+ All Categories
Home > Documents > Enhanced performance for PV installations - Schneider Electric · according to IEC 61439-2 Protect...

Enhanced performance for PV installations - Schneider Electric · according to IEC 61439-2 Protect...

Date post: 05-Apr-2018
Category:
Upload: dongoc
View: 216 times
Download: 0 times
Share this document with a friend
3
A string combiner for 1500 VDC that protects and enhances the performance of your photovoltaic installation. Solution at a glance Applications A Conext SmartGen TM Array Box is a photovoltaic (PV) string combiner box installed between the PV modules and the inverter, providing protection and performance monitoring for your PV power plant. Key benefits • Reliable: designed for the most severe environments; corrosion and pollution resistant • Flexible: fits every PV power plant design, module technology and customer preferences for PV cable connection • Cost effective: self-powering to avoid the need for external auxilliary power • Easy to install: 750mm height for fitting under any racking design, wide variety of mounting solutions and DC fuse systems for reduced on-site labor • Cloud-connected: enables PV module aging, soiling and shading detection through Conext TM Advisor 2 monitoring and control solution © 2017 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. DS20170711_ArrayBox Centralized PV power plants Enhanced performance for PV installations Conext SmartGen TM Array Box
Transcript

A string combiner for 1500 VDC that protects and enhances the performance of your photovoltaic installation.

Solution at a glanceApplications

A Conext SmartGenTM Array Box is a photovoltaic (PV) string combiner box installed between the PV modules and the inverter, providing protection and performance monitoring for your PV power plant.

Key benefits

• Reliable: designed for the most severe environments; corrosion and pollution resistant

• Flexible: fits every PV power plant design, module technology and customer preferences for PV cable connection

• Cost effective: self-powering to avoid the need for external auxilliary power

• Easy to install: 750mm height for fitting under any racking design, wide variety of mounting solutions and DC fuse systems for reduced on-site labor

• Cloud-connected: enables PV module aging, soiling and shading detection through ConextTM Advisor 2 monitoring and control solution

© 2017 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. DS20170711_ArrayBox

Centralized PV power plants

Enhanced performance for PV installationsConext SmartGenTM Array Box

Technical specificationsConext SmartGenTM Array Box In-Box

solar.schneider-electric.com | 2

© 2017 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. DS20170711_ArrayBox

Device short name Array Box In-Box 16/32 Array Box In-Box24 Array Box In-Box 32

Available versionsProtectString MonitoringString Monitoring High Power

ProtectString MonitoringString Monitoring High Power

ProtectString MonitoringString Monitoring High Power

Electrical specifications

PV input

Number of connectable PV strings Up to 32 Up to 24 Up to 32

Max. voltage in open circuit 1500 Vdc 1500 Vdc 1500 Vdc

PV input cable entries Cable plate membrane, IP 65 - Accepts 1 or 2 PV string cables Ø 4 mm² to Ø 10 mm² each

Maximum current per input (Inc) @ STCProtect: 20.9 AString Monitoring: 20.9 AString Monitoring High Power: 25.0 A

Protect: 13.9 AString Monitoring: 13.9 AString Monitoring High Power: 16.6 A

Protect : 10.4 AString Monitoring: 10.4 AString Monitoring High Power: 12.5 A

DC output

Rated current of the assembly (InA) @ STC according to IEC 61439-2 Protect : 335 A - String Monitoring : 335 A - String Monitoring High Power: 400 A

Rated current of the assembly (InA) @ 50°C according to IEC 61439-2 Protect : 305 A - String Monitoring : 305 A - String Monitoring High Power: 350 A

Temperature derating (rated current) Derating 3.3% per °K over 50°C operating temperature

DC output cable entries Cable glands M40, Ø 22 mm to Ø 32 mm, IP 68

DC output cables 2 x 300 mm² or 1 x 400 mm² per polarity

Electrical protection (max)

Number of protected circuits 16 24 32

Type of protection 1500Vdc gPV fuses, size 10 x 85 mm, protection on both polarities. Fuse supplies available separately

Fuse installation Fuse holders

Overvoltage protection Surge arresters 1500Vdc, type 2, Iscpv 10kA, Imax 40kA, In 10kA, Up< 5kV (standard) or type 1+2 (option)

Environmental specifications (in operation)

Operating temperature range -40°C to 60°C (1)

-40°C to 60°C (1)

-40°C to 60°C (1)

Relative humidity Up to 100%, condensation possible Up to 100%, condensation possible Up to 100%, condensation possible

Altitude Up to 4000 m (2)

Up to 4000 m (2)

Up to 4000 m (2)

Mechanical specifications

Dimensions and weight

Dimensions (H x W x D) (mm) 750 x 1250 x 320 750 x 1250 x 320 750 x 1250 x 320

Weight (kg) 75kg 75kg 75kg

Enclosure

Material Fully insulated enclosure, electrical insulation class 2 (fibreglass reinforced polyester)

Fire resistance level Halogen-free, self extinguishing. Fire retardant. Tested to the glow wire at 960°C

Protection grade IP 65, IK 10

Installation

Installation modes On plinth (floor standing) / On a chair / Mounted on module racks with brackets

Installation accessories Canopy for Array Box In-Box

Monitoring and Communication (String Monitoring and String Monitoring High Power versions only)

Number of monitoring channels 8 (1 channel per group of 2 protected circuits)

8 (1 channel per group of 3 protected circuits)

8 (1 channel per group of 4 protected circuits)

PV string current scale and accuracy 0 to 60 A, accuracy +/-0.18% @25°C, +/- 0.8% @ the maximum operating temperature

PV string voltage scale and accuracy 0 to 1500 V, accuracy +/- 0.5% full scale

Internal temperature -40°C to 120°C, accuracy +/- 3°C

Digital Inputs 3 Digital inputs: Monitoring of overvoltage protection and main switch, 1 spare

External temperature / Irradiance sensors Possible using the optional weather sensor monitoring kit PVSAB15WB001. 1 input for temperature, 2 inputs for irradiance

Monitoring power supply PV powered, no need for external power supply cable

Communication Modbus RTU / RS 485 link (3)

Communication line overvoltage protection Included on communication board

Compliance IEC / EN 61439-1 and IEC / EN 61439-2

CE marking

Footnotes(1) See derating curves provided in the product documentation(2) Derating from 2000 m(3) PC software available for Modbus network settings. The PC can be connected at any network node.

Technical specificationsConext SmartGenTM Array Box In-Line

solar.schneider-electric.com | 3

© 2017 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. DS20170711_ArrayBox

Device short name Array Box In-Line

Available versionsProtectString MonitoringString Monitoring High Power

Electrical specifications

PV input

Number of connectable PV strings16 with the pack of 32 connection sets PVSAB15LF32SCX (SunClixTM connectors)24 with the pack of 48 connection sets PVSAB15LF48SCX (SunClixTM connectors)32 with the pack of 64 connection sets PVSAB15LF64SCX (SunClixTM connectors)

Max. voltage in open circuit 1500 Vdc

PV input cable entries Cable plate membrane, IP 65 - Accepts 1 or 2 PV string cables Ø 4 mm² to Ø 10 mm² each

Maximum current per input (Inc) @ STC Protect / String Monitoring: 46.2 AString Monitoring High Power: 50.0 A

DC output

Rated current of the assembly (InA) @ STC according to IEC 61439-2

Protect / String Monitoring: 370 AString Monitoring High Power: 400 A

Rated current of the assembly (InA) @ 50°C according to IEC 61439-2

Protect / String Monitoring: 310 AString Monitoring High Power: 360 A

Temperature derating (rated current) Protect / String Monitoring: Derating 3.9% per °K over 50°C operating temperatureString Monitoring High Power: Derating 3.2% per °K over 50°C operating temperature

DC output cable entries Cable glands M40, Ø 22 mm to Ø 32 mm, IP 68

DC output cables 2 x 300 mm² or 1 x 400 mm² per polarity

Electrical protection (max)

Number of protected circuitsUp to 16 with the pack of 32 connection sets PVSAB15LF32SCX (SunClixTM connectors)Up to 24 with the pack of 48 connection sets PVSAB15LF48SCX (SunClixTM connectors)Up to 32 with the pack of 64 connection sets PVSAB15LF64SCX (SunClixTM connectors)

Type of protection Use external 1500Vdc gPV fuses, protection on both polarities. Fuse supplies available separately

Fuse installation In- Line fuse

Overvoltage protection Surge arresters 1500Vdc, type 2, (standard) Iscpv 10kA, Imax 40kA, In 10kA, Up< 5kV or type 1+2 (option)

Environmental specifications (in operation)

Operating temperature range -40°C to 60°C (1)

Relative humidity Up to 100%, condensation possible

Altitude Up to 4000 m (2)

Mechanical specifications

Dimensions and weight

Dimensions (H x W x D) (mm) 747 x 536 x 300

Weight (kg) 45kg

Enclosure

Material Fully insulated enclosure, electrical insulation class 2 (fibreglass reinforced polyester)

Fire resistance level Halogen-free, self extinguishing. Fire retardant. Tested to the glow wire at 960°C

Protection grade IP 65, IK 10

Installation

Installation modes On a chair / Mounted on module racks with brackets

Installation accessories Canopy for Array Box In-Line

Monitoring and Communication (String Monitoring and String Monitoring High Power versions only)

Number of monitoring channels 8 (1 channel per group of 2, 3 or 4 protected circuits depending on the pack of connection sets used)

PV string current scale and accuracy 0 to 60 A, accuracy +/-0.18% @25°C, +/- 0.8% @ the maximum operating temperature

PV string voltage scale and accuracy 0 to 1500 V, accuracy +/- 0.5% full scale

Internal temperature -40°C to 120°C, accuracy +/- 3°C

Digital Inputs 3 Digital inputs: Monitoring of overvoltage protection and main switch, 1 spare

External temperature / Irradiance sensors Possible using the optional weather sensor monitoring kit PVSAB15WB001. 1 input for temperature, 2 inputs for irradiance

Monitoring power supply PV powered, no need for external power supply cable

Communication Modbus RTU / RS 485 link (3)

Communication line overvoltage protection Included on communication board

Compliance IEC / EN 61439-1 and IEC / EN 61439-2

CE marking

Footnotes(1) See derating curves provided in the product documentation(2) Derating from 2000 m(3) PC software available for Modbus network settings. The PC can be connected at any network node.


Recommended