FBS Underfloor Ducts Underfloor Duct System Ducts FBS manufactures a complete line of underfloor raceways and fittings that are NRTL Listed and approved under spec C22-2 No 80 to both, Canadian & U.S. standards.  Underfloor duct can be ordered in combinations of duct sizes and runs of up to four ducts to provide the solution that best suits your project needs. Numbers 3 & 6 ducts are commonly used in commercial applications such as grocery stores, retail outlets and offices where surface race- ways may not be practical or feasible. Number 8 duct provides a heavy duty power distribution system, which is used in industrial and commercial applications such as manufacturing plants, warehouses and warehouse type retail outlets, all of which may place heavy demands on an electrical system. The #F3 is a 1 1/2” x 3” duct and has a cross sectional area of 3.94 sq. inches. Duct is supplied either blank (F3B) or with preset inserts. The #F6 is a 1 1/2” x 6 1/2” duct and has a cross sectional area of 8.75 sq. In. Duct is supplied either blank (F6B) or with preset inserts. The #F8 is a 4” x 4” duct which has a cross sectional area of 14.78 sq. In. Duct is supplied either blank (F8B) or with preset insert. Length: 10 ft. Length: 10 ft. The FBS underfloor duct system includes two different sizes of ducts that can be combined to match the cable capacity re- quired for your project; junction boxes, duct supports, duct couplings and several accessories complete the FBS underfloor system. FBS ducts and related parts are manufactured of 16-gauge galvanized steel. Approved under spec C22-2 No 80 to both, Canadian & U.S. standards. Ducts are supplied either blank ( no preset inserts ) for use with after set inserts or with preset inserts with various heights ( up to 3” ) available to suit the concrete pour. Combine with up to 3 F3 or F6 ducts #F3 Duct #F6 Duct #F8 Duct L: 10 ft. UFD 1 FBS Floor Box Systems - 1-800-216-8307 FBS UNDERFLOOR DUCTS C US NRTL
Transcript
Page 1: FBS Underfloor ducts - FBS Floor Box Systems

FBS Underfloor Ducts

Underfloor Duct System

Ducts

FBS manufactures a complete line of underfloor raceways and fittingsthat are NRTL Listed and approved under spec C22-2 No 80 to both,Canadian & U.S. standards. 

Underfloor duct can be ordered in combinations of duct sizes and runsof up to four ducts to provide the solution that best suits your projectneeds.

Numbers 3 & 6 ducts are commonly used in commercial applicationssuch as grocery stores, retail outlets and offices where surface race-ways may not be practical or feasible.

Number 8 duct provides a heavy duty power distribution system, whichis used in industrial and commercial applications such as manufacturingplants, warehouses and warehouse type retail outlets, all of which mayplace heavy demands on an electrical system.

The #F3 is a 1 1/2” x 3” duct and hasa cross sectional area of 3.94 sq.inches. Duct is supplied either blank(F3B) or with preset inserts.

The #F6 is a 1 1/2” x 6 1/2” duct andhas a cross sectional area of 8.75 sq.In. Duct is supplied either blank (F6B)or with preset inserts.

The #F8 is a 4” x 4” duct which hasa cross sectional area of 14.78 sq.In. Duct is supplied either blank(F8B) or with preset insert.

Length: 10 ft. Length: 10 ft.

The FBS underfloor duct system includes two different sizes of ducts that can be combined to match the cable capacity re-quired for your project; junction boxes, duct supports, duct couplings and several accessories complete the FBS underfloorsystem.

FBS ducts and related parts are manufactured of 16-gauge galvanized steel.Approved under spec C22-2 No 80 to both, Canadian & U.S. standards.

Ducts are supplied either blank ( no preset inserts ) for use with after set inserts or with preset inserts with variousheights ( up to 3” ) available to suit the concrete pour.

Combine with up to 3 F3 or F6 ducts

#F3 Duct #F6 Duct #F8 Duct

L: 10 ft.

UFD 1FBS Floor Box Systems - 1-800-216-8307

FBS UNDERFLO

OR DUCTS

C USNRTL

Page 2: FBS Underfloor ducts - FBS Floor Box Systems

F3-1-24

FBS Underfloor Ducts

Standard spacing for preset inserts is 24”OC. 12” OC insert spacing is also available.

Duct inserts are 2” pipe sized zinc die castings radiused internallyfor safe wire pulling.

The 1 inch (7/8” actual size) high preset inserts are the standard formost applications requiring 1” topping over the underfloor ductwhich is considered the minimum covering for the underfloor ductsystem. Higher insert heights are available in 1/2” increments up to2-7/8” ( 3” topping). See Table A, Page 4 for details.

F6B / F3B Blank duct - Use as aduct run or use with afterset inserts.

F6 / F3 duct - with Std. 1” high round preset24” OC

NOTE: Illustration for reference only. See Ordering information for a complete list of part numbers.

F6 / F3 duct - with Std. 1” high round preset12” OC

F6-1-24 F6B with afterset

F8 Blank duct (without presets) 10 ft high heavy duty power distributionsystem for industries

10’

FBS Floor Box Systems - 1-800-216-8307UFD 2

FBS UNDERFLOOR DUCTS

Page 3: FBS Underfloor ducts - FBS Floor Box Systems

FBS Underfloor duct system (Illustrative layout)

12

3

4

5 6

7

89

9

1011

1213

Underfloor duct System

Part Number Description1 F6-1-24 Std F6 duct - Preset 24” OC2 F3-1-24 Std F3 duct - Preset 24” OC3 36S Duct support - Std height4 Std 1” preset insert5 F640 Box plug for F6 duct6 F36JB Junction box for F3 & F67 F340/F640 Box plug for F3 & F6 ducts8 F636JB JB for “F6-F3-F6” ducts9 F315/F615 Coupling for F3 & F6 ducts

10 F330/F630 End blanks for F3 & F6 ducts11 Floor Box Recessed floor box12 F690FE 90 Deg. Flat elbow for F613 F690VE Vertical elbow for F6 duct14 F6B/F3B/F6B F6B-F3B-F6B Blank ducts15 F395 JB corner to 2” IPS conduits

15

14

Duct Wire Fill Capacity.

The National Electrical Code establishes that ducts cannotbe filled more than 40%. The chart shows the Max. Qty. ofcables (same type) allowed in each duct.

F3 duct cross sectional area: 3.94 Sq. In. (40% fill = 1.56 Sq. In.)F6 duct cross sectional area: 8.75 Sq. In. (40% fill = 3.5 Sq. In.)

Wire fill calculation (For different types of wires)

1 - Determine cross sec. area (Sq. In.) of all cables.(See Cable Manufacturer specs or calculate it)

Sq. Area = 0.79 x Diameter2

2 - Add square area of all cables.

The total of all square areas of cables added togethershould not be greater than F3 / F6 40% duct allowanceshown above.

How to choose the right duct size for your project?

Before selecting a duct, it is very important to determine the type and quanity of cables required for your project as well asthe duct wire fill allowance. Determined the 40% duct fill ratio, you can select the duct that best meet your project needsassuring compliance with the NEC.

FBS Underfloor Ducts

UFD 3FBS Floor Box Systems - 1-800-216-8307

FBS UNDERFLO

OR DUCTS

Page 4: FBS Underfloor ducts - FBS Floor Box Systems

Duct Preset Height (OC24)Type Height Width Min. topping 1.5”F3PC 1 1/2” 3 F3PC-24F6PC 1 1/2” 6 1/2” F6PC-24

Type Height Width Blank(*) Preset Insert height options (Inserts spacing 12” O.C.)F3 1 1/2” 3” B F3-1-12 F3-1.5-12 F3-2-12 F3-2.5-12 F3-3-12F6 1 1/2” 6 1/2” B F6-1-12 F6-1.5-12 F6-2-12 F6-2.5-12 F6-3-12F8 4” 4” B F8-1-12 F8-1.5-12 F8-2-12 F8-2.5-12 F8-3-12

Duct Preset Insert height options (Insert spacing 24” on centers)Type Height Width Blank 1” 1.5” 2” 2.5” 3”

F3 1 1/2” 3 B F3-1-24 F3-1.5-24 F3-2-24 F3-2.5-24 F3-3-24F6 1 1/2” 6 1/2” B F6-1-24 F6-1.5-24 F6-2-24 F6-2.5-24 F6-3-24F8 4” 4” B F8-1-24 F8-1.5-24 F8-2-24 F8-2.5-24 F8-3-24

See chart for duct type, insert height and spacing. Standard insert spacing is 24” O.C.

Insert heights shown indicate height of topping over duct. 1” H preset is the standard. Preset insert castings are approxi-mately 1/4” shorter than dimensions indicated to allow for covering of concrete.

Underfloor ducts - Ordering information

Part number: F___ - ___ - ___

Type of duct: 3 / 6(For Blank use 3B /6B)

Preset Insert HeightPreset distance on center

ie: F3-1-24 (F3 standard duct)F3-2-12 (F3 duct with 2” high preset inserts every 12“)

NOTE: The resulting Part # represent asingle piece of duct 10 ft long.

Select the part number from the table (above) or use the numeric system below.

Underfloor Duct - PRO-C SERIES

F6PC24 / F3PC24 duct - with rectangular presets 24” OCfor use with flush mounted devices & covers.

NOTE: Supplied with mud caps. Also available as aftersets.

F3PC24 Duct#

Preset inserts

Mtg. Strap

F6PC-24F3PC-24

The Pro-C duct series provide rectangular preset inserts which allow to install flush mounted activations.F3PC and F6PC require a minimum of 1.5 In. of concrete topping over the duct. Preset insert castings are approximately1/4” shorter than dimensions indicated to allow for covering of concrete.

See page ........for aftersets and device covers.

FBS Underfloor Ducts

FBS Floor Box Systems - 1-800-216-8307UFD 4

FBS UNDERFLOOR DUCTS

Page 5: FBS Underfloor ducts - FBS Floor Box Systems

Junction Boxes

Junction boxes are configured with up to four openings onall four sides in combinations to provide for a wide variety ofduct applications.

Multiple compartment junction boxes have interior partitionswhich keep the duct runs separated inside the box and pro-vide a continuous path through the box to the exiting ductruns.

Corner conduit feeds are also available upon request. See item F395.

Standard boxes are fabricated from galvanized steel with around 1/4” thick mild steel plate (6” cover plate is die cast).Junction boxes have adjustable cover plate assemblieswhich allow for 1/2” vertical adjustment upwards permittingaccurate leveling to the finished floor.

Heavy duty junction boxes are available for applicationswhen heavy loads will be placed or rolled over the duct sys-tems. These boxes are constructed with 3/8” thick cover-plates and the boxes are provided with adjustable supportstuds as required for the application. Please contact factoryfor further details.

Junction boxes are placed at duct intersections to provide:

1 - Access to the underfloor duct system in order to pull wires or make splices.2 - A method to separate duct runs as they cross each other at the intersection.3 - A means of connecting the duct system to conduit.

Levelingscrew

H: 1 11/16”

Extension ringStandard Height 1”

Coverplate

UFD 5FBS Floor Box Systems - 1-800-216-8307

Standard boxes are supplied with a 1” high adjusting ring tomatch the 7/8” high preset. Boxes for use with higher presetsrequire a junction box with a higher adjusting ring to suit thepreset height.

Junction boxes for Quarry tile applications.

These boxes are supplied with an aluminum ring and pan3/4 “ deep to accept the tile. Boxes to be used with quarrytile must be specified as such (suffix QT), as this assemblycan not be added later.

A series of stainless steel pans and rings are available toaccept a wide range of floor finishes.

Part # F6666JB

Part # F6JB

FBS Underfloor Ducts

FBS UNDERFLO

OR DUCTS

Page 6: FBS Underfloor ducts - FBS Floor Box Systems

F6JBF3333JB

Four F3 ducts per side.Cover plate diameter 17”

One F6 duct per side.No interior partitions.

Cover plate diameter 5-3/4”

Two F6 ducts per side.Cover plate diameter 11-1/4”

F33JB

F66JB

F333JB1 2

3 4 5

FBS Floor Box Systems - 1-800-216-8307UFD 6

Duct paths illustrations through the boxisolated compartments provide a visualreference that helps to determine theright duct layout for your project.

The following drawings provide an illustrative guidance and overall dimensions for the available duct configurations and theircorresponding junction boxes.

Need help?

Our Account Representativesand Product Specialists are avail-able by phone and email to assistyou through the project designand the installation process.

FBS Underfloor Ducts

Three F3 ducts per side.Cover plate diameter 11-1/4”

Two F3 ducts per side.Cover plate diameter 11-1/4”

FBS UNDERFLOOR DUCTS

Page 7: FBS Underfloor ducts - FBS Floor Box Systems

One F3 and one F6 duct perside.

Cover plate diameter 11-1/4”

Four F6 ducts per side.Cover plate diameter 2 covers

11-1/4”

F6666JB

Three F6 ducts per side.Cover plate diameter 17”

F666JB F36JB

F336JB F3336JBF363JB

6 7 8

9 10 11

Two F3 and one F6 duct perside.

Cover plate diameter 17”

Two F3 and one F6 duct perside.

Cover plate diameter 17”

FBS Underfloor Ducts

Three F3 and one F6 ducts.Cover plate diameter 2 covers

11-1/4”

UFD 7FBS Floor Box Systems - 1-800-216-8307

FBS UNDERFLO

OR DUCTS

Page 8: FBS Underfloor ducts - FBS Floor Box Systems

Two F6 and two F3 ductsCover plate diameter: 2 Covers

11-1/4”

F636JB F6633JB

F8JB F88JB F888JB

F366JB

Two F6 and one F3 ductCover plate diameter 17”

12 13 14

15 16 17

One F3 and Two F6 ducts.Cover plate diameter 17”

FBS Underfloor Ducts

One F8 duct per side.No interior partition.

Cover plate diameter 5-3/4”

Two F8 ducts per side.Cover plate diameter 11-1/4”

Three F8 ducts per side.Cover plate diameter 17”

FBS Floor Box Systems - 1-800-216-8307UFD 8

FBS UNDERFLOOR DUCTS

Page 9: FBS Underfloor ducts - FBS Floor Box Systems

Junction BoxesFIG#

Junction Box Part #

Duct OpeningConfiguration

Compart-ments

Overall DIM. (In.)

Cover plateDia. (In.)

Carpet/Tile holderPart #

1 F33JB F33 2 15.75 11 F11FP-*2 F333JB F333 3 20.125 11 F11FP-*3 F3333JB F3333 4 24.5 17 F17FP-*4 F6JB F6 1 14.875 6 F6FP-*5 F66JB F66 2 22.75 11 F11FP-*6 F666JB F666 3 30.625 17 F17FP-*7 F6666JB F6666 4 38.5 11” x 2 F11FPx2-*8 F36JB F36 2 19.25 11 F11FP-*9 F336JB F336 3 23.625 17 F17FP-*

10 F363JB F363 3 23.625 17 F17FP-*11 F3336JB F3336 4 28 11” x 2 F11FPx2-*12 F366JB F366 3 27.125 17 F17FP-*13 F636JB F636 3 27.125 17 F17FP-*14 F6633JB F6633 4 31.25 11” x 2 F11FPx2-*15 F8JB F8 1 12.38 6 F6FP-*16 F88JB F88 2 17.75 11 F11FP-*17 F888JB F888 3 23.13 17 F17FP-*

To specify higher than standard box adjusting ring height to matchduct insert heights greater than 1”, add one of the following suffixesto the junction box number:

Junction box adjusting rings

Quarry tile applications – Add “QT” as a suffix to the junction box part number.

Suffix-1.5 for 1-1/2” high preset inserts-2 for 2” high preset insert-2.5 for 2-1/2” high preset insert-3 for 3” high preset insert

(Chart A)

Junction boxes - Ordering information

Based on the duct configuration previously selected, find the corresponding junction box from the following chart:

All part numbers specified in the Chart A (above) are based on a preset insert height of 1”.

Junction boxes are available for Quarry tile applications. Theses boxes are supplied with an aluminum ring and pan 3/4 “deep to accept the tile. Boxes to be used with quarry tile must be specified as such as this assembly can not be addedlater.

JB Part number: F___ JB - ___ ___

Duct opening configuration: Suffix preset Height

(If higher than 1” only)ie: F333JB (Three 3” W ducts with 1” H standard preset.)

F333JB-2 (Three 3” W ducts with 2” High preset.)

QT (If applicable)

(*) See Tile/carpet hold-ers details in next page.

FBS Underfloor Ducts

UFD 9FBS Floor Box Systems - 1-800-216-8307

FBS UNDERFLO

OR DUCTS

Page 10: FBS Underfloor ducts - FBS Floor Box Systems

We manufacture several stainless pans and rings which fit the round junction box cover plate to accept a wide variety of floorcoverings. The “pan” style accessories are available in single lip, used for tile and carpet and double lip used for carpet (providesprotection against fraying on both cut edges. 1/8” deep pans normally supplied for carpet. 1/4” deep are normally supplied fortile.

Also available is a carpet ring which installs over the cut joint in the carpet and stands up better against loads which can deformthe “lip” of conventional carpet pans.

Tile / Carpet holder (Pans)- Ordering information

Based on the junction box (duct configuration) selected, find thecorresponding holder number below and add the req’d suffix.

Junction Box Part #

Cover plateDia. (In.)

Carpet/Tile holderPart #

F33JB 11 F11FP-*F333JB 11 F11FP-*

F3333JB 17 F17FP-*F6JB 6 F6FP-*

F66JB 11 F11FP-*F666JB 17 F17FP-*

F6666JB 11” x 2 units F11FPx2-*F36JB 11 F11FP-*

F336JB 17 F17FP-*F363JB 17 F17FP-*

F3336JB 11” x 2 units F11FPx2-*F366JB 17 F17FP-*F636JB 17 F17FP-*

F6633JB 11” x 2 units F11FPx2-*F8JB 6 F6FP-*

F88JB 11 F11FP-*F888JB 17 F17FP-*

Available for QT box only

Suffix Holder heightSL4 Single lip 1/4” deep panSL8 Single lip 1/8” deep panDL4 Double lip 1/4” deep panQT Quarry tile /terrazzo 3/4” deep pan

Holder/pan Part number: F ___FP ___ - ___

Cover platediameter:

Suffix: SL4 / SL8 DL4 / QT

ie: F11FPX2DL4 (Two units of 11” Dia.cover with 1/4” deep pan and doublelip for carpet - Use with F3336JB junc-tion box)

- If 2 units req’d only- Leave blank If 1 unit is req’d

X2ie: F17FPQT (17” Dia. cover with 3/4”deep pan and aluminum ring for tile -Use with F336JB junction box)

Tile / Carpet holder (Pans)

Flanged round carpet/tile pans mount onto cover plate and provide a recessed space in the box surface that permit to installa carpet insert, tile or any floor covering material of your choice.

Heavy duty junction boxes are available for applications when heavy loads will be placed or rolled over the duct systems.These boxes are constructed with 3/8” thick coverplates and the boxes are provided with adjustable support studs as re-quired for the application. Please contact factory for further details.

FBS Underfloor Ducts

Single lip carpet/tilepan – 1/8” or 1/4”

deep pan

Double lip carpetpans – available 1/4”

deep

QT - Tile / terrazzoAlum. ring & 3/4” deep

pan

FBS Floor Box Systems - 1-800-216-8307UFD 10

FBS UNDERFLOOR DUCTS

Page 11: FBS Underfloor ducts - FBS Floor Box Systems

Duct supports are supplied to hold ducts in place before and during the concrete pour. Supports are manufactured fromgalvanized steel for maximum corrosion resistance and are available in configurations to match all combinations of ductruns as specified in the junction box listings.

F333S-A

DUCT SUPPORT SUFFIX

Suffix Height of Support

Floor depth

A 2 1/4” 2 1/2” - 3 5/8”B 2 3/4” 3”- 4 1/4”C 4 1/4” 4 1/2” - 5 3/4”D 5 3/4” 6”- 7 1/4”E 7 1/4” 7 1/2” - 8 3/4”

A variety of leg heights are available to provide for pours of up to 8-3/4”. Each support is also adjustable by means of aleveling screw on each leg to provide adjustment within a range of 1-1/2”.

Duct support - Ordering information

The Chart C specifies suffix for the support height and values specifiedare based on a preset insert height of 1” (1” topping).For supports used with concrete topping greater than 1”, subtract the height inexcess of 1” from the floor depth column on the chart C.

DUCT SUPPORT

Duct Support Part #

Duct SupportWidth (DSW)

Duct Config.

F33S-** 12 F33F333S-** 16 5/16 F333F3333S-** 20 5/8 F3333F6S-** 11 1/4 F6F66S-** 19 F66F666S-** 26 13/16 F666F6666S-** 34 5/8 F6666F36S-** 15 1/2 F36F336S-** 19 13/16 F336F363S-** 19 13/16 F363F3336S-** 24 1/8 F3336F366S-** 23 5/16 F366F636S-** 23 5/16 F636F6633S-** 27 5/8 F6633F8S-** F8F88S-** F88F888S-** F888

Std. PresetHeight 1” (7/8”)

1 1/2”2 1/4”

(**) Add suffix support heightChart C

NOTE: Supports are to be located at 5’ intervals.

JB Extension ring

F333JB (junction box) F3-1-24 Duct F333S-A support

1 5/8”

1” 7/8”

Concrete 2 5/8”

Std. Preset Height2.5” (2 3/8”)

1 1/2”2 3/4”

JB Extension ringH=2.5”

F333JB-2.5 (junction box) F3-2.5-24 Duct

F333S-B support

1 5/8”

2 1/2” 2 3/8”

Concrete 5”

Based on the duct configuration selected, find the corresponding support #below and add the required suffix from Chart C.

Ie: Duct configuration F333-1-24 (3 duct runs with 1” high preset.) Duct supportnumber is F333S. See table C for suffix. Suffix A corresponds to 2 5/8” concrete depth and 1” std. preset.

Floor depth is 5”. Locate 5” floor depth in Chart C. If concrete topping is greaterthan 1, subtract the exceeding amount. (Preset 2.5”H -1=1.5”.) Subtract 1.5 from“floor depth” 5”. Suffix B corresponds to 3.5” in “floor depth” column. (F333S-B)

FBS Underfloor Ducts

F333S Saddle Support for three #3underfloor ducts

Duct supports

UFD 11FBS Floor Box Systems - 1-800-216-8307

FBS UNDERFLO

OR DUCTS

Page 12: FBS Underfloor ducts - FBS Floor Box Systems

Box plugs

ORDERING INFORMATIONPart Number Ducts

FAS36 ALL

ORDERING INFORMATIONPart Number Ducts

F300 ALL

FBS Underfloor Ducts

Duct accessories

Ordering InformationPart # Ducts

F390FE F3F690FE F6F890FE F8

Ordering InformationPart # Ducts

F390VE F3F690VE F6F890VE F8

90o Vertical Elbow 90o Horizontal Flat Elbow

Ordering InformationPart # Ducts

F345FE F3 F645FE F6 F845FE F8

45o Horizontal Elbow

Ordering InformationPart # DescriptionF641 F6 to F3

F641 Reduces F6 boxopening to F3 duct

Ordering InformationPart # DescriptionF340 F3 F640 F6 F840 F8

JB Reducing plug

Ordering InformationPart # Description

F390RE F3 F690RE F6 F890RE F8

90o V. Elbow 3” R

FBS Floor Box Systems - 1-800-216-8307UFD 12

F300 - Afterset insert 2” IPSAfterset inserts 2” IPS 1” high two piece assemblies toprovide an outlet in blank duct, can be installed afterpour (3” hole required in concrete 2-1/2” hole in duct) orinstalled pre-pour when only a few outlets are requiredand location is known prior to pour (if ordering for pre-pour installation order #304 mud cap as well).

FAS36 - Afterset insert for flush coversAfterset inserts 1.25” high provide access to flush installeddevices in blank ducts. Can be installed after pour or in-stalled pre-pour when only a few outlets are required andlocation is known prior to pour. 4.75X4X1.25 H requires amin 1.5” topping. Insert heights are available in 1.25” in-crements. Ask factory for details.

FBS UNDERFLOOR DUCTS

Page 13: FBS Underfloor ducts - FBS Floor Box Systems

Ordering InformationPart # DuctsF315 F3F615 F6F815 F8

Ordering InformationPart # Description

F660 F3 duct to F6 duct

Ordering InformationPart # DuctsF320 F3F620 F6F820 F8

Ordering InformationPart # DescriptionF354 F3 box to double 2” con.F654 F6 box to double 2” con.F854 F8 box to double 2” con.

Ordering InformationPart # DescriptionF364 F3 box opening to 2” cond.F664 F6 box opening to 2” cond.F864 F8 box opening to 2” cond.

Junction Box to Conduit JB opening to Double Conduit

Ordering InformationPart # DescriptionF372 F3 duct to 2” conduitF672 F6 duct to 2” conduitF872 F8 duct to 2” conduit

Duct to Conduit

Ordering InformationPart # DescriptionF355 F3 duct to double 2” cond.F655 F6 duct to double 2” cond.F855 F8 duct to double 2” cond.

Duct to Double Conduit

FBS Underfloor Ducts

Coupler Duct reducer

Ordering InformationPart # Description

F395 Junction Box Corner to 2” IPS

JB Corner Conduit Adapter

Ordering InformationPart # DescriptionF330 F3 F630 F6 F830 F8

End Blanks

Expansion Joint

UFD 13FBS Floor Box Systems - 1-800-216-8307

FBS UNDERFLO

OR DUCTS

Page 14: FBS Underfloor ducts - FBS Floor Box Systems

Ordering InformationPart # DescriptionF270 Extension 2” IPS 1/2” high.F272 Extension 2” IPS 1” high.Note Ext. for 2” preset/afterset

Ordering InformationPart # DescriptionF305 Brass Marker (Slotted)F306 Stainless Steel (Slotted)F307 Stainless steel (Philips)

Ordering InformationPart # DuctsF380 F3F680 F6F880 F8

Ordering InformationPart # Ducts

F304Mudcap fits all 2” IPS preset/af-terset inserts. Recessed to hold3/8” concrete. Supplied w/ducts

Ordering InformationPart # DuctsF325 F3F625 F6F825 F8

FBS Underfloor Ducts

Cabinet Connector Mudcap

Marker cap Duct extensionBlanking plate

Ordering Information

Part # Ducts

F280

Sealing compound forjoints and/or ducts at junc-

tion box opening. (1 G/1000ft F3 duct)

Sealing compound

Ordering InformationPart # DescriptionF260 2” to 1 1/2”F261 2” to 1 1/4”F262 2” to 1”F263 2” to 3/4”F264 2” to 1/2”

Conduit reducer

Offset 1 1/2 In.

NOTE: Marker cap replaces mudcap oninserts to indicate location of duct run.

NOTE: Blanking plate fits 2” IPS pre-set/afterset inserts.

Ordering InformationPart # Description

F310 Stainless Steel plate

F311 Brass plate

FBS Floor Box Systems - 1-800-216-8307UFD 14

FBS UNDERFLOOR DUCTS

Page 15: FBS Underfloor ducts - FBS Floor Box Systems

R

FBS Underfloor Ducts

“F500” series is a die cast service fitting designed to be “flush mounted” in a duct insert. It comes complete with anabandon plug and accepts a standard short strap single receptacle. The fitting is available in a standard brushed aluminumfinish or can be ordered in chrome or brass finish.

F500 Series Service Fittings

Abandon plugF500 Flush fitting abandonplug available in standardbrush aluminum, chrome orbrass. Includes fitting and plug.

2 1/2” OD2 3/8” ID3 1/2” High

F525 Drive plug conduit adapter

15A ReceptacleF515 - F500 Flush fitting w/15A receptacle.

Bell housing F500BC Bell housing. FitsF500 fittings. Protects plug and cables.

PlugF500C Abandon plug only.Fits F500 fitting. Available inBrass, aluminum and Chromefinish.

RingF500RT Retainer ring for usewith receptacle F505. FitsF500 fittings. Sold separately.

F505 15A Receptacle F505 15A Receptacle only.Fits F500 fittings. Sold sepa-rately. Receptacle requires re-tainer ring F500RT

F505

F500RT

F500C Plug

F500 Fitting

F525 Conduit adapter

F520 Drive Plug

Drive plug

Power outlet

F500 Series Service fittings - Ordering information

Part # Description F500 Brass flush fitting w/ abandon plugF515 Brass flush finish w/15A receptacle

F500BC Bell Housing for comm fit F500 F500C Abandon plug only - fit F500 F505 15A Receptacle

F500RT Retainer ring for use w/F505F520 Drive plug 3 1/2” H

Suffix Description Suffix Description-AL Brush aluminum SS Chrome finish-AL Brush aluminum SS Chrome finish-AL Brush aluminum SS Chrome finish-AL Brush aluminum SS Chrome finish

F500 Assembly exploded view

UFD 15FBS Floor Box Systems - 1-800-216-8307

FBS UNDERFLO

OR DUCTS

Page 16: FBS Underfloor ducts - FBS Floor Box Systems

F200 Series service fittings- Ordering information

FBS Underfloor Ducts

F200 Series Service Fittings The F200 Series service fittings provide access to power and communication services on the preset designated loca-tions and consist of a die cast chromed and polished housing with stainless steel faceplates to fit a wide variety of power,data and communication devices.

15A Duplex receptacle

15A SSR 1.04” Dia.

Decorator style

Blank

Two Keystonestyle openings

Keystone styleopening

1/4” Dia.w/Bushing

1” Dia. Comm platew/bushing

The F200 series service fittings are approved for installation on the F3, F6 and F8 underfloor ducts and NRTL Listed for USand Canada.

For plates not listed above or special/custom plates please contact us.

For cross reference numbers please consult the “Cross References” catalog section.

ORDERING INFORMATIONPart # Description

F200STD F200 housing w/standard duplex receptacle plate and blank plate F200DUP Duplex receptacle plate only.F200DEP Decorator style plate only.F200BLP Blank plate only.F240COM F200 housing w/1” Dia. bushing plate (Housing and plate)F240TPS Communication plate w/ small bushing (plate only)F240TPL Communication plate w/1” Dia bushing (plate only)F2401RJ One keystone style opening (plate only)F2402RJ Two keystone style openings (plate only)F201FIT F200 fitting housing only

F261 Adapter 2” to 1 1/4”F265 1 1/4” nipple

FBS Floor Box Systems - 1-800-216-8307UFD 16

FBS UNDERFLOOR DUCTS

Page 17: FBS Underfloor ducts - FBS Floor Box Systems

FBS Underfloor Ducts

F900 Series Service Fittings FBS “F900” series service fittings consist of an aluminum die cast housing with a brushed satin finish and aluminumfaceplates.

F900 Series service fittings- Ordering information

The F900 series service fittings are approved for installation on the F3, F6 and F8 underfloor ducts, NRTL Listed for USand Canada.

For cross reference numbers please consult the “Cross References” catalog section.

ORDERING INFORMATIONPart # Description

F903NR F900 housing w/standard duplex receptacle plate and blank plate F903P2 Duplex receptacle plate only.F903PB Blank plate only.

F904 F900 housing w/1” Dia. bushing plate (Housing and plate) and blank plateF900N1 1” IPS nipple 1/ 3/4 long

262 2” to 1” reducer

PF10266 and PF10222 Series

UFD 17FBS Floor Box Systems - 1-800-216-8307

Part # F903PB

Part # F903P2

Part # F904 Includeshousing and plate

The PF service fittings provide a versatile solution toaccess power and low voltage connectors. Compatible with 2” round presets.

Please see the “Surface mount boxes” section forcomplete product details and ordering information.

FBS UNDERFLO

OR DUCTS

Page 18: FBS Underfloor ducts - FBS Floor Box Systems

FBS Underfloor Ducts

Flush Activations for F3PC/F6PC Ducts

FBS Floor Box Systems - 1-800-216-8307UFD 18

F3PC24 Duct#

Preset inserts

Mtg. Strap

Flush activations for single, double and triple-duct runs forboth tiled and carpeted floors.

Ordering Information Part #: FAF1One gang brasscarpet and tileflange

Part #: FAF2Two gang brasscarpet and tileflange

Part #: FAF3Three gangbrass carpet andtile flange

Carpet / Tile Flange

Ordering Information Part #: FAF1TOne gang brasstile flange

Part #: FAF2TTwo gang brasstile flange

Part #: FAF3TThree gangbrass tile flange

Tile Flange

Ordering Information Part #: F970-1/2Brass Communi-cation Cover Plate.Supplied with one2 5/8" and one 1/2"Screw Plug

Part #: F970-3/4Brass Communi-cation Cover Plate Supplied with one2 5/8" and one 3/4"Screw Plug

Cover plates

FBS UNDERFLOOR DUCTS

Page 19: FBS Underfloor ducts - FBS Floor Box Systems

FBS Underfloor Ducts

UFD 19FBS Floor Box Systems - 1-800-216-8307

Ordering Information Part #: F970-1Brass Communi-cation Cover PlateSupplied with one2 5/8" and one 1"Screw Plug

Part #: 970-2-1/4One gang brasstile flange Commu-nication CoverPlate -Supplied with one2 5/8" and one 21/4" Screw Plug

2-5/8" Diameter

2-1/4" Diameter

Ordering Information Part #: F970-PPBrass DuplexCover Plate.Supplied with two1 1/2" Screw Plugs

Part #: 971-TCBrass Communi-cation Cover Plate Supplied with DataSlides for FeedThrough CableEntry

Ordering Information Part #: F970-DPBrass DuplexCover Plate - FlipLids

Part #: 970-GFIBrass GFI (Dec-ora) Cover Plate

FBS UNDERFLO

OR DUCTS


Recommended