EXTRACT FROM REPORT N. 2221 / 0017
REFERENCE STANDARD
FGW TG3: DETERMINATION OF THE ELECTRICAL CHARACTERISTICS OF POWER GENERATING UNITS AND
SYSTEMS, STORAGE SYSTEMS AS WELL FOR THEIR COMPONENTS IN MV, HV AND EHV GRIDS.
(REV. 25 DATED ON 01/09/2018 + SUPPLEMENT 1 DATED ON 22/01/2019)
Reference Test Report Number ................... : 2221 / 0017 (Extract from test resuls) – Rev. 1
Product Type............................................... : 3 Phase Grid Connected PV Inverter
Tested Model .............................................. : STP 110-60
Variant Models ............................................ : N/A
APPLICANT
Name .......................................................... : SMA SOLAR TECHNOLOGY AG
Address ...................................................... : Sonnenallee 1, 34266 Niestetal (Germany)
TESTING LABORATORY
Name .......................................................... : SGS Tecnos, S.A. (Electrical Testing Laboratory)
Address ...................................................... : C/ Trespaderne, 29 - Edificio Barajas 1
28042 Madrid (Spain)
Conducted (tested) by ................................. : Michael Tong
(Project Engineer)
Reviewed and Approved by ......................... : Jacobo Tévar
(Technical Reviewer)
Date of issue ............................................... : 05/03/2021
Number of pages......................................... : 28
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 2 of 28
Rev. 1
FGW-TG3+SP1
Important Note:
• This document is issued by the Company under its General Conditions of service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of liability, indemnification and jurisdiction issues defined therein. Any holder of this document is advised that information contained hereon reflects the Company's findings at the time of its intervention only and within the limits of Client's instructions, if any. The Company's sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising all their rights and obligations under the transaction documents.
• This document cannot be reproduced except in full, without prior written approval of the Company. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be prosecuted to the fullest extent of the law.
• Unless otherwise stated the results shown in this test report refer only to the sample(s) tested as received. Information of derived or extension models of the range as provided by the applicant, (if any), is included in this report only for informative purposes. The Company SGS shall not be liable for any incorrect results arising from unclear, erroneous, incomplete, misleading or false information provided by Client.
Document Historical Revision:
Test Report Version Date Resume
Extract from report n. 2221 / 0017 – TG3 Revision 1 of the Extract from report n. 2221 / 0017 – TG3
01/03//2021 05/03/2021
First issuance Corrected words with spelling mistakes in pages 16 and 26.
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 3 of 28
Rev. 1
FGW-TG3+SP1
INDEX
1 SCOPE ................................................................................................................................................... 4
2 GENERAL INFORMATION ..................................................................................................................... 5
2.1 TESTING PERIOD AND CLIMATIC CONDITIONS ......................................................................................... 5 2.2 EQUIPMENT UNDER TESTING ................................................................................................................ 5
2.2.1 Reference Values ...................................................................................................................... 7
3 TEST RESULTS ...................................................................................................................................... 8
3.1 NENNDATEN / RATED DATA: ................................................................................................................ 8 3.2 POWER QUALITY ................................................................................................................................. 9
3.2.1 Wirkleistungsspitzen / Power Peaks ........................................................................................... 9 3.2.2 Schalthandlungen / Switching Operation .................................................................................. 10 3.2.3 Unsymmetrie / Unbalances ...................................................................................................... 11 3.2.4 Flicker ..................................................................................................................................... 11 3.2.5 Oberschwingungsmessungen / Harmonics .............................................................................. 12 3.2.6 Zwischenharmonische / lnterharmonics.................................................................................... 13 3.2.7 Höhere Frequenzen / Higher Frequencies components ............................................................ 14
3.3 GRID CONTROL CAPABILITY .............................................................................................................. 15 3.3.1 Wirkleistungs einspeisung in Abhängigkeit der Netfrequenz / Active power vs frequency .......... 15 3.3.2 Blindleistungbereitstellung / Provision of reactive power ........................................................... 16
3.4 PROTECTION SYSTEM ........................................................................................................................ 22 3.4.1 Trennung der EZE vom Netz / Cut-off from grid........................................................................ 22 3.4.2 Zuschaltbedingungen / Cut-in conditions .................................................................................. 26 3.4.3 Zuschaltbedingungen nach Auslösung des Entkupplungsschutzes / Cut-in conditions after tripping of protection .............................................................................................................................. 26 3.4.4 Zuschaltbedingungen nach Auslösung des Entkupplungsschutzes / Cut-in conditions after tripping of protection .............................................................................................................................. 27
3.5 RESPONSE DURING GRID FAULTS........................................................................................................ 28
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 4 of 28
Rev. 1
FGW-TG3+SP1
1 Scope
SGS Tecnos, S.A. (Electrical Testing Laboratory) has been contracted by SMA SOLAR TECHNOLOGY AG,
in order to perform testing according to FGW-TG3: Technical Guidelines for Power Generating Units and
Systems. TG3 (Revision 25 Dated 01/09/2018 + Supplement 1 Dated 22/01/2019): Determination of Electrical
Characteristics of Power Generating Units and Systems, Storage Systems as well for their Components in
MV, HV and EHV grids.
The following standards are covered with testing of FGW-TG3 (Revision 25 Dated 01/09/2018) (*):
- VDE-AR-N 4110: 2018-11. Technical requirements for the connection and operation of customer installations to the medium voltage network (TAR medium voltage).
- VDE-AR-N 4120: 2018-11. Technical requirements for the connection and operation of customer installations to the high voltage network (TAR high voltage).
This document is an extract from the test report 2221 / 0017 compliant with the Annex B of FGW TG3 (Rev.
25 dated on 01/09/2018 + supplement 1 dated on 22/01/2019).
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 5 of 28
Rev. 1
FGW-TG3+SP1
2 General Information 2.1 Testing Period and Climatic conditions
The necessary testing has been performed between April 15th of 2020 and February 20th of 2021.
SITE TEST
Name ......................................................... : Dongguan BALUN Technology Co., Ltd.
Address ...................................................... : Room 104, 204, 205, Building 1, No. 6, Industrial South
Road, Songshan Lake Park, Dongguan, Guangdong
Province, P. R. China. 523808.
2.2 Equipment under Testing
Apparatus type .......................................... : Grid Connected PV Inverter
Installation ................................................. : 3 Phase ~ / Fixed installation
Manufacturer ............................................. : SMA Solar Technology AG
Trade mark ................................................ :
Model / Type reference .............................. : STP 110-60
Serial Number ........................................... : A2005190011
Software Version ....................................... : 1.00.00.R
Rated Characteristics ................................ : Input: 200~1000 Vdc MPPT Voltage Range (500~800Vdc with rated power output); 12*26 Adc Max.
Output: 3 Phase ~ 400Vac; 50Hz; 158.8Aac @110kW rated.
Date of manufacturing: 2020
Test item particulars
Input .......................................................... : DC
Output ........................................................ 3~/PE
Class of protection against electric shock ... : Class I
Degree of protection against moisture ........ : IP 66
Type of connection to the main supply ....... : Three-phase – Fixed installation
Cooling group ............................................ : Forced ventilation (Fans)
Modular ..................................................... : No
Internal Transformer .................................. : No
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 6 of 28
Rev. 1
FGW-TG3+SP1
Copy of marking plate:
Note:
1. Label is attached on the side surface of enclosure and visible after installation.
Equipment under testing:
- STP 110-60 The results obtained apply only to the particular sample tested that is the subject of the present test report. The most unfavorable result values of the verifications and tests performed are contained herein. Throughout this report a point is used as the decimal separator.
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 7 of 28
Rev. 1
FGW-TG3+SP1
2.2.1 Reference Values
The values presented in the following table have been used for calculation of referenced values (p.u.; %) thougth the report.
Reference Values
Rated power, Pn in kW 110
Rated apparent power, Sn in kVA 110
Rated wind speed (only WT), vn in m/s Not applicable
Rated current (determined), In in A 158.8
Rated output voltage, (phase to phase) Un in Vac
400 (*)
Note: In this report p.u. values are calculated as follows: -For Active & Reactive Power p.u values are reference to Pn -For Currents p.u values, the reference is always In -For Voltages p.u values, the reference is always Un -Only “Un=400V” has been evaluated in this report.
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 8 of 28
Rev. 1
FGW-TG3+SP1
3 TEST RESULTS 3.1 Nenndaten / Rated data:
Nennscheinleistung Sn 110 kVA Nennstrom In 158.8 A
Nennfrequenz fn rated frequency fn
50 Hz Nennspannung Un rated Voltage Un
400 V
Note 1: The maximum apparent power of the certified unit is 110 kVA.
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 9 of 28
Rev. 1
FGW-TG3+SP1
3.2 Power quality
3.2.1 Wirkleistungsspitzen / Power Peaks Test results under are offered in the following table:
DC Voltage (V)
Wirkleistungsspitzen in kW / Power peaks in kW
Wirkleistungsspitzen in p.u. / Power peaks in p.u.
Anzahl 10-Minuten Datensätze in / Number of 10-
minute data set
200 p600 = P600/Pn 47.493 p60 = P60/Pn 0.431 21
250 p600 = P600/Pn 57.661 p60 = P60/Pn 0.524 21
300 p600 = P600/Pn 67.023 p60 = P60/Pn 0.610 21
350 p600 = P600/Pn 77.874 p60 = P60/Pn 0.708 21
400 p600 = P600/Pn 87.842 p60 = P60/Pn 0.798 21
450 p600 = P600/Pn 109.485 p60 = P60/Pn 0.996 21
500 p600 = P600/Pn 109.673 p60 = P60/Pn 0.997 21
530 p600 = P600/Pn 109.740 p60 = P60/Pn 0.998 21
560 p600 = P600/Pn 109.895 p60 = P60/Pn 0.999 21
590 p600 = P600/Pn 109.895 p60 = P60/Pn 1.000 21
620 p600 = P600/Pn 109.787 p60 = P60/Pn 0.999 21
650 p600 = P600/Pn 109.463 p60 = P60/Pn 0.995 21
680 p600 = P600/Pn 108.899 p60 = P60/Pn 0.990 21
710 p600 = P600/Pn 109.109 p60 = P60/Pn 0.992 21
740 p600 = P600/Pn 109.417 p60 = P60/Pn 0.994 21
770 p600 = P600/Pn 109.755 p60 = P60/Pn 0.998 21
800 p600 = P600/Pn 109.755 p60 = P60/Pn 0.998 21
850 p600 = P600/Pn 105.264 p60 = P60/Pn 0.957 21
900 p600 = P600/Pn 92.527 p60 = P60/Pn 0.841 21
950 p600 = P600/Pn 54.864 p60 = P60/Pn 0.499 21
1000 p600 = P600/Pn 4.884 p60 = P60/Pn 0.051 21
Note: The MPPT range is 200V to 1000V, while the MPPT range of nominal power is from 500V to 800V.
Active Power Peaks
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 10 of 28
Rev. 1
FGW-TG3+SP1
3.2.2 Schalthandlungen / Switching Operation
Schalthandlungen / Case of switching operation
Einschalten bei Pverfügbar <10 % Pn (Einschaltwindgeschw.) /
Start-up at Pavailable < 10% Pn (cut-in wind speed)
Max Anz. Schalthandlungen / Max, number of switching operations, N10
20
Max Anz. Schalthandlungen / Max, number of switching operations, N120
240
Netzimpedanzwinkel / Grid impedance angle
30º 50º 70º 85º
Flickerformfaktor / Flicker step factor, kf (Ψk)
Phase A 0.014 0.015 0.009 0.007
Phase B 0.015 0.015 0.009 0.007
Phase C 0.016 0.015 0.009 0.007
Spannungsänderungsfaktor / Voltage change factor, kU (Ψk)
Phase A 0.073 0.073 0.073 0.073
Phase B 0.084 0.084 0.084 0.084
Phase C 0.111 0.111 0.111 0.111
Schalthandlungen / Case of switching operation
Einschalten bei Pverfügbar - Pn (Nennwindgeschwindigkeit) Start-up at Pavailable = Pn (rated wind speed)
Max Anz. Schalthandlungen / Max, number of switching operations, N10
20
Max Anz. Schalthandlungen / Max, number of switching operations, N120
240
Netzimpedanzwinkel / Grid impedance angle
30º 50º 70º 85º
Flickerformfaktor / Flicker step factor, kf (Ψk)
Phase A 0.015 0.018 0.021 0.022
Phase B 0.015 0.018 0.021 0.022
Phase C 0.015 0.018 0.021 0.022
Spannungsänderungsfaktor / Voltage change factor, kU (Ψk)
Phase A 0.180 0.180 0.180 0.180
Phase B 0.139 0.139 0.139 0.139
Phase C 0.177 0.177 0.177 0.177
Schalthandlungen / Case of switching operation
Seviceabschaltung bei Nennleistung / Cut off at rated power
Max Anz. Schalthandlungen / Max, number of switching operations, N10
20
Max Anz. Schalthandlungen / Max, number of switching operations, N120
240
Netzimpedanzwinkel / Grid impedance angle
30º 50º 70º 85º
Flickerformfaktor / Flicker step factor, kf (Ψk)
Phase A 0.177 0.177 0.177 0.177
Phase B 0.034 0.029 0.023 0.021
Phase C 0.033 0.029 0.023 0.021
Spannungsänderungsfaktor / Voltage change factor, kU (Ψk)
Phase A 0.191 0.191 0.191 0.191
Phase B 0.155 0.155 0.155 0.155
Phase C 0.216 0.216 0.216 0.216
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 11 of 28
Rev. 1
FGW-TG3+SP1
3.2.3 Unsymmetrie / Unbalances
Pn (%Sn)
V1+ (V) V1- (V) I1+ (A) I1- (A) Ui (%) Number of
records
100 399.988 0.144 158.036 0.199 0.126 1200
90 399.911 0.155 142.493 0.186 0.130 1200
80 399.846 0.146 126.896 0.174 0.137 1200
70 399.784 0.142 111.303 0.148 0.133 1200
60 399.729 0.139 95.652 0.121 0.126 1200
50 399.670 0.131 79.915 0.110 0.138 1200
40 399.605 0.126 64.148 0.094 0.146 1200
30 399.553 0.110 48.355 0.085 0.177 1200
20 399.492 0.111 31.996 0.098 0.305 1200
10 399.430 0.120 16.153 0.117 0.726 1200
0 399.381 0.139 1.824 0.162 8.893 1200
3.2.4 Flicker
Netzimpedanzwinkel / Network impedance phase angle, Ψk
30º 50º 70º 85º
P (%Pn) Flickerkoeffizient / Flicker coefficient, C (Ψk, Pa)
0 0.275 0.275 0.275 0.275
10 0.282 0.291 0.297 0.300
20 0.301 0.331 0.354 0.363
30 0.326 0.386 0.432 0.448
40 0.360 0.454 0.524 0.548
50 0.400 0.526 0.619 0.652
60 0.442 0.605 0.720 0.759
70 0.494 0.692 0.828 0.873
80 0.536 0.770 0.929 0.982
90 0.591 0.858 1.038 1.096
100 0.643 0.945 1.145 1.208
Max 0.643 0.945 1.145 1.208
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 12 of 28
Rev. 1
FGW-TG3+SP1
3.2.5 Oberschwingungsmessungen / Harmonics
Pn (%) 0 10 20 30 40 50 60 70 80 90 100 Max (%) Nr./ Order Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%)
2 0.097 0.108 0.098 0.097 0.093 0.117 0.111 0.139 0.152 0.153 0.117 0.153
3 0.036 0.067 0.067 0.072 0.080 0.087 0.090 0.113 0.126 0.133 0.139 0.139
4 0.062 0.070 0.046 0.040 0.034 0.032 0.025 0.035 0.034 0.029 0.028 0.070
5 0.859 0.879 0.703 0.583 0.512 0.412 0.355 0.280 0.093 0.138 0.277 0.879
6 0.029 0.030 0.023 0.021 0.022 0.028 0.024 0.028 0.032 0.029 0.018 0.032
7 0.446 0.490 0.528 0.455 0.402 0.353 0.364 0.379 0.332 0.370 0.395 0.528
8 0.016 0.028 0.033 0.027 0.023 0.020 0.020 0.020 0.026 0.032 0.027 0.033
9 0.027 0.038 0.043 0.039 0.035 0.042 0.042 0.042 0.049 0.066 0.069 0.069
10 0.017 0.032 0.046 0.048 0.050 0.046 0.040 0.045 0.045 0.043 0.044 0.050
11 0.197 0.195 0.183 0.187 0.186 0.165 0.143 0.121 0.136 0.146 0.146 0.197
12 0.017 0.017 0.022 0.019 0.022 0.030 0.028 0.028 0.027 0.028 0.017 0.030
13 0.183 0.192 0.185 0.175 0.177 0.164 0.157 0.152 0.126 0.095 0.066 0.192
14 0.019 0.019 0.021 0.028 0.032 0.030 0.027 0.030 0.033 0.034 0.029 0.034
15 0.022 0.022 0.024 0.027 0.027 0.028 0.028 0.031 0.034 0.036 0.039 0.039
16 0.015 0.020 0.019 0.026 0.031 0.030 0.032 0.034 0.035 0.040 0.039 0.040
17 0.117 0.115 0.112 0.099 0.096 0.107 0.098 0.086 0.089 0.088 0.090 0.117
18 0.016 0.018 0.017 0.018 0.016 0.016 0.019 0.021 0.021 0.021 0.018 0.021
19 0.106 0.104 0.099 0.109 0.098 0.103 0.107 0.100 0.097 0.092 0.095 0.109
20 0.017 0.019 0.016 0.021 0.026 0.024 0.025 0.026 0.027 0.025 0.022 0.027 21 0.032 0.022 0.022 0.023 0.024 0.025 0.028 0.027 0.026 0.024 0.023 0.032
22 0.016 0.014 0.016 0.017 0.019 0.023 0.023 0.024 0.026 0.026 0.024 0.026
23 0.087 0.089 0.086 0.081 0.080 0.088 0.080 0.076 0.083 0.082 0.077 0.089
24 0.019 0.015 0.015 0.016 0.016 0.017 0.017 0.020 0.020 0.018 0.016 0.020
25 0.082 0.078 0.078 0.079 0.080 0.084 0.084 0.076 0.076 0.074 0.073 0.084
26 0.019 0.016 0.015 0.016 0.016 0.015 0.016 0.018 0.020 0.018 0.016 0.020
27 0.036 0.019 0.020 0.021 0.020 0.021 0.022 0.022 0.022 0.020 0.021 0.036
28 0.017 0.014 0.015 0.015 0.015 0.015 0.016 0.017 0.016 0.017 0.015 0.017
29 0.074 0.079 0.064 0.071 0.074 0.078 0.077 0.076 0.077 0.078 0.077 0.079
30 0.017 0.013 0.013 0.013 0.013 0.014 0.014 0.016 0.015 0.015 0.014 0.017
31 0.073 0.064 0.059 0.063 0.066 0.067 0.069 0.066 0.063 0.064 0.065 0.073
32 0.018 0.025 0.026 0.028 0.028 0.029 0.031 0.032 0.014 0.013 0.023 0.032
33 0.026 0.019 0.020 0.020 0.020 0.020 0.021 0.021 0.019 0.019 0.020 0.026
34 0.015 0.025 0.026 0.028 0.028 0.029 0.030 0.032 0.014 0.014 0.023 0.032
35 0.061 0.065 0.066 0.065 0.063 0.066 0.066 0.066 0.066 0.068 0.069 0.069
36 0.015 0.013 0.014 0.014 0.014 0.013 0.014 0.015 0.014 0.014 0.013 0.015
37 0.053 0.061 0.061 0.059 0.061 0.060 0.061 0.058 0.056 0.057 0.055 0.061
38 0.017 0.013 0.014 0.015 0.014 0.014 0.013 0.014 0.013 0.013 0.012 0.017
39 0.025 0.023 0.025 0.024 0.025 0.023 0.024 0.023 0.026 0.019 0.019 0.026
40 0.015 0.013 0.014 0.014 0.014 0.014 0.014 0.013 0.012 0.012 0.012 0.015
41 0.046 0.054 0.054 0.054 0.055 0.051 0.053 0.053 0.049 0.050 0.053 0.055
42 0.014 0.013 0.013 0.013 0.014 0.013 0.013 0.013 0.012 0.012 0.012 0.014
43 0.039 0.050 0.051 0.052 0.052 0.048 0.049 0.047 0.043 0.045 0.046 0.052
44 0.015 0.012 0.013 0.013 0.013 0.012 0.012 0.012 0.011 0.011 0.011 0.015
45 0.020 0.017 0.017 0.018 0.019 0.017 0.018 0.017 0.015 0.015 0.016 0.020
46 0.013 0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.011 0.011 0.011 0.013
47 0.040 0.048 0.047 0.049 0.048 0.043 0.044 0.044 0.041 0.044 0.046 0.049
48 0.012 0.012 0.012 0.012 0.012 0.011 0.012 0.012 0.011 0.010 0.011 0.012
49 0.035 0.041 0.041 0.044 0.043 0.039 0.040 0.040 0.038 0.040 0.042 0.044
50 0.013 0.012 0.012 0.014 0.013 0.012 0.012 0.012 0.011 0.010 0.010 0.014
TDC (%) 1.048 1.089 0.966 0.839 0.762 0.671 0.634 0.605 0.515 0.550 0.605 1.089
PWHD (%) 1.377 1.412 1.376 1.395 1.392 1.411 1.412 1.367 1.329 1.333 1.343 1.412
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 13 of 28
Rev. 1
FGW-TG3+SP1
3.2.6 Zwischenharmonische / lnterharmonics
Pn (%) 0 10 20 30 40 50 60 70 80 90 100 MAX (%) F [Hz] Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%)
75 0.016 0.020 0.020 0.022 0.023 0.022 0.022 0.023 0.022 0.021 0.041 0.041
125 0.015 0.016 0.015 0.019 0.023 0.020 0.020 0.022 0.024 0.027 0.033 0.033
175 0.014 0.015 0.014 0.017 0.020 0.022 0.019 0.020 0.030 0.037 0.024 0.037
225 0.014 0.013 0.013 0.014 0.018 0.022 0.021 0.023 0.026 0.031 0.019 0.031
275 0.014 0.013 0.015 0.015 0.016 0.022 0.021 0.022 0.032 0.036 0.019 0.036
325 0.015 0.015 0.014 0.015 0.016 0.020 0.021 0.025 0.025 0.020 0.017 0.025
375 0.015 0.013 0.013 0.014 0.014 0.017 0.021 0.022 0.027 0.024 0.015 0.027
425 0.015 0.012 0.013 0.013 0.014 0.016 0.019 0.020 0.030 0.027 0.015 0.030
475 0.014 0.013 0.013 0.014 0.014 0.016 0.018 0.016 0.026 0.025 0.015 0.026
525 0.014 0.013 0.013 0.014 0.014 0.015 0.017 0.016 0.024 0.023 0.016 0.024
575 0.014 0.013 0.013 0.014 0.014 0.015 0.016 0.015 0.017 0.016 0.015 0.017
625 0.014 0.013 0.013 0.014 0.014 0.015 0.016 0.015 0.018 0.018 0.015 0.018
675 0.013 0.013 0.013 0.013 0.014 0.014 0.015 0.014 0.017 0.017 0.014 0.017
725 0.013 0.012 0.013 0.013 0.013 0.014 0.014 0.013 0.016 0.017 0.014 0.017
775 0.013 0.012 0.013 0.013 0.013 0.014 0.014 0.014 0.016 0.016 0.014 0.016
825 0.014 0.012 0.013 0.013 0.014 0.014 0.015 0.015 0.016 0.016 0.015 0.016
875 0.013 0.013 0.014 0.015 0.015 0.015 0.015 0.015 0.016 0.017 0.016 0.017
925 0.014 0.014 0.014 0.014 0.014 0.015 0.015 0.014 0.015 0.016 0.015 0.016
975 0.014 0.013 0.013 0.013 0.014 0.014 0.014 0.014 0.015 0.014 0.013 0.015 1025 0.014 0.012 0.013 0.013 0.013 0.014 0.014 0.013 0.014 0.014 0.013 0.014
1075 0.014 0.012 0.013 0.013 0.013 0.013 0.013 0.013 0.014 0.014 0.013 0.014
1125 0.014 0.012 0.015 0.016 0.016 0.016 0.017 0.017 0.021 0.020 0.016 0.021
1175 0.014 0.019 0.018 0.018 0.019 0.020 0.021 0.021 0.027 0.026 0.018 0.027
1225 0.015 0.013 0.015 0.016 0.016 0.016 0.016 0.016 0.020 0.019 0.015 0.020
1275 0.014 0.019 0.018 0.018 0.018 0.019 0.019 0.020 0.025 0.024 0.016 0.025
1325 0.014 0.012 0.013 0.013 0.013 0.013 0.013 0.013 0.013 0.013 0.012 0.014
1375 0.014 0.012 0.013 0.013 0.013 0.012 0.013 0.012 0.013 0.020 0.012 0.020
1425 0.014 0.012 0.013 0.013 0.013 0.013 0.013 0.013 0.019 0.031 0.013 0.031
1475 0.016 0.013 0.013 0.013 0.013 0.013 0.013 0.013 0.026 0.023 0.015 0.026
1525 0.014 0.012 0.013 0.013 0.013 0.013 0.013 0.013 0.019 0.028 0.013 0.028
1575 0.016 0.013 0.013 0.013 0.013 0.013 0.013 0.012 0.024 0.012 0.012 0.024
1625 0.013 0.012 0.012 0.012 0.013 0.012 0.012 0.011 0.012 0.011 0.011 0.013
1675 0.014 0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.015 0.011 0.015
1725 0.013 0.012 0.013 0.013 0.013 0.013 0.013 0.013 0.015 0.023 0.014 0.023
1775 0.017 0.013 0.014 0.014 0.014 0.014 0.014 0.014 0.017 0.021 0.016 0.021
1825 0.013 0.013 0.014 0.014 0.014 0.014 0.013 0.012 0.012 0.018 0.011 0.018
1875 0.013 0.013 0.013 0.013 0.013 0.012 0.013 0.012 0.012 0.011 0.012 0.013
1925 0.013 0.012 0.012 0.012 0.013 0.012 0.012 0.012 0.011 0.011 0.011 0.013
1975 0.013 0.012 0.012 0.013 0.013 0.012 0.012 0.012 0.011 0.011 0.012 0.013
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 14 of 28
Rev. 1
FGW-TG3+SP1
3.2.7 Höhere Frequenzen / Higher Frequencies components
Pbin (%) 0 10 20 30 40 50 60 70 80 90 100 MAX (%) F [kHz] Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%) Ih(%)
2.1 0.070 0.081 0.083 0.083 0.084 0.078 0.081 0.078 0.073 0.074 0.077 0.084
2.3 0.055 0.059 0.059 0.061 0.061 0.055 0.056 0.056 0.052 0.055 0.057 0.061
2.5 0.049 0.053 0.053 0.056 0.056 0.052 0.053 0.053 0.050 0.054 0.064 0.064
2.7 0.054 0.057 0.059 0.059 0.061 0.056 0.058 0.059 0.056 0.060 0.062 0.062
2.9 0.043 0.051 0.048 0.053 0.055 0.050 0.052 0.055 0.054 0.055 0.052 0.055
3.1 0.044 0.041 0.036 0.038 0.038 0.036 0.036 0.035 0.037 0.040 0.045 0.045
3.3 0.047 0.049 0.048 0.049 0.051 0.047 0.047 0.047 0.045 0.048 0.052 0.052
3.5 0.030 0.041 0.040 0.040 0.041 0.039 0.040 0.040 0.037 0.037 0.037 0.041
3.7 0.028 0.037 0.036 0.036 0.036 0.034 0.035 0.038 0.042 0.045 0.047 0.047
3.9 0.027 0.038 0.037 0.037 0.036 0.033 0.034 0.034 0.033 0.036 0.036 0.038
4.1 0.024 0.035 0.036 0.036 0.036 0.034 0.034 0.036 0.037 0.032 0.030 0.037
4.3 0.024 0.033 0.033 0.032 0.033 0.031 0.031 0.030 0.034 0.035 0.033 0.035
4.5 0.068 0.033 0.034 0.034 0.034 0.032 0.032 0.031 0.029 0.027 0.024 0.068
4.7 0.025 0.038 0.038 0.038 0.038 0.036 0.035 0.035 0.034 0.033 0.032 0.038
4.9 0.029 0.054 0.054 0.054 0.055 0.054 0.054 0.053 0.053 0.053 0.054 0.055
5.1 0.023 0.051 0.053 0.053 0.052 0.049 0.047 0.047 0.045 0.044 0.046 0.053
5.3 0.023 0.040 0.040 0.041 0.041 0.038 0.037 0.037 0.036 0.035 0.031 0.041
5.5 0.028 0.046 0.047 0.048 0.047 0.045 0.043 0.039 0.037 0.035 0.033 0.048
5.7 0.029 0.055 0.056 0.056 0.055 0.053 0.051 0.050 0.048 0.045 0.040 0.056
5.9 0.032 0.065 0.065 0.065 0.063 0.059 0.057 0.054 0.049 0.044 0.040 0.065
6.1 0.033 0.077 0.077 0.077 0.076 0.071 0.069 0.062 0.055 0.051 0.048 0.077
6.3 0.031 0.093 0.090 0.090 0.089 0.083 0.082 0.079 0.074 0.068 0.061 0.093
6.5 0.025 0.087 0.085 0.085 0.083 0.076 0.075 0.074 0.069 0.067 0.062 0.087
6.7 0.019 0.088 0.085 0.086 0.085 0.079 0.082 0.081 0.076 0.077 0.076 0.088
6.9 0.015 0.085 0.083 0.084 0.085 0.084 0.096 0.094 0.091 0.089 0.083 0.096
7.1 0.016 0.062 0.061 0.062 0.063 0.063 0.073 0.082 0.080 0.078 0.070 0.082
7.3 0.015 0.047 0.047 0.046 0.047 0.046 0.052 0.064 0.069 0.076 0.078 0.078
7.5 0.016 0.040 0.040 0.041 0.041 0.040 0.045 0.054 0.060 0.064 0.065 0.065
7.7 0.012 0.031 0.031 0.031 0.032 0.031 0.034 0.038 0.045 0.052 0.054 0.054
7.9 0.023 0.029 0.029 0.030 0.030 0.029 0.032 0.036 0.042 0.052 0.052 0.052
8.1 0.011 0.025 0.026 0.026 0.027 0.026 0.029 0.032 0.036 0.045 0.042 0.045
8.3 0.010 0.024 0.024 0.024 0.024 0.024 0.025 0.027 0.029 0.032 0.040 0.040
8.5 0.008 0.023 0.023 0.024 0.024 0.025 0.025 0.027 0.031 0.034 0.038 0.038
8.7 0.005 0.042 0.042 0.041 0.041 0.040 0.040 0.040 0.040 0.039 0.039 0.042
8.9 0.004 0.073 0.073 0.074 0.075 0.076 0.079 0.080 0.082 0.077 0.065 0.082
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 15 of 28
Rev. 1
FGW-TG3+SP1
3.3 Grid Control Capability 3.3.1 Wirkleistungs einspeisung in Abhängigkeit der Netfrequenz / Active power vs frequency
Überfrequenz / overfrequency
Mittlerer Gradient der Wirkleistung sum Zeitpunkt der Frequenzüberhöhung / Mean power gradient at overfrequency
mittl. Gradient / mean gradient 39.6 % PM/Hz
Max. Einschwingzeit / Max. Settling time
0.6 s
Gradient der Wirkleistung nach Rückkehr aus Überfrequenz / Power gradient after recovery of over frequency
mittl. Gradient / mean gradient 8.9 %Pn/Hz max. Gradient / max. gradient 8.9 %Pn/Hz
Unterfrequenz / underfrequency
Mittlerer Gradient der Wirkleistung sum Zeitpunkt der Frequenzunterschreitung / Mean power gradient at underfrequency
mittl. Gradient / mean gradient 41.2 % PM/Hz
Max. Einschwingzeit / Max. Settling time
0.8 s
Gradient der Wirkleistung nach Rückkehr aus Unterfrequenz / Power gradient after recovery of under frequency
mittl. Gradient / mean gradient 8.9 %Pn/Hz max. Gradient / max. gradient 8.9 %Pn/Hz
Die EZE kann mit reduzierter Leistung betrieben werden. / The unit is able to run at reduced power
Ja / Yes Nein / No
Maximale Sollwertabweichung der Wirkleistung Max. deviation of power setting
Überschreitung / Exceeding 1.407 kW
Unterschreitung / Undercut 0.321 kW
Trennung vom Nets bei Wirkleistungssollwertvorgabe von: Disconnection from the grid at external active power setpoints at:
-- % Pn No disconnection is recorded.
Operation at 0%Pn is evidenced.
Einschwingzeit der Leistung für einen Sollwertsprung mit minimalem Gradienten / Response time of the power output after a change in setpoint with minimal gradient
P0 -> Pmin Zeit / time : 44.76 s
Gradient: 0.33 % Pn / s
Pmin -> P0 Zeit / time : 44.74 s
Gradient: 0.33 % Pn / s
Einschwingzeit der Leistung für einen Sollwertsprung mit maximalem Gradienten / Response time of the power output after a change in setpoint with maximum gradient
P0 -> Pmin Zeit / time : 112.72 s
Gradient: 0.67 % Pn / s
Pmin -> P0 Zeit / time : 112.18 s
Gradient: 0.66 % Pn / s
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 16 of 28
Rev. 1
FGW-TG3+SP1
3.3.2 Blindleistungbereitstellung / Provision of reactive power
Blindleistungsregelung im Normalbetrieb und maximaler Blindleistungstellbreich / Control of reactive power in normal operation and maximum reactive power range
P/Pn Qind Q0 Qkap P/Pn Qind Q0 Qkap
0% 66.433 1.185 -66.253 60% 65.494 1.813 -66.673
10% 66.308 1.255 -66.331 70% 65.317 2.027 -66.745
20% 66.081 1.235 -66.404 80% 65.249 2.288 -66.940
30% 65.920 1.262 -66.481 90% 47.272 2.573 -47.216
40% 65.776 1.392 -66.553 100% 1.877 2.854 -1.883
50% 65.659 1.589 -66.603
Q in kVAr.
Arbitspunkte des spannungsanhängigen P-Q Diagramms / Working points of the voltage dependent P-Q diagram
AP / WP U/Un in % P/Pn in % Q in kVAr
See measured points and results in the following pages of this annex
Blindleistungsregelung durch Sollwertvorgabe / Control of reactive power through set point signal
Verschiebungsfaktor / power factor Blindleistung / reactive power
Pbin bei / at Qmax Q range at 50 %Pn is ± 60 %Pn
Längste Einschwingzeit /Longest response time
Parameter Einschwingzeit / settling time
T < 6 s 4.2 s
Standardzeit / standard time --
T < 60 s 37.4 s
Einstellgenauigkeit des Verschiebungsfaktors bzw. Blindleistung / Positioning accuracy of power factor or reactive power
Sollwert / setpoint Istwert / measured value
33.000 kVAr 33.346 kVAr
0 kVA -2.058 kVAr
-33.000 kVA -32.972 kVAr
Anmerkung / remark Soweit Q(U) und Q(P)- Regelung wurde, sind diese im Prüfbericht hinterlegt /
See Q(U) and Q(P) in test report
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 17 of 28
Rev. 1
FGW-TG3+SP1
In following charts, they are offered main results after performed tests included in the FGW TG3 test report.
Q = 0 kVAr: Active Power over Reactive Power
Semicircular Curve (100%Un): Active Power over Reactive Power
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 18 of 28
Rev. 1
FGW-TG3+SP1
Semicircular Curve (90%Un): Active Power over Reactive Power
Semicircular Curve (110%Un): Active Power over Reactive Power
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 19 of 28
Rev. 1
FGW-TG3+SP1
The tables below show measured values for each power step tested to verify the voltage-dependent PQ diagram at different ambient temperature conditions:
Semicircular Curve (U = 100% Un) – Inductive
P Desired (%Pn)
P measured
(kW)
Q measured
(kVAr)
S measured (kVA)
S deviation
(kVA)
Power Factor (cos φ)
VAC + (V) Number of
records
0 2.006 66.433 66.463 -43.537 0.030 399.2 900
10 11.338 66.308 67.270 -42.730 0.169 399.3 900
20 22.321 66.081 69.749 -40.251 0.320 399.4 900
30 33.243 65.920 73.828 -36.172 0.450 399.5 900
40 44.157 65.776 79.224 -30.776 0.557 399.6 900
50 55.068 65.659 85.695 -24.305 0.643 399.8 900
60 66.283 65.494 93.182 -16.818 0.711 399.9 900
70 77.135 65.317 101.075 -8.925 0.763 400.0 900
80 88.198 65.249 109.711 -0.289 0.804 400.2 900
90 98.973 47.272 109.683 -0.317 0.902 400.5 900
100 109.943 1.877 109.959 -0.041 1.000 401.4 900
Semicircular Curve (U = 100% Un) – Capacitive
P Desired (%Pn)
P measured
(kW)
Q measured
(kVAr)
S measured (kVA)
S deviation
(kVA)
Power Factor (cos φ)
VAC + (V) Number of
records
0 0.722 -66.253 66.257 -43.743 0.011 401.0 900
10 11.585 -66.331 67.335 -42.665 0.172 401.1 900
20 22.573 -66.404 70.136 -39.864 0.322 401.3 900
30 33.528 -66.481 74.457 -35.543 0.450 401.4 900
40 44.461 -66.553 80.038 -29.962 0.556 401.5 900
50 55.405 -66.603 86.635 -23.365 0.640 401.6 900
60 66.319 -66.673 94.040 -15.960 0.705 401.8 900
70 77.297 -66.745 102.126 -7.874 0.757 401.9 900
80 87.397 -66.940 110.087 0.087 0.794 402.0 900
90 99.353 -47.216 110.002 0.002 0.903 401.9 900
100 109.846 -1.883 109.862 -0.138 1.000 401.4 900
Note: Test performed in active power priority mode. Maximum apparent power that can be reached corresponds to 100%Pn, approximately. Deviations are calculated in relation to this expected semicircular value.
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 20 of 28
Rev. 1
FGW-TG3+SP1
Semicircular Curve (U = 90% Un) – Inductive
P Desired (%Pn)
P measured
(kW)
Q measured
(kVAr)
S measured (kVA) (*)
S deviation
(kVA)
Power Factor (cos φ)
VAC + (V) Number of
records
0 4.360 66.211 66.355 -32.645 0.066 360.4 1800
10 11.380 65.983 66.957 -32.043 0.170 360.5 1800
20 22.246 65.588 69.258 -29.742 0.321 360.5 1800
30 33.241 66.698 74.522 -24.478 0.446 361.0 1800
40 43.958 66.762 79.935 -19.065 0.550 361.0 1800
50 54.960 66.892 86.574 -12.426 0.635 361.1 1800
60 66.013 66.976 94.040 -4.960 0.702 361.2 1800
70 77.566 62.143 99.389 0.389 0.780 361.2 1800
80 88.482 45.135 99.329 0.329 0.891 360.9 1800
90 99.092 3.481 99.153 0.153 0.999 360.2 1800
100(*) 99.124 1.773 99.140 0.140 1.000 360.2 1800
Semicircular Curve (U = 90% Un) – Capacitive
P Desired (%Pn)
P measured
(kW)
Q measured
(kVAr)
S measured (kVA) (*)
S deviation
(kVA)
Power Factor (cos φ)
VAC + (V) Number of
records
0 0.771 -66.502 66.506 -32.494 0.012 357.9 1800
10 11.044 -66.784 67.691 -31.309 0.163 358.0 1800
20 22.041 -66.105 69.683 -29.317 0.316 358.1 1800
30 32.971 -66.115 73.880 -25.120 0.446 358.2 1800
40 43.909 -66.107 79.361 -19.639 0.553 358.3 1800
50 55.328 -66.162 86.247 -12.753 0.642 358.4 1800
60 66.161 -66.138 93.550 -5.450 0.707 358.5 1800
70 77.213 -61.542 98.738 -0.262 0.782 358.6 1800
80 88.166 -44.693 98.847 -0.153 0.892 359.0 1800
90 98.981 -3.252 99.034 0.034 0.999 359.9 1800
100(*) 98.972 -3.252 99.025 0.025 0.999 359.9 1800
(*) Test performed in active power priority mode. Working at 90% Un the inverter does not reach the maximum 100% Sn due to the current limitation function. Maximum apparent power that can be reached corresponds to 90%Sn, approximately. Deviations are calculated in relation to this expected semicircular value.
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 21 of 28
Rev. 1
FGW-TG3+SP1
Semicircular Curve (U = 110% Un) – Inductive
P Desired (%Pn)
P measured
(kW)
Q measured
(kVAr)
S measured
(kVA)
S deviation
(kVA)
Power Factor (cos φ)
VAC + (V) Number of
records
0 1.756 66.389 66.413 -43.587 0.026 439.3 1800
10 11.388 66.249 67.220 -42.780 0.169 439.4 1800
20 22.425 66.086 69.787 -40.213 0.321 439.5 1800
30 33.475 65.872 73.890 -36.110 0.453 439.6 1800
40 44.536 65.723 79.391 -30.609 0.561 439.8 1800
50 55.603 65.573 85.974 -24.026 0.647 439.9 1800
60 66.699 65.438 93.440 -16.560 0.714 440.0 1800
70 77.308 65.304 101.198 -8.802 0.764 440.1 1800
80 88.670 65.275 110.106 0.106 0.805 440.2 1800
90 98.970 48.022 110.005 0.005 0.900 440.5 1800
100 110.081 2.248 110.104 0.104 1.000 441.3 1800
Semicircular Curve (U = 110% Un) – Capacitive
P Desired (%Pn)
P measured
(kW)
Q measured
(kVAr)
S measured (kVA) (*)
S deviation
(kVA)
Power Factor (cos φ)
VAC + (V) Number of
records
0 0.320 -66.273 66.274 -43.726 0.005 441.0 1800
10 11.598 -66.355 67.361 -42.639 0.172 441.1 1800
20 22.688 -66.452 70.218 -39.782 0.323 441.2 1800
30 33.767 -66.550 74.627 -35.373 0.452 441.4 1800
40 44.866 -66.618 80.318 -29.682 0.559 441.5 1800
50 55.680 -66.708 86.892 -23.108 0.641 441.6 1800
60 66.772 -66.851 94.486 -15.514 0.707 441.7 1800
70 77.618 -66.945 102.500 -7.500 0.757 441.8 1800
80 88.348 -67.158 110.976 0.976 0.796 441.9 1800
90 99.636 -48.039 110.612 0.612 0.901 441.8 1800
100 110.082 -2.306 110.106 0.106 1.000 441.3 1800
(*) Test performed in active power priority mode. Maximum apparent power that can be reached corresponds to 100%Sn, approximately. Deviations are calculated in relation to this expected semicircular value.
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 22 of 28
Rev. 1
FGW-TG3+SP1
3.4 Protection system
3.4.1 Trennung der EZE vom Netz / Cut-off from grid
Die Überprüfung der Gesamtwirkungskette führte zu einer erfolgreichen Abschaltung. The test of the whole trip circuit led to a successful shut down
Einstellwert Setting
In pu oder/or [Hz]
Auslösewert / Release value
In pu oder/or [Hz]
Abschaltzeit / Disconnection time
[ms] Rückfallverhältnis Disengaging ratio
Schwelle / value
Zelt / time
Min. Max. Min. Max.
Spannungssteigerungsschutz/ Overvoltage protection: U>
1.000 180.00 s 1.006 1.010 180.00 s 180.00 s ≥0.98 <0.98
1.300 0.040 s 1.300 1.303 0.018 s 0.047 s
Spannungssteigerungsschutz/ Overvoltage protection: U>>
1.000 180.00 s 1.006 1.008 180.00 s 180.00 s ---
1.300 0.040 s 1.297 1.306 0.018 s 0.047 s
Spannungsrückgangsschutz/ Undervoltage protection: U<
0.100 0.040 s 0.101 0.110 0.022 s 0.034 s ≤1.02 >1.02
1.000 2.500 s 0.995 0.996 2.490 s 2.498 s
Spannungsrückgangsschutz/ Undervoltage protection: U<<
0.100 0.040 s 0.100 0.108 0.023 s 0.047 s ≤1.02 >1.02
1.000 0.900 s 0.995 0.996 0.878 s 0.900 s
Frequenzsteigerungsschutz/ Overfrequency protection: F>
50.00 5.000 s 50.05 4.980 s ---
55.00 0.040 s 54.99 0.045 s
Frequenzsteigerungsschutz/ Overfrequency protection: F>>
50.00 5.000 s 50.04 4.956 s ---
55.00 0.040 s 54.99 0.047 s
Frequenzrückgangsschutz/ Underfrequency protection: F<
45.00 0.040 s 45.00 0.038 s ---
50.00 0.100 s 49.95 0.119 s
Eigenzeit der Abschalteinheit / Operating time of a circuit breaker:
aus Messung by measurement
aus Prüfzertifikat by test certificate
According to the point 4.4.1 of the test report no. 2221/0017, the measured circuit breaker operating time is 2.6 ms
The PGU can either be assembled with following alternatives of the circuit breaker:
- Alternative 1: Power Relay CHAR-112A200 with: - Declared operate time given by the supplier: 35 ms as maximum. - Declared release time given by the supplier: 30 ms as maximum.
- Alternative 2: Power Relay 511ZP-1AD-F-C M06 with:
- Declared operate time given by the supplier: 50 ms as maximum. - Declared release time given by the supplier: 30 ms as maximum.
See next pages.
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 23 of 28
Rev. 1
FGW-TG3+SP1
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 24 of 28
Rev. 1
FGW-TG3+SP1
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 25 of 28
Rev. 1
FGW-TG3+SP1
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 26 of 28
Rev. 1
FGW-TG3+SP1
3.4.2 Zuschaltbedingungen / Cut-in conditions
Since this is optional testing, this test has not been performed as is an optional measurement according to point 4.5.1.1 of the standard.
3.4.3 Zuschaltbedingungen nach Auslösung des Entkupplungsschutzes / Cut-in conditions after tripping of protection
• For VDE-AR-N 4110: 2018-11
Bereich / range In pu order/ or [Hz]
Zuschaltung erfolgte im angegebenen Bereich / cut in occurred within the given range
Spannung / Voltage: 0.90 – 1.10 nein / no ja / yes
Frequenz / Frequency: 47.5 – 50.2 nein / no ja / yes
• For VDE-AR-N 4120: 2018-11
Bereich / range In pu order/ or [Hz]
Zuschaltung erfolgte im angegebenen Bereich / cut in occurred within the given range
Spannung / Voltage: 0.90 – 1.10 nein / no ja / yes
Frequenz / Frequency: 47.5 – 51.0 nein / no ja / yes
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 27 of 28
Rev. 1
FGW-TG3+SP1
3.4.4 Zuschaltbedingungen nach Auslösung des Entkupplungsschutzes / Cut-in conditions after
tripping of protection
Bereich / range In pu order/ or [Hz]
Zuschaltung erfolgte im angegebenen Bereich cut in occurred within the given range
Unterspannung / Undervoltage:
> 0.95 nein / no ja / yes
Unterfrequenz / Underfrequency:
≥ 49.9 nein / no ja / yes
Überfrequenz / Overfrequency:
≤ 50.1 nein / no ja / yes
As evidenced in the FGW TG3 test report, the certified unit follows a ramp gradient inside of the range 33%Pn/s – 66%Pn/s after the reconnection occurs.
Graphical representation of the test over time
Report N. 2221 / 0017 – E1 (Extract from test results)
Page 28 of 28
Rev. 1
FGW-TG3+SP1
3.5 Response during grid faults The compliance with these requirements including all calculations defined in the FGW TR3 standard is stated in the attachement to the test report:
- 2221 / 0017-Att1: FGW-TG3: Grid Fault Tests Results
--- END OF THE EXTRACT OF THE TEST REPORT ---