Page 1: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

HELPHPWESPILOT

Page 2: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Energy Efficiency in Rehab

Late 1980s – RIP Early 1990s – energy standards developed

Approx 20 pages Prescriptive Lowering energy usage Controlling moisture

Late 1990s – HELP Duke Energy awards $$ to NCHFA (Special Needs

Energy Products Program) Duke Energy/NCHFA agreement (1997)

Page 3: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Goal of HELP

To encourage the inclusion of high-performance energy-efficiency standards in the rehabilitation of scattered-site single-family housing owned and occupied by low-income customers of Duke Energy Carolinas.

Page 4: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

And to make homes

• more affordable - via lower monthly energy bills;

• more comfortable;• more healthy and safe.

It also:• HELPs Duke reduce need to continually

produce more electricity and better control peak demand;

• AND society benefits by reduced carbon/greenhouse gases.

Page 5: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Energy Efficiency in Rehab

Late 1990s - 2005 - 2011, HELP funds used with SFR to pay for energy-efficiency measures in comp rehab

2005 HPwES symposium held at ACI in Austin Texas

Page 6: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

HPwES

Home Performance with ENERGY STAR, a national program from the U.S. EPA and U.S. DOE, offers a comprehensive, whole-house approach to improving energy efficiency and comfort of existing homes, while helping to protect the environment.

Page 7: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

HPwES & Affordable Housing

2006, some HPwES principals Air-sealing, ES appliances) introduced in SFR Energy-Efficiency Standards

2006 – 2009, HPwES model in the affordable housing market conceptualized at NCHFA

2009 – 2010, NCHFA & AE massage and refine pilot program structure

Page 8: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

HPwES & Affordable Housing

2010 - AE & NCHFA work toward developing model HPwES Standards

Early 2011 – HPwES Program standards formulated and adopted for HPwES Pilot Program

Page 9: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Definitions

Sponsor (Advanced Energy)

NCHFA Partner (Pool Member)

(Executes Tri-Party Agreement, NCHFA & AE)

HPwES Contractor (requires BPI certification)

Executes a participation agreement with the Sponsor

Whole House Performance Assessment (HPwES audit)

Performed by HPwES Contractor

Page 10: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Definitions

Rehab Specialist Responsible for WWU & const mgt

Contractor

Responsible for completing EEMs

May or may not be HPwES Contractor

Verification Inspection

Performed by HPwES Contractor

HPwES Summary Certificate

Issued by AE

Page 11: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

The HPwES Processs

AE trains Member staff (Rehab Specialist) HPwES Contractor performs HPwES audit

Audit results and HC data to AE HC data reviewed for complexity

AE approves unit, Member reserves funds Rehab Sp generates WWU & CE Contractor installs EEMs HPwES Contractor does post assessment QA by AE – 1st 3, then 10% Approval & HPwES certification

Page 12: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Benefits

HPwES provides Members with structured training and a consistently applied energy-efficiency process.

It provides Members with a HPwES manual containing illustrated technical materials which can be used for “job-site” training of contractors and workers.

Page 14: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Tech sheet – critical details

Page 15: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Tech sheet – critical details

Page 16: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Tech sheet – critical details

Page 17: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Benefits

HPwES quality assurance process gives Members and NCHFA confidence that the work was appropriate and performed correctly.

Page 18: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

HPwES Standards

Air Tightness Ventilation Insulation & Windows HVAC Sizing & Installation Combustion Safety Crawlspaces

Page 19: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Air Tightness

There shall be a continuous, durable air barrier enclosing the conditioned space. This includes features such as chases, knee walls, soffits, garage interfaces, intersecting walls and dropped ceilings.

Page 20: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Air Tightness

Air sealing shall be required for the following building planes:

 Attic plane – The highest priority for air sealing shall be given first to any plane adjacent to attic space.

Page 21: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Air Tightness

Exterior walls—Windows, doors, and any visible hole or crack leading from the building to the exterior

Crawlspace/Basement—All plumbing penetrations (e.g., “P” trap) between the conditioned and unconditioned space shall be sealed.

Page 22: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Air tightness

Page 23: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Air tightness

Page 24: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Air tightness

Page 25: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Ventilation

There shall be a filtered whole-house mechanical fresh air ventilation system in compliance with ASHRAE 62.2., 2007.

Page 26: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Ventilation

All bathrooms shall have a fan vented to the outside

All ventilation ducts shall terminate at or beyond the exterior skin of the building.

Page 27: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Insulation, Windows and Doors

Insulation shall be installed to manufacturer specifications without gaps, voids, compression or wind intrusion.

Page 28: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Insulation, Windows and Doors

Insulation and the air barrier in physical contact with each other.

Accessible attics shall be insulated to R-38 or greater.

Replacement windows, if installed, shall be ENERGY STAR labeled.

Knee walls shall be insulated and backed with support material

Page 29: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

HVAC Sizing and Installation

Heat pumps shall have an outdoor thermostat installed to prevent supplementary heater operation when the heat pump is capable of meeting the load.

All accessible duct connections shall be sealed with a UL-listed bucket mastic product.

Page 30: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

HVAC Sizing and Installation

Duct leakage shall meet the Advanced Energy approved Duct Location Table targets.

New mechanical systems (HVAC) shall be properly sized to ACCA Manual J

Replacement furnaces, if installed, shall be 90 percent efficient or greater.

 

Page 31: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Combustion Safety

If existing gas equipment will remain atmospherically vented safety testing protocol must be completed and needed repairs must be performed immediately

Page 32: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Combustion safety

Page 33: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Combustion Safety

Homes containing vent-free gas logs or space heaters shall not be retrofitted until units are removed or disabled.

Page 34: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Combustion Safety

One carbon monoxide (CO) detector shall be installed outside of each bedroom area and to manufacturer specifications in homes that have a combustion appliance or an attached garage (minimum 1 per floor).

 

Page 35: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

Crawlspaces

All crawlspaces shall have a 100 percent ground cover of 6 mil thickness or greater.

Houses having crawlspaces with standing water shall not be included in the program unless drainage is a part of the retrofit plan.

Page 36: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

HPwES subsidy

1. $7,500 ( including hard & soft costs) if work includes energy-efficiency measures necessary to meet HPwES energy standards; or

2. $10,000 ( including hard & soft costs) if work includes installation of a heat pump.

Page 37: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

HPwES and Affordable Housing

HPwES Pilot Program - 7 HELP Members

Currently an option under NCHFA’s Home Energy Loan Program (HELP) when Energy-Efficiency measures applied in the comprehensive rehabilitation of single-family homes

Page 38: Energy Efficiency in Rehab Late 1980s – RIP Early 1990s – energy standards developed Approx 20 pages Prescriptive Lowering energy usage Controlling moisture.

HPwES and Affordable Housing

2012 - incorporate HPwES standards into NCHFA’s HOME-funded Single-Family Rehabilitation