® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 1 01.09.17
Energi Savr Node QS Phase Adaptive Fixture ControllerThe Energi Savr Node QS family is a group of modular products for the control of lighting loads. This product is compatible with Quantum and QS systems.
Features
•Automaticallyselectsleading-edgeortrailing-edge dimming for incandescent / halogen, electronic/magnetic low-voltageandneon/coldcathodelightsources.
•ControlsdimmableCFL/LEDloads.RefertoLutronP/N 048478 on www.lutron.com for compatibility with dimmableCFL/LEDlightsources.
•RTISSEquippedtechnologycompensatesforincomingline-voltagevariations(upto±2%changeinfrequency/second)suchaschangesinRootMeanSquare(RMS)voltage,frequencyshifts,harmonicsandline noise.
•RTISS-TEoperatesonthetrailingedgeoftheACsine wave. This allows for true instantaneous voltage compensation.
QSNE-4A-D
Note:MultipleQSMscanbeaddedtoincreasethenumber of wireless inputs and Pico wireless controllers.
LUTR
ON
LUTR
ON
R
LUTRON
LUTR
ON
RH
M
L
QSNE
-4A-D
DIN
Rai
l Pow
er M
odul
e
230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657
InputS1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
DefOption
Notes: 1 Uptofourwiredinputstotal(ofanytype).2 See"OutputZoneRatings"in"Specifications"section,forspecificloadtyperatings.
QSLink
Energi Savr Node QS unit
Energi Savr Node QS Phase Adaptive
unit
Energi Savr Node Programming Interface seeTouch
QS Wallstation
WiredIR Receiver1IR
Transmitter
WiredDaylight Sensor1
Wired Occupancy Sensor1
EmergencyContactClosureInputUp to 100 total QS devices
220-240V~ ControlPower
800WAdaptiveload2
500WAdaptiveload2
500WAdaptiveload2
500WAdaptiveload2
Fourmulti-function inputs that accept
multiple sensor types
Wireless Communication
QS Sensor Module(QSM)
QS Power Supply
RadioPowrSavrOccupancy Sensor (upto10perQSM)
RadioPowr SavrDaylightSensor(upto 10perQSM)
Pico Wireless Controller(up to10perQSM)
Wired Daylight Sensors
Wired Occupancy
Sensors
Wired IRReceivers
IR Transmitter
IECPELV/NECR Class2DryContactSwitch(byothers)1
H
M
L
QSNE
-4A-D
DIN
Rai
l Pow
er M
odul
e
230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657
InputS1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
DefOption
System Example
•Unitis12DINmodules(216mm)wide.•Fourmulti-functioninputscompatiblewiththefollowing:
– Daylightsensors – Occupancy sensors – IRreceivers – IECPELV / NEC®Class2drycontactswitches
•Providesairgapoff(whenallzonesareoff).•Integralprotectionforcommontemporaryover- currentandover-voltageconditions.
•LEDsonfrontofunitprovidediagnosticinformation.•IncludesQSlinkforseamlessintegrationoflights
and controls.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 2 01.09.17
Specifications
Power
•220–240V~50/60Hz
•10Amaximumtotalinputcurrent
•LightningstrikeprotectionmeetsANSI/IEEEstandard62.31-1980.Canwithstandvoltagesurgesofupto 6000Vandcurrentsurgesofupto3000A.
•24V-132mA,4PDUssupplied
Regulatory Approvals
•IEC/EN60669-2-1•CEmarked•LutronQualitySystemsregisteredtoISO9001.2008
Environment
•SeeMountingsectionforthermalspecifications•Relativehumidity:lessthan90%non-condensing•Forindooruseonly
Output Zone Ratings
•No Deratingisrequiredifalltheconditionsbelowaremet: –Calibrationpointmaximumis70ºC –Roomambienttemperatureisbetween0ºCand30ºC –Panelambienttemperatureisbetween0ºCand50ºC
•100 W Deratingisrequiredonallzonesforasinglemoduleinasinglenon-ventilatedDINenclosureif: – The room ambient temperature is between 30ºCand40ºC.
•200 W Deratingisrequiredonallzonesformultiple rownon-ventilatedDINenclosureif: – The room ambient temperature is between 30ºCand40ºC.
Output Zone Ratings (continued)
•Eachzonehasnominimumloadrequirement.
•Automaticallyselectsleading-edgeortrailing-edgedimmingorcanalsobemanuallyconfiguredforaspecificloadtype.
•Internalrelayprovidesanairgapoffwhenallzonesare off.
•Oneloadtypeperzone.
•Outputmustnotbeusedtocontrolreceptacles.
•Outputmustbedirectlyconnectedtotheload.ContactLutronforapplicationswithloadsidebreakers.
•Runaseparateneutralforeachloadcircuit.Acommonneutral connection is not recommended.
•MaximumwirelengthbetweentheEnergiSavrNodeunitandtheloadmustbelessthan30.5m.
•UnitmaybepoweredbyGroundFaultInterrupter(GFI)orResidualCurrentCircuitBreakerwithOverload(RCBO)protectedcircuitifrequired.Loadcircuitwiring(frombreakertounittoload)mustberuninitsownnon-metallic conduit, or nuisance tripping may occur.
•Forapplicationsrequiring0–10V-control,useTenVoltInterface(GRX-TVI)ortheQSNE-4T10-D.
•Forapplicationsrequiringhigherwattageratings,useapowerbooster(NGRX-PB,NGRX-ELVI,NGRX-FDBI).
Each zone is rated for the following wattage and load types A, B:
Load TypeZone 1 Rating Zone 2, 3 and 4 Rating (per zone)
No Derating 100 W Derating
200 W Derating
No Derating 100 W Derating
200 W Derating
Incandescent/Halogen 800 W 700 W 600W 500 W 400 W 300W
ElectronicLow-Voltage 800 W 700 W 600W 500 W 400 W 300W
MagneticLow-VoltageD 800VA(600WC) 700VA(525WC) 600VA(450WC) 500VA(375WC) 400VA(300WC) 300VA(225WC)
Neon/ColdCathodeD 800VA(600WC) 700VA(525WC) 600VA(450WC) 500VA(375WC) 400VA(300WC) 300VA(225WC) A AdditionalloadtypeoptionsareavailableintheQuantumsoftwaresuite,somemayrequireaninterface.ContactLutronfordetails. B RefertoLutronP/N048478onwww.lutron.comforcompatibilitywithdimmableCFL/LEDlightsources. C Actuallampwattage. D OnlyuseironcoretransformersintendedforusewithanelectronicswitchordimmerperClause8.3ofIEC/EN60669-2-1.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 3 01.09.17
Specifications (continued)
Terminals (Torque,wiregauge&typeratings)
•Mainswiring:0.6N•m 1.0 mm² to 4.0 mm²
(singlewire,solidorstranded) 1.0 mm² to 1.5 mm² (twowires,solidorstranded)
• Zonewiring: 0.6N•m 1.0 mm² to 4.0 mm²
(singlewire,solidorstranded)• CCIwiring: 0.6N•m
0.5 mm² to 4.0 mm² (singlewire,solidorstranded)
•Multi-function InputWiring: 0.6N•m 0.5 mm² to 1.5 mm²
(singlewire,solidorstranded)• QSLink: 0.6N•m 0.5 mm² to 4.0 mm²
(singlewire,solidorstranded) 0.5 mm² to 1.0 mm²
(twowires,solidorstranded)
Multi-Function Inputs
•Eachmulti-functioninputiscompatiblewithoccupancyanddaylightssensorsaswellasIRreceiversandIECPELV/NECRClass2drycontactswitches.
•DedicatedPowerSupplyOutputforeachinput –20V-50mAmaximumeach. – Anauxiliarysupplyisrequiredifaninput
requiresmorethan50mA.
Wired Occupancy Sensors
•EachoftheinputscanpoweroneLutron occupancy sensor, up to four sensors per unit.
•Lutronoccupancysensorscanbeconfiguredtohaveone of the following modes:
–Occupancy:AutomaticOn,AutomaticOff –Vacancy:ManualOn,AutomaticOff•Eacharea’soccupiedandunoccupiedscenecanbeconfiguredindependently.
•Eachoccupancysensorcancontroloneor morezones.
•Occupancysensormustprovideadrycontact closureorsolid-stateoutput.
•Eachunitmaybecontrolledbyoccupancysensorsconnectedtootherdevices,uptoamaximumof sixteenoccupancysensors.
Wired Infrared (IR) Receivers•EachoftheinputscanpoweroneIRreceiver,upto
four receivers per unit.•UseLutronIRreceiversandcompatibletransmittersforpersonalcontrolofindividuallightingzones.
Wired Daylight Sensors•Eachoftheinputscanpoweronedaylightsensor,up
to four sensors per unit.•Lutrondaylightsensorsallowdaylightharvestingand
can be programmed to affect light output.•UseLutronEC-DIR-WHsensorstocontroloneormorezones.
•Eachzonemaybecontrolledbyamaximumoftwodaylight sensors.
Dry Contact Switches
•MustberatedforIECPELV/NEC®Class2operation.•Canbeconfiguredformomentaryormaintained
operation.•ZonescanbeprogrammedtoanylevelincludingOff.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 4 01.09.17
Specifications (continued)
Communication with GRAFIK Eye QS
•EnergiSavrNodeQSunitzonescanbeconfiguredtorespondtoGRAFIKEyeQSscenebuttonswhenassociatedwiththeGRAFIKEye QS.
•EnergiSavrNode QSunitzonescanbeconfiguredtorespond to scene commands initiated by the GRAFIKEye QSastronomictimeclockwhenassociatedwiththeGRAFIKEye QS.
•EnergiSavrNodeQSunitoperatesinafterhoursmodewhenassociatedwithaGRAFIKEye QS that is in afterhours mode.
•ZonesontheGRAFIKEye QSmaybeconfiguredtoremotelycontrolzonesontheEnergiSavrNodeQSunit.
Communication with QSE-IO
•EnergiSavrNode QSunitzonescanbeconfigured to respond to scene commands initiated by the QSE-IOinsceneselectionmode.
•EnergiSavrNode QSunitcanbeconfiguredtorespondtozonetoggleoroccupancysensorcommandsinitiatedbytheQSE-IOinscenetogglemode or occupancy sensor mode.
•RefertotheQSE-IOSpecificationSubmittalformoreinformation.
Communication with QSE-CI-NWK-E
•IntegrateEnergiSavrNode QS units with touchscreens,PCs,A/Vsystemsorotherdigitalsystems and devices.
•RefertoLutronIntegrationProtocolguideon www.lutron.com for more information.
QSM (QS Sensor Module): Integrating Wired and Wireless Sensors
•UsetheQSMtointegrateRadioPowrSavr Occupancy/Vacancysensors,RadioPowrSavr Daylightsensors,andPicoWirelessControllerstocontrolzonesontheEnergiSavrNode QS unit.
•Wireupto4wiredinputs(ofanytypelistedbelow)totaltotheQSM –Daylightsensors – Occupancy sensors –Infrared(IR)receivers
•TheRadioPowrSavr sensors and Pico Wireless ControllersassociatedwiththeQSMshouldbemountedwithin18mlineofsight,or9mthroughwalls,oftheQSM.
•RefertoQSMSpecificationSubmittalformore information.
seeTouch QS Wallstation
•seeTouchQSwallstationscanbeconfiguredto: –selectscenes1-16andoff –togglezonesbetweenpresetandoff – set and display partition status – enable/disable panic mode –start/stopsequencing•Inscenemode,wallstationscanbeassignedtoone
or more Energi Savr Node QS units connected to theQSlink.
•Inzonetogglemode,zonebuttonscanbeassigned tooneormorezonesonanyEnergiSavrNodeQSunitconnectedtotheQSlink.
•LEDindicatordisplayssceneorzonestatus.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 5 01.09.17
Out-of-Box (Default) Functionality
Multi-Function Inputs (Occupancy, Photo, IR Sensors, or Dry Contact Switches)
•Sensorsorswitcheswillhavenoeffectonany ofthezonesuntilset up via unit programming.
seeTouch QS Wallstations
•AllseeTouchQSlightingwallstationsareScene keypadsbydefault.
•Scenes1-16willdimlightstothepresetlevels in the table below:
Scene # Light Level: All Zones1,5-16 100%2 75%3 50%4 25%
•SceneOffwillturnallthelightsOff.
Emergency Contact Closure Input (CCI)
•WhentheCCIisopen,theEnergiSavrNodeQSunitwillenterEmergencyMode,whichwillturnonall loads to their emergency level and disable control oflocalzonesandQSdevices.
•WhentheCCIisclosedorjumpered,EnergiSavrNodeQSunitzoneswillreturntothesettingsorlevelsthey were at prior to entering emergency mode.
Note: Unit will process any sensor events received whileinemergencymodeafteritexitsemergencymode.
Normal Mode Operation
•BydefaulteachzoneissettoanUnassigned/Non-Dimloadtype.Eachzonewillswitchloadonoroffuntilitisconfiguredviaunitprogramming.Once configured,theloadtypecannotbechangedbacktoUnassigned/Non-Dim.
•Zoneandraise/lowerbuttonsontheunitcanbeused to:
– turn loads on and off. – dim loads up and down.•InputandsensorstatusLEDs(‘Occupancy’,‘Photo’,‘IR’,and‘Switch’)verifyconnectionstodrycontact switches and sensors.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 6 01.09.17
Programming Options
Detailsforeachoptioncanbefoundinthe“ProgrammingOptionsandFeatures”tableonthenextpage.
Manual Programming: •Use buttons on the front of the Energi Savr Node unit.•Use manual programming in installations with only one Energi Savr Node unit and with one QS Sensor Module(QSM)orfewerontheQSlink.
•Seethemanualprogrammingguide(032416)fordetails.
HHD Programming
•RequiresESNProgrammingInterface(QSE-CI-AP-D).•RequiresApple iPod touch or iPhone mobile digital device.•Use the intuitive programming application for the Apple iPod touch or iPhone to program systems with
multiple Energi Savr NodeunitsandQSMsontheQSlink.
•WirelessrouteronlyrequiredforprogrammingwithanApple iPod touch or iPhone.•Wirelessroutermayberemovedfornormaloperation.•EthernetconnectionmaybemadeviaananEnergi Savr NodeProgrammingInterface(QSE-CI-AP-D)
or an Energi Savr NodeunitwithintegralEthernetjack.•Lutron recommends that an Energi Savr NodeProgrammingInterface(orEnergi Savr Node unit with Ethernetjack)bewiredtoanEthernetjackinthespaceforeaseofaccessandproximitytopowerforthewireless router.
•Workswithanystandardwirelessrouterthatsupportsmulticastpackets.•Apple iPod touch or iPhone can program all Energi Savr Node units connected to an Energi Savr Node ProgrammingInterfaceviatheQSLink(exceptwhenpartofaQuantumsystem).
•Energi SavrappisrequiredandisavailablefromtheApple AppStoreonlinemarketplace.
Quantum Programming
•Programming is achieved using the Quantum software suite.•Requiresa Quantum Processor.
*Note:EnergiSavrNodeunitsarenotdesignedtoexistonanopennetwork. Connectiontoanopennetworkcouldresultinreducedperformanceand Ethernet connectivity issues.
QSLink
Energi Savr Node unit
QSM
DedicatedEthernet Connectionfor
Energi Savr Node units*
Apple iPod touch or iPhone
mobile digital deviceWireless
Router (byothers)
Energi Savr Node Programming
InterfaceQSE-CI-AP-D
Wire types:1 Lessthan153m:Lutroncable
GRX-CBL-346S 153mto610m:Lutroncable GRX-CBL-46L
2 StandardCAT5/CAT5Ecable:Totallengthnottoexceed100m
1 1
22
Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.AppStoreisaservicemarkofAppleInc.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 7 01.09.17
Programming Options and Features
Manual Programming
HHD Programming:• Requires ESN Programming Interface
QSE-CI-AP-D• Requires Apple iPod touch or iPhone mobile
digital device
Energi Savr Node units (ESNs) Connected to QS Link
Not more than 1 Multiple: 100 QS devices and 100 zone limits apply
QS Sensor Modules (QSMs) Connected to QS link
Not more than 1 Multiple: 100 QS devices limit applies
Wired Occupancy SensorsSystem Limits 2 connected directly to ESN unit
Up to 4 wired to QSMUp to 100 total occupancy sensors per QS link (wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link
Occupancy Dependency and Grouping Supported
No Yes
Wireless Occupancy Sensors
System Limits Associate 10 occupancy sensors to QSM to control zones on the ESN unit
Up to 100 total occupancy sensors per QS link (wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link
Occupancy Dependency and Grouping Supported
No Yes
Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.
Continued on next page…
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 8 01.09.17
Programming Options and Features (continued)
Manual Programming
HHD Programming:• Requires ESN Programming Interface
QSE-CI-AP-D• Requires Apple iPod touch or iPhone mobile
digital device
Wired Daylight SensorsSystem Limits Maximum of 1 daylight sensor per zone
2 connect directly to the ESN unit Additional daylight sensors can connect to the QSM
Maximum of 2 daylight sensors per zone Up to 100 total daylight sensors per QS link (wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link
Disable daylighting in Scenes No Yes
Wireless Daylight SensorsSystem Limits Maximum of 1 daylight sensor per zone
Associate wireless daylight sensors to the QSM
Maximum of 2 daylight sensors per zone Associate up to 10 wireless daylight sensors per QSM Up to 100 total daylight sensors per QS link (wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link
Disable daylighting in Scenes No Yes
Pico Wireless ControllersCan be assigned to… Any zone on the local ESN unit Any number of zones or areas on ESN units on same
QS link
IR Receivers and WallstationsSystem Limits 2 connect directly to the ESN unit
Up to 4 wired to the QSMUp to 100 total controls per QS link (wired wallstations, IR receivers)
Can be assigned to… Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on same QS link
Emergency Contact Closure InputCan be assigned to… Any zone(s) on the ESN unit Any or all local ESN unit zones
Emergency Light level Configurable Configurable
Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.
Continued on next page…
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 9 01.09.17
Programming Options and Features (continued)
Manual Programming
HHD Programming:• Requires ESN Programming Interface
QSE-CI-AP-D• Requires Apple iPod touch or iPhone mobile
digital device
seeTouch QS wallstationsScene Keypads assigned to… Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link
Scene + off keypads assigned to…
Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link
Zone toggle keypad buttons assigned to…
Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link
Change Keypad to Scene or Zone
Yes Yes
Changing keypads to shade, panic, fine tune
No Yes
Zone Configuration ParametersLoad type Auto, ELV, MLV Auto, ELV, MLV
High-end trim Adjustable Adjustable
Low-end trim Adjustable Adjustable
Absolute minimum level Adjustable Adjustable
ScenesAvailable scenes Scenes 1-16 and off Scenes 1-16 and off
GRAFIK EyeR QS Follow GRAFIK Eye QS scenes, timeclock events, and/or afterhours events
Follow GRAFIK Eye QS scenes, timeclock events, and/or afterhours events
QSE-IO Scene, zone toggle, occupancy Scene, zone toggle, occupancy
QSE-CI-NWK-E Yes Yes
Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 10 01.09.17
Mounting
•SeeLutronP/N048466atwww.lutron.comformore information on mounting and installation in panels with integratedDINrail.
•MountinIP20(minimum)ratedconsumerpanelorbreaker panelwithintegratedDINrail.
•Unitis12DINmodules(216mm)wide.•Mountunitinorientationshown.•Unitmaybemountedbyunlockingthefourmountingclipsonthebackoftheunit.ClipsmustbelockedonceunitissecurelyattachedtotheDINrail.
•Mountinanaccessibleandserviceablelocation.•Unitgeneratesheat,maximum75BTUs/Hour•Mountunitsuchthatalltheconditionsbelowaremet: –Roomambienttemperatureisbetween0ºCand30ºC –Temperatureinsidemountingpanel,within20mmofunit,
isbetween0ºCand50ºC –Calibrationpointmaximum:70ºC
Unlocked
4 mounting clips on unit
Locked
H
M
L
QSNE
-4A-D
DIN
Rai
l Pow
er M
odul
e
230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657
InputS1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
DefOption
Mechanical DimensionsFront View
H
M
L
QSNE
-4A-D
DIN
Rai
l Pow
er M
odul
e
230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657
InputS1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
DefOption
90m
m
216mm
Left Side View
Calibration point
90m
m
55 mm70 mm
76mm
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 11 01.09.17
Overview of Wiring Terminals
QS Link
Mains Input
Load Neutrals
EmergencyContact Closure
Input
QSNE-4A-D
Phase Adaptive Outputs
H
M
L
QSNE
-4A-D
DIN
Rai
l Pow
er M
odul
e
230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657
InputS1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
DefOption
Mains Wiring
Multi-Function Inputs
Zone 1
Zone 4
Zone 2
Zone 3
L L N N N N N DL1 DL2 DL3 DL4
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 12 01.09.17
QSNE-4A-D
Wiring Verification
•Unitshipswithbypassconnectorpre-installedforloadwiringverification.Bypassconnectorisusedtoapplypower to loads to identify any load or wiring faults prior to wiring loads to unit.
•Loadwiringmustbeverifiedbeforewiringloadstounit.
H
M
L
QSNE
-4A-D
DIN
Rai
l Pow
er M
odul
e
230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657
InputS1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
DefOption
L N N N N N DL1 DL2 DL3 DL4
a
b
c
Neutral
Line/Hot
Earth
•Toverifywiring: 1. Turn off power. 2.Wireloadstoprovidedconnector. 3.Applypower,ensurethedesiredloadsare
powered and properly wired. 4.TurnoffpowerandwireloadstoDLterminals
on unit.
L
Distribution Panel
(220–240 V~)
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 13 01.09.17
Wiring from Distribution to Energi Savr NodeT QS unit
•TurnoffallcircuitbreakersorisolatorsfeedingtheEnergi Savr Node QS unit at distribution panel.
•Runline/hot,neutral,andearth wires froma220–240V~50/60Hzfeedtothe Energi Savr Node QS unit.
•Runaseparateneutralforeachloadcircuit.A common neutral connection is not recommended.
Mains Wiring and IEC PELV Separation
•Followappropriatelocalandnationalcodestoavoidviolatingrequiredseparationguidelines.
Dim Line/Hot (220–240 V~)
Neutral
H
M
L
QSNE
-4A-D
DIN
Rai
l Pow
er M
odul
e
230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657
InputS1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
DefOption
Zone 1 Example
Mains Voltage Wiring
H
M
L
QSNE
-4A-D
DIN
Rai
l Pow
er M
odul
e
230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657
InputS1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
DefOption
L N N N N N DL1 DL2 DL3 DL4
Load
Earth
Neutral
Line/HotDistribution
Panel(220–240 V~)
L
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 14 01.09.17
IEC PELV Emergency Contact Closure Input
•ContactClosureInput(CCI)wiringis IECPELV/NECClass2.Followallapplicable national and local codes for proper circuit separation and protection.
•Turnoffallbreakersorisolatorsfeedingthe Energi Savr Node QS unit at distribution panel be-fore servicing unit.
•TheCCIisalocalcontrolonlyandcannotcontrolotherEnergiSavrNodeQSunitsovertheQSlink.Amaximumof32EnergiSavrNodeQSunitsmaybeconnectedinparalleltoanEmergencyorManualoverride device if the event is intended to affect multiple devices.
•Wheninemergencymode,allzoneoutputswill be at their programmed emergency light level (configurableforeachzone,defaultis100%). Allsensorsandcontrolsarelockedout.
•Emergencycontactclosureinputisnormallyclosed(NC).TheEnergiSavrNode QS unit is shipped with ajumperpre-installed.
Note: The Energi Savr Node QS unit will default to EmergencyModeiftheCCIisleftopen.IfnoEmergency ContactClosureInputisrequired,pleaseleavethewire jumperintheCCIterminals.
H
M
L
QSNE
-4A-D
DIN
Rai
l Pow
er M
odul
e
230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657
InputS1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
DefOption
H
M
L
QSNE
-4A-D
DIN
Rai
l Pow
er M
odul
e
230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657
InputS1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
DefOption
CCICommon
Wiring: Emergency Contact Closure Input
CCI COM
Note: Shown with pre-installedjumper.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 15 01.09.17
Wiring: QS LinkQS Link IEC PELV Wiring
•LinkcommunicatesusingIECPELV/NEC® Class2wiring.
•TurnoffallbreakersorisolatorsfeedingtheEnergiSavrNode QS unit at distribution panel before servicing unit.
•Followallapplicablenationalandlocalcodesforproper circuit separation and protection.
•Wiringmaybedaisychainedort-tapped.•TotallengthofQSlinkmustnotexceed600m.•Forlengthsunder150m,use1.0mm2 or larger conductorsforcontrolpower(24V-,COM).
•Forlengthsover150m,use4.0mm2 conductorsforcontrolpower(24V-,COM).
•Useone,twisted-shieldedpairof1.0mm2 conductorsfordatalink(MUX,_).
•Terminal2(+24V-)shouldNEVERbeconnected betweendevicesthatsupplyPDUs.
•See“PowerDrawUnitsontheQSLink” (LutronP/N369405)onwww.lutron.comfor QSlinklimitsandPDUcounts.
H
M
L
QSNE
-4A-D
DIN
Rai
l Pow
er M
odul
e
230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657
InputS1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
DefOption
H
M
L
QSNE
-4A-D
DIN
Rai
l Pow
er M
odul
e
230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657
InputS1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
DefOption
(1) COM
(2) 24 V-
(3) MUX
(4) MUX
Energi Savr Node QS
Energi Savr Node QS
seeTouch QS wallstations
seeTouch QS wallstations
QSE-IO or QSE-CI-NWK-E
QSE-IO or QSE-CI-NWK-E
Daisy-Chain Wiring Example
T-Tap Wiring Example
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller
369609f 16 01.09.17
Wiring: IEC PELV Multi-Function InputsWiring Instructions:
•AllinputwiringisIECPELV/NEC®Class2.Followallapplicable national and local codes for proper circuit separation and protection.
•Inputterminalsaccept0.5mm2 to 1.5 mm2 solid or stranded conductors.
•MainsvoltageandIECPELV/NEC®Class2wiringmustbekeptseparate.
•Note: One device per input.•TurnoffallbreakersorisolatorsfeedingtheEnergiSavr
Node QS unit at distribution panel before servicing unit.
Daylight Sensor:•Connectthefourconductorstothefourterminals
as shown. Red=20V- White=IR* Black=Common Yellow=Daylight•MaximumwirelengthbetweentheDaylightSensor
and the Energi Savr Node QS unit must be less than 46m.
•Onedaylightsensorcanbewiredtoeachinput.
•Consultthedaylightsensorspecificationsheettoproperlyinstall sensor.
•Donotplacethesensorabovependants,fixtures, directlybelowlightingfixtures,orwithinskylightwells.
Occupancy Sensor:•Connectthreeconductorstothreeterminalsasshown.•Oneoccupancysensorcanbewiredtoeachinput.•Maximumwirelengthbetweenthesensorandthe
Energi Savr Node QSunitmustbelessthan46m. Note:Ifsensorhasanautomaticsensitivityorthresholdadjustment,Lutronrecommendsdisablingit.
IR Receiver:•Connectthethreeconductorstothethreeterminalsasshown.•Maximumwirelengthbetweenthereceiverandthe
Energi Savr Node QSunitmustbelessthan46m.•OneIRreceivercanbewiredtoeachinput.
Dry Contact Switch:•Connectoneconductortocommonandtheothertoinput(notshown).
•Maximumwirelengthbetweentheswitchandthe EnergiSavrNodeQSunitmustbelessthan46m.
H
M
L
QSNE
-4A-D
DIN
Rai
l Pow
er M
odul
e
230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657
InputS1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
DefOption
* Note:DaylightsensorwithIRmayrequiretwoinputs.OnlyoneIRdevicemaybeconnectedperinput.IftheIRsignalfromadaylightsensor is connected, another control may not beconnectedtothesameinput.IfIRisnotbeing used, leave white wire disconnected.
** Note:Connectthegraywireon-ROccupancySensor models.
+ Note:SensorCommonsareinternallyshorted.
Sensor 1+20V Input
Sensor2+20V Input
Sensor3+20V Input
Com
mon
+
Com
mon
+
Sensor 4+20V Input
H
M
L
QSNE
-4A-D
DIN
Rai
l Pow
er M
odul
e
230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657
InputS1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
DefOption
IR Transmitter
LUTR
ON
R
IR Transmitter
LUTR
ON
R
Daylight Sensor (IR)
Red
Blac
k
Yello
w
Whi
te*
Occupancy Sensor
Red
Blac
k
Blue
/Gra
y**
IR Receiver
Blac
kW
hite
Red
LUTRON
LUTRONR
Example Sensor Setup
)Lutron,Lutron,Quantum,RTISSEquipped,SeeTouch,Pico,andGRAFIKEyeareregisteredtrademarksofLutronElectronicsCo.,Inc.registeredintheU.S.andother countries.
EnergiSavrNode,RTISS-TE,andRadioPowrSavraretrademarksofLutronElectronicsCo.,Inc.