Safeguarding our future with consistent energy efficiency! Rittal – System climate control
Transcript
Page 1: Erdinc  klima sk_broschuere_gb

Safeguarding our future with consistent energy efficiency!

Rittal – System climate control

Page 2: Erdinc  klima sk_broschuere_gb

Rittal is your value-creating partner for comprehensive

technology packaging solutions. We offer individual

system benefits based on our complete product range,

extensive expertise and global customer service – cross-

sector, value-maximising solutions that are one hundred

percent benefit-focussed.

Page 3: Erdinc  klima sk_broschuere_gb

Rittal system climate control is proven to boost energy

efficiency by up to 45 percent – while ensuring optimum

cooling performance for all control and IT components.

Thanks to the significant reduction in energy consumption,

Rittal’s innovative cooling concepts are major contributors

to cost efficiency in your company, while at the same time

helping to cut CO2 emissions in the environment.

Page 4: Erdinc  klima sk_broschuere_gb

From system to solution: Comprehensively individual

However individual your business, you can be sure

that all Rittal climate control systems provide a

comprehensive expert package:

● Exemplary energy efficiency

● Plus special project engineering

● Plus permanent innovative strength

● Plus typical Rittal high-quality production.

Rittal never loses sight of a project’s particular

customer requirements. The aim is always the same:

to produce maximum benefits for the customer.

Expertise +

Efficiency + Engineering + Innovation + High quality
Page 5: Erdinc  klima sk_broschuere_gb

System solutions from page 15For mechanical engineering .............................................................15For the IT sector ................................................................................19

For various ambient conditions.........................................................23For final assembly/handling systems................................................27

Project planning from page 31Basic principles for the use of climate control components ............32Cooling with ambient air ...................................................................35Cooling units .....................................................................................36

Liquid cooling IE/IT ...........................................................................37Enclosure heaters .............................................................................39

Cooling with ambient air from page 41Fan-and-filter units ............................................................................42Rack-mounted fans...........................................................................50Tangential fans..................................................................................50

Fan systems......................................................................................54Air/air heat exchangers.....................................................................60

Cooling units from page 67Modular climate control concept ......................................................68Roof-mounted cooling units ..............................................................72

Wall-mounted cooling units ..............................................................80Thermoelectric coolers .....................................................................96

Liquid cooling IE from page 99Air/water heat exchangers, roof-mounted .....................................100 Air/water heat exchangers, wall-mounted .................................... 100Direct Cooling Package (mounting plate cooling)......................... 110Recooling systems for water ..........................................................116

Recooling systems for oil ............................................................... 130Immersible recooling systems for oil/emulsion ............................. 132

Liquid cooling IT from page 135CRAC systems................................................................................136 Aisle containment........................................................................... 139Liquid Cooling Package (rack cooling) ......................................... 140

Chillers for IT cooling ......................................................................146 Water/water heat exchangers ........................................................150 Piping systems................................................................................154

Outdoor climate control from page 157Cooling units for CS modular enclosures .......................................160Heat exchangers for CS modular enclosures ................................161

Climate control units for Toptec CR............................................... 163Ex-proof climate control systems ...................................................164

Enclosure heaters from page 167Enclosure heaters ..........................................................................168

System accessories from page 171Air routing....................................................................................... 174Control/regulation........................................................................... 177Mounting accessories.................................................................... 181Cold Plate....................................................................................... 184

Liquid Cooling Package ................................................................ 186Filter technology ............................................................................ 189General .......................................................................................... 192Software service........................................................................... 195

Tips and tricks from page 197Cooling with ambient air .................................................................198Cooling units ...................................................................................207Liquid cooling IE .............................................................................217

Liquid cooling IT .............................................................................230Enclosure heaters ...........................................................................234Monitoring .......................................................................................235

Technical details from page 239Cooling with ambient air .................................................................240Cooling units ...................................................................................245Liquid cooling IE .............................................................................251

Liquid cooling IT .............................................................................266Enclosure heaters ...........................................................................267System accessories........................................................................268

Overview of products and approvals from page 271Overview of products and approvals .............................................272

Service .......................................................................................... 298List of model numbers................................................................. 300Index.............................................................................................. 303

3Rittal System Climate Control

Page 6: Erdinc  klima sk_broschuere_gb

Rittal climate expertise

4

Page 7: Erdinc  klima sk_broschuere_gb

Rittal climate expertise –

Outstanding breadth and quality.

Rittal cooling concepts are

synonymous with guaranteed

quality, from the product itself

right through to customer service.

Global availability, globally sought-

after. International approvals are

just as much part of the Rittal

“system concept” as uniform

system platforms for cooling units

and heat exchangers. Rittal’s

winning formula for climate control

expertise centres around one

basic idea, with infinite

possibilities. Flexible, inexpensive,

and exceptionally efficient. Rittal

cooling concepts are complete

solutions, precisely tailored to

your requirements and offering

exceptional added-value.

5

Page 8: Erdinc  klima sk_broschuere_gb

Total efficiency

6

Page 9: Erdinc  klima sk_broschuere_gb

Rittal efficiency – A fresh take on

creativity and value-added.

Thanks to its intensive research

and development work with

Pro Ozone cooling units, Rittal

has helped to focus the world’s

attention on “efficiency”. With a

host of innovative ideas such as

nano surface protection, the

Liquid Cooling product family and

coolants based on environmentally

neutral CO2, Rittal is renowned as

a world leader in this field.

Less is more, is our guiding

principle: Less consumption of

energy and resources on the

one hand, and more cost-

effectiveness and productivity

for customers on the other. Rittal’s

solutions successfully unite these

two principles.

7

Page 10: Erdinc  klima sk_broschuere_gb

Engineering partners

Page 11: Erdinc  klima sk_broschuere_gb

Rittal engineering – Building on

cooperation for a shared future.

Whether you require analysis of an

existing climate control concept,

or help planning a new one, Rittal

is a partner you can rely on. As

well as manufacturing system com-

ponents, Rittal also collaborates

closely with customers in the

research and development field.

We act as engineering partners

to our clients. A combination of

practical experience and project

planning leads to innovative,

comprehensive climate control

concepts.

Rittal’s customer service and main-

tenance divisions guarantee com-

plete customer satisfaction from

start to finish.

9

Page 12: Erdinc  klima sk_broschuere_gb

Innovative strength

10

Page 13: Erdinc  klima sk_broschuere_gb

Rittal’s innovative strength –

Deriving fresh growth from

ideas.

Innovation cannot be planned,

but it can be continuously re-

evaluated. This is Rittal’s approach

when tackling any new task. In an

instant, an idea is born, which the

Rittal laboratories then develop

into a new product solution. The

thermoelectric cooler, which cuts

energy consumption by more than

60 % compared with conventional

systems, is just one innovative

high-end example among many.

Rittal’s engineers are encouraged

to think outside the box and come

up with new solutions. These ideas

add value and help to make our

customers more competitive.

11

Page 14: Erdinc  klima sk_broschuere_gb

High quality production

12

Page 15: Erdinc  klima sk_broschuere_gb

Rittal high quality production –

Top quality begins with the

tiniest detail.

Rittal achieves outstanding high-

quality at its own production sites

and in-house research depart-

ments, development units and test

laboratories. This in turn enables

us to guarantee outstanding pro-

duct quality, because our process

quality is second to none. Every

department is broken down into

individual process units, each of

which plays a vital role in Rittal’s

overall quality. High quality pro-

duction relies on a perfect quality

assurance chain. This quality

standard reflects Rittal’s 100 %

customer dedication.

13

Page 16: Erdinc  klima sk_broschuere_gb

14

Page 17: Erdinc  klima sk_broschuere_gb

Rittal System Clim

Sys

tem

sol

utio

ns/M

echa

nica

l eng

inee

ring

Rittal system climate control for mechanical engineering

Precision scores an ace Whenever a higher enclosure protection category is required due to hot, metal dust-

laden or oily ambient conditions, Rittal liquid cooling concepts really come up

trumps.

Precise temperature control of machine and process cooling is another priority.

When cooling spindles with 40,000 rpm, for example, Rittal recooling systems

supply volumetric flows and coolant temperatures at precisely the required level.

Rittal system climate control is the key to a high level of dimensional accuracy,

consistently perfect workpieces, and stable production conditions.

Rittal recooling systems Energy-efficient cooling of liquid cooling media. ● A high level of temperature

accuracy. ● Powerful performance. ● Individual system solutions.

ate Control

Air/water heat exchangers The classic liquid cooling solution ● For extremely hot and dusty ambient

conditions ● To dissipate high heat loads without putting

thermal pressure on the ambient air.

Rittal DCP – Direct Cooling Package Direct cooling of power electronics inside the enclosure ● Using liquid-cooled mounting

plates, with or without fans ● No impairment to the protection

category ● With efficient frequency converter

cooling.

15

Page 18: Erdinc  klima sk_broschuere_gb

Sys

tem

exa

mpl

e

16

System exampleRittal system climate control for m

5

C

11 12

19 20

4

17

18

29

31

32

35

30

33

34

echanical engineering

A

B

2

6

10 8 9

13 16

16

14 15

26 27 28 25 2123 24 22

7

3 1

Example: Rittal system climate control for mechanical and plant engineeringThe air inside the hall is contaminated with metal swarf and oil mist, and is unable to absorb waste heat from the controllers and machine cooling system. A comprehensive Rittal liquid cooling concept with central recooling (1) provides a particularly efficient solution.

All function and safety-relevant components are remotely monitored with Rittal CMC-TC (3). The benefit to you: Added perfection and increased productivity.

Machining centre, welding robot

● The coolant temperature of the process emulsion is precisely coordinated with the machining cycle of the spindle rotating at

high speed, thanks to the immersion recooling system (7).

● Process heat from the welding robot and heat loss from the PC case of the robot controller (18) – case based on TS 8, equipped with air/water heat exchanger (17) – is effectively dissipated via Rittal recooling systems (1).

● The twin-doored enclosure ES 5000 with air/water heat exchanger, wall-mounted (8), is integrated into the design of the machines.

● Rittal thermoelectric coolers (16) are a particularly compact, efficient solution for cooling the Rittal Comfort Panel (13) command panels. The enclosure is custom-built and equipped to order, with a support arm system (15) tailored to your individual requirements.

Machine controller, low-voltage distributor

● Bayed Top enclosure system TS 8 (24). ● Rittal DCP: Liquid-cooled mounting plates

(Cold Plate) (21) for efficient frequency converter cooling and

● TopTherm air/water heat exchangers, roof-mounted (23) and wall-mounted (22), with internal controllers for monitoring and control, reliably dissipate the heat loss.

● The modular power supply is type-tested for global use (28).

Industrial IT and control room

● Network enclosures are effectively climate-controlled with a special, low-noise office cooling unit (29).

● EMC fan-and-filter units (30) cool the command controller in the pedestals of the TopConsole systems (33).

A

C

B

Rittal System Climate Control

Page 19: Erdinc  klima sk_broschuere_gb

Sys

tem

exa

mpl

e

Rittal system climate control for mechanical engineering

System example

Ex overpressure enclosure with integral enclosure cooling unit for zone II, gas (6)

System-wide Components Page

Central recooling system for enclosure and machine cooling 148

Piping systems 154 CMC-TC for monitoring access, climate, power supply Cat. 32, p. 808

Test workstation: Rittal Industrial Workstation with support arm CP-S, TFT screen, membrane keyboard

Cat. 32, p. 172

Air/water heat exchanger on the IW pedestal 63 Ex overpressure enclosure, climate-controlled 164

1

2

3

4

5

6

More compact, lightweight and efficient. The powerful thermoelectric cooling unit in a lightweight design (16). The eco-friendly climate control solution for command panels and small enclosures – an energy saving of more than 60 % compared with conven-tional industry systems.

Rittal DCP Cold Plate – Liquid-

Machining centre, welding robot Components Page

Immersible recooling system for process emulsion 132 Air/water heat exchanger, wall-mounted 104 Free-standing enclosure ES 5000, twin-door Cat. 32, p. 155Cable entry, cable routing Cat. 32, p. 1045Interior installation, mounting levels Cat. 32, p. 988Signal pillar (in conjunction with CMC-TC) Cat. 32, p. 1125Rittal Comfort Panel command panel Cat. 32, p. 192Monitors, keyboards, handles for the Comfort Panel Cat. 32, p. 1133CP-L support arm system for Comfort Panel Cat. 32, p. 250Thermoelectric cooler for Comfort Panel 97 Air/water heat exchanger, space-saving accommodated on the roof of the PC case 74

PS enclosure system, based on TS 8 Cat. 32, p. 168Base/plinth for PC case system Cat. 32, p. 892Bus enclosure Cat. 32, p. 120

A

7

8

9

10

11

12

13

14

15

16

17

18

19

20

cooled mounting plates (21)

Machine controller, low-voltage distributor Components Page

Rittal DCP Cold Plate – Liquid-cooled mounting plates 112

Air/water heat exchanger, wall-mounted 104 Air/water heat exchanger, roof-mounted 102 Baying enclosure system TS 8 Cat. 32, p. 136System accessories (base/plinth, walls, baying technique, locks, interior installation, cable routing) Cat. 32, p. 926

Ri4Power Form 1, heavy current power distributor Cat. 32, p. 438Ri4Power Form 2-4, form separation for low-voltage switchgear Cat. 32, p. 472

RiLine60, busbar systems Cat. 32, p. 350

B

21

22

23

24

25

26

27

28

17

Quiet performance: Office cooling units for network enclosures (29)

Rittal System Climate Control

Industrial IT and control room Components Page

Office cooling units for network enclosures 76 EMC fan-and-filter units for console systems 48Network enclosures, based on TS 8 Cat. 32, p. 745System accessories for IT (patch panels, component shelves) Cat. 32, p. 1013

TopConsole system Cat. 32, p. 156System accessories for consoles (base/plinth, interior installation) Cat. 32, p. 890

System accessories for the human/machine interface (keyboard drawers, TFT monitors, keyboards)

Cat. 32, p. 1115

C

29

30

31

32

33

34

35

Page 20: Erdinc  klima sk_broschuere_gb
Page 21: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Sys

tem

sol

utio

ns/IT

sec

tor

Rittal system climate control for data centres and IT

Cool and efficient! A high performance server in the data centre or in the middle of the office? Without

putting additional thermal pressure on the air-conditioning system? Without the

irritating noise of high-speed fan-and-filter units? All that can now be achieved very

easily!

Because Rittal Liquid Cooling concepts offer new framework conditions for your

IT infrastructures in terms of flexibility, safety and cost-efficiency. Independent of the

room situation, with almost zero heat and noise emissions, individual server CPUs

and complete server units or electronic components receive direct, highly effective

cooling.

Modular concepts, tailored precisely to your current requirements, and easily

scalable to meet future needs.

Rittal CRAC systems By using Rittal aisle containment,

● you can optimise air-conditioning of the room

● in conjunction with the Rittal CRAC system

● in terms of energy efficiency and cooling output.

LCP – Liquid Cooling PackageRittal solves the problem of climate control for high heat losses per rack with this system family.

● Extremely high heat loads are dissipated from the rack via the LCP (air/water heat exchanger).

● Additionally, this system also allows temperature-neutral expansion of the data centre.

Piping systems The Rittal piping system provides the link between the equipment and the refrigeration system.

● An optimum design and targeted media supply ensure efficient oper-ation of all cooling components.

19

Page 22: Erdinc  klima sk_broschuere_gb

Sys

tem

exa

mpl

e

20

System exampleRittal system climate control for th

A

9

30

1.1

8

10

13

11

12

292824

e IT sector

C

B

3

2

1

4

5

6

14

17

15

16

18

19

22

20

21

7

23272625

Example: Rittal system climate control for data centres and IT High heat loads in modern data centres, maximum availability, and the most energy-efficient climate control system available. To accommodate all three requirements, you will need an individual concept: Rittal liquid cooling IT. Redundant chillers (1), free cooling (1.1) and heat recovery (7). Piping systems are designed on a project-specific basis.

Data centre

● At the heart of this concept are server racks (9) with the option of aisle containment (8).

● The cold air required is blasted in via the raised floor by two CRAC systems (10).

● Other LCP-cooled (11) computer cases also operate without dissipating heat to the ambient air.

Development server room, UPS

● The server systems are cooled via LCPs (14), without a raised floor and without putting pressure on the climate control system. The heat is dissipated completely silently via the piping system.

● All server racks are based on the TS 8 enclosure platform (15).

● The dissipation of heat loss from the UPS is also integrated into the liquid cooling concept via the air/water heat exchanger.

● Alternative recooling via LCP Inline or LCP Extend.

Administration, monitoring

● All function and safety-relevant components are remotely monitored with Rittal CMC-TC. Messages and controls occur centrally in the control room (23).

● Super-low-noise roof-mounted fans (23) cool the network enclosures in the office. An even quieter alternative are air/water heat exchangers integrated into the coolant cycle.

● EMC fan-and-filter units with speed control (24) ensure fault-free operation and cooling of the control room consoles. The result: Targeted, low-noise, energy efficient!

A

B

C

Rittal System Climate Control

Page 23: Erdinc  klima sk_broschuere_gb

Sys

tem

exa

mpl

e

Rittal system climate control for the IT sector

System example

IT chiller, redundant configuration, also with free cooling (1).

System-wide Components Page

IT chiller, redundant configuration, also with free cooling device 146

or external free cooling function 147 Double pump unit 147 Water/water heat exchanger 152 Buffer store Water/water heat exchanger 152 Emergency water supply Heat recovery

1

1.1

2

3

4

5

6

7

CRAC systems for raised floor and aisle flooding (10)

Data centre with raised floor Components Page

Rittal aisle containment 139 Server racks for aisle containment CRAC systems for raised floor and aisle flooding 138 Room temperature-neutral server extension, cooling with LCP Standard, Plus or Smart Cat. 32, p. 726

Server racks, based on TS 8, bayed with LCPs Cat. 32, p. 777System accessories for server racks (cable management devices, monitor/keyboard unit, KVM switch, power distribution, plug-in modules, component shelves, base/plinths and much more besides)

Cat. 32, p. 890

A

8

9

10

11

12

13

Ambient air-neutral server cooling with LCP air/water heat exchangers (14)

Server room without raised floor, UPS Components Page

Separate servers in the development department, cooling with LCP Standard, Plus or Smart 140

LCP Inline 145 LCP Extend 143 Server racks, based on TS 8, bayed with LCPs Cat. 32, p. 777 System accessories for server racks Cat. 32, p. 787 Air/water heat exchangers for UPS cooling 104 UPS: Power Modular Concept PMC, rack basis TS 8 Cat. 32, p. 786

Power distribution: Power Distribution Rack PDR Cat. 32, p. 787Socket strips: Power System Module PSM Cat. 32, p. 789

B

14

15

16

17

18

19

20

21

22

Roof-mounted fan for the office sector (23)

Server and network administration, video monitoring Components Page

Roof-mounted fan for the office sector 76 EMC fan-and-filter units for console systemswith speed control 48

CMC-TC, modular system for monitoring climate, access and power supply Cat. 32, p. 806

Network enclosures, based on TS 8 Cat. 32, p. 745System accessories for IT (patch panels, component shelves) Cat. 32, p. 1013

TopConsole system Cat. 32, p. 156 System accessories for consoles (base/plinth, interior installation) Cat. 32, p. 890

System accessories for the human/machine interface (keyboard drawers, TFT monitors, keyboards)

Cat. 32, p. 1115

C

23

24

25

26

27

28

29

30

21Rittal System Climate Control

Page 24: Erdinc  klima sk_broschuere_gb
Page 25: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Sys

tem

sol

utio

ns/V

ario

us a

mbi

ent c

ondi

tions

Rittal system climate control for various ambient conditions

TopTherm-Plus Cleaning, phosphating, dipcoat-priming, spray-finishing, drying. The process

chain in a spray-finishing plant creates extremely varied ambient conditions – and

this also affects climate control of the controllers. Whether humidity, paint dust or

drying heat – these varying requirements are met by a single product range:

Rittal TopTherm-Plus cooling units.

With nano-coating of the heat exchanger surfaces, this ensures a high level of

efficiency and exceptional durability.

Rittal cooling units – Masters of energy efficiency

TopTherm-Plus cooling units Cooling units keep the enclosure internal temperature at a constant level, even to below room tempera-ture, with the air routing being tai-lored to individual requirements. Two separate circuits prevent the ingress of dust into the enclosure.

● Climate control doors ● Roof-mounted cooling units ● Wall-mounted cooling units

Electronic condensate evaporation Any condensate incurred is effectively evaporated and doesn’t need to be collected or dissipated.

Your value-added: ● Enhanced safety – No condensate drips

onto the floor. ● Time savings – No need to empty

condensate containers. ● Cost benefits – No need to lay condensate

tubing.

Master/slave mode In open bayed enclosure systems, cooling units or air/water heat exchangers with Comfort control are set to master/slave mode via a bus cable:

● Even temperature distribution across all sections of the enclosure.

● Simultaneous activation and deactivation of the devices.

● Parallel system and door limit switch function.

23

Page 26: Erdinc  klima sk_broschuere_gb

Sys

tem

exa

mpl

e

24

System exampleRittal system climate control for va

8 91211 7

14

16

15

B

C

rious ambient conditions

1 2 6

10

19

5

4

17

18

20

23

24

21

22

3

13

A

D

Example: Rittal system climate control for various ambient conditions Rittal TopTherm-Plus cooling units define the performance class of the future. Even under extremely varied ambient conditions, the control electronics are climate-controlled at a stable level and with a high degree of reliability. This is supplemented by plant-wide remote monitoring with Rittal CMC-TC (23) – this ensures availability and also saves money.

Control of the cleaning and priming line – high humidity

● Roof-mounted cooling units (1) and wall-mounted cooling units (2) in master/slave mode (3). The cooling output of several cooling units in a bayed enclosure suite is carefully coordinated to boost efficiency.

● Wall-mounted cooling units (2) may be internally mounted, partially internally mounted or externally mounted.

● Design variants: Standard, stainless steel (4), NEMA 4x, all including RiNano coating and condensate management.

Control of the spray-finishing and drying line – paint dust and heat

● Perfection in cooling and design with the modular climate control concept (7). The enclosure door and climate components are combined into one – no need for time-consuming assembly.

● Comfort controller (8) – the ideal control and safety electronics.

● Bayed EMC systems TS 8 (9) with a high level of RF attenuation.

Control and inspection workstations

● Test workstation with mini-cooling units (14).

● Individual configuration from IW modules (15) (Industrial Workstation).

● Command Panel (Optipanel) (17) with thermoelectric cooler (18) and individual panel design. Support arm system CP-XL. Configured entirely to your requirements.

Control room for the entire production process

● Server enclosures – based on TS 8 (21) – in the control room, bayed with LCP cooling (20).

● The central recooling system (19). supplies cooling medium in a particularly energy-efficient manner.

A

B

C

D

Rittal System Climate Control

Page 27: Erdinc  klima sk_broschuere_gb

Sys

tem

exa

mpl

e

Rittal system climate control for various ambient conditions

System example

Cooling units also available in stainless steel. TopTherm-Plus cooling units (1, 2) ensure constant temperatures for control electronics, regardless of variations in the ambient conditions.

Control of the cleaning and priming line Components Page

TopTherm-Plus cooling units, roof-mounted 74 TopTherm-Plus cooling units, wall-mounted 83 Master/slave mode 235 Cooling units in stainless steel 74 Bayed Top enclosure system TS 8 Cat. 32, p. 136System accessories for TS 8 (base/plinth, walls, doors, baying system, rail systems for interior installation, cable entry and much more besides)

Cat. 32, p. 926

A

1

2

3

4

5

6

TopTherm-Plus climate control doors combined with TS 8 enclosure system: Optimum airflow, no assembly work (7)

Mini-cooling unit, wall-mounted for efficient cooling of small

Control of the spray-finishing and drying line Components Page

TopTherm-Plus climate control doors combined with TS 8 70

Comfort controller 70 Bayed Top enclosure system TS 8 with EMC shielding Cat. 32, p. 329

Base/plinth (100/200 mm) for TS 8, compulsory when using climate control doors (modular climate control concept)

Cat. 32, p. 893

EMC system accessories Cat. 32, p. 572 Signal pillars Cat. 32, p. 1125Recooling system to cool the robot controller 127

B

7

8

9

10

11

12

13

Control and inspection workstations C

control and computer units (14)

Components Page

Mini-cooling unit, wall-mounted, on IW and TopConsole 83

Industrial Workstation (IW) Cat. 32, p. 172 TopConsole system (pedestal, desk unit) with TFT monitor in the Optipanel (CP-S support arm system) Cat. 32, p. 156

Comfort-Panel command panel on CP-XL support arm system Cat. 32, p. 192

Thermoelectric cooler 97

14

15

16

17

18

Server cooling with LCP: Horizontal cold air routing, no thermal pressure on the room, cost-effective, central recooling (19)

Control room for the entire production process Components Page

IT chiller with integral free cooling device 148 Server cooling with LCP 141 Server racks, based on TS 8, bayed with LCPs Cat. 32, p. 774 System accessories for server racks Cat. 32, p. 890 CMC-TC, modular system for monitoring climate, access and power supply Cat. 32, p. 806

System accessories for the human/machine interface (keyboard drawers, TFT monitors, keyboards)

Cat. 32, p. 1115

D

19

20

21

22

23

24

25Rittal System Climate Control

Page 28: Erdinc  klima sk_broschuere_gb
Page 29: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Sys

tem

sol

utio

ns/fi

nal a

ssem

bly,

han

dlin

g sy

stem

s

System climate control for final assembly and handling systems

Air versus heat Even in apparently non-critical ambient conditions, for example when there is an

adequate supply of clean, cool air, it is still worthwhile to provide climate control.

Here too, the aim is to achieve maximum reliability with exceptional efficiency.

Reliability and efficiency with fan-and-filter units: Temperature-dependent speed

control plus temperature and airflow monitoring.

Reliability and efficiency with air/air heat exchangers: Thanks to separate air

circuits (external/internal), dust remains excluded, while a micro-controller

provides temperature-dependent control and monitoring of key parameters.

The benefit to you: Efficient reliability at all times.

Fan-and-filter units Fan-and-filter units are ideal for dissipating heat loads cost-effectively.

● The prerequisite is that the ambient air must be relatively clean with a temperature below the desired enclosure internal temperature.

● The entire range of fan-and-filter units is also available with EMC shielding.

Air/air heat exchangers The requirement for using air/air heat exchangers is that the ambient temperature must be below the required enclosure internal temperature.

● Dust and contaminated ambient air is unable to ingress the enclosure, thanks to the two separate air circuits.

Machine, process and enclosure cooling ● Operational reliability thanks

to liquid cooling e.g. of high-frequency motor spindles and other drive technology.

● Precise workpiece machining thanks to precise, constant temperatures of the cooling media.

● In this way, temperature peaks inside enclosures – for example, in summer – can be effectively dissipated via air/water heat exchangers.

27

Page 30: Erdinc  klima sk_broschuere_gb

Sys

tem

exa

mpl

e

28

System exampleRittal system climate control for fin

D

A

18

1 2

3

4

6

8

10

9

24

26

25

30

27

31

28

29

11

5

al assembly/handling systems

C

B13

12

15

14

22

20

21

17

16

23

18

19

B 7

System climate control for final assembly and handling systems Air versus heat – Even in non-critical ambient conditions, it is still worthwhile providing systematic climate control. Here too, the aim is to achieve maximum reliability with exceptional efficiency.

Control of production plant and handling systems

Reliability and efficiency with air/air heat exchangers (1) to cool the free-standing enclosures ES 5000 (3).

● Thanks to separate air circuits (external/internal), dust is unable to ingress.

● A high operating ratio and minimal cleaning required.

● Monitoring of key parameters via a micro-controller.

Robot: Effective liquid cooling of controller and process

A central recooling system (7) “kills two birds with one stone”:

● Effective cooling of the PC case (8) via air/water heat exchangers (6).

● Precise cooling of machine spindles and/or welding heads.

Machine operation, quality assurance

Reliability and efficiency thanks to fan-and-filter units (21) for Industrial Workstations IW (20):

● Temperature-dependent speed control. ● Temperature and airflow monitoring. Exceptionally energy-efficient cooling of command panels with thermoelectric coolers (17).

Control room

The aim is to minimise the level of noise pollution in offices:

● This can be achieved with Office roof-mounted fans (24) and speed-controlled fan-and-filter units (27).

● Zero emissions of heat and noise, thanks to a liquid cooling concept.

A

B

C

D

Rittal System Climate Control

Page 31: Erdinc  klima sk_broschuere_gb

Sys

tem

exa

mpl

e

Rittal system climate control for final assembly/handling systems

System example

Platform concept: Air/air heat exchangers, wall-mounted, have the same mounting interface as TopTherm-Plus (1, 2)

Control of production plant and handling systems Components Page

Air/air heat exchangers, wall-mounted 62 Alternatively or additionally: Rittal TopTherm-Plus cooling units, wall-mounted 83

Free-standing enclosure ES 5000 Cat. 32, p. 154Viewing window Cat. 32, p. 944System accessories (base/plinth, cable entry and interior installation) Cat. 32, p. 890

A

1

2

3

4

5

Recooling system for central enclosure and process cooling (7)

Thermoelectric cooler for

Robot control and process cooling Components Page

Air/water heat exchanger, wall-mounted on the rear door of the PC case 104

Recooling system for central enclosure and process cooling 116

PS enclosure system, based on TS 8 Cat. 32, p. 168Base/plinth for PC case system Cat. 32, p. 892Bus enclosure Cat. 32, p. 120Signal pillar (in conjunction with CMC-TC) Cat. 32, p. 1125Rittal Comfort Panel command panel Cat. 32, p. 192Monitors, keyboards, handles for Comfort Panel Cat. 32, p. 1133CP-L support arm system for Comfort Panel Cat. 32, p. 250Thermoelectric cooler for Comfort Panel 97

B

6

7

8

9

10

11

12

13

14

15

Machine operation, quality assurance C

Comfort Panel (15, 17)

Components Page

Rittal Comfort Panel command panel Cat. 32, p. 192Thermoelectric cooler for Comfort Panel 97Monitors, keyboards, handles for Comfort Panel Cat. 32, p. 1133CP-L support arm system for Comfort Panel Cat. 32, p. 250Industrial workstation IW Cat. 32, p. 172Fan-and-filter unit, speed-controlled 44Optipanel with TFT monitor, CP-S support arm system Cat. 32, p. 204

Compact Panel, CP-S support arm system Cat. 32, p. 231

16

17

18

19

20

21

22

23

Effective cooling, on request with RF shielding: EMC fan-and-filter unit (27)

Control room Components Page

Office roof-mounted fans for network enclosures 55 Network enclosures, based on TS 8 Cat. 32, p. 745System accessories for IT (patch panels, component shelves) Cat. 32, p. 1013

EMC fan-and-filter units for console systems 48TopConsole system Cat. 32, p. 156System accessories for consoles (base/plinth, interior installation) Cat. 32, p. 890

System accessories for the human/machine interface (keyboard drawers, TFT monitors, keyboards)

Cat. 32, p. 1115

CMC-TC for monitoring access, climate, power supply Cat. 32, p. 806

D

24

25

26

27

28

29

30

31

29Rittal System Climate Control

Page 32: Erdinc  klima sk_broschuere_gb

30

Page 33: Erdinc  klima sk_broschuere_gb

Project planning

nn

ing

Basic principles for the use of climate control components from page 32Guide to selecting suitable units.......................................................32Heat dissipation ................................................................................33Calculation basis for enclosure climate control ................................34

Project planning software .................................................................34Interactive performance diagrams ...................................................34

Pro

ject

pla

Cooling with ambient air from page 35Fan-and-filter units ............................................................................35Air/air heat exchangers.....................................................................35

Cooling units from page 36Condensation and dehumidification of the enclosure air .................36Practical tips .....................................................................................36

Liquid cooling IE/IT from page 37Air/water heat exchangers ................................................................37Notes on water quality ......................................................................37Recooling systems/chillers ...............................................................38

Cooling water....................................................................................38Form for designing recooling systems .............................................38

Enclosure heaters from page 39Heating performance diagram..........................................................39

31Rittal System Climate Control

Page 34: Erdinc  klima sk_broschuere_gb

Pro

ject

pla

nn

ing

Project planning

32

Basic principles for the use of climate control components

Ambient conditions Enclosure interior problems

Heat Heat loss

Dust Condensate

Cool

Heat conduction

Convection Radiation

There are three basic forms of heat transfer:

Thermal conduction:Heat is transported by matter, without the matter itself being moved. The energy is passed from particle to particle.

Convection:Energy flows with the matter. The transport medium, e.g. a liquid or gas, takes up energy in the form of heat and dissipates energy as heat.

Radiation:Heat is passed from one body to another in the form of radiation energy, without a medium material.

The decisive factor for the type of heat dissipation to be used in enclosures is whether they are open (air-permeable) or closed (air-tight). Whereas in open enclosures, the heat is dissipated by means of air circulation, in closed enclosures the heat can only be dissipated via the enclosure wall.

Rittal cooling units provide the ideal system solution for ensuring an optimum operating temperature inside an air-tight enclosure, even at high external temperatures.

On the following pages, you will find a chrono-logical guide to help you to easily find the most suitable climate control solution.

Guide to selecting suitable unitsAs electronic components become ever smaller and are more densely packed in enclosures and electronic cases, systems are becoming increasingly sensitive to external factors such as dust, oil, moisture and temperature. Heat in particular is a deadly enemy of sensitive microelectronics.

For example, a general rule of thumb for semi-conductors is that an increase in the operating temperature of 10°C, in relation to the maximum permissible operating temperature, will shorten its service life by half.In order to guarantee proper functioning of the electronics, this heat needs to be dissipated.

Rittal System Climate Control

Page 35: Erdinc  klima sk_broschuere_gb

Project planning

Rittal System Climate Co

Pro

ject

pla

nn

ing

Protection category

Ti target > Tu max.

nt

IP 54 important

rol

No

Integrated louvres, air inlet/outlet grille

Roof ventilation, fan-and-filter unit

Yes

Air/air heat exchanger

Ti target < or = Tu max.

Cooling water cycleavailable at theinstallation site

Yes

Air/water heat exchanger

No

Cooling unit

Recooling system

Ti = Required internal temperature of enclosure [°C]Tu = Ambient temperature of enclosure [°C]

es contain detailed calculation formulae for your chosen option.

Fast selection

Heat dissipation Before you start, please consider your peripheral conditions such as external temperature, internal temperature and protection category. In order to achieve targeted, effective cooling, it is important to ensure correct calculation of the required climate control components and possible thermal analysis using computer-assisted flow models (CFD – Computational Fluid Dynamics).

Basic selection:

The following pag

Calculation of effective enclosure surface areaOf the variables required for calculation purposes, the effec-tive enclosure surface area A requires special explanation. The thermal output dissipated by the enclosure not only depends on its actual surface area; the installation type of the enclosure also plays a decisive role.

An enclosure which stands in a room unobstructed on all sides may dissipate more heat than one sited against a wall or in a niche. For this reason, there are precise specifications on how to calculate the effective enclosure surface area depending on the type of installation site. The formulae for calculating A are specified in DIN 57 660, part 500 and IEC 890 (see table below).

Enclosure installation type to IEC 890

Single enclosure, free-standing on all sidesSingle enclosure for wall mountingFirst or last enclosure in a suite, free-standing

First or last enclosure in a suite, for wallmountingEnclosure within a suite, free-standing

Enclosure within a suite, for wall mountingEnclosure within a suite, for wall mounting, covered roof surfaces

Installation typeto IEC 890 Formula for calculating A [m2]

A = 1.8 x H x (W + D) + 1.4 x W x DA = 1.4 x W x (H + D) + 1.8 x D x HA = 1.4 x D x (H + W) + 1.8 x W x HA = 1.4 x H x (W + D) + 1.4 x W x DA = 1.8 x W x H + 1.4 x W x D + D x HA = 1.4 x W x (H + D) + D x HA = 1.4 x W x H + 0.7 x W x D + D x HA = Effective enclosure surface areaW = Enclosure width [m]H = Enclosure height [m]D = Enclosure depth [m]

33

Page 36: Erdinc  klima sk_broschuere_gb

Pro

ject

pla

nn

ing

Project planning

34

General information

Calculation basis for enclosure climate controlIn natural convection, heat loss is dissipated to the outside via the enclosure panels. The prerequisite for this is that the ambient temperature must be lower than the temperature inside the enclosure. The maximum temperature increase (ΔT)max. which may occur inside an enclosure compared with the ambient air is calculated as follows:

Note:If the heat loss inside the enclosure is not known, this basic formula can be used to calculate actual heat loss, by measuring the ambient temperature Tu and the en-closure internal temperature Ti

QV = Heat loss installed in the enclosure [W]

QS = Heat emitted by the enclosure surface [W]QS > 0: Radiation (Ti > Tu)QS < 0: Irradiation (Ti < Tu)

QE = Required cooling output of an enclosure cooling unit [W]

QH = Required thermal output of an enclosure heater [W]

qw = Specific thermal output of a heat exchanger [W/K]

V = Required volumetric air flow of a fan-and-filter unit to maintain the maximum permissible temperature difference between the extracted air and the emitted air [m3/h]

ΔT = Ti – Tu = Max. admissible temperature difference [K]

A = Effective, heat loss-dissipating enclosure surface area to IEC 890 [m2]

k = Heat transfer coefficient [W/m2K] for sheet steel k = 5.5 W/m2K

.

...

.

.

.

(ΔT)max. = QV.

k � A

QS = A � k � ΔT (watts) .

Project planning software Rittal Therm Make calculation even easier and faster by using our project planning software Rittal Therm.Model No. see page 195.

EPLAN Cabinet Tool for the planning of enclosures and defining data for climate control calculations. Order information see page 195.

Interactive performance diagramsInteractive performance diagrams may be found on the Internet at www.rittal.com on the respective component data sheets in the “Downloads” section, under the heading “Characteristic curve”.

Enter your required interior temperature and the maximum exterior temperature in the relevant boxes, then click on “Calculate”. The heat loss that may be dissipated under these conditions will be displayed.

Rittal System Climate Control

Page 37: Erdinc  klima sk_broschuere_gb

Project planning

Pro

ject

pla

nn

ing

Fan-and-filter units, air/air heat exchangers

35Rittal System Climate Control

Fan-and-filter unitsThe following applies when calculating the volumetric air flow:

Performance diagram SK 3325. . . .

f = 3.1 m3 � K/Wh at h = ( 0 to 100)f = 3.2 m3 � K/Wh at h = (100 to 250)f = 3.3 m3 � K/Wh at h = (250 to 500)f = 3.4 m3 � K/Wh at h = (500 to 750)f = 3.5 m3 � K/Wh at h = (750 to 1000)f = Compensating factorh = Height above sea level [m]

V.

QV.

30 50 70 90 300 500 70010 20 40 60 80100 200 400 600800

100

200

300

400500600

8001000

1500

2000

30002500

Δ T

40 K

Δ T

35 K

Δ T

30 K

Δ T

25 K

Δ T

20 K

Δ T

15 K

Δ T

10 K

Δ T

5 K

Selection diagramThe styling of the vent louvres in Rittal fan-and-filter units guarantees exemplary stability of the air vol-umes in relation to pressure loss. The correct fan-and-filter unit has been chosen if the specified heat loss is dissipated whilst complying with the desired maximum enclosure internal temperature.

V = Volumetric flow (m3/h)

QV = Heat loss (W)

.

.

100 200 300

20

40

60

80

100

120

140

00

ΔPst

V.

50 Hz60 Hz

V = Volumetric flow (m3/h)ΔPst = Stat. pressure difference (Pa)

.

V = f � QV ΔT

. .

Air/air heat exchangersCalculate the specific thermal outputof the heat exchanger:

Selection diagram

Note: For ambient temperatures that are lower than the desired enclosure internal temperature, the use of air/air heat exchangers may be appropriate, particularly in cases where there are dust, oil and aggressive substances in the ambient air which must not be allowed to ingress the enclosure under any circumstances.

ΔT = Temperature difference (K)QV = Heat loss (W)qw = Specific thermal output (W/K)A = Enclosure surface area to IEC 890 (m2)k = Heat transfer coefficient (W/m2 K)

for sheet steel k = 5.5 W/m2 K

qw

ΔT

A

5 010152025

30

40

50

6070

10 30 50 70

024681012

3000 2000 1000 0 20 40 60 80

QV.

.

qw =QV – (A � ΔT � k)

ΔT

.

Page 38: Erdinc  klima sk_broschuere_gb

Project planningP

roje

ct p

lan

nin

g

Cooling units

36 Rittal System Climate Control

Cooling units

Condensation and dehumidification of enclosure air when using cooling unitsOne unavoidable side-effect of using cooling units is the dehumidification of the enclosure’s interior air. As it cools down, part of the humidity contained in the air condenses on the evaporator coil. This condensate must be reliably discharged from the enclosure. The amount of condensate occurring depends on relative humidity, the air temperature inside the enclosure and on the evaporator coil, and the air volume present in the enclosure. The Mollier h-x diagram shows the water content of air depending on its temperature and relative air humidity.

Mollier h-x diagram for calculating the water content of air.

Pd

T

x

50

45

40

35

30

25

20

15

10

5

0

– 5

– 10

– 15

– 200

50 10 15 20 25x2 x1 30 35 40

6030 45155 10 20 25 35 40 50 55

10%

20%

30%

40%

50%

60%

70%

80%

100%

90%

Pd = Water vapour partial pressure (mbar)T = Air temperature (°C)x = Water content (g/kg dry air)➀ = Relative humidity

Practical tipsIn all situations where optimum operating temperatures are required inside an enclosure, even at high external temperatures, a Rittal enclosure cooling unit can provide the right solution. It is even possible to cool the interior temperature of the enclosure to well below the ambient temperature. The favourable aerodynamic arrangement of the air inlet and outlet openings in the internal and external circuits ensures optimum air circulation inside the enclosure. This sample calculation will show you a quick, time-saving method for calculating a cooling unit.

For example:A cooling unit with a refrigeration output of 1500 watts commences operation with a temperature setting of Ti = 35°C. The relative ambient air humidity is 70 %. If air at 35°C is passed over the evaporator coil, the surface temperature of the evaporator coil (evaporation temperature of the refrigerant) is approximately 18°C. At the boundary layer adhering to the surface of the evaporator coil, water is deposited at the dew point. The difference Δx = x1 – x2 indicates how much condensation is incurred per kg of air with complete dehumidification. The leak-tightness of the enclosure has a decisive effect on the quantity of condensation.

Enclosure door closed:Only the enclosure volume is dehumidified.

Poorly sealed cable designs, damaged door seals and the attachment of display media to enclosure surfaces lead to increased rates of leakage in the enclosure. Hence, with a leakage rate of, say, 5 m3/h, a continuous condensate volume of up to 80 ml/h may occur.

Summary:Enclosure cooling units should only operate with the door closed.

● Seal the enclosure on all sides.● Use a door limit switch.● Use TÜV-tested equipment.● Only set the enclosure internal temperature as low as is

actually needed.

W = Water quantity in gV = Volume of the enclosure in m3 ρ = Density of air kg/m3 Δx = Difference of water content in g/kg dry air

(from the Mollier h-x diagram)

V = width � height � depth = 0.6 m � 2 m � 0.5 mV = 0.6 m3 W = V � ρ � Δx

= 0.6 m3 � 1.2 kg/m3 � 11 g/kgW = 7.92 g 8 ml

Calculate your required cooling output.

The quantity of condensation is calculated from the following equation:

QE = QV – k � A � ΔT . .

W = V � ρ � Δx

Page 39: Erdinc  klima sk_broschuere_gb

Project planning

Pro

ject

pla

nn

ing

Air/water heat exchangers

37Rittal System Climate Control

Air/water heat exchangers Calculate your required cooling output:

e.g. performance diagramAir/water heat exchanger 1000 W

TW

Ti

5250

10 15 20 25 30

500

750

1000

1250

1500

1750

QK.

45°C

35°C

25°C

VW = 400 l/hVW = 200 l/hVW = 100 l/h

.

.

.

Tw = Water inlet temperature (°C)

QK = Continuous useful cooling output (W)

Ti = Enclosure internal temperature (°C)

.

Notes on water qualityFor safe operation of the equipment, it is essential to observe the VGB guidelines on cooling water (VGB-R 455 P).

Cooling water must not contain any limescale deposits or loose debris; in other words, it should have a low level of hardness, particularly a low level of calcium hardness. For recooling within the plant, the calcium hardness should not be too high. On the other hand, however, the water should not be so soft that it attacks the operating materials. When recooling the cooling water, the salt content should not be allowed to increase excessively due to the evaporation of large quantities of water, since electrical conductivity increases as the concentration of dissolved substances rises, and the water thereby becomes more corrosive. For this reason, not only is it always necessary to add a corresponding quantity of fresh water, but also to remove part of the enriched water.

Gypsiferous water is unsuitable for cooling purposes because it has a tendency to form boiler scale, which is particularly difficult to remove. Furthermore, cooling water should be free from iron and manganese, because otherwise deposits may occur which settle in the pipes and block them. At best, organic substances should only be present in small quantities, because otherwise sludge deposits and microbiological contamination may occur.

Material of the water-carrying parts Hydrological data CuAl V4A1) pH value 7 – 8.5 6 – 9Calcium hardness > 3 < 8° dH 1 – 12° dHFree carbonic acid 8 – 15 mg/dm3 1 – 100 mg/dm3 Accompanying carbonic acid 8 – 15 mg/dm3 freeAggressive carbonic acid 0 mg/dm3 0 – 400 mg/dm3 Sulphides free freeOxygen < 10 mg/dm3 < 10 mg/dm3 Chloride ions < 50 mg/dm3 < 200 mg/dm3 Sulphate ions < 250 mg/dm3 < 500 mg/dm3 Nitrates and nitrites < 10 mg/dm3 < 100 mg/dm3 COD < 7 mg/dm3 < 40 mg/dm3 Ammonia < 5 mg/dm3 < 20 mg/dm3 Iron < 0.2 mg/dm3 freeManganese < 0.2 mg/dm3 freeConductivity < 2200 μS/cm < 4000 μS/cmResidue on evaporation < 500 mg/dm3 < 200 mg/dm3 Potassium permanganate consumption < 25 mg/dm3 < 40 mg/dm3

Suspended matter

< 3 mg/dm3 > 3 < 15 mg/dm3 partial current purification recommended> 15 mg/dm3 continuous purification recommended

1) The complete absence of corrosion under experimental conditions suggests that solutions with a significantly higher salt content and greater corrosion potential (such as seawater) may still be tolerated.

QE = QV – k � A � ΔT . .

Page 40: Erdinc  klima sk_broschuere_gb

Project planningP

roje

ct p

lan

nin

g

Recooling systems/chillers

38 Rittal System Climate Control

Recooling systems/chillersRecooling systems may be used in all situations where a high cooling load is required, e.g. in process and machine cooling, in media cooling or when dissipating heat loss from enclosures via air/water heat exchangers.

Our project engineers will be happy to help you design a recooling system for your specific application area. An overview of the planning data required for this purpose can also be found on the Internet at www.rittal.com in the section on system climate control/process and machine cooling.

Cooling waterPreparation and maintenance of the water in recooling systemsDepending on the type of installation to be cooled, certain requirements are placed on the cooling water with respect to purity. According to the level of contamination and the size and design of the recooling systems, a suitable process is used to prepare and/or maintain the water. The most common types of contamination and most frequently used techniques to eliminate them in industrial cooling are:

Contamination of the water Procedure

Mechanical contamination

Filtering of water via– Mesh filter– Gravel filter– Cartridge filter– Precoated filter

Excessive hardness Water softening via ion exchange

Moderate content of mechanical contaminants and hardeners

Addition of stabilisers and/or dispersing agents to the water

Moderate content of chemical contaminants

Addition of passifiers and/or inhibitors to the water

Biological contaminants, slime bacteria and algae Addition of biocides to the water

Form for designing recooling systemsSimply tick the type of system, and select or enter the criteria to suit your requirements. Please also include your name, company and address. Once you have completed the form, you can generate a PDF to print out or send via e-mail as an enquiry. The form for the design of recooling systems may be found on the Internet at:

www.rittal.com –> Products –> System climate control

–> Product portfolio –> Process and machine cooling –> Recooling systems

–> Form for designing recooling systems

Page 41: Erdinc  klima sk_broschuere_gb

Project planning

Pro

ject

pla

nn

ing

Enclosure heaters

39Rittal System Climate Control

Enclosure heatersThe required thermal output is calculated from:

Heating performance diagram

QH = Thermal output (W)A = Enclosure surface area to IEC 890 (m2)ΔT = Temperature difference (K)

Based on:Interior siting, static air, heat transfer coefficient k = 5.5 W/m2 K

For exterior siting (moving air): Double the determined thermal output

A

ΔT

1

1.5

2

3

4568

10

15 30 50 150 300 50010 20 40 60 80 100 200

20

30

2 5 7.5 10

15

QH.

.

QH = A � ΔT � k .

Page 42: Erdinc  klima sk_broschuere_gb
Page 43: Erdinc  klima sk_broschuere_gb

Cooling with ambient air

Co

olin

g w

ith

am

bie

nt

air

Fan-and-filter units from page 42

� � Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . . . 20/55 m3/h. . . . . . . . 44� � Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . 105/180 m3/h. . . . . . . . 45� � Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230 m3/h. . . . . . . . 46� � Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . 550/700 m3/h. . . . . . . . 47

� � � Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . 20 – 105 m3/h. . . . . . . . 48� � � Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . 180 – 700 m3/h. . . . . . . . 49

Rack-mounted fans from page 50

� � for 482.6 mm (19˝) . . . . . . . . . . . . . . . . . . . . . . . . 320/480 m3/h. . . . . . . . 52

Tangential fans from page 50

� � for 482.6 mm (19˝) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320 m3/h. . . . . . . . 53

Fan systems from page 50

� � RTT roof-mounted fan and vent attachment. . . . . 400/800 m3/h. . . . . . . . 54� � Roof-mounted fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 360 m3/h. . . . . . . . 54� Roof-mounted fan for the office sector. . . . . . . . . . . 1500 m3/h. . . . . . . . 55

� Enclosure internal fan . . . . . . . . . . . . . . . . . . . . . . . . . 160 m3/h. . . . . . . . 55� Fan mounting plate. . . . . . . . . . . . . . . . . . . . . . . . . . . 180 m3/h. . . . . . . . 56

Fan expansion kit . . . . . . . . . . . . . . . . . . . . . . . . 108/184 m3/h. . . . . . . . 56� Fan mounting plate DC . . . . . . . . . . . . . . . . . . . . . . . 990 m3/h. . . . . . . . 57� Fan roof, modular, two-piece . . . . . . . . . . . . . . . . . . . . 180 m3/h. . . . . . . . 58� Fan unit, active . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160 m3/h. . . . . . . . 58

� � Door-mounted fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . 600 m3/h. . . . . . . . 59� Fan expansion kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 m3/h. . . . . . . . 59

With EMC shielding Standardised installation 482.6 mm (19˝) installation

Rittal System Clima

Interchangeable airflow direction

Passive ventilation

Air/air heat exchangers from page 60

� � � Wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12/62 W/K. . . . . . . . 62� � Wall-mounted with controller . . . . . . . . . . . . . . . 17.5 to 90 W/K. . . . . . . . 63

� � Wall-mounted, railway-compatible version . . . . . .27 to 98 W/K. . . . . . . . 64 � Roof-mounted. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 W/K. . . . . . . . 65

Standardised installation

Suitable for command panels

Wall-mounted

Roof-mounted

24 V DC and 110 V DC

41te Control

Page 44: Erdinc  klima sk_broschuere_gb

Fan-

and-

filte

r un

its

Fan-and-filter units

Fan-and-filter units are ideal for dissipating heat loads

cost-effectively. The prerequisite is that the ambient air

must be relatively clean with a temperature below the

desired enclosure internal temperature. The entire

range of fan-and-filter units is now also available with

EMC shielding and all required rated voltages.

42 Rittal System Climate Control

Page 45: Erdinc  klima sk_broschuere_gb

Fan-

and-

filte

r un

its

Aesthetics and functionTypical of the Rittal fan-and-filter unit design is the extremely low build height. The super-slimline vent grille guarantees optimum air throughput with low noise generation. Combined with the technical features, Rittal fan-and-filter units meet all application requirements.

Rittal System Climate Control

Fast assemblySuper-fast clip-on mountingThis guarantees fast, completely secure attachment of the fan-and-filter unit. The prerequisites for protection category IP 54 are met as standard. Screws are not required. Removal of the louvred grille, like-wise without any screws, means that filter mat changes can be achieved in next to no time.

Draw-in or extract?The air direction may be quickly reversed from draw-in (default setting) to extracting. Simply rotate the fan through 180°.

Application diversity and functionsParticularly for applications in the food industry, the hose-proof hood prevents the ingress of damp. The protection category of IP 56 is achieved in conjunction with filter mats.

Not always full power!At lower ambient temperatures, the air throughput may be reduced. By adapting the fan-and-filter speed to match the temperature using a controller, noise generation is reduced.

Also available with EMC shieldingAll fan-and-filter units and outlet filters are alternatively available with EMC shielding. The required conductive connection is achieved via a metallic coating on the fan-and-filter unit housing and a special sealing frame.

Benefits at a glance● Air throughput from 20 m3/h to 700 m3/h● Super-fast assembly● IP 54 as standard● Air flow direction may be reversed from

draw-in (default setting) to extracting● All fans also available with EMC shielding● Minimal installation depth● Fan also bayable

Important● The prescribed heat loss and the

maximum anticipated ambient temperature define the required volumetric flow

● Always use the fan-and-filter units and outlet filters together

Tips and tricksApplications see page 198

Selection criteria see page 199

Assembly see page 200

43

Page 46: Erdinc  klima sk_broschuere_gb

Fan-

a

Fan-and-filter unitsAir throughput 20/55 m3/h

H2

B2

T2

B1

T1

H1

B = WidthT = Depth

nd-f

ilter

uni

ts

Su

pply includes:Fan-and-filter units ready for installation, including filter mats.

German registered design no. M 93 04 846

Approvals, see page 272.

Performance diagrams, available on the Internet.

Model No. SK fan-and-filter unit 3321.107 3321.117 3321.027 3321.0471) 3322.107 3322.117 3322.027 3322.0471)

Rated operating voltage V/Hz 230, 50/60 115, 50/60 24 (DC) 48 (DC) 230, 50/60 115, 50/60 24 (DC) 48 (DC)

Dimensions in mmB1/H1 116.5 148.5B2/H2 92 + 0.82) 1242)

T1 10 10.5Max. installation depth mm T2 42 57Air throughput, unimpeded air flow 20/25 m3/h 20 m3/h 55/66 m3/h 55 m3/h

Air throughput with outlet filter including standard filter mat 1 x SK 3321.207: 15/18 m3/h 1 x SK 3322.207: 43/50 m3/h

Axial fan Self-starting shaded pole motor DC motor Self-starting

shaded pole motor DC motor

Rated current max. 69 mA58 mA

138 mA115 mA 125 mA 90 mA 0.12 A

0.11 A0.24 A0.23 A 170 mA 90 mA

Power 12.5 W/10.3 W 3.0 W 4.1 W 19.0 W/18.0 W 4.0 W 4.4 WNoise level 41/46 dB (A) 41 dB (A) 46/49 dB (A) 42 dB (A)Temperature range –10°C to +55°CColour RAL 70353)

Protection category to EN 60 529 IP 54 standard IP 56 when using a hose-proof hood

Model No. SK outlet filter 3321.207 3322.207

Accessories Packs of PageSpare filter mats 5 3321.700 3322.700 191 Thermostat 1 3110.000 178 Temperature indicator 1 3114.100 3114.115 3114.024 – 3114.100 3114.115 3114.024 – 177 Speed control 1 3120.000 3120.115 – – 3120.000 3120.115 – – 179 Hose-proof hood 1 3321.800 3322.800 193

1) Delivery times on request.2) For metal thickness > 2.5 mm the cut-out B2/H2 must be 1 mm larger. 3) RAL 7032 on request.Special voltages available on request. We reserve the right to make technical modifications.

44 Rittal System Climate Control

Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195

Page 47: Erdinc  klima sk_broschuere_gb

Air throughput 105/180 m3/h

Fan-and-filter units

and-

filte

r un

its

H2

B2

T2

B1

T1

H1

B = WidthT = Depth

Su

Fan-

pply includes:Fan-and-filter units ready for installation, including filter mats.

German registered design no. M 93 04 846

Approvals, see page 272.

Performance diagrams, available on the Internet.

Model No. SK fan-and-filter unit 3323.107 3323.117 3323.027 3323.0471) 3324.107 3324.117 3324.027 3324.0471)

Rated operating voltage V/Hz 230, 50/60 115, 50/60 24 (DC) 48 (DC) 230, 50/60 115, 50/60 24 (DC) 48 (DC)

Dimensions in mmB1/H1 204 255B2/H2 1772) 2242)

T1 12.5 12.5Max. installation depth mm T2 82.5 105Air throughput, unimpeded air flow 105/120 m3/h 105 m3/h 180/160 m3/h 180 m3/h

Air throughput with outlet filter including standard filter mat

1 x SK 3323.207: 71/82 m3/h 2 x SK 3323.207: 85/98 m3/h 1 x SK 3325.207: 78/90 m3/h

1 x SK 3325.207: 115/95 m3/h 2 x SK 3325.207: 165/140 m3/h 1 x SK 3326.207: 155/130 m3/h

Axial fan Self-starting shaded pole motor DC motor Self-starting

shaded pole motor DC motor

Rated current max. 0.12 A0.11 A

0.24 A0.23 A 170 mA 90 mA 0.19 A

0.20 A0.38 A0.40 A 0.3 A 0.34 A

Power 19.0 W/18.0 W 4.0 W 4.3 W 30.0 W/35.0 W 7.2 W 14.0 WNoise level 46/49 dB (A) 42 dB (A) 52/48 dB (A) 52 dB (A)Temperature range –10°C to +55°CColour RAL 70353)

Protection category to EN 60 529IP 54 standard IP 55 when using an additional fine filter mat IP 56 when using an additional fine filter mat and hose-proof hood

Model No. SK outlet filter 3323.207 3325.207

Accessories Packs of PageSpare filter mats 5 3171.100 3172.100 191 Fine filter mats 5 3181.100 3182.100 191 Thermostat 1 3110.000 178 Temperature indicator 1 3114.100 3114.115 3114.024 – 3114.100 3114.115 3114.024 – 177 Speed control 1 3120.000 3120.115 – – 3120.000 3120.115 – – 179 Hose-proof hood 1 3323.800 3324.800 193

1) Delivery times available on request. 2) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger. 3) RAL 7032 on request. Special voltages available on request. We reserve the right to make technical modifications.

45Rittal System Climate Control

Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195

Page 48: Erdinc  klima sk_broschuere_gb

Fan-and-filter uAir throughput 230 m3/h

Fan-

a

nits

H2

B2

T2

B1

T1

H1

B = WidthT = Depth

nd-f

ilter

uni

ts

Su

pply includes:Fan-and-filter units ready for installation, including filter mats.

German registered design no. M 93 04 846

Approvals, see page 272.

Performance diagrams, available on the Internet.

Model No. SK fan-and-filter unit 3325.107 3325.117 3325.027 3325.0471)

Rated operating voltage V/Hz 230, 50/60 115, 50/60 24 (DC) 48 (DC)

Dimensions in mmB1/H1 255B2/H2 2242)

T1 12.5Max. installation depth mm T2 105Air throughput, unimpeded air flow 230/265 m3/h 230 m3/h

Air throughput with outlet filter including standard filter mat

1 x SK 3325.207: 170/205 m3/h 2 x SK 3325.207: 200/230 m3/h 1 x SK 3326.207: 190/215 m3/h

Axial fan Self-starting shaded pole motor DC motor

Rated current max. 0.28 A0.24 A

0.53 A0.49 A 0.59 A 0.31 A

Power 41.0 W/38.0 W 14.0 W 15.0 WNoise level 54/56 dB (A) 54 dB (A)Temperature range –10°C to +55°CColour RAL 70353)

Protection categoryto EN 60 529

IP 54 standard IP 55 when using an additional fine filter mat IP 56 when using an additional fine filter mat and hose-proof hood

Model No. SK outlet filter 3325.207

Accessories Packs of PageSpare filter mats 5 3172.100 191 Fine filter mats 5 3182.100 191 Thermostat 1 3110.000 178 Temperature indicator 1 3114.100 3114.115 3114.024 – 177 Speed control 1 3120.000 3120.115 – – 179 Hose-proof hood 1 3324.800 193

1) Delivery times available on request. 2) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger. 3) RAL 7032 on request. Special voltages available on request. We reserve the right to make technical modifications.

46 Rittal System Climate Control

Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195

Page 49: Erdinc  klima sk_broschuere_gb

Air throughput 550/700 m3/h

Fan-and-filter units

nd-f

ilter

uni

ts

H2

B2

T2

B1

T1

H1

B = WidthT = Depth

Su

Fan-

a

pply includes:Fan-and-filter units ready for installation, including filter mats.

German registered design no. M 93 04 846

Approvals, see page 272.

Performance diagrams, available on the Internet.

Model No. SK fan-and-filter unit 3326.107 3326.117 3327.107 3327.117 3327.147

Rated operating voltage V/Hz 230, 50/60 115, 50/60 230, 50/60 115, 50/60 400/460, 3~, 50/60

Dimensions in mmB1/H1 323B2/H2 2921)

T1 12.5Max. installation depth mm T2 129 145Air throughput, unimpeded air flow 550/600 m3/h 700/720 m3/h

Air throughput with outlet filter including standard filter mat

1 x SK 3326.207: 360/390 m3/h 2 x SK 3326.207: 440/495 m3/h 1 x SK 3326.207: 525/575 m3/h

Axial fan Capacitor motor Rotary current motor

Rated current max. 0.29 A0.35 A

0.58 A0.70 A

0.65 A0.95 A

1.5 A2.0 A

0.27 A0.37 A

Power 64.0 W/80.0 W 115.0 W/212.0 W 167.0 W/230.0 W 146.0 W/220.0 WNoise level 59/61 dB (A) 75/76 dB (A)Temperature range –10°C to +55°CColour RAL 70352)

Protection category to EN 60 529

IP 54 standard IP 55 when using an additional fine filter mat IP 56 when using an additional fine filter mat and hose-proof hood

Model No. SK outlet filter 3326.207

Accessories Packs of PageSpare filter mats 5 3173.100 3327.700 191 Fine filter mats 5 3183.100 191 Thermostat 1 3110.000 – 178 Temperature indicator 1 3114.100 3114.115 3114.100 3114.115 – 177 Speed control 1 3120.000 3120.115 3120.000 – – 179 Hose-proof hood 1 3326.800 193

1) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger. 2) RAL 7032 on request. Special voltages available on request. We reserve the right to make technical modifications.

47Rittal System Climate Control

Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195

Page 50: Erdinc  klima sk_broschuere_gb

Fan-

and-

filte

Fan-and-filterAir throughput 20 – 1

units – EMC05 m3/h

T1

B T =

H2

B2

T2

B1

H1

= Width Depth

r un

its –

EM

C

Su

pply includes:Complete fan-and-filter units ready for installation, including drilling template, filter mat and assembly parts.

Approvals, see page 273.

Performance diagrams, available on the Internet.

Model No. SK fan-and-filter unit 3321.607 3321.6171) 3322.607 3322.6171) 3323.607 3323.6171)

Rated operating voltage V/Hz 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60

Dimensions in mmB1/H1 116.5 148.5 204B2/H2 92 + 0.82) 1242) 1772)

T1 10 10.5 12.5Max. installation depth mm T2 42 57 82.5Air throughput, unimpeded air flow 20/25 m3/h 55/66 m3/h 105/120 m3/h

Air throughput with outlet filter including standard filter mat 1 x 3321.267: 15/18 m3/h

1 x 3322.267: 43/50 m3/h2 x 3322.267: 48/55 m3/h1 x 3323.267: 48/55 m3/h

1 x 3323.267: 71/82 m3/h2 x 3323.267: 85/98 m3/h1 x 3325.267: 78/90 m3/h

Axial fan Self-starting shaded pole motor

Rated current max. 69 mA/ 58 mA

138 mA/ 115 mA

0.12 A/ 0.11 A

0.24 A/ 0.23 A

0.12 A/ 0.11 A

0.24 A/ 0.23 A

Power 12.5 W/10.3 W 19.0 W/18.0 WNoise level 41/46 dB (A) 46/49 dB (A)Temperature range –10°C to +55°CColour RAL 70353)

Protection category to EN 60 529 IP 54 standardModel No. SK outlet filter – EMC 3321.267 3322.267 3323.267

Accessories Packs of PageSpare filter mats 5 3321.700 3322.700 3171.100 191 Fine filter mats 5 – 3181.100 191 Thermostat 1 3110.000 178 Temperature indicator 1 3114.100 3114.115 3114.100 3114.115 3114.100 3114.115 177 Speed control 1 3120.000 3120.115 3120.000 3120.115 3120.000 3120.115 179 Hose-proof hood 1 3321.800 3322.800 3323.800 193

1) Delivery times available on request. 2) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger. 3) RAL 7032 on request. Special voltages available on request. We reserve the right to make technical modifications.

48 Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 51: Erdinc  klima sk_broschuere_gb

T

BT

Air throughput 180 – 700 m3/h

Fan-and-filter units – EMC

r un

its –

EM

C

H2

B2

T2

B1

1

H1

= Width = Depth

Su

Fan-

and-

filte

pply includes:Complete fan-and-filter units ready for installation, including drilling template, filter mat and assembly parts.

Approvals, see page 273.

Performance diagrams, available on the Internet.

Model No. SK fan-and-filter unit 3324.607 3324.6171) 3325.607 3325.6171) 3326.607 3326.6171) 3327.607 3327.6171)

Rated operating voltage V/Hz 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60

Dimensions in mmB1/H1 255 323B2/H2 2242) 2922)

T1 12.5 12.5Max. installation depth mm T2 105 129 145Air throughput, unimpeded air flow 180/160 m3/h 230/265 m3/h 550/600 m3/h 700/720 m3/h

Air throughput with outlet filter including standard filter mat

1 x 3325.267: 115/95 m3/h2 x 3325.267: 165/140 m3/h1 x 3326.267: 155/130 m3/h

1 x 3325.267: 170/205 m3/h2 x 3325.267: 200/230 m3/h1 x 3326.267: 190/215 m3/h

1 x 3325.267: 170/205 m3/h2 x 3325.267: 200/230 m3/h1 x 3326.267: 360/390 m3/h

1 x 3326.267: 525/575 m3/h

Axial fan Self-starting shaded pole motor Capacitor motor

Rated current max. 0.19 A/ 0.20 A

0.38 A/ 0.40 A

0.28 A/ 0.24 A

0.53 A/ 0.49 A

0.29 A/ 0.35 A

0.58 A/ 0.70 A

0.65 A/ 0.95 A

1.50 A/ 2.00 A

Power 30.0 W/35.0 W

41.0 W/38.0 W

64.0 W/80.0 W

155.0 W/212.0 W

167.0 W/230.0 W

Noise level 52/48 dB (A) 54/56 dB (A) 59/61 dB (A) 75/76 dB (A)Temperature range –10°C to +55°CColour RAL 70353)

Protection category to EN 60 529 IP 54 standardModel No. SK outlet filter – EMC 3325.267 3326.267

Accessories Packs of PageSpare filter mats 5 3172.100 3173.100 3327.700 191 Fine filter mats 5 3182.100 3183.100 191 Thermostat 1 3110.000 178 Temperature indicator 1 3114.100 3114.115 3114.100 3114.115 3114.100 3114.115 3114.100 3114.115 177 Speed control 1 3120.000 3120.115 3120.000 3120.115 3120.000 3120.115 3120.000 3120.115 179 Hose-proof hood 1 3324.800 3326.800 193

1) Delivery times available on request. 2) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger. 3) RAL 7032 on request. Special voltages available on request. We reserve the right to make technical modifications.

49Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 52: Erdinc  klima sk_broschuere_gb

Rac

k-m

ount

ed/ta

ngen

tial f

ans,

fan

syst

ems

Rack-mounted/tangential fans, fan systems

All rack-mounted climate control components are fitted

directly onto the 482.6 mm (19˝) mounting level for

subracks. Positioning directly beneath the electronic

components ensures effective cooling, and prevents

the formation of hot-spots.

Ready-to-use, wired modules equipped with fans for

numerous Rittal enclosure system platforms offer

effective air throughput and minimal assembly work.

Fan roofs, door-mounted fans for server enclosures,

internal fan mounting panels and enclosure internal

fans are all available.

50 Rittal System Climate Control

Page 53: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Rac

k-m

ount

ed/ta

ngen

tial f

ans,

fan

syst

ems

Rack-mounted fan moduleThe rack-mounted fan slides into the guide frame like a drawer. Connectors on the rear ensure immediate contact. Installation options for the guide frame: Directly in the subrack, via two mounting brackets on the 482.6 mm (19˝) mounting angles. Ideal for avoiding hot-spots in fully populated enclosures.

Tangential fans320 m3/h air throughput, 2 UThe high air throughput means that Rittal tangential fans are capable of dissipating large heat losses from the enclosure. The minimal noise generation of 52 dB creates a pleasant working environment. Front outlet grille 2 U for hot air outlet to the outside in the upper section of the enclosure.

For the office sector: Roof-mounted fanLow noise generation and high performance for sensitive office areas. Unit consisting of TS roof plate and fan.

Benefits at a glanceRack-mounted/tangential fans ● Rapid installation on 482.6 mm (19˝)

mounting levels● Direct, effective dissipation of heat loss,

thanks to positioning beneath the assemblies

● No externally mounted equipment to disrupt the aesthetic appearance of the enclosure

Fan systems ● Fast assembly● Targeted air routing to avoid hot-spots● Perfect system integration

Tips and tricksApplications see page 201

51

Page 54: Erdinc  klima sk_broschuere_gb

Rac

k-m

Rack-mountedfor 482.6 mm (19˝), air t

fanshroughput 320/480 m3/h

482.6 (19˝)

180200

73

410

100

1 HE

1

426482.6 (19˝)

206214

55

432

120

1 HE

2

ount

ed fa

ns

Ra

ck-mounted fan/Vario rack-mounted fan supply includes: Wired unit ready for connection, including terminal strip and assembly parts.

Guide frame supply includes: Guide frame including connec-tor and fitted connection cable (3 m), bracket for optional attachment to the 482.6 mm (19˝) system, assembly parts.

Also required:

Remember to order the appropriate guide frame for your chosen application.

Approvals, see page 273.

Detailed drawing,see page 240.

Performance diagrams, available on the Internet.

Rack-mounted fans Vario rack-mounted fans

Model No. SK Model No. SK

2 fans Distance between axes 85 mm 3340.0241) 3340.1151) 3340.230 – – 3350.0241) 3350.1151) 3350.2301) –

3 fans Distance between axes 85 mm 3341.0241) 3341.115 3341.230 – 9769.0021)2) 3351.0241) 3351.1151) 3351.230 –

3 fans Distance between axes 105 mm 3342.024 3342.1151) 3342.230 3342.5002)3) – 3352.0241) 3352.1151) 3352.230 3352.5003)

Rated operating voltage V 24 V (DC) 115 V (AC) 230 V (AC)24 V (DC) 115 – 230 V (AC)

36 V (DC) up to 72 V (DC)

24 V (DC) 115 V (AC) 230 V (AC)24 V (DC) 115 – 230 V (AC)

Model No. SKmatching guide frame – – – – – 3356.1001) 3355.100 3355.100 3357.100

Accessories PageTemperature indicator230 V (AC) 714 3114.100 3114.115 3114.100 3114.024 – 3114.100 3114.115 3114.100 3114.024

Thermostat 715 3110.000Speed control 716 3120.000 3120.115 3120.000 – – 3120.000 3120.115 3120.000 –

1 2

Technical specifications

3341.230 3341.115 3341.024

Model No. SK/CS 3340.230 3350.230

3340.115 3350.115

3340.024 3350.024

3351.230 3342.230 3352.230

3351.115 3342.115 3352.115

3351.024 3342.024 3352.024

3342.5002) 3352.5002) 9769.002

Rated operating voltage V, Hz

AC 230 V 50/60 Hz

AC 115 V 50/60 Hz

DC 24 V –

AC 230 V 50/60 Hz

AC 115 V 50/60 Hz

DC 24 V –

DC 24 V AC 115 – 230 V 50/60 Hz

36 V (DC) up to 72 V (DC)

Rated current max. 0.24 A/ 0.22 A

0.46 A/ 0.46 A 0.49 A 0.36 A/

0.33 A0.69 A/ 0.69 A 0.74 A 0.85 A 0.28 A

Pre-fuse T 6.0 A 6.0 ANumber of fans 2 3 3Air throughput, unimpeded air flow 320 m3/h 480 m3/h 250 m3/h

Temperature range –10°C to +55°C –33°C to +55°C

Noise level 51 dB (A) 52 dB (A) 51 dB (A) 51 dB (A) 52 dB (A) 51 dB (A) 52 dB (A)1) Delivery times available on request. 2) Rack-mounted fan for metric mounting angles available on request. 3) Version with monitoring

52 Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 55: Erdinc  klima sk_broschuere_gb

for 482.6 m

88

482.6 (19

163 17

m (19˝), air throughput 320 m3/h

Tangential fans

ngen

tial f

ans

˝)

380

Su

Ta

pply includes:Fully assembled and wired unit, ready for connection, including filter mat.

Approvals, see page 274.

Detailed drawing,see page 240.

Performance diagrams, available on the Internet.

Model No. SK 3145.000 3144.000

Rated operating voltage V/Hz 115, 50/60 230, 50/60

Dimensions in mmWHD

482.6 (19˝) 88 (2 U) 158

Air throughput, unimpeded air flow 320 m3/h

Rated current max. 0.32 A 0.16 APower 37 WNoise level 52 dB (A)Speed 2245 rpm–1

Temperature range –10°C to +55°CMaximum static pressure difference 65 – 70 PaAccessories Packs of PageTemperature indicator 1 3114.115 3114.100 177 Thermostat 1 3110.000 178 Filter mats 5 3177.000 189 Front outlet grille 2 U 1 3176.000 193 Roof vent 1 3148.007 54 Speed control 1 3120.115 3120.000 179

Special voltages available on request. We reserve the right to make technical modifications.

53Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 56: Erdinc  klima sk_broschuere_gb

Fan systems

54

Fan

syst

ems

RTT roof-mounted fan and vent attachmentfor TSThe active roof-mounted fan and the passive vent attachment (TS 8801.380) integrate perfectly into the system-wide mounting concept of the Rittal TopTherm platform. They fit precisely onto the cut-outs of the small and medium performance cate-gory of TopTherm roof-mounted cooling units.

Of course, they may also be mounted on any suffi-ciently large roof surface.

TS roof plates with prepared mounting cut-outs are additionally available.

Roof-mounted fan supply includes: Unit ready to connect with built-in radial fan, sealing material and assembly parts.

Vent attachment: see page 182.

Protection category:IP 43 to EN 60 529

Detailed drawing, see page 240.

3149.410 3149.420 3149.440 3149.810 3149.820 3149.840 8801.380 Page

Model No. SK

Rated operating voltage V/Hz 115, 50/60 230, 50/60 400, 3~, 50/60460, 3~, 60 115, 50/60 230, 50/60 400, 3~, 50/60

460, 3~, 60 Roof vent

Air throughput, unimpeded air flow 400 m3/h 800 m3/h Without motor

Required mounting cut-out W x D mm 475 x 260 490 x 390Power consumption of fan 120 W/170 W 95 W/140 W 170 W/225 W 180 W/310 WRated current of fan 1.1/1.6 A 0.55/0.88 A 0.35/0.35 A 1.5/2.2 A 0.75/1.1 A 0.35/0.55 ATemperature range –10°C to +55°CNoise level 68/69 dB (A) 69/70 dB (A)Weight 10 kg 11 kg 6 kgColour shade RAL 7035Accessories

Roof plate 600 x 600 mm for TS 8 with cut-out 8801.300 8801.310 181 Roof plate 600 x 800 mm for TS 8 with cut-out 8801.320 8801.330 181 Roof plate 1200 x 600 mm for TS 8 with cut-out – 8801.350 181 Temperature indicator 3114.115 3114.100 – 3114.115 3114.100 – – 177 Speed control 3120.115 3120.100 – 3120.115 3120.100 – – 179

Roof-mounted fan● The roof-mounted fan is easily installed using

6 screws. The sealing tape supplied can be used to seal it against the enclosure.

● The attachment screws are invisible from the outside.

● The roof-mounted fan casing has a large air outlet surface and labyrinth air ducting.

Protection category:IP 43 to EN 60 529. By additionally installing the filter holder with filter mat SK 3175.000, with roof vent SK 3148.007 a protection category of IP 44 is achieved.

Fully wired unit ready for connection with built-in radial fan, sealing material and assembly parts, connection cable (3 m), drilling template.

Accessories:

Filter holder,see page 194.

Detailed drawing, see page 240.

Model No. SK 3149.007 3169.007 3148.007

Rated operating voltage V/Hz 230, 50/60 115, 50/60 Without fan motorAir throughput 360 m3/h

Rated current max. 0.2 A 0.55 APower consumption 42 W 65 WTemperature range –10°C to +60°CNoise level 53 dB (A)Weight 7.8 kgColour1) RAL 7035, textured enamel

1) To order the version in RAL 7032, please add extension .000 to the Model No. Special voltages available on request. We reserve the right to make technical modifications.

TB

290500

370 550

125

B = WidthT = Depth

50

265345

340 420

Rittal System Climate Control

Page 57: Erdinc  klima sk_broschuere_gb

Fan systems

Fan

syst

ems

55Rittal System Climate Control

Roof-mounted fanfor TS/FR(i) for the office sectorThis new roof ventilation concept offers a wealth of performance, assembly and cost benefits associated with the use of integrated ventilation systems. This roof-mounted fan may be ordered with and without a roof plate. Another outstanding feature is the enormous volumetric flow in propor-tion to exceptionally low noise levels, making it ideal for use in sensitive office areas.

Technical specifications: ● Fitted onto a roof plate based on TS.● Easy assembly; mounting cut-outs have been

provided.● Radial fan.

Supply includes:Fully wired ready for connection, including assembly parts.

T

H

B

511 511

410450450

410

H

13.5

T B

20

2424

225

205

410

450

Ø 6.5(8x)

Model No. SK 3164.610 3164.620 3164.810 3164.820 3164.115 3164.230 PageRated operating voltage V/Hz 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60 Air throughput (unimpeded air flow) 1500 m3/h1)

Version With roof plate without roof plate

Dimensions in mmWHD

800 240 800

800 240 900

511 227 511

Power consumption 68 W/81 WRated current 0.6 A/0.7 A 0.3 A/0.35 A 0.6 A/0.7 A 0.3 A/0.35 A 0.6 A/0.7 A 0.3 A/0.35 ARadial fan –Noise level 40 dB (A)Temperature range +20°C to +55°CColour RAL 7035Accessories

Temperature indicator in 1 U patch panel 7109.035 177 Temperature indicator 3114.115 3114.100 3114.115 3114.100 3114.115 3114.100 177 Thermostat 3110.000 178

1) 800 m3/h at 40 Pa counterpressure using two integrated louvres, type DK 7825.801, in the enclosure base/plinth. Special voltages available on request. We reserve the right to make technical modifications.

Mounting cut-out only required for fans wtihout roof plate

B = WidthT = Depth

Enclosure internal fanfor TSTo prevent hot-spots and support the air routing of active enclosure climate control components. Adjustable in two axes. Attached to the TS 8 frame section. Several fans may be cascaded using the quick-release clamping strip.

Supply includes:Fully wired unit ready for connection with radial fan and lockable swivel device, as well as assembly parts.

213.5

100

120

Ø 6

(2x)

Air through-put (unim-peded air

flow)

Power consump-

tionW

Rated current

A

Rated voltageV, Hz

Model No. SK

160 m3/h 19.0/18.0 0.12/0.11 230, 50/60 3108.100

160 m3/h 19.0/18.0 0.24/0.23 115, 50/60 3108.115

160 m3/h 3.5 0.15 24 V (DC) 3108.024

Page 58: Erdinc  klima sk_broschuere_gb

Fan systemsFa

n sy

stem

s

Fan mounting plate for TSThe fan mounting plate may be retro-fitted in all TS 8 network enclosures from above. The plate is mounted at the front of the enclosure, whilst the rear section is left free for cable entry. A rubber cable clamp strip is supplied loose for optional sealing at the rear.

The following combinations are also possible:

● Solid roof plate raised with 20 or 50 mm roof spacers.

● Roof plate for cable entry raised with 20 or 50 mm roof spacers.

● Vented roof plate for cable entry.

In conjunction with the large swing frame, usage is only possible from an enclosure depth of 800 mm, in conjunction with a roof plate for cable entry from 900 mm.

Note:Not suitable for crane transportation. Not suitable for combination with 482.6 mm (19˝) mounting frame.

The air throughput can be increased with the fan expansion kit DK 7980.000.

Technical specifications for one fan: Rated operating voltage: 230 V Power consumption: 15/14 W at 50/60 Hz Air throughput (unimpeded air flow): 160/180 m3/h, 50/60 Hz Temperature range: –10°C to +55°C

Technical specifications of thermostat: Rated operating voltage: 250 V Temperature range: +5°C to +55°C

Colour:RAL 7035

Supply includes:2 fans, 2/4 cut-outs to extend to 4/6 fans, thermostat, rubber cable clamp strip. Thermostat and fan fully wired to connection cable (2.5 m).

Accessories:

Fan expansion kit, see page 56. Rubber cable clamp strip SZ 2573.000 for sealing at the sides and targeted air routing when bayed, see Cat. 32 page 1047.

385/585525/725

40

For enclosuresNumber of fans

Max. number of

fans

Model No. DKWidth

mmDepth mm

600 600 2 4 7966.035

600

800900

10001200

2 6 7968.035

800 600 2 6 7986.035

800

800900

10001200

2 6 7988.035

Fan expansion kitFor retro-fitting various fan units or to supplement the fan mounting plate and modular fan roof.

Technical specifications DK 7980.000: Rated operating voltage: 230 V~ Power consumption: 15/14 W at 50/60 Hz Air throughput (unimpeded air flow): 160/180 m3/h, 50/60 Hz Noise level (unimpeded air flow): 37 dB (A) Temperature range: –10°C to +55°C

Technical specifications DK 7980.100: Rated operating voltage: 230 V~ Power consumption: 14/12 W at 50/60 Hz Air throughput (unimpeded air flow): 108/120 m3/h, 50/60 Hz Noise level (unimpeded air flow): 34 dB (A) Temperature range: –20°C to +70°C

Technical specifications DK 7980.148: Rated operating voltage: 48 V (DC) Power consumption: 7.7 W Air throughput (unimpeded air flow): 184 m3/h Noise level (unimpeded air flow): 43 dB (A) Temperature range: –20°C to +70°C

Supply includes:Fan, including assembly parts and connection cable (0.61 m).

Dimensions W x H x D mm Packs of Model No. DK

119 x 119 x 38 1 set 7980.000

119 x 119 x 25 1 set 7980.100

119 x 119 x 25 1 set 7980.148

56 Rittal System Climate Control

Page 59: Erdinc  klima sk_broschuere_gb

Fan systems

Fan

syst

ems

Cover plates for fan panelsfor FlatBox To cover unused fan panels when using fans in the FlatBox.

Material:Sheet steel

Surface finish:Powder coated in RAL 7035

Supply includes:Assembly parts.

Packs of Model No. DK

6 7507.760

Fan mounting plate DC for TS

Super-low noise thanks to FCS speed control, fully fittedSuitable for TS 8 enclosures with a raised roof (> 20 mm) or TS 8 roof plate, vented. The fan mounting plate may be used as an alternative to fan mounting plate 7988.035. It is installed from above. Cable entry is prepared in the rear section of the plate.Not suitable for combination with 482.6 mm (19˝) mounting frame.

Advantages of the DC fan mounting plate with FCS technology: ● Super-low noise thanks to speed control.● All fans are monitored for failure.● High air throughput thanks to DC technology

(unimpeded airflow 6 x 175 m3/h = 990 m3/h).● EMC compatibility.● Temperature monitoring and control.● High level of safety (low safety voltage with

24 V DC power supply).● Visual and acoustic alarm messages, plus relay

alarm output.● Freely selectable installation location for the

FCS control unit (included with the supply of the fan mounting plate, in 482.6 mm (19˝) with 7320.440 or on the frame with 7320.450).

● Suitable for international use, thanks to wide-range power supply 100 – 240 V AC and socket to IEC 320.

● Pre-configured.● Network-compatible via CMC-TC processing

unit II 7320.100 (all relevant data such as temperature etc. are displayed in the web browser, or alarms are sent in the form of an SNMP trap).

Technical specifications:Power pack rated voltage: 100 – 240 V AC, 50/60 Hz Power supply rated current: max. 1.5 A Power supply secondary range: 24 V DC, 3 A Temperature range: +5°C to +40°C Total air throughput (unimpeded air flow): 6 x 175 m3/h = 990 m3/h

Technical specifications for one fan: Rated voltage: 24 V DC Rated current: max. 0.3 A Air throughput (unimpeded air flow): 175 m3/h Speed: 2650 rpm Noise level: up to 45 dB (A) at maximum speed activation

Also required:

Connection cable 230/115 V. Example D version, Model No. 7200.210,see Cat. 32, page 818.

Accessories:

1 U mounting unit, Model No. 7320.440,see Cat. 32, page 821. Mounting module, Model No. 7320.450,see Cat. 32, page 821.

For enclosures

width mm

For enclosures

depth mm

Number of DC fans

Model No. DK

800800 900 1000

6 7858.488

Note:For more information on the FCS system, see Cat. 32, page 813.

57Rittal System Climate Control

Page 60: Erdinc  klima sk_broschuere_gb

Fan systemsFa

n sy

stem

s

58 Rittal System Climate Control

Fan roof, modular, two-piecefor TS, FR(i) The modular roof plate consists of individual com-ponents and can be configured for the ventilation of the enclosures in various ways. The modules consist of:

Roof plate, two-piece with cut-out For fan mounting and cable entry at the rear via a sliding angular bracket with rubber cable clamp strip. Replacing the existing roof plate. The two-piece design allows convenient retrofitting of cables at any time.

Cover plate To cover the cut-out, optionally solid or vented options. The top-mounted cover plate may be raised for extra air throughput using the supplied spacers.

Fan insert For active ventilation:A fully pre-wired fan tray including 2.5 m connec-tion cable, with two fan motors and additional cut-outs. The air throughput may be increased with a fan expansion kit.

Material:Sheet steel, spray finished

Colour:RAL 7035

Technical specifications for one fan: Rated operating voltage: 230 V Power consumption: 15/14 W at 50/60 Hz Air throughput (unimpeded air flow): 160/180 m3/h at 50/60 Hz Temperature range: –10°C to +55°C

Detailed drawing,see page 241.

Accessories:

Fan expansion kit DK 7980.000, see page 56. Thermostat SK 3110.000, see page 178. Speed control SK 3120.000, see page 179.

1

2

1 2

3 45

For enclosuresModel No. DK

Fan insertRoof plate FR(i)

Roof plate TS Cover plate

Width mm

Depth mm With

cut-out With

cut-out Solid Vented Fan insert

Fans pre-wired

Maximum no. of fans

600 600 7856.3661) 7826.366 2102.1801) 2102.400 2102.320 2 2600 800 7856.3681) 7826.368 2102.1901) 2102.410 2102.490 2 6600 900 – 7826.369 2102.1901) 2102.410 2102.490 2 6600 1000 7856.3601) 7826.360 2102.1901) 2102.410 2102.490 2 6600 1200 7856.3621) 7826.362 2102.1901) 2102.410 2102.490 2 6800 600 – 7826.486 7885.100 7885.200 7885.000 2 3800 800 7856.3881) 7826.488 7886.100 7886.200 7886.000 2 8800 900 – 7826.489 7886.100 7886.200 7886.000 2 8800 1000 7856.3801) 7826.480 7886.100 7886.200 7886.000 2 8800 1200 – 7826.382 7886.100 7886.200 7886.000 2 8

1) Delivery times available on request. Design panel FR(i) already included with the supply of the standard roof plate.

1 2 4 5 3

Fan unit, active for TEFor active ventilation of the TE 7000. The fan unit is installed in the prepunched cut-out. An additional fan may optionally be integrated.

Supply includes:Fan unit including assembly parts, 2 fans, 1 thermostat and open connection cable.

Technical specifications for one fan: Fan extension kit, 7980.000, see page 56.

Technical specifications of thermostat: Rated operating voltage: 250 V Temperature range: +5°C to +55°C

Note:Connection via distributor box or country-specific connector.

Accessories:

Fan expansion kit, see page 56.

For enclosures W x D mm

Number of pre-wired

fans

Possible number of

fans

Model No. TE

All dimensions 2 3 7000.670

Active kit for TEconsisting of fan unit including thermostat, com-plete, wired ready for connection, socket strip (DK 7000.630) for up to 8 earthing pin plugs, version D and connection cable (DK 7200.210).

Packs of Model No. DK

1 set 7000.680

Page 61: Erdinc  klima sk_broschuere_gb

Fan systems

Fan

syst

ems

Door-mounted fanfor server enclosures TS, TE

Specifically for installing in perforated doors. The growing packaging density in data communications and network enclosures make active, direct ventilation of the enclosure indispen-sable. The door-mounted fan, which is attached to the rear or front door, supports horizontal air rout-ing via the servers and therefore facilitates faster heat dissipation from active components.

Technical specifications: ● Standard assembly with two fans.● Air throughput, unimpeded air flow 600 m3/h. ● By adding two fan extension kits, the air

throughput is increased to 1200 m3/h. ● The direction of air flow is easily reversed by

rotating the fan.● Several units may be positioned in a cascade

arrangement. ● Simple mounting on the tubular door frame.

Supply includes:Wired ready for connection with 2.5 m connection cable, including assembly parts.

Accessories:

Fan expansion kit, see page 59.

Note:Only for mounting on the tubular door frame!

Door configuration for installation in 2 and 4-door ISP racks available on request.

B

T

H 552

27 230 (350)

Ø 4.5

475 (675)

493 (693)

606

9

59.5

5

Model No. SK 3165.6241) 3165.6481) 3165.6151) 3165.630 3165.8241) 3165.8481) 3165.8151) 3165.830 PageRated operating voltage V/Hz 24 (DC) 48 (DC) 115, 50/60 230, 50/60 24 (DC) 48 (DC) 115, 50/60 230, 50/60 Air throughput (unimpeded air flow) 600 m3/h

Power consumption for two fans 40 W 48 W 70 W/64 W 70 W/70 W 40 W 48 W 70 W/64 W 70 W/70 WRated current of fan 1.5 A 1.0 A 0.76 A/0.72 A 0.38 A/0.36 A 1.5 A 1.0 A 0.76 A/0.72 A 0.38 A/0.36 A

Dimensions in mm WHD

493 606 64.5

693 606 64.5

For doors with width (mm) 600 800Noise level 55 dB (A)Temperature range +20°C to +55°CColour RAL 7035Accessories

Temperature indicator 3114.024 – 3114.115 3114.100 3114.024 – 3114.115 3114.100 177 Thermostat 3110.000 178

1) Delivery times on request.Special voltages available on request. Technical modifications reserved.

B = WidthT = Depth

Fan expansion kitfor door-mounted fanTo increase the air throughput of the door-mounted fan.

To fit door-mounted fan Model No. SK

SK 3165.624, SK 3165.824 3165.024

SK 3165.648, SK 3165.848 3165.048

SK 3165.615, SK 3165.815 3165.115

SK 3165.630, SK 3165.830 3165.230

Rittal System Climate Control

59
Page 62: Erdinc  klima sk_broschuere_gb

Air

/air

hea

t exc

hang

ers

Air/air heat exchangers

The requirement for using air/air heat exchangers is

that the ambient temperature must be below the

required enclosure internal temperature. Dust and any

aggressive ambient air is unable to ingress the

enclosure interior, thanks to the two separate air

circuits.

60 Rittal System Climate Control

Page 63: Erdinc  klima sk_broschuere_gb

Air

/air

hea

t exc

hang

ers

Platform strategy/installationIdentical installation cut-outsfor various output classes.

Easily retrofittedThanks to the low weight, simple assembly cut-outs and problem-free attachment of the heat exchangers, a cabinet or enclosure is easily retro-fitted.

Rittal System Climate Control

Simple maintenanceThe heat exchanger unit is very easily removed and cleaned. The cleverly thought-out structure enables fast, economical main-tenance.

SafetyHigh protection categoryThanks to the seamlessly sealed heat exchanger module, a protection category of IP 54 to EN 60 529 is achieved.

High load capacityThe motors of the fans are equipped with thermal winding protection.

Top quality: Guaranteed protection for your electronics.All devices in the Rittal TopTherm-Plus series are tested in accordance with the interna-tionally valid approvals (GS, UL).

Benefits at a glance● Specific thermal output from 17.5 W/K to

90 W/K● External and internal circuit may be

controlled separately● Mounting cut-outs and enclosure

dimensions identical to TopTherm wall-mounted cooling units

● Suitable for external and internal mounting

● Top design identical to TopTherm wall-mounted cooling units

ImportantThe temperature difference between the room temperature and enclosure internal temperature will have a decisive effect on the heat loss that may be dissipated.

Tips and tricksApplications see page 202

Selection criteria see page 203

Assembly see page 204

Air routing see page 205

Electrical connection and control see page 206

61

Page 64: Erdinc  klima sk_broschuere_gb

Air/air heat exchaWall-mounted

ngers

T

H

B

B

H

T

B

H

T

B = WidthT = Depth

Air

/air

hea

t exc

hang

ers

Supply includes:Fully wired unit readnection.

Detailed drawing,see page 241.

Performance diagravailable on the Inte

y for con-

ams, rnet.

SK 3125.800Compact wall-mounted air/air heat exchanger. Ideal for small enclosures and command panels. Suitable for external and inter-nal mounting.

SK 3129.800Super-slimline air/air heat exchangers. Ideal for external door mounting.

Model No. SK 3125.800 3129.800

Rated operating voltage V/Hz 230, 1~, 50/60

Dimensions in mm WHD

200400146

4001360110

Specific thermal output 12 W/K 62 W/K

Fans 2 per heat exchangerMax. rated current per fan 0.11 A/0.13 A 0.45 A/0.55 APre-fuse T 2.0 AOutput per fan 25 W/30 W 100 W/130 W

Air throughput of fans (unimpeded air flow) External circuit 265 m3/h / 315 m3/h 860 m3/h / 900 m3/hInternal circuit 265 m3/h / 315 m3/h 860 m3/h / 900 m3/h

Temperature range –5°C to +55°CType of connection Connection cableWeight 8 kg 30 kgColour RAL 7035Protection category to EN 60 529 Internal circuit IP 54Accessories Packs of PageThermostat 1 3110.000 178 Temperature display 1 3114.100 177 Speed control 1 3120.000 179

Special voltages available on request. We reserve the right to make technical modifications.

62 Rittal System Climate Control

Accessories Page 171 Recooling systems From page 116 Configuration software Page 195

Page 65: Erdinc  klima sk_broschuere_gb

Wall-mounted with controller

Air/air heat exchangers

Air

/air

hea

t exc

hang

ers

T2

50

950

T1400108

42

550

150

280

1580

215400 165

50

T = Depth

● With controller atemperature disp

● Floating fault sigin case of overte

nd digital lay nal contact mperature

Supply includes:Fully wired unit ready for con-nection.

Approvals, see page 276.

Detailed drawing,see page 244.

Performance diagrams, available on the Internet.

Model No. SK 230 V 3126.100 3127.100 3128.100 3129.100 3130.100

115 V 3126.115 3127.115 3128.115 3129.115 3130.115

Rated operating voltage V/Hz 230/115, 1~, 50/60

Dimensions in mm

WHT1T2

280550150–

400950205155

400950225175

4001580215–

Specific thermal output 17.5 W/K 30 W/K 45 W/K 60 W/K 90 W/K

Fans 2 per heat exchanger

Max. rated current per fan 230 V 0.11 A/0.13 A 0.28 A/0.34 A 0.3 A/0.4 A 0.38 A/0.4 A 0.67 A/0.88 A115 V 0.23 A/0.25 A 0.55 A/0.7 A 0.6 A/0.8 A 0.65 A/0.8 A 1.3 A/1.8 A

Pre-fuse T 2.0 A 4.0 AOutput per fan 23 W/27 W 60 W/75 W 70 W/90 W 85 W/90 W 150 W/200 W

Air throughput of fans (unimpeded air flow)

External circuit 265 m3/h / 315 m3/h 480 m3/h / 525 m3/h 600 m3/h / 625 m3/h 860 m3/h / 900 m3/h 850 m3/h / 945 m3/hInternal circuit 265 m3/h / 315 m3/h 480 m3/h / 525 m3/h 600 m3/h / 625 m3/h 860 m3/h / 900 m3/h 850 m3/h / 945 m3/h

Temperature range –5°C to +55°CType of connection Plug-in terminal stripWeight 10 kg 18 kg 19 kg 21 kg 34 kgColour RAL 7035Protection category to EN 60 529 Internal circuit IP 54Accessories Packs of PageFilter mats 3 3286.300 3286.400 189 Metal filters 1 3286.310 3286.410 190

Special voltages available on request. We reserve the right to make technical modifications.

63Rittal System Climate Control

Accessories Page 171 Recooling systems From page 116 Configuration software Page 195

Page 66: Erdinc  klima sk_broschuere_gb

Air/air heat exchangWall-mounted, railway-compat

64

Air

/air

hea

ersible version

H

T1B T1

External mounting

Partial internal mounting1)

Internal mounting

B = WidthT = Depth

t exc

hang

ers

Rittal air/air h

eat exchangers in a railway-compatible version are used specifically in the mobile railway engineering sector, e.g. for local trains, locomotives and high-speed trains. Products are available both in 24 V DC and in 110 V DC.

Railway-compatible design of the units includes construction to EN 50 155, halogen-free con-nection cables, screw protec-tion, shock and vibration testing to EN 61 373, preparation for EN 45 545, and spray-finishing in RAL 7035 S to DB TL 918340, among other things.

Benefits, technical details:● External and internal fans may

be controlled separately● Simple maintenance

Supply includes:Fully wired unit ready for connection.

Detailed drawing, see page 242/243.

Model No. SK 3126.424 3128.424 3129.424 3130.424 3126.410 3128.410 3129.410 3130.410

Rated operating voltage 24 V (DC) 24 V (DC) 24 V (DC) 24 V (DC) 110 V (DC) 110 V (DC) 110 V (DC) 110 V (DC)

Dimensions in mm BH

T1

280650127

400950140

400950150

4001580150

280650127

400950140

400950150

4001580150

Specific thermal output 27 W/K 47 W/K 66 W/K 98 W/K 27 W/K 47 W/K 66 W/K 98 W/K

Max. rated current per fan 2.7 A 7.5 A 10.5 A 9.2 A 2.7 A 1.9 A 2.47 A 2.3 A Output per fan 65 W 180 W 240 W 220 W 65 W 203 W 256 W 230 W

Air throughput of fans (unimpeded air flow)

External circuit 360 m3/h 560 m3/h 1055 m3/h 1125 m3/h 360 m3/h 560 m3/h 1055 m3/h 1125 m3/hInternal circuit 360 m3/h 560 m3/h 1055 m3/h 1125 m3/h 360 m3/h 560 m3/h 1055 m3/h 1125 m3/h

Temperature range –5°C to +55°CWeight 10 kg 16 kg 18 kg 25 kg 12.5 kg 18.5 kg 20.5 kg 27.5 kgColour RAL 7035Protection category to EN 60 529 Internal circuit IP 54

Accessories Packs of PageAdjustable frame 1 3286.260 3286.270 3286.270 3286.280 3286.260 3286.270 3286.270 3286.280 183 Metal filters 1 3286.230 3286.240 3286.240 3286.250 3286.230 3286.240 3286.240 3286.250 190

Delivery times available on request. We reserve the right to make technical modifications. 1) Partial installation is only supported with an adjustable frame (see accessories).

The requirement for using air/air heat exchangers is that the ambient tem-perature must be below the required enclosure internal temperature. Dust and any aggressive ambient air is unable to ingress the enclosure, thanks to the two separate air cir-cuits. Contamination of the outer circuit with coarse dust can be reduced via the use of optional metal filters. Attachment options: External mount-ing, internal mounting, partial inter-nal mounting via a special mounting frame.

Rittal System Climate Control

Page 67: Erdinc  klima sk_broschuere_gb

Roof-mounted

Air/air heat exchangers

t exc

hang

ers

T

H

B

B = WidthT = Depth

Application

Air

/air

hea

: These units are used specifi-cally if the doors or side panels must not be obstructed, or space must be kept clear for escape routes.

Technical design: ● The heat exchanger module

and the enclosure of the heat exchanger form a single unit, thereby substantially enlarg-ing the surface area for heat dissipation.

● This design gives the unit an extremely low weight (16.8 kg) combined with a high degree of enclosure rigidity.

● The built-in radial fans ensure effective air circulation, even where the enclosure is densely packed.

● All motors are equipped with thermal winding protection.

● As you would expect, the heat exchanger membranes are conductively connected to one another and thereby incorporated into the electri-cal safety features.

● The internal and external circuits can be connected separately; separate routing effectively prevents the ingress of dust, moisture and dirt.

Supply includes:Fully wired unit ready for connection. The fans are connected via two 3-wire connection cables, with wire end ferrules.

Detailed drawing, see page 241.

Model No. SK 3248.000

Rated operating voltage V/Hz 230, 1~, 50/60

Dimensions in mm WHD

595362440

Specific thermal output 66 W/K

Fans 2 per heat exchanger Max. rated current per fan 0.45 A/0.55 APre-fuse T 4.0 AOutput per fan 75 W

Air throughput of fans (unimpeded air flow)

External circuit 965 m3/hInternal circuit 965 m3/h

Temperature range –5°C to +55°CType of connection Connection cable Weight 16.8 kg Colour RAL 7035/9005 Protection category to EN 60 529 Internal circuit IP 54 Accessories Packs of PageTemperature display 1 3114.100 177 Thermostat 1 3110.000 178 Hygrostat 1 3118.000 178 Speed control 1 3120.000 179

Special voltages available on request. We reserve the right to make technical modifications.

65Rittal System Climate Control

Page 68: Erdinc  klima sk_broschuere_gb
Page 69: Erdinc  klima sk_broschuere_gb

Cooling units

Co

olin

g u

nit

s

Modular climate control concept from page 68

� � � Cooling modules . . . . . . . . . . . . . . . . . . . . . . . . . 1500/2500 W. . . . . . . . 70 � Section doors for installing cooling modules . . . . . . . . . . . . . . . . . . . . . . . 71

Roof-mounted cooling units from page 72

� � � � Roof-mounted cooling units . . . . . . . . . . . . . . . . . . 500/750 W. . . . . . . . 74 � � � � Roof-mounted cooling units . . . . . . . . . . . . . . . . . . . . . . 1000 W. . . . . . . . 75

� � � Roof-mounted cooling units . . . . . . . . . . . . . . . . 1100/3000 W. . . . . . . . 76 � � � � Roof-mounted cooling units . . . . . . . . . . . . . . . . 1500/2000 W. . . . . . . . 77 � � � � Roof-mounted cooling units . . . . . . . . . . . . . . . . 3000/4000 W. . . . . . . . 78

� � � � with CO2 as the coolant . . . . . . . . . . . . . . . . . . . . . . . . . 1000 W. . . . . . . . 79

Wall-mounted cooling units from page 80

� � VIP small cooling units . . . . . . . . . . . . . . . . . . . . . . . . . . 225 W. . . . . . . . 82 � � � Mini, in horizontal format . . . . . . . . . . . . . . . . . . . . . . . . . 300 W. . . . . . . . 83

� � � Wall-mounted cooling units . . . . . . . . . . . . . . . . . . . 300/500 W. . . . . . . . 84 � � � Wall-mounted cooling units . . . . . . . . . . . . . . . . . . . . . . . 750 W. . . . . . . . 85

� � � Cool Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000 W. . . . . . . . 86 � � � � Wall-mounted cooling units . . . . . . . . . . . . . . . . . 1000/1500 W. . . . . . . . 87 � � � � Wall-mounted cooling units, slimline . . . . . . . . . . . . . . . 1500 W. . . . . . . . 88 � � � � Wall-mounted cooling units . . . . . . . . . . . . . . . . . 2000/2500 W. . . . . . . . 89 � � � � Wall-mounted cooling units . . . . . . . . . . . . . . . . . . . . . . 4000 W. . . . . . . . 90 � � � � � Design NEMA 4x . . . . . . . . . . . . . . . . . . . . . . 500/1000/1500 W. . . . . . . . 91 � � � � � Design NEMA 4x . . . . . . . . . . . . . . . . . . . . . . . . . 2000/2500 W. . . . . . . . 92

� � � � for precision machine tools . . . . . . . . . . . . . . . . . 1000/1500 W. . . . . . . . 93

� � � Explosion-proof cooling units for zone 22 (dust) . . . . . . . . . . . . . . . . . . . . . . . . . 1000/1500 W. . . . . . . . 94

� � � � with CO2 as the coolant . . . . . . . . . . . . . . . . . . . . . . . . . 1000 W. . . . . . . . 95

Thermoelectric coolers from page 96

� � Thermoelectric coolers . . . . . . . . . . . . . . . . . . . . . . . . . . 100 W. . . . . . . . 97

E

E

E

E

Stainless steel version

Standardised installation

Integral condensate evaporation

Energy-efficient and nano-coated

Suitable for command panels

NEMA 4x

Coolant CO2

Industry solutions

E

Rittal System Clima

67te Control
Page 70: Erdinc  klima sk_broschuere_gb

Mod

ular

clim

ate

cont

rol c

once

pt

Modular climate control concept

Less is more! We offer almost limitless application

possibilities from just six cooling modules and eight

door modules. Top cooling technology, complete and

ready to use – no need to make mounting cut-outs.

The existing sheet steel doors are easily exchanged

for section doors with cooling modules. These can

also be exchanged or upgraded while the system is

operational.

68 Rittal System Climate Control

Page 71: Erdinc  klima sk_broschuere_gb

Mod

ular

clim

ate

cont

rol c

once

pt2 6

800

1800

/200

0

120018

00/2

000

1200

1800

/200

0

ModularityWith the section door and cooling module, you can create your own individual climate control solution in next to no time.Choose from 48 different options with varying sizes, cooling outputs and voltages.

Rittal System Climate Control

1

3

4

5

600

1800

/200

0

Infinite possibilitiesSeamless baying and perfect integration. Cooling of a bayed enclosure suite is easily achieved, even under awkward room condi-tions, such as low ceiling heights.

Cooling module, 1500 W useful cooling output

Cooling module, 2500 W useful cooling output

Section doors for installing cooling modules in 600 mm wide enclosures

Section doors for installing cooling modules in 800 mm wide enclosures

Section doors for installing cooling modules in 1200 mm wide enclosures; cooling module fitted on the left

Section doors for installing cooling modules in 1200 mm wide enclosures; cooling module fitted on the right, including lockable door on the left

1

2

3

4

5

6

Benefits at a glance● Combination of TS 8 section door and

climate control module● One item number each for the door and

climate control module● 8 section doors x 6 climate control

modules = 48 combination options● Standard RTT PLUS version with integral

condensate evaporation and RiNano coating

● Intelligent control− Climate control module with Comfort

controller − Controller is identical to those used

with TopTherm climate control systems

ImportantThe TS base/plinth is required for opera-tional purposes.

Tips and tricksApplications see page 207

Selection criteria see page 208

Assembly see page 209

Air routing see page 210

Condensate management see page 213

Electrical connection and control see page 215

69

Page 72: Erdinc  klima sk_broschuere_gb

MCo

Mod

ular

clim

ate

cont

rol c

once

pt

odular climate control conceptoling modules, 1500/2500 W useful cooling output

Su

pply includes:Cooling module prepared for installation in section door, with RiNano coating and integrated condensation evaporation.

Also required:

Section door, fits TS 8 enclo-sures, 600, 800, 1200 mm widths and 1800, 2000 mm heights, see page 71.

Base/plinth, 100 or 200 mm high, see Cat. 32, page 893.

Approvals, see page 277.

Detailed drawing,see page 245.

Performance diagrams, available on the Internet.

Model No. SK with Comfort controller 3307.700 3307.710 3307.740 3310.700 3310.710 3310.740

Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 400, 3~, 50/460, 3~, 60 230, 1~, 50/60 115, 1~, 50/60 400, 3~, 50/

460, 3~, 60Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

1500 W/1550 W 850 W/900 W

1500 W/1550 W 930 W/950 W

2500 W/2520 W 1620 W/1730 W

2500 W/2500 W 1760 W/1800 W

Rated current max. 6.0 A/6.5 A 12.6 A/12.6 A 2.6 A/2.8 A 7.8 A/8.8 A 18.1 A/19.8 A 3.6 A/3.8 AStart-up current 22.0 A/24.0 A 36.0 A/39.0 A 8.5 A/9.2 A 22.0 A/24.0 A 36.0 A/39.0 A 13.0 A/14.0 APre-fuse gG 16.0 A/16.0 A 16.0 A/16.0 A 6.3 – 10.0 A1) 16.0 A/16.0 A 20.0 A/20.0 A 6.3 – 10.0 A1) Power consumption Pelto DIN 3168

L 35 L 35L 35 L 50

910 W/1100 W 1100 W/1250 W

940 W/1130 W 1140 W/1280 W

850 W/910 W 920 W/980 W

1410 W/1620 W 1580 W/1950 W

1460 W/1670 W 1630 W/2000 W

1380 W/1580 W 1620 W/1920 W

Refrigeration factor ε = L 35 L 35 1.6 1.6 1.7 1.7 1.8Refrigerant R134a, 700 g R134a, 900 gPermissible operating pressure p. max. 28 barTemperature and setting range +20°C to +55°C

Protection category to EN 60 529

External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight2) 72 kg 72 kg 75 kg 74 kg 74 kg 76 kgColour RAL 7035

Air throughput of fansExternal circuit 1100 m3/h 1100 m3/hInternal circuit 520 m3/h 1100 m3/h

Temperature control Comfort controller (factory setting +35°C)Accessories Packs of PageDoor-operated switch 1 4127.000 176 Filter media 1 See accessories section door 71 SK BUS system for Comfort controller 1 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195

Interface card for Comfort controller 1 3124.200 179 Special voltages available on request. We reserve the right to make technical modifications.1) Motor circuit-breaker2) Includes section door weight

QK .

QK/Pel.

70 Rittal System Climate Control

Accessories Page 171 TS 8 enclosures Cat. 32, from Page 142 Configuration software Page 195

Page 73: Erdinc  klima sk_broschuere_gb

B

H

Width Depth

Modular climate control conceptSection doors for installing cooling modules

B

H

B

H

B

H

B =T =

Co

dula

r cl

imat

e co

ntro

l con

cept

lour:RAL 7035

Supply includes:Section door unit without pre-fitted cooling module, including TS 8 hinges, door opening angle approx. 110°.

Note for 1200 mm wide TS 8 enclosures: With the device positioned on the “right”, one pack consists of a section door for installing in the right-hand half of the enclosure plus a special lockable door for the left-hand half.

With the device positioned on the “left”, one pack consists of a section door for installing in the left-hand half of the enclosure. The existing lockable door on the right may be used.

Also required:

Cooling module,see page 70.

Base/plinth, 100 or 200 mm high, see Cat. 32, page 893.

Detailed drawing,see page 245.

Mo

Model No. SK for 1800 mm high TS enclosures 3300.040 3300.060 3300.080 3300.110

Model No. SK for 2000 mm high TS enclosures 3300.050 3300.070 3300.090 3300.120

Dimensions to fit TS enclosures

Width mm 600 800

1200 (unit positioned on the left)

1200 (unit positioned on the right)

Accessories Packs of Filter media 1 3284.210 3284.210 3284.210 3284.210

All SK 3307.700/.710/.740 or 3310.700/.710/.740 cooling module models, see page 70, can be integrated in the section doors mentioned above.

71Rittal System Climate Control

Accessories Page 171 TS 8 enclosures Cat. 32, from Page 142 Configuration software Page 195

Page 74: Erdinc  klima sk_broschuere_gb

Roo

f-m

ount

ed c

oolin

g un

its

Roof-mounted cooling units

Cooling units keep the enclosure internal temperature

at a constant level, with the air routing being tailored to

individual requirements. Two separate circuits prevent

the ingress of dust into the enclosure.

Rittal TopTherm-Plus roof-mounted cooling units:

Top design and top performance with a host of

assembly benefits and sophisticated air routing.

Superb performance plus cost-cutting

design.

72 Rittal System Climate Control

Page 75: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Roo

f-m

ount

ed c

oolin

g un

its

Versatility and flexibility of roof mountingCut your costsAll three-phase cooling units are suitable for a voltage range of 400/460 V and a frequency range of 50/60 Hz without rewiring. No need for expensive additional transformers.

Flexible performanceJust 3 mounting cut-outs for 6 dif-ferent output categories provide investment security and facilitate easy adaptation of the cooling out-put to the ambient conditions and the installed heat loss.

Rittal platform strategyTopTherm air/water heat exchang-ers and roof-mounted fans are also compatible with the mounting cut-outs.

Optimum flow conditionsTargeted air routing inside the enclosureThe internal air circulation is targeted and effective: The heated air is extracted cen-trally. Air exhaust occurs in the four corners, depending on requirements. Cold air is routed in a controlled manner into the lower enclosure chamber via the optional ducting system. The result is highly effective cooling and the avoidance of air short-circuits. The targeted air circulation inside the enclosure via ducts also prevents the creation of hot-spots.

Integrated into TopTherm-Plus cooling unitsElectrical condensate evaporationCondensate arising inside the enclosure or on the evaporator coil of the cooling unit is effectively evaporated. The evaporator device inside the cooling units has a very high evaporation output (several litres per day). This is achieved thanks to the princi-ple of direct evaporation.

RiNano coating The standard nano-coating on the heat exchanger membranes ensure a longer, constant cooling output and renders the use of filter media superfluous in many areas.

Benefits at a glance● Highly efficient in both performance and

energy consumption● Wide output range from 500 to 4000 W● Control and monitoring with Basic or

Comfort controllers● Three-phase cooling units support

multiple voltages as standard ● Uniform, performance-related, system-

wide mounting cut-outs● Targeted, individual air routing● Electric condensate evaporation and

RiNano coating

Important Avoid overloading the roof plate by using stays (with TS 8 system accessories, Catalogue 32, page 998)

Tips and tricksApplications see page 207

Selection criteria see page 208

Assembly see page 209

Air routing see page 210

Condensate management see page 213

Electrical connection and control see page 215

73

Page 76: Erdinc  klima sk_broschuere_gb

Roo

f-m

ount

Roof-mounted cooling unitsUseful cooling output 500/750 W

380

597

417

475 260

ed c

oolin

g un

its

SupplyNano-cintegralevaporaFully wiincludinassemb

Property rights:German registered designno. 402 02 324 German registered design no. 402 02 325

includes:oated condenser and electronic condensate tion.

red ready for connection, g drilling template and ly parts.

Accessories:

Roof plate for TS 8 with mounting cut-out, see page 181.

Approvals, see page 277.

Detailed drawing, see page 246.

Performance diagrams, available on the Internet.

Model No. SK with Basic controller, RAL 7035 3382.100 3382.110 3359.100 3359.110 3359.140

Model No. SK with Comfort controller, RAL 7035 3382.500 3382.510 3359.500 3359.510 3359.540

Model No. SK with Basic controller, stainless steel1) 3382.200 3382.210 3359.200 3359.210 3359.240

Model No. SK with Comfort controller, stainless steel1) 3382.600 3382.610 3359.600 3359.610 3359.640

Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 230, 1~, 50/60 115, 1~, 50/60 400, 2~, 50/60Dimensions in mm WHD 597 x 417 x 380Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

500 W/510 W 270 W/370 W

750 W/810 W 545 W/590 W

Rated current max. 3.3 A/3.5 A 6.7 A/7.2 A 3.6 A/4.5 A 7.2 A/9.0 A 2.1 A/2.6 AStart-up current 9.2 A/10.2 A 18.4 A/18.4 A 10.0 A/10.7 A 20.0 A/21.4 A 5.8 A/6.2 APre-fuse T 10.0 A 10.0 A 10.0 A 16.0 A 6.3 A – 10.0 A2) Power consumption Pelto DIN 3168

L 35 L 35L 35 L 50

500 W/550 W 550 W/590 W

510 W/560 W 560 W/610 W

550 W/660 W630 W/740 W

560 W/675 W640 W/750 W

Refrigeration factor ε = L 35 L 35 1.0 1.4Refrigerant R134a, 250 g R134a, 300 gPermissible operating pressure p. max. 25 barTemperature and setting range +20°C to +55°C

Protection category to EN 60 529

External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 30 kg 35 kg 32 kg 37 kg

Air throughput of fans (unimpeded air flow)

External circuit 910 m3/hInternal circuit 440 m3/h

Temperature control Basic or Comfort controller (factory setting +35°C) Accessories Packs of PageFilter mats 3 3286.500 189 Metal filters 1 3286.510 190 Quick-change frame 1 3286.700 182 Door-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195Interface card for Comfort controller 1 3124.200 179 Air-ducting system 1 3286.870 174 Cover stoppers for interior air outlet 2 3286.780 175 Condensate hose 1 3301.612 192

1) Delivery times available on request. 2) Transformer protection switch. Special voltages available on request. We reserve the right to make technical modifications.

QK .

QK/Pel.

74 Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 77: Erdinc  klima sk_broschuere_gb

Useful cooling output 1000 W

Roof-mounted cooling units

ed c

oolin

g un

its

475

597

417

490 390

Supply iNano-coaintegral eevaporatFully wireincludingassembly

Property rights:German registered designno. 402 02 324 German registered design no. 402 02 325

nt

ncludes:ted condenser and lectronic condensate ion. d ready for connection, drilling template and parts.

Accessories:

Roof plate for TS 8 with mounting cut-out, see page 181.

Approvals, see page 277.

Detailed drawing,see page 246.

Performance diagrams, available on the Internet.

Model No. SK with Basic controller, RAL 7035 3383.100 3383.110 3383.140

Roo

f-m

ou

Model No. SK with Comfort controller, RAL 7035 3383.500 3383.510 3383.540

Model No. SK with Basic controller, stainless steel1) 3383.200 3383.210 3383.240

Model No. SK with Comfort controller, stainless steel1) 3383.600 3383.610 3383.640

Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 400, 2~, 50/60Dimensions in mm WHD 597 x 417 x 475Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

1000 W/1080 W760 W/820 W

Rated current max. 4.9 A/5.1 A 9.5 A/10.0 A 2.8 A/2.8 AStart-up current 15.5 A/15.5 A 25.3 A/24.3 A 8.0 A/8.8 APre-fuse T 10.0 A 16.0 A 6.3 A – 10.0 A2) Power consumption Pel to DIN 3168

L 35 L 35L 35 L 50

690 W/790 W800 W/890 W

720 W/800 W810 W/900 W

Refrigeration factor ε = L 35 L 35 1.4 Refrigerant R134a, 500 gPermissible operating pressure p. max. 25 barTemperature and setting range +20°C to +55°C

Protection category to EN 60 529

External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 40 kg 46 kg 46 kg

Air throughput of fansExternal circuit 1760 m3/hInternal circuit 440 m3/h

Temperature control Basic or Comfort controller (factory setting +35°C)Accessories Packs of PageFilter mats 3 3286.500 189 Metal filters 1 3286.510 190 Quick-change frame 1 3286.800 182 Door-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195Interface card for Comfort controller 1 3124.200 179 Air-ducting system 1 3286.870 174 Cover stoppers for interior air outlet 2 3286.880 175 Condensate hose 1 3301.612 192

1) Delivery times available on request. 2) Transformer protection switch. Special voltages available on request. We reserve the right to make technical modifications.

QK .

QK/Pel.

Accessories Page 171 Configuration software Page 195

75Rittal System Climate Control

Page 78: Erdinc  klima sk_broschuere_gb

Roof-mounted Useful cooling output 11

Roo

f-m

oun

cooling units00/3000 W

895

597

417

392 692

475

597

417

490 390

ted

cool

ing

units

Especialapplicati(considecooling uapplicatio

Supply iNano-coaintegral eevaporat

ly for office ons. Low noise level rably quieter than nits for industrial ns).

ncludes:ted condenser and lectronic condensate ion. Fully wired ready

for connection, including drilling template and assembly parts.

Property rights: (Not with SK 3301.800)German registered design no. 402 02 324 German registered design no. 402 02 325

Accessories:

Roof plate for TS 8 with mounting cut-out, see page 181.

Approvals, see page 278.

Detailed drawing,see page 246.

Performance diagrams, available on the Internet.

Model No. SK with Comfort controller 3273.500 3273.5151) 3301.800

Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 230, 1~, 50Dimensions in mm WHD 597 x 417 x 475 597 x 417 x 895Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

1100 W/1200 W850 W/870 W

L 35 L 25L 45 L 35

3000 W3200 W

Rated current max. 5.2 A/5.4 A 11.0 A/11.5 A 9.2 AStart-up current 15.5 A/16.5 A 32.0 A/35.0 A 36.0 APre-fuse T gG 10.0 A 20.0 A Power circuit-breaker 16.0 A Power consumption Pel to DIN 3168

L 35 L 35L 35 L 50

890 W/910 W960 W/1100 W

920 W/940 W990 W/1140 W

L 35 L 25L 45 L 35

1820 W2325 W

Refrigeration factor ε = L 35 L 35 1.2 1.6Refrigerant R134a, 700 g R134a, 1200 gPermissible operating pressure p. max. 25 barTemperature and setting range +20°C to +55°C

Protection category to EN 60 529

External circuit IP 34Internal circuit IP 542)

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 42 kg 47 kg 72 kgColour RAL 7035

Air throughput of fansExternal circuit 1760 m3/h 1850 m3/hInternal circuit 440 m3/h 1450 m3/h

Temperature control Comfort controller (factory setting +35°C)Accessories Packs of PageFilter mats 3 3286.500 3286.600 189 Metal filters 1 3286.510 3286.610 190 Door-operated switch 1 4127.000 176 SK BUS system for Comfort controller 1 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195 Interface card for Comfort controller 1 3124.200 179 Air-ducting system 1 3286.870 3286.970 174 Cover stoppers for interior air outlet 2 3286.880 3286.980 175 Condensate hose 1 3301.612 192

1) Delivery times on request. 2) In order to avoid increased condensation, we recommend enclosures with a protection category of at least IP 54.Special voltages available on request. We reserve the right to make technical modifications.

QK .

QK/Pel.

Accessories Page 171 Configuration software Page 195

76 Rittal System Climate Control

Page 79: Erdinc  klima sk_broschuere_gb

Useful cooling output 1500/2000 W

Roof-mounted cooling units

nted

coo

ling

units

475

597

417

490 390

Supply Nano-cointegral evaporafor conntemplate

Model N

Property rights:German registered design no. 402 02 324 German registered design no. 402 02 325

includes:ated condenser and electronic condensate tion. Fully wired ready ection, including drilling and assembly parts.

Accessories:

Roof plate for TS 8 with mounting cut-out, see page 181.

Approvals, see page 277.

Detailed drawing,see page 246.

Performance diagrams, available on the Internet.

o. SK with Basic controller, RAL 7035 3384.100 3384.110 3384.140 3385.100 3385.110 3385.140

Roo

f-m

ou

Model No. SK with Comfort controller, RAL 7035 3384.500 3384.510 3384.540 3385.500 3385.510 3385.540

Model No. SK with Basic controller, stainless steel1) 3384.200 3384.210 3384.240 3385.200 3385.210 3385.240

Model No. SK with Comfort controller, stainless steel1) 3384.600 3384.610 3384.640 3385.600 3385.610 3385.640

Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 400, 2~, 50/60 230, 1~, 50/60 115, 1~, 50/60 400, 2~, 50/60Dimensions in mm WHD 597 x 417 x 475 597 x 417 x 475Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

1500 W/1520 W1100 W/1210 W

2000 W/2130 W1570 W/1670 W

Rated current max. 6.3 A/7.4 A 13.7 A/15.3 A 3.8 A/4.4 A 6.3 A/7.2 A 14.2 A/15.4 A 3.7 A/4.2 AStart-up current 16.6 A/17.1 A 30.7 A/29.1 A 9.8 A/9.6 A 16.8 A/18.4 A 36.0 A/32.0 A 10.0 A/12.0 APre-fuse T 10.0 A 20.0 A 6.3 A – 10.0 A2) 10.0 A 20.0 A 6.3 A – 10.0 A2) Power consumption Pel to DIN 3168

L 35 L 35L 35 L 50

955 W/1070 W1090 W/1230 W

990 W/1090 W1140 W/1290 W

1140 W/1310 W1240 W/1450 W

1190 W/1390 W1300 W/1520 W

Refrigeration factor ε = L 35 L 35 1.6 1.5 1.8 1.7Refrigerant R134a, 500 g R134a, 950 gPermissible operating pressure p. max. 25 barTemperature and setting range +20°C to +55°C

Protection categoryto EN 60 529

External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 41 kg 47 kg 47 kg 42 kg 48 kg 48 kg

Air throughput of fansExternal circuit 1760 m3/h 1820 m3/hInternal circuit 470 m3/h

Temperature control Basic or Comfort controller (factory setting +35°C)Accessories Packs of PageFilter mats 3 3286.500 189 Metal filters 1 3286.510 190 Quick-change frame 1 3286.800 182 Door-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195

Interface card for Comfort controller 1 3124.200 179 Air-ducting system 1 3286.870 174 Cover stoppers for interior air outlet 2 3286.880 175 Condensate hose 1 3301.612 192

1) Delivery times available on request. 2) Transformer protection switch. Special voltages available on request. We reserve the right to make technical modifications.

QK .

QK/Pel.

Accessories Page 171 Configuration software Page 195

77Rittal System Climate Control

Page 80: Erdinc  klima sk_broschuere_gb

Roof-moUseful coolin

Roo

f-m

ount

unted cooling unitsg output 3000/4000 W

580

796

470

692 392

ed c

oolin

g un

its

Supply inNano-coaintegral eevaporatiFully wireincludingeyebolt a

Property rights:German registered design no. 402 02 324 German registered design no. 402 02 325

cludes:ted condenser and lectronic condensate on. d ready for connection, drilling template, nd assembly parts.

Accessories:

Roof plate for TS 8 with mounting cut-out, see page 181.

Approvals, see page 277.

Detailed drawing,see page 246.

Performance diagrams, available on the Internet.

Model No. SK with Basic controller, RAL 7035 3386.140 3387.140

Model No. SK with Comfort controller, RAL 7035 3386.540 3387.540

Model No. SK with Basic controller, stainless steel1) 3386.240 3387.240

Model No. SK with Comfort controller, stainless steel1) 3386.640 3387.640

Rated operating voltage V/Hz 400, 3~, 50/460, 3~, 60 400, 3~, 50/460, 3~, 60Dimensions in mm WHD 796 x 470 x 580 796 x 470 x 580Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

3000 W/3300 W2200 W/2500 W

4000 W/4200 W3250 W/3490 W

Rated current max. 3.4 A/3.4 A 3.9 A/3.9 AStart-up current 8.0 A/9.0 A 17.0 A/19.0 APre-fuse T Motor circuit breaker 6.3 A – 10.0 APower consumption Pel to DIN 3168

L 35 L 35L 35 L 50

1320 W/1630 W1570 W/1910 W

1760 W/2200 W2010 W/2480 W

Refrigeration factor ε = L 35 L 35 2.3 Refrigerant R134a, 1600 g R134a, 1800 gPermissible operating pressure p. max. 25 barTemperature and setting range +20°C to +55°C

Protection category to EN 60 529External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 70 kg 77 kg

Air throughput of fansExternal circuit 3450 m3/h 3870 m3/hInternal circuit 1280 m3/h 1420 m3/h

Temperature control Basic or Comfort controller (factory setting +35°C)Accessories Packs of PageFilter mats 3 3286.600 189 Metal filters 1 3286.610 190 Quick-change frame 1 3286.900 182 Door-operated switch 1 4127.000 176 SK BUS system for Comfort controller 1 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195Interface card for Comfort controller 1 3124.200 179 Air-ducting system 1 3286.970 174 Cover stoppers for interior air outlet 2 3286.980 175 Condensate hose 1 3301.612 192

1) Delivery times available on request. Special voltages available on request. We reserve the right to make technical modifications.

QK .

QK/Pel.

78 Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 81: Erdinc  klima sk_broschuere_gb

with CO2 as the coolant, useful cooling output 1000 W

Roof-mounted cooling units

Roo

f-m

ount

ed c

oolin

g un

its

475

597

417

490 390

Environmcoolant This genealready uas the cocooling p

Supply iNano-coaintegral eevaporatFully wireincludingassembly

Model No

Rated opDimensioUseful coto DIN 31

entally friendly

ration of cooling units ses the alternative CO2 olant for generating the ower.

ncludes:ted condenser and lectronic condensate ion. d ready for connection, drilling template and parts.

Accessories:

Roof plate for TS 8 with mounting cut-out, see page 181.

Approvals, see page 278.

Detailed drawing,see page 246.

. SK with Comfort controller 3383.740

erating voltage V/Hz 230, 50/60ns in mm WHD 597 x 417 x 475oling output 68 L 35 L 35 1000 W

Temperature and setting range +20°C to +55°C

Protection category to EN 60 529External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 42 kgColour RAL 7035

Air throughput of fansExternal circuit 1760 m3/hInternal circuit 440 m3/h

Temperature control Comfort controller (factory setting +35°C)Accessories Packs of PageFilter mats 3 3286.500 189 Metal filters 1 3286.510 190 Door-operated switch 1 4127.000 176Air-ducting system 1 3286.870 174 Cover stoppers for interior air outlet 2 3286.880 175 Condensate hose 1 3301.612 192

We reserve the right to make technical modifications. Other specifications available upon request.

QK .

79Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 82: Erdinc  klima sk_broschuere_gb

Wal

l-mou

nted

coo

ling

units

Wall-mounted cooling units

Top design and top performance with a host of

assembly benefits. The Rittal platform strategy with

system-wide mounting cut-outs to fit cooling units and

air/air heat exchangers allows easy adaptation to the

required cooling output, even retrospectively.

80 Rittal System Climate Control

Page 83: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Wal

l-mou

nted

coo

ling

units

Versatility and flexibility of wall mountingWall-mounted cooling units – practical and elegant.Determination of the mounting cut-out depends on the mounting vari-ant – external, internal or partial internal mounting. This makes opti-mum use of the space available. With external mounting, openings are only required for air inlet and outlet. The enclosure surface con-taining the cut-out for partial or full internal mounting is stabilised by the divided internal case construc-tion. Special internal or external mounting kits are not required.

Integrated into TopTherm-Plus cooling unitsElectrical condensate evaporationCondensate arising inside the enclosure or on the evaporator coil of the cooling unit is effectively evaporated. The evaporator device inside the cooling units has a very high evaporation output (several litres per day). This is achieved thanks to the princi-ple of direct evaporation.

RiNano coatingThe standard nano-surface finish on heat exchanger membranes ensures a long, constant cooling output and eliminates the need for filter media in many areas.

Platform strategyFlexible performanceJust 5 mounting cut-outs for 8 different out-put categories provide investment security and facilitate easy adaptation of the cooling output to the ambient conditions and the installed heat loss.

Rittal platform strategyTopTherm air/air heat exchangers are also compatible with the mounting cut-outs.

Benefits at a glance● Super-efficient performance and energy

consumption● Wide output range from 225 to 4000 W● Controlling and monitoring via Basic or

Comfort controller ● Three-phase cooling units support

multiple voltages as standard● Uniform, output-related, cross-system

mounting cut-outs, to match TopTherm-Plus air/air heat exchangers

● Electrical condensate evaporation and RiNano coating

ImportantAir inlet and outlet openings in the internal and external circuit must not be obstructed by electrical installations.

Tips and tricksApplications see page 207

Selection criteria see page 208

Assembly see page 209

Air routing see page 210

Condensate management see page 213

Electrical connection and control see page 215

81

Page 84: Erdinc  klima sk_broschuere_gb

Wal

l-mou

nted

coo

ling

units

Wall-mountedVIP small cooling unit

cooling unitss, useful cooling output 225 W

526

353.

5288465

105

32183

296

288465

183

32

353.

5

296

105

1

1

60

60

Th

e new VIP SK small cooling units were developed especially for cooling the VIP 6000 com-mand panel. In addition, VIP small cooling units also offer a space-saving, economical solu-tion for the climate control of small enclosures where small heat loads are generated by the system.

Supply includes:Fully wired ready for connection and pre-mounted on an aluminium rear panel to fit VIP 6000 operating housing 7 U.

Property rights:German patent no. 198 17 917

Distance from installed equipment at least 60 mm

Approvals, see page 279.

Performance diagrams, available on the Internet.

1

Model No. SK 3201.100 3202.100

Condenser version Left RightRated operating voltage V/Hz 230, 50/60

Dimensions in mm WHD

526 353.5 105

Useful cooling output to DIN 3168

L 35 L 35L 35 L 45

225 W/270 W160 W/200 W

Rated current max. 1.5 A/1.5 AStart-up current 1.9 A/2.0 APre-fuse T 4.0 A/4.0 APower consumption Pel to DIN 3168

L 35 L 35L 35 L 45

285 W/300 W315 W/325 W

Refrigeration factor ε = L 35 L 35 0.8/0.9Refrigerant R134a, 170 gPermissible operating pressure p. max. 27 barTemperature and setting range +20°C to +45°C

Protection category to EN 60 529

External circuit IP 24Internal circuit IP 54

Duty cycle 100 %Type of connection Terminal stripWeight 10.5 kgColour Rear panel aluminium, vent grille RAL 7035

Air throughput of fansExternal circuit 235 m3/h / 270 m3/hInternal circuit 160 m3/h / 180 m3/h

Temperature control Electronic control (factory setting +35°C)Accessories Packs of PageTemperature indicator 1 3114.100 177 Condensate hose 1 3301.608 192

Special voltages available on request. We reserve the right to make technical modifications.

QK .

QK/Pel.

82 Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 85: Erdinc  klima sk_broschuere_gb

Mini cooling unit in horizontal format, useful cooling output 300 W

Wall-mounted cooling units

ed c

oolin

g un

its

340

525

153 98

55

Mini coolingformat, ideaenclosures ings with option.

l-mou

nt

units in horizontal l for cooling small and operating hous-timum space utilisa-

Supply includes:Nano-coated condenser. Fully wired ready for connection, including drilling template and assembly parts.

Approvals, see page 279.

Detailed drawing,see page 247.

Performance diagrams, available on the Internet.

Model No. SK 3302.300 3302.310

Wal

Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 60

Dimensions in mm WHD

525 340 153

Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

300 W/320 W 150 W/160 W

300 W150 W

Rated current max. 1.6 A/1.7 A 4.0 AStart-up current 4.3 A/5.3 A 12.0 APre-fuse T 10.0 A 10.0 APower consumption Pel to DIN 3168

L 35 L 35L 35 L 50

285 W/300 W320 W/340 W

290 W340 W

Refrigeration factor ε = L 35 L 35 1.1Refrigerant R134a, 100 g R134a, 95 gPermissible operating pressure p. max. 25 barTemperature and setting range +20°C to +55°C

Protection category to EN 60 529

External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 13 kgColour RAL 7035

Air throughput of fansExternal circuit 345 m3/hInternal circuit 310 m3/h

Temperature control Basic controllerAccessories Packs of PageTemperature indicator 1 3114.100 177 Condensate hose 1 3301.608 192 Filter mats 3 3286.110 189 Metal filters 1 3286.120 190

Special voltages available on request. We reserve the right to make technical modifications.

QK .

QK/Pel.

83Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 86: Erdinc  klima sk_broschuere_gb

Wall-mounteUseful cooling outp

Wal

l-mou

d cooling unitsut 300/500 W

T2

42

550

T

280 100110

1

T = Depth

nted

coo

ling

units

Supply iNano-coawired reaincludingassembly

ncludes:ted condenser. Fully dy for connection, drilling template and parts.

Partial internal mounting possible with 3303.XXX only.

Approvals, see page 280.

Detailed drawing,see page 247.

Performance diagrams, available on the Internet.

Property rights: German registered design no. 402 02 324 and no. 402 02 325 Japanese registered design no. 1 187 896 Indian registered design no. 189 953 US design patent no. D 488,480 IR reg. design no. DM/061 967 with validity for FR, IT, ES

1

Model No. SK with Basic controller, RAL 7035 3302.100 3302.110 3303.100 3303.110

Model No. SK with Comfort controller, RAL 7035 – – 3303.500 3303.510

Model No. SK with Basic controller, stainless steel1) 3302.200 3302.210 3303.200 3303.210

Model No. SK with Comfort controller, stainless steel1) – – 3303.600 3303.610

Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 60 230, 1~, 50/60 115, 1~, 60

Dimensions in mm

WHTT2

280 550 14098

280 550 210164

Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

300 W/320 W150 W/170 W

300 W150 W

500 W/610 W280 W/350 W

500 W280 W

Rated current max. 1.6 A/1.7 A 3.3 A 2.6 A/2.6 A 5.7 AStart-up current 3.0 A/3.4 A 8.0 A 5.1 A/6.4 A 11.5 APre-fuse T 10.0 A 10.0 A 10.0 A 10.0 APower consumption Pelto DIN 3168

L 35 L 35L 35 L 50

245 W/255 W255 W/275 W

290 W340 W

360 W/380 W420 W/390 W

470 W500 W

Refrigeration factor ε = L 35 L 35 1.2 1.4Refrigerant R134a, 100 g R134a, 170 gPermissible operating pressure p. max. 25 bar 28 barTemperature and setting range +20°C to +55°C

Protection category to EN 60 529

External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 13 kg 17 kg

Air throughput of fansExternal circuit 310 m3/h 345 m3/hInternal circuit 345 m3/h 310 m3/h

Temperature control Basic or Comfort controller (factory setting +35°C)Accessories Packs of PageFilter mats 3 3286.300 189 Metal filters 1 3286.310 190 Door-operated switch 1 4127.000 176 SK BUS system for Comfort controller 1 – 3124.100 180 RiDiag II including cables for Comfort controller 1 – 3159.100 195Interface card for Comfort controller 1 – 3124.200 179 Condensate hose 1 3301.608 3301.610 192

1) Delivery times available on request. Special voltages available on request. We reserve the right to make technical modifications.

QK .

QK/Pel.

Accessories Page 171 Configuration software Page 195

84 Rittal System Climate Control

Page 87: Erdinc  klima sk_broschuere_gb

Useful cooling output 750 W

Wall-mounted cooling units

ount

ed c

oolin

g un

its

235

45

550

280

280 125155

Supply inNano-coatwired readincluding dassembly

ll-m

cludes:ed condenser. Fully y for connection, rilling template and

parts.

Approvals, see page 280.

Detailed drawing,see page 247.

Performance diagrams, available on the Internet.

Property rights: German registered design no. 402 02 324 and no. 402 02 325 Japanese registered design no. 1 187 896 Indian registered design no. 189 953 US design patent no. D 488,480 IR reg. design no. DM/061 967 with validity for FR, IT, ES

Model No. SK with Basic controller, RAL 7035 3361.100 3361.110 3361.140

Model No. SK with Comfort controller, RAL 7035 3361.500 3361.510 3361.540

Wa

Model No. SK with Basic controller, stainless steel1) 3361.200 3361.210 3361.240

Model No. SK with Comfort controller, stainless steel1) 3361.600 3361.610 3361.640

Rated operating voltage V/Hz 230, 1~, 50/603) 115, 1~, 603) 4002), 2~, 50/603)

Dimensions in mmWHD

280 550 280

Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

750 W/780 W510 W/540 W

750 W500 W

750 W/780 W510 W/540 W

Rated current max. 2.3 A/2.4 A 5.3 A 1.2 A/1.4 AStart-up current 5.6 A/5.6 A 12.0 A 3.1 A/3.3 APre-fuse T 10.0 A 10.0 A 6.3 A – 10.0 A4) Power consumption Pelto DIN 3168

L 35 L 35L 35 L 50

480 W/550 W530 W/640 W

570 W670 W

480 W/550 W530 W/640 W

Refrigeration factor ε = L 35 L 35 1.5Refrigerant R134a, 280 g R134a, 260 g R134a, 280 g Permissible operating pressure p. max. 28 barTemperature and setting range +20°C to +55°C

Protection category to EN 60 529

External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 22 kg

Air throughput of fans (unimpeded air flow)

External circuit 480 m3/hInternal circuit 600 m3/h

Temperature control Basic or Comfort controller (factory setting +35°C)Accessories Packs of PageFilter mats 3 3286.300 189 Metal filters 1 3286.310 190 Door-operated switch 1 4127.000 176 SK BUS system for Comfort controller 1 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195Interface card for Comfort controller 1 3124.200 179 Condensate hose 1 3301.610 192

1) Delivery times on request. 2) External toroidal core transformer Ø 126 x 65 mm deep for mounting in the enclosure. 3) Tu max. = 52°C/60 Hz.4) Transformer protection switch. Special voltages available on request. Technical modifications reserved.

QK .

QK/Pel.

85Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 88: Erdinc  klima sk_broschuere_gb

Wall-mounted coolCool Efficiency, useful coolin

Wal

l-mou

NEWup to 45 % less

energy consump

ing unitsg output 1000 W

tion

105155

210

50

950

260400

nted

coo

ling

units

Supply inNano-coatintegral coration. Fullconnectiontemplate a

cludes:ed condenser and ndensate evapo-y wired ready for , including drilling nd assembly parts.

Approvals, see page 280.

Detailed drawing,see page 248.

Performance diagrams, available on the Internet.

Model No. SK with Basic controller, RAL 7035 3304.700

Model No. SK with Comfort controller, RAL 7035 3304.800

Rated operating voltage V/Hz 230, 1~, 50

Dimensions in mm WHD

400 950 260

Useful cooling output to DIN 3168 L35 L35 1000 W

Rated current max. 3.0 AStart-up current 12.0 APre-fuse T 10.0 APower consumption Pel to DIN 3168

L 35 L 35L 35 L 45

520 W580 W

Refrigeration factor ε = L 35 L 35 1.9Refrigerant R134a, 325 gPermissible operating pressure p. max. 20 barTemperature and setting range +20°C to +45°C

Protection category to EN 60 529

External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 40 kg

Air throughput of fansExternal circuit 600 m3/hInternal circuit 450 m3/h

Temperature control Basic or Comfort controller (factory setting +35°C)Accessories Packs of PageFilter mats 3 3286.400 189 Metal filters 1 3286.410 190 Door-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195

Interface card for Comfort controller 1 3124.200 179 Condensate hose 1 3301.612 192

Delivery times on request.Special voltages and other output categories available on request. Technical modifications reserved.

QK .

QK/Pel.

86 Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 89: Erdinc  klima sk_broschuere_gb

Useful cooling output 1000/1500 W

Wall-mounted cooling units

nted

coo

ling

units

105155

210

50

950

260400

Supply inNano-coatintegral eleevaporatiofor connectemplate a

Model No.

u

cludes:ed condenser and ctronic condensate n. Fully wired ready tion, including drilling nd assembly parts.

Approvals, see page 280.

Detailed drawing,see page 248.

Performance diagrams, available on the Internet.

Property rights: German registered design no. 402 02 325 IR reg. design no. DM/062 557 with validity for FR, IT, ES Indian registered design no. 190 269 Japanese registered design no. 1 187 905

SK with Basic controller, RAL 7035 3304.100 3304.110 3304.140 3305.100

3305.110 3305.140

Wal

l-mo

Model No. SK with Comfort controller, RAL 7035 3304.500 3304.510 3304.540 3305.500 3305.5101) 3305.540

Model No. SK with Basic controller, stainless steel1) 3304.200 3304.210 3304.240 3305.200 3305.210 3305.240

Model No. SK with Comfort controller, stainless steel1) 3304.600 3304.610 3304.640 3305.600 3305.610 3305.640

Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 400, 3~, 50/460, 3~, 60 230, 1~, 50/60 115, 1~, 50/60 400, 3~, 50/

460, 3~, 60

Dimensions in mm WHD

400 950 260

400 950 260

Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

1000 W/1060 W790 W/840 W

1500 W/1510 W1230 W/1250 W

Rated current max. 5.4 A/5.0 A 10.6 A/11.1 A 2.8 A/2.9 A 6.0 A/6.5 A 12.1 A/13.6 A 2.6 A/2.9 AStart-up current 12.0 A/14.0 A 26.0 A/28.0 A 11.5 A/12.7 A 22.0 A/24.0 A 42.0 A/46.0 A 12.2 A/11.3 APre-fuse T 10.0 A 16.0 A 6.3 A – 10.0 A2) 16.0 A 20.0 A 6.3 A – 10.0 A2) Power consumption Pel to DIN 3168

L 35 L 35L 35 L 50

825 W/775 W875 W/835 W

850 W/800 W900 W/875 W

700 W/675 W785 W/800 W

975 W/1125 W1125 W/1285 W

1000 W/1175 W1165 W/1325 W

925 W/1100 W1085 W/1275 W

Refrigeration factor ε = L 35 L 35 1.2 1.4 1.5 1.6Refrigerant R134a, 325 g R134a, 500 g R134a, 600 gPermissible operating pressure p. max. 25 barTemperature and setting range +20°C to +55°C

Protection category to EN 60 529

External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 39 kg 44 kg 40 kg 41 kg 46 kg 42 kg

Air throughput of fansExternal circuit 900 m3/hInternal circuit 600 m3/h 800 m3/h

Temperature control Basic or Comfort controller (factory setting +35°C)Accessories Packs of PageFilter mats 3 3286.400 189 Metal filters 1 3286.410 190 Door-operated switch 1 4127.000 176 SK BUS system for Comfort controller 1 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195

Interface card for Comfort controller 1 3124.200 179 Condensate hose 1 3301.612 192

1) Delivery times available on request. 2) Motor circuit-breaker. Special voltages available on request. We reserve the right to make technical modifications.

QK .

QK/Pel.

87Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 90: Erdinc  klima sk_broschuere_gb

Wall-mounted cSlimline, useful cooling

Wal

l-mou

ooling units output 1500 W

1590

205435 140

65

1590

165435 140

25

nted

coo

ling

units

● Simple, fast assemblthe need to drill addiholes

● Ideal for restricted mlocations

● Super-slimline design● Minimal installation d

build height.

Model No. SK with Basic

y without tional

ounting

epth and

Supply includes:Nano-coated condenser and integral electronic condensate evaporation. Fully wired ready for connection, including drilling template and assembly parts.

Approvals, see page 281/282.

Detailed drawing,see page 249.

Performance diagrams, available on the Internet.

controller, RAL 7035 3366.100 3377.1001) 3366.110 3377.1101) 3366.140 3377.1401)

1) 1) 1)

Model No. SK with Comfort controller, RAL 7035 3366.500 3377.500 3366.510 3377.510 3366.540 3377.540

Model No. SK with Basic controller, stainless steel1) 3366.200 3377.200 3366.210 3377.210 3366.240 3377.240

Model No. SK with Comfort controller, stainless steel1) 3366.600 3377.600 3366.610 3377.610 3366.640 3377.640

Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 400, 3~, 50/460, 3~, 60

Dimensions in mmWHD

435 1590 205

4351590165

4351590205

4351590165

4351590205

4351590165

Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

1500 W/1500 W1050 W/1100 W

1500 W/1500 W980 W/1080 W

Rated current max. 7.1 A/7.3 A 14.3 A/14.7 A 3.0 A/3.1 AStart-up current 22.0 A/24.0 A 43.0 A/47.0 A 8.0 A/8.8 APre-fuse T 10.0 A 20.0 A 6.3 A – 10.0 A2) Power consumption Pelto DIN 3168

L 35 L 35L 35 L 50

1045 W/1175 W1220 W/1335 W

1075 W/1200 W1265 W/1375 W

1090 W/1240 W1260 W/1430 W

Refrigeration factor ε = L 35 L 35 1.4 1.3Refrigerant R134a, 700 gPermissible operating pressure p. max. 28 barTemperature and setting range +20°C to +55°C

Protection category to EN 60 529

External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 45 kg 50 kg 46 kg

Air throughput of fans (unimpeded air flow)

External circuit 910 m3/hInternal circuit 860 m3/h

Temperature control Basic or Comfort controller (factory setting +35°C)Accessories Packs of PageFilter mats 3 3286.400 3253.010 3286.400 3253.010 3286.400 3253.010 189 Metal filters 1 3286.410 3253.220 3286.410 3253.220 3286.410 3253.220 190 Trim frame for external device mounting 1 3377.000 182 Door-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195

Interface card for Comfort controller 1 3124.200 179 Condensate hose 1 3301.612 192

1) Delivery times available on request. 2) Motor circuit-breaker. Special voltages available on request. Technical modifications reserved.

QK .

QK/Pel.

Accessories Page 171 Configuration software Page 195

88 Rittal System Climate Control

Page 91: Erdinc  klima sk_broschuere_gb

Useful cooling output 2000/2500 W

Wall-mounted cooling units

unte

d co

olin

g un

its

400

40

1580

295 145150

245

50

Supply includes:Nano-coated condeintegral electronic cevaporation. Fully wfor connection, inclutemplate, eyebolt anparts.

nser and ondensate ired ready ding drilling d assembly

Also required:

For installation in the door, we recommend the use of the ride-up roller (TS 4538.000) see Cat. 32, page 967 and 180° hinges (TS 8800.710), see Cat. 32, page 961, and for use in the side panel we recommend the use of the TS enclosure

panel fasteners (TS 8800.071), see Cat. 32, page 918.

Approvals, see page 280.

Detailed drawing,see page 248.

Performance diagrams, available on the Internet.

Wal

l-mo

Model No. SK with Basic controller, RAL 7035 3328.100 3328.110 3328.140 3329.100 3329.110 3329.140

Model No. SK with Comfort controller, RAL 7035 3328.500 3328.510 3328.540 3329.500 3329.510 3329.540

Model No. SK with Basic controller, stainless steel1) 3328.200 3328.210 3328.240 3329.200 3329.210 3329.240

Model No. SK with Comfort controller, stainless steel1) 3328.600 3328.610 3328.640 3329.600 3329.610 3329.640

Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 400, 3~, 50/460, 3~, 60 230, 1~, 50/60 115, 1~, 50/60 400, 3~, 50/

460, 3~, 60

Dimensions in mmWHD

400 1580 295

400 1580 295

Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

2000 W/2350 W1450 W/1690 W

2500 W/2750 W1600 W/1750 W

2500 W/2700 W1900 W/1950 W

Rated current max. 7.5 A/9.1 A 14.7 A/17.3 A 2.8 A/3.3 A 8.6 A/10.6 A 17.0 A/22.0 A 3.7 A/3.8 AStart-up current 22.0 A/26.0 A 36.0 A/39.0 A 6.8 A/7.8 A 21.0 A/21.0 A 44.0 A/42.0 A 6.8 A/7.6 APre-fuse T 16.0 A 25.0 A 6.3 A – 10.0 A2) 16.0 A 25.0 A 6.3 A – 10.0 A2) Power consumption Pel to DIN 3168

L 35 L 35L 35 L 50

1025 W/1200 W1250 W/1350 W

1085 W/1250 W1300 W/1410 W

1050 W/1275 W1275 W/1525 W

1450 W/1675 W1625 W/2000 W

1500 W/1725 W1675 W/2065 W

1425 W/1625 W1675 W/1975 W

Refrigeration factor ε = L 35 L 35 2.0 1.8 1.9 1.7 1.8Refrigerant R134a, 950 gPermissible operating pressure p. max. 28 barTemperature and setting range +20°C to +55°C

Protection category to EN 60 529

External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 66 kg 73 kg 67 kg 69 kg 76 kg 70 kg

Air throughput of fansExternal circuit 640 m3/h 710 m3/hInternal circuit 550 m3/h 640 m3/h

Temperature control Basic or Comfort controller (factory setting +35°C)Accessories Packs of PageFilter mats 3 3286.400 189 Metal filters 1 3286.410 190 Door-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195

Interface card for Comfort controller 1 3124.200 179 Condensate hose 1 3301.612 192

1) Delivery times available on request. 2) Motor circuit-breaker. Special voltages available on request. Technical modifications reserved.

QK .

QK/Pel.

89Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 92: Erdinc  klima sk_broschuere_gb

Wall-mounUseful cooling ou

Wal

l-mou

ted cooling unitstput 4000 W

1580

340500 145

195

nted

coo

ling

units

Supply includes:Nano-coated condintegral electronic evaporation. Fully for connection, inctemplate, eyebolt aparts.

enser and condensate wired ready luding drilling nd assembly

Note:External mounting and partial internal mounting of the cooling unit are available as standard. Partial internal mounting not possible with: – 600 mm wide TS enclosures and – 1200 mm wide TS enclosures

in the lockable door.

Also required:

When mounting in the door: Ride-up roller (TS 4538.000), see Cat. 32, page 967.When fitted with 180° hinges (TS 8800.710), see Cat. 32, page 961. When mounting in the side panel: Enclosure panel fasteners (TS 8800.071), see Cat. 32, page 918.

Approvals, see page 280.

Detailed drawing,see page 248.

Performance diagrams, available on the Internet.

Model No. SK with Basic controller, RAL 7035 3332.140

Model No. SK with Comfort controller, RAL 7035 3332.540

Model No. SK with Basic controller, stainless steel1) 3332.240

Model No. SK with Comfort controller, stainless steel1) 3332.640

Rated operating voltage V/Hz 400, 3~, 50/460, 3~, 60

Dimensions in mmWHD

500 1580 340

Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

4000 W/4400 W3070 W/3570 W

Rated current max. 4.2 A/4.2 AStart-up current 9.2 A/11.0 APre-fuse T Motor circuit-breaker 6.3 A – 10.0 APower consumption Pelto DIN 3168

L 35 L 35L 35 L 50

1850 W/2250 W2120 W/2590 W

Refrigeration factor ε = L 35 L 35 2.1Refrigerant R134a, 3000 gPermissible operating pressure p. max. 28 barTemperature and setting range +20°C to +55°C

Protection category to EN 60 529

External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 91 kg

Air throughput of fansExternal circuit 2000 m3/hInternal circuit 1500 m3/h

Temperature control Basic or Comfort controller (factory setting +35°C)Accessories Packs of PageFilter mats 3 3286.400 189 Metal filters 1 3286.410 190 Door-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195Interface card for Comfort controller 1 3124.200 179 Condensate hose 1 3301.612 192

1) Delivery times available on request. Special voltages available on request. Technical modifications reserved.

QK .

QK/Pel.

Accessories Page 171 Configuration software Page 195

90 Rittal System Climate Control

Page 93: Erdinc  klima sk_broschuere_gb

Design NEMA 4x, useful cooling output 500/1000/1500 W

Wall-mounted cooling units

ount

ed c

oolin

g un

its

298

358

405

1020

238

298

285

620

Supply includNano-coated partly integralcondensate ewired ready foincluding drillassembly par

m

es:condenser and electrical vaporation. Fully r connection,

ing template and ts.

Approvals, see page 282.

Detailed drawing,see page 249.

Performance diagrams, available on the Internet.

Model No. SK with Basic controller1) 3303.1043) 3303.1143) 3304.104 3304.114 3304.144 3305.104 3305.114 3305.1441) 3) 3)

Wal

l-

Model No. SK with Comfort controller 3303.504 3303.514 3304.504 3304.514 3304.544 3305.504 3305.514 3305.544

Rated operating voltage V/Hz 230, 1~, 50/60

115, 1~,60

230, 1~,50/60

115, 1~,50/60

400, 3~, 50/ 460, 3~, 60

230, 1~, 50/60

115, 1~, 50/60

400, 3~, 50/460, 3~, 60

Dimensions in mmWHD

285 620 298

405 1020 358

405 1020 358

Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

500 W/610 W 280 W/350 W

500 W280 W

1000 W/1060 W790 W/840 W

1500 W/1510 W1230 W/1250 W

Rated current max. 2.6/2.6 A 5.7 A 5.4/5.0 A 10.6/11.1 A 2.8/2.9 A 6.0/6.5 A 12.1/13.6 A 2.6/2.9 AStart-up current 5.1/6.4 A 11.5 A 12.0/14.0 A 26.0/28.0 A 11.5/12.7 A 22.0/24.0 A 42.0/46.0 A 12.2/11.3 A

Pre-fuse T 10.0 A 10.0 A 10.0 A 16.0 A 6.3 A – 10.0 A2) 16.0 A 20.0 A 6.3 A –

10.0 A2) Power consumption Pelto DIN 3168

L 35 L 35L 35 L 50

360/380 W420/390 W

470 W500 W

825/775 W875/835 W

850/800 W900/875 W

700/675 W785/800 W

975/1125 W1125/1285 W

1000/1175 W1165/1325 W

925/1100 W1085/1275 W

Refrigeration factor ε = L 35 L 35 1.4 1.7 1.8 1.7 1.9

Refrigerant R134a, 170 g R134a, 325 g R134a, 500 g R134a, 600 g

Permissible operating pressure p. max. 28 bar 25 bar 25 barTemperature and setting range +20°C to +55°CProtection rating NEMA 4xDuty cycle 100 %Type of connection Plug-in terminal stripWeight 25 kg 49 kg 54 kg 50 kg 51 kg 56 kg 52 kgMaterial Stainless steel 1.4404 (V4A) (AISI 316L)

Air throughput of fans

External circuit 345 m3/h 900 m3/h 900 m3/hInternal circuit 310 m3/h 600 m3/h 800 m3/h

Temperature control Basic or Comfort controller (factory setting +35°C)

Accessories Packs of Page

Door-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 – 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195

Interface card for Comfort controller 1 3124.200 179

Condensate hose 1 3301.610 3301.612 192 1) Delivery times available on request. 2) Motor circuit-breaker. 3) Without integral condensate evaporation. Special voltages available on request. We reserve the right to make technical modifications.

QK .

QK/Pel.

91Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 94: Erdinc  klima sk_broschuere_gb

Wall-Design

Wal

l-m

mounted cooling units NEMA 4x, useful cooling output 2000/2500 W

1650

328

388

405

ount

ed c

oolin

g un

its

Supply iNano-coaintegral eevaporatfor connetemplate

Model No

ncludes:ted condenser and lectronic condensate ion. Fully wired ready ction, including drilling

and assembly parts.

Approvals, see page 282.

Detailed drawing,see page 250.

Performance diagrams, available on the Internet.

. SK with Basic controller1) 3328.104 3328.114 3328.144 3329.104 3329.114 3329.144

Model No. SK with Comfort controller1) 3328.504 3328.514 3328.544 3329.504 3329.514 3329.544

Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 400, 3~, 50/ 460, 3~, 60 230, 1~, 50/60 115, 1~, 50/60 400, 3~, 50/

460, 3~, 60

Dimensions in mmWHD

405 1650 388

Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

2000 W/2350 W1450 W/1690 W

2500 W/2750 W1600 W/1750 W

2500 W/2700 W1900 W/1950 W

Rated current max. 7.5 A/9.1 A 14.7 A/17.3 A 2.8 A/3.3 A 8.6 A/10.6 A 17.0 A/22.0 A 3.7 A/3.8 AStart-up current 22.0 A/26.0 A 36.0 A/39.0 A 6.8 A/7.8 A 21.0 A/21.0 A 44.0 A/42.0 A 6.8 A/7.6 APre-fuse T 16.0 A 25.0 A 6.3 A – 10.0 A2) 16.0 A 25.0 A 6.3 A – 10.0 A2) Power consumption Pelto DIN 3168

L 35 L 35L 35 L 50

1025/1200 W1250/1350 W

1085/1250 W1300/1410 W

1050/1275 W1275/1525 W

1450/1675 W1625/2000 W

1500/1725 W1675/2065 W

1425/1625 W1675/1975 W

Refrigeration factor ε = L 35 L 35 1.7 2.3 1.9 2.0Refrigerant R134a, 900 gPermissible operating pressure p. max. 28 barTemperature and setting range +20°C to +55°CProtection rating NEMA 4xDuty cycle 100 %Type of connection Plug-in terminal stripWeight 80 kg 87 kg 80 kg 83 kg 90 kg 83 kgMaterial Stainless steel 1.4404 (V4A) (AISI 316L)

Air throughput of fansExternal circuit 640 m3/h 710 m3/hInternal circuit 550 m3/h 640 m3/h

Temperature control Basic or Comfort controller (factory setting +35°C)Accessories Packs of PageDoor-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195

Interface card for Comfort controller 1 3124.200 179 Condensate hose 1 3301.612 192

1) Delivery times available on request. 2) Motor circuit-breaker. Special voltages available on request. We reserve the right to make technical modifications.

QK .

QK/Pel.

92 Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 95: Erdinc  klima sk_broschuere_gb

for precision machine tools, useful cooling output 1000/1500 W

Wall-mounted cooling units

nted

coo

ling

units

105155

210

50

950

260400

These newcurrent reqsion machcludes higand a masweight. Thcreased sealso placeon supply cooling un

mou

devices meet the uirements of preci-

ine tools. This in-h acceleration values sive reduction in e associated in-nsitivity to vibration

s greater demands equipment such as its.

Supply includes:Nano-coated condenser and integral electronic condensate evaporation. Fully wired ready for connection, including drilling template and assembly parts.

Approvals, see page 283.

Detailed drawing,see page 248.

Performance diagrams, available on the Internet.

1)

Property rights: German registered design no. 402 02 325 IR reg. design no. DM/062 557 with validity for FR, IT, ES Indian registered design no. 190 269 Japanese registered design no. 1 187 905

Wal

l-

Model No. SK with Basic controller, RAL 7035 3304.142 3305.142

Model No. SK with Comfort controller, RAL 70351) 3304.542 3305.542

Rated operating voltage V/Hz 400, 3~, 50/460, 3~, 60

400, 3~, 50/460, 3~, 60

Dimensions in mm WHD

400 950 260

400 950 260

Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

1000 W/1060 W790 W/840 W

1500 W/1510 W1230 W/1250 W

Rated current max. 2.8 A/2.9 A 2.6 A/2.9 AStart-up current 11.5 A/12.7 A 12.2 A/11.3 APre-fuse T Motor circuit breaker 6.3 A – 10.0 APower consumption Pel to DIN 3168

L 35 L 35L 35 L 50

700 W/675 W785 W/800 W

925 W/1100 W1085 W/1275 W

Refrigeration factor ε = L 35 L 35 1.4 1.9Refrigerant R134a, 500 g R134a, 600 g Permissible operating pressure p. max. 25 barTemperature and setting range +20°C to +55°C

Protection category to EN 60 529

External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 40 kg 42 kg

Air throughput of fansExternal circuit 900 m3/hInternal circuit 600 m3/h 800 m3/h

Temperature control Basic or Comfort controller (factory setting +35°C)Accessories Packs of PageFilter mats 3 3286.400 189 Metal filters 1 3286.410 190 Door-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195

Interface card for Comfort controller 1 3124.200 179 Condensate hose 1 3301.612 192

1) Delivery times available on request. Special voltages available on request. We reserve the right to make technical modifications.

QK .

QK/Pel.

Accessories Page 171 Configuration software Page 195

93Rittal System Climate Control

Page 96: Erdinc  klima sk_broschuere_gb

Wal

l-mou

Wall-mounted cooling unitsExplosion-proof cooling units for zone 22 (dust), useful cooling output 1000/1500 W

950

260400

nted

coo

ling

units

These cooespeciallyling the cliexplosive

ling units have been developed for control-mate in potentially dust Zone 22 sectors.

Supply includes:Nano-coated condenser. Fully wired ready for connection, including drilling template and assembly parts.

Approvals, see page 283.

Detailed drawing,see page 248.

Performance diagrams, available on the Internet.

Model No. SK with Basic controller, RAL 7035 3304.130 3304.160 3305.130 3305.160

Model No. SK with Comfort controller, RAL 7035 3304.530 3304.560 3305.530 3305.560

Rated operating voltage V/Hz 230, 50/60 400, 3~, 50/460, 3~, 60 230, 50/60 400, 3~, 50/460, 3~, 60

Dimensions in mm WHD

400 950 260

400 950 260

Useful cooling output to DIN 3168

L 35 L 35L 35 L 50

1000 W/1060 W790 W/840 W

1500 W/1510 W1230 W/1250 W

Rated current max. 4.8 A/4.4 A 2.5 A/2.6 A 5.4 A/6.0 A 2.3 A/2.6 AStart-up current 12.0 A/14.0 A 11.5 A/12.7 A 22.0 A/24.0 A 12.2 A/11.3 APre-fuse T 10.0 A/10.0 A 6.3 A – 10.0 A1) 16.0 A/16.0 A 6.3 A – 10.0 A1) Power consumption Pel to DIN 3168

L 35 L 35L 35 L 50

700 W/650 W750 W/710 W

580 W/550 W660 W/680 W

850 W/1000 W1000 W/1160 W

800 W/980 W960 W/1150 W

Refrigeration factor ε = L 35 L 35 1.4 1.7 1.8 1.9Refrigerant R134a, 325 g R134a, 500 g R134a, 600 gPermissible operating pressure p. max. 25 barTemperature and setting range +20°C to +50°C

Protection category to EN 60 529

External circuit IP 54Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 39 kg 41 kg

Air throughput of fansExternal circuit 900 m3/hInternal circuit 600 m3/h 800 m3/h

Temperature control Basic or Comfort controller (factory setting +35°C)Accessories Packs of PageFilter mats 3 3286.400 189 Door-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 180 RiDiag II including cables for Comfort controller 1 3159.100 195Interface card for Comfort controller 1 3124.200 179 Condensate hose 1 3301.612 192

Delievery times available on request. We reserve the right to make technical modifications.1) Motor circuit-breaker

QK .

QK/Pel.

94 Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 97: Erdinc  klima sk_broschuere_gb

with CO2 as the coolant, useful cooling output 1000 W

Wall-mounted cooling units

Wal

l-mou

nted

coo

ling

units

105155

210

50

950

260400

Environmcoolant This genealready uas the cocooling p

Supply iNano-coaintegral eevaporatfor connetemplate

Model No

Rated opDimensioUseful coto DIN 31

entally friendly

ration of cooling units ses the alternative CO2 olant for generating the ower.

ncludes:ted condenser and lectronic condensate ion. Fully wired ready ction, including drilling

and assembly parts.

Approvals, see page 283.

Detailed drawing,see page 248.

. SK with Comfort controller 3304.740

erating voltage V/Hz 230, 50/60ns in mm WHD 400 x 950 x 260oling output 68 L 35 L 35 1000 W

Temperature and setting range +20°C to +40°C

Protection category to EN 60 529

External circuit IP 34Internal circuit IP 54

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 47 kgColour RAL 7035

Air throughput of fansExternal circuit 900 m3/hInternal circuit 600 m3/h

Temperature control Comfort controller (factory setting +35°C)Accessories Packs of PageFilter mats 3 3286.400 189 Metal filters 1 3286.410 190 Door-operated switch 1 4127.000 176Air-ducting system 1 – 174 Cover stoppers for interior air outlet 2 – 175 Condensate hose 1 3301.612 192

We reserve the right to make technical modifications. Other specifications available upon request.

QK .

95Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 98: Erdinc  klima sk_broschuere_gb

Ther

moe

lect

ric

cool

ers

96

Thermoelectric coolers

The powerful thermoelectric unit in a light-weight

design is the eco-friendly climate-control solution for

command panels and small enclosures producing

energy savings of more than 60 % compared with

conventional industry systems.

Internal mountingWhen installed in the enclosure, the unit only protrudes by a few millimetres, and therefore does not interrupt either the aesthetic appearance or freedom of move-ment on support arm systems.

External mountingIts low weight also allows it to be externally mounted on simple aluminium rear panels or blanking panels.

Scalable output The modular designs allows simple scaling of the cooling output depending on your requirements.

Rittal System Climate Control

Page 99: Erdinc  klima sk_broschuere_gb

Useful cooling output 100 W

Thermoelectric coolers

B = WidthT = Depth

Ap

herm

oele

ctri

c co

oler

s

plication: ● Ideal for cooling small

enclosures and command panels.

● Especially suitable for use on support arm systems as well.

● Optimum space utilisation. ● Targeted cooling of hot-spots. ● RJ45 interface for connecting

to the Rittal CMC system

Supply includes:Thermoelectric cooling unit, wired ready for connection, with multilingual documentation and mounting accessories.

Approvals, see page 284.

Detailed drawing,see page 250.

T

Model No. SK 3201.200 3201.300

Dimensions in mmWHD

125 400 155

Rated operating voltage V/Hz 100 – 230 V (AC) 24 V DCRefrigeration factor/COP L 35 L 35 1.0 1.2Useful cooling output to DIN 3168 L 35 L 35 100 W 100 W

Power pack integrated � – Colour of cover/unit RAL 7024/Anodised aluminiumProtection rating IP 54Weight 3.0 kg 2.5 kgTemperature range 0°C to +55°C 0°C to +55°C Air throughput, unimpeded air flow 50 m3/hType of connection Plug-in spring connection terminalPre-fuse gG 2 A 10 AAccessories Packs of PagePower pack 150 watts for 35 mm top-hat rail 1 – 3201.030 192 Filter mat 1 3201.050 191 Door-operated switch 1 4127.010 176Digital temperature indicator 1 3114.100/3114.115 3114.024 177 CMC monitoring system See Cat. 32, from page 808. Condensate hose, ∅ 6 mm 1 St. 3301.606 –

We reserve the right to make technical modifications. Special voltages available on request.

QK .

Innovative controlThe PID control ensures opti-mum activation of the Peltier elements and fans. Speed and output are energy-efficiently adjusted to the optimum operat-ing point thanks to pulse width modulation.

97Rittal System Climate Control

Accessories Page 171 Configuration software Page 195

Page 100: Erdinc  klima sk_broschuere_gb
Page 101: Erdinc  klima sk_broschuere_gb

Liquid cooling IE

Air/water heat exchangers from page 100

� � � Roof-mounted. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2500 W. . . . . . . 102� � � Roof-mounted. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4000 W. . . . . . . 103

� � � Micro, wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 W. . . . . . . 104� � Wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 600/1250 W. . . . . . . 105

� � � Wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500/1000 W. . . . . . . 106� � � Wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2000/3000 W. . . . . . . 107� � � Wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5000 W. . . . . . . 108

� Wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7000 W. . . . . . . 109

E

Water-carrying parts Suitable for command panels Wall-mounted

Rittal System Clima

stainless steel

Standardised installation Roof-mounted

E

qu

id c

oo

ling

IE

Direct Cooling Package from page 110

� � Cold Plate for frequency converters. . . . . . . . . . 2500 – 6000 W. . . . . . . 112� � � Cold Plate for frequency converters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113� � Cooling Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 400 – 900 W. . . . . . . 114

� Panel Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150/350 W. . . . . . . 115

E

Stainless steel Suitable for command panelsE

Li

Standardised installation Manufacturer-specific

Medium to be cooled: Water

Medium to be cooled: Oil

Medium to be cooled: Emulsion

Roof-mounted

Wall-mounted

Fast delivery range

W

Ö

E

Recooling systems from page 116

� Mini . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/1.5 kW. . . . . . . 118� Mini . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3/4.5 kW. . . . . . . 119� Mini . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 kW. . . . . . . 120� � Power Fluid Cooler . . . . . . . . . . . . . . . . . . . . . . . . . 7.5 to 59 kW. . . . . . . 121� In floor-standing enclosure. . . . . . . . . . . . . . . . . . . 2.1 to 36 kW. . . . . . . 123� Power Fluid Cooler . . . . . . . . . . . . . . . . . . . . . . . . 68 to 502 kW. . . . . . . 125� In TS 8 Top enclosure system . . . . . . . . . . . . . . . . . 6 to 25 kW. . . . . . . 127� � Mini for wall mounting. . . . . . . . . . . . . . . . . . . . . . . . 1/2.5/4 kW. . . . . . . 129

� � In floor-standing enclosure. . . . . . . . . . . . . . . . . . . 2.5 to 26 kW. . . . . . . 130

Immersible recooling systems from page 116

� Immersible recooling systems . . . . . . . . . . . . . . . 2.4 to 5.6 kW. . . . . . . 132� Immersible recooling systems . . . . . . . . . . . . . . 8.5 to 17.3 kW. . . . . . . 133� Immersible recooling systems . . . . . . . . . . . . . . . . 21 to 78 kW. . . . . . . 134

� Immersible recooling systems . . . . . . . . . . . . . . . 2.4 to 5.6 kW. . . . . . . 132� Immersible recooling systems . . . . . . . . . . . . . . 8.5 to 17.3 kW. . . . . . . 133� Immersible recooling systems . . . . . . . . . . . . . . . . 21 to 78 kW. . . . . . . 134

W Ö E

W Ö E

99te Control

Page 102: Erdinc  klima sk_broschuere_gb

Air

/wat

er h

eat e

xcha

nger

s

Air/water heat exchangers

The air of the enclosure interior may also be cooled to

below the level of the external temperature, if required,

by using cooling water from a central recooling

system. The ingress of dust from outside into the

cooled enclosure is prevented. The waste heat from

the enclosure does not raise the temperature of the

ambient air, provided the heat exchanger and cold

water supply system are spatially separated from one

another.

100 Rittal System Climate Control

Page 103: Erdinc  klima sk_broschuere_gb

Climate control platform strategy Identical mounting interface for cooling units and air/water heat exchangers. In this way, the device type and cooling output are easily varied.

VariantsRoof mountedEspecially for bayed enclosures, where wall-mounted devices would obstruct the door.

Wall mountedFor mounting on the wall or any sufficiently large vertical surface.

Rittal System Climate Control

Air

/wat

er h

eat e

xcha

nger

s

Effective in extreme conditionsAir/water heat exchangers can also be used at particularly extreme ambient tempera-tures from +1° to +70°C. Even extreme lev-els of contamination in the ambient air, e.g. with dust and oil, do not affect functionality. High heat losses are dissipated in the most confined spaces without emitting them directly to the ambient air. A high operating ratio is achieved, thanks to the large surface area of the heat exchanger unit.

Basic controller● Visualisation of the operating status via

LED display ● Switching hysteresis: 5 K● Floating fault signal contact in case of

overtemperature● Setpoint externally adjustable via poten-

tiometer (setting range 20°C – 55°C)

Comfort controller● Switching hysteresis: 2 – 10 K

preset to 5 K● System alarm, individually configurable for

2 floating fault signal contacts● Visualisation of the current enclosure

internal temperature and all system messages on the display

● Storage of all system statuses in the log file

● Optional extension card for integration into superordinate remote monitoring systems e.g. with CMC

Benefits at a glance● Useful cooling output from 300 W to

7000 W● Suitable for use even under extreme

conditions and at ambient temperatures of up to +70°C

● Also available with all water-carrying parts made from V4A

● System for TS 8 integrated into the side panel

● High protection category. Thanks to the sealed design, a protection category of IP 55 to EN 60 529 is achieved.

ImportantAir/water heat exchangers should always be used in conjunction with recooling systems or a cooling water circuit.

Tips and tricksApplications see page 217

Selection criteria see page 218

Assembly see page 219

Air routing see page 220/221

Condensate management see page 222/223

Electrical connection and control see page 224/225

101

Page 104: Erdinc  klima sk_broschuere_gb

Air

/wat

er h

eat e

xc

Air/water heaRoof-mounted, usef

t exchangersul cooling output 2500 W

2

1

475 597

417

390 490

hang

ers

Supply Fully wirewith contemplateassembl

Als

Cooling Rittal recfrom pag

includes:d ready for connection,

nector, including drilling , sealing mat and y parts.

o required:

water system such as ooling systems, e 116.

Condensate discharge 1/2˝ (flexible)

Cooling water connection 1/2˝ (flexible)

Approvals, see page 284.

Detailed drawing,see page 251.

Performance diagrams, available on the Internet.

Property rights: German registered designs no. 402 02 324 and no. 402 02 325 US design patent no. US D 492,319S Indian registered design no. 189 956 Chinese registered design no. ZL 0330 6415.6

1

2

Water-carrying parts

Model No. SK Basic controller CuAL 3209.100 3209.110 3209.1401)

Model No. SK Comfort controller CuAL 3209.500 3209.510 3209.5401)

Useful cooling output CuAL L 35 W 10, 400 l/h 2500 W

Model No. SK Basic controller V4A (stainless steel) 3209.1041) 3209.1141) 3209.1441)

Model No. SK Comfort controller V4A (stainless steel) 3209.5041) 3209.5141) 3209.5441)

Useful cooling output V4A L 35 W 10, 400 l/h 1875 W

Rated operating voltage V, Hz 230, 50/60 115, 50/60 400, 2~, 50/60

Dimensions in mmWHD

597417475

Rated current max. 0.40 A/0.48 A 0.85 A/0.95 A 0.25 A/0.30 APre-fuse T 4.0 ACooling medium Water (refer to specifications on the Internet; assembly instructions chapter 13)Water inlet temperature > +1°C to +30°CPermissible operating pressure p. max. 1 to 10 barTemperature range +1°C to +70°CProtection category to EN 60 529 IP 552)

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 23.5 kg 27.5 kg 27.5 kgColour RAL 7035Air throughput of fans (unimpeded air flow) 1030 m3/hTemperature control Basic or Comfort controller (factory setting +35°C)Accessories Packs of PageDoor-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 180 Interface card for Comfort controller 1 3124.200 179 Air ducting system 1 3286.870 174 Cover stoppers for interior air outlet 1 3286.880 175 Condensate hose 1 3301.612 192 Flow regulator valve 1 See accessories 194

1) Delivery times available on request. 2) IP 65 available on request. Special voltages available on request. We reserve the right to make technical modifications.

102 Rittal System Climate Control

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

Page 105: Erdinc  klima sk_broschuere_gb

Roof-mounted, useful cooling output 4000 W

Air/water heat exchangers

nger

s

2

1

475 597

417

390 490

SupplyFully wiwith cotemplatassemb

A

CoolingRittal refrom pa

xcha

includes:red ready for connection, nnector, including drilling e, sealing mat and ly parts.

lso required:

water system such as cooling systems, ge 116.

Condensate discharge 1/2˝ (flexible)

Cooling water connection 1/2˝ (flexible)

Approvals, see page 284.

Detailed drawing,see page 251.

Performance diagrams, available on the Internet.

Property rights:German registered designs no. 402 02 324 and no. 402 02 325 US design patent no. US D 492,319S Indian registered design no. 189 956 Chinese registered design no. ZL 0330 6415.6

1

2

Air

/wat

er h

eat e

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

Water-carrying parts

Model No. SK Basic controller CuAL 3210.100 3210.110 3210.1401)

Model No. SK Comfort controller CuAL 3210.500 3210.510 3210.5401)

Useful cooling output CuAL L 35 W 10, 400 l/h 4000 W

Model No. SK Basic controller V4A (stainless steel) 3210.1041) 3210.1141) 3210.1441)

Model No. SK Comfort controller V4A (stainless steel) 3210.5041) 3210.5141) 3210.5441)

Useful cooling output V4A L 35 W 10, 400 l/h 3000 W

Rated operating voltage V, Hz 230, 50/60 115, 50/60 400, 2~, 50/60

Dimensions in mmWHD

597417475

Rated current max. 0.44 A/0.5 A 0.9 A/1.0 A 0.25 A/0.3 APre-fuse T 4.0 ACooling medium Water (refer to specifications on the Internet; assembly instructions chapter 13)Water inlet temperature > +1°C to +30°CPermissible operating pressure p. max. 1 to 10 barTemperature range +1°C to +70°CProtection category to EN 60 529 IP 552)

Duty cycle 100 %Type of connection Plug-in terminal stripWeight 25.5 kg 29.5 kg 29.5 kgColour RAL 7035Air throughput of fans (unimpeded air flow) 925 m3/hTemperature control Basic or Comfort controller (factory setting +35°C)Accessories Packs of PageDoor-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 180 Interface card for Comfort controller 1 3124.200 179 Air ducting system 1 3286.870 174 Cover stoppers for interior air outlet 1 3286.880 175 Condensate hose 1 3301.612 192 Flow regulator valve 1 See accessories 194

1) Delivery times available on request. 2) IP 65 available on request. Special voltages available on request. We reserve the right to make technical modifications.

103Rittal System Climate Control

Page 106: Erdinc  klima sk_broschuere_gb

Air/water heaMicro, wall-mounted

Air

/wat

er h

eat e

xcha

nger

s

t exchangers, useful cooling output 300 W

85

300

150

12

85

300

150

12

Espe

cially for selective cooling of hot-spots in small enclosures.

Supply includes:Fully wired ready for connection, including drilling template and assembly parts.

Condensate discharge 3/8˝

Cooling water connection 3/8˝

Approvals, see page 284.

Detailed drawing,see page 251.

Performance diagrams, available on the Internet.

1

2

Model No. SK 3212.230 3212.1151) 3212.024

Rated operating voltage V, Hz 230, 50/60 115, 50/60 24 V (DC)

Dimensions in mmWHD

15030085

Useful cooling output L 35 W 10, 200 l/h 300 W

Rated current max. 0.11 A/0.13 A 0.23 A/0.24 A 1.20 APre-fuse T 4.0 ACooling medium Water (refer to specifications on the Internet; assembly instructions chapter 12)Water inlet temperature > +1°C to +30°CPermissible operating pressure p. max. 1 to 10 barTemperature range +1°C to +70°CProtection category to EN 60 529 IP 552)

Duty cycle 100 %Type of connection Connection clampWeight 3 kgColour RAL 7035Air throughput of fans (unimpeded air flow) 280 m3/h 250 m3/hAccessories Packs of PageTemperature indicator 1 3114.100 177 Door-operated switch 1 4127.000 176Condensate hose 1 3301.612 192 Flow regulator valve 1 See accessories 194

1) Delivery times available on request. 2) IP 65 available on request. Special voltages available on request. We reserve the right to make technical modifications.

104 Rittal System Climate Control

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

Page 107: Erdinc  klima sk_broschuere_gb

Wall-mounted, useful cooling output 600/1250 W

Air/water heat exchangers

100

500

200

12

100

950

200

12

Supply in

ange

rs

cludes:Fully wired ready for connection, with terminal strip, including drilling template, sealing mat and assembly parts.

Also required:

Cooling water system such as Rittal recooling systems, see page 116 onwards.

Condensate discharge 1/2˝

Cooling water connection 1/2˝

Approvals, see page 285.

Detailed drawing, see page 251/252.

Performance diagrams, available on the Internet.

1

2

Air

/wat

er h

eat e

xch

Model No. SK 3214.100 3215.100

Rated operating voltage V, Hz 230, 50/60

Dimensions in mmWHD

200 500 100

200950100

Useful cooling output L 35 W 10, 200 l/hL 35 W 10, 400 l/h

600 W650 W

1250 W1300 W

Rated current max. 0.17 A/0.18 A 0.38 A/0.4 APre-fuse T 2.0 A 4.0 ACooling medium Water (refer to specifications on the Internet; assembly instructions chapter 12)Water inlet temperature > +1°C to +30°CPermissible operating pressure p. max. 1 to 10 barTemperature range +1°C to +70°CProtection category to EN 60 529 IP 551) Duty cycle 100 %Type of connection Terminal stripWeight 7 kg 13 kgColour RAL 7035Air throughput of fans 120 m3/h 200 m3/hTemperature control Thermostat-controlled magnetic valve

Temperature monitoring Internal thermostat, with change-over contact, switching load 16 A, setting range +20°C to +60°C (factory setting +35°C)

Accessories Packs of PageTemperature indicator 1 3114.100 177 Door-operated switch 1 4127.000 176Condensate hose 1 3301.612 192 Flow regulator valve 1 See accessories 194

1) IP 65 available on request. Special voltages available on request. We reserve the right to make technical modifications.

105Rittal System Climate Control

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

Page 108: Erdinc  klima sk_broschuere_gb

Air/wateWall-mount

Air

/wat

er h

eat e

xcha

r heat exchangersed, useful cooling output 500/1000 W

142

550

280

2

1

92

550

280

2

1

nger

s

SupplyFully wiwith cotemplatassemb

includes:red ready for connection, nnector, including drilling e, sealing mat and ly parts.

Also required:

Cooling water system such as Rittal recooling systems, from page 116.

Approvals, see page 285.

Detailed drawing,see page 252.

Performance diagrams, available on the Internet.

Cooling water connection 1/2˝

Condensate discharge 1/2˝

1

2

Water-carrying parts

Model No. SK Basic controller CuAL 3363.100 3363.1101) 3363.1401) 3364.100 3364.1101) 3364.1401)

Model No. SK Comfort controller CuAL 3363.500 3363.5101) 3363.5401) 3364.500 3364.5101) 3364.5401)

Useful cooling output CuAL L 35 W 10, 400 l/h 500 W 1000 W

Model No. SK Basic controller V4A (stainless steel) 3363.1041) 3363.1141) 3363.1441) 3364.1041) 3364.1141) 3364.1441)

Model No. SK Comfort controller V4A (stainless steel) 3363.5041) 3363.5141) 3363.5441) 3364.5041) 3364.5141) 3364.5441)

Useful cooling output V4A L 35 W 10, 400 l/h 375 W 750 W

Rated operating voltage V, Hz 230, 1~,50/60

115, 1~,50/60

400, 2~, 50/60

230, 1~,50/60

115, 1~,50/60

400, 2~, 50/60

Dimensions in mmWHD

28055092

280550142

Rated current max. 0.17 A/0.18 A 0.35 A/0.40 A 0.1 A/0.12 A 0.2 A/0.19 A 0.4 A/0.38 A 0.12 A/0.11 APre-fuse T 4.0 A 4.0 A3) 4.0 A 4.0 A3) Cooling medium Water (refer to specifications on the Internet; assembly instructions chapter 13)Water inlet temperature +1°C to +30°CPermissible operating pressure p. max. 1 to 10 barTemperature range +1°C to +70°CProtection category to EN 60 529 IP 552) Duty cycle 100 %Type of connection Plug-in terminal stripWeight 12 kg 15 kgColour RAL 7035Air throughput of fans (unimpeded air flow) 270/320 m3/hTemperature control Basic or Comfort controller (factory setting +35°C) Accessories Packs of PageDoor-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 180 Interface card for Comfort controller 1 3124.200 179 Condensate hose 1 3301.612 192 Flow regulator valve 1 See accessories 194

1) Delivery times available on request. 2) IP 65 available on request. 3) 2-pole miniature circuit breaker Special voltages available on request. We reserve the right to make technical modifications.

106 Rittal System Climate Control

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

Page 109: Erdinc  klima sk_broschuere_gb

Wall-mounted, useful cooling output 2000/3000 W

Air/water heat exchangers

hang

ers

142

950

400

2

1

Supply Fully wirewith contemplateassembl

includes:d ready for connection,

nector, including drilling , sealing mat and y parts.

Also required:

Cooling water system such as Rittal recooling systems, from page 116.

Approvals, see page 285.

Detailed drawing,see page 253.

Performance diagrams, available on the Internet.

Cooling water connection 1/2˝

Condensate discharge 1/2˝

1

2

Air

/wat

er h

eat e

xc

1 Water-carrying parts

Model No. SK Basic controller CuAL 3373.100 3373.1101) 3373.1401) 3374.100 3374.1101) 3374.1401)

Model No. SK Comfort controller CuAL 3373.500 3373.5101) 3373.5401) 3374.500 3374.5101) 3374.5401)

Useful cooling output CuAL L 35 W 10, 400 l/h 2000 W 3000 W

Model No. SK Basic controller V4A (stainless steel) 3373.1041) 3373.1141) 3373.1441) 3374.1041) 3374.1141) 3374.1441)

Model No. SK Comfort controller V4A (stainless steel) 3373.5041) 3373.5141) 3373.5441) 3374.5041) 3374.5141) 3374.5441)

Useful cooling output V4A L 35 W 10, 400 l/h 1500 W 2250 W

Rated operating voltage V, Hz 230, 1~,50/60

115, 1~,50/60

400, 2~, 50/60

230, 1~,50/60

115, 1~,50/60

400, 2~, 50/60

Dimensions in mmWHD

400950142

Rated current max. 0.38 A/0.43 A 0.75 A/0.85 A 0.22 A/0.25 A 0.57 A/0.78 A 1.15 A/1.55 A 0.35 A/0.45 APre-fuse T 4.0 A 4.0 A3) 4.0 A 4.0 A3) Cooling medium Water (refer to specifications on the Internet; assembly instructions chapter 13)Water inlet temperature +1°C to +30°CPermissible operating pressure p. max. 1 to 10 barTemperature range +1°C to +70°CProtection category to EN 60 529 IP 552) Duty cycle 100 %Type of connection Plug-in terminal stripWeight 20 kgColour RAL 7035Air throughput of fans (unimpeded air flow) 600/625 m3/h 700/730 m3/hTemperature control Basic or Comfort controller (factory setting +35°C) Accessories Packs of PageDoor-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 180 Interface card for Comfort controller 1 3124.200 179 Condensate hose 1 3301.612 192 Flow regulator valve 1 See accessories 194

1) Delivery times available on request. 2) IP 65 available on request. 3) 2-pole miniature circuit breaker Special voltages available on request. We reserve the right to make technical modifications.

107Rittal System Climate Control

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

Page 110: Erdinc  klima sk_broschuere_gb

Air/water heWall-mounted, use

Air

/wat

er h

eat e

xcha

at exchangersful cooling output 5000 W

250

1400

450

2

1

nger

s

SupplyFully wiwith cotemplatassemb

includes:red ready for connection, nnector, including drilling e, sealing mat and ly parts.

Also required:

Cooling water system such as Rittal recooling systems, from page 116.

Approvals, see page 285.

Detailed drawing,see page 253.

Performance diagrams, available on the Internet.

Cooling water connection 1/2˝

Condensate discharge 1/2˝

1

2

Water-carrying parts

Model No. SK Basic controller CuAL 3375.100 3375.1101) 3375.1401)

Model No. SK Comfort controller CuAL 3375.500 3375.5101) 3375.5401)

Useful cooling output CuAL L 35 W 10, 400 l/h 5000 W

Model No. SK Basic controller V4A (stainless steel) 3375.1041) 3375.1141) 3375.1441)

Model No. SK Comfort controller V4A (stainless steel) 3375.5041) 3375.5141) 3375.5441)

Useful cooling output V4A L 35 W 10, 400 l/h 3750 W

Rated operating voltage V, Hz 230, 1~, 50/60 115, 1~, 50/60 400, 2~, 50/60

Dimensions in mmWHD

450 1400 250

Rated current max. 1.0 A/1.35 A 2.0 A/2.7 A 0.6 A/0.8 APre-fuse T 4.0 A 4.0 A3) Cooling medium Water (refer to specifications on the Internet; assembly instructions chapter 13) Water inlet temperature +1°C to +30°CPermissible operating pressure p. max. 1 to 10 barTemperature range +1°C to +70°CProtection category to EN 60 529 IP 552) Duty cycle 100 %Type of connection Plug-in terminal stripWeight 56 kg 59 kgColour RAL 7035Air throughput of fans (unimpeded air flow) 2365/2750 m3/hTemperature control Basic or Comfort controller (factory setting +35°C) Accessories Packs of PageDoor-operated switch 1 4127.000 176SK BUS system for Comfort controller 1 3124.100 180 Interface card for Comfort controller 1 3124.200 179 Condensate hose 1 3301.612 192 Flow regulator valve 1 See accessories 194

1) Delivery times available on request. 2) IP 65 available on request. 3) 2-pole miniature circuit breaker Special voltages available on request. We reserve the right to make technical modifications.

108 Rittal System Climate Control

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

Page 111: Erdinc  klima sk_broschuere_gb

Wall-mounted, useful cooling output 7000 W

Air/water heat exchangers

300

1800

450

12

Su

s

pply includes:Fully wired ready for connection, with terminal strip, including drilling template, sealing mat and assembly parts.

Also required:

Cooling water system such as Rittal recooling systems, from page 116.

Condensate discharge 1/2˝

Cooling water connection 1/2˝

Approvals, see page 285.

Detailed drawing,see page 254.

Performance diagrams, available on the Internet.

1

2

Model No. SK 3216.4801)

Air

/wat

er h

eat e

xcha

nger

Rated operating voltage V, Hz 400, 3~, 50/60 480, 3~, 60

Dimensions in mmWHD

450 1800 300

Useful cooling output L 35 W 10, 500 l/hL 35 W 20, 500 l/h

7000 W4500 W

Rated current max. 1.4 A/1.6 A 1.2 APre-fuse T 4.0 A, 3-pole Power consumption Pel 450 W/700 W 630 WCooling medium Water (refer to specifications on the Internet; assembly instructions chapter 12)Water inlet temperature +1°C to +30°CPermissible operating pressure p. max. 1 to 10 barTemperature range +1°C to +70°CProtection category to EN 60 529 IP 552) Duty cycle 100 %Type of connection Terminal stripWeight 79 kgColour RAL 7035Air throughput of fans 2400 m3/hTemperature control Thermostat-controlled magnetic valveAccessories Packs of PageTemperature indicator 1 3114.100 177 Door-operated switch 1 4127.000 176Condensate hose 1 3301.612 192 Flow regulator valve 1 See accessories 194

1) Delivery times available on request. 2) IP 65 available on request. Special voltages available on request. We reserve the right to make technical modifications.

Adaptor frameFor mounting the air/water heat exchanger SK 3216.480 on side panels of 500 mm deep TS enclosures.

Material:Sheet steel

Colour:RAL 7035

Detailed drawing, see page 254.

Packs of Model No. SK

1 3216.470

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

109Rittal System Climate Control

Page 112: Erdinc  klima sk_broschuere_gb

Dir

ect c

oolin

g pa

ckag

e

Direct cooling package

Power electronic components can be cooled

particularly effectively using the liquid cooled DCP

mounting plate. Heat losses are cleverly dissipated

from the enclosure or housing without compromising

the high enclosure protection category in any way.

Furthermore, liquid cooling is both quiet and

1000 times more efficient than heat dissipation

via air.

110

y p e Te s te

The Rittal DCP Cold Plate has received type-tested certification from the TÜV inspection authority and is approved for pressures up to 10 bar.

Rittal System Climate Control

Page 113: Erdinc  klima sk_broschuere_gb

Dir

ect c

oolin

g pa

ckag

e

AssemblyHeight and depth-variable mount-ing positions are offered by the system punchings of the TS 8 profiles in conjunction with punched section with mounting flange 17 x 73 mm (for the outer mounting level).

Rittal System Climate Control

AssemblyAttachment directly in the T-slotDirect and fast mounting using sliding nuts for components with suitable dimensions. Direct earthing or equipotential bonding points may be provided on the Cold Plate.

Attachment with variable clamping systemSupports fast mechanical installation with-out the need for drilling, independently of the original attachment points on the compo-nent. For use with a wide range of models and makes.

AssemblyAttachment with retainersFrequency converters with dimensions marginally smaller than the T-slot spacing can be secured with special retainers.

Attachment with tapped holesPower electronics can be mounted at any position over the whole surface by drilling tapped holes up to max. 12 mm in depth.

Benefits at a glance● High surface quality (Ra = 1.2 μm) to

reduce thermal resistance● No vibrations from compressors and fans● Ideal for precision machine tools● No noise generation● No top-mounted parts on the enclosure● Enclosure may be installed in the

machine base and in niches● The protection category of the enclosure

is preserved● Mounting surface on both sides may be

used as a contact surface for heat dissipation

● Space-saving configuration of electronic components in the enclosure

ImportantManufacturer or customer-specific Cold Plates may be supplied on a project-related basis on request.

111

Page 114: Erdinc  klima sk_broschuere_gb

DC

P –

Dir

ect C

oolin

g P

acka

ge

DCP – Direct Cooling Cold Plate for frequency converter

112

Packages

B

T

H

B = WidthT = Depth

Wi

thout T-slotLiquid-cooled partial mounting plate with drilling surfaceWhole surface can be used by the customer for own tapped holes (blind holes) to a maxi-mum drilling depth of 12 mm.

With T-slotLiquid-cooled partial mounting plate for fastening with a variable clamping systemFast mounting of converters with system fastening and additional possibility for tapped holes (blind holes) to a maximum drilling depth of 8 mm.

Version:Press-fitted copper or stainless steel tubes, dependent on the application, in closed recooling systems or existing (open) water circuit. Cooling water connec-tion: G 1/4˝, anti-twist.

Supply includes:Mounting accessories for system integration into TS.

Accessories:

Accessories for fluid distribution connection, see page 184.

TS punched section with mount-ing flange 17 x 73 mm for the external mounting level, see Catalogue 32, page 1023.

Recooling systems for closed cooling circuits, see from page 116.

Further technical information is available at www.rittal.com/dcp

Approvals, see page 286.

Detailed drawing,see page 255.

Without T-slot

With T-slot

Model No. DCP 8616.610 8616.630 8616.810 8616.830 8616.0102) 8616.0302) 8616.2102) 8616.2302)

For installation in Enclosure width mm 600 600 800 800 1000 1000 1200 1200Enclosure depth (side) mm 600 600 800 800 1000 1000 – –

Dimensions in mmWHD

499 399 25

499 399 25

699 399 25

699 399 25

899 399 25

899 399 25

1099 399 25

109939925

Output1) 2500 W 2500 W 3000 W 3000 W 5000 W 5000 W 6000 W 6000 W

Material CU VA CU VA CU VA CU VAPacks of 1 1 1 1 1 1 1 1

1) At 25°C medium inlet temperature, DCP surface temperature ≈ 50°C, medium flowrate = 200 l/h, surface roughness: 1.2 μm. 2) Delivery times available on request.

Model No. DCP 8616.600 8616.620 8616.800 8616.820 8616.0002) 8616.0202) 8616.2002) 8616.2202)

For installation in Enclosure width mm 600 600 800 800 1000 1000 1200 1200Enclosure depth (side) mm 600 600 800 800 1000 1000 – –

Dimensions in mmWHD

499 399 20

499 399 20

699 399 20

699 399 20

899 399 20

899 399 20

1099 399 20

109939920

Output1) 2500 W 2500 W 3000 W 3000 W 5000 W 5000 W 6000 W 6000 W

Material CU VA CU VA CU VA CU VAPacks of 1 1 1 1 1 1 1 1

1) At 25°C medium inlet temperature, DCP surface temperature ≈ 50°C, medium flowrate = 200 l/h, surface roughness: 1.2 μm. 2) Delivery times available on request.

Q.

Q.

Recooling systems page 116 Accessories page 184

Rittal System Climate Control

Page 115: Erdinc  klima sk_broschuere_gb

Cold Plate

Rittal System Climate Control

for frequency converters, manufacturer-specific

DCP – Direct Cooling Package

B

T

H

B = WidthT = Depth

Sie

ng P

acka

ge

mens SINAMICS S120 series BooksizePre-manufactured tapped holes on a 50 mm pitch pattern for attaching the S120 modules. For the design of SINAMICS drive modules in the S120 series, please contact your local Siemens agent.

Danfoss frequency converters VLT� Automation Drive FC300 for enclosure sizes A2 (0.37 – 4 kW/380 – 500 V) A3 (5.5 – 7.5 kW/380 – 500 V) with a channel spacing of 257 mm may be used.

Approvals, see page 286.

Detailed drawing,see page 255.

DC

P –

Dir

ect C

ooli

Version Siemens SINAMICS S120 Booksize Danfoss VLT� Automation Drive FC300

Model No. DCP 8616.640 8616.6411) 8616.840 8616.8411) 8616.6501) 8616.6511) 8616.8501) 8616.8511)

For installation in Enclosure width mm 600 600 800 800 600 600 800 800Enclosure depth mm 600 600 800 800 600 600 800 800

Dimensions in mmWHD

499 44920

499 44920

699 44920

699 44920

499 299 20

499 299 20

699 299 20

699 299 20

Material CU VA CU VA CU VA CU VAPacks of 1 1 1 1 1 1 1 1

Special sizes available on request. Surface roughness: 1.2 μm. Rear: Press-fitted copper or stainless steel tubes, dependent on the application, in closed recooling systems or existing (open) water infrastructure. Cooling water connection: G 1/4˝, anti-twist. 1) Delivery times available on request.

Recooling systems page 116 Accessories page 184

113

Page 116: Erdinc  klima sk_broschuere_gb

DC

P –

Dir

ect C

oolin

g P

acka

ge

DCP – Direct Cooling PackageCooling Unit

2

H

B

T

B = WidthT = Depth

1

Th

e Cooling Unit is available in two variants. As add-on in conjunction with a Rittal Cold Plate or as a stand-alone unit with press-fitted pipework in the cooler. The optional housing for the cooler ensures even more efficient air routing and thus reliable cooling of the air inside the enclosure.

Functional principle: The warm air inside the enclo-sure is drawn in by a powerful radial fan and passed through the cooler.

The unit can be operated either indirectly, i.e. mounted on a Rittal Cold Plate, or as a fully autonomous system with its own cooling water circulation. The latter supports direct mounting on the mounting plate in the immediate vicinity of major heat loss sources. In this variant, additional copper or stainless steel tubes are press-fitted into the cooler.

Convincing arguments: ● Direct cooling of power

electronics on the Rittal Cold Plate and lowering of the enclosure internal temperature

● Decentralised cooling of high-performance power electronics

● No change to the existing protection category of the enclosure

Approvals, see page 286.

Further technical information is available at www.rittal.com/dcp

1

2

Version Add-on Stand-alone

Model No. DCP 8616.500 8616.5101) 8616.5502) 8616.5602)

Dimensions in mmWHD

252 572 205

252 572 205

252 572 205

252 572 205

Power 400 W 800 W 500 W 900 W

Packs of 1 1 1 11) Space required behind the DCP = 110 mm 2) Cooling unit as stand-alone unit with its own fluid connection (2 x G 1/4˝), anti-twist. Delivery times available on request.

1 2

Recooling systems page 116 Accessories page 184

114 Rittal System Climate Control

Page 117: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Panel Cooling

DCP – Direct Cooling Package

B

H

T

B = WidthT = Depth

Th

irec

t Coo

ling

Pac

kage

is integrated Panel Cooling solution was developed by Rittal for optimum, space-saving cooling of operating housings. Heat losses of approx. 150 – 350 W can be dissipated without the need for external add-ons. The high protection category of the enclosure is retained, thanks to the fluid connection at the rear of the panel.

Functional principle: The fan unit with six individual fans ensures optimum air circu-lation at the cooler for efficient dissipation of the heat losses arising in the housing. The unit can be connected either to an existing coolant circuit or else to an external recooling system.

Convincing arguments: ● High performance with

minimal space requirements ● No reduction of the original

protection category ● No external add-ons

necessary

Operating housing cooling e.g. for the Comfort Panel and for special enclosures such as stainless steel enclosures for the food and consumables industry. Cooling units may be ordered for heat losses of up to 350 W on a project-specific basis.

Approvals, see page 287.

Further technical winformation is available at www.rittal.com/dcp

DC

P –

D

Model No. DCP 8616.300 8616.310

Dimensions in mmWHD

300 250 50

400 300 60

Power 150 W 350 W

Packs of 1 1Delivery times available on request.

Recooling systems page 116

115

Page 118: Erdinc  klima sk_broschuere_gb

Rec

oolin

g sy

stem

s IE

Recooling systems IE

Recooling systems ensure centralised, efficient cooling

and supply of the cooling medium (generally water). All

cooling tasks on a system or machine can be solved

via a single pipeline system.

Spatial separation between cooling production and

process cooling can be achieved with recooling

systems.

116 Rittal System Climate Control

Page 119: Erdinc  klima sk_broschuere_gb

Rittal Syste

Rec

oolin

g sy

stem

s IE

NEW

Fast delivery range up to 50 kW ● Standardised versions ● Basic version available off-the-shelf ● Shorter delivery times for defined

options

m Climate Control

Application diversity of centralised cooling technologyEnclosure coolingIn conjunction with air/water heat exchang-ers, optimum dissipation of high heat loads is guaranteed, even under extreme ambient temperatures and air contamination levels.

Cooling of liquid mediaThe direct and indirect cooling of liquids is essential for ensuring the required levels of machine accuracy and speed.

Process coolingHigh-quality material processing, such as laser cutting, necessitates high levels of temperature precision with simultaneous cooling of the peripheral technology.

Standard RiNano coatingRecooling systems, mini-wall-mounted and Power Fluid coolers: with RiNano coating as standard. The heat exchanger membranes ultra-thin, glass-like seals prevent dirt from settling on the condenser.

Benefits at a glance● Cooling output from 1 to 500 kW● A single system for enclosure cooling,

process and machine cooling, and the cooling of liquid media.

● Integration into bayed enclosure suites● Individual project management● Commissioning and servicing● Comprehensive pipeline calculation● Global service network

ImportantCooling output calculated at 32°C ambient temperature and an inlet temperature of 10°C and 18°C (water) or 20°C (oil)

Tips and tricksApplications see page 226

Selection criteria see page 227

Assembly see page 228

Notes see page 229

117

Page 120: Erdinc  klima sk_broschuere_gb

Rec

oolin

g sy

stem

s fo

r w

ater

Recooling systemsMini, cooling output 1/1.5 kW

for water

430

600

400

Technic

al design: ● Compact, modular structure

of the cooling components on a base plate designed as a collecting tray.

● With RiNano coating. ● Pump to convey the medium. ● Precise temperature control,

based on microprocessor technology.

● Collective fault signal with floating contact.

● Application-specific special equipment available on request.

● Pressure-sealed system (.600) or open system with tank (.610).

Supply includes:Recooling system wired ready for connection, with multilingual documentation including func-tional diagram and wiring plans.

Approvals, see page 287.

Layout diagram, see page 258.

Characteristic curves of pump, see page 258.

Other options, see page 256.

Model No. SK 3318.600 3318.610 3319.600 3319.610

Rated operating voltage V/Hz 230, 50/60

Dimensions in mmWHD

600 400 430

Cooling output at Tw = 10°C/Tu = 32°C Tw = 18°C/Tu = 32°C

0.8 kW/0.9 kW 1.0 kW/1.1 kW

1.2 kW/1.3 kW 1.5 kW/1.7 kW

Power consumption 0.63 kW/0.78 kW 0.85 kW/1.05 kWRated current max. 4.2 A 5.4 ARefrigerant R134aNo. of cooling circuits 1

Temperature range Environment +15°C to +43°CLiquid media +10°C to +25°C

Pump capacity See characteristic curveTank Pressure-sealed Made from PP plastic Pressure-sealed Made from PP plasticTank capacity – 2.5 l – 2.5 lWater connections 1/2˝ internal threadWeight 48 kg 51 kgColour RAL 7035Protection category (electrics) IP 44Air throughput of fans 900 m3/hTemperature control Microcontroller control (factory setting +18°C) Accessories Packs of PageMetal filters 1 3286.510 190

Special voltages and technical modifications available on request. We reserve the right to make technical modifications.

118 Rittal System Climate Control

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194

Page 121: Erdinc  klima sk_broschuere_gb

Mini, cooling output 3/4.5 kW

Recooling systems for water

645

602

676

25

Technical de● Compact,

tion of the nents with

olin

g sy

stem

s fo

r w

ater

sign: modular configura-cooling compo-integral water tank.

● With RiNano coating. ● Integral tank level display.● Pump to convey the medium.● Precise temperature control,

based on microprocessor technology.

● Collective fault signal with floating contact.

● Application-specific special equipment available on request.

Supply includes:Recooling system wired ready for connection, with multilingual documentation including func-tional diagram and wiring plans.

Approvals, see page 287.

Layout diagram, see page 258.

Characteristic curves of pump, see page 258.

Other options, see page 256.

Rec

o

Model No. SK 3320.600 3334.600

Rated operating voltage V/Hz 400, 3~, 50/60/460, 3~, 601)

Dimensions in mmWHD

602 676 645

Cooling output at Tw = 10°C/Tu = 32°C Tw = 18°C/Tu = 32°C

2.7 kW/3.0 kW 3.0 kW/3.4 kW

3.9 kW/4.7 kW 4.5 kW/5.4 kW

Power consumption 1.72 kW/1.95 kW 2.00 kW/2.51 kWRated current max. 3.8 A/4.6 A/3.9 A 4.9 A/5.9 A/5.0 ARefrigerant R134aNo. of cooling circuits 1

Temperature range Environment +15°C to +43°CLiquid media +10°C to +25°C

Pump capacity See characteristic curveTank Plastic Tank capacity 30 lWater connections 1/2˝ internal threadWeight (empty) 88 kg 94 kgColour RAL 7035Protection category (electrics) IP 44Air throughput of fans 1785 m3/hTemperature control Microcontroller control (factory setting +18°C)Accessories Packs of PageMetal filters 1 3286.520 190

1) Supports multiple voltages without rewiring. Special voltages and technical modifications available on request. We reserve the right to make technical modifications.

119Rittal System Climate Control

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194

Page 122: Erdinc  klima sk_broschuere_gb

Recooling systeMini, cooling output 6 kW

Rec

oolin

g sy

stem

s fo

r w

ater

ms for water

645

602

1050

25

Technical design● Compact, mod

: ular configura-

tion of the cooling compo-nents with integral water tank.

● With RiNano coating. ● Integral tank level display.● Pump to convey the medium.● Precise cooling control based

on microprocessor technol-ogy.

● Collective fault signal with floating contact.

● Application-specific special equipment available on request.

Supply includes:Recooling system wired ready for connection, with multilingual documentation including func-tional diagram and wiring plans.

Approvals, see page 288.

Layout diagram, see page 258.

Characteristic curves of pump, see page 258.

Other options, see page 256.

Model No. SK 3334.660

Rated operating voltage V/Hz 400, 3~, 50/60/460, 3~, 601)

Dimensions in mmWHD

602 1050 645

Cooling output at Tw = 10°C/Tu = 32°C Tw = 18°C/Tu = 32°C

4.8 kW/5.2 kW/5.2 kW 6.0 kW/6.6 kW/6.6 kW

Power consumption 4.3 kW/5.1 kW/5.1 kWRated current max. 8 A/9.7 A/8 ARefrigerant R134aNo. of cooling circuits 1

Temperature range Environment +15°C to +43°CLiquid media +10°C to +25°C

Pump capacity See characteristic curveTank Made from PP plastic Tank capacity 30 lWater connections 3/4˝ internal threadWeight 125 kgColour RAL 7035Protection category (electrics) IP 44Air throughput of fans 2200/2500 m3/hTemperature control Microcontroller control (factory setting +18°C)Accessories Packs of PageMetal filters 1 3286.520 190

1) Supports multiple voltages without rewiring. Special voltages and technical modifications available on request. We reserve the right to make technical modifications.

120 Rittal System Climate Control

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194 Twin castors Catalogue 32, page 907

Page 123: Erdinc  klima sk_broschuere_gb

Power Fluid Cooler, cooling output 7.5 kW

Recooling systems for water

Fast delivery range

H

TB

B = WidthT = Depth

Technical design● Enclosure in a

ling

syst

ems

for

wat

er

: modern indus-

trial design. ● Compact, modular layout of

the refrigeration components. ● With RiNano coating. ● Collective fault signal with

floating contact. ● Space-saving, compact

design.

Options: 1. Flow monitor 2. Flow monitor

+ pump (4 bar stainless steel) 3. Automatic bypass valve 4. Automatic bypass valve

+ pump (4 bar stainless steel) 5. Hot gas bypass6. Flow monitor

+ pump (4 bar stainless steel) + hot gas bypass

Supply includes:Recooling system wired ready for connection, with multilingual documentation including func-tional diagram and wiring plans.

Approvals, see page 288.

Layout diagram, see page 258.

Characteristic curves of pump, see page 258.

Rec

oo

Model No. SK 3234.090

Rated operating voltage V/Hz 400, 3~, 50

Dimensions in mmWHD

595 1305 800

Cooling output at Tw = 10°C/Tu = 32°C Tw = 18°C/Tu = 32°C

5.2 kW 7.5 kW

Power consumption 3.8 kWRated current max. 7 ARefrigerant R134aNo. of cooling circuits 1

Temperature range Environment +15°C to +43°CLiquid media +10°C to +25°C

Pump capacity See characteristic curveTank Plastic Tank capacity 57 lWater connections 1˝ internal threadWeight (empty) 147 kgColour RAL 7035Protection category (electrics) IP 44Air throughput of fans 3140 m3/hTemperature control Microcontroller control (factory setting +18°C) Accessories Packs ofMetal filters 1 on request

We reserve the right to make technical modifications.

121Rittal System Climate Control

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194

Page 124: Erdinc  klima sk_broschuere_gb

RecooPower Fl

Rec

oolin

g sy

stem

s fo

r w

ater

ling systems for wateruid Cooler, cooling output 10 to 59 kW

Fast delivery range

H

TB

B = WidthT = Depth

Technical de

sign: ● Enclosure in a modern indus-

trial design. ● Compact, modular layout of

the refrigeration components. ● With RiNano coating. ● Collective fault signal with

floating contact. ● Space-saving, compact

design.

Options for SK 3234.100/.110/.120/.130/.140/.1501. Flow monitor 2. Flow monitor

+ pump (4 bar stainless steel) 3. Automatic bypass valve 4. Automatic bypass valve

+ pump (4 bar stainless steel) 5. Hot gas bypass6. Flow monitor

+ pump (4 bar stainless steel) + hot gas bypass

Options for SK 3234.160/.170/.180/.190 1. Automatic bypass valve

+ pump (4 bar stainless steel) 2. Pressure-sealed tank

+ pump (4 bar stainless steel) + automatic bypass valve

3. Pressure-sealed tank

Supply includes:Recooling system wired ready for connection, with multilingual documentation including func-tional diagram and wiring plans.

Approvals, see page 288.

Layout diagram, see page 258.

Characteristic curves of pump, see page 258.

Model No. SK 3234.100 3234.110 3234.120 3234.130 3234.140 3234.150 3234.160 3234.170 3234.180 3234.190

Rated operating voltage V, Hz 400, 3~, 50

Dimensions in mmWHD

655 1280 1160

755 1280 1360

85515001560

104017002000

Cooling output at Tw = 10°C/Tu = 32°C Tw = 18°C/Tu = 32°C

7 kW 10 kW

10 kW 14 kW

11 kW 16 kW

13 kW 19 kW

15 kW 21 kW

18 kW 25 kW

23 kW 32 kW

25 kW 36 kW

33 kW 47 kW

41 kW 59 kW

Power consumption 3.8 kW 4.8 kW 5.3 kW 6.4 kW 7.1 kW 8.1 kW 15.9 kW 17.6 kW 15.0 kW 21.0 kWRated current max. 10.6 A 13.1 A 14.1 A 16.2 A 18.2 A 19.7 A 24.4 A 26.9 A 28.0 A 36.0 ARefrigerant R407CNo. of cooling circuits 1

Temperature range Environment +15°C to +43°CLiquid media +10°C to +25°C

Pump capacity See characteristic curveTank Plastic Stainless steelTank capacity 60 l 100 l 150 l 220 lWater connections 1˝ internal thread 11/4˝ internal thread 11/2˝ internal threadWeight (empty) 215 kg 225 kg 235 kg 240 kg 250 kg 260 kg 280 kg 300 kg 460 kg 490 kgColour RAL 7035Protection category (electrics) IP 54Air throughput of fans 6280 m3/h 10880 m3/h 18000 m3/h 32000 m3/hTemperature control Microcontroller control (factory setting +18°C) Accessories Packs ofMetal filters 1 on request

We reserve the right to make technical modifications.

122 Rittal System Climate Control

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194

Page 125: Erdinc  klima sk_broschuere_gb

In floor-standing enclosure, cooling output 2.1 to 7.7 kW

Recooling systems for water

T

H

B

B = WidthT = Depth

Te

ng s

yste

ms

for

wat

er

chnical design: ● Robust industrial standard in

3 enclosure sizes.● Identical basic enclosure

for oil and water recooling systems.

● Spare space for the integra-tion of special equipment

● Variable air routing is possi-ble via the l/h or r/h side panel

● Floating contact for collective fault signal.

● Level monitor/float-actuated switch.

● Multi-coil vaporiser in the tank.

Supply includes:Recooling system wired ready for connection, with multilingual documentation including func-tional diagram and wiring plans.

Note:The illustration shows units with customer-specific options.

Accessories:

Metal filter mats, castors and bypass valve available on request.

Approvals, see page 288.

Layout diagram, see page 260.

Characteristic curves of pump, see page 260.

Options, see page 256.

Rec

ooli

Model No. SK 3336.100 3336.200 3336.300 3336.500 3336.600 3336.650

Rated operating voltage V/Hz 400, 3~, 50

Dimensions in mmWHD

470 725 540

485 965 650

595 1180 800

Cooling output at Tw = 10°C/Tu = 32°C Tw = 18°C/Tu = 32°C

1.7 kW 2.1 kW

2.1 kW 2.6 kW

2.3 kW 3.4 kW

3.6 kW 5.0 kW

4.8 kW 6.2 kW

5.2 kW 7.7 kW

Power consumption 1.5 kW 1.7 kW 2.3 kW 2.9 kW 3.7 kW 3.9 kWRated current max. 3.4 A 3.0 A 4.2 A 5.5 A 6.2 A 7.3 ARefrigerant R134aNo. of cooling circuits 1

Temperature range Environment +15°C to +43°CLiquid media +10°C to +25°C

Pump capacity See characteristic curveTank Made from stainless steel 1.4301 (AISI 304)Tank capacity 17 l 33 l 57 lWater connections 3/4˝ internal thread 1˝ internal threadWeight 75 kg 97 kg 99 kg 141 kg 143 kg 147 kgColour RAL 7035Protection category (electrics) IP 54Air throughput of fans 700 m3/h 1250 m3/h 1785 m3/h 3140 m3/hTemperature control Electronic control with digital display (factory setting +18°C)

Delivery times available on request. Special voltages, other frequencies, and technical modifications available on request. We reserve the right to make technical modifications.

123Rittal System Climate Control

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194

Page 126: Erdinc  klima sk_broschuere_gb

Recooling sIn floor-standing e

Rec

oolin

g sy

stem

s fo

r w

ater

ystems for waternclosure, cooling output 10 to 36 kW

T

H

B

B = WidthT = Depth

Te

chnical design: ● Robust industrial housing in

2 enclosure sizes.● Identical basic enclosure

for oil and water recooling systems.

● Integration of application-specific special equipment on request.

● Variable air routing is possi-ble via the l/h or r/h side panel.

● Optimum accessibility for servicing purposes by remov-ing the side panel.

● Floating contact for collective fault signal.

● Flow monitor.

Supply includes:Recooling system wired ready for connection, with multilingual documentation including func-tional diagram and wiring plans.

Note:The illustration shows units with customer-specific options.

Accessories:

Metal filter mats, castors, eyebolts and bypass valve available on request.

Approvals, see page 288.

Layout diagram, see page 260.

Characteristic curves of pump, see page 260.

Options, see page 256.

Model No. SK 3336.700 3336.710 3336.720 3336.730 3336.740 3336.750 3339.100 3339.200

Rated operating voltage V, Hz 400, 3~, 50/460, 3~, 60

Dimensions in mmWHD

615 1178 1160

715 1178 1360

81514001560

Cooling output at Tw = 10°C/Tu = 32°C Tw = 18°C/Tu = 32°C

8.3/10.4 kW10.0/12.6 kW

11.9/15.514.4/18.7

13.5/16.616.3/20.1

15.0/18.118.5/22.4

17.0/20.720.9/25.4

20.6/26.425.2/32.3

26.2/31.432.0/38.4

29.6/35.536.2/43.5

Power consumption 3.8 kW 4.8 kW 5.3 kW 6.4 kW 7.1 kW 13.1 kW 18.3 kW 18.6 kWRated current max. 10.6 A 13.1 A 14.1 A 16.2 A 18.2 A 23.7 A 29.2 A 30.7 ARefrigerant R407CNo. of cooling circuits 1

Temperature range Environment +15°C to +43°C1) Liquid media +10°C to +25°C

Pump capacity See characteristic curveTank Made from stainless steel 1.4301 (AISI 304)Tank capacity 60 l 100 l 150 lWater connections 1˝ internal thread 11/4˝ internal threadWeight 215 kg 225 kg 235 kg 240 kg 250 kg 260 kg 260 kg 300 kgColour RAL 7035Protection category (electrics) IP 54 IP 54Air throughput of fans 6280 m3/h 10880 m3/h 16000 m3/hTemperature control Electronic control with digital display (factory setting +18°C)

1) SK 3336.720 and SK 3336.750 +15°C to +40°C.Delivery times available on request. Special voltages and technical modifications available on request. We reserve the right to make technical modifications.

124 Rittal System Climate Control

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194

Page 127: Erdinc  klima sk_broschuere_gb

Power Fluid Cooler, cooling output 68 to 209 kW

Recooling systems for water

T

H

B

B = WidthT = Depth

Te

oolin

g sy

stem

s fo

r w

ater

chnical design: ● Compact design with control

components in the front and air intake via both side pan-els, air outlet upwards.

● Open system. ● Digital thermostat for tempera-

ture control with setpoint and actual value display.

● Flow monitor.

Options: 1. Automatic bypass valve

+ pump (4 bar stainless steel) 2. Pressure-sealed tank

+ pump (4 bar stainless steel) + automatic bypass valve

3. Pressure-sealed tank

Supply includes:Recooling system wired ready for connection, with multilingual documentation including func-tional diagram and wiring plans.

Approvals, see page 289.

Layout diagram, see page 258.

Characteristic curves of pump, see page 258.

Rec

Model No. SK 3234.200 3234.210 3234.220 3234.230 3234.240 3234.250 3234.260 3234.270 3234.280

Rated operating voltage V, Hz 400, 3~, 50

Dimensions in mmWHD

1100 1606 2450

1100 1606 2450

1100 1606 2450

1100 1606 2950

1100 1875 2950

1100 1875 2950

110018752950

1100 1875 2950

110018753950

Cooling output at Tw = 10°C/Tu = 32°C Tw = 18°C/Tu = 32°C

48 kW 68 kW

55 kW 79 kW

63 kW 90 kW

71 kW 101 kW

87 kW 124 kW

95 kW 135 kW

111 kW 158 kW

123 kW 175 kW

146 kW 209 kW

Power consumption 20.5 kW 24.0 kW 27.0 kW 28.0 kW 38.5 kW 41.2 kW 50.0 kW 55.8 kW 66.0 kWRated current max. 40.0 A 46.0 A 50.0 A 77.0 A 66.5 A 71.9 A 88.4 A 99.7 A 112.3 ARefrigerant R410ANo. of cooling circuits 2

Temperature range Environment –20°C to +43°C Liquid media +10°C to +25°C

Pump capacity See characteristic curveTank Made from stainless steel 1.4301 (AISI 304) Tank capacity 300 l 500 l Water connections 21/2˝ internal threadWeight (empty) 790 kg 820 kg 835 kg 920 kg 1115 kg 1140 kg 1215 kg 1305 kg 1485 kgColour RAL 9002 Protection category (electrics) IP 54Air throughput of fans 13720 m3/h 20450 m3/h 27300 m3/h 35500 m3/h 60900 m3/hTemperature control Microcontroller control

We reserve the right to make technical modifications.

125Rittal System Climate Control

Air/water heat exchangers From page 102 Cooling medium Page 194

Page 128: Erdinc  klima sk_broschuere_gb

Rec

oolin

g sy

stem

s fo

r w

ater

Recooling systems for waterPower Fluid Cooler, cooling output 271 to 502 kW

T

H

B

B = WidthT = Depth

Te

chnical design: ● Compact design with control

components in the front and air intake via both side pan-els, air outlet upwards.

● Pressure-sealed system. ● Digital thermostat for tempera-

ture control with setpoint and actual value display.

● Flow monitor.

Options: Automatic bypass valve + pump (4 bar stainless steel)

Supply includes:Recooling system wired ready for connection, with multilingual documentation including func-tional diagram and wiring plans.

Approvals, see page 289.

Layout diagram, see page 258.

Characteristic curves of pump, see page 258.

Model No. SK 3234.290 3234.300 3234.310 3234.320 3234.330 3234.340

Rated operating voltage V, Hz 400, 3~, 50

Dimensions in mmWHD

2200 2450 3400

2200 2450 4250

Cooling output at Tw = 10°C/Tu = 32°C Tw = 18°C/Tu = 32°C

190 kW 271 kW

214 kW 305 kW

237 kW 339 kW

284 kW 406 kW

316 kW 452 kW

351 kW 502 kW

Power consumption 80 kW 88 kW 96 kW 120 kW 132 kW 144 kWRated current max. 200 A 219 A 237 A 300 A 328 A 355 ARefrigerant R410ANo. of cooling circuits 2

Temperature range Environment –20°C to +43°C Liquid media +10°C to +25°C

Pump capacity See characteristic curveTank Steel Tank capacity 700 l Water connections 3˝ internal thread 4˝ internal thread Weight (empty) 2650 kg 2740 kg 2780 kg 3400 kg 3500 kg 3600 kgColour RAL 9002 Protection category (electrics) IP 54Air throughput of fans 83000 m3/h 78000 m3/h 76000 m3/h 112000 m3/h 111500 m3/h 111000 m3/hTemperature control Microcontroller control

We reserve the right to make technical modifications.

126 Rittal System Climate Control

Air/water heat exchangers From page 102 Cooling medium Page 194

Page 129: Erdinc  klima sk_broschuere_gb

Rittal System

In TS 8 Top enclosure system, cooling output 6/7.5 W

Recooling systems for water

TB

H10

0

B = WidthT = Depth

Te

ling

syst

ems

for

wat

er

chnical design: ● Compact structure with con-

trol components in the front and air intake via the rear.

● Suitable for bayed siting.● Special fittings and options

available on request.● Float-actuated switch as pro-

tection against running dry.● Floating collective fault signal.● Equipped with Grundfos

pumps and Siemens compo-nents.

● Service accessibility from all sides.

Supply includes:Recooling system wired ready for connection, with multilingual documentation including func-tional diagram and wiring plans.

Note:The illustration shows units with customer-specific options.

Accessories:

Metal filter mat and bypass valve available on request.

Approvals, see page 289.

Detailed drawing,see page 263.

Layout diagram, see page 263.

Characteristic curves of pump, see page 263.

Options, see page 256.

Rec

oo

Model No. SK 3335.060 3335.075

Rated operating voltage V/Hz 400, 3~, 50

Dimensions in mmWHD

600 2150 600

Base/plinth height mm 100Cooling output at Tw = 10°C/Tu = 32°C Tw = 18°C/Tu = 32°C

4.8 kW 6.0 kW

6.0 kW 7.5 kW

Power consumption 2.4 kW 2.5 kWRated current max. 8.0 A 8.5 ARefrigerant R407CNo. of cooling circuits 1

Temperature range Environment +10°C to +43°CLiquid media +10°C to +30°C

Pump capacity See characteristic curveTank Made from PP plasticTank capacity 105 lWater connections 3/4˝ external thread Weight 180 kg 190 kgColour RAL 7035Protection category (electrics) IP 54Air throughput of fans 4000 m3/h

Temperature control Electronic control with digital display, setting range +10°C to +30°C (factory setting +18°C)

Delivery times available on request. Special voltages, other frequencies and refrigerants, and technical modifications available on request. We reserve the right to make technical modifications.

Air/water heat exchangers From page 102 TS 8 lock systems Cat. 32, from page 947 TS 8 baying system Cat. 32, from page 138Overflow valve page 194 Cooling medium page 194

127 Climate Control

Page 130: Erdinc  klima sk_broschuere_gb

RecooIn TS 8 T

128

Rec

oolin

g sy

stem

s fo

r w

ater

ling systems for waterop enclosure system, cooling output 10/25 W

T

H10

0

BT

B

H10

0

B = WidthT = Depth

Te

chnical design: ● Compact design with control

components in the front and air intake via the rear.

● Suitable for bayed siting.● Special fittings and options

available on request.● Float-actuated switch as pro-

tection against running dry.● Floating collective fault signal.● Magnetic valve in the cooling

circuit.● Equipped with Grundfos

pumps and Siemens compo-nents.

● Service accessibility from all sides.

Supply includes:Recooling system wired ready for connection, with multilingual documentation including func-tional diagram and wiring plans.

Note:The illustration shows units with customer-specific options.

Accessories:

Metal filter mat and bypass valve available on request.

Approvals, see page 289.

Layout diagram, see page 263.

Characteristic curves of pump, see page 263.

Options, see page 256.

Model No. SK 3335.100 3335.120 3335.150 3335.200 3335.250

Rated operating voltage V/Hz 400, 3~, 50

Dimensions in mmWHD

800 2150 600

1200 2150 600

Base/plinth height mm 100 Cooling output at Tw = 10°C/Tu = 32°C Tw = 18°C/Tu = 32°C

8.0 kW 10.0 kW

10.0 kW 12.0 kW

11.5 kW 15.0 kW

17.0 kW 20.0 kW

22.0 kW 25.0 kW

Power consumption 4.0 kW 4.8 kW 5.8 kW 8.0 kW 9.0 kWRated current max. 12.0 A 14.0 A 17.0 A 20.0 A 22.0 ARefrigerant R407CNo. of cooling circuits 1

Temperature range Environment +15°C to +43°CLiquid media +10°C to +25°C

Pump capacity See characteristic curveTank Made from PP plasticTank capacity 120 l 240 lWater connections 3/4˝ external thread 1˝ external threadWeight 250 kg 270 kg 380 kg 530 kg 560 kgColour RAL 7035Protection category (electrics) IP 54Air throughput of fans 6000 m3/h 8000 m3/hTemperature control Electronic control with digital display (factory setting +18°C)

Delivery times available on request. Special voltages, other frequencies, and technical modifications available on request. We reserve the right to make technical modifications.

Air/water heat exchangers From page 102 TS 8 lock systems Cat. 32, from page 947 TS 8 baying system Cat. 32, from page 138Overflow valve page 194 Cooling medium page 194

Rittal System Climate Control

Page 131: Erdinc  klima sk_broschuere_gb

Mini, for wall mounting, cooling output 1/2.5/4 kW

Recooling systems for water

T

H

BT

H

B

B = WidthT = Depth

Technical d● Compact

tion of the

olin

g sy

stem

s fo

r w

ater

esign: , modular configura- cooling compo-

nents with integral water tank. ● With RiNano coating ● Application-specific special

equipment available on request.

● Open system with tank.

Supply includes:Recooling system wired ready for connection, with multilingual documentation including func-tional diagram and wiring plans.

Approvals, see page 289.

Layout diagram, see page 264.

Characteristic curves of pump, see page 264.

Other options, see page 256.

Rec

o

Model No. SK 3360.100 3360.250 3360.470

Rated operating voltage V/Hz 400, 3~, 50/60/460, 3~, 601)

Dimensions in mmWHD

400 950 310

400 1580 290

500 1580 390

Cooling output at Tw = 10°C/Tu = 32°C Tw = 18°C/Tu = 32°C

0.8 W/0.9 kW1.0 kW/1.1 kW

2.1 kW/2.3 kW 2.5 kW/2.8 kW

3.3 kW/3.7 kW 4.0 kW/4.5 kW

Power consumption 0.7 kW/0.76 kW 1.55 kW/2.0 kW 1.85 kW/2.74 kWRated current max. 2.7 A/3.0 A 3.7 A/3.8 A 4.6 A/5.2 ARefrigerant R134aNo. of cooling circuits 1

Temperature rangeEnvironment +15°C to +43°CLiquid media +10°C to +25°C

Pump capacity See characteristic curveTank Plastic Tank capacity 5 l 10 l 15 lWater connections Quick-release coupling (counterpart included in accessory bag) 3/4˝ internal threadWeight 47 kg 78 kg 103 kgColour RAL 7035Protection category (electrics) IP 44Air throughput of fans 500 m3/h 710 m3/h 2000 m3/hTemperature control Microcontroller control (factory setting +18°C)

Accessories Packs of Page

Filter mat 1 3286.400 189 Metal filter mat 1 3286.410 190

1) Supports multiple voltages without rewiring. Special voltages and technical modifications available on request. We reserve the right to make technical modifications.

129Rittal System Climate Control

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194

Page 132: Erdinc  klima sk_broschuere_gb

Rec

oolin

g sy

stem

s fo

r oi

l

Recooling sIn floor-standing e

ystems for oilnclosure, cooling output 2.5 to 8 kW

T

H

B

B = WidthT = Depth

Te

chnical design: ● Robust industrial standard in

2 enclosure sizes.● Identical basic enclosure

for oil and water recooling systems.

● Variable air routing is possi-ble via the l/h or r/h side panel

● High-capacity gear pump.● Floating contact for collective

fault signal.● Integration of application-spe-

cific special equipment on request.

Supply includes:Recooling system wired ready for connection, with multilingual documentation including func-tional diagram and wiring plans.

Note:The illustration shows units with customer-specific options.

Accessories:

Metal filter mats and castors available on request.

Approvals, see page 290.

Layout diagram, see page 265.

Options, see page 256.

Model No. SK 3337.200 3337.300 3337.500 3337.600 3337.650

Rated operating voltage V/Hz 400, 3~, 50

Dimensions in mmWHD

485 965 650

595 1180 800

Cooling output with oil ISO VG 32 Toil = 20°CTu = 32°C

2.5 kW 3.4 kW 5.2 kW 6.7 kW 8.0 kW

Power consumption 1.4 kW 1.9 kW 3.0 kW 3.9 kW 4.9 kWRated current max. 3.1 A 3.5 A 5.0 A 7.0 A 7.8 ARefrigerant R134aNo. of cooling circuits 1

Temperature range Environment +15°C to +43°CLiquid media +15°C to +25°C

Pump capacity at 10 bar 10 l /min 24 l /minOptional tank Made from stainless steel 1.4301 (AISI 304) Optional tank capacity 33 l 57 lConnections 3/4˝ internal thread 1˝ internal threadWeight 103 kg 105 kg 148 kg 150 kg 154 kgColour RAL 7035Protection category (electrics) IP 54Air throughput of fans 1250 m3/h 1785 m3/h 3140 m3/hTemperature control Electronic control with digital display (factory setting +20°C)

Delivery times available on request. Special voltages, other frequencies, and technical modifications available on request. We reserve the right to make technical modifications.

130 Rittal System Climate Control

^goLayout diagram Page 265

Page 133: Erdinc  klima sk_broschuere_gb

In floor-standing enclosure, cooling output 11 to 26 kW

Recooling systems for oil

T

H

B

B = WidthT = Depth

Te

cool

ing

syst

ems

for

oil

chnical design: ● Robust industrial housing in

2 enclosure sizes.● Identical basic enclosure

for oil and water recooling systems.

● Variable air routing is possi-ble via the l/h or r/h side panel.

● Optimum accessibility for servicing purposes by remov-ing the side panel.

● High-capacity gear pump.● Floating contact for collective

fault signal.● Integration of application-

specific special equipment on request.

Supply includes:Recooling system wired ready for connection, with multilingual documentation including func-tional diagram and wiring plans.

Note:The illustration shows units with customer-specific options.

Accessories:

Metal filter mats and castors available on request.

Approvals, see page 290.

Layout diagram, see page 265.

Options, see page 256.

Re

Model No. SK 3337.700 3337.710 3337.720 3337.730 3337.740 3337.750

Rated operating voltage V/Hz 400, 3~, 50/460, 3~, 60

Dimensions in mmWHD

615 1178 1160

715 1178 1360

Cooling output with oil ISO VG 32 Toil = 20°CTu = 32°C

11 kW 15.5 kW 17.2 kW 19.0 kW 22.0 kW 26.0 kW

Power consumption 5.3 kW 6.4 kW 7.1 kW 8.7 kW 9.6 kW 10.5 kWRated current max. 12.0 A 15.0 A 16.0 A 19.0 A 21.0 A 22.0 ARefrigerant R407CNo. of cooling circuits 1

Temperature range Environment +15°C to +43°C1) Liquid media +15°C to +25°C

Pump capacity at 10 bar 45 l /min 68 l /minOptional tank Made from stainless steel 1.4301 (AISI 304)Optional tank capacity 60 l 100 lConnections 1˝ internal threadWeight 222 kg 232 kg 242 kg 248 kg 258 kg 268 kgColour RAL 7035Protection category (electrics) IP 54Air throughput of fans 6280 m3/h 10880 m3/hTemperature control Electronic control with digital display (factory setting +20°C)

1) SK 3337.720 and SK 3337.750 +15°C to +40°C.Delivery times available on request. Special voltages, other refrigerants, and technical modifications available on request. We reserve the right to make technical modifications.

131Rittal System Climate Control

Layout diagram Page 265

Page 134: Erdinc  klima sk_broschuere_gb

Imm

ersi

ble

reco

olin

g sy

stem

s fo

r oi

l/em

ulsi

on

Immersible recoolinCooling output 2.4 to 5.6 kW

g systems for oil/emulsion

T1 B1

H2

B2 T2

H1

B = WidthT = Depth

Ap

plication: Ideal for cooling contaminated cooling lubricants, such as drill-ing, cutting and grinding oils in machine tools. The units are placed on top of the oil or emul-sion tank and immersed in the fluid.

Technical design: ● For the cooling of oil/emulsion. ● Robust industrial standard. ● Flat evaporator coil insensi-

tive to dirt. ● Bi-frequency components

(50/60 Hz).

Supply includes:Immersible recooling system wired ready for connection, metal filter, eyebolts, with multilingual documentation, including functional diagram and wiring plans.

Approvals, see page 290.

Layout diagram, see page 265.

Options, see page 257.

Model No. SK for oil 3338.020 3338.040 3338.060 3338.080

Model No. SK for emulsion 3338.500 3338.520 3338.540 3338.560

Rated operating voltage V, Hz 400, 3~, 50/460, 3~, 60Cooling output at Toil/EM = 20°C/Tu = 32°C 2.4 kW/2.7 kW 3.2 kW/3.6 kW 4.6 kW/5.2 kW 5.6 kW/6.3 kW

Dimensions in mmB1H1T1

785 1650 785

Dimensions of immersible part, mm B2T2

719 719

Immersion depth mm H2 550Minimum media level with oil/emulsion mm 203/178 278/203

Power consumption Oil 1.6 kW/1.9 kW 1.8 kW/2.2 kW 2.4 kW/3.0 kW 2.6 kW/3.3 kWEmulsion 1.8 kW/2.1 kW 2.0 kW/2.5 kW 2.6 kW/3.2 kW 2.8 kW/3.6 kW

Rated current max. Oil 3.5 A/3.7 A 3.8 A/4.0 A 5.5 A/5.9 A 5.6 A/5.8 AEmulsion 3.8 A/4.0 A 4.1 A/4.3 A 5.9 A/6.3 A 6.0 A/6.3 A

Refrigerant R134aNumber of cooling circuits 1

Temperature range Environment +15°C to +42°CLiquid media +10°C to +25°C

Weight 133/130 kg 143/140 kg 158/155 kg 173/170 kgColour RAL 7035Protection category (electrics) IP 54Air throughput of fans 1500/1560 m3/h 2200/2350 m3/h

Temperature control Electronic controller with digital display; +10°C to +25°C adjustment range (factory setting +20°C)

Delivery times available on request. Special voltages available on request. Technical modifications reserved.

132 Rittal System Climate Control

Layout diagram Page 265

Page 135: Erdinc  klima sk_broschuere_gb

Immersible r

ecooling systems for oil/emulsionCooling output 8.5 to 17.3 kW

T1 B1

H2

B2 T2

H1

B = WidthT = Depth

Ap

stem

s fo

r oi

l/em

ulsi

on

plication: Ideal for cooling contaminated cooling lubricants, such as drill-ing, cutting and grinding oils in machine tools. The units are placed on top of the oil or emul-sion tank and immersed in the fluid.

Technical design: ● For the cooling of oil/emulsion. ● Robust industrial standard. ● Flat evaporator coil insensi-

tive to dirt. ● Bi-frequency components

(50/60 Hz).

Supply includes:Immersible recooling system wired ready for connection, metal filter, eyebolts, with multilingual documentation, including functional diagram and wiring plans.

Approvals, see page 290.

Layout diagram, see page 265.

Options, see page 257.

Imm

ersi

ble

reco

olin

g sy

Model No. SK for oil 3338.100 3338.120 3338.140 3338.160 3338.180 3338.200

Model No. SK for emulsion 3338.580 3338.600 3338.620 3338.640 3338.660 3338.680

Rated operating voltage V, Hz 400, 3~, 50/460, 3~, 60Cooling output at Toil/EM = 20°C/Tu = 32°C

8.5 kW/ 9.5 kW

10.5 kW/ 11.8 kW

12.0 kW/ 13.4 kW

13.6 kW/ 15.2 kW

15.3 kW/ 17.1 kW

17.3 kW/ 19.4 kW

Dimensions in mmB1H1T1

785 1650 785

Dimensions of immersible part, mm B2T2

719 719

Immersion depth mm H2 550Minimum media level with oil/emulsion mm 328/278 378/278 428/328

Power consumption Oil 4.6 kW/5.5 kW 5.0 kW/6.0 kW 5.6 kW/6.6 kW 6.1 kW/7.3 kW 6.7 kW/8.1 kW 7.5 kW/9.0 kWEmulsion 4.8 kW/5.7 kW 5.3 kW/6.3 kW 5.8 kW/6.8 kW 6.3 kW/7.6 kW 6.6 kW/8.5 kW 7.7 kW/9.3 kW

Rated current max. Oil 8.4 A/8.6 A 9.2 A/9.3 A 10.1 A/10.5 A 11.1 A/11.5 A 12.1 A/12.4 A 13.3 A/13.7 AEmulsion 8.5 A/9.0 A 9.6 A/9.9 A 10.6 A/11.2 A 11.5 A/12.0 A 12.5 A/13.2 A 13.7 A/14.1 A

Refrigerant R407CNumber of cooling circuits 1

Temperature range Environment +15°C to +42°CLiquid media +10°C to +25°C

Weight 183 kg 203 kg 228 kg 248 kg 253 kg 263 kgColour RAL 7035Protection category (electrics) IP 54Air throughput of fans 7200/7480 m3/h 7900/8480 m3/hTemperature control Electronic control with digital display (factory setting +20°C)

Delivery times available on request. Special voltages available on request. Technical modifications reserved.

133Rittal System Climate Control

Layout diagram Page 265

Page 136: Erdinc  klima sk_broschuere_gb

Immersible reCooling output 21 to

Imm

ersi

ble

reco

olin

g sy

stem

s fo

r oi

l/em

ulsi

on

cooling systems for oil/emulsion78 kW

T1

B1

H2

B2T2

H1

B = WidthT = Depth

Ap

plication: Ideal for cooling contaminated cooling lubricants, such as drill-ing, cutting and grinding oils in machine tools. The units are placed on top of the oil or emul-sion tank and immersed in the fluid.

Technical design: ● For the cooling of oil/emulsion. ● Robust industrial standard in

2 enclosure sizes. ● Flat evaporator coil insensi-

tive to dirt. ● Bi-frequency components

(50/60 Hz).

Supply includes:Immersible recooling system wired ready for connection, metal filter, eyebolts, with multilingual documentation, including functional diagram and wiring plans.

Approvals, see page 290/291.

Layout diagram, see page 265.

Options, see page 257.

Model No. SK for oil 3338.220 3338.240 3338.260 3338.280 3338.300 3338.320 3338.340 3338.360

Model No. SK for emulsion 3338.700 3338.720 3338.740 3338.760 3338.780 3338.800 3338.820 3338.840

Rated operating voltage V, Hz 400, 3~, 50/460, 3~, 60Cooling output at Toil/EM = 20°C/Tu = 32°C

21.0 kW/ 23.0 kW

31.0 kW/ 35.0 kW

35.0 kW/ 39.0 kW

46.0 kW/ 50.0 kW

49.0 kW/ 54.0 kW

61.0 kW/ 69.0 kW

73.0 kW/ 81.0 kW

78.0 kW/ 87.0 kW

Dimensions in mmB1H1T1

785 1650 1830

1830 1650 1830

Dimensions of immersible part, mm B2T2

719 1764

1764 1764

Immersion depth mm H2 550Minimum media level with oil/emulsion mm 378/278 428/328 378/278 428/278 428/328 428/378

Power consumption Oil 9.7 kW/

9.9 kW13.0 kW/ 16.2 kW

14.6 kW/ 18.2 kW

18.8 kW/ 22.6 kW

20.0 kW/ 24.1 kW

23.6 kW/ 28.5 kW

27.3 kW/ 32.9 kW

29.0 kW/ 34.9 kW

Emulsion 10.1 kW/12.6 kW

13.4 kW/16.7 kW

14.0 kW/18.7 kW

19.5 kW/23.5 kW

20.8 kW/25.0 kW

24.4 kW/29.5 kW

28.0 kW/33.9 kW

29.8 kW/35.9 kW

Rated current max. Oil 17.3 A/

17.8 A21.6 A/ 23.0 A

24.3 A/ 25.5 A

35.5 A/ 35.2 A

35.4 A/ 35.8 A

42.7 A/ 42.9 A

50.0 A/ 50.0 A

53.0 A/ 53.0 A

Emulsion 17.9 A/ 18.4 A

22.2 A/ 23.6 A

24.9 A/ 26.1 A

36.7 A/ 36.5 A

36.6 A/ 37.0 A

43.9 A/ 44.1 A

50.2 A/ 51.1 A

54.2 A/ 54.2 A

Refrigerant R407CNumber of cooling circuits 1

Temperature range Environment +15°C to +45°CLiquid media +10°C to +25°C

Weight 305 kg 380 kg 425 kg 435 kg 455 kgColour RAL 7035Protection category (electrics) IP 54Air throughput of fans 15000/15600 m3/h 30000/31200 m3/hTemperature control Electronic control with digital display (factory setting +20°C)

Delivery times available on request. Special voltages available on request. Technical modifications reserved.

134 Rittal System Climate Control

Layout diagram Page 265

Page 137: Erdinc  klima sk_broschuere_gb

Liquid cooling IT

CRAC systems from page 136

� � � � � � CRAC systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 – 118 kW. . . . . . . 138

Water-cooled

Refrigerant-cooled

With heater

Without heater

With humidifier

With heater and humidifier

Rittal System Clima

Aisle containment page 136

Aisle containment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139

g IT

+–

Liquid Cooling Package from page 136

� � � � LCP Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . up to 20 kW. . . . . . . 141� � LCP Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . up to 40 kW. . . . . . . 142� � LCP Extend. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 kW. . . . . . . 143

� � � � LCP Smart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . up to 20 kW. . . . . . . 144� � LCP Inline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . up to 30 kW. . . . . . . 145

+–

Liq

uid

co

olin

Scalable output

Standardised installation

Suitable for retrofitting

Low density

Mid density

High density

Chillers for IT cooling from page 146

� Chillers for IT cooling . . . . . . . . . . . . . . . . . . . . . . 15 to 123 kW. . . . . . . 148� Chillers for IT cooling . . . . . . . . . . . . . . . . . . . . . 145 to 462 kW. . . . . . . 149

W Ö E

Medium to be cooled: Water

Medium to be cooled: Oil

Medium to be cooled: Emulsion

W Ö E

Water/water heat exchangers from page 150

� Water/water heat exchangers . . . . . . . . . . . . . . . 25 to 250 kW. . . . . . . 153

E

Water-carrying parts

stainless steel (optional)E

Piping systems page

� Piping systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154

User-specific

135te Control

Page 138: Erdinc  klima sk_broschuere_gb

CR

AC

sys

tem

s, L

iqui

d C

oolin

g P

acka

ge

CRAC systems, Liquid Cooling Package

Modular climate control concepts – tailored to your

specific requirements! Rittal solves the problem of

climate control for high heat losses per rack with liquid

cooling components. Extremely high heat loads are

dissipated from the network enclosures and server

racks via air/water heat exchangers.

Additionally, this system allows data centres to be

extended in a temperature-neutral way.

136 Rittal System Climate Control

Page 139: Erdinc  klima sk_broschuere_gb

CRAC systemsPerfect solutions for cooling via a raised floor. Integral, scalable, and energy-efficient.

Rittal System Climate Control

AC

sys

tem

s, L

iqui

d C

oolin

g P

acka

ge

LCP Inline The LCP Inline is designed for siting within a bayed enclosure suite. The hot air is drawn in from the room or hot aisle at the rear of the device and expelled at the front into the cold aisle after cooling. The LCP Inline achieves maximum performance and efficiency in conjunction with Rittal aisle containment. With this product, a raised floor is not necessary.

LCP Smart/LCP Plus These units provide reliable climate control and precise server loads up to 30 kW.

CR

Benefits at a glance CRAC systems: ● An alternative to water and refrigerant● Energy-efficient EC fan system

LCP Plus: ● Complete unit with 30 kW useful cooling

output ● Touchscreen ● Basic CMC as standard

LCP Smart: ● Complete unit with 20 kW useful cooling

output ● Basic CMC as standard● Optional touchscreen

LCP Extend: ● Complete unit with 12 kW useful cooling

output● Independent unit; ideal for retrofitting to

racks while operational● Relieves the pressure on the room air-

conditioning system

LCP Inline: ● Complete unit with 30 kW useful cooling

output ● No raised-floor climate control is required

in the cold aisle

All LCPs come with networking capability as standard, thanks to the Basic CMC with integral graphic user interface.

Important● All enclosures are bayable with the corre-

sponding TS 8 racks.● To ensure proper use of LCP compo-

nents, the racks being cooled should be sealed against the ingress of ambient air wherever possible. For suitable accessories see page 187.

Tips and tricksApplications see page 140

Selection criteria see page 227

Assembly see page 228

137

Page 140: Erdinc  klima sk_broschuere_gb

CR

AC

sys

tem

s

CRAC systemsUseful cooling output 18 – 11

8 kW

BT

H

B = WidthT = Depth

Ap

plication and mode of operation: The CRAC system draws warm waste air from the top of your data centre, cools it using either water or refrigerant in a closed heat exchanger, and blows the cooled, filtered supply air into the raised floor with overpres-sure.

Benefits: ● The unit is available in a

broad output range, and for a variety of cooling media.

● The unit supports optimum integration of both hardware and software.

● Optimum energy and space efficiency thanks to intelligent design features, such as the slanted heat exchanger and base-integrated fan.

● Frame based on the popular TS 8 system.

Equipment: User-friendly, high-quality con-troller with an extensive range of functions and connectivity. Space-saving, readily accessi-ble, high-efficiency fan. Flow and energy-optimised special heat exchanger with a generous safety factor.

Colour:RAL 7035

Model No. SK Without heater 3301.620 3301.660 3301.830 3301.870 3300.510 3300.560 3300.710 3300.760

Model No. SK With heater 3301.630 3301.670 3301.840 3301.880 3300.520 3300.570 3300.720 3300.770

Model No. SK With humidifier 3301.640 3301.680 3301.850 3301.890 3300.530 3300.580 3300.730 3300.780

Model No. SK With heater and humidifier 3301.650 3301.690 3301.860 3301.990 3300.540 3300.590 3300.740 3300.790

Useful cooling output1) 23 kW 39 kW 78 kW 118 kW 18 kW 30 kW 43 kW 54 kW

Operating voltage V/Hz 400/50 400/50 400/50 400/50 400/50 400/50 400/50 400/50

Dimensions in mmWHD

1100 1950 650

1100 1950 850

1800 1950850

2600 1950 850

11001950850

11001950850

14001950850

18001950850

Cooling medium Water2) Refrigerant R407C2) Volumetric airflow at an external pressure loss of 20 Pa 6000 m3/h 11000 m3/h 22000 m3/h 33000 m3/h 6000 m3/h 8500 m3/h 12500 m3/h 16000 m3/h

No. of fans 1 1 2 3 1 1 1 2Power consumption of fans 0.6 kW 1.5 kW 3.0 kW 4.6 kW 0.6 kW 0.9 kW 1.8 kW 1.7 kWStart-up current of fans 1.8 A 4.6 A 9.2 A 13.8 A 1.8 A 4.6 A 4.6 A 9.2 AMax. speed 1150 rpm 1200 rpm 1200 rpm 1200 rpm 1150 rpm 1200 rpm 1200 rpm 1200 rpmNo. of compressors – 1 2 3 3Power consumption of compressors – 5 kW 8.8 kW 13.1 kW 15 kWStart-up current of compressors – 13.1 A 25.6 A 38.4 A 39.3 AType of connection Terminal strip –Weight 300 kg 360 kg 550 kg 770 kg 455 kg 505 kg 585 kg 935 kgNoise output 75 dB (A) 79 dB (A) 82 dB (A) 84 dB (A) 74 dB (A) 74 dB (A) 81 dB (A) 76 dB (A)Filter quality to DIN EN 779 G4 G4

1) Output figures less heat from the fans. CW: 26°C/45 % air inlet and 10°C/15°C water temperatures DX: 26°C/45 % air inlet and 50°C condensation temperature

2) Other media available on request. Other options available on request. We reserve the right to make technical modifications.

138 Rittal System Climate Control

Recooling systems From page 146

Page 141: Erdinc  klima sk_broschuere_gb

Aisle containment

1200

2000

600/800

Apop

Ais

le c

onta

inm

ent

plication and mode of eration:

Rittal aisle containment is a combination of door and roof components which facilitate consistent separation of the hot and cold air in the data centre. Such separation is elementary when it comes to saving energy and increasing the efficiency of the available climate control technology. It is the cold air that determines whether your equip-ment is at its best in the enclo-sures. With this in mind, Rittal has deliberately chosen to focus on this aspect, and to route cold air selectively to the equipment.

Benefits: ● Increased energy efficiency

and performance capability of climate control.

● Superior output density is facilitated, thanks to guaran-teed cold air supply.

● Easily installed and retrofit-ted, as it is fully compatible with the TS 8 enclosure system.

● An inexpensive way to boost the performance of your exist-ing plant, lengthening the investment cycle until a replacement needs to be pur-chased.

Equipment: Slimline door element with view-ing window. Stable roof components in a composite metal with a high level of light permeability. Where required, safety glass may also be used.

Note:Other size variants and individually modified systems available on request.

Model No. SK roof element 3300.170 3300.180 –

Model No. SK door element – – 3300.160

Width of element (identical to enclosure width), mm 600 800 –Width of cold aisle mm 1200 1200 1200Height of cold aisle mm – – 2000

139Rittal System Climate Control

LCP Extend From page 143

Page 142: Erdinc  klima sk_broschuere_gb

Liqu

id C

oolin

g P

acka

ge

Liquid Cooling PaApplications

140

ckage

Possible interfaces for

● Emergency water supply

● Free cooling

● Heat recovery

Water/water heat exchanger

IT chiller

Control Distribution

Efficient climate control concepts – tailored to your specific

requirements!

Rittal solves the problem of climate control for high heat

losses per rack with liquid cooling components. Extremely

high heat loads are dissipated from the enclosures, IT and

server racks via air/water heat exchangers. Additionally,

data centres may be extended in a temperature-neutral

manner, and cold aisles efficiently supplied with cold air.

LCP Standard

Bayable with TS 8 server racks As the height and depth are identical, it may be bayed either in the middle of an enclosure suite or at the end.

LCP Plus

Useful cooling output up to 40 kW Useful cooling outputs of 30 kW (rack height 2000 mm) or 40 kW (rack height 2400 mm) are achieved with 6 or 8 high-per-formance fans, which may be exchanged without the need for tools.

LCP Extend

Rittal System Climate Control

Installation while operationalAir/water heat exchanger (12 kW) to support climate control of the room.

LCP Smart

Maximum efficiency with EC fan technologyThe latest yardstick in the mid-range performance category. Highly efficient and compact.

LCP Inline

Targeted cooling of selected aislesWith a useful cooling output of up to 30 kW, aisles can be effi-ciently cooled in conjunction with aisle containment.

Page 143: Erdinc  klima sk_broschuere_gb

LCP Standard, useful cooling output up to 20 kW

Liquid Cooling Package

TB

H

B = WidthT = Depth

Ap

plication and mode of operation:Air/water heat exchanger, bayable with server racks based on TS 8 (H x D 2000 x 1000/1200 mm). The useful cooling output of max. 20 kW can be achieved by installing additional modules.

Benefits: ● The separation of cooling and

rack prevents water from pen-etrating the server rack.

● Increased assembly- and service-friendliness

● LCPs are easy to handle (max. 2 m) and may be trans-ported in lifts and through doors.

● The low weight means a mini-mal area load.

Approvals, see page 293.

Liqu

id C

oolin

g P

acka

ge

Model No. SK 3301.2301) 3301.420

Description LCP StandardRated operating voltage V/Hz 230, 50/60

Dimensions in mm WHD

30020001000

30020001200

Usable U 42Useful cooling output Up to 20 kW

Rated current 3.8 A/4.4 APre-fuse 10 A/10 ACooling medium Water (for specifications see Internet) Water inlet temperature +6°C to +20°CPermissible operating pressure p. max. 5 barProtection category to EN 60 529 IP 30 Duty cycle 100 % Electrical connection Connection cableWater connection 3/4˝ external thread Weight max. 160 kgColour RAL 7035Air throughput of fans 3000 m3/h

Temperature control4-way fan controlElectro-magnetic valve

Accessories Packs of PageAdd-on cover for height compensation with 2200 mm high racks 1 3301.221 3301.421 188

Special voltages and sizes available on request. We reserve the right to make technical modifications. 1) Also available with 115 V, Model No. 3301.210.

Accessories Page 186 IT chillers From page 146 Server racks Cat. 32, from page 774

Cooling moduleThe cooling module allows the useful cooling output of the LCP Standard to be increased in 6.6 kW increments. Model No. see page 186.

141Rittal System Climate Control

Page 144: Erdinc  klima sk_broschuere_gb

Liquid Cooling PaLCP Plus, useful cooling ou

Liqu

id C

oolin

g P

acka

ge

ckagetput up to 40 kW

TB

H

B = WidthT = Depth

Ap

plication and mode of operation:Air/water heat exchanger, bayable with server racks based on TS 8 (H x D 2000 x 1200 mm). Complete unit with 40 kW useful cooling output.

Benefits: ● The separation of cooling and

rack prevents water from pen-etrating the server rack.

● Increased assembly- and service-friendliness

● LCPs are easy to handle and may be transported in lifts and through doors.

● The low weight means a mini-mal area load.

Approvals, see page 293.

Model No. SK 3301.4801) on request

Description LCP Plus LCP Plus

Rated operating voltage V/Hz 230, 1~, 50/60 400, 3~, 50/60

230, 1~, 50/60 400, 3~, 50/60

Dimensions in mm WHD

30020001200

30024001200

Usable U 42 51Useful cooling output Up to 30 kW Up to 40 kW

Rated current 9.3 A/10.4 A

Technical specifications available on request.

Pre-fuse 16 A/16 A

Cooling medium Water (for specifications see Internet)

Water inlet temperature +6°C to +20°CPermissible operating pressure p. max. 5 barProtection category to EN 60 529 IP 30 Duty cycle 100 % Electrical connection Connection cableWater connection 1˝ external thread Weight 230 kgColour RAL 7035Air throughput of fans 5000 m3/h

Temperature control4-way fan controlTwo-way control valve

Accessories Packs of Page Add-on cover for height compensation with 2200 mm high racks 1 3301.421 188

Special voltages and sizes available on request. We reserve the right to make technical modifications. 1) Delivery times available on request.

142 Rittal System Climate Control

Accessories Page 186 IT chillers From page 146 Server racks Cat. 32, from page 774

Page 145: Erdinc  klima sk_broschuere_gb

LCP Extend, useful cooling output 12 kW

Liquid Cooling Package

H

BT

B = WidthT = Depth

Ap

plication and mode of operation:Air/water heat exchanger for retrofitting to racks while opera-tional.

The stand-alone unit replaces the rear door (for other brands on request).

Benefits: ● Mounted on the rear of

the server rack; eases the pressure on the room air-conditioning system.

● Water connection either at the bottom or top.

Approvals, see page 294.

Liqu

id C

oolin

g P

acka

ge

Model No. SK 3301.4901)

Description LCP Extend

Rated operating voltage V/Hz 230, 1~, 50/60 400, 3~, 50/60

Dimensions in mm WHD

5201910160

Usable U 42Useful cooling output 12 kW

Rated current 2.4 A/3.0 APre-fuse 6 A/6 ACooling medium Water (for specifications see Internet) Water inlet temperature +15°CPermissible operating pressure p. max. 5 barProtection category to EN 60 529 IP 20Duty cycle 100 % Electrical connection Connection cableWater connection 3/4˝ external thread Weight 130 kgColour RAL 7035Air throughput of fans 3000 m3/h Temperature control Fan control

Special voltages and sizes available on request. We reserve the right to make technical modifications. 1) Delivery times available on request.

143Rittal System Climate Control

Accessories Page 186 IT chillers From page 146 Server racks Cat. 32, from page 774

Page 146: Erdinc  klima sk_broschuere_gb

LiquidLCP Smar

Liqu

id C

oolin

g P

acka

ge

Cooling Packaget, useful cooling output up to 20 kW

TB

H

B = WidthT = Depth

Apop

plication and mode of eration:

The LCP Smart draws in the air at the sides of the server enclo-sure rear, cools it using high-performance compact registers, and blasts the cooled air back into the front part of the server enclosure at the sides.

Maximum efficiency is achieved, thanks to the use of EC fans. The heat exchanger of the LCP Smart supports the longest possible usage of free cooling.

Benefits: ● High energy efficiency. ● Bayable with server/network

enclosures based on TS 8 (H 2000, D 1000).

● Fans may be individually exchanged with the system operational, self-contacting.

● Basic CMC as standard. ● Touchscreen display may be

retrofitted. ● Shorter servicing times.

● Extended functionality of the monitoring and control tech-nology/software.

● Optimum adaptability thanks to dynamic, continuous con-trol of the cold water volume flow.

● Control of the inlet air temper-ature and the temperature dif-ference for the best possible supply to your server systems.

Model No. SK 3301.460

Number of preassembled cooling modules 1

Rated operating voltage V/Hz 200 – 230, 1~, 50/60 400, 3~, 50/60

Dimensions in mmWHD

30020001000

Usable U 42 Useful cooling output Up to 20 kW

Pre-fuse 10 APower consumption Pel max. 600 WCooling medium WaterPermissible operating pressure p. max. 5 barDuty cycle 100 %Electrical connection Connection cable Water connection 1˝ external threadWeight 230 kgColour RAL 7035Temperature control Via integral controllerMax. air throughput 3000 m3/h

Touchscreen display for LCP Smart, Model No. see page 186.

Accessories Page 186 IT chillers From page 146 Server racks Cat. 32, from page 774

144 Rittal System Climate Control

Page 147: Erdinc  klima sk_broschuere_gb

LCP Inline, useful cooling output up to 30 kW

Liquid Cooling Package

kage

T1B

H

B = WidthT = Depth

Applicatiooperation:The LCP Insiting withinsuite. The hfrom the rothe rear of expelled foaisle, wherIT equipmeThe LCP Inmum perfociency in ccold aisle cproduct, a necessary.

ac

n and mode of line is designed for a bayed enclosure ot air is extracted

om or warm aisle at the unit, cooled, then rwards into the cold e it is available to your nt. line achieves maxi-rmance and effi-onjunction with Rittal ontainment. With this raised floor is not

Equipment: High-performance heat exchanger with very even temperature distribution. Integrated condensate management. Controller with networking capa-bility, compatible with all com-mon communication standards (SNMP, BACnet etc.).

Benefits: ● Combines the slimline design

of the LCP with the function of room air-conditioning.

● Climate control technology, specially designed for IT envi-ronments with comprehensive monitoring functions.

● Frame based on the popular TS 8 system.

Liqu

id C

oolin

g P

Model No. SK 3301.470

Rated operating voltage V/Hz 230, 1~, 50/60 400, 3~, 50/60

Dimensions in mmBH

T1

30020001200

Usable U 42 Useful cooling output Up to 30 kW

Rated current 9.3 A/10.4 APre-fuse 16 A/16 ACooling medium Water1) Permissible operating pressure p. max. 5 barDuty cycle 100 % Electrical connection Connection cable Water connection 1˝ external thread Weight 230 kgColour RAL 7035 Temperature control Via integral controller Max. air throughput 4600/4300 m3/h

1) Water quality according to unit specifications.

Front cover

145Rittal System Climate Control

The optional front cover reduces the air outlet speed, thereby minimising draught effects. Model No. see page 186.

Accessories Page 186 IT chillers From page 146 Server racks Cat. 32, from page 774 Aisle containment Page 139

Page 148: Erdinc  klima sk_broschuere_gb

Chi

llers

for

IT c

oolin

g

Chillers for IT cooling

IT chillers in conjunction with free cooling, for example,

ensure efficient cooling and supply of the cooling

medium. Specially designed for supplying critical IT

applications cooled via LCP, air/water heat exchangers

or CRAC systems.

Safety-relevant options such as redundant pumps,

emergency cooling or buffer stores are the distinguish-

ing features of these atmospherically sealed systems.

146 Rittal System Climate Control

Page 149: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Chi

llers

for

IT c

oolin

g

SafetyChillers are particularly well-suited for cooling IT applications, such as LCP or air/water heat exchangers. Redundant pumps and optional special equipment for emergency cooling or thermal recovery are the distinguishing features of these systems.

Piping systemThe Rittal piping system provides the link between the equipment and the refrigera-tion system.

Energy-saving free cooling chillersCold ambient air is used for cooling. If the ambient temperature is too high, the chiller will cut in. Free cooling systems are particu-larly energy-saving. The operating costs may be cut by up to 80 %. The service life of components is extended, and operational reliability is increased. The waste heat pro-duced may be effectively used for heating and hot water supply in facility management.

Energy savings

of up to 80 %

Benefits at a glanceCooling output from 15 to 462 kW● A system for cooling server racks and

IT applications● Compact structure with control

components in the front and air intake via both sides

● Individual project management● Commissioning and servicing● Comprehensive pipeline calculation● Global service network

Tips and tricksApplications see page 226

Selection criteria see page 227

Assembly see page 228

Notes see page 229

147

Page 150: Erdinc  klima sk_broschuere_gb

Chi

llers

for

IT c

oolin

g

Chillers for IT Cooling output 15 to 1

cooling23 kW

T

H

B

B = WidthT = Depth

Ap

plication: Especially for cooling IT applica-tions, such as LCP or air/water heat exchangers. Safety-rele-vant features such as redundant speed-controlled pumps, com-pressors or buffer stores are the distinguishing features of these atmospherically sealed systems.

Technical design: ● Compact design with control

components in the front and air intake via both side pan-els, air outlet upwards.

● Pressure-sealed system. ● Digital thermostat for tempera-

ture control with setpoint and actual value display.

● Monitoring interface with Rittal CMC-TC supported.

● Integral automatic bypass valve.

● Flow monitor.

Supply includes:Chiller wired ready for connection, with multilingual documentation including functional diagram and wiring plans.

Options: ● Free cooling may be inte-

grated from 61 kW. Please follow the instructions!

● Buffer store for separate siting ● Emergency cooling with

mains water infeed ● Special voltages

Note:The illustration shows a unit with customer-specific options. Technical deviations in terms of cooling output, dimensions or weight are possible for unit types with free cooling.

Layout diagram, see page 266.

Model No. SK 3232.700 3232.710 3232.720 3232.730 3232.740 3232.750 3232.760 3232.770 3232.780 3232.790

Rated operating voltage V/Hz 400, 3~, 50

Dimensions in mmWHD

8151400 1560

8151400 1560

8151400 1560

100021802000

110016062450

110016062450

110016062450

110016062950

110018752950

110018752950

Cooling output at Tw = 15°C/Tu = 35°C 15 kW 24 kW 36 kW 48 kW 61 kW 72 kW 82 kW 92 kW 113 kW 123 kW

Power consumption 6900 W 9700 W 14600 W 21000 W 21400 W 24400 W 27500 W 31100 W 38900 W 42600 WRated current max. 23.0 A 25.0 A 37.0 A 46.5 A 71.2 A 74.2 A 77.2 A 83.2 A 106.1 A 112.1 ARefrigerant R407CPmax. cooling circuit 28 bar

Temperature rangeEnvironment –20°C to +43°CLiquid media +5°C to +15°C

Pump capacity 60 l/min. 120 l/min. 240 l/min. 500 l/min. Pump pressure 2.5 barNumber of cooling circuits 1 2Tank with 10 mm condensate insulation SteelTank capacity 48 l 100 l 300 l 500 lWater connections 1˝ 1 1/4˝ 2 ˝ 2 1/2˝ Operating weight 375 kg 390 kg 480 kg 710 kg 810 kg 849 kg 864 kg 949 kg 1150 kg 1175 kgColour RAL 7035 RAL 9002Protection category (electrics) IP 54Air throughput of fans m3/h 10880 14000 18000 13720 20450 27300 35000

Temperature control Electronic control with digital display (factory setting +15°C) Delivery times available on request. We reserve the right to make technical modifications. Cooling output makes allowance for 35 % glycol.

148 Rittal System Climate Control

Accessories Page 181

Page 151: Erdinc  klima sk_broschuere_gb

Chillers for IT coolingCooling output 145 to 462 kW

T

H

B

B = WidthT = Depth

Appl

r IT

coo

ling

ication: Especially for cooling IT applica-tions, such as LCP or air/water heat exchangers. Safety-rele-vant features such as redundant speed-controlled pumps, com-pressors or buffer stores are the distinguishing features of these atmospherically sealed systems.

Technical design: ● Compact design with control

components in the front and air intake via both side pan-els, air outlet upwards.

● Pressure-sealed system. ● Digital thermostat for tempera-

ture control with setpoint and actual value display.

● Monitoring interface with Rittal CMC-TC supported.

● Integral automatic bypass valve.

● Flow monitor.

Supply includes:Chiller wired ready for connection, with multilingual documentation including functional diagram and wiring plans.

Options: ● Free cooling may be inte-

grated from 61 kW. Please follow the instructions!

● Buffer store for separate siting ● Emergency cooling with

mains water infeed ● Special voltages

Note:The illustration shows a customised unit design up to 180 kW. Technical deviations in terms of cooling output, dimensions or weight are possible for unit types with free cooling.

Layout diagram, see page 266.

Chi

llers

fo

Model No. SK 3232.800 3232.810 3232.820 3232.830 3232.840 3232.850 3232.860 3232.870 3232.880

Rated operating voltage V/Hz 400, 3~, 50

Dimensions mmWHD

110018752950

110018752950

110018753950

220024503400

220024503400

220024503400

220024504250

220024504250

220024504250

Cooling output at Tw = 15°C/Tu = 35°C 145 kW 161 kW 193 kW 248 kW 280 kW 312 kW 372 kW 415 kW 462 kW

Power consumption 50900 W 57600 W 63700 W 89100 W 97300 W 105400 W 138000 W 148200 W 158400 WRated current max. 141 A 146 A 153 A 208 A 227 A 245 A 311 A 339 A 366 ARefrigerant R407CPmax. cooling circuit 28 bar

Temperature rangeEnvironment –20°C to +43°CLiquid media +5°C to +15°C

Pump capacity 500 l/min. 810 l/min. 1200 l/min. Pump pressure 2.5 barNumber of cooling circuits 2Tank with 10 mm condensate insulation SteelTank capacity 500 l 700 l 1000 lWater connections 2 1/2˝ 3˝ 4˝ Operating weight 1250 kg 1340 kg 1520 kg 2702 kg 2795 kg 2831 kg 3460 kg 3567 kg 3667 kgColour RAL 9002Protection category (electrics) IP 54Air throughput of fans m3/h 35500 60900 86000 76000 111000

Temperature control Electronic control with digital display (factory setting +15°C) Delivery times available on request. We reserve the right to make technical modifications. Cooling output makes allowance for 35 % glycol.

149Rittal System Climate Control

Accessories Page 181

Page 152: Erdinc  klima sk_broschuere_gb

Wat

er/w

ater

hea

t exc

hang

ers

Water/water heat exchangers

Water/water heat exchangers allow existing water

circuits within the company to be used, even if they

are not suitable for direct enclosure climate control,

such as water circuits with cooling tower, process or

well water, or aggressive or contaminated water.

150 Rittal System Climate Control

Page 153: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

ter/

wat

er h

eat e

xcha

nger

s

Interrogate operating statusesand make settings via the Web (TCP/IP).

RedundancyDouble pump, speed-controlled, with alter-nating 24 h operation.

Stainless steel pipeworkFor added safety (optional).

Wa

Benefits at a glance● Redundancy thanks to double pump unit

fitted with linear speed control● Linear controlled 3-way valve (4 – 20 mA) ● Floating contact for collective fault signal● Flow rate display and monitoring● Digital controller● Water connection in base● Integrated into a TS 8 enclosure● Compact construction mounted in a

tubular frame

ImportantThe pipework may also be supplied in stainless steel (1.4401).

151

Page 154: Erdinc  klima sk_broschuere_gb

Water/water heat exchangersLayout diagram

152

Wat

er/w

ater

hea

t exc

hang

ers

1

2

3

5

Ritt

7

4

8

al System Climate C

6

9

10

All climate control solutions from a single source:

Rittal aisle containment

CRAC systems

LCP Standard/Plus/Smart

+ Water/water heat exchangers

IT chiller

Double pump unit

Heat recovery

Buffer store

Emergency water supply

1

2

3

4 8

5

6

7

9

10

ontrol

Page 155: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Cooling output 25 to 250 kW

Water/water heat exchangers

H

T

B

B = WidthT = Depth

Ap

chan

gers

plication: Water/water heat exchangers are primarily used to hydrauli-cally and physically separate a definable primary water circuit (dirt, pressure fluctuations) from a defined secondary water cir-cuit.

Technical design: ● Compact construction

mounted in a tubular frame● Integrated in a TS 8 enclosure● Digital controller ● Floating contact for collective

fault signal● Flow rate display and

monitoring● Water connection in base● Double pump unit fitted with

linear speed controller● Linear controlled 3-way valve

(4 – 20 mA)

Supply includes:Water/water heat exchanger wired ready for connection, with multilingual documentation including functional diagram and wiring plans.

Note:The illustration shows units with customer-specific options.

Accessories:

● Buffer store 1000 – 3000 l ● Standard pump with

automatic bypass ● Emergency water infeed ● Secondary flow monitor ● Ethernet, BACnet and

SNMP link ● Magnetic filter ● Pipework in stainless steel

1.4401 (AISI 316) ● Tubular frame,

without TS 8 enclosure

Layout diagram, see page 267.

Wat

er/w

ater

hea

t ex

Model No. SK 3232.900 3232.910 3232.920 3232.930 3232.940 3232.950 3232.960

Rated operating voltage V/Hz 400, 3~, 50

Dimensions incl. base/plinth in mm

WHD

1200 1900 800

1200 1900 800

1200 1900 800

1600 1900 800

1600 1900 800

2000 1900 800

2000 1900 800

Cooling output at Twp = 6°C/Tws = 15°C 25 kW 50 kW 75 kW 100 kW 150 kW 200 kW 250 kW

Power consumption 3.54 kW 5.7 kW 5.7 kW 10.4 kW 10.4 kW 13.6 kW 13.6 kWRated current max. 3.5 A 5.9 A 5.9 A 10.2 A 10.2 A 10.8 A 10.8 A

Temperature range Environment +5°C to +45°CTp primary side +6°C to +30°CTs secondary side +6°C to +30°C

Pump capacity (l/min.) primary/secondary 62 125 187 250 375 500 625

Pump pressure (bar)primary 1.5 – 6.0secondary (equipment) 2.5

Water connections primary/secondary RP 1˝ RP 1 1/4˝ RP 1 1/2˝ RP 2˝ RP 2˝ RP 2 1/2˝ RP 2 1/2˝ Weight 400 kg 450 kg 450 kg 700 kg 700 kg 900 kg 900 kgColour RAL 7035Protection category (electrics) IP 54Temperature control Electronic controller with digital display; +5°C to +50°C adjustment range

Delivery times available on request. Special voltages, other frequencies, and technical modifications available on request.

Air/water heat exchangers From page 102 TS 8 lock systems Cat. 32, from page 947 TS 8 baying system Cat. 32, from page 138Overflow valve Page 194 Cooling medium Page 194

153

Page 156: Erdinc  klima sk_broschuere_gb

Pip

ing

syst

ems

in th

e da

ta c

entr

e

Piping systems in

the data centre

Efficient cooling solutions rely on an excellent infra-

structure. The Rittal piping system provides the link

between the equipment and the refrigeration system.

An optimum design and targeted media supply ensure

efficient operation of all cooling components. This also

includes safety-relevant options such as redundant

pumps, emergency cooling or buffer stores.

Rittal System Climate Control

154

Speed-controlled pumps are used to convey the coolant. The pumped volume may be varied by using state-of-the-art EC motors.

Your practical benefit: Lower energy consumption thanks to “cold water on demand”. Only the volume of water that is actually needed for cooling is moved through the system.

The standard hydraulic layout includes the use of a hydraulic separating filter. Different volumes of water on the producer side and equipment side for process cooling do not adversely affect the function of the cooling sys-tems.

Your practical benefit: Less energy consumption thanks to the use of free-cooling heat exchangers including redun-dancy.Chiller pumps may be switched on and off as required.

Use of compact distributors to distrib-ute the cooling medium among differ-ent pieces of equipment.

Your practical benefit: Redundancies in the supply lines to the equipment may be designed as required. For example, a layout can be designed to facilitate the auto-matic shut off of sub-sections in the event of pipe leaks.

Page 157: Erdinc  klima sk_broschuere_gb

Piping systems in the data centre

● Pipeline systems are part of a turnkey solution for the targeted cooling of IT operating environments

● Media network for the connection of coolers (IT chillers) and cooling equipment (liquid cooling package and CRAC systems)

● Free scalability of chiller and equipment output via the hydraulic separation of the producer and equipment sides

● Use of a hydraulic separating filter with dual function as a buffer store

● Maximum energy efficiency thanks to the use of polypropylene piping with exceptionally low pipe friction losses

● Systems are suitable for the use of cold water and water/antifreeze mixtures (glycol)

● Media pumping redundancy by fitting every chiller with its own primary pump and via the use of redundant main pumps on the equipment side

155

Pip

ing

syst

ems

in th

e da

ta c

entr

e1 2

4

3

7

5 6

Rittal System Climate Control

The innovative polypropylene piping is distinguished by minimal pipe friction resistance.

Your practical benefit: Less energy consumption for conveying the cooling medium, thanks to lower flow resistance. The material is corrosion-resistant and may be machined without residues.

Direct cooling systems (e.g. LCP)

CRAC systems

IT chiller

Buffer store

1

2

3

4

Dirt collector station with maintenance bypass

Main pump (redundant)

Compact distributor with lockable outlets

5

6

7

Page 158: Erdinc  klima sk_broschuere_gb

156

Page 159: Erdinc  klima sk_broschuere_gb

Outdoor climate control

Ou

tdo

or

clim

ate

con

tro

l

Cooling units for CS modular enclosures from page 158

� � � � for roof-mounted type 1 . . . . . . . . . . . . . . . . . . . . . . . . . . 900 W. . . . . . . 160� � � for door-mounted type 2. . . . . . . . . . . . . . . . . . . . . . . . . . 900 W. . . . . . . 160� � � for wall-mounted type 3 . . . . . . . . . . . . . . . . . 900/1400/2500 W. . . . . . . 160� � � � for universal installation type 4 . . . . . . . . . . . . . . . . . . . . 1500 W. . . . . . . 160

Heat exchangers for CS modular enclosures from page 158

� � � for roof-mounted type 1 . . . . . . . . . . . . . . . . . . . . . . . . . 30 W/K. . . . . . . 161� � � � for roof-mounted type 2 . . . . . . . . . . . . . . . . . . . . . . . . . 60 W/K. . . . . . . 161� � � for wall-mounted type 3 . . . . . . . . . . . . . . . . . . . . . . . . . 60 W/K. . . . . . . 161� � � for door-mounted type 4. . . . . . . . . . . . . . . . . . . . . . .40/60 W/K. . . . . . . 162� � � for door-mounted type 5. . . . . . . . . . . . . . . . . . . . . .85/120 W/K. . . . . . . 162

Climate control units for Toptec CR from page 158

� � � Heat exchangers . . . . . . . . . . . . . . . . . . . . . . . . . . .85/105 W/K. . . . . . . 163� � � � Cooling units . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000/1600 W. . . . . . . 163

Ex-proof climate control systems page

Ex overpressure enclosure with integral enclosure cooling unit . . . . . . . 164

Integral heater

Protection category IP 55

Aluminium

Roof-mounted

Wall-mounted

Rittal System Clima

157te Control
Page 160: Erdinc  klima sk_broschuere_gb

Out

door

clim

ate

cont

rol

Outdoor climate control

Rittal Communication Systems offer everything you

need to protect your electronic equipment, from

weather-tested enclosure solutions, to a variety of

climate control components, through to complete

security management systems. Cooling units, heat

exchangers, fans and heaters especially designed for

outdoor use ensure constant interior temperatures. A

protection category of IP 55 is retained for the system

as a whole when using Outdoor heat exchangers and

cooling units.

158 Rittal System Climate Control

Page 161: Erdinc  klima sk_broschuere_gb

FlexibilityClimate control modules in varying output categories may be posi-tioned on the door, rear panel, side panel or roof of the modular enclo-sure.Suitable for use within the tem-perature range –33°C to +55°C (cooling units) and +65°C (heat exchangers). Many units feature an integral heater.

Rittal System Climate Control

te c

ontr

ol

Standardised installationThe full 25 mm double wall takes care of heat exchange and minimises the influence of sunlight, featuring an active climate con-trol concept with fixed cut-out sizes and a mounting frame for depth-variable position-ing of the climate control unit. Depending on the local conditions at the installation site, either a heat exchanger or a cooling unit may be used.

Heat exchanger/cooling unitWith three mounting positions for internal mounting, partial internal mounting or exter-nal mounting plus a choice between cooling via the front or rear door of the Toptec CR.

Out

door

clim

a

Benefits at a glance● The IP 55 protection category of the

enclosures is retained.● Hermetically separate air circuits –

Pollutant-laden ambient air is unable to penetrate the enclosure

● Backup-compatible 48 V DC air/air heat exchangers

● Integral heater in many units

Important● CS Outdoor cooling units and CS Out-

door heat exchangers are manufactured to order.

● CS Outdoor cooling units and CS Out-door heat exchangers are supplied as fully integrated units on the CS Outdoor enclosure. Mounting on other Rittal enclosures is only possible by arrange-ment.

159

Page 162: Erdinc  klima sk_broschuere_gb

CS

Out

door

clim

ate

cont

rol

CS Outdoor climatCooling units for CS modular

e control enclosures

Type 1 for roof m

ountingWith microcontroller and 400 watt heater as standard.

Mounting frame:Required for CS 9764.012.

Type 2 for door mountingWith microcontroller and 400 watt heater as standard.

Type 3 for wall mountingWith microcontroller and 400 watt heater as standard. Alternative mounting on the rear or side panels is also possible. The picture shows the cooling unit with designer cover (not included in the supply).

Type 4 for universal installationWith microcontroller and 800 watt heater as standard.

Installation options: ● in the door or rear panel● in the side panel

Model No. CS 9762.012 9768.100 9761.012 9761.032 9761.042 9768.150 Page

Internal mounting Type 1 Roof-mounted

Type 2 Door-mounted

Type 3 Wall-mounted

Type 4 Universal

Rated operating voltage AC 230 V, 50/60 Hz

Unit dimensions (mm)WHD

535 390 400

430 1070 210

515 1170 151.5

695 1132 151.5

776 1100 250

400 1050 310

Minimum enclosure dimensions (mm)

W x H/D x H – 600 x 1200 600 x 1200 800 x 1200 800 x 1200 600 x 1200W x D 600 x 500 – – – – –

Useful cooling output EN 814

L35 L35L35 L50

900 W750 W

900 W650 W

900 W750 W

1400 W1050 W

2500 W2000 W

1500 W1250 W

Heater 400 W 400 W 400 W 400 W 400 W 800 W

Rated current max. 4.0 A 4.0 A 3.5 A 5.5 A 10.0 A 5.8 AStart-up current max. 10.7 A 11.6 A 10.8 A 15.5 A 32.0 A 19.0 A

Power consumption L35 L35L35 L50

460 W520 W

470 W530 W

450 W520 W

900 W1000 W

1450 W1650 W

940 W1045 W

Coolant R134ap. max. 26 bar 28 bar 24 bar 24 bar 28 bar 28 barTemperature range –33°C to +55°CAir throughput of fans– unimpeded air flow

Internal circuit fan External circuit fan

570 m3/h 570 m3/h

580 m3/h 430 m3/h

880 m3/h 880 m3/h

850 m3/h 880 m3/h

1450 m3/h 1450 m3/h

850 m3/h 680 m3/h

Temperature control Microcontroller1) Type of connection Plug panelWeight 29 kg 31 kg 45 kg 48 kg 52 kg 40 kgProtection category to EN 60 529/IEC 529 IP 55 (internal circuit to external circuit)Material (enclosure) Aluminium Sheet steel AluminiumSurface finish Spray finished in RAL 7035CE Declaration of Conformity � � � � � � Accessories

Cable connection kit 9765.105 9765.105 9765.105 9765.105 9765.105 9765.105 180 Mounting frame 9765.051 – – – – – –

1) With temperature-controlled activation of the components (internal/external circuit, heater). Setpoints are preset. Modifications can only be made by arrangement.

Delivery times available on request.

Cooling units for modular enclosures are manufactured to order. The units are assembled and supplied connected to the modular enclosure. Adaptations to other enclosure platforms are available on request.

CS modular enclosures Cat. 32, page 874 Test adaptor Page 180 Heaters Page 169

160 Rittal System Climate Control

Page 163: Erdinc  klima sk_broschuere_gb

Heat exchan

CS Out

gers for CS modular enclosures

door climate control

Type 1 for

roof mounting Without microcontroller, without heater.

Type 2 for roof mounting With microcontroller and heater as standard.

Mounting frame: Required for CS 9764.012.

Type 3 for wall mounting With microcontroller and heater as standard. For external mount-ing on side or rear panels. The picture shows the heat exchanger with designer cover (not included in the supply).

Property rights for Type 1 and 2: German patent no. 196 09 796

CS

Out

door

clim

ate

cont

rol

Model No. CS 9764.040 9764.012 9763.012 Page

Internal mounting Type 1 Roof-mounted

Type 2 Roof-mounted

Type 3 Wall-mounted

Rated operating voltage DC (fan/ microcontroller) 48 V

AC (heater) – 230 V, 50/60 Hz

Unit dimensions (mm)WHD

470 158 380

535 390 400

515 1170 151.5

Minimum enclosure dimensions (mm)

W x H/D x H – – 600 x 1200W x D 600 x 500 600 x 500 –

Specific thermal output 30 W/K 60 W/K 60 W/K

Heater – 400 W 400 W

Rated current max.

DC (fan/ microcontroller) 1.3 A 3.1 A 3.2 A

AC (heater) – 1.9 A 1.9 ATemperature range –33°C to +65°CAir throughput of fans– unimpeded air flow

internal/ external circuit fan 345 m3/h 830 m3/h 830 m3/h

Temperature control without1) Microcontroller2)

Type of connection Plug panelWeight 7 kg 17 kg 31 kgProtection category to EN 60 529/IEC 529 IP 55 (internal circuit to external circuit)Material (enclosure) Aluminium Sheet steelSurface finish Spray finished in RAL 7035CE Declaration of Conformity � � � UL/CUL – � � Accessories

Cable connection kit 9765.110 9765.110 9765.110 180 Thermostat 3110.000 – – 178 Mounting frame – 9765.051 – –

1) Customers may fit their own temperature control (SK 3110.000). 2) With temperature-controlled activation of the components (internal/external circuit, heater).

Setpoints are preset. Modifications can only be made by arrangement.

Delivery times available on request.

Heat exchangers for modular enclosures are manufactured to order. The units are assembled and supplied connected to the modular enclosure. Adaptations to other enclosure platforms are available on request.

161Rittal System Climate Control

CS modular enclosures Cat. 32, page 874 Test adaptor Page 180 Heaters Page 169

Page 164: Erdinc  klima sk_broschuere_gb

CS OutdHeat exchang

CS

Out

door

clim

ate

cont

rol

oor climate controlers for CS modular enclosures

Type 4

for door mountingWith microcontroller and 400 watt heater as standard.

Type 5 for door mountingWith microcontroller and heater as standard.

Model No. CS 9768.032 9768.012 9768.042 9768.062 Page

Internal mounting Type 4 Door-mounted

Type 5 Door-mounted

Rated operating voltage DC (fan/ microcontroller) 48 V

AC (heater) 230 V, 50/60 Hz –

Unit dimensions (mm)WHD

480 1005 110

510 1005 150

445 1050 150

575 1050 195

Minimum enclosure dimensions (mm)

WH

600 1200

650 1200

650 1300

800 1300

Specific thermal output 40 W/K 60 W/K 85 W/K 120 W/K

Heater 400 W –

Rated current max.

DC (fan/ microcontroller) 2.0 A 3.2 A 6.4 A 7.9 A

AC (heater) 1.9 A –Temperature range –33°C to +65°CAir throughput of fans– unimpeded air flow

internal/ external circuit fan 515 m3/h 530 m3/h 1020 m3/h

Temperature control Microcontroller1)

Type of connection Plug panel Sub-D connector 13W32)

Weight 13 kg 15 kg 28 kg 32 kgProtection category to EN 60 529/IEC 529 IP 55 (internal circuit to external circuit)Material (enclosure) AluminiumSurface finish Spray finished in RAL 7035CE Declaration of Conformity � � � � UL/CUL � � � � Accessories

Cable connection kit 9765.110 9765.110 9765.115 – 180 1) With temperature-controlled activation of the components (internal/external circuit, heater).

Setpoints are preset. Modifications can only be made by arrangement. 2) Special connection cable included in the supply.

Delivery times available on request.

Heat exchangers for modular enclosures are manufactured to order. The units are assembled and supplied connected to the modular enclosure. Adaptations to other enclosure platforms are available on request.

162 Rittal System Climate Control

CS modular enclosures Cat. 32, page 874 Test adaptor Page 180 Heaters Page 169

Page 165: Erdinc  klima sk_broschuere_gb

2

Clima

CS Outdo

B2

H2

T1

B1

H1

B = WidthT = Depth

te control units for Toptec CR

or climate control

1

Heat e1

xchanger/cooling unit With three mounting positions for internal mounting, partial internal mounting or external mounting plus a choice between cooling via front or rear door.

Heat exchanger/cooling unit, built into the Toptec CR.

2

CS

Out

door

clim

ate

cont

rol

Heat exchangers Cooling units PageModel No. CS 9776.100 9776.150 9776.500 9776.550

Internal mounting Universal Universal

Rated operating voltageDC 48 V –AC – 230 V, 50/60 Hz

Unit dimensions (mm)B1H1T1

500 1000 150

500 1000 200

500 1000 150

500 1000 260

Minimum enclosure dimensions (mm) W x H 800 x 1200 800 x 1200Specific thermal output 85 W/K 105 W/K – –

Useful cooling output EN 814

L35 L35L35 L50 – – 1000 W/1180 W

650 W/700 W 1600 W/1750 W1200 W/1250 W

Heater – – 400 W

Rated current max.

DC 4.2 A 4.5 A – –AC – 5.0 A/5.0 A 6.0 A/6.8 A

Start-up current max. – 24.0 A/22.0 A 34.0 A/32.0 A

Power consumption L35 L35L35 L50 – 640 W/760 W

780 W/920 W960 W/1170 W1125 W/1310 W

Coolant – R134ap. max. – 28 bar 28 barTemperature range –33°C to +65°C –33°C to +55°CAir throughput of fans– unimpeded air flow

internal/external circuit fan 530 m3/h 1130 m3/h 600/625 m3/h

600/625 m3/h880/950 m3/h1000/1090 m3/h

Temperature control Microcontroller1) Microcontroller2) Type of connection Plug panel Female multi-point connector 9-poleWeight 22 kg 30 kg 35 kg 45 kgProtection category to EN 60 529/IEC 529 IP 55 (internal circuit to external circuit)Material (enclosure) AluminiumSurface finish Spray finished in RAL 7035CE Declaration of Conformity � � � � Accessories

Cable connection kit 9765.115 – – – 180 1) With temperature-controlled activation of the components (internal/external circuit, heater).

Setpoints are preset. Modifications can only be made by arrangement. 2) Settings may be amended directly on the unit display.

163Rittal System Climate Control

Toptec CR Cat. 32, page 877 Heaters Page 169

Page 166: Erdinc  klima sk_broschuere_gb

Ex-

proo

f clim

ate

cont

rol s

yste

ms

Ex-proof climate controEx overpressure enclosure with integ

l systemsral enclosure cooling unit for zone II (gas)

Ex-proof climate control systems for zone II (gas) provide protection for high-tech monitoring systems in the oil and gas extraction industry.These days, high-tech monitoring systems have become a permanent feature in almost every sector. Whether in indus-trial zones or public areas, a sophisticated camera system makes everything more transparent and manageable. In this specialist field, it is necessary to ensure signal tranasmis-

sion over long distances, from the camera systems to the control room. To this end, amplifier units, known as concen-trators, are needed, and are installed half-way between the camera system and the control room. The technical challenge faced by climate control technology in these applications is the potentially explosive zone II (gas) occur-ring in selected areas of the oil and gas extracting industry.

164

The compressed air connection including control unit integrated into the enclosure ensures a constant overpressure (2 mbar). This produces an ex-free zone in the enclosure interior.

The design challenge with this type of climate control technology is to arrange the external air circuit with all the components of the cooling circuit in such a way that effective cooling out-put is provided, while at the same time meet-ing the ex-proof requirements for zone II (gas).

Rittal System Climate Control

Further information available on request.

Page 167: Erdinc  klima sk_broschuere_gb

Ex overpressure enclosure with integral enclosure cooling unit for zone II (gas)

Ex-proof climate control systems

These concentrator units must be kept at a certain internal temperature in order to ensure optimum performance capabilities and transmissions from the camera systems. Rittal has taken up the challenge and designed enclosure and climate control components for use in potentially explo-

sive zone II. A compact cooling output of up to 4 kW is ensured by a unit designed specifically for potentially explosive areas.

5

Ex-

proo

f clim

ate

cont

rol s

yste

ms

Rittal System Climate Control

The sealed cover and intelligent filter design in the extraction zone of the external circuit provides effective protection against exter-nal ambient influences such as coarse dust or even sand.

Special fans designed for potentially explosive areas are used here.

16

Control of the cooling unit with the popular Comfort controller ensures an efficient supply of useful cooling output. Visualisation of the operating states and the current enclosure internal temperature are easily read via the display positioned centrally in the enclosure.

Page 168: Erdinc  klima sk_broschuere_gb
Page 169: Erdinc  klima sk_broschuere_gb

Enclosure heaters

Enclosure heaters from page 168

� � � Enclosure heaters . . . . . . . . . . . . . . . . . . . . . . . . . . 10 – 150 W. . . . . . . 169� � � Enclosure heaters . . . . . . . . . . . . . . . . . . . . . . . . . 250 – 800 W. . . . . . . 169

Indoor

Outdoor

with fan

without fan

Rittal System Clima

En

clo

sure

hea

ters

Benefits at a glance● Useful cooling output from 10 to

800 watts● Self-regulating PTC technology● Quick-assembly system

Important● For the correct temperature and to avoid

condensation, use a thermostat and/or hygrostat, see page 178

● Heaters should always be installed in an upright position. Leave a distance of 50 mm at the top and bottom to allow convection

● The thermal output is increased with fans ● Heat is distributed evenly in large

enclosures by using several low-output heaters

Tips and tricksApplications see page 234

Assembly see page 234

Electrical connection see page 234

167te Control

Page 170: Erdinc  klima sk_broschuere_gb

Enc

losu

re h

eate

rs

168

Enclosure heaters

Condensation poses a particular risk for control

electronics, especially with outdoor siting, but also

indoors. A range of output categories ensures that the

correct thermal output is always available. In this way,

the total required thermal output can be distributed

with complete accuracy within an enclosure.

Fast assemblyAchieved using snap fastening on 35 mm support rails to EN 50 022 or via screw fastening directly onto the mounting plate.

Fully wired unit ready for connectionClamp-type terminal connection for simple, effective wiring.

Rittal System Climate Control

Page 171: Erdinc  klima sk_broschuere_gb

Continuous thermal output 10 – 800 W

Enclosure heaters

B = WidthT = Depth

SuRetyp

No● T

(mt

● I

pply includes:ady-to-install unit with clamp-e terminal connection

te: hermostat SK 3110.000 see accessories) is recom-ended for precise tempera-

ure control in the enclosure. n order to prevent condensa-

tion on assemblies, hygrostat SK 3118.000 (see accesso-ries) is recommended to regulate heating.

● In larger enclosures, even heat distribution is best achieved by installing several low-output heaters.

● The installation of heaters is generally advisable, even when using heat exchangers and cooling units, in order to prevent condensation.

Approvals, see page 297.

Detailed drawing,see page 267.

ure

hea

ters

Enclosure heaters without fan

Model No. SK 3105.110 3106.120 3115.130 3116.140 3107.150 3107.160 3102.170

Dimensions in mmWHD

81 123 49

8116449

10215560

10222560

10226081

14020560

14025081

Rated operating voltage V, Hz 110 – 240 V ACContinuous thermal output at Tu = 10°C 10 W 20 W 30 W 50 W 75 W 100 W 150 W

Pre-fuse T 2 A 4 AAccessories Packs of PageThermostat 1 3110.000 178 Hygrostat 1 3118.000 178 Temperature indicator 1 3114.100 177

Special voltages available on request. We reserve the right to make technical modifications.

E

ncl

os

Enclosure heaters with fan

Model No. SK 110 V 3105.210 3105.220 3105.230

Model No. SK 230 V 3105.180 3105.190 3105.200

Dimensions in mmWHD

142170101

142170101

142170101

Rated operating voltage V, Hz 110 or 240 V ACContinuous thermal output at Tu = 10°C 250 W1) 400 W1) 800 W1)

Pre-fuse gG for 110 V 4 A 6 A 10 APre-fuse gG for 230 V 4 A 6 A 6 AAccessories Packs of PageThermostat 1 3110.000 178 Hygrostat 1 3118.000 178 Temperature indicator 1 3114.100 177

1) Output with fan. Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

169Rittal System Climate Control

Page 172: Erdinc  klima sk_broschuere_gb
Page 173: Erdinc  klima sk_broschuere_gb

System accessories

Air routing from page 174

Features from page 172

Air duct system ...............................................................................17490° deflector ..................................................................................174Shallow air duct system ..................................................................175Shallow duct extension ..................................................................175

Stoppers .........................................................................................175Air diverter ......................................................................................176Door-operated switch .....................................................................176

Control/regulation from page 177Digital enclosure internal temperature display and thermostat .....177Enclosure internal thermostat .........................................................178Hygrostat.........................................................................................178Bottom-mounted adaptor................................................................178Speed control..................................................................................179

Mounting adaptor for speed control ...............................................179Interface card .................................................................................179SK BUS system...............................................................................180Cable connection kit .......................................................................180Test adaptor ...................................................................................180

Mounting accessories from page 181Roof plates TS.................................................................................181Roof plates DK-TS...........................................................................181Vent attachment TS.........................................................................182Trim frame.......................................................................................182

Quick-change frame .......................................................................182Adjustable frame.............................................................................183Adaptor frame.................................................................................183Integrated louvres...........................................................................183

esso

ries

Cold Plate from page 184System attachment .........................................................................184Fluid distributor ...............................................................................184Direct fluid connection ....................................................................184Flexible hose...................................................................................184

Quick-action vent valve ..................................................................184Elbow coupling ...............................................................................185Double-nipple coupling .................................................................185Temperature sensor TF25...............................................................185

Sys

tem

acc

Liquid Cooling Package from page 186 Cooling module...............................................................................186Touchscreen display.......................................................................186Front cover ......................................................................................186Vertical shielding ............................................................................186Horizontal shielding ........................................................................187Covers.............................................................................................187

Accessories for rack sealing ..........................................................187Vent valve .......................................................................................188Connection hose.............................................................................188Quick-release fastener ...................................................................188Add-on cover ..................................................................................188

Filter technology from page 189Filter mats for centrifugal fans ........................................................189Filter mats for cooling units ............................................................189Metal filter........................................................................................190Lint screen ......................................................................................191

Louvred grille for lint screen ...........................................................191Spare filter mats..............................................................................191Fine filter mats for fan-and-filter units .............................................191

General from page 192Wide-range power pack 24 V (DC) for thermoelectric cooler ........192Electric condensate evaporator......................................................192Condensate collecting bottle ..........................................................192Condensate hose............................................................................192Outlet filters .....................................................................................193Hose-proof hoods ...........................................................................193

Front outlet grille, 2 U, for centrifugal fans......................................193Filter holder .....................................................................................194Overflow valve ................................................................................194Flow regulator valve........................................................................194Cooling medium for recooling systems ..........................................194

Software service from page 195Therm Software...............................................................................195EPLAN Cabinet ...............................................................................195

RiDiag II ..........................................................................................195

171Rittal System Climate Control

Page 174: Erdinc  klima sk_broschuere_gb

Sys

tem

acc

esso

ries

System accessories

Finding the perfect climate control solution is now even

easier, with matching system accessories. Superbly

coordinated components tailor the climate control

components perfectly to your specific requirements.

Be it targeted air routing or precise control of the

equipment, Rittal has the perfect solution for

everything.

172 Rittal System Climate Control

Page 175: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

OPC

Sys

tem

acc

esso

ries

SNMP

PC

TCP/IP

Air duct systemfor TopTherm roof-mounted cooling systemsCold air can be routed directly to specific areas of the enclosure using the air duct system. The risk of “short circuits” in the air circula-tion due to self-ventilated installed devices is therefore eliminated.

Interface boardfor TopTherm cooling systems with Comfort controllerThe interface card is an extension for TopTherm cooling systems with Comfort controller. In this way it is possible, e.g. to monitor a master/slave combination of up to 10 cooling systems. Control is via stand-ardised interfaces: RS232 (DB9) or RS485, one PLC interface (DB9). RS422 (RJ 45 jack) is the connection to the Rittal CMC-TC. In this way, remote monitoring via TCP-IP, graphical interfaces for operation, evalua-tion and control, documentation, and con-nection to additional sensors for access control and monitoring are possible.

Recooling

Roof platesFor fast mounting of:● TopTherm roof-mounted cooling units● TopTherm air/water heat exchangers● TopTherm roof-mounted fans● Vent attachment TSThe cut-outs are pre-integrated into the roof plate.

Benefits at a glance● Complete system solutions● Simple assembly● Fast ordering

ImportantDetails of direct matching accessories and (where applicable) Model Numbers may be found in the relevant product ordering table.

173

Page 176: Erdinc  klima sk_broschuere_gb

Sys

tem

acc

esso

ries

System accessories

174

Air routing

Air duct systemfor TopTherm roof-mounted cooling units and air/water heat exchangersIt is possible to route the cold air directly to specific areas of the enclosure using the air duct system. The risk of “short circuits” in the air circulation due to self-ventilated installed devices is therefore eliminated.The length of the shallow duct is 1500 mm, and it may be cut to any required length.

Material:Flame-resistant plastic to DIN 4102/B1

Supply includes:Shallow duct, compensating hose.

Accessories:

Deflector 90°, see page 174. Stopper, see page 175.

Also required:

TS support strips for securing the shallow duct in a vertical direction, see Cat. 32, page 997.

Note:Do not direct cold air straight at active compo-nents. When using the ducting system, the performance of the cooling unit may be reduced, depending on the application in question.

For Packs of Model No. SKAir duct system

SK 3209. . . ./SK 3210. . . ./SK 3273. . . ./SK 3359. . . ./SK 3382. . . ./SK 3383. . . ./SK 3384. . . ./SK 3385. . . . 1 3286.870

SK 3386. . . ./SK 3387. . . . 1 3286.970

Deflector, 90°for air duct systemFor targeted air deflection at the end of the shallow channel.

Material:Flame-resistant plastic to DIN 4102/B1

Packs of Model No. SK

1 3286.990

Rittal System Climate Control

Page 177: Erdinc  klima sk_broschuere_gb

System accessories

Sys

tem

acc

esso

ries

Air routing

175Rittal System Climate Control

Shallow air duct systemfor TopTherm roof-mounted cooling units and air/water heat exchangers, to fit TS 8 enclosures from a width of 800 mm.It is possible to route the cold air directly to specific areas of the enclosure using the air duct system. The risk of “short circuits” in the air circulation due to self-ventilated installed devices is therefore eliminated.The length of the shallow duct is 1500 mm, and it may be cut to any required length.

Material:Flame-resistant plastic to DIN 4102/B1

Supply includes:Shallow duct, adaptor, compensating piece, deflector 90°.

Accessories:

Deflector 90°, see page 174. Stopper, see page 175.

Also required:

Shallow duct extension SK 3286.860 to compen-sate for the enclosure width and height. TS support strips for securing the shallow duct in a vertical direction, see Cat. 32, page 997.

Note:Do not direct cold air straight at active compo-nents. When using the ducting system, the performance of the cooling unit may be reduced, depending on the application in question.

Max. 1 x

Max. 2 x

SK 3359. . . . /SK 3382. . . . SK 3386. . . . /SK 3387. . . .

SK 3209. . . . /SK 3210. . . . SK 3383. . . . /SK 3384. . . . SK 3385. . . .

For Packs of Model No. SKShallow air duct system

SK 3209. . . ./SK 3210. . . ./SK 3273. . . ./SK 3359. . . ./SK 3382. . . ./SK 3383. . . ./SK 3384. . . ./SK 3385. . . . 1 3286.850

Note:Observe max. no. of stoppers per unit.

Shallow duct extensionExtension kit for shallow air duct system SK 3286.850 for width, depth or height length extensions in TS 8 enclosures.

Material:Flame-resistant plastic to DIN 4102/B1

Supply includes:1500 mm shallow duct, connection piece.

Packs of Model No. SK

1 3286.860

Stoppersfor TopTherm roof-mounted cooling units To cover unneeded cold air outlets in TopTherm roof-mounted cooling units.

Material:Polyurethane foam

For Max. no. of stoppers per unit Packs of Model No. SK

SK 3359. . . ./SK 3382. . . . 1 2 3286.780

SK 3209. . . ./SK 3210. . . ./SK 3273. . . ./SK 3383. . . ./SK 3384. . . ./SK 3385. . . . 2 2 3286.880

SK 3386. . . ./SK 3387. . . . 1 2 3286.980

Page 178: Erdinc  klima sk_broschuere_gb

System accessoriesS

yste

m a

cces

sori

es

Air routing

176 Rittal System Climate Control

Air diverterFor use in climate controlled enclosures, climate control doors, climate control side panels and TopTherm wall-mounted cooling units. For targeted air routing of the cold air in a down-ward direction. Particularly well-suited for densely-packed elec-trical components in the lower section of the enclosure.

Material:Sheet steel

651)

External air circuit

Internal air circuit

1) 115 mm for SK 3213.330

For Model No. SK

SK 8607. . . ./SK 8687. . . .SK 3306. . . ./SK 3331. . . . 3213.300

SK 3304. . . ./SK 3305. . . . 3213.310

SK 3328. . . ./SK 3329. . . . 3213.320

SK 3332. . . . 3213.3301)

Door-operated switchWithout connection cableFor activation/deactivation of enclosure lights, for deactivation of cooling units and air/water heat exchangers whilst the door is open (to prevent condensation) or for monitoring the door.

No drilling required for installation.

Supply includes:Door-operated switch including mounting accessories

Packs of Model No. SZ

1 4127.000

Page 179: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

System accessories

Sys

tem

acc

esso

ries

Control/regulation

Digital enclosure internal temperature display and thermostatFor installing on the enclosure door or wall and in a cooling unit or heat exchanger.

Technical specifications: ● Small dimensions. ● Depth: 100 mm. ● The 3-digit 7-segment display is 13 mm high

and clearly legible. ● Can be switched from °C/°F. ● The display can be used in a temperature

range from +5°C to +70°C. ● Includes 1500 mm long NTC sensor. ● Two relay outputs as change-over contact and

normally open contact (maximum contact load 230 V, 6 A).

● Freely selectable switching difference. ● The freely adjustable setpoint values can be

adjusted via the membrane keyboard at the front. Setting range: +5°C to +55°C.

● Display and switching accuracy +/– 2 K. ● Mounting cut-out 68 x 33 mm. ● The minimum and maximum recorded tempera-

tures are stored until it is next reset.

Rated operating voltage Model No. SK

230 V (AC) 3114.100

115 V (AC) 3114.1151)

24 V (DC) 3114.0241) 1) Delivery times available on request.Special requirements available on request.

Digital enclosure internal temperature display and thermostatIntegrated into a patch panel 1 U. Including cable attachment for connection cable and label holder.

Rated operating voltage: 230 V (AC) Special voltages available on request.

Technical specifications: ● Small dimensions. ● Depth: 100 mm. ● The 3-digit 7-segment display is 13 mm high

and clearly legible. ● Can be switched from °C/°F. ● The display can be used in a temperature

range from +5°C to +70°C. ● Includes 1500 mm long NTC sensor. ● Two relay outputs as change-over contact and

normally open contact (maximum contact load 230 V, 6 A).

● Freely selectable switching difference. ● The freely adjustable setpoint values can be

adjusted via the membrane keyboard at the front. Setting range: +5°C to +55°C.

● Display and switching accuracy +/– 2 K. ● Mounting cut-out 68 x 33 mm. ● The minimum and maximum recorded tempera-

tures are stored until it is next reset.

Supply includes:Patch panel, temperature display and thermostat, identification strip.

Colour Model No. DK

RAL 7035 7109.035

177

Page 180: Erdinc  klima sk_broschuere_gb

System accessoriesS

yste

m a

cces

sori

es

Control/regulation

Enclosure internal thermostatEspecially suitable for controlling fan-and-filter units, heaters and heat exchangers, this thermo-stat can also be used as a signal generator for monitoring the enclosure internal temperature.

Technical specifications: ● Bi-metal sensor as a temperature-sensitive

element with thermal feedback. ● Contact population: Single-pole change-over

contact as a quick-break contact. ● Permissible contact load:

Cat. 5 – 3 (heating) AC 10 (4)1) A, DC = 30 W cat 5 – 4 (cooling) AC 5 (4)1) A, DC = 30 W (1)) = inductive load at cos ϕ = 0.6

● Setting range: +5°C to +60°C ● Weight: approx. 105 g ● Dimensions: 71 x 71 x 33.5 mm ● Switching difference: approx. 1 K ± 0.8 K.

● A broad voltage spectrum i.e. just one model covers 24 to 230 V.

● Time-saving connection technique using a terminal strip with a screw connection from the outside.

● Flexible mounting on a vertical or horizontal 35 mm support rail to EN 50 022, and snap fastening in the TS/ES enclosure section using the supplied adaptor.

Rated operating voltage Model No. SK

230/115/60/48/24 V (AC)3110.000

60/48/24 V (DC)

HygrostatThe hygrostat switches on the heater and/or fan when a preset relative humidity in the enclosure is exceeded. In this way, the relative humidity is raised above the dew point, and condensation on assemblies or electronic components is avoided.

Technical specifications: ● Contact population: Single-pole change-over

contact as a quick-break contact. ● Permissible contact load:

AC ~ 5 (0.2)1) A DC = max. 20 W (1)) = inductive load at cos ϕ = 0.6

● Setting range: 50 – 100 % relative humidity ● Weight: approx. 100 g ● Dimensions: 71 x 71 x 33.5 mm ● Switching difference: approx. 4 %

● A broad voltage spectrum i.e. just one model covers 24 to 230 V.

● Time-saving connection technique using a terminal strip with a screw connection from the outside.

● Flexible mounting on a vertical or horizontal 35 mm support rail to EN 50 022, and snap fastening in the TS/ES enclosure section using the supplied adaptor.

Rated operating voltage Model No. SK

24 – 230 V (AC/DC) 3118.000

Bottom-mounted adaptorfor enclosure internal thermostat SK 3110.000 and hygrostat SK 3118.000Bottom-mounted adaptor with mounting option for screwed cable glands, for targeted cable infeed from appropriate equipment such as SK fan-and-filter units and enclosure heaters. In conjunction with screwed cable glands, it is also suitable for use as strain relief.

Packs of Model No. SK

1 3110.200

178 Rittal System Climate Control

Page 181: Erdinc  klima sk_broschuere_gb

System accessories

Sys

tem

acc

esso

ries

Control/regulation

Speed controlTemperature-dependent speed control for Rittal fan-and-filter units and air/air heat exchangers with a rated operating voltage of 230 V AC, for noise reduction and to save energy in part-load operation.

Technical specifications: ● For mounting on a 35 mm support rail

DIN EN 50 022 ● Dimensions (W x H x D):

180 x 94 x 57 mm ● Rated operating voltage:

230 V (AC)/115 V (AC) ● Setting range: +20°C to +55°C ● Phase cross-over with microcontroller ● Maximum fan output 250 W or 1.2 A

at 230 V (AC) ● Maximum fan output 100 W or 1.2 A

at 115 V (AC)

Supply includes:Speed control, built into a PK enclosure 9512.100, NTC sensor, length 1.80 m.

Rated operating voltage Model No. SK

230 V (AC) 3120.000

115 V (AC) 3120.1151) 1) Delivery times available on request.

Mounting adaptor for speed controlThe mounting adaptor enables direct attachment of the speed control SK 3120.000/.115 to the vertical frame sections of network enclosures.

Material:Sheet steel, zinc-plated, passivated

Supply includes:Mounting adaptor including assembly parts.

Packs of Model No. DK

1 set 7526.964

Interface card for TopTherm cooling units with Comfort controller The interface card is an extension for TopTherm cooling units with Comfort controller. In this way it is possible, e.g. to monitor a master/slave com-bination of up to 10 cooling units in conjunction with a Rittal CMC-TC. Control is achieved via standardised interfaces: RS-232 (DB9) or RS-485, one PLC interface (DB9). RS-422 (RJ 45 jack) is the connection to the Rittal CMC-TC. Remote monitoring via TCP-IP, graphical interfaces for operation, evaluation and control, documentation and connection of additional sensors for access control is therefore possible. The extension card is built into a 1 U plastic housing. A voltage supply of 24 V DC is needed. This may be supplied from the CMC-TC via a wide-range power pack DK 7320.425 (100 to 240 V AC, 50/60 Hz) or externally via a Kycon connector.

Supply includes:Interface card integrated into a plastic box W x H x D (mm): 136 x 44 (1 U) x 129. Serial SUB-D cable 1.5 m.

Note:Networking and monitoring plan may be found on the relevant product page on the Internet, under “Download”.

Packs of Model No. SK

1 3124.200

Rittal System Climate Control

179
Page 182: Erdinc  klima sk_broschuere_gb

System accessoriesS

yste

m a

cces

sori

es

Control/regulation

SK BUS systemThe SK bus system facilitates communications between several enclosure cooling units, Rittal TopTherm .500/.510/.540, production date 05/02 or later, via a master/slave construction such as that required e.g. in complex bayed enclosure systems for optimum operating conditions.

Technical specifications:The master/slave construction facilitates common activation and deactivation via door limit switches, parallel activation and deactivation via a tempera-ture setpoint, and common collective fault signals and temperature logging, thereby eliminating the need for intricate wiring.

Supply includes:3 m shielded interface cable, including operating manual on programming the cooling units.

Note:nB = nK – 1 nB: Number of order units (SK bus system)nK: Number of cooling units to be linked.

Networking and monitoring plan may be found on the relevant product page on the Internet, under “Download”.

Property rights:German patent no. 196 15 469

35C

30C

25C

20C

20C

40C

35C

For Model No. SK

TopTherm 3124.100

Climate controlled enclosures 3124.000

Cable connection kit for CS Outdoor cooling unitsFor simple connection of CS cooling units. All cables preassembled with the corresponding connectors. Length of cables approx. 2500 mm.

Supply includes:1 set = 3 cables for AC, door-operated switch and alarm connection.

Note:Not required for CS 9776.500 and CS 9776.550.

Packs of Model No. CS

1 set 9765.105

Cable connection kit for CS Outdoor heat exchangers For simple connection of CS heat exchangers. All cables preassembled with the corresponding connectors. Length of cables approx. 2500 mm.

Note:Not required for CS 9776.150.

Design Model No. CS

3 cables for AC/DC and alarm connection 9765.110

2 cables for AC/DC and alarm connection 9765.115

Test adaptor for CS Outdoor climate control equipment The 9-pole sub-D interface allows testing of CS climate control equipment. Alternatively supports automatic or manual test procedures.

Supply includes:1 set = Test adaptor including 2 m connection cable.

Note:Not suitable for CS 9776.XXX.

Packs of Model No. CS

1 set 9765.050

180 Rittal System Climate Control

Page 183: Erdinc  klima sk_broschuere_gb

System accessories

Rittal System Climate Control

Roof plates TS For mounting: ● TopTherm roof-mounted cooling units ● TopTherm air/water heat exchangers● TopTherm roof-mounted fans ● Vent attachment TS The cut-outs in the roof plate are arranged in such a way that the TopTherm roof-mounted cooling units are positioned centrally on the enclosure.

Material:Sheet steel

Supply includes:Assembly parts.

Colour:RAL 7035

For enclosures W x D mm

To fit the mounting of

Model No. TS

600 x 600 SK 3359. . . .SK 3382. . . .SK 3149.4 . .SK 3149.8 . .

8801.3001)

800 x 600 8801.320

600 x 600 SK 3273.5. . SK 3383. . . . SK 3384. . . . SK 3385. . . . SK 3209. . . . SK 3210. . . . TS 8801.380

8801.3101)

800 x 600 8801.330

1200 x 600 8801.350

800 x 800 8801.920

800 x 600 SK 3386. . . . SK 3387. . . .

8801.3402)

1200 x 600 8801.3601) When mounting the cooling units, there may be a

collision with the eyebolts of the enclosure; for thisreason, roof fastening screws are supplied loose with the roof plates.

2) Attachment is from the inside using metal brackets andretaining clamps.

sori

es

For mounting B1mm

B2mm

T1 mm

T2mm

T3mm Model No. TS

SK 3382. . . ./SK 3359. . . .SK 3149.4 . ./SK 3149.8 . .

567.5 475 567.5 260 129.3 8801.300

767.5 475 567.5 260 129.3 8801.320

SK 3209. . . ./SK 3383. . . ./SK 3210. . . ./SK 3384. . . ./SK 3273. . . ./SK 3385. . . .

TS 8801.380

567.5 490 567.5 390 61.3 8801.310

767.5 490 567.5 390 61.3 8801.330

1167.5 490 567.5 390 61.3 8801.350

767.5 490 767.5 390 161.3 8801.920

SK 3386. . . ./SK 3387. . . .767.5 692 567.5 392 57.8 8801.340

1167.5 692 567.5 392 57.8 8801.360

T = Depth

Sys

tem

acc

es

Roof plates DK-TSFor mounting: ● TopTherm roof-mounted cooling units ● TopTherm air/water heat exchangers● TopTherm roof-mounted fans ● Vent attachment TS The cut-outs in the roof plate are arranged in such a way that the TopTherm roof-mounted cooling units are positioned centrally on the enclosure.

Material:Sheet steel

Colour:RAL 7035

For enclosures W x D mm

To fit the mounting of

Model No. TS

600 x 900 SK 3209. . . .SK 3210. . . . SK 3273.5 . .SK 3383. . . . SK 3384. . . . SK 3385. . . .TS 8801.380

8801.410

600 x 1000 8801.420

800 x 900 8801.430

800 x 1000 8801.440

For mounting B1mm

B2mm

T1 mm

T2mm

T3mm Model No. TS

SK 3209. . . . SK 3210. . . . SK 3273.5 . .SK 3383. . . . SK 3384. . . . SK 3385. . . .TS 8801.380

567.5 490 867.5 390 211.3 8801.410

767.5 490 967.5 390 261.3 8801.420

567.5 490 867.5 390 211.3 8801.430

767.5 490 967.5 390 261.3 8801.440

Mounting accessories

13

T1B1

T2T3

B2

=

=

B = Width

13

T1B1

T2T3

B2

=

=

B = WidthT = Depth

181

Page 184: Erdinc  klima sk_broschuere_gb

System accessoriesS

yste

m a

cces

sori

es

Mounting accessories

182 Rittal System Climate Control

Vent attachment TS For passive ventilation with labyrinthine air flow routing, to match the roofs for TopTherm roof-mounted cooling units.

Colour:RAL 7035

Protection category:IP 43

Supply includes:Assembly parts.

37.5

495595

For roof plates with cut-out Model No. TS

490 x 390 mm 8801.380

Trim framefor slimline cooling unitsSlimline cooling units can be internally or exter-nally mounted on an enclosure door or wall. The trim frame presents a closed front for the cooling unit.

Material:Sheet steel

Colour:RAL 7035 14

0

For cooling unit Model No. SK

SK 3366. . . .SK 3377. . . . 3377.000

Quick-change framefor TopTherm roof-mounted cooling units The quick-change frame is more than just an alter-nate frame. Together with the seal, the lower part of the frame is screw-fastened to the enclosure, making it possible to attach or remove the plug-in cooling unit to/from the top part of the quick-change frame. In case of servicing, this means minimal assembly times and hence minimal down-time. What is more, the quick-change frame offers effective protection against the ingress of oil into the enclosure in oily atmospheres, thanks to its integral drainage trough.

Material:Sheet steel

Colour:RAL 7035

Supply includes:Quick-change frame, seal, quick-release fasteners.

Property rights: German patent no. 41 10 323French patent no. 2 675 317 UK patent no. 2 254 735

For TopTherm cooling unit

Model No. SK

SK 3359. . . ./SK 3382. . . . 3286.700

SK 3209. . . ./SK 3210. . . .SK 3383. . . .SK 3384. . . . SK 3385. . . .

3286.800

SK 3386. . . . SK 3387. . . . 3286.900

Page 185: Erdinc  klima sk_broschuere_gb

System accessories

Sys

tem

acc

esso

ries

Mounting accessories

183Rittal System Climate Control

Adjustable framefor air/air heat exchangers, railway-compatible version

The adjustable frame allows variable partial instal-lation of air/air heat exchangers on enclosures, to facilitate optimum space utilisation.

Material:Sheet steel

Colour:RAL 7035

For heat exchangers Model No. SK

SK 3126.4. . 3286.260

SK 3128.4. ./SK 3129.4. . 3286.270

SK 3130.4. . 3286.280

Adaptor framefor wall-mounted cooling units

To compensate for the rear tilt of the TP consoles.

Material:Sheet steel

Surface finish:Powder coated in textured RAL 7035

Supply includes:Assembly parts.

245

167

481

77.520020077.5

20

329

8484

201

277

Ø7

Mounting cut-out1

Top edge of console

Adaptor frame

Cooling units SK 3302.3X0

1

2

3

2 3

For cooling units 300 W Cat. 32,

pagePacks

ofModel No.

TPModel No. SK

3302.3X0 642 1 6730.600

Delivery times available on request.

Integrated louvresFor ventilation by convection; easily retro-fitted using 4 screws.

Material:Sheet steel

Colour:RAL 7035

Detailed drawing, see page 268.

B H

T

W (B) mm

H mm

D (T)mm

Packs of Model No. SK

160 110 8 4 2541.235

210 100 8 4 2542.235

330 110 8 4 2543.235

To order in textured RAL 7032 please add extension .200 to the Model No., and for a primed version please add extension .300. Delivery times available on request.

Page 186: Erdinc  klima sk_broschuere_gb

System accessorieS

yste

m a

cces

sori

es

s

Cold Plate

184 Rittal System Climate Control

System attachment for frequency converters For mounting frequency converters on the Cold Plate.

Supply includes:Wire clamp system, T-slot blocks.

For the attachment of frequency converters

Packs of

Model No. DCP

with all-round clamping surface 1 8616.700

with side clamping surfaces 1 8616.710

with clamping surfaces top and bottom 1 8616.720

Fluid distribution manifoldin stainless steelFor the connection of up to 4 Cold Plate units.

Supply includes:2 fluid distributors (inlet and return), screw plugs G1/4˝, G3/8˝, connector sleeves G1/2˝, seals.

Accessories:

Flex hose, see page 184, quick-action vent valve, see page 184, temperature sensor, see page 185.

Packs of Model No. DCP

1 set 8616.750

Direct fluid connectionFor connection of the Cold Plate through the rear or side panel of the enclosure.

Supply includes:2 connector sleeves G1/2˝, 2 Mini stop valves G1/2˝, 2 reducers G1/2˝ – G1/4˝, seals.

Accessories:

Flex hose, see page 184, double-nipple coupling, see page 185.

Packs of Model No. DCP

1 set 8616.751

Flexible hoseFor connection of the Cold Plate to a fluid distribu-tion manifold or direct fluid connection.

Supply includes:2 flexible hoses G1/4˝ with stainless steel braid, seals.

Accessories:

Elbow coupling, see page 185

Packs of Length mm Model No. DCP

1 set 500 8616.760

1 set 1000 8616.761

Quick-action vent valveTo vent the complete Direct Cooling Package system.Easily mounted on the fluid distributor.

Supply includes:Quick-action vent valve G3/8˝, seal.

Packs of Model No. DCP

1 8616.762

Page 187: Erdinc  klima sk_broschuere_gb

System accessories

Sys

tem

acc

esso

ries

Cold Plate

185Rittal System Climate Control

Elbow couplingFor horizontal or vertical connection of the Cold Plate.

Supply includes:4 L-shaped 90° fittings G1/4˝, seals.

Packs of Model No. DCP

1 set 8616.763

Double-nipple couplingFor connection of the flexible hose to the fluid distribution manifold.

Supply includes:4 double-nipple fittings G1/4˝, seals.

Packs of Model No. DCP

1 set 8616.764

Temperature sensor TF25For monitoring the inlet and return temperatures in the fluid distributor.

Supply includes:Temperature sensor TF25 (NTC, 10 kΩ), stainless steel cable gland G1/4˝, seal.

Other versions available on request.

Packs of Model No. DCP

1 8616.765

Page 188: Erdinc  klima sk_broschuere_gb

Sys

tem

acc

esso

ries

System accessories

Liquid Cooling Package

Cooling modulefor LCP Standard and SmartWith the cooling module, the useful cooling output may be gradually increased. There is 1 module fitted as standard.

For LCP Cooling output Model No. SK

Standard 6.6 kW 3301.250

Smart 7.0 kW 3301.290

Touchscreen displayfor LCP SmartThe display offers the opportunity of directly monitoring key functions of the LCP Smart, and implementing settings.

Packs of Model No. SK

1 3301.790

Front coverThe optional front cover, together with the built-in filter fleece, ensures even air outlet at the sides as well, and reduces the air outlet speed, thus mini-mising draught effects.

Packs of Model No. SK

1 3301.980

Vertical shielding To block the airflow on the left and right of the 482.6 mm (19˝) level, for enclosure height 2000 mm.

Material:Cellular PU foam, flame-inhibiting to UL 94 (HF1)Length: 1900 mm, self-adhesive on one side.

For sealing between

For enclosure width

mmModel No. SK

Side panel and 482.6 mm (19˝)

level

600 3301.380

800 3301.390

LCP and 482.6 mm (19˝)

level

600 3301.370

800 3301.320

Packs of 1

186 Rittal System Climate Control

Page 189: Erdinc  klima sk_broschuere_gb

System accessories

Sys

tem

acc

esso

ries

Liquid Cooling Package

187Rittal System Climate Control

Horizontal shielding Allows horizontal shielding of the airflow with a partially configured 482.6 mm (19˝) rack.

Material:Sheet steel, spray finished in RAL 7035

For enclosure width

mmPacks of Model No. SK

600 1 3301.330

800 1 3301.340

Coversfor LCP StandardFor sealing any air inlet and outlet openings that are not required.

Material:Sheet steel, spray finished in RAL 7035

Packs of Model No. SK

2 3301.310

Accessories for rack sealing for LCP Standard and LCP PlusTo prevent the ingress of ambient air.

Description Dimensions mm Packs of Model No. Cat. 32, page Side panel, screw fastened H x D 2000 x 1000 2 8100.235 917

Glazed door W x H 600 x 2000 1 8610.600 934 800 x 2000 1 8610.800 934

Sheet steel door, solid W x H 600 x 2000 1 7824.205 936 800 x 2000 1 7824.207 936

Divided roof plate for cable entry W x D600 x 1000 1 7826.6051) 972 800 x 1000 1 7826.8051) 972

1) Retrospective installation is not possible.

Page 190: Erdinc  klima sk_broschuere_gb

System accessoriesS

yste

m a

cces

sori

es

Liquid Cooling Package

188 Rittal System Climate Control

Vent valve For effective cooling of individual LCP modules (SK 3301.250). With quick-release system for simple installation in the water inlet of the LCP, including stop valve.

Packs of Model No. SK

1 3301.400

Connection hose 1 m long, flexible connection hose, may be shortened, including union nuts on both sides for connecting the LCP to existing pipework.

For LCP Thread Model No. SK

SK 3301.230/.420 3/4˝ 3301.350

SK 3301.480 1˝ 3301.351

Packs of 2

Quick-release fastener The shut-off quick-release fasteners on both sides facilitate easy connection and disconnection of the LCP to the existing pipe work (3/4˝ external thread) and connection hose SK 3301.350.

Packs of Model No. SK

1 connector1 coupling 3301.360

Add-on cover For height compensation with 2200 mm high racks in conjunction with the LCP (H = 2000 mm).

Material:Sheet steel, spray finished in RAL 7035

For LCP Model No. SK

SK 3301.210SK 3301.230 3301.221

SK 3301.420SK 3301.480 3301.421

Delivery times available on request.

Page 191: Erdinc  klima sk_broschuere_gb

System accessories

Sys

tem

acc

esso

ries

Filter technology

189Rittal System Climate Control

Filter mats for tangential fans Made of chopped-fibre mat with a progressive structure. Temperature-resistant to 100°C, self-extinguishing category F1 to DIN 53 438. Dust-laden air side: Open structure. Clean air side: Closed structure. Reliable filtering of virtually all types of dust from a particle size of 10 μm.

Material:Chemical fibre

For tangential fans/front outlet grilles 2 U W x H x D mm Packs of Model No. SK

SK 3144.000/SK 3145.000/SK 3176.000 425 x 85 x 8 5 3177.000

Filter mats for cooling unitsRittal cooling units are low-maintenance and are supplied without filter mats. Filter mats may be used for extreme conditions.

Material:Open-celled polyurethane foamed plastic with excellent physical and mechanical properties. Temperature-resistant from –40°C to +80°C. Thickness: 10 mm.

For TopTherm cooling units W x H x D mm Packs of Model No. SK

SK 3302.300/SK 3302.310 190 x 95 x 10 3 3286.110

SK 3302. . . ./SK 3303. . . ./SK 3361. . . . 265 x 200 x 10 3 3286.300

SK 3304. . . ./SK 3305. . . ./SK 3328. . . ./SK 3329. . . ./SK 3332. . . ./SK 3366. . . . 344 x 268 x 10 3 3286.400

SK 3273. . . ./SK 3382. . . ./SK 3383. . . ./SK 3384. . . ./ SK 3385. . . ./SK 3359. . . . 530 x 255 x 10 3 3286.500

SK 3386. . . ./SK 3387. . . . 720 x 300 x 10 3 3286.600

SK 3377. . . . 205 x 210 x 10 3 3253.010

For discontinued cooling units W x H x D mm Packs of Model No. SK

SK 3296. . . ./SK 3272.100/SK 3290. . . ./SK 3280.100/ SK 3299. . . ./SK 3261. . . . 539 x 332 x 10 3 3286.100

SK 3265.100/SK 3266.100 270 x 332 x 10 3 3267.100

SK 3256. . . . 395 x 300 x 10 3 3254.000

SK 3293. . . ./SK 3281.100/SK 3298. . . ./SK 3279.100/ SK 3260. . . ./SK 3269. . . ./SK 3262.100/SK 3393. . . ./ SK 3381.100/SK 3391. . . .

334 x 313 x 10 3 3294.100

SK 3255. . . ./SK 3395. . . . 350 x 245 x 10 3 3253.000

SK 3394. . . . 315 x 200 x 10 3 3285.000

SK 3292.134/SK 3278.134 325 x 250 x 10 3 3286.000

Page 192: Erdinc  klima sk_broschuere_gb

System accessoriesS

yste

m a

cces

sori

es

Filter technology

Metal filter Particularly when cooling units are used in dusty and damp environments, it is advisable to use washable metal filters. If air or steam condenses on the metal surfaces, any particles that may be present will adhere to the metal and are easily washed out with water or grease-dissolving detergents.

Material:Aluminium Thickness: 10 mm

For TopTherm cooling units W x H x D mm Packs of Model No. SK

SK 3302.300/SK 3302.310 190 x 95 x 10 1 3286.120

SK 3302.100/SK 3302.110/SK 3303. . . ./SK 3361. . . . 265 x 200 x 10 1 3286.310

SK 3304. . . ./SK 3305. . . ./SK 3328. . . ./SK 3329. . . ./ SK 3332. . . ./SK 3366. . . . 344 x 288 x 10 1 3286.410

SK 3273. . . ./SK 3382. . . ./SK 3383. . . ./SK 3384. . . ./ SK 3385. . . ./SK 3359. . . . 530 x 255 x 10 1 3286.510

SK 3386. . . ./SK 3387. . . . 720 x 300 x 10 1 3286.610

SK 3377. . . . 225 x 200 x 10 1 3253.220

For discontinued cooling units W x H x D mm Packs of Model No. SK

SK 3296. . . ./SK 3272.100/SK 3290. . . ./SK 3280.100 520 x 290 x 10 1 3286.210

SK 3299. . . ./SK 3261. . . . 520 x 315 x 10 1 3286.200

SK 3265.100/SK 3266.100 265 x 320 x 10 1 3267.200

SK 3256. . . . 315 x 365 x 10 1 3254.200

SK 3293. . . ./SK 3281.100/SK 3298. . . ./SK 3279.100/ SK 3260. . . ./SK 3269. . . ./SK 3262.100/SK 3393. . . ./ SK 3381.100/SK 3391. . . .

300 x 328 x 10 1 3294.200

SK 3255. . . ./SK 3395. . . . 348 x 210 x 10 1 3253.200

SK 3394. . . . 375 x 415 x 10 1 3285.200

For TopTherm climate control door/section door W x H x D mm Packs of Model No. SK

SK 3300.040/SK 3300.050/SK 3300.060/SK 3300.070/SK 3300.080/SK 3300.090/SK 3300.110/SK 3300.120 425 x 78 x 10 1 3284.210

For discontinued climate control doors W x H x D mm Packs of Model No. SK

SK 3306. . . ./SK 3307. . . ./SK 3309. . . ./SK 3310. . . . 424 x 100 x 10 1 3284.200

SK 3308. . . . 624 x 100 x 10 1 3288.200

For discontinued climate control side panel W x H x D mm Packs of Model No. SK

SK 3331. . . . 380 x 150 x 10 1 3289.200

For heat exchangers W x H x D mm Packs of Model No. SK

SK 3126.4XX 130 x 130 x 10 1 3286.230

SK 3128.4XX/SK 3129.4XX 208 x 208 x 10 1 3286.240

SK 3130.4XX 225 x 225 x 10 1 3286.250

For Mini recooling systems W x H x D mm Packs of Model No. SK

SK 3318.600/SK 3318.610/SK 3319.600/SK 3319.610 530 x 255 x 10 1 3286.510

SK 3320.600/SK 3334.600 500 x 558 x 8 1 3286.520

SK 3360. . . . 344 x 268 x 10 1 3286.410

190 Rittal System Climate Control

Page 193: Erdinc  klima sk_broschuere_gb

System accessories

Sys

tem

acc

esso

ries

Filter technology

191Rittal System Climate Control

Lint screen Especially for the use of cooling units and air/air heat exchangers where there is a high proportion of lint in the ambient air.

Material:Stainless steel mesh

For Packs of Model No. SK

SK 3304. . . ./SK 3305. . . ./SK 3328. . . ./SK 3329. . . ./SK 3332. . . ./SK 3360. . . ./SK 3126. . . ./SK 3127. . . ./SK 3128. . . ./SK 3129. . . ./SK 3130. . . .

1 3329.904

Delivery times available on request.

Louvred grille for lint screen Material:ABS

For Packs of Model No. SK

SK 3329.904 1 3329.903

Delivery times available on request.

Spare filter mats Made of chopped-fibre mat with a progressive structure. Temperature-resistant to 100°C, self-extinguish-ing category F1 to DIN 53 438. Dust-laden air side: Open structure. Clean air side: Closed structure. Reliable filtering of virtually all types of dust from a particle size of 10 μm.

Material:Chemical fibre

For thermoelectric coolers W x H x D mm Packs of Model No. SK

SK 3201.200/SK 3201.300 106 x 90 x 8 5 3201.050

For fan-and-filter units/outlet filters W x H x D mm Packs of Model No. SK

SK 3321. . . . 89 x 89 x 10 5 3321.700

SK 3322. . . . 120 x 120 x 12 5 3322.700

SK 3323. . . . 173 x 173 x 17 5 3171.100

SK 3324. . . ./SK 3325. . . . 221 x 221 x 17 5 3172.100

SK 3326. . . . 289 x 289 x 17 5 3173.100

SK 3327. . . . 286 x 286 x 10 5 3327.700

For filter holders W x H x D mm Packs of Model No. SK

SK 3175.000 338 x 242 x 20 3 3174.000

Fine filter mats for fan-and-filter units Made of chopped-fibre mat with a progressive structure. Temperature-resistant to 100°C, self-extinguishing category F1 to DIN 53 438. Dust-laden air side: Open structure. Clean air side: Closed structure. Reliable filtering of virtually all types of dust from a particle size of 10 μm.

Material:Chemical fibre

For fan-and-filter units/outlet filters W x H x D mm Packs of Model No. SK

SK 3323. . . . 173 x 173 x 12 5 3181.100

SK 3324. . . ./SK 3325. . . . 221 x 221 x 12 5 3182.100

SK 3326. . . ./SK 3327. . . . 289 x 289 x 12 5 3183.100

Page 194: Erdinc  klima sk_broschuere_gb

System accessories

192

Sys

tem

acc

esso

ries

General

Wide-range power pack 24 V (DC) for thermoelectric cooler

To supply voltage to the thermoelectric cooler with primary 96 – 264 V (AC) voltage supply input. Power packs for other outputs available on request.

Power pack 24 V (DC) for SK 3201.300 Model No. SK

150 W for snap-mounting onto top-hat rail 35 mm 3201.030

Electric condensate evaporatorFor external mounting on enclosures. For use with all enclosure cooling units and air/water heat exchangers. Evaporation performance: 1) 2.4 l/d 2) 4.2 l/d

Colour:RAL 7035

Supply includes:Electric condensate evaporator, ready to connect.

Detailed drawing, see page 268.

Rated operating voltage

Model No. SK

for SK 3302/SK 3303

for 400 mm wide cooling units

230 V, 50/60 Hz 3301.5601) 3301.5702)

115 V, 50/60 Hz 3301.5801) 3301.5902)

Condensate collecting bottleFor mounting on the enclosure. For use with all enclosure cooling units and air/water heat exchangers. Safety overflow at the side. Capacity approximately 0.75 l.

Condensate discharge tube

Membrane grommet

Max. 70 mm

Supply includes:Condensate collecting bottle, bottle holder including assembly parts.

12

3

Ø 73

239

66

1

2

3

Packs of Model No. SK

1 3301.600

Condensate hoseFor removing and forwarding condensate. For connecting to enclosure cooling units.

Material:PVC, transparent

Supply includes:10 m hose.

For devicesMaterial

thickness Ø

Model No. SK

SK 3302. . . ./SK 3201. . . . 8 x 1.5 mm 3301.608

SK 3303. . . ./SK 3361. . . . 10 x 1.5 mm 3301.610

SK 3273. . . ./SK 3304. . . ./SK 3305. . . ./SK 3328. . . ./SK 3329. . . ./SK 3332. . . ./SK 3359. . . ./SK 3366. . . ./SK 3377. . . ./SK 3382. . . ./SK 3383. . . ./SK 3384. . . ./SK 3385. . . ./SK 3386. . . ./SK 3387. . . .

12 x 2 mm 3301.612

Rittal System Climate Control

Page 195: Erdinc  klima sk_broschuere_gb

System accessories

Sys

tem

acc

esso

ries

General

193Rittal System Climate Control

Outlet filtersFor ventilation by convection, an outlet filter can be installed in the upper and lower sections of the enclosure.

Material:ABS, material resistance to UL 94-V0.

Colour:RAL 7035

Supply includes:Outlet filter including filter mat.

Note:EMC version, see page 48.

Accessories:

Spare filter mats, see page 191. Fine filter mats, see page 191.

Dimensions in mm Model No. SK

116.5 x 22 3321.207

148.5 x 24.5 3322.207

204 x 30 3323.207

255 x 30 3325.207

323 x 30 3326.207

For RAL 7032, use order extension .200.

Hose-proof hoodsfor fan-and-filter units/outlet filtersWhen the hose-proof hood is mounted above the fan-and-filter unit and outlet filter in conjunction with a fine filter mat, a protection category of IP 56 to EN 60 529 is achieved.

Material:Stainless steel

Protection category:In conjunction with the fan-and-filter units/outlet filters, NEMA 3R + 12 is met.

For Dimensions in mm

Model No. SK

SK 3321. . . . 150 x 260 x 40 3321.8001)

SK 3322. . . . 176 x 270 x 55 3322.800

SK 3323. . . . 233 x 410 x 55 3323.800

SK 3324. . . . SK 3325. . . . 282 x 500 x 85 3324.800

SK 3326. . . . SK 3327. . . . 350 x 560 x 110 3326.800

1) Delivery times available on request.

Front outlet grille 2 Ufor tangential fans This front outlet grille is required if a 482.6 mm (19˝) cross-flow blower (SK 3144.000/SK 3145.000) is used in the lower section of the electronic enclosure and the hot air is to be expelled to the outside from the upper section of the enclosure. The design of the grille matches that of the intake grille in the cross-flow blower. These grilles can also be used as simple inflow and outflow grilles with natural convection.

Accessories:

Filter mat, see page 189.

Packs of Model No. SK

1 3176.000

Page 196: Erdinc  klima sk_broschuere_gb

System accessoriesS

yste

m a

cces

sori

es

General

194 Rittal System Climate Control

Filter holderfor roof ventilationThe use of a filter mat is required in order to increase the protection category of the roof vent (SK 3148.007). Protection category IP 44 to EN 60 529 is achieved.

Material:Sheet steel

Supply includes:Filter holder including filter mat.

Accessories:

Spare filter mat, see page 191.

W x H x D mm Model No. SK

340 x 244 x 15 3175.000

Overflow valvePressostat for use in the water cycle between the recooling system and the air/water heat exchanger. It prevents an increase in pump pres-sure in the recooling system against the closed magnetic valve of the air/water heat exchanger outside of the cooling cycle.

Material:Brass

Setting range: 2 – 12 bar

Presetting: 3 bar

Version Packs of Model No. SK1/2˝ bypass valve 1 3301.9003/4˝ bypass valve 1 3301.910

1˝ bypass valve 1 3301.920

Flow regulator valveFor use with air/water heat exchangers, espe-cially if more than one heat exchanger (n > 1) is used in the water cooling circuit. The correctly set valve then ensures the same quantity of cooling medium for all equipment. The valve is used for hydraulic balancing.

Material:Brass

Setting range: 3 – 12 l/min

Version Packs of Model No. SK3/4˝ x 1/2˝

for volumetric flow control 1 3301.930

3/4˝ x 3/4˝for volumetric flow control 1 3301.940

Cooling medium for recooling systemsReady mixApart from the recooling systems for oil and emul-sion, all other recooling systems are only suitable for the cooling of water or a water/glycol mixture.

As well as protecting against frost, this cooling medium also serves to inhibit bacterial growth and provide optimum corrosion protection.

Supply includes:10 l canister, 25 l canister or 200 l barrel.

Rifrost Antifreeze/water mixture Container Model No. SK

Outdoor 1 : 210 l 3301.950

25 l 3301.955

200 l 3301.9571)

Standard 1 : 410 l 3301.960

25 l 3301.965

200 l 3301.9671) 1) Delivery times available on request.

Page 197: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

System accessories

Sys

tem

acc

esso

ries

Software service

Therm SoftwareRittal Therm is a calculation program for enclosure climate control. All electrical and electronic components have a certain power loss which is dissipated to the envi-ronment in the form of heat. Because an increas-ing number of components are now being housed in ever smaller spaces, the heat produced can soon reach levels which are harmful to electronic components and may severely curtail their useful lives. The Therm software package takes care of the complex calculation of climate control require-ments. A user-friendly interface guides the opera-tor to the most suitable, correctly dimensioned climate control component. All evaluations are closely based on the require-ments of IEC/TR 60 890 AMD 1/02.95 and DIN 3168 for enclosure cooling units.

Supply includes

CD-ROMLanguages: Available in 13 languages Model No. SK 3121.000

Note:Your free 30-day trial version may be downloaded at www.rittal.com

EPLAN CabinetBoost your productivity at every stage, from electrical planning, to enclosure population, through to production

The electrical planning and mechanical installa-tion of an enclosure are combined into an inte-grated workflow with EPLAN Cabinet.

Equipment and component data is transferred from the wiring schematic in EPLAN Electric P8 or earlier versions of EPLAN into the layout plan. Rittal enclosures are integrated as original 3D models via component libraries (Rittal RiCAD-3D). Cable trunking, support rails, terminals and devices may be positioned in the 3D representa-tion of the enclosure at a click of the mouse. Colli-sion controls ensure compliance with distances and blocked surfaces, and help to avoid design errors.

Automatic generation of bills of materials and order lists are, of course, included, as are high-quality, dimensioned drawings for plant documen-tation.

Supplementary modules such as routing or NC generate drilling plans and programs, optimised wiring paths and lists, as well as information for drilling and milling machines. The simple plan-ning and detailed documentation of EPLAN Cabinet support an optimum workflow, from the wiring schematic through to the populated enclosure.

EPLAN Cabinet is available from: www.eplan.com

RiDiag IIRiDiag II is a tool for diagnosing the operating behaviour of Comfort controller-regulated cooling units. By connecting a PC, it is possible to retrieve error messages, temperatures and capacity utili-sation levels of the cooling units which are stored in the Comfort controller. The system includes integrated temperature measurement from four sensors in the cooling unit, and also features graphical representation of the temperature development over time.

Supply includes

CD-ROMLanguage: German/English/Italian/FrenchConnection cableModel No. SK 3159.100

195

Page 198: Erdinc  klima sk_broschuere_gb

196

Page 199: Erdinc  klima sk_broschuere_gb

Tips and tricks

Cooling with ambient air from page 198Fan-and-filter units Applications/selection criteria ........................................................198Assembly ........................................................................................200Rack-mounted fans/tangential fans – Applications .......................201

Air/air heat exchangers Applications ....................................................................................202Selection criteria .............................................................................203Assembly ........................................................................................204Air routing .......................................................................................205Electrical connection and control ..................................................206

Cooling units from page 207Applications ....................................................................................207Selection criteria .............................................................................208Assembly ........................................................................................209Air routing........................................................................................210

Condensation management ...........................................................213Electrical connection and control ..................................................215Thermoelectric cooler – Mounting options .....................................216

Liquid cooling IE from page 217Air/water heat exchangers Applications ....................................................................................217Selection criteria .............................................................................218Assembly ........................................................................................219Air routing........................................................................................220Condensation management............................................................222Electrical connection and control ..................................................224

Recooling systems/chillers Applications ....................................................................................226Selection criteria ............................................................................227Assembly ........................................................................................228Notes...............................................................................................229

rick

s

Liquid cooling IT from page 230Aisle containment Benefits ...........................................................................................230Usage..............................................................................................231Application examples ....................................................................232

Liquid Cooling Package Plus, Smart, Extend.........................................................................233

Tip

s an

d t

Enclosure heaters from page 234Applications/assembly/electrical connection ................................234

Monitoring from page 235Master/slave mode..........................................................................235Interface card..................................................................................235

CMC-TC enclosure monitoring system...........................................237

197Rittal System Climate Control

Page 200: Erdinc  klima sk_broschuere_gb

Coo

ling

with

am

bien

t air

Cooling with ambieFan-and-filter units – Applica

nt airtions/selection critiera

Fan-and-filter units utilise the ambient air for direct

cooling of the enclosure interior.

This requires cool, reasonably clean ambient air.

Ambient conditions

Cool

198 Rittal System Climate Control

Fan-and-filter units are ideal for dissipating heat loads cost-effectively. The prerequisite is that the ambient air must be relatively clean with a temperature below the desired enclosure internal temperature. A temperature difference of 10 K is ideal.

Application diversity and designIn most cases, it makes sense to install the axial fan with the air directed from outside into the enclosure so that over-pressure is created inside the enclos-ure, as per the delivered state. This helps to avoid the ingress of unfiltered ambient air.

Advantage: Aesthetics and functionThe extremely low build height is typical of the Rittal fan-and-filter unit design. The super-slimline vent grille guarantees optimum air throughput with low noise generation.

Air directionDirection of airflow “blowing into the enclosure”. Standard arrangement of fan and outlet filter. In this case, a mini-mal overpressure is generated inside the enclosure. The incoming air is routed completely via the filter mat.

Direction of airflow “extracting from the enclosure”. Configuration after changing the airflow direction of the fan-and-filter motor. In such cases, unfiltered “bad air” may be drawn in via leaks in the enclosure.

180°

1

2

3

Dismantling

Direction of airflow in the supplied state/standard

Direction of airflow after rotating the fan motor

1

2

3

1

2

2

1

Fan-and-filter unit

Outlet filter

1

2

Page 201: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Cooling with ambient air

Coo

ling

with

am

bien

t air

Fan-and-filter units – Applications/selection critiera

Small enclosure

Command panel

Console

Bayed enclosure/large enclosures

PC enclosure

1

2

3

4

5

Practical example of a fan-and-filter unit Fan-and-filter units are used in virtually all segments of indus-try: from the smallest enclosures, to command panels and consoles, through to large and bayed enclosure systems. They are the easiest method of protecting against overheat-ing and hot-spots.

The basic prerequisite for their use is that the ambient tem-perature must be significantly lower than the enclosure inter-nal temperature.

A wide range of control units such as thermostat, hygrostat and speed control for noise minimisation extend the applica-tion range to other areas, such as the office sector and labo-ratories.

EMC fans meet the requirements for increased RF shielding. Particularly when using fan-and-filter units in conjunction with PC enclosures or monitor panels, DC variants are used which provide effective protection from interference.

5

5

4

2

3 1

Sealed and shieldedAlso available with EMC shieldingAll fan-and-filter units and outlet filters are alternatively available with EMC shield-ing. The required conduc-tive connection is achieved via a metallic coating on the fan-and-filter unit housing and a special sealing frame.

Protection functionsThe membranes of the fan grille in the form of a rain canopy provide exceptional protection against the ingress of splashed water and dust.Protection category IP 54 is achieved as standard.

Hosed water protectionParticularly for applications in the food industry, the hose-proof hood prevents the ingress of damp. The protection category IP 55 is achieved in conjunction with additional fine filter mats.

Important● The prescribed heat loss

and the maximum antici-pated ambient tempera-ture define the required volumetric flow.

● Always use the fan-and-filter units and outlet filters together.

Calculation formulae, see page 34 or refer to the Internet at www.rittal.com

199

Page 202: Erdinc  klima sk_broschuere_gb

Cooling with ambieC

oolin

g w

ith a

mbi

ent a

ir

nt air

Fan-and-filter units – Assembly

200 Rittal System Climate Control

Benefits of Rittal fan-and-filter units and outlet filters● All-round foamed-in seal as standard to achieve a protec-

tion category of IP 54● Additional mounting catches for fast, screwless assembly,

to ensure secure attachment to the enclosure ● A new unlatching system for removal of the louvred grille

Super-simple assembly without screws.

Benefits:● Air throughput from 20 to 700 m3/h● Super-fast assembly ● Air flow direction may be reversed from blowing (default

setting) to extracting● All fans also available with EMC shielding

Louvred grill lock system● Can only be opened with tools● Achieves a protection category of IP 55 with types

SK 3323 . . . . to SK 3327. . . .

IP 55 with standard mat (A)plus additional micro-filter mat (B)Not applicable to SK 3321.... and SK 3322....

y

1

2

3

45

6

(A)

(B)

y

2

1

Page 203: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Cooling with ambient air

Coo

ling

with

am

bien

t air

Rack-mounted fans/tangential fans – Applications

Rack-mounted fan● Air throughput 320/480 m3/h, 1 U.● Direct ventilation of the subracks prevents hot-spots and

heat accumulation. ● The fan units (24 V DC, 115 – 230 V AC) are also available

with integral speed control and fault evaluation.Mounting directly on the 482.6 mm (19˝) level

Rack-mounted Vario fan with guide frame ● The rack-mounted fan slides like a drawer.● Connectors on the rear ensure immediate contact.

Installation directly in the subrack

Installation via two mounting brackets on the 482.6 mm (19˝) mounting level

1

2

3

1

2

3

Tangential fan● 320 m3/h air throughput, 2 U.● The high air throughput means that Rittal tangential fans

are capable of dissipating large heat losses from the enclosure.

● The ambient air is drawn in via the front grille and con-veyed upwards.

● The minimal noise generation of 52 dB creates a pleasant working environment.

201

Page 204: Erdinc  klima sk_broschuere_gb

Coo

ling

with

am

bien

t air

Cooling with ambient aAir/air heat exchangers – Applicatio

irns

Air/air heat exchangers use the external temperature

for cooling. By separating the internal and external air

circuits, the ingress of dust into the enclosure is

prevented.

Ambient conditions

Cool Dust

202 Rittal System Climate Control

Outstanding performance and designThe requirement for use of air/air heat exchangers is that the ambient temperature must be below the desired enclosure internal temperature.Dust and aggressive ambient air are unable to enter the enclosure interior, thanks to the two separate air circuits.

In all situations where the ambient air is sufficient for cooling, air/air heat exchangers offer effective, energy-saving solu-tions. The high specific thermal output is attributable to the special construction and functional design of the heat exchangers:

● A large heat exchanger area with compact dimensions● Exceptionally conductive materials and connections● Fans that may be controlled separately● Optimum flow conditions

Wood-processing industry

Air/air heat exchangers (wall-mounted)

1

2

Practical example of an air/air heat exchangerIn the paper and wood-processing industries, for example, particular requirements are placed on climate control compo-nents. They ensure good internal ventilation and heat dissi-pation from the enclosure. At the same time, they also pre-vent the ingress of super-fine dusts.

Air/air heat exchangers are ideal for this purpose, since they effectively dissipate the heat from the enclosure with their two hermetically separate air circuits based on the reverse cur-rent or counter-current principle, and prevent the ingress of ambient air into the enclosure.

1

2

2

Page 205: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Cooling with ambient air

Coo

ling

with

am

bien

t air

Air/air heat exchangers – Selection criteria

Cool ambient airAir/air heat exchangers utilise the ambient air to cool the air in the enclosure interior. Based on the counterflow principle, the completely separate airflows are routed through the heat exchanger module by powerful fans.

● Ambient conditions: The ambient temperature Tu must be lower than the permissible enclosure interior temperature. A temperature difference of 10 K is ideal.

● Also ideal for use in dusty ambient conditions.

Flow and siting conditionsInternal/external mountingAir/air heat exchangers may optionally be mounted on the outside or inside of the enclosure. The slimline design facili-tates external mounting on the door, rear panel and side panels.

By diverting the waste air upwards, this prevents the crea-tion of disruptive air flows in front of the enclosures.

The fans in the internal and external circuit may be activated separately via an intelligent controller and thus adapted ideally to the ambient conditions.

External mounting

Internal mounting

1 2

1

2

203

Page 206: Erdinc  klima sk_broschuere_gb

Cooling with ambient airC

oolin

g w

ith a

mbi

ent a

ir

Air/air heat exchangers – Assembly

204 Rittal System Climate Control

Sealing of the enclosureThe enclosure must be sealed on all sides (IP 54). Particular attention should be paid to the sealing of the area around the cable entry openings and above all, the floor section of the enclosure.

Additionally, the door seal must be in perfect condition.

The sealing material included with the heat exchangers must be applied in accordance with the installation instructions.

Take care not to bend the side panel or enclosure door.

External circuit Flow and siting conditionsAir/air heat exchangers in the external circuit should have a distance of at least 200 mm from a wall and from one another (air inlet and outlet openings). If this distance cannot be met, air baffle plates should be used.

Siting optionsWall-mounted heat exchangers may be mounted on the rear panel, side panels or door of the enclosure.

Distance from the wallat least 200 mm

Page 207: Erdinc  klima sk_broschuere_gb

C

Rittal System Climate Control

ooling with ambient air

Coo

ling

with

am

bien

t air

Air/air heat exchangers – Air routing

Free air circulationIt is important to ensure “even” air circulation inside the enclosure. Air inlet and outlet openings in the internal circuit must on no account be obstructed by electrical installations. This would prevent air from circulating inside the enclosure. Under such conditions, the capacity of the device would not be adequately utilised. A clearance of > 200 mm must be guaranteed.

Note:Wall-mounted cooling units should never be fitted directly behind the mounting plate. Active power components are located on the front of the mounting plates. The heat exchanger would then operate in its own air short-circuit.

If it is impossible to install the device any other way, appropri-ate air baffle plates should be used, and air inlet and outlet openings should be provided in the mounting plate.

200

Internal circuit – Wall-mounted unitsAttention should be paid to components and electronic com-ponents equipped with their own ventilation systems, such as blowers and axial fans. If their air flow is directed against the chilled air flow of the heat exchanger, this could cause an air short-circuit and adequate climate control would no longer be guaranteed.

Note: Never direct the chilled air flow at active components.

205

Page 208: Erdinc  klima sk_broschuere_gb

Cooling with ambie

206

Coo

ling

with

am

bien

t air

nt air

Air/air heat exchanger – Electrical connection and control

Simple control with digital temperature display● Specific thermal output from 17.5 to 90 W/K● With controller and digital temperature display● Floating fault signal contact in case of overtemperature● System analysis via display

Supply connection● The mains connection parameters (voltage and frequency)

specified on the rating plate must be observed.● The pre-fuse specified on the rating plate must be used.

Rated voltage 230 V, 50/60 HzRated current 0.6 A/0.8 ARated consumption 140 W/180 WPre-fuse T 2 ASpecific cooling output 45 W/K

CablingSignal data cable

Control cable

Motor cable

The power cable, power supply unit cable, signal cable and data cable must be laid separately; cable lengths should be kept as short as possible. Avoid coupled sections.

1

2

3

1231

2

3

Rittal System Climate Control

Page 209: Erdinc  klima sk_broschuere_gb

Applications

Cooling units

Cooling units keep the enclosure internal temperature

at a constant level, even to below room temperature.

The air routing meets individual requirements. Two

separate circuits prevent the ingress of dust into the

enclosure.

Ambient conditions

Heat Dust

Co

olin

g u

nit

s

207Rittal System Climate Control

● Climate controlled enclosures ● Roof-mounted cooling units ● Wall-mounted cooling units ● Thermoelectric cooler

Integral cooling system/climate controlled enclosuresThe combination of enclosure and cooling components achieves particularly effective cooling. Assembly time is eliminated. The investment costs for the complete unit offer exceptional value for money.

Roof-mounted cooling unitsRequirement-oriented routing of cooling air in the internal circuit is possible, with up to four cold air outlet openings and the optional use of ducts. In the external circuit, the heated air is expelled to the rear, left and right, and option-ally upwards. This means that the enclosure may be sited in a bayed suite or close to the wall.

Wall-mounted cooling unitsDepending on the space and design requirements, internal mounting, partial internal mounting and external mounting are all possible. Thanks to large distances between the air intake and outlet openings, effective cold air throughput of the enclosure is achieved.

Page 210: Erdinc  klima sk_broschuere_gb

Cooling unitsC

oo

ling

un

its

Selection criteria

208 Rittal System Climate Control

Enclosure climate control poses escalating demands on inte-gration and adaptation to the local conditions and the exist-ing process control and monitoring system. Rittal offers the right solution to suit every requirement.

When selecting the appropriate cooling unit for your enclosure, please observe the following points:

● What is the installation type to IEC 890?(see page 34, calculation bases)

● What ambient conditions are anticipated (max. ambient temperature and humidity)?

● What is the required maximum internal temperature of the enclosure (Ti)?

● What is the heat loss from electronic components inside the enclosure?

● Is there a requirement regarding the protection category to EN 60 529/IEC 529?

● What type of ambient pollution, such as dust, oil and chemicals, are the cooling units exposed to?

● For bayed enclosure suites, the output irradiated from neighbouring units may also need to be taken into account.

● Good ventilation should be ensured at the site of installa-tion (for example, the heat dissipated by the cooling unit may cause a significant rise in the temperature of small rooms).

● Particularly with poor ambient conditions, such as dirt or small, unvented rooms, air/water heat exchangers should be used.

Proper use of enclosure cooling unitsIn order to ensure the proper use of enclosure cooling units, the following points should be observed:

1. The unit must only be installed and opened by authorised, expertly trained personnel.

2. Choose a location for the cooling unit which ensures excellent ventilation. The site must be free from excessive contamination and moisture. For example, the atmosphere must not contain any conductive dusts or corrosive media.

3. The mains connection data (connection voltage and frequency) specified on the rating plate must be observed. In the case of 400 V, 2~ cooling units, we recommend the use of transformer circuit-breakers, and for three-phase units, the use of motor circuit-breakers is advisable.

4. The prescribed electrical protection devices must be con-nected upstream of the unit. No additional temperature control must be connected upstream of the device at the supply end. The pre-fuse specified on the rating plate should be provided as line protection. Observe the locally valid regulations when installing.

5. Where a door contact switch is used, a shielded cable should be used in environments with increased levels of electro-magnetic interference.

6. The temperature range specified on the rating plate must be observed when operating the cooling unit, both indoors and outdoors.

7. The enclosure must be sealed on all sides (IP 54).

8. The air inlet and outlet openings in the internal circuit of the cooling unit must not be obstructed.

9. The cold air flow should not be directed straight at electronic components, to prevent the formation of condensation.

10. The unit must only be installed horizontally, in accordance with the prescribed installation position. The maximum permissible deviation from the horizontal is 2°.

11. After disconnecting from the supply voltage, the cooling circuit of the cooling unit must not be switched back on for at least 5 minutes.

12. The customer must not make any modifications to the cooling unit.

13. The heat loss of the components installed in the enclosure must not exceed the specific useful cooling output of the cooling unit.

14. The installation instructions contained in the cooling unit manual must be observed in full.

Important

Page 211: Erdinc  klima sk_broschuere_gb

Cooling units

Co

olin

g u

nit

s

Assembly

209Rittal System Climate Control

Sealing of the enclosureThe enclosure must be sealed on all sides (IP 54). Particular attention should be paid to the sealing of the area around the cable entry openings and above all, the floor section of the enclosure.

Additionally, the door seal must be in perfect condition.

The sealing material included with the cooling units must be applied in accordance with the installation instructions.

Take care not to bend the side panel or enclosure door.

Installation on enclosuresThe cooling unit must be correctly installed.

The roof plate of the enclosure must not be allowed to give under the weight of the cooling unit.

If necessary, additional stays should be used. Do not obstruct the air inlets and outlets of the internal circuit.

Note:For TopTherm-Plus roof-mounted units, TS 8 roof plates pre-pared with mounting cut-outs and reinforcement strips for all standard enclosure sizes are available as an accessory (see page 181).

When installing after the unit has been assembled, the twin-threaded bolts supplied loose should be screwed into the core holes in the plastic base on the underside of the device, with a maximum torque of 3 Nm.

Page 212: Erdinc  klima sk_broschuere_gb

Cooling unitsC

oo

ling

un

its

Air routing

210 Rittal System Climate Control

External circuit Flow and siting conditionsIn the outer circuit, enclosure cooling units should be spaced > 200 mm from the wall and/or from each other (air inlet and outlet openings). In order to ensure adequate air circulation, at least one air outlet opening must be kept free. If this clearance cannot be maintained, air baffle plates will need to be used.

The external circuit supports all siting variants.Thanks to their compact dimensions and external air routing design, roof-mounted cooling units may even be installed in low-height rooms and with bayed enclosure suites.Air intake is always from the front. The air is expelled at the sides and rear. An outlet to the top is also possible as an option. In other words, regardless of which siting mode is chosen, one air outlet must always be kept free.

Siting optionsThere are no restrictions here. Only the air intake and exhaust area in front of the cooling unit must be kept free. Wall-mounted cooling units may be mounted on the rear panel, side panels or door of the enclosure.

Distance from the wallat least 200 mm

Internal circuit – Wall-mounted unitsFlow conditions Attention should be paid to components/electronic compo-nents equipped with their own ventilation systems, such as blowers and axial fans. If their air flow is directed against the chilled air flow of the cooling unit, this could cause an air short-circuit. In the worst case, the internal safety valves of the cooling unit would discontinue cooling operation.

Note:Never direct the chilled air flow at active components.

Accessories:Air diverter, see page 176.

Page 213: Erdinc  klima sk_broschuere_gb

Cooling units

Co

olin

g u

nit

s

Air routing

211Rittal System Climate Control

Free air circulationIt is important to ensure “even” air circulation inside the enclosure. Air inlet and outlet openings in the internal circuit must on no account be obstructed by electrical installations. This would prevent air from circulating inside the enclosure. Under such conditions, the cooling capacity of the device would not be adequately utilised. A clearance of > 200 mm must be guaranteed.

Note:Wall-mounted cooling units should never be fitted directly behind the mounting plate. Active power components are located on the front of the mounting plates. The cooling unit would then be left to operate in its own air short-circuit.

If it is impossible to install the device any other way, appropri-ate air baffle plates should be used, and air inlet and outlet openings should be provided in the mounting plate.

Accessories:Air diverter, see page 176.

200

Air diverter systems for wall-mounted unitsSee page 176.

For use in climate control side panels and TopTherm-Plus wall-mounted cooling units. For targeted air routing of the cold air in a downward direction. Particularly well-suited for densely-packed electrical components in the lower section of the enclosure.

Internal circuit – Roof-mounted unitsFlow conditionsWhen using roof-mounted units, particular attention should be paid to the air flow from the blowers of built-in electronic components (such as frequency converters and other drive units).

Page 214: Erdinc  klima sk_broschuere_gb

Cooling unitsC

oo

ling

un

its

Air routing

Air duct systemfor TopTherm-Plus roof-mounted cooling units It is possible to route the cold air directly to specific areas of the enclosure using the air duct system. The risk of “short circuits” in the air circulation due to self-ventilated installed devices is therefore eliminated.

Note:● Never direct the cold air flow straight at active compo-

nents.● Route the air duct system directly downwards with no

bends.● Cold air must be able to escape unobstructed at the end of

the duct.● Additional deflections will reduce the useful cooling output.● When using the ducting system, the performance of the

cooling unit may be reduced, depending on the respec-tive application.

● The air duct system should not be extended. CAUTION Risk of icing!

1

Accessories:Air duct system for roof-mounted units,see page 174.

1

Stoppers for TopTherm-Plus roof-mounted cooling units For sealing any cold air outlets that are not required.

Note:At least two outlet openings must always remain open!

Please note that if two or three openings are closed, the cool-ing output may be reduced by 20 % and 30 % respectively!

SK 3286.880 for units

SK 3286.780 for units

SK 3286.980 for units

SK 3383.xxxSK 3384.xxxSK 3385.xxx

SK 3273.xxxSK 3209.xxxSK 3210.xxx

SK 3382.xxxSK 3359.xxx

SK 3386.xxxSK 3387.xxx

max. 2x

max. 1x

212 Rittal System Climate Control

Page 215: Erdinc  klima sk_broschuere_gb

Cooling units

Co

olin

g u

nit

s

Condensation management

213Rittal System Climate Control

Condensate routing (roof-mounted units)Any condensation which forms on the evaporator coil (with high humidity and low enclosure interior temperatures) is routed to the right and/or downwards out of the device via a drain in the evaporator tray. For this purpose, a piece of hose should be connected to one of the two condensate nozzles (1 or 2). The drain which is not required should be tightly sealed. The condensate must be able to run off freely. If the condensate is to be drained off over a greater distance, then care must be taken to ensure that the hose is free from kinks and checked for correct drainage. Units with a Comfort controller are additionally equipped with a condensate alarm.

Condensate discharge rear

Condensate discharge right

Note:Condensate discharge (wall-mounted units)For wall-mounted units, a hose should be connected to the condensate nozzle on the bottom of the unit.

The condensate drain pipe should be laid with a gradient, taking care to ensure there are no kinks in the pipe!

y

1 2

y

21

1

2

Condensate dischargeIf the condensate discharge is extended, its cross-section must not be reduced.

Accessories:PVC condensate hose

Condensate hose For unit(s)

SK 3301.608 (8 x 1.5) SK 3302.xxxSK 3301.610 (10 x 1.5) SK 3303.xxx/SK 3361.xxx

SK 3301.612 (12 x 2)SK 3304.xxx/SK 3305.xxxSK 3328.xxx/SK 3329.xxxSK 3332.xxx/SK 3382.xxxSK 3359.xxx/SK 3383.xxxSK 3384.xxx/SK 3385.xxxSK 3386.xxx/SK 3387.xxxSK 3366.xxx/SK 3377.xxxSK 3209.xxx/SK 3210.xxxSK 3273.xxx

Page 216: Erdinc  klima sk_broschuere_gb

Cooling unitsC

oo

ling

un

its

Condensation management

214 Rittal System Climate Control

Condensate evaporation, electricalintegrated into TopTherm-Plus cooling unitsCondensate arising inside the enclosure or on the evapora-tor coil of the cooling unit is effectively evaporated. The evap-orator device inside the cooling units has a very high evapo-ration output (several litres per day). This is achieved thanks to the principle of direct evaporation. Important note: The enclosure must be sealed on all sides.

Energy-efficient: Activation of the evaporator device is via a separate heater cartridge. “Condensate evaporation” based on the hot gas bypass principle is too ineffective, due to inadequate evaporation temperatures.

Advantage: ● Safe use: No condensate drips onto the factory floor

(no puddles/no risks of slipping/accidents).● No need to empty the condensate collecting receptacles.● No time-consuming laying of condensate hoses required.

Rittalinnovation

The internal and external units are active “direct evaporator coils”, which actively evaporate the condensate incurred.

Advantage: ● No collecting vessel required● No long hosepipes

Note: For roof and wall-mounted units, either external evaporator units or integral condensate evaporators may be used.

TopTherm-Plus cooling units are available with integrated electronic condensate evaporation and external evaporator units for retro-fitting.

Filter matsIn dusty environments, we recommend the use of filter mats to make it easier to clean the cooling unit. The filter should be changed at regular intervals, depending on the level of contamination.

If the air is oil-contaminated, it is better to use metal filter mats which may be cleaned with appropriate detergents and reused.

Page 217: Erdinc  klima sk_broschuere_gb

Cooling units

Co

olin

g u

nit

s

Electrical connection and control

215Rittal System Climate Control

Supply connection● Supply connection data (voltage and frequency) must be

observed in accordance with the rating plate.● The pre-fuse specified on the rating plate must be used.

Voltage range 400 V/460 VFrequency range 50 Hz/60 Hz

400 V/50 Hz 3~ 400 V/60 Hz 3~Rated current 2.5 A 3.0 AStart-up current 6.5 A 7.5 AMotor circuit-breaker 10 A 10 A

Rated consumption L 35 L 35 L 35 L 50

930 W1150 W

1150 W1400 W

Useful cooling output L 35 L 35 L 35 L 50

2000 W1450 W

2350 W1690 W

Coolant/filled weight R 134a, 950 g (34 oz), Fluid Group 2

Use of door-operated switchesOne floating door-operated contact should be used for each unit; under no circumstances must several cooling units be operated via one door-operated switch.

In environments with increased electromagnetic inter-ference, a shielded cable should be used. Alternatively, the door contact may be switched e.g. via an additional relay in the vicinity of the cooling unit.

Note:The cables should be laid separately from the mains cables; short cable distances should be observed.

CablingSignal data cable

Control cable

Motor cable

The power cable, power supply unit cable, signal cable and data cable must be laid separately; cable lengths should be kept as short as possible. Avoid coupled sections.

1

2

3

1231

2

3

Page 218: Erdinc  klima sk_broschuere_gb

Co

olin

g u

nit

s

Cooling units

Electrical connection and control/Thermoelectric Cooler – Mounting options

216 Rittal System Climate Control

Intelligent controlThe two controller variants for operational reliability offer a comprehensive range of functions. Essential control elec-tronics are well protected and cooled in the inner circuit.

Both variants have the following properties: ● Three voltage options: 115 V, 230 V, 400/460 V 3 ̃ ● Integral start-up delay and door limit switch function ● Icing protection function● Monitoring of all motors● Phase monitoring for three-phase units

Basic controller: ● Visualisation of the operating status via LED display:

− Voltage applied, functions OK− Door open− Overtemperature− High-pressure monitor has switched

● Switching hysteresis: 5 K● Floating fault signal contact in case of overtemperature● Setpoint adjustable from outside via potentiometer (setting

range 20 – 55°C)

Comfort controller:

● Master/slave function for up to 10 units, i.e. the unit which reaches the setpoint first reports this to the “master”, which switches all the other “slaves” on and off. The unit in which the door limit switch function is activated reports this to the “master”, which deactivates all the “slaves”.

● Switching hysteresis: 2 – 10 K; preset to 5 K● System alarm, individually configurable for 2 floating fault

signal contacts● Visualisation of the current enclosure internal temperature

and all system messages on the display● Storage of all system statuses in the log file● Optional extension card (SK 3124.200) with RS232,

RS485, RS422 and PLC interface for integration into superordinate remote control systems, e.g. with CMC, is also possible

Thermoelectric Cooler – MountingInstallationWhen installed in the enclosure, the unit only protrudes by a few millimetres, and therefore does not interrupt either the aesthetic appearance or freedom of movement on support arm systems.

External mountingIts low weight also allows it to be externally mounted on sim-ple aluminium rear panels or blanking panels.

Support arm systems Thanks to its low-vibration operation and minimal weight, the thermoelectric cooler from Rittal is the ideal partner on sup-port arm systems.

Thermoelectric Cooler – ScalabilityScalable output The modular design allows simple scaling of the cooling output depending on your requirements, both horizontally and vertically.

Page 219: Erdinc  klima sk_broschuere_gb

Air/water heat exchangers – Applications

Liquid cooling IE

Air/water heat exchangers effectively dissipate high

heat losses. Thanks to the spatial separation of the

heat exchanger and recooling system, the room is not

burdened with waste heat.

Ambient conditions

Heat Dust

Liq

uid

co

olin

g IE

217Rittal System Climate Control

Ideal at any installation siteHigh ambient temperatures and extreme levels of conta-mination are ideal conditions for the use of air/water heat exchangers. If direct dissipation of heat loss to the ambient air is undesirable or ineffective due to the confined space, the air/water heat exchanger may likewise offer an ideal solution. Very effective cooling solutions for individual enclosures or bayed enclosure suites may be achieved by separating the exchanger from the recooling system.

Extreme industrial environments

Air/water heat exchangers (roof-mounted, wall-mounted)

Recooling system

1

2

3

Practical example of an air/water heat exchangerIn all areas with extreme ambient conditions, enclosure and climate control components are subject to special require-ments. This applies, for example, to metal foundries, engine factories and the chemical and metal-working industries.

In such situations, low-maintenance air/water heat exchang-ers are used as efficient all-rounders. Either fed from existing cooling water networks or from separate recooling systems, these products contribute to an ideal climate inside the enclosure. The cooling water absorbs the heat inside the heat exchanger and conveys it to the corresponding cooling system. In this way, even small rooms are not subject to addi-tional waste heat from the enclosure, and the electronics inside the enclosure are effectively protected.

1

32

2

Page 220: Erdinc  klima sk_broschuere_gb

Liquid cooling IEL

iqu

id c

oo

ling

IE

Application example: Parallel connection of 4 air/water heat exchangers

1 5

6

2 2 2 2

3

4 4 4 4

Recooling system

Air/water heat exchangers

Overflow valve SK 3301.900/.910/.920 (Bypass function with closed magnetic valve of the air/water heat exchanger)

Flow regulator valve SK 3301.930/.940 (to regulate the volume flow in air/water heat exchangers)

Non-return valve (optional)

Magnetic valve (optional)

1

2

3

4

5

6

Example: Parallel connection of air/water heat exchangers with cold water supply via a recooling system.

Overflow valves and bypass control should be integrated into the recooling system and the customer’s own pipeline system respectively.

Air/water heat exchangers – Selection criteria

218 Rittal System Climate Control

Roof or wall mounting Two design variants for mounting on the enclosure roof or the side panel or door are available in the output range from 300 to 7000 watts. Available in two control variants (Basic and Comfort control), and also optionally with all water-carrying parts made from V4A (1.4571).

High temperature range● Application areas with temperatures up to +70°C and

extreme dust contamination, e.g. in foundries, are ideal for the use of this technology.

● Spatial separation of the heat exchanger and cold water supply is easily achieved.

Recooling system

Air/water heat exchanger, roof-mounted

Air/water heat exchanger, wall-mounted

Additional cooling water circuit for machine cooling

1

4

3

3

2

1

2

3

4

Cooling medium quality requirementsFor cooling media that cannot be precisely defined, or even seawater, air/water heat exchangers with all water carrying parts of stainless steel 1.4571 (V4A) are available.

General water quality requirements are outlined on page 37 “Hydrological data”.

Page 221: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Liquid cooling IE

Liq

uid

co

olin

g IE

Air/water heat exchangers – Assembly

Application benefitsCompact and lightweightAir/water heat exchangers have a low weight and a compar-atively low volume in relation to the heat loss dissipated. As a result, they are easily mounted on vertical enclosure sur-faces or on the roof.

Virtually maintenance-freeBecause the ingress of ambient air into the heat exchanger is prevented, dirt is unable to penetrate. Control of the air and water circuit is electronically monitored.

Sealing of the enclosureThe enclosure must be sealed on all sides (IP 54). Particular attention should be paid to the sealing of the area around the cable entry openings and above all, the floor section of the enclosure.

Additionally, the door seal must be in perfect condition.

The sealing material included with the heat exchangers must be applied in accordance with the installation instructions.

Take care not to bend the side panel or enclosure door.

Installation on enclosuresThe heat exchanger must be correctly installed.

The roof plate of the enclosure must not be allowed to give under the weight of the heat exchanger.

If necessary, additional stays should be used. Do not obstruct the air inlets and outlets of the internal circuit.

Note:For TopTherm-Plus roof-mounted units, TS 8 roof plates pre-pared with mounting cut-outs and reinforcement strips for all standard enclosure sizes are available as an accessory (see page 181).

When installing after the unit has been assembled, the twin-threaded bolts supplied loose should be screwed into the core holes in the plastic base on the underside of the device, with a maximum torque of 3 Nm.

219

Page 222: Erdinc  klima sk_broschuere_gb

Liquid cooling IE

220

Liq

uid

co

olin

g IE

Air/water heat exchangers – Air routing

Free air circulationIt is important to ensure “even” air circulation inside the enclosure. Air inlet and outlet openings in the internal circuit must on no account be obstructed by electrical installations. This would prevent air from circulating inside the enclosure. Under such conditions, the cooling capacity of the device would not be adequately utilised. A clearance of > 200 mm must be guaranteed.

Note:Wall-mounted cooling units should never be fitted directly behind the mounting plate. Active power components are located on the front of the mounting plates. The heat exchanger would then operate in its own air short-circuit.

If it is impossible to install the device any other way, appropri-ate air baffle plates should be used, and air inlet and outlet openings should be provided in the mounting plate.

200

Internal circuit – Roof-mounted unitsFlow conditionsWhen using roof-mounted units, particular attention should be paid to the air flow from the blowers of built-in electronic components such as frequency converters and other drive units.

Rittal System Climate Control

Page 223: Erdinc  klima sk_broschuere_gb

Liquid cooling IE

Liq

uid

co

olin

g IE

Air/water heat exchangers – Air routing

221Rittal System Climate Control

Air duct systemfor TopTherm-Plus roof-mounted air/water heat exchangersIt is possible to route the cold air directly to specific areas of the enclosure using the air duct system. The risk of “short circuits” in the air circulation due to self-ventilated installed devices is therefore eliminated.

Note:● Never direct the cold air flow straight at active compo-

nents.● Route the air duct system directly downwards with no

bends.● Cold air must be able to escape unobstructed at the end of

the duct.● Additional deflections will reduce the useful cooling output.● When using the ducting system, the performance of the

heat exchanger may be reduced, depending on the respective application.

● The air duct system should not be extended.

1

Accessories:Air duct system for roof-mounted units, see page 174. 1

Stoppers for TopTherm-Plus roof-mounted air/water heat exchangersFor sealing any cold air outlets that are not required.

Note:At least two outlet openings must always remain open!

Please note that if two or three openings are closed, the cool-ing output may be reduced by 20 % and 30 % respectively!

SK 3286.880 for unitsSK 3209.xxxSK 3210.xxx

max. 2x

Internal circuit – Wall-mounted unitsFlow conditions Attention should be paid to components/electronic compo-nents equipped with their own ventilation systems, such as blowers and axial fans. If their air flow is directed against the chilled air flow of the heat exchanger, this could cause an air short-circuit and prevent adequate climate control. In a worst case scenario, the heat exchanger will suffer an air short-circuit.

Note:Never direct the chilled air flow at active components.

Page 224: Erdinc  klima sk_broschuere_gb

Liquid cooling IEL

iqu

id c

oo

ling

IE

Air/water heat exchangers – Condensation management

222 Rittal System Climate Control

Condensate routing (roof-mounted units)Any condensation which forms on the heat exchanger (with high humidity and low enclosure interior temperatures) is routed to the right and/or downwards out of the device via a drain in the tray. For this purpose, a piece of hose should be connected to one of the two condensate nozzles (1 or 2). The drain which is not required should be tightly sealed. The condensate must be able to run off freely. If the con-densate is to be drained off over a greater distance, then care must be taken to ensure that the hose is free from kinks, laid with a gradient and checked for correct drain-age. Units with a Comfort controller are additionally equipped with a condensate alarm.

Condensate discharge rear

Condensate discharge right

y

1 2

y

21

1

2

Condensate discharge (flexible)

Cooling water connection (flexible)

1

2

Flexible cooling water connection and condensate drain pipeRoof-mounted units:In its delivered state, hose nozzles for connecting the cool-ing water and condensate hoses are located on the right-hand side of the unit. There is a second connection point for cooling water and condensate at the rear of the unit, which is sealed with sealing caps. If the connections at the rear are used, the sealing cap and hose nozzle should be un-screwed, cleaned and resealed using standard commer-cially available sealant (Teflon tape or hemp with sealing paste). Next, screw in the three sealing caps on the right and the three hose nozzles at the rear of the unit with the follow-ing torques:

● 15 Nm for hose nozzles for the supply and return flow● 15 Nm for sealing caps for the inlet and return● 2 Nm for condensate discharge● 2 Nm for sealing caps for condensate discharge

Note:Any condensate arising is discharged via the 1/2˝ tube con-nector and a discharge hose, which should be laid with a gradient ensuring that there are no kinks. In order to avoid increased condensation, the cooling water temperature should be adapted to match the required cooling output. Any condensate occurring may be disposed of using an external electronic condensate evaporator.

2

1

Page 225: Erdinc  klima sk_broschuere_gb

Liquid cooling IE

Liq

uid

co

olin

g IE

Air/water heat exchangers – Condensation management

223Rittal System Climate Control

Note:Condensate discharge (wall-mounted units)For wall-mounted units, a hose should be connected to the condensate nozzle on the bottom of the unit.

The condensate drain pipe should be laid with a gradient, taking care to ensure there are no kinks in the pipe!

Condensate dischargeIf the condensate discharge is extended, its cross-section must not be reduced.

Accessories:PVC condensate hose

Condensate hose For unit(s)

SK 3301.612 (12 x 2) SK 3209.xxx/SK 3210.xxxSK 3364.xxx/SK 3373.xxxSK 3374.xxx/SK 3375.xxx

Page 226: Erdinc  klima sk_broschuere_gb

Liquid cooling IE

224

Liq

uid

co

olin

g IE

Air/water heat exchangers – Electrical connection and control

Supply connection● Supply connection data (voltage and frequency) must be

observed in accordance with the rating plate.● The pre-fuse specified on the rating plate must be used.

Rated voltage 230 V 50 Hz/60 HzRated current 0.4/0.48 APre-fuse T 4 APower consumption 95/110 WUseful cooling output 400 l/h L 35 W 10 2500 W

Cooling medium Water (see specifications)

Use of door-operated switchesOne floating door-operated contact should be used for each unit; under no circumstances must several air/water heat exchangers be operated via one door-operated switch.

In environments with increased electromagnetic interfer-ence, a shielded cable should be used. Alternatively, the door contact may be switched e.g. via an additional relay in the vicinity of the air/water heat exchanger.

Note:The cables should be laid separately from the mains cables; short cable distances should be observed.

CablingSignal data cable

Control cable

Motor cable

The power cable, power supply unit cable, signal cable and data cable must be laid separately; cable lengths should be kept as short as possible. Avoid coupled sections.

1

2

3

1231

2

3

Rittal System Climate Control

Page 227: Erdinc  klima sk_broschuere_gb

Liquid cooling IE

Liq

uid

co

olin

g IE

Air/water heat exchangers – Electrical connection and control

Intelligent controlThe two controller variants for operational reliability offer a comprehensive range of functions. Essential control elec-tronics are well protected and cooled in the inner circuit.

Both variants have the following properties: ● Three voltage options: 115 V, 230 V, 400/2 ˜● Integral start-up delay and door limit switch function ● Leak detection● Monitoring of all motors

Basic controller: ● Visualisation of the operating status via LED display:

− Voltage applied, functions OK− Door open− Overtemperature

● Switching hysteresis: 5 K● Floating fault signal contact in case of overtemperature● Setpoint adjustable from outside via potentiometer (setting

range 20 – 55°C)

Comfort controller:

● Master/slave function for up to 10 units, i.e. the unit which reaches the setpoint first reports this to the “master”, which switches all the other “slaves” on and off. The unit in which the door limit switch function is activated reports this to the “master”, which deactivates all the “slaves”.

● Switching hysteresis: 2 – 10 K; preset to 5 K● System alarm, individually configurable for 2 floating fault

signal contacts● Visualisation of the current enclosure internal temperature

and all system messages on the display● Storage of all system statuses in the log file● Optional extension card (SK 3124.200) with RS232,

RS485, RS422 and PLC interface for integration into superordinate remote control systems, e.g. with CMC, is also possible

225Rittal System Climate Control

Page 228: Erdinc  klima sk_broschuere_gb

Liqu

id c

oolin

g IE

Liquid cooling IERecooling systems/chillers –

226

Applications

Recooling systems ensure centralised, efficient cool-

ing and supply of the cooling medium (generally

water), and are used with particularly high heat loads.

They may serve several pieces of equipment simulta-

neously, and are particularly effective in terms of cool-

ing output.

Ambient conditions

Heat Dust

Application diversity of centralised cooling technology

Enclosure coolingIn conjunction with air/water heat exchangers, optimum dissipation of high heat loads is guaranteed, even under extreme ambient temperatures and air con-tamination levels.

Cooling of liquid mediaDirect and indirect cooling of liquids are the prerequisite for ensuring the required machine precision and speed.

Process coolingHigh-quality material processing, such as laser cutting, necessitates high levels of temperature preci-sion with simultaneous cooling of the peripheral technology.

Rack cooling ITRittal offers solutions for base load cooling and ambient air-neutral, high-performance cooling for all IT sectors.

Rittal System Climate Control

Page 229: Erdinc  klima sk_broschuere_gb

Liquid cooling IE

Liqu

id c

oolin

g IE

Recooling systems/chillers – Selection criteria

227Rittal System Climate Control

Generally speaking, recooling systems are divided into open and closed systems.

In the pressure-sealed configuration, the water circuit is equipped with a pressure relief valve and automatic exhaust. There is no need to top up the water.

Recooling systems designed as an open system have a tank made of PP/PE plastic or stainless steel 1.4301 with lid built into the recooling system. This is easily filled.

If a recooling system is required to serve several pieces of equipment having different requirements in terms of inlet temperature and flow rate of the cooling medium, e.g. com-bined enclosure and process cooling, multi-circuit systems are used. In such cases, the different circuits may be tai-lored to the respective equipment.

If there is already a central cooling water supply available at the installation site, e.g. in the case of plant water in the auto-motive industry, recooling systems may optionally be fitted with a water-cooled condenser. One of the major benefits of this solution lies in the fact that the factory temperature is not additionally raised by waste process heat.

Liquid cooling IEMini-recooling systems● Cooling output from 1 to

6 kW ● Space-saving, compact

design● Attractive design● Wall-mounted units: Inte-

gration into the machine and enclosure housing without using additional floor space

Recooling systems integrated into the TS 8 Top enclosure system● Cooling output from 6 to

60 kW● Compact design ● Option of integration into

existing TS 8 enclosure combinations

Recooling systems in a floor-standing enclosure for water and oil● Cooling output from 2.1 to

26 kW ● Stand-alone enclosure● Minimal base area● The functionally equipped

design facilitates the cool-ing of oil and water

● There are a range of options available

Recooling systems in an industrial enclosure● Cooling output up to

502 kW● High cooling output with

optimised space require-ments

● Removable enclosure pan-els offer easier accessibil-ity in case of servicing

Immersible recooling systems● Wherever it is necessary to

cool dirt-contaminated media (metal swarf or aggressive sludge)

● High-end flat condenser made of stainless steel

● Sealed cooling circuit

Power Fluid Cooler ● Fast delivery range ● Standardised version

available ex works ● New design in the output

category 8 to 59 kW ● Defined options

Liquid cooling ITData centre with recooling systems● Recooling systems ensure

central cooling and supply of the cooling medium for liquid cooling sys-tems

● Spatial separation between refrigeration and cooling for temperature-neutral expansion of the data centre.

Page 230: Erdinc  klima sk_broschuere_gb

Liquid cooling IE

228

Liqu

id c

oolin

g IE

Recooling systems/chillers – Assembly

Unity with enclosuresFor example, recooling systems may be connected directly to a bayed enclosure suite, providing effective, centralised cooling for all enclosures and housings on a machine or system.

Recooling systems in the TS 8 Top enclosure system are eas-ily integrated into existing enclosure combinations. For appli-cations in confined conditions, the Mini-recooling systems for wall and roof mounting are ideal, with their space-saving, compact design.

Recooling system

Air/water heat exchanger, roof-mounted

1

2

2

1

2

Spatially separatedHigh heat loads can even be dissipated in confined and awkward spaces, thanks to the spatial separation of the recooling system from the enclosures and machine. In all cases, as well as enclosure cooling, cooling water may also be produced for process and machine cooling or for cooling liquid media.

Recooling systems in floor-standing and industrial enclo-sures, with their robust design, are the ideal stand-alone solution, and provide optimum accessibility for servicing purposes.

Recooling system

Air/water heat exchanger, roof-mounted

Air/water heat exchanger, wall-mounted

Other components, e.g. machine cooling

12

3

3

4

1

2

3

4

Outdoor sitingTo avoid putting additional pressure on the factory air with the waste heat incurred during the process, the recooling system may be supplied with the option of outdoor siting (for ambient temperatures down to –20°C).

In such cases, a rain canopy should be provided to protect the recooling system from extreme weather. The water circuit must be filled with 34 % anti-freeze agent Antifrogen N (or equivalent) to 66 % water in relation to the total water vol-ume, or with Rifrost 1 : 2.

IT chillers do not require a rain canopy.

Rittal System Climate Control

Page 231: Erdinc  klima sk_broschuere_gb

Liquid cooling IE

Liqu

id c

oolin

g IE

Recooling systems/chillers – Notes

229Rittal System Climate Control

Assembly and commissioningWhen siting the recooling system, the following points should be observed:● Connection of an inlet and outlet duct requires the manu-

facturer's prior consent. − Performance loss (air-cooled recooling system)

● Never site the recooling system in the vicinity of a heater.− Performance loss

● The recooling system may only be sited on flat, solid surfaces. The maximum permissible deviation from the vertical is 2°.

● Connect the equipment to the recooling system using insulated pipe or hose connections.

● If the equipment is positioned higher than the recooling system, install a non-return valve upstream in the inlet and a magnetic valve in the return.− To avoid overflowing the tank.

● With recooling systems that are intended for covered out-door siting, the minimum external temperature is given in the technical specifications.

● In the case of recooling systems (for water) at tempera-tures below zero, a water/glycol mixture should be added in the prescribed ratio.

● If it is possible to shut off the equipment cycle, a bypass must be provided in order to protect the pump.

● Under no circumstances must the circulation pump be allowed to run dry – Damage to the pump.

1

2

In the case of air-cooled recooling systems, the following mini-mum distances from the wall and ceiling should be observed:

Wall: At least 1x condenser height

Ceiling: At least 3x the condenser height

1

2

Re-cooling system

Distance from equipmentSite the recooling system close to the equipment in order to avoid long distances, which could lead to performance losses. When selecting the installation site, care should be taken to ensure easy access at all times; this will make main-tenance of the system easier.

You should also ensure adequate ventilation of the room where the recooling system is sited. If there is inadequate ventilation, the temperature of the room will increase as a result of waste heat, leading to impaired performance of the recooling system.

Cooling mediaApart from the recooling systems for oil and emulsion, all other recooling systems are only suitable for the cooling of water or a water/glycol mixture. When filling the systems for the first time, water from the existing supply line is generally suitable, although care should be taken to ensure a consist-ent water quality.

However, as satisfactory results are only rarely achieved with-out water treatment, additives should always be added to the cooling water, irrespective of the installation site. As well as protecting against frost, these also serve to impair bacterial growth and achieve optimum corrosion protection.

Pre-mixed additive is available from Rittal in the mix ratios ● 1 : 2 for outdoor siting● 1 : 4 for standard applications, available in 10 l, 25 l and

200 l containers. See page 194.

Page 232: Erdinc  klima sk_broschuere_gb

Liqu

id c

oolin

g IT

Liquid cooling ITAisle containment – Benefits

230

Instead of flooding the room with cold air, this Rittal concept routes the cold air generated directly to the equipment via the cold aisle. The servers are supplied with chilled air distributed evenly across the entire rack height. Due to the cold aisle being contained there is no chance of the hot exhaust air mixing with the cold inlet air, leading to enhanced system efficiency.

The outstanding energy efficiency of the Rittal cold aisle concept has a simple and plausible explanation:

1. Cold and hot air cannot mix, hot air does not flow into the cold aisle. 2. The system can be operated with a much higher waste air temperature. 3. Standard air circulation cooling units are operated at an optimum thermal efficiency level.

Standard market concepts

Hot air extraction using a duct system

● Complex and costly duct system.● Larger surface area and height require-

ments. ● Limitation of the raised floor height.● As a result, there is no uniform cooling

air supply to the room area.● Cable management is made more

difficult.● Limited rack positioning flexibility due to

the air duct connection.

Rittal aisle containment

Cold aisle variant

● Use of standard, inexpensive CRAC sys-tems. Positioning outside the server area.

● Even with low room heights, the raised floor height for cooling air supply can be maximised without flow losses.

● Undisturbed and uniform air flow distribu-tion of cooling air in the cold aisle guaran-tees high efficiency.

● Favourable working conditions in the cold aisle due to low temperature, flow and noise load conditions.

● Hardware racks not connected to the enclosure do not impair the cooling efficiency of the cold aisle.

H

ot aisle variant

Standard CRAC systems cannot be used here.Inline climate control systems are needed to cool the air. The waste air produced can be selec-tively controlled. Efficiently raises the waste air tempera-tures without impairing the environment.

Rittal System Climate Control

Page 233: Erdinc  klima sk_broschuere_gb

Aisle containment – Usage

Liquid cooling IT

T

1

2

3

4

5

6

7

8

231

Liqu

id c

oolin

g I

Rittal System Climate Control

Representation of the air flows in the cold aisle variant

Supply of cooled air via the raised floor. The recirculation cooling units can be installed in an air conditioning strip or an external technical building.

Air supply to the cold aisle via air outlet grilles in the floor void. The feed air quantity is calculated and regulated based on the cold load to be removed.

A cold air pool forms in the sealed cold aisle according to the fresh air princi-ple. The hardware components draw the required cooling air quantity from this source.

The heat-laden waste air is discharged to the surroundings and rises to the ceiling.

A cushion of hot air forms below the ceiling. The hot air cushion cannot force its way into the cold aisle thanks to isolation.

Unimpeded suction of the exhaust air out of the air space. The separation enables high exhaust air temperatures, therefore the overall equipment effi-ciency of the cooling units is maximised.

The temperature neutrality of server racks fitted with LCP climate compo-nents allows them to be positioned in the room for expansion or extension purposes.

Optimised use of the server room area by use of sliding doors to further isolate the cold aisle.

1

2

3

4

5

6

7

8

Page 234: Erdinc  klima sk_broschuere_gb

Liquid cooling ITAisle containment – Applicat

232

Liqu

id c

oolin

g IT

ion examples

Rittal cold aisle containment with CRAC systems (cold aisle variant)

1

5

By using cold aisle containment, climate control of the room (in conjunction with the CRAC system) may be optimised in terms of energy efficiency and cooling output.● High energy efficiency● Increased cooling output per server enclosure● Easily retro-fitted to existing systems● Protection of your existing infrastructure

2

3

4

Aisle containment (cold aisle variant)

CRAC systems

Water/water heat exchanger

IT chiller

Temperature-neutral expan-sion, e.g. with LCP Smart

1

2

3

4

5

Aisle containment with LCP Inline (cold aisle variant)

1

5

2

In conjunction with the new LCP Inline, the cold aisle variant is a further option for the efficient dissipation of high heat loads from server enclosures. ● A raised floor is not required for climate control● To accommodate higher heat loads per server enclosure● Redundancies easily achieved● Direct supply of cold air to your server and network components

3

4

Aisle containment (cold aisle variant)

LCP Inline

Water/water heat exchanger

IT chiller

Temperature-neutral expan-sion, e.g. with LCP Extend

1

2

3

4

5

Rittal System Climate Control

Page 235: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Liquid Cooling Package Plus, Smart, Extend

Liquid cooling IT

Basic solutions

CRAC systems

with aisle c

LCP Extend

LCP Inline

duct

LCP Standard/Smart

LCP Plus

Pro

ontainment

with aisle containment

Low DensityThe entry-level option for professional IT climate control

MidThesoludata

Density tailor-made tions for discerning centres

HigThsolda

h Densitye most powerful utions for high-end ta centres

Cooling requirements

LCP Plus Functional principle: Air/water heat exchanger, bayable with server racks based on TS 8 (H x D 2000 x 1200 mm). Complete unit with 30 kW useful cooling output.

The separation of cooling and rack prevents water from penetrating the server rack, and makes it very easy to assemble and service.

LCPs are easy to handle (max. 2 m) and may be transported in lifts and through doors. The low weight means a minimal area load.

Liqu

id c

oolin

g IT

LCP Smart Functional principle: The LCP Smart draws in air at the rear of the server enclosure, cools it, and blasts the cooled air back into the front part of the server enclosure.

Differences compared with the LCP Standard: ● Fans may be individually exchanged with the system operational. ● Basic CMC as standard. ● Touchscreen display may be retrofitted. ● Shorter service times. ● Extended functionality of the monitoring and control technology/

software. Optimum adaptability thanks to dynamic, continuous control of the cold water volume flow.

LCP Extend

Functional principle: Air/water heat exchanger for retrofitting to racks while operational.

The stand-alone unit replaces the rear door (for other brands on request).

Mounted on the rear of the server enclosure and eases the pressure on the room air-conditioning system.

Technical specifications: ● Up to 12 kW useful cooling outputMax. air volume 3000 m3/h.

233

Page 236: Erdinc  klima sk_broschuere_gb

En

clo

sure

hea

ters

Enclosure heaters

Applications/assembly/electrical connection

234 Rittal System Climate Control

Installation positionHeaters should always be installed in an upright position. Leave a distance of 50 mm at the top and bottom to allow convection. In order to increase efficiency, where possible, heaters should always be fitted in the lower part of theenclosure.

effective ineffectiveFlow circuit Installation position

Installation option for enclosure heatersThe device is attached vertically, i.e. with the connection cable pointing downwards. The connection cable should be tightly secured. In order to create the required convection, a distance of at least 50 mm from components must be main-tained above and below the device. The thermal safety clear-ance from neighbouring components is at least 35 mm. Pro-vided these distances are observed, an ambient temperature of 65°C will not be exceeded.Enclosure heaters are used to prevent the formation of con-densation inside the enclosure and maintain a constant minimum operating temperature (e.g. when the system is switched off overnight). They achieve thermal outputs of 10 to 800 watts.

Electrical connectionDue to the particular characteristics of the PTC thermal ele-ment, the startup current is approx. 1.8 A for around 0.5 sec. A slow pre-fuse (gL) is therefore essential.

According to IEC 6100-4-5, a fuse is to be provided by the customer for pulse loads in excess of 1000 V. The surface temperature of the aluminium section is regu-lated automatically. A separate thermostat (SK 3110.000) should be connected to control the room temperature. To control the air humidity inside the enclosure, a hygrostat (SK 3118.000) may be connected upstream.

Page 237: Erdinc  klima sk_broschuere_gb

Monitoring

All the relevant parameters for the function and cooling

output of the climate control components are available

on the control desk for monitoring and control

purposes.

Mo

nito

rin

g

235Rittal System Climate Control

Master/slave operationIn open bayed enclosure systems which are not separate from one another, cooling units and air/water heat exchang-ers with Comfort control should always be used. These may be placed in master/slave mode via bus cable SK 3124.100:

● Simultaneous activation and deactivation of the devices● Parallel fault and door limit switch function ● Even temperature distribution across all sections of the

enclosure 1

2

3

7

4

5

5

6

Control cabinets

Wall-mounted unit

Roof-mounted unit

Comfort controller

Door limit switch

Connection terminals 1 and 2 of the cooling unit

Master/slave unit

1

2

3

4

5

6

7

Interface cardThe new interface board (SK 3124.200) is an extension for TopTherm-Plus cooling units and air/water heat exchangers with Comfort controller; see page 179. In this way it is possi-ble, e.g. to monitor a master/slave combination of up to 10 cooling units. Control is achieved via standardised inter-faces RS232 (DB9) or RS485, a PLC interface. RS422 (RJ 45 jack) is the connection to the Rittal CMC-TC. Remote moni-toring via TCP-IP, graphical interfaces for operation, evalua-tion and control, documentation, and connection to addi-tional sensors for access control facilitates monitoring.

The extension card is built into a 1 U plastic housing. A volt-age supply of 24 V (DC) is required. This can be supplied from the CMC-TC via long-range power pack or externally via a Kycon connector.

Further information may be found in our assembly and oper-ating instructions, at www.rittal.com –> Products –> Product search–> SK 3124.200.

Warnings and alarms from the interface board● Interior temperaure too

high● Icing● High-pressure sensor● Leakage● Condenser/fan defect● Evaporator coil/fan defect● Compressor defect● Sensor failure, condenser

temperature

● Sensor failure, ambient temperature

● Sensor failure, icing sensor

● Sensor failure, conden-sate level

● Sensor failure, internal temperature

● Phase missing or incorrect ● EEPROM defect

Page 238: Erdinc  klima sk_broschuere_gb

MonitoringM

on

itori

ng

236 Rittal System Climate Control

Application example: Master/slave operation and interface board

Control point/server room

Recooling system

Machining centre

Welding robot

1

2

2

3

4

4

1

2

3

4

Connection example: Master/slave operationwith bus cable and interface board

Serial interface board,Model No.: SK 3124.200

Serial interface cable

Master/slave BUS cable, Model No.: SK 3124.100

RTT = Rittal TopTherm-Plus cooling unit/Air/water heat exchanger

X1 = Supply connection/door limit switch/alarmsX2 = Master/slave connection SUB-D 9-poleX3 = Serial interface SUB-D 9-poleSt. = SUB-D connector 9-poleBu. = SUB-D jack 9-pole

Description:The address of the master depends on the number of attached slave units (09 = master with 9 slave units). The address of a slave device always begins with a 1. The sec-ond number represents the actual address. Up to a maxi-mum of 9 slave units may be operated with one master unit, whereby any unit may be a master. The maximum overall length of all connected units is 50 m. Single-phase and 3-phase units may be connected.

CMC

RTTMaster

Adr.: 09

X1

X2 X3

RTTSlave

Adr.: 11

X1

X2 X3

Adr.: 12

X1

X2 X3

Adr.: 19

X1

X2 X3

X2 X3 X2X2

X2 X2 X2 X2

X2

X2

St. St. St. St.

St.Bu. Bu.

St.

St.Bu.

1

RTTSlave

RTTSlave

2

3

1

2

3

Page 239: Erdinc  klima sk_broschuere_gb

Monitoring

Mo

nito

rin

g

237Rittal System Climate Control

Only one unit may be configured as master; the address ID must match the number of slave units. All slave units must have different addresses, and the addresses must be in ascending order without any gaps in between.

If changes are made to the configuration of the master, please proceed as follows:

1. Disconnect any existing connections between the RTT I/O unit and the PU– Timeout on the PU

2. Confirmation on the PU– Unit has been removed

3. Make the required changes to the master

4. Make the connection between the RTT I/O unitand the PU – Message on the PU “Unit found”

5. Wait 60 s then confirm– RTT I/O unit is correctly displayed with all its slaves

in the Web

Configuration settings on the cooling unit master regarding the number of slaves must only be made if there is no supply voltage at the RTT I/O unit, neither from the PU nor externally.

Notes on connecting cooling units and air/water heat exchangers in the master/slave combination

Enclosure monitoring system CMC-TC The RTT I/O unit may be connected to the CMC-TC system (Ethernet, TCPIP, SNMP, HTTP).

Note:For detailed information, see Cat. 32, page 806.

Programming cable Processing Unit II

Power pack

Connection cable for power pack

Connection cable for sensor units

Up to 4 sensor units

Page 240: Erdinc  klima sk_broschuere_gb
Page 241: Erdinc  klima sk_broschuere_gb

Technical Details

Cooling with ambient air from page 240Fan systems....................................................................................240Air/air heat exchangers...................................................................241

Cooling units from page 245Modular climate control concept ....................................................245Roof-mounted cooling units ............................................................246

Wall-mounted cooling units ............................................................247Thermoelectric coolers ...................................................................250

Liquid cooling IE from page 251Air/water heat exchangers ..............................................................251Cold Plate........................................................................................255Recooling systems .........................................................................256

Liquid cooling IT from page 266Chillers for IT cooling ......................................................................266Water/water heat exchangers ........................................................267

Enclosure heaters from page 267Enclosure heaters ..........................................................................267

ical

det

ails

System accessories from page 268

Electric condensate evaporator......................................................268Integrated louvres ...........................................................................268

239Rittal System Climate Control

Tech

n

Page 242: Erdinc  klima sk_broschuere_gb

Technical detailsTe

chni

cal d

etai

ls

Rack-mounted fansfor 482.6 mm (19˝), air throughput 320/480 m3/h Page 52

Rack-mounted fan Vario rack-mounted fan Vario rack-mounted fan

mounted between a pair of 482.6 mm (19˝) mounting angles

mounted in subracks 84 HP

mounted between a pair of 482.6 mm (19˝) mounting angles

Centrifugal fansAir throughput 320 m3/h Page 53

17

Front grille

Roof-mounted fansAir throughput 360 m3/h Page 54

Mounting cut-out

Without fan W

ith fan

50

RTT roof-mounted fan and vent attachment Air throughput (unimpeded air flow) 400/800 m3/h Page 54

Mounting cut-out

Fan systems

240 Rittal System Climate Control

1

2

465.1

482.6 (19″)

76.2

88

380

163

7560

250

345

265

360

280

Ø 8

□ 260 x 340

15 44

420

340

550

500

101

125

20

370

290

475 + 1

260

+ 1

Page 243: Erdinc  klima sk_broschuere_gb

Technical details

B1

Fan roof, modular, two-piece for TS/FR(i)Air throughput per fan (unimpeded air flow) 160/180 mm3/h at 50/60 Hz Page 58

Rittal System Climate Control

For enclosures Cover plate Roof dimensionsC D Model No.

TSWidthmm

Depthmm Solid Vented B1 B2 T1

600 600 2102.180 2102.400 567.5 435 567.5 400 224 7826.366

600 800 2102.190 2102.410 567.5 435 767.5 400 424 7826.368

600 900 2102.190 2102.410 567.5 435 867.5 400 424 7826.369

600 1000 2102.190 2102.410 567.5 435 967.5 400 424 7826.360

800 600 7885.100 7885.200 767.5 635 567.5 600 224 7826.486

800 800 7886.100 7886.200 767.5 635 767.5 600 424 7826.488

800 900 7886.100 7886.200 767.5 635 867.5 600 424 7826.489

800 1000 7886.100 7886.200 767.5 635 967.5 600 424 7826.480

Air/air heat exchangersWall-mounted Page 62

SK 3129.800 Mounting cut-out for external mounting

External mounting

Rear S

Mfoin

ide view

164

ounting cut-outr external and ternal mounting

110

Optional cable gland 1

Tech

nica

l det

ails

Air/air heat exchangersRoof-mounted Page 65

Rear Mounting cut-outfor external and internal mounting

Side view

420

301

360

400

440

320

480

600

Ø 23 (2x)

Ø7(4x)

62 45

50

21

440 595

362

Fan systems/Air/air heat exchangers

T1

D

36.5

133

223.

5

3

C

B2

B = WidthT = Depth

200

32.5

130

135.

5

1

147

36

159

400

1 378

400

1360

280

35 25

295

380

110

325

275

(655

)

1360

25

30.5

75

350

210340

280

400

Ø 13 (8

x)

Ø 30

241

Page 244: Erdinc  klima sk_broschuere_gb

Technical detailsTe

chni

cal d

etai

ls

Air/air heat exchangersWall-mounted, railway-compatible version, specific thermal output 27 – 98 W/K Page 64

Mounting cut-out SK 3126.4xx

External mounting Installation with adjustable frame

280

127

282

244 60

Internal mounting

8

254

107

Adjustment options

Microcellular rubber seal EPDM, black 12 mm, as solid all-round rubber seal

1

Mounting cut-out SK 3128.4xx

External mounting Installation with adjustable frame

27.5 250

400 140

70 250

23

Internal mounting370

0 10

Adjustment options

Microcellular rubber seal EPDM, black 12 mm, as solid all-round rubber seal

1

Air/air heat exchangers

242 Rittal System Climate Control

650

22.5

22.5

600

611

255

Ø 7 (4 x)

(66.

5)23

699

= =

Ø 8 (8 x)

==

520

653

328

57

254

75.5

21.5

Ø 8 (8 x)

74

650

362.

5

105

254

118

105

215

624

17.5

37.5

89.5

109.

5

60 60

84.5

104.

5

127

42.5

22.5

1.5

60

1

27.5

7.5

M6

M6

30

7.5

50

327

950

36.5

180180

280

255

920

385

345

20160

30

50

327

Ø 40 (2 x)

Ø 9.5 (8 x)

999

250

750

953

250

448

402

336

5

160

920190.5

619

127

198

175

175

39.5

39.5 28

Ø 8 (7 x)

70

92.5

112.

5

47.5

27.5

140

250

70

27.5

47.5

92.5

112.

5

50

7.5

30

M6M6

M6

1

7.5

27.5

Page 245: Erdinc  klima sk_broschuere_gb

Technical details

Tech

nica

l det

ails

Air/air heat exchangers

243Rittal System Climate Control

Air/air heat exchangersWall-mounted, railway-compatible version, specific thermal output 27 – 98 W/K Page 64 Mounting cut-out SK 3129.4xxExternal mounting Installation with adjustable frame

Mounting cut-out SK 3130.4xxExternal mounting Installation with adjustable frame

Internal mounting

Adjustment options

Microcellular rubber seal EPDM, black 12 mm, as solid all-round rubber seal

1

25 250

400

327

950

25

210210

280

255

920

385

345

35145

35

50

327

Ø 4

0 (2

x)

Ø 9.5 (8 x)

150

70

250

23

999

250

750

953

250

448

402

400

1580

210

210

65

395

280

380

275

875

340

260

320 1530

Ø 4

0 (1

x)

Ø 1

1 (8

x)

150

70 402

1582

448

250

1480

1628

200

280

260

260

280

200

320

113

205

205

1558

924.

5

97.5

67.5

370

370

400

965

1580

367

215

62.5 200

Ø 1

1 (6

x)

Ø 8

(2 x

)

250

27.5

47.5

102.

5

122.

5 92.5

112.

5

57.5

47.5

15070

70

50

7.5

30

M6M6

M6

1

7.5

27.5

Internal mounting

Adjustment options

Microcellular rubber seal EPDM, black 12 mm, as solid all-round rubber seal

1

370

3036

5

160

10

920190.5

619

127

215

180

180

37

37

19.5

250

27.5

47.5

102.

5

122.

5 92.5

112.

5

57.5

37.5

15070

70

50

7.5

30

M6M6

M6

1

7.5

27.5

Page 246: Erdinc  klima sk_broschuere_gb

Technical detailsTe

chni

cal d

etai

ls

Air/air heat exchangers

244 Rittal System Climate Control

280

550

501

251

18 x 45°

280

(230)

200

254

524

Ø 8 (4x)

Ø 15 (2x)

266

2549

2

518

550

280

550

150 42

108

TopTherm air/air heat exchangers Wall-mounted with controller, specific thermal output 17.5 W/K Page 63

Mounting cut-out for external mounting

Mounting cut-out for internal mounting

Internal mounting

External mounting

400

250

345 280

36.5

235

255

950

15

350

25

Ø 9.5 (8x)

385

350

380

Ø 9.5 (4x)

400

370

R6 (4x) 25

920

920

950

25 x

45°

950

400 205 (225)

50

155 (175)

Wall-mounted with controller, specific thermal output 30 – 60 W/K Page 63

Mounting cut-out for external mounting

Mounting cut-out for internal mounting

External mounting

Internal mounting

Dimensions in brackets for 45 W/K and 60 W/K

280

350

Ø 13 (8x)

400

3529

5

380

1580

260

2587

5

320

275

340

400

370

324

324

Ø 13 (4x)

1558

1554

1538

1580

Ø 12 (2x)

22

R6 (2x)

3761580

400 215 50

165

Wall-mounted with controller, specific thermal output 90 W/K Page 63

Mounting cut-out for external mounting

Mounting cut-out for internal mounting

External mounting

Internal mounting

Page 247: Erdinc  klima sk_broschuere_gb

Technical details

Cooling modulesUseful cooling output 1500/2500 W Page 70

1500 W

2500 W

Section doorsPage 71

For enclosures

600 mm wide

800 mm wide

For enclosures 1200 mm

Device position

Left

Right

Tech

nica

l det

ails

Modular climate control concept

245Rittal System Climate Control

115/135

1561

500

1608

135

85

115

85

135

461

115

461

140

820

145

1777

.5/1

977.

5

592

94

1777

.5/1

977.

5

792

94

1777

.5/1

977.

5

592

94

1777

.5/1

977.

5

592

94

Page 248: Erdinc  klima sk_broschuere_gb

Technical detailsTe

chni

cal d

etai

ls

597 379

Roof-mounted cooling unitsUseful cooling output 500/750 W Page 74

Mounting cut-out

475

597

Condensate discharge 1/2˝, flexible1

597 475

Mounting cut-out

490

597

Useful cooling output 1000 W Page 75

Useful cooling output 1100 W Page 76

Useful cooling output 1500/2000 W Page 77

Condensate discharge 1/2˝, flexible1

Useful cooling output 3000 W Page 76 Mounting cut-out901

Useful cooling output 3000/4000 W Page 78 Mounting cut-out

Condensate discharge 1/2˝, flexible

1

Roof-mounted cooling units

246 Rittal System Climate Control

417

365

Ø 80 30

1

417

326

1701

260

326

379

417

380

Ø 100 27

1

417

420

2801

420

390

475

692

597

392

597

Ø 150

404

511.

5

37

488.5

901

511.

5

470

796

538

Ø 150

38.5

1

580

238Ø 150

1580 52

0

392

796

692

Page 249: Erdinc  klima sk_broschuere_gb

Technical details

Wall-mounted cooling unitsMini in horizontal format, useful cooling output 300 W Page 83

Mounting cut-out for external mounting

Mounting cut-out for internal mounting

External mounting

Internal mounting

153

98

98

Useful cooling output 300 W Page 84

280

Mounting cut-out for external mounting

Mounting cut-out for internal mounting

Internal mounting

External mounting

280

etai

ls

Useful cooling output 500 W Page 84

Useful cooling output 750 W Page 85

Partial internal mounting

External mounting

Internal mounting

Mounting cut-out for external mounting

Mounting cut-out for partial internal mounting

Mounting cut-out for internal mounting

d

T3 l a 280

Tech

nic

T1 T2 T3 T4 T5500 W 210 100 110 164 42750 W 280 125 155 235 42

Wall-mounted cooling units

247Rittal System Climate Control

6

340

27

281

471

525

525

340

55

7.5

5.5

2020

314

325

340

7.5

20

5.5

525

510

499

Ø 7

.5 (4

x)

280

550

140 42

550

501

251

18 x 45°(230)

200

254

524

Ø 8 (4x)

Ø 15 (2x)

266

2549

2

518

550

280

550

T1 T2T5

T4

262

266

280

480

15.5

550

Ø 8 (4x)

532

254

200

18 x 45°

Ø 8 (4x)

(230)

524 266 49

225

518

550

Ø 19 (2x)

254

266

18 x 45

Ø 8 (4x)

(230)

280

524 49

720

523

550

Page 250: Erdinc  klima sk_broschuere_gb

Technical detailsTe

chni

cal d

etai

ls

Wall-mounted cooling units

248 Rittal System Climate Control

950

400

Wall-mounted cooling unitsUseful cooling output 1000/1500 W Page 87

Mounting cut-out for external mounting

Mounting cut-out for internal mounting

Mounting cut-out Partial internal mounting

External mounting

Internal mounting

Partial internal mounting

260

155105 50

210 370

330

Ø 9.5 (4x)

380950

920

920

25 x 45

400

380

Ø 9.5 (4x)

400

370R6 (4x) 25

920

920

950

2

25 x

45

400

250

345

280

36.5

235

255

950

15

350

25

Ø 9.5 (8x)

385

350

1580

400

Useful cooling output 2000/2500 W Page 89

Mounting cut-out for partial internal mounting, internal mounting

Mounting cut-out for external mounting

50

245

150

145

295

400

370

320

320

Ø 13 (4x)

1558

1554

1540

1580

R9.5 (2x)

20

R9.5 (2x)

376

280

350

Ø 13 (10x)

400

3531

0

380

1580

260

2555

0

320

275

340

325

External mounting

Internal mounting1)

Partial internal mounting

1) For installation in 600 mm wide doors, move the mounting cut-out from the centre of the door to the hinged side by at least 10 mm.

500

1580

Useful cooling output 4000 W Page 90

Mounting cut-out for partial internal mounting

Mounting cut-out for external mounting

340 145 195

External mounting

Partial internal mounting

500

362

153015

50

25

474

Ø 13 (4x)

1580

500

380

440

440

Ø 13 (10x)

4533

0

1580

164

360

380

500

375

380

275

25

Page 251: Erdinc  klima sk_broschuere_gb

Technical details

Tech

nica

l det

ails

Wall-mounted cooling units

249Rittal System Climate Control

435

1590

382

12 140

205

4545

1500

Ø 8 (10x)

155

354

340

326

354

240

5526

016

5.5

353

360

85.5

360

353

78.5

354

354

49

1510

400

Wall-mounted cooling unitsUseful cooling output 1500 W Page 88 (SK 3366.XXX and SK 3377.XXX)

Mounting cut-out for external mounting

Mounting cut-out for internal mounting

Internal mounting

External mounting

285

620

238

298

185

285

262

1219

017

217

076

1917

3.5259

220

7014

3.5

620

Ø 8 (8x)

Design NEMA 4x, useful cooling output 500 W Page 91

External mounting Mounting cut-out for external mounting

405

1020

358

245

298

38.5

250

1020

350

93

350

Ø 9.5 (8x)

8338

525

5

345 280

405

250

Design NEMA 4x, useful cooling output 1000/1500 W Page 91

External mounting Mounting cut-out for external mounting

Page 252: Erdinc  klima sk_broschuere_gb

Technical detailsTe

chni

cal d

etai

ls

Wall-mounted cooling unitsDesign NEMA 4x, useful cooling output 2000/2500 W Page 92

External mounting Mounting cut-out

405

for external mounting

Thermoelectric coolerPage 97

155

External mounting

100 55

Internal mounting

Wall-mounted cooling units/Thermoelectric cooler

250 Rittal System Climate Control

405

1650

388

275

328

3731

0

1650

260

408

320

Ø 13 (10x)

550

380

280

350

9327

532

5

125

1100

85

(8.5)

(12.5)

125

108

377

11.5 10 7

25

15

15

25

11

18

25

40

Ø 6.5

Ø 12

400

386

1

377

100

(8.5)

(12.5)

125

10811.5

15

25

Ø 6.5

400

366

25

400

400

100

55

Mounting cut-out for external mounting

Mounting cut-outfor internal mounting

Outer contour of climate control unit 1

Page 253: Erdinc  klima sk_broschuere_gb

Technical details

Air/water heat exchangersRoof-mounted, useful cooling output 2500 W Page 102

Roof-mounted, useful cooling output 4000 W Page 103

Condensate discharge 1/2˝

Cooling water connection 1/2˝

1

2

Micro, wall-mounted, useful cooling output 300 W Page 104

Mounting holes for internal mounting

Mounting cut-out for external mounting

Cooling water connection

Condensate discharge

1

2

Wall-mounted, useful cooling output 600 W Page 105

Mounting holes Mounting cut-out Condensate discharge 1/2˝1

ai

ls

for internal mounting

t

for external mounting

de

Cooling water connection 1/2˝2

Tech

nica

l

Air/water heat exchangers

251Rittal System Climate Control

280

420

475

417

380

Ø 100 (4x)

59727

490

597

390

420475

1 2

85

18

55

1 2

300

150

60

300

276

102

150

Ø 7 (4x)30

0

276

232

41

150

125

102

Ø 7 (4x)

18

75

100

12

80

500

200

420

200

500

150

Ø 7

420

500

170

50

30

133

150

150

160

200

130

145

34 Ø 74x

160

Page 254: Erdinc  klima sk_broschuere_gb

Technical detailsTe

chni

cal d

etai

ls

Air/water heat exchangers

252 Rittal System Climate Control

Ø 7 (4x

)

1192

0

200

140100

18

75

12

80

950

200

175

170 15

475

315

24

126

96

1992

0

950

164

140

Ø 7 (6x)

Air/water heat exchangersWall-mounted, useful cooling output 1250 W Page 105

Mounting holes for internal mounting

Mounting cut-out for external mounting

Condensate discharge 1/2˝

Cooling water connection 1/2˝

1

2

90

550

15

520

4914

250

280

91 14

1

550

280

90 70

2150

2

1

90

550

280

2915

50

140

12

140140

Wall-mounted, useful cooling output 500 W/1000 W Page 106 Mounting cut-out for external mounting

Mounting cut-outfor internal mounting

Ø 6.5 (4 x for internal and external mounting)1

Condensate discharge 1/2˝

Water connections 1/2˝

1

2

Ext

erna

l mou

ntin

g

Inte

rnal

mou

ntin

g

Ext

erna

l mou

ntin

g

Inte

rnal

mou

ntin

g

506

550

2215

520

250

256

2801

Page 255: Erdinc  klima sk_broschuere_gb

Technical details

Tech

nica

l det

ails

Air/water heat exchangers

253Rittal System Climate Control

280

1515

255

385

920

950

36.5

235

250

25

250

400

345

350

Ø9.

5

920

950

250

400

Ø9.

5

4949

91 26

1515

950

400

21 14

0

20

400

50

50

140 140

Air/water heat exchangersWall mounting, useful cooling output 2000 W/3000 W Page 107

Exte

rnal

mou

ntin

g

Inte

rnal

mou

ntin

g

Mounting cut-out for external mounting

Mounting cut-out for internal mounting

Condensate discharge 1/2˝

Water connections 1/2˝

1

2

1400

1400

450

250

100

450

4080

12

1

250 250

Ø9.0

(4x)

1400

350

450

1513

65

492691 49

Wall mounting, useful cooling output 5000 W Page 108

Ext

erna

l mou

ntin

g

Inte

rnal

mou

ntin

g

Mounting cut-out for external mounting

Mounting cut-out for internal mounting

Condensate discharge 1/2˝

Water connections 1/2˝

1

2

455

455

455

350

433.5

Ø7.

0 (8

x)

1400

410

450

420

165

335

15

470

681.

5

Page 256: Erdinc  klima sk_broschuere_gb

Technical detailsTe

chni

cal d

etai

ls

Air/water heat exchangersWall-mounted, useful cooling output 7000 W Page 109

Adaptor framePage 109

450

Condensate discharge 1/2˝

Cooling water connection 1/2˝

1

2

417

Bolts M6 x 20

1

Air/water heat exchangers

254 Rittal System Climate Control

300

100

45018

00

80

21

451

Ø 8 (10x)

350

433.5

350

417

417

442.

5

230

145

442.

544

2.5

442.

5

530

30 15

1655

.1

1740

1800

400

442.

544

2.5

442.

5

400

442.

5

392

433.5

350

380

40

Ø 8 (10x)

1

Page 257: Erdinc  klima sk_broschuere_gb

Technical details

Tech

nica

l det

ails

Cold Plate

255Rittal System Climate Control

94.5 94.562 62 62 62 62

325

399

3737

475

499

272

50 55

1

18

2532

539

937

37

70.5 70.562 62 62 62 62 62 62 62 62

675

699

55

272 24

3

31

31

18

25

1

94.5 94.562 62 62 62 62

325

399

37

475

21

499

50

55575125

1

18

21

378

10.5

10.5

325

399

37

70.5 70.562 62 62 62 62 62 62 62 62

675

699

272 24

3

31

31

55

1

378

10.5

10.5

18

20

Cold PlatePage 112

Cooling water connection 1/4˝1

SK 8616.610, SK 8616.630 SK 8616.810, SK 8616.830

SK 8616.600, SK 8616.620 SK 8616.800, SK 8616.820

Page 258: Erdinc  klima sk_broschuere_gb

Tech

nica

l det

ails

Technical details

Recooling systems

256 Rittal System Climate Control

Options for recooling systems

Pres

sure

-sea

led

syst

em

Ope

n sy

stem

with

tank

Des

igne

d a

s a

once

-thr

oug

h co

oler

with

out t

ank

Hot

gas

byp

ass

cont

rol i

n th

e co

olin

g c

ircui

t

Mor

e po

wer

ful p

ump(

s)

Hea

ter

in th

e ta

nk (1

000

W)

Wat

er le

vel s

witc

h

Flow

mon

itor

Wat

er fi

lter/

oil f

ilter

Wat

er-c

oole

d c

ond

ense

r

Ups

tream

pip

ewor

k, fr

ee fr

om n

on-fe

rrou

s m

etal

s

Aut

omat

ic ta

nk fi

lling

Faul

t sig

nal w

ith in

divi

dual

mes

sage

s

Am

bie

nt te

mp

erat

ure

cont

rol

Aut

omat

ic b

ypas

s

Man

ual b

ypas

s

Har

ting

conn

ecto

r

Out

doo

r siti

ng

Spec

ial s

pray

fini

sh

Spec

ial v

olta

ges

Met

al fi

lter m

at

Cas

tors

Ref

riger

ant R

134a

Dou

ble

pum

p un

it

Filte

r mat

mon

itorin

g

Bas

e tr

ay

Tank

(sta

inle

ss s

teel

1.4

301)

Add

ition

al m

ediu

m c

onne

ctio

ns

Recooling systems Mini and Mini for wall mounting

SK 3318.600 � – – – ▫ – – � – ▫ ▫ – – ▫ – – ▫ – ▫ ▫ ▫ ▫ � – � – – –SK 3318.610 – � – – ▫ – – � – ▫ ▫ – – ▫ – – ▫ – ▫ ▫ ▫ ▫ � – � – – –SK 3319.600 � – – – ▫ – – � – ▫ ▫ – – ▫ – – ▫ – ▫ ▫ ▫ ▫ � – � – – –SK 3319.610 – � – – ▫ – – � – ▫ ▫ – – ▫ – – ▫ – ▫ ▫ ▫ ▫ � – � – – –SK 3320.600 – � – ▫ ▫ – – � – ▫ ▫ – – ▫ ▫ ▫ ▫ – ▫ – ▫ ▫ � – � – – –SK 3334.600 – � – ▫ ▫ – – � – ▫ ▫ – – ▫ ▫ ▫ ▫ – ▫ – ▫ ▫ � – � – – –SK 3334.660 – � – ▫ ▫ – – � – ▫ ▫ – – ▫ ▫ ▫ ▫ – ▫ – ▫ ▫ � – � – – –SK 3360.100 – � – – ▫ – ▫ � – ▫ ▫ – – ▫ – ▫ ▫ – ▫ – ▫ – � – � – – –SK 3360.250 – � – – ▫ – ▫ � – ▫ ▫ – – ▫ – ▫ ▫ – ▫ – ▫ – � – � – – –SK 3360.470 – � – ▫ ▫ – ▫ � – ▫ ▫ – – ▫ – ▫ ▫ – ▫ – ▫ – � – � – – –Recooling systems in floor-standing enclosure and industrial enclosure

SK 3336.100 – � ▫ ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ � – – – � ▫ SK 3336.200 – � ▫ ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ � – – – � ▫ SK 3336.300 – � ▫ ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ � – – – � ▫ SK 3336.500 – � ▫ ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ � – – – � ▫ SK 3336.600 – � ▫ ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ � – – – � ▫ SK 3336.650 – � ▫ ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – ▫ ▫ � – – – � ▫ SK 3336.700 – � ▫ ▫ ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – – � ▫ SK 3336.710 – � ▫ ▫ ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – – � ▫ SK 3336.720 – � ▫ ▫ ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – – � ▫ SK 3336.730 – � ▫ ▫ ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – – � ▫ SK 3336.740 – � ▫ ▫ ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – – � ▫ SK 3336.750 – � ▫ ▫ ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – – � ▫ SK 3339.100 – � ▫ ▫ ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – – � ▫ SK 3339.200 – � ▫ ▫ ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – – � ▫ Recooling systems in a floor standing enclosure for oil

SK 3337.200 – ▫ � ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫ � – ▫ ▫ ▫ ▫ ▫ ▫ � – – – ▫ ▫ SK 3337.300 – ▫ � ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫ � – ▫ ▫ ▫ ▫ ▫ ▫ � – – – ▫ ▫ SK 3337.500 – ▫ � ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫ � – ▫ ▫ ▫ ▫ ▫ ▫ � – – – ▫ ▫ SK 3337.600 – ▫ � ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫ � – ▫ ▫ ▫ ▫ ▫ ▫ � – – – ▫ ▫ SK 3337.650 – ▫ � ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫ � – ▫ ▫ ▫ – ▫ ▫ � – – – ▫ ▫ SK 3337.700 – ▫ � ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫ � – ▫ ▫ ▫ ▫ ▫ ▫ – – – – ▫ ▫ SK 3337.710 – ▫ � ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫ � – ▫ ▫ ▫ ▫ ▫ ▫ – – – – ▫ ▫ SK 3337.720 – ▫ � ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫ � – ▫ ▫ ▫ ▫ ▫ ▫ – – – – ▫ ▫ SK 3337.730 – ▫ � ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫ � – ▫ ▫ ▫ ▫ ▫ ▫ – – – – ▫ ▫ SK 3337.740 – ▫ � ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫ � – ▫ ▫ ▫ ▫ ▫ ▫ – – – – ▫ ▫ SK 3337.750 – ▫ � ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫ � – ▫ ▫ ▫ ▫ ▫ ▫ – – – – ▫ ▫ Recooling systems in the TS 8 Top enclosure system

SK 3335.060 – � – ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3335.075 – � – ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3335.100 – � – ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3335.120 – � – ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3335.150 – � – ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3335.200 – � – ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3335.250 – � – ▫ ▫ ▫ � ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫

� Standard ▫ Optional

Page 259: Erdinc  klima sk_broschuere_gb

Technical details

Tech

nica

l det

ails

Recooling systems

257Rittal System Climate Control

Options for recooling systems

Wat

er-c

oole

d c

ond

ense

r

Rad

ial f

an

Hot

gas

byp

ass

cont

rol i

n th

e co

olin

g c

ircui

t

Har

ting

con

nect

or

Spec

ial s

pray

fini

sh

Spec

ial v

olta

ges

Am

bie

nt te

mp

erat

ure

cont

rol

Con

trol v

olta

ge 2

4 V

DC

Liqu

id in

ject

ion

valv

e

Faul

t sig

nal “

Filte

r m

at d

irty”

Imm

ersi

on d

epth

650

mm

Imm

ersi

on d

epth

750

mm

Imm

ersi

on d

epth

850

mm

Imm

ersi

on d

epth

100

0 m

m

Immersible recooling systems

SK 3338.020 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.040 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.060 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.080 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.100 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.120 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.140 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.160 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.180 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.200 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.220 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.240 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.260 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.280 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.300 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.320 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.340 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.360 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.500 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.520 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.540 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.560 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.580 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.600 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.620 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.640 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.660 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.680 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.700 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.720 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.740 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.760 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.780 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.800 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.820 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ SK 3338.840 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫

▫ Optional

Page 260: Erdinc  klima sk_broschuere_gb

Technical detailsTe

chni

cal d

etai

ls

Recooling systems

258 Rittal System Climate Control

Recooling systems for waterMini, cooling output 1/1.5 W Page 118 Key to the diagram opposite:

CompressorCondenserCondenser fanEvaporator coilExpansion valveFilter dryerFillingVent valveTemperature sensorPumpFlow monitorOverpressure valvePressure relief valve/alternatively tankHigh-pressure switch

5

25

20

35

50

55

61

45

15

1070

1

60

65

P

T

S

Layout diagram1

5

10

15

20

25

35

45

50

55

60

61

65

70 60 Hz

65 7 8 90

35

30

H

Q.

25

20

15

10

5

50 Hz

20.5 4 6 80

35

30

H

Q.

25

20

15

10

5

H = Delivery head H [m] Q = Delivery flow Q [l/min] .

Characteristic curves of pump Model No. SK 3318.600/3318.610/ 3319.600/3319.610

Note:With an externally lockable cooling cycle, a bypass (overpressure valve) should be provided in the external water pipes.

Mini, cooling output 3/4.5 kW Page 119

Mini, cooling output 6 kW Page 120 Key to the diagram opposite:

CompressorCondenserCondenser fanEvaporator coilExpansion valveFilter dryerTankFillingTank drainWater level switch, optionalTemperature sensorPumpFlow monitorHigh-pressure switch

55

4030

60

1

7010

15

5

35

46

50

20

25P

S

Layout diagram1

5

10

15

20

25

30

35

40

46

50

55

60

70

Note:With an externally lockable cooling cycle, a bypass (overpressure valve) should be provided in the external water pipes.

60 Hz

200 40 60 800

10

20

40

30

50

H

Q.

50 Hz

200 40 60 800

10

20

30

40

H

Q.

H = Delivery head H [m] Q = Delivery flow Q [l/min] .

Characteristic curves of pump Model No. SK 3320.600/3334.600/3334.660

Page 261: Erdinc  klima sk_broschuere_gb

Technical details

Tech

nica

l det

ails

Recooling systems

259Rittal System Climate Control

Characteristic curves of pumpModel No. SK 3234.090

Recooling systems for waterPower Fluid Cooler, cooling output 7.5 kW Page 121

Power Fluid Cooler, cooling output 10 to 59 kW Page 122Key to the diagram opposite:

CompressorCondenserCondenser fanEvaporator coilExpansion valveInspection glassMagnetic valveLiquid collectorFilter dryerTankManometerFillingTank drainLevel indicatorPumpFlow monitor (optional)High-pressure switchLow-pressure switchThermostatAnti-frost thermostat

Layout diagram

2022

21

25

23

553031

35

48

40

6015

80

71

705

1

10

81

1

5

10

15

20

21

22

23

25

30

31

35

40

48

55

60

70

71

80

81

50 Hz

200 40 60 800

10

20

30

40

H

Q.

Note:With an externally lockable cooling cycle, a bypass (overpressure valve) should be provided in the external water pipes.

Model No. SK 3234.130/.140/.150

50 Hz

4020 60 80 10018

H

Q.

20

22

24

26

28

30

32

34

36

Model No. SK 3234.160/.170

50 Hz

16014

H

Q.

16

18

20

22

24

26

50 140120958035

Model No. SK 3234.180/.190

50 Hz

25022

H

Q.

24

26

28

30

32

34

36

2101801601301109080

Model No. SK 3234.100/.110/.120

50 Hz

3520 50 65 8010

H

Q.

12

14

16

18

20

22

24

H = Delivery head H [m]Q = Delivery flow Q [l/min].

Page 262: Erdinc  klima sk_broschuere_gb

Technical detailsTe

chni

cal d

etai

ls

Recooling systems

260 Rittal System Climate Control

Recooling systems for waterIn floor-standing enclosure, cooling output 2.1 to 7.7 kW Page 123 Key to the diagram opposite:

CompressorCondenserCondenser fanMulti-coil vaporiserCapillary tube/expansion valve1)

Filter dryerTankManometerFillingTank drainLevel monitor/float-actuated switchLevel indicatorPumpHigh-pressure switch1) Thermostat

1) from SK 3336.500

5

10

25

35

40

48

19

553016 31

1

80

70P

46

Layout diagram1

5

10

16

19

25

30

31

35

40

46

48

55

70

80

Characteristic curve of pump Model No. SK 3336.100/3336.200/3336.300/ 3336.500/3336.600/3336.650

50 Hz

H

Q

20

0

25

30

35

3020 40 50 60.

H = Delivery head H [m] Q = Delivery flow Q [l/min] .

Note:With an externally lockable cooling cycle, a bypass (overpressure valve) should be provided in the external water pipes.

Characteristic curves of pump Model No. SK 3336.700/3336.710/3336.720

In floor-standing enclosure, cooling output 10 to 36 kW Page 124 Key to the diagram opposite:

CompressorCondenserCondenser fanEvaporator coilExpansion valveInspection glassMagnetic valveLiquid collectorFilter dryerTankManometerFillingTank drainLevel indicatorPumpFlow monitorHigh-pressure switchLow-pressure switchThermostat

2022

21

25

23

553031

35

48

40

6015

80

71

705

1

10

Layout diagram1

5

10

15

20

21

22

23

25

30

31

35

40

48

55

60

70

71

80

50 Hz

3520 50 65 80

H

Q

20

25

30

35

40

.

Model No. SK 3336.730/3336.740/3336.750

50 Hz

H

Q

26

.40 8020 60

38

36

34

32

30

28

H = Delivery head H [m] Q = Delivery flow Q [l/min] .

Note:With an externally lockable cooling cycle, a bypass (overpressure valve) should be provided in the external water pipes.

Page 263: Erdinc  klima sk_broschuere_gb

Technical details

Tech

nica

l det

ails

Recooling systems

261Rittal System Climate Control

Recooling systems for waterPower Fluid Cooler, cooling output 68 to 209 kW Page 125 Key to the diagram opposite:

Compressor with oil sump heaterDuo pressure monitor LP/HPCondenser with fanExpansion valveInspection glassMagnetic valveFilter dryerEvaporator coilFlow monitorThermostat Draining ManometerPumpReturn INInlet OUTTankFillingLevel indicatorTemperature sensor

2

10

3

6

78

9

1

4812

14

1718

19

20

68

9

7

3

2

1

21

35 50

13

Layout diagram1

2

3

6

7

8

9

10

12

13

14

17

18

19

20

21

35

48

50

Characteristic curves of pump Model No. SK 3234.200/.210/.220/.230

50 Hz

40014

H

Q.

161820222426283032343638

300250200150100

50 Hz

80012

H

Q.

14161820222426283032

250 700600500400300

50 Hz

80020

H

Q.

222426283032343638404244

700600500400300250

H = Delivery head H [m] Q = Delivery flow Q [l/min] .

Note:With an externally lockable cooling cycle, a bypass (overpressure valve) should be provided in the external water pipes.

Model No. SK 3234.240/.250/.260/.270

Model No. SK 3234.280

Page 264: Erdinc  klima sk_broschuere_gb

Technical detailsTe

chni

cal d

etai

ls

Recooling systems

262 Rittal System Climate Control

Recooling systems for waterPower Fluid Cooler, cooling output 271 to 502 kW Page 126 Key to the diagram opposite:

Compressor with oil sump heaterDuo pressure monitor LP/HPCondenser with fanExpansion valveInspection glassMagnetic valveFilter dryerEvaporator coilSafety assemblyFlow monitorThermostat Draining/fillingPressure relief valveManometerPumpReturn INInlet OUTTank

2

10

3

6

78

9

1

1112

14

15

17

19

2021

68

9

7

3

2

1

FC 18

13

Layout diagram1

2

3

6

7

8

9

10

11

12

13

14

15

17

18

19

20

21

Characteristic curves of pump Model No. SK 3234.290/.300/.310

50 Hz

80028

H

Q.

303234363840424446485052

700600500400300250

50 Hz

140028

H

Q.

303234363840424446485052

12001000800700600500

H = Delivery head H [m] Q = Delivery flow Q [l/min] .

Note:With an externally lockable cooling cycle, a bypass (overpressure valve) should be provided in the external water pipes.

Model No. SK 3234.320/.330/.340

Page 265: Erdinc  klima sk_broschuere_gb

Technical details

Tech

nica

l det

ails

Recooling systems

263Rittal System Climate Control

Recooling systems for waterIn TS 8 Top enclosure system, cooling output 6/7.5 kW Page 127 Key to the diagram opposite:

CompressorCondenserCondenser fanMulti-coil vaporiserExpansion valveInspection glassLiquid collectorFilter dryerTankManometerFixed pump bypassFillingTank drainLevel switchPumpHigh-pressure switchThermostat

333516

47

70

201

80

31

5540

30

21

23

25

10

5

Layout diagram1

5

10

16

20

21

23

25

30

31

33

35

40

47

55

70

80

Characteristic curve of pump Model No. SK 3335.060/3335.075

50 Hz

H = Delivery head H [m]Q = Delivery flow Q [l/min]

3020 40 50 60

H

Q

12

16

20

24

28

.

.

In TS 8 Top enclosure system, cooling output 10 to 25 kW Page 128 Key to the diagram opposite:

CompressorCondenserCondenser fanMulti-coil vaporiserExpansion valveInspection glassLiquid collectorFilter dryerTankManometerFixed pump bypassFillingTank drainLevel switchPumpHigh-pressure switchThermostat

333516

47

70

201

80

31

5540

30

21

23

25

10

5

Layout diagram1

5

10

16

20

21

23

25

30

31

33

35

40

47

55

70

80

Characteristic curves of pump Model No. SK 3335.100/3335.120/3335.150

50 Hz

6030 90 120 150

H

Q

20

26

32

38

44

50

.

50 Hz

2010 30 40 5016

44

40

H

Q.

36

32

28

24

20

H = Delivery head H [m] Q = Delivery flow Q [l/min] .

Model No. SK 3335.200/3335.250

Page 266: Erdinc  klima sk_broschuere_gb

Technical detailsTe

chni

cal d

etai

ls

Recooling systems

264 Rittal System Climate Control

Recooling systems for waterMini, for wall mounting, cooling output 1/2.5/4 kW Page 129 Key to the diagram opposite:

CompressorCondenserCondenser fanEvaporator coilExpansion valveFilter dryerTankFillingTank drainWater level switch, optionalTemperature sensorPumpFlow monitorHigh-pressure switch

5

15

10

1

70

60

55

35

4030

50

46

25

20

P

S

Layout diagram1

5

10

15

20

25

30

35

40

46

50

55

60

70

Characteristic curves of pump Model No. SK 3360.100/3360.250/3360.470

50 Hz

H

Q

0

10

20

30

100 20 30 40.

60 Hz

H

Q

0

10

20

30

40

100 20 30 40.

H = Delivery head H [m] Q = Delivery flow Q [l/min] .

Note:With an externally lockable cooling cycle, a bypass (overpressure valve) should be provided in the external water pipes.

Page 267: Erdinc  klima sk_broschuere_gb

Technical details

Tech

nica

l det

ails

Recooling systems

265Rittal System Climate Control

Recooling systems for oilIn floor-standing enclosure, cooling output 2.5 to 8 kW Page 130 Key to the diagram opposite:

Compressor Automatic bypass valveCondenser Oil pumpCondenser fan Motor for oil pumpEvaporator coil High-pressure switch1) Capillary tube/expansion valve1) ThermostatFilter dryer Anti-frost thermostatManometer

1) from SK 3337.500

5

180

31 56

3257

8119

25

15

10

70P

Layout diagram1 32

5 56

10 57

15 70

19 80

25 81

31

In floor-standing enclosure, cooling output 11 to 26 kW Page 131 Key to the diagram opposite:

Compressor ManometerCondenser Automatic bypass valveCondenser fan Oil pumpEvaporator coil Motor for oil pumpExpansion valve High-pressure switchInspection glass Low-pressure switchMagnetic valve ThermostatLiquid collector Anti-frost thermostatFilter dryer

31

152022

21

25

23

81

1

70

80

71

56

5732

5

10

M

Layout diagram1 31

5 32

10 56

15 57

20 70

21 71

22 80

23 81

25

Immersible recooling systems for oil/emulsion2.4 – 78 kW cooling output Page 132 – 134

Key to the diagram opposite:

CompressorCondenserCondenser fanEvaporator coilExpansion valveInspection glassMagnetic valveLiquid collector

Layout diagram

5

80

70

1

71

30

5082

10

15

23

21

25

2022

1

5

10

15

20

21

22

23

Filter dryerTank, to be supplied by the customerTemperature sensorHigh-pressure switchLow-pressure switchThermostatStirrer

25

30

50

70

71

80

82

Page 268: Erdinc  klima sk_broschuere_gb

Technical detailsTe

chni

cal d

etai

ls

Recooling systems for IT cooling

266 Rittal System Climate Control

Recooling systems for IT cooling15 – 123 kW cooling output Page 148 Key to the diagram opposite:

Compressor with oil sump heaterDuo pressure monitor LP/HPCondenser with fanNon-return valvePressure sensorExpansion valveInspection glassMagnetic valveFilter dryerEvaporator coilSafety assemblyFlow monitorThermostatDraining/fillingPressure relief valveBypass valveManometerPumpReturn INInlet OUTTankRefrigerant collector

2

10

4

6

78

5

9

1

1112

13

14

15 16

17

18

19

2021

22

4

5

3

Controller

FU

FU

PA

PA

FC PI

Layout diagram

2

10

3

4

6

78

5

9

1

1112

13

14

1516

17

18

19

2021

FU

PA

PA

FU

68

9

7

3

2

1

Controller

PI

4 5

FC

Layout diagram

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

Cooling output 145 to 462 kW Page 149 Key to the diagram opposite:

Compressor with oil sump heaterDuo pressure monitor LP/HPCondenser with fanNon-return valvePressure sensorExpansion valveInspection glassMagnetic valveFilter dryerEvaporator coilSafety assemblyFlow monitorThermostatDraining/fillingPressure relief valveBypass valveManometerPumpReturn INInlet OUTTank

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

Page 269: Erdinc  klima sk_broschuere_gb

Technical details

2 420

21

Water/water heat exchangersPage 153

Layout diagram

Key to the diagram opposite:

Temperature sensorPressure transmitterDifferential pressure monitoringFlow gaugeExtension tankSpeed controlled pumpNon-return valveSafety valveAutomatic bleed systemShut-off valveWater filter3-way valvePlate-type heat exchangerPressure reduction valve

1

2

3

4

5

6

7

8

9

10

11

12

13

14

1

1

1

1

1

2

2

2

2

2

2

2

2

2

Automatic bypass valveEmergency water supply heat exchangerWater tankMagnetic filterStandard pumpCustomer Rittal Emergency water supply onPrimary on (onsite)Primary offSecondary on (LCP)Secondary offFillingEmergency water supply off

5

6

7

8

9

0

1

2

3

4

5

6

7

8

tails

Enclosure heatersContinuous thermal output 10 – 800 W Page 169

With fanWithout fan

Without fanModel No. SK W (B) mm H mm D (T) mm

3105.110 81 123 493106.120 81 173 49

de

l

B

Tech

nica

Water/water heat exchangers/enclosure heaters

267Rittal System Climate Control

Option E

Option D

Option COption B

Opt

ion

A

14

1

1

1

1

2 4

2

2

2

2

3

3

5

7

7

7

8

15

9

9

10 10

10 10

10

10

10

10

10

10 10

10 10

1010

10

10

10

12

10

13

16

17

18

11 + 18

6 + 19

28

22

23

24

25

27

26

11

M

H

T

With fan

3115.130 102 155 603116.140 102 225 603107.150 102 260 603107.160 140 205 803102.170 140 250 80

Model No. SK W (B) mm H mm D (T) mm 3105.210 142 170 1013105.220 142 170 1013105.230 142 170 1013105.180 142 170 1013105.190 142 170 1013105.200 142 170 101

B

T

H

Page 270: Erdinc  klima sk_broschuere_gb

Technical detailsTe

chni

cal d

etai

ls

Electronic condensate evaporatorPage 192

SK 3301.560/.580 SK 3301.570/.590

258Ø

378

Condensate hose SK 3301.608 for SK 3302.XXX SK 3301.610 for SK 3303.XXX

Suggestion for position of cable entry

Hose Length as required

1

2

3

Condensate hose SK 3301.612

Suggestion for position of cable entry

Hose Length as required

1

2

3

Integrated louvresPage 183

SK 2541.235 SK 2542.235 SK 2543.235

System accessories

268 Rittal System Climate Control

125

132.

5

42 6

280 400

125

42

132.

5

Ø 6

Ø 6

258

75

5025

1

32

378

45

6025

Ø 6 1

3

2

B

A

140

100

160

50 110

90

4.5

10

1.5

8

10

150

210

190

80 40 100

B

A

1.5

8

4.5

10

4.5

270

330

310

50 110

90

B

A

1.5

8

Page 271: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Notes

269

Not

es

Page 272: Erdinc  klima sk_broschuere_gb
Page 273: Erdinc  klima sk_broschuere_gb

Overview of products and approvals

Cooling with ambient air from page 272Fan-and-filter units ..........................................................................272EMC fan-and-filter units ..................................................................273Rack-mounted fans ........................................................................273Vario rack-mounted fans .................................................................274

Tangential fans ...............................................................................274RTT roof-mounted fan and vent attachment for TS.........................274Roof-mounted fans .........................................................................275Air/air heat exchangers...................................................................276

Cooling units from page 277Cooling modules .............................................................................277Section doors ..................................................................................277Roof-mounted cooling units ............................................................278

Wall-mounted cooling units ...........................................................279Thermoelectric coolers ...................................................................284

Liquid cooling IE from page 284Air/water heat exchangers, roof-mounted .....................................284Air/water heat exchangers, wall-mounted .....................................284Direct Cooling Package .................................................................286

Recooling systems for water ..........................................................287Recooling systems for oil ................................................................290Immersible recooling systems for oil ..............................................290Immersible recooling systems for emulsion ...................................291

Liquid cooling IT from page 292CRAC systems................................................................................292Aisle containment............................................................................293Liquid Cooling Package..................................................................293

Chillers for IT cooling ......................................................................295Water/water heat exchangers.........................................................295

pro

vals

Outdoor climate control from page 296Cooling units for CS modular enclosures .......................................296Heat exchangers for CS modular enclosures.................................296

Climate control units for Toptec CR................................................297

o

f p

rod

uct

s an

d a

p

Enclosure heaters from page 297Enclosure heaters ..........................................................................297

271Rittal System Climate Control

Ove

rvie

w

Page 274: Erdinc  klima sk_broschuere_gb

Ove

rvie

w o

f pro

duct

s an

d ap

prov

als

Overview of products and a

pprovals

272 Rittal System Climate Control

System climate control creates the correct ambient conditions for every application, particularly for sensitive electronics. A broad selection of cooling units, recooling systems, heat exchangers, fan-and-filter units and enclosure heaters protects against adverse physical and thermal influences. This is supplemented by a versatile range of accessory components.

With a full advisory service and its PC software package Rittal Therm, Rittal will help you to select the correct climate control unit to optimally suit your requirements.

Enhanced operational reliability and a longer service life for electronics ● Cooling with ambient air● Cooling units● Liquid cooling IE● Liquid cooling IT● Outdoor climate control● Enclosure heaters

Detailed information may be found on pages 41 – 169 and on our website at www.rittal.com

The latest status of approvals may be found on our website at: www.rittal.com

Fan-and-filter units Air throughput

unimpeded air flowVoltage V, Hz

Model No. SK RAL 7035

ApprovalsPage

UL CUL DIN GS CSA

20/25 m3/h230, 50/60 3321.107 � � 44 115, 50/60 3321.117 � � 44

20 m3/h24 (DC) 3321.027 � � 44 48 (DC) 3321.0471) � � 44

55/66 m3/h230, 50/60 3322.107 � � � 44 115, 50/60 3322.117 � � � 44

55 m3/h24 (DC) 3322.027 � � � 44 48 (DC) 3322.0471) � � 44

105/120 m3/h230, 50/60 3323.107 � � � 45 115, 50/60 3323.117 � � � 45

105 m3/h24 (DC) 3323.027 � � � 45 48 (DC) 3323.0471) � � 45

180/160 m3/h230, 50/60 3324.107 � � � 45 115, 50/60 3324.117 � � � 45

180 m3/h24 (DC) 3324.027 � � � 45 48 (DC) 3324.0471) � � 45

230/265 m3/h230, 50/60 3325.107 � � � 46 115, 50/60 3325.117 � � � 46

230 m3/h24 (DC) 3325.027 � � � 46 48 (DC) 3325.0471) � � 46

550/600 m3/h230, 50/60 3326.107 � � � 47 115, 50/60 3326.117 � � � 47

700/720 m3/h230, 50/60 3327.107 � � 47 115, 50/60 3327.117 � � 47

400/460, 3~, 50/60 3327.147 � � 47 1) Delivery times available on request.

Page 275: Erdinc  klima sk_broschuere_gb

Overview of products and approvals

Ove

rvie

w o

f pro

duct

s an

d ap

prov

als

273Rittal System Climate Control

Fan-and-filter units – EMCAir throughput

unimpeded air flowVoltage V, Hz

Model No. SK RAL 7035

ApprovalsPage

UL CUL DIN GS CSA

20/25 m3/h230, 50/60 3321.607 � � 48 115, 50/60 3321.6171) � � 48

55/66 m3/h230, 50/60 3322.607 � � 48 115, 50/60 3322.6171) � � 48

105/120 m3/h230, 50/60 3323.607 � � � 48 115, 50/60 3323.6171) � � � 48

180/160 m3/h230, 50/60 3324.607 � � � 49 115, 50/60 3324.6171) � � � 49

230/265 m3/h230, 50/60 3325.607 � � � 49 115, 50/60 3325.617 � � � 49

550/600 m3/h230, 50/60 3326.607 � � 49 115, 50/60 3326.6171) � � 49

700/720 m3/h230, 50/60 3327.607 � � 49 115, 50/60 3327.6171) � � 49

1) Delivery times available on request.

Rack-mounted fans Air

throughput unimpeded

air flow

No. of fans

Distance between

axes mm

Voltage V, Hz

Model No. SK

Approvals

PageUL CUL DIN GS VDE

250 m3/h 3 85 36 (DC) – 72 (DC) 9769.0021) 52

320 m3/h2 85 24 (DC) 3340.0241) � � � 52 2 85 115 (AC), 50/60 3340.1151) � � � 52 2 85 230 (AC), 50/60 3340.230 � � � 52

480 m3/h

3 85 24 (DC) 3341.0241) � � � 52 3 105 24 (DC) 3342.024 � � � 52 3 85 115 (AC), 50/60 3341.115 � � � 52 3 105 115 (AC), 50/60 3342.1151) � � � 52 3 85 230 (AC), 50/60 3341.230 � � � 52 3 105 230 (AC), 50/60 3342.230 � � � 52

3 10524 (DC)

115 – 230 (AC), 50/60

3342.500 � � � 52

1) Delivery times available on request.

Page 276: Erdinc  klima sk_broschuere_gb

Overview of products and approvalsO

verv

iew

of p

rodu

cts

and

appr

oval

s

274 Rittal System Climate Control

Vario rack-mounted fanAir

throughput unimpeded

air flow

No. of fans

Distance between

axes mm

Voltage V, Hz

Model No. SK

Approvals

PageUL CUL DIN GS VDE

320 m3/h2 85 24 (DC) 3350.0241) � � � 52 2 85 115 (AC), 50/60 3350.1151) � � � 52 2 85 230 (AC), 50/60 3350.2301) � � � 52

480 m3/h

3 85 24 (DC) 3351.0241) � � � 52 3 105 24 (DC) 3352.0241) � � � 52 3 85 115 (AC), 50/60 3351.1151) � � � 52 3 105 115 (AC), 50/60 3352.1151) � � � 52 3 85 230 (AC), 50/60 3351.230 � � � 52 3 105 230 (AC), 50/60 3352.230 � � � 52

3 10524 (DC)

115 – 230 (AC), 50/60

3352.500 � � � 52

1) Delivery times available on request.

Tangential fansAir throughput

unimpeded air flow

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

320 m3/h 482.6 x 87.2 x 158115, 50/60 3145.000 53 230, 50/60 3144.000 53

RTT roof-mounted fan and vent attachment for TS

Air throughput unimpeded

air flow

Voltage V, Hz

Required mounting cut-out

W x D mm

Model No. SK

Approvals

PageUL CUL DIN GS CSA

400 m3/h

115, 50/60 475 x 260 3149.410 54 230, 50/60 475 x 260 3149.420 54

400, 3~, 50/60 460, 3~, 60 475 x 260 3149.440 54

800 m3/h

115, 50/60 475 x 260 3149.810 54 230, 50/60 475 x 260 3149.820 54

400, 3~, 50/60 460, 3~, 60 475 x 260 3149.840 54

Without motor 490 x 390 8801.380 54

Page 277: Erdinc  klima sk_broschuere_gb

Overview of products and approvals

Ove

rvie

w o

f pro

duct

s an

d ap

prov

als

275Rittal System Climate Control

Roof-mounted fans Air throughput

unimpeded air flow

Voltage V, Hz

Required mounting cut-out

W x D mmModel No. SK

ApprovalsPage

UL CUL DIN GS CSA

360 m3/h230, 50/60 345 x 265 3149.007 54 115, 50/60 345 x 265 3169.007 54

Without fan motor 345 x 265 3148.007 54

For TS/FR(i) for the office sector

Air throughput unimpeded

air flow

Voltage V, Hz

DesignDimensions W x H x D

mm

Model No. SK

Approvals

Pagewith roof plate

without roof plate

UL CUL DIN GS CSA

1500 m3/h115, 50/60 � 800 x 240 x 800 3164.610 55 230, 50/60 � 800 x 240 x 800 3164.620 55

1500 m3/h115, 50/60 � 800 x 240 x 900 3164.810 55 230, 50/60 � 800 x 240 x 900 3164.820 55

1500 m3/h115, 50/60 � 511 x 227 x 511 3164.115 55 230, 50/60 � 511 x 227 x 511 3164.230 55

Page 278: Erdinc  klima sk_broschuere_gb

Overview of products and approvalsO

verv

iew

of p

rodu

cts

and

appr

oval

s

276 Rittal System Climate Control

TopTherm air/air heat exchangersWall-mounted, with controller

Air/air heat exchangersWall-mounted

Wall-mounted, railway-compatible version

Roof-mounted

Specific thermal output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

17.5 W/K 280 x 550 x 150 230, 50/60 3126.100 � � 63 17.5 W/K 280 x 550 x 150 115, 50/60 3126.115 � � 63 30.0 W/K 400 x 950 x 205 230, 50/60 3127.100 � � 63 30.0 W/K 400 x 950 x 205 115, 50/60 3127.115 � � 63 45.0 W/K 400 x 950 x 225 230, 50/60 3128.100 � � 63 45.0 W/K 400 x 950 x 225 115, 50/60 3128.115 � � 63 60.0 W/K 400 x 950 x 225 230, 50/60 3129.100 � � 63 60.0 W/K 400 x 950 x 225 115, 50/60 3129.115 � � 63 90.0 W/K 400 x 1580 x 215 230, 50/60 3130.100 � � 63 90.0 W/K 400 x 1580 x 215 115, 50/60 3130.115 � � 63

Specific thermal output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

12.0 W/K 200 x 400 x 146 230, 50/60 3125.800 62 62.0 W/K 400 x 1360 x 110 230, 50/60 3129.800 62

Specific thermal output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

27.0 W/K 280 x 650 x 127 24 V (DC) 3126.424 64 27.0 W/K 280 x 650 x 127 110 V (DC) 3126.410 64 47.0 W/K 400 x 950 x 140 24 V (DC) 3128.424 64 47.0 W/K 400 x 950 x 140 110 V (DC) 3128.410 64 66.0 W/K 400 x 950 x 150 24 V (DC) 3129.424 64 66.0 W/K 400 x 950 x 150 110 V (DC) 3129.410 64 98.0 W/K 400 x 1580 x 150 24 V (DC) 3130.424 64 98.0 W/K 400 x 1580 x 150 110 V (DC) 3130.410 64

Specific thermal output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

66.0 W/K 595 x 362 x 440 230, 50/60 3248.000 65

Page 279: Erdinc  klima sk_broschuere_gb

Overview of products and approvals

Ove

rvie

w o

f pro

duct

s an

d ap

prov

als

277Rittal System Climate Control

Cooling modules

Section doorsfor installing cooling modules

Useful cooling output Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

1500 W230, 1~, 50/60 3307.700 70 115, 1~, 50/60 3307.710 70

400/460, 3~, 50/60 3307.740 70

2500 W230, 1~, 50/60 3310.700 70 115, 1~, 50/60 3310.710 70

400/460, 3~, 50/60 3310.740 70

For enclosure dimensions W x H mm Model No. SK

ApprovalsPage

UL CUL DIN GS600 x 1800 3300.040 71 600 x 2000 3300.050 71 800 x 1800 3300.060 71 800 x 2000 3300.070 71

12001) x 1800 3300.080 71 12001) x 2000 3300.090 71 12002) x 1800 3300.110 71 12002) x 2000 3300.120 71

1) Unit positioned on the left 2) Unit positioned on the right

TopTherm roof-mounted cooling units Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK ApprovalsPagewith Basic

controllerwith Comfort

controller UL CUL DIN GS CSA

500 W 597 x 417 x 380230, 50/60 3382.100 3382.500 � � � � 74 115, 50/60 3382.110 3382.510 � � � � 74

750 W 597 x 417 x 380230, 50/60 3359.100 3359.500 � � 74 115, 50/60 3359.110 3359.510 � � 74

400, 2~, 50/60 3359.140 3359.540 � � 74

1000 W 597 x 417 x 475230, 50/60 3383.100 3383.500 � � � � 75 115, 50/60 3383.110 3383.510 � � � � 75

400, 2~, 50/60 3383.140 3383.540 � � � � 75

1500 W 597 x 417 x 475230, 50/60 3384.100 3384.500 � � � � 77 115, 50/60 3384.110 3384.510 � � � � 77

400, 2~, 50/60 3384.140 3384.540 � � � � 77

2000 W 597 x 417 x 475230, 50/60 3385.100 3385.500 � � � � 77 115, 50/60 3385.110 3385.510 � � � � 77

400, 2~, 50/60 3385.140 3385.540 � � � � 77

3000 W 796 x 470 x 580 400, 3~, 50 460, 3~, 60 3386.140 3386.540 � � � � 78

4000 W 796 x 470 x 580 400, 3~, 50 460, 3~, 60 3387.140 3387.540 � � � � 78

Roof-mounted cooling units in stainless steel version, see page 278. Delivery times available on request.

Page 280: Erdinc  klima sk_broschuere_gb

Overview of products and approvalsO

verv

iew

of p

rodu

cts

and

appr

oval

s

278 Rittal System Climate Control

TopTherm roof-mounted cooling unitsfor the office sector

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

1100 W 597 x 417 x 475115, 50/60 3273.5151) 76 230, 50/60 3273.500 76

3000 W 597 x 417 x 895 230, 50/60 3301.800 76 1) Delivery times available on request.

Stainless steel

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK ApprovalsPagewith Basic

controllerwith Comfort

controller UL CUL DIN GS CSA

500 W 597 x 415 x 380

230, 50/60 3382.200 3382.600 � 74 115, 50/60 3382.210 3382.610 � 74

750 W 597 x 415 x 380

230, 50/60 3359.200 3359.600 � � 74 115, 50/60 3359.210 3359.610 � � 74

400, 2~, 50/60 3359.240 3359.640 � � 74

1000 W 597 x 417 x 475

230, 50/60 3383.200 3383.600 � � � 75 115, 50/60 3383.210 3383.610 � � � 75

400, 2~, 50/60 3383.240 3383.640 � � � 75

1500 W 597 x 417 x 475

230, 50/60 3384.200 3384.600 � � � 77 115, 50/60 3384.210 3384.610 � � � 77

400, 2~, 50/60 3384.240 3384.640 � � � 77

2000 W 597 x 417 x 475

230, 50/60 3385.200 3385.600 � � � 77 115, 50/60 3385.210 3385.610 � � � 77

400, 2~, 50/60 3385.240 3385.640 � � � 77

3000 W 796 x 470 x 580

400, 3~, 50 460, 3~, 60 3386.240 3386.640 � � � 78

4000 W 796 x 470 x 580

400, 3~, 50 460, 3~, 60 3387.240 3387.640 � � � 78

Delivery times available on request.

With CO2 as the coolant

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK ApprovalsPage

with Basic controller UL CUL DIN GS

1000 W 597 x 417 x 475 230, 50/60 3383.740 79 Delivery times available on request.

Page 281: Erdinc  klima sk_broschuere_gb

Overview of products and approvals

Ove

rvie

w o

f pro

duct

s an

d ap

prov

als

Wall-mounted cooling units VIP small cooling units

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Condenser version Model No. SK

ApprovalsPage

UL CUL DIN GS

225 W 526 x 353.5 x 105 230, 50/60

Left 3201.100 � � 82 Right 3202.100 � � 82

TopTherm wall-mounted cooling unitsMini cooling unit, in horizontal format

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS CSA

300 W 525 x 340 x 153230, 50/60 3302.300 � � � 83

115, 60 3302.310 � � 83

279Rittal System Climate Control

Page 282: Erdinc  klima sk_broschuere_gb

Overview of products and approvalsO

verv

iew

of p

rodu

cts

and

appr

oval

s

TopTherm wall-mounted cooling units Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK ApprovalsPagewith Basic

controllerwith Comfort

controller UL CUL DIN GS CSA

300 W 280 x 550 x 140

230, 50/60 3302.100 – � � � � 84 115, 60 3302.110 – � � � � 84

500 W 280 x 550 x 210

230, 50/60 3303.100 3303.500 � � � � 84 115, 60 3303.110 3303.510 � � � � 84

750 W 280 x 550 x 280

230, 50/60 3361.100 3361.500 � � � 85 115, 60 3361.110 3361.510 � � � 85

400, 2~, 50/60 3361.140 3361.540 � � � 85

1000 W 400 x 950 x 260

230, 50/60 3304.100 3304.500 � � � � 87 115, 50/60 3304.110 3304.510 � � � � 87 400, 3~, 50 460, 3~, 60 3304.140 3304.540 � � � � 87

1500 W 400 x 950 x 260

230, 50/60 3305.100 3305.500 � � � � 87 115, 50/60 3305.110 3305.510 � � � � 87 400, 3~, 50 460, 3~, 60 3305.140 3305.540 � � � � 87

2000 W 400 x 1580 x 295

230, 50/60 3328.100 3328.500 � � � � 89 115, 50/60 3328.110 3328.510 � � � � 89 400, 3~, 50 460, 3~, 60 3328.140 3328.540 � � � � 89

2500 W 400 x 1580 x 295

230, 50/60 3329.100 3329.500 � � � � 89 115, 50/60 3329.110 3329.510 � � � � 89 400, 3~, 50 460, 3~, 60 3329.140 3329.540 � � � � 89

4000 W 500 x 1580 x 340

400, 3~, 50 460, 3~, 60 3332.140 3332.540 � � � � 90

TopTherm wall-mounted cooling units in stainless steel version, see page 281.

Cool Efficiency, up to 45% less energy consumption

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK ApprovalsPagewith Basic

controllerwith Comfort

controller UL CUL DIN GS CSA

1000 W 400 x 950 x 260 230, 1~, 50

3304.700 – 86 – 3304.800 86

280 Rittal System Climate Control

Page 283: Erdinc  klima sk_broschuere_gb

Overview of products and approvals

Ove

rvie

w o

f pro

duct

s an

d ap

prov

als

TopTherm wall-mounted cooling unitsStainless steel

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK ApprovalsPagewith Basic

controllerwith Comfort

controller UL CUL DIN GS CSA

300 W 280 x 550 x 140

230, 50/60 3302.200 – � � � 84 115, 60 3302.210 – � � � 84

500 W 280 x 550 x 210

230, 50/60 3303.200 3303.600 � � � 84 115, 60 3303.210 3303.610 � � � 84

750 W 280 x 550 x 280

230, 50/60 3361.200 3361.600 � � � 85 115, 60 3361.210 3361.610 � � � 85

400, 2~, 50/60 3361.240 3361.640 � � � 85

1000 W 400 x 950 x 260

230, 50/60 3304.200 3304.600 � � � 87 115, 50/60 3304.210 3304.610 � � � 87 400, 3~, 50 460, 3~, 60 3304.240 3304.640 � � � 87

1500 W 400 x 950 x 260

230, 50/60 3305.200 3305.600 � � � 87 115, 50/60 3305.210 3305.610 � � � 87 400, 3~, 50 460, 3~, 60 3305.240 3305.640 � � � 87

2000 W 400 x 1580 x 290

230, 50/60 3328.200 3328.600 � � � 89 115, 50/60 3328.210 3328.610 � � � 89 400, 3~, 50 460, 3~, 60 3328.240 3328.640 � � � 89

2500 W 400 x 1580 x 295

230, 50/60 3329.200 3329.600 � � � 89 115, 50/60 3329.210 3329.610 � � � 89 400, 3~, 50 460, 3~, 60 3329.240 3329.640 � � � 89

4000 W 500 x 1580 x 340

400, 3~, 50 460, 3~, 60 3332.240 3332.640 � � � 90

Delivery times available on request.

Slimline

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK ApprovalsPagewith Basic

controllerwith Comfort

controller UL CUL DIN GS CSA

1500 W 435 x 1590 x 165

230, 50/60 3377.1001) 3377.5001) � � � 88 115, 50/60 3377.1101) 3377.5101) � � � 88

400/460, 3~, 50/60 3377.1401) 3377.5401) � 88

1500 W 450 x 1590 x 205

230, 50/60 3366.100 3366.500 � � � 88 115, 50/60 3366.110 3366.510 � � � 88

400/460, 3~, 50/60 3366.140 3366.540 � 88

1) Delivery times available on request.

281Rittal System Climate Control

Page 284: Erdinc  klima sk_broschuere_gb

Overview of products and approvalsO

verv

iew

of p

rodu

cts

and

appr

oval

s

282 Rittal System Climate Control

TopTherm wall-mounted cooling unitsSlimline, stainless steel

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK ApprovalsPagewith Basic

controllerwith Comfort

controller UL CUL DIN GS CSA

1500 W 450 x 1590 x 165

230, 50/60 3377.200 3377.600 � � � 88 115, 50/60 3377.210 3377.610 � � � 88

400/460, 3~, 50/60 3377.240 3377.640 � 88

1500 W 450 x 1590 x 205

230, 50/60 3366.200 3366.600 � � � 88 115, 50/60 3366.210 3366.610 � � � 88

400/460, 3~, 50/60 3366.240 3366.640 � 88

Delivery times available on request.

Nema 4x design

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK ApprovalsPagewith Basic

controllerwith Comfort

controller UL CUL DIN GS CSA

500 W 285 x 620 x 298230, 50/60 3303.104 3303.504 � � � 91 115, 50/60 3303.114 3303.514 � � � 91

1000 W 405 x 1020 x 358

230, 50/60 3304.104 3304.504 � � � 91 115, 50/60 3304.114 3304.514 � � � 91 400, 3~, 50 460, 3~, 60 3304.144 3304.544 � � � 91

1500 W 405 x 1020 x 358

230, 50/60 3305.104 3305.504 � � � 91 115, 50/60 3305.114 3305.514 � � � 91 400, 3~, 50 460, 3~, 60 3305.144 3305.544 � � � 91

2000 W 405 x 1650 x 388

230, 50/60 3328.104 3328.504 � � � 92 115, 50/60 3328.114 3328.514 � � � 92 400, 3~, 50 460, 3~, 60 3328.144 3328.544 � � � 92

2500 W 405 x 1650 x 388

230, 50/60 3329.104 3329.504 � � � 92 115, 50/60 3329.114 3329.514 � � � 92 400, 3~, 50 460, 3~, 60 3329.144 3329.544 � � � 92

Delivery times available on request.

Page 285: Erdinc  klima sk_broschuere_gb

Overview of products and approvals

Ove

rvie

w o

f pro

duct

s an

d ap

prov

als

283Rittal System Climate Control

TopTherm wall-mounted cooling unitsfor machine tools

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK ApprovalsPagewith Basic

controllerwith Comfort

controller UL CUL DIN GS

1000 W 400 x 950 x 260

400, 3~, 50 460, 3~, 60 3304.142 3304.542 93

1500 W 400 x 950 x 260

400, 3~, 50 460, 3~, 60 3305.142 3305.542 93

Delivery times available on request.

Zone 22 (dust) explosion-proof cooling units

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK ApprovalsPagewith Basic

controllerwith Comfort

controller UL CUL DIN GS

1000 W 400 x 950 x 260

230, 50/60 3304.130 3304.530 94 400, 3~, 50/60 3304.160 3304.560 94

1500 W 400 x 950 x 260

230, 50/60 3305.130 3305.530 94 400, 3~, 50/60 3305.160 3305.560 94

Delivery times available on request.

With CO2 as the coolant

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK ApprovalsPage

with Basic controller UL CUL DIN GS

1000 W 460 x 950 x 260 230, 50/60 3304.740 95 Delivery times available on request.

Page 286: Erdinc  klima sk_broschuere_gb

Overview of products and approvalsO

verv

iew

of p

rodu

cts

and

appr

oval

s

284 Rittal System Climate Control

Thermoelectric coolers Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS CSA

100 W 125 x 400 x 15590 – 264 V (AC) 3201.200 97

24 V (DC) 3201.300 97

TopTherm air/water heat exchangers Roof mounting with Basic/Comfort controller

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK ApprovalsPagewith Basic

controllerwith Comfort

controller UL CUL DIN GS

1875 W2) 597 x 415 x 475230, 50/60 3209.1041) 3209.5041) 102 115, 50/60 3209.1141) 3209.5141) 102

400, 2~, 50/60 3209.1441) 3209.5441) 102

2500 W3) 597 x 415 x 475230, 50/60 3209.100 3209.500 � � 102 115, 50/60 3209.110 3209.510 � � 102

400, 2~, 50/60 3209.1401) 3209.5401) � � 102

3000 W2) 597 x 415 x 475230, 50/60 3210.1041) 3210.5041) 103 115, 50/60 3210.1141) 3210.5141) 103

400, 2~, 50/60 3210.1441) 3210.5441) 103

4000 W3) 597 x 415 x 475230, 50/60 3210.100 3210.500 � � 103 115, 50/60 3210.110 3210.510 � � 103

400, 2~, 50/60 3210.1401) 3210.5401) � � 103 1) Delivery times available on request. 2) All water-carrying parts made from stainless steel V4A (1.4571)3) All water-carrying parts made from CuAl

Air/water heat exchangers Micro, for wall mounting

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

300 W 150 x 300 x 85230, 50/60 3212.230 104 115, 50/60 3212.1151) 104 24 V (DC) 3212.024 104

1) Delivery times available on request.

Page 287: Erdinc  klima sk_broschuere_gb

Overview of products and approvals

Ove

rvie

w o

f pro

duct

s an

d ap

prov

als

285Rittal System Climate Control

Air/water heat exchangers Wall mounting with thermostat-controlled magnetic valve

Wall mounting with Basic/Comfort controller

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK ApprovalsPage

Wall mounting UL CUL DIN GS

600 W 200 x 500 x 100 230, 50/60 3214.100 � � 105 1250 W 200 x 950 x 100 230, 50/60 3215.100 105

7000 W 450 x 1800 x 300 400, 3~, 50/60480, 3~, 60 3216.4801) 109

1) Delivery times available on request.

Useful cooling output

Water-carrying parts Dimensions

W x H x D mm

Rated operating voltage V, Hz

Model No. SK ApprovalsPage

V4A (1.4571) CuAL with Basic

controllerwith Comfort

controller UL CUL DIN GS

375 W � 280 x 550 x 92230, 1~, 50/60 3363.1041) 3363.5041) 106 115, 1~, 50/60 3363.1141) 3363.5141) 106 400, 2~, 50/60 3363.1441) 3363.5441) 106

500 W � 280 x 550 x 92230, 1~, 50/60 3363.100 3363.500 � � 106 115, 1~, 50/60 3363.1101) 3363.5101) � � 106 400, 2~, 50/60 3363.1401) 3363.5401) � � 106

750 W � 280 x 550 x 142230, 1~, 50/60 3364.1041) 3364.5041) 106 115, 1~, 50/60 3364.1141) 3364.5141) 106 400, 2~, 50/60 3364.1441) 3364.5441) 106

1000 W � 280 x 550 x 142230, 1~, 50/60 3364.100 3364.500 � � 106 115, 1~, 50/60 3364.1101) 3364.5101) � � 106 400, 2~, 50/60 3364.1401) 3364.5401) � � 106

1500 W � 400 x 950 x 142230, 1~, 50/60 3373.1041) 3373.5041) 107 115, 1~, 50/60 3373.1141) 3373.5141) 107 400, 2~, 50/60 3373.1441) 3373.5441) 107

2000 W � 400 x 950 x 142230, 1~, 50/60 3373.100 3373.500 � � 107 115, 1~, 50/60 3373.1101) 3373.5101) � � 107 400, 2~, 50/60 3373.1401) 3373.5401) � � 107

2250 W � 400 x 950 x 142230, 1~, 50/60 3374.1041) 3374.5041) 107 115, 1~, 50/60 3374.1141) 3374.5141) � � 107 400, 2~, 50/60 3374.1441) 3374.5441) 107

3000 W � 400 x 950 x 142230, 1~, 50/60 3374.100 3374.500 � � 107 115, 1~, 50/60 3374.1101) 3374.5101) � � 107 400, 2~, 50/60 3374.1401) 3374.5401) � � 107

3750 W � 450 x 1400 x 250230, 1~, 50/60 3375.1041) 3375.5041) � � 108 115, 1~, 50/60 3375.1141) 3375.5141) � � 108 400, 2~, 50/60 3375.1441) 3375.5441) 108

5000 W � 450 x 1400 x 250230, 1~, 50/60 3375.100 3375.500 � � 108 115, 1~, 50/60 3375.1101) 3375.5101) � � 108 400, 2~, 50/60 3375.1401) 3375.5401) � � 108

1) Delivery times available on request.

Page 288: Erdinc  klima sk_broschuere_gb

Overview of products and approvalsO

verv

iew

of p

rodu

cts

and

appr

oval

s

286 Rittal System Climate Control

Direct Cooling Package Cold Plate for frequency converters

Cooling output1)

For installation inDimensions W x H x D

mm

Model No. DCP Approvals

PageEnclosure width mm

Enclosure depth

(side) mm

Without T-slot

With T-slot UL CUL DIN GS TÜV

2500 W 600 600 499 x 399 x 25 8616.610 8616.6002) � 112 2500 W 600 600 499 x 399 x 25 8616.630 8616.6202) � 112 3000 W 800 800 699 x 399 x 25 8616.810 8616.8002) � 112 3000 W 800 800 699 x 399 x 25 8616.830 8616.8202) � 112 5000 W 1000 1000 899 x 399 x 25 8616.010 8616.0002) 112 5000 W 1000 1000 899 x 399 x 25 8616.030 8616.0202) 112 6000 W 1200 – 1099 x 399 x 25 8616.210 8616.2002) 112 6000 W 1200 – 1099 x 399 x 25 8616.230 8616.2202) 112

1) With 25°C fluid inlet temperature,Tu = 40°C and DCP surface temperature = 40°C. 2) Versions with T-slot are 20 mm deep.

Cold Plate for frequency converters, manufacturer-specific

For installation in Dimensions W x H x D

mmModel No. DCP

ApprovalsPageEnclosure width

mmEnclosure depth

mm UL CUL DIN GS TÜV

Suitable for Siemens SINAMICS S210 Booksize

600 600 499 x 449 x 20 8616.640 � 113 600 600 499 x 449 x 20 8616.6411) � 113 800 800 699 x 449 x 20 8616.840 � 113 800 800 699 x 449 x 20 8616.8411) � 113

Suitable for Danfoss VLT® Automation Drive FC300

600 600 499 x 299 x 20 8616.6501) 113 600 600 499 x 299 x 20 8616.6511) 113 800 800 699 x 299 x 20 8616.8501) 113 800 800 699 x 299 x 20 8616.8511) 113

1) Delivery times available on request.

Cooling Unit

PowerDimensions W x H x D

mm

Model No. DCP ApprovalsPage

Add-on Stand-alone UL CUL DIN GS

400 W 252 x 572 x 205 8616.500 – 114 800 W 252 x 572 x 205 8616.5101) – 114 500 W 252 x 572 x 205 – 8616.5502) 114 900 W 252 x 572 x 205 – 8616.5602) 114

1) Space required behind the DCP = 110 mm 2) Cooling Unit as stand-alone with its own fluid connection (2 x G 1/4˝). Delivery times available on request.

Page 289: Erdinc  klima sk_broschuere_gb

Overview of products and approvals

Ove

rvie

w o

f pro

duct

s an

d ap

prov

als

287Rittal System Climate Control

Direct Cooling PackagePanel Cooling

PowerDimensions W x H x D

mm

Model No. DCP ApprovalsPage

Stand-alone UL CUL DIN GS

150 W 300 x 250 x 50 8616.300 115 350 W 400 x 300 x 60 8616.310 115

Delivery times available on request.

TopTherm recooling systems for waterMini

Cooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

1.0 kW 600 x 400 x 430 230, 50/603318.600 � 118 3318.610 � 118

1.5 kW 600 x 400 x 430 230, 50/603319.600 � 118 3319.610 � 118

3.0 kW 602 x 676 x 645 400, 3~, 50/60/ 460, 3~, 60 3320.600 � 119

4.5 kW 602 x 676 x 645 400, 3~, 50/60/ 460, 3~, 60 3334.600 � 119

6.0 kW 602 x 1050 x 645

400, 3~, 50/60/ 460, 3~, 60 3334.660 � 120

Page 290: Erdinc  klima sk_broschuere_gb

Overview of products and approvalsO

verv

iew

of p

rodu

cts

and

appr

oval

s

288 Rittal System Climate Control

TopTherm recooling systems for waterPower Fluid Cooler

Cooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

7.5 kW 595 x 1305 x 800 400, 3~, 50 3234.090 121 10.0 kW 655 x 1280 x 1160 400, 3~, 50 3234.100 122 14.0 kW 655 x 1280 x 1160 400, 3~, 50 3234.110 122 16.0 kW 655 x 1280 x 1160 400, 3~, 50 3234.120 122 19.0 kW 755 x 1280 x 1360 400, 3~, 50 3234.130 122 21.0 kW 755 x 1280 x 1360 400, 3~, 50 3234.140 122 25.0 kW 755 x 1280 x 1360 400, 3~, 50 3234.150 122 32.0 kW 855 x 1500 x 1560 400, 3~, 50 3234.160 122 36.0 kW 855 x 1500 x 1560 400, 3~, 50 3234.170 122 47.0 kW 1040 x 1700 x 2000 400, 3~, 50 3234.180 122 59.0 kW 1040 x 1700 x 2000 400, 3~, 50 3234.190 122

Recooling systems for water In a floor standing enclosure

Cooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS TÜV

2.1 kW 470 x 725 x 540 400, 3~, 50/460, 3~, 60 3336.100 � 123

2.6 kW 485 x 965 x 650 400, 3~, 50/460, 3~, 60 3336.200 � 123

3.4 kW 485 x 965 x 650 400, 3~, 50/460, 3~, 60 3336.300 � 123

5.0 kW 595 x 1180 x 800 400, 3~, 50/460, 3~, 60 3336.500 � 123

6.2 kW 595 x 1180 x 800 400, 3~, 50/460, 3~, 60 3336.600 � 123

7.7 kW 595 x 1180 x 800 400, 3~, 50/460, 3~, 60 3336.650 � 123

10.0 kW 615 x 1178 x 1160 400, 3~, 50/460, 3~, 60 3336.700 � 124

14.4 kW 615 x 1178 x 1160 400, 3~, 50/460, 3~, 60 3336.710 � 124

16.3 kW 615 x 1178 x 1160 400, 3~, 50/460, 3~, 60 3336.720 � 124

18.5 kW 715 x 1178 x 1360 400, 3~, 50/460, 3~, 60 3336.730 � 124

20.9 kW 715 x 1178 x 1360 400, 3~, 50/460, 3~, 60 3336.740 � 124

25.2 kW 715 x 1178 x 1360 400, 3~, 50/460, 3~, 60 3336.750 � 124

32.0 kW 815 x 1400 x 1560 400, 3~, 50/460, 3~, 60 3339.100 � 124

36.2 kW 815 x 1400 x 1560 400, 3~, 50/460, 3~, 60 3339.200 � 124

Delivery times available on request.

Page 291: Erdinc  klima sk_broschuere_gb

Overview of products and approvals

Ove

rvie

w o

f pro

duct

s an

d ap

prov

als

289Rittal System Climate Control

Recooling systems for water Power Fluid Cooler

Cooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS TÜV

68.0 kW 1100 x 1606 x 2450 400, 3~, 50 3234.200 125 79.0 kW 1100 x 1606 x 2450 400, 3~, 50 3234.210 125 90.0 kW 1100 x 1606 x 2450 400, 3~, 50 3234.220 125

101.0 kW 1100 x 1606 x 2950 400, 3~, 50 3234.230 125 124.0 kW 1100 x 1875 x 2950 400, 3~, 50 3234.240 125 135.0 kW 1100 x 1875 x 2950 400, 3~, 50 3234.250 125 158.0 kW 1100 x 1875 x 2950 400, 3~, 50 3234.260 125 175.0 kW 1100 x 1875 x 2950 400, 3~, 50 3234.270 125 209.0 kW 1100 x 1875 x 3950 400, 3~, 50 3234.280 125 271.0 kW 2200 x 2450 x 3400 400, 3~, 50 3234.290 126 305.0 kW 2200 x 2450 x 3400 400, 3~, 50 3234.300 126 339.0 kW 2200 x 2450 x 3400 400, 3~, 50 3234.310 126 406.0 kW 2200 x 2450 x 4250 400, 3~, 50 3234.320 126 452.0 kW 2200 x 2450 x 4250 400, 3~, 50 3234.330 126 502.0 kW 2200 x 2450 x 4250 400, 3~, 50 3234.340 126

In the TS 8 Top enclosure system

Cooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS TÜV

6.0 kW 600 x 2150 x 600 400, 3~, 50 3335.060 127 7.5 kW 600 x 2150 x 600 400, 3~, 50 3335.075 127 10.0 kW 800 x 2150 x 600 400, 3~, 50 3335.100 128 12.0 kW 800 x 2150 x 600 400, 3~, 50 3335.120 128 15.0 kW 800 x 2150 x 600 400, 3~, 50 3335.150 128 20.0 kW 1200 x 2150 x 600 400, 3~, 50 3335.200 128 25.0 kW 1200 x 2150 x 600 400, 3~, 50 3335.250 128

Delivery times available on request.

Mini, for wall mounting

Cooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

1.0 kW 400 x 950 x 310 400, 3~, 50/60/ 460, 3~, 60 3360.100 129

2.5 kW 400 x 1580 x 290 400, 3~, 50/60/ 460, 3~, 60 3360.250 129

4.0 kW 500 x 1580 x 390 400, 3~, 50/60/ 460, 3~, 60 3360.470 129

Page 292: Erdinc  klima sk_broschuere_gb

Overview of products and approvalsO

verv

iew

of p

rodu

cts

and

appr

oval

s

290 Rittal System Climate Control

Recooling systems for oil In a floor standing enclosure

Cooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

2.5 kW 485 x 965 x 650 400, 3~, 50 3337.200 130 3.4 kW 485 x 965 x 650 400, 3~, 50 3337.300 130 5.2 kW 595 x 1180 x 800 400, 3~, 50 3337.500 130 6.7 kW 595 x 1180 x 800 400, 3~, 50 3337.600 130 8.0 kW 595 x 1180 x 800 400, 3~, 50 3337.650 130 11.0 kW 615 x 1178 x 1160 400, 3~, 50 3337.700 131 15.5 kW 615 x 1178 x 1160 400, 3~, 50 3337.710 131 17.2 kW 615 x 1178 x 1160 400, 3~, 50 3337.720 131 19.0 kW 715 x 1178 x 1360 400, 3~, 50 3337.730 131 22.0 kW 715 x 1178 x 1360 400, 3~, 50 3337.740 131 26.0 kW 715 x 1178 x 1360 400, 3~, 50 3337.750 131

Delivery times available on request.

Immersible recooling systems for oilCooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

2.4 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.020 132

3.2 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.040 132

4.6 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.060 132

5.6 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.080 132

8.5 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.100 133

10.5 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.120 133

12.0 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.140 133

13.6 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.160 133

15.3 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.180 133

17.3 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.200 133

21.0 kW 785 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.220 134

31.0 kW 785 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.240 134

35.0 kW 785 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.260 134

46.0 kW 1830 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.280 134

49.0 kW 1830 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.300 134

61.0 kW 1830 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.320 134

73.0 kW 1830 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.340 134

78.0 kW 1830 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.360 134

Delivery times available on request.

Page 293: Erdinc  klima sk_broschuere_gb

Overview of products and approvals

Ove

rvie

w o

f pro

duct

s an

d ap

prov

als

291Rittal System Climate Control

Immersible recooling systems for emulsionCooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

2.4 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.500 132

3.2 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.520 132

4.6 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.540 132

5.6 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.560 132

8.5 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.580 133

10.5 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.600 133

12.0 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.620 133

13.6 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.640 133

15.3 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.660 133

17.3 kW 785 x 1650 x 785 400, 3~, 50 460, 3~, 60 3338.680 133

21.0 kW 785 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.700 134

31.0 kW 785 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.720 134

35.0 kW 785 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.740 134

46.0 kW 1830 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.760 134

49.0 kW 1830 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.780 134

61.0 kW 1830 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.800 134

73.0 kW 1830 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.820 134

78.0 kW 1830 x 1650 x 1830 400, 3~, 50 460, 3~, 60 3338.840 134

Delivery times available on request.

Page 294: Erdinc  klima sk_broschuere_gb

Overview of products and approvalsO

verv

iew

of p

rodu

cts

and

appr

oval

s

CRAC systems Without heater

With heater

With humidifier

With heater and humidifier

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK Approvals PageWithout

heater UL CUL DIN GS

23 kW 1100 x 1950 x 650 400/50 3301.620 138 39 kW 1100 x 1950 x 850 400/50 3301.660 138 78 kW 1800 x 1950 x 850 400/50 3301.830 138

118 kW 2600 x 1950 x 850 400/50 3301.870 138 18 kW 1100 x 1950 x 850 400/50 3300.510 138 30 kW 1100 x 1950 x 850 400/50 3300.560 138 43 kW 1400 x 1950 x 850 400/50 3300.710 138 54 kW 1800 x 1950 x 850 400/50 3300.760 138

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK Approvals PageWith

heater UL CUL DIN GS

23 kW 1100 x 1950 x 650 400/50 3301.630 138 39 kW 1100 x 1950 x 850 400/50 3301.670 138 78 kW 1800 x 1950 x 850 400/50 3301.840 138

118 kW 2600 x 1950 x 850 400/50 3301.880 138 18 kW 1100 x 1950 x 850 400/50 3300.520 138 30 kW 1100 x 1950 x 850 400/50 3300.570 138 43 kW 1400 x 1950 x 850 400/50 3300.720 138 54 kW 1800 x 1950 x 850 400/50 3300.770 138

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK Approvals PageWith

humidifier UL CUL DIN GS

23 kW 1100 x 1950 x 650 400/50 3301.640 138 39 kW 1100 x 1950 x 850 400/50 3301.680 138 78 kW 1800 x 1950 x 850 400/50 3301.850 138

118 kW 2600 x 1950 x 850 400/50 3301.890 138 18 kW 1100 x 1950 x 850 400/50 3300.530 138 30 kW 1100 x 1950 x 850 400/50 3300.580 138 43 kW 1400 x 1950 x 850 400/50 3300.730 138 54 kW 1800 x 1950 x 850 400/50 3300.780 138

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK Approvals PageWith heater

and humidifier UL CUL DIN GS

23 kW 1100 x 1950 x 650 400/50 3301.650 138 39 kW 1100 x 1950 x 850 400/50 3301.690 138 78 kW 1800 x 1950 x 850 400/50 3301.860 138

118 kW 2600 x 1950 x 850 400/50 3301.990 138 18 kW 1100 x 1950 x 850 400/50 3300.540 138 30 kW 1100 x 1950 x 850 400/50 3300.590 138 43 kW 1400 x 1950 x 850 400/50 3300.740 138 54 kW 1800 x 1950 x 850 400/50 3300.790 138

292 Rittal System Climate Control

Page 295: Erdinc  klima sk_broschuere_gb

Overview of products and approvals

Ove

rvie

w o

f pro

duct

s an

d ap

prov

als

Aisle containment Model No. SK Approvals

PageUL CUL DIN GS

Roof element 3300.170 3300.180 – 139 Door element – – 3300.160 139 Width of element (identical to enclosure width), mm 600 800 –

Width of cold aisle mm 1200 1200 1200Height of cold aisle mm – – 2000

Liquid Cooling PackageLCP Standard

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

Approvals Page

UL CUL GS

Up to 20 kW 300 x 2000 x 1000 230, 50/60 3301.230 � � � 141 Up to 20 kW 300 x 2000 x 1000 115, 50/60 3301.210 � � � 141 Up to 20 kW 300 x 2000 x 1200 230, 50/60 3301.420 141

LCP Plus

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

Approvals Page

UL CUL GS

Up to 30 kW 300 x 2000 x 1200 230, 50/60 3301.4801) � � � 142 Up to 40 kW 300 x 2400 x 1200 230, 50/60 on request 142

1) Delivery times available on request.

293Rittal System Climate Control

Page 296: Erdinc  klima sk_broschuere_gb

Overview of products and approvalsO

verv

iew

of p

rodu

cts

and

appr

oval

s

Liquid Cooling PackageLCP Extend

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

Approvals Page

UL CUL GS

12 kW 520 x 1910 x 160 230, 50/60 3301.4901) � 143 1) Delivery times available on request.

LCP Smart

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz

Model No. SK

Approvals Page

UL CUL GS

Up to 20 kW 300 x 2000 x 1000 200 – 230, 1~, 50/60 400, 3~, 50/60 3301.460 144

LCP Inline

Useful cooling output

Dimensions W x H x D

mm

Voltage V, Hz Model No. SK

Approvals Page

UL CUL DIN GS

Up to 30 kW1) 300 x 2000 x 1200 230, 1~, 50/60 400, 3~, 50/60 3301.470 145

1) Achievable with 15°C cold water inlet temperature, volumetric flow 35 l/min and ΔT of 20°C on the air side.

294 Rittal System Climate Control

Page 297: Erdinc  klima sk_broschuere_gb

Overview of products and approvals

Ove

rvie

w o

f pro

duct

s an

d ap

prov

als

Chillers for IT cooling

Cooling outputDimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

15.0 kW 815 x 1400 x 1560 400, 3~, 50 3232.700 148 24.0 kW 815 x 1400 x 1560 400, 3~, 50 3232.710 148 35.0 kW 815 x 1400 x 1560 400, 3~, 50 3232.720 148 48.0 kW 1000 x 2180 x 2000 400, 3~, 50 3232.730 148 61.0 kW 1100 x 1606 x 2450 400, 3~, 50 3232.740 148 72.0 kW 1100 x 1606 x 2450 400, 3~, 50 3232.750 148 82.0 kW 1100 x 1606 x 2450 400, 3~, 50 3232.760 148 92.0 kW 1100 x 1606 x 2950 400, 3~, 50 3232.770 148

113.0 kW 1100 x 1875 x 2950 400, 3~, 50 3232.780 148 123.0 kW 1100 x 1875 x 2950 400, 3~, 50 3232.790 148 145.0 kW 1100 x 1875 x 2950 400, 3~, 50 3232.800 149 161.0 kW 1100 x 1875 x 2950 400, 3~, 50 3232.810 149 193.0 kW 1100 x 1875 x 3950 400, 3~, 50 3232.820 149 248.0 kW 2200 x 2450 x 3400 400, 3~, 50 3232.830 149 280.0 kW 2200 x 2450 x 3400 400, 3~, 50 3232.840 149 312.0 kW 2200 x 2450 x 3400 400, 3~, 50 3232.850 149 372.0 kW 2200 x 2450 x 4250 400, 3~, 50 3232.860 149 415.0 kW 2200 x 2450 x 4250 400, 3~, 50 3232.870 149 462.0 kW 2200 x 2450 x 4250 400, 3~, 50 3232.880 149

Delivery times available on request.

Water/water heat exchangers

Cooling outputDimensions W x H x D

mm

Voltage V, Hz Model No. SK

ApprovalsPage

UL CUL DIN GS

25.0 kW 1200 x 1900 x 800 400, 3~, 50 3232.900 153 50.0 kW 1200 x 1900 x 800 400, 3~, 50 3232.910 153 75.0 kW 1200 x 1900 x 800 400, 3~, 50 3232.920 153

100.0 kW 1200 x 1900 x 800 400, 3~, 50 3232.930 153 150.0 kW 1200 x 1900 x 800 400, 3~, 50 3232.940 153 200.0 kW 2000 x 1900 x 800 400, 3~, 50 3232.950 153 250.0 kW 2000 x 1900 x 800 400, 3~, 50 3232.960 153

Delivery times available on request.

295Rittal System Climate Control

Page 298: Erdinc  klima sk_broschuere_gb

Overview of products and approvalsO

verv

iew

of p

rodu

cts

and

appr

oval

s

Cooling units for CS modular enclosures

Approvals CS 9761.032: ● UL ● C-UL

Dimensions W x H x D

mm

Mounting position

Useful cooling output EN 814 Rated operating

voltageModel No.

CS PageL35 L35 L35 L50

535 x 390 x 400 Roof mounting 900 W 750 W 230 V AC, 50/60 Hz 9762.012 160 430 x 1070 x 210 Door mounting 900 W 650 W 230 V AC, 50/60 Hz 9768.100 160

515 x 1170 x 151.5 Wall mounting 900 W 750 W 230 V AC, 50/60 Hz 9761.012 160 695 x 1132 x 151.5 Wall mounting 1400 W 1050 W 230 V AC, 50/60 Hz 9761.032 160 776 x 1100 x 250 Wall mounting 2500 W 2000 W 230 V AC, 50/60 Hz 9761.042 160 400 x 1050 x 310 Universal built-in 1500 W 1250 W 230 V AC, 50/60 Hz 9768.150 160

Delivery times available on request.

Heat exchangers for CS modular enclosures Dimensions W x H x D

mm

Mounting position

Specific thermal output

Heater1) Rated operating voltage Model No. CS Page

470 x 158 x 380 Roof mounting 30 W/K without 48 V DC 9764.040 161 535 x 390 x 400 Roof mounting 60 W/K 400 W 48 V DC 9764.012 161

515 x 1170 x 151.5 Wall mounting 60 W/K 400 W 48 V DC 9763.012 161 480 x 1005 x 110 Door mounting 40 W/K 400 W 48 V DC 9768.032 162 510 x 1005 x 150 Door mounting 60 W/K 400 W 48 V DC 9768.012 162 445 x 1050 x 150 Door mounting 85 W/K without 48 V DC 9768.042 162 575 x 1050 x 195 Door mounting 120 W/K without 48 V DC 9768.062 162

1) Rated operating voltage 230 V AC, 50/60 Hz Delivery times available on request.

296 Rittal System Climate Control

Page 299: Erdinc  klima sk_broschuere_gb

Overview of products and approvals

Ove

rvie

w o

f pro

duct

s an

d ap

prov

als

Climate control units for Toptec CR

Dimensions W x H x D

mmInstallation

Useful cooling output EN 814

Specific thermal output

Rated operating voltage

Model No. CS Page

L35 L35 L35 L50

Heat exchangers

500 x 1000 x 150 Universal built-in – – 85 W/K 48 V DC 9776.100 163

500 x 1000 x 200 Universal built-in – – 105 W/K 48 V DC 9776.150 163

Cooling units

500 x 1000 x 150 Universal built-in 1000 W 650 W – 230 V AC, 50/60 Hz 9776.500 163

500 x 1000 x 260 Universal built-in 1600 W 1200 W – 230 V AC, 50/60 Hz 9776.550 163

Delivery times available on request.

Enclosure heatersWithout fan

With fan

Continuous thermal output at Tu = 10°C

Voltage Volt Model No. SK

ApprovalsPage

UL CUL DIN GS VDE

10 W 100 – 240 (AC/DC) 3105.110 169 20 W 100 – 240 (AC/DC) 3106.120 169 30 W 100 – 240 (AC/DC) 3115.130 169 50 W 100 – 240 (AC/DC) 3116.140 169 75 W 100 – 240 (AC/DC) 3107.150 169 100 W 100 – 240 (AC/DC) 3107.160 169 150 W 100 – 240 (AC/DC) 3102.170 169

Continuous thermal output at Tu = 10°C

Voltage Volt

Model No. SK ApprovalsPage

110 V 230 V UL CUL DIN GS VDE

250 W1) 115 or 240 (AC/DC) 3105.210 3105.180 169 400 W1) 115 or 240 (AC/DC) 3105.220 3105.190 169 800 W1) 115 or 240 (AC/DC) 3105.230 3105.200 169

1) Output with fan.

297Rittal System Climate Control

Page 300: Erdinc  klima sk_broschuere_gb

ServiceRittal Global Service – for system

298

climate control

A central point of contact, decentralised implementation, short response times – this is the successful concept

behind Rittal Global Service. High-tech system climate control must offer a permanently high level of reliability

in enclosure cooling as well as in machine and process cooling.

With this in mind, we offer fast and reliable response times worldwide – thanks to our network of local service

engineers.

Customer satisfaction from the outset

Pre-Sales We face up to our responsibilities

● Requirement analysis ● Load tests● Thermal imaging● Simulation and calculation

Implementation Because we are pleased to be on board when you arrive at a solution.

● Installation/integration ● Commissioning ● Instruction ● Certification

After-SalesWe smooth the way for your decision.

● Service contracts ● Maintenance/servicing● Repairs● Spare parts management● Training

Rittal Global Service – always on hand, whenever you need us!

Our worldwide Rittal Global Service hubs

Europe: [email protected] Tel. +49(0)2772 5051855

North America: [email protected] Tel. +1800 477 4000

South America: [email protected] Tel. +55 11 36 22 23 77

China: [email protected] Tel. +86 800 820 0866

India: [email protected] Tel. +91 80 22 890 783

� Five global service support points in the world's major economic hubs

� Over 60 other service sites with

� more than 250 qualified partners and our own technical specialists, worldwide!

Rittal System Climate Control

Page 301: Erdinc  klima sk_broschuere_gb

Rittal System Climate Control

Service

Rittal climate checks

Service packages for every aspect of system climate control

Load tests482.6 mm (19˝) slide-in equipment which simu-lates the thermodynamic response of servers allows you to determine in advance whether your cooling system is adequate for any planned extensions. Furthermore, after installing the LCP family, the cooling response can be tested directly, without the presence of a server.

Load tests as the optimum basis for planning.

Intelligent wireless sensor technologySensors the size of a button record the tempera-ture and humidity at specified locations in the rack. The location and time-dependent readings are extracted and displayed. The result is a 3D analysis of the data centre's cooling response.

With sensor technology for 3D analyses.

Piping network calculationThe Rittal specialists use a software package to design and dimension the pipe networks of liquid cooling systems, taking into consideration the architectural conditions. The specifications cre-ated allow the local installation engineer to start work immediately.

Perfect dimensioning of pipe networks.

CFD (Computational Fluid Dynamics)A 3D computer simulation is used to visualise the thermodynamic response of the planned data centre with server racks and climate control system. Predicting the temperature, speed, pres-sure and hence flow conditions in the data centre facilitates fast response times.

Forward planning with CFD.

ThermographyUsing a thermal imaging camera illustrates the temperature conditions (surface) inside the data centre with colour coding, hot-spots can be located and eliminated.

Localisation of hot-spots via thermography.

299

Page 302: Erdinc  klima sk_broschuere_gb

List of model numbers2102.180 to 3302.110

Model No. Page2102.180 582102.190 582102.320 582102.400 582102.410 582102.490 582541.235 1832542.235 1832543.235 1833102.170 1693105.110 1693105.180 1693105.190 1693105.200 1693105.210 1693105.220 1693105.230 1693106.120 1693107.150 1693107.160 1693108.024 553108.100 553108.115 553110.000 1783110.200 1783114.024 1773114.100 1773114.115 1773115.130 1693116.140 1693118.000 1783120.000 1793120.115 1793121.000 1953124.000 1803124.100 1803124.200 1793125.800 623126.100 633126.115 633126.410 643126.424 643127.100 633127.115 633128.100 633128.115 633128.410 643128.424 643129.100 633129.115 633129.410 643129.424 643129.800 623130.100 633130.115 633130.410 643130.424 643144.000 533145.000 533148.007 543149.007 543149.410 543149.420 543149.440 543149.810 543149.820 54

3149.840 543159.100 1953164.115 553164.230 553164.610 553164.620 553164.810 553164.820 553165.024 593165.048 593165.115 593165.230 593165.615 593165.624 593165.630 593165.648 593165.815 593165.824 593165.830 593165.848 593169.007 543171.100 1913172.100 1913173.100 1913174.000 1913175.000 1943176.000 1933177.000 1893181.100 1913182.100 1913183.100 1913201.030 1923201.050 1913201.100 823201.200 973201.300 973202.100 823209.100 1023209.104 1023209.110 1023209.114 1023209.140 1023209.144 1023209.500 1023209.504 1023209.510 1023209.514 1023209.540 1023209.544 1023210.100 1033210.104 1033210.110 1033210.114 1033210.140 1033210.144 1033210.500 1033210.504 1033210.510 1033210.514 1033210.540 1033210.544 1033212.024 1043212.115 1043212.230 1043213.300 1763213.310 176

Model No. Page3213.320 1763213.330 1763214.100 1053215.100 1053216.470 1093216.480 1093232.700 1483232.710 1483232.720 1483232.730 1483232.740 1483232.750 1483232.760 1483232.770 1483232.780 1483232.790 1483232.800 1493232.810 1493232.820 1493232.830 1493232.840 1493232.850 1493232.860 1493232.870 1493232.880 1493232.900 1533232.910 1533232.920 1533232.930 1533232.940 1533232.950 1533232.960 1533234.090 1213234.100 1223234.110 1223234.120 1223234.130 1223234.140 1223234.150 1223234.160 1223234.170 1223234.180 1223234.190 1223234.200 1253234.210 1253234.220 1253234.230 1253234.240 1253234.250 1253234.260 1253234.270 1253234.280 1253234.290 1263234.300 1263234.310 1263234.320 1263234.330 1263234.340 1263248.000 653253.000 1893253.010 1893253.200 1903253.220 1903254.000 1893254.200 1903267.100 189

Model No. Page3267.200 1903273.500 763273.515 763284.200 1903284.210 1903285.000 1893285.200 1903286.000 1893286.100 1893286.110 1893286.120 1903286.200 1903286.210 1903286.230 1903286.240 1903286.250 1903286.260 1833286.270 1833286.280 1833286.300 1893286.310 1903286.400 1893286.410 1903286.500 1893286.510 1903286.520 1903286.600 1893286.610 1903286.700 1823286.780 1753286.800 1823286.850 1753286.860 1753286.870 1743286.880 1753286.900 1823286.970 1743286.980 1753286.990 1743288.200 1903289.200 1903294.100 1893294.200 1903300.040 713300.050 713300.060 713300.070 713300.080 713300.090 713300.110 713300.120 713300.160 139, 2933300.170 139, 2933300.180 139, 2933300.510 1383300.520 1383300.530 1383300.540 1383300.560 1383300.570 1383300.580 1383300.590 1383300.710 1383300.720 1383300.730 1383300.740 138

Model No. Page3300.760 1383300.770 1383300.780 1383300.790 1383301.210 1413301.221 1883301.230 1413301.250 1863301.290 1863301.310 1873301.320 1863301.330 1873301.340 1873301.350 1883301.351 1883301.360 1883301.370 1863301.380 1863301.390 1863301.400 1883301.420 1413301.421 1883301.460 1443301.470 1453301.480 1423301.490 1433301.560 1923301.570 1923301.580 1923301.590 1923301.600 1923301.608 1923301.610 1923301.612 1923301.620 1383301.630 1383301.640 1383301.650 1383301.660 1383301.670 1383301.680 1383301.690 1383301.790 1863301.800 763301.830 1383301.840 1383301.850 1383301.860 1383301.870 1383301.880 1383301.890 1383301.900 1943301.910 1943301.920 1943301.930 1943301.940 1943301.950 1943301.955 1943301.957 1943301.960 1943301.965 1943301.967 1943301.980 1863301.990 1383302.100 843302.110 84

Model No. Page

300 Rittal System Climate Control

Page 303: Erdinc  klima sk_broschuere_gb

List of model numbers3302.200 to 3366.540

3302.200 843302.210 843302.300 833302.310 833303.100 843303.104 913303.110 843303.114 913303.200 843303.210 843303.500 843303.504 913303.510 843303.514 913303.600 843303.610 843304.100 86, 873304.104 913304.110 873304.114 913304.130 943304.140 873304.142 933304.144 913304.160 943304.200 873304.210 873304.240 873304.500 86, 873304.504 913304.510 873304.514 913304.530 943304.540 873304.542 933304.544 913304.560 943304.600 873304.610 873304.640 873304.700 863304.740 953304.800 863305.100 873305.104 913305.110 873305.114 913305.130 943305.140 873305.142 933305.144 913305.160 943305.200 873305.210 873305.240 873305.500 873305.504 913305.510 873305.514 913305.530 943305.540 873305.542 933305.544 913305.560 943305.600 873305.610 87

Model No. Page3305.640 873307.700 703307.710 703307.740 703310.700 703310.710 703310.740 703318.600 1183318.610 1183319.600 1183319.610 1183320.600 1193321.027 443321.047 443321.107 443321.117 443321.207 1933321.267 483321.607 483321.617 483321.700 1913321.800 1933322.027 443322.047 443322.107 443322.117 443322.207 1933322.267 483322.607 483322.617 483322.700 1913322.800 1933323.027 453323.047 453323.107 453323.117 453323.207 1933323.267 483323.607 483323.617 483323.800 1933324.027 453324.047 453324.107 453324.117 453324.607 493324.617 493324.800 1933325.027 463325.047 463325.107 463325.117 463325.207 1933325.267 493325.607 493325.617 493326.107 473326.117 473326.207 1933326.267 493326.607 493326.617 493326.800 1933327.107 473327.117 473327.147 47

Model No. Page3327.607 493327.617 493327.700 1913328.100 893328.104 923328.110 893328.114 923328.140 893328.144 923328.200 893328.210 893328.240 893328.500 893328.504 923328.510 893328.514 923328.540 893328.544 923328.600 893328.610 893328.640 893329.100 893329.104 923329.110 893329.114 923329.140 893329.144 923329.200 893329.210 893329.240 893329.500 893329.504 923329.510 893329.514 923329.540 893329.544 923329.600 893329.610 893329.640 893329.903 1913329.904 1913332.140 903332.240 903332.540 903332.640 903334.600 1193334.660 1203335.060 1273335.075 1273335.100 1283335.120 1283335.150 1283335.200 1283335.250 1283336.100 1233336.200 1233336.300 1233336.500 1233336.600 1233336.650 1233336.700 1243336.710 1243336.720 1243336.730 1243336.740 1243336.750 124

Model No. Page3337.200 1303337.300 1303337.500 1303337.600 1303337.650 1303337.700 1313337.710 1313337.720 1313337.730 1313337.740 1313337.750 1313338.020 1323338.040 1323338.060 1323338.080 1323338.100 1333338.120 1333338.140 1333338.160 1333338.180 1333338.200 1333338.220 1343338.240 1343338.260 1343338.280 1343338.300 1343338.320 1343338.340 1343338.360 1343338.500 1323338.520 1323338.540 1323338.560 1323338.580 1333338.600 1333338.620 1333338.640 1333338.660 1333338.680 1333338.700 1343338.720 1343338.740 1343338.760 1343338.780 1343338.800 1343338.820 1343338.840 1343339.100 1243339.200 1243340.024 523340.115 523340.230 523341.024 523341.115 523341.230 523342.024 523342.115 523342.230 523342.500 523350.024 523350.115 523350.230 523351.024 523351.115 523351.230 523352.024 52

Model No. Page3352.115 523352.230 523352.500 523355.100 523356.100 523357.100 523359.100 743359.110 743359.140 743359.200 743359.210 743359.240 743359.500 743359.510 743359.540 743359.600 743359.610 743359.640 743360.100 1293360.250 1293360.470 1293361.100 853361.110 853361.140 853361.200 853361.210 853361.240 853361.500 853361.510 853361.540 853361.600 853361.610 853361.640 853363.100 1063363.104 1063363.110 1063363.114 1063363.140 1063363.144 1063363.500 1063363.504 1063363.510 1063363.514 1063363.540 1063363.544 1063364.100 1063364.104 1063364.110 1063364.114 1063364.140 1063364.144 1063364.500 1063364.504 1063364.510 1063364.514 1063364.540 1063364.544 1063366.100 883366.110 883366.140 883366.200 883366.210 883366.240 883366.500 883366.510 883366.540 88

Model No. Page

301Rittal System Climate Control

Page 304: Erdinc  klima sk_broschuere_gb

List of model numbers3366.600 to 9776.550

3366.600 883366.610 883366.640 883373.100 1073373.104 1073373.110 1073373.114 1073373.140 1073373.144 1073373.500 1073373.504 1073373.510 1073373.514 1073373.540 1073373.544 1073374.100 1073374.104 1073374.110 1073374.114 1073374.140 1073374.144 1073374.500 1073374.504 1073374.510 1073374.514 1073374.540 1073374.544 1073375.100 1083375.104 1083375.110 1083375.114 1083375.140 1083375.144 1083375.500 1083375.504 1083375.510 1083375.514 1083375.540 1083375.544 1083377.000 1823377.100 883377.110 883377.140 883377.200 883377.210 883377.240 883377.500 883377.510 883377.540 883377.600 883377.610 883377.640 883382.100 743382.110 743382.200 743382.210 743382.500 743382.510 743382.600 743382.610 743383.100 753383.110 753383.140 753383.200 753383.210 753383.240 75

Model No. Page3383.500 753383.510 753383.540 753383.600 753383.610 753383.640 753383.740 793384.100 773384.110 773384.140 773384.200 773384.210 773384.240 773384.500 773384.510 773384.540 773384.600 773384.610 773384.640 773385.100 773385.110 773385.140 773385.200 773385.210 773385.240 773385.500 773385.510 773385.540 773385.600 773385.610 773385.640 773386.140 783386.240 783386.540 783386.640 783387.140 783387.240 783387.540 783387.640 784127.000 1766730.600 1837000.670 587000.680 587109.035 1777507.760 577526.964 1797826.360 587826.362 587826.366 587826.368 587826.369 587826.382 587826.480 587826.486 587826.488 587826.489 587856.360 587856.362 587856.366 587856.368 587856.380 587856.388 587858.488 577885.000 587885.100 587885.200 58

Model No. Page7886.000 587886.100 587886.200 587966.035 567968.035 567980.000 567980.100 567980.148 567986.035 567988.035 568616.000 1128616.010 1128616.020 1128616.030 1128616.200 1128616.210 1128616.220 1128616.230 1128616.300 1158616.310 1158616.500 1148616.510 1148616.550 1148616.560 1148616.600 1128616.610 1128616.620 1128616.630 1128616.640 1138616.641 1138616.650 1138616.651 1138616.700 1848616.710 1848616.720 1848616.750 1848616.751 1848616.760 1848616.761 1848616.762 1848616.763 1858616.764 1858616.765 1858616.800 1128616.810 1128616.820 1128616.830 1128616.840 1138616.841 1138616.850 1138616.851 1138801.300 1818801.310 1818801.320 1818801.330 1818801.340 1818801.350 1818801.360 1818801.380 1828801.410 1818801.420 1818801.430 1818801.440 1818801.920 1819761.012 1609761.032 160

Model No. Page9761.042 1609762.012 1609763.012 1619764.012 1619764.040 1619765.050 1809765.051 1609765.105 1809765.110 1809765.115 1809768.012 1629768.032 1629768.042 1629768.062 1629768.100 1609768.150 1609769.002 529776.100 1639776.150 1639776.500 1639776.550 163

Model No. Page

302 Rittal System Climate Control

Page 305: Erdinc  klima sk_broschuere_gb

Index

AAccessories 171 – 195– Air routing 174 – 176– Control/regulation 177 – 180– Filter technology 189 – 191– for Cold Plate 184, 185– for Liquid Cooling Package 186 – 188– General 192 – 194– Mounting accessories 181 – 183– Software 195Active kit for TE 58Adaptor frame 109– for wall-mounted cooling units 183Add-on cover 188Adjustable frame– for air/air heat exchangers 183Air diverter 176Air duct system– for TopTherm roof-mounted

cooling units and air/water heat exchangers 174

Air routing 174Air/air heat exchangers 60 – 65– Roof-mounted 65– Wall-mounted,

railway-compatible version 64Air/water heat exchangers 100 – 109Aisle containment 139Approvals and product overview 270 – 297

BBottom-mounted adaptor– for enclosure internal thermostat

and hygrostat 178BUS system SK 180

CCable connection kit– for CS outdoor cooling units 180– for CS outdoor heat exchangers 180Chillers for IT cooling 146 – 149Climate control components, Outdoor 160 – 165Climate control doors 71CO2 cooling units 79Cold Plate– for frequency converters 112, 113Condensate collecting bottle 192Condensate hose 192Connection hose 188Cool Efficiency 86Cooling medium for recooling systems 194Cooling module 70– for LCP Standard 141– for LCP Standard and Smart 186Cooling Unit 114Cooling units 66 – 97– Cool Efficiency 86– for CS modular enclosures 160– for precision machine tools 93– for Toptec CR 163– for VIP 6000 command panels 82– Mini in horizontal format 83– NEMA 4x design 91, 92– Roof-mounted 74 – 79– Roof-mounted, stainless steel 74, 75,

77, 78– Wall-mounted 82 – 95– Wall-mounted, stainless steel 84, 85,

87 – 90Cooling with ambient air 41 – 65

Cover bungs 175Cover plates– for fan panels FlatBox 57Covers– for fan-and-filter units/outlet filters 193– for LCP Standard 187CRAC systems 136CS Outdoor climate control 157 – 165

DDC fan mounting plate– for TS 57DCP Cold Plate 112, 113DCP Cooling Unit 114DCP Panel Cooling 115Deflector for air duct system, 90° 174Digital enclosure internal temperature display and thermostat 177Direct cooling package 110 – 115Direct fluid connection 184Door-mounted fan– for server enclosures TS, TE 59Door-operated switch 176Double-nipple coupling 185

EElbow coupling 185Electric condensate evaporator 192EMC– Fan-and-filter units, outlet filters 48, 49Enclosure heaters 167 – 169Enclosure internal fan– for TS 8 55Enclosure internal temperature display and thermostat, digital 177Enclosure internal thermostat 178EPLAN Cabinet 195Explosion-proof cooling units 94Ex-proof climate control systems 164

FFan expansion kit 56– for door-mounted fan TS 59Fan mounting plate– for TS 56, 57Fan roof, modular, two-piece– for TS 8, FR(i) 58Fan systems 50 – 59– for TS 8 54Fan unit, active– for TE 58Fan-and-filter unit– EMC 48, 49Fan-and-filter units 42 – 47Filter holder for roof ventilation 194Filter mats– for tangential fans/

front outlet grilles 189– for discontinued

climate control doors 190– for discontinued cooling units 189, 190– for heat exchangers 190– for Mini recooling systems 190– for TopTherm climate control door/

section door 190– for TopTherm cooling units 189, 190Filter technology 189 – 191Fine filter mats– for fan-and-filter units/outlet filters 191

Flexible hose 184Flow regulator valve 194Fluid distribution manifold 184Front cover 145, 186– for LCP Inline 145Front outlet grille 2 U– for tangential fans 193

HHeat exchangers– Air/air 62 – 65– Air/water 102 – 109– for CS modular enclosures 161, 162– for Toptec CR 163– LCP Extend 143– LCP Plus 142– LCP Standard 141– Water/water 150 – 153Heaters 167 – 169Hood– for fan-and-filter units/outlet filters 193Hose-proof hoods– for fan-and-filter units/outlet filters 193Hygrostat 178

IImmersible recooling systems– for oil/emulsion 132 – 134Integrated louvres 183Interface card for TopTherm 179

LLCP Inline 145LCP Smart 144LCP Extend 143LCP Plus 142LCP Standard 141Lint screen 191Liquid cooling IE 99 – 134Liquid cooling IT 135 – 155Liquid Cooling Package 136, 140 – 145Louvred grille– for lint screen 191

MMetal filters 190Micro air/water heat exchanger 104Mini cooling unit in horizontal format 83Mini recooling systems 118 – 120, 129– for wall mounting 129Modular climate control concept 68 – 71Monitoring 235 – 237Mounting accessories 181 – 183Mounting adaptor– for speed control 179

NNEMA 4x– Cooling units 91, 92

303Rittal System Climate Control

Page 306: Erdinc  klima sk_broschuere_gb

Index

OOutdoor climate control 157 – 165Outlet filter 193– EMC 48, 49Overflow valve 194Overview of products and approvals 270 – 297

PPanel Cooling 115Piping systems– in the data centre 154, 155Power Fluid Cooler 121, 122, 125, 126Power packs 24 V (DC)– for thermoelectric cooler 192Project planning 30 – 39

QQuick-action vent valve 184Quick-change frame– for TopTherm roof-mounted

cooling units 182Quick-release fastener 188

RRack-mounted fans 482.6 mm (19˝) 50, 52Raised-floor, CRAC system 138Recooling systems 116 – 134– for oil 130, 131– for water 118 – 129– immersible, oil/emulsion 132 – 134RiDiag II 195Roof plates– DK-TS 181– TS 181Roof-mounted– Air/air heat exchangers 65– Air/water heat exchangers 102, 103– Cooling units 72 – 79Roof-mounted fan 54– for the office sector 55RTT roof-mounted fans 54

SSection doors for cooling modules 71Service 298, 299Shallow air duct system 175Shallow duct extension 175Shielding– Horizontal 187– Vertical 186SK BUS system 180Software service 195Spare filter mat– for fan-and-filter units/outlet filters 191– for filter holder 191– for thermoelectric cooler 191Speed control 179

Stainless steel– Cooling units – roof-mounted 74, 75,

77, 78– Cooling units – wall-mounted 84, 85,

87 – 90Stoppers– for roof-mounted cooling units 175System accessories 171 – 195System attachment– for frequency converters 184System solutions 14 – 29

TTangential fans 50, 53Technical details 239 – 268Temperature display and thermostat, digital 177Temperature sensor TF25 185Test adaptor– for CS Outdoor

climate control equipment 180Therm Software 195Thermoelectric coolers 96, 97Thermostat 178– Digital 177Tips and tricks 197 – 237Touchscreen display– for LCP Smart 186Trim frame– for slimline cooling units 182

VVent attachment 54– TS 182Vent valve 188VIP small cooling units 82

WWall-mounted cooling units 80 – 95– Cool Efficiency 86– Thermoelectric coolers 96, 97Wall-mounted heat exchangers– Air/air 62, 63– Air/water 104 – 109Wide-range power pack– for thermoelectric cooler 192

RAL-coloursColour RAL Description

3001 signal red

5002 ultramarine blue

5005 signal blue

5018 turquoise blue

7015 slate grey

7022 umbra grey

7024 graphite grey

7030 stone grey

7032 pebble grey

7033 cement grey

7035 pale grey

7044 silky grey

8019 grey brown

9005 jet black

9006 white aluminium

9011 graphite black

9017 traffic black

We reserve the right to further develop-ments and technical modifications of our products. Such modifications, along with errors and printing errata, shall not con-stitute grounds for compensation.We refer customers to our Terms of Sale and Delivery.

304

Rittal System Climate Control
Page 307: Erdinc  klima sk_broschuere_gb

Switch to perfection

Rittal GmbH & Co. KG � Postfach 1662 � D-35726 HerbornTelephone: +49(0)2772 505-0 � Telefax: +49(0)2772 505-2319 � eMail: [email protected] � www.rittal.com

All in all – solutions from Rittal

Rittal has one of the largest ranges of enclosures available for immediate delivery. However, Rittal also supplies inte-grated solutions – up to Level 4. This comprises mechanical installation, power supply, electronic components, climate control and central monitoring. For all of your requirements.

Fully assembled and functional. Wherever in the world you develop and implement solutions for yourself and your customers, we are close at hand. The global alliance between production, distribution and service guarantees closeness to the customer. Worldwide!

04/0

9 � E

384

Cooling units � Recooling units � Heat exchangers Fan-and-filter units � 19˝ climate control � Heaters � IT cooling

Electronic Packaging

IT Solutions

Communication Systems

System Climate Control

Power Distribution

Industrial Enclosures


Recommended