+ All Categories
Home > Documents > Explosion Protection Postertktrade.co.kr/download/ex-poster-p-en-rstahl.pdf · 2020. 1. 30. · ISO...

Explosion Protection Postertktrade.co.kr/download/ex-poster-p-en-rstahl.pdf · 2020. 1. 30. · ISO...

Date post: 21-Mar-2021
Category:
Upload: others
View: 9 times
Download: 1 times
Share this document with a friend
1
Types of protection for electrical equipment in explosive atmospheres Type of protection Symbol Zone Diagram Main application Standard general requirements IEC 60079-0 EN 60079-0 UL 60079-0 increased safety e, eb ec 1 2 terminal and junction boxes, control stations for installing Ex components (with a different type of protection), squirrel-cage motors, light fittings IEC 60079-7 EN 60079-7 UL 60079-7 flameproof enclosures da d, db dc 0 1 2 switchgears, control stations, indicating equipment, control systems, motors, transformers, heating equipment, light fittings IEC 60079-1 EN 60079-1 UL 60079-1 pressurized enclosure px, pxb py, pyb pz, pzc 1 21 1 21 2 22 switchgear and control cabinets, analysers, large motors old identification for dust pD21, pD22 IEC 60079-2 EN 60079-2 UL 60079-2 intrinsic safety ia ib ic 0 20 1 21 2 22 instrumentation technology, fieldbus technology, sensors, actuators [Ex ib] = associated electrical apparatus – installation in the safe area old identification for dust: iaD = for use in Zone 20, 21, 22 ibD = for use in Zone 21, 22 IEC 60079-11 EN 60079-11 UL 60079-11 intrinsically safe systems IEC 60079-25 EN 60079-25 UL 60079-25 liquid immersion o, ob oc 1 2 transformers, starting resistors IEC 60079-6 EN 60079-6 UL 60079-6 powder filling q, qb 1 sensors, display units, electronic ballasts, transmitters IEC 60079-5 EN 60079-5 UL 60079-5 encapsulation ma mb mc 0 20 1 21 2 22 switchgear with small capacity, control and signalling units, display units, sensors old identification for dust: maD = for use in Zone 20, 21, 22 mbD = for use in Zone 21, 22 IEC 60079-18 EN 60079-18 UL 60079-18 type of protection “n” nA, nAc nC, nCc nR, nRc 2 2 2 all electrical equipment for Zone 2 nA = non-sparking devices nC = sparking devices and components nR = restricted breathing enclosures IEC 60079-15 EN 60079-15 UL 60079-15 optical radiation op _ op _ op _ 0 20 1 21 2 22 op is = inherently safe optical radiation op pr = protected optical radiation op sh = optical radiation interlock IEC 60079-28 EN 60079-28 protection by enclosure ta tb tc 20 21 22 switchgear, control stations, junction boxes, control boxes, motors, light fittings old identification: tD A21 = under procedure A for Zone 21 tD B21 = under procedure B for Zone 21 IEC 60079-31 EN 60079-31 UL 60079-31 IEC 61241-1 EN 61241-1 ISA 61241-1 Equipment category and equipment protection level (EPL) According to EU directive 2014/34/EU (ATEX) According to IEC and CENELEC Group Equipment category EPL Suffi cient safety Mines susceptible to firedamp I M1 Ma during rare malfunctions I M2 Mb until de-energizing of the equipment Explosive gas atmosphere II 1G Ga Zone 0 during rare malfunctions II 2G Gb Zone 1 during expected malfunctions II 3G Gc Zone 2 in normal operation Explosive dust atmosphere II 1D Da Zone 20 during rare malfunctions II 2D Db Zone 21 during expected malfunctions II 3D Dc Zone 22 in normal operation (1)G associated apparatus – installation in non-hazardous area Zones Dangerous explosive atmosphere Continuously, long- term or frequently Occasionally Not likely to occur and for short period only Gas CENELEC/IEC/NEC 505 Zone 0 Zone 1 Zone 2 NEC 500 (Class I) Division 1 Division 2 Dust CENELEC/IEC/NEC 506 Zone 20 Zone 21 Zone 22 NEC 500 (Class II, III) Division 1 Division 2 Groups IEC/CENELEC/NEC 505/NEC 506 NEC 500 Group I Mines susceptible to firedamp –– methane Group II Explosive gas atmosphere Class I Subdivisions Typical gas Subdivisions IIA propane propane Class I, Group D IIB ethylene ethylene Class I, Group C IIC hydrogen hydrogen Class I, Group B acetylene acetylene Class I, Group A Group III Explosive dust atmosphere Class II, Class III Subdivisions Typical dust Subdivisions IIIA combustible flyings fibres/flyings Class III IIIB non-conductive dust non-conductive dust Class II, Group G IIIC conductive dust carbonaceous dust Class II, Group F combustible metal dust Class II, Group E Types of protection for non-electrical equipment in explosive atmospheres Type of protection Diagram Main application Standard basic methods and requirements ISO 80079-36 EN ISO 80079-36 constructional safety “c” h couplings, pumps, gear drives, chain drives, belt drives old marking according to EN 13463-5: c ISO 80079-37 EN ISO 80079-37 control of ignition sources “b” h pumps, belt drives old marking according to EN 13463-6: b ISO 80079-37 EN ISO 80079-37 liquid immersion “k” h submerged pumps, gears old marking according to EN 13463-8: k ISO 80079-37 EN ISO 80079-37 flameproof enclosures “d” h brakes, couplings old marking according to EN 13463-3: d IEC 60079-1 EN 60079-1 protection by enclosure “t” h equipment for explosive dust atmospheres IEC 60079-31 EN 60079-31 pressurized enclosure “p” h pumps IEC 60079-2 EN 60079-2 Temperature classification Maximum surface temperature Gas temperature classes Maximum surface temperature Gas temperature classes Equipment marking Equipment marking NEC 500 CENELEC/ IEC/NEC 505 NEC 500 CENELEC/ IEC/NEC 505 450°C T1 T1 200°C T3 T3 300°C T2 T2 180°C T3A 280°C T2A 165°C T3B 260°C T2B 160°C T3C 230°C T2C 135°C T4 T4 215 °C T2D 120°C T4A Dust: indication of the max. surface temperature in °C. 100°C T5 T5 85°C T6 T6 ID 103061 | 2016-11 / EN | Printed in Germany LIGHTING AND SIGNALLING INSTALLATION AND CONTROLS AUTOMATION OPERATING AND MONITORING SYSTEM AND INTEGRATED SOLUTIONS Explosion protection by R. STAHL is always state of the art – and guarantees the safety of people, machines and the environment in hazardous areas all over the world. SEMINARS MARINE OFFSHORE R. STAHL, Am Bahnhof 30, 74638 Waldenburg, Germany, T +49 7942 943-0, F +49 7942 943-4333, r-stahl.com SAFETY. EVERYWHERE. ATEX IECEx NEC 505 Electrical equipment II (1) 2 G Ex db [ia Ga] IIC T4 Gb Ex db [ia Ga] IIC T4 Gb Class I, Zone 1 AEx db [ia Ga] IIC T4 Gb IECEx (dust) Ex tb IIIC T90°C Db NEC 506 Zone 21 AEx tb IIIC T90°C Db NEC 500 Class I, Division 1 Group C,D T4 ATEX IECEx EN 13463-1 Non-electrical equipment II 2 G Ex h IIC T6 Gb Ex h IIC T6 Gb II 2 G c k IIC T6 ATEX: Explosion protection for Europe IECEx: International explosion protection NEC: Explosion protection for USA Ex labelling also available as an app:
Transcript
Page 1: Explosion Protection Postertktrade.co.kr/download/ex-poster-p-en-rstahl.pdf · 2020. 1. 30. · ISO 80079-37 EN ISO 80079-37 liquid immersion “k” h submerged pumps, gears old

Types of protection for electrical equipment in explosive atmospheres

Type ofprotection

Symbol Zone Diagram Main application Standard

generalrequirements

IEC 60079-0EN 60079-0UL 60079-0

increasedsafety

e, ebec

12

terminal and junction boxes, control stationsfor installing Ex components (with a differenttype of protection), squirrel-cage motors,light fittings

IEC 60079-7EN 60079-7 UL 60079-7

flameproofenclosures

dad, dbdc

012

switchgears, control stations, indicatingequipment, control systems, motors,transformers, heating equipment, light fittings

IEC 60079-1 EN 60079-1UL 60079-1

pressurizedenclosure

px, pxbpy, pybpz, pzc

1 211 212 22

switchgear and control cabinets, analysers,large motorsold identification for dust pD21, pD22

IEC 60079-2 EN 60079-2UL 60079-2

intrinsic safety iaibic

0 201 212 22

instrumentation technology,fieldbus technology, sensors, actuators[Ex ib] = associated electrical apparatus –installation in the safe areaold identification for dust:iaD = for use in Zone 20, 21, 22ibD = for use in Zone 21, 22

IEC 60079-11 EN 60079-11UL 60079-11

intrinsically safe systems IEC 60079-25 EN 60079-25UL 60079-25

liquid immersion o, oboc

12

transformers, starting resistors IEC 60079-6 EN 60079-6UL 60079-6

powder filling q, qb 1 sensors, display units, electronic ballasts,transmitters

IEC 60079-5 EN 60079-5UL 60079-5

encapsulation mambmc

0 201 212 22

switchgear with small capacity, control andsignalling units, display units, sensorsold identification for dust:maD = for use in Zone 20, 21, 22mbD = for use in Zone 21, 22

IEC 60079-18 EN 60079-18UL 60079-18

type ofprotection “n”

nA, nAcnC, nCcnR, nRc

222

all electrical equipment for Zone 2

nA = non-sparking devicesnC = sparking devices and componentsnR = restricted breathing enclosures

IEC 60079-15 EN 60079-15UL 60079-15

opticalradiation

op _ op _ op _

0 201 212 22

op is = inherently safe optical radiationop pr = protected optical radiationop sh = optical radiation interlock

IEC 60079-28 EN 60079-28

protection byenclosure

tatbtc

202122

switchgear, control stations, junction boxes,control boxes, motors, light fittings

old identification:tD A21 = under procedure A for Zone 21tD B21 = under procedure B for Zone 21

IEC 60079-31 EN 60079-31UL 60079-31IEC 61241-1 EN 61241-1ISA 61241-1

Equipment category and equipment protection level (EPL)

According to EU directive2014/34/EU (ATEX)

According toIEC and CENELEC

Group Equipment category EPL Suffi cient safety

Mines susceptible to firedamp

I M1 Ma during rare malfunctions

I M2 Mb until de-energizing of the equipment

Explosive gas atmosphere

II 1G Ga Zone 0 during rare malfunctions

II 2G Gb Zone 1 during expected malfunctions

II 3G Gc Zone 2 in normal operation

Explosive dust atmosphere

II 1D Da Zone 20 during rare malfunctions

II 2D Db Zone 21 during expected malfunctions

II 3D Dc Zone 22 in normal operation

(1)G associated apparatus – installation in non-hazardous area

Zones

Dangerousexplosive atmosphere

Continuously, long- term or frequently

Occasionally Not likely to occur andfor short period only

GasCENELEC/IEC/NEC 505 Zone 0 Zone 1 Zone 2

NEC 500 (Class I) Division 1 Division 2

DustCENELEC/IEC/NEC 506 Zone 20 Zone 21 Zone 22

NEC 500 (Class II, III) Division 1 Division 2

Groups

IEC/CENELEC/NEC 505/NEC 506 NEC 500

Group I Mines susceptible to firedamp ––

methane

Group II Explosive gas atmosphere Class I

Subdivisions Typical gas Subdivisions

IIA propane propane Class I, Group D

IIB ethylene ethylene Class I, Group C

IIC hydrogen hydrogen Class I, Group B

acetylene acetylene Class I, Group A

Group III Explosive dust atmosphere Class II, Class III

Subdivisions Typical dust Subdivisions

IIIA combustible flyings fibres/flyings Class III

IIIB non-conductive dust non-conductive dust Class II, Group G

IIIC conductive dust carbonaceous dust Class II, Group F

combustible metal dust Class II, Group E

Types of protection for non-electrical equipment in explosive atmospheres

Type of protection Diagram Main application Standard

basic methodsand requirements

ISO 80079-36EN ISO 80079-36

constructionalsafety “c”

h couplings, pumps, gear drives, chain drives,belt drives

old marking according to EN 13463-5: c

ISO 80079-37EN ISO 80079-37

control ofignition sources“b”

h pumps, belt drives

old marking according to EN 13463-6: b

ISO 80079-37EN ISO 80079-37

liquidimmersion “k”

h submerged pumps, gears

old marking according to EN 13463-8: k

ISO 80079-37EN ISO 80079-37

flameproofenclosures “d”

h

brakes, couplings

old marking according to EN 13463-3: d

IEC 60079-1EN 60079-1

protection byenclosure “t”

h

equipment for explosive dust atmospheres IEC 60079-31EN 60079-31

pressurizedenclosure “p”

h pumps IEC 60079-2EN 60079-2

Temperature classification

Maximumsurfacetemperature

Gas temperature classesMaximumsurfacetemperature

Gas temperature classes

Equipment marking Equipment marking

NEC 500 CENELEC/IEC/NEC 505

NEC 500 CENELEC/IEC/NEC 505

450°C T1 T1 200°C T3 T3

300°C T2 T2 180°C T3 A

280°C T2A 165°C T3B

260°C T2B 160°C T3C

230°C T2C 135°C T4 T4

215°C T2D 120°C T4A

Dust: indication of the max. surfacetemperature in °C.

100°C T5 T5

85°C T6 T6

ID 1

0306

1 |

20

16-1

1 / E

N

| P

rinte

d in

Ger

man

y

LIGHTINGAND

SIGNALLING

INSTALLATIONAND

CONTROLS

AUTOMATION

OPERATINGAND

MONITORING

SYSTEM ANDINTEGRATEDSOLUTIONS

Explosion protection by R. STAHLis always state of the art – andguarantees the safety of people,machines and the environmentin hazardous areas all over theworld.

SEMINARS

MARINEOFFSHORE

R. STAHL, Am Bahnhof 30, 74638 Waldenburg, Germany, T +49 7942 943-0, F +49 7942 943-4333, r-stahl.com

SAFETY. EVERYWHERE. ATEX IECExNEC 505

Electrical equipment

II (1)2 G Ex db [ia Ga] IIC T4 Gb

Ex db [ia Ga] IIC T4 GbClass I, Zone 1 AEx db [ia Ga] IIC T4 Gb

IECEx (dust) Ex tb IIIC T90°C Db

NEC 506 Zone 21 AEx tb IIIC T90°C Db

NEC 500 Class I, Division 1 Group C,D T4

ATEX IECEx EN 13463-1

Non-electrical equipment

II 2 G Ex h IIC T6 Gb Ex h IIC T6 GbII 2 G c k IIC T6

ATEX: Explosion protection for Europe IECEx: International explosion protectionNEC: Explosion protection for USA

Ex labelling alsoavailable as an app:

Recommended