+ All Categories
Home > Documents > ETSU BUILDING 2 ETSU BUILDING 2 RENOVATION RENOVATION

ETSU BUILDING 2 ETSU BUILDING 2 RENOVATION RENOVATION

Date post: 24-Jan-2022
Category:
Upload: others
View: 11 times
Download: 0 times
Share this document with a friend
16
JOHNSON CITY, TN 37601 210 E. WATAUGA AVENUE 423.929.2191 1 2 3 4 5 6 A B C D E DESIGN: DRAWN: REVIEW: SHEET KEY PLAN SUBMITTAL PROFESSIONAL SEAL DESIGNER REVISIONS C:\Revit Projects\9195_ETSU Building 2 Renovation_A21_tmclauchlan.rvt 1/7/2021 5:00:47 PM G-001 COVER SHEET SCHEMATIC DESIGN Designer Author Checker ETSU BUILDING 2 RENOVATION EAST TENNESSEE STATE UNIVERSITY BUILDING #2 DOGWOOD AVE VA MEDICAL CENTER CAMPUS MOUNTAIN HOME, TN 37684 01.07.2021 CN 9195 100 N ETSU BUILDING 2 RENOVATION EAST TENNESSEE STATE UNIVERSITY SCHEMATIC DESIGN 01.07.2021 BUILDING #2 DOGWOOD AVE VA MEDICAL CENTER CAMPUS MOUNTAIN HOME, TN 37684 SITE MAP PROJECT SITE OWNER EAST TENNESSEE STATE UNIVERSITY PROJECT TEAM MECHANICAL, PLUMBING, ELECTRICAL AND FIRE PROTECTION ENGINEER ARCHITECT CLARK NEXSEN 210 EAST WATAUGA AVENUE, JOHNSON CITY , TN 37601 T: 423.929.2191 F: 757.455.5638 STRUCTURAL ENGINEER LYNCH MYKINS 301 N WEST STREET, SUITE 105 RALEIGH, NC 27603 T: 919.782.1833 SHEET NUMBER SHEET NAME GENERAL G-001 COVER SHEET GI101 FIRST FLOOR LIFE SAFETY PLAN ARCHITECTURAL A-001 ARCHITECTURAL LEGENDS AND NOTES AD101 DEMOLITION PLANS AE100 BASEMENT FLOOR PLAN AE101 FIRST FLOOR PLAN AE111 FIRST FLOOR REFLECTED CEILING PLAN AE410 INTERIOR ELEVATIONS AE411 INTERIOR ELEVATIONS Mechanical M-001 MECHANICAL LEGEND M-601 SCHEDULES MD101 FIRST FLOOR DEMOLITION PLAN - HVAC MD102 FIRST FLOOR DEMOLITION PLAN - PIPING MH100 BASEMENT FLOOR NEW WORK PLAN - HVAC MH101 FIRST FLOOR NEW WORK PLAN - HVAC MP101 FIRST FLOOR NEW WORK PLAN - PIPING CLARK NEXSEN 210 EAST WATAUGA AVENUE, JOHNSON CITY , TN 37601 T: 423.929.2191 F: 757.455.5638 PROJECT SCOPE RENOVATION OF LEVEL 1 OF BUILDING NO.2 OF THE JAMES H. QUILLEN C OLLEGE OF MEDICINE AT EAST TENNESSEE STATE UNIVERSITY. SPACES INCLUDE CLASSROOMS, FACULTY OFFICES, LA BORATORY SPACE, AND STUDY/MEETING ROOMS. THIS BUILIDNG IS LOCATED ON THE CAMPUS OF THE "MOUNTAIN B RANCH HOME FOR DISABLED VOLUNTEER SOLDIERS", A U.S. NATIONAL HISTORIC LANDMARK APPLICABLE CODES -- TENNESSEE STATE FIRE MARSHAL'S OFFICE. INTERNATIONAL BUILDING CODE 2012 INTERNATIONAL ENERGY CONSERVATION CODE 2012 INTERNATIONAL GAS CODE 2012 INTERNATIONAL MECHANICAL CODE 2012 INTERNATIONAL PLUMBING CODE 2012 INTERNATIONAL FIRE CODE 2012 INTERNATIONAL EXISTING BUILDING CODE 2012 LIFE SAFETY CODE (NFPA 101) 2012 BUILDING CLASSIFICATIONS IBC OCCUPANCY: BUSINESS IBC CONSTRUCTION TYPE: TYPE IIIB, SPRINKLERED NFPA OCCUPANCY: EXISTING BUSINESS (LSC CHAPTER 39) NFPA CONSTRUCTION TYPE: TYPE III (2 - 1 - 1) FIRE PROTECTION INTERIOR BEARING WALLS: NO RATING COLUMNS: NO RATING BEAMS: NO RATING FLOOR - CEILING ASSEMBLY: NO RATING EXTERIOR BEARING WALL: 2 HR RATED SHAFT ENCLOSURERS: 2 HR RATED OCCUPANCY SEPARATIONS: (NOT APPLICABLE) SMOKE PARTITIONS: NO RATING, SMOKE TIGHT "HAZARDOUS" SPACE PROTECTION: SMOKE TIGHT (>50SF) OR 1HR (>10 0 SF) SMOKE BARRIERS: (NOT APPLICABLE) HORIZONTAL EXITS: (NOT APPLICABLE) RATED ASSEMBLIES FLOOR - CEILING (N/A): NO RATING ROOF - CEILING (N/A): NO RATING COLUMNS (N/A): NO RATING EXTERIOR BEARING WALLS (EXISTING SOLID BRICK: 2 HOUR SEE IBC TABLE 721.1(2), ITEM 1 - 1.2: ZONING ZONING JURISDICTION: JOHNSON CITY, TENNESSEE EXISTING BUILDING ZONING: R - 4 , MEDIUM - DENSITY RESIDENTIAL DISTRICT BUILDING DATA ALLOWABLE HEIGHTS AND AREAS BUILDING HEIGHT (STORIES) 4 BUILDING HEIGHT (FEET) 75 FEET AREA PER STORY 57,000 SF TOTAL BUILDING AREA (3 STORIES PLUS BASEMENT) 228,000 SF NOTE: SEE IBC TABLE 503; SECTION S504.2; AND SECTION 506.3 ACTUAL HIEIGHTS BUILDING HEIGHT (STORIES) 3 PLUS BASEMENT BUILDING HEIGHT (FEET) 748 FEET LEVEL 1 - RENOVATED AREA 13,400 SF TOTAL BUILDING AREA (3 STORIES PLUS BASEMENT) APPROX 55,000 SF
Transcript

JOHNSON CITY, TN 37601

210 E. W ATAUGA AVENUE

423.929.2191

1 2 3 4 5 6

A

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

SHEET

KEY PLAN

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\91

95

_E

TS

U B

uild

ing 2

Ren

ova

tio

n_

A21

_tm

cla

uchla

n.r

vt

1/7

/20

21 5

:00

:47

PM

G-001

COVER SHEET

SCHEMATIC DESIGN

Designer

Author

Checker

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

BUILDING #2 DOGW OOD AVEVA MEDICAL CENTER CAMPUSMOUNTAIN HOME, TN 37684

01.07.2021

CN 9195

10

0

N

ETSU BUILDING 2 RENOVATIONEAST TENNESSEE STATE UNIVERSITY

SCHEMATIC DESIGN

01.07.2021

BUILDING #2 DOGWOOD AVE

VA MEDICAL CENTER CAMPUS

MOUNTAIN HOME, TN 37684

SITE MAP

PROJECT SITE

OWNER

EAST TENNESSEE STATE UNIVERSITY

PROJECT TEAM

MECHANICAL, PLUMBING, ELECTRICAL AND FIRE PROTECTION ENGINEER

ARCHITECT

CLARK NEXSEN210 EAST W ATAUGA AVENUE,JOHNSON CITY , TN 37601T: 423.929.2191F: 757.455.5638

STRUCTURAL ENGINEER

LYNCH MYKINS301 N W EST STREET, SUITE 105RALEIGH, NC 27603T: 919.782.1833

SHEETNUMBER SHEET NAME

GENERAL

G-001 COVER SHEET

GI101 FIRST FLOOR LIFE SAFETY PLAN

ARCHITECTURAL

A-001 ARCHITECTURAL LEGENDS AND NOTES

AD101 DEMOLITION PLANS

AE100 BASEMENT FLOOR PLAN

AE101 FIRST FLOOR PLAN

AE111 FIRST FLOOR REFLECTED CEILING PLAN

AE410 INTERIOR ELEVATIONS

AE411 INTERIOR ELEVATIONS

Mechanical

M-001 MECHANICAL LEGEND

M-601 SCHEDULES

MD101 FIRST FLOOR DEMOLITION PLAN - HVAC

MD102 FIRST FLOOR DEMOLITION PLAN - PIPING

MH100 BASEMENT FLOOR NEW WORK PLAN - HVAC

MH101 FIRST FLOOR NEW WORK PLAN - HVAC

MP101 FIRST FLOOR NEW WORK PLAN - PIPING

CLARK NEXSEN210 EAST W ATAUGA AVENUE,JOHNSON CITY , TN 37601T: 423.929.2191F: 757.455.5638

PROJECT SCOPE

RENOVATION OF LEVEL 1 OF BUILDING NO.2 OF THE JAMES H. QUILLEN COLLEGE OF MEDICINE AT EAST TENNESSEE

STATE UNIVERSITY. SPACES INCLUDE CLASSROOMS, FACULTY OFFICES, LABORATORY SPACE, AND STUDY/MEETING

ROOMS. THIS BUILIDNG IS LOCATED ON THE CAMPUS OF THE "MOUNTAIN BRANCH HOME FOR DISABLED VOLUNTEER

SOLDIERS", A U.S. NATIONAL HISTORIC LANDMARK

APPLICABLE CODES -- TENNESSEE STATE FIRE MARSHAL'S OFFICE.

INTERNATIONAL BUILDING CODE 2012

INTERNATIONAL ENERGY CONSERVATION CODE 2012

INTERNATIONAL GAS CODE 2012

INTERNATIONAL MECHANICAL CODE 2012

INTERNATIONAL PLUMBING CODE 2012

INTERNATIONAL FIRE CODE 2012

INTERNATIONAL EXISTING BUILDING CODE 2012

LIFE SAFETY CODE (NFPA 101) 2012

BUILDING CLASSIFICATIONS

IBC OCCUPANCY: BUSINESS

IBC CONSTRUCTION TYPE: TYPE IIIB, SPRINKLERED

NFPA OCCUPANCY: EXISTING BUSINESS (LSC CHAPTER 39)

NFPA CONSTRUCTION TYPE: TYPE III (2-1-1)

FIRE PROTECTION

INTERIOR BEARING W ALLS: NO RATING

COLUMNS: NO RATING

BEAMS: NO RATING

FLOOR-CEILING ASSEMBLY: NO RATING

EXTERIOR BEARING W ALL: 2 HR RATED

SHAFT ENCLOSURERS: 2 HR RATED

OCCUPANCY SEPARATIONS: (NOT APPLICABLE)

SMOKE PARTITIONS: NO RATING, SMOKE TIGHT

"HAZARDOUS" SPACE PROTECTION: SMOKE TIGHT (>50SF) OR 1HR (>100 SF)

SMOKE BARRIERS: (NOT APPLICABLE)

HORIZONTAL EXITS: (NOT APPLICABLE)

RATED ASSEMBLIES

FLOOR-CEILING (N/A): NO RATING

ROOF-CEILING (N/A): NO RATING

COLUMNS (N/A): NO RATING

EXTERIOR BEARING W ALLS (EXISTING SOLID BRICK: 2 HOUR

SEE IBC TABLE 721.1(2), ITEM 1-1.2:

ZONING

ZONING JURISDICTION: JOHNSON CITY, TENNESSEE

EXISTING BUILDING ZONING: R-4 , MEDIUM-DENSITY RESIDENTIAL DISTRICT

BUILDING DATAALLOWABLE HEIGHTS AND AREAS

BUILDING HEIGHT (STORIES) 4

BUILDING HEIGHT (FEET) 75 FEET

AREA PER STORY 57,000 SF

TOTAL BUILDING AREA (3 STORIES PLUS BASEMENT) 228,000 SF

NOTE: SEE IBC TABLE 503; SECTION S504.2; AND SECTION 506.3

ACTUAL HIEIGHTS

BUILDING HEIGHT (STORIES) 3 PLUS BASEMENT

BUILDING HEIGHT (FEET) 748 FEET

LEVEL 1 - RENOVATED AREA 13,400 SF

TOTAL BUILDING AREA (3 STORIES PLUS BASEMENT) APPROX 55,000 SF

UP

DN UP

REF

UP

DW

EGRESS TRAVEL PATH

DOOR TAG. REFER TO LIFE SAFETY EGRESS DOOR SCHEDULE.

STAIR TAG. REFER TO LIFE SAFETY EGRESS STAIR SCHEDULE

FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER BRACKET

FEC

SPACE AREA

SPACE NAME

OCCUPANCY LOAD (PEOPLE)

PATH ID

FEB

SPACE NAME

9,876 SF 385 OCC

101A

A1

A CCES SORYS TORAGEA REAS,MECHA NICALE QUIP ME NTROOM

A SSE MBLYUNCONCENTRATEDTAB LESANDCHA IRS

B USINESSA REAS

E DUCA TIONALCLA SSROOMAREA

E DUCA TIONALS HOPS&OTHERV OCATIONAL

100' - 11"

PATH A

126' - 6"

PATH B

122' - 4"

PATH C

1,318 SF

Area

26 OCC

958 SF

Area

48 OCC

656 SF

Area

13 OCC

314 SF

Area

2 OCC468 SF

Area

5 OCC

600 SF

Area

3 OCC162 SF

assembly

11 OCC

331 SF

BUSINESS

4 OCC

167 SF

STORAGE

1 OCC

1,076 SF

Area

52 OCC

137 SF

STORAGE

1 OCC639 SF

Area

7 OCC

1,093 SF

Area

52 OCC201 SF

STORAGE

1 OCC

110 SF

Area

8 OCC

46 SF

Area

3 OCC

155 SF

Area

11 OCC

DOORS:TOTAL OCCUPANTS THIS DOOR 34.34 (.15") = 5.1" REQUIRED36" PROVIDED

DOORS:TOTAL OCCUPANTS THIS DOOR 13.13 (.15") = 1.95" REQUIRED36" PROVIDED

EXIT

EXIT

EXIT

DOORS:TOTAL OCCUPANTS THIS DOOR 5757 (.15") = 8.55" REQUIRED36" PROVIDED

DOORS:TOTAL OCCUPANTS THIS DOOR 7878 (.15") = 11.7 " REQUIRED36" PROVIDED

DOORS:TOTAL OCCUPANTS THIS DOOR 6868 (.15") = 10.2 " REQUIRED36" PROVIDED

1. COORDINATE ALL FIRE EXTINGUISHERS LOCATIONS SHOWN ON PLANS W/ LOCAL FIRE OFFICIAL'S REQUIREMENTS.

2. GC TO PROVIDE & INSTALL ALL BLOCKING IN W ALLS AS REQUIRED FOR MOUNTING FIRE EXTINGUISHERS.

3. GC TO COORDINATE INSTALLATION REQUIREMENTS OF EXIT SIGNS, ALL ASSOCIATED HARDW ARE, JUNCTION BOXES, W IRING & REQUIRED EXIT DEVICES W/ ELECTRICAL DRAWINGS & LOCAL INSPECTOR.

4. RATED WALLS AND PARTITIONS REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE PERMANENTLY STENCILED EVERY 10'-0" ABOVE THE CEILING OR CONCEALED SPACE.

EXAMPLE:• 1-HOUR RATED BARRIER - PROTECT ALL OPENINGS

1/8" = 1'-0"A1FIRST FLOOR LIFE SAFETY PLAN

LIFE SAFETY - OCCUPANT CALCULATION - FIRST FLOOR

LEVEL PATTERN OCCUPANCYSF PER

PERSON OCCUPANCY SF TYPE AREA PEOPLE*NUMBER OFOCCUPANTS

FIRST FLOOR ACCESSORY STORAGE AREAS, MECHANICAL EQUIPMENT ROOM 300 GROSS 1,419 SF 7 8

FIRST FLOOR ASSEMBLY UNCONCENTRATED TABLES AND CHAIRS 15 NET 473 SF 34 33

FIRST FLOOR BUSINESS AREAS 100 GROSS 1,439 SF 16 16

FIRST FLOOR EDUCATIONAL CLASSROOM AREA 20 NET 3,126 SF 157 152

FIRST FLOOR EDUCATIONAL SHOPS & OTHER VOCATIONAL 50 NET 1,974 SF 41 39

FIRST FLOOR TOTALS: 8,430 SF 255 248

LIFE SAFETY - EGRESS DOOR SCHEDULE - FIRST FLOOR

DOOR NO. CLEAR EGRESSWIDTH PROVIDED

EGRESS WIDTHFACTOR

OCCUPANT LOAD DELAYED EGRESS(SECONDS)

ELECTROMAGNETICLOCK

HOLD OPENDEVICE

PANICHARDWAREMAX PROVIDED REQUIRED

LIFE SAFETY - STAIR SCHEDULE

TOP LEVEL STAIR MARK

CLEAR STAIRWIDTH

PROVIDED

EGRESSWIDTH

FACTOR

OCCUPANT LOAD

MAXPROVIDED REQUIRED

ONE HALF HOUR FIRE RATING

ONE HOUR FIRE RATING

TW O HOUR FIRE RATING

THREE HOUR FIRE RATING

FOUR HOUR FIRE RATING

(SB) SMOKE BARRIER (SB), SMOKE PARTITION (SP), OR PARTITION CAPABLE OF RESISTING THE PASSAGE OF SMOKE (S)

* NUMBER OF OCCUPANTS IS AN AGGREGATE AND IS A RESULT OF ROUNDING UP INDIVIDUAL AREAS

PATH OF TRAVEL SCHEDULE

MARK LENGTH

PATH A 100'-11"

PATH B 126'-6"

PATH C 122'-4"

JOHNSON CITY, TN 37601

210 E. W ATAUGA AVENUE

423.929.2191

1 2 3 4 5 6

A

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

SHEET

KEY PLAN

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\91

95

_E

TS

U B

uild

ing 2

Ren

ova

tio

n_

A21

_a

bru

mo

.rvt

1/7

/20

21 5

:16

:47

PM

GI101

FIRST FLOOR LIFE SAFETY

PLAN

SCHEMATIC DESIGN

Designer

Author

Checker

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

BUILDING #2 DOGWOOD AVEVA MEDICAL CENTER CAMPUSMOUNTAIN HOME, TN 37684

01.07.2021

CN 9195

10

0

AND&

EXIST EXISTING

VINYL COMPOSITION TILEVCT

AFS

ADJ

AT

APPROX

AFF

BD

@

ALUM

APPROXIMATE

BOARD

ABOVE FINISH FLOOR

ABOVE FINISH SLAB

ALUMINUM

ADJUSTABLE, ADJUST

CEILING

COL

CLG

DIA

CMU

CONC

DOW NDN

EQUIP

ELEC

ELEV

EQUIPMENT

ELECTRICAL

ELEVATION

CONCRETE MASONRY UNIT

CONCRETE

DIAMETER

COLUMN

FLOOR

FO

FLR

GWB GYPSUM WALLBOARD

FACE OF

EQ EQUAL

CENTER LINE

HORIZ HORIZONTAL

TYPICALTYP

TOC TOP OF CONCRETE

W IDTH / WASHER

VERT

W

VERTICAL

UNLESS OTHERWISE NOTEDUON

HOLLOW METALHM

VIF VERIFY IN FIELD

CL

ALT ALTERNATE

APC ARCHITECTURAL PRECAST CONCRETE

ACT ACOUSTICAL CEILING TILE

BLDG BUILDING

BLKG BLOCKING

BRG BEARING

BUR BUILT-UP ROOFING

CORNER GUARDCG

CONTROL JOINTCJ

CLEARCLR

CONST CONSTRUCTION

CONT CONTINUOUS

CPT CARPET

CT CERAMIC TILE

D DEPTH / DRYER

DBL DOUBLE

DIAG DIAGONAL

DIM DIMENSION

DISP DISPENSER

DOW NSPOUTDS

DRAW INGDWG

EACHEA

EXPANSION JOINTEJ

EDGE OF SLABEOS

EPS EXPANDED POLYSTYRENE

EXP EXPANSION / EXPOSED

EXT EXTERIOR

FD FLOOR DRAIN

FEB FIRE EXTINGUISHER BRACKET

FEC FIRE EXTINGUISHER CABINET

FGL FIBERGLASS

FF FINISH FLOOR

FIN FINISH

FRT FIRE RETARDANT TREATED

GA GAUGE

GALV GALVANIZED

GFRG GLASS FIBER REINFORCED GYPSUM

GL GLASS

GYP GYPSUM

HDW HARDWARE

HDWD HARDWOOD

HT HEIGHT

HVAC HEATING, VENTILATION, & AIR CONDITIONING

ID INSIDE DIAMETER

INSUL INSULATION

INT INTERIOR

JT JOINT

L LENGTH / LONG

MATL MATERIAL

SUSPENDEDSUSP

THR THRESHOLD

TOW TOP OF W ALL

TP TOILET PARTITION

TOP & BOTTOMT & B

VINYL BASEVB

VTR VENT THRU ROOF

WITHW/

WITHOUTW/O

WALLCOVERINGWC

WOODWD

WINDOWWDW

WINDOW OPENINGWO

WORK POINTWP

WEIGHTW T

EXTRUDED POLYSTYRENEXPS

METALMTL

NIC

MISC

OC

MISCELLANEOUS

ON CENTER

NOT IN CONTRACT

ROOM

SIMILAR

R

RM

REF

SIM

RO

SS

RADIUS

STAINLESS STEEL

ROUGH OPENING

REFRIGERATOR

MAX MAXIMUM

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MO MASONRY OPENING

MTG MOUNTING

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

OD OUTSIDE DIAMETER

OFCI OWNER FURNISHED

OFOI OWNER FURNISHED

OH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

ORD OVERFLOW ROOF DRAIN

PL PLATE

PLAM PLASTIC LAMINATE

PLYWD PLYWOOD

PR PAIR

PTD PAINTED

RD ROOF DRAIN

REINF REINFORCING

REQ'D REQUIRED

RWL RAIN WATER LEADER

SAFB SOUND ATTENUATING FIRE BLANKET

SF SQUARE FEET

SQUARESQ

STRUCTURALSTRUCT

STD STANDARD

STL STEEL

CONTRACTOR INSTALLED

OW NER INSTALLED

TTL TOTAL

PH PANIC HARDWARE

KO KNOCK OUT

GC GENERAL CONTRACTOR

IGU INSULATING GLASS UNIT

POLYISO POLYISOCYANURATEINSULATION

SAB SOUND ATTENUATING BLANKET

FP FIRE PROTECTION

TELE TELECOMMUNICATION

CONCRETE

W OOD BLOCKING - INTERRUPTED

BRICK

CONCRETE MASONRY UNIT (CMU)

INSULATION - BATT / LOOSE / BLANKET

PLYWOOD / MDF

EARTH

INSULATION - MINERAL WOOL

SPANDREL GLAZING

W OOD BLOCKING / FRAMING - CONTINUOUS

INSULATION - RIGID

GRAVEL

INSULATION - SPRAY FOAM

GW B / GROUT / SPRAY FIREPROOFING STEEL

ALUMINUM

FILL - GRANULAR

FILL - POROUS

A

#

DEMOLITION KEYNOTE

A1

AE201

A1

AE201

A3

A2A4

NEW W ORK KEYNOTE

PARTITION / W ALL TYPE

DETAIL / PLAN NUMBER

SHEET WHERE SHOW N

ELEVATION NUMBER

SHEET WHERE SHOWN

XX.X

1

COLUMN GRID LINE

ELEVATION DATUM

+12'-0"

FIRST FLOOR

ROOM DESIGNATION

DIRECTION OF SLOPE ROOF SLOPE

FLOOR DRAIN

FIRE EXTINGUISHER CABINET FIRE EXTINGUISHER BRACKET

124

FD

DETAIL, SECTION, ELEVATION TITLE

DETAIL / ENLARGED PLAN

PLAN TITLEAND NORTH ARROW

INTERIOR ELEVATION

EXTERIOR ELEVATION

ELEVATION NUMBER

SHEET WHERE SHOWN

BUILDING SECTION

SECTION NUMBER

SHEET WHERE SHOWN

DETAIL / W ALL SECTION

DOOR NUMBER120

AE301

A1

AE301

A1

AE301

A1

A1

AE101

1E1

W INDOW / LOUVER / CURTAIN WALL / STOREFRONT DESIGNATION

EXISTING COLUMN GRID LINE

#

REVISION TAG

FEC FEB

A1 DETAIL SECTION

DETAIL NUMBER

SHEET NUMBER NOTED IN GENERAL NOTES ON SHEET

A1 / AE101ADJACENT AREA REFERENCE

W 1 L1 C1 S1

ACCESSIBLE BEDROOMS - MOBILITY FEATURES ACCESSIBLE BEDROOMS - COMMUNICATION FEATURES

SPECIALTY ITEM DESIGNATION

1

MATCHLINE

BUILDING

SHEET WHERE SHOWN

SECTION NUMBER

NAMESCALE:A1

NAMESCALE:

TRUE NORTH INDICATOR

PLAN NORTH INDICATOR

101

ROOM NAME

CJ BSJ EJ

CONTROL JOINT

EXPANSION JOINT

BUILDING SEPARATION JOINT

PHOTOGRAPH / 3D VIEW REFERENCE

BUILDING

3D

A1 / AE101A1 / AE1012' x 2' ACOUSTICAL TILE LAY-IN CEILING

GW BCEILING / SOFFIT

METAL PANEL CEILING / SOFFIT

4' x 4' ACOUSTICAL TILE LAY-IN CEILING

OS

S

H P

LIGHT FIXTURE

CEILING MOUNTED EXIT

LIGHT

FIRE ALARM STROBE / FIRE ALARM HORN STROBE

SPEAKER / SPEAKER W/ STROBE

CEILING MOUNTED OCCUPANCY SENSOR

CARBON MONOXIDE SENSOR

HEAT SENSOR / PHOTO SENSOR

SMOKE DETECTOR

CEILING HEIGHT

EXPOSED CEILING

SPRINKLER HEAD

CEILING MOUNTED RECEPTACLE

CO

8'-0"

S

S

EXP

SUPPLY GRILLE / RETURN GRILLE

V F

EXHAUST FAN

CEILING MOUNTED SECURITY CAMERA

ACCESS PANEL

CEILING FAN

2' x 4' ACOUSTICAL TILE LAY-IN CEILING

CEILING MOUNTED EXIT

LIGHT W/ ARROW

EMERGENCY EGRESS LIGHT FIXTURE

INDICATES BRACKET, W ALL MOUNTED ELECTRICAL LIGHT / FIXTURE / EQUIPMENT, ETC

INDICATES BRACKET, W ALL MOUNTEDFIRE PROTECTION FIXTURE / EQUIPMENT, ETC

W OODCEILING / SOFFIT

1. PLAN DIMENSIONS SHOWN ARE TO FACE OF FRAMING MEMBERS, FACE OF MASONRY, FACE OF EXISTING WALL AND TO CENTERLINE OF COLUMNS.

2. ALL NOTES, DETAILS, AND FEATURES DRAWN AS APPLICABLE FOR ONE CONDITION ARE APPLICABLE TO SIMILAR CONDITIONS, WHETHER OR NOT SPECIFICALLY INDICATED.

3. IN STUD WALLS, LOCATE ALL INTERIOR DOOR FRAMES A DISTANCE OF 4" (FOUR) INCHES FROM THE THROAT RETURN TO THE CLOSEST ADJACENT PERPENDICULAR PARTITION, UON. IN CMU W ALLS, LOCATE MASONRY OPENING AT DOORS 8" (EIGHT) FROM THE PERPENDICULAR W ALL.

4. ALL ELEVATIONS ARE MEASURED FROM THE REFERENCE ELEVATION +0'-0", W HICH IS THE TOP OF THE FIRST FLOOR SLAB, UON.

5. DO NOT SCALE DRAWINGS TO DETERMINE DIMENSIONS OR SIZES OF BUILDING ELEMENTS.

6. ALL WOOD BLOCKING AND MISCELLANEOUS STEEL SHOW N IN DETAILS AND SECTIONS SHALL BE CONTINUOUS, UON.

7. USE FIRE-RETARDANT TREATED W OOD PRODUCTS FOR ALL CONCEALED W OOD BLOCKING, UON.

8. USE PRESERVATIVE-TREATED WOOD PRODUCTS FOR ALL W OOD BLOCKING IN CONTACT W ITH EXTERIOR MASONRY OR CONCRETE WALLS, AND FOR ALL W OOD BLOCKING IN CONTACT WITH CONCRETE SLABS ON GRADE.

9. VERIFY ALL DIMENSIONS. BRING ANY DISCREPANCIES TO THE IMMEDIATE ATTENTION OF THE ARCHITECT.

10. NOTIFY ARCHITECT OF ANY DISCREPANCY BETWEEN DRAWINGS, SPECIFICATIONS AND/OR EXISTING CONDITIONS.

11. PROVIDE W OOD OR METAL BLOCKING BEHIND GW B AT THE FOLLOWING LOCATIONS:

A. ALL WALL-MOUNTED OR CEILING-MOUNTED DOOR STOPS, DOOR HOLD-OPEN DEVICES, AND OTHER HARDWARE.

B. ALL WALL-MOUNTED TOILET ACCESSORIES. AT GRAB BARS, PROVIDE BLOCKING CAPABLE OF RESISTING A MINIMUM LOAD OF 250 POUNDS APPLIED VERTICALLY OR HORIZONTALLY AT ANY POINT ON THE GRAB BAR.

C. ALL WALL-MOUNTED PLUMBING FIXTURES, INCLUDING BUT NOT LIMITED TO LAVATORIES, SINKS, URINALS, W ATER CLOSETS, AND WATER COOLERS. PROVIDE BLOCKING CAPABLE OF RESISTING A MINIMUM LOAD OF 400 POUNDS APPLIED VERTICALLY AT ANY POINT ON THE PLUMBING FIXTURE.

D. ALL WALL-MOUNTED CABINETRY, SHELVING, AND SIMILAR ITEMS.

E. ALL WALL-MOUNTED VIDEO MONITORS, AND SIMILAR ITEMS.

12. ALL MATERIALS USED IN THE PROJECT SHALL BE NEW AND PROVIDED BY THE CONTRACTOR, UON.

13. USE BITUMINOUS MEMBRANE TO SEPARATE PRESERVATIVE-TREATED W OOD PRODUCTS FROM CONTACT WITH ANY METAL SURFACE.

JOHNSON CITY, TN 37601

210 E. W ATAUGA AVENUE

423.929.2191

1 2 3 4 5 6

A

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

SHEET

KEY PLAN

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\91

95

_E

TS

U B

uild

ing 2

Ren

ova

tio

n_

A21

_tm

cla

uchla

n.r

vt

1/7

/20

21 5

:00

:35

PM

A-001

ARCHITECTURAL LEGENDS

AND NOTES

SCHEMATIC DESIGN

Designer

Author

Checker

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

BUILDING #2 DOGW OOD AVEVA MEDICAL CENTER CAMPUSMOUNTAIN HOME, TN 37684

01.07.2021

CN 9195

60

0

ARCHITECTURAL GENERAL NOTES

ARCHITECTURAL ABBREVIATIONS

ARCHITECTURAL SYMBOLOGY

MATERIAL LEGEND

RATED PARTITION LEGEND

RCP LEGEND

NOT ALL ABBREVIATIONS, SYMBOLS, AND LEGEND GRAPHICS LISTED ARE NECESSARILY USED ON THIS PROJECT. REFER TO DOCUMENTS FOR SPECIFIC INFORMATION.

ONE HALF HOUR FIRE RATING

ONE HOUR FIRE RATING

TW O HOUR FIRE RATING

THREE HOUR FIRE RATING

FOUR HOUR FIRE RATING

(SB) SMOKE BARRIER (SB), SMOKE PARTITION (SP), OR PARTITION CAPABLE OF RESISTING THE PASSAGE OF SMOKE (S)

ELE

CT

RIC

AL

FIR

E P

RO

TE

CT

ION

AR

CH

ITE

CT

UR

AL

ME

CH

AN

ICA

L

UP

DN UP

UP

EXISTING WALL TO REMAIN

EXISTING WALL TO BE REMOVED IN ITS ENTIRETY

PORTION OF EXISTING W ALL TO BE DEMOLISHED TO RECEIVE NEW W ORK (REFER TO NEW FLOOR PLANS)

EXISTING DOOR TO REMAIN

EXISTING DOOR AND HARDW ARE TO BE REMOVED. FRAME TO REMAIN IN PLACE. REFER TO NEW W ORK FLOOR PLANS FOR DOOR TAGS.

EXISTING WALL, DOOR, FRAME AND HARDWARE TO BE REMOVED IN THEIR ENTIRETY

EXISTING PLUMBING FIXTURES TO BE REMOVED

DENOTES NEW OPENING IN EXISTING FLOOR SLAB(REFER TO STRUCTURAL)

X' - Y"

1. ALL ITEMS SALVAGED FOR OWNER SHALL BE PRESENTED TO THE OW NER FOR THE FIRST RIGHT OF REFUSAL. IF OWNER CHOOSES TO RETAIN ITEMS, THE CONTRACTOR WILL MOVE ITEMS TO THE LOCATION OF THE OW NERS CHOOSING ON SITE. IF OW NER CHOOSES TO NOT RETAIN ITEMS, CONTRACTOR IS TO DISPOSE OF ITEMS LEGALLY OFF SITE.

2. ALL ITEMS SALVAGED FOR REINSTALLATION SHALL BE PROTECTED FROM DAMAGE AND STORED ON SITE IN A SECURE LOCATION. ITEMS TO BE REINSTALLED W ILL BE CLEANED PRIOR TO INSTALLATION. IF ITEM IS DAMAGED IN ACT OF REMOVAL FROM ITS CURRENT LOCATION, NOTIFY OW NER AND ARCHITECT IMMEDIATELY.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

G

H

I

J

K

F

0201

0201 0201

0201

02010203

0204

0204

0204

0203 0203

02010203

0207

0207

0207

0203

0203

0203

0208

0208 0208

0208

0208

15 16 17 18 19 20

B

C

D

E

G

H

I

J

F

Mech

029

Mech

030

Mech

031

NO NEW W ORK IN AREA SHOW N HATCHED

COMMROOM

028

3'-0

"

6"

0208

1/8" = 1'-0"C1FIRST FLOOR DEMO PLAN

JOHNSON CITY, TN 37601

210 E. W ATAUGA AVENUE

423.929.2191

1 2 3 4 5 6

A

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

SHEET

KEY PLAN

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\91

95

_E

TS

U B

uild

ing 2

Ren

ova

tio

n_

A21

_tm

cla

uchla

n.r

vt

1/7

/20

21 5

:00

:36

PM

AD101

DEMOLITION PLANS

SCHEMATIC DESIGN

Designer

Author

Checker

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

BUILDING #2 DOGW OOD AVEVA MEDICAL CENTER CAMPUSMOUNTAIN HOME, TN 37684

01.07.2021

CN 9195

60

0

# KEY NOTESGENERAL NOTES

0201 DEMOLISH AND REMOVE EXISTING STRUCTURAL COLUMNFINISHES. PREP COLUMN FOR NEW WORK. VERIFY CONDITIONOF COLUMN PRIOR TO ANY WORK. TYPICAL AT GRID LINE "F"

0203 DEMOLISH AND REMOVE EXISTING FLOOR FINISHESTHROUGHOUT. PREP AREA FOR NEW WORK.

0204 DEMOLISH AND REMOVE ALL PLUMBING FIXTURES &ACCESSORIES WITHIN INDICATED SPACE

0207 EXISTING STAIR AND FINISHES TO REMAIN.

0208 CUT MASONRY WALL TO CREATE OR ENLARGE OPENING, SEESTRUCTURAL DWGS FOR DETAILS

1/8" = 1'-0"B5PARTIAL BASEMENT DEMO PLAN

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

B

C

D

E

G

H

I

J

K

F

Mech

029

Mech

030

Mech

031

NO NEW W ORK IN AREA SHOW N HATCHED

COMMROOM

028

8'-0

"

1. PLAN DIMENSIONS SHOWN ARE TO FACE OF FRAMING MEMBERS, FACE OF MASONRY, FACE OF EXISTING W ALL, AND TO CENTER LINE OF COLUMNS, EXCLUSIVE OF INTERIOR WALLS.

2. ALL INTERIOR DIMENSIONS ARE TO FACE OF PARTITION ASSEMBLY AS DEFINED BY THE PARTITION SCHEDULE AND IS EXCLUSIVE OF ANY APPLIED FINISH.

3. ALL FURNITURE AND LAB EQUIPMENT SHOWN GRAY ON PLANS TO BE BY OW NER

4. ALL DIMENSIONS TO BE FIELD VERIFIED PRIOR TO INSTALLATION OF EQUIPMENT / SHELVING / CASEW ORK.

5. ANY CONFLICTING INFORMATION BETWEEN THE ARCHITECTURAL DRAW INGS AND THE CIVIL, LANDSCAPE, STRUCTURAL, FIRE PROTECTION, PLUMBING, HVAC, AUDIO VISUAL OR ELECTRICAL DRAW INGS SHALL BE NOTED IN W RITING TO THE ARCHITECT FOR REVIEW AND MUST BE CLARIFIED PRIOR TO COMMENCING THE CONSTRUCTION IN QUESTION.

6. PROVIDE FIRE RETARDANT TREATED W OOD BLOCKING IN METAL STUD PARTITIONS FOR MOUNTING FIXTURES, MILLW ORK, SHELVING, HARDWARE, DOOR STOPS AND OTHER EQUIPMENT.

7. VERIFY AND COORDINATE PENETRATIONS THROUGH FLOOR SLABS, ROOF DECK AND PARTITIONS WITH PM&E AND FP DRAW INGS.

8. VERIFY AND COORDINATE FINISH FLOOR ELEVATIONS W ITH CIVIL AND STRUCTURAL PRIOR TO COMMENCING CONSTRUCTION. NOTIFY ARCHITECT IN W RITING BEFORE CONSTRUCTION OF ANY CONFLICTS.

9. REFER TO SHEET AE601 FOR DOOR SCHEDULE. REFER TO SHEET AE611 - AE612 FOR CURTAIN W ALL, LOUVER, AND STOREFRONT ELEVATIONS.

JOHNSON CITY, TN 37601

210 E. W ATAUGA AVENUE

423.929.2191

1 2 3 4 5 6

A

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

SHEET

KEY PLAN

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\91

95

_E

TS

U B

uild

ing 2

Ren

ova

tio

n_

A21

_tm

cla

uchla

n.r

vt

1/7

/20

21 5

:00

:38

PM

AE100

BASEMENT FLOOR PLAN

SCHEMATIC DESIGN

Designer

Author

Checker

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

BUILDING #2 DOGW OOD AVEVA MEDICAL CENTER CAMPUSMOUNTAIN HOME, TN 37684

01.07.2021

CN 9195

60

0

1/8" = 1'-0"1BASEMENT PLAN

# KEY NOTESGENERAL NOTES

UP

DN

REF

UP

DW

DN

1. PLAN DIMENSIONS SHOWN ARE TO FACE OF FRAMING MEMBERS, FACE OF MASONRY, FACE OF EXISTING W ALL, AND TO CENTER LINE OF COLUMNS, EXCLUSIVE OF INTERIOR WALLS.

2. ALL INTERIOR DIMENSIONS ARE TO FACE OF PARTITION ASSEMBLY AS DEFINED BY THE PARTITION SCHEDULE AND IS EXCLUSIVE OF ANY APPLIED FINISH.

3. ALL FURNITURE AND LAB EQUIPMENT SHOWN GRAY ON PLANS TO BE BY OW NER

4. ALL DIMENSIONS TO BE FIELD VERIFIED PRIOR TO INSTALLATION OF EQUIPMENT / SHELVING / CASEW ORK.

5. ANY CONFLICTING INFORMATION BETWEEN THE ARCHITECTURAL DRAW INGS AND THE CIVIL, LANDSCAPE, STRUCTURAL, FIRE PROTECTION, PLUMBING, HVAC, AUDIO VISUAL OR ELECTRICAL DRAW INGS SHALL BE NOTED IN W RITING TO THE ARCHITECT FOR REVIEW AND MUST BE CLARIFIED PRIOR TO COMMENCING THE CONSTRUCTION IN QUESTION.

6. PROVIDE FIRE RETARDANT TREATED W OOD BLOCKING IN METAL STUD PARTITIONS FOR MOUNTING FIXTURES, MILLW ORK, SHELVING, HARDWARE, DOOR STOPS AND OTHER EQUIPMENT.

7. VERIFY AND COORDINATE PENETRATIONS THROUGH FLOOR SLABS, ROOF DECK AND PARTITIONS WITH PM&E AND FP DRAW INGS.

8. VERIFY AND COORDINATE FINISH FLOOR ELEVATIONS W ITH CIVIL AND STRUCTURAL PRIOR TO COMMENCING CONSTRUCTION. NOTIFY ARCHITECT IN W RITING BEFORE CONSTRUCTION OF ANY CONFLICTS.

9. REFER TO SHEET AE601 FOR DOOR SCHEDULE. REFER TO SHEET AE611 - AE612 FOR CURTAIN W ALL, LOUVER, AND STOREFRONT ELEVATIONS.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

26'-6"14'-8"

12'-0" 12'-0" 12'-0" 12'-0" 12'-0" 14'-8" 17'-10" 13'-8" 17'-10" 14'-8" 12'-0" 12'-0" 12'-0" 12'-0" 12'-0" 14'-8" 26'-6"

A

B

C

D

E

G

H

I

J

K

F

AE410

E1

AE410

E4AE410

C4

D4

C5

D1

AE410 C1AE411

C4

C1

B4

B1

AE411

D4

D1

E4

E1

OTLECTURE /

LAB2

130

LOBBY

100 TELECOM

107

ELECT.

106

O&PSTORAGE

104

EXEC AIDE /RECEPT

101

COPY

102

WAITING

103

ELEVATOR

108

EQUIPMENTSTORAGE

118

FACULTYOFFICE

119

O/TPROGRAMDIRECTOR

120

CAPSTONEPROFESSOR

121

FACULTYOFFICE

122

FACULTYOFFICE

123

FIELDCOORDINATOR

124

EQUIPMENTSTORAGE

128

OTLECTURE /

LAB 1

129

STUDENTLOUNGE

126

STUDENTLOUNGE

127

STUDENTLOUNGE

125

UNISEX /DRESSING

112

O&PSTORAGE

113

STAIR

109O&P

FACULTY

131

O&PFACULTY

132

O&PPROGRAMDIRECTOR

133

O&P TECHOFFICE

134

LAUNDRY /CLEANING

135

CLINICALMETHODS /LECTURE

139

ASSEMBLYLAB

138

MACHINESHOP

137

O&PSTORAGE

136

CORRIDOR

140CORRIDOR

141

UNISEX /DRESSING

111

UNISEX /DRESSING

110UNISEXTOILET

116

UNISEXTOILET

115

LOCKERS

117

CUSTODIAL

114

1102

8'-0

"

17'-11 1/8"

1102

2612

28012102

B1

1102110211021102 12041102

1102

1204

0802

0601 06010601

0601

0609

1104

08071103

1104

0607

1202

1203

0503

0608

0605

0609

1102

0907

0805 0805 0805

0805

0805

0805

0805

0805

0805

0601

1201

1104

2301 1202

PDQ INFRARED

OVEN

LAN

DIS

S

HO

E

MA

CH

INE

15"

DIS

C

SA

ND

ER

DRILL PRESS

PA

NE

L S

AW

SHOPVAC

SHOPVAC

VAC STATION(FLOOR)

DU

ST

C

OLL

EC

TO

R

DUST COLLECTOR

DUST

COLLECTOR

BAND

SAW

BAND

SAW

COMPRESSOR

W ORK BENCH

MOBILESTORAGE

SANDBOX

MA

T P

LAT

FO

RM

TA

BLE

MA

T P

LAT

FO

RM

TA

BLE

SEW ING

MOBILESTORAGE

MOBILESTORAGE 5'x2'

TOOL STATION

PDQ INFRARED

OVEN

GLU

ING

TOOL STATION

TOOL STATION SANDBOX

SH

ELV

ING

SH

ELV

ING

SEW ING

TRAUTMANROUTER

TRAUTMANROUTER

TRAUTMAN

ROUTER

TRAUTMAN

ROUTERTR

AU

TM

AN

RO

UT

ER

TRAUTMAN

ROUTER

2301

2601

PDQ INFRARED

OVEN

2606

2612

2612

0808

0604

1/8" = 1'-0"B1FIRST FLOOR PLAN

JOHNSON CITY, TN 37601

210 E. W ATAUGA AVENUE

423.929.2191

1 2 3 4 5 6

A

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

SHEET

KEY PLAN

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\91

95

_E

TS

U B

uild

ing 2

Ren

ova

tio

n_

A21

_a

bru

mo

.rvt

1/7

/20

21 5

:22

:01

PM

AE101

FIRST FLOOR PLAN

SCHEMATIC DESIGN

Designer

Author

Checker

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

BUILDING #2 DOGWOOD AVEVA MEDICAL CENTER CAMPUSMOUNTAIN HOME, TN 37684

01.07.2021

CN 9195

60

0

# KEY NOTESGENERAL NOTES

1204 DRY ERASE BOARD

2102 EXISTING FIRE SPRINKLER RISER

2301 EXHAUST HOOD, SEE MECHANICAL DRAWINGS

2601 CARDKEY READER, SEE ELECTRICAL DRAWINGS

2606 NEW ELECTRICAL PANEL, SEE ELECTRICAL DRAWINGS

2612 EXISTING ELECTRICAL PANELS- SEE ELECTRICAL SHEETS

2801 FIRE ALARM CONTROL PANEL

0503 EXISTING STEEL COLUMN, PAINTED, TYPICAL ALONG GRID LINE "F"

0601 BUILT-IN CASEWORK

0604 BUILT-IN MAILBOXES, P-LAM ON 3/4" PLYWOOD

0605 CUSTOM WOOD DISPLAY CASE

0607 PHENOLIC LOCKERS

0608 EXISTING WOOD COLUMN, SANDED AND FINISHED

0609 PLYWOOD WALL TO MATCH ADJ. DISPLAY CASE

0802 ACCOUSTICALLY SEALED FOLDING PARTITION WALL

0805 EXISTING EXTERIOR WINDOW TO REMAIN, PAINT EXISTING WOODTRIM

0807 PAINTED ALUMINUM COILING DOOR

0808 ALUMINUM SLIDING WINDOW

0907 GYPSUM BOARD, PAINTED

1102 WALL MOUNTED T.V., OFCI.

1103 EQUIPMENT, NIC

1104 MOBILE STORAGE RACK, NIC

1201 FURNITURE, NIC

1202 WORK BENCH, NIC

1203 OFFICE FURNITURE, NIC

9'-0"

9'-0"

10'-0"

10'-0"11'-0"

8'-0"

10'-0"

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

G

H

I

J

K

F

10'-0"

0904

0905

09040908

0908

0908

0908

0908

0907

0908

OTLECTURE /

LAB2

130

LOBBY

100

TELECOM

107

ELECT.

106

O&PSTORAGE

104EXEC AIDE /RECEPT

101

COPY

102

WAITING

103

ELEVATOR

108

EQUIPMENTSTORAGE

118

FACULTYOFFICE

119

O/TPROGRAMDIRECTOR

120

CAPSTONEPROFESSOR

121

FACULTYOFFICE

122

FACULTYOFFICE

123

FIELDCOORDINATOR

124

EQUIPMENTSTORAGE

128

OTLECTURE /

LAB 1

129

STUDENTLOUNGE

126

STUDENTLOUNGE

127

STUDENTLOUNGE

125

UNISEX /DRESSING

112

O&PSTORAGE

113

STAIR

109O&P

FACULTY

131

O&PFACULTY

132

O&PPROGRAMDIRECTOR

133

O&P TECHOFFICE

134

LAUNDRY /CLEANING

135

CLINICALMETHODS /LECTURE

139

ASSEMBLYLAB

138

MACHINESHOP

137

O&PSTORAGE

136

CORRIDOR

140CORRIDOR

141

UNISEX /DRESSING

111

UNISEX /DRESSING

110

UNISEXTOILET

116

UNISEXTOILET

115

LOCKERS

117

CUSTODIAL

114

260426042604 2604

7'-0"7'-0" 8'-0"

2609

0908

2609

0908

1. REFER TO SHEET A-001 FOR RCP LEGEND

2. REFER TO SHEETS AExxx - AExxx FOR CEILING DETAILS.

3. ALL CEILINGS ARE x'-x" AFF, UON.

4. HVAC & LIGHTING FIXTURES SHOWN ARE FOR GRAPHICAL PURPOSES ONLY. GC TO REFER TO PME DRAW INGS AND SPRINKLER PIPING SHOP DRAW INGS AND SHOULD NOTIFY ARCHITECT IMMEDIATELY OF ANY CONFLICTS OR DISCREPANCIES.

5. GENERAL CONTRACTOR TO COORDINATE ALL SOFFIT/ BULKHEAD FRAMING W ITH FINAL LIGHTING FIXTURES & HVAC DIFFUSER LOCATIONS.

6. GENERAL CONTRACTOR TO FIELD VERIFY CEILING HEIGHTS SHOW N ON RCP DRAWINGS PRIOR TO INSTALLATION OF ALL MECHANICAL DUCTWORK, SPRINKLER PIPING, ELECTRICAL EQUIPMENT, CONDUITS, ETC. ARCHITECT TO BE NOTIFIED IMMEDIATELY OF ANY DISCREPANCIES.

7. GENERAL CONTRACTOR TO INSTALL W IRE HANGERS @ ALL CORNERS OF LIGHT FIXTURES, REGISTERS, & GRILLES.

8. REFER TO INTERIOR & EXTERIOR SECTIONS FOR ADDITIONAL CEILING DETAILS NOT NOTED ON THIS SHEET.

9. ALL RECESSED LIGHTING SHALL BE CENTERED W ITHIN THE SOFFIT DIMENSIONS, UON.

10. W HERE ACT IS LOCATED, ALL FIXTURES INCLUDING BUT NOT LIMITED TO MOTION DETECTORS, FIRE ALARM DEVICES, & SPRINKLER HEADS, ARE TO BE LOCATED IN THE CENTER OF THE TILE.

11. W HERE GWB SOFFITS SPAN LONGER THAN 30'-0", CONTROL JOINTS SHOULD BE LOCATED IN GWB SOFFIT EVERY 30'-0". ALIGN W ITH CONTROL JOINTS IN GWB W ALLS W HERE PRESENT.

2 X 4 LAY IN TROFFER FIXTURE

2 X 2 LAY IN TROFFER FIXTURE

UTILITY CLOSET PENDANT FIXTURE

RECESSED LINEAR 4" X 48" FIXTURE

4" ROUND RECESSED CAN FIXTURE

8" X 96" LINEAR PENDANT FIXTURE (DIRECT / INDIRECT)

LINEAR UNDER CABINET MOUNTED FIXTURE

2 X 2 ACT

GYPSUM W ALL BOARD

W OOD CEILING

1/8" = 1'-0"C1FIRST FLOOR REFLECTED CEILING PLAN

JOHNSON CITY, TN 37601

210 E. W ATAUGA AVENUE

423.929.2191

1 2 3 4 5 6

A

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

SHEET

KEY PLAN

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\91

95

_E

TS

U B

uild

ing 2

Ren

ova

tio

n_

A21

_tm

cla

uchla

n.r

vt

1/7

/20

21 5

:00

:41

PM

AE111

FIRST FLOOR REFLECTED

CEILING PLAN

SCHEMATIC DESIGN

Designer

Author

Checker

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

BUILDING #2 DOGW OOD AVEVA MEDICAL CENTER CAMPUSMOUNTAIN HOME, TN 37684

01.07.2021

CN 9195

60

0

# KEY NOTESGENERAL NOTES

0904 ACT CEILING

0905 WOOD SLAT CEILING WITH ACCESS PANELS DIVISION 09-FINISHES

0907 GYPSUM BOARD, PAINTED

0908 OPEN TO PAINTED STRUCTURE

2604 LIGHITNG FIXUTRE, UNDER CABINET MOUNTED, SEEELECTRICAL DRAWINGS.

2609 LINEAR PENDANT LIGHT FIXTURE, SEE ELECTRICAL DRAWINGS

1/8" = 1'-0"

FIXTURE LEGEND1/8" = 1'-0"

CEILING LEGEND

FIRST FLOOR0'-0"

6 7 8

130B 130A

06010801

0801

0907

0803 0803

0606

0802

3 4 5

129B129A

08030801 0601

0606

0907

0802

FIRST FLOOR0'-0"

G H IF

0802

0601

0606

0601

0907

1105

FIRST FLOOR0'-0"

G H I JF

104A

0907

0605

1102

345

1102 110212040805 0805 0805 0805

0907

0802

FIRST FLOOR0'-0"

678

0805 0805 0805

1102 1102

0907

0802

FIRST FLOOR0'-0"

10 11

06051102

0907

JOHNSON CITY, TN 37601

210 E. W ATAUGA AVENUE

423.929.2191

1 2 3 4 5 6

A

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

SHEET

KEY PLAN

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\91

95

_E

TS

U B

uild

ing 2

Ren

ova

tio

n_

A21

_tm

cla

uchla

n.r

vt

1/7

/20

21 5

:00

:45

PM

AE410

INTERIOR ELEVATIONS

SCHEMATIC DESIGN

Designer

Author

Checker

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

BUILDING #2 DOGW OOD AVEVA MEDICAL CENTER CAMPUSMOUNTAIN HOME, TN 37684

01.07.2021

CN 9195

60

0

3/8" = 1'-0"E1OT LAB - NORTH

3/8" = 1'-0"E4OT LECT. NORTH

3/8" = 1'-0"C5OT LECTURE EAST (FOLDING WALL)

3/8" = 1'-0"C4STUDENT LOUNGE

3/8" = 1'-0"C1LOBBY -

# KEY NOTESGENERAL NOTES

3/8" = 1'-0"D4OT LECTURE SOUTH

3/8" = 1'-0"D1OT LAB SOUTH

0601 BUILT-IN CASEWORK

0605 CUSTOM WOOD DISPLAY CASE

0606 SOLID SURFACE COUNTERTOP

0801 ALUMINUM STOREFRONT SYSTEM

0802 ACCOUSTICALLY SEALED FOLDING PARTITION WALL

0803 INTERIOR SIDELITE GLAZING

0805 EXISTING EXTERIOR WINDOW TO REMAIN, PAINT EXISTINGWOOD TRIM

0907 GYPSUM BOARD, PAINTED

1102 WALL MOUNTED T.V., OFCI.

1105 RERIDGERATOR, OFOI

1204 DRY ERASE BOARD

3/8" = 1'-0"B1LOBBY DISPLAY CASE WALL

FIRST FLOOR0'-0"

G H IF

1102

2201

1103

1103

11020907

ASSEMBLYLAB

138

FIRST FLOOR0'-0"

15 16 17 18

ASSEMBLYLAB

138

08041102

0907

138

1103

FIRST FLOOR0'-0"

15161718

ASSEMBLYLAB

138

0805

1102

0907

1103

2301

FIRST FLOOR0'-0"

GHI F

0804 0907

ASSEMBLYLAB

138

11031103 1103

2301

FIRST FLOOR0'-0"

G H IF

0804

12041103

0601

0907

CLINICALMETHODS /LECTURE

139

FIRST FLOOR0'-0"

GHI F

1102 1103

0907

104B

FIRST FLOOR0'-0"

13 14

CLINICALMETHODS /LECTURE

139

0601

1103

0804

0801 0803

0907

0907

FIRST FLOOR0'-0"

1314

12040805

1103

0907

JOHNSON CITY, TN 37601

210 E. W ATAUGA AVENUE

423.929.2191

1 2 3 4 5 6

A

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

SHEET

KEY PLAN

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\91

95

_E

TS

U B

uild

ing 2

Ren

ova

tio

n_

A21

_tm

cla

uchla

n.r

vt

1/7

/20

21 5

:00

:47

PM

AE411

INTERIOR ELEVATIONS

SCHEMATIC DESIGN

Designer

Author

Checker

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

BUILDING #2 DOGW OOD AVEVA MEDICAL CENTER CAMPUSMOUNTAIN HOME, TN 37684

01.07.2021

CN 9195

60

0

3/8" = 1'-0"E1ASSEMBLY LAB - EAST

3/8" = 1'-0"E4ASSEMBLY LAB - NORTH

3/8" = 1'-0"D4ASSEMBLY LAB - SOUTH

3/8" = 1'-0"D1ASSEMBLY LAB - WEST

3/8" = 1'-0"C1CLINICAL METHODS - EAST

3/8" = 1'-0"B1CLINICAL METHODS - WEST

3/8" = 1'-0"C4CLINICAL METHODS - NORTH

3/8" = 1'-0"B4CLINICAL METHODS - SOUTH

0601 BUILT-IN CASEWORK

0801 ALUMINUM STOREFRONT SYSTEM

0803 INTERIOR SIDELITE GLAZING

0804 INTERIOR HOLLOW MEETAL WINDOW

0805 EXISTING EXTERIOR WINDOW TO REMAIN, PAINT EXISTINGWOOD TRIM

0907 GYPSUM BOARD, PAINTED

1102 WALL MOUNTED T.V., OFCI.

1103 EQUIPMENT, NIC

1204 DRY ERASE BOARD

2201 WALL MOUNTED SINK

2301 EXHAUST HOOD, SEE MECHANICAL DRAWINGS

# KEY NOTESGENERAL NOTES

# DEMOLITION NOTE IDENTIFICATION

INDICATES ITEM TO BE REMOVED

FLEXIBLE DUCT CONNECTION

VERTICAL FIRE DAMPER

VOLUME DAMPER

CEILING RETURN, EXHAUST OR TRANSFER REGISTER

CEILING SUPPLY DIFFUSER

MITERED ELBOW WITH TURNING VANES

RETURN DUCT TURNING UP

RETURN DUCT TURNING DOWN

EXHAUST DUCT TURNING UP

EXHAUST DUCT TURNING DOWN

SUPPLY DUCT TURNING UP (ROUND OR RECTANGULAR)

SUPPLY DUCT TURNING DOWN (ROUND OR RECTANGULAR)

10"x10" SQUARE OR RECTANGULAR DUCTWORK

PIPE TURNING UP

PIPE TURNING DOWN

THERMOSTAT (C=COOLING, H=HEATING,H,C=HEATING AND COOLING

DUCT SMOKE DETECTOR

F10/6(CFM)

EXHAUST GRILLE DESIGNATION WITH CFM INDICATED

A6(CFM)

CEILING DIFFUSER DESIGNATIONWITH CFM INDICATED

G20/20 RETURN GRILLE DESIGNATION

GENERAL

DUCTWORK

MOTORIZED CONTROL DAMPER

INDICATES ROUND DUCTWORK

FLEXIBLE CONNECTION

RETURN, EXHAUST OR TRANSFER AIR FLOW

SUPPLY AIR FLOW

ACCESS DOORAD

ABOVE FINISHED FLOORAFF

ABOVE FINISHED GRADEAFG

ALUMINUMALUM

ARCHITECTURALARCH

DIAMETERDIA

DRAWINGDWG

EXISTINGEX

EXISTING TO REMAINEXR

GAUGEGA

MISCELLANEOUSMISC

NOT IN CONTRACTNIC

TYPICALTYP

UNLESS OTHERWISE NOTED

UON

GALVANIZEDGALV

AUTOMATIC AIR VENT

VALVES AND ACCESSORIES

AUTOMATIC FLOW CONTROL VALVE

BACKFLOW PREVENTER

BALL VALVE

BOTTOM CONNECTION

BUTTERFLY VALVE

CAPPED PIPE

CHECK VALVE

CLEAN OUT

CONCENTRIC REDUCER

DIRECTION OF FLOW

ECCENTRIC REDUCER

FLANGED CONNECTION

FLEXIBLE CONNECTION

FLOW METER

BALL VALVE FOR 2" & UNDERBUTTERFLY FOR 2.5" AND LARGER

GLOBE VALVE

MANUAL AIR VENT

METERED BALANCING VALVEW/PRESSURE TAPS

PRESSURE/TEMPERATURE TEST PLUGPT

PITCH

PRESSURE REDUCING VALVE

PRESSURE RELIEF VALVE

PRESSURE GAUGE WITH GAUGE COCK

STEAM TRAP

STRAINER

THREE WAY CONTROL VALVE

TWO WAY CONTROL VALVE

THERMOMETER

TOP CONNECTION

UNION

VACUUM BREAKER

VALVE IDENTIFICATION

CONTROLS

ANALOG INPUT (TO PANEL)

ANALOG OUTPUT (OUT OF PANEL)

BINARY INPUT (TO PANEL)

BINARY OUTPUT (OUT OF PANEL)

TWO WAY CONTROL VALVE

THREE WAY CONTROL VALVE

BYPASS TIMER SWITCH

COMMON

CONTROL WIRING (SIGNAL PATH)

DATA TERMINAL CABINET

DIFFERENTIAL PRESSURE SWITCH

DIFFERENTIAL PRESSURE SENSOR

DUCT SMOKE DETECTOR

FAN ON-OFF SWITCH

FAN VARIABLE SPEED SWITCH

AI

BI

BO

C

FLOW MEASURING SYSTEM

FIRESTAT

FREEZESTAT

HUMIDISTAT

LOW LIMIT TEMPERATURE SENSOR

LOCAL TEMPERATURE CONTROL PANEL

MOTOR

MOTORIZED CONTROL DAMPER

MOTOR STARTER

NORMALLY CLOSEDNC

NORMALLY OPENEDNO

POWER WIRINGEP

SENSOR

STATIC PRESSURE SENSOR

STATIC TOTALIZER STATION

SWITCH

ZONE TEMPERATURE SENSOR

TEMPERATURE TRANSMITTER

H,C

CURRENT SENSING RELAY

NORMALLY OPEN CONTROLS

NORMALLY CLOSED CONTROLS

CWR

MPS

MPC

HWS

HWR

LPS

PC

V

RS

RL

G

LPC

D

CWS

CHILLED WATER RETURN

MEDIUM PRESSURE CONDENSATE

NATURAL GAS PIPING

MEDIUM PRESSURE STEAM

LOW PRESSURE STEAM

HOT WATER SUPPLY

HOT WATER RETURN

REFRIGERANT LIQUID

REFRIGERANT SUCTION

STEAM VENT LINE

PUMPED CONDENSATE

LOW PRESSURE CONDENSATE

DIRECTION OF FLOW

CONDENSATE DRAIN LINE

CHILLED WATER SUPPLY

PIPING

FLEXIBLE DUCT CONNECTION

LEGEND

M

M

M

AO

S

P

T

TT

DTC

DPS

DSD

FMS

FZ

LL

TCP

MS

STS

BT

DP

F

VSF

FS

H

S

TSUPPLY DUCT TURNING UP (OVAL)

SUPPLY DUCT TURNING DOWN (OVAL)

10"/10" OVAL DUCTWORK

SD

V-1

# CONSTRUCTION NOTE IDENTIFICATION

INDICATES NEW ITEM

INDICATES EXISTING ITEM

REMOVE TO THIS POINT

CONNECT NEW TO EXISTING

ROOM NUMBER IDENTIFICATIONXXX

Ø

CSR

PUMP

1.

2.

3.

4.

5.

7.

8.

9.

16.

15.

14.

13.

12.

11.

10.

6.

17.

18.

19.

20.

GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH MECHANICAL DRAWING OF THIS SET. NOTES SPECIFIC TO INDIVIDUAL MECHANICAL DRAWINGS WILL BE SHOWN ON THE RESPECTIVE MECHANICAL DRAWING.

PROVIDE A COMPLETE HVAC SYSTEM TO INCLUDE ALL LABOR, MATERIALS, TOOLS, AND EQUIPMENT FOR A COMPLETE AND FUNCTIONAL SYSTEM INCLUDING ALL NECESSARY APPURTENANCES CUSTOMARILY INCLUDED IF NOT SPECIFICALLY CALLED OUT.

CONFORM WITH ALL APPLICABLE LAWS, CODES, AND REGULATIONS OF MUNICIPAL, STATE AND FEDERAL AUTHORITIES.

CONFORM TO APPLICABLE ASHRAE, NFPA, AND SMACNA STANDARDS AND OTHER REGULATORY BODIES HAVING JURISDICTION OVER THE CLASS OF WORK.

MATERIALS AND EQUIPMENT SHALL HAVE STAMPS OR SEALS OF ARI, ASME, UL, AND ASTM.

MAKE TESTS FOR ACCEPTANCE AND APPROVAL AS REQUIRED BY CODE AND THE REQUIREMENTS OF APPLICABLE REGULATORY AGENCIES. REQUIRED TESTS SHALL BE PERFORMED IN THE PRESENCE OF THE OWNER UNLESS OTHERWISE WAIVED IN WRITING.

OBTAIN AND PAY FOR ALL PERMITS, LICENSES, DOCUMENTS, AND SERVICES RELATED TO INSTALLATION OF THE WORK.

EQUIPMENT OF HIGHER ELECTRICAL CHARACTERISTICS MAY BE SUBSTITUTED PROVIDED SUCH PROPOSED EQUIPMENT IS APPROVED IN WRITING AND CONNECTING ELECTRICAL SERVICE, CIRCUIT BREAKERS AND CONDUIT SIZES ARE APPROPRIATELY MODIFIED AT NO COST TO THE OWNER.

COORDINATE WORK WITH THE OTHER TRADES IN ORDER TO RESOLVE ANY CONFLICT THAT MIGHT ARISE DUE TO THE LOCATION OF EQUIPMENT OR THE USE OF SPACE.

RUN ALL HORIZONTAL PIPING AND DUCTWORK ABOVE CEILING UNLESS OTHERWISE NOTED.

CUT OPENINGS, AS REQUIRED, IN THE EXISTING CONSTRUCTION FOR THE INSTALLATION OF PIPING, DUCTWORK, AND EQUIPMENT. PATCH AND REPAIR TO MATCH THE EXISTING ADJACENT CONSTRUCTION.

ALL ELBOWS IN DUCTWORK SHALL BE RADIUS ELBOWS UNLESS OTHERWISE NOTED. WHERE SQUARE ELBOWS ARE SHOWN, INSTALL DOUBLE WALL TURNING VANES. RADIUS ELBOWS SHALL HAVE A MINIMUM CENTERLINE RADIUS OF CURVATURE OF 1.5 TIMES DUCT WIDTH OR DIAMETER

MAKE DUCT PENETRATIONS OF ALL WALLS WITH SHEET METAL DUCTS. FLEXIBLE DUCT PENETRATIONS OF WALLS ARE NOT ACCEPTABLE.

REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF DIFFUSERS, REGISTERS, AND GRILLES. FINISH AND COLOR TO BE SELECTED BY GOVERNMENT FROM MANUFACTURER'S STANDARD PALETTE.

DO NOT INSTALL EQUIPMENT, PIPING OR DUCTWORK OVER ANY ELECTRICAL EQUIPMENT OR ELECTRICAL SERVICE SPACE.

PROVIDE DYNAMIC FIRE AND SMOKE DAMPERS IN ACCORDANCE WITH THEIR U.L. LISTING AND THE REQUIREMENTS OF NFPA-90A.

PROVIDE ACCESS PANELS WHERE COMPONENTS REQUIRING ACCESS ARE INSTALLED BEHIND WALLS OR ABOVE INACCESSIBLE CEILINGS. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS.

LAYOUT OF PIPING AND DUCTWORK IS DIAGRAMMATIC. RUN ALL EXPOSED PIPING AND DUCTWORK AS HIGH AS POSSIBLE UNLESS OTHERWISE NOTED. ALLOW FOR RISES, DROPS AND OFFSETS AS REQUIRED.

DUCTWORK SIZES ARE INSIDE CLEAR DIMENSIONS.

INSTALL MECHANICAL EQUIPMENT TO FACILITATE SERVICING, MAINTENANCE, AND REPAIR OR REPLACEMENT OF EQUIPMENT COMPONENTS. CONNECT EQUIPMENT FOR EASE OF DISCONNECTING, WITH A MINIMUM OF INTERFERENCE WITH OTHER INSTALLATIONS. PIPING SHALL NOT INTERFERE WITH FILTER PULL. MAINTAIN EQUIPMENT MANUFACTURER'S RECOMMENDED MINIMUM SERVICE CLEARANCE.

21.

22.

23.

24.

25.

27.

28.

29.

34.

33.

32.

31.

30.

26.

MECHANICAL CONTRACTOR SHALL PROVIDE AUTOMATIC CONTROL DEVICES, SUCH AS TEMPERATURE SENSORS, RELAYS, PRESSURE SWITCHES WHICH ARE ASSOCIATED WITH MECHANICAL EQUIPMENT AND ASSOCIATED CONTROL WIRING FROM STARTER TO THE CONTROL DEVICE. ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT AND WIRING FROM POWER SOURCE TO DISCONNECT SWITCH, FROM DISCONNECT SWITCH TO STARTER, AND FROM STARTER TO THE EQUIPMENT.

ALL CONTROL WIRING EXCEPT IN EQUIPMENT ROOMS SHALL BE RUN CONCEALED. WIRING IN WALLS SHALL BE IN CONDUIT. ALL WIRING SHALL BE PLENUM RATED. CONTROL WIRING IN EXPOSED AREAS SHALL BE BUNDLED AND SECURED OR RUN IN CONDUIT. NO WIRING MUST BE SURFACE MOUNTED IN FINISHED SPACES. ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE.

LOCATE THERMOSTATS 48" ABOVE FINISHED FLOOR OR AS NOTED ON THE PLANS.

FOR EQUIPMENT WITH WATER OR STEAM CONNECTIONS, OR ANY COOLING EQUIPMENT, PROVIDE AUXILIARY DRAIN PANS UNDER EQUIPMENT LOCATED ABOVE CEILINGS.

ALL VALVES ARE FULL LINE SIZE EXCEPT CONTROL AND BALANCING VALVES. SIZE CONTROL VALVES TO OPERATE ACROSS THE FULL RANGE OF FLOW AT THE COIL SERVED.

FOR BALANCING 3-WAY VALVES, BALANCE BY-PASS WITH VALVE AT 50% POSITION SUCH THAT TOTAL FLOW DOES NOT EXCEED 100%.

PROVIDE PRESSURE/TEMPERATURE (P/T) PLUGS, WITH CAPS UP AND DOWNSTREAM OF ALL EQUIPMENT, AT THE SUPPLY AND RETURN TAPS OF ALL PIPING BRANCHES AND WHERE INDICATED. PROVIDE EXTENDED PLUGS AND LABELS WHERE PIPING IS INSULATED. PROVIDE REMOVABLE INSULATION PLUG.

PROVIDE FLUSHING VALVES AND TEES AT BOTH SIDES OF ALL EQUIPMENT. TAPS SHALL MATCH EQUIPMENT PIPING UP TO 1". FOR LARGER EQUIPMENT AND PIPE LOOPS PROVIDE 1 1/2" TAPS AND VALVES.

PROVIDE MANUAL AIR VENTS AT ALL HIGH POINTS AND THE ENDS OF ALL PIPING LOOPS. PROVIDE 1/2" DRAIN VALVES AT LOW POINTS IN PIPING. PROVIDE MINIMUM PITCH SUFFICIENT TO INSURE ADEQUATE VENTING AND DRAINING.

LOCATE AND SIZE 5 1/2" THICK CONCRETE HOUSEKEEPING PADS AND CURBS IN ACCORDANCE WITH ACTUAL EQUIPMENT PURCHASED. EXTEND PAD BEYOND EQUIPMENT FOR 6" IN ALL DIRECTIONS.

ALL EQUIPMENT REMOVED FROM THE BUILDING, DURING DEMOLITION, SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE SITE UNLESS OTHERWISE NOTED.

EXISTING DUCT, PIPE AND EQUIPMENT SIZES NOTED ARE FOR THE CONVENIENCE OF THE CONTRACTOR ONLY AND ARE NOT WARRANTED TO BE CORRECT. FIELD VERIFY ALL EXISTING DUCT, PIPE AND EQUIPMENT SIZES AND THEIR RESPECTIVE LOCATIONS BEFORE PROCEEDING WITH ANY ASSOCIATED WORK.

PRIOR TO SUBMITTING A PROPOSAL THE CONTRACTOR IS STRONGLY ENCOURAGED TO VISIT THE SITE AND THOROUGHLY INSPECT ALL EXISTING CONDITIONS TO INSURE THAT THE WORK REPRESENTED ON THE DRAWINGS CAN BE INSTALLED AS INDICATED.

UNLESS OTHERWISE NOTED, FLEXIBLE CONNECTORS AND RIGID DUCT RUNOUTS SERVING A SINGLE GRILLE/REGISTER/DIFFUSER MUST BE THE SAME SIZE AS THE GRILLE/REGISTER/DIFFUSER NECK. REFER TO SCHEDULES FOR NECK SIZES.

GENERAL NOTES

REFER TO ELECTRICAL DRAWINGS FOR VOLTAGE AND PHASE REQUIREMENTS FOR ALL EQUIPMENT REQUIRING AN ELECTRICAL CONNECTION.

35.

ALL REFRIGERANT PIPING MUST BE SIZED IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTRUCTIONS.

36.

JOHNSON CITY, TN 37601

210 E. WATAUGA AVENUE

423.929.2191

DESIGN:

DRAWN:

REVIEW:

SHEET

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\919

5_

Pro

ject

Na

me

M2

1_

WW

illia

ms.r

vt

1/7

/20

21 1

2:2

5:4

6 P

M

M-001

MECHANICAL LEGEND

SCHEMATIC DESIGN

WAW

JD

WAW

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

Ed Allen Hall, 3rd St, Johnson City, TN 37604

01.07.2021

CN 9195

1100

1. FOR LEGEND AND GENERAL NOTES SEE SHEET M-001.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

I

J

K

(TYP)

(TYP)

1

2

2

JOHNSON CITY, TN 37601

210 E. WATAUGA AVENUE

423.929.2191

1 2 3 4 5 6

A

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

SHEET

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\919

5_

Pro

ject

Na

me

M2

1_

WW

illia

ms.r

vt

1/7

/20

21 1

2:2

5:4

7 P

M

MD101

FIRST FLOOR DEMOLITION

PLAN - HVAC

SCHEMATIC DESIGN

WAW

JD

WAW

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

Ed Allen Hall, 3rd St, Johnson City, TN 37604

01.07.2021

CN 9195

1100

GENERAL NOTES # DEMOLITION NOTES

1/8" = 1'-0"1FIRST FLOOR DEMOLITION PLAN - HVAC

1 REMOVE OUTDOOR AIR DUCT BACK TO LOCATION INDICATED.

2 REMOVE CEILING MOUNTED FAN COIL UNIT.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

I

J

K

(TYP)

1

22 (TYP)

1. FOR LEGEND AND GENERAL NOTES SEE SHEET M-001.

JOHNSON CITY, TN 37601

210 E. WATAUGA AVENUE

423.929.2191

1 2 3 4 5 6

A

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

SHEET

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\919

5_

Pro

ject

Na

me

M2

1_

WW

illia

ms.r

vt

1/7

/20

21 1

2:2

5:4

8 P

M

MD102

FIRST FLOOR DEMOLITION

PLAN - PIPING

SCHEMATIC DESIGN

WAW

JD

WAW

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

Ed Allen Hall, 3rd St, Johnson City, TN 37604

01.07.2021

CN 9195

1100

1/8" = 1'-0"1FIRST FLOOR DEMOLITION PLAN - PIPING

GENERAL NOTES # DEMOLITION NOTES

1 REMOVE HWS/HWR AND CWS/CWR BACK TO RISER. MAKE READY FOR RECONNECTION. COORDINATE SYSTEM OUTAGES WITH ETSU AND VA. INSTALL ISOLATION VALVES AT RISER TAKEOFFS.

2 REMOVE CEILING MOUNTED FCU, CONTROLS, SUPPORT, AND CONDENSATION DRAIN.

1. FOR LEGEND AND GENERAL NOTES SEE SHEET M-001.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

I

J

K

EF-1

1 2 2

3

MAU-1

4

55

6

77

8

JOHNSON CITY, TN 37601

210 E. WATAUGA AVENUE

423.929.2191

1 2 3 4 5 6

A

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

SHEET

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\919

5_

Pro

ject

Na

me

M2

1_

WW

illia

ms.r

vt

1/7

/20

21 1

2:2

5:4

8 P

M

MH100

BASEMENT FLOOR NEW WORK

PLAN - HVAC

SCHEMATIC DESIGN

WAW

JD

WAW

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

Ed Allen Hall, 3rd St, Johnson City, TN 37604

01.07.2021

CN 9195

1100

1 OVEN HOOD EXHAUST DOWN FROM FIRST FLOOR.

2 REMOVE WINDOW AND INSTALL LOUVER.

3 MAKE UP AIR UNIT FOR OVEN HOOD. CONNECT TO CHILLED WATER AND HOT WATER FROM ADJACENT MECHANICAL ROOM.

4 EXISTING DOAS UNIT.

5 EXISTING CHILLED WATER PUMPS.

6 EXISTING STEAM TO WATER HEAT EXCHANGER.

7 EXISTING HOT WATER PUMPS.

8 EXISTING AIR COOLED CHILLER.

# KEY NOTESGENERAL NOTES

1/8" = 1'-0"1BASEMENT FLOOR - NEW - DUCT

REF

DW

1. FOR LEGEND AND GENERAL NOTES SEE SHEET M-001.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

I

J

K

1

1 1

1 1

1 1

1

1 1 1 1 1 1 1

2

2

234

5

5

211

4

4

1

1

1

1

1 1 1

223

1

1

1

1

4

1

1

1

66

77

8

8

3

FCU-6

FCU-5

FCU-8

FCU-6

FCU-4

FCU-4 FCU-4

FCU-4 FCU-4

FCU-4 FCU-4

FCU-4

FCU-1 FCU-1 FCU-1 FCU-1 FCU-1 FCU-1 FCU-1

FCU-2

FCU-7

FCU-10FCU-3FCU-2

FCU-2

AC-1

AC-1

FCU-9

FCU-4

FCU-4

FCU-4

FCU-4

FCU-2

FCU-1 FCU-1 FCU-1 FCU-1

FCU-9FCU-4

FCU-4

FCU-4

FCU-8

FCU-7

CORRIDOR

141

STUDENT LOUNGE

125

STUDENT LOUNGE

127

STUDENT LOUNGE

126

EQUIPMENTSTORAGE

128

OT LECTURE / LAB 1

129

OT LECTURE / LAB2

130

FIELDCOORDINATOR

124

FACULTY OFFICE

123

FACULTY OFFICE

122

CAPSTONEPROFESSOR

121

O/T PROGRAMDIRECTOR

120

FACULTY OFFICE

119

EQUIPMENTSTORAGE

118

LOCKERS

117

UNISEX TOILET

115

UNISEX TOILET

116

CUSTODIAL

114

O&P STORAGE

113

STAIR

109

LOBBY

100

ELEVATOR

108

WAITING

103

EXEC AIDE / RECEPT

101

COPY

102

O&P STORAGE

104

TELECOM

107

ELECT.

106

CLINICAL METHODS /LECTURE

139

ASSEMBLY LAB

138

CORRIDOR

140

UNISEX / DRESSING

110

UNISEX / DRESSING

111

UNISEX / DRESSING

112

O&P FACULTY

131

O&P FACULTY

132

O&P PROGRAMDIRECTOR

133

O&P TECH OFFICE

134

LAUNDRY /CLEANING

135O&P STORAGE

136

MACHINE SHOP

137

20"ø

18"x18"

9

10

1118"X18" 12

13

JOHNSON CITY, TN 37601

210 E. WATAUGA AVENUE

423.929.2191

1 2 3 4 5 6

A

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

SHEET

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\919

5_

Pro

ject

Na

me

M2

1_

WW

illia

ms.r

vt

1/7

/20

21 1

2:2

5:4

9 P

M

MH101

FIRST FLOOR NEW WORK PLAN

- HVAC

SCHEMATIC DESIGN

WAW

JD

WAW

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

Ed Allen Hall, 3rd St, Johnson City, TN 37604

01.07.2021

CN 9195

1100

1 EXPOSED CEILING MOUNTED FAN COIL UNIT.

2 DUCTED FAN COIL UNIT.

3 EXPOSED DUCT WORK.

4 EXPOSED FLOOR MOUNTED FAN COIL UNIT.

5 DUCTLESS SPLIT SYSTEM.

6 CONNECT TO EXISTING EXHAUST RISER.

7 TO DIFFUSER IN SOFFIT.

8 TO LINEAR SLOT DIFFUSER.

9 PROVIDE 4" DRYER EXHAUST AND WALL CAP.

10 EXHAUST HOOD OVER OVENS. CONTROL VIA FACE MOUNTED SWITCH.

11 DOWN TO GROUND FLOOR.

12 SUPPLY DUCT UP FROM BASEMENT. MAKE UP AIR FOR OVEN HOOD.

13 O.A. DUCT TO BE EXTENDED TO FCUS.

1/8" = 1'-0"1FIRST FLOOR NEW WORK PLAN - HVAC

# KEY NOTESGENERAL NOTES

REF

DW

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

I

J

K

1

2

2

2

2

CWSCWR

HWSHWR

CWSCWR

HWSHWR CWS

CWRHWS

HWR

CWSCWR

HWSHWR

FCU-6

FCU-1 FCU-1 FCU-1 FCU-1

FCU-4

FCU-4

FCU-4 FCU-4

FCU-4 FCU-4

FCU-4

FCU-2

FCU-9

FCU-1

FCU-2 FCU-3FCU-10

FCU-2

AC-1

AC-1

FCU-4

FCU-7FCU-1 FCU-1

FCU-1FCU-1

FCU-4 FCU-4 FCU-4 FCU-2

FCU-9

FCU-7FCU-4

FCU-4

FCU-4

FCU-8FCU-8FCU-6

FCU-1 FCU-1

CORRIDOR

141

STUDENT LOUNGE

125

STUDENT LOUNGE

127

STUDENT LOUNGE

126

EQUIPMENTSTORAGE

128

OT LECTURE / LAB 1

129

OT LECTURE / LAB2

130

FIELDCOORDINATOR

124

FACULTY OFFICE

123

FACULTY OFFICE

122

CAPSTONEPROFESSOR

121

O/T PROGRAMDIRECTOR

120

FACULTY OFFICE

119

EQUIPMENTSTORAGE

118

LOCKERS

117

UNISEX TOILET

115

UNISEX TOILET

116

CUSTODIAL

114

O&P STORAGE

113

STAIR

109

LOBBY

100

ELEVATOR

108

WAITING

103

EXEC AIDE / RECEPT

101

COPY

102

O&P STORAGE

104

TELECOM

107

ELECT.

106

CLINICAL METHODS /LECTURE

139

ASSEMBLY LAB

138

CORRIDOR

140

UNISEX / DRESSING

110

UNISEX / DRESSING

111

UNISEX / DRESSING

112

O&P FACULTY

131

O&P FACULTY

132

O&P PROGRAMDIRECTOR

133

O&P TECH OFFICE

134

LAUNDRY /CLEANING

135

O&P STORAGE

136

MACHINE SHOP

137

1. FOR LEGEND AND GENERAL NOTES SEE SHEET M-001.

JOHNSON CITY, TN 37601

210 E. WATAUGA AVENUE

423.929.2191

1 2 3 4 5 6

A

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

SHEET

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\919

5_

Pro

ject

Na

me

M2

1_

WW

illia

ms.r

vt

1/7

/20

21 1

2:2

5:5

2 P

M

MP101

FIRST FLOOR NEW WORK PLAN

- PIPING

SCHEMATIC DESIGN

WAW

JD

WAW

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

Ed Allen Hall, 3rd St, Johnson City, TN 37604

01.07.2021

CN 9195

1100

1/8" = 1'-0"1FIRST FLOOR NEW WORK PLAN - PIPING

1 CONNECT TO EXISTING CWS/CWR AND HWS/HWR PIPES.

2 FCU FED FROM BELOW.

# KEY NOTESGENERAL NOTES

JOHNSON CITY, TN 37601

210 E. WATAUGA AVENUE

423.929.2191

1 2 3 4 5 6

A

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

SHEET

SUBMITTAL

PROFESSIONAL SEAL

DESIGNER

REVISIONS

C:\R

evit P

roje

cts

\919

5_

Pro

ject

Na

me

M2

1_

WW

illia

ms.r

vt

1/7

/20

21 1

2:2

5:4

6 P

M

M-601

SCHEDULES

SCHEMATIC DESIGN

Designer

Author

Checker

ETSU BUILDING 2

RENOVATION

EAST TENNESSEE STATE UNIVERSITY

Ed Allen Hall, 3rd St, Johnson City, TN 37604

01.07.2021

CN 9195

1100

1: PROVIDE WITH PREWIRED FAN SPEED CONTROLLER, RUBBER IN SHEAR VIBRATION ISOLATORS, BUILT IN THERMAL OVERLOAD PROTECTION ANDNON FUSED DISCONNECT.

NOTES:

EF-1 2500 0.75 X EQD-15-VG 2 175 6750 15 X X 1:

CO

OK

GR

EE

NH

EC

K

MAX. HP.

DIR

EC

T

BE

LT

GR

AV

ITY

DA

MP

ER

ELE

CT

RIC

DA

MP

ER

BIR

D S

CR

EE

N

RO

OF

CU

RB

NOTES

MARK C.F.M.E.S.P. IN.

W.G.

MNFR

MODEL NO.

MOTORMAX

OPER.WEIGHT

(LBS)

MAX. TIPSPEEDF.P.M.

MAX.NOISESONES

DRIVE ACCESSORIES

MARK:SF=SUPPLY FANEF=EXHAUST FANRF=RETURN FAN

FAN SCHEDULE

NOTES:

FCU-10 X 520 0.25 75/63 54.5/53.5 13.3 10.6 45/55 2.9 1.51 0.09 15.7 67/95 180/160 1.57 0.37 0.04

FCU-9 X 350 0.25 75/63 56.7/54.7 7.77 6.33 45/55 1.8 0.8 0.03 10.6 67/95 180/160 1.06 0.15 0.02

FCU-8 X 100 0.05 75/63 55.7/54 2.46 1.92 45/55 0.5 3.32 0.03 3.02 67/95 180/160 0.30 0.23 0.01

FCU-7 X 250 0.25 75/63 53.6/52.9 6.85 5.34 45/55 1.5 1.35 0.06 7.56 67/95 180/160 0.756 0.3 0.03

FCU-6 X 375 0.15 75/63 55.1/53.4 9.87 7.46 45/55 2.1 3.28 0.04 11.3 67/95 180/160 1.13 0.05 0.01

FCU-5 X 375 0.15 74/62 58.1/56.0 5.93 5.8 45/55 1.5 0.33 0.04 11.3 67/95 180/160 1.13 0.17 0.03

FCU-4 X 550 0.15 74/62 54.5/53.3 12.7 10.7 45/55 2.8 1.39 0.09 16.6 67/95 180/160 1.66 0.33 0.05

FCU-3 X 75 0.15 74/62 53.2/52.9 1.77 1.5 45/55 0.4 0.3 0.01 2.27 67/95 180/160 0.23 0.06 0.02

FCU-2 X 225 0.15 74/62 57.5/55.8 3.75 3.68 45/55 0.8 0.4 0.04 6.80 67/95 180/160 0.68 0.13 0.02

FCU-1 X 120 0.15 74/62 55.3/54.6 2.36 2.15 45/55 0.5 0.5 0.02 3.18 67/95 180/160 0.32 0.06 0.01

EX

PO

SE

DC

EIL

ING

DU

CT

ED

FLO

OR

MO

UN

TE

D

MARK

TYPE

MODEL NO.SUPPLYC.F.M.

E.S.P. IN.W.G.

MAX. HP.COOLING

EATCOOLING

LATTOTAL

COOLING MBHSENSIBLE

COOLING MBHCOOLINGEWT/LWT

COOLINGGPM

WPDAIR PRESSURE

DROP

HEATINGCAPACITY

MBH

HEATINGEAT/LAT

HEATINGEWT/LWT

HEATING GPM WPDAIR PRESSURE

DROPNOTES

FAN COIL UNIT SCHEDULE

2: EXISTING PUMP TAG NOT LEGIBLE

1: EXISTING PUMP TO BE REBALANCED. CAPCITY SHOWN BASED ON EXISTING CONDITIONS.

NOTES:

HPW-2 X * * 2 HOT WATER 1:2:

HPW-1 X * * 2 HOT WATER 1:2:

CWP-2 X 560 70 15 CHILLED WATER 1:

CWP-1 X 560 70 15 CHILLED WATER 1:

TA

CO

B&

G

MARK

MNFR

MODELSERIES

NO.

CAPACITYG.P.M.

WATERHEAD FT

W.G.

MAX.MOTOR HP.

SERVICE FLUID NOTES

PUMP SCHEDULE

1. REFER TO HOOD DETAIL DRAWINGS

NOTES:

H-1 2500 0.25 X 12' 4" 5' 6" 1:

304 S

.S. 16

GA LENGTH WIDTH

SKIRTHIGHT

MARKAIR

FLOWCFM

MAXIMUM AIRLOSS IN W.G.

MATERIAL DIMENSION

NOTES

INDUSTRIAL HOOD SCHEDULE

1: PROVIDE WITH HARD WIRED WALL MOUNTED THERMOSTAT AND FACTORY CONTROLS.

NOTES:

AC-1/CU-1 X X 38MPRAQ09AA3 40MPHAQ09ZA3 245 9.0 1:

MIT

SU

BIS

HI

SA

MS

UN

G

CA

RR

IER

CE

ILIN

G M

OU

NT

ED

DU

CT

ED

WA

LL H

UN

G OUTDOOR UNIT INDOOR UNITMARK

MNFR TYPE MODEL NO.

SUPPLYC.F.M.

TOTALCOOLING

MBHNOTES

DUCTLESS SPIT SYSTEM

NOTES:

MAU-1 2,500 0.5 86.7/71.8 55/54 144.9 86 45/55 26.3 171.4 8.8/72 180/160 17.1

MARK MAKE MODEL NO.SUPPLYC.F.M.

E.S.P. IN.W.G.

MAX. HP.COOLING

EATCOOLING

LATTOTAL

COOLING MBHSENSIBLE

COOLING MBHCOOLINGEWT/LWT

COOLINGGPM

WPDAIR PRESSURE

DROP

HEATINGCAPACITY

MBH

HEATINGEAT/LAT

HEATINGEWT/LWT

HEATING GPM WPDAIR PRESSURE

DROPNOTES

MAKE UP AIR UNIT


Recommended