+ All Categories
Home > Documents > Exterior Renovation, The Webster School Pond Project No. · 2011. 8. 12. · Exterior Renovation,...

Exterior Renovation, The Webster School Pond Project No. · 2011. 8. 12. · Exterior Renovation,...

Date post: 29-Jan-2021
Category:
Upload: others
View: 2 times
Download: 0 times
Share this document with a friend
32
Addendum No. 1, Page 1 Exterior Renovation Pond Project No. The Webster School 1110218 St. Johns County School District April 15, 2011 SJCSD Project No. 2011-27 Addendum No. 1 Make the following changes and or clarifications to the contract documents. Drawings Drwg. Description of Change No. G-002 GENERAL NOTE 16. Where St. Johns School Building Department is referenced, change to “St. Johns County School District.” At the last note; Delete reference to “Phasing.” No phasing is included in this project. G-021 Life Safety Plan; At Vestibule Space 669, add Travel Distances of 25’ from the north pair of doors to the exit and 45’ from the south pair of doors to the exit. Delete the arrow and 65’ located above Vestibule Space 669. L-101 Landscape Plan; Add the following note: ‘Irrigation system exists in the landcaped area between the existing building and the existing sidewalk where landscaping is shown to be demolished and replaced on sheet AD-101. Contractor shall repair and or replace existing sprinkler system to provide 100% coverage of the newly landscaped areas indicated.’ L-101 New Concrete Pavers indicated shall be as manufactured by Tremron, Inc. Park Plaza Series, 24” square or 16” square, 2 3/8” thick, South Beach Blend color, or equal. AD-101 Demolition Plan Area A, Note 1; Add the following to Note 1: ‘Irrigation system exists in the landcaped area between the existing building and the existing sidewalk where landscaping is shown to be demolished and replaced. Contractor shall repair and or replace existing sprinkler system to provide 100% coverage of the newly landscaped areas indicated on sheet L-101.’ AD-101 Add the following to the Demolition Plan General Notes: ‘Contractor shall provide for the security and weathertightness of the building on a nightly basis. Door and window openings shall not be left open to the weather. Where doors and windows are removed from openings, openings shall have temporary plywood coverings secured in place. Contractor shall provide dust barrier to separate the new construction area and alteration areas from the existing building spaces as required. Coordinate locations with SJCSD Project Manager.’ AD-101 Demolition Key Notes, Note 13; Add the following note to the end of the note “Existing Koi fish shall be removed and maintained during construction, or they shall be replaced at the conclusion of construction with similar items.”
Transcript
  • Addendum No. 1, Page 1

    Exterior Renovation Pond Project No. The Webster School 1110218 St. Johns County School District April 15, 2011 SJCSD Project No. 2011-27 Addendum No. 1 Make the following changes and or clarifications to the contract documents. Drawings Drwg. Description of Change No.

    G-002 GENERAL NOTE 16. Where St. Johns School Building Department is referenced, change to “St. Johns County School District.” At the last note; Delete reference to “Phasing.” No phasing is included in this project.

    G-021 Life Safety Plan; At Vestibule Space 669, add Travel Distances of 25’ from the north pair of doors to the exit and 45’ from the south pair of doors to the exit. Delete the arrow and 65’ located above Vestibule Space 669.

    L-101 Landscape Plan; Add the following note: ‘Irrigation system exists in the landcaped area between the existing building and the existing sidewalk where landscaping is shown to be demolished and replaced on sheet AD-101. Contractor shall repair and or replace existing sprinkler system to provide 100% coverage of the newly landscaped areas indicated.’

    L-101 New Concrete Pavers indicated shall be as manufactured by Tremron, Inc. Park Plaza Series, 24” square or 16” square, 2 3/8” thick, South Beach Blend color, or equal.

    AD-101 Demolition Plan Area A, Note 1; Add the following to Note 1: ‘Irrigation system exists in the landcaped area between the existing building and the existing sidewalk where landscaping is shown to be demolished and replaced. Contractor shall repair and or replace existing sprinkler system to provide 100% coverage of the newly landscaped areas indicated on sheet L-101.’

    AD-101 Add the following to the Demolition Plan General Notes: ‘Contractor shall provide for the security and weathertightness of the building on a nightly basis. Door and window openings shall not be left open to the weather. Where doors and windows are removed from openings, openings shall have temporary plywood coverings secured in place. Contractor shall provide dust barrier to separate the new construction area and alteration areas from the existing building spaces as required. Coordinate locations with SJCSD Project Manager.’

    AD-101 Demolition Key Notes, Note 13; Add the following note to the end of the note “Existing Koi fish shall be removed and maintained during construction, or they shall be replaced at the conclusion of construction with similar items.”

  • Exterior Renovation, The Webster School Pond Project No. St. Johns County School District 1110218

    Addendum No. 1, Page 2

    A-102 Sheet A-102, Roof Drainage and Storm Sewer Plan is added to the set and is attached to this addendum. As indicated on sheet A-102 the new pre-engineered canopy column drains shall be tied into a below grade storm pipe.

    A-151 Roof Plan General Notes; Add the following as Note B “The existing roofs north and south of the new Lobby space are planned to be reroofed during the same time frame as this project. Contractor shall coordinate the construction and roof tie-in work indicated with the Contractor responsible for the reroofing project.

    A-201 Delete the repainting of the entire school with the exception of the painting and new finishes indicated on the attached sketch. The main West Elevation facing Orange Street will still be completely repainted and/or new concrete masonry unit and stucco construction as indicated on Exterior Elevation sheet A-201 and the General Notes and Photographs 1–4 on sheet A-211. The main South Elevation facing Chapin Street will also still be completely repainted as indicated. See General Notes and Photograph 9, sheet A-212. The remainder of the existing buildings will be left as-is and do not require painting. See attached sketch A201-1 for plan showing the extent of the exterior painting required.

    A-211 Delete Photographs 5–9. Repainting of these building facades is deleted from the scope of work. See item above for sheet A-201.

    A-212 Delete Photographs 1–8. Repainting of these building facades is deleted from the scope of work. Photograph 9 is still applicable. See item above for sheet A-201.

    A-351 Section 2; Waterproof the backside of all new masonry parapet walls with self-adhering modified bitumen flashing membrane installed per roofing manufacturers recommendations. Membrane shall begin at the flashing reglet and extend up and over the top of the masonry parapet. The two-piece metal flashing and reglet will remain as indicated.

    A-352 Sections 1 & 2; Waterproof the backside of all new masonry parapet walls with self-adhering modified bitumen flashing membrane installed per roofing manufacturers recommendations. Membrane shall begin at the flashing reglet and extend up and over the top of the masonry parapet. The two-piece metal flashing and reglet will remain as indicated.

    A-352 Section 1; At new pre-engineered aluminum canopy, change note from ‘Column drains to grade’ to ‘Connect column drain to new storm sewer piping with 3” dia. pvc below grade. Coordinate concrete footing blockout requirements with canopy manufacturer.’ See sheet A-102 added as part of this addendum.

    A-352 Section 2; All new gypsum wallboard indicated at the new returns surrounding the windows (door opening similar) shall be painted to match the existing space.

    A-352 Sections 1 & 2; At the junction of the existing roof and the new parapet wall, delete the ‘Expando-Flash’ bellows assembly noted. The junction shall be flashed with Modified bitumen flashing assembly and extended up and under

  • Exterior Renovation, The Webster School Pond Project No. St. Johns County School District 1110218

    Addendum No. 1, Page 3

    the two-piece counterflashing shown. Change the reference tag from 4/A-501 to 2/A-501.

    A-353 Section 1; Waterproof the backside of all new masonry parapet walls with self-adhering modified bitumen flashing membrane installed per roofing manufacturers recommendations. Membrane shall begin at the flashing reglet and extend up and over the top of the masonry parapet. The two-piece metal flashing and reglet will remain as indicated.

    A-353 Section 1; All new gypsum wallboard indicated at the new returns surrounding the windows (door opening similar) shall be painted to match the existing space. The new gypsum wallboard returns occur at each opening along the west wall where new masonry walls are indicated.

    A-353 Section 1; At the junction of the existing roof and the new parapet wall, delete the ‘Expando-Flash’ bellows assembly noted. The junction shall be flashed with Modified bitumen flashing assembly and extended up and under the two-piece counterflashing shown. Change the reference tag from 4/A-501 to 2/A-501.

    A-501 Delete Detail 4/A-501 in its entirety. Any references to this detail shall be changed to reference detail 2/A-501.

    A-611 Change Door Number 675 from 3’-10 width to 3’-6 width. Change Door Number 637 from a Pair of 3’-2 width to a Pair of 3’-0 width. At Door Number 670, the sidelight mullion shall be the manufacturer’s standard double rabbet hollow metal mullion of frame depth indicated at other details. Sidelight shall be glazed with Laminated Ceramic Glazing, GL-4.

    A-611 New Aluminum Louvers noted shall have Florida Product Approval.

    A-612 Detail 9; Threshold shall meet Accessibility requirements.

    A-614 Detail 4; Threshold shall meet Accessibility requirements. Provide sealant joint between slabs at expansion joint material.

    S-001 4. CONCRETE, Note 3; add to the end of the sentence “as referenced by the Florida Building Code.”

    Add the following as Note 15; “15. Post installed anchors and rebar require inspection prior to installation.”

    6. REINFORCED MASONRY, Note 1; add to the end of the sentence “as referenced by the Florida Building Code.”

    Add the following as Note 18; “18. Post installed anchors and rebar require inspection prior to installation.”

    S-XXX Structural sheets are being reissued and are attached as part of this addendum. Delete the Structural sheets and substitute the attached revised Structural sheets as follows:

    S-101, S-102, S-201, S-202, S-301, S-302, & S-303.

    The attached sheets are intended to improve the graphic quality, but also include clarifications and minor revisions which have been clouded.

  • Exterior Renovation, The Webster School Pond Project No. St. Johns County School District 1110218

    Addendum No. 1, Page 4

    M100 HVAC Schedule, Notes, and Legend; Exhaust Fan Schedule: Add note 2: “2. Unit shall be tied into school’s existing Building Management System.”

    M201 Partial Floor Plan HVAC – Demo Plan; Modify note for condensing unit relocation to read: “Existing condensing unit to be removed and relocated. Completely remove refrigerant piping from existing air handling unit to existing condensing unit. Cap the connections at the equipment for future reconnection. Refer to sheet M301 for new location (typ. of 7).”

    M301 Partial Floor Plan HVAC; Modify note for condensing unit relocation to read: “RELOCATED CONDENSING UNIT LOCATION (TYP OF 7). PROVIDE NEW REFRIGERANT PIPING FROM EXISTING AIR HANDLING UNIT TO EXISTING CONDENSING UNIT’S NEW LOCATION.”

    Add the following sequence of operation: “SEQUENCE OF OPERATION RTU-1: During scheduled occupancy and after verification of safeties, unit shall be energized by a call for heating or cooling from the space temperature sensor. The heat pump unit’s internal controls shall control the temperature of the air supplied to the space as well as the position of the reversing valve and when the unit is in defrost. RTU-1’s fan shall run continuously during scheduled occupancy and shall cycle during unoccupied hours to maintain set points. The occupied space design temperature is 75°F, adjustable, during summer, and 72°F, adjustable, during winter. The unoccupied space design temperature is 82°F, adjustable, during summer, and 60°F, adjustable, during winter. During morning warm-up/cool-down and unoccupied times, RTU-1’s motorized outdoor intake damper shall be de-energized and modulate closed. During occupied times, RTU-1’s motorized outdoor intake damper shall be energized and modulate open until the set points are reached. EF-1: During scheduled occupancy and after verification of safeties, unit shall be energized and controlled via wall switch. During morning warm-up/cool-down and unoccupied times, EF-1 shall be de-energized.”

    P100 Plumbing Legend, Notes, and Details; General Notes: Delete note 7 in its entirety.

    FP100 Partial Floor Plan Fire Protection; Delete Flow Test Schedule

    E100 Demolition Notes: Delete Note 10 in its entirety.

    Fire Alarm Riser Diagram; Change Note 3 to read as follows: ‘Fire Alarm Shop Drawings- Submit 3 sets, signed and sealed, to the Architect for approval. Shop drawings will then be forwarded to SJCSD Building Code Administrator, Attn. David Lee, for final approval.’

    Typical Lay-In Fixture. Delete note “Securely fasten fixture to grid with 1 screw at each corner, (four screws per fixture).”

    E301 Partial Floor Plan – Lighting; Provide lighting switch by the double doors to corridor 667. See lighting control diagram sheet E-100.

    E401 Panel Schedules; At the end of note 2 add the following: “Exterior lighting shall be controlled by Building Energy Management System. Provide

  • Exterior Renovation, The Webster School Pond Project No. St. Johns County School District 1110218

    Addendum No. 1, Page 5

    relay, control wires, conduit, and all needed accessories to control exterior lighting.”

    Project Manual Spec. Description of Change Section TOC Project Table of Contents

    Add the following sections to the Project Table of Contents: Section 06 41 16 Plastic-Laminate-Faced Architectural Cabinets Section 12 36 61 Solid Surface Countertops Section 33 41 00 Storm Utility Drainage Piping A Revised Table of Contents and the three added sections accompanies this Addendum.

    GC General Conditions, page 85, Paragraph 9.8.1, It shall be noted that all warranties required by the Contract Documents shall commence on the date of Final Completion of the Work, and not on the date of Substantial Completion.

    01110 Summary of Work, Article 1.02 Work Under a Single Contract, delete paragraph B and substitute the following:

    B. Base Bid - General Construction Contract: Includes demolition of portions of the existing building and landscaping, minor amounts of new sitework, landscaping, and irrigation, reconstruction of a new Lobby space including general trade work in concrete, masonry, steel, roofing, aluminum curtainwall, storefront, and entrances, hollow metal doors and frames, interior and exterior finishes, pre-engineered aluminum canopies, mechanical, fire protection, and electrical items specified in Divisions 1 through 33 of the Specifications and Work shown on the Drawings.

    01110 SUMMARY; Add the following to the end of the section as Articles 1.12 and 1.13.

    1.12 PRECONSTRUCTION VIDEO

    A. The Contractor shall make a video of the pertinent areas of the existing site and existing building in order to document the conditions of all existing construction including, but not limited to, pavements, sidewalks, turf and landscaped areas, buildings, site utilities, lighting, mechanical equipment, furniture, items indicated to be salvaged and returned to Owner, interior finishes, etc. The express purpose of the preconstruction video is to document the condition of all items, especially if existing elements have been previously damaged, in an effort to eliminate any disputes between Owner and Contractor as regards to items that may become damaged from construction activities during the course of construction.

  • Exterior Renovation, The Webster School Pond Project No. St. Johns County School District 1110218

    Addendum No. 1, Page 6

    1.13 STORM PIPING VIDEO

    A. All new storm piping shall be video recorded to comply with St. Johns County School District standards.

    01550 Article 3.03, Paragraph E Temporary Project Identification Signs: Delete this paragraph and its subparagraphs in their entirety. No Project Identification Sign is required for this project.

    08 41 13 Article 1.10 Warranty; Paragraphs A.2. & B.1. Revise Warranty periods to be from date of Final Completion as specified in General Conditions paragraph 9.8.1.

    08 44 13 Article 1.9 Warranty; Paragraphs A.2. & B.2. Revise Warranty periods to be from date of Final Completion as specified in General Conditions paragraph 9.8.1.

    08 71 00 Article 2.15 Fabrication; Paragraph A.1. Concealed Fasteners: Delete the second sentence beginning with “Do not use through bolts….. and substitute the following; “Use through bolts (sexbolts) for door hardware units that are exposed such as closers, hold-open devices, etc.”

    10 73 00 Protective Covers; A substitution request was received for the use of products manufactured by Architectural Metal Systems, Inc. for the materials specified in this section. This substitution request is approved and Architectural Metal Systems, Inc. is approved as a manufacturer for use on this project subject to compliance with the specifications.

    10 73 00 Protective Covers; A substitution request was received for the use of products manufactured by Mason-Florida, LLC. for the materials specified in this section. This substitution request is approved and Mason-Florida, LLC is approved as a manufacturer for use on this project subject to compliance with the specifications.

    10 73 00 Protective Covers; A substitution request was received for the use of products manufactured by Mitchell Metals, LLC. for the materials specified in this section. This substitution request is approved and Mitchell Metals, LLC is approved as a manufacturer for use on this project subject to compliance with the specifications.

    10 73 00 Protective Covers; A substitution request was received for the use of products manufactured by Peachtree Protective Covers for the materials specified in this section. This substitution request is approved and Peachtree Protective Covers is approved as a manufacturer for use on this project subject to compliance with the specifications.

  • Exterior Renovation, The Webster School Pond Project No. St. Johns County School District 1110218

    Addendum No. 1, Page 7

    23 74 33 Packaged Rooftop Units; Article 2.1 Manufacturer; Delete subparagraph A and substitute the following to correspond with the Roof Top Unit Schedule shown on sheet M100:

    A. Products shall be furnished by the following manufacturers:

    1. The basis-of-design is CARRIER. Other acceptable manufacturers are Trane and McQuay provided their equipment will be provided with the following items:

    a. R-410A refrigerant b. Direct drive supply fans c. Double wall cabinet construction d. Insulation with a minimum R-value of 13 e. Stainless steel drain pans f. Hinged access doors with lockable handles g. Variable capacity compressor with 10-100% capacity h. All other provisions of the specifications must be

    satisfactorily addressed

    Attachments: Revised Table of Contents Section 064116 Plastic-Laminate-Faced Architectural Cabinets Section 12 36 61 Solid Surface Countertops Section 33 41 00 Storm Utility Drainage Piping Sketch sheet A201-1, Painting Schedule Added sheet A-102, Drainage and Storm Sewer Plan Revised Structural sheets; S-101, S-102, S-201, S-202, S-301, S-302, & S-303.

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    1

    TABLE OF CONTENTS

    INVITATION TO BID

    Division 00 - Procurement and Contracting Requirements

    ADV Advertisement for Bids

    Section A Information for Bidders

    Section B Form of Proposal

    Sworn Statement Public Entity Crimes

    Sworn Statement Jessica Lunsford Act

    Bid Bond

    Section C Owner Contractor Agreement

    Notice of Disclaimer

    Section SC Supplementary Conditions

    Division 01 - General Requirements

    01100 Summary

    01210 Allowances

    01280 Schedule of Values

    01310 Project Meetings

    01320 Schedules and Reports

    01330 Submittal Procedures

    01340 Owner Purchased Material/Equipment

    01450 Quality Control

    01451 Testing Laboratory Services

    01500 Temporary Facilities and Controls

    01560 Temporary Controls

    01600 Product Requirements

    01731 Cutting and Patching

    01740 Construction Cleaning

    01770 Closeout Procedures

    Division 02 -Existing Conditions

    02 41 19 Selective Structure Demolition

    Division 03-Concrete

    03 30 00 Cast-In-Place Concrete

    Division 04 - Masonry

    04 22 00 Concrete Unit Masonry

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    2

    Division 05 - Metals

    05 12 00 Structural Steel Framing

    05 21 00 Steel Joist Framing

    05 31 00 Steel Decking

    05 40 00 Cold-Formed Metal Framing

    Division 06 - Wood, Plastics, And Composites

    06 10 53 Miscellaneous Rough Carpentry

    06 41 16 Plastic-Laminate-Faced Architectural Cabinets, added by Addendum No. 1

    Division 07 - Thermal and Moisture Protection

    07 11 13 Bituminous Dampproofing

    07 42 13.53 Metal Soffit Panels

    07 55 00 SBS Modified Bitumen Membrane Roofing

    07 62 00 Sheet Metal Flashing and Trim

    07 84 13 Penetration Firestopping

    07 92 00 Joint Sealants

    Division 08 - Openings

    08 11 13 Hollow Metal Doors and Frames

    08 14 16 Flush Wood Doors

    08 41 13 Aluminum Storefront Entrances and Framing

    08 44 13 Glazed Aluminum Curtain Walls

    08 71 00 Door Hardware

    08 80 00 Glazing

    Division 09 - Finishes

    09 22 16 Non-Structural Metal Framing

    09 24 00 Portland Cement Plastering

    09 29 00 Gypsum Board

    09 51 13 Acoustical Panel Ceilings

    09 91 13 Interior Painting

    09 91 23 Exterior Painting

    Division 10 - Specialties

    10 73 00 Protective Covers

    Division 11 - Equipment (Not Used)

    Division 12 - Furnishings

    12 36 61 Solid Surface Countertops, Added by Addendum No. 1

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    3

    Division 13 - Special Construction (Not Used)

    Division 14 - Conveying Equipment (Not Used)

    Division 22 - Plumbing (Not Used)

    Division 23 - Heating, Ventilating and Air Conditioning

    23 02 50 Mechanical Insulation

    23 04 00 Plumbing

    23 05 11 Mechanical Basic Requirements

    23 09 90 Testing, Adjusting & Balancing For HVAC

    23 74 33 Packaged Rooftop Units

    23 86 50 Fans

    23 89 00 Ductwork

    Division 25 - Fire Suppression

    25 56 00 Automatic Sprinkler System

    Division 26 – Electrical

    26 00 50 Basic Electrical Materials and Methods

    26 00 73 Hangers & Supports for Electrical Systems

    26 00 75 Electrical Identifications

    26 01 20 Conductors & Cables

    26 01 30 Raceways & Boxes

    26 04 10 Enclosed Switches & Circuit Breakers

    26 05 11 Interior Lighting

    26 07 10 Fire Alarm

    26 07 17 Communications Horizontal Cabling

    Division 27 - Communications (Not Used)

    Division 28 - Electronic Safety and Security (Not Used)

    Division 31 - Earthwork

    311000 Site Clearing

    312000 Earth Moving

    313116 Termite Control

    Division 32 - Exterior Improvements (Not Used)

    Division 33 - Utilities

    33 41 00 Storm Utility Drainage Piping, Added by Addendum No. 1

    Division 48 - Electrical Power Generation (Not Used)

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    PLASTIC-LAMINATE-FACED ARCHITECTURAL CABINETS

    Added by Addendum No. 1

    064116 - 1

    SECTION 064116 - PLASTIC-LAMINATE-FACED ARCHITECTURAL CABINETS

    PART 1 - GENERAL

    1.1 SUMMARY

    A. Section Includes:

    1. Plastic-laminate-faced architectural cabinets. 2. Wood furring, blocking, shims, and hanging strips for installing plastic-laminate-faced

    architectural cabinets unless concealed within other construction before cabinet

    installation.

    1.2 ACTION SUBMITTALS

    A. Shop Drawings: Show location of each item, dimensioned plans and elevations, large-scale details, attachment devices, and other components.

    B. Samples:

    1. Plastic laminates, for each color, pattern, and surface finish.

    1.3 QUALITY ASSURANCE

    A. Fabricator Qualifications: Certified participant in AWI's Quality Certification Program.

    B. Installer Qualifications: Fabricator of products or certified participant in AWI's Quality Certification Program.

    1.4 FIELD CONDITIONS

    A. Environmental Limitations: Do not deliver or install cabinets until building is enclosed, wet work is complete, and HVAC system is operating and maintaining temperature and relative

    humidity at occupancy levels during the remainder of the construction period.

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    PLASTIC-LAMINATE-FACED ARCHITECTURAL CABINETS

    Added by Addendum No. 1

    064116 - 2

    PART 2 - PRODUCTS

    2.1 ARCHITECTURAL CABINET FABRICATORS

    2.2 PLASTIC-LAMINATE-FACED ARCHITECTURAL CABINETS

    A. Quality Standard: Unless otherwise indicated, comply with the "Architectural Woodwork Standards" for grades of architectural plastic-laminate cabinets indicated for construction,

    finishes, installation, and other requirements.

    B. Grade: Custom.

    C. Type of Construction: Face frame.

    D. Cabinet, Door, and Drawer Front Interface Style: Flush overlay.

    E. Reveal Dimension: As indicated.

    F. High-Pressure Decorative Laminate: NEMA LD 3, grades as indicated or if not indicated, as required by woodwork quality standard.

    G. Laminate Cladding for Exposed Surfaces:

    1. Horizontal Surfaces: Grade HGS. 2. Postformed Surfaces: Grade HGP. 3. Vertical Surfaces: Grade VGS. 4. Pattern Direction: Vertically for drawer fronts, doors, and fixed panels.

    H. Materials for Semiexposed Surfaces:

    1. Surfaces Other Than Drawer Bodies: High-pressure decorative laminate, NEMA LD 3, Grade VGS.

    2. Drawer Sides and Backs: Thermoset decorative panels with PVC or polyester edge banding.

    3. Drawer Bottoms: Thermoset decorative panels.

    I. Colors, Patterns, and Finishes: Provide materials and products that result in colors and textures of exposed laminate surfaces complying with the following requirements:

    1. As indicated by laminate manufacturer's designations.

    2.3 PLASTIC-LAMINATE COUNTERTOPS

    A. Quality Standard: Unless otherwise indicated, comply with the "Architectural Woodwork Standards" for grades indicated for construction, installation, and other requirements.

    B. Grade: Custom.

    C. High-Pressure Decorative Laminate: NEMA LD 3, Grade HGS.

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    PLASTIC-LAMINATE-FACED ARCHITECTURAL CABINETS

    Added by Addendum No. 1

    064116 - 3

    D. Colors, Patterns, and Finishes: Provide materials and products that result in colors and textures of exposed laminate surfaces complying with the following requirements:

    1. As indicated by manufacturer's designations.

    E. Edge Treatment: Same as laminate cladding on horizontal surfaces.

    F. Core Thickness: 3/4 inch (19 mm).

    1. Build up countertop thickness to 1-1/2 inches (38 mm) at front, back, and ends with additional layers of core material laminated to top.

    G. Paper Backing: Provide paper backing on underside of countertop substrate.

    2.4 WOOD MATERIALS

    A. Wood Products: Provide materials that comply with requirements of referenced quality standard for each type of woodwork and quality grade specified unless otherwise indicated.

    1. Wood Moisture Content: 8 to 13 percent.

    B. Composite Wood and Agrifiber Products: Provide materials that comply with requirements of referenced quality standard for each type of woodwork and quality grade specified unless

    otherwise indicated.

    1. Medium-Density Fiberboard: ANSI A208.2, Grade 130. 1. Particleboard: ANSI A208.1, Grade M-2. 2. Softwood Plywood: DOC PS 1. 3. Thermoset Decorative Panels: Particleboard or medium-density fiberboard finished with

    thermally fused, melamine-impregnated decorative paper and complying with

    requirements of NEMA LD 3, Grade VGL, for test methods 3.3, 3.4, 3.6, 3.8, and 3.10.

    2.5 CABINET HARDWARE AND ACCESSORIES

    A. Back-Mounted Pulls: BHMA A156.9, B02011.

    B. Wire Pulls: Back mounted, solid metal, 4 inches (100 mm) long, 5/16 inch (8 mm) in diameter.

    C. Shelf Rests: BHMA A156.9, B04013; metal.

    D. Drawer Slides: BHMA A156.9.

    1. Grade 1 and Grade 2: Side mounted; full-extension type; epoxy-coated steel with polymer rollers.

    2. Grade 1HD-100 and Grade 1HD-200: Side mounted; full-extension type; zinc-plated-steel ball-bearing slides.

    3. For drawers not more than 3 inches (75 mm) high and not more than 24 inches (600 mm) wide, provide Grade 1.

    4. For drawers more than 3 inches (75 mm) high but not more than 6 inches (150 mm) high and not more than 24 inches (600 mm) wide, provide Grade 1.

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    PLASTIC-LAMINATE-FACED ARCHITECTURAL CABINETS

    Added by Addendum No. 1

    064116 - 4

    5. For drawers more than 6 inches (150 mm) high or more than 24 inches (600 mm) wide, provide Grade 1HD-100.

    6. For computer keyboard shelves, provide Grade 1.

    E. Door Locks: BHMA A156.11, E07121.

    F. Drawer Locks: BHMA A156.11, E07041.

    G. Door and Drawer Silencers: BHMA A156.16, L03011.

    H. Exposed Hardware Finishes: For exposed hardware, provide finish that complies with BHMA A156.18 for BHMA finish number indicated.

    1. Satin Chromium Plated: BHMA 626 for brass or bronze base; BHMA 652 for steel base.

    I. Grommets for Cable Passage through Countertops: 2-inch (51-mm) OD, black, molded-plastic grommets and matching plastic caps with slot for wire passage.

    1. Product: Subject to compliance with requirements, provide " SG series" by Doug Mockett & Company, Inc.

    2.6 MISCELLANEOUS MATERIALS

    A. Furring, Blocking, Shims, and Hanging Strips: Softwood or hardwood lumber, kiln dried to less than 15 percent moisture content.

    B. Anchors: Select material, type, size, and finish required for each substrate for secure anchorage. Provide metal expansion sleeves or expansion bolts for post-installed anchors. Use nonferrous-

    metal or hot-dip galvanized anchors and inserts at inside face of exterior walls and at floors.

    2.7 FABRICATION

    A. Complete fabrication, including assembly and hardware application, to maximum extent possible before shipment to Project site. Disassemble components only as necessary for

    shipment and installation. Where necessary for fitting at site, provide ample allowance for

    scribing, trimming, and fitting.

    B. Shop-cut openings to maximum extent possible to receive hardware, appliances, electrical work, and similar items. Locate openings accurately and use templates or roughing-in diagrams to

    produce accurately sized and shaped openings. Sand edges of cutouts to remove splinters and

    burrs.

    PART 3 - EXECUTION

    3.1 PREPARATION

    A. Before installation, condition cabinets to average prevailing humidity conditions in installation areas.

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    PLASTIC-LAMINATE-FACED ARCHITECTURAL CABINETS

    Added by Addendum No. 1

    064116 - 5

    3.2 CABINET INSTALLATION

    A. Grade: Install cabinets to comply with same grade as item to be installed.

    B. Install cabinets level, plumb, true, and straight. Shim as required with concealed shims. Install level and plumb to a tolerance of 1/8 inch in 96 inches (3 mm in 2400 mm).

    C. Scribe and cut cabinets to fit adjoining work, refinish cut surfaces, and repair damaged finish at cuts.

    D. Anchor cabinets to anchors or blocking built in or directly attached to substrates. Secure with countersunk, concealed fasteners and blind nailing. Use fine finishing nails for exposed

    fastening, countersunk and filled flush with woodwork.

    E. Cabinets: Install without distortion so doors and drawers fit openings properly and are accurately aligned. Adjust hardware to center doors and drawers in openings and to provide

    unencumbered operation. Complete installation of hardware and accessory items as indicated.

    1. Install cabinets with no more than 1/8 inch in 96-inch (3 mm in 2400-mm) sag, bow, or other variation from a straight line.

    3.3 COUNTERTOP INSTALLATION

    A. Grade: Install countertops to comply with same grade as item to be installed.

    B. Assemble countertops and complete fabrication at Project site to the extent that it was not completed in the shop.

    1. Provide cutouts for appliances, plumbing fixtures, electrical work, and similar items. 2. Seal edges of cutouts by saturating with varnish.

    C. Field Jointing: Prepare edges to be joined in shop so Project-site processing of top and edge surfaces is not required.

    1. Secure field joints in plastic-laminate countertops with concealed clamping devices located within 6 inches (150 mm) of front and back edges and at intervals not exceeding

    24 inches (600 mm). Tighten according to manufacturer's written instructions to exert a

    constant, heavy-clamping pressure at joints.

    D. Install countertops level, plumb, true, and straight. Shim as required with concealed shims. Install level and plumb to a tolerance of 1/8 inch in 96 inches (3 mm in 2400 mm).

    E. Scribe and cut countertops to fit adjoining work, refinish cut surfaces, and repair damaged finish at cuts.

    F. Countertops: Anchor securely by screwing through corner blocks of base cabinets or other supports into underside of countertop.

    1. Install countertops with no more than 1/8 inch in 96-inch (3 mm in 2400-mm) sag, bow, or other variation from a straight line.

    2. Secure backsplashes to walls with adhesive.

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    PLASTIC-LAMINATE-FACED ARCHITECTURAL CABINETS

    Added by Addendum No. 1

    064116 - 6

    3. Seal junctures of tops, splashes, and walls with mildew-resistant silicone sealant or another permanently elastic sealing compound recommended by countertop material

    manufacturer.

    END OF SECTION 064116

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    SOLID SURFACE COUNTERTOPS

    Added by Addendum No. 1

    123661 - 1

    SECTION 123661 – SOLID SURFACE COUNTERTOPS

    PART 1 - GENERAL

    1.1 SUMMARY

    A. Section Includes: 1. Solid-surface-material countertops.

    1.2 ACTION SUBMITTALS

    A. Product Data: For countertop materials.

    B. Shop Drawings: For countertops. Show materials, finishes, edge and backsplash profiles, methods of joining, and cutouts for plumbing fixtures.

    C. Samples: For each type of material exposed to view.

    PART 2 - PRODUCTS

    2.1 SOLID-SURFACE-MATERIAL COUNTERTOPS

    A. Configuration: Provide countertops with the following front and backsplash style:

    1. Front: 1-1/2-inch (38-mm) laminated bullnose.

    B. Countertops: 1/2-inch- (12.7-mm-) thick, solid surface material with front edge built up with same material.

    2.2 COUNTERTOP MATERIALS

    A. Particleboard: ANSI A208.1, Grade M-2.

    B. Plywood: Exterior softwood plywood complying with DOC PS 1, Grade C-C Plugged, touch sanded.

    C. Solid Surface Material: Homogeneous solid sheets of filled plastic resin complying with ANSI SS1.

    1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

    a. Avonite Surfaces. b. E. I. du Pont de Nemours and Company. c. Formica Corporation.

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    SOLID SURFACE COUNTERTOPS

    Added by Addendum No. 1

    123661 - 2

    d. LG Chemical, Ltd. e. Samsung Chemical USA, Inc. f. Swan Corporation (The). g. Wilsonart International.

    2. Type: Provide Standard Type unless Special Purpose Type is indicated. 3. Colors and Patterns: As indicated by manufacturer's designations.

    PART 3 - EXECUTION

    3.1 INSTALLATION

    A. Fasten countertops by screwing through corner blocks of base units into underside of countertop. Align adjacent surfaces and, using adhesive in color to match countertop, form

    seams to comply with manufacturer's written instructions. Carefully dress joints smooth,

    remove surface scratches, and clean entire surface.

    END OF SECTION 123661

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    STORM UTILITY DRAINAGE PIPING

    Added by Addendum No. 1

    334100 - 1

    SECTION 334100 - STORM UTILITY DRAINAGE PIPING

    PART 1 - GENERAL

    1.1 SUMMARY

    A. Section Includes:

    1. Pipe and fittings. 2. Cleanouts. 3. Nonpressure transition couplings. 4. Pipe outlets.

    1.2 ACTION SUBMITTALS

    A. Product Data: For each type of product indicated.

    PART 2 - PRODUCTS

    2.1 PVC PIPE AND FITTINGS

    A. PVC Corrugated Sewer Piping:

    1. Pipe: ASTM F 949, PVC, corrugated pipe with bell-and-spigot ends for gasketed joints. 2. Fittings: ASTM F 949, PVC molded or fabricated, socket type. 3. Gaskets: ASTM F 477, elastomeric seals.

    2.2 NONPRESSURE TRANSITION COUPLINGS

    A. Comply with ASTM C 1173, elastomeric, sleeve-type, reducing or transition coupling, for joining underground nonpressure piping. Include ends of same sizes as piping to be joined, and

    corrosion-resistant-metal tension band and tightening mechanism on each end.

    B. Sleeve Materials:

    1. For Plastic Pipes: ASTM F 477, elastomeric seal or ASTM D 5926, PVC. 2. For Dissimilar Pipes: ASTM D 5926, PVC or other material compatible with pipe

    materials being joined.

    2.3 CLEANOUTS

    A. Plastic Cleanouts:

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    STORM UTILITY DRAINAGE PIPING

    Added by Addendum No. 1

    334100 - 2

    1. Description: PVC body with PVC threaded plug. Include PVC sewer pipe fitting and riser to cleanout of same material as sewer piping.

    2.4 CONCRETE

    A. General: Cast-in-place concrete according to ACI 318, ACI 350/350R (ACI 350M/350RM), and the following:

    1. Cement: ASTM C 150, Type II. 2. Fine Aggregate: ASTM C 33, sand. 3. Coarse Aggregate: ASTM C 33, crushed gravel. 4. Water: Potable.

    B. Portland Cement Design Mix: 4000 psi (27.6 MPa) minimum, with 0.45 maximum water/cementitious materials ratio.

    1. Reinforcing Fabric: ASTM A 185/A 185M, steel, welded wire fabric, plain. 2. Reinforcing Bars: ASTM A 615/A 615M, Grade 60 (420 MPa) deformed steel.

    C. Ballast and Pipe Supports: Portland cement design mix, 3000 psi (20.7 MPa) minimum, with 0.58 maximum water/cementitious materials ratio.

    1. Reinforcing Fabric: ASTM A 185/A 185M, steel, welded wire fabric, plain. 2. Reinforcing Bars: ASTM A 615/A 615M, Grade 60 (420 MPa) deformed steel.

    PART 3 - EXECUTION

    3.1 EARTHWORK

    A. Excavation, trenching, and backfilling are specified in Section 312000 "Earth Moving."

    3.2 PIPING INSTALLATION

    A. General Locations and Arrangements: Drawing plans and details indicate general location and arrangement of underground storm drainage piping. Location and arrangement of piping layout

    take into account design considerations. Install piping as indicated, to extent practical. Where

    specific installation is not indicated, follow piping manufacturer's written instructions.

    B. Install piping beginning at low point, true to grades and alignment indicated with unbroken continuity of invert. Place bell ends of piping facing upstream. Install gaskets, seals, sleeves,

    and couplings according to manufacturer's written instructions for use of lubricants, cements,

    and other installation requirements.

    C. Install proper size increasers, reducers, and couplings where different sizes or materials of pipes and fittings are connected. Reducing size of piping in direction of flow is prohibited.

    D. Install gravity-flow, nonpressure drainage piping according to the following:

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    STORM UTILITY DRAINAGE PIPING

    Added by Addendum No. 1

    334100 - 3

    1. Install piping pitched down in direction of flow. 2. Install piping NPS 6 (DN 150) and larger with restrained joints at tee fittings and at

    changes in direction. Use corrosion-resistant rods, pipe or fitting manufacturer's

    proprietary restraint system, or cast-in-place concrete supports or anchors.

    3. Install piping with 36-inch (915-mm) minimum cover. 4. Install PVC sewer piping according to ASTM D 2321 and ASTM F 1668.

    3.3 PIPE JOINT CONSTRUCTION

    A. Join gravity-flow, nonpressure drainage piping according to the following: 1. Join PVC corrugated sewer piping according to ASTM D 2321 for elastomeric-seal

    joints.

    2. Join dissimilar pipe materials with nonpressure-type flexible couplings.

    3.4 CLEANOUT INSTALLATION

    A. Install cleanouts and riser extensions from sewer pipes to cleanouts at grade. Use cast-iron soil pipe fittings in sewer pipes at branches for cleanouts and cast-iron soil pipe for riser extensions

    to cleanouts. Install piping so cleanouts open in direction of flow in sewer pipe.

    1. Use Light-Duty, top-loading classification cleanouts in earth or unpaved foot-traffic areas.

    2. Use Medium-Duty, top-loading classification cleanouts in paved foot-traffic areas. 3. Use Heavy-Duty, top-loading classification cleanouts in vehicle-traffic service areas.

    B. Set cleanout frames and covers in earth in cast-in-place concrete block, 18 by 18 by 12 inches (450 by 450 by 300 mm) deep. Set with tops 1 inch (25 mm) above surrounding earth grade.

    C. Set cleanout frames and covers in concrete pavement with tops flush with pavement surface.

    3.5 STORMWATER INLET AND OUTLET INSTALLATION

    A. Install outlets that spill onto grade, anchored with concrete, where indicated.

    B. Install outlets that spill onto grade, with flared end sections that match pipe, where indicated.

    3.6 CONCRETE PLACEMENT

    A. Place cast-in-place concrete according to ACI 318.

    3.7 CONNECTIONS

    A. Make connections to existing piping and underground manholes.

    1. Use commercially manufactured wye fittings for piping branch connections. Remove section of existing pipe; install wye fitting into existing piping; and encase entire wye

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    STORM UTILITY DRAINAGE PIPING

    Added by Addendum No. 1

    334100 - 4

    fitting, plus 6-inch (150-mm) overlap, with not less than 6 inches (150 mm) of concrete

    with 28-day compressive strength of 3000 psi (20.7 MPa).

    2. Make branch connections from side into existing piping, NPS 4 to NPS 20 (DN 100 to DN 500). Remove section of existing pipe, install wye fitting into existing piping, and

    encase entire wye with not less than 6 inches (150 mm) of concrete with 28-day

    compressive strength of 3000 psi (20.7 MPa).

    3. Make branch connections from side into existing piping, NPS 21 (DN 525) or larger, or to underground manholes and structures by cutting into existing unit and creating an

    opening large enough to allow 3 inches (76 mm) of concrete to be packed around

    entering connection. Cut end of connection pipe passing through pipe or structure wall to

    conform to shape of and be flush with inside wall unless otherwise indicated. On outside

    of pipe, manhole, or structure wall, encase entering connection in 6 inches (150 mm) of

    concrete for minimum length of 12 inches (300 mm) to provide additional support of

    collar from connection to undisturbed ground.

    a. Use concrete that will attain a minimum 28-day compressive strength of 3000 psi (20.7 MPa) unless otherwise indicated.

    b. Use epoxy-bonding compound as interface between new and existing concrete and piping materials.

    4. Protect existing piping, manholes, and structures to prevent concrete or debris from entering while making tap connections. Remove debris or other extraneous material that

    may accumulate.

    B. Pipe couplings and expansion joints with pressure ratings at least equal to piping rating may be used in applications below unless otherwise indicated.

    1. Use nonpressure-type flexible couplings where required to join gravity-flow, nonpressure sewer piping unless otherwise indicated.

    3.8 IDENTIFICATION

    A. Materials and their installation are specified in Section 312000 "Earth Moving." Arrange for installation of green warning tape directly over piping and at outside edge of underground

    structures.

    1. Use detectable warning tape over nonferrous piping and over edges of underground structures.

    3.9 FIELD QUALITY CONTROL

    A. Inspect interior of piping to determine whether line displacement or other damage has occurred. Inspect after approximately 24 inches (610 mm) of backfill is in place, and again at completion

    of Project.

    1. Submit separate reports for each system inspection. 2. Defects requiring correction include the following:

    a. Alignment: Less than full diameter of inside of pipe is visible between structures.

  • Exterior Renovation, The Webster School Pond Project No.

    St. Johns County School District 1110218

    STORM UTILITY DRAINAGE PIPING

    Added by Addendum No. 1

    334100 - 5

    b. Deflection: Flexible piping with deflection that prevents passage of ball or cylinder of size not less than 92.5 percent of piping diameter.

    c. Damage: Crushed, broken, cracked, or otherwise damaged piping. d. Infiltration: Water leakage into piping. e. Exfiltration: Water leakage from or around piping.

    3. Replace defective piping using new materials, and repeat inspections until defects are within allowances specified.

    4. Reinspect and repeat procedure until results are satisfactory.

    B. Test new piping systems, and parts of existing systems that have been altered, extended, or repaired, for leaks and defects.

    1. Do not enclose, cover, or put into service before inspection and approval. 2. Test completed piping systems according to requirements of authorities having

    jurisdiction.

    3. Schedule tests and inspections by authorities having jurisdiction with at least 24 hours' advance notice.

    4. Submit separate report for each test.

    C. Leaks and loss in test pressure constitute defects that must be repaired.

    D. Replace leaking piping using new materials, and repeat testing until leakage is within allowances specified.

    END OF SECTION 334100


Recommended