COPY RECEIV/:D DATE: S/ 1 /1 f TIME: 3 ! ~d'~ FACILITIES COMMITTEE IVIINUTES . -WNClERCS <>ACE February 28, 2018 Chatlield-LoPresti School 7:00p,m. COMMITTEE MEMBERS IN ATTENDANCE: Jim Garofolo Pete Kubik Fred Stanek COMMITTEE MEMBERS ABSENT: OTHERS IN ATTENDANCE: I. CALL TO ORDER Rick Belden, Assistant Superintendent Joe Falzone, Facilities Manager Pat Boyle, Board Clerk A Mr. Belden called the meeting to order with the Pledge of Allegiance 7:10 p.m. II. ELECTION OF CHAIRPERSON Mr. Garofolo nominated Mr. Kubik to be the Chairperson. All were in favor and Mr. Kubik was appointed chairperson of the Facilities Committee. Ill. PUBLIC COMMENT None IV. DISCUSSION AND POSSIBLE ACTION A. Health Status 1. Bungay School a. Oil Spill-Root Cause and Corrective Action Mr. Falzone reviewed recent minor oil spill. The oil spill may have been caused by a defective vent pipe, which will be addressed when the weather warms up enough to inspect the oil tank and pipe. The contracted oil company has p~id all expenses to remediate the effects of the spill and subsequent deliveries have been monitored by a Seymour School employee. Mr. Falzone indicated that the oil tank would also be inspected and sludge removal would be done during the summer. Bungay School is the oldest building in district at this time and is need of major repairs. Major areas of concern are floor tiles, roof leaks, paving issues and heating issues including the need for a new boiler. Mr. Belden indicated that we are going to need to address these issues. The district will either have to start putting significant operating expense funds into addressing these issues or we can go to the town Permanent Building Committee as well as the First Selectman to start talks on a "renovate as new" capital building project. Mr. Kubik says he will broach the issue with the town. He would also like to do a walkthrough to see for himself the areas of concern. 2. Chatlield-LoPresti School The only area of concern with this school is the Snow Melt system, which is now in the hands of the town attorney, 3. Seymour Middle School The floor tiles in this school are reaching end of life and are starting to need replacement. There are also several roof leaks and the roof is reaching end of life. ------------ "IT'S ALL ABOUT STUDENT LEARNING" -"--,---------
Transcript
Page 1: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

COPY RECEIV/:D DATE: S/ 1 /1 f TIME: 3 ! ~d'~

FACILITIES COMMITTEE IVIINUTES .

-WNClERCS <>ACE

February 28, 2018 Chatlield-LoPresti School 7:00p,m. COMMITTEE MEMBERS IN ATTENDANCE: Jim Garofolo

Pete Kubik Fred Stanek COMMITTEE MEMBERS ABSENT:

OTHERS IN ATTENDANCE:

I. CALL TO ORDER

Rick Belden, Assistant Superintendent Joe Falzone, Facilities Manager Pat Boyle, Board Clerk

A Mr. Belden called the meeting to order with the Pledge of Allegiance 7:10 p.m. II. ELECTION OF CHAIRPERSON

Mr. Garofolo nominated Mr. Kubik to be the Chairperson. All were in favor and Mr. Kubik was appointed chairperson of the Facilities Committee.

Ill. PUBLIC COMMENT None

IV. DISCUSSION AND POSSIBLE ACTION A. Health Status

1. Bungay School a. Oil Spill-Root Cause and Corrective Action

Mr. Falzone reviewed recent minor oil spill. The oil spill may have been caused by a defective vent pipe, which will be addressed when the weather warms up enough to inspect the oil tank and pipe. The contracted oil company has p~id all expenses to remediate the effects of the spill and subsequent deliveries have been monitored by a Seymour School employee. Mr. Falzone indicated that the oil tank would also be inspected and sludge removal would be done during the summer. Bungay School is the oldest building in district at this time and is need of major repairs. Major areas of concern are floor tiles, roof leaks, paving issues and heating issues including the need for a new boiler. Mr. Belden indicated that we are going to need to address these issues. The district will either have to start putting significant operating expense funds into addressing these issues or we can go to the town Permanent Building Committee as well as the First Selectman to start talks on a "renovate as new" capital building project. Mr. Kubik says he will broach the issue with the town. He would also like to do a walkthrough to see for himself the areas of concern.

2. Chatlield-LoPresti School The only area of concern with this school is the Snow Melt system, which is now in the hands of the town attorney,

3. Seymour Middle School The floor tiles in this school are reaching end of life and are starting to need replacement. There are also several roof leaks and the roof is reaching end of life.

------------ "IT'S ALL ABOUT STUDENT LEARNING" -"--,---------

Page 2: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

4. Seymour High School a. Boilers

The two boilers had eight sections replaced at a cost of $35,000 during the summer of 2017. The water returning to the boilers was too cold resulting in cracking. It was decided to call in an outside company to see if there are any solutions to this issue (i.e. insulating pipes, mixing value, and a system to monitor the return water temperature.)

b. Pool The pool has a dedicated boiler which runs 24/7 and is not energy efficient due to the length of the pipe run. Mr. Falzone reco·mmended the possibility of adding an auxiliary pump.

C. OCR Status Update Mr. Belden distributed a copy of our Voluntary Corrective Action Plan with the areas that we are continuing to address. Mr. Belden indicated we are chipping away at the open issues and Dr. Wood (State Consultant) is satisfied with the work that is being done. An annual report is prepared for the State OCR department with the status of the remediation efforts. Mr. Belden noted that there is significant work to be done in the locker room/gym areas if a student/staff member requires ADA accessibility.

B. Planned/Required Maintenance and Updates 1. Bungay School

Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area '

2. Chatfield-LoPresti School Parking lot striping, recoat gym floor

3. Seymour Middle School Parking lot striping, locker repair, recoat gym floor, paving in drop off area, bathroom partition replacement, install new flooring

4. Seymour High School Parking lot striping, locker repairs, recoat gym floor, replace state curtain, OCR Repairs, replace flooring The items above are the areas proposed to be repaired and maintained. These items were identified in the supporting detail for the 2018-19 budget.

C. Needed Equipment and Supplies The following equipment is budgeted for this 2018-19: 2 riding floor machines (one at CLS and one at SMS). Mr. Belden indicated that funding has been maintained in our annual operating budgets to replace custodial equipment in a planned manner.

D. Reviewof2017 Fire Marshall School Inspections Mr. Falzone provided a copy of the Fire Marshall's inspection report for 2017 (attached), along with the work performed to address the cited items. There are no outstanding issues.

fie; REPORTS A. Chairman's Report: None B. Superintendent's Report: Mr. Belden provided a copy of the Asbestos Re-Inspection report filed with the

State of Connecticut. This inspection is required every three years and there were no issues cited that require any remediation in the report.

-2-

--------~~· "IT'S ALL ABOUT STUDENT LEAJlNING" ~~-~------'-'

Page 3: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

VI. PUBLIC COMMENT None

VII. ADJOURNMENT MOTION: (Mr. Garofolo /sec. Mr. Kubik) to adjourn the meeting at 8:20p.m.

AFFIRMATIVE: Mr. Garofolo, Mr. Kubik SO VOTED

Submitted by: Pat Boyle

~~-'-'--~--'-~-- "IT'S ALL ABOUT STUDENT LEARNING" -~-~-"'-~-----'-

Page 4: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

I

I t

STATE OF CONNECTICUT

Raul Pino, M.D., M.P .H. Commissioner

DEPARTMENT OF PUBLIC HEALTH

Dannel P. Malloy Governor

Nancy Wyman Lt.Governor

LOCAL EDUCATION AGENCY (LEA) MANDATORY REPORT DOCUMENTATION OF THREE-YEAR REINSPECTION FOR ASBESTOS-CONTAINING MATERIALS

INSTRUCTIONS: Form must be typed or prepared electronically. Digital signatures are acceptable. The LEA may submit the form electronically to [email protected] or mall to the Department of Public Health at 410 Capitol Avenue, MS #51 AIR., PO Bax 340308, Hartford, CT, 06134-0308

Sections 1·2: Management Planner (MP) shall complete and submit form electronically to the LEA Designated Person (DP). If MP recommends a response action, other than operations and maintenance (O&MJ and/or Preventive Measures, submit Attachment A, detailing the specific recommendations for each school.

Section 3: Local education agency (LEA) shall complete and submit to the DPH within thirty-tao) days of the date al the relnspection. The DP must 11st the course name, dates and hours of training received to carry out the LEA's duties. If the DP satisfied training requirement by reading the DP's Self Study Guide, specify the dates and number of hours It was read. Upon submittal to the DPH, the DP must place a copy of the fonm and Attachment A, If applicable, in the asbestos management plan for eaeh school, and send a completed copy of the form to the MP.

SECTION 1: ,', '', ' ''

LEA Street Address Cft\'andZ11>code

Town of Seymour Board of Education 98 Bank Street #1 Seymour, 06483 Initial Approval:

Unknown Management Planner

Michael Difabio lnspector1

Michael DiFabio lnspector2

lnspector3 '

-~-

. -- "" -- . . Last 3-Year Re Inspection Date/s Current RelnspecUon Date/s:

','

November 3, 2014 ', January 25--31, 2017 Lie#! Ucense Exp. Accred EJcp. Date Signature ..

. :· 000340 12/31/2018 6/23/2018 " . ..,;._,_._

Lie#! Ucensel!xp.1 Accred Elcp. Date 1 :srgnatur(i '

000340 12/31/2018 6/23/2018 "'" Llc#J UcenseExp.2 Accred Exp, Date 2 s1gifafure z

.... (,""· ...

' Uc #J Lite11se Exp. 3 Accred Exp. Date 3 Slitia!• re 3

,,,,, ,,, '

Phone: (860) 509-7367 • Fax: (860) S09-7378 410 Capitol Avenue, MS #SlAIR-P.O. Box340308

Hartford, Co1U1ect!cut 0613~308 www.at.gov/dph

Affirmative Acrton/Equa/ Opportunity Employer

'',

,,

,,

,,,

,,,

',,,, .

',

'

-

[

Page 5: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

I

I I I I

I

I I I

I I I

If the MP only recommends O&M {less than 3 square feet or 3 linear feet) or preventive measures, Section 2 and Appendix 1 are not applicable. MP recommendations other than O&M, please check the column below for each school. If MP recommends lnltlal clean Ing (IC) or addltlonal cleaning {AC}, as a result of the inspection findings, please note with IC or AC or leave blank.

SECTION 2 (If space Is Inadequate, please attach additional pages)

Schoel Name Address MP Cleaning Recommendatfons (IC or AC)

Seymour Board ol Education Office 98 Bank Street, Seymour CT YesD Nol!!

Bungay Elementary School 35 Bungay Road, Seymour CT YesO Nol!!

Seymour High School 2 Botsford Road, Seymour CT YesO Nol!!

Seymour Middle School 211 Mountain Road, Seymour CT YesD Nol!! Chatfield-LaPresJI Elemenlary School 51 Skokorat Street, Seymour CT YesD Noli!

YesO NoO

YesD NoO

YesD NoO

YesO NoO

YesO NoO

YesO NoO

YesD NoO

SECTION3

Superintendent/Head of School Designated Person DP Training Course {Name, Date, #of Hours

Michael Wilson Joe Falzone CT DPH.'AHERA sa1r Sludy Guldllfl ,2017/.clhni

Designated Person Phone Designated Person Cell Deslsnated Person Email

203-888-4513 x1221 203-893-0255 [email protected]

I understand my responslbtlltles as the designated person, and have reviewed the management planner's recommendations. I cert!Fy that the general local education agency responslbtlltles, as stipulated by Section 19a-333-2 of the Regulations of ConnectlcutState-A•encles, have been (or wlll be) met.

--

'::?-(2-I 18 ....,,_~~- --------Date

Three Year RelnspectJan Farm• rev. 11/21/2016

j

i ' l

I

Page 6: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

:ertified Mail Return Receipt#:

:eymour Middle School oeseph Falzone 11 Mountain Road leymour, CT 06483

Office Of The Fire Marshal

'Town of Seymour l First Street

Seymour, Connecticut 06483

Wednesday, August 16, 2017

CONNECTICUT STATE FIRE SAFETY CODE ABATEMENT ORDER OF FIRE/LIFE SAFETY 1:I!U,ARDS

>ear Mr. Falzone,

>n 8/14/2017, at approximat~ly 9:45 am hours, an inspection was conducted of the premises located at 11 Mountain Road, Seymour, Connecticut for the purpose of compliance with Connecticut Fire Safety Code and the applicable ,ferenced applicable standards, adopted pursuant to the Connecticut General Statutes §29-292 and §29-293. The Code and said tandards are available for your inspection at this office.

'he violation of the code found on the date ofinspection are listed on the attached inspection report.

'ou are hereby ordered to take the proper corrective action to remove or remedy all the listed violations within thirty (30) days :om the day that this notice is received, unless otherwise noted on the attached inspection report.

f you believe that compliance with the code will impose an unreasonable hardship, and that alternative methods of achieving an quivalent level of safety could be attained, you may request, in writing, a modification of the requirements of said Code as outlined 1 the Connecticut General Statues § 29-296. If you believe compliance will take more.than that specified, you may request an xtension of time prior to the expiration of the thirty (30) day period, unless otherwise noted on the attached inspection report. Sample ,rms for application for modification and extension of time for compliance are available from this office. In addition you have the ight to appeal this order pursuant to Connecticut General Statues §29-306 for a period of not more than thirty (30) days from receipt.

'Jans/specifications for work to be done shall be submitted to this office prior to the commencement of any construction. This review fall plans/specifications would avoid urmecessary expense that could result from non-complying changes. Please note that the orrection of certain violations may require proper permits and approval from the building official and other local agencies prior to ny construction.

'his is the only order you will receive. This office will conduct a re-inspection of the premises to determine compliance with this rder after the expiration of the thirty-day (30) or the time period noted on the inspection report. Your failure to comply with this rder within the period specified as determined by said re-inspection constitutes your failure to comply with the Connecticut State 'ire Safety Code which may subject you to criminal prosecution as prescribed by Connecticut General Statues §29-306 with enalties ofa1ii)e not less than two hundred dollars ($200.) nor more than one thousand dollars ($1000.00) or imprisonment ofup to ix months or both, as prescribed in Connecticut General Statues §29-295. Non-compliance may result in a civil proceeding against ou as authorized in Connecticut General Statues § 29-306

'his Office is looking forward to working with you in the interest of fire and life safety for the community and awaits your timely ~sponse to this matter.

nspec # :17-038

:c: Fire Marshal Paul Wetowitz

Telephone: 203-881-5010 • FaxTl!~~1~imnour

Page 7: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

lnspt No. 11-!!Jll·

Violation I Regulation/ No. Referenced

Standard

NFPA I

2 NFPA72

3 NFPA I

INSPECTION REPORT

Inspection Date: !!1)412017 Owner/Occupant: Joeseph Falzone/ Seymour Middle School

Inspection Time: 9:45am Address: 211 Mountain Road OccupancyType: Educational

* ~cific

Section No. of Referenced Standard

10.4.1

13.7.3.2.4•

10.4.1

Violation Location Description ofYioJation

Time for Date i:;omplianc~ Violation

Corrected

Left stairway door Whenever or wherever any device, equipment, system, condition, arrangement, level of) 10-10-2017

n.~ room M49, protection, or any other feature is required for compliance with the provisions of this Science Room M76 storage room, Left code,, the Connecticut State Fire Safety Code or the State Building Code, such device.

stairway door next to equipment, system, condition, arrangement, level of protection or other feature shall

room M80, east side thereafter be continuously maintained in accordance with applicable NFP A corridor door near room L61, Library north exit door left

side

Building

Sprinkler room

requirements or as directed by the AHJ.

I

The listed corridor or stairway tire doors are not latching closed. Steps need to be taken

to ensure these fire doors self close and POSITIVELY LATCH CLOSE.

Testing frequency- Unless otherwise pennitted by other sections of the Code and

!NFPA 72, testing shall be performed in accordance with the schedules in Table

13.7.3.2.4, or more often if required by the AHJ. (annually)

!Please provide a copy of this year's annual fire alarm inspection test report.

10-10-2017

1/zd11

Comments

~ . .% ;::;;,-s6"l-Y C,I..O

...\- Pl£,lTI r) 1{ i.--A"1-a-{

/JlltS"T~R

~~~ ._/

Whenever or wherever aI)Y device, equipment, system, condition, arrangement, level of I I ()...10-2017

protectio~ or any other feature is required for compliance with the provisions of this

code. the Connecticut State Fire Safety Code or the State Building Code. such device,

equipment, system, condition, arrangement, level of protection or other feature shall

0~0 \"I) "I"' f' $

11 ltu! l ? 1--rg;,-r6D c.oi-t-W1;:>

thereafter be continuously maintained in accordance with applicable NFPA ~,C/l<t-

Inspected By: -#fae9~~e: - requirements or as directed by the AHJ.

8-/(;-f/7 · 1 Page -1 • As noted in the accompanying Abatement Order of Fire/Life

Safety Hazards, all violations must be corrected within the (30) thirty day period except for those that are identified in this column

--r --,

Approved By: Date:

Page 8: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

INSPECTION REPORT

lnspt No. 17-038 Inspection Date: 8(14/2017 Owner/Occupant: Joeseph Falzone / Seymour Middle School OccupaucyType: Educational

Inspection Time: 2_:4Sam Address: 211 Mountain Road * Specifi,

Regulation/ Section No. of Time for Date Violation Violation Complianco No. Referenced Referenced Location Description ofViolation Violation Comments Standard Standard Corrected

..--,-Please provide a copy of this years fire pump test and water flow.

4 NFPAI 10.4.J Sprinkler systems Whenever or wherever any device, equipment, system, condition, arrangement, level of 10-10-2017 co i,1. ~~1,Gl-1 throughout the !J)rotection, or any other feature is required for compliance with the provisions of this

c[h 1-t· ~µ I->

building !code, the Connecticut State Fire Safety Code or the State Building Code, such device,

equipment. system, condition, arrangement. level of protection or other feature shall '-"' ·" .-,/

thereafter be continuously maintained in accordance with applicable NFPA AL..L- 5pR1.

requirements or as directed by the AHJ. l<S'(S ,,.;: µ& ~57tf;l)

Pl~ provide copies of the most recent testing of all the sprinkler systems

5 NFPA I 10.4.1 Bui1ding Whenever or wherever any device, equipment. system. condition, arrangement. Jevel of 10.10-2017

protection, or any other feature is required for compliance with the provisions of this

~ code, the Connecticut State Fire Safety Code or the State Building Code, such device,

fGUipment, system, condition, arrangement, level of protection or other feature shall ,ti 1h1 0JJO

thereafter be continuously maintained in accordance with applicable NFPA t,.?Jo l

requirements or as directed by the AHJ. :(~ -<;

Please provide a copy of this year's testing of the entire Area Of Refuge intercom 0

system.

6 CFSC IV 7.2.1.4.5 Right side exterior The forces required to fully open any door manually in a means of egress shall not 10-10-2017 Exit door near the exceed 67N (15 lbf) to release the latch and 133N (30 lbf) to set the door in motion, and

Auditorium Catwalk door. 67N (15 lbf) to open the door to the minimum required width, unless otherwise

;:, specified in 7.2.1.4.5.2 through 7.2.1.4.5.5.

-1auK..~--,(_---= ""° lY...,/{,;"i 7 Inspected By: • As noted in the accompanying Abatement Order of Fire/Life Date: Page .2 Safety Hazards, all violations must be correoted within the (30) Approved By, Date: thirty day period except for those that are identified in this column

Page 9: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

INSPECTION REPORT

lospt No. I 7-038 Inspection Date: 8/14/20)7 Owner/Occupant: Joeseph Falzone / Seymour Middle School OccupancyType: Educational

* Specific

'Violation No.

7

8

Regulation/ Referenced Standard

NFPAI

NFPA I

Inspection Time:

Section No. of Referenced Standard

9:4~_am

Violation Location

Address: 211 Mountain Road

Description of Violation Time for

Compliance Date

Violation Corrected

Comments

IThis Exit door is too hard to push open. Steps need to be taken to make it easy to push f?[~l,11 ~R.:

(WM~~

10.4.1

/;..-W,4.1

ii r-i'j l! _-z):) :\. -

-

I

Building

·open.

Whenever or wherever any device, equipment. system, condition, arrangement, level of I 10-10-2017

protection, or any other feature is required for compliance with the provisions of this

~

ode, the Connecticut State Fire Safety Code or the State Building Code, such device,

quipment, system, condition, arrangement, level of protection or other feature shall

ereafter be continuously maintained in accordance with applicable NFPA

·equirements or as directed by the AHJ.

!Please provide a copy of this year's emergency lights and generator load testing.

ElectricaJ data rm Whenever or wherever any device, equipment, system, condition, arrangement. level of 1 OR 1()..2017

··d,~17

M33, Asst. Prin~ipal's protection, or any other feature is required for compliance with the provisions of this I ,_J y, offic~p,er nn, o }VI., exit stairway next to ode, the Connecticut State Fire Safety Code or the State Building Code, such device, 1,1

M80, Science rm M56 quipment. system, condition, arrangement, level of protection or other feature shall

storage rm, Rm. L44, thereafter be continuously maintained in accordance with applicable NFPA jelectrical nn L36, Rm.

L70, Rm. L5J, requirements or as directed by the AHJ.

Classrm L47, L49,

L51, Library storage e,e listed rooms have suspended ceiling tiles missing or displaced. These situations can rm M3G, Custodial

rm. ,,M24, e]ectrical rm ect the proper operation of sprinkler heads. AH ceiling tiles must be in place.

behind M24, Studio nn next to Editing nn

~,RmM_3P,

<(v'fP'·J_..., ~y~

~~\) .._.... A"-.._,

C'..1i:' l L-1 "14 &

---1tt..!3~ ~~t,

Inspected By: ~!?kl&~. jl-1 & ---~.7 ---- Date. ,,,,. Page

..1 • As noted in the accompanying Abatement Order of Fire/Life Safety Hazards, all violations must be corrected within the (30)

thirty day period except for those that are identified in this column Approved By: Date:

Page 10: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

INSPECTION REPORT

lnsptNo. 17-038 Inspection Date: 8/14/2017 Owner/Occupant: Joeseph Falzone / Seymour Middle School OccupancyType: Educational

• Specific Inspection Time: 9:45 am

!Violation I Regulation/ I Section No. of I Violation No. Referenced Referenced Location

Standard Standard

Auditorium storage nn MSL B=snnMll

9 NFPA l 11.l.7.6 Classroom M48

IO NEC ll0.27(a) cafeteria Teachers Lounge

II NFPA l I0.4.1 Electrical nn M36

12 NFPA l I0.4.1 The small clothing closet in the Main Office across from

room ~IL.

Address: 211 Mountain Road

Description of Violation

Extension cords shall not be used as a substitute for permanent wiring.

A zip electrical cord is feeding a dehumidifier and pencil sharpener. The extension cord

must be removed and a proper way of feeding these devices must be found.

Live electricaJ equipment shall be guarded against accidental contact by approved

enclosures.

The wall electrical box where the dock used to be is not covered exposing live wires.

This box needs to be properly covered.

Whenever or wherever any device, equipment, system, condition, arrangement, level of

protection, or any other feature is required for compJiance with the provisions of this

code, the Connecticut State Fire Safety Code or the State Building Code, such device,

equipment, system, condition, arrangement, level of protection or other feature shall

thereafter be continuously maintained in accordance with applicable NFP A

requirements or as directed by the AIU.

The sheetrock wa11 in this room has an opening in it behind a transfonner and the

corridor door. These openings must be properly repaired.

Whenever or wherever any device, equipment,. system, condition, arrangement, level of

rorotection, or any other feature is required for compliance with the provisions of this

code, the Connecticut State Fire Safety Code or the Stale Building Code, such device,

Time for Date ompliancq Violation

Corrected

10-10-2017

10/1.dt7 10-10-2017

~b,o\\1

10-10-2017

1\~b

10-10-2017

Comments

--·-~~

~~%1c--t0?-e,.~o,£ ~!)~E· ~<l\.GTA~

f~S>

~

\/tc}fo~ R~1 f1i"''.

~~Ir t,)t-:>~

CJ,~ 'i?D'C,

_.I c.,u,,/7 /W .do-~ rl~l~-1 7 * As noted in the accompanying Abatement Order of Fire/Life Inspected By: Date: Page ..! Safety Hazards, all violations must be corrected within the (30)

Approved By: Date: thirty day period except for those that are identified in this colurrm

Page 11: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

INSPECTION REPORT

Jnspt No. 17-038 Inspection Date: 8114/2017 Owner/Occupant: Joesepb Falzone / Seymour Middle School OccupaneyType: .Educatjonal

Inspection Time· 2:45 am Address: 211 Mountain_ Road * SnP.cific

Regulation/ Section No. of / Time for Date

Violation Violation Complianc, No. Referenced Referenced Location Description of Violation Violation Comments

Standard Standard Corrected

equipment, system, condition, arrangement. level of protection or other fearure shall

thereafter be continuously maintained in ~cordance with applicable NFPA

q ,~ lt' ' ~)f requirements or as clirected by the AHJ. CJ>~~·.

~~ This clothing closet does not have sprink1er protection inside of it. Sprinkler protection ~~~.-must be provided.

13 NFPA 1 10.4.l Boiler room Whenever or wherever any device, equipment, system, condition, arrangement, level of 10-10-2017

protection, or any other feature is required for compliance with the provisions of this ,J10°(1.

code, the Connecticut State Fire Safety Code or the State Building Code, such device,

equipment. system, condition, arrangement, level of protection or other feature shall /?$ thereafter be continuously maintained in accordance with applicable NFPA i~l\1 ~\~ requirements or as directed by the AHJ.

~ Gasoline fueled trimmers are being stored in the boiler room. They must only be stored

in the ropm with the snow blowers, tractor and lawn mowers.

14 NFPAI 10.4.1 Across from Custodial Whenever or wherever any device. equipment, system, condition, arrangement, level of 10-10-2017

roomM24. protection, or any other feature is required for compliance with the provisions of this

code, the Connecticut State Fire Safety Code or the State Building Code, such device,

equipment. system, condition, arrangement, level of protection or other feature shall

thereafter be continuously maintained in accordance with applicable NFP A ~ requirements or as directed by the AHJ.

---;P~~d:!/ ./-/~-/ r7 Inspected By: Date: Page ..:i

* As noted in the accompanying Abatement Order of Fire/Life

Safety Hazards, all violations must be corrected within the (30) Approved By: Date: thirty day period except for those that are identified in this column

Page 12: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

INSPECTION REPORT

lnspt No. 17--038 Inspection Date: 8/14/2017 Owner/Occupant: Joeseph Falzone/ Seymour Middle School OccupancyType: Edueational Inspection Time, 9:<I_S BIii Address: 211 MountainJ!oru:! * SnPcific

Regulation/ Section No. of Time for Date Violation Violation Compliane< No. Referenced Referenced Location Description of Violation Violation Comments

Standard Standard Corrected

A corridor door's panic hardware cover is falling away from its normal position. This crlslr,~ may interfere-with the hardware operation. The cover needs to be properly reattached.

15 NFPA I I0.4.1 Two small rooms Whenever or wherever any device, equipment, system, condition, arrangement, level of 10-10-2017 ..

within room Ml 8 near protection, or any other feature is required for compliance with the provisions of this

~,,JMlS the Auditorium

.,,..,,. -~()/~

Inspected By: Date:

Approved By: Date:

code, the Connecticut State Fire Safety Code or the State Building Code, such device,

equipment, system, condition, arrangement, level of protection or other feature shall

q,l1IV ~·w' thereafter be continuously maintained in accordance with applicable NFP A

requirements or as directed by the AHJ.

~-~v

I/

These small rooms had tile cabinets or n,iusica1 instruments blocking one of their 2 roon

doors. All doors must remain clear at all times .

J--1,, 11·7 Page Ji

* As noted in the accompanying Abatement Order of Fire/Life Safety Hazards, all violations must be corrected within the (30) thirty day period except for those that are identified in this column

Page 13: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

~ ,,o• R•'>, ,v 1;.,

ll \ ~

.. ~

Office Of The Fire Marshal

'Town of Se9mour 1 First Street

Seymour, Connecticut 06483

Certified Mail Return Receipt #: Thursday, August 17, 2017

Seymour High School Joseph Falzone 211 Mountain Road Seymour, CT 06483

Dear Mr. Falzone,

CONNECTICUT STATE FIRE SAFETY CODE ABATEMENT ORDER OF FIRE/LIFE SAFETY HAZARDS

On 8116/2017, at approximately 0900 hours, an inspection was conducted of the premises located at 2 Botsford Road, Seymour, Connecticut for the purpose of compliance with Connecticut Fire Safety Code and the applicable referenced applicable standards, adopted pursuant to the Connecticut General Statutes §29-292 and §29-293. The Code and said standards are available for your inspection at this office.

The violation of the code found on the date of inspection are listed on the attached inspection report.

You are hereby ordered to take the proper corrective action to remove or remedy all the listed violations within thirty (30) days from the day that this notice is received, unless otherwise noted on the attached mspection report.

If you believe that compliance with the code will impose an unreasonable hardship, and that alternative methods of achieving an equivalent level of safety could be attained, you may reques~ in writing, a modification of the requirements of said Code as outlined in the Connecticut General Statues § 29-296. If you believe compliance will take more than that specified, you may request an extension of time prior to the expiration of the thirty (30) day period, unless otherwise noted on the attached inspection report. Sample forms for application for modification and extension of time for compliance are available from this office. In addition you have the right to appeal this order pursuant to Connecticut General Statues §29-306 for a period of not more than thirty (30) days from receipt.

Plans/specifications for work to be done shall be submitted to this office prior to the commencement of any construction. This review of all plans/specifications would avoid unnecessary expense that could result from non-complying changes. Please note that the correction of certain violations may require proper permits and approval from the building official and other local agencies prior to any construction.

This is the only order you will receive. This office will conduct a re-inspection of the premises to determine compliance with this order after the expiration of the thirty-day (30) or the time period noted on the inspection report. Your failure to comply with this order within the period specified as determined by said re-inspection constitutes your failure to comply with the Connecticut State Fire Safety Code which may subject you to criminal prosecution as prescribed by Connecticut General Statues §29-306 with penalties of a fine not less than two hundred dollars ($200.) nor more than one thousand dollars ($1000.00) or imprisonment ofup to six months or both, as prescribed in Connecticut General Statues §29-295. Non-compliance may result in a civil proceeding against you as authorized in Connecticut General Statues§ 29-306

This Office is looking forward to working with you in the interest of tire and life safety for the community and awaits your timely response to this matter.

Inspec # :17-039

Cc: Superintendent Wilson

Telephone: 203-881-5010 • Fax: I@Ji8!3C[lf5~mour

Page 14: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

INSPECTION REPORT

lnspt No. 17-039 Inspection Date: 8/16/2017 Owner/Occupant: Joseph Falzone I Seymour High School OccupancyType: Existing Education Inspection Time: 0900 Address: 2 Botsford Road

• Specifi - -

Violation Regulation/ Section No. of Time fur Date Violation ~ompliance; No. Referenced Referenced Location · Description of Violation Violation Comments

Standard Standard Corrected

1 NFPA 1 13.7.3.2.3.1 Fire Alarm A complete, una1terable record of the tests and operations of each system shall be kept 10.10.2011 Ii,"{ ce:;s~fr7 . until the next test and one year thereafter. 1, ~ 17 , ~-

f,1AS~li?....

Please provide this Office with the last report of fire alarm testing. ~e.c•y 2 NFPA I 13.3.3.2 Sprink.Jer System A sprinkler system instaUed in accordance with this Code shall be inspected, tested, and 10.10.2017 _7/e:,Jr CoN.~1::>

maintained in accordance with NFPA 25, Standard for the Inspection, Testing. and , l z.\z.1 ll'. t'!J) l"\81 t,v'.'..

Maintenance of Water-Based Fire Protection Systems. .\--(Mf;. <:I!AN1C1+

Please provide this Office with the documentation of the last years quarterly tests. 4::>.\JC.

...-,---

3 NFPA 1 14.13.2.1.l Emergency lights Testing of required emergency lighting systems shall be pennitted to be conducted as 10.10.2017 ~ ?(tz/r Te:5-rED follow:

..-1{[2-'l(t· .....-

~$ (1) Functional testing shall be conducted at 30-day intervals for not less than 30

seconds. -rc;~L (2) Functional testing shall be conducted annually for not less than I l/2 hours if the W&t,7i/1G-emergency 1ighting system is battery powered. 5\t,

~

Inspected By: i ----r J

Date: ~t,111] • As noted in the accompanying Abatement Order of Fire/Life '---"" Page ..1 Safety Hazards, all violations must be correcred within the (30) Approved By: Date: thirty day period except for those that are identified in this column

Page 15: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

INSPECTION REPORT

InsptNo. 17-039 Inspection Date: 8/)6/20)7 0900

Owner/Occupant: Joseph Falzone/ Seymour High School OccupancyType: Existing Edueation Inspection Time• Address: 2 Botsford Road * ~nPr.ifi., ---- -

Regulation/ Section No. of Time for Date Violation Violation Complianc,

No. Referenced Referenced Location Description of Violation Violation Comments Standard Standard Corrected

(3) The emergency lighting equipment shall be fully operational for the duration of the 2(2.f 18 '"T.1.--,S ,

tests required by 14.13.2.1.1 (1) and 14.13.2.1.1 (2).

3, (4) Written records of visual inspections and tests shall be kept by the owner for 1./' inspection by the AHJ.

Please provide this office with documentation from the last 90 minute lighting test.

4 NFPA l 50.5.3 Commercial Cooking The entire exhaust system shall he inspected by a properly trained, qualified, and 10.10.2017 7(t,ll"1 CP\-1.KOV

~N~ L Hoods !certified company or person(s) acceptable to the AHJ in accordance with table 50.5.3

+\_oohs Please provide this Office with proof of the last kitchen hood cleaning. CL&/t,-l8'P

s CFSC IV 31.3.6.2.3 Numerous Doors Doors that open into exit access sha1l be self closing and self latching. 10.10.2017 q(5'. (11 -~tees

l. Door5nearAED 2. Door l firstfloorfrontstairs 3. Guidance entrance doors 4.

~·~·-:" ,::; Gym doors near Perucci's room. 5. Doors to small gym 6. Library doors near

auditorium 7. Door to science wing near auditorium 8. First floor science wing doors .,:\-Lt.~ (;,. ~~~

9. Science wing first floor to back stairs 10. Fire doors near music room. lA -re.,.// I.J.( -6 CFSC !V 8.3.4.1 Ceiling tiles Every opening in a fire barrier shall be protected to limit the spread offire aad restrict 10.10.2017

tollh In ~~ e.

throughout the movement of smoke from one side of the fire barrier to the other. AU.. C!fc I L.111& ~ -r(LJ=.S I ,-(

Please ensure all ceiling tiles are in place. ~~

7 NFPA 13 8.5.6.l* Storage near sprinklers The clearance between the deflector and the top of storage shall be 18 inches or greater. 10.10.2017 q\i~d l 1 ~ a

-? /tU_ --• c,/ll2J I Follow locations: I'll.""·~

11-1.C

[nspected. By: ~ ~fl? JtI • As noted in the accompanying Abateffient Order of Fire/Life \.!_,..,

Date: Page ~ Safety Hazards, all violations must he corrected within the (30) Approved By: Date: thirty day period except for those that are identified in this column

Page 16: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

lnspt No. 17 ::032

Violation Regulation/ No. Referenced

Standard

=t-8 CFSC

9 NFPAI

@

Inspected By:

Approved By:

Inspection Date:

Inspection Time·

Section No. of Referenced Standard

IV 7.2.1.4.5

I 1.1.2

,,......, ff' \ ' -

8/16/2017 09()!!_ ----

Violation Location

Numerous Doors

Multi-tap (surge protectors)

continued from violation 9

Date:

Date:

JNSPECJIDN REPQRI

Owner/Occupant: Joseph Falzone/ Seymour High School OccupancyType: Existing Edueatinn Address: 2 Botsford Road

• Soecitic Time for Date

Complianc, Description of Violation Violation Comments Corrected

1. Home economics closet 2. Storage room237 (data cord). 3. Art room closet 4. q r i.1 / 17;wii y-Room 188 closet 5. Custodian office top shelf

IThe forces required to fully open any door manually in a means of egress shall not I0.10.2017 q t1c, \r A~\:>!:;1.

exceed 67N (15 !bf) to release the latch and 133N (30 lbf) to set the door in motion, and

~-~ 67N ( 15 Jbf) to open the door to the minimum required width, unless otherwise

specified in 7.2.1.4.5.2 through 7.2.1.4.5.5. v" A-LL 1:oo~S

tn,e following: ,t:_ ,_ 1\1.e.°"TE'b -\-V>: .

I.S

1£ J. Door 10 (main hallway center stiars 1st floor) Bi:'GN- sa<.ll1u; :i,..

12. Science wing exterior door near auditorium ..\, ()~e'N .-D 3. Auditorium exterior exits Co~

4. Stage Exterior exit

All electrical appliances, fixtures, equipment, or wiring shall be instaJled and 10.10.2017

maintained in accordance with NFP A 70, National ·Electrical Code.

Extension cords and multi-taps are not intended to be plugged into each other or

additional multi-taps. Numerous were found throughout and must be corrected to -? prevent a fire. The next section will name the specific locations.

1. Room 121- multi tap into multi tap

2. Room 128- Extension cord into multi-tap

3. Room 104- multi tap into multi tap ~ 4. Room221- Extension cord into multi-tap

1¥1] /,7 * As noted in the accompanying Abatement Order of Fire/Life Page .J I Safety Hazards, all violations must be corrected within the (30)

thirty day perio<lexcept for those that are identified in this column

Page 17: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

INSPECTION REPORT

Inspt No. 17-039 Inspection Date: 8/1612017 Inspection Time: _O\IOC!

Owner/Occupant: Joseph Falzone/ Seymour High School OccupancyType: -Existine -Education Address: 2 Botsf1>r!lR_oad

• S=cific

Molation Regulation/ Section No. of Time for Date

Violation :::omplianc, No. Referenced Referenced Location Descrjptjon of Violation Violation Comments

Standard Standard Corrected

@ 5. Room 258 - multi tap into multi tap

q/1'/ll: 'fsp.~\':iv I o_p..,J.J

6. Room 252- Extension cord into multi-tap R_i,;;f,A<ttJFt::> /a ~ 7. Room 142 -Extension cord into multi-tap ~'1;,T§'~t~H_.! .

-

11 NEC 2I0.8(A)(6) Home Ee outlet near All 125 vol~ single phase, 15 and 20-ampere receptacles installed in locations specified IO.I0.2017 ~,'-"-' north end in {I) through (8) shall have ground-fault circuit-interruptor protection for personnel in

CJ (1zl11 -:5J!<fi!!-'J\S kitchens serving countertop serves. ~- ---

~3: . .. The GFI failed to function on this outlet.

'BY ~c., 12 NEC Chapter 3 Storage room Wiring shall be installed in accordance with NFPA 70 and wires shall be protected from 10.10.2017 1}/t\J~ C. '.

damage. o.._ \l-zl \1 w1i<.e,:; ~, ID:

A wire is currently unsecured hanging from the ceiling from one wall to the other. .J-:se=-u~ B: 16'~iCJ4 f-}

Please have this properly secured.

13 NFPAI 10.4.1 Sprinkler head in boys Whenever or wherever any device, equipment, system, condition, arrangement, level of 10.I0.2017 bathroom main hall lorotection, or any other feature is required for compliance with the provisions of this

~<;,'f ( -o,t>16' first floor Icade, the Connecticut State Fire Safety Code or the State Building Code, such device, ~rzl17 equipment. system, condition, arrangement, level of protection or other feature shall

~bW)V~ thereafter be continuously maintained in accordance with applicable NFPA ~ requirements or as directed by the AHJ.

The sprinkler is currently covered in what appears to be wet papertowels. Please have

these removed.

14 NEC 110~) Room 106 outlet Live electrical equipment shall be guarded against accidental contact by approved -;> 10.I0.2017

,'t Date:. * As noted in the accompanying Abatement Order of Fire/Life Inspected By:

\.._....,- Page ~ Safety Hwirds, all violations must be corrected within the (30) Approved By: Date: thirty day period except for those that are identified in this cclumn

Page 18: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

lnspt No. 17-039

Violation Regulatii>n/ No. Referenced

Standard

® 15 CGS

16 CFSC

17 NEC

Inspected By:

Approved By:

INSPECTION REPORT

Inspection Date: 8/16/2017 !1900

Owner/Occupant: Joseph Falzone / Seymour High School OccupancyType: ,Existing Education

Inspection Time~ Address: 2 Botsford Road -- - - * Snecific

Section No. of Time for Date Violation Complianc, Referenced Location Description of Violation Violation Comments Standard Corrected

enclosures. ~/;dn vP<"t' ~~~ aJTl!i:' ,'

Please have an outlet cover installed. c.o\/-e~ 29-306 Boiler When the local fire marshal ascertains that there exists in any building, or upon ay 10.J0.2017

premises, a condition in violation of the statues relating to fire prevention or safety, or

any regulation made pursuant thereto, the local fire marshal shall order such materials t4

"I J,dn A-*.6 . ,,J

be immediately removed or the conditions remedied by the owner or occupant of such ~; building or premises.

··~ =· ~ A water leak was observed dripping on to the boiler. Please have this addressed (YP=K immediately.

IV 8.6.4.l BoiJer room shaft Shafts sha11 be enclosed at the lowest level of the shaft, with construction in accordance IO.J0.2017 {possibly old chimney) with 8.6.5 GfJrl.,..1 ... 0

S('t>h-r (3) Existing enclosures in existing buildings 1/2 hour fire barrier. ~"f", +Li\S f? ·-· -

~." .... Please have this shaft enclosed with sheet rock. LP I $1-f,!?T -Ptt.

!I 0.26 (3) {B) Electrical room across Working space required by electrical panels must not be utilized for storage. 10.10.2017 from nurse

\)~ Room 190 Have the storage removed. i(~lrt S"' ,,.,~,

~~ ... -.~ ,,., ..

f.-1V . <f/n/17 • As noted in the accompanying Abatement Order of Fire/Life \...'./

Date: Page j I Safety Hazards, all violations must be corrected within the (30) Date: thirty day period except for those that are identified in this column

~

-K

Page 19: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

INSPECTION BEPQBI

Inspt No. 17-039 Inspection Date: WJ612017 O!IOO

Owner/Occupant: Joseph Falzone I Sevmour High School OccupancyType: Existing Edueatjon Inspection Time: Address: 2 Botsford Road

• Specifi -- - -

Regulation/ Section No. of Time for Date Violation Violation :omplianc,

No. Referenced Referenced Location Description of Violation Violation Comments

Standard Standard Corrected

18 CFSC IV 7.2.1.8.1* Door to guidance suite A door leaf nonnally required to be kept closed shall not be secured in the open position 10.10.2017

at any time and shall be self-closing or automatic closing in accordance with 7.2.1.8.2. -s;,# unless otherwise permitted by 7 .2.1.8.3 toli.J I t1 M~i,,-

This door is continually propped open. It is our recommendation that a magnet release \µ$~

is installed. ~~:::;:

19 CFSC IV7.I.IO.t• Exit door between Means of egress shall be continuously maintained free of all obstructions or· 10.10.2017 A-6?£k room 219 and 221 impediments to full instant use in the case of fire or other emergency. q(20h?

,,,. t:,,Av~ 1&D

~{)\. [This door is blocked where it cannot fully swing open.

20 NEC l l0.27(a) Room 219 Live electrical equipment shall be guarded against accidental contact by approved 10.10.2017 @.P:.-,*J~ enclosures. '!)\V-

/o!i\\\.1 6wl"'':> .4 Numerous cords pulling out of their outlets. Please have an electrician repair or replace wi~c, these. p._€{)

21 NFPA 1 11.1.7.6 fl olleybal! locker room Extension cords shall not be used as a substitute for permanent wiring. 10.10.2017 ~ O•J\<-=1

10\~ Ir? ~~I The extension cord shall not be utilized to power the ice machine and sump pump. ,µ~~tC1i

' 22 NFPA I 14.13.2.1.1 Emergency light in Testing of required emergency lighting systems shall be pennitted to be conducted as 10.10.2017

~ce.S hall across from follow: q~\l1 library

( 1) Functional testing shalt be conducted at 30-day intervals for not less than 30 \~~ seconds. -? ~,-JG,--~·

Inspected By: fV * • As noted in the accompanying Abatement Order of Fire/Life - Date: Page Ji Safety Hazards, all violations must be corrected within the (30) Approved By: Date: thirty day period except for those that are-identified in this column

;

--' ~ I

c-

;f ,t-\

Page 20: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

Inspt No. 17-039 Inspection Date:

Inspection Time~

Violation Regulation/ Section No. of

No. Referenced Referenced

Standard Standard

22--

8/Jli12Ql7 090Q_ v---

Violation Location

INSfECTION REPORT

Owner/Occupant: Joseph Falzone / Seymour High School OccupancyType: Existing Education Address: _2 Botsfo!"!I Roa_!!_

• Specific Time for Date

~ompliane< D~s£Dmi,m QfYi2l1tiQD Violation Comments Corrected

When tested this light failed to illuminate.

23 CFSC 7.2.1.5.3 S1ide0bolts on door to Locks if provided shall not require the use ofa key, a tool or special knowledge or e:ffor 10.102017 ~J)-t>J€'~ small gym (weight for operation from tb·e egress side.

to{1{17 '9,.,-\~~ room) /

The slide bolts on these two sets of double doors must be removed from the top and D,,._Je: [bottom. t--

24 CFSC 7.10.1.2.1* Pool equipment Exits. other than main exterior exit doors tat obvious1y and clearly are identifiable as 10.102017 exterior exit exits shall be marked by an approved sign that is readily visible from any direction of ..-rcrriH--

exit access. ff(idn u~-n,.,~ ~~ Please have an exit sign installed above this door to the outsite, - t t-\':'.;

25 NFPA I 10.4.1 Sprinlker escusion Whenever or wherever any device, equipment, system, condition, arrangement. level of 10.10.2017 ~ 5,l<t\O ,-.t missing in library protection, or any other feature is required for compliance with the provisions of this ~b'llfi storage I 66c code; the Connecticut State Fire Safety Code or the State Building Code, such device,

G~·

equipment, system, condition. arrangement. level of protection or other feature shall ~-· thereafter be continuously maintained in accordance with applicable NFPA ? \~

. c_/ requirements or as directed by the AHJ.

rrtiis sprinkler is missing its escushion.

26 NFPA 10 13.6.8.1.3.4* Room 180 Portable fire extinguishers other than the wheeled type shall be installed using any of 10.10.2017

/he following:

J. Securely on a hanger intended for the extinguisher. --> --9

Inspected By: r-,-e

Date· y; }17 /17 * As noted in the accompanying Abatement Order of Fire/Life ' / . r, Page J. - Safety Hazards, all violations must be corrected within the (30)

Approved By: Date: thirty day period except for those that are identified in this column

V

I/

Page 21: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

lnspt No. 17-039

Violation Regulation/ No. Referenced

Standard

-Z.(i:;

27 NFPA l

28 NFPA l

29 NEC

Inspected By:

Approved By:

Inspection Date:

lnspeetion Time· .

Section No. of Referenced Standard

8/16/2017 ~(IQ_ -~ --

Violation Location

INSPECTION REPORT

Owner/Occupant: Joseph Falzone/ Seymour High School Address: 2 Botsford Road

Description of Violation

Please have this fire extinguisher mounted.

OccupancyType: Existing Edu@tion

* S=citic Time for Date

Complianc Violation Comments Corrected

? ~ e . ,-..w ,+-re: [

q)zi/n •\<\~

10.4.1 Exist sign in 292 is ou t Whenever or wherever any device, equipment, system, condition, arrangement, level of 10.10.2017

~\es protection, or any other feature is required for compliance with the provisions of this

~ code, the Connecticut State Fire Safety Code or the State Building Code, such device,

1{to(\1 equipment, system, condition, arrangement, level of protection or other feature shall ,..,.srA-L,

~"f \ 9'1,,--thereafter be continuously maintained in accordance with applicable NFPA

,._, requirements or as directed by the AIU. ..,,-//

When tested this exit sign failed to illumiante.

10.4.l Kitchen servcry Whenever or wherever any device, equipmen~ system, condition, arrangement, level of 10.10.2017

cc/i'{l1 &=> tu$#10N Storage room protection, or any other feature is required for compliance with the provisions of this ~le'~ r

code, the Connecticut State Fire Safety Code or the State Building COde, such device,

equipment, system. condition, arrangement, level of protection or other feature shall '7 CJll-lR.Ob !thereafter be continuously maintained in accordance with applicable NFPA

requirements or as directed by the AHJ. ~ Eschusion is falling from around sprinkler.

Chapter 3 Former Machine Shop Wiring shall be installed in accordance with NFPA 70 and wires shall be protected from 10.10.2017

damage. ,...

-:? 1)-1\"~

A wire is currently unsecured hanging in front of the egress door. Please have this wire + /'.::;\

_,., JU Date~' {7 / r1 * As noted in the accompanying Abatement Order of Fire/Life -~ . I r Page J! Safety Hazards, all violations must be corrected within the (30) Date: thirty day period except for those that are identified in this colunm

Page 22: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

lnspt No. 17-039 Inspection Date:

Inspection Time:

Violation Regulation/ Section No. of

No. Referenced Referenced Standard Standard

zq 30 NFPA I 11.1.7.6

Inspected By:

Approved By:

8/16/2017 0900 ----

Violation Location

Football coach room 157 J air conditioner

Date:

Date:

J:NSPECUQN'BF,IDBT

Owner/Occupant: Joseph Falzone/ Seymour High School OccupancyType: Existing Education Address: 2 Botsford Road

• Specifi Time for Date

Complianc, Description ofVio]ation Violation Comments Corrected

'

properly secured. te, /qir (;}~~

Extension cords shall not be used as a substitute for permanent wiring. 10.10.2017 ,, q\1kr ~ p,\Jt:::

Air conditioners need to be plugged directly into outlets and not extension cords. e('.-,at'Sl ot-1-~fU:>5® ~

* As noted in the accompanying Abatement Order of Fire/Life Page .2. Safety Hazards, all violations must be corrected within the (30)

thirty day period except for those that are identified in this column

Page 23: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

~ ,,o• ••i,, !' ,r,. i \

~

~

Office Of The Fire Marshal

'Town of Seymour l First Street

Seymour, Connecticut 06483

Certified Mail Return Receipt #: Monday, August 14, 2017

Bungay Elementary School Joseph Falzone 211 Mountain Road Seymour, CT 06483

Dear Mr. Falzone,

CONNECTICUT STAT;lilFfflFJ.·.SAFETY CODE ABATEMENT ORDER OF FIRE/LIFJ)lSAFETY HAZARDS

On 8/14/2017, at approximately 1030 hours, an inspection was conducted of the premises located at 211 Mountain Road, Seymour, Connecticut for the purpose of compliance with Connecticut Fire Safety Code and the applicable referenced applicable standards, adopted pursuant to the Connecticut General Statutes §29-292 and §29-293. The Code and said standards are available for your inspection at this office.

The violation of the code found on the date of inspection are listed on the attached inspection report.

You are hereby ordered to take the proper corrective action to remove or remedy all the listed violations within thirty (30) days from the day that this notice is received, unless otherwise noted on the attached inspection report.

If you believe that compliance with the code will impose an unreasonable hardship, and that alternative methods of achieving an equivalent level of safety could be attained, you may request, in writing, a modification of the requirements of said Code as outlined in the Connecticut General Statues§ 29-296. If you believe compliance will take more than that specified, you may request an extension of time prior to the expiration of the thirty (30) day.period, unless otherwise noted on the attached inspection report. Sample forms for application for modification and extension of time for compliance are available from this office. In addition you have the right to appeal this order pursuant to Connecticut General Statues §29-306 for a period of not more than thirty (30) days from receipt.

Plans/specifications for work to be done shall be submitted to this office prior to the commencement of any construction. This review of all plans/specifications would avoid unnecessary expense that could result from non-complying changes. Please note that the correction of certain violations may require proper permits and approval from the building official and other local agencies prior to any construction.

This is the only order you will receive. This office will conduct a re-inspection of the premises to determine compliance with this order after the expiration of the thirty-day (30) or the time period noted on the inspection report. Your failure to comply with this order within the period specified as determined by said re-inspection consti.tutes your failure to comply with the Connecticut State Fire Safety Code which may subject you to criminal prosecution as prescribed by Connecticut General Statues §29-306 with penalties ofa fine not Jess than two hundred dollars ($200.) nor more than one thousand dollars ($1000.00) or imprisomnent ofup to six months or both, as prescribed in Connecticut General Statues §29-295. Non-compliance may result in a civil proceeding against you as authorized in Connecticut General Statues § 29-306

This Office is looking forward to working with you in the interest of fire and life safety for the community and awaits your timely response to this matter.

Inspec # :17-035

Cc: Superintendent Wilson . Willis

Telephone: 203-881-5010 • Fax: 2(B't•{!Ul;§®'mour

Page 24: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

lnspt No. )7-035 Inspection Date:

Inspection Time·

Violation Regulation/ Section No. of

No. Referenced Referenced Standard Standard

l NFPAI 13.7.3.2.3.1

8/14/20)7 1030 ----

Violation Location

Fire Alarm

cci,__

INSPECTION REPORT

Owner/Occupant: Joseph Falzone/ Bungay Elementary School OccupancyType: Existing Ed11cation Address: 211 Mountai11 ]load

• Specific Time for Date

:omplianc, D~~!ccigti20 Qf Yi2JmiWl Violation Comments Corrected

IA complete, unalterable record of the tests and operations of each system shall be kept IO.I0.2017

1(zr,,li1 !U.Asre-,~

until the next test and one year thereafter. SEO){:_\

' ~~~ Please provide this Office with the last report of fire alarm testing.

2 NFPAI 14.13.2.l.l Emergency Light test Testing of required emergency lighting systems shal1 be pennitted to be conducted as 10.10.2017 -roTA-L follow: '7\Lz.l,~ l-\~t,.Lc (I) Functional testing shall be cOnducted at 30-day intervals for not less than 30

seconds.

(2) Functional testing shall be conducted annually for not less than I 112 hours if the

emergency lighting system is battery powered.

(3) The emergency lighting equipment shall be fully operational for the duration of the I---"' tests required by 14.13.2. l.l (1) and 14.13.2. l.l (2).

(4) Written records of visual inspections and tests shall be kept by the owner for

inspection by the AHJ.

Please provide this Office with documentation from the last 90 minute test.

3 NFPA l 50.5.3 Kitchen Hood The entire exhaust system shall be inspected by a properly trained, qualified, and 10.10.2017 I rnt- \ Llll"" .l

MfPW.)\Gl-1 certified company or person(s) acceptable to the AHJ in accordance with table 50.5.3

1 (bl\:t "' l::::::i' " E?b Please provide documentation of the last hood cleaning. I r.V' n D

• 4 NFPA l 13.6.6.8.3.1 Fire Extinguisher in Frequency. Fire extinguishers shall be subjected to maintenance at intervals of not mori 10.10.2016

/" \ computer room than 1 year, at the time of hydrostatic test, or when specifically indicated by an -=r

1YV ,,,J,, '11---' Inspected By: Date: ., ~r, -1 * As noted in the accompanying Abatement Order of Fire/Life '-..'../ , Page .l Safety Hazards, all violations must be corrected within the (30)

Approved By: Date: thirty day period except for those that are identified in this column

-

Page 25: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

lnspt No. 17-03S

Violation Regulation/

No. Referenced Standard

4

5 NFPAI

6 NFPA I

7 CFSC

8 CFSC

9 CFSC

lnspeeted By:

Approved By:

*

INSPECJION REPORT

Inspection Date: 8/14/20)1 1030

Owner/Occupant: Joseph Falzone / Bungay Elementary School OccupancyType: t;xisting Fs!d.ucation Inspection Time• Address: 211 Mountain Road * Sne.cific

Section No. of Time for Date Violation Compliance Referenced Location Description of Violation Violation Comments Standard Corrected

inspection or electronic notification. 6[1slr \L\~~ - .....: efS\61:?\~

The fire extinguisher was last serviced in July of 2016. '--D1)\ /

I 1.1.7.3 Multi-plug surge The extension cords shall be maintained in good condition without splices, 10.10.2017

rA#~~,j. protector room 23 deterioration, or damage. ~\~\ ···-~·~ The multi-plug adapter has exposed wiring at the connection and must be removed. '.A~

11.1.7.3 Sun-beam microwave The extension cords shall be maintained in good condition without splices, 10.10.2017 cord deterioration, or damage. rN'~" !.,)~\,'{,

g~l~ ~"\).;;

t,Jc\; The power cord to the sunbeam microwave in the break room is melted and must be

v)~,J~ repaired or replaced.

JV 7.2.1.4.5 Exit doors across from The forces required to fully open any door manually in a means of egress shall not 10.10.2017

~-custodial office exceed 67N (15 !bf) to release the latch and 133N (30 lbf) to set the door in motion, and

67N (15 lbf) to open the door to the minimum required width, unless otherwise

q(13/i: Vv)~-

specified in 7.2.1.4.5.2 through 7.2.1.4.5.5.

~~11-i These doors are extremely difficult to push open. 0~

IV 31.3.6.2.3 Gym door near nurse's Doors that open into exit access shall be self closing and selflatching. I0.10.2017

~~ office ~ (r,\n These doors are not properly latching. Please have them adjusted. ~ l.)l;.~

IV 31.3.6.2.3 Hall fire doors near 10.10.2017

.Ml Date:~ * As noted in the accompanying Abatement Order of Fire/Life

U/ Page .1 Safety Hazards, all violations must be corrected within the (30) Date: thirty day period except for those that are identified in this column

Page 26: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

lnsptNo. !7-035 Inspection Date:

Inspection Tim..,• ..

Violation Regulation/ Section No. of

No. Referenced Referenced

Standard Standard

q_

IO NFPA I

Inspected By:

Approved By:

8/14/2017 J03ll ----

Violation Location

first grade wing

Freezer threshold

Date:

Date:

INSPECTION REPORT

' Owner/0.:Cupant: Joseph Falzone/ Bungay Elementary School OccupancyType: -Existing Education

Address: 211 Mountain RQ11d • Specific

Time for Date Complianc, DeSCrintion of Violation Violation Comments

Corrected

-Doors that open into exit access shall be self closing and self latching.

qg~/11 ~~' ~,if'i";:; These doors are not properly latching.

/JO

The threshold coming out of the freezer is loose creating a tripping hazard. 10.10.2017

cr(cb7 'i) >'<'V'-' (.:I' .

J* ~

.. ~PA~~~ Ir , ',yffrfj: ,_,...

f-1,i

Page ..1 "'As noted in the accompanying Abatement Order of Fire/Life Safety Hazards. an violations must be corrected within the (30) thirty day period except for those that are identified in this column

"'l

6

(?

Page 27: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

Certified Mail Return Receipt#:

Chatfield LoPresti School Joseph Falzone 211 Mountain Road Seymour, CT 06483

Office Of The Fire Marshal

'Town of Seymour I First Street

Seymour, Connecticut 06483

Thursday, August 17, 2017

CONNECTICUT STATE FIRE SAFETY CODE ABATEMENT ORDER OF FIRE/LIFE SAFETY OZARDS

Dear Mr. Falzone,

On 8/17/2017, at approximately 0930 hours, an inspection was conducted of the premises located at 51 Skokorat Street, Seymour, Connecticut for the purpose of compliance with Connecticut Fire Safety Code and the applicable referenced applicable standards, adopted pursuant to the Connecticut General Statutes §29-292 and §29-293. The Code and said standards are available for your inspection at this office.

The violation of the code found on the date of inspection are listed on the attached inspection report.

You are hereby ordered to take the proper corrective action to remove or remedy all the listed violations within thirty (30) days from the day that this notice is received, unless otherwise noted on the attached inspection report.

If you believe that compliance with the code will impose an unreasonable hardship, and that alternative methods ofachieving an equivalent level of safety could be attained, you may request, in writing, a modification of the requirements of said Code as outlined in the Connecticut General Statues§ 29-296. If you believe compliance will take more than that specified, you may request an extension of time prior to the expiration of the thirty (30) day period., unless otherwise noted on the attached inspection report. Sample forms for application for modification and extension of time for compliance are available from this office. In addition you have the right to appeal this order pursuant to Connecticut General Statues §29-306 for a period ofnot more than thirty (30) days from receipt.

Plans/specifications for work to be done shall be submitted to this office prior to the commencement of any construction. This review of all plans/specifications would avoid unnecessary expense that could result from non-complying changes. Please note that the correction of certain violations may require proper permits and approval from the building official and other local agencies prior to any construction.

This is the only order you will receive. This office will conduct a re-inspection of the premises to determine compliance with this order after the expiration of the thirty-day (30) or the time period noted on the inspection report. Your failure to comply with this order within the period specified as determined by said re-inspection constitutes your failure to comply with the Connecticut State Fire Safety Code which may subject you to criminal prosecution as prescribed by Connecticut General Statues §29-306 with ~enalties ofa fine not less than two hundred dollars ($200.) nor more than one thousand dollars($ I000.00) or imprisonment ofup to ;ix months or both, as prescnlled in Connecticut General Statues §29-295. Non-compliance may result in a civil proceeding against ;ou as authorized in Connecticut General Statues§ 29-306

fhis Office is looking forward to working with you in the interest of fire and life safety for the community and awaits your timely :espouse to this matter.

lnspec # :17-040

Cc: Superintendent Wilson //?11

~~ty Fire M~thy P. Willis

Telephone: 203-881-5010 • Fax:T~.rgg:i[~Jmour

Page 28: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

lnsptNo. 17-040 Inspection Date:

Inspection Time·

Violation Regulation/ Section No. of No. Referenced Referenced

Standard Standard

l NFPA I 13.7.3.2.3.1

2 NFPA I 13.3.3.2

3 NFPA l 14.13.2.l.l

,-..

Inspected By: 11V ~

Approved By:

8/17/20)7 0930 ------

Violation Location

Fire Alarm

Sprinkler System

Emergency Lights

lNSPE(;tJOlS:.iJF,ROR'.J'

Owner/Occupant: Joseph Falzone/ Chatfield LoPresti School Address: 51 Skokorat Street

Description of Violation

A complete, unalterable record of the tests and operations of each system shall be kept

until the next test and one year thereafter.

Please provide this Office with the 1ast report of fire alarm testing.

A sprinkler system installed in accordance with this Code shall_ be inspected, test:d, and

maintained in accordance,with NFPA 25, Standard for the Inspection, Testing, and

Maintenance of Water-Based Fire Protection Systems.

Please provide this Office with the documentation of the last years quarterly ~1s.

Testing of required emergency lighting systems shall be permitted to be conducted as

follow:

(1) Functional testing shall be conducted at 30 ... day intervals for not less than 30

seconds.

(2) Functional testing shall be conducted annua1ly for not less than I 1/2 hours if the

emergency lighting system is battery powered.

OccupancyType: Existing Educ;ation

* Soecific Time for Date

Complianc, Violation Comments Corrected

10.10.2017 Mb%~ ~~\

1/llP/17 z~ 10.10.2017

'l1~n CDl-l \(O~o1,1 ~t"

11.. li.--zlr --(¢~ ,zJz..l \1 .....----

10.10.2017 ""70-,:M..-. -r. (t-ill1 L.-\.G+fTI µ&-.

<fe'> I=-

>

Date:~ "'As noted in the accompanying Abatement Order of Fire/Life Page .! Safety Hazards, all violations must be corrected within the (30)

Date: thirty day period except for those that are identified in this column

Page 29: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

INSPECTION REPORT •

Inspt No. 17-040 Inspection Date: 8/17/2017 093!!

Owner/Occupant: Joseph Falzone / Chatfield LoPresti School OccupancyType: Existing Education Inspection Time· Address: 51 Skokorat Street ---- • s-ific

Regulation/ Section No. of Time for Date Violation Violation Complianc

No. Referenced Referenced Location Description of Violation Violation Comments

Standard Standard Corrected

3) The emergency lighting equipment shall be fully operational for the duration of the

) tests required by 14.13.2.1.1 (I) and 14.13.2.l.l (2).

(4) Written records of visual inspections and tests shall be kept by the owner for ..__.--inspection by the AHJ.

Please provide this office with documentation from the last 90 minute lighting test

4 NFPA I 50.5.3 Commercial Kitchen The entire exhaust system shall be' inspected by a properly trained, qualified, and IO.I0.2017

1 lb\ I'{ O,t-1 i<5:l ""'. \~

Hood certified company or person(s) acceptable to the AHJ in accordance with table 50.5.3 ~,M,11

~ Please provide this Office with proof of the last kitchen hood cleaning. ~~

5 NFPA I 11.1.2 Main conference room All electrical appliances, fixtures, equipment. or wiring shall be instalied and IO.I0.2017 ~-f'R1CP<-L multi-tap power strip maintained in accordance with NFPA 70, National Electrical Code.

51[o/>l Y1 CD~~..,._.

Gr~¢ Extension cords and multi-taps are not intended to be plugged into each other or t'-::1.)\,""'(\ iV ~ additional multi-taps. ~

6 NEC 110.26 (3)(B) Custodial closet near Working space required by electrical panels must not be utilized for storage. 10.10.2017

~J;j 114 irzd"' Please remove storage from in front of electrical panels.

7 CGS 29-306 Stairwell #2 storage· When the local fire marshal ascertains that there exists in any building, or upon ay I0.10.2017

premises, • (2) obstructions or conditions that present a fire hazard to the occupants or G-~ interfere with their egress in case of fire. ~J;oh7 ~~

/"'' Storage shaU be removed from the bottom of stairwell 2. ~

Ht' ·wr+li Inspected By:

'---"' Date· / ( +-

Page .1 • As noted in the accompanying Abatement Order of Fire/Life

' I I Safety Hazards,, all violations must be corrected within the (30) Approved By: Date; thirty day period except for those that are identified in this column

Page 30: FACILITIES COMMITTEE IVIINUTES · 2018-03-01 · Parking lot striping, painting exterior woodwork, replace classroom A/C units, repair sidewalk, paving in drop off area ' 2. Chatfield-LoPresti

Inspt No. )7-040 Inspection Date:

Inspection Time:

Violation Regulation/ Section No. of

No. Referenced Referenced Standard Standard

8 CFSC IV 7.2.1.4.5

9 CFSC IV 31.3.6.2.3

10 CFSC IV 7.2.1.8.I•

I I NEC 110.26 (3) (B)

Inspected By:

Approved By:

S11mo12 0930

Violation Location

Exit door near basement stairs

Library doors near cafe

Doortoroom 131

Large Storage room near custodial office

JiNs:PErnlON:BEPORJ.

Owner/Occupant: Joseph Falzone / Chatfield LoPresti School Address: 51 Skokorat Street

Description of Violation

The forces required to fully open any door manually in a means of egress shall not

exceed 67N ( 15 lbf) to release the latch and 133N (30 lbf) to set the door in motion, and

67N ( 15 lbf) to open the door to the minimum required width, unless otherwise

specified in 7.2.1.4.5.2 through 7.2.1.4.5.5.

This door was very difficult to operate.

Doors that open into exit access shall be self closing and self latching.

These doors did not properly latch.

A door leaf normally required to be kept closed shall not be secured in the open position

at any time and shall be self-closing or automatic closing in accordance with 7 .2.1.8.2,

unless otherwise pennitted by 7.2.l.8.3

This room is being utilized as storage and the door is to remain in the closed position.

Working space required by electrical panels must not be utilized for storage.

All storage must be cleared a minimum of 36 inches from the service panels.

'

OccupancyType: Existing Ed11cation

-• Specifi Time for

Date ~ompliance; Violation Comments

Corrected

10.10.2017

~ ~}G'?___>( 1ln.\, ;,,-aP-~.~ ' ~".t-\~ of!"

10.10.2017 ~~c...~/, e, ll'?,\ ,1 ~;"~c.i

IO.I0.2017

~

4\l\l'"I ~D~ ~~~· K~-

I0.I0.20I7 ~ ~l°?" \\1 ~

Date: * Page ..l • As noted in the accompanying Abatement Order ofFire/Life Safety Hazards, all violations must be corrected within the (30) thirty day period except for those that are identified in this column Date:


Recommended