PRODUCT CATALOGUE | 2013 AUSTRALIAN MADE Evaporative Condensers Induced Draft
Transcript
Page 1: Evaporative Condensers Induced Draft

PRODUCT CATALOGUE | 2013AUSTRALIAN MADE

Evaporative CondensersInduced Draft

Page 2: Evaporative Condensers Induced Draft

2 www.fct.net.au

DisclaimerThe information or advice contained in this catalogue is intended for use only by persons who have had adequate

technical training in the field to which the catalogue relates. The information in this catalogue is a guide only and not to

be used for construction. The user should also establish the applicability of the information or advice in relation to any

specific circumstances. While the information or advice is believed to be correct the employees and agents disclaim

responsibility for any inaccuracies contained within the document including those due to any negligence in the preparation

and publication of the catalogue.

Page 3: Evaporative Condensers Induced Draft

3www.fct.net.au

Contents

5Company Profile

3Contents2Disclaimer

6Evaporative Condensors Induced Draft

20Access and Maintenance 19Engineering Design Layout 18Components

23Plinth Arrangements 22Lifting Techniques 21Sound Levels

26Site Assembly 25Freight24Variable Speed Drives

28Modular Design 27Compliance with the Standards

29Notes

4Nomenclature

10Quick Selection DataFeatures Engineering DataSound Data Line Drawing

121416

7

Page 4: Evaporative Condensers Induced Draft

4 www.fct.net.au

Nomenclature (Model Number Legend)

ctcf f 215 a ln1 2 3 4 5

CTCF - Cooling Tower Counter Flow CTDF - Cooling Tower Dual Flow

CFSF - Cooling Tower Single Flow

CTFD - Cooling Tower Forced Draft

Open Cooling Towers1.

ECCF - Evaporative Condenser Counter Flow ECFD - Evaporative Condenser Forced Draft

Evaporative Condensers

IFCCF - Industrial Fluid Cooler Counter Flow IFCFD - Industrial Fluid Cooler Forced Draft

Industrial Fluid Coolers

F - Fibreglass M - Metal Mild Steel

SS - Stainless Steel

Material of Construction2.

Series4.

S - Standard LN - Low Noise

Fan Type5.

Kilowatts Total Heat Rejection with conditions 35/ 29.5/ 24 Deg. Celcius divided by 10Cooling Towers

3.

Kilowatts Total Heat Rejection with conditions 40.5 Deg. Celcius, Condensing @ 24 Deg. Celcius Wet Bulb divided by 10. For R22 and R134A

Evaporative Condensers

Kilowatts Total Heat Rejection with conditions 35/ 29.5/ 24 Deg. Celcius divided by 10Industrial Fluid Coolers

Page 5: Evaporative Condensers Induced Draft

5www.fct.net.au

FIBREFLOW COOLING TOWERS

Fibreflow Cooling Towers is wholly Australian owned and made. Fibreflow

Cooling Towers was established in response to the demand for a quality HVAC

manufacturer in Australia and develop and design composite products to related

manufacturing methods. Various production methods include cold pressing heavy section

FRP mouldings and forming hollow and complex one piece FRP sections. Our production

methods use the best isophthalic, vinyl ester resins, gelcoats and high quality reinforcements.

Our products are developed to stand the test of time with the quality, lifecycle and performance

that goes above and beyond the expectations of our customers. With a combined experience of

over 50 years in the industry, we have formed an insight as to what is required of our products,

thus meeting the market with the best solutions for the application. Typical applications include

cooling tower structures and components, support assemblies, motor mounts and bearing

housing mounts in a variety of materials to suit the clients’ requirements. Our range of FRP

Process Cooling equipment are developed and manufactured right here in Australia. With

benefits ranging from the low cost of ownership to long service life, high quality materials and

virtually no maintenance, we can provide a tailored solution for your application.

Company Profile

AUSTRALIAN MADE

Page 6: Evaporative Condensers Induced Draft

Evaporative CONDENSORS

Induced Draft

6 www.fct.net.au

Page 7: Evaporative Condensers Induced Draft

7www.fct.net.au

NOTE: Do not use for construction. Refer to your sales representative for certified weights & dimensions. Data subject to change for product improvement.

Evaporative CONDENSORS

Quick Selection - Induced Draft - ECCF Model

MODEL WET BULB - DEG C

ECCF BOX SIZE MOTOR (KW) 18 19 20 21 22 23 24 25 25.5 26 27 28

TOTAL HEAT REJECTION (KW) AT 40.5 DEG CONDENSING FOR R22 & R134A

010 3 x 3 0.55 116 112 109 105 102 98 95 90 88 86 81 71

012 3 x 3 0.75 145 140 136 131 127 123 119 113 110 107 101 89

015 3 x 3 1.5 184 179 173 167 162 156 151 144 140 137 129 113

017 4 x 4 1.5 211 204 198 191 185 179 173 164 160 156 147 130

018 4 x 4 2.2 217 210 204 197 191 184 178 169 165 161 152 134

020 4 x 4 3.0 237 230 223 215 208 201 194 185 180 176 165 146

024 4 x 4 4.0 292 283 275 265 257 248 240 228 222 217 204 180

027 4 x 6 1.5 329 319 310 299 289 279 270 256 250 244 230 202

033 4 x 6 2.2 395 383 372 358 347 335 324 308 300 293 275 243

038 4 x 6 4.0 461 446 434 418 405 391 378 359 350 341 321 283

043 4 x 6 5.5 526 510 496 478 463 446 432 410 400 390 367 324

044 4 x 9 1.5 539 523 508 490 475 458 443 421 410 400 376 332

053 4 x 9 2.2 645 625 607 585 567 547 529 503 490 478 450 397

059 4 x 9 3.0 711 689 669 645 625 603 583 554 540 527 496 437

064 4 x 9 4.0 776 753 731 705 683 658 637 605 590 576 542 478

066 4 x 12 2.2 803 778 756 729 706 681 659 626 610 595 560 494

074 4 x 12 3.0 895 867 843 812 787 759 734 697 680 663 624 551

082 4 x 12 4.0 1000 969 942 908 880 848 821 779 760 741 698 615

088 4 x 12 5.5 1066 1033 1004 968 938 904 875 831 810 790 744 656

028 5 x 5 3.0 342 332 322 311 301 290 281 267 260 254 239 211

035 5 x 5 4.0 421 408 397 382 370 357 346 328 320 312 294 259

041 5 x 5 5.5 500 485 471 454 440 424 410 390 380 371 349 308

051 6 x 6 4.0 624 605 587 566 549 529 512 486 474 463 435 384

058 6 x 6 5.5 709 687 668 644 624 601 582 553 539 526 495 436

063 6 x 6 7.5 766 742 721 695 673 649 628 597 582 568 534 471

070 6 x 8 4.0 851 825 801 772 748 722 698 663 647 631 594 523

080 6 x 8 5.5 974 944 917 884 856 826 799 759 740 722 680 599

087 6 x 8 7.5 1049 1017 988 953 923 890 861 818 797 778 732 646

092 8 x 8 5.5 1118 1084 1053 1016 984 949 918 872 850 829 781 688

102 8 x 8 7.5 1237 1199 1165 1123 1088 1049 1015 964 940 917 863 761

112 8 x 8 11.0 1355 1314 1276 1231 1192 1150 1112 1056 1030 1005 946 834

Page 8: Evaporative Condensers Induced Draft

8 www.fct.net.au

NOTE: Do not use for construction. Refer to your sales representative for certified weights & dimensions. Data subject to change for product improvement.

Evaporative CONDENSORS

Quick Selection - Induced Draft - ECCF Model

MODEL WET BULB - DEG C

ECCF BOX SIZE MOTOR (KW) 18 19 20 21 22 23 24 25 25.5 26 27 28

TOTAL HEAT REJECTION (KW) AT 40.5 DEG CONDENSING FOR R22 & R134A

115 8 x 10 5.5 1395 1352 1314 1266 1227 1183 1145 1087 1060 1034 973 858

130 8 x 10 7.5 1579 1531 1487 1434 1389 1339 1296 1231 1200 1171 1102 972

143 8 x 10 11.0 1733 1680 1632 1573 1524 1470 1422 1351 1317 1285 1209 1066

162 10 x 10 5.5 1961 1901 1846 1780 1725 1663 1609 1528 1490 1454 1368 1206

173 10 x 10 7.5 2092 2028 1970 1900 1840 1775 1717 1631 1590 1551 1460 1287

183 10 x 10 11.0 2224 2156 2094 2019 1956 1886 1825 1733 1690 1649 1552 1368

183 10 x 12 7.5 2224 2156 2094 2019 1956 1886 1825 1733 1690 1649 1552 1368

194 10 x 12 11.0 2355 2283 2218 2139 2072 1998 1933 1836 1790 1746 1644 1449

205 10 x 12 15.0 2487 2411 2342 2258 2188 2109 2041 1938 1890 1844 1736 1530

217 10 x 18 2 x 7.5 2632 2551 2478 2389 2315 2232 2160 2051 2000 1951 1837 1619

228 10 x 18 2 x 11 2763 2679 2602 2509 2431 2344 2268 2154 2100 2049 1928 1700

239 10 x 18 2 x 15 2895 2806 2726 2628 2546 2455 2376 2256 2200 2146 2020 1781

201 12 x 12 11.0 2434 2360 2292 2210 2141 2065 1998 1897 1850 1805 1699 1498

216 12 x 12 15.0 2618 2538 2466 2378 2303 2221 2149 2041 1990 1941 1827 1611

244 12 x 12 18.5 2961 2870 2788 2688 2604 2511 2430 2308 2250 2195 2066 1822

326 12 x 18 2 x 7.5 3947 3827 3717 3584 3472 3348 3240 3077 3000 2927 2755 2429

369 12 x 18 2 x 11 4474 4337 4213 4062 3935 3795 3672 3487 3400 3317 3122 2753

401 12 x 18 2 x 15 4868 4719 4585 4421 4282 4129 3996 3795 3700 3610 3398 2996

Page 9: Evaporative Condensers Induced Draft

9www.fct.net.au

NOTE: Do not use for construction. Refer to your sales representative for certified weights & dimensions. Data subject to change for product improvement.

Evaporative CONDENSORS

Page 10: Evaporative Condensers Induced Draft

10 www.fct.net.au

NOTE: Do not use for construction. Refer to your sales representative for certified weights & dimensions. Data subject to change for product improvement.

Evaporative CONDENSORS Features

a) High Efficiency MEPS 2 Standard IP66 TEFb) Power Band Drive Systemc) Cast Iron or Aluminium Pulleys SPB Minimumd) Heavy Duty Bearings

Evaporative Condensor Induced Draft

1 Motor and Drives

a) High Efficiencyb) Low Noisec) Aluminium/GRP/FRP Constructiond) Anti Corrosive

2 Fan

a) High Pressure PVC Pipeb) ABS Anti Clog Distribution Nozzles

3 Spray System

a) Stainless Steel, Mild Steel or Fibreglass b) Isophthalic Polyesther Based Resins & Gelcoatsc) High Quality Chemical and Corrosion resistantd) High Strength a) UV Resistant Flow Coat

4 Casing

a) High Strength, Lightweight Fibreglassb) Easily Removable

5 Access Door

a) 304 Stainless Steel Minimum

6 Hardware

a) Mild Steelb) Stainless Steel 304Lc) Copper Heavy Duty Thick Wall Pipe Mounted in PTFE Tube Place with Stainless Steel Framed) Pressure tested to 3000 KPA

7 Coil

a) Rigid PVC Anti splash Louvresb) Stainless Steel or PVC frames c) Easy to Maintaind) Easy to Remove and Self Retaining

8 Louvres

Page 11: Evaporative Condensers Induced Draft

11www.fct.net.au

NOTE: Do not use for construction. Refer to your sales representative for certified weights & dimensions. Data subject to change for product improvement.

Evaporative CONDENSORS Features

4

5

8

6

2

3

1

7

Evaporative Condensor Induced Draft

Page 12: Evaporative Condensers Induced Draft

12 www.fct.net.au

NOTE: Do not use for construction. Refer to your sales representative for certified weights & dimensions. Data subject to change for product improvement.

Evaporative CONDENSORS

Engineering Data - Induced Draft - ECCF Model

COPPER COIL STEEL COIL

MODEL BOX SIZE

LENGTH L

WIDTH W

HEIGHT H

FAN DIAMETER

MOTOR SIZE

FULL LOAD CURRENT

AIR FLOW

PUMPMOTOR

SHIPPING WEIGHT

OPERATING WEIGHT

SHIPPING WEIGHT

OPERATING WEIGHT

ECCF MM MM MM MM KW AMPS L /SEC KW KG KG KG KG

010 3 x3 1150 1150 2700 610 0.55 2.2 2095 0.55 372 756 614 1247

012 3 x3 1150 1150 3000 610 1.5 4.3 1982 0.55 420 864 693 1426

015 3 x3 1150 1150 3000 610 2.2 5.3 2224 0.55 468 912 772 1505

017 4 x 4 1450 1450 2700 1000 1.5 4.3 3449 0.75 661 1344 1091 2218

018 4 x 4 1450 1450 2700 1000 2.2 5.3 3727 0.75 747 1536 1232 2534

020 4 x 4 1450 1450 3000 1000 3 7.1 3557 0.75 828 1620 1366 2673

024 4 x 4 1450 1450 3000 1000 4 9.5 3951 0.75 936 1788 1544 2950

027 4 x 6 1450 1850 2750 1000 1.5 4.3 6065 1.1 992 2016 1637 3326

033 4 x 6 1450 1850 2750 1000 2.2 5.3 6447 1.1 1120 2304 1848 3802

038 4 x 6 1450 1850 3050 1000 4 9.5 6853 1.1 1242 2430 2049 4010

043 4 x 6 1450 1850 3050 1000 5.5 13.2 7033 1.1 1500 2820 2475 4653

044 4 x 9 1450 2750 2800 2 x 1000 1.5 4.3 6537 1.1 1020 2412 1683 3980

053 4 x 9 1450 2750 2800 2 x 1000 2.2 5.3 6844 1.1 1164 2520 1921 4158

059 4 x 9 1450 2750 3100 2 x 1000 3 7.1 7377 1.1 1248 2640 2059 4356

064 4 x 9 1450 2750 3100 2 x 1000 4 9.5 7505 1.1 1416 2904 2336 4792

066 4 x 12 1450 3700 2800 2 x 2100 2.2 5.3 6844 1.5 1176 2748 1940 4534

074 4 x 12 1450 3700 2800 2 x 1000 3 7.1 7363 1.5 1272 2976 2099 4910

082 4 x 12 1450 3700 3100 2 x 1000 4 9.5 7930 1.5 1392 3096 2297 5108

088 4 x 12 1450 3700 3100 2 x 1000 5.5 13.2 8269 1.5 1530 3450 2525 5693

028 5 x 5 1800 1800 3150 1220 3 5.3 5805 1.1 1120 2304 1848 3802

035 5 x 5 1800 1800 3450 1220 4 7.1 5212 1.1 1242 2430 2049 4010

041 5 x 5 1800 1800 3450 1220 5.5 13.2 5950 1.1 1500 2820 2475 4653

051 6 x 6 2100 2100 3150 1500 4 9.5 8924 1.5 1164 2520 1921 4158

058 6 x 6 2100 2100 3450 1500 5.5 13.2 8924 1.5 1248 2640 2059 4356

063 6 x 6 2100 2100 3450 1500 7.5 16.7 9815 1.5 1416 2904 2336 4792

070 6 x 8 2100 2700 3150 1500 4 9.5 14101 1.5 1272 2976 2099 4910

080 6 x 8 2100 2700 3450 1500 5.5 13.2 13335 1.5 1392 3096 2297 5108

087 6 x 8 2100 2700 3450 1500 7.5 16.7 13360 1.5 1530 3450 2525 5693

092 8 x 8 2700 2700 3250 2120 5.5 13.2 14479 2.2 1944 5436 3208 8969

102 8 x 8 2700 2700 3550 2120 7.5 16.7 16645 2.2 2136 5628 3524 9286

112 8 x 8 2700 2700 3550 2120 11 24.8 16181 2.2 2328 5988 3841 9880

Page 13: Evaporative Condensers Induced Draft

13www.fct.net.au

NOTE: Do not use for construction. Refer to your sales representative for certified weights & dimensions. Data subject to change for product improvement.

COPPER COIL STEEL COIL

MODEL BOX SIZE

LENGTH L

WIDTH W

HEIGHT H

FAN DIAMETER

MOTOR SIZE

FULL LOAD CURRENT

AIR FLOW

PUMPMOTOR

SHIPPING WEIGHT

OPERATING WEIGHT

SHIPPING WEIGHT

OPERATING WEIGHT

ECCF MM MM MM MM KW AMPS L /SEC KW KG KG KG KG

Evaporative CONDENSORS

Engineering Data - Induced Draft - ECCF Model

115 8 x 10 2700 3300 3250 2120 5.5 13.2 18099 4.0 2004 6036 3307 9959

130 8 x 10 2700 3300 3550 2120 7.5 16.7 20806 4.0 2208 6240 3643 10296

143 8 x 10 2700 3300 3550 2120 11 24.8 20226 4.0 2442 7182 4029 11850

162 10 x 10 3300 3300 3400 2440 5.5 13.2 20296 4.0 2724 7944 4495 13108

173 10 x 10 3300 3300 3700 2440 7.5 16.7 22656 4.0 2952 8172 4871 13484

183 10 x 10 3300 3300 3700 2440 11 24.8 24544 4.0 3228 8976 5326 14810

183 10 x 12 3300 3900 3400 2440 7.5 16.7 31836 5.5 3228 8976 5326 14810

194 10 x 12 3300 3900 3700 2440 11 24.8 33064 5.5 3468 9216 5722 15206

205 10 x 12 3300 3900 3700 2440 15 28.9 36835 5.5 3708 9456 6118 15602

217 10 x 18 3300 5750 3650 2 x 2100 2 x 7.5 16.7 46282 7.5 4842 13464 7989 22216

228 10 x 18 3300 5750 3950 2 x 2100 2 x 11 24.8 45155 7.5 5202 13824 8583 22810

239 10 x 18 3300 5750 3950 2 x 2100 2 x 15 28.9 43947 7.5 5562 14184 9177 23404

201 12 x 12 3900 3900 4100 3048 11 24.8 36117 7.5 3874 10771 6391 17772

216 12 x 12 3900 3900 4400 3048 15 28.9 38350 7.5 4162 11059 6867 18248

244 12 x 12 3900 3900 4400 3048 18.5 35 40856 7.5 4450 11347 7342 18723

326 12 x 18 3900 5750 4400 2 x 2100 2 x 7.5 16.7 54280 7.5 5810 16157 9587 26659

369 12 x 18 3900 5750 4400 2 x 2100 2 x 11 24.8 56640 7.5 6242 16589 10300 27372

401 12 x 18 3900 5750 4400 2 x 2100 2 x 15 28.9 59000 7.5 6674 17021 11013 28084

Page 14: Evaporative Condensers Induced Draft

14 www.fct.net.au

NOTE: Do not use for construction. Refer to your sales representative for certified weights & dimensions. Data subject to change for product improvement.

Evaporative CONDENSORS

Sound Data - Induced Draft - ECCF Model

010 3 x3 0.55 75 74 74 73 68 65 59 53 73 58 56 57 57 53 51 46 39 56 44 42 41 42 37 34 26 21 41

012 3 x3 1.5 79 78 77 76 74 70 64 56 77 62 60 60 60 59 56 51 42 60 48 46 44 45 43 39 31 24 45

015 3 x3 2.2 82 83 82 81 77 74 71 64 81 65 65 65 65 62 60 58 50 64 51 51 49 50 46 43 38 32 49

017 4 x 4 1.5 79 81 80 79 75 71 63 59 79 62 63 63 63 60 57 50 45 62 48 49 47 48 44 40 30 27 47

018 4 x 4 2.2 83 85 84 83 79 75 67 63 83 66 67 67 67 64 61 54 49 66 52 53 51 52 48 44 34 31 51

020 4 x 4 3 86 89 90 88 87 80 77 71 88 69 71 73 72 72 66 64 57 71 55 57 57 57 56 49 44 39 56

024 4 x 4 4 89 91 93 91 90 85 79 74 91 72 73 76 75 75 71 66 60 74 58 59 60 60 59 54 46 42 59

027 4 x 6 1.5 79 81 80 79 75 71 63 59 79 62 63 63 63 60 57 50 45 62 48 49 47 48 44 40 30 27 47

033 4 x 6 2.2 83 85 84 83 79 75 67 63 83 66 67 67 67 64 61 54 49 66 52 53 51 52 48 44 34 31 51

038 4 x 6 4 86 89 90 88 87 80 77 71 88 69 71 73 72 72 66 64 57 71 55 57 57 57 56 49 44 39 56

043 4 x 6 5.5 89 91 93 91 90 85 79 74 91 72 73 76 75 75 71 66 60 74 58 59 60 60 59 54 46 42 59

044 4 x 9 1.5 83 85 84 83 79 75 67 63 83 66 67 67 67 64 61 54 49 66 52 53 51 52 48 44 34 31 51

053 4 x 9 2.2 87 89 91 89 88 83 77 72 89 70 71 74 73 73 69 64 58 72 56 57 58 58 57 52 44 40 57

059 4 x 9 3 90 91 90 88 86 83 79 74 89 73 73 73 72 71 69 66 60 72 59 59 57 57 55 52 46 42 57

064 4 x 9 4 90 91 90 88 86 83 79 74 89 73 73 73 72 71 69 66 60 72 59 59 57 57 55 52 46 42 57

066 4 x 12 2.2 86 89 90 88 87 80 77 71 88 69 71 73 72 72 66 64 57 71 55 57 57 57 56 49 44 39 56

074 4 x 12 3 86 87 85 83 80 74 69 64 84 69 69 68 67 65 60 56 50 68 55 55 52 52 49 43 36 32 53

082 4 x 12 4 89 91 93 91 90 85 79 74 91 72 73 76 75 75 71 66 60 74 58 59 60 60 59 54 46 42 59

088 4 x 12 5.5 92 93 94 92 87 84 81 74 92 75 75 77 76 72 70 68 60 75 61 61 61 61 56 53 48 42 60

028 5 x 5 3 88 89 87 85 82 76 71 66 86 71 71 70 69 67 62 58 52 70 57 57 54 54 51 45 38 34 55

035 5 x 5 4 91 92 90 88 84 81 77 71 89 74 74 73 72 69 67 64 57 72 60 60 57 57 53 50 44 39 57

041 5 x 5 5.5 91 92 90 88 84 81 77 71 89 74 74 73 72 69 67 64 57 72 60 60 57 57 53 50 44 39 57

051 6 x 6 4 86 82 86 83 79 76 70 65 83 69 64 69 67 64 62 57 51 67 55 50 53 52 48 45 37 33 52

058 6 x 6 5.5 86 88 86 84 80 77 72 67 85 69 70 69 68 65 63 59 53 68 55 56 53 53 49 46 39 35 53

063 6 x 6 7.5 83 89 90 87 83 81 76 69 86 66 71 73 71 68 67 63 55 70 52 57 57 56 52 50 43 37 55

070 6 x 8 4 86 88 86 84 80 77 72 67 85 69 70 69 68 65 63 59 53 68 55 56 53 53 49 46 39 35 53

080 6 x 8 5.5 87 89 87 85 81 77 72 68 86 70 71 70 69 66 63 59 54 69 56 57 54 54 50 46 39 36 54

087 6 x 8 7.5 93 95 94 92 90 86 83 78 93 76 77 77 76 75 72 70 64 76 62 63 61 61 59 55 50 46 61

092 8 x 8 5.5 87 90 91 89 84 81 76 70 88 70 72 74 73 69 67 63 56 72 56 58 58 58 53 50 43 38 57

102 8 x 8 7.5 88 91 92 90 85 82 77 71 89 71 73 75 74 70 68 64 57 73 57 59 59 59 54 51 44 39 58

112 8 x 8 11 92 95 96 94 89 86 81 75 93 75 77 79 78 74 72 68 61 77 61 63 63 63 58 55 48 43 62

115 8 x 10 5.5 92 95 96 94 89 86 81 75 93 75 77 79 78 74 72 68 61 77 61 63 63 63 58 55 48 43 62

130 8 x 10 7.5 93 96 97 95 90 87 82 76 94 76 78 80 79 75 73 69 62 78 62 64 64 64 59 56 49 44 63

MODEL BOX SIZE

MOTOR

SIZE

ECCF KW

SOUND POWER LEvELS

dB RE 10¹² WATT

63 125 250 500 1000 2000 4000 8000 DB(A)

SOUND PRESSURE LEvELS FAN AT 1.5M

SPL IN dB RE 0.0002 MICROBAR

63 125 250 500 1000 2000 4000 8000 DB(A)

SOUND PRESSURE LEvELS FAN AT 15M

SPL IN dB RE 0.0002 MICROBAR

63 125 250 500 1000 2000 4000 8000 DB(A)

(Note: + / - 2 dBa. Variable speed drives increase the noise from cooling towers)

Page 15: Evaporative Condensers Induced Draft

15www.fct.net.au

NOTE: Do not use for construction. Refer to your sales representative for certified weights & dimensions. Data subject to change for product improvement.

Evaporative CONDENSORS

Sound Data - Induced Draft - ECCF Model

MODEL BOX SIZE

MOTOR

SIZE

ECCF KW

SOUND POWER LEvELS

dB RE 10¹² WATT

63 125 250 500 1000 2000 4000 8000 DB(A)

SOUND PRESSURE LEvELS FAN AT 1.5M

SPL IN dB RE 0.0002 MICROBAR

63 125 250 500 1000 2000 4000 8000 DB(A)

SOUND PRESSURE LEvELS FAN AT 15M

SPL IN dB RE 0.0002 MICROBAR

63 125 250 500 1000 2000 4000 8000 DB(A)

(Note: + / - 2 dBa. Variable speed drives increase the noise from cooling towers)

143 8 x 10 11 93 96 97 95 90 87 82 76 94 76 78 80 79 75 73 69 62 78 62 64 64 64 59 56 49 44 63

162 10 x 10 5.5 93 94 92 89 85 81 75 77 91 76 76 75 73 70 67 62 63 74 62 62 59 58 54 50 42 45 59

173 10 x 10 7.5 94 95 93 90 86 82 76 78 92 77 77 76 74 71 68 63 64 75 63 63 60 59 55 51 43 46 60

183 10 x 10 11 99 100 98 95 91 87 81 74 97 82 82 81 79 76 73 68 60 80 68 68 65 64 60 56 48 42 65

183 10 x 12 7.5 93 94 92 89 85 81 75 77 91 76 76 75 73 70 67 62 63 74 62 62 59 58 54 50 42 45 59

194 10 x 12 11 94 95 93 90 86 82 76 78 92 77 77 76 74 71 68 63 64 75 63 63 60 59 55 51 43 46 60

205 10 x 12 15 99 100 98 95 91 87 81 74 97 82 82 81 79 76 73 68 60 80 68 68 65 64 60 56 48 42 65

217 10 x 18 2 x 7.5 93 94 92 89 85 81 75 77 91 76 76 75 73 70 67 62 63 74 62 62 59 58 54 50 42 45 59

228 10 x 18 2 x 11 97 98 96 95 91 85 79 73 95 80 80 79 79 76 71 66 59 79 66 66 63 64 60 54 46 41 64

239 10 x 18 2 x 15 99 100 98 95 91 87 81 74 97 82 82 81 79 76 73 68 60 80 68 68 65 64 60 56 48 42 65

201 12 x 12 11 98 100 98 94 91 85 82 77 96 81 82 81 78 76 71 69 63 80 67 68 65 63 60 54 49 45 65

216 12 x 12 15 100 102 100 96 93 87 84 79 98 83 84 83 80 78 73 71 65 82 69 70 67 65 62 56 51 47 67

244 12 x 12 18.5 100 102 100 96 93 87 84 79 98 83 84 83 80 78 73 71 65 82 69 70 67 65 62 56 51 47 67

326 12 x 18 2 x 7.5 100 102 100 96 93 87 84 79 98 83 84 83 80 78 73 71 65 82 69 70 67 65 62 56 51 47 67

369 12 x 18 2 x 11 105 107 105 101 98 92 89 84 103 88 89 88 85 83 78 76 70 87 74 75 72 70 67 61 56 52 72

401 12 x 18 2 x 15 105 107 105 101 98 92 89 84 103 88 89 88 85 83 78 76 70 87 74 75 72 70 67 61 56 52 72

Page 16: Evaporative Condensers Induced Draft

16 www.fct.net.au

NOTE: Do not use for construction. Refer to your sales representative for certified weights & dimensions. Data subject to change for product improvement.

Evaporative CONDENSORS

Page 17: Evaporative Condensers Induced Draft

17www.fct.net.au

NOTE: Do not use for construction. Refer to your sales representative for certified weights & dimensions. Data subject to change for product improvement.

Evaporative CONDENSORS

Page 18: Evaporative Condensers Induced Draft

COMpONENtS

18 www.fct.net.au

COMPONENTS

PVC Fill

Eliminators

Inlet Louvres

Centrifugal Fan Wheel

Fan Housings

Fan Shafts

Fan Bearings

Nozzles

Float Valves

Pultruded Components

Axial Fans

FRP Fan Stacks

FRP Hot Water Basins

Gearbox assemblies including new or rebuilds

Pulleys and Belts

Access ladders & Platforms

Guard Rails

Replacement Coils

Custom Designs

Engineering and Design

Repair and Overhaul of Fans

Balancing Facilities including Static and

Dynamic

Onsite vibration analysis and balancing

Pattern and Mould making Facilities

Manufacture of FRP Components using hand

lay, Press Moulding and Vacuum Moulding

Techniques

Manufacture of Fan Housings and Fan Stacks

High Performance Laminates in e-glass or

Carbon Reinforcements

AUSTRALIAN MADE

Fibreflow Components Include:

Page 19: Evaporative Condensers Induced Draft

19www.fct.net.au

ENGINEERING DESIGN LAYOUT

When considering installation the unit must have suitable fresh air available to ensure correct operation of the system. Care must be taken to ensure moist air does reticulate back into the air inlets and due consideration must be given to ensuring discharge air does not flow into separate fresh air intake for building air-conditioning systems. Consult local regulations for details.

Air Flow

When using or combining multiple cells as a single component cooling source, equalizer lines must be installed to ensure balanced operation. Units must be mounted on the same level on secure plinths.

Multiple Cells

Valves should be installed on all pipe connections and the correct pipe sizes must be used to ensure correct operation. Pipe work and other components to the system should be installed in a manner that ensures the system water does not flow into the cooling tower causing overflow and water loss on shut down.

On start up the water level would drop considerably causing air to be introduced into the system. Preferably such pipe work and components should be located under the level of the basin operating level. Pipe work and ducting cannot be supported from the tower structure.

Pipe Work

If installing cells hard against each other then a de-rating must be applied - generally around 5%. Consult Fibreflow Cooling Towers for confirmation.

De-Rating

When installing in plant rooms and applying ductwork and restricted air supply the external static pressure will increase. Motor size will need to be increased to overcome additional load - consult factory for advice.

Placement

Refer to engineering for layout clearances. Rule of thumb, 1500mm all around minimum.

Layout Clearances

Page 20: Evaporative Condensers Induced Draft

20 www.fct.net.au

ACCESS AND MAINTENANCE

Fibreflow Cooling Towers adhears to local government regulations and Australian Standards.Health and Safety

Fibreflow Cooling Towers offers a full range of working platforms with access ladders, low level and high level, multiple cell platforms and movable working platforms. All platforms conform to the Australian Standard AS1657.

Working Platforms

Standard configurations are available as shown, as well as custom-made to suit a specific location.

Configuration

Material including hot dipped galvanized steel, aluminium, stainless steel and fibreglass.

Materials

Davit cranes mounted on platforms for motor removal are also available as shown.

Crane Mounting

Page 21: Evaporative Condensers Induced Draft

21www.fct.net.au

SOUND LEVELS

The noise that humans can hear covers a frequency from 20Hz to 10,000Hz. There are exceptions, however these levels have become accepted for most practical purposes. This audio band has been divided into eight bands called “octave bands”. The noise of cooling towers is controlled by many contributing factors such as layout, adjacent structures, variable speed drives, etc. Low noise options are available please consult your representative for further assistance.

Noise

The Sickle axial fan series are the answer for generating pressure with low noise axial fans. The sickle blade’s swept design and thin trailing edge reduce pure tones in the sound spectrum and decrease vortex shedding to generate low wake turbulence for a quieter axial fan. The sickle profile’s large chord length and overall surface area also combine to generate greater pressure at slower speeds. The sickle axial fans are Fibreflows natural choice for applications where low noise capabilities are a much required first priority.

Sickle Fan

Reduces noise by up to 7 dB(A)

Maintains performance at lower speeds

Large chord length generates greater pressureSickle Blade

Page 22: Evaporative Condensers Induced Draft

22 www.fct.net.au

LIFTING TECHNIQUES

Lifting Cooling Towers incorrectly can cause the unit to buckle. Please take the following precautions when installing your towers or alternatively, have Fibreflow take care of installation for you.

Lifting

Use soft slings only

Beware of possible crushing of the Tower Casing when Lifting

Use only Tested and Tagged Lifting Gear

Licensed Crane Operators

Always insure there is an exclusion zone whilst lifting is underway

Refer to our factory for further information.

Cooling Tower Being Lifted

Cooling Tower About to be Lifted

Page 23: Evaporative Condensers Induced Draft

23www.fct.net.au

PLINTH ARRANGEMENTS

Plinth arrangements are done based on the size and weight of the cooling tower. Please refer to our factory or your representative for further information.

Page 24: Evaporative Condensers Induced Draft

24 www.fct.net.au

VARIABLE SPEED DRIVES

Cooling towers are used in conjunction with water cooled chillers which are highly efficient. The tower fans cool the water with ambient temperature air. Drives replace two speed motors to regulate the condenser water temperature.

During light loads or cool days, the cooling tower has too high of a capacity. The drive regulates the fans speed to maintain the set point to optimise the energy consumption.

A temperature sensor is placed in the condenser water return line or in the cooling tower basin. A minimum speed of 15% is needed on gear driven fans to maintain proper gear lubrication.

Variable Speed Drive Cooling Tower Fans

No Air Surge/ Water Hammer on Start-up

Redused Noise

Wider Operating Range

Cooling Tower Fans Sensor Placement

Substantial Energy Savings

System Advantages

Fibreflow Cooling Towers recommends the use of VSD’s

on all installations to conserve energy, and reduce wear on

mechanical components.

Page 25: Evaporative Condensers Induced Draft

25www.fct.net.au

FREIGHT

FreightDepending on transport requirements, box sizes up to 3850 x 1450 are generally shipped assembled, unless otherwise specified. 2400 x 2400 units are shipped in two sections for final assembly on site, alternatively these are supplied in complete knock down format (CKD) All other units are shipped in CKD format to reduce transport and handling costs. Fiberflow has a fleet of trucks to deliver your Cooling Tower to any destination around Australia and can also ship to anywhere in the world.

Cooling Tower Components Packed for Shipping

Cooling Tower Components Packed for Shipping

Page 26: Evaporative Condensers Induced Draft

26 www.fct.net.au

SITE ASSEMBLY

Site AssemblyFibreflow Cooling Towers offer a complete onsite assembly service to ensure that the products are assembled in the correct manner. They can be assembled quickly and safely onsite or offsite depending on your needs. Fiberflow can work well with many companies/ contractors to ensure that the assembly is completed smoothly whilst onsite.

It is not compulsory that Fibreflow Cooling Towers or its authorised representatives assemble the units however it is preferred. CKD units can be purchased with assembly instructions for those wishing to assemble themselves.

Cooling Tower Being Assembled

Cooling Tower Being Assembled

Page 27: Evaporative Condensers Induced Draft

27www.fct.net.au

COMPLIANCE WITH THE STANDARDS

Compliance with Standards

Fibreflow Cooling Towers are designed and constructed to meet the following Standards:

Performance Guaranteed

AS4180.1 - Drift Test

AS1170 - Wind Loads

AS1657 - Code for platforms, ladders, stairways and walkways

AS3666 - Air Handling and Water Systems of Buildings – Microbial Control

AS3500 - Australian Plumbing Code

CTI STD 136 - PVC materials for use with fill, louvres and drift eliminators

Fibreflow Cooling Towers guarantee the tHERMal PERfORMancE of our cooling towers

The performance evaluation is taken as per CTI Test Code ATC 105

The thermal performance guaranteed is that submitted in the technical data on whichthe purchase order was based in free field conditions unless otherwise stated

BCA - Building Code of Australia

MEPS - Electric Motor Standard Compliance

Page 28: Evaporative Condensers Induced Draft

28 www.fct.net.au

MODULAR DESIGN

Fibreflow Cooling Towers can be assembled on site.

Modular Design

Hard to get into plantrooms, no issues. Towers are manufactured modular for that exact reason.

No issues with wide load movement

No issues with rain delays or road works

Dedicated professional team of tradesman to assemble on site

Assured quality construction if assembled on site with no transport issues

Over 30 years of on site construction experience

Safety is main priority

No location too remote

Page 29: Evaporative Condensers Induced Draft

29www.fct.net.au

NOTES

Page 30: Evaporative Condensers Induced Draft

HEAD OFFICE

PO BOX 219

6/ 36 Blanck St Ormeau 4208 QLD

Australia

Phone: 1300 784 093Fax: 1300 784 095

Mobile: 0408 013 366Web: www.fct.net.au

Email: [email protected]

SOutH EASt ASIA

AuStRALIA

NEW ZEALAND

AUSTRALIAN MADE

pvC FILL MANuFACtuRING FACILIty

PO BOX 219

2/ 36 Blanck St Ormeau 4208 QLD

Australia

Phone: 1300 784 093Fax: 1300 784 095

Web: www.fct.net.auEmail: [email protected]