    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    4 33KV, XLPE HT Cable

    Supply and laying of 33KV grade 3 core stranded, aluminum

    conductor, XLPE insulated PVC beddedgalvanized flat steel/

    strip armored and PVC overall sheathed, screened cables,

    confirming to IS:7098 Part II (with latest amendments)suitable

    for earthed system. The cable shall bear ISI certification mark.

    Laying of the cable in ground, in soft/ Hard soil at 1000mm

    below ground level including transportation cable to site,

    excavation, refilling with sand and baked bricks on sides and

    pre cast cement slabs on top, providing cable route markers

    complete and as per standard dwg no CED/ELE/S/9

    4.1 3C x 300Sq.mm 33KV(E) XLPE100 Supply Mtr

    100 Laying Mtr

    5 Providing end terminations to 33KV(E), 3core, aluminium

    conductor XLPE cable including supply of heat shrinkable

    Reychem joints end termination kit with all items complete as

    required and as directed ny EIC.

    5.1 3core 300Sq.mm

    2 Out door Nos

    10 Indoor Nos

    6 MV Panels

    Notes for electrical panel works/ bus duct

    1. Cleaning and surface treatment of panel frame and all steel

    parts of the panel shall be carried out through seven tank

    process

    Page 2 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    3/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    2. After rigorous surface treatment, panel shall be treated with

    powder coating process.

    3. Fire retardantpaint shall be applied inside switch chambers

    and bus bar chambers

    4. The panel shall have fire retarding DMC/SMC filling for the

    opening around the bus bar near to the sectional barriers

    5. All terminations shall be made with proper lugs in the

    approved manner.

    6. All exposed cables laid in trench/ wall/ ceiling/ floor/trusses

    shall be painted.

    7. All components,panels, cablesetc., shall confirm to relevant

    IS specificationsand shall also be got approvedby engineerin

    charge

    8. Erection, testing and commissioning of the system and

    various components shal l be done as per the reavant IS

    specifications.

    9. The Panels shall have the following.

    a. High Mechanical and die electric strength

    b. Door interlocking facility for all switchgear cubicles.

    c. Facility for direct termination of specified size and numbers

    of armored aluminum conductor cables.

    d. Shall have 50KA short circuit with standard capability.

    e. The Panel manufacturers shall have both ISO & CPRI

    certification.

    f. Indoor / Outdoor floor mounted cubicles, dead front type,

    Panels, dust & verminproof,fully tropicalisedconstruction with

    14SWG CRCA sheet with necessary anti corrosive treatment

    and powder coating of approvedquality & shade. The panels

    shall be suitable for operation on 500V, 3phase, 4wire, 50Hz

    AC supply complete with all interconnections and consists

    components as specified. (Aluminum Bus bar 0.8A/Sq.mm)

    NOTE:

    1. All ACBs Shall be Electrically Operated and

    Mechanically Drawn out.

    operated.

    2. All ACBs Shall be provided with 110V DC Shunt Coil

    Page 3 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    4/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    for tripping and closing with remote operation facility.

    3. All ACB's shall be suitable for operation of PLC

    System, 1NO and 1NC/auxiliary contacts, potential freecontacts Space shall be provided for the accommodation

    of PLC Modules.

    4. All Load Managers shall be Digital and Multi

    parameters with RS485 port connectivity

    6.1 MAIN PANEL

    1 Supply Set

    1 Installation Set

    i) Main incoming-1: FP EDO ACB of 2500A rating with 50KA

    symmetricalbreaking capacity, Over current and Short circuit

    andEarth fault releasesof Micro processorbased andauxiliary

    contact block and having door interlocking facility and power

    sensing relay provision (provision for operation on

    Electrical/PLC controls) -2Nos

    ii) DG set incoming-2: FP EDO ACB of 2500A rating with 50KA

    symmetricalbreaking capacity, Over current and Short circuit,

    Earth fault protection releasesof Micro processorand auxiliary

    contact block and having door interlockingfacility (provision for

    operation on PLC controls) -2Nos

    iii) Bus couplers: FP EDO ACB of 3200A rating with 50KA

    symmetrical breaking capacity and having door interlocking

    facility (Electrical interlocking& PLC control facility)- 1no.

    .iv) TPN Aluminum Bus bar

    TPN aluminum bus bar of 3200A ,60kA/1Sec capacity,

    mounted on non-hygroscopic, glass fiber reinforced insulators

    with 100% Neutral bus bar-1set (Extendable Bus Bar)

    Page 4 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    5/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    PLC : PLC for Interlocking and automatic operation of

    DG sets as per the Scheme given. Space to be provided

    in Panel for PLC and wiring shall out accordingly. Cost

    of PLC shall be separatedbe carried

    Out going:-

    i) 1250A TP ACB 50KA with Microprocessor based Over c urrent

    and Short circuit releases and Earth fault release 4nos

    ii) 800A TP ACB 50KA with Microprocessor based Over current

    and Short circuit releases and Earth fault release 4nos

    iii) 630A TP ACB 50KA with Microprocessor based Over current

    and Short circuit releases and Earth fault release 4nos

    ..iv) 400A TP MCCB 50KA with Microprocessor based Over current and Short circuit releases 6nos

    v) 250A TP MCCB 35KA with Thermal magnetic Over current

    and Short circuit releases 12nos

    vi) 160A TP MCCB 25KA with Thermal magnetic Over current

    and Short circuit releases 20nos

    viii) 100A TP MCCB 25KA with Thermal magnetic Over current

    and Short circuit releases 10nos

    Metering

    ii)Cast resin CT's 2500-1250/5A With Load Managers

    with RS 485 Connectivity at incoming side 4Sets

    Iii) CT Operated Load Managers with RS485 connectivity

    of different ratings at out going side-58sets.

    a) 2500-1250/5A single CT 2nos for APFCR.

    b) Cts 1200-600/5A- 4Sets (Each-3)

    c) Cts 800-400/5A- 4Sets (Each-3)

    d) Cts 600-300/5A- 4Sets (Each-3)

    e) Cts 400/5A- 6Sets (Each-3)

    f) Cts 250/5A- 12Sets (Each-3)

    g) Cts 160/5A- 20Sets (Each-3)

    h) Cts 100/5A- 10Sets (Each-3)

    i.) PF Meter - 4nos

    j.) HZ Meters 2nos

    k) KW Transducers - 4nos

    l) LED type Phase indication lamps with

    individual TPMCB control and toggle switches -4sets

    m) Control MCBs for Power failure sensing relay -2sets

    n) Auto/ manual selector switch with 1NO for eacho) All Outgoing MCCBs shall be with auxiliary contact

    Page 5 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    6/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    Two numbers of earthing terminals - one on each side of the

    panel with earth strip run inside the panel

    Electrical interlocking to be provided between incomers & bus

    coupler with UV & Auxiliary coils required.

    *** PLC Module with Digital input& output

    6.2 1 Supply, testing and commissioning of Programmable Logic

    Control units for monitoringall services in Rittal/ Euro president

    rack with mounting brackets/terminalconnections etc. Digital

    input 92 nos, Digital output - 64 nos, RS485 modules 6

    nos ( each with may 20nos Energy Meters ), Analog input

    4Nos -16 Channel - 1no, Analogoutput- Nil ( For Main Panel

    )

    Set

    6.3 BUS DUCT

    Electrical works comprising of supply, installation, testing and

    commissioning of Outdoor type standard Aluminum TPN Busduct (0.8A/Sqmm for Phases & 1.6A/Sqmm for Neutral) with

    supports, fixing MS rods, anchor fastener with all fixing hard

    ware materials for outdoor and indoor bus duct complete as

    required.

    i) 2500A TPN Bus duct ( Transformers& DG Syn. Panel

    outgoing )

    OUT DOOR:

    16 Supply Mtr

    16 Installation Mtr

    IN DOOR:

    Transformers & DG Sets

    14 Supply Mtr

    14 Installation Mtr

    Flexible Copper Bus Links for 2Nos of Transformers (2500A)

    Page 6 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    7/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    2.5 Supply Mtr

    2.5 Installation Mtr

    ii) 1250A TPN Bus duct (for DG Sets to DG Syn. Panel)

    IN DOOR:

    33 Supply Mtr

    33 Installation Mtr

    6.4 APFCR Panel

    2 Supply Set

    2 Installation Set

    i) Main incoming: TP ACB of 1250A EDO rating with 50KA

    symmetricalbreaking capacity, Neutral link, shunt trip release

    and auxil iary contact block and having door interlocking

    facility.

    ii) TPN Aluminum Bus bar

    TPN aluminum bus bar of 1600A capacity, mounted on non-

    hygroscopic, glass fiber reinforced insulators with Neutral bus

    bar-1set

    iii) Out goings:-

    250A 35KA TP MCCB with 50KVAR 415V, delta connected

    APP type Capacitor Banks 2sets(Fixed)

    250A, 35KA TP MCCB & 200A TP AC3 duty Contactorwith

    50KVAR 415V, delta connected APP type Capacitor Banks-

    5sets(Variable)

    125A, 25KA TP MCCB & 110A TP AC3 duty Contactorwith

    25KVAR 415V, delta connected APP type Capacitor Banks-

    3sets(Variable)

    Spare 125ATP MCCBs with suitable Contactor & space forfuture 25KVAR capacitor bank 2nos

    Page 7 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    8/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    Metering

    i) Instrumentation, consisting of 0-1200A digital ammeter with

    selector switch and 1250/5A class 1, 15VA resin cast CTs of

    suitable range and accuracy class I, digital voltmeter with

    selector switch, 10stage APFC Relay & digital PF Meter,

    indication lamps, fuses and controls-1set

    ii) Two numbers of earthing terminals - one on each side of the

    panel with earth strip run inside the panel

    iii) All the capacitor feeders shall have digital Ammeter with

    requiredCTs & ON/OFF Indicationlamps & Push buttons and

    Auto / Manual selector switch. And all the contactors shall be

    Capacitor operating duly type.

    6.5 MAIN POWER PANEL ( Block-A ):

    1 Supply Set

    1 Installation Set

    i) Main incoming TP MCCB of 160A rating with 25KA

    symmetrical breaking capacity, Neutral link with Thermal

    magnetic release earth leakage protection with 300-3000mA

    ELR with resin cast CBCT, shunt trip release and auxiliary

    contact block and having door interlocking& mechanical

    interlocking facility -2nos

    ii) Bus couplers: 160A 25KA TP MCCB symmetrical breaking

    capacity and having door interlocking & mechanical

    interlocking facility - 1no.

    Note: Mechanical interlocking facility between Two

    incomers and Bus-coupler shall be provided, so that any

    2 Breakers operate at a time.

    Page 8 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    9/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    iii) TPN Aluminium Busbar

    200A capacity, mounted on non-hygroscopic, glass fiber

    reinforced insulators with 100% Neutral bus bar-1set

    .iv) Outgoing:

    100A, 25KA TPN MCCBs with thermal magnetic release

    2nos

    63A, 25kATPN MCCBs 1nos

    63A TPN MCBs 3nos

    40A TPN MCBs 5nos

    32A DP MCBs 1no

    Metering:

    i) Instrumentation, consistingo f160/5A class 1, 15VA resin cast

    CTs and accuracy class I with Load Manager, indication

    lamps, fuses and controls -2 Sets, CT's 60/5A with Load

    Managers -1set as outgoing

    ii) Two numbers of earthing terminals - one on each side of the

    panel with earth strip run inside the panel

    6.6 MAIN POWER PANEL ( Block-B):

    1 Supply Set

    1 Installation Set

    i) Main incoming TP MCCB of 160A rating of with 25kA

    symmetrical breaking capacity, Neutral link with Adjustable

    Thermal magnetic release earth leakage protection with 300-

    3000mA ELR with resin cast CBCT, shunt trip release and

    auxiliary contact block and having door interlocking facility -

    2nos

    ii) Bus couplers: 160A 25KA TP MCCB symmetrical breaking

    capacity and having door interlocking facility - 1no.

    Page 9 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    10/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    Note: Mechanical interlocking facility between Two

    incomers and Bus-coupler shall be provided so that any

    2 Breakers operate at a time.

    iii) TPN Aluminum Bus bar200A capacity, mounted on non-hygroscopic, glass fiber

    reinforced insulators with 100% Neutral bus bar-1set

    Outgoings:

    125A, 25KA TPN MCCBs with thermal magnetic release-

    2nos

    63A, 25kATPN MCCBs 1nos

    63A TPN MCBs - 3nos

    40A TPN MCBs 5nos

    32A DP MCBs 1no

    Metering:

    i) Instrumentation, consistingo f160/5A class 1, 15VA resin cast

    CTs and accuracy class I with Load Manager, indication

    lamps, fuses and controls -2 Sets, CT's 60/5A with Load

    Managers -1set as outgoing

    ii) Two numbers of earthing terminals - one on each side of the

    panel with earth strip run inside the panel

    6.7 MAIN LIGHTING PANEL -1 ( Block-C )

    1 Supply Set

    1 Installation Set

    i) Main incoming TP ACB of 630A rating with 50KA EDO

    symmetrical breaking capacity, Neutral link with

    microprocessor based release with EF and auxiliary contact

    block and having door interlocking facility 2nos

    ii) Bus couplers: 630A 50KA TP ACB EDO symmetrical

    breaking capacity and having door interlocking facility - 1no.

    Page 10 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    11/32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    12/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    Note: Mechanical interlocking facility between Two

    incomers and Bus-coupler shall be provided so that any

    2 Breakers operate at a time.

    iii) TPN Aluminum Bus bar

    500A capacity, mounted on non-hygroscopic, glass fiber

    reinforced insulators with 100% Neutral bus bar-1set

    .iv) Outgoing:

    250A, 35KA TPN MCCBs with Electronic release- 2nos

    100A, 25KA TPN MCCBs thermal magnetic release 2nos

    63A, 25kATPN MCCBs 1nos

    63A TPN MCBs 2nos

    40A TPN MCBs 3nos

    32A DP MCBs 1no

    Metering:

    i) Instrumentation, consistingo f400/5A class 1, 15VA resin castCTs and accuracy class I with Load Manager, indication

    lamps, fuses and controls -2 Sets, CT's 60/5A with Load

    Managers -1set as outgoing

    ii) Two numbers of earthing terminals - one on each side of the

    panel with earth strip run inside the panel

    6.9 PANEL-2 ( Block-C)

    1 Supply Set

    1 Installation Set

    i) Main incoming TP MCCB of 100A rating with 25KA

    symmetrical breaking capacity, Neutral link with thermal

    magnetic release and earth leakage protection with 300-

    3000mA ELR with resin cast CBCT, shunt trip release and

    auxiliary contact block and having door interlocking facility -

    2nos

    ii) Bus couplers: 100A 25KA TP MCCB symmetrical breaking

    capacity and having door interlocking facility - 1no.

    Page 12 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    13/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    Note: Mechanical interlocking facility between Two

    incomers and Bus-coupler shall be provided so that any

    2 Breakers operate at a time.

    iii) TPN Aluminum Bus bar

    125A capacity, mounted on non-hygroscopic, glass fiber

    reinforced insulators with 100% Neutral bus bar-1set

    .iv) Outgoing:

    63A TPN MCBs 2nos

    40A TPN MCBs 2nos

    Metering:

    i) Instrumentation, consistingo f100/5A class 1, 15VA resin cast

    CTs and accuracy class I with Load Manager, indication

    lamps, fuses and controls -2 Sets, CT's 60/5A with Load

    Managers -1set as outgoing

    ii) Two numbers of earthing terminals - one on each side of the

    panel with earth strip run inside the panel

    6.10 PANEL-2 ( Block-D )

    1 Supply Set

    1 Installation Set

    i) Main incoming TP MCCBs of 100A rating with 25KA

    symmetrical breaking capacity, Neutral link with thermal

    magnetic release earth leakage protection with 300-3000mA

    ELR with resin cast CBCT, shunt trip release and auxiliary

    contact block and having door interlocking facility-2nos

    ii) Bus couplers: 100A 25KA TP MCCB symmetrical breaking

    capacity and having door interlocking facility - 1no.

    Page 13 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    14/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    Note: Mechanical interlocking facility between Two

    incomers and Bus-coupler shall be provided so that any

    2 Breakers operate at a time.

    iii) TPN Aluminum Bus bar125A capacity, mounted on non-hygroscopic, glass fiber

    reinforced insulators with 100% Neutral bus bar-1set

    .iv) Outgoing:

    63A TPN MCCBs 1no

    63A TPN MCBs 2nos

    40A TPN MCBs 3nos

    Metering:

    i) Instrumentation, consistingo f100/5A class 1, 15VA resin cast

    CTs and accuracy class I with Load Manager, indication

    lamps, fuses and controls -2 Sets, CT's 60/5A with Load

    Managers -1set as outgoing

    ii) Two numbers of earthing terminals - one on each side of the

    panel with earth strip run inside the panel

    6.11 UPS INPUT Panel AT Block-C

    1 Supply Set

    1 Installation Set

    i) Main incoming FP MCCBs of 400A rating with 50KA

    symmetricalbreakingcapacity with Microprocessorbasedwith

    EF release facility - 2nos

    ii) Bus couplers: 400A 50KA TP MCCBs with Neutral link &

    mechanical interlocking facility - 1no.

    iii) TPN Aluminum Bus bar

    500A TPN Aluminum with 200% Neutral Bus bar - 1set

    .iv) Outgoing:

    250A 35KA TP MCCB with Thermal Magnetic release -8nos

    v) Metering

    Page 14 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    15/32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    16/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    i) Main incoming FP MCCB of 100A rating with 25KA

    symmetrical breaking capacity with thermal magnetic release-

    1no

    ii) TPN Aluminum Bus bar125A TPN Aluminum with 200% Neutral Bus bar - 1set

    iii) Outgoing:

    63A 16KA FP MCCB with Neutral link - 3nos

    40A 16KA FP MCCB with Neutral link - 1no

    .iv) Metering

    i) instrumentation consisting of 0-500V digital voltmeter with

    selector switch, indication lamps, fuses and controls-1set and

    0-100A Ammeter with CT 100/5A.

    ii) Two numbers of earthing terminals - one on each side of the

    panel with earth strip connected inside the panel

    6.14 UPS OUTPUT Panel at Block-B

    2 Supply Set

    2 Installation Set

    i) Main incoming FP MCCB of 125A rating with 25KA

    symmetrical breaking capacity with thermal magnetic release-

    1no

    ii) TPN Aluminum Bus bar

    160A TPN Aluminum with 200% Neutral Bus bar - 1set

    iii) Outgoing:

    63A 16KA FP MCCB with Neutral link - 1no

    40A 16KA FP MCCB with Neutral link - 5nos

    .iv) Metering

    i) Instrumentation, consisting of 0-500V digital voltmeter with

    selector switch, indication lamps, fuses and controls-1set and

    0-100A Ammeter with CT 125/5A.

    ii) Two numbers of earthing terminals - one on each side of the

    panel with earth strip connected inside the panel

    6.15 UPS OUTPUT Panel at Block-C

    Page 16 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    17/32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    18/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    i) Instrumentation, consisting of, 0-500V digital voltmeter with

    selector switch, indication lamps, fuses and controls and

    0-100A Ammeter with CT 250/5A.- 2Sets

    ii) Two numbers of earthing terminals - one on each side of the

    panel with earth strip connected inside the panel

    6.17 Distribution PANEL ( Antenna pedestal Bldg

    4 Supply Set

    4 Installation Set

    i) Main incoming TP MCCB of 160A rating with 25KA

    symmetrical breaking capacity, Neutral link with thermal

    magnetic release and earth leakage protection with 300-

    3000mA ELR with resin cast CBCT, shunt trip release and

    auxiliary contact block and having door interlocking facility-

    2nos

    ii) Bus couplers: 160A 25KA FP MCCB symmetrical breaking

    capacity and having door interlocking facility - 1no.

    Note: Mechanical interlocking facility between Two

    incomers and Bus-coupler shall be provided so that any

    2 Breakers operate at a time.

    iii) TPN Aluminum Bus bar

    200A capacity, mounted on non-hygroscopic, glass fiber

    reinforced insulators with 100% Neutral bus bar-1set

    Iv) Outgoing:

    100A, 25KA FP MCCBs with Thermal magnetic release-3nos

    25A, 16kA FP MCCBs 5nos

    Page 18 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    19/32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    20/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    Bus bars : 300A TPN Aluminum Bus bar

    with 100% neutral - 1Set

    Outgoings:

    100A 35KA TP MCCB 2nos

    63A 35KA TP MCCB 1no

    63A TP MCB 2nos

    40A TP MCB 1no

    32A DP MCB -1no

    Spares-1no

    Metering :

    i) CT 250\5A with Digital load manager with RS 485

    connectivity-1No

    ii)LED type Phase indication lamps with

    individual TPMCB control and toggle switches -2set

    6.20 MAIN PCC (SECURITY BLDG)

    1 Supply Each

    1 Installation Each

    Incomer :250A,35KA TP MCCB 2sets

    Bus bars : 300A TPN Aluminum Bus bar

    with 100% neutral - 1Set

    Outgoings:

    100A TP MCCB 1No

    63A TP MCB 2nos

    40A TP MCB 3Nos

    Metering :

    i) 250/5A CT with load manager with RS485 connectivity

    2Sets

    2)LED type Phase indication lamps with

    individual TPMCB control and toggle switches -2set

    (Mechanical interlocking between two bus couplers)

    6.21 UPS OUTPUT PANEL (SECURITY BLDG& SERVICES

    BLDG)

    2 Supply Each

    2 Installation Each

    Incomer :100A,25KA TP MCCB 1Set

    Bus bars : 125A TPN Aluminum Bus bar

    Page 20 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    21/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    With 200% neutral - 1Set

    Outgoings:

    40A FP MCCB 3Nos

    Metering :

    i)Instrumentation, consisting of 0-500V digital voltmeter with

    selector switch, indication lamps, fuses and controls-1set

    0-100A Ammeter with CT 100/5A.- 1Set

    ii)LED type Phase indication lamps with

    individual TPMCB control and toggle switches -1set

    (Mechanical interlocking between two bus couplers)

    6.22 PCC (SUB STATION BLDG)

    1 Supply Nos

    1 Installation Nos

    Incoming :250A,35KA TP+NL MCCB with

    80-100% Thermal Setting plug 2nos

    Bus bars : 350A 35KA TPN Aluminum Bus bars-1set

    Bus coupler : 250A 35KA TPN MCCB -1set

    Out goings :

    100A,25KA TPNMCCB-2nos

    63A,10KA TPNMCB 6 nos

    40A,10KA TPNMCB 3 nos

    Metering :

    i) CT 250/5V WITH LOAD MANAGER WITH RS-485

    CONNECTIVITY - 1set

    ii)LED type Phase indication lamps withIndividual TPMCB control and toggle switches -3set

    Iii) Control MCBs for Power failure indication -1set

    MV CABLES

    7 Supply of 1.1KV grade XLPE insulated, and overall sheathed,

    stranded aluminum/ Copper conductor, flat steel strip/wire

    armored / unarmoredcables confirming to IS:7098/Part I (with

    latest amendments) and of following sizes. The cable shall be

    ISI certification mark.

    Note: The Actual Lengths of cables shall be verified at

    site before procurements

    For Aluminum

    Page 21 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    22/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    7.1 7520 3.5Core 240sq.mm Mtr

    7.2 8013 3.5Core 185sq.mm Mtr

    7.3 18153 3.5Core 120sq.mm Mtr

    7.4 2438 3.5Core 95sq.mm Mtr

    7.5 115 3.5Core 70sq.mm Mtr

    7.6 346 3.5Core 25sq.mm Mtr

    7.7 625 4Core 16sq.mm Mtr

    For Copper

    7.8 210 3.5Core 95sq.mm - Copper Mtr

    7.9 140 3Core 95sq.mm - Copper Mtr

    7.10 140 2Core 95sq.mm - Copper Mtr

    7.11 690 3Core 35sq.mm - Copper Mtr

    7.12 970 2Core 35sq.mm - Copper Mtr

    Page 22 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    23/32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    24/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    7.25 200 8Core 1.5sq.mm Copper Mtr

    8 Laying of followingcables in existing trench /on cable tray, on

    wall / floor / cei ling / above false cei ling / below false floor

    including transportation of cable to site, removing of trench /

    false ceiling / false flooring covers and re closing the covers

    after laying the cables in good condition with supply of al l

    necessary materials such as brackets, clamps, MS spacers

    complete as required and the cable laying in ground, 750mm

    below ground level including Transportation of cable to site,

    excavation, refilling with sand and baked bricks on top and

    sides and providing cable route marker etc as DWG NO:

    CED/ELE/8&10 and as directed by Engineer-in-charge.

    For Aluminum: Laying in ground

    8.1 1300 3.5Core 240sq.mm (2Runs) Mtr

    8.2 1235 3.5Core 240sq.mm (4Runs) Mtr

    8.3 800 3.5Core 185sq.mm (1Run) Mtr

    8.4 1740 3.5Core 185sq.mm (3 Runs) Mtr

    8.5 200 3.5Core 185sq.mm (5 Runs) Mtr

    8.6 1200 3.5Core 120sq.mm (1 Run) Mtr

    8.7 60 3.5Core 120sq.mm (1 Run on Tray) Mtr

    Page 24 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    25/32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    26/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    8.21 280 2Core 10sq.mm - Copper Mtr

    8.22 125 3Core 10sq.mm - Copper Mtr

    8.23 100 4Core 6sq.mm - Copper Mtr

    8.24 50 4Core 16sq.mm - Copper Mtr

    8.25 20 3Core 16sq.mm - Copper Mtr

    8.26 20 2Core 16sq.mm - Copper Mtr

    Control cables

    8.27 400 3Core 2.5sq.mm Copper for APFCR Mtr

    8.28 500 4Core 2.5sq.mm Copper Mtr

    8.29 300 10Core 2.5sq.mm Copper Mtr

    8.3 200 4Core 1.5sq.mm Copper Mtr

    8.31 200 8Core 1.5sq.mm Copper Mtr

    Page 26 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    27/32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    28/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    9.11 8 3Core 35sq.mm - Copper Nos

    9.12 8 2Core 35sq.mm - Copper Nos

    9.13 8 3Core 25sq.mm - Copper Nos

    9.14 8 2Core 25sq.mm - Copper Nos

    9.15 14 2Core 10sq.mm - Copper Nos

    9.16 14 3Core 10sq.mm - Copper Nos

    9.17 8 4Core 6sq.mm - Copper Nos

    9.18 2 4Core 16sq.mm - Copper Nos

    9.19 2 3Core 16sq.mm - Copper Nos

    9.20 2 2Core 16sq.mm - Copper Nos

    Control cables

    9.21 30 3Core 2.5sq.mm Copper for APFCR Nos

    9.22 60 4Core 2.5sq.mm Copper Nos

    9.23 60 10Core 2.5sq.mm Copper Nos

    Page 28 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    29/32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    30/32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    31/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    15.1 27 Providingstandard pipe earth to earth stations with 2.5m long,

    38mm dia GI pipe earth stations confirming to IS : 3043 with

    latest amendments and as per standard dwg., and including

    supply of all materials and providingchamber completeas per

    standarddrawingas required.(DP Structure-2nos,HT Panels-

    Transco-2nos& Supplier side-4nos, Transformers 4nos,

    Fencing-1no, MV Panels -4nos, DG-8nos ) (Wherever hard

    rock, the arrangementshall be horizontaltype as shown in the

    drawing)

    each

    15.2 12 Providing standard 2.5m depth with copper plate earth for

    earth station with 600x600x3.15mm electrolytic copper plate,

    confirming to IS:3043 with latest amendments and as per

    standard dwg., including supply of all materials and providing

    chamber complete as required. ( for Tr.Nu-4nos, DG Nu-8nos)

    each

    16 Supply and laying of electrolytic copper/GI strip of following

    sizes includingsupply and fixingusing MS/Aluminiumspacers,

    saddles welding with all fixing materialsrequired and when laid

    inside the building and inclusive of excavation & refilling of

    earth when laid outside the building and tinning of all the joints

    & terminations interconnections interconnections with earth pit

    and equipment, terminations/ interconnections in an approved

    manner as per IS 3043 (with latest amendments) inclusive of

    supply os all hardwares complete as required.

    16.1 350 50 x 6mm GI strip (Body Earthing of TR, Main PCC etc) Mtr

    16.2 140 50 x 6mm copper strip (for Neutrals of Tr) Mtr

    Page 31 of 32

  • 7/29/2019 EXTERNAL POWER SUPPLY WORKS

    32/32

    Package-II Part-V EXTERNAL POWER SUPPLY WORKS

    Sl. NO QTY DESCRIPTION OF ITEM UNITS RATE (IN

    FIGURES & WORDS)

    AMOUNT

    16.3 295 25 x 6mm GI strip ( for Sub Panels Earthing, earthing to

    Fencing & cable trays)

    Mtr

    17 HEAT/ FIRE RESISTANT COATING:

    10 Supply and Coating of Fire resistant compoundof waterbased

    thermoplastic resin, flame retardant chemicals and inorganic

    incombustible fibers for coating on the cables to withstand

    severe fires and to prevent propagationalong horizontallyand

    vertically laid cables on wall or on cable trays under high

    temperature conditions. The compound shall be similar to

    VIPER CABLEMASTIC FR-903 Complete as required.

    kG