Daily Maintenance Record (EWSD) Month : ______ Description 1st 2nd 3rd 4th 5th 6th 7th 8th 9th 10th 11th 12th 13th 14th 15th 16th 17th 18th 19th 20th 21st 22nd 23rd 24th 25th 26th 27th 28th 29th General Core EWSD Are both MDD's active? Is there abnormal rise in CP Load? Are both OMT's active? Enviromental Execute DISPALARM; to enlist the ongoing alarms and faults. Execute DISPINDIC; to enlist the recent ongoing maintenance activities in the switch. Execute DISPLNLCKOUT: LNTYPE=SUB, DN=X; to enlist the Blocked Permanent (BPRM) subscribers. Check the Power supply status i.e. readings on the Rectifiers, Batteries and ensure operational status of Diesel Generator Set. Check the environmental parameters of the Switch Room i.e. Humidity, Temperature and Cleanliness. Is the X.25 Link for Net Manager active? Are the installed Indoor and Outdoor units operational? Is the Switch Room temperature maintained between 18 to 21˚C? Is the Switch Room temperature record maintained on daily basis? Is the Switch room floor cleaned daily? Is the enterance in switch room with shoes strictly prohibited? Is the storage or eating of edible items strictly prohibited in the switch room? Are any insects or small animals seen in the switch room?
Transcript
Page 1: EWSD Maintenance

Daily Maintenance Record (EWSD)Month : ____________

Description 1st 2nd 3rd 4th 5th 6th 7th 8th 9th 10th 11th 12th 13th 14th 15th 16th 17th 18th 19th 20th 21st 22nd 23rd 24th 25th 26th 27th 28th 29th 30th 31st

General

Core EWSDAre both MDD's active?Is there abnormal rise in CP Load?Is the X.25 Link for Net Manager active?Are both OMT's active?Enviromental

Is the Switch room floor cleaned daily?

Execute DISPALARM; to enlist the ongoing alarms and faults.

Execute DISPINDIC; to enlist the recent ongoing maintenance activities in the switch.

Execute DISPLNLCKOUT: LNTYPE=SUB, DN=X; to enlist the Blocked Permanent (BPRM) subscribers.

Check the Power supply status i.e. readings on the Rectifiers, Batteries and ensure operational status of Diesel Generator Set.

Check the environmental parameters of the Switch Room i.e. Humidity, Temperature and Cleanliness.

Are the installed Indoor and Outdoor units operational?

Is the Switch Room temperature maintained between 18 to 21˚C?

Is the Switch Room temperature record maintained on daily basis?

Is the enterance in switch room with shoes strictly prohibited?

Is the storage or eating of edible items strictly prohibited in the switch room?

Are any insects or small animals seen in the switch room?

Page 2: EWSD Maintenance

Weekly Maintenance Record (EWSD)Month : ____________________

Description 1st 2nd 3rd 4th 5th 6th 7th 8th 9th 10th 11th

General

Core EWSDAre the core critical spares available in MSU?

Are the all CCNC units active from both control sides?

Are both CCG's in active state?Are both CCG's in Synchronous mode 4?Is MB active from both control sides?Are both BAP (Basic Processors) active?Are all IOP's (Input/Output Processors) active?

Check the status of Billing Files. If the AMA and IACAMA files filling capacity exceeds 75%, then perform the files saving.

Save all the History Files including HF.ARCHIVE, HF.MSP, HF.MRD,

Routine tests of Core are scheduled for every Monday night. Hence check the OMT log for every Monday night from 12:00 am to 08:00 am. Report if any abnormal messages are displayed.

Check the status of Free F1 Labels. If Free F1 labels are less than 50, then delete unnecessary files.

Execute DISPTRAMORD; to enlist all traffic jobs. Cancel unnecessary jobs.

Execute DISPCFTJOB; to enlist all scheduled jobs. Cancel unnecessary jobs.

Are all TSG's and SSG's Active from both control sides?

Page 3: EWSD Maintenance

Weekly Maintenance Record (EWSD)Month : ____________________

Is the M.O. Drive active?

What is the status of Annoucment Machine?Access EWSDAre all DLU's Active from both control sides?

Does the LTG redundancy exist for all DLU's?

Are the spare MDF fuses maintained?

SoftwareAre the History files saved on regular intervals?Are the Billing Files saved on regular intervals?

Environmental EWSD

Are any lights faulty out of order?

Is only the authorized software installed on the OMT PC?

Are all Subscriber Line modules active from both sides?

Is there any alarm indication on any DLU's control or bus modules?

Are the spares maintained of all DLU Frames and Modules in MSU?

Are the Message Channels of all LTG's active from both sides?

Are there extra,unnecessary or leftover cables on the DDF?

Is the new routing and zoning database created according to predefined ORIG1, ORIG2 and Zone values?

Are there any lose connections in the electrical wiring?

Page 4: EWSD Maintenance

Weekly Maintenance Record (EWSD)Month : ____________________

Are the fire fighting arrangements proper?

Is there any type of water leakage, seepage or cracks in the switch room floor, walls or ceiling?

Page 5: EWSD Maintenance

Weekly Maintenance Record (EWSD)Month : ____________________

12th

General

Core EWSD

Page 6: EWSD Maintenance

Weekly Maintenance Record (EWSD)Month : ____________________

Access EWSD

Software

Environmental EWSD

Page 7: EWSD Maintenance

Weekly Maintenance Record (EWSD)Month : ____________________

Page 8: EWSD Maintenance

Bi-Weekly Maintenance Record (EWSD)Month : _____________

Description 1st 2nd 3rd 4th 5th 6th 7th 8th 9th 10th 11th 12th

General

Save all the Billing Files.

Software

Perform Routine or Quarterly APS Saving procedure, whichever is due.

Keep the M.O. Disks labeled LOGMOD and SAVMOD ready all the time. Report immediately if any M.O. Disk is damaged or files are lost.

Are the APS saving procedures followed properly?

Are the LOGMOD and SAVMOD M.O.Disks administered properly?

Page 9: EWSD Maintenance

Monthly Maintenance Record (EWSD)Year : __________________

Description January February March April May June July August September October November December

GeneralPrepare the M.O. Disk for billing purpose.Core

Are all racks with core subsystems labelled?Are all SN back plane cables labelled?

Access

Are the DLU Racks labelled with the DLU Number?

Are the alarms extended in all DLU's?

Are the thermostats connected to all DLU Frames?

Is the installed base inventory updated for DLU's?

Are the MDF fuses present on all subscriber ports?

Are the thermostats connected to all LTG Frames?

Is the installed base inventory updated for LTG's?

Are the spares maintained for LTG's in MSU?

Is the installed base inventory updated for all EWSD Core subsystems?

Are all SN racks connected with the Earthing plates?

Are all CCNC racks connected with the Earthing plates?

Is the CCG Rack labelled with the DIU numbers for reference frequencies?

Are all DLU racks connected with the Earthing plates?

Are the MDF tag blocks labelled with the Equipment number?

Is the MDF equipment connected with the earthing point?

Are the LTG Racks labelled with the LTG Number and Hardware type?

Are all LTG racks connected with the earthing plate?

Page 10: EWSD Maintenance

Monthly Maintenance Record (EWSD)Year : __________________

Software

Is the ODAGEN due for any software module?

Does the excessive database exist of any type?

Are there any excessive User ID's?

Enviornmental

Is there one AC per rackrow in the switch room?

Are the AC units serviced after regular intervals?

Is the condition of plaster satisfactory?

Are the DDF modules labelled with the Equipment number?

Is the DDF equipment connected with the earthing point?

Is the History files backup M.O.Disk administered properly?

Are the billing files backup kept on MDD's for last 12 months?

Are the billing files backup M.O.Disk administered properly?

Does the testing database cancelled when testing is over?

Are the User ID's adminisitered by the concerned D.E.?

Is the record maintained for the use of Passwords by persons other than authorized?

Are the electrical cables, switches, circuit breakers and fuses properly labelled?

Is the sufficient lights arrangement in the switch room to conduct routine tasks?

Is there a shoe rack present outside the switch room?

Are all doors related to the switch room properly labelled?

Are there any holes in the building which cause the enterance of insects and small animals?

Page 11: EWSD Maintenance

EWSD (Environmetal) Preventive MaintenanceAir Conditioning

S.No Task/Activity Time Schedule Remarks

1 Are the installed Indoor and Outdoor units operational? Daily

2 Is there one AC per rackrow in the switch room? Monthly

3 Are the AC units serviced after regular intervals? Monthly

Temperature

S.No Task/Activity Time Schedule Remarks

1 Is the Switch Room temperature maintained between 18 to 21˚C? Daily

2 Is the Switch Room temperature record maintained on daily basis? Daily

Electrical Works & Lights

S.No Task/Activity Time Schedule Remarks

1 Are the electrical cables, switches, circuit breakers and fuses properly labelled? Monthly

2 Are there any lose connections in the electrical wiring? Weekly

3 Is the sufficient lights arrangement in the switch room to conduct routine tasks? Monthly

4 Are any lights faulty out of order? Weekly

Cleanliness

S.No Task/Activity Time Schedule Remarks

1 Is the Switch room floor cleaned daily? Daily

2 Is there a shoe rack present outside the switch room? Monthly

3 Is the enterance in switch room with shoes strictly prohibited? Daily

4 Is the storage or eating of edible items strictly prohibited in the switch room? Daily

5 Are any insects or small animals seen in the switch room? Daily

Civil Works

S.No Task/Activity Time Schedule Remarks

1 Are all doors related to the switch room properly labelled? Monthly

2 Weekly

3 Is the condition of plaster satisfactory? Monthly

4 Are the fire fighting arrangements proper? Weekly

5 Monthly

Is there any type of water leakage, seepage or cracks in the switch room floor, walls or ceiling?

Are there any holes in the building which cause the enterance of insects and small animals?

Page 12: EWSD Maintenance

EWSD (Software) Preventive Maintenance APS Saving

S.No Task/Activity Time Schedule Remarks

1 Are the APS saving procedures followed properly? Bi-Weekly

2 Are the LOGMOD and SAVMOD M.O.Disks administered properly? Bi-Weekly

History Files

S.No Task/Activity Time Schedule Remarks

1 Are the History files saved on regular intervals? Weekly

2 Is the History files backup M.O.Disk administered properly? Monthly

Billing Files

S.No Task/Activity Time Schedule Remarks

1 Are the Billing Files saved on regular intervals? Weekly

2 Are the billing files backup kept on MDD's for last 12 months? Monthly

3 Are the billing files backup M.O.Disk administered properly? Monthly

Database

S.No Task/Activity Time Schedule Remarks

1 Is the ODAGEN due for any software module? Monthly

2 Does the excessive database exist of any type? Monthly

3 Does the testing database cancelled when testing is over? Monthly

4 Weekly

Password Management

S.No Task/Activity Time Schedule Remarks

1 Are the User ID's adminisitered by the concerned D.E.? Monthly

2 Are there any excessive User ID's? Monthly

3 Monthly

Is the new routing and zoning database created according to predefined ORIG1, ORIG2 and Zone values?

Is the record maintained for the use of Passwords by persons other than authorized?

Page 13: EWSD Maintenance

EWSD Access Preventive Maintenance DLUS.No Task/Activity Time Schedule

1 Are the DLU Racks labelled with the DLU Number? Monthly

2 Are all DLU's Active from both control sides? Weekly

3 Are all Subscriber Line modules active from both sides? Weekly

4 Is there any alarm indication on any DLU's control or bus modules? Weekly

5 Are the alarms extended in all DLU's? Monthly

6 Are the thermostats connected to all DLU Frames? Monthly

7 Does the LTG redundancy exist for all DLU's? Weekly

8 Are all DLU racks connected with the Earthing plates? Monthly

9 Is the installed base inventory updated for DLU's? Monthly

10 Are the spares maintained of all DLU Frames and Modules in MSU? Weekly

MDFS.No Task/Activity Time Schedule

1 Are the MDF tag blocks labelled with the Equipment number? Monthly

2 Is the MDF equipment connected with the earthing point? Monthly

3 Are the MDF fuses present on all subscriber ports? Monthly

4 Are the spare MDF fuses maintained? Weekly

LTGS.No Task/Activity Time Schedule

1 Are the LTG Racks labelled with the LTG Number and Hardware type? Monthly

2 Are the Message Channels of all LTG's active from both sides? Weekly

3 Is there any PCM fault indication on any DIU module? Weekly

4 Are the thermostats connected to all LTG Frames? Monthly

5 Are all LTG racks connected with the earthing plate? Monthly

6 Is the installed base inventory updated for LTG's? Monthly

7 Are the spares maintained for LTG's in MSU? Monthly

DDFS.No Task/Activity Time Schedule

1 Are the DDF modules labelled with the Equipment number? Monthly

2 Are there extra,unnecessary or leftover cables on the DDF? Weekly

3 Is the DDF equipment connected with the earthing point? Monthly

Page 14: EWSD Maintenance

EWSD Access Preventive Maintenance DLU

Remarks

MDFRemarks

LTGRemarks

DDFRemarks

Page 15: EWSD Maintenance

EWSD Core Preventive Maintenance

GeneralS.No Task/Activity Time Schedule Remarks

1 Is the installed base inventory updated for all EWSD Core subsystems? Monthly

2 Are the core critical spares available in MSU? Weekly

3 Are all racks with core subsystems labelled? Monthly

SN

S.No Task/Activity Time Schedule Remarks

1 Are all TSG's and SSG's Active from both control sides? Weekly

2 Are all SN back plane cables labelled? Monthly

3 Are all SN racks connected with the Earthing plates? Monthly

CCNC

S.No Task/Activity Time Schedule Remarks

1 Are the all CCNC units active from both control sides? Weekly

2 Are all CCNC racks connected with the Earthing plates? Monthly

CCG

S.No Task/Activity Time Schedule Remarks

1 Is the CCG Rack labelled with the DIU numbers for reference frequencies? Monthly

2 Are both CCG's in active state? Weekly

3 Are both CCG's in Synchronous mode 4? Weekly

MB

S.No Task/Activity Time Schedule Remarks

1 Is MB active from both control sides? Weekly

CP113 & Peripheries

S.No Task/Activity Time Schedule Remarks

1 Are both BAP (Basic Processors) active? Weekly

2 Are all IOP's (Input/Output Processors) active? Weekly

3 Are both MDD's active? Daily

4 Is the M.O. Drive active? Weekly

5 Is there abnormal rise in CP Load? Daily

6 Is the X.25 Link for Net Manager active? Daily

7 Are both OMT's active? Daily

8 Is only the authorized software installed on the OMT PC? Weekly

9 What is the status of Annoucment Machine? Weekly

Page 16: EWSD Maintenance

ROUTINE CHECKLIST FOR EWSD

S.No Task/Activity Time Schedule

1 Execute DISPALARM; to enlist the ongoing alarms and faults. Daily

2 Daily

3 Daily

4 Daily

5 Daily

6 Weekly

7 Weekly

8 Weekly

9 Weekly

10 Weekly

11 Weekly

12 Save all the Billing Files. Bi-Weekly

13 Bi-Weekly

14 Bi-Weekly

15 Prepare the M.O. Disk for billing purpose. Monthly

Execute DISPINDIC; to enlist the recent ongoing maintenance activities in the switch.

Execute DISPLNLCKOUT: LNTYPE=SUB, DN=X; to enlist the Blocked Permanent (BPRM) subscribers.

Check the Power supply status i.e. readings on the Rectifiers, Batteries and ensure operational status of Diesel Generator Set.

Check the environmental parameters of the Switch Room i.e. Humidity, Temperature and Cleanliness.

Check the status of Billing Files. If the AMA and IACAMA files filling capacity exceeds 75%, then perform the files saving.

Save all the History Files including HF.ARCHIVE, HF.MSP, HF.MRD,

Routine tests of Core are scheduled for every Monday night. Hence check the OMT log for every Monday night from 12:00 am to 08:00 am. Report if any abnormal messages are displayed.

Check the status of Free F1 Labels. If Free F1 labels are less than 50, then delete unnecessary files.

Execute DISPTRAMORD; to enlist all traffic jobs. Cancel unnecessary jobs.

Execute DISPCFTJOB; to enlist all scheduled jobs. Cancel unnecessary jobs.

Perform Routine or Quarterly APS Saving procedure, whichever is due.

Keep the M.O. Disks labeled LOGMOD and SAVMOD ready all the time. Report immediately if any M.O. Disk is damaged or files are lost.

Page 17: EWSD Maintenance

ROUTINE CHECKLIST FOR EWSD

Remarks


Recommended