Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y- connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the armature resistance and synchronous reactance given that the filed excitation voltage is 11935.44 V and leads the terminal voltage by an angle 47.96°.
Transcript
Page 1: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Example 1

A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected

synchronous generator is delivering rated current at rated

voltage and unity PF. Find the armature resistance and

synchronous reactance given that the filed excitation

voltage is 11935.44 V and leads the terminal voltage by an

angle 47.96°.

Page 2: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Example 2

A cylindrical rotor machine is delivering active power of

0.8 p.u. and reactive power of 0.6 p.u. at a terminal

voltage of 1 p.u. If the power angle is 20°, compute the

excitation voltage and the machine’s synchronous

reactance.

Page 3: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Announcement

Quiz I : Next Tuesday (April 5, 2011) at 12:00 in

H11

Assignment I: will be posted today and due

Next Tuesday (April 5, 2011) at 12:00 in H11

Page 4: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Power Transformers

Page 5: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Transformation ratio

Primary (supply) Secondary (Load)

Page 6: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Transformers at no load

The no load current I is needed to supply the no load

losses and to magnetize the transformer core.

Im

Ic E1

I

c

E1

I

I

Ic Im

Page 7: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Transformer losses

The transformer losses are divided into electrical losses

(copper losses) and Magnetic losses (Iron losses).

Copper losses in both the primary and secondary windings.

Magnetic losses, these losses are divided into eddy current

losses and hysteresis losses.

2221

21 RIRI

mhysteriseseddymag IVPPP 1

Page 8: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Loaded Transformer

Z2’ is the load impedancereferred to the primary

Page 9: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Equivalent circuit

V1: Primary voltage (supply)I1 : Primary current.V2: Secondary voltage (load)I2: : Secondary current

Page 10: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Exact Circuit

Page 11: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Approximate Circuit

The no load current ranges from 1% to 3% of the full load current.Therefore, the circuit can be simplified to circuit (b).

(a) (b)

Page 12: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Phasor Diagram

)('2'21 eqeq jXRIVV

Page 13: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Performance Measures

The percent regulation

The transformer efficiency

Page 14: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Voltage Regulation

sincos '2

'2

'21 eqeq XIRIVVVR

Page 15: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Efficiency

The efficiency of the transformer is the ratio of output (secondary)

power to the input (primary) power. Formally the efficiency is η:

1

2

P

P

LPPP 21

Where,

P2 : The output power (Secondary) = V2I2 cos2

P1 : The input power (Primary) = V1I1 cos1

Where,

PL is the power loss in the transformer = Pcopper + Piron

ironeq PRIIV

IV

2'22

'2

'2

2'2

'2

cos

cos

Page 16: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Example

A 100-kVA, 400/2000 V, single-phase transformer has the following parameters

R1 = 0.01 R2 = 0.25 ohms

X1 = 0.03 ohms X2 = 0.75 ohms

The transformer supplies a load of 90 kVA at 2000 V and 0.8 PF lagging.

Calculate the primary voltage and current using the simplest equivalent circuit.

Find also the V.R. and efficiency for the transformer

Page 17: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Solution

Page 18: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Voltage Regulation

sincos '2

'2

'21 eqeq XIRIVVVR

%84.296.411

7.11%

7.11

6.006.02258.002.0225

VR

VVR

VR

Page 19: Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.

Efficiency