ETAP PowerStation 4.0 User Guide Copyright 2001 Operation Technology, Inc. All Rights Reserved This manual has copyrights by Operation Technology, Inc. All rights reserved. Under the copyright laws, this manual may not be copied, in whole or in part, without the written consent of Operation Technology, Inc. The Licensee may copy portions of this documentation only for the exclusive use of Licensee. Any reproduction shall include the copyright notice. This exception does not allow copies to be made for other persons or entities, whether or not sold. Under this law, copying includes translating into another language. Certain names and/or logos used in this document may constitute trademarks, service marks, or trade names of Operation Technology, Inc. or other entities. Access, Excel, ODBC, SQL Server, Windows NT, Windows 2000, Windows Me, Windows 98, Windows XP, and Microsoft Word are registered trademarks of Microsoft Corporation. AutoCad is a registered trademark of Autodesk. Oracle is a registered trademark of Oracle Corporation. PowerPlot is a registered trademark of Jackson & Associates. Crystal Reports is a registered trademark of Seagate Software. MATLAB and Simulink are registered trademarks of MathWorks Screen shot(s) reprinted by permission from Microsoft Corporation. Operation Technology, Inc. believes that the information contained herein is accurate as of its publication date, and such information is subject to change without notice. This information is provided “as is” without warranty of any kind, either expressed or implied, including but not limited to the implied warranties of merchantability, fitness for a particular purpose, or non- infringement. Operation Technology, Inc. assumes no responsibility for errors or omissions in this publication or any other documents referenced in this publication. Operation Technology, Inc. Southern California (949) 462-0100 Sales (949) 462-0400 Fax (949) 462-0400 User Support
Transcript
Page 1: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

ETAP PowerStation 4.0

User Guide

Copyright 2001 Operation Technology, Inc.

All Rights Reserved This manual has copyrights by Operation Technology, Inc. All rights reserved. Under the copyright laws, this manual may not be copied, in whole or in part, without the written consent of Operation Technology, Inc. The Licensee may copy portions of this documentation only for the exclusive use of Licensee. Any reproduction shall include the copyright notice. This exception does not allow copies to be made for other persons or entities, whether or not sold. Under this law, copying includes translating into another language. Certain names and/or logos used in this document may constitute trademarks, service marks, or trade names of Operation Technology, Inc. or other entities. • Access, Excel, ODBC, SQL Server, Windows NT, Windows 2000, Windows Me, Windows

98, Windows XP, and Microsoft Word are registered trademarks of Microsoft Corporation. • AutoCad is a registered trademark of Autodesk. • Oracle is a registered trademark of Oracle Corporation. • PowerPlot is a registered trademark of Jackson & Associates. • Crystal Reports is a registered trademark of Seagate Software. • MATLAB and Simulink are registered trademarks of MathWorks • Screen shot(s) reprinted by permission from Microsoft Corporation. Operation Technology, Inc. believes that the information contained herein is accurate as of its publication date, and such information is subject to change without notice. This information is provided “as is” without warranty of any kind, either expressed or implied, including but not limited to the implied warranties of merchantability, fitness for a particular purpose, or non-infringement. Operation Technology, Inc. assumes no responsibility for errors or omissions in this publication or any other documents referenced in this publication.

Operation Technology, Inc. Southern California

(949) 462-0100 Sales (949) 462-0400 Fax (949) 462-0400 User Support

Page 2: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

Chapter 9

Instrumentation Elements

This chapter addresses editors for all Instrumentation elements in the One-Line Diagram. Except for the element IDs, bus connections, and status, all other data that appear in the editors are considered engineering properties, which are subject to Base & Revision Data. The following table lists all the Instrumentation elements in PowerStation as seen from the Instrumentation (Inst) Toolbar.

Transformers Current Transformer Potential Transformer

Meters Voltmeter

MultimeterAmmeter

Relays Voltage Relay

Frequency Relay Solid State Device

Power Relay Motor Relay OverCurrent Relay

Operation Technology, Inc. 9-1 ETAP PowerStation 4.0

Page 3: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Current Transformer

9.1 Current Transformer The properties associated with current transformers (CT) of the electrical distribution system can be entered in this editor. The Current Transformer Editor contains three pages of properties. • Info Page • Remarks Page • Comment Page

9.1.1 Info Page

Info

ID Enter a unique ID with up to 25 alphanumeric characters. PowerStation automatically assigns a unique ID to each current transformer. The assigned IDs consist of the default current transformer ID plus an integer, starting with the number one and increasing as the number of current transformers increase. The default current transformer ID (CT) can be changed from the Defaults Menu in the menu bar or from the Project View.

Operation Technology, Inc. 9-2 ETAP PowerStation 4.0

Page 4: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Current Transformer

From & To Bus IDs for the connecting buses of a current transformer are designated as From and To buses. If a terminal of current transformer (From or To) is not connected to any bus, a blank entry will be shown for bus ID. If a terminal of a current transformer is connected to a branch (directly or indirectly), the ID of the branch will be displayed for the terminal connection. To connect or reconnect a current transformer to a bus, select a bus from the list box. The one-line diagram will be updated to show the new connection after you click on OK. Note that you can only connect to buses that reside in the same view where the current transformer resides, i.e., you cannot connect to a bus that resides in the Dumpster or in another composite network. If a current transformer is connected to a bus through a number of other protective devices, reconnection of the current transformer to a new bus from this editor will reconnect the last existing protective device to the new bus, as shown below where CT2 is reconnected from Bus10 to Bus4.

Next to the From and To bus IDs, PowerStation displays the nominal kV of the buses for your convenience.

In/Out of Service Operating condition of a current transformer can be selected by choosing either the In Service or Out of Service options. The properties of an Out of Service branch can be edited like an In Service branch; however, an Out of Service branch will not be included in any system studies. When Continuity Check is activated, an Out of Service branch automatically becomes dimmed in the one-line diagram. Note that the In / Out of Service option is an engineering property which is independent of the configuration status. Therefore, you can set a branch to be In Service for the Base Data and Out of Service in Revision Data.

Equipment

FDR Tag Enter the feeder tag in this field, up to 25 alphanumeric characters.

Name Enter equipment name, up to 50 alphanumeric characters.

Description Enter equipment description, up to 100 alphanumeric characters.

Operation Technology, Inc. 9-3 ETAP PowerStation 4.0

Page 5: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Current Transformer

Rating Enter the primary and secondary current ratings (turn ratio) for the current transformer in amperes.

9.1.2 Remarks Page

User-Defined Info These fields allow you to keep track of extra data associated with this component. The names of the User-Defined (UD) fields can be changed from the Settings option in the Project menu in the Menu bar.

UD Field 1 (Eq. Ref.) This is a number field with the default name Eq. Ref. You can change the name of this field and enter the equipment reference number or any other number here, up to five digits.

UD Field 2 (Last Maint.) This is an alphanumeric field with the default name Last Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 3 (Next Maint.) This is an alphanumeric field with the default name Next Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

Operation Technology, Inc. 9-4 ETAP PowerStation 4.0

Page 6: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Current Transformer

UD Field 4 (Tests Req.) This is an alphanumeric field with the default name Tests Req. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A5 This is an alphanumeric field with the default name UD Field A5. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A6 This is an alphanumeric field with the default name UD Field A6. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A7 This is an alphanumeric field with the default name UD Field A7. You can change the name of this field and enter any extra data for this element here, up to 18 alphanumeric characters.

Drawing/Diagram

One-Line Enter the name or ID of a one-line drawing or diagram associated with this element, up to 50 alphanumeric characters. An example is the manufacturer diagram or specifications for this element.

Reference Enter the name or ID of a reference drawing or document for this element, up to 50 alphanumeric characters.

Manufacturer

Name Enter the manufacturer’s name for this element here, up to 25 alphanumeric characters.

Purchase Date Enter the date of purchase for this element here, up to 8 alphanumeric characters.

Operation Technology, Inc. 9-5 ETAP PowerStation 4.0

Page 7: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Current Transformer

9.1.3 Comment Page Enter any extra data or comments regarding condition, maintenance, tests, or studies, associated with this element. This field can be up to 64kb with a default size of 4kb. To increase the size of this field, refer to the entries in the ETAPS.INI file.

When entering information in the page, use Ctrl+Enter to start a new paragraph. Standard keys such as Ctrl+X, Ctrl+C, and Ctrl+V can be used to cut, copy, and paste information.

Operation Technology, Inc. 9-6 ETAP PowerStation 4.0

Page 8: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Potential Transformer

9.2 Potential Transformer The properties associated with potential transformers (PT) of the electrical distribution system can be entered in this editor. The Potential Transformer Editor contains three pages of properties. • Info Page • Remarks Page • Comment Page

9.1.1 Info Page

Info

ID Enter a unique ID with up to 25 alphanumeric characters. PowerStation automatically assigns a unique ID to each potential transformer. The assigned IDs consist of the default potential transformer ID plus an integer, starting with the number one and increasing as the number of potential transformers increase. The default potential transformer ID (PT) can be changed from the Defaults Menu in the menu bar or from the Project View.

From & To The primary terminal of the potential transformer has two pins as From and To which can be connected directly to buses or in between branch elements. These primary pins are located on top of each other.

Operation Technology, Inc. 9-7 ETAP PowerStation 4.0

Page 9: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Potential Transformer

Also, if the primary terminal of a potential transformer is connected to a From bus, the ID of the To bus will be hidden and visa versa. To connect or reconnect a potential transformer to a bus, select a bus from the list box. The one-line diagram will be updated to show the new connection after you click on OK. Note that you can only connect to buses that reside in the same view where the branch resides, i.e., you cannot connect to a bus that resides in the Dumpster or in another composite network.

The secondary terminal of a PT has only one pin, which can be connected to voltmeters, multimeters, frequency relays, and voltage relays.

In/Out of Service The operating condition of a potential transformer can be selected by choosing either the In Service or Out of Service options. The properties of an Out of Service potential transformer can be edited like an In Service potential transformer; however, an Out of Service potential transformer will not be included in any system studies. When Continuity Check is activated, an Out of Service potential transformer automatically becomes dimmed in the one-line diagram. Note that the In / Out of Service option is an engineering property which is independent of the configuration status. Therefore, you can set a branch to be In Service for the Base Data and Out of Service in Revision Data.

Rating

Primary Enter the primary rated voltage of the potential transformer in kV or select the rating from the list box.

Secondary Enter the secondary rated voltage of the potential transformer in V or select the rating from the list box.

Connection This is the type of connection of the potential transformer. Select the connection type from the list box. Options for phase connection include: • L-G Line-to-ground connection • L-L Line-to-line connection

Operation Technology, Inc. 9-8 ETAP PowerStation 4.0

Page 10: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Potential Transformer

Ratio This is the turn ratio of the potential transformer based on the primary and secondary voltages.

Equipment

FDR Tag Enter the feeder tag in this field, up to 25 alphanumeric characters.

Name Enter equipment name, up to 50 alphanumeric characters.

Description Enter equipment description, up to 100 alphanumeric characters.

9.2.1 Remarks Page

User-Defined Info These fields allow you to keep track of extra data associated with this component. The names of the User-Defined (UD) fields can be changed from the Settings option in the Project menu in the Menu bar.

UD Field 1 (Eq. Ref.) This is a number field with the default name Eq. Ref. You can change the name of this field and enter the equipment reference number or any other number here, up to five digits.

UD Field 2 (Last Maint.) This is an alphanumeric field with the default name Last Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 3 (Next Maint.) This is an alphanumeric field with the default name Next Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 4 (Tests Req.) This is an alphanumeric field with the default name Tests Req. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

Operation Technology, Inc. 9-9 ETAP PowerStation 4.0

Page 11: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Potential Transformer

UD Field A5 This is an alphanumeric field with the default name UD Field A5. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A6 This is an alphanumeric field with the default name UD Field A6. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A7 This is an alphanumeric field with the default name UD Field A7. You can change the name of this field and enter any extra data for this element here, up to 18 alphanumeric characters.

Drawing/Diagram

One-Line Enter the name or ID of a one-line drawing or diagram associated with this element, up to 50 alphanumeric characters. An example is the manufacturer diagram or specifications for this element.

Reference Enter the name or ID of a reference drawing or document for this element, up to 50 alphanumeric characters.

Manufacturer

Name Enter the manufacturer’s name for this element here, up to 25 alphanumeric characters.

Purchase Date Enter the date of purchase for this element here, up to 8 alphanumeric characters.

Operation Technology, Inc. 9-10 ETAP PowerStation 4.0

Page 12: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Potential Transformer

9.2.2 Comment Page Enter any extra data or comments regarding condition, maintenance, tests, or studies, associated with this element. This field can be up to 64kb with a default size of 4kb. To increase the size of this field, refer to the entries in the ETAPS.INI file.

When entering information in the page, use Ctrl+Enter to start a new paragraph. Standard keys such as Ctrl+X, Ctrl+C, and Ctrl+V can be used to cut, copy, and paste information.

Operation Technology, Inc. 9-11 ETAP PowerStation 4.0

Page 13: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Voltmeter

9.3 Voltmeter The properties associated with voltmeters can be entered in this editor. The Voltmeter Editor contains three pages of properties. • Info Page • Remarks Page • Comment Page

9.0.1 Info Page

Info

ID Enter a unique ID with up to 25 alphanumeric characters. PowerStation automatically assigns a unique ID to each voltmeter. The assigned IDs consist of the default voltmeter ID plus an integer, starting with the number one and increasing as the number of voltmeters increase. The default voltmeter ID (VM) can be changed from the Defaults Menu in the menu bar or from the Project View.

PT Voltmeters have one pin, which can be connected to a potential transformer (PT). A blank entry will be shown for the PT if the terminal of the voltmeter is not directly connected to a PT. If the terminal of a voltmeter is connected to a PT, the ID of the PT will be displayed for the terminal connection.

Operation Technology, Inc. 9-12 ETAP PowerStation 4.0

Page 14: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Voltmeter

Ratio This is the turn ratio of the potential transformer connected to the voltmeter.

In/Out of Service The operating condition of a voltmeter can be selected by choosing either the In Service or Out of Service option. The properties of an Out of Service voltmeter can be edited like an In Service voltmeter; however, an Out of Service voltmeter will not be included in any system studies. When Continuity Check is activated, an Out of Service voltmeter automatically becomes dimmed in the one-line diagram. Note that the In / Out of Service option is an engineering property which is independent of the configuration status. Therefore, you can set a branch to be In Service for the Base Data and Out of Service in Revision Data.

Voltage

Operating This field displays the operating voltage in volts. This field is updated when used with the on-line monitoring module.

Full Scale Enter the full scale value of the meter. This is used for PSMS only.

Std. Deviation Enter the standard deviation of the meter. This is used for PSMS only.

Online Data The data here are associated with the online (real-time) operation of PowerStation (PSMS).

Scanned Displays the scanned value of the meter as it is obtained from the system.

Pinned For PSMS, you can pin a value for the meter that may be different from the real-time data. This option is provided to overwrite the actual scanned value for the system.

Equipment

FDR Tag Enter the feeder tag in this field, up to 25 alphanumeric characters.

Name Enter equipment name, up to 50 alphanumeric characters.

Description Enter equipment description, up to 100 alphanumeric characters.

Operation Technology, Inc. 9-13 ETAP PowerStation 4.0

Page 15: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Voltmeter

9.3.1 Remarks Page

User-Defined Info These fields allow you to keep track of extra data associated with this component. The names of the User-Defined (UD) fields can be changed from the Settings option in the Project menu in the Menu bar.

UD Field 1 (Eq. Ref.) This is a number field with the default name Eq. Ref. You can change the name of this field and enter the equipment reference number or any other number here, up to five digits.

UD Field 2 (Last Maint.) This is an alphanumeric field with the default name Last Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 3 (Next Maint.) This is an alphanumeric field with the default name Next Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 4 (Tests Req.) This is an alphanumeric field with the default name Tests Req. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A5 This is an alphanumeric field with the default name UD Field A5. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A6 This is an alphanumeric field with the default name UD Field A6. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

Operation Technology, Inc. 9-14 ETAP PowerStation 4.0

Page 16: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Voltmeter

UD Field A7 This is an alphanumeric field with the default name UD Field A7. You can change the name of this field and enter any extra data for this element here, up to 18 alphanumeric characters.

Drawing/Diagram

One-Line Enter the name or ID of a one-line drawing or diagram associated with this element, up to 50 alphanumeric characters. An example is the manufacturer diagram or specifications for this element.

Reference Enter the name or ID of a reference drawing or document for this element, up to 50 alphanumeric characters.

Manufacturer

Name Enter the manufacturer’s name for this element here, up to 25 alphanumeric characters.

Purchase Date Enter the date of purchase for this element here, up to 8 alphanumeric characters.

9.3.2 Comment Page Enter any extra data or comments regarding condition, maintenance, tests, or studies, associated with this element. This field can be up to 64kb with a default size of 4kb. To increase the size of this field, refer to the entries in the ETAPS.INI file.

When entering information in the page, use Ctrl+Enter to start a new paragraph. Standard keys such as Ctrl+X, Ctrl+C, and Ctrl+V can be used to cut, copy, and paste information.

Operation Technology, Inc. 9-15 ETAP PowerStation 4.0

Page 17: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Ammeter

9.4 Ammeter The properties associated with ammeters can be entered in this editor. The Ammeter Editor contains three pages of properties. • Info Page • Remarks Page • Comment Page

9.0.1 Info Page

Info

ID Enter a unique ID with up to 25 alphanumeric characters. PowerStation automatically assigns a unique ID to each ammeter. The assigned IDs consist of the default ammeter ID plus an integer, starting with the number one and increasing as the number of ammeters increase. The default ammeter ID (AM) can be changed from the Defaults Menu in the menu bar or from the Project View.

CT Ammeters have two pins, one of which can be connected to a current transformer (CT) and the other pin can be connected to other relays and/or meters. A blank entry will be shown for the CT if the terminal of the ammeter is not connected directly to a CT or indirectly through other relays and/or meters. If the terminal of an ammeter is connected to a CT or to a relay, which is connected to a CT, the ID of the CT will be displayed for the terminal connection.

Ratio This is the turn ratio of the current transformer connected to the ammeter.

Operation Technology, Inc. 9-16 ETAP PowerStation 4.0

Page 18: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Ammeter

In/Out of Service The operating condition of an ammeter can be selected by choosing either the In Service or Out of Service options. The properties of an Out of Service ammeter can be edited like an In Service ammeter; however, an Out of Service ammeter will not be included in any system studies. When Continuity Check is activated, an Out of Service ammeter automatically becomes dimmed in the one-line diagram. Note that the In / Out of Service option is an engineering property which is independent of the configuration status. Therefore, you can set a branch to be In Service for the Base Data and Out of Service in Revision Data.

Current

Operating This field displays the operating current in amperes. This field is updated when it is used with the on-line monitoring module.

Rating

Full Scale Enter the full-scale value of the meter. This is used for PSMS only.

Std. Deviation Enter the standard deviation of the meter. This is used for PSMS only.

Online Data The data here are associated with the online (real-time) operation of PowerStation (PSMS).

Scanned Displays the scanned value of the meter as it is obtained from the system.

Pinned For PSMS, you can pin a value for the meter that may be different from the real-time data. This option is provided to overwrite the actual scanned value for the system.

Equipment

FDR Tag Enter the feeder tag in this field, up to 25 alphanumeric characters.

Name Enter equipment name, up to 50 alphanumeric characters.

Description Enter equipment description, up to 100 alphanumeric characters.

Operation Technology, Inc. 9-17 ETAP PowerStation 4.0

Page 19: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Ammeter

9.4.1 Remarks Page

User-Defined Info These fields allow you to keep track of extra data associated with this component. The names of the User-Defined (UD) fields can be changed from the Settings option in the Project menu in the Menu bar.

UD Field 1 (Eq. Ref.) This is a number field with the default name Eq. Ref. You can change the name of this field and enter the equipment reference number or any other number here, up to five digits.

UD Field 2 (Last Maint.) This is an alphanumeric field with the default name Last Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 3 (Next Maint.) This is an alphanumeric field with the default name Next Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 4 (Tests Req.) This is an alphanumeric field with the default name Tests Req. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A5 This is an alphanumeric field with the default name UD Field A5. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A6 This is an alphanumeric field with the default name UD Field A6. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

Operation Technology, Inc. 9-18 ETAP PowerStation 4.0

Page 20: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Ammeter

UD Field A7 This is an alphanumeric field with the default name UD Field A7. You can change the name of this field and enter any extra data for this element here, up to 18 alphanumeric characters.

Drawing/Diagram

One-Line Enter the name or ID of a one-line drawing or diagram associated with this element, up to 50 alphanumeric characters. An example is the manufacturer diagram or specifications for this element.

Reference Enter the name or ID of a reference drawing or document for this element, up to 50 alphanumeric characters.

Manufacturer

Name Enter the manufacturer’s name for this element here, up to 25 alphanumeric characters.

Purchase Date Enter the date of purchase for this element here, up to 8 alphanumeric characters.

9.4.2 Comment Page Enter any extra data or comments regarding condition, maintenance, tests, or studies, associated with this element. This field can be up to 64kb with a default size of 4kb. To increase the size of this field, refer to the entries in the ETAPS.INI file.

When entering information in the page, use Ctrl+Enter to start a new paragraph. Standard keys such as Ctrl+X, Ctrl+C, and Ctrl+V can be used to cut, copy, and paste information.

Operation Technology, Inc. 9-19 ETAP PowerStation 4.0

Page 21: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Multimeter

9.5 Multimeter The properties associated with multimeters of the electrical distribution system can be entered in this editor. The Multimeter Editor includes three pages of properties. • Info Page • Remarks Page • Comment Page

9.0.1 Info Page

Info

ID Enter a unique ID with up to 25 alphanumeric characters. PowerStation automatically assigns a unique ID to each multimeter. The assigned IDs consist of the default multimeter ID plus an integer, starting with the number one and increasing as the number of multimeters increase. The default multimeter ID (MM) can be changed from the Defaults Menu in the menu bar or from the Project View.

Multimeters have three connection pins: two current pins that can be connected to a current transformer (CT) and relays/meters, and a voltage pin, which can be connected to a PT.

Operation Technology, Inc. 9-20 ETAP PowerStation 4.0

Page 22: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Multimeter

CT A blank entry will be shown for the CT if the CT terminal of the multimeter is not directly connected to a CT or indirectly through other relays and/or meters. If the CT terminal of a multimeter is connected to a CT or to a relay/ammeter, which is connected to a CT, the ID of the CT will be displayed for the terminal connection.

PT A blank entry will be shown for the PT if the PT terminal of the multimeter (bottom pin) is not directly connected to a PT. If the terminal of a multimeter is connected to a PT, the ID of the PT will be displayed for the terminal connection.

Ratio The turn ratio of the current and/or potential transformer connected to the multimeter is shown here.

In/Out of Service The operating condition of a multimeter can be selected by choosing either the In Service or Out of Service options. The properties of an Out of Service multimeter can be edited like an In Service multimeter. However, an Out of Service multimeter will not be included in any system studies. When the continuity check is activated, an Out of Service multimeter automatically becomes dimmed in the one-line diagram. Note that the In / Out of Service option is an engineering property which is independent of the configuration status. Therefore, you can set a branch to be In Service for the base data and Out of Service in revision data.

Reverse Polarity Check this box to reverse the voltage potential polarity.

Type

Voltage Check this box to select a voltmeter function. A PT connection is required for this function.

Current Check this box to select an ammeter function. A CT connection is required for this function.

Operation Technology, Inc. 9-21 ETAP PowerStation 4.0

Page 23: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Multimeter

kW/MW Check this box to select a wattmeter function. Both CT and PT connection are required for this function. Click on the kW/MW button to toggle between kilo and Mega units for watt and var values for entering and displaying multimeter data.

kvar/Mvar Check this box to select a varmeter function. Both CT and PT connection are required for this function.

PF Check this box to meter power factor. A CT connection is required for this function.

Freq. Check this box for frequency measurement.

Operating Displays the operating/metered values for selected multimeter functions.

Full Scale Enter the full-scale value of the meter. This is used for PSMS only.

Std. Deviation Enter the standard deviation of the meter. This is used for PSMS only.

Online Data The data here are associated with the online (real-time) operation of PowerStation (PSMS).

Scanned Displays the scanned value of the meter as it is obtained from the system.

Pinned For PSMS, you can pin a value for the meter that may be different from the real-time data. This option is provided to overwrite the actual scanned value for the system.

Equipment

FDR Tag Enter the feeder tag in this field, up to 25 alphanumeric characters.

Name Enter equipment name, up to 50 alphanumeric characters.

Description Enter equipment description, up to 100 alphanumeric characters.

Operation Technology, Inc. 9-22 ETAP PowerStation 4.0

Page 24: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Multimeter

9.5.1 Remarks Page

User-Defined Info These fields allow you to keep track of extra data associated with this component. The names of the User-Defined (UD) fields can be changed from the Settings option in the Project menu in the Menu bar.

UD Field 1 (Eq. Ref.) This is a number field with the default name Eq. Ref. You can change the name of this field and enter the equipment reference number or any other number here, up to five digits.

UD Field 2 (Last Maint.) This is an alphanumeric field with the default name Last Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 3 (Next Maint.) This is an alphanumeric field with the default name Next Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 4 (Tests Req.) This is an alphanumeric field with the default name Tests Req. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A5 This is an alphanumeric field with the default name UD Field A5. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A6 This is an alphanumeric field with the default name UD Field A6. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A7 This is an alphanumeric field with the default name UD Field A7. You can change the name of this field and enter any extra data for this element here, up to 18 alphanumeric characters.

Operation Technology, Inc. 9-23 ETAP PowerStation 4.0

Page 25: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Multimeter

Drawing/Diagram

One-Line Enter the name or ID of a one-line drawing or diagram associated with this element, up to 50 alphanumeric characters. An example is the manufacturer diagram or specifications for this element.

Reference Enter the name or ID of a reference drawing or document for this element, up to 50 alphanumeric characters.

Manufacturer

Name Enter the manufacturer’s name for this element here, up to 25 alphanumeric characters.

Purchase Date Enter the date of purchase for this element here, up to 8 alphanumeric characters.

Operation Technology, Inc. 9-24 ETAP PowerStation 4.0

Page 26: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Multimeter

9.5.2 Comment Page Enter any extra data or comments regarding condition, maintenance, tests, or studies, associated with this element. This field can be up to 64kb with a default size of 4kb. To increase the size of this field, refer to the entries in the ETAPS.INI file.

When entering information in the page, use Ctrl+Enter to start a new paragraph. Standard keys such as Ctrl+X, Ctrl+C, and Ctrl+V can be used to cut, copy, and paste information.

Operation Technology, Inc. 9-25 ETAP PowerStation 4.0

Page 27: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Over Current Relay

9.6 Over Current Relay The properties associated with over current relays of the electrical distribution system can be entered in this editor. The Over Current Relay Editor includes four pages of properties. • Info Page • Setting Page • Remarks Page • Comment Page

9.0.1 Info Page

Info

ID Enter a unique ID with up to 25 alphanumeric characters. PowerStation automatically assigns a unique ID to each over current relay. The assigned IDs consist of the default over current relay ID plus an integer, starting with the number one and increasing as the number of over current relay increase. The default over current relay ID (OCR) can be changed from the Defaults Menu in the menu bar or from the Project View.

CT Over current relays have two pins, one of which can be connected to a current transformer (CT) and the other pin can be connected to other current/power relays. A blank entry will be shown for the CT if the terminal of the over current relay is not directly connected to a CT or indirectly through other relays. If the terminal of an over current relay is connected to a CT or to a relay which is connected to a CT, the ID of the CT will be displayed for the terminal connection.

Operation Technology, Inc. 9-26 ETAP PowerStation 4.0

Page 28: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Over Current Relay

Ratio This field displays the relay connected CT ratio.

In/Out of Service The operating condition of an over current relay can be selected by choosing either the In Service or Out of Service options. The properties of an Out of Service relay can be edited like an In Service relay; however, an Out of Service relay will not display results of any system studies. When Continuity Check is activated, an Out of Service relay automatically becomes dimmed in the one-line diagram. Note that the In/Out of Service option is an engineering property, which is independent of the configuration status. Therefore, you can set a relay to be In Service for the Base Data and Out of Service in Revision Data.

Interlock

Device Set and display the over current control interlock data.

ID

Add Click on this button to open the over current Interlock Editor to set parameters for a new over current control interlock parameters, including Device type, device ID, and control Action.

Edit Click on this button to open the over current Interlock Editor and edit the settings of an existing over current control interlock.

Delete Click on this button to delete the selected control interlock.

Operation Technology, Inc. 9-27 ETAP PowerStation 4.0

Page 29: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Over Current Relay

Equipment

FDR Tag Enter the feeder tag in this field, up to 25 alphanumeric characters.

Name Enter equipment name, up to 50 alphanumeric characters.

Description Enter equipment description, up to 100 alphanumeric characters.

9.6.1 Setting Page

50 (For Transient Stability Analysis) These settings are used as 50 relay settings for the transient stability analysis.

Instantaneous Check this box for instantaneous relay action.

Setting Enter the pickup current as Relay Amp. The primary current is calculated and displayed as Primary Amp.

Time Delay Enter the intentional relay time delay in second.

Operation Technology, Inc. 9-28 ETAP PowerStation 4.0

Page 30: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Over Current Relay

67 (For Transient Stability Analysis) These settings are used if the relay is used as a 67 relay for the transient stability analysis.

Directional Check this box if the relay pickup current is directional.

Direction Select the relay pickup current direction either in Forward or in Reverse. Based on the selected direction and CT connection (polarity), tripping direction of the relay will be shown in an arrow on one-line diagram.

9.6.2 Remarks Page

User-Defined Info These fields allow you to keep track of extra data associated with this component. The names of the User-Defined (UD) fields can be changed from the Settings option in the Project menu in the Menu bar.

UD Field 1 (Eq. Ref.) This is a number field with the default name Eq. Ref. You can change the name of this field and enter the equipment reference number or any other number here, up to five digits.

UD Field 2 (Last Maint.) This is an alphanumeric field with the default name Last Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

Operation Technology, Inc. 9-29 ETAP PowerStation 4.0

Page 31: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Over Current Relay

UD Field 3 (Next Maint.) This is an alphanumeric field with the default name Next Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 4 (Tests Req.) This is an alphanumeric field with the default name Tests Req. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A5 This is an alphanumeric field with the default name UD Field A5. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A6 This is an alphanumeric field with the default name UD Field A6. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A7 This is an alphanumeric field with the default name UD Field A7. You can change the name of this field and enter any extra data for this element here, up to 18 alphanumeric characters.

Drawing/Diagram

One-Line Enter the name or ID of a one-line drawing or diagram associated with this element, up to 50 alphanumeric characters. An example is the manufacturer diagram or specifications for this element.

Reference Enter the name or ID of a reference drawing or document for this element, up to 50 alphanumeric characters.

Manufacturer

Name Enter the manufacturer’s name for this element here, up to 25 alphanumeric characters.

Purchase Date Enter the date of purchase for this element here, up to 8 alphanumeric characters.

Operation Technology, Inc. 9-30 ETAP PowerStation 4.0

Page 32: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Over Current Relay

9.6.3 Comment Page Enter any extra data or comments regarding condition, maintenance, tests, or studies, associated with this element. This field can be up to 64kb with a default size of 4kb. To increase the size of this field, refer to the entries in the ETAPS.INI file.

When entering information in the page, use Ctrl+Enter to start a new paragraph. Standard keys such as Ctrl+X, Ctrl+C, and Ctrl+V can be used to cut, copy, and paste information.

Operation Technology, Inc. 9-31 ETAP PowerStation 4.0

Page 33: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Voltage Relay

9.7 Voltage Relay The properties associated with voltage relays are specified in Voltage Relay Editor. Voltage relays can be used in transient stability study. According to the specified circuit breaker control interlock functions and settings, transient stability program will check the monitored system quantities and compare them with the relay settings. When the control conditions are met, the associated control actions will be triggered. Voltage relays should be connected to a bus via a potential transformer. The Voltage Relay Editor contains four pages of information. • Info Page • Setting Page • Remarks Page • Comment Page

9.0.1 Info Page

Operation Technology, Inc. 9-32 ETAP PowerStation 4.0

Page 34: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Voltage Relay

Info

ID Enter a unique ID with up to 25 alphanumeric characters. PowerStation automatically assigns a unique ID to each voltage relay. The assigned IDs consist of the default voltage relay ID plus an integer, starting with the number one and increasing as the number of voltage relays increase. The default voltage relay ID (VR) can be changed from the Defaults Menu in the menu bar or from the Project View.

PT Display the connected PT ID.

In/Out of Service The operating condition of a voltage relay can be selected by choosing either the In Service or Out of Service options. The properties of an Out of Service relay can be edited like an In Service relay; however, an Out of Service relay will not display results of any system studies. When Continuity Check is activated, an Out of Service relay automatically becomes dimmed in the one-line diagram. Note that the In / Out of Service option is an engineering property which is independent of the configuration status. Therefore, you can set a relay to be In Service for the Base Data and Out of Service in Revision Data

Equipment

FDR Tag Enter the feeder tag in this field, up to 25 alphanumeric characters.

Name Enter equipment name, up to 50 alphanumeric characters.

Description Enter equipment description, up to 100 alphanumeric characters.

Operation Technology, Inc. 9-33 ETAP PowerStation 4.0

Page 35: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Voltage Relay

9.7.1 Setting Page

OverVoltage (59) Control Interlock Set and display the over-voltage control interlock data.

Add Button Click on this button to open the Voltage Relay Control Interlock Editor to set parameters for a new over-voltage control interlock parameters.

Edit Button Click on this button to open the Voltage Relay Control Interlock Editor and edit the settings of an existing over-voltage control interlock.

Delete Button Click on this button to delete the highlighted over-voltage control interlock.

UnderVoltage (27) Control Interlock Set and display the under-voltage control interlock data.

Add Button Click on this button to open the Voltage Relay Control Interlock Editor to set parameters for a new under-voltage control interlock parameters.

Edit Button Click on this button to open the Voltage Relay Control Interlock Editor and edit the settings of an existing under-voltage control interlock.

Delete Button Click on this button to delete the highlighted under-voltage control interlock.

Operation Technology, Inc. 9-34 ETAP PowerStation 4.0

Page 36: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Voltage Relay

Setting Settings of the under-voltage control interlock in percent of the selected Unit.

Unit Unit of the setting in V% or V/Hz%.

Voltage Relay Control Interlock Editor

Setting Settings of the overvoltage or undervoltage control interlock in percent of the selected Unit.

Unit Unit for the relay setting in V% or V/Hz%.

Circuit Breaker ID Select the ID of the circuit breaker to be controlled.

Action Action type of the circuit breaker, Open or Close.

Time Delay This is the time delay of the control action in seconds. The relay action will be reset if the operating voltage falls within the limit during the time delay period.

9.7.2 Remarks Page

Operation Technology, Inc. 9-35 ETAP PowerStation 4.0

Page 37: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Voltage Relay

User-Defined Info These fields allow you to keep track of extra data associated with this component. The names of the User-Defined (UD) fields can be changed from the Settings option in the Project menu in the Menu bar.

UD Field 1 (Eq. Ref.) This is a number field with the default name Eq. Ref. You can change the name of this field and enter the equipment reference number or any other number here, up to five digits.

UD Field 2 (Last Maint.) This is an alphanumeric field with the default name Last Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 3 (Next Maint.) This is an alphanumeric field with the default name Next Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 4 (Tests Req.) This is an alphanumeric field with the default name Tests Req. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A5 This is an alphanumeric field with the default name UD Field A5. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A6 This is an alphanumeric field with the default name UD Field A6. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A7 This is an alphanumeric field with the default name UD Field A7. You can change the name of this field and enter any extra data for this element here, up to 18 alphanumeric characters.

Drawing/Diagram

One-Line Enter the name or ID of a one-line drawing or diagram associated with this element, up to 50 alphanumeric characters. An example is the manufacturer diagram or specifications for this element.

Reference Enter the name or ID of a reference drawing or document for this element, up to 50 alphanumeric characters.

Manufacturer

Name Enter the manufacturer’s name for this element here, up to 25 alphanumeric characters.

Purchase Date Enter the date of purchase for this element here, up to 8 alphanumeric characters.

Operation Technology, Inc. 9-36 ETAP PowerStation 4.0

Page 38: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Voltage Relay 9.7.3 Comment Page Enter any extra data or comments regarding condition, maintenance, tests, or studies, associated with this element. This field can be up to 64kb with a default size of 4kb. To increase the size of this field, refer to the entries in the ETAPS.INI file.

When entering information in the page, use Ctrl+Enter to start a new paragraph. Standard keys such as Ctrl+X, Ctrl+C, and Ctrl+V can be used to cut, copy, and paste information.

Operation Technology, Inc. 9-37 ETAP PowerStation 4.0

Page 39: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Frequency Relay

9.8 Frequency Relay The properties associated with frequency relays are specified in Frequency Relay Editor. Same as voltage relays, frequency relays can be used in transient stability study. According to the specified circuit breaker control interlock functions and settings, transient stability program will check the monitored system quantities and compare them with the relay settings. When the control conditions are met, the associated control actions will be triggered. Frequency relays should be connected to a bus via a potential transformer. The Frequency Relay Editor contains four pages of information. • Info Page • Setting Page • Remarks Page • Comment Page

9.0.1 Info Page

Operation Technology, Inc. 9-38 ETAP PowerStation 4.0

Page 40: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Frequency Relay

Info

ID Enter a unique ID with up to 25 alphanumeric characters. PowerStation automatically assigns a unique ID to each frequency relay. The assigned IDs consist of the default frequency relay ID plus an integer, starting with the number one and increasing as the number of frequency relays increase. The default frequency relay ID (FR) can be changed from the Defaults Menu in the menu bar or from the Project View.

PT Display the connect PT ID.

In/Out of Service The operating condition of a frequency relay can be selected by choosing either the In Service or Out of Service options. The properties of an Out of Service relay can be edited like an In Service relay; however, an Out of Service relay will not display results of any system studies. When Continuity Check is activated, an Out of Service relay automatically becomes dimmed in the one-line diagram. Note that the In / Out of Service option is an engineering property which is independent of the configuration status. Therefore, you can set a relay to be In Service for the Base Data and Out of Service in Revision Data.

Equipment

FDR Tag Enter the feeder tag in this field, up to 25 alphanumeric characters.

Name Enter equipment name, up to 50 alphanumeric characters.

Description Enter equipment description, up to 100 alphanumeric characters.

Operation Technology, Inc. 9-39 ETAP PowerStation 4.0

Page 41: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Frequency Relay

9.8.1 Setting Page

OverFrequency Control Interlock Set and display the over-frequency control interlock data.

Add Button Click on this button to open the Frequency Relay Control Interlock Editor to set parameters for a new over-frequency control interlock parameters.

Edit Button Click on this button to open the Frequency Relay Control Interlock Editor and edit the properties of an existing over-voltage control interlock

Delete Button Click on this button to delete the highlighted over-frequency control interlock.

UnderFrequency Control Interlock Set and display the under-frequency control interlock data.

Add Button Click on this button to open the Frequency Relay Control Interlock Editor to set parameters for a new under-frequency control interlock parameters.

Edit Button Click on this button to open the Frequency Relay Control Interlock Editor and edit the settings of an existing under-frequency control interlock.

Delete Button Click on this button to delete the highlighted under- frequency control interlock.

Operation Technology, Inc. 9-40 ETAP PowerStation 4.0

Page 42: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Frequency Relay

Frequency Relay Control Interlock Editor

Setting This is the setting of the under-frequency and over-frequency relay in percent of the selected Unit.

Unit This is the unit for the relay setting in Hz or Hz/Sec.

Circuit Breaker ID Select the ID of the circuit breaker to be controlled.

Action Action type of the circuit breaker, Open or Close.

Time Delay Time delay of the control action in seconds. The relay action will be reset if the operating voltage falls within the limit during the time delay period.

9.8.2 Remarks Page

Operation Technology, Inc. 9-41 ETAP PowerStation 4.0

Page 43: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Frequency Relay

User-Defined Info These fields allow you to keep track of extra data associated with this component. The names of the User-Defined (UD) fields can be changed from the Settings option in the Project menu in the Menu bar.

UD Field 1 (Eq. Ref.) This is a number field with the default name Eq. Ref. You can change the name of this field and enter the equipment reference number or any other number here, up to five digits.

UD Field 2 (Last Maint.) This is an alphanumeric field with the default name Last Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 3 (Next Maint.) This is an alphanumeric field with the default name Next Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 4 (Tests Req.) This is an alphanumeric field with the default name Tests Req. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A5 This is an alphanumeric field with the default name UD Field A5. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A6 This is an alphanumeric field with the default name UD Field A6. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A7 This is an alphanumeric field with the default name UD Field A7. You can change the name of this field and enter any extra data for this element here, up to 18 alphanumeric characters.

Drawing/Diagram

One-Line Enter the name or ID of a one-line drawing or diagram associated with this element, up to 50 alphanumeric characters. An example is the manufacturer diagram or specifications for this element.

Reference Enter the name or ID of a reference drawing or document for this element, up to 50 alphanumeric characters.

Manufacturer

Name Enter the manufacturer’s name for this element here, up to 25 alphanumeric characters.

Purchase Date Enter the date of purchase for this element here, up to 8 alphanumeric characters.

Operation Technology, Inc. 9-42 ETAP PowerStation 4.0

Page 44: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Frequency Relay 9.8.3 Comment Page Enter any extra data or comments regarding condition, maintenance, tests, or studies, associated with this element. This field can be up to 64kb with a default size of 4kb. To increase the size of this field, refer to the entries in the ETAPS.INI file.

When entering information in the page, use Ctrl+Enter to start a new paragraph. Standard keys such as Ctrl+X, Ctrl+C, and Ctrl+V can be used to cut, copy, and paste information.

Operation Technology, Inc. 9-43 ETAP PowerStation 4.0

Page 45: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Reverse Power Relay

9.9 Reverse Power Relay The properties associated with reverse power relays of the electrical distribution system can be entered in this editor. The Reverse Power Relay Editor includes four pages of properties. • Info Page • Setting Page • Remarks Page • Comment Page

9.0.1 Info Page

Info

ID Enter a unique ID with up to 25 alphanumeric characters. PowerStation automatically assigns a unique ID to each reverse power relay. The assigned IDs consist of the default reverse power relay ID plus an integer, starting with the number one and increasing as the number of reverse power relay increase. The default reverse power relay ID (Relay32) can be changed from the Defaults Menu in the menu bar or from the Project View.

Operation Technology, Inc. 9-44 ETAP PowerStation 4.0

Page 46: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Reverse Power Relay CT Reverse power relays have two pins, one of which can be connected to a current transformer (CT) and the other pin can be connected to other current/power relays. A blank entry will be shown for the CT if the terminal of the reverse power relay is not directly connected to a CT or indirectly through other relays. If the terminal of a reverse power relay is connected to a CT or to a relay, which is connected to a CT, the ID of the CT will be displayed for the terminal connection.

Ratio This field displays the relay connected CT ratio.

In/Out of Service The operating condition of a reverse power current relay can be selected by choosing either the In Service or Out of Service options. The properties of an Out of Service relay can be edited like an In Service relay; however, an Out of Service relay will not display results of any system studies. When Continuity Check is activated, an Out of Service relay automatically becomes dimmed in the one-line diagram. Note that the In/Out of Service option is an engineering property, which is independent of the configuration status. Therefore, you can set a relay to be In Service for the Base Data and Out of Service in Revision Data.

Control Interlock

Device Set and display the reverse power control interlock data.

ID

Add Click on this button to open the reverse power Interlock Editor to set parameters for a new reverse power control interlock parameters, including Device type, device ID, and control Action.

Operation Technology, Inc. 9-45 ETAP PowerStation 4.0

Page 47: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Reverse Power Relay Edit Click on this button to open the reverse power Interlock Editor and edit the settings of an existing reverse power control interlock.

Delete Click on this button to delete the selected control interlock.

Equipment

FDR Tag Enter the feeder tag in this field, up to 25 alphanumeric characters.

Name Enter equipment name, up to 50 alphanumeric characters.

Description Enter equipment description, up to 100 alphanumeric characters.

9.9.1 Setting Page

Setting

Real Power Check this box if real power is used as trip setting. Pickup power base in MW is entered in the field next.

Operation Technology, Inc. 9-46 ETAP PowerStation 4.0

Page 48: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Reverse Power Relay Reactive Power Check this box if reactive power is used as trip setting. Pickup power base in Mvar is entered in the field next.

Over Power

Pickup Enter the setting for over power trip. If the measured power exceeds this value, the relay will trip. The setting is entered in percentage of the pickup power base.

Time Delay Enter the intentional relay time delay for over power trip in second.

Under Power

Pickup Enter the setting for under power trip. If the measured power drops below this value, the relay will trip. The setting is entered in percentage of the pickup power base.

Time Delay Enter the intentional relay time delay for under power trip in second.

9.9.2 Remarks Page

Operation Technology, Inc. 9-47 ETAP PowerStation 4.0

Page 49: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Reverse Power Relay

User-Defined Info These fields allow you to keep track of extra data associated with this component. The names of the User-Defined (UD) fields can be changed from the Settings option in the Project menu in the Menu bar.

UD Field 1 (Eq. Ref.) This is a number field with the default name Eq. Ref. You can change the name of this field and enter the equipment reference number or any other number here, up to five digits.

UD Field 2 (Last Maint.) This is an alphanumeric field with the default name Last Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 3 (Next Maint.) This is an alphanumeric field with the default name Next Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 4 (Tests Req.) This is an alphanumeric field with the default name Tests Req. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A5 This is an alphanumeric field with the default name UD Field A5. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A6 This is an alphanumeric field with the default name UD Field A6. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A7 This is an alphanumeric field with the default name UD Field A7. You can change the name of this field and enter any extra data for this element here, up to 18 alphanumeric characters.

Drawing/Diagram

One-Line Enter the name or ID of a one-line drawing or diagram associated with this element, up to 50 alphanumeric characters. An example is the manufacturer diagram or specifications for this element.

Reference Enter the name or ID of a reference drawing or document for this element, up to 50 alphanumeric characters.

Manufacturer

Name Enter the manufacturer’s name for this element here, up to 25 alphanumeric characters.

Purchase Date Enter the date of purchase for this element here, up to 8 alphanumeric characters.

Operation Technology, Inc. 9-48 ETAP PowerStation 4.0

Page 50: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Reverse Power Relay

9.9.3 Comment Page Enter any extra data or comments regarding condition, maintenance, tests, or studies, associated with this element. This field can be up to 64kb with a default size of 4kb. To increase the size of this field, refer to the entries in the ETAPS.INI file.

Operation Technology, Inc. 9-49 ETAP PowerStation 4.0

Page 51: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Solid State Trip Relay

9.10 Solid State Trip Relay The properties associated with solid state trip relays of the electrical distribution system can be entered in this editor. The Solid State Trip Relay Editor includes four pages of properties. • Info Page • Setting Page • Remarks Page • Comment Page

9.0.1 Info Page

Info

ID Enter a unique ID with up to 25 alphanumeric characters. PowerStation automatically assigns a unique ID to each solid state trip relay. The assigned IDs consist of the default solid state trip relay ID plus an integer, starting with the number one and increasing as the number of solid state trip relay increase. The default solid state trip relay ID (MVSST) can be changed from the Defaults Menu in the menu bar or from the Project View.

Operation Technology, Inc. 9-50 ETAP PowerStation 4.0

Page 52: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Solid State Trip Relay

CT Solid state trip relays have two pins, one of which can be connected to a current transformer (CT) and the other pin can be connected to other current/power relays. A blank entry will be shown for the CT if the terminal of the solid state trip relay is not directly connected to a CT or indirectly through other relays. If the terminal of a solid state trip relay is connected to a CT or to a relay, which is connected to a CT, the ID of the CT will be displayed for the terminal connection.

Ratio This field displays the relay connected CT ratio.

In/Out of Service The operating condition of a solid state trip relay can be selected by choosing either the In Service or Out of Service options. The properties of an Out of Service relay can be edited like an In Service relay; however, an Out of Service relay will not display results of any system studies. When Continuity Check is activated, an Out of Service relay automatically becomes dimmed in the one-line diagram. Note that the In/Out of Service option is an engineering property, which is independent of the configuration status. Therefore, you can set a relay to be In Service for the Base Data and Out of Service in Revision Data.

Control Interlock

Device Set and display the solid state trip control interlock data.

ID

Add Click on this button to open the solid state trip Interlock Editor to set parameters for a new solid state trip control interlock parameters, including Device type, device ID, and control Action.

Operation Technology, Inc. 9-51 ETAP PowerStation 4.0

Page 53: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Solid State Trip Relay

Edit Click on this button to open the solid state trip Interlock Editor and edit the settings of an existing solid state trip control interlock.

Delete Click on this button to delete the selected control interlock.

Equipment

FDR Tag Enter the feeder tag in this field, up to 25 alphanumeric characters.

Name Enter equipment name, up to 50 alphanumeric characters.

Description Enter equipment description, up to 100 alphanumeric characters.

9.10.1 Setting Page

Setting

Instantaneous Check this box for instantaneous relay action.

Setting Enter the pickup current as Relay Amp. The primary current is calculated and display as Primary Amp.

Time Delay Enter the intentional relay time delay for over power trip in second.

Operation Technology, Inc. 9-52 ETAP PowerStation 4.0

Page 54: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Solid State Trip Relay 9.10.2 Remarks Page

User-Defined Info These fields allow you to keep track of extra data associated with this component. The names of the User-Defined (UD) fields can be changed from the Settings option in the Project menu in the Menu bar.

UD Field 1 (Eq. Ref.) This is a number field with the default name Eq. Ref. You can change the name of this field and enter the equipment reference number or any other number here, up to five digits.

UD Field 2 (Last Maint.) This is an alphanumeric field with the default name Last Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 3 (Next Maint.) This is an alphanumeric field with the default name Next Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 4 (Tests Req.) This is an alphanumeric field with the default name Tests Req. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A5 This is an alphanumeric field with the default name UD Field A5. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A6 This is an alphanumeric field with the default name UD Field A6. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

Operation Technology, Inc. 9-53 ETAP PowerStation 4.0

Page 55: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Solid State Trip Relay UD Field A7 This is an alphanumeric field with the default name UD Field A7. You can change the name of this field and enter any extra data for this element here, up to 18 alphanumeric characters.

Drawing/Diagram

One-Line Enter the name or ID of a one-line drawing or diagram associated with this element, up to 50 alphanumeric characters. An example is the manufacturer diagram or specifications for this element.

Reference Enter the name or ID of a reference drawing or document for this element, up to 50 alphanumeric characters.

Manufacturer

Name Enter the manufacturer’s name for this element here, up to 25 alphanumeric characters.

Purchase Date Enter the date of purchase for this element here, up to 8 alphanumeric characters.

9.10.3 Comment Page Enter any extra data or comments regarding condition, maintenance, tests, or studies, associated with this element. This field can be up to 64kb with a default size of 4kb. To increase the size of this field, refer to the entries in the ETAPS.INI file.

When entering information in the page, use Ctrl+Enter to start a new paragraph. Standard keys such as Ctrl+X, Ctrl+C, and Ctrl+V can be used to cut, copy, and paste information.

Operation Technology, Inc. 9-54 ETAP PowerStation 4.0

Page 56: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Motor Relay

9.11 Motor Relay The properties associated with motor relays of the electrical distribution system can be entered in this editor. The Motor Relay Editor includes four pages of properties. Info Page Setting Page Remarks Page Comment Page

9.0.1 Info Page

Info

ID Enter a unique ID with up to 25 alphanumeric characters. PowerStation automatically assigns a unique ID to each motor relay. The assigned IDs consist of the default motor relay ID plus an integer, starting with the number one and increasing as the number of motor relay increase. The default motor relay ID (MTTR) can be changed from the Defaults Menu in the menu bar or from the Project View.

Operation Technology, Inc. 9-55 ETAP PowerStation 4.0

Page 57: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Motor Relay

CT Motor relays have two pins, one of which can be connected to a current transformer (CT) and the other pin can be connected to other current/power relays. A blank entry will be shown for the CT if the terminal of the motor relay is not directly connected to a CT or indirectly through other relays. If the terminal of a motor relay is connected to a CT or to a relay, which is connected to a CT, the ID of the CT will be displayed for the terminal connection.

Ratio This field displays the relay connected CT ratio.

In/Out of Service The operating condition of a motor relay can be selected by choosing either the In Service or Out of Service options. The properties of an Out of Service relay can be edited like an In Service relay; however, an Out of Service relay will not display results of any system studies. When Continuity Check is activated, an Out of Service relay automatically becomes dimmed in the one-line diagram. Note that the In/Out of Service option is an engineering property, which is independent of the configuration status. Therefore, you can set a relay to be In Service for the Base Data and Out of Service in Revision Data.

Control Interlock

Device Set and display the motor control interlock data.

ID

Add Click on this button to open the motor Interlock Editor to set parameters for a new motor control interlock parameters, including Device type, device ID, and control Action.

Operation Technology, Inc. 9-56 ETAP PowerStation 4.0

Page 58: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Motor Relay

Edit Click on this button to open the motor Interlock Editor and edit the settings of an existing motor control interlock.

Delete Click on this button to delete the selected control interlock.

Equipment

FDR Tag Enter the feeder tag in this field, up to 25 alphanumeric characters.

Name Enter equipment name, up to 50 alphanumeric characters.

Description Enter equipment description, up to 100 alphanumeric characters.

9.11.1 Setting Page

Setting

Instantaneous Check this box for instantaneous relay action.

Setting Enter the pickup current as Relay Amp. The primary current is calculated and display as Primary Amp.

Time Delay Enter the intentional relay time delay for over power trip in second.

Operation Technology, Inc. 9-57 ETAP PowerStation 4.0

Page 59: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Motor Relay 9.11.2 Remarks Page

User-Defined Info These fields allow you to keep track of extra data associated with this component. The names of the User-Defined (UD) fields can be changed from the Settings option in the Project menu in the Menu bar.

UD Field 1 (Eq. Ref.) This is a number field with the default name Eq. Ref. You can change the name of this field and enter the equipment reference number or any other number here, up to five digits.

UD Field 2 (Last Maint.) This is an alphanumeric field with the default name Last Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 3 (Next Maint.) This is an alphanumeric field with the default name Next Maint. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field 4 (Tests Req.) This is an alphanumeric field with the default name Tests Req. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

Operation Technology, Inc. 9-58 ETAP PowerStation 4.0

Page 60: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Motor Relay

UD Field A5 This is an alphanumeric field with the default name UD Field A5. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A6 This is an alphanumeric field with the default name UD Field A6. You can change the name of this field and enter any extra data for this element here, up to 12 alphanumeric characters.

UD Field A7 This is an alphanumeric field with the default name UD Field A7. You can change the name of this field and enter any extra data for this element here, up to 18 alphanumeric characters.

Drawing/Diagram

One-Line Enter the name or ID of a one-line drawing or diagram associated with this element, up to 50 alphanumeric characters. An example is the manufacturer diagram or specifications for this element.

Reference Enter the name or ID of a reference drawing or document for this element, up to 50 alphanumeric characters.

Manufacturer

Name Enter the manufacturer’s name for this element here, up to 25 alphanumeric characters.

Purchase Date Enter the date of purchase for this element here, up to 8 alphanumeric characters.

Operation Technology, Inc. 9-59 ETAP PowerStation 4.0

Page 61: ETAP PowerStation 4 - Home - .:: ISI Academy ::. Eng Courses/ETab... · Operation Technology, Inc. 9-1 ETAP PowerStation 4.0. AC Elements Current Transformer 9.1 Current Transformer

AC Elements Motor Relay

9.11.3 Comment Page Enter any extra data or comments regarding condition, maintenance, tests, or studies, associated with this element. This field can be up to 64kb with a default size of 4kb. To increase the size of this field, refer to the entries in the ETAPS.INI file.

When entering information in the page, use Ctrl+Enter to start a new paragraph. Standard keys such as Ctrl+X, Ctrl+C, and Ctrl+V can be used to cut, copy, and paste information.

Operation Technology, Inc. 9-60 ETAP PowerStation 4.0