2/2 Product overview
2/3 RCCBs, type AInstantaneousSIGRES Super resistant æSelective î
2/9 SIQUENCE, type BRCCBs, super resistant æRCCB, selective îRCBOs, super resistant æRCBOs, selective î
2/14 Additional components
2/17 RC units, type AInstantaneousSuper resistant æSelective î
2/22 RCBOs, type AInstantaneousSuper resistant æSelective î
2/27 Busbars
2/30 Accessories
2/31 Residual-current operated circuit breakers
BETA ProtectingResidual CurrentProtective Devices
Note: Only the chapters indicated in black contain selection and ordering data.
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
Product overview
2/2 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
Overview
Devices Page Field of application Standards Used in
Non
-res
iden
tial
bui
ldin
gs
Res
iden
tial
bui
ldin
gs
Ind
ustr
y
RCCBs, type A 2/3 Personnel, material and fire protection, as well as protection against direct contact SIGRES with active condensation protection for use in harsh environments. Super resistant and selective versions
IEC/EN 61008
SIQUENCE, type B 2/9 SIQUENCE, the technology of universal current-sensitive residual current protective devices
VDE 0664-100VDE 0664-200
Additional components 2/14 Remote controlled mechanisms, auxiliary switches for all residual current operated circuit breakers.
Leakage current measurement device for fault locating and the optimum selection of RCCBs
IEC/EN 62019
RC units, type A 2/17 The freely selectable combination of RC units with miniature circuit breakers permits the flexible configuration of RCBO combinations
IEC/EN 61009
RCBOs, type A 2/22 The ideal protection combination for all electrical circuits due to the compact device versions of RCCBs and MCBs in a single device
IEC/EN 61009
Busbars 2/27 Busbars in 10 and 16 mm2 save space in the distribution board and time during mounting.
--
Accessories 2/30 Locking devices, covers – everything you need for mounting
--
Residual-current operated circuit breakers
2/31 This section tells you all you need to know about RCCBs in combination with miniature circuit breakers, such as tripping characteristics, selectivity and breaking capacity
--
t
10000
2000
1000
500
200
100
50
20
ms
0,1 0,2 0,5 1 2 5 10 20 50 100
1
30 mA
2 3
10 mA
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RCCBs, type A
2/3Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Overview
RCCBs of type A are used in all systems up to 240/415 V AC. They trip in the event of both sinusoidal AC residual currents and pulsating DC residual currents.
RCCBs with a rated residual current of maximum 30 mA are used for personnel, material and fire protection, as well as for protection against direct contact. RCCBs with a rated residual current of 10 mA are primarily used in areas that represent an increased risk for personnel.
Since DIN VDE 0100-410 came into effect in June 2007, all socket outlet current circuits up to 20 A must now also be fitted with residual current protective devices with a rated residual current of max. 30 mA. This also applies to outdoor electrical circuits up to 32 A for the connection of portable equipment.
Devices with a rated residual current of maximum 300 mA are used as preventative fire protection in case of insulation faults. RCCBs with a rated residual current of 100 mA are primarily used outside Europe.
SIGRES
SIGRES RCCBs were developed for use in harsh ambient conditions, such as swimming baths as protection against chlorine and ozone, in the agricultural sector (ammonia), on building sites and in the chemical industry (nitrogen oxide, sulfur dioxide, solvents), in the food processing industry (hydrogen sulfide) and in unheated rooms (dampness). The patented active condensation protection requires the infeed from below with the RCCBs switched off.
Super resistant æ
Super resistant (short-time delayed) RCCBs meet the maximum permissible break times for instantaneous devices. However, by implementing a short-time delay they prevent unnecessary trippings, and thus plant faults, when pulse-shaped leakage currents occur - as is the case when capacitors are switched on.
Selective î
Selective RCCBs are used as upstream group switches for selective tripping as opposed to the downstream, instantaneous or super resistant RCCBs of type A. Selective RCCBs up to 300 mA are also used as preventative fire protection against insulation faults. The dimensioning of the rated residual current depends on the size of the plant.
Benefits• Instantaneous RCCBs with the N-connection on the left-hand side
enable simple bus-mounting with standard pin busbars with MCBs installed on the right-hand side
• Instantaneous RCCBs with the N connection on the right-hand side can be bus-mounted with MCBs using a special pin busbar
• Instantaneous devices have a surge current withstand capability with current waveform 8/20 µs of more than 1 kA, super resistant of more than 3 kA and selective of more than 5 kA. This ensures safe operation
• SIGRES has an extremely long service life due to patented active condensation protection and the same dimensions for the quick and easy replacement of instantaneous RCCBs already installed
• Super resistant devices increase plant availability, as unnecessary tripping is prevented in systems with short-time glitches
• Selective RCCBs increase plant availability, as in the event of a fault, a staggered tripping time enables the selective tripping of RCCBs connected in series
• Auxiliary switches or remote controlled mechanisms are also available as additional components
• The operating handle and the test button can be locked by means of a handle locking device.
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RCCBs, type A
2/4 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
Technical specifications
Instantaneous SIGRES Super resistant Selective
Standards IEC/EN 61008-1 (VDE 0664-10); IEC/EN 61008-2-1 (VDE0664-11); IEC/EN 61543 (VDE 0664-30)
Approved acc. to IEC 61008-1, IEC 61008-2-1; EN 61008-1, EN 61008-2-1
Surge current withstand capability
With current waveform 8/20 µs acc. to EN 60060-2 kA > 1 > 3 > 5
Rated breaking capacity A 10000
Minimum operational voltage for test function operation V AC 100
Terminal conductor cross-sections
• For 2 MW at In = 16 A, 25 A, 40 A mm2 1.0 ... 16
at In = 100 A, 125 A mm2 1.5 ... 50 -- -- --
• For 2.5 MW at In = 63 A, 80 A mm2 1.5 ... 25
• For 4 MW at In = 25 A, 40 A, 63 A, 80 A mm2 1.5 ... 25
at In = 125 A mm2 2.5 ... 50 -- -- 2.5 ... 50
Terminal tightening torque
• Up to In = 80 A Nm 2.5 ... 3.0
• At In = 100 A,125 A Nm 3.0 ... 3.5 -- -- 3.0 ... 3.5
Mains connection Top or bottom Bottom Top or bottom
Mounting position Any
Degree of protection acc. to EN 60529 (VDE 0470-1)
IP20, with connected conductors
Touch protection acc. to EN 50274 (VDE 0660-514)
Finger and back-of-hand safe
Service life test cycle acc. to IEC/EN 61008 Switching cycles
> 10000
Storage temperature °C -40 ... +75
Ambient temperature °C -25 ... +45, Marked with
Resistance to climate acc. to IEC 60068-2-30 28 cycles (55 °C; 95 % rel. air humidity)
CFC and silicone-free Yes
-25
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RCCBs, type A
2/5Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Selection and ordering data
Rated residual current
Rated current Max. permissi-ble short-circuit series fuse
MW DT Order No. Priceper PU
PG PU PS*/P. unit
Weightper P. unitapprox
I∆n In
mA A A Unit(s) Unit(s) kg
RCCBs, type A Instantaneous
up to 40 A
63 A and 80 A
1P+N; 125 ... 230 V AC; 50 ... 60 Hz
10 16 63 2 A 5SM3 111-6 007 1 1 0.230
30 16 63 2 A 5SM3 311-6 007 1 1 0.23025 5SM3 312-6 007 1 1 0.23040 5SM3 314-6 007 1 1 0.230
63 100 2.5 A 5SM3 316-6 007 1 1 0.32080 B 5SM3 317-6 007 1 1 0.320
100 N 2 B 5SM3 318-6KK 007 1 1 0.245
125 N B 5SM3 315-6KK 007 1 1 0.245
100 25 63 2 B 5SM3 412-6 007 1 1 0.23040 B 5SM3 414-6 007 1 1 0.230
63 100 2.5 B 5SM3 416-6 007 1 1 0.30080 B 5SM3 417-6 007 1 1 0.300
100 125 N 2 B 5SM3 418-6KK 007 1 1 0.245
125 N B 5SM3 415-6KK 007 1 1 0.245
300 25 63 2 A 5SM3 612-6 007 1 1 0.21040 A 5SM3 614-6 007 1 1 0.210
63 100 2.5 B 5SM3 616-6 007 1 1 0.28080 B 5SM3 617-6 007 1 1 0.280
100 A and 125 A:
100 125 N 2 B 5SM3 618-6KK 007 1 1 0.245
125 N B 5SM3 615-6KK 007 1 1 0.245
up to 80 A
125 A
3P+N; 230 ... 400 V AC; 50 ... 60 Hz
N-connection, right
30 25 100 4 5SM3 342-6 007 1 1 0.50040 5SM3 344-6 007 1 1 0.50063 5SM3 346-6 007 1 1 0.50080 A 5SM3 347-6 007 1 1 0.500125 125 A 5SM3 345-6 007 1 1 0.500
100 40 100 4 A 5SM3 444-6 007 1 1 0.46063 A 5SM3 446-6 007 1 1 0.460125 125 B 5SM3 445-6 007 1 1 0.480
300 25 100 4 A 5SM3 642-6 007 1 1 0.44040 A 5SM3 644-6 007 1 1 0.44063 A 5SM3 646-6 007 1 1 0.44080 A 5SM3 647-6 007 1 1 0.440125 125 A 5SM3 645-6 007 1 1 0.480
500 25 100 4 B 5SM3 742-6 007 1 1 0.44040 A 5SM3 744-6 007 1 1 0.44063 A 5SM3 746-6 007 1 1 0.440125 125 A 5SM3 745-6 007 1 1 0.480
N-connection, left
30 25 100 4 B 5SM3 342-6KL 007 1 1 0.50040 5SM3 344-6KL 007 1 1 0.50063 B 5SM3 346-6KL 007 1 1 0.50080 B 5SM3 347-6KL 007 1 1 0.500
300 25 100 4 B 5SM3 642-6KL 007 1 1 0.44040 B 5SM3 644-6KL 007 1 1 0.44063 B 5SM3 646-6KL 007 1 1 0.44080 B 5SM3 647-6KL 007 1 1 0.440
10 000
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RCCBs, type A
2/6 Siemens ET B1 · 2008
12
3456789101112131415
1716
* You can order this quantity or a multiple thereof.
RCCBs, type A Instantaneous, special versions
1P+N; 24 ... 125 V AC; 50 ... 60 Hz
30 16 63 2 B 5SM3 311-6KK13 007 1 1 0.280
3P+N; 500 V AC; 50 ... 60 Hz
30 25 63 4 B 5SM3 352-6 007 1 1 0.50040 B 5SM3 354-6 007 1 1 0.50063 B 5SM3 356-6 007 1 1 0.500
300 25 63 4 B 5SM3 652-6 007 1 1 0.44040 B 5SM3 654-6 007 1 1 0.44063 B 5SM3 656-6 007 1 1 0.440
3P+N; 230 ... 400 V AC, 50 ... 400 Hz
30 25 80 4 B 5SM3 342-6KK03 007 1 1 0.500
40 B 5SM3 344-6KK03 007 1 1 0.500
RCCBs, type A SIGRES instantaneous
1P+N; 125 ... 230 V AC; 50 ... 60 Hz
30 25 63 2 B 5SM3 312-6KK12 007 1 1 0.23040 B 5SM3 314-6KK12 007 1 1 0.230
63 100 2.5 B 5SM3 316-6KK12 007 1 1 0.32080 B 5SM3 317-6KK12 007 1 1 0.320
3P+N; 230 ... 400 V AC; 50 ... 60 Hz
30 25 100 4 B 5SM3 342-6KK12 007 1 1 0.50040 B 5SM3 344-6KK12 007 1 1 0.50063 B 5SM3 346-6KK12 007 1 1 0.50080 B 5SM3 347-6KK12 007 1 1 0.500
300 40 100 4 B 5SM3 644-6KK12 007 1 1 0.44063 B 5SM3 646-6KK12 007 1 1 0.440
RCCBs, type A SIGRES, selective î
3P+N; 230 ... 400 V AC; 50 ... 60 Hz
300 63 100 4 B 5SM3 646-8KK12 007 1 1 0.440
Rated residual current
Rated current Max. permissi-ble short-circuit series fuse
MW DT Order No. Priceper PU
PG PU PS*/P. unit
Weightper P. unitapprox
I∆n In
mA A A Unit(s) Unit(s) kg
10 000
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RCCBs, type A
2/7Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
RCCBs, type A Super resistant æ
1P+N; 230 ... 400 V AC; 50 ... 60 Hz
30 25 63 N 2 B 5SM3 312-6KK01 007 1 1 0.230
40 N B 5SM3 314-6KK01 007 1 1 0.230
63 100 N 2.5 B 5SM3 316-6KK01 007 1 1 0.320
300 63 100 N 2.5 B 5SM3 616-6KK01 007 1 1 0.320
3P+N; 230 ... 400 V AC; 50 ... 60 Hz
30 25 100 4 B 5SM3 342-6KK01 007 1 1 0.50040 B 5SM3 344-6KK01 007 1 1 0.50063 B 5SM3 346-6KK01 007 1 1 0.500
300 40 100 N 4 B 5SM3 644-6KK01 007 1 1 0.492
63 N B 5SM3 646-6KK01 007 1 1 0.491
80 N B 5SM3 647-6KK01 007 1 1 0.493
RCCBs, type A Selective î
1P+N; 125 ... 230 V AC; 50 ... 60 Hz
100 63 100 2.5 B 5SM3 416-8 007 1 1 0.300
300 40 100 N 2 B 5SM3 614-8 007 1 1 0.250
63 2.5 A 5SM3 616-8 007 1 1 0.28080 N B 5SM3 617-8 007 1 1 0.320
up to 80 A
3P+N; 230 ... 400 V AC; 50 ... 60 Hz
N-connection, right
100 40 100 4 B 5SM3 444-8 007 1 1 0.46063 B 5SM3 446-8 007 1 1 0.460
300 40 100 4 A 5SM3 644-8 007 1 1 0.44063 A 5SM3 646-8 007 1 1 0.440125 125 A 5SM3 645-8 007 1 1 0.480
500 125 125 4 B 5SM3 745-8 007 1 1 0.4801000 63 100 4 A 5SM3 846-8 007 1 1 0.515
125 A
N-connection, left
300 63 100 4 B 5SM3 646-8KL 007 1 1 0.440
Rated residual current
Rated current Max. permissi-ble short-circuit series fuse
MW DT Order No. Priceper PU
PG PU PS*/P. unit
Weightper P. unitapprox
I∆n In
mA A A Unit(s) Unit(s) kg
10 000
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RCCBs, type A
2/8 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
Dimensional drawings
Schematics
Note:The infeed for SIGRES devices must be from below at terminals 2, 4, 6 and N.
RCCB up to 80 A
1P+N2 MW
1P+N2.5 MW
3P+N4 MW
RCCBs 100 and 125 A
1P+N, 2 MW 3P+N, 4 MW
T
N2
N1
36
T
N2
N1
45
T
72
N642
N531
45 90
44647
I2_07860c
45 88
443665770
N2
N1
I2_1
2856
a
72
1/L1 3/L2 5/L3 7/N
2/L1 4/L2 6/L3 8/N
I2_0
7830
a
45 87
4465768
1P+N 3P+Nup to 80 AN-connection, right
3P+N100 A, 125 A
N-connection, left
I2_1
3636
2 N
1 N
I2_1
3637
2 4 6 N
1 5 N3
I2_1
3639
2 4 6 N
1 5 N3
I2_1
3638
2 4 6N
N 3 51
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
SIQUENCE, type B
2/9Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Overview
Frequency converters, medical devices and UPS systems are seeing increasing usage in industry. Smooth DC residual currents or currents with low residual ripple may occur in the event of faults on these devices.
Type A residual current protective devices are unable to detect these smooth DC residual currents. Furthermore, such smooth DC residual currents make Type A devices increasingly insensitive to AC residual currents and pulsating DC residual currents. Hence if a fault occurs, there is no tripping and the desired protective function is no longer assured.
Universal current-sensitive residual current protective devices of Type B have an additional transformer which is supplied with a control signal. It is therefore possible to evaluate the change of the transformer's operating range caused by smooth DC residual currents. The desired protective function is thus assured.
The devices in this series are designed as residual current operated circuit breakers (RCCBs) up to 80 A and as residual current circuit breakers with integral overcurrent protection (RCBOs) for 100 A or 125 A in Characteristics C or D.
Benefits• Universal current-sensitive residual current protective devices detect
not only AC residual currents and pulsating DC residual currents, but also smooth DC residual currents, thus ensuring the desired protective function with all types of residual current.
• The tripping characteristic is adapted to the increase of leakage currents at higher frequencies in systems with capacitive impedances and results in increased operating safety.
• The RCBO is a compact device for up to 125 A. It provides not only personnel, property and fire protection but also overload and short-circuit protection for cables. This enables great savings on wiring and installation costs.
Technical specifications
5SM3cRCCBs
5SU1RCBOs
Standards IEC/EN 61008-1 (VDE 0664-10) IEC/EN 61008-2-1 (VDE 0664-11) IEC/EN 61543 (VDE 0664-30) VDE 0664-100
IEC/EN 61009-1 (VDE 0664-20) IEC/EN 61009-2-1 (VDE 0664-21) IEC/EN 61543 (VDE 0664-30) VDE 0664-200
Approved acc. to VDE 0664-100 VDE 0664-200
Versions 3P+N 4P
Tripping characteristic -- C, D
Surge current withstand capability with current waveform 8/20 µs acc. to EN 60060-2
• Super resistant kA > 3
• Selective kA > 5
Minimum operational voltage for test function operation V AC 150
Rated voltages Un V AC 400 400, 480
Rated frequency fn Hz 50 ... 60
Rated currents In A 25, 40, 63, 80 100, 125
Rated residual currents I∆n mA 30, 300
Rated switching capacity
• Im A 800 --
• Icn kA -- 10
Conductor cross-sections
• Solid and stranded mm2 1.5 ... 25 6 ... 50
• Finely stranded, with end sleeve mm2 1.5 ... 16 6 ... 35
Terminal tightening torque Nm 2.5 ... 3.0 3.0 ... 3.5
Mains connection Either top or bottom
Mounting position Any
Degree of protection acc. to EN 60529 (VDE 0470-1)
IP20, with connected conductors
Touch protection acc. to EN 50274 (VDE 0660-514)
Finger and back-of-hand safe
Service life Test cycle acc. to VDE 0664 Switching cycles
> 10000
Storage temperature °C -40 ... +75
Ambient temperature °C -25 ... +45, Marked with
Resistance to climate acc. to IEC 60068-2-30 28 cycles (55 °C; 95 % rel. air humidity)
CFC and silicone-free Yes
-25
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
SIQUENCE, type B
2/10 Siemens ET B1 · 2008
12
3456789101112131415
1716
* You can order this quantity or a multiple thereof.
Selection and ordering data
Rated residual current
Rated current Max. permissible short-circuit series fuse
MW DT Order No. Priceper PU
PG PU PS*/P. unit
Weightper P. unitapprox
I∆n InmA A A Unit(s) Unit(s) kg
SIQUENCE RCCBs, type B Super resistant æ
3P+N; 230 ... 400 V AC; 50 ... 60 Hz
30 25 100 4 A 5SM3 342-4 008 1 1 0.60040 A 5SM3 344-4 008 1 1 0.60063 A 5SM3 346-4 008 1 1 0.60080 B 5SM3 347-4 008 1 1 0.600
300 25 100 4 5SM3 642-4 008 1 1 0.52040 A 5SM3 644-4 008 1 1 0.52063 A 5SM3 646-4 008 1 1 0.52080 B 5SM3 647-4 008 1 1 0.520
500 63 100 N 4 B 5SM3 746-4 008 1 1 0.520
80 N B 5SM3 747-4 008 1 1 0.520
SIQUENCE RCCBs, type B Selective î
3P+N; 230 ... 400 V AC; 50 ... 60 Hz
300 63 100 N 4 B 5SM3 646-5 008 1 1 0.520
80 N B 5SM3 647-5 008 1 1 0.520
500 63 100N
4 B 5SM3 746-5 008 1 1 0.520
80N
B 5SM3 747-5 008 1 1 0.520
SIQUENCE RCBOs, type B Super resistant æ,rated switching capacity 10 kA
4P; 400 V AC; 50 ... 60 Hz
Characteristic C
30 100 11 B 5SU1 374-7AK81 011 1 1 2.050125 B 5SU1 374-7AK82 011 1 1 2.050
300 100 11 B 5SU1 674-7AK81 011 1 1 2.050125 B 5SU1 674-7AK82 011 1 1 2.050
Characteristic D
30 100 11 B 5SU1 374-8AK81 011 1 1 2.050300 100 11 B 5SU1 674-8AK81 011 1 1 2.050
4P; 480 V AC; 50 ... 60 Hz
Characteristic C
300 100 11 B 5SU1 674-7CK81 011 1 1 2.050125 B 5SU1 674-7CK82 011 1 1 2.050
SIQUENCE RCBOs, type B Selective î,rated switching capacity 10 kA
4P; 400 V AC; 50 ... 60 Hz
Characteristic C
300 125 11 B 5SU1 674-7BK82 011 1 1 1.950
Characteristic D
300 100 11 B 5SU1 674-8BK81 011 1 1 1.950
10 000
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
SIQUENCE, type B
2/11Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Dimensional drawings
Schematics
SIQUENCE RCCBs, Type B
3P+N, 4 MW
SIQUENCE RCBO, type B
4P, 11 MW
45 90m
ax 6
7
I2_1
3622
7198 4470
SIQUENCE RCCBs, type B
3P+N, 4 MW
SIQUENCE RCBO, type B
4P, 11 MW
1 3 5 N
2 4 6 N
I2_1
3765
Y1 Y2 1 3 5 7
2 4 6 8
I2_1
3766
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
SIQUENCE, type B
2/12 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
More information
Device setup
Universal current-sensitive residual current protective devices are based on a pulse-current-sensitive circuit-protection device with tripping independent of line voltage, supplemented with an auxiliary unit for the detection of smooth DC residual currents. The diagrams below show the basic design.
The summation current transformer W1 monitors the electrical system for AC and pulse current-type residual currents. The summation current transformer W2 detects the smooth DC residual currents and, in the event of a fault, relays the tripping command through electronic unit E to release A, which uses the mechanics to disconnect the circuit.
Design of RCCBs
Design of RCBOs
Method of operation
The universal current-sensitive residual current protective devices work independent of the supply voltage compliant with current requirements in Germany for type A acc. to DIN VDE 0664-100.
A voltage supply is required solely for the detection of smooth DC residual currents by a second transformer. This is done from all system cables and is dimensioned so that the electronics still reliably trip even with a voltage reduction to 50 V.
This ensures tripping for smooth DC residual currents, as long as such residual current waveforms can occur, even in the event of faults in the electrical power supply, e.g. an N-conductor break. This means that the pulse-current-sensitive switch part, which trips regardless of line voltage, will still reliably trigger the tripping operation – even in the highly unlikely event that two outer conductors and the neutral conductor fail – if the remaining intact outer conductor presents a hazard.
The residual current protective devices of type B are suitable for use in three-phase current systems before input circuits with rectifiers. They are not intended for use in DC systems and in networks with operating frequencies other than 50 or 60 Hz.
RCBOs are a combination of RCCB and miniature circuit breaker for up to 125 A in a single compact device.
It thus provides not only personnel, property and fire protection but also overload and short-circuit protection for cables. The mechanics of the RCCB act on the tripping unit of the miniature circuit breaker, which disconnects the circuit.
Protective effect at high frequencies
In addition to the described residual current waveforms (AC residual currents, pulsating and smooth DC residual currents), AC residual currents with a wide range of frequencies may also occur on electronic equipment such as rectifiers in frequency converters or computer tomographs a well as at the outgoing terminal of a frequency converter.
Requirements for frequencies up to 2 kHz are defined in the device regulations DIN VDE 0664-100.
To date, only limited statements can be made with regard to the risk of ventricular fibrillations (up to 1 kHz) for frequencies higher than 100 Hz. No reliable statements can be made on any further effects of thermal or electrolytic influence on the human organism.
For this reason, protection against direct contact is only possible for frequencies up to 100 Hz.
For higher frequencies, protection against indirect contact must be implemented under consideration of the frequency response of the residual current protective device, the maximum permissible touch voltages up to 50 V and permissible grounding resistance derived from this information.
M Mechanics of the RCCB
MCB Miniature circuit breaker part
A Release
E Electronics for tripping in the event of smooth DC residual currents
n Secondary winding
W1 Summation current transformer for detection of sinusoidal residual currents
W2 Summation current transformer for detection of smooth DC residual currents
T Test button
E
642 N
T
An
n
W1
W2
I2_13608a
M
531 N
E
642 8
T
An
n
W1
W2
I2_13609a
531 7
M LS
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
SIQUENCE, type B
2/13Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Versions
Super resistant æ short-time delayed tripping in the case of transient leakage currents. High surge current withstand capability: > 3 kA.
Selective î: can be used as upstream group switch for selective tripping contrary to a downstream standard RCCB.
Configuration
DIN VDE 0100-530 "Selection of protective devices" also describes the configuration of systems with residual current protective devices.
EN 50178 "Equipping power installations with electronic equipment" de-scribes, among other things, how to select the type ofresidual cur-rent protective device suitable.
When configuring and installing electrical installations, electrical loads that can generate smooth DC residual currents in the event of a fault must be assigned a separate electrical circuit with a universal current-sensitive residual current protective device (type B) (see configuration example).
It is not permitted to branch electrical circuits with these types of electrical loads after pulse-current-sensitive residual current protective devices (type A):
Sn
n n
≥
≤ ≥
I2_1
3610
a
TypeAC/A
300 mA
TypeAC/A
100 mA
TypeB
30 mA
Wh
230/400 V AC, 3-phase
Wh
TypeAC/A
n 300 mA
TypeAC/A
n 100 mA
TypeB
n 30 mA
≥
≤ ≥
S
I2_1
3611
a
230/400 V AC, 3-phase
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
Additional components
2/14 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
Overview
Auxiliary switches (AS) signal the contact position of the RCCB.
Remote controlled mechanisms are used for the remote ON/OFF switching of RCCBs. They also enable local manual switching. A blocking function permits maintenance work. If the RCCB is tripped, an acknowledgment must be carried out prior to switching back on.
The leakage current measurement device detects the leakage currents – like the circuit breaker – thus providing a direct statement as to the current loading of the RCCB. It is used to measure leakage currents up to 300 mA. This requires a voltmeter with an internal resistance more than 1 MΩ/V and a measuring range for AC voltages of Urms = 1 mV to 2 V. For the fault-free operation of an RCCB, the measured leakage current should be no greater than 1/3 of the rated residual current.
Benefits• Using captive brackets, the remote controlled mechanism can be
attached (or retrofitted) to the right-hand side of the basic device without the need for tools
• Bus systems, such as instabus KNX EIB, AS-Interface bus or PROFIBUS, can be integrated in the communication over binary inputs
• The leakage current measurement device enables the systematic selection of the rated residual current, thus preventing the inadvertent tripping of RCCBs.
Technical specifications
Auxiliary switches (AS) Auxiliary switches (AS)5SW3 30. 5SW3 330
Standards IEC/EN 62019 (VDE 0640)
Approved acc. to IEC 62019; EN 62019
Terminals
• Conductor cross-section mm2 0.75 ... 2.5
• Tightening torques Nm 0.6 ... 0.8
Short-circuit protection B6 or C6 or gL/gG 6 A fuse
Min. contact load 50 mA/24 V
Max. contact load
• 230 V AC, AC-12 A 6 5
• 230 V AC, AC-14 A 3.6 –
• 220 V DC, DC-12 A 1 0.5
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
Additional components
2/15Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Selection and ordering data
Version MW DT Order No. Priceper PU
PG PU PS*/P. unit
Weightper P. unitapprox
Unit(s) Unit(s) kg
Auxiliary switches (AS)for 5SM3 RCCBs up to 80 A
1 NO + 1 NC 0.5 5SW3 300 008 1 1/10 0.042
2 NC 0.5 C 5SW3 301 008 1 1/10 0.042
2 NO 0.5 A 5SW3 302 008 1 1/10 0.042
Auxiliary switches (AS)for 5SM3 RCCBs up to 125 A, 3P+N
1 NO + 1 NC 0.5 B 5SW3 330 008 1 1 0.040
Remote controlled mechanisms (RC) for 5SM3 RCCBs up to 80 A
Rated voltage Un = 230 V AC 3.5 B 5ST3 051 027 1 1 0.395
Leakage current measurement devices
Rated voltage Un = 500 V AC; 50 ... 60 Hz; 4P
4 B 5SM1 930-0 008 1 1 0.430
Rated residual current I∆n = 0 ... 300 mA
Rated current In = 63 A
Covers for connection terminals
For residual current operated circuit breakers up to 80 A,sealable (2 units in plastic bag)
2 A 5SW3 010 008 1 1/50 0.003
2.5 A 5SW3 011 008 1 1/50 0.004
4 A 5SW3 008 008 1 1/50 0.006
Locking devices
For RCCBs up to 80 A,sealable and lockable
4.5 mm lock hasp diameter B 5SW3 303 008 1 1 0.008
Padlocks
For 5SW3 303 locking device 5ST3 802 027 1 1 0.027
Locking devices with padlock
Comprising 5SW3 303 locking device and 5ST3 802 padlock
B 5SW3 312 008 1 set 1 set 0.035
I2_1
3711
a
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
Additional components
2/16 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
Dimensional drawings
Schematics
More informationGossen-Metrawatt offers suitable test devices for RCCB function tests and for testing protective measures.
Information is available at:Gossen-Metrawatt GmbH Thomas-Mann-Str. 16-20 D-90471 NurembergTel. +49 (0)9 11/86 02-111Fax +49 (0)9 11/86 02-777http://www.gmc-instruments.come-mail: [email protected]
Auxiliary switches (AS) for RCCBs for 5SM3 up to 80 A
Auxiliary switches (AS) for RCCBs for 5SM3 up to 125 A, 3P+N
Remote controlled mechanism Leakage current measurement device
9045
I2_1
2624
74736
44
63
I2_0
7843
b
74455
72
45 90
N642
N531
Auxiliary switches (AS) for RCCBs for 5SM3 up to 80 A
Auxiliary switches (AS) for RCCBs for 5SM3 up to 125 A, 3P+N
Remote controlled mechanism Leakage current measurement device
21 13
22 14
21 11
22 12
23 13
24 14
≥ 1 MΩ/V
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RC units, type A
2/17Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Overview
RC units of type A can be used in all systems up to 240/415 V AC. They trip in the event of both sinusoidal AC fault currents and pulsating DC residual currents.
RCCBs with a rated residual current of maximum 30 mA are used for personnel, material and fire protection, and for additional protection against direct contact.
Devices with a rated residual current of maximum 300 mA are used as preventative fire protection in case of insulation faults.
RC units are combined with MCBs with characteristics A, B, C and D, provided that these are available in the MCB range. The two compo-nents are simply plugged together without the need for any tools.
They then form a combination of RCCB and MCB for personnel, fire and line protection.
Super resistant æ
Super resistant (short-time delayed) RC units satisfy the maximum permissible break times for instantaneous devices. However, by implementing a short-time delay they prevent unnecessary trippings, and thus plant faults, when pulse-shaped leakage currents occur – as is the case when capacitors are switched on.
Selective î
Selective RC units are used as upstream group switches for selective tripping as opposed to the downstream, instantaneous or super resistant residual current protective device of type A. Selective RC units up to 300 mA are also used as preventative fire protection against insulation faults.
The dimensioning of the rated residual current depends on the size of the plant.
Benefits• Our wide variety of RC unit types and comprehensive range of miniature
circuit breakers offer a huge spectrum of combinations for all applications
• All devices have surge current withstand capability of more than 1 kA, thus ensuring safe and reliable operation
• All additional components for miniature circuit breakers can be retrofitted on the right-hand side
• All 100 A and 125 A RC units offer external remote tripping over terminals Y1/Y2. This supports implementation of central OFF circuits
• Both components can be simply plugged into each other and secured with captive metal brackets – no tools required. This saves considerable time when mounting.
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RC units, type A
2/18 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
Technical specifications
5SM2
Standards IEC/EN 61009-1 (VDE 0664-20), IEC/EN 61009-2-1 (VDE 0664-21)IEC/EN 61543 (VDE 0664-30)
Approved acc. to EN 61009-1, EN 61009-2-1; IEC 61009-1, IEC 61009-2-1
Surge current withstand capability With current waveform 8/20 µs acc. to EN 60060-2• Instantaneous kA > 1• Super resistant kA > 3• Selective kA > 5
Minimum operational voltage for test function operation• Up to In = 63 A, 2 and 3-pole V AC 195• Up to In = 63 A, 4-pole V AC 100• At In = 80 ... 100 A V AC 100
Rated voltage Un V AC 230 ... 400
Rated frequency fn Hz 50 ... 60
Rated currents In A 0.3 ... 16; 0.3 ... 40; 0.3 ... 63; 80 ... 100
Rated residual currents I∆n mA 10, 30, 100, 300, 500, 1000
Terminal conductor cross-sections• Up to In = 63 A mm2 1.5 ... 25• At In = 80 ... 100 A mm2 6.0 ... 50
Terminal tightening torque Nm 2.5 ... 3.0
Mains connection Either top or bottom
Mounting position Any
Degree of protection acc. to EN 60529 (VDE 0470-1) IP20, with connected conductors
Touch protection acc. to EN 50274 (VDE 0660-514) Finger and back-of-hand safe
Service life Test cycle acc. to EN 61009 > 10000 switching cycles
Storage temperature °C -40 ... +75
Ambient temperature °C -25 ... +45,Marked with
Resistance to climate acc. to IEC 60068-2-30 28 cycles (55 °C; 95 % rel. humidity)
CFC and silicone-free Yes
-25
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RC units, type A
2/19Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Selection and ordering data
Rated current Rated residual current
MW DT Order No. Priceper PU
PG PU PS*/P. unit
Weightper P. unitapprox
In I∆n
A mA Unit(s) Unit(s) kg
RC units, type A, Instantaneous tripping
For 5SY miniature circuit breakersbut not for 5SY5 and 5SY6 0..
2P, 230 ... 400 V AC, 50 ... 60 Hz
0.3 ... 16 10 2 B 5SM2 121-6 007 1 1 0.180
0.3 ... 40 30 5SM2 322-6 007 1 1 0.170300 A 5SM2 622-6 007 1 1 0.170
0.3 ... 63 30 A 5SM2 325-6 007 1 1 0.170100 B 5SM2 425-6 007 1 1 0.170300 B 5SM2 625-6 007 1 1 0.170500 B 5SM2 725-6 007 1 1 0.170
3P, 230 ... 400 V AC, 50 ... 60 Hz
0.3 ... 40 30 3 A 5SM2 332-6 007 1 1 0.260300 A 5SM2 632-6 007 1 1 0.260
0.3 ... 63 30 B 5SM2 335-6 007 1 1 0.260100 B 5SM2 435-6 007 1 1 0.260300 B 5SM2 635-6 007 1 1 0.260500 B 5SM2 735-6 007 1 1 0.260
4P, 230 ... 400 V AC, 50 ... 60 Hz
0.3 ... 40 30 3 5SM2 342-6 007 1 1 0.290300 5SM2 642-6 007 1 1 0.290
0.3 ... 63 30 A 5SM2 345-6 007 1 1 0.290100 B 5SM2 445-6 007 1 1 0.290300 A 5SM2 645-6 007 1 1 0.290500 A 5SM2 745-6 007 1 1 0.290
For 5SP4 miniature circuit breakers
2P; 125 ... 230 V AC, 50 ... 60 Hz
80 ... 100 30 3.5 B 5SM2 327-6 007 1 1 0.410300 B 5SM2 627-6 007 1 1 0.410
4P; 230 ... 400 V AC, 50 ... 60 Hz
80 ... 100 30 5 B 5SM2 347-6 007 1 1 0.630300 A 5SM2 647-6 007 1 1 0.630
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RC units, type A
2/20 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
RC units, type A Super resistant æ
For 5SY miniature circuit breakersbut not for 5SY5 and 5SY6 0..
2P, 230 ... 400 V AC, 50 ... 60 Hz
0.3 ... 40 30 N 2 B 5SM2 322-6KK01 007 1 1 0.350
0.3 ... 63 30 N B 5SM2 325-6KK01 007 1 1 0.350
3P, 230 ... 400 V AC, 50 ... 60 Hz
0.3 ... 40 30 N 3 B 5SM2 332-6KK01 007 1 1 0.365
0.3 ... 63 30 N B 5SM2 335-6KK01 007 1 1 0.365
4P, 230 ... 400 V AC, 50 ... 60 Hz
0.3 ... 40 30 3 B 5SM2 342-6KK01 007 1 1 0.290
0.3 ... 63 30 B 5SM2 345-6KK01 007 1 1 0.290
RC units, type A Selective î
For 5SY miniature circuit breakersbut not for 5SY5 and 5SY6 0..
2P, 230 ... 400 V AC, 50 ... 60 Hz
0.3 ... 40 300 2 A 5SM2 622-8 007 1 1 0.170
0.3 ... 63 300 B 5SM2 625-8 007 1 1 0.170
3P, 230 ... 400 V AC, 50 ... 60 Hz
0.3 ... 63 300 3 B 5SM2 635-8 007 1 1 0.260500 B 5SM2 735-8 007 1 1 0.4001000 B 5SM2 835-8 007 1 1 0.260
4P, 230 ... 400 V AC, 50 ... 60 Hz
0.3 ... 63 300 3 A 5SM2 645-8 007 1 1 0.290500 A 5SM2 745-8 007 1 1 0.4001000 A 5SM2 845-8 007 1 1 0.290
For 5SP4 miniature circuit breakers
2P; 125 ... 230 V AC, 50 ... 60 Hz
80 ... 100 300 3.5 B 5SM2 627-8 007 1 1 0.410
4P; 230 ... 400 V AC, 50 ... 60 Hz
80 ... 100 300 5 A 5SM2 647-8 007 1 1 0.6301000 A 5SM2 847-8 007 1 1 0.630
Rated current Rated residual current
MW DT Order No. Priceper PU
PG PU PS*/P. unit
Weightper P. unitapprox
In I∆n
A mA Unit(s) Unit(s) kg
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RC units, type A
2/21Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Dimensional drawings
Schematics
RC units for 5SY
2P 3P 4P
RC units for 5SP4
2P 4P
RC units for 5SY
2P 3P 4P
RC units for 5SP4
2P 4P
I2_13640a 2/1 4/3
1 3(N)
2 4 I2_13641a 2/1 4/3 6/5
1 53
2 64 I2_13642a 2/1 4/3 6/5 8/7
1 5 7(N)3
2 6 84
I2_13643a 2/1 4/3
1 3(N)
2 4
Y2Y1
I2_13644a 2/1 4/3 6/5 8/7
1 5 7(N)3
2 6 84
Y1 Y2
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RCBOs, type A
2/22 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
Overview
RCBOs are a combination of an RCCB and a miniature circuit breaker in a compact design for personnel, fire and line protection. For personnel and fire protection, the residual current part of the type A trips in the event of sinusoidal AC residual currents and pulsating DC residual currents.
RCBOs with a rated residual current of maximum 30 mA are used for personnel, material and fire protection, as well as for protection against direct contact. RCBOs with a rated residual current of 10 mA are primarily used in areas that represent an increased risk for personnel and the outdoor installations of residential buildings.
Devices with a rated residual current of maximum 300 mA are used as preventative fire protection in case of insulation faults.
The MCB part of the RCBO protects lines against overload and short circuits and is available in characteristics B and C.
Since DIN VDE 0100-410 came into effect in June 2007, all socket outlet current circuits up to 20 A must now also be fitted with residual current protective devices with a rated residual current of max. 30 mA. This also applies to outdoor electrical circuits up to 32 A for the connection of portable equipment.
In order to implement this protection, we recommend the use of RCBOs with 30 mA.
Assignment to each individual branch circuit, helps prevent the unwanted tripping of fault-free circuits induced by the accumulation of operation-related leakage currents or by transient current pulses during switching operations.
Additional components of the 5SY miniature circuit breakers can be mounted at the side and carry out additional functions.
For further details on additional components, please refer to the chapter "Miniature circuit breakers".
Benefits
For all versions • Clear and visible conductor connection that can be easily checked
in front of the busbar.• Large and easily accessible wiring space enables easy insertion of
conductor in the terminals.• The surge current withstand capability of more than 1 kA ensures
safe and reliable operation.• All additional components for miniature circuit breakers can be
retrofitted on the right-hand side.
For all 10 kA versions up to 40 A• Integrated movable terminal covers located at the cable entries
ensure the terminals are fully insulated when the screws are tightened. The effective touch protection when grasping the device considerably exceeds the requirements of BGV A3.
• The RCBOs can be quickly and easily removed from the assembly by hand if connections need to be replaced. This saves time if parts need to be replaced because the busbars no longer need to be freed from the adjacent miniature circuit breakers.
For all 125 A versions• The RCBOs offer external remote tripping over terminals Y1/Y2.
This supports implementation of central OFF circuits.
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RCBOs, type A
2/23Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Technical specifications
Selection and ordering data
up to 40 A 125 A
Standards IEC/EN 61009-1 (VDE 0664-10), IEC/EN 61009-2-1 (VDE 0664-11)IEC/EN 61543; VDE 0664-30
Approved acc. to IEC/EN 61009-1, IEC/EN 61009-2-1; EN 61009-1, EN 61009-2-1
Rated voltages Un V AC 125 ... 230 400
Rated frequency fn Hz 50 ... 60
Rated currents In A 6, 8, 10, 13, 16, 20, 25, 32, 40 125
Rated residual currents I∆n mA 10, 30, 300 30, 300, 1000
Rated switching capacity kA 6, 10 10
Energy limitation class 3 --
Surge current withstand capabilitywith current waveform 8/20 µs acc. to EN 60060-2• Instantaneous kA > 1• Super resistant kA > 3 --• Selective kA > 5
Terminal conductor cross-sections• Solid and stranded mm2 0.75 ... 35 6 ... 50• Finely stranded with end sleeve mm2 0.75 ... 25 6 ... 35
Terminal tightening torque Nm 2.5 ... 3.0 3.0 ... 3.5
Mains connection Top or bottom
Mounting position Any
Degree of protection acc. to EN 60529 (VDE 0470-1)
IP20, with connected conductors
Touch protection acc. to EN 50274 (VDE 0660-514)
Finger and back-of-hand safe
Service life Test cycle acc. to IEC/EN 61009
Switching cycles
> 10000
Storage temperature °C -40 ... +75
Ambient temperature °C -25 ... +45, Marked with
Resistance to climate acc. to IEC 60068-2-30 28 cycles (55 °C; 95 % rel. air humidity)
CFC and silicone-free Yes
Tripping characteristic B Tripping characteristic C
Rated residual current
Rated current
MW DT Order No. Priceper PU
PG DT Order No. Priceper PU
PG PU PS*/P. unit
Weightper P. unitapprox
I∆n In
mA A Unit(s) Unit(s) kg
RCBOs, type A Instantaneous
1P+N; 230 V AC; 50 ... 60 Hz
30 6 2 A 5SU1 356-6KK06 011 A 5SU1 356-7KK06 011 1 1 0.2608 -- B 5SU1 356-7KK08 011 1 1 0.260
10 A 5SU1 356-6KK10 011 5SU1 356-7KK10 011 1 1 0.26013 B 5SU1 356-6KK13 011 A 5SU1 356-7KK13 011 1 1 0.26016 5SU1 356-6KK16 011 5SU1 356-7KK16 011 1 1 0.260
20 B 5SU1 356-6KK20 011 B 5SU1 356-7KK20 011 1 1 0.26025 B 5SU1 356-6KK25 011 A 5SU1 356-7KK25 011 1 1 0.26032 B 5SU1 356-6KK32 011 B 5SU1 356-7KK32 011 1 1 0.26040 B 5SU1 356-6KK40 011 B 5SU1 356-7KK40 011 1 1 0.260
300 6 2 B 5SU1 656-6KK06 011 B 5SU1 656-7KK06 011 1 1 0.26010 B 5SU1 656-6KK10 011 A 5SU1 656-7KK10 011 1 1 0.26013 B 5SU1 656-6KK13 011 B 5SU1 656-7KK13 011 1 1 0.26016 B 5SU1 656-6KK16 011 A 5SU1 656-7KK16 011 1 1 0.260
20 B 5SU1 656-6KK20 011 B 5SU1 656-7KK20 011 1 1 0.26025 B 5SU1 656-6KK25 011 B 5SU1 656-7KK25 011 1 1 0.26032 B 5SU1 656-6KK32 011 B 5SU1 656-7KK32 011 1 1 0.26040 B 5SU1 656-6KK40 011 B 5SU1 656-7KK40 011 1 1 0.260
-25
6 0003
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RCBOs, type A
2/24 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
RCBOs, type A Instantaneous
1P+N; 230 V AC; 50 ... 60 Hz
10 6 2 B 5SU1 154-6KK06 011 B 5SU1 154-7KK06 011 1 1 0.26010 B 5SU1 154-6KK10 011 B 5SU1 154-7KK10 011 1 1 0.26013 B 5SU1 154-6KK13 011 B 5SU1 154-7KK13 011 1 1 0.26016 B 5SU1 154-6KK16 011 5SU1 154-7KK16 011 1 1 0.260
30 6 2 B 5SU1 354-6KK06 011 5SU1 354-7KK06 011 1 1 0.2608 -- B 5SU1 354-7KK08 011 1 1 0.260
10 B 5SU1 354-6KK10 011 5SU1 354-7KK10 011 1 1 0.26013 B 5SU1 354-6KK13 011 B 5SU1 354-7KK13 011 1 1 0.26016 5SU1 354-6KK16 011 5SU1 354-7KK16 011 1 1 0.260
20 B 5SU1 354-6KK20 011 B 5SU1 354-7KK20 011 1 1 0.26025 B 5SU1 354-6KK25 011 B 5SU1 354-7KK25 011 1 1 0.26032 B 5SU1 354-6KK32 011 B 5SU1 354-7KK32 011 1 1 0.26040 B 5SU1 354-6KK40 011 B 5SU1 354-7KK40 011 1 1 0.260
300 6 2 B 5SU1 654-6KK06 011 B 5SU1 654-7KK06 011 1 1 0.26010 B 5SU1 654-6KK10 011 B 5SU1 654-7KK10 011 1 1 0.26013 B 5SU1 654-6KK13 011 B 5SU1 654-7KK13 011 1 1 0.26016 B 5SU1 654-6KK16 011 B 5SU1 654-7KK16 011 1 1 0.260
20 B 5SU1 654-6KK20 011 B 5SU1 654-7KK20 011 1 1 0.26025 B 5SU1 654-6KK25 011 B 5SU1 654-7KK25 011 1 1 0.26032 B 5SU1 654-6KK32 011 B 5SU1 654-7KK32 011 1 1 0.26040 B 5SU1 654-6KK40 011 B 5SU1 654-7KK40 011 1 1 0.260
2P; 230 V AC; 50 ... 60 Hz
30 6 3 B 5SU1 324-6FA06 011 B 5SU1 324-7FA06 011 1 1 0.40310 5SU1 324-6FA10 011 5SU1 324-7FA10 011 1 1 0.40313 B 5SU1 324-6FA13 011 B 5SU1 324-7FA13 011 1 1 0.40316 5SU1 324-6FA16 011 5SU1 324-7FA16 011 1 1 0.403
20 B 5SU1 324-6FA20 011 B 5SU1 324-7FA20 011 1 1 0.40325 B 5SU1 324-6FA25 011 B 5SU1 324-7FA25 011 1 1 0.40332 B 5SU1 324-6FA32 011 B 5SU1 324-7FA32 011 1 1 0.40340 B 5SU1 324-6FA40 011 B 5SU1 324-7FA40 011 1 1 0.403
2P; 400 V AC; 50...60 Hz
30 125N 6 B 5SU1 324-6KK82 011 B 5SU1 324-7KK82 011 1 1 0.930
300 125N B 5SU1 624-6KK82 011 B 5SU1 624-7KK82 011 1 1 0.930
4P; 400 V AC; 50...60 Hz
30 125N 11 B 5SU1 344-6KK82 011 B 5SU1 344-7KK82 011 1 1 1.900
300 125N B 5SU1 644-6KK82 011 B 5SU1 644-7KK82 011 1 1 1.900
Tripping characteristic B Tripping characteristic C
Rated residual current
Rated current
MW DT Order No. Priceper PU
PG DT Order No. Priceper PU
PG PU PS*/P. unit
Weightper P. unitapprox
I∆n In
mA A Unit(s) Unit(s) kg
10 0003
10 0003
10 000
10 000
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RCBOs, type A
2/25Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Note:The same additional components are used for RCBOs as for MCBs. See chapter "Miniature circuit breakers".
RCBOs, type A Super resistant æ
1P+N; 230 V AC; 50...60 Hz
30 10N 3 -- B 5SU1 354-7VK10 011 1 1 0.26016N -- B 5SU1 354-7VK16 011 1 1 0.26020N -- B 5SU1 354-7VK20 011 1 1 0.26025N -- B 5SU1 354-7VK25 011 1 1 0.260
RCBOs, type A Selective î
2P; 400 V AC; 50...60 Hz
300 125N 6 B 5SU1 624-6WK82 011 B 5SU1 624-7WK82 011 1 1 0.930
4P; 400 V AC; 50...60 Hz
300 125N 11 B 5SU1 644-6WK82 011 B 5SU1 644-7WK82 011 1 1 1.900
Version DT Order No. Priceper PU
PG PU PS*/P. unit
Weightper P. unitapprox
Unit(s) Unit(s) kg
Handle couplers for additional components
For mounting the additional components: auxiliary switches,fault signal contacts, shunt trips and undervoltage releases onto 5SU1 RCBOs, you require a handle coupler (1 set = 5 units).
5ST3 805-1 027 1 set 1 set 0.008
Tripping characteristic B Tripping characteristic C
Rated residual current
Rated current
MW DT Order No. Priceper PU
PG DT Order No. Priceper PU
PG PU PS*/P. unit
Weightper P. unitapprox
I∆n In
mA A Unit(s) Unit(s) kg
10 0003
10 000
10 000
or
or or or
or or or
5ST3
RCBO RC
AS FC ASFC
ASFC
ASFC
FCAS
AS FC ASFC
ASFC
ASFC
FCAS
AS FC ASFC
ASFC
ASFC
FCAS
ST
UR
or or
5SU1
I2_1
3658
b
RCBO: Residual current operated circuit breakers with integral overcurrent protectionRC: Remote controlled mechanismUR: Undervoltage releaseST: Shunt tripAS: Auxiliary switchFC: Fault signal contact
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
RCBOs, type A
2/26 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
Dimensional drawings
Schematics
1P+N,up to 40 A
2P, up to 40 A
2P, 125 A
4P, 125 A
45
44707
90
5436
I2_1
3650
45 90m
ax 6
7
I2_1
3649
7198 4470
117
Handle coupler
1P+N,up to 40 A
2P, up to 40 A
2P, 125 A
4P, 125 A
I2_1
3645
2 N
1 N
I2_1
3646
2 4
1 3
I2_13647 2 4
1 3Y2Y1
I2_13648 2/1 4/3 6/5 8/7(N)
1 5 7(N)3Y1 Y2
-25
(Type A)
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
Busbars
2/27Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Overview
4-pole 5SM3 RCCBs are bus-mounted either together or in combination with miniature circuit breakers. RCCBs with an N wire connection on the left-hand side facilitate installation because normal busbars are used, as for miniature circuit breakers.
Busbars in 10 mm2 and 16 mm2 versions are available.
The extremely flexible 5ST3 6 busbar system with fixed lengths enables installation in any length as the busbars can be overlapped.
No further need for time-consuming tasks, such as cutting, cutting to length, deburring, cleaning of cut surfaces and mounting of end caps.
Any free pins on the busbars can be made safe by covering with touch protection.
If several RCBOs are bus-mounted together, this is implemented with 2-phase busbars, which are used as 1+N busbars.
Benefits• Connection of miniature circuit breakers to 4-pole RCCBs with
N connection right and 3-phase busbar, using busbar specially designed for this application. No cutting or end caps required.
• Connection of miniature circuit breakers to 4-pole RCCBs with N connection left, with 3-phase busbar that can be cut. No additional items to be stored and busbars that are always available.
• Connection of 1P+N RCBOs with 2-phase busbar. No cutting or end caps required.
• Bus-mounting of RCCBs on busbar (3-phase +N) that can be cut. A proven and frequently used application.
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
Busbars
2/28 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
Technical specifications
5ST3, 5ST2
Standards EN 60439-1 (VDE 0660-500)
Busbar material SF-Cu F 24
Partition material Plastic, Cycoloy 3600 Heat-resistant more than 90 °CFlame-retardant and self-extinguishing, dioxin and halogen-free
Rated operational voltage Ue V AC 400
Rated current In
• Cross-section 10 mm2 A 63
• Cross-section 16 mm2 A 80
Rated impulse withstand voltage Uimp kV 4
Test pulse voltage (1.2/50) kV 6.2
Rated conditional short-circuit current Icc kA 25
Resistance to climate
• Constant atmosphere acc. to DIN 50015 23/83; 40/92; 55/20
• Humid heat acc. to IEC 68-2-30 28 cycles
Insulation coordination acc. to IEC 664 (VDE 0110-1)
• Overvoltage category III
• Degree of pollution 2
Maximum busbar current per phase
• Cross-section 10 mm2 A 63
• Cross-section 16 mm2 A 80
Maximum branch-circuit current per phase
• Cross-section 10 mm2 A 100
• Cross-section 16 mm2 A 130
Infeed at the busbar end Infeed near the busbar end or at the busbar center
The sum of the output current per branch must not be greater than the busbar current IS1.2 / phase.
S
I2_13755
S1 S2
3 2 1 1 2 3
I2_13754
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
Busbars
2/29Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Selection and ordering data
Dimensional drawings
Note:Pin spacing in MWDimensions of side views in mm (approx.)
Version Pin spacing
Length DT Order No. Priceper PU
PG PU PS*/P. unit
Weightper P. unitapprox
MW mm Unit(s) Unit(s) kg
5ST3 6 busbar systems, fixed lengths, cannot be cut, fully insulated
For 1 RCCB 4P+N right and 8 MCB 1P
• 3-phase 10 mm2 1 210 A 5ST3 624 027 1 10 0.075
• 3-phase 16 mm2 1 210 A 5ST3 654 027 1 10 0.114
For 6 RCBOs 1P+N together
• 2-phase 10 mm2 210 A 5ST3 608 027 1 10 0.048
• 2-phase 16 mm2 210 A 5ST3 638 027 1 10 0.076
5ST3 7 busbar systems, 12 MW, can be cut, with end caps
For 6 RCBOs 1P+N
• 2-phase 10 mm2 1 214 A 5ST3 704 027 1 1/25 0.060
• 2-phase 16 mm2 1 214 A 5ST3 734 027 1 1/25 0.060
End caps for 5ST3 7, can be cut
For 2-phase busbars 5ST3 750 027 1 10 0.001
Touch protection
For free connections, yellow (RAL 1004) A 5ST3 655 027 1 10 0.003
Busbars, 56 MW, with fork-type connections, can be cut, without end caps
For bus-mounting RCCBs together
• 3-phase + N, 16 mm2 1 1016 A 5ST2 145 027 1 1/10 0.315
End caps for 5ST3 7, can be cut
For 3-phase busbars A 5ST2 156 027 1 10 0.017
Terminals up to 35 mm2 (stranded),for direct infeed of 5ST2 145 busbar
Side-by-side mounting possible A 5ST2 157 027 1 5 0.030
5ST3 624 5ST3 608 5ST3 638
5ST3 654 5ST2 145
15,2
9,2
I2_1
3672
L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2
111111211 1
L1 L2
15,2
6,6
I2_1
3666
1
19
7,3
L1 L2
1
I2_1
3665
I2_1
3673
L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2
111111211 1
19
10,3
I2_1
3768
1
14
24,5
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
Accessories
2/30 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
Accessories
Version DT Order No. Priceper PU
PG PU PS*/P. unit
Weightper P. unitapprox
Unit(s) Unit(s) kg
Terminal covers, gray
For surface mounting, degree of protection IP40, sealable, with 35 mm standard mounting rail
• Up to 2.5 MW B 5SW3 004 008 1 1/10 0.084
• Up to 4.5 MW B 5SW3 005 008 1 1 0.114
Wall enclosures, gray
For flush mounting, degree of protection IP40 with 35 mm standard mounting rail
• Up to 2.5 MW B 5SW3 006 008 1 1/4 0.126
• Up to 4.5 MW B 5SW3 007 008 1 1/5 0.147
Molded-plastic enclosures, gray
For surface mounting, degree of protection IP54, sealable, with 35 mm standard mounting rail, with transparent hinged lidfor 4.5 MW
A 5SW1 200 008 1 1 0.450
Covers
Can be assembled as mini distribution board, suitable for all devices, cover parts prepared for rail mounting of conventional label caps, comprising:
• End plates (for snapping onto standard mounting rail) A 5ST2 134 027 1 10 0.022
• Angled profile (approx. 1 m long) A 5ST2 135 027 1 5 0.330
• Flat profile (as a cover between the rows of devices length ap-prox. 1 m)
B 5ST2 136 027 1 5 0.260
Fixing parts
Plastic 4 MW
B 5ST2 201 027 1 1/20 0.012
Inscription labels (white)
15 mm × 9 mm, 3 frames with 44 labels each any attachment and inscription, self-adhesive
B 5ST2 173 027 1 set 1 set 0.038
Labeling systems
To download the labeling program free of charge, please visit our Web site at:http://www.siemens.com/beta
Recommended labels ELAT-3-747can be ordered at: Brady GmbH
Otto-Hahn-Str. 5-7 D-63222 Langen Tel: +49 (0)6103/598-660
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
Residual-current operated circuit breakers
2/31Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Overview
Protection against dangerous leakage currents according to DIN VDE 0100-410
Application• Protection against indirect contact (indirect personnel protection) –
as leakage protection through tripping in the event of higher touch voltages due to short-circuits to frame on equipment
• Using residual current protective devices with I∆n ≤ 30 mA also largely protects against direct contact (direct personnel protection) - as additional protection through tripping as soon as live parts are touched
Protective actionWhile devices for rated residual current I∆n > 30 mA provide protection against indirect contact, using devices with I∆n ≤ 30 mA also offers the best possible additional protection against accidental direct contact with live parts.The diagram above shows a summary of the physiological reactions of the human body to power flows in the effective current ranges. The dangerous values are the current/time values in range 4 as they can trigger ventricular fibrillations, which can cause death.It also shows the tripping range of the residual current protective device with rated residual current 10 mA and 30 mA. The instanta-neous tripping time lies in the middle between 10 ms and 30 ms.
The permissible tripping time of max. 0.3 s (300 ms) according to EN 61008 or IEC 61008 is not reached.Residual current protective devices with rated residual current 10 or 30 mA also offer reliable protection when a current flows through a person after accidental direct contact with live parts. This protective action is not matched by any other comparable protective measure in the event of indirect contact.
However, when using residual current protective devices, a suitably grounded PE conductor must also be fitted to the system components and equipment to be protected. This means that it is only possible for a person to be subjected to a flow of current if two faults occur or in the event of accidental contact with live parts.
If live parts are directly touched, two resistors determine the level of the current - the internal resistance of the person RM and the contact resistance of the location RSt. For a proper assessment of the accident risk, the worst case scenario must be assumed, which is that the contact resistance of the location is virtually zero.
I2_0
6158
f
t
MM
t
10000
2000
1000
500
200
100
50
20
ms
0,1 0,2 0,5 1 2 5 10 20 50 100 200 500 1000 mA 10000
1
30 mA
2 3 4
10 mA
A
1
2
3
4
RangeUsually, the effectis not perceived.
RangeUsually, there areno noxious effects.
RangeUsually, no dangerof heart fibrillation.
RangeHeart fibrillationdanger.
Shock current:
Duration:Effective current ranges according to IEC 60479
! "
#
$
! # % !
& ! % # #
' $ (
) ! ( ! "
% !
*
*
*
Examples of accidental direct contact
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
Residual-current operated circuit breakers
2/32 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
The resistance of the human body depends on the current path. Measurements have shown, for example, that a current path of hand/hand or hand/foot has a resistance of approx. 1 000 Ω. Taking into account a fault voltage of 230 V AC, this produces a current of 230 mA for the current path hand/hand.
ApplicationResidual current protective devices can be used in all three system types (DIN VDE 0100-410). In the IT system, tripping is not required for the first fault as this situation cannot produce any dangerous touch voltages. It is essential that an insulation monitoring device is fitted so that the first fault is indicated by an acoustic or visual signal and the fault can be eliminated as quickly as possible. Tripping is not requested until the 2nd fault. Depending on the grounding situation, the tripping conditions of the TN or TT system must be complied with. A residual current protective device is also a suitable circuit-protection device, whereby a separate residual current protective device is required for each piece of current-using equipment.
Grounding resistancesWhen using residual current protective devices in a TT system, the maximum grounding resistances (as shown in the following table) must be complied with, depending on the rated residual current and the max. permissible touch voltage.
Fire protection according to DIN VDE 0100-482
Application• When using residual current protective devices with I∆n ≤ 300 mA
protection against the occurrence of fires started electrically due to insulation faults.
Protective actionDIN VDE 0100-482 requires measures to be taken to prevent fires in "Locations exposed to fire hazards" that may result from insulation faults.Electrical equipment must be selected and set up taking external influences into account so that their temperature rise during normal operation, and the foreseeable temperature rise, cannot cause a fire in the event of a fault.This is achieved by ensuring the equipment is suitably designed or by implementing additional protective measures during installation.For this reason, additional residual current protective devices with a rated residual current of max. 300 mA is required for TN and TT systems used in "Locations exposed to fire hazards".Where resistance-related faults may cause a fire (e.g. when using ceiling heating with panel heating elements), the rated residual current must not exceed max. 30 mA.The additional protection against fires provided by separate residual current protective devices should not just be restricted to locations exposed to fire hazards, rather it should be universally implemented.
IM: Leakage current
RM: Internal resistance of human being
RSt: Contact resistance of location
RA: Grounding resistance of all bodies connected to a grounding electrode
Principle diagram: Additional protection against direct contact with live parts
I2_06153e
L1L2L3N
PEN
N PE
PE
TN-C TN-S
TN network
RC
CB
RC
CB
L2L3N
I2_06154e
L1
PEPE
L2L3N
L1
TT network
RCCB RCCB
Rated residual current
Max. permissible grounding resistance at a max. permissible touch voltage of
I∆n 50 V 25 V
10 mA 5000 Ω 2500 Ω30 mA 1660 Ω 830 Ω
100 mA 500 Ω 250 Ω300 mA 166 Ω 83 Ω500 mA 100 Ω 50 Ω
1 A 50 Ω 25 Ω
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
Residual-current operated circuit breakers
2/33Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Design and method of operation of residual current protective devicesThe design of residual current protective devices is largely determined by 3 function groups: 1) Summation current transformers for fault-current detection2) Releases to convert the electrical measured quantities into a
mechanical tripping operation3) Breaker mechanism with contactsThe summation current transformer covers all conductors required to conduct the current, i.e. also the neutral conductor where applicable.In a fault-free system, the magnetizing effects of the conductors through which current is flowing cancel each other out for the summation current transformer as, in accordance with Kirchhoff's current law, the sum of all currents is zero. There is no residual magnetic field left that could induce a voltage in the secondary winding.However, by contrast, if a residual current is flowing due to an insulation fault, this destroys the equilibrium and a residual magnetic field is left in the transformer core. This generates a voltage in the secondary winding, which then uses the release and the breaker mechanism to switch off the electrical circuit afflicted by the insulation fault.This tripping principle operates independently of the supply voltage or an auxiliary power supply. This is also a condition for the high protection level provided by residual current protective devicesaccording to IEC/EN 61008 (VDE 0664).Only this way can it be ensured that the full protective action of the residual current protective device is maintained even in the event of a system fault, e.g. failure of an outer conductor or an interruption in the neutral conductor.
Test buttonAll residual current protective devices are equipped with a test button. Simply press this button to test whether the residual current protective device is ready to run. Pressing the test button generates an artificial residual current – the residual current protective device must trip.We recommend testing the functionality when commissioning the system and then at regular intervals – approx. every six months.Furthermore, it is also essential to ensure compliance with the test intervals specified in the pertinent rules and regulations (e.g. accident prevention regulations).The minimum working voltage for operation of the test equipment normally is 100 V AC (series 5SM3)1).1) For detailed information, see Technical specifications
3-pole connection4-pole residual current protective devices can also be operated in 3-pole systems. In this case, connection must be at terminals 1, 3 and 5 and 2, 4 and 6.The function of the test equipment is only ensured if a jumper is fitted between terminals 3 and N.
SIGRES RCCBs for severe ambient conditions Our SIGRES RCCBs have been developed for use in environments with increased pollution gas loads, such as • Indoor swimming pools: chlorine gas atmosphere,• Agriculture: ammoniac, • Worksite distribution boards, chemical industry: nitrogen oxides
[NOx], sulfur dioxide [SO2], A significant increase in service life is achieved using our patented active condensation protection.
When using SIGRES RCCBs, the following points must be observed:• The infeed must always be from below, from terminals 2/N or 2/4/6/N.• Before carrying out insulation tests on installation systems with voltages
greater than 500 V, the SIGRES RCCB must be switched off or the cables on the input side (below) must be disconnected.
Short-time delayed tripping, super resistant æ
Electrical loads that temporarily produce high leakage currents when they are switched on (e.g. temporary residual currents flowing through interference-suppression capacitors between outer conductor and PE) may trip instantaneous residual current protective devices, if the leakage current exceeds the rated residual current I∆n of the residual current protective device.Short-time delayed, super resistant residual current protective devices can be installed for this type of application, where it is not possible, or only partially possible, to eliminate such interference sources. These devices have a minimum tripping delay of 10 ms, i.e., they should not trip for a residual current pulse of 10 ms. This complies with the maximum permissible break times according to IEC/EN 61008-1 (VDE 0664-10). The devices have a high surge current withstand capability of 3 kA.Short-time delayed, super resistant residual current protective devices has the identification code æ.
Selective tripping îResidual current protective devices normally have an instantaneous tripping operation. This means that a series connection of this type of residual current protective devices does not provide selective tripping in the event of a fault. In order to achieve selectivity for a series connection of residual current protective devices, both the tripping time and the rated residual current of series-connected devices must be time graded. Selective residual current protective devices has a tripping delay.Furthermore, selective residual current protective devices must have an increased surge current withstand capability of at least 3 kA according to IEC/EN 61008-1. Siemens devices have a surge current withstand capability of ≥ 5 kA.Selective residual current protective devices have the identification code î.
The table below shows the time grading options available for residual current protective devices for selective tripping in series connection with devices without time delay and super resistant devices with short-time delay æ.
!
"
"
"
# " $ % % % # & " $ % % % " $
$ ' $ ( $ ) * " +
, - $ "
. $ / '
/ 0 ' / * $ / ' /
$ 1
$ !
2 $ "
3 $ 1 $
$ ' $
$ !
$ ) * " +
$ !
" ( " "
" ( " "
" ( " ( " (
" "
2 $
"
2 $
"
2 $
"
1) For residual current circuit breakers of type AC: <40 ms.
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
Residual-current operated circuit breakers
2/34 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
Versions for 50 to 400 Hz Due to their principle of operation, the standard versions of residual current protective devices are designed for maximum efficiency in 50/60 Hz systems. Product standards and tripping conditions also refer to this frequency. The sensitivity decreases with increasing frequency. In order to implement an effective fault-current protection for applications in systems up to 400 Hz (e.g. industry), you need to use suitable devices. This type of residual current protective device fulfills the tripping conditions up to the specified frequency and provides the appropriate level of protection.
Residual current circuit breaker with left-side N-connectionThe fact that the RCCBs are usually located to the left of the miniature circuit breakers, but have their N wire connection on the right-hand side, interferes with the integrated busbar connection. For this reason, when used with miniature circuit breakers, RCCBs require a special busbar. In order to enable the use of standard busbars, 4-pole RCCBs are also provided with their N connection on the left-hand side. This means that RCCBs can continue to be installed to the left of miniature circuit breakers using standard busbar connections.
Surge current withstand capabilityDuring thunderstorms, atmospheric overvoltages in the form of traveling waves can penetrate the installations of a system over an overhead system and trip the residual current protective devices. To prevent such inadvertent tripping operations, residual current protective devices sensitive to power pulse currents must pass specific tests proving its surge current withstand capability. These tests are carried out using a surge current of the standardized surge current wave 8/20 µs.
Surge current wave 8/20 µs (front time 8 µs: Time to half-value 20 µs)
Siemens residual current protective devices of types A and B all have a high surge current withstand capability. The following table shows the surge current withstand capability of the various versions:
Switching capacity, short-circuit strengthIn accordance with the installation regulations DIN VDE 0100-410 (protection against electric shock) residual current protective devices can be installed in three system types (TN, TT and IT systems).However, if using the neutral conductor as a protection conductor in TN systems, a fault may cause residual currents similar to a short-circuit. For this reason, residual current protective devices must be installed together with a back-up fuse and have the appropriate short-circuit strength. Tests have been defined for this purpose.The short-circuit strength of the combination must be specified on the devices.Siemens residual current protective devices, together with a suitable back-up fuse, have a short-circuit strength of 10000 A. This is the highest possible level of short-circuit strength as specified in the VDE regulations.Data for the rated switching capacity according to IEC/EN 61008, i.e. the maximum permissible short-circuit back-up fuses for residual current protective devices are contained in the following table:
Example:
Short-circuit strength 10 kA with max. permissible short-circuit series fuse 100 A.
Version Surge current withstand capability
Instantaneous > 1 kA
Short-time delayed, Super resistant æ
> 3 kA
Selective î > 5 kA
4
5
0
"
/
) $ $ 6 ' " -
2 7 8 2 &
01 ' " ) 6 * 1 ' 1 ' !
" - 1 '
6 " $
3
Rated current of the Rated short-circuit capacity Im according to IEC/EN 61008 for a grid distance of 35 mm
Maximum permissible short-circuit back-up fuse NH, DIAZED, NEOZEDoperational class gL/gG residual current protective device
residual current protective device
125 ... 400 V AC
500 V AC
A A A A
Type A
16 ... 40 2 MW 500 63 --
63 2.5 MW 800 100 --
80 2.5 MW 800 100 --
100 2 MW 1000 125 --
125 2 MW 1250 125 --
25 4 MW 800 100 63
40 4 MW 800 100 63
63 4 MW 800 100 63
80 4 MW 800 100 --
125 4 MW 1250 125 --
Type B
25 ... 80 4 MW 800 100 --
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
Residual-current operated circuit breakers
2/35Siemens ET B1 · 2008
12
34567891011121314151617* You can order this quantity or a multiple thereof.
Types of currentDue to the use of electronic components in household appliances and industrial plants, insulation faults can also cause residual currents that are not AC residual currents to flow through residual current protective devices, even in the case of devices with ground termi-nals (Safety class I).The regulations for residual current protective devices contain additional requirements and test regulations for residual currents whose power supply frequency is zero or virtually zero within a certain period.
Residual current protective devices that trip for both sinusoidal AC residual currents and pulsating DC residual currents (type A) are identified by the mark .Residual current protective devices that also trip for smooth DC residual currents (type B) are identified by the mark .
1) Tripping currents according to IEC/EN 61008-1 (VDE 0664, Part -10); for smooth DC residual currents defined to IEC 60755 UB1 INT.
Type of current Current waveform
Correct function of residual current protective devices of type
Tripping current1)
AC A B
AC residual current 0.5 ... 1.0 I∆n
Pulsating DC residual currents (pos. or neg. half-waves) -- 0.35 ... 1.4 I∆n
Started half-wave currents
Start angle 90° el Start angle 135° el
--
0.25 ... 1.4 I∆n0.11 ... 1.4 I∆n
Half-wave current during superimposition with smooth direct current of 6 mA
-- max. 1.4 I∆n+ 6 mA
Smooth direct current -- -- 0.5 ... 2.0 I∆n
© Siemens AG 2007
BETA ProtectingResidual Current Protective Devices
Residual-current operated circuit breakers
2/36 Siemens ET B1 · 2008
2
* You can order this quantity or a multiple thereof.
Application
Notes:
For reasons of basic fire protection, we recommend a maximum rated residual current of 300 mA for residual current protective devices.
The contents of DIN VDE 0100 is mostly identical with IEC 60364.
Standards Application Required I∆n Recommended residual current protective devices
[mA] 5SM. (Type A)
5SM. (Type B)
SIGRES
DIN VDE 0100-470 Socket outlets up to 20 A, outdoor plants ≤ 30 -- --
DIN VDE 0100-482 Fire protection for particular risks or safety hazard 30, 300 --
DIN VDE 0100-551 Low-voltage generating sets ≤ 30 -- --
DIN VDE 0100-559 Luminaires and lighting installations, display stands for lights ≤ 30 -- --
DIN VDE 0100-701 Rooms with baths or showers, socket outlets in zone 3 ≤ 30 -- --
DIN VDE 0100-702 Swimming pools, zone 1 and 2 ≤ 30 --
DIN VDE 0100-704 Construction and demolition site installations, socket outlet current circuits
(single-phase operation) up to 32 A and for hand-held equipment
≤ 30
--
DIN VDE 0100-705 Agricultural and general horticultural premises
Socket outlet current circuits
≤ 500
≤ 30
--
--
DIN VDE 0100-706 Conductive areas with limited freedom of movement ≤ 30 -- --
DIN VDE 0100-708 Feeding points for caravan parking spaces, camping sites ≤ 30 -- --
DIN VDE 0100-710 Medical premises, depending on application group 1 or 2 and equipment
≤ 30 or --
≤ 300 --
DIN VDE 0100-722 Portable buildings, vehicles, mobile homes for fairgrounds ≤ 500 --
DIN VDE 0100-723 Classrooms with experiment equipment ≤ 30 --
DIN VDE 0100-738 Fountains zone 2, general
Socket outlets in zone 2
Zones 0 and 1
≤ 500
≤ 30
≤ 30
--
--
--
DIN VDE 0100-739 Additional protection against direct contact in homes ≤ 30 -- --
DIN VDE 0118-100 Mining plants ≤ 500 --
EN 50178 Fitting of power installations with electronic equipment General requirements for correct selection when using res. current protection
--
DIN VDE 0832-100 Traffic signals• Class T1• Class U1
≤ 300≤ 30
----
BG FEBGI 608
Selection and operation of electrical equipment on worksitesGeneral:• Socket outlet circuits ≤ 32 A• Socket outlet circuits > 32 AFrequency-controlled equipment:• With plug-and-socket device ≤ 32 A• With plug-and-socket device > 32 A
≤ 30≤ 500
≤ 30≤ 500
----
----
Chemical industry and food processing industries 30 (recommended)