LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707 www.lvscontrols.com Project: Model No.: Comments: APPLICATION FEATURES MOUNTING LED COMPATIBLE U L ® UL924 LISTED C US 5 YEAR WARRANTY In the past, emergency lights were kept on 24 hours a day to meet life safety codes. Now, you can use a UL 924 listed Emergency Power Control, Model EPC-1-D, to convert regular light fixtures into approved emergency lights. The EPC-1-D saves energy and money while ensuring compliance with both life safety and energy codes. During normal operation, the same dimmer, occu- pancy sensor, dimming panel, or lighting control can switch and dim regular and emergency fixtures on and off simultaneously. During a utility power interruption, the EPC-1-D automatically bypasses the regular lighting controls, turning the emergency lights ON at full brightness, regardless of dimmer position. The EPC-1-D is ceiling or wall mounted in a junc- tion box with a single gang plaster ring and is usually located in the area where the emergency fixtures are installed. Unique, Patented Automatic Diagnostic Fire Alarm, Remote Test & 0-10V Dimming Option When the room switch is turned off, the EPC-1 will run a 2.5 self-test routine, verifying that the emergency power source was available and that the EPC-1, ballast, and lamp(s) are all function- ing correctly. This feature eliminates the need for time-consuming and costly manual monthly testing and is approved for this purpose. This also allows the unit to be installed in remote or inaccessible locations, because the unit does not rely on access to its manual test switch. Utility & Emergency Power Indicator LED’s Slim, aractive flush mount profile allows easy access to manual test switch and LED’s. Isolated 0-10V relay contact ensures full bright- ness during utility power interruption, regardless of dimmer model. EPC-1-D Emergency Power Control For 4-Wire Dimmable Loads 0-10 V Dimmer Compatible
Transcript
Page 1: EPC 1D Template - LVS Inc. · SPECIFICATIONS SINGLE LINE DRAWING WIRING DIAGRAM ORDERING INFORMATION ADDITIONAL RESOURCES EPC-1-D Installation Sheet FAQ Sheet Alternative Wiring Sheet

LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707

www.lvscontrols.com

Project:

Model No.:

Comments:

APPLICATION

FEATURES

MOUNTING

LED COMPATIBLE

UL®UL924 LISTEDC US

5YEAR

WARRANTY

In the past, emergency lights were kept on 24 hours a day to meet life safety codes. Now, you can use a UL 924 listed Emergency Power Control, Model EPC-1-D, to convert regular light fixtures into approved emergency lights. The EPC-1-D saves energy and money while ensuring compliance with both life safety and energy codes.

During normal operation, the same dimmer, occu-pancy sensor, dimming panel, or lighting control can switch and dim regular and emergency fixtures on and off simultaneously.

During a utility power interruption, the EPC-1-D automatically bypasses the regular lighting controls, turning the emergency lights ON at full brightness, regardless of dimmer position.

The EPC-1-D is ceiling or wall mounted in a junc-tion box with a single gang plaster ring and is usually located in the area where the emergency fixtures are installed.

Unique, Patented Automatic Diagnostic

Fire Alarm, Remote Test & 0-10V Dimming Option

When the room switch is turned off, the EPC-1 will run a 2.5 self-test routine, verifying that the emergency power source was available and that the EPC-1, ballast, and lamp(s) are all function-ing correctly. This feature eliminates the need for time-consuming and costly manual monthly testing and is approved for this purpose. This also allows the unit to be installed in remote or inaccessible locations, because the unit does not rely on access to its manual test switch.

Utility & Emergency Power Indicator LED’sSlim, attractive flush mount profile allows easy access to manual test switch and LED’s.

Isolated 0-10V relay contact ensures full bright-ness during utility power interruption, regardless of dimmer model.

EPC-1-DEmergency Power ControlFor 4-Wire Dimmable Loads

0-10 V Dimmer Compatible

Page 2: EPC 1D Template - LVS Inc. · SPECIFICATIONS SINGLE LINE DRAWING WIRING DIAGRAM ORDERING INFORMATION ADDITIONAL RESOURCES EPC-1-D Installation Sheet FAQ Sheet Alternative Wiring Sheet

SPECIFICATIONS

SINGLE LINE DRAWING

WIRING DIAGRAM

ORDERING INFORMATION ADDITIONAL RESOURCES

EPC-1-D Installation SheetFAQ SheetAlternative Wiring Sheet

Terms & Conditions/Warranty InformationAlternate model: EPC-1-D-ATS InternationalDual field-selectable auto test features (2.5sec, monthly, annual), 120,220,230,277V input.

20160421_E001_Spec

LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707

www.lvscontrols.com

DESIGNATEDEMERGENCY

LIGHTS

REGULAR ROOM LIGHTS

EPC-1-D CONTROL

UL 1008Transfer SwitchOr Equivalent

RegularUtility Power

Emergency Power Source

Neutral Not Shown

EPC-1-DCONTROL

TO ADDITIONAL EPC-1 CONTROLS

REGULARPANEL

RegularUtility Power

EMERGENCYPANEL

$

EPC-1-D

ZONECONTROLLER

Photo-cell D

EMERGENCY HOT

#4 WHITE

REGULAR PANEL

EMERGENCYPOWER

TEST SWITCH

UTILITYPOWER

20A

#3 RED

#2 ORANGE

#1 BLACK

*

Relay Panel, Power Pack, Sensor, or other (optional)*

Regular Light (optional)

EMERGENCY PANEL OR INVERTER

20AREGULAR HOT

REGULAR NEUTRALEMERGENCY NEUTRAL

#7 WHITE/BLUE

#6 YELLOW

#5 BLUE

Emergency Light

Note: Emergency Light is also called N/E Light or Normal/Emergency

Light by many specifiers

120V

277V

RedBlue

Note: Blue & Red low voltage wires are plenum rated. Additional Black plenum wire (N/C) not shown. For

use with BMS or other systems. Contact LVS for wiring diagrams.

MODEL NO.

SENSING INPUT

LOAD RATING

BALLAST LOAD RATING

INCANDESCENT LOAD

WARRANTY

EPC-1-D

120V / 277V

120V - 277V (20A)

20A (120-277V)

1800W (120V) / 1500W (277V)

5 Year Replacement Warranty

ELECTRICAL

MOUNTING

RATING

SHIPPING WEIGHT / COLOR

TEMPERATURE

FLUSH MOUNTED SIZE

BODY SIZE

4-11/16” Junction Box w/ single gang plaster

UL94-5VA + UL2043 Plenum Rating

8 oz. / White

32ºF - 140ºF (0ºC - 60ºC)

4-3/4” x 2-3/4” x 1/4”

2-7/8” x 1-3/4” x 1-3/4”

MECHANICAL


Recommended