-SOUTA= 4, SOUTF as 61-SOUTA= 3

13 SOUTA as 61-SOUTA= 5, SOUTF as 61-SOUTA= 3

14 SOUTA as 61-SOUTA= 6, SOUTF as 61-SOUTA= 3

62-S1OUT Programmable control output S1OUT [Decimal]63-S2OUT Programmable control output S2OUT [Decimal]64-S3OUT Programmable control output S3OUT [Decimal]

6_-S_OUT Function (62-S1OUT,63-S2OUT,64-S3OUT)

0,9 No function, output S_OUT = 0

1 Active as soon as the inverter is connected to themain power supply an there are no errors

2 Active as long as the motor is excited

3 Active as longh as counterclockwise > 0 or DC-hold active

4 Active as long as clockwise >0 or DC-hold active

5 Active as long as rotating field frequency 12-F = 0

6 Active as soon as the reference value is achieved

7 Active when rotating field frequency 12-F > 25-FF5

8 Active when apparent current 14-IS > 110%59-TRIP current limit reached

10 Active after switch off on error

Factory setting: 62-S1OUT ->1, 63-S2OUT -> 7, 64-S3OUT -> 7

Page 76: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-18

6.8 Program Functions

67-FST Filter Time Constants [Decimal]This determines the filter time constants for analog reference value inputFSIN (see also 04-FSSEL). Time characteristics as PT-element (low pass).

67-FST Function

0 0 ms

1 8,2 ms

2 24,6 ms, factory setting

3 57,4 ms

4 123 ms

69-KOUTA Factor for Analog Output 61-SOUTA [Decimal]This parameter is used for scaling the analog output SOUTA.The voltage of an analog signal output is multiplied by the factor69-KOUTA and limited to 10V in accordance with programming of61-SOUTA.On output of a PWM signal the pulse duty factor output is multiplied by thefactor 69-KOUDA and limited to 100% in accordance with the61-SOUTA programming.

71-PROG Special Programs [Decimal]71-PROG is used for activating special programs. Special programs cur-rently available:

71-PROG Function

0 No special program active

1 Reset to factory setting (after entering 71-PROG=0)

2 Changed allocation of control terminalsSTR = 0 -> clockwise, STL = 1 -> STARTSTR = 1 -> counterclockwise, STL = 0 -> STOP

72-START Start Options [Decimal]

72-START Funktion

0 No start option active, factory setting

1 Auto start after power on with STL or STR bridged

2 Synchronisation to running motor

3 Auto start and synchronisation

4 Direction block: counterclockwise blocked

5 Direction block and auto start

6 Direction block and synchronisation

7 Auto start, synchronisation and direction block

Page 77: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-19

Auto start 72-START = 1If one of the start contacts STL or STR is bridged and the reference valueinput FSIN > 0,5 Hz, the inverter starts automatically when the main supplyis restored.

Synchronisation 72-START = 2After activating the start contact, the inverter first searches for the currentmotor speed. It starts by searching for maximum frequency 22-FMAX1which means that the inverter is running faster than synchronisation speed.This causes a positive effective current to flow. The rotating field frequencyis reduced until the effective current becomes negative so that the in-verter is running at below synchronised speed. In this way the invertersynchronises to the motor speed found with the appropriate rotating fieldfrequency.Synchronisation functions in both directions.

Direction Block 72-START = 4This start option blocks counterclockwise rotation of the inverter absolutely.In this case counterclockwise can be activated neither using control inputSTL nor from the CTRL-menu.

74-PWM Switching frequency [decimal]The parameter 74-PWM determines the switching frequency of the finalstages. The inverter output current must be reduced if the switchingfrequencies > factory setting.

74-PWM Switching freq. Phase current 100% Equipment2* 7,8 kHz 6,2 A VF1207L3 15,6 kHz 6,2 A2* 7,8 kHz 9,5 A VF1209L3 15,6 kHz 8,5 A2* 7,8 kHz 3,8 A VF1404L3 15,6 kHz 3,8 A2* 7,8 kHz 5,6 A VF1406L3 15,6 kHz 5,6 A2* 7,8 kHz 7,2 A VF1408L3 15,6 kHz 7,2 A2* 7,8 kHz 8,9 A VF1410L3 15,6 kHz 7,2 A2* 7,8 kHz 12,5 A VF1414L3 15,6 kHz 7,2 A2* 7,8 kHz 16,5 A VF1418L3 15,6 kHz 11,3 A1* 3,9 kHz 23,0 A VF1424L2 7,8 kHz 23,0 A3 15,6 kHz 15,6 A1* 3,9 kHz 30,0 A VF1432L2 7,8 kHz 25,4 A3 15,6 kHz 15,4 A0* 1,9 kHz 43,5 A VF1445L1 3,9 kHz 33,5 A

* Factory setting

Con

tinuo

us 1

10%

pha

se c

urre

nt is

per

mitt

ed.

Page 78: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

6-20

86-KG Scaling Factor for 10-GThe factor determines the value of the display parameter 10-G inaccordance with the formula:

(10-G) = (12-F) ∗ (86-KG)

87-DISP Continuous Display [Decimal]87-DISP determines the parameter for continuous display. All parameterson the VAL menu are possible.

88-PSW1 Password 1 [Decimal]Determines the password for parametering <PARA> menu

89-PSW2 Password 2 [Decimal]89-PSW2 determines the password for control from the KEYPAD CTRLmenu.

91-TYPE Inver ter Type [Decimal]91-TYPE returns the type of the final stage which has been recognised.All the MIN and MAX values and factory settings of the voltage and cur-rent values which are given as absolute values depend upon this param-eter. e.g. VF1209L - 44-VN1 = 220 V Factory Setting

VF1406L - 44-VN1 = 380 V Factory Setting

92-REV Software Version [Decimal]This returns the software version in use (see page 2).

94-MAXF Absolute Maximum Frequency [Hz]This is the maximum frequency which the inverter can produce. The pa-rameter is used for setting frequency reference values, current limit valueregulation, slip compensation and synchronisation to a running motor. Ifthis parameter is set to 0 the limit is switched off.

95-ERR1 Error 1 [Decimal 0.1s]Stores the latest error message number - error - time (after each reset,max. 1.5 hours). Possible error messages:

Number Meaning1-1.5 Error in processor2-1.5 Undervoltage (no entry in 95-ERR1 ÷ 98-ERR4)3-1.5 Overcurrent, short circuit or short circuit to

ground after power on4-1.5 Overvoltage5-1.5 I ∗ t motor6-1.5 I ∗ t inverter7-1.5 Overtemperature motor8-1.5 Overtemperature inverter9-1.5 Error in EEPROM

Acknowledge errors by pressing the start/enter key and holding it down for at least3 seconds.

Page 79: EN Frequency Inverters 1.5 to 22kW - LTI Motion · Frequency Inverters 1.5 to 22kW stop return start enter VAL Hz SMART CARD EN ANTRIEBSTECHNIK. Instruction Manual for static Frequency

Technical modifications reserved Id.No.: 0786.21B.1 - 00 EN 6/96