APPLICATION
FEATURES
MOUNTING
LED COMPATIBLE
UL®UL924 LISTEDC US
5YEAR
WARRANTY
In the past, emergency lights were kept on 24 hours a day to meet life safety codes. Now, you can use a UL 924 listed Emergency Power Control, Model EPC-1-D, to convert regular light fixtures into approved emergency lights. The EPC-1-D saves energy and money while ensuring compliance with both life safety and energy codes.
During normal operation, the same dimmer, occu-pancy sensor, dimming panel, or lighting control can switch and dim regular and emergency fixtures on and off simultaneously.
During a utility power interruption, the EPC-1-D automatically bypasses the regular lighting controls, turning the emergency lights ON at full brightness, regardless of dimmer position.
The EPC-1-D is ceiling or wall mounted in a junc-tion box with a single gang plaster ring and is usually located in the area where the emergency fixtures are installed.
Unique, Patented Automatic Diagnostic
Fire Alarm, Remote Test & 0-10V Dimming Option
When the room switch is turned off, the EPC-1 will run a 2.5 self-test routine, verifying that the emergency power source was available and that the EPC-1, ballast, and lamp(s) are all function-ing correctly. This feature eliminates the need for time-consuming and costly manual monthly testing and is approved for this purpose. This also allows the unit to be installed in remote or inaccessible locations, because the unit does not rely on access to its manual test switch.
Utility & Emergency Power Indicator LED’sSlim, attractive flush mount profile allows easy access to manual test switch and LED’s.
Isolated 0-10V relay contact ensures full bright-ness during utility power interruption, regardless of dimmer model.
EPC-1-DEmergency Power ControlFor 4-Wire Dimmable Loads
0-10 V Dimmer Compatible
SPECIFICATIONS
SINGLE LINE DRAWING
WIRING DIAGRAM
ORDERING INFORMATION ADDITIONAL RESOURCES
EPC-1-D Installation SheetFAQ SheetAlternative Wiring Sheet
Terms & Conditions/Warranty InformationAlternate model: EPC-1-D-ATS InternationalDual field-selectable auto test features (2.5sec, monthly, annual), 120,220,230,277V input.
20160421_E001_Spec
LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707
www.lvscontrols.com
DESIGNATEDEMERGENCY
LIGHTS
REGULAR ROOM LIGHTS
EPC-1-D CONTROL
UL 1008Transfer SwitchOr Equivalent
RegularUtility Power
Emergency Power Source
Neutral Not Shown
EPC-1-DCONTROL
TO ADDITIONAL EPC-1 CONTROLS
REGULARPANEL
RegularUtility Power
EMERGENCYPANEL
$
EPC-1-D
ZONECONTROLLER
Photo-cell D
EMERGENCY HOT
#4 WHITE
REGULAR PANEL
EMERGENCYPOWER
TEST SWITCH
UTILITYPOWER
20A
#3 RED
#2 ORANGE
#1 BLACK
*
Relay Panel, Power Pack, Sensor, or other (optional)*
Regular Light (optional)
EMERGENCY PANEL OR INVERTER
20AREGULAR HOT
REGULAR NEUTRALEMERGENCY NEUTRAL
#7 WHITE/BLUE
#6 YELLOW
#5 BLUE
Emergency Light
Note: Emergency Light is also called N/E Light or Normal/Emergency
Light by many specifiers
120V
277V
RedBlue
Note: Blue & Red low voltage wires are plenum rated. Additional Black plenum wire (N/C) not shown. For
use with BMS or other systems. Contact LVS for wiring diagrams.
MODEL NO.
SENSING INPUT
LOAD RATING
BALLAST LOAD RATING
INCANDESCENT LOAD
WARRANTY
EPC-1-D
120V / 277V
120V - 277V (20A)
20A (120-277V)
1800W (120V) / 1500W (277V)
5 Year Replacement Warranty
ELECTRICAL
MOUNTING
RATING
SHIPPING WEIGHT / COLOR
TEMPERATURE
FLUSH MOUNTED SIZE
BODY SIZE
4-11/16” Junction Box w/ single gang plaster
UL94-5VA + UL2043 Plenum Rating
8 oz. / White
32ºF - 140ºF (0ºC - 60ºC)
4-3/4” x 2-3/4” x 1/4”
2-7/8” x 1-3/4” x 1-3/4”